Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:49
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2020-06-03 19:49:28
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 9514.24 | 838.61 | 838.61 |
Net Site Energy | 9514.24 | 838.61 | 838.61 |
Total Source Energy | 21262.98 | 1874.17 | 1874.17 |
Net Source Energy | 21262.98 | 1874.17 | 1874.17 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 345.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 960.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 526.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 182.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.47 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 971.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 667.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 107.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.56 | 2123.02 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 48.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5256.62 | 4257.62 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 345.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 960.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 526.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 182.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 667.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 52.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 107.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.56 | 2123.02 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 18.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 23.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 62.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 156.15 | 217.60 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 244.70 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 463.33 | 375.28 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 62.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 156.15 | 217.60 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 244.70 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 463.33 | 375.28 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5256.620 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5256.620 | 100.00 |
Total On-Site and Utility Electric Sources | 5256.620 | 100.00 |
Total Electricity End Uses | 5256.620 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 235.64 | 7.77 |
Air to Air Heat Recovery for Heating | 2796.35 | 92.23 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3031.99 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 25.17 |
Time Setpoint Not Met During Occupied Cooling | 8756.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8760.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:49 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.8889 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 9.0417 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.0417 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.0903 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 6.4583 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 5.4896 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 6.4583 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 6.4583 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 4.4132 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 5.3388 | 7.60 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 5.3388 | 7.60 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-AUG-19:19 | 06-FEB-17:10 | - | - | - | 27-MAR-20:00 |
Heating | 0.00 | 117127.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 161238.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 47387.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86131.51 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 50267.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28113.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3414.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4880.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4083.07 | 170946.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1913.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 399062.12 | 377686.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 117127.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 161238.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 47387.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1228.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28113.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3414.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 4880.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 4083.07 | 170946.55 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 937.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 734.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 374.79 | 0.00 | 0.00 | 0.00 |
Cooling | 3042.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1666.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 578.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.69 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3078.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2115.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 166.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 339.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 286.79 | 2301.36 | 0.00 | 0.00 | 0.00 |
Refrigeration | 154.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 16647.72 | 4615.26 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 33.03 | 0.00 | 0.00 | 0.00 |
Cooling | 268.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 146.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 186.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 14.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 29.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.28 | 202.85 | 0.00 | 0.00 | 0.00 |
Refrigeration | 13.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1467.37 | 406.80 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 33.03 | 0.00 | 0.00 | 0.00 |
Cooling | 268.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 146.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 186.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 14.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 29.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.28 | 202.85 | 0.00 | 0.00 | 0.00 |
Refrigeration | 13.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1467.37 | 406.80 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.20 | 0.685698 | 0.583000 | 1.28 | 1.00 | 0.500000 | 0.000556 | 0.000149 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.284123 | 0.179881 | 0.418000 | 0.118763 | 0.498292 | 0.500000 | 0.002118 | 0.000084 | 0.132375 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.206836 | 0.286139 | 0.665000 | 0.137546 | 0.763036 | 0.500000 | 0.001332 | 0.000035 | 0.137546 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.217554 | 0.575274 | 0.010000 | 0.002176 | 1.00 | 0.500000 | 0.000662 | 0.000042 | 0.066726 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.087839 | 0.822031 | 0.986000 | 0.086610 | 1.00 | 0.500000 | 0.000463 | 0.000034 | 0.086610 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.25 | 0.018278 | 0.010000 | 0.032534 | 0.300000 | 0.500000 | 0.020845 | 0.000056 | 0.089309 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.22 | 0.117733 | 0.830000 | 1.01 | 0.830000 | 0.500000 | 0.003236 | 0.000294 | 1.01 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.07 | 0.244800 | 0.697000 | 2.84 | 0.697000 | 0.500000 | 0.001556 | 0.000707 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.600000 | 0.712143 | 1.00 | 0.500000 | 0.000381 | 0.000276 | 0.712143 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.00 | 0.126070 | 0.888000 | 1.78 | 0.888000 | 0.500000 | 0.003022 | 0.000332 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.11 | 0.119905 | 0.845000 | 1.78 | 0.845000 | 0.500000 | 0.003178 | 0.000334 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.15 | 0.700000 | 0.256000 | 0.551544 | 0.300000 | 0.500000 | 0.010428 | 0.000115 | 0.551544 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.520319 | 0.603550 | 0.362000 | 0.188356 | 1.00 | 0.500000 | 0.000631 | 0.000160 | 0.253778 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 6765.89 | 0.000149 | 119.73 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3784.46 | 0.000084 | 82.03 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1600.16 | 0.000035 | 30.38 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1907.62 | 0.000042 | 41.35 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1552.86 | 0.000034 | 30.96 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 2553.24 | 0.000056 | 55.34 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 13294.51 | 0.000294 | 256.77 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 31987.11 | 0.000707 | 604.73 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 5776.26 | 0.000128 | 131.51 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 5792.64 | 0.000128 | 131.88 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 32805.91 | 0.000725 | 746.90 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 33126.35 | 0.000732 | 754.19 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 5745.94 | 0.000127 | 130.82 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 5762.27 | 0.000127 | 131.19 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12483.36 | 0.000276 | 248.22 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 1749.09 | 0.000039 | 39.82 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 1757.68 | 0.000039 | 40.02 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 8349.27 | 0.000184 | 190.08 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 15014.61 | 0.000332 | 274.94 |
DINING_FLR_6 VAV BOX REHEAT COIL | 15137.29 | 0.000334 | 277.38 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5215.08 | 0.000115 | 96.59 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7256.42 | 0.000160 | 157.29 |
VAV WITH REHEAT_HEATC | 188205.56 | 0.004158 | 2641.15 |
FLR_3_DOAS_HEATC | 20392.24 | 0.000451 | 286.17 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.963785 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 0.948040 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 4.88 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 5.28 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 0.862883 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 0.857003 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.253962 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.249787 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.02 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.963785 | 0.000128 | 0.000317 |
ROOM_2_FLR_3 FAN COIL | 0.948040 | 0.000128 | 0.000312 |
ROOM_3_MULT19_FLR_3 FAN COIL | 4.88 | 0.000725 | 0.001578 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.28 | 0.000732 | 0.001823 |
ROOM_5_FLR_3 FAN COIL | 0.862883 | 0.000127 | 0.000286 |
ROOM_6_FLR_3 FAN COIL | 0.857003 | 0.000127 | 0.000284 |
ROOM_1_FLR_6 FAN COIL | 0.253962 | 0.000039 | 0.000083 |
ROOM_2_FLR_6 FAN COIL | 0.249787 | 0.000039 | 0.000082 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.02 | 0.000184 | 0.000343 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 0.963785 |
ROOM_2_FLR_3 FAN COILFAN | 0.948040 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 4.88 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 5.28 |
ROOM_5_FLR_3 FAN COILFAN | 0.862883 |
ROOM_6_FLR_3 FAN COILFAN | 0.857003 |
ROOM_1_FLR_6 FAN COILFAN | 0.253962 |
ROOM_2_FLR_6 FAN COILFAN | 0.249787 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.02 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000317 | 0.963785 | 0.008696 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000312 | 0.948040 | 0.008699 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.001578 | 4.88 | 0.008627 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.001823 | 5.28 | 0.008879 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000286 | 0.862883 | 0.008720 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000284 | 0.857003 | 0.008722 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000083 | 0.253962 | 0.008686 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000082 | 0.249787 | 0.008690 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000343 | 1.02 | 0.008792 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.016986 | 0.011907 | 27.98 | 6.70 | 10.98 | 0.008281 | 593909.90 | 18.93 | |
FLR_3_DOAS_COOLC | 0.002460 | 0.014097 | 32.03 | 6.70 | 10.99 | 0.008281 | 86019.67 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.85 | 10.53 | 19.52 | 10.53 | 18.93 | 18.93 | 0.300000 | 0.555995 | 18.93 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 18.93 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT HEAT RECOVERY | 9.33 |
FLR_3_DOAS HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 18.93 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.016986 | 0.000028 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.004158 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002460 | 0.000194 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000451 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.024556 | 4650.76 |
HEATSYS1 PUMP | 0.009456 | 2392.09 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.009456 | 1.13 |
COOLSYS1 | 0.024556 | 2.95 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.024556 | 1550.25 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 428015.82 | 428015.82 | 0.009456 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.024556 | 858607.51 | 858982.81 | 97.92 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.889 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.269 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.042 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.802 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.042 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.802 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 10.226 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.606 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 4.090 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.780 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 6.458 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.838 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 5.490 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.560 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 6.458 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 74.278 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 6.458 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 74.278 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 13631.969 | 6.889 | 128.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13631.969 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 606.438 | 9.042 | 56.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 606.438 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 702.258 | 9.042 | 56.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 702.258 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 1679.504 | 10.226 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1679.504 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 387.593 | 4.090 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 387.593 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1219.735 | 6.458 | 8.572 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1219.735 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 7181.411 | 5.490 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7181.411 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 1718.522 | 4.413 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.522 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2141.959 | 6.458 | 8.571 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2141.959 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2141.959 | 6.458 | 8.571 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2141.959 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.036 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.036 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 1818.790 | 4.413 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.790 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.6478 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.376 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.49119318E-15 | -0.33550344E-15 | -0.16284357E-09 | -0.12303907E-16 |
25 | 8 | 0.23714982E-07 | 0.88106564E-13 | 0.39686193E-03 | -0.26964751E-09 |
26 | 7 | -0.12809687E-01 | 0.44996568E-08 | -0.23903550E-01 | 0.14565082E-03 |
27 | 6 | 0.42078637 | 0.15559313E-05 | 0.48521577 | -0.49297162E-02 |
28 | 5 | -5.3411857 | 0.57794581E-04 | -4.5419698 | 0.65051509E-01 |
29 | 4 | 33.669005 | 0.47055528E-03 | 21.833772 | -0.43096765 |
30 | 3 | -112.64328 | 0.10212385E-02 | -56.401742 | 1.5356680 |
31 | 2 | 198.53538 | 0.57229644E-03 | 78.588493 | -2.9230166 |
32 | 1 | -171.68312 | 0.60883279E-04 | -55.462911 | 2.7546764 |
33 | 0 | 57.057407 | 0.34515708E-06 | 15.524833 | |
34 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
35 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
36 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
37 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
38 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
39 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
40 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
41 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
42 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
43 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
44 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
45 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
46 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
47 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
48 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
49 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
59 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
60 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
61 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
62 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
63 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
64 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
65 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
66 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
67 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
68 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
69 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
70 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
71 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
72 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
73 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
74 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
75 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
76 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
77 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
78 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
79 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
80 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
81 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
82 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
83 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
84 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
85 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
86 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
87 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
88 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
89 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_0.36 | 31 | 1 | VerySmooth | 2.045 | 0.355 | 0.274 | 0.397 |
2 | RESWINDOW_U_0.37_SHGC_0.36 | 32 | 1 | VerySmooth | 2.102 | 0.355 | 0.274 | 0.397 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.27318 | 0.51999 | 0.51999 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.55893E-002 | 0.27318 | 0.51890 | 0.51890 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11739 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 30251.28278 | 30251.28278 | 2.19903 | 2.19903 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 28.80700 | 1.40969E-002 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85413 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 3907.79458 | 3907.79458 | 0.28412 | 0.28412 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.40969E-002 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3087.32962 | 3087.32962 | 0.13238 | 0.13238 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2844.99237 | 2844.99237 | 0.20684 | 0.20684 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36000 | 1.40969E-002 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 875.25708 | 875.25708 | 3.75328E-002 | 9.16993E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2993.13857 | 2993.13857 | 0.21755 | 0.21755 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36000 | 1.40969E-002 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1556.04617 | 1556.04617 | 6.67262E-002 | 6.67262E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1208.49782 | 1208.49782 | 8.78393E-002 | 8.78393E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 32.02600 | 1.40969E-002 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1096.52922 | 1096.52922 | 4.70210E-002 | 5.77430E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44754.00143 | 44754.00143 | 3.25339 | 3.25339 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.40969E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2082.78660 | 2082.78660 | 8.93091E-002 | 8.93091E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 16798.64305 | 16798.64305 | 1.22236 | 1.22236 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.40969E-002 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 7951.12998 | 7951.12998 | 0.34092 | 0.67613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 55994.44312 | 55994.44312 | 4.07206 | 4.07206 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.97667 | 1.40969E-002 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 17033.41952 | 17033.41952 | 0.73042 | 1.89326 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9838.66784 | 9838.66784 | 0.96378 | 0.96378 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 5776.44142 | 5776.44142 | 0.24915 | 0.24915 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9677.92950 | 9677.92950 | 0.94804 | 0.94804 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 5792.82549 | 5792.82549 | 0.24986 | 0.24986 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 49848.24332 | 49848.24332 | 4.88268 | 4.88268 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.97667 | 1.40969E-002 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 32806.35985 | 32806.35985 | 1.41505 | 1.41505 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 53927.95260 | 53927.95260 | 5.28270 | 5.28270 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 32.10000 | 1.40969E-002 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 33126.79855 | 33126.79855 | 1.42887 | 1.42887 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8808.59760 | 8808.59760 | 0.86288 | 0.86288 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.40969E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 5746.12226 | 5746.12226 | 0.24784 | 0.24784 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8748.57911 | 8748.57911 | 0.85700 | 0.85700 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.40969E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 5762.45442 | 5762.45442 | 0.24855 | 0.24855 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 9662.35518 | 9662.35518 | 0.70229 | 1.18691 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 31.80400 | 1.40969E-002 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 8728.56208 | 8728.56208 | 0.37430 | 0.47458 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2592.54034 | 2592.54034 | 0.25396 | 0.25396 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.40969E-002 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1749.14633 | 1749.14633 | 7.54443E-002 | 7.54443E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2549.91746 | 2549.91746 | 0.24979 | 0.24979 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1757.73603 | 1757.73603 | 7.58148E-002 | 7.58148E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10383.76264 | 10383.76264 | 1.01720 | 1.01720 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.97667 | 1.40969E-002 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8349.47802 | 8349.47802 | 0.36014 | 0.36014 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 27542.81095 | 27542.81095 | 2.00462 | 2.00462 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.40969E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5627.75215 | 5627.75215 | 0.24133 | 1.18734 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 28959.30639 | 28959.30639 | 2.10768 | 2.10768 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.40969E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 5745.62400 | 5745.62400 | 0.24638 | 1.18734 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29560.93077 | 29560.93077 | 2.15447 | 2.15447 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.43400 | 1.40969E-002 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2313.81979 | 2313.81979 | 9.92079E-002 | 0.36721 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -10.70000 | 1.50390E-003 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 7158.69552 | 7158.69552 | 0.52032 | 0.52032 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.40969E-002 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 5918.00346 | 5918.00346 | 0.25378 | 0.25378 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -10.70000 | 1.50390E-003 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 347654.47 | 18.93108 | 18.93108 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 242960.52 | 7.33162 | 7.33162 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 47696.01 | 14.63235 | 2.05120 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 67974.13 | 4.35065 | 2.05120 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.19903 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68570 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28203 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.55638E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49484E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28203 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6765.89312 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49484E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 119.72570 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28412 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17988 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.41800 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11876 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49829 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11807E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.36131E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13238 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3784.46353 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.36131E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 82.02648 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.20684 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28614 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.66500 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13755 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76304 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33152E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.53536E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13755 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1600.15930 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.53536E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 30.37865 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21755 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.57527 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.17554E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.62293E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.21464E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.67262E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1907.61589 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.21464E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 41.34662 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.78393E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.82203 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.98600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.66095E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.63486E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.43086E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.66095E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1552.86108 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.43086E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 30.96041 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.25339 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.82782E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.25339E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08445E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.64107E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.93091E-002 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2553.23906 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.64107E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 55.34022 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.22236 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11773 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.83000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01456 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.23613E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.93726E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01456 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13294.50728 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.93726E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 256.77008 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.07206 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24480 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.69700 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.83822 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69700 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55637E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.06716E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.83822 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31987.11469 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.06716E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 604.72589 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96378 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.96378 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.96378 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.27619E-004 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.17334E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.17334E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.96378 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.69650E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68263 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5776.25577 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27619E-004 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 131.50987 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94804 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94804 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.94804 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.27981E-004 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.12395E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.12395E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.94804 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.69946E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68262 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5792.63927 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27981E-004 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 131.88280 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.88268 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.88268 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 4.88268 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.24807E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.57808E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.57808E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 4.88268 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.62695E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68337 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 32805.91496 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.24807E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 746.89515 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.28270 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.28270 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.28270 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.31886E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.82347E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.82347E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.28270 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.87856E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68246 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 33126.34966 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.31886E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 754.18916 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.86288 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.86288 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.86288 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.26949E-004 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.85901E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.85901E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.86288 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.72023E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68259 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5745.93752 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.26949E-004 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 130.81975 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.85700 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.85700 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.85700 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.27310E-004 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.84077E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.84077E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.85700 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.72188E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68259 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5762.26911 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27310E-004 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 131.19150 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60000 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71214 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.75804E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71214 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12483.35552 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.75804E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 248.22199 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.25396 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.25396 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.25396 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.86440E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.33925E-005 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 8.33925E-005 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.25396 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68629E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68265 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1749.09193 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.86440E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 39.82072 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.24979 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24979 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.24979 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 3.88338E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.20933E-005 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 8.20933E-005 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.24979 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68958E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68264 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1757.68136 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.88338E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 40.01624 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01720 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.01720 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.01720 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.84467E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.43423E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.43423E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.01720 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.79215E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68241 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 8349.26912 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.84467E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 190.08292 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00462 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12607 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.88800 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78011 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88800 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.02213E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.31729E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78011 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15014.61059 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.31729E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 274.93711 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.10768 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11991 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.84500 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78099 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84500 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17750E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.34440E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78099 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15137.28835 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.34440E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 277.38221 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.15447 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55154 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04278E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15221E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55154 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5215.08194 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15221E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 96.58857 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52032 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60355 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36200 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18836 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.31265E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.60322E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25378 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7256.41698 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.60322E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 157.28599 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.84714 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.52559 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 19.51719 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.52559 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 18.93108 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 18.93108 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.55600 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 18.93108 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 18.93108 |
346 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32560 |
347 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 593909.89554 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.69857E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 18.93108 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.19072E-002 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 27.98403 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.97964 |
354 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
355 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 188205.56200 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 4.15817E-003 |
357 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 2641.15342 |
358 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 18.93108 |
359 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.69857E-002 |
360 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.80347E-005 |
361 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.15817E-003 |
362 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
363 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
364 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05120 |
365 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 86019.67144 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 2.46015E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.40969E-002 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 32.02600 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
371 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.98683 |
372 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
373 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 20392.24032 |
374 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 4.50542E-004 |
375 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 286.17133 |
376 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
377 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.46015E-003 |
378 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.93561E-004 |
379 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.50542E-004 |
380 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.45561E-002 |
381 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4650.76104 |
382 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
383 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
384 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
385 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
386 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
387 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 9.45649E-003 |
388 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.13478 |
389 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 9.45649E-003 |
390 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2392.09014 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 428015.81836 |
392 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 428015.82000 |
393 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 9.45649E-003 |
394 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.45561E-002 |
395 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.94673 |
396 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.45561E-002 |
397 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 1550.25368 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.45561E-002 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 858607.51174 |
400 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 858982.81000 |
401 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 97.92404 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 6804.71 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 3805.92 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1608.58 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1918.43 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1562.58 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 2567.71 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 13363.11 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 32156.22 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 6233.02 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 6250.69 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 35399.87 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 35745.60 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 6200.31 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 6217.93 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12561.77 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 1887.35 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 1896.62 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 9009.24 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 15097.79 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 15221.09 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5243.68 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 7297.56 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 133523.10 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 14467.35 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 16087.89 | 13768.22 | 2319.67 | 0.86 | 2906.92 | 29.48 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 15833.41 | 13546.34 | 2287.07 | 0.86 | 2859.24 | 29.00 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 80474.67 | 69371.24 | 11103.43 | 0.86 | 14736.21 | 149.46 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 91009.87 | 76520.88 | 14488.99 | 0.84 | 15916.57 | 161.43 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 14464.33 | 12349.01 | 2115.32 | 0.85 | 2601.29 | 26.38 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 14369.98 | 12266.41 | 2103.56 | 0.85 | 2583.48 | 26.20 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 4230.75 | 3624.58 | 606.18 | 0.86 | 765.31 | 7.76 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 4163.64 | 3565.88 | 597.76 | 0.86 | 752.68 | 7.63 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 17266.13 | 14636.79 | 2629.33 | 0.85 | 3063.24 | 31.07 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 598185.64 | 391220.72 | 206964.92 | 0.65 | 118901.93 | 1205.97 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 67907.90 | 43748.42 | 24159.48 | 0.64 | 11137.91 | 112.97 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 4.04 | 13.79 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.36 | N/A | 2.102 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.36 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 12 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.8497088795E-002 | 3.8746363291E-002 | Pass | Pass | 1.7089329739E-002 | 8.7460937605E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.4186709732E-002 | 7.6760313469E-002 | Pass | Pass | 0.1699246993 | 0.5480023098 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5147652162E-002 | 4.2186736289E-002 | Pass | Pass | 1.2420114854E-002 | 8.1280636622E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.3932116281E-002 | 2.0001911345E-002 | Pass | Pass | 0.2993136656 | 2.0886999295 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.6490589351E-003 | 1.6641895502E-002 | Pass | Pass | 1.7001623083E-002 | 8.2982054784E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1485655766 | 0.3527077301 | Pass | Pass | 2.4987466463E-002 | 8.9702206777E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.6558457457E-002 | 0.1015249086 | Pass | Pass | 5.1922446117E-002 | 0.1220618573 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.2846825278E-002 | 6.9030911417E-002 | Pass | Pass | 1.4712366049E-002 | 7.9693278501E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.4392318365E-002 | 0.3081417376 | Pass | Pass | 0.1110909378 | 0.3833201545 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2594472824E-002 | 0.3226225349 | Pass | Pass | 0.1560029293 | 0.7121384245 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.2367348689E-002 | 5.4831847864E-002 | Pass | Pass | 8.2690657339E-003 | 8.6646214445E-002 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.2367697068E-002 | 0.1564839177 | Pass | Pass | 5.3858487919E-002 | 0.1582420368 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.1931276613E-002 | 0.2604928035 | Pass | Pass | 8.8866072161E-002 | 0.3880139377 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.5908255351E-002 | 0.2879791696 | Pass | Pass | 7.5184439607E-002 | 0.3261075926 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.1707100809E-002 | 1.2860837837E-002 | Pass | Pass | 9.3616752999E-003 | 8.1288114195E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2604084682E-002 | 0.3259728541 | Pass | Pass | 0.1246075766 | 0.5734859960 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2607986697E-002 | 0.3321924094 | Pass | Pass | 0.1233540611 | 0.5408929043 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.5767425239E-002 | 0.2088574073 | Pass | Pass | 8.4310158821E-002 | 0.4667796477 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.3817243186E-002 | 0.1145423680 | Pass | Pass | 1.6223893683E-002 | 8.1334894161E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.2061972808E-002 | 0.1162931757 | Pass | Pass | 1.5934058353E-002 | 8.0126305024E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1366794168 | 0.2107527325 | Pass | Pass | 2.1764809556E-002 | 8.1568264920E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.8162861736E-003 | 2.3440057682E-002 | Pass | Pass | 0.1992907946 | 0.7459156911 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 2.045 | 0.355 | 0.397 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 2.045 | 0.355 | 0.397 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 2.045 | 0.355 | 0.397 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.355 | 0.397 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.355 | 0.397 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.355 | 0.397 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.355 | 0.397 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 2.102 | 0.355 | 0.397 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 2.102 | 0.355 | 0.397 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.355 | 0.397 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.355 | 0.397 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.355 | 0.397 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.355 | 0.397 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.355 | 0.397 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.045 | 0.355 | 0.397 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.045 | 0.355 | 0.397 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.355 | 0.397 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.102 | 0.355 | 0.397 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.102 | 0.355 | 0.397 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.102 | 0.355 | 0.397 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.102 | 0.355 | 0.397 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.36 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 2.102 | 0.355 | 0.397 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.355 | 0.397 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.355 | 0.397 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.355 | 0.397 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.355 | 0.397 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.355 | 0.397 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 2.045 | 0.355 | 0.397 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.045 | 0.355 | 0.397 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.36 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.355 | 0.397 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 2.085 | 0.355 | 0.397 | ||||||||||||
North Total or Average | 432.93 | 2.087 | 0.355 | 0.397 | ||||||||||||
Non-North Total or Average | 781.15 | 2.084 | 0.355 | 0.397 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 6.8889 | 1978.83 | 13631.97 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 52.48 | 168.00 | 52.43 | 0.0000 | Y | 134.15 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 9.0417 | 67.07 | 606.44 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 6.67 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 9.0417 | 77.67 | 702.26 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.73 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 10.2257 | 164.24 | 1679.50 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.48 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 4.0903 | 94.76 | 387.59 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 26.12 | 168.00 | 26.09 | 0.0000 | Y | 1.90 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 5.7049 | 78.04 | 445.21 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 6.4583 | 188.86 | 1219.74 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 39.13 | 0.0000 | Y | 8.96 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 5.4896 | 1308.19 | 7181.41 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 55.29 | 0.0000 | Y | 74.54 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 4.4132 | 156.09 | 688.85 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 4.4132 | 156.07 | 688.77 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 4.4132 | 1863.81 | 8225.38 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 65.84 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 4.4132 | 1864.32 | 8227.63 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 65.86 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 4.4132 | 156.09 | 688.85 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 4.4132 | 156.07 | 688.77 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 4.4132 | 1557.62 | 6874.09 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 41.03 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 4.4132 | 39.02 | 172.21 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 1.38 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 4.4132 | 39.02 | 172.19 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 1.38 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 4.4132 | 220.77 | 974.32 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 7.80 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 6.4583 | 331.66 | 2141.96 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 48.97 | 0.0000 | Y | 19.69 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 6.4583 | 331.66 | 2141.96 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 48.97 | 0.0000 | Y | 19.69 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 11.7327 | 103.30 | 1212.04 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 4.4132 | 412.12 | 1818.79 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 10.86 |
Interior Lighting Total | 5.3388 | 11345.29 | 60569.92 | 342.04 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1219.74 | 475.70 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1219.74 | 475.70 |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 7181.41 | 502.70 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 7181.41 | 502.70 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11632.50 | AstronomicalClock | - | 83.64 | 83.64 | 182.64 | |
Exterior Lighting Total | 11632.50 | 182.64 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 428015.82 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 858982.81 | 2.96 | 4.04 | 13.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11095.85 | 16087.89 | 13768.22 | 2319.67 | 0.86 | - | 2906.92 | 29.48 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 10923.16 | 15833.41 | 13546.34 | 2287.07 | 0.86 | - | 2859.24 | 29.00 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 55178.95 | 80474.67 | 69371.24 | 11103.43 | 0.86 | - | 14736.21 | 149.46 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 63759.15 | 91009.87 | 76520.88 | 14488.99 | 0.84 | - | 15916.57 | 161.43 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 9996.76 | 14464.33 | 12349.01 | 2115.32 | 0.85 | - | 2601.29 | 26.38 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 9932.99 | 14369.98 | 12266.41 | 2103.56 | 0.85 | - | 2583.48 | 26.20 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 2915.89 | 4230.75 | 3624.58 | 606.18 | 0.86 | - | 765.31 | 7.76 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 2870.46 | 4163.64 | 3565.88 | 597.76 | 0.86 | - | 752.68 | 7.63 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 12008.07 | 17266.13 | 14636.79 | 2629.33 | 0.85 | - | 3063.24 | 31.07 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 593909.90 | 598185.64 | 391220.72 | 206964.92 | 0.65 | - | 118901.93 | 1205.97 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 86019.67 | 67907.90 | 43748.42 | 24159.48 | 0.64 | - | 11137.91 | 112.97 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 6765.89 | 6804.71 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3784.46 | 3805.92 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1600.16 | 1608.58 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1907.62 | 1918.43 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1552.86 | 1562.58 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2553.24 | 2567.71 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13294.51 | 13363.11 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 31987.11 | 32156.22 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5776.26 | 6233.02 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5792.64 | 6250.69 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 32805.91 | 35399.87 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 33126.35 | 35745.60 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5745.94 | 6200.31 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 5762.27 | 6217.93 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12483.36 | 12561.77 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1749.09 | 1887.35 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1757.68 | 1896.62 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 8349.27 | 9009.24 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15014.61 | 15097.79 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 15137.29 | 15221.09 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 5215.08 | 5243.68 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 7256.42 | 7297.56 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 188205.56 | 133523.10 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 20392.24 | 14467.35 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.96 | 678.15 | 703.64 | 1.00 | 1.21 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.95 | 667.08 | 703.64 | 1.00 | 1.21 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 4.88 | 3435.63 | 703.64 | 1.00 | 0.97 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.28 | 3717.10 | 703.64 | 1.00 | 0.97 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.86 | 607.16 | 703.64 | 1.00 | 1.24 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.86 | 603.02 | 703.64 | 1.00 | 1.24 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 178.70 | 703.64 | 1.00 | 1.84 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 175.76 | 703.64 | 1.00 | 1.85 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.02 | 715.74 | 703.64 | 1.00 | 1.19 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 18.93 | 42596.30 | 2250.07 | 1.00 | 1.11 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 134283.83 | 0.024556 | 4650.76 | 189393.57 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.009456 | 2392.09 | 252957.60 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.024556 | 1550.25 | 63131.19 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 30251.28 | 30251.28 | 15.29 | 2.199 | 2.199 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 24.00 | 24.00 | 0.00930 | 28.81 | 0.01410 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3907.79 | 3907.79 | 58.26 | 0.284 | 0.284 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00943 | 31.85 | 0.01410 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2844.99 | 2844.99 | 36.63 | 0.207 | 0.207 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00958 | 31.36 | 0.01410 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44754.00 | 44754.00 | 573.48 | 3.253 | 3.253 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00856 | 32.10 | 0.01410 | 0.000 | 0.00 |
CAFE_FLR_1 | 16798.64 | 16798.64 | 88.95 | 1.222 | 1.222 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01055 | 31.85 | 0.01410 | 0.676 | 0.00 |
LOBBY_FLR_1 | 55994.44 | 55994.44 | 42.80 | 4.072 | 4.072 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.01029 | 31.98 | 0.01410 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 9838.67 | 9838.67 | 252.13 | 0.964 | 0.964 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00870 | 31.16 | 0.01410 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9677.93 | 9677.93 | 248.04 | 0.948 | 0.948 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00870 | 31.16 | 0.01410 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 49848.24 | 49848.24 | 2032.64 | 4.883 | 4.883 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00863 | 31.98 | 0.01410 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 53927.95 | 53927.95 | 2198.40 | 5.283 | 5.283 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00888 | 32.10 | 0.01410 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8808.60 | 8808.60 | 225.73 | 0.863 | 0.863 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00872 | 28.03 | 0.01410 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8748.58 | 8748.58 | 224.22 | 0.857 | 0.857 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00872 | 28.03 | 0.01410 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2592.54 | 2592.54 | 66.44 | 0.254 | 0.254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00869 | 31.26 | 0.01410 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2549.92 | 2549.92 | 65.35 | 0.250 | 0.250 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00869 | 31.16 | 0.01410 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10383.76 | 10383.76 | 423.30 | 1.017 | 1.017 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00879 | 31.98 | 0.01410 | 0.099 | 0.00 |
BANQUET_FLR_6 | 27542.81 | 27542.81 | 83.05 | 2.005 | 2.005 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.98 | 0.01057 | 32.10 | 0.01410 | 1.187 | 0.00 |
DINING_FLR_6 | 28959.31 | 28959.31 | 87.32 | 2.108 | 2.108 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.98 | 0.01047 | 32.10 | 0.01410 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 29560.93 | 29560.93 | 286.15 | 2.154 | 2.154 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01016 | 31.43 | 0.01410 | 0.367 | 0.00 |
MECH_FLR_1 | 2993.14 | 2993.14 | 18.22 | 0.218 | 0.218 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00871 | 31.36 | 0.01410 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1208.50 | 1208.50 | 12.75 | 0.088 | 0.088 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00885 | 32.03 | 0.01410 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 9662.36 | 9662.36 | 24.81 | 0.702 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00870 | 31.80 | 0.01410 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 7158.70 | 7158.70 | 17.37 | 0.520 | 0.520 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00862 | 32.10 | 0.01410 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 3087.33 | 3087.33 | 46.03 | 0.132 | 0.132 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00709 | -10.70 | 0.00150 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 875.26 | 875.26 | 11.27 | 0.038 | 0.092 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00730 | -10.70 | 0.00150 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 2082.79 | 2082.79 | 26.69 | 0.089 | 0.089 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00713 | -10.70 | 0.00150 | 0.000 | 0.00 |
CAFE_FLR_1 | 7951.13 | 7951.13 | 42.10 | 0.341 | 0.676 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00711 | -10.70 | 0.00150 | 0.676 | 0.00 |
LOBBY_FLR_1 | 17033.42 | 17033.42 | 13.02 | 0.730 | 1.893 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00716 | -10.70 | 0.00150 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 5776.44 | 5776.44 | 148.03 | 0.249 | 0.249 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00740 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 5792.83 | 5792.83 | 148.47 | 0.250 | 0.250 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00740 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 32806.36 | 32806.36 | 1337.73 | 1.415 | 1.415 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00744 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 33126.80 | 33126.80 | 1350.43 | 1.429 | 1.429 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.11 | 21.11 | 0.00744 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 5746.12 | 5746.12 | 147.25 | 0.248 | 0.248 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00740 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 5762.45 | 5762.45 | 147.69 | 0.249 | 0.249 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00740 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 1749.15 | 1749.15 | 44.82 | 0.075 | 0.075 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00750 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1757.74 | 1757.74 | 45.05 | 0.076 | 0.076 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00750 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8349.48 | 8349.48 | 340.37 | 0.360 | 0.360 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00751 | -10.70 | 0.00150 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5627.75 | 5627.75 | 16.97 | 0.241 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00761 | -10.70 | 0.00150 | 1.187 | 0.00 |
DINING_FLR_6 | 5745.62 | 5745.62 | 17.32 | 0.246 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00762 | -10.70 | 0.00150 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 2313.82 | 2313.82 | 22.40 | 0.099 | 0.367 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00662 | -10.70 | 0.00150 | 0.367 | 0.00 |
MECH_FLR_1 | 1556.05 | 1556.05 | 9.47 | 0.067 | 0.067 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00716 | -10.70 | 0.00150 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1096.53 | 1096.53 | 11.57 | 0.047 | 0.058 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00717 | -10.70 | 0.00150 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 8728.56 | 8728.56 | 22.42 | 0.374 | 0.475 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00751 | -10.70 | 0.00150 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 5918.00 | 5918.00 | 14.36 | 0.254 | 0.254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00767 | -10.70 | 0.00150 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 18.93 | 18.93 | 7.33 | 7.33 | 18.9311 | 10.5256 | 18.9311 | 0.5560 | 0.3000 |
FLR_3_DOAS | 14.63 | 2.05 | 4.35 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 6765.893 | 6765.893 | 1.282032 | 0.00014948 | 119.726 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6804.71 | 6765.89 | 1.282032 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 6806.02 | 6806.02 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 3784.464 | 3784.464 | 0.132375 | 0.00008361 | 82.026 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3805.92 | 3784.46 | 0.132375 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00709098 | 45.8908 | 3087.33 | 0.00 | 3808.64 | 3808.64 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1600.159 | 1600.159 | 0.137546 | 0.00003535 | 30.379 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1608.58 | 1600.16 | 0.137546 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00730160 | 47.2336 | 875.26 | 0.00 | 1609.28 | 1609.28 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1907.616 | 1907.616 | 0.066726 | 0.00004215 | 41.347 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1918.43 | 1907.62 | 0.066726 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00715659 | 46.3062 | 1556.05 | 0.00 | 1919.80 | 1919.80 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1552.861 | 1552.861 | 0.086610 | 0.00003431 | 30.960 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1562.58 | 1552.86 | 0.086610 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00716648 | 46.3697 | 1096.53 | 0.00 | 1563.17 | 1563.17 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 2553.239 | 2553.239 | 0.089309 | 0.00005641 | 55.340 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2567.71 | 2553.24 | 0.089309 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00712519 | 46.1073 | 2082.79 | 0.00 | 2569.55 | 2569.55 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 13294.507 | 13294.507 | 1.014563 | 0.00029373 | 256.770 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 13363.11 | 13294.51 | 1.014563 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00710675 | 45.9913 | 7951.13 | 0.00 | 13369.74 | 13369.74 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 31987.115 | 31987.115 | 2.838223 | 0.00070672 | 604.726 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 32156.22 | 31987.11 | 2.838223 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00716035 | 46.3308 | 17033.42 | 0.00 | 32169.81 | 32169.81 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11095.847 | -999.000 | 0.963785 | 0.00031733 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 11095.85 | 10582.77 | 0.963785 | 21.68 | 15.71 | 0.00869650 | 12.80 | 12.09 | 0.00850000 | 31.16 | 0.01409687 | 22.84 | 0.0000 | 21.11 | 0.00869650 | 55.7530 | 9838.67 | 0.00 | 11115.38 | 11115.38 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 5776.256 | 5776.256 | 0.249149 | 0.00012762 | 131.510 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6233.02 | 5776.26 | 0.249149 | 21.11 | 14.32 | 0.00740057 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00740057 | 47.5422 | 5776.44 | 0.00 | 6235.65 | 6235.65 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10923.159 | -999.000 | 0.948040 | 0.00031240 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 10923.16 | 10410.81 | 0.948040 | 21.68 | 15.71 | 0.00869946 | 12.80 | 12.09 | 0.00850000 | 31.16 | 0.01409687 | 22.84 | 0.0000 | 21.11 | 0.00869946 | 55.7717 | 9677.93 | 0.00 | 10942.33 | 10942.33 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 5792.639 | 5792.639 | 0.249856 | 0.00012798 | 131.883 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6250.69 | 5792.64 | 0.249856 | 21.11 | 14.32 | 0.00740215 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00740215 | 47.5523 | 5792.83 | 0.00 | 6253.33 | 6253.33 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 55178.953 | -999.000 | 4.882679 | 0.00157808 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 55178.95 | 53503.26 | 4.882679 | 21.68 | 15.65 | 0.00862695 | 12.80 | 12.09 | 0.00850000 | 31.98 | 0.01409687 | 23.07 | 0.0000 | 21.11 | 0.00862695 | 55.3109 | 49848.24 | 0.00 | 55271.98 | 55271.98 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 32805.915 | 32805.915 | 1.415051 | 0.00072481 | 746.895 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 35399.87 | 32805.91 | 1.415051 | 21.11 | 14.35 | 0.00743703 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00743703 | 47.7729 | 32806.36 | 0.00 | 35415.17 | 35415.17 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 63759.148 | -999.000 | 5.282701 | 0.00182347 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 63759.15 | 58312.57 | 5.282701 | 21.68 | 15.87 | 0.00887856 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01409687 | 23.10 | 0.0000 | 21.11 | 0.00887856 | 56.9037 | 53927.95 | 0.00 | 63865.16 | 60777.87 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 33126.350 | 33126.350 | 1.428873 | 0.00073189 | 754.189 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 35745.60 | 33126.35 | 1.428873 | 21.11 | 14.36 | 0.00744187 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00744187 | 47.8036 | 33126.80 | 0.00 | 35761.09 | 35761.09 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9996.764 | -999.000 | 0.862883 | 0.00028590 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 9996.76 | 9481.56 | 0.862883 | 21.68 | 15.73 | 0.00872023 | 12.80 | 12.09 | 0.00850000 | 28.03 | 0.01409688 | 21.96 | 0.0000 | 21.11 | 0.00872023 | 55.9031 | 8808.60 | 0.00 | 10013.93 | 10013.93 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 5745.938 | 5745.938 | 0.247842 | 0.00012695 | 130.820 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6200.31 | 5745.94 | 0.247842 | 21.11 | 14.32 | 0.00739770 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00739770 | 47.5240 | 5746.12 | 0.00 | 6202.92 | 6202.92 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9932.986 | -999.000 | 0.857003 | 0.00028408 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 9932.99 | 9417.42 | 0.857003 | 21.68 | 15.73 | 0.00872188 | 12.80 | 12.09 | 0.00850000 | 28.03 | 0.01409688 | 21.96 | 0.0000 | 21.11 | 0.00872188 | 55.9136 | 8748.58 | 0.00 | 9950.01 | 9950.01 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 5762.269 | 5762.269 | 0.248546 | 0.00012731 | 131.191 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6217.93 | 5762.27 | 0.248546 | 21.11 | 14.32 | 0.00739929 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00739929 | 47.5341 | 5762.45 | 0.00 | 6220.55 | 6220.55 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12483.356 | 12483.356 | 0.712143 | 0.00027580 | 248.222 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 12561.77 | 12483.36 | 0.712143 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00750860 | 48.5560 | 8728.56 | 0.00 | 12566.33 | 12566.33 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2915.891 | -999.000 | 0.253962 | 0.00008339 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 2915.89 | 2787.75 | 0.253962 | 21.68 | 15.70 | 0.00868629 | 12.80 | 12.09 | 0.00850000 | 31.26 | 0.01409687 | 22.87 | 0.0000 | 21.11 | 0.00868629 | 55.6885 | 2592.54 | 0.00 | 2920.51 | 2920.51 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1749.092 | 1749.092 | 0.075444 | 0.00003864 | 39.821 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1887.35 | 1749.09 | 0.075444 | 21.11 | 14.41 | 0.00749689 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00749689 | 48.1537 | 1749.15 | 0.00 | 1888.20 | 1888.20 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2870.462 | -999.000 | 0.249787 | 0.00008209 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 2870.46 | 2742.19 | 0.249787 | 21.68 | 15.70 | 0.00868958 | 12.80 | 12.09 | 0.00850000 | 31.16 | 0.01409687 | 22.84 | 0.0000 | 21.11 | 0.00868958 | 55.7092 | 2549.92 | 0.00 | 2874.99 | 2874.99 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1757.681 | 1757.681 | 0.075815 | 0.00003883 | 40.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1896.62 | 1757.68 | 0.075815 | 21.11 | 14.41 | 0.00749921 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00749921 | 48.1683 | 1757.74 | 0.00 | 1897.47 | 1897.47 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12008.071 | -999.000 | 1.017196 | 0.00034342 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 12008.07 | 11200.68 | 1.017196 | 21.68 | 15.79 | 0.00879215 | 12.80 | 12.09 | 0.00850000 | 31.98 | 0.01409687 | 23.07 | 0.0000 | 21.11 | 0.00879215 | 56.3581 | 10383.76 | 0.00 | 12027.25 | 11695.65 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8349.269 | 8349.269 | 0.360135 | 0.00018447 | 190.083 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 9009.24 | 8349.27 | 0.360135 | 21.11 | 14.43 | 0.00751338 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00751338 | 48.2578 | 8349.48 | 0.00 | 9013.32 | 9013.32 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15014.611 | 15014.611 | 1.780107 | 0.00033173 | 274.937 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 15097.79 | 15014.61 | 1.780107 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00760876 | 49.1966 | 5627.75 | 0.00 | 15102.50 | 15102.50 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15137.288 | 15137.288 | 1.780994 | 0.00033444 | 277.382 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 15221.09 | 15137.29 | 1.780994 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00761631 | 49.2448 | 5745.62 | 0.00 | 15225.88 | 15225.88 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 5215.082 | 5215.082 | 0.551544 | 0.00011522 | 96.589 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 5243.68 | 5215.08 | 0.551544 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00662024 | 42.8797 | 2313.82 | 0.00 | 5245.52 | 5245.52 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 7256.417 | 7256.417 | 0.253778 | 0.00016032 | 157.286 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 7297.56 | 7256.42 | 0.253778 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00767068 | 49.5917 | 5918.00 | 0.00 | 7302.78 | 7302.78 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 593909.896 | -999.000 | 18.931077 | 0.01698575 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 593909.90 | 385472.31 | 18.931077 | 27.98 | 20.39 | 0.01190723 | 10.98 | 10.98 | 0.00828082 | 32.10 | 0.01409687 | 23.10 | 49.2608 | 23.99 | 0.00959367 | 51.5538 | 260244.43 | 0.00 | 649666.78 | 413147.40 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 188205.562 | 188205.562 | 5.679323 | 0.00415817 | 2641.153 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 133523.10 | 188205.56 | 5.679323 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 164.2027 | 21.00 | 0.00742850 | 48.0454 | 61673.82 | 0.00 | 133365.72 | 133365.72 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 86019.671 | -999.000 | 2.051199 | 0.00246015 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 86019.67 | 50571.42 | 2.051199 | 32.03 | 23.08 | 0.01409687 | 10.99 | 12.09 | 0.00828082 | 32.03 | 0.01409687 | 23.08 | 100.0000 | 21.11 | 0.00875716 | 56.1354 | 149035.38 | 0.00 | 92067.83 | 54149.50 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20392.240 | 20392.240 | 0.615360 | 0.00045054 | 286.171 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 14467.35 | 20392.24 | 0.615360 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 333.3333 | 21.11 | 0.00743987 | 47.7909 | 100866.54 | 0.00 | 14450.29 | 14450.29 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 6765.893 | 6765.893 | 1.282032 | 0.00014948 | 119.726 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 1.5585 | 1.580758 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6804.71 | 6765.89 | 1.0000 | 1.54304758 | 1.282032 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.14946889 | 60.00 | 49.00 | 11.00 | 0.000 | 6804.71 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 6806.02 | 6806.02 | 1.54304758 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 20.93 | 14.81 | 0.00800000 | 41345.5 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3784.464 | 3784.464 | 0.132375 | 0.00008361 | 82.026 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 0.8717 | 0.884188 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 3805.92 | 3784.46 | 1.0000 | 0.15932637 | 0.132375 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.08360457 | 60.00 | 49.00 | 11.00 | 0.000 | 3805.92 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00709098 | 21.00 | 0.00709098 | 45.8908 | 3087.33 | 0.00 | 3808.64 | 3808.64 | 0.15932637 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60839.4 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1600.159 | 1600.159 | 0.137546 | 0.00003535 | 30.379 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 0.3684 | 0.373855 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1608.58 | 1600.16 | 1.0000 | 0.16554942 | 0.137546 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03534996 | 60.00 | 49.00 | 11.00 | 0.000 | 1608.58 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00730160 | 21.00 | 0.00730160 | 47.2336 | 875.26 | 0.00 | 1609.28 | 1609.28 | 0.16554942 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.13 | 16.69 | 0.00800000 | 46655.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1907.616 | 1907.616 | 0.066726 | 0.00004215 | 41.347 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 0.4394 | 0.445688 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1918.43 | 1907.62 | 1.0000 | 0.08031132 | 0.066726 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.04214214 | 60.00 | 49.00 | 11.00 | 0.000 | 1918.43 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00715659 | 21.00 | 0.00715659 | 46.3062 | 1556.05 | 0.00 | 1919.80 | 1919.80 | 0.08031132 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60839.2 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1552.861 | 1552.861 | 0.086610 | 0.00003431 | 30.960 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 0.3579 | 0.362805 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 1562.58 | 1552.86 | 1.0000 | 0.10424278 | 0.086610 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03430507 | 60.00 | 49.00 | 11.00 | 0.000 | 1562.58 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00716648 | 21.00 | 0.00716648 | 46.3697 | 1096.53 | 0.00 | 1563.17 | 1563.17 | 0.10424278 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 31.31 | 18.45 | 0.00800000 | 51930.2 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2553.239 | 2553.239 | 0.089309 | 0.00005641 | 55.340 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 0.5881 | 0.596529 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 2567.71 | 2553.24 | 1.0000 | 0.10749203 | 0.089309 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.05640494 | 60.00 | 49.00 | 11.00 | 0.000 | 2567.71 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00712519 | 21.00 | 0.00712519 | 46.1073 | 2082.79 | 0.00 | 2569.55 | 2569.55 | 0.10749203 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60839.3 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13294.507 | 13294.507 | 1.014563 | 0.00029373 | 256.770 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 3.0605 | 3.106078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 13363.11 | 13294.51 | 1.0000 | 1.22112266 | 1.014563 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.29369593 | 60.00 | 49.00 | 11.00 | 0.000 | 13363.11 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00710675 | 21.00 | 0.00710675 | 45.9913 | 7951.13 | 0.00 | 13369.74 | 13369.74 | 1.22112266 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 27.34 | 17.11 | 0.00800000 | 47883.5 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31987.115 | 31987.115 | 2.838223 | 0.00070672 | 604.726 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 7.3646 | 7.473349 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 32156.22 | 31987.11 | 1.0000 | 3.41607081 | 2.838223 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.70664412 | 60.00 | 49.00 | 11.00 | 0.000 | 32156.22 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00716035 | 21.00 | 0.00716035 | 46.3308 | 17033.42 | 0.00 | 32169.81 | 32169.81 | 3.41607081 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 25.84 | 16.59 | 0.00800000 | 46351.9 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11095.847 | -999.000 | 0.963785 | 0.00031733 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0064 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.963785 | 1.16000655 | 4197.9300 | 999.8980 | 24.55356117 | 15.03 | 6.70 | 8.33 | 858607.51 | 1.2923 | 1.292283 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | 11095.85 | 10582.77 | 1.0000 | 1.16000655 | 0.963785 | 21.68 | 15.71 | 0.00869650 | 43887.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.31730152 | 6.70 | 13.38 | 8.33 | 0.000 | 11095.85 | 31.16 | 0.01409687 | 22.84 | 0.00000000 | 0.0000 | 21.11 | 0.00869650 | 21.11 | 0.00869650 | 55.7530 | 9838.67 | 0.00 | 11115.38 | 11115.38 | 1.16000655 | 21.68 | 15.71 | 0.00869650 | 43887.5 | 12.30 | 12.09 | 0.00869650 | 34305.4 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5776.256 | 5776.256 | 0.249149 | 0.00012762 | 131.510 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.963785 | 1.16000655 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 1.4275 | 1.349543 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6233.02 | 5776.26 | 1.0000 | 0.29987507 | 0.249149 | 21.11 | 14.32 | 0.00740057 | 40011.1 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.12760629 | 60.00 | 49.00 | 11.00 | 0.000 | 6233.02 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00740057 | 21.11 | 0.00740057 | 47.5422 | 5776.44 | 0.00 | 6235.65 | 6235.65 | 0.29987507 | 16.60 | 12.55 | 0.00740057 | 35417.1 | 37.01 | 19.80 | 0.00740057 | 56211.2 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10923.159 | -999.000 | 0.948040 | 0.00031240 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0119 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.948040 | 1.14105583 | 4197.9300 | 999.8980 | 24.55356117 | 15.03 | 6.70 | 8.33 | 858607.51 | 1.2722 | 1.272171 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | 10923.16 | 10410.81 | 1.0000 | 1.14105583 | 0.948040 | 21.68 | 15.71 | 0.00869946 | 43895.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.31236328 | 6.70 | 13.38 | 8.33 | 0.000 | 10923.16 | 31.16 | 0.01409687 | 22.84 | 0.00000000 | 0.0000 | 21.11 | 0.00869946 | 21.11 | 0.00869946 | 55.7717 | 9677.93 | 0.00 | 10942.33 | 10942.33 | 1.14105583 | 21.68 | 15.72 | 0.00869946 | 43895.0 | 12.29 | 12.09 | 0.00869946 | 34305.4 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5792.639 | 5792.639 | 0.249856 | 0.00012798 | 131.883 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.948040 | 1.14105583 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 1.4316 | 1.353370 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6250.69 | 5792.64 | 1.0000 | 0.30072562 | 0.249856 | 21.11 | 14.32 | 0.00740215 | 40015.1 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.12796823 | 60.00 | 49.00 | 11.00 | 0.000 | 6250.69 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00740215 | 21.11 | 0.00740215 | 47.5523 | 5792.83 | 0.00 | 6253.33 | 6253.33 | 0.30072562 | 16.60 | 12.56 | 0.00740215 | 35421.1 | 37.01 | 19.80 | 0.00740215 | 56215.2 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 55178.953 | -999.000 | 4.882679 | 0.00157808 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8771 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 4.882679 | 5.87676829 | 4197.9300 | 999.8980 | 24.55356117 | 15.03 | 6.70 | 8.33 | 858607.51 | 6.4266 | 6.426443 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | 55178.95 | 53503.26 | 1.0000 | 5.87676829 | 4.882679 | 21.68 | 15.65 | 0.00862695 | 43711.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 1.57792062 | 6.70 | 13.38 | 8.33 | 0.000 | 55178.95 | 31.98 | 0.01409687 | 23.07 | 0.00000000 | 0.0000 | 21.11 | 0.00862695 | 21.11 | 0.00862695 | 55.3109 | 49848.24 | 0.00 | 55271.98 | 55271.98 | 5.87676829 | 21.68 | 15.65 | 0.00862695 | 43711.5 | 12.47 | 12.09 | 0.00862695 | 34306.4 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32805.915 | 32805.915 | 1.415051 | 0.00072481 | 746.895 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 4.882679 | 5.87676829 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 8.1075 | 7.664650 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 35399.87 | 32805.91 | 1.0000 | 1.70314833 | 1.415051 | 21.11 | 14.35 | 0.00743703 | 40104.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.72473267 | 60.00 | 49.00 | 11.00 | 0.000 | 35399.87 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00743703 | 21.11 | 0.00743703 | 47.7729 | 32806.36 | 0.00 | 35415.17 | 35415.17 | 1.70314833 | 16.60 | 12.59 | 0.00743703 | 35509.4 | 37.01 | 19.83 | 0.00743703 | 56303.4 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 63759.148 | -999.000 | 5.282701 | 0.00182347 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3448 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.282701 | 6.35823226 | 4197.9300 | 999.8980 | 24.55356117 | 15.03 | 6.70 | 8.33 | 858607.51 | 7.4259 | 7.425740 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | 63759.15 | 58312.57 | 1.0000 | 6.35823226 | 5.282701 | 21.68 | 15.87 | 0.00887856 | 44350.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 1.82328351 | 6.70 | 13.38 | 8.33 | 0.000 | 63759.15 | 32.10 | 0.01409687 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00887856 | 21.11 | 0.00887856 | 56.9037 | 53927.95 | 0.00 | 63865.16 | 60777.87 | 6.35823226 | 21.68 | 15.87 | 0.00887856 | 44350.0 | 12.32 | 12.09 | 0.00868617 | 34305.5 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33126.350 | 33126.350 | 1.428873 | 0.00073189 | 754.189 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.282701 | 6.35823226 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 8.1867 | 7.739515 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 35745.60 | 33126.35 | 1.0000 | 1.71978398 | 1.428873 | 21.11 | 14.36 | 0.00744187 | 40116.3 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.73181156 | 60.00 | 49.00 | 11.00 | 0.000 | 35745.60 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00744187 | 21.11 | 0.00744187 | 47.8036 | 33126.80 | 0.00 | 35761.09 | 35761.09 | 1.71978398 | 16.60 | 12.60 | 0.00744187 | 35521.7 | 37.01 | 19.83 | 0.00744187 | 56315.6 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9996.764 | -999.000 | 0.862883 | 0.00028590 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0505 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.862883 | 1.03856137 | 4197.9300 | 999.8980 | 24.55356117 | 15.03 | 6.70 | 8.33 | 858607.51 | 1.1643 | 1.164278 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 9996.76 | 9481.56 | 1.0000 | 1.03856137 | 0.862883 | 21.68 | 15.73 | 0.00872023 | 43947.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.28587169 | 6.70 | 13.38 | 8.33 | 0.000 | 9996.76 | 28.03 | 0.01409688 | 21.96 | 0.00000000 | 0.0000 | 21.11 | 0.00872023 | 21.11 | 0.00872023 | 55.9031 | 8808.60 | 0.00 | 10013.93 | 10013.93 | 1.03856137 | 21.68 | 15.74 | 0.00872023 | 43947.8 | 12.24 | 12.09 | 0.00872023 | 34305.7 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5745.938 | 5745.938 | 0.247842 | 0.00012695 | 130.820 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.862883 | 1.03856137 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 1.4200 | 1.342459 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6200.31 | 5745.94 | 1.0000 | 0.29830110 | 0.247842 | 21.11 | 14.32 | 0.00739770 | 40003.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.12693652 | 60.00 | 49.00 | 11.00 | 0.000 | 6200.31 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00739770 | 21.11 | 0.00739770 | 47.5240 | 5746.12 | 0.00 | 6202.92 | 6202.92 | 0.29830110 | 16.60 | 12.55 | 0.00739770 | 35409.8 | 37.01 | 19.80 | 0.00739770 | 56204.0 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9932.986 | -999.000 | 0.857003 | 0.00028408 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0535 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.857003 | 1.03148478 | 4197.9300 | 999.8980 | 24.55356117 | 15.03 | 6.70 | 8.33 | 858607.51 | 1.1569 | 1.156850 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 9932.99 | 9417.42 | 1.0000 | 1.03148478 | 0.857003 | 21.68 | 15.73 | 0.00872188 | 43952.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.28404785 | 6.70 | 13.38 | 8.33 | 0.000 | 9932.99 | 28.03 | 0.01409688 | 21.96 | 0.00000000 | 0.0000 | 21.11 | 0.00872188 | 21.11 | 0.00872188 | 55.9136 | 8748.58 | 0.00 | 9950.01 | 9950.01 | 1.03148478 | 21.68 | 15.74 | 0.00872188 | 43952.0 | 12.24 | 12.09 | 0.00872188 | 34305.7 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5762.269 | 5762.269 | 0.248546 | 0.00012731 | 131.191 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.857003 | 1.03148478 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 1.4241 | 1.346275 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 6217.93 | 5762.27 | 1.0000 | 0.29914895 | 0.248546 | 21.11 | 14.32 | 0.00739929 | 40007.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.12729731 | 60.00 | 49.00 | 11.00 | 0.000 | 6217.93 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00739929 | 21.11 | 0.00739929 | 47.5341 | 5762.45 | 0.00 | 6220.55 | 6220.55 | 0.29914895 | 16.60 | 12.55 | 0.00739929 | 35413.9 | 37.01 | 19.80 | 0.00739929 | 56208.0 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12483.356 | 12483.356 | 0.712143 | 0.00027580 | 248.222 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 2.8770 | 2.916564 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 12561.77 | 12483.36 | 1.0000 | 0.85713207 | 0.712143 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.27577635 | 60.00 | 49.00 | 11.00 | 0.000 | 12561.77 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00750860 | 21.00 | 0.00750860 | 48.5560 | 8728.56 | 0.00 | 12566.33 | 12566.33 | 0.85713207 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 30.98 | 18.34 | 0.00800000 | 51595.6 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2915.891 | -999.000 | 0.253962 | 0.00008339 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9874 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.253962 | 0.30566766 | 4197.9300 | 999.8980 | 24.55356117 | 15.03 | 6.70 | 8.33 | 858607.51 | 0.3396 | 0.339601 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | 2915.89 | 2787.75 | 1.0000 | 0.30566766 | 0.253962 | 21.68 | 15.70 | 0.00868629 | 43861.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.08338404 | 6.70 | 13.38 | 8.33 | 0.000 | 2915.89 | 31.26 | 0.01409687 | 22.87 | 0.00000000 | 0.0000 | 21.11 | 0.00868629 | 21.11 | 0.00868629 | 55.6885 | 2592.54 | 0.00 | 2920.51 | 2920.51 | 0.30566766 | 21.68 | 15.71 | 0.00868629 | 43861.6 | 12.32 | 12.09 | 0.00868629 | 34307.1 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1749.092 | 1749.092 | 0.075444 | 0.00003864 | 39.821 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.253962 | 0.30566766 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 0.4323 | 0.408651 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1887.35 | 1749.09 | 1.0000 | 0.09080434 | 0.075444 | 21.11 | 14.41 | 0.00749689 | 40255.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03864011 | 60.00 | 49.00 | 11.00 | 0.000 | 1887.35 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00749689 | 21.11 | 0.00749689 | 48.1537 | 1749.15 | 0.00 | 1888.20 | 1888.20 | 0.09080434 | 16.60 | 12.65 | 0.00749689 | 35661.0 | 37.01 | 19.87 | 0.00749689 | 56455.1 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2870.462 | -999.000 | 0.249787 | 0.00008209 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9935 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.249787 | 0.30064231 | 4197.9300 | 999.8980 | 24.55356117 | 15.03 | 6.70 | 8.33 | 858607.51 | 0.3343 | 0.334310 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | 2870.46 | 2742.19 | 1.0000 | 0.30064231 | 0.249787 | 21.68 | 15.70 | 0.00868958 | 43870.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.08208494 | 6.70 | 13.38 | 8.33 | 0.000 | 2870.46 | 31.16 | 0.01409687 | 22.84 | 0.00000000 | 0.0000 | 21.11 | 0.00868958 | 21.11 | 0.00868958 | 55.7092 | 2549.92 | 0.00 | 2874.99 | 2874.99 | 0.30064231 | 21.68 | 15.71 | 0.00868958 | 43870.0 | 12.32 | 12.09 | 0.00868958 | 34307.1 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1757.681 | 1757.681 | 0.075815 | 0.00003883 | 40.016 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.249787 | 0.30064231 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 0.4344 | 0.410658 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1896.62 | 1757.68 | 1.0000 | 0.09125026 | 0.075815 | 21.11 | 14.41 | 0.00749921 | 40261.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03882986 | 60.00 | 49.00 | 11.00 | 0.000 | 1896.62 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00749921 | 21.11 | 0.00749921 | 48.1683 | 1757.74 | 0.00 | 1897.47 | 1897.47 | 0.09125026 | 16.60 | 12.65 | 0.00749921 | 35666.8 | 37.01 | 19.87 | 0.00749921 | 56461.0 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12008.071 | -999.000 | 1.017196 | 0.00034342 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1842 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.017196 | 1.22429161 | 4197.9300 | 999.8980 | 24.55356117 | 15.03 | 6.70 | 8.33 | 858607.51 | 1.3986 | 1.398526 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | 12008.07 | 11200.68 | 1.0000 | 1.22429161 | 1.017196 | 21.68 | 15.79 | 0.00879215 | 44130.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.34338788 | 6.70 | 13.38 | 8.33 | 0.000 | 12008.07 | 31.98 | 0.01409687 | 23.07 | 0.00000000 | 0.0000 | 21.11 | 0.00879215 | 21.11 | 0.00879215 | 56.3581 | 10383.76 | 0.00 | 12027.25 | 11695.65 | 1.22429161 | 21.68 | 15.80 | 0.00879215 | 44130.4 | 12.33 | 12.09 | 0.00868484 | 34306.5 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8349.269 | 8349.269 | 0.360135 | 0.00018447 | 190.083 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.017196 | 1.22429161 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 2.0634 | 1.950692 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 9009.24 | 8349.27 | 1.0000 | 0.43345711 | 0.360135 | 21.11 | 14.43 | 0.00751338 | 40297.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.18444808 | 60.00 | 49.00 | 11.00 | 0.000 | 9009.24 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00751338 | 21.11 | 0.00751338 | 48.2578 | 8349.48 | 0.00 | 9013.32 | 9013.32 | 0.43345711 | 16.60 | 12.67 | 0.00751338 | 35702.7 | 37.01 | 19.88 | 0.00751338 | 56496.8 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15014.611 | 15014.611 | 1.780107 | 0.00033173 | 274.937 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 3.4578 | 3.507957 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 15097.79 | 15014.61 | 1.0000 | 2.14252771 | 1.780107 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.33169563 | 60.00 | 49.00 | 11.00 | 0.000 | 15097.79 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00760876 | 21.00 | 0.00760876 | 49.1966 | 5627.75 | 0.00 | 15102.50 | 15102.50 | 2.14252771 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 23.51 | 15.76 | 0.00800000 | 43983.7 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15137.288 | 15137.288 | 1.780994 | 0.00033444 | 277.382 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 3.4860 | 3.536619 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 15221.09 | 15137.29 | 1.0000 | 2.14359496 | 1.780994 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.33440577 | 60.00 | 49.00 | 11.00 | 0.000 | 15221.09 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00761631 | 21.00 | 0.00761631 | 49.2448 | 5745.62 | 0.00 | 15225.88 | 15225.88 | 2.14359496 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 23.57 | 15.78 | 0.00800000 | 44037.7 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5215.082 | 5215.082 | 0.551544 | 0.00011522 | 96.589 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 1.2009 | 1.218432 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 5243.68 | 5215.08 | 1.0000 | 0.66383589 | 0.551544 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.11520911 | 60.00 | 49.00 | 11.00 | 0.000 | 5243.68 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.56 | 0.00662024 | 21.00 | 0.00662024 | 42.8797 | 2313.82 | 0.00 | 5245.52 | 5245.52 | 0.66383589 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.35 | 16.06 | 0.00800000 | 44836.6 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7256.417 | 7256.417 | 0.253778 | 0.00016032 | 157.286 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 1.6713 | 1.695362 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 7297.56 | 7256.42 | 1.0000 | 0.30544609 | 0.253778 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.16030531 | 60.00 | 49.00 | 11.00 | 0.000 | 7297.56 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00767068 | 21.00 | 0.00767068 | 49.5917 | 5918.00 | 0.00 | 7302.78 | 7302.78 | 0.30544609 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.05 | 21.16 | 0.00800000 | 60843.3 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 593909.896 | -999.000 | 18.931077 | 0.01698575 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.9749 | 1004.8586 | 1.2036 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 18.931077 | 22.78534911 | 4197.9300 | 999.8980 | 24.55356117 | 15.03 | 6.70 | 8.33 | 858607.51 | 69.1713 | 69.171290 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 593909.90 | 385472.31 | 1.0000 | 22.78534911 | 18.931077 | 27.98 | 20.39 | 0.01190723 | 58518.2 | 10.98 | 10.98 | 0.00828082 | 32464.3 | 16.98401511 | 6.70 | 13.38 | 8.33 | 42596.303 | 551313.59 | 32.10 | 0.01409687 | 23.10 | 9.32560000 | 49.2608 | 23.99 | 0.00978139 | 23.99 | 0.00959367 | 51.5538 | 260244.43 | 0.00 | 649666.78 | 413147.40 | 22.78534911 | 27.98 | 20.40 | 0.01190723 | 58518.2 | 10.33 | 10.31 | 0.00778828 | 30005.7 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 188205.562 | 188205.562 | 5.679323 | 0.00415817 | 2641.153 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 18.931077 | 22.78534911 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 30.5804 | 43.971637 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 133523.10 | 188205.56 | 1.0000 | 6.83560473 | 5.679323 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 4.15774774 | 60.00 | 49.00 | 11.00 | 0.000 | 133523.10 | -10.70 | 0.00150390 | -10.70 | 9.32560000 | 164.2027 | 18.53 | 0.00614937 | 21.00 | 0.00742850 | 48.0454 | 61673.82 | 0.00 | 133365.72 | 133365.72 | 6.83560473 | 16.60 | 5.98 | 0.00150390 | 20487.9 | 35.96 | 14.43 | 0.00150390 | 39998.4 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 86019.671 | -999.000 | 2.051199 | 0.00246015 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.0454 | 1004.8586 | 1.2036 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.46881288 | 4197.9300 | 999.8980 | 24.55356117 | 15.03 | 6.70 | 8.33 | 858607.51 | 10.0185 | 10.018509 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 86019.67 | 50571.42 | 1.0000 | 2.46881288 | 2.051199 | 32.03 | 23.08 | 0.01409687 | 68275.7 | 10.99 | 12.09 | 0.00828082 | 34322.2 | 2.45990075 | 6.70 | 13.38 | 8.33 | 2194.880 | 83824.79 | 32.03 | 0.01409687 | 23.08 | 2.05119905 | 100.0000 | 21.11 | 0.00875859 | 21.11 | 0.00875716 | 56.1354 | 149035.38 | 0.00 | 92067.83 | 54149.50 | 2.46881288 | 32.03 | 23.09 | 0.01409687 | 68275.7 | 10.75 | 10.73 | 0.00800430 | 30983.3 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20392.240 | 20392.240 | 0.615360 | 0.00045054 | 286.171 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.46881288 | 4197.9300 | 999.8980 | 9.45552184 | 71.00 | 82.00 | 11.00 | 436629.81 | 3.3134 | 4.764366 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 14467.35 | 20392.24 | 1.0000 | 0.74064386 | 0.615360 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.45049567 | 60.00 | 49.00 | 11.00 | 0.000 | 14467.35 | -10.70 | 0.00150390 | -10.70 | 2.05119905 | 333.3333 | 21.11 | 0.00743857 | 21.11 | 0.00743987 | 47.7909 | 100866.54 | 0.00 | 14450.29 | 14450.29 | 0.74064386 | 16.60 | 5.98 | 0.00150390 | 20487.9 | 35.96 | 14.43 | 0.00150390 | 39998.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 18.93 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.001447 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.003555 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000609 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5227.17 | 771.67 | 0.00 |
RETAIL_1_FLR_1 | 4021.17 | 4226.00 | 492.17 |
RETAIL_2_FLR_1 | 4366.17 | 2533.17 | 4.33 |
LAUNDRY_FLR_1 | 8760.00 | 7064.17 | 7064.17 |
CAFE_FLR_1 | 5210.33 | 3991.00 | 1599.00 |
LOBBY_FLR_1 | 5886.00 | 2211.00 | 1168.50 |
ROOM_1_FLR_3 | 2168.50 | 8264.33 | 2127.33 |
ROOM_2_FLR_3 | 3395.17 | 8043.33 | 3123.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 1424.67 | 8666.50 | 1390.33 |
ROOM_5_FLR_3 | 2086.50 | 8294.50 | 2063.83 |
ROOM_6_FLR_3 | 3214.00 | 8139.17 | 3037.17 |
ROOM_1_FLR_6 | 2794.00 | 8101.17 | 2681.50 |
ROOM_2_FLR_6 | 3966.33 | 7883.33 | 3618.67 |
ROOM_3_MULT9_FLR_6 | 1176.00 | 8151.83 | 1147.17 |
BANQUET_FLR_6 | 7809.17 | 2640.33 | 2384.50 |
DINING_FLR_6 | 8520.33 | 4020.83 | 3989.00 |
KITCHEN_FLR_6 | 8760.00 | 8606.17 | 8606.17 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 8760.00 | 8760.00 | 8760.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 4013.33 | 0.00 | 4013.33 |
RETAIL_1_FLR_1 | 17.17 | 1114.83 | 17.17 | 1114.83 |
RETAIL_2_FLR_1 | 0.00 | 2178.17 | 0.00 | 2178.17 |
LAUNDRY_FLR_1 | 0.00 | 6566.67 | 0.00 | 6566.67 |
CAFE_FLR_1 | 0.00 | 2993.17 | 0.00 | 2993.17 |
LOBBY_FLR_1 | 0.00 | 3986.67 | 0.00 | 3986.67 |
ROOM_1_FLR_3 | 1.67 | 3.83 | 1.67 | 3.83 |
ROOM_2_FLR_3 | 3.83 | 21.33 | 3.83 | 21.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3.17 | 43.50 | 3.17 | 43.50 |
ROOM_5_FLR_3 | 2.83 | 1.67 | 2.83 | 1.67 |
ROOM_6_FLR_3 | 6.67 | 30.17 | 6.67 | 30.17 |
ROOM_1_FLR_6 | 1.50 | 9.50 | 1.50 | 9.50 |
ROOM_2_FLR_6 | 3.67 | 27.00 | 3.67 | 27.00 |
ROOM_3_MULT9_FLR_6 | 1.33 | 18.33 | 1.33 | 18.33 |
BANQUET_FLR_6 | 0.00 | 7445.33 | 0.00 | 7445.33 |
DINING_FLR_6 | 0.00 | 8489.00 | 0.00 | 8489.00 |
KITCHEN_FLR_6 | 0.00 | 8717.83 | 0.00 | 8717.83 |
MECH_FLR_1 | 0.00 | 478.17 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 184.50 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 447.83 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 4.83 | 1285.50 | 0.00 | 0.00 |
Facility | 451.83 | 8756.00 | 25.17 | 8756.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.73 | 106.50 | 4826.41 | 0.796 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.245 | 0.271 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.098 | 0.049 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 17.795 | 0.152 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 2.804 | 0.244 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.87 | 422.44 | 5183.56 | 1.368 | 0.070 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.340 | 0.177 | 0.000 | 0.088 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.340 | 0.177 | 0.000 | 0.074 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.386 | 0.079 | 0.000 | 0.135 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.340 | 0.177 | 0.000 | 0.088 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.340 | 0.177 | 0.000 | 0.082 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.340 | 0.177 | 0.000 | 0.106 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.340 | 0.177 | 0.000 | 0.078 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.386 | 0.144 | 0.000 | 0.169 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 3.668 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 3.875 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 12.840 | 0.150 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.73 | 106.50 | 4826.41 | 0.000 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.000 | 0.004 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.000 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 0.000 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 0.000 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.87 | 422.44 | 5183.56 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 0.000 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 0.000 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 0.000 | 0.002 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5256.62 | 71421.00 | 03-JAN-04:00 | 399062.12 | 02-AUG-19:20 |
Electricity:Building | 2181.80 | 28412.25 | 03-JUN-05:00 | 133760.38 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 277.26 | 3246.85 | 02-JAN-02:10 | 20603.11 | 02-JAN-20:10 |
InteriorLights:Electricity | 526.25 | 4377.43 | 03-JUN-05:00 | 47387.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 134.15 | 1218.95 | 02-JAN-02:10 | 10970.58 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 526.25 | 4377.43 | 03-JUN-05:00 | 47387.53 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.86 | 204.98 | 02-JAN-02:10 | 1231.40 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.67 | 60.64 | 02-JAN-02:10 | 545.79 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.52 | 237.37 | 02-JAN-02:10 | 1425.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.73 | 70.23 | 02-JAN-02:10 | 632.03 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.96 | 344.68 | 02-JAN-02:10 | 2351.00 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.48 | 167.95 | 02-JAN-02:10 | 1511.55 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.50 | 68.23 | 02-JAN-02:10 | 397.38 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.90 | 17.25 | 02-JAN-02:10 | 155.22 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 23.30 | 252.93 | 03-JUN-05:00 | 2063.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 8.96 | 49.71 | 03-JUN-05:00 | 1097.76 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 223.54 | 2764.09 | 10-JUN-05:00 | 16492.48 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 74.54 | 652.68 | 10-JUN-05:00 | 6463.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.99 | 160.87 | 02-JAN-10:10 | 1278.06 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.08 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.99 | 160.85 | 02-JAN-10:10 | 1277.91 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.01 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 260.83 | 2764.15 | 02-JAN-10:10 | 21347.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 65.84 | 411.27 | 01-JAN-11:10 | 6580.30 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 260.91 | 2764.90 | 02-JAN-10:10 | 21353.83 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 65.86 | 411.38 | 01-JAN-11:10 | 6582.10 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.99 | 160.87 | 02-JAN-10:10 | 1278.06 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.08 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.99 | 160.85 | 02-JAN-10:10 | 1277.91 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.01 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 41.03 | 372.78 | 02-JAN-02:10 | 3355.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 41.03 | 372.78 | 02-JAN-02:10 | 3355.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.00 | 40.22 | 02-JAN-10:10 | 319.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.38 | 8.61 | 01-JAN-11:10 | 137.77 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.00 | 40.21 | 02-JAN-10:10 | 319.48 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.38 | 8.61 | 01-JAN-11:10 | 137.75 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.90 | 327.42 | 02-JAN-10:10 | 2528.74 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.80 | 48.72 | 01-JAN-11:10 | 779.46 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 195.55 | 2377.82 | 03-JUN-05:00 | 8675.67 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 19.69 | 128.52 | 03-JUN-05:00 | 1927.76 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 195.55 | 2377.82 | 03-JUN-05:00 | 8675.67 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 19.69 | 128.52 | 03-JUN-05:00 | 1927.76 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 10.86 | 98.63 | 02-JAN-02:10 | 887.69 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 10.86 | 98.63 | 02-JAN-02:10 | 887.69 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.47 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 872.73 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 48.71 | 779.88 | 01-JAN-23:30 | 2828.32 | 01-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1145.26 | 2508.07 | 09-NOV-04:00 | 179094.19 | 20-JUL-20:30 |
LowTempRefrigeration:Refrigeration:Electricity | 18.50 | 0.00 | 01-JAN-11:10 | 1553.43 | 29-MAY-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 23.12 | 637.78 | 01-JAN-00:10 | 734.88 | 01-JAN-08:20 |
WaterSystems:Electricity | 90.56 | 1086.42 | 03-OCT-01:00 | 4736.32 | 29-JUN-06:10 |
Water Heater:WaterSystems:Electricity | 90.56 | 1086.42 | 03-OCT-01:00 | 4736.32 | 29-JUN-06:10 |
Fans:Electricity | 667.87 | 11623.73 | 01-JAN-18:00 | 32831.71 | 19-SEP-21:40 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 796.46 | 12484.77 | 27-MAR-13:50 | 36525.03 | 20-OCT-21:20 |
ExteriorEquipment:Electricity | 971.97 | 6508.89 | 02-JAN-02:20 | 62573.78 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.51 | 378.96 | 03-JUN-05:00 | 1274.84 | 02-JAN-07:20 |
ElectricityPurchased:Facility | 5256.62 | 71421.00 | 03-JAN-04:00 | 399062.12 | 02-AUG-19:20 |
ElectricityPurchased:Plant | 5256.62 | 71421.00 | 03-JAN-04:00 | 399062.12 | 02-AUG-19:20 |
Cogeneration:ElectricityPurchased | 5256.62 | 71421.00 | 03-JAN-04:00 | 399062.12 | 02-AUG-19:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5256.62 | 71421.00 | 03-JAN-04:00 | 399062.12 | 02-AUG-19:20 |
ElectricityNet:Plant | 5256.62 | 71421.00 | 03-JAN-04:00 | 399062.12 | 02-AUG-19:20 |
Cogeneration:ElectricityNet | 5256.62 | 71421.00 | 03-JAN-04:00 | 399062.12 | 02-AUG-19:20 |
General:Fans:Electricity | 667.87 | 11623.73 | 01-JAN-18:00 | 32831.71 | 19-SEP-21:40 |
ExteriorLights:Electricity | 182.64 | 0.00 | 01-JAN-07:30 | 11632.50 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 182.64 | 0.00 | 01-JAN-07:30 | 11632.50 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.79 | 01-JAN-00:10 | 187.95 | 01-JAN-07:10 |
HeatRecovery:Electricity | 107.08 | 0.00 | 02-MAR-15:40 | 6004.29 | 01-JAN-00:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 960.62 | 0.00 | 01-JAN-00:10 | 169700.85 | 20-JUL-20:30 |
General:Cooling:Electricity | 960.62 | 0.00 | 01-JAN-00:10 | 169700.85 | 20-JUL-20:30 |
Pumps:Electricity | 52.47 | 47.91 | 03-MAR-18:00 | 3617.18 | 20-JUL-20:20 |
General:Pumps:Electricity | 52.47 | 47.91 | 03-MAR-18:00 | 3617.18 | 20-JUL-20:20 |
WIRED_LTG_ELECTRICITY | 18.52 | 0.00 | 01-JAN-00:10 | 1668.04 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 4257.62 | 29270.80 | 08-APR-01:10 | 377686.38 | 06-FEB-17:10 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 2468.77 | 15908.90 | 07-APR-15:10 | 298909.27 | 05-FEB-23:40 |
WaterSystems:Gas | 2123.02 | 15908.90 | 07-APR-09:00 | 177876.67 | 08-FEB-21:40 |
Water Heater:WaterSystems:Gas | 2123.02 | 15908.90 | 07-APR-09:00 | 177876.67 | 08-FEB-21:40 |
Heating:Gas | 345.75 | 0.00 | 19-JAN-13:50 | 143705.23 | 06-FEB-09:10 |
Boiler:Heating:Gas | 345.75 | 0.00 | 19-JAN-13:50 | 143705.23 | 06-FEB-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3239.21 | 0.00 | 01-JAN-00:10 | 632023.16 | 20-JUL-20:20 |
PlantLoopCoolingDemand:HVAC | 3239.21 | 0.00 | 01-JAN-00:10 | 632023.16 | 20-JUL-20:20 |
CoolingCoils:PlantLoopCoolingDemand | 3239.21 | 0.00 | 01-JAN-00:10 | 632023.16 | 20-JUL-20:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 07-APR-01:00 | 0.00 | 27-MAR-21:00 |
Water:Plant | 22864.31 | 0.00 | 07-APR-01:00 | 0.00 | 27-MAR-21:00 |
WaterSystems:Water | 22864.31 | 0.00 | 07-APR-01:00 | 0.00 | 27-MAR-21:00 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 08-APR-00:50 | 0.00 | 02-JAN-19:10 |
MainsWater:Facility | 22864.31 | 0.00 | 07-APR-01:00 | 0.00 | 27-MAR-21:00 |
MainsWater:Plant | 22864.31 | 0.00 | 07-APR-01:00 | 0.00 | 27-MAR-21:00 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 07-APR-01:00 | 0.00 | 27-MAR-21:00 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 08-APR-00:50 | 0.00 | 02-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 07-APR-01:00 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 07-APR-01:00 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 19359.81 | 107345.55 | 07-MAY-14:00 | 2338933.24 | 20-JUL-20:20 |
EnergyTransfer:Building | 4234.94 | 67540.68 | 01-JAN-14:40 | 281634.08 | 19-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 652.80 | 7283.94 | 01-JAN-00:10 | 34041.00 | 25-MAY-18:20 |
Refrigeration:EnergyTransfer | 213.81 | 4535.18 | 01-JAN-00:10 | 10745.76 | 01-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 106.90 | 2267.59 | 01-JAN-00:10 | 5372.88 | 01-JAN-11:40 |
EnergyTransfer:Plant | 8596.12 | 16018.05 | 19-OCT-00:10 | 1444687.02 | 20-JUL-20:30 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 22.55 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 84.35 | 2008.72 | 01-JAN-00:10 | 2686.44 | 01-JAN-08:20 |
PlantLoopHeatingDemand:Facility | 1001.25 | 8527.42 | 28-AUG-00:10 | 167664.33 | 06-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 743.70 | 8527.42 | 28-AUG-00:10 | 56368.29 | 08-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 743.70 | 8527.42 | 28-AUG-00:10 | 56368.29 | 08-FEB-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 349.25 | 5194.30 | 01-JAN-00:40 | 21853.66 | 21-SEP-06:40 |
Heating:EnergyTransfer | 154.27 | 0.00 | 19-JAN-11:00 | 75855.92 | 14-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 3973.77 | 44210.70 | 01-JAN-00:10 | 277505.59 | 19-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 349.25 | 5194.30 | 01-JAN-00:40 | 21853.66 | 21-SEP-06:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 27.84 | 0.18 | 01-MAR-04:30 | 3002.24 | 13-OCT-12:40 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.91 | 0.00 | 01-JAN-08:50 | 1167.56 | 01-JAN-00:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 26.93 | 0.00 | 01-JAN-00:10 | 3002.24 | 13-OCT-12:40 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 29.59 | 355.51 | 01-JAN-00:10 | 2004.87 | 20-JUN-05:10 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 29.59 | 355.51 | 01-JAN-00:10 | 2004.87 | 20-JUN-05:10 |
EnergyTransfer:Zone:MECH_FLR_1 | 20.63 | 0.54 | 02-JAN-12:20 | 1921.92 | 19-AUG-00:30 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.01 | 0.00 | 01-JAN-07:10 | 263.98 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 20.63 | 0.00 | 01-JAN-00:10 | 1921.92 | 19-AUG-00:30 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.51 | 0.84 | 09-FEB-08:40 | 906.49 | 20-JUN-05:10 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.07 | 0.00 | 03-JAN-07:10 | 346.42 | 01-JAN-00:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 11.44 | 0.00 | 01-JAN-00:10 | 906.49 | 20-JUN-05:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 567.49 | 7924.62 | 01-JAN-00:10 | 37989.68 | 06-JUN-20:10 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 567.49 | 7924.62 | 01-JAN-00:10 | 37989.68 | 06-JUN-20:10 |
EnergyTransfer:Zone:CAFE_FLR_1 | 179.79 | 11.24 | 14-JAN-14:30 | 12094.45 | 13-OCT-12:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 373.59 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 179.79 | 0.00 | 08-JAN-15:30 | 12094.45 | 13-OCT-12:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 637.81 | 8113.80 | 01-JAN-16:00 | 42853.63 | 20-JUN-05:10 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 637.81 | 8113.80 | 01-JAN-16:00 | 42853.63 | 20-JUN-05:10 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 54.73 | 0.00 | 01-JAN-08:00 | 10835.10 | 31-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 16.20 | 0.00 | 01-JAN-08:00 | 6284.20 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 38.53 | 0.00 | 01-JAN-00:10 | 10835.10 | 31-AUG-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 47.92 | 0.00 | 01-JAN-08:00 | 10482.24 | 02-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 20.21 | 0.00 | 01-JAN-08:00 | 6348.24 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 27.71 | 0.00 | 01-JAN-00:10 | 10482.24 | 02-AUG-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 207.25 | 0.00 | 01-JAN-00:10 | 42709.49 | 04-OCT-12:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.11 | 0.00 | 01-JAN-00:10 | 5500.66 | 16-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 207.14 | 0.00 | 01-JAN-00:10 | 42709.49 | 04-OCT-12:10 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 335.30 | 0.00 | 01-JAN-08:00 | 64470.03 | 25-AUG-21:30 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 32.32 | 0.00 | 01-JAN-08:00 | 34033.10 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 302.98 | 0.00 | 01-JAN-00:10 | 64470.03 | 25-AUG-21:30 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 53.77 | 0.00 | 01-JAN-08:00 | 10107.21 | 22-AUG-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 16.02 | 0.00 | 01-JAN-08:00 | 6118.04 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.75 | 0.00 | 01-JAN-00:10 | 10107.21 | 22-AUG-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 47.83 | 0.00 | 01-JAN-08:00 | 10632.04 | 22-AUG-08:20 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 19.91 | 0.00 | 01-JAN-08:00 | 6123.60 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 27.92 | 0.00 | 01-JAN-00:10 | 10632.04 | 22-AUG-08:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 75.96 | 2.98 | 04-MAY-02:20 | 6208.46 | 20-JUN-05:10 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 21.79 | 0.00 | 19-JAN-10:30 | 2965.76 | 01-JAN-00:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 54.17 | 0.00 | 01-JAN-00:10 | 6208.46 | 20-JUN-05:10 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.23 | 0.00 | 01-JAN-08:00 | 2921.43 | 02-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.78 | 0.00 | 01-JAN-08:00 | 1854.93 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.46 | 0.00 | 01-JAN-00:10 | 2921.43 | 02-AUG-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 14.85 | 0.00 | 01-JAN-08:00 | 2904.43 | 02-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.05 | 0.00 | 01-JAN-08:00 | 1852.60 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.80 | 0.00 | 01-JAN-00:10 | 2904.43 | 02-AUG-15:20 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 77.86 | 0.00 | 01-JAN-08:00 | 12413.37 | 04-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 12.76 | 0.00 | 01-JAN-08:00 | 8162.05 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 65.10 | 0.00 | 01-JAN-00:10 | 12413.37 | 04-SEP-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 367.62 | 6240.03 | 01-JAN-16:00 | 22366.66 | 20-JUN-05:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 367.62 | 6240.03 | 01-JAN-16:00 | 22366.66 | 20-JUN-05:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 406.43 | 7066.16 | 01-JAN-16:00 | 23910.42 | 20-JUN-05:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 406.43 | 7066.16 | 01-JAN-16:00 | 23910.42 | 20-JUN-05:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 545.90 | 5016.35 | 01-JAN-00:10 | 29913.43 | 25-MAY-18:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 52.47 | 2.27 | 13-FEB-19:00 | 4823.85 | 08-JUN-17:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.12 | 0.00 | 01-JAN-12:10 | 2196.27 | 01-JAN-00:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 51.36 | 0.00 | 01-JAN-00:10 | 4823.85 | 08-JUN-17:20 |
WaterSystems:EnergyTransfer | 743.70 | 8527.42 | 28-AUG-00:10 | 56368.29 | 08-FEB-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 743.70 | 8527.42 | 28-AUG-00:10 | 56368.29 | 08-FEB-08:00 |
EnergyTransfer:HVAC | 6528.75 | 1094.02 | 03-MAY-12:30 | 684423.46 | 04-AUG-15:20 |
HeatingCoils:EnergyTransfer | 257.55 | 0.00 | 02-FEB-14:10 | 119400.15 | 02-JAN-09:10 |
PlantLoopHeatingDemand:HVAC | 257.55 | 0.00 | 02-FEB-14:10 | 119400.15 | 02-JAN-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 257.55 | 0.00 | 02-FEB-14:10 | 119400.15 | 02-JAN-09:10 |
CoolingCoils:EnergyTransfer | 3239.21 | 0.00 | 01-JAN-00:10 | 632023.16 | 20-JUL-20:20 |
HeatRecoveryForHeating:EnergyTransfer | 2796.35 | 0.00 | 02-MAR-15:40 | 399310.38 | 06-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 235.64 | 0.00 | 01-JAN-00:10 | 191861.26 | 04-AUG-09:50 |
Boilers:EnergyTransfer | 245.76 | 0.00 | 19-JAN-13:50 | 113563.33 | 06-FEB-09:10 |
Chillers:EnergyTransfer | 3269.57 | 0.00 | 01-JAN-00:10 | 618690.90 | 20-JUL-20:30 |
HeatRejection:EnergyTransfer | 4230.19 | 0.00 | 01-JAN-00:10 | 788391.74 | 20-JUL-20:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -349.243 | 0.000 | 0.000 | 126.428 | 134.155 | 143.109 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -54.448 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.913 | -26.927 | 0.000 | 0.000 | 14.329 | 6.674 | 10.186 | 18.546 | 0.000 | 0.217 | 0.000 | 0.000 | -10.543 | 0.000 | -8.618 | -4.778 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -29.594 | 0.000 | 0.000 | 15.391 | 7.729 | 11.795 | 0.000 | 0.000 | 0.050 | 0.000 | 0.000 | 0.000 | 0.000 | -1.965 | -3.406 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -567.479 | 0.000 | 0.000 | 8.778 | 4.900 | 658.148 | 0.000 | 0.000 | 0.122 | 0.000 | 0.000 | 0.000 | 0.000 | -7.032 | -97.437 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.002 | -179.777 | 0.000 | 0.000 | 175.521 | 8.961 | 14.341 | 51.588 | 0.000 | 0.543 | 0.000 | 0.000 | -31.848 | 0.000 | -23.373 | -15.956 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -637.794 | 0.000 | 0.000 | 504.529 | 74.542 | 149.002 | 68.259 | 0.000 | 1.162 | 0.000 | 0.000 | -43.663 | 0.000 | -48.326 | -67.711 |
ROOM_1_FLR_3 | 16.202 | -27.318 | 0.000 | -11.209 | 0.000 | 0.000 | 9.725 | 5.514 | 10.478 | 38.019 | 0.000 | 1.190 | 0.000 | 0.000 | -21.763 | 0.000 | -9.499 | -11.339 |
ROOM_2_FLR_3 | 20.213 | -15.909 | 0.000 | -11.798 | 0.000 | 0.000 | 9.577 | 5.513 | 10.477 | 27.344 | 0.000 | 0.598 | 0.000 | 0.000 | -22.848 | 0.000 | -9.975 | -13.191 |
ROOM_3_MULT19_FLR_3 | 0.109 | -192.644 | 0.000 | -14.500 | 0.000 | 0.000 | 0.000 | 65.838 | 194.997 | 212.792 | 0.000 | 0.575 | 0.001 | 0.000 | -152.212 | 0.000 | -61.675 | -53.278 |
ROOM_4_MULT19_FLR_3 | 32.324 | -145.094 | 0.000 | -157.879 | 0.000 | 0.000 | 182.447 | 65.856 | 195.050 | 71.725 | 0.000 | 5.815 | 0.000 | 0.000 | -130.036 | 0.000 | -64.876 | -55.331 |
ROOM_5_FLR_3 | 16.021 | -26.526 | 0.000 | -11.221 | 0.000 | 0.000 | 9.719 | 5.514 | 10.478 | 37.430 | 0.000 | 1.190 | 0.000 | 0.000 | -21.457 | 0.000 | -9.525 | -11.624 |
ROOM_6_FLR_3 | 19.915 | -16.211 | 0.000 | -11.708 | 0.000 | 0.000 | 9.605 | 5.513 | 10.477 | 26.533 | 0.000 | 0.626 | 0.000 | 0.000 | -22.183 | 0.000 | -9.899 | -12.668 |
ROOM_1_FLR_6 | 5.776 | -7.658 | 0.000 | -2.801 | 0.000 | 0.000 | 2.433 | 1.378 | 2.620 | 9.450 | 0.000 | 0.318 | 0.000 | 0.000 | -5.430 | 0.000 | -2.413 | -3.673 |
ROOM_2_FLR_6 | 7.050 | -4.823 | 0.000 | -2.973 | 0.000 | 0.000 | 2.388 | 1.378 | 2.619 | 6.765 | 0.000 | 0.147 | 0.000 | 0.000 | -5.725 | 0.000 | -2.542 | -4.284 |
ROOM_3_MULT9_FLR_6 | 12.762 | -46.954 | 0.000 | -18.145 | 0.000 | 0.000 | 21.787 | 7.799 | 23.098 | 50.507 | 0.000 | 2.167 | 0.000 | 0.000 | -25.627 | 0.000 | -12.193 | -15.200 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -367.591 | 0.000 | 0.000 | 274.128 | 19.690 | 175.857 | 6.461 | 0.000 | 0.106 | 0.000 | 0.000 | -19.890 | 0.000 | -7.446 | -81.315 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -406.393 | 0.000 | 0.000 | 264.094 | 19.690 | 175.857 | 6.095 | 0.000 | 0.090 | 0.000 | 0.000 | -21.127 | 0.000 | -7.688 | -30.618 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -545.649 | 0.000 | 0.000 | 18.217 | 13.339 | 540.650 | 14.821 | 0.000 | 0.007 | 0.000 | 0.000 | -15.803 | 0.000 | -8.473 | -17.109 |
MECH_FLR_1 | 0.000 | 0.000 | 0.007 | -20.627 | 0.000 | 0.000 | 0.000 | 18.484 | 12.472 | 0.000 | 0.000 | 0.119 | 0.000 | 0.000 | 0.000 | 0.000 | -4.248 | -6.207 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.068 | -11.442 | 0.000 | 0.000 | 0.000 | 1.898 | 3.598 | 0.000 | 0.000 | 0.085 | 8.490 | 0.000 | 0.000 | 0.000 | -2.697 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 21.792 | -54.171 | 0.000 | 0.000 | 0.000 | 41.027 | 0.000 | 34.659 | 0.000 | 0.614 | 0.000 | 0.000 | -26.739 | 0.000 | -10.676 | -6.507 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.116 | -51.355 | 0.000 | 0.000 | 0.000 | 10.855 | 0.000 | 15.571 | 0.000 | 0.117 | 43.111 | 0.000 | -13.922 | 0.000 | -5.493 | -0.000 |
Total Facility | 130.372 | -483.137 | 23.898 | -3490.277 | 0.000 | 0.000 | 1649.095 | 526.246 | 2355.308 | 696.564 | 0.000 | 15.859 | 51.601 | 0.000 | -590.816 | 0.000 | -318.632 | -566.081 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-OCT-11:57 | 0.00 | 0.00 | 0.00 | -34231.17 | 0.00 | 0.00 | 2037.86 | 3656.86 | 4055.80 | 0.00 | 0.00 | 0.00 | 24480.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 13-OCT-12:49 | 0.00 | 0.00 | 0.00 | -4985.04 | 0.00 | 0.00 | 125.95 | 151.61 | 252.59 | 4632.24 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -113.49 | -63.85 |
RETAIL_2_FLR_1 | 10-JUL-23:13 | 0.00 | 0.00 | 0.00 | -3230.80 | 0.00 | 0.00 | 710.70 | 140.45 | 250.72 | 0.00 | 0.00 | 0.00 | 2130.39 | 0.00 | -0.00 | 0.00 | -1.45 | 0.00 |
LAUNDRY_FLR_1 | 30-AUG-19:51 | 0.00 | 0.00 | 0.00 | -72293.62 | 0.00 | 0.00 | 102.22 | 400.68 | 44299.38 | 0.00 | 0.00 | 0.00 | 27600.72 | 0.00 | -0.00 | 0.00 | -109.39 | 0.00 |
CAFE_FLR_1 | 13-OCT-12:05 | 0.00 | 0.00 | 0.00 | -20364.34 | 0.00 | 0.00 | 1635.65 | 67.09 | 355.63 | 15181.39 | 0.00 | 0.00 | 3323.28 | 0.00 | -0.00 | 0.00 | -198.70 | 0.00 |
LOBBY_FLR_1 | 10-JUL-23:13 | 0.00 | 0.00 | 0.00 | -65254.62 | 0.00 | 0.00 | 23302.36 | 1436.28 | 3167.12 | 0.00 | 0.00 | 0.00 | 37929.16 | 0.00 | -511.33 | 0.00 | -68.98 | 0.00 |
ROOM_1_FLR_3 | 27-MAY-18:01 | 0.00 | -12521.94 | 0.00 | -752.30 | 0.00 | 0.00 | 283.21 | 551.08 | 484.65 | 3702.47 | 0.00 | 0.00 | 8488.41 | 0.00 | -0.00 | 0.00 | -235.57 | 0.00 |
ROOM_2_FLR_3 | 27-MAY-21:11 | 0.00 | -12559.48 | 0.00 | -711.67 | 0.00 | 0.00 | 326.10 | 468.36 | 358.18 | 0.00 | 0.00 | 0.00 | 12830.60 | 0.00 | -604.18 | 0.00 | -107.91 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:03 | 0.00 | -42709.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.27 | 2352.88 | 61486.75 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -319.47 | -21221.47 |
ROOM_4_MULT19_FLR_3 | 04-JUN-08:11 | 0.00 | -70875.63 | 0.00 | -10441.64 | 0.00 | 0.00 | 2480.65 | 1535.83 | 12159.85 | 9556.50 | 0.00 | 0.00 | 55654.30 | 0.00 | -0.00 | 0.00 | -69.86 | 0.00 |
ROOM_5_FLR_3 | 10-SEP-18:01 | 0.00 | -11208.62 | 0.00 | -750.54 | 0.00 | 0.00 | 283.21 | 551.08 | 484.65 | 0.00 | 0.00 | 0.00 | 11115.87 | 0.00 | -321.08 | 0.00 | -154.58 | 0.00 |
ROOM_6_FLR_3 | 22-JUN-08:11 | 0.00 | -12155.22 | 0.00 | -1028.83 | 0.00 | 0.00 | 65.35 | 241.07 | 452.99 | 8021.81 | 0.00 | 0.00 | 4445.17 | 0.00 | -0.00 | 0.00 | -42.34 | 0.00 |
ROOM_1_FLR_6 | 27-MAY-18:01 | 0.00 | -3299.44 | 0.00 | -188.30 | 0.00 | 0.00 | 70.80 | 137.77 | 121.16 | 912.70 | 0.00 | 0.00 | 2317.28 | 0.00 | -0.00 | 0.00 | -71.98 | 0.00 |
ROOM_2_FLR_6 | 27-MAY-21:11 | 0.00 | -3466.42 | 0.00 | -192.60 | 0.00 | 0.00 | 76.91 | 117.09 | 89.55 | 0.00 | 0.00 | 0.00 | 3582.44 | 0.00 | -174.22 | 0.00 | -32.75 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10-SEP-18:01 | 0.00 | -13431.29 | 0.00 | -1217.32 | 0.00 | 0.00 | 637.23 | 779.46 | 1068.37 | 0.00 | 0.00 | 0.00 | 12942.05 | 0.00 | -361.72 | 0.00 | -416.79 | 0.00 |
BANQUET_FLR_6 | 23-JUN-21:51 | 0.00 | 0.00 | 0.00 | -34311.07 | 0.00 | 0.00 | 11896.40 | 1285.18 | 6747.90 | 0.00 | 0.00 | 0.00 | 14701.96 | 0.00 | -249.04 | 0.00 | -71.32 | 0.00 |
DINING_FLR_6 | 23-JUN-21:51 | 0.00 | 0.00 | 0.00 | -37022.65 | 0.00 | 0.00 | 11419.42 | 1285.18 | 6747.90 | 0.00 | 0.00 | 0.00 | 17943.62 | 0.00 | -296.04 | 0.00 | -77.42 | 0.00 |
KITCHEN_FLR_6 | 31-MAY-17:41 | 0.00 | 0.00 | 0.00 | -50198.22 | 0.00 | 0.00 | 173.72 | 727.22 | 26450.81 | 245.46 | 0.00 | 0.00 | 22756.03 | 0.00 | -0.00 | 0.00 | -155.01 | 0.00 |
MECH_FLR_1 | 10-JUL-23:18 | 0.00 | 0.00 | 0.00 | -3260.01 | 0.00 | 0.00 | 0.00 | 335.90 | 265.09 | 0.00 | 0.00 | 3.10 | 2655.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 10-JUL-23:18 | 0.00 | 0.00 | 0.00 | -1319.60 | 0.00 | 0.00 | 0.00 | 34.49 | 76.47 | 0.00 | 0.00 | 1.94 | 1206.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 20-AUG-14:49 | 0.00 | 0.00 | 0.00 | -9788.79 | 0.00 | 0.00 | 0.00 | 745.56 | 0.00 | 3355.31 | 0.00 | 156.77 | 5531.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 20-AUG-14:49 | 0.00 | 0.00 | 0.00 | -8554.09 | 0.00 | 0.00 | 0.00 | 197.26 | 0.00 | 1420.19 | 0.00 | 36.62 | 6900.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 22-JUN-18:01 | 0.00 | -142260.81 | 0.00 | -317406.93 | 0.00 | 0.00 | 61797.59 | 39282.31 | 120174.13 | 33171.46 | 0.00 | 3165.81 | 202123.75 | 0.00 | 0.00 | 0.00 | -47.32 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 02-JAN-07:20 | 0.00 | 0.00 | 2036.89 | -0.00 | 0.00 | 0.00 | 379.51 | 303.22 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1258.39 | 0.00 | -836.99 | -1057.24 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 02-JAN-07:04 | 0.00 | 0.00 | 2519.27 | -0.00 | 0.00 | 0.00 | 4656.22 | 609.87 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3725.28 | 0.00 | -2208.32 | -2461.41 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 14-JAN-16:11 | 6636.93 | 271.52 | 0.00 | -271.52 | 0.00 | 0.00 | 163.32 | 34.44 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2396.06 | 0.00 | -776.89 | -3883.00 |
ROOM_2_FLR_3 | 14-JAN-16:11 | 6615.53 | 271.17 | 0.00 | -271.17 | 0.00 | 0.00 | 163.32 | 34.44 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2409.17 | 0.00 | -776.68 | -3848.66 |
ROOM_3_MULT19_FLR_3 | 16-JAN-05:51 | 5500.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.52 | 3333.24 | 0.00 | 0.00 | 0.00 | 5458.19 | 0.00 | -11487.48 | 0.00 | -3298.27 | 0.00 |
ROOM_4_MULT19_FLR_3 | 14-JAN-16:11 | 35794.49 | 3622.88 | 0.00 | -3622.88 | 0.00 | 0.00 | 3103.15 | 411.38 | 4118.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13421.66 | 0.00 | -4108.96 | -25897.06 |
ROOM_5_FLR_3 | 14-JAN-16:11 | 6365.46 | 270.27 | 0.00 | -270.27 | 0.00 | 0.00 | 163.32 | 34.44 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2432.07 | 0.00 | -776.37 | -3576.04 |
ROOM_6_FLR_3 | 14-JAN-16:11 | 6364.65 | 270.00 | 0.00 | -270.00 | 0.00 | 0.00 | 163.32 | 34.44 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2445.08 | 0.00 | -776.21 | -3562.35 |
ROOM_1_FLR_6 | 14-JAN-16:11 | 1921.95 | 67.87 | 0.00 | -67.87 | 0.00 | 0.00 | 40.83 | 8.61 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -598.83 | 0.00 | -194.73 | -1233.15 |
ROOM_2_FLR_6 | 14-JAN-16:11 | 1917.53 | 67.77 | 0.00 | -67.77 | 0.00 | 0.00 | 40.83 | 8.61 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -602.68 | 0.00 | -194.67 | -1224.93 |
ROOM_3_MULT9_FLR_6 | 14-JAN-16:11 | 8478.21 | 433.80 | 0.00 | -433.80 | 0.00 | 0.00 | 367.48 | 48.72 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2802.01 | 0.00 | -895.65 | -5684.48 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 02-JAN-04:52 | 0.00 | 0.00 | 530.37 | -0.00 | 0.00 | 0.00 | 0.00 | 167.95 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -412.34 | -462.72 |
STORAGE_FLR_1 | 02-JAN-06:02 | 0.00 | 0.00 | 611.55 | -0.00 | 0.00 | 0.00 | 0.00 | 68.99 | 127.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -278.36 | -529.63 |
CORRIDOR_FLR_3 | 02-JAN-06:02 | 0.00 | 0.00 | 5563.39 | -0.00 | 0.00 | 0.00 | 0.00 | 1491.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3710.01 | 0.00 | -1202.19 | -2142.32 |
CORRIDOR_FLR_6 | 02-JAN-06:02 | 0.00 | 0.00 | 3645.40 | -0.00 | 0.00 | 0.00 | 0.00 | 394.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1682.57 | 0.00 | -541.52 | -1815.83 |
Total Facility | 14-JAN-16:12 | -60691.00 | 138597.18 | 10149.13 | -138597.18 | 0.00 | 0.00 | 31029.77 | 9491.80 | 74529.96 | 0.00 | 0.00 | 0.00 | 14871.15 | 0.00 | -56559.34 | 0.00 | -22821.47 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 19.5172 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 18.9311 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.8471 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 10.5256 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1990 | 2.1990 | 1.2820 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2841 | 0.2841 | 0.1188 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2068 | 0.2068 | 0.1375 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2534 | 3.2534 | 0.0325 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2224 | 1.2224 | 1.0146 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0721 | 4.0721 | 2.8382 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0046 | 2.0046 | 1.7801 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1077 | 2.1077 | 1.7810 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1545 | 2.1545 | 0.5515 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2176 | 0.2176 | 0.0022 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0878 | 0.0878 | 0.0866 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 0.7121 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5203 | 0.5203 | 0.1884 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 19.5172 | 18.9311 | 19.5172 | 10.5256 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2820 | 1.2820 | 1.2820 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1421 | 0.1421 | 0.1188 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1375 | 0.1375 | 0.1375 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6267 | 1.6267 | 0.0325 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0146 | 1.0146 | 1.0146 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8382 | 2.8382 | 2.8382 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7801 | 1.7801 | 1.7801 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7810 | 1.7810 | 1.7810 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0772 | 1.0772 | 0.5515 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1088 | 0.1088 | 0.0022 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0866 | 0.0866 | 0.0866 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7121 | 0.7121 | 0.7121 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2602 | 0.2602 | 0.1884 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.8471 | 10.5256 | 10.5256 | 10.5256 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:28
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 25.17 |
Number of hours cooling loads not met | 8756.00 |
Number of hours not met | 8756.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 345.75 | 143705.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 960.62 | 169700.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 526.25 | 47387.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 182.64 | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.73 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.51 | 1274.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 187.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 667.87 | 32831.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 52.47 | 3617.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 107.08 | 6004.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.56 | 4736.32 | 2123.02 | 177876.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 18.50 | 1553.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 23.12 | 734.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1697.18 | 5256.62 |
Natural Gas | 1788.85 | 4257.62 |
Additional | 0.00 | 0.00 |
Total | 3486.03 | 9514.24 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.38 |
Space Heating | 0.00 |
Space Cooling | 84.67 |
Fans (All) | 58.87 |
Service Water Heating | 7.98 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 463.33 |
Subtotal | 463.33 |
Natural Gas [MJ/m2] | |
Space Heating | 30.47 |
Service Water Heating | 187.13 |
Miscellaneous (All) | 375.28 |
Subtotal | 375.28 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.53 |
Space Heating | 3.63 |
Space Cooling | 10.10 |
Fans (All) | 7.02 |
Service Water Heating | 23.27 |
Receptacle Equipment | 36.13 |
Miscellaneous | 14.32 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 1660. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 2221. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2737. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1362. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.976081E+11 |
February | 0.000 | 0.898620E+11 |
March | 0.000 | 0.366673E+11 |
April | 0.000 | 0.145458E+11 |
May | 0.000 | 0.232654E+10 |
June | 0.000 | 0.991179E+08 |
July | 0.000 | 0.309218E+08 |
August | 0.000 | 0.162854E+09 |
September | 0.000 | 0.412024E+09 |
October | 0.000 | 0.325862E+10 |
November | 0.000 | 0.358510E+11 |
December | 0.000 | 0.649218E+11 |
Annual Sum or Average | 0.345746E+12 | |
Minimum of Months | 0.000 | 0.309218E+08 |
Maximum of Months | 0.000 | 0.976081E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.976081E+11 |
February | 0.000 | 0.898620E+11 |
March | 0.000 | 0.366673E+11 |
April | 0.000 | 0.145458E+11 |
May | 0.000 | 0.232654E+10 |
June | 0.000 | 0.991179E+08 |
July | 0.000 | 0.309218E+08 |
August | 0.000 | 0.162854E+09 |
September | 0.000 | 0.412024E+09 |
October | 0.000 | 0.325862E+10 |
November | 0.000 | 0.358510E+11 |
December | 0.000 | 0.649218E+11 |
Annual Sum or Average | 0.345746E+12 | |
Minimum of Months | 0.000 | 0.309218E+08 |
Maximum of Months | 0.000 | 0.976081E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.976081E+11 |
February | 0.000 | 0.898620E+11 |
March | 0.000 | 0.366673E+11 |
April | 0.000 | 0.145458E+11 |
May | 0.000 | 0.232654E+10 |
June | 0.000 | 0.991179E+08 |
July | 0.000 | 0.309218E+08 |
August | 0.000 | 0.162854E+09 |
September | 0.000 | 0.412024E+09 |
October | 0.000 | 0.325862E+10 |
November | 0.000 | 0.358510E+11 |
December | 0.000 | 0.649218E+11 |
Annual Sum or Average | 0.345746E+12 | |
Minimum of Months | 0.000 | 0.309218E+08 |
Maximum of Months | 0.000 | 0.976081E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.976081E+11 |
February | 0.000 | 0.898620E+11 |
March | 0.000 | 0.366673E+11 |
April | 0.000 | 0.145458E+11 |
May | 0.000 | 0.232654E+10 |
June | 0.000 | 0.991179E+08 |
July | 0.000 | 0.309218E+08 |
August | 0.000 | 0.162854E+09 |
September | 0.000 | 0.412024E+09 |
October | 0.000 | 0.325862E+10 |
November | 0.000 | 0.358510E+11 |
December | 0.000 | 0.649218E+11 |
Annual Sum or Average | 0.345746E+12 | |
Minimum of Months | 0.000 | 0.309218E+08 |
Maximum of Months | 0.000 | 0.976081E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.976081E+11 |
February | 0.000 | 0.898620E+11 |
March | 0.000 | 0.366673E+11 |
April | 0.000 | 0.145458E+11 |
May | 0.000 | 0.232654E+10 |
June | 0.000 | 0.991179E+08 |
July | 0.000 | 0.309218E+08 |
August | 0.000 | 0.162854E+09 |
September | 0.000 | 0.412024E+09 |
October | 0.000 | 0.325862E+10 |
November | 0.000 | 0.358510E+11 |
December | 0.000 | 0.649218E+11 |
Annual Sum or Average | 0.345746E+12 | |
Minimum of Months | 0.000 | 0.309218E+08 |
Maximum of Months | 0.000 | 0.976081E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.976081E+11 |
February | 0.000 | 0.898620E+11 |
March | 0.000 | 0.366673E+11 |
April | 0.000 | 0.145458E+11 |
May | 0.000 | 0.232654E+10 |
June | 0.000 | 0.991179E+08 |
July | 0.000 | 0.309218E+08 |
August | 0.000 | 0.162854E+09 |
September | 0.000 | 0.412024E+09 |
October | 0.000 | 0.325862E+10 |
November | 0.000 | 0.358510E+11 |
December | 0.000 | 0.649218E+11 |
Annual Sum or Average | 0.345746E+12 | |
Minimum of Months | 0.000 | 0.309218E+08 |
Maximum of Months | 0.000 | 0.976081E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.976081E+11 |
February | 0.000 | 0.898620E+11 |
March | 0.000 | 0.366673E+11 |
April | 0.000 | 0.145458E+11 |
May | 0.000 | 0.232654E+10 |
June | 0.000 | 0.991179E+08 |
July | 0.000 | 0.309218E+08 |
August | 0.000 | 0.162854E+09 |
September | 0.000 | 0.412024E+09 |
October | 0.000 | 0.325862E+10 |
November | 0.000 | 0.358510E+11 |
December | 0.000 | 0.649218E+11 |
Annual Sum or Average | 0.345746E+12 | |
Minimum of Months | 0.000 | 0.309218E+08 |
Maximum of Months | 0.000 | 0.976081E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.976081E+11 |
February | 0.000 | 0.898620E+11 |
March | 0.000 | 0.366673E+11 |
April | 0.000 | 0.145458E+11 |
May | 0.000 | 0.232654E+10 |
June | 0.000 | 0.991179E+08 |
July | 0.000 | 0.309218E+08 |
August | 0.000 | 0.162854E+09 |
September | 0.000 | 0.412024E+09 |
October | 0.000 | 0.325862E+10 |
November | 0.000 | 0.358510E+11 |
December | 0.000 | 0.649218E+11 |
Annual Sum or Average | 0.345746E+12 | |
Minimum of Months | 0.000 | 0.309218E+08 |
Maximum of Months | 0.000 | 0.976081E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.976081E+11 |
February | 0.000 | 0.898620E+11 |
March | 0.000 | 0.366673E+11 |
April | 0.000 | 0.145458E+11 |
May | 0.000 | 0.232654E+10 |
June | 0.000 | 0.991179E+08 |
July | 0.000 | 0.309218E+08 |
August | 0.000 | 0.162854E+09 |
September | 0.000 | 0.412024E+09 |
October | 0.000 | 0.325862E+10 |
November | 0.000 | 0.358510E+11 |
December | 0.000 | 0.649218E+11 |
Annual Sum or Average | 0.345746E+12 | |
Minimum of Months | 0.000 | 0.309218E+08 |
Maximum of Months | 0.000 | 0.976081E+11 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275898E+11 | 23025.11 | 23-JAN-22:00 | 10.60 | 10.26 | 0.903191E+10 | 5703.09 | 20-JAN-22:10 | 3.72 | 3.02 |
February | 0.241196E+11 | 22490.38 | 01-FEB-22:00 | 5.00 | 2.84 | 0.795394E+10 | 5642.29 | 01-FEB-22:10 | 4.90 | 2.78 |
March | 0.255090E+11 | 29374.41 | 27-MAR-18:53 | 18.30 | 13.17 | 0.859974E+10 | 5336.29 | 01-MAR-22:10 | 5.50 | 4.48 |
April | 0.241505E+11 | 28852.17 | 16-APR-19:07 | 18.53 | 12.45 | 0.819083E+10 | 5265.73 | 14-APR-21:10 | 6.70 | 5.12 |
May | 0.249192E+11 | 29739.13 | 31-MAY-20:51 | 20.60 | 17.62 | 0.833722E+10 | 5219.15 | 01-MAY-21:10 | 9.50 | 5.24 |
June | 0.272318E+11 | 30761.82 | 23-JUN-20:51 | 22.80 | 20.82 | 0.807200E+10 | 5157.10 | 02-JUN-21:10 | 15.60 | 9.68 |
July | 0.308940E+11 | 31358.66 | 11-JUL-23:37 | 21.30 | 18.26 | 0.833915E+10 | 5207.44 | 20-JUL-21:10 | 27.12 | 25.09 |
August | 0.337214E+11 | 32080.50 | 19-AUG-00:57 | 21.70 | 16.47 | 0.850209E+10 | 5284.16 | 16-AUG-21:10 | 26.60 | 25.03 |
September | 0.342021E+11 | 32958.60 | 10-SEP-00:55 | 21.70 | 18.76 | 0.846601E+10 | 5605.88 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.346238E+11 | 34232.71 | 22-OCT-11:57 | 21.10 | 16.23 | 0.955203E+10 | 6134.27 | 30-OCT-21:10 | 8.80 | 3.74 |
November | 0.315817E+11 | 33057.14 | 04-NOV-15:59 | 17.80 | 11.29 | 0.966835E+10 | 6194.21 | 22-NOV-22:10 | -1.1 | -3.3 |
December | 0.307024E+11 | 25169.36 | 01-DEC-22:00 | 1.10 | -2.0 | 0.971122E+10 | 6148.61 | 01-DEC-22:10 | 1.20 | -2.0 |
Annual Sum or Average | 0.349245E+12 | 0.104424E+12 | ||||||||
Minimum of Months | 0.241196E+11 | 22490.38 | 1.10 | -2.0 | 0.795394E+10 | 5157.10 | -1.1 | -3.3 | ||
Maximum of Months | 0.346238E+11 | 34232.71 | 22.80 | 20.82 | 0.971122E+10 | 6194.21 | 27.12 | 25.09 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.604545E+09 | 3064.73 | 17-JAN-13:42 | 10.92 | 5.21 | 0.649720E+09 | 474.65 | 19-JAN-22:10 | 5.60 | 1.05 |
February | 0.686005E+09 | 2882.33 | 02-FEB-13:30 | 6.15 | 0.23 | 0.598701E+09 | 450.92 | 22-FEB-22:10 | 2.20 | -0.9 |
March | 0.119738E+10 | 4282.31 | 03-MAR-13:25 | 14.70 | 8.31 | 0.720461E+09 | 495.42 | 27-MAR-21:10 | 14.13 | 10.86 |
April | 0.158808E+10 | 4523.39 | 07-APR-12:04 | 25.78 | 15.55 | 0.740329E+09 | 511.04 | 07-APR-21:10 | 19.22 | 13.75 |
May | 0.234049E+10 | 4234.50 | 30-MAY-11:19 | 29.07 | 17.32 | 0.821390E+09 | 514.34 | 30-MAY-21:10 | 19.32 | 15.30 |
June | 0.337841E+10 | 4298.81 | 22-JUN-15:19 | 30.20 | 17.77 | 0.820534E+09 | 562.15 | 19-JUN-21:10 | 28.72 | 20.61 |
July | 0.415159E+10 | 4251.88 | 11-JUL-15:03 | 28.30 | 17.50 | 0.857976E+09 | 558.25 | 10-JUL-21:10 | 27.12 | 20.10 |
August | 0.434768E+10 | 4680.14 | 30-AUG-13:26 | 28.05 | 15.53 | 0.879611E+09 | 581.02 | 04-AUG-21:10 | 31.55 | 23.91 |
September | 0.336391E+10 | 4910.46 | 28-SEP-12:43 | 22.88 | 13.71 | 0.824914E+09 | 558.64 | 01-SEP-21:10 | 26.60 | 18.07 |
October | 0.302357E+10 | 4985.35 | 13-OCT-12:49 | 21.88 | 17.79 | 0.845648E+09 | 538.15 | 04-OCT-21:10 | 17.12 | 15.79 |
November | 0.135165E+10 | 4467.23 | 04-NOV-12:05 | 17.80 | 12.51 | 0.707710E+09 | 494.86 | 02-NOV-21:10 | 12.62 | 7.04 |
December | 0.893653E+09 | 3526.18 | 17-DEC-13:00 | 12.20 | 4.93 | 0.677064E+09 | 476.47 | 18-DEC-22:10 | 2.20 | 0.94 |
Annual Sum or Average | 0.269270E+11 | 0.914406E+10 | ||||||||
Minimum of Months | 0.604545E+09 | 2882.33 | 6.15 | 0.23 | 0.598701E+09 | 450.92 | 2.20 | -0.9 | ||
Maximum of Months | 0.434768E+10 | 4985.35 | 30.20 | 17.79 | 0.879611E+09 | 581.02 | 31.55 | 23.91 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155723E+10 | 1929.70 | 19-JAN-22:00 | 5.60 | 1.05 | 0.933769E+09 | 624.66 | 19-JAN-22:10 | 5.60 | 1.05 |
February | 0.146425E+10 | 1890.87 | 02-FEB-22:00 | -2.2 | -5.6 | 0.858077E+09 | 616.71 | 02-FEB-22:10 | -2.3 | -5.7 |
March | 0.196156E+10 | 2791.05 | 27-MAR-18:53 | 18.30 | 13.17 | 0.987648E+09 | 649.39 | 03-MAR-22:10 | 10.50 | 6.38 |
April | 0.221657E+10 | 2941.11 | 07-APR-23:20 | 17.60 | 13.18 | 0.970166E+09 | 655.81 | 28-APR-21:10 | 10.60 | 7.57 |
May | 0.274786E+10 | 3102.39 | 31-MAY-20:51 | 20.60 | 17.62 | 0.101458E+10 | 659.88 | 11-MAY-21:10 | 12.20 | 10.07 |
June | 0.311129E+10 | 3197.17 | 22-JUN-23:13 | 24.23 | 15.65 | 0.990737E+09 | 671.33 | 19-JUN-21:10 | 28.72 | 20.61 |
July | 0.338194E+10 | 3231.14 | 10-JUL-23:13 | 24.83 | 18.49 | 0.103313E+10 | 680.15 | 20-JUL-21:10 | 27.12 | 25.09 |
August | 0.345901E+10 | 3215.62 | 19-AUG-00:57 | 21.70 | 16.47 | 0.105258E+10 | 691.35 | 16-AUG-22:10 | 26.10 | 25.32 |
September | 0.304437E+10 | 3209.87 | 01-SEP-23:57 | 25.00 | 17.03 | 0.989580E+09 | 671.97 | 01-SEP-21:10 | 26.60 | 18.07 |
October | 0.286573E+10 | 3049.62 | 05-OCT-23:45 | 18.98 | 18.21 | 0.103564E+10 | 668.73 | 04-OCT-21:10 | 17.12 | 15.79 |
November | 0.202143E+10 | 2725.07 | 04-NOV-12:05 | 17.80 | 12.51 | 0.959803E+09 | 656.72 | 03-NOV-21:10 | 12.80 | 10.16 |
December | 0.176293E+10 | 1953.48 | 18-DEC-22:00 | 2.20 | 1.01 | 0.966035E+09 | 628.66 | 18-DEC-22:10 | 2.20 | 0.94 |
Annual Sum or Average | 0.295942E+11 | 0.117917E+11 | ||||||||
Minimum of Months | 0.146425E+10 | 1890.87 | -2.2 | -5.6 | 0.858077E+09 | 616.71 | -2.3 | -5.7 | ||
Maximum of Months | 0.345901E+10 | 3231.14 | 25.00 | 18.49 | 0.105258E+10 | 691.35 | 28.72 | 25.32 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204059E+09 | 1813.81 | 23-JAN-22:00 | 10.60 | 10.26 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.146403E+09 | 1718.12 | 24-FEB-20:52 | 1.10 | -2.5 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.692311E+09 | 2750.00 | 27-MAR-19:27 | 17.20 | 12.60 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.134601E+10 | 2805.64 | 10-APR-19:12 | 17.40 | 9.12 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.219263E+10 | 3106.88 | 29-MAY-21:07 | 21.78 | 17.01 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.288451E+10 | 3208.47 | 22-JUN-23:13 | 24.23 | 15.65 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.336791E+10 | 3260.09 | 10-JUL-23:18 | 24.83 | 18.49 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.338263E+10 | 3239.84 | 19-AUG-00:57 | 21.70 | 16.47 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.266696E+10 | 3171.99 | 01-SEP-23:57 | 25.00 | 17.03 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.224077E+10 | 2983.83 | 03-OCT-20:01 | 19.90 | 17.46 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.108294E+10 | 2657.05 | 04-NOV-18:23 | 15.85 | 10.89 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.420046E+09 | 1806.31 | 04-DEC-22:00 | 7.80 | 7.49 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.206272E+11 | 0.00 | ||||||||
Minimum of Months | 0.146403E+09 | 1718.12 | 1.10 | -2.5 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.338263E+10 | 3260.09 | 25.00 | 18.49 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.502097E+09 | 603.57 | 24-JAN-11:54 | 12.20 | 11.93 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.464162E+09 | 534.06 | 20-FEB-15:56 | 7.20 | 4.43 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.720327E+09 | 1082.68 | 27-MAR-13:33 | 20.93 | 16.67 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.852708E+09 | 1175.46 | 08-APR-14:53 | 21.70 | 15.01 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.110839E+10 | 1221.11 | 30-MAY-11:19 | 29.07 | 17.32 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.128784E+10 | 1282.79 | 22-JUN-23:13 | 24.23 | 15.65 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.139465E+10 | 1319.62 | 10-JUL-23:18 | 24.83 | 18.49 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.140739E+10 | 1311.42 | 19-AUG-00:57 | 21.70 | 16.47 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.122611E+10 | 1298.38 | 01-SEP-13:39 | 30.93 | 17.67 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.105255E+10 | 1194.49 | 13-OCT-10:24 | 21.15 | 17.55 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.757962E+09 | 1070.60 | 04-NOV-15:59 | 17.80 | 11.29 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.667900E+09 | 599.85 | 17-DEC-14:14 | 12.20 | 5.34 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.114421E+11 | 0.00 | ||||||||
Minimum of Months | 0.464162E+09 | 534.06 | 7.20 | 4.43 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.140739E+10 | 1319.62 | 30.93 | 18.49 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.451503E+11 | 61820.14 | 19-JAN-20:52 | 3.90 | 0.78 | 0.804402E+09 | 746.89 | 19-JAN-22:10 | 5.60 | 1.05 |
February | 0.408460E+11 | 61594.71 | 17-FEB-20:52 | 1.10 | -0.7 | 0.729153E+09 | 742.30 | 02-FEB-22:10 | -2.3 | -5.7 |
March | 0.465672E+11 | 67329.82 | 27-MAR-19:41 | 16.47 | 12.21 | 0.820435E+09 | 834.04 | 06-MAR-22:10 | 9.82 | 5.93 |
April | 0.460843E+11 | 67777.36 | 10-APR-19:11 | 17.40 | 9.12 | 0.787018E+09 | 761.62 | 11-APR-21:10 | 9.22 | 1.64 |
May | 0.494164E+11 | 71735.91 | 31-MAY-20:01 | 20.10 | 17.77 | 0.807993E+09 | 837.52 | 11-MAY-21:10 | 12.20 | 10.07 |
June | 0.489466E+11 | 72271.66 | 23-JUN-19:51 | 23.30 | 21.43 | 0.760159E+09 | 810.58 | 02-JUN-21:10 | 15.60 | 9.68 |
July | 0.507255E+11 | 66890.50 | 10-JUL-19:52 | 28.30 | 20.23 | 0.758182E+09 | 703.31 | 20-JUL-21:10 | 27.12 | 25.09 |
August | 0.512697E+11 | 72353.04 | 30-AUG-19:51 | 23.90 | 17.14 | 0.782447E+09 | 768.62 | 28-AUG-21:10 | 19.90 | 14.70 |
September | 0.485554E+11 | 71314.41 | 08-SEP-19:51 | 20.00 | 17.43 | 0.765844E+09 | 827.20 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.489570E+11 | 71291.00 | 03-OCT-19:51 | 20.00 | 17.43 | 0.816039E+09 | 853.81 | 30-OCT-21:10 | 8.80 | 3.74 |
November | 0.452615E+11 | 63549.66 | 03-NOV-19:52 | 12.80 | 10.92 | 0.788313E+09 | 753.32 | 01-NOV-21:10 | 9.90 | 5.48 |
December | 0.457057E+11 | 61904.27 | 19-DEC-20:52 | 8.30 | 3.93 | 0.810013E+09 | 746.29 | 20-DEC-22:10 | 4.32 | 1.21 |
Annual Sum or Average | 0.567485E+12 | 0.943000E+10 | ||||||||
Minimum of Months | 0.408460E+11 | 61594.71 | 1.10 | -0.7 | 0.729153E+09 | 703.31 | -2.3 | -5.7 | ||
Maximum of Months | 0.512697E+11 | 72353.04 | 28.30 | 21.43 | 0.820435E+09 | 853.81 | 27.12 | 25.09 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.993180E+10 | 13826.88 | 17-JAN-13:32 | 10.73 | 5.29 | 0.102135E+11 | 7059.10 | 19-JAN-22:40 | 5.60 | 1.05 |
February | 0.960049E+10 | 13134.56 | 02-FEB-13:24 | 6.15 | 0.23 | 0.941176E+10 | 6867.91 | 22-FEB-22:40 | 2.20 | -0.7 |
March | 0.121743E+11 | 18143.29 | 03-MAR-13:25 | 14.70 | 8.31 | 0.110147E+11 | 7520.03 | 03-MAR-22:40 | 10.20 | 6.22 |
April | 0.132307E+11 | 18865.21 | 08-APR-11:53 | 24.40 | 16.23 | 0.108306E+11 | 7446.27 | 07-APR-21:49 | 18.48 | 13.48 |
May | 0.160742E+11 | 18067.49 | 31-MAY-23:03 | 19.08 | 17.29 | 0.113883E+11 | 7463.52 | 31-MAY-22:10 | 19.78 | 17.35 |
June | 0.182756E+11 | 19047.23 | 22-JUN-23:13 | 24.23 | 15.65 | 0.112639E+11 | 7797.98 | 19-JUN-21:19 | 28.53 | 20.49 |
July | 0.201570E+11 | 19301.03 | 10-JUL-23:13 | 24.83 | 18.49 | 0.118752E+11 | 7858.66 | 20-JUL-21:19 | 27.03 | 25.01 |
August | 0.207581E+11 | 19127.97 | 24-AUG-23:13 | 22.60 | 13.48 | 0.121610E+11 | 8046.07 | 16-AUG-22:10 | 26.10 | 25.32 |
September | 0.184487E+11 | 20307.29 | 30-SEP-12:46 | 20.50 | 12.36 | 0.113897E+11 | 7828.04 | 01-SEP-21:19 | 26.50 | 17.93 |
October | 0.175805E+11 | 20367.19 | 13-OCT-12:05 | 22.62 | 18.07 | 0.119948E+11 | 7757.13 | 12-OCT-21:19 | 15.93 | 15.93 |
November | 0.124032E+11 | 19108.02 | 04-NOV-12:05 | 17.80 | 12.51 | 0.107300E+11 | 7564.12 | 02-NOV-21:40 | 12.07 | 6.86 |
December | 0.111525E+11 | 15913.49 | 17-DEC-13:00 | 12.20 | 4.93 | 0.106622E+11 | 7032.96 | 18-DEC-22:40 | 2.20 | 0.71 |
Annual Sum or Average | 0.179787E+12 | 0.132936E+12 | ||||||||
Minimum of Months | 0.960049E+10 | 13134.56 | 6.15 | 0.23 | 0.941176E+10 | 6867.91 | 2.20 | -0.7 | ||
Maximum of Months | 0.207581E+11 | 20367.19 | 24.83 | 18.49 | 0.121610E+11 | 8046.07 | 28.53 | 25.32 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389052E+11 | 40733.00 | 19-JAN-23:00 | 5.60 | 1.05 | 0.330333E+11 | 22030.87 | 19-JAN-23:10 | 5.60 | 1.05 |
February | 0.366211E+11 | 39770.96 | 22-FEB-23:00 | 2.20 | -0.6 | 0.301439E+11 | 21637.35 | 22-FEB-23:10 | 2.20 | -0.6 |
March | 0.453268E+11 | 56198.81 | 27-MAR-18:53 | 18.30 | 13.17 | 0.346471E+11 | 22818.66 | 03-MAR-23:10 | 9.82 | 6.11 |
April | 0.483240E+11 | 60154.49 | 07-APR-23:20 | 17.60 | 13.18 | 0.339202E+11 | 22720.50 | 28-APR-22:10 | 10.50 | 7.90 |
May | 0.569753E+11 | 61964.38 | 31-MAY-23:03 | 19.08 | 17.29 | 0.352223E+11 | 22758.86 | 15-MAY-22:10 | 10.60 | 7.46 |
June | 0.629615E+11 | 64813.87 | 22-JUN-23:13 | 24.23 | 15.65 | 0.341965E+11 | 22894.28 | 19-JUN-21:00 | 27.80 | 20.01 |
July | 0.681543E+11 | 65265.93 | 10-JUL-23:13 | 24.83 | 18.49 | 0.356692E+11 | 23292.36 | 20-JUL-21:19 | 27.03 | 25.01 |
August | 0.694014E+11 | 64933.63 | 19-AUG-00:57 | 21.70 | 16.47 | 0.361922E+11 | 23737.07 | 16-AUG-22:10 | 26.10 | 25.32 |
September | 0.624803E+11 | 65235.02 | 01-SEP-23:57 | 25.00 | 17.03 | 0.342391E+11 | 22965.52 | 01-SEP-22:10 | 26.10 | 17.29 |
October | 0.592610E+11 | 62286.38 | 05-OCT-23:45 | 18.98 | 18.21 | 0.361411E+11 | 23251.61 | 30-OCT-21:30 | 8.60 | 3.95 |
November | 0.461260E+11 | 56730.23 | 04-NOV-12:05 | 17.80 | 12.51 | 0.337952E+11 | 23013.96 | 02-NOV-22:10 | 11.60 | 6.69 |
December | 0.432726E+11 | 41055.58 | 17-DEC-13:00 | 12.20 | 4.93 | 0.339604E+11 | 22040.13 | 19-DEC-22:30 | 5.00 | 2.82 |
Annual Sum or Average | 0.637809E+12 | 0.411160E+12 | ||||||||
Minimum of Months | 0.366211E+11 | 39770.96 | 2.20 | -0.6 | 0.301439E+11 | 21637.35 | 2.20 | -0.6 | ||
Maximum of Months | 0.694014E+11 | 65265.93 | 25.00 | 18.49 | 0.361922E+11 | 23737.07 | 27.80 | 25.32 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11532548.43 | 3218.18 | 17-JAN-16:11 | 8.90 | 4.26 | 93154196.00 | 56.69 | 14-JAN-04:00 | -7.2 | -7.8 |
February | 22311059.28 | 3219.11 | 02-FEB-16:11 | 3.87 | -2.1 | 84659983.15 | 56.69 | 13-FEB-03:49 | -8.8 | -10.7 |
March | 0.147451E+09 | 3257.54 | 15-MAR-15:11 | 14.80 | 5.95 | 95742282.73 | 56.69 | 03-MAR-22:10 | 10.50 | 6.38 |
April | 0.398416E+09 | 3275.57 | 10-APR-18:01 | 19.22 | 9.98 | 93730017.99 | 59.67 | 25-APR-18:10 | 16.32 | 11.26 |
May | 0.866810E+09 | 3318.47 | 27-MAY-18:01 | 21.02 | 11.60 | 98439173.31 | 56.69 | 31-MAY-02:30 | 16.95 | 15.09 |
June | 0.161945E+10 | 3075.83 | 17-JUN-15:11 | 23.30 | 20.38 | 96220720.95 | 56.69 | 26-JUN-04:49 | 20.60 | 16.93 |
July | 0.210783E+10 | 3107.87 | 22-JUL-15:11 | 26.70 | 23.39 | 99538967.14 | 56.69 | 14-JUL-21:10 | 21.70 | 20.94 |
August | 0.224026E+10 | 3056.43 | 29-AUG-18:01 | 23.22 | 18.30 | 99623504.54 | 56.69 | 29-AUG-03:49 | 16.78 | 14.04 |
September | 0.132169E+10 | 3314.91 | 10-SEP-18:01 | 21.52 | 11.56 | 95788766.36 | 56.69 | 14-SEP-21:00 | 22.80 | 16.23 |
October | 0.796752E+09 | 3258.72 | 08-OCT-15:11 | 12.20 | 5.82 | 98334716.54 | 56.69 | 06-OCT-00:20 | 18.90 | 18.13 |
November | 83824277.00 | 3236.31 | 02-NOV-15:11 | 16.50 | 8.77 | 92028016.24 | 56.69 | 03-NOV-21:19 | 12.80 | 10.19 |
December | 15351162.28 | 3142.94 | 17-DEC-16:11 | 9.63 | 4.15 | 93722874.43 | 56.69 | 31-DEC-05:00 | -1.7 | -4.3 |
Annual Sum or Average | 0.963168E+10 | 0.114098E+10 | ||||||||
Minimum of Months | 11532548.43 | 3056.43 | 3.87 | -2.1 | 84659983.15 | 56.69 | -8.8 | -10.7 | ||
Maximum of Months | 0.224026E+10 | 3318.47 | 26.70 | 23.39 | 99623504.54 | 59.67 | 22.80 | 20.94 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3386645.81 | 2262.48 | 17-JAN-16:11 | 8.90 | 4.26 | 92406818.79 | 56.69 | 08-JAN-04:30 | -5.3 | -7.7 |
February | 5901584.13 | 2882.39 | 20-FEB-16:11 | 7.03 | 4.34 | 83675264.95 | 56.69 | 14-FEB-05:10 | -4.4 | -6.6 |
March | 76616367.19 | 3192.60 | 15-MAR-15:11 | 14.80 | 5.95 | 94820728.58 | 58.39 | 27-MAR-18:10 | 18.80 | 14.34 |
April | 0.267882E+09 | 3208.43 | 11-APR-15:11 | 15.00 | 5.11 | 94272719.65 | 71.47 | 07-APR-21:19 | 19.03 | 13.69 |
May | 0.645230E+09 | 3318.00 | 27-MAY-21:11 | 19.23 | 10.67 | 0.102517E+09 | 81.15 | 31-MAY-21:19 | 20.37 | 17.53 |
June | 0.122935E+10 | 3123.71 | 22-JUN-08:11 | 24.80 | 16.37 | 0.105783E+09 | 84.93 | 26-JUN-18:10 | 24.22 | 20.03 |
July | 0.168212E+10 | 3027.48 | 20-JUL-18:01 | 27.62 | 24.84 | 0.109873E+09 | 86.16 | 05-JUL-18:10 | 24.72 | 22.65 |
August | 0.175065E+10 | 3158.26 | 28-AUG-21:11 | 19.80 | 14.66 | 0.108964E+09 | 87.16 | 10-AUG-18:10 | 24.22 | 20.65 |
September | 0.857017E+09 | 3290.65 | 10-SEP-21:11 | 17.43 | 10.25 | 0.102404E+09 | 83.04 | 07-SEP-21:10 | 23.80 | 21.51 |
October | 0.378510E+09 | 3190.51 | 07-OCT-15:11 | 12.40 | 5.41 | 99802560.16 | 69.80 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 26184103.13 | 3035.63 | 01-NOV-15:11 | 13.70 | 7.22 | 90964506.02 | 56.69 | 02-NOV-21:10 | 12.62 | 7.04 |
December | 4093329.68 | 905.89 | 17-DEC-16:11 | 9.63 | 4.15 | 92563420.65 | 56.69 | 15-DEC-05:10 | -2.9 | -5.0 |
Annual Sum or Average | 0.692694E+10 | 0.117805E+10 | ||||||||
Minimum of Months | 3386645.81 | 905.89 | 7.03 | 4.15 | 83675264.95 | 56.69 | -5.3 | -7.7 | ||
Maximum of Months | 0.175065E+10 | 3318.00 | 27.62 | 24.84 | 0.109873E+09 | 87.16 | 24.72 | 22.65 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6332619.51 | 125.77 | 31-JAN-15:01 | -1.6 | -5.7 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 10684634.49 | 150.28 | 20-FEB-15:01 | 8.12 | 4.60 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 22970505.76 | 205.71 | 15-MAR-15:03 | 14.90 | 6.01 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 80238560.26 | 368.33 | 08-APR-12:21 | 23.60 | 16.17 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.192555E+09 | 266.01 | 22-MAY-15:03 | 21.83 | 14.14 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.362481E+09 | 327.13 | 19-JUN-20:12 | 29.63 | 21.57 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.493186E+09 | 339.79 | 08-JUL-07:52 | 28.30 | 24.27 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.562623E+09 | 387.22 | 30-AUG-12:32 | 27.03 | 15.26 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.431245E+09 | 511.27 | 28-SEP-12:21 | 23.05 | 14.06 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.433779E+09 | 561.97 | 04-OCT-12:01 | 24.50 | 18.62 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 99799665.43 | 488.25 | 02-NOV-12:21 | 15.30 | 8.09 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 29690539.97 | 287.68 | 21-DEC-13:22 | 3.05 | -1.4 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.272559E+10 | 0.00 | ||||||||
Minimum of Months | 6332619.51 | 125.77 | -1.6 | -5.7 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.562623E+09 | 561.97 | 29.63 | 24.27 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28199092.30 | 865.28 | 22-JAN-09:01 | 5.10 | 4.57 | 94342345.74 | 56.69 | 23-JAN-23:10 | 10.50 | 10.22 |
February | 19462049.43 | 878.74 | 25-FEB-09:01 | -2.0 | -5.2 | 85152264.61 | 56.69 | 16-FEB-22:10 | 3.30 | 0.62 |
March | 0.111326E+09 | 946.99 | 15-MAR-18:01 | 13.12 | 4.92 | 95836236.43 | 56.69 | 27-MAR-21:10 | 14.13 | 10.86 |
April | 0.263615E+09 | 995.40 | 11-APR-18:01 | 12.52 | 3.44 | 94218222.45 | 69.80 | 07-APR-21:19 | 19.03 | 13.69 |
May | 0.452655E+09 | 1061.27 | 27-MAY-21:11 | 19.23 | 10.67 | 0.100719E+09 | 76.26 | 31-MAY-21:19 | 20.37 | 17.53 |
June | 0.608976E+09 | 1069.98 | 04-JUN-08:11 | 22.57 | 12.57 | 0.102065E+09 | 79.96 | 15-JUN-21:10 | 23.40 | 21.81 |
July | 0.779581E+09 | 1001.00 | 11-JUL-18:01 | 26.73 | 16.70 | 0.107375E+09 | 81.60 | 21-JUL-21:10 | 25.60 | 23.68 |
August | 0.743432E+09 | 1019.83 | 28-AUG-21:11 | 19.80 | 14.66 | 0.105885E+09 | 80.73 | 03-AUG-21:10 | 26.02 | 24.78 |
September | 0.502117E+09 | 1037.09 | 10-SEP-21:11 | 17.43 | 10.25 | 0.100223E+09 | 78.92 | 07-SEP-21:10 | 23.80 | 21.51 |
October | 0.313716E+09 | 995.08 | 25-OCT-21:11 | 16.83 | 7.69 | 98464143.52 | 68.15 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 0.131591E+09 | 956.66 | 02-NOV-18:01 | 13.80 | 7.35 | 92716573.81 | 56.69 | 02-NOV-21:19 | 12.43 | 6.98 |
December | 31850727.74 | 913.29 | 02-DEC-09:01 | 2.38 | -1.4 | 94625549.05 | 56.69 | 26-DEC-22:10 | 5.40 | 1.94 |
Annual Sum or Average | 0.398652E+10 | 0.117162E+10 | ||||||||
Minimum of Months | 19462049.43 | 865.28 | -2.0 | -5.2 | 85152264.61 | 56.69 | 3.30 | 0.62 | ||
Maximum of Months | 0.779581E+09 | 1069.98 | 26.73 | 16.70 | 0.107375E+09 | 81.60 | 26.02 | 24.78 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16745471.64 | 2622.67 | 20-JAN-09:01 | 5.40 | 0.61 | 93140510.68 | 56.69 | 14-JAN-02:30 | -5.5 | -6.2 |
February | 25145872.33 | 2847.22 | 25-FEB-09:01 | -2.0 | -5.2 | 84763753.38 | 56.69 | 13-FEB-01:49 | -7.8 | -10.0 |
March | 0.121248E+09 | 2924.93 | 15-MAR-15:11 | 14.80 | 5.95 | 95720041.98 | 56.69 | 03-MAR-22:10 | 10.50 | 6.38 |
April | 0.393349E+09 | 2954.31 | 12-APR-08:61 | 5.78 | 0.37 | 93946194.69 | 56.69 | 07-APR-23:00 | 17.20 | 13.07 |
May | 0.886614E+09 | 2981.56 | 27-MAY-18:01 | 21.02 | 11.60 | 98708788.40 | 56.69 | 28-MAY-23:49 | 15.78 | 14.25 |
June | 0.150989E+10 | 2784.82 | 08-JUN-15:11 | 22.03 | 16.07 | 96299155.96 | 56.69 | 22-JUN-22:40 | 24.60 | 15.70 |
July | 0.206733E+10 | 2814.76 | 17-JUL-08:61 | 26.38 | 20.83 | 99566569.81 | 56.69 | 28-JUL-22:10 | 24.32 | 20.84 |
August | 0.220780E+10 | 2821.05 | 13-AUG-08:61 | 26.38 | 19.12 | 99678869.62 | 56.69 | 03-AUG-23:40 | 24.60 | 23.85 |
September | 0.131997E+10 | 2989.53 | 10-SEP-18:01 | 21.52 | 11.56 | 95935117.86 | 56.69 | 01-SEP-23:00 | 25.00 | 17.03 |
October | 0.747187E+09 | 2926.86 | 07-OCT-15:11 | 12.40 | 5.41 | 98520102.38 | 56.69 | 06-OCT-00:20 | 18.90 | 18.13 |
November | 0.111852E+09 | 2885.51 | 02-NOV-15:11 | 16.50 | 8.77 | 92287938.23 | 56.69 | 03-NOV-21:19 | 12.80 | 10.19 |
December | 29686449.52 | 2692.07 | 02-DEC-09:01 | 2.38 | -1.4 | 93809103.56 | 56.69 | 31-DEC-04:10 | -1.1 | -3.7 |
Annual Sum or Average | 0.943682E+10 | 0.114238E+10 | ||||||||
Minimum of Months | 16745471.64 | 2622.67 | -2.0 | -5.2 | 84763753.38 | 56.69 | -7.8 | -10.0 | ||
Maximum of Months | 0.220780E+10 | 2989.53 | 26.38 | 20.83 | 99678869.62 | 56.69 | 25.00 | 23.85 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3502493.85 | 622.33 | 24-JAN-19:04 | 10.00 | 8.53 | 92408016.25 | 56.69 | 11-JAN-00:20 | -3.3 | -5.5 |
February | 7016661.96 | 2689.41 | 25-FEB-09:01 | -2.0 | -5.2 | 83746536.65 | 56.69 | 06-FEB-03:00 | -13.3 | -14.7 |
March | 63828262.79 | 2655.70 | 23-MAR-08:61 | -0.8 | -4.3 | 94619489.75 | 56.69 | 03-MAR-22:10 | 10.50 | 6.38 |
April | 0.285839E+09 | 2964.97 | 08-APR-08:11 | 20.57 | 15.12 | 94034398.09 | 69.27 | 07-APR-21:19 | 19.03 | 13.69 |
May | 0.700989E+09 | 3285.27 | 30-MAY-08:11 | 25.37 | 16.09 | 0.101750E+09 | 76.99 | 31-MAY-21:19 | 20.37 | 17.53 |
June | 0.118736E+10 | 3295.66 | 22-JUN-08:11 | 24.80 | 16.37 | 0.103528E+09 | 78.83 | 15-JUN-21:10 | 23.40 | 21.81 |
July | 0.166859E+10 | 3167.21 | 11-JUL-08:11 | 23.17 | 16.17 | 0.108902E+09 | 81.29 | 21-JUL-21:10 | 25.60 | 23.68 |
August | 0.174414E+10 | 3254.63 | 22-AUG-08:11 | 27.07 | 18.46 | 0.107878E+09 | 82.45 | 03-AUG-21:10 | 26.02 | 24.78 |
September | 0.899026E+09 | 3195.66 | 10-SEP-08:11 | 19.27 | 13.31 | 0.101255E+09 | 79.31 | 05-SEP-21:10 | 23.90 | 20.41 |
October | 0.372579E+09 | 2734.80 | 25-OCT-21:11 | 16.83 | 7.69 | 98935900.56 | 67.54 | 05-OCT-21:19 | 18.90 | 17.68 |
November | 41273941.57 | 2480.52 | 04-NOV-08:61 | 12.57 | 9.41 | 91191930.78 | 56.69 | 02-NOV-21:10 | 12.62 | 7.04 |
December | 5610364.13 | 2024.56 | 17-DEC-09:01 | 6.05 | 2.93 | 92633210.27 | 56.69 | 31-DEC-03:30 | -0.9 | -3.4 |
Annual Sum or Average | 0.697975E+10 | 0.117088E+10 | ||||||||
Minimum of Months | 3502493.85 | 622.33 | -2.0 | -5.2 | 83746536.65 | 56.69 | -13.3 | -14.7 | ||
Maximum of Months | 0.174414E+10 | 3295.66 | 27.07 | 18.46 | 0.108902E+09 | 82.45 | 26.02 | 24.78 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5655682.31 | 598.22 | 19-JAN-13:54 | 9.40 | 3.68 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 32191146.04 | 829.95 | 20-FEB-15:42 | 7.38 | 4.47 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.224369E+09 | 1857.95 | 27-MAR-17:14 | 20.37 | 15.14 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.735645E+09 | 2069.84 | 08-APR-14:53 | 21.70 | 15.01 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.152456E+10 | 2131.88 | 30-MAY-13:15 | 29.80 | 17.62 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.217097E+10 | 2271.31 | 20-JUN-15:17 | 26.67 | 17.25 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.240906E+10 | 2338.35 | 12-JUL-12:29 | 28.90 | 18.31 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.246193E+10 | 2447.20 | 20-AUG-14:49 | 27.98 | 15.83 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.204979E+10 | 2417.59 | 01-SEP-13:39 | 30.93 | 17.67 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.156589E+10 | 2115.71 | 05-OCT-11:36 | 22.43 | 18.09 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.306143E+09 | 1774.87 | 04-NOV-15:59 | 17.80 | 11.29 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 56446564.64 | 959.06 | 17-DEC-14:24 | 12.20 | 5.38 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.135426E+11 | 0.00 | ||||||||
Minimum of Months | 5655682.31 | 598.22 | 7.38 | 3.68 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.246193E+10 | 2447.20 | 30.93 | 18.31 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10895465.75 | 3380.47 | 17-JAN-16:11 | 8.90 | 4.26 | 92785375.68 | 56.69 | 06-JAN-01:49 | -5.1 | -7.1 |
February | 22844696.61 | 3373.64 | 02-FEB-16:11 | 3.87 | -2.1 | 84320773.30 | 56.69 | 14-FEB-02:30 | -5.0 | -7.1 |
March | 0.157552E+09 | 3417.44 | 15-MAR-15:11 | 14.80 | 5.95 | 95435619.71 | 56.69 | 27-MAR-21:10 | 14.13 | 10.86 |
April | 0.441361E+09 | 3437.35 | 10-APR-18:01 | 19.22 | 9.98 | 93633765.97 | 63.80 | 25-APR-18:10 | 16.32 | 11.26 |
May | 0.989241E+09 | 3487.66 | 27-MAY-18:01 | 21.02 | 11.60 | 98545401.15 | 56.69 | 31-MAY-21:00 | 19.90 | 17.34 |
June | 0.179580E+10 | 3255.43 | 25-JUN-15:11 | 26.50 | 22.76 | 96233288.93 | 56.69 | 19-JUN-23:49 | 24.78 | 21.20 |
July | 0.231072E+10 | 3283.83 | 22-JUL-15:11 | 26.70 | 23.39 | 99547971.50 | 56.69 | 25-JUL-21:30 | 22.50 | 20.73 |
August | 0.242104E+10 | 3240.39 | 15-AUG-18:01 | 26.42 | 20.40 | 99626545.12 | 56.69 | 09-AUG-00:49 | 18.90 | 16.06 |
September | 0.140999E+10 | 3483.22 | 10-SEP-18:01 | 21.52 | 11.56 | 95774394.44 | 56.69 | 05-SEP-21:49 | 23.90 | 19.95 |
October | 0.815266E+09 | 3418.13 | 08-OCT-15:11 | 12.20 | 5.82 | 98220436.03 | 56.69 | 30-OCT-21:00 | 8.30 | 4.24 |
November | 72332253.46 | 3393.71 | 02-NOV-15:11 | 16.50 | 8.77 | 91566735.56 | 56.69 | 03-NOV-21:30 | 12.80 | 10.23 |
December | 11874075.58 | 3352.52 | 17-DEC-16:11 | 9.63 | 4.15 | 93240012.13 | 56.69 | 07-DEC-01:19 | -1.1 | -2.9 |
Annual Sum or Average | 0.104589E+11 | 0.113893E+10 | ||||||||
Minimum of Months | 10895465.75 | 3240.39 | 3.87 | -2.1 | 84320773.30 | 56.69 | -5.1 | -7.1 | ||
Maximum of Months | 0.242104E+10 | 3487.66 | 26.70 | 23.39 | 99626545.12 | 63.80 | 24.78 | 21.20 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1341302.49 | 1791.22 | 17-JAN-16:11 | 8.90 | 4.26 | 92157377.19 | 56.69 | 02-JAN-04:19 | -11.9 | -13.2 |
February | 2946072.50 | 2888.34 | 20-FEB-16:11 | 7.03 | 4.34 | 83421706.45 | 56.69 | 05-FEB-04:19 | -2.4 | -4.5 |
March | 74165201.25 | 3334.59 | 11-MAR-16:11 | 11.30 | 5.46 | 94519615.20 | 61.97 | 27-MAR-18:10 | 18.80 | 14.34 |
April | 0.297623E+09 | 3488.02 | 09-APR-17:31 | 15.37 | 13.32 | 94418781.46 | 76.17 | 07-APR-18:10 | 22.98 | 15.46 |
May | 0.761910E+09 | 3659.20 | 27-MAY-21:11 | 19.23 | 10.67 | 0.103890E+09 | 90.41 | 31-MAY-21:10 | 20.48 | 17.57 |
June | 0.143902E+10 | 3317.44 | 20-JUN-21:11 | 20.93 | 17.06 | 0.107858E+09 | 92.18 | 26-JUN-21:10 | 22.20 | 19.61 |
July | 0.191839E+10 | 3288.06 | 04-JUL-21:11 | 21.50 | 18.54 | 0.111375E+09 | 94.20 | 05-JUL-21:10 | 22.70 | 21.96 |
August | 0.196013E+10 | 3345.46 | 28-AUG-21:11 | 19.80 | 14.66 | 0.110309E+09 | 96.14 | 10-AUG-18:10 | 24.22 | 20.65 |
September | 0.943613E+09 | 3551.87 | 10-SEP-21:11 | 17.43 | 10.25 | 0.103728E+09 | 89.61 | 07-SEP-21:10 | 23.80 | 21.51 |
October | 0.374932E+09 | 3341.96 | 07-OCT-15:11 | 12.40 | 5.41 | 0.100149E+09 | 72.54 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 19609637.16 | 3124.77 | 01-NOV-15:11 | 13.70 | 7.22 | 90538309.34 | 56.69 | 03-NOV-21:10 | 12.80 | 10.16 |
December | 2322329.48 | 864.31 | 25-DEC-16:13 | 9.40 | 7.10 | 92173067.92 | 56.69 | 15-DEC-05:00 | -3.3 | -5.3 |
Annual Sum or Average | 0.779601E+10 | 0.118454E+10 | ||||||||
Minimum of Months | 1341302.49 | 864.31 | 7.03 | 4.26 | 83421706.45 | 56.69 | -11.9 | -13.2 | ||
Maximum of Months | 0.196013E+10 | 3659.20 | 21.50 | 18.54 | 0.111375E+09 | 96.14 | 24.22 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 95692114.12 | 1587.90 | 31-JAN-16:11 | -1.5 | -5.6 | 95089477.79 | 56.69 | 19-JAN-22:30 | 5.60 | 1.05 |
February | 0.128192E+09 | 1594.28 | 02-FEB-16:11 | 3.87 | -2.1 | 86775052.61 | 56.69 | 17-FEB-22:10 | 2.02 | 0.23 |
March | 0.221936E+09 | 1592.76 | 13-MAR-15:11 | 7.03 | 1.44 | 96846205.97 | 56.69 | 15-MAR-21:30 | 9.45 | 3.06 |
April | 0.316253E+09 | 1591.84 | 11-APR-15:11 | 15.00 | 5.11 | 94256225.62 | 56.69 | 07-APR-22:19 | 18.13 | 13.35 |
May | 0.555074E+09 | 1621.86 | 20-MAY-18:01 | 22.02 | 11.69 | 98629719.86 | 56.69 | 31-MAY-02:30 | 16.95 | 15.09 |
June | 0.929555E+09 | 1526.54 | 01-JUN-18:01 | 27.70 | 16.08 | 96154107.65 | 56.69 | 22-JUN-23:40 | 24.07 | 15.74 |
July | 0.128114E+10 | 1515.30 | 03-JUL-15:11 | 27.77 | 21.76 | 99566760.85 | 56.69 | 24-JUL-21:10 | 22.98 | 20.54 |
August | 0.137586E+10 | 1527.54 | 18-AUG-18:01 | 29.27 | 19.97 | 99643450.38 | 56.69 | 25-AUG-00:40 | 21.47 | 13.58 |
September | 0.100130E+10 | 1627.50 | 10-SEP-18:01 | 21.52 | 11.56 | 95931967.10 | 56.69 | 02-SEP-02:30 | 23.60 | 16.71 |
October | 0.884465E+09 | 1605.39 | 25-OCT-15:12 | 22.77 | 10.18 | 98813914.48 | 56.69 | 14-OCT-02:00 | 14.40 | 13.43 |
November | 0.263623E+09 | 1505.58 | 24-NOV-16:11 | 1.30 | -2.0 | 93988931.35 | 56.69 | 03-NOV-21:10 | 12.80 | 10.16 |
December | 0.180177E+09 | 1586.91 | 15-DEC-16:11 | 4.23 | 0.73 | 95811073.45 | 56.69 | 19-DEC-22:30 | 5.00 | 2.82 |
Annual Sum or Average | 0.723326E+10 | 0.115151E+10 | ||||||||
Minimum of Months | 95692114.12 | 1505.58 | -1.5 | -5.6 | 86775052.61 | 56.69 | 2.02 | 0.23 | ||
Maximum of Months | 0.137586E+10 | 1627.50 | 29.27 | 21.76 | 99643450.38 | 56.69 | 24.07 | 20.54 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251119E+11 | 23965.73 | 23-JAN-23:00 | 10.60 | 10.26 | 0.216286E+11 | 14601.47 | 24-JAN-00:10 | 10.00 | 10.00 |
February | 0.227080E+11 | 23325.28 | 23-FEB-23:02 | 4.90 | 4.18 | 0.195999E+11 | 14468.90 | 23-FEB-23:10 | 4.90 | 4.18 |
March | 0.275309E+11 | 29638.47 | 27-MAR-18:53 | 18.30 | 13.17 | 0.228312E+11 | 15100.77 | 28-MAR-22:10 | 7.70 | 5.12 |
April | 0.291385E+11 | 31477.60 | 07-APR-23:25 | 17.50 | 13.15 | 0.224457E+11 | 15211.93 | 28-APR-23:10 | 10.00 | 7.19 |
May | 0.336287E+11 | 33436.31 | 31-MAY-21:11 | 20.37 | 17.53 | 0.231677E+11 | 15335.28 | 11-MAY-22:10 | 12.12 | 9.99 |
June | 0.356228E+11 | 34256.48 | 23-JUN-21:51 | 22.80 | 21.20 | 0.222572E+11 | 15174.87 | 02-JUN-22:10 | 15.50 | 9.66 |
July | 0.375713E+11 | 33702.24 | 10-JUL-23:13 | 24.83 | 18.49 | 0.232079E+11 | 15322.28 | 20-JUL-21:19 | 27.03 | 25.01 |
August | 0.376065E+11 | 33847.25 | 30-AUG-21:51 | 21.70 | 17.71 | 0.233415E+11 | 15553.15 | 16-AUG-22:10 | 26.10 | 25.32 |
September | 0.342898E+11 | 33273.01 | 01-SEP-23:57 | 25.00 | 17.03 | 0.220108E+11 | 15070.73 | 29-SEP-22:40 | 12.57 | 10.55 |
October | 0.317239E+11 | 32284.64 | 03-OCT-21:11 | 19.23 | 17.43 | 0.230200E+11 | 15166.75 | 17-OCT-22:10 | 9.32 | 4.05 |
November | 0.268042E+11 | 28478.67 | 10-NOV-06:47 | 15.40 | 15.40 | 0.219708E+11 | 15045.59 | 01-NOV-22:10 | 9.40 | 5.17 |
December | 0.258859E+11 | 23700.89 | 04-DEC-23:02 | 8.22 | 7.50 | 0.220769E+11 | 14636.85 | 04-DEC-23:10 | 8.22 | 7.50 |
Annual Sum or Average | 0.367622E+12 | 0.267558E+12 | ||||||||
Minimum of Months | 0.227080E+11 | 23325.28 | 4.90 | 4.18 | 0.195999E+11 | 14468.90 | 4.90 | 4.05 | ||
Maximum of Months | 0.376065E+11 | 34256.48 | 25.00 | 21.20 | 0.233415E+11 | 15553.15 | 27.03 | 25.32 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287138E+11 | 26644.89 | 23-JAN-23:00 | 10.60 | 10.26 | 0.226962E+11 | 15250.69 | 24-JAN-00:10 | 10.00 | 10.00 |
February | 0.259703E+11 | 25920.93 | 23-FEB-23:02 | 4.90 | 4.18 | 0.205696E+11 | 15116.06 | 23-FEB-23:10 | 4.90 | 4.18 |
March | 0.309145E+11 | 32395.86 | 27-MAR-16:27 | 21.65 | 15.86 | 0.238561E+11 | 15642.68 | 28-MAR-22:10 | 7.70 | 5.12 |
April | 0.322948E+11 | 33987.89 | 07-APR-23:25 | 17.50 | 13.15 | 0.233148E+11 | 15729.08 | 28-APR-22:10 | 10.50 | 7.90 |
May | 0.368731E+11 | 36196.63 | 31-MAY-21:11 | 20.37 | 17.53 | 0.239619E+11 | 15921.32 | 11-MAY-22:10 | 12.12 | 9.99 |
June | 0.386907E+11 | 36963.04 | 23-JUN-21:51 | 22.80 | 21.20 | 0.229083E+11 | 15704.12 | 02-JUN-22:10 | 15.50 | 9.66 |
July | 0.406427E+11 | 36080.57 | 10-JUL-23:13 | 24.83 | 18.49 | 0.238112E+11 | 15739.13 | 20-JUL-21:19 | 27.03 | 25.01 |
August | 0.406866E+11 | 36493.44 | 30-AUG-21:51 | 21.70 | 17.71 | 0.239462E+11 | 15929.66 | 16-AUG-22:10 | 26.10 | 25.32 |
September | 0.373211E+11 | 35613.89 | 01-SEP-23:57 | 25.00 | 17.03 | 0.226577E+11 | 15578.76 | 29-SEP-22:10 | 13.12 | 10.81 |
October | 0.348665E+11 | 34972.50 | 03-OCT-21:11 | 19.23 | 17.43 | 0.238003E+11 | 15732.28 | 30-OCT-22:10 | 8.22 | 4.04 |
November | 0.300036E+11 | 30744.85 | 10-NOV-06:47 | 15.40 | 15.40 | 0.229013E+11 | 15571.97 | 01-NOV-22:10 | 9.40 | 5.17 |
December | 0.294510E+11 | 26266.55 | 04-DEC-23:02 | 8.22 | 7.50 | 0.231685E+11 | 15263.49 | 04-DEC-23:10 | 8.22 | 7.50 |
Annual Sum or Average | 0.406429E+12 | 0.277592E+12 | ||||||||
Minimum of Months | 0.259703E+11 | 25920.93 | 4.90 | 4.18 | 0.205696E+11 | 15116.06 | 4.90 | 4.04 | ||
Maximum of Months | 0.406866E+11 | 36963.04 | 25.00 | 21.20 | 0.239619E+11 | 15929.66 | 27.03 | 25.32 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.413770E+11 | 39824.82 | 19-JAN-19:04 | 5.82 | 1.54 | 0.196390E+11 | 11915.72 | 21-JAN-18:00 | 7.20 | 6.67 |
February | 0.375648E+11 | 40009.72 | 19-FEB-11:42 | 7.88 | 4.26 | 0.177522E+11 | 11923.34 | 18-FEB-18:00 | 2.80 | 1.19 |
March | 0.436143E+11 | 46195.98 | 27-MAR-16:51 | 21.10 | 15.40 | 0.197562E+11 | 11953.20 | 11-MAR-18:00 | 6.70 | 4.16 |
April | 0.442004E+11 | 48103.20 | 07-APR-10:41 | 23.03 | 14.32 | 0.191310E+11 | 12037.22 | 08-APR-17:00 | 15.60 | 13.00 |
May | 0.485562E+11 | 50055.38 | 31-MAY-17:41 | 21.88 | 18.87 | 0.197471E+11 | 12083.72 | 13-MAY-17:00 | 12.80 | 8.06 |
June | 0.488510E+11 | 49989.07 | 23-JUN-17:51 | 25.00 | 21.53 | 0.190204E+11 | 12030.53 | 03-JUN-17:00 | 17.80 | 13.60 |
July | 0.508746E+11 | 47769.06 | 11-JUL-15:51 | 28.30 | 17.16 | 0.196155E+11 | 11892.91 | 08-JUL-17:00 | 24.40 | 23.27 |
August | 0.513165E+11 | 49857.55 | 19-AUG-18:01 | 23.12 | 17.93 | 0.196774E+11 | 12015.45 | 19-AUG-17:00 | 23.30 | 18.00 |
September | 0.480596E+11 | 49152.57 | 04-SEP-18:11 | 23.70 | 18.94 | 0.190339E+11 | 12018.54 | 30-SEP-17:00 | 16.70 | 13.46 |
October | 0.471568E+11 | 48203.76 | 03-OCT-18:01 | 20.00 | 18.16 | 0.197569E+11 | 12008.26 | 14-OCT-17:00 | 16.70 | 15.97 |
November | 0.421449E+11 | 45400.80 | 04-NOV-10:51 | 17.20 | 11.72 | 0.190946E+11 | 11944.07 | 04-NOV-17:10 | 17.52 | 10.87 |
December | 0.421801E+11 | 40700.38 | 17-DEC-11:42 | 11.93 | 4.45 | 0.196929E+11 | 11926.46 | 16-DEC-18:00 | 6.70 | 2.69 |
Annual Sum or Average | 0.545896E+12 | 0.231917E+12 | ||||||||
Minimum of Months | 0.375648E+11 | 39824.82 | 5.82 | 1.54 | 0.177522E+11 | 11892.91 | 2.80 | 1.19 | ||
Maximum of Months | 0.513165E+11 | 50055.38 | 28.30 | 21.53 | 0.197569E+11 | 12083.72 | 24.40 | 23.27 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.894409E+09 | 1383.82 | 17-JAN-14:00 | 11.10 | 5.13 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.920525E+09 | 1455.37 | 20-FEB-13:54 | 8.90 | 4.50 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.185735E+10 | 5818.67 | 27-MAR-13:32 | 20.93 | 16.67 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.308834E+10 | 7812.48 | 08-APR-14:53 | 21.70 | 15.01 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.532290E+10 | 8119.56 | 30-MAY-13:15 | 29.80 | 17.62 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.740504E+10 | 8241.26 | 20-JUN-14:17 | 27.20 | 17.59 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.860375E+10 | 8354.53 | 11-JUL-15:03 | 28.30 | 17.50 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.863892E+10 | 8553.86 | 20-AUG-14:49 | 27.98 | 15.83 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.645590E+10 | 8455.88 | 01-SEP-13:39 | 30.93 | 17.67 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.479463E+10 | 7858.49 | 13-OCT-12:49 | 21.88 | 17.79 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.202959E+10 | 7022.55 | 04-NOV-12:05 | 17.80 | 12.51 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.134384E+10 | 1590.48 | 17-DEC-13:44 | 12.20 | 5.21 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.513552E+11 | 0.00 | ||||||||
Minimum of Months | 0.894409E+09 | 1383.82 | 8.90 | 4.50 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.863892E+10 | 8553.86 | 30.93 | 17.79 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449949E+09 | 2036.96 | 02-JAN-07:20 | -11.5 |
February | 0.294094E+09 | 1969.56 | 06-FEB-07:12 | -13.1 |
March | 26776098.74 | 956.39 | 18-MAR-06:02 | -1.7 |
April | 91779.05 | 64.00 | 02-APR-04:52 | 3.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 17275022.76 | 857.74 | 23-NOV-05:52 | -3.9 |
December | 0.124359E+09 | 1204.16 | 11-DEC-14:56 | 1.10 |
Annual Sum or Average | 0.912544E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.1 | |
Maximum of Months | 0.449949E+09 | 2036.96 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7303617.42 | 530.37 | 02-JAN-04:52 | -12.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 7303617.42 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 7303617.42 | 530.37 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52512186.06 | 611.55 | 02-JAN-06:02 | -11.7 |
February | 15854778.96 | 362.52 | 07-FEB-04:52 | -8.9 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 68366965.02 | |||
Minimum of Months | 0.00 | 0.00 | -11.7 | |
Maximum of Months | 52512186.06 | 611.55 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1502838.48 | 2519.68 | 02-JAN-07:04 | -11.6 |
February | 13189.87 | 219.83 | 06-FEB-07:06 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 1516028.35 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 1502838.48 | 2519.68 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114253E+10 | 1659.20 | 14-JAN-16:11 | -6.1 |
February | 0.940200E+09 | 1644.33 | 06-FEB-19:01 | -8.2 |
March | 0.421931E+09 | 1627.33 | 16-MAR-15:11 | 0.77 |
April | 0.174731E+09 | 1590.37 | 21-APR-15:11 | 7.40 |
May | 9804318.15 | 1485.09 | 11-MAY-08:03 | 13.98 |
June | 849521.86 | 1127.29 | 03-JUN-08:03 | 16.57 |
July | 128041.21 | 621.57 | 12-JUL-08:04 | 26.28 |
August | 611481.16 | 825.88 | 28-AUG-08:04 | 23.17 |
September | 2134847.04 | 1236.46 | 23-SEP-08:03 | 13.30 |
October | 30795430.89 | 1464.46 | 30-OCT-18:03 | 12.02 |
November | 0.468518E+09 | 1627.82 | 25-NOV-16:11 | 4.23 |
December | 0.858160E+09 | 1636.71 | 11-DEC-16:11 | 1.10 |
Annual Sum or Average | 0.405040E+10 | |||
Minimum of Months | 128041.21 | 621.57 | -8.2 | |
Maximum of Months | 0.114253E+10 | 1659.20 | 26.28 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135516E+10 | 1653.85 | 14-JAN-16:11 | -6.1 |
February | 0.119579E+10 | 1649.46 | 06-FEB-09:01 | -12.0 |
March | 0.535110E+09 | 1624.29 | 16-MAR-15:11 | 0.77 |
April | 0.198701E+09 | 1587.06 | 21-APR-15:11 | 7.40 |
May | 10088042.23 | 1402.62 | 12-MAY-08:03 | 15.87 |
June | 415357.88 | 750.62 | 03-JUN-08:13 | 17.03 |
July | 69134.01 | 306.70 | 15-JUL-08:15 | 20.60 |
August | 310558.38 | 734.02 | 20-AUG-08:14 | 20.17 |
September | 1609118.61 | 1342.52 | 23-SEP-08:03 | 13.30 |
October | 60757336.26 | 1531.03 | 31-OCT-08:61 | 7.38 |
November | 0.613814E+09 | 1625.83 | 25-NOV-16:11 | 4.23 |
December | 0.108137E+10 | 1632.47 | 31-DEC-19:01 | -5.7 |
Annual Sum or Average | 0.505319E+10 | |||
Minimum of Months | 69134.01 | 306.70 | -12.0 | |
Maximum of Months | 0.135516E+10 | 1653.85 | 20.60 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1434160.47 | 72.38 | 16-JAN-05:51 | -5.0 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 1434160.47 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 1434160.47 | 72.38 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145238E+09 | 470.95 | 14-JAN-16:11 | -6.1 |
February | 0.148624E+09 | 470.88 | 06-FEB-16:11 | -7.0 |
March | 22863292.55 | 439.25 | 16-MAR-15:11 | 0.77 |
April | 831101.28 | 435.64 | 12-APR-08:03 | 5.78 |
May | 103794.84 | 259.35 | 04-MAY-08:04 | 11.20 |
June | 13906.04 | 134.58 | 05-JUN-08:15 | 19.07 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 2706.17 | 38.70 | 30-AUG-08:16 | 22.40 |
September | 95841.60 | 210.14 | 19-SEP-08:14 | 16.83 |
October | 346676.24 | 434.00 | 28-OCT-18:03 | 8.22 |
November | 29154405.61 | 449.58 | 23-NOV-16:11 | 1.33 |
December | 78044938.50 | 457.09 | 31-DEC-16:11 | -3.3 |
Annual Sum or Average | 0.425318E+09 | |||
Minimum of Months | 0.00 | 0.00 | -7.0 | |
Maximum of Months | 0.148624E+09 | 470.95 | 22.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113449E+10 | 1591.34 | 14-JAN-16:11 | -6.1 |
February | 0.917230E+09 | 1575.35 | 06-FEB-16:11 | -7.0 |
March | 0.444302E+09 | 1564.37 | 17-MAR-18:01 | -1.1 |
April | 0.175357E+09 | 1528.06 | 21-APR-15:11 | 7.40 |
May | 10570446.04 | 1541.80 | 01-MAY-18:03 | 12.43 |
June | 413756.99 | 739.44 | 08-JUN-08:04 | 22.70 |
July | 61781.33 | 336.69 | 24-JUL-08:05 | 22.07 |
August | 20312.66 | 338.54 | 06-AUG-08:05 | 22.12 |
September | 1455597.59 | 1015.96 | 23-SEP-08:03 | 13.30 |
October | 33595787.03 | 1251.87 | 30-OCT-18:03 | 12.02 |
November | 0.440873E+09 | 1562.78 | 25-NOV-16:11 | 4.23 |
December | 0.846966E+09 | 1570.45 | 11-DEC-16:11 | 1.10 |
Annual Sum or Average | 0.400533E+10 | |||
Minimum of Months | 20312.66 | 336.69 | -7.0 | |
Maximum of Months | 0.113449E+10 | 1591.34 | 22.70 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134493E+10 | 1591.14 | 14-JAN-16:11 | -6.1 |
February | 0.116677E+10 | 1582.61 | 06-FEB-16:11 | -7.0 |
March | 0.565354E+09 | 1563.86 | 16-MAR-15:11 | 0.77 |
April | 0.201633E+09 | 1530.23 | 01-APR-15:11 | 6.47 |
May | 11371060.28 | 1352.00 | 01-MAY-18:03 | 12.43 |
June | 255369.32 | 536.78 | 08-JUN-21:14 | 18.13 |
July | 5897.87 | 91.09 | 05-JUL-08:16 | 23.17 |
August | 52066.18 | 403.31 | 24-AUG-21:15 | 25.20 |
September | 1214644.16 | 770.35 | 30-SEP-20:03 | 15.50 |
October | 63439358.30 | 1462.14 | 31-OCT-15:11 | 13.30 |
November | 0.567583E+09 | 1566.69 | 23-NOV-16:11 | 1.33 |
December | 0.105610E+10 | 1577.23 | 02-DEC-16:11 | 5.73 |
Annual Sum or Average | 0.497870E+10 | |||
Minimum of Months | 5897.87 | 91.09 | -7.0 | |
Maximum of Months | 0.134493E+10 | 1591.14 | 25.20 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151858E+10 | 1390.84 | 02-JAN-06:02 | -11.7 |
February | 0.121359E+10 | 1377.10 | 07-FEB-06:02 | -9.4 |
March | 0.639030E+09 | 1262.16 | 01-MAR-06:02 | 3.98 |
April | 0.233719E+09 | 1166.39 | 02-APR-05:02 | 3.80 |
May | 5940480.54 | 506.66 | 01-MAY-04:48 | 6.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 1709.82 | 18.48 | 27-SEP-02:33 | 16.10 |
October | 479012.77 | 131.22 | 29-OCT-06:28 | 2.75 |
November | 0.634849E+09 | 1242.52 | 24-NOV-06:02 | -4.4 |
December | 0.120190E+10 | 1292.18 | 31-DEC-24:00 | -8.3 |
Annual Sum or Average | 0.544809E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.7 | |
Maximum of Months | 0.151858E+10 | 1390.84 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153166E+10 | 1921.92 | 14-JAN-16:11 | -6.1 |
February | 0.129989E+10 | 1905.32 | 06-FEB-19:01 | -8.2 |
March | 0.635708E+09 | 1882.78 | 16-MAR-15:11 | 0.77 |
April | 0.279542E+09 | 1863.80 | 21-APR-15:11 | 7.40 |
May | 20738260.25 | 1629.63 | 04-MAY-08:61 | 11.20 |
June | 820973.04 | 917.38 | 06-JUN-18:03 | 18.22 |
July | 110646.01 | 442.67 | 12-JUL-08:04 | 26.28 |
August | 490935.06 | 858.93 | 10-AUG-08:04 | 24.18 |
September | 3500413.50 | 1490.74 | 10-SEP-08:03 | 19.08 |
October | 72515111.31 | 1766.47 | 31-OCT-08:61 | 7.38 |
November | 0.704807E+09 | 1882.17 | 25-NOV-16:11 | 4.23 |
December | 0.122599E+10 | 1894.97 | 11-DEC-16:11 | 1.10 |
Annual Sum or Average | 0.577577E+10 | |||
Minimum of Months | 110646.01 | 442.67 | -8.2 | |
Maximum of Months | 0.153166E+10 | 1921.92 | 26.28 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179264E+10 | 1917.50 | 14-JAN-16:11 | -6.1 |
February | 0.160681E+10 | 1911.71 | 06-FEB-09:01 | -12.0 |
March | 0.780559E+09 | 1881.65 | 16-MAR-15:11 | 0.77 |
April | 0.311002E+09 | 1859.61 | 21-APR-15:11 | 7.40 |
May | 21423798.94 | 1721.62 | 04-MAY-08:61 | 11.20 |
June | 303528.14 | 686.56 | 03-JUN-08:13 | 17.03 |
July | 60469.31 | 300.99 | 15-JUL-08:15 | 20.60 |
August | 202615.22 | 769.58 | 23-AUG-08:14 | 22.40 |
September | 2882183.35 | 1193.67 | 16-SEP-08:13 | 19.07 |
October | 0.123746E+09 | 1800.91 | 29-OCT-08:61 | 6.88 |
November | 0.901633E+09 | 1882.40 | 25-NOV-16:11 | 4.23 |
December | 0.150911E+10 | 1892.58 | 31-DEC-19:01 | -5.7 |
Annual Sum or Average | 0.705038E+10 | |||
Minimum of Months | 60469.31 | 300.99 | -12.0 | |
Maximum of Months | 0.179264E+10 | 1917.50 | 22.40 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443889E+09 | 941.95 | 14-JAN-16:11 | -6.1 |
February | 0.322933E+09 | 930.66 | 27-FEB-16:11 | 0.60 |
March | 0.154366E+09 | 925.02 | 16-MAR-15:11 | 0.77 |
April | 64248272.48 | 897.88 | 21-APR-15:11 | 7.40 |
May | 2047049.65 | 650.09 | 02-MAY-08:03 | 14.68 |
June | 150379.14 | 386.54 | 06-JUN-18:03 | 18.22 |
July | 17234.13 | 152.02 | 12-JUL-08:05 | 26.28 |
August | 101138.94 | 427.64 | 25-AUG-08:04 | 19.60 |
September | 324553.57 | 388.26 | 12-SEP-08:04 | 20.00 |
October | 3803795.81 | 590.98 | 09-OCT-08:03 | 9.18 |
November | 0.121727E+09 | 899.36 | 25-NOV-16:11 | 4.23 |
December | 0.304385E+09 | 930.53 | 11-DEC-16:11 | 1.10 |
Annual Sum or Average | 0.141799E+10 | |||
Minimum of Months | 17234.13 | 152.02 | -6.1 | |
Maximum of Months | 0.443889E+09 | 941.95 | 26.28 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.656740E+09 | 3645.38 | 02-JAN-06:02 | -11.7 |
February | 0.424746E+09 | 3526.62 | 06-FEB-06:02 | -12.9 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
November | 7514863.56 | 799.87 | 25-NOV-05:52 | -3.3 |
December | 27001258.34 | 1567.85 | 31-DEC-23:52 | -8.3 |
Annual Sum or Average | 0.111600E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.656740E+09 | 3645.38 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.113897E+11 | 10970.58 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.102838E+11 | 10970.58 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.114292E+11 | 10970.58 | 01-MAR-20:10 | 0.121808E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.110035E+11 | 10970.58 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.114094E+11 | 10970.58 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.110540E+11 | 10970.58 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.113589E+11 | 10970.58 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.114292E+11 | 10970.58 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.110035E+11 | 10970.58 | 01-SEP-19:10 | 0.117446E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.113897E+11 | 10970.58 | 02-OCT-19:10 | 0.121516E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.110452E+11 | 10970.58 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.113589E+11 | 10970.58 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.134155E+12 | 0.143109E+12 | ||||
Minimum of Months | 0.102838E+11 | 10970.58 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.114292E+11 | 10970.58 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.566644E+09 | 545.79 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.511628E+09 | 545.79 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.568609E+09 | 545.79 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.547432E+09 | 545.79 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.567626E+09 | 545.79 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.549942E+09 | 545.79 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.565115E+09 | 545.79 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.568609E+09 | 545.79 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.547432E+09 | 545.79 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.566644E+09 | 545.79 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.549506E+09 | 545.79 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.565115E+09 | 545.79 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.667430E+10 | 0.101859E+11 | ||||
Minimum of Months | 0.511628E+09 | 545.79 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.568609E+09 | 545.79 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.656175E+09 | 632.03 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.592467E+09 | 632.03 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.658451E+09 | 632.03 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.633928E+09 | 632.03 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.657313E+09 | 632.03 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.636835E+09 | 632.03 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.654406E+09 | 632.03 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.658451E+09 | 632.03 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.633928E+09 | 632.03 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.656175E+09 | 632.03 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.636330E+09 | 632.03 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.654406E+09 | 632.03 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.772886E+10 | 0.117953E+11 | ||||
Minimum of Months | 0.592467E+09 | 632.03 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.658451E+09 | 632.03 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156929E+10 | 1511.55 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.141693E+10 | 1511.55 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.157474E+10 | 1511.55 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.151609E+10 | 1511.55 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.157202E+10 | 1511.55 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.152304E+10 | 1511.55 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.156506E+10 | 1511.55 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.157474E+10 | 1511.55 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.151609E+10 | 1511.55 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.156929E+10 | 1511.55 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.152183E+10 | 1511.55 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.156506E+10 | 1511.55 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | ||||
Minimum of Months | 0.141693E+10 | 1511.55 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.157474E+10 | 1511.55 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.161153E+09 | 155.22 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.145507E+09 | 155.22 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.161712E+09 | 155.22 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.155689E+09 | 155.22 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.161433E+09 | 155.22 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.156404E+09 | 155.22 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.160719E+09 | 155.22 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.161712E+09 | 155.22 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.155689E+09 | 155.22 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.161153E+09 | 155.22 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.156279E+09 | 155.22 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.160719E+09 | 155.22 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.189817E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.145507E+09 | 155.22 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.161712E+09 | 155.22 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417433E+09 | 400.68 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.401887E+09 | 400.68 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415991E+09 | 400.68 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489981E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.876083E+09 | 1097.76 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.749337E+09 | 1097.76 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.785849E+09 | 1097.76 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.700842E+09 | 1097.76 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.658055E+09 | 1097.76 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.611942E+09 | 1097.76 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.635657E+09 | 1097.76 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.695963E+09 | 1097.76 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.733296E+09 | 1097.76 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.820555E+09 | 1097.76 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.823546E+09 | 1097.76 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.869378E+09 | 1097.76 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.896050E+10 | 0.143409E+11 | ||||
Minimum of Months | 0.611942E+09 | 1097.76 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.876083E+09 | 1097.76 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.644537E+10 | 6463.27 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.577341E+10 | 6463.27 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.637146E+10 | 6463.27 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.608312E+10 | 6463.27 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.623666E+10 | 6463.27 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.602061E+10 | 6463.27 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.619501E+10 | 6463.27 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.628212E+10 | 6463.27 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.611340E+10 | 6463.27 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.638155E+10 | 6463.27 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.621814E+10 | 6463.27 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.642067E+10 | 6463.27 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.745415E+11 | 0.149002E+12 | ||||
Minimum of Months | 0.577341E+10 | 6463.27 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.644537E+10 | 6463.27 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117159E+09 | 137.77 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.105814E+09 | 137.77 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.116728E+09 | 137.77 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.113449E+09 | 137.77 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.116943E+09 | 137.77 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113018E+09 | 137.77 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.117374E+09 | 137.77 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.116728E+09 | 137.77 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.113449E+09 | 137.77 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.117159E+09 | 137.77 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113234E+09 | 137.77 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.117374E+09 | 137.77 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.137843E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.105814E+09 | 137.77 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.117374E+09 | 137.77 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117145E+09 | 137.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.105801E+09 | 137.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.116714E+09 | 137.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.113436E+09 | 137.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.116930E+09 | 137.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113005E+09 | 137.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.117360E+09 | 137.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.116714E+09 | 137.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.113436E+09 | 137.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.117145E+09 | 137.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113220E+09 | 137.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.117360E+09 | 137.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.137827E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.105801E+09 | 137.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.117360E+09 | 137.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 73629799.21 | 86.58 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 66499969.88 | 86.58 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 73359176.20 | 86.58 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 71298293.27 | 86.58 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 73494487.70 | 86.58 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 71027670.26 | 86.58 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 73765110.71 | 86.58 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 73359176.20 | 86.58 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 71298293.27 | 86.58 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 73629799.21 | 86.58 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 71162981.76 | 86.58 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 73765110.71 | 86.58 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.866290E+09 | 0.256575E+10 | ||||
Minimum of Months | 66499969.88 | 86.58 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 73765110.71 | 86.58 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 73649933.14 | 86.61 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 66518154.18 | 86.61 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 73379236.13 | 86.61 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 71317789.65 | 86.61 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 73514584.64 | 86.61 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 71047092.65 | 86.61 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 73785281.65 | 86.61 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 73379236.13 | 86.61 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 71317789.65 | 86.61 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 73649933.14 | 86.61 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 71182441.15 | 86.61 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 73785281.65 | 86.61 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.866527E+09 | 0.256645E+10 | ||||
Minimum of Months | 66518154.18 | 86.61 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 73785281.65 | 86.61 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117159E+09 | 137.77 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.105814E+09 | 137.77 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.116728E+09 | 137.77 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.113449E+09 | 137.77 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.116943E+09 | 137.77 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113018E+09 | 137.77 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.117374E+09 | 137.77 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.116728E+09 | 137.77 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.113449E+09 | 137.77 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.117159E+09 | 137.77 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113234E+09 | 137.77 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.117374E+09 | 137.77 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.137843E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.105814E+09 | 137.77 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.117374E+09 | 137.77 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117145E+09 | 137.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.105801E+09 | 137.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.116714E+09 | 137.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.113436E+09 | 137.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.116930E+09 | 137.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113005E+09 | 137.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.117360E+09 | 137.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.116714E+09 | 137.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.113436E+09 | 137.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.117145E+09 | 137.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113220E+09 | 137.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.117360E+09 | 137.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.137827E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.105801E+09 | 137.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.117360E+09 | 137.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.870792E+09 | 838.75 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.786245E+09 | 838.75 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.873811E+09 | 838.75 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.841268E+09 | 838.75 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.872301E+09 | 838.75 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.845126E+09 | 838.75 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.868443E+09 | 838.75 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.873811E+09 | 838.75 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.841268E+09 | 838.75 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.870792E+09 | 838.75 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.844455E+09 | 838.75 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.868443E+09 | 838.75 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102568E+11 | ||||
Minimum of Months | 0.786245E+09 | 838.75 | 0.00 | 0.00 | |
Maximum of Months | 0.873811E+09 | 838.75 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117159E+09 | 137.77 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.105814E+09 | 137.77 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.116728E+09 | 137.77 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.113449E+09 | 137.77 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.116943E+09 | 137.77 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113018E+09 | 137.77 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.117374E+09 | 137.77 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.116728E+09 | 137.77 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.113449E+09 | 137.77 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.117159E+09 | 137.77 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113234E+09 | 137.77 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.117374E+09 | 137.77 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.137843E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.105814E+09 | 137.77 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.117374E+09 | 137.77 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117145E+09 | 137.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.105801E+09 | 137.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.116714E+09 | 137.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.113436E+09 | 137.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.116930E+09 | 137.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113005E+09 | 137.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.117360E+09 | 137.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.116714E+09 | 137.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.113436E+09 | 137.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.117145E+09 | 137.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113220E+09 | 137.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.117360E+09 | 137.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.137827E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.105801E+09 | 137.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.117360E+09 | 137.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 73649933.14 | 86.61 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 66518154.18 | 86.61 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 73379236.13 | 86.61 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 71317789.65 | 86.61 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 73514584.64 | 86.61 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 71047092.65 | 86.61 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 73785281.65 | 86.61 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 73379236.13 | 86.61 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 71317789.65 | 86.61 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 73649933.14 | 86.61 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 71182441.15 | 86.61 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 73785281.65 | 86.61 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.866527E+09 | 0.256645E+10 | ||||
Minimum of Months | 66518154.18 | 86.61 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 73785281.65 | 86.61 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.179285E+10 | 1927.76 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.157693E+10 | 1927.76 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.170054E+10 | 1927.76 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.157882E+10 | 1927.76 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.156402E+10 | 1927.76 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.149042E+10 | 1927.76 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.153945E+10 | 1927.76 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.160450E+10 | 1927.76 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.161276E+10 | 1927.76 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.172890E+10 | 1927.76 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.170769E+10 | 1927.76 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.179286E+10 | 1927.76 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.196897E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.149042E+10 | 1927.76 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.179286E+10 | 1927.76 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.179285E+10 | 1927.76 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.157693E+10 | 1927.76 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.170054E+10 | 1927.76 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.157882E+10 | 1927.76 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.156402E+10 | 1927.76 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.149042E+10 | 1927.76 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.153945E+10 | 1927.76 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.160450E+10 | 1927.76 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.161276E+10 | 1927.76 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.172890E+10 | 1927.76 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.170769E+10 | 1927.76 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.179286E+10 | 1927.76 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.196897E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.149042E+10 | 1927.76 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.179286E+10 | 1927.76 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113643E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109411E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113447E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109411E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113250E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133394E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.921598E+09 | 887.69 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.832119E+09 | 887.69 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.924794E+09 | 887.69 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.890352E+09 | 887.69 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.923196E+09 | 887.69 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.894435E+09 | 887.69 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.919113E+09 | 887.69 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.924794E+09 | 887.69 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.890352E+09 | 887.69 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.921598E+09 | 887.69 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.893725E+09 | 887.69 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.919113E+09 | 887.69 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.108552E+11 | ||||
Minimum of Months | 0.832119E+09 | 887.69 | 0.00 | 0.00 | |
Maximum of Months | 0.924794E+09 | 887.69 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.113897E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.102838E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.114292E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.110035E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.114094E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.110540E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.113589E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.114292E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.110035E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.113897E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.110452E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.113589E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.134155E+12 | 0.143109E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.102838E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.114292E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.566644E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138779E+10 |
February | 0.179968E+10 | 0.511628E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134665E+10 |
March | 0.199896E+10 | 0.568609E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112888E+10 |
April | 0.192973E+10 | 0.547432E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 448942.03 | 0.768801E+09 |
May | 0.199475E+10 | 0.567626E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5744549.01 | 0.504224E+09 |
June | 0.193394E+10 | 0.549942E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33667498.68 | 0.182835E+09 |
July | 0.199054E+10 | 0.565115E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84825201.75 | 42956770.72 |
August | 0.199896E+10 | 0.568609E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84414552.08 | 76389826.41 |
September | 0.192973E+10 | 0.547432E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8239246.67 | 0.277413E+09 |
October | 0.199054E+10 | 0.566644E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670343E+09 |
November | 0.192552E+10 | 0.549506E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.987854E+09 |
December | 0.199054E+10 | 0.565115E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124373E+10 |
Annual Sum or Average | 0.234734E+11 | 0.667430E+10 | 0.101859E+11 | 0.217340E+09 | 0.861787E+10 | ||||
Minimum of Months | 0.179968E+10 | 0.511628E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42956770.72 |
Maximum of Months | 0.199896E+10 | 0.568609E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84825201.75 | 0.138779E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.656175E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317913E+09 |
February | 0.208403E+10 | 0.592467E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305937E+09 |
March | 0.231480E+10 | 0.658451E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258552E+09 |
April | 0.223463E+10 | 0.633928E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 208325.09 | 0.176945E+09 |
May | 0.230993E+10 | 0.657313E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1349545.95 | 0.113386E+09 |
June | 0.223950E+10 | 0.636835E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7425150.20 | 42549261.81 |
July | 0.230505E+10 | 0.654406E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18183183.40 | 12417160.64 |
August | 0.231480E+10 | 0.658451E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19733804.31 | 19368049.77 |
September | 0.223463E+10 | 0.633928E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2882000.16 | 61192345.96 |
October | 0.230505E+10 | 0.656175E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27039.08 | 0.144215E+09 |
November | 0.222975E+10 | 0.636330E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226033E+09 |
December | 0.230505E+10 | 0.654406E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286648E+09 |
Annual Sum or Average | 0.271823E+11 | 0.772886E+10 | 0.117953E+11 | 49809048.18 | 0.196515E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.592467E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12417160.64 |
Maximum of Months | 0.231480E+10 | 0.658451E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19733804.31 | 0.317913E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110570E+10 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105007E+10 |
March | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903429E+09 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 424803.43 | 0.634534E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 3246342.52 | 0.423877E+09 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 16923818.23 | 0.184061E+09 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 45411402.04 | 77780517.89 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 49673315.55 | 98013902.72 |
September | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 6710684.19 | 0.247195E+09 |
October | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 43060.19 | 0.518168E+09 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793822E+09 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994882E+09 |
Annual Sum or Average | 0.182082E+11 | 0.489981E+10 | 0.679373E+11 | 0.590211E+12 | 0.122433E+09 | 0.703154E+10 | |||
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77780517.89 |
Maximum of Months | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 49673315.55 | 0.110570E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.876083E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374906E+10 |
February | 0.236489E+11 | 0.749337E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362588E+10 |
March | 0.262677E+11 | 0.785849E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306797E+10 |
April | 0.253579E+11 | 0.700842E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1369824.13 | 0.208379E+10 |
May | 0.262123E+11 | 0.658055E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15435802.24 | 0.132665E+10 |
June | 0.254132E+11 | 0.611942E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86141555.63 | 0.501097E+09 |
July | 0.261570E+11 | 0.635657E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206645E+09 | 0.158246E+09 |
August | 0.262677E+11 | 0.695963E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210011E+09 | 0.239210E+09 |
September | 0.253579E+11 | 0.733296E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23734171.09 | 0.747783E+09 |
October | 0.261570E+11 | 0.820555E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22462.37 | 0.179022E+10 |
November | 0.253025E+11 | 0.823546E+09 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269136E+10 |
December | 0.261570E+11 | 0.869378E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339211E+10 |
Annual Sum or Average | 0.308456E+12 | 0.896050E+10 | 0.143409E+11 | 0.543359E+09 | 0.233734E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.611942E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158246E+09 |
Maximum of Months | 0.262677E+11 | 0.876083E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210011E+09 | 0.374906E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.644537E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779132E+10 |
February | 0.702046E+11 | 0.577341E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746752E+10 |
March | 0.779788E+11 | 0.637146E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632663E+10 |
April | 0.752779E+11 | 0.608312E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4781813.74 | 0.434632E+10 |
May | 0.778146E+11 | 0.623666E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31999405.94 | 0.279671E+10 |
June | 0.754422E+11 | 0.602061E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174967E+09 | 0.107535E+10 |
July | 0.776503E+11 | 0.619501E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423460E+09 | 0.348436E+09 |
August | 0.779788E+11 | 0.628212E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460336E+09 | 0.503445E+09 |
September | 0.752779E+11 | 0.611340E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66182440.13 | 0.153304E+10 |
October | 0.776503E+11 | 0.638155E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 283007.13 | 0.357036E+10 |
November | 0.751137E+11 | 0.621814E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555441E+10 |
December | 0.776503E+11 | 0.642067E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701251E+10 |
Annual Sum or Average | 0.915690E+12 | 0.745415E+11 | 0.149002E+12 | 0.116201E+10 | 0.483261E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.577341E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348436E+09 |
Maximum of Months | 0.779788E+11 | 0.644537E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460336E+09 | 0.779132E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390776E+09 |
February | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377800E+09 |
March | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9036.36 | 0.305261E+09 |
April | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 689606.97 | 0.195107E+09 |
May | 0.303504E+09 | 0.116943E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3643624.02 | 0.109598E+09 |
June | 0.293842E+09 | 0.113018E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21928879.05 | 24606191.05 |
July | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59176794.72 | 1339620.92 |
August | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59777829.91 | 7032239.32 |
September | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12571994.81 | 46064954.03 |
October | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 437621.80 | 0.146862E+09 |
November | 0.293661E+09 | 0.113234E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259252E+09 |
December | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342484E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137843E+10 | 0.261953E+10 | 0.158235E+09 | 0.220618E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1339620.92 |
Maximum of Months | 0.303685E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59777829.91 | 0.390776E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387408E+09 |
February | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373567E+09 |
March | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301124E+09 |
April | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 418225.30 | 0.194832E+09 |
May | 0.303504E+09 | 0.116930E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2733374.57 | 0.115218E+09 |
June | 0.293842E+09 | 0.113005E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17655106.58 | 35601135.69 |
July | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47892426.42 | 6231614.49 |
August | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50914317.99 | 12544362.22 |
September | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8971179.00 | 52858131.62 |
October | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 238841.84 | 0.147221E+09 |
November | 0.293661E+09 | 0.113220E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254778E+09 |
December | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337667E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137827E+10 | 0.261922E+10 | 0.128823E+09 | 0.221905E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6231614.49 |
Maximum of Months | 0.303685E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50914317.99 | 0.387408E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 73629799.21 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101224E+09 |
February | 0.00 | 66499969.88 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115393E+09 |
March | 0.00 | 73359176.20 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103294E+09 |
April | 0.00 | 71298293.27 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75710344.77 |
May | 0.00 | 73494487.70 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 124838.14 | 55553469.50 |
June | 0.00 | 71027670.26 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1100824.66 | 26135306.75 |
July | 0.00 | 73765110.71 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2575168.50 | 11173380.92 |
August | 0.00 | 73359176.20 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3486200.47 | 13524837.10 |
September | 0.00 | 71298293.27 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 272897.62 | 34384448.65 |
October | 0.00 | 73629799.21 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67244179.93 |
November | 0.00 | 71162981.76 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93953642.28 |
December | 0.00 | 73765110.71 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109677E+09 |
Annual Sum or Average | 0.00 | 0.866290E+09 | 0.256575E+10 | 7559929.39 | 0.807267E+09 | ||||
Minimum of Months | 0.00 | 66499969.88 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11173380.92 |
Maximum of Months | 0.00 | 73765110.71 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3486200.47 | 0.115393E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110040E+09 |
February | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105706E+09 |
March | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 904.40 | 85247069.09 |
April | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 173086.22 | 54734274.51 |
May | 0.303504E+09 | 73514584.64 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 816168.76 | 31387209.83 |
June | 0.293842E+09 | 71047092.65 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5141839.55 | 8443798.52 |
July | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13800166.89 | 1088063.57 |
August | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14770936.33 | 2719522.62 |
September | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2716712.21 | 13864373.49 |
October | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 122350.85 | 40430638.82 |
November | 0.293661E+09 | 71182441.15 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72756230.89 |
December | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96228999.86 |
Annual Sum or Average | 0.357224E+10 | 0.866527E+09 | 0.256645E+10 | 37542165.21 | 0.622646E+09 | ||||
Minimum of Months | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1088063.57 |
Maximum of Months | 0.303685E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14770936.33 | 0.110040E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390820E+09 |
February | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378261E+09 |
March | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10863.25 | 0.306107E+09 |
April | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 687803.98 | 0.196405E+09 |
May | 0.303504E+09 | 0.116943E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3625602.02 | 0.110693E+09 |
June | 0.293842E+09 | 0.113018E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21890425.05 | 24835949.19 |
July | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59104159.94 | 1356186.66 |
August | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59731989.48 | 7148478.56 |
September | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12561197.54 | 46492286.48 |
October | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 432098.27 | 0.147636E+09 |
November | 0.293661E+09 | 0.113234E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260142E+09 |
December | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342761E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137843E+10 | 0.261953E+10 | 0.158044E+09 | 0.221266E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1356186.66 |
Maximum of Months | 0.303685E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59731989.48 | 0.390820E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387474E+09 |
February | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373832E+09 |
March | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5803.43 | 0.301704E+09 |
April | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 456712.39 | 0.195568E+09 |
May | 0.303504E+09 | 0.116930E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2708487.18 | 0.114956E+09 |
June | 0.293842E+09 | 0.113005E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17785841.97 | 32950129.99 |
July | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 48044964.82 | 5558027.20 |
August | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50892478.17 | 11873323.07 |
September | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9067708.73 | 51809216.41 |
October | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 216226.95 | 0.146459E+09 |
November | 0.293661E+09 | 0.113220E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255685E+09 |
December | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337861E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137827E+10 | 0.261922E+10 | 0.129178E+09 | 0.221573E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5558027.20 |
Maximum of Months | 0.303685E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50892478.17 | 0.387474E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390608E+09 |
February | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377643E+09 |
March | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7848.17 | 0.305296E+09 |
April | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 665543.53 | 0.195923E+09 |
May | 0.303504E+09 | 0.116943E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3546794.52 | 0.111151E+09 |
June | 0.293842E+09 | 0.113018E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21436852.69 | 25271780.23 |
July | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58140372.88 | 1421349.83 |
August | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58860752.93 | 7215906.28 |
September | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12192195.82 | 46777944.74 |
October | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 404485.35 | 0.147618E+09 |
November | 0.293661E+09 | 0.113234E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258795E+09 |
December | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341963E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137843E+10 | 0.261953E+10 | 0.155255E+09 | 0.220968E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1421349.83 |
Maximum of Months | 0.303685E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58860752.93 | 0.390608E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387777E+09 |
February | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373804E+09 |
March | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301124E+09 |
April | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 365882.29 | 0.196042E+09 |
May | 0.303504E+09 | 0.116930E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2644505.53 | 0.118700E+09 |
June | 0.293842E+09 | 0.113005E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17210376.89 | 39091963.14 |
July | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46747113.77 | 8195269.94 |
August | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49934480.64 | 14327544.74 |
September | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8650368.77 | 55704715.98 |
October | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 202643.05 | 0.148768E+09 |
November | 0.293661E+09 | 0.113220E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254419E+09 |
December | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337493E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137827E+10 | 0.261922E+10 | 0.125755E+09 | 0.223545E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8195269.94 |
Maximum of Months | 0.303685E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49934480.64 | 0.387777E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204511E+09 |
February | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198081E+09 |
March | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4166.48 | 0.159204E+09 |
April | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 339141.22 | 0.101586E+09 |
May | 0.303504E+09 | 73514584.64 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1816409.50 | 57083123.35 |
June | 0.293842E+09 | 71047092.65 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10969665.82 | 12831875.43 |
July | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29719880.67 | 729201.70 |
August | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30101646.99 | 3699429.67 |
September | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6216866.63 | 24161698.42 |
October | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 198960.16 | 76517515.62 |
November | 0.293661E+09 | 71182441.15 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136832E+09 |
December | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179775E+09 |
Annual Sum or Average | 0.357224E+10 | 0.866527E+09 | 0.256645E+10 | 79366737.47 | 0.115501E+10 | ||||
Minimum of Months | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 729201.70 |
Maximum of Months | 0.303685E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30101646.99 | 0.204511E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.179285E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116608E+10 |
February | 0.415303E+11 | 0.157693E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111070E+10 |
March | 0.461292E+11 | 0.170054E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961721E+09 |
April | 0.445315E+11 | 0.157882E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 378447.53 | 0.679541E+09 |
May | 0.460320E+11 | 0.156402E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2797128.83 | 0.453687E+09 |
June | 0.446286E+11 | 0.149042E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16127950.79 | 0.194352E+09 |
July | 0.459349E+11 | 0.153945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36834133.45 | 81641138.73 |
August | 0.461292E+11 | 0.160450E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44310591.96 | 99444601.90 |
September | 0.445315E+11 | 0.161276E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5764226.27 | 0.257749E+09 |
October | 0.459349E+11 | 0.172890E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35888.99 | 0.549028E+09 |
November | 0.444343E+11 | 0.170769E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841609E+09 |
December | 0.459349E+11 | 0.179286E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105032E+10 |
Annual Sum or Average | 0.541686E+12 | 0.196897E+11 | 0.175857E+12 | 0.106248E+09 | 0.744587E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.149042E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81641138.73 |
Maximum of Months | 0.461292E+11 | 0.179286E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44310591.96 | 0.116608E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.179285E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119470E+10 |
February | 0.415303E+11 | 0.157693E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113655E+10 |
March | 0.461292E+11 | 0.170054E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988898E+09 |
April | 0.445315E+11 | 0.157882E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 231945.25 | 0.701682E+09 |
May | 0.460320E+11 | 0.156402E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2163647.76 | 0.472791E+09 |
June | 0.446286E+11 | 0.149042E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13688459.77 | 0.207863E+09 |
July | 0.459349E+11 | 0.153945E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31136916.80 | 90908526.84 |
August | 0.461292E+11 | 0.160450E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38246721.99 | 0.108099E+09 |
September | 0.445315E+11 | 0.161276E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4525332.82 | 0.272476E+09 |
October | 0.459349E+11 | 0.172890E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3260.83 | 0.568633E+09 |
November | 0.444343E+11 | 0.170769E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865979E+09 |
December | 0.459349E+11 | 0.179286E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107909E+10 |
Annual Sum or Average | 0.541686E+12 | 0.196897E+11 | 0.175857E+12 | 89996285.22 | 0.768766E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.149042E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90908526.84 |
Maximum of Months | 0.461292E+11 | 0.179286E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38246721.99 | 0.119470E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122662E+10 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116137E+10 |
March | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104056E+10 |
April | 0.396281E+10 | 0.109411E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.769506E+09 |
May | 0.409635E+10 | 0.113447E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 10035.00 | 0.557258E+09 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 1395474.27 | 0.293562E+09 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 1958179.11 | 0.171843E+09 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3110515.84 | 0.188570E+09 |
September | 0.396281E+10 | 0.109411E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 84056.52 | 0.365651E+09 |
October | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654034E+09 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921718E+09 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112207E+10 |
Annual Sum or Average | 0.482041E+11 | 0.133394E+11 | 0.382987E+12 | 0.359593E+12 | 6558260.74 | 0.847276E+10 | |||
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171843E+09 |
Maximum of Months | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3110515.84 | 0.122662E+10 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693297E+09 |
February | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665716E+09 |
March | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565467E+09 |
April | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 468299.43 | 0.384036E+09 |
May | 0.00 | 0.157202E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3016620.81 | 0.241693E+09 |
June | 0.00 | 0.152304E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17174234.91 | 86805716.05 |
July | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43218431.60 | 21788855.86 |
August | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47962733.49 | 36258479.07 |
September | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7185982.00 | 0.126488E+09 |
October | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93531.40 | 0.302816E+09 |
November | 0.00 | 0.152183E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492619E+09 |
December | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631280E+09 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | 0.119120E+09 | 0.424826E+10 | |||||
Minimum of Months | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21788855.86 |
Maximum of Months | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47962733.49 | 0.693297E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.161153E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443441E+09 |
February | 0.00 | 0.145507E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425382E+09 |
March | 0.00 | 0.161712E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356667E+09 |
April | 0.00 | 0.155689E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 526652.22 | 0.241874E+09 |
May | 0.00 | 0.161433E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2459285.26 | 0.152071E+09 |
June | 0.00 | 0.156404E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12705549.04 | 53938896.75 |
July | 0.00 | 0.160719E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30374932.23 | 13538602.71 |
August | 0.00 | 0.161712E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33770887.07 | 23324799.53 |
September | 0.00 | 0.155689E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5442756.67 | 78718432.39 |
October | 0.00 | 0.161153E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 137319.03 | 0.196328E+09 |
November | 0.00 | 0.156279E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313902E+09 |
December | 0.00 | 0.160719E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398192E+09 |
Annual Sum or Average | 0.189817E+10 | 0.359769E+10 | 85417381.52 | 0.269738E+10 | |||||
Minimum of Months | 0.00 | 0.145507E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13538602.71 |
Maximum of Months | 0.00 | 0.161712E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 33770887.07 | 0.443441E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.870792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469460E+09 |
February | 0.00 | 0.786245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455321E+09 |
March | 0.00 | 0.873811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25598.06 | 0.366790E+09 |
April | 0.00 | 0.841268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1320569.95 | 0.231520E+09 |
May | 0.00 | 0.872301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5577457.29 | 0.127028E+09 |
June | 0.00 | 0.845126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23983599.91 | 35563164.17 |
July | 0.00 | 0.868443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54642009.42 | 4826556.19 |
August | 0.00 | 0.873811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55781644.33 | 15164775.93 |
September | 0.00 | 0.841268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11189893.29 | 59535037.63 |
October | 0.00 | 0.870792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1030209.71 | 0.175365E+09 |
November | 0.00 | 0.844455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312577E+09 |
December | 0.00 | 0.868443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415897E+09 |
Annual Sum or Average | 0.102568E+11 | 0.153551E+09 | 0.266905E+10 | ||||||
Minimum of Months | 0.00 | 0.786245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4826556.19 |
Maximum of Months | 0.00 | 0.873811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55781644.33 | 0.469460E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.921598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872473E+09 |
February | 0.00 | 0.832119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840596E+09 |
March | 0.00 | 0.924794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727364E+09 |
April | 0.00 | 0.890352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455728.28 | 0.510901E+09 |
May | 0.00 | 0.923196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2756088.68 | 0.331853E+09 |
June | 0.00 | 0.894435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17627925.01 | 0.122715E+09 |
July | 0.00 | 0.919113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42144204.48 | 33600217.81 |
August | 0.00 | 0.924794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47904716.36 | 53257888.67 |
September | 0.00 | 0.890352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6204553.28 | 0.176782E+09 |
October | 0.00 | 0.921598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8177.70 | 0.412773E+09 |
November | 0.00 | 0.893725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632056E+09 |
December | 0.00 | 0.919113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778501E+09 |
Annual Sum or Average | 0.108552E+11 | 0.117101E+09 | 0.549287E+10 | ||||||
Minimum of Months | 0.00 | 0.832119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33600217.81 |
Maximum of Months | 0.00 | 0.924794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47904716.36 | 0.872473E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 10970.58 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 10970.58 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 10970.58 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 10970.58 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 10970.58 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 10970.58 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 10970.58 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 10970.58 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 10970.58 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 10970.58 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 10970.58 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 10970.58 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 10970.58 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 10970.58 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 545.79 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 861.69 | 02-JAN-04:52 |
February | 1169.53 | 01-FEB-00:10 | 545.79 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 903.87 | 06-FEB-02:52 |
March | 1169.53 | 01-MAR-00:10 | 545.79 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 676.87 | 23-MAR-05:56 |
April | 1169.53 | 01-APR-00:10 | 545.79 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.06 | 07-APR-16:44 | 477.68 | 03-APR-05:59 |
May | 1169.53 | 01-MAY-00:10 | 545.79 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.92 | 30-MAY-13:17 | 398.73 | 01-MAY-04:51 |
June | 1169.53 | 01-JUN-00:10 | 545.79 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.68 | 19-JUN-11:52 | 254.97 | 03-JUN-02:51 |
July | 1169.53 | 01-JUL-00:10 | 545.79 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.30 | 07-JUL-11:52 | 135.86 | 02-JUL-02:53 |
August | 1169.53 | 01-AUG-00:10 | 545.79 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.04 | 24-AUG-16:00 | 217.83 | 08-AUG-04:57 |
September | 1169.53 | 01-SEP-00:10 | 545.79 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.13 | 01-SEP-13:41 | 329.85 | 30-SEP-00:53 |
October | 1169.53 | 02-OCT-00:10 | 545.79 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 515.10 | 09-OCT-03:51 |
November | 1169.53 | 01-NOV-00:10 | 545.79 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 659.23 | 24-NOV-06:54 |
December | 1169.53 | 01-DEC-00:10 | 545.79 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 767.73 | 31-DEC-23:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 545.79 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.86 | |||||
Maximum of Months | 1169.53 | 545.79 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 259.68 | 903.87 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 632.03 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 192.97 | 02-JAN-04:51 |
February | 1354.32 | 01-FEB-00:10 | 632.03 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 203.81 | 06-FEB-02:51 |
March | 1354.32 | 01-MAR-00:10 | 632.03 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 158.59 | 23-MAR-05:51 |
April | 1354.32 | 01-APR-00:10 | 632.03 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 07-APR-12:58 | 116.33 | 03-APR-05:51 |
May | 1354.32 | 01-MAY-00:10 | 632.03 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.76 | 30-MAY-13:10 | 94.19 | 01-MAY-04:59 |
June | 1354.32 | 01-JUN-00:10 | 632.03 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.15 | 19-JUN-11:54 | 57.60 | 03-JUN-02:51 |
July | 1354.32 | 01-JUL-00:10 | 632.03 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 07-JUL-11:52 | 29.94 | 02-JUL-02:51 |
August | 1354.32 | 01-AUG-00:10 | 632.03 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.55 | 24-AUG-14:52 | 48.56 | 08-AUG-04:59 |
September | 1354.32 | 01-SEP-00:10 | 632.03 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.56 | 01-SEP-13:41 | 74.81 | 30-SEP-00:51 |
October | 1354.32 | 02-OCT-00:10 | 632.03 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.34 | 25-OCT-10:52 | 118.28 | 09-OCT-05:51 |
November | 1354.32 | 01-NOV-00:10 | 632.03 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 153.82 | 24-NOV-06:59 |
December | 1354.32 | 01-DEC-00:10 | 632.03 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 175.98 | 31-DEC-23:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 632.03 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | |||||
Maximum of Months | 1354.32 | 632.03 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 59.15 | 203.81 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 696.53 | 01-JAN-20:53 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 726.58 | 05-FEB-20:53 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 586.35 | 17-MAR-19:53 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 36.91 | 07-APR-12:52 | 474.95 | 13-APR-19:53 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 86.72 | 30-MAY-12:51 | 399.98 | 01-MAY-19:53 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 179.12 | 19-JUN-11:54 | 281.05 | 02-JUN-21:00 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 140.49 | 07-JUL-11:54 | 170.06 | 14-JUL-19:53 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 139.76 | 24-AUG-16:10 | 198.17 | 28-AUG-21:00 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 101.35 | 01-SEP-14:04 | 332.04 | 29-SEP-20:00 |
October | 907.20 | 02-OCT-00:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 13.18 | 04-OCT-12:51 | 438.12 | 18-OCT-19:53 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 577.60 | 23-NOV-20:53 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 665.94 | 31-DEC-20:53 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 170.06 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 179.12 | 726.58 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1097.76 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2309.48 | 02-JAN-04:51 |
February | 15368.40 | 01-FEB-00:10 | 1097.76 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2398.19 | 06-FEB-02:51 |
March | 15368.40 | 01-MAR-00:10 | 1097.76 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1883.96 | 23-MAR-04:13 |
April | 15368.40 | 01-APR-00:10 | 1097.76 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.89 | 08-APR-09:52 | 1384.84 | 01-APR-03:51 |
May | 15368.40 | 01-MAY-00:10 | 1097.76 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.91 | 30-MAY-13:15 | 1138.36 | 01-MAY-04:59 |
June | 15368.40 | 01-JUN-00:10 | 1097.76 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 689.53 | 19-JUN-11:52 | 706.62 | 03-JUN-02:51 |
July | 15368.40 | 01-JUL-00:10 | 1097.76 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 520.41 | 07-JUL-11:52 | 361.93 | 02-JUL-04:41 |
August | 15368.40 | 01-AUG-00:10 | 1097.76 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.98 | 24-AUG-15:00 | 605.37 | 08-AUG-04:59 |
September | 15368.40 | 01-SEP-00:10 | 1097.76 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.90 | 01-SEP-13:41 | 923.60 | 30-SEP-00:51 |
October | 15368.40 | 02-OCT-00:10 | 1097.76 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.01 | 25-OCT-12:26 | 1408.95 | 09-OCT-05:51 |
November | 15368.40 | 01-NOV-00:10 | 1097.76 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1834.37 | 24-NOV-05:51 |
December | 15368.40 | 01-DEC-00:10 | 1097.76 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2054.32 | 31-DEC-23:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 1097.76 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.93 | |||||
Maximum of Months | 15368.40 | 1097.76 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 689.53 | 2398.19 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 6463.27 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4801.23 | 02-JAN-04:51 |
February | 45622.98 | 01-FEB-00:10 | 6463.27 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 5015.79 | 06-FEB-02:51 |
March | 45622.98 | 01-MAR-00:10 | 6463.27 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 3843.58 | 23-MAR-04:43 |
April | 45622.98 | 01-APR-00:10 | 6463.27 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.99 | 07-APR-13:00 | 2833.52 | 03-APR-05:51 |
May | 45622.98 | 01-MAY-00:10 | 6463.27 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 692.72 | 30-MAY-13:10 | 2359.43 | 01-MAY-04:59 |
June | 45622.98 | 01-JUN-00:10 | 6463.27 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.61 | 19-JUN-11:54 | 1448.61 | 03-JUN-02:51 |
July | 45622.98 | 01-JUL-00:10 | 6463.27 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.94 | 07-JUL-11:52 | 749.38 | 02-JUL-04:51 |
August | 45622.98 | 01-AUG-00:10 | 6463.27 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1066.33 | 24-AUG-15:00 | 1233.01 | 08-AUG-04:59 |
September | 45622.98 | 01-SEP-00:10 | 6463.27 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 784.31 | 01-SEP-13:41 | 1859.59 | 30-SEP-00:51 |
October | 45622.98 | 02-OCT-00:10 | 6463.27 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.62 | 25-OCT-11:00 | 2898.86 | 29-OCT-06:59 |
November | 45622.98 | 01-NOV-00:10 | 6463.27 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3739.51 | 24-NOV-05:53 |
December | 45622.98 | 01-DEC-00:10 | 6463.27 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 4265.49 | 31-DEC-23:53 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 6463.27 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 749.38 | |||||
Maximum of Months | 45622.98 | 6463.27 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1418.61 | 5015.79 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.77 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263.56 | 02-JAN-04:51 |
February | 180.00 | 01-FEB-00:10 | 137.77 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 270.73 | 06-FEB-02:54 |
March | 180.00 | 01-MAR-00:10 | 137.77 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.92 | 27-MAR-16:07 | 200.17 | 23-MAR-05:51 |
April | 180.00 | 01-APR-00:10 | 137.77 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.71 | 07-APR-16:41 | 141.47 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.77 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 | 30-MAY-15:51 | 110.09 | 01-MAY-04:51 |
June | 180.00 | 01-JUN-00:10 | 137.77 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 19-JUN-12:00 | 55.76 | 02-JUN-07:00 |
July | 180.00 | 01-JUL-00:10 | 137.77 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 10-JUL-15:20 | 19.88 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 137.77 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.51 | 24-AUG-15:20 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 137.77 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 14-SEP-15:51 | 80.56 | 24-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 137.77 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 04-OCT-15:18 | 142.34 | 09-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.77 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 194.98 | 24-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.77 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 226.89 | 31-DEC-23:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | |||||
Maximum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 270.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263.54 | 02-JAN-04:51 |
February | 180.00 | 01-FEB-00:10 | 137.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 270.71 | 06-FEB-02:54 |
March | 180.00 | 01-MAR-00:10 | 137.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 200.15 | 23-MAR-05:51 |
April | 180.00 | 01-APR-00:10 | 137.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.59 | 08-APR-09:51 | 141.46 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 30-MAY-15:51 | 110.08 | 01-MAY-04:51 |
June | 180.00 | 01-JUN-00:10 | 137.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 19-JUN-12:00 | 66.27 | 03-JUN-18:01 |
July | 180.00 | 01-JUL-00:10 | 137.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 10-JUL-15:20 | 41.94 | 01-JUL-17:51 |
August | 180.00 | 01-AUG-00:10 | 137.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24-AUG-15:20 | 43.62 | 08-AUG-04:51 |
September | 180.00 | 01-SEP-00:10 | 137.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 14-SEP-15:26 | 80.56 | 24-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 137.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 | 25-OCT-09:51 | 142.33 | 09-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 194.96 | 24-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 226.87 | 31-DEC-23:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.94 | |||||
Maximum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 270.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 86.58 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 65.04 | 31-JAN-07:20 |
February | 0.00 | 01-FEB-00:10 | 86.58 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 74.53 | 05-FEB-23:51 |
March | 0.00 | 01-MAR-00:10 | 86.58 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 59.56 | 23-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 86.58 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 46.52 | 12-APR-06:20 |
May | 0.00 | 01-MAY-00:10 | 86.58 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 30-MAY-13:00 | 39.02 | 01-MAY-05:10 |
June | 0.00 | 01-JUN-00:10 | 86.58 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 19-JUN-12:00 | 26.20 | 03-JUN-02:51 |
July | 0.00 | 01-JUL-00:10 | 86.58 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 | 07-JUL-12:00 | 16.33 | 02-JUL-04:58 |
August | 0.00 | 01-AUG-00:10 | 86.58 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 | 24-AUG-14:51 | 23.15 | 08-AUG-04:52 |
September | 0.00 | 01-SEP-00:10 | 86.58 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 01-SEP-14:00 | 32.47 | 24-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 86.58 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 50.04 | 29-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 86.58 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 60.03 | 24-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 86.58 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 63.64 | 22-DEC-07:20 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 86.58 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | |||||
Maximum of Months | 0.00 | 86.58 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 74.53 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 86.61 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 73.56 | 02-JAN-04:51 |
February | 180.00 | 01-FEB-00:10 | 86.61 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 75.56 | 06-FEB-02:53 |
March | 180.00 | 01-MAR-00:10 | 86.61 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 27-MAR-15:51 | 55.86 | 23-MAR-05:53 |
April | 180.00 | 01-APR-00:10 | 86.61 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 | 08-APR-09:51 | 39.48 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 86.61 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 | 30-MAY-15:54 | 30.72 | 01-MAY-04:51 |
June | 180.00 | 01-JUN-00:10 | 86.61 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 19-JUN-11:51 | 16.17 | 02-JUN-07:10 |
July | 180.00 | 01-JUL-00:10 | 86.61 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 | 10-JUL-15:20 | 7.72 | 01-JUL-21:10 |
August | 180.00 | 01-AUG-00:10 | 86.61 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 | 24-AUG-15:20 | 12.17 | 08-AUG-04:51 |
September | 180.00 | 01-SEP-00:10 | 86.61 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 | 14-SEP-15:25 | 22.48 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 86.61 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 | 04-OCT-12:51 | 40.15 | 29-OCT-07:00 |
November | 180.00 | 01-NOV-00:10 | 86.61 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 54.42 | 24-NOV-06:52 |
December | 180.00 | 01-DEC-00:10 | 86.61 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 63.32 | 31-DEC-23:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.72 | |||||
Maximum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.27 | 75.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.77 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263.56 | 02-JAN-04:51 |
February | 180.00 | 01-FEB-00:10 | 137.77 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 270.73 | 06-FEB-02:54 |
March | 180.00 | 01-MAR-00:10 | 137.77 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.92 | 27-MAR-16:04 | 200.17 | 23-MAR-05:51 |
April | 180.00 | 01-APR-00:10 | 137.77 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.71 | 07-APR-16:44 | 141.47 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.77 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 | 30-MAY-15:51 | 110.09 | 01-MAY-04:53 |
June | 180.00 | 01-JUN-00:10 | 137.77 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 19-JUN-12:00 | 62.94 | 02-JUN-07:00 |
July | 180.00 | 01-JUL-00:10 | 137.77 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 10-JUL-15:17 | 19.88 | 02-JUL-04:51 |
August | 180.00 | 01-AUG-00:10 | 137.77 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.51 | 24-AUG-15:18 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 137.77 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 14-SEP-15:54 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 137.77 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 | 04-OCT-15:16 | 142.34 | 09-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.77 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 194.98 | 24-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.77 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 226.89 | 31-DEC-23:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 | |||||
Maximum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 270.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 263.54 | 02-JAN-04:51 |
February | 180.00 | 01-FEB-00:10 | 137.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 270.71 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 137.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 27-MAR-15:51 | 200.15 | 23-MAR-05:51 |
April | 180.00 | 01-APR-00:10 | 137.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 08-APR-09:51 | 141.46 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 30-MAY-15:51 | 110.08 | 01-MAY-04:53 |
June | 180.00 | 01-JUN-00:10 | 137.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 19-JUN-12:00 | 63.49 | 03-JUN-08:00 |
July | 180.00 | 01-JUL-00:10 | 137.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 10-JUL-15:18 | 32.11 | 11-JUL-08:00 |
August | 180.00 | 01-AUG-00:10 | 137.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24-AUG-15:17 | 48.63 | 25-AUG-08:00 |
September | 180.00 | 01-SEP-00:10 | 137.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 14-SEP-15:44 | 80.56 | 24-SEP-05:53 |
October | 180.00 | 01-OCT-00:10 | 137.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 | 25-OCT-09:51 | 142.33 | 09-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 194.96 | 24-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 226.87 | 31-DEC-23:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.11 | |||||
Maximum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 270.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.77 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 264.11 | 02-JAN-04:51 |
February | 180.00 | 01-FEB-00:10 | 137.77 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 271.26 | 06-FEB-02:54 |
March | 180.00 | 01-MAR-00:10 | 137.77 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 27-MAR-16:09 | 200.68 | 23-MAR-05:51 |
April | 180.00 | 01-APR-00:10 | 137.77 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 07-APR-16:45 | 141.95 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.77 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 | 30-MAY-15:51 | 110.55 | 01-MAY-04:51 |
June | 180.00 | 01-JUN-00:10 | 137.77 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.58 | 19-JUN-12:00 | 56.02 | 03-JUN-04:52 |
July | 180.00 | 01-JUL-00:10 | 137.77 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 | 10-JUL-15:20 | 20.29 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 137.77 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.13 | 24-AUG-15:30 | 44.05 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 137.77 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.45 | 14-SEP-15:41 | 81.01 | 24-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 137.77 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 | 04-OCT-15:20 | 142.82 | 09-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.77 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 195.48 | 24-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.77 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 227.41 | 31-DEC-23:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 | |||||
Maximum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.58 | 271.26 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 264.08 | 02-JAN-04:51 |
February | 180.00 | 01-FEB-00:10 | 137.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 271.24 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 137.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 200.66 | 23-MAR-05:51 |
April | 180.00 | 01-APR-00:10 | 137.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.03 | 08-APR-09:51 | 141.94 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.79 | 30-MAY-15:51 | 110.54 | 01-MAY-04:51 |
June | 180.00 | 01-JUN-00:10 | 137.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 19-JUN-12:00 | 74.70 | 03-JUN-18:01 |
July | 180.00 | 01-JUL-00:10 | 137.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.78 | 10-JUL-15:20 | 49.74 | 01-JUL-18:01 |
August | 180.00 | 01-AUG-00:10 | 137.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.13 | 24-AUG-15:30 | 44.05 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 137.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.45 | 14-SEP-15:41 | 81.01 | 24-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 137.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.34 | 25-OCT-09:51 | 142.81 | 09-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 195.46 | 24-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 227.39 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.05 | |||||
Maximum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 271.24 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 86.61 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 135.11 | 02-JAN-04:51 |
February | 180.00 | 01-FEB-00:10 | 86.61 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 138.77 | 06-FEB-02:54 |
March | 180.00 | 01-MAR-00:10 | 86.61 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 | 27-MAR-16:07 | 102.66 | 23-MAR-05:51 |
April | 180.00 | 01-APR-00:10 | 86.61 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 | 07-APR-16:44 | 72.62 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 86.61 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 30-MAY-16:00 | 56.56 | 01-MAY-04:51 |
June | 180.00 | 01-JUN-00:10 | 86.61 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | 19-JUN-12:00 | 29.11 | 02-JUN-07:00 |
July | 180.00 | 01-JUL-00:10 | 86.61 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 | 10-JUL-15:20 | 10.38 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 86.61 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 | 24-AUG-15:36 | 22.54 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 86.61 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 14-SEP-15:41 | 41.45 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 86.61 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 | 02-OCT-15:54 | 73.07 | 09-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 86.61 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 100.01 | 24-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 86.61 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 116.34 | 31-DEC-23:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 | |||||
Maximum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | 138.77 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1927.76 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 710.50 | 02-JAN-04:51 |
February | 26988.77 | 01-FEB-00:10 | 1927.76 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 733.39 | 06-FEB-02:51 |
March | 26988.77 | 01-MAR-00:10 | 1927.76 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 574.04 | 23-MAR-04:13 |
April | 26988.77 | 01-APR-00:10 | 1927.76 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.81 | 07-APR-14:06 | 436.21 | 03-APR-05:53 |
May | 26988.77 | 01-MAY-00:10 | 1927.76 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.51 | 30-MAY-13:21 | 364.34 | 01-MAY-04:59 |
June | 26988.77 | 01-JUN-00:10 | 1927.76 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.32 | 19-JUN-11:52 | 230.41 | 03-JUN-02:53 |
July | 26988.77 | 01-JUL-00:10 | 1927.76 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.90 | 07-JUL-11:52 | 131.71 | 01-JUL-22:53 |
August | 26988.77 | 01-AUG-00:10 | 1927.76 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.35 | 24-AUG-15:00 | 199.11 | 08-AUG-04:59 |
September | 26988.77 | 01-SEP-00:10 | 1927.76 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.67 | 01-SEP-13:41 | 291.28 | 24-SEP-05:59 |
October | 26988.77 | 02-OCT-00:10 | 1927.76 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.91 | 25-OCT-13:52 | 441.42 | 29-OCT-06:59 |
November | 26988.77 | 01-NOV-00:10 | 1927.76 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 557.76 | 24-NOV-05:53 |
December | 26988.77 | 01-DEC-00:10 | 1927.76 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 643.55 | 31-DEC-23:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.71 | |||||
Maximum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 182.32 | 733.39 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1927.76 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 717.70 | 02-JAN-04:51 |
February | 26988.77 | 01-FEB-00:10 | 1927.76 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 743.94 | 05-FEB-23:51 |
March | 26988.77 | 01-MAR-00:10 | 1927.76 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 583.11 | 23-MAR-05:59 |
April | 26988.77 | 01-APR-00:10 | 1927.76 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.03 | 07-APR-14:06 | 444.62 | 03-APR-05:59 |
May | 26988.77 | 01-MAY-00:10 | 1927.76 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.83 | 30-MAY-13:21 | 370.03 | 01-MAY-04:59 |
June | 26988.77 | 01-JUN-00:10 | 1927.76 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.58 | 19-JUN-11:52 | 235.64 | 03-JUN-02:53 |
July | 26988.77 | 01-JUL-00:10 | 1927.76 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.32 | 07-JUL-11:52 | 138.31 | 01-JUL-22:53 |
August | 26988.77 | 01-AUG-00:10 | 1927.76 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.78 | 24-AUG-15:00 | 203.56 | 08-AUG-04:59 |
September | 26988.77 | 01-SEP-00:10 | 1927.76 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.78 | 01-SEP-13:41 | 296.84 | 24-SEP-05:59 |
October | 26988.77 | 02-OCT-00:10 | 1927.76 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 | 25-OCT-13:52 | 449.07 | 29-OCT-06:59 |
November | 26988.77 | 01-NOV-00:10 | 1927.76 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 567.43 | 24-NOV-06:59 |
December | 26988.77 | 01-DEC-00:10 | 1927.76 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 654.80 | 31-DEC-23:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.31 | |||||
Maximum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 175.58 | 743.94 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 688.82 | 02-JAN-08:49 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 724.78 | 05-FEB-23:41 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 556.52 | 23-MAR-06:19 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 453.76 | 13-APR-18:51 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 26.08 | 30-MAY-13:21 | 378.88 | 01-MAY-19:51 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 83.96 | 19-JUN-12:00 | 273.44 | 02-JUN-07:09 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 43.83 | 10-JUL-15:00 | 185.19 | 01-JUL-19:53 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 53.31 | 24-AUG-15:00 | 208.27 | 08-AUG-05:19 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 43.83 | 01-SEP-13:29 | 306.29 | 29-SEP-22:41 |
October | 2401.70 | 02-OCT-00:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 451.98 | 29-OCT-06:59 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 578.75 | 24-NOV-07:59 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 647.20 | 31-DEC-23:41 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 185.19 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 83.96 | 724.78 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1511.55 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 412.34 | 02-JAN-04:58 |
February | 0.00 | 1511.55 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 440.99 | 06-FEB-02:51 |
March | 0.00 | 1511.55 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 344.16 | 23-MAR-06:00 |
April | 0.00 | 1511.55 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.52 | 07-APR-12:52 | 255.78 | 03-APR-05:51 |
May | 0.00 | 1511.55 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.28 | 30-MAY-12:51 | 205.81 | 01-MAY-04:53 |
June | 0.00 | 1511.55 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.25 | 19-JUN-11:54 | 119.21 | 03-JUN-02:53 |
July | 0.00 | 1511.55 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.72 | 07-JUL-11:52 | 62.78 | 02-JUL-02:58 |
August | 0.00 | 1511.55 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.45 | 24-AUG-14:52 | 100.91 | 08-AUG-04:51 |
September | 0.00 | 1511.55 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.74 | 01-SEP-13:41 | 159.10 | 24-SEP-05:51 |
October | 0.00 | 1511.55 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.64 | 04-OCT-12:51 | 257.40 | 09-OCT-05:53 |
November | 0.00 | 1511.55 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 334.34 | 24-NOV-07:00 |
December | 0.00 | 1511.55 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 384.41 | 31-DEC-23:51 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.78 | ||||
Maximum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 130.25 | 440.99 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 155.22 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 282.79 | 02-JAN-04:52 |
February | 0.00 | 155.22 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 294.55 | 06-FEB-02:56 |
March | 0.00 | 155.22 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 221.42 | 23-MAR-05:59 |
April | 0.00 | 155.22 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.96 | 07-APR-12:52 | 162.15 | 03-APR-05:59 |
May | 0.00 | 155.22 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.68 | 30-MAY-12:53 | 133.10 | 01-MAY-04:59 |
June | 0.00 | 155.22 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.95 | 19-JUN-11:52 | 79.71 | 03-JUN-02:51 |
July | 0.00 | 155.22 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.63 | 07-JUL-11:52 | 40.54 | 02-JUL-02:51 |
August | 0.00 | 155.22 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 24-AUG-14:52 | 67.53 | 08-AUG-04:59 |
September | 0.00 | 155.22 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.28 | 01-SEP-13:41 | 104.21 | 24-SEP-05:59 |
October | 0.00 | 155.22 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.06 | 25-OCT-10:52 | 169.28 | 09-OCT-03:51 |
November | 0.00 | 155.22 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 214.66 | 24-NOV-06:59 |
December | 0.00 | 155.22 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 247.83 | 31-DEC-23:51 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 155.22 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.54 | ||||
Maximum of Months | 0.00 | 155.22 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 89.95 | 294.55 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 838.75 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 305.94 | 02-JAN-04:52 |
February | 0.00 | 838.75 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 317.48 | 06-FEB-02:52 |
March | 0.00 | 838.75 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 27-MAR-16:00 | 239.44 | 23-MAR-06:00 |
April | 0.00 | 838.75 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.87 | 07-APR-12:52 | 170.06 | 03-APR-05:54 |
May | 0.00 | 838.75 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.86 | 30-MAY-12:53 | 132.14 | 01-MAY-04:56 |
June | 0.00 | 838.75 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.09 | 19-JUN-11:52 | 73.66 | 03-JUN-02:51 |
July | 0.00 | 838.75 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.44 | 07-JUL-11:52 | 32.41 | 02-JUL-02:51 |
August | 0.00 | 838.75 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | 24-AUG-16:00 | 62.50 | 08-AUG-04:59 |
September | 0.00 | 838.75 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.12 | 01-SEP-13:51 | 96.97 | 24-SEP-05:59 |
October | 0.00 | 838.75 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 25-OCT-11:00 | 171.14 | 09-OCT-05:53 |
November | 0.00 | 838.75 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 231.20 | 24-NOV-07:00 |
December | 0.00 | 838.75 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 267.20 | 31-DEC-23:52 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 838.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.41 | |||
Maximum of Months | 0.00 | 838.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.09 | 317.48 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 887.69 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 551.53 | 02-JAN-04:52 |
February | 0.00 | 887.69 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 575.65 | 06-FEB-02:52 |
March | 0.00 | 887.69 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 432.36 | 23-MAR-03:51 |
April | 0.00 | 887.69 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 | 07-APR-12:52 | 321.25 | 01-APR-03:51 |
May | 0.00 | 887.69 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.08 | 30-MAY-12:53 | 271.32 | 01-MAY-04:51 |
June | 0.00 | 887.69 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.99 | 19-JUN-11:52 | 163.87 | 03-JUN-02:53 |
July | 0.00 | 887.69 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.81 | 07-JUL-11:52 | 86.90 | 02-JUL-03:00 |
August | 0.00 | 887.69 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.91 | 24-AUG-16:00 | 138.79 | 08-AUG-04:51 |
September | 0.00 | 887.69 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.13 | 01-SEP-13:41 | 212.65 | 24-SEP-05:59 |
October | 0.00 | 887.69 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.56 | 25-OCT-11:00 | 337.11 | 09-OCT-03:51 |
November | 0.00 | 887.69 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 416.47 | 24-NOV-06:52 |
December | 0.00 | 887.69 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 484.76 | 31-DEC-23:54 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 887.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.90 | |||
Maximum of Months | 0.00 | 887.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.99 | 575.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 23025.11 | 23-JAN-22:00 | 102239.04 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22490.38 | 01-FEB-22:00 | 102239.04 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29374.41 | 27-MAR-18:53 | 89459.16 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28852.17 | 16-APR-19:07 | 76679.28 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29739.13 | 31-MAY-20:51 | 102239.04 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30761.82 | 23-JUN-20:51 | 102239.04 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31358.66 | 11-JUL-23:37 | 115018.92 | 24379.07 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32080.50 | 19-AUG-00:57 | 115018.92 | 24379.07 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32958.60 | 10-SEP-00:55 | 89459.16 | 36568.61 | 40558.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34232.71 | 22-OCT-11:57 | 38339.64 | 36568.61 | 40558.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33057.14 | 04-NOV-15:59 | 38339.64 | 30473.84 | 35488.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25169.36 | 01-DEC-22:00 | 102239.04 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 22490.38 | 38339.64 | 24379.07 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34232.71 | 115018.92 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3064.73 | 17-JAN-13:42 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.96 |
February | 2882.33 | 02-FEB-13:30 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.82 |
March | 4282.31 | 03-MAR-13:25 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.59 |
April | 4523.39 | 07-APR-12:04 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 10.23 | 0.00 |
May | 4234.50 | 30-MAY-11:19 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 107.06 | 0.00 |
June | 4298.81 | 22-JUN-15:19 | 6497.40 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 124.69 | 0.00 |
July | 4251.88 | 11-JUL-15:03 | 6497.40 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 84.42 | 0.00 |
August | 4680.14 | 30-AUG-13:26 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 52.59 | 0.00 |
September | 4910.46 | 28-SEP-12:43 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.95 |
October | 4985.35 | 13-OCT-12:49 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.49 |
November | 4467.23 | 04-NOV-12:05 | 3898.44 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.35 |
December | 3526.18 | 17-DEC-13:00 | 3898.44 | 1819.31 | 2886.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2882.33 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4985.35 | 6497.40 | 1819.31 | 2886.75 | 0.00 | 0.00 | 0.00 | 0.00 | 124.69 | 476.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1929.70 | 19-JAN-22:00 | 12038.40 | 5618.06 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.59 |
February | 1890.87 | 02-FEB-22:00 | 12038.40 | 5618.06 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.82 |
March | 2791.05 | 27-MAR-18:53 | 10533.60 | 5618.06 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 |
April | 2941.11 | 07-APR-23:20 | 12188.88 | 1264.06 | 2256.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.23 |
May | 3102.39 | 31-MAY-20:51 | 12038.40 | 5618.06 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 |
June | 3197.17 | 22-JUN-23:13 | 13543.20 | 1404.52 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 |
July | 3231.14 | 10-JUL-23:13 | 13543.20 | 1404.52 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 |
August | 3215.62 | 19-AUG-00:57 | 13543.20 | 1404.52 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.18 |
September | 3209.87 | 01-SEP-23:57 | 13543.20 | 1404.52 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
October | 3049.62 | 05-OCT-23:45 | 13543.20 | 1404.52 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.03 |
November | 2725.07 | 04-NOV-12:05 | 4514.40 | 1755.64 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.92 |
December | 1953.48 | 18-DEC-22:00 | 12038.40 | 5618.06 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.32 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1890.87 | 4514.40 | 1264.06 | 2256.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | |
Maximum of Months | 3231.14 | 13543.20 | 5618.06 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1813.81 | 23-JAN-22:00 | 0.00 | 13436.03 | 7952.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.89 |
February | 1718.12 | 24-FEB-20:52 | 0.00 | 15115.54 | 8394.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.47 |
March | 2750.00 | 27-MAR-19:27 | 0.00 | 15115.54 | 8394.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.55 |
April | 2805.64 | 10-APR-19:12 | 0.00 | 15115.54 | 8394.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.41 |
May | 3106.88 | 29-MAY-21:07 | 0.00 | 8397.52 | 5301.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.81 |
June | 3208.47 | 22-JUN-23:13 | 0.00 | 3359.01 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
July | 3260.09 | 10-JUL-23:18 | 0.00 | 3359.01 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.10 | 0.00 |
August | 3239.84 | 19-AUG-00:57 | 0.00 | 3359.01 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.35 |
September | 3171.99 | 01-SEP-23:57 | 0.00 | 3359.01 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 | 0.00 |
October | 2983.83 | 03-OCT-20:01 | 0.00 | 13436.03 | 7952.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.86 |
November | 2657.05 | 04-NOV-18:23 | 0.00 | 11756.53 | 7069.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.81 |
December | 1806.31 | 04-DEC-22:00 | 0.00 | 13436.03 | 7952.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.44 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1718.12 | 0.00 | 3359.01 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3260.09 | 0.00 | 15115.54 | 8394.47 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 | 265.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 603.57 | 24-JAN-11:54 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.10 |
February | 534.06 | 20-FEB-15:56 | 0.00 | 344.94 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.10 |
March | 1082.68 | 27-MAR-13:33 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 |
April | 1175.46 | 08-APR-14:53 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 |
May | 1221.11 | 30-MAY-11:19 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 39.26 | 0.00 |
June | 1282.79 | 22-JUN-23:13 | 0.00 | 344.94 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 | 0.00 |
July | 1319.62 | 10-JUL-23:18 | 0.00 | 344.94 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 0.00 |
August | 1311.42 | 19-AUG-00:57 | 0.00 | 344.94 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.32 |
September | 1298.38 | 01-SEP-13:39 | 0.00 | 388.06 | 802.94 | 0.00 | 0.00 | 0.00 | 0.00 | 49.61 | 0.00 |
October | 1194.49 | 13-OCT-10:24 | 0.00 | 388.06 | 802.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 |
November | 1070.60 | 04-NOV-15:59 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.73 |
December | 599.85 | 17-DEC-14:14 | 0.00 | 344.94 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.10 |
Annual Sum or Average | |||||||||||
Minimum of Months | 534.06 | 0.00 | 344.94 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1319.62 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 49.61 | 117.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 61820.14 | 19-JAN-20:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 465.89 |
February | 61594.71 | 17-FEB-20:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 521.78 |
March | 67329.82 | 27-MAR-19:41 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 225.73 |
April | 67777.36 | 10-APR-19:11 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 208.48 |
May | 71735.91 | 31-MAY-20:01 | 8064.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 171.74 |
June | 72271.66 | 23-JUN-19:51 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 118.02 |
July | 66890.50 | 10-JUL-19:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 46.24 |
August | 72353.04 | 30-AUG-19:51 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 109.39 |
September | 71314.41 | 08-SEP-19:51 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 170.96 |
October | 71291.00 | 03-OCT-19:51 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 170.90 |
November | 63549.66 | 03-NOV-19:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 308.56 |
December | 61904.27 | 19-DEC-20:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 388.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 61594.71 | 7056.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 46.24 | |
Maximum of Months | 72353.04 | 8064.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 521.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13826.88 | 17-JAN-13:32 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 969.34 |
February | 13134.56 | 02-FEB-13:24 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1233.03 |
March | 18143.29 | 03-MAR-13:25 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.81 |
April | 18865.21 | 08-APR-11:53 | 51228.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 |
May | 18067.49 | 31-MAY-23:03 | 153684.00 | 2439.47 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.12 |
June | 19047.23 | 22-JUN-23:13 | 153684.00 | 2439.47 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.42 |
July | 19301.03 | 10-JUL-23:13 | 153684.00 | 2439.47 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.87 |
August | 19127.97 | 24-AUG-23:13 | 153684.00 | 2439.47 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.72 |
September | 20307.29 | 30-SEP-12:46 | 51228.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.89 |
October | 20367.19 | 13-OCT-12:05 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.70 |
November | 19108.02 | 04-NOV-12:05 | 51228.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.77 |
December | 15913.49 | 17-DEC-13:00 | 51228.00 | 805.03 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.89 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13134.56 | 34152.00 | 670.85 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.87 | |
Maximum of Months | 20367.19 | 153684.00 | 2439.47 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1233.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 40733.00 | 19-JAN-23:00 | 456229.80 | 43088.47 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2477.45 |
February | 39770.96 | 22-FEB-23:00 | 456229.80 | 43088.47 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2918.39 |
March | 56198.81 | 27-MAR-18:53 | 354845.40 | 57451.29 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.09 |
April | 60154.49 | 07-APR-23:20 | 410606.82 | 12926.54 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894.43 |
May | 61964.38 | 31-MAY-23:03 | 456229.80 | 14362.82 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.27 |
June | 64813.87 | 22-JUN-23:13 | 456229.80 | 14362.82 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.75 |
July | 65265.93 | 10-JUL-23:13 | 456229.80 | 14362.82 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.98 |
August | 64933.63 | 19-AUG-00:57 | 456229.80 | 14362.82 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.34 |
September | 65235.02 | 01-SEP-23:57 | 456229.80 | 14362.82 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.25 |
October | 62286.38 | 05-OCT-23:45 | 456229.80 | 14362.82 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 745.00 |
November | 56730.23 | 04-NOV-12:05 | 152076.60 | 15440.03 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.53 |
December | 41055.58 | 17-DEC-13:00 | 152076.60 | 18528.04 | 42228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1556.66 |
Annual Sum or Average | |||||||||||
Minimum of Months | 39770.96 | 152076.60 | 12926.54 | 28504.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.25 | |
Maximum of Months | 65265.93 | 456229.80 | 57451.29 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2918.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3218.18 | 17-JAN-16:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.46 |
February | 3219.11 | 02-FEB-16:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.02 |
March | 3257.54 | 15-MAR-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.28 |
April | 3275.57 | 10-APR-18:01 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 |
May | 3318.47 | 27-MAY-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 |
June | 3075.83 | 17-JUN-15:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 0.00 |
July | 3107.87 | 22-JUL-15:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 24.82 | 0.00 |
August | 3056.43 | 29-AUG-18:01 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
September | 3314.91 | 10-SEP-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.88 |
October | 3258.72 | 08-OCT-15:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.15 |
November | 3236.31 | 02-NOV-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 |
December | 3142.94 | 17-DEC-16:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.51 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3056.43 | 540.00 | 86.11 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3318.47 | 1386.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 24.82 | 136.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2262.48 | 17-JAN-16:11 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.80 |
February | 2882.39 | 20-FEB-16:11 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.33 |
March | 3192.60 | 15-MAR-15:11 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.75 |
April | 3208.43 | 11-APR-15:11 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.97 |
May | 3318.00 | 27-MAY-21:11 | 1386.00 | 1170.91 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.98 |
June | 3123.71 | 22-JUN-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 | 0.00 |
July | 3027.48 | 20-JUL-18:01 | 1386.00 | 1222.56 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 | 0.00 |
August | 3158.26 | 28-AUG-21:11 | 1800.00 | 929.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.37 |
September | 3290.65 | 10-SEP-21:11 | 1386.00 | 1170.91 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.40 |
October | 3190.51 | 07-OCT-15:11 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.29 |
November | 3035.63 | 01-NOV-15:11 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.55 |
December | 905.89 | 17-DEC-16:11 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.01 |
Annual Sum or Average | |||||||||||
Minimum of Months | 905.89 | 360.00 | 86.10 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3318.00 | 1800.00 | 1222.56 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 | 102.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 125.77 | 31-JAN-15:01 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 |
February | 150.28 | 20-FEB-15:01 | 0.00 | 54.11 | 335.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.89 |
March | 205.71 | 15-MAR-15:03 | 0.00 | 69.27 | 490.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.21 |
April | 368.33 | 08-APR-12:21 | 0.00 | 48.70 | 301.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 |
May | 266.01 | 22-MAY-15:03 | 0.00 | 69.27 | 490.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 |
June | 327.13 | 19-JUN-20:12 | 0.00 | 768.42 | 1780.14 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 0.00 |
July | 339.79 | 08-JUL-07:52 | 0.00 | 487.03 | 2321.92 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 0.00 |
August | 387.22 | 30-AUG-12:32 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 | 0.00 |
September | 511.27 | 28-SEP-12:21 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 |
October | 561.97 | 04-OCT-12:01 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 |
November | 488.25 | 02-NOV-12:21 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.37 |
December | 287.68 | 21-DEC-13:22 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.77 |
Annual Sum or Average | |||||||||||
Minimum of Months | 125.77 | 0.00 | 48.70 | 301.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 561.97 | 0.00 | 768.42 | 2321.92 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 | 56.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 865.28 | 22-JAN-09:01 | 540.00 | 202.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 |
February | 878.74 | 25-FEB-09:01 | 540.00 | 202.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.64 |
March | 946.99 | 15-MAR-18:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 |
April | 995.40 | 11-APR-18:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.76 |
May | 1061.27 | 27-MAY-21:11 | 1386.00 | 736.16 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 |
June | 1069.98 | 04-JUN-08:11 | 540.00 | 202.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 |
July | 1001.00 | 11-JUL-18:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 0.00 |
August | 1019.83 | 28-AUG-21:11 | 1800.00 | 584.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 |
September | 1037.09 | 10-SEP-21:11 | 1386.00 | 736.16 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 |
October | 995.08 | 25-OCT-21:11 | 1800.00 | 584.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.47 |
November | 956.66 | 02-NOV-18:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 |
December | 913.29 | 02-DEC-09:01 | 540.00 | 202.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.61 |
Annual Sum or Average | |||||||||||
Minimum of Months | 865.28 | 540.00 | 202.08 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1069.98 | 1800.00 | 768.63 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 48.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2622.67 | 20-JAN-09:01 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.10 |
February | 2847.22 | 25-FEB-09:01 | 540.00 | 321.46 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.93 |
March | 2924.93 | 15-MAR-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.98 |
April | 2954.31 | 12-APR-08:61 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.81 |
May | 2981.56 | 27-MAY-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.94 |
June | 2784.82 | 08-JUN-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
July | 2814.76 | 17-JUL-08:61 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 | 0.00 |
August | 2821.05 | 13-AUG-08:61 | 540.00 | 321.46 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 22.87 | 0.00 |
September | 2989.53 | 10-SEP-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.78 |
October | 2926.86 | 07-OCT-15:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.43 |
November | 2885.51 | 02-NOV-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.96 |
December | 2692.07 | 02-DEC-09:01 | 540.00 | 321.46 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.95 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2622.67 | 360.00 | 86.11 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2989.53 | 1170.00 | 1377.70 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 22.87 | 182.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 622.33 | 24-JAN-19:04 | 1386.00 | 1222.56 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.38 |
February | 2689.41 | 25-FEB-09:01 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.73 |
March | 2655.70 | 23-MAR-08:61 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.79 |
April | 2964.97 | 08-APR-08:11 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 |
May | 3285.27 | 30-MAY-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 |
June | 3295.66 | 22-JUN-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 |
July | 3167.21 | 11-JUL-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 |
August | 3254.63 | 22-AUG-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
September | 3195.66 | 10-SEP-08:11 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.44 |
October | 2734.80 | 25-OCT-21:11 | 1800.00 | 929.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.07 |
November | 2480.52 | 04-NOV-08:61 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 |
December | 2024.56 | 17-DEC-09:01 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 622.33 | 360.00 | 321.43 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | |
Maximum of Months | 3295.66 | 1800.00 | 1222.56 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 598.22 | 19-JAN-13:54 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.43 |
February | 829.95 | 20-FEB-15:42 | 0.00 | 1863.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.15 |
March | 1857.95 | 27-MAR-17:14 | 0.00 | 5591.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 |
April | 2069.84 | 08-APR-14:53 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
May | 2131.88 | 30-MAY-13:15 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.47 | 0.00 |
June | 2271.31 | 20-JUN-15:17 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.01 | 0.00 |
July | 2338.35 | 12-JUL-12:29 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.93 | 0.00 |
August | 2447.20 | 20-AUG-14:49 | 0.00 | 1863.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.19 | 0.00 |
September | 2417.59 | 01-SEP-13:39 | 0.00 | 2096.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.39 | 0.00 |
October | 2115.71 | 05-OCT-11:36 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
November | 1774.87 | 04-NOV-15:59 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 |
December | 959.06 | 17-DEC-14:24 | 0.00 | 1863.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 598.22 | 0.00 | 1863.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2447.20 | 0.00 | 5591.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.47 | 118.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3380.47 | 17-JAN-16:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.93 |
February | 3373.64 | 02-FEB-16:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.31 |
March | 3417.44 | 15-MAR-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.62 |
April | 3437.35 | 10-APR-18:01 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 |
May | 3487.66 | 27-MAY-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 |
June | 3255.43 | 25-JUN-15:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 | 0.00 |
July | 3283.83 | 22-JUL-15:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 | 0.00 |
August | 3240.39 | 15-AUG-18:01 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 22.54 | 0.00 |
September | 3483.22 | 10-SEP-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 |
October | 3418.13 | 08-OCT-15:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.49 |
November | 3393.71 | 02-NOV-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.59 |
December | 3352.52 | 17-DEC-16:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.47 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3240.39 | 540.00 | 86.11 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3487.66 | 1386.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 | 136.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1791.22 | 17-JAN-16:11 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.16 |
February | 2888.34 | 20-FEB-16:11 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.78 |
March | 3334.59 | 11-MAR-16:11 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.01 |
April | 3488.02 | 09-APR-17:31 | 972.00 | 1170.91 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.05 |
May | 3659.20 | 27-MAY-21:11 | 1386.00 | 1170.91 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.75 |
June | 3317.44 | 20-JUN-21:11 | 1800.00 | 929.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 |
July | 3288.06 | 04-JUL-21:11 | 1386.00 | 1170.91 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.35 |
August | 3345.46 | 28-AUG-21:11 | 1800.00 | 929.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 |
September | 3551.87 | 10-SEP-21:11 | 1386.00 | 1170.91 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.78 |
October | 3341.96 | 07-OCT-15:11 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.53 |
November | 3124.77 | 01-NOV-15:11 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.05 |
December | 864.31 | 25-DEC-16:13 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 864.31 | 540.00 | 86.10 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.35 | |
Maximum of Months | 3659.20 | 1800.00 | 1170.91 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1587.90 | 31-JAN-16:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.31 |
February | 1594.28 | 02-FEB-16:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 |
March | 1592.76 | 13-MAR-15:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.38 |
April | 1591.84 | 11-APR-15:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.71 |
May | 1621.86 | 20-MAY-18:01 | 1170.00 | 866.07 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
June | 1526.54 | 01-JUN-18:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 15.97 | 0.00 |
July | 1515.30 | 03-JUL-15:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 | 0.00 |
August | 1527.54 | 18-AUG-18:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 0.00 |
September | 1627.50 | 10-SEP-18:01 | 1170.00 | 866.07 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 |
October | 1605.39 | 25-OCT-15:12 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 | 0.00 |
November | 1505.58 | 24-NOV-16:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.84 |
December | 1586.91 | 15-DEC-16:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.82 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1505.58 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1627.50 | 1386.00 | 866.07 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 21.21 | 95.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23965.73 | 23-JAN-23:00 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.84 |
February | 23325.28 | 23-FEB-23:02 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.01 |
March | 29638.47 | 27-MAR-18:53 | 209912.64 | 17135.67 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.93 |
April | 31477.60 | 07-APR-23:25 | 269887.68 | 4283.92 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.11 |
May | 33436.31 | 31-MAY-21:11 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.24 |
June | 34256.48 | 23-JUN-21:51 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.32 |
July | 33702.24 | 10-JUL-23:13 | 269887.68 | 4283.92 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.52 |
August | 33847.25 | 30-AUG-21:51 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 |
September | 33273.01 | 01-SEP-23:57 | 269887.68 | 4283.92 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 |
October | 32284.64 | 03-OCT-21:11 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.97 |
November | 28478.67 | 10-NOV-06:47 | 209912.64 | 7980.80 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.19 |
December | 23700.89 | 04-DEC-23:02 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.58 |
Annual Sum or Average | |||||||||||
Minimum of Months | 23325.28 | 209912.64 | 4283.92 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | |
Maximum of Months | 34256.48 | 269887.68 | 17135.67 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26644.89 | 23-JAN-23:00 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.52 |
February | 25920.93 | 23-FEB-23:02 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.49 |
March | 32395.86 | 27-MAR-16:27 | 149937.60 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.26 |
April | 33987.89 | 07-APR-23:25 | 269887.68 | 4283.92 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.95 |
May | 36196.63 | 31-MAY-21:11 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.05 |
June | 36963.04 | 23-JUN-21:51 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.42 |
July | 36080.57 | 10-JUL-23:13 | 269887.68 | 4283.92 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 |
August | 36493.44 | 30-AUG-21:51 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.76 |
September | 35613.89 | 01-SEP-23:57 | 269887.68 | 4283.92 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.05 |
October | 34972.50 | 03-OCT-21:11 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.71 |
November | 30744.85 | 10-NOV-06:47 | 209912.64 | 7980.80 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.39 |
December | 26266.55 | 04-DEC-23:02 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 25920.93 | 149937.60 | 3212.94 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.05 | |
Maximum of Months | 36963.04 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39824.82 | 19-JAN-19:04 | 18679.92 | 9696.29 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 422.46 |
February | 40009.72 | 19-FEB-11:42 | 8005.68 | 3636.11 | 146045.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 390.75 |
March | 46195.98 | 27-MAR-16:51 | 13342.80 | 3030.09 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 142.20 |
April | 48103.20 | 07-APR-10:41 | 5337.12 | 3030.09 | 146045.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 125.08 |
May | 50055.38 | 31-MAY-17:41 | 13342.80 | 7272.22 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 155.01 |
June | 49989.07 | 23-JUN-17:51 | 13342.80 | 7272.22 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 105.10 |
July | 47769.06 | 11-JUL-15:51 | 13342.80 | 3030.09 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 44.56 |
August | 49857.55 | 19-AUG-18:01 | 16011.36 | 8484.25 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 132.99 |
September | 49152.57 | 04-SEP-18:11 | 16011.36 | 8484.25 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 122.95 |
October | 48203.76 | 03-OCT-18:01 | 18679.92 | 9696.29 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 175.97 |
November | 45400.80 | 04-NOV-10:51 | 8005.68 | 3030.09 | 146045.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 217.33 |
December | 40700.38 | 17-DEC-11:42 | 8005.68 | 3636.11 | 146045.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 315.32 |
Annual Sum or Average | |||||||||||
Minimum of Months | 39824.82 | 5337.12 | 3030.09 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 44.56 | |
Maximum of Months | 50055.38 | 18679.92 | 9696.29 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 422.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1383.82 | 17-JAN-14:00 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.01 |
February | 1455.37 | 20-FEB-13:54 | 0.00 | 1972.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.16 |
March | 5818.67 | 27-MAR-13:32 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.93 |
April | 7812.48 | 08-APR-14:53 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.63 |
May | 8119.56 | 30-MAY-13:15 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.14 | 0.00 |
June | 8241.26 | 20-JUN-14:17 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.42 | 0.00 |
July | 8354.53 | 11-JUL-15:03 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.80 | 0.00 |
August | 8553.86 | 20-AUG-14:49 | 0.00 | 1972.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.62 | 0.00 |
September | 8455.88 | 01-SEP-13:39 | 0.00 | 2219.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.73 | 0.00 |
October | 7858.49 | 13-OCT-12:49 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 |
November | 7022.55 | 04-NOV-12:05 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.28 |
December | 1590.48 | 17-DEC-13:44 | 0.00 | 1972.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1383.82 | 0.00 | 1972.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8553.86 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.73 | 227.16 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.366936E+12 | 232628.20 | 18-JAN-20:00 | 0.441627E+12 | 377434.28 | 14-JAN-17:19 |
February | 0.331575E+12 | 232647.22 | 02-FEB-20:19 | 0.401874E+12 | 377686.38 | 06-FEB-17:10 |
March | 0.368536E+12 | 248984.07 | 27-MAR-19:10 | 0.380320E+12 | 305475.91 | 16-MAR-16:30 |
April | 0.368475E+12 | 284391.95 | 07-APR-19:10 | 0.341537E+12 | 286675.12 | 21-APR-17:10 |
May | 0.413322E+12 | 293349.97 | 29-MAY-19:19 | 0.333663E+12 | 279830.79 | 04-MAY-17:30 |
June | 0.519185E+12 | 372842.95 | 19-JUN-19:30 | 0.314536E+12 | 278435.43 | 01-JUN-17:19 |
July | 0.638793E+12 | 393552.25 | 20-JUL-20:30 | 0.320226E+12 | 277618.77 | 03-JUL-17:10 |
August | 0.604405E+12 | 399062.12 | 02-AUG-19:19 | 0.319490E+12 | 287211.24 | 24-AUG-17:40 |
September | 0.484116E+12 | 347687.90 | 13-SEP-19:10 | 0.311496E+12 | 278046.53 | 26-SEP-17:49 |
October | 0.427234E+12 | 291765.42 | 05-OCT-19:10 | 0.329855E+12 | 279566.51 | 30-OCT-17:00 |
November | 0.363809E+12 | 243269.75 | 03-NOV-19:30 | 0.358271E+12 | 308925.08 | 25-NOV-17:10 |
December | 0.370233E+12 | 232766.68 | 04-DEC-20:10 | 0.404727E+12 | 342447.61 | 31-DEC-17:30 |
Annual Sum or Average | 0.525662E+13 | 0.425762E+13 | ||||
Minimum of Months | 0.331575E+12 | 232628.20 | 0.311496E+12 | 277618.77 | ||
Maximum of Months | 0.638793E+12 | 399062.12 | 0.441627E+12 | 377686.38 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.451682E+11 | 0.189005E+11 | 0.140003E+12 | 0.825502E+11 | 0.522428E+11 | 0.363877E+10 | 0.00 | 0.521986E+09 | 0.00 | 0.00 | 0.121183E+11 | 0.768873E+10 | 0.00 |
February | 0.406148E+11 | 0.158504E+11 | 0.126445E+12 | 0.745615E+11 | 0.483015E+11 | 0.359125E+10 | 0.00 | 0.612078E+09 | 0.00 | 0.00 | 0.109449E+11 | 0.694757E+10 | 0.00 |
March | 0.448385E+11 | 0.158714E+11 | 0.140067E+12 | 0.825526E+11 | 0.543065E+11 | 0.369514E+10 | 0.00 | 0.358595E+10 | 0.00 | 0.00 | 0.117811E+11 | 0.768713E+10 | 0.00 |
April | 0.430723E+11 | 0.136798E+11 | 0.135446E+12 | 0.798867E+11 | 0.525710E+11 | 0.376572E+10 | 0.00 | 0.191421E+11 | 0.00 | 0.00 | 0.944523E+10 | 0.744860E+10 | 0.00 |
May | 0.442933E+11 | 0.126469E+11 | 0.140035E+12 | 0.825510E+11 | 0.544064E+11 | 0.441526E+10 | 0.00 | 0.579935E+11 | 0.00 | 0.00 | 0.513866E+10 | 0.768862E+10 | 0.00 |
June | 0.427827E+11 | 0.114534E+11 | 0.135537E+12 | 0.798889E+11 | 0.551385E+11 | 0.504608E+10 | 0.00 | 0.172926E+12 | 0.00 | 0.00 | 0.496546E+10 | 0.744254E+10 | 0.00 |
July | 0.441415E+11 | 0.121862E+11 | 0.139944E+12 | 0.825485E+11 | 0.611262E+11 | 0.609166E+10 | 0.00 | 0.270186E+12 | 0.00 | 0.00 | 0.107580E+11 | 0.769660E+10 | 0.00 |
August | 0.444671E+11 | 0.134565E+11 | 0.140067E+12 | 0.825524E+11 | 0.627794E+11 | 0.571148E+10 | 0.00 | 0.236247E+12 | 0.00 | 0.00 | 0.729369E+10 | 0.768877E+10 | 0.00 |
September | 0.432029E+11 | 0.146221E+11 | 0.135446E+12 | 0.798868E+11 | 0.579824E+11 | 0.478035E+10 | 0.00 | 0.132400E+12 | 0.00 | 0.00 | 0.433710E+10 | 0.745090E+10 | 0.00 |
October | 0.449209E+11 | 0.168555E+11 | 0.140003E+12 | 0.825501E+11 | 0.602844E+11 | 0.449073E+10 | 0.00 | 0.593107E+11 | 0.00 | 0.00 | 0.697471E+10 | 0.768800E+10 | 0.00 |
November | 0.436364E+11 | 0.178466E+11 | 0.135531E+12 | 0.798880E+11 | 0.542048E+11 | 0.363431E+10 | 0.00 | 0.641757E+10 | 0.00 | 0.00 | 0.112071E+11 | 0.743251E+10 | 0.00 |
December | 0.451077E+11 | 0.192704E+11 | 0.139944E+12 | 0.825491E+11 | 0.545253E+11 | 0.360499E+10 | 0.00 | 0.127693E+10 | 0.00 | 0.00 | 0.121176E+11 | 0.769595E+10 | 0.00 |
Annual Sum or Average | 0.526246E+12 | 0.182640E+12 | 0.164847E+13 | 0.971966E+12 | 0.667869E+12 | 0.524658E+11 | 0.00 | 0.960620E+12 | 0.107082E+12 | 0.905559E+11 | |||
Minimum of Months | 0.406148E+11 | 0.114534E+11 | 0.126445E+12 | 0.745615E+11 | 0.483015E+11 | 0.359125E+10 | 0.00 | 0.521986E+09 | 0.00 | 0.00 | 0.433710E+10 | 0.694757E+10 | 0.00 |
Maximum of Months | 0.451682E+11 | 0.192704E+11 | 0.140067E+12 | 0.825526E+11 | 0.627794E+11 | 0.609166E+10 | 0.00 | 0.270186E+12 | 0.00 | 0.00 | 0.121183E+11 | 0.769660E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.976081E+11 | 0.00 | 0.192101E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.898620E+11 | 0.00 | 0.174808E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.366673E+11 | 0.00 | 0.191614E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.145458E+11 | 0.00 | 0.180035E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.232654E+10 | 0.00 | 0.179358E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 99117911.44 | 0.00 | 0.167323E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 30921797.25 | 0.00 | 0.168375E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.162854E+09 | 0.00 | 0.167288E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.412024E+09 | 0.00 | 0.164128E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.325862E+10 | 0.00 | 0.174678E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.358510E+11 | 0.00 | 0.175329E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.649218E+11 | 0.00 | 0.187985E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.345746E+12 | 0.212302E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 30921797.25 | 0.00 | 0.164128E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.976081E+11 | 0.00 | 0.192101E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 47387.53 | 02-JAN-20:10 | 11632.50 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 62573.78 | 02-JAN-07:19 | 25976.66 | 31-JAN-16:19 | 3017.53 | 05-JAN-16:19 | 0.00 | 01-JAN-00:10 |
February | 47387.53 | 01-FEB-20:10 | 11632.50 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 62573.78 | 01-FEB-07:19 | 24871.40 | 08-FEB-19:10 | 3043.86 | 06-FEB-10:39 | 0.00 | 01-FEB-00:10 |
March | 47387.53 | 01-MAR-20:10 | 11632.50 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 62573.78 | 13-MAR-06:19 | 28171.65 | 27-MAR-20:30 | 2786.48 | 17-MAR-15:20 | 0.00 | 01-MAR-00:10 |
April | 47387.53 | 03-APR-19:10 | 11632.50 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 62572.97 | 14-APR-06:19 | 30664.92 | 06-APR-21:10 | 2579.80 | 19-APR-05:19 | 0.00 | 01-APR-00:10 |
May | 47387.53 | 01-MAY-19:10 | 11632.50 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 62572.99 | 04-MAY-06:19 | 30489.56 | 29-MAY-21:49 | 2437.25 | 01-MAY-04:49 | 0.00 | 01-MAY-00:10 |
June | 47387.53 | 01-JUN-19:19 | 11632.50 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 62572.71 | 29-JUN-06:19 | 32554.37 | 06-JUN-21:30 | 3217.80 | 25-JUN-08:20 | 0.00 | 01-JUN-00:10 |
July | 47387.53 | 03-JUL-19:30 | 11632.50 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 62572.83 | 24-JUL-06:19 | 30016.80 | 06-JUL-18:40 | 3617.18 | 20-JUL-20:19 | 0.00 | 01-JUL-00:10 |
August | 47387.53 | 01-AUG-19:10 | 11632.50 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 62572.82 | 16-AUG-06:19 | 30132.26 | 03-AUG-08:20 | 3562.12 | 03-AUG-21:19 | 0.00 | 01-AUG-00:10 |
September | 47387.53 | 01-SEP-19:10 | 11632.50 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 62573.42 | 27-SEP-06:19 | 32831.71 | 19-SEP-21:40 | 2794.99 | 13-SEP-21:19 | 0.00 | 01-SEP-00:10 |
October | 47387.53 | 02-OCT-19:10 | 11632.50 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 62573.78 | 16-OCT-06:19 | 32170.52 | 20-OCT-21:19 | 2433.41 | 28-OCT-06:40 | 0.00 | 01-OCT-00:10 |
November | 47387.53 | 01-NOV-19:10 | 11632.50 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 62573.78 | 01-NOV-06:19 | 28506.69 | 04-NOV-19:30 | 2913.55 | 23-NOV-16:00 | 0.00 | 01-NOV-00:10 |
December | 47387.53 | 01-DEC-20:10 | 11632.50 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 62573.78 | 08-DEC-07:19 | 25200.67 | 21-DEC-16:19 | 2873.84 | 31-DEC-10:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 47387.53 | 11632.50 | 88863.15 | 62572.71 | 24871.40 | 2433.41 | 0.00 | |||||||
Maximum of Months | 47387.53 | 11632.50 | 88863.15 | 62573.78 | 32831.71 | 3617.18 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 4981.09 | 24-JAN-19:10 | 0.00 | 0.00 | 6004.29 | 01-JAN-00:30 | 4735.79 | 02-JAN-07:19 | 0.00 |
February | 5211.27 | 19-FEB-09:09 | 0.00 | 0.00 | 4880.77 | 01-FEB-00:10 | 4735.22 | 16-FEB-07:10 | 0.00 |
March | 44741.18 | 27-MAR-16:10 | 0.00 | 0.00 | 5255.28 | 06-MAR-23:40 | 4734.86 | 23-MAR-06:19 | 0.00 |
April | 71804.11 | 07-APR-16:49 | 0.00 | 0.00 | 4880.77 | 01-APR-00:10 | 4734.59 | 13-APR-06:19 | 0.00 |
May | 103616.95 | 30-MAY-15:50 | 0.00 | 0.00 | 5554.88 | 13-MAY-23:49 | 4735.19 | 30-MAY-06:49 | 0.00 |
June | 151471.37 | 19-JUN-18:10 | 0.00 | 0.00 | 5255.28 | 23-JUN-22:40 | 4736.32 | 29-JUN-06:10 | 0.00 |
July | 169700.85 | 20-JUL-20:30 | 0.00 | 0.00 | 4880.77 | 01-JUL-08:20 | 4735.32 | 19-JUL-06:10 | 0.00 |
August | 165648.52 | 16-AUG-21:19 | 0.00 | 0.00 | 5554.88 | 29-AUG-23:40 | 4736.18 | 24-AUG-06:40 | 0.00 |
September | 138443.38 | 13-SEP-21:19 | 0.00 | 0.00 | 4880.77 | 01-SEP-00:10 | 4735.53 | 15-SEP-06:10 | 0.00 |
October | 87732.33 | 25-OCT-09:50 | 0.00 | 0.00 | 5255.28 | 30-OCT-22:40 | 4735.92 | 05-OCT-06:10 | 0.00 |
November | 38651.96 | 04-NOV-12:20 | 0.00 | 0.00 | 4880.77 | 01-NOV-00:10 | 4735.25 | 22-NOV-07:10 | 0.00 |
December | 10684.02 | 20-DEC-09:00 | 0.00 | 0.00 | 4880.77 | 01-DEC-00:10 | 4735.22 | 07-DEC-07:19 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 4981.09 | 0.00 | 0.00 | 4880.77 | 4734.59 | 0.00 | |||
Maximum of Months | 169700.85 | 0.00 | 0.00 | 6004.29 | 4736.32 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 232628.20 | 18-JAN-20:00 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 22484.46 | 2578.46 | 0.00 | 1270.19 | 0.00 |
February | 232647.22 | 02-FEB-20:19 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 23087.03 | 2651.11 | 0.00 | 730.78 | 0.00 |
March | 248984.07 | 27-MAR-19:10 | 47387.53 | 86131.51 | 11632.50 | 50262.95 | 22821.76 | 1647.96 | 0.00 | 23147.62 | 0.00 |
April | 284391.95 | 07-APR-19:10 | 47387.53 | 86131.51 | 11632.50 | 50262.95 | 24606.29 | 1839.66 | 0.00 | 55725.17 | 0.00 |
May | 293349.97 | 29-MAY-19:19 | 43946.87 | 84670.41 | 11632.50 | 50230.42 | 24669.93 | 1868.79 | 0.00 | 69938.34 | 0.00 |
June | 372842.95 | 19-JUN-19:30 | 47387.53 | 86131.51 | 11632.50 | 50266.79 | 28728.03 | 2400.19 | 0.00 | 135433.09 | 0.00 |
July | 393552.25 | 20-JUL-20:30 | 42099.44 | 87910.25 | 11632.50 | 38044.67 | 29661.61 | 3610.79 | 0.00 | 169700.85 | 0.00 |
August | 399062.12 | 02-AUG-19:19 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 28113.73 | 3414.46 | 0.00 | 161238.00 | 0.00 |
September | 347687.90 | 13-SEP-19:10 | 47387.53 | 86131.51 | 11632.50 | 50262.95 | 24673.06 | 2498.64 | 0.00 | 114450.28 | 0.00 |
October | 291765.42 | 05-OCT-19:10 | 47387.53 | 86131.51 | 11632.50 | 50262.95 | 24516.44 | 1903.12 | 0.00 | 64502.84 | 0.00 |
November | 243269.75 | 03-NOV-19:30 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 24383.11 | 1619.99 | 0.00 | 11483.80 | 0.00 |
December | 232766.68 | 04-DEC-20:10 | 47387.53 | 86131.51 | 11632.50 | 50262.95 | 22759.34 | 2303.59 | 0.00 | 1492.52 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 232628.20 | 42099.44 | 84670.41 | 11632.50 | 38044.67 | 22484.46 | 1619.99 | 0.00 | 730.78 | 0.00 | |
Maximum of Months | 399062.12 | 47387.53 | 87910.25 | 11632.50 | 50267.24 | 29661.61 | 3610.79 | 0.00 | 169700.85 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 142659.14 | 02-JAN-09:09 | 0.00 | 177847.74 | 31-JAN-21:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 143705.23 | 06-FEB-09:09 | 0.00 | 177876.67 | 08-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 61267.87 | 16-MAR-15:20 | 0.00 | 177733.11 | 01-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 33331.21 | 21-APR-15:20 | 0.00 | 176971.90 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 23081.95 | 13-MAY-23:10 | 0.00 | 176001.44 | 01-MAY-20:19 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 7578.65 | 22-JUN-15:20 | 0.00 | 174890.07 | 01-JUN-20:40 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 2940.96 | 12-JUL-12:20 | 0.00 | 173999.11 | 03-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 21490.44 | 30-AUG-13:50 | 0.00 | 173709.38 | 31-AUG-20:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 14509.77 | 01-SEP-13:00 | 0.00 | 174271.75 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 21118.78 | 29-OCT-03:20 | 0.00 | 175284.15 | 31-OCT-20:10 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 60616.21 | 23-NOV-07:19 | 0.00 | 176382.25 | 30-NOV-21:49 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 102318.42 | 31-DEC-23:00 | 0.00 | 177298.61 | 29-DEC-21:00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 2940.96 | 0.00 | 173709.38 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 143705.23 | 0.00 | 177876.67 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 637.33 | 25.07 | 637.33 | 25.07 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 420.17 | 24.84 | 420.17 | 24.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 147.50 | 24.78 | 147.50 | 24.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 82.33 | 24.73 | 82.33 | 24.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 24.65 | 26.17 | 24.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.59 | 6.33 | 24.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 24.62 | 46.50 | 24.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 105.50 | 24.73 | 105.50 | 24.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 335.17 | 24.87 | 335.17 | 24.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 742.33 | 25.57 | 742.33 | 25.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 26.12 | 720.00 | 26.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 25.79 | 744.00 | 25.79 |
Annual Sum or Average | 0.00 | 0.00 | 4013.33 | 25.41 | 4013.33 | 25.41 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 24.59 | 6.33 | 24.59 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 26.12 | 744.00 | 26.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.17 | 20.11 | 12.17 | 20.11 | 12.00 | 25.21 | 12.00 | 25.21 |
February | 5.00 | 20.28 | 5.00 | 20.28 | 22.33 | 25.00 | 22.33 | 25.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 25.28 | 31.83 | 25.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 25.11 | 13.50 | 25.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.73 | 6.83 | 24.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 57.33 | 24.85 | 57.33 | 24.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 200.17 | 24.92 | 200.17 | 24.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 333.33 | 25.20 | 333.33 | 25.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 151.67 | 25.38 | 151.67 | 25.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 204.83 | 25.61 | 204.83 | 25.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 25.41 | 45.83 | 25.41 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 35.17 | 25.50 | 35.17 | 25.50 |
Annual Sum or Average | 17.17 | 20.16 | 17.17 | 20.16 | 1114.83 | 25.24 | 1114.83 | 25.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.73 | 6.83 | 24.73 |
Maximum of Months | 12.17 | 20.28 | 12.17 | 20.28 | 333.33 | 25.61 | 333.33 | 25.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 24.75 | 15.00 | 24.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 24.68 | 18.00 | 24.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 91.00 | 24.85 | 91.00 | 24.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 147.50 | 24.94 | 147.50 | 24.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 205.67 | 24.93 | 205.67 | 24.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 225.17 | 24.99 | 225.17 | 24.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 325.50 | 25.01 | 325.50 | 25.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 400.00 | 25.09 | 400.00 | 25.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 243.67 | 24.97 | 243.67 | 24.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 339.33 | 24.98 | 339.33 | 24.98 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 124.83 | 24.89 | 124.83 | 24.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 | 24.76 | 42.50 | 24.76 |
Annual Sum or Average | 0.00 | 0.00 | 2178.17 | 24.98 | 2178.17 | 24.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 24.68 | 15.00 | 24.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 400.00 | 25.09 | 400.00 | 25.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.60 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 24.66 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 74.50 | 24.74 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 127.50 | 24.84 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 166.00 | 24.86 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 24.72 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 24.65 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.59 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 478.17 | 24.80 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 166.00 | 24.86 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.65 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 52.50 | 24.67 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 126.33 | 24.72 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.58 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 184.50 | 24.70 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 126.33 | 24.72 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 502.17 | 27.35 | 502.17 | 27.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 468.67 | 27.32 | 468.67 | 27.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 571.33 | 27.23 | 571.33 | 27.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 558.50 | 27.04 | 558.50 | 27.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 550.33 | 26.80 | 550.33 | 26.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 534.50 | 26.44 | 534.50 | 26.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 549.50 | 26.31 | 549.50 | 26.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 598.67 | 26.30 | 598.67 | 26.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 540.33 | 26.49 | 540.33 | 26.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 584.33 | 26.91 | 584.33 | 26.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 558.17 | 27.18 | 558.17 | 27.18 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 550.17 | 27.25 | 550.17 | 27.25 |
Annual Sum or Average | 0.00 | 0.00 | 6566.67 | 26.87 | 6566.67 | 26.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 468.67 | 26.30 | 468.67 | 26.30 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 598.67 | 27.35 | 598.67 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 25.18 | 40.17 | 25.18 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 49.00 | 25.25 | 49.00 | 25.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 137.33 | 25.06 | 137.33 | 25.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 165.17 | 24.89 | 165.17 | 24.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 196.00 | 24.87 | 196.00 | 24.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 281.67 | 24.97 | 281.67 | 24.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 426.50 | 25.10 | 426.50 | 25.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 531.00 | 25.23 | 531.00 | 25.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 373.50 | 25.16 | 373.50 | 25.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 533.33 | 25.30 | 533.33 | 25.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 175.50 | 25.14 | 175.50 | 25.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 84.00 | 25.38 | 84.00 | 25.38 |
Annual Sum or Average | 0.00 | 0.00 | 2993.17 | 25.14 | 2993.17 | 25.14 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 24.87 | 40.17 | 24.87 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 533.33 | 25.38 | 533.33 | 25.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 113.33 | 24.86 | 113.33 | 24.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 120.17 | 24.83 | 120.17 | 24.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 285.83 | 24.99 | 285.83 | 24.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 336.83 | 25.08 | 336.83 | 25.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 368.33 | 25.08 | 368.33 | 25.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 359.67 | 25.09 | 359.67 | 25.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 452.00 | 25.16 | 452.00 | 25.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 474.50 | 25.23 | 474.50 | 25.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 364.67 | 25.12 | 364.67 | 25.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 536.17 | 25.18 | 536.17 | 25.18 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 354.33 | 25.05 | 354.33 | 25.05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 220.83 | 24.91 | 220.83 | 24.91 |
Annual Sum or Average | 0.00 | 0.00 | 3986.67 | 25.09 | 3986.67 | 25.09 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 113.33 | 24.83 | 113.33 | 24.83 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 536.17 | 25.23 | 536.17 | 25.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 20.48 | 1.33 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.51 | 0.33 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.71 | 0.67 | 21.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.78 | 2.17 | 21.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.72 | 0.83 | 21.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 20.49 | 1.67 | 20.49 | 3.83 | 21.75 | 3.83 | 21.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.51 | 1.33 | 20.51 | 2.17 | 21.78 | 2.17 | 21.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 20.46 | 2.17 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.67 | 20.48 | 1.67 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.81 | 0.83 | 21.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.85 | 3.50 | 21.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 21.89 | 8.83 | 21.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 21.84 | 6.83 | 21.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.82 | 1.33 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 20.47 | 3.83 | 20.47 | 21.33 | 21.86 | 21.33 | 21.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 20.48 | 2.17 | 20.48 | 8.83 | 21.89 | 8.83 | 21.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 20.27 | 1.83 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.17 | 20.20 | 1.17 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.84 | 1.83 | 21.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 21.97 | 8.67 | 21.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 22.12 | 16.83 | 22.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 21.98 | 12.17 | 21.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.94 | 4.00 | 21.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.47 | 0.17 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.17 | 20.26 | 3.17 | 20.26 | 43.50 | 22.02 | 43.50 | 22.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 20.47 | 1.83 | 20.47 | 16.83 | 22.12 | 16.83 | 22.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 20.46 | 1.67 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.52 | 0.83 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.73 | 0.67 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.83 | 20.49 | 2.83 | 20.49 | 1.67 | 21.71 | 1.67 | 21.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 20.54 | 1.67 | 20.54 | 0.67 | 21.73 | 0.67 | 21.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 20.46 | 3.33 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.67 | 20.50 | 2.67 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.82 | 0.33 | 21.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.42 | 1.67 | 22.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 22.37 | 4.67 | 22.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 22.40 | 10.33 | 22.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 22.47 | 9.00 | 22.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 22.29 | 3.67 | 22.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.53 | 0.67 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6.67 | 20.48 | 6.67 | 20.48 | 30.17 | 22.39 | 30.17 | 22.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 20.53 | 3.33 | 20.53 | 10.33 | 22.47 | 10.33 | 22.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 315.33 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 120.83 | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11.67 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 447.83 | 20.17 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 315.33 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 20.46 | 1.17 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.49 | 0.33 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.74 | 0.50 | 21.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.81 | 0.33 | 21.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.75 | 1.33 | 21.75 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.78 | 1.67 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.81 | 4.00 | 21.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.81 | 1.17 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 20.47 | 1.50 | 20.47 | 9.50 | 21.79 | 9.50 | 21.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 20.49 | 1.17 | 20.49 | 4.00 | 21.81 | 4.00 | 21.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.44 | 2.00 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.50 | 20.45 | 1.50 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.00 | 1.50 | 22.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.97 | 5.17 | 21.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 22.00 | 10.17 | 22.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 21.93 | 8.33 | 21.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.91 | 1.83 | 21.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.67 | 20.45 | 3.67 | 20.45 | 27.00 | 21.97 | 27.00 | 21.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.55 | 2.00 | 20.55 | 10.17 | 22.00 | 10.17 | 22.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.36 | 0.67 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.52 | 0.33 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.96 | 0.17 | 21.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.68 | 0.50 | 21.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.79 | 1.50 | 21.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.80 | 4.00 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.80 | 5.67 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.83 | 3.33 | 21.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.76 | 2.83 | 21.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
December | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 20.44 | 1.33 | 20.44 | 18.33 | 21.80 | 18.33 | 21.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.52 | 0.67 | 20.52 | 5.67 | 21.96 | 5.67 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 466.67 | 25.53 | 466.67 | 25.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 465.50 | 25.46 | 465.50 | 25.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 633.33 | 25.78 | 633.33 | 25.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 663.83 | 25.89 | 663.83 | 25.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 662.67 | 25.87 | 662.67 | 25.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 658.00 | 25.78 | 658.00 | 25.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 738.83 | 25.93 | 738.83 | 25.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 723.33 | 25.91 | 723.33 | 25.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 622.17 | 25.72 | 622.17 | 25.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 656.00 | 25.86 | 656.00 | 25.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 603.17 | 25.79 | 603.17 | 25.79 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 551.83 | 25.59 | 551.83 | 25.59 |
Annual Sum or Average | 0.00 | 0.00 | 7445.33 | 25.78 | 7445.33 | 25.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 465.50 | 25.46 | 465.50 | 25.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 738.83 | 25.93 | 738.83 | 25.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 643.17 | 25.78 | 643.17 | 25.78 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 593.33 | 25.79 | 593.33 | 25.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 741.17 | 26.14 | 741.17 | 26.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 715.33 | 26.27 | 715.33 | 26.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 741.50 | 26.15 | 741.50 | 26.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 715.17 | 26.03 | 715.17 | 26.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 26.26 | 744.00 | 26.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 740.00 | 26.21 | 740.00 | 26.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 699.83 | 25.93 | 699.83 | 25.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 725.33 | 26.15 | 725.33 | 26.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 708.67 | 26.11 | 708.67 | 26.11 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 721.50 | 25.87 | 721.50 | 25.87 |
Annual Sum or Average | 0.00 | 0.00 | 8489.00 | 26.07 | 8489.00 | 26.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 593.33 | 25.78 | 593.33 | 25.78 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 26.27 | 744.00 | 26.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 725.83 | 29.32 | 725.83 | 29.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 658.50 | 29.41 | 658.50 | 29.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.78 | 744.00 | 29.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 29.78 | 720.00 | 29.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.47 | 744.00 | 29.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 716.17 | 29.11 | 716.17 | 29.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 739.83 | 29.22 | 739.83 | 29.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.50 | 29.31 | 743.50 | 29.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 718.00 | 29.11 | 718.00 | 29.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.62 | 744.00 | 29.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 29.68 | 720.00 | 29.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.50 | 744.00 | 29.50 |
Annual Sum or Average | 0.00 | 0.00 | 8717.83 | 29.44 | 8717.83 | 29.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 658.50 | 29.11 | 658.50 | 29.11 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.78 | 744.00 | 29.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.63 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 24.86 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 179.67 | 24.85 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 438.33 | 25.02 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 468.17 | 25.10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 126.83 | 24.86 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 24.73 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.83 | 20.32 | 0.00 | 1285.50 | 24.99 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.83 | 20.32 | 0.00 | 0.00 | 468.17 | 25.10 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.67 | 24.06 | 427.00 | 25.19 | 0.00 | 0.00 |
February | 124.17 | 24.25 | 120.33 | 25.05 | 0.00 | 0.00 |
March | 192.17 | 24.06 | 117.33 | 24.64 | 0.00 | 0.00 |
April | 164.50 | 24.05 | 110.00 | 24.46 | 0.00 | 0.00 |
May | 197.50 | 23.94 | 182.17 | 24.16 | 0.00 | 0.00 |
June | 33.00 | 23.99 | 376.33 | 24.13 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 498.00 | 24.17 | 0.00 | 0.00 |
August | 1.67 | 24.02 | 573.33 | 24.30 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 626.83 | 24.59 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 735.83 | 25.57 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 720.00 | 26.12 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 740.00 | 25.79 | 0.00 | 0.00 |
Annual Sum or Average | 771.67 | 24.05 | 5227.17 | 25.05 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 110.00 | 24.13 | 0.00 | 0.00 |
Maximum of Months | 197.50 | 24.25 | 740.00 | 26.12 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 700.67 | 21.41 | 191.33 | 21.17 | 179.33 | 20.90 |
February | 612.17 | 21.59 | 144.00 | 21.55 | 122.17 | 20.94 |
March | 627.50 | 22.17 | 44.67 | 24.95 | 1.67 | 26.51 |
April | 490.83 | 22.60 | 97.83 | 24.22 | 0.00 | 0.00 |
May | 231.67 | 23.34 | 256.67 | 24.04 | 8.00 | 23.66 |
June | 20.17 | 23.82 | 646.67 | 24.14 | 11.00 | 23.88 |
July | 5.33 | 24.02 | 744.00 | 24.35 | 5.33 | 24.02 |
August | 26.00 | 25.90 | 740.67 | 24.61 | 26.00 | 25.90 |
September | 69.83 | 24.72 | 558.33 | 24.44 | 30.50 | 26.26 |
October | 224.67 | 24.21 | 449.33 | 24.78 | 64.50 | 26.31 |
November | 545.83 | 22.27 | 81.00 | 24.69 | 9.83 | 24.17 |
December | 671.33 | 21.75 | 66.67 | 23.41 | 33.83 | 21.54 |
Annual Sum or Average | 4226.00 | 22.20 | 4021.17 | 24.15 | 492.17 | 22.49 |
Minimum of Months | 5.33 | 21.41 | 44.67 | 21.17 | 0.00 | 0.00 |
Maximum of Months | 700.67 | 25.90 | 744.00 | 24.95 | 179.33 | 26.51 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 617.17 | 23.32 | 16.33 | 24.43 | 0.17 | 21.13 |
February | 579.33 | 23.56 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.00 | 23.76 | 102.50 | 24.69 | 0.00 | 0.00 |
April | 161.67 | 23.81 | 273.83 | 24.60 | 0.00 | 0.00 |
May | 17.33 | 23.95 | 489.50 | 24.49 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 666.33 | 24.45 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 744.00 | 24.57 | 0.00 | 0.00 |
August | 3.50 | 25.82 | 727.50 | 24.72 | 3.50 | 25.82 |
September | 3.33 | 23.99 | 622.33 | 24.49 | 0.00 | 0.00 |
October | 2.00 | 24.34 | 532.67 | 24.68 | 0.67 | 24.99 |
November | 264.83 | 23.80 | 175.50 | 24.68 | 0.00 | 0.00 |
December | 546.00 | 23.72 | 15.67 | 24.80 | 0.00 | 0.00 |
Annual Sum or Average | 2533.17 | 23.61 | 4366.17 | 24.58 | 4.33 | 25.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 617.17 | 25.82 | 744.00 | 24.80 | 3.50 | 25.82 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 439.00 | 27.72 | 744.00 | 26.40 | 439.00 | 27.72 |
February | 378.83 | 27.92 | 672.00 | 26.45 | 378.83 | 27.92 |
March | 513.67 | 27.49 | 744.00 | 26.58 | 513.67 | 27.49 |
April | 588.17 | 26.91 | 720.00 | 26.46 | 588.17 | 26.91 |
May | 665.17 | 26.40 | 744.00 | 26.19 | 665.17 | 26.40 |
June | 697.33 | 25.99 | 720.00 | 25.94 | 697.33 | 25.99 |
July | 725.00 | 25.86 | 744.00 | 25.83 | 725.00 | 25.86 |
August | 734.83 | 25.96 | 744.00 | 25.94 | 734.83 | 25.96 |
September | 681.17 | 26.07 | 720.00 | 25.98 | 681.17 | 26.07 |
October | 649.33 | 26.66 | 744.00 | 26.38 | 649.33 | 26.66 |
November | 525.83 | 27.32 | 720.00 | 26.56 | 525.83 | 27.32 |
December | 465.83 | 27.70 | 744.00 | 26.52 | 465.83 | 27.70 |
Annual Sum or Average | 7064.17 | 26.69 | 8760.00 | 26.27 | 7064.17 | 26.69 |
Minimum of Months | 378.83 | 25.86 | 672.00 | 25.83 | 378.83 | 25.86 |
Maximum of Months | 734.83 | 27.92 | 744.00 | 26.58 | 734.83 | 27.92 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 584.17 | 22.68 | 84.67 | 24.12 | 20.17 | 22.03 |
February | 474.33 | 22.87 | 64.67 | 25.04 | 0.17 | 26.13 |
March | 328.83 | 23.05 | 232.67 | 24.74 | 5.33 | 26.40 |
April | 212.00 | 23.14 | 354.33 | 24.48 | 17.83 | 24.67 |
May | 177.17 | 23.99 | 562.17 | 24.36 | 123.83 | 24.53 |
June | 272.17 | 24.80 | 685.50 | 24.43 | 272.17 | 24.80 |
July | 353.83 | 25.09 | 744.00 | 24.71 | 353.83 | 25.09 |
August | 306.17 | 25.30 | 743.50 | 24.93 | 306.17 | 25.30 |
September | 244.50 | 24.85 | 662.33 | 24.70 | 223.83 | 25.02 |
October | 253.00 | 25.29 | 666.50 | 25.07 | 237.00 | 25.44 |
November | 298.17 | 23.34 | 288.83 | 24.79 | 24.83 | 25.52 |
December | 486.67 | 23.09 | 121.17 | 25.07 | 13.83 | 26.82 |
Annual Sum or Average | 3991.00 | 23.77 | 5210.33 | 24.70 | 1599.00 | 25.06 |
Minimum of Months | 177.17 | 22.68 | 64.67 | 24.12 | 0.17 | 22.03 |
Maximum of Months | 584.17 | 25.30 | 744.00 | 25.07 | 353.83 | 26.82 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 365.67 | 23.52 | 134.50 | 24.73 | 1.17 | 24.62 |
February | 302.17 | 23.70 | 105.00 | 24.81 | 0.00 | 0.00 |
March | 102.17 | 23.76 | 345.67 | 24.85 | 0.00 | 0.00 |
April | 36.50 | 24.13 | 463.00 | 24.82 | 9.17 | 25.08 |
May | 98.67 | 24.96 | 610.83 | 24.70 | 97.67 | 24.97 |
June | 226.83 | 25.05 | 696.83 | 24.63 | 226.83 | 25.05 |
July | 294.50 | 25.26 | 744.00 | 24.78 | 294.50 | 25.26 |
August | 238.00 | 25.39 | 743.33 | 24.87 | 238.00 | 25.39 |
September | 148.50 | 25.09 | 689.00 | 24.68 | 148.50 | 25.09 |
October | 141.33 | 25.30 | 699.83 | 24.97 | 141.33 | 25.30 |
November | 82.00 | 24.01 | 433.50 | 24.90 | 11.33 | 25.16 |
December | 174.67 | 23.66 | 220.50 | 24.86 | 0.00 | 0.00 |
Annual Sum or Average | 2211.00 | 24.47 | 5886.00 | 24.80 | 1168.50 | 25.20 |
Minimum of Months | 36.50 | 23.52 | 105.00 | 24.63 | 0.00 | 0.00 |
Maximum of Months | 365.67 | 25.39 | 744.00 | 24.97 | 294.50 | 25.39 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.67 | 561.00 | 20.52 | 561.00 | 20.52 |
February | 672.00 | 20.79 | 500.17 | 20.62 | 500.17 | 20.62 |
March | 743.17 | 21.09 | 201.83 | 20.61 | 201.33 | 20.60 |
April | 709.83 | 21.29 | 41.67 | 20.35 | 41.67 | 20.35 |
May | 728.67 | 21.56 | 12.00 | 21.88 | 11.33 | 21.82 |
June | 631.50 | 21.57 | 25.33 | 22.52 | 18.67 | 22.36 |
July | 603.67 | 21.48 | 43.33 | 22.80 | 27.00 | 22.67 |
August | 604.50 | 21.48 | 26.17 | 22.86 | 12.33 | 22.68 |
September | 659.00 | 21.58 | 21.67 | 22.37 | 18.50 | 22.25 |
October | 704.00 | 21.53 | 8.50 | 21.66 | 8.50 | 21.66 |
November | 720.00 | 21.04 | 226.50 | 20.62 | 226.50 | 20.62 |
December | 744.00 | 20.80 | 500.33 | 20.61 | 500.33 | 20.61 |
Annual Sum or Average | 8264.33 | 21.23 | 2168.50 | 20.71 | 2127.33 | 20.66 |
Minimum of Months | 603.67 | 20.67 | 8.50 | 20.35 | 8.50 | 20.35 |
Maximum of Months | 744.00 | 21.58 | 561.00 | 22.86 | 561.00 | 22.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.50 | 637.83 | 20.41 | 637.83 | 20.41 |
February | 672.00 | 20.55 | 611.00 | 20.49 | 611.00 | 20.49 |
March | 741.67 | 20.87 | 303.17 | 20.47 | 301.50 | 20.45 |
April | 695.67 | 21.22 | 76.17 | 20.92 | 66.83 | 20.37 |
May | 678.33 | 21.69 | 61.33 | 24.30 | 21.00 | 22.47 |
June | 580.67 | 22.28 | 168.67 | 24.58 | 120.00 | 24.25 |
July | 582.83 | 22.43 | 209.67 | 24.54 | 173.50 | 24.47 |
August | 556.50 | 22.12 | 161.67 | 24.75 | 85.17 | 24.58 |
September | 625.50 | 22.00 | 112.50 | 24.33 | 68.50 | 23.79 |
October | 702.17 | 21.52 | 72.67 | 22.33 | 57.17 | 21.77 |
November | 720.00 | 20.80 | 309.50 | 20.43 | 309.50 | 20.43 |
December | 744.00 | 20.55 | 671.00 | 20.50 | 671.00 | 20.50 |
Annual Sum or Average | 8043.33 | 21.32 | 3395.17 | 21.37 | 3123.00 | 21.05 |
Minimum of Months | 556.50 | 20.50 | 61.33 | 20.41 | 21.00 | 20.37 |
Maximum of Months | 744.00 | 22.43 | 671.00 | 24.75 | 671.00 | 24.58 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.85 | 301.67 | 20.55 | 301.67 | 20.55 |
February | 672.00 | 20.84 | 335.67 | 20.59 | 335.67 | 20.59 |
March | 744.00 | 21.10 | 51.83 | 20.51 | 51.83 | 20.51 |
April | 720.00 | 21.38 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 734.50 | 21.76 | 13.00 | 23.39 | 6.67 | 22.71 |
June | 707.50 | 22.25 | 127.83 | 23.50 | 120.83 | 23.45 |
July | 729.17 | 22.45 | 188.17 | 23.88 | 180.83 | 23.86 |
August | 701.00 | 22.22 | 90.50 | 23.77 | 79.00 | 23.71 |
September | 706.33 | 22.04 | 58.67 | 23.56 | 56.50 | 23.53 |
October | 744.00 | 21.51 | 20.33 | 22.25 | 20.33 | 22.25 |
November | 720.00 | 21.12 | 60.00 | 20.50 | 60.00 | 20.50 |
December | 744.00 | 20.92 | 177.00 | 20.40 | 177.00 | 20.40 |
Annual Sum or Average | 8666.50 | 21.53 | 1424.67 | 21.62 | 1390.33 | 21.56 |
Minimum of Months | 672.00 | 20.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.45 | 335.67 | 23.88 | 335.67 | 23.86 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.68 | 553.50 | 20.53 | 553.50 | 20.53 |
February | 672.00 | 20.81 | 480.17 | 20.65 | 480.17 | 20.65 |
March | 744.00 | 21.14 | 197.17 | 20.66 | 197.17 | 20.66 |
April | 718.17 | 21.39 | 42.50 | 20.38 | 42.50 | 20.38 |
May | 730.67 | 21.63 | 8.33 | 21.63 | 8.33 | 21.63 |
June | 663.17 | 21.67 | 27.83 | 22.49 | 26.00 | 22.48 |
July | 580.00 | 21.41 | 31.67 | 22.73 | 23.00 | 22.64 |
August | 587.17 | 21.44 | 16.33 | 22.88 | 6.83 | 22.71 |
September | 669.17 | 21.63 | 21.50 | 22.34 | 19.17 | 22.28 |
October | 722.17 | 21.61 | 7.50 | 21.99 | 7.17 | 22.01 |
November | 720.00 | 21.09 | 206.50 | 20.63 | 206.50 | 20.63 |
December | 744.00 | 20.81 | 493.50 | 20.62 | 493.50 | 20.62 |
Annual Sum or Average | 8294.50 | 21.26 | 2086.50 | 20.70 | 2063.83 | 20.68 |
Minimum of Months | 580.00 | 20.68 | 7.50 | 20.38 | 6.83 | 20.38 |
Maximum of Months | 744.00 | 21.67 | 553.50 | 22.88 | 553.50 | 22.71 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.51 | 636.83 | 20.42 | 636.83 | 20.42 |
February | 672.00 | 20.56 | 601.67 | 20.50 | 601.67 | 20.50 |
March | 744.00 | 20.91 | 297.00 | 20.58 | 297.00 | 20.58 |
April | 717.00 | 21.35 | 64.00 | 20.48 | 63.33 | 20.45 |
May | 701.00 | 21.80 | 42.17 | 23.68 | 21.17 | 22.73 |
June | 619.17 | 22.26 | 152.67 | 23.87 | 125.50 | 23.68 |
July | 550.67 | 22.34 | 207.83 | 24.35 | 174.67 | 24.33 |
August | 534.83 | 22.07 | 150.17 | 24.54 | 78.67 | 24.52 |
September | 650.17 | 22.06 | 90.00 | 23.85 | 67.50 | 23.60 |
October | 742.33 | 21.61 | 52.83 | 21.84 | 52.00 | 21.82 |
November | 720.00 | 20.85 | 276.67 | 20.43 | 276.67 | 20.43 |
December | 744.00 | 20.56 | 642.17 | 20.48 | 642.17 | 20.48 |
Annual Sum or Average | 8139.17 | 21.35 | 3214.00 | 21.24 | 3037.17 | 21.04 |
Minimum of Months | 534.83 | 20.51 | 42.17 | 20.42 | 21.17 | 20.42 |
Maximum of Months | 744.00 | 22.34 | 642.17 | 24.54 | 642.17 | 24.52 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.60 | 634.33 | 20.50 | 634.33 | 20.50 |
February | 672.00 | 20.71 | 578.50 | 20.61 | 578.50 | 20.61 |
March | 742.50 | 21.03 | 297.67 | 20.57 | 297.00 | 20.57 |
April | 699.50 | 21.24 | 106.50 | 20.56 | 104.50 | 20.48 |
May | 704.83 | 21.54 | 15.83 | 22.04 | 12.17 | 21.74 |
June | 597.17 | 21.48 | 44.00 | 22.66 | 22.33 | 22.32 |
July | 578.33 | 21.40 | 65.83 | 22.90 | 30.50 | 22.68 |
August | 576.83 | 21.40 | 52.67 | 23.00 | 13.83 | 22.67 |
September | 633.50 | 21.51 | 29.00 | 22.42 | 21.00 | 22.19 |
October | 688.50 | 21.47 | 44.00 | 21.17 | 41.67 | 21.07 |
November | 720.00 | 20.96 | 317.00 | 20.56 | 317.00 | 20.56 |
December | 744.00 | 20.71 | 608.67 | 20.59 | 608.67 | 20.59 |
Annual Sum or Average | 8101.17 | 21.15 | 2794.00 | 20.74 | 2681.50 | 20.64 |
Minimum of Months | 576.83 | 20.60 | 15.83 | 20.50 | 12.17 | 20.48 |
Maximum of Months | 744.00 | 21.54 | 634.33 | 23.00 | 634.33 | 22.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.46 | 698.83 | 20.42 | 698.83 | 20.42 |
February | 672.00 | 20.50 | 648.50 | 20.47 | 648.50 | 20.47 |
March | 741.33 | 20.81 | 391.33 | 20.48 | 389.17 | 20.45 |
April | 685.50 | 21.18 | 154.50 | 21.03 | 136.83 | 20.51 |
May | 653.33 | 21.74 | 80.17 | 24.91 | 29.83 | 24.20 |
June | 549.50 | 22.44 | 194.00 | 24.98 | 133.67 | 25.03 |
July | 561.33 | 22.55 | 232.33 | 24.77 | 181.50 | 24.92 |
August | 533.00 | 22.21 | 183.83 | 24.97 | 96.17 | 25.26 |
September | 591.50 | 22.03 | 128.17 | 24.75 | 73.83 | 24.37 |
October | 687.83 | 21.49 | 131.17 | 21.99 | 106.83 | 21.39 |
November | 720.00 | 20.72 | 411.67 | 20.44 | 411.67 | 20.44 |
December | 744.00 | 20.48 | 711.83 | 20.45 | 711.83 | 20.45 |
Annual Sum or Average | 7883.33 | 21.30 | 3966.33 | 21.44 | 3618.67 | 21.11 |
Minimum of Months | 533.00 | 20.46 | 80.17 | 20.42 | 29.83 | 20.42 |
Maximum of Months | 744.00 | 22.55 | 711.83 | 24.98 | 711.83 | 25.26 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.17 | 21.05 | 308.33 | 20.61 | 308.33 | 20.61 |
February | 668.50 | 21.23 | 244.67 | 20.70 | 244.67 | 20.70 |
March | 729.33 | 21.30 | 86.33 | 20.64 | 86.33 | 20.64 |
April | 706.17 | 21.41 | 18.50 | 20.39 | 18.50 | 20.39 |
May | 733.67 | 21.62 | 37.33 | 21.87 | 37.33 | 21.87 |
June | 652.17 | 21.61 | 53.50 | 22.37 | 53.50 | 22.37 |
July | 619.83 | 21.53 | 66.17 | 22.46 | 66.17 | 22.46 |
August | 609.50 | 21.49 | 29.33 | 22.54 | 29.33 | 22.54 |
September | 623.83 | 21.51 | 31.67 | 22.64 | 26.83 | 22.52 |
October | 638.17 | 21.44 | 38.17 | 22.84 | 14.17 | 22.03 |
November | 702.50 | 21.37 | 52.00 | 20.82 | 52.00 | 20.82 |
December | 729.00 | 21.15 | 210.00 | 20.56 | 210.00 | 20.56 |
Annual Sum or Average | 8151.83 | 21.38 | 1176.00 | 21.03 | 1147.17 | 20.97 |
Minimum of Months | 609.50 | 21.05 | 18.50 | 20.39 | 14.17 | 20.39 |
Maximum of Months | 739.17 | 21.62 | 308.33 | 22.84 | 308.33 | 22.54 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 121.00 | 24.00 | 461.17 | 25.50 | 9.83 | 26.29 |
February | 107.50 | 23.86 | 408.67 | 25.55 | 0.00 | 0.00 |
March | 48.67 | 26.82 | 659.50 | 25.72 | 48.67 | 26.82 |
April | 165.67 | 26.61 | 714.50 | 25.78 | 165.67 | 26.61 |
May | 275.67 | 26.39 | 744.00 | 25.71 | 275.67 | 26.39 |
June | 355.50 | 26.21 | 720.00 | 25.66 | 355.50 | 26.21 |
July | 483.67 | 26.29 | 744.00 | 25.92 | 483.67 | 26.29 |
August | 449.00 | 26.31 | 744.00 | 25.87 | 449.00 | 26.31 |
September | 287.00 | 26.12 | 720.00 | 25.53 | 287.00 | 26.12 |
October | 229.50 | 26.29 | 744.00 | 25.68 | 229.50 | 26.29 |
November | 88.00 | 26.36 | 631.00 | 25.72 | 77.00 | 26.69 |
December | 29.17 | 24.29 | 518.33 | 25.63 | 3.00 | 26.70 |
Annual Sum or Average | 2640.33 | 26.08 | 7809.17 | 25.70 | 2384.50 | 26.32 |
Minimum of Months | 29.17 | 23.86 | 408.67 | 25.50 | 0.00 | 0.00 |
Maximum of Months | 483.67 | 26.82 | 744.00 | 25.92 | 483.67 | 26.82 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 90.33 | 26.15 | 642.33 | 25.77 | 66.33 | 26.97 |
February | 52.50 | 26.61 | 573.33 | 25.83 | 44.67 | 27.06 |
March | 232.00 | 26.93 | 744.00 | 26.13 | 232.00 | 26.93 |
April | 355.83 | 26.85 | 720.00 | 26.26 | 355.83 | 26.85 |
May | 447.67 | 26.63 | 744.00 | 26.14 | 447.67 | 26.63 |
June | 501.17 | 26.37 | 720.00 | 26.02 | 501.17 | 26.37 |
July | 647.33 | 26.40 | 744.00 | 26.26 | 647.33 | 26.40 |
August | 603.33 | 26.42 | 744.00 | 26.20 | 603.33 | 26.42 |
September | 401.17 | 26.39 | 720.00 | 25.89 | 401.17 | 26.39 |
October | 370.50 | 26.65 | 744.00 | 26.10 | 370.50 | 26.65 |
November | 231.83 | 26.92 | 707.50 | 26.11 | 231.83 | 26.92 |
December | 87.17 | 27.00 | 717.17 | 25.88 | 87.17 | 27.00 |
Annual Sum or Average | 4020.83 | 26.56 | 8520.33 | 26.06 | 3989.00 | 26.58 |
Minimum of Months | 52.50 | 26.15 | 573.33 | 25.77 | 44.67 | 26.37 |
Maximum of Months | 647.33 | 27.00 | 744.00 | 26.26 | 647.33 | 27.06 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 679.83 | 29.61 | 744.00 | 29.20 | 679.83 | 29.61 |
February | 613.50 | 29.73 | 672.00 | 29.31 | 613.50 | 29.73 |
March | 736.00 | 29.83 | 744.00 | 29.78 | 736.00 | 29.83 |
April | 720.00 | 29.78 | 720.00 | 29.78 | 720.00 | 29.78 |
May | 744.00 | 29.47 | 744.00 | 29.47 | 744.00 | 29.47 |
June | 720.00 | 29.08 | 720.00 | 29.08 | 720.00 | 29.08 |
July | 744.00 | 29.19 | 744.00 | 29.19 | 744.00 | 29.19 |
August | 744.00 | 29.30 | 744.00 | 29.30 | 744.00 | 29.30 |
September | 720.00 | 29.10 | 720.00 | 29.10 | 720.00 | 29.10 |
October | 744.00 | 29.62 | 744.00 | 29.62 | 744.00 | 29.62 |
November | 711.33 | 29.73 | 720.00 | 29.68 | 711.33 | 29.73 |
December | 729.50 | 29.58 | 744.00 | 29.50 | 729.50 | 29.58 |
Annual Sum or Average | 8606.17 | 29.50 | 8760.00 | 29.42 | 8606.17 | 29.50 |
Minimum of Months | 613.50 | 29.08 | 672.00 | 29.08 | 613.50 | 29.08 |
Maximum of Months | 744.00 | 29.83 | 744.00 | 29.78 | 744.00 | 29.83 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.94462 | 30.07103 | 0.47963 | 10.18810 |
February | 672.00000 | 24.64876 | 26.81254 | 0.38061 | 8.21940 |
March | 744.00000 | 24.35156 | 34.15829 | 0.35664 | 7.82883 |
April | 720.00000 | 24.22310 | 39.32198 | 0.35976 | 7.84500 |
May | 744.00000 | 24.07030 | 45.70458 | -0.5523 | 11.56758 |
June | 720.00000 | 24.07681 | 52.34404 | -0.4895 | 10.10802 |
July | 744.00000 | 24.11937 | 54.45890 | -0.4474 | 9.25327 |
August | 744.00000 | 24.24223 | 52.15112 | -0.4067 | 8.60162 |
September | 720.00000 | 24.55070 | 48.26015 | -0.3194 | 7.40011 |
October | 744.00000 | 25.56756 | 40.46747 | 0.73380 | 16.59839 |
November | 720.00000 | 26.12021 | 32.89363 | 0.80722 | 18.91028 |
December | 744.00000 | 25.78545 | 28.31530 | 0.68308 | 14.97811 |
Annual Sum or Average | 8760.00000 | 24.72549 | 40.49444 | 0.13055 | 10.97956 |
Minimum of Months | 672.00000 | 24.07030 | 26.81254 | -0.5523 | 7.40011 |
Maximum of Months | 744.00000 | 26.12021 | 54.45890 | 0.80722 | 18.91028 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.58943 | 34.04112 | -0.3350 | 9.04963 |
February | 672.00000 | 21.84631 | 29.24932 | -0.2806 | 8.61129 |
March | 744.00000 | 22.50912 | 37.01015 | -0.0482 | 7.01210 |
April | 720.00000 | 23.06880 | 41.61952 | 0.13012 | 7.04235 |
May | 744.00000 | 23.79653 | 46.52074 | -0.5491 | 11.99908 |
June | 720.00000 | 24.12592 | 53.42745 | -0.3252 | 7.57889 |
July | 744.00000 | 24.34514 | 56.42876 | -0.1942 | 6.30667 |
August | 744.00000 | 24.61178 | 52.44689 | -0.1154 | 6.43584 |
September | 720.00000 | 24.29981 | 50.02227 | -0.2866 | 8.36964 |
October | 744.00000 | 24.33897 | 42.91999 | 0.51664 | 12.50394 |
November | 720.00000 | 22.76605 | 38.39996 | 0.02804 | 7.42155 |
December | 744.00000 | 22.03390 | 33.00003 | -0.2091 | 8.17087 |
Annual Sum or Average | 8760.00000 | 23.28626 | 43.00399 | -0.1382 | 8.38167 |
Minimum of Months | 672.00000 | 21.58943 | 29.24932 | -0.5491 | 6.30667 |
Maximum of Months | 744.00000 | 24.61178 | 56.42876 | 0.51664 | 12.50394 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.46804 | 34.58101 | 0.13872 | 6.13085 |
February | 672.00000 | 23.66474 | 30.40385 | 0.16373 | 5.96251 |
March | 744.00000 | 24.05082 | 36.34330 | 0.31399 | 7.37319 |
April | 720.00000 | 24.22931 | 40.44569 | 0.40172 | 8.75346 |
May | 744.00000 | 24.34494 | 45.58560 | -0.3814 | 8.52195 |
June | 720.00000 | 24.42368 | 52.35908 | -0.2796 | 7.10711 |
July | 744.00000 | 24.57384 | 54.99740 | -0.2001 | 6.33442 |
August | 744.00000 | 24.70701 | 52.57159 | -0.1648 | 6.20064 |
September | 720.00000 | 24.43596 | 50.02446 | -0.2948 | 7.33514 |
October | 744.00000 | 24.58526 | 43.47269 | 0.54033 | 11.52583 |
November | 720.00000 | 24.15619 | 37.59594 | 0.35433 | 8.00008 |
December | 744.00000 | 23.86955 | 32.99374 | 0.23597 | 6.43332 |
Annual Sum or Average | 8760.00000 | 24.21247 | 42.68759 | 0.06848 | 7.48206 |
Minimum of Months | 672.00000 | 23.46804 | 30.40385 | -0.3814 | 5.96251 |
Maximum of Months | 744.00000 | 24.70701 | 54.99740 | 0.54033 | 11.52583 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 26.40358 | 23.42864 | 1.34101 | 41.26032 |
February | 672.00000 | 26.44648 | 20.05718 | 1.32864 | 40.77913 |
March | 744.00000 | 26.57869 | 26.11151 | 1.43682 | 44.89061 |
April | 720.00000 | 26.45689 | 30.56868 | 1.46775 | 46.14003 |
May | 744.00000 | 26.19142 | 35.97375 | 1.06119 | 31.20230 |
June | 720.00000 | 25.93767 | 42.60472 | 1.04989 | 30.28690 |
July | 744.00000 | 25.82511 | 45.40181 | 1.02418 | 29.57785 |
August | 744.00000 | 25.94293 | 43.50704 | 1.07627 | 30.97019 |
September | 720.00000 | 25.98489 | 40.55292 | 1.04630 | 30.43997 |
October | 744.00000 | 26.37982 | 34.43190 | 1.51307 | 48.07742 |
November | 720.00000 | 26.56070 | 27.56333 | 1.44785 | 45.39885 |
December | 744.00000 | 26.51704 | 22.71088 | 1.37630 | 42.65275 |
Annual Sum or Average | 8760.00000 | 26.26768 | 32.81869 | 1.26370 | 38.45853 |
Minimum of Months | 672.00000 | 25.82511 | 20.05718 | 1.02418 | 29.57785 |
Maximum of Months | 744.00000 | 26.57869 | 45.40181 | 1.51307 | 48.07742 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.03503 | 39.36150 | 0.07855 | 7.04027 |
February | 672.00000 | 23.32346 | 34.89087 | 0.14109 | 7.13979 |
March | 744.00000 | 23.80946 | 41.47083 | 0.32636 | 8.56665 |
April | 720.00000 | 23.96217 | 45.88685 | 0.41274 | 9.56482 |
May | 744.00000 | 24.12143 | 51.32433 | -0.3410 | 8.29450 |
June | 720.00000 | 24.37637 | 58.23366 | -0.1460 | 6.21011 |
July | 744.00000 | 24.70833 | 60.85407 | 0.01464 | 5.63135 |
August | 744.00000 | 24.92415 | 57.87112 | 0.08729 | 6.03591 |
September | 720.00000 | 24.58642 | 55.14651 | -0.0856 | 6.73205 |
October | 744.00000 | 24.93669 | 48.00496 | 0.74472 | 17.89011 |
November | 720.00000 | 23.99254 | 42.61799 | 0.38780 | 9.58617 |
December | 744.00000 | 23.54395 | 37.81245 | 0.21486 | 7.86843 |
Annual Sum or Average | 8760.00000 | 24.11516 | 47.86622 | 0.15317 | 8.39412 |
Minimum of Months | 672.00000 | 23.03503 | 34.89087 | -0.3410 | 5.63135 |
Maximum of Months | 744.00000 | 24.93669 | 60.85407 | 0.74472 | 17.89011 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.95771 | 37.32420 | 0.29261 | 7.50735 |
February | 672.00000 | 24.08936 | 33.12694 | 0.30541 | 7.36335 |
March | 744.00000 | 24.42690 | 39.35136 | 0.44578 | 9.60250 |
April | 720.00000 | 24.55275 | 43.77506 | 0.52110 | 11.20607 |
May | 744.00000 | 24.58524 | 49.23055 | -0.2511 | 7.03195 |
June | 720.00000 | 24.61320 | 56.18539 | -0.1598 | 6.21769 |
July | 744.00000 | 24.77562 | 58.88061 | -0.0719 | 5.79814 |
August | 744.00000 | 24.87222 | 56.49191 | -0.0478 | 5.82172 |
September | 720.00000 | 24.65710 | 53.67937 | -0.1623 | 6.23998 |
October | 744.00000 | 24.92901 | 47.00538 | 0.67124 | 14.93650 |
November | 720.00000 | 24.57310 | 40.52921 | 0.49796 | 10.74489 |
December | 744.00000 | 24.28280 | 35.58431 | 0.37644 | 8.37457 |
Annual Sum or Average | 8760.00000 | 24.52904 | 46.00697 | 0.20090 | 8.41010 |
Minimum of Months | 672.00000 | 23.95771 | 33.12694 | -0.2511 | 5.79814 |
Maximum of Months | 744.00000 | 24.92901 | 58.88061 | 0.67124 | 14.93650 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67353 | 39.80266 | -0.6264 | 13.83621 |
February | 672.00000 | 20.78503 | 34.83285 | -0.6122 | 13.49498 |
March | 744.00000 | 21.09668 | 43.93068 | -0.4287 | 9.54593 |
April | 720.00000 | 21.31975 | 49.14976 | -0.3041 | 7.83338 |
May | 744.00000 | 21.59357 | 54.35736 | -1.2887 | 40.67365 |
June | 720.00000 | 21.77072 | 58.17689 | -1.1159 | 32.83476 |
July | 744.00000 | 21.80645 | 59.64757 | -1.0578 | 30.35969 |
August | 744.00000 | 21.80373 | 55.99821 | -1.0656 | 30.74269 |
September | 720.00000 | 21.71751 | 56.77189 | -1.1770 | 35.63708 |
October | 744.00000 | 21.61848 | 51.70006 | -0.1632 | 6.68565 |
November | 720.00000 | 21.04446 | 46.66044 | -0.4426 | 9.77435 |
December | 744.00000 | 20.79951 | 39.75733 | -0.5770 | 12.51625 |
Annual Sum or Average | 8760.00000 | 21.33892 | 49.31260 | -0.7391 | 20.37098 |
Minimum of Months | 672.00000 | 20.67353 | 34.83285 | -1.2887 | 6.68565 |
Maximum of Months | 744.00000 | 21.80645 | 59.64757 | -0.1632 | 40.67365 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.50449 | 40.15312 | -0.6851 | 15.49296 |
February | 672.00000 | 20.54735 | 35.27473 | -0.6945 | 15.71760 |
March | 744.00000 | 20.88542 | 44.40495 | -0.4970 | 10.78974 |
April | 720.00000 | 21.32346 | 49.32761 | -0.3164 | 8.24596 |
May | 744.00000 | 21.94754 | 53.75315 | -1.1953 | 37.61873 |
June | 720.00000 | 22.62975 | 57.21001 | -0.8655 | 25.74471 |
July | 744.00000 | 22.69160 | 59.63964 | -0.7961 | 23.41220 |
August | 744.00000 | 22.59011 | 55.88875 | -0.8474 | 24.83520 |
September | 720.00000 | 22.30069 | 57.01884 | -1.0275 | 30.97486 |
October | 744.00000 | 21.65310 | 53.53097 | -0.1820 | 7.16019 |
November | 720.00000 | 20.80468 | 47.31786 | -0.5197 | 11.24791 |
December | 744.00000 | 20.55233 | 40.27927 | -0.6563 | 14.50869 |
Annual Sum or Average | 8760.00000 | 21.54149 | 49.56457 | -0.6903 | 18.83519 |
Minimum of Months | 672.00000 | 20.50449 | 35.27473 | -1.1953 | 7.16019 |
Maximum of Months | 744.00000 | 22.69160 | 59.63964 | -0.1820 | 37.61873 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.85211 | 42.84686 | -0.5206 | 11.01705 |
February | 672.00000 | 20.83705 | 38.79325 | -0.5496 | 11.61976 |
March | 744.00000 | 21.10437 | 46.58850 | -0.4072 | 8.64284 |
April | 720.00000 | 21.37709 | 49.93800 | -0.2914 | 7.07518 |
May | 744.00000 | 21.78718 | 52.60141 | -1.2784 | 39.98810 |
June | 720.00000 | 22.28558 | 58.97380 | -1.0347 | 29.69871 |
July | 744.00000 | 22.47866 | 62.31654 | -0.9350 | 26.36874 |
August | 744.00000 | 22.32656 | 58.56816 | -1.0172 | 29.05776 |
September | 720.00000 | 22.07894 | 56.81701 | -1.1434 | 34.09402 |
October | 744.00000 | 21.51273 | 53.74488 | -0.2251 | 6.57529 |
November | 720.00000 | 21.11999 | 48.51819 | -0.3907 | 8.42609 |
December | 744.00000 | 20.91753 | 42.99075 | -0.4975 | 10.32634 |
Annual Sum or Average | 8760.00000 | 21.56065 | 51.13148 | -0.6918 | 18.61762 |
Minimum of Months | 672.00000 | 20.83705 | 38.79325 | -1.2784 | 6.57529 |
Maximum of Months | 744.00000 | 22.47866 | 62.31654 | -0.2251 | 39.98810 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.67531 | 39.77608 | -0.6244 | 13.75492 |
February | 672.00000 | 20.81000 | 34.75835 | -0.6035 | 13.22091 |
March | 744.00000 | 21.13902 | 43.81549 | -0.4237 | 9.43196 |
April | 720.00000 | 21.39000 | 48.58324 | -0.2898 | 7.70583 |
May | 744.00000 | 21.65297 | 53.68818 | -1.2689 | 39.79736 |
June | 720.00000 | 21.78566 | 58.26967 | -1.1205 | 32.98749 |
July | 744.00000 | 21.81134 | 59.37928 | -1.0598 | 30.40959 |
August | 744.00000 | 21.81250 | 55.73153 | -1.0647 | 30.68146 |
September | 720.00000 | 21.74153 | 56.34396 | -1.1698 | 35.29555 |
October | 744.00000 | 21.65911 | 51.34622 | -0.1592 | 6.64950 |
November | 720.00000 | 21.09202 | 46.38357 | -0.4264 | 9.54167 |
December | 744.00000 | 20.81333 | 39.71104 | -0.5710 | 12.37651 |
Annual Sum or Average | 8760.00000 | 21.36829 | 49.06172 | -0.7327 | 20.19792 |
Minimum of Months | 672.00000 | 20.67531 | 34.75835 | -1.2689 | 6.64950 |
Maximum of Months | 744.00000 | 21.81250 | 59.37928 | -0.1592 | 39.79736 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.50744 | 40.12898 | -0.6833 | 15.45629 |
February | 672.00000 | 20.56161 | 35.21515 | -0.6881 | 15.52979 |
March | 744.00000 | 20.91332 | 44.30194 | -0.4951 | 10.58021 |
April | 720.00000 | 21.36001 | 48.84563 | -0.3092 | 7.94423 |
May | 744.00000 | 21.93390 | 53.34260 | -1.1962 | 37.07762 |
June | 720.00000 | 22.47323 | 58.31506 | -0.9169 | 26.03598 |
July | 744.00000 | 22.64622 | 60.19795 | -0.8087 | 23.19580 |
August | 744.00000 | 22.55411 | 56.17511 | -0.8569 | 24.52862 |
September | 720.00000 | 22.23566 | 57.06767 | -1.0450 | 30.82818 |
October | 744.00000 | 21.61222 | 53.12211 | -0.1978 | 6.89950 |
November | 720.00000 | 20.85308 | 47.10584 | -0.5021 | 10.88392 |
December | 744.00000 | 20.56179 | 40.23704 | -0.6512 | 14.40745 |
Annual Sum or Average | 8760.00000 | 21.52324 | 49.58556 | -0.6960 | 18.63593 |
Minimum of Months | 672.00000 | 20.50744 | 35.21515 | -1.1962 | 6.89950 |
Maximum of Months | 744.00000 | 22.64622 | 60.19795 | -0.1978 | 37.07762 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.59984 | 39.97747 | -0.6754 | 15.24867 |
February | 672.00000 | 20.71067 | 34.97254 | -0.6627 | 14.94510 |
March | 744.00000 | 21.03518 | 44.07917 | -0.4630 | 10.41469 |
April | 720.00000 | 21.30357 | 49.15006 | -0.3162 | 8.29436 |
May | 744.00000 | 21.62086 | 54.07596 | -1.2696 | 40.03141 |
June | 720.00000 | 21.77635 | 57.90583 | -1.0947 | 32.11483 |
July | 744.00000 | 21.80915 | 59.36934 | -1.0367 | 29.66234 |
August | 744.00000 | 21.80545 | 55.93813 | -1.0467 | 30.17885 |
September | 720.00000 | 21.71849 | 56.81204 | -1.1676 | 35.43046 |
October | 744.00000 | 21.59908 | 51.87104 | -0.1724 | 6.95942 |
November | 720.00000 | 20.95713 | 46.90014 | -0.4866 | 10.82865 |
December | 744.00000 | 20.70844 | 39.96512 | -0.6304 | 13.95046 |
Annual Sum or Average | 8760.00000 | 21.30708 | 49.33106 | -0.7524 | 20.70776 |
Minimum of Months | 672.00000 | 20.59984 | 34.97254 | -1.2696 | 6.95942 |
Maximum of Months | 744.00000 | 21.80915 | 59.36934 | -0.1724 | 40.03141 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.45806 | 40.27865 | -0.7310 | 16.91064 |
February | 672.00000 | 20.49520 | 35.38340 | -0.7434 | 17.24588 |
March | 744.00000 | 20.82234 | 44.56610 | -0.5341 | 11.78083 |
April | 720.00000 | 21.33131 | 49.22084 | -0.3241 | 8.80553 |
May | 744.00000 | 22.07859 | 53.15660 | -1.1419 | 36.56451 |
June | 720.00000 | 22.79114 | 55.84966 | -0.7920 | 25.09354 |
July | 744.00000 | 22.80292 | 58.56826 | -0.7361 | 22.94633 |
August | 744.00000 | 22.68255 | 55.13066 | -0.7961 | 24.49393 |
September | 720.00000 | 22.41753 | 56.30981 | -0.9804 | 30.32248 |
October | 744.00000 | 21.67698 | 53.31500 | -0.1849 | 7.66950 |
November | 720.00000 | 20.72227 | 47.53656 | -0.5659 | 12.43798 |
December | 744.00000 | 20.47908 | 40.45506 | -0.7088 | 16.09122 |
Annual Sum or Average | 8760.00000 | 21.56918 | 49.22691 | -0.6863 | 19.21325 |
Minimum of Months | 672.00000 | 20.45806 | 35.38340 | -1.1419 | 7.66950 |
Maximum of Months | 744.00000 | 22.80292 | 58.56826 | -0.1849 | 36.56451 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.06073 | 46.12599 | -0.4628 | 10.60342 |
February | 672.00000 | 21.24558 | 41.16253 | -0.4232 | 10.07123 |
March | 744.00000 | 21.33708 | 49.85855 | -0.3207 | 8.21998 |
April | 720.00000 | 21.44588 | 53.59807 | -0.2494 | 7.23787 |
May | 744.00000 | 21.64333 | 57.02780 | -1.2772 | 40.18103 |
June | 720.00000 | 21.76545 | 60.81593 | -1.1436 | 34.06637 |
July | 744.00000 | 21.81196 | 62.11602 | -1.0806 | 31.33413 |
August | 744.00000 | 21.80744 | 57.85718 | -1.0899 | 31.84076 |
September | 720.00000 | 21.74559 | 57.51675 | -1.1594 | 35.03004 |
October | 744.00000 | 21.70159 | 53.27094 | -0.1024 | 6.56166 |
November | 720.00000 | 21.42026 | 51.04456 | -0.2859 | 7.74065 |
December | 744.00000 | 21.19378 | 45.86566 | -0.4060 | 9.70570 |
Annual Sum or Average | 8760.00000 | 21.51623 | 53.08931 | -0.6683 | 19.44134 |
Minimum of Months | 672.00000 | 21.06073 | 41.16253 | -1.2772 | 6.56166 |
Maximum of Months | 744.00000 | 21.81196 | 62.11602 | -0.1024 | 40.18103 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.97839 | 37.74498 | 0.53693 | 12.35497 |
February | 672.00000 | 25.02243 | 34.12229 | 0.52332 | 11.81157 |
March | 744.00000 | 25.56219 | 40.14704 | 0.74323 | 17.62143 |
April | 720.00000 | 25.76924 | 44.17260 | 0.86273 | 21.55501 |
May | 744.00000 | 25.71207 | 49.25707 | 0.22392 | 7.36442 |
June | 720.00000 | 25.65717 | 55.53999 | 0.30102 | 8.07950 |
July | 744.00000 | 25.92109 | 57.58945 | 0.42279 | 9.65375 |
August | 744.00000 | 25.87127 | 56.01416 | 0.39575 | 9.43921 |
September | 720.00000 | 25.52672 | 53.85580 | 0.21821 | 7.25042 |
October | 744.00000 | 25.68007 | 48.16910 | 0.89010 | 22.53934 |
November | 720.00000 | 25.54662 | 41.52644 | 0.75132 | 18.03459 |
December | 744.00000 | 25.22538 | 36.74600 | 0.60455 | 13.60715 |
Annual Sum or Average | 8760.00000 | 25.54270 | 46.31225 | 0.53969 | 13.28301 |
Minimum of Months | 672.00000 | 24.97839 | 34.12229 | 0.21821 | 7.25042 |
Maximum of Months | 744.00000 | 25.92109 | 57.58945 | 0.89010 | 22.53934 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 25.56899 | 36.38412 | 0.73441 | 17.68350 |
February | 672.00000 | 25.61417 | 32.89319 | 0.72049 | 16.99338 |
March | 744.00000 | 26.13201 | 38.79346 | 0.92810 | 24.01170 |
April | 720.00000 | 26.26232 | 42.80051 | 1.02342 | 27.79834 |
May | 744.00000 | 26.14279 | 47.84779 | 0.42516 | 10.05859 |
June | 720.00000 | 26.02469 | 54.09812 | 0.47520 | 10.88999 |
July | 744.00000 | 26.25760 | 56.15849 | 0.58331 | 13.03440 |
August | 744.00000 | 26.20231 | 54.63475 | 0.55474 | 12.60051 |
September | 720.00000 | 25.89051 | 52.46183 | 0.39165 | 9.44542 |
October | 744.00000 | 26.10413 | 46.80690 | 1.02998 | 28.07919 |
November | 720.00000 | 26.08024 | 40.16951 | 0.92600 | 24.05445 |
December | 744.00000 | 25.82945 | 35.44147 | 0.80354 | 19.47627 |
Annual Sum or Average | 8760.00000 | 26.01174 | 44.94517 | 0.71643 | 17.84858 |
Minimum of Months | 672.00000 | 25.56899 | 32.89319 | 0.39165 | 9.44542 |
Maximum of Months | 744.00000 | 26.26232 | 56.15849 | 1.02998 | 28.07919 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 29.19843 | 35.73395 | 2.24200 | 77.02778 |
February | 672.00000 | 29.30572 | 32.77999 | 2.24825 | 77.06508 |
March | 744.00000 | 29.78099 | 36.99023 | 2.45486 | 81.84215 |
April | 720.00000 | 29.77608 | 40.28949 | 2.53131 | 83.69312 |
May | 744.00000 | 29.47198 | 44.75332 | 2.52546 | 78.33109 |
June | 720.00000 | 29.08289 | 50.66811 | 2.48476 | 76.96733 |
July | 744.00000 | 29.19133 | 52.68135 | 2.54467 | 77.31297 |
August | 744.00000 | 29.30432 | 50.90713 | 2.59307 | 77.92260 |
September | 720.00000 | 29.10150 | 49.07810 | 2.45543 | 76.59934 |
October | 744.00000 | 29.61855 | 43.61848 | 2.55532 | 84.07509 |
November | 720.00000 | 29.67735 | 38.22015 | 2.43662 | 81.81902 |
December | 744.00000 | 29.49663 | 34.61737 | 2.32202 | 79.31776 |
Annual Sum or Average | 8760.00000 | 29.41815 | 42.58595 | 2.45083 | 79.34493 |
Minimum of Months | 672.00000 | 29.08289 | 32.77999 | 2.24200 | 76.59934 |
Maximum of Months | 744.00000 | 29.78099 | 52.68135 | 2.59307 | 84.07509 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.521986E+09 | 12367.78 | 24-JAN-19:01 | 112.80 | 0.162647E+10 | 0.00 | 0.214846E+10 | 0.47 | 3.12 | 01-JAN-09:02 | 0.00 | 0.00 |
February | 0.612078E+09 | 14952.75 | 19-FEB-09:02 | 144.28 | 0.190719E+10 | 0.00 | 0.251927E+10 | 0.67 | 3.12 | 01-FEB-09:46 | 0.00 | 0.00 |
March | 0.358595E+10 | 73589.04 | 27-MAR-16:02 | 297.80 | 0.109723E+11 | 0.00 | 0.145582E+11 | 1.24 | 3.42 | 27-MAR-13:07 | 0.00 | 0.00 |
April | 0.191421E+11 | 103046.10 | 07-APR-16:41 | 484.64 | 0.575803E+11 | 0.00 | 0.767224E+11 | 2.05 | 3.80 | 09-APR-10:51 | 0.00 | 0.00 |
May | 0.579935E+11 | 146685.01 | 31-MAY-08:11 | 719.47 | 0.177546E+12 | 0.00 | 0.235539E+12 | 2.90 | 4.27 | 19-MAY-18:01 | 0.00 | 0.00 |
June | 0.172926E+12 | 225865.00 | 19-JUN-08:02 | 720.00 | 0.602988E+12 | 0.00 | 0.775915E+12 | 3.15 | 4.47 | 12-JUN-21:13 | 0.00 | 0.00 |
July | 0.270186E+12 | 230963.87 | 20-JUL-18:22 | 744.00 | 0.952930E+12 | 0.00 | 0.122312E+13 | 3.17 | 4.36 | 15-JUL-08:14 | 0.00 | 0.00 |
August | 0.236247E+12 | 243473.58 | 04-AUG-18:04 | 744.00 | 0.794872E+12 | 0.00 | 0.103112E+13 | 3.06 | 4.32 | 06-AUG-21:12 | 0.00 | 0.00 |
September | 0.132400E+12 | 211556.15 | 13-SEP-21:14 | 719.73 | 0.449360E+12 | 0.00 | 0.581760E+12 | 3.08 | 4.39 | 22-SEP-19:37 | 0.00 | 0.00 |
October | 0.593107E+11 | 141065.89 | 04-OCT-15:21 | 693.13 | 0.196239E+12 | 0.00 | 0.255549E+12 | 2.89 | 4.46 | 24-OCT-08:11 | 0.00 | 0.00 |
November | 0.641757E+10 | 61918.68 | 10-NOV-09:01 | 350.59 | 0.195692E+11 | 0.00 | 0.259868E+11 | 1.51 | 3.58 | 10-NOV-09:01 | 0.00 | 0.00 |
December | 0.127693E+10 | 12686.77 | 25-DEC-09:02 | 163.72 | 0.397882E+10 | 0.00 | 0.525575E+10 | 0.69 | 3.12 | 01-DEC-07:07 | 0.00 | 0.00 |
Annual Sum or Average | 0.960620E+12 | 5894.16 | 0.326957E+13 | 0.423019E+13 | 2.08 | |||||||
Minimum of Months | 0.521986E+09 | 12367.78 | 112.80 | 0.162647E+10 | 0.00 | 0.214846E+10 | 0.47 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.270186E+12 | 243473.58 | 744.00 | 0.952930E+12 | 0.00 | 0.122312E+13 | 3.17 | 4.47 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.712367E+11 | 0.00 | 710.48 | 179116.72 | 02-JAN-09:02 | 0.00 | 57.17 | 59.92 | 2.04 | 0.00 | 0.06 | 0.42 | 02-JAN-09:02 |
February | 0.662138E+11 | 0.00 | 621.90 | 190465.16 | 06-FEB-09:02 | 0.00 | 57.35 | 59.96 | 2.13 | 0.00 | 0.06 | 0.44 | 06-FEB-09:02 |
March | 0.249964E+11 | 0.00 | 605.72 | 87986.26 | 16-MAR-15:14 | 0.00 | 58.08 | 59.67 | 1.23 | 0.00 | 0.02 | 0.21 | 16-MAR-15:14 |
April | 0.948115E+10 | 0.00 | 421.59 | 40397.88 | 21-APR-15:14 | 0.00 | 57.14 | 58.54 | 0.55 | 0.00 | 0.01 | 0.09 | 21-APR-15:14 |
May | 0.146195E+10 | 0.00 | 175.73 | 64112.65 | 13-MAY-23:03 | 0.00 | 55.53 | 56.49 | 0.06 | 0.00 | 0.00 | 0.15 | 13-MAY-23:03 |
June | 62656097.74 | 0.00 | 4.74 | 29460.99 | 05-JUN-08:15 | 0.00 | 50.45 | 50.52 | 0.00 | 0.00 | 0.00 | 0.07 | 05-JUN-08:15 |
July | 19430713.13 | 0.00 | 2.51 | 8171.35 | 03-JUL-08:20 | 0.00 | 48.33 | 48.37 | 0.00 | 0.00 | 0.00 | 0.02 | 03-JUL-08:20 |
August | 0.105875E+09 | 0.00 | 3.95 | 41420.58 | 30-AUG-13:54 | 0.00 | 48.10 | 48.17 | 0.00 | 0.00 | 0.00 | 0.10 | 30-AUG-13:54 |
September | 0.257437E+09 | 0.00 | 61.18 | 28534.76 | 10-SEP-08:16 | 0.00 | 50.44 | 50.83 | 0.01 | 0.00 | 0.00 | 0.07 | 10-SEP-08:16 |
October | 0.207420E+10 | 0.00 | 243.32 | 39088.65 | 30-OCT-20:33 | 0.00 | 57.92 | 58.47 | 0.18 | 0.00 | 0.00 | 0.09 | 30-OCT-20:33 |
November | 0.243669E+11 | 0.00 | 592.70 | 77526.93 | 23-NOV-06:20 | 0.00 | 57.54 | 59.56 | 1.00 | 0.00 | 0.02 | 0.18 | 23-NOV-06:20 |
December | 0.454838E+11 | 0.00 | 682.02 | 121355.65 | 31-DEC-23:10 | 0.00 | 57.88 | 59.91 | 1.71 | 0.00 | 0.04 | 0.28 | 31-DEC-23:10 |
Annual Sum or Average | 0.245760E+12 | 4125.84 | 54.65 | 55.84 | 0.74 | 0.00 | 0.02 | ||||||
Minimum of Months | 19430713.13 | 0.00 | 2.51 | 8171.35 | 0.00 | 48.10 | 48.17 | 0.00 | 0.00 | 0.00 | 0.02 | ||
Maximum of Months | 0.712367E+11 | 0.00 | 710.48 | 190465.16 | 0.00 | 58.08 | 59.96 | 2.13 | 0.00 | 0.06 | 0.44 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 15582806.69 | 0.00 | 3.85 | 14625877.48 | 0.00 | 0.00 | 0.00 | 0.00 | 13854.00 | 17-JAN-16:11 | 13854.00 | 17-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 47893373.55 | 0.00 | 11.65 | 47492645.64 | 0.00 | 0.00 | 0.00 | 0.00 | 13847.09 | 02-FEB-16:11 | 13847.09 | 02-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.451736E+09 | 0.00 | 82.10 | 0.351451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14312.95 | 27-MAR-16:01 | 13860.45 | 07-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.134698E+10 | 0.00 | 233.57 | 0.814778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14621.05 | 09-APR-08:61 | 13862.32 | 04-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.312955E+10 | 0.00 | 480.01 | 0.169561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15757.99 | 18-MAY-15:11 | 13864.12 | 02-MAY-15:11 | 0.00 | 0.00 | 0.00 |
June | 0.727541E+10 | 0.00 | 655.02 | 0.354279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17688.04 | 18-JUN-08:61 | 12723.18 | 17-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.101482E+11 | 0.00 | 721.18 | 0.506380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17645.45 | 28-JUL-08:61 | 12792.15 | 15-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.101329E+11 | 0.00 | 716.40 | 0.562789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17194.08 | 27-AUG-08:61 | 12702.50 | 29-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.549984E+10 | 0.00 | 607.88 | 0.268259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18982.36 | 22-SEP-18:01 | 13862.87 | 10-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.312584E+10 | 0.00 | 474.21 | 0.153529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15814.57 | 24-OCT-08:61 | 13860.46 | 07-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.191543E+09 | 0.00 | 67.18 | 0.106805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13864.60 | 01-NOV-15:11 | 13864.60 | 01-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 18826760.58 | 0.00 | 7.85 | 14937920.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13665.12 | 17-DEC-16:11 | 13665.12 | 17-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.413843E+11 | 4060.89 | 0.214981E+11 | ||||||||||||
Minimum of Months | 15582806.69 | 0.00 | 3.85 | 14625877.48 | 0.00 | 0.00 | 0.00 | 0.00 | 13665.12 | 12702.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101482E+11 | 0.00 | 721.18 | 0.562789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18982.36 | 13864.60 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 2625883.70 | 0.00 | 0.42 | 2155067.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9630.93 | 17-JAN-16:11 | 9630.93 | 17-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 5827161.44 | 0.00 | 1.87 | 5619404.82 | 0.00 | 0.00 | 0.00 | 0.00 | 12551.67 | 20-FEB-16:11 | 12551.67 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.198631E+09 | 0.00 | 40.96 | 0.158283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13632.35 | 11-MAR-16:11 | 13632.35 | 11-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.787354E+09 | 0.00 | 171.06 | 0.425882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14381.24 | 09-APR-08:61 | 13934.51 | 09-APR-17:31 | 0.00 | 0.00 | 0.00 |
May | 0.204313E+10 | 0.00 | 366.31 | 0.955828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15821.01 | 31-MAY-21:11 | 14223.58 | 02-MAY-17:41 | 0.00 | 0.00 | 0.00 |
June | 0.487480E+10 | 0.00 | 452.95 | 0.236034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19549.93 | 25-JUN-08:11 | 13402.72 | 22-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.732580E+10 | 0.00 | 511.33 | 0.382787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20976.64 | 22-JUL-08:11 | 12615.82 | 11-JUL-08:11 | 0.00 | 0.00 | 0.00 |
August | 0.737034E+10 | 0.00 | 528.43 | 0.411657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19826.58 | 03-AUG-08:11 | 13205.96 | 28-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.300605E+10 | 0.00 | 386.70 | 0.130384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19004.18 | 14-SEP-08:11 | 13805.20 | 10-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.109084E+10 | 0.00 | 263.84 | 0.414018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15519.39 | 25-OCT-08:11 | 13637.05 | 07-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 30497948.67 | 0.00 | 12.41 | 18722471.13 | 0.00 | 0.00 | 0.00 | 0.00 | 13017.73 | 01-NOV-15:11 | 13017.73 | 01-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 1365093.22 | 0.00 | 0.33 | 973846.78 | 0.00 | 0.00 | 0.00 | 0.00 | 3420.24 | 17-DEC-16:11 | 3420.24 | 17-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267373E+11 | 2736.61 | 0.135901E+11 | ||||||||||||
Minimum of Months | 1365093.22 | 0.00 | 0.33 | 973846.78 | 0.00 | 0.00 | 0.00 | 0.00 | 3420.24 | 3420.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.737034E+10 | 0.00 | 528.43 | 0.411657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20976.64 | 14223.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 14737305.69 | 0.00 | 4.47 | 1482324.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2607.75 | 03-FEB-12:31 | 378.49 | 03-FEB-12:31 | 0.00 | 0.00 | 0.00 |
March | 0.767806E+09 | 0.00 | 41.56 | 0.198722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16907.33 | 28-MAR-12:21 | 8963.46 | 15-MAR-15:03 | 0.00 | 0.00 | 0.00 |
April | 0.577406E+10 | 0.00 | 173.87 | 0.229447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33382.40 | 08-APR-12:01 | 24118.22 | 08-APR-12:21 | 0.00 | 0.00 | 0.00 |
May | 0.157011E+11 | 0.00 | 488.58 | 0.486873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26529.89 | 29-MAY-07:51 | 13018.53 | 22-MAY-15:03 | 0.00 | 0.00 | 0.00 |
June | 0.331794E+11 | 0.00 | 687.34 | 0.119821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31173.26 | 19-JUN-17:11 | 19333.52 | 19-JUN-20:11 | 0.00 | 0.00 | 0.00 |
July | 0.470220E+11 | 0.00 | 738.60 | 0.192372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35412.61 | 08-JUL-07:51 | 21192.14 | 08-JUL-07:51 | 0.00 | 0.00 | 0.00 |
August | 0.511592E+11 | 0.00 | 742.95 | 0.246361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35999.80 | 16-AUG-12:21 | 26276.20 | 30-AUG-12:31 | 0.00 | 0.00 | 0.00 |
September | 0.377264E+11 | 0.00 | 668.93 | 0.180223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42330.80 | 14-SEP-12:21 | 35464.04 | 29-SEP-12:22 | 0.00 | 0.00 | 0.00 |
October | 0.364045E+11 | 0.00 | 615.18 | 0.194372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47180.26 | 04-OCT-12:10 | 35162.90 | 22-OCT-10:42 | 0.00 | 0.00 | 0.00 |
November | 0.734702E+10 | 0.00 | 180.83 | 0.351747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40217.97 | 04-NOV-12:32 | 35505.15 | 02-NOV-11:12 | 0.00 | 0.00 | 0.00 |
December | 0.142572E+10 | 0.00 | 37.97 | 0.637065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23586.17 | 20-DEC-09:51 | 14872.37 | 21-DEC-13:21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236522E+12 | 4380.27 | 0.104833E+12 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.511592E+11 | 0.00 | 742.95 | 0.246361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47180.26 | 35505.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.307218E+09 | 0.00 | 26.82 | 0.103940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73239.33 | 24-JAN-09:01 | 65164.04 | 22-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.110843E+09 | 0.00 | 12.83 | 56503275.47 | 0.00 | 0.00 | 0.00 | 0.00 | 66569.08 | 25-FEB-09:01 | 66569.08 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.271058E+10 | 0.00 | 151.38 | 0.116149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74965.73 | 06-MAR-16:11 | 71293.48 | 15-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.121664E+11 | 0.00 | 341.73 | 0.602007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80992.13 | 30-APR-15:11 | 74350.78 | 11-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.270681E+11 | 0.00 | 431.48 | 0.150085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86978.56 | 31-MAY-21:11 | 76522.74 | 27-MAY-21:11 | 0.00 | 0.00 | 0.00 |
June | 0.407966E+11 | 0.00 | 404.46 | 0.247353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109168.75 | 25-JUN-08:11 | 78251.74 | 04-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.571522E+11 | 0.00 | 470.72 | 0.351763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117581.55 | 22-JUL-08:11 | 71471.05 | 11-JUL-08:11 | 0.00 | 0.00 | 0.00 |
August | 0.525429E+11 | 0.00 | 477.61 | 0.325740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110735.97 | 17-AUG-07:11 | 72346.73 | 28-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.307728E+11 | 0.00 | 372.32 | 0.175216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107299.09 | 14-SEP-08:11 | 74938.31 | 10-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.157840E+11 | 0.00 | 369.96 | 0.731242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86610.89 | 25-OCT-08:11 | 73688.35 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.397455E+10 | 0.00 | 197.73 | 0.149607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82193.64 | 10-NOV-09:01 | 71853.71 | 02-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 0.251545E+09 | 0.00 | 25.42 | 0.118260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70188.46 | 25-DEC-09:01 | 69244.63 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243638E+12 | 3282.45 | 0.141284E+12 | ||||||||||||
Minimum of Months | 0.110843E+09 | 0.00 | 12.83 | 56503275.47 | 0.00 | 0.00 | 0.00 | 0.00 | 66569.08 | 65164.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.571522E+11 | 0.00 | 477.61 | 0.351763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117581.55 | 78251.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 25305234.80 | 0.00 | 10.12 | 14802520.65 | 0.00 | 0.00 | 0.00 | 0.00 | 11186.05 | 20-JAN-09:01 | 11186.05 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 48574693.73 | 0.00 | 14.88 | 36472759.66 | 0.00 | 0.00 | 0.00 | 0.00 | 12036.90 | 25-FEB-09:01 | 12036.90 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.332862E+09 | 0.00 | 76.57 | 0.233454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12433.35 | 15-MAR-15:11 | 12433.35 | 15-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.132857E+10 | 0.00 | 252.68 | 0.741886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12867.71 | 09-APR-08:61 | 12435.03 | 12-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.325322E+10 | 0.00 | 512.20 | 0.176479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14070.90 | 18-MAY-15:11 | 12434.96 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.675461E+10 | 0.00 | 671.23 | 0.323738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16221.39 | 18-JUN-08:61 | 11549.96 | 08-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.996460E+10 | 0.00 | 726.72 | 0.496996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15662.22 | 23-JUL-08:61 | 11478.92 | 27-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.999738E+10 | 0.00 | 727.87 | 0.547167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15321.59 | 06-AUG-08:61 | 11532.67 | 13-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.549741E+10 | 0.00 | 627.68 | 0.272353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17064.54 | 22-SEP-18:01 | 12436.48 | 10-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.292139E+10 | 0.00 | 476.71 | 0.140719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14552.54 | 24-OCT-08:61 | 12434.03 | 07-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.296265E+09 | 0.00 | 80.09 | 0.154285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13652.45 | 10-NOV-09:01 | 12251.92 | 02-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 59815316.14 | 0.00 | 14.27 | 33339311.98 | 0.00 | 0.00 | 0.00 | 0.00 | 11470.67 | 02-DEC-09:01 | 11470.67 | 02-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.404800E+11 | 4191.02 | 0.207888E+11 | ||||||||||||
Minimum of Months | 25305234.80 | 0.00 | 10.12 | 14802520.65 | 0.00 | 0.00 | 0.00 | 0.00 | 11186.05 | 11186.05 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.999738E+10 | 0.00 | 727.87 | 0.547167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17064.54 | 12436.48 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 1135172.98 | 0.00 | 0.53 | 563197.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.66 | 24-JAN-19:04 | 1753.10 | 30-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 8602094.22 | 0.00 | 3.08 | 6518076.67 | 0.00 | 0.00 | 0.00 | 0.00 | 11462.82 | 25-FEB-09:01 | 11462.82 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.148298E+09 | 0.00 | 36.94 | 91967030.71 | 0.00 | 0.00 | 0.00 | 0.00 | 11912.66 | 26-MAR-08:61 | 11258.59 | 23-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.871874E+09 | 0.00 | 184.41 | 0.476021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12852.63 | 09-APR-08:61 | 12351.99 | 12-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.232963E+10 | 0.00 | 389.75 | 0.122502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15735.75 | 31-MAY-08:11 | 13666.80 | 30-MAY-08:11 | 0.00 | 0.00 | 0.00 |
June | 0.467826E+10 | 0.00 | 463.95 | 0.229579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18460.51 | 25-JUN-08:11 | 13708.27 | 22-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.727246E+10 | 0.00 | 513.80 | 0.382841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19202.39 | 22-JUL-08:11 | 13187.61 | 11-JUL-08:11 | 0.00 | 0.00 | 0.00 |
August | 0.733846E+10 | 0.00 | 532.71 | 0.409310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18454.53 | 03-AUG-08:11 | 13471.99 | 22-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.320176E+10 | 0.00 | 409.73 | 0.154344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17228.77 | 14-SEP-08:11 | 13365.11 | 10-SEP-08:11 | 0.00 | 0.00 | 0.00 |
October | 0.111479E+10 | 0.00 | 247.40 | 0.487449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14914.68 | 25-OCT-08:11 | 11653.72 | 26-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 74195631.97 | 0.00 | 23.79 | 29760555.37 | 0.00 | 0.00 | 0.00 | 0.00 | 12049.23 | 11-NOV-09:01 | 10539.83 | 08-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 3173484.17 | 0.00 | 1.37 | 2022611.39 | 0.00 | 0.00 | 0.00 | 0.00 | 8670.16 | 17-DEC-09:01 | 8670.16 | 17-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270427E+11 | 2807.47 | 0.140801E+11 | ||||||||||||
Minimum of Months | 1135172.98 | 0.00 | 0.53 | 563197.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3223.66 | 1753.10 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.733846E+10 | 0.00 | 532.71 | 0.409310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19202.39 | 13708.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 4752569.37 | 0.00 | 4.35 | 4598545.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3648.32 | 17-JAN-16:11 | 3648.32 | 17-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 13720907.73 | 0.00 | 11.92 | 13625196.40 | 0.00 | 0.00 | 0.00 | 0.00 | 3648.86 | 20-FEB-16:11 | 3648.86 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.129084E+09 | 0.00 | 81.70 | 0.101003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3775.70 | 27-MAR-16:01 | 3648.04 | 07-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.390397E+09 | 0.00 | 222.25 | 0.246254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3853.57 | 09-APR-08:61 | 3648.54 | 04-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.924407E+09 | 0.00 | 486.93 | 0.540330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4149.66 | 18-MAY-15:11 | 3648.95 | 02-MAY-15:11 | 0.00 | 0.00 | 0.00 |
June | 0.203183E+10 | 0.00 | 665.62 | 0.104004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4729.78 | 18-JUN-08:61 | 3372.83 | 28-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.278961E+10 | 0.00 | 722.97 | 0.144672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4710.24 | 28-JUL-08:61 | 3369.16 | 22-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.273865E+10 | 0.00 | 716.61 | 0.157497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4623.03 | 27-AUG-08:61 | 3358.37 | 09-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.148140E+10 | 0.00 | 598.53 | 0.758127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5059.51 | 22-SEP-18:01 | 3648.28 | 10-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.819085E+09 | 0.00 | 431.41 | 0.427279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4158.40 | 25-OCT-08:61 | 3648.99 | 29-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 45459190.29 | 0.00 | 53.23 | 27965364.87 | 0.00 | 0.00 | 0.00 | 0.00 | 3649.13 | 01-NOV-15:11 | 3649.13 | 01-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 4197248.16 | 0.00 | 4.67 | 3878234.74 | 0.00 | 0.00 | 0.00 | 0.00 | 3639.80 | 17-DEC-16:11 | 3639.80 | 17-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113726E+11 | 4000.20 | 0.618478E+10 | ||||||||||||
Minimum of Months | 4197248.16 | 0.00 | 4.35 | 3878234.74 | 0.00 | 0.00 | 0.00 | 0.00 | 3639.80 | 3358.37 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.278961E+10 | 0.00 | 722.97 | 0.157497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5059.51 | 3649.13 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 312112.98 | 0.00 | 0.27 | 246495.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1833.77 | 17-JAN-16:11 | 1833.77 | 17-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 631585.59 | 0.00 | 0.70 | 604081.69 | 0.00 | 0.00 | 0.00 | 0.00 | 3149.80 | 20-FEB-16:11 | 3149.80 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 50537855.10 | 0.00 | 40.33 | 39616859.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3587.74 | 11-MAR-16:11 | 3587.74 | 11-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.236166E+09 | 0.00 | 167.79 | 0.134580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3894.06 | 09-APR-17:31 | 3894.06 | 09-APR-17:31 | 0.00 | 0.00 | 0.00 |
May | 0.643774E+09 | 0.00 | 374.14 | 0.336964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4357.93 | 31-MAY-21:11 | 3857.23 | 02-MAY-17:41 | 0.00 | 0.00 | 0.00 |
June | 0.145096E+10 | 0.00 | 463.94 | 0.762759E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5229.46 | 25-JUN-08:11 | 3522.69 | 22-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.209493E+10 | 0.00 | 513.10 | 0.116759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5622.91 | 22-JUL-08:11 | 3458.45 | 04-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.207053E+10 | 0.00 | 531.03 | 0.121471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5267.98 | 03-AUG-08:11 | 3535.94 | 28-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.849653E+09 | 0.00 | 393.25 | 0.393622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5052.92 | 14-SEP-08:11 | 3725.13 | 10-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.284014E+09 | 0.00 | 237.74 | 0.111805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4117.75 | 05-OCT-21:11 | 3588.97 | 07-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 6836709.17 | 0.00 | 9.42 | 4414493.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3369.57 | 01-NOV-15:11 | 3369.57 | 01-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 288274.60 | 0.00 | 0.27 | 240915.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.60 | 25-DEC-16:13 | 527.33 | 03-DEC-16:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.768864E+10 | 2731.97 | 0.416715E+10 | ||||||||||||
Minimum of Months | 288274.60 | 0.00 | 0.27 | 240915.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1044.60 | 527.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.209493E+10 | 0.00 | 531.03 | 0.121471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5622.91 | 3894.06 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.699795E+09 | 0.00 | 89.37 | 0.509698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14736.64 | 31-JAN-16:11 | 14736.64 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.920332E+09 | 0.00 | 135.65 | 0.693429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14749.81 | 25-FEB-16:11 | 14749.81 | 25-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.163419E+10 | 0.00 | 200.50 | 0.106848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15228.81 | 04-MAR-09:01 | 14747.22 | 13-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.245232E+10 | 0.00 | 307.98 | 0.135389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17003.05 | 09-APR-08:61 | 14743.21 | 11-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.454546E+10 | 0.00 | 542.20 | 0.224692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17526.09 | 18-MAY-15:11 | 14746.43 | 27-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.966212E+10 | 0.00 | 651.63 | 0.461648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19853.24 | 18-JUN-08:61 | 13744.53 | 01-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.144429E+11 | 0.00 | 719.57 | 0.741929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19778.35 | 21-JUL-08:61 | 13583.07 | 03-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.143680E+11 | 0.00 | 715.62 | 0.842141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19340.43 | 16-AUG-08:61 | 13689.46 | 18-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.980952E+10 | 0.00 | 643.59 | 0.550708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21030.90 | 22-SEP-18:01 | 14747.48 | 10-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.829389E+10 | 0.00 | 594.73 | 0.502680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17656.14 | 05-OCT-18:01 | 14751.10 | 26-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.205993E+10 | 0.00 | 231.28 | 0.120555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16660.73 | 11-NOV-09:01 | 14153.14 | 24-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.138793E+10 | 0.00 | 141.48 | 0.101573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14751.13 | 15-DEC-16:11 | 14751.13 | 15-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.702764E+11 | 4973.60 | 0.390848E+11 | ||||||||||||
Minimum of Months | 0.699795E+09 | 0.00 | 89.37 | 0.509698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14736.64 | 13583.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.144429E+11 | 0.00 | 719.57 | 0.842141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21030.90 | 14751.13 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.278109E+10 | 0.00 | 10.97 | 0.253730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 236251.80 | 27-MAR-13:11 | 203603.09 | 27-MAR-15:42 | 0.00 | 0.00 | 0.00 |
April | 0.277150E+11 | 0.00 | 76.92 | 0.271700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 332799.56 | 09-APR-10:51 | 301711.09 | 07-APR-16:41 | 0.00 | 0.00 | 0.00 |
May | 0.105657E+12 | 0.00 | 235.69 | 0.875468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 473384.86 | 31-MAY-17:11 | 367760.56 | 30-MAY-13:01 | 0.00 | 0.00 | 0.00 |
June | 0.446720E+12 | 0.00 | 360.91 | 0.244891E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 757174.19 | 25-JUN-08:42 | 403189.96 | 22-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.730089E+12 | 0.00 | 373.04 | 0.353911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 872142.07 | 20-JUL-18:22 | 376111.92 | 10-JUL-18:52 | 0.00 | 0.00 | 0.00 |
August | 0.584795E+12 | 0.00 | 376.95 | 0.349467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 889394.15 | 03-AUG-17:52 | 469797.55 | 24-AUG-16:08 | 0.00 | 0.00 | 0.00 |
September | 0.319281E+12 | 0.00 | 330.62 | 0.203377E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 695359.22 | 14-SEP-10:40 | 435782.53 | 01-SEP-13:51 | 0.00 | 0.00 | 0.00 |
October | 0.113308E+12 | 0.00 | 177.43 | 0.683735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 473638.70 | 04-OCT-15:21 | 303588.72 | 04-OCT-12:51 | 0.00 | 0.00 | 0.00 |
November | 0.356229E+10 | 0.00 | 17.97 | 0.308653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 199245.54 | 10-NOV-08:05 | 124148.16 | 04-NOV-12:11 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233391E+13 | 1960.50 | 0.134036E+13 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.730089E+12 | 0.00 | 376.95 | 0.353911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 889394.15 | 469797.55 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.255549E+09 | 0.00 | 14.33 | 0.220960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19163.40 | 27-MAR-12:51 | 15246.74 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.203530E+10 | 0.00 | 94.33 | 0.199944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18758.48 | 09-APR-12:03 | 17791.46 | 07-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.856939E+10 | 0.00 | 311.17 | 0.713884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31270.33 | 31-MAY-16:31 | 19330.49 | 30-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.418372E+11 | 0.00 | 538.00 | 0.231086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50430.65 | 25-JUN-08:61 | 22112.67 | 19-JUN-12:01 | 0.00 | 0.00 | 0.00 |
July | 0.608101E+11 | 0.00 | 568.33 | 0.321096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52007.89 | 21-JUL-08:61 | 21066.24 | 07-JUL-12:02 | 0.00 | 0.00 | 0.00 |
August | 0.484433E+11 | 0.00 | 568.33 | 0.301825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56281.59 | 05-AUG-18:02 | 20964.43 | 24-AUG-15:11 | 0.00 | 0.00 | 0.00 |
September | 0.284806E+11 | 0.00 | 478.00 | 0.184545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47143.64 | 13-SEP-18:01 | 19559.61 | 14-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.953549E+10 | 0.00 | 241.50 | 0.545277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30380.78 | 05-OCT-15:15 | 17153.76 | 04-OCT-12:01 | 0.00 | 0.00 | 0.00 |
November | 0.195362E+09 | 0.00 | 18.50 | 0.168823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6795.51 | 10-NOV-07:41 | 6399.30 | 04-NOV-12:51 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200162E+12 | 2832.50 | 0.118836E+12 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.608101E+11 | 0.00 | 568.33 | 0.321096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56281.59 | 22112.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 607.15 | 398.42 | 208.73 | 538.40 | 623.83 | 0.00 | 0.00 | 744.00 |
February | 803.78 | 534.32 | 269.47 | 699.03 | 628.93 | 0.00 | 0.00 | 672.00 |
March | 712.13 | 392.12 | 320.00 | 576.30 | 470.66 | 0.00 | 0.00 | 744.00 |
April | 566.59 | 229.19 | 337.40 | 403.81 | 343.56 | 0.00 | 0.00 | 720.00 |
May | 486.60 | 99.56 | 387.04 | 361.11 | 213.06 | 0.00 | 0.00 | 744.00 |
June | 459.45 | 70.71 | 388.74 | 427.14 | 106.60 | 0.00 | 0.00 | 720.00 |
July | 478.08 | 80.62 | 397.46 | 510.24 | 51.76 | 0.00 | 0.00 | 744.00 |
August | 640.34 | 236.14 | 404.19 | 649.77 | 79.70 | 0.00 | 0.00 | 744.00 |
September | 675.92 | 339.41 | 336.51 | 670.04 | 164.25 | 0.00 | 0.00 | 720.00 |
October | 955.55 | 599.38 | 356.17 | 986.49 | 316.28 | 0.00 | 0.00 | 744.00 |
November | 661.41 | 396.80 | 264.62 | 619.38 | 460.93 | 0.00 | 0.00 | 720.00 |
December | 655.86 | 465.80 | 190.06 | 618.77 | 572.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 641.13 | 319.12 | 322.02 | 588.10 | 334.31 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 459.45 | 70.71 | 190.06 | 361.11 | 51.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 955.55 | 599.38 | 404.19 | 986.49 | 628.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1709.69 | 1121.93 | 587.76 | 1487.83 | 1882.74 | 0.00 | 0.00 | 744.00 |
February | 2263.40 | 1504.60 | 758.81 | 1932.25 | 1894.31 | 0.00 | 0.00 | 672.00 |
March | 2005.30 | 1104.19 | 901.11 | 1593.23 | 1433.30 | 0.00 | 0.00 | 744.00 |
April | 1595.47 | 645.39 | 950.08 | 1115.66 | 1041.32 | 0.00 | 0.00 | 720.00 |
May | 1370.24 | 280.36 | 1089.88 | 1006.62 | 627.96 | 0.00 | 0.00 | 744.00 |
June | 1293.77 | 199.10 | 1094.67 | 1195.01 | 318.85 | 0.00 | 0.00 | 720.00 |
July | 1346.23 | 227.02 | 1119.21 | 1423.87 | 165.75 | 0.00 | 0.00 | 744.00 |
August | 1803.15 | 664.97 | 1138.18 | 1820.81 | 246.00 | 0.00 | 0.00 | 744.00 |
September | 1903.35 | 955.75 | 947.60 | 1880.55 | 489.86 | 0.00 | 0.00 | 720.00 |
October | 2690.75 | 1687.81 | 1002.94 | 2759.51 | 939.88 | 0.00 | 0.00 | 744.00 |
November | 1862.50 | 1117.35 | 745.15 | 1713.26 | 1399.11 | 0.00 | 0.00 | 720.00 |
December | 1846.86 | 1311.67 | 535.20 | 1709.55 | 1739.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1805.39 | 898.61 | 906.78 | 1635.84 | 1009.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1293.77 | 199.10 | 535.20 | 1006.62 | 165.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2690.75 | 1687.81 | 1138.18 | 2759.51 | 1894.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2220.99 | 1457.45 | 763.54 | 1947.68 | 2616.73 | 0.00 | 0.00 | 744.00 |
February | 2940.29 | 1954.56 | 985.73 | 2540.15 | 2604.40 | 0.00 | 0.00 | 672.00 |
March | 2605.00 | 1434.41 | 1170.59 | 2097.02 | 1970.45 | 0.00 | 0.00 | 744.00 |
April | 2072.61 | 838.39 | 1234.21 | 1464.04 | 1439.81 | 0.00 | 0.00 | 720.00 |
May | 1780.02 | 364.21 | 1415.82 | 1323.69 | 865.87 | 0.00 | 0.00 | 744.00 |
June | 1680.68 | 258.65 | 1422.04 | 1588.20 | 433.69 | 0.00 | 0.00 | 720.00 |
July | 1748.83 | 294.91 | 1453.92 | 1903.54 | 220.90 | 0.00 | 0.00 | 744.00 |
August | 2342.40 | 863.83 | 1478.57 | 2440.94 | 318.72 | 0.00 | 0.00 | 744.00 |
September | 2472.56 | 1241.57 | 1230.99 | 2503.27 | 650.33 | 0.00 | 0.00 | 720.00 |
October | 3495.44 | 2192.56 | 1302.88 | 3671.56 | 1245.59 | 0.00 | 0.00 | 744.00 |
November | 2419.49 | 1451.50 | 967.99 | 2254.90 | 1924.12 | 0.00 | 0.00 | 720.00 |
December | 2399.18 | 1703.93 | 695.25 | 2247.67 | 2406.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2345.30 | 1167.35 | 1177.96 | 2164.47 | 1384.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1680.68 | 258.65 | 695.25 | 1323.69 | 220.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3495.44 | 2192.56 | 1478.57 | 3671.56 | 2616.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.80 | 78.61 | 41.18 | 108.31 | 123.92 | 0.00 | 0.00 | 744.00 |
February | 158.60 | 105.43 | 53.17 | 140.79 | 124.82 | 0.00 | 0.00 | 672.00 |
March | 140.51 | 77.37 | 63.14 | 116.93 | 89.59 | 0.00 | 0.00 | 744.00 |
April | 111.80 | 45.22 | 66.57 | 84.43 | 61.71 | 0.00 | 0.00 | 720.00 |
May | 96.01 | 19.65 | 76.37 | 78.12 | 33.93 | 0.00 | 0.00 | 744.00 |
June | 90.66 | 13.95 | 76.70 | 93.58 | 12.61 | 0.00 | 0.00 | 720.00 |
July | 94.33 | 15.91 | 78.42 | 113.98 | 2.96 | 0.00 | 0.00 | 744.00 |
August | 126.35 | 46.59 | 79.75 | 142.97 | 7.36 | 0.00 | 0.00 | 744.00 |
September | 133.37 | 66.97 | 66.40 | 141.60 | 21.58 | 0.00 | 0.00 | 720.00 |
October | 188.54 | 118.27 | 70.28 | 203.13 | 50.90 | 0.00 | 0.00 | 744.00 |
November | 130.51 | 78.29 | 52.21 | 126.88 | 84.58 | 0.00 | 0.00 | 720.00 |
December | 129.41 | 91.91 | 37.50 | 125.50 | 110.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.50 | 62.97 | 63.54 | 123.00 | 60.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 90.66 | 13.95 | 37.50 | 78.12 | 2.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.54 | 118.27 | 79.75 | 203.13 | 124.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.05 | 36.56 | 52.48 | 38.51 | 253.15 | 0.00 | 0.00 | 744.00 |
February | 130.79 | 57.40 | 73.39 | 66.25 | 256.92 | 0.00 | 0.00 | 672.00 |
March | 194.29 | 90.05 | 104.24 | 144.06 | 165.42 | 0.00 | 0.00 | 744.00 |
April | 211.00 | 90.17 | 120.83 | 185.86 | 112.24 | 0.00 | 0.00 | 720.00 |
May | 246.46 | 93.68 | 152.79 | 254.33 | 60.93 | 0.00 | 0.00 | 744.00 |
June | 269.28 | 108.66 | 160.62 | 321.25 | 22.88 | 0.00 | 0.00 | 720.00 |
July | 251.94 | 94.66 | 157.28 | 331.41 | 5.46 | 0.00 | 0.00 | 744.00 |
August | 278.76 | 128.89 | 149.88 | 364.24 | 13.65 | 0.00 | 0.00 | 744.00 |
September | 198.35 | 86.60 | 111.75 | 224.10 | 40.29 | 0.00 | 0.00 | 720.00 |
October | 196.80 | 95.87 | 100.93 | 188.33 | 97.20 | 0.00 | 0.00 | 744.00 |
November | 92.68 | 27.08 | 65.60 | 45.17 | 169.72 | 0.00 | 0.00 | 720.00 |
December | 81.87 | 35.35 | 46.52 | 35.40 | 229.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.17 | 78.93 | 108.24 | 184.09 | 118.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 81.87 | 27.08 | 46.52 | 35.40 | 5.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 278.76 | 128.89 | 160.62 | 364.24 | 256.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.05 | 0.00 | 23.05 | 0.39 | 140.81 | 0.00 | 0.00 | 744.00 |
February | 31.54 | 0.00 | 31.54 | 1.42 | 145.27 | 0.00 | 0.00 | 672.00 |
March | 43.75 | 0.00 | 43.75 | 10.48 | 93.63 | 0.00 | 0.00 | 744.00 |
April | 52.64 | 0.21 | 52.43 | 26.43 | 61.58 | 0.00 | 0.00 | 720.00 |
May | 70.02 | 2.56 | 67.46 | 54.29 | 32.41 | 0.00 | 0.00 | 744.00 |
June | 73.86 | 3.92 | 69.94 | 77.43 | 13.77 | 0.00 | 0.00 | 720.00 |
July | 71.69 | 2.79 | 68.90 | 92.22 | 4.41 | 0.00 | 0.00 | 744.00 |
August | 63.40 | 0.84 | 62.57 | 83.01 | 8.90 | 0.00 | 0.00 | 744.00 |
September | 47.74 | 0.03 | 47.72 | 46.13 | 23.54 | 0.00 | 0.00 | 720.00 |
October | 41.29 | 0.00 | 41.29 | 25.49 | 53.46 | 0.00 | 0.00 | 744.00 |
November | 28.96 | 0.00 | 28.96 | 5.90 | 92.50 | 0.00 | 0.00 | 720.00 |
December | 20.10 | 0.00 | 20.10 | 0.33 | 127.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.43 | 0.87 | 46.56 | 35.53 | 66.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 20.10 | 0.00 | 20.10 | 0.33 | 4.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.86 | 3.92 | 69.94 | 92.22 | 145.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.05 | 36.56 | 52.48 | 40.63 | 249.89 | 0.00 | 0.00 | 744.00 |
February | 130.79 | 57.40 | 73.39 | 69.55 | 252.65 | 0.00 | 0.00 | 672.00 |
March | 194.29 | 90.05 | 104.24 | 148.08 | 163.05 | 0.00 | 0.00 | 744.00 |
April | 211.00 | 90.17 | 120.83 | 187.31 | 111.68 | 0.00 | 0.00 | 720.00 |
May | 246.46 | 93.68 | 152.79 | 252.27 | 62.35 | 0.00 | 0.00 | 744.00 |
June | 269.28 | 108.66 | 160.62 | 314.73 | 26.64 | 0.00 | 0.00 | 720.00 |
July | 251.94 | 94.66 | 157.28 | 324.28 | 8.40 | 0.00 | 0.00 | 744.00 |
August | 278.76 | 128.89 | 149.88 | 359.61 | 16.88 | 0.00 | 0.00 | 744.00 |
September | 198.35 | 86.60 | 111.75 | 222.51 | 43.27 | 0.00 | 0.00 | 720.00 |
October | 196.80 | 95.87 | 100.93 | 192.12 | 96.57 | 0.00 | 0.00 | 744.00 |
November | 92.68 | 27.08 | 65.60 | 48.67 | 166.30 | 0.00 | 0.00 | 720.00 |
December | 81.87 | 35.35 | 46.52 | 38.07 | 225.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.17 | 78.93 | 108.24 | 183.97 | 117.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 81.87 | 27.08 | 46.52 | 38.07 | 8.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 278.76 | 128.89 | 160.62 | 359.61 | 252.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 95.82 | 62.88 | 32.94 | 87.05 | 93.80 | 0.00 | 0.00 | 744.00 |
February | 126.85 | 84.33 | 42.53 | 107.33 | 112.94 | 0.00 | 0.00 | 672.00 |
March | 112.39 | 61.88 | 50.50 | 87.46 | 90.49 | 0.00 | 0.00 | 744.00 |
April | 89.42 | 36.17 | 53.25 | 59.00 | 69.54 | 0.00 | 0.00 | 720.00 |
May | 76.80 | 15.71 | 61.08 | 50.11 | 46.11 | 0.00 | 0.00 | 744.00 |
June | 72.51 | 11.16 | 61.35 | 61.03 | 25.07 | 0.00 | 0.00 | 720.00 |
July | 75.45 | 12.72 | 62.73 | 75.23 | 14.18 | 0.00 | 0.00 | 744.00 |
August | 101.06 | 37.27 | 63.79 | 99.29 | 18.54 | 0.00 | 0.00 | 744.00 |
September | 106.67 | 53.57 | 53.11 | 101.39 | 36.21 | 0.00 | 0.00 | 720.00 |
October | 150.80 | 94.59 | 56.21 | 151.23 | 63.37 | 0.00 | 0.00 | 744.00 |
November | 104.38 | 62.62 | 41.76 | 92.37 | 90.72 | 0.00 | 0.00 | 720.00 |
December | 103.51 | 73.51 | 30.00 | 94.37 | 104.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 101.18 | 50.36 | 50.82 | 88.78 | 63.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 72.51 | 11.16 | 30.00 | 50.11 | 14.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 150.80 | 94.59 | 63.79 | 151.23 | 112.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.44 | 0.00 | 18.44 | 0.14 | 118.29 | 0.00 | 0.00 | 744.00 |
February | 25.24 | 0.00 | 25.24 | 0.89 | 120.65 | 0.00 | 0.00 | 672.00 |
March | 35.00 | 0.00 | 35.00 | 8.06 | 76.98 | 0.00 | 0.00 | 744.00 |
April | 42.12 | 0.17 | 41.95 | 21.72 | 50.25 | 0.00 | 0.00 | 720.00 |
May | 56.02 | 2.04 | 53.98 | 45.56 | 25.68 | 0.00 | 0.00 | 744.00 |
June | 59.10 | 3.14 | 55.96 | 66.03 | 9.93 | 0.00 | 0.00 | 720.00 |
July | 57.36 | 2.23 | 55.13 | 77.96 | 2.76 | 0.00 | 0.00 | 744.00 |
August | 50.73 | 0.67 | 50.06 | 71.00 | 5.89 | 0.00 | 0.00 | 744.00 |
September | 38.20 | 0.02 | 38.18 | 39.27 | 17.80 | 0.00 | 0.00 | 720.00 |
October | 33.03 | 0.00 | 33.03 | 21.59 | 42.08 | 0.00 | 0.00 | 744.00 |
November | 23.17 | 0.00 | 23.17 | 4.29 | 77.97 | 0.00 | 0.00 | 720.00 |
December | 16.09 | 0.00 | 16.09 | 0.16 | 107.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 37.95 | 0.69 | 37.25 | 29.93 | 54.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 16.09 | 0.00 | 16.09 | 0.14 | 2.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.10 | 3.14 | 55.96 | 77.96 | 120.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.67 | 35.83 | 53.84 | 35.31 | 248.60 | 0.00 | 0.00 | 744.00 |
February | 139.21 | 64.83 | 74.38 | 70.06 | 247.66 | 0.00 | 0.00 | 672.00 |
March | 178.76 | 75.97 | 102.79 | 125.46 | 166.04 | 0.00 | 0.00 | 744.00 |
April | 214.00 | 93.93 | 120.07 | 185.55 | 108.62 | 0.00 | 0.00 | 720.00 |
May | 258.32 | 102.93 | 155.39 | 267.16 | 58.87 | 0.00 | 0.00 | 744.00 |
June | 239.87 | 86.87 | 153.00 | 283.51 | 21.74 | 0.00 | 0.00 | 720.00 |
July | 240.61 | 86.61 | 154.00 | 317.94 | 5.14 | 0.00 | 0.00 | 744.00 |
August | 271.45 | 122.46 | 148.99 | 354.32 | 12.71 | 0.00 | 0.00 | 744.00 |
September | 203.08 | 91.49 | 111.58 | 227.54 | 38.43 | 0.00 | 0.00 | 720.00 |
October | 183.45 | 83.04 | 100.41 | 168.48 | 94.33 | 0.00 | 0.00 | 744.00 |
November | 113.63 | 43.67 | 69.96 | 65.23 | 164.54 | 0.00 | 0.00 | 720.00 |
December | 88.84 | 41.93 | 46.92 | 39.23 | 224.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 185.37 | 77.55 | 107.82 | 179.07 | 115.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 88.84 | 35.83 | 46.92 | 35.31 | 5.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 271.45 | 122.46 | 155.39 | 354.32 | 248.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.80 | 78.61 | 41.18 | 108.01 | 123.75 | 0.00 | 0.00 | 744.00 |
February | 158.60 | 105.43 | 53.17 | 140.08 | 124.53 | 0.00 | 0.00 | 672.00 |
March | 140.51 | 77.37 | 63.14 | 116.11 | 88.80 | 0.00 | 0.00 | 744.00 |
April | 111.80 | 45.22 | 66.57 | 83.42 | 61.32 | 0.00 | 0.00 | 720.00 |
May | 96.01 | 19.65 | 76.37 | 77.01 | 33.50 | 0.00 | 0.00 | 744.00 |
June | 90.66 | 13.95 | 76.70 | 93.56 | 12.21 | 0.00 | 0.00 | 720.00 |
July | 94.33 | 15.91 | 78.42 | 113.91 | 2.81 | 0.00 | 0.00 | 744.00 |
August | 126.35 | 46.59 | 79.75 | 142.66 | 7.11 | 0.00 | 0.00 | 744.00 |
September | 133.37 | 66.97 | 66.40 | 141.09 | 21.31 | 0.00 | 0.00 | 720.00 |
October | 188.54 | 118.27 | 70.28 | 202.57 | 50.36 | 0.00 | 0.00 | 744.00 |
November | 130.51 | 78.29 | 52.21 | 126.14 | 84.67 | 0.00 | 0.00 | 720.00 |
December | 129.41 | 91.91 | 37.50 | 125.07 | 110.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.50 | 62.97 | 63.54 | 122.45 | 59.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 90.66 | 13.95 | 37.50 | 77.01 | 2.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.54 | 118.27 | 79.75 | 202.57 | 124.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.05 | 0.00 | 23.05 | 0.32 | 140.84 | 0.00 | 0.00 | 744.00 |
February | 31.54 | 0.00 | 31.54 | 1.28 | 145.44 | 0.00 | 0.00 | 672.00 |
March | 43.75 | 0.00 | 43.75 | 9.91 | 93.00 | 0.00 | 0.00 | 744.00 |
April | 52.64 | 0.21 | 52.43 | 25.65 | 61.19 | 0.00 | 0.00 | 720.00 |
May | 70.02 | 2.56 | 67.46 | 53.49 | 31.79 | 0.00 | 0.00 | 744.00 |
June | 73.86 | 3.92 | 69.94 | 78.12 | 12.85 | 0.00 | 0.00 | 720.00 |
July | 71.69 | 2.79 | 68.90 | 92.24 | 3.94 | 0.00 | 0.00 | 744.00 |
August | 63.40 | 0.84 | 62.57 | 82.60 | 8.19 | 0.00 | 0.00 | 744.00 |
September | 47.74 | 0.03 | 47.72 | 45.67 | 22.73 | 0.00 | 0.00 | 720.00 |
October | 41.29 | 0.00 | 41.29 | 24.93 | 52.28 | 0.00 | 0.00 | 744.00 |
November | 28.96 | 0.00 | 28.96 | 5.50 | 92.91 | 0.00 | 0.00 | 720.00 |
December | 20.10 | 0.00 | 20.10 | 0.26 | 127.40 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.43 | 0.87 | 46.56 | 35.23 | 65.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 20.10 | 0.00 | 20.10 | 0.26 | 3.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.86 | 3.92 | 69.94 | 92.24 | 145.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.67 | 35.83 | 53.84 | 36.37 | 244.28 | 0.00 | 0.00 | 744.00 |
February | 139.21 | 64.83 | 74.38 | 71.93 | 241.81 | 0.00 | 0.00 | 672.00 |
March | 178.76 | 75.97 | 102.79 | 128.84 | 162.82 | 0.00 | 0.00 | 744.00 |
April | 214.00 | 93.93 | 120.07 | 187.27 | 107.75 | 0.00 | 0.00 | 720.00 |
May | 258.32 | 102.93 | 155.39 | 265.99 | 60.04 | 0.00 | 0.00 | 744.00 |
June | 239.87 | 86.87 | 153.00 | 278.75 | 24.79 | 0.00 | 0.00 | 720.00 |
July | 240.61 | 86.61 | 154.00 | 311.11 | 7.59 | 0.00 | 0.00 | 744.00 |
August | 271.45 | 122.46 | 148.99 | 349.56 | 15.19 | 0.00 | 0.00 | 744.00 |
September | 203.08 | 91.49 | 111.58 | 226.50 | 40.60 | 0.00 | 0.00 | 720.00 |
October | 183.45 | 83.04 | 100.41 | 172.66 | 92.71 | 0.00 | 0.00 | 744.00 |
November | 113.63 | 43.67 | 69.96 | 68.09 | 160.57 | 0.00 | 0.00 | 720.00 |
December | 88.84 | 41.93 | 46.92 | 40.48 | 218.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 185.37 | 77.55 | 107.82 | 178.87 | 114.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 88.84 | 35.83 | 46.92 | 36.37 | 7.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 271.45 | 122.46 | 155.39 | 349.56 | 244.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.19 | 0.00 | 29.19 | 0.25 | 181.59 | 0.00 | 0.00 | 744.00 |
February | 39.94 | 0.00 | 39.94 | 1.43 | 187.55 | 0.00 | 0.00 | 672.00 |
March | 55.40 | 0.00 | 55.40 | 13.19 | 119.22 | 0.00 | 0.00 | 744.00 |
April | 66.67 | 0.27 | 66.40 | 36.41 | 76.89 | 0.00 | 0.00 | 720.00 |
May | 88.67 | 3.24 | 85.43 | 76.59 | 38.65 | 0.00 | 0.00 | 744.00 |
June | 93.54 | 4.96 | 88.58 | 107.00 | 15.81 | 0.00 | 0.00 | 720.00 |
July | 90.80 | 3.53 | 87.26 | 122.40 | 5.25 | 0.00 | 0.00 | 744.00 |
August | 80.29 | 1.06 | 79.23 | 109.07 | 11.13 | 0.00 | 0.00 | 744.00 |
September | 60.46 | 0.03 | 60.43 | 62.82 | 28.60 | 0.00 | 0.00 | 720.00 |
October | 52.29 | 0.00 | 52.29 | 34.56 | 66.57 | 0.00 | 0.00 | 744.00 |
November | 36.67 | 0.00 | 36.67 | 7.17 | 120.90 | 0.00 | 0.00 | 720.00 |
December | 25.46 | 0.00 | 25.46 | 0.24 | 167.50 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.07 | 1.10 | 58.97 | 47.91 | 84.40 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.46 | 0.00 | 25.46 | 0.24 | 5.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 93.54 | 4.96 | 88.58 | 122.40 | 187.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 10.76 | 0.00 | 10.76 | 0.09 | 66.94 | 0.00 | 0.00 | 744.00 |
February | 14.72 | 0.00 | 14.72 | 0.53 | 69.14 | 0.00 | 0.00 | 672.00 |
March | 20.42 | 0.00 | 20.42 | 4.86 | 43.95 | 0.00 | 0.00 | 744.00 |
April | 24.58 | 0.10 | 24.48 | 13.42 | 28.34 | 0.00 | 0.00 | 720.00 |
May | 32.69 | 1.19 | 31.49 | 28.23 | 14.25 | 0.00 | 0.00 | 744.00 |
June | 34.48 | 1.83 | 32.65 | 39.44 | 5.83 | 0.00 | 0.00 | 720.00 |
July | 33.47 | 1.30 | 32.17 | 45.12 | 1.94 | 0.00 | 0.00 | 744.00 |
August | 29.60 | 0.39 | 29.21 | 40.21 | 4.10 | 0.00 | 0.00 | 744.00 |
September | 22.29 | 0.01 | 22.28 | 23.16 | 10.54 | 0.00 | 0.00 | 720.00 |
October | 19.27 | 0.00 | 19.27 | 12.74 | 24.54 | 0.00 | 0.00 | 744.00 |
November | 13.52 | 0.00 | 13.52 | 2.64 | 44.57 | 0.00 | 0.00 | 720.00 |
December | 9.39 | 0.00 | 9.39 | 0.09 | 61.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 22.14 | 0.40 | 21.74 | 17.66 | 31.11 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 9.39 | 0.00 | 9.39 | 0.09 | 1.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 34.48 | 1.83 | 32.65 | 45.12 | 69.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 55.90 | 36.68 | 19.22 | 50.86 | 57.83 | 0.00 | 0.00 | 744.00 |
February | 74.00 | 49.19 | 24.81 | 66.21 | 58.21 | 0.00 | 0.00 | 672.00 |
March | 65.56 | 36.10 | 29.46 | 55.50 | 41.43 | 0.00 | 0.00 | 744.00 |
April | 52.16 | 21.10 | 31.06 | 40.84 | 28.19 | 0.00 | 0.00 | 720.00 |
May | 44.80 | 9.17 | 35.63 | 38.82 | 15.13 | 0.00 | 0.00 | 744.00 |
June | 42.30 | 6.51 | 35.79 | 45.47 | 6.17 | 0.00 | 0.00 | 720.00 |
July | 44.01 | 7.42 | 36.59 | 53.59 | 1.99 | 0.00 | 0.00 | 744.00 |
August | 58.95 | 21.74 | 37.21 | 67.09 | 4.20 | 0.00 | 0.00 | 744.00 |
September | 62.23 | 31.25 | 30.98 | 67.41 | 10.43 | 0.00 | 0.00 | 720.00 |
October | 87.97 | 55.18 | 32.79 | 96.78 | 23.36 | 0.00 | 0.00 | 744.00 |
November | 60.89 | 36.53 | 24.36 | 59.84 | 39.74 | 0.00 | 0.00 | 720.00 |
December | 60.38 | 42.88 | 17.50 | 58.88 | 52.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.03 | 29.38 | 29.65 | 58.43 | 28.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 42.30 | 6.51 | 17.50 | 38.82 | 1.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 87.97 | 55.18 | 37.21 | 96.78 | 58.21 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 151.72 | 99.56 | 52.16 | 138.04 | 156.96 | 0.00 | 0.00 | 744.00 |
February | 200.85 | 133.52 | 67.34 | 179.71 | 157.99 | 0.00 | 0.00 | 672.00 |
March | 177.95 | 97.99 | 79.96 | 150.63 | 112.45 | 0.00 | 0.00 | 744.00 |
April | 141.58 | 57.27 | 84.31 | 110.86 | 76.52 | 0.00 | 0.00 | 720.00 |
May | 121.60 | 24.88 | 96.72 | 105.36 | 41.07 | 0.00 | 0.00 | 744.00 |
June | 114.81 | 17.67 | 97.14 | 123.40 | 16.75 | 0.00 | 0.00 | 720.00 |
July | 119.46 | 20.15 | 99.32 | 145.45 | 5.40 | 0.00 | 0.00 | 744.00 |
August | 160.01 | 59.01 | 101.00 | 182.09 | 11.41 | 0.00 | 0.00 | 744.00 |
September | 168.90 | 84.81 | 84.09 | 182.97 | 28.31 | 0.00 | 0.00 | 720.00 |
October | 238.78 | 149.78 | 89.00 | 262.68 | 63.40 | 0.00 | 0.00 | 744.00 |
November | 165.28 | 99.15 | 66.12 | 162.41 | 107.87 | 0.00 | 0.00 | 720.00 |
December | 163.89 | 116.40 | 47.49 | 159.80 | 141.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 160.21 | 79.74 | 80.47 | 158.59 | 76.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.81 | 17.67 | 47.49 | 105.36 | 5.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 238.78 | 149.78 | 101.00 | 262.68 | 157.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.90 | 78.68 | 41.22 | 107.97 | 123.81 | 0.00 | 0.00 | 744.00 |
February | 158.73 | 105.51 | 53.21 | 140.38 | 124.75 | 0.00 | 0.00 | 672.00 |
March | 140.63 | 77.43 | 63.19 | 116.53 | 89.60 | 0.00 | 0.00 | 744.00 |
April | 111.89 | 45.26 | 66.63 | 83.95 | 61.80 | 0.00 | 0.00 | 720.00 |
May | 96.09 | 19.66 | 76.43 | 77.01 | 34.25 | 0.00 | 0.00 | 744.00 |
June | 90.73 | 13.96 | 76.77 | 92.70 | 12.66 | 0.00 | 0.00 | 720.00 |
July | 94.41 | 15.92 | 78.49 | 113.40 | 2.88 | 0.00 | 0.00 | 744.00 |
August | 126.45 | 46.63 | 79.82 | 142.65 | 7.16 | 0.00 | 0.00 | 744.00 |
September | 133.48 | 67.02 | 66.45 | 140.92 | 21.51 | 0.00 | 0.00 | 720.00 |
October | 188.70 | 118.36 | 70.33 | 202.27 | 50.78 | 0.00 | 0.00 | 744.00 |
November | 130.61 | 78.36 | 52.26 | 126.61 | 84.09 | 0.00 | 0.00 | 720.00 |
December | 129.52 | 91.98 | 37.53 | 125.34 | 110.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.61 | 63.02 | 63.59 | 122.46 | 59.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 90.73 | 13.96 | 37.53 | 77.01 | 2.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.70 | 118.36 | 79.82 | 202.27 | 124.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.12 | 36.59 | 52.53 | 38.49 | 253.03 | 0.00 | 0.00 | 744.00 |
February | 130.90 | 57.45 | 73.45 | 65.94 | 257.02 | 0.00 | 0.00 | 672.00 |
March | 194.45 | 90.12 | 104.33 | 143.02 | 165.20 | 0.00 | 0.00 | 744.00 |
April | 211.18 | 90.25 | 120.93 | 184.18 | 112.11 | 0.00 | 0.00 | 720.00 |
May | 246.67 | 93.75 | 152.91 | 251.42 | 61.27 | 0.00 | 0.00 | 744.00 |
June | 269.50 | 108.75 | 160.75 | 318.75 | 22.90 | 0.00 | 0.00 | 720.00 |
July | 252.15 | 94.74 | 157.41 | 329.56 | 5.30 | 0.00 | 0.00 | 744.00 |
August | 278.99 | 128.99 | 150.00 | 362.75 | 13.26 | 0.00 | 0.00 | 744.00 |
September | 198.51 | 86.67 | 111.84 | 222.55 | 40.07 | 0.00 | 0.00 | 720.00 |
October | 196.96 | 95.95 | 101.01 | 187.00 | 96.83 | 0.00 | 0.00 | 744.00 |
November | 92.75 | 27.10 | 65.66 | 45.13 | 168.68 | 0.00 | 0.00 | 720.00 |
December | 81.94 | 35.38 | 46.56 | 35.54 | 228.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.32 | 78.99 | 108.33 | 182.87 | 117.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 81.94 | 27.10 | 46.56 | 35.54 | 5.30 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 278.99 | 128.99 | 160.75 | 362.75 | 257.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.07 | 0.00 | 23.07 | 0.43 | 140.62 | 0.00 | 0.00 | 744.00 |
February | 31.57 | 0.00 | 31.57 | 1.46 | 145.22 | 0.00 | 0.00 | 672.00 |
March | 43.78 | 0.00 | 43.78 | 10.44 | 93.50 | 0.00 | 0.00 | 744.00 |
April | 52.69 | 0.21 | 52.47 | 25.86 | 61.68 | 0.00 | 0.00 | 720.00 |
May | 70.07 | 2.56 | 67.52 | 52.51 | 33.17 | 0.00 | 0.00 | 744.00 |
June | 73.92 | 3.92 | 70.00 | 75.61 | 14.70 | 0.00 | 0.00 | 720.00 |
July | 71.75 | 2.79 | 68.96 | 90.72 | 4.96 | 0.00 | 0.00 | 744.00 |
August | 63.45 | 0.84 | 62.62 | 82.06 | 9.40 | 0.00 | 0.00 | 744.00 |
September | 47.78 | 0.03 | 47.76 | 45.20 | 24.32 | 0.00 | 0.00 | 720.00 |
October | 41.32 | 0.00 | 41.32 | 25.16 | 53.56 | 0.00 | 0.00 | 744.00 |
November | 28.98 | 0.00 | 28.98 | 6.01 | 91.68 | 0.00 | 0.00 | 720.00 |
December | 20.12 | 0.00 | 20.12 | 0.38 | 126.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 0.87 | 46.60 | 34.89 | 66.16 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 20.12 | 0.00 | 20.12 | 0.38 | 4.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.92 | 3.92 | 70.00 | 90.72 | 145.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 89.12 | 36.59 | 52.53 | 40.68 | 249.85 | 0.00 | 0.00 | 744.00 |
February | 130.90 | 57.45 | 73.45 | 69.44 | 252.82 | 0.00 | 0.00 | 672.00 |
March | 194.45 | 90.12 | 104.33 | 147.37 | 162.74 | 0.00 | 0.00 | 744.00 |
April | 211.18 | 90.25 | 120.93 | 185.52 | 111.72 | 0.00 | 0.00 | 720.00 |
May | 246.67 | 93.75 | 152.91 | 248.42 | 63.54 | 0.00 | 0.00 | 744.00 |
June | 269.50 | 108.75 | 160.75 | 310.64 | 28.30 | 0.00 | 0.00 | 720.00 |
July | 252.15 | 94.74 | 157.41 | 321.15 | 9.36 | 0.00 | 0.00 | 744.00 |
August | 278.99 | 128.99 | 150.00 | 357.26 | 17.68 | 0.00 | 0.00 | 744.00 |
September | 198.51 | 86.67 | 111.84 | 220.15 | 44.41 | 0.00 | 0.00 | 720.00 |
October | 196.96 | 95.95 | 101.01 | 190.84 | 96.60 | 0.00 | 0.00 | 744.00 |
November | 92.75 | 27.10 | 65.66 | 48.91 | 165.14 | 0.00 | 0.00 | 720.00 |
December | 81.94 | 35.38 | 46.56 | 38.43 | 224.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.32 | 78.99 | 108.33 | 182.38 | 118.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 81.94 | 27.10 | 46.56 | 38.43 | 9.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 278.99 | 128.99 | 160.75 | 357.26 | 252.82 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 175.84 | 115.39 | 60.45 | 152.68 | 188.37 | 0.17 | 0.00 | 744.00 |
February | 232.79 | 154.75 | 78.04 | 198.69 | 190.08 | 0.00 | 0.00 | 672.00 |
March | 206.24 | 113.57 | 92.68 | 167.07 | 134.89 | 0.00 | 0.00 | 744.00 |
April | 164.09 | 66.38 | 97.72 | 121.77 | 91.59 | 0.00 | 0.00 | 720.00 |
May | 140.93 | 28.84 | 112.09 | 114.35 | 49.27 | 0.00 | 0.00 | 744.00 |
June | 133.06 | 20.48 | 112.59 | 139.59 | 17.11 | 0.00 | 0.00 | 720.00 |
July | 138.46 | 23.35 | 115.11 | 170.37 | 3.50 | 0.00 | 0.00 | 744.00 |
August | 185.45 | 68.39 | 117.06 | 212.64 | 9.61 | 0.00 | 0.00 | 744.00 |
September | 195.76 | 98.30 | 97.46 | 206.84 | 31.21 | 0.00 | 0.00 | 720.00 |
October | 276.74 | 173.59 | 103.15 | 293.79 | 76.02 | 0.00 | 0.00 | 744.00 |
November | 191.56 | 114.92 | 76.64 | 180.03 | 129.85 | 0.00 | 0.00 | 720.00 |
December | 189.95 | 134.90 | 55.04 | 177.56 | 168.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 185.68 | 92.42 | 93.26 | 177.95 | 90.29 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 133.06 | 20.48 | 55.04 | 114.35 | 3.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 276.74 | 173.59 | 117.06 | 293.79 | 190.08 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.46 | 0.00 | 161.46 | 0.02 | 1243.08 | 0.00 | 0.00 | 744.00 |
February | 220.95 | 0.00 | 220.95 | 1.27 | 1263.61 | 0.00 | 0.00 | 672.00 |
March | 306.47 | 0.01 | 306.47 | 35.75 | 876.64 | 0.00 | 0.00 | 744.00 |
April | 368.80 | 1.50 | 367.30 | 129.02 | 614.89 | 0.00 | 0.00 | 720.00 |
May | 490.49 | 17.90 | 472.59 | 305.73 | 346.42 | 0.00 | 0.00 | 744.00 |
June | 517.45 | 27.46 | 489.99 | 480.39 | 176.30 | 0.00 | 0.00 | 720.00 |
July | 502.25 | 19.55 | 482.70 | 565.93 | 98.03 | 0.00 | 0.00 | 744.00 |
August | 444.16 | 5.86 | 438.30 | 504.52 | 131.78 | 0.00 | 0.00 | 744.00 |
September | 334.47 | 0.19 | 334.28 | 272.40 | 272.52 | 0.00 | 0.00 | 720.00 |
October | 289.22 | 0.00 | 289.22 | 130.26 | 530.37 | 0.00 | 0.00 | 744.00 |
November | 202.86 | 0.00 | 202.86 | 16.05 | 897.03 | 0.00 | 0.00 | 720.00 |
December | 140.84 | 0.00 | 140.84 | 0.12 | 1160.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 332.26 | 6.08 | 326.19 | 204.89 | 630.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 140.84 | 0.00 | 140.84 | 0.02 | 98.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 517.45 | 27.46 | 489.99 | 565.93 | 1263.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.46 | 0.00 | 161.46 | 0.00 | 1308.31 | 0.00 | 0.00 | 744.00 |
February | 220.95 | 0.00 | 220.95 | 0.46 | 1327.72 | 0.00 | 0.00 | 672.00 |
March | 306.47 | 0.01 | 306.47 | 28.32 | 929.41 | 0.00 | 0.00 | 744.00 |
April | 368.80 | 1.50 | 367.30 | 115.29 | 653.59 | 0.00 | 0.00 | 720.00 |
May | 490.49 | 17.90 | 472.59 | 284.95 | 371.65 | 0.00 | 0.00 | 744.00 |
June | 517.45 | 27.46 | 489.99 | 457.88 | 194.20 | 0.00 | 0.00 | 720.00 |
July | 502.25 | 19.55 | 482.70 | 544.27 | 113.25 | 0.00 | 0.00 | 744.00 |
August | 444.16 | 5.86 | 438.30 | 484.44 | 148.41 | 0.00 | 0.00 | 744.00 |
September | 334.47 | 0.19 | 334.28 | 256.38 | 296.57 | 0.00 | 0.00 | 720.00 |
October | 289.22 | 0.00 | 289.22 | 118.21 | 563.78 | 0.00 | 0.00 | 744.00 |
November | 202.86 | 0.00 | 202.86 | 12.53 | 950.88 | 0.00 | 0.00 | 720.00 |
December | 140.84 | 0.00 | 140.84 | 0.03 | 1226.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 332.26 | 6.08 | 326.19 | 193.27 | 669.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 140.84 | 0.00 | 140.84 | 0.00 | 113.25 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 517.45 | 27.46 | 489.99 | 544.27 | 1327.72 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.07 | 0.00 | 23.07 | 0.01 | 184.29 | 0.00 | 0.00 | 744.00 |
February | 31.57 | 0.00 | 31.57 | 0.21 | 187.73 | 0.00 | 0.00 | 672.00 |
March | 43.78 | 0.00 | 43.78 | 4.45 | 132.19 | 0.00 | 0.00 | 744.00 |
April | 52.69 | 0.21 | 52.47 | 18.87 | 93.80 | 0.00 | 0.00 | 720.00 |
May | 70.07 | 2.56 | 67.52 | 46.47 | 55.29 | 0.00 | 0.00 | 744.00 |
June | 73.92 | 3.92 | 70.00 | 75.23 | 29.95 | 0.00 | 0.00 | 720.00 |
July | 71.75 | 2.79 | 68.96 | 90.11 | 17.08 | 0.00 | 0.00 | 744.00 |
August | 63.45 | 0.84 | 62.62 | 78.96 | 22.50 | 0.00 | 0.00 | 744.00 |
September | 47.78 | 0.03 | 47.76 | 43.31 | 43.01 | 0.00 | 0.00 | 720.00 |
October | 41.32 | 0.00 | 41.32 | 19.15 | 80.68 | 0.00 | 0.00 | 744.00 |
November | 28.98 | 0.00 | 28.98 | 2.33 | 134.69 | 0.00 | 0.00 | 720.00 |
December | 20.12 | 0.00 | 20.12 | 0.02 | 173.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 47.47 | 0.87 | 46.60 | 31.81 | 95.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 20.12 | 0.00 | 20.12 | 0.01 | 17.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.92 | 3.92 | 70.00 | 90.11 | 187.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 179.47 | 71.72 | 107.76 | 64.11 | 644.32 | 0.00 | 0.00 | 744.00 |
February | 278.62 | 129.75 | 148.87 | 129.04 | 628.81 | 0.00 | 0.00 | 672.00 |
March | 357.79 | 152.06 | 205.73 | 229.86 | 467.83 | 0.00 | 0.00 | 744.00 |
April | 428.32 | 188.01 | 240.31 | 343.41 | 334.25 | 0.00 | 0.00 | 720.00 |
May | 517.04 | 206.02 | 311.02 | 503.68 | 209.13 | 0.00 | 0.00 | 744.00 |
June | 480.10 | 173.87 | 306.23 | 546.35 | 116.51 | 0.00 | 0.00 | 720.00 |
July | 481.57 | 173.35 | 308.23 | 613.18 | 66.54 | 0.00 | 0.00 | 744.00 |
August | 543.30 | 245.11 | 298.19 | 684.55 | 85.66 | 0.00 | 0.00 | 744.00 |
September | 406.46 | 183.12 | 223.33 | 441.82 | 157.59 | 0.00 | 0.00 | 720.00 |
October | 367.18 | 166.21 | 200.97 | 319.66 | 288.89 | 0.00 | 0.00 | 744.00 |
November | 227.43 | 87.40 | 140.02 | 114.77 | 465.03 | 0.00 | 0.00 | 720.00 |
December | 177.82 | 83.92 | 93.90 | 70.57 | 595.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 371.01 | 155.22 | 215.79 | 339.88 | 336.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 177.82 | 71.72 | 93.90 | 64.11 | 66.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 543.30 | 245.11 | 311.02 | 684.55 | 644.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.90 | 78.68 | 41.22 | 102.40 | 158.98 | 0.00 | 0.00 | 744.00 |
February | 158.73 | 105.51 | 53.21 | 133.48 | 156.26 | 0.00 | 0.00 | 672.00 |
March | 140.63 | 77.43 | 63.19 | 109.49 | 123.11 | 0.00 | 0.00 | 744.00 |
April | 111.89 | 45.26 | 66.63 | 76.30 | 93.27 | 0.00 | 0.00 | 720.00 |
May | 96.09 | 19.66 | 76.43 | 69.73 | 58.84 | 0.00 | 0.00 | 744.00 |
June | 90.73 | 13.96 | 76.77 | 88.01 | 32.34 | 0.00 | 0.00 | 720.00 |
July | 94.41 | 15.92 | 78.49 | 107.72 | 18.11 | 0.00 | 0.00 | 744.00 |
August | 126.45 | 46.63 | 79.82 | 136.43 | 23.32 | 0.00 | 0.00 | 744.00 |
September | 133.48 | 67.02 | 66.45 | 137.98 | 43.06 | 0.00 | 0.00 | 720.00 |
October | 188.70 | 118.36 | 70.33 | 197.90 | 77.03 | 0.00 | 0.00 | 744.00 |
November | 130.61 | 78.36 | 52.26 | 119.53 | 118.36 | 0.00 | 0.00 | 720.00 |
December | 129.52 | 91.98 | 37.53 | 118.94 | 145.66 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 126.61 | 63.02 | 63.59 | 116.47 | 86.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 90.73 | 13.96 | 37.53 | 69.73 | 18.11 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.70 | 118.36 | 79.82 | 197.90 | 158.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.21 | 0.00 | 29.21 | 0.06 | 197.03 | 0.00 | 0.00 | 744.00 |
February | 39.98 | 0.00 | 39.98 | 0.64 | 201.94 | 0.00 | 0.00 | 672.00 |
March | 55.45 | 0.00 | 55.45 | 8.11 | 139.11 | 0.00 | 0.00 | 744.00 |
April | 66.73 | 0.27 | 66.45 | 25.75 | 97.81 | 0.00 | 0.00 | 720.00 |
May | 88.74 | 3.24 | 85.50 | 58.99 | 54.69 | 0.00 | 0.00 | 744.00 |
June | 93.62 | 4.97 | 88.65 | 90.20 | 26.30 | 0.00 | 0.00 | 720.00 |
July | 90.87 | 3.54 | 87.33 | 104.96 | 13.32 | 0.00 | 0.00 | 744.00 |
August | 80.36 | 1.06 | 79.30 | 92.65 | 19.42 | 0.00 | 0.00 | 744.00 |
September | 60.51 | 0.03 | 60.48 | 50.45 | 42.74 | 0.00 | 0.00 | 720.00 |
October | 52.33 | 0.00 | 52.33 | 24.34 | 86.61 | 0.00 | 0.00 | 744.00 |
November | 36.70 | 0.00 | 36.70 | 3.42 | 143.04 | 0.00 | 0.00 | 720.00 |
December | 25.48 | 0.00 | 25.48 | 0.06 | 183.36 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 60.11 | 1.10 | 59.02 | 38.57 | 99.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.48 | 0.00 | 25.48 | 0.06 | 13.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 93.62 | 4.97 | 88.65 | 104.96 | 201.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.14 | 0.00 | 26.14 | 0.05 | 176.28 | 0.00 | 0.00 | 744.00 |
February | 35.77 | 0.00 | 35.77 | 0.57 | 180.67 | 0.00 | 0.00 | 672.00 |
March | 49.61 | 0.00 | 49.61 | 7.26 | 124.46 | 0.00 | 0.00 | 744.00 |
April | 59.70 | 0.24 | 59.46 | 23.04 | 87.51 | 0.00 | 0.00 | 720.00 |
May | 79.40 | 2.90 | 76.50 | 52.77 | 48.93 | 0.00 | 0.00 | 744.00 |
June | 83.76 | 4.45 | 79.32 | 80.70 | 23.53 | 0.00 | 0.00 | 720.00 |
July | 81.30 | 3.16 | 78.14 | 93.90 | 11.92 | 0.00 | 0.00 | 744.00 |
August | 71.90 | 0.95 | 70.95 | 82.90 | 17.38 | 0.00 | 0.00 | 744.00 |
September | 54.14 | 0.03 | 54.11 | 45.14 | 38.24 | 0.00 | 0.00 | 720.00 |
October | 46.82 | 0.00 | 46.82 | 21.78 | 77.49 | 0.00 | 0.00 | 744.00 |
November | 32.84 | 0.00 | 32.84 | 3.06 | 127.98 | 0.00 | 0.00 | 720.00 |
December | 22.80 | 0.00 | 22.80 | 0.06 | 164.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.79 | 0.98 | 52.80 | 34.51 | 89.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 22.80 | 0.00 | 22.80 | 0.05 | 11.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 83.76 | 4.45 | 79.32 | 93.90 | 180.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 447.61 | 293.73 | 153.88 | 394.05 | 498.36 | 0.00 | 0.00 | 744.00 |
February | 592.58 | 393.92 | 198.66 | 514.00 | 496.58 | 0.00 | 0.00 | 672.00 |
March | 525.01 | 289.09 | 235.92 | 421.69 | 384.17 | 0.00 | 0.00 | 744.00 |
April | 417.71 | 168.97 | 248.74 | 293.06 | 286.22 | 0.00 | 0.00 | 720.00 |
May | 358.74 | 73.40 | 285.34 | 262.48 | 172.63 | 0.00 | 0.00 | 744.00 |
June | 338.72 | 52.13 | 286.59 | 316.75 | 83.37 | 0.00 | 0.00 | 720.00 |
July | 352.46 | 59.44 | 293.02 | 378.77 | 40.96 | 0.00 | 0.00 | 744.00 |
August | 472.08 | 174.09 | 297.99 | 489.87 | 59.12 | 0.00 | 0.00 | 744.00 |
September | 498.31 | 250.22 | 248.09 | 501.70 | 124.79 | 0.00 | 0.00 | 720.00 |
October | 704.46 | 441.88 | 262.58 | 735.92 | 240.39 | 0.00 | 0.00 | 744.00 |
November | 487.62 | 292.53 | 195.09 | 453.49 | 370.77 | 0.00 | 0.00 | 720.00 |
December | 483.53 | 343.41 | 140.12 | 455.82 | 452.85 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 472.67 | 235.26 | 237.40 | 434.63 | 266.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 338.72 | 52.13 | 140.12 | 262.48 | 40.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 704.46 | 441.88 | 297.99 | 735.92 | 498.36 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162619E+10 | 0.106714E+10 | 0.559054E+09 | 0.144204E+10 | 0.167085E+10 |
February | 0.194451E+10 | 0.129262E+10 | 0.651898E+09 | 0.169109E+10 | 0.152152E+10 |
March | 0.190736E+10 | 0.105026E+10 | 0.857099E+09 | 0.154357E+10 | 0.126061E+10 |
April | 0.146859E+10 | 0.594063E+09 | 0.874529E+09 | 0.104667E+10 | 0.890516E+09 |
May | 0.130332E+10 | 0.266668E+09 | 0.103665E+10 | 0.967209E+09 | 0.570655E+09 |
June | 0.119089E+10 | 0.183270E+09 | 0.100762E+10 | 0.110714E+10 | 0.276312E+09 |
July | 0.128048E+10 | 0.215929E+09 | 0.106455E+10 | 0.136662E+10 | 0.138643E+09 |
August | 0.171508E+10 | 0.632490E+09 | 0.108259E+10 | 0.174034E+10 | 0.213474E+09 |
September | 0.175199E+10 | 0.879741E+09 | 0.872245E+09 | 0.173674E+10 | 0.425740E+09 |
October | 0.255933E+10 | 0.160538E+10 | 0.953957E+09 | 0.264221E+10 | 0.847136E+09 |
November | 0.171439E+10 | 0.102849E+10 | 0.685893E+09 | 0.160544E+10 | 0.119473E+10 |
December | 0.175666E+10 | 0.124760E+10 | 0.509057E+09 | 0.165731E+10 | 0.153270E+10 |
Annual Sum or Average | 0.202188E+11 | 0.100636E+11 | 0.101551E+11 | 0.185464E+11 | 0.105429E+11 |
Minimum of Months | 0.119089E+10 | 0.183270E+09 | 0.509057E+09 | 0.967209E+09 | 0.138643E+09 |
Maximum of Months | 0.255933E+10 | 0.160538E+10 | 0.108259E+10 | 0.264221E+10 | 0.167085E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.457924E+10 | 0.300499E+10 | 0.157426E+10 | 0.398500E+10 | 0.504274E+10 |
February | 0.547562E+10 | 0.363992E+10 | 0.183570E+10 | 0.467449E+10 | 0.458271E+10 |
March | 0.537100E+10 | 0.295746E+10 | 0.241353E+10 | 0.426731E+10 | 0.383895E+10 |
April | 0.413546E+10 | 0.167284E+10 | 0.246262E+10 | 0.289180E+10 | 0.269910E+10 |
May | 0.367006E+10 | 0.750920E+09 | 0.291914E+10 | 0.269613E+10 | 0.168194E+10 |
June | 0.335345E+10 | 0.516075E+09 | 0.283738E+10 | 0.309747E+10 | 0.826469E+09 |
July | 0.360574E+10 | 0.608043E+09 | 0.299770E+10 | 0.381369E+10 | 0.443949E+09 |
August | 0.482956E+10 | 0.178105E+10 | 0.304851E+10 | 0.487686E+10 | 0.658874E+09 |
September | 0.493348E+10 | 0.247729E+10 | 0.245619E+10 | 0.487440E+10 | 0.126971E+10 |
October | 0.720691E+10 | 0.452063E+10 | 0.268628E+10 | 0.739106E+10 | 0.251738E+10 |
November | 0.482760E+10 | 0.289617E+10 | 0.193143E+10 | 0.444077E+10 | 0.362650E+10 |
December | 0.494664E+10 | 0.351317E+10 | 0.143347E+10 | 0.457887E+10 | 0.465962E+10 |
Annual Sum or Average | 0.569348E+11 | 0.283386E+11 | 0.285962E+11 | 0.515879E+11 | 0.318479E+11 |
Minimum of Months | 0.335345E+10 | 0.516075E+09 | 0.143347E+10 | 0.269613E+10 | 0.443949E+09 |
Maximum of Months | 0.720691E+10 | 0.452063E+10 | 0.304851E+10 | 0.739106E+10 | 0.504274E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.594870E+10 | 0.390365E+10 | 0.204505E+10 | 0.521668E+10 | 0.700866E+10 |
February | 0.711314E+10 | 0.472846E+10 | 0.238468E+10 | 0.614512E+10 | 0.630057E+10 |
March | 0.697723E+10 | 0.384192E+10 | 0.313532E+10 | 0.561667E+10 | 0.527766E+10 |
April | 0.537220E+10 | 0.217312E+10 | 0.319908E+10 | 0.379480E+10 | 0.373198E+10 |
May | 0.476761E+10 | 0.975488E+09 | 0.379212E+10 | 0.354537E+10 | 0.231914E+10 |
June | 0.435633E+10 | 0.670411E+09 | 0.368592E+10 | 0.411661E+10 | 0.112413E+10 |
July | 0.468407E+10 | 0.789882E+09 | 0.389418E+10 | 0.509845E+10 | 0.591663E+09 |
August | 0.627388E+10 | 0.231369E+10 | 0.396019E+10 | 0.653783E+10 | 0.853663E+09 |
September | 0.640887E+10 | 0.321815E+10 | 0.319072E+10 | 0.648849E+10 | 0.168566E+10 |
October | 0.936219E+10 | 0.587256E+10 | 0.348963E+10 | 0.983389E+10 | 0.333618E+10 |
November | 0.627133E+10 | 0.376229E+10 | 0.250904E+10 | 0.584469E+10 | 0.498732E+10 |
December | 0.642597E+10 | 0.456381E+10 | 0.186216E+10 | 0.602016E+10 | 0.644633E+10 |
Annual Sum or Average | 0.739615E+11 | 0.368134E+11 | 0.371481E+11 | 0.682588E+11 | 0.436630E+11 |
Minimum of Months | 0.435633E+10 | 0.670411E+09 | 0.186216E+10 | 0.354537E+10 | 0.591663E+09 |
Maximum of Months | 0.936219E+10 | 0.587256E+10 | 0.396019E+10 | 0.983389E+10 | 0.700866E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320870E+09 | 0.210561E+09 | 0.110309E+09 | 0.290086E+09 | 0.331905E+09 |
February | 0.383680E+09 | 0.255051E+09 | 0.128629E+09 | 0.340608E+09 | 0.301956E+09 |
March | 0.376349E+09 | 0.207231E+09 | 0.169118E+09 | 0.313192E+09 | 0.239951E+09 |
April | 0.289774E+09 | 0.117217E+09 | 0.172557E+09 | 0.218840E+09 | 0.159944E+09 |
May | 0.257163E+09 | 52617425.58 | 0.204546E+09 | 0.209230E+09 | 90866442.34 |
June | 0.234979E+09 | 36161720.47 | 0.198817E+09 | 0.242554E+09 | 32692671.91 |
July | 0.252657E+09 | 42605912.80 | 0.210051E+09 | 0.305297E+09 | 7931630.54 |
August | 0.338410E+09 | 0.124799E+09 | 0.213611E+09 | 0.382929E+09 | 19713830.95 |
September | 0.345692E+09 | 0.173585E+09 | 0.172106E+09 | 0.367039E+09 | 55933707.02 |
October | 0.504993E+09 | 0.316763E+09 | 0.188229E+09 | 0.544072E+09 | 0.136339E+09 |
November | 0.338273E+09 | 0.202937E+09 | 0.135336E+09 | 0.328864E+09 | 0.219231E+09 |
December | 0.346614E+09 | 0.246170E+09 | 0.100444E+09 | 0.336141E+09 | 0.296507E+09 |
Annual Sum or Average | 0.398945E+10 | 0.198570E+10 | 0.200375E+10 | 0.387885E+10 | 0.189297E+10 |
Minimum of Months | 0.234979E+09 | 36161720.47 | 0.100444E+09 | 0.209230E+09 | 7931630.54 |
Maximum of Months | 0.504993E+09 | 0.316763E+09 | 0.213611E+09 | 0.544072E+09 | 0.331905E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238500E+09 | 97925523.83 | 0.140574E+09 | 0.103137E+09 | 0.678031E+09 |
February | 0.316408E+09 | 0.138864E+09 | 0.177545E+09 | 0.160281E+09 | 0.621541E+09 |
March | 0.520380E+09 | 0.241180E+09 | 0.279200E+09 | 0.385861E+09 | 0.443053E+09 |
April | 0.546919E+09 | 0.233732E+09 | 0.313187E+09 | 0.481748E+09 | 0.290914E+09 |
May | 0.660131E+09 | 0.250900E+09 | 0.409231E+09 | 0.681186E+09 | 0.163190E+09 |
June | 0.697972E+09 | 0.281637E+09 | 0.416334E+09 | 0.832688E+09 | 59310846.82 |
July | 0.674794E+09 | 0.253543E+09 | 0.421251E+09 | 0.887656E+09 | 14637031.02 |
August | 0.746637E+09 | 0.345207E+09 | 0.401429E+09 | 0.975578E+09 | 36551672.39 |
September | 0.514123E+09 | 0.224471E+09 | 0.289652E+09 | 0.580857E+09 | 0.104421E+09 |
October | 0.527097E+09 | 0.256769E+09 | 0.270327E+09 | 0.504410E+09 | 0.260328E+09 |
November | 0.240219E+09 | 70180947.51 | 0.170039E+09 | 0.117078E+09 | 0.439903E+09 |
December | 0.219280E+09 | 94672763.34 | 0.124607E+09 | 94826444.71 | 0.615345E+09 |
Annual Sum or Average | 0.590246E+10 | 0.248908E+10 | 0.341338E+10 | 0.580531E+10 | 0.372723E+10 |
Minimum of Months | 0.219280E+09 | 70180947.51 | 0.124607E+09 | 94826444.71 | 14637031.02 |
Maximum of Months | 0.746637E+09 | 0.345207E+09 | 0.421251E+09 | 0.975578E+09 | 0.678031E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61730780.89 | 0.00 | 61730780.89 | 1054223.62 | 0.377157E+09 |
February | 76300861.09 | 0.00 | 76300861.09 | 3445237.85 | 0.351434E+09 |
March | 0.117174E+09 | 2329.53 | 0.117172E+09 | 28078185.23 | 0.250774E+09 |
April | 0.136455E+09 | 556193.62 | 0.135898E+09 | 68497538.15 | 0.159607E+09 |
May | 0.187529E+09 | 6843609.71 | 0.180685E+09 | 0.145397E+09 | 86809241.92 |
June | 0.191453E+09 | 10160814.05 | 0.181293E+09 | 0.200689E+09 | 35699302.03 |
July | 0.192023E+09 | 7474350.78 | 0.184549E+09 | 0.247009E+09 | 11810248.26 |
August | 0.169816E+09 | 2241668.73 | 0.167574E+09 | 0.222343E+09 | 23846960.13 |
September | 0.123752E+09 | 70321.09 | 0.123681E+09 | 0.119556E+09 | 61014889.00 |
October | 0.110579E+09 | 0.00 | 0.110579E+09 | 68262477.90 | 0.143192E+09 |
November | 75058300.98 | 0.00 | 75058300.98 | 15284785.77 | 0.239754E+09 |
December | 53845644.44 | 0.00 | 53845644.44 | 897088.15 | 0.340971E+09 |
Annual Sum or Average | 0.149572E+10 | 27349287.52 | 0.146837E+10 | 0.112051E+10 | 0.208207E+10 |
Minimum of Months | 53845644.44 | 0.00 | 53845644.44 | 897088.15 | 11810248.26 |
Maximum of Months | 0.192023E+09 | 10160814.05 | 0.184549E+09 | 0.247009E+09 | 0.377157E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238500E+09 | 97925523.83 | 0.140574E+09 | 0.108831E+09 | 0.669314E+09 |
February | 0.316408E+09 | 0.138864E+09 | 0.177545E+09 | 0.168247E+09 | 0.611208E+09 |
March | 0.520380E+09 | 0.241180E+09 | 0.279200E+09 | 0.396628E+09 | 0.436708E+09 |
April | 0.546919E+09 | 0.233732E+09 | 0.313187E+09 | 0.485497E+09 | 0.289485E+09 |
May | 0.660131E+09 | 0.250900E+09 | 0.409231E+09 | 0.675679E+09 | 0.167010E+09 |
June | 0.697972E+09 | 0.281637E+09 | 0.416334E+09 | 0.815768E+09 | 69062276.79 |
July | 0.674794E+09 | 0.253543E+09 | 0.421251E+09 | 0.868553E+09 | 22494029.87 |
August | 0.746637E+09 | 0.345207E+09 | 0.401429E+09 | 0.963182E+09 | 45217186.39 |
September | 0.514123E+09 | 0.224471E+09 | 0.289652E+09 | 0.576749E+09 | 0.112153E+09 |
October | 0.527097E+09 | 0.256769E+09 | 0.270327E+09 | 0.514579E+09 | 0.258645E+09 |
November | 0.240219E+09 | 70180947.51 | 0.170039E+09 | 0.126147E+09 | 0.431053E+09 |
December | 0.219280E+09 | 94672763.34 | 0.124607E+09 | 0.101970E+09 | 0.603985E+09 |
Annual Sum or Average | 0.590246E+10 | 0.248908E+10 | 0.341338E+10 | 0.580183E+10 | 0.371633E+10 |
Minimum of Months | 0.219280E+09 | 70180947.51 | 0.124607E+09 | 0.101970E+09 | 22494029.87 |
Maximum of Months | 0.746637E+09 | 0.345207E+09 | 0.421251E+09 | 0.963182E+09 | 0.669314E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.256645E+09 | 0.168415E+09 | 88229912.29 | 0.233157E+09 | 0.251228E+09 |
February | 0.306883E+09 | 0.204001E+09 | 0.102882E+09 | 0.259653E+09 | 0.273215E+09 |
March | 0.301019E+09 | 0.165752E+09 | 0.135267E+09 | 0.234245E+09 | 0.242371E+09 |
April | 0.231773E+09 | 93755041.77 | 0.138018E+09 | 0.152935E+09 | 0.180256E+09 |
May | 0.205690E+09 | 42085570.78 | 0.163604E+09 | 0.134211E+09 | 0.123501E+09 |
June | 0.187945E+09 | 28923624.25 | 0.159022E+09 | 0.158190E+09 | 64971821.88 |
July | 0.202085E+09 | 34077953.05 | 0.168007E+09 | 0.201500E+09 | 37971736.72 |
August | 0.270674E+09 | 99819567.05 | 0.170855E+09 | 0.265950E+09 | 49662354.21 |
September | 0.276498E+09 | 0.138841E+09 | 0.137658E+09 | 0.262810E+09 | 93843547.74 |
October | 0.403914E+09 | 0.253360E+09 | 0.150554E+09 | 0.405057E+09 | 0.169725E+09 |
November | 0.270565E+09 | 0.162317E+09 | 0.108248E+09 | 0.239419E+09 | 0.235136E+09 |
December | 0.277236E+09 | 0.196897E+09 | 80339342.33 | 0.252764E+09 | 0.280916E+09 |
Annual Sum or Average | 0.319093E+10 | 0.158824E+10 | 0.160268E+10 | 0.279989E+10 | 0.200280E+10 |
Minimum of Months | 0.187945E+09 | 28923624.25 | 80339342.33 | 0.134211E+09 | 37971736.72 |
Maximum of Months | 0.403914E+09 | 0.253360E+09 | 0.170855E+09 | 0.405057E+09 | 0.280916E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49391170.92 | 0.00 | 49391170.92 | 385938.49 | 0.316837E+09 |
February | 61048780.16 | 0.00 | 61048780.16 | 2162586.83 | 0.291888E+09 |
March | 93751937.54 | 1863.87 | 93750073.66 | 21583953.55 | 0.206183E+09 |
April | 0.109178E+09 | 445013.88 | 0.108733E+09 | 56301044.97 | 0.130259E+09 |
May | 0.150043E+09 | 5475613.50 | 0.144567E+09 | 0.122028E+09 | 68793610.14 |
June | 0.153183E+09 | 8129728.74 | 0.145053E+09 | 0.171152E+09 | 25746022.06 |
July | 0.153639E+09 | 5980273.24 | 0.147659E+09 | 0.208800E+09 | 7386789.98 |
August | 0.135871E+09 | 1793572.70 | 0.134077E+09 | 0.190174E+09 | 15774202.08 |
September | 99014499.97 | 56264.33 | 98958235.64 | 0.101791E+09 | 46129648.29 |
October | 88474560.91 | 0.00 | 88474560.91 | 57820928.65 | 0.112714E+09 |
November | 60054600.30 | 0.00 | 60054600.30 | 11130113.32 | 0.202107E+09 |
December | 43082225.59 | 0.00 | 43082225.59 | 415290.52 | 0.287187E+09 |
Annual Sum or Average | 0.119673E+10 | 21882330.26 | 0.117485E+10 | 0.943746E+09 | 0.171100E+10 |
Minimum of Months | 43082225.59 | 0.00 | 43082225.59 | 385938.49 | 7386789.98 |
Maximum of Months | 0.153639E+09 | 8129728.74 | 0.147659E+09 | 0.208800E+09 | 0.316837E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240168E+09 | 95969669.36 | 0.144198E+09 | 94586277.23 | 0.665845E+09 |
February | 0.336766E+09 | 0.156828E+09 | 0.179938E+09 | 0.169490E+09 | 0.599151E+09 |
March | 0.478787E+09 | 0.203481E+09 | 0.275306E+09 | 0.336044E+09 | 0.444714E+09 |
April | 0.554692E+09 | 0.243479E+09 | 0.311214E+09 | 0.480938E+09 | 0.281539E+09 |
May | 0.691897E+09 | 0.275693E+09 | 0.416204E+09 | 0.715554E+09 | 0.157670E+09 |
June | 0.621750E+09 | 0.225167E+09 | 0.396583E+09 | 0.734862E+09 | 56351723.29 |
July | 0.644437E+09 | 0.231970E+09 | 0.412467E+09 | 0.851557E+09 | 13756344.46 |
August | 0.727047E+09 | 0.328005E+09 | 0.399042E+09 | 0.949022E+09 | 34029976.49 |
September | 0.526373E+09 | 0.237150E+09 | 0.289223E+09 | 0.589772E+09 | 99599138.25 |
October | 0.491360E+09 | 0.222425E+09 | 0.268935E+09 | 0.451256E+09 | 0.252642E+09 |
November | 0.294523E+09 | 0.113190E+09 | 0.181333E+09 | 0.169088E+09 | 0.426493E+09 |
December | 0.237958E+09 | 0.112299E+09 | 0.125659E+09 | 0.105087E+09 | 0.600451E+09 |
Annual Sum or Average | 0.584576E+10 | 0.244566E+10 | 0.340010E+10 | 0.564726E+10 | 0.363224E+10 |
Minimum of Months | 0.237958E+09 | 95969669.36 | 0.125659E+09 | 94586277.23 | 13756344.46 |
Maximum of Months | 0.727047E+09 | 0.328005E+09 | 0.416204E+09 | 0.949022E+09 | 0.665845E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.320870E+09 | 0.210561E+09 | 0.110309E+09 | 0.289284E+09 | 0.331450E+09 |
February | 0.383680E+09 | 0.255051E+09 | 0.128629E+09 | 0.338871E+09 | 0.301267E+09 |
March | 0.376349E+09 | 0.207231E+09 | 0.169118E+09 | 0.310995E+09 | 0.237851E+09 |
April | 0.289774E+09 | 0.117217E+09 | 0.172557E+09 | 0.216221E+09 | 0.158952E+09 |
May | 0.257163E+09 | 52617425.58 | 0.204546E+09 | 0.206262E+09 | 89738722.66 |
June | 0.234979E+09 | 36161720.47 | 0.198817E+09 | 0.242497E+09 | 31639353.62 |
July | 0.252657E+09 | 42605912.80 | 0.210051E+09 | 0.305099E+09 | 7530288.53 |
August | 0.338410E+09 | 0.124799E+09 | 0.213611E+09 | 0.382100E+09 | 19035583.43 |
September | 0.345692E+09 | 0.173585E+09 | 0.172106E+09 | 0.365697E+09 | 55244223.81 |
October | 0.504993E+09 | 0.316763E+09 | 0.188229E+09 | 0.542551E+09 | 0.134894E+09 |
November | 0.338273E+09 | 0.202937E+09 | 0.135336E+09 | 0.326945E+09 | 0.219460E+09 |
December | 0.346614E+09 | 0.246170E+09 | 0.100444E+09 | 0.334995E+09 | 0.296160E+09 |
Annual Sum or Average | 0.398945E+10 | 0.198570E+10 | 0.200375E+10 | 0.386152E+10 | 0.188322E+10 |
Minimum of Months | 0.234979E+09 | 36161720.47 | 0.100444E+09 | 0.206262E+09 | 7530288.53 |
Maximum of Months | 0.504993E+09 | 0.316763E+09 | 0.213611E+09 | 0.542551E+09 | 0.331450E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61730780.89 | 0.00 | 61730780.89 | 862849.34 | 0.377217E+09 |
February | 76300861.09 | 0.00 | 76300861.09 | 3107213.67 | 0.351853E+09 |
March | 0.117174E+09 | 2329.53 | 0.117172E+09 | 26544869.00 | 0.249096E+09 |
April | 0.136455E+09 | 556193.62 | 0.135898E+09 | 66477394.49 | 0.158601E+09 |
May | 0.187529E+09 | 6843609.71 | 0.180685E+09 | 0.143267E+09 | 85139355.96 |
June | 0.191453E+09 | 10160814.05 | 0.181293E+09 | 0.202477E+09 | 33314744.63 |
July | 0.192023E+09 | 7474350.78 | 0.184549E+09 | 0.247067E+09 | 10559321.18 |
August | 0.169816E+09 | 2241668.73 | 0.167574E+09 | 0.221244E+09 | 21926734.13 |
September | 0.123752E+09 | 70321.09 | 0.123681E+09 | 0.118383E+09 | 58917301.61 |
October | 0.110579E+09 | 0.00 | 0.110579E+09 | 66770716.30 | 0.140020E+09 |
November | 75058300.98 | 0.00 | 75058300.98 | 14253492.21 | 0.240824E+09 |
December | 53845644.44 | 0.00 | 53845644.44 | 707684.12 | 0.341238E+09 |
Annual Sum or Average | 0.149572E+10 | 27349287.52 | 0.146837E+10 | 0.111116E+10 | 0.206871E+10 |
Minimum of Months | 53845644.44 | 0.00 | 53845644.44 | 707684.12 | 10559321.18 |
Maximum of Months | 0.192023E+09 | 10160814.05 | 0.184549E+09 | 0.247067E+09 | 0.377217E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.240168E+09 | 95969669.36 | 0.144198E+09 | 97412789.07 | 0.654284E+09 |
February | 0.336766E+09 | 0.156828E+09 | 0.179938E+09 | 0.174014E+09 | 0.584976E+09 |
March | 0.478787E+09 | 0.203481E+09 | 0.275306E+09 | 0.345078E+09 | 0.436110E+09 |
April | 0.554692E+09 | 0.243479E+09 | 0.311214E+09 | 0.485392E+09 | 0.279299E+09 |
May | 0.691897E+09 | 0.275693E+09 | 0.416204E+09 | 0.712434E+09 | 0.160811E+09 |
June | 0.621750E+09 | 0.225167E+09 | 0.396583E+09 | 0.722513E+09 | 64245455.15 |
July | 0.644437E+09 | 0.231970E+09 | 0.412467E+09 | 0.833274E+09 | 20340854.12 |
August | 0.727047E+09 | 0.328005E+09 | 0.399042E+09 | 0.936272E+09 | 40692138.34 |
September | 0.526373E+09 | 0.237150E+09 | 0.289223E+09 | 0.587080E+09 | 0.105231E+09 |
October | 0.491360E+09 | 0.222425E+09 | 0.268935E+09 | 0.462463E+09 | 0.248319E+09 |
November | 0.294523E+09 | 0.113190E+09 | 0.181333E+09 | 0.176486E+09 | 0.416199E+09 |
December | 0.237958E+09 | 0.112299E+09 | 0.125659E+09 | 0.108415E+09 | 0.585142E+09 |
Annual Sum or Average | 0.584576E+10 | 0.244566E+10 | 0.340010E+10 | 0.564083E+10 | 0.359565E+10 |
Minimum of Months | 0.237958E+09 | 95969669.36 | 0.125659E+09 | 97412789.07 | 20340854.12 |
Maximum of Months | 0.727047E+09 | 0.328005E+09 | 0.416204E+09 | 0.936272E+09 | 0.654284E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78178139.00 | 0.00 | 78178139.00 | 659824.13 | 0.486365E+09 |
February | 96630226.25 | 0.00 | 96630226.25 | 3463908.29 | 0.453710E+09 |
March | 0.148394E+09 | 2950.20 | 0.148391E+09 | 35315505.74 | 0.319310E+09 |
April | 0.172811E+09 | 704384.12 | 0.172107E+09 | 94383521.98 | 0.199294E+09 |
May | 0.237493E+09 | 8666999.89 | 0.228826E+09 | 0.205140E+09 | 0.103526E+09 |
June | 0.242464E+09 | 12868029.88 | 0.229596E+09 | 0.277344E+09 | 40975385.92 |
July | 0.243185E+09 | 9465793.66 | 0.233720E+09 | 0.327841E+09 | 14074185.74 |
August | 0.215061E+09 | 2838932.01 | 0.212222E+09 | 0.292143E+09 | 29820542.73 |
September | 0.156724E+09 | 89057.23 | 0.156635E+09 | 0.162831E+09 | 74129258.47 |
October | 0.140041E+09 | 0.00 | 0.140041E+09 | 92574024.08 | 0.178302E+09 |
November | 95056602.27 | 0.00 | 95056602.27 | 18576584.66 | 0.313380E+09 |
December | 68192111.22 | 0.00 | 68192111.22 | 644122.13 | 0.448642E+09 |
Annual Sum or Average | 0.189423E+10 | 34636147.00 | 0.185959E+10 | 0.151092E+10 | 0.266153E+10 |
Minimum of Months | 68192111.22 | 0.00 | 68192111.22 | 644122.13 | 14074185.74 |
Maximum of Months | 0.243185E+09 | 12868029.88 | 0.233720E+09 | 0.327841E+09 | 0.486365E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 28819699.14 | 0.00 | 28819699.14 | 243238.50 | 0.179294E+09 |
February | 35621902.54 | 0.00 | 35621902.54 | 1276940.02 | 0.167256E+09 |
March | 54704162.36 | 1087.57 | 54703074.79 | 13018757.72 | 0.117711E+09 |
April | 63705355.58 | 259665.15 | 63445690.43 | 34793674.32 | 73467857.31 |
May | 87549904.44 | 3195015.03 | 84354889.40 | 75623018.87 | 38163949.86 |
June | 89382171.01 | 4743688.64 | 84638482.37 | 0.102240E+09 | 15105223.91 |
July | 89648234.72 | 3489483.49 | 86158751.23 | 0.120856E+09 | 5188327.63 |
August | 79280545.61 | 1046547.89 | 78233997.72 | 0.107696E+09 | 10993086.82 |
September | 57774862.31 | 32830.18 | 57742032.13 | 60026237.30 | 27327114.12 |
October | 51624818.34 | 0.00 | 51624818.34 | 34126618.47 | 65729529.10 |
November | 35041799.58 | 0.00 | 35041799.58 | 6848098.30 | 0.115525E+09 |
December | 25138435.81 | 0.00 | 25138435.81 | 237450.09 | 0.165388E+09 |
Annual Sum or Average | 0.698292E+09 | 12768317.95 | 0.685524E+09 | 0.556986E+09 | 0.981149E+09 |
Minimum of Months | 25138435.81 | 0.00 | 25138435.81 | 237450.09 | 5188327.63 |
Maximum of Months | 89648234.72 | 4743688.64 | 86158751.23 | 0.120856E+09 | 0.179294E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.149717E+09 | 98246975.53 | 51469885.86 | 0.136223E+09 | 0.154888E+09 |
February | 0.179024E+09 | 0.119006E+09 | 60017623.81 | 0.160177E+09 | 0.140822E+09 |
March | 0.175603E+09 | 96693315.15 | 78909658.94 | 0.148644E+09 | 0.110969E+09 |
April | 0.135207E+09 | 54693030.66 | 80514420.21 | 0.105867E+09 | 73075052.78 |
May | 0.119991E+09 | 24551078.75 | 95440189.24 | 0.103967E+09 | 40532419.82 |
June | 0.109640E+09 | 16872913.05 | 92767131.95 | 0.117845E+09 | 15992609.46 |
July | 0.117889E+09 | 19879747.22 | 98008828.48 | 0.143530E+09 | 5324227.90 |
August | 0.157901E+09 | 58230837.92 | 99670033.13 | 0.179689E+09 | 11258811.54 |
September | 0.161298E+09 | 80994270.27 | 80304143.70 | 0.174731E+09 | 27033798.52 |
October | 0.235628E+09 | 0.147801E+09 | 87827048.88 | 0.259216E+09 | 62562351.30 |
November | 0.157837E+09 | 94689424.36 | 63147392.96 | 0.155099E+09 | 0.103013E+09 |
December | 0.161729E+09 | 0.114862E+09 | 46866835.43 | 0.157692E+09 | 0.140102E+09 |
Annual Sum or Average | 0.186146E+10 | 0.926520E+09 | 0.934943E+09 | 0.184268E+10 | 0.885572E+09 |
Minimum of Months | 0.109640E+09 | 16872913.05 | 46866835.43 | 0.103967E+09 | 5324227.90 |
Maximum of Months | 0.235628E+09 | 0.147801E+09 | 99670033.13 | 0.259216E+09 | 0.154888E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.406362E+09 | 0.266662E+09 | 0.139700E+09 | 0.369738E+09 | 0.420396E+09 |
February | 0.485907E+09 | 0.323007E+09 | 0.162900E+09 | 0.434752E+09 | 0.382219E+09 |
March | 0.476622E+09 | 0.262445E+09 | 0.214177E+09 | 0.403452E+09 | 0.301192E+09 |
April | 0.366981E+09 | 0.148448E+09 | 0.218533E+09 | 0.287346E+09 | 0.198341E+09 |
May | 0.325681E+09 | 66636649.53 | 0.259044E+09 | 0.282188E+09 | 0.110013E+09 |
June | 0.297586E+09 | 45796537.30 | 0.251789E+09 | 0.319857E+09 | 43407213.30 |
July | 0.319974E+09 | 53957700.28 | 0.266016E+09 | 0.389569E+09 | 14451043.57 |
August | 0.428575E+09 | 0.158050E+09 | 0.270525E+09 | 0.487714E+09 | 30558717.45 |
September | 0.437797E+09 | 0.219835E+09 | 0.217962E+09 | 0.474257E+09 | 73375258.83 |
October | 0.639541E+09 | 0.401161E+09 | 0.238381E+09 | 0.703566E+09 | 0.169807E+09 |
November | 0.428401E+09 | 0.257006E+09 | 0.171395E+09 | 0.420970E+09 | 0.279598E+09 |
December | 0.438965E+09 | 0.311759E+09 | 0.127206E+09 | 0.428009E+09 | 0.380267E+09 |
Annual Sum or Average | 0.505239E+10 | 0.251476E+10 | 0.253763E+10 | 0.500142E+10 | 0.240362E+10 |
Minimum of Months | 0.297586E+09 | 45796537.30 | 0.127206E+09 | 0.282188E+09 | 14451043.57 |
Maximum of Months | 0.639541E+09 | 0.401161E+09 | 0.270525E+09 | 0.703566E+09 | 0.420396E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321134E+09 | 0.210734E+09 | 0.110400E+09 | 0.289193E+09 | 0.331611E+09 |
February | 0.383995E+09 | 0.255261E+09 | 0.128734E+09 | 0.339600E+09 | 0.301803E+09 |
March | 0.376658E+09 | 0.207401E+09 | 0.169256E+09 | 0.312104E+09 | 0.239986E+09 |
April | 0.290012E+09 | 0.117313E+09 | 0.172699E+09 | 0.217591E+09 | 0.160173E+09 |
May | 0.257374E+09 | 52660590.00 | 0.204713E+09 | 0.206266E+09 | 91727688.85 |
June | 0.235171E+09 | 36191385.54 | 0.198980E+09 | 0.240274E+09 | 32815783.58 |
July | 0.252864E+09 | 42640864.33 | 0.210223E+09 | 0.303730E+09 | 7702728.90 |
August | 0.338688E+09 | 0.124902E+09 | 0.213786E+09 | 0.382067E+09 | 19187554.40 |
September | 0.345975E+09 | 0.173728E+09 | 0.172248E+09 | 0.365275E+09 | 55744604.28 |
October | 0.505407E+09 | 0.317023E+09 | 0.188384E+09 | 0.541763E+09 | 0.136003E+09 |
November | 0.338550E+09 | 0.203103E+09 | 0.135447E+09 | 0.328179E+09 | 0.217967E+09 |
December | 0.346898E+09 | 0.246372E+09 | 0.100527E+09 | 0.335700E+09 | 0.295233E+09 |
Annual Sum or Average | 0.399273E+10 | 0.198733E+10 | 0.200540E+10 | 0.386174E+10 | 0.188995E+10 |
Minimum of Months | 0.235171E+09 | 36191385.54 | 0.100527E+09 | 0.206266E+09 | 7702728.90 |
Maximum of Months | 0.505407E+09 | 0.317023E+09 | 0.213786E+09 | 0.541763E+09 | 0.331611E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238695E+09 | 98005856.50 | 0.140689E+09 | 0.103091E+09 | 0.677712E+09 |
February | 0.316668E+09 | 0.138978E+09 | 0.177690E+09 | 0.159514E+09 | 0.621785E+09 |
March | 0.520807E+09 | 0.241378E+09 | 0.279429E+09 | 0.383066E+09 | 0.442472E+09 |
April | 0.547367E+09 | 0.233924E+09 | 0.313443E+09 | 0.477407E+09 | 0.290587E+09 |
May | 0.660673E+09 | 0.251106E+09 | 0.409566E+09 | 0.673415E+09 | 0.164105E+09 |
June | 0.698544E+09 | 0.281869E+09 | 0.416676E+09 | 0.826202E+09 | 59344579.25 |
July | 0.675347E+09 | 0.253751E+09 | 0.421596E+09 | 0.882686E+09 | 14202268.43 |
August | 0.747249E+09 | 0.345491E+09 | 0.401759E+09 | 0.971597E+09 | 35528478.63 |
September | 0.514545E+09 | 0.224655E+09 | 0.289890E+09 | 0.576853E+09 | 0.103870E+09 |
October | 0.527529E+09 | 0.256980E+09 | 0.270549E+09 | 0.500854E+09 | 0.259338E+09 |
November | 0.240417E+09 | 70238520.06 | 0.170178E+09 | 0.116984E+09 | 0.437231E+09 |
December | 0.219460E+09 | 94750427.63 | 0.124709E+09 | 95195714.10 | 0.612560E+09 |
Annual Sum or Average | 0.590730E+10 | 0.249113E+10 | 0.341618E+10 | 0.576686E+10 | 0.371874E+10 |
Minimum of Months | 0.219460E+09 | 70238520.06 | 0.124709E+09 | 95195714.10 | 14202268.43 |
Maximum of Months | 0.747249E+09 | 0.345491E+09 | 0.421596E+09 | 0.971597E+09 | 0.677712E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61781421.40 | 0.00 | 61781421.40 | 1152624.16 | 0.376641E+09 |
February | 76363454.09 | 0.00 | 76363454.09 | 3538150.29 | 0.351324E+09 |
March | 0.117271E+09 | 2331.44 | 0.117268E+09 | 27951413.41 | 0.250418E+09 |
April | 0.136567E+09 | 556649.89 | 0.136010E+09 | 67023518.46 | 0.159862E+09 |
May | 0.187683E+09 | 6849223.83 | 0.180833E+09 | 0.140630E+09 | 88835144.24 |
June | 0.191611E+09 | 10169149.42 | 0.181441E+09 | 0.195984E+09 | 38113635.67 |
July | 0.192181E+09 | 7480482.32 | 0.184700E+09 | 0.242996E+09 | 13297456.23 |
August | 0.169955E+09 | 2243507.67 | 0.167712E+09 | 0.219797E+09 | 25179550.76 |
September | 0.123853E+09 | 70378.78 | 0.123783E+09 | 0.117149E+09 | 63026636.15 |
October | 0.110669E+09 | 0.00 | 0.110669E+09 | 67392027.67 | 0.143460E+09 |
November | 75119874.64 | 0.00 | 75119874.64 | 15577167.76 | 0.237625E+09 |
December | 53889816.42 | 0.00 | 53889816.42 | 1030169.69 | 0.338676E+09 |
Annual Sum or Average | 0.149694E+10 | 27371723.36 | 0.146957E+10 | 0.110022E+10 | 0.208646E+10 |
Minimum of Months | 53889816.42 | 0.00 | 53889816.42 | 1030169.69 | 13297456.23 |
Maximum of Months | 0.192181E+09 | 10169149.42 | 0.184700E+09 | 0.242996E+09 | 0.376641E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238695E+09 | 98005856.50 | 0.140689E+09 | 0.108945E+09 | 0.669192E+09 |
February | 0.316668E+09 | 0.138978E+09 | 0.177690E+09 | 0.167996E+09 | 0.611633E+09 |
March | 0.520807E+09 | 0.241378E+09 | 0.279429E+09 | 0.394725E+09 | 0.435886E+09 |
April | 0.547367E+09 | 0.233924E+09 | 0.313443E+09 | 0.480857E+09 | 0.289572E+09 |
May | 0.660673E+09 | 0.251106E+09 | 0.409566E+09 | 0.665356E+09 | 0.170197E+09 |
June | 0.698544E+09 | 0.281869E+09 | 0.416676E+09 | 0.805186E+09 | 73341396.79 |
July | 0.675347E+09 | 0.253751E+09 | 0.421596E+09 | 0.860167E+09 | 25078255.98 |
August | 0.747249E+09 | 0.345491E+09 | 0.401759E+09 | 0.956898E+09 | 47360656.81 |
September | 0.514545E+09 | 0.224655E+09 | 0.289890E+09 | 0.570633E+09 | 0.115107E+09 |
October | 0.527529E+09 | 0.256980E+09 | 0.270549E+09 | 0.511137E+09 | 0.258724E+09 |
November | 0.240417E+09 | 70238520.06 | 0.170178E+09 | 0.126779E+09 | 0.428052E+09 |
December | 0.219460E+09 | 94750427.63 | 0.124709E+09 | 0.102922E+09 | 0.601362E+09 |
Annual Sum or Average | 0.590730E+10 | 0.249113E+10 | 0.341618E+10 | 0.575160E+10 | 0.372551E+10 |
Minimum of Months | 0.219460E+09 | 70238520.06 | 0.124709E+09 | 0.102922E+09 | 25078255.98 |
Maximum of Months | 0.747249E+09 | 0.345491E+09 | 0.421596E+09 | 0.956898E+09 | 0.669192E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.470973E+09 | 0.309061E+09 | 0.161912E+09 | 0.408937E+09 | 0.504519E+09 |
February | 0.563165E+09 | 0.374364E+09 | 0.188801E+09 | 0.480672E+09 | 0.459831E+09 |
March | 0.552405E+09 | 0.304174E+09 | 0.248231E+09 | 0.447477E+09 | 0.361292E+09 |
April | 0.425330E+09 | 0.172051E+09 | 0.253279E+09 | 0.315633E+09 | 0.237396E+09 |
May | 0.377464E+09 | 77231809.09 | 0.300232E+09 | 0.306277E+09 | 0.131959E+09 |
June | 0.344901E+09 | 53078140.20 | 0.291823E+09 | 0.361804E+09 | 44342307.65 |
July | 0.370849E+09 | 62536919.79 | 0.308312E+09 | 0.456309E+09 | 9371312.61 |
August | 0.496718E+09 | 0.183180E+09 | 0.313538E+09 | 0.569531E+09 | 25735438.11 |
September | 0.507406E+09 | 0.254789E+09 | 0.252618E+09 | 0.536131E+09 | 80907255.53 |
October | 0.741228E+09 | 0.464945E+09 | 0.276283E+09 | 0.786891E+09 | 0.203622E+09 |
November | 0.496517E+09 | 0.297870E+09 | 0.198647E+09 | 0.466642E+09 | 0.336561E+09 |
December | 0.508760E+09 | 0.361328E+09 | 0.147432E+09 | 0.475565E+09 | 0.451947E+09 |
Annual Sum or Average | 0.585572E+10 | 0.291461E+10 | 0.294111E+10 | 0.561187E+10 | 0.284748E+10 |
Minimum of Months | 0.344901E+09 | 53078140.20 | 0.147432E+09 | 0.306277E+09 | 9371312.61 |
Maximum of Months | 0.741228E+09 | 0.464945E+09 | 0.313538E+09 | 0.786891E+09 | 0.504519E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.432454E+09 | 0.00 | 0.432454E+09 | 56145.79 | 0.332946E+10 |
February | 0.534524E+09 | 0.00 | 0.534524E+09 | 3075957.87 | 0.305692E+10 |
March | 0.820863E+09 | 16319.47 | 0.820846E+09 | 95748366.72 | 0.234799E+10 |
April | 0.955930E+09 | 3896401.65 | 0.952033E+09 | 0.334432E+09 | 0.159380E+10 |
May | 0.131373E+10 | 47942751.02 | 0.126579E+10 | 0.818856E+09 | 0.927850E+09 |
June | 0.134122E+10 | 71181349.98 | 0.127004E+10 | 0.124517E+10 | 0.456963E+09 |
July | 0.134522E+10 | 52361393.11 | 0.129285E+10 | 0.151579E+10 | 0.262572E+09 |
August | 0.118964E+10 | 15703958.94 | 0.117394E+10 | 0.135130E+10 | 0.352967E+09 |
September | 0.866940E+09 | 492632.81 | 0.866447E+09 | 0.706048E+09 | 0.706364E+09 |
October | 0.774655E+09 | 0.00 | 0.774655E+09 | 0.348894E+09 | 0.142055E+10 |
November | 0.525819E+09 | 0.00 | 0.525819E+09 | 41605249.94 | 0.232510E+10 |
December | 0.377214E+09 | 0.00 | 0.377214E+09 | 325340.78 | 0.310946E+10 |
Annual Sum or Average | 0.104782E+11 | 0.191595E+09 | 0.102866E+11 | 0.646130E+10 | 0.198900E+11 |
Minimum of Months | 0.377214E+09 | 0.00 | 0.377214E+09 | 56145.79 | 0.262572E+09 |
Maximum of Months | 0.134522E+10 | 71181349.98 | 0.129285E+10 | 0.151579E+10 | 0.332946E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.432454E+09 | 0.00 | 0.432454E+09 | 0.00 | 0.350418E+10 |
February | 0.534524E+09 | 0.00 | 0.534524E+09 | 1116892.33 | 0.321202E+10 |
March | 0.820863E+09 | 16319.47 | 0.820846E+09 | 75863082.48 | 0.248934E+10 |
April | 0.955930E+09 | 3896401.65 | 0.952033E+09 | 0.298844E+09 | 0.169410E+10 |
May | 0.131373E+10 | 47942751.02 | 0.126579E+10 | 0.763200E+09 | 0.995417E+09 |
June | 0.134122E+10 | 71181349.98 | 0.127004E+10 | 0.118681E+10 | 0.503378E+09 |
July | 0.134522E+10 | 52361393.11 | 0.129285E+10 | 0.145776E+10 | 0.303337E+09 |
August | 0.118964E+10 | 15703958.94 | 0.117394E+10 | 0.129752E+10 | 0.397506E+09 |
September | 0.866940E+09 | 492632.81 | 0.866447E+09 | 0.664542E+09 | 0.768701E+09 |
October | 0.774655E+09 | 0.00 | 0.774655E+09 | 0.316604E+09 | 0.151003E+10 |
November | 0.525819E+09 | 0.00 | 0.525819E+09 | 32482922.44 | 0.246468E+10 |
December | 0.377214E+09 | 0.00 | 0.377214E+09 | 79718.54 | 0.328394E+10 |
Annual Sum or Average | 0.104782E+11 | 0.191595E+09 | 0.102866E+11 | 0.609483E+10 | 0.211266E+11 |
Minimum of Months | 0.377214E+09 | 0.00 | 0.377214E+09 | 0.00 | 0.303337E+09 |
Maximum of Months | 0.134522E+10 | 71181349.98 | 0.129285E+10 | 0.145776E+10 | 0.350418E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61781421.40 | 0.00 | 61781421.40 | 16098.23 | 0.493602E+09 |
February | 76363454.09 | 0.00 | 76363454.09 | 500560.38 | 0.454149E+09 |
March | 0.117271E+09 | 2331.44 | 0.117268E+09 | 11910258.30 | 0.354064E+09 |
April | 0.136567E+09 | 556649.89 | 0.136010E+09 | 48906091.38 | 0.243131E+09 |
May | 0.187683E+09 | 6849223.83 | 0.180833E+09 | 0.124466E+09 | 0.148077E+09 |
June | 0.191611E+09 | 10169149.42 | 0.181441E+09 | 0.194984E+09 | 77643276.47 |
July | 0.192181E+09 | 7480482.32 | 0.184700E+09 | 0.241356E+09 | 45746386.58 |
August | 0.169955E+09 | 2243507.67 | 0.167712E+09 | 0.211480E+09 | 60256928.71 |
September | 0.123853E+09 | 70378.78 | 0.123783E+09 | 0.112267E+09 | 0.111478E+09 |
October | 0.110669E+09 | 0.00 | 0.110669E+09 | 51292752.66 | 0.216104E+09 |
November | 75119874.64 | 0.00 | 75119874.64 | 6028267.69 | 0.349121E+09 |
December | 53889816.42 | 0.00 | 53889816.42 | 60975.00 | 0.463362E+09 |
Annual Sum or Average | 0.149694E+10 | 27371723.36 | 0.146957E+10 | 0.100327E+10 | 0.301673E+10 |
Minimum of Months | 53889816.42 | 0.00 | 53889816.42 | 16098.23 | 45746386.58 |
Maximum of Months | 0.192181E+09 | 10169149.42 | 0.184700E+09 | 0.241356E+09 | 0.493602E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.480696E+09 | 0.192083E+09 | 0.288612E+09 | 0.171713E+09 | 0.172575E+10 |
February | 0.674037E+09 | 0.313891E+09 | 0.360146E+09 | 0.312181E+09 | 0.152121E+10 |
March | 0.958292E+09 | 0.407267E+09 | 0.551025E+09 | 0.615658E+09 | 0.125303E+10 |
April | 0.111022E+10 | 0.487322E+09 | 0.622894E+09 | 0.890106E+09 | 0.866374E+09 |
May | 0.138483E+10 | 0.551800E+09 | 0.833031E+09 | 0.134907E+10 | 0.560123E+09 |
June | 0.124443E+10 | 0.450671E+09 | 0.793760E+09 | 0.141613E+10 | 0.302005E+09 |
July | 0.128984E+10 | 0.464288E+09 | 0.825552E+09 | 0.164234E+10 | 0.178215E+09 |
August | 0.145518E+10 | 0.656501E+09 | 0.798682E+09 | 0.183350E+10 | 0.229423E+09 |
September | 0.105353E+10 | 0.474654E+09 | 0.578880E+09 | 0.114519E+10 | 0.408485E+09 |
October | 0.983456E+09 | 0.445182E+09 | 0.538274E+09 | 0.856170E+09 | 0.773750E+09 |
November | 0.589487E+09 | 0.226550E+09 | 0.362937E+09 | 0.297475E+09 | 0.120535E+10 |
December | 0.476272E+09 | 0.224766E+09 | 0.251506E+09 | 0.189004E+09 | 0.159391E+10 |
Annual Sum or Average | 0.117003E+11 | 0.489498E+10 | 0.680530E+10 | 0.107185E+11 | 0.106176E+11 |
Minimum of Months | 0.476272E+09 | 0.192083E+09 | 0.251506E+09 | 0.171713E+09 | 0.178215E+09 |
Maximum of Months | 0.145518E+10 | 0.656501E+09 | 0.833031E+09 | 0.183350E+10 | 0.172575E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321134E+09 | 0.210734E+09 | 0.110400E+09 | 0.274281E+09 | 0.425803E+09 |
February | 0.383995E+09 | 0.255261E+09 | 0.128734E+09 | 0.322918E+09 | 0.378025E+09 |
March | 0.376658E+09 | 0.207401E+09 | 0.169256E+09 | 0.293246E+09 | 0.329741E+09 |
April | 0.290012E+09 | 0.117313E+09 | 0.172699E+09 | 0.197768E+09 | 0.241746E+09 |
May | 0.257374E+09 | 52660590.00 | 0.204713E+09 | 0.186764E+09 | 0.157600E+09 |
June | 0.235171E+09 | 36191385.54 | 0.198980E+09 | 0.228129E+09 | 83835703.25 |
July | 0.252864E+09 | 42640864.33 | 0.210223E+09 | 0.288524E+09 | 48509039.08 |
August | 0.338688E+09 | 0.124902E+09 | 0.213786E+09 | 0.365417E+09 | 62457723.06 |
September | 0.345975E+09 | 0.173728E+09 | 0.172248E+09 | 0.357641E+09 | 0.111619E+09 |
October | 0.505407E+09 | 0.317023E+09 | 0.188384E+09 | 0.530045E+09 | 0.206307E+09 |
November | 0.338550E+09 | 0.203103E+09 | 0.135447E+09 | 0.309815E+09 | 0.306777E+09 |
December | 0.346898E+09 | 0.246372E+09 | 0.100527E+09 | 0.318580E+09 | 0.390143E+09 |
Annual Sum or Average | 0.399273E+10 | 0.198733E+10 | 0.200540E+10 | 0.367313E+10 | 0.274256E+10 |
Minimum of Months | 0.235171E+09 | 36191385.54 | 0.100527E+09 | 0.186764E+09 | 48509039.08 |
Maximum of Months | 0.505407E+09 | 0.317023E+09 | 0.213786E+09 | 0.530045E+09 | 0.425803E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 78242272.01 | 0.00 | 78242272.01 | 151714.24 | 0.527713E+09 |
February | 96709496.33 | 0.00 | 96709496.33 | 1539666.65 | 0.488527E+09 |
March | 0.148516E+09 | 2952.62 | 0.148513E+09 | 21734722.32 | 0.372590E+09 |
April | 0.172953E+09 | 704961.96 | 0.172248E+09 | 66733703.45 | 0.253519E+09 |
May | 0.237688E+09 | 8674109.82 | 0.229014E+09 | 0.157987E+09 | 0.146488E+09 |
June | 0.242663E+09 | 12878586.10 | 0.229784E+09 | 0.233799E+09 | 68166984.73 |
July | 0.243385E+09 | 9473558.87 | 0.233911E+09 | 0.281114E+09 | 35669708.36 |
August | 0.215238E+09 | 2841260.91 | 0.212397E+09 | 0.248158E+09 | 52019165.32 |
September | 0.156852E+09 | 89130.29 | 0.156763E+09 | 0.130764E+09 | 0.110775E+09 |
October | 0.140156E+09 | 0.00 | 0.140156E+09 | 65198363.68 | 0.231990E+09 |
November | 95134581.43 | 0.00 | 95134581.43 | 8864597.77 | 0.370760E+09 |
December | 68248052.24 | 0.00 | 68248052.24 | 173356.01 | 0.491119E+09 |
Annual Sum or Average | 0.189578E+10 | 34664560.57 | 0.186112E+10 | 0.121622E+10 | 0.314934E+10 |
Minimum of Months | 68248052.24 | 0.00 | 68248052.24 | 151714.24 | 35669708.36 |
Maximum of Months | 0.243385E+09 | 12878586.10 | 0.233911E+09 | 0.281114E+09 | 0.527713E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 70003657.22 | 0.00 | 70003657.22 | 135739.30 | 0.472144E+09 |
February | 86526352.80 | 0.00 | 86526352.80 | 1377545.59 | 0.437087E+09 |
March | 0.132878E+09 | 2641.72 | 0.132875E+09 | 19446138.41 | 0.333358E+09 |
April | 0.154742E+09 | 630732.14 | 0.154111E+09 | 59706897.33 | 0.226824E+09 |
May | 0.212661E+09 | 7760758.92 | 0.204900E+09 | 0.141351E+09 | 0.131063E+09 |
June | 0.217111E+09 | 11522519.78 | 0.205589E+09 | 0.209181E+09 | 60989259.52 |
July | 0.217757E+09 | 8476029.02 | 0.209281E+09 | 0.251514E+09 | 31913823.22 |
August | 0.192574E+09 | 2542086.90 | 0.190032E+09 | 0.222028E+09 | 46541744.31 |
September | 0.140336E+09 | 79745.20 | 0.140257E+09 | 0.116995E+09 | 99110953.12 |
October | 0.125398E+09 | 0.00 | 0.125398E+09 | 58333223.02 | 0.207562E+09 |
November | 85117270.47 | 0.00 | 85117270.47 | 7931189.21 | 0.331721E+09 |
December | 61061790.93 | 0.00 | 61061790.93 | 155102.28 | 0.439394E+09 |
Annual Sum or Average | 0.169617E+10 | 31014513.69 | 0.166515E+10 | 0.108815E+10 | 0.281771E+10 |
Minimum of Months | 61061790.93 | 0.00 | 61061790.93 | 135739.30 | 31913823.22 |
Maximum of Months | 0.217757E+09 | 11522519.78 | 0.209281E+09 | 0.251514E+09 | 0.472144E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119889E+10 | 0.786732E+09 | 0.412155E+09 | 0.105542E+10 | 0.133480E+10 |
February | 0.143357E+10 | 0.952964E+09 | 0.480603E+09 | 0.124348E+10 | 0.120132E+10 |
March | 0.140618E+10 | 0.774291E+09 | 0.631885E+09 | 0.112946E+10 | 0.102896E+10 |
April | 0.108270E+10 | 0.437965E+09 | 0.644735E+09 | 0.759610E+09 | 0.741886E+09 |
May | 0.960854E+09 | 0.196598E+09 | 0.764256E+09 | 0.703033E+09 | 0.462367E+09 |
June | 0.877965E+09 | 0.135113E+09 | 0.742851E+09 | 0.821021E+09 | 0.216106E+09 |
July | 0.944016E+09 | 0.159191E+09 | 0.784825E+09 | 0.101450E+10 | 0.109696E+09 |
August | 0.126442E+10 | 0.466295E+09 | 0.798128E+09 | 0.131207E+10 | 0.158335E+09 |
September | 0.129163E+10 | 0.648578E+09 | 0.643051E+09 | 0.130040E+10 | 0.323457E+09 |
October | 0.188683E+10 | 0.118354E+10 | 0.703293E+09 | 0.197109E+10 | 0.643854E+09 |
November | 0.126391E+10 | 0.758245E+09 | 0.505665E+09 | 0.117545E+10 | 0.961039E+09 |
December | 0.129508E+10 | 0.919780E+09 | 0.375296E+09 | 0.122087E+10 | 0.121291E+10 |
Annual Sum or Average | 0.149060E+11 | 0.741929E+10 | 0.748674E+10 | 0.137064E+11 | 0.839473E+10 |
Minimum of Months | 0.877965E+09 | 0.135113E+09 | 0.375296E+09 | 0.703033E+09 | 0.109696E+09 |
Maximum of Months | 0.188683E+10 | 0.118354E+10 | 0.798128E+09 | 0.197109E+10 | 0.133480E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 538.40 | 623.83 | 607.15 | 398.42 | 208.73 | 0.00 | 0.00 |
February | 699.03 | 628.93 | 803.78 | 534.32 | 269.47 | 0.00 | 0.00 |
March | 576.30 | 470.66 | 712.13 | 392.12 | 320.00 | 0.00 | 0.00 |
April | 403.81 | 343.56 | 566.59 | 229.19 | 337.40 | 0.00 | 0.00 |
May | 361.11 | 213.06 | 486.60 | 99.56 | 387.04 | 0.00 | 0.00 |
June | 427.14 | 106.60 | 459.45 | 70.71 | 388.74 | 0.00 | 0.00 |
July | 510.24 | 51.76 | 478.08 | 80.62 | 397.46 | 0.00 | 0.00 |
August | 649.77 | 79.70 | 640.34 | 236.14 | 404.19 | 0.00 | 0.00 |
September | 670.04 | 164.25 | 675.92 | 339.41 | 336.51 | 0.00 | 0.00 |
October | 986.49 | 316.28 | 955.55 | 599.38 | 356.17 | 0.00 | 0.00 |
November | 619.38 | 460.93 | 661.41 | 396.80 | 264.62 | 0.00 | 0.00 |
December | 618.77 | 572.24 | 655.86 | 465.80 | 190.06 | 0.00 | 0.00 |
Annual Sum or Average | 588.10 | 334.31 | 641.13 | 319.12 | 322.02 | 0.00 | 0.00 |
Minimum of Months | 361.11 | 51.76 | 459.45 | 70.71 | 190.06 | 0.00 | 0.00 |
Maximum of Months | 986.49 | 628.93 | 955.55 | 599.38 | 404.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1487.83 | 1882.74 | 1709.69 | 1121.93 | 587.76 | 0.00 | 0.00 |
February | 1932.25 | 1894.31 | 2263.40 | 1504.60 | 758.81 | 0.00 | 0.00 |
March | 1593.23 | 1433.30 | 2005.30 | 1104.19 | 901.11 | 0.00 | 0.00 |
April | 1115.66 | 1041.32 | 1595.47 | 645.39 | 950.08 | 0.00 | 0.00 |
May | 1006.62 | 627.96 | 1370.24 | 280.36 | 1089.88 | 0.00 | 0.00 |
June | 1195.01 | 318.85 | 1293.77 | 199.10 | 1094.67 | 0.00 | 0.00 |
July | 1423.87 | 165.75 | 1346.23 | 227.02 | 1119.21 | 0.00 | 0.00 |
August | 1820.81 | 246.00 | 1803.15 | 664.97 | 1138.18 | 0.00 | 0.00 |
September | 1880.55 | 489.86 | 1903.35 | 955.75 | 947.60 | 0.00 | 0.00 |
October | 2759.51 | 939.88 | 2690.75 | 1687.81 | 1002.94 | 0.00 | 0.00 |
November | 1713.26 | 1399.11 | 1862.50 | 1117.35 | 745.15 | 0.00 | 0.00 |
December | 1709.55 | 1739.70 | 1846.86 | 1311.67 | 535.20 | 0.00 | 0.00 |
Annual Sum or Average | 1635.84 | 1009.89 | 1805.39 | 898.61 | 906.78 | 0.00 | 0.00 |
Minimum of Months | 1006.62 | 165.75 | 1293.77 | 199.10 | 535.20 | 0.00 | 0.00 |
Maximum of Months | 2759.51 | 1894.31 | 2690.75 | 1687.81 | 1138.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1947.68 | 2616.73 | 2220.99 | 1457.45 | 763.54 | 0.00 | 0.00 |
February | 2540.15 | 2604.40 | 2940.29 | 1954.56 | 985.73 | 0.00 | 0.00 |
March | 2097.02 | 1970.45 | 2605.00 | 1434.41 | 1170.59 | 0.00 | 0.00 |
April | 1464.04 | 1439.81 | 2072.61 | 838.39 | 1234.21 | 0.00 | 0.00 |
May | 1323.69 | 865.87 | 1780.02 | 364.21 | 1415.82 | 0.00 | 0.00 |
June | 1588.20 | 433.69 | 1680.68 | 258.65 | 1422.04 | 0.00 | 0.00 |
July | 1903.54 | 220.90 | 1748.83 | 294.91 | 1453.92 | 0.00 | 0.00 |
August | 2440.94 | 318.72 | 2342.40 | 863.83 | 1478.57 | 0.00 | 0.00 |
September | 2503.27 | 650.33 | 2472.56 | 1241.57 | 1230.99 | 0.00 | 0.00 |
October | 3671.56 | 1245.59 | 3495.44 | 2192.56 | 1302.88 | 0.00 | 0.00 |
November | 2254.90 | 1924.12 | 2419.49 | 1451.50 | 967.99 | 0.00 | 0.00 |
December | 2247.67 | 2406.78 | 2399.18 | 1703.93 | 695.25 | 0.00 | 0.00 |
Annual Sum or Average | 2164.47 | 1384.54 | 2345.30 | 1167.35 | 1177.96 | 0.00 | 0.00 |
Minimum of Months | 1323.69 | 220.90 | 1680.68 | 258.65 | 695.25 | 0.00 | 0.00 |
Maximum of Months | 3671.56 | 2616.73 | 3495.44 | 2192.56 | 1478.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 131.77 | 362.02 | 208.84 | 115.18 | 93.67 | 0.00 | 0.00 |
February | 187.65 | 362.34 | 289.39 | 162.83 | 126.56 | 0.00 | 0.00 |
March | 255.14 | 249.15 | 334.80 | 167.42 | 167.38 | 0.00 | 0.00 |
April | 268.25 | 171.91 | 322.80 | 135.40 | 187.40 | 0.00 | 0.00 |
May | 331.20 | 93.61 | 342.48 | 113.32 | 229.16 | 0.00 | 0.00 |
June | 414.51 | 35.17 | 359.93 | 122.61 | 237.33 | 0.00 | 0.00 |
July | 445.38 | 8.41 | 346.27 | 110.57 | 235.70 | 0.00 | 0.00 |
August | 507.17 | 20.97 | 405.11 | 175.48 | 229.63 | 0.00 | 0.00 |
September | 365.35 | 61.52 | 331.72 | 153.57 | 178.15 | 0.00 | 0.00 |
October | 389.76 | 146.40 | 385.34 | 214.13 | 171.21 | 0.00 | 0.00 |
November | 164.55 | 246.80 | 223.18 | 105.37 | 117.81 | 0.00 | 0.00 |
December | 145.17 | 324.71 | 211.28 | 127.26 | 84.02 | 0.00 | 0.00 |
Annual Sum or Average | 301.39 | 172.52 | 313.67 | 141.89 | 171.78 | 0.00 | 0.00 |
Minimum of Months | 131.77 | 8.41 | 208.84 | 105.37 | 84.02 | 0.00 | 0.00 |
Maximum of Months | 507.17 | 362.34 | 405.11 | 214.13 | 237.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 35.43 | 385.11 | 112.09 | 36.56 | 75.53 | 0.00 | 0.00 |
February | 63.22 | 390.17 | 162.33 | 57.40 | 104.93 | 0.00 | 0.00 |
March | 152.61 | 250.72 | 238.04 | 90.05 | 147.99 | 0.00 | 0.00 |
April | 211.84 | 171.37 | 263.65 | 90.39 | 173.26 | 0.00 | 0.00 |
May | 305.77 | 93.99 | 316.48 | 96.23 | 220.25 | 0.00 | 0.00 |
June | 391.83 | 40.09 | 343.14 | 112.58 | 230.57 | 0.00 | 0.00 |
July | 416.41 | 12.71 | 323.63 | 97.45 | 226.18 | 0.00 | 0.00 |
August | 442.51 | 25.67 | 342.16 | 129.72 | 212.44 | 0.00 | 0.00 |
September | 268.10 | 66.27 | 246.09 | 86.63 | 159.47 | 0.00 | 0.00 |
October | 215.70 | 148.12 | 238.08 | 95.87 | 142.21 | 0.00 | 0.00 |
November | 51.78 | 256.02 | 121.63 | 27.08 | 94.56 | 0.00 | 0.00 |
December | 32.97 | 347.37 | 101.97 | 35.35 | 66.63 | 0.00 | 0.00 |
Annual Sum or Average | 216.77 | 181.13 | 234.59 | 79.80 | 154.80 | 0.00 | 0.00 |
Minimum of Months | 32.97 | 12.71 | 101.97 | 27.08 | 66.63 | 0.00 | 0.00 |
Maximum of Months | 442.51 | 390.17 | 343.14 | 129.72 | 230.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 87.05 | 93.80 | 95.82 | 62.88 | 32.94 | 0.00 | 0.00 |
February | 107.33 | 112.94 | 126.85 | 84.33 | 42.53 | 0.00 | 0.00 |
March | 87.46 | 90.49 | 112.39 | 61.88 | 50.50 | 0.00 | 0.00 |
April | 59.00 | 69.54 | 89.42 | 36.17 | 53.25 | 0.00 | 0.00 |
May | 50.11 | 46.11 | 76.80 | 15.71 | 61.08 | 0.00 | 0.00 |
June | 61.03 | 25.07 | 72.51 | 11.16 | 61.35 | 0.00 | 0.00 |
July | 75.23 | 14.18 | 75.45 | 12.72 | 62.73 | 0.00 | 0.00 |
August | 99.29 | 18.54 | 101.06 | 37.27 | 63.79 | 0.00 | 0.00 |
September | 101.39 | 36.21 | 106.67 | 53.57 | 53.11 | 0.00 | 0.00 |
October | 151.23 | 63.37 | 150.80 | 94.59 | 56.21 | 0.00 | 0.00 |
November | 92.37 | 90.72 | 104.38 | 62.62 | 41.76 | 0.00 | 0.00 |
December | 94.37 | 104.88 | 103.51 | 73.51 | 30.00 | 0.00 | 0.00 |
Annual Sum or Average | 88.78 | 63.51 | 101.18 | 50.36 | 50.82 | 0.00 | 0.00 |
Minimum of Months | 50.11 | 14.18 | 72.51 | 11.16 | 30.00 | 0.00 | 0.00 |
Maximum of Months | 151.23 | 112.94 | 150.80 | 94.59 | 63.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.14 | 118.29 | 18.44 | 0.00 | 18.44 | 0.00 | 0.00 |
February | 0.89 | 120.65 | 25.24 | 0.00 | 25.24 | 0.00 | 0.00 |
March | 8.06 | 76.98 | 35.00 | 0.00 | 35.00 | 0.00 | 0.00 |
April | 21.72 | 50.25 | 42.12 | 0.17 | 41.95 | 0.00 | 0.00 |
May | 45.56 | 25.68 | 56.02 | 2.04 | 53.98 | 0.00 | 0.00 |
June | 66.03 | 9.93 | 59.10 | 3.14 | 55.96 | 0.00 | 0.00 |
July | 77.96 | 2.76 | 57.36 | 2.23 | 55.13 | 0.00 | 0.00 |
August | 71.00 | 5.89 | 50.73 | 0.67 | 50.06 | 0.00 | 0.00 |
September | 39.27 | 17.80 | 38.20 | 0.02 | 38.18 | 0.00 | 0.00 |
October | 21.59 | 42.08 | 33.03 | 0.00 | 33.03 | 0.00 | 0.00 |
November | 4.29 | 77.97 | 23.17 | 0.00 | 23.17 | 0.00 | 0.00 |
December | 0.16 | 107.22 | 16.09 | 0.00 | 16.09 | 0.00 | 0.00 |
Annual Sum or Average | 29.93 | 54.26 | 37.95 | 0.69 | 37.25 | 0.00 | 0.00 |
Minimum of Months | 0.14 | 2.76 | 16.09 | 0.00 | 16.09 | 0.00 | 0.00 |
Maximum of Months | 77.96 | 120.65 | 59.10 | 3.14 | 55.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 130.32 | 359.35 | 209.47 | 114.45 | 95.02 | 0.00 | 0.00 |
February | 194.64 | 356.70 | 297.80 | 170.25 | 127.55 | 0.00 | 0.00 |
March | 237.53 | 250.79 | 319.27 | 153.34 | 165.93 | 0.00 | 0.00 |
April | 266.12 | 167.10 | 325.80 | 139.16 | 186.64 | 0.00 | 0.00 |
May | 342.47 | 90.67 | 354.34 | 122.58 | 231.76 | 0.00 | 0.00 |
June | 376.56 | 33.44 | 330.53 | 100.82 | 229.71 | 0.00 | 0.00 |
July | 431.77 | 7.87 | 334.94 | 102.52 | 232.42 | 0.00 | 0.00 |
August | 496.73 | 19.56 | 397.80 | 169.06 | 228.74 | 0.00 | 0.00 |
September | 367.87 | 58.99 | 336.44 | 158.46 | 177.98 | 0.00 | 0.00 |
October | 369.59 | 143.23 | 372.00 | 201.31 | 170.69 | 0.00 | 0.00 |
November | 186.50 | 244.34 | 244.13 | 121.96 | 122.17 | 0.00 | 0.00 |
December | 151.10 | 321.55 | 218.25 | 133.84 | 84.42 | 0.00 | 0.00 |
Annual Sum or Average | 296.73 | 170.10 | 311.87 | 140.52 | 171.36 | 0.00 | 0.00 |
Minimum of Months | 130.32 | 7.87 | 209.47 | 100.82 | 84.42 | 0.00 | 0.00 |
Maximum of Months | 496.73 | 359.35 | 397.80 | 201.31 | 232.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 29.61 | 378.03 | 112.72 | 35.83 | 76.89 | 0.00 | 0.00 |
February | 60.54 | 374.57 | 170.75 | 64.83 | 105.92 | 0.00 | 0.00 |
March | 133.59 | 250.67 | 222.51 | 75.97 | 146.53 | 0.00 | 0.00 |
April | 209.80 | 165.83 | 266.65 | 94.15 | 172.50 | 0.00 | 0.00 |
May | 318.73 | 91.08 | 328.34 | 105.49 | 222.85 | 0.00 | 0.00 |
June | 356.56 | 37.33 | 313.74 | 90.79 | 222.95 | 0.00 | 0.00 |
July | 403.29 | 11.48 | 312.30 | 89.40 | 222.90 | 0.00 | 0.00 |
August | 432.02 | 23.23 | 334.85 | 123.30 | 211.55 | 0.00 | 0.00 |
September | 271.11 | 62.27 | 250.82 | 91.52 | 159.30 | 0.00 | 0.00 |
October | 195.35 | 142.75 | 224.74 | 83.04 | 141.69 | 0.00 | 0.00 |
November | 68.38 | 248.27 | 142.59 | 43.67 | 98.92 | 0.00 | 0.00 |
December | 32.72 | 337.85 | 108.95 | 41.93 | 67.02 | 0.00 | 0.00 |
Annual Sum or Average | 210.34 | 175.85 | 232.80 | 78.42 | 154.38 | 0.00 | 0.00 |
Minimum of Months | 29.61 | 11.48 | 108.95 | 35.83 | 67.02 | 0.00 | 0.00 |
Maximum of Months | 432.02 | 378.03 | 334.85 | 123.30 | 222.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 165.24 | 439.32 | 247.56 | 136.24 | 111.32 | 0.00 | 0.00 |
February | 220.36 | 445.37 | 329.52 | 182.71 | 146.81 | 0.00 | 0.00 |
March | 220.79 | 313.67 | 319.34 | 134.09 | 185.25 | 0.00 | 0.00 |
April | 201.21 | 209.62 | 284.99 | 78.74 | 206.25 | 0.00 | 0.00 |
May | 248.29 | 108.40 | 287.75 | 38.47 | 249.28 | 0.00 | 0.00 |
June | 314.74 | 43.98 | 285.14 | 30.97 | 254.16 | 0.00 | 0.00 |
July | 366.42 | 14.43 | 287.74 | 32.40 | 255.34 | 0.00 | 0.00 |
August | 398.40 | 30.79 | 328.86 | 82.20 | 246.66 | 0.00 | 0.00 |
September | 336.25 | 77.77 | 313.89 | 116.11 | 197.78 | 0.00 | 0.00 |
October | 404.80 | 175.90 | 398.31 | 204.96 | 193.35 | 0.00 | 0.00 |
November | 220.84 | 301.86 | 276.36 | 135.69 | 140.68 | 0.00 | 0.00 |
December | 193.67 | 398.20 | 259.12 | 159.28 | 99.84 | 0.00 | 0.00 |
Annual Sum or Average | 274.76 | 211.97 | 301.45 | 110.63 | 190.82 | 0.00 | 0.00 |
Minimum of Months | 165.24 | 14.43 | 247.56 | 30.97 | 99.84 | 0.00 | 0.00 |
Maximum of Months | 404.80 | 445.37 | 398.31 | 204.96 | 255.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 131.47 | 361.84 | 209.02 | 115.27 | 93.75 | 0.00 | 0.00 |
February | 186.94 | 362.40 | 289.63 | 162.96 | 126.66 | 0.00 | 0.00 |
March | 253.65 | 248.90 | 335.08 | 167.55 | 167.52 | 0.00 | 0.00 |
April | 266.02 | 171.79 | 323.06 | 135.51 | 187.55 | 0.00 | 0.00 |
May | 327.09 | 94.17 | 342.76 | 113.41 | 229.35 | 0.00 | 0.00 |
June | 411.10 | 35.20 | 360.23 | 122.71 | 237.52 | 0.00 | 0.00 |
July | 442.93 | 8.15 | 346.55 | 110.66 | 235.89 | 0.00 | 0.00 |
August | 505.35 | 20.38 | 405.44 | 175.62 | 229.82 | 0.00 | 0.00 |
September | 363.11 | 61.21 | 331.99 | 153.70 | 178.29 | 0.00 | 0.00 |
October | 387.61 | 145.94 | 385.65 | 214.31 | 171.35 | 0.00 | 0.00 |
November | 164.40 | 245.44 | 223.37 | 105.46 | 117.91 | 0.00 | 0.00 |
December | 145.45 | 323.51 | 211.45 | 127.36 | 84.09 | 0.00 | 0.00 |
Annual Sum or Average | 299.65 | 172.18 | 313.93 | 142.01 | 171.92 | 0.00 | 0.00 |
Minimum of Months | 131.47 | 8.15 | 209.02 | 105.46 | 84.09 | 0.00 | 0.00 |
Maximum of Months | 505.35 | 362.40 | 405.44 | 214.31 | 237.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 35.58 | 384.94 | 112.19 | 36.59 | 75.59 | 0.00 | 0.00 |
February | 63.25 | 390.39 | 162.46 | 57.45 | 105.02 | 0.00 | 0.00 |
March | 151.79 | 250.22 | 238.23 | 90.12 | 148.11 | 0.00 | 0.00 |
April | 209.36 | 171.38 | 263.86 | 90.46 | 173.40 | 0.00 | 0.00 |
May | 300.04 | 95.83 | 316.74 | 96.31 | 220.43 | 0.00 | 0.00 |
June | 385.88 | 42.63 | 343.42 | 112.67 | 230.76 | 0.00 | 0.00 |
July | 411.78 | 14.23 | 323.90 | 97.53 | 226.37 | 0.00 | 0.00 |
August | 439.15 | 26.90 | 342.45 | 129.83 | 212.62 | 0.00 | 0.00 |
September | 264.64 | 68.01 | 246.30 | 86.70 | 159.60 | 0.00 | 0.00 |
October | 213.96 | 148.12 | 238.28 | 95.95 | 142.33 | 0.00 | 0.00 |
November | 52.19 | 254.09 | 121.73 | 27.10 | 94.64 | 0.00 | 0.00 |
December | 33.54 | 345.70 | 102.06 | 35.38 | 66.68 | 0.00 | 0.00 |
Annual Sum or Average | 214.50 | 181.53 | 234.79 | 79.86 | 154.93 | 0.00 | 0.00 |
Minimum of Months | 33.54 | 14.23 | 102.06 | 27.10 | 66.68 | 0.00 | 0.00 |
Maximum of Months | 439.15 | 390.39 | 343.42 | 129.83 | 230.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 152.68 | 188.37 | 175.84 | 115.39 | 60.45 | 0.00 | 0.00 |
February | 198.69 | 190.08 | 232.79 | 154.75 | 78.04 | 0.00 | 0.00 |
March | 167.07 | 134.89 | 206.24 | 113.57 | 92.68 | 0.00 | 0.00 |
April | 121.77 | 91.59 | 164.09 | 66.38 | 97.72 | 0.00 | 0.00 |
May | 114.35 | 49.27 | 140.93 | 28.84 | 112.09 | 0.00 | 0.00 |
June | 139.59 | 17.11 | 133.06 | 20.48 | 112.59 | 0.00 | 0.00 |
July | 170.37 | 3.50 | 138.46 | 23.35 | 115.11 | 0.00 | 0.00 |
August | 212.64 | 9.61 | 185.45 | 68.39 | 117.06 | 0.00 | 0.00 |
September | 206.84 | 31.21 | 195.76 | 98.30 | 97.46 | 0.00 | 0.00 |
October | 293.79 | 76.02 | 276.74 | 173.59 | 103.15 | 0.00 | 0.00 |
November | 180.03 | 129.85 | 191.56 | 114.92 | 76.64 | 0.00 | 0.00 |
December | 177.56 | 168.74 | 189.95 | 134.90 | 55.04 | 0.00 | 0.00 |
Annual Sum or Average | 177.95 | 90.29 | 185.68 | 92.42 | 93.26 | 0.00 | 0.00 |
Minimum of Months | 114.35 | 3.50 | 133.06 | 20.48 | 55.04 | 0.00 | 0.00 |
Maximum of Months | 293.79 | 190.08 | 276.74 | 173.59 | 117.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.02 | 1243.08 | 161.46 | 0.00 | 161.46 | 0.00 | 0.00 |
February | 1.27 | 1263.61 | 220.95 | 0.00 | 220.95 | 0.00 | 0.00 |
March | 35.75 | 876.64 | 306.47 | 0.01 | 306.47 | 0.00 | 0.00 |
April | 129.02 | 614.89 | 368.80 | 1.50 | 367.30 | 0.00 | 0.00 |
May | 305.73 | 346.42 | 490.49 | 17.90 | 472.59 | 0.00 | 0.00 |
June | 480.39 | 176.30 | 517.45 | 27.46 | 489.99 | 0.00 | 0.00 |
July | 565.93 | 98.03 | 502.25 | 19.55 | 482.70 | 0.00 | 0.00 |
August | 504.52 | 131.78 | 444.16 | 5.86 | 438.30 | 0.00 | 0.00 |
September | 272.40 | 272.52 | 334.47 | 0.19 | 334.28 | 0.00 | 0.00 |
October | 130.26 | 530.37 | 289.22 | 0.00 | 289.22 | 0.00 | 0.00 |
November | 16.05 | 897.03 | 202.86 | 0.00 | 202.86 | 0.00 | 0.00 |
December | 0.12 | 1160.94 | 140.84 | 0.00 | 140.84 | 0.00 | 0.00 |
Annual Sum or Average | 204.89 | 630.71 | 332.26 | 6.08 | 326.19 | 0.00 | 0.00 |
Minimum of Months | 0.02 | 98.03 | 140.84 | 0.00 | 140.84 | 0.00 | 0.00 |
Maximum of Months | 565.93 | 1263.61 | 517.45 | 27.46 | 489.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1308.31 | 161.46 | 0.00 | 161.46 | 0.00 | 0.00 |
February | 0.46 | 1327.72 | 220.95 | 0.00 | 220.95 | 0.00 | 0.00 |
March | 28.32 | 929.41 | 306.47 | 0.01 | 306.47 | 0.00 | 0.00 |
April | 115.29 | 653.59 | 368.80 | 1.50 | 367.30 | 0.00 | 0.00 |
May | 284.95 | 371.65 | 490.49 | 17.90 | 472.59 | 0.00 | 0.00 |
June | 457.88 | 194.20 | 517.45 | 27.46 | 489.99 | 0.00 | 0.00 |
July | 544.27 | 113.25 | 502.25 | 19.55 | 482.70 | 0.00 | 0.00 |
August | 484.44 | 148.41 | 444.16 | 5.86 | 438.30 | 0.00 | 0.00 |
September | 256.38 | 296.57 | 334.47 | 0.19 | 334.28 | 0.00 | 0.00 |
October | 118.21 | 563.78 | 289.22 | 0.00 | 289.22 | 0.00 | 0.00 |
November | 12.53 | 950.88 | 202.86 | 0.00 | 202.86 | 0.00 | 0.00 |
December | 0.03 | 1226.08 | 140.84 | 0.00 | 140.84 | 0.00 | 0.00 |
Annual Sum or Average | 193.27 | 669.92 | 332.26 | 6.08 | 326.19 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 113.25 | 140.84 | 0.00 | 140.84 | 0.00 | 0.00 |
Maximum of Months | 544.27 | 1327.72 | 517.45 | 27.46 | 489.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.43 | 940.50 | 322.44 | 150.39 | 172.04 | 0.00 | 0.00 |
February | 202.34 | 912.41 | 468.91 | 235.26 | 233.65 | 0.00 | 0.00 |
March | 325.29 | 704.63 | 542.20 | 229.49 | 312.71 | 0.00 | 0.00 |
April | 430.18 | 512.93 | 592.90 | 233.48 | 359.41 | 0.00 | 0.00 |
May | 616.13 | 319.50 | 683.20 | 228.24 | 454.96 | 0.00 | 0.00 |
June | 708.22 | 177.45 | 644.76 | 191.76 | 453.00 | 0.00 | 0.00 |
July | 810.42 | 101.13 | 647.73 | 192.06 | 455.67 | 0.00 | 0.00 |
August | 899.20 | 130.74 | 733.21 | 292.58 | 440.63 | 0.00 | 0.00 |
September | 620.67 | 241.23 | 587.72 | 250.17 | 337.54 | 0.00 | 0.00 |
October | 529.90 | 439.79 | 597.20 | 284.57 | 312.62 | 0.00 | 0.00 |
November | 213.70 | 695.15 | 387.02 | 165.76 | 221.26 | 0.00 | 0.00 |
December | 141.26 | 865.48 | 327.46 | 175.90 | 151.55 | 0.00 | 0.00 |
Annual Sum or Average | 469.97 | 501.11 | 545.09 | 219.10 | 325.99 | 0.00 | 0.00 |
Minimum of Months | 119.43 | 101.13 | 322.44 | 150.39 | 151.55 | 0.00 | 0.00 |
Maximum of Months | 899.20 | 940.50 | 733.21 | 292.58 | 455.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 354.26 | 831.76 | 502.96 | 293.73 | 209.23 | 0.00 | 0.00 |
February | 469.41 | 833.39 | 668.32 | 393.92 | 274.40 | 0.00 | 0.00 |
March | 429.24 | 639.92 | 630.07 | 289.09 | 340.98 | 0.00 | 0.00 |
April | 340.83 | 470.53 | 544.13 | 169.48 | 374.65 | 0.00 | 0.00 |
May | 372.91 | 274.92 | 526.88 | 79.54 | 447.35 | 0.00 | 0.00 |
June | 486.30 | 131.85 | 516.10 | 61.54 | 454.56 | 0.00 | 0.00 |
July | 576.86 | 65.41 | 524.63 | 66.14 | 458.49 | 0.00 | 0.00 |
August | 665.21 | 95.70 | 624.34 | 176.10 | 448.24 | 0.00 | 0.00 |
September | 596.93 | 205.42 | 612.97 | 250.29 | 362.68 | 0.00 | 0.00 |
October | 776.60 | 399.06 | 803.61 | 441.88 | 361.73 | 0.00 | 0.00 |
November | 437.90 | 619.71 | 557.16 | 292.53 | 264.63 | 0.00 | 0.00 |
December | 412.67 | 756.99 | 531.80 | 343.41 | 188.40 | 0.00 | 0.00 |
Annual Sum or Average | 493.76 | 441.47 | 586.57 | 237.35 | 349.22 | 0.00 | 0.00 |
Minimum of Months | 340.83 | 65.41 | 502.96 | 61.54 | 188.40 | 0.00 | 0.00 |
Maximum of Months | 776.60 | 833.39 | 803.61 | 441.88 | 458.49 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.144204E+10 | 0.167085E+10 | 0.162619E+10 | 0.106714E+10 | 0.559054E+09 | 0.00 | 0.00 |
February | 0.169109E+10 | 0.152152E+10 | 0.194451E+10 | 0.129262E+10 | 0.651898E+09 | 0.00 | 0.00 |
March | 0.154357E+10 | 0.126061E+10 | 0.190736E+10 | 0.105026E+10 | 0.857099E+09 | 0.00 | 0.00 |
April | 0.104667E+10 | 0.890516E+09 | 0.146859E+10 | 0.594063E+09 | 0.874529E+09 | 0.00 | 0.00 |
May | 0.967209E+09 | 0.570655E+09 | 0.130332E+10 | 0.266668E+09 | 0.103665E+10 | 0.00 | 0.00 |
June | 0.110714E+10 | 0.276312E+09 | 0.119089E+10 | 0.183270E+09 | 0.100762E+10 | 0.00 | 0.00 |
July | 0.136662E+10 | 0.138643E+09 | 0.128048E+10 | 0.215929E+09 | 0.106455E+10 | 0.00 | 0.00 |
August | 0.174034E+10 | 0.213474E+09 | 0.171508E+10 | 0.632490E+09 | 0.108259E+10 | 0.00 | 0.00 |
September | 0.173674E+10 | 0.425740E+09 | 0.175199E+10 | 0.879741E+09 | 0.872245E+09 | 0.00 | 0.00 |
October | 0.264221E+10 | 0.847136E+09 | 0.255933E+10 | 0.160538E+10 | 0.953957E+09 | 0.00 | 0.00 |
November | 0.160544E+10 | 0.119473E+10 | 0.171439E+10 | 0.102849E+10 | 0.685893E+09 | 0.00 | 0.00 |
December | 0.165731E+10 | 0.153270E+10 | 0.175666E+10 | 0.124760E+10 | 0.509057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.185464E+11 | 0.105429E+11 | 0.202188E+11 | 0.100636E+11 | 0.101551E+11 | 0.00 | 0.00 |
Minimum of Months | 0.967209E+09 | 0.138643E+09 | 0.119089E+10 | 0.183270E+09 | 0.509057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.264221E+10 | 0.167085E+10 | 0.255933E+10 | 0.160538E+10 | 0.108259E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.398500E+10 | 0.504274E+10 | 0.457924E+10 | 0.300499E+10 | 0.157426E+10 | 0.00 | 0.00 |
February | 0.467449E+10 | 0.458271E+10 | 0.547562E+10 | 0.363992E+10 | 0.183570E+10 | 0.00 | 0.00 |
March | 0.426731E+10 | 0.383895E+10 | 0.537100E+10 | 0.295746E+10 | 0.241353E+10 | 0.00 | 0.00 |
April | 0.289180E+10 | 0.269910E+10 | 0.413546E+10 | 0.167284E+10 | 0.246262E+10 | 0.00 | 0.00 |
May | 0.269613E+10 | 0.168194E+10 | 0.367006E+10 | 0.750920E+09 | 0.291914E+10 | 0.00 | 0.00 |
June | 0.309747E+10 | 0.826469E+09 | 0.335345E+10 | 0.516075E+09 | 0.283738E+10 | 0.00 | 0.00 |
July | 0.381369E+10 | 0.443949E+09 | 0.360574E+10 | 0.608043E+09 | 0.299770E+10 | 0.00 | 0.00 |
August | 0.487686E+10 | 0.658874E+09 | 0.482956E+10 | 0.178105E+10 | 0.304851E+10 | 0.00 | 0.00 |
September | 0.487440E+10 | 0.126971E+10 | 0.493348E+10 | 0.247729E+10 | 0.245619E+10 | 0.00 | 0.00 |
October | 0.739106E+10 | 0.251738E+10 | 0.720691E+10 | 0.452063E+10 | 0.268628E+10 | 0.00 | 0.00 |
November | 0.444077E+10 | 0.362650E+10 | 0.482760E+10 | 0.289617E+10 | 0.193143E+10 | 0.00 | 0.00 |
December | 0.457887E+10 | 0.465962E+10 | 0.494664E+10 | 0.351317E+10 | 0.143347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.515879E+11 | 0.318479E+11 | 0.569348E+11 | 0.283386E+11 | 0.285962E+11 | 0.00 | 0.00 |
Minimum of Months | 0.269613E+10 | 0.443949E+09 | 0.335345E+10 | 0.516075E+09 | 0.143347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.739106E+10 | 0.504274E+10 | 0.720691E+10 | 0.452063E+10 | 0.304851E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.521668E+10 | 0.700866E+10 | 0.594870E+10 | 0.390365E+10 | 0.204505E+10 | 0.00 | 0.00 |
February | 0.614512E+10 | 0.630057E+10 | 0.711314E+10 | 0.472846E+10 | 0.238468E+10 | 0.00 | 0.00 |
March | 0.561667E+10 | 0.527766E+10 | 0.697723E+10 | 0.384192E+10 | 0.313532E+10 | 0.00 | 0.00 |
April | 0.379480E+10 | 0.373198E+10 | 0.537220E+10 | 0.217312E+10 | 0.319908E+10 | 0.00 | 0.00 |
May | 0.354537E+10 | 0.231914E+10 | 0.476761E+10 | 0.975488E+09 | 0.379212E+10 | 0.00 | 0.00 |
June | 0.411661E+10 | 0.112413E+10 | 0.435633E+10 | 0.670411E+09 | 0.368592E+10 | 0.00 | 0.00 |
July | 0.509845E+10 | 0.591663E+09 | 0.468407E+10 | 0.789882E+09 | 0.389418E+10 | 0.00 | 0.00 |
August | 0.653783E+10 | 0.853663E+09 | 0.627388E+10 | 0.231369E+10 | 0.396019E+10 | 0.00 | 0.00 |
September | 0.648849E+10 | 0.168566E+10 | 0.640887E+10 | 0.321815E+10 | 0.319072E+10 | 0.00 | 0.00 |
October | 0.983389E+10 | 0.333618E+10 | 0.936219E+10 | 0.587256E+10 | 0.348963E+10 | 0.00 | 0.00 |
November | 0.584469E+10 | 0.498732E+10 | 0.627133E+10 | 0.376229E+10 | 0.250904E+10 | 0.00 | 0.00 |
December | 0.602016E+10 | 0.644633E+10 | 0.642597E+10 | 0.456381E+10 | 0.186216E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.682588E+11 | 0.436630E+11 | 0.739615E+11 | 0.368134E+11 | 0.371481E+11 | 0.00 | 0.00 |
Minimum of Months | 0.354537E+10 | 0.591663E+09 | 0.435633E+10 | 0.670411E+09 | 0.186216E+10 | 0.00 | 0.00 |
Maximum of Months | 0.983389E+10 | 0.700866E+10 | 0.936219E+10 | 0.587256E+10 | 0.396019E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.352924E+09 | 0.969637E+09 | 0.559370E+09 | 0.308487E+09 | 0.250883E+09 | 0.00 | 0.00 |
February | 0.453969E+09 | 0.876577E+09 | 0.700088E+09 | 0.393915E+09 | 0.306173E+09 | 0.00 | 0.00 |
March | 0.683376E+09 | 0.667327E+09 | 0.896729E+09 | 0.448411E+09 | 0.448318E+09 | 0.00 | 0.00 |
April | 0.695309E+09 | 0.445579E+09 | 0.836693E+09 | 0.350949E+09 | 0.485744E+09 | 0.00 | 0.00 |
May | 0.887088E+09 | 0.250728E+09 | 0.917294E+09 | 0.303518E+09 | 0.613776E+09 | 0.00 | 0.00 |
June | 0.107441E+10 | 91173501.23 | 0.932950E+09 | 0.317799E+09 | 0.615151E+09 | 0.00 | 0.00 |
July | 0.119290E+10 | 22512988.67 | 0.927451E+09 | 0.296149E+09 | 0.631301E+09 | 0.00 | 0.00 |
August | 0.135840E+10 | 56162388.58 | 0.108505E+10 | 0.470007E+09 | 0.615040E+09 | 0.00 | 0.00 |
September | 0.946993E+09 | 0.159452E+09 | 0.859815E+09 | 0.398056E+09 | 0.461759E+09 | 0.00 | 0.00 |
October | 0.104395E+10 | 0.392131E+09 | 0.103209E+10 | 0.573533E+09 | 0.458556E+09 | 0.00 | 0.00 |
November | 0.426511E+09 | 0.639702E+09 | 0.578492E+09 | 0.273118E+09 | 0.305375E+09 | 0.00 | 0.00 |
December | 0.388818E+09 | 0.869703E+09 | 0.565894E+09 | 0.340843E+09 | 0.225051E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.950465E+10 | 0.544068E+10 | 0.989191E+10 | 0.447478E+10 | 0.541713E+10 | 0.00 | 0.00 |
Minimum of Months | 0.352924E+09 | 22512988.67 | 0.559370E+09 | 0.273118E+09 | 0.225051E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135840E+10 | 0.969637E+09 | 0.108505E+10 | 0.573533E+09 | 0.631301E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 94884029.85 | 0.103147E+10 | 0.300230E+09 | 97925523.83 | 0.202305E+09 | 0.00 | 0.00 |
February | 0.152949E+09 | 0.943900E+09 | 0.392709E+09 | 0.138864E+09 | 0.253845E+09 | 0.00 | 0.00 |
March | 0.408744E+09 | 0.671519E+09 | 0.637555E+09 | 0.241182E+09 | 0.396372E+09 | 0.00 | 0.00 |
April | 0.549081E+09 | 0.444178E+09 | 0.683373E+09 | 0.234288E+09 | 0.449085E+09 | 0.00 | 0.00 |
May | 0.818986E+09 | 0.251730E+09 | 0.847660E+09 | 0.257744E+09 | 0.589916E+09 | 0.00 | 0.00 |
June | 0.101561E+10 | 0.103916E+09 | 0.889425E+09 | 0.291798E+09 | 0.597627E+09 | 0.00 | 0.00 |
July | 0.111531E+10 | 34050952.41 | 0.866817E+09 | 0.261018E+09 | 0.605800E+09 | 0.00 | 0.00 |
August | 0.118521E+10 | 68753541.76 | 0.916453E+09 | 0.347449E+09 | 0.569004E+09 | 0.00 | 0.00 |
September | 0.694919E+09 | 0.171782E+09 | 0.637875E+09 | 0.224541E+09 | 0.413334E+09 | 0.00 | 0.00 |
October | 0.577736E+09 | 0.396733E+09 | 0.637675E+09 | 0.256769E+09 | 0.380906E+09 | 0.00 | 0.00 |
November | 0.134220E+09 | 0.663594E+09 | 0.315278E+09 | 70180947.51 | 0.245097E+09 | 0.00 | 0.00 |
December | 88297296.18 | 0.930386E+09 | 0.273126E+09 | 94672763.34 | 0.178453E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.683595E+10 | 0.571201E+10 | 0.739818E+10 | 0.251643E+10 | 0.488174E+10 | 0.00 | 0.00 |
Minimum of Months | 88297296.18 | 34050952.41 | 0.273126E+09 | 70180947.51 | 0.178453E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118521E+10 | 0.103147E+10 | 0.916453E+09 | 0.347449E+09 | 0.605800E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.233157E+09 | 0.251228E+09 | 0.256645E+09 | 0.168415E+09 | 88229912.29 | 0.00 | 0.00 |
February | 0.259653E+09 | 0.273215E+09 | 0.306883E+09 | 0.204001E+09 | 0.102882E+09 | 0.00 | 0.00 |
March | 0.234245E+09 | 0.242371E+09 | 0.301019E+09 | 0.165752E+09 | 0.135267E+09 | 0.00 | 0.00 |
April | 0.152935E+09 | 0.180256E+09 | 0.231773E+09 | 93755041.77 | 0.138018E+09 | 0.00 | 0.00 |
May | 0.134211E+09 | 0.123501E+09 | 0.205690E+09 | 42085570.78 | 0.163604E+09 | 0.00 | 0.00 |
June | 0.158190E+09 | 64971821.88 | 0.187945E+09 | 28923624.25 | 0.159022E+09 | 0.00 | 0.00 |
July | 0.201500E+09 | 37971736.72 | 0.202085E+09 | 34077953.05 | 0.168007E+09 | 0.00 | 0.00 |
August | 0.265950E+09 | 49662354.21 | 0.270674E+09 | 99819567.05 | 0.170855E+09 | 0.00 | 0.00 |
September | 0.262810E+09 | 93843547.74 | 0.276498E+09 | 0.138841E+09 | 0.137658E+09 | 0.00 | 0.00 |
October | 0.405057E+09 | 0.169725E+09 | 0.403914E+09 | 0.253360E+09 | 0.150554E+09 | 0.00 | 0.00 |
November | 0.239419E+09 | 0.235136E+09 | 0.270565E+09 | 0.162317E+09 | 0.108248E+09 | 0.00 | 0.00 |
December | 0.252764E+09 | 0.280916E+09 | 0.277236E+09 | 0.196897E+09 | 80339342.33 | 0.00 | 0.00 |
Annual Sum or Average | 0.279989E+10 | 0.200280E+10 | 0.319093E+10 | 0.158824E+10 | 0.160268E+10 | 0.00 | 0.00 |
Minimum of Months | 0.134211E+09 | 37971736.72 | 0.187945E+09 | 28923624.25 | 80339342.33 | 0.00 | 0.00 |
Maximum of Months | 0.405057E+09 | 0.280916E+09 | 0.403914E+09 | 0.253360E+09 | 0.170855E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 385938.49 | 0.316837E+09 | 49391170.92 | 0.00 | 49391170.92 | 0.00 | 0.00 |
February | 2162586.83 | 0.291888E+09 | 61048780.16 | 0.00 | 61048780.16 | 0.00 | 0.00 |
March | 21583953.55 | 0.206183E+09 | 93751937.54 | 1863.87 | 93750073.66 | 0.00 | 0.00 |
April | 56301044.97 | 0.130259E+09 | 0.109178E+09 | 445013.88 | 0.108733E+09 | 0.00 | 0.00 |
May | 0.122028E+09 | 68793610.14 | 0.150043E+09 | 5475613.50 | 0.144567E+09 | 0.00 | 0.00 |
June | 0.171152E+09 | 25746022.06 | 0.153183E+09 | 8129728.74 | 0.145053E+09 | 0.00 | 0.00 |
July | 0.208800E+09 | 7386789.98 | 0.153639E+09 | 5980273.24 | 0.147659E+09 | 0.00 | 0.00 |
August | 0.190174E+09 | 15774202.08 | 0.135871E+09 | 1793572.70 | 0.134077E+09 | 0.00 | 0.00 |
September | 0.101791E+09 | 46129648.29 | 99014499.97 | 56264.33 | 98958235.64 | 0.00 | 0.00 |
October | 57820928.65 | 0.112714E+09 | 88474560.91 | 0.00 | 88474560.91 | 0.00 | 0.00 |
November | 11130113.32 | 0.202107E+09 | 60054600.30 | 0.00 | 60054600.30 | 0.00 | 0.00 |
December | 415290.52 | 0.287187E+09 | 43082225.59 | 0.00 | 43082225.59 | 0.00 | 0.00 |
Annual Sum or Average | 0.943746E+09 | 0.171100E+10 | 0.119673E+10 | 21882330.26 | 0.117485E+10 | 0.00 | 0.00 |
Minimum of Months | 385938.49 | 7386789.98 | 43082225.59 | 0.00 | 43082225.59 | 0.00 | 0.00 |
Maximum of Months | 0.208800E+09 | 0.316837E+09 | 0.153639E+09 | 8129728.74 | 0.147659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.349047E+09 | 0.962471E+09 | 0.561038E+09 | 0.306531E+09 | 0.254507E+09 | 0.00 | 0.00 |
February | 0.470864E+09 | 0.862921E+09 | 0.720446E+09 | 0.411880E+09 | 0.308567E+09 | 0.00 | 0.00 |
March | 0.636192E+09 | 0.671718E+09 | 0.855136E+09 | 0.410712E+09 | 0.444424E+09 | 0.00 | 0.00 |
April | 0.689782E+09 | 0.433114E+09 | 0.844467E+09 | 0.360696E+09 | 0.483771E+09 | 0.00 | 0.00 |
May | 0.917263E+09 | 0.242855E+09 | 0.949060E+09 | 0.328311E+09 | 0.620749E+09 | 0.00 | 0.00 |
June | 0.976033E+09 | 86665337.49 | 0.856728E+09 | 0.261329E+09 | 0.595400E+09 | 0.00 | 0.00 |
July | 0.115644E+10 | 21073003.64 | 0.897094E+09 | 0.274576E+09 | 0.622518E+09 | 0.00 | 0.00 |
August | 0.133044E+10 | 52388666.98 | 0.106546E+10 | 0.452804E+09 | 0.612653E+09 | 0.00 | 0.00 |
September | 0.953529E+09 | 0.152903E+09 | 0.872065E+09 | 0.410735E+09 | 0.461330E+09 | 0.00 | 0.00 |
October | 0.989912E+09 | 0.383640E+09 | 0.996353E+09 | 0.539188E+09 | 0.457165E+09 | 0.00 | 0.00 |
November | 0.483406E+09 | 0.633325E+09 | 0.632796E+09 | 0.316127E+09 | 0.316669E+09 | 0.00 | 0.00 |
December | 0.404706E+09 | 0.861237E+09 | 0.584572E+09 | 0.358469E+09 | 0.226103E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.935762E+10 | 0.536431E+10 | 0.983521E+10 | 0.443136E+10 | 0.540386E+10 | 0.00 | 0.00 |
Minimum of Months | 0.349047E+09 | 21073003.64 | 0.561038E+09 | 0.261329E+09 | 0.226103E+09 | 0.00 | 0.00 |
Maximum of Months | 0.133044E+10 | 0.962471E+09 | 0.106546E+10 | 0.539188E+09 | 0.622518E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 79295444.69 | 0.101252E+10 | 0.301899E+09 | 95969669.36 | 0.205929E+09 | 0.00 | 0.00 |
February | 0.146451E+09 | 0.906159E+09 | 0.413067E+09 | 0.156828E+09 | 0.256239E+09 | 0.00 | 0.00 |
March | 0.357803E+09 | 0.671386E+09 | 0.595962E+09 | 0.203483E+09 | 0.392479E+09 | 0.00 | 0.00 |
April | 0.543805E+09 | 0.429836E+09 | 0.691147E+09 | 0.244035E+09 | 0.447112E+09 | 0.00 | 0.00 |
May | 0.853693E+09 | 0.243943E+09 | 0.879426E+09 | 0.282537E+09 | 0.596889E+09 | 0.00 | 0.00 |
June | 0.924191E+09 | 96761314.42 | 0.813203E+09 | 0.235328E+09 | 0.577876E+09 | 0.00 | 0.00 |
July | 0.108018E+10 | 30736477.25 | 0.836461E+09 | 0.239445E+09 | 0.597016E+09 | 0.00 | 0.00 |
August | 0.115712E+10 | 62223309.19 | 0.896863E+09 | 0.330246E+09 | 0.566617E+09 | 0.00 | 0.00 |
September | 0.702721E+09 | 0.161406E+09 | 0.650125E+09 | 0.237220E+09 | 0.412905E+09 | 0.00 | 0.00 |
October | 0.523237E+09 | 0.382342E+09 | 0.601938E+09 | 0.222425E+09 | 0.379514E+09 | 0.00 | 0.00 |
November | 0.177230E+09 | 0.643513E+09 | 0.369581E+09 | 0.113190E+09 | 0.256391E+09 | 0.00 | 0.00 |
December | 87635028.89 | 0.904893E+09 | 0.291803E+09 | 0.112299E+09 | 0.179505E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.663336E+10 | 0.554572E+10 | 0.734147E+10 | 0.247300E+10 | 0.486847E+10 | 0.00 | 0.00 |
Minimum of Months | 79295444.69 | 30736477.25 | 0.291803E+09 | 95969669.36 | 0.179505E+09 | 0.00 | 0.00 |
Maximum of Months | 0.115712E+10 | 0.101252E+10 | 0.896863E+09 | 0.330246E+09 | 0.597016E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.442587E+09 | 0.117667E+10 | 0.663077E+09 | 0.364909E+09 | 0.298168E+09 | 0.00 | 0.00 |
February | 0.533093E+09 | 0.107743E+10 | 0.797182E+09 | 0.442013E+09 | 0.355170E+09 | 0.00 | 0.00 |
March | 0.591371E+09 | 0.840121E+09 | 0.855323E+09 | 0.359143E+09 | 0.496181E+09 | 0.00 | 0.00 |
April | 0.521542E+09 | 0.543328E+09 | 0.738705E+09 | 0.204105E+09 | 0.534600E+09 | 0.00 | 0.00 |
May | 0.665018E+09 | 0.290335E+09 | 0.770715E+09 | 0.103050E+09 | 0.667666E+09 | 0.00 | 0.00 |
June | 0.815811E+09 | 0.114005E+09 | 0.739071E+09 | 80281168.88 | 0.658790E+09 | 0.00 | 0.00 |
July | 0.981413E+09 | 38654224.79 | 0.770696E+09 | 86792724.65 | 0.683903E+09 | 0.00 | 0.00 |
August | 0.106708E+10 | 82466606.47 | 0.880818E+09 | 0.220167E+09 | 0.660651E+09 | 0.00 | 0.00 |
September | 0.871550E+09 | 0.201570E+09 | 0.813594E+09 | 0.300951E+09 | 0.512643E+09 | 0.00 | 0.00 |
October | 0.108421E+10 | 0.471124E+09 | 0.106683E+10 | 0.548961E+09 | 0.517873E+09 | 0.00 | 0.00 |
November | 0.572411E+09 | 0.782433E+09 | 0.716337E+09 | 0.351696E+09 | 0.364641E+09 | 0.00 | 0.00 |
December | 0.518718E+09 | 0.106654E+10 | 0.694024E+09 | 0.426621E+09 | 0.267404E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.866480E+10 | 0.668467E+10 | 0.950638E+10 | 0.348869E+10 | 0.601769E+10 | 0.00 | 0.00 |
Minimum of Months | 0.442587E+09 | 38654224.79 | 0.663077E+09 | 80281168.88 | 0.267404E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108421E+10 | 0.117667E+10 | 0.106683E+10 | 0.548961E+09 | 0.683903E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.352121E+09 | 0.969160E+09 | 0.559829E+09 | 0.308740E+09 | 0.251089E+09 | 0.00 | 0.00 |
February | 0.452237E+09 | 0.876711E+09 | 0.700663E+09 | 0.394238E+09 | 0.306424E+09 | 0.00 | 0.00 |
March | 0.679367E+09 | 0.666655E+09 | 0.897465E+09 | 0.448779E+09 | 0.448686E+09 | 0.00 | 0.00 |
April | 0.689525E+09 | 0.445287E+09 | 0.837379E+09 | 0.351237E+09 | 0.486142E+09 | 0.00 | 0.00 |
May | 0.876066E+09 | 0.252218E+09 | 0.918047E+09 | 0.303767E+09 | 0.614280E+09 | 0.00 | 0.00 |
June | 0.106556E+10 | 91246947.76 | 0.933716E+09 | 0.318060E+09 | 0.615656E+09 | 0.00 | 0.00 |
July | 0.118635E+10 | 21838803.01 | 0.928211E+09 | 0.296392E+09 | 0.631819E+09 | 0.00 | 0.00 |
August | 0.135354E+10 | 54593874.58 | 0.108594E+10 | 0.470392E+09 | 0.615545E+09 | 0.00 | 0.00 |
September | 0.941174E+09 | 0.158660E+09 | 0.860520E+09 | 0.398383E+09 | 0.462137E+09 | 0.00 | 0.00 |
October | 0.103817E+10 | 0.390893E+09 | 0.103294E+10 | 0.574003E+09 | 0.458933E+09 | 0.00 | 0.00 |
November | 0.426133E+09 | 0.636168E+09 | 0.578967E+09 | 0.273342E+09 | 0.305625E+09 | 0.00 | 0.00 |
December | 0.389584E+09 | 0.866481E+09 | 0.566358E+09 | 0.341122E+09 | 0.225236E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.944983E+10 | 0.542991E+10 | 0.990003E+10 | 0.447846E+10 | 0.542157E+10 | 0.00 | 0.00 |
Minimum of Months | 0.352121E+09 | 21838803.01 | 0.559829E+09 | 0.273342E+09 | 0.225236E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135354E+10 | 0.969160E+09 | 0.108594E+10 | 0.574003E+09 | 0.631819E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 95286731.43 | 0.103102E+10 | 0.300477E+09 | 98005856.50 | 0.202471E+09 | 0.00 | 0.00 |
February | 0.153016E+09 | 0.944439E+09 | 0.393031E+09 | 0.138978E+09 | 0.254054E+09 | 0.00 | 0.00 |
March | 0.406559E+09 | 0.670187E+09 | 0.638078E+09 | 0.241380E+09 | 0.396698E+09 | 0.00 | 0.00 |
April | 0.542673E+09 | 0.444226E+09 | 0.683934E+09 | 0.234481E+09 | 0.449453E+09 | 0.00 | 0.00 |
May | 0.803620E+09 | 0.256666E+09 | 0.848355E+09 | 0.257955E+09 | 0.590400E+09 | 0.00 | 0.00 |
June | 0.100021E+10 | 0.110492E+09 | 0.890155E+09 | 0.292038E+09 | 0.598117E+09 | 0.00 | 0.00 |
July | 0.110290E+10 | 38115631.78 | 0.867528E+09 | 0.261232E+09 | 0.606297E+09 | 0.00 | 0.00 |
August | 0.117621E+10 | 72055420.01 | 0.917205E+09 | 0.347734E+09 | 0.569471E+09 | 0.00 | 0.00 |
September | 0.685941E+09 | 0.176292E+09 | 0.638398E+09 | 0.224725E+09 | 0.413673E+09 | 0.00 | 0.00 |
October | 0.573068E+09 | 0.396722E+09 | 0.638198E+09 | 0.256980E+09 | 0.381218E+09 | 0.00 | 0.00 |
November | 0.135289E+09 | 0.658610E+09 | 0.315536E+09 | 70238520.06 | 0.245298E+09 | 0.00 | 0.00 |
December | 89840705.55 | 0.925927E+09 | 0.273350E+09 | 94750427.63 | 0.178599E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.676461E+10 | 0.572476E+10 | 0.740425E+10 | 0.251850E+10 | 0.488575E+10 | 0.00 | 0.00 |
Minimum of Months | 89840705.55 | 38115631.78 | 0.273350E+09 | 70238520.06 | 0.178599E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117621E+10 | 0.103102E+10 | 0.917205E+09 | 0.347734E+09 | 0.606297E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.408937E+09 | 0.504519E+09 | 0.470973E+09 | 0.309061E+09 | 0.161912E+09 | 0.00 | 0.00 |
February | 0.480672E+09 | 0.459831E+09 | 0.563165E+09 | 0.374364E+09 | 0.188801E+09 | 0.00 | 0.00 |
March | 0.447477E+09 | 0.361292E+09 | 0.552405E+09 | 0.304174E+09 | 0.248231E+09 | 0.00 | 0.00 |
April | 0.315633E+09 | 0.237396E+09 | 0.425330E+09 | 0.172051E+09 | 0.253279E+09 | 0.00 | 0.00 |
May | 0.306277E+09 | 0.131959E+09 | 0.377464E+09 | 77231809.09 | 0.300232E+09 | 0.00 | 0.00 |
June | 0.361804E+09 | 44342307.65 | 0.344901E+09 | 53078140.20 | 0.291823E+09 | 0.00 | 0.00 |
July | 0.456309E+09 | 9371312.61 | 0.370849E+09 | 62536919.79 | 0.308312E+09 | 0.00 | 0.00 |
August | 0.569531E+09 | 25735438.11 | 0.496718E+09 | 0.183180E+09 | 0.313538E+09 | 0.00 | 0.00 |
September | 0.536131E+09 | 80907255.53 | 0.507406E+09 | 0.254789E+09 | 0.252618E+09 | 0.00 | 0.00 |
October | 0.786891E+09 | 0.203622E+09 | 0.741228E+09 | 0.464945E+09 | 0.276283E+09 | 0.00 | 0.00 |
November | 0.466642E+09 | 0.336561E+09 | 0.496517E+09 | 0.297870E+09 | 0.198647E+09 | 0.00 | 0.00 |
December | 0.475565E+09 | 0.451947E+09 | 0.508760E+09 | 0.361328E+09 | 0.147432E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.561187E+10 | 0.284748E+10 | 0.585572E+10 | 0.291461E+10 | 0.294111E+10 | 0.00 | 0.00 |
Minimum of Months | 0.306277E+09 | 9371312.61 | 0.344901E+09 | 53078140.20 | 0.147432E+09 | 0.00 | 0.00 |
Maximum of Months | 0.786891E+09 | 0.504519E+09 | 0.741228E+09 | 0.464945E+09 | 0.313538E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 56145.79 | 0.332946E+10 | 0.432454E+09 | 0.00 | 0.432454E+09 | 0.00 | 0.00 |
February | 3075957.87 | 0.305692E+10 | 0.534524E+09 | 0.00 | 0.534524E+09 | 0.00 | 0.00 |
March | 95748366.72 | 0.234799E+10 | 0.820863E+09 | 16319.47 | 0.820846E+09 | 0.00 | 0.00 |
April | 0.334432E+09 | 0.159380E+10 | 0.955930E+09 | 3896401.65 | 0.952033E+09 | 0.00 | 0.00 |
May | 0.818856E+09 | 0.927850E+09 | 0.131373E+10 | 47942751.02 | 0.126579E+10 | 0.00 | 0.00 |
June | 0.124517E+10 | 0.456963E+09 | 0.134122E+10 | 71181349.98 | 0.127004E+10 | 0.00 | 0.00 |
July | 0.151579E+10 | 0.262572E+09 | 0.134522E+10 | 52361393.11 | 0.129285E+10 | 0.00 | 0.00 |
August | 0.135130E+10 | 0.352967E+09 | 0.118964E+10 | 15703958.94 | 0.117394E+10 | 0.00 | 0.00 |
September | 0.706048E+09 | 0.706364E+09 | 0.866940E+09 | 492632.81 | 0.866447E+09 | 0.00 | 0.00 |
October | 0.348894E+09 | 0.142055E+10 | 0.774655E+09 | 0.00 | 0.774655E+09 | 0.00 | 0.00 |
November | 41605249.94 | 0.232510E+10 | 0.525819E+09 | 0.00 | 0.525819E+09 | 0.00 | 0.00 |
December | 325340.78 | 0.310946E+10 | 0.377214E+09 | 0.00 | 0.377214E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.646130E+10 | 0.198900E+11 | 0.104782E+11 | 0.191595E+09 | 0.102866E+11 | 0.00 | 0.00 |
Minimum of Months | 56145.79 | 0.262572E+09 | 0.377214E+09 | 0.00 | 0.377214E+09 | 0.00 | 0.00 |
Maximum of Months | 0.151579E+10 | 0.332946E+10 | 0.134522E+10 | 71181349.98 | 0.129285E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.350418E+10 | 0.432454E+09 | 0.00 | 0.432454E+09 | 0.00 | 0.00 |
February | 1116892.33 | 0.321202E+10 | 0.534524E+09 | 0.00 | 0.534524E+09 | 0.00 | 0.00 |
March | 75863082.48 | 0.248934E+10 | 0.820863E+09 | 16319.47 | 0.820846E+09 | 0.00 | 0.00 |
April | 0.298844E+09 | 0.169410E+10 | 0.955930E+09 | 3896401.65 | 0.952033E+09 | 0.00 | 0.00 |
May | 0.763200E+09 | 0.995417E+09 | 0.131373E+10 | 47942751.02 | 0.126579E+10 | 0.00 | 0.00 |
June | 0.118681E+10 | 0.503378E+09 | 0.134122E+10 | 71181349.98 | 0.127004E+10 | 0.00 | 0.00 |
July | 0.145776E+10 | 0.303337E+09 | 0.134522E+10 | 52361393.11 | 0.129285E+10 | 0.00 | 0.00 |
August | 0.129752E+10 | 0.397506E+09 | 0.118964E+10 | 15703958.94 | 0.117394E+10 | 0.00 | 0.00 |
September | 0.664542E+09 | 0.768701E+09 | 0.866940E+09 | 492632.81 | 0.866447E+09 | 0.00 | 0.00 |
October | 0.316604E+09 | 0.151003E+10 | 0.774655E+09 | 0.00 | 0.774655E+09 | 0.00 | 0.00 |
November | 32482922.44 | 0.246468E+10 | 0.525819E+09 | 0.00 | 0.525819E+09 | 0.00 | 0.00 |
December | 79718.54 | 0.328394E+10 | 0.377214E+09 | 0.00 | 0.377214E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.609483E+10 | 0.211266E+11 | 0.104782E+11 | 0.191595E+09 | 0.102866E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.303337E+09 | 0.377214E+09 | 0.00 | 0.377214E+09 | 0.00 | 0.00 |
Maximum of Months | 0.145776E+10 | 0.350418E+10 | 0.134522E+10 | 71181349.98 | 0.129285E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.319884E+09 | 0.251902E+10 | 0.863611E+09 | 0.402817E+09 | 0.460794E+09 | 0.00 | 0.00 |
February | 0.489507E+09 | 0.220729E+10 | 0.113440E+10 | 0.569152E+09 | 0.565244E+09 | 0.00 | 0.00 |
March | 0.871261E+09 | 0.188728E+10 | 0.145222E+10 | 0.614671E+09 | 0.837550E+09 | 0.00 | 0.00 |
April | 0.111504E+10 | 0.132951E+10 | 0.153679E+10 | 0.605192E+09 | 0.931603E+09 | 0.00 | 0.00 |
May | 0.165025E+10 | 0.855749E+09 | 0.182989E+10 | 0.611309E+09 | 0.121858E+10 | 0.00 | 0.00 |
June | 0.183571E+10 | 0.459955E+09 | 0.167121E+10 | 0.497032E+09 | 0.117418E+10 | 0.00 | 0.00 |
July | 0.217062E+10 | 0.270867E+09 | 0.173488E+10 | 0.514410E+09 | 0.122048E+10 | 0.00 | 0.00 |
August | 0.240843E+10 | 0.350168E+09 | 0.196383E+10 | 0.783646E+09 | 0.118018E+10 | 0.00 | 0.00 |
September | 0.160877E+10 | 0.625255E+09 | 0.152336E+10 | 0.648453E+09 | 0.874910E+09 | 0.00 | 0.00 |
October | 0.141928E+10 | 0.117794E+10 | 0.159953E+10 | 0.762206E+09 | 0.837327E+09 | 0.00 | 0.00 |
November | 0.553899E+09 | 0.180183E+10 | 0.100316E+10 | 0.429653E+09 | 0.573504E+09 | 0.00 | 0.00 |
December | 0.378341E+09 | 0.231811E+10 | 0.877060E+09 | 0.471138E+09 | 0.405923E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.148210E+11 | 0.158030E+11 | 0.171899E+11 | 0.690968E+10 | 0.102803E+11 | 0.00 | 0.00 |
Minimum of Months | 0.319884E+09 | 0.270867E+09 | 0.863611E+09 | 0.402817E+09 | 0.405923E+09 | 0.00 | 0.00 |
Maximum of Months | 0.240843E+10 | 0.251902E+10 | 0.196383E+10 | 0.783646E+09 | 0.122048E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.948849E+09 | 0.222779E+10 | 0.134713E+10 | 0.786732E+09 | 0.560401E+09 | 0.00 | 0.00 |
February | 0.113559E+10 | 0.201613E+10 | 0.161680E+10 | 0.952964E+09 | 0.663839E+09 | 0.00 | 0.00 |
March | 0.114968E+10 | 0.171395E+10 | 0.168757E+10 | 0.774297E+09 | 0.913273E+09 | 0.00 | 0.00 |
April | 0.883440E+09 | 0.121962E+10 | 0.141040E+10 | 0.439301E+09 | 0.971094E+09 | 0.00 | 0.00 |
May | 0.998789E+09 | 0.736336E+09 | 0.141120E+10 | 0.213033E+09 | 0.119817E+10 | 0.00 | 0.00 |
June | 0.126049E+10 | 0.341748E+09 | 0.133774E+10 | 0.159514E+09 | 0.117822E+10 | 0.00 | 0.00 |
July | 0.154506E+10 | 0.175207E+09 | 0.140516E+10 | 0.177141E+09 | 0.122802E+10 | 0.00 | 0.00 |
August | 0.178169E+10 | 0.256331E+09 | 0.167223E+10 | 0.471678E+09 | 0.120056E+10 | 0.00 | 0.00 |
September | 0.154725E+10 | 0.532440E+09 | 0.158882E+10 | 0.648747E+09 | 0.940071E+09 | 0.00 | 0.00 |
October | 0.208005E+10 | 0.106884E+10 | 0.215239E+10 | 0.118354E+10 | 0.968846E+09 | 0.00 | 0.00 |
November | 0.113503E+10 | 0.160630E+10 | 0.144416E+10 | 0.758245E+09 | 0.685917E+09 | 0.00 | 0.00 |
December | 0.110530E+10 | 0.202753E+10 | 0.142439E+10 | 0.919780E+09 | 0.504605E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.155712E+11 | 0.139222E+11 | 0.184980E+11 | 0.748497E+10 | 0.110130E+11 | 0.00 | 0.00 |
Minimum of Months | 0.883440E+09 | 0.175207E+09 | 0.133774E+10 | 0.159514E+09 | 0.504605E+09 | 0.00 | 0.00 |
Maximum of Months | 0.208005E+10 | 0.222779E+10 | 0.215239E+10 | 0.118354E+10 | 0.122802E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.6 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.5 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.46 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 7.99 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.30 | 9.14 | 4.42 | 7.76 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.07 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.75 | 20.26 | 4.06 | 17.38 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.83 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.95 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.02 | 7.95 | 4.86 | 2.63 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 5.00 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.97 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.51 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.5 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.75 | 20.26 | 5.65 | 17.38 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.34 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.33 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.37 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 17.98 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.26 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.29 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.20 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.31 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.52 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.56 | 8.50 | 3.60 | 6.14 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.63 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.34 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.26 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.4 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.2 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.4 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.56 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.34 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.46 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.1 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.4 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.2 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.98 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.69 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.42 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.95 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.09 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.83 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.56 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.75 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.09 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.69 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.95 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.16 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.56 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.419156E+11 | -.715481E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.142190E+10 | 59.01 | 0.00 | 0.00 |
February | 0.385770E+11 | -.652788E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.129516E+10 | 59.01 | 0.00 | 0.00 |
March | 0.410413E+11 | -.707113E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.144740E+10 | 59.03 | 0.00 | 0.00 |
April | 0.359048E+11 | -.648871E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.140808E+10 | 59.08 | 0.00 | 0.00 |
May | 0.320824E+11 | -.623833E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.146492E+10 | 59.15 | 0.00 | 0.00 |
June | 0.264615E+11 | -.561106E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.142359E+10 | 59.31 | 0.00 | 0.00 |
July | 0.240298E+11 | -.549051E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.147394E+10 | 59.44 | 0.00 | 0.00 |
August | 0.232214E+11 | -.541585E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.146950E+10 | 59.44 | 0.00 | 0.00 |
September | 0.241859E+11 | -.540158E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.140865E+10 | 59.41 | 0.00 | 0.00 |
October | 0.288678E+11 | -.594603E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.140613E+10 | 59.25 | 0.00 | 0.00 |
November | 0.327865E+11 | -.620673E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.133408E+10 | 59.16 | 0.00 | 0.00 |
December | 0.386406E+11 | -.685428E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.138845E+10 | 59.06 | 0.00 | 0.00 |
Annual Sum or Average | 0.387715E+12 | -.744069E+12 | 8760.00 | -.169418E+11 | 59.20 | |||||
Minimum of Months | 0.232214E+11 | -.715481E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.147394E+10 | 59.01 | 0.00 | 0.00 |
Maximum of Months | 0.419156E+11 | -.540158E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129516E+10 | 59.44 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.768763E+10 | -.754276E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -144872411.1 | 81.21 | 0.00 | 0.00 |
February | 0.694651E+10 | -.681595E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -130569122.2 | 81.21 | 0.00 | 0.00 |
March | 0.768600E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -143213803.9 | 81.21 | 0.00 | 0.00 |
April | 0.744736E+10 | -.730857E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -138787370.8 | 81.21 | 0.00 | 0.00 |
May | 0.768763E+10 | -.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -144855098.9 | 81.21 | 0.00 | 0.00 |
June | 0.744145E+10 | -.730050E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -140946890.6 | 81.21 | 0.00 | 0.00 |
July | 0.769546E+10 | -.755083E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -144624076.5 | 81.21 | 0.00 | 0.00 |
August | 0.768762E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -144829577.3 | 81.21 | 0.00 | 0.00 |
September | 0.744972E+10 | -.730857E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -141159343.4 | 81.21 | 0.00 | 0.00 |
October | 0.768701E+10 | -.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -144238645.8 | 81.21 | 0.00 | 0.00 |
November | 0.743130E+10 | -.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -138879661.8 | 81.21 | 0.00 | 0.00 |
December | 0.769483E+10 | -.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -143991833.5 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.905425E+11 | -.888416E+11 | 8760.00 | -.170097E+10 | 81.21 | |||||
Minimum of Months | 0.694651E+10 | -.755084E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -144872411.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.769546E+10 | -.681595E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -130569122.2 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.784905E+11 | -.773462E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.114432E+10 | 62.95 | 0.00 | 0.00 |
February | 0.709513E+11 | -.699151E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.103624E+10 | 62.75 | 0.00 | 0.00 |
March | 0.783925E+11 | -.772266E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.116593E+10 | 63.07 | 0.00 | 0.00 |
April | 0.756334E+11 | -.744767E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.115672E+10 | 63.91 | 0.00 | 0.00 |
May | 0.777993E+11 | -.765679E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.123138E+10 | 64.94 | 0.00 | 0.00 |
June | 0.748546E+11 | -.736350E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.121964E+10 | 65.91 | 0.00 | 0.00 |
July | 0.770436E+11 | -.757653E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.127829E+10 | 66.57 | 0.00 | 0.00 |
August | 0.769628E+11 | -.756828E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128003E+10 | 66.74 | 0.00 | 0.00 |
September | 0.745806E+11 | -.733613E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.121925E+10 | 66.37 | 0.00 | 0.00 |
October | 0.772589E+11 | -.760538E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.120509E+10 | 65.57 | 0.00 | 0.00 |
November | 0.752261E+11 | -.741051E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.112096E+10 | 64.59 | 0.00 | 0.00 |
December | 0.781730E+11 | -.770348E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.113814E+10 | 63.59 | 0.00 | 0.00 |
Annual Sum or Average | 0.915367E+12 | -.901171E+12 | 8760.00 | -.141960E+11 | 64.76 | |||||
Minimum of Months | 0.709513E+11 | -.773462E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.128003E+10 | 62.75 | 0.00 | 0.00 |
Maximum of Months | 0.784905E+11 | -.699151E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.103624E+10 | 66.74 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.87 | 0.86 | 01-JAN-07:49 | 5666.23 | 36.98 | 196.67 | 248.00 | 2706.87 | 33.77 | 187.50 | 189.50 |
February | 216.00 | 0.87 | 0.86 | 01-FEB-07:49 | 8296.62 | 37.60 | 208.33 | 259.83 | 1176.89 | 27.26 | 204.50 | 226.33 |
March | 275.00 | 0.87 | 0.86 | 01-MAR-06:00 | 4011.68 | 25.73 | 160.33 | 328.00 | 728.65 | 22.62 | 208.50 | 261.83 |
April | 261.17 | 0.87 | 0.86 | 01-APR-14:39 | 1427.81 | 20.42 | 75.17 | 344.83 | 582.27 | 22.17 | 201.17 | 279.83 |
May | 372.00 | 0.87 | 0.86 | 01-MAY-06:10 | 1291.97 | 20.14 | 105.67 | 396.67 | 513.28 | 21.87 | 241.50 | 318.33 |
June | 351.83 | 0.87 | 0.86 | 01-JUN-05:00 | 1225.13 | 20.04 | 80.67 | 387.17 | 494.67 | 21.80 | 247.00 | 320.33 |
July | 365.17 | 0.87 | 0.86 | 01-JUL-06:10 | 1366.03 | 20.21 | 109.33 | 396.17 | 541.27 | 21.95 | 264.83 | 324.00 |
August | 389.17 | 0.87 | 0.86 | 01-AUG-06:10 | 1462.72 | 20.49 | 143.33 | 375.17 | 592.31 | 22.22 | 306.67 | 323.83 |
September | 285.33 | 0.87 | 0.86 | 01-SEP-06:30 | 1627.73 | 20.60 | 89.83 | 328.17 | 657.59 | 22.38 | 235.33 | 275.17 |
October | 305.50 | 0.86 | 0.86 | 01-OCT-14:39 | 8257.61 | 35.99 | 283.00 | 309.83 | 1006.75 | 24.96 | 276.67 | 281.67 |
November | 240.83 | 0.87 | 0.86 | 01-NOV-06:49 | 5623.49 | 36.43 | 234.83 | 259.67 | 1495.20 | 29.89 | 223.00 | 229.33 |
December | 211.17 | 0.87 | 0.86 | 01-DEC-07:30 | 5261.19 | 37.97 | 207.83 | 247.83 | 4064.58 | 37.95 | 207.00 | 208.00 |
Annual Sum or Average | 3472.67 | 0.87 | 3406.83 | 26.34 | 1895.00 | 3881.33 | 1052.05 | 24.86 | 2803.67 | 3238.17 | ||
Minimum of Months | 199.50 | 0.86 | 0.86 | 1225.13 | 20.04 | 75.17 | 247.83 | 494.67 | 21.80 | 187.50 | 189.50 | |
Maximum of Months | 389.17 | 0.87 | 0.86 | 8296.62 | 37.97 | 283.00 | 396.67 | 4064.58 | 37.95 | 306.67 | 324.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.25 | 0.22 | 01-JAN-07:40 | 6098.38 | 37.05 | 197.00 | 260.00 | 3139.48 | 33.72 | 189.33 | 220.33 |
February | 216.00 | 0.24 | 0.22 | 01-FEB-07:40 | 8791.25 | 37.69 | 208.33 | 269.33 | 1670.88 | 26.92 | 192.67 | 246.33 |
March | 275.00 | 0.25 | 0.22 | 01-MAR-06:00 | 4415.86 | 25.86 | 149.83 | 336.83 | 1131.07 | 22.62 | 212.00 | 307.00 |
April | 261.17 | 0.25 | 0.22 | 01-APR-06:30 | 1740.12 | 20.72 | 82.50 | 357.83 | 893.69 | 22.31 | 234.33 | 319.83 |
May | 372.00 | 0.25 | 0.22 | 01-MAY-05:40 | 1516.55 | 20.72 | 142.83 | 411.67 | 736.98 | 22.26 | 268.17 | 371.33 |
June | 351.83 | 0.25 | 0.22 | 01-JUN-05:19 | 1439.87 | 20.64 | 145.33 | 404.50 | 708.60 | 22.20 | 274.67 | 361.17 |
July | 365.17 | 0.25 | 0.22 | 01-JUL-05:19 | 1594.74 | 20.79 | 159.00 | 413.50 | 769.03 | 22.35 | 291.83 | 366.83 |
August | 389.17 | 0.25 | 0.22 | 01-AUG-05:49 | 1751.16 | 20.86 | 173.00 | 384.50 | 879.79 | 22.43 | 317.17 | 357.67 |
September | 285.33 | 0.25 | 0.22 | 01-SEP-06:10 | 1988.56 | 20.77 | 100.00 | 340.00 | 1017.30 | 22.41 | 232.67 | 307.50 |
October | 305.50 | 0.24 | 0.22 | 01-OCT-14:39 | 8751.69 | 36.05 | 278.33 | 317.17 | 1499.11 | 24.78 | 283.00 | 299.67 |
November | 240.83 | 0.24 | 0.22 | 01-NOV-06:49 | 6026.44 | 36.50 | 235.00 | 267.83 | 1894.42 | 29.79 | 226.83 | 250.17 |
December | 211.17 | 0.25 | 0.22 | 01-DEC-07:30 | 5690.96 | 38.02 | 208.00 | 256.67 | 4492.28 | 37.95 | 204.67 | 233.17 |
Annual Sum or Average | 3472.67 | 0.25 | 3747.29 | 26.63 | 2079.17 | 4019.83 | 1391.28 | 24.98 | 2927.33 | 3641.00 | ||
Minimum of Months | 199.50 | 0.24 | 0.22 | 1439.87 | 20.64 | 82.50 | 256.67 | 708.60 | 22.20 | 189.33 | 220.33 | |
Maximum of Months | 389.17 | 0.25 | 0.22 | 8791.25 | 38.02 | 278.33 | 413.50 | 4492.28 | 37.95 | 317.17 | 371.33 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.60 | 01-JAN-08:39 | 428.19 | 15.12 | 0.00 | 231.00 | 206.50 | 18.53 | 0.00 | 113.83 |
February | 216.00 | 0.64 | 0.60 | 01-FEB-08:39 | 440.14 | 15.82 | 0.00 | 246.83 | 225.64 | 19.28 | 0.00 | 152.33 |
March | 275.00 | 0.62 | 0.60 | 01-MAR-07:19 | 603.44 | 17.17 | 0.00 | 325.17 | 291.00 | 20.42 | 23.50 | 240.00 |
April | 261.17 | 0.62 | 0.60 | 01-APR-14:39 | 664.85 | 17.76 | 0.00 | 355.33 | 320.63 | 20.99 | 80.17 | 299.00 |
May | 372.00 | 0.61 | 0.60 | 01-MAY-05:40 | 913.04 | 18.46 | 0.00 | 417.83 | 407.85 | 22.36 | 246.50 | 372.17 |
June | 351.83 | 0.61 | 0.60 | 01-JUN-04:00 | 1013.70 | 19.58 | 29.00 | 410.17 | 440.62 | 23.39 | 262.17 | 375.33 |
July | 365.17 | 0.61 | 0.60 | 01-JUL-04:00 | 1018.78 | 18.51 | 0.00 | 419.17 | 439.50 | 23.04 | 268.50 | 376.00 |
August | 389.17 | 0.62 | 0.60 | 01-AUG-05:40 | 807.50 | 18.21 | 0.00 | 387.50 | 373.65 | 21.43 | 218.83 | 355.50 |
September | 285.33 | 0.62 | 0.60 | 01-SEP-06:10 | 609.27 | 17.39 | 0.00 | 333.83 | 297.70 | 20.64 | 45.00 | 270.33 |
October | 305.50 | 0.62 | 0.60 | 01-OCT-14:39 | 551.11 | 16.94 | 0.00 | 301.83 | 282.38 | 20.31 | 0.00 | 244.33 |
November | 240.83 | 0.64 | 0.60 | 01-NOV-07:19 | 481.16 | 15.68 | 0.00 | 248.00 | 225.57 | 19.00 | 0.00 | 152.17 |
December | 211.17 | 0.67 | 0.60 | 01-DEC-08:50 | 339.08 | 14.22 | 0.00 | 218.83 | 170.43 | 17.79 | 0.00 | 69.17 |
Annual Sum or Average | 3472.67 | 0.62 | 700.43 | 17.37 | 29.00 | 3895.50 | 324.78 | 20.93 | 1144.67 | 3020.17 | ||
Minimum of Months | 199.50 | 0.61 | 0.60 | 339.08 | 14.22 | 0.00 | 218.83 | 170.43 | 17.79 | 0.00 | 69.17 | |
Maximum of Months | 389.17 | 0.67 | 0.60 | 1018.78 | 19.58 | 29.00 | 419.17 | 440.62 | 23.39 | 268.50 | 376.00 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.60 | 01-JAN-08:39 | 428.19 | 15.12 | 0.00 | 231.00 | 206.50 | 18.53 | 0.00 | 113.83 |
February | 216.00 | 0.64 | 0.60 | 01-FEB-08:39 | 440.14 | 15.82 | 0.00 | 246.83 | 225.64 | 19.28 | 0.00 | 152.33 |
March | 275.00 | 0.62 | 0.60 | 01-MAR-07:19 | 603.44 | 17.17 | 0.00 | 325.17 | 291.00 | 20.42 | 23.50 | 240.00 |
April | 261.17 | 0.62 | 0.60 | 01-APR-14:39 | 664.85 | 17.76 | 0.00 | 355.33 | 320.63 | 20.99 | 80.17 | 299.00 |
May | 372.00 | 0.61 | 0.60 | 01-MAY-05:40 | 913.04 | 18.46 | 0.00 | 417.83 | 407.85 | 22.36 | 246.50 | 372.17 |
June | 351.83 | 0.61 | 0.60 | 01-JUN-04:00 | 1013.70 | 19.58 | 29.00 | 410.17 | 440.62 | 23.39 | 262.17 | 375.33 |
July | 365.17 | 0.61 | 0.60 | 01-JUL-04:00 | 1018.78 | 18.51 | 0.00 | 419.17 | 439.50 | 23.04 | 268.50 | 376.00 |
August | 389.17 | 0.62 | 0.60 | 01-AUG-05:40 | 807.50 | 18.21 | 0.00 | 387.50 | 373.65 | 21.43 | 218.83 | 355.50 |
September | 285.33 | 0.62 | 0.60 | 01-SEP-06:10 | 609.27 | 17.39 | 0.00 | 333.83 | 297.70 | 20.64 | 45.00 | 270.33 |
October | 305.50 | 0.62 | 0.60 | 01-OCT-14:39 | 551.11 | 16.94 | 0.00 | 301.83 | 282.38 | 20.31 | 0.00 | 244.33 |
November | 240.83 | 0.64 | 0.60 | 01-NOV-07:19 | 481.16 | 15.68 | 0.00 | 248.00 | 225.57 | 19.00 | 0.00 | 152.17 |
December | 211.17 | 0.67 | 0.60 | 01-DEC-08:50 | 339.08 | 14.22 | 0.00 | 218.83 | 170.43 | 17.79 | 0.00 | 69.17 |
Annual Sum or Average | 3472.67 | 0.62 | 700.43 | 17.37 | 29.00 | 3895.50 | 324.78 | 20.93 | 1144.67 | 3020.17 | ||
Minimum of Months | 199.50 | 0.61 | 0.60 | 339.08 | 14.22 | 0.00 | 218.83 | 170.43 | 17.79 | 0.00 | 69.17 | |
Maximum of Months | 389.17 | 0.67 | 0.60 | 1018.78 | 19.58 | 29.00 | 419.17 | 440.62 | 23.39 | 268.50 | 376.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.801582E+09 | 2557.85 | 01-JAN-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.550666E+09 | 2495.76 | 06-FEB-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103288E+09 | 1520.77 | 18-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12284396.45 | 605.97 | 02-APR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 61528726.61 | 1411.98 | 23-NOV-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334748E+09 | 1775.09 | 11-DEC-14:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186410E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.801582E+09 | 2557.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 57274.25 | 190.91 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57274.25 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57274.25 | 190.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8995771.67 | 661.61 | 02-JAN-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8995771.67 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8995771.67 | 661.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160274E+09 | 1009.20 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95561919.32 | 792.57 | 06-FEB-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.255836E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160274E+09 | 1009.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186112E+09 | 7320.49 | 02-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 68752927.70 | 5009.92 | 06-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3983092.77 | 1551.15 | 17-MAR-12:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56111868.55 | 3245.02 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314960E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186112E+09 | 7320.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.499108E+10 | 6493.46 | 03-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.415033E+10 | 6492.08 | 28-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215664E+10 | 6490.56 | 17-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101506E+10 | 6439.58 | 21-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129169E+09 | 5660.91 | 11-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4281092.03 | 4533.31 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 923463.96 | 2915.89 | 12-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3050755.12 | 3708.73 | 28-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21863146.55 | 4922.28 | 23-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.253944E+09 | 5600.06 | 31-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232213E+10 | 6490.10 | 25-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.391869E+10 | 6491.71 | 11-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189672E+11 | |||||||
Minimum of Months | 923463.96 | 2915.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.499108E+10 | 6493.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.579912E+10 | 6473.19 | 03-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.512669E+10 | 6471.90 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262697E+10 | 6470.26 | 17-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113377E+10 | 6426.20 | 21-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130512E+09 | 5378.25 | 12-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2366061.85 | 3242.14 | 03-JUN-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 735747.78 | 1699.25 | 15-JUL-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1801004.12 | 3322.73 | 20-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23853290.55 | 5137.85 | 23-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.433675E+09 | 6243.05 | 31-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.294470E+10 | 6470.27 | 21-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.478925E+10 | 6471.42 | 11-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230135E+11 | |||||||
Minimum of Months | 735747.78 | 1699.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.579912E+10 | 6473.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 97770940.50 | 5057.05 | 16-JAN-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 97770940.50 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97770940.50 | 5057.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.187261E+11 | 36692.31 | 14-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184351E+11 | 36685.48 | 06-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.622058E+10 | 35775.28 | 16-MAR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111528E+10 | 34957.85 | 01-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18197872.47 | 23354.31 | 04-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3863510.25 | 16711.71 | 05-JUN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 281887.22 | 2090.54 | 03-JUL-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3555322.08 | 10696.80 | 30-AUG-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14614589.22 | 21168.49 | 19-SEP-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.340491E+09 | 34770.21 | 28-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.580875E+10 | 36008.51 | 24-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136331E+11 | 36230.03 | 31-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643199E+11 | |||||||
Minimum of Months | 281887.22 | 2090.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187261E+11 | 36692.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.496500E+10 | 6247.45 | 03-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.407089E+10 | 6246.01 | 28-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225120E+10 | 6244.44 | 17-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101227E+10 | 6197.99 | 21-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142759E+09 | 5910.12 | 01-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2503699.13 | 3372.27 | 08-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 509128.98 | 1847.85 | 24-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 111281.06 | 1854.68 | 06-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17567946.48 | 4078.16 | 23-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.278355E+09 | 5007.34 | 30-OCT-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.220934E+10 | 6243.96 | 25-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387890E+10 | 6245.63 | 11-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188294E+11 | |||||||
Minimum of Months | 111281.06 | 1847.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.496500E+10 | 6247.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.576799E+10 | 6245.37 | 03-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.502808E+10 | 6362.61 | 02-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275847E+10 | 6242.34 | 17-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113917E+10 | 6202.49 | 21-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149290E+09 | 5233.76 | 01-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1675850.23 | 2507.56 | 08-JUN-21:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 121689.47 | 912.45 | 05-JUL-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 421674.53 | 2094.12 | 24-AUG-21:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20104099.30 | 3322.43 | 17-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.463918E+09 | 6012.03 | 31-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276055E+10 | 6242.00 | 25-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.470753E+10 | 6332.02 | 02-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227973E+11 | |||||||
Minimum of Months | 121689.47 | 912.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.576799E+10 | 6362.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.999634E+10 | 8112.11 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.841634E+10 | 7903.73 | 06-FEB-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.616080E+10 | 7965.89 | 01-MAR-09:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.308506E+10 | 7866.80 | 22-APR-04:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.680228E+09 | 5765.02 | 08-MAY-16:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76683358.86 | 6596.57 | 27-SEP-02:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139609E+09 | 3721.34 | 29-OCT-06:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.576055E+10 | 8037.76 | 26-NOV-14:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.881660E+10 | 7888.63 | 10-DEC-15:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.431322E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.999634E+10 | 8112.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161878E+10 | 1880.93 | 24-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138065E+10 | 1880.26 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.748315E+09 | 1879.86 | 08-MAR-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.360949E+09 | 1880.24 | 21-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 50199178.72 | 1672.84 | 04-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1206252.81 | 989.92 | 06-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 196955.27 | 558.85 | 12-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 657584.29 | 958.70 | 10-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9961062.41 | 1500.42 | 10-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117948E+09 | 1814.24 | 31-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.815905E+09 | 1881.19 | 26-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133515E+10 | 1880.36 | 30-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.643992E+10 | |||||||
Minimum of Months | 196955.27 | 558.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161878E+10 | 1881.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186540E+10 | 1876.61 | 24-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167179E+10 | 1875.93 | 28-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.895280E+09 | 1876.06 | 05-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396716E+09 | 1875.91 | 21-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49608036.69 | 1769.54 | 04-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 479982.05 | 749.93 | 03-JUN-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 135213.79 | 422.69 | 15-JUL-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 308415.25 | 872.36 | 23-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10163955.63 | 1222.76 | 16-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.181044E+09 | 1836.45 | 29-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.101622E+10 | 1876.87 | 26-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160914E+10 | 1876.03 | 30-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769628E+10 | |||||||
Minimum of Months | 135213.79 | 422.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186540E+10 | 1876.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.480803E+10 | 8437.56 | 25-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359073E+10 | 8441.08 | 28-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207005E+10 | 8437.08 | 16-MAR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101268E+10 | 8338.72 | 21-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94018994.85 | 6069.43 | 02-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3612559.68 | 4110.11 | 06-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 678539.79 | 2233.77 | 12-JUL-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1723385.64 | 4523.73 | 25-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9557549.25 | 4222.82 | 12-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128683E+09 | 5563.93 | 09-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168295E+10 | 8286.65 | 28-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351231E+10 | 8439.65 | 23-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169150E+11 | |||||||
Minimum of Months | 678539.79 | 2233.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.480803E+10 | 8441.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110106E+10 | 4786.46 | 01-JAN-00:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.726848E+09 | 4670.47 | 06-FEB-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1267544.01 | 466.19 | 01-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30865119.34 | 1694.71 | 25-NOV-05:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 95317932.26 | 2428.16 | 31-DEC-23:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195535E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.110106E+10 | 4786.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114370E+11 | 101694.86 | 02-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136652E+11 | 109623.13 | 06-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.607820E+09 | 59960.96 | 06-MAR-19:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15455709.35 | 45774.97 | 30-APR-22:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151290E+09 | 66652.83 | 13-MAY-21:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37191144.50 | 22042.77 | 22-JUN-15:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15791559.46 | 13787.31 | 11-JUL-13:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.103805E+09 | 48878.79 | 30-AUG-13:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 36020083.53 | 26501.61 | 01-SEP-13:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20794121.03 | 58661.44 | 30-OCT-18:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223764E+09 | 28958.28 | 23-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.953406E+09 | 64650.54 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272675E+11 | |||||||
Minimum of Months | 15455709.35 | 13787.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136652E+11 | 109623.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153314E+10 | 5898.21 | 02-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168736E+10 | 6667.12 | 06-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123610E+09 | 1998.83 | 17-MAR-12:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11866.60 | 0.30 | 26-APR-09:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26506.54 | 0.31 | 22-MAY-16:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28553.79 | 0.31 | 06-JUN-21:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35468.64 | 0.31 | 09-JUL-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38995.80 | 50.80 | 08-AUG-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40498.05 | 31.88 | 12-SEP-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30312.21 | 24.19 | 12-OCT-08:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136635E+09 | 1720.31 | 24-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.193582E+09 | 3624.84 | 31-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367453E+10 | |||||||
Minimum of Months | 11866.60 | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168736E+10 | 6667.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 15582806.69 | 14625877.48 | 13854.00 | 17-JAN-16:11 | 13854.00 | 0.00 |
February | 0.00 | 0.00 | 47893373.55 | 47492645.64 | 13847.09 | 02-FEB-16:11 | 13847.09 | 0.00 |
March | 0.00 | 0.00 | 0.451736E+09 | 0.351451E+09 | 14312.95 | 27-MAR-16:01 | 12772.80 | 0.06 |
April | 0.00 | 0.00 | 0.134698E+10 | 0.814778E+09 | 14621.05 | 09-APR-08:61 | 10560.96 | 0.27 |
May | 0.00 | 0.00 | 0.312955E+10 | 0.169561E+10 | 15757.99 | 18-MAY-15:11 | 10088.58 | 0.60 |
June | 0.00 | 0.00 | 0.727541E+10 | 0.354279E+10 | 17688.04 | 18-JUN-08:61 | 8985.47 | 0.91 |
July | 0.00 | 0.00 | 0.101482E+11 | 0.506380E+10 | 17645.45 | 28-JUL-08:61 | 8902.97 | 0.97 |
August | 0.00 | 0.00 | 0.101329E+11 | 0.562789E+10 | 17194.08 | 27-AUG-08:61 | 9337.86 | 0.96 |
September | 0.00 | 0.00 | 0.549984E+10 | 0.268259E+10 | 18982.36 | 22-SEP-18:01 | 7720.06 | 0.83 |
October | 0.00 | 0.00 | 0.312584E+10 | 0.153529E+10 | 15814.57 | 24-OCT-08:61 | 8632.52 | 0.54 |
November | 0.00 | 0.00 | 0.191543E+09 | 0.106805E+09 | 13864.60 | 01-NOV-15:11 | 13864.60 | 0.08 |
December | 0.00 | 0.00 | 18826760.58 | 14937920.24 | 13665.12 | 17-DEC-16:11 | 13665.12 | 0.00 |
Annual Sum or Average | 0.413843E+11 | 0.214981E+11 | 0.44 | |||||
Minimum of Months | 0.00 | 0.00 | 15582806.69 | 14625877.48 | 13665.12 | 7720.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101482E+11 | 0.562789E+10 | 18982.36 | 13864.60 | 0.97 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2625883.70 | 2155067.35 | 9630.93 | 17-JAN-16:11 | 9630.93 | 0.00 |
February | 0.00 | 0.00 | 5827161.44 | 5619404.82 | 12551.67 | 20-FEB-16:11 | 12551.67 | 0.00 |
March | 0.00 | 0.00 | 0.198631E+09 | 0.158283E+09 | 13632.35 | 11-MAR-16:11 | 13632.35 | 0.03 |
April | 0.00 | 0.00 | 0.787354E+09 | 0.425882E+09 | 14381.24 | 09-APR-08:61 | 10321.97 | 0.20 |
May | 0.00 | 0.00 | 0.204313E+10 | 0.955828E+09 | 15821.01 | 31-MAY-21:11 | 11912.10 | 0.47 |
June | 0.00 | 0.00 | 0.487480E+10 | 0.236034E+10 | 19549.93 | 25-JUN-08:11 | 8530.45 | 0.63 |
July | 0.00 | 0.00 | 0.732580E+10 | 0.382787E+10 | 20976.64 | 22-JUL-08:11 | 8041.19 | 0.69 |
August | 0.00 | 0.00 | 0.737034E+10 | 0.411657E+10 | 19826.58 | 03-AUG-08:11 | 8808.16 | 0.71 |
September | 0.00 | 0.00 | 0.300605E+10 | 0.130384E+10 | 19004.18 | 14-SEP-08:11 | 7817.52 | 0.54 |
October | 0.00 | 0.00 | 0.109084E+10 | 0.414018E+09 | 15519.39 | 25-OCT-08:11 | 8618.62 | 0.30 |
November | 0.00 | 0.00 | 30497948.67 | 18722471.13 | 13017.73 | 01-NOV-15:11 | 13017.73 | 0.01 |
December | 0.00 | 0.00 | 1365093.22 | 973846.78 | 3420.24 | 17-DEC-16:11 | 3420.24 | 0.00 |
Annual Sum or Average | 0.267373E+11 | 0.135901E+11 | 0.30 | |||||
Minimum of Months | 0.00 | 0.00 | 1365093.22 | 973846.78 | 3420.24 | 3420.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.737034E+10 | 0.411657E+10 | 20976.64 | 13632.35 | 0.71 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 14737305.69 | 1482324.58 | 2607.75 | 03-FEB-12:31 | 378.49 | 0.01 |
March | 0.00 | 0.00 | 0.767806E+09 | 0.198722E+09 | 16907.33 | 28-MAR-12:21 | 5883.14 | 0.06 |
April | 0.00 | 0.00 | 0.577406E+10 | 0.229447E+10 | 33382.40 | 08-APR-12:01 | 23849.59 | 0.23 |
May | 0.00 | 0.00 | 0.157011E+11 | 0.486873E+10 | 26529.89 | 29-MAY-07:51 | 12493.69 | 0.66 |
June | 0.00 | 0.00 | 0.331794E+11 | 0.119821E+11 | 31173.26 | 19-JUN-17:11 | 19277.86 | 0.95 |
July | 0.00 | 0.00 | 0.470220E+11 | 0.192372E+11 | 35412.61 | 08-JUL-07:51 | 21192.14 | 0.99 |
August | 0.00 | 0.00 | 0.511592E+11 | 0.246361E+11 | 35999.80 | 16-AUG-12:21 | 24152.46 | 1.00 |
September | 0.00 | 0.00 | 0.377264E+11 | 0.180223E+11 | 42330.80 | 14-SEP-12:21 | 34360.67 | 0.93 |
October | 0.00 | 0.00 | 0.364045E+11 | 0.194372E+11 | 47180.26 | 04-OCT-12:10 | 34304.81 | 0.82 |
November | 0.00 | 0.00 | 0.734702E+10 | 0.351747E+10 | 40217.97 | 04-NOV-12:32 | 35354.87 | 0.25 |
December | 0.00 | 0.00 | 0.142572E+10 | 0.637065E+09 | 23586.17 | 20-DEC-09:51 | 12462.49 | 0.05 |
Annual Sum or Average | 0.236522E+12 | 0.104833E+12 | 0.50 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.511592E+11 | 0.246361E+11 | 47180.26 | 35354.87 | 1.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.307218E+09 | 0.103940E+09 | 73239.33 | 24-JAN-09:01 | 58077.70 | 0.03 |
February | 0.00 | 0.00 | 0.110843E+09 | 56503275.47 | 66569.08 | 25-FEB-09:01 | 66569.08 | 0.02 |
March | 0.00 | 0.00 | 0.271058E+10 | 0.116149E+10 | 74965.73 | 06-MAR-16:11 | 55965.51 | 0.19 |
April | 0.00 | 0.00 | 0.121664E+11 | 0.602007E+10 | 80992.13 | 30-APR-15:11 | 55966.31 | 0.42 |
May | 0.00 | 0.00 | 0.270681E+11 | 0.150085E+11 | 86978.56 | 31-MAY-21:11 | 65444.63 | 0.56 |
June | 0.00 | 0.00 | 0.407966E+11 | 0.247353E+11 | 109168.75 | 25-JUN-08:11 | 50270.53 | 0.56 |
July | 0.00 | 0.00 | 0.571522E+11 | 0.351763E+11 | 117581.55 | 22-JUL-08:11 | 45754.65 | 0.63 |
August | 0.00 | 0.00 | 0.525429E+11 | 0.325740E+11 | 110735.97 | 17-AUG-07:11 | 48909.30 | 0.64 |
September | 0.00 | 0.00 | 0.307728E+11 | 0.175216E+11 | 107299.09 | 14-SEP-08:11 | 45789.79 | 0.52 |
October | 0.00 | 0.00 | 0.157840E+11 | 0.731242E+10 | 86610.89 | 25-OCT-08:11 | 52203.18 | 0.43 |
November | 0.00 | 0.00 | 0.397455E+10 | 0.149607E+10 | 82193.64 | 10-NOV-09:01 | 55521.63 | 0.27 |
December | 0.00 | 0.00 | 0.251545E+09 | 0.118260E+09 | 70188.46 | 25-DEC-09:01 | 62299.72 | 0.03 |
Annual Sum or Average | 0.243638E+12 | 0.141284E+12 | 0.36 | |||||
Minimum of Months | 0.00 | 0.00 | 0.110843E+09 | 56503275.47 | 66569.08 | 45754.65 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.571522E+11 | 0.351763E+11 | 117581.55 | 66569.08 | 0.64 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 25305234.80 | 14802520.65 | 11186.05 | 20-JAN-09:01 | 11186.05 | 0.01 |
February | 0.00 | 0.00 | 48574693.73 | 36472759.66 | 12036.90 | 25-FEB-09:01 | 12036.90 | 0.01 |
March | 0.00 | 0.00 | 0.332862E+09 | 0.233454E+09 | 12433.35 | 15-MAR-15:11 | 12433.35 | 0.07 |
April | 0.00 | 0.00 | 0.132857E+10 | 0.741886E+09 | 12867.71 | 09-APR-08:61 | 10322.91 | 0.30 |
May | 0.00 | 0.00 | 0.325322E+10 | 0.176479E+10 | 14070.90 | 18-MAY-15:11 | 9321.56 | 0.64 |
June | 0.00 | 0.00 | 0.675461E+10 | 0.323738E+10 | 16221.39 | 18-JUN-08:61 | 7811.21 | 0.93 |
July | 0.00 | 0.00 | 0.996460E+10 | 0.496996E+10 | 15662.22 | 23-JUL-08:61 | 8210.50 | 0.98 |
August | 0.00 | 0.00 | 0.999738E+10 | 0.547167E+10 | 15321.59 | 06-AUG-08:61 | 8451.33 | 0.98 |
September | 0.00 | 0.00 | 0.549741E+10 | 0.272353E+10 | 17064.54 | 22-SEP-18:01 | 6881.37 | 0.86 |
October | 0.00 | 0.00 | 0.292139E+10 | 0.140719E+10 | 14552.54 | 24-OCT-08:61 | 9029.86 | 0.55 |
November | 0.00 | 0.00 | 0.296265E+09 | 0.154285E+09 | 13652.45 | 10-NOV-09:01 | 8088.14 | 0.09 |
December | 0.00 | 0.00 | 59815316.14 | 33339311.98 | 11470.67 | 02-DEC-09:01 | 11470.67 | 0.01 |
Annual Sum or Average | 0.404800E+11 | 0.207888E+11 | 0.45 | |||||
Minimum of Months | 0.00 | 0.00 | 25305234.80 | 14802520.65 | 11186.05 | 6881.37 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.999738E+10 | 0.547167E+10 | 17064.54 | 12433.35 | 0.98 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1135172.98 | 563197.25 | 3223.66 | 24-JAN-19:04 | 1192.86 | 0.00 |
February | 0.00 | 0.00 | 8602094.22 | 6518076.67 | 11462.82 | 25-FEB-09:01 | 11462.82 | 0.00 |
March | 0.00 | 0.00 | 0.148298E+09 | 91967030.71 | 11912.66 | 26-MAR-08:61 | 10978.94 | 0.03 |
April | 0.00 | 0.00 | 0.871874E+09 | 0.476021E+09 | 12852.63 | 09-APR-08:61 | 10202.56 | 0.22 |
May | 0.00 | 0.00 | 0.232963E+10 | 0.122502E+10 | 15735.75 | 31-MAY-08:11 | 12697.61 | 0.50 |
June | 0.00 | 0.00 | 0.467826E+10 | 0.229579E+10 | 18460.51 | 25-JUN-08:11 | 9587.73 | 0.64 |
July | 0.00 | 0.00 | 0.727246E+10 | 0.382841E+10 | 19202.39 | 22-JUL-08:11 | 7325.63 | 0.69 |
August | 0.00 | 0.00 | 0.733846E+10 | 0.409310E+10 | 18454.53 | 03-AUG-08:11 | 9995.19 | 0.72 |
September | 0.00 | 0.00 | 0.320176E+10 | 0.154344E+10 | 17228.77 | 14-SEP-08:11 | 7046.82 | 0.57 |
October | 0.00 | 0.00 | 0.111479E+10 | 0.487449E+09 | 14914.68 | 25-OCT-08:11 | 9302.22 | 0.30 |
November | 0.00 | 0.00 | 74195631.97 | 29760555.37 | 12049.23 | 11-NOV-09:01 | 9884.85 | 0.03 |
December | 0.00 | 0.00 | 3173484.17 | 2022611.39 | 8670.16 | 17-DEC-09:01 | 8670.16 | 0.00 |
Annual Sum or Average | 0.270427E+11 | 0.140801E+11 | 0.31 | |||||
Minimum of Months | 0.00 | 0.00 | 1135172.98 | 563197.25 | 3223.66 | 1192.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.733846E+10 | 0.409310E+10 | 19202.39 | 12697.61 | 0.72 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4752569.37 | 4598545.43 | 3648.32 | 17-JAN-16:11 | 3648.32 | 0.00 |
February | 0.00 | 0.00 | 13720907.73 | 13625196.40 | 3648.86 | 20-FEB-16:11 | 3648.86 | 0.00 |
March | 0.00 | 0.00 | 0.129084E+09 | 0.101003E+09 | 3775.70 | 27-MAR-16:01 | 3431.39 | 0.06 |
April | 0.00 | 0.00 | 0.390397E+09 | 0.246254E+09 | 3853.57 | 09-APR-08:61 | 2720.79 | 0.26 |
May | 0.00 | 0.00 | 0.924407E+09 | 0.540330E+09 | 4149.66 | 18-MAY-15:11 | 2709.37 | 0.60 |
June | 0.00 | 0.00 | 0.203183E+10 | 0.104004E+10 | 4729.78 | 18-JUN-08:61 | 2299.10 | 0.92 |
July | 0.00 | 0.00 | 0.278961E+10 | 0.144672E+10 | 4710.24 | 28-JUL-08:61 | 2284.16 | 0.97 |
August | 0.00 | 0.00 | 0.273865E+10 | 0.157497E+10 | 4623.03 | 27-AUG-08:61 | 2373.72 | 0.96 |
September | 0.00 | 0.00 | 0.148140E+10 | 0.758127E+09 | 5059.51 | 22-SEP-18:01 | 1993.25 | 0.82 |
October | 0.00 | 0.00 | 0.819085E+09 | 0.427279E+09 | 4158.40 | 25-OCT-08:61 | 2341.97 | 0.50 |
November | 0.00 | 0.00 | 45459190.29 | 27965364.87 | 3649.13 | 01-NOV-15:11 | 3649.13 | 0.06 |
December | 0.00 | 0.00 | 4197248.16 | 3878234.74 | 3639.80 | 17-DEC-16:11 | 3639.80 | 0.00 |
Annual Sum or Average | 0.113726E+11 | 0.618478E+10 | 0.43 | |||||
Minimum of Months | 0.00 | 0.00 | 4197248.16 | 3878234.74 | 3639.80 | 1993.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.278961E+10 | 0.157497E+10 | 5059.51 | 3649.13 | 0.97 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 312112.98 | 246495.67 | 1833.77 | 17-JAN-16:11 | 1833.77 | 0.00 |
February | 0.00 | 0.00 | 631585.59 | 604081.69 | 3149.80 | 20-FEB-16:11 | 3149.80 | 0.00 |
March | 0.00 | 0.00 | 50537855.10 | 39616859.33 | 3587.74 | 11-MAR-16:11 | 3587.74 | 0.03 |
April | 0.00 | 0.00 | 0.236166E+09 | 0.134580E+09 | 3894.06 | 09-APR-17:31 | 3894.06 | 0.19 |
May | 0.00 | 0.00 | 0.643774E+09 | 0.336964E+09 | 4357.93 | 31-MAY-21:11 | 3362.58 | 0.48 |
June | 0.00 | 0.00 | 0.145096E+10 | 0.762759E+09 | 5229.46 | 25-JUN-08:11 | 2256.81 | 0.64 |
July | 0.00 | 0.00 | 0.209493E+10 | 0.116759E+10 | 5622.91 | 22-JUL-08:11 | 2094.98 | 0.69 |
August | 0.00 | 0.00 | 0.207053E+10 | 0.121471E+10 | 5267.98 | 03-AUG-08:11 | 2368.26 | 0.71 |
September | 0.00 | 0.00 | 0.849653E+09 | 0.393622E+09 | 5052.92 | 14-SEP-08:11 | 2045.68 | 0.55 |
October | 0.00 | 0.00 | 0.284014E+09 | 0.111805E+09 | 4117.75 | 05-OCT-21:11 | 2680.22 | 0.28 |
November | 0.00 | 0.00 | 6836709.17 | 4414493.98 | 3369.57 | 01-NOV-15:11 | 3369.57 | 0.01 |
December | 0.00 | 0.00 | 288274.60 | 240915.41 | 1044.60 | 25-DEC-16:13 | 519.68 | 0.00 |
Annual Sum or Average | 0.768864E+10 | 0.416715E+10 | 0.30 | |||||
Minimum of Months | 0.00 | 0.00 | 288274.60 | 240915.41 | 1044.60 | 519.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.209493E+10 | 0.121471E+10 | 5622.91 | 3894.06 | 0.71 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.699795E+09 | 0.509698E+09 | 14736.64 | 31-JAN-16:11 | 14736.64 | 0.08 |
February | 0.00 | 0.00 | 0.920332E+09 | 0.693429E+09 | 14749.81 | 25-FEB-16:11 | 14749.81 | 0.11 |
March | 0.00 | 0.00 | 0.163419E+10 | 0.106848E+10 | 15228.81 | 04-MAR-09:01 | 10885.97 | 0.22 |
April | 0.00 | 0.00 | 0.245232E+10 | 0.135389E+10 | 17003.05 | 09-APR-08:61 | 10870.42 | 0.38 |
May | 0.00 | 0.00 | 0.454546E+10 | 0.224692E+10 | 17526.09 | 18-MAY-15:11 | 10237.99 | 0.71 |
June | 0.00 | 0.00 | 0.966212E+10 | 0.461648E+10 | 19853.24 | 18-JUN-08:61 | 8912.12 | 0.90 |
July | 0.00 | 0.00 | 0.144429E+11 | 0.741929E+10 | 19778.35 | 21-JUL-08:61 | 8998.41 | 0.97 |
August | 0.00 | 0.00 | 0.143680E+11 | 0.842141E+10 | 19340.43 | 16-AUG-08:61 | 9272.57 | 0.96 |
September | 0.00 | 0.00 | 0.980952E+10 | 0.550708E+10 | 21030.90 | 22-SEP-18:01 | 7830.52 | 0.88 |
October | 0.00 | 0.00 | 0.829389E+10 | 0.502680E+10 | 17656.14 | 05-OCT-18:01 | 10551.28 | 0.75 |
November | 0.00 | 0.00 | 0.205993E+10 | 0.120555E+10 | 16660.73 | 11-NOV-09:01 | 11250.37 | 0.31 |
December | 0.00 | 0.00 | 0.138793E+10 | 0.101573E+10 | 14751.13 | 15-DEC-16:11 | 14751.13 | 0.15 |
Annual Sum or Average | 0.702764E+11 | 0.390848E+11 | 0.54 | |||||
Minimum of Months | 0.00 | 0.00 | 0.699795E+09 | 0.509698E+09 | 14736.64 | 7830.52 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.144429E+11 | 0.842141E+10 | 21030.90 | 14751.13 | 0.97 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.278109E+10 | 0.253730E+10 | 236251.80 | 27-MAR-13:11 | 162379.70 | 0.01 |
April | 0.00 | 0.00 | 0.277150E+11 | 0.271700E+11 | 332799.56 | 09-APR-10:51 | 205062.32 | 0.09 |
May | 0.00 | 0.00 | 0.105657E+12 | 0.875468E+11 | 473384.86 | 31-MAY-17:11 | 247240.10 | 0.23 |
June | 0.00 | 0.00 | 0.446720E+12 | 0.244891E+12 | 757174.19 | 25-JUN-08:42 | 288947.27 | 0.47 |
July | 0.00 | 0.00 | 0.730089E+12 | 0.353911E+12 | 872142.07 | 20-JUL-18:22 | 336895.81 | 0.50 |
August | 0.00 | 0.00 | 0.584795E+12 | 0.349467E+12 | 889394.15 | 03-AUG-17:52 | 324579.60 | 0.50 |
September | 0.00 | 0.00 | 0.319281E+12 | 0.203377E+12 | 695359.22 | 14-SEP-10:40 | 288126.02 | 0.42 |
October | 0.00 | 0.00 | 0.113308E+12 | 0.683735E+11 | 473638.70 | 04-OCT-15:21 | 268220.38 | 0.22 |
November | 0.00 | 0.00 | 0.356229E+10 | 0.308653E+10 | 199245.54 | 10-NOV-08:05 | 74894.67 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.233391E+13 | 0.134036E+13 | 0.20 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.730089E+12 | 0.353911E+12 | 889394.15 | 336895.81 | 0.50 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.255549E+09 | 0.220960E+09 | 19163.40 | 27-MAR-12:51 | 12683.27 | 0.01 |
April | 0.00 | 0.00 | 0.203530E+10 | 0.199944E+10 | 18758.48 | 09-APR-12:03 | 13159.94 | 0.11 |
May | 0.00 | 0.00 | 0.856939E+10 | 0.713884E+10 | 31270.33 | 31-MAY-16:31 | 17129.59 | 0.31 |
June | 0.00 | 0.00 | 0.418372E+11 | 0.231086E+11 | 50430.65 | 25-JUN-08:61 | 19193.95 | 0.70 |
July | 0.00 | 0.00 | 0.608101E+11 | 0.321096E+11 | 52007.89 | 21-JUL-08:61 | 19395.82 | 0.76 |
August | 0.00 | 0.00 | 0.484433E+11 | 0.301825E+11 | 56281.59 | 05-AUG-18:02 | 18945.17 | 0.76 |
September | 0.00 | 0.00 | 0.284806E+11 | 0.184545E+11 | 47143.64 | 13-SEP-18:01 | 18735.81 | 0.62 |
October | 0.00 | 0.00 | 0.953549E+10 | 0.545277E+10 | 30380.78 | 05-OCT-15:15 | 15184.82 | 0.30 |
November | 0.00 | 0.00 | 0.195362E+09 | 0.168823E+09 | 6795.51 | 10-NOV-07:41 | 2456.62 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.200162E+12 | 0.118836E+12 | 0.30 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.608101E+11 | 0.321096E+11 | 56281.59 | 19395.82 | 0.76 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 28145.00 | 58061.61 | 31-JAN-07:48 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 28425.94 | 58140.49 | 08-FEB-07:19 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 27820.59 | 57697.38 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 26395.13 | 56108.25 | 10-APR-06:01 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 24562.42 | 54615.59 | 19-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 22716.66 | 49066.03 | 01-JUN-05:51 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 21402.61 | 45227.66 | 03-JUL-06:31 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 21119.78 | 47371.11 | 28-AUG-06:02 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 21776.94 | 47914.26 | 27-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 23346.57 | 49773.76 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 25203.87 | 53579.71 | 10-NOV-07:02 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 26970.16 | 56359.68 | 29-DEC-07:17 |
Annual Sum or Average | 0.00 | 24802.97 | ||||
Minimum of Months | 0.00 | 0.00 | 21119.78 | 45227.66 | ||
Maximum of Months | 0.00 | 0.00 | 28425.94 | 58140.49 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.13 | 203.95 | 19-JAN-14:32 | 26596.74 | 179116.72 | 02-JAN-09:02 |
February | 28.86 | 9098.48 | 02-FEB-16:10 | 27370.12 | 190465.16 | 06-FEB-09:02 |
March | 7.73 | 4317.83 | 13-MAR-15:10 | 9332.60 | 87986.26 | 16-MAR-15:14 |
April | 3.16 | 2085.28 | 03-APR-18:00 | 3657.85 | 40397.88 | 21-APR-15:14 |
May | 0.83 | 1273.16 | 15-MAY-06:00 | 545.83 | 64112.65 | 13-MAY-23:03 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 24.17 | 29460.99 | 05-JUN-08:15 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 7.25 | 8171.35 | 03-JUL-08:20 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 39.53 | 41420.58 | 30-AUG-13:54 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 99.32 | 28534.76 | 10-SEP-08:16 |
October | 4.94 | 2903.23 | 26-OCT-21:10 | 774.42 | 39088.65 | 30-OCT-20:33 |
November | 2.78 | 1710.49 | 29-NOV-14:02 | 9400.79 | 77526.93 | 23-NOV-06:20 |
December | 16.26 | 5714.59 | 02-DEC-15:32 | 16981.70 | 121355.65 | 31-DEC-23:10 |
Annual Sum or Average | 5.24 | 7793.01 | ||||
Minimum of Months | 0.00 | 0.00 | 7.25 | 8171.35 | ||
Maximum of Months | 28.86 | 9098.48 | 27370.12 | 190465.16 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 607.26 | 38537.15 | 24-JAN-19:01 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 788.36 | 46591.75 | 19-FEB-09:02 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 4096.59 | 246719.26 | 27-MAR-13:07 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 22214.64 | 357285.60 | 07-APR-16:21 | 0.00 | 0.00 | 01-APR-00:01 |
May | 66287.91 | 592451.69 | 31-MAY-08:11 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 232672.73 | 1012198.20 | 25-JUN-08:14 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 356957.78 | 1163653.31 | 20-JUL-20:14 | 0.00 | 0.00 | 01-JUL-00:02 |
August | 298305.35 | 1155358.87 | 03-AUG-21:14 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 173364.87 | 881310.08 | 14-SEP-08:12 | 0.00 | 0.00 | 01-SEP-00:01 |
October | 73267.11 | 569719.51 | 04-OCT-15:21 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 7549.85 | 221572.06 | 10-NOV-09:01 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 1485.52 | 39531.11 | 25-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 103910.60 | 0.00 | ||||
Minimum of Months | 607.26 | 38537.15 | 0.00 | 0.00 | ||
Maximum of Months | 356957.78 | 1163653.31 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261252E+10 | 0.67 | 1298.89 | 01-JAN-09:01 | 0.88 |
February | 0.235970E+10 | 0.67 | 1298.89 | 01-FEB-09:01 | 0.88 |
March | 0.261252E+10 | 0.67 | 1298.89 | 01-MAR-09:01 | 0.88 |
April | 0.252825E+10 | 0.67 | 1298.89 | 01-APR-08:61 | 0.88 |
May | 0.261252E+10 | 0.67 | 1298.89 | 01-MAY-15:11 | 0.88 |
June | 0.252825E+10 | 0.67 | 1298.89 | 01-JUN-08:11 | 0.87 |
July | 0.261252E+10 | 0.67 | 1298.89 | 01-JUL-08:11 | 0.87 |
August | 0.261252E+10 | 0.67 | 1298.89 | 01-AUG-08:11 | 0.87 |
September | 0.252825E+10 | 0.67 | 1298.89 | 01-SEP-08:11 | 0.87 |
October | 0.261252E+10 | 0.67 | 1298.89 | 01-OCT-08:61 | 0.87 |
November | 0.252825E+10 | 0.67 | 1298.89 | 01-NOV-08:61 | 0.88 |
December | 0.261252E+10 | 0.67 | 1298.89 | 01-DEC-09:02 | 0.88 |
Annual Sum or Average | 0.307604E+11 | 0.67 | |||
Minimum of Months | 0.235970E+10 | 0.67 | 1298.89 | 0.87 | |
Maximum of Months | 0.261252E+10 | 0.67 | 1298.89 | 0.88 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.446980E+11 | 0.79 | 40211.89 | 19-JAN-20:02 | 1.78 |
February | 0.415080E+11 | 0.80 | 40128.27 | 24-FEB-21:52 | 1.78 |
March | 0.483719E+11 | 0.83 | 42430.98 | 29-MAR-14:42 | 1.84 |
April | 0.469486E+11 | 0.83 | 42579.26 | 06-APR-22:22 | 1.83 |
May | 0.478707E+11 | 0.82 | 42579.26 | 05-MAY-18:28 | 1.83 |
June | 0.471409E+11 | 0.83 | 42579.26 | 01-JUN-00:42 | 1.83 |
July | 0.513421E+11 | 0.85 | 42579.26 | 01-JUL-00:22 | 1.83 |
August | 0.529271E+11 | 0.88 | 42579.26 | 01-AUG-05:02 | 1.83 |
September | 0.505020E+11 | 0.87 | 42579.26 | 01-SEP-05:02 | 1.83 |
October | 0.534383E+11 | 0.88 | 42579.26 | 02-OCT-14:22 | 1.83 |
November | 0.482128E+11 | 0.84 | 42579.26 | 01-NOV-11:52 | 1.85 |
December | 0.476819E+11 | 0.82 | 40528.50 | 20-DEC-09:52 | 1.79 |
Annual Sum or Average | 0.580642E+12 | 0.84 | |||
Minimum of Months | 0.415080E+11 | 0.79 | 40128.27 | 1.78 | |
Maximum of Months | 0.534383E+11 | 0.88 | 42579.26 | 1.85 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:05 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:01 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:01 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:01 | 0.26 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:01 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:01 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:02 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:01 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:01 | 0.26 |
October | 0.205205E+09 | 0.26 | 76.61 | 01-OCT-00:01 | 0.26 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:01 | 0.26 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:01 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:01 | 0.26 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:01 | 0.26 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:01 | 0.26 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:01 | 0.26 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:01 | 0.26 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:01 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:01 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:01 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:01 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:01 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:01 | 0.26 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:01 | 0.26 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.26 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.363774E+09 | 0.44 | 678.15 | 01-JAN-09:01 | 0.58 |
February | 0.306343E+09 | 0.43 | 678.15 | 01-FEB-09:01 | 0.57 |
March | 0.205009E+09 | 0.41 | 678.15 | 01-MAR-09:01 | 0.57 |
April | 0.162421E+09 | 0.42 | 678.15 | 01-APR-08:61 | 0.57 |
May | 0.168696E+09 | 0.45 | 678.15 | 01-MAY-15:11 | 0.58 |
June | 0.294601E+09 | 0.52 | 678.15 | 01-JUN-08:61 | 0.57 |
July | 0.387463E+09 | 0.55 | 678.15 | 01-JUL-08:61 | 0.57 |
August | 0.411709E+09 | 0.55 | 678.15 | 01-AUG-08:61 | 0.57 |
September | 0.235433E+09 | 0.51 | 678.15 | 01-SEP-08:61 | 0.57 |
October | 0.168074E+09 | 0.47 | 678.15 | 01-OCT-08:61 | 0.57 |
November | 0.199022E+09 | 0.40 | 678.15 | 01-NOV-08:61 | 0.57 |
December | 0.288426E+09 | 0.42 | 678.15 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.319097E+10 | 0.47 | |||
Minimum of Months | 0.162421E+09 | 0.40 | 678.15 | 0.57 | |
Maximum of Months | 0.411709E+09 | 0.55 | 678.15 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.422809E+09 | 0.48 | 667.08 | 01-JAN-09:01 | 0.58 |
February | 0.371349E+09 | 0.47 | 667.08 | 01-FEB-09:01 | 0.57 |
March | 0.219104E+09 | 0.40 | 667.08 | 01-MAR-09:01 | 0.57 |
April | 0.143410E+09 | 0.39 | 667.08 | 01-APR-08:61 | 0.57 |
May | 0.115455E+09 | 0.36 | 667.08 | 01-MAY-15:11 | 0.58 |
June | 0.194258E+09 | 0.36 | 667.08 | 01-JUN-08:11 | 0.57 |
July | 0.281485E+09 | 0.39 | 667.08 | 01-JUL-08:11 | 0.57 |
August | 0.296620E+09 | 0.41 | 667.08 | 01-AUG-08:11 | 0.57 |
September | 0.127474E+09 | 0.33 | 667.08 | 01-SEP-08:11 | 0.57 |
October | 97502259.17 | 0.35 | 667.08 | 01-OCT-08:61 | 0.57 |
November | 0.227403E+09 | 0.40 | 667.08 | 01-NOV-08:61 | 0.57 |
December | 0.333660E+09 | 0.46 | 667.08 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.283053E+10 | 0.40 | |||
Minimum of Months | 97502259.17 | 0.33 | 667.08 | 0.57 | |
Maximum of Months | 0.422809E+09 | 0.48 | 667.08 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 11225213.74 | 0.01 | 443.80 | 16-JAN-05:51 | 0.58 |
February | 1226852.55 | 0.00 | 164.55 | 03-FEB-12:31 | 0.57 |
March | 32392156.98 | 0.03 | 625.04 | 15-MAR-15:03 | 0.58 |
April | 0.199020E+09 | 0.14 | 944.92 | 08-APR-12:21 | 0.57 |
May | 0.537056E+09 | 0.38 | 705.47 | 22-MAY-15:03 | 0.57 |
June | 0.101106E+10 | 0.55 | 854.45 | 19-JUN-17:11 | 0.57 |
July | 0.135257E+10 | 0.57 | 899.34 | 08-JUL-07:51 | 0.57 |
August | 0.150360E+10 | 0.57 | 979.95 | 30-AUG-12:21 | 0.57 |
September | 0.116419E+10 | 0.53 | 1615.12 | 28-SEP-12:11 | 0.57 |
October | 0.119560E+10 | 0.47 | 1749.62 | 04-OCT-12:10 | 0.57 |
November | 0.253422E+09 | 0.14 | 1635.33 | 02-NOV-12:11 | 0.57 |
December | 51076227.12 | 0.03 | 745.82 | 21-DEC-13:21 | 0.57 |
Annual Sum or Average | 0.731243E+10 | 0.29 | |||
Minimum of Months | 1226852.55 | 0.00 | 164.55 | 0.57 | |
Maximum of Months | 0.150360E+10 | 0.57 | 1749.62 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143317E+10 | 0.39 | 3717.10 | 01-JAN-09:01 | 0.58 |
February | 0.140044E+10 | 0.39 | 3717.10 | 01-FEB-09:01 | 0.57 |
March | 0.745759E+09 | 0.39 | 3717.10 | 01-MAR-09:01 | 0.57 |
April | 0.693568E+09 | 0.37 | 3717.10 | 01-APR-08:61 | 0.57 |
May | 0.113954E+10 | 0.33 | 3717.10 | 01-MAY-08:61 | 0.57 |
June | 0.167404E+10 | 0.32 | 3717.10 | 01-JUN-08:11 | 0.57 |
July | 0.238874E+10 | 0.36 | 3717.10 | 01-JUL-08:11 | 0.57 |
August | 0.219083E+10 | 0.37 | 3717.10 | 01-AUG-08:11 | 0.57 |
September | 0.124057E+10 | 0.30 | 3717.10 | 01-SEP-08:11 | 0.57 |
October | 0.712131E+09 | 0.32 | 3717.10 | 01-OCT-08:61 | 0.57 |
November | 0.726406E+09 | 0.39 | 3717.10 | 01-NOV-08:61 | 0.57 |
December | 0.113139E+10 | 0.39 | 3717.10 | 01-DEC-16:11 | 0.58 |
Annual Sum or Average | 0.154766E+11 | 0.36 | |||
Minimum of Months | 0.693568E+09 | 0.30 | 3717.10 | 0.57 | |
Maximum of Months | 0.238874E+10 | 0.39 | 3717.10 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.346059E+09 | 0.44 | 607.16 | 01-JAN-09:01 | 0.58 |
February | 0.283503E+09 | 0.43 | 607.16 | 01-FEB-16:11 | 0.58 |
March | 0.189472E+09 | 0.40 | 607.16 | 01-MAR-09:01 | 0.57 |
April | 0.151090E+09 | 0.43 | 607.16 | 01-APR-08:61 | 0.57 |
May | 0.169477E+09 | 0.48 | 607.16 | 01-MAY-08:61 | 0.57 |
June | 0.266759E+09 | 0.53 | 607.16 | 01-JUN-08:61 | 0.57 |
July | 0.377039E+09 | 0.56 | 607.16 | 01-JUL-08:61 | 0.57 |
August | 0.401824E+09 | 0.56 | 607.16 | 01-AUG-08:61 | 0.57 |
September | 0.228984E+09 | 0.52 | 607.16 | 01-SEP-08:61 | 0.57 |
October | 0.157278E+09 | 0.48 | 607.16 | 01-OCT-08:61 | 0.57 |
November | 0.181604E+09 | 0.40 | 607.16 | 01-NOV-08:61 | 0.57 |
December | 0.266451E+09 | 0.42 | 607.16 | 01-DEC-16:11 | 0.58 |
Annual Sum or Average | 0.301954E+10 | 0.47 | |||
Minimum of Months | 0.151090E+09 | 0.40 | 607.16 | 0.57 | |
Maximum of Months | 0.401824E+09 | 0.56 | 607.16 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.410209E+09 | 0.48 | 603.02 | 01-JAN-09:01 | 0.58 |
February | 0.351871E+09 | 0.47 | 603.02 | 01-FEB-09:01 | 0.57 |
March | 0.208767E+09 | 0.40 | 603.02 | 01-MAR-09:01 | 0.57 |
April | 0.138771E+09 | 0.40 | 603.02 | 01-APR-08:61 | 0.57 |
May | 0.129194E+09 | 0.38 | 603.02 | 01-MAY-08:61 | 0.57 |
June | 0.192712E+09 | 0.37 | 603.02 | 01-JUN-08:11 | 0.57 |
July | 0.286133E+09 | 0.40 | 603.02 | 01-JUL-08:11 | 0.57 |
August | 0.302849E+09 | 0.41 | 603.02 | 01-AUG-08:11 | 0.57 |
September | 0.139804E+09 | 0.35 | 603.02 | 01-SEP-08:11 | 0.57 |
October | 97114235.87 | 0.35 | 603.02 | 01-OCT-08:61 | 0.57 |
November | 0.203650E+09 | 0.40 | 603.02 | 01-NOV-08:61 | 0.57 |
December | 0.308843E+09 | 0.46 | 603.02 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.276992E+10 | 0.41 | |||
Minimum of Months | 97114235.87 | 0.35 | 603.02 | 0.57 | |
Maximum of Months | 0.410209E+09 | 0.48 | 603.02 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110585E+09 | 0.47 | 178.70 | 01-JAN-09:01 | 0.58 |
February | 94427499.15 | 0.46 | 178.70 | 01-FEB-09:01 | 0.57 |
March | 61467475.90 | 0.42 | 178.70 | 01-MAR-09:01 | 0.57 |
April | 48874626.18 | 0.43 | 178.70 | 01-APR-08:61 | 0.57 |
May | 51026414.01 | 0.47 | 178.70 | 01-MAY-15:11 | 0.58 |
June | 83902894.21 | 0.53 | 178.70 | 01-JUN-08:61 | 0.57 |
July | 0.108422E+09 | 0.56 | 178.70 | 01-JUL-08:61 | 0.57 |
August | 0.113475E+09 | 0.55 | 178.70 | 01-AUG-08:61 | 0.57 |
September | 64408057.75 | 0.51 | 178.70 | 01-SEP-08:61 | 0.57 |
October | 47896124.76 | 0.47 | 178.70 | 01-OCT-08:61 | 0.57 |
November | 60231875.80 | 0.41 | 178.70 | 01-NOV-08:61 | 0.57 |
December | 87543778.31 | 0.45 | 178.70 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.932260E+09 | 0.48 | |||
Minimum of Months | 47896124.76 | 0.41 | 178.70 | 0.57 | |
Maximum of Months | 0.113475E+09 | 0.56 | 178.70 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129571E+09 | 0.52 | 175.76 | 01-JAN-09:01 | 0.58 |
February | 0.116124E+09 | 0.50 | 175.76 | 01-FEB-09:01 | 0.57 |
March | 65086761.58 | 0.42 | 175.76 | 01-MAR-09:01 | 0.57 |
April | 43150761.75 | 0.40 | 175.76 | 01-APR-08:61 | 0.57 |
May | 36366602.63 | 0.38 | 175.76 | 01-MAY-15:11 | 0.58 |
June | 59076251.19 | 0.37 | 175.76 | 01-JUN-08:11 | 0.57 |
July | 82874227.96 | 0.39 | 175.76 | 01-JUL-08:11 | 0.57 |
August | 85119004.57 | 0.41 | 175.76 | 01-AUG-08:11 | 0.57 |
September | 36478965.86 | 0.34 | 175.76 | 01-SEP-08:11 | 0.57 |
October | 29347531.27 | 0.36 | 175.76 | 01-OCT-08:61 | 0.57 |
November | 70393304.90 | 0.43 | 175.76 | 01-NOV-08:61 | 0.57 |
December | 0.101287E+09 | 0.50 | 175.76 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.854875E+09 | 0.42 | |||
Minimum of Months | 29347531.27 | 0.34 | 175.76 | 0.57 | |
Maximum of Months | 0.129571E+09 | 0.52 | 175.76 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.336861E+09 | 0.44 | 715.74 | 01-JAN-16:11 | 0.58 |
February | 0.272831E+09 | 0.46 | 715.74 | 01-FEB-16:11 | 0.57 |
March | 0.226985E+09 | 0.44 | 715.74 | 01-MAR-09:01 | 0.57 |
April | 0.190023E+09 | 0.44 | 715.74 | 01-APR-08:61 | 0.57 |
May | 0.208291E+09 | 0.47 | 715.74 | 01-MAY-08:61 | 0.57 |
June | 0.369090E+09 | 0.52 | 715.74 | 01-JUN-08:61 | 0.57 |
July | 0.538859E+09 | 0.55 | 715.74 | 01-JUL-08:61 | 0.57 |
August | 0.565707E+09 | 0.55 | 715.74 | 01-AUG-08:61 | 0.57 |
September | 0.390942E+09 | 0.52 | 715.74 | 01-SEP-08:61 | 0.57 |
October | 0.360678E+09 | 0.51 | 715.74 | 01-OCT-08:61 | 0.57 |
November | 0.217699E+09 | 0.44 | 715.74 | 01-NOV-08:61 | 0.57 |
December | 0.294207E+09 | 0.45 | 715.74 | 01-DEC-09:01 | 0.57 |
Annual Sum or Average | 0.397217E+10 | 0.48 | |||
Minimum of Months | 0.190023E+09 | 0.44 | 715.74 | 0.57 | |
Maximum of Months | 0.565707E+09 | 0.55 | 715.74 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.288057E+10 | 0.261844E+10 | 1881.08 | 02-JAN-02:42 | 1709.90 | 1709.90 | 52.95 | 5.56 |
February | 0.266972E+10 | 0.242678E+10 | 1874.58 | 06-FEB-05:30 | 1703.99 | 1703.99 | 54.31 | 5.47 |
March | 0.190008E+10 | 0.172717E+10 | 1761.58 | 23-MAR-04:00 | 1601.27 | 1601.27 | 57.03 | 4.28 |
April | 0.892482E+09 | 0.811266E+09 | 1620.99 | 01-APR-04:10 | 1473.48 | 1473.48 | 57.69 | 3.41 |
May | 0.119098E+09 | 0.108260E+09 | 1310.04 | 01-MAY-05:00 | 1190.82 | 1190.82 | 58.49 | 2.28 |
June | 1225679.09 | 1114142.30 | 456.23 | 05-JUN-08:15 | 414.71 | 414.71 | 48.33 | 0.60 |
July | 327965.10 | 298120.28 | 142.90 | 03-JUL-08:20 | 129.90 | 129.90 | 48.94 | 0.18 |
August | 1473997.89 | 1339864.08 | 494.90 | 30-AUG-13:54 | 449.86 | 449.86 | 45.03 | 0.66 |
September | 11710487.31 | 10644832.97 | 520.56 | 19-SEP-08:14 | 473.19 | 473.19 | 52.45 | 0.70 |
October | 0.309605E+09 | 0.281431E+09 | 1515.63 | 29-OCT-04:00 | 1377.71 | 1377.71 | 58.22 | 2.95 |
November | 0.154457E+10 | 0.140401E+10 | 1760.65 | 24-NOV-06:00 | 1600.43 | 1600.43 | 56.71 | 4.27 |
December | 0.256188E+10 | 0.232875E+10 | 1809.39 | 31-DEC-19:02 | 1644.74 | 1644.74 | 55.24 | 4.71 |
Annual Sum or Average | 0.128927E+11 | 0.117195E+11 | ||||||
Minimum of Months | 327965.10 | 298120.28 | 142.90 | 129.90 | 129.90 | 45.03 | 0.18 | |
Maximum of Months | 0.288057E+10 | 0.261844E+10 | 1881.08 | 1709.90 | 1709.90 | 58.49 | 5.56 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 358999.46 | 326330.51 | 28.29 | 20-JAN-09:01 | 25.71 | 25.71 | 6.71 | 2.32 |
February | 399547.33 | 363188.52 | 39.09 | 20-FEB-09:02 | 35.53 | 35.53 | 6.71 | 2.78 |
March | 4755787.80 | 4323011.11 | 201.35 | 27-MAR-16:27 | 183.03 | 183.03 | 6.71 | 6.39 |
April | 44337183.96 | 40302500.22 | 751.81 | 07-APR-12:01 | 683.40 | 683.40 | 6.71 | 11.59 |
May | 0.152558E+09 | 0.138675E+09 | 1359.23 | 31-MAY-08:41 | 1235.54 | 1235.54 | 6.71 | 14.90 |
June | 0.902422E+09 | 0.820302E+09 | 3201.26 | 25-JUN-08:16 | 2909.95 | 2909.95 | 7.44 | 21.13 |
July | 0.181082E+10 | 0.164604E+10 | 3942.87 | 20-JUL-20:14 | 3584.07 | 3584.07 | 8.11 | 22.95 |
August | 0.142950E+10 | 0.129941E+10 | 3814.91 | 16-AUG-21:14 | 3467.76 | 3467.76 | 8.06 | 22.66 |
September | 0.627723E+09 | 0.570600E+09 | 2416.92 | 14-SEP-08:12 | 2196.98 | 2196.98 | 6.77 | 18.88 |
October | 0.184494E+09 | 0.167705E+09 | 1341.57 | 04-OCT-15:11 | 1219.49 | 1219.49 | 6.71 | 14.82 |
November | 8943543.64 | 8129681.17 | 243.19 | 04-NOV-11:11 | 221.06 | 221.06 | 6.71 | 6.99 |
December | 1105735.99 | 1005114.01 | 39.49 | 20-DEC-09:01 | 35.90 | 35.90 | 6.71 | 2.79 |
Annual Sum or Average | 0.516742E+10 | 0.469718E+10 | ||||||
Minimum of Months | 358999.46 | 326330.51 | 28.29 | 25.71 | 25.71 | 6.71 | 2.32 | |
Maximum of Months | 0.181082E+10 | 0.164604E+10 | 3942.87 | 3584.07 | 3584.07 | 8.11 | 22.95 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 48.09 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:01 | 14.37 | 14.37 | 43.54 | 0.08 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:01 | 14.37 | 14.37 | 43.66 | 0.08 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:01 | 14.37 | 14.37 | 48.72 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:01 | 14.37 | 14.37 | 49.78 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:01 | 14.37 | 14.37 | 46.71 | 0.06 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:02 | 14.37 | 14.37 | 49.29 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:01 | 14.37 | 14.37 | 50.16 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:01 | 14.37 | 14.37 | 50.98 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:01 | 14.37 | 14.37 | 48.09 | 0.06 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:01 | 14.37 | 14.37 | 50.72 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:01 | 14.37 | 14.37 | 48.63 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 43.54 | 0.06 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 50.98 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.629527E+09 | 0.572240E+09 | 1550.25 | 01-JAN-09:02 | 1409.18 | 1409.18 | 6.76 | 24.55 |
February | 0.805233E+09 | 0.731957E+09 | 1550.25 | 01-FEB-09:01 | 1409.18 | 1409.18 | 6.75 | 24.55 |
March | 0.166200E+10 | 0.151075E+10 | 1550.25 | 01-MAR-07:11 | 1409.18 | 1409.18 | 6.73 | 24.55 |
April | 0.270473E+10 | 0.245860E+10 | 1550.25 | 01-APR-08:61 | 1409.18 | 1409.18 | 6.95 | 24.55 |
May | 0.401529E+10 | 0.364990E+10 | 1550.25 | 01-MAY-00:01 | 1409.18 | 1409.18 | 6.77 | 24.55 |
June | 0.401826E+10 | 0.365260E+10 | 1550.25 | 01-JUN-00:01 | 1409.18 | 1409.18 | 7.74 | 24.55 |
July | 0.415220E+10 | 0.377435E+10 | 1550.25 | 01-JUL-00:02 | 1409.18 | 1409.18 | 11.04 | 24.55 |
August | 0.415220E+10 | 0.377435E+10 | 1550.25 | 01-AUG-00:01 | 1409.18 | 1409.18 | 8.05 | 24.55 |
September | 0.401674E+10 | 0.365122E+10 | 1550.25 | 01-SEP-00:01 | 1409.18 | 1409.18 | 8.14 | 24.55 |
October | 0.386832E+10 | 0.351630E+10 | 1550.25 | 01-OCT-00:01 | 1409.18 | 1409.18 | 6.91 | 24.55 |
November | 0.195662E+10 | 0.177857E+10 | 1550.25 | 01-NOV-00:01 | 1409.18 | 1409.18 | 6.73 | 24.55 |
December | 0.913689E+09 | 0.830543E+09 | 1550.25 | 01-DEC-07:01 | 1409.18 | 1409.18 | 6.72 | 24.55 |
Annual Sum or Average | 0.328948E+11 | 0.299014E+11 | ||||||
Minimum of Months | 0.629527E+09 | 0.572240E+09 | 1550.25 | 1409.18 | 1409.18 | 6.72 | 24.55 | |
Maximum of Months | 0.415220E+10 | 0.377435E+10 | 1550.25 | 1409.18 | 1409.18 | 11.04 | 24.55 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 48.09 | 59.90 | 28145.00 | 58061.61 | 31-JAN-07:48 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 43.54 | 59.48 | 28425.94 | 58140.49 | 08-FEB-07:19 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 43.66 | 59.52 | 27820.59 | 57697.38 | 01-MAR-07:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 48.72 | 59.43 | 26395.13 | 56108.25 | 10-APR-06:01 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 49.78 | 58.21 | 24562.42 | 54615.59 | 19-MAY-06:02 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 46.71 | 58.38 | 22716.66 | 49066.03 | 01-JUN-05:51 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 49.29 | 58.98 | 21402.61 | 45227.66 | 03-JUL-06:31 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.16 | 58.35 | 21119.78 | 47371.11 | 28-AUG-06:02 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.98 | 59.50 | 21776.94 | 47914.26 | 27-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 48.09 | 58.57 | 23346.57 | 49773.76 | 31-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.72 | 58.51 | 25203.87 | 53579.71 | 10-NOV-07:02 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 48.63 | 59.13 | 26970.16 | 56359.68 | 29-DEC-07:17 |
Annual Sum or Average | 0.00 | 24802.97 | ||||||
Minimum of Months | 0.00 | 0.00 | 43.54 | 58.21 | 21119.78 | 45227.66 | ||
Maximum of Months | 0.00 | 0.00 | 50.98 | 59.90 | 28425.94 | 58140.49 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.13 | 203.95 | 19-JAN-14:32 | 60.03 | 60.03 | 26596.74 | 179116.72 | 02-JAN-09:02 |
February | 28.86 | 9098.48 | 02-FEB-16:10 | 60.95 | 60.95 | 27370.12 | 190465.16 | 06-FEB-09:02 |
March | 7.73 | 4317.83 | 13-MAR-15:10 | 60.57 | 60.57 | 9332.60 | 87986.26 | 16-MAR-15:14 |
April | 3.16 | 2085.28 | 03-APR-18:00 | 60.27 | 60.27 | 3657.85 | 40397.88 | 21-APR-15:14 |
May | 0.83 | 1273.16 | 15-MAY-06:00 | 60.23 | 60.23 | 545.83 | 64112.65 | 13-MAY-23:03 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 45.91 | 45.91 | 24.17 | 29460.99 | 05-JUN-08:15 |
July | 0.00 | 0.00 | 01-JUL-00:02 | 48.70 | 48.70 | 7.25 | 8171.35 | 03-JUL-08:20 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 48.84 | 48.84 | 39.53 | 41420.58 | 30-AUG-13:54 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 45.41 | 45.41 | 99.32 | 28534.76 | 10-SEP-08:16 |
October | 4.94 | 2903.23 | 26-OCT-21:10 | 60.46 | 60.46 | 774.42 | 39088.65 | 30-OCT-20:33 |
November | 2.78 | 1710.49 | 29-NOV-14:02 | 60.30 | 60.30 | 9400.79 | 77526.93 | 23-NOV-06:20 |
December | 16.26 | 5714.59 | 02-DEC-15:32 | 60.73 | 60.73 | 16981.70 | 121355.65 | 31-DEC-23:10 |
Annual Sum or Average | 5.24 | 7793.01 | ||||||
Minimum of Months | 0.00 | 0.00 | 45.41 | 45.41 | 7.25 | 8171.35 | ||
Maximum of Months | 28.86 | 9098.48 | 60.95 | 60.95 | 27370.12 | 190465.16 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 607.26 | 38537.15 | 24-JAN-19:01 | 7.07 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 788.36 | 46591.75 | 19-FEB-09:02 | 7.15 | 6.70 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 4096.59 | 246719.26 | 27-MAR-13:07 | 9.10 | 6.70 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 22214.64 | 357285.60 | 07-APR-16:21 | 10.17 | 6.70 | 0.00 | 0.00 | 01-APR-00:01 |
May | 66287.91 | 592451.69 | 31-MAY-08:11 | 12.46 | 6.70 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 232672.73 | 1012198.20 | 25-JUN-08:14 | 16.55 | 8.19 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 356957.78 | 1163653.31 | 20-JUL-20:14 | 18.03 | 9.67 | 0.00 | 0.00 | 01-JUL-00:02 |
August | 298305.35 | 1155358.87 | 03-AUG-21:14 | 17.95 | 9.59 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 173364.87 | 881310.08 | 14-SEP-08:12 | 15.28 | 6.92 | 0.00 | 0.00 | 01-SEP-00:01 |
October | 73267.11 | 569719.51 | 04-OCT-15:21 | 12.24 | 6.70 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 7549.85 | 221572.06 | 10-NOV-09:01 | 8.85 | 6.70 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 1485.52 | 39531.11 | 25-DEC-09:02 | 7.08 | 6.70 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 103910.60 | 0.00 | ||||||
Minimum of Months | 607.26 | 38537.15 | 7.07 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 356957.78 | 1163653.31 | 18.03 | 9.67 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.06 | 74.55 |
September | 0.17 | 88.75 |
October | 0.17 | 95.85 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.39 | 89.76 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 95.85 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 7.58 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.13 | 5.26 |
May | 0.02 | 2.17 |
June | 0.30 | 6.93 |
July | 0.11 | 8.02 |
August | 2.86 | 9.28 |
September | 0.93 | 7.83 |
October | 0.72 | 5.36 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 5.13 | 8.15 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.86 | 9.28 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.10 | 11.29 |
May | 0.00 | 0.00 |
June | 0.07 | 9.89 |
July | 0.08 | 11.29 |
August | 0.52 | 10.01 |
September | 0.35 | 10.28 |
October | 0.21 | 11.29 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 10.45 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.52 | 11.29 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 742.50 | 4.80 |
February | 670.75 | 4.81 |
March | 741.10 | 4.82 |
April | 707.84 | 4.82 |
May | 713.35 | 4.82 |
June | 694.40 | 4.80 |
July | 739.22 | 4.80 |
August | 723.37 | 4.81 |
September | 687.03 | 4.81 |
October | 721.92 | 4.82 |
November | 715.73 | 4.81 |
December | 742.65 | 4.80 |
Annual Sum or Average | 8599.87 | 4.81 |
Minimum of Months | 670.75 | 4.80 |
Maximum of Months | 742.65 | 4.82 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.45 | 38.30 |
April | 9.24 | 84.90 |
May | 16.79 | 114.78 |
June | 135.67 | 116.48 |
July | 284.33 | 111.59 |
August | 320.95 | 100.01 |
September | 142.21 | 101.14 |
October | 53.79 | 66.42 |
November | 2.84 | 36.27 |
December | 1.02 | 41.06 |
Annual Sum or Average | 967.29 | 103.86 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 320.95 | 116.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 295.70 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.17 | 288.21 |
May | 0.16 | 295.70 |
June | 0.53 | 262.06 |
July | 0.12 | 323.87 |
August | 0.46 | 308.94 |
September | 0.87 | 331.22 |
October | 0.44 | 345.21 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 2.81 | 311.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.87 | 345.21 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.02 | 0.80 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.02 | 0.80 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.02 | 0.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.06 | 0.63 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.02 | 0.45 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.08 | 0.59 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.06 | 0.63 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 164.69 | 209.20 |
February | 157.47 | 209.09 |
March | 337.85 | 197.47 |
April | 462.36 | 170.10 |
May | 542.51 | 152.47 |
June | 599.57 | 144.62 |
July | 712.45 | 143.18 |
August | 648.04 | 145.46 |
September | 548.68 | 147.42 |
October | 475.03 | 164.17 |
November | 344.72 | 190.37 |
December | 257.12 | 209.08 |
Annual Sum or Average | 5250.48 | 163.17 |
Minimum of Months | 157.47 | 143.18 |
Maximum of Months | 712.45 | 209.20 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 435.77 | 180.50 |
February | 418.12 | 181.26 |
March | 614.15 | 156.89 |
April | 637.55 | 147.58 |
May | 598.60 | 148.16 |
June | 620.27 | 144.05 |
July | 722.13 | 142.87 |
August | 663.35 | 145.00 |
September | 579.51 | 146.32 |
October | 617.60 | 148.77 |
November | 574.41 | 158.69 |
December | 517.73 | 173.96 |
Annual Sum or Average | 6999.19 | 154.33 |
Minimum of Months | 418.12 | 142.87 |
Maximum of Months | 722.13 | 181.26 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 743.65 | 12.72 |
February | 672.00 | 12.73 |
March | 742.58 | 12.77 |
April | 707.24 | 12.78 |
May | 713.06 | 12.78 |
June | 696.51 | 12.76 |
July | 740.71 | 12.71 |
August | 725.35 | 12.78 |
September | 687.61 | 12.77 |
October | 719.61 | 12.79 |
November | 716.01 | 12.74 |
December | 744.00 | 12.72 |
Annual Sum or Average | 8608.34 | 12.76 |
Minimum of Months | 672.00 | 12.71 |
Maximum of Months | 744.00 | 12.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.236914E+11 | 0.00 | 0.00 | 0.446980E+11 | 0.00 | 0.00 |
February | 0.235234E+11 | 0.00 | 0.00 | 0.415080E+11 | 0.00 | 0.00 |
March | 0.687716E+10 | 0.00 | 0.278109E+10 | 0.483719E+11 | 0.00 | 0.00 |
April | 0.311280E+10 | 0.00 | 0.277150E+11 | 0.469486E+11 | 0.00 | 0.00 |
May | 0.831518E+09 | 0.00 | 0.105657E+12 | 0.478707E+11 | 0.00 | 0.00 |
June | 37191144.50 | 0.00 | 0.446720E+12 | 0.471409E+11 | 0.00 | 0.00 |
July | 15791559.46 | 0.00 | 0.730089E+12 | 0.513421E+11 | 0.00 | 0.00 |
August | 0.103805E+09 | 0.00 | 0.584795E+12 | 0.529271E+11 | 0.00 | 0.00 |
September | 0.112703E+09 | 0.00 | 0.319281E+12 | 0.505020E+11 | 0.00 | 0.00 |
October | 0.160403E+09 | 0.00 | 0.113308E+12 | 0.534383E+11 | 0.00 | 0.00 |
November | 0.607671E+10 | 0.00 | 0.356229E+10 | 0.482128E+11 | 0.00 | 0.00 |
December | 0.102562E+11 | 0.00 | 0.00 | 0.476819E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.747990E+11 | 0.00 | 0.233391E+13 | 0.580642E+12 | 0.00 | 0.00 |
Minimum of Months | 15791559.46 | 0.00 | 0.00 | 0.415080E+11 | 0.00 | 0.00 |
Maximum of Months | 0.236914E+11 | 0.00 | 0.730089E+12 | 0.534383E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.153314E+10 | 0.00 | 0.00 | 0.261252E+10 | 0.00 | 0.00 |
February | 0.168736E+10 | 0.00 | 0.00 | 0.235970E+10 | 0.00 | 0.00 |
March | 0.123610E+09 | 0.00 | 0.255549E+09 | 0.261252E+10 | 0.00 | 0.00 |
April | 11866.60 | 0.00 | 0.203530E+10 | 0.252825E+10 | 0.00 | 0.00 |
May | 26506.54 | 0.00 | 0.856939E+10 | 0.261252E+10 | 0.00 | 0.00 |
June | 28553.79 | 0.00 | 0.418372E+11 | 0.252825E+10 | 0.00 | 0.00 |
July | 35468.64 | 0.00 | 0.608101E+11 | 0.261252E+10 | 0.00 | 0.00 |
August | 38995.80 | 0.00 | 0.484433E+11 | 0.261252E+10 | 0.00 | 0.00 |
September | 40498.05 | 0.00 | 0.284806E+11 | 0.252825E+10 | 0.00 | 0.00 |
October | 30312.21 | 0.00 | 0.953549E+10 | 0.261252E+10 | 0.00 | 0.00 |
November | 0.136635E+09 | 0.00 | 0.195362E+09 | 0.252825E+10 | 0.00 | 0.00 |
December | 0.193582E+09 | 0.00 | 0.00 | 0.261252E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.367453E+10 | 0.00 | 0.200162E+12 | 0.307604E+11 | 0.00 | 0.00 |
Minimum of Months | 11866.60 | 0.00 | 0.00 | 0.235970E+10 | 0.00 | 0.00 |
Maximum of Months | 0.168736E+10 | 0.00 | 0.608101E+11 | 0.261252E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.446980E+11 | 0.00 | 0.236914E+11 | 0.515637E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.415080E+11 | 0.00 | 0.235234E+11 | 0.508196E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.483719E+11 | 0.278109E+10 | 0.687716E+10 | 0.385491E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.469486E+11 | 0.277150E+11 | 0.311280E+10 | 0.193960E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.478707E+11 | 0.105657E+12 | 0.831518E+09 | 0.427464E+11 | 0.663670E+09 | 0.00 | 0.00 | 0.00 |
June | 0.471409E+11 | 0.446720E+12 | 37191144.50 | 0.439633E+09 | 0.184959E+11 | 0.00 | 0.00 | 0.00 |
July | 0.513421E+11 | 0.730089E+12 | 15791559.46 | 0.00 | 0.785414E+11 | 0.00 | 0.00 | 0.00 |
August | 0.529271E+11 | 0.584795E+12 | 0.103805E+09 | 0.00 | 0.750006E+11 | 0.00 | 0.00 | 0.00 |
September | 0.505020E+11 | 0.319281E+12 | 0.112703E+09 | 0.769851E+10 | 0.696815E+10 | 0.00 | 0.00 | 0.00 |
October | 0.534383E+11 | 0.113308E+12 | 0.160403E+09 | 0.104203E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.482128E+11 | 0.356229E+10 | 0.607671E+10 | 0.309347E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476819E+11 | 0.00 | 0.102562E+11 | 0.467324E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.580642E+12 | 0.233391E+13 | 0.747990E+11 | 0.253504E+13 | 0.179670E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.415080E+11 | 0.00 | 15791559.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.534383E+11 | 0.730089E+12 | 0.236914E+11 | 0.515637E+12 | 0.785414E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261252E+10 | 0.00 | 0.153314E+10 | 0.535451E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235970E+10 | 0.00 | 0.168736E+10 | 0.525211E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261252E+10 | 0.255549E+09 | 0.123610E+09 | 0.392246E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252825E+10 | 0.203530E+10 | 11866.60 | 0.197831E+11 | 19394848.40 | 0.00 | 0.00 | 0.00 |
May | 0.261252E+10 | 0.856939E+10 | 26506.54 | 0.471382E+10 | 0.280596E+09 | 0.00 | 0.00 | 0.00 |
June | 0.252825E+10 | 0.418372E+11 | 28553.79 | 0.121939E+09 | 0.668584E+10 | 0.00 | 0.00 | 0.00 |
July | 0.261252E+10 | 0.608101E+11 | 35468.64 | 2368001.46 | 0.250601E+11 | 0.00 | 0.00 | 0.00 |
August | 0.261252E+10 | 0.484433E+11 | 38995.80 | 0.108317E+09 | 0.194481E+11 | 0.00 | 0.00 | 0.00 |
September | 0.252825E+10 | 0.284806E+11 | 40498.05 | 0.967653E+09 | 0.438147E+10 | 0.00 | 0.00 | 0.00 |
October | 0.261252E+10 | 0.953549E+10 | 30312.21 | 0.107516E+11 | 91961341.38 | 0.00 | 0.00 | 0.00 |
November | 0.252825E+10 | 0.195362E+09 | 0.136635E+09 | 0.315992E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261252E+10 | 0.00 | 0.193582E+09 | 0.479724E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307604E+11 | 0.200162E+12 | 0.367453E+10 | 0.261311E+12 | 0.559674E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.235970E+10 | 0.00 | 11866.60 | 2368001.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261252E+10 | 0.608101E+11 | 0.168736E+10 | 0.535451E+11 | 0.250601E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.446980E+11 | 0.236914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.415080E+11 | 0.235234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.483719E+11 | 0.687716E+10 | 0.278109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.469486E+11 | 0.311280E+10 | 0.277150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.478707E+11 | 0.831518E+09 | 0.105657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.471409E+11 | 37191144.50 | 0.446720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.513421E+11 | 15791559.46 | 0.730089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.529271E+11 | 0.103805E+09 | 0.584795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.505020E+11 | 0.112703E+09 | 0.319281E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.534383E+11 | 0.160403E+09 | 0.113308E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.482128E+11 | 0.607671E+10 | 0.356229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476819E+11 | 0.102562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.580642E+12 | 0.747990E+11 | 0.233391E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.415080E+11 | 15791559.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.534383E+11 | 0.236914E+11 | 0.730089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.261252E+10 | 0.153314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235970E+10 | 0.168736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261252E+10 | 0.123610E+09 | 0.255549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252825E+10 | 11866.60 | 0.203530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261252E+10 | 26506.54 | 0.856939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252825E+10 | 28553.79 | 0.418372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261252E+10 | 35468.64 | 0.608101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261252E+10 | 38995.80 | 0.484433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252825E+10 | 40498.05 | 0.284806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261252E+10 | 30312.21 | 0.953549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252825E+10 | 0.136635E+09 | 0.195362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261252E+10 | 0.193582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307604E+11 | 0.367453E+10 | 0.200162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.235970E+10 | 11866.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261252E+10 | 0.168736E+10 | 0.608101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.487752E+09 | 0.00 | 0.00 | 0.431199E+10 | 0.00 | 0.00 | 0.472970E+11 | 0.00 | 0.82 |
February | 0.00 | 0.00 | 0.00 | 0.274898E+10 | 0.00 | 0.00 | 0.453303E+11 | 0.00 | 0.84 |
March | 0.00 | 0.00 | 0.00 | 0.181618E+10 | 0.00 | 0.00 | 0.502350E+11 | 0.00 | 0.82 |
April | 0.464018E+09 | 0.00 | 0.00 | 0.123823E+10 | 0.00 | 0.00 | 0.453587E+11 | 0.00 | 0.77 |
May | 0.198339E+10 | 14116741.48 | 0.00 | 0.694315E+09 | 50060107.80 | 0.00 | 0.372053E+11 | 0.00 | 0.69 |
June | 0.112732E+09 | 0.603265E+10 | 0.00 | 0.436162E+09 | 0.117101E+09 | 0.00 | 0.124483E+11 | 0.00 | 0.69 |
July | 327450.01 | 0.216114E+11 | 0.00 | 85168062.94 | 27098.87 | 0.00 | 0.959208E+09 | 0.00 | 0.74 |
August | 0.00 | 0.135839E+11 | 0.00 | 0.648450E+09 | 0.00 | 0.00 | 0.863441E+10 | 0.00 | 0.81 |
September | 0.00 | 0.426652E+10 | 0.00 | 0.204972E+10 | 0.00 | 0.00 | 0.243777E+11 | 0.00 | 0.85 |
October | 0.00 | 0.204536E+09 | 0.00 | 0.673183E+10 | 0.00 | 0.00 | 0.391165E+11 | 0.00 | 0.85 |
November | 0.00 | 0.00 | 0.00 | 0.889148E+10 | 0.00 | 0.00 | 0.434492E+11 | 0.00 | 0.84 |
December | 0.00 | 0.00 | 0.00 | 0.775247E+10 | 0.00 | 0.00 | 0.449433E+11 | 0.00 | 0.84 |
Annual Sum or Average | 0.304822E+10 | 0.457132E+11 | 0.00 | 0.374050E+11 | 0.167188E+09 | 0.00 | 0.399355E+12 | 0.00 | 0.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 85168062.94 | 0.00 | 0.00 | 0.959208E+09 | 0.00 | 0.69 |
Maximum of Months | 0.198339E+10 | 0.216114E+11 | 0.00 | 0.889148E+10 | 0.117101E+09 | 0.00 | 0.502350E+11 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159170E+10 | 0.00 | 0.00 | 8207042.21 | 0.00 | 0.112897E+10 | 0.318736E+09 | 0.00 | 0.87 |
February | 0.151122E+10 | 0.00 | 0.00 | 11733107.29 | 0.00 | 0.864958E+09 | 0.453887E+09 | 0.00 | 0.90 |
March | 0.218481E+10 | 0.00 | 0.00 | 21805655.31 | 0.00 | 0.169411E+09 | 0.874442E+09 | 0.00 | 0.94 |
April | 0.195019E+10 | 0.00 | 0.00 | 20574098.83 | 0.00 | 5349911.67 | 0.124902E+10 | 0.00 | 1.01 |
May | 0.110779E+10 | 13954406.63 | 0.00 | 28956244.08 | 0.00 | 0.00 | 0.215689E+10 | 0.00 | 1.17 |
June | 64948292.35 | 0.905696E+09 | 0.00 | 32443032.85 | 204576.02 | 0.00 | 0.118103E+10 | 0.00 | 1.54 |
July | 127489.40 | 0.283461E+10 | 0.00 | 8682594.58 | 0.00 | 0.00 | 0.111416E+09 | 0.00 | 1.77 |
August | 2718434.69 | 0.177505E+10 | 0.00 | 57934502.40 | 0.00 | 0.00 | 0.906568E+09 | 0.00 | 1.81 |
September | 0.317122E+09 | 0.466833E+09 | 0.00 | 77903039.63 | 0.00 | 0.00 | 0.192066E+10 | 0.00 | 1.52 |
October | 0.640226E+09 | 26387645.18 | 0.00 | 0.129239E+09 | 0.00 | 0.00 | 0.338786E+10 | 0.00 | 1.47 |
November | 0.205938E+10 | 0.00 | 0.00 | 32134438.37 | 0.00 | 0.106125E+09 | 0.120922E+10 | 0.00 | 0.99 |
December | 0.197227E+10 | 0.00 | 0.00 | 22410002.76 | 0.00 | 0.581749E+09 | 0.576526E+09 | 0.00 | 0.91 |
Annual Sum or Average | 0.134025E+11 | 0.602253E+10 | 0.00 | 0.452023E+09 | 204576.02 | 0.285657E+10 | 0.143462E+11 | 0.00 | 1.24 |
Minimum of Months | 127489.40 | 0.00 | 0.00 | 8207042.21 | 0.00 | 0.00 | 0.111416E+09 | 0.00 | 0.87 |
Maximum of Months | 0.218481E+10 | 0.283461E+10 | 0.00 | 0.129239E+09 | 204576.02 | 0.112897E+10 | 0.338786E+10 | 0.00 | 1.81 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.215109E+10 | 0.00 | 0.00 | 18485589.90 | 0.00 | 0.00 | 0.146867E+10 | 0.00 | 0.89 |
February | 0.167768E+10 | 0.00 | 0.00 | 21695846.47 | 0.00 | 0.00 | 0.166784E+10 | 0.00 | 0.91 |
March | 0.863029E+09 | 0.00 | 0.00 | 65976153.16 | 0.00 | 0.00 | 0.326519E+10 | 0.00 | 1.02 |
April | 0.440387E+09 | 0.00 | 0.00 | 98581374.28 | 0.00 | 0.00 | 0.368834E+10 | 0.00 | 1.09 |
May | 0.125747E+09 | 9655214.70 | 0.00 | 0.126827E+09 | 0.00 | 0.00 | 0.383594E+10 | 0.00 | 1.15 |
June | 363848.02 | 0.721563E+09 | 0.00 | 86200577.69 | 0.00 | 0.00 | 0.125288E+10 | 0.00 | 1.19 |
July | 0.00 | 0.224690E+10 | 0.00 | 17664212.04 | 0.00 | 0.00 | 86840571.41 | 0.00 | 1.22 |
August | 13103.39 | 0.133517E+10 | 0.00 | 87312626.61 | 0.00 | 0.00 | 0.798440E+09 | 0.00 | 1.24 |
September | 16903797.48 | 0.382497E+09 | 0.00 | 0.107723E+09 | 0.00 | 0.00 | 0.226717E+10 | 0.00 | 1.20 |
October | 389553.17 | 19024688.46 | 0.00 | 0.188345E+09 | 0.00 | 0.00 | 0.408190E+10 | 0.00 | 1.23 |
November | 0.685511E+09 | 0.00 | 0.00 | 83910632.43 | 0.00 | 0.00 | 0.352994E+10 | 0.00 | 1.07 |
December | 0.129236E+10 | 0.00 | 0.00 | 38228291.59 | 0.00 | 0.00 | 0.259178E+10 | 0.00 | 0.97 |
Annual Sum or Average | 0.725348E+10 | 0.471481E+10 | 0.00 | 0.940950E+09 | 0.00 | 0.00 | 0.285349E+11 | 0.00 | 1.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 17664212.04 | 0.00 | 0.00 | 86840571.41 | 0.00 | 0.89 |
Maximum of Months | 0.215109E+10 | 0.224690E+10 | 0.00 | 0.188345E+09 | 0.00 | 0.00 | 0.408190E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 38115647.86 | 0.00 | 0.00 | 3344026.51 | 0.00 | 5855498.92 | 0.460405E+09 | 0.00 | 0.05 |
February | 38003209.06 | 0.00 | 0.00 | 2182863.07 | 0.00 | 0.00 | 0.322124E+09 | 0.00 | 0.04 |
March | 15573328.23 | 0.00 | 0.00 | 15729740.79 | 0.00 | 0.00 | 0.155985E+10 | 0.00 | 0.17 |
April | 1794025.01 | 0.00 | 0.00 | 40837436.50 | 0.00 | 0.00 | 0.262377E+10 | 0.00 | 0.32 |
May | 5111.04 | 9346222.92 | 0.00 | 71278431.09 | 0.00 | 0.00 | 0.328255E+10 | 0.00 | 0.45 |
June | 1645.76 | 0.717164E+09 | 0.00 | 67347032.67 | 0.00 | 0.00 | 0.116542E+10 | 0.00 | 0.54 |
July | 0.00 | 0.232520E+10 | 0.00 | 17369165.09 | 0.00 | 0.00 | 89381342.64 | 0.00 | 0.59 |
August | 0.00 | 0.139121E+10 | 0.00 | 76537089.47 | 0.00 | 0.00 | 0.795448E+09 | 0.00 | 0.59 |
September | 13686.23 | 0.373646E+09 | 0.00 | 68736120.39 | 0.00 | 0.00 | 0.204573E+10 | 0.00 | 0.51 |
October | 0.00 | 15569591.40 | 0.00 | 80530646.82 | 0.00 | 0.00 | 0.349307E+10 | 0.00 | 0.48 |
November | 8036821.19 | 0.00 | 0.00 | 32276627.33 | 0.00 | 0.00 | 0.238614E+10 | 0.00 | 0.27 |
December | 25352513.11 | 0.00 | 0.00 | 7566775.89 | 0.00 | 0.00 | 0.983996E+09 | 0.00 | 0.11 |
Annual Sum or Average | 0.126896E+09 | 0.483214E+10 | 0.00 | 0.483736E+09 | 0.00 | 5855498.92 | 0.192079E+11 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2182863.07 | 0.00 | 0.00 | 89381342.64 | 0.00 | 0.04 |
Maximum of Months | 38115647.86 | 0.232520E+10 | 0.00 | 80530646.82 | 0.00 | 5855498.92 | 0.349307E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207808E+09 | 0.00 | 0.00 | 0.42 |
February | 0.172262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171000E+09 | 0.00 | 0.00 | 0.42 |
March | 0.207842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
April | 0.197877E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
May | 0.180655E+10 | 0.00 | 0.00 | 637459.20 | 4315326.11 | 0.00 | 18504674.58 | 0.00 | 0.43 |
June | 0.490173E+09 | 0.145965E+09 | 0.00 | 6324808.37 | 0.176714E+09 | 0.00 | 82854522.47 | 0.00 | 0.43 |
July | 6144569.64 | 0.835138E+09 | 0.00 | 6261009.85 | 0.129681E+09 | 0.00 | 32021306.42 | 0.00 | 0.43 |
August | 0.148053E+09 | 0.523907E+09 | 0.00 | 21687078.87 | 43532500.60 | 0.00 | 0.207088E+09 | 0.00 | 0.43 |
September | 0.962439E+09 | 63753788.83 | 0.00 | 4910185.47 | 0.105111E+09 | 0.00 | 76019557.93 | 0.00 | 0.43 |
October | 0.178590E+10 | 0.00 | 0.00 | 239091.29 | 8055733.61 | 0.00 | 19748306.01 | 0.00 | 0.43 |
November | 0.206146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
December | 0.207544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.169887E+11 | 0.156876E+10 | 0.00 | 40059633.05 | 0.467410E+09 | 0.378807E+09 | 0.436237E+09 | 0.00 | 0.42 |
Minimum of Months | 6144569.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.207842E+10 | 0.835138E+09 | 0.00 | 21687078.87 | 0.176714E+09 | 0.207808E+09 | 0.207088E+09 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.130248E+10 | 0.00 | 0.00 | 0.730822E+11 | 0.00 | 18.33 |
February | 0.00 | 0.00 | 0.00 | 0.118469E+10 | 0.00 | 0.00 | 0.667037E+11 | 0.00 | 18.50 |
March | 0.00 | 0.00 | 0.00 | 0.137066E+10 | 0.00 | 0.00 | 0.736326E+11 | 0.00 | 18.54 |
April | 0.00 | 0.00 | 0.00 | 0.130135E+10 | 0.00 | 0.00 | 0.689039E+11 | 0.00 | 18.29 |
May | 0.00 | 0.138557E+09 | 0.00 | 0.126125E+10 | 0.00 | 0.00 | 0.606093E+11 | 0.00 | 17.58 |
June | 0.00 | 0.101895E+11 | 0.00 | 0.692603E+09 | 0.00 | 0.00 | 0.177686E+11 | 0.00 | 16.70 |
July | 0.00 | 0.309010E+11 | 0.00 | 0.105259E+09 | 0.00 | 0.00 | 0.126248E+10 | 0.00 | 16.65 |
August | 0.00 | 0.184571E+11 | 0.00 | 0.532566E+09 | 0.00 | 0.00 | 0.110846E+11 | 0.00 | 16.78 |
September | 0.00 | 0.537568E+10 | 0.00 | 0.884101E+09 | 0.00 | 0.00 | 0.333344E+11 | 0.00 | 16.94 |
October | 0.00 | 0.250922E+09 | 0.00 | 0.130331E+10 | 0.00 | 0.00 | 0.619283E+11 | 0.00 | 17.93 |
November | 0.00 | 0.00 | 0.00 | 0.132031E+10 | 0.00 | 0.00 | 0.729699E+11 | 0.00 | 18.65 |
December | 0.00 | 0.00 | 0.00 | 0.133624E+10 | 0.00 | 0.00 | 0.735721E+11 | 0.00 | 18.70 |
Annual Sum or Average | 0.00 | 0.653128E+11 | 0.00 | 0.125948E+11 | 0.00 | 0.00 | 0.614852E+12 | 0.00 | 17.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.105259E+09 | 0.00 | 0.00 | 0.126248E+10 | 0.00 | 16.65 |
Maximum of Months | 0.00 | 0.309010E+11 | 0.00 | 0.137066E+10 | 0.00 | 0.00 | 0.736326E+11 | 0.00 | 18.70 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164090E+11 | 0.00 | 0.00 | 0.110294E+09 | 0.00 | 0.109856E+09 | 0.859553E+10 | 0.00 | 2.55 |
February | 0.129436E+11 | 0.00 | 0.00 | 0.138426E+09 | 0.00 | 1522650.72 | 0.102218E+11 | 0.00 | 2.60 |
March | 0.829115E+10 | 0.00 | 0.00 | 0.289004E+09 | 0.00 | 0.00 | 0.180824E+11 | 0.00 | 2.70 |
April | 0.647106E+10 | 0.00 | 0.00 | 0.308237E+09 | 0.00 | 0.00 | 0.190220E+11 | 0.00 | 2.77 |
May | 0.374134E+10 | 58193919.94 | 0.00 | 0.363349E+09 | 0.00 | 0.00 | 0.200844E+11 | 0.00 | 2.83 |
June | 0.434978E+09 | 0.384136E+10 | 0.00 | 0.279217E+09 | 0.441907E+09 | 0.00 | 0.711594E+10 | 0.00 | 2.90 |
July | 1916600.50 | 0.129439E+11 | 0.00 | 58201350.17 | 0.260510E+09 | 0.00 | 0.552104E+09 | 0.00 | 2.96 |
August | 74668401.71 | 0.783040E+10 | 0.00 | 0.314346E+09 | 38891408.70 | 0.00 | 0.478246E+10 | 0.00 | 3.00 |
September | 0.104903E+10 | 0.201713E+10 | 0.00 | 0.449139E+09 | 0.248473E+09 | 0.00 | 0.126491E+11 | 0.00 | 2.94 |
October | 0.960040E+09 | 0.113368E+09 | 0.00 | 0.808062E+09 | 271555.90 | 0.00 | 0.231908E+11 | 0.00 | 2.97 |
November | 0.753407E+10 | 0.00 | 0.00 | 0.341253E+09 | 0.00 | 0.00 | 0.189301E+11 | 0.00 | 2.76 |
December | 0.115748E+11 | 0.00 | 0.00 | 0.219574E+09 | 0.00 | 0.00 | 0.141563E+11 | 0.00 | 2.65 |
Annual Sum or Average | 0.694856E+11 | 0.268044E+11 | 0.00 | 0.367910E+10 | 0.990052E+09 | 0.111379E+09 | 0.157383E+12 | 0.00 | 2.80 |
Minimum of Months | 1916600.50 | 0.00 | 0.00 | 58201350.17 | 0.00 | 0.00 | 0.552104E+09 | 0.00 | 2.55 |
Maximum of Months | 0.164090E+11 | 0.129439E+11 | 0.00 | 0.808062E+09 | 0.441907E+09 | 0.109856E+09 | 0.231908E+11 | 0.00 | 3.00 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.218166E+11 | 0.00 | 0.00 | 0.130743E+10 | 0.00 | 0.00 | 0.609772E+11 | 0.00 | 1.22 |
February | 0.133964E+11 | 0.00 | 0.00 | 0.134495E+10 | 0.00 | 0.00 | 0.640337E+11 | 0.00 | 1.27 |
March | 0.614763E+10 | 0.00 | 0.00 | 0.265495E+10 | 0.00 | 0.00 | 0.826880E+11 | 0.00 | 1.33 |
April | 0.264837E+10 | 0.00 | 0.00 | 0.304244E+10 | 0.00 | 0.00 | 0.823389E+11 | 0.00 | 1.36 |
May | 0.126463E+10 | 0.188112E+09 | 0.00 | 0.325690E+10 | 0.00 | 0.00 | 0.773637E+11 | 0.00 | 1.38 |
June | 10055358.37 | 0.142586E+11 | 0.00 | 0.198399E+10 | 0.00 | 0.00 | 0.245360E+11 | 0.00 | 1.41 |
July | 0.00 | 0.442835E+11 | 0.00 | 0.369780E+09 | 0.00 | 0.00 | 0.168827E+10 | 0.00 | 1.43 |
August | 728107.67 | 0.262838E+11 | 0.00 | 0.183009E+10 | 0.00 | 0.00 | 0.156362E+11 | 0.00 | 1.45 |
September | 0.243884E+09 | 0.758875E+10 | 0.00 | 0.260122E+10 | 333183.44 | 0.00 | 0.450822E+11 | 0.00 | 1.43 |
October | 12218964.62 | 0.378454E+09 | 0.00 | 0.474581E+10 | 0.00 | 0.00 | 0.796588E+11 | 0.00 | 1.45 |
November | 0.412340E+10 | 0.00 | 0.00 | 0.314533E+10 | 0.00 | 0.00 | 0.851880E+11 | 0.00 | 1.37 |
December | 0.943567E+10 | 0.00 | 0.00 | 0.215423E+10 | 0.00 | 0.00 | 0.787618E+11 | 0.00 | 1.33 |
Annual Sum or Average | 0.590997E+11 | 0.929812E+11 | 0.00 | 0.284371E+11 | 333183.44 | 0.00 | 0.697953E+12 | 0.00 | 1.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.369780E+09 | 0.00 | 0.00 | 0.168827E+10 | 0.00 | 1.22 |
Maximum of Months | 0.218166E+11 | 0.442835E+11 | 0.00 | 0.474581E+10 | 333183.44 | 0.00 | 0.851880E+11 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 56639263.36 | 0.00 | 0.00 | 425348.11 | 0.00 | 0.147714E+10 | 18882967.54 | 0.00 | 0.34 |
February | 56791013.93 | 0.00 | 0.00 | 1205783.04 | 0.00 | 0.132896E+10 | 37201728.10 | 0.00 | 0.34 |
March | 80560569.20 | 0.00 | 0.00 | 9199767.71 | 0.00 | 0.114354E+10 | 0.273249E+09 | 0.00 | 0.34 |
April | 77429606.34 | 351558.39 | 0.00 | 22859635.74 | 0.00 | 0.680250E+09 | 0.567724E+09 | 0.00 | 0.34 |
May | 53933644.45 | 12924328.70 | 481.83 | 45313669.84 | 21937.14 | 98665674.39 | 0.875678E+09 | 3056.27 | 0.34 |
June | 4596217.81 | 0.478161E+09 | 12594.65 | 26240059.00 | 6738961.73 | 500110.74 | 0.185579E+09 | 1185.52 | 0.34 |
July | 0.00 | 0.898226E+09 | 43826.97 | 1575522.63 | 517029.44 | 13195.92 | 1408312.12 | 3008.19 | 0.34 |
August | 0.00 | 0.622357E+09 | 19076.26 | 16763585.40 | 1426075.94 | 203562.66 | 59229954.82 | 5230.96 | 0.34 |
September | 9681604.95 | 0.229154E+09 | 12825.98 | 32707349.86 | 4013549.77 | 11416370.54 | 0.434635E+09 | 2770.36 | 0.34 |
October | 42067789.97 | 38000851.37 | 0.00 | 36821974.93 | 0.00 | 0.211785E+09 | 0.791692E+09 | 0.00 | 0.34 |
November | 79897158.30 | 0.00 | 0.00 | 4769625.53 | 0.00 | 0.111502E+10 | 0.263512E+09 | 0.00 | 0.34 |
December | 62414591.08 | 0.00 | 0.00 | 547749.58 | 0.00 | 0.140695E+10 | 36208373.43 | 0.00 | 0.34 |
Annual Sum or Average | 0.524011E+09 | 0.227918E+10 | 88805.70 | 0.198430E+09 | 12717554.02 | 0.747444E+10 | 0.354500E+10 | 15251.31 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 425348.11 | 0.00 | 13195.92 | 1408312.12 | 0.00 | 0.34 |
Maximum of Months | 80560569.20 | 0.898226E+09 | 43826.97 | 45313669.84 | 6738961.73 | 0.147714E+10 | 0.875678E+09 | 5230.96 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 32621148.29 | 0.00 | 0.00 | 60165.80 | 0.00 | 0.151585E+10 | 4551936.69 | 0.00 | 0.34 |
February | 35449902.78 | 0.00 | 0.00 | 191191.97 | 0.00 | 0.137027E+10 | 18250428.21 | 0.00 | 0.34 |
March | 85467697.36 | 0.00 | 0.00 | 4775392.45 | 0.00 | 0.123821E+10 | 0.178096E+09 | 0.00 | 0.34 |
April | 0.105667E+09 | 350334.07 | 0.00 | 15155080.97 | 1224.32 | 0.728552E+09 | 0.498889E+09 | 0.00 | 0.34 |
May | 0.170219E+09 | 11507186.12 | 5635.50 | 29502489.85 | 1436279.02 | 0.102138E+09 | 0.771731E+09 | 703.32 | 0.34 |
June | 80372046.50 | 0.401205E+09 | 63268.33 | 12168152.88 | 83636998.55 | 158290.99 | 0.124217E+09 | 8959.25 | 0.34 |
July | 2256996.73 | 0.723465E+09 | 127234.50 | 335898.38 | 0.175193E+09 | 0.00 | 404135.56 | 4476.94 | 0.34 |
August | 26927963.24 | 0.536291E+09 | 77563.74 | 9729762.69 | 87429937.39 | 71709.32 | 39467667.63 | 9283.02 | 0.34 |
September | 0.128962E+09 | 0.177464E+09 | 41608.79 | 14707396.32 | 55671955.81 | 10053290.91 | 0.334717E+09 | 4976.11 | 0.34 |
October | 0.145164E+09 | 30692143.49 | 0.00 | 15125880.83 | 7308707.88 | 0.355362E+09 | 0.566715E+09 | 0.00 | 0.34 |
November | 83535062.55 | 0.00 | 0.00 | 1125526.78 | 0.00 | 0.126453E+10 | 0.114001E+09 | 0.00 | 0.34 |
December | 44363544.64 | 0.00 | 0.00 | 32089.88 | 0.00 | 0.145982E+10 | 1903535.07 | 0.00 | 0.34 |
Annual Sum or Average | 0.941007E+09 | 0.188097E+10 | 315310.85 | 0.102909E+09 | 0.410678E+09 | 0.804502E+10 | 0.265294E+10 | 28398.64 | 0.34 |
Minimum of Months | 2256996.73 | 0.00 | 0.00 | 32089.88 | 0.00 | 0.00 | 404135.56 | 0.00 | 0.34 |
Maximum of Months | 0.170219E+09 | 0.723465E+09 | 127234.50 | 29502489.85 | 0.175193E+09 | 0.151585E+10 | 0.771731E+09 | 9283.02 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
February | 0.145505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.174769E+10 | 0.00 | 0.00 | 514645.84 | 0.00 | 0.00 | 87758334.24 | 0.00 | 0.02 |
April | 0.151244E+10 | 0.00 | 0.00 | 4868127.04 | 0.00 | 0.00 | 0.216220E+09 | 0.00 | 0.02 |
May | 0.138849E+10 | 14638695.70 | 0.00 | 3025678.36 | 0.00 | 0.00 | 70409768.82 | 0.00 | 0.02 |
June | 0.196137E+09 | 0.232440E+09 | 0.00 | 4725160.41 | 0.184302E+09 | 0.00 | 95115494.25 | 0.00 | 0.02 |
July | 0.00 | 0.755045E+09 | 0.00 | 897507.70 | 0.107848E+09 | 0.00 | 264072.25 | 0.00 | 0.02 |
August | 0.00 | 0.613646E+09 | 0.00 | 9477787.77 | 9635927.45 | 0.00 | 37366684.53 | 0.00 | 0.02 |
September | 0.177483E+09 | 0.215494E+09 | 0.00 | 18076231.99 | 42009725.92 | 0.00 | 0.330126E+09 | 0.00 | 0.02 |
October | 0.146593E+09 | 58537448.18 | 0.00 | 36377361.38 | 0.00 | 0.00 | 0.103797E+10 | 0.00 | 0.02 |
November | 0.148254E+10 | 0.00 | 0.00 | 6814139.64 | 0.00 | 0.00 | 0.334843E+09 | 0.00 | 0.02 |
December | 0.154406E+10 | 0.00 | 0.00 | 1290355.48 | 0.00 | 0.00 | 0.147549E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.107266E+11 | 0.188980E+10 | 0.00 | 86066995.61 | 0.343796E+09 | 0.00 | 0.235762E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.174769E+10 | 0.755045E+09 | 0.00 | 36377361.38 | 0.184302E+09 | 0.00 | 0.103797E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105891E+10 | 0.00 | 0.00 | 27993255.69 | 0.00 | 0.153214E+11 | 0.464781E+10 | 0.00 | 0.38 |
February | 0.985445E+09 | 0.00 | 0.00 | 17838004.78 | 0.00 | 0.150494E+11 | 0.325549E+10 | 0.00 | 0.39 |
March | 0.122260E+10 | 0.00 | 0.00 | 0.135381E+09 | 0.00 | 0.528000E+10 | 0.137872E+11 | 0.00 | 0.38 |
April | 0.143270E+10 | 4749686.33 | 0.00 | 0.329107E+09 | 16598.80 | 0.208318E+09 | 0.163091E+11 | 0.00 | 0.39 |
May | 0.232099E+10 | 0.140427E+09 | 0.00 | 0.487887E+09 | 35141069.27 | 11326430.48 | 0.117351E+11 | 0.00 | 0.39 |
June | 0.110663E+10 | 0.517160E+10 | 0.00 | 0.143981E+09 | 0.140267E+10 | 627220.09 | 0.168961E+10 | 0.00 | 0.39 |
July | 30599440.37 | 0.932105E+10 | 0.00 | 3749735.20 | 0.286438E+10 | 0.00 | 6283342.97 | 0.00 | 0.39 |
August | 0.385663E+09 | 0.684393E+10 | 155247.89 | 0.100527E+09 | 0.161325E+10 | 68049.11 | 0.546792E+09 | 414.43 | 0.39 |
September | 0.177711E+10 | 0.229515E+10 | 99581.78 | 0.242480E+09 | 0.866142E+09 | 6213722.54 | 0.459627E+10 | 3154.33 | 0.39 |
October | 0.196807E+10 | 0.415706E+09 | 0.00 | 0.311606E+09 | 99494377.78 | 28617130.54 | 0.123660E+11 | 0.00 | 0.39 |
November | 0.124897E+10 | 0.00 | 0.00 | 0.162994E+09 | 0.00 | 0.477139E+10 | 0.136540E+11 | 0.00 | 0.39 |
December | 0.106624E+10 | 0.00 | 0.00 | 32402444.92 | 0.00 | 0.130264E+11 | 0.629432E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.146039E+11 | 0.241926E+11 | 254829.67 | 0.199595E+10 | 0.688109E+10 | 0.537037E+11 | 0.888880E+11 | 3568.76 | 0.39 |
Minimum of Months | 30599440.37 | 0.00 | 0.00 | 3749735.20 | 0.00 | 0.00 | 6283342.97 | 0.00 | 0.38 |
Maximum of Months | 0.232099E+10 | 0.932105E+10 | 155247.89 | 0.487887E+09 | 0.286438E+10 | 0.153214E+11 | 0.163091E+11 | 3154.33 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 57775539.82 | 0.00 | 0.00 | 696274.07 | 0.00 | 0.145817E+10 | 36437744.75 | 0.00 | 0.34 |
February | 58397494.59 | 0.00 | 0.00 | 1310981.85 | 0.00 | 0.131051E+10 | 53942971.00 | 0.00 | 0.34 |
March | 77809637.25 | 0.00 | 0.00 | 7907328.16 | 0.00 | 0.113195E+10 | 0.288881E+09 | 0.00 | 0.34 |
April | 68377501.53 | 351558.39 | 0.00 | 23212841.15 | 0.00 | 0.653670E+09 | 0.603003E+09 | 0.00 | 0.34 |
May | 37713369.87 | 12927866.81 | 0.00 | 46230449.48 | 21937.14 | 0.120019E+09 | 0.869628E+09 | 0.00 | 0.34 |
June | 906379.38 | 0.477704E+09 | 5213.14 | 26259882.87 | 7204643.45 | 287591.34 | 0.189462E+09 | 118.87 | 0.34 |
July | 0.00 | 0.898695E+09 | 41659.69 | 1797175.03 | 50831.70 | 15508.92 | 1184346.72 | 2492.62 | 0.34 |
August | 0.00 | 0.622382E+09 | 0.00 | 17266354.48 | 1426075.94 | 2442.42 | 58928305.98 | 0.00 | 0.34 |
September | 9114880.49 | 0.229148E+09 | 28461.30 | 34213017.12 | 4005735.70 | 10036580.11 | 0.435076E+09 | 334.58 | 0.34 |
October | 30994977.68 | 38000851.37 | 0.00 | 36424997.07 | 0.00 | 0.234191E+09 | 0.780756E+09 | 0.00 | 0.34 |
November | 76637541.04 | 0.00 | 0.00 | 7105146.60 | 0.00 | 0.106417E+10 | 0.315287E+09 | 0.00 | 0.34 |
December | 62864383.54 | 0.00 | 0.00 | 1597408.48 | 0.00 | 0.136840E+10 | 73254936.59 | 0.00 | 0.34 |
Annual Sum or Average | 0.480592E+09 | 0.227921E+10 | 75334.13 | 0.204022E+09 | 12709223.92 | 0.735142E+10 | 0.370584E+10 | 2946.07 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 696274.07 | 0.00 | 2442.42 | 1184346.72 | 0.00 | 0.34 |
Maximum of Months | 77809637.25 | 0.898695E+09 | 41659.69 | 46230449.48 | 7204643.45 | 0.145817E+10 | 0.869628E+09 | 2492.62 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33155824.57 | 0.00 | 0.00 | 46504.65 | 0.00 | 0.151545E+10 | 4426611.19 | 0.00 | 0.34 |
February | 33987669.27 | 0.00 | 0.00 | 279408.79 | 0.00 | 0.137139E+10 | 18501872.40 | 0.00 | 0.34 |
March | 85467697.36 | 0.00 | 0.00 | 3855462.15 | 0.00 | 0.124166E+10 | 0.175571E+09 | 0.00 | 0.34 |
April | 0.105156E+09 | 351077.59 | 0.00 | 16650445.76 | 480.80 | 0.716254E+09 | 0.510204E+09 | 0.00 | 0.34 |
May | 0.163728E+09 | 11513524.93 | 0.00 | 32357857.41 | 1436279.02 | 0.129912E+09 | 0.747593E+09 | 0.00 | 0.34 |
June | 76518121.89 | 0.399220E+09 | 90465.18 | 13293724.82 | 85595490.22 | 162629.96 | 0.126941E+09 | 8019.83 | 0.34 |
July | 2256996.73 | 0.723579E+09 | 17823.59 | 335620.83 | 0.175193E+09 | 0.00 | 404413.11 | 387.56 | 0.34 |
August | 26927963.24 | 0.536515E+09 | 16340.09 | 9486910.96 | 87275249.61 | 15870.70 | 39766357.98 | 1187.64 | 0.34 |
September | 0.124987E+09 | 0.177895E+09 | 61845.44 | 18064013.30 | 55220828.79 | 9429889.43 | 0.335959E+09 | 5511.12 | 0.34 |
October | 0.146070E+09 | 31653610.70 | 0.00 | 15651889.31 | 6347240.68 | 0.359557E+09 | 0.561088E+09 | 0.00 | 0.34 |
November | 82867779.96 | 0.00 | 0.00 | 2176388.03 | 0.00 | 0.121189E+10 | 0.166262E+09 | 0.00 | 0.34 |
December | 44777419.71 | 0.00 | 0.00 | 113571.14 | 0.00 | 0.144873E+10 | 12496047.48 | 0.00 | 0.34 |
Annual Sum or Average | 0.925900E+09 | 0.188073E+10 | 186474.30 | 0.112312E+09 | 0.411069E+09 | 0.800445E+10 | 0.269921E+10 | 15106.14 | 0.34 |
Minimum of Months | 2256996.73 | 0.00 | 0.00 | 46504.65 | 0.00 | 0.00 | 404413.11 | 0.00 | 0.34 |
Maximum of Months | 0.163728E+09 | 0.723579E+09 | 90465.18 | 32357857.41 | 0.175193E+09 | 0.151545E+10 | 0.747593E+09 | 8019.83 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.267745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168390E+11 | 0.00 | 0.00 | 0.27 |
February | 0.900363E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146699E+11 | 0.00 | 0.00 | 0.27 |
March | 0.475150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123383E+11 | 0.00 | 0.00 | 0.27 |
April | 0.102919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597846E+10 | 0.00 | 0.00 | 0.27 |
May | 0.144459E+11 | 0.00 | 0.00 | 0.00 | 35482594.66 | 0.563986E+09 | 0.00 | 0.00 | 0.28 |
June | 0.475621E+10 | 0.00 | 0.00 | 0.00 | 0.264061E+10 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.361194E+09 | 0.00 | 0.00 | 0.00 | 0.784852E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
August | 0.307644E+10 | 0.00 | 0.00 | 0.00 | 0.460786E+10 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.857019E+10 | 0.00 | 0.00 | 0.00 | 0.138388E+10 | 1506883.11 | 0.00 | 0.00 | 0.28 |
October | 0.147699E+11 | 0.00 | 0.00 | 0.00 | 66237944.31 | 77810827.41 | 0.00 | 0.00 | 0.28 |
November | 0.575053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111997E+11 | 0.00 | 0.00 | 0.27 |
December | 0.131285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157524E+11 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.692547E+11 | 0.00 | 0.00 | 0.00 | 0.165826E+11 | 0.774210E+11 | 0.00 | 0.00 | 0.27 |
Minimum of Months | 0.267745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.147699E+11 | 0.00 | 0.00 | 0.00 | 0.784852E+10 | 0.168390E+11 | 0.00 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 11608535.82 | 0.00 | 0.00 | 110714.38 | 0.00 | 0.373233E+09 | 3318323.78 | 0.00 | 0.34 |
February | 13015166.15 | 0.00 | 0.00 | 326979.65 | 0.00 | 0.334108E+09 | 8590224.93 | 0.00 | 0.34 |
March | 19533843.25 | 0.00 | 0.00 | 2381669.29 | 0.00 | 0.298501E+09 | 56221045.19 | 0.00 | 0.34 |
April | 16971490.74 | 87889.60 | 0.00 | 6016990.43 | 0.00 | 0.188452E+09 | 0.125625E+09 | 0.00 | 0.34 |
May | 9656723.52 | 3231082.18 | 327.29 | 12238803.32 | 5484.28 | 40931661.69 | 0.205570E+09 | 557.24 | 0.34 |
June | 364985.98 | 0.120268E+09 | 3333.85 | 6852154.57 | 957265.69 | 116807.77 | 46894955.08 | 111.20 | 0.34 |
July | 0.00 | 0.224688E+09 | 8287.01 | 386048.37 | 0.00 | 3298.98 | 359910.31 | 761.15 | 0.34 |
August | 0.00 | 0.155707E+09 | 6735.45 | 4120195.18 | 235902.00 | 43655.02 | 14885425.52 | 1949.90 | 0.34 |
September | 2157133.83 | 57283354.21 | 10243.35 | 8260902.87 | 1001433.92 | 4786561.21 | 0.106906E+09 | 663.61 | 0.34 |
October | 10275362.02 | 9500212.84 | 0.00 | 8751471.18 | 0.00 | 83030070.07 | 0.168535E+09 | 0.00 | 0.34 |
November | 18732795.94 | 0.00 | 0.00 | 973236.23 | 0.00 | 0.297016E+09 | 49077213.63 | 0.00 | 0.34 |
December | 13720509.61 | 0.00 | 0.00 | 100900.05 | 0.00 | 0.357570E+09 | 5138104.69 | 0.00 | 0.34 |
Annual Sum or Average | 0.116037E+09 | 0.570766E+09 | 28926.94 | 50520065.52 | 2200085.91 | 0.197779E+10 | 0.791121E+09 | 4043.10 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 100900.05 | 0.00 | 3298.98 | 359910.31 | 0.00 | 0.34 |
Maximum of Months | 19533843.25 | 0.224688E+09 | 10243.35 | 12238803.32 | 1001433.92 | 0.373233E+09 | 0.205570E+09 | 1949.90 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3066958.78 | 0.00 | 0.00 | 7574.27 | 0.00 | 0.384574E+09 | 622731.85 | 0.00 | 0.34 |
February | 5042829.88 | 0.00 | 0.00 | 24080.00 | 0.00 | 0.348023E+09 | 2950777.05 | 0.00 | 0.34 |
March | 18179408.46 | 0.00 | 0.00 | 1184321.88 | 0.00 | 0.319965E+09 | 37308367.28 | 0.00 | 0.34 |
April | 25274903.01 | 87583.52 | 0.00 | 4034709.91 | 306.08 | 0.199235E+09 | 0.108522E+09 | 0.00 | 0.34 |
May | 40840453.73 | 2878381.23 | 0.00 | 8241572.94 | 359069.75 | 41802608.18 | 0.177513E+09 | 0.00 | 0.34 |
June | 19132023.29 | 0.100934E+09 | 15464.50 | 3424333.96 | 20277295.07 | 36375.36 | 31636170.79 | 1519.29 | 0.34 |
July | 564249.18 | 0.180880E+09 | 18628.11 | 78563.90 | 43798348.06 | 0.00 | 106444.59 | 996.51 | 0.34 |
August | 6731990.81 | 0.134124E+09 | 7797.69 | 2515035.87 | 21818812.40 | 17784.24 | 9784464.80 | 1195.58 | 0.34 |
September | 31197734.12 | 44493349.72 | 3505.94 | 3754697.94 | 13798015.81 | 4345728.45 | 82811940.19 | 823.63 | 0.34 |
October | 36278625.52 | 7932414.36 | 0.00 | 3368342.14 | 1567798.48 | 0.112786E+09 | 0.118159E+09 | 0.00 | 0.34 |
November | 17402926.94 | 0.00 | 0.00 | 200340.52 | 0.00 | 0.334515E+09 | 13680103.90 | 0.00 | 0.34 |
December | 6714729.57 | 0.00 | 0.00 | 6286.73 | 0.00 | 0.369530E+09 | 278671.90 | 0.00 | 0.34 |
Annual Sum or Average | 0.210427E+09 | 0.471330E+09 | 45396.24 | 26839860.07 | 0.101620E+09 | 0.211483E+10 | 0.583374E+09 | 4535.01 | 0.34 |
Minimum of Months | 564249.18 | 0.00 | 0.00 | 6286.73 | 0.00 | 0.00 | 106444.59 | 0.00 | 0.34 |
Maximum of Months | 40840453.73 | 0.180880E+09 | 18628.11 | 8241572.94 | 43798348.06 | 0.384574E+09 | 0.177513E+09 | 1519.29 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 73519954.07 | 0.00 | 0.00 | 10289016.14 | 0.00 | 0.207047E+10 | 0.339205E+09 | 0.00 | 0.38 |
February | 53109069.73 | 0.00 | 0.00 | 14276267.87 | 0.00 | 0.170787E+10 | 0.511247E+09 | 0.00 | 0.39 |
March | 69265027.31 | 0.00 | 0.00 | 27523801.51 | 0.00 | 0.135227E+10 | 0.969711E+09 | 0.00 | 0.38 |
April | 79125564.10 | 564428.50 | 0.00 | 40816103.92 | 0.00 | 0.749100E+09 | 0.129560E+10 | 0.00 | 0.39 |
May | 40872630.66 | 20748720.14 | 5331.46 | 68411493.99 | 35220.17 | 56380900.97 | 0.155799E+10 | 1694.09 | 0.39 |
June | 3892086.95 | 0.767815E+09 | 0.00 | 34489418.35 | 10716810.67 | 492382.85 | 0.309385E+09 | 44.87 | 0.39 |
July | 0.00 | 0.144018E+10 | 14158.25 | 2474252.73 | 2818481.35 | 1314.25 | 2336178.64 | 853.62 | 0.39 |
August | 0.00 | 0.999177E+09 | 26820.41 | 24574221.93 | 2321393.23 | 154995.94 | 97605558.09 | 834.95 | 0.39 |
September | 8048761.94 | 0.367944E+09 | 406.58 | 59898965.82 | 6431225.87 | 1536875.32 | 0.714709E+09 | 278.38 | 0.39 |
October | 12120352.33 | 61010530.10 | 0.00 | 87829514.47 | 0.00 | 0.112529E+09 | 0.152527E+10 | 0.00 | 0.39 |
November | 78163918.59 | 0.00 | 0.00 | 33266197.50 | 0.00 | 0.115642E+10 | 0.108132E+10 | 0.00 | 0.39 |
December | 68863565.72 | 0.00 | 0.00 | 19897547.06 | 0.00 | 0.175130E+10 | 0.578018E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.486981E+09 | 0.365744E+10 | 46716.70 | 0.423747E+09 | 22323131.29 | 0.895852E+10 | 0.898239E+10 | 3705.91 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2474252.73 | 0.00 | 1314.25 | 2336178.64 | 0.00 | 0.38 |
Maximum of Months | 79125564.10 | 0.144018E+10 | 26820.41 | 87829514.47 | 10716810.67 | 0.207047E+10 | 0.155799E+10 | 1694.09 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.220557E+10 | 0.00 | 0.00 | 0.121973E+10 | 0.00 | 0.00 | 0.439472E+11 | 0.00 | 3.56 |
February | 0.184626E+10 | 0.00 | 0.00 | 0.112553E+10 | 0.00 | 0.00 | 0.402337E+11 | 0.00 | 3.59 |
March | 0.00 | 0.00 | 0.00 | 0.174745E+10 | 0.00 | 0.00 | 0.463195E+11 | 0.00 | 3.64 |
April | 0.00 | 0.00 | 0.00 | 0.189082E+10 | 0.00 | 0.00 | 0.438890E+11 | 0.00 | 3.68 |
May | 0.00 | 99880591.96 | 0.00 | 0.188658E+10 | 0.00 | 0.00 | 0.403474E+11 | 0.00 | 3.72 |
June | 0.00 | 0.743293E+10 | 0.00 | 0.102290E+10 | 0.00 | 0.00 | 0.123599E+11 | 0.00 | 3.73 |
July | 0.00 | 0.220929E+11 | 0.00 | 0.170578E+09 | 0.00 | 0.00 | 0.846154E+09 | 0.00 | 3.67 |
August | 0.00 | 0.129707E+11 | 0.00 | 0.817045E+09 | 0.00 | 0.00 | 0.783691E+10 | 0.00 | 3.71 |
September | 0.00 | 0.389301E+10 | 0.00 | 0.125013E+10 | 0.00 | 0.00 | 0.228404E+11 | 0.00 | 3.72 |
October | 1778718.85 | 0.186366E+09 | 0.00 | 0.184249E+10 | 0.00 | 0.00 | 0.399134E+11 | 0.00 | 3.69 |
November | 0.00 | 0.00 | 0.00 | 0.167279E+10 | 0.00 | 0.00 | 0.459415E+11 | 0.00 | 3.66 |
December | 20997990.32 | 0.00 | 0.00 | 0.141972E+10 | 0.00 | 0.00 | 0.462913E+11 | 0.00 | 3.64 |
Annual Sum or Average | 0.407460E+10 | 0.466759E+11 | 0.00 | 0.160658E+11 | 0.00 | 0.00 | 0.390766E+12 | 0.00 | 3.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.170578E+09 | 0.00 | 0.00 | 0.846154E+09 | 0.00 | 3.56 |
Maximum of Months | 0.220557E+10 | 0.220929E+11 | 0.00 | 0.189082E+10 | 0.00 | 0.00 | 0.463195E+11 | 0.00 | 3.73 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165372E+09 | 0.00 | 0.00 | 0.177902E+10 | 0.00 | 0.00 | 0.484735E+11 | 0.00 | 3.80 |
February | 0.00 | 0.00 | 0.00 | 0.163418E+10 | 0.00 | 0.00 | 0.443602E+11 | 0.00 | 3.84 |
March | 0.00 | 0.00 | 0.00 | 0.230318E+10 | 0.00 | 0.00 | 0.482762E+11 | 0.00 | 3.83 |
April | 0.00 | 0.00 | 0.00 | 0.236033E+10 | 0.00 | 0.00 | 0.457917E+11 | 0.00 | 3.88 |
May | 0.00 | 0.105016E+09 | 0.00 | 0.229919E+10 | 0.00 | 0.00 | 0.421240E+11 | 0.00 | 3.92 |
June | 0.00 | 0.781523E+10 | 0.00 | 0.120488E+10 | 0.00 | 0.00 | 0.128711E+11 | 0.00 | 3.93 |
July | 0.00 | 0.232288E+11 | 0.00 | 0.192915E+09 | 0.00 | 0.00 | 0.876089E+09 | 0.00 | 3.87 |
August | 0.00 | 0.136376E+11 | 0.00 | 0.945188E+09 | 0.00 | 0.00 | 0.815848E+10 | 0.00 | 3.91 |
September | 0.00 | 0.409578E+10 | 0.00 | 0.150079E+10 | 0.00 | 0.00 | 0.238574E+11 | 0.00 | 3.92 |
October | 0.00 | 0.196019E+09 | 0.00 | 0.224585E+10 | 0.00 | 0.00 | 0.416886E+11 | 0.00 | 3.89 |
November | 0.00 | 0.00 | 0.00 | 0.217624E+10 | 0.00 | 0.00 | 0.479890E+11 | 0.00 | 3.86 |
December | 0.00 | 0.00 | 0.00 | 0.200169E+10 | 0.00 | 0.00 | 0.485053E+11 | 0.00 | 3.86 |
Annual Sum or Average | 0.165372E+09 | 0.490784E+11 | 0.00 | 0.206435E+11 | 0.00 | 0.00 | 0.412972E+12 | 0.00 | 3.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.192915E+09 | 0.00 | 0.00 | 0.876089E+09 | 0.00 | 3.80 |
Maximum of Months | 0.165372E+09 | 0.232288E+11 | 0.00 | 0.236033E+10 | 0.00 | 0.00 | 0.485053E+11 | 0.00 | 3.93 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.206306E+10 | 0.00 | 0.00 | 0.495936E+11 | 0.00 | 12.67 |
February | 0.00 | 0.00 | 0.00 | 0.188552E+10 | 0.00 | 0.00 | 0.451984E+11 | 0.00 | 12.77 |
March | 0.00 | 0.00 | 0.00 | 0.225965E+10 | 0.00 | 0.00 | 0.494426E+11 | 0.00 | 12.74 |
April | 0.00 | 0.00 | 0.00 | 0.220750E+10 | 0.00 | 0.00 | 0.469751E+11 | 0.00 | 12.86 |
May | 0.00 | 0.107347E+09 | 0.00 | 0.215730E+10 | 0.00 | 0.00 | 0.430911E+11 | 0.00 | 12.99 |
June | 0.00 | 0.798856E+10 | 0.00 | 0.105410E+10 | 0.00 | 0.00 | 0.131558E+11 | 0.00 | 12.93 |
July | 0.00 | 0.237440E+11 | 0.00 | 0.146859E+09 | 0.00 | 0.00 | 0.920963E+09 | 0.00 | 12.80 |
August | 0.00 | 0.139403E+11 | 0.00 | 0.829471E+09 | 0.00 | 0.00 | 0.826988E+10 | 0.00 | 12.86 |
September | 0.00 | 0.418656E+10 | 0.00 | 0.146245E+10 | 0.00 | 0.00 | 0.242226E+11 | 0.00 | 12.92 |
October | 0.00 | 0.200392E+09 | 0.00 | 0.214846E+10 | 0.00 | 0.00 | 0.426673E+11 | 0.00 | 12.89 |
November | 0.00 | 0.00 | 0.00 | 0.214955E+10 | 0.00 | 0.00 | 0.491306E+11 | 0.00 | 12.83 |
December | 0.00 | 0.00 | 0.00 | 0.214545E+10 | 0.00 | 0.00 | 0.494826E+11 | 0.00 | 12.83 |
Annual Sum or Average | 0.00 | 0.501672E+11 | 0.00 | 0.205094E+11 | 0.00 | 0.00 | 0.422150E+12 | 0.00 | 12.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.146859E+09 | 0.00 | 0.00 | 0.920963E+09 | 0.00 | 12.67 |
Maximum of Months | 0.00 | 0.237440E+11 | 0.00 | 0.225965E+10 | 0.00 | 0.00 | 0.495936E+11 | 0.00 | 12.99 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.302498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155560E+10 | 0.00 | 0.00 | 0.27 |
February | 0.317007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100106E+10 | 0.00 | 0.00 | 0.28 |
March | 0.421972E+10 | 0.00 | 0.00 | 5209654.21 | 0.00 | 0.00 | 0.488352E+09 | 0.00 | 0.29 |
April | 0.264824E+10 | 0.00 | 0.00 | 49018513.62 | 0.00 | 0.00 | 0.299114E+10 | 0.00 | 0.38 |
May | 0.647966E+09 | 25924958.54 | 0.00 | 0.154271E+09 | 0.00 | 0.00 | 0.639824E+10 | 0.00 | 0.54 |
June | 619718.07 | 0.188170E+10 | 0.00 | 0.170406E+09 | 0.00 | 0.00 | 0.274384E+10 | 0.00 | 0.70 |
July | 0.00 | 0.569917E+10 | 0.00 | 56853368.92 | 0.00 | 0.00 | 0.197280E+09 | 0.00 | 0.75 |
August | 0.00 | 0.335948E+10 | 0.00 | 0.253140E+09 | 0.00 | 0.00 | 0.181730E+10 | 0.00 | 0.75 |
September | 0.225294E+09 | 0.930017E+09 | 0.00 | 0.193324E+09 | 0.00 | 0.00 | 0.404450E+10 | 0.00 | 0.63 |
October | 0.118724E+10 | 48355258.09 | 0.00 | 0.130686E+09 | 0.00 | 0.00 | 0.537382E+10 | 0.00 | 0.52 |
November | 0.360010E+10 | 0.00 | 0.00 | 15498987.74 | 0.00 | 67896598.80 | 0.133835E+10 | 0.00 | 0.31 |
December | 0.433773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175880E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.230620E+11 | 0.119446E+11 | 0.00 | 0.102841E+10 | 0.00 | 0.280043E+10 | 0.253928E+11 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.433773E+10 | 0.569917E+10 | 0.00 | 0.253140E+09 | 0.00 | 0.155560E+10 | 0.639824E+10 | 0.00 | 0.75 |