Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:49
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2020-06-03 19:49:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10069.79 | 887.57 | 887.57 |
Net Site Energy | 10069.79 | 887.57 | 887.57 |
Total Source Energy | 21106.65 | 1860.39 | 1860.39 |
Net Source Energy | 21106.65 | 1860.39 | 1860.39 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1112.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 616.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 525.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 182.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.47 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 971.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 664.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 36.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 106.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.56 | 2275.68 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 48.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4892.46 | 5177.32 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 1112.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 616.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 525.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 182.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 664.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 36.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 106.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.56 | 2275.68 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 18.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 23.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 62.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 124.15 | 298.67 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 244.63 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 431.23 | 456.34 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 62.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 124.15 | 298.67 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 244.63 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 431.23 | 456.34 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 4892.464 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 4892.464 | 100.00 |
Total On-Site and Utility Electric Sources | 4892.464 | 100.00 |
Total Electricity End Uses | 4892.464 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 95.34 | 2.20 |
Air to Air Heat Recovery for Heating | 4231.63 | 97.80 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4326.98 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 586.50 |
Time Setpoint Not Met During Occupied Cooling | 8599.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8760.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:49 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.8889 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 9.0417 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.0417 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.0903 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 6.4583 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 5.4896 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 6.4583 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 6.4583 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 4.4132 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 5.3388 | 7.60 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 5.3388 | 7.60 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-19:40 | 02-FEB-20:00 | - | - | - | 10-APR-20:19 |
Heating | 0.00 | 416993.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 161986.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 47387.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86131.51 | 89710.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 50267.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28071.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3450.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4880.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3893.47 | 177400.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1914.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 399615.74 | 684105.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 416993.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 161986.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 47387.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1228.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28071.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3450.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 4880.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3893.47 | 177400.78 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 938.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 734.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1206.27 | 0.00 | 0.00 | 0.00 |
Cooling | 1953.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1665.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 578.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.69 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3078.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2103.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 116.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 337.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 286.82 | 2466.83 | 0.00 | 0.00 | 0.00 |
Refrigeration | 153.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 15494.43 | 5612.22 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 106.32 | 0.00 | 0.00 | 0.00 |
Cooling | 172.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 146.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 185.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 10.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 29.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.28 | 217.43 | 0.00 | 0.00 | 0.00 |
Refrigeration | 13.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1365.72 | 494.67 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 106.32 | 0.00 | 0.00 | 0.00 |
Cooling | 172.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 146.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 185.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 10.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 29.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.28 | 217.43 | 0.00 | 0.00 | 0.00 |
Refrigeration | 13.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1365.72 | 494.67 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.28 | 0.661440 | 0.562000 | 1.28 | 1.00 | 0.500000 | 0.000576 | 0.000176 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.297573 | 0.171751 | 0.399000 | 0.118732 | 0.475769 | 0.500000 | 0.002218 | 0.000115 | 0.191213 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.211713 | 0.279547 | 0.650000 | 0.137614 | 0.745458 | 0.500000 | 0.001363 | 0.000040 | 0.137614 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.218577 | 0.572583 | 0.010000 | 0.002186 | 1.00 | 0.500000 | 0.000665 | 0.000053 | 0.088691 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.086367 | 0.836041 | 1.00 | 0.086367 | 1.00 | 0.500000 | 0.000456 | 0.000042 | 0.086367 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.41 | 0.017459 | 0.010000 | 0.034060 | 0.300000 | 0.500000 | 0.021822 | 0.000072 | 0.119000 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.29 | 0.111741 | 0.787000 | 1.01 | 0.787000 | 0.500000 | 0.003410 | 0.000357 | 1.01 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.24 | 0.235213 | 0.670000 | 2.84 | 0.670000 | 0.500000 | 0.001620 | 0.000822 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.600000 | 0.712143 | 1.00 | 0.500000 | 0.000381 | 0.000331 | 0.712143 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.07 | 0.122026 | 0.860000 | 1.78 | 0.860000 | 0.500000 | 0.003122 | 0.000369 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.18 | 0.115972 | 0.817000 | 1.78 | 0.817000 | 0.500000 | 0.003285 | 0.000372 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.27 | 0.700000 | 0.242000 | 0.550158 | 0.300000 | 0.500000 | 0.011003 | 0.000141 | 0.550158 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.519822 | 0.604128 | 0.362000 | 0.188176 | 1.00 | 0.500000 | 0.000631 | 0.000221 | 0.366989 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7982.30 | 0.000176 | 143.15 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5216.54 | 0.000115 | 113.07 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1824.88 | 0.000040 | 35.48 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2419.62 | 0.000053 | 52.44 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1898.01 | 0.000042 | 39.27 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 3246.45 | 0.000072 | 70.37 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 16167.63 | 0.000357 | 319.80 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 37220.33 | 0.000822 | 722.99 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 7677.65 | 0.000170 | 174.79 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 7697.68 | 0.000170 | 175.25 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 43280.33 | 0.000956 | 985.35 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 43636.09 | 0.000964 | 993.44 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 7642.96 | 0.000169 | 174.00 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 7662.89 | 0.000169 | 174.46 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14963.55 | 0.000331 | 307.25 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 2355.67 | 0.000052 | 53.63 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 2367.28 | 0.000052 | 53.89 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 11254.55 | 0.000249 | 256.22 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 16707.32 | 0.000369 | 310.74 |
DINING_FLR_6 VAV BOX REHEAT COIL | 16847.19 | 0.000372 | 313.65 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6361.90 | 0.000141 | 121.46 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10013.73 | 0.000221 | 217.05 |
VAV WITH REHEAT_HEATC | 291811.00 | 0.006447 | 3715.55 |
FLR_3_DOAS_HEATC | 30467.96 | 0.000673 | 387.94 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 1.07 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 1.05 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 5.10 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 5.29 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 0.948604 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 0.943568 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.278322 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.273529 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.05 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.07 | 0.000170 | 0.000337 |
ROOM_2_FLR_3 FAN COIL | 1.05 | 0.000170 | 0.000331 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.10 | 0.000956 | 0.001586 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.29 | 0.000964 | 0.001764 |
ROOM_5_FLR_3 FAN COIL | 0.948604 | 0.000169 | 0.000302 |
ROOM_6_FLR_3 FAN COIL | 0.943568 | 0.000169 | 0.000300 |
ROOM_1_FLR_6 FAN COIL | 0.278322 | 0.000052 | 0.000088 |
ROOM_2_FLR_6 FAN COIL | 0.273529 | 0.000052 | 0.000086 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.05 | 0.000249 | 0.000342 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 1.07 |
ROOM_2_FLR_3 FAN COILFAN | 1.05 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 5.10 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 5.29 |
ROOM_5_FLR_3 FAN COILFAN | 0.948604 |
ROOM_6_FLR_3 FAN COILFAN | 0.943568 |
ROOM_1_FLR_6 FAN COILFAN | 0.278322 |
ROOM_2_FLR_6 FAN COILFAN | 0.273529 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.05 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000337 | 1.07 | 0.008706 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000331 | 1.05 | 0.008709 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.001586 | 5.10 | 0.008649 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.001764 | 5.29 | 0.008917 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000302 | 0.948604 | 0.008734 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000300 | 0.943568 | 0.008735 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000088 | 0.278322 | 0.008697 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000086 | 0.273529 | 0.008700 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000342 | 1.05 | 0.008819 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.017366 | 0.012437 | 27.41 | 6.70 | 10.90 | 0.008683 | 607211.53 | 19.65 | |
FLR_3_DOAS_COOLC | 0.002508 | 0.015344 | 31.20 | 6.70 | 10.91 | 0.008683 | 87700.73 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.99 | 10.53 | 20.26 | 10.53 | 19.65 | 19.65 | 0.300000 | 0.535750 | 19.65 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 19.65 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT HEAT RECOVERY | 9.33 |
FLR_3_DOAS HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 19.65 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.017366 | 0.000027 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.006447 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002508 | 0.000190 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000673 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.025011 | 4736.85 |
HEATSYS1 PUMP | 0.013184 | 3334.96 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.013184 | 1.58 |
COOLSYS1 | 0.025011 | 3.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.025011 | 1578.95 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 596723.50 | 596723.50 | 0.013184 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.025011 | 874501.25 | 875069.10 | 99.76 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.889 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.269 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.042 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.802 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.042 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.802 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 10.226 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.606 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 4.090 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.780 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 6.458 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.838 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 5.490 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.560 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 6.458 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 74.278 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 6.458 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 74.278 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 13631.969 | 6.889 | 128.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13631.969 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 606.438 | 9.042 | 56.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 606.438 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 702.258 | 9.042 | 56.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 702.258 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 1679.504 | 10.226 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1679.504 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 387.593 | 4.090 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 387.593 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1219.735 | 6.458 | 8.572 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1219.735 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 7181.411 | 5.490 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7181.411 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 1718.522 | 4.413 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.522 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2141.959 | 6.458 | 8.571 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2141.959 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2141.959 | 6.458 | 8.571 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2141.959 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.036 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.036 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 1818.790 | 4.413 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.790 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4874 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.884 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.22071239E-14 | -0.25891382E-15 | -0.17018650E-09 | -0.41695020E-16 |
25 | 8 | 0.24744598E-07 | 0.66649001E-13 | 0.40731198E-03 | -0.28135460E-09 |
26 | 7 | -0.13120292E-01 | 0.33703133E-08 | -0.24350396E-01 | 0.14918252E-03 |
27 | 6 | 0.42922440 | 0.11607716E-05 | 0.49237259 | -0.50291810E-02 |
28 | 5 | -5.4235101 | 0.42968024E-04 | -4.5968048 | 0.66072313E-01 |
29 | 4 | 34.033019 | 0.34874410E-03 | 22.047808 | -0.43580094 |
30 | 3 | -113.41739 | 0.75474606E-03 | -56.824750 | 1.5468526 |
31 | 2 | 199.30218 | 0.42189037E-03 | 78.976973 | -2.9351941 |
32 | 1 | -171.96619 | 0.44777434E-04 | -55.576854 | 2.7596376 |
33 | 0 | 57.057407 | 0.25325413E-06 | 15.506813 | |
34 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
35 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
36 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
37 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
38 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
39 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
40 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
41 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
42 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
43 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
44 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
45 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
46 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
47 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
48 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
49 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
59 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
60 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
61 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
62 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
63 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
64 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
65 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
66 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
67 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
68 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
69 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
70 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
71 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
72 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
73 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
74 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
75 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
76 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
77 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
78 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
79 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
80 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
81 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
82 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
83 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
84 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
85 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
86 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
87 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
88 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
89 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.34_SHGC_0.38 | 31 | 1 | VerySmooth | 1.931 | 0.374 | 0.294 | 0.419 |
2 | RESWINDOW_U_0.35_SHGC_0.38 | 32 | 1 | VerySmooth | 1.988 | 0.374 | 0.294 | 0.419 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.84193E-002 | 0.29373 | 0.50285 | 0.50285 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11150 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.75028E-002 | 0.29373 | 0.50179 | 0.50179 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11365 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 29926.55388 | 29926.55388 | 2.27968 | 2.27968 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.48300 | 1.53444E-002 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 1530.51374 | 1530.51374 | 6.87787E-002 | 0.85413 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 3905.49739 | 3905.49739 | 0.29757 | 0.29757 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53444E-002 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 4255.82979 | 4255.82979 | 0.19121 | 0.19121 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2778.87825 | 2778.87825 | 0.21171 | 0.21171 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.14000 | 1.53444E-002 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1132.79840 | 1132.79840 | 5.09039E-002 | 9.16993E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2869.67300 | 2869.67300 | 0.21858 | 0.21858 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.88200 | 1.53444E-002 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1973.71130 | 1973.71130 | 8.86913E-002 | 8.86913E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1133.89971 | 1133.89971 | 8.63672E-002 | 8.63672E-002 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53444E-002 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1463.76817 | 1463.76817 | 6.57758E-002 | 6.57758E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44710.47321 | 44710.47321 | 3.40602 | 3.40602 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53444E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2648.37551 | 2648.37551 | 0.11900 | 0.11900 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 16889.15520 | 16889.15520 | 1.28791 | 1.28791 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53444E-002 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 11074.55379 | 11074.55379 | 0.49758 | 0.67613 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 55610.19355 | 55610.19355 | 4.23802 | 4.23802 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 22944.33086 | 22944.33086 | 1.03102 | 1.89326 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10387.25645 | 10387.25645 | 1.06630 | 1.06630 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 7677.65443 | 7677.65443 | 0.34701 | 0.34701 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10213.39114 | 10213.39114 | 1.04845 | 1.04845 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 7697.67765 | 7697.67765 | 0.34791 | 0.34791 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 49652.33506 | 49652.33506 | 5.09659 | 5.09659 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 43280.32944 | 43280.32944 | 1.95626 | 1.95626 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 51517.54717 | 51517.54717 | 5.28847 | 5.28847 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53444E-002 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 43636.09093 | 43636.09093 | 1.97234 | 1.97234 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9240.70666 | 9240.70666 | 0.94860 | 0.94860 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53444E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 7642.95572 | 7642.95572 | 0.34544 | 0.34544 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9191.65438 | 9191.65438 | 0.94357 | 0.94357 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.03433 | 1.53444E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 7662.89120 | 7662.89120 | 0.34634 | 0.34634 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 9214.17655 | 9214.17655 | 0.70181 | 1.18691 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53444E-002 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 11380.38377 | 11380.38377 | 0.51141 | 0.51141 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2711.24838 | 2711.24838 | 0.27832 | 0.27832 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2355.66835 | 2355.66835 | 0.10647 | 0.10647 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2664.55808 | 2664.55808 | 0.27353 | 0.27353 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2367.27610 | 2367.27610 | 0.10699 | 0.10699 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10237.96359 | 10237.96359 | 1.05099 | 1.05099 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 11254.55442 | 11254.55442 | 0.50868 | 0.50868 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 27153.05481 | 27153.05481 | 2.07105 | 2.07105 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53444E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7744.71125 | 7744.71125 | 0.34802 | 1.18734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 28571.05969 | 28571.05969 | 2.17917 | 2.17917 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53444E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 7888.12952 | 7888.12952 | 0.35446 | 1.18734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29765.62093 | 29765.62093 | 2.27338 | 2.27338 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.67033 | 1.53444E-002 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3597.96845 | 3597.96845 | 0.16166 | 0.36721 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 6824.77815 | 6824.77815 | 0.51982 | 0.51982 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53444E-002 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8166.73219 | 8166.73219 | 0.36699 | 0.36699 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -26.20000 | 3.61342E-004 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 331235.22 | 19.64563 | 19.64563 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 376303.57 | 7.60018 | 7.60018 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 43559.48 | 14.80124 | 2.05120 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 101559.87 | 6.03745 | 2.05120 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27968 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.66144 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.56200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28118 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.76016E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.76359E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28118 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7982.30498 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.76359E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.15394 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.29757 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17175 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39900 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11873 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47577 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.21833E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15253E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19121 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5216.54018 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15253E-004 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 113.06588 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21171 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27955 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.65000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13761 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74546 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36292E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.03184E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13761 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1824.87699 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.03184E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 35.47960 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.21858 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.57258 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.18577E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.65405E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.34585E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.86913E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2419.61988 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.34585E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 52.44405 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.63672E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.83604 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.63672E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.55719E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.19343E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.63672E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1898.01380 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.19343E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 39.27372 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.40602 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.74591E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.40602E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18224E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.17264E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11900 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3246.45152 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.17264E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 70.36504 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28791 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11174 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.78700 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01359 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78700 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.40967E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.57204E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01359 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16167.62993 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.57204E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 319.79847 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.23802 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23521 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.67000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.83947 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67000 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61981E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.22338E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.83947 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37220.32514 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.22338E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 722.98614 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06630 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.06630 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.06630 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69628E-004 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.36816E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.36816E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.06630 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.70556E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70994 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7677.65443 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69628E-004 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 174.79360 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04845 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.04845 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.04845 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.70071E-004 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.31450E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.31450E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.04845 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.70867E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70993 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7697.67765 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70071E-004 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 175.24937 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.09659 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.09659 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.09659 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.56226E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.58601E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.58601E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.09659 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.64913E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.71073 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 43280.32944 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.56226E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 985.34573 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.28847 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.28847 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.28847 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.64086E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.76381E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.76381E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.28847 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.91701E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70977 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 43636.09093 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.64086E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 993.44381 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94860 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94860 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.94860 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.68862E-004 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.01866E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.01866E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.94860 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.73371E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70989 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7642.95572 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.68862E-004 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 174.00378 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94357 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94357 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.94357 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.69302E-004 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.00371E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.00371E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.94357 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.73507E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70988 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7662.89120 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69302E-004 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 174.45755 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60000 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71214 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.30601E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71214 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14963.54782 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.30601E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 307.24815 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.27832 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27832 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.27832 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.20456E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.77216E-005 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 8.77216E-005 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.27832 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.69725E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70996 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 2355.66835 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.20456E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 53.62855 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.27353 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.27353 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.27353 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.23021E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.62806E-005 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 8.62806E-005 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.27353 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.70030E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70995 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 2367.27610 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.23021E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 53.89276 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05099 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.05099 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.05099 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.48656E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.41905E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.41905E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.05099 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.81879E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70970 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 11254.55442 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.48656E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 256.21812 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.07105 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12203 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.86000 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78111 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86000 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.12228E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.69128E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78111 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16707.31680 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.69128E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 310.74458 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.17917 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11597 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.81700 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78038 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81700 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.28527E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.72218E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78038 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16847.19028 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.72218E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 313.65213 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.27338 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24200 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55016 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10033E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40558E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55016 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6361.89537 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40558E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 121.46009 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.51982 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60413 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36200 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18818 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.30661E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.21241E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36699 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10013.73301 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.21241E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 217.05245 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.98953 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.52516 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.25619 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.52516 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 19.64563 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 19.64563 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.53575 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 19.64563 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 19.64563 |
346 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32560 |
347 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 607211.52549 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.73662E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 19.64563 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.24367E-002 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 27.41204 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.90223 |
354 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.68318E-003 |
355 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 291810.99861 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.44721E-003 |
357 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 3715.54512 |
358 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 19.64563 |
359 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.73662E-002 |
360 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.74206E-005 |
361 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.44721E-003 |
362 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
363 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
364 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05120 |
365 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 87700.73147 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 2.50823E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.53444E-002 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 31.20000 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
371 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.91216 |
372 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.68318E-003 |
373 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 30467.96244 |
374 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.73152E-004 |
375 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 387.93976 |
376 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
377 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.50823E-003 |
378 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.89851E-004 |
379 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.73152E-004 |
380 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.50106E-002 |
381 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 4736.85156 |
382 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
383 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
384 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
385 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
386 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
387 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.31839E-002 |
388 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.58207 |
389 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.31839E-002 |
390 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3334.96182 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 596723.50499 |
392 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 596723.50000 |
393 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.31839E-002 |
394 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.50106E-002 |
395 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.00127 |
396 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.50106E-002 |
397 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 1578.95052 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.50106E-002 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 874501.24876 |
400 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 875069.10000 |
401 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 99.75788 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8027.71 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5246.61 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1836.88 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2433.57 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1909.47 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 3265.17 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 16271.87 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 37465.47 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 8285.11 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 8306.71 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 46705.20 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 47089.06 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 8247.67 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 8269.18 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15055.42 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 2541.99 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 2554.51 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 12144.74 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 16799.41 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 16939.99 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6395.54 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10071.46 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 177515.64 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 18534.39 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 17849.57 | 14916.98 | 2932.60 | 0.84 | 4158.50 | 42.18 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 17560.53 | 14670.49 | 2890.05 | 0.84 | 4086.11 | 41.44 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 84445.18 | 71011.79 | 13433.40 | 0.84 | 20113.43 | 204.00 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 91831.14 | 75092.74 | 16738.40 | 0.82 | 19924.60 | 202.09 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 15958.88 | 13296.56 | 2662.32 | 0.83 | 3677.35 | 37.30 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 15877.98 | 13227.24 | 2650.74 | 0.83 | 3656.81 | 37.09 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 4652.12 | 3891.32 | 760.81 | 0.84 | 1087.44 | 11.03 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 4574.51 | 3825.12 | 749.38 | 0.84 | 1067.99 | 10.83 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 17946.67 | 14820.21 | 3126.46 | 0.83 | 4013.31 | 40.71 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 607275.27 | 386434.81 | 220840.46 | 0.64 | 115823.41 | 1174.75 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 67246.26 | 42001.83 | 25244.43 | 0.62 | 10754.43 | 109.08 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 4.04 | 13.79 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.35_SHGC_0.38 | N/A | 1.988 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.34_SHGC_0.38 | N/A | 1.931 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.9740598122E-002 | 3.8621678903E-002 | Pass | Pass | 1.6016766736E-002 | 9.0166485367E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7689819805E-003 | 1.4934471224E-002 | Pass | Pass | 6.9653045874E-002 | 0.1740590794 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.7428131192E-002 | 4.9661979175E-002 | Pass | Pass | 1.2165735800E-002 | 8.2417723560E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.0014413982E-002 | 2.4580127920E-002 | Pass | Pass | 1.1143944214E-002 | 8.6376525340E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.3452434197E-004 | 2.9827589202E-003 | Pass | Pass | 0.1683297033 | 1.0156407984 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1545241764 | 0.3684628158 | Pass | Pass | 2.4356934952E-002 | 8.8708009192E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.7547069619E-002 | 9.2430996440E-002 | Pass | Pass | 0.1018276401 | 0.3432571405 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.8838956650E-002 | 7.1456787241E-002 | Pass | Pass | 1.6080228282E-002 | 8.2021670136E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2595133111E-002 | 0.3215160101 | Pass | Pass | 0.1287007095 | 0.8038488554 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2596913581E-002 | 0.3260812233 | Pass | Pass | 0.1137089268 | 0.6650950989 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 1.4864520376E-002 | 3.1229290891E-002 | Pass | Pass | 0.1823046741 | 0.7395898991 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.4118298751E-002 | 0.1141114412 | Pass | Pass | 8.6619113574E-002 | 0.1927096408 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2593649831E-002 | 0.3175065512 | Pass | Pass | 0.1096069194 | 0.5512376781 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2595284319E-002 | 0.3219457413 | Pass | Pass | 0.1264711916 | 0.7803737249 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.8294319971E-003 | 9.1224905662E-003 | Pass | Pass | 8.1022193157E-003 | 8.0992384362E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2594183882E-002 | 0.3399930232 | Pass | Pass | 0.1821346852 | 0.8232391992 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2594459030E-002 | 0.3428664923 | Pass | Pass | 0.1753928586 | 0.8291468641 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.5508972672E-002 | 0.2811140541 | Pass | Pass | 6.1314644582E-002 | 0.1190290876 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.4788185225E-002 | 0.1180732297 | Pass | Pass | 1.5749914625E-002 | 7.4946887410E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.0903233695E-002 | 0.1190974769 | Pass | Pass | 1.4298387772E-002 | 7.1455854832E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1389804048 | 0.2247822678 | Pass | Pass | 2.1095112948E-002 | 8.1161162887E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 1.1284152251E-003 | 7.0334226201E-003 | Pass | Pass | 4.7855056998E-002 | 0.1178612196 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.354 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.354 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.354 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.354 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 1.931 | 0.374 | 0.419 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 1.931 | 0.374 | 0.419 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 1.931 | 0.374 | 0.419 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 1.988 | 0.374 | 0.419 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 1.988 | 0.374 | 0.419 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 1.988 | 0.374 | 0.419 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 1.988 | 0.374 | 0.419 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 1.988 | 0.374 | 0.419 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 1.988 | 0.374 | 0.419 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 1.988 | 0.374 | 0.419 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 1.988 | 0.374 | 0.419 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 1.988 | 0.374 | 0.419 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 1.988 | 0.374 | 0.419 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 1.931 | 0.374 | 0.419 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 1.931 | 0.374 | 0.419 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 1.931 | 0.374 | 0.419 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 1.931 | 0.374 | 0.419 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.988 | 0.374 | 0.419 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 1.988 | 0.374 | 0.419 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.988 | 0.374 | 0.419 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 1.988 | 0.374 | 0.419 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.35_SHGC_0.38 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 1.988 | 0.374 | 0.419 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 1.931 | 0.374 | 0.419 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 1.931 | 0.374 | 0.419 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.931 | 0.374 | 0.419 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 1.931 | 0.374 | 0.419 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 1.931 | 0.374 | 0.419 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 1.931 | 0.374 | 0.419 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 1.931 | 0.374 | 0.419 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.34_SHGC_0.38 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 1.931 | 0.374 | 0.419 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 1.972 | 0.374 | 0.419 | ||||||||||||
North Total or Average | 432.93 | 1.974 | 0.374 | 0.419 | ||||||||||||
Non-North Total or Average | 781.15 | 1.970 | 0.374 | 0.419 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 6.8889 | 1978.83 | 13631.97 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 52.48 | 168.00 | 52.43 | 0.0000 | Y | 134.15 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 9.0417 | 67.07 | 606.44 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 6.67 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 9.0417 | 77.67 | 702.26 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.73 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 10.2257 | 164.24 | 1679.50 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.48 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 4.0903 | 94.76 | 387.59 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 26.12 | 168.00 | 26.09 | 0.0000 | Y | 1.90 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 5.7049 | 78.04 | 445.21 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 6.4583 | 188.86 | 1219.74 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 38.80 | 0.0000 | Y | 8.88 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 5.4896 | 1308.19 | 7181.41 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 55.23 | 0.0000 | Y | 74.46 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 4.4132 | 156.09 | 688.85 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 4.4132 | 156.07 | 688.77 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 4.4132 | 1863.81 | 8225.38 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 65.84 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 4.4132 | 1864.32 | 8227.63 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 65.86 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 4.4132 | 156.09 | 688.85 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 4.4132 | 156.07 | 688.77 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 4.4132 | 1557.62 | 6874.09 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 41.03 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 4.4132 | 39.02 | 172.21 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 1.38 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 4.4132 | 39.02 | 172.19 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 1.38 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 4.4132 | 220.77 | 974.32 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 7.80 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 6.4583 | 331.66 | 2141.96 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 48.78 | 0.0000 | Y | 19.61 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 6.4583 | 331.66 | 2141.96 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 48.78 | 0.0000 | Y | 19.61 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 11.7327 | 103.30 | 1212.04 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 4.4132 | 412.12 | 1818.79 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 10.86 |
Interior Lighting Total | 5.3388 | 11345.29 | 60569.92 | 341.72 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1219.74 | 475.70 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1219.74 | 475.70 |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 7181.41 | 502.70 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 7181.41 | 502.70 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11632.50 | AstronomicalClock | - | 83.63 | 83.63 | 182.61 | |
Exterior Lighting Total | 11632.50 | 182.61 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 596723.50 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 875069.10 | 2.96 | 4.04 | 13.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11777.05 | 17849.57 | 14916.98 | 2932.60 | 0.84 | - | 4158.50 | 42.18 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11589.43 | 17560.53 | 14670.49 | 2890.05 | 0.84 | - | 4086.11 | 41.44 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 55456.04 | 84445.18 | 71011.79 | 13433.40 | 0.84 | - | 20113.43 | 204.00 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 61672.97 | 91831.14 | 75092.74 | 16738.40 | 0.82 | - | 19924.60 | 202.09 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 10555.01 | 15958.88 | 13296.56 | 2662.32 | 0.83 | - | 3677.35 | 37.30 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 10502.72 | 15877.98 | 13227.24 | 2650.74 | 0.83 | - | 3656.81 | 37.09 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3067.26 | 4652.12 | 3891.32 | 760.81 | 0.84 | - | 1087.44 | 11.03 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3016.87 | 4574.51 | 3825.12 | 749.38 | 0.84 | - | 1067.99 | 10.83 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 11954.99 | 17946.67 | 14820.21 | 3126.46 | 0.83 | - | 4013.31 | 40.71 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 607211.53 | 607275.27 | 386434.81 | 220840.46 | 0.64 | - | 115823.41 | 1174.75 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 87700.73 | 67246.26 | 42001.83 | 25244.43 | 0.62 | - | 10754.43 | 109.08 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7982.30 | 8027.71 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5216.54 | 5246.61 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1824.88 | 1836.88 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2419.62 | 2433.57 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1898.01 | 1909.47 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 3246.45 | 3265.17 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16167.63 | 16271.87 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 37220.33 | 37465.47 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7677.65 | 8285.11 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7697.68 | 8306.71 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 43280.33 | 46705.20 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 43636.09 | 47089.06 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7642.96 | 8247.67 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7662.89 | 8269.18 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14963.55 | 15055.42 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 2355.67 | 2541.99 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 2367.28 | 2554.51 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 11254.55 | 12144.74 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 16707.32 | 16799.41 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 16847.19 | 16939.99 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6361.90 | 6395.54 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10013.73 | 10071.46 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 291811.00 | 177515.64 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 30467.96 | 18534.39 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.07 | 750.29 | 703.64 | 1.00 | 1.18 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 737.73 | 703.64 | 1.00 | 1.19 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.10 | 3586.14 | 703.64 | 1.00 | 0.97 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.29 | 3721.16 | 703.64 | 1.00 | 0.97 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.95 | 667.47 | 703.64 | 1.00 | 1.21 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.94 | 663.93 | 703.64 | 1.00 | 1.21 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.28 | 195.84 | 703.64 | 1.00 | 1.77 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.27 | 192.47 | 703.64 | 1.00 | 1.78 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 739.51 | 703.64 | 1.00 | 1.18 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 19.65 | 44018.77 | 2240.64 | 1.00 | 1.12 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 134283.83 | 0.025011 | 4736.85 | 189393.57 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.013184 | 3334.96 | 252957.60 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.025011 | 1578.95 | 63131.19 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 29926.55 | 29926.55 | 15.12 | 2.280 | 2.280 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 24.00 | 24.00 | 0.00931 | 26.48 | 0.01534 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3905.50 | 3905.50 | 58.23 | 0.298 | 0.298 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00949 | 30.85 | 0.01534 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2778.88 | 2778.88 | 35.78 | 0.212 | 0.212 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00963 | 30.14 | 0.01534 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44710.47 | 44710.47 | 572.92 | 3.406 | 3.406 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00857 | 31.20 | 0.01534 | 0.000 | 0.00 |
CAFE_FLR_1 | 16889.16 | 16889.16 | 89.43 | 1.288 | 1.288 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01057 | 30.85 | 0.01534 | 0.676 | 0.00 |
LOBBY_FLR_1 | 55610.19 | 55610.19 | 42.51 | 4.238 | 4.238 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01033 | 30.93 | 0.01534 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 10387.26 | 10387.26 | 266.19 | 1.066 | 1.066 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00871 | 29.36 | 0.01534 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10213.39 | 10213.39 | 261.76 | 1.048 | 1.048 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00871 | 29.36 | 0.01534 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 49652.34 | 49652.34 | 2024.66 | 5.097 | 5.097 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00865 | 30.93 | 0.01534 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 51517.55 | 51517.55 | 2100.14 | 5.288 | 5.288 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00892 | 31.20 | 0.01534 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9240.71 | 9240.71 | 236.81 | 0.949 | 0.949 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00873 | 25.37 | 0.01534 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9191.65 | 9191.65 | 235.58 | 0.944 | 0.944 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 21.11 | 21.11 | 0.00874 | 25.03 | 0.01534 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2711.25 | 2711.25 | 69.48 | 0.278 | 0.278 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00870 | 29.36 | 0.01534 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2664.56 | 2664.56 | 68.29 | 0.274 | 0.274 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00870 | 29.36 | 0.01534 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10237.96 | 10237.96 | 417.36 | 1.051 | 1.051 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00882 | 30.93 | 0.01534 | 0.099 | 0.00 |
BANQUET_FLR_6 | 27153.05 | 27153.05 | 81.87 | 2.071 | 2.071 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01061 | 31.20 | 0.01534 | 1.187 | 0.00 |
DINING_FLR_6 | 28571.06 | 28571.06 | 86.15 | 2.179 | 2.179 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01051 | 31.20 | 0.01534 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 29765.62 | 29765.62 | 288.13 | 2.273 | 2.273 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 23.97 | 0.01008 | 25.67 | 0.01534 | 0.367 | 0.00 |
MECH_FLR_1 | 2869.67 | 2869.67 | 17.47 | 0.219 | 0.219 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00875 | 30.88 | 0.01534 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1133.90 | 1133.90 | 11.97 | 0.086 | 0.086 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00894 | 31.20 | 0.01534 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 9214.18 | 9214.18 | 23.66 | 0.702 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00876 | 31.20 | 0.01534 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 6824.78 | 6824.78 | 16.56 | 0.520 | 0.520 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00865 | 31.20 | 0.01534 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1530.51 | 1530.51 | 0.77 | 0.069 | 0.854 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -26.20 | 0.00036 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4255.83 | 4255.83 | 63.45 | 0.191 | 0.191 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00718 | -26.20 | 0.00036 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1132.80 | 1132.80 | 14.58 | 0.051 | 0.092 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00734 | -26.20 | 0.00036 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 2648.38 | 2648.38 | 33.94 | 0.119 | 0.119 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00716 | -26.20 | 0.00036 | 0.000 | 0.00 |
CAFE_FLR_1 | 11074.55 | 11074.55 | 58.64 | 0.498 | 0.676 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00720 | -26.20 | 0.00036 | 0.676 | 0.00 |
LOBBY_FLR_1 | 22944.33 | 22944.33 | 17.54 | 1.031 | 1.893 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00723 | -26.20 | 0.00036 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 7677.65 | 7677.65 | 196.75 | 0.347 | 0.347 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00745 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7697.68 | 7697.68 | 197.29 | 0.348 | 0.348 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00745 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 43280.33 | 43280.33 | 1764.83 | 1.956 | 1.956 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00748 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 43636.09 | 43636.09 | 1778.85 | 1.972 | 1.972 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00748 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7642.96 | 7642.96 | 195.86 | 0.345 | 0.345 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00745 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7662.89 | 7662.89 | 196.40 | 0.346 | 0.346 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00745 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2355.67 | 2355.67 | 60.37 | 0.106 | 0.106 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00754 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2367.28 | 2367.28 | 60.67 | 0.107 | 0.107 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00755 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11254.55 | 11254.55 | 458.80 | 0.509 | 0.509 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00756 | -26.20 | 0.00036 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7744.71 | 7744.71 | 23.35 | 0.348 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 1.187 | 0.00 |
DINING_FLR_6 | 7888.13 | 7888.13 | 23.78 | 0.354 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 3597.97 | 3597.97 | 34.83 | 0.162 | 0.367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00707 | -26.20 | 0.00036 | 0.367 | 0.00 |
MECH_FLR_1 | 1973.71 | 1973.71 | 12.02 | 0.089 | 0.089 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00718 | -26.20 | 0.00036 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1463.77 | 1463.77 | 15.45 | 0.066 | 0.066 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00723 | -26.20 | 0.00036 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 11380.38 | 11380.38 | 29.23 | 0.511 | 0.511 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00754 | -26.20 | 0.00036 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 8166.73 | 8166.73 | 19.82 | 0.367 | 0.367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00771 | -26.20 | 0.00036 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 19.65 | 19.65 | 7.60 | 7.60 | 19.6456 | 10.5252 | 19.6456 | 0.5358 | 0.3000 |
FLR_3_DOAS | 14.80 | 2.05 | 6.04 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7982.305 | 7982.305 | 1.281179 | 0.00017636 | 143.154 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8027.71 | 7982.30 | 1.281179 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00796605 | 49.1223 | 1530.51 | 0.00 | 8029.38 | 8029.38 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 5216.540 | 5216.540 | 0.191213 | 0.00011525 | 113.066 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5246.61 | 5216.54 | 0.191213 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00718188 | 44.3520 | 4255.83 | 0.00 | 5249.87 | 5249.87 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1824.877 | 1824.877 | 0.137614 | 0.00004032 | 35.480 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1836.88 | 1824.88 | 0.137614 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00734009 | 45.3096 | 1132.80 | 0.00 | 1837.28 | 1837.28 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2419.620 | 2419.620 | 0.088691 | 0.00005346 | 52.444 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2433.57 | 2419.62 | 0.088691 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00718466 | 44.3612 | 1973.71 | 0.00 | 2435.08 | 2435.08 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1898.014 | 1898.014 | 0.086367 | 0.00004193 | 39.274 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1909.47 | 1898.01 | 0.086367 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00723047 | 44.6412 | 1463.77 | 0.00 | 1910.35 | 1910.35 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 3246.452 | 3246.452 | 0.119000 | 0.00007173 | 70.365 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3265.17 | 3246.45 | 0.119000 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00715506 | 44.1841 | 2648.38 | 0.00 | 3267.19 | 3267.19 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 16167.630 | 16167.630 | 1.013587 | 0.00035720 | 319.798 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16271.87 | 16167.63 | 1.013587 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00720403 | 44.4865 | 11074.55 | 0.00 | 16276.65 | 16276.65 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 37220.325 | 37220.325 | 2.839471 | 0.00082234 | 722.986 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 37465.47 | 37220.33 | 2.839471 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00723085 | 44.6441 | 22944.33 | 0.00 | 37473.56 | 37473.56 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11777.052 | -999.000 | 1.066300 | 0.00033682 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 11777.05 | 11245.32 | 1.066300 | 21.71 | 15.26 | 0.00870556 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00870556 | 53.2585 | 10387.26 | 0.00 | 12341.37 | 12341.37 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 7677.654 | 7677.654 | 0.347007 | 0.00016963 | 174.794 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8285.11 | 7677.65 | 0.347007 | 21.11 | 13.91 | 0.00744908 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00744908 | 45.6661 | 7677.65 | 0.00 | 8288.07 | 8288.07 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11589.430 | -999.000 | 1.048452 | 0.00033145 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 11589.43 | 11058.62 | 1.048452 | 21.71 | 15.26 | 0.00870867 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00870867 | 53.2773 | 10213.39 | 0.00 | 12144.45 | 12144.45 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 7697.678 | 7697.678 | 0.347912 | 0.00017007 | 175.249 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8306.71 | 7697.68 | 0.347912 | 21.11 | 13.92 | 0.00745045 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00745045 | 45.6744 | 7697.68 | 0.00 | 8309.69 | 8309.69 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 55456.042 | -999.000 | 5.096586 | 0.00158601 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 55456.04 | 53616.84 | 5.096586 | 21.71 | 15.21 | 0.00864913 | 12.80 | 11.67 | 0.00850000 | 30.93 | 0.01534436 | 23.03 | 0.0000 | 21.11 | 0.00864913 | 52.9157 | 49652.34 | 0.00 | 58132.86 | 58132.86 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 43280.329 | 43280.329 | 1.956263 | 0.00095623 | 985.346 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 46705.20 | 43280.33 | 1.956263 | 21.11 | 13.94 | 0.00747971 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00747971 | 45.8482 | 43280.33 | 0.00 | 46722.29 | 46722.29 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 61672.966 | -999.000 | 5.288466 | 0.00176381 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 61672.97 | 56274.67 | 5.288466 | 21.71 | 15.44 | 0.00891701 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 0.0000 | 21.11 | 0.00891701 | 54.5337 | 51517.55 | 0.00 | 64548.54 | 60265.64 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 43636.091 | 43636.091 | 1.972343 | 0.00096409 | 993.444 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 47089.06 | 43636.09 | 1.972343 | 21.11 | 13.95 | 0.00748354 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00748354 | 45.8714 | 43636.09 | 0.00 | 47106.35 | 47106.35 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 10555.006 | -999.000 | 0.948604 | 0.00030187 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 10555.01 | 10016.51 | 0.948604 | 21.71 | 15.28 | 0.00873371 | 12.80 | 11.67 | 0.00850000 | 25.37 | 0.01534436 | 21.50 | 0.0000 | 21.11 | 0.00873371 | 53.4284 | 9240.71 | 0.00 | 11058.21 | 10809.26 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7642.956 | 7642.956 | 0.345438 | 0.00016886 | 174.004 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8247.67 | 7642.96 | 0.345438 | 21.11 | 13.91 | 0.00744676 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00744676 | 45.6520 | 7642.96 | 0.00 | 8250.62 | 8250.62 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 10502.723 | -999.000 | 0.943568 | 0.00030037 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | unknown | 7/21 08:50:00 | 10502.72 | 9963.94 | 0.943568 | 21.71 | 15.28 | 0.00873507 | 12.80 | 11.67 | 0.00850000 | 25.03 | 0.01534436 | 21.41 | 0.0000 | 21.11 | 0.00873507 | 53.4367 | 9191.65 | 0.00 | 11003.31 | 10751.85 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7662.891 | 7662.891 | 0.346339 | 0.00016930 | 174.458 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8269.18 | 7662.89 | 0.346339 | 21.11 | 13.91 | 0.00744814 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00744814 | 45.6603 | 7662.89 | 0.00 | 8272.14 | 8272.14 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14963.548 | 14963.548 | 0.712143 | 0.00033060 | 307.248 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15055.42 | 14963.55 | 0.712143 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00754205 | 46.5400 | 11380.38 | 0.00 | 15061.97 | 15061.97 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3067.259 | -999.000 | 0.278322 | 0.00008772 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3067.26 | 2934.13 | 0.278322 | 21.71 | 15.25 | 0.00869725 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00869725 | 53.2083 | 2711.25 | 0.00 | 3214.46 | 3214.46 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2355.668 | 2355.668 | 0.106469 | 0.00005205 | 53.629 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2541.99 | 2355.67 | 0.106469 | 21.11 | 14.00 | 0.00754491 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00754491 | 46.2463 | 2355.67 | 0.00 | 2542.96 | 2542.96 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3016.875 | -999.000 | 0.273529 | 0.00008628 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3016.87 | 2883.99 | 0.273529 | 21.71 | 15.25 | 0.00870030 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00870030 | 53.2268 | 2664.56 | 0.00 | 3161.57 | 3161.57 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2367.276 | 2367.276 | 0.106994 | 0.00005230 | 53.893 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2554.51 | 2367.28 | 0.106994 | 21.11 | 14.00 | 0.00754705 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00754705 | 46.2593 | 2367.28 | 0.00 | 2555.49 | 2555.49 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11954.994 | -999.000 | 1.050988 | 0.00034190 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 11954.99 | 11138.20 | 1.050988 | 21.71 | 15.36 | 0.00881879 | 12.80 | 11.67 | 0.00850000 | 30.93 | 0.01534436 | 23.03 | 0.0000 | 21.11 | 0.00881879 | 53.9419 | 10237.96 | 0.00 | 12518.18 | 11975.08 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11254.554 | 11254.554 | 0.508685 | 0.00024866 | 256.218 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12144.74 | 11254.55 | 0.508685 | 21.11 | 14.02 | 0.00756048 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00756048 | 46.3394 | 11254.55 | 0.00 | 12149.46 | 12149.46 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 16707.317 | 16707.317 | 1.781105 | 0.00036913 | 310.745 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16799.41 | 16707.32 | 1.781105 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765483 | 47.2287 | 7744.71 | 0.00 | 16804.75 | 16804.75 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 16847.190 | 16847.190 | 1.780381 | 0.00037222 | 313.652 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 16939.99 | 16847.19 | 1.780381 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766082 | 47.2653 | 7888.13 | 0.00 | 16945.42 | 16945.42 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6361.895 | 6361.895 | 0.550158 | 0.00014056 | 121.460 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 6395.54 | 6361.90 | 0.550158 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00706969 | 43.6656 | 3597.97 | 0.00 | 6398.07 | 6398.07 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 10013.733 | 10013.733 | 0.366989 | 0.00022124 | 217.052 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 10071.46 | 10013.73 | 0.366989 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00771096 | 47.5701 | 8166.73 | 0.00 | 10077.71 | 10077.71 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 607211.525 | -999.000 | 19.645634 | 0.01736617 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 607211.53 | 384610.70 | 19.645634 | 27.41 | 20.07 | 0.01243669 | 10.90 | 10.89 | 0.00868318 | 31.20 | 0.01534436 | 23.10 | 47.4691 | 23.99 | 0.00962255 | 49.3433 | 257651.65 | 0.00 | 657971.03 | 395123.95 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 291810.999 | 291810.999 | 5.893690 | 0.00644721 | 3715.545 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 177515.64 | 291811.00 | 5.893690 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.74 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 158.2302 | 21.00 | 0.00748975 | 46.2231 | 84847.89 | 0.00 | 177106.04 | 177106.04 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 87700.731 | -999.000 | 2.051199 | 0.00250823 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 87700.73 | 47797.05 | 2.051199 | 31.20 | 23.10 | 0.01534436 | 10.91 | 11.67 | 0.00868318 | 31.20 | 0.01534436 | 23.10 | 100.0000 | 21.11 | 0.00878459 | 53.7340 | 143339.11 | 0.00 | 93096.22 | 49675.25 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 30467.962 | 30467.962 | 0.615360 | 0.00067315 | 387.940 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 18534.39 | 30467.96 | 0.615360 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.74 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 333.3333 | 21.11 | 0.00748225 | 45.8637 | 133575.10 | 0.00 | 18491.63 | 18491.63 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7982.305 | 7982.305 | 1.281179 | 0.00017636 | 143.154 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 1.3188 | 1.337689 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8027.71 | 7982.30 | 1.0000 | 1.47150508 | 1.281179 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17634128 | 60.00 | 49.00 | 11.00 | 0.000 | 8027.71 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00796605 | 21.00 | 0.00796605 | 49.1223 | 1530.51 | 0.00 | 8029.38 | 8029.38 | 1.47150508 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 21.95 | 15.19 | 0.00800000 | 42391.3 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5216.540 | 5216.540 | 0.191213 | 0.00011525 | 113.066 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 0.8619 | 0.874197 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5246.61 | 5216.54 | 1.0000 | 0.21961840 | 0.191213 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.11524132 | 60.00 | 49.00 | 11.00 | 0.000 | 5246.61 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00718188 | 21.00 | 0.00718188 | 44.3520 | 4255.83 | 0.00 | 5249.87 | 5249.87 | 0.21961840 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60839.2 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1824.877 | 1824.877 | 0.137614 | 0.00004032 | 35.480 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 0.3018 | 0.305816 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1836.88 | 1824.88 | 1.0000 | 0.15805686 | 0.137614 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.04031431 | 60.00 | 49.00 | 11.00 | 0.000 | 1836.88 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00734009 | 21.00 | 0.00734009 | 45.3096 | 1132.80 | 0.00 | 1837.28 | 1837.28 | 0.15805686 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 28.00 | 17.34 | 0.00800000 | 48558.9 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2419.620 | 2419.620 | 0.088691 | 0.00005346 | 52.444 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 0.3998 | 0.405484 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2433.57 | 2419.62 | 1.0000 | 0.10186688 | 0.088691 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05345309 | 60.00 | 49.00 | 11.00 | 0.000 | 2433.57 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00718466 | 21.00 | 0.00718466 | 44.3612 | 1973.71 | 0.00 | 2435.08 | 2435.08 | 0.10186688 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60839.2 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1898.014 | 1898.014 | 0.086367 | 0.00004193 | 39.274 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 0.3137 | 0.318073 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1909.47 | 1898.01 | 1.0000 | 0.09919756 | 0.086367 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.04193002 | 60.00 | 49.00 | 11.00 | 0.000 | 1909.47 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00723047 | 21.00 | 0.00723047 | 44.6412 | 1463.77 | 0.00 | 1910.35 | 1910.35 | 0.09919756 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 35.49 | 19.78 | 0.00800000 | 56192.8 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3246.452 | 3246.452 | 0.119000 | 0.00007173 | 70.365 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 0.5364 | 0.544046 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3265.17 | 3246.45 | 1.0000 | 0.13667814 | 0.119000 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.07171906 | 60.00 | 49.00 | 11.00 | 0.000 | 3265.17 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00715506 | 21.00 | 0.00715506 | 44.1841 | 2648.38 | 0.00 | 3267.19 | 3267.19 | 0.13667814 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60839.0 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16167.630 | 16167.630 | 1.013587 | 0.00035720 | 319.798 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 2.6731 | 2.709401 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16271.87 | 16167.63 | 1.0000 | 1.16416108 | 1.013587 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.35716759 | 60.00 | 49.00 | 11.00 | 0.000 | 16271.87 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00720403 | 21.00 | 0.00720403 | 44.4865 | 11074.55 | 0.00 | 16276.65 | 16276.65 | 1.16416108 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 30.31 | 18.12 | 0.00800000 | 50916.2 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37220.325 | 37220.325 | 2.839471 | 0.00082234 | 722.986 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 6.1547 | 6.237449 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 37465.47 | 37220.33 | 1.0000 | 3.26129082 | 2.839471 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.82225372 | 60.00 | 49.00 | 11.00 | 0.000 | 37465.47 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00723085 | 21.00 | 0.00723085 | 44.6441 | 22944.33 | 0.00 | 37473.56 | 37473.56 | 3.26129082 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 27.87 | 17.29 | 0.00800000 | 48425.1 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11777.052 | -999.000 | 1.066300 | 0.00033682 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0232 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.066300 | 1.22470468 | 4197.9300 | 999.8980 | 25.00807367 | 15.03 | 6.70 | 8.33 | 874501.25 | 1.3467 | 1.346691 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 11777.05 | 11245.32 | 1.0000 | 1.22470468 | 1.066300 | 21.71 | 15.26 | 0.00870556 | 43938.4 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.33678154 | 6.70 | 13.38 | 8.33 | 0.000 | 11777.05 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00870556 | 21.11 | 0.00870556 | 53.2585 | 10387.26 | 0.00 | 12341.37 | 12341.37 | 1.22470468 | 21.71 | 15.73 | 0.00870556 | 43938.4 | 11.84 | 11.84 | 0.00870556 | 33861.4 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7677.654 | 7677.654 | 0.347007 | 0.00016963 | 174.794 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.066300 | 1.22470468 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 1.3610 | 1.286635 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8285.11 | 7677.65 | 1.0000 | 0.39855651 | 0.347007 | 21.11 | 13.91 | 0.00744908 | 40132.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.16961109 | 60.00 | 49.00 | 11.00 | 0.000 | 8285.11 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00744908 | 21.11 | 0.00744908 | 45.6661 | 7677.65 | 0.00 | 8288.07 | 8288.07 | 0.39855651 | 16.60 | 12.60 | 0.00744908 | 35539.9 | 37.01 | 19.84 | 0.00744908 | 56335.2 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11589.430 | -999.000 | 1.048452 | 0.00033145 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0290 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.048452 | 1.20420617 | 4197.9300 | 999.8980 | 25.00807367 | 15.03 | 6.70 | 8.33 | 874501.25 | 1.3253 | 1.325237 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 11589.43 | 11058.62 | 1.0000 | 1.20420617 | 1.048452 | 21.71 | 15.26 | 0.00870867 | 43946.3 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.33141622 | 6.70 | 13.38 | 8.33 | 0.000 | 11589.43 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00870867 | 21.11 | 0.00870867 | 53.2773 | 10213.39 | 0.00 | 12144.45 | 12144.45 | 1.20420617 | 21.71 | 15.74 | 0.00870867 | 43946.3 | 11.83 | 11.83 | 0.00870867 | 33861.3 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7697.678 | 7697.678 | 0.347912 | 0.00017007 | 175.249 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.048452 | 1.20420617 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 1.3646 | 1.289991 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8306.71 | 7697.68 | 1.0000 | 0.39959593 | 0.347912 | 21.11 | 13.92 | 0.00745045 | 40136.4 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17005343 | 60.00 | 49.00 | 11.00 | 0.000 | 8306.71 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00745045 | 21.11 | 0.00745045 | 45.6744 | 7697.68 | 0.00 | 8309.69 | 8309.69 | 0.39959593 | 16.60 | 12.60 | 0.00745045 | 35543.4 | 37.01 | 19.84 | 0.00745045 | 56338.6 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 55456.042 | -999.000 | 5.096586 | 0.00158601 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9183 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.096586 | 5.85371407 | 4197.9300 | 999.8980 | 25.00807367 | 15.03 | 6.70 | 8.33 | 874501.25 | 6.3414 | 6.341330 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 55456.04 | 53616.84 | 1.0000 | 5.85371407 | 5.096586 | 21.71 | 15.21 | 0.00864913 | 43795.8 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 1.58584437 | 6.70 | 13.38 | 8.33 | 0.000 | 55456.04 | 30.93 | 0.01534436 | 23.03 | 0.00000000 | 0.0000 | 21.11 | 0.00864913 | 21.11 | 0.00864913 | 52.9157 | 49652.34 | 0.00 | 58132.86 | 58132.86 | 5.85371407 | 21.71 | 15.68 | 0.00864913 | 43795.8 | 11.98 | 11.91 | 0.00864913 | 33864.9 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 43280.329 | 43280.329 | 1.956263 | 0.00095623 | 985.346 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.096586 | 5.85371407 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 7.6725 | 7.252996 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 46705.20 | 43280.33 | 1.0000 | 2.24687721 | 1.956263 | 21.11 | 13.94 | 0.00747971 | 40211.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.95612845 | 60.00 | 49.00 | 11.00 | 0.000 | 46705.20 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00747971 | 21.11 | 0.00747971 | 45.8482 | 43280.33 | 0.00 | 46722.29 | 46722.29 | 2.24687721 | 16.60 | 12.63 | 0.00747971 | 35617.5 | 37.01 | 19.86 | 0.00747971 | 56411.8 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 61672.966 | -999.000 | 5.288466 | 0.00176381 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4163 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.288466 | 6.07409883 | 4197.9300 | 999.8980 | 25.00807367 | 15.03 | 6.70 | 8.33 | 874501.25 | 7.0524 | 7.052227 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | 61672.97 | 56274.67 | 1.0000 | 6.07409883 | 5.288466 | 21.71 | 15.44 | 0.00891701 | 44475.6 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 1.76362614 | 6.70 | 13.38 | 8.33 | 0.000 | 61672.97 | 31.20 | 0.01534436 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00891701 | 21.11 | 0.00891701 | 54.5337 | 51517.55 | 0.00 | 64548.54 | 60265.64 | 6.07409883 | 21.71 | 15.92 | 0.00891701 | 44475.6 | 12.00 | 11.90 | 0.00863757 | 33848.8 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 43636.091 | 43636.091 | 1.972343 | 0.00096409 | 993.444 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.288466 | 6.07409883 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 7.7356 | 7.312615 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 47089.06 | 43636.09 | 1.0000 | 2.26534644 | 1.972343 | 21.11 | 13.95 | 0.00748354 | 40221.6 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.96398776 | 60.00 | 49.00 | 11.00 | 0.000 | 47089.06 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748354 | 21.11 | 0.00748354 | 45.8714 | 43636.09 | 0.00 | 47106.35 | 47106.35 | 2.26534644 | 16.60 | 12.64 | 0.00748354 | 35627.1 | 37.01 | 19.86 | 0.00748354 | 56421.5 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10555.006 | -999.000 | 0.948604 | 0.00030187 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0755 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.948604 | 1.08952411 | 4197.9300 | 999.8980 | 25.00807367 | 15.03 | 6.70 | 8.33 | 874501.25 | 1.2070 | 1.206952 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 10555.01 | 10016.51 | 1.0000 | 1.08952411 | 0.948604 | 21.71 | 15.28 | 0.00873371 | 44009.9 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.30183540 | 6.70 | 13.38 | 8.33 | 0.000 | 10555.01 | 25.37 | 0.01534436 | 21.50 | 0.00000000 | 0.0000 | 21.11 | 0.00873371 | 21.11 | 0.00873371 | 53.4284 | 9240.71 | 0.00 | 11058.21 | 10809.26 | 1.08952411 | 21.71 | 15.76 | 0.00873371 | 44009.9 | 11.99 | 11.91 | 0.00864316 | 33860.3 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7642.956 | 7642.956 | 0.345438 | 0.00016886 | 174.004 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.948604 | 1.08952411 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 1.3549 | 1.280820 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8247.67 | 7642.96 | 1.0000 | 0.39675524 | 0.345438 | 21.11 | 13.91 | 0.00744676 | 40127.0 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.16884454 | 60.00 | 49.00 | 11.00 | 0.000 | 8247.67 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00744676 | 21.11 | 0.00744676 | 45.6520 | 7642.96 | 0.00 | 8250.62 | 8250.62 | 0.39675524 | 16.60 | 12.60 | 0.00744676 | 35534.1 | 37.01 | 19.83 | 0.00744676 | 56329.3 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10502.723 | -999.000 | 0.943568 | 0.00030037 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0781 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.943568 | 1.08374109 | 4197.9300 | 999.8980 | 25.00807367 | 15.03 | 6.70 | 8.33 | 874501.25 | 1.2010 | 1.200973 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | unknown | unknown | unknown | 7/21 08:50:00 | 10502.72 | 9963.94 | 1.0000 | 1.08374109 | 0.943568 | 21.71 | 15.28 | 0.00873507 | 44013.4 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.30034031 | 6.70 | 13.38 | 8.33 | 0.000 | 10502.72 | 25.03 | 0.01534436 | 21.41 | 0.00000000 | 0.0000 | 21.11 | 0.00873507 | 21.11 | 0.00873507 | 53.4367 | 9191.65 | 0.00 | 11003.31 | 10751.85 | 1.08374109 | 21.71 | 15.76 | 0.00873507 | 44013.4 | 11.99 | 11.91 | 0.00864311 | 33860.3 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7662.891 | 7662.891 | 0.346339 | 0.00016930 | 174.458 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.943568 | 1.08374109 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 1.3584 | 1.284161 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8269.18 | 7662.89 | 1.0000 | 0.39779011 | 0.346339 | 21.11 | 13.91 | 0.00744814 | 40130.5 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.16928495 | 60.00 | 49.00 | 11.00 | 0.000 | 8269.18 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00744814 | 21.11 | 0.00744814 | 45.6603 | 7662.89 | 0.00 | 8272.14 | 8272.14 | 0.39779011 | 16.60 | 12.60 | 0.00744814 | 35537.5 | 37.01 | 19.84 | 0.00744814 | 56332.8 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14963.548 | 14963.548 | 0.712143 | 0.00033060 | 307.248 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 2.4732 | 2.507618 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15055.42 | 14963.55 | 1.0000 | 0.81793631 | 0.712143 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.33056758 | 60.00 | 49.00 | 11.00 | 0.000 | 15055.42 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00754205 | 21.00 | 0.00754205 | 46.5400 | 11380.38 | 0.00 | 15061.97 | 15061.97 | 0.81793631 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 34.66 | 19.52 | 0.00800000 | 55349.3 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3067.259 | -999.000 | 0.278322 | 0.00008772 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0077 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.278322 | 0.31966816 | 4197.9300 | 999.8980 | 25.00807367 | 15.03 | 6.70 | 8.33 | 874501.25 | 0.3507 | 0.350737 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 3067.26 | 2934.13 | 1.0000 | 0.31966816 | 0.278322 | 21.71 | 15.25 | 0.00869725 | 43917.3 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.08771263 | 6.70 | 13.38 | 8.33 | 0.000 | 3067.26 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00869725 | 21.11 | 0.00869725 | 53.2083 | 2711.25 | 0.00 | 3214.46 | 3214.46 | 0.31966816 | 21.71 | 15.73 | 0.00869725 | 43917.3 | 11.86 | 11.86 | 0.00869725 | 33861.7 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2355.668 | 2355.668 | 0.106469 | 0.00005205 | 53.629 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.278322 | 0.31966816 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 0.4176 | 0.394767 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2541.99 | 2355.67 | 1.0000 | 0.12228605 | 0.106469 | 21.11 | 14.00 | 0.00754491 | 40376.4 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05204030 | 60.00 | 49.00 | 11.00 | 0.000 | 2541.99 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00754491 | 21.11 | 0.00754491 | 46.2463 | 2355.67 | 0.00 | 2542.96 | 2542.96 | 0.12228605 | 16.60 | 12.70 | 0.00754491 | 35782.5 | 37.01 | 19.91 | 0.00754491 | 56577.7 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3016.875 | -999.000 | 0.273529 | 0.00008628 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0134 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.273529 | 0.31416343 | 4197.9300 | 999.8980 | 25.00807367 | 15.03 | 6.70 | 8.33 | 874501.25 | 0.3450 | 0.344976 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 3016.87 | 2883.99 | 1.0000 | 0.31416343 | 0.273529 | 21.71 | 15.25 | 0.00870030 | 43925.1 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.08627182 | 6.70 | 13.38 | 8.33 | 0.000 | 3016.87 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00870030 | 21.11 | 0.00870030 | 53.2268 | 2664.56 | 0.00 | 3161.57 | 3161.57 | 0.31416343 | 21.71 | 15.73 | 0.00870030 | 43925.1 | 11.85 | 11.85 | 0.00870030 | 33861.6 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2367.276 | 2367.276 | 0.106994 | 0.00005230 | 53.893 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.273529 | 0.31416343 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 0.4196 | 0.396712 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2554.51 | 2367.28 | 1.0000 | 0.12288862 | 0.106994 | 21.11 | 14.00 | 0.00754705 | 40381.8 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05229674 | 60.00 | 49.00 | 11.00 | 0.000 | 2554.51 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00754705 | 21.11 | 0.00754705 | 46.2593 | 2367.28 | 0.00 | 2555.49 | 2555.49 | 0.12288862 | 16.60 | 12.70 | 0.00754705 | 35788.0 | 37.01 | 19.91 | 0.00754705 | 56583.1 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11954.994 | -999.000 | 1.050988 | 0.00034190 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2337 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.050988 | 1.20711874 | 4197.9300 | 999.8980 | 25.00807367 | 15.03 | 6.70 | 8.33 | 874501.25 | 1.3671 | 1.367039 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 11954.99 | 11138.20 | 1.0000 | 1.20711874 | 1.050988 | 21.71 | 15.36 | 0.00881879 | 44225.9 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.34187005 | 6.70 | 13.38 | 8.33 | 0.000 | 11954.99 | 30.93 | 0.01534436 | 23.03 | 0.00000000 | 0.0000 | 21.11 | 0.00881879 | 21.11 | 0.00881879 | 53.9419 | 10237.96 | 0.00 | 12518.18 | 11975.08 | 1.20711874 | 21.71 | 15.83 | 0.00881879 | 44225.9 | 12.00 | 11.91 | 0.00864048 | 33855.6 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11254.554 | 11254.554 | 0.508685 | 0.00024866 | 256.218 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.050988 | 1.20711874 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 1.9951 | 1.886059 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12144.74 | 11254.55 | 1.0000 | 0.58425296 | 0.508685 | 21.11 | 14.02 | 0.00756048 | 40416.4 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.24863026 | 60.00 | 49.00 | 11.00 | 0.000 | 12144.74 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00756048 | 21.11 | 0.00756048 | 46.3394 | 11254.55 | 0.00 | 12149.46 | 12149.46 | 0.58425296 | 16.60 | 12.71 | 0.00756048 | 35822.0 | 37.01 | 19.92 | 0.00756048 | 56616.8 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16707.317 | 16707.317 | 1.781105 | 0.00036913 | 310.745 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 2.7597 | 2.799842 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16799.41 | 16707.32 | 1.0000 | 2.04569902 | 1.781105 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.36909009 | 60.00 | 49.00 | 11.00 | 0.000 | 16799.41 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00765483 | 21.00 | 0.00765483 | 47.2287 | 7744.71 | 0.00 | 16804.75 | 16804.75 | 2.04569902 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.66 | 16.17 | 0.00800000 | 45149.4 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16847.190 | 16847.190 | 1.780381 | 0.00037222 | 313.652 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 2.7828 | 2.823282 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 16939.99 | 16847.19 | 1.0000 | 2.04486680 | 1.780381 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.37218011 | 60.00 | 49.00 | 11.00 | 0.000 | 16939.99 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766082 | 21.00 | 0.00766082 | 47.2653 | 7888.13 | 0.00 | 16945.42 | 16945.42 | 2.04486680 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.73 | 16.20 | 0.00800000 | 45221.5 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6361.895 | 6361.895 | 0.550158 | 0.00014056 | 121.460 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 1.0506 | 1.066138 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 6395.54 | 6361.90 | 1.0000 | 0.63188740 | 0.550158 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.14054397 | 60.00 | 49.00 | 11.00 | 0.000 | 6395.54 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.72 | 0.00706969 | 21.00 | 0.00706969 | 43.6656 | 3597.97 | 0.00 | 6398.07 | 6398.07 | 0.63188740 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.53 | 16.83 | 0.00800000 | 47060.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10013.733 | 10013.733 | 0.366989 | 0.00022124 | 217.052 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 1.6545 | 1.678119 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 10071.46 | 10013.73 | 1.0000 | 0.42150716 | 0.366989 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.22121863 | 60.00 | 49.00 | 11.00 | 0.000 | 10071.46 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00771096 | 21.00 | 0.00771096 | 47.5701 | 8166.73 | 0.00 | 10077.71 | 10077.71 | 0.42150716 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.05 | 21.16 | 0.00800000 | 60843.5 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 607211.525 | -999.000 | 19.645634 | 0.01736617 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.9592 | 1004.8586 | 1.1486 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 19.645634 | 22.56410753 | 4197.9300 | 999.8980 | 25.00807367 | 15.03 | 6.70 | 8.33 | 874501.25 | 69.4352 | 69.435181 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 607211.53 | 384610.70 | 1.0000 | 22.56410753 | 19.645634 | 27.41 | 20.07 | 0.01243669 | 59281.9 | 10.90 | 10.89 | 0.00868318 | 32385.3 | 17.36440123 | 6.70 | 13.38 | 8.33 | 44018.766 | 563192.76 | 31.20 | 0.01534436 | 23.10 | 9.32560000 | 47.4691 | 23.99 | 0.00980808 | 23.99 | 0.00962255 | 49.3433 | 257651.65 | 0.00 | 657971.03 | 395123.95 | 22.56410753 | 27.41 | 20.61 | 0.01243669 | 59281.9 | 10.38 | 10.36 | 0.00781453 | 30121.8 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 291810.999 | 291810.999 | 5.893690 | 0.00644721 | 3715.545 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 19.645634 | 22.56410753 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 29.1615 | 48.902213 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 177515.64 | 291811.00 | 1.0000 | 6.76923226 | 5.893690 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 6.44654976 | 60.00 | 49.00 | 11.00 | 0.000 | 177515.64 | -26.20 | 0.00036134 | -26.20 | 9.32560000 | 158.2302 | 20.98 | 0.00747424 | 21.00 | 0.00748975 | 46.2231 | 84847.89 | 0.00 | 177106.04 | 177106.04 | 6.76923226 | 16.60 | 4.51 | 0.00036134 | 17595.2 | 42.62 | 15.83 | 0.00036134 | 43758.6 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87700.731 | -999.000 | 2.051199 | 0.00250823 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.3644 | 1004.8586 | 1.1486 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.35591662 | 4197.9300 | 999.8980 | 25.00807367 | 15.03 | 6.70 | 8.33 | 874501.25 | 10.0287 | 10.028657 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 87700.73 | 47797.05 | 1.0000 | 2.35591662 | 2.051199 | 31.20 | 23.10 | 0.01534436 | 70616.3 | 10.91 | 11.67 | 0.00868318 | 34322.2 | 2.50797395 | 6.70 | 13.38 | 8.33 | 2194.880 | 85505.85 | 31.20 | 0.01534436 | 23.10 | 2.05119905 | 100.0000 | 21.11 | 0.00879428 | 21.11 | 0.00878459 | 53.7340 | 143339.11 | 0.00 | 93096.22 | 49675.25 | 2.35591662 | 31.20 | 23.68 | 0.01534436 | 70616.3 | 10.80 | 10.78 | 0.00803355 | 31100.4 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 30467.962 | 30467.962 | 0.615360 | 0.00067315 | 387.940 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.35591662 | 4197.9300 | 999.8980 | 13.18253179 | 71.00 | 82.00 | 11.00 | 608732.80 | 3.0448 | 5.105876 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 18534.39 | 30467.96 | 1.0000 | 0.70677499 | 0.615360 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 0.67308373 | 60.00 | 49.00 | 11.00 | 0.000 | 18534.39 | -26.20 | 0.00036134 | -26.20 | 2.05119905 | 333.3333 | 21.11 | 0.00748297 | 21.11 | 0.00748225 | 45.8637 | 133575.10 | 0.00 | 18491.63 | 18491.63 | 0.70677499 | 16.60 | 4.51 | 0.00036134 | 17595.2 | 42.62 | 15.83 | 0.00036134 | 43758.6 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 19.65 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.001447 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.003555 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000609 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4771.33 | 1819.67 | 111.17 |
RETAIL_1_FLR_1 | 4609.17 | 4910.33 | 1755.83 |
RETAIL_2_FLR_1 | 4298.67 | 3386.00 | 363.83 |
LAUNDRY_FLR_1 | 8723.67 | 6819.83 | 6819.83 |
CAFE_FLR_1 | 4986.00 | 4740.00 | 1911.50 |
LOBBY_FLR_1 | 5324.17 | 3271.83 | 1333.33 |
ROOM_1_FLR_3 | 3109.67 | 8356.50 | 3068.67 |
ROOM_2_FLR_3 | 4062.83 | 8159.83 | 3783.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2194.50 | 8670.67 | 2174.50 |
ROOM_5_FLR_3 | 3059.33 | 8376.17 | 3036.67 |
ROOM_6_FLR_3 | 3815.83 | 8226.00 | 3648.50 |
ROOM_1_FLR_6 | 3612.50 | 8225.00 | 3498.67 |
ROOM_2_FLR_6 | 4569.33 | 8069.17 | 4261.00 |
ROOM_3_MULT9_FLR_6 | 2255.33 | 8272.33 | 2225.50 |
BANQUET_FLR_6 | 7081.33 | 3405.67 | 2432.50 |
DINING_FLR_6 | 7869.50 | 4023.33 | 3660.17 |
KITCHEN_FLR_6 | 8721.83 | 8366.83 | 8335.50 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 8760.00 | 8760.00 | 8760.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 64.00 | 3383.83 | 64.00 | 3383.83 |
RETAIL_1_FLR_1 | 568.33 | 720.00 | 568.33 | 720.00 |
RETAIL_2_FLR_1 | 175.17 | 2023.17 | 175.17 | 2023.17 |
LAUNDRY_FLR_1 | 0.00 | 6914.00 | 0.00 | 6914.00 |
CAFE_FLR_1 | 176.33 | 2336.33 | 176.33 | 2336.33 |
LOBBY_FLR_1 | 135.67 | 3330.17 | 135.67 | 3330.17 |
ROOM_1_FLR_3 | 58.50 | 0.83 | 58.50 | 0.83 |
ROOM_2_FLR_3 | 83.67 | 6.17 | 83.67 | 6.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 123.83 | 24.33 | 123.83 | 24.33 |
ROOM_5_FLR_3 | 73.83 | 0.00 | 73.83 | 0.00 |
ROOM_6_FLR_3 | 98.17 | 16.33 | 98.17 | 16.33 |
ROOM_1_FLR_6 | 51.33 | 2.83 | 51.33 | 2.83 |
ROOM_2_FLR_6 | 83.00 | 15.17 | 83.00 | 15.17 |
ROOM_3_MULT9_FLR_6 | 39.50 | 8.00 | 39.50 | 8.00 |
BANQUET_FLR_6 | 157.00 | 6602.67 | 157.00 | 6602.67 |
DINING_FLR_6 | 136.00 | 7675.50 | 136.00 | 7675.50 |
KITCHEN_FLR_6 | 0.00 | 8462.17 | 0.00 | 8462.17 |
MECH_FLR_1 | 206.00 | 434.17 | 0.00 | 0.00 |
STORAGE_FLR_1 | 355.50 | 29.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 1757.67 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 623.50 | 769.17 | 0.00 | 0.00 |
Facility | 1760.00 | 8599.00 | 586.50 | 8599.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.75 | 106.50 | 4826.41 | 0.798 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.184 | 0.277 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.089 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 18.595 | 0.155 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.51 | 142.30 | 748.35 | 2.843 | 0.249 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.374 | 0.072 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.340 | 0.181 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.341 | 0.181 | 0.000 | 0.053 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.387 | 0.080 | 0.000 | 0.101 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.340 | 0.181 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.341 | 0.181 | 0.000 | 0.063 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.340 | 0.181 | 0.000 | 0.082 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.341 | 0.181 | 0.000 | 0.055 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.387 | 0.148 | 0.000 | 0.131 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 3.775 | 0.053 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.011 | 0.053 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 13.480 | 0.154 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.75 | 106.50 | 4826.41 | 0.000 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.000 | 0.004 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.000 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 0.000 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.51 | 142.30 | 748.35 | 0.000 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 0.000 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 0.000 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 0.000 | 0.002 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 4892.46 | 68721.92 | 07-FEB-04:00 | 399615.74 | 26-JUL-19:40 |
Electricity:Building | 2181.49 | 28395.58 | 03-JUN-05:00 | 133760.38 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 277.26 | 3246.85 | 02-JAN-02:10 | 20603.11 | 02-JAN-20:10 |
InteriorLights:Electricity | 525.93 | 4360.76 | 03-JUN-05:00 | 47387.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 134.15 | 1218.95 | 02-JAN-02:10 | 10970.58 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 525.93 | 4360.76 | 03-JUN-05:00 | 47387.53 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.86 | 204.98 | 02-JAN-02:10 | 1231.40 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.67 | 60.64 | 02-JAN-02:10 | 545.79 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.52 | 237.37 | 02-JAN-02:10 | 1425.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.73 | 70.23 | 02-JAN-02:10 | 632.03 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.96 | 344.68 | 02-JAN-02:10 | 2351.00 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.48 | 167.95 | 02-JAN-02:10 | 1511.55 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.50 | 68.23 | 02-JAN-02:10 | 397.38 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.90 | 17.25 | 02-JAN-02:10 | 155.22 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 23.23 | 250.10 | 17-JUN-05:00 | 2063.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 8.88 | 46.89 | 17-JUN-05:00 | 1097.76 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 223.46 | 2762.69 | 03-JUN-05:00 | 16492.48 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 74.46 | 651.28 | 03-JUN-05:00 | 6463.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.99 | 160.87 | 02-JAN-10:10 | 1278.06 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.08 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.99 | 160.85 | 02-JAN-10:10 | 1277.91 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.01 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 260.83 | 2764.15 | 02-JAN-10:10 | 21347.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 65.84 | 411.27 | 01-JAN-11:10 | 6580.30 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 260.91 | 2764.90 | 02-JAN-10:10 | 21353.83 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 65.86 | 411.38 | 01-JAN-11:10 | 6582.10 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.99 | 160.87 | 02-JAN-10:10 | 1278.06 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.08 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.99 | 160.85 | 02-JAN-10:10 | 1277.91 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.01 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 41.03 | 372.78 | 02-JAN-02:10 | 3355.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 41.03 | 372.78 | 02-JAN-02:10 | 3355.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.00 | 40.22 | 02-JAN-10:10 | 319.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.38 | 8.61 | 01-JAN-11:10 | 137.77 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.00 | 40.21 | 02-JAN-10:10 | 319.48 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.38 | 8.61 | 01-JAN-11:10 | 137.75 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.90 | 327.42 | 02-JAN-10:10 | 2528.74 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.80 | 48.72 | 01-JAN-11:10 | 779.46 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 195.47 | 2377.82 | 03-JUN-05:00 | 8675.67 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 19.61 | 128.52 | 03-JUN-05:00 | 1927.76 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 195.47 | 2377.82 | 03-JUN-05:00 | 8675.67 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 19.61 | 128.52 | 03-JUN-05:00 | 1927.76 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 10.86 | 98.63 | 02-JAN-02:10 | 887.69 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 10.86 | 98.63 | 02-JAN-02:10 | 887.69 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.47 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 872.73 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 48.50 | 747.77 | 29-JAN-23:30 | 2828.32 | 01-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 785.67 | 2235.51 | 24-MAR-03:00 | 183206.09 | 04-AUG-15:20 |
LowTempRefrigeration:Refrigeration:Electricity | 18.38 | 0.00 | 01-JAN-11:10 | 1556.35 | 11-JUN-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 23.03 | 599.03 | 02-FEB-04:10 | 734.88 | 01-JAN-08:20 |
WaterSystems:Electricity | 90.56 | 1086.49 | 27-JUL-03:00 | 4739.42 | 02-FEB-07:10 |
Water Heater:WaterSystems:Electricity | 90.56 | 1086.49 | 27-JUL-03:00 | 4739.42 | 02-FEB-07:10 |
Fans:Electricity | 664.24 | 7329.18 | 19-JAN-11:00 | 33249.69 | 31-MAY-18:20 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 792.24 | 10695.17 | 09-JUL-01:10 | 37813.88 | 31-MAY-18:20 |
ExteriorEquipment:Electricity | 971.97 | 6508.89 | 02-JAN-02:20 | 62573.78 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.51 | 378.95 | 17-JUN-05:00 | 1274.84 | 02-JAN-07:20 |
ElectricityPurchased:Facility | 4892.46 | 68721.92 | 07-FEB-04:00 | 399615.74 | 26-JUL-19:40 |
ElectricityPurchased:Plant | 4892.46 | 68721.92 | 07-FEB-04:00 | 399615.74 | 26-JUL-19:40 |
Cogeneration:ElectricityPurchased | 4892.46 | 68721.92 | 07-FEB-04:00 | 399615.74 | 26-JUL-19:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 4892.46 | 68721.92 | 07-FEB-04:00 | 399615.74 | 26-JUL-19:40 |
ElectricityNet:Plant | 4892.46 | 68721.92 | 07-FEB-04:00 | 399615.74 | 26-JUL-19:40 |
Cogeneration:ElectricityNet | 4892.46 | 68721.92 | 07-FEB-04:00 | 399615.74 | 26-JUL-19:40 |
General:Fans:Electricity | 664.24 | 7329.18 | 19-JAN-11:00 | 33249.69 | 31-MAY-18:20 |
ExteriorLights:Electricity | 182.61 | 0.00 | 01-JAN-08:00 | 11632.50 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 182.61 | 0.00 | 01-JAN-08:00 | 11632.50 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.79 | 01-JAN-00:10 | 187.95 | 01-JAN-07:10 |
HeatRecovery:Electricity | 106.48 | 0.00 | 19-MAR-11:10 | 6004.29 | 01-JAN-00:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 616.78 | 0.00 | 01-JAN-00:10 | 176926.02 | 04-AUG-15:20 |
General:Cooling:Electricity | 616.78 | 0.00 | 01-JAN-00:10 | 176926.02 | 04-AUG-15:20 |
Pumps:Electricity | 36.92 | 47.91 | 20-MAR-10:00 | 3520.29 | 26-JUL-19:20 |
General:Pumps:Electricity | 36.92 | 47.91 | 20-MAR-10:00 | 3520.29 | 26-JUL-19:20 |
WIRED_LTG_ELECTRICITY | 18.51 | 0.00 | 01-JAN-00:10 | 1668.04 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 5177.32 | 29270.80 | 17-APR-01:10 | 684105.20 | 02-FEB-21:00 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 3388.47 | 15908.90 | 14-APR-13:10 | 597148.87 | 02-FEB-23:00 |
WaterSystems:Gas | 2275.68 | 15908.90 | 14-APR-13:10 | 180940.81 | 02-FEB-21:40 |
Water Heater:WaterSystems:Gas | 2275.68 | 15908.90 | 14-APR-13:10 | 180940.81 | 02-FEB-21:40 |
Heating:Gas | 1112.79 | 0.00 | 24-FEB-11:30 | 444491.53 | 02-FEB-06:00 |
Boiler:Heating:Gas | 1112.79 | 0.00 | 24-FEB-11:30 | 444491.53 | 02-FEB-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2029.20 | 0.00 | 01-JAN-00:10 | 591215.22 | 26-JUL-19:20 |
PlantLoopCoolingDemand:HVAC | 2029.20 | 0.00 | 01-JAN-00:10 | 591215.22 | 26-JUL-19:20 |
CoolingCoils:PlantLoopCoolingDemand | 2029.20 | 0.00 | 01-JAN-00:10 | 591215.22 | 26-JUL-19:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 05-MAY-00:40 | 0.00 | 10-APR-20:20 |
Water:Plant | 22864.31 | 0.00 | 05-MAY-00:40 | 0.00 | 10-APR-20:20 |
WaterSystems:Water | 22864.31 | 0.00 | 05-MAY-00:40 | 0.00 | 10-APR-20:20 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 12-MAY-00:10 | 0.00 | 18-APR-18:20 |
MainsWater:Facility | 22864.31 | 0.00 | 05-MAY-00:40 | 0.00 | 10-APR-20:20 |
MainsWater:Plant | 22864.31 | 0.00 | 05-MAY-00:40 | 0.00 | 10-APR-20:20 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 05-MAY-00:40 | 0.00 | 10-APR-20:20 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 12-MAY-00:10 | 0.00 | 18-APR-18:20 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 05-MAY-00:40 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 05-MAY-00:40 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 17839.69 | 118686.30 | 06-JUN-11:30 | 2246312.66 | 26-JUL-19:20 |
EnergyTransfer:Building | 4095.81 | 61109.63 | 06-JAN-11:00 | 286421.11 | 31-MAY-18:20 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 640.46 | 7860.39 | 01-JAN-00:10 | 33329.55 | 12-MAY-10:40 |
Refrigeration:EnergyTransfer | 212.36 | 3963.28 | 02-FEB-04:00 | 10745.76 | 01-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 106.18 | 1981.64 | 02-FEB-04:00 | 5372.88 | 01-JAN-11:40 |
EnergyTransfer:Plant | 6532.90 | 18466.28 | 10-APR-00:40 | 1392337.10 | 26-JUL-19:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 22.49 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 83.69 | 1738.23 | 02-FEB-04:10 | 2686.44 | 01-JAN-08:20 |
PlantLoopHeatingDemand:Facility | 1702.71 | 9841.70 | 01-SEP-00:10 | 416860.33 | 02-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 847.92 | 9841.70 | 01-SEP-00:10 | 63639.17 | 21-FEB-07:40 |
WaterSystems:PlantLoopHeatingDemand | 847.92 | 9841.70 | 01-SEP-00:10 | 63639.17 | 21-FEB-07:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 326.68 | 1.82 | 04-FEB-14:30 | 36711.91 | 25-NOV-21:40 |
Heating:EnergyTransfer | 369.17 | 0.00 | 20-FEB-14:00 | 113477.13 | 12-DEC-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 509.70 | 04-FEB-11:30 |
Cooling:EnergyTransfer | 3620.46 | 23952.29 | 04-FEB-11:30 | 282284.49 | 31-MAY-18:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 326.68 | 0.00 | 04-FEB-11:30 | 36711.91 | 25-NOV-21:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 25.59 | 0.27 | 08-MAR-12:30 | 3216.92 | 20-OCT-14:30 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 4.80 | 0.00 | 02-JAN-09:40 | 1513.43 | 20-JAN-08:10 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 20.79 | 0.00 | 01-JAN-00:10 | 3216.92 | 20-OCT-14:30 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 26.64 | 1.67 | 12-DEC-14:50 | 2176.19 | 08-SEP-23:50 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 627.59 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 26.59 | 0.00 | 06-JAN-10:50 | 2176.19 | 08-SEP-23:50 |
EnergyTransfer:Zone:MECH_FLR_1 | 17.49 | 0.15 | 13-DEC-14:20 | 1923.71 | 15-APR-20:40 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.34 | 0.00 | 01-JAN-00:10 | 966.13 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 17.15 | 0.00 | 06-JAN-10:40 | 1923.71 | 15-APR-20:40 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 10.21 | 0.39 | 19-FEB-05:30 | 841.51 | 08-SEP-23:50 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.99 | 0.00 | 01-JAN-20:10 | 764.57 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.22 | 0.00 | 01-JAN-00:10 | 841.51 | 08-SEP-23:50 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 559.45 | 5991.28 | 04-FEB-06:00 | 40099.50 | 11-JUL-19:50 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 559.45 | 5991.28 | 04-FEB-06:00 | 40099.50 | 11-JUL-19:50 |
EnergyTransfer:Zone:CAFE_FLR_1 | 159.63 | 1.34 | 23-DEC-14:30 | 13263.72 | 20-OCT-14:30 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.74 | 0.00 | 01-JAN-00:10 | 3657.46 | 20-JAN-08:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 158.89 | 0.00 | 01-JAN-14:50 | 13263.72 | 20-OCT-14:30 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 586.07 | 188.85 | 05-FEB-16:00 | 44193.25 | 09-SEP-24:00 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.16 | 0.00 | 01-JAN-00:10 | 9178.76 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 585.91 | 0.00 | 31-JAN-11:40 | 44193.25 | 09-SEP-24:00 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 62.69 | 0.00 | 01-JAN-08:00 | 11223.32 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 32.47 | 0.00 | 01-JAN-08:00 | 7927.37 | 11-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 30.22 | 0.00 | 01-JAN-00:10 | 11223.32 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 59.62 | 0.00 | 01-JAN-08:00 | 10727.49 | 30-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 38.00 | 0.00 | 01-JAN-08:00 | 8004.64 | 04-FEB-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 21.62 | 0.00 | 01-JAN-00:10 | 10727.49 | 30-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 175.68 | 0.00 | 01-JAN-08:10 | 46462.71 | 20-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 19.98 | 0.00 | 01-JAN-08:10 | 26066.36 | 19-JAN-05:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 155.70 | 0.00 | 01-JAN-00:10 | 46462.71 | 20-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 340.01 | 0.00 | 01-JAN-08:00 | 64121.48 | 18-JUN-20:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 99.80 | 0.00 | 01-JAN-08:00 | 43091.53 | 03-FEB-11:00 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 240.21 | 0.00 | 01-JAN-00:10 | 64121.48 | 18-JUN-20:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 61.65 | 0.00 | 01-JAN-08:00 | 9921.46 | 02-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 32.47 | 0.00 | 01-JAN-08:00 | 7621.00 | 04-FEB-19:10 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 29.18 | 0.00 | 01-JAN-00:10 | 9921.46 | 02-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 60.03 | 0.00 | 01-JAN-08:00 | 10735.66 | 01-JUL-08:20 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 38.08 | 0.00 | 01-JAN-08:00 | 8272.31 | 03-FEB-08:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 21.95 | 0.00 | 01-JAN-00:10 | 10735.66 | 01-JUL-08:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 81.83 | 0.94 | 12-OCT-04:50 | 5917.69 | 09-SEP-24:00 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 37.31 | 0.00 | 05-JAN-07:50 | 5557.10 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 44.52 | 0.00 | 01-JAN-00:10 | 5917.69 | 09-SEP-24:00 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.02 | 0.00 | 01-JAN-08:00 | 3058.39 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.80 | 0.00 | 01-JAN-08:00 | 2303.37 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 8.21 | 0.00 | 01-JAN-00:10 | 3058.39 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.61 | 0.00 | 01-JAN-08:00 | 3006.16 | 25-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.51 | 0.00 | 01-JAN-08:00 | 2318.70 | 02-FEB-08:00 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.10 | 0.00 | 01-JAN-00:10 | 3006.16 | 25-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 79.52 | 0.00 | 01-JAN-08:00 | 12849.12 | 08-SEP-15:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 31.25 | 0.00 | 01-JAN-08:00 | 9863.77 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 48.27 | 0.00 | 01-JAN-00:10 | 12849.12 | 08-SEP-15:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 348.00 | 129.60 | 31-JAN-12:50 | 21624.43 | 09-SEP-24:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 3578.04 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 347.96 | 0.00 | 31-JAN-11:40 | 21624.43 | 09-SEP-24:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 388.21 | 109.32 | 04-FEB-12:20 | 24511.88 | 05-JAN-22:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.01 | 0.00 | 01-JAN-00:10 | 2241.20 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 388.21 | 0.00 | 31-JAN-11:50 | 24511.88 | 05-JAN-22:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 534.28 | 5550.23 | 01-JAN-00:10 | 29840.05 | 12-JUN-17:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 48.74 | 2.26 | 20-FEB-04:30 | 4919.31 | 03-JUL-07:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 9.37 | 0.00 | 02-JAN-10:20 | 3185.43 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 39.37 | 0.00 | 01-JAN-00:10 | 4919.31 | 03-JUL-07:30 |
WaterSystems:EnergyTransfer | 847.92 | 9841.70 | 01-SEP-00:10 | 63639.17 | 21-FEB-07:40 |
WaterUse:WaterSystems:EnergyTransfer | 847.92 | 9841.70 | 01-SEP-00:10 | 63639.17 | 21-FEB-07:40 |
EnergyTransfer:HVAC | 7210.97 | 446.80 | 29-APR-12:20 | 723195.02 | 04-AUG-16:00 |
HeatingCoils:EnergyTransfer | 854.79 | 0.00 | 24-FEB-11:30 | 362727.20 | 02-FEB-05:50 |
PlantLoopHeatingDemand:HVAC | 854.79 | 0.00 | 24-FEB-11:30 | 362727.20 | 02-FEB-05:50 |
HeatingCoils:PlantLoopHeatingDemand | 854.79 | 0.00 | 24-FEB-11:30 | 362727.20 | 02-FEB-05:50 |
CoolingCoils:EnergyTransfer | 2029.20 | 0.00 | 01-JAN-00:10 | 591215.22 | 26-JUL-19:20 |
HeatRecoveryForHeating:EnergyTransfer | 4231.63 | 0.00 | 05-JAN-08:00 | 469093.15 | 05-JAN-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 95.34 | 0.00 | 01-JAN-00:10 | 224531.12 | 04-AUG-13:00 |
Boilers:EnergyTransfer | 850.71 | 0.00 | 24-FEB-11:30 | 360537.57 | 02-FEB-06:00 |
Chillers:EnergyTransfer | 2055.65 | 0.00 | 01-JAN-00:10 | 595594.78 | 26-JUL-19:20 |
HeatRejection:EnergyTransfer | 2672.44 | 0.00 | 01-JAN-00:10 | 763148.06 | 26-JUL-19:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.001 | -326.679 | 0.000 | 0.000 | 127.991 | 134.155 | 143.109 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -78.577 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 4.799 | -20.790 | 0.000 | 0.000 | 14.770 | 6.674 | 10.186 | 18.497 | 0.000 | 0.106 | 0.000 | 0.000 | -14.487 | 0.000 | -12.598 | -7.158 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.047 | -26.592 | 0.000 | 0.000 | 15.711 | 7.729 | 11.795 | 0.000 | 0.000 | 0.028 | 0.000 | 0.000 | 0.000 | 0.000 | -2.834 | -5.884 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -559.441 | 0.000 | 0.000 | 8.699 | 4.900 | 658.148 | 0.000 | 0.000 | 0.066 | 0.000 | 0.000 | 0.000 | 0.000 | -9.913 | -102.458 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.741 | -158.881 | 0.000 | 0.000 | 181.364 | 8.885 | 14.341 | 51.491 | 0.000 | 0.289 | 0.000 | 0.000 | -42.940 | 0.000 | -33.475 | -21.816 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.163 | -585.890 | 0.000 | 0.000 | 514.305 | 74.459 | 149.002 | 67.781 | 0.000 | 0.653 | 0.000 | 0.000 | -59.113 | 0.000 | -69.316 | -92.045 |
ROOM_1_FLR_3 | 32.467 | -19.412 | 0.000 | -10.807 | 0.000 | 0.000 | 9.766 | 5.514 | 10.478 | 36.925 | 0.000 | 0.600 | 0.000 | 0.000 | -32.568 | 0.000 | -14.449 | -18.513 |
ROOM_2_FLR_3 | 38.001 | -10.361 | 0.000 | -11.254 | 0.000 | 0.000 | 9.640 | 5.513 | 10.477 | 26.526 | 0.000 | 0.284 | 0.000 | 0.000 | -34.802 | 0.000 | -14.793 | -19.232 |
ROOM_3_MULT19_FLR_3 | 19.984 | -143.856 | 0.000 | -11.840 | 0.000 | 0.000 | 0.000 | 65.838 | 194.997 | 215.219 | 0.000 | 0.286 | 0.000 | 0.000 | -191.298 | 0.000 | -82.170 | -67.159 |
ROOM_4_MULT19_FLR_3 | 99.802 | -90.260 | 0.000 | -149.946 | 0.000 | 0.000 | 183.952 | 65.856 | 195.050 | 62.867 | 0.000 | 3.047 | 0.000 | 0.000 | -198.119 | 0.000 | -89.813 | -82.436 |
ROOM_5_FLR_3 | 32.465 | -18.374 | 0.000 | -10.807 | 0.000 | 0.000 | 9.763 | 5.514 | 10.478 | 35.668 | 0.000 | 0.601 | 0.000 | 0.000 | -31.979 | 0.000 | -14.476 | -18.853 |
ROOM_6_FLR_3 | 38.080 | -10.825 | 0.000 | -11.127 | 0.000 | 0.000 | 9.684 | 5.513 | 10.477 | 25.217 | 0.000 | 0.314 | 0.000 | 0.000 | -33.983 | 0.000 | -14.767 | -18.584 |
ROOM_1_FLR_6 | 10.805 | -5.509 | 0.000 | -2.701 | 0.000 | 0.000 | 2.443 | 1.378 | 2.620 | 9.183 | 0.000 | 0.162 | 0.000 | 0.000 | -8.169 | 0.000 | -3.653 | -6.558 |
ROOM_2_FLR_6 | 12.507 | -3.267 | 0.000 | -2.837 | 0.000 | 0.000 | 2.403 | 1.378 | 2.619 | 6.572 | 0.000 | 0.070 | 0.000 | 0.000 | -8.754 | 0.000 | -3.725 | -6.966 |
ROOM_3_MULT9_FLR_6 | 31.253 | -30.742 | 0.000 | -17.525 | 0.000 | 0.000 | 21.876 | 7.799 | 23.098 | 49.275 | 0.000 | 1.124 | 0.000 | 0.000 | -37.958 | 0.000 | -17.922 | -30.277 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.038 | -347.933 | 0.000 | 0.000 | 280.560 | 19.612 | 175.857 | 5.805 | 0.000 | 0.059 | 0.000 | 0.000 | -27.156 | 0.000 | -10.423 | -96.419 |
DINING_FLR_6 | 0.000 | 0.000 | 0.006 | -388.171 | 0.000 | 0.000 | 269.889 | 19.612 | 175.857 | 5.482 | 0.000 | 0.049 | 0.000 | 0.000 | -28.486 | 0.000 | -10.683 | -43.555 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -534.020 | 0.000 | 0.000 | 18.564 | 13.339 | 540.650 | 14.388 | 0.000 | 0.001 | 0.001 | 0.000 | -20.589 | 0.000 | -11.196 | -21.137 |
MECH_FLR_1 | 0.000 | 0.000 | 0.341 | -17.148 | 0.000 | 0.000 | 0.000 | 18.484 | 12.472 | 0.000 | 0.000 | 0.065 | 0.000 | 0.000 | 0.000 | 0.000 | -6.131 | -8.083 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.988 | -9.221 | 0.000 | 0.000 | 0.000 | 1.898 | 3.598 | 0.000 | 0.000 | 0.049 | 6.690 | 0.000 | 0.000 | 0.000 | -4.002 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 37.313 | -44.518 | 0.000 | 0.000 | 0.000 | 41.027 | 0.000 | 32.353 | 0.000 | 0.348 | 0.000 | 0.000 | -39.134 | 0.000 | -16.432 | -10.957 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 9.369 | -39.367 | 0.000 | 0.000 | 0.000 | 10.855 | 0.000 | 14.947 | 0.000 | 0.062 | 31.303 | 0.000 | -19.189 | 0.000 | -7.980 | -0.000 |
Total Facility | 315.364 | -332.607 | 53.806 | -3287.497 | 0.000 | 0.000 | 1681.380 | 525.934 | 2355.308 | 678.198 | 0.000 | 8.264 | 37.993 | 0.000 | -828.725 | 0.000 | -450.748 | -756.669 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-NOV-21:32 | 0.00 | 0.00 | 0.00 | -75008.00 | 0.00 | 0.00 | 5115.15 | 8532.68 | 8111.60 | 0.00 | 0.00 | 0.00 | 53248.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 20-OCT-13:24 | 0.00 | 0.00 | 0.00 | -5161.24 | 0.00 | 0.00 | 108.67 | 151.61 | 252.59 | 5834.73 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -111.74 | -1074.61 |
RETAIL_2_FLR_1 | 25-NOV-21:32 | 0.00 | 0.00 | 0.00 | -4111.25 | 0.00 | 0.00 | 704.82 | 491.58 | 668.57 | 0.00 | 0.00 | 0.00 | 2499.18 | 0.00 | -0.00 | 0.00 | -252.90 | 0.00 |
LAUNDRY_FLR_1 | 05-JAN-21:34 | 0.00 | 0.00 | 0.00 | -82705.58 | 0.00 | 0.00 | 362.54 | 356.16 | 41967.83 | 0.00 | 0.00 | 0.00 | 40856.70 | 0.00 | -0.00 | 0.00 | -837.65 | 0.00 |
CAFE_FLR_1 | 20-OCT-12:23 | 0.00 | 0.00 | 0.00 | -21321.29 | 0.00 | 0.00 | 1534.35 | 67.09 | 355.63 | 18371.60 | 0.00 | 0.00 | 1279.96 | 0.00 | -0.00 | 0.00 | -287.34 | 0.00 |
LOBBY_FLR_1 | 25-NOV-21:32 | 0.00 | 0.00 | 0.00 | -84579.30 | 0.00 | 0.00 | 23862.10 | 5026.99 | 8445.65 | 0.00 | 0.00 | 0.00 | 60003.38 | 0.00 | -6710.56 | 0.00 | -6048.25 | 0.00 |
ROOM_1_FLR_3 | 29-APR-18:01 | 0.00 | -14630.39 | 0.00 | -547.26 | 0.00 | 0.00 | 272.46 | 551.08 | 484.65 | 3710.87 | 0.00 | 0.00 | 10374.69 | 0.00 | -0.00 | 0.00 | -216.10 | 0.00 |
ROOM_2_FLR_3 | 20-MAY-18:01 | 0.00 | -15831.36 | 0.00 | -663.76 | 0.00 | 0.00 | 240.13 | 551.01 | 484.60 | 4771.03 | 0.00 | 0.00 | 10704.74 | 0.00 | -0.00 | 0.00 | -256.38 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-OCT-12:38 | 0.00 | -46470.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.27 | 2352.88 | 77217.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -711.19 | -32799.67 |
ROOM_4_MULT19_FLR_3 | 06-MAY-18:51 | 0.00 | -70590.77 | 0.00 | -6656.52 | 0.00 | 0.00 | 5617.39 | 6582.10 | 9021.83 | 0.00 | 0.00 | 0.00 | 58234.42 | 0.00 | -1170.18 | 0.00 | -1038.28 | 0.00 |
ROOM_5_FLR_3 | 04-NOV-15:11 | 0.00 | -12596.25 | 0.00 | -513.48 | 0.00 | 0.00 | 130.71 | 34.44 | 221.25 | 2030.34 | 0.00 | 0.00 | 10932.77 | 0.00 | -0.00 | 0.00 | -239.80 | 0.00 |
ROOM_6_FLR_3 | 20-JUN-08:11 | 0.00 | -13143.19 | 0.00 | -961.69 | 0.00 | 0.00 | 66.62 | 241.07 | 452.99 | 9030.27 | 0.00 | 0.00 | 4450.13 | 0.00 | -0.00 | 0.00 | -136.20 | 0.00 |
ROOM_1_FLR_6 | 29-APR-18:01 | 0.00 | -3878.71 | 0.00 | -141.12 | 0.00 | 0.00 | 66.85 | 137.77 | 121.16 | 914.65 | 0.00 | 0.00 | 2835.42 | 0.00 | -0.00 | 0.00 | -56.03 | 0.00 |
ROOM_2_FLR_6 | 20-MAY-18:01 | 0.00 | -4443.33 | 0.00 | -192.19 | 0.00 | 0.00 | 51.94 | 137.75 | 121.15 | 1156.24 | 0.00 | 0.00 | 3242.67 | 0.00 | -0.00 | 0.00 | -74.24 | 0.00 |
ROOM_3_MULT9_FLR_6 | 30-JAN-16:11 | 0.00 | -13198.56 | 0.00 | -2796.00 | 0.00 | 0.00 | 559.70 | 62.36 | 441.28 | 751.59 | 0.00 | 0.00 | 15856.84 | 0.00 | -0.00 | 0.00 | -1677.20 | 0.00 |
BANQUET_FLR_6 | 19-JAN-01:52 | 0.00 | 0.00 | 0.00 | -50443.14 | 0.00 | 0.00 | 16868.18 | 321.29 | 2249.30 | 0.00 | 0.00 | 0.00 | 34716.10 | 0.00 | -2845.21 | 0.00 | -866.52 | 0.00 |
DINING_FLR_6 | 19-JAN-01:52 | 0.00 | 0.00 | 0.00 | -51981.22 | 0.00 | 0.00 | 16140.47 | 321.29 | 2249.30 | 0.00 | 0.00 | 0.00 | 37066.59 | 0.00 | -2915.92 | 0.00 | -880.52 | 0.00 |
KITCHEN_FLR_6 | 25-NOV-21:14 | 0.00 | 0.00 | 0.00 | -56502.85 | 0.00 | 0.00 | 854.24 | 848.43 | 18953.20 | 0.00 | 0.00 | 0.00 | 38879.80 | 0.00 | -2214.53 | 0.00 | -818.28 | 0.00 |
MECH_FLR_1 | 29-JUN-23:19 | 0.00 | 0.00 | 0.00 | -3121.43 | 0.00 | 0.00 | 0.00 | 335.90 | 265.09 | 0.00 | 0.00 | 0.00 | 2532.28 | 0.00 | -0.00 | 0.00 | -11.84 | 0.00 |
STORAGE_FLR_1 | 29-JUN-23:19 | 0.00 | 0.00 | 0.00 | -1228.36 | 0.00 | 0.00 | 0.00 | 34.49 | 76.47 | 0.00 | 0.00 | 0.00 | 1125.26 | 0.00 | -0.00 | 0.00 | -7.86 | 0.00 |
CORRIDOR_FLR_3 | 06-JUL-13:43 | 0.00 | 0.00 | 0.00 | -8890.41 | 0.00 | 0.00 | 0.00 | 931.95 | 0.00 | 3597.65 | 0.00 | 68.03 | 4292.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 01-JUL-17:12 | 0.00 | 0.00 | 0.00 | -7865.37 | 0.00 | 0.00 | 0.00 | 591.79 | 0.00 | 713.16 | 0.00 | 7.98 | 6552.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUN-18:01 | 0.00 | -149527.04 | 0.00 | -321777.48 | 0.00 | 0.00 | 60529.46 | 39163.16 | 120174.13 | 45348.82 | 0.00 | 2885.30 | 203256.99 | 0.00 | 0.00 | 0.00 | -53.35 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 04-FEB-11:22 | 0.00 | 0.00 | 1325.67 | -0.00 | 0.00 | 0.00 | 2856.80 | 3047.38 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10778.68 |
RETAIL_1_FLR_1 | 20-JAN-08:02 | 0.00 | 0.00 | 3044.06 | -0.00 | 0.00 | 0.00 | 436.24 | 242.58 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1378.01 | 0.00 | -1027.55 | -1678.16 |
RETAIL_2_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 1302.98 | -0.00 | 0.00 | 0.00 | 379.88 | 175.56 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -217.66 | -1933.27 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 20-JAN-08:02 | 0.00 | 0.00 | 7624.42 | -0.00 | 0.00 | 0.00 | 5143.79 | 316.67 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4154.66 | 0.00 | -2809.69 | -6628.56 |
LOBBY_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 19721.62 | -0.00 | 0.00 | 0.00 | 11977.94 | 1544.00 | 3694.97 | 21869.16 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5501.77 | -53305.92 |
ROOM_1_FLR_3 | 04-FEB-07:52 | 8790.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.83 | 227.32 | 653.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3866.66 | 0.00 | -1599.82 | -4489.17 |
ROOM_2_FLR_3 | 01-FEB-10:53 | 8751.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.98 | 34.44 | 126.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3144.55 | 0.00 | -1516.59 | -4356.31 |
ROOM_3_MULT19_FLR_3 | 19-JAN-05:01 | 26066.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 904.79 | 3333.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21808.04 | 0.00 | -7107.23 | -1389.41 |
ROOM_4_MULT19_FLR_3 | 02-FEB-10:51 | 47176.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2147.77 | 411.38 | 2353.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17934.83 | 0.00 | -8567.59 | -25587.03 |
ROOM_5_FLR_3 | 02-FEB-17:53 | 8340.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.28 | 48.22 | 505.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4459.34 | 0.00 | -1596.75 | -3122.62 |
ROOM_6_FLR_3 | 03-FEB-07:51 | 8333.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.53 | 309.95 | 948.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3383.89 | 0.00 | -1700.54 | -4750.76 |
ROOM_1_FLR_6 | 03-FEB-07:52 | 2521.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.64 | 77.50 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1038.46 | 0.00 | -433.03 | -1422.62 |
ROOM_2_FLR_6 | 01-FEB-07:53 | 2507.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.94 | 77.49 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1115.59 | 0.00 | -411.04 | -1351.76 |
ROOM_3_MULT9_FLR_6 | 09-DEC-16:11 | 10136.84 | 410.86 | 0.00 | -410.86 | 0.00 | 0.00 | 367.48 | 48.72 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3917.72 | 0.00 | -1345.23 | -5777.83 |
BANQUET_FLR_6 | 04-FEB-11:22 | 0.00 | 0.00 | 8069.10 | -0.00 | 0.00 | 0.00 | 7100.24 | 321.29 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1329.54 | 0.00 | -787.61 | -20121.39 |
DINING_FLR_6 | 04-FEB-11:22 | 0.00 | 0.00 | 5315.19 | -0.00 | 0.00 | 0.00 | 6734.96 | 321.29 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1427.34 | 0.00 | -814.02 | -16878.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 1946.74 | -0.00 | 0.00 | 0.00 | 0.00 | 419.88 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -467.68 | -2208.20 |
STORAGE_FLR_1 | 04-FEB-11:22 | 0.00 | 0.00 | 1544.37 | -0.00 | 0.00 | 0.00 | 0.00 | 43.12 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -311.84 | -1364.86 |
CORRIDOR_FLR_3 | 04-FEB-11:22 | 0.00 | 0.00 | 11203.06 | -0.00 | 0.00 | 0.00 | 0.00 | 931.95 | 0.00 | 6839.80 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1432.18 | -17542.63 |
CORRIDOR_FLR_6 | 04-FEB-11:22 | 0.00 | 0.00 | 6403.22 | -0.00 | 0.00 | 0.00 | 0.00 | 246.58 | 0.00 | 3979.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -603.20 | -10026.31 |
Total Facility | 12-DEC-16:12 | -18141.92 | 129022.68 | 19058.50 | -129022.68 | 0.00 | 0.00 | 53596.76 | 9855.08 | 73604.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -72323.18 | 0.00 | -30257.15 | -35392.38 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 20.2562 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 19.6456 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.9895 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 10.5252 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2797 | 2.2797 | 1.2812 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2976 | 0.2976 | 0.1187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2117 | 0.2117 | 0.1376 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4060 | 3.4060 | 0.0341 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2879 | 1.2879 | 1.0136 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.2380 | 4.2380 | 2.8395 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0711 | 2.0711 | 1.7811 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1792 | 2.1792 | 1.7804 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2734 | 2.2734 | 0.5502 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2186 | 0.2186 | 0.0022 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0864 | 0.0864 | 0.0864 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 0.7121 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5198 | 0.5198 | 0.1882 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 20.2562 | 19.6456 | 20.2562 | 10.5252 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2812 | 1.2812 | 1.2812 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1488 | 0.1488 | 0.1187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1376 | 0.1376 | 0.1376 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7030 | 1.7030 | 0.0341 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0136 | 1.0136 | 1.0136 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8395 | 2.8395 | 2.8395 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7811 | 1.7811 | 1.7811 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7804 | 1.7804 | 1.7804 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1367 | 1.1367 | 0.5502 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1093 | 0.1093 | 0.0022 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0864 | 0.0864 | 0.0864 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7121 | 0.7121 | 0.7121 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2599 | 0.2599 | 0.1882 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.9895 | 10.5252 | 10.5252 | 10.5252 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:49:30
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 586.50 |
Number of hours cooling loads not met | 8599.00 |
Number of hours not met | 8756.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 1112.79 | 444491.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 616.78 | 176926.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 525.93 | 47387.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 182.61 | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.73 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.51 | 1274.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 187.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 664.24 | 33249.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 36.92 | 3520.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 106.48 | 6004.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.56 | 4739.42 | 2275.68 | 180940.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 18.38 | 1556.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 23.03 | 734.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1696.97 | 4892.46 |
Natural Gas | 1788.85 | 5177.32 |
Additional | 0.00 | 0.00 |
Total | 3485.82 | 10069.79 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.36 |
Space Heating | 0.00 |
Space Cooling | 54.36 |
Fans (All) | 58.55 |
Service Water Heating | 7.98 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 431.23 |
Subtotal | 431.23 |
Natural Gas [MJ/m2] | |
Space Heating | 98.08 |
Service Water Heating | 200.58 |
Miscellaneous (All) | 456.34 |
Subtotal | 456.34 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.22 |
Space Heating | 11.05 |
Space Cooling | 6.13 |
Fans (All) | 6.60 |
Service Water Heating | 23.50 |
Receptacle Equipment | 34.13 |
Miscellaneous | 13.37 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 1660. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 2221. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2737. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1362. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.370544E+12 |
February | 0.000 | 0.247277E+12 |
March | 0.000 | 0.885365E+11 |
April | 0.000 | 0.313328E+11 |
May | 0.000 | 0.250533E+10 |
June | 0.000 | 0.962941E+09 |
July | 0.000 | 0.907834E+08 |
August | 0.000 | 0.960492E+08 |
September | 0.000 | 0.486283E+10 |
October | 0.000 | 0.226529E+11 |
November | 0.000 | 0.118663E+12 |
December | 0.000 | 0.225266E+12 |
Annual Sum or Average | 0.111279E+13 | |
Minimum of Months | 0.000 | 0.907834E+08 |
Maximum of Months | 0.000 | 0.370544E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.370544E+12 |
February | 0.000 | 0.247277E+12 |
March | 0.000 | 0.885365E+11 |
April | 0.000 | 0.313328E+11 |
May | 0.000 | 0.250533E+10 |
June | 0.000 | 0.962941E+09 |
July | 0.000 | 0.907834E+08 |
August | 0.000 | 0.960492E+08 |
September | 0.000 | 0.486283E+10 |
October | 0.000 | 0.226529E+11 |
November | 0.000 | 0.118663E+12 |
December | 0.000 | 0.225266E+12 |
Annual Sum or Average | 0.111279E+13 | |
Minimum of Months | 0.000 | 0.907834E+08 |
Maximum of Months | 0.000 | 0.370544E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.370544E+12 |
February | 0.000 | 0.247277E+12 |
March | 0.000 | 0.885365E+11 |
April | 0.000 | 0.313328E+11 |
May | 0.000 | 0.250533E+10 |
June | 0.000 | 0.962941E+09 |
July | 0.000 | 0.907834E+08 |
August | 0.000 | 0.960492E+08 |
September | 0.000 | 0.486283E+10 |
October | 0.000 | 0.226529E+11 |
November | 0.000 | 0.118663E+12 |
December | 0.000 | 0.225266E+12 |
Annual Sum or Average | 0.111279E+13 | |
Minimum of Months | 0.000 | 0.907834E+08 |
Maximum of Months | 0.000 | 0.370544E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.370544E+12 |
February | 0.000 | 0.247277E+12 |
March | 0.000 | 0.885365E+11 |
April | 0.000 | 0.313328E+11 |
May | 0.000 | 0.250533E+10 |
June | 0.000 | 0.962941E+09 |
July | 0.000 | 0.907834E+08 |
August | 0.000 | 0.960492E+08 |
September | 0.000 | 0.486283E+10 |
October | 0.000 | 0.226529E+11 |
November | 0.000 | 0.118663E+12 |
December | 0.000 | 0.225266E+12 |
Annual Sum or Average | 0.111279E+13 | |
Minimum of Months | 0.000 | 0.907834E+08 |
Maximum of Months | 0.000 | 0.370544E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.370544E+12 |
February | 0.000 | 0.247277E+12 |
March | 0.000 | 0.885365E+11 |
April | 0.000 | 0.313328E+11 |
May | 0.000 | 0.250533E+10 |
June | 0.000 | 0.962941E+09 |
July | 0.000 | 0.907834E+08 |
August | 0.000 | 0.960492E+08 |
September | 0.000 | 0.486283E+10 |
October | 0.000 | 0.226529E+11 |
November | 0.000 | 0.118663E+12 |
December | 0.000 | 0.225266E+12 |
Annual Sum or Average | 0.111279E+13 | |
Minimum of Months | 0.000 | 0.907834E+08 |
Maximum of Months | 0.000 | 0.370544E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.370544E+12 |
February | 0.000 | 0.247277E+12 |
March | 0.000 | 0.885365E+11 |
April | 0.000 | 0.313328E+11 |
May | 0.000 | 0.250533E+10 |
June | 0.000 | 0.962941E+09 |
July | 0.000 | 0.907834E+08 |
August | 0.000 | 0.960492E+08 |
September | 0.000 | 0.486283E+10 |
October | 0.000 | 0.226529E+11 |
November | 0.000 | 0.118663E+12 |
December | 0.000 | 0.225266E+12 |
Annual Sum or Average | 0.111279E+13 | |
Minimum of Months | 0.000 | 0.907834E+08 |
Maximum of Months | 0.000 | 0.370544E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.370544E+12 |
February | 0.000 | 0.247277E+12 |
March | 0.000 | 0.885365E+11 |
April | 0.000 | 0.313328E+11 |
May | 0.000 | 0.250533E+10 |
June | 0.000 | 0.962941E+09 |
July | 0.000 | 0.907834E+08 |
August | 0.000 | 0.960492E+08 |
September | 0.000 | 0.486283E+10 |
October | 0.000 | 0.226529E+11 |
November | 0.000 | 0.118663E+12 |
December | 0.000 | 0.225266E+12 |
Annual Sum or Average | 0.111279E+13 | |
Minimum of Months | 0.000 | 0.907834E+08 |
Maximum of Months | 0.000 | 0.370544E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.370544E+12 |
February | 0.000 | 0.247277E+12 |
March | 0.000 | 0.885365E+11 |
April | 0.000 | 0.313328E+11 |
May | 0.000 | 0.250533E+10 |
June | 0.000 | 0.962941E+09 |
July | 0.000 | 0.907834E+08 |
August | 0.000 | 0.960492E+08 |
September | 0.000 | 0.486283E+10 |
October | 0.000 | 0.226529E+11 |
November | 0.000 | 0.118663E+12 |
December | 0.000 | 0.225266E+12 |
Annual Sum or Average | 0.111279E+13 | |
Minimum of Months | 0.000 | 0.907834E+08 |
Maximum of Months | 0.000 | 0.370544E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.370544E+12 |
February | 0.000 | 0.247277E+12 |
March | 0.000 | 0.885365E+11 |
April | 0.000 | 0.313328E+11 |
May | 0.000 | 0.250533E+10 |
June | 0.000 | 0.962941E+09 |
July | 0.000 | 0.907834E+08 |
August | 0.000 | 0.960492E+08 |
September | 0.000 | 0.486283E+10 |
October | 0.000 | 0.226529E+11 |
November | 0.000 | 0.118663E+12 |
December | 0.000 | 0.225266E+12 |
Annual Sum or Average | 0.111279E+13 | |
Minimum of Months | 0.000 | 0.907834E+08 |
Maximum of Months | 0.000 | 0.370544E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274929E+11 | 49631.96 | 05-JAN-21:22 | -23.6 | -23.9 | 0.842199E+10 | 5478.21 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.223216E+11 | 44591.47 | 01-FEB-07:52 | -32.2 | -32.3 | 0.714226E+10 | 5307.24 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.222308E+11 | 26237.24 | 19-MAR-19:29 | 15.25 | 11.77 | 0.842297E+10 | 5213.12 | 01-MAR-22:10 | -4.4 | -5.1 |
April | 0.199507E+11 | 27148.50 | 14-APR-19:11 | 18.70 | 13.11 | 0.803244E+10 | 5127.91 | 20-APR-21:10 | 7.70 | 3.19 |
May | 0.230591E+11 | 28620.40 | 05-MAY-19:11 | 21.47 | 12.30 | 0.831173E+10 | 5196.91 | 19-MAY-21:10 | 6.97 | 4.81 |
June | 0.258459E+11 | 30345.45 | 29-JUN-20:51 | 24.40 | 19.17 | 0.812206E+10 | 5257.78 | 05-JUN-21:10 | 11.70 | 11.34 |
July | 0.297588E+11 | 31188.42 | 26-JUL-23:05 | 22.70 | 21.17 | 0.837948E+10 | 5213.62 | 11-JUL-21:10 | 15.92 | 14.61 |
August | 0.328585E+11 | 31900.89 | 10-AUG-08:28 | 21.10 | 17.04 | 0.859957E+10 | 5388.65 | 17-AUG-21:10 | 15.82 | 13.28 |
September | 0.318707E+11 | 32758.50 | 23-SEP-14:22 | 21.15 | 11.45 | 0.877512E+10 | 6036.18 | 29-SEP-21:10 | 2.62 | 0.96 |
October | 0.317884E+11 | 34107.54 | 20-OCT-12:23 | 21.45 | 12.41 | 0.985462E+10 | 6175.07 | 18-OCT-21:10 | -0.1 | -1.4 |
November | 0.303922E+11 | 75012.75 | 25-NOV-21:32 | -24.0 | -24.4 | 0.940240E+10 | 6161.11 | 01-NOV-21:10 | 6.60 | 5.09 |
December | 0.291119E+11 | 23713.43 | 08-DEC-21:00 | -22.8 | -23.1 | 0.939677E+10 | 5909.77 | 07-DEC-22:10 | -7.8 | -9.6 |
Annual Sum or Average | 0.326681E+12 | 0.102861E+12 | ||||||||
Minimum of Months | 0.199507E+11 | 23713.43 | -32.2 | -32.3 | 0.714226E+10 | 5127.91 | -7.8 | -9.6 | ||
Maximum of Months | 0.328585E+11 | 75012.75 | 24.40 | 21.17 | 0.985462E+10 | 6175.07 | 15.92 | 14.61 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191802E+09 | 2713.95 | 12-JAN-12:34 | 2.03 | 0.42 | 0.568180E+09 | 443.56 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.409405E+09 | 3095.21 | 08-FEB-13:40 | 2.60 | 1.30 | 0.525968E+09 | 477.36 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.862944E+09 | 4015.24 | 25-MAR-13:57 | 16.70 | 9.60 | 0.689081E+09 | 494.01 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.143499E+10 | 4434.35 | 16-APR-11:50 | 24.82 | 19.56 | 0.718718E+09 | 511.58 | 18-APR-21:10 | 16.32 | 13.38 |
May | 0.220697E+10 | 4217.20 | 06-MAY-13:33 | 22.20 | 11.54 | 0.820023E+09 | 523.20 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.299371E+10 | 4213.64 | 29-JUN-18:21 | 28.05 | 20.18 | 0.816413E+09 | 548.24 | 26-JUN-21:10 | 25.40 | 21.25 |
July | 0.350564E+10 | 4223.63 | 28-JUL-11:23 | 25.30 | 19.01 | 0.848479E+09 | 535.92 | 03-JUL-21:10 | 24.22 | 22.81 |
August | 0.349069E+10 | 4672.62 | 29-AUG-13:15 | 23.50 | 16.48 | 0.855426E+09 | 541.51 | 02-AUG-21:10 | 24.32 | 21.63 |
September | 0.278157E+10 | 5020.40 | 17-SEP-12:50 | 25.68 | 17.80 | 0.808072E+09 | 563.94 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.176213E+10 | 5161.27 | 20-OCT-13:24 | 22.20 | 12.80 | 0.779895E+09 | 520.04 | 20-OCT-21:10 | 13.90 | 9.44 |
November | 0.794557E+09 | 4463.49 | 03-NOV-13:17 | 15.77 | 10.84 | 0.658774E+09 | 491.92 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.356200E+09 | 3231.43 | 03-DEC-13:00 | 5.60 | 2.40 | 0.614480E+09 | 406.60 | 01-DEC-22:10 | -3.8 | -4.6 |
Annual Sum or Average | 0.207906E+11 | 0.870351E+10 | ||||||||
Minimum of Months | 0.191802E+09 | 2713.95 | 2.03 | 0.42 | 0.525968E+09 | 406.60 | -3.8 | -4.6 | ||
Maximum of Months | 0.350564E+10 | 5161.27 | 28.05 | 20.18 | 0.855426E+09 | 563.94 | 25.40 | 22.81 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134713E+10 | 4023.23 | 05-JAN-21:52 | -23.9 | -24.2 | 0.829754E+09 | 611.32 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.139372E+10 | 2631.01 | 02-FEB-06:02 | -36.7 | -36.8 | 0.767130E+09 | 628.46 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.174483E+10 | 2572.52 | 19-MAR-18:53 | 16.10 | 12.23 | 0.968802E+09 | 652.09 | 24-MAR-21:10 | 2.43 | 0.92 |
April | 0.208749E+10 | 3038.38 | 15-APR-20:35 | 23.17 | 17.17 | 0.965474E+09 | 668.65 | 19-APR-21:10 | 7.62 | 3.95 |
May | 0.265453E+10 | 3044.65 | 31-MAY-22:07 | 19.42 | 14.31 | 0.102343E+10 | 660.37 | 22-MAY-21:10 | 9.32 | 7.91 |
June | 0.291418E+10 | 3173.65 | 29-JUN-23:19 | 23.30 | 18.93 | 0.998149E+09 | 672.79 | 29-JUN-21:10 | 24.22 | 19.11 |
July | 0.318398E+10 | 3115.78 | 26-JUL-23:05 | 22.70 | 21.17 | 0.102610E+10 | 667.58 | 03-JUL-21:10 | 24.22 | 22.81 |
August | 0.314237E+10 | 3107.08 | 22-AUG-23:05 | 20.92 | 19.49 | 0.103867E+10 | 674.26 | 04-AUG-21:10 | 18.30 | 17.90 |
September | 0.273954E+10 | 3115.92 | 08-SEP-23:15 | 19.80 | 15.50 | 0.100328E+10 | 689.55 | 08-SEP-21:10 | 17.38 | 14.80 |
October | 0.231481E+10 | 2914.37 | 20-OCT-15:35 | 21.97 | 12.93 | 0.101906E+10 | 667.47 | 30-OCT-21:10 | 4.78 | 3.08 |
November | 0.173701E+10 | 4111.52 | 25-NOV-21:32 | -24.0 | -24.4 | 0.926691E+09 | 664.92 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.133294E+10 | 1771.13 | 05-DEC-22:00 | -7.2 | -9.4 | 0.904323E+09 | 602.93 | 05-DEC-22:10 | -7.1 | -9.3 |
Annual Sum or Average | 0.265925E+11 | 0.114709E+11 | ||||||||
Minimum of Months | 0.133294E+10 | 1771.13 | -36.7 | -36.8 | 0.767130E+09 | 602.93 | -7.1 | -9.3 | ||
Maximum of Months | 0.318398E+10 | 4111.52 | 23.30 | 21.17 | 0.103867E+10 | 689.55 | 24.22 | 22.81 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86145615.49 | 1069.54 | 13-JAN-21:52 | 2.20 | 0.77 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.147359E+09 | 1692.89 | 24-FEB-21:00 | 2.20 | 1.49 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.530240E+09 | 2345.76 | 19-MAR-21:21 | 14.70 | 11.66 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.116824E+10 | 2983.62 | 15-APR-20:35 | 23.17 | 17.17 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.213825E+10 | 2980.32 | 31-MAY-18:12 | 26.83 | 18.96 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.261898E+10 | 3121.50 | 29-JUN-23:19 | 23.30 | 18.93 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.291464E+10 | 3080.37 | 26-JUL-23:10 | 22.70 | 21.17 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.285919E+10 | 3039.80 | 05-AUG-08:25 | 23.05 | 19.34 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.232725E+10 | 3025.79 | 08-SEP-08:29 | 23.35 | 17.65 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.157838E+10 | 2616.22 | 20-OCT-18:13 | 16.83 | 10.69 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.730147E+09 | 2109.11 | 08-NOV-22:00 | 14.40 | 12.79 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 48853443.50 | 1232.11 | 04-DEC-20:52 | 1.70 | 0.04 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.171477E+11 | 0.00 | ||||||||
Minimum of Months | 48853443.50 | 1069.54 | 1.70 | 0.04 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.291464E+10 | 3121.50 | 26.83 | 21.17 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165812E+09 | 727.46 | 19-JAN-07:52 | -28.3 | -28.5 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.351126E+09 | 734.48 | 02-FEB-07:02 | -36.7 | -36.8 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.566993E+09 | 976.70 | 25-MAR-15:17 | 18.53 | 10.44 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.770641E+09 | 1130.04 | 16-APR-11:29 | 24.45 | 19.34 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.102452E+10 | 1145.29 | 31-MAY-18:12 | 26.83 | 18.96 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.115685E+10 | 1228.38 | 29-JUN-23:19 | 23.30 | 18.93 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.128445E+10 | 1210.61 | 04-JUL-02:13 | 21.67 | 20.91 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.124727E+10 | 1202.79 | 05-AUG-10:03 | 23.48 | 18.55 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.102947E+10 | 1192.02 | 11-SEP-10:00 | 25.00 | 20.00 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.800548E+09 | 1088.44 | 20-OCT-15:05 | 22.97 | 13.24 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.559632E+09 | 967.24 | 03-NOV-14:35 | 16.10 | 9.87 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.264191E+09 | 481.68 | 03-DEC-15:52 | 3.30 | 0.76 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.922149E+10 | 0.00 | ||||||||
Minimum of Months | 0.165812E+09 | 481.68 | -36.7 | -36.8 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.128445E+10 | 1228.38 | 26.83 | 20.91 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.437341E+11 | 82717.05 | 05-JAN-21:34 | -23.7 | -24.0 | 0.782655E+09 | 747.53 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.401276E+11 | 68851.70 | 01-FEB-20:52 | -28.9 | -29.1 | 0.712107E+09 | 752.88 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.462728E+11 | 68003.07 | 23-MAR-20:01 | 9.90 | 6.65 | 0.821413E+09 | 858.15 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.458923E+11 | 69083.27 | 14-APR-20:01 | 15.92 | 12.07 | 0.788411E+09 | 769.76 | 19-APR-21:10 | 7.62 | 3.95 |
May | 0.491923E+11 | 69802.24 | 05-MAY-20:01 | 17.43 | 11.42 | 0.814289E+09 | 816.45 | 05-MAY-21:10 | 15.40 | 10.69 |
June | 0.486764E+11 | 72823.42 | 29-JUN-19:51 | 25.00 | 19.38 | 0.782299E+09 | 829.58 | 21-JUN-21:10 | 14.40 | 12.12 |
July | 0.505740E+11 | 72640.51 | 05-JUL-19:51 | 23.30 | 21.01 | 0.794887E+09 | 788.86 | 28-JUL-21:10 | 19.40 | 17.20 |
August | 0.506843E+11 | 72518.45 | 01-AUG-19:51 | 21.10 | 19.55 | 0.811082E+09 | 817.23 | 16-AUG-21:10 | 15.50 | 13.14 |
September | 0.476626E+11 | 71158.99 | 01-SEP-20:01 | 18.90 | 13.04 | 0.787857E+09 | 866.37 | 19-SEP-21:10 | 7.12 | 5.30 |
October | 0.475325E+11 | 68547.08 | 19-OCT-19:51 | 8.90 | 5.89 | 0.827901E+09 | 861.49 | 19-OCT-21:10 | 7.17 | 4.85 |
November | 0.445752E+11 | 73654.65 | 25-NOV-21:14 | -23.7 | -24.1 | 0.785342E+09 | 763.18 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.445216E+11 | 61311.96 | 01-DEC-20:52 | -5.0 | -5.7 | 0.801402E+09 | 742.76 | 05-DEC-22:10 | -7.1 | -9.3 |
Annual Sum or Average | 0.559446E+12 | 0.950964E+10 | ||||||||
Minimum of Months | 0.401276E+11 | 61311.96 | -28.9 | -29.1 | 0.712107E+09 | 742.76 | -7.1 | -9.3 | ||
Maximum of Months | 0.506843E+11 | 82717.05 | 25.00 | 21.01 | 0.827901E+09 | 866.37 | 19.40 | 17.20 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.759021E+10 | 13602.81 | 05-JAN-21:52 | -23.9 | -24.2 | 0.873404E+10 | 6823.48 | 13-JAN-22:30 | 1.65 | 0.57 |
February | 0.876824E+10 | 14222.09 | 02-FEB-06:02 | -36.7 | -36.8 | 0.832902E+10 | 7042.12 | 24-FEB-22:19 | 1.67 | 1.15 |
March | 0.107180E+11 | 17679.20 | 25-MAR-13:57 | 16.70 | 9.60 | 0.105978E+11 | 7397.70 | 23-MAR-21:19 | 9.23 | 5.99 |
April | 0.125143E+11 | 18479.92 | 16-APR-11:26 | 24.45 | 19.34 | 0.106834E+11 | 7516.88 | 18-APR-22:10 | 14.03 | 11.86 |
May | 0.155957E+11 | 18282.97 | 31-MAY-22:07 | 19.42 | 14.31 | 0.114551E+11 | 7494.75 | 05-MAY-22:10 | 14.03 | 10.36 |
June | 0.173070E+11 | 19376.75 | 26-JUN-23:07 | 23.80 | 20.39 | 0.112781E+11 | 7699.17 | 29-JUN-21:19 | 24.03 | 19.05 |
July | 0.190152E+11 | 19137.29 | 26-JUL-02:43 | 23.40 | 19.54 | 0.116141E+11 | 7590.27 | 25-JUL-21:40 | 25.77 | 21.14 |
August | 0.189501E+11 | 18986.40 | 29-AUG-13:15 | 23.50 | 16.48 | 0.118163E+11 | 7702.39 | 02-AUG-21:19 | 24.23 | 21.62 |
September | 0.166266E+11 | 20507.34 | 17-SEP-12:50 | 25.68 | 17.80 | 0.113771E+11 | 7827.41 | 07-SEP-21:19 | 22.07 | 16.31 |
October | 0.139346E+11 | 21322.45 | 20-OCT-12:23 | 21.45 | 12.41 | 0.114838E+11 | 7735.29 | 20-OCT-21:19 | 13.90 | 9.46 |
November | 0.101515E+11 | 18674.32 | 03-NOV-13:17 | 15.77 | 10.84 | 0.100663E+11 | 7434.06 | 03-NOV-21:19 | 5.73 | 3.32 |
December | 0.771816E+10 | 14996.45 | 03-DEC-13:00 | 5.60 | 2.40 | 0.965718E+10 | 6578.46 | 04-DEC-23:10 | 2.30 | 0.32 |
Annual Sum or Average | 0.158890E+12 | 0.127092E+12 | ||||||||
Minimum of Months | 0.759021E+10 | 13602.81 | -36.7 | -36.8 | 0.832902E+10 | 6578.46 | 1.65 | 0.32 | ||
Maximum of Months | 0.190152E+11 | 21322.45 | 25.68 | 20.39 | 0.118163E+11 | 7827.41 | 25.77 | 21.62 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334475E+11 | 83149.89 | 05-JAN-21:52 | -23.9 | -24.2 | 0.300262E+11 | 21596.87 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.348334E+11 | 58470.02 | 02-FEB-06:02 | -36.7 | -36.8 | 0.272587E+11 | 22044.58 | 24-FEB-22:30 | 1.40 | 0.87 |
March | 0.419103E+11 | 53002.02 | 25-MAR-13:57 | 16.70 | 9.60 | 0.340273E+11 | 22624.81 | 23-MAR-22:10 | 8.90 | 5.66 |
April | 0.467371E+11 | 61380.36 | 15-APR-20:35 | 23.17 | 17.17 | 0.336700E+11 | 23097.78 | 19-APR-21:30 | 7.25 | 3.75 |
May | 0.558211E+11 | 62258.84 | 31-MAY-22:07 | 19.42 | 14.31 | 0.355172E+11 | 22950.53 | 24-MAY-22:10 | 10.00 | 9.66 |
June | 0.601617E+11 | 65090.25 | 29-JUN-23:19 | 23.30 | 18.93 | 0.344566E+11 | 22897.89 | 29-JUN-21:40 | 23.67 | 18.92 |
July | 0.650675E+11 | 64153.98 | 26-JUL-23:05 | 22.70 | 21.17 | 0.352574E+11 | 22777.76 | 28-JUL-22:10 | 19.22 | 17.09 |
August | 0.645971E+11 | 63809.84 | 22-AUG-23:05 | 20.92 | 19.49 | 0.357896E+11 | 23052.11 | 17-AUG-22:10 | 14.32 | 12.46 |
September | 0.573374E+11 | 63862.33 | 08-SEP-00:53 | 21.10 | 16.14 | 0.347843E+11 | 23344.03 | 08-SEP-21:19 | 17.57 | 14.81 |
October | 0.505745E+11 | 59898.84 | 20-OCT-15:35 | 21.97 | 12.93 | 0.357807E+11 | 23193.28 | 24-OCT-21:40 | 9.60 | 5.57 |
November | 0.410118E+11 | 84586.99 | 25-NOV-21:32 | -24.0 | -24.4 | 0.326729E+11 | 23113.40 | 03-NOV-21:19 | 5.73 | 3.32 |
December | 0.344057E+11 | 38427.46 | 04-DEC-23:00 | 2.20 | 0.30 | 0.321436E+11 | 21340.80 | 04-DEC-23:10 | 2.30 | 0.32 |
Annual Sum or Average | 0.585905E+12 | 0.401385E+12 | ||||||||
Minimum of Months | 0.334475E+11 | 38427.46 | -36.7 | -36.8 | 0.272587E+11 | 21340.80 | 1.40 | 0.32 | ||
Maximum of Months | 0.650675E+11 | 84586.99 | 23.30 | 21.17 | 0.357896E+11 | 23344.03 | 23.67 | 18.92 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2377129.00 | 3355.60 | 12-JAN-16:11 | 2.43 | 0.92 | 91986037.67 | 56.69 | 05-JAN-02:09 | -19.2 | -19.4 |
February | 22002986.05 | 3630.02 | 20-FEB-16:11 | 2.43 | -0.6 | 82730265.77 | 56.69 | 05-FEB-05:40 | -17.4 | -17.8 |
March | 84669651.79 | 3640.99 | 22-MAR-15:11 | 6.70 | 3.36 | 94758379.20 | 56.69 | 23-MAR-21:40 | 9.07 | 5.84 |
April | 0.450912E+09 | 3794.66 | 29-APR-18:01 | 15.03 | 9.30 | 93464411.01 | 62.51 | 10-APR-21:19 | 16.33 | 11.96 |
May | 0.787363E+09 | 3691.39 | 21-MAY-18:01 | 16.93 | 9.10 | 98392171.38 | 56.69 | 31-MAY-22:10 | 19.42 | 14.31 |
June | 0.143773E+10 | 3297.30 | 13-JUN-15:11 | 28.50 | 23.25 | 95786691.60 | 56.69 | 26-JUN-23:30 | 23.60 | 20.21 |
July | 0.182084E+10 | 3308.85 | 12-JUL-15:11 | 24.07 | 17.01 | 99309893.21 | 56.69 | 09-JUL-01:19 | 15.93 | 15.59 |
August | 0.161926E+10 | 3323.91 | 30-AUG-18:01 | 20.13 | 17.18 | 99327266.13 | 56.69 | 12-AUG-03:09 | 15.68 | 14.34 |
September | 0.103843E+10 | 3658.58 | 20-SEP-18:01 | 17.23 | 10.69 | 95117499.85 | 56.69 | 06-SEP-02:30 | 16.95 | 13.44 |
October | 0.236753E+09 | 3655.51 | 27-OCT-15:11 | 9.87 | 4.35 | 96537156.39 | 56.69 | 20-OCT-23:19 | 13.90 | 9.68 |
November | 49745065.27 | 3677.68 | 04-NOV-15:11 | 13.87 | 6.60 | 90855004.67 | 56.69 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 4771551.65 | 2378.33 | 01-DEC-16:11 | -2.4 | -4.4 | 92491470.78 | 56.69 | 10-DEC-03:49 | -21.6 | -22.0 |
Annual Sum or Average | 0.755485E+10 | 0.113076E+10 | ||||||||
Minimum of Months | 2377129.00 | 2378.33 | -2.4 | -4.4 | 82730265.77 | 56.69 | -21.6 | -22.0 | ||
Maximum of Months | 0.182084E+10 | 3794.66 | 28.50 | 23.25 | 99327266.13 | 62.51 | 23.60 | 20.21 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 207351.95 | 172.67 | 12-JAN-16:13 | 2.43 | 0.92 | 91496438.21 | 56.69 | 15-JAN-02:49 | -14.9 | -15.6 |
February | 6553033.24 | 3274.65 | 20-FEB-16:11 | 2.43 | -0.6 | 81596544.20 | 56.69 | 06-FEB-02:39 | -16.8 | -17.4 |
March | 37151609.26 | 3474.54 | 24-MAR-15:11 | 12.07 | 6.15 | 93863467.83 | 56.69 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.315074E+09 | 3667.81 | 29-APR-18:01 | 15.03 | 9.30 | 94110483.64 | 75.54 | 17-APR-18:10 | 18.03 | 11.62 |
May | 0.567932E+09 | 4123.87 | 20-MAY-18:01 | 15.22 | 8.18 | 0.101870E+09 | 77.78 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.115868E+10 | 3461.38 | 23-JUN-21:11 | 19.63 | 14.24 | 0.103003E+09 | 86.56 | 16-JUN-18:10 | 23.62 | 16.29 |
July | 0.135323E+10 | 3357.41 | 18-JUL-21:11 | 19.03 | 14.53 | 0.111047E+09 | 91.22 | 06-JUL-18:10 | 25.40 | 21.36 |
August | 0.115179E+10 | 3285.45 | 08-AUG-21:11 | 16.50 | 13.52 | 0.108953E+09 | 87.21 | 18-AUG-18:10 | 23.35 | 16.96 |
September | 0.694070E+09 | 3862.73 | 19-SEP-17:01 | 15.22 | 9.18 | 98804990.44 | 80.75 | 01-SEP-18:10 | 21.42 | 14.20 |
October | 99033290.66 | 3489.21 | 19-OCT-16:31 | 15.17 | 9.12 | 95562252.50 | 56.69 | 20-OCT-21:30 | 13.90 | 9.48 |
November | 19708006.62 | 3579.37 | 04-NOV-15:11 | 13.87 | 6.60 | 90118252.67 | 56.69 | 26-NOV-03:49 | -25.0 | -25.3 |
December | 421214.03 | 787.85 | 01-DEC-16:13 | -2.4 | -4.4 | 91918567.11 | 56.69 | 15-DEC-04:00 | -12.2 | -12.9 |
Annual Sum or Average | 0.540385E+10 | 0.116234E+10 | ||||||||
Minimum of Months | 207351.95 | 172.67 | -2.4 | -4.4 | 81596544.20 | 56.69 | -25.0 | -25.3 | ||
Maximum of Months | 0.135323E+10 | 4123.87 | 19.63 | 14.53 | 0.111047E+09 | 91.22 | 25.40 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3116325.70 | 213.68 | 30-JAN-15:01 | -24.0 | -24.3 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 7520762.50 | 252.59 | 02-FEB-15:01 | -28.9 | -29.2 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 17503236.84 | 209.88 | 25-MAR-15:02 | 18.72 | 10.43 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 88923336.48 | 422.16 | 15-APR-12:52 | 28.30 | 20.27 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.191100E+09 | 284.20 | 31-MAY-17:12 | 28.33 | 19.56 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.321458E+09 | 326.99 | 26-JUN-17:12 | 30.73 | 21.79 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.401914E+09 | 305.82 | 30-JUL-13:02 | 26.78 | 20.35 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.420187E+09 | 407.91 | 29-AUG-13:12 | 23.50 | 16.48 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.354680E+09 | 551.85 | 07-SEP-12:41 | 31.52 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.179641E+09 | 611.45 | 20-OCT-12:38 | 21.57 | 12.47 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 58734818.48 | 590.50 | 04-NOV-12:21 | 13.35 | 6.67 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 3869398.20 | 125.03 | 07-DEC-15:01 | -3.6 | -7.1 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.204865E+10 | 0.00 | ||||||||
Minimum of Months | 3116325.70 | 125.03 | -28.9 | -29.2 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.420187E+09 | 611.45 | 31.52 | 21.79 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3544283.99 | 561.08 | 01-JAN-09:01 | -3.2 | -3.4 | 91956927.24 | 56.69 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 11244093.70 | 753.60 | 25-FEB-09:01 | 0.78 | -0.3 | 82348622.69 | 56.69 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 76434141.98 | 926.56 | 11-MAR-09:01 | -1.9 | -3.5 | 95211349.83 | 56.69 | 29-MAR-22:10 | 7.20 | 6.65 |
April | 0.206988E+09 | 977.37 | 26-APR-18:01 | 9.13 | 3.52 | 94009277.87 | 69.99 | 18-APR-21:19 | 15.93 | 13.15 |
May | 0.422786E+09 | 1016.48 | 06-MAY-18:51 | 15.00 | 9.53 | 99951502.13 | 74.52 | 31-MAY-21:19 | 21.40 | 16.39 |
June | 0.580666E+09 | 1015.53 | 23-JUN-21:11 | 19.63 | 14.24 | 99849476.67 | 76.41 | 27-JUN-21:10 | 23.62 | 18.89 |
July | 0.617582E+09 | 992.04 | 18-JUL-21:11 | 19.03 | 14.53 | 0.105578E+09 | 77.92 | 05-JUL-21:10 | 22.43 | 20.32 |
August | 0.565757E+09 | 962.46 | 01-AUG-18:01 | 26.73 | 21.32 | 0.104510E+09 | 76.85 | 21-AUG-21:10 | 23.72 | 21.58 |
September | 0.412204E+09 | 977.66 | 10-SEP-21:11 | 23.30 | 16.94 | 97103710.60 | 73.62 | 11-SEP-21:19 | 19.40 | 17.91 |
October | 0.180543E+09 | 917.80 | 21-OCT-18:01 | 13.40 | 10.80 | 96401962.15 | 56.69 | 04-OCT-21:10 | 9.32 | 7.32 |
November | 77570052.05 | 870.07 | 09-NOV-09:01 | 9.03 | 7.06 | 91668345.48 | 56.69 | 07-NOV-22:10 | 12.80 | 11.46 |
December | 5308168.99 | 671.66 | 03-DEC-09:01 | -1.5 | -1.7 | 93221458.54 | 56.69 | 13-DEC-04:10 | -11.6 | -12.0 |
Annual Sum or Average | 0.316063E+10 | 0.115181E+10 | ||||||||
Minimum of Months | 3544283.99 | 561.08 | -3.2 | -3.5 | 82348622.69 | 56.69 | -11.6 | -12.0 | ||
Maximum of Months | 0.617582E+09 | 1016.48 | 26.73 | 21.32 | 0.105578E+09 | 77.92 | 23.72 | 21.58 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2063864.52 | 801.53 | 12-JAN-09:03 | -4.1 | -4.6 | 91693881.48 | 56.69 | 10-JAN-03:09 | -13.1 | -13.3 |
February | 15528354.42 | 2852.81 | 21-FEB-09:01 | -4.8 | -6.2 | 82169628.69 | 56.69 | 06-FEB-02:00 | -16.1 | -16.7 |
March | 77164645.80 | 3257.14 | 24-MAR-15:11 | 12.07 | 6.15 | 94890900.89 | 56.69 | 28-MAR-21:10 | 9.82 | 7.62 |
April | 0.376682E+09 | 3263.20 | 30-APR-18:01 | 15.22 | 9.03 | 93398981.24 | 59.71 | 10-APR-21:19 | 16.33 | 11.96 |
May | 0.828934E+09 | 3210.22 | 06-MAY-18:01 | 16.83 | 10.28 | 98911201.63 | 56.69 | 31-MAY-22:10 | 19.42 | 14.31 |
June | 0.144020E+10 | 3010.13 | 28-JUN-08:61 | 24.27 | 19.17 | 96001234.16 | 56.69 | 25-JUN-23:19 | 24.23 | 21.02 |
July | 0.174763E+10 | 3039.19 | 29-JUL-08:61 | 22.48 | 19.22 | 99466184.66 | 56.69 | 25-JUL-23:10 | 25.00 | 20.30 |
August | 0.153303E+10 | 2996.63 | 01-AUG-18:01 | 26.73 | 21.32 | 99540853.00 | 56.69 | 01-AUG-01:39 | 17.63 | 17.02 |
September | 0.102783E+10 | 3214.39 | 20-SEP-18:01 | 17.23 | 10.69 | 95435619.13 | 56.69 | 06-SEP-02:30 | 16.95 | 13.44 |
October | 0.199034E+09 | 3229.30 | 31-OCT-15:11 | 9.43 | 3.98 | 96678697.09 | 56.69 | 20-OCT-22:00 | 13.90 | 9.65 |
November | 40978055.07 | 3277.12 | 04-NOV-15:11 | 13.87 | 6.60 | 90821164.01 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 6355776.67 | 2063.12 | 03-DEC-09:01 | -1.5 | -1.7 | 92399113.75 | 56.69 | 11-DEC-02:30 | -21.7 | -22.1 |
Annual Sum or Average | 0.729543E+10 | 0.113141E+10 | ||||||||
Minimum of Months | 2063864.52 | 801.53 | -4.8 | -6.2 | 82169628.69 | 56.69 | -21.7 | -22.1 | ||
Maximum of Months | 0.174763E+10 | 3277.12 | 26.73 | 21.32 | 99540853.00 | 59.71 | 25.00 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 310417.83 | 481.91 | 12-JAN-09:04 | -4.1 | -4.6 | 91150219.70 | 56.69 | 05-JAN-23:30 | -24.7 | -25.0 |
February | 3941877.29 | 2183.19 | 24-FEB-09:01 | 3.07 | 0.60 | 80963453.97 | 56.69 | 07-FEB-01:00 | -1.7 | -2.6 |
March | 39090364.93 | 2988.52 | 22-MAR-08:61 | -1.4 | -3.1 | 93869049.02 | 56.69 | 28-MAR-21:10 | 9.82 | 7.62 |
April | 0.262787E+09 | 3231.19 | 30-APR-18:01 | 15.22 | 9.03 | 93570892.75 | 70.22 | 18-APR-21:19 | 15.93 | 13.15 |
May | 0.659607E+09 | 3254.85 | 31-MAY-08:11 | 24.23 | 19.12 | 0.101032E+09 | 75.75 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.120139E+10 | 3525.89 | 20-JUN-08:11 | 20.97 | 14.82 | 0.101395E+09 | 78.71 | 29-JUN-21:10 | 24.22 | 19.11 |
July | 0.136387E+10 | 3519.23 | 18-JUL-08:11 | 19.47 | 13.74 | 0.107979E+09 | 79.64 | 05-JUL-21:10 | 22.43 | 20.32 |
August | 0.115332E+10 | 3414.92 | 09-AUG-08:11 | 21.50 | 16.16 | 0.106142E+09 | 78.11 | 02-AUG-21:10 | 24.32 | 21.63 |
September | 0.718310E+09 | 3346.63 | 06-SEP-08:11 | 21.33 | 16.35 | 97872323.83 | 74.85 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 74039351.36 | 2711.02 | 01-OCT-08:61 | 10.72 | 8.44 | 95328941.88 | 56.69 | 20-OCT-21:00 | 13.90 | 9.53 |
November | 10573659.86 | 2236.09 | 04-NOV-08:61 | 2.77 | 0.70 | 90035631.85 | 56.69 | 29-NOV-01:00 | -6.1 | -7.0 |
December | 585462.99 | 827.68 | 03-DEC-09:02 | -1.5 | -1.7 | 91903127.96 | 56.69 | 09-DEC-00:10 | -22.8 | -23.0 |
Annual Sum or Average | 0.548783E+10 | 0.115124E+10 | ||||||||
Minimum of Months | 310417.83 | 481.91 | -4.1 | -4.6 | 80963453.97 | 56.69 | -24.7 | -25.0 | ||
Maximum of Months | 0.136387E+10 | 3525.89 | 24.23 | 19.12 | 0.107979E+09 | 79.64 | 24.32 | 21.63 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163504E+09 | 1587.70 | 06-JAN-07:52 | -28.3 | -28.5 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.183002E+09 | 1853.81 | 02-FEB-07:02 | -36.7 | -36.8 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.188960E+09 | 1701.99 | 25-MAR-14:45 | 18.53 | 10.29 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.633656E+09 | 2030.89 | 18-APR-18:17 | 22.80 | 16.70 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.146070E+10 | 1973.24 | 31-MAY-18:12 | 26.83 | 18.96 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.187207E+10 | 2193.91 | 29-JUN-23:19 | 23.30 | 18.93 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.223586E+10 | 2222.63 | 06-JUL-13:43 | 24.90 | 20.95 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.213627E+10 | 2193.21 | 05-AUG-11:47 | 24.90 | 19.02 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.154561E+10 | 2195.64 | 12-SEP-13:26 | 21.95 | 15.92 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.543567E+09 | 1935.47 | 20-OCT-15:05 | 22.97 | 13.24 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.162297E+09 | 1606.47 | 03-NOV-14:35 | 16.10 | 9.87 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 4136936.82 | 597.53 | 03-DEC-13:28 | 5.60 | 2.31 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.111296E+11 | 0.00 | ||||||||
Minimum of Months | 4136936.82 | 597.53 | -36.7 | -36.8 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.223586E+10 | 2222.63 | 26.83 | 20.95 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1752146.01 | 3500.09 | 12-JAN-16:11 | 2.43 | 0.92 | 91871801.88 | 56.69 | 04-JAN-23:10 | -16.7 | -17.0 |
February | 23330436.76 | 3773.50 | 20-FEB-16:11 | 2.43 | -0.6 | 82840454.43 | 56.69 | 18-FEB-02:20 | -15.8 | -16.2 |
March | 77657477.63 | 3782.62 | 24-MAR-15:11 | 12.07 | 6.15 | 94315837.59 | 56.69 | 19-MAR-23:49 | 13.48 | 11.19 |
April | 0.496405E+09 | 4020.08 | 29-APR-18:01 | 15.03 | 9.30 | 93252464.71 | 62.85 | 10-APR-21:19 | 16.33 | 11.96 |
May | 0.890346E+09 | 3855.33 | 21-MAY-18:01 | 16.93 | 9.10 | 98488187.15 | 56.69 | 10-MAY-01:49 | 14.40 | 12.17 |
June | 0.160650E+10 | 3393.49 | 17-JUN-18:01 | 23.72 | 19.21 | 95792528.78 | 56.69 | 25-JUN-23:19 | 24.23 | 21.02 |
July | 0.199771E+10 | 3444.84 | 13-JUL-18:01 | 24.72 | 19.29 | 99287017.17 | 56.69 | 09-JUL-01:19 | 15.93 | 15.59 |
August | 0.174335E+10 | 3465.82 | 21-AUG-18:01 | 26.52 | 21.93 | 99277432.80 | 56.69 | 31-AUG-00:20 | 18.13 | 16.46 |
September | 0.108976E+10 | 3811.11 | 20-SEP-18:01 | 17.23 | 10.69 | 94961227.87 | 56.69 | 02-SEP-04:40 | 9.40 | 8.33 |
October | 0.234907E+09 | 3801.06 | 31-OCT-15:11 | 9.43 | 3.98 | 96185343.76 | 56.69 | 20-OCT-22:40 | 13.90 | 9.61 |
November | 45476739.47 | 3830.05 | 04-NOV-15:11 | 13.87 | 6.60 | 90464875.99 | 56.69 | 26-NOV-05:00 | -26.1 | -26.4 |
December | 3256886.48 | 2772.17 | 01-DEC-16:11 | -2.4 | -4.4 | 92256760.81 | 56.69 | 07-DEC-04:49 | -12.1 | -13.3 |
Annual Sum or Average | 0.821045E+10 | 0.112899E+10 | ||||||||
Minimum of Months | 1752146.01 | 2772.17 | -2.4 | -4.4 | 82840454.43 | 56.69 | -26.1 | -26.4 | ||
Maximum of Months | 0.199771E+10 | 4020.08 | 26.52 | 21.93 | 99287017.17 | 62.85 | 24.23 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86224.88 | 940.86 | 12-JAN-16:13 | 2.43 | 0.92 | 91391649.70 | 56.69 | 28-JAN-01:30 | -22.8 | -23.0 |
February | 5087348.72 | 2345.14 | 24-FEB-16:11 | 7.93 | 5.63 | 81690592.87 | 56.69 | 15-FEB-04:49 | -11.0 | -11.5 |
March | 29782123.90 | 3567.62 | 24-MAR-15:11 | 12.07 | 6.15 | 93493258.09 | 56.69 | 08-MAR-05:00 | -13.3 | -14.0 |
April | 0.348462E+09 | 3865.13 | 29-APR-18:01 | 15.03 | 9.30 | 94202987.40 | 83.92 | 17-APR-18:10 | 18.03 | 11.62 |
May | 0.663806E+09 | 4635.61 | 20-MAY-18:01 | 15.22 | 8.18 | 0.103189E+09 | 83.55 | 30-MAY-21:19 | 19.63 | 16.88 |
June | 0.134685E+10 | 3769.05 | 22-JUN-21:01 | 15.60 | 12.06 | 0.104715E+09 | 95.99 | 08-JUN-18:10 | 22.88 | 16.37 |
July | 0.156498E+10 | 3803.19 | 23-JUL-21:11 | 17.57 | 13.04 | 0.113569E+09 | 99.73 | 06-JUL-18:10 | 25.40 | 21.36 |
August | 0.130023E+10 | 3514.18 | 16-AUG-21:01 | 15.50 | 13.14 | 0.111050E+09 | 95.62 | 18-AUG-18:10 | 23.35 | 16.96 |
September | 0.741248E+09 | 4111.60 | 19-SEP-17:01 | 15.22 | 9.18 | 99420694.00 | 89.93 | 01-SEP-18:10 | 21.42 | 14.20 |
October | 88211806.76 | 3650.62 | 19-OCT-16:31 | 15.17 | 9.12 | 95131513.70 | 57.44 | 11-OCT-18:10 | 15.35 | 9.77 |
November | 15642159.37 | 3702.28 | 04-NOV-15:11 | 13.87 | 6.60 | 89795840.14 | 56.69 | 22-NOV-02:49 | -9.4 | -10.1 |
December | 76469.24 | 707.29 | 02-DEC-16:13 | 4.30 | 2.44 | 91837084.08 | 56.69 | 06-DEC-03:49 | -9.5 | -11.1 |
Annual Sum or Average | 0.610446E+10 | 0.116949E+10 | ||||||||
Minimum of Months | 76469.24 | 707.29 | 2.43 | 0.92 | 81690592.87 | 56.69 | -22.8 | -23.0 | ||
Maximum of Months | 0.156498E+10 | 4635.61 | 17.57 | 13.14 | 0.113569E+09 | 99.73 | 25.40 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47724201.33 | 1776.92 | 30-JAN-16:11 | -24.6 | -24.9 | 93688712.46 | 56.69 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 87469811.28 | 1664.14 | 17-FEB-16:11 | -6.9 | -8.7 | 85066716.86 | 56.69 | 08-FEB-22:19 | -0.2 | -1.0 |
March | 0.146899E+09 | 1676.92 | 21-MAR-15:11 | -0.2 | -3.7 | 96155873.17 | 56.69 | 20-MAR-00:20 | 12.93 | 10.95 |
April | 0.315823E+09 | 1672.02 | 26-APR-15:11 | 10.20 | 3.42 | 93740394.47 | 64.94 | 10-APR-21:19 | 16.33 | 11.96 |
May | 0.521895E+09 | 1657.67 | 20-MAY-18:01 | 15.22 | 8.18 | 98656709.55 | 56.69 | 31-MAY-22:49 | 17.88 | 12.65 |
June | 0.815730E+09 | 1543.07 | 25-JUN-18:01 | 30.82 | 21.74 | 95872899.28 | 56.69 | 26-JUN-00:20 | 23.70 | 21.12 |
July | 0.986096E+09 | 1545.94 | 26-JUL-15:11 | 30.00 | 25.66 | 99224164.75 | 56.69 | 26-JUL-01:39 | 24.27 | 19.84 |
August | 0.976813E+09 | 1536.48 | 17-AUG-18:01 | 22.65 | 15.93 | 99270391.98 | 56.69 | 21-AUG-23:00 | 22.20 | 20.98 |
September | 0.789807E+09 | 1565.30 | 20-SEP-15:29 | 21.95 | 11.81 | 95426200.69 | 56.69 | 08-SEP-01:19 | 19.80 | 15.89 |
October | 0.428929E+09 | 1446.48 | 03-OCT-15:11 | 13.47 | 9.09 | 97754559.90 | 56.69 | 20-OCT-22:30 | 13.90 | 9.59 |
November | 0.152603E+09 | 1612.07 | 21-NOV-16:11 | -7.2 | -8.7 | 92414738.24 | 56.69 | 02-NOV-21:10 | 11.10 | 9.90 |
December | 93209666.85 | 1667.39 | 05-DEC-16:11 | -5.2 | -8.1 | 94289608.48 | 56.69 | 12-DEC-05:30 | -20.0 | -20.3 |
Annual Sum or Average | 0.536300E+10 | 0.114156E+10 | ||||||||
Minimum of Months | 47724201.33 | 1446.48 | -24.6 | -24.9 | 85066716.86 | 56.69 | -20.0 | -20.3 | ||
Maximum of Months | 0.986096E+09 | 1776.92 | 30.82 | 25.66 | 99270391.98 | 64.94 | 24.27 | 21.12 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238701E+11 | 50464.44 | 19-JAN-01:52 | -23.9 | -24.0 | 0.191829E+11 | 14303.59 | 13-JAN-23:10 | 0.82 | 0.04 |
February | 0.227602E+11 | 38601.73 | 02-FEB-06:02 | -36.7 | -36.8 | 0.173851E+11 | 14504.29 | 24-FEB-23:10 | 0.60 | 0.06 |
March | 0.259898E+11 | 28283.99 | 19-MAR-21:19 | 14.80 | 11.72 | 0.223229E+11 | 15109.35 | 29-MAR-22:10 | 7.20 | 6.65 |
April | 0.280650E+11 | 31838.41 | 16-APR-20:29 | 22.75 | 18.28 | 0.222347E+11 | 15384.56 | 19-APR-22:10 | 6.60 | 3.32 |
May | 0.326607E+11 | 33195.63 | 30-MAY-22:47 | 18.90 | 16.16 | 0.233579E+11 | 15435.79 | 24-MAY-22:10 | 10.00 | 9.66 |
June | 0.342832E+11 | 34213.11 | 29-JUN-21:51 | 23.30 | 18.79 | 0.226205E+11 | 15418.64 | 01-JUN-22:10 | 9.40 | 8.81 |
July | 0.366727E+11 | 33898.65 | 05-JUL-21:11 | 22.07 | 20.22 | 0.229680E+11 | 15211.86 | 05-JUL-22:10 | 20.60 | 19.73 |
August | 0.358160E+11 | 33779.05 | 02-AUG-21:51 | 23.90 | 21.57 | 0.231930E+11 | 15367.24 | 17-AUG-22:10 | 14.32 | 12.46 |
September | 0.315587E+11 | 32579.38 | 11-SEP-02:33 | 21.30 | 17.46 | 0.225013E+11 | 15345.90 | 19-SEP-22:10 | 6.70 | 5.27 |
October | 0.282736E+11 | 29079.78 | 20-OCT-16:03 | 20.95 | 12.54 | 0.232314E+11 | 15272.06 | 11-OCT-22:10 | 8.98 | 4.63 |
November | 0.250361E+11 | 40766.89 | 25-NOV-21:12 | -23.7 | -24.1 | 0.211901E+11 | 15135.55 | 06-NOV-23:10 | 10.60 | 9.72 |
December | 0.229775E+11 | 22325.13 | 04-DEC-23:02 | 2.30 | 0.32 | 0.209388E+11 | 14256.13 | 04-DEC-23:10 | 2.30 | 0.32 |
Annual Sum or Average | 0.347964E+12 | 0.261126E+12 | ||||||||
Minimum of Months | 0.227602E+11 | 22325.13 | -36.7 | -36.8 | 0.173851E+11 | 14256.13 | 0.60 | 0.04 | ||
Maximum of Months | 0.366727E+11 | 50464.44 | 23.90 | 21.57 | 0.233579E+11 | 15435.79 | 20.60 | 19.73 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274096E+11 | 52002.24 | 19-JAN-01:52 | -23.9 | -24.0 | 0.202466E+11 | 14970.05 | 13-JAN-23:10 | 0.82 | 0.04 |
February | 0.261499E+11 | 40226.86 | 02-FEB-06:02 | -36.7 | -36.8 | 0.184322E+11 | 15181.19 | 24-FEB-23:10 | 0.60 | 0.06 |
March | 0.296242E+11 | 30943.10 | 19-MAR-21:19 | 14.80 | 11.72 | 0.233911E+11 | 15734.05 | 23-MAR-22:10 | 8.90 | 5.66 |
April | 0.313353E+11 | 34257.51 | 16-APR-21:07 | 21.93 | 18.00 | 0.231629E+11 | 15908.19 | 19-APR-21:19 | 7.43 | 3.85 |
May | 0.359598E+11 | 35697.64 | 31-MAY-22:07 | 19.42 | 14.31 | 0.241642E+11 | 15960.55 | 18-MAY-22:10 | 9.90 | 7.31 |
June | 0.374337E+11 | 36926.51 | 29-JUN-21:11 | 24.03 | 19.05 | 0.233209E+11 | 15939.60 | 01-JUN-22:10 | 9.40 | 8.81 |
July | 0.398893E+11 | 36569.67 | 05-JUL-21:11 | 22.07 | 20.22 | 0.236105E+11 | 15675.74 | 28-JUL-22:10 | 19.22 | 17.09 |
August | 0.390517E+11 | 36515.23 | 02-AUG-21:51 | 23.90 | 21.57 | 0.238664E+11 | 15884.97 | 17-AUG-22:10 | 14.32 | 12.46 |
September | 0.346372E+11 | 34810.32 | 11-SEP-23:07 | 20.50 | 18.60 | 0.232284E+11 | 15916.93 | 19-SEP-22:10 | 6.70 | 5.27 |
October | 0.315291E+11 | 31568.27 | 20-OCT-16:03 | 20.95 | 12.54 | 0.241596E+11 | 15806.64 | 04-OCT-22:10 | 8.80 | 6.75 |
November | 0.284222E+11 | 51968.69 | 25-NOV-21:42 | -24.2 | -24.6 | 0.221945E+11 | 15676.04 | 06-NOV-23:10 | 10.60 | 9.72 |
December | 0.267651E+11 | 24857.67 | 04-DEC-23:02 | 2.30 | 0.32 | 0.220199E+11 | 14895.10 | 04-DEC-23:10 | 2.30 | 0.32 |
Annual Sum or Average | 0.388207E+12 | 0.271797E+12 | ||||||||
Minimum of Months | 0.261499E+11 | 24857.67 | -36.7 | -36.8 | 0.184322E+11 | 14895.10 | 0.60 | 0.04 | ||
Maximum of Months | 0.398893E+11 | 52002.24 | 24.03 | 21.57 | 0.241642E+11 | 15960.55 | 19.22 | 17.09 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393361E+11 | 54337.86 | 29-JAN-19:24 | -23.6 | -23.8 | 0.194395E+11 | 11862.37 | 14-JAN-18:00 | -9.4 | -10.4 |
February | 0.366744E+11 | 45168.92 | 01-FEB-11:32 | -27.8 | -28.0 | 0.176136E+11 | 11934.71 | 25-FEB-18:49 | 1.88 | 0.15 |
March | 0.428978E+11 | 45258.66 | 23-MAR-18:11 | 13.17 | 8.57 | 0.197014E+11 | 11996.16 | 25-MAR-17:00 | 15.00 | 9.99 |
April | 0.438155E+11 | 47549.84 | 16-APR-18:11 | 26.13 | 19.68 | 0.191022E+11 | 12010.70 | 29-APR-17:30 | 16.15 | 9.66 |
May | 0.483904E+11 | 51168.88 | 31-MAY-18:11 | 26.83 | 18.96 | 0.197463E+11 | 12055.59 | 20-MAY-17:00 | 15.60 | 8.28 |
June | 0.487295E+11 | 51611.68 | 29-JUN-18:01 | 28.62 | 20.21 | 0.190926E+11 | 12035.43 | 24-JUN-17:40 | 26.30 | 20.29 |
July | 0.511980E+11 | 51130.37 | 29-JUL-18:01 | 24.63 | 19.72 | 0.196790E+11 | 12065.31 | 29-JUL-17:00 | 25.00 | 19.69 |
August | 0.506728E+11 | 51450.01 | 02-AUG-18:11 | 27.43 | 22.31 | 0.197130E+11 | 11991.18 | 26-AUG-17:00 | 24.40 | 20.93 |
September | 0.466074E+11 | 50617.03 | 09-SEP-18:01 | 23.77 | 15.47 | 0.191027E+11 | 12040.88 | 09-SEP-17:00 | 24.40 | 15.59 |
October | 0.447494E+11 | 45620.67 | 11-OCT-17:31 | 15.97 | 10.35 | 0.197770E+11 | 11959.09 | 28-OCT-17:00 | 7.20 | 3.19 |
November | 0.409385E+11 | 56551.75 | 25-NOV-21:14 | -23.7 | -24.1 | 0.190265E+11 | 11973.88 | 04-NOV-17:49 | 5.97 | 2.43 |
December | 0.402671E+11 | 39467.60 | 03-DEC-11:42 | 4.90 | 2.33 | 0.195757E+11 | 11906.73 | 02-DEC-18:00 | 1.10 | 0.61 |
Annual Sum or Average | 0.534277E+12 | 0.231570E+12 | ||||||||
Minimum of Months | 0.366744E+11 | 39467.60 | -27.8 | -28.0 | 0.176136E+11 | 11862.37 | -9.4 | -10.4 | ||
Maximum of Months | 0.511980E+11 | 56551.75 | 28.62 | 22.31 | 0.197770E+11 | 12065.31 | 26.30 | 20.93 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107420E+09 | 1097.42 | 13-JAN-14:52 | 3.90 | 1.71 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.433504E+09 | 1275.33 | 24-FEB-14:32 | 8.13 | 5.46 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.115284E+10 | 4340.76 | 28-MAR-14:22 | 16.95 | 10.48 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.266032E+10 | 7367.37 | 18-APR-15:57 | 25.00 | 19.36 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.493473E+10 | 7537.99 | 29-MAY-13:03 | 24.72 | 19.75 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.660121E+10 | 7768.09 | 09-JUN-13:33 | 25.20 | 19.76 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.753193E+10 | 7865.65 | 01-JUL-17:12 | 26.10 | 18.79 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.709021E+10 | 7761.89 | 11-AUG-16:06 | 25.63 | 17.38 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.504541E+10 | 7659.44 | 12-SEP-13:40 | 22.23 | 15.84 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.237422E+10 | 7138.84 | 20-OCT-13:24 | 22.20 | 12.80 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.119268E+10 | 6399.75 | 03-NOV-13:36 | 15.93 | 10.65 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.242066E+09 | 1194.56 | 03-DEC-13:40 | 5.60 | 2.29 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.393665E+11 | 0.00 | ||||||||
Minimum of Months | 0.107420E+09 | 1097.42 | 3.90 | 1.71 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.753193E+10 | 7865.65 | 26.10 | 19.76 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 1125079.20 | 1325.65 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 1125079.20 | |||
Minimum of Months | 0.00 | 0.00 | -23.0 | |
Maximum of Months | 1125079.20 | 1325.65 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170867E+10 | 3043.98 | 20-JAN-08:02 | -23.0 |
February | 0.738550E+09 | 2805.68 | 05-FEB-07:02 | -19.2 |
March | 0.385247E+09 | 2223.35 | 06-MAR-05:02 | -15.4 |
April | 79262265.72 | 1682.67 | 03-APR-06:02 | -7.1 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 9665.87 | 61.18 | 23-OCT-06:02 | -3.0 |
November | 0.510727E+09 | 2645.72 | 26-NOV-09:02 | -22.7 |
December | 0.137648E+10 | 2795.98 | 10-DEC-06:02 | -22.6 |
Annual Sum or Average | 0.479895E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.0 | |
Maximum of Months | 0.170867E+10 | 3043.98 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10268965.41 | 895.41 | 31-JAN-11:42 | -23.1 |
February | 36357414.45 | 1302.95 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 59475.37 | 276.90 | 26-NOV-08:52 | -23.3 |
December | 2676.99 | 10.03 | 12-DEC-14:58 | -15.6 |
Annual Sum or Average | 46688532.21 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 36357414.45 | 1302.95 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130244E+09 | 1519.04 | 31-JAN-11:42 | -23.1 |
February | 0.180173E+09 | 1946.72 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 542234.61 | 177.98 | 26-NOV-17:52 | -13.9 |
December | 29545249.19 | 791.67 | 12-DEC-04:52 | -20.0 |
Annual Sum or Average | 0.340505E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.180173E+09 | 1946.72 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.515908E+09 | 1207.41 | 31-JAN-11:42 | -23.1 |
February | 0.169701E+09 | 1544.35 | 04-FEB-11:22 | -23.0 |
March | 7590026.93 | 436.87 | 06-MAR-04:44 | -15.7 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 88953937.63 | 961.19 | 26-NOV-09:02 | -22.7 |
December | 0.206145E+09 | 879.65 | 11-DEC-18:02 | -20.6 |
Annual Sum or Average | 0.988299E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.515908E+09 | 1544.35 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295218E+09 | 7624.02 | 20-JAN-08:02 | -23.0 |
February | 47856908.27 | 6249.31 | 04-FEB-11:22 | -23.0 |
March | 909.26 | 8.29 | 01-MAR-14:56 | -3.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 69427589.81 | 5775.48 | 26-NOV-09:02 | -22.7 |
December | 0.328974E+09 | 6044.79 | 12-DEC-15:00 | -15.6 |
Annual Sum or Average | 0.741477E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.0 | |
Maximum of Months | 0.328974E+09 | 7624.02 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8810726.22 | 12850.18 | 31-JAN-11:42 | -23.1 |
February | 0.154433E+09 | 19721.11 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 192209.11 | 3203.49 | 26-NOV-08:52 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.163436E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.154433E+09 | 19721.11 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.225786E+10 | 2040.82 | 19-JAN-19:01 | -23.3 |
February | 0.150221E+10 | 2197.51 | 04-FEB-07:52 | -30.6 |
March | 0.805728E+09 | 2001.80 | 01-MAR-16:11 | -3.9 |
April | 0.325421E+09 | 1993.38 | 03-APR-08:61 | -5.9 |
May | 24241118.21 | 1887.46 | 02-MAY-08:61 | 4.08 |
June | 8044185.73 | 1651.89 | 04-JUN-15:13 | 15.00 |
July | 1268509.78 | 1206.33 | 19-JUL-08:03 | 19.27 |
August | 1323097.71 | 1363.64 | 25-AUG-08:03 | 14.68 |
September | 59605059.80 | 1909.92 | 29-SEP-08:61 | 5.05 |
October | 0.252968E+09 | 1947.54 | 26-OCT-08:61 | 1.28 |
November | 0.100177E+10 | 2033.12 | 26-NOV-16:11 | -13.9 |
December | 0.187620E+10 | 2050.37 | 09-DEC-16:11 | -19.1 |
Annual Sum or Average | 0.811663E+10 | |||
Minimum of Months | 1268509.78 | 1206.33 | -30.6 | |
Maximum of Months | 0.225786E+10 | 2197.51 | 19.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260573E+10 | 2041.27 | 19-JAN-16:11 | -23.0 |
February | 0.178147E+10 | 2187.88 | 01-FEB-10:53 | -28.9 |
March | 0.943538E+09 | 1995.22 | 06-MAR-09:01 | -9.5 |
April | 0.364338E+09 | 1985.19 | 03-APR-08:61 | -5.9 |
May | 27358297.32 | 1886.39 | 02-MAY-08:61 | 4.08 |
June | 8183217.91 | 1611.73 | 01-JUN-08:03 | 12.88 |
July | 699285.61 | 1115.43 | 22-JUL-08:13 | 16.67 |
August | 1127636.26 | 1301.53 | 07-AUG-08:03 | 15.47 |
September | 73178353.50 | 1914.59 | 29-SEP-08:61 | 5.05 |
October | 0.361497E+09 | 1951.75 | 23-OCT-08:61 | 0.70 |
November | 0.118275E+10 | 2028.82 | 26-NOV-16:11 | -13.9 |
December | 0.215047E+10 | 2045.19 | 11-DEC-16:11 | -20.2 |
Annual Sum or Average | 0.950034E+10 | |||
Minimum of Months | 699285.61 | 1115.43 | -28.9 | |
Maximum of Months | 0.260573E+10 | 2187.88 | 16.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132855E+09 | 342.98 | 19-JAN-05:01 | -27.3 |
February | 33173277.25 | 287.98 | 04-FEB-05:51 | -30.6 |
March | 6282187.92 | 129.68 | 05-MAR-05:51 | -8.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 8216424.44 | 223.49 | 28-NOV-04:51 | -21.7 |
December | 82424421.74 | 259.94 | 12-DEC-04:51 | -20.0 |
Annual Sum or Average | 0.262952E+09 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 0.132855E+09 | 342.98 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.447049E+09 | 563.57 | 31-JAN-16:11 | -20.2 |
February | 0.277100E+09 | 620.78 | 02-FEB-10:51 | -31.7 |
March | 95342684.98 | 547.81 | 05-MAR-16:11 | -9.8 |
April | 15737493.84 | 521.16 | 03-APR-15:11 | -3.1 |
May | 178792.69 | 289.87 | 20-MAY-18:04 | 15.22 |
June | 80114.32 | 325.41 | 05-JUN-08:04 | 9.90 |
July | 34947.36 | 170.30 | 13-JUL-08:16 | 21.67 |
August | 73974.14 | 209.06 | 16-AUG-08:14 | 17.43 |
September | 466360.78 | 451.50 | 30-SEP-18:03 | 5.92 |
October | 2901831.17 | 443.97 | 28-OCT-08:03 | 1.55 |
November | 0.140623E+09 | 559.04 | 25-NOV-16:11 | -18.3 |
December | 0.333599E+09 | 560.92 | 09-DEC-16:11 | -19.1 |
Annual Sum or Average | 0.131319E+10 | |||
Minimum of Months | 34947.36 | 170.30 | -31.7 | |
Maximum of Months | 0.447049E+09 | 620.78 | 21.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224202E+10 | 1949.17 | 19-JAN-16:11 | -23.0 |
February | 0.151000E+10 | 2085.09 | 02-FEB-17:53 | -30.6 |
March | 0.789961E+09 | 1911.38 | 01-MAR-16:11 | -3.9 |
April | 0.354672E+09 | 1900.42 | 03-APR-08:61 | -5.9 |
May | 19908747.33 | 1594.78 | 20-MAY-18:03 | 15.22 |
June | 5790489.42 | 1181.86 | 02-JUN-18:03 | 13.90 |
July | 631686.80 | 950.68 | 09-JUL-08:03 | 17.03 |
August | 839923.29 | 1030.16 | 30-AUG-08:03 | 16.88 |
September | 52878880.04 | 1788.48 | 27-SEP-15:11 | 11.10 |
October | 0.254025E+09 | 1849.45 | 26-OCT-08:61 | 1.28 |
November | 0.100589E+10 | 1939.97 | 26-NOV-16:11 | -13.9 |
December | 0.187970E+10 | 1957.25 | 09-DEC-16:11 | -19.1 |
Annual Sum or Average | 0.811631E+10 | |||
Minimum of Months | 631686.80 | 950.68 | -30.6 | |
Maximum of Months | 0.224202E+10 | 2085.09 | 17.03 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258915E+10 | 2075.32 | 31-JAN-07:53 | -30.0 |
February | 0.179688E+10 | 2083.59 | 03-FEB-07:51 | -33.9 |
March | 0.928174E+09 | 1915.00 | 05-MAR-19:01 | -14.0 |
April | 0.402760E+09 | 1900.18 | 03-APR-08:61 | -5.9 |
May | 22900765.34 | 1470.46 | 20-MAY-18:03 | 15.22 |
June | 5936898.18 | 1394.06 | 03-JUN-18:03 | 14.22 |
July | 262875.98 | 942.77 | 10-JUL-21:13 | 15.73 |
August | 712714.43 | 980.17 | 30-AUG-08:13 | 17.07 |
September | 63899253.68 | 1792.89 | 27-SEP-15:11 | 11.10 |
October | 0.360108E+09 | 1860.20 | 26-OCT-08:61 | 1.28 |
November | 0.118776E+10 | 1944.00 | 26-NOV-16:11 | -13.9 |
December | 0.216135E+10 | 1959.42 | 09-DEC-16:11 | -19.1 |
Annual Sum or Average | 0.951989E+10 | |||
Minimum of Months | 262875.98 | 942.77 | -33.9 | |
Maximum of Months | 0.258915E+10 | 2083.59 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214182E+10 | 2297.74 | 31-JAN-11:42 | -23.1 |
February | 0.170884E+10 | 2800.74 | 04-FEB-11:22 | -23.0 |
March | 0.118071E+10 | 1746.53 | 06-MAR-06:02 | -14.1 |
April | 0.473738E+09 | 1636.35 | 03-APR-04:02 | -6.8 |
May | 11806922.46 | 664.74 | 02-MAY-04:58 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 45443307.64 | 1210.63 | 30-SEP-04:52 | 0.00 |
October | 0.262691E+09 | 1361.07 | 27-OCT-03:58 | 0.00 |
November | 0.123434E+10 | 1978.02 | 26-NOV-09:02 | -22.7 |
December | 0.226874E+10 | 2023.43 | 12-DEC-18:02 | -15.5 |
Annual Sum or Average | 0.932813E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.226874E+10 | 2800.74 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.285258E+10 | 2359.21 | 19-JAN-19:01 | -23.3 |
February | 0.187112E+10 | 2521.84 | 03-FEB-07:52 | -33.9 |
March | 0.114861E+10 | 2311.96 | 01-MAR-16:11 | -3.9 |
April | 0.498385E+09 | 2297.05 | 03-APR-08:61 | -5.9 |
May | 48781501.09 | 2198.04 | 02-MAY-08:61 | 4.08 |
June | 18879740.72 | 1542.40 | 03-JUN-18:03 | 14.22 |
July | 995252.91 | 979.61 | 19-JUL-08:03 | 19.27 |
August | 1178646.34 | 1324.90 | 09-AUG-08:03 | 21.05 |
September | 0.111075E+09 | 2235.12 | 29-SEP-08:61 | 5.05 |
October | 0.431949E+09 | 2274.62 | 26-OCT-08:61 | 1.28 |
November | 0.139363E+10 | 2349.24 | 26-NOV-16:11 | -13.9 |
December | 0.242740E+10 | 2369.84 | 09-DEC-16:11 | -19.1 |
Annual Sum or Average | 0.108046E+11 | |||
Minimum of Months | 995252.91 | 979.61 | -33.9 | |
Maximum of Months | 0.285258E+10 | 2521.84 | 21.05 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325206E+10 | 2504.37 | 31-JAN-07:53 | -30.0 |
February | 0.220295E+10 | 2507.86 | 01-FEB-07:53 | -32.2 |
March | 0.133330E+10 | 2304.72 | 01-MAR-16:11 | -3.9 |
April | 0.550625E+09 | 2289.05 | 03-APR-08:61 | -5.9 |
May | 51550248.61 | 2198.60 | 02-MAY-08:61 | 4.08 |
June | 19117488.30 | 1561.95 | 03-JUN-18:03 | 14.22 |
July | 582337.64 | 1065.97 | 18-JUL-08:13 | 19.47 |
August | 995447.77 | 1158.27 | 25-AUG-08:03 | 14.68 |
September | 0.130766E+09 | 2240.69 | 29-SEP-08:61 | 5.05 |
October | 0.582775E+09 | 2272.27 | 23-OCT-08:61 | 0.70 |
November | 0.162230E+10 | 2345.71 | 26-NOV-16:11 | -13.9 |
December | 0.276046E+10 | 2364.47 | 11-DEC-16:11 | -20.2 |
Annual Sum or Average | 0.125075E+11 | |||
Minimum of Months | 582337.64 | 1065.97 | -32.2 | |
Maximum of Months | 0.325206E+10 | 2507.86 | 19.47 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.993751E+09 | 1118.31 | 26-JAN-16:11 | -11.5 |
February | 0.580953E+09 | 1104.74 | 28-FEB-19:01 | -15.7 |
March | 0.357743E+09 | 1104.11 | 01-MAR-16:11 | -3.9 |
April | 0.169132E+09 | 1097.83 | 03-APR-08:61 | -5.9 |
May | 7393867.28 | 689.29 | 01-MAY-18:03 | 6.93 |
June | 1557557.37 | 593.02 | 03-JUN-08:03 | 8.68 |
July | 278890.59 | 445.58 | 24-JUL-08:03 | 19.18 |
August | 519888.48 | 379.09 | 16-AUG-08:03 | 17.07 |
September | 17650773.97 | 1030.87 | 29-SEP-08:61 | 5.05 |
October | 65791637.82 | 1052.29 | 26-OCT-08:61 | 1.28 |
November | 0.425425E+09 | 1114.97 | 26-NOV-16:11 | -13.9 |
December | 0.852321E+09 | 1126.22 | 09-DEC-16:11 | -19.1 |
Annual Sum or Average | 0.347252E+10 | |||
Minimum of Months | 278890.59 | 379.09 | -19.1 | |
Maximum of Months | 0.993751E+09 | 1126.22 | 19.18 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6531604.65 | 5746.18 | 31-JAN-11:42 | -23.1 |
February | 31961866.33 | 8068.56 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 38493470.99 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 31961866.33 | 8068.56 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1415632.19 | 4067.70 | 31-JAN-11:42 | -23.1 |
February | 4574003.91 | 5314.83 | 04-FEB-11:22 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 5989636.10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 4574003.91 | 5314.83 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362930E+10 | 5183.06 | 31-JAN-11:42 | -23.1 |
February | 0.170197E+10 | 6403.14 | 04-FEB-11:22 | -23.0 |
March | 0.514163E+09 | 4101.36 | 06-MAR-06:02 | -14.1 |
April | 11507729.40 | 982.46 | 03-APR-04:52 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.908046E+09 | 4758.77 | 26-NOV-09:02 | -22.7 |
December | 0.260368E+10 | 4616.22 | 12-DEC-06:02 | -19.9 |
Annual Sum or Average | 0.936868E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.362930E+10 | 6403.14 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.113897E+11 | 10970.58 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.102838E+11 | 10970.58 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.114292E+11 | 10970.58 | 01-MAR-20:10 | 0.121808E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.110035E+11 | 10970.58 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.114094E+11 | 10970.58 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.110540E+11 | 10970.58 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.113589E+11 | 10970.58 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.114292E+11 | 10970.58 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.110035E+11 | 10970.58 | 01-SEP-19:10 | 0.117446E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.113897E+11 | 10970.58 | 02-OCT-19:10 | 0.121516E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.110452E+11 | 10970.58 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.113589E+11 | 10970.58 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.134155E+12 | 0.143109E+12 | ||||
Minimum of Months | 0.102838E+11 | 10970.58 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.114292E+11 | 10970.58 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.566644E+09 | 545.79 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.511628E+09 | 545.79 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.568609E+09 | 545.79 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.547432E+09 | 545.79 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.567626E+09 | 545.79 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.549942E+09 | 545.79 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.565115E+09 | 545.79 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.568609E+09 | 545.79 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.547432E+09 | 545.79 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.566644E+09 | 545.79 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.549506E+09 | 545.79 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.565115E+09 | 545.79 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.667430E+10 | 0.101859E+11 | ||||
Minimum of Months | 0.511628E+09 | 545.79 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.568609E+09 | 545.79 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.656175E+09 | 632.03 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.592467E+09 | 632.03 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.658451E+09 | 632.03 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.633928E+09 | 632.03 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.657313E+09 | 632.03 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.636835E+09 | 632.03 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.654406E+09 | 632.03 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.658451E+09 | 632.03 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.633928E+09 | 632.03 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.656175E+09 | 632.03 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.636330E+09 | 632.03 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.654406E+09 | 632.03 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.772886E+10 | 0.117953E+11 | ||||
Minimum of Months | 0.592467E+09 | 632.03 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.658451E+09 | 632.03 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156929E+10 | 1511.55 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.141693E+10 | 1511.55 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.157474E+10 | 1511.55 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.151609E+10 | 1511.55 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.157202E+10 | 1511.55 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.152304E+10 | 1511.55 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.156506E+10 | 1511.55 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.157474E+10 | 1511.55 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.151609E+10 | 1511.55 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.156929E+10 | 1511.55 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.152183E+10 | 1511.55 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.156506E+10 | 1511.55 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | ||||
Minimum of Months | 0.141693E+10 | 1511.55 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.157474E+10 | 1511.55 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.161153E+09 | 155.22 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.145507E+09 | 155.22 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.161712E+09 | 155.22 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.155689E+09 | 155.22 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.161433E+09 | 155.22 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.156404E+09 | 155.22 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.160719E+09 | 155.22 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.161712E+09 | 155.22 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.155689E+09 | 155.22 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.161153E+09 | 155.22 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.156279E+09 | 155.22 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.160719E+09 | 155.22 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.189817E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.145507E+09 | 155.22 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.161712E+09 | 155.22 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417433E+09 | 400.68 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.401887E+09 | 400.68 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415991E+09 | 400.68 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489981E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.879220E+09 | 1097.76 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.759983E+09 | 1097.76 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.777699E+09 | 1097.76 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.687260E+09 | 1097.76 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.631773E+09 | 1097.76 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.590267E+09 | 1097.76 | 01-JUN-19:40 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.614237E+09 | 1097.76 | 03-JUL-19:00 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.666958E+09 | 1097.76 | 01-AUG-19:40 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.725561E+09 | 1097.76 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.821102E+09 | 1097.76 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.837426E+09 | 1097.76 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.893302E+09 | 1097.76 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.888479E+10 | 0.143409E+11 | ||||
Minimum of Months | 0.590267E+09 | 1097.76 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.893302E+09 | 1097.76 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.644482E+10 | 6463.27 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.578259E+10 | 6463.27 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.636346E+10 | 6463.27 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.606948E+10 | 6463.27 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.621384E+10 | 6463.27 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.599509E+10 | 6463.27 | 01-JUN-19:40 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.616597E+10 | 6463.27 | 03-JUL-19:00 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.625484E+10 | 6463.27 | 01-AUG-19:40 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.610203E+10 | 6463.27 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.638439E+10 | 6463.27 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.623415E+10 | 6463.27 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.644873E+10 | 6463.27 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.744594E+11 | 0.149002E+12 | ||||
Minimum of Months | 0.578259E+10 | 6463.27 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.644873E+10 | 6463.27 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117159E+09 | 137.77 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.105814E+09 | 137.77 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.116728E+09 | 137.77 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.113449E+09 | 137.77 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.116943E+09 | 137.77 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113018E+09 | 137.77 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.117374E+09 | 137.77 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.116728E+09 | 137.77 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.113449E+09 | 137.77 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.117159E+09 | 137.77 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113234E+09 | 137.77 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.117374E+09 | 137.77 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.137843E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.105814E+09 | 137.77 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.117374E+09 | 137.77 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117145E+09 | 137.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.105801E+09 | 137.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.116714E+09 | 137.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.113436E+09 | 137.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.116930E+09 | 137.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113005E+09 | 137.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.117360E+09 | 137.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.116714E+09 | 137.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.113436E+09 | 137.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.117145E+09 | 137.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113220E+09 | 137.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.117360E+09 | 137.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.137827E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.105801E+09 | 137.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.117360E+09 | 137.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 73629799.21 | 86.58 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 66499969.88 | 86.58 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 73359176.20 | 86.58 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 71298293.27 | 86.58 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 73494487.70 | 86.58 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 71027670.26 | 86.58 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 73765110.71 | 86.58 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 73359176.20 | 86.58 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 71298293.27 | 86.58 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 73629799.21 | 86.58 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 71162981.76 | 86.58 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 73765110.71 | 86.58 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.866290E+09 | 0.256575E+10 | ||||
Minimum of Months | 66499969.88 | 86.58 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 73765110.71 | 86.58 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 73649933.14 | 86.61 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 66518154.18 | 86.61 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 73379236.13 | 86.61 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 71317789.65 | 86.61 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 73514584.64 | 86.61 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 71047092.65 | 86.61 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 73785281.65 | 86.61 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 73379236.13 | 86.61 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 71317789.65 | 86.61 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 73649933.14 | 86.61 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 71182441.15 | 86.61 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 73785281.65 | 86.61 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.866527E+09 | 0.256645E+10 | ||||
Minimum of Months | 66518154.18 | 86.61 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 73785281.65 | 86.61 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117159E+09 | 137.77 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.105814E+09 | 137.77 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.116728E+09 | 137.77 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.113449E+09 | 137.77 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.116943E+09 | 137.77 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113018E+09 | 137.77 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.117374E+09 | 137.77 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.116728E+09 | 137.77 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.113449E+09 | 137.77 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.117159E+09 | 137.77 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113234E+09 | 137.77 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.117374E+09 | 137.77 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.137843E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.105814E+09 | 137.77 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.117374E+09 | 137.77 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117145E+09 | 137.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.105801E+09 | 137.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.116714E+09 | 137.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.113436E+09 | 137.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.116930E+09 | 137.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113005E+09 | 137.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.117360E+09 | 137.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.116714E+09 | 137.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.113436E+09 | 137.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.117145E+09 | 137.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113220E+09 | 137.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.117360E+09 | 137.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.137827E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.105801E+09 | 137.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.117360E+09 | 137.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.870792E+09 | 838.75 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.786245E+09 | 838.75 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.873811E+09 | 838.75 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.841268E+09 | 838.75 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.872301E+09 | 838.75 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.845126E+09 | 838.75 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.868443E+09 | 838.75 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.873811E+09 | 838.75 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.841268E+09 | 838.75 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.870792E+09 | 838.75 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.844455E+09 | 838.75 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.868443E+09 | 838.75 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102568E+11 | ||||
Minimum of Months | 0.786245E+09 | 838.75 | 0.00 | 0.00 | |
Maximum of Months | 0.873811E+09 | 838.75 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117159E+09 | 137.77 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.105814E+09 | 137.77 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.116728E+09 | 137.77 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.113449E+09 | 137.77 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.116943E+09 | 137.77 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113018E+09 | 137.77 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.117374E+09 | 137.77 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.116728E+09 | 137.77 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.113449E+09 | 137.77 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.117159E+09 | 137.77 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113234E+09 | 137.77 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.117374E+09 | 137.77 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.137843E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.105814E+09 | 137.77 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.117374E+09 | 137.77 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117145E+09 | 137.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.105801E+09 | 137.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.116714E+09 | 137.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.113436E+09 | 137.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.116930E+09 | 137.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113005E+09 | 137.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.117360E+09 | 137.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.116714E+09 | 137.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.113436E+09 | 137.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.117145E+09 | 137.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113220E+09 | 137.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.117360E+09 | 137.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.137827E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.105801E+09 | 137.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.117360E+09 | 137.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 73649933.14 | 86.61 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 66518154.18 | 86.61 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 73379236.13 | 86.61 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 71317789.65 | 86.61 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 73514584.64 | 86.61 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 71047092.65 | 86.61 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 73785281.65 | 86.61 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 73379236.13 | 86.61 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 71317789.65 | 86.61 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 73649933.14 | 86.61 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 71182441.15 | 86.61 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 73785281.65 | 86.61 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.866527E+09 | 0.256645E+10 | ||||
Minimum of Months | 66518154.18 | 86.61 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 73785281.65 | 86.61 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.179194E+10 | 1927.76 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.158684E+10 | 1927.76 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.169260E+10 | 1927.76 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.156613E+10 | 1927.76 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.153874E+10 | 1927.76 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.146514E+10 | 1927.76 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.151697E+10 | 1927.76 | 03-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.157675E+10 | 1927.76 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.160439E+10 | 1927.76 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.173487E+10 | 1927.76 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.172333E+10 | 1927.76 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.181457E+10 | 1927.76 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.196123E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.146514E+10 | 1927.76 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.181457E+10 | 1927.76 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.179194E+10 | 1927.76 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.158684E+10 | 1927.76 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.169260E+10 | 1927.76 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.156613E+10 | 1927.76 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.153874E+10 | 1927.76 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.146514E+10 | 1927.76 | 01-JUN-19:40 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.151697E+10 | 1927.76 | 03-JUL-19:00 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.157675E+10 | 1927.76 | 01-AUG-19:40 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.160439E+10 | 1927.76 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.173487E+10 | 1927.76 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.172333E+10 | 1927.76 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.181457E+10 | 1927.76 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.196123E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.146514E+10 | 1927.76 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.181457E+10 | 1927.76 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113643E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109411E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113447E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109411E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113250E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133394E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.921598E+09 | 887.69 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.832119E+09 | 887.69 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.924794E+09 | 887.69 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.890352E+09 | 887.69 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.923196E+09 | 887.69 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.894435E+09 | 887.69 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.919113E+09 | 887.69 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.924794E+09 | 887.69 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.890352E+09 | 887.69 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.921598E+09 | 887.69 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.893725E+09 | 887.69 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.919113E+09 | 887.69 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.108552E+11 | ||||
Minimum of Months | 0.832119E+09 | 887.69 | 0.00 | 0.00 | |
Maximum of Months | 0.924794E+09 | 887.69 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.113897E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.102838E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.114292E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.110035E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.114094E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.110540E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.113589E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.114292E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.110035E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.113897E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.110452E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.113589E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.134155E+12 | 0.143109E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.102838E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.114292E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.566644E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223718E+10 |
February | 0.179968E+10 | 0.511628E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170310E+10 |
March | 0.199896E+10 | 0.568609E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140368E+10 |
April | 0.192973E+10 | 0.547432E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4064099.40 | 0.974036E+09 |
May | 0.199475E+10 | 0.567626E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5306591.57 | 0.600084E+09 |
June | 0.193394E+10 | 0.549942E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36262804.88 | 0.329169E+09 |
July | 0.199054E+10 | 0.565115E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25370797.22 | 0.224498E+09 |
August | 0.199896E+10 | 0.568609E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24018859.45 | 0.281167E+09 |
September | 0.192973E+10 | 0.547432E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11474345.20 | 0.534914E+09 |
October | 0.199054E+10 | 0.566644E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100936E+10 |
November | 0.192552E+10 | 0.549506E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138843E+10 |
December | 0.199054E+10 | 0.565115E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191209E+10 |
Annual Sum or Average | 0.234734E+11 | 0.667430E+10 | 0.101859E+11 | 0.106497E+09 | 0.125977E+11 | ||||
Minimum of Months | 0.179968E+10 | 0.511628E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224498E+09 |
Maximum of Months | 0.199896E+10 | 0.568609E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36262804.88 | 0.223718E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.656175E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496359E+09 |
February | 0.208403E+10 | 0.592467E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381073E+09 |
March | 0.231480E+10 | 0.658451E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318169E+09 |
April | 0.223463E+10 | 0.633928E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1300303.96 | 0.223127E+09 |
May | 0.230993E+10 | 0.657313E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1238454.04 | 0.134191E+09 |
June | 0.223950E+10 | 0.636835E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8321572.63 | 74908533.36 |
July | 0.230505E+10 | 0.654406E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6157375.32 | 51656435.85 |
August | 0.231480E+10 | 0.658451E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6396530.70 | 64079463.83 |
September | 0.223463E+10 | 0.633928E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4374888.42 | 0.120317E+09 |
October | 0.230505E+10 | 0.656175E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225188E+09 |
November | 0.222975E+10 | 0.636330E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314555E+09 |
December | 0.230505E+10 | 0.654406E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430076E+09 |
Annual Sum or Average | 0.271823E+11 | 0.772886E+10 | 0.117953E+11 | 27789125.06 | 0.283370E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.592467E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51656435.85 |
Maximum of Months | 0.231480E+10 | 0.658451E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8321572.63 | 0.496359E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169738E+10 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132504E+10 |
March | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109322E+10 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 3132219.32 | 0.777676E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 2782901.30 | 0.489440E+09 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 19447441.16 | 0.289809E+09 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 13562499.62 | 0.214467E+09 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 15358528.95 | 0.256074E+09 |
September | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 11951393.27 | 0.439130E+09 |
October | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787068E+09 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108031E+10 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146311E+10 |
Annual Sum or Average | 0.182082E+11 | 0.489981E+10 | 0.679373E+11 | 0.590211E+12 | 66234983.61 | 0.991272E+10 | |||
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214467E+09 |
Maximum of Months | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 19447441.16 | 0.169738E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.879220E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585409E+10 |
February | 0.236489E+11 | 0.759983E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451288E+10 |
March | 0.262677E+11 | 0.777699E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375320E+10 |
April | 0.253579E+11 | 0.687260E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11522913.40 | 0.262174E+10 |
May | 0.262123E+11 | 0.631773E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13931357.85 | 0.157986E+10 |
June | 0.254132E+11 | 0.590267E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94908814.19 | 0.880091E+09 |
July | 0.261570E+11 | 0.614237E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68172700.24 | 0.603497E+09 |
August | 0.262677E+11 | 0.666958E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66306616.73 | 0.758487E+09 |
September | 0.253579E+11 | 0.725561E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34391937.86 | 0.143306E+10 |
October | 0.261570E+11 | 0.821102E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270612E+10 |
November | 0.253025E+11 | 0.837426E+09 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370165E+10 |
December | 0.261570E+11 | 0.893302E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507029E+10 |
Annual Sum or Average | 0.308456E+12 | 0.888479E+10 | 0.143409E+11 | 0.289234E+09 | 0.334750E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.590267E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603497E+09 |
Maximum of Months | 0.262677E+11 | 0.893302E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94908814.19 | 0.585409E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.644482E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121329E+11 |
February | 0.702046E+11 | 0.578259E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930522E+10 |
March | 0.779788E+11 | 0.636346E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776165E+10 |
April | 0.752779E+11 | 0.606948E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30186743.69 | 0.544473E+10 |
May | 0.778146E+11 | 0.621384E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29188612.87 | 0.329227E+10 |
June | 0.754422E+11 | 0.599509E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197502E+09 | 0.185137E+10 |
July | 0.776503E+11 | 0.616597E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145052E+09 | 0.128242E+10 |
August | 0.779788E+11 | 0.625484E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150510E+09 | 0.158788E+10 |
September | 0.752779E+11 | 0.610203E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100329E+09 | 0.295697E+10 |
October | 0.776503E+11 | 0.638439E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552476E+10 |
November | 0.751137E+11 | 0.623415E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768240E+10 |
December | 0.776503E+11 | 0.644873E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104932E+11 |
Annual Sum or Average | 0.915690E+12 | 0.744594E+11 | 0.149002E+12 | 0.652767E+09 | 0.693157E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.578259E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128242E+10 |
Maximum of Months | 0.779788E+11 | 0.644873E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197502E+09 | 0.121329E+11 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662364E+09 |
February | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504811E+09 |
March | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391958E+09 |
April | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3047633.43 | 0.261995E+09 |
May | 0.303504E+09 | 0.116943E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3316882.99 | 0.138979E+09 |
June | 0.293842E+09 | 0.113018E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21069457.14 | 67041609.66 |
July | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19581918.24 | 36318006.59 |
August | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18164383.76 | 50412582.56 |
September | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11194202.47 | 0.122374E+09 |
October | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13958.70 | 0.258401E+09 |
November | 0.293661E+09 | 0.113234E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387940E+09 |
December | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553719E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137843E+10 | 0.261953E+10 | 76388436.73 | 0.343631E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36318006.59 |
Maximum of Months | 0.303685E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21069457.14 | 0.662364E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660665E+09 |
February | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501206E+09 |
March | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388256E+09 |
April | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2536011.92 | 0.261144E+09 |
May | 0.303504E+09 | 0.116930E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2536021.81 | 0.143380E+09 |
June | 0.293842E+09 | 0.113005E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18227519.55 | 74414445.60 |
July | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14325498.19 | 48071240.34 |
August | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14197906.58 | 60413025.29 |
September | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9620416.88 | 0.125569E+09 |
October | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8734.09 | 0.253999E+09 |
November | 0.293661E+09 | 0.113220E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384985E+09 |
December | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551127E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137827E+10 | 0.261922E+10 | 61452109.02 | 0.345323E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48071240.34 |
Maximum of Months | 0.303685E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18227519.55 | 0.660665E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 73629799.21 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162894E+09 |
February | 0.00 | 66499969.88 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132693E+09 |
March | 0.00 | 73359176.20 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109422E+09 |
April | 0.00 | 71298293.27 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 171436.97 | 88227249.08 |
May | 0.00 | 73494487.70 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 131939.92 | 62411895.04 |
June | 0.00 | 71027670.26 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1444845.12 | 37810200.73 |
July | 0.00 | 73765110.71 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 543420.30 | 29294138.34 |
August | 0.00 | 73359176.20 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 768484.33 | 33978610.21 |
September | 0.00 | 71298293.27 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 704377.67 | 55482206.22 |
October | 0.00 | 73629799.21 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97181430.76 |
November | 0.00 | 71162981.76 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117298E+09 |
December | 0.00 | 73765110.71 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137914E+09 |
Annual Sum or Average | 0.00 | 0.866290E+09 | 0.256575E+10 | 3764504.31 | 0.106461E+10 | ||||
Minimum of Months | 0.00 | 66499969.88 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29294138.34 |
Maximum of Months | 0.00 | 73765110.71 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1444845.12 | 0.162894E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185034E+09 |
February | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140786E+09 |
March | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109784E+09 |
April | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 762360.12 | 73364833.91 |
May | 0.303504E+09 | 73514584.64 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 795897.74 | 39235649.49 |
June | 0.293842E+09 | 71047092.65 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5280772.60 | 19747062.93 |
July | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4402778.47 | 11584592.13 |
August | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4338929.26 | 15331433.91 |
September | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2908878.85 | 34614017.37 |
October | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13563.85 | 71816685.16 |
November | 0.293661E+09 | 71182441.15 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108916E+09 |
December | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155012E+09 |
Annual Sum or Average | 0.357224E+10 | 0.866527E+09 | 0.256645E+10 | 18503180.88 | 0.965226E+09 | ||||
Minimum of Months | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11584592.13 |
Maximum of Months | 0.303685E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5280772.60 | 0.185034E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661890E+09 |
February | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504037E+09 |
March | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393236E+09 |
April | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3042071.31 | 0.262564E+09 |
May | 0.303504E+09 | 0.116943E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3303577.57 | 0.140870E+09 |
June | 0.293842E+09 | 0.113018E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21044868.00 | 67751165.55 |
July | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19564078.86 | 36745239.70 |
August | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18138287.92 | 50953014.13 |
September | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11188805.09 | 0.123432E+09 |
October | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14436.07 | 0.259301E+09 |
November | 0.293661E+09 | 0.113234E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387835E+09 |
December | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553380E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137843E+10 | 0.261953E+10 | 76296124.82 | 0.344199E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36745239.70 |
Maximum of Months | 0.303685E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21044868.00 | 0.661890E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660197E+09 |
February | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500182E+09 |
March | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389192E+09 |
April | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2589186.58 | 0.261216E+09 |
May | 0.303504E+09 | 0.116930E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2624120.25 | 0.143477E+09 |
June | 0.293842E+09 | 0.113005E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18326243.79 | 73445216.53 |
July | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14727487.89 | 45372301.54 |
August | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14544074.15 | 57653297.79 |
September | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9797173.77 | 0.125360E+09 |
October | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3464.53 | 0.254345E+09 |
November | 0.293661E+09 | 0.113220E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384802E+09 |
December | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551036E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137827E+10 | 0.261922E+10 | 62611750.95 | 0.344628E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45372301.54 |
Maximum of Months | 0.303685E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18326243.79 | 0.660197E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663170E+09 |
February | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505797E+09 |
March | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391453E+09 |
April | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2994320.51 | 0.262275E+09 |
May | 0.303504E+09 | 0.116943E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3235334.99 | 0.140420E+09 |
June | 0.293842E+09 | 0.113018E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20723595.86 | 67813829.66 |
July | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19139252.29 | 36916477.17 |
August | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17789870.09 | 51014223.60 |
September | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10994857.34 | 0.122777E+09 |
October | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12584.57 | 0.258283E+09 |
November | 0.293661E+09 | 0.113234E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387704E+09 |
December | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554006E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137843E+10 | 0.261953E+10 | 74889815.65 | 0.344163E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36916477.17 |
Maximum of Months | 0.303685E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20723595.86 | 0.663170E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661745E+09 |
February | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502338E+09 |
March | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388184E+09 |
April | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2456305.92 | 0.261808E+09 |
May | 0.303504E+09 | 0.116930E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2452980.12 | 0.146619E+09 |
June | 0.293842E+09 | 0.113005E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17886656.16 | 77211428.63 |
July | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13925230.44 | 51742253.82 |
August | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13818378.13 | 63629185.29 |
September | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9409823.55 | 0.126978E+09 |
October | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7339.58 | 0.253526E+09 |
November | 0.293661E+09 | 0.113220E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385054E+09 |
December | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552123E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137827E+10 | 0.261922E+10 | 59956713.89 | 0.347096E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51742253.82 |
Maximum of Months | 0.303685E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17886656.16 | 0.661745E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343623E+09 |
February | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263012E+09 |
March | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204002E+09 |
April | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1527375.96 | 0.135448E+09 |
May | 0.303504E+09 | 73514584.64 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1656695.11 | 72232346.54 |
June | 0.293842E+09 | 71047092.65 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10612876.72 | 34848123.33 |
July | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9805262.34 | 18815103.14 |
August | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9097846.07 | 26092372.33 |
September | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5610048.66 | 63619035.40 |
October | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1730.46 | 0.134886E+09 |
November | 0.293661E+09 | 71182441.15 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202056E+09 |
December | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287584E+09 |
Annual Sum or Average | 0.357224E+10 | 0.866527E+09 | 0.256645E+10 | 38311835.33 | 0.178622E+10 | ||||
Minimum of Months | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18815103.14 |
Maximum of Months | 0.303685E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10612876.72 | 0.343623E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.179194E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176889E+10 |
February | 0.415303E+11 | 0.158684E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135335E+10 |
March | 0.461292E+11 | 0.169260E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116121E+10 |
April | 0.445315E+11 | 0.156613E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3177106.27 | 0.832256E+09 |
May | 0.460320E+11 | 0.153874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2580209.20 | 0.523064E+09 |
June | 0.446286E+11 | 0.146514E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18612206.34 | 0.306436E+09 |
July | 0.459349E+11 | 0.151697E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10650007.35 | 0.221134E+09 |
August | 0.461292E+11 | 0.157675E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13322076.08 | 0.263917E+09 |
September | 0.445315E+11 | 0.160439E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10967776.86 | 0.463728E+09 |
October | 0.459349E+11 | 0.173487E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838092E+09 |
November | 0.444343E+11 | 0.172333E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114243E+10 |
December | 0.459349E+11 | 0.181457E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154839E+10 |
Annual Sum or Average | 0.541686E+12 | 0.196123E+11 | 0.175857E+12 | 59309382.11 | 0.104229E+11 | ||||
Minimum of Months | 0.415303E+11 | 0.146514E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221134E+09 |
Maximum of Months | 0.461292E+11 | 0.181457E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18612206.34 | 0.176889E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.179194E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179999E+10 |
February | 0.415303E+11 | 0.158684E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138326E+10 |
March | 0.461292E+11 | 0.169260E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118787E+10 |
April | 0.445315E+11 | 0.156613E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2657160.26 | 0.854878E+09 |
May | 0.460320E+11 | 0.153874E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2063979.34 | 0.541624E+09 |
June | 0.446286E+11 | 0.146514E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15982673.68 | 0.320079E+09 |
July | 0.459349E+11 | 0.151697E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8123390.13 | 0.233285E+09 |
August | 0.461292E+11 | 0.157675E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10667955.24 | 0.276544E+09 |
September | 0.445315E+11 | 0.160439E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9275013.23 | 0.479255E+09 |
October | 0.459349E+11 | 0.173487E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861099E+09 |
November | 0.444343E+11 | 0.172333E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116834E+10 |
December | 0.459349E+11 | 0.181457E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157673E+10 |
Annual Sum or Average | 0.541686E+12 | 0.196123E+11 | 0.175857E+12 | 48770171.89 | 0.106830E+11 | ||||
Minimum of Months | 0.415303E+11 | 0.146514E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233285E+09 |
Maximum of Months | 0.461292E+11 | 0.181457E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15982673.68 | 0.179999E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177964E+10 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140604E+10 |
March | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121178E+10 |
April | 0.396281E+10 | 0.109411E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 94.13 | 0.898270E+09 |
May | 0.409635E+10 | 0.113447E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611235E+09 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 610429.86 | 0.391380E+09 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 9230.14 | 0.320285E+09 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 378672.47 | 0.358754E+09 |
September | 0.396281E+10 | 0.109411E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 305728.07 | 0.547655E+09 |
October | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913900E+09 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119073E+10 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156681E+10 |
Annual Sum or Average | 0.482041E+11 | 0.133394E+11 | 0.382987E+12 | 0.359593E+12 | 1304154.67 | 0.111965E+11 | |||
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320285E+09 |
Maximum of Months | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 610429.86 | 0.177964E+10 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107826E+10 |
February | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826957E+09 |
March | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694414E+09 |
April | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3020171.81 | 0.486305E+09 |
May | 0.00 | 0.157202E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2838201.63 | 0.286184E+09 |
June | 0.00 | 0.152304E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19179170.55 | 0.157296E+09 |
July | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14605731.02 | 0.106405E+09 |
August | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14932794.13 | 0.132163E+09 |
September | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10896137.28 | 0.254490E+09 |
October | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485377E+09 |
November | 0.00 | 0.152183E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687190E+09 |
December | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935602E+09 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | 65472206.43 | 0.613064E+10 | |||||
Minimum of Months | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106405E+09 |
Maximum of Months | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19179170.55 | 0.107826E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.161153E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724091E+09 |
February | 0.00 | 0.145507E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539245E+09 |
March | 0.00 | 0.161712E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445690E+09 |
April | 0.00 | 0.155689E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2433764.27 | 0.310615E+09 |
May | 0.00 | 0.161433E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2406408.18 | 0.183677E+09 |
June | 0.00 | 0.156404E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14111389.55 | 0.101447E+09 |
July | 0.00 | 0.160719E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11122642.25 | 67700796.54 |
August | 0.00 | 0.161712E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11345564.91 | 85186404.91 |
September | 0.00 | 0.155689E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7938363.32 | 0.165831E+09 |
October | 0.00 | 0.161153E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 787.80 | 0.315422E+09 |
November | 0.00 | 0.156279E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447516E+09 |
December | 0.00 | 0.160719E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615139E+09 |
Annual Sum or Average | 0.189817E+10 | 0.359769E+10 | 49358920.28 | 0.400156E+10 | |||||
Minimum of Months | 0.00 | 0.145507E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67700796.54 |
Maximum of Months | 0.00 | 0.161712E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14111389.55 | 0.724091E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.870792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777383E+09 |
February | 0.00 | 0.786245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583822E+09 |
March | 0.00 | 0.873811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473061E+09 |
April | 0.00 | 0.841268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4181736.48 | 0.315477E+09 |
May | 0.00 | 0.872301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5104017.77 | 0.162387E+09 |
June | 0.00 | 0.845126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23938483.54 | 84885342.12 |
July | 0.00 | 0.868443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20539631.97 | 53965651.38 |
August | 0.00 | 0.873811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20455973.17 | 71142191.21 |
September | 0.00 | 0.841268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12783661.39 | 0.152968E+09 |
October | 0.00 | 0.870792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75682.11 | 0.307387E+09 |
November | 0.00 | 0.844455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467084E+09 |
December | 0.00 | 0.868443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658343E+09 |
Annual Sum or Average | 0.102568E+11 | 87079186.43 | 0.410790E+10 | ||||||
Minimum of Months | 0.00 | 0.786245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53965651.38 |
Maximum of Months | 0.00 | 0.873811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23938483.54 | 0.777383E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.921598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140752E+10 |
February | 0.00 | 0.832119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104776E+10 |
March | 0.00 | 0.924794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886093E+09 |
April | 0.00 | 0.890352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3294785.81 | 0.633122E+09 |
May | 0.00 | 0.923196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2882840.71 | 0.389376E+09 |
June | 0.00 | 0.894435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19432786.64 | 0.217601E+09 |
July | 0.00 | 0.919113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11948414.10 | 0.150090E+09 |
August | 0.00 | 0.924794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13991331.79 | 0.182783E+09 |
September | 0.00 | 0.890352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10479550.26 | 0.344595E+09 |
October | 0.00 | 0.921598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643344E+09 |
November | 0.00 | 0.893725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877944E+09 |
December | 0.00 | 0.919113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120001E+10 |
Annual Sum or Average | 0.108552E+11 | 62029709.30 | 0.798024E+10 | ||||||
Minimum of Months | 0.00 | 0.832119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150090E+09 |
Maximum of Months | 0.00 | 0.924794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19432786.64 | 0.140752E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 10970.58 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 10970.58 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 10970.58 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 10970.58 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 10970.58 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 10970.58 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 10970.58 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 10970.58 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 10970.58 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 10970.58 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 10970.58 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 10970.58 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 10970.58 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 10970.58 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 545.79 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1246.99 | 30-JAN-11:50 |
February | 1169.53 | 01-FEB-00:10 | 545.79 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1343.84 | 02-FEB-05:52 |
March | 1169.53 | 01-MAR-00:10 | 545.79 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 985.17 | 06-MAR-00:54 |
April | 1169.53 | 01-APR-00:10 | 545.79 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.36 | 15-APR-17:00 | 702.28 | 03-APR-05:56 |
May | 1169.53 | 01-MAY-00:10 | 545.79 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.55 | 31-MAY-12:53 | 523.73 | 03-MAY-02:51 |
June | 1169.53 | 01-JUN-00:10 | 545.79 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.58 | 11-JUN-14:53 | 438.96 | 01-JUN-04:51 |
July | 1169.53 | 01-JUL-00:10 | 545.79 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.16 | 26-JUL-14:52 | 323.59 | 24-JUL-02:51 |
August | 1169.53 | 01-AUG-00:10 | 545.79 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.45 | 04-AUG-16:00 | 358.98 | 07-AUG-05:59 |
September | 1169.53 | 01-SEP-00:10 | 545.79 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.25 | 06-SEP-15:00 | 551.66 | 30-SEP-00:51 |
October | 1169.53 | 02-OCT-00:10 | 545.79 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 613.83 | 31-OCT-20:53 |
November | 1169.53 | 01-NOV-00:10 | 545.79 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1193.05 | 26-NOV-06:51 |
December | 1169.53 | 01-DEC-00:10 | 545.79 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1135.00 | 08-DEC-20:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 545.79 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.59 | |||||
Maximum of Months | 1169.53 | 545.79 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 176.58 | 1343.84 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 632.03 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 279.56 | 31-JAN-03:51 |
February | 1354.32 | 01-FEB-00:10 | 632.03 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 309.00 | 02-FEB-05:51 |
March | 1354.32 | 01-MAR-00:10 | 632.03 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 220.27 | 06-MAR-00:51 |
April | 1354.32 | 01-APR-00:10 | 632.03 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 | 15-APR-16:00 | 160.84 | 03-APR-05:59 |
May | 1354.32 | 01-MAY-00:10 | 632.03 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.13 | 31-MAY-12:51 | 120.83 | 03-MAY-02:51 |
June | 1354.32 | 01-JUN-00:10 | 632.03 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 | 11-JUN-14:51 | 98.30 | 01-JUN-04:53 |
July | 1354.32 | 01-JUL-00:10 | 632.03 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.05 | 26-JUL-14:52 | 72.94 | 24-JUL-04:59 |
August | 1354.32 | 01-AUG-00:10 | 632.03 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.99 | 04-AUG-14:52 | 81.74 | 07-AUG-05:59 |
September | 1354.32 | 01-SEP-00:10 | 632.03 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.98 | 06-SEP-13:52 | 129.46 | 30-SEP-00:51 |
October | 1354.32 | 02-OCT-00:10 | 632.03 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 141.57 | 23-OCT-05:51 |
November | 1354.32 | 01-NOV-00:10 | 632.03 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 274.23 | 26-NOV-06:51 |
December | 1354.32 | 01-DEC-00:10 | 632.03 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 256.63 | 08-DEC-20:59 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 632.03 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.94 | |||||
Maximum of Months | 1354.32 | 632.03 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 41.99 | 309.00 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 981.96 | 05-JAN-20:51 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1123.69 | 02-FEB-07:01 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 794.34 | 05-MAR-20:53 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 80.00 | 15-APR-15:54 | 643.83 | 03-APR-20:51 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 81.67 | 31-MAY-12:51 | 480.88 | 01-MAY-20:51 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 126.24 | 11-JUN-14:51 | 367.25 | 01-JUN-19:53 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 81.12 | 26-JUL-14:54 | 261.30 | 11-JUL-20:01 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 132.41 | 04-AUG-14:54 | 303.82 | 06-AUG-20:53 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 111.12 | 06-SEP-14:54 | 488.45 | 29-SEP-20:51 |
October | 907.20 | 02-OCT-00:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 560.57 | 31-OCT-20:51 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 934.20 | 25-NOV-20:51 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 960.01 | 08-DEC-20:53 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 261.30 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 132.41 | 1123.69 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1097.76 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3263.85 | 31-JAN-03:51 |
February | 15368.40 | 01-FEB-00:10 | 1097.76 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3585.67 | 02-FEB-05:51 |
March | 15368.40 | 01-MAR-00:10 | 1097.76 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2592.33 | 06-MAR-00:51 |
April | 15368.40 | 01-APR-00:10 | 1097.76 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.28 | 15-APR-16:00 | 1897.53 | 03-APR-04:51 |
May | 15368.40 | 01-MAY-00:10 | 1097.76 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.74 | 31-MAY-12:53 | 1446.95 | 03-MAY-02:51 |
June | 15368.40 | 01-JUN-00:10 | 1097.76 | 01-JUN-19:40 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.43 | 11-JUN-14:53 | 1184.05 | 01-JUN-04:53 |
July | 15368.40 | 01-JUL-00:10 | 1097.76 | 03-JUL-19:00 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.67 | 26-JUL-14:52 | 887.19 | 24-JUL-04:59 |
August | 15368.40 | 01-AUG-00:10 | 1097.76 | 01-AUG-19:40 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.26 | 04-AUG-15:00 | 980.97 | 07-AUG-03:51 |
September | 15368.40 | 01-SEP-00:10 | 1097.76 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.77 | 06-SEP-15:00 | 1545.50 | 30-SEP-00:51 |
October | 15368.40 | 02-OCT-00:10 | 1097.76 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 1667.52 | 23-OCT-05:51 |
November | 15368.40 | 01-NOV-00:10 | 1097.76 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 3096.55 | 26-NOV-06:51 |
December | 15368.40 | 01-DEC-00:10 | 1097.76 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2947.90 | 08-DEC-23:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 1097.76 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.19 | |||||
Maximum of Months | 15368.40 | 1097.76 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 481.43 | 3585.67 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 6463.27 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6855.51 | 31-JAN-03:51 |
February | 45622.98 | 01-FEB-00:10 | 6463.27 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 7577.60 | 02-FEB-05:51 |
March | 45622.98 | 01-MAR-00:10 | 6463.27 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 5353.32 | 06-MAR-00:53 |
April | 45622.98 | 01-APR-00:10 | 6463.27 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 624.36 | 15-APR-16:00 | 3915.87 | 03-APR-05:51 |
May | 45622.98 | 01-MAY-00:10 | 6463.27 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 650.59 | 31-MAY-12:51 | 2978.68 | 03-MAY-02:51 |
June | 45622.98 | 01-JUN-00:10 | 6463.27 | 01-JUN-19:40 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 995.13 | 11-JUN-14:51 | 2418.95 | 01-JUN-04:59 |
July | 45622.98 | 01-JUL-00:10 | 6463.27 | 03-JUL-19:00 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 644.88 | 26-JUL-14:52 | 1815.24 | 24-JUL-04:59 |
August | 45622.98 | 01-AUG-00:10 | 6463.27 | 01-AUG-19:40 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.83 | 04-AUG-15:00 | 2010.06 | 07-AUG-03:51 |
September | 45622.98 | 01-SEP-00:10 | 6463.27 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 821.10 | 06-SEP-14:00 | 3193.58 | 30-SEP-00:51 |
October | 45622.98 | 02-OCT-00:10 | 6463.27 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 3458.74 | 23-OCT-05:51 |
November | 45622.98 | 01-NOV-00:10 | 6463.27 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 6641.14 | 26-NOV-06:51 |
December | 45622.98 | 01-DEC-00:10 | 6463.27 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 6189.73 | 08-DEC-20:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 6463.27 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1815.24 | |||||
Maximum of Months | 45622.98 | 6463.27 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.83 | 7577.60 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.77 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 411.52 | 31-JAN-03:51 |
February | 180.00 | 01-FEB-00:10 | 137.77 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 460.73 | 02-FEB-07:56 |
March | 180.00 | 01-MAR-00:10 | 137.77 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 290.80 | 06-MAR-00:52 |
April | 180.00 | 01-APR-00:10 | 137.77 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 15-APR-15:20 | 207.59 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.77 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.49 | 31-MAY-15:18 | 146.71 | 03-MAY-02:51 |
June | 180.00 | 01-JUN-00:10 | 137.77 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.87 | 11-JUN-15:19 | 111.81 | 03-JUN-03:53 |
July | 180.00 | 01-JUL-00:10 | 137.77 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:18 | 76.51 | 23-JUL-03:52 |
August | 180.00 | 01-AUG-00:10 | 137.77 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 04-AUG-15:20 | 88.58 | 07-AUG-05:52 |
September | 180.00 | 01-SEP-00:10 | 137.77 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.80 | 06-SEP-15:20 | 158.99 | 30-SEP-00:54 |
October | 180.00 | 01-OCT-00:10 | 137.77 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 20-OCT-15:20 | 177.38 | 23-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.77 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 395.19 | 26-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.77 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 341.74 | 10-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | |||||
Maximum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 460.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 407.46 | 31-JAN-03:51 |
February | 180.00 | 01-FEB-00:10 | 137.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 460.70 | 02-FEB-07:57 |
March | 180.00 | 01-MAR-00:10 | 137.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 290.78 | 06-MAR-00:52 |
April | 180.00 | 01-APR-00:10 | 137.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 | 15-APR-15:19 | 207.57 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.49 | 31-MAY-15:20 | 146.70 | 03-MAY-02:51 |
June | 180.00 | 01-JUN-00:10 | 137.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.86 | 11-JUN-15:19 | 111.80 | 03-JUN-03:53 |
July | 180.00 | 01-JUL-00:10 | 137.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:17 | 76.50 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 137.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 04-AUG-15:20 | 88.58 | 07-AUG-05:51 |
September | 180.00 | 01-SEP-00:10 | 137.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.80 | 06-SEP-15:20 | 158.98 | 30-SEP-00:54 |
October | 180.00 | 01-OCT-00:10 | 137.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 20-OCT-13:01 | 177.37 | 23-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 393.80 | 26-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 341.71 | 10-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | |||||
Maximum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 460.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 86.58 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 104.56 | 31-JAN-03:51 |
February | 0.00 | 01-FEB-00:10 | 86.58 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 120.85 | 02-FEB-06:01 |
March | 0.00 | 01-MAR-00:10 | 86.58 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 69.95 | 06-MAR-00:51 |
April | 0.00 | 01-APR-00:10 | 86.58 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 15-APR-14:51 | 61.47 | 01-APR-04:51 |
May | 0.00 | 01-MAY-00:10 | 86.58 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 31-MAY-13:00 | 47.68 | 03-MAY-02:51 |
June | 0.00 | 01-JUN-00:10 | 86.58 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 11-JUN-14:51 | 41.23 | 01-JUN-04:51 |
July | 0.00 | 01-JUL-00:10 | 86.58 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 26-JUL-14:51 | 31.73 | 24-JUL-02:51 |
August | 0.00 | 01-AUG-00:10 | 86.58 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 04-AUG-14:51 | 35.40 | 07-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 86.58 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 | 07-SEP-13:51 | 51.31 | 30-SEP-00:51 |
October | 0.00 | 01-OCT-00:10 | 86.58 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 57.48 | 23-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 86.58 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 99.54 | 26-NOV-06:51 |
December | 0.00 | 01-DEC-00:10 | 86.58 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 90.76 | 08-DEC-20:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 86.58 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.73 | |||||
Maximum of Months | 0.00 | 86.58 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 120.85 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 86.61 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 112.48 | 31-JAN-03:51 |
February | 180.00 | 01-FEB-00:10 | 86.61 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 128.58 | 02-FEB-07:57 |
March | 180.00 | 01-MAR-00:10 | 86.61 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 81.16 | 06-MAR-00:51 |
April | 180.00 | 01-APR-00:10 | 86.61 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 15-APR-15:20 | 57.94 | 03-APR-05:54 |
May | 180.00 | 01-MAY-00:10 | 86.61 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 31-MAY-15:19 | 40.95 | 03-MAY-02:52 |
June | 180.00 | 01-JUN-00:10 | 86.61 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 11-JUN-15:19 | 31.20 | 03-JUN-03:53 |
July | 180.00 | 01-JUL-00:10 | 86.61 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | 26-JUL-15:20 | 21.35 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 86.61 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 04-AUG-15:20 | 24.72 | 07-AUG-05:51 |
September | 180.00 | 01-SEP-00:10 | 86.61 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.92 | 06-SEP-15:18 | 44.37 | 30-SEP-00:51 |
October | 180.00 | 01-OCT-00:10 | 86.61 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 20-OCT-14:51 | 49.50 | 23-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 86.61 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 108.61 | 26-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 86.61 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 95.37 | 10-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 | |||||
Maximum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 128.58 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.77 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 407.58 | 31-JAN-03:51 |
February | 180.00 | 01-FEB-00:10 | 137.77 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 460.73 | 02-FEB-07:56 |
March | 180.00 | 01-MAR-00:10 | 137.77 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 290.80 | 06-MAR-00:54 |
April | 180.00 | 01-APR-00:10 | 137.77 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 15-APR-15:19 | 207.59 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.77 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.49 | 31-MAY-15:16 | 146.71 | 03-MAY-02:51 |
June | 180.00 | 01-JUN-00:10 | 137.77 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.87 | 11-JUN-15:16 | 111.81 | 03-JUN-03:54 |
July | 180.00 | 01-JUL-00:10 | 137.77 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:16 | 76.51 | 23-JUL-03:52 |
August | 180.00 | 01-AUG-00:10 | 137.77 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 04-AUG-15:16 | 88.58 | 07-AUG-05:51 |
September | 180.00 | 01-SEP-00:10 | 137.77 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.80 | 06-SEP-15:17 | 158.99 | 30-SEP-00:54 |
October | 180.00 | 01-OCT-00:10 | 137.77 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 20-OCT-15:20 | 177.38 | 23-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.77 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 393.36 | 26-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.77 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 341.74 | 10-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | |||||
Maximum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 460.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 403.34 | 31-JAN-03:51 |
February | 180.00 | 01-FEB-00:10 | 137.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 460.70 | 02-FEB-07:59 |
March | 180.00 | 01-MAR-00:10 | 137.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 290.78 | 06-MAR-00:54 |
April | 180.00 | 01-APR-00:10 | 137.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 | 15-APR-15:16 | 207.57 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.49 | 31-MAY-15:16 | 146.70 | 03-MAY-02:51 |
June | 180.00 | 01-JUN-00:10 | 137.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.86 | 11-JUN-15:16 | 111.80 | 03-JUN-03:54 |
July | 180.00 | 01-JUL-00:10 | 137.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:20 | 76.50 | 23-JUL-03:55 |
August | 180.00 | 01-AUG-00:10 | 137.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 04-AUG-15:16 | 88.58 | 07-AUG-05:51 |
September | 180.00 | 01-SEP-00:10 | 137.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.80 | 06-SEP-15:19 | 158.98 | 30-SEP-00:54 |
October | 180.00 | 01-OCT-00:10 | 137.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 20-OCT-14:51 | 177.37 | 23-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 391.17 | 26-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 341.71 | 10-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | |||||
Maximum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.43 | 460.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.77 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 412.83 | 31-JAN-03:51 |
February | 180.00 | 01-FEB-00:10 | 137.77 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 461.50 | 02-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 137.77 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 291.33 | 06-MAR-00:54 |
April | 180.00 | 01-APR-00:10 | 137.77 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 15-APR-15:20 | 208.08 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.77 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.13 | 31-MAY-15:19 | 147.18 | 03-MAY-02:51 |
June | 180.00 | 01-JUN-00:10 | 137.77 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.51 | 11-JUN-15:20 | 112.25 | 03-JUN-03:54 |
July | 180.00 | 01-JUL-00:10 | 137.77 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.09 | 26-JUL-15:20 | 76.93 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 137.77 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 04-AUG-15:20 | 89.02 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 137.77 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.41 | 06-SEP-15:20 | 159.46 | 30-SEP-00:54 |
October | 180.00 | 01-OCT-00:10 | 137.77 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.19 | 20-OCT-15:20 | 177.86 | 23-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.77 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 394.94 | 26-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.77 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 342.30 | 10-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 | |||||
Maximum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 461.50 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 408.11 | 31-JAN-03:51 |
February | 180.00 | 01-FEB-00:10 | 137.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 461.32 | 02-FEB-07:59 |
March | 180.00 | 01-MAR-00:10 | 137.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 291.30 | 06-MAR-00:54 |
April | 180.00 | 01-APR-00:10 | 137.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 15-APR-15:20 | 208.06 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 137.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.12 | 31-MAY-15:20 | 147.16 | 03-MAY-02:51 |
June | 180.00 | 01-JUN-00:10 | 137.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.51 | 11-JUN-15:20 | 112.24 | 03-JUN-03:54 |
July | 180.00 | 01-JUL-00:10 | 137.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 26-JUL-15:20 | 76.93 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 137.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 04-AUG-15:20 | 89.01 | 07-AUG-05:52 |
September | 180.00 | 01-SEP-00:10 | 137.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.43 | 06-SEP-15:20 | 159.44 | 30-SEP-00:54 |
October | 180.00 | 01-OCT-00:10 | 137.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 | 20-OCT-13:01 | 177.84 | 23-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 392.63 | 26-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 137.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 342.26 | 10-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 | |||||
Maximum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 461.32 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 86.61 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 212.47 | 31-JAN-03:51 |
February | 180.00 | 01-FEB-00:10 | 86.61 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 238.16 | 02-FEB-07:50 |
March | 180.00 | 01-MAR-00:10 | 86.61 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 149.04 | 06-MAR-00:54 |
April | 180.00 | 01-APR-00:10 | 86.61 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 15-APR-15:20 | 106.45 | 03-APR-05:51 |
May | 180.00 | 01-MAY-00:10 | 86.61 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 31-MAY-15:20 | 75.29 | 03-MAY-02:51 |
June | 180.00 | 01-JUN-00:10 | 86.61 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.12 | 11-JUN-15:19 | 57.42 | 03-JUN-03:51 |
July | 180.00 | 01-JUL-00:10 | 86.61 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 | 26-JUL-15:20 | 39.36 | 23-JUL-03:52 |
August | 180.00 | 01-AUG-00:10 | 86.61 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 | 04-AUG-15:20 | 45.54 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 86.61 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 | 06-SEP-15:20 | 81.58 | 30-SEP-00:54 |
October | 180.00 | 01-OCT-00:10 | 86.61 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.24 | 20-OCT-15:20 | 90.99 | 23-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 86.61 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 201.80 | 26-NOV-06:51 |
December | 180.00 | 01-DEC-00:10 | 86.61 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 175.11 | 10-DEC-05:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 | |||||
Maximum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 | 238.16 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1927.76 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 951.09 | 31-JAN-03:51 |
February | 26988.77 | 01-FEB-00:10 | 1927.76 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1043.08 | 02-FEB-05:51 |
March | 26988.77 | 01-MAR-00:10 | 1927.76 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 785.41 | 06-MAR-00:51 |
April | 26988.77 | 01-APR-00:10 | 1927.76 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.07 | 15-APR-16:00 | 586.44 | 03-APR-05:57 |
May | 26988.77 | 01-MAY-00:10 | 1927.76 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.74 | 31-MAY-12:53 | 452.02 | 03-MAY-02:51 |
June | 26988.77 | 01-JUN-00:10 | 1927.76 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.22 | 11-JUN-14:53 | 368.92 | 01-JUN-04:59 |
July | 26988.77 | 01-JUL-00:10 | 1927.76 | 03-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.05 | 26-JUL-14:52 | 282.27 | 24-JUL-04:59 |
August | 26988.77 | 01-AUG-00:10 | 1927.76 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.15 | 04-AUG-14:52 | 312.95 | 07-AUG-05:59 |
September | 26988.77 | 01-SEP-00:10 | 1927.76 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.87 | 06-SEP-14:00 | 480.83 | 30-SEP-00:51 |
October | 26988.77 | 02-OCT-00:10 | 1927.76 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 523.02 | 23-OCT-05:53 |
November | 26988.77 | 01-NOV-00:10 | 1927.76 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 925.11 | 26-NOV-06:51 |
December | 26988.77 | 01-DEC-00:10 | 1927.76 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 915.51 | 08-DEC-23:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.27 | |||||
Maximum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 124.22 | 1043.08 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1927.76 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 965.64 | 31-JAN-03:51 |
February | 26988.77 | 01-FEB-00:10 | 1927.76 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1060.55 | 02-FEB-05:51 |
March | 26988.77 | 01-MAR-00:10 | 1927.76 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 796.02 | 06-MAR-00:51 |
April | 26988.77 | 01-APR-00:10 | 1927.76 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 | 15-APR-16:00 | 595.77 | 03-APR-05:59 |
May | 26988.77 | 01-MAY-00:10 | 1927.76 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.69 | 31-MAY-12:53 | 458.74 | 03-MAY-02:51 |
June | 26988.77 | 01-JUN-00:10 | 1927.76 | 01-JUN-19:40 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.20 | 11-JUN-14:53 | 373.55 | 01-JUN-04:59 |
July | 26988.77 | 01-JUL-00:10 | 1927.76 | 03-JUL-19:00 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.08 | 26-JUL-14:52 | 286.87 | 24-JUL-04:59 |
August | 26988.77 | 01-AUG-00:10 | 1927.76 | 01-AUG-19:40 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.54 | 04-AUG-14:52 | 318.66 | 07-AUG-05:59 |
September | 26988.77 | 01-SEP-00:10 | 1927.76 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.80 | 06-SEP-14:00 | 488.47 | 30-SEP-00:51 |
October | 26988.77 | 02-OCT-00:10 | 1927.76 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 530.08 | 23-OCT-05:59 |
November | 26988.77 | 01-NOV-00:10 | 1927.76 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 939.21 | 26-NOV-06:51 |
December | 26988.77 | 01-DEC-00:10 | 1927.76 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 926.04 | 08-DEC-23:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.87 | |||||
Maximum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 117.54 | 1060.55 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 968.56 | 31-JAN-06:11 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1111.73 | 02-FEB-07:55 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 768.22 | 05-MAR-20:51 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.50 | 15-APR-15:00 | 606.51 | 03-APR-20:51 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 457.03 | 02-MAY-07:19 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 39.39 | 11-JUN-14:53 | 386.14 | 01-JUN-17:53 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 10.11 | 26-JUL-00:29 | 272.22 | 24-JUL-05:19 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 48.12 | 04-AUG-15:00 | 330.86 | 06-AUG-22:41 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 32.91 | 06-SEP-14:00 | 484.12 | 29-SEP-22:41 |
October | 2401.70 | 02-OCT-00:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 526.69 | 31-OCT-17:53 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 927.14 | 26-NOV-06:51 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 905.03 | 08-DEC-20:51 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 272.22 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 48.12 | 1111.73 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1511.55 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 617.96 | 31-JAN-03:51 |
February | 0.00 | 1511.55 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 685.30 | 02-FEB-07:21 |
March | 0.00 | 1511.55 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 474.21 | 06-MAR-00:51 |
April | 0.00 | 1511.55 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 | 15-APR-14:54 | 353.08 | 03-APR-06:00 |
May | 0.00 | 1511.55 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.73 | 31-MAY-12:51 | 262.57 | 03-MAY-02:53 |
June | 0.00 | 1511.55 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.36 | 11-JUN-14:51 | 206.80 | 03-JUN-03:53 |
July | 0.00 | 1511.55 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 26-JUL-14:58 | 151.14 | 23-JUL-03:53 |
August | 0.00 | 1511.55 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.59 | 04-AUG-14:52 | 171.83 | 07-AUG-05:59 |
September | 0.00 | 1511.55 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.75 | 06-SEP-13:54 | 281.94 | 30-SEP-00:53 |
October | 0.00 | 1511.55 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 311.34 | 23-OCT-05:51 |
November | 0.00 | 1511.55 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 622.10 | 26-NOV-06:51 |
December | 0.00 | 1511.55 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 561.67 | 08-DEC-21:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.14 | ||||
Maximum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 94.59 | 685.30 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 155.22 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 414.23 | 31-JAN-03:51 |
February | 0.00 | 155.22 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 457.09 | 02-FEB-05:51 |
March | 0.00 | 155.22 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 316.51 | 06-MAR-01:00 |
April | 0.00 | 155.22 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.09 | 15-APR-16:40 | 227.51 | 03-APR-05:59 |
May | 0.00 | 155.22 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 | 31-MAY-12:53 | 171.69 | 03-MAY-02:51 |
June | 0.00 | 155.22 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.93 | 11-JUN-14:53 | 140.67 | 01-JUN-04:59 |
July | 0.00 | 155.22 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.96 | 26-JUL-14:52 | 101.88 | 23-JUL-03:51 |
August | 0.00 | 155.22 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.32 | 04-AUG-14:52 | 116.20 | 07-AUG-05:59 |
September | 0.00 | 155.22 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.06 | 06-SEP-13:52 | 185.62 | 30-SEP-00:51 |
October | 0.00 | 155.22 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 | 20-OCT-14:52 | 205.14 | 23-OCT-05:51 |
November | 0.00 | 155.22 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 410.22 | 26-NOV-06:51 |
December | 0.00 | 155.22 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 369.48 | 09-DEC-08:54 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 155.22 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.88 | ||||
Maximum of Months | 0.00 | 155.22 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 64.32 | 457.09 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 838.75 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 459.01 | 31-JAN-03:51 |
February | 0.00 | 838.75 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 514.34 | 02-FEB-05:51 |
March | 0.00 | 838.75 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 344.31 | 06-MAR-00:52 |
April | 0.00 | 838.75 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.46 | 15-APR-16:40 | 247.64 | 03-APR-06:00 |
May | 0.00 | 838.75 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.12 | 31-MAY-12:51 | 176.45 | 03-MAY-02:54 |
June | 0.00 | 838.75 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.04 | 11-JUN-14:51 | 138.76 | 01-JUN-04:59 |
July | 0.00 | 838.75 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.60 | 26-JUL-14:52 | 99.66 | 23-JUL-03:51 |
August | 0.00 | 838.75 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.20 | 04-AUG-14:52 | 115.67 | 07-AUG-05:59 |
September | 0.00 | 838.75 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.42 | 06-SEP-13:52 | 191.29 | 30-SEP-00:52 |
October | 0.00 | 838.75 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.79 | 20-OCT-14:52 | 213.52 | 23-OCT-06:00 |
November | 0.00 | 838.75 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 451.52 | 26-NOV-06:51 |
December | 0.00 | 838.75 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 401.77 | 08-DEC-20:52 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 838.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.66 | |||
Maximum of Months | 0.00 | 838.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.04 | 514.34 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 887.69 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 797.80 | 31-JAN-03:52 |
February | 0.00 | 887.69 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 874.35 | 02-FEB-05:51 |
March | 0.00 | 887.69 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 621.57 | 06-MAR-00:52 |
April | 0.00 | 887.69 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.45 | 15-APR-17:00 | 445.98 | 01-APR-04:51 |
May | 0.00 | 887.69 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.00 | 31-MAY-12:53 | 346.63 | 03-MAY-02:51 |
June | 0.00 | 887.69 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.16 | 11-JUN-14:53 | 281.76 | 01-JUN-04:51 |
July | 0.00 | 887.69 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.78 | 26-JUL-14:52 | 207.14 | 23-JUL-03:51 |
August | 0.00 | 887.69 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.62 | 04-AUG-14:52 | 233.27 | 07-AUG-05:51 |
September | 0.00 | 887.69 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.46 | 06-SEP-15:00 | 368.21 | 30-SEP-00:51 |
October | 0.00 | 887.69 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 402.69 | 23-OCT-05:51 |
November | 0.00 | 887.69 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 789.07 | 26-NOV-06:51 |
December | 0.00 | 887.69 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 720.87 | 08-DEC-20:52 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 887.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.14 | |||
Maximum of Months | 0.00 | 887.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.62 | 874.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 49631.96 | 05-JAN-21:22 | 102239.04 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44591.47 | 01-FEB-07:52 | 51119.52 | 60947.68 | 60837.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26237.24 | 19-MAR-19:29 | 76679.28 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27148.50 | 14-APR-19:11 | 89459.16 | 109705.82 | 96325.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28620.40 | 05-MAY-19:11 | 89459.16 | 109705.82 | 96325.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30345.45 | 29-JUN-20:51 | 102239.04 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31188.42 | 26-JUL-23:05 | 115018.92 | 24379.07 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31900.89 | 10-AUG-08:28 | 25559.76 | 48758.14 | 50697.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32758.50 | 23-SEP-14:22 | 38339.64 | 30473.84 | 35488.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34107.54 | 20-OCT-12:23 | 25559.76 | 30473.84 | 35488.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75012.75 | 25-NOV-21:32 | 89459.16 | 85326.75 | 81116.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23713.43 | 08-DEC-21:00 | 89459.16 | 109705.82 | 96325.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 23713.43 | 25559.76 | 24379.07 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75012.75 | 115018.92 | 109705.82 | 96325.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2713.95 | 12-JAN-12:34 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.78 |
February | 3095.21 | 08-FEB-13:40 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.12 |
March | 4015.24 | 25-MAR-13:57 | 3898.44 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.51 |
April | 4434.35 | 16-APR-11:50 | 3898.44 | 1819.31 | 2886.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.04 |
May | 4217.20 | 06-MAY-13:33 | 3898.44 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.91 |
June | 4213.64 | 29-JUN-18:21 | 9096.36 | 4851.50 | 6495.19 | 0.00 | 0.00 | 0.00 | 0.00 | 61.11 | 0.00 |
July | 4223.63 | 28-JUL-11:23 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 25.91 | 0.00 |
August | 4672.62 | 29-AUG-13:15 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.47 |
September | 5020.40 | 17-SEP-12:50 | 2598.96 | 1212.88 | 2165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.59 |
October | 5161.27 | 20-OCT-13:24 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.74 |
November | 4463.49 | 03-NOV-13:17 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.77 |
December | 3231.43 | 03-DEC-13:00 | 3898.44 | 1819.31 | 2886.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.39 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2713.95 | 2598.96 | 1212.88 | 2165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5161.27 | 9096.36 | 4851.50 | 6495.19 | 0.00 | 0.00 | 0.00 | 0.00 | 61.11 | 555.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4023.23 | 05-JAN-21:52 | 12038.40 | 5618.06 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.24 |
February | 2631.01 | 02-FEB-06:02 | 10533.60 | 2809.03 | 4178.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.34 |
March | 2572.52 | 19-MAR-18:53 | 9028.80 | 4915.80 | 6685.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 |
April | 3038.38 | 15-APR-20:35 | 10533.60 | 4915.80 | 6685.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.85 |
May | 3044.65 | 31-MAY-22:07 | 13543.20 | 2106.77 | 3342.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.96 |
June | 3173.65 | 29-JUN-23:19 | 13543.20 | 1404.52 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 |
July | 3115.78 | 26-JUL-23:05 | 13543.20 | 1404.52 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
August | 3107.08 | 22-AUG-23:05 | 13543.20 | 1404.52 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 |
September | 3115.92 | 08-SEP-23:15 | 13543.20 | 1404.52 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.76 |
October | 2914.37 | 20-OCT-15:35 | 7524.00 | 1755.64 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 |
November | 4111.52 | 25-NOV-21:32 | 10533.60 | 4915.80 | 6685.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.90 |
December | 1771.13 | 05-DEC-22:00 | 12038.40 | 5618.06 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.91 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1771.13 | 7524.00 | 1404.52 | 2507.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.85 | |
Maximum of Months | 4111.52 | 13543.20 | 5618.06 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1069.54 | 13-JAN-21:52 | 0.00 | 13436.03 | 7952.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.96 |
February | 1692.89 | 24-FEB-21:00 | 0.00 | 15115.54 | 8394.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.29 |
March | 2345.76 | 19-MAR-21:21 | 0.00 | 8397.52 | 5301.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.55 |
April | 2983.62 | 15-APR-20:35 | 0.00 | 11756.53 | 7069.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.51 |
May | 2980.32 | 31-MAY-18:12 | 0.00 | 13436.03 | 7952.65 | 0.00 | 0.00 | 0.00 | 0.00 | 25.37 | 0.00 |
June | 3121.50 | 29-JUN-23:19 | 0.00 | 3359.01 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.84 |
July | 3080.37 | 26-JUL-23:10 | 0.00 | 3359.01 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 |
August | 3039.80 | 05-AUG-08:25 | 0.00 | 6718.02 | 4418.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 |
September | 3025.79 | 08-SEP-08:29 | 0.00 | 6046.21 | 3976.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 |
October | 2616.22 | 20-OCT-18:13 | 0.00 | 13436.03 | 7952.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.46 |
November | 2109.11 | 08-NOV-22:00 | 0.00 | 13436.03 | 7952.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.00 |
December | 1232.11 | 04-DEC-20:52 | 0.00 | 15115.54 | 8394.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1069.54 | 0.00 | 3359.01 | 2650.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3121.50 | 0.00 | 15115.54 | 8394.47 | 0.00 | 0.00 | 0.00 | 0.00 | 25.37 | 243.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 727.46 | 19-JAN-07:52 | 0.00 | 862.35 | 1529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.90 |
February | 734.48 | 02-FEB-07:02 | 0.00 | 862.35 | 1529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.10 |
March | 976.70 | 25-MAR-15:17 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.49 |
April | 1130.04 | 16-APR-11:29 | 0.00 | 517.41 | 1019.61 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | 0.00 |
May | 1145.29 | 31-MAY-18:12 | 0.00 | 1379.77 | 2294.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 0.00 |
June | 1228.38 | 29-JUN-23:19 | 0.00 | 344.94 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 |
July | 1210.61 | 04-JUL-02:13 | 0.00 | 344.94 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 |
August | 1202.79 | 05-AUG-10:03 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 |
September | 1192.02 | 11-SEP-10:00 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 0.00 |
October | 1088.44 | 20-OCT-15:05 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
November | 967.24 | 03-NOV-14:35 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.45 |
December | 481.68 | 03-DEC-15:52 | 0.00 | 344.94 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 481.68 | 0.00 | 344.94 | 764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1228.38 | 0.00 | 1379.77 | 2294.12 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 456.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 82717.05 | 05-JAN-21:34 | 8064.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 837.65 |
February | 68851.70 | 01-FEB-20:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 931.65 |
March | 68003.07 | 23-MAR-20:01 | 8064.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 340.85 |
April | 69083.27 | 14-APR-20:01 | 8064.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 230.48 |
May | 69802.24 | 05-MAY-20:01 | 8064.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 205.35 |
June | 72823.42 | 29-JUN-19:51 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 90.79 |
July | 72640.51 | 05-JUL-19:51 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 114.72 |
August | 72518.45 | 01-AUG-19:51 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 147.34 |
September | 71158.99 | 01-SEP-20:01 | 8064.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 185.04 |
October | 68547.08 | 19-OCT-19:51 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 361.93 |
November | 73654.65 | 25-NOV-21:14 | 7056.00 | 3116.44 | 38507.80 | 334539.59 | 0.00 | 0.00 | 0.00 | 0.00 | 825.78 |
December | 61311.96 | 01-DEC-20:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 596.55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 61311.96 | 7056.00 | 3116.44 | 38507.80 | 334539.59 | 0.00 | 0.00 | 0.00 | 0.00 | 90.79 | |
Maximum of Months | 82717.05 | 8064.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 931.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13602.81 | 05-JAN-21:52 | 136608.00 | 9757.88 | 9144.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2976.17 |
February | 14222.09 | 02-FEB-06:02 | 119532.00 | 4878.94 | 5080.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3559.07 |
March | 17679.20 | 25-MAR-13:57 | 51228.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.42 |
April | 18479.92 | 16-APR-11:26 | 51228.00 | 805.03 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 | 0.00 |
May | 18282.97 | 31-MAY-22:07 | 153684.00 | 3659.21 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.59 |
June | 19376.75 | 26-JUN-23:07 | 153684.00 | 2439.47 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.35 |
July | 19137.29 | 26-JUL-02:43 | 153684.00 | 1219.74 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.14 |
August | 18986.40 | 29-AUG-13:15 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.83 |
September | 20507.34 | 17-SEP-12:50 | 34152.00 | 536.68 | 3048.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 |
October | 21322.45 | 20-OCT-12:23 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.34 |
November | 18674.32 | 03-NOV-13:17 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.44 |
December | 14996.45 | 03-DEC-13:00 | 51228.00 | 805.03 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1296.66 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13602.81 | 34152.00 | 536.68 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21322.45 | 153684.00 | 9757.88 | 9144.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 | 3559.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 83149.89 | 05-JAN-21:52 | 405537.60 | 57451.29 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6119.16 |
February | 58470.02 | 02-FEB-06:02 | 354845.40 | 28725.64 | 52785.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7552.61 |
March | 53002.02 | 25-MAR-13:57 | 152076.60 | 15440.03 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 847.14 |
April | 61380.36 | 15-APR-20:35 | 354845.40 | 50269.88 | 84456.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.39 |
May | 62258.84 | 31-MAY-22:07 | 456229.80 | 21544.23 | 42228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.49 |
June | 65090.25 | 29-JUN-23:19 | 456229.80 | 14362.82 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.23 |
July | 64153.98 | 26-JUL-23:05 | 456229.80 | 14362.82 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.19 |
August | 63809.84 | 22-AUG-23:05 | 456229.80 | 14362.82 | 31671.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.45 |
September | 63862.33 | 08-SEP-00:53 | 456229.80 | 10772.12 | 26392.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.42 |
October | 59898.84 | 20-OCT-15:35 | 253461.00 | 15440.03 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.47 |
November | 84586.99 | 25-NOV-21:32 | 354845.40 | 50269.88 | 84456.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6048.25 |
December | 38427.46 | 04-DEC-23:00 | 456229.80 | 43088.47 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2717.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 38427.46 | 152076.60 | 10772.12 | 26392.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.39 | |
Maximum of Months | 84586.99 | 456229.80 | 57451.29 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7552.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3355.60 | 12-JAN-16:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.09 |
February | 3630.02 | 20-FEB-16:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.08 |
March | 3640.99 | 22-MAR-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.37 |
April | 3794.66 | 29-APR-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.03 |
May | 3691.39 | 21-MAY-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 |
June | 3297.30 | 13-JUN-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 35.70 | 0.00 |
July | 3308.85 | 12-JUL-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 | 0.00 |
August | 3323.91 | 30-AUG-18:01 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 |
September | 3658.58 | 20-SEP-18:01 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.87 |
October | 3655.51 | 27-OCT-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.18 |
November | 3677.68 | 04-NOV-15:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.27 |
December | 2378.33 | 01-DEC-16:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2378.33 | 540.00 | 86.11 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3794.66 | 1386.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 35.70 | 168.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 172.67 | 12-JAN-16:13 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.89 |
February | 3274.65 | 20-FEB-16:11 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.42 |
March | 3474.54 | 24-MAR-15:11 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.59 |
April | 3667.81 | 29-APR-18:01 | 1170.00 | 1377.54 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.16 |
May | 4123.87 | 20-MAY-18:01 | 1170.00 | 1377.54 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.09 |
June | 3461.38 | 23-JUN-21:11 | 1800.00 | 929.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 |
July | 3357.41 | 18-JUL-21:11 | 1800.00 | 929.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.75 |
August | 3285.45 | 08-AUG-21:11 | 1800.00 | 929.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.01 |
September | 3862.73 | 19-SEP-17:01 | 972.00 | 929.84 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.73 |
October | 3489.21 | 19-OCT-16:31 | 972.00 | 120.53 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.86 |
November | 3579.37 | 04-NOV-15:11 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.44 |
December | 787.85 | 01-DEC-16:13 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 172.67 | 540.00 | 86.10 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | |
Maximum of Months | 4123.87 | 1800.00 | 1377.54 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 213.68 | 30-JAN-15:01 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.60 |
February | 252.59 | 02-FEB-15:01 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.24 |
March | 209.88 | 25-MAR-15:02 | 0.00 | 54.11 | 541.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 |
April | 422.16 | 15-APR-12:52 | 0.00 | 54.11 | 335.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 | 0.00 |
May | 284.20 | 31-MAY-17:12 | 0.00 | 584.43 | 1238.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 | 0.00 |
June | 326.99 | 26-JUN-17:12 | 0.00 | 584.43 | 1238.36 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 0.00 |
July | 305.82 | 30-JUL-13:02 | 0.00 | 54.11 | 335.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 | 0.00 |
August | 407.91 | 29-AUG-13:12 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 |
September | 551.85 | 07-SEP-12:41 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 0.00 |
October | 611.45 | 20-OCT-12:38 | 0.00 | 48.70 | 278.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.36 |
November | 590.50 | 04-NOV-12:21 | 0.00 | 54.11 | 335.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 |
December | 125.03 | 07-DEC-15:01 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.02 |
Annual Sum or Average | |||||||||||
Minimum of Months | 125.03 | 0.00 | 48.70 | 278.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 611.45 | 0.00 | 584.43 | 1238.36 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 105.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 561.08 | 01-JAN-09:01 | 540.00 | 202.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.49 |
February | 753.60 | 25-FEB-09:01 | 540.00 | 202.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.68 |
March | 926.56 | 11-MAR-09:01 | 540.00 | 202.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.92 |
April | 977.37 | 26-APR-18:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.54 |
May | 1016.48 | 06-MAY-18:51 | 1170.00 | 866.07 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.66 |
June | 1015.53 | 23-JUN-21:11 | 1800.00 | 584.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 |
July | 992.04 | 18-JUL-21:11 | 1800.00 | 584.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.71 |
August | 962.46 | 01-AUG-18:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 | 0.00 |
September | 977.66 | 10-SEP-21:11 | 1386.00 | 736.16 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 917.80 | 21-OCT-18:01 | 1170.00 | 866.07 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 |
November | 870.07 | 09-NOV-09:01 | 360.00 | 378.90 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.18 |
December | 671.66 | 03-DEC-09:01 | 540.00 | 202.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 561.08 | 360.00 | 202.08 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1016.48 | 1800.00 | 866.07 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 | 48.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 801.53 | 12-JAN-09:03 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.25 |
February | 2852.81 | 21-FEB-09:01 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.73 |
March | 3257.14 | 24-MAR-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.46 |
April | 3263.20 | 30-APR-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.18 |
May | 3210.22 | 06-MAY-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 |
June | 3010.13 | 28-JUN-08:61 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 | 0.00 |
July | 3039.19 | 29-JUL-08:61 | 540.00 | 321.46 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
August | 2996.63 | 01-AUG-18:01 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 | 0.00 |
September | 3214.39 | 20-SEP-18:01 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.01 |
October | 3229.30 | 31-OCT-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.21 |
November | 3277.12 | 04-NOV-15:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 |
December | 2063.12 | 03-DEC-09:01 | 540.00 | 321.46 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 801.53 | 360.00 | 86.11 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3277.12 | 1386.00 | 1377.70 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 | 187.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 481.91 | 12-JAN-09:04 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.24 |
February | 2183.19 | 24-FEB-09:01 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.72 |
March | 2988.52 | 22-MAR-08:61 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.31 |
April | 3231.19 | 30-APR-18:01 | 1170.00 | 1377.54 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 |
May | 3254.85 | 31-MAY-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.73 |
June | 3525.89 | 20-JUN-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.05 |
July | 3519.23 | 18-JUL-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.21 |
August | 3414.92 | 09-AUG-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.41 |
September | 3346.63 | 06-SEP-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.30 |
October | 2711.02 | 01-OCT-08:61 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 |
November | 2236.09 | 04-NOV-08:61 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.45 |
December | 827.68 | 03-DEC-09:02 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 481.91 | 360.00 | 321.43 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.73 | |
Maximum of Months | 3525.89 | 1170.00 | 1377.54 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1587.70 | 06-JAN-07:52 | 0.00 | 4659.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.13 |
February | 1853.81 | 02-FEB-07:02 | 0.00 | 4659.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.27 |
March | 1701.99 | 25-MAR-14:45 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 |
April | 2030.89 | 18-APR-18:17 | 0.00 | 5964.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 0.00 |
May | 1973.24 | 31-MAY-18:12 | 0.00 | 7455.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.97 | 0.00 |
June | 2193.91 | 29-JUN-23:19 | 0.00 | 1863.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 0.00 |
July | 2222.63 | 06-JUL-13:43 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.01 | 0.00 |
August | 2193.21 | 05-AUG-11:47 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.25 | 0.00 |
September | 2195.64 | 12-SEP-13:26 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 |
October | 1935.47 | 20-OCT-15:05 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.81 | 0.00 |
November | 1606.47 | 03-NOV-14:35 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.26 |
December | 597.53 | 03-DEC-13:28 | 0.00 | 1863.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.16 |
Annual Sum or Average | |||||||||||
Minimum of Months | 597.53 | 0.00 | 1863.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2222.63 | 0.00 | 7455.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.97 | 513.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3500.09 | 12-JAN-16:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.63 |
February | 3773.50 | 20-FEB-16:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.35 |
March | 3782.62 | 24-MAR-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.71 |
April | 4020.08 | 29-APR-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.03 |
May | 3855.33 | 21-MAY-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.10 |
June | 3393.49 | 17-JUN-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 | 0.00 |
July | 3444.84 | 13-JUL-18:01 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 | 0.00 |
August | 3465.82 | 21-AUG-18:01 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 | 0.00 |
September | 3811.11 | 20-SEP-18:01 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 |
October | 3801.06 | 31-OCT-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.75 |
November | 3830.05 | 04-NOV-15:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.64 |
December | 2772.17 | 01-DEC-16:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2772.17 | 540.00 | 86.11 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4020.08 | 1386.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 | 168.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 940.86 | 12-JAN-16:13 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.33 |
February | 2345.14 | 24-FEB-16:11 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.60 |
March | 3567.62 | 24-MAR-15:11 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.68 |
April | 3865.13 | 29-APR-18:01 | 1170.00 | 1377.54 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.65 |
May | 4635.61 | 20-MAY-18:01 | 1170.00 | 1377.54 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.24 |
June | 3769.05 | 22-JUN-21:01 | 1800.00 | 929.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.63 |
July | 3803.19 | 23-JUL-21:11 | 1386.00 | 1170.91 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.26 |
August | 3514.18 | 16-AUG-21:01 | 1800.00 | 929.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.70 |
September | 4111.60 | 19-SEP-17:01 | 972.00 | 929.84 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.40 |
October | 3650.62 | 19-OCT-16:31 | 972.00 | 120.53 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.68 |
November | 3702.28 | 04-NOV-15:11 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.07 |
December | 707.29 | 02-DEC-16:13 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.28 |
Annual Sum or Average | |||||||||||
Minimum of Months | 707.29 | 540.00 | 86.10 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.68 | |
Maximum of Months | 4635.61 | 1800.00 | 1377.54 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1776.92 | 30-JAN-16:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.36 |
February | 1664.14 | 17-FEB-16:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.97 |
March | 1676.92 | 21-MAR-15:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.88 |
April | 1672.02 | 26-APR-15:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.59 |
May | 1657.67 | 20-MAY-18:01 | 1170.00 | 866.07 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.61 |
June | 1543.07 | 25-JUN-18:01 | 1170.00 | 866.07 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 25.40 | 0.00 |
July | 1545.94 | 26-JUL-15:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 22.65 | 0.00 |
August | 1536.48 | 17-AUG-18:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
September | 1565.30 | 20-SEP-15:29 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 0.00 |
October | 1446.48 | 03-OCT-15:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.46 |
November | 1612.07 | 21-NOV-16:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.21 |
December | 1667.39 | 05-DEC-16:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.26 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1446.48 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1776.92 | 1386.00 | 866.07 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 25.40 | 186.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 50464.44 | 19-JAN-01:52 | 269887.68 | 3212.94 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.52 |
February | 38601.73 | 02-FEB-06:02 | 209912.64 | 8567.83 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.07 |
March | 28283.99 | 19-MAR-21:19 | 239900.16 | 10709.79 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.76 |
April | 31838.41 | 16-APR-20:29 | 239900.16 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.54 |
May | 33195.63 | 30-MAY-22:47 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.39 |
June | 34213.11 | 29-JUN-21:51 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.55 |
July | 33898.65 | 05-JUL-21:11 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.99 |
August | 33779.05 | 02-AUG-21:51 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.74 |
September | 32579.38 | 11-SEP-02:33 | 269887.68 | 2141.96 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.29 |
October | 29079.78 | 20-OCT-16:03 | 149937.60 | 3552.00 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.52 |
November | 40766.89 | 25-NOV-21:12 | 209912.64 | 14993.71 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 877.07 |
December | 22325.13 | 04-DEC-23:02 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 411.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 22325.13 | 149937.60 | 2141.96 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.54 | |
Maximum of Months | 50464.44 | 269887.68 | 14993.71 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 52002.24 | 19-JAN-01:52 | 269887.68 | 3212.94 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 880.52 |
February | 40226.86 | 02-FEB-06:02 | 209912.64 | 8567.83 | 56232.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.46 |
March | 30943.10 | 19-MAR-21:19 | 239900.16 | 10709.79 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.11 |
April | 34257.51 | 16-APR-21:07 | 239900.16 | 10709.79 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.72 |
May | 35697.64 | 31-MAY-22:07 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.04 |
June | 36926.51 | 29-JUN-21:11 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.41 |
July | 36569.67 | 05-JUL-21:11 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.65 |
August | 36515.23 | 02-AUG-21:51 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.80 |
September | 34810.32 | 11-SEP-23:07 | 269887.68 | 4283.92 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.54 |
October | 31568.27 | 20-OCT-16:03 | 149937.60 | 3552.00 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.58 |
November | 51968.69 | 25-NOV-21:42 | 209912.64 | 14993.71 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 860.16 |
December | 24857.67 | 04-DEC-23:02 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 24857.67 | 149937.60 | 3212.94 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.41 | |
Maximum of Months | 52002.24 | 269887.68 | 14993.71 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 54337.86 | 29-JAN-19:24 | 16011.36 | 8484.25 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 830.72 |
February | 45168.92 | 01-FEB-11:32 | 5337.12 | 3030.09 | 146045.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 897.66 |
March | 45258.66 | 23-MAR-18:11 | 18679.92 | 9696.29 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 277.23 |
April | 47549.84 | 16-APR-18:11 | 16011.36 | 8484.25 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 69.74 |
May | 51168.88 | 31-MAY-18:11 | 18679.92 | 9696.29 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 76.35 |
June | 51611.68 | 29-JUN-18:01 | 18679.92 | 9696.29 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 |
July | 51130.37 | 29-JUL-18:01 | 16011.36 | 8484.25 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 110.37 |
August | 51450.01 | 02-AUG-18:11 | 18679.92 | 9696.29 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 70.07 |
September | 50617.03 | 09-SEP-18:01 | 16011.36 | 8484.25 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 119.24 |
October | 45620.67 | 11-OCT-17:31 | 13342.80 | 7272.22 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 227.44 |
November | 56551.75 | 25-NOV-21:14 | 18679.92 | 8484.25 | 146045.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 818.28 |
December | 39467.60 | 03-DEC-11:42 | 8005.68 | 3636.11 | 146045.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 415.48 |
Annual Sum or Average | |||||||||||
Minimum of Months | 39467.60 | 5337.12 | 3030.09 | 146045.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | |
Maximum of Months | 56551.75 | 18679.92 | 9696.29 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 897.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1097.42 | 13-JAN-14:52 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.69 |
February | 1275.33 | 24-FEB-14:32 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.50 |
March | 4340.76 | 28-MAR-14:22 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.04 |
April | 7367.37 | 18-APR-15:57 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 | 0.00 |
May | 7537.99 | 29-MAY-13:03 | 0.00 | 1972.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.40 | 0.00 |
June | 7768.09 | 09-JUN-13:33 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 0.00 |
July | 7865.65 | 01-JUL-17:12 | 0.00 | 5917.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 0.00 |
August | 7761.89 | 11-AUG-16:06 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 0.00 |
September | 7659.44 | 12-SEP-13:40 | 0.00 | 2219.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.48 |
October | 7138.84 | 20-OCT-13:24 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
November | 6399.75 | 03-NOV-13:36 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.27 |
December | 1194.56 | 03-DEC-13:40 | 0.00 | 1972.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.75 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1097.42 | 0.00 | 1972.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7865.65 | 0.00 | 5917.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.98 | 272.69 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.362481E+12 | 231771.65 | 12-JAN-20:19 | 0.726911E+12 | 660935.69 | 30-JAN-20:40 |
February | 0.326441E+12 | 232188.28 | 08-FEB-20:40 | 0.571720E+12 | 684105.20 | 02-FEB-20:00 |
March | 0.364652E+12 | 239457.16 | 19-MAR-19:40 | 0.447041E+12 | 401814.97 | 05-MAR-19:10 |
April | 0.371437E+12 | 333070.56 | 16-APR-19:19 | 0.373212E+12 | 323250.76 | 01-APR-16:10 |
May | 0.411717E+12 | 329063.18 | 31-MAY-18:19 | 0.349227E+12 | 281872.89 | 01-MAY-17:19 |
June | 0.474341E+12 | 368477.42 | 26-JUN-19:00 | 0.329759E+12 | 280706.04 | 01-JUN-17:19 |
July | 0.528565E+12 | 399615.74 | 26-JUL-19:40 | 0.334110E+12 | 279657.21 | 03-JUL-17:19 |
August | 0.515495E+12 | 383925.79 | 03-AUG-19:19 | 0.331751E+12 | 279089.03 | 01-AUG-17:00 |
September | 0.428584E+12 | 326455.32 | 07-SEP-18:10 | 0.326612E+12 | 293297.73 | 29-SEP-17:00 |
October | 0.383120E+12 | 261011.68 | 20-OCT-19:40 | 0.359707E+12 | 290501.80 | 06-OCT-18:30 |
November | 0.358821E+12 | 241218.12 | 03-NOV-19:19 | 0.451117E+12 | 603150.34 | 25-NOV-21:49 |
December | 0.366810E+12 | 230137.94 | 06-DEC-20:19 | 0.576156E+12 | 495791.44 | 11-DEC-17:40 |
Annual Sum or Average | 0.489246E+13 | 0.517732E+13 | ||||
Minimum of Months | 0.326441E+12 | 230137.94 | 0.326612E+12 | 279089.03 | ||
Maximum of Months | 0.528565E+12 | 399615.74 | 0.726911E+12 | 684105.20 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.451689E+11 | 0.192913E+11 | 0.140003E+12 | 0.825502E+11 | 0.497865E+11 | 0.168061E+10 | 0.00 | 0.181901E+09 | 0.00 | 0.00 | 0.121183E+11 | 0.769190E+10 | 0.00 |
February | 0.406544E+11 | 0.160738E+11 | 0.126445E+12 | 0.745616E+11 | 0.452690E+11 | 0.150164E+10 | 0.00 | 0.391818E+09 | 0.00 | 0.00 | 0.109449E+11 | 0.694986E+10 | 0.00 |
March | 0.448064E+11 | 0.159272E+11 | 0.140067E+12 | 0.825526E+11 | 0.532216E+11 | 0.171248E+10 | 0.00 | 0.283431E+10 | 0.00 | 0.00 | 0.117214E+11 | 0.768793E+10 | 0.00 |
April | 0.430197E+11 | 0.134984E+11 | 0.135446E+12 | 0.798867E+11 | 0.524607E+11 | 0.256651E+10 | 0.00 | 0.228679E+11 | 0.00 | 0.00 | 0.102358E+11 | 0.744875E+10 | 0.00 |
May | 0.441936E+11 | 0.122769E+11 | 0.140035E+12 | 0.825509E+11 | 0.565561E+11 | 0.432208E+10 | 0.00 | 0.529669E+11 | 0.00 | 0.00 | 0.697508E+10 | 0.768834E+10 | 0.00 |
June | 0.426849E+11 | 0.110416E+11 | 0.135537E+12 | 0.798889E+11 | 0.575004E+11 | 0.468525E+10 | 0.00 | 0.126336E+12 | 0.00 | 0.00 | 0.520671E+10 | 0.744188E+10 | 0.00 |
July | 0.440461E+11 | 0.117674E+11 | 0.139944E+12 | 0.825484E+11 | 0.603178E+11 | 0.519879E+10 | 0.00 | 0.169547E+12 | 0.00 | 0.00 | 0.337467E+10 | 0.769793E+10 | 0.00 |
August | 0.443554E+11 | 0.132122E+11 | 0.140067E+12 | 0.825523E+11 | 0.620346E+11 | 0.509465E+10 | 0.00 | 0.152109E+12 | 0.00 | 0.00 | 0.423521E+10 | 0.768979E+10 | 0.00 |
September | 0.431671E+11 | 0.145592E+11 | 0.135446E+12 | 0.798868E+11 | 0.600057E+11 | 0.412152E+10 | 0.00 | 0.730613E+11 | 0.00 | 0.00 | 0.686766E+10 | 0.744930E+10 | 0.00 |
October | 0.449363E+11 | 0.170230E+11 | 0.140003E+12 | 0.825501E+11 | 0.598297E+11 | 0.300292E+10 | 0.00 | 0.128062E+11 | 0.00 | 0.00 | 0.111225E+11 | 0.768681E+10 | 0.00 |
November | 0.436975E+11 | 0.181816E+11 | 0.135531E+12 | 0.798880E+11 | 0.535615E+11 | 0.167390E+10 | 0.00 | 0.329804E+10 | 0.00 | 0.00 | 0.115622E+11 | 0.743338E+10 | 0.00 |
December | 0.452031E+11 | 0.197590E+11 | 0.139944E+12 | 0.825492E+11 | 0.536984E+11 | 0.135529E+10 | 0.00 | 0.381426E+09 | 0.00 | 0.00 | 0.121176E+11 | 0.769787E+10 | 0.00 |
Annual Sum or Average | 0.525934E+12 | 0.182612E+12 | 0.164847E+13 | 0.971966E+12 | 0.664242E+12 | 0.369156E+11 | 0.00 | 0.616782E+12 | 0.106482E+12 | 0.905637E+11 | |||
Minimum of Months | 0.406544E+11 | 0.110416E+11 | 0.126445E+12 | 0.745616E+11 | 0.452690E+11 | 0.135529E+10 | 0.00 | 0.181901E+09 | 0.00 | 0.00 | 0.337467E+10 | 0.694986E+10 | 0.00 |
Maximum of Months | 0.452031E+11 | 0.197590E+11 | 0.140067E+12 | 0.825526E+11 | 0.620346E+11 | 0.519879E+10 | 0.00 | 0.169547E+12 | 0.00 | 0.00 | 0.121183E+11 | 0.769793E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.370544E+12 | 0.00 | 0.204448E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.247277E+12 | 0.00 | 0.187239E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.885365E+11 | 0.00 | 0.206466E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.313328E+11 | 0.00 | 0.194923E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.250533E+10 | 0.00 | 0.194743E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.962941E+09 | 0.00 | 0.181682E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 90783435.62 | 0.00 | 0.182199E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 96049227.21 | 0.00 | 0.179616E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.486283E+10 | 0.00 | 0.174793E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.226529E+11 | 0.00 | 0.185136E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.118663E+12 | 0.00 | 0.185363E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.225266E+12 | 0.00 | 0.199069E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.111279E+13 | 0.227568E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 90783435.62 | 0.00 | 0.174793E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.370544E+12 | 0.00 | 0.206466E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 47387.53 | 02-JAN-20:10 | 11632.50 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 62573.78 | 02-JAN-07:19 | 25378.32 | 18-JAN-19:10 | 2844.42 | 30-JAN-14:20 | 0.00 | 01-JAN-00:10 |
February | 47387.53 | 01-FEB-20:10 | 11632.50 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 62573.78 | 01-FEB-07:19 | 25442.84 | 24-FEB-16:19 | 2028.36 | 16-FEB-10:30 | 0.00 | 01-FEB-00:10 |
March | 47387.53 | 01-MAR-20:10 | 11632.50 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 62573.78 | 13-MAR-06:19 | 27802.96 | 19-MAR-20:30 | 1965.74 | 05-MAR-16:19 | 0.00 | 01-MAR-00:10 |
April | 47387.53 | 03-APR-19:10 | 11632.50 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 62573.45 | 14-APR-06:19 | 31145.95 | 15-APR-18:40 | 2413.24 | 16-APR-21:19 | 0.00 | 01-APR-00:10 |
May | 47387.53 | 01-MAY-19:10 | 11632.50 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 62572.63 | 10-MAY-06:19 | 33249.69 | 31-MAY-18:19 | 2423.30 | 31-MAY-18:19 | 0.00 | 01-MAY-00:10 |
June | 47387.53 | 01-JUN-19:40 | 11632.50 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 62572.81 | 13-JUN-06:19 | 30925.73 | 25-JUN-18:19 | 2754.85 | 25-JUN-22:30 | 0.00 | 01-JUN-00:10 |
July | 47387.53 | 03-JUL-19:00 | 11632.50 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 62572.61 | 20-JUL-06:30 | 32262.81 | 11-JUL-19:49 | 3520.29 | 26-JUL-19:19 | 0.00 | 01-JUL-00:10 |
August | 47387.53 | 01-AUG-19:40 | 11632.50 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 62572.77 | 31-AUG-06:19 | 31486.20 | 05-AUG-08:20 | 3485.56 | 03-AUG-19:19 | 0.00 | 01-AUG-00:10 |
September | 47387.53 | 01-SEP-19:10 | 11632.50 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 62573.78 | 21-SEP-06:19 | 30940.00 | 14-SEP-18:40 | 2454.37 | 11-SEP-08:30 | 0.00 | 01-SEP-00:10 |
October | 47387.53 | 02-OCT-19:10 | 11632.50 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 62573.78 | 02-OCT-06:19 | 30515.85 | 20-OCT-19:40 | 1831.54 | 01-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 47387.53 | 01-NOV-19:10 | 11632.50 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 62573.78 | 01-NOV-06:19 | 29531.79 | 03-NOV-15:39 | 2024.46 | 25-NOV-10:39 | 0.00 | 01-NOV-00:10 |
December | 47387.53 | 01-DEC-20:10 | 11632.50 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 62573.78 | 01-DEC-07:19 | 26587.68 | 05-DEC-16:19 | 1984.86 | 15-DEC-17:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 47387.53 | 11632.50 | 88863.15 | 62572.61 | 25378.32 | 1831.54 | 0.00 | |||||||
Maximum of Months | 47387.53 | 11632.50 | 88863.15 | 62573.78 | 33249.69 | 3520.29 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 2878.50 | 12-JAN-16:19 | 0.00 | 0.00 | 6004.29 | 01-JAN-00:30 | 4738.08 | 30-JAN-07:49 | 0.00 |
February | 6914.63 | 24-FEB-16:19 | 0.00 | 0.00 | 4880.77 | 01-FEB-00:10 | 4739.42 | 02-FEB-07:10 | 0.00 |
March | 32382.26 | 25-MAR-15:20 | 0.00 | 0.00 | 5255.28 | 23-MAR-22:40 | 4735.26 | 06-MAR-07:49 | 0.00 |
April | 112621.75 | 18-APR-15:30 | 0.00 | 0.00 | 4880.77 | 01-APR-00:10 | 4735.06 | 05-APR-06:10 | 0.00 |
May | 116843.98 | 31-MAY-18:19 | 0.00 | 0.00 | 5554.88 | 20-MAY-23:49 | 4735.12 | 31-MAY-06:19 | 0.00 |
June | 155328.32 | 11-JUN-15:20 | 0.00 | 0.00 | 5255.28 | 28-JUN-08:50 | 4736.28 | 14-JUN-06:19 | 0.00 |
July | 167553.28 | 26-JUL-19:19 | 0.00 | 0.00 | 5255.28 | 17-JUL-09:20 | 4736.28 | 05-JUL-06:10 | 0.00 |
August | 176926.02 | 04-AUG-15:20 | 0.00 | 0.00 | 5255.28 | 02-AUG-22:40 | 4736.61 | 31-AUG-06:19 | 0.00 |
September | 130977.63 | 06-SEP-15:20 | 0.00 | 0.00 | 5255.28 | 10-SEP-12:20 | 4735.65 | 06-SEP-06:10 | 0.00 |
October | 70145.02 | 20-OCT-15:20 | 0.00 | 0.00 | 5255.28 | 19-OCT-22:40 | 4734.58 | 05-OCT-06:19 | 0.00 |
November | 30448.09 | 05-NOV-15:20 | 0.00 | 0.00 | 4880.77 | 01-NOV-00:10 | 4735.70 | 27-NOV-07:19 | 0.00 |
December | 3260.35 | 03-DEC-14:30 | 0.00 | 0.00 | 4880.77 | 01-DEC-00:10 | 4736.23 | 11-DEC-07:19 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 2878.50 | 0.00 | 0.00 | 4880.77 | 4734.58 | 0.00 | |||
Maximum of Months | 176926.02 | 0.00 | 0.00 | 6004.29 | 4739.42 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 231771.65 | 12-JAN-20:19 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 23376.58 | 1730.47 | 0.00 | 508.34 | 0.00 |
February | 232188.28 | 08-FEB-20:40 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 23315.24 | 1770.64 | 0.00 | 830.28 | 0.00 |
March | 239457.16 | 19-MAR-19:40 | 43946.87 | 84670.41 | 11632.50 | 50231.18 | 26232.22 | 1660.38 | 0.00 | 16095.61 | 0.00 |
April | 333070.56 | 16-APR-19:19 | 43946.87 | 84670.41 | 11632.50 | 50231.18 | 28748.74 | 2361.52 | 0.00 | 104995.89 | 0.00 |
May | 329063.18 | 31-MAY-18:19 | 39246.43 | 77265.07 | 0.00 | 50070.79 | 33249.69 | 2423.30 | 0.00 | 116843.98 | 0.00 |
June | 368477.42 | 26-JUN-19:00 | 47387.53 | 86131.51 | 11632.50 | 50267.08 | 29643.78 | 2616.29 | 0.00 | 130291.85 | 0.00 |
July | 399615.74 | 26-JUL-19:40 | 47387.53 | 86131.51 | 11632.50 | 50267.18 | 28071.61 | 3450.18 | 0.00 | 161986.58 | 0.00 |
August | 383925.79 | 03-AUG-19:19 | 46442.41 | 86131.51 | 0.00 | 50265.65 | 29865.16 | 3485.56 | 0.00 | 156859.73 | 0.00 |
September | 326455.32 | 07-SEP-18:10 | 40680.69 | 77265.07 | 0.00 | 50064.42 | 29746.28 | 2233.77 | 0.00 | 115234.29 | 0.00 |
October | 261011.68 | 20-OCT-19:40 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 30515.85 | 1689.85 | 0.00 | 27810.48 | 0.00 |
November | 241218.12 | 03-NOV-19:19 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 24705.75 | 1641.30 | 0.00 | 9020.19 | 0.00 |
December | 230137.94 | 06-DEC-20:19 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 23527.73 | 323.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 230137.94 | 39246.43 | 77265.07 | 0.00 | 50064.42 | 23315.24 | 323.58 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 399615.74 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 33249.69 | 3485.56 | 0.00 | 161986.58 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 416136.73 | 31-JAN-03:00 | 0.00 | 180182.51 | 31-JAN-21:19 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 444491.53 | 02-FEB-05:00 | 0.00 | 180940.81 | 02-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 154233.81 | 05-MAR-23:00 | 0.00 | 180289.18 | 01-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 92714.17 | 03-APR-08:20 | 0.00 | 179653.25 | 03-APR-20:49 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 21605.67 | 18-MAY-02:49 | 0.00 | 178645.42 | 01-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 16234.97 | 03-JUN-01:19 | 0.00 | 177362.16 | 01-JUN-20:49 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 7192.34 | 23-JUL-08:20 | 0.00 | 176219.95 | 03-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 4857.03 | 19-AUG-05:10 | 0.00 | 175594.64 | 01-AUG-20:19 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 31662.23 | 30-SEP-04:00 | 0.00 | 175937.60 | 29-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 36786.82 | 27-OCT-03:00 | 0.00 | 176951.85 | 31-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 388272.43 | 26-NOV-07:10 | 0.00 | 178174.56 | 30-NOV-21:00 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 248777.01 | 11-DEC-16:30 | 0.00 | 179311.35 | 29-DEC-21:19 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 4857.03 | 0.00 | 175594.64 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 444491.53 | 0.00 | 180940.81 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 217.67 | 24.81 | 217.67 | 24.81 |
February | 64.00 | 19.31 | 64.00 | 19.31 | 80.67 | 24.76 | 80.67 | 24.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 70.00 | 24.67 | 70.00 | 24.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 24.59 | 15.50 | 24.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 24.64 | 23.17 | 24.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 24.69 | 31.33 | 24.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 | 24.64 | 51.17 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 212.17 | 24.79 | 212.17 | 24.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 489.83 | 25.25 | 489.83 | 25.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 25.95 | 744.00 | 25.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 704.33 | 25.83 | 704.33 | 25.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 25.40 | 744.00 | 25.40 |
Annual Sum or Average | 64.00 | 19.31 | 64.00 | 19.31 | 3383.83 | 25.45 | 3383.83 | 25.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 24.59 | 15.50 | 24.59 |
Maximum of Months | 64.00 | 19.31 | 64.00 | 19.31 | 744.00 | 25.95 | 744.00 | 25.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 264.83 | 18.58 | 264.83 | 18.58 | 3.00 | 24.87 | 3.00 | 24.87 |
February | 131.00 | 15.58 | 131.00 | 15.58 | 13.67 | 25.50 | 13.67 | 25.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 25.04 | 16.33 | 25.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 25.31 | 33.67 | 25.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 24.79 | 12.67 | 24.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 91.17 | 24.96 | 91.17 | 24.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 107.67 | 24.88 | 107.67 | 24.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 147.00 | 25.01 | 147.00 | 25.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 162.17 | 25.57 | 162.17 | 25.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 89.17 | 25.74 | 89.17 | 25.74 |
November | 53.50 | 19.16 | 53.50 | 19.16 | 28.33 | 25.88 | 28.33 | 25.88 |
December | 119.00 | 18.96 | 119.00 | 18.96 | 15.17 | 25.36 | 15.17 | 25.36 |
Annual Sum or Average | 568.33 | 18.02 | 568.33 | 18.02 | 720.00 | 25.26 | 720.00 | 25.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.79 | 3.00 | 24.79 |
Maximum of Months | 264.83 | 19.16 | 264.83 | 19.16 | 162.17 | 25.88 | 162.17 | 25.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 69.50 | 18.99 | 69.50 | 18.99 | 3.17 | 24.68 | 3.17 | 24.68 |
February | 100.17 | 16.36 | 100.17 | 16.36 | 12.17 | 24.73 | 12.17 | 24.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 65.83 | 24.90 | 65.83 | 24.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 143.67 | 24.94 | 143.67 | 24.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 259.83 | 24.95 | 259.83 | 24.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 264.83 | 25.03 | 264.83 | 25.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 265.33 | 25.03 | 265.33 | 25.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 313.67 | 25.06 | 313.67 | 25.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 335.17 | 25.02 | 335.17 | 25.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 255.33 | 24.96 | 255.33 | 24.96 |
November | 5.50 | 20.01 | 5.50 | 20.01 | 102.83 | 24.94 | 102.83 | 24.94 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.61 | 1.33 | 24.61 |
Annual Sum or Average | 175.17 | 17.52 | 175.17 | 17.52 | 2023.17 | 25.00 | 2023.17 | 25.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.61 | 1.33 | 24.61 |
Maximum of Months | 100.17 | 20.01 | 100.17 | 20.01 | 335.17 | 25.06 | 335.17 | 25.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 67.17 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 138.83 | 16.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 24.67 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 | 24.67 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 89.00 | 24.76 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 92.50 | 24.75 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 96.17 | 24.78 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 69.67 | 24.74 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 24.64 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 24.63 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 206.00 | 17.68 | 0.00 | 434.17 | 24.74 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.83 | 19.37 | 0.00 | 0.00 | 96.17 | 24.78 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 167.17 | 18.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 152.67 | 15.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 24.64 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.60 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 24.63 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.57 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21.33 | 19.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14.33 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 355.50 | 17.60 | 0.00 | 29.00 | 24.63 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.17 | 20.36 | 0.00 | 0.00 | 18.00 | 24.64 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 437.83 | 27.28 | 437.83 | 27.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 458.17 | 27.05 | 458.17 | 27.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 601.83 | 27.11 | 601.83 | 27.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 583.00 | 27.00 | 583.00 | 27.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 619.00 | 26.79 | 619.00 | 26.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 616.50 | 26.52 | 616.50 | 26.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 650.83 | 26.27 | 650.83 | 26.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 641.17 | 26.44 | 641.17 | 26.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 612.00 | 26.76 | 612.00 | 26.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 615.67 | 27.24 | 615.67 | 27.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 552.17 | 27.17 | 552.17 | 27.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 525.83 | 27.19 | 525.83 | 27.19 |
Annual Sum or Average | 0.00 | 0.00 | 6914.00 | 26.88 | 6914.00 | 26.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 437.83 | 26.27 | 437.83 | 26.27 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 650.83 | 27.28 | 650.83 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 81.33 | 17.57 | 81.33 | 17.57 | 14.67 | 25.00 | 14.67 | 25.00 |
February | 83.33 | 14.80 | 83.33 | 14.80 | 36.00 | 25.32 | 36.00 | 25.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 85.83 | 24.97 | 85.83 | 24.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 169.00 | 24.97 | 169.00 | 24.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 236.83 | 24.90 | 236.83 | 24.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 290.50 | 25.00 | 290.50 | 25.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 305.67 | 24.98 | 305.67 | 24.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 365.67 | 25.09 | 365.67 | 25.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 378.00 | 25.23 | 378.00 | 25.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 300.83 | 25.30 | 300.83 | 25.30 |
November | 11.67 | 18.05 | 11.67 | 18.05 | 119.17 | 25.24 | 119.17 | 25.24 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 25.43 | 34.17 | 25.43 |
Annual Sum or Average | 176.33 | 16.29 | 176.33 | 16.29 | 2336.33 | 25.10 | 2336.33 | 25.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 24.90 | 14.67 | 24.90 |
Maximum of Months | 83.33 | 18.05 | 83.33 | 18.05 | 378.00 | 25.43 | 378.00 | 25.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.33 | 19.21 | 48.33 | 19.21 | 16.67 | 24.88 | 16.67 | 24.88 |
February | 85.00 | 16.75 | 85.00 | 16.75 | 77.50 | 24.82 | 77.50 | 24.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 205.67 | 25.00 | 205.67 | 25.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 291.83 | 25.09 | 291.83 | 25.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 392.67 | 25.18 | 392.67 | 25.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 371.33 | 25.19 | 371.33 | 25.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 365.50 | 25.13 | 365.50 | 25.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 390.83 | 25.23 | 390.83 | 25.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 449.67 | 25.21 | 449.67 | 25.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 483.83 | 25.16 | 483.83 | 25.16 |
November | 2.33 | 20.26 | 2.33 | 20.26 | 237.00 | 25.10 | 237.00 | 25.10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 24.79 | 47.67 | 24.79 |
Annual Sum or Average | 135.67 | 17.69 | 135.67 | 17.69 | 3330.17 | 25.14 | 3330.17 | 25.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 24.79 | 16.67 | 24.79 |
Maximum of Months | 85.00 | 20.26 | 85.00 | 20.26 | 483.83 | 25.23 | 483.83 | 25.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.00 | 20.28 | 11.00 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45.33 | 19.58 | 45.33 | 19.58 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.70 | 0.50 | 21.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.49 | 0.17 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.41 | 2.00 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 58.50 | 19.74 | 58.50 | 19.74 | 0.83 | 21.69 | 0.83 | 21.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.33 | 20.49 | 45.33 | 20.49 | 0.50 | 21.71 | 0.50 | 21.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.00 | 20.16 | 26.00 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 54.50 | 19.12 | 54.50 | 19.12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.90 | 0.67 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.71 | 1.83 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.80 | 3.00 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.74 | 0.67 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 20.50 | 0.83 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 20.36 | 2.33 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.67 | 19.49 | 83.67 | 19.49 | 6.17 | 21.78 | 6.17 | 21.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.50 | 20.50 | 54.50 | 20.50 | 3.00 | 21.90 | 3.00 | 21.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.17 | 19.98 | 50.17 | 19.98 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 63.67 | 18.81 | 63.67 | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 20.44 | 0.17 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.79 | 0.17 | 21.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.78 | 1.17 | 21.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 21.83 | 7.67 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 21.92 | 8.67 | 21.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.87 | 5.50 | 21.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.00 | 20.41 | 5.00 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.83 | 20.26 | 4.83 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.83 | 19.41 | 123.83 | 19.41 | 24.33 | 21.86 | 24.33 | 21.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.67 | 20.44 | 63.67 | 20.44 | 8.67 | 21.92 | 8.67 | 21.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.00 | 20.16 | 20.00 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50.50 | 19.17 | 50.50 | 19.17 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.51 | 0.67 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.39 | 2.67 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 73.83 | 19.49 | 73.83 | 19.49 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.50 | 20.51 | 50.50 | 20.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.33 | 20.01 | 34.33 | 20.01 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 60.00 | 18.78 | 60.00 | 18.78 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.12 | 0.33 | 22.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.43 | 0.50 | 22.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 22.53 | 3.67 | 22.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 22.45 | 6.50 | 22.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 22.30 | 3.83 | 22.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.15 | 1.50 | 22.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.46 | 1.17 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.31 | 2.67 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 98.17 | 19.27 | 98.17 | 19.27 | 16.33 | 22.40 | 16.33 | 22.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 60.00 | 20.46 | 60.00 | 20.46 | 6.50 | 22.53 | 6.50 | 22.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 581.33 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 375.50 | 18.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95.33 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 140.83 | 19.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 564.67 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1757.67 | 19.27 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 581.33 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 20.31 | 10.50 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38.67 | 19.78 | 38.67 | 19.78 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.82 | 0.33 | 21.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.86 | 0.17 | 21.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.70 | 0.67 | 21.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.81 | 0.83 | 21.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.46 | 0.17 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.36 | 2.00 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 51.33 | 19.91 | 51.33 | 19.91 | 2.83 | 21.76 | 2.83 | 21.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.67 | 20.46 | 38.67 | 20.46 | 0.83 | 21.86 | 0.83 | 21.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.83 | 20.17 | 27.83 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52.17 | 19.32 | 52.17 | 19.32 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.91 | 0.33 | 21.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.24 | 1.33 | 22.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.83 | 4.33 | 21.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 21.98 | 4.83 | 21.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.79 | 3.83 | 21.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.73 | 0.50 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.43 | 0.67 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 20.29 | 2.33 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 83.00 | 19.64 | 83.00 | 19.64 | 15.17 | 21.90 | 15.17 | 21.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.17 | 20.43 | 52.17 | 20.43 | 4.83 | 22.24 | 4.83 | 22.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.67 | 20.34 | 11.67 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24.50 | 19.83 | 24.50 | 19.83 | 0.17 | 21.70 | 0.17 | 21.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.69 | 0.33 | 21.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.74 | 1.50 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.82 | 2.50 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.89 | 2.00 | 21.89 |
November | 0.50 | 20.49 | 0.50 | 20.49 | 0.67 | 21.98 | 0.67 | 21.98 |
December | 2.83 | 20.35 | 2.83 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.50 | 20.03 | 39.50 | 20.03 | 8.00 | 21.82 | 8.00 | 21.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.50 | 20.49 | 24.50 | 20.49 | 2.50 | 21.98 | 2.50 | 21.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.83 | 17.84 | 62.83 | 17.84 | 243.17 | 25.23 | 243.17 | 25.23 |
February | 85.33 | 14.59 | 85.33 | 14.59 | 333.67 | 25.47 | 333.67 | 25.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 567.67 | 25.66 | 567.67 | 25.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 630.50 | 25.86 | 630.50 | 25.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 660.17 | 26.00 | 660.17 | 26.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 657.17 | 25.95 | 657.17 | 25.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 644.67 | 25.85 | 644.67 | 25.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 635.33 | 25.90 | 635.33 | 25.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 650.17 | 25.95 | 650.17 | 25.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 699.83 | 25.92 | 699.83 | 25.92 |
November | 8.83 | 19.34 | 8.83 | 19.34 | 508.00 | 25.70 | 508.00 | 25.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 372.33 | 25.34 | 372.33 | 25.34 |
Annual Sum or Average | 157.00 | 16.16 | 157.00 | 16.16 | 6602.67 | 25.80 | 6602.67 | 25.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 243.17 | 25.23 | 243.17 | 25.23 |
Maximum of Months | 85.33 | 19.34 | 85.33 | 19.34 | 699.83 | 26.00 | 699.83 | 26.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.83 | 17.98 | 46.83 | 17.98 | 394.00 | 25.46 | 394.00 | 25.46 |
February | 82.83 | 15.44 | 82.83 | 15.44 | 449.67 | 25.78 | 449.67 | 25.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 686.50 | 26.01 | 686.50 | 26.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 707.33 | 26.23 | 707.33 | 26.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 724.67 | 26.29 | 724.67 | 26.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 705.00 | 26.24 | 705.00 | 26.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 713.17 | 26.05 | 713.17 | 26.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 702.33 | 26.12 | 702.33 | 26.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 695.67 | 26.26 | 695.67 | 26.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 731.33 | 26.37 | 731.33 | 26.37 |
November | 6.33 | 19.87 | 6.33 | 19.87 | 630.00 | 26.00 | 630.00 | 26.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 535.83 | 25.62 | 535.83 | 25.62 |
Annual Sum or Average | 136.00 | 16.52 | 136.00 | 16.52 | 7675.50 | 26.08 | 7675.50 | 26.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 394.00 | 25.46 | 394.00 | 25.46 |
Maximum of Months | 82.83 | 19.87 | 82.83 | 19.87 | 731.33 | 26.37 | 731.33 | 26.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 604.67 | 29.01 | 604.67 | 29.01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 566.67 | 29.30 | 566.67 | 29.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 735.50 | 29.56 | 735.50 | 29.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 719.67 | 29.68 | 719.67 | 29.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.52 | 744.00 | 29.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 29.38 | 720.00 | 29.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.09 | 744.00 | 29.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.16 | 744.00 | 29.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 29.55 | 720.00 | 29.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.90 | 744.00 | 29.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 703.00 | 29.44 | 703.00 | 29.44 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 716.67 | 29.03 | 716.67 | 29.03 |
Annual Sum or Average | 0.00 | 0.00 | 8462.17 | 29.39 | 8462.17 | 29.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 566.67 | 29.01 | 566.67 | 29.01 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.90 | 744.00 | 29.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 303.00 | 19.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 155.33 | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 24.70 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 24.88 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 179.17 | 25.03 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 240.33 | 24.98 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 188.83 | 24.91 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 117.00 | 24.97 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 56.33 | 19.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 108.83 | 19.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 623.50 | 18.11 | 0.00 | 769.17 | 24.96 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 303.00 | 19.63 | 0.00 | 0.00 | 240.33 | 25.03 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 382.00 | 23.74 | 53.00 | 24.86 | 0.83 | 21.04 |
February | 386.33 | 22.67 | 107.00 | 20.28 | 98.33 | 19.87 |
March | 413.17 | 24.04 | 6.33 | 24.59 | 0.00 | 0.00 |
April | 442.33 | 23.98 | 17.17 | 24.05 | 0.00 | 0.00 |
May | 181.00 | 23.93 | 191.83 | 24.12 | 11.33 | 24.00 |
June | 3.83 | 23.87 | 443.17 | 24.19 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 608.50 | 24.18 | 0.00 | 0.00 |
August | 0.67 | 24.51 | 709.67 | 24.35 | 0.67 | 24.51 |
September | 0.00 | 0.00 | 663.67 | 24.99 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 744.00 | 25.95 | 0.00 | 0.00 |
November | 10.33 | 24.06 | 667.83 | 25.88 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 559.17 | 25.51 | 0.00 | 0.00 |
Annual Sum or Average | 1819.67 | 23.66 | 4771.33 | 24.91 | 111.17 | 20.33 |
Minimum of Months | 0.00 | 0.00 | 6.33 | 20.28 | 0.00 | 0.00 |
Maximum of Months | 442.33 | 24.51 | 744.00 | 25.95 | 98.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 724.50 | 20.21 | 555.83 | 19.85 | 550.00 | 19.80 |
February | 634.50 | 20.20 | 297.17 | 18.82 | 281.33 | 18.45 |
March | 634.00 | 21.71 | 173.00 | 21.62 | 143.17 | 20.98 |
April | 510.00 | 22.18 | 121.83 | 24.08 | 21.50 | 22.63 |
May | 195.50 | 23.25 | 338.33 | 24.05 | 16.83 | 23.83 |
June | 83.17 | 23.26 | 565.50 | 24.21 | 16.00 | 23.94 |
July | 35.67 | 23.94 | 725.67 | 24.19 | 34.00 | 23.96 |
August | 53.50 | 24.13 | 709.83 | 24.27 | 49.50 | 24.18 |
September | 244.50 | 23.66 | 384.00 | 24.72 | 46.00 | 26.54 |
October | 481.50 | 22.91 | 124.33 | 25.29 | 21.83 | 26.73 |
November | 614.50 | 21.59 | 209.00 | 21.22 | 185.17 | 20.71 |
December | 699.00 | 20.84 | 404.67 | 20.52 | 390.50 | 20.36 |
Annual Sum or Average | 4910.33 | 21.55 | 4609.17 | 22.84 | 1755.83 | 20.48 |
Minimum of Months | 35.67 | 20.20 | 121.83 | 18.82 | 16.00 | 18.45 |
Maximum of Months | 724.50 | 24.13 | 725.67 | 25.29 | 550.00 | 26.73 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 726.83 | 22.15 | 118.17 | 19.85 | 116.67 | 19.79 |
February | 590.50 | 22.06 | 138.17 | 17.76 | 133.17 | 17.49 |
March | 465.17 | 23.51 | 90.33 | 24.71 | 0.00 | 0.00 |
April | 249.17 | 23.74 | 231.50 | 24.63 | 0.00 | 0.00 |
May | 28.83 | 24.27 | 581.50 | 24.52 | 15.00 | 24.52 |
June | 7.17 | 24.65 | 659.83 | 24.52 | 7.17 | 24.65 |
July | 13.33 | 24.81 | 742.33 | 24.47 | 13.33 | 24.81 |
August | 36.50 | 24.91 | 729.67 | 24.55 | 36.50 | 24.91 |
September | 37.83 | 24.27 | 543.67 | 24.72 | 10.17 | 24.91 |
October | 88.50 | 23.99 | 289.00 | 24.85 | 0.00 | 0.00 |
November | 430.17 | 23.25 | 157.67 | 24.36 | 15.00 | 20.61 |
December | 712.00 | 23.06 | 16.83 | 21.01 | 16.83 | 21.01 |
Annual Sum or Average | 3386.00 | 22.90 | 4298.67 | 24.21 | 363.83 | 20.17 |
Minimum of Months | 7.17 | 22.06 | 16.83 | 17.76 | 0.00 | 0.00 |
Maximum of Months | 726.83 | 24.91 | 742.33 | 24.85 | 133.17 | 24.91 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 346.17 | 27.96 | 732.50 | 26.14 | 346.17 | 27.96 |
February | 349.83 | 27.79 | 647.17 | 26.29 | 349.83 | 27.79 |
March | 504.83 | 27.57 | 744.00 | 26.60 | 504.83 | 27.57 |
April | 563.67 | 27.08 | 720.00 | 26.52 | 563.67 | 27.08 |
May | 690.50 | 26.55 | 744.00 | 26.40 | 690.50 | 26.55 |
June | 703.50 | 26.27 | 720.00 | 26.23 | 703.50 | 26.27 |
July | 740.00 | 26.06 | 744.00 | 26.05 | 740.00 | 26.06 |
August | 736.33 | 26.19 | 744.00 | 26.17 | 736.33 | 26.19 |
September | 668.00 | 26.57 | 720.00 | 26.42 | 668.00 | 26.57 |
October | 635.00 | 27.16 | 744.00 | 26.76 | 635.00 | 27.16 |
November | 488.17 | 27.49 | 720.00 | 26.54 | 488.17 | 27.49 |
December | 393.83 | 28.02 | 744.00 | 26.38 | 393.83 | 28.02 |
Annual Sum or Average | 6819.83 | 26.89 | 8723.67 | 26.37 | 6819.83 | 26.89 |
Minimum of Months | 346.17 | 26.06 | 647.17 | 26.05 | 346.17 | 26.06 |
Maximum of Months | 740.00 | 28.02 | 744.00 | 26.76 | 740.00 | 28.02 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 690.67 | 21.32 | 229.33 | 20.14 | 208.83 | 19.68 |
February | 547.83 | 21.32 | 176.00 | 19.28 | 130.50 | 17.36 |
March | 454.50 | 22.75 | 159.67 | 24.63 | 1.17 | 23.18 |
April | 315.83 | 23.03 | 293.50 | 24.64 | 28.17 | 24.89 |
May | 170.50 | 24.44 | 596.17 | 24.35 | 151.83 | 24.59 |
June | 283.67 | 24.67 | 674.33 | 24.46 | 266.50 | 24.79 |
July | 377.17 | 24.71 | 731.50 | 24.42 | 371.17 | 24.75 |
August | 352.00 | 24.88 | 735.83 | 24.55 | 351.67 | 24.88 |
September | 215.50 | 24.84 | 587.67 | 24.84 | 162.33 | 25.38 |
October | 196.00 | 24.02 | 428.33 | 24.98 | 52.00 | 26.15 |
November | 475.83 | 22.63 | 211.67 | 24.08 | 67.33 | 22.63 |
December | 660.50 | 22.26 | 162.00 | 22.17 | 120.00 | 21.19 |
Annual Sum or Average | 4740.00 | 22.95 | 4986.00 | 24.09 | 1911.50 | 23.50 |
Minimum of Months | 170.50 | 21.32 | 159.67 | 19.28 | 1.17 | 17.36 |
Maximum of Months | 690.67 | 24.88 | 735.83 | 24.98 | 371.17 | 26.15 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 657.83 | 22.69 | 91.50 | 20.90 | 70.50 | 19.75 |
February | 404.83 | 21.86 | 200.33 | 20.80 | 114.67 | 17.84 |
March | 241.17 | 23.63 | 237.00 | 24.89 | 0.00 | 0.00 |
April | 89.50 | 23.80 | 410.17 | 24.83 | 12.17 | 24.92 |
May | 135.67 | 25.05 | 649.00 | 24.75 | 135.67 | 25.05 |
June | 229.50 | 25.10 | 710.67 | 24.68 | 229.50 | 25.10 |
July | 331.50 | 25.05 | 744.00 | 24.62 | 331.50 | 25.05 |
August | 308.00 | 25.17 | 737.00 | 24.72 | 308.00 | 25.17 |
September | 102.83 | 25.25 | 633.17 | 24.92 | 102.83 | 25.25 |
October | 6.83 | 25.21 | 572.33 | 25.01 | 6.83 | 25.21 |
November | 257.50 | 23.40 | 300.17 | 24.85 | 19.67 | 24.11 |
December | 506.67 | 23.34 | 38.83 | 24.60 | 2.00 | 21.02 |
Annual Sum or Average | 3271.83 | 23.67 | 5324.17 | 24.57 | 1333.33 | 24.18 |
Minimum of Months | 6.83 | 21.86 | 38.83 | 20.80 | 0.00 | 0.00 |
Maximum of Months | 657.83 | 25.25 | 744.00 | 25.01 | 331.50 | 25.25 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.46 | 714.83 | 20.43 | 714.83 | 20.43 |
February | 672.00 | 20.52 | 550.67 | 20.36 | 550.67 | 20.36 |
March | 744.00 | 20.92 | 402.00 | 20.59 | 402.00 | 20.59 |
April | 698.50 | 21.17 | 148.83 | 20.51 | 146.50 | 20.45 |
May | 721.00 | 21.54 | 9.50 | 21.54 | 9.50 | 21.54 |
June | 643.00 | 21.51 | 21.17 | 22.61 | 11.83 | 22.35 |
July | 630.50 | 21.51 | 32.33 | 22.71 | 13.83 | 22.34 |
August | 639.50 | 21.52 | 32.83 | 22.58 | 23.33 | 22.40 |
September | 660.33 | 21.45 | 12.50 | 21.17 | 11.17 | 20.98 |
October | 740.00 | 21.29 | 62.17 | 20.66 | 62.17 | 20.66 |
November | 719.67 | 20.80 | 424.33 | 20.53 | 424.33 | 20.53 |
December | 744.00 | 20.56 | 698.50 | 20.52 | 698.50 | 20.52 |
Annual Sum or Average | 8356.50 | 21.09 | 3109.67 | 20.55 | 3068.67 | 20.52 |
Minimum of Months | 630.50 | 20.46 | 9.50 | 20.36 | 9.50 | 20.36 |
Maximum of Months | 744.00 | 21.54 | 714.83 | 22.71 | 714.83 | 22.40 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.38 | 743.33 | 20.38 | 743.33 | 20.38 |
February | 672.00 | 20.32 | 632.83 | 20.27 | 632.83 | 20.27 |
March | 744.00 | 20.72 | 468.83 | 20.46 | 468.83 | 20.46 |
April | 691.67 | 21.10 | 200.00 | 20.76 | 188.33 | 20.49 |
May | 682.33 | 21.64 | 62.17 | 24.25 | 25.17 | 22.87 |
June | 593.33 | 21.91 | 125.17 | 24.65 | 62.67 | 24.49 |
July | 592.00 | 22.39 | 188.67 | 25.07 | 124.17 | 25.05 |
August | 601.17 | 22.18 | 183.00 | 24.52 | 118.50 | 24.25 |
September | 634.33 | 21.55 | 71.17 | 23.58 | 31.67 | 21.58 |
October | 741.00 | 21.05 | 166.00 | 20.51 | 166.00 | 20.51 |
November | 720.00 | 20.64 | 478.67 | 20.43 | 478.67 | 20.43 |
December | 744.00 | 20.43 | 743.00 | 20.43 | 743.00 | 20.43 |
Annual Sum or Average | 8159.83 | 21.14 | 4062.83 | 21.06 | 3783.17 | 20.77 |
Minimum of Months | 592.00 | 20.32 | 62.17 | 20.27 | 25.17 | 20.27 |
Maximum of Months | 744.00 | 22.39 | 743.33 | 25.07 | 743.33 | 25.05 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.50 | 589.50 | 20.34 | 589.50 | 20.34 |
February | 672.00 | 20.51 | 360.67 | 20.03 | 360.67 | 20.03 |
March | 744.00 | 20.99 | 182.17 | 20.50 | 182.17 | 20.50 |
April | 719.33 | 21.30 | 28.33 | 20.74 | 28.33 | 20.74 |
May | 737.50 | 21.68 | 12.33 | 23.05 | 12.17 | 23.04 |
June | 697.83 | 21.97 | 47.33 | 23.30 | 46.83 | 23.29 |
July | 705.00 | 22.18 | 114.50 | 23.63 | 98.83 | 23.54 |
August | 729.00 | 22.12 | 94.00 | 23.25 | 90.50 | 23.20 |
September | 714.00 | 21.71 | 2.50 | 23.02 | 2.33 | 22.94 |
October | 744.00 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 720.00 | 20.93 | 227.00 | 20.44 | 227.00 | 20.44 |
December | 744.00 | 20.65 | 536.17 | 20.47 | 536.17 | 20.47 |
Annual Sum or Average | 8670.67 | 21.31 | 2194.50 | 20.73 | 2174.50 | 20.70 |
Minimum of Months | 672.00 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.18 | 589.50 | 23.63 | 589.50 | 23.54 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.44 | 713.33 | 20.41 | 713.33 | 20.41 |
February | 672.00 | 20.48 | 556.83 | 20.34 | 556.83 | 20.34 |
March | 744.00 | 20.99 | 378.50 | 20.66 | 378.50 | 20.66 |
April | 703.83 | 21.22 | 168.33 | 20.54 | 167.50 | 20.53 |
May | 730.00 | 21.66 | 6.83 | 21.67 | 6.00 | 21.49 |
June | 644.00 | 21.56 | 11.33 | 22.52 | 5.50 | 22.04 |
July | 623.17 | 21.52 | 20.00 | 22.63 | 10.17 | 22.37 |
August | 645.33 | 21.57 | 24.33 | 22.49 | 20.50 | 22.40 |
September | 661.83 | 21.51 | 6.50 | 21.53 | 5.00 | 21.17 |
October | 744.00 | 21.34 | 49.67 | 20.88 | 49.67 | 20.88 |
November | 720.00 | 20.80 | 429.00 | 20.51 | 429.00 | 20.51 |
December | 744.00 | 20.54 | 694.67 | 20.50 | 694.67 | 20.50 |
Annual Sum or Average | 8376.17 | 21.12 | 3059.33 | 20.52 | 3036.67 | 20.50 |
Minimum of Months | 623.17 | 20.44 | 6.50 | 20.34 | 5.00 | 20.34 |
Maximum of Months | 744.00 | 21.66 | 713.33 | 22.63 | 713.33 | 22.40 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.35 | 740.00 | 20.35 | 740.00 | 20.35 |
February | 672.00 | 20.27 | 632.50 | 20.22 | 632.50 | 20.22 |
March | 744.00 | 20.77 | 452.83 | 20.53 | 452.83 | 20.53 |
April | 705.50 | 21.17 | 198.00 | 20.65 | 194.83 | 20.59 |
May | 715.00 | 21.80 | 31.33 | 23.28 | 22.17 | 22.88 |
June | 588.83 | 21.88 | 85.00 | 24.33 | 49.50 | 24.09 |
July | 554.50 | 22.14 | 172.83 | 24.31 | 105.00 | 24.16 |
August | 619.00 | 22.09 | 140.00 | 23.75 | 101.17 | 23.49 |
September | 675.17 | 21.72 | 24.50 | 23.18 | 11.67 | 21.74 |
October | 744.00 | 21.07 | 125.33 | 20.75 | 125.33 | 20.75 |
November | 720.00 | 20.63 | 475.50 | 20.42 | 475.50 | 20.42 |
December | 744.00 | 20.42 | 738.00 | 20.42 | 738.00 | 20.42 |
Annual Sum or Average | 8226.00 | 21.15 | 3815.83 | 20.84 | 3648.50 | 20.67 |
Minimum of Months | 554.50 | 20.27 | 24.50 | 20.22 | 11.67 | 20.22 |
Maximum of Months | 744.00 | 22.14 | 740.00 | 24.33 | 740.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.43 | 731.33 | 20.42 | 731.33 | 20.42 |
February | 672.00 | 20.51 | 595.17 | 20.41 | 595.17 | 20.41 |
March | 743.17 | 20.83 | 480.00 | 20.56 | 480.00 | 20.56 |
April | 692.83 | 21.11 | 227.33 | 20.63 | 218.33 | 20.51 |
May | 699.50 | 21.51 | 20.50 | 21.79 | 15.00 | 21.36 |
June | 613.67 | 21.43 | 39.17 | 22.75 | 12.83 | 22.21 |
July | 601.33 | 21.43 | 56.33 | 22.81 | 18.50 | 22.38 |
August | 610.17 | 21.43 | 53.00 | 22.56 | 27.50 | 22.11 |
September | 646.33 | 21.38 | 41.50 | 21.30 | 31.83 | 20.75 |
October | 739.17 | 21.21 | 168.50 | 20.75 | 168.50 | 20.75 |
November | 718.83 | 20.72 | 478.67 | 20.49 | 478.67 | 20.49 |
December | 744.00 | 20.51 | 721.00 | 20.48 | 721.00 | 20.48 |
Annual Sum or Average | 8225.00 | 21.02 | 3612.50 | 20.60 | 3498.67 | 20.52 |
Minimum of Months | 601.33 | 20.43 | 20.50 | 20.41 | 12.83 | 20.41 |
Maximum of Months | 744.00 | 21.51 | 731.33 | 22.81 | 731.33 | 22.38 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.36 | 744.00 | 20.36 | 744.00 | 20.36 |
February | 672.00 | 20.31 | 649.83 | 20.29 | 649.83 | 20.29 |
March | 744.00 | 20.65 | 537.33 | 20.46 | 537.33 | 20.46 |
April | 688.83 | 21.07 | 282.83 | 20.88 | 264.83 | 20.62 |
May | 664.50 | 21.72 | 86.83 | 24.48 | 42.50 | 23.73 |
June | 574.33 | 22.04 | 144.67 | 25.04 | 79.33 | 25.43 |
July | 577.67 | 22.63 | 209.67 | 25.51 | 145.17 | 25.84 |
August | 581.50 | 22.33 | 197.17 | 24.97 | 133.83 | 24.94 |
September | 618.50 | 21.52 | 110.50 | 23.32 | 57.67 | 21.75 |
October | 739.83 | 20.95 | 317.17 | 20.60 | 317.17 | 20.60 |
November | 720.00 | 20.58 | 545.33 | 20.43 | 545.33 | 20.43 |
December | 744.00 | 20.41 | 744.00 | 20.41 | 744.00 | 20.41 |
Annual Sum or Average | 8069.17 | 21.15 | 4569.33 | 21.16 | 4261.00 | 20.89 |
Minimum of Months | 574.33 | 20.31 | 86.83 | 20.29 | 42.50 | 20.29 |
Maximum of Months | 744.00 | 22.63 | 744.00 | 25.51 | 744.00 | 25.84 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.67 | 20.85 | 576.83 | 20.60 | 576.83 | 20.60 |
February | 660.67 | 20.94 | 355.50 | 20.52 | 355.50 | 20.52 |
March | 735.17 | 21.19 | 234.83 | 20.67 | 234.83 | 20.67 |
April | 696.00 | 21.26 | 108.17 | 20.50 | 106.67 | 20.46 |
May | 720.17 | 21.60 | 16.00 | 22.14 | 16.00 | 22.14 |
June | 660.67 | 21.57 | 27.00 | 22.16 | 27.00 | 22.16 |
July | 643.17 | 21.53 | 42.33 | 22.42 | 42.33 | 22.42 |
August | 646.00 | 21.52 | 47.33 | 22.21 | 47.33 | 22.21 |
September | 640.67 | 21.46 | 27.33 | 23.08 | 4.17 | 21.86 |
October | 687.17 | 21.37 | 8.50 | 21.82 | 4.83 | 20.67 |
November | 704.00 | 21.07 | 287.50 | 20.61 | 286.00 | 20.60 |
December | 736.00 | 20.90 | 524.00 | 20.59 | 524.00 | 20.59 |
Annual Sum or Average | 8272.33 | 21.26 | 2255.33 | 20.72 | 2225.50 | 20.69 |
Minimum of Months | 640.67 | 20.85 | 8.50 | 20.50 | 4.17 | 20.46 |
Maximum of Months | 742.67 | 21.60 | 576.83 | 23.08 | 576.83 | 22.42 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 451.17 | 22.61 | 242.33 | 23.11 | 83.33 | 18.67 |
February | 235.83 | 20.13 | 409.50 | 23.04 | 106.33 | 15.92 |
March | 110.83 | 25.02 | 549.00 | 25.67 | 42.50 | 26.76 |
April | 125.83 | 26.50 | 666.50 | 25.78 | 121.17 | 26.59 |
May | 326.67 | 26.48 | 744.00 | 25.81 | 326.67 | 26.48 |
June | 407.50 | 26.36 | 720.00 | 25.81 | 407.50 | 26.36 |
July | 452.00 | 26.16 | 744.00 | 25.64 | 452.00 | 26.16 |
August | 434.83 | 26.26 | 744.00 | 25.67 | 434.83 | 26.26 |
September | 277.83 | 26.45 | 720.00 | 25.79 | 277.83 | 26.45 |
October | 104.00 | 26.92 | 734.50 | 25.84 | 104.00 | 26.92 |
November | 189.67 | 24.54 | 498.00 | 25.61 | 76.33 | 25.84 |
December | 289.50 | 23.77 | 309.50 | 25.45 | 0.00 | 0.00 |
Annual Sum or Average | 3405.67 | 25.07 | 7081.33 | 25.48 | 2432.50 | 25.64 |
Minimum of Months | 104.00 | 20.13 | 242.33 | 23.04 | 0.00 | 0.00 |
Maximum of Months | 452.00 | 26.92 | 744.00 | 25.84 | 452.00 | 26.92 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 268.83 | 22.46 | 399.83 | 24.58 | 62.67 | 19.55 |
February | 180.17 | 20.36 | 542.17 | 24.13 | 124.33 | 18.99 |
March | 150.33 | 26.98 | 680.17 | 26.02 | 150.33 | 26.98 |
April | 307.17 | 26.85 | 714.33 | 26.21 | 307.17 | 26.85 |
May | 476.33 | 26.75 | 744.00 | 26.25 | 476.33 | 26.75 |
June | 548.50 | 26.52 | 720.00 | 26.20 | 548.50 | 26.52 |
July | 529.67 | 26.39 | 744.00 | 25.98 | 529.67 | 26.39 |
August | 517.00 | 26.47 | 744.00 | 26.02 | 517.00 | 26.47 |
September | 447.17 | 26.67 | 720.00 | 26.19 | 447.17 | 26.67 |
October | 318.50 | 27.01 | 744.00 | 26.33 | 318.50 | 27.01 |
November | 210.33 | 26.08 | 625.50 | 25.95 | 172.00 | 26.67 |
December | 69.33 | 24.21 | 491.50 | 25.69 | 6.50 | 27.00 |
Annual Sum or Average | 4023.33 | 26.01 | 7869.50 | 25.89 | 3660.17 | 26.26 |
Minimum of Months | 69.33 | 20.36 | 399.83 | 24.13 | 6.50 | 18.99 |
Maximum of Months | 548.50 | 27.01 | 744.00 | 26.33 | 548.50 | 27.01 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 607.33 | 28.91 | 728.83 | 28.21 | 597.67 | 29.03 |
February | 610.50 | 28.80 | 649.17 | 28.67 | 588.83 | 29.09 |
March | 699.17 | 29.80 | 744.00 | 29.50 | 699.17 | 29.80 |
April | 714.17 | 29.71 | 720.00 | 29.67 | 714.17 | 29.71 |
May | 744.00 | 29.52 | 744.00 | 29.52 | 744.00 | 29.52 |
June | 720.00 | 29.38 | 720.00 | 29.38 | 720.00 | 29.38 |
July | 744.00 | 29.09 | 744.00 | 29.09 | 744.00 | 29.09 |
August | 744.00 | 29.16 | 744.00 | 29.16 | 744.00 | 29.16 |
September | 720.00 | 29.55 | 720.00 | 29.55 | 720.00 | 29.55 |
October | 744.00 | 29.90 | 744.00 | 29.90 | 744.00 | 29.90 |
November | 674.67 | 29.62 | 719.83 | 29.32 | 674.67 | 29.62 |
December | 645.00 | 29.48 | 744.00 | 28.86 | 645.00 | 29.48 |
Annual Sum or Average | 8366.83 | 29.42 | 8721.83 | 29.24 | 8335.50 | 29.45 |
Minimum of Months | 607.33 | 28.80 | 649.17 | 28.21 | 588.83 | 29.03 |
Maximum of Months | 744.00 | 29.90 | 744.00 | 29.90 | 744.00 | 29.90 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.17911 | 22.29069 | 0.23654 | 6.91934 |
February | 672.00000 | 23.43560 | 25.84893 | 0.07633 | 8.88983 |
March | 744.00000 | 24.15991 | 30.61543 | 0.27443 | 6.67171 |
April | 720.00000 | 24.03553 | 36.55492 | 0.28037 | 6.72303 |
May | 744.00000 | 24.03284 | 46.35969 | -0.5689 | 11.92698 |
June | 720.00000 | 24.12439 | 51.75595 | -0.4832 | 9.97741 |
July | 744.00000 | 24.14650 | 53.99897 | -0.4452 | 9.22753 |
August | 744.00000 | 24.33193 | 52.34991 | -0.3777 | 8.17902 |
September | 720.00000 | 24.93786 | 42.27881 | -0.2406 | 6.70583 |
October | 744.00000 | 25.94636 | 31.52645 | 0.75086 | 17.02217 |
November | 720.00000 | 25.79359 | 28.86322 | 0.69196 | 15.53642 |
December | 744.00000 | 25.40056 | 24.19600 | 0.55252 | 11.56852 |
Annual Sum or Average | 8760.00000 | 24.55083 | 37.28441 | 0.06217 | 9.95663 |
Minimum of Months | 672.00000 | 23.43560 | 22.29069 | -0.5689 | 6.67171 |
Maximum of Months | 744.00000 | 25.94636 | 53.99897 | 0.75086 | 17.02217 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.31444 | 23.25381 | -0.7408 | 20.25809 |
February | 672.00000 | 20.44116 | 26.47629 | -0.6434 | 20.21697 |
March | 744.00000 | 22.08219 | 32.31222 | -0.2039 | 8.48063 |
April | 720.00000 | 22.76579 | 37.30741 | 0.02630 | 8.17676 |
May | 744.00000 | 23.80645 | 46.68000 | -0.5470 | 12.33336 |
June | 720.00000 | 24.07176 | 52.25733 | -0.3721 | 8.97089 |
July | 744.00000 | 24.18061 | 55.03732 | -0.2912 | 7.26697 |
August | 744.00000 | 24.25067 | 53.72897 | -0.2747 | 7.36699 |
September | 720.00000 | 24.10514 | 43.69342 | -0.4249 | 13.18109 |
October | 744.00000 | 23.42932 | 35.38968 | 0.19131 | 8.05175 |
November | 720.00000 | 21.98233 | 33.23417 | -0.2289 | 10.65161 |
December | 744.00000 | 21.05871 | 27.33073 | -0.5354 | 14.27436 |
Annual Sum or Average | 8760.00000 | 22.72027 | 38.96389 | -0.3355 | 11.54653 |
Minimum of Months | 672.00000 | 20.31444 | 23.25381 | -0.7408 | 7.26697 |
Maximum of Months | 744.00000 | 24.25067 | 55.03732 | 0.19131 | 20.25809 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.19936 | 26.00900 | -0.2268 | 8.58672 |
February | 672.00000 | 22.31992 | 28.06386 | -0.1717 | 14.13866 |
March | 744.00000 | 23.82114 | 32.74079 | 0.22400 | 6.68637 |
April | 720.00000 | 24.16961 | 36.84581 | 0.35678 | 8.19294 |
May | 744.00000 | 24.42904 | 45.81568 | -0.3558 | 8.14007 |
June | 720.00000 | 24.48117 | 51.51286 | -0.2769 | 7.15137 |
July | 744.00000 | 24.47129 | 54.19211 | -0.2500 | 6.79662 |
August | 744.00000 | 24.53753 | 53.22330 | -0.2361 | 6.72216 |
September | 720.00000 | 24.57475 | 43.91723 | -0.3082 | 7.78551 |
October | 744.00000 | 24.42781 | 34.84642 | 0.41495 | 8.89649 |
November | 720.00000 | 23.73873 | 33.48876 | 0.21324 | 7.56367 |
December | 744.00000 | 23.11238 | 29.40674 | 0.01133 | 6.01742 |
Annual Sum or Average | 8760.00000 | 23.86532 | 39.23831 | -0.0499 | 8.01071 |
Minimum of Months | 672.00000 | 22.19936 | 26.00900 | -0.3558 | 6.01742 |
Maximum of Months | 744.00000 | 24.57475 | 54.19211 | 0.41495 | 14.13866 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 26.10939 | 15.43268 | 1.18368 | 35.40194 |
February | 672.00000 | 26.20883 | 18.02128 | 1.24101 | 37.56053 |
March | 744.00000 | 26.59589 | 22.57100 | 1.40972 | 43.70682 |
April | 720.00000 | 26.51631 | 27.31384 | 1.45422 | 45.68020 |
May | 744.00000 | 26.39808 | 36.29885 | 1.12578 | 33.04350 |
June | 720.00000 | 26.22563 | 41.78087 | 1.14389 | 33.20591 |
July | 744.00000 | 26.05098 | 44.50220 | 1.11759 | 32.24302 |
August | 744.00000 | 26.17196 | 43.51746 | 1.15390 | 33.30013 |
September | 720.00000 | 26.41919 | 34.95590 | 1.12272 | 33.00391 |
October | 744.00000 | 26.76000 | 25.90725 | 1.50462 | 47.54242 |
November | 720.00000 | 26.53565 | 23.36066 | 1.39626 | 43.33264 |
December | 744.00000 | 26.38440 | 18.54306 | 1.29100 | 39.40158 |
Annual Sum or Average | 8760.00000 | 26.36532 | 29.41611 | 1.26202 | 38.11561 |
Minimum of Months | 672.00000 | 26.05098 | 15.43268 | 1.11759 | 32.24302 |
Maximum of Months | 744.00000 | 26.76000 | 44.50220 | 1.50462 | 47.54242 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.53716 | 29.81176 | -0.3707 | 12.03178 |
February | 672.00000 | 21.87036 | 32.03250 | -0.2334 | 15.70881 |
March | 744.00000 | 23.37921 | 37.52807 | 0.17322 | 7.75403 |
April | 720.00000 | 23.80796 | 41.94543 | 0.34060 | 9.44065 |
May | 744.00000 | 24.21767 | 51.16847 | -0.3148 | 7.80895 |
June | 720.00000 | 24.37843 | 56.81702 | -0.1729 | 6.66008 |
July | 744.00000 | 24.39470 | 59.58908 | -0.1224 | 6.09393 |
August | 744.00000 | 24.53028 | 58.34465 | -0.0823 | 6.05169 |
September | 720.00000 | 24.61352 | 48.53199 | -0.1586 | 8.26447 |
October | 744.00000 | 24.42259 | 39.71999 | 0.49898 | 11.65770 |
November | 720.00000 | 23.23326 | 38.37584 | 0.13835 | 9.31154 |
December | 744.00000 | 22.51261 | 33.75594 | -0.1170 | 8.21601 |
Annual Sum or Average | 8760.00000 | 23.58407 | 44.03966 | -0.0342 | 9.03613 |
Minimum of Months | 672.00000 | 21.53716 | 29.81176 | -0.3707 | 6.05169 |
Maximum of Months | 744.00000 | 24.61352 | 59.58908 | 0.49898 | 15.70881 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.87251 | 29.78431 | -0.0336 | 7.49835 |
February | 672.00000 | 22.86436 | 31.02546 | -0.0069 | 13.07022 |
March | 744.00000 | 24.22669 | 35.50500 | 0.36033 | 8.40425 |
April | 720.00000 | 24.47687 | 39.90437 | 0.47186 | 10.30214 |
May | 744.00000 | 24.66849 | 49.20374 | -0.2256 | 6.80323 |
June | 720.00000 | 24.67289 | 54.97311 | -0.1578 | 6.26726 |
July | 744.00000 | 24.62309 | 57.74073 | -0.1426 | 6.08100 |
August | 744.00000 | 24.71434 | 56.70600 | -0.1191 | 6.05949 |
September | 720.00000 | 24.82784 | 47.26970 | -0.1684 | 6.48613 |
October | 744.00000 | 24.81993 | 38.05524 | 0.55354 | 11.84986 |
November | 720.00000 | 24.17808 | 36.39910 | 0.35769 | 9.27995 |
December | 744.00000 | 23.64488 | 32.31899 | 0.17274 | 6.57165 |
Annual Sum or Average | 8760.00000 | 24.22340 | 42.47626 | 0.08888 | 8.18447 |
Minimum of Months | 672.00000 | 22.86436 | 29.78431 | -0.2256 | 6.05949 |
Maximum of Months | 744.00000 | 24.82784 | 57.74073 | 0.55354 | 13.07022 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.45986 | 28.00070 | -0.8041 | 19.32112 |
February | 672.00000 | 20.52315 | 32.07757 | -0.7248 | 17.42169 |
March | 744.00000 | 20.92074 | 38.22245 | -0.5339 | 11.91582 |
April | 720.00000 | 21.23580 | 43.65474 | -0.3585 | 9.11132 |
May | 744.00000 | 21.58545 | 53.56955 | -1.3028 | 41.43359 |
June | 720.00000 | 21.68776 | 56.22323 | -1.1793 | 35.77435 |
July | 744.00000 | 21.76750 | 57.43060 | -1.1056 | 32.42513 |
August | 744.00000 | 21.75602 | 57.58912 | -1.1276 | 33.41426 |
September | 720.00000 | 21.59072 | 50.31804 | -1.2980 | 41.63572 |
October | 744.00000 | 21.29605 | 44.08869 | -0.3583 | 8.41127 |
November | 720.00000 | 20.80104 | 40.15950 | -0.5759 | 13.09366 |
December | 744.00000 | 20.56105 | 31.93607 | -0.7410 | 17.25520 |
Annual Sum or Average | 8760.00000 | 21.18590 | 44.50627 | -0.8433 | 23.46775 |
Minimum of Months | 672.00000 | 20.45986 | 28.00070 | -1.3028 | 8.41127 |
Maximum of Months | 744.00000 | 21.76750 | 57.58912 | -0.3583 | 41.63572 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.37623 | 28.13710 | -0.8529 | 21.10359 |
February | 672.00000 | 20.32066 | 32.40988 | -0.7997 | 19.86466 |
March | 744.00000 | 20.72321 | 38.65226 | -0.5978 | 13.32624 |
April | 720.00000 | 21.22314 | 43.97290 | -0.3760 | 9.77493 |
May | 744.00000 | 21.88103 | 53.36806 | -1.2265 | 39.05873 |
June | 720.00000 | 22.28833 | 55.46230 | -1.0076 | 31.09616 |
July | 744.00000 | 22.73763 | 56.35824 | -0.8262 | 25.93353 |
August | 744.00000 | 22.55180 | 57.11648 | -0.9052 | 27.44031 |
September | 720.00000 | 21.87333 | 50.43261 | -1.2434 | 40.38192 |
October | 744.00000 | 21.05724 | 44.73656 | -0.4387 | 9.57181 |
November | 720.00000 | 20.63880 | 40.54950 | -0.6339 | 14.43928 |
December | 744.00000 | 20.42740 | 32.18757 | -0.7960 | 18.99368 |
Annual Sum or Average | 8760.00000 | 21.34816 | 44.51299 | -0.8087 | 22.58971 |
Minimum of Months | 672.00000 | 20.32066 | 28.13710 | -1.2434 | 9.57181 |
Maximum of Months | 744.00000 | 22.73763 | 57.11648 | -0.3760 | 40.38192 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.49803 | 32.31464 | -0.6942 | 15.88654 |
February | 672.00000 | 20.51462 | 35.92264 | -0.6551 | 15.38073 |
March | 744.00000 | 20.99190 | 41.58111 | -0.4754 | 10.04595 |
April | 720.00000 | 21.30082 | 46.08569 | -0.3422 | 8.02051 |
May | 744.00000 | 21.70229 | 52.49375 | -1.3119 | 41.63635 |
June | 720.00000 | 22.03159 | 56.18733 | -1.1490 | 34.31095 |
July | 744.00000 | 22.28001 | 59.05335 | -1.0415 | 29.95009 |
August | 744.00000 | 22.16212 | 58.44543 | -1.0938 | 31.88496 |
September | 720.00000 | 21.73171 | 51.26942 | -1.3154 | 41.93172 |
October | 744.00000 | 21.23225 | 46.42252 | -0.3622 | 7.87243 |
November | 720.00000 | 20.92840 | 42.83134 | -0.4901 | 10.62918 |
December | 744.00000 | 20.64800 | 36.33461 | -0.6277 | 13.72827 |
Annual Sum or Average | 8760.00000 | 21.34010 | 46.63851 | -0.7974 | 21.80431 |
Minimum of Months | 672.00000 | 20.49803 | 32.31464 | -1.3154 | 7.87243 |
Maximum of Months | 744.00000 | 22.28001 | 59.05335 | -0.3422 | 41.93172 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43703 | 28.00084 | -0.8075 | 19.47257 |
February | 672.00000 | 20.48334 | 32.05911 | -0.7355 | 17.86289 |
March | 744.00000 | 20.98871 | 38.03901 | -0.5174 | 11.54767 |
April | 720.00000 | 21.26721 | 43.42704 | -0.3619 | 9.14426 |
May | 744.00000 | 21.69065 | 52.20793 | -1.2666 | 39.71943 |
June | 720.00000 | 21.73012 | 55.24088 | -1.1669 | 35.22642 |
July | 744.00000 | 21.79253 | 56.74266 | -1.1054 | 32.42461 |
August | 744.00000 | 21.78777 | 56.86128 | -1.1275 | 33.40275 |
September | 720.00000 | 21.65096 | 49.61296 | -1.2795 | 40.73108 |
October | 744.00000 | 21.34425 | 43.95566 | -0.3504 | 8.27228 |
November | 720.00000 | 20.79505 | 40.18015 | -0.5780 | 13.14646 |
December | 744.00000 | 20.54327 | 31.95327 | -0.7448 | 17.36609 |
Annual Sum or Average | 8760.00000 | 21.21355 | 44.08785 | -0.8375 | 23.22185 |
Minimum of Months | 672.00000 | 20.43703 | 28.00084 | -1.2795 | 8.27228 |
Maximum of Months | 744.00000 | 21.79253 | 56.86128 | -0.3504 | 40.73108 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.35386 | 28.12979 | -0.8570 | 21.30630 |
February | 672.00000 | 20.26648 | 32.41447 | -0.8137 | 20.49114 |
March | 744.00000 | 20.77257 | 38.50102 | -0.5850 | 12.92814 |
April | 720.00000 | 21.22172 | 43.80792 | -0.3868 | 9.64948 |
May | 744.00000 | 21.87861 | 52.32596 | -1.2215 | 37.91018 |
June | 720.00000 | 22.22489 | 55.11603 | -1.0243 | 30.60943 |
July | 744.00000 | 22.55944 | 56.94256 | -0.8813 | 25.40774 |
August | 744.00000 | 22.37395 | 57.33980 | -0.9639 | 27.51693 |
September | 720.00000 | 21.84801 | 49.96472 | -1.2498 | 39.70261 |
October | 744.00000 | 21.07444 | 44.67485 | -0.4381 | 9.32093 |
November | 720.00000 | 20.62851 | 40.56536 | -0.6380 | 14.54489 |
December | 744.00000 | 20.42255 | 32.18911 | -0.7983 | 19.10503 |
Annual Sum or Average | 8760.00000 | 21.30864 | 44.39568 | -0.8215 | 22.37616 |
Minimum of Months | 672.00000 | 20.26648 | 28.12979 | -1.2498 | 9.32093 |
Maximum of Months | 744.00000 | 22.55944 | 57.33980 | -0.3868 | 39.70261 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.43121 | 28.05330 | -0.8538 | 21.06883 |
February | 672.00000 | 20.50812 | 32.15165 | -0.7599 | 18.45706 |
March | 744.00000 | 20.82871 | 38.41041 | -0.5856 | 13.30314 |
April | 720.00000 | 21.19193 | 43.72779 | -0.3827 | 9.87061 |
May | 744.00000 | 21.60914 | 53.19972 | -1.2903 | 41.08821 |
June | 720.00000 | 21.69300 | 55.91186 | -1.1632 | 35.31418 |
July | 744.00000 | 21.76698 | 57.37604 | -1.0879 | 31.88138 |
August | 744.00000 | 21.75152 | 57.72966 | -1.1162 | 33.11893 |
September | 720.00000 | 21.56472 | 50.46538 | -1.3116 | 42.56359 |
October | 744.00000 | 21.22668 | 44.24419 | -0.3944 | 9.15517 |
November | 720.00000 | 20.72216 | 40.33981 | -0.6287 | 14.55991 |
December | 744.00000 | 20.50781 | 32.02658 | -0.7946 | 19.00661 |
Annual Sum or Average | 8760.00000 | 21.15388 | 44.53651 | -0.8649 | 24.14613 |
Minimum of Months | 672.00000 | 20.43121 | 28.05330 | -1.3116 | 9.15517 |
Maximum of Months | 744.00000 | 21.76698 | 57.72966 | -0.3827 | 42.56359 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.36270 | 28.15729 | -0.9010 | 22.90124 |
February | 672.00000 | 20.31495 | 32.46744 | -0.8361 | 21.01638 |
March | 744.00000 | 20.65369 | 38.80721 | -0.6478 | 14.72633 |
April | 720.00000 | 21.20380 | 43.92763 | -0.3963 | 10.71092 |
May | 744.00000 | 22.00680 | 52.60590 | -1.1812 | 38.30006 |
June | 720.00000 | 22.41188 | 54.55539 | -0.9509 | 30.83382 |
July | 744.00000 | 22.90951 | 55.15345 | -0.7500 | 26.13052 |
August | 744.00000 | 22.69582 | 56.20447 | -0.8440 | 27.23132 |
September | 720.00000 | 21.90722 | 50.22347 | -1.2378 | 41.17423 |
October | 744.00000 | 20.96889 | 44.93759 | -0.4819 | 10.59446 |
November | 720.00000 | 20.57655 | 40.71088 | -0.6857 | 15.96873 |
December | 744.00000 | 20.41150 | 32.22204 | -0.8441 | 20.68677 |
Annual Sum or Average | 8760.00000 | 21.37556 | 44.22558 | -0.8128 | 23.36104 |
Minimum of Months | 672.00000 | 20.31495 | 28.15729 | -1.2378 | 10.59446 |
Maximum of Months | 744.00000 | 22.90951 | 56.20447 | -0.3963 | 41.17423 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.85895 | 34.67795 | -0.6270 | 14.69222 |
February | 672.00000 | 20.97969 | 38.40564 | -0.5338 | 12.64396 |
March | 744.00000 | 21.21767 | 44.25543 | -0.4112 | 9.92180 |
April | 720.00000 | 21.32986 | 48.87252 | -0.3155 | 8.49168 |
May | 744.00000 | 21.65111 | 56.01390 | -1.2845 | 40.62499 |
June | 720.00000 | 21.70892 | 58.75063 | -1.1983 | 36.59719 |
July | 744.00000 | 21.75757 | 60.30110 | -1.1456 | 34.19597 |
August | 744.00000 | 21.75116 | 59.46418 | -1.1523 | 34.56492 |
September | 720.00000 | 21.65613 | 52.97687 | -1.2598 | 39.97243 |
October | 744.00000 | 21.51920 | 48.86922 | -0.2441 | 7.43182 |
November | 720.00000 | 21.11840 | 45.94660 | -0.4368 | 10.58657 |
December | 744.00000 | 20.92924 | 38.66789 | -0.5744 | 13.68461 |
Annual Sum or Average | 8760.00000 | 21.37551 | 48.99040 | -0.7668 | 22.00568 |
Minimum of Months | 672.00000 | 20.85895 | 34.67795 | -1.2845 | 7.43182 |
Maximum of Months | 744.00000 | 21.75757 | 60.30110 | -0.2441 | 40.62499 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.57155 | 29.20844 | 0.10077 | 10.58034 |
February | 672.00000 | 23.40438 | 31.31251 | 0.10323 | 19.07132 |
March | 744.00000 | 25.29575 | 36.23331 | 0.62219 | 14.42881 |
April | 720.00000 | 25.66678 | 40.52600 | 0.79271 | 19.26938 |
May | 744.00000 | 25.81224 | 49.24787 | 0.24303 | 7.58536 |
June | 720.00000 | 25.80877 | 54.38873 | 0.32837 | 8.63552 |
July | 744.00000 | 25.64199 | 56.96894 | 0.30941 | 8.39501 |
August | 744.00000 | 25.66698 | 56.32593 | 0.29869 | 8.41226 |
September | 720.00000 | 25.78647 | 47.94106 | 0.21945 | 7.48194 |
October | 744.00000 | 25.82154 | 39.34306 | 0.81593 | 19.86568 |
November | 720.00000 | 25.11715 | 37.05222 | 0.58142 | 14.79567 |
December | 744.00000 | 24.61586 | 32.55528 | 0.37608 | 9.17784 |
Annual Sum or Average | 8760.00000 | 25.19425 | 42.65852 | 0.40082 | 12.25007 |
Minimum of Months | 672.00000 | 23.40438 | 29.20844 | 0.10077 | 7.48194 |
Maximum of Months | 744.00000 | 25.82154 | 56.96894 | 0.81593 | 19.86568 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.21194 | 28.15261 | 0.31060 | 12.34067 |
February | 672.00000 | 24.09565 | 30.22737 | 0.32640 | 21.55493 |
March | 744.00000 | 25.87619 | 34.93379 | 0.81565 | 20.22683 |
April | 720.00000 | 26.19558 | 39.21665 | 0.96560 | 25.50202 |
May | 744.00000 | 26.24607 | 47.83557 | 0.44769 | 10.53203 |
June | 720.00000 | 26.19750 | 52.92931 | 0.51325 | 11.92392 |
July | 744.00000 | 25.98357 | 55.54895 | 0.47564 | 11.19728 |
August | 744.00000 | 26.02182 | 54.88534 | 0.47078 | 11.26019 |
September | 720.00000 | 26.19215 | 46.61939 | 0.41257 | 9.99897 |
October | 744.00000 | 26.33244 | 38.07691 | 0.98297 | 26.09183 |
November | 720.00000 | 25.69591 | 35.75983 | 0.77299 | 20.04727 |
December | 744.00000 | 25.20986 | 31.26985 | 0.57908 | 13.25462 |
Annual Sum or Average | 8760.00000 | 25.69712 | 41.35319 | 0.59076 | 16.10879 |
Minimum of Months | 672.00000 | 24.09565 | 28.15261 | 0.31060 | 9.99897 |
Maximum of Months | 744.00000 | 26.33244 | 55.54895 | 0.98297 | 26.09183 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 28.08629 | 32.31102 | 1.88112 | 66.05582 |
February | 672.00000 | 28.41279 | 34.94782 | 2.01365 | 69.39435 |
March | 744.00000 | 29.50179 | 33.69454 | 2.33667 | 79.05669 |
April | 720.00000 | 29.67279 | 37.02809 | 2.46385 | 82.05996 |
May | 744.00000 | 29.52491 | 44.16549 | 2.53144 | 78.62809 |
June | 720.00000 | 29.38287 | 48.68631 | 2.58306 | 78.74831 |
July | 744.00000 | 29.08634 | 51.22689 | 2.52688 | 77.83795 |
August | 744.00000 | 29.16397 | 50.47696 | 2.53086 | 78.04682 |
September | 720.00000 | 29.55071 | 43.25100 | 2.51871 | 77.87916 |
October | 744.00000 | 29.89756 | 35.82547 | 2.49938 | 82.96307 |
November | 720.00000 | 29.31821 | 35.02054 | 2.28396 | 77.90667 |
December | 744.00000 | 28.86013 | 31.50983 | 2.08699 | 73.10304 |
Annual Sum or Average | 8760.00000 | 29.20835 | 39.87297 | 2.35634 | 76.84192 |
Minimum of Months | 672.00000 | 28.08629 | 31.50983 | 1.88112 | 66.05582 |
Maximum of Months | 744.00000 | 29.89756 | 51.22689 | 2.58306 | 82.96307 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.181901E+09 | 9584.71 | 01-JAN-09:01 | 42.22 | 0.566790E+09 | 0.00 | 0.748691E+09 | 0.18 | 3.12 | 02-JAN-12:01 | 0.00 | 0.00 |
February | 0.391818E+09 | 11444.07 | 24-FEB-16:13 | 76.33 | 0.122088E+10 | 0.00 | 0.161270E+10 | 0.35 | 3.12 | 08-FEB-13:01 | 0.00 | 0.00 |
March | 0.283431E+10 | 54321.49 | 25-MAR-15:12 | 217.35 | 0.855989E+10 | 0.00 | 0.113942E+11 | 0.90 | 3.12 | 21-MAR-14:02 | 0.00 | 0.00 |
April | 0.228679E+11 | 168282.11 | 16-APR-18:05 | 393.04 | 0.727972E+11 | 0.00 | 0.956650E+11 | 1.68 | 4.21 | 16-APR-21:13 | 0.00 | 0.00 |
May | 0.529669E+11 | 175377.93 | 31-MAY-18:12 | 710.74 | 0.165833E+12 | 0.00 | 0.218800E+12 | 2.90 | 4.25 | 29-MAY-19:07 | 0.00 | 0.00 |
June | 0.126336E+12 | 239007.76 | 11-JUN-15:11 | 702.01 | 0.420169E+12 | 0.00 | 0.546505E+12 | 3.00 | 4.38 | 14-JUN-08:13 | 0.00 | 0.00 |
July | 0.169547E+12 | 248106.53 | 26-JUL-18:02 | 743.94 | 0.588034E+12 | 0.00 | 0.757582E+12 | 3.15 | 4.42 | 20-JUL-06:43 | 0.00 | 0.00 |
August | 0.152109E+12 | 265012.58 | 04-AUG-15:14 | 744.00 | 0.520172E+12 | 0.00 | 0.672281E+12 | 3.12 | 4.45 | 26-AUG-21:11 | 0.00 | 0.00 |
September | 0.730613E+11 | 187709.64 | 06-SEP-15:14 | 656.65 | 0.228058E+12 | 0.00 | 0.301119E+12 | 2.75 | 4.27 | 11-SEP-23:07 | 0.00 | 0.00 |
October | 0.128062E+11 | 87596.65 | 20-OCT-15:20 | 488.08 | 0.388972E+11 | 0.00 | 0.517034E+11 | 2.03 | 3.57 | 20-OCT-15:20 | 0.00 | 0.00 |
November | 0.329804E+10 | 55231.64 | 05-NOV-15:11 | 202.12 | 0.101572E+11 | 0.00 | 0.134553E+11 | 0.87 | 3.12 | 05-NOV-15:11 | 0.00 | 0.00 |
December | 0.381426E+09 | 13577.73 | 03-DEC-09:01 | 79.22 | 0.118850E+10 | 0.00 | 0.156992E+10 | 0.33 | 3.12 | 05-DEC-16:52 | 0.00 | 0.00 |
Annual Sum or Average | 0.616782E+12 | 5055.70 | 0.205565E+13 | 0.267244E+13 | 1.78 | |||||||
Minimum of Months | 0.181901E+09 | 9584.71 | 42.22 | 0.566790E+09 | 0.00 | 0.748691E+09 | 0.18 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.169547E+12 | 265012.58 | 744.00 | 0.588034E+12 | 0.00 | 0.757582E+12 | 3.15 | 4.45 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.292270E+12 | 0.00 | 739.15 | 478163.48 | 19-JAN-04:42 | 0.00 | 55.19 | 59.98 | 4.81 | 0.00 | 0.18 | 0.80 | 19-JAN-04:42 |
February | 0.192962E+12 | 0.00 | 649.78 | 487844.50 | 02-FEB-05:50 | 0.00 | 56.44 | 59.97 | 4.00 | 0.00 | 0.13 | 0.82 | 02-FEB-05:50 |
March | 0.637553E+11 | 0.00 | 647.80 | 199493.57 | 06-MAR-05:04 | 0.00 | 57.61 | 59.70 | 2.27 | 0.00 | 0.04 | 0.33 | 06-MAR-05:04 |
April | 0.214007E+11 | 0.00 | 460.00 | 123885.90 | 03-APR-08:04 | 0.00 | 57.84 | 59.11 | 1.15 | 0.00 | 0.01 | 0.21 | 03-APR-08:04 |
May | 0.157316E+10 | 0.00 | 177.24 | 34380.35 | 20-MAY-23:24 | 0.00 | 57.78 | 58.14 | 0.17 | 0.00 | 0.00 | 0.06 | 20-MAY-23:24 |
June | 0.601855E+09 | 0.00 | 79.09 | 40543.29 | 01-JUN-03:52 | 0.00 | 56.41 | 56.73 | 0.03 | 0.00 | 0.00 | 0.07 | 01-JUN-03:52 |
July | 61247473.46 | 0.00 | 8.66 | 28622.84 | 23-JUL-08:16 | 0.00 | 54.05 | 54.11 | 0.00 | 0.00 | 0.00 | 0.05 | 23-JUL-08:16 |
August | 59830861.74 | 0.00 | 11.70 | 17561.17 | 01-AUG-08:17 | 0.00 | 55.27 | 55.35 | 0.00 | 0.00 | 0.00 | 0.03 | 01-AUG-08:17 |
September | 0.311549E+10 | 0.00 | 209.27 | 43729.75 | 29-SEP-17:54 | 0.00 | 57.71 | 58.32 | 0.20 | 0.00 | 0.00 | 0.07 | 29-SEP-17:54 |
October | 0.146955E+11 | 0.00 | 526.32 | 47830.53 | 06-OCT-18:24 | 0.00 | 57.70 | 59.27 | 0.84 | 0.00 | 0.01 | 0.08 | 06-OCT-18:24 |
November | 0.886980E+11 | 0.00 | 658.52 | 454015.09 | 25-NOV-22:52 | 0.00 | 56.97 | 59.74 | 2.32 | 0.00 | 0.06 | 0.76 | 25-NOV-22:52 |
December | 0.171520E+12 | 0.00 | 736.63 | 281709.57 | 11-DEC-16:22 | 0.00 | 56.42 | 59.97 | 3.91 | 0.00 | 0.11 | 0.47 | 11-DEC-16:22 |
Annual Sum or Average | 0.850713E+12 | 4904.16 | 56.61 | 58.35 | 1.63 | 0.00 | 0.05 | ||||||
Minimum of Months | 59830861.74 | 0.00 | 8.66 | 17561.17 | 0.00 | 54.05 | 54.11 | 0.00 | 0.00 | 0.00 | 0.03 | ||
Maximum of Months | 0.292270E+12 | 0.00 | 739.15 | 487844.50 | 0.00 | 57.84 | 59.98 | 4.81 | 0.00 | 0.18 | 0.82 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 1638343.16 | 0.00 | 0.47 | 1617178.56 | 0.00 | 0.00 | 0.00 | 0.00 | 14734.05 | 12-JAN-16:11 | 14734.05 | 12-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 63059537.73 | 0.00 | 11.57 | 50387181.59 | 0.00 | 0.00 | 0.00 | 0.00 | 15767.15 | 20-FEB-16:11 | 15767.15 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.232244E+09 | 0.00 | 52.81 | 0.166851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15769.37 | 24-MAR-15:11 | 15769.37 | 24-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.169184E+10 | 0.00 | 215.02 | 0.104162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16050.87 | 16-APR-08:61 | 16030.22 | 29-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.302119E+10 | 0.00 | 441.38 | 0.149991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17088.15 | 29-MAY-08:61 | 15766.94 | 02-MAY-15:11 | 0.00 | 0.00 | 0.00 |
June | 0.627202E+10 | 0.00 | 564.22 | 0.313666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18063.19 | 25-JUN-08:61 | 13903.51 | 24-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.835394E+10 | 0.00 | 680.50 | 0.412434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18266.84 | 20-JUL-08:61 | 14010.30 | 08-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.733751E+10 | 0.00 | 676.88 | 0.337886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19564.32 | 03-AUG-08:61 | 14072.04 | 30-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.415151E+10 | 0.00 | 461.16 | 0.216238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16962.11 | 10-SEP-08:61 | 15768.75 | 24-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.750290E+09 | 0.00 | 137.13 | 0.489577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15767.45 | 17-OCT-15:11 | 15767.45 | 17-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.134649E+09 | 0.00 | 24.73 | 96147163.05 | 0.00 | 0.00 | 0.00 | 0.00 | 15764.21 | 04-NOV-15:11 | 15764.21 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 2441598.60 | 0.00 | 0.38 | 2268353.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10054.53 | 01-DEC-16:11 | 10054.53 | 01-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320123E+11 | 3266.24 | 0.161506E+11 | ||||||||||||
Minimum of Months | 1638343.16 | 0.00 | 0.38 | 1617178.56 | 0.00 | 0.00 | 0.00 | 0.00 | 10054.53 | 10054.53 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.835394E+10 | 0.00 | 680.50 | 0.412434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19564.32 | 16030.22 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 49364.99 | 0.00 | 0.10 | 46908.81 | 0.00 | 0.00 | 0.00 | 0.00 | 311.62 | 12-JAN-16:13 | 311.62 | 12-JAN-16:13 | 0.00 | 0.00 | 0.00 |
February | 15356554.17 | 0.00 | 4.45 | 10187994.56 | 0.00 | 0.00 | 0.00 | 0.00 | 14271.18 | 20-FEB-16:11 | 14271.18 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 75846075.64 | 0.00 | 25.35 | 56140462.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15114.20 | 24-MAR-15:11 | 15114.20 | 24-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.107130E+10 | 0.00 | 156.05 | 0.635776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16416.03 | 16-APR-21:11 | 15506.35 | 09-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.189464E+10 | 0.00 | 344.20 | 0.775316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17683.96 | 21-MAY-19:01 | 17683.96 | 21-MAY-19:01 | 0.00 | 0.00 | 0.00 |
June | 0.474336E+10 | 0.00 | 433.69 | 0.231722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20084.34 | 26-JUN-08:11 | 14700.72 | 23-JUN-21:11 | 0.00 | 0.00 | 0.00 |
July | 0.570887E+10 | 0.00 | 483.94 | 0.266712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19200.78 | 02-JUL-08:11 | 14250.04 | 18-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.473952E+10 | 0.00 | 485.03 | 0.195037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21887.76 | 03-AUG-08:11 | 13973.11 | 08-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.253073E+10 | 0.00 | 334.22 | 0.114937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17157.89 | 11-SEP-08:11 | 16750.37 | 19-SEP-17:01 | 0.00 | 0.00 | 0.00 |
October | 0.234651E+09 | 0.00 | 56.06 | 0.149199E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15213.50 | 24-OCT-15:11 | 15213.50 | 24-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 45486028.06 | 0.00 | 5.48 | 30610531.32 | 0.00 | 0.00 | 0.00 | 0.00 | 15501.47 | 04-NOV-15:11 | 15501.47 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 366362.39 | 0.00 | 0.18 | 360459.79 | 0.00 | 0.00 | 0.00 | 0.00 | 2870.35 | 01-DEC-16:13 | 2870.35 | 01-DEC-16:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210602E+11 | 2328.76 | 0.974171E+10 | ||||||||||||
Minimum of Months | 49364.99 | 0.00 | 0.10 | 46908.81 | 0.00 | 0.00 | 0.00 | 0.00 | 311.62 | 311.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.570887E+10 | 0.00 | 485.03 | 0.266712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21887.76 | 17683.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.735007E+09 | 0.00 | 33.56 | 0.190964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17826.01 | 24-MAR-13:11 | 7888.73 | 25-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.688193E+10 | 0.00 | 136.43 | 0.312433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39568.40 | 15-APR-12:31 | 30223.99 | 15-APR-12:51 | 0.00 | 0.00 | 0.00 |
May | 0.164566E+11 | 0.00 | 480.16 | 0.468415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28688.29 | 28-MAY-15:03 | 14211.58 | 31-MAY-17:11 | 0.00 | 0.00 | 0.00 |
June | 0.290662E+11 | 0.00 | 602.33 | 0.105650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30532.44 | 26-JUN-17:11 | 18559.21 | 26-JUN-17:11 | 0.00 | 0.00 | 0.00 |
July | 0.372088E+11 | 0.00 | 713.10 | 0.135516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30606.01 | 26-JUL-16:01 | 16388.13 | 30-JUL-13:01 | 0.00 | 0.00 | 0.00 |
August | 0.384138E+11 | 0.00 | 715.48 | 0.150845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36728.83 | 22-AUG-12:51 | 28122.74 | 29-AUG-13:11 | 0.00 | 0.00 | 0.00 |
September | 0.299787E+11 | 0.00 | 525.57 | 0.147091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45388.36 | 09-SEP-13:52 | 36742.20 | 05-SEP-12:12 | 0.00 | 0.00 | 0.00 |
October | 0.138655E+11 | 0.00 | 308.14 | 0.712320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48742.02 | 20-OCT-12:50 | 37876.74 | 20-OCT-12:21 | 0.00 | 0.00 | 0.00 |
November | 0.410036E+10 | 0.00 | 102.88 | 0.206748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46751.06 | 04-NOV-12:21 | 37037.37 | 04-NOV-12:21 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176707E+12 | 3617.68 | 0.711002E+11 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.384138E+11 | 0.00 | 715.48 | 0.150845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48742.02 | 37876.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 9268276.39 | 0.00 | 0.42 | 6027862.87 | 0.00 | 0.00 | 0.00 | 0.00 | 40177.31 | 01-JAN-09:01 | 36694.41 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 53177019.44 | 0.00 | 4.80 | 28959598.09 | 0.00 | 0.00 | 0.00 | 0.00 | 56777.08 | 20-FEB-09:01 | 56777.08 | 20-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.218698E+10 | 0.00 | 109.31 | 0.784663E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 73069.09 | 26-MAR-08:61 | 70606.08 | 11-MAR-09:01 | 0.00 | 0.00 | 0.00 |
April | 0.967482E+10 | 0.00 | 242.46 | 0.504483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84218.78 | 16-APR-21:11 | 73807.40 | 26-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.265193E+11 | 0.00 | 430.01 | 0.139010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85934.29 | 29-MAY-08:11 | 74498.40 | 06-MAY-18:51 | 0.00 | 0.00 | 0.00 |
June | 0.411880E+11 | 0.00 | 447.07 | 0.241077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102929.13 | 26-JUN-08:11 | 72566.66 | 23-JUN-21:11 | 0.00 | 0.00 | 0.00 |
July | 0.445456E+11 | 0.00 | 421.71 | 0.258734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97099.45 | 20-JUL-08:11 | 70835.39 | 18-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.402854E+11 | 0.00 | 417.83 | 0.223665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111898.85 | 03-AUG-08:11 | 70420.66 | 06-AUG-08:61 | 0.00 | 0.00 | 0.00 |
September | 0.249088E+11 | 0.00 | 407.04 | 0.132771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87694.53 | 11-SEP-21:11 | 72544.42 | 30-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.635381E+10 | 0.00 | 275.53 | 0.243603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74831.59 | 02-OCT-18:01 | 68643.74 | 21-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.288404E+10 | 0.00 | 116.17 | 0.954021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75116.40 | 08-NOV-19:01 | 65489.65 | 09-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 20462086.68 | 0.00 | 0.57 | 15824239.70 | 0.00 | 0.00 | 0.00 | 0.00 | 50766.25 | 03-DEC-09:01 | 50766.25 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198630E+12 | 2872.92 | 0.108796E+12 | ||||||||||||
Minimum of Months | 9268276.39 | 0.00 | 0.42 | 6027862.87 | 0.00 | 0.00 | 0.00 | 0.00 | 40177.31 | 36694.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.445456E+11 | 0.00 | 447.07 | 0.258734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111898.85 | 74498.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 698886.22 | 0.00 | 0.17 | 440670.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2933.84 | 12-JAN-09:03 | 1834.90 | 12-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 35427676.67 | 0.00 | 7.88 | 20284809.61 | 0.00 | 0.00 | 0.00 | 0.00 | 12207.82 | 21-FEB-09:01 | 12207.82 | 21-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.189384E+09 | 0.00 | 61.14 | 0.113163E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14024.96 | 24-MAR-15:11 | 14024.96 | 24-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.139926E+10 | 0.00 | 205.75 | 0.755577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14045.30 | 30-APR-18:01 | 14045.30 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.323736E+10 | 0.00 | 499.99 | 0.153071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14787.83 | 12-MAY-08:61 | 13787.54 | 06-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.634077E+10 | 0.00 | 596.47 | 0.316836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16053.88 | 14-JUN-18:01 | 12485.32 | 08-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.807632E+10 | 0.00 | 707.25 | 0.386030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16314.78 | 20-JUL-08:61 | 12553.68 | 29-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.700163E+10 | 0.00 | 696.02 | 0.313751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16936.52 | 31-AUG-18:01 | 12559.91 | 20-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.413254E+10 | 0.00 | 480.72 | 0.210694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15053.64 | 10-SEP-08:61 | 13797.47 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.580532E+09 | 0.00 | 147.43 | 0.307705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13899.00 | 31-OCT-15:11 | 13899.00 | 31-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 90434275.74 | 0.00 | 29.45 | 57671586.07 | 0.00 | 0.00 | 0.00 | 0.00 | 14043.61 | 04-NOV-15:11 | 14043.61 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 5405146.77 | 0.00 | 2.68 | 2025666.40 | 0.00 | 0.00 | 0.00 | 0.00 | 8892.61 | 03-DEC-09:01 | 8892.61 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.310898E+11 | 3434.96 | 0.150607E+11 | ||||||||||||
Minimum of Months | 698886.22 | 0.00 | 0.17 | 440670.27 | 0.00 | 0.00 | 0.00 | 0.00 | 2933.84 | 1834.90 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.807632E+10 | 0.00 | 707.25 | 0.386030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16936.52 | 14045.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 203754.09 | 0.00 | 0.12 | 103346.51 | 0.00 | 0.00 | 0.00 | 0.00 | 1603.83 | 12-JAN-09:04 | 618.07 | 12-JAN-09:04 | 0.00 | 0.00 | 0.00 |
February | 6543685.33 | 0.00 | 1.75 | 2872393.89 | 0.00 | 0.00 | 0.00 | 0.00 | 9399.68 | 24-FEB-09:01 | 9399.68 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 73740257.11 | 0.00 | 24.03 | 39334795.34 | 0.00 | 0.00 | 0.00 | 0.00 | 12782.55 | 22-MAR-08:61 | 12782.55 | 22-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.881150E+09 | 0.00 | 137.03 | 0.467152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16101.72 | 18-APR-08:11 | 13904.93 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.234539E+10 | 0.00 | 385.85 | 0.108535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17285.54 | 31-MAY-08:11 | 13694.70 | 31-MAY-08:11 | 0.00 | 0.00 | 0.00 |
June | 0.495029E+10 | 0.00 | 458.69 | 0.250820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19130.10 | 26-JUN-08:11 | 14836.36 | 20-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.578109E+10 | 0.00 | 495.69 | 0.280688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18805.19 | 02-JUL-08:11 | 14868.18 | 18-JUL-08:11 | 0.00 | 0.00 | 0.00 |
August | 0.477348E+10 | 0.00 | 501.62 | 0.209973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20788.58 | 03-AUG-08:11 | 14254.20 | 10-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.267303E+10 | 0.00 | 355.24 | 0.127711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16668.49 | 11-SEP-08:11 | 13831.81 | 06-SEP-08:11 | 0.00 | 0.00 | 0.00 |
October | 0.142620E+09 | 0.00 | 48.55 | 58875571.98 | 0.00 | 0.00 | 0.00 | 0.00 | 12774.06 | 02-OCT-18:01 | 11572.33 | 01-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 13632490.83 | 0.00 | 3.02 | 5637080.19 | 0.00 | 0.00 | 0.00 | 0.00 | 9585.56 | 04-NOV-08:61 | 9585.56 | 04-NOV-08:61 | 0.00 | 0.00 | 0.00 |
December | 619266.70 | 0.00 | 0.15 | 401463.51 | 0.00 | 0.00 | 0.00 | 0.00 | 3039.89 | 03-DEC-09:02 | 1957.94 | 05-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216418E+11 | 2411.74 | 0.103516E+11 | ||||||||||||
Minimum of Months | 203754.09 | 0.00 | 0.12 | 103346.51 | 0.00 | 0.00 | 0.00 | 0.00 | 1603.83 | 618.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.578109E+10 | 0.00 | 501.62 | 0.280688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20788.58 | 14868.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 511575.32 | 0.00 | 0.58 | 483786.80 | 0.00 | 0.00 | 0.00 | 0.00 | 3849.16 | 12-JAN-16:11 | 3849.16 | 12-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 18234369.88 | 0.00 | 12.15 | 14771474.60 | 0.00 | 0.00 | 0.00 | 0.00 | 4113.79 | 20-FEB-16:11 | 4113.79 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 56276928.08 | 0.00 | 45.37 | 41379244.29 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.39 | 24-MAR-15:11 | 4114.39 | 24-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.479564E+09 | 0.00 | 204.26 | 0.308481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4229.30 | 29-APR-18:01 | 4229.30 | 29-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.883181E+09 | 0.00 | 440.52 | 0.472442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4462.92 | 29-MAY-08:61 | 4113.78 | 02-MAY-15:11 | 0.00 | 0.00 | 0.00 |
June | 0.176241E+10 | 0.00 | 569.87 | 0.940538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4759.82 | 26-JUN-08:61 | 3625.46 | 04-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.228730E+10 | 0.00 | 686.65 | 0.119525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4829.33 | 20-JUL-08:61 | 3632.17 | 16-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.197651E+10 | 0.00 | 674.49 | 0.974782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5155.84 | 03-AUG-08:61 | 3670.28 | 03-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.110304E+10 | 0.00 | 428.76 | 0.625150E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4434.12 | 11-SEP-08:61 | 4114.11 | 24-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.197949E+09 | 0.00 | 119.97 | 0.135631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4113.88 | 17-OCT-15:11 | 4113.88 | 17-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 36236154.89 | 0.00 | 19.42 | 27156740.05 | 0.00 | 0.00 | 0.00 | 0.00 | 4113.02 | 04-NOV-15:11 | 4113.02 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 537311.49 | 0.00 | 0.27 | 485347.21 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.07 | 01-DEC-16:11 | 3027.07 | 01-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.880175E+10 | 3202.31 | 0.473655E+10 | ||||||||||||
Minimum of Months | 511575.32 | 0.00 | 0.27 | 483786.80 | 0.00 | 0.00 | 0.00 | 0.00 | 3027.07 | 3027.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.228730E+10 | 0.00 | 686.65 | 0.119525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5155.84 | 4229.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 77542.86 | 0.00 | 0.03 | 77542.86 | 0.00 | 0.00 | 0.00 | 0.00 | 877.05 | 12-JAN-16:13 | 877.05 | 12-JAN-16:13 | 0.00 | 0.00 | 0.00 |
February | 3001372.28 | 0.00 | 3.85 | 1801807.84 | 0.00 | 0.00 | 0.00 | 0.00 | 2555.97 | 24-FEB-16:11 | 2555.97 | 24-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 14747254.64 | 0.00 | 19.03 | 10730320.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3897.56 | 24-MAR-15:11 | 3897.56 | 24-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.309769E+09 | 0.00 | 153.11 | 0.194974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4342.35 | 16-APR-21:11 | 4064.28 | 29-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.591568E+09 | 0.00 | 352.36 | 0.273071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4967.86 | 20-MAY-18:01 | 4967.86 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.139925E+10 | 0.00 | 443.53 | 0.734054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5313.24 | 26-JUN-08:11 | 4076.51 | 22-JUN-21:01 | 0.00 | 0.00 | 0.00 |
July | 0.166229E+10 | 0.00 | 493.60 | 0.834226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5050.29 | 07-JUL-08:11 | 4097.31 | 23-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.135224E+10 | 0.00 | 496.95 | 0.603508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5745.61 | 03-AUG-08:11 | 3799.15 | 16-AUG-21:01 | 0.00 | 0.00 | 0.00 |
September | 0.692742E+09 | 0.00 | 316.03 | 0.342585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4518.80 | 11-SEP-21:11 | 4442.08 | 19-SEP-17:01 | 0.00 | 0.00 | 0.00 |
October | 56051454.60 | 0.00 | 49.93 | 35352516.82 | 0.00 | 0.00 | 0.00 | 0.00 | 3910.42 | 19-OCT-16:31 | 3910.42 | 19-OCT-16:31 | 0.00 | 0.00 | 0.00 |
November | 11207969.67 | 0.00 | 5.07 | 7441190.38 | 0.00 | 0.00 | 0.00 | 0.00 | 4003.92 | 04-NOV-15:11 | 4003.92 | 04-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 54829.17 | 0.00 | 0.03 | 54829.17 | 0.00 | 0.00 | 0.00 | 0.00 | 635.22 | 02-DEC-16:13 | 635.22 | 02-DEC-16:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609300E+10 | 2333.52 | 0.303788E+10 | ||||||||||||
Minimum of Months | 54829.17 | 0.00 | 0.03 | 54829.17 | 0.00 | 0.00 | 0.00 | 0.00 | 635.22 | 635.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.166229E+10 | 0.00 | 496.95 | 0.834226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5745.61 | 4967.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.334970E+09 | 0.00 | 41.82 | 0.267586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15624.55 | 02-JAN-16:11 | 15624.55 | 02-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.629001E+09 | 0.00 | 73.50 | 0.418719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15624.75 | 17-FEB-16:11 | 15624.75 | 17-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.105511E+10 | 0.00 | 154.97 | 0.633105E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16425.16 | 26-MAR-08:61 | 15628.52 | 07-MAR-16:11 | 0.00 | 0.00 | 0.00 |
April | 0.267705E+10 | 0.00 | 260.79 | 0.152234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16341.01 | 16-APR-08:61 | 15630.01 | 26-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.466928E+10 | 0.00 | 512.61 | 0.207369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17368.59 | 29-MAY-08:61 | 15183.10 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.817153E+10 | 0.00 | 589.28 | 0.402009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19152.51 | 26-JUN-08:61 | 13951.76 | 25-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.104767E+11 | 0.00 | 676.91 | 0.503631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19277.79 | 20-JUL-08:61 | 14012.41 | 21-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.102996E+11 | 0.00 | 674.73 | 0.504818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20350.69 | 03-AUG-08:61 | 13943.50 | 17-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.724679E+10 | 0.00 | 523.53 | 0.432375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17443.28 | 11-SEP-08:61 | 14034.63 | 20-SEP-15:29 | 0.00 | 0.00 | 0.00 |
October | 0.345371E+10 | 0.00 | 332.84 | 0.224486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16383.93 | 10-OCT-08:61 | 13558.08 | 21-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.114800E+10 | 0.00 | 135.83 | 0.756210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16468.87 | 08-NOV-09:01 | 15254.05 | 21-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.750990E+09 | 0.00 | 78.45 | 0.621457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15622.68 | 05-DEC-16:11 | 15622.68 | 05-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.509127E+11 | 4055.27 | 0.269663E+11 | ||||||||||||
Minimum of Months | 0.334970E+09 | 0.00 | 41.82 | 0.267586E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15622.68 | 13558.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.104767E+11 | 0.00 | 676.91 | 0.504818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20350.69 | 15630.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.262160E+10 | 0.00 | 13.59 | 0.262160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120275.99 | 19-MAR-15:51 | 120275.99 | 19-MAR-15:51 | 0.00 | 0.00 | 0.00 |
April | 0.424811E+11 | 0.00 | 62.92 | 0.324216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 533525.81 | 16-APR-18:49 | 347913.27 | 15-APR-18:29 | 0.00 | 0.00 | 0.00 |
May | 0.953623E+11 | 0.00 | 185.89 | 0.712430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 544498.50 | 30-MAY-18:04 | 354859.82 | 31-MAY-18:11 | 0.00 | 0.00 | 0.00 |
June | 0.288838E+12 | 0.00 | 281.84 | 0.182266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 664800.37 | 30-JUN-08:32 | 377914.31 | 29-JUN-18:21 | 0.00 | 0.00 | 0.00 |
July | 0.423852E+12 | 0.00 | 364.84 | 0.235413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 949092.15 | 26-JUL-19:04 | 354123.17 | 03-JUL-18:20 | 0.00 | 0.00 | 0.00 |
August | 0.370692E+12 | 0.00 | 339.65 | 0.211083E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 875815.03 | 04-AUG-07:52 | 373911.06 | 02-AUG-18:21 | 0.00 | 0.00 | 0.00 |
September | 0.136632E+12 | 0.00 | 200.31 | 0.118050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 486844.23 | 11-SEP-09:32 | 351550.82 | 07-SEP-18:10 | 0.00 | 0.00 | 0.00 |
October | 0.101241E+11 | 0.00 | 35.52 | 0.101133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 257935.65 | 20-OCT-14:21 | 257935.65 | 20-OCT-14:21 | 0.00 | 0.00 | 0.00 |
November | 0.624702E+09 | 0.00 | 5.71 | 0.624702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79113.40 | 03-NOV-14:53 | 79113.40 | 03-NOV-14:53 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137123E+13 | 1490.27 | 0.863837E+12 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.423852E+12 | 0.00 | 364.84 | 0.235413E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 949092.15 | 377914.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.192466E+09 | 0.00 | 16.33 | 0.192466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8513.13 | 19-MAR-15:51 | 8513.13 | 19-MAR-15:51 | 0.00 | 0.00 | 0.00 |
April | 0.320445E+10 | 0.00 | 77.33 | 0.248039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28950.18 | 18-APR-16:50 | 18727.03 | 15-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.715673E+10 | 0.00 | 236.00 | 0.532921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29106.59 | 29-MAY-15:12 | 18559.43 | 31-MAY-12:01 | 0.00 | 0.00 | 0.00 |
June | 0.237482E+11 | 0.00 | 395.00 | 0.151238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40744.52 | 26-JUN-08:02 | 20060.98 | 11-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.361656E+11 | 0.00 | 518.17 | 0.200651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42550.34 | 17-JUL-18:04 | 18984.28 | 26-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.293845E+11 | 0.00 | 475.17 | 0.167277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49615.14 | 04-AUG-08:02 | 20403.81 | 04-AUG-15:11 | 0.00 | 0.00 | 0.00 |
September | 0.105441E+11 | 0.00 | 268.33 | 0.894140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29509.45 | 11-SEP-08:11 | 19407.99 | 06-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.606742E+09 | 0.00 | 38.17 | 0.606742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15180.49 | 20-OCT-15:12 | 15180.49 | 20-OCT-15:12 | 0.00 | 0.00 | 0.00 |
November | 23848089.77 | 0.00 | 6.83 | 23848089.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1790.73 | 03-NOV-15:11 | 1790.73 | 03-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111027E+12 | 2031.33 | 0.694907E+11 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.361656E+11 | 0.00 | 518.17 | 0.200651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49615.14 | 20403.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 807.15 | 552.96 | 254.19 | 661.19 | 905.87 | 0.00 | 0.00 | 744.00 |
February | 870.46 | 590.61 | 279.85 | 715.25 | 736.82 | 0.00 | 0.00 | 672.00 |
March | 745.79 | 390.54 | 355.25 | 568.41 | 562.59 | 0.00 | 0.00 | 744.00 |
April | 664.59 | 304.56 | 360.03 | 486.64 | 420.10 | 0.00 | 0.00 | 720.00 |
May | 566.74 | 158.48 | 408.27 | 415.87 | 248.69 | 0.00 | 0.00 | 744.00 |
June | 541.02 | 107.97 | 433.05 | 459.86 | 162.67 | 0.00 | 0.00 | 720.00 |
July | 574.13 | 143.51 | 430.62 | 510.14 | 134.13 | 0.00 | 0.00 | 744.00 |
August | 636.24 | 220.27 | 415.97 | 604.14 | 163.58 | 0.00 | 0.00 | 744.00 |
September | 768.42 | 396.57 | 371.84 | 736.81 | 283.62 | 0.00 | 0.00 | 720.00 |
October | 828.25 | 522.28 | 305.96 | 781.18 | 438.60 | 0.00 | 0.00 | 744.00 |
November | 619.63 | 387.93 | 231.71 | 517.68 | 615.86 | 0.00 | 0.00 | 720.00 |
December | 659.57 | 499.45 | 160.12 | 589.20 | 855.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 689.14 | 354.96 | 334.18 | 586.55 | 459.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 541.02 | 107.97 | 160.12 | 415.87 | 134.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 870.46 | 590.61 | 433.05 | 781.18 | 905.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2272.88 | 1557.09 | 715.79 | 1835.72 | 2649.93 | 0.00 | 0.00 | 744.00 |
February | 2451.16 | 1663.13 | 788.03 | 1983.94 | 2188.96 | 0.00 | 0.00 | 672.00 |
March | 2100.09 | 1099.73 | 1000.36 | 1570.49 | 1683.68 | 0.00 | 0.00 | 744.00 |
April | 1871.43 | 857.61 | 1013.82 | 1349.40 | 1263.80 | 0.00 | 0.00 | 720.00 |
May | 1595.91 | 446.26 | 1149.66 | 1159.98 | 731.94 | 0.00 | 0.00 | 744.00 |
June | 1523.46 | 304.03 | 1219.43 | 1285.50 | 480.91 | 0.00 | 0.00 | 720.00 |
July | 1616.70 | 404.10 | 1212.60 | 1430.23 | 393.41 | 0.00 | 0.00 | 744.00 |
August | 1791.60 | 620.26 | 1171.34 | 1695.18 | 483.59 | 0.00 | 0.00 | 744.00 |
September | 2163.81 | 1116.73 | 1047.08 | 2063.28 | 837.82 | 0.00 | 0.00 | 720.00 |
October | 2332.29 | 1470.72 | 861.57 | 2172.27 | 1307.42 | 0.00 | 0.00 | 744.00 |
November | 1744.85 | 1092.38 | 652.47 | 1433.33 | 1834.33 | 0.00 | 0.00 | 720.00 |
December | 1857.32 | 1406.42 | 450.89 | 1635.03 | 2530.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1940.57 | 999.54 | 941.03 | 1632.77 | 1361.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1523.46 | 304.03 | 450.89 | 1159.98 | 393.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2451.16 | 1663.13 | 1219.43 | 2172.27 | 2649.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2952.60 | 2022.75 | 929.85 | 2389.37 | 3672.43 | 0.00 | 0.00 | 744.00 |
February | 3184.19 | 2160.50 | 1023.69 | 2595.39 | 3012.16 | 0.00 | 0.00 | 672.00 |
March | 2728.14 | 1428.62 | 1299.53 | 2051.67 | 2322.61 | 0.00 | 0.00 | 744.00 |
April | 2431.10 | 1114.08 | 1317.02 | 1776.36 | 1749.73 | 0.00 | 0.00 | 720.00 |
May | 2073.18 | 579.71 | 1493.47 | 1527.41 | 1003.29 | 0.00 | 0.00 | 744.00 |
June | 1979.07 | 394.95 | 1584.11 | 1706.73 | 657.04 | 0.00 | 0.00 | 720.00 |
July | 2100.18 | 524.95 | 1575.23 | 1901.83 | 532.27 | 0.00 | 0.00 | 744.00 |
August | 2327.39 | 805.75 | 1521.63 | 2253.31 | 649.45 | 0.00 | 0.00 | 744.00 |
September | 2810.91 | 1450.69 | 1360.22 | 2738.80 | 1132.97 | 0.00 | 0.00 | 720.00 |
October | 3029.77 | 1910.55 | 1119.22 | 2866.61 | 1775.63 | 0.00 | 0.00 | 744.00 |
November | 2266.66 | 1419.07 | 847.59 | 1872.51 | 2545.90 | 0.00 | 0.00 | 720.00 |
December | 2412.76 | 1827.02 | 585.74 | 2138.67 | 3504.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2520.92 | 1298.46 | 1222.46 | 2149.31 | 1874.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1979.07 | 394.95 | 585.74 | 1527.41 | 532.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3184.19 | 2160.50 | 1584.11 | 2866.61 | 3672.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.26 | 109.11 | 50.16 | 129.60 | 192.37 | 0.00 | 0.00 | 744.00 |
February | 171.75 | 116.54 | 55.22 | 140.22 | 155.56 | 0.00 | 0.00 | 672.00 |
March | 147.15 | 77.06 | 70.10 | 114.54 | 112.35 | 0.00 | 0.00 | 744.00 |
April | 131.13 | 60.09 | 71.04 | 99.81 | 80.08 | 0.00 | 0.00 | 720.00 |
May | 111.83 | 31.27 | 80.56 | 88.63 | 41.82 | 0.00 | 0.00 | 744.00 |
June | 106.75 | 21.30 | 85.45 | 99.34 | 24.07 | 0.00 | 0.00 | 720.00 |
July | 113.28 | 28.32 | 84.97 | 109.33 | 18.41 | 0.00 | 0.00 | 744.00 |
August | 125.54 | 43.46 | 82.08 | 127.92 | 23.39 | 0.00 | 0.00 | 744.00 |
September | 151.62 | 78.25 | 73.37 | 153.54 | 46.66 | 0.00 | 0.00 | 720.00 |
October | 163.42 | 103.05 | 60.37 | 159.83 | 79.81 | 0.00 | 0.00 | 744.00 |
November | 122.26 | 76.54 | 45.72 | 104.62 | 122.66 | 0.00 | 0.00 | 720.00 |
December | 130.14 | 98.55 | 31.59 | 117.65 | 177.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 135.98 | 70.04 | 65.94 | 120.32 | 89.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 106.75 | 21.30 | 31.59 | 88.63 | 18.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.75 | 116.54 | 85.45 | 159.83 | 192.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.80 | 41.40 | 60.40 | 29.52 | 414.35 | 0.00 | 0.00 | 744.00 |
February | 148.57 | 73.14 | 75.42 | 72.23 | 329.61 | 0.00 | 0.00 | 672.00 |
March | 177.31 | 65.95 | 111.36 | 103.04 | 215.29 | 0.00 | 0.00 | 744.00 |
April | 259.30 | 128.32 | 130.97 | 228.28 | 145.55 | 0.00 | 0.00 | 720.00 |
May | 259.78 | 104.00 | 155.78 | 257.62 | 75.34 | 0.00 | 0.00 | 744.00 |
June | 303.88 | 131.37 | 172.51 | 346.51 | 44.04 | 0.00 | 0.00 | 720.00 |
July | 326.39 | 154.82 | 171.57 | 385.54 | 33.99 | 0.00 | 0.00 | 744.00 |
August | 285.02 | 130.42 | 154.60 | 336.23 | 43.21 | 0.00 | 0.00 | 744.00 |
September | 231.30 | 109.61 | 121.69 | 243.96 | 86.35 | 0.00 | 0.00 | 720.00 |
October | 162.12 | 72.43 | 89.70 | 121.58 | 154.54 | 0.00 | 0.00 | 744.00 |
November | 96.73 | 35.92 | 60.81 | 42.19 | 253.15 | 0.00 | 0.00 | 720.00 |
December | 74.47 | 35.24 | 39.22 | 25.59 | 370.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 202.44 | 90.24 | 112.20 | 183.24 | 179.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 74.47 | 35.24 | 39.22 | 25.59 | 33.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 326.39 | 154.82 | 172.51 | 385.54 | 414.35 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.53 | 0.00 | 25.53 | 0.00 | 235.64 | 0.00 | 0.00 | 744.00 |
February | 32.37 | 0.00 | 32.37 | 0.44 | 189.99 | 0.00 | 0.00 | 672.00 |
March | 48.52 | 0.00 | 48.52 | 9.43 | 122.10 | 0.00 | 0.00 | 744.00 |
April | 56.23 | 0.45 | 55.78 | 23.83 | 80.74 | 0.00 | 0.00 | 720.00 |
May | 73.11 | 2.76 | 70.35 | 52.14 | 39.72 | 0.00 | 0.00 | 744.00 |
June | 85.55 | 7.92 | 77.63 | 80.15 | 23.53 | 0.00 | 0.00 | 720.00 |
July | 80.24 | 5.52 | 74.72 | 78.69 | 19.56 | 0.00 | 0.00 | 744.00 |
August | 67.24 | 1.36 | 65.88 | 69.04 | 24.60 | 0.00 | 0.00 | 744.00 |
September | 51.46 | 0.05 | 51.41 | 42.03 | 48.31 | 0.00 | 0.00 | 720.00 |
October | 38.21 | 0.00 | 38.21 | 12.78 | 85.13 | 0.00 | 0.00 | 744.00 |
November | 26.73 | 0.00 | 26.73 | 2.76 | 141.18 | 0.00 | 0.00 | 720.00 |
December | 17.34 | 0.00 | 17.34 | 0.00 | 206.11 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 50.31 | 1.51 | 48.80 | 31.12 | 100.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 17.34 | 0.00 | 17.34 | 0.00 | 19.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.55 | 7.92 | 77.63 | 80.15 | 235.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.80 | 41.40 | 60.40 | 30.70 | 410.47 | 0.00 | 0.00 | 744.00 |
February | 148.57 | 73.14 | 75.42 | 74.64 | 325.15 | 0.00 | 0.00 | 672.00 |
March | 177.31 | 65.95 | 111.36 | 106.47 | 212.80 | 0.00 | 0.00 | 744.00 |
April | 259.30 | 128.32 | 130.97 | 230.26 | 144.92 | 0.00 | 0.00 | 720.00 |
May | 259.78 | 104.00 | 155.78 | 256.25 | 76.31 | 0.00 | 0.00 | 744.00 |
June | 303.88 | 131.37 | 172.51 | 342.54 | 46.51 | 0.00 | 0.00 | 720.00 |
July | 326.39 | 154.82 | 171.57 | 379.22 | 38.34 | 0.00 | 0.00 | 744.00 |
August | 285.02 | 130.42 | 154.60 | 332.07 | 47.09 | 0.00 | 0.00 | 744.00 |
September | 231.30 | 109.61 | 121.69 | 244.91 | 87.76 | 0.00 | 0.00 | 720.00 |
October | 162.12 | 72.43 | 89.70 | 126.18 | 152.09 | 0.00 | 0.00 | 744.00 |
November | 96.73 | 35.92 | 60.81 | 44.51 | 250.21 | 0.00 | 0.00 | 720.00 |
December | 74.47 | 35.24 | 39.22 | 27.08 | 366.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 202.44 | 90.24 | 112.20 | 183.43 | 179.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 74.47 | 35.24 | 39.22 | 27.08 | 38.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 326.39 | 154.82 | 172.51 | 379.22 | 410.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 127.38 | 87.27 | 40.12 | 106.69 | 136.23 | 0.00 | 0.00 | 744.00 |
February | 137.38 | 93.21 | 44.17 | 113.11 | 119.64 | 0.00 | 0.00 | 672.00 |
March | 117.70 | 61.63 | 56.07 | 89.78 | 91.13 | 0.00 | 0.00 | 744.00 |
April | 104.89 | 48.06 | 56.82 | 74.16 | 79.80 | 0.00 | 0.00 | 720.00 |
May | 89.44 | 25.01 | 64.43 | 59.09 | 51.47 | 0.00 | 0.00 | 744.00 |
June | 85.38 | 17.04 | 68.34 | 66.99 | 35.22 | 0.00 | 0.00 | 720.00 |
July | 90.61 | 22.65 | 67.96 | 75.01 | 29.17 | 0.00 | 0.00 | 744.00 |
August | 100.41 | 34.76 | 65.65 | 90.43 | 34.97 | 0.00 | 0.00 | 744.00 |
September | 121.27 | 62.59 | 58.68 | 112.50 | 57.66 | 0.00 | 0.00 | 720.00 |
October | 130.71 | 82.43 | 48.29 | 117.14 | 87.24 | 0.00 | 0.00 | 744.00 |
November | 97.79 | 61.22 | 36.57 | 78.82 | 109.78 | 0.00 | 0.00 | 720.00 |
December | 104.09 | 78.82 | 25.27 | 95.25 | 128.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 108.76 | 56.02 | 52.74 | 89.80 | 79.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 85.38 | 17.04 | 25.27 | 59.09 | 29.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 137.38 | 93.21 | 68.34 | 117.14 | 136.23 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.43 | 0.00 | 20.43 | 0.00 | 194.50 | 0.00 | 0.00 | 744.00 |
February | 25.90 | 0.00 | 25.90 | 0.24 | 156.83 | 0.00 | 0.00 | 672.00 |
March | 38.82 | 0.00 | 38.82 | 7.10 | 100.74 | 0.00 | 0.00 | 744.00 |
April | 44.99 | 0.36 | 44.63 | 19.91 | 65.62 | 0.00 | 0.00 | 720.00 |
May | 58.50 | 2.21 | 56.29 | 43.87 | 31.57 | 0.00 | 0.00 | 744.00 |
June | 68.45 | 6.34 | 62.12 | 67.69 | 18.15 | 0.00 | 0.00 | 720.00 |
July | 64.20 | 4.42 | 59.78 | 67.65 | 14.17 | 0.00 | 0.00 | 744.00 |
August | 53.80 | 1.08 | 52.71 | 59.14 | 18.25 | 0.00 | 0.00 | 744.00 |
September | 41.17 | 0.04 | 41.13 | 35.51 | 38.12 | 0.00 | 0.00 | 720.00 |
October | 30.57 | 0.00 | 30.57 | 9.85 | 69.75 | 0.00 | 0.00 | 744.00 |
November | 21.39 | 0.00 | 21.39 | 1.94 | 117.51 | 0.00 | 0.00 | 720.00 |
December | 13.87 | 0.00 | 13.87 | 0.00 | 170.98 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.25 | 1.21 | 39.04 | 26.23 | 82.66 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 13.87 | 0.00 | 13.87 | 0.00 | 14.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 68.45 | 6.34 | 62.12 | 67.69 | 194.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.88 | 41.76 | 60.13 | 23.96 | 407.85 | 0.00 | 0.00 | 744.00 |
February | 135.66 | 59.71 | 75.95 | 53.20 | 322.64 | 0.00 | 0.00 | 672.00 |
March | 184.25 | 73.11 | 111.14 | 106.58 | 209.54 | 0.00 | 0.00 | 744.00 |
April | 224.87 | 98.01 | 126.86 | 182.88 | 141.33 | 0.00 | 0.00 | 720.00 |
May | 284.09 | 124.24 | 159.86 | 282.15 | 70.75 | 0.00 | 0.00 | 744.00 |
June | 312.20 | 135.98 | 176.22 | 352.12 | 41.42 | 0.00 | 0.00 | 720.00 |
July | 315.62 | 145.67 | 169.95 | 368.85 | 31.57 | 0.00 | 0.00 | 744.00 |
August | 266.12 | 114.68 | 151.44 | 309.57 | 40.15 | 0.00 | 0.00 | 744.00 |
September | 238.45 | 113.10 | 125.35 | 249.15 | 83.57 | 0.00 | 0.00 | 720.00 |
October | 150.99 | 62.85 | 88.14 | 102.17 | 148.95 | 0.00 | 0.00 | 744.00 |
November | 89.31 | 28.99 | 60.33 | 29.51 | 248.43 | 0.00 | 0.00 | 720.00 |
December | 68.93 | 29.51 | 39.41 | 16.20 | 366.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 198.00 | 85.75 | 112.25 | 173.68 | 175.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 68.93 | 28.99 | 39.41 | 16.20 | 31.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 315.62 | 145.67 | 176.22 | 368.85 | 407.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.26 | 109.11 | 50.16 | 129.42 | 192.11 | 0.00 | 0.00 | 744.00 |
February | 171.75 | 116.54 | 55.22 | 139.95 | 154.85 | 0.00 | 0.00 | 672.00 |
March | 147.15 | 77.06 | 70.10 | 113.62 | 112.11 | 0.00 | 0.00 | 744.00 |
April | 131.13 | 60.09 | 71.04 | 99.35 | 79.23 | 0.00 | 0.00 | 720.00 |
May | 111.83 | 31.27 | 80.56 | 87.32 | 41.80 | 0.00 | 0.00 | 744.00 |
June | 106.75 | 21.30 | 85.45 | 98.56 | 23.86 | 0.00 | 0.00 | 720.00 |
July | 113.28 | 28.32 | 84.97 | 108.80 | 17.95 | 0.00 | 0.00 | 744.00 |
August | 125.54 | 43.46 | 82.08 | 127.55 | 23.00 | 0.00 | 0.00 | 744.00 |
September | 151.62 | 78.25 | 73.37 | 152.65 | 46.36 | 0.00 | 0.00 | 720.00 |
October | 163.42 | 103.05 | 60.37 | 159.25 | 79.44 | 0.00 | 0.00 | 744.00 |
November | 122.26 | 76.54 | 45.72 | 104.50 | 122.43 | 0.00 | 0.00 | 720.00 |
December | 130.14 | 98.55 | 31.59 | 117.59 | 176.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 135.98 | 70.04 | 65.94 | 119.78 | 88.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 106.75 | 21.30 | 31.59 | 87.32 | 17.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.75 | 116.54 | 85.45 | 159.25 | 192.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.53 | 0.00 | 25.53 | 0.00 | 235.46 | 0.00 | 0.00 | 744.00 |
February | 32.37 | 0.00 | 32.37 | 0.36 | 189.34 | 0.00 | 0.00 | 672.00 |
March | 48.52 | 0.00 | 48.52 | 9.06 | 122.29 | 0.00 | 0.00 | 744.00 |
April | 56.23 | 0.45 | 55.78 | 23.59 | 79.85 | 0.00 | 0.00 | 720.00 |
May | 73.11 | 2.76 | 70.35 | 51.32 | 39.46 | 0.00 | 0.00 | 744.00 |
June | 85.55 | 7.92 | 77.63 | 79.73 | 22.94 | 0.00 | 0.00 | 720.00 |
July | 80.24 | 5.52 | 74.72 | 78.84 | 18.37 | 0.00 | 0.00 | 744.00 |
August | 67.24 | 1.36 | 65.88 | 69.30 | 23.41 | 0.00 | 0.00 | 744.00 |
September | 51.46 | 0.05 | 51.41 | 41.34 | 47.67 | 0.00 | 0.00 | 720.00 |
October | 38.21 | 0.00 | 38.21 | 12.44 | 84.70 | 0.00 | 0.00 | 744.00 |
November | 26.73 | 0.00 | 26.73 | 2.69 | 140.94 | 0.00 | 0.00 | 720.00 |
December | 17.34 | 0.00 | 17.34 | 0.00 | 206.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 50.31 | 1.51 | 48.80 | 30.90 | 100.46 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 17.34 | 0.00 | 17.34 | 0.00 | 18.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.55 | 7.92 | 77.63 | 79.73 | 235.46 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.88 | 41.76 | 60.13 | 24.51 | 403.33 | 0.00 | 0.00 | 744.00 |
February | 135.66 | 59.71 | 75.95 | 54.55 | 317.00 | 0.00 | 0.00 | 672.00 |
March | 184.25 | 73.11 | 111.14 | 109.44 | 206.28 | 0.00 | 0.00 | 744.00 |
April | 224.87 | 98.01 | 126.86 | 184.93 | 140.25 | 0.00 | 0.00 | 720.00 |
May | 284.09 | 124.24 | 159.86 | 281.99 | 71.38 | 0.00 | 0.00 | 744.00 |
June | 312.20 | 135.98 | 176.22 | 349.12 | 43.39 | 0.00 | 0.00 | 720.00 |
July | 315.62 | 145.67 | 169.95 | 364.18 | 34.73 | 0.00 | 0.00 | 744.00 |
August | 266.12 | 114.68 | 151.44 | 307.20 | 42.91 | 0.00 | 0.00 | 744.00 |
September | 238.45 | 113.10 | 125.35 | 250.54 | 84.23 | 0.00 | 0.00 | 720.00 |
October | 150.99 | 62.85 | 88.14 | 106.50 | 145.74 | 0.00 | 0.00 | 744.00 |
November | 89.31 | 28.99 | 60.33 | 31.06 | 244.64 | 0.00 | 0.00 | 720.00 |
December | 68.93 | 29.51 | 39.41 | 16.60 | 361.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 198.00 | 85.75 | 112.25 | 174.03 | 173.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 68.93 | 28.99 | 39.41 | 16.60 | 34.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 315.62 | 145.67 | 176.22 | 364.18 | 403.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.34 | 0.00 | 32.34 | 0.00 | 293.12 | 0.00 | 0.00 | 744.00 |
February | 41.00 | 0.00 | 41.00 | 0.41 | 232.31 | 0.00 | 0.00 | 672.00 |
March | 61.45 | 0.00 | 61.45 | 11.70 | 155.54 | 0.00 | 0.00 | 744.00 |
April | 71.21 | 0.57 | 70.64 | 32.74 | 101.16 | 0.00 | 0.00 | 720.00 |
May | 92.59 | 3.50 | 89.09 | 73.40 | 48.06 | 0.00 | 0.00 | 744.00 |
June | 108.35 | 10.03 | 98.32 | 109.26 | 28.53 | 0.00 | 0.00 | 720.00 |
July | 101.62 | 7.00 | 94.63 | 108.00 | 23.45 | 0.00 | 0.00 | 744.00 |
August | 85.15 | 1.72 | 83.44 | 94.12 | 30.07 | 0.00 | 0.00 | 744.00 |
September | 65.17 | 0.06 | 65.11 | 56.30 | 60.79 | 0.00 | 0.00 | 720.00 |
October | 48.39 | 0.00 | 48.39 | 16.32 | 107.75 | 0.00 | 0.00 | 744.00 |
November | 33.85 | 0.00 | 33.85 | 3.28 | 181.16 | 0.00 | 0.00 | 720.00 |
December | 21.96 | 0.00 | 21.96 | 0.00 | 261.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 63.71 | 1.91 | 61.80 | 42.38 | 126.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.96 | 0.00 | 21.96 | 0.00 | 23.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.35 | 10.03 | 98.32 | 109.26 | 293.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.92 | 0.00 | 11.92 | 0.00 | 108.06 | 0.00 | 0.00 | 744.00 |
February | 15.11 | 0.00 | 15.11 | 0.15 | 85.64 | 0.00 | 0.00 | 672.00 |
March | 22.65 | 0.00 | 22.65 | 4.31 | 57.34 | 0.00 | 0.00 | 744.00 |
April | 26.25 | 0.21 | 26.04 | 12.07 | 37.29 | 0.00 | 0.00 | 720.00 |
May | 34.13 | 1.29 | 32.84 | 27.06 | 17.72 | 0.00 | 0.00 | 744.00 |
June | 39.94 | 3.70 | 36.24 | 40.28 | 10.52 | 0.00 | 0.00 | 720.00 |
July | 37.46 | 2.58 | 34.88 | 39.81 | 8.64 | 0.00 | 0.00 | 744.00 |
August | 31.39 | 0.63 | 30.76 | 34.69 | 11.08 | 0.00 | 0.00 | 744.00 |
September | 24.02 | 0.02 | 24.00 | 20.75 | 22.41 | 0.00 | 0.00 | 720.00 |
October | 17.84 | 0.00 | 17.84 | 6.01 | 39.72 | 0.00 | 0.00 | 744.00 |
November | 12.48 | 0.00 | 12.48 | 1.21 | 66.78 | 0.00 | 0.00 | 720.00 |
December | 8.09 | 0.00 | 8.09 | 0.00 | 96.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 23.49 | 0.71 | 22.78 | 15.62 | 46.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.09 | 0.00 | 8.09 | 0.00 | 8.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 39.94 | 3.70 | 36.24 | 40.28 | 108.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 74.31 | 50.91 | 23.40 | 61.32 | 87.07 | 0.00 | 0.00 | 744.00 |
February | 80.14 | 54.38 | 25.76 | 67.18 | 69.44 | 0.00 | 0.00 | 672.00 |
March | 68.66 | 35.96 | 32.71 | 54.12 | 52.02 | 0.00 | 0.00 | 744.00 |
April | 61.19 | 28.04 | 33.15 | 48.01 | 36.77 | 0.00 | 0.00 | 720.00 |
May | 52.18 | 14.59 | 37.59 | 43.72 | 18.78 | 0.00 | 0.00 | 744.00 |
June | 49.81 | 9.94 | 39.87 | 48.27 | 11.30 | 0.00 | 0.00 | 720.00 |
July | 52.86 | 13.21 | 39.65 | 52.65 | 9.15 | 0.00 | 0.00 | 744.00 |
August | 58.58 | 20.28 | 38.30 | 61.25 | 11.50 | 0.00 | 0.00 | 744.00 |
September | 70.75 | 36.51 | 34.23 | 73.06 | 22.01 | 0.00 | 0.00 | 720.00 |
October | 76.25 | 48.08 | 28.17 | 75.95 | 36.69 | 0.00 | 0.00 | 744.00 |
November | 57.05 | 35.72 | 21.33 | 49.23 | 57.06 | 0.00 | 0.00 | 720.00 |
December | 60.72 | 45.98 | 14.74 | 55.36 | 81.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 63.45 | 32.68 | 30.77 | 57.46 | 40.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 49.81 | 9.94 | 14.74 | 43.72 | 9.15 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 80.14 | 54.38 | 39.87 | 75.95 | 87.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 201.70 | 138.18 | 63.52 | 166.45 | 236.31 | 0.00 | 0.00 | 744.00 |
February | 217.52 | 147.59 | 69.93 | 182.35 | 188.49 | 0.00 | 0.00 | 672.00 |
March | 186.36 | 97.59 | 88.77 | 146.91 | 141.18 | 0.00 | 0.00 | 744.00 |
April | 166.07 | 76.10 | 89.97 | 130.31 | 99.79 | 0.00 | 0.00 | 720.00 |
May | 141.62 | 39.60 | 102.02 | 118.65 | 50.97 | 0.00 | 0.00 | 744.00 |
June | 135.19 | 26.98 | 108.21 | 131.02 | 30.68 | 0.00 | 0.00 | 720.00 |
July | 143.47 | 35.86 | 107.61 | 142.92 | 24.84 | 0.00 | 0.00 | 744.00 |
August | 158.99 | 55.04 | 103.94 | 166.25 | 31.21 | 0.00 | 0.00 | 744.00 |
September | 192.02 | 99.10 | 92.92 | 198.30 | 59.74 | 0.00 | 0.00 | 720.00 |
October | 206.97 | 130.51 | 76.46 | 206.15 | 99.58 | 0.00 | 0.00 | 744.00 |
November | 154.84 | 96.94 | 57.90 | 133.63 | 154.86 | 0.00 | 0.00 | 720.00 |
December | 164.82 | 124.81 | 40.01 | 150.25 | 220.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 172.21 | 88.70 | 83.51 | 155.97 | 111.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 135.19 | 26.98 | 40.01 | 118.65 | 24.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 217.52 | 147.59 | 108.21 | 206.15 | 236.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.39 | 109.20 | 50.20 | 128.87 | 193.49 | 0.00 | 0.00 | 744.00 |
February | 171.89 | 116.63 | 55.26 | 139.34 | 156.65 | 0.00 | 0.00 | 672.00 |
March | 147.28 | 77.12 | 70.15 | 114.43 | 112.50 | 0.00 | 0.00 | 744.00 |
April | 131.24 | 60.14 | 71.10 | 99.53 | 80.17 | 0.00 | 0.00 | 720.00 |
May | 111.92 | 31.30 | 80.62 | 87.74 | 42.13 | 0.00 | 0.00 | 744.00 |
June | 106.84 | 21.32 | 85.52 | 98.67 | 24.11 | 0.00 | 0.00 | 720.00 |
July | 113.38 | 28.34 | 85.04 | 108.73 | 18.35 | 0.00 | 0.00 | 744.00 |
August | 125.64 | 43.50 | 82.14 | 127.38 | 23.39 | 0.00 | 0.00 | 744.00 |
September | 151.74 | 78.31 | 73.43 | 153.26 | 46.45 | 0.00 | 0.00 | 720.00 |
October | 163.56 | 103.14 | 60.42 | 159.54 | 79.71 | 0.00 | 0.00 | 744.00 |
November | 122.36 | 76.61 | 45.76 | 104.42 | 122.81 | 0.00 | 0.00 | 720.00 |
December | 130.25 | 98.63 | 31.62 | 117.34 | 177.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 136.09 | 70.10 | 65.99 | 119.84 | 89.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 106.84 | 21.32 | 31.62 | 87.74 | 18.35 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.89 | 116.63 | 85.52 | 159.54 | 193.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.88 | 41.44 | 60.45 | 29.23 | 417.41 | 0.00 | 0.00 | 744.00 |
February | 148.69 | 73.20 | 75.49 | 71.50 | 332.84 | 0.00 | 0.00 | 672.00 |
March | 177.45 | 66.01 | 111.45 | 102.84 | 215.63 | 0.00 | 0.00 | 744.00 |
April | 259.51 | 128.43 | 131.08 | 226.94 | 145.63 | 0.00 | 0.00 | 720.00 |
May | 259.99 | 104.08 | 155.91 | 255.14 | 75.75 | 0.00 | 0.00 | 744.00 |
June | 304.13 | 131.47 | 172.65 | 344.39 | 44.04 | 0.00 | 0.00 | 720.00 |
July | 326.66 | 154.95 | 171.71 | 383.50 | 33.81 | 0.00 | 0.00 | 744.00 |
August | 285.25 | 130.52 | 154.73 | 334.41 | 43.15 | 0.00 | 0.00 | 744.00 |
September | 231.49 | 109.70 | 121.79 | 243.05 | 85.93 | 0.00 | 0.00 | 720.00 |
October | 162.26 | 72.49 | 89.77 | 121.23 | 154.23 | 0.00 | 0.00 | 744.00 |
November | 96.81 | 35.95 | 60.86 | 42.33 | 253.25 | 0.00 | 0.00 | 720.00 |
December | 74.53 | 35.27 | 39.26 | 25.61 | 372.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 202.60 | 90.31 | 112.29 | 182.23 | 180.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 74.53 | 35.27 | 39.26 | 25.61 | 33.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 326.66 | 154.95 | 172.65 | 383.50 | 417.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.55 | 0.00 | 25.55 | 0.00 | 237.16 | 0.00 | 0.00 | 744.00 |
February | 32.40 | 0.00 | 32.40 | 0.46 | 191.49 | 0.00 | 0.00 | 672.00 |
March | 48.56 | 0.00 | 48.56 | 9.57 | 122.15 | 0.00 | 0.00 | 744.00 |
April | 56.28 | 0.45 | 55.83 | 23.50 | 80.99 | 0.00 | 0.00 | 720.00 |
May | 73.17 | 2.76 | 70.41 | 50.60 | 40.45 | 0.00 | 0.00 | 744.00 |
June | 85.62 | 7.93 | 77.70 | 78.64 | 24.17 | 0.00 | 0.00 | 720.00 |
July | 80.31 | 5.53 | 74.78 | 77.10 | 20.48 | 0.00 | 0.00 | 744.00 |
August | 67.29 | 1.36 | 65.94 | 67.86 | 25.63 | 0.00 | 0.00 | 744.00 |
September | 51.50 | 0.05 | 51.45 | 41.68 | 48.54 | 0.00 | 0.00 | 720.00 |
October | 38.24 | 0.00 | 38.24 | 13.04 | 84.71 | 0.00 | 0.00 | 744.00 |
November | 26.75 | 0.00 | 26.75 | 2.87 | 140.95 | 0.00 | 0.00 | 720.00 |
December | 17.35 | 0.00 | 17.35 | 0.00 | 206.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 50.35 | 1.51 | 48.84 | 30.62 | 101.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 17.35 | 0.00 | 17.35 | 0.00 | 20.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.62 | 7.93 | 77.70 | 78.64 | 237.16 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.88 | 41.44 | 60.45 | 30.43 | 413.48 | 0.00 | 0.00 | 744.00 |
February | 148.69 | 73.20 | 75.49 | 74.09 | 328.21 | 0.00 | 0.00 | 672.00 |
March | 177.45 | 66.01 | 111.45 | 106.37 | 213.16 | 0.00 | 0.00 | 744.00 |
April | 259.51 | 128.43 | 131.08 | 228.93 | 145.20 | 0.00 | 0.00 | 720.00 |
May | 259.99 | 104.08 | 155.91 | 252.85 | 77.46 | 0.00 | 0.00 | 744.00 |
June | 304.13 | 131.47 | 172.65 | 339.34 | 47.66 | 0.00 | 0.00 | 720.00 |
July | 326.66 | 154.95 | 171.71 | 375.69 | 40.00 | 0.00 | 0.00 | 744.00 |
August | 285.25 | 130.52 | 154.73 | 329.11 | 48.76 | 0.00 | 0.00 | 744.00 |
September | 231.49 | 109.70 | 121.79 | 243.74 | 88.09 | 0.00 | 0.00 | 720.00 |
October | 162.26 | 72.49 | 89.77 | 126.35 | 151.58 | 0.00 | 0.00 | 744.00 |
November | 96.81 | 35.95 | 60.86 | 44.78 | 250.35 | 0.00 | 0.00 | 720.00 |
December | 74.53 | 35.27 | 39.26 | 27.10 | 368.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 202.60 | 90.31 | 112.29 | 182.09 | 180.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 74.53 | 35.27 | 39.26 | 27.10 | 40.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 326.66 | 154.95 | 172.65 | 375.69 | 413.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 233.76 | 160.15 | 73.62 | 182.11 | 290.49 | 0.17 | 0.00 | 744.00 |
February | 252.10 | 171.05 | 81.05 | 197.83 | 236.40 | 0.00 | 0.00 | 672.00 |
March | 215.99 | 113.11 | 102.89 | 162.64 | 169.16 | 0.00 | 0.00 | 744.00 |
April | 192.48 | 88.20 | 104.27 | 144.87 | 118.36 | 0.00 | 0.00 | 720.00 |
May | 164.14 | 45.90 | 118.24 | 129.54 | 61.12 | 0.00 | 0.00 | 744.00 |
June | 156.69 | 31.27 | 125.42 | 147.75 | 34.26 | 0.00 | 0.00 | 720.00 |
July | 166.28 | 41.56 | 124.71 | 163.23 | 25.21 | 0.00 | 0.00 | 744.00 |
August | 184.26 | 63.79 | 120.47 | 189.13 | 33.03 | 0.00 | 0.00 | 744.00 |
September | 222.55 | 114.86 | 107.69 | 223.95 | 68.46 | 0.00 | 0.00 | 720.00 |
October | 239.87 | 151.26 | 88.61 | 229.27 | 120.43 | 0.00 | 0.00 | 744.00 |
November | 179.46 | 112.35 | 67.11 | 148.20 | 186.04 | 0.00 | 0.00 | 720.00 |
December | 191.02 | 144.65 | 46.37 | 166.20 | 267.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 199.59 | 102.80 | 96.78 | 173.61 | 133.74 | 0.17 | 0.00 | 8760.00 |
Minimum of Months | 156.69 | 31.27 | 46.37 | 129.54 | 25.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 252.10 | 171.05 | 125.42 | 229.27 | 290.49 | 0.17 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 178.87 | 0.00 | 178.87 | 0.00 | 1819.04 | 0.00 | 0.00 | 744.00 |
February | 226.78 | 0.00 | 226.78 | 0.13 | 1480.64 | 0.00 | 0.00 | 672.00 |
March | 339.92 | 0.00 | 339.91 | 34.95 | 1059.26 | 0.00 | 0.00 | 744.00 |
April | 393.93 | 3.16 | 390.77 | 126.02 | 741.29 | 0.00 | 0.00 | 720.00 |
May | 512.17 | 19.35 | 492.82 | 299.81 | 398.72 | 0.00 | 0.00 | 744.00 |
June | 599.34 | 55.48 | 543.86 | 495.11 | 255.49 | 0.00 | 0.00 | 720.00 |
July | 562.14 | 38.70 | 523.45 | 502.58 | 206.44 | 0.00 | 0.00 | 744.00 |
August | 471.04 | 9.49 | 461.54 | 436.96 | 259.92 | 0.00 | 0.00 | 744.00 |
September | 360.49 | 0.32 | 360.16 | 247.79 | 472.02 | 0.00 | 0.00 | 720.00 |
October | 267.69 | 0.00 | 267.69 | 46.29 | 795.43 | 0.00 | 0.00 | 744.00 |
November | 187.25 | 0.00 | 187.25 | 5.89 | 1211.04 | 0.00 | 0.00 | 720.00 |
December | 121.46 | 0.00 | 121.46 | 0.00 | 1669.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 352.42 | 10.58 | 341.83 | 184.07 | 861.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 121.46 | 0.00 | 121.46 | 0.00 | 206.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 599.34 | 55.48 | 543.86 | 502.58 | 1819.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 178.87 | 0.00 | 178.87 | 0.00 | 1884.99 | 0.00 | 0.00 | 744.00 |
February | 226.78 | 0.00 | 226.78 | 0.01 | 1549.96 | 0.00 | 0.00 | 672.00 |
March | 339.92 | 0.00 | 339.91 | 28.76 | 1114.18 | 0.00 | 0.00 | 744.00 |
April | 393.93 | 3.16 | 390.77 | 114.88 | 784.00 | 0.00 | 0.00 | 720.00 |
May | 512.17 | 19.35 | 492.82 | 279.78 | 423.54 | 0.00 | 0.00 | 744.00 |
June | 599.34 | 55.48 | 543.86 | 473.27 | 274.45 | 0.00 | 0.00 | 720.00 |
July | 562.14 | 38.70 | 523.45 | 481.78 | 222.47 | 0.00 | 0.00 | 744.00 |
August | 471.04 | 9.49 | 461.54 | 418.08 | 279.32 | 0.00 | 0.00 | 744.00 |
September | 360.49 | 0.32 | 360.16 | 234.12 | 500.81 | 0.00 | 0.00 | 720.00 |
October | 267.69 | 0.00 | 267.69 | 38.67 | 839.58 | 0.00 | 0.00 | 744.00 |
November | 187.25 | 0.00 | 187.25 | 4.23 | 1269.26 | 0.00 | 0.00 | 720.00 |
December | 121.46 | 0.00 | 121.46 | 0.00 | 1733.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 352.42 | 10.58 | 341.83 | 173.85 | 903.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 121.46 | 0.00 | 121.46 | 0.00 | 222.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 599.34 | 55.48 | 543.86 | 481.78 | 1884.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.55 | 0.00 | 25.55 | 0.00 | 262.88 | 1.33 | 0.00 | 744.00 |
February | 32.40 | 0.00 | 32.40 | 0.02 | 220.32 | 10.50 | 0.00 | 672.00 |
March | 48.56 | 0.00 | 48.56 | 4.98 | 154.91 | 0.00 | 0.00 | 744.00 |
April | 56.28 | 0.45 | 55.83 | 19.56 | 108.61 | 0.00 | 0.00 | 720.00 |
May | 73.17 | 2.76 | 70.41 | 48.33 | 60.58 | 0.00 | 0.00 | 744.00 |
June | 85.62 | 7.93 | 77.70 | 78.53 | 40.70 | 0.00 | 0.00 | 720.00 |
July | 80.31 | 5.53 | 74.78 | 81.09 | 33.28 | 0.00 | 0.00 | 744.00 |
August | 67.29 | 1.36 | 65.94 | 70.34 | 40.77 | 0.00 | 0.00 | 744.00 |
September | 51.50 | 0.05 | 51.45 | 40.06 | 69.90 | 0.00 | 0.00 | 720.00 |
October | 38.24 | 0.00 | 38.24 | 7.40 | 115.47 | 0.00 | 0.00 | 744.00 |
November | 26.75 | 0.00 | 26.75 | 1.18 | 174.63 | 0.00 | 0.00 | 720.00 |
December | 17.35 | 0.00 | 17.35 | 0.00 | 239.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 50.35 | 1.51 | 48.84 | 29.47 | 126.34 | 11.83 | 0.00 | 8760.00 |
Minimum of Months | 17.35 | 0.00 | 17.35 | 0.00 | 33.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.62 | 7.93 | 77.70 | 81.09 | 262.88 | 10.50 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.92 | 83.58 | 120.34 | 46.77 | 908.96 | 1.33 | 0.00 | 744.00 |
February | 271.51 | 119.51 | 152.01 | 101.58 | 743.98 | 7.83 | 0.00 | 672.00 |
March | 368.77 | 146.32 | 222.45 | 195.20 | 527.92 | 0.00 | 0.00 | 744.00 |
April | 450.08 | 196.16 | 253.91 | 350.36 | 386.57 | 0.00 | 0.00 | 720.00 |
May | 568.61 | 248.67 | 319.95 | 549.86 | 221.44 | 0.00 | 0.00 | 744.00 |
June | 624.87 | 272.17 | 352.70 | 693.33 | 155.01 | 0.00 | 0.00 | 720.00 |
July | 631.72 | 291.56 | 340.16 | 737.04 | 126.95 | 0.00 | 0.00 | 744.00 |
August | 532.64 | 229.54 | 303.11 | 617.32 | 152.52 | 0.00 | 0.00 | 744.00 |
September | 477.25 | 226.36 | 250.88 | 493.90 | 250.36 | 0.00 | 0.00 | 720.00 |
October | 302.20 | 125.78 | 176.42 | 187.04 | 400.17 | 0.00 | 0.00 | 744.00 |
November | 178.76 | 58.02 | 120.74 | 52.17 | 614.70 | 0.00 | 0.00 | 720.00 |
December | 137.96 | 59.07 | 78.89 | 29.84 | 845.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 396.31 | 171.64 | 224.67 | 339.16 | 443.06 | 9.17 | 0.00 | 8760.00 |
Minimum of Months | 137.96 | 58.02 | 78.89 | 29.84 | 126.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 631.72 | 291.56 | 352.70 | 737.04 | 908.96 | 7.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.39 | 109.20 | 50.20 | 126.15 | 213.57 | 1.33 | 0.00 | 744.00 |
February | 171.89 | 116.63 | 55.26 | 136.32 | 178.60 | 8.83 | 0.00 | 672.00 |
March | 147.28 | 77.12 | 70.15 | 107.48 | 139.54 | 0.00 | 0.00 | 744.00 |
April | 131.24 | 60.14 | 71.10 | 95.32 | 106.88 | 0.00 | 0.00 | 720.00 |
May | 111.92 | 31.30 | 80.62 | 84.23 | 63.89 | 0.00 | 0.00 | 744.00 |
June | 106.84 | 21.32 | 85.52 | 96.02 | 43.95 | 0.00 | 0.00 | 720.00 |
July | 113.38 | 28.34 | 85.04 | 108.71 | 35.44 | 0.00 | 0.00 | 744.00 |
August | 125.64 | 43.50 | 82.14 | 127.03 | 42.78 | 0.00 | 0.00 | 744.00 |
September | 151.74 | 78.31 | 73.43 | 151.64 | 69.02 | 0.00 | 0.00 | 720.00 |
October | 163.56 | 103.14 | 60.42 | 154.32 | 106.13 | 0.00 | 0.00 | 744.00 |
November | 122.36 | 76.61 | 45.76 | 100.02 | 151.12 | 0.00 | 0.00 | 720.00 |
December | 130.25 | 98.63 | 31.62 | 114.20 | 203.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 136.09 | 70.10 | 65.99 | 116.69 | 112.56 | 10.17 | 0.00 | 8760.00 |
Minimum of Months | 106.84 | 21.32 | 31.62 | 84.23 | 35.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 171.89 | 116.63 | 85.52 | 154.32 | 213.57 | 8.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.36 | 0.00 | 32.36 | 0.00 | 305.44 | 0.00 | 0.00 | 744.00 |
February | 41.03 | 0.00 | 41.03 | 0.13 | 241.39 | 0.00 | 0.00 | 672.00 |
March | 61.50 | 0.00 | 61.50 | 7.97 | 169.39 | 0.00 | 0.00 | 744.00 |
April | 71.27 | 0.57 | 70.70 | 24.69 | 118.64 | 0.00 | 0.00 | 720.00 |
May | 92.67 | 3.50 | 89.16 | 57.47 | 63.85 | 0.00 | 0.00 | 744.00 |
June | 108.44 | 10.04 | 98.40 | 92.59 | 40.32 | 0.00 | 0.00 | 720.00 |
July | 101.71 | 7.00 | 94.71 | 92.97 | 32.86 | 0.00 | 0.00 | 744.00 |
August | 85.22 | 1.72 | 83.51 | 80.61 | 41.23 | 0.00 | 0.00 | 744.00 |
September | 65.22 | 0.06 | 65.16 | 45.74 | 76.83 | 0.00 | 0.00 | 720.00 |
October | 48.43 | 0.00 | 48.43 | 9.45 | 130.34 | 0.00 | 0.00 | 744.00 |
November | 33.88 | 0.00 | 33.88 | 1.38 | 197.30 | 0.00 | 0.00 | 720.00 |
December | 21.98 | 0.00 | 21.98 | 0.00 | 274.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 63.76 | 1.91 | 61.85 | 34.63 | 140.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.98 | 0.00 | 21.98 | 0.00 | 32.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 108.44 | 10.04 | 98.40 | 92.97 | 305.44 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 28.96 | 0.00 | 28.96 | 0.00 | 273.27 | 0.00 | 0.00 | 744.00 |
February | 36.71 | 0.00 | 36.71 | 0.11 | 215.98 | 0.00 | 0.00 | 672.00 |
March | 55.02 | 0.00 | 55.02 | 7.13 | 151.56 | 0.00 | 0.00 | 744.00 |
April | 63.77 | 0.51 | 63.26 | 22.09 | 106.15 | 0.00 | 0.00 | 720.00 |
May | 82.91 | 3.13 | 79.78 | 51.42 | 57.13 | 0.00 | 0.00 | 744.00 |
June | 97.02 | 8.98 | 88.04 | 82.84 | 36.07 | 0.00 | 0.00 | 720.00 |
July | 91.00 | 6.26 | 84.73 | 83.18 | 29.40 | 0.00 | 0.00 | 744.00 |
August | 76.25 | 1.54 | 74.71 | 72.12 | 36.89 | 0.00 | 0.00 | 744.00 |
September | 58.35 | 0.05 | 58.30 | 40.92 | 68.74 | 0.00 | 0.00 | 720.00 |
October | 43.33 | 0.00 | 43.33 | 8.46 | 116.61 | 0.00 | 0.00 | 744.00 |
November | 30.31 | 0.00 | 30.31 | 1.24 | 176.53 | 0.00 | 0.00 | 720.00 |
December | 19.66 | 0.00 | 19.66 | 0.00 | 245.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 57.05 | 1.71 | 55.33 | 30.98 | 125.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.66 | 0.00 | 19.66 | 0.00 | 29.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 97.02 | 8.98 | 88.04 | 83.18 | 273.27 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 595.06 | 407.66 | 187.40 | 479.49 | 723.84 | 0.00 | 0.00 | 744.00 |
February | 641.74 | 435.42 | 206.31 | 527.18 | 575.10 | 0.00 | 0.00 | 672.00 |
March | 549.82 | 287.92 | 261.90 | 414.18 | 451.01 | 0.00 | 0.00 | 744.00 |
April | 489.96 | 224.53 | 265.43 | 358.27 | 344.30 | 0.00 | 0.00 | 720.00 |
May | 417.82 | 116.83 | 300.99 | 305.25 | 199.62 | 0.00 | 0.00 | 744.00 |
June | 398.86 | 79.60 | 319.26 | 341.35 | 129.43 | 0.00 | 0.00 | 720.00 |
July | 423.27 | 105.80 | 317.47 | 380.24 | 104.21 | 0.00 | 0.00 | 744.00 |
August | 469.06 | 162.39 | 306.67 | 451.80 | 126.89 | 0.00 | 0.00 | 744.00 |
September | 566.50 | 292.37 | 274.14 | 551.01 | 221.89 | 0.00 | 0.00 | 720.00 |
October | 610.61 | 385.05 | 225.57 | 574.58 | 349.65 | 0.00 | 0.00 | 744.00 |
November | 456.82 | 286.00 | 170.82 | 377.50 | 496.50 | 0.00 | 0.00 | 720.00 |
December | 486.26 | 368.21 | 118.05 | 432.80 | 682.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 508.06 | 261.69 | 246.37 | 432.31 | 366.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 398.86 | 79.60 | 118.05 | 305.25 | 104.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 641.74 | 435.42 | 319.26 | 574.58 | 723.84 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.216187E+10 | 0.148104E+10 | 0.680827E+09 | 0.177094E+10 | 0.242627E+10 |
February | 0.210582E+10 | 0.142881E+10 | 0.677004E+09 | 0.173033E+10 | 0.178251E+10 |
March | 0.199752E+10 | 0.104602E+10 | 0.951502E+09 | 0.152242E+10 | 0.150685E+10 |
April | 0.172261E+10 | 0.789409E+09 | 0.933202E+09 | 0.126137E+10 | 0.108890E+10 |
May | 0.151797E+10 | 0.424460E+09 | 0.109351E+10 | 0.111387E+10 | 0.666095E+09 |
June | 0.140231E+10 | 0.279854E+09 | 0.112246E+10 | 0.119196E+10 | 0.421652E+09 |
July | 0.153774E+10 | 0.384367E+09 | 0.115337E+10 | 0.136637E+10 | 0.359266E+09 |
August | 0.170409E+10 | 0.589967E+09 | 0.111413E+10 | 0.161813E+10 | 0.438136E+09 |
September | 0.199173E+10 | 0.102792E+10 | 0.963813E+09 | 0.190981E+10 | 0.735151E+09 |
October | 0.221837E+10 | 0.139889E+10 | 0.819486E+09 | 0.209232E+10 | 0.117473E+10 |
November | 0.160609E+10 | 0.100551E+10 | 0.600580E+09 | 0.134182E+10 | 0.159630E+10 |
December | 0.176660E+10 | 0.133773E+10 | 0.428872E+09 | 0.157813E+10 | 0.229142E+10 |
Annual Sum or Average | 0.217327E+11 | 0.111940E+11 | 0.105387E+11 | 0.184975E+11 | 0.144873E+11 |
Minimum of Months | 0.140231E+10 | 0.279854E+09 | 0.428872E+09 | 0.111387E+10 | 0.359266E+09 |
Maximum of Months | 0.221837E+10 | 0.148104E+10 | 0.115337E+10 | 0.209232E+10 | 0.242627E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.608768E+10 | 0.417051E+10 | 0.191716E+10 | 0.491680E+10 | 0.709756E+10 |
February | 0.592984E+10 | 0.402344E+10 | 0.190640E+10 | 0.479955E+10 | 0.529553E+10 |
March | 0.562489E+10 | 0.294553E+10 | 0.267937E+10 | 0.420640E+10 | 0.450958E+10 |
April | 0.485076E+10 | 0.222292E+10 | 0.262783E+10 | 0.349766E+10 | 0.327577E+10 |
May | 0.427449E+10 | 0.119525E+10 | 0.307924E+10 | 0.310690E+10 | 0.196042E+10 |
June | 0.394882E+10 | 0.788050E+09 | 0.316077E+10 | 0.333201E+10 | 0.124652E+10 |
July | 0.433017E+10 | 0.108235E+10 | 0.324782E+10 | 0.383073E+10 | 0.105370E+10 |
August | 0.479861E+10 | 0.166131E+10 | 0.313731E+10 | 0.454037E+10 | 0.129525E+10 |
September | 0.560859E+10 | 0.289456E+10 | 0.271403E+10 | 0.534801E+10 | 0.217164E+10 |
October | 0.624679E+10 | 0.393917E+10 | 0.230762E+10 | 0.581821E+10 | 0.350178E+10 |
November | 0.452265E+10 | 0.283146E+10 | 0.169119E+10 | 0.371518E+10 | 0.475458E+10 |
December | 0.497464E+10 | 0.376696E+10 | 0.120768E+10 | 0.437928E+10 | 0.677725E+10 |
Annual Sum or Average | 0.611979E+11 | 0.315215E+11 | 0.296764E+11 | 0.514911E+11 | 0.429396E+11 |
Minimum of Months | 0.394882E+10 | 0.788050E+09 | 0.120768E+10 | 0.310690E+10 | 0.105370E+10 |
Maximum of Months | 0.624679E+10 | 0.417051E+10 | 0.324782E+10 | 0.581821E+10 | 0.709756E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.790824E+10 | 0.541773E+10 | 0.249051E+10 | 0.639969E+10 | 0.983624E+10 |
February | 0.770320E+10 | 0.522668E+10 | 0.247652E+10 | 0.627877E+10 | 0.728701E+10 |
March | 0.730706E+10 | 0.382641E+10 | 0.348065E+10 | 0.549518E+10 | 0.622087E+10 |
April | 0.630141E+10 | 0.288770E+10 | 0.341371E+10 | 0.460433E+10 | 0.453529E+10 |
May | 0.555281E+10 | 0.155270E+10 | 0.400011E+10 | 0.409102E+10 | 0.268720E+10 |
June | 0.512974E+10 | 0.102372E+10 | 0.410601E+10 | 0.442385E+10 | 0.170304E+10 |
July | 0.562513E+10 | 0.140604E+10 | 0.421910E+10 | 0.509385E+10 | 0.142564E+10 |
August | 0.623367E+10 | 0.215813E+10 | 0.407554E+10 | 0.603525E+10 | 0.173948E+10 |
September | 0.728588E+10 | 0.376020E+10 | 0.352568E+10 | 0.709897E+10 | 0.293665E+10 |
October | 0.811494E+10 | 0.511721E+10 | 0.299773E+10 | 0.767792E+10 | 0.475584E+10 |
November | 0.587518E+10 | 0.367822E+10 | 0.219696E+10 | 0.485354E+10 | 0.659897E+10 |
December | 0.646233E+10 | 0.489350E+10 | 0.156884E+10 | 0.572821E+10 | 0.938641E+10 |
Annual Sum or Average | 0.794996E+11 | 0.409482E+11 | 0.385514E+11 | 0.677806E+11 | 0.591127E+11 |
Minimum of Months | 0.512974E+10 | 0.102372E+10 | 0.156884E+10 | 0.409102E+10 | 0.142564E+10 |
Maximum of Months | 0.811494E+10 | 0.541773E+10 | 0.421910E+10 | 0.767792E+10 | 0.983624E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.426567E+09 | 0.292230E+09 | 0.134337E+09 | 0.347122E+09 | 0.515252E+09 |
February | 0.415507E+09 | 0.281925E+09 | 0.133582E+09 | 0.339212E+09 | 0.376338E+09 |
March | 0.394140E+09 | 0.206395E+09 | 0.187745E+09 | 0.306774E+09 | 0.300925E+09 |
April | 0.339895E+09 | 0.155762E+09 | 0.184134E+09 | 0.258700E+09 | 0.207568E+09 |
May | 0.299516E+09 | 83752079.35 | 0.215764E+09 | 0.237384E+09 | 0.111999E+09 |
June | 0.276696E+09 | 55219150.57 | 0.221477E+09 | 0.257477E+09 | 62390613.75 |
July | 0.303417E+09 | 75840985.94 | 0.227576E+09 | 0.292818E+09 | 49319381.16 |
August | 0.336242E+09 | 0.116409E+09 | 0.219833E+09 | 0.342616E+09 | 62656473.76 |
September | 0.392998E+09 | 0.202824E+09 | 0.190174E+09 | 0.397987E+09 | 0.120939E+09 |
October | 0.437717E+09 | 0.276020E+09 | 0.161696E+09 | 0.428099E+09 | 0.213774E+09 |
November | 0.316905E+09 | 0.198402E+09 | 0.118503E+09 | 0.271184E+09 | 0.317947E+09 |
December | 0.348576E+09 | 0.263953E+09 | 84622584.52 | 0.315110E+09 | 0.474354E+09 |
Annual Sum or Average | 0.428818E+10 | 0.220873E+10 | 0.207944E+10 | 0.379448E+10 | 0.281346E+10 |
Minimum of Months | 0.276696E+09 | 55219150.57 | 84622584.52 | 0.237384E+09 | 49319381.16 |
Maximum of Months | 0.437717E+09 | 0.292230E+09 | 0.227576E+09 | 0.428099E+09 | 0.515252E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272662E+09 | 0.110889E+09 | 0.161773E+09 | 79054818.88 | 0.110980E+10 |
February | 0.359413E+09 | 0.176949E+09 | 0.182464E+09 | 0.174730E+09 | 0.797399E+09 |
March | 0.474903E+09 | 0.176644E+09 | 0.298259E+09 | 0.275991E+09 | 0.576644E+09 |
April | 0.672095E+09 | 0.332611E+09 | 0.339483E+09 | 0.591703E+09 | 0.377254E+09 |
May | 0.695793E+09 | 0.278545E+09 | 0.417248E+09 | 0.690007E+09 | 0.201781E+09 |
June | 0.787647E+09 | 0.340499E+09 | 0.447148E+09 | 0.898154E+09 | 0.114149E+09 |
July | 0.874206E+09 | 0.414672E+09 | 0.459535E+09 | 0.103262E+10 | 91028807.31 |
August | 0.763385E+09 | 0.349306E+09 | 0.414079E+09 | 0.900560E+09 | 0.115736E+09 |
September | 0.599529E+09 | 0.284118E+09 | 0.315411E+09 | 0.632355E+09 | 0.223823E+09 |
October | 0.434228E+09 | 0.193989E+09 | 0.240239E+09 | 0.325629E+09 | 0.413929E+09 |
November | 0.250734E+09 | 93106182.22 | 0.157628E+09 | 0.109351E+09 | 0.656169E+09 |
December | 0.199447E+09 | 94391805.94 | 0.105055E+09 | 68551104.98 | 0.992680E+09 |
Annual Sum or Average | 0.638404E+10 | 0.284572E+10 | 0.353832E+10 | 0.577870E+10 | 0.567039E+10 |
Minimum of Months | 0.199447E+09 | 93106182.22 | 0.105055E+09 | 68551104.98 | 91028807.31 |
Maximum of Months | 0.874206E+09 | 0.414672E+09 | 0.459535E+09 | 0.103262E+10 | 0.110980E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68388766.43 | 0.00 | 68388766.43 | 7838.70 | 0.631139E+09 |
February | 78312909.17 | 0.00 | 78312909.17 | 1076511.78 | 0.459627E+09 |
March | 0.129960E+09 | 1099.13 | 0.129959E+09 | 25245038.18 | 0.327037E+09 |
April | 0.145753E+09 | 1168822.97 | 0.144585E+09 | 61756593.56 | 0.209285E+09 |
May | 0.195819E+09 | 7398927.34 | 0.188420E+09 | 0.139656E+09 | 0.106385E+09 |
June | 0.221753E+09 | 20526356.82 | 0.201227E+09 | 0.207747E+09 | 60980106.00 |
July | 0.214924E+09 | 14794636.40 | 0.200129E+09 | 0.210759E+09 | 52381315.46 |
August | 0.180091E+09 | 3629439.91 | 0.176461E+09 | 0.184930E+09 | 65880322.26 |
September | 0.133379E+09 | 119692.30 | 0.133259E+09 | 0.108950E+09 | 0.125221E+09 |
October | 0.102344E+09 | 0.00 | 0.102344E+09 | 34242128.75 | 0.228008E+09 |
November | 69281530.96 | 0.00 | 69281530.96 | 7154943.55 | 0.365929E+09 |
December | 46438156.31 | 0.00 | 46438156.31 | 0.00 | 0.552045E+09 |
Annual Sum or Average | 0.158645E+10 | 47638974.86 | 0.153881E+10 | 0.981525E+09 | 0.318392E+10 |
Minimum of Months | 46438156.31 | 0.00 | 46438156.31 | 0.00 | 52381315.46 |
Maximum of Months | 0.221753E+09 | 20526356.82 | 0.201227E+09 | 0.210759E+09 | 0.631139E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272662E+09 | 0.110889E+09 | 0.161773E+09 | 82216123.84 | 0.109942E+10 |
February | 0.359413E+09 | 0.176949E+09 | 0.182464E+09 | 0.180559E+09 | 0.786614E+09 |
March | 0.474903E+09 | 0.176644E+09 | 0.298259E+09 | 0.285182E+09 | 0.569969E+09 |
April | 0.672095E+09 | 0.332611E+09 | 0.339483E+09 | 0.596832E+09 | 0.375624E+09 |
May | 0.695793E+09 | 0.278545E+09 | 0.417248E+09 | 0.686342E+09 | 0.204378E+09 |
June | 0.787647E+09 | 0.340499E+09 | 0.447148E+09 | 0.887865E+09 | 0.120553E+09 |
July | 0.874206E+09 | 0.414672E+09 | 0.459535E+09 | 0.101570E+10 | 0.102682E+09 |
August | 0.763385E+09 | 0.349306E+09 | 0.414079E+09 | 0.889419E+09 | 0.126125E+09 |
September | 0.599529E+09 | 0.284118E+09 | 0.315411E+09 | 0.634814E+09 | 0.227477E+09 |
October | 0.434228E+09 | 0.193989E+09 | 0.240239E+09 | 0.337950E+09 | 0.407361E+09 |
November | 0.250734E+09 | 93106182.22 | 0.157628E+09 | 0.115368E+09 | 0.648549E+09 |
December | 0.199447E+09 | 94391805.94 | 0.105055E+09 | 72525886.54 | 0.982517E+09 |
Annual Sum or Average | 0.638404E+10 | 0.284572E+10 | 0.353832E+10 | 0.578477E+10 | 0.565126E+10 |
Minimum of Months | 0.199447E+09 | 93106182.22 | 0.105055E+09 | 72525886.54 | 0.102682E+09 |
Maximum of Months | 0.874206E+09 | 0.414672E+09 | 0.459535E+09 | 0.101570E+10 | 0.109942E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.341186E+09 | 0.233738E+09 | 0.107448E+09 | 0.285753E+09 | 0.364873E+09 |
February | 0.332340E+09 | 0.225495E+09 | 0.106845E+09 | 0.273639E+09 | 0.289424E+09 |
March | 0.315249E+09 | 0.165083E+09 | 0.150166E+09 | 0.240461E+09 | 0.244073E+09 |
April | 0.271862E+09 | 0.124584E+09 | 0.147278E+09 | 0.192226E+09 | 0.206838E+09 |
May | 0.239565E+09 | 66988341.30 | 0.172577E+09 | 0.158261E+09 | 0.137859E+09 |
June | 0.221313E+09 | 44166536.92 | 0.177146E+09 | 0.173627E+09 | 91298472.53 |
July | 0.242686E+09 | 60660724.97 | 0.182025E+09 | 0.200900E+09 | 78129494.58 |
August | 0.268940E+09 | 93108532.74 | 0.175831E+09 | 0.242202E+09 | 93673913.58 |
September | 0.314336E+09 | 0.162227E+09 | 0.152109E+09 | 0.291600E+09 | 0.149447E+09 |
October | 0.350104E+09 | 0.220772E+09 | 0.129331E+09 | 0.313739E+09 | 0.233669E+09 |
November | 0.253473E+09 | 0.158690E+09 | 94783559.68 | 0.204306E+09 | 0.284554E+09 |
December | 0.278805E+09 | 0.211121E+09 | 67684606.97 | 0.255113E+09 | 0.343244E+09 |
Annual Sum or Average | 0.342986E+10 | 0.176663E+10 | 0.166322E+10 | 0.283183E+10 | 0.251708E+10 |
Minimum of Months | 0.221313E+09 | 44166536.92 | 67684606.97 | 0.158261E+09 | 78129494.58 |
Maximum of Months | 0.350104E+09 | 0.233738E+09 | 0.182025E+09 | 0.313739E+09 | 0.364873E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 54718265.40 | 0.00 | 54718265.40 | 0.00 | 0.520954E+09 |
February | 62658631.99 | 0.00 | 62658631.99 | 590380.80 | 0.379392E+09 |
March | 0.103982E+09 | 879.42 | 0.103981E+09 | 19011128.63 | 0.269817E+09 |
April | 0.116618E+09 | 935182.32 | 0.115683E+09 | 51607852.14 | 0.170097E+09 |
May | 0.156676E+09 | 5919926.48 | 0.150756E+09 | 0.117507E+09 | 84553050.65 |
June | 0.177426E+09 | 16423262.16 | 0.161003E+09 | 0.175457E+09 | 47034029.46 |
July | 0.171962E+09 | 11837278.01 | 0.160125E+09 | 0.181187E+09 | 37965300.65 |
August | 0.144092E+09 | 2903936.81 | 0.141188E+09 | 0.158397E+09 | 48875359.75 |
September | 0.106717E+09 | 95766.54 | 0.106622E+09 | 92032478.61 | 98818901.83 |
October | 81886317.06 | 0.00 | 81886317.06 | 26386487.38 | 0.186807E+09 |
November | 55432571.70 | 0.00 | 55432571.70 | 5021073.85 | 0.304582E+09 |
December | 37155449.56 | 0.00 | 37155449.56 | 0.00 | 0.457940E+09 |
Annual Sum or Average | 0.126932E+10 | 38116231.74 | 0.123121E+10 | 0.827199E+09 | 0.260683E+10 |
Minimum of Months | 37155449.56 | 0.00 | 37155449.56 | 0.00 | 37965300.65 |
Maximum of Months | 0.177426E+09 | 16423262.16 | 0.161003E+09 | 0.181187E+09 | 0.520954E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272883E+09 | 0.111842E+09 | 0.161041E+09 | 64175831.28 | 0.109238E+10 |
February | 0.328178E+09 | 0.144447E+09 | 0.183731E+09 | 0.128707E+09 | 0.780530E+09 |
March | 0.493487E+09 | 0.195806E+09 | 0.297680E+09 | 0.285452E+09 | 0.561223E+09 |
April | 0.582862E+09 | 0.254039E+09 | 0.328822E+09 | 0.474024E+09 | 0.366339E+09 |
May | 0.760919E+09 | 0.332763E+09 | 0.428156E+09 | 0.755710E+09 | 0.189497E+09 |
June | 0.809220E+09 | 0.352463E+09 | 0.456758E+09 | 0.912694E+09 | 0.107364E+09 |
July | 0.845368E+09 | 0.390166E+09 | 0.455201E+09 | 0.987933E+09 | 84559399.43 |
August | 0.712780E+09 | 0.307163E+09 | 0.405616E+09 | 0.829160E+09 | 0.107531E+09 |
September | 0.618050E+09 | 0.293149E+09 | 0.324901E+09 | 0.645792E+09 | 0.216619E+09 |
October | 0.404405E+09 | 0.168325E+09 | 0.236080E+09 | 0.273640E+09 | 0.398936E+09 |
November | 0.231501E+09 | 75138110.57 | 0.156363E+09 | 76501071.67 | 0.643918E+09 |
December | 0.184617E+09 | 79051632.14 | 0.105565E+09 | 43391991.15 | 0.981108E+09 |
Annual Sum or Average | 0.624427E+10 | 0.270435E+10 | 0.353991E+10 | 0.547718E+10 | 0.553001E+10 |
Minimum of Months | 0.184617E+09 | 75138110.57 | 0.105565E+09 | 43391991.15 | 84559399.43 |
Maximum of Months | 0.845368E+09 | 0.390166E+09 | 0.456758E+09 | 0.987933E+09 | 0.109238E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.426567E+09 | 0.292230E+09 | 0.134337E+09 | 0.346638E+09 | 0.514539E+09 |
February | 0.415507E+09 | 0.281925E+09 | 0.133582E+09 | 0.338566E+09 | 0.374615E+09 |
March | 0.394140E+09 | 0.206395E+09 | 0.187745E+09 | 0.304321E+09 | 0.300272E+09 |
April | 0.339895E+09 | 0.155762E+09 | 0.184134E+09 | 0.257525E+09 | 0.205357E+09 |
May | 0.299516E+09 | 83752079.35 | 0.215764E+09 | 0.233882E+09 | 0.111955E+09 |
June | 0.276696E+09 | 55219150.57 | 0.221477E+09 | 0.255461E+09 | 61839305.02 |
July | 0.303417E+09 | 75840985.94 | 0.227576E+09 | 0.291420E+09 | 48066328.94 |
August | 0.336242E+09 | 0.116409E+09 | 0.219833E+09 | 0.341638E+09 | 61609374.21 |
September | 0.392998E+09 | 0.202824E+09 | 0.190174E+09 | 0.395676E+09 | 0.120157E+09 |
October | 0.437717E+09 | 0.276020E+09 | 0.161696E+09 | 0.426532E+09 | 0.212766E+09 |
November | 0.316905E+09 | 0.198402E+09 | 0.118503E+09 | 0.270865E+09 | 0.317329E+09 |
December | 0.348576E+09 | 0.263953E+09 | 84622584.52 | 0.314960E+09 | 0.473870E+09 |
Annual Sum or Average | 0.428818E+10 | 0.220873E+10 | 0.207944E+10 | 0.377748E+10 | 0.280238E+10 |
Minimum of Months | 0.276696E+09 | 55219150.57 | 84622584.52 | 0.233882E+09 | 48066328.94 |
Maximum of Months | 0.437717E+09 | 0.292230E+09 | 0.227576E+09 | 0.426532E+09 | 0.514539E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68388766.43 | 0.00 | 68388766.43 | 3279.09 | 0.630649E+09 |
February | 78312909.17 | 0.00 | 78312909.17 | 873339.88 | 0.458049E+09 |
March | 0.129960E+09 | 1099.13 | 0.129959E+09 | 24260677.26 | 0.327538E+09 |
April | 0.145753E+09 | 1168822.97 | 0.144585E+09 | 61147351.22 | 0.206979E+09 |
May | 0.195819E+09 | 7398927.34 | 0.188420E+09 | 0.137445E+09 | 0.105677E+09 |
June | 0.221753E+09 | 20526356.82 | 0.201227E+09 | 0.206666E+09 | 59453924.92 |
July | 0.214924E+09 | 14794636.40 | 0.200129E+09 | 0.211158E+09 | 49191786.11 |
August | 0.180091E+09 | 3629439.91 | 0.176461E+09 | 0.185621E+09 | 62699520.47 |
September | 0.133379E+09 | 119692.30 | 0.133259E+09 | 0.107158E+09 | 0.123567E+09 |
October | 0.102344E+09 | 0.00 | 0.102344E+09 | 33306340.79 | 0.226869E+09 |
November | 69281530.96 | 0.00 | 69281530.96 | 6963347.56 | 0.365314E+09 |
December | 46438156.31 | 0.00 | 46438156.31 | 0.00 | 0.552024E+09 |
Annual Sum or Average | 0.158645E+10 | 47638974.86 | 0.153881E+10 | 0.974601E+09 | 0.316801E+10 |
Minimum of Months | 46438156.31 | 0.00 | 46438156.31 | 0.00 | 49191786.11 |
Maximum of Months | 0.221753E+09 | 20526356.82 | 0.201227E+09 | 0.211158E+09 | 0.630649E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272883E+09 | 0.111842E+09 | 0.161041E+09 | 65636779.78 | 0.108029E+10 |
February | 0.328178E+09 | 0.144447E+09 | 0.183731E+09 | 0.131965E+09 | 0.766886E+09 |
March | 0.493487E+09 | 0.195806E+09 | 0.297680E+09 | 0.293116E+09 | 0.552494E+09 |
April | 0.582862E+09 | 0.254039E+09 | 0.328822E+09 | 0.479344E+09 | 0.363523E+09 |
May | 0.760919E+09 | 0.332763E+09 | 0.428156E+09 | 0.755270E+09 | 0.191173E+09 |
June | 0.809220E+09 | 0.352463E+09 | 0.456758E+09 | 0.904920E+09 | 0.112465E+09 |
July | 0.845368E+09 | 0.390166E+09 | 0.455201E+09 | 0.975427E+09 | 93030189.44 |
August | 0.712780E+09 | 0.307163E+09 | 0.405616E+09 | 0.822818E+09 | 0.114942E+09 |
September | 0.618050E+09 | 0.293149E+09 | 0.324901E+09 | 0.649395E+09 | 0.218335E+09 |
October | 0.404405E+09 | 0.168325E+09 | 0.236080E+09 | 0.285249E+09 | 0.390341E+09 |
November | 0.231501E+09 | 75138110.57 | 0.156363E+09 | 80506849.54 | 0.634103E+09 |
December | 0.184617E+09 | 79051632.14 | 0.105565E+09 | 44455054.42 | 0.968559E+09 |
Annual Sum or Average | 0.624427E+10 | 0.270435E+10 | 0.353991E+10 | 0.548810E+10 | 0.548614E+10 |
Minimum of Months | 0.184617E+09 | 75138110.57 | 0.105565E+09 | 44455054.42 | 93030189.44 |
Maximum of Months | 0.845368E+09 | 0.390166E+09 | 0.456758E+09 | 0.975427E+09 | 0.108029E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86610057.59 | 0.00 | 86610057.59 | 0.00 | 0.785100E+09 |
February | 99178358.19 | 0.00 | 99178358.19 | 985844.22 | 0.562016E+09 |
March | 0.164586E+09 | 1391.97 | 0.164584E+09 | 31327342.83 | 0.416612E+09 |
April | 0.184588E+09 | 1480240.54 | 0.183107E+09 | 84864928.29 | 0.262205E+09 |
May | 0.247993E+09 | 9370274.62 | 0.238623E+09 | 0.196598E+09 | 0.128725E+09 |
June | 0.280836E+09 | 25995335.77 | 0.254841E+09 | 0.283192E+09 | 73952095.06 |
July | 0.272188E+09 | 18736473.51 | 0.253451E+09 | 0.289276E+09 | 62797240.35 |
August | 0.228074E+09 | 4596456.64 | 0.223477E+09 | 0.252079E+09 | 80536313.74 |
September | 0.168916E+09 | 151582.75 | 0.168765E+09 | 0.145930E+09 | 0.157576E+09 |
October | 0.129613E+09 | 0.00 | 0.129613E+09 | 43702426.31 | 0.288595E+09 |
November | 87740687.54 | 0.00 | 87740687.54 | 8490017.10 | 0.469570E+09 |
December | 58810994.88 | 0.00 | 58810994.88 | 0.00 | 0.699078E+09 |
Annual Sum or Average | 0.200913E+10 | 60331755.80 | 0.194880E+10 | 0.133645E+10 | 0.398676E+10 |
Minimum of Months | 58810994.88 | 0.00 | 58810994.88 | 0.00 | 62797240.35 |
Maximum of Months | 0.280836E+09 | 25995335.77 | 0.254841E+09 | 0.289276E+09 | 0.785100E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31928053.47 | 0.00 | 31928053.47 | 0.00 | 0.289420E+09 |
February | 36561249.48 | 0.00 | 36561249.48 | 363423.00 | 0.207182E+09 |
March | 60673113.71 | 513.14 | 60672600.57 | 11548555.73 | 0.153580E+09 |
April | 68046624.82 | 545677.95 | 67500946.87 | 31284726.55 | 96659586.46 |
May | 91420465.78 | 3454271.22 | 87966194.56 | 72474203.91 | 47453234.44 |
June | 0.103528E+09 | 9582957.15 | 93944879.03 | 0.104396E+09 | 27261804.36 |
July | 0.100340E+09 | 6907039.95 | 93432647.15 | 0.106639E+09 | 23149663.02 |
August | 84077416.20 | 1694444.24 | 82382971.96 | 92926749.17 | 29689019.99 |
September | 62269501.28 | 55879.68 | 62213621.60 | 53795983.02 | 58089104.89 |
October | 47780584.61 | 0.00 | 47780584.61 | 16110523.91 | 0.106388E+09 |
November | 32344850.48 | 0.00 | 32344850.48 | 3129771.85 | 0.173103E+09 |
December | 21680167.89 | 0.00 | 21680167.89 | 0.00 | 0.257709E+09 |
Annual Sum or Average | 0.740650E+09 | 22240783.33 | 0.718409E+09 | 0.492669E+09 | 0.146969E+10 |
Minimum of Months | 21680167.89 | 0.00 | 21680167.89 | 0.00 | 23149663.02 |
Maximum of Months | 0.103528E+09 | 9582957.15 | 93944879.03 | 0.106639E+09 | 0.289420E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.199035E+09 | 0.136353E+09 | 62681045.37 | 0.164250E+09 | 0.233197E+09 |
February | 0.193874E+09 | 0.131545E+09 | 62329030.32 | 0.162529E+09 | 0.168000E+09 |
March | 0.183904E+09 | 96303001.02 | 87600984.34 | 0.144968E+09 | 0.139318E+09 |
April | 0.158594E+09 | 72677694.40 | 85916151.51 | 0.124444E+09 | 95300886.54 |
May | 0.139753E+09 | 39078382.73 | 0.100675E+09 | 0.117088E+09 | 50301315.01 |
June | 0.129105E+09 | 25765033.14 | 0.103340E+09 | 0.125125E+09 | 29294618.70 |
July | 0.141573E+09 | 35387098.43 | 0.106186E+09 | 0.141031E+09 | 24514033.66 |
August | 0.156889E+09 | 54315882.54 | 0.102573E+09 | 0.164061E+09 | 30802356.86 |
September | 0.183371E+09 | 94636674.59 | 88734383.82 | 0.189373E+09 | 57046563.37 |
October | 0.204237E+09 | 0.128790E+09 | 75446793.59 | 0.203431E+09 | 98265730.44 |
November | 0.147867E+09 | 92573492.46 | 55293027.86 | 0.127613E+09 | 0.147889E+09 |
December | 0.162644E+09 | 0.123159E+09 | 39484556.93 | 0.148272E+09 | 0.218043E+09 |
Annual Sum or Average | 0.200085E+10 | 0.103059E+10 | 0.970260E+09 | 0.181218E+10 | 0.129197E+10 |
Minimum of Months | 0.129105E+09 | 25765033.14 | 39484556.93 | 0.117088E+09 | 24514033.66 |
Maximum of Months | 0.204237E+09 | 0.136353E+09 | 0.106186E+09 | 0.203431E+09 | 0.233197E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.540220E+09 | 0.370091E+09 | 0.170129E+09 | 0.445807E+09 | 0.632945E+09 |
February | 0.526214E+09 | 0.357040E+09 | 0.169174E+09 | 0.441136E+09 | 0.455986E+09 |
March | 0.499153E+09 | 0.261386E+09 | 0.237767E+09 | 0.393472E+09 | 0.378136E+09 |
April | 0.430456E+09 | 0.197262E+09 | 0.233194E+09 | 0.337767E+09 | 0.258666E+09 |
May | 0.379319E+09 | 0.106067E+09 | 0.273252E+09 | 0.317801E+09 | 0.136528E+09 |
June | 0.350418E+09 | 69931570.06 | 0.280486E+09 | 0.339615E+09 | 79511587.24 |
July | 0.384259E+09 | 96047823.40 | 0.288211E+09 | 0.382786E+09 | 66536101.59 |
August | 0.425829E+09 | 0.147424E+09 | 0.278404E+09 | 0.445295E+09 | 83603897.01 |
September | 0.497707E+09 | 0.256863E+09 | 0.240843E+09 | 0.513997E+09 | 0.154836E+09 |
October | 0.554340E+09 | 0.349562E+09 | 0.204778E+09 | 0.552154E+09 | 0.266713E+09 |
November | 0.401340E+09 | 0.251263E+09 | 0.150077E+09 | 0.346367E+09 | 0.401400E+09 |
December | 0.441449E+09 | 0.334280E+09 | 0.107169E+09 | 0.402441E+09 | 0.591814E+09 |
Annual Sum or Average | 0.543070E+10 | 0.279722E+10 | 0.263348E+10 | 0.491864E+10 | 0.350668E+10 |
Minimum of Months | 0.350418E+09 | 69931570.06 | 0.107169E+09 | 0.317801E+09 | 66536101.59 |
Maximum of Months | 0.554340E+09 | 0.370091E+09 | 0.288211E+09 | 0.552154E+09 | 0.632945E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.426917E+09 | 0.292470E+09 | 0.134447E+09 | 0.345162E+09 | 0.518238E+09 |
February | 0.415848E+09 | 0.282156E+09 | 0.133692E+09 | 0.337101E+09 | 0.378961E+09 |
March | 0.394463E+09 | 0.206564E+09 | 0.187899E+09 | 0.306486E+09 | 0.301331E+09 |
April | 0.340174E+09 | 0.155889E+09 | 0.184285E+09 | 0.257982E+09 | 0.207789E+09 |
May | 0.299762E+09 | 83820784.91 | 0.215941E+09 | 0.234999E+09 | 0.112831E+09 |
June | 0.276923E+09 | 55264449.30 | 0.221658E+09 | 0.255762E+09 | 62497920.69 |
July | 0.303666E+09 | 75903201.68 | 0.227763E+09 | 0.291223E+09 | 49137475.70 |
August | 0.336518E+09 | 0.116504E+09 | 0.220013E+09 | 0.341170E+09 | 62661053.41 |
September | 0.393320E+09 | 0.202990E+09 | 0.190330E+09 | 0.397243E+09 | 0.120390E+09 |
October | 0.438076E+09 | 0.276247E+09 | 0.161829E+09 | 0.427320E+09 | 0.213491E+09 |
November | 0.317165E+09 | 0.198565E+09 | 0.118600E+09 | 0.270668E+09 | 0.318316E+09 |
December | 0.348862E+09 | 0.264170E+09 | 84692004.19 | 0.314290E+09 | 0.476162E+09 |
Annual Sum or Average | 0.429169E+10 | 0.221054E+10 | 0.208115E+10 | 0.377941E+10 | 0.282181E+10 |
Minimum of Months | 0.276923E+09 | 55264449.30 | 84692004.19 | 0.234999E+09 | 49137475.70 |
Maximum of Months | 0.438076E+09 | 0.292470E+09 | 0.227763E+09 | 0.427320E+09 | 0.518238E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272886E+09 | 0.110980E+09 | 0.161906E+09 | 78300076.96 | 0.111798E+10 |
February | 0.359708E+09 | 0.177094E+09 | 0.182614E+09 | 0.172966E+09 | 0.805204E+09 |
March | 0.475292E+09 | 0.176789E+09 | 0.298503E+09 | 0.275448E+09 | 0.577532E+09 |
April | 0.672646E+09 | 0.332884E+09 | 0.339762E+09 | 0.588234E+09 | 0.377464E+09 |
May | 0.696364E+09 | 0.278773E+09 | 0.417591E+09 | 0.683367E+09 | 0.202902E+09 |
June | 0.788293E+09 | 0.340778E+09 | 0.447515E+09 | 0.892646E+09 | 0.114157E+09 |
July | 0.874923E+09 | 0.415012E+09 | 0.459912E+09 | 0.102716E+10 | 90568173.20 |
August | 0.764011E+09 | 0.349593E+09 | 0.414418E+09 | 0.895677E+09 | 0.115583E+09 |
September | 0.600021E+09 | 0.284351E+09 | 0.315669E+09 | 0.629993E+09 | 0.222738E+09 |
October | 0.434584E+09 | 0.194148E+09 | 0.240436E+09 | 0.324695E+09 | 0.413095E+09 |
November | 0.250940E+09 | 93182561.37 | 0.157758E+09 | 0.109720E+09 | 0.656427E+09 |
December | 0.199611E+09 | 94469239.74 | 0.105141E+09 | 68601108.91 | 0.997094E+09 |
Annual Sum or Average | 0.638928E+10 | 0.284805E+10 | 0.354123E+10 | 0.574681E+10 | 0.569074E+10 |
Minimum of Months | 0.199611E+09 | 93182561.37 | 0.105141E+09 | 68601108.91 | 90568173.20 |
Maximum of Months | 0.874923E+09 | 0.415012E+09 | 0.459912E+09 | 0.102716E+10 | 0.111798E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68444868.78 | 0.00 | 68444868.78 | 10471.48 | 0.635205E+09 |
February | 78377152.73 | 0.00 | 78377152.73 | 1107318.26 | 0.463249E+09 |
March | 0.130066E+09 | 1100.03 | 0.130065E+09 | 25627394.82 | 0.327158E+09 |
April | 0.145873E+09 | 1169781.80 | 0.144703E+09 | 60903124.89 | 0.209915E+09 |
May | 0.195980E+09 | 7404997.01 | 0.188575E+09 | 0.135526E+09 | 0.108334E+09 |
June | 0.221935E+09 | 20543195.50 | 0.201392E+09 | 0.203835E+09 | 62648804.27 |
July | 0.215100E+09 | 14806773.10 | 0.200294E+09 | 0.206517E+09 | 54849095.67 |
August | 0.180239E+09 | 3632417.30 | 0.176606E+09 | 0.181748E+09 | 68657197.36 |
September | 0.133488E+09 | 119790.49 | 0.133369E+09 | 0.108034E+09 | 0.125808E+09 |
October | 0.102428E+09 | 0.00 | 0.102428E+09 | 34939532.95 | 0.226883E+09 |
November | 69338365.69 | 0.00 | 69338365.69 | 7443965.98 | 0.365330E+09 |
December | 46476251.60 | 0.00 | 46476251.60 | 0.00 | 0.554145E+09 |
Annual Sum or Average | 0.158775E+10 | 47678055.23 | 0.154007E+10 | 0.965691E+09 | 0.320218E+10 |
Minimum of Months | 46476251.60 | 0.00 | 46476251.60 | 0.00 | 54849095.67 |
Maximum of Months | 0.221935E+09 | 20543195.50 | 0.201392E+09 | 0.206517E+09 | 0.635205E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.272886E+09 | 0.110980E+09 | 0.161906E+09 | 81509689.06 | 0.110745E+10 |
February | 0.359708E+09 | 0.177094E+09 | 0.182614E+09 | 0.179236E+09 | 0.793999E+09 |
March | 0.475292E+09 | 0.176789E+09 | 0.298503E+09 | 0.284911E+09 | 0.570925E+09 |
April | 0.672646E+09 | 0.332884E+09 | 0.339762E+09 | 0.593374E+09 | 0.376350E+09 |
May | 0.696364E+09 | 0.278773E+09 | 0.417591E+09 | 0.677239E+09 | 0.207461E+09 |
June | 0.788293E+09 | 0.340778E+09 | 0.447515E+09 | 0.879563E+09 | 0.123523E+09 |
July | 0.874923E+09 | 0.415012E+09 | 0.459912E+09 | 0.100624E+10 | 0.107138E+09 |
August | 0.764011E+09 | 0.349593E+09 | 0.414418E+09 | 0.881480E+09 | 0.130604E+09 |
September | 0.600021E+09 | 0.284351E+09 | 0.315669E+09 | 0.631762E+09 | 0.228325E+09 |
October | 0.434584E+09 | 0.194148E+09 | 0.240436E+09 | 0.338420E+09 | 0.405994E+09 |
November | 0.250940E+09 | 93182561.37 | 0.157758E+09 | 0.116080E+09 | 0.648901E+09 |
December | 0.199611E+09 | 94469239.74 | 0.105141E+09 | 72590104.89 | 0.987368E+09 |
Annual Sum or Average | 0.638928E+10 | 0.284805E+10 | 0.354123E+10 | 0.574241E+10 | 0.568804E+10 |
Minimum of Months | 0.199611E+09 | 93182561.37 | 0.105141E+09 | 72590104.89 | 0.107138E+09 |
Maximum of Months | 0.874923E+09 | 0.415012E+09 | 0.459912E+09 | 0.100624E+10 | 0.110745E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.626115E+09 | 0.428935E+09 | 0.197180E+09 | 0.487760E+09 | 0.778042E+09 |
February | 0.609882E+09 | 0.413809E+09 | 0.196072E+09 | 0.478591E+09 | 0.571908E+09 |
March | 0.578518E+09 | 0.302946E+09 | 0.275572E+09 | 0.435609E+09 | 0.453087E+09 |
April | 0.498898E+09 | 0.228627E+09 | 0.270272E+09 | 0.375510E+09 | 0.306777E+09 |
May | 0.439630E+09 | 0.122931E+09 | 0.316699E+09 | 0.346970E+09 | 0.163711E+09 |
June | 0.406134E+09 | 81050618.64 | 0.325083E+09 | 0.382971E+09 | 88794111.55 |
July | 0.445356E+09 | 0.111319E+09 | 0.334036E+09 | 0.437188E+09 | 67518641.12 |
August | 0.493535E+09 | 0.170865E+09 | 0.322671E+09 | 0.506576E+09 | 88460767.35 |
September | 0.576841E+09 | 0.297704E+09 | 0.279137E+09 | 0.580475E+09 | 0.177436E+09 |
October | 0.642480E+09 | 0.405142E+09 | 0.237338E+09 | 0.614088E+09 | 0.322555E+09 |
November | 0.465153E+09 | 0.291214E+09 | 0.173939E+09 | 0.384136E+09 | 0.482214E+09 |
December | 0.511639E+09 | 0.387430E+09 | 0.124209E+09 | 0.445161E+09 | 0.717085E+09 |
Annual Sum or Average | 0.629418E+10 | 0.324197E+10 | 0.305221E+10 | 0.547503E+10 | 0.421759E+10 |
Minimum of Months | 0.406134E+09 | 81050618.64 | 0.124209E+09 | 0.346970E+09 | 67518641.12 |
Maximum of Months | 0.642480E+09 | 0.428935E+09 | 0.334036E+09 | 0.614088E+09 | 0.778042E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.479096E+09 | 0.00 | 0.479096E+09 | 0.00 | 0.487213E+10 |
February | 0.548619E+09 | 0.00 | 0.548619E+09 | 316073.35 | 0.358195E+10 |
March | 0.910430E+09 | 7699.91 | 0.910422E+09 | 93606077.26 | 0.283713E+10 |
April | 0.102107E+10 | 8188162.50 | 0.101288E+10 | 0.326644E+09 | 0.192143E+10 |
May | 0.137181E+10 | 51833015.89 | 0.131998E+10 | 0.803009E+09 | 0.106793E+10 |
June | 0.155349E+10 | 0.143797E+09 | 0.140969E+10 | 0.128331E+10 | 0.662225E+09 |
July | 0.150565E+10 | 0.103643E+09 | 0.140200E+10 | 0.134610E+10 | 0.552916E+09 |
August | 0.126162E+10 | 25425958.08 | 0.123620E+10 | 0.117035E+10 | 0.696170E+09 |
September | 0.934384E+09 | 838501.69 | 0.933546E+09 | 0.642272E+09 | 0.122347E+10 |
October | 0.716971E+09 | 0.00 | 0.716971E+09 | 0.123978E+09 | 0.213048E+10 |
November | 0.485350E+09 | 0.00 | 0.485350E+09 | 15274332.52 | 0.313901E+10 |
December | 0.325321E+09 | 0.00 | 0.325321E+09 | 0.00 | 0.447153E+10 |
Annual Sum or Average | 0.111138E+11 | 0.333734E+09 | 0.107801E+11 | 0.580486E+10 | 0.271564E+11 |
Minimum of Months | 0.325321E+09 | 0.00 | 0.325321E+09 | 0.00 | 0.552916E+09 |
Maximum of Months | 0.155349E+10 | 0.143797E+09 | 0.140969E+10 | 0.134610E+10 | 0.487213E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.479096E+09 | 0.00 | 0.479096E+09 | 0.00 | 0.504877E+10 |
February | 0.548619E+09 | 0.00 | 0.548619E+09 | 21707.28 | 0.374967E+10 |
March | 0.910430E+09 | 7699.91 | 0.910422E+09 | 77043952.76 | 0.298422E+10 |
April | 0.102107E+10 | 8188162.50 | 0.101288E+10 | 0.297762E+09 | 0.203213E+10 |
May | 0.137181E+10 | 51833015.89 | 0.131998E+10 | 0.749362E+09 | 0.113442E+10 |
June | 0.155349E+10 | 0.143797E+09 | 0.140969E+10 | 0.122673E+10 | 0.711362E+09 |
July | 0.150565E+10 | 0.103643E+09 | 0.140200E+10 | 0.129041E+10 | 0.595877E+09 |
August | 0.126162E+10 | 25425958.08 | 0.123620E+10 | 0.111978E+10 | 0.748120E+09 |
September | 0.934384E+09 | 838501.69 | 0.933546E+09 | 0.606836E+09 | 0.129809E+10 |
October | 0.716971E+09 | 0.00 | 0.716971E+09 | 0.103569E+09 | 0.224874E+10 |
November | 0.485350E+09 | 0.00 | 0.485350E+09 | 10955391.17 | 0.328992E+10 |
December | 0.325321E+09 | 0.00 | 0.325321E+09 | 0.00 | 0.464428E+10 |
Annual Sum or Average | 0.111138E+11 | 0.333734E+09 | 0.107801E+11 | 0.548247E+10 | 0.284856E+11 |
Minimum of Months | 0.325321E+09 | 0.00 | 0.325321E+09 | 0.00 | 0.595877E+09 |
Maximum of Months | 0.155349E+10 | 0.143797E+09 | 0.140969E+10 | 0.129041E+10 | 0.504877E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 68444868.78 | 0.00 | 68444868.78 | 0.00 | 0.704097E+09 |
February | 78377152.73 | 0.00 | 78377152.73 | 51915.87 | 0.533009E+09 |
March | 0.130066E+09 | 1100.03 | 0.130065E+09 | 13332952.12 | 0.414909E+09 |
April | 0.145873E+09 | 1169781.80 | 0.144703E+09 | 50690827.48 | 0.281529E+09 |
May | 0.195980E+09 | 7404997.01 | 0.188575E+09 | 0.129452E+09 | 0.162253E+09 |
June | 0.221935E+09 | 20543195.50 | 0.201392E+09 | 0.203557E+09 | 0.105507E+09 |
July | 0.215100E+09 | 14806773.10 | 0.200294E+09 | 0.217191E+09 | 89136995.80 |
August | 0.180239E+09 | 3632417.30 | 0.176606E+09 | 0.188396E+09 | 0.109209E+09 |
September | 0.133488E+09 | 119790.49 | 0.133369E+09 | 0.103846E+09 | 0.181181E+09 |
October | 0.102428E+09 | 0.00 | 0.102428E+09 | 19818703.55 | 0.309278E+09 |
November | 69338365.69 | 0.00 | 69338365.69 | 3063912.08 | 0.452630E+09 |
December | 46476251.60 | 0.00 | 46476251.60 | 0.00 | 0.641537E+09 |
Annual Sum or Average | 0.158775E+10 | 47678055.23 | 0.154007E+10 | 0.929400E+09 | 0.398428E+10 |
Minimum of Months | 46476251.60 | 0.00 | 46476251.60 | 0.00 | 89136995.80 |
Maximum of Months | 0.221935E+09 | 20543195.50 | 0.201392E+09 | 0.217191E+09 | 0.704097E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.546175E+09 | 0.223851E+09 | 0.322324E+09 | 0.125266E+09 | 0.243455E+10 |
February | 0.656848E+09 | 0.289111E+09 | 0.367737E+09 | 0.245735E+09 | 0.179985E+10 |
March | 0.987713E+09 | 0.391906E+09 | 0.595807E+09 | 0.522827E+09 | 0.141399E+10 |
April | 0.116660E+10 | 0.508459E+09 | 0.658138E+09 | 0.908129E+09 | 0.100199E+10 |
May | 0.152298E+10 | 0.666024E+09 | 0.856953E+09 | 0.147275E+10 | 0.593116E+09 |
June | 0.161965E+10 | 0.705453E+09 | 0.914200E+09 | 0.179712E+10 | 0.401779E+09 |
July | 0.169200E+10 | 0.780917E+09 | 0.911085E+09 | 0.197409E+10 | 0.340014E+09 |
August | 0.142663E+10 | 0.614787E+09 | 0.811840E+09 | 0.165343E+10 | 0.408498E+09 |
September | 0.123703E+10 | 0.586738E+09 | 0.650289E+09 | 0.128020E+10 | 0.648925E+09 |
October | 0.809416E+09 | 0.336902E+09 | 0.472514E+09 | 0.500977E+09 | 0.107181E+10 |
November | 0.463349E+09 | 0.150389E+09 | 0.312960E+09 | 0.135220E+09 | 0.159331E+10 |
December | 0.369510E+09 | 0.158222E+09 | 0.211289E+09 | 79929679.40 | 0.226438E+10 |
Annual Sum or Average | 0.124979E+11 | 0.541276E+10 | 0.708513E+10 | 0.106957E+11 | 0.139722E+11 |
Minimum of Months | 0.369510E+09 | 0.150389E+09 | 0.211289E+09 | 79929679.40 | 0.340014E+09 |
Maximum of Months | 0.169200E+10 | 0.780917E+09 | 0.914200E+09 | 0.197409E+10 | 0.243455E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.426917E+09 | 0.292470E+09 | 0.134447E+09 | 0.337874E+09 | 0.572016E+09 |
February | 0.415848E+09 | 0.282156E+09 | 0.133692E+09 | 0.329773E+09 | 0.432063E+09 |
March | 0.394463E+09 | 0.206564E+09 | 0.187899E+09 | 0.287877E+09 | 0.373733E+09 |
April | 0.340174E+09 | 0.155889E+09 | 0.184285E+09 | 0.247072E+09 | 0.277035E+09 |
May | 0.299762E+09 | 83820784.91 | 0.215941E+09 | 0.225613E+09 | 0.171129E+09 |
June | 0.276923E+09 | 55264449.30 | 0.221658E+09 | 0.248887E+09 | 0.113918E+09 |
July | 0.303666E+09 | 75903201.68 | 0.227763E+09 | 0.291172E+09 | 94914292.08 |
August | 0.336518E+09 | 0.116504E+09 | 0.220013E+09 | 0.340247E+09 | 0.114578E+09 |
September | 0.393320E+09 | 0.202990E+09 | 0.190330E+09 | 0.393053E+09 | 0.178895E+09 |
October | 0.438076E+09 | 0.276247E+09 | 0.161829E+09 | 0.413332E+09 | 0.284266E+09 |
November | 0.317165E+09 | 0.198565E+09 | 0.118600E+09 | 0.259245E+09 | 0.391701E+09 |
December | 0.348862E+09 | 0.264170E+09 | 84692004.19 | 0.305887E+09 | 0.545331E+09 |
Annual Sum or Average | 0.429169E+10 | 0.221054E+10 | 0.208115E+10 | 0.368003E+10 | 0.354958E+10 |
Minimum of Months | 0.276923E+09 | 55264449.30 | 84692004.19 | 0.225613E+09 | 94914292.08 |
Maximum of Months | 0.438076E+09 | 0.292470E+09 | 0.227763E+09 | 0.413332E+09 | 0.572016E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86681107.68 | 0.00 | 86681107.68 | 0.00 | 0.818087E+09 |
February | 99259718.61 | 0.00 | 99259718.61 | 309551.26 | 0.583981E+09 |
March | 0.164721E+09 | 1393.12 | 0.164719E+09 | 21359074.34 | 0.453706E+09 |
April | 0.184739E+09 | 1481454.85 | 0.183258E+09 | 63994995.41 | 0.307527E+09 |
May | 0.248196E+09 | 9377961.48 | 0.238818E+09 | 0.153933E+09 | 0.171011E+09 |
June | 0.281067E+09 | 26016660.90 | 0.255050E+09 | 0.239997E+09 | 0.104501E+09 |
July | 0.272411E+09 | 18751843.88 | 0.253659E+09 | 0.248998E+09 | 88011734.97 |
August | 0.228261E+09 | 4600227.31 | 0.223661E+09 | 0.215899E+09 | 0.110423E+09 |
September | 0.169055E+09 | 151707.10 | 0.168903E+09 | 0.118554E+09 | 0.199140E+09 |
October | 0.129719E+09 | 0.00 | 0.129719E+09 | 25313168.18 | 0.349090E+09 |
November | 87812665.13 | 0.00 | 87812665.13 | 3583487.71 | 0.511402E+09 |
December | 58859240.16 | 0.00 | 58859240.16 | 0.00 | 0.735061E+09 |
Annual Sum or Average | 0.201078E+10 | 60381248.63 | 0.195040E+10 | 0.109194E+10 | 0.443194E+10 |
Minimum of Months | 58859240.16 | 0.00 | 58859240.16 | 0.00 | 88011734.97 |
Maximum of Months | 0.281067E+09 | 26016660.90 | 0.255050E+09 | 0.248998E+09 | 0.818087E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 77553915.47 | 0.00 | 77553915.47 | 0.00 | 0.731936E+09 |
February | 88808046.34 | 0.00 | 88808046.34 | 276956.68 | 0.522489E+09 |
March | 0.147376E+09 | 1246.43 | 0.147375E+09 | 19110044.74 | 0.405932E+09 |
April | 0.165287E+09 | 1325463.26 | 0.163961E+09 | 57256564.87 | 0.275145E+09 |
May | 0.222062E+09 | 8390497.67 | 0.213672E+09 | 0.137725E+09 | 0.153005E+09 |
June | 0.251471E+09 | 23277205.08 | 0.228194E+09 | 0.214726E+09 | 93497758.29 |
July | 0.243727E+09 | 16777345.77 | 0.226950E+09 | 0.222780E+09 | 78744432.76 |
August | 0.204226E+09 | 4115840.81 | 0.200110E+09 | 0.193166E+09 | 98796291.36 |
September | 0.151254E+09 | 135732.92 | 0.151118E+09 | 0.106071E+09 | 0.178171E+09 |
October | 0.116060E+09 | 0.00 | 0.116060E+09 | 22647787.48 | 0.312332E+09 |
November | 78566324.22 | 0.00 | 78566324.22 | 3206160.04 | 0.457553E+09 |
December | 52661585.19 | 0.00 | 52661585.19 | 0.00 | 0.657648E+09 |
Annual Sum or Average | 0.179905E+10 | 54023331.93 | 0.174503E+10 | 0.976965E+09 | 0.396525E+10 |
Minimum of Months | 52661585.19 | 0.00 | 52661585.19 | 0.00 | 78744432.76 |
Maximum of Months | 0.251471E+09 | 23277205.08 | 0.228194E+09 | 0.222780E+09 | 0.731936E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.159381E+10 | 0.109188E+10 | 0.501931E+09 | 0.128427E+10 | 0.193872E+10 |
February | 0.155249E+10 | 0.105337E+10 | 0.499112E+09 | 0.127537E+10 | 0.139129E+10 |
March | 0.147265E+10 | 0.771166E+09 | 0.701482E+09 | 0.110933E+10 | 0.120798E+10 |
April | 0.126997E+10 | 0.581981E+09 | 0.687991E+09 | 0.928628E+09 | 0.892420E+09 |
May | 0.111910E+10 | 0.312928E+09 | 0.806173E+09 | 0.817569E+09 | 0.534668E+09 |
June | 0.103384E+10 | 0.206319E+09 | 0.827517E+09 | 0.884772E+09 | 0.335470E+09 |
July | 0.113368E+10 | 0.283369E+09 | 0.850308E+09 | 0.101842E+10 | 0.279125E+09 |
August | 0.125632E+10 | 0.434945E+09 | 0.821375E+09 | 0.121010E+10 | 0.339857E+09 |
September | 0.146838E+10 | 0.757822E+09 | 0.710558E+09 | 0.142823E+10 | 0.575133E+09 |
October | 0.163547E+10 | 0.103131E+10 | 0.604155E+09 | 0.153895E+10 | 0.936497E+09 |
November | 0.118407E+10 | 0.741301E+09 | 0.442770E+09 | 0.978483E+09 | 0.128693E+10 |
December | 0.130240E+10 | 0.986224E+09 | 0.316180E+09 | 0.115922E+10 | 0.182869E+10 |
Annual Sum or Average | 0.160222E+11 | 0.825262E+10 | 0.776955E+10 | 0.136333E+11 | 0.115468E+11 |
Minimum of Months | 0.103384E+10 | 0.206319E+09 | 0.316180E+09 | 0.817569E+09 | 0.279125E+09 |
Maximum of Months | 0.163547E+10 | 0.109188E+10 | 0.850308E+09 | 0.153895E+10 | 0.193872E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 661.19 | 905.87 | 807.15 | 552.96 | 254.19 | 0.00 | 0.00 |
February | 715.25 | 736.82 | 870.46 | 590.61 | 279.85 | 0.00 | 0.00 |
March | 568.41 | 562.59 | 745.79 | 390.54 | 355.25 | 0.00 | 0.00 |
April | 486.64 | 420.10 | 664.59 | 304.56 | 360.03 | 0.00 | 0.00 |
May | 415.87 | 248.69 | 566.74 | 158.48 | 408.27 | 0.00 | 0.00 |
June | 459.86 | 162.67 | 541.02 | 107.97 | 433.05 | 0.00 | 0.00 |
July | 510.14 | 134.13 | 574.13 | 143.51 | 430.62 | 0.00 | 0.00 |
August | 604.14 | 163.58 | 636.24 | 220.27 | 415.97 | 0.00 | 0.00 |
September | 736.81 | 283.62 | 768.42 | 396.57 | 371.84 | 0.00 | 0.00 |
October | 781.18 | 438.60 | 828.25 | 522.28 | 305.96 | 0.00 | 0.00 |
November | 517.68 | 615.86 | 619.63 | 387.93 | 231.71 | 0.00 | 0.00 |
December | 589.20 | 855.52 | 659.57 | 499.45 | 160.12 | 0.00 | 0.00 |
Annual Sum or Average | 586.55 | 459.39 | 689.14 | 354.96 | 334.18 | 0.00 | 0.00 |
Minimum of Months | 415.87 | 134.13 | 541.02 | 107.97 | 160.12 | 0.00 | 0.00 |
Maximum of Months | 781.18 | 905.87 | 870.46 | 590.61 | 433.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1835.72 | 2649.93 | 2272.88 | 1557.09 | 715.79 | 0.00 | 0.00 |
February | 1983.94 | 2188.96 | 2451.16 | 1663.13 | 788.03 | 0.00 | 0.00 |
March | 1570.49 | 1683.68 | 2100.09 | 1099.73 | 1000.36 | 0.00 | 0.00 |
April | 1349.40 | 1263.80 | 1871.43 | 857.61 | 1013.82 | 0.00 | 0.00 |
May | 1159.98 | 731.94 | 1595.91 | 446.26 | 1149.66 | 0.00 | 0.00 |
June | 1285.50 | 480.91 | 1523.46 | 304.03 | 1219.43 | 0.00 | 0.00 |
July | 1430.23 | 393.41 | 1616.70 | 404.10 | 1212.60 | 0.00 | 0.00 |
August | 1695.18 | 483.59 | 1791.60 | 620.26 | 1171.34 | 0.00 | 0.00 |
September | 2063.28 | 837.82 | 2163.81 | 1116.73 | 1047.08 | 0.00 | 0.00 |
October | 2172.27 | 1307.42 | 2332.29 | 1470.72 | 861.57 | 0.00 | 0.00 |
November | 1433.33 | 1834.33 | 1744.85 | 1092.38 | 652.47 | 0.00 | 0.00 |
December | 1635.03 | 2530.33 | 1857.32 | 1406.42 | 450.89 | 0.00 | 0.00 |
Annual Sum or Average | 1632.77 | 1361.61 | 1940.57 | 999.54 | 941.03 | 0.00 | 0.00 |
Minimum of Months | 1159.98 | 393.41 | 1523.46 | 304.03 | 450.89 | 0.00 | 0.00 |
Maximum of Months | 2172.27 | 2649.93 | 2451.16 | 1663.13 | 1219.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2389.37 | 3672.43 | 2952.60 | 2022.75 | 929.85 | 0.00 | 0.00 |
February | 2595.39 | 3012.16 | 3184.19 | 2160.50 | 1023.69 | 0.00 | 0.00 |
March | 2051.67 | 2322.61 | 2728.14 | 1428.62 | 1299.53 | 0.00 | 0.00 |
April | 1776.36 | 1749.73 | 2431.10 | 1114.08 | 1317.02 | 0.00 | 0.00 |
May | 1527.41 | 1003.29 | 2073.18 | 579.71 | 1493.47 | 0.00 | 0.00 |
June | 1706.73 | 657.04 | 1979.07 | 394.95 | 1584.11 | 0.00 | 0.00 |
July | 1901.83 | 532.27 | 2100.18 | 524.95 | 1575.23 | 0.00 | 0.00 |
August | 2253.31 | 649.45 | 2327.39 | 805.75 | 1521.63 | 0.00 | 0.00 |
September | 2738.80 | 1132.97 | 2810.91 | 1450.69 | 1360.22 | 0.00 | 0.00 |
October | 2866.61 | 1775.63 | 3029.77 | 1910.55 | 1119.22 | 0.00 | 0.00 |
November | 1872.51 | 2545.90 | 2266.66 | 1419.07 | 847.59 | 0.00 | 0.00 |
December | 2138.67 | 3504.49 | 2412.76 | 1827.02 | 585.74 | 0.00 | 0.00 |
Annual Sum or Average | 2149.31 | 1874.45 | 2520.92 | 1298.46 | 1222.46 | 0.00 | 0.00 |
Minimum of Months | 1527.41 | 532.27 | 1979.07 | 394.95 | 585.74 | 0.00 | 0.00 |
Maximum of Months | 2866.61 | 3672.43 | 3184.19 | 2160.50 | 1584.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 119.67 | 567.28 | 261.06 | 150.51 | 110.55 | 0.00 | 0.00 |
February | 182.08 | 454.81 | 320.32 | 189.68 | 130.64 | 0.00 | 0.00 |
March | 208.00 | 318.07 | 324.46 | 143.01 | 181.45 | 0.00 | 0.00 |
April | 324.48 | 222.02 | 390.43 | 188.42 | 202.01 | 0.00 | 0.00 |
May | 345.08 | 115.99 | 371.61 | 135.27 | 236.34 | 0.00 | 0.00 |
June | 445.45 | 67.72 | 410.63 | 152.67 | 257.96 | 0.00 | 0.00 |
July | 494.68 | 52.22 | 439.67 | 183.14 | 256.54 | 0.00 | 0.00 |
August | 463.86 | 66.31 | 410.55 | 173.88 | 236.68 | 0.00 | 0.00 |
September | 396.30 | 131.80 | 382.92 | 187.86 | 195.06 | 0.00 | 0.00 |
October | 276.53 | 229.48 | 325.55 | 175.48 | 150.07 | 0.00 | 0.00 |
November | 132.64 | 361.65 | 219.00 | 112.46 | 106.53 | 0.00 | 0.00 |
December | 117.33 | 521.81 | 204.61 | 133.79 | 70.82 | 0.00 | 0.00 |
Annual Sum or Average | 292.72 | 258.18 | 338.41 | 160.28 | 178.14 | 0.00 | 0.00 |
Minimum of Months | 117.33 | 52.22 | 204.61 | 112.46 | 70.82 | 0.00 | 0.00 |
Maximum of Months | 494.68 | 567.28 | 439.67 | 189.68 | 257.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 20.89 | 636.31 | 127.33 | 41.40 | 85.93 | 0.00 | 0.00 |
February | 62.08 | 502.15 | 180.94 | 73.14 | 107.79 | 0.00 | 0.00 |
March | 109.15 | 328.16 | 225.83 | 65.95 | 159.88 | 0.00 | 0.00 |
April | 250.80 | 222.37 | 315.53 | 128.77 | 186.75 | 0.00 | 0.00 |
May | 307.75 | 115.39 | 332.89 | 106.76 | 226.13 | 0.00 | 0.00 |
June | 421.66 | 69.01 | 389.43 | 139.28 | 250.14 | 0.00 | 0.00 |
July | 457.30 | 57.29 | 406.63 | 160.34 | 246.29 | 0.00 | 0.00 |
August | 400.76 | 71.33 | 352.25 | 131.77 | 220.48 | 0.00 | 0.00 |
September | 285.69 | 134.81 | 282.76 | 109.66 | 173.10 | 0.00 | 0.00 |
October | 135.63 | 233.89 | 200.33 | 72.43 | 127.91 | 0.00 | 0.00 |
November | 42.33 | 386.45 | 123.46 | 35.92 | 87.54 | 0.00 | 0.00 |
December | 20.14 | 566.00 | 91.80 | 35.24 | 56.56 | 0.00 | 0.00 |
Annual Sum or Average | 210.28 | 275.89 | 252.74 | 91.75 | 160.99 | 0.00 | 0.00 |
Minimum of Months | 20.14 | 57.29 | 91.80 | 35.24 | 56.56 | 0.00 | 0.00 |
Maximum of Months | 457.30 | 636.31 | 406.63 | 160.34 | 250.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 106.69 | 136.23 | 127.38 | 87.27 | 40.12 | 0.00 | 0.00 |
February | 113.11 | 119.64 | 137.38 | 93.21 | 44.17 | 0.00 | 0.00 |
March | 89.78 | 91.13 | 117.70 | 61.63 | 56.07 | 0.00 | 0.00 |
April | 74.16 | 79.80 | 104.89 | 48.06 | 56.82 | 0.00 | 0.00 |
May | 59.09 | 51.47 | 89.44 | 25.01 | 64.43 | 0.00 | 0.00 |
June | 66.99 | 35.22 | 85.38 | 17.04 | 68.34 | 0.00 | 0.00 |
July | 75.01 | 29.17 | 90.61 | 22.65 | 67.96 | 0.00 | 0.00 |
August | 90.43 | 34.97 | 100.41 | 34.76 | 65.65 | 0.00 | 0.00 |
September | 112.50 | 57.66 | 121.27 | 62.59 | 58.68 | 0.00 | 0.00 |
October | 117.14 | 87.24 | 130.71 | 82.43 | 48.29 | 0.00 | 0.00 |
November | 78.82 | 109.78 | 97.79 | 61.22 | 36.57 | 0.00 | 0.00 |
December | 95.25 | 128.15 | 104.09 | 78.82 | 25.27 | 0.00 | 0.00 |
Annual Sum or Average | 89.80 | 79.82 | 108.76 | 56.02 | 52.74 | 0.00 | 0.00 |
Minimum of Months | 59.09 | 29.17 | 85.38 | 17.04 | 25.27 | 0.00 | 0.00 |
Maximum of Months | 117.14 | 136.23 | 137.38 | 93.21 | 68.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 194.50 | 20.43 | 0.00 | 20.43 | 0.00 | 0.00 |
February | 0.24 | 156.83 | 25.90 | 0.00 | 25.90 | 0.00 | 0.00 |
March | 7.10 | 100.74 | 38.82 | 0.00 | 38.82 | 0.00 | 0.00 |
April | 19.91 | 65.62 | 44.99 | 0.36 | 44.63 | 0.00 | 0.00 |
May | 43.87 | 31.57 | 58.50 | 2.21 | 56.29 | 0.00 | 0.00 |
June | 67.69 | 18.15 | 68.45 | 6.34 | 62.12 | 0.00 | 0.00 |
July | 67.65 | 14.17 | 64.20 | 4.42 | 59.78 | 0.00 | 0.00 |
August | 59.14 | 18.25 | 53.80 | 1.08 | 52.71 | 0.00 | 0.00 |
September | 35.51 | 38.12 | 41.17 | 0.04 | 41.13 | 0.00 | 0.00 |
October | 9.85 | 69.75 | 30.57 | 0.00 | 30.57 | 0.00 | 0.00 |
November | 1.94 | 117.51 | 21.39 | 0.00 | 21.39 | 0.00 | 0.00 |
December | 0.00 | 170.98 | 13.87 | 0.00 | 13.87 | 0.00 | 0.00 |
Annual Sum or Average | 26.23 | 82.66 | 40.25 | 1.21 | 39.04 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 14.17 | 13.87 | 0.00 | 13.87 | 0.00 | 0.00 |
Maximum of Months | 67.69 | 194.50 | 68.45 | 6.34 | 62.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.05 | 564.62 | 261.14 | 150.86 | 110.28 | 0.00 | 0.00 |
February | 163.61 | 447.95 | 307.41 | 176.25 | 131.16 | 0.00 | 0.00 |
March | 212.03 | 313.48 | 331.40 | 150.16 | 181.24 | 0.00 | 0.00 |
April | 278.34 | 216.67 | 356.00 | 158.10 | 197.90 | 0.00 | 0.00 |
May | 366.18 | 109.25 | 395.92 | 155.51 | 240.41 | 0.00 | 0.00 |
June | 449.09 | 63.69 | 418.95 | 157.28 | 261.66 | 0.00 | 0.00 |
July | 476.66 | 48.52 | 428.91 | 173.99 | 254.92 | 0.00 | 0.00 |
August | 435.76 | 61.78 | 391.66 | 158.14 | 233.52 | 0.00 | 0.00 |
September | 399.95 | 128.08 | 390.06 | 191.35 | 198.72 | 0.00 | 0.00 |
October | 257.78 | 224.75 | 314.41 | 165.90 | 148.51 | 0.00 | 0.00 |
November | 120.39 | 357.23 | 211.58 | 105.53 | 106.04 | 0.00 | 0.00 |
December | 107.49 | 516.92 | 199.07 | 128.06 | 71.01 | 0.00 | 0.00 |
Annual Sum or Average | 282.76 | 253.51 | 333.98 | 155.79 | 178.19 | 0.00 | 0.00 |
Minimum of Months | 107.49 | 48.52 | 199.07 | 105.53 | 71.01 | 0.00 | 0.00 |
Maximum of Months | 476.66 | 564.62 | 428.91 | 191.35 | 261.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.36 | 627.65 | 127.42 | 41.76 | 85.66 | 0.00 | 0.00 |
February | 41.38 | 492.81 | 168.03 | 59.71 | 108.32 | 0.00 | 0.00 |
March | 109.97 | 320.05 | 232.77 | 73.11 | 159.66 | 0.00 | 0.00 |
April | 204.39 | 215.97 | 281.10 | 98.46 | 182.64 | 0.00 | 0.00 |
May | 331.33 | 108.85 | 357.21 | 127.00 | 230.20 | 0.00 | 0.00 |
June | 428.27 | 65.74 | 397.75 | 143.90 | 253.85 | 0.00 | 0.00 |
July | 442.66 | 52.74 | 395.87 | 151.20 | 244.67 | 0.00 | 0.00 |
August | 375.74 | 65.56 | 333.36 | 116.04 | 217.32 | 0.00 | 0.00 |
September | 289.41 | 129.43 | 289.90 | 113.14 | 176.76 | 0.00 | 0.00 |
October | 113.50 | 225.01 | 189.20 | 62.85 | 126.35 | 0.00 | 0.00 |
November | 27.99 | 379.82 | 116.04 | 28.99 | 87.05 | 0.00 | 0.00 |
December | 10.42 | 561.54 | 86.27 | 29.51 | 56.75 | 0.00 | 0.00 |
Annual Sum or Average | 199.91 | 269.40 | 248.31 | 87.27 | 161.05 | 0.00 | 0.00 |
Minimum of Months | 10.42 | 52.74 | 86.27 | 28.99 | 56.75 | 0.00 | 0.00 |
Maximum of Months | 442.66 | 627.65 | 397.75 | 151.20 | 253.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.80 | 668.59 | 320.26 | 189.08 | 131.18 | 0.00 | 0.00 |
February | 207.83 | 533.62 | 353.76 | 201.96 | 151.80 | 0.00 | 0.00 |
March | 206.80 | 395.84 | 339.13 | 133.55 | 205.58 | 0.00 | 0.00 |
April | 222.10 | 273.98 | 324.72 | 104.93 | 219.80 | 0.00 | 0.00 |
May | 262.31 | 135.01 | 320.52 | 58.98 | 261.54 | 0.00 | 0.00 |
June | 327.23 | 79.43 | 333.29 | 50.65 | 282.64 | 0.00 | 0.00 |
July | 342.47 | 65.17 | 335.41 | 58.65 | 276.76 | 0.00 | 0.00 |
August | 356.07 | 83.62 | 334.11 | 77.67 | 256.44 | 0.00 | 0.00 |
September | 347.94 | 164.48 | 351.95 | 135.69 | 216.26 | 0.00 | 0.00 |
October | 298.72 | 278.02 | 349.45 | 178.60 | 170.86 | 0.00 | 0.00 |
November | 164.86 | 437.37 | 258.21 | 132.65 | 125.56 | 0.00 | 0.00 |
December | 166.09 | 620.06 | 255.59 | 170.79 | 84.81 | 0.00 | 0.00 |
Annual Sum or Average | 256.48 | 310.23 | 322.85 | 124.00 | 198.85 | 0.00 | 0.00 |
Minimum of Months | 164.86 | 65.17 | 255.59 | 50.65 | 84.81 | 0.00 | 0.00 |
Maximum of Months | 356.07 | 668.59 | 353.76 | 201.96 | 282.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 118.41 | 571.20 | 261.28 | 150.63 | 110.65 | 0.00 | 0.00 |
February | 180.15 | 458.79 | 320.58 | 189.84 | 130.75 | 0.00 | 0.00 |
March | 207.69 | 318.55 | 324.73 | 143.13 | 181.60 | 0.00 | 0.00 |
April | 322.76 | 222.08 | 390.75 | 188.57 | 202.18 | 0.00 | 0.00 |
May | 341.64 | 116.64 | 371.91 | 135.38 | 236.53 | 0.00 | 0.00 |
June | 442.63 | 67.72 | 410.96 | 152.79 | 258.17 | 0.00 | 0.00 |
July | 492.02 | 51.95 | 440.03 | 183.29 | 256.75 | 0.00 | 0.00 |
August | 461.46 | 66.22 | 410.89 | 174.02 | 236.87 | 0.00 | 0.00 |
September | 395.09 | 131.16 | 383.23 | 188.02 | 195.22 | 0.00 | 0.00 |
October | 275.98 | 229.15 | 325.81 | 175.63 | 150.19 | 0.00 | 0.00 |
November | 132.70 | 362.01 | 219.18 | 112.56 | 106.62 | 0.00 | 0.00 |
December | 117.22 | 524.32 | 204.78 | 133.90 | 70.88 | 0.00 | 0.00 |
Annual Sum or Average | 291.20 | 259.05 | 338.69 | 160.41 | 178.28 | 0.00 | 0.00 |
Minimum of Months | 117.22 | 51.95 | 204.78 | 112.56 | 70.88 | 0.00 | 0.00 |
Maximum of Months | 492.02 | 571.20 | 440.03 | 189.84 | 258.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 20.66 | 640.86 | 127.44 | 41.44 | 86.00 | 0.00 | 0.00 |
February | 61.54 | 506.69 | 181.09 | 73.20 | 107.88 | 0.00 | 0.00 |
March | 109.22 | 328.58 | 226.01 | 66.01 | 160.01 | 0.00 | 0.00 |
April | 249.01 | 222.77 | 315.79 | 128.88 | 186.91 | 0.00 | 0.00 |
May | 302.69 | 117.14 | 333.16 | 106.85 | 226.32 | 0.00 | 0.00 |
June | 416.93 | 70.78 | 389.75 | 139.40 | 250.35 | 0.00 | 0.00 |
July | 452.15 | 59.84 | 406.97 | 160.48 | 246.49 | 0.00 | 0.00 |
August | 396.45 | 73.88 | 352.54 | 131.88 | 220.66 | 0.00 | 0.00 |
September | 284.05 | 135.26 | 282.99 | 109.75 | 173.24 | 0.00 | 0.00 |
October | 136.07 | 232.97 | 200.50 | 72.49 | 128.01 | 0.00 | 0.00 |
November | 42.80 | 386.44 | 123.56 | 35.95 | 87.61 | 0.00 | 0.00 |
December | 20.21 | 568.65 | 91.88 | 35.27 | 56.61 | 0.00 | 0.00 |
Annual Sum or Average | 208.41 | 277.60 | 252.95 | 91.82 | 161.13 | 0.00 | 0.00 |
Minimum of Months | 20.21 | 59.84 | 91.88 | 35.27 | 56.61 | 0.00 | 0.00 |
Maximum of Months | 452.15 | 640.86 | 406.97 | 160.48 | 250.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 182.11 | 290.49 | 233.76 | 160.15 | 73.62 | 0.00 | 0.00 |
February | 197.83 | 236.40 | 252.10 | 171.05 | 81.05 | 0.00 | 0.00 |
March | 162.64 | 169.16 | 215.99 | 113.11 | 102.89 | 0.00 | 0.00 |
April | 144.87 | 118.36 | 192.48 | 88.20 | 104.27 | 0.00 | 0.00 |
May | 129.54 | 61.12 | 164.14 | 45.90 | 118.24 | 0.00 | 0.00 |
June | 147.75 | 34.26 | 156.69 | 31.27 | 125.42 | 0.00 | 0.00 |
July | 163.23 | 25.21 | 166.28 | 41.56 | 124.71 | 0.00 | 0.00 |
August | 189.13 | 33.03 | 184.26 | 63.79 | 120.47 | 0.00 | 0.00 |
September | 223.95 | 68.46 | 222.55 | 114.86 | 107.69 | 0.00 | 0.00 |
October | 229.27 | 120.43 | 239.87 | 151.26 | 88.61 | 0.00 | 0.00 |
November | 148.20 | 186.04 | 179.46 | 112.35 | 67.11 | 0.00 | 0.00 |
December | 166.20 | 267.73 | 191.02 | 144.65 | 46.37 | 0.00 | 0.00 |
Annual Sum or Average | 173.61 | 133.74 | 199.59 | 102.80 | 96.78 | 0.00 | 0.00 |
Minimum of Months | 129.54 | 25.21 | 156.69 | 31.27 | 46.37 | 0.00 | 0.00 |
Maximum of Months | 229.27 | 290.49 | 252.10 | 171.05 | 125.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1819.04 | 178.87 | 0.00 | 178.87 | 0.00 | 0.00 |
February | 0.13 | 1480.64 | 226.78 | 0.00 | 226.78 | 0.00 | 0.00 |
March | 34.95 | 1059.26 | 339.92 | 0.00 | 339.91 | 0.00 | 0.00 |
April | 126.02 | 741.29 | 393.93 | 3.16 | 390.77 | 0.00 | 0.00 |
May | 299.81 | 398.72 | 512.17 | 19.35 | 492.82 | 0.00 | 0.00 |
June | 495.11 | 255.49 | 599.34 | 55.48 | 543.86 | 0.00 | 0.00 |
July | 502.58 | 206.44 | 562.14 | 38.70 | 523.45 | 0.00 | 0.00 |
August | 436.96 | 259.92 | 471.04 | 9.49 | 461.54 | 0.00 | 0.00 |
September | 247.79 | 472.02 | 360.49 | 0.32 | 360.16 | 0.00 | 0.00 |
October | 46.29 | 795.43 | 267.69 | 0.00 | 267.69 | 0.00 | 0.00 |
November | 5.89 | 1211.04 | 187.25 | 0.00 | 187.25 | 0.00 | 0.00 |
December | 0.00 | 1669.48 | 121.46 | 0.00 | 121.46 | 0.00 | 0.00 |
Annual Sum or Average | 184.07 | 861.12 | 352.42 | 10.58 | 341.83 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 206.44 | 121.46 | 0.00 | 121.46 | 0.00 | 0.00 |
Maximum of Months | 502.58 | 1819.04 | 599.34 | 55.48 | 543.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1884.99 | 178.87 | 0.00 | 178.87 | 0.00 | 0.00 |
February | 0.01 | 1549.96 | 226.78 | 0.00 | 226.78 | 0.00 | 0.00 |
March | 28.76 | 1114.18 | 339.92 | 0.00 | 339.91 | 0.00 | 0.00 |
April | 114.88 | 784.00 | 393.93 | 3.16 | 390.77 | 0.00 | 0.00 |
May | 279.78 | 423.54 | 512.17 | 19.35 | 492.82 | 0.00 | 0.00 |
June | 473.27 | 274.45 | 599.34 | 55.48 | 543.86 | 0.00 | 0.00 |
July | 481.78 | 222.47 | 562.14 | 38.70 | 523.45 | 0.00 | 0.00 |
August | 418.08 | 279.32 | 471.04 | 9.49 | 461.54 | 0.00 | 0.00 |
September | 234.12 | 500.81 | 360.49 | 0.32 | 360.16 | 0.00 | 0.00 |
October | 38.67 | 839.58 | 267.69 | 0.00 | 267.69 | 0.00 | 0.00 |
November | 4.23 | 1269.26 | 187.25 | 0.00 | 187.25 | 0.00 | 0.00 |
December | 0.00 | 1733.97 | 121.46 | 0.00 | 121.46 | 0.00 | 0.00 |
Annual Sum or Average | 173.85 | 903.27 | 352.42 | 10.58 | 341.83 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 222.47 | 121.46 | 0.00 | 121.46 | 0.00 | 0.00 |
Maximum of Months | 481.78 | 1884.99 | 599.34 | 55.48 | 543.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 85.71 | 1298.20 | 388.87 | 192.77 | 196.09 | 0.00 | 0.00 |
February | 158.98 | 1063.97 | 475.81 | 236.14 | 239.67 | 0.00 | 0.00 |
March | 278.52 | 793.23 | 564.61 | 223.44 | 341.16 | 0.00 | 0.00 |
April | 454.50 | 591.32 | 637.59 | 256.76 | 380.84 | 0.00 | 0.00 |
May | 675.68 | 339.17 | 753.70 | 282.72 | 470.98 | 0.00 | 0.00 |
June | 864.32 | 236.10 | 817.33 | 301.41 | 515.91 | 0.00 | 0.00 |
July | 924.82 | 193.64 | 825.41 | 325.43 | 499.98 | 0.00 | 0.00 |
August | 811.91 | 233.28 | 725.58 | 274.39 | 451.19 | 0.00 | 0.00 |
September | 680.20 | 383.86 | 680.49 | 304.73 | 375.77 | 0.00 | 0.00 |
October | 332.73 | 605.74 | 504.00 | 228.92 | 275.08 | 0.00 | 0.00 |
November | 113.95 | 901.03 | 327.88 | 134.63 | 193.25 | 0.00 | 0.00 |
December | 74.16 | 1218.67 | 285.56 | 157.70 | 127.86 | 0.00 | 0.00 |
Annual Sum or Average | 456.25 | 652.88 | 582.74 | 243.25 | 339.50 | 0.00 | 0.00 |
Minimum of Months | 74.16 | 193.64 | 285.56 | 134.63 | 127.86 | 0.00 | 0.00 |
Maximum of Months | 924.82 | 1298.20 | 825.41 | 325.43 | 515.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 394.17 | 1217.23 | 656.38 | 407.66 | 248.72 | 0.00 | 0.00 |
February | 462.63 | 967.67 | 719.47 | 435.42 | 284.05 | 0.00 | 0.00 |
March | 411.43 | 754.11 | 666.35 | 287.92 | 378.43 | 0.00 | 0.00 |
April | 402.81 | 566.86 | 625.00 | 225.61 | 399.39 | 0.00 | 0.00 |
May | 413.29 | 319.74 | 593.40 | 123.47 | 469.93 | 0.00 | 0.00 |
June | 512.57 | 201.60 | 604.31 | 98.62 | 505.69 | 0.00 | 0.00 |
July | 553.99 | 164.08 | 615.97 | 119.06 | 496.91 | 0.00 | 0.00 |
August | 604.07 | 204.55 | 630.53 | 165.64 | 464.88 | 0.00 | 0.00 |
September | 636.45 | 366.23 | 690.08 | 292.48 | 397.60 | 0.00 | 0.00 |
October | 579.15 | 583.26 | 702.38 | 385.05 | 317.33 | 0.00 | 0.00 |
November | 343.95 | 834.15 | 521.01 | 286.00 | 235.01 | 0.00 | 0.00 |
December | 371.91 | 1141.84 | 527.90 | 368.21 | 159.69 | 0.00 | 0.00 |
Annual Sum or Average | 473.96 | 608.46 | 628.87 | 265.32 | 363.55 | 0.00 | 0.00 |
Minimum of Months | 343.95 | 164.08 | 521.01 | 98.62 | 159.69 | 0.00 | 0.00 |
Maximum of Months | 636.45 | 1217.23 | 719.47 | 435.42 | 505.69 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177094E+10 | 0.242627E+10 | 0.216187E+10 | 0.148104E+10 | 0.680827E+09 | 0.00 | 0.00 |
February | 0.173033E+10 | 0.178251E+10 | 0.210582E+10 | 0.142881E+10 | 0.677004E+09 | 0.00 | 0.00 |
March | 0.152242E+10 | 0.150685E+10 | 0.199752E+10 | 0.104602E+10 | 0.951502E+09 | 0.00 | 0.00 |
April | 0.126137E+10 | 0.108890E+10 | 0.172261E+10 | 0.789409E+09 | 0.933202E+09 | 0.00 | 0.00 |
May | 0.111387E+10 | 0.666095E+09 | 0.151797E+10 | 0.424460E+09 | 0.109351E+10 | 0.00 | 0.00 |
June | 0.119196E+10 | 0.421652E+09 | 0.140231E+10 | 0.279854E+09 | 0.112246E+10 | 0.00 | 0.00 |
July | 0.136637E+10 | 0.359266E+09 | 0.153774E+10 | 0.384367E+09 | 0.115337E+10 | 0.00 | 0.00 |
August | 0.161813E+10 | 0.438136E+09 | 0.170409E+10 | 0.589967E+09 | 0.111413E+10 | 0.00 | 0.00 |
September | 0.190981E+10 | 0.735151E+09 | 0.199173E+10 | 0.102792E+10 | 0.963813E+09 | 0.00 | 0.00 |
October | 0.209232E+10 | 0.117473E+10 | 0.221837E+10 | 0.139889E+10 | 0.819486E+09 | 0.00 | 0.00 |
November | 0.134182E+10 | 0.159630E+10 | 0.160609E+10 | 0.100551E+10 | 0.600580E+09 | 0.00 | 0.00 |
December | 0.157813E+10 | 0.229142E+10 | 0.176660E+10 | 0.133773E+10 | 0.428872E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.184975E+11 | 0.144873E+11 | 0.217327E+11 | 0.111940E+11 | 0.105387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.111387E+10 | 0.359266E+09 | 0.140231E+10 | 0.279854E+09 | 0.428872E+09 | 0.00 | 0.00 |
Maximum of Months | 0.209232E+10 | 0.242627E+10 | 0.221837E+10 | 0.148104E+10 | 0.115337E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.491680E+10 | 0.709756E+10 | 0.608768E+10 | 0.417051E+10 | 0.191716E+10 | 0.00 | 0.00 |
February | 0.479955E+10 | 0.529553E+10 | 0.592984E+10 | 0.402344E+10 | 0.190640E+10 | 0.00 | 0.00 |
March | 0.420640E+10 | 0.450958E+10 | 0.562489E+10 | 0.294553E+10 | 0.267937E+10 | 0.00 | 0.00 |
April | 0.349766E+10 | 0.327577E+10 | 0.485076E+10 | 0.222292E+10 | 0.262783E+10 | 0.00 | 0.00 |
May | 0.310690E+10 | 0.196042E+10 | 0.427449E+10 | 0.119525E+10 | 0.307924E+10 | 0.00 | 0.00 |
June | 0.333201E+10 | 0.124652E+10 | 0.394882E+10 | 0.788050E+09 | 0.316077E+10 | 0.00 | 0.00 |
July | 0.383073E+10 | 0.105370E+10 | 0.433017E+10 | 0.108235E+10 | 0.324782E+10 | 0.00 | 0.00 |
August | 0.454037E+10 | 0.129525E+10 | 0.479861E+10 | 0.166131E+10 | 0.313731E+10 | 0.00 | 0.00 |
September | 0.534801E+10 | 0.217164E+10 | 0.560859E+10 | 0.289456E+10 | 0.271403E+10 | 0.00 | 0.00 |
October | 0.581821E+10 | 0.350178E+10 | 0.624679E+10 | 0.393917E+10 | 0.230762E+10 | 0.00 | 0.00 |
November | 0.371518E+10 | 0.475458E+10 | 0.452265E+10 | 0.283146E+10 | 0.169119E+10 | 0.00 | 0.00 |
December | 0.437928E+10 | 0.677725E+10 | 0.497464E+10 | 0.376696E+10 | 0.120768E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.514911E+11 | 0.429396E+11 | 0.611979E+11 | 0.315215E+11 | 0.296764E+11 | 0.00 | 0.00 |
Minimum of Months | 0.310690E+10 | 0.105370E+10 | 0.394882E+10 | 0.788050E+09 | 0.120768E+10 | 0.00 | 0.00 |
Maximum of Months | 0.581821E+10 | 0.709756E+10 | 0.624679E+10 | 0.417051E+10 | 0.324782E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.639969E+10 | 0.983624E+10 | 0.790824E+10 | 0.541773E+10 | 0.249051E+10 | 0.00 | 0.00 |
February | 0.627877E+10 | 0.728701E+10 | 0.770320E+10 | 0.522668E+10 | 0.247652E+10 | 0.00 | 0.00 |
March | 0.549518E+10 | 0.622087E+10 | 0.730706E+10 | 0.382641E+10 | 0.348065E+10 | 0.00 | 0.00 |
April | 0.460433E+10 | 0.453529E+10 | 0.630141E+10 | 0.288770E+10 | 0.341371E+10 | 0.00 | 0.00 |
May | 0.409102E+10 | 0.268720E+10 | 0.555281E+10 | 0.155270E+10 | 0.400011E+10 | 0.00 | 0.00 |
June | 0.442385E+10 | 0.170304E+10 | 0.512974E+10 | 0.102372E+10 | 0.410601E+10 | 0.00 | 0.00 |
July | 0.509385E+10 | 0.142564E+10 | 0.562513E+10 | 0.140604E+10 | 0.421910E+10 | 0.00 | 0.00 |
August | 0.603525E+10 | 0.173948E+10 | 0.623367E+10 | 0.215813E+10 | 0.407554E+10 | 0.00 | 0.00 |
September | 0.709897E+10 | 0.293665E+10 | 0.728588E+10 | 0.376020E+10 | 0.352568E+10 | 0.00 | 0.00 |
October | 0.767792E+10 | 0.475584E+10 | 0.811494E+10 | 0.511721E+10 | 0.299773E+10 | 0.00 | 0.00 |
November | 0.485354E+10 | 0.659897E+10 | 0.587518E+10 | 0.367822E+10 | 0.219696E+10 | 0.00 | 0.00 |
December | 0.572821E+10 | 0.938641E+10 | 0.646233E+10 | 0.489350E+10 | 0.156884E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.677806E+11 | 0.591127E+11 | 0.794996E+11 | 0.409482E+11 | 0.385514E+11 | 0.00 | 0.00 |
Minimum of Months | 0.409102E+10 | 0.142564E+10 | 0.512974E+10 | 0.102372E+10 | 0.156884E+10 | 0.00 | 0.00 |
Maximum of Months | 0.767792E+10 | 0.983624E+10 | 0.811494E+10 | 0.541773E+10 | 0.421910E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.320530E+09 | 0.151940E+10 | 0.699230E+09 | 0.403120E+09 | 0.296110E+09 | 0.00 | 0.00 |
February | 0.440486E+09 | 0.110028E+10 | 0.774921E+09 | 0.458874E+09 | 0.316047E+09 | 0.00 | 0.00 |
March | 0.557120E+09 | 0.851925E+09 | 0.869042E+09 | 0.383039E+09 | 0.486003E+09 | 0.00 | 0.00 |
April | 0.841051E+09 | 0.575470E+09 | 0.101199E+10 | 0.488373E+09 | 0.523617E+09 | 0.00 | 0.00 |
May | 0.924270E+09 | 0.310660E+09 | 0.995310E+09 | 0.362297E+09 | 0.633013E+09 | 0.00 | 0.00 |
June | 0.115461E+10 | 0.175518E+09 | 0.106434E+10 | 0.395718E+09 | 0.668625E+09 | 0.00 | 0.00 |
July | 0.132495E+10 | 0.139858E+09 | 0.117762E+10 | 0.490513E+09 | 0.687111E+09 | 0.00 | 0.00 |
August | 0.124240E+10 | 0.177615E+09 | 0.109963E+10 | 0.465715E+09 | 0.633912E+09 | 0.00 | 0.00 |
September | 0.102720E+10 | 0.341623E+09 | 0.992526E+09 | 0.486942E+09 | 0.505585E+09 | 0.00 | 0.00 |
October | 0.740660E+09 | 0.614635E+09 | 0.871945E+09 | 0.470009E+09 | 0.401935E+09 | 0.00 | 0.00 |
November | 0.343804E+09 | 0.937385E+09 | 0.567639E+09 | 0.291508E+09 | 0.276131E+09 | 0.00 | 0.00 |
December | 0.314256E+09 | 0.139763E+10 | 0.548023E+09 | 0.358345E+09 | 0.189678E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.923134E+10 | 0.814200E+10 | 0.106722E+11 | 0.505445E+10 | 0.561777E+10 | 0.00 | 0.00 |
Minimum of Months | 0.314256E+09 | 0.139858E+09 | 0.548023E+09 | 0.291508E+09 | 0.189678E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132495E+10 | 0.151940E+10 | 0.117762E+10 | 0.490513E+09 | 0.687111E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 55964637.51 | 0.170430E+10 | 0.341051E+09 | 0.110889E+09 | 0.230162E+09 | 0.00 | 0.00 |
February | 0.150193E+09 | 0.121480E+10 | 0.437726E+09 | 0.176949E+09 | 0.260777E+09 | 0.00 | 0.00 |
March | 0.292351E+09 | 0.878931E+09 | 0.604862E+09 | 0.176645E+09 | 0.428217E+09 | 0.00 | 0.00 |
April | 0.650063E+09 | 0.576384E+09 | 0.817848E+09 | 0.333780E+09 | 0.484068E+09 | 0.00 | 0.00 |
May | 0.824284E+09 | 0.309049E+09 | 0.891613E+09 | 0.285944E+09 | 0.605669E+09 | 0.00 | 0.00 |
June | 0.109295E+10 | 0.178870E+09 | 0.100940E+10 | 0.361025E+09 | 0.648375E+09 | 0.00 | 0.00 |
July | 0.122485E+10 | 0.153451E+09 | 0.108913E+10 | 0.429466E+09 | 0.659664E+09 | 0.00 | 0.00 |
August | 0.107339E+10 | 0.191049E+09 | 0.943476E+09 | 0.352935E+09 | 0.590540E+09 | 0.00 | 0.00 |
September | 0.740503E+09 | 0.349438E+09 | 0.732908E+09 | 0.284238E+09 | 0.448670E+09 | 0.00 | 0.00 |
October | 0.363276E+09 | 0.626453E+09 | 0.536573E+09 | 0.193989E+09 | 0.342584E+09 | 0.00 | 0.00 |
November | 0.109721E+09 | 0.100168E+10 | 0.320016E+09 | 93106182.22 | 0.226910E+09 | 0.00 | 0.00 |
December | 53945718.15 | 0.151598E+10 | 0.245885E+09 | 94391805.94 | 0.151493E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.663149E+10 | 0.870038E+10 | 0.797049E+10 | 0.289336E+10 | 0.507713E+10 | 0.00 | 0.00 |
Minimum of Months | 53945718.15 | 0.153451E+09 | 0.245885E+09 | 93106182.22 | 0.151493E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122485E+10 | 0.170430E+10 | 0.108913E+10 | 0.429466E+09 | 0.659664E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.285753E+09 | 0.364873E+09 | 0.341186E+09 | 0.233738E+09 | 0.107448E+09 | 0.00 | 0.00 |
February | 0.273639E+09 | 0.289424E+09 | 0.332340E+09 | 0.225495E+09 | 0.106845E+09 | 0.00 | 0.00 |
March | 0.240461E+09 | 0.244073E+09 | 0.315249E+09 | 0.165083E+09 | 0.150166E+09 | 0.00 | 0.00 |
April | 0.192226E+09 | 0.206838E+09 | 0.271862E+09 | 0.124584E+09 | 0.147278E+09 | 0.00 | 0.00 |
May | 0.158261E+09 | 0.137859E+09 | 0.239565E+09 | 66988341.30 | 0.172577E+09 | 0.00 | 0.00 |
June | 0.173627E+09 | 91298472.53 | 0.221313E+09 | 44166536.92 | 0.177146E+09 | 0.00 | 0.00 |
July | 0.200900E+09 | 78129494.58 | 0.242686E+09 | 60660724.97 | 0.182025E+09 | 0.00 | 0.00 |
August | 0.242202E+09 | 93673913.58 | 0.268940E+09 | 93108532.74 | 0.175831E+09 | 0.00 | 0.00 |
September | 0.291600E+09 | 0.149447E+09 | 0.314336E+09 | 0.162227E+09 | 0.152109E+09 | 0.00 | 0.00 |
October | 0.313739E+09 | 0.233669E+09 | 0.350104E+09 | 0.220772E+09 | 0.129331E+09 | 0.00 | 0.00 |
November | 0.204306E+09 | 0.284554E+09 | 0.253473E+09 | 0.158690E+09 | 94783559.68 | 0.00 | 0.00 |
December | 0.255113E+09 | 0.343244E+09 | 0.278805E+09 | 0.211121E+09 | 67684606.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.283183E+10 | 0.251708E+10 | 0.342986E+10 | 0.176663E+10 | 0.166322E+10 | 0.00 | 0.00 |
Minimum of Months | 0.158261E+09 | 78129494.58 | 0.221313E+09 | 44166536.92 | 67684606.97 | 0.00 | 0.00 |
Maximum of Months | 0.313739E+09 | 0.364873E+09 | 0.350104E+09 | 0.233738E+09 | 0.182025E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.520954E+09 | 54718265.40 | 0.00 | 54718265.40 | 0.00 | 0.00 |
February | 590380.80 | 0.379392E+09 | 62658631.99 | 0.00 | 62658631.99 | 0.00 | 0.00 |
March | 19011128.63 | 0.269817E+09 | 0.103982E+09 | 879.42 | 0.103981E+09 | 0.00 | 0.00 |
April | 51607852.14 | 0.170097E+09 | 0.116618E+09 | 935182.32 | 0.115683E+09 | 0.00 | 0.00 |
May | 0.117507E+09 | 84553050.65 | 0.156676E+09 | 5919926.48 | 0.150756E+09 | 0.00 | 0.00 |
June | 0.175457E+09 | 47034029.46 | 0.177426E+09 | 16423262.16 | 0.161003E+09 | 0.00 | 0.00 |
July | 0.181187E+09 | 37965300.65 | 0.171962E+09 | 11837278.01 | 0.160125E+09 | 0.00 | 0.00 |
August | 0.158397E+09 | 48875359.75 | 0.144092E+09 | 2903936.81 | 0.141188E+09 | 0.00 | 0.00 |
September | 92032478.61 | 98818901.83 | 0.106717E+09 | 95766.54 | 0.106622E+09 | 0.00 | 0.00 |
October | 26386487.38 | 0.186807E+09 | 81886317.06 | 0.00 | 81886317.06 | 0.00 | 0.00 |
November | 5021073.85 | 0.304582E+09 | 55432571.70 | 0.00 | 55432571.70 | 0.00 | 0.00 |
December | 0.00 | 0.457940E+09 | 37155449.56 | 0.00 | 37155449.56 | 0.00 | 0.00 |
Annual Sum or Average | 0.827199E+09 | 0.260683E+10 | 0.126932E+10 | 38116231.74 | 0.123121E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 37965300.65 | 37155449.56 | 0.00 | 37155449.56 | 0.00 | 0.00 |
Maximum of Months | 0.181187E+09 | 0.520954E+09 | 0.177426E+09 | 16423262.16 | 0.161003E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.316178E+09 | 0.151229E+10 | 0.699450E+09 | 0.404072E+09 | 0.295378E+09 | 0.00 | 0.00 |
February | 0.395817E+09 | 0.108369E+10 | 0.743686E+09 | 0.426373E+09 | 0.317313E+09 | 0.00 | 0.00 |
March | 0.567889E+09 | 0.839612E+09 | 0.887626E+09 | 0.402201E+09 | 0.485425E+09 | 0.00 | 0.00 |
April | 0.721470E+09 | 0.561617E+09 | 0.922757E+09 | 0.409801E+09 | 0.512956E+09 | 0.00 | 0.00 |
May | 0.980768E+09 | 0.292628E+09 | 0.106044E+10 | 0.416515E+09 | 0.643920E+09 | 0.00 | 0.00 |
June | 0.116404E+10 | 0.165092E+09 | 0.108592E+10 | 0.407682E+09 | 0.678234E+09 | 0.00 | 0.00 |
July | 0.127669E+10 | 0.129965E+09 | 0.114878E+10 | 0.466007E+09 | 0.682778E+09 | 0.00 | 0.00 |
August | 0.116713E+10 | 0.165474E+09 | 0.104902E+10 | 0.423572E+09 | 0.625449E+09 | 0.00 | 0.00 |
September | 0.103668E+10 | 0.331989E+09 | 0.101105E+10 | 0.495973E+09 | 0.515075E+09 | 0.00 | 0.00 |
October | 0.690438E+09 | 0.601967E+09 | 0.842121E+09 | 0.444345E+09 | 0.397776E+09 | 0.00 | 0.00 |
November | 0.312063E+09 | 0.925944E+09 | 0.548406E+09 | 0.273540E+09 | 0.274866E+09 | 0.00 | 0.00 |
December | 0.287891E+09 | 0.138452E+10 | 0.533193E+09 | 0.343005E+09 | 0.190188E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.891706E+10 | 0.799478E+10 | 0.105324E+11 | 0.491309E+10 | 0.561936E+10 | 0.00 | 0.00 |
Minimum of Months | 0.287891E+09 | 0.129965E+09 | 0.533193E+09 | 0.273540E+09 | 0.190188E+09 | 0.00 | 0.00 |
Maximum of Months | 0.127669E+10 | 0.151229E+10 | 0.114878E+10 | 0.495973E+09 | 0.682778E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 35787369.74 | 0.168108E+10 | 0.341272E+09 | 0.111842E+09 | 0.229430E+09 | 0.00 | 0.00 |
February | 0.100101E+09 | 0.119220E+10 | 0.406491E+09 | 0.144447E+09 | 0.262044E+09 | 0.00 | 0.00 |
March | 0.294555E+09 | 0.857210E+09 | 0.623446E+09 | 0.195807E+09 | 0.427639E+09 | 0.00 | 0.00 |
April | 0.529782E+09 | 0.559794E+09 | 0.728615E+09 | 0.255208E+09 | 0.473407E+09 | 0.00 | 0.00 |
May | 0.887421E+09 | 0.291556E+09 | 0.956738E+09 | 0.340162E+09 | 0.616576E+09 | 0.00 | 0.00 |
June | 0.111007E+10 | 0.170408E+09 | 0.103097E+10 | 0.372989E+09 | 0.657984E+09 | 0.00 | 0.00 |
July | 0.118563E+10 | 0.141262E+09 | 0.106029E+10 | 0.404961E+09 | 0.655331E+09 | 0.00 | 0.00 |
August | 0.100638E+10 | 0.175584E+09 | 0.892870E+09 | 0.310793E+09 | 0.582078E+09 | 0.00 | 0.00 |
September | 0.750143E+09 | 0.335492E+09 | 0.751429E+09 | 0.293269E+09 | 0.458160E+09 | 0.00 | 0.00 |
October | 0.304011E+09 | 0.602665E+09 | 0.506749E+09 | 0.168325E+09 | 0.338424E+09 | 0.00 | 0.00 |
November | 72537490.17 | 0.984484E+09 | 0.300783E+09 | 75138110.57 | 0.225644E+09 | 0.00 | 0.00 |
December | 27913377.53 | 0.150404E+10 | 0.231055E+09 | 79051632.14 | 0.152003E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.630433E+10 | 0.849578E+10 | 0.783071E+10 | 0.275199E+10 | 0.507872E+10 | 0.00 | 0.00 |
Minimum of Months | 27913377.53 | 0.141262E+09 | 0.231055E+09 | 75138110.57 | 0.152003E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118563E+10 | 0.168108E+10 | 0.106029E+10 | 0.404961E+09 | 0.657984E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.460147E+09 | 0.179075E+10 | 0.857793E+09 | 0.506445E+09 | 0.351348E+09 | 0.00 | 0.00 |
February | 0.502774E+09 | 0.129094E+10 | 0.855828E+09 | 0.488585E+09 | 0.367242E+09 | 0.00 | 0.00 |
March | 0.553883E+09 | 0.106021E+10 | 0.908316E+09 | 0.357691E+09 | 0.550625E+09 | 0.00 | 0.00 |
April | 0.575694E+09 | 0.710165E+09 | 0.841684E+09 | 0.271966E+09 | 0.569718E+09 | 0.00 | 0.00 |
May | 0.702560E+09 | 0.361606E+09 | 0.858485E+09 | 0.157970E+09 | 0.700516E+09 | 0.00 | 0.00 |
June | 0.848183E+09 | 0.205875E+09 | 0.863887E+09 | 0.131275E+09 | 0.732612E+09 | 0.00 | 0.00 |
July | 0.917276E+09 | 0.174541E+09 | 0.898360E+09 | 0.157078E+09 | 0.741281E+09 | 0.00 | 0.00 |
August | 0.953708E+09 | 0.223979E+09 | 0.894869E+09 | 0.208031E+09 | 0.686838E+09 | 0.00 | 0.00 |
September | 0.901870E+09 | 0.426321E+09 | 0.912263E+09 | 0.351707E+09 | 0.560556E+09 | 0.00 | 0.00 |
October | 0.800093E+09 | 0.744657E+09 | 0.935970E+09 | 0.478352E+09 | 0.457618E+09 | 0.00 | 0.00 |
November | 0.427308E+09 | 0.113367E+10 | 0.669292E+09 | 0.343837E+09 | 0.325455E+09 | 0.00 | 0.00 |
December | 0.444844E+09 | 0.166078E+10 | 0.684584E+09 | 0.457439E+09 | 0.227145E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.808834E+10 | 0.978350E+10 | 0.101813E+11 | 0.391038E+10 | 0.627096E+10 | 0.00 | 0.00 |
Minimum of Months | 0.427308E+09 | 0.174541E+09 | 0.669292E+09 | 0.131275E+09 | 0.227145E+09 | 0.00 | 0.00 |
Maximum of Months | 0.953708E+09 | 0.179075E+10 | 0.935970E+09 | 0.506445E+09 | 0.741281E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.317157E+09 | 0.152991E+10 | 0.699803E+09 | 0.403450E+09 | 0.296353E+09 | 0.00 | 0.00 |
February | 0.435811E+09 | 0.110991E+10 | 0.775556E+09 | 0.459250E+09 | 0.316306E+09 | 0.00 | 0.00 |
March | 0.556286E+09 | 0.853215E+09 | 0.869755E+09 | 0.383353E+09 | 0.486402E+09 | 0.00 | 0.00 |
April | 0.836586E+09 | 0.575624E+09 | 0.101282E+10 | 0.488773E+09 | 0.524047E+09 | 0.00 | 0.00 |
May | 0.915055E+09 | 0.312422E+09 | 0.996126E+09 | 0.362594E+09 | 0.633532E+09 | 0.00 | 0.00 |
June | 0.114729E+10 | 0.175537E+09 | 0.106522E+10 | 0.396042E+09 | 0.669174E+09 | 0.00 | 0.00 |
July | 0.131783E+10 | 0.139151E+09 | 0.117859E+10 | 0.490915E+09 | 0.687675E+09 | 0.00 | 0.00 |
August | 0.123597E+10 | 0.177371E+09 | 0.110053E+10 | 0.466097E+09 | 0.634432E+09 | 0.00 | 0.00 |
September | 0.102407E+10 | 0.339963E+09 | 0.993341E+09 | 0.487341E+09 | 0.505999E+09 | 0.00 | 0.00 |
October | 0.739177E+09 | 0.613748E+09 | 0.872660E+09 | 0.470395E+09 | 0.402265E+09 | 0.00 | 0.00 |
November | 0.343962E+09 | 0.938318E+09 | 0.568105E+09 | 0.291747E+09 | 0.276358E+09 | 0.00 | 0.00 |
December | 0.313963E+09 | 0.140433E+10 | 0.548472E+09 | 0.358639E+09 | 0.189833E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.918316E+10 | 0.816950E+10 | 0.106810E+11 | 0.505860E+10 | 0.562238E+10 | 0.00 | 0.00 |
Minimum of Months | 0.313963E+09 | 0.139151E+09 | 0.548472E+09 | 0.291747E+09 | 0.189833E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131783E+10 | 0.152991E+10 | 0.117859E+10 | 0.490915E+09 | 0.687675E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 55332596.47 | 0.171647E+10 | 0.341331E+09 | 0.110980E+09 | 0.230351E+09 | 0.00 | 0.00 |
February | 0.148888E+09 | 0.122579E+10 | 0.438085E+09 | 0.177094E+09 | 0.260991E+09 | 0.00 | 0.00 |
March | 0.292529E+09 | 0.880073E+09 | 0.605358E+09 | 0.176790E+09 | 0.428568E+09 | 0.00 | 0.00 |
April | 0.645435E+09 | 0.577422E+09 | 0.818519E+09 | 0.334054E+09 | 0.484465E+09 | 0.00 | 0.00 |
May | 0.810721E+09 | 0.313751E+09 | 0.892344E+09 | 0.286178E+09 | 0.606166E+09 | 0.00 | 0.00 |
June | 0.108068E+10 | 0.183452E+09 | 0.101023E+10 | 0.361321E+09 | 0.648907E+09 | 0.00 | 0.00 |
July | 0.121105E+10 | 0.160279E+09 | 0.109002E+10 | 0.429819E+09 | 0.660205E+09 | 0.00 | 0.00 |
August | 0.106185E+10 | 0.197879E+09 | 0.944250E+09 | 0.353225E+09 | 0.591025E+09 | 0.00 | 0.00 |
September | 0.736258E+09 | 0.350595E+09 | 0.733509E+09 | 0.284471E+09 | 0.449038E+09 | 0.00 | 0.00 |
October | 0.364457E+09 | 0.623974E+09 | 0.537013E+09 | 0.194148E+09 | 0.342865E+09 | 0.00 | 0.00 |
November | 0.110945E+09 | 0.100165E+10 | 0.320278E+09 | 93182561.37 | 0.227096E+09 | 0.00 | 0.00 |
December | 54142864.48 | 0.152307E+10 | 0.246087E+09 | 94469239.74 | 0.151618E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.657228E+10 | 0.875440E+10 | 0.797703E+10 | 0.289573E+10 | 0.508129E+10 | 0.00 | 0.00 |
Minimum of Months | 54142864.48 | 0.160279E+09 | 0.246087E+09 | 93182561.37 | 0.151618E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121105E+10 | 0.171647E+10 | 0.109002E+10 | 0.429819E+09 | 0.660205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.487760E+09 | 0.778042E+09 | 0.626115E+09 | 0.428935E+09 | 0.197180E+09 | 0.00 | 0.00 |
February | 0.478591E+09 | 0.571908E+09 | 0.609882E+09 | 0.413809E+09 | 0.196072E+09 | 0.00 | 0.00 |
March | 0.435609E+09 | 0.453087E+09 | 0.578518E+09 | 0.302946E+09 | 0.275572E+09 | 0.00 | 0.00 |
April | 0.375510E+09 | 0.306777E+09 | 0.498898E+09 | 0.228627E+09 | 0.270272E+09 | 0.00 | 0.00 |
May | 0.346970E+09 | 0.163711E+09 | 0.439630E+09 | 0.122931E+09 | 0.316699E+09 | 0.00 | 0.00 |
June | 0.382971E+09 | 88794111.55 | 0.406134E+09 | 81050618.64 | 0.325083E+09 | 0.00 | 0.00 |
July | 0.437188E+09 | 67518641.12 | 0.445356E+09 | 0.111319E+09 | 0.334036E+09 | 0.00 | 0.00 |
August | 0.506576E+09 | 88460767.35 | 0.493535E+09 | 0.170865E+09 | 0.322671E+09 | 0.00 | 0.00 |
September | 0.580475E+09 | 0.177436E+09 | 0.576841E+09 | 0.297704E+09 | 0.279137E+09 | 0.00 | 0.00 |
October | 0.614088E+09 | 0.322555E+09 | 0.642480E+09 | 0.405142E+09 | 0.237338E+09 | 0.00 | 0.00 |
November | 0.384136E+09 | 0.482214E+09 | 0.465153E+09 | 0.291214E+09 | 0.173939E+09 | 0.00 | 0.00 |
December | 0.445161E+09 | 0.717085E+09 | 0.511639E+09 | 0.387430E+09 | 0.124209E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.547503E+10 | 0.421759E+10 | 0.629418E+10 | 0.324197E+10 | 0.305221E+10 | 0.00 | 0.00 |
Minimum of Months | 0.346970E+09 | 67518641.12 | 0.406134E+09 | 81050618.64 | 0.124209E+09 | 0.00 | 0.00 |
Maximum of Months | 0.614088E+09 | 0.778042E+09 | 0.642480E+09 | 0.428935E+09 | 0.334036E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.487213E+10 | 0.479096E+09 | 0.00 | 0.479096E+09 | 0.00 | 0.00 |
February | 316073.35 | 0.358195E+10 | 0.548619E+09 | 0.00 | 0.548619E+09 | 0.00 | 0.00 |
March | 93606077.26 | 0.283713E+10 | 0.910430E+09 | 7699.91 | 0.910422E+09 | 0.00 | 0.00 |
April | 0.326644E+09 | 0.192143E+10 | 0.102107E+10 | 8188162.50 | 0.101288E+10 | 0.00 | 0.00 |
May | 0.803009E+09 | 0.106793E+10 | 0.137181E+10 | 51833015.89 | 0.131998E+10 | 0.00 | 0.00 |
June | 0.128331E+10 | 0.662225E+09 | 0.155349E+10 | 0.143797E+09 | 0.140969E+10 | 0.00 | 0.00 |
July | 0.134610E+10 | 0.552916E+09 | 0.150565E+10 | 0.103643E+09 | 0.140200E+10 | 0.00 | 0.00 |
August | 0.117035E+10 | 0.696170E+09 | 0.126162E+10 | 25425958.08 | 0.123620E+10 | 0.00 | 0.00 |
September | 0.642272E+09 | 0.122347E+10 | 0.934384E+09 | 838501.69 | 0.933546E+09 | 0.00 | 0.00 |
October | 0.123978E+09 | 0.213048E+10 | 0.716971E+09 | 0.00 | 0.716971E+09 | 0.00 | 0.00 |
November | 15274332.52 | 0.313901E+10 | 0.485350E+09 | 0.00 | 0.485350E+09 | 0.00 | 0.00 |
December | 0.00 | 0.447153E+10 | 0.325321E+09 | 0.00 | 0.325321E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.580486E+10 | 0.271564E+11 | 0.111138E+11 | 0.333734E+09 | 0.107801E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.552916E+09 | 0.325321E+09 | 0.00 | 0.325321E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134610E+10 | 0.487213E+10 | 0.155349E+10 | 0.143797E+09 | 0.140969E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.504877E+10 | 0.479096E+09 | 0.00 | 0.479096E+09 | 0.00 | 0.00 |
February | 21707.28 | 0.374967E+10 | 0.548619E+09 | 0.00 | 0.548619E+09 | 0.00 | 0.00 |
March | 77043952.76 | 0.298422E+10 | 0.910430E+09 | 7699.91 | 0.910422E+09 | 0.00 | 0.00 |
April | 0.297762E+09 | 0.203213E+10 | 0.102107E+10 | 8188162.50 | 0.101288E+10 | 0.00 | 0.00 |
May | 0.749362E+09 | 0.113442E+10 | 0.137181E+10 | 51833015.89 | 0.131998E+10 | 0.00 | 0.00 |
June | 0.122673E+10 | 0.711362E+09 | 0.155349E+10 | 0.143797E+09 | 0.140969E+10 | 0.00 | 0.00 |
July | 0.129041E+10 | 0.595877E+09 | 0.150565E+10 | 0.103643E+09 | 0.140200E+10 | 0.00 | 0.00 |
August | 0.111978E+10 | 0.748120E+09 | 0.126162E+10 | 25425958.08 | 0.123620E+10 | 0.00 | 0.00 |
September | 0.606836E+09 | 0.129809E+10 | 0.934384E+09 | 838501.69 | 0.933546E+09 | 0.00 | 0.00 |
October | 0.103569E+09 | 0.224874E+10 | 0.716971E+09 | 0.00 | 0.716971E+09 | 0.00 | 0.00 |
November | 10955391.17 | 0.328992E+10 | 0.485350E+09 | 0.00 | 0.485350E+09 | 0.00 | 0.00 |
December | 0.00 | 0.464428E+10 | 0.325321E+09 | 0.00 | 0.325321E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.548247E+10 | 0.284856E+11 | 0.111138E+11 | 0.333734E+09 | 0.107801E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.595877E+09 | 0.325321E+09 | 0.00 | 0.325321E+09 | 0.00 | 0.00 |
Maximum of Months | 0.129041E+10 | 0.504877E+10 | 0.155349E+10 | 0.143797E+09 | 0.140969E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229570E+09 | 0.347709E+10 | 0.104154E+10 | 0.516321E+09 | 0.525216E+09 | 0.00 | 0.00 |
February | 0.384605E+09 | 0.257397E+10 | 0.115107E+10 | 0.571268E+09 | 0.579806E+09 | 0.00 | 0.00 |
March | 0.745984E+09 | 0.212458E+10 | 0.151224E+10 | 0.598471E+09 | 0.913771E+09 | 0.00 | 0.00 |
April | 0.117805E+10 | 0.153271E+10 | 0.165264E+10 | 0.665518E+09 | 0.987126E+09 | 0.00 | 0.00 |
May | 0.180975E+10 | 0.908436E+09 | 0.201872E+10 | 0.757250E+09 | 0.126147E+10 | 0.00 | 0.00 |
June | 0.224033E+10 | 0.611969E+09 | 0.211851E+10 | 0.781261E+09 | 0.133725E+10 | 0.00 | 0.00 |
July | 0.247703E+10 | 0.518645E+09 | 0.221077E+10 | 0.871627E+09 | 0.133914E+10 | 0.00 | 0.00 |
August | 0.217462E+10 | 0.624828E+09 | 0.194338E+10 | 0.734924E+09 | 0.120846E+10 | 0.00 | 0.00 |
September | 0.176307E+10 | 0.994973E+09 | 0.176384E+10 | 0.789848E+09 | 0.973988E+09 | 0.00 | 0.00 |
October | 0.891183E+09 | 0.162241E+10 | 0.134992E+10 | 0.613149E+09 | 0.736771E+09 | 0.00 | 0.00 |
November | 0.295359E+09 | 0.233548E+10 | 0.849852E+09 | 0.348953E+09 | 0.500899E+09 | 0.00 | 0.00 |
December | 0.198643E+09 | 0.326408E+10 | 0.764848E+09 | 0.422391E+09 | 0.342457E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.143882E+11 | 0.205892E+11 | 0.183773E+11 | 0.767098E+10 | 0.107064E+11 | 0.00 | 0.00 |
Minimum of Months | 0.198643E+09 | 0.518645E+09 | 0.764848E+09 | 0.348953E+09 | 0.342457E+09 | 0.00 | 0.00 |
Maximum of Months | 0.247703E+10 | 0.347709E+10 | 0.221077E+10 | 0.871627E+09 | 0.133914E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105574E+10 | 0.326022E+10 | 0.175804E+10 | 0.109188E+10 | 0.666166E+09 | 0.00 | 0.00 |
February | 0.111919E+10 | 0.234099E+10 | 0.174055E+10 | 0.105337E+10 | 0.687180E+09 | 0.00 | 0.00 |
March | 0.110198E+10 | 0.201980E+10 | 0.178474E+10 | 0.771168E+09 | 0.101358E+10 | 0.00 | 0.00 |
April | 0.104409E+10 | 0.146930E+10 | 0.162000E+10 | 0.584788E+09 | 0.103521E+10 | 0.00 | 0.00 |
May | 0.110694E+10 | 0.856400E+09 | 0.158936E+10 | 0.330696E+09 | 0.125866E+10 | 0.00 | 0.00 |
June | 0.132858E+10 | 0.522550E+09 | 0.156637E+10 | 0.255613E+09 | 0.131076E+10 | 0.00 | 0.00 |
July | 0.148380E+10 | 0.439482E+09 | 0.164982E+10 | 0.318898E+09 | 0.133092E+10 | 0.00 | 0.00 |
August | 0.161795E+10 | 0.547857E+09 | 0.168881E+10 | 0.443661E+09 | 0.124515E+10 | 0.00 | 0.00 |
September | 0.164967E+10 | 0.949259E+09 | 0.178869E+10 | 0.758110E+09 | 0.103058E+10 | 0.00 | 0.00 |
October | 0.155120E+10 | 0.156221E+10 | 0.188125E+10 | 0.103131E+10 | 0.849934E+09 | 0.00 | 0.00 |
November | 0.891515E+09 | 0.216213E+10 | 0.135045E+10 | 0.741301E+09 | 0.609149E+09 | 0.00 | 0.00 |
December | 0.996133E+09 | 0.305832E+10 | 0.141393E+10 | 0.986224E+09 | 0.427701E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.149468E+11 | 0.191885E+11 | 0.198320E+11 | 0.836702E+10 | 0.114650E+11 | 0.00 | 0.00 |
Minimum of Months | 0.891515E+09 | 0.439482E+09 | 0.135045E+10 | 0.255613E+09 | 0.427701E+09 | 0.00 | 0.00 |
Maximum of Months | 0.164967E+10 | 0.326022E+10 | 0.188125E+10 | 0.109188E+10 | 0.133092E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.3 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.42 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.29 | 8.94 | 5.14 | 4.69 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.70 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.86 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 16.99 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.23 | 8.10 | 4.97 | 3.17 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.70 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.4 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.18 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.86 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.61 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.92 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.10 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.68 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.80 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.66 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.30 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.17 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.34 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.46 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.93 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.66 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.0 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.87 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.92 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.93 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.92 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.80 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.63 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.17 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.83 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.03 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.93 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.93 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.63 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.87 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.92 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.34 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.63 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.78 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.78 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.63 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.509702E+11 | -.799169E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.145275E+10 | 58.99 | 0.00 | 0.00 |
February | 0.476589E+11 | -.736586E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.134010E+10 | 58.98 | 0.00 | 0.00 |
March | 0.519096E+11 | -.807865E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.145320E+10 | 58.97 | 0.00 | 0.00 |
April | 0.469303E+11 | -.751097E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.141187E+10 | 58.98 | 0.00 | 0.00 |
May | 0.435315E+11 | -.730078E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.146090E+10 | 59.02 | 0.00 | 0.00 |
June | 0.370677E+11 | -.659618E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.141196E+10 | 59.06 | 0.00 | 0.00 |
July | 0.341617E+11 | -.643146E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.146210E+10 | 59.16 | 0.00 | 0.00 |
August | 0.323502E+11 | -.626419E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.145570E+10 | 59.19 | 0.00 | 0.00 |
September | 0.321307E+11 | -.614094E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.138363E+10 | 59.19 | 0.00 | 0.00 |
October | 0.365360E+11 | -.665957E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.138314E+10 | 59.09 | 0.00 | 0.00 |
November | 0.401877E+11 | -.689260E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.134212E+10 | 59.03 | 0.00 | 0.00 |
December | 0.467714E+11 | -.760716E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.140141E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.500206E+12 | -.848400E+12 | 8760.00 | -.169589E+11 | 59.05 | |||||
Minimum of Months | 0.321307E+11 | -.807865E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.146210E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.519096E+11 | -.614094E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.134010E+10 | 59.19 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.769082E+10 | -.754276E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -148053832.1 | 81.21 | 0.00 | 0.00 |
February | 0.694879E+10 | -.681595E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -132839313.8 | 81.21 | 0.00 | 0.00 |
March | 0.768679E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -143999527.6 | 81.21 | 0.00 | 0.00 |
April | 0.744756E+10 | -.730857E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -138982123.0 | 81.21 | 0.00 | 0.00 |
May | 0.768723E+10 | -.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -144451544.2 | 81.21 | 0.00 | 0.00 |
June | 0.744090E+10 | -.730052E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -140383498.8 | 81.21 | 0.00 | 0.00 |
July | 0.769689E+10 | -.755083E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146062006.5 | 81.21 | 0.00 | 0.00 |
August | 0.768870E+10 | -.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145897095.8 | 81.21 | 0.00 | 0.00 |
September | 0.744817E+10 | -.730857E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -139596430.1 | 81.21 | 0.00 | 0.00 |
October | 0.768570E+10 | -.754276E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -142935709.8 | 81.21 | 0.00 | 0.00 |
November | 0.743223E+10 | -.729242E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -139815131.0 | 81.21 | 0.00 | 0.00 |
December | 0.769666E+10 | -.755083E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145827400.0 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.905504E+11 | -.888416E+11 | 8760.00 | -.170884E+10 | 81.21 | |||||
Minimum of Months | 0.694879E+10 | -.755083E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -148053832.1 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.769689E+10 | -.681595E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -132839313.8 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.793802E+11 | -.782687E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.111150E+10 | 61.10 | 0.00 | 0.00 |
February | 0.718546E+11 | -.708414E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.101324E+10 | 60.69 | 0.00 | 0.00 |
March | 0.794061E+11 | -.783021E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.110408E+10 | 60.82 | 0.00 | 0.00 |
April | 0.765435E+11 | -.754497E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.109379E+10 | 61.56 | 0.00 | 0.00 |
May | 0.787012E+11 | -.775396E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.116157E+10 | 62.59 | 0.00 | 0.00 |
June | 0.757887E+11 | -.746356E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.115308E+10 | 63.67 | 0.00 | 0.00 |
July | 0.779957E+11 | -.767795E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.121625E+10 | 64.51 | 0.00 | 0.00 |
August | 0.777515E+11 | -.765295E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.122199E+10 | 64.89 | 0.00 | 0.00 |
September | 0.751821E+11 | -.740231E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.115904E+10 | 64.70 | 0.00 | 0.00 |
October | 0.779755E+11 | -.768292E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.114629E+10 | 64.02 | 0.00 | 0.00 |
November | 0.759199E+11 | -.748350E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.108491E+10 | 63.03 | 0.00 | 0.00 |
December | 0.789343E+11 | -.778350E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.109931E+10 | 61.92 | 0.00 | 0.00 |
Annual Sum or Average | 0.925433E+12 | -.911868E+12 | 8760.00 | -.135650E+11 | 62.80 | |||||
Minimum of Months | 0.718546E+11 | -.783021E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.122199E+10 | 60.69 | 0.00 | 0.00 |
Maximum of Months | 0.794061E+11 | -.708414E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.101324E+10 | 64.89 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.86 | 0.86 | 01-JAN-09:39 | 6199.44 | 37.92 | 207.17 | 250.00 | 4164.46 | 37.39 | 209.00 | 217.67 |
February | 226.83 | 0.87 | 0.86 | 01-FEB-07:49 | 7515.48 | 37.72 | 221.50 | 257.33 | 1594.01 | 28.96 | 208.17 | 232.83 |
March | 334.33 | 0.87 | 0.86 | 01-MAR-07:00 | 4196.07 | 26.04 | 200.17 | 330.50 | 724.33 | 22.21 | 234.00 | 283.00 |
April | 285.17 | 0.87 | 0.86 | 01-APR-07:19 | 1552.95 | 20.75 | 113.83 | 350.50 | 633.74 | 22.48 | 222.50 | 279.67 |
May | 428.67 | 0.87 | 0.86 | 01-MAY-06:49 | 1277.65 | 19.85 | 70.83 | 399.50 | 500.56 | 21.57 | 278.50 | 330.33 |
June | 400.67 | 0.87 | 0.86 | 01-JUN-05:49 | 1301.26 | 20.23 | 118.17 | 400.67 | 521.72 | 21.97 | 281.67 | 333.50 |
July | 414.00 | 0.87 | 0.86 | 01-JUL-05:00 | 1338.13 | 20.57 | 131.33 | 411.33 | 540.37 | 22.31 | 308.83 | 343.17 |
August | 410.83 | 0.87 | 0.86 | 01-AUG-06:19 | 1500.56 | 20.31 | 128.50 | 382.33 | 589.10 | 22.03 | 303.50 | 328.83 |
September | 326.50 | 0.87 | 0.86 | 01-SEP-06:30 | 2540.85 | 22.98 | 176.67 | 336.33 | 699.79 | 22.63 | 247.33 | 290.33 |
October | 325.17 | 0.87 | 0.86 | 01-OCT-06:00 | 6520.87 | 33.68 | 296.00 | 309.33 | 887.24 | 23.62 | 239.67 | 278.33 |
November | 254.83 | 0.87 | 0.86 | 01-NOV-07:40 | 4433.30 | 33.20 | 238.83 | 251.50 | 2131.46 | 30.64 | 224.00 | 220.33 |
December | 186.17 | 0.87 | 0.86 | 01-DEC-07:00 | 5373.44 | 38.02 | 180.33 | 225.67 | 4772.67 | 39.00 | 180.83 | 173.67 |
Annual Sum or Average | 3807.33 | 0.87 | 3203.77 | 25.94 | 2083.33 | 3905.00 | 1185.70 | 24.92 | 2938.00 | 3311.67 | ||
Minimum of Months | 186.17 | 0.86 | 0.86 | 1277.65 | 19.85 | 70.83 | 225.67 | 500.56 | 21.57 | 180.83 | 173.67 | |
Maximum of Months | 428.67 | 0.87 | 0.86 | 7515.48 | 38.02 | 296.00 | 411.33 | 4772.67 | 39.00 | 308.83 | 343.17 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.24 | 0.22 | 01-JAN-09:39 | 6704.91 | 38.00 | 207.17 | 258.83 | 4668.98 | 37.37 | 203.67 | 236.83 |
February | 226.83 | 0.24 | 0.22 | 01-FEB-07:49 | 8013.23 | 37.79 | 221.83 | 265.00 | 2087.56 | 28.69 | 200.33 | 248.00 |
March | 334.33 | 0.24 | 0.22 | 01-MAR-07:40 | 4558.57 | 26.27 | 202.00 | 341.17 | 1083.50 | 22.34 | 234.67 | 312.00 |
April | 285.17 | 0.25 | 0.22 | 01-APR-06:00 | 1902.46 | 20.97 | 114.83 | 360.67 | 982.13 | 22.56 | 226.83 | 329.67 |
May | 428.67 | 0.25 | 0.22 | 01-MAY-05:00 | 1508.52 | 20.41 | 125.83 | 414.50 | 730.55 | 21.95 | 298.83 | 375.50 |
June | 400.67 | 0.25 | 0.22 | 01-JUN-05:19 | 1531.07 | 20.78 | 171.50 | 414.83 | 750.64 | 22.33 | 306.67 | 378.83 |
July | 414.00 | 0.24 | 0.22 | 01-JUL-05:40 | 1583.94 | 21.07 | 185.50 | 424.33 | 785.25 | 22.62 | 330.33 | 389.33 |
August | 410.83 | 0.25 | 0.22 | 01-AUG-05:00 | 1771.83 | 20.75 | 169.67 | 394.50 | 859.28 | 22.30 | 320.00 | 363.83 |
September | 326.50 | 0.24 | 0.22 | 01-SEP-06:10 | 2907.48 | 23.16 | 172.67 | 345.67 | 1064.99 | 22.70 | 262.17 | 318.50 |
October | 325.17 | 0.24 | 0.22 | 01-OCT-06:49 | 6916.48 | 33.83 | 297.50 | 316.17 | 1282.91 | 23.65 | 234.00 | 296.83 |
November | 254.83 | 0.24 | 0.22 | 01-NOV-07:40 | 4774.94 | 33.31 | 240.17 | 260.83 | 2473.23 | 30.69 | 227.00 | 239.67 |
December | 186.17 | 0.24 | 0.22 | 01-DEC-07:00 | 5844.42 | 38.11 | 180.50 | 236.50 | 5239.78 | 39.07 | 180.83 | 206.83 |
Annual Sum or Average | 3807.33 | 0.24 | 3537.16 | 26.25 | 2289.17 | 4033.00 | 1517.71 | 25.08 | 3025.33 | 3695.83 | ||
Minimum of Months | 186.17 | 0.24 | 0.22 | 1508.52 | 20.41 | 114.83 | 236.50 | 730.55 | 21.95 | 180.83 | 206.83 | |
Maximum of Months | 428.67 | 0.25 | 0.22 | 8013.23 | 38.11 | 297.50 | 424.33 | 5239.78 | 39.07 | 330.33 | 389.33 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.60 | 01-JAN-09:00 | 445.73 | 15.45 | 0.00 | 230.00 | 217.39 | 18.95 | 0.50 | 124.67 |
February | 226.83 | 0.64 | 0.60 | 01-FEB-09:09 | 457.54 | 15.69 | 0.00 | 241.83 | 225.14 | 19.13 | 0.00 | 149.33 |
March | 334.33 | 0.62 | 0.60 | 01-MAR-08:09 | 642.86 | 16.97 | 0.00 | 330.33 | 288.11 | 20.18 | 14.00 | 262.83 |
April | 285.17 | 0.61 | 0.60 | 01-APR-07:10 | 730.56 | 18.13 | 0.00 | 360.17 | 347.78 | 21.34 | 126.33 | 295.50 |
May | 428.67 | 0.61 | 0.60 | 01-MAY-05:00 | 862.77 | 18.21 | 4.17 | 421.33 | 377.01 | 22.22 | 204.33 | 383.50 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1047.12 | 21.21 | 67.00 | 423.00 | 485.44 | 24.28 | 291.83 | 395.50 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 978.66 | 20.76 | 54.00 | 431.17 | 453.32 | 23.43 | 287.83 | 402.83 |
August | 410.83 | 0.62 | 0.60 | 01-AUG-05:49 | 804.85 | 18.29 | 4.50 | 396.83 | 365.66 | 21.67 | 203.17 | 367.67 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:10 | 645.86 | 17.66 | 0.00 | 339.33 | 310.39 | 20.86 | 63.50 | 287.00 |
October | 325.17 | 0.63 | 0.60 | 01-OCT-07:19 | 523.56 | 16.16 | 0.00 | 297.00 | 241.73 | 19.48 | 0.00 | 214.67 |
November | 254.83 | 0.64 | 0.60 | 01-NOV-08:20 | 458.70 | 15.24 | 0.00 | 237.83 | 203.09 | 18.55 | 0.00 | 130.33 |
December | 186.17 | 0.67 | 0.60 | 02-DEC-09:09 | 316.10 | 14.02 | 0.00 | 198.33 | 160.32 | 17.65 | 0.00 | 40.50 |
Annual Sum or Average | 3807.33 | 0.62 | 710.36 | 17.76 | 129.67 | 3907.17 | 327.97 | 21.08 | 1191.50 | 3054.33 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 316.10 | 14.02 | 0.00 | 198.33 | 160.32 | 17.65 | 0.00 | 40.50 | |
Maximum of Months | 428.67 | 0.67 | 0.60 | 1047.12 | 21.21 | 67.00 | 431.17 | 485.44 | 24.28 | 291.83 | 402.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.64 | 0.60 | 01-JAN-09:00 | 445.73 | 15.45 | 0.00 | 230.00 | 217.39 | 18.95 | 0.50 | 124.67 |
February | 226.83 | 0.64 | 0.60 | 01-FEB-09:09 | 457.54 | 15.69 | 0.00 | 241.83 | 225.14 | 19.13 | 0.00 | 149.33 |
March | 334.33 | 0.62 | 0.60 | 01-MAR-08:09 | 642.86 | 16.97 | 0.00 | 330.33 | 288.11 | 20.18 | 14.00 | 262.83 |
April | 285.17 | 0.61 | 0.60 | 01-APR-07:10 | 730.56 | 18.13 | 0.00 | 360.17 | 347.78 | 21.34 | 126.33 | 295.50 |
May | 428.67 | 0.61 | 0.60 | 01-MAY-05:00 | 862.77 | 18.21 | 4.17 | 421.33 | 377.01 | 22.22 | 204.33 | 383.50 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1047.12 | 21.21 | 67.00 | 423.00 | 485.44 | 24.28 | 291.83 | 395.50 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 978.66 | 20.76 | 54.00 | 431.17 | 453.32 | 23.43 | 287.83 | 402.83 |
August | 410.83 | 0.62 | 0.60 | 01-AUG-05:49 | 804.85 | 18.29 | 4.50 | 396.83 | 365.66 | 21.67 | 203.17 | 367.67 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:10 | 645.86 | 17.66 | 0.00 | 339.33 | 310.39 | 20.86 | 63.50 | 287.00 |
October | 325.17 | 0.63 | 0.60 | 01-OCT-07:19 | 523.56 | 16.16 | 0.00 | 297.00 | 241.73 | 19.48 | 0.00 | 214.67 |
November | 254.83 | 0.64 | 0.60 | 01-NOV-08:20 | 458.70 | 15.24 | 0.00 | 237.83 | 203.09 | 18.55 | 0.00 | 130.33 |
December | 186.17 | 0.67 | 0.60 | 02-DEC-09:09 | 316.10 | 14.02 | 0.00 | 198.33 | 160.32 | 17.65 | 0.00 | 40.50 |
Annual Sum or Average | 3807.33 | 0.62 | 710.36 | 17.76 | 129.67 | 3907.17 | 327.97 | 21.08 | 1191.50 | 3054.33 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 316.10 | 14.02 | 0.00 | 198.33 | 160.32 | 17.65 | 0.00 | 40.50 | |
Maximum of Months | 428.67 | 0.67 | 0.60 | 1047.12 | 21.21 | 67.00 | 431.17 | 485.44 | 24.28 | 291.83 | 402.83 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 23506442.39 | 7313.86 | 31-JAN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104776E+10 | 7765.50 | 02-FEB-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107126E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104776E+10 | 7765.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.272637E+10 | 4240.48 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158297E+10 | 4477.06 | 02-FEB-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.625065E+09 | 2874.17 | 06-MAR-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180625E+09 | 2218.70 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 898778.99 | 423.14 | 30-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6345502.48 | 560.57 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.839860E+09 | 4155.81 | 26-NOV-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186358E+10 | 2873.59 | 11-DEC-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.782571E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.272637E+10 | 4477.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.270957E+09 | 1697.71 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329983E+09 | 1790.94 | 02-FEB-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32456966.82 | 1664.27 | 26-NOV-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8541083.50 | 644.49 | 12-DEC-14:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.641938E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.329983E+09 | 1790.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.445763E+09 | 2542.51 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.585581E+09 | 2687.73 | 02-FEB-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 661641.62 | 216.63 | 26-NOV-17:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36268024.83 | 1001.00 | 12-DEC-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106827E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.585581E+09 | 2687.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112240E+10 | 1776.17 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530680E+09 | 1875.31 | 02-FEB-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71811303.93 | 847.13 | 06-MAR-04:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209766E+09 | 1740.69 | 26-NOV-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.463770E+09 | 1203.06 | 11-DEC-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239842E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112240E+10 | 1875.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.346696E+10 | 15066.22 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.266679E+10 | 15897.40 | 02-FEB-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136575E+09 | 4735.46 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27229713.50 | 3552.62 | 03-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.626758E+09 | 14768.25 | 26-NOV-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129602E+10 | 10207.85 | 09-DEC-16:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.822034E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.346696E+10 | 15897.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.460879E+10 | 34623.53 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.576151E+10 | 36524.42 | 02-FEB-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.569843E+09 | 33941.68 | 26-NOV-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11807387.14 | 4241.07 | 12-DEC-14:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109519E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.576151E+10 | 36524.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.940404E+10 | 7993.08 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.653321E+10 | 8028.71 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.362895E+10 | 7992.15 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160578E+10 | 7990.86 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214718E+09 | 7717.88 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86379067.25 | 6263.24 | 04-JUN-15:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6078490.05 | 4904.86 | 19-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6238069.43 | 5373.32 | 25-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.375667E+09 | 7807.83 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141569E+10 | 7886.42 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.441146E+10 | 7992.28 | 30-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.774062E+10 | 7993.48 | 14-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.354288E+11 | |||||||
Minimum of Months | 6078490.05 | 4904.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.940404E+10 | 8028.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107040E+11 | 7958.94 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.757900E+10 | 8088.63 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.418566E+10 | 7958.50 | 10-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177839E+10 | 7956.70 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.224587E+09 | 7704.70 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87073286.69 | 6309.64 | 01-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3583554.26 | 4644.70 | 22-JUL-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5503562.58 | 5150.74 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.441516E+09 | 7800.26 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189140E+10 | 7895.09 | 27-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.512399E+10 | 7958.14 | 30-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.878585E+10 | 7959.35 | 14-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.408106E+11 | |||||||
Minimum of Months | 3583554.26 | 4644.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107040E+11 | 8088.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.949335E+10 | 24951.44 | 19-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237657E+10 | 20886.87 | 04-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.438451E+09 | 9245.69 | 05-MAR-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.579158E+09 | 16132.44 | 28-NOV-04:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.586468E+10 | 18817.57 | 12-DEC-04:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187522E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.949335E+10 | 24951.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.450215E+11 | 43207.09 | 21-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317786E+11 | 44227.35 | 03-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130147E+11 | 42915.17 | 05-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388463E+10 | 42056.42 | 03-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83853665.95 | 25360.62 | 20-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11255194.10 | 28026.75 | 05-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6197691.10 | 20037.37 | 13-JUL-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11585215.81 | 21173.39 | 16-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272843E+09 | 36265.83 | 30-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.247600E+10 | 35722.74 | 28-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167105E+11 | 43204.18 | 27-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331745E+11 | 43209.68 | 23-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146446E+12 | |||||||
Minimum of Months | 6197691.10 | 20037.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.450215E+11 | 44227.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.937374E+10 | 7639.01 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.657833E+10 | 7778.47 | 03-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357584E+10 | 7638.04 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173711E+10 | 7636.72 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178479E+09 | 6105.33 | 20-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 71278577.45 | 4737.42 | 02-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3305261.92 | 4042.88 | 09-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5970283.66 | 4341.68 | 30-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.347179E+09 | 7360.73 | 27-SEP-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142491E+10 | 7500.99 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444147E+10 | 7638.19 | 30-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.776647E+10 | 7639.42 | 14-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.355041E+11 | |||||||
Minimum of Months | 3305261.92 | 4042.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.937374E+10 | 7778.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106661E+11 | 7636.20 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.765747E+10 | 7867.45 | 03-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413594E+10 | 7635.23 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195200E+10 | 7633.90 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195529E+09 | 5817.09 | 20-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 71542923.96 | 5512.96 | 03-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1513544.88 | 3966.75 | 10-JUL-21:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4610215.87 | 4146.49 | 30-AUG-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.407619E+09 | 7374.36 | 27-SEP-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190865E+10 | 7531.64 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.516806E+10 | 7636.08 | 20-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.882416E+10 | 7636.61 | 14-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.409932E+11 | |||||||
Minimum of Months | 1513544.88 | 3966.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106661E+11 | 7867.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131351E+11 | 13993.47 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113008E+11 | 14772.97 | 02-FEB-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.813483E+10 | 9484.15 | 05-MAR-15:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.416166E+10 | 9487.18 | 02-APR-14:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.318849E+09 | 5652.28 | 02-MAY-03:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82353557.09 | 5187.00 | 06-JUN-13:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.632035E+09 | 7972.47 | 30-SEP-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.333913E+10 | 8587.16 | 27-OCT-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.847738E+10 | 13714.36 | 26-NOV-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122797E+11 | 9482.56 | 11-DEC-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.618618E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131351E+11 | 14772.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.292013E+10 | 2310.81 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199100E+10 | 2314.24 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124110E+10 | 2310.96 | 14-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.573086E+09 | 2310.80 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85888755.26 | 2253.25 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35571615.58 | 1510.33 | 03-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1380629.93 | 1055.33 | 19-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2522563.52 | 1356.76 | 09-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153589E+09 | 2287.78 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.535472E+09 | 2310.80 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148364E+10 | 2311.75 | 15-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246201E+10 | 2310.95 | 14-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114854E+11 | |||||||
Minimum of Months | 1380629.93 | 1055.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.292013E+10 | 2314.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.329421E+10 | 2302.27 | 16-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230381E+10 | 2337.99 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142381E+10 | 2302.42 | 14-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.628109E+09 | 2302.26 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86120453.47 | 2251.10 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35433526.98 | 1535.75 | 03-JUN-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 721019.62 | 1134.27 | 18-JUL-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1337387.14 | 1188.68 | 25-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.174221E+09 | 2286.67 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.692661E+09 | 2302.55 | 16-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170547E+10 | 2303.22 | 15-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.277237E+10 | 2302.41 | 14-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131183E+11 | |||||||
Minimum of Months | 721019.62 | 1134.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.329421E+10 | 2337.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.998858E+10 | 10030.58 | 17-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.633875E+10 | 10027.60 | 22-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.389540E+10 | 10031.04 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202503E+10 | 10028.90 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192033E+09 | 6404.45 | 01-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65213271.33 | 5579.75 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4378096.69 | 4637.65 | 24-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9605450.82 | 3940.30 | 16-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.306742E+09 | 9674.41 | 29-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103137E+10 | 9758.19 | 26-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.450425E+10 | 10028.44 | 30-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.830577E+10 | 10029.57 | 24-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366671E+11 | |||||||
Minimum of Months | 4378096.69 | 3940.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.998858E+10 | 10031.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.216697E+10 | 15464.19 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242568E+10 | 16305.49 | 02-FEB-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.302914E+09 | 15162.15 | 26-NOV-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489557E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.242568E+10 | 16305.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203861E+10 | 15594.83 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237964E+10 | 16443.41 | 02-FEB-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.281607E+09 | 15290.18 | 26-NOV-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469986E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237964E+10 | 16443.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 13864285.26 | 5861.89 | 31-JAN-03:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115594E+09 | 6189.41 | 02-FEB-05:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129459E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115594E+09 | 6189.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.552673E+10 | 7685.81 | 31-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.300701E+10 | 8112.95 | 02-FEB-07:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.831799E+09 | 5214.80 | 06-MAR-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34102542.14 | 1805.19 | 03-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138288E+10 | 7532.87 | 26-NOV-06:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351970E+10 | 5213.71 | 11-DEC-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143022E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.552673E+10 | 8112.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131523E+12 | 309454.52 | 30-JAN-20:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.784314E+11 | 317786.88 | 02-FEB-20:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164138E+11 | 125723.01 | 05-MAR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251039E+10 | 69202.59 | 23-APR-22:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13296268.09 | 58612.08 | 20-MAY-19:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 55170409.47 | 66516.81 | 01-JUN-14:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 47092054.15 | 47329.00 | 19-JUL-03:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 983833.18 | 2075.14 | 17-AUG-21:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9079048.92 | 51272.13 | 19-SEP-18:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27860967.99 | 58317.02 | 19-OCT-18:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285125E+11 | 311093.29 | 25-NOV-21:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.604160E+11 | 185642.59 | 09-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317960E+12 | |||||||
Minimum of Months | 983833.18 | 2075.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131523E+12 | 317786.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157070E+11 | 31339.03 | 31-JAN-03:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106288E+11 | 32737.04 | 02-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232243E+10 | 7153.11 | 05-MAR-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.428509E+09 | 3217.10 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23950.69 | 0.29 | 29-MAY-08:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34310.59 | 0.29 | 30-JUN-12:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37644.35 | 0.29 | 25-JUL-16:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39665.97 | 0.29 | 01-AUG-05:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 310540.08 | 189.79 | 30-SEP-00:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21183851.61 | 1121.91 | 23-OCT-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373761E+10 | 30768.44 | 26-NOV-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.670847E+10 | 10986.20 | 09-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395544E+11 | |||||||
Minimum of Months | 23950.69 | 0.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157070E+11 | 32737.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1638343.16 | 1617178.56 | 14734.05 | 12-JAN-16:11 | 14734.05 | 0.00 |
February | 0.00 | 0.00 | 63059537.73 | 50387181.59 | 15767.15 | 20-FEB-16:11 | 15767.15 | 0.01 |
March | 0.00 | 0.00 | 0.232244E+09 | 0.166851E+09 | 15769.37 | 24-MAR-15:11 | 15769.37 | 0.04 |
April | 0.00 | 0.00 | 0.169184E+10 | 0.104162E+10 | 16050.87 | 16-APR-08:61 | 12178.52 | 0.24 |
May | 0.00 | 0.00 | 0.302119E+10 | 0.149991E+10 | 17088.15 | 29-MAY-08:61 | 11644.02 | 0.56 |
June | 0.00 | 0.00 | 0.627202E+10 | 0.313666E+10 | 18063.19 | 25-JUN-08:61 | 10868.95 | 0.78 |
July | 0.00 | 0.00 | 0.835394E+10 | 0.412434E+10 | 18266.84 | 20-JUL-08:61 | 10330.59 | 0.91 |
August | 0.00 | 0.00 | 0.733751E+10 | 0.337886E+10 | 19564.32 | 03-AUG-08:61 | 9601.73 | 0.91 |
September | 0.00 | 0.00 | 0.415151E+10 | 0.216238E+10 | 16962.11 | 10-SEP-08:61 | 11729.20 | 0.62 |
October | 0.00 | 0.00 | 0.750290E+09 | 0.489577E+09 | 15767.45 | 17-OCT-15:11 | 15767.45 | 0.15 |
November | 0.00 | 0.00 | 0.134649E+09 | 96147163.05 | 15764.21 | 04-NOV-15:11 | 15764.21 | 0.02 |
December | 0.00 | 0.00 | 2441598.60 | 2268353.96 | 10054.53 | 01-DEC-16:11 | 10054.53 | 0.00 |
Annual Sum or Average | 0.320123E+11 | 0.161506E+11 | 0.36 | |||||
Minimum of Months | 0.00 | 0.00 | 1638343.16 | 1617178.56 | 10054.53 | 9601.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.835394E+10 | 0.412434E+10 | 19564.32 | 15769.37 | 0.91 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 49364.99 | 46908.81 | 311.62 | 12-JAN-16:13 | 311.62 | 0.00 |
February | 0.00 | 0.00 | 15356554.17 | 10187994.56 | 14271.18 | 20-FEB-16:11 | 14271.18 | 0.00 |
March | 0.00 | 0.00 | 75846075.64 | 56140462.55 | 15114.20 | 24-MAR-15:11 | 15114.20 | 0.02 |
April | 0.00 | 0.00 | 0.107130E+10 | 0.635776E+09 | 16416.03 | 16-APR-21:11 | 12544.81 | 0.17 |
May | 0.00 | 0.00 | 0.189464E+10 | 0.775316E+09 | 17683.96 | 21-MAY-19:01 | 17683.96 | 0.45 |
June | 0.00 | 0.00 | 0.474336E+10 | 0.231722E+10 | 20084.34 | 26-JUN-08:11 | 10461.90 | 0.60 |
July | 0.00 | 0.00 | 0.570887E+10 | 0.266712E+10 | 19200.78 | 02-JUL-08:11 | 11417.12 | 0.65 |
August | 0.00 | 0.00 | 0.473952E+10 | 0.195037E+10 | 21887.76 | 03-AUG-08:11 | 8797.78 | 0.65 |
September | 0.00 | 0.00 | 0.253073E+10 | 0.114937E+10 | 17157.89 | 11-SEP-08:11 | 11465.59 | 0.45 |
October | 0.00 | 0.00 | 0.234651E+09 | 0.149199E+09 | 15213.50 | 24-OCT-15:11 | 15213.50 | 0.05 |
November | 0.00 | 0.00 | 45486028.06 | 30610531.32 | 15501.47 | 04-NOV-15:11 | 15501.47 | 0.00 |
December | 0.00 | 0.00 | 366362.39 | 360459.79 | 2870.35 | 01-DEC-16:13 | 2870.35 | 0.00 |
Annual Sum or Average | 0.210602E+11 | 0.974171E+10 | 0.26 | |||||
Minimum of Months | 0.00 | 0.00 | 49364.99 | 46908.81 | 311.62 | 311.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.570887E+10 | 0.266712E+10 | 21887.76 | 17683.96 | 0.65 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.735007E+09 | 0.190964E+09 | 17826.01 | 24-MAR-13:11 | 6981.67 | 0.05 |
April | 0.00 | 0.00 | 0.688193E+10 | 0.312433E+10 | 39568.40 | 15-APR-12:31 | 29937.23 | 0.19 |
May | 0.00 | 0.00 | 0.164566E+11 | 0.468415E+10 | 28688.29 | 28-MAY-15:03 | 13749.34 | 0.65 |
June | 0.00 | 0.00 | 0.290662E+11 | 0.105650E+11 | 30532.44 | 26-JUN-17:11 | 18559.21 | 0.84 |
July | 0.00 | 0.00 | 0.372088E+11 | 0.135516E+11 | 30606.01 | 26-JUL-16:01 | 15401.95 | 0.96 |
August | 0.00 | 0.00 | 0.384138E+11 | 0.150845E+11 | 36728.83 | 22-AUG-12:51 | 24597.89 | 0.96 |
September | 0.00 | 0.00 | 0.299787E+11 | 0.147091E+11 | 45388.36 | 09-SEP-13:52 | 36159.78 | 0.73 |
October | 0.00 | 0.00 | 0.138655E+11 | 0.712320E+10 | 48742.02 | 20-OCT-12:50 | 37837.07 | 0.41 |
November | 0.00 | 0.00 | 0.410036E+10 | 0.206748E+10 | 46751.06 | 04-NOV-12:21 | 37037.37 | 0.14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.176707E+12 | 0.711002E+11 | 0.41 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.384138E+11 | 0.150845E+11 | 48742.02 | 37837.07 | 0.96 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9268276.39 | 6027862.87 | 40177.31 | 01-JAN-09:01 | 36694.41 | 0.00 |
February | 0.00 | 0.00 | 53177019.44 | 28959598.09 | 56777.08 | 20-FEB-09:01 | 56777.08 | 0.01 |
March | 0.00 | 0.00 | 0.218698E+10 | 0.784663E+09 | 73069.09 | 26-MAR-08:61 | 63954.28 | 0.15 |
April | 0.00 | 0.00 | 0.967482E+10 | 0.504483E+10 | 84218.78 | 16-APR-21:11 | 62597.96 | 0.31 |
May | 0.00 | 0.00 | 0.265193E+11 | 0.139010E+11 | 85934.29 | 29-MAY-08:11 | 62056.98 | 0.57 |
June | 0.00 | 0.00 | 0.411880E+11 | 0.241077E+11 | 102929.13 | 26-JUN-08:11 | 51868.19 | 0.62 |
July | 0.00 | 0.00 | 0.445456E+11 | 0.258734E+11 | 97099.45 | 20-JUL-08:11 | 50836.53 | 0.57 |
August | 0.00 | 0.00 | 0.402854E+11 | 0.223665E+11 | 111898.85 | 03-AUG-08:11 | 44435.41 | 0.56 |
September | 0.00 | 0.00 | 0.249088E+11 | 0.132771E+11 | 87694.53 | 11-SEP-21:11 | 61095.74 | 0.56 |
October | 0.00 | 0.00 | 0.635381E+10 | 0.243603E+10 | 74831.59 | 02-OCT-18:01 | 64098.26 | 0.37 |
November | 0.00 | 0.00 | 0.288404E+10 | 0.954021E+09 | 75116.40 | 08-NOV-19:01 | 61432.37 | 0.16 |
December | 0.00 | 0.00 | 20462086.68 | 15824239.70 | 50766.25 | 03-DEC-09:01 | 50766.25 | 0.00 |
Annual Sum or Average | 0.198630E+12 | 0.108796E+12 | 0.32 | |||||
Minimum of Months | 0.00 | 0.00 | 9268276.39 | 6027862.87 | 40177.31 | 36694.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.445456E+11 | 0.258734E+11 | 111898.85 | 64098.26 | 0.62 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 698886.22 | 440670.27 | 2933.84 | 12-JAN-09:03 | 1834.90 | 0.00 |
February | 0.00 | 0.00 | 35427676.67 | 20284809.61 | 12207.82 | 21-FEB-09:01 | 12207.82 | 0.01 |
March | 0.00 | 0.00 | 0.189384E+09 | 0.113163E+09 | 14024.96 | 24-MAR-15:11 | 14024.96 | 0.06 |
April | 0.00 | 0.00 | 0.139926E+10 | 0.755577E+09 | 14045.30 | 30-APR-18:01 | 14045.30 | 0.25 |
May | 0.00 | 0.00 | 0.323736E+10 | 0.153071E+10 | 14787.83 | 12-MAY-08:61 | 9687.74 | 0.64 |
June | 0.00 | 0.00 | 0.634077E+10 | 0.316836E+10 | 16053.88 | 14-JUN-18:01 | 9330.33 | 0.83 |
July | 0.00 | 0.00 | 0.807632E+10 | 0.386030E+10 | 16314.78 | 20-JUL-08:61 | 9187.47 | 0.95 |
August | 0.00 | 0.00 | 0.700163E+10 | 0.313751E+10 | 16936.52 | 31-AUG-18:01 | 9030.01 | 0.94 |
September | 0.00 | 0.00 | 0.413254E+10 | 0.210694E+10 | 15053.64 | 10-SEP-08:61 | 10558.36 | 0.65 |
October | 0.00 | 0.00 | 0.580532E+09 | 0.307705E+09 | 13899.00 | 31-OCT-15:11 | 13899.00 | 0.17 |
November | 0.00 | 0.00 | 90434275.74 | 57671586.07 | 14043.61 | 04-NOV-15:11 | 14043.61 | 0.03 |
December | 0.00 | 0.00 | 5405146.77 | 2025666.40 | 8892.61 | 03-DEC-09:01 | 8892.61 | 0.00 |
Annual Sum or Average | 0.310898E+11 | 0.150607E+11 | 0.38 | |||||
Minimum of Months | 0.00 | 0.00 | 698886.22 | 440670.27 | 2933.84 | 1834.90 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.807632E+10 | 0.386030E+10 | 16936.52 | 14045.30 | 0.95 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 203754.09 | 103346.51 | 1603.83 | 12-JAN-09:04 | 618.07 | 0.00 |
February | 0.00 | 0.00 | 6543685.33 | 2872393.89 | 9399.68 | 24-FEB-09:01 | 9399.68 | 0.00 |
March | 0.00 | 0.00 | 73740257.11 | 39334795.34 | 12782.55 | 22-MAR-08:61 | 12782.55 | 0.02 |
April | 0.00 | 0.00 | 0.881150E+09 | 0.467152E+09 | 16101.72 | 18-APR-08:11 | 12920.30 | 0.17 |
May | 0.00 | 0.00 | 0.234539E+10 | 0.108535E+10 | 17285.54 | 31-MAY-08:11 | 13694.70 | 0.50 |
June | 0.00 | 0.00 | 0.495029E+10 | 0.250820E+10 | 19130.10 | 26-JUN-08:11 | 12715.25 | 0.64 |
July | 0.00 | 0.00 | 0.578109E+10 | 0.280688E+10 | 18805.19 | 02-JUL-08:11 | 13389.01 | 0.67 |
August | 0.00 | 0.00 | 0.477348E+10 | 0.209973E+10 | 20788.58 | 03-AUG-08:11 | 10034.03 | 0.67 |
September | 0.00 | 0.00 | 0.267303E+10 | 0.127711E+10 | 16668.49 | 11-SEP-08:11 | 12371.68 | 0.49 |
October | 0.00 | 0.00 | 0.142620E+09 | 58875571.98 | 12774.06 | 02-OCT-18:01 | 10439.22 | 0.06 |
November | 0.00 | 0.00 | 13632490.83 | 5637080.19 | 9585.56 | 04-NOV-08:61 | 9585.56 | 0.00 |
December | 0.00 | 0.00 | 619266.70 | 401463.51 | 3039.89 | 03-DEC-09:02 | 1957.63 | 0.00 |
Annual Sum or Average | 0.216418E+11 | 0.103516E+11 | 0.27 | |||||
Minimum of Months | 0.00 | 0.00 | 203754.09 | 103346.51 | 1603.83 | 618.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.578109E+10 | 0.280688E+10 | 20788.58 | 13694.70 | 0.67 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 511575.32 | 483786.80 | 3849.16 | 12-JAN-16:11 | 3849.16 | 0.00 |
February | 0.00 | 0.00 | 18234369.88 | 14771474.60 | 4113.79 | 20-FEB-16:11 | 4113.79 | 0.01 |
March | 0.00 | 0.00 | 56276928.08 | 41379244.29 | 4114.39 | 24-MAR-15:11 | 4114.39 | 0.04 |
April | 0.00 | 0.00 | 0.479564E+09 | 0.308481E+09 | 4229.30 | 29-APR-18:01 | 4229.30 | 0.22 |
May | 0.00 | 0.00 | 0.883181E+09 | 0.472442E+09 | 4462.92 | 29-MAY-08:61 | 3029.60 | 0.56 |
June | 0.00 | 0.00 | 0.176241E+10 | 0.940538E+09 | 4759.82 | 26-JUN-08:61 | 2794.04 | 0.79 |
July | 0.00 | 0.00 | 0.228730E+10 | 0.119525E+10 | 4829.33 | 20-JUL-08:61 | 2597.93 | 0.92 |
August | 0.00 | 0.00 | 0.197651E+10 | 0.974782E+09 | 5155.84 | 03-AUG-08:61 | 2455.04 | 0.91 |
September | 0.00 | 0.00 | 0.110304E+10 | 0.625150E+09 | 4434.12 | 11-SEP-08:61 | 3010.37 | 0.57 |
October | 0.00 | 0.00 | 0.197949E+09 | 0.135631E+09 | 4113.88 | 17-OCT-15:11 | 4113.88 | 0.12 |
November | 0.00 | 0.00 | 36236154.89 | 27156740.05 | 4113.02 | 04-NOV-15:11 | 4113.02 | 0.02 |
December | 0.00 | 0.00 | 537311.49 | 485347.21 | 3027.07 | 01-DEC-16:11 | 3027.07 | 0.00 |
Annual Sum or Average | 0.880175E+10 | 0.473655E+10 | 0.35 | |||||
Minimum of Months | 0.00 | 0.00 | 511575.32 | 483786.80 | 3027.07 | 2455.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.228730E+10 | 0.119525E+10 | 5155.84 | 4229.30 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 77542.86 | 77542.86 | 877.05 | 12-JAN-16:13 | 877.05 | 0.00 |
February | 0.00 | 0.00 | 3001372.28 | 1801807.84 | 2555.97 | 24-FEB-16:11 | 2555.97 | 0.00 |
March | 0.00 | 0.00 | 14747254.64 | 10730320.43 | 3897.56 | 24-MAR-15:11 | 3897.56 | 0.02 |
April | 0.00 | 0.00 | 0.309769E+09 | 0.194974E+09 | 4342.35 | 16-APR-21:11 | 3378.90 | 0.17 |
May | 0.00 | 0.00 | 0.591568E+09 | 0.273071E+09 | 4967.86 | 20-MAY-18:01 | 4967.86 | 0.46 |
June | 0.00 | 0.00 | 0.139925E+10 | 0.734054E+09 | 5313.24 | 26-JUN-08:11 | 2739.80 | 0.62 |
July | 0.00 | 0.00 | 0.166229E+10 | 0.834226E+09 | 5050.29 | 07-JUL-08:11 | 2866.16 | 0.66 |
August | 0.00 | 0.00 | 0.135224E+10 | 0.603508E+09 | 5745.61 | 03-AUG-08:11 | 2324.94 | 0.67 |
September | 0.00 | 0.00 | 0.692742E+09 | 0.342585E+09 | 4518.80 | 11-SEP-21:11 | 3168.62 | 0.43 |
October | 0.00 | 0.00 | 56051454.60 | 35352516.82 | 3910.42 | 19-OCT-16:31 | 3910.42 | 0.05 |
November | 0.00 | 0.00 | 11207969.67 | 7441190.38 | 4003.92 | 04-NOV-15:11 | 4003.92 | 0.00 |
December | 0.00 | 0.00 | 54829.17 | 54829.17 | 635.22 | 02-DEC-16:13 | 635.22 | 0.00 |
Annual Sum or Average | 0.609300E+10 | 0.303788E+10 | 0.26 | |||||
Minimum of Months | 0.00 | 0.00 | 54829.17 | 54829.17 | 635.22 | 635.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.166229E+10 | 0.834226E+09 | 5745.61 | 4967.86 | 0.67 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.334970E+09 | 0.267586E+09 | 15624.55 | 02-JAN-16:11 | 15624.55 | 0.02 |
February | 0.00 | 0.00 | 0.629001E+09 | 0.418719E+09 | 15624.75 | 17-FEB-16:11 | 15624.75 | 0.09 |
March | 0.00 | 0.00 | 0.105511E+10 | 0.633105E+09 | 16425.16 | 26-MAR-08:61 | 10605.73 | 0.17 |
April | 0.00 | 0.00 | 0.267705E+10 | 0.152234E+10 | 16341.01 | 16-APR-08:61 | 11762.64 | 0.34 |
May | 0.00 | 0.00 | 0.466928E+10 | 0.207369E+10 | 17368.59 | 29-MAY-08:61 | 11457.38 | 0.67 |
June | 0.00 | 0.00 | 0.817153E+10 | 0.402009E+10 | 19152.51 | 26-JUN-08:61 | 10074.65 | 0.82 |
July | 0.00 | 0.00 | 0.104767E+11 | 0.503631E+10 | 19277.79 | 20-JUL-08:61 | 9276.63 | 0.91 |
August | 0.00 | 0.00 | 0.102996E+11 | 0.504818E+10 | 20350.69 | 03-AUG-08:61 | 9066.28 | 0.91 |
September | 0.00 | 0.00 | 0.724679E+10 | 0.432375E+10 | 17443.28 | 11-SEP-08:61 | 11325.29 | 0.72 |
October | 0.00 | 0.00 | 0.345371E+10 | 0.224486E+10 | 16383.93 | 10-OCT-08:61 | 9932.55 | 0.45 |
November | 0.00 | 0.00 | 0.114800E+10 | 0.756210E+09 | 16468.87 | 08-NOV-09:01 | 9822.50 | 0.17 |
December | 0.00 | 0.00 | 0.750990E+09 | 0.621457E+09 | 15622.68 | 05-DEC-16:11 | 15622.68 | 0.05 |
Annual Sum or Average | 0.509127E+11 | 0.269663E+11 | 0.44 | |||||
Minimum of Months | 0.00 | 0.00 | 0.334970E+09 | 0.267586E+09 | 15622.68 | 9066.28 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.104767E+11 | 0.504818E+10 | 20350.69 | 15624.75 | 0.91 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.262160E+10 | 0.262160E+10 | 120275.99 | 19-MAR-15:51 | 120275.99 | 0.01 |
April | 0.00 | 0.00 | 0.424811E+11 | 0.324216E+11 | 533525.81 | 16-APR-18:49 | 317288.57 | 0.07 |
May | 0.00 | 0.00 | 0.953623E+11 | 0.712430E+11 | 544498.50 | 30-MAY-18:04 | 312187.63 | 0.21 |
June | 0.00 | 0.00 | 0.288838E+12 | 0.182266E+12 | 664800.37 | 30-JUN-08:32 | 297297.59 | 0.39 |
July | 0.00 | 0.00 | 0.423852E+12 | 0.235413E+12 | 949092.15 | 26-JUL-19:04 | 322875.55 | 0.49 |
August | 0.00 | 0.00 | 0.370692E+12 | 0.211083E+12 | 875815.03 | 04-AUG-07:52 | 297051.39 | 0.45 |
September | 0.00 | 0.00 | 0.136632E+12 | 0.118050E+12 | 486844.23 | 11-SEP-09:32 | 274927.03 | 0.24 |
October | 0.00 | 0.00 | 0.101241E+11 | 0.101133E+11 | 257935.65 | 20-OCT-14:21 | 257935.65 | 0.02 |
November | 0.00 | 0.00 | 0.624702E+09 | 0.624702E+09 | 79113.40 | 03-NOV-14:53 | 79113.40 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.137123E+13 | 0.863837E+12 | 0.16 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.423852E+12 | 0.235413E+12 | 949092.15 | 322875.55 | 0.49 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.192466E+09 | 0.192466E+09 | 8513.13 | 19-MAR-15:51 | 8513.13 | 0.01 |
April | 0.00 | 0.00 | 0.320445E+10 | 0.248039E+10 | 28950.18 | 18-APR-16:50 | 17095.42 | 0.09 |
May | 0.00 | 0.00 | 0.715673E+10 | 0.532921E+10 | 29106.59 | 29-MAY-15:12 | 14559.61 | 0.28 |
June | 0.00 | 0.00 | 0.237482E+11 | 0.151238E+11 | 40744.52 | 26-JUN-08:02 | 18218.40 | 0.55 |
July | 0.00 | 0.00 | 0.361656E+11 | 0.200651E+11 | 42550.34 | 17-JUL-18:04 | 17070.23 | 0.70 |
August | 0.00 | 0.00 | 0.293845E+11 | 0.167277E+11 | 49615.14 | 04-AUG-08:02 | 18332.40 | 0.63 |
September | 0.00 | 0.00 | 0.105441E+11 | 0.894140E+10 | 29509.45 | 11-SEP-08:11 | 15607.07 | 0.33 |
October | 0.00 | 0.00 | 0.606742E+09 | 0.606742E+09 | 15180.49 | 20-OCT-15:12 | 15180.49 | 0.02 |
November | 0.00 | 0.00 | 23848089.77 | 23848089.77 | 1790.73 | 03-NOV-15:11 | 1790.73 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.111027E+12 | 0.694907E+11 | 0.22 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.361656E+11 | 0.200651E+11 | 49615.14 | 18332.40 | 0.70 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 31287.52 | 64956.96 | 31-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 31903.44 | 65378.35 | 21-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 31633.24 | 65279.68 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:01 | 30445.51 | 63442.29 | 03-APR-06:58 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 28686.76 | 60477.31 | 01-MAY-06:35 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 26830.29 | 57082.40 | 20-JUN-06:01 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 25275.98 | 58746.31 | 05-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 24604.99 | 50780.60 | 01-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 24915.27 | 52502.75 | 06-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 26205.24 | 55258.06 | 31-OCT-06:18 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 28004.80 | 59083.56 | 30-NOV-07:26 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 29865.24 | 62484.52 | 29-DEC-07:16 |
Annual Sum or Average | 0.00 | 28283.56 | ||||
Minimum of Months | 0.00 | 0.00 | 24604.99 | 50780.60 | ||
Maximum of Months | 0.00 | 0.00 | 31903.44 | 65378.35 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 109121.00 | 478163.48 | 19-JAN-04:42 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 79762.93 | 487844.50 | 02-FEB-05:50 |
March | 0.02 | 74.35 | 22-MAR-12:00 | 23803.49 | 199493.57 | 06-MAR-05:04 |
April | 0.00 | 32.18 | 19-APR-06:50 | 8256.45 | 123885.90 | 03-APR-08:04 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 587.35 | 34380.35 | 20-MAY-23:24 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 232.20 | 40543.29 | 01-JUN-03:52 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.87 | 28622.84 | 23-JUL-08:16 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 22.34 | 17561.17 | 01-AUG-08:17 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 1201.96 | 43729.75 | 29-SEP-17:54 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5486.69 | 47830.53 | 06-OCT-18:24 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 34219.91 | 454015.09 | 25-NOV-22:52 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 64038.05 | 281709.57 | 11-DEC-16:22 |
Annual Sum or Average | 0.00 | 26975.93 | ||||
Minimum of Months | 0.00 | 0.00 | 22.34 | 17561.17 | ||
Maximum of Months | 0.02 | 74.35 | 109121.00 | 487844.50 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 211.62 | 29865.29 | 01-JAN-09:01 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 504.66 | 35658.94 | 24-FEB-16:13 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 3195.90 | 153109.47 | 25-MAR-15:12 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 28085.33 | 652869.21 | 16-APR-18:49 | 0.00 | 0.00 | 01-APR-00:01 |
May | 61915.03 | 656188.07 | 31-MAY-18:12 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 162102.39 | 847048.58 | 30-JUN-08:11 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 219720.87 | 1089974.96 | 26-JUL-19:10 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 194287.33 | 1012522.51 | 03-AUG-21:14 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 87985.17 | 609141.37 | 06-SEP-15:14 | 0.00 | 0.00 | 01-SEP-00:01 |
October | 14522.53 | 312345.43 | 20-OCT-15:20 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 3918.69 | 172310.40 | 05-NOV-15:11 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 443.73 | 42307.28 | 03-DEC-09:01 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 65205.71 | 0.00 | ||||
Minimum of Months | 211.62 | 29865.29 | 0.00 | 0.00 | ||
Maximum of Months | 219720.87 | 1089974.96 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261252E+10 | 0.70 | 1298.89 | 01-JAN-00:23 | 0.92 |
February | 0.235970E+10 | 0.70 | 1298.89 | 01-FEB-00:01 | 0.93 |
March | 0.261252E+10 | 0.70 | 1298.89 | 01-MAR-00:42 | 0.92 |
April | 0.252825E+10 | 0.70 | 1298.89 | 01-APR-08:61 | 0.92 |
May | 0.261252E+10 | 0.70 | 1298.89 | 01-MAY-15:11 | 0.92 |
June | 0.252825E+10 | 0.70 | 1298.89 | 01-JUN-08:61 | 0.92 |
July | 0.261252E+10 | 0.70 | 1298.89 | 01-JUL-08:11 | 0.91 |
August | 0.261252E+10 | 0.70 | 1298.89 | 01-AUG-08:11 | 0.91 |
September | 0.252825E+10 | 0.70 | 1298.89 | 01-SEP-08:11 | 0.91 |
October | 0.261252E+10 | 0.70 | 1298.89 | 01-OCT-18:01 | 0.92 |
November | 0.252825E+10 | 0.70 | 1298.89 | 01-NOV-08:61 | 0.92 |
December | 0.261252E+10 | 0.70 | 1298.89 | 01-DEC-00:09 | 0.92 |
Annual Sum or Average | 0.307604E+11 | 0.70 | |||
Minimum of Months | 0.235970E+10 | 0.70 | 1298.89 | 0.91 | |
Maximum of Months | 0.261252E+10 | 0.70 | 1298.89 | 0.93 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.377639E+11 | 0.72 | 41249.60 | 13-JAN-21:52 | 1.84 |
February | 0.363195E+11 | 0.75 | 41720.93 | 24-FEB-15:22 | 1.86 |
March | 0.466152E+11 | 0.83 | 42706.76 | 25-MAR-17:22 | 1.88 |
April | 0.464786E+11 | 0.84 | 44001.16 | 13-APR-18:19 | 1.92 |
May | 0.501264E+11 | 0.87 | 44001.16 | 03-MAY-18:04 | 1.92 |
June | 0.497081E+11 | 0.88 | 44001.16 | 02-JUN-18:02 | 1.91 |
July | 0.518422E+11 | 0.89 | 44001.16 | 01-JUL-00:03 | 1.91 |
August | 0.539112E+11 | 0.91 | 44001.16 | 01-AUG-00:22 | 1.90 |
September | 0.529776E+11 | 0.92 | 44001.16 | 01-SEP-12:02 | 1.92 |
October | 0.537886E+11 | 0.91 | 44001.16 | 01-OCT-10:54 | 1.92 |
November | 0.462484E+11 | 0.84 | 44001.16 | 03-NOV-10:32 | 1.91 |
December | 0.440125E+11 | 0.80 | 41629.22 | 03-DEC-12:52 | 1.86 |
Annual Sum or Average | 0.569792E+12 | 0.85 | |||
Minimum of Months | 0.363195E+11 | 0.72 | 41249.60 | 1.84 | |
Maximum of Months | 0.539112E+11 | 0.92 | 44001.16 | 1.92 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:05 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:01 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:01 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:01 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:01 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:01 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:01 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:02 | 0.28 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:01 | 0.28 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:01 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:01 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:01 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.28 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | -0.0 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:02 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | -0.0 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | -0.0 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | -0.0 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:02 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:01 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:01 | 0.27 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:01 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:01 | 0.28 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:01 | 0.28 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:01 | 0.28 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:01 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:01 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:01 | 0.27 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:01 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:01 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:01 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.722409E+09 | 0.56 | 750.29 | 01-JAN-09:01 | 0.60 |
February | 0.500766E+09 | 0.51 | 750.29 | 01-FEB-01:11 | 0.61 |
March | 0.269010E+09 | 0.44 | 750.29 | 01-MAR-09:01 | 0.60 |
April | 0.208409E+09 | 0.45 | 750.29 | 01-APR-08:61 | 0.60 |
May | 0.160986E+09 | 0.46 | 750.29 | 01-MAY-15:11 | 0.60 |
June | 0.269090E+09 | 0.52 | 750.29 | 01-JUN-08:61 | 0.60 |
July | 0.331947E+09 | 0.55 | 750.29 | 01-JUL-08:61 | 0.60 |
August | 0.293502E+09 | 0.55 | 750.29 | 01-AUG-08:61 | 0.59 |
September | 0.219605E+09 | 0.50 | 750.29 | 01-SEP-08:61 | 0.60 |
October | 0.170225E+09 | 0.43 | 750.29 | 01-OCT-15:11 | 0.60 |
November | 0.335585E+09 | 0.47 | 750.29 | 01-NOV-08:61 | 0.60 |
December | 0.526320E+09 | 0.52 | 750.29 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.400785E+10 | 0.50 | |||
Minimum of Months | 0.160986E+09 | 0.43 | 750.29 | 0.59 | |
Maximum of Months | 0.722409E+09 | 0.56 | 750.29 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.815744E+09 | 0.59 | 737.73 | 01-JAN-09:01 | 0.60 |
February | 0.573356E+09 | 0.54 | 737.73 | 01-FEB-00:01 | 0.61 |
March | 0.294405E+09 | 0.46 | 737.73 | 01-MAR-09:01 | 0.60 |
April | 0.191032E+09 | 0.42 | 737.73 | 01-APR-08:61 | 0.60 |
May | 0.111872E+09 | 0.38 | 737.73 | 01-MAY-15:11 | 0.60 |
June | 0.203294E+09 | 0.41 | 737.73 | 01-JUN-08:61 | 0.60 |
July | 0.220659E+09 | 0.39 | 737.73 | 01-JUL-08:11 | 0.60 |
August | 0.185275E+09 | 0.39 | 737.73 | 01-AUG-08:11 | 0.59 |
September | 0.152637E+09 | 0.41 | 737.73 | 01-SEP-08:11 | 0.60 |
October | 0.175804E+09 | 0.40 | 737.73 | 01-OCT-18:01 | 0.60 |
November | 0.375640E+09 | 0.49 | 737.73 | 01-NOV-08:61 | 0.60 |
December | 0.591024E+09 | 0.57 | 737.73 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.389074E+10 | 0.45 | |||
Minimum of Months | 0.111872E+09 | 0.38 | 737.73 | 0.59 | |
Maximum of Months | 0.815744E+09 | 0.59 | 737.73 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.605161E+09 | 0.24 | 1115.38 | 19-JAN-05:01 | 0.61 |
February | 0.144594E+09 | 0.06 | 999.48 | 04-FEB-05:51 | 0.61 |
March | 67139554.85 | 0.05 | 610.34 | 05-MAR-05:51 | 0.60 |
April | 0.212072E+09 | 0.11 | 1078.77 | 15-APR-12:41 | 0.60 |
May | 0.523745E+09 | 0.39 | 752.44 | 31-MAY-17:11 | 0.60 |
June | 0.870278E+09 | 0.50 | 854.46 | 26-JUN-17:11 | 0.60 |
July | 0.109272E+10 | 0.57 | 806.55 | 30-JUL-13:01 | 0.60 |
August | 0.113349E+10 | 0.58 | 1038.84 | 29-AUG-13:11 | 0.60 |
September | 0.946632E+09 | 0.44 | 1701.31 | 07-SEP-12:50 | 0.60 |
October | 0.467221E+09 | 0.25 | 1857.25 | 20-OCT-12:50 | 0.60 |
November | 0.190703E+09 | 0.12 | 1876.21 | 04-NOV-12:11 | 0.60 |
December | 0.401080E+09 | 0.18 | 937.43 | 12-DEC-04:51 | 0.61 |
Annual Sum or Average | 0.665484E+10 | 0.29 | |||
Minimum of Months | 67139554.85 | 0.05 | 610.34 | 0.60 | |
Maximum of Months | 0.113349E+10 | 0.58 | 1876.21 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.334846E+10 | 0.48 | 3721.16 | 01-JAN-16:11 | 0.60 |
February | 0.238019E+10 | 0.45 | 3721.16 | 01-FEB-00:01 | 0.60 |
March | 0.103099E+10 | 0.40 | 3721.16 | 01-MAR-09:01 | 0.60 |
April | 0.782139E+09 | 0.39 | 3721.16 | 01-APR-08:61 | 0.60 |
May | 0.107712E+10 | 0.36 | 3721.16 | 01-MAY-08:61 | 0.60 |
June | 0.166066E+10 | 0.37 | 3721.16 | 01-JUN-08:61 | 0.60 |
July | 0.175556E+10 | 0.34 | 3721.16 | 01-JUL-08:11 | 0.60 |
August | 0.155053E+10 | 0.34 | 3721.16 | 01-AUG-08:11 | 0.59 |
September | 0.105711E+10 | 0.37 | 3721.16 | 01-SEP-08:11 | 0.60 |
October | 0.585636E+09 | 0.40 | 3721.16 | 01-OCT-08:61 | 0.60 |
November | 0.134413E+10 | 0.42 | 3721.16 | 01-NOV-08:61 | 0.60 |
December | 0.221084E+10 | 0.44 | 3721.16 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.187833E+11 | 0.40 | |||
Minimum of Months | 0.585636E+09 | 0.34 | 3721.16 | 0.59 | |
Maximum of Months | 0.334846E+10 | 0.48 | 3721.16 | 0.60 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.685427E+09 | 0.56 | 667.47 | 01-JAN-09:01 | 0.60 |
February | 0.477990E+09 | 0.50 | 667.47 | 01-FEB-00:01 | 0.61 |
March | 0.246571E+09 | 0.44 | 667.47 | 01-MAR-09:01 | 0.60 |
April | 0.189936E+09 | 0.45 | 667.47 | 01-APR-08:61 | 0.60 |
May | 0.160420E+09 | 0.50 | 667.47 | 01-MAY-08:61 | 0.60 |
June | 0.261918E+09 | 0.54 | 667.47 | 01-JUN-08:61 | 0.60 |
July | 0.311254E+09 | 0.57 | 667.47 | 01-JUL-08:61 | 0.60 |
August | 0.270061E+09 | 0.56 | 667.47 | 01-AUG-08:61 | 0.60 |
September | 0.209411E+09 | 0.52 | 667.47 | 01-SEP-08:61 | 0.60 |
October | 0.152203E+09 | 0.43 | 667.47 | 01-OCT-08:61 | 0.60 |
November | 0.314067E+09 | 0.47 | 667.47 | 02-NOV-08:61 | 0.60 |
December | 0.510227E+09 | 0.53 | 667.47 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.378948E+10 | 0.51 | |||
Minimum of Months | 0.152203E+09 | 0.43 | 667.47 | 0.60 | |
Maximum of Months | 0.685427E+09 | 0.57 | 667.47 | 0.61 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.781920E+09 | 0.58 | 663.93 | 01-JAN-09:01 | 0.60 |
February | 0.550013E+09 | 0.54 | 663.93 | 01-FEB-00:01 | 0.61 |
March | 0.271819E+09 | 0.45 | 663.93 | 01-MAR-09:01 | 0.60 |
April | 0.181661E+09 | 0.42 | 663.93 | 01-APR-08:61 | 0.60 |
May | 0.125318E+09 | 0.41 | 663.93 | 01-MAY-08:61 | 0.60 |
June | 0.213693E+09 | 0.43 | 663.93 | 01-JUN-08:61 | 0.60 |
July | 0.231234E+09 | 0.40 | 663.93 | 01-JUL-08:11 | 0.60 |
August | 0.190255E+09 | 0.41 | 663.93 | 01-AUG-08:11 | 0.59 |
September | 0.153523E+09 | 0.42 | 663.93 | 01-SEP-08:11 | 0.60 |
October | 0.161312E+09 | 0.40 | 663.93 | 01-OCT-08:61 | 0.60 |
November | 0.356056E+09 | 0.49 | 663.93 | 01-NOV-08:61 | 0.60 |
December | 0.594427E+09 | 0.58 | 663.93 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.381123E+10 | 0.46 | |||
Minimum of Months | 0.125318E+09 | 0.40 | 663.93 | 0.59 | |
Maximum of Months | 0.781920E+09 | 0.58 | 663.93 | 0.61 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.207031E+09 | 0.57 | 195.84 | 01-JAN-09:01 | 0.60 |
February | 0.138664E+09 | 0.53 | 195.84 | 01-FEB-02:61 | 0.61 |
March | 81343741.79 | 0.46 | 195.84 | 01-MAR-09:01 | 0.60 |
April | 62893659.12 | 0.46 | 195.84 | 01-APR-08:61 | 0.60 |
May | 48547667.47 | 0.48 | 195.84 | 01-MAY-15:11 | 0.60 |
June | 77957763.59 | 0.53 | 195.84 | 01-JUN-08:61 | 0.60 |
July | 93710217.36 | 0.56 | 195.84 | 01-JUL-08:61 | 0.60 |
August | 80685149.72 | 0.55 | 195.84 | 01-AUG-08:61 | 0.59 |
September | 62311447.80 | 0.50 | 195.84 | 01-SEP-08:61 | 0.60 |
October | 51988485.56 | 0.43 | 195.84 | 01-OCT-15:11 | 0.60 |
November | 0.101644E+09 | 0.49 | 195.84 | 01-NOV-08:61 | 0.60 |
December | 0.157197E+09 | 0.54 | 195.84 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.116397E+10 | 0.51 | |||
Minimum of Months | 48547667.47 | 0.43 | 195.84 | 0.59 | |
Maximum of Months | 0.207031E+09 | 0.57 | 195.84 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.232202E+09 | 0.59 | 192.47 | 01-JAN-09:01 | 0.60 |
February | 0.157591E+09 | 0.56 | 192.47 | 01-FEB-00:01 | 0.61 |
March | 89099346.05 | 0.49 | 192.47 | 01-MAR-09:01 | 0.60 |
April | 57262039.20 | 0.44 | 192.47 | 01-APR-08:61 | 0.60 |
May | 35070919.65 | 0.40 | 192.47 | 01-MAY-15:11 | 0.60 |
June | 62075931.70 | 0.42 | 192.47 | 01-JUN-08:61 | 0.60 |
July | 66420879.31 | 0.40 | 192.47 | 01-JUL-08:11 | 0.60 |
August | 53599111.68 | 0.40 | 192.47 | 01-AUG-08:11 | 0.59 |
September | 44567879.24 | 0.41 | 192.47 | 01-SEP-08:11 | 0.60 |
October | 53421823.12 | 0.40 | 192.47 | 01-OCT-08:61 | 0.60 |
November | 0.112916E+09 | 0.51 | 192.47 | 01-NOV-08:61 | 0.60 |
December | 0.182340E+09 | 0.59 | 192.47 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.114657E+10 | 0.47 | |||
Minimum of Months | 35070919.65 | 0.40 | 192.47 | 0.59 | |
Maximum of Months | 0.232202E+09 | 0.59 | 192.47 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.643649E+09 | 0.50 | 739.51 | 01-JAN-09:01 | 0.60 |
February | 0.431041E+09 | 0.47 | 739.51 | 01-FEB-03:11 | 0.61 |
March | 0.275435E+09 | 0.47 | 739.51 | 01-MAR-09:01 | 0.60 |
April | 0.244626E+09 | 0.47 | 739.51 | 01-APR-08:61 | 0.60 |
May | 0.206114E+09 | 0.49 | 739.51 | 01-MAY-08:61 | 0.60 |
June | 0.321160E+09 | 0.52 | 739.51 | 01-JUN-08:61 | 0.60 |
July | 0.391560E+09 | 0.55 | 739.51 | 01-JUL-08:61 | 0.60 |
August | 0.385459E+09 | 0.55 | 739.51 | 01-AUG-08:61 | 0.59 |
September | 0.330102E+09 | 0.52 | 739.51 | 01-SEP-08:61 | 0.60 |
October | 0.242778E+09 | 0.49 | 739.51 | 01-OCT-08:61 | 0.60 |
November | 0.330170E+09 | 0.47 | 739.51 | 01-NOV-15:11 | 0.60 |
December | 0.531888E+09 | 0.52 | 739.51 | 01-DEC-09:01 | 0.60 |
Annual Sum or Average | 0.433398E+10 | 0.50 | |||
Minimum of Months | 0.206114E+09 | 0.47 | 739.51 | 0.59 | |
Maximum of Months | 0.643649E+09 | 0.55 | 739.51 | 0.61 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.131224E+10 | 0.119282E+10 | 3109.42 | 19-JAN-05:08 | 2826.46 | 2826.46 | 51.04 | 12.64 |
February | 0.951599E+09 | 0.865003E+09 | 3280.67 | 04-FEB-05:06 | 2982.13 | 2982.13 | 51.35 | 12.90 |
March | 0.345531E+09 | 0.314088E+09 | 1060.33 | 06-MAR-04:10 | 963.84 | 963.84 | 55.62 | 8.17 |
April | 0.130931E+09 | 0.119017E+09 | 586.61 | 03-APR-08:02 | 533.23 | 533.23 | 55.80 | 6.36 |
May | 14516471.95 | 13195473.00 | 202.34 | 03-MAY-03:00 | 183.93 | 183.93 | 58.75 | 3.95 |
June | 1238596.91 | 1125884.59 | 110.86 | 03-JUN-04:00 | 100.78 | 100.78 | 59.11 | 2.98 |
July | 17434.12 | 15847.61 | 10.42 | 13-JUL-08:16 | 9.48 | 9.48 | 56.25 | 0.83 |
August | 22826.82 | 20749.58 | 11.02 | 16-AUG-08:14 | 10.02 | 10.02 | 55.62 | 0.86 |
September | 16761794.52 | 15236471.22 | 242.39 | 30-SEP-04:00 | 220.33 | 220.33 | 57.98 | 4.30 |
October | 79730647.63 | 72475158.69 | 301.67 | 23-OCT-08:02 | 274.22 | 274.22 | 58.85 | 4.74 |
November | 0.397048E+09 | 0.360916E+09 | 2586.82 | 26-NOV-06:52 | 2351.42 | 2351.42 | 51.11 | 11.75 |
December | 0.776484E+09 | 0.705824E+09 | 1302.16 | 11-DEC-16:12 | 1183.66 | 1183.66 | 53.26 | 8.90 |
Annual Sum or Average | 0.402612E+10 | 0.365974E+10 | ||||||
Minimum of Months | 17434.12 | 15847.61 | 10.42 | 9.48 | 9.48 | 51.04 | 0.83 | |
Maximum of Months | 0.131224E+10 | 0.119282E+10 | 3280.67 | 2982.13 | 2982.13 | 59.11 | 12.90 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 92821.02 | 84374.30 | 15.04 | 01-JAN-09:01 | 13.67 | 13.67 | 6.71 | 1.61 |
February | 247080.25 | 224595.95 | 29.71 | 25-FEB-09:01 | 27.00 | 27.00 | 6.71 | 2.40 |
March | 3167069.21 | 2878865.91 | 87.13 | 19-MAR-15:51 | 79.20 | 79.20 | 6.71 | 4.28 |
April | 77250813.09 | 70220989.10 | 1698.21 | 15-APR-18:29 | 1543.67 | 1543.67 | 6.71 | 16.52 |
May | 0.139248E+09 | 0.126576E+09 | 1952.58 | 31-MAY-18:12 | 1774.90 | 1774.90 | 6.71 | 17.50 |
June | 0.569465E+09 | 0.517644E+09 | 2741.51 | 11-JUN-18:41 | 2492.03 | 2492.03 | 6.71 | 20.08 |
July | 0.841749E+09 | 0.765150E+09 | 3700.80 | 26-JUL-19:10 | 3364.03 | 3364.03 | 7.74 | 22.63 |
August | 0.737250E+09 | 0.670160E+09 | 3646.19 | 03-AUG-19:20 | 3314.39 | 3314.39 | 7.33 | 22.50 |
September | 0.248039E+09 | 0.225467E+09 | 1453.13 | 11-SEP-09:41 | 1320.89 | 1320.89 | 6.71 | 15.49 |
October | 20501447.00 | 18635815.32 | 413.24 | 01-OCT-15:17 | 375.63 | 375.63 | 6.71 | 9.00 |
November | 3801554.82 | 3455613.34 | 297.40 | 05-NOV-15:11 | 270.34 | 270.34 | 6.71 | 7.75 |
December | 204622.41 | 186001.77 | 29.78 | 03-DEC-09:01 | 27.07 | 27.07 | 6.71 | 2.41 |
Annual Sum or Average | 0.264102E+10 | 0.240068E+10 | ||||||
Minimum of Months | 92821.02 | 84374.30 | 15.04 | 13.67 | 13.67 | 6.71 | 1.61 | |
Maximum of Months | 0.841749E+09 | 0.765150E+09 | 3700.80 | 3364.03 | 3364.03 | 7.74 | 22.63 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:05 | 14.37 | 14.37 | 47.01 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:01 | 14.37 | 14.37 | 41.29 | 0.08 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:01 | 14.37 | 14.37 | 40.88 | 0.08 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:01 | 14.37 | 14.37 | 46.86 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:01 | 14.37 | 14.37 | 49.24 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:01 | 14.37 | 14.37 | 48.41 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:01 | 14.37 | 14.37 | 44.31 | 0.06 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:02 | 14.37 | 14.37 | 46.98 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:01 | 14.37 | 14.37 | 50.18 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:01 | 14.37 | 14.37 | 48.89 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:01 | 14.37 | 14.37 | 44.35 | 0.06 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:01 | 14.37 | 14.37 | 42.53 | 0.08 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 40.88 | 0.06 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 50.18 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.239969E+09 | 0.218132E+09 | 1578.95 | 01-JAN-09:01 | 1435.27 | 1435.27 | 6.98 | 25.01 |
February | 0.433896E+09 | 0.394411E+09 | 1578.95 | 01-FEB-16:11 | 1435.27 | 1435.27 | 6.74 | 25.01 |
March | 0.123547E+10 | 0.112304E+10 | 1578.95 | 01-MAR-09:04 | 1435.27 | 1435.27 | 6.80 | 25.01 |
April | 0.223415E+10 | 0.203084E+10 | 1578.95 | 01-APR-08:61 | 1435.27 | 1435.27 | 6.91 | 25.01 |
May | 0.404000E+10 | 0.367236E+10 | 1578.95 | 01-MAY-00:01 | 1435.27 | 1435.27 | 6.76 | 25.01 |
June | 0.399037E+10 | 0.362725E+10 | 1578.95 | 01-JUN-00:01 | 1435.27 | 1435.27 | 7.17 | 25.01 |
July | 0.422871E+10 | 0.384389E+10 | 1578.95 | 01-JUL-00:01 | 1435.27 | 1435.27 | 7.56 | 25.01 |
August | 0.422906E+10 | 0.384422E+10 | 1578.95 | 01-AUG-00:02 | 1435.27 | 1435.27 | 10.07 | 25.01 |
September | 0.373254E+10 | 0.339288E+10 | 1578.95 | 01-SEP-00:01 | 1435.27 | 1435.27 | 7.34 | 25.01 |
October | 0.277437E+10 | 0.252191E+10 | 1578.95 | 01-OCT-06:11 | 1435.27 | 1435.27 | 6.72 | 25.01 |
November | 0.114888E+10 | 0.104433E+10 | 1578.95 | 01-NOV-05:01 | 1435.27 | 1435.27 | 6.73 | 25.01 |
December | 0.450285E+09 | 0.409309E+09 | 1578.95 | 01-DEC-09:03 | 1435.27 | 1435.27 | 6.90 | 25.01 |
Annual Sum or Average | 0.287377E+11 | 0.261226E+11 | ||||||
Minimum of Months | 0.239969E+09 | 0.218132E+09 | 1578.95 | 1435.27 | 1435.27 | 6.72 | 25.01 | |
Maximum of Months | 0.422906E+10 | 0.384422E+10 | 1578.95 | 1435.27 | 1435.27 | 10.07 | 25.01 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 47.01 | 59.87 | 31287.52 | 64956.96 | 31-JAN-07:56 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 41.29 | 59.00 | 31903.44 | 65378.35 | 21-FEB-07:55 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 40.88 | 58.52 | 31633.24 | 65279.68 | 01-MAR-07:15 |
April | 0.00 | 0.00 | 01-APR-00:01 | 46.86 | 59.26 | 30445.51 | 63442.29 | 03-APR-06:58 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 49.24 | 59.60 | 28686.76 | 60477.31 | 01-MAY-06:35 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 48.41 | 59.54 | 26830.29 | 57082.40 | 20-JUN-06:01 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 44.31 | 58.69 | 25275.98 | 58746.31 | 05-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 46.98 | 59.22 | 24604.99 | 50780.60 | 01-AUG-07:00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.18 | 58.01 | 24915.27 | 52502.75 | 06-SEP-06:02 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 48.89 | 58.59 | 26205.24 | 55258.06 | 31-OCT-06:18 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 44.35 | 59.67 | 28004.80 | 59083.56 | 30-NOV-07:26 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 42.53 | 58.43 | 29865.24 | 62484.52 | 29-DEC-07:16 |
Annual Sum or Average | 0.00 | 28283.56 | ||||||
Minimum of Months | 0.00 | 0.00 | 40.88 | 58.01 | 24604.99 | 50780.60 | ||
Maximum of Months | 0.00 | 0.00 | 50.18 | 59.87 | 31903.44 | 65378.35 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 52.65 | 60.00 | 109121.00 | 478163.48 | 19-JAN-04:42 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.21 | 60.00 | 79762.93 | 487844.50 | 02-FEB-05:50 |
March | 0.02 | 74.35 | 22-MAR-12:00 | 60.01 | 60.01 | 23803.49 | 199493.57 | 06-MAR-05:04 |
April | 0.00 | 32.18 | 19-APR-06:50 | 60.00 | 60.00 | 8256.45 | 123885.90 | 03-APR-08:04 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 57.78 | 60.00 | 587.35 | 34380.35 | 20-MAY-23:24 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 55.71 | 55.71 | 232.20 | 40543.29 | 01-JUN-03:52 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 56.27 | 56.27 | 22.87 | 28622.84 | 23-JUL-08:16 |
August | 0.00 | 0.00 | 01-AUG-00:02 | 52.35 | 52.35 | 22.34 | 17561.17 | 01-AUG-08:17 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 55.82 | 55.82 | 1201.96 | 43729.75 | 29-SEP-17:54 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 58.69 | 60.00 | 5486.69 | 47830.53 | 06-OCT-18:24 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 58.70 | 60.00 | 34219.91 | 454015.09 | 25-NOV-22:52 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 57.62 | 60.00 | 64038.05 | 281709.57 | 11-DEC-16:22 |
Annual Sum or Average | 0.00 | 26975.93 | ||||||
Minimum of Months | 0.00 | 0.00 | 51.21 | 52.35 | 22.34 | 17561.17 | ||
Maximum of Months | 0.02 | 74.35 | 60.01 | 60.01 | 109121.00 | 487844.50 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 211.62 | 29865.29 | 01-JAN-09:01 | 6.98 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 504.66 | 35658.94 | 24-FEB-16:13 | 7.04 | 6.70 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 3195.90 | 153109.47 | 25-MAR-15:12 | 8.16 | 6.70 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 28085.33 | 652869.21 | 16-APR-18:49 | 12.93 | 6.70 | 0.00 | 0.00 | 01-APR-00:01 |
May | 61915.03 | 656188.07 | 31-MAY-18:12 | 12.97 | 6.70 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 162102.39 | 847048.58 | 30-JUN-08:11 | 14.79 | 6.70 | 0.00 | 0.00 | 01-JUN-00:01 |
July | 219720.87 | 1089974.96 | 26-JUL-19:10 | 17.12 | 8.75 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 194287.33 | 1012522.51 | 03-AUG-21:14 | 16.38 | 8.01 | 0.00 | 0.00 | 01-AUG-00:02 |
September | 87985.17 | 609141.37 | 06-SEP-15:14 | 12.52 | 6.70 | 0.00 | 0.00 | 01-SEP-00:01 |
October | 14522.53 | 312345.43 | 20-OCT-15:20 | 9.68 | 6.70 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 3918.69 | 172310.40 | 05-NOV-15:11 | 8.34 | 6.70 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 443.73 | 42307.28 | 03-DEC-09:01 | 7.10 | 6.70 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 65205.71 | 0.00 | ||||||
Minimum of Months | 211.62 | 29865.29 | 6.98 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 219720.87 | 1089974.96 | 17.12 | 8.75 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.06 | 74.55 |
July | 0.32 | 70.38 |
August | 0.33 | 88.75 |
September | 0.69 | 79.66 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.40 | 79.51 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.69 | 88.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.93 | 6.73 |
May | 0.52 | 7.79 |
June | 2.01 | 8.42 |
July | 3.08 | 7.73 |
August | 1.98 | 5.85 |
September | 2.30 | 7.00 |
October | 0.35 | 3.00 |
November | 0.04 | 2.17 |
December | 0.00 | 0.00 |
Annual Sum or Average | 11.21 | 7.13 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.08 | 8.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.21 | 9.10 |
May | 0.52 | 10.29 |
June | 1.07 | 9.08 |
July | 1.70 | 9.71 |
August | 1.39 | 9.85 |
September | 1.08 | 9.53 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 5.98 | 9.63 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.70 | 10.29 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.26 | 0.00 |
August | 0.00 | 0.00 |
September | 0.14 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.40 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.26 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 742.55 | 4.80 |
February | 671.00 | 4.81 |
March | 737.99 | 4.83 |
April | 700.76 | 4.83 |
May | 695.24 | 4.87 |
June | 670.42 | 4.83 |
July | 677.70 | 4.82 |
August | 682.75 | 4.86 |
September | 680.77 | 4.84 |
October | 730.09 | 4.83 |
November | 716.88 | 4.81 |
December | 742.70 | 4.80 |
Annual Sum or Average | 8448.85 | 4.83 |
Minimum of Months | 670.42 | 4.80 |
Maximum of Months | 742.70 | 4.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.19 | 99.61 |
February | 0.00 | 0.00 |
March | 0.63 | 46.73 |
April | 26.30 | 59.71 |
May | 30.67 | 97.27 |
June | 139.50 | 92.03 |
July | 189.97 | 97.49 |
August | 154.93 | 92.02 |
September | 130.00 | 78.40 |
October | 7.96 | 42.10 |
November | 4.58 | 52.88 |
December | 0.33 | 40.56 |
Annual Sum or Average | 685.08 | 89.04 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 189.97 | 99.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 295.70 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.59 | 294.13 |
May | 0.74 | 343.62 |
June | 2.99 | 295.31 |
July | 2.35 | 298.44 |
August | 1.80 | 284.08 |
September | 1.30 | 297.94 |
October | 0.03 | 211.22 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 9.86 | 297.65 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.99 | 343.62 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.07 | 0.65 |
July | 0.00 | 0.00 |
August | 0.02 | 0.80 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.10 | 0.68 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.07 | 0.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.04 | 0.65 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.04 | 0.65 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.04 | 0.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.04 | 0.65 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.04 | 0.65 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.04 | 0.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.04 | 0.65 |
July | 0.00 | 0.00 |
August | 0.02 | 0.80 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.07 | 0.70 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.04 | 0.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.03 | 0.45 |
May | 0.00 | 0.00 |
June | 0.10 | 0.95 |
July | 0.14 | 0.59 |
August | 0.06 | 0.39 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 0.65 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.14 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.03 | 0.65 |
July | 0.00 | 0.00 |
August | 0.02 | 0.80 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.06 | 0.71 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.03 | 0.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.04 | 0.65 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.04 | 0.65 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.04 | 0.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.03 | 0.45 |
May | 0.00 | 0.00 |
June | 0.07 | 0.65 |
July | 0.00 | 0.00 |
August | 0.02 | 0.80 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.13 | 0.63 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.07 | 0.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 166.69 | 190.93 |
February | 243.18 | 193.12 |
March | 340.96 | 191.44 |
April | 430.45 | 175.22 |
May | 509.98 | 158.57 |
June | 504.83 | 152.24 |
July | 488.99 | 150.89 |
August | 506.77 | 153.07 |
September | 504.95 | 158.04 |
October | 463.59 | 177.84 |
November | 304.30 | 184.17 |
December | 125.37 | 209.94 |
Annual Sum or Average | 4590.07 | 168.44 |
Minimum of Months | 125.37 | 150.89 |
Maximum of Months | 509.98 | 209.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 368.74 | 186.22 |
February | 450.48 | 170.10 |
March | 582.30 | 161.59 |
April | 618.48 | 148.60 |
May | 551.36 | 153.76 |
June | 534.24 | 149.69 |
July | 508.21 | 151.01 |
August | 524.55 | 152.76 |
September | 572.13 | 149.66 |
October | 657.86 | 148.58 |
November | 544.67 | 161.61 |
December | 409.30 | 184.61 |
Annual Sum or Average | 6322.33 | 158.15 |
Minimum of Months | 368.74 | 148.58 |
Maximum of Months | 657.86 | 186.22 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 742.35 | 12.71 |
February | 669.55 | 12.70 |
March | 738.60 | 12.80 |
April | 698.23 | 12.78 |
May | 685.21 | 12.94 |
June | 664.35 | 12.89 |
July | 667.81 | 12.87 |
August | 667.70 | 12.99 |
September | 672.59 | 12.92 |
October | 727.42 | 12.83 |
November | 717.30 | 12.73 |
December | 744.00 | 12.72 |
Annual Sum or Average | 8395.11 | 12.82 |
Minimum of Months | 664.35 | 12.70 |
Maximum of Months | 744.00 | 12.99 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.06 | 0.00 |
July | 0.12 | 0.00 |
August | 0.06 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.24 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.12 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.167069E+12 | 0.00 | 0.00 | 0.377639E+11 | 0.00 | 0.00 |
February | 0.110165E+12 | 0.00 | 0.00 | 0.363195E+11 | 0.00 | 0.00 |
March | 0.262139E+11 | 0.00 | 0.262160E+10 | 0.466152E+11 | 0.00 | 0.00 |
April | 0.691400E+10 | 0.00 | 0.424811E+11 | 0.464786E+11 | 0.00 | 0.00 |
May | 0.332145E+09 | 0.00 | 0.953623E+11 | 0.501264E+11 | 0.00 | 0.00 |
June | 0.137524E+09 | 0.00 | 0.288838E+12 | 0.497081E+11 | 0.00 | 0.00 |
July | 47092054.15 | 0.00 | 0.423852E+12 | 0.518422E+11 | 0.00 | 0.00 |
August | 983833.18 | 0.00 | 0.370692E+12 | 0.539112E+11 | 0.00 | 0.00 |
September | 0.642013E+09 | 0.00 | 0.136632E+12 | 0.529776E+11 | 0.00 | 0.00 |
October | 0.337333E+10 | 0.00 | 0.101241E+11 | 0.537886E+11 | 0.00 | 0.00 |
November | 0.412366E+11 | 0.00 | 0.624702E+09 | 0.462484E+11 | 0.00 | 0.00 |
December | 0.798954E+11 | 0.00 | 0.00 | 0.440125E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.436027E+12 | 0.00 | 0.137123E+13 | 0.569792E+12 | 0.00 | 0.00 |
Minimum of Months | 983833.18 | 0.00 | 0.00 | 0.363195E+11 | 0.00 | 0.00 |
Maximum of Months | 0.167069E+12 | 0.00 | 0.423852E+12 | 0.539112E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.157070E+11 | 0.00 | 0.00 | 0.261252E+10 | 0.00 | 0.00 |
February | 0.106288E+11 | 0.00 | 0.00 | 0.235970E+10 | 0.00 | 0.00 |
March | 0.232243E+10 | 0.00 | 0.192466E+09 | 0.261252E+10 | 0.00 | 0.00 |
April | 0.428509E+09 | 0.00 | 0.320445E+10 | 0.252825E+10 | 0.00 | 0.00 |
May | 23950.69 | 0.00 | 0.715673E+10 | 0.261252E+10 | 0.00 | 0.00 |
June | 34310.59 | 0.00 | 0.237482E+11 | 0.252825E+10 | 0.00 | 0.00 |
July | 37644.35 | 0.00 | 0.361656E+11 | 0.261252E+10 | 0.00 | 0.00 |
August | 39665.97 | 0.00 | 0.293845E+11 | 0.261252E+10 | 0.00 | 0.00 |
September | 310540.08 | 0.00 | 0.105441E+11 | 0.252825E+10 | 0.00 | 0.00 |
October | 21183851.61 | 0.00 | 0.606742E+09 | 0.261252E+10 | 0.00 | 0.00 |
November | 0.373761E+10 | 0.00 | 23848089.77 | 0.252825E+10 | 0.00 | 0.00 |
December | 0.670847E+10 | 0.00 | 0.00 | 0.261252E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.395544E+11 | 0.00 | 0.111027E+12 | 0.307604E+11 | 0.00 | 0.00 |
Minimum of Months | 23950.69 | 0.00 | 0.00 | 0.235970E+10 | 0.00 | 0.00 |
Maximum of Months | 0.157070E+11 | 0.00 | 0.361656E+11 | 0.261252E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.377639E+11 | 0.00 | 0.167069E+12 | 0.656944E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363195E+11 | 0.00 | 0.110165E+12 | 0.505540E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.466152E+11 | 0.262160E+10 | 0.262139E+11 | 0.532576E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.464786E+11 | 0.424811E+11 | 0.691400E+10 | 0.333256E+12 | 0.250040E+10 | 0.00 | 0.00 | 0.00 |
May | 0.501264E+11 | 0.953623E+11 | 0.332145E+09 | 0.107725E+12 | 0.131774E+10 | 0.00 | 0.00 | 0.00 |
June | 0.497081E+11 | 0.288838E+12 | 0.137524E+09 | 0.391556E+11 | 0.228418E+11 | 0.00 | 0.00 | 0.00 |
July | 0.518422E+11 | 0.423852E+12 | 47092054.15 | 0.555766E+10 | 0.236368E+11 | 0.00 | 0.00 | 0.00 |
August | 0.539112E+11 | 0.370692E+12 | 983833.18 | 0.144433E+11 | 0.228604E+11 | 0.00 | 0.00 | 0.00 |
September | 0.529776E+11 | 0.136632E+12 | 0.642013E+09 | 0.114762E+12 | 0.306453E+10 | 0.00 | 0.00 | 0.00 |
October | 0.537886E+11 | 0.101241E+11 | 0.337333E+10 | 0.324708E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.462484E+11 | 0.624702E+09 | 0.412366E+11 | 0.488155E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440125E+11 | 0.00 | 0.798954E+11 | 0.720051E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.569792E+12 | 0.137123E+13 | 0.436027E+12 | 0.384287E+13 | 0.762216E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.363195E+11 | 0.00 | 983833.18 | 0.555766E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.539112E+11 | 0.423852E+12 | 0.167069E+12 | 0.720051E+12 | 0.236368E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261252E+10 | 0.00 | 0.157070E+11 | 0.689383E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235970E+10 | 0.00 | 0.106288E+11 | 0.518883E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261252E+10 | 0.192466E+09 | 0.232243E+10 | 0.533771E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252825E+10 | 0.320445E+10 | 0.428509E+09 | 0.332628E+11 | 0.525884E+09 | 0.00 | 0.00 | 0.00 |
May | 0.261252E+10 | 0.715673E+10 | 23950.69 | 0.107322E+11 | 0.458155E+09 | 0.00 | 0.00 | 0.00 |
June | 0.252825E+10 | 0.237482E+11 | 34310.59 | 0.355060E+10 | 0.543693E+10 | 0.00 | 0.00 | 0.00 |
July | 0.261252E+10 | 0.361656E+11 | 37644.35 | 0.507690E+09 | 0.603319E+10 | 0.00 | 0.00 | 0.00 |
August | 0.261252E+10 | 0.293845E+11 | 39665.97 | 0.122556E+10 | 0.544904E+10 | 0.00 | 0.00 | 0.00 |
September | 0.252825E+10 | 0.105441E+11 | 310540.08 | 0.113962E+11 | 0.121987E+10 | 0.00 | 0.00 | 0.00 |
October | 0.261252E+10 | 0.606742E+09 | 21183851.61 | 0.324669E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252825E+10 | 23848089.77 | 0.373761E+10 | 0.485761E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261252E+10 | 0.00 | 0.670847E+10 | 0.728375E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307604E+11 | 0.111027E+12 | 0.395544E+11 | 0.388759E+12 | 0.191231E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.235970E+10 | 0.00 | 23950.69 | 0.507690E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261252E+10 | 0.361656E+11 | 0.157070E+11 | 0.728375E+11 | 0.603319E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.377639E+11 | 0.167069E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363195E+11 | 0.110165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.466152E+11 | 0.262139E+11 | 0.262160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.464786E+11 | 0.691400E+10 | 0.424811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.501264E+11 | 0.332145E+09 | 0.953623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.497081E+11 | 0.137524E+09 | 0.288838E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.518422E+11 | 47092054.15 | 0.423852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.539112E+11 | 983833.18 | 0.370692E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529776E+11 | 0.642013E+09 | 0.136632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.537886E+11 | 0.337333E+10 | 0.101241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.462484E+11 | 0.412366E+11 | 0.624702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440125E+11 | 0.798954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.569792E+12 | 0.436027E+12 | 0.137123E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.363195E+11 | 983833.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.539112E+11 | 0.167069E+12 | 0.423852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.261252E+10 | 0.157070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235970E+10 | 0.106288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261252E+10 | 0.232243E+10 | 0.192466E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252825E+10 | 0.428509E+09 | 0.320445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261252E+10 | 23950.69 | 0.715673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252825E+10 | 34310.59 | 0.237482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261252E+10 | 37644.35 | 0.361656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261252E+10 | 39665.97 | 0.293845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252825E+10 | 310540.08 | 0.105441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261252E+10 | 21183851.61 | 0.606742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252825E+10 | 0.373761E+10 | 23848089.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261252E+10 | 0.670847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307604E+11 | 0.395544E+11 | 0.111027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.235970E+10 | 23950.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261252E+10 | 0.157070E+11 | 0.361656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129938E+11 | 0.00 | 0.00 | 0.171010E+10 | 0.00 | 0.00 | 0.488872E+11 | 0.00 | 0.78 |
February | 0.599483E+10 | 0.00 | 0.00 | 0.991566E+09 | 0.00 | 0.984343E+10 | 0.342301E+11 | 0.00 | 0.74 |
March | 0.346271E+09 | 0.00 | 0.00 | 0.947798E+09 | 0.00 | 0.00 | 0.475448E+11 | 0.00 | 0.78 |
April | 0.299781E+10 | 7608745.70 | 0.00 | 0.523900E+09 | 0.182971E+09 | 0.00 | 0.366489E+11 | 0.00 | 0.70 |
May | 0.305185E+10 | 14038050.74 | 0.00 | 0.584926E+09 | 0.154339E+09 | 0.00 | 0.360876E+11 | 0.00 | 0.71 |
June | 0.339971E+09 | 0.233675E+10 | 0.00 | 0.709519E+09 | 0.342957E+09 | 0.00 | 0.248332E+11 | 0.00 | 0.74 |
July | 5721153.13 | 0.533841E+10 | 0.00 | 0.631162E+09 | 24507219.34 | 0.00 | 0.168369E+11 | 0.00 | 0.77 |
August | 0.00 | 0.587704E+10 | 0.00 | 0.137970E+10 | 361296.83 | 0.00 | 0.231238E+11 | 0.00 | 0.86 |
September | 1020537.99 | 0.267478E+09 | 0.00 | 0.390676E+10 | 0.00 | 0.00 | 0.379115E+11 | 0.00 | 0.89 |
October | 0.00 | 0.00 | 0.00 | 0.812764E+10 | 0.00 | 0.00 | 0.460428E+11 | 0.00 | 0.88 |
November | 0.00 | 0.00 | 0.00 | 0.724556E+10 | 0.00 | 0.00 | 0.478512E+11 | 0.00 | 0.87 |
December | 0.00 | 0.00 | 0.00 | 0.593446E+10 | 0.00 | 0.00 | 0.523995E+11 | 0.00 | 0.87 |
Annual Sum or Average | 0.257313E+11 | 0.138413E+11 | 0.00 | 0.326931E+11 | 0.705135E+09 | 0.984343E+10 | 0.452398E+12 | 0.00 | 0.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.523900E+09 | 0.00 | 0.00 | 0.168369E+11 | 0.00 | 0.70 |
Maximum of Months | 0.129938E+11 | 0.587704E+10 | 0.00 | 0.812764E+10 | 0.342957E+09 | 0.984343E+10 | 0.523995E+11 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.491752E+09 | 0.00 | 0.00 | 2748447.23 | 0.00 | 0.394245E+10 | 0.157745E+09 | 0.00 | 0.92 |
February | 0.983999E+09 | 0.00 | 0.00 | 8829626.94 | 0.00 | 0.260380E+10 | 0.263153E+09 | 0.00 | 0.91 |
March | 0.155609E+10 | 0.00 | 0.00 | 12568294.37 | 0.00 | 0.887587E+09 | 0.681335E+09 | 0.00 | 0.93 |
April | 0.153660E+10 | 43127980.60 | 0.00 | 18657512.30 | 0.00 | 0.299559E+09 | 0.116450E+10 | 0.00 | 1.05 |
May | 0.103559E+10 | 35069459.07 | 0.00 | 26124427.71 | 0.00 | 0.00 | 0.218243E+10 | 0.00 | 1.20 |
June | 0.419175E+09 | 0.473762E+09 | 0.00 | 31063581.55 | 594978.01 | 0.00 | 0.168666E+10 | 0.00 | 1.49 |
July | 0.134874E+09 | 0.788006E+09 | 0.00 | 31525348.66 | 236970.37 | 0.00 | 0.134977E+10 | 0.00 | 1.62 |
August | 93124320.27 | 0.764681E+09 | 0.00 | 49428646.89 | 318130.48 | 0.00 | 0.204351E+10 | 0.00 | 1.64 |
September | 0.853596E+09 | 34233816.23 | 0.00 | 88328088.54 | 0.00 | 0.00 | 0.239356E+10 | 0.00 | 1.44 |
October | 0.174058E+10 | 0.00 | 0.00 | 66228267.49 | 0.00 | 675532.07 | 0.200183E+10 | 0.00 | 1.13 |
November | 0.141594E+10 | 0.00 | 0.00 | 22174957.04 | 0.00 | 0.121959E+10 | 0.686649E+09 | 0.00 | 0.93 |
December | 0.695331E+09 | 0.00 | 0.00 | 9985611.76 | 0.00 | 0.237464E+10 | 0.356809E+09 | 0.00 | 0.91 |
Annual Sum or Average | 0.109566E+11 | 0.213888E+10 | 0.00 | 0.367663E+09 | 1150078.86 | 0.113283E+11 | 0.149680E+11 | 0.00 | 1.18 |
Minimum of Months | 93124320.27 | 0.00 | 0.00 | 2748447.23 | 0.00 | 0.00 | 0.157745E+09 | 0.00 | 0.91 |
Maximum of Months | 0.174058E+10 | 0.788006E+09 | 0.00 | 88328088.54 | 594978.01 | 0.394245E+10 | 0.239356E+10 | 0.00 | 1.64 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.312503E+10 | 0.00 | 0.00 | 3463458.68 | 0.00 | 0.115951E+10 | 0.333710E+09 | 0.00 | 0.83 |
February | 0.162148E+10 | 0.00 | 0.00 | 13265266.29 | 0.00 | 0.142733E+10 | 0.109696E+10 | 0.00 | 0.88 |
March | 0.143569E+10 | 0.00 | 0.00 | 48527615.05 | 0.00 | 0.00 | 0.247447E+10 | 0.00 | 0.99 |
April | 0.613300E+09 | 29288501.53 | 0.00 | 86582451.85 | 50038.75 | 0.00 | 0.320214E+10 | 0.00 | 1.10 |
May | 16139706.43 | 20854664.84 | 0.00 | 0.140592E+09 | 851768.99 | 0.00 | 0.400135E+10 | 0.00 | 1.21 |
June | 10736972.93 | 0.345699E+09 | 0.00 | 0.116941E+09 | 926443.92 | 0.00 | 0.241241E+10 | 0.00 | 1.24 |
July | 6456131.90 | 0.588650E+09 | 0.00 | 94631423.89 | 401921.57 | 0.00 | 0.158590E+10 | 0.00 | 1.25 |
August | 302085.45 | 0.565011E+09 | 0.00 | 0.129924E+09 | 859716.03 | 0.00 | 0.213847E+10 | 0.00 | 1.26 |
September | 3191166.26 | 24353022.81 | 0.00 | 0.167437E+09 | 0.00 | 0.00 | 0.358508E+10 | 0.00 | 1.25 |
October | 47741774.32 | 0.00 | 0.00 | 0.140683E+09 | 0.00 | 0.00 | 0.461008E+10 | 0.00 | 1.20 |
November | 0.143514E+10 | 0.00 | 0.00 | 62325882.08 | 0.00 | 0.105750E+09 | 0.251347E+10 | 0.00 | 1.00 |
December | 0.278601E+10 | 0.00 | 0.00 | 8834062.51 | 0.00 | 1177611.66 | 0.911738E+09 | 0.00 | 0.85 |
Annual Sum or Average | 0.111012E+11 | 0.157386E+10 | 0.00 | 0.101321E+10 | 3089889.26 | 0.269376E+10 | 0.288658E+11 | 0.00 | 1.09 |
Minimum of Months | 302085.45 | 0.00 | 0.00 | 3463458.68 | 0.00 | 0.00 | 0.333710E+09 | 0.00 | 0.83 |
Maximum of Months | 0.312503E+10 | 0.588650E+09 | 0.00 | 0.167437E+09 | 926443.92 | 0.142733E+10 | 0.461008E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 45960509.59 | 0.00 | 0.00 | 132694.24 | 0.00 | 0.947885E+09 | 21010809.95 | 0.00 | 0.05 |
February | 30503297.24 | 0.00 | 0.00 | 1325334.59 | 0.00 | 0.124872E+10 | 0.183284E+09 | 0.00 | 0.09 |
March | 27886242.76 | 0.00 | 0.00 | 14734315.95 | 0.00 | 0.00 | 0.117734E+10 | 0.00 | 0.14 |
April | 8023209.91 | 24339412.79 | 0.00 | 35057959.02 | 0.00 | 0.00 | 0.211931E+10 | 0.00 | 0.29 |
May | 2165.90 | 20456590.48 | 0.00 | 79572307.15 | 0.00 | 0.00 | 0.344315E+10 | 0.00 | 0.48 |
June | 953.53 | 0.342178E+09 | 0.00 | 84770814.06 | 0.00 | 0.00 | 0.223071E+10 | 0.00 | 0.55 |
July | 0.00 | 0.582251E+09 | 0.00 | 72025900.48 | 0.00 | 0.00 | 0.149901E+10 | 0.00 | 0.56 |
August | 0.00 | 0.561599E+09 | 0.00 | 97007453.79 | 0.00 | 0.00 | 0.208811E+10 | 0.00 | 0.57 |
September | 0.00 | 24240065.96 | 0.00 | 0.103106E+09 | 0.00 | 0.00 | 0.322524E+10 | 0.00 | 0.53 |
October | 0.00 | 0.00 | 0.00 | 58598092.85 | 0.00 | 0.00 | 0.345700E+10 | 0.00 | 0.41 |
November | 25004428.68 | 0.00 | 0.00 | 25059501.33 | 0.00 | 527902.77 | 0.163513E+10 | 0.00 | 0.20 |
December | 50119510.16 | 0.00 | 0.00 | 529975.71 | 0.00 | 31558934.92 | 83779736.62 | 0.00 | 0.02 |
Annual Sum or Average | 0.187500E+09 | 0.155506E+10 | 0.00 | 0.571920E+09 | 0.00 | 0.222869E+10 | 0.211631E+11 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 132694.24 | 0.00 | 0.00 | 21010809.95 | 0.00 | 0.02 |
Maximum of Months | 50119510.16 | 0.582251E+09 | 0.00 | 0.103106E+09 | 0.00 | 0.124872E+10 | 0.345700E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.537662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232662E+10 | 0.00 | 0.00 | 0.42 |
February | 0.123665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121155E+10 | 0.00 | 0.00 | 0.42 |
March | 0.195622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92829176.45 | 0.00 | 0.00 | 0.42 |
April | 0.183870E+10 | 0.00 | 0.00 | 0.00 | 12806582.89 | 0.00 | 0.00 | 0.00 | 0.42 |
May | 0.177329E+10 | 23694.17 | 0.00 | 532151.09 | 11191146.98 | 0.00 | 11850343.29 | 0.00 | 0.43 |
June | 0.966094E+09 | 80605867.08 | 0.00 | 6974430.22 | 70571838.79 | 0.00 | 0.109787E+09 | 0.00 | 0.44 |
July | 0.578111E+09 | 0.114221E+09 | 0.00 | 7407759.14 | 0.142120E+09 | 0.00 | 0.126104E+09 | 0.00 | 0.44 |
August | 0.694119E+09 | 0.125707E+09 | 0.00 | 7691613.10 | 0.119691E+09 | 0.00 | 0.242782E+09 | 0.00 | 0.44 |
September | 0.141392E+10 | 5864063.49 | 0.00 | 9344876.35 | 4431553.53 | 0.00 | 0.165327E+09 | 0.00 | 0.43 |
October | 0.205229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
November | 0.169504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427510E+09 | 0.00 | 0.00 | 0.42 |
December | 0.136408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845945E+09 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.161062E+11 | 0.326422E+09 | 0.00 | 31950829.90 | 0.360811E+09 | 0.490445E+10 | 0.655851E+09 | 0.00 | 0.43 |
Minimum of Months | 0.537662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.205229E+10 | 0.125707E+09 | 0.00 | 9344876.35 | 0.142120E+09 | 0.232662E+10 | 0.242782E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.117258E+10 | 0.00 | 0.00 | 0.846092E+11 | 0.00 | 17.48 |
February | 0.00 | 0.00 | 0.00 | 0.109098E+10 | 0.00 | 0.00 | 0.689521E+11 | 0.00 | 17.57 |
March | 0.00 | 0.00 | 0.00 | 0.133464E+10 | 0.00 | 0.00 | 0.759542E+11 | 0.00 | 19.55 |
April | 0.00 | 0.404105E+09 | 0.00 | 0.125339E+10 | 0.00 | 0.00 | 0.676809E+11 | 0.00 | 19.34 |
May | 0.00 | 0.342144E+09 | 0.00 | 0.126041E+10 | 0.00 | 0.00 | 0.632525E+11 | 0.00 | 18.81 |
June | 0.00 | 0.494891E+10 | 0.00 | 0.907469E+09 | 0.00 | 0.00 | 0.370771E+11 | 0.00 | 18.10 |
July | 0.00 | 0.850011E+10 | 0.00 | 0.692285E+09 | 0.00 | 0.00 | 0.229676E+11 | 0.00 | 17.68 |
August | 0.00 | 0.822087E+10 | 0.00 | 0.869857E+09 | 0.00 | 0.00 | 0.316200E+11 | 0.00 | 17.92 |
September | 0.00 | 0.340009E+09 | 0.00 | 0.122479E+10 | 0.00 | 0.00 | 0.561976E+11 | 0.00 | 18.67 |
October | 0.00 | 0.00 | 0.00 | 0.139890E+10 | 0.00 | 0.00 | 0.763578E+11 | 0.00 | 19.59 |
November | 0.00 | 0.00 | 0.00 | 0.127502E+10 | 0.00 | 0.00 | 0.760131E+11 | 0.00 | 19.25 |
December | 0.00 | 0.00 | 0.00 | 0.125932E+10 | 0.00 | 0.00 | 0.812699E+11 | 0.00 | 19.12 |
Annual Sum or Average | 0.00 | 0.227562E+11 | 0.00 | 0.137396E+11 | 0.00 | 0.00 | 0.741952E+12 | 0.00 | 18.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.692285E+09 | 0.00 | 0.00 | 0.229676E+11 | 0.00 | 17.48 |
Maximum of Months | 0.00 | 0.850011E+10 | 0.00 | 0.139890E+10 | 0.00 | 0.00 | 0.846092E+11 | 0.00 | 19.59 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201985E+11 | 0.00 | 0.00 | 29971138.31 | 0.00 | 0.116018E+11 | 0.210993E+10 | 0.00 | 2.49 |
February | 0.132874E+11 | 0.00 | 0.00 | 89343307.02 | 0.00 | 0.981882E+10 | 0.638357E+10 | 0.00 | 2.57 |
March | 0.123351E+11 | 0.00 | 0.00 | 0.180717E+09 | 0.00 | 941953.50 | 0.135631E+11 | 0.00 | 2.71 |
April | 0.774753E+10 | 0.182820E+09 | 0.00 | 0.270458E+09 | 3648949.01 | 0.00 | 0.163613E+11 | 0.00 | 2.84 |
May | 0.322988E+10 | 0.125815E+09 | 0.00 | 0.372161E+09 | 20493069.86 | 0.00 | 0.210408E+11 | 0.00 | 2.98 |
June | 0.172949E+10 | 0.196621E+10 | 0.00 | 0.331325E+09 | 0.153831E+09 | 0.00 | 0.130173E+11 | 0.00 | 3.05 |
July | 0.644995E+09 | 0.324461E+10 | 0.00 | 0.280980E+09 | 0.316035E+09 | 0.00 | 0.914648E+10 | 0.00 | 3.09 |
August | 0.579160E+09 | 0.315705E+10 | 0.00 | 0.398309E+09 | 0.308763E+09 | 0.00 | 0.125398E+11 | 0.00 | 3.12 |
September | 0.237859E+10 | 0.136001E+09 | 0.00 | 0.564063E+09 | 11464493.37 | 0.00 | 0.194914E+11 | 0.00 | 3.08 |
October | 0.452538E+10 | 0.00 | 0.00 | 0.534952E+09 | 0.00 | 0.00 | 0.235263E+11 | 0.00 | 2.96 |
November | 0.128955E+11 | 0.00 | 0.00 | 0.214738E+09 | 0.00 | 0.181103E+10 | 0.119168E+11 | 0.00 | 2.68 |
December | 0.191368E+11 | 0.00 | 0.00 | 76845001.54 | 0.00 | 0.263191E+10 | 0.471925E+10 | 0.00 | 2.53 |
Annual Sum or Average | 0.986883E+11 | 0.881251E+10 | 0.00 | 0.334386E+10 | 0.814235E+09 | 0.258645E+11 | 0.153816E+12 | 0.00 | 2.84 |
Minimum of Months | 0.579160E+09 | 0.00 | 0.00 | 29971138.31 | 0.00 | 0.00 | 0.210993E+10 | 0.00 | 2.49 |
Maximum of Months | 0.201985E+11 | 0.324461E+10 | 0.00 | 0.564063E+09 | 0.316035E+09 | 0.116018E+11 | 0.235263E+11 | 0.00 | 3.12 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.559649E+11 | 0.00 | 0.00 | 0.307758E+09 | 0.00 | 0.170575E+11 | 0.264494E+11 | 0.00 | 1.08 |
February | 0.204326E+11 | 0.00 | 0.00 | 0.876606E+09 | 0.00 | 0.263198E+11 | 0.454398E+11 | 0.00 | 1.20 |
March | 0.123453E+11 | 0.00 | 0.00 | 0.197545E+10 | 0.00 | 0.00 | 0.751382E+11 | 0.00 | 1.34 |
April | 0.525531E+10 | 0.604784E+09 | 0.00 | 0.265062E+10 | 1032482.42 | 0.00 | 0.762358E+11 | 0.00 | 1.41 |
May | 0.242267E+09 | 0.433367E+09 | 0.00 | 0.346416E+10 | 15177436.89 | 0.00 | 0.806652E+11 | 0.00 | 1.46 |
June | 0.122818E+09 | 0.692156E+10 | 0.00 | 0.270212E+10 | 54518472.67 | 0.00 | 0.484715E+11 | 0.00 | 1.49 |
July | 0.236835E+09 | 0.116962E+11 | 0.00 | 0.207548E+10 | 37186974.35 | 0.00 | 0.316358E+11 | 0.00 | 1.49 |
August | 17956848.75 | 0.113110E+11 | 0.00 | 0.282234E+10 | 75820000.42 | 0.00 | 0.426884E+11 | 0.00 | 1.51 |
September | 53169408.48 | 0.486837E+09 | 0.00 | 0.391039E+10 | 0.00 | 0.00 | 0.723755E+11 | 0.00 | 1.51 |
October | 31470745.93 | 0.00 | 0.00 | 0.416145E+10 | 0.00 | 0.00 | 0.948304E+11 | 0.00 | 1.48 |
November | 0.166607E+11 | 0.00 | 0.00 | 0.219471E+10 | 0.00 | 0.137631E+10 | 0.707626E+11 | 0.00 | 1.32 |
December | 0.338082E+11 | 0.00 | 0.00 | 0.749987E+09 | 0.00 | 0.00 | 0.517906E+11 | 0.00 | 1.19 |
Annual Sum or Average | 0.145172E+12 | 0.314537E+11 | 0.00 | 0.278911E+11 | 0.183735E+09 | 0.447536E+11 | 0.716483E+12 | 0.00 | 1.37 |
Minimum of Months | 17956848.75 | 0.00 | 0.00 | 0.307758E+09 | 0.00 | 0.00 | 0.264494E+11 | 0.00 | 1.08 |
Maximum of Months | 0.559649E+11 | 0.116962E+11 | 0.00 | 0.416145E+10 | 75820000.42 | 0.263198E+11 | 0.948304E+11 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17769775.63 | 0.00 | 0.00 | 48689.25 | 0.00 | 0.250934E+10 | 2815747.87 | 0.00 | 0.34 |
February | 35307777.16 | 0.00 | 0.00 | 1279566.70 | 0.00 | 0.209358E+10 | 28572131.85 | 0.00 | 0.34 |
March | 76215164.69 | 0.00 | 0.00 | 5044568.91 | 0.00 | 0.128397E+10 | 0.188032E+09 | 0.00 | 0.34 |
April | 72987961.95 | 18223034.11 | 0.00 | 18851448.91 | 0.00 | 0.788614E+09 | 0.425424E+09 | 0.00 | 0.34 |
May | 53519390.71 | 17196629.10 | 23640.43 | 37574618.23 | 1778793.02 | 0.177618E+09 | 0.775349E+09 | 2545.18 | 0.34 |
June | 21539632.88 | 0.264986E+09 | 39312.88 | 31779359.14 | 1144683.42 | 77270319.55 | 0.377593E+09 | 8984.13 | 0.34 |
July | 4120460.05 | 0.425350E+09 | 45606.72 | 26157708.51 | 857909.53 | 435592.55 | 0.186854E+09 | 19160.54 | 0.34 |
August | 2117601.69 | 0.292356E+09 | 94499.89 | 37667752.18 | 4701132.32 | 460973.38 | 0.317981E+09 | 11459.44 | 0.34 |
September | 40008106.70 | 48154662.69 | 560.56 | 34245872.81 | 74819.39 | 0.267612E+09 | 0.572249E+09 | 2799.05 | 0.34 |
October | 81516900.16 | 0.00 | 0.00 | 13913982.75 | 0.00 | 0.922656E+09 | 0.435174E+09 | 0.00 | 0.34 |
November | 59049948.20 | 0.00 | 0.00 | 2542481.21 | 0.00 | 0.141707E+10 | 0.148913E+09 | 0.00 | 0.34 |
December | 37332993.20 | 0.00 | 0.00 | 63625.76 | 0.00 | 0.170430E+10 | 3310212.05 | 0.00 | 0.34 |
Annual Sum or Average | 0.501486E+09 | 0.106627E+10 | 203620.48 | 0.209170E+09 | 8557337.69 | 0.112429E+11 | 0.346226E+10 | 44948.35 | 0.34 |
Minimum of Months | 2117601.69 | 0.00 | 0.00 | 48689.25 | 0.00 | 435592.55 | 2815747.87 | 0.00 | 0.34 |
Maximum of Months | 81516900.16 | 0.425350E+09 | 94499.89 | 37667752.18 | 4701132.32 | 0.250934E+10 | 0.775349E+09 | 19160.54 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2256380.07 | 0.00 | 0.00 | 4350.83 | 0.00 | 0.252717E+10 | 549552.75 | 0.00 | 0.34 |
February | 10322341.47 | 0.00 | 0.00 | 418525.65 | 0.00 | 0.213096E+10 | 17043106.15 | 0.00 | 0.34 |
March | 58324100.92 | 0.00 | 0.00 | 2073142.30 | 0.00 | 0.139484E+10 | 98025498.57 | 0.00 | 0.34 |
April | 98288971.85 | 15301810.70 | 1424.12 | 13169219.94 | 2914529.96 | 0.833992E+09 | 0.360427E+09 | 5269.33 | 0.34 |
May | 0.144723E+09 | 12518670.57 | 5166.88 | 26004304.98 | 6472425.01 | 0.180958E+09 | 0.692375E+09 | 5345.29 | 0.34 |
June | 87913650.23 | 0.237014E+09 | 83910.67 | 19999215.59 | 29069703.83 | 80174882.77 | 0.320095E+09 | 11267.62 | 0.34 |
July | 69822334.50 | 0.361799E+09 | 114193.17 | 15710445.69 | 64348450.84 | 262061.53 | 0.131773E+09 | 11653.64 | 0.34 |
August | 99757715.15 | 0.251534E+09 | 126804.94 | 23284070.26 | 45484776.22 | 407572.40 | 0.234778E+09 | 17575.94 | 0.34 |
September | 0.124382E+09 | 45170959.50 | 3771.26 | 19579790.55 | 3054295.56 | 0.301893E+09 | 0.468260E+09 | 3815.37 | 0.34 |
October | 0.101595E+09 | 0.00 | 0.00 | 5671228.16 | 0.00 | 0.105430E+10 | 0.291696E+09 | 0.00 | 0.34 |
November | 44458417.20 | 0.00 | 0.00 | 1109496.38 | 0.00 | 0.151811E+10 | 63898886.95 | 0.00 | 0.34 |
December | 4560682.95 | 0.00 | 0.00 | 11129.70 | 0.00 | 0.173958E+10 | 851706.45 | 0.00 | 0.34 |
Annual Sum or Average | 0.846405E+09 | 0.923338E+09 | 335271.03 | 0.127035E+09 | 0.151344E+09 | 0.117626E+11 | 0.267977E+10 | 54927.20 | 0.34 |
Minimum of Months | 2256380.07 | 0.00 | 0.00 | 4350.83 | 0.00 | 262061.53 | 549552.75 | 0.00 | 0.34 |
Maximum of Months | 0.144723E+09 | 0.361799E+09 | 126804.94 | 26004304.98 | 64348450.84 | 0.252717E+10 | 0.692375E+09 | 17575.94 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296027E+09 | 0.00 | 0.00 | 0.02 |
February | 0.149969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.116613E+10 | 0.00 | 0.00 | 1863257.68 | 0.00 | 27393823.80 | 0.173984E+09 | 0.00 | 0.02 |
April | 0.130049E+10 | 42936241.62 | 0.00 | 2720750.42 | 0.00 | 0.00 | 0.121964E+09 | 0.00 | 0.02 |
May | 0.115525E+10 | 44465828.07 | 0.00 | 1609022.58 | 694673.54 | 0.00 | 92796927.03 | 0.00 | 0.02 |
June | 0.512308E+09 | 0.239744E+09 | 0.00 | 1963897.72 | 49175307.80 | 0.00 | 0.103366E+09 | 0.00 | 0.02 |
July | 76858826.59 | 0.440421E+09 | 0.00 | 4385331.61 | 3924061.12 | 0.00 | 85901919.14 | 0.00 | 0.02 |
August | 1336703.91 | 0.340092E+09 | 0.00 | 8930868.14 | 42236718.76 | 0.00 | 0.141696E+09 | 0.00 | 0.02 |
September | 0.564724E+09 | 45487787.28 | 0.00 | 14115561.97 | 0.00 | 0.00 | 0.437525E+09 | 0.00 | 0.02 |
October | 0.951894E+09 | 0.00 | 0.00 | 23306726.83 | 0.00 | 0.00 | 0.905903E+09 | 0.00 | 0.02 |
November | 0.127498E+10 | 0.00 | 0.00 | 6104626.44 | 0.00 | 59365699.20 | 0.230832E+09 | 0.00 | 0.02 |
December | 0.893160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258651E+09 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.104514E+11 | 0.115315E+10 | 0.00 | 65000043.40 | 96030761.22 | 0.641437E+09 | 0.229397E+10 | 0.00 | 0.02 |
Minimum of Months | 1336703.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.149969E+10 | 0.440421E+09 | 0.00 | 23306726.83 | 49175307.80 | 0.296027E+09 | 0.905903E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.575879E+09 | 0.00 | 0.00 | 1192376.48 | 0.00 | 0.334116E+11 | 0.311732E+09 | 0.00 | 0.39 |
February | 0.780604E+09 | 0.00 | 0.00 | 9117822.75 | 0.00 | 0.265363E+11 | 0.194135E+10 | 0.00 | 0.39 |
March | 0.125018E+10 | 0.00 | 0.00 | 89937967.35 | 0.00 | 0.115906E+11 | 0.812777E+10 | 0.00 | 0.39 |
April | 0.143910E+10 | 0.182058E+09 | 0.00 | 0.214551E+09 | 65002867.39 | 0.368681E+10 | 0.123641E+11 | 0.00 | 0.39 |
May | 0.196298E+10 | 0.152010E+09 | 0.00 | 0.463901E+09 | 0.105606E+09 | 14660387.24 | 0.117134E+11 | 0.00 | 0.39 |
June | 0.120628E+10 | 0.299532E+10 | 68781.08 | 0.300281E+09 | 0.613352E+09 | 5620205.70 | 0.537755E+10 | 2850.06 | 0.39 |
July | 0.950263E+09 | 0.458018E+10 | 101236.59 | 0.189207E+09 | 0.119893E+10 | 1169514.24 | 0.180905E+10 | 16056.72 | 0.39 |
August | 0.136750E+10 | 0.314364E+10 | 526556.37 | 0.275520E+09 | 0.884644E+09 | 1650057.38 | 0.321202E+10 | 3837.84 | 0.39 |
September | 0.169002E+10 | 0.567449E+09 | 42885.41 | 0.347607E+09 | 86397142.30 | 46788076.10 | 0.103088E+11 | 31868.06 | 0.39 |
October | 0.137738E+10 | 0.00 | 0.00 | 0.225311E+09 | 0.00 | 0.155510E+10 | 0.165449E+11 | 0.00 | 0.39 |
November | 0.103351E+10 | 0.00 | 0.00 | 94580171.89 | 0.00 | 0.134874E+11 | 0.745059E+10 | 0.00 | 0.39 |
December | 0.940468E+09 | 0.00 | 0.00 | 1274074.75 | 0.00 | 0.223509E+11 | 0.365431E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.145742E+11 | 0.116207E+11 | 739459.45 | 0.221248E+10 | 0.295394E+10 | 0.112689E+12 | 0.795267E+11 | 54612.67 | 0.39 |
Minimum of Months | 0.575879E+09 | 0.00 | 0.00 | 1192376.48 | 0.00 | 1169514.24 | 0.311732E+09 | 0.00 | 0.38 |
Maximum of Months | 0.196298E+10 | 0.458018E+10 | 526556.37 | 0.463901E+09 | 0.119893E+10 | 0.334116E+11 | 0.165449E+11 | 31868.06 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 18356897.34 | 0.00 | 0.00 | 15939.14 | 0.00 | 0.251100E+10 | 607434.49 | 0.00 | 0.34 |
February | 34044101.97 | 0.00 | 0.00 | 803434.66 | 0.00 | 0.209824E+10 | 25656669.66 | 0.00 | 0.34 |
March | 76109034.33 | 0.00 | 0.00 | 4482908.92 | 0.00 | 0.127261E+10 | 0.200060E+09 | 0.00 | 0.34 |
April | 67826571.49 | 18213317.79 | 8508.23 | 15724328.56 | 0.00 | 0.801967E+09 | 0.420360E+09 | 1208.09 | 0.34 |
May | 47140266.61 | 18948197.07 | 40553.21 | 40947561.52 | 10173.21 | 0.138287E+09 | 0.817686E+09 | 2684.26 | 0.34 |
June | 17844453.66 | 0.264991E+09 | 60165.20 | 31588417.81 | 1125538.39 | 61138268.46 | 0.397611E+09 | 2227.41 | 0.34 |
July | 2285843.40 | 0.425763E+09 | 34273.87 | 25358995.79 | 469715.46 | 374038.68 | 0.189549E+09 | 6241.86 | 0.34 |
August | 0.00 | 0.292567E+09 | 74929.98 | 34860754.47 | 4514661.10 | 542207.48 | 0.322824E+09 | 6204.22 | 0.34 |
September | 33001222.22 | 48197152.48 | 707.13 | 35010031.45 | 34093.92 | 0.246658E+09 | 0.599446E+09 | 888.17 | 0.34 |
October | 76324169.58 | 0.00 | 0.00 | 12301862.90 | 0.00 | 0.922394E+09 | 0.442241E+09 | 0.00 | 0.34 |
November | 55675704.90 | 0.00 | 0.00 | 2233008.58 | 0.00 | 0.141140E+10 | 0.158274E+09 | 0.00 | 0.34 |
December | 37313019.65 | 0.00 | 0.00 | 161199.66 | 0.00 | 0.169761E+10 | 9921607.08 | 0.00 | 0.34 |
Annual Sum or Average | 0.465921E+09 | 0.106868E+10 | 219137.63 | 0.203488E+09 | 6154182.08 | 0.111622E+11 | 0.358424E+10 | 19454.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 15939.14 | 0.00 | 374038.68 | 607434.49 | 0.00 | 0.34 |
Maximum of Months | 76324169.58 | 0.425763E+09 | 74929.98 | 40947561.52 | 4514661.10 | 0.251100E+10 | 0.817686E+09 | 6241.86 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2296582.65 | 0.00 | 0.00 | 5983.38 | 0.00 | 0.252736E+10 | 319654.55 | 0.00 | 0.34 |
February | 14879087.65 | 0.00 | 0.00 | 179647.31 | 0.00 | 0.213204E+10 | 11645802.75 | 0.00 | 0.34 |
March | 73616772.20 | 0.00 | 0.00 | 1983890.84 | 0.00 | 0.136543E+10 | 0.112233E+09 | 0.00 | 0.34 |
April | 98055105.30 | 16152561.99 | 35689.49 | 10618628.75 | 2030736.15 | 0.870759E+09 | 0.326445E+09 | 4046.49 | 0.34 |
May | 0.141247E+09 | 14228583.73 | 9128.17 | 30986640.73 | 4763707.65 | 0.146937E+09 | 0.724890E+09 | 188.19 | 0.34 |
June | 84092793.14 | 0.237043E+09 | 81362.58 | 21344974.61 | 29050558.79 | 62172227.54 | 0.340572E+09 | 4084.71 | 0.34 |
July | 67147249.98 | 0.362054E+09 | 65385.57 | 15446237.08 | 64150866.40 | 178748.20 | 0.134795E+09 | 2366.47 | 0.34 |
August | 96610660.51 | 0.251820E+09 | 107774.39 | 20720116.60 | 45224906.69 | 570034.57 | 0.240326E+09 | 10203.27 | 0.34 |
September | 0.120482E+09 | 45345119.33 | 19005.29 | 21290017.50 | 2867070.17 | 0.304042E+09 | 0.468301E+09 | 1646.90 | 0.34 |
October | 0.102018E+09 | 0.00 | 0.00 | 3957956.39 | 0.00 | 0.106351E+10 | 0.283777E+09 | 0.00 | 0.34 |
November | 43052937.56 | 0.00 | 0.00 | 421540.89 | 0.00 | 0.153416E+10 | 49945998.91 | 0.00 | 0.34 |
December | 5005913.30 | 0.00 | 0.00 | 13868.21 | 0.00 | 0.173943E+10 | 551679.69 | 0.00 | 0.34 |
Annual Sum or Average | 0.848503E+09 | 0.926644E+09 | 318345.49 | 0.126970E+09 | 0.148088E+09 | 0.117466E+11 | 0.269380E+10 | 22536.03 | 0.34 |
Minimum of Months | 2296582.65 | 0.00 | 0.00 | 5983.38 | 0.00 | 178748.20 | 319654.55 | 0.00 | 0.34 |
Maximum of Months | 0.141247E+09 | 0.362054E+09 | 107774.39 | 30986640.73 | 64150866.40 | 0.252736E+10 | 0.724890E+09 | 10203.27 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236175E+11 | 0.00 | 0.00 | 0.27 |
February | 0.435256E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197515E+11 | 0.00 | 0.00 | 0.27 |
March | 0.383301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130624E+11 | 0.00 | 0.00 | 0.27 |
April | 0.761074E+10 | 0.00 | 0.00 | 0.00 | 0.105597E+09 | 0.755028E+10 | 0.00 | 0.00 | 0.28 |
May | 0.142621E+11 | 0.00 | 0.00 | 0.00 | 92472291.28 | 0.461769E+09 | 0.00 | 0.00 | 0.28 |
June | 0.892871E+10 | 0.00 | 0.00 | 0.00 | 0.124654E+10 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.586771E+10 | 0.00 | 0.00 | 0.00 | 0.211367E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.778867E+10 | 0.00 | 0.00 | 0.00 | 0.202343E+10 | 0.00 | 0.00 | 0.00 | 0.29 |
September | 0.118778E+11 | 0.00 | 0.00 | 0.00 | 84892802.57 | 0.122098E+10 | 0.00 | 0.00 | 0.28 |
October | 0.100157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690653E+10 | 0.00 | 0.00 | 0.27 |
November | 0.355675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139448E+11 | 0.00 | 0.00 | 0.27 |
December | 0.166590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180562E+11 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.743430E+11 | 0.00 | 0.00 | 0.00 | 0.566660E+10 | 0.104572E+12 | 0.00 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.142621E+11 | 0.00 | 0.00 | 0.00 | 0.211367E+10 | 0.236175E+11 | 0.00 | 0.00 | 0.29 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2691915.80 | 0.00 | 0.00 | 12765.30 | 0.00 | 0.629411E+09 | 378525.66 | 0.00 | 0.34 |
February | 6124678.56 | 0.00 | 0.00 | 350573.86 | 0.00 | 0.527215E+09 | 5995577.25 | 0.00 | 0.34 |
March | 17410855.94 | 0.00 | 0.00 | 1143821.44 | 0.00 | 0.338118E+09 | 31641849.71 | 0.00 | 0.34 |
April | 16856735.02 | 4555758.53 | 0.00 | 4900996.18 | 0.00 | 0.207792E+09 | 96919660.86 | 0.00 | 0.34 |
May | 12292538.76 | 4749479.99 | 29.04 | 9919314.20 | 490.16 | 65913270.83 | 0.172890E+09 | 402.74 | 0.34 |
June | 4355115.23 | 66255761.30 | 6123.28 | 8333212.29 | 281384.60 | 28800180.07 | 85557083.35 | 1520.52 | 0.34 |
July | 533801.88 | 0.106503E+09 | 10630.48 | 6516451.35 | 50778.11 | 97895.67 | 47243728.88 | 3998.75 | 0.34 |
August | 84677.47 | 73374911.83 | 11352.35 | 9256468.87 | 902369.31 | 235051.02 | 79980530.35 | 2067.98 | 0.34 |
September | 8636487.59 | 12057370.52 | 247.03 | 8240541.73 | 0.00 | 90841519.59 | 0.120810E+09 | 592.87 | 0.34 |
October | 20578927.53 | 0.00 | 0.00 | 3374260.49 | 0.00 | 0.256008E+09 | 83354321.14 | 0.00 | 0.34 |
November | 12331065.29 | 0.00 | 0.00 | 568460.20 | 0.00 | 0.379498E+09 | 14497007.70 | 0.00 | 0.34 |
December | 7207586.47 | 0.00 | 0.00 | 11894.71 | 0.00 | 0.428710E+09 | 321916.37 | 0.00 | 0.34 |
Annual Sum or Average | 0.109104E+09 | 0.267496E+09 | 28382.19 | 52628760.62 | 1235022.18 | 0.295264E+10 | 0.739590E+09 | 8582.86 | 0.34 |
Minimum of Months | 84677.47 | 0.00 | 0.00 | 11894.71 | 0.00 | 97895.67 | 321916.37 | 0.00 | 0.34 |
Maximum of Months | 20578927.53 | 0.106503E+09 | 11352.35 | 9919314.20 | 902369.31 | 0.629411E+09 | 0.172890E+09 | 3998.75 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 1433.02 | 0.00 | 0.632474E+09 | 19514.03 | 0.00 | 0.34 |
February | 1341314.39 | 0.00 | 0.00 | 81381.47 | 0.00 | 0.534225E+09 | 4037916.97 | 0.00 | 0.34 |
March | 12561607.77 | 0.00 | 0.00 | 408419.38 | 0.00 | 0.355325E+09 | 20019475.52 | 0.00 | 0.34 |
April | 23621558.19 | 4046601.33 | 346.89 | 3458096.13 | 507684.04 | 0.220146E+09 | 79243596.93 | 1126.27 | 0.34 |
May | 35553659.72 | 3570211.42 | 170.07 | 7218378.17 | 1179035.11 | 62434582.08 | 0.155809E+09 | 985.33 | 0.34 |
June | 20871944.62 | 59290798.66 | 13876.47 | 5592290.01 | 7238329.68 | 29379453.72 | 71201902.59 | 1784.89 | 0.34 |
July | 16751757.77 | 90599309.82 | 14133.34 | 4206260.79 | 15953406.35 | 66050.74 | 33367808.48 | 1394.29 | 0.34 |
August | 23983635.44 | 63994733.97 | 14858.54 | 6265806.48 | 10277318.71 | 85218.30 | 59222067.49 | 3790.26 | 0.34 |
September | 30860053.40 | 11350011.32 | 1357.84 | 4734114.99 | 705980.54 | 95255681.93 | 97678841.83 | 860.71 | 0.34 |
October | 24893610.02 | 0.00 | 0.00 | 1235240.29 | 0.00 | 0.288457E+09 | 48729564.33 | 0.00 | 0.34 |
November | 9024508.14 | 0.00 | 0.00 | 226952.27 | 0.00 | 0.392086E+09 | 5556833.37 | 0.00 | 0.34 |
December | 104366.03 | 0.00 | 0.00 | 1068.52 | 0.00 | 0.436125E+09 | 21088.08 | 0.00 | 0.34 |
Annual Sum or Average | 0.199568E+09 | 0.232852E+09 | 44743.16 | 33429441.52 | 35861754.43 | 0.304606E+10 | 0.574907E+09 | 9941.75 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1068.52 | 0.00 | 66050.74 | 19514.03 | 0.00 | 0.34 |
Maximum of Months | 35553659.72 | 90599309.82 | 14858.54 | 7218378.17 | 15953406.35 | 0.632474E+09 | 0.155809E+09 | 3790.26 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101100E+09 | 0.00 | 0.00 | 3727905.52 | 0.00 | 0.380809E+10 | 0.148971E+09 | 0.00 | 0.39 |
February | 0.132769E+09 | 0.00 | 0.00 | 8631784.68 | 0.00 | 0.305438E+10 | 0.270089E+09 | 0.00 | 0.39 |
March | 74476502.15 | 0.00 | 0.00 | 17403228.16 | 0.00 | 0.177531E+10 | 0.626575E+09 | 0.00 | 0.39 |
April | 74462507.29 | 29257159.54 | 0.00 | 29145067.14 | 0.00 | 0.110004E+10 | 0.892943E+09 | 0.00 | 0.39 |
May | 59664302.54 | 30503940.52 | 2427.97 | 58879674.36 | 0.00 | 0.171257E+09 | 0.138644E+10 | 794.35 | 0.39 |
June | 28578887.09 | 0.425476E+09 | 9729.52 | 42313283.97 | 1863600.66 | 38607260.59 | 0.706390E+09 | 2341.89 | 0.39 |
July | 3555401.46 | 0.682239E+09 | 57856.59 | 31794190.03 | 2081158.56 | 592497.62 | 0.313363E+09 | 5168.80 | 0.39 |
August | 485501.70 | 0.470107E+09 | 76150.67 | 50022361.00 | 6910211.44 | 3232614.96 | 0.521394E+09 | 2328.92 | 0.39 |
September | 29502818.39 | 77429990.92 | 6613.16 | 60489173.10 | 0.00 | 0.226996E+09 | 0.115063E+10 | 1430.42 | 0.39 |
October | 57317291.03 | 0.00 | 0.00 | 51290240.53 | 0.00 | 0.763606E+09 | 0.146100E+10 | 0.00 | 0.39 |
November | 72504491.54 | 0.00 | 0.00 | 18122148.00 | 0.00 | 0.185732E+10 | 0.665137E+09 | 0.00 | 0.39 |
December | 37419564.80 | 0.00 | 0.00 | 7781949.95 | 0.00 | 0.254990E+10 | 0.206514E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.671836E+09 | 0.171501E+10 | 152777.90 | 0.379601E+09 | 10854970.65 | 0.153493E+11 | 0.834945E+10 | 12064.38 | 0.39 |
Minimum of Months | 485501.70 | 0.00 | 0.00 | 3727905.52 | 0.00 | 592497.62 | 0.148971E+09 | 0.00 | 0.38 |
Maximum of Months | 0.132769E+09 | 0.682239E+09 | 76150.67 | 60489173.10 | 6910211.44 | 0.380809E+10 | 0.146100E+10 | 5168.80 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.158260E+11 | 0.00 | 0.00 | 0.584706E+09 | 0.00 | 0.120233E+11 | 0.347128E+11 | 0.00 | 3.50 |
February | 0.459090E+10 | 0.00 | 0.00 | 0.805321E+09 | 0.00 | 0.163612E+11 | 0.328219E+11 | 0.00 | 3.57 |
March | 0.493031E+09 | 0.00 | 0.00 | 0.143328E+10 | 0.00 | 0.00 | 0.465710E+11 | 0.00 | 3.75 |
April | 0.00 | 0.305431E+09 | 0.00 | 0.168612E+10 | 0.00 | 0.00 | 0.423025E+11 | 0.00 | 3.82 |
May | 0.00 | 0.264911E+09 | 0.00 | 0.187570E+10 | 0.00 | 0.00 | 0.408832E+11 | 0.00 | 3.90 |
June | 0.00 | 0.360791E+10 | 0.00 | 0.138706E+10 | 0.00 | 0.00 | 0.245482E+11 | 0.00 | 3.91 |
July | 0.00 | 0.611623E+10 | 0.00 | 0.103992E+10 | 0.00 | 0.00 | 0.159839E+11 | 0.00 | 3.94 |
August | 0.00 | 0.584303E+10 | 0.00 | 0.128244E+10 | 0.00 | 0.00 | 0.213090E+11 | 0.00 | 3.93 |
September | 714414.29 | 0.243786E+09 | 0.00 | 0.177437E+10 | 0.00 | 0.00 | 0.362237E+11 | 0.00 | 3.87 |
October | 11846429.51 | 0.00 | 0.00 | 0.190865E+10 | 0.00 | 0.00 | 0.472218E+11 | 0.00 | 3.80 |
November | 0.298748E+10 | 0.00 | 0.00 | 0.131783E+10 | 0.00 | 0.166740E+10 | 0.437145E+11 | 0.00 | 3.71 |
December | 0.647216E+10 | 0.00 | 0.00 | 0.886658E+09 | 0.00 | 0.00 | 0.435207E+11 | 0.00 | 3.59 |
Annual Sum or Average | 0.303821E+11 | 0.163813E+11 | 0.00 | 0.159821E+11 | 0.00 | 0.300519E+11 | 0.429813E+12 | 0.00 | 3.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.584706E+09 | 0.00 | 0.00 | 0.159839E+11 | 0.00 | 3.50 |
Maximum of Months | 0.158260E+11 | 0.611623E+10 | 0.00 | 0.190865E+10 | 0.00 | 0.163612E+11 | 0.472218E+11 | 0.00 | 3.94 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.993118E+10 | 0.00 | 0.00 | 0.974588E+09 | 0.00 | 0.887306E+10 | 0.468122E+11 | 0.00 | 3.74 |
February | 0.278131E+10 | 0.00 | 0.00 | 0.121213E+10 | 0.00 | 0.158275E+11 | 0.376341E+11 | 0.00 | 3.82 |
March | 0.00 | 0.00 | 0.00 | 0.197216E+10 | 0.00 | 0.00 | 0.497105E+11 | 0.00 | 4.01 |
April | 0.00 | 0.322636E+09 | 0.00 | 0.215438E+10 | 0.00 | 0.00 | 0.442345E+11 | 0.00 | 4.03 |
May | 0.00 | 0.281671E+09 | 0.00 | 0.227057E+10 | 0.00 | 0.00 | 0.427761E+11 | 0.00 | 4.12 |
June | 0.00 | 0.380749E+10 | 0.00 | 0.164086E+10 | 0.00 | 0.00 | 0.256754E+11 | 0.00 | 4.13 |
July | 0.00 | 0.645701E+10 | 0.00 | 0.121223E+10 | 0.00 | 0.00 | 0.167300E+11 | 0.00 | 4.16 |
August | 0.00 | 0.617130E+10 | 0.00 | 0.149635E+10 | 0.00 | 0.00 | 0.223163E+11 | 0.00 | 4.15 |
September | 0.00 | 0.258613E+09 | 0.00 | 0.212811E+10 | 0.00 | 0.00 | 0.379177E+11 | 0.00 | 4.09 |
October | 686647.72 | 0.00 | 0.00 | 0.239238E+10 | 0.00 | 0.00 | 0.493705E+11 | 0.00 | 4.01 |
November | 0.150703E+10 | 0.00 | 0.00 | 0.180525E+10 | 0.00 | 0.120192E+10 | 0.481746E+11 | 0.00 | 3.95 |
December | 0.108804E+10 | 0.00 | 0.00 | 0.138799E+10 | 0.00 | 0.00 | 0.525056E+11 | 0.00 | 3.90 |
Annual Sum or Average | 0.153082E+11 | 0.172987E+11 | 0.00 | 0.206470E+11 | 0.00 | 0.259025E+11 | 0.473858E+12 | 0.00 | 4.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.974588E+09 | 0.00 | 0.00 | 0.167300E+11 | 0.00 | 3.74 |
Maximum of Months | 0.993118E+10 | 0.645701E+10 | 0.00 | 0.239238E+10 | 0.00 | 0.158275E+11 | 0.525056E+11 | 0.00 | 4.16 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.750380E+09 | 0.00 | 0.00 | 0.166745E+10 | 0.00 | 0.00 | 0.601448E+11 | 0.00 | 12.45 |
February | 0.140387E+10 | 0.00 | 0.00 | 0.160959E+10 | 0.00 | 0.00 | 0.478718E+11 | 0.00 | 12.38 |
March | 0.00 | 0.00 | 0.00 | 0.209361E+10 | 0.00 | 0.00 | 0.518302E+11 | 0.00 | 13.59 |
April | 0.00 | 0.337098E+09 | 0.00 | 0.202002E+10 | 0.00 | 0.00 | 0.463455E+11 | 0.00 | 13.65 |
May | 0.00 | 0.295200E+09 | 0.00 | 0.204248E+10 | 0.00 | 0.00 | 0.447665E+11 | 0.00 | 13.90 |
June | 0.00 | 0.395710E+10 | 0.00 | 0.139640E+10 | 0.00 | 0.00 | 0.267915E+11 | 0.00 | 13.82 |
July | 0.00 | 0.669574E+10 | 0.00 | 0.104851E+10 | 0.00 | 0.00 | 0.173044E+11 | 0.00 | 13.87 |
August | 0.00 | 0.645122E+10 | 0.00 | 0.127614E+10 | 0.00 | 0.00 | 0.231962E+11 | 0.00 | 13.89 |
September | 0.00 | 0.271004E+09 | 0.00 | 0.196036E+10 | 0.00 | 0.00 | 0.394783E+11 | 0.00 | 13.75 |
October | 0.00 | 0.00 | 0.00 | 0.223639E+10 | 0.00 | 0.00 | 0.517845E+11 | 0.00 | 13.61 |
November | 0.00 | 0.00 | 0.00 | 0.197308E+10 | 0.00 | 0.00 | 0.520406E+11 | 0.00 | 13.37 |
December | 0.00 | 0.00 | 0.00 | 0.189127E+10 | 0.00 | 0.00 | 0.561816E+11 | 0.00 | 13.38 |
Annual Sum or Average | 0.215425E+10 | 0.180074E+11 | 0.00 | 0.212153E+11 | 0.00 | 0.00 | 0.517736E+12 | 0.00 | 13.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104851E+10 | 0.00 | 0.00 | 0.173044E+11 | 0.00 | 12.38 |
Maximum of Months | 0.140387E+10 | 0.669574E+10 | 0.00 | 0.223639E+10 | 0.00 | 0.00 | 0.601448E+11 | 0.00 | 13.90 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:49:30
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.472704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740236E+10 | 0.00 | 0.00 | 0.33 |
February | 0.169598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455158E+10 | 0.00 | 0.00 | 0.30 |
March | 0.319417E+10 | 0.00 | 0.00 | 1102245.88 | 0.00 | 0.120310E+10 | 0.120419E+09 | 0.00 | 0.28 |
April | 0.289189E+10 | 76138528.80 | 0.00 | 39694148.14 | 0.00 | 71995599.51 | 0.198882E+10 | 0.00 | 0.37 |
May | 0.759976E+09 | 67044761.27 | 0.00 | 0.102373E+09 | 0.00 | 0.00 | 0.621440E+10 | 0.00 | 0.55 |
June | 0.206728E+09 | 0.899234E+09 | 0.00 | 0.188259E+09 | 0.00 | 0.00 | 0.464334E+10 | 0.00 | 0.68 |
July | 29844568.69 | 0.152191E+10 | 0.00 | 0.186413E+09 | 0.00 | 0.00 | 0.321187E+10 | 0.00 | 0.72 |
August | 2753684.98 | 0.143936E+10 | 0.00 | 0.205931E+09 | 95854.37 | 0.00 | 0.449053E+10 | 0.00 | 0.70 |
September | 0.105860E+10 | 61293655.84 | 0.00 | 0.209407E+09 | 0.00 | 0.00 | 0.485551E+10 | 0.00 | 0.56 |
October | 0.332129E+10 | 0.00 | 0.00 | 20576085.21 | 0.00 | 0.00 | 0.191391E+10 | 0.00 | 0.33 |
November | 0.269167E+10 | 0.00 | 0.00 | 9230719.04 | 0.00 | 0.184300E+10 | 0.614852E+09 | 0.00 | 0.30 |
December | 0.951788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436342E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.172774E+11 | 0.406498E+10 | 0.00 | 0.962986E+09 | 95854.37 | 0.194355E+11 | 0.280537E+11 | 0.00 | 0.45 |
Minimum of Months | 2753684.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.332129E+10 | 0.152191E+10 | 0.00 | 0.209407E+09 | 95854.37 | 0.740236E+10 | 0.621440E+10 | 0.00 | 0.72 |