Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:46
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2020-06-03 19:46:57
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 9436.72 | 831.77 | 831.77 |
Net Site Energy | 9436.72 | 831.77 | 831.77 |
Total Source Energy | 20841.63 | 1837.03 | 1837.03 |
Net Source Energy | 20841.63 | 1837.03 | 1837.03 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 367.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 640.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 526.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 182.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1648.47 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 971.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 836.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 45.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 103.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.56 | 2185.81 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 48.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5094.68 | 4342.04 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 367.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 640.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 526.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 182.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 8.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 4.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 836.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 45.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 103.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.56 | 2185.81 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 18.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 22.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 62.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 142.24 | 225.04 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 244.34 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 449.06 | 382.72 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 62.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 142.24 | 225.04 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 244.34 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 449.06 | 382.72 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5094.681 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5094.681 | 100.00 |
Total On-Site and Utility Electric Sources | 5094.681 | 100.00 |
Total Electricity End Uses | 5094.681 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 11.98 | 0.32 |
Air to Air Heat Recovery for Heating | 3780.33 | 99.68 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3792.31 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 61.50 |
Time Setpoint Not Met During Occupied Cooling | 8757.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8756.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:46 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 6.8889 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 9.0417 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 9.0417 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.0903 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 5.7049 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 6.4583 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 5.4896 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 4.4132 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 4.4132 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 4.4132 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 4.4132 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 4.4132 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 4.4132 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 6.4583 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 6.4583 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 11.7327 | 4.65 | 2931.5031 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 4.4132 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 5.3388 | 7.60 | 41.0437 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 5.3388 | 7.60 | 41.0437 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUN-19:30 | 21-DEC-17:40 | - | - | - | 05-MAY-20:00 |
Heating | 0.00 | 198710.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 114113.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 47387.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86131.51 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 50266.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38378.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2503.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4880.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3869.61 | 171171.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1955.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 361118.72 | 459494.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 198710.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 114113.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 47387.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1227.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 38378.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2503.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 4880.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3869.61 | 171171.59 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 978.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 734.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 398.24 | 0.00 | 0.00 | 0.00 |
Cooling | 2030.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1665.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 578.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5220.69 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3078.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2649.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 144.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 327.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 286.81 | 2369.42 | 0.00 | 0.00 | 0.00 |
Refrigeration | 153.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 16134.85 | 4706.77 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 35.10 | 0.00 | 0.00 | 0.00 |
Cooling | 178.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 146.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 233.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 12.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 28.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.28 | 208.85 | 0.00 | 0.00 | 0.00 |
Refrigeration | 13.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1422.16 | 414.87 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 35.10 | 0.00 | 0.00 | 0.00 |
Cooling | 178.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 146.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 460.16 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 233.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 12.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 28.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.28 | 208.85 | 0.00 | 0.00 | 0.00 |
Refrigeration | 13.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1422.16 | 414.87 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.62 | 0.575820 | 0.489000 | 1.28 | 1.00 | 0.500000 | 0.000662 | 0.000121 | 1.28 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.344103 | 0.148526 | 0.345000 | 0.118716 | 0.411435 | 0.500000 | 0.002565 | 0.000093 | 0.180829 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.252839 | 0.234077 | 0.544000 | 0.137544 | 0.624204 | 0.500000 | 0.001628 | 0.000034 | 0.137544 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.259940 | 0.481469 | 0.010000 | 0.002599 | 1.00 | 0.500000 | 0.000791 | 0.000044 | 0.085660 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.104810 | 0.688927 | 0.826000 | 0.086573 | 1.00 | 0.500000 | 0.000553 | 0.000034 | 0.086573 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 4.01 | 0.014848 | 0.010000 | 0.040050 | 0.300000 | 0.500000 | 0.025660 | 0.000060 | 0.116361 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.49 | 0.096352 | 0.679000 | 1.01 | 0.679000 | 0.500000 | 0.003954 | 0.000292 | 1.01 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.97 | 0.200694 | 0.572000 | 2.84 | 0.572000 | 0.500000 | 0.001898 | 0.000678 | 2.84 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.600000 | 0.712143 | 1.00 | 0.500000 | 0.000381 | 0.000278 | 0.712143 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.50 | 0.101235 | 0.713000 | 1.78 | 0.713000 | 0.500000 | 0.003764 | 0.000313 | 1.78 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.62 | 0.096304 | 0.679000 | 1.78 | 0.679000 | 0.500000 | 0.003956 | 0.000316 | 1.78 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.67 | 0.700000 | 0.207000 | 0.551762 | 0.300000 | 0.500000 | 0.012901 | 0.000114 | 0.551762 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.668487 | 0.469776 | 0.282000 | 0.188513 | 1.00 | 0.500000 | 0.000811 | 0.000189 | 0.367569 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 5488.08 | 0.000121 | 97.11 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4198.41 | 0.000093 | 91.00 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1525.19 | 0.000034 | 29.61 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1988.79 | 0.000044 | 43.11 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1546.72 | 0.000034 | 31.75 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 2701.62 | 0.000060 | 58.56 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 13219.20 | 0.000292 | 260.37 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 30678.44 | 0.000678 | 593.88 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 6305.12 | 0.000139 | 143.54 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 6311.23 | 0.000139 | 143.68 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 35966.78 | 0.000795 | 818.83 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 36086.86 | 0.000797 | 821.56 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 6305.12 | 0.000139 | 143.54 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 6311.23 | 0.000139 | 143.68 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12596.84 | 0.000278 | 258.19 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 1957.22 | 0.000043 | 44.56 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 1961.64 | 0.000043 | 44.66 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 9430.94 | 0.000208 | 214.70 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 14149.21 | 0.000313 | 263.04 |
DINING_FLR_6 VAV BOX REHEAT COIL | 14286.77 | 0.000316 | 265.85 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5178.43 | 0.000114 | 98.22 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8535.41 | 0.000189 | 185.01 |
VAV WITH REHEAT_HEATC | 236776.80 | 0.005231 | 3168.57 |
FLR_3_DOAS_HEATC | 20912.17 | 0.000462 | 279.85 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 1.28 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 1.27 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 5.82 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 6.41 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 1.10 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 1.10 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.342462 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.338410 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.23 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.28 | 0.000139 | 0.000332 |
ROOM_2_FLR_3 FAN COIL | 1.27 | 0.000139 | 0.000328 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.82 | 0.000795 | 0.001497 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.41 | 0.000797 | 0.001745 |
ROOM_5_FLR_3 FAN COIL | 1.10 | 0.000139 | 0.000285 |
ROOM_6_FLR_3 FAN COIL | 1.10 | 0.000139 | 0.000284 |
ROOM_1_FLR_6 FAN COIL | 0.342462 | 0.000043 | 0.000089 |
ROOM_2_FLR_6 FAN COIL | 0.338410 | 0.000043 | 0.000087 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.23 | 0.000208 | 0.000327 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 1.28 |
ROOM_2_FLR_3 FAN COILFAN | 1.27 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 5.82 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 6.41 |
ROOM_5_FLR_3 FAN COILFAN | 1.10 |
ROOM_6_FLR_3 FAN COILFAN | 1.10 |
ROOM_1_FLR_6 FAN COILFAN | 0.342462 |
ROOM_2_FLR_6 FAN COILFAN | 0.338410 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.23 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000332 | 1.28 | 0.008519 | 21.82 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000328 | 1.27 | 0.008519 | 21.82 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.001497 | 5.82 | 0.008441 | 21.82 | 6.70 | 12.80 | 0.008441 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.001745 | 6.41 | 0.008712 | 21.82 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000285 | 1.10 | 0.008521 | 21.82 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000284 | 1.10 | 0.008521 | 21.82 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000089 | 0.342462 | 0.008518 | 21.82 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000087 | 0.338410 | 0.008518 | 21.82 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000327 | 1.23 | 0.008603 | 21.82 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.011529 | 0.007974 | 27.97 | 6.70 | 10.55 | 0.007974 | 403126.32 | 23.22 | |
FLR_3_DOAS_COOLC | 0.001291 | 0.005430 | 33.90 | 6.70 | 10.54 | 0.005430 | 45130.47 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 13.63 | 10.54 | 23.69 | 10.54 | 23.22 | 23.22 | 0.300000 | 0.453634 | 23.22 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 23.22 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT HEAT RECOVERY | 9.33 |
FLR_3_DOAS HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 23.22 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.011529 | 0.000041 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.005231 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001291 | 0.000369 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000462 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.017793 | 3369.84 |
HEATSYS1 PUMP | 0.010703 | 2707.31 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.010703 | 1.28 |
COOLSYS1 | 0.017793 | 2.14 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.017793 | 1123.28 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 484418.22 | 484418.22 | 0.010703 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.017793 | 622128.09 | 622765.82 | 71.00 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 6.889 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 12.269 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 9.042 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.802 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 9.042 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 19.802 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 10.226 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.606 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 4.090 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 6.780 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 5.705 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.235 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 6.458 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 11.838 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 5.490 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 13.560 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 4.413 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 11.163 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 4.413 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 14.933 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 6.458 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 74.278 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 6.458 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 74.278 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.733 | 512.243 | 2419.260 | 0.000 | 0.000 | 0.000 | 2943.236 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 4.413 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.413 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 13631.969 | 6.889 | 128.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 13631.969 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 606.438 | 9.042 | 56.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 606.438 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 702.258 | 9.042 | 56.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 702.258 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 1679.504 | 10.226 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1679.504 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 387.593 | 4.090 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 387.593 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 445.205 | 5.705 | 53.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 445.205 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1219.735 | 6.458 | 8.572 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1219.735 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 7181.411 | 5.490 | 17.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7181.411 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 108.229 | 4.413 | 72.152 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.229 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 1718.522 | 4.413 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1718.522 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 172.212 | 4.413 | 114.808 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.212 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 172.192 | 4.413 | 114.795 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.192 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 108.258 | 4.413 | 72.172 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.258 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2141.959 | 6.458 | 8.571 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2141.959 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2141.959 | 6.458 | 8.571 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2141.959 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1212.036 | 11.733 | 54.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1212.036 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 1818.790 | 4.413 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1818.790 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 277.500 | 2.686 | 12.479 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 277.500 | 277.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 156.700 | 1.517 | 7.046 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 156.700 | 156.700 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.5534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.640 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.29758781E-14 | -0.29065710E-15 | -0.16717921E-09 | -0.54082436E-16 |
25 | 8 | 0.24322757E-07 | 0.75510264E-13 | 0.40304845E-03 | -0.27655812E-09 |
26 | 7 | -0.12993629E-01 | 0.38338009E-08 | -0.24168191E-01 | 0.14774231E-03 |
27 | 6 | 0.42578349 | 0.13225368E-05 | 0.48945559 | -0.49886206E-02 |
28 | 5 | -5.3899404 | 0.49024379E-04 | -4.5744615 | 0.65656055E-01 |
29 | 4 | 33.884590 | 0.39840510E-03 | 21.960611 | -0.43383013 |
30 | 3 | -113.10176 | 0.86320527E-03 | -56.652426 | 1.5422922 |
31 | 2 | 198.98955 | 0.48301085E-03 | 78.818690 | -2.9302292 |
32 | 1 | -171.85079 | 0.51313109E-04 | -55.530381 | 2.7576150 |
33 | 0 | 57.057407 | 0.29052359E-06 | 15.514123 | |
34 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
35 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
36 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
37 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
38 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
39 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
40 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
41 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
42 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
43 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
44 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
45 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
46 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
47 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
48 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
49 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
59 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
60 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
61 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
62 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
63 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
64 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
65 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
66 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
67 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
68 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
69 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
70 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
71 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
72 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
73 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
74 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
75 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
76 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
77 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
78 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
79 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
80 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
81 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
82 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
83 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
84 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
85 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
86 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
87 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
88 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
89 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_0.38 | 31 | 1 | VerySmooth | 2.045 | 0.374 | 0.294 | 0.419 |
2 | RESWINDOW_U_0.37_SHGC_0.38 | 32 | 1 | VerySmooth | 2.102 | 0.374 | 0.294 | 0.419 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.29373 | 0.50072 | 0.50072 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.55893E-002 | 0.29373 | 0.49964 | 0.49964 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11739 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 29254.38326 | 29254.38326 | 2.61865 | 2.61865 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 26.50000 | 5.43031E-003 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85413 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90000 | 9.55238E-004 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 3844.06736 | 3844.06736 | 0.34410 | 0.34410 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.77667 | 5.43030E-003 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3424.97043 | 3424.97043 | 0.18083 | 0.18083 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 2824.29976 | 2824.29976 | 0.25284 | 0.25284 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 32.22267 | 5.43030E-003 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 936.43714 | 936.43714 | 4.94475E-002 | 9.16993E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2904.42339 | 2904.42339 | 0.25994 | 0.25994 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 32.42000 | 5.43030E-003 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1622.23234 | 1622.23234 | 8.56600E-002 | 8.56600E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1171.09231 | 1171.09231 | 0.10481 | 0.10481 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.43030E-003 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1176.23532 | 1176.23532 | 6.21091E-002 | 6.21091E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44744.84689 | 44744.84689 | 4.00504 | 4.00504 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.43030E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2203.78838 | 2203.78838 | 0.11636 | 0.11636 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 16670.09633 | 16670.09633 | 1.49362 | 1.49362 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.43030E-003 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 8881.05906 | 8881.05906 | 0.46890 | 0.67613 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 55465.55348 | 55465.55348 | 4.96696 | 4.96696 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.90000 | 5.43030E-003 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 18520.29754 | 18520.29754 | 0.97793 | 1.89326 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 10634.13337 | 10634.13337 | 1.28260 | 1.28260 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.43030E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6305.20067 | 6305.20067 | 0.33487 | 0.33487 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 10504.28109 | 10504.28109 | 1.26694 | 1.26694 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.43030E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6311.30687 | 6311.30687 | 0.33520 | 0.33520 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 48251.95468 | 48251.95468 | 5.81958 | 5.81958 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.60400 | 5.43030E-003 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 35967.01402 | 35967.01402 | 1.91033 | 1.91033 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 53138.35345 | 53138.35345 | 6.40948 | 6.40948 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.43030E-003 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 36087.08905 | 36087.08905 | 1.91671 | 1.91671 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 9136.39175 | 9136.39175 | 1.10196 | 1.10196 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.43031E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6305.20067 | 6305.20067 | 0.33487 | 0.33487 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 9085.66073 | 9085.66073 | 1.09584 | 1.09584 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.43031E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6311.30687 | 6311.30687 | 0.33520 | 0.33520 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 9488.43081 | 9488.43081 | 0.84920 | 1.18691 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 33.30800 | 5.43030E-003 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9547.23043 | 9547.23043 | 0.50414 | 0.50414 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -17.90000 | 9.55238E-004 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2839.37185 | 2839.37185 | 0.34246 | 0.34246 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.43030E-003 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1957.24231 | 1957.24231 | 0.10395 | 0.10395 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2805.77773 | 2805.77773 | 0.33841 | 0.33841 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.43030E-003 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1961.66687 | 1961.66687 | 0.10419 | 0.10419 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10234.32552 | 10234.32552 | 1.23443 | 1.23443 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.90000 | 5.43030E-003 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 9431.02373 | 9431.02373 | 0.50090 | 0.50090 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 27851.29201 | 27851.29201 | 2.49639 | 2.49639 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.43030E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 6526.05851 | 6526.05851 | 0.34460 | 1.18734 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 29278.07725 | 29278.07725 | 2.62422 | 2.62422 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.43030E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6655.31123 | 6655.31123 | 0.35143 | 1.18734 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29697.29685 | 29697.29685 | 2.66552 | 2.66552 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.43031E-003 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 2819.17701 | 2819.17701 | 0.14885 | 0.36721 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -17.90000 | 9.55238E-004 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 7469.24632 | 7469.24632 | 0.66849 | 0.66849 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90000 | 5.43030E-003 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6960.95134 | 6960.95134 | 0.36757 | 0.36757 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | -17.90000 | 9.55238E-004 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 345991.05 | 23.22458 | 23.22458 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 257384.28 | 7.57377 | 7.57377 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 42509.33 | 17.92230 | 2.05120 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 69707.24 | 5.87622 | 2.05120 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.61865 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.57582 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48900 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28052 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.61665E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21252E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28052 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5488.08176 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21252E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 97.11422 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.34410 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14853 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34500 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11872 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41143 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56520E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.27588E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18083 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4198.41303 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.27588E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 90.99927 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.25284 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23408 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54400 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13754 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62420 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.62767E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.36971E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13754 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1525.18581 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.36971E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 29.61224 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.25994 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.48147 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.59940E-003 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.91328E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.39399E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.56600E-002 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1988.79063 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.39399E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 43.10625 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.10481 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.68893 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.82600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 8.65732E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.53034E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.41730E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.65732E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1546.72309 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.41730E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.75443 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.00504 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.48478E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 1.00000E-002 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.00504E-002 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.56604E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.96889E-005 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.11636 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2701.61686 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.96889E-005 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 58.55658 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.49362 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.63516E-002 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.67900 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.01417 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67900 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.95427E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.92062E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.01417 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13219.20419 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.92062E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 260.36735 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.96696 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20069 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57200 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.84110 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57200 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.89841E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.77803E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.84110 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 30678.43969 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.77803E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 593.87786 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.28260 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.28260 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.28260 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.39304E-004 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.31668E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.31668E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.28260 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.51898E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6305.12269 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39304E-004 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.54466 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.26694 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.26694 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.26694 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.39439E-004 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.27637E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.27637E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.26694 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.51918E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6311.22879 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39439E-004 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.68365 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.81958 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.81958 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.81958 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.94642E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.49694E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.49694E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.81958 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.44103E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.81654 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.44103E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 35966.78443 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.94642E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 818.83063 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.40948 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.40948 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 6.40948 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.97295E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.74530E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.74530E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 6.40948 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.71223E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.81547 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 36086.85880 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.97295E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 821.56387 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10196 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.10196 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.10196 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.39304E-004 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.85086E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.85086E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.10196 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.52065E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6305.12269 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39304E-004 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.54466 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09584 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09584 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.09584 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.39439E-004 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.83515E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.83515E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.09584 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.52080E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6311.22879 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39439E-004 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.68365 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60000 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71214 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.78312E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71214 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12596.83542 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.78312E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 258.18554 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.34246 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.34246 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.34246 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.32424E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.85286E-005 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 8.85286E-005 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.34246 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.51780E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1957.21980 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.32424E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 44.55724 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.33841 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.33841 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.33841 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.33401E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 8.74856E-005 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 8.74856E-005 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.33841 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.51798E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.81619 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1961.64431 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.33401E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 44.65796 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23443 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.23443 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.23443 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.08365E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.26544E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.26544E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.23443 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.60277E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.81578 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 9430.93614 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.08365E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 214.70012 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.49639 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10124 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.71300 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.77993 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71300 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.76351E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.12609E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.77993 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14149.20753 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.12609E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 263.04308 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.62422 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.63039E-002 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.67900 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.78185 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67900 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.95623E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.15649E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.78185 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14286.77235 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.15649E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 265.85425 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.66552 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20700 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.55176 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29013E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14411E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55176 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5178.42944 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14411E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 98.22394 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66849 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.46978 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28200 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18851 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.11025E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.88579E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36757 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8535.40869 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.88579E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 185.00969 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 13.63417 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 10.53546 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.68748 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 10.53546 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.22458 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 23.22458 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.45363 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 23.22458 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.22458 |
346 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 9.32560 |
347 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 403126.32042 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.15294E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 23.22458 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 7.97380E-003 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 27.96782 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.55185 |
354 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 7.97380E-003 |
355 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 236776.79608 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.23129E-003 |
357 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 3168.56749 |
358 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 23.22458 |
359 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.15294E-002 |
360 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.13024E-005 |
361 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.23129E-003 |
362 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
363 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
364 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05120 |
365 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 45130.46586 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.29073E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 5.43030E-003 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 33.90000 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
371 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.54137 |
372 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 5.43030E-003 |
373 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 20912.17262 |
374 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 4.62029E-004 |
375 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 279.84850 |
376 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
377 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.29073E-003 |
378 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.68932E-004 |
379 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.62029E-004 |
380 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 1.77928E-002 |
381 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3369.83902 |
382 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
383 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
384 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
385 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
386 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
387 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.07026E-002 |
388 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.28432 |
389 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.07026E-002 |
390 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2707.31128 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 484418.22362 |
392 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 484418.22000 |
393 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.07026E-002 |
394 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 1.77928E-002 |
395 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.13513 |
396 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 1.77928E-002 |
397 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 1123.27967 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 1.77928E-002 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 622128.09317 |
400 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 622765.82000 |
401 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 70.99530 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 5520.25 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4224.15 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1535.43 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2000.98 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1556.62 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 2718.18 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 13306.93 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 30860.88 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 6806.00 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 6812.59 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 38824.19 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 38953.79 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 6806.00 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 6812.59 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 12677.45 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 2112.65 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 2117.42 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 10179.88 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 14229.86 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 14368.18 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 5207.15 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8587.73 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 155991.69 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 13777.22 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 13499.31 | 10455.93 | 3043.38 | 0.77 | 1167.64 | 11.84 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 13335.13 | 10328.65 | 3006.48 | 0.77 | 1153.44 | 11.70 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 64916.89 | 50964.23 | 13952.66 | 0.79 | 6242.41 | 63.31 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 70548.14 | 54071.43 | 16476.71 | 0.77 | 6145.75 | 62.33 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 11602.66 | 8986.05 | 2616.62 | 0.77 | 1003.65 | 10.18 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 11538.65 | 8936.39 | 2602.25 | 0.77 | 998.11 | 10.12 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 3603.38 | 2791.19 | 812.19 | 0.77 | 311.66 | 3.16 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 3560.90 | 2758.26 | 802.64 | 0.77 | 307.99 | 3.12 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 13251.23 | 10216.73 | 3034.50 | 0.77 | 1149.72 | 11.66 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 442597.74 | 293164.88 | 149432.86 | 0.66 | 49061.85 | 497.61 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 50094.14 | 30517.23 | 19576.91 | 0.61 | 7512.39 | 76.19 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 4.04 | 13.79 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.37_SHGC_0.38 | N/A | 2.102 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.38 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 10 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.2207555373E-002 | 2.5726075213E-002 | Pass | Pass | 1.2003909296E-002 | 4.0779894836E-002 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.9878778578E-002 | 0.1149047236 | Pass | Pass | 3.4325248973E-002 | 6.1888483637E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.2223921448E-002 | 4.4471889804E-002 | Pass | Pass | 1.9526403584E-002 | 3.6650603349E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1758521836E-002 | 1.5504295163E-002 | Pass | Pass | 9.9493584612E-002 | 0.5630478005 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.5449163847E-002 | 1.5310861793E-002 | Pass | Pass | 5.7724709609E-003 | 1.1916283866E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1637629592 | 0.3840444669 | Pass | Pass | 1.9092955499E-002 | 5.1236975542E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.8092560324E-002 | 0.1151128417 | Pass | Pass | 1.9394289045E-002 | 3.3750817166E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.7419678092E-002 | 4.8008893962E-002 | Pass | Pass | 1.1603812222E-002 | 2.7031535805E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.4644732670E-002 | 0.1920624688 | Pass | Pass | 0.1132157857 | 0.2661373652 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.5953857471E-002 | 0.2229301874 | Pass | Pass | 5.7612691009E-002 | 0.1854276959 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.3074920817E-002 | 3.5688865039E-002 | Pass | Pass | 0.1510884262 | 0.8515137346 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.8339062107E-002 | 8.5902015745E-002 | Pass | Pass | 0.1793127413 | 0.8265058116 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.8675517445E-002 | 0.2254314162 | Pass | Pass | 0.3271631315 | 1.9051470239 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.0603446299E-002 | 0.2178422563 | Pass | Pass | 0.1602631012 | 1.0668195551 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.2583361012E-003 | 1.2901830749E-002 | Pass | Pass | 0.1722852093 | 0.9254299396 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.1787299541E-002 | 0.2006902649 | Pass | Pass | 0.1361427429 | 0.3794718318 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.8865876241E-002 | 0.2884408631 | Pass | Pass | 0.1200115871 | 0.5729725259 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1087397817 | 0.2371705140 | Pass | Pass | 0.1527950601 | 0.6462879044 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.6431238933E-002 | 9.7897023799E-002 | Pass | Pass | 9.2457672567E-003 | 2.4032882159E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.9760288559E-002 | 9.1310005620E-002 | Pass | Pass | 6.9878455455E-003 | 2.1561882595E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 0.1403961196 | 0.2224875630 | Pass | Pass | 1.5712573163E-002 | 2.8273942589E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.7355508258E-002 | 3.5234817167E-002 | Pass | Pass | 0.2113466569 | 1.5888653600 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 2.045 | 0.374 | 0.419 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 2.045 | 0.374 | 0.419 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 2.045 | 0.374 | 0.419 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.374 | 0.419 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.374 | 0.419 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.374 | 0.419 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.374 | 0.419 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 2.102 | 0.374 | 0.419 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 2.102 | 0.374 | 0.419 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.374 | 0.419 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.374 | 0.419 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.102 | 0.374 | 0.419 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.102 | 0.374 | 0.419 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.374 | 0.419 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.045 | 0.374 | 0.419 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.045 | 0.374 | 0.419 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.374 | 0.419 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.102 | 0.374 | 0.419 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.102 | 0.374 | 0.419 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.102 | 0.374 | 0.419 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.102 | 0.374 | 0.419 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.37_SHGC_0.38 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 2.102 | 0.374 | 0.419 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.374 | 0.419 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.374 | 0.419 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.374 | 0.419 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.374 | 0.419 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.374 | 0.419 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 2.045 | 0.374 | 0.419 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.045 | 0.374 | 0.419 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.38 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.374 | 0.419 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 2.085 | 0.374 | 0.419 | ||||||||||||
North Total or Average | 432.93 | 2.087 | 0.374 | 0.419 | ||||||||||||
Non-North Total or Average | 781.15 | 2.084 | 0.374 | 0.419 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 6.8889 | 1978.83 | 13631.97 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 52.48 | 168.00 | 52.43 | 0.0000 | Y | 134.15 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 9.0417 | 67.07 | 606.44 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 6.67 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 9.0417 | 77.67 | 702.26 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 7.73 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 10.2257 | 164.24 | 1679.50 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.48 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 4.0903 | 94.76 | 387.59 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 26.12 | 168.00 | 26.09 | 0.0000 | Y | 1.90 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 5.7049 | 78.04 | 445.21 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 4.90 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 6.4583 | 188.86 | 1219.74 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 38.94 | 0.0000 | Y | 8.92 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 5.4896 | 1308.19 | 7181.41 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 55.24 | 0.0000 | Y | 74.46 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 4.4132 | 156.09 | 688.85 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 4.4132 | 156.07 | 688.77 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 4.4132 | 1863.81 | 8225.38 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 65.84 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 4.4132 | 1864.32 | 8227.63 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 65.86 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 4.4132 | 156.09 | 688.85 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 4.4132 | 156.07 | 688.77 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 5.51 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 4.4132 | 1557.62 | 6874.09 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 41.03 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 4.4132 | 39.02 | 172.21 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 1.38 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 4.4132 | 39.02 | 172.19 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 1.38 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 4.4132 | 220.77 | 974.32 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 7.80 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 6.4583 | 331.66 | 2141.96 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 48.83 | 0.0000 | Y | 19.63 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 6.4583 | 331.66 | 2141.96 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 48.83 | 0.0000 | Y | 19.63 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 11.7327 | 103.30 | 1212.04 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 13.34 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 4.4132 | 412.12 | 1818.79 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 10.86 |
Interior Lighting Total | 5.3388 | 11345.29 | 60569.92 | 341.81 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1219.74 | 475.70 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1219.74 | 475.70 |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 7181.41 | 502.70 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.07 | 7181.41 | 502.70 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Continuous/Off | 0.20 | 2141.96 | 428.39 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11632.50 | AstronomicalClock | - | 83.67 | 83.67 | 182.70 | |
Exterior Lighting Total | 11632.50 | 182.70 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 484418.22 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 622765.82 | 2.96 | 4.04 | 13.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11597.06 | 13499.31 | 10455.93 | 3043.38 | 0.77 | - | 1167.64 | 11.84 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11456.09 | 13335.13 | 10328.65 | 3006.48 | 0.77 | - | 1153.44 | 11.70 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 52341.64 | 64916.89 | 50964.23 | 13952.66 | 0.79 | - | 6242.41 | 63.31 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 61025.79 | 70548.14 | 54071.43 | 16476.71 | 0.77 | - | 6145.75 | 62.33 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 9968.27 | 11602.66 | 8986.05 | 2616.62 | 0.77 | - | 1003.65 | 10.18 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 9913.32 | 11538.65 | 8936.39 | 2602.25 | 0.77 | - | 998.11 | 10.12 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3095.48 | 3603.38 | 2791.19 | 812.19 | 0.77 | - | 311.66 | 3.16 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3059.01 | 3560.90 | 2758.26 | 802.64 | 0.77 | - | 307.99 | 3.12 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 11417.89 | 13251.23 | 10216.73 | 3034.50 | 0.77 | - | 1149.72 | 11.66 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 403126.32 | 442597.74 | 293164.88 | 149432.86 | 0.66 | - | 49061.85 | 497.61 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 45130.47 | 50094.14 | 30517.23 | 19576.91 | 0.61 | - | 7512.39 | 76.19 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 5488.08 | 5520.25 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4198.41 | 4224.15 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1525.19 | 1535.43 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1988.79 | 2000.98 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1546.72 | 1556.62 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2701.62 | 2718.18 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13219.20 | 13306.93 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 30678.44 | 30860.88 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6305.12 | 6806.00 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6311.23 | 6812.59 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 35966.78 | 38824.19 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 36086.86 | 38953.79 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6305.12 | 6806.00 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6311.23 | 6812.59 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 12596.84 | 12677.45 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1957.22 | 2112.65 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1961.64 | 2117.42 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 9430.94 | 10179.88 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14149.21 | 14229.86 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14286.77 | 14368.18 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 5178.43 | 5207.15 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8535.41 | 8587.73 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 236776.80 | 155991.69 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 20912.17 | 13777.22 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.28 | 902.49 | 703.64 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.27 | 891.47 | 703.64 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.82 | 4094.87 | 703.64 | 1.00 | 0.96 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 6.41 | 4509.94 | 703.64 | 1.00 | 0.95 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 775.38 | 703.64 | 1.00 | 1.17 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 771.07 | 703.64 | 1.00 | 1.17 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.34 | 240.97 | 703.64 | 1.00 | 1.63 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.34 | 238.12 | 703.64 | 1.00 | 1.63 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.23 | 868.59 | 703.64 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 23.22 | 52037.88 | 2240.64 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 134283.83 | 0.017793 | 3369.84 | 189393.57 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.010703 | 2707.31 | 252957.60 | 0.91 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.017793 | 1123.28 | 63131.19 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 29254.38 | 29254.38 | 14.78 | 2.619 | 2.619 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 20:00:00 | 24.00 | 24.00 | 0.00932 | 26.50 | 0.00543 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3844.07 | 3844.07 | 57.31 | 0.344 | 0.344 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00895 | 33.78 | 0.00543 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 2824.30 | 2824.30 | 36.36 | 0.253 | 0.253 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00944 | 32.22 | 0.00543 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44744.85 | 44744.85 | 573.36 | 4.005 | 4.005 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00853 | 33.75 | 0.00543 | 0.000 | 0.00 |
CAFE_FLR_1 | 16670.10 | 16670.10 | 88.27 | 1.494 | 1.494 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 23.99 | 0.01028 | 33.65 | 0.00543 | 0.676 | 0.00 |
LOBBY_FLR_1 | 55465.55 | 55465.55 | 42.40 | 4.967 | 4.967 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.01014 | 33.90 | 0.00543 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 10634.13 | 10634.13 | 272.52 | 1.283 | 1.283 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00543 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 10504.28 | 10504.28 | 269.22 | 1.267 | 1.267 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00543 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 48251.95 | 48251.95 | 1967.55 | 5.820 | 5.820 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 21.11 | 21.11 | 0.00844 | 33.60 | 0.00543 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 53138.35 | 53138.35 | 2166.21 | 6.409 | 6.409 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 21.11 | 21.11 | 0.00871 | 33.75 | 0.00543 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 9136.39 | 9136.39 | 234.13 | 1.102 | 1.102 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00852 | 25.76 | 0.00543 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 9085.66 | 9085.66 | 232.86 | 1.096 | 1.096 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00852 | 25.76 | 0.00543 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2839.37 | 2839.37 | 72.76 | 0.342 | 0.342 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00543 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2805.78 | 2805.78 | 71.91 | 0.338 | 0.338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 21.11 | 21.11 | 0.00852 | 31.83 | 0.00543 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10234.33 | 10234.33 | 417.21 | 1.234 | 1.234 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00860 | 33.90 | 0.00543 | 0.099 | 0.00 |
BANQUET_FLR_6 | 27851.29 | 27851.29 | 83.98 | 2.496 | 2.496 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01050 | 33.90 | 0.00543 | 1.187 | 0.00 |
DINING_FLR_6 | 29278.08 | 29278.08 | 88.28 | 2.624 | 2.624 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01040 | 33.90 | 0.00543 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 29697.30 | 29697.30 | 287.47 | 2.666 | 2.666 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 23.97 | 0.01004 | 26.60 | 0.00543 | 0.367 | 0.00 |
MECH_FLR_1 | 2904.42 | 2904.42 | 17.68 | 0.260 | 0.260 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00840 | 32.42 | 0.00543 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1171.09 | 1171.09 | 12.36 | 0.105 | 0.105 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00834 | 33.75 | 0.00543 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 9488.43 | 9488.43 | 24.37 | 0.849 | 1.187 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00841 | 33.31 | 0.00543 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 7469.25 | 7469.25 | 18.12 | 0.668 | 0.668 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00845 | 33.90 | 0.00543 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 3424.97 | 3424.97 | 51.06 | 0.181 | 0.181 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00723 | -17.90 | 0.00096 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 936.44 | 936.44 | 12.06 | 0.049 | 0.092 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00739 | -17.90 | 0.00096 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 2203.79 | 2203.79 | 28.24 | 0.116 | 0.116 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00723 | -17.90 | 0.00096 | 0.000 | 0.00 |
CAFE_FLR_1 | 8881.06 | 8881.06 | 47.02 | 0.469 | 0.676 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00725 | -17.90 | 0.00096 | 0.676 | 0.00 |
LOBBY_FLR_1 | 18520.30 | 18520.30 | 14.16 | 0.978 | 1.893 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00728 | -17.90 | 0.00096 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 6305.20 | 6305.20 | 161.58 | 0.335 | 0.335 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00749 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6311.31 | 6311.31 | 161.76 | 0.335 | 0.335 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00749 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 35967.01 | 35967.01 | 1466.61 | 1.910 | 1.910 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00752 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 36087.09 | 36087.09 | 1471.11 | 1.917 | 1.917 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00753 | -17.90 | 0.00096 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6305.20 | 6305.20 | 161.58 | 0.335 | 0.335 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00749 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6311.31 | 6311.31 | 161.76 | 0.335 | 0.335 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00749 | -17.90 | 0.00096 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 1957.24 | 1957.24 | 50.16 | 0.104 | 0.104 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00758 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1961.67 | 1961.67 | 50.28 | 0.104 | 0.104 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00759 | -17.90 | 0.00096 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 9431.02 | 9431.02 | 384.46 | 0.501 | 0.501 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.11 | 21.11 | 0.00760 | -17.90 | 0.00096 | 0.099 | 0.00 |
BANQUET_FLR_6 | 6526.06 | 6526.06 | 19.68 | 0.345 | 1.187 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00769 | -17.90 | 0.00096 | 1.187 | 0.00 |
DINING_FLR_6 | 6655.31 | 6655.31 | 20.07 | 0.351 | 1.187 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00769 | -17.90 | 0.00096 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 2819.18 | 2819.18 | 27.29 | 0.149 | 0.367 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 21.00 | 0.00708 | -17.90 | 0.00096 | 0.367 | 0.00 |
MECH_FLR_1 | 1622.23 | 1622.23 | 9.88 | 0.086 | 0.086 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00725 | -17.90 | 0.00096 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1176.24 | 1176.24 | 12.41 | 0.062 | 0.062 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00728 | -17.90 | 0.00096 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 9547.23 | 9547.23 | 24.52 | 0.504 | 0.504 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00759 | -17.90 | 0.00096 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 6960.95 | 6960.95 | 16.89 | 0.368 | 0.368 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 21.00 | 21.00 | 0.00774 | -17.90 | 0.00096 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 23.22 | 23.22 | 7.57 | 7.57 | 23.2246 | 10.5355 | 23.2246 | 0.4536 | 0.3000 |
FLR_3_DOAS | 17.92 | 2.05 | 5.88 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 5488.082 | 5488.082 | 1.280518 | 0.00012125 | 97.114 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 5520.25 | 5488.08 | 1.280518 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 5520.63 | 5520.63 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4198.413 | 4198.413 | 0.180829 | 0.00009276 | 90.999 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 4224.15 | 4198.41 | 0.180829 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00723064 | 37.9950 | 3424.97 | 0.00 | 4225.24 | 4225.24 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1525.186 | 1525.186 | 0.137544 | 0.00003370 | 29.612 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1535.43 | 1525.19 | 0.137544 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00739408 | 38.8391 | 936.44 | 0.00 | 1535.57 | 1535.57 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1988.791 | 1988.791 | 0.085660 | 0.00004394 | 43.106 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2000.98 | 1988.79 | 0.085660 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00724737 | 38.0774 | 1622.23 | 0.00 | 2001.50 | 2001.50 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1546.723 | 1546.723 | 0.086573 | 0.00003417 | 31.754 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1556.62 | 1546.72 | 0.086573 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00727514 | 38.2216 | 1176.24 | 0.00 | 1556.90 | 1556.90 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 2701.617 | 2701.617 | 0.116361 | 0.00005969 | 58.557 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2718.18 | 2701.62 | 0.116361 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00722871 | 37.9824 | 2203.79 | 0.00 | 2718.88 | 2718.88 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 13219.204 | 13219.204 | 1.014168 | 0.00029206 | 260.367 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 13306.93 | 13219.20 | 1.014168 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00724905 | 38.0902 | 8881.06 | 0.00 | 13308.45 | 13308.45 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 30678.440 | 30678.440 | 2.841101 | 0.00067780 | 593.878 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 30860.88 | 30678.44 | 2.841101 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00727844 | 38.2390 | 18520.30 | 0.00 | 30863.49 | 30863.49 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 11597.058 | -999.000 | 1.282604 | 0.00033167 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 11597.06 | 11556.10 | 1.282604 | 21.82 | 13.51 | 0.00851898 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00543030 | 14.32 | 0.0000 | 21.11 | 0.00851898 | 44.3629 | 10634.13 | 0.00 | 8715.15 | 8715.15 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6305.123 | 6305.123 | 0.334874 | 0.00013930 | 143.545 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 6806.00 | 6305.12 | 0.334874 | 21.11 | 12.38 | 0.00749117 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00749117 | 39.0778 | 6305.20 | 0.00 | 6806.49 | 6806.49 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 11456.092 | -999.000 | 1.266942 | 0.00032764 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 11456.09 | 11415.19 | 1.266942 | 21.82 | 13.51 | 0.00851918 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00543030 | 14.32 | 0.0000 | 21.11 | 0.00851918 | 44.3639 | 10504.28 | 0.00 | 8609.31 | 8609.31 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6311.229 | 6311.229 | 0.335198 | 0.00013944 | 143.684 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 6812.59 | 6311.23 | 0.335198 | 21.11 | 12.38 | 0.00749166 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00749166 | 39.0804 | 6311.31 | 0.00 | 6813.08 | 6813.08 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 52341.643 | -999.000 | 5.819585 | 0.00149694 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | unknown | 7/21 15:20:00 | 52341.64 | 52341.64 | 5.819585 | 21.82 | 13.44 | 0.00844103 | 12.80 | 10.21 | 0.00844103 | 33.60 | 0.00543030 | 14.90 | 0.0000 | 21.11 | 0.00844103 | 43.9617 | 48251.95 | 0.00 | 41841.15 | 41841.15 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 35966.784 | 35966.784 | 1.910331 | 0.00079464 | 818.831 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 38824.19 | 35966.78 | 1.910331 | 21.11 | 12.41 | 0.00752472 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00752472 | 39.2487 | 35967.01 | 0.00 | 38827.33 | 38827.33 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 61025.791 | -999.000 | 6.409480 | 0.00174530 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | 7/21 15:10:00 | 61025.79 | 58698.87 | 6.409480 | 21.82 | 13.67 | 0.00871223 | 12.80 | 10.21 | 0.00850000 | 33.75 | 0.00543030 | 14.95 | 0.0000 | 21.11 | 0.00871223 | 45.3567 | 53138.35 | 0.00 | 46341.41 | 45500.52 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 36086.859 | 36086.859 | 1.916709 | 0.00079730 | 821.564 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 38953.79 | 36086.86 | 1.916709 | 21.11 | 12.41 | 0.00752607 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00752607 | 39.2557 | 36087.09 | 0.00 | 38956.95 | 38956.95 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9968.274 | -999.000 | 1.101957 | 0.00028509 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 9968.27 | 9929.97 | 1.101957 | 21.82 | 13.51 | 0.00852065 | 12.80 | 10.21 | 0.00850000 | 25.76 | 0.00543031 | 12.23 | 0.0000 | 21.11 | 0.00852065 | 44.3715 | 9136.39 | 0.00 | 7491.81 | 7491.81 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6305.123 | 6305.123 | 0.334874 | 0.00013930 | 143.545 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 6806.00 | 6305.12 | 0.334874 | 21.11 | 12.38 | 0.00749117 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00749117 | 39.0778 | 6305.20 | 0.00 | 6806.49 | 6806.49 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 9913.324 | -999.000 | 1.095838 | 0.00028351 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 9913.32 | 9874.96 | 1.095838 | 21.82 | 13.51 | 0.00852080 | 12.80 | 10.21 | 0.00850000 | 25.76 | 0.00543031 | 12.23 | 0.0000 | 21.11 | 0.00852080 | 44.3722 | 9085.66 | 0.00 | 7450.57 | 7450.57 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6311.229 | 6311.229 | 0.335198 | 0.00013944 | 143.684 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 6812.59 | 6311.23 | 0.335198 | 21.11 | 12.38 | 0.00749166 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00749166 | 39.0804 | 6311.31 | 0.00 | 6813.08 | 6813.08 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 12596.835 | 12596.835 | 0.712143 | 0.00027831 | 258.186 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12677.45 | 12596.84 | 0.712143 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00758530 | 39.8305 | 9547.23 | 0.00 | 12679.71 | 12679.71 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3095.476 | -999.000 | 0.342462 | 0.00008853 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3095.48 | 3085.22 | 0.342462 | 21.82 | 13.51 | 0.00851780 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00543030 | 14.32 | 0.0000 | 21.11 | 0.00851780 | 44.3568 | 2839.37 | 0.00 | 2326.09 | 2326.09 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1957.220 | 1957.220 | 0.103951 | 0.00004324 | 44.557 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2112.65 | 1957.22 | 0.103951 | 21.11 | 12.46 | 0.00758425 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00758425 | 39.5575 | 1957.24 | 0.00 | 2112.85 | 2112.85 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3059.008 | -999.000 | 0.338410 | 0.00008749 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3059.01 | 3048.77 | 0.338410 | 21.82 | 13.51 | 0.00851798 | 12.80 | 10.21 | 0.00850000 | 31.83 | 0.00543030 | 14.32 | 0.0000 | 21.11 | 0.00851798 | 44.3578 | 2805.78 | 0.00 | 2298.71 | 2298.71 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1961.644 | 1961.644 | 0.104186 | 0.00004334 | 44.658 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2117.42 | 1961.64 | 0.104186 | 21.11 | 12.46 | 0.00758517 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00758517 | 39.5622 | 1961.67 | 0.00 | 2117.63 | 2117.63 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11417.889 | -999.000 | 1.234427 | 0.00032654 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 11417.89 | 11202.85 | 1.234427 | 21.82 | 13.58 | 0.00860277 | 12.80 | 10.21 | 0.00850000 | 33.90 | 0.00543030 | 15.00 | 0.0000 | 21.11 | 0.00860277 | 44.7941 | 10234.33 | 0.00 | 8619.81 | 8619.81 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 9430.936 | 9430.936 | 0.500899 | 0.00020837 | 214.700 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 10179.88 | 9430.94 | 0.500899 | 21.11 | 12.48 | 0.00760170 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.11 | 0.00760170 | 39.6466 | 9431.02 | 0.00 | 10180.92 | 10180.92 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14149.208 | 14149.208 | 1.779926 | 0.00031261 | 263.043 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 14229.86 | 14149.21 | 1.779926 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00768892 | 40.3686 | 6526.06 | 0.00 | 14231.73 | 14231.73 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14286.772 | 14286.772 | 1.781847 | 0.00031565 | 265.854 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 14368.18 | 14286.77 | 1.781847 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00769470 | 40.3985 | 6655.31 | 0.00 | 14370.08 | 14370.08 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 5178.429 | 5178.429 | 0.551762 | 0.00011441 | 98.224 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 5207.15 | 5178.43 | 0.551762 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00708076 | 37.2167 | 2819.18 | 0.00 | 5207.96 | 5207.96 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8535.409 | 8535.409 | 0.367569 | 0.00018858 | 185.010 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 8587.73 | 8535.41 | 0.367569 | 16.70 | 11.23 | 0.00800000 | 40.00 | 18.73 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00774241 | 40.6455 | 6960.95 | 0.00 | 8589.94 | 8589.94 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 403126.320 | -999.000 | 23.224576 | 0.01152936 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 403126.32 | 403126.32 | 23.224576 | 27.97 | 15.11 | 0.00797380 | 10.55 | 8.80 | 0.00797380 | 33.90 | 0.00543030 | 15.00 | 40.1540 | 23.99 | 0.00949254 | 41.4337 | 259264.35 | 0.00 | 344273.78 | 344273.78 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 236776.796 | 236776.796 | 6.967373 | 0.00523129 | 3168.567 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 155991.69 | 236776.80 | 6.967373 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.23 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 133.8467 | 21.00 | 0.00753026 | 39.5461 | 68847.49 | 0.00 | 155665.62 | 155665.62 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 45130.466 | -999.000 | 2.051199 | 0.00129073 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 45130.47 | 45130.47 | 2.051199 | 33.90 | 15.00 | 0.00543030 | 10.54 | 7.12 | 0.00543030 | 33.90 | 0.00543030 | 15.00 | 100.0000 | 21.11 | 0.00858210 | 44.6874 | 145774.93 | 0.00 | 49767.40 | 49767.40 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20912.173 | 20912.173 | 0.615360 | 0.00046203 | 279.848 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 13777.22 | 20912.17 | 0.615360 | -17.90 | -17.90 | 0.00095524 | 16.70 | 11.23 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 333.3333 | 21.11 | 0.00752597 | 39.2552 | 110637.05 | 0.00 | 13748.42 | 13748.42 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 5488.082 | 5488.082 | 1.280518 | 0.00012125 | 97.114 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 1.1171 | 1.132922 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 5520.25 | 5488.08 | 1.0000 | 1.25162652 | 1.280518 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.12124009 | 60.00 | 49.00 | 11.00 | 0.000 | 5520.25 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 0.00 | 0.00 | 5520.63 | 5520.63 | 1.25162652 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 20.93 | 14.81 | 0.00800000 | 41345.5 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4198.413 | 4198.413 | 0.180829 | 0.00009276 | 90.999 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 0.8548 | 0.866692 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 4224.15 | 4198.41 | 1.0000 | 0.17674886 | 0.180829 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.09274934 | 60.00 | 49.00 | 11.00 | 0.000 | 4224.15 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00723064 | 21.00 | 0.00723064 | 37.9950 | 3424.97 | 0.00 | 4225.24 | 4225.24 | 0.17674886 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60840.0 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1525.186 | 1525.186 | 0.137544 | 0.00003370 | 29.612 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 0.3107 | 0.314849 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1535.43 | 1525.19 | 1.0000 | 0.13444113 | 0.137544 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.03369368 | 60.00 | 49.00 | 11.00 | 0.000 | 1535.43 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00739408 | 21.00 | 0.00739408 | 38.8391 | 936.44 | 0.00 | 1535.57 | 1535.57 | 0.13444113 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 27.80 | 17.27 | 0.00800000 | 48356.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1988.791 | 1988.791 | 0.085660 | 0.00004394 | 43.106 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 0.4049 | 0.410552 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2000.98 | 1988.79 | 1.0000 | 0.08372727 | 0.085660 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.04393542 | 60.00 | 49.00 | 11.00 | 0.000 | 2000.98 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00724737 | 21.00 | 0.00724737 | 38.0774 | 1622.23 | 0.00 | 2001.50 | 2001.50 | 0.08372727 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60839.7 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1546.723 | 1546.723 | 0.086573 | 0.00003417 | 31.754 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 0.3150 | 0.319295 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 1556.62 | 1546.72 | 1.0000 | 0.08461993 | 0.086573 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.03416947 | 60.00 | 49.00 | 11.00 | 0.000 | 1556.62 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00727514 | 21.00 | 0.00727514 | 38.2216 | 1176.24 | 0.00 | 1556.90 | 1556.90 | 0.08461993 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 34.64 | 19.52 | 0.00800000 | 55333.4 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2701.617 | 2701.617 | 0.116361 | 0.00005969 | 58.557 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 0.5501 | 0.557703 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2718.18 | 2701.62 | 1.0000 | 0.11373611 | 0.116361 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.05968283 | 60.00 | 49.00 | 11.00 | 0.000 | 2718.18 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00722871 | 21.00 | 0.00722871 | 37.9824 | 2203.79 | 0.00 | 2718.88 | 2718.88 | 0.11373611 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60839.9 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13219.204 | 13219.204 | 1.014168 | 0.00029206 | 260.367 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 2.6928 | 2.728883 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 13306.93 | 13219.20 | 1.0000 | 0.99128623 | 1.014168 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.29203237 | 60.00 | 49.00 | 11.00 | 0.000 | 13306.93 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00724905 | 21.00 | 0.00724905 | 38.0902 | 8881.06 | 0.00 | 13308.45 | 13308.45 | 0.99128623 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 29.77 | 17.94 | 0.00800000 | 50360.2 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 30678.440 | 30678.440 | 2.841101 | 0.00067780 | 593.878 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 6.2450 | 6.333048 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 30860.88 | 30678.44 | 1.0000 | 2.77699854 | 2.841101 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.67773349 | 60.00 | 49.00 | 11.00 | 0.000 | 30860.88 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00727844 | 21.00 | 0.00727844 | 38.2390 | 18520.30 | 0.00 | 30863.49 | 30863.49 | 2.77699854 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 27.50 | 17.17 | 0.00800000 | 48048.7 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11597.058 | -999.000 | 1.282604 | 0.00033167 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6764 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.282604 | 1.25366527 | 4197.9300 | 999.8980 | 17.79096966 | 15.03 | 6.70 | 8.33 | 622128.09 | 1.8641 | 1.864060 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | 11597.06 | 11556.10 | 1.0000 | 1.25366527 | 1.282604 | 21.82 | 13.51 | 0.00851898 | 43572.7 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.33163436 | 6.70 | 13.38 | 8.33 | 0.000 | 11597.06 | 31.83 | 0.00543030 | 14.32 | 0.00000000 | 0.0000 | 21.11 | 0.00851898 | 21.11 | 0.00851898 | 44.3629 | 10634.13 | 0.00 | 8715.15 | 8715.15 | 1.25366527 | 21.82 | 15.61 | 0.00851898 | 43572.7 | 15.01 | 13.01 | 0.00851898 | 36621.0 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6305.123 | 6305.123 | 0.334874 | 0.00013930 | 143.545 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.282604 | 1.25366527 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 1.3773 | 1.301587 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 6806.00 | 6305.12 | 1.0000 | 0.32731801 | 0.334874 | 21.11 | 12.38 | 0.00749117 | 40240.5 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.13928977 | 60.00 | 49.00 | 11.00 | 0.000 | 6806.00 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00749117 | 21.11 | 0.00749117 | 39.0778 | 6305.20 | 0.00 | 6806.49 | 6806.49 | 0.32731801 | 16.60 | 12.64 | 0.00749117 | 35646.5 | 37.01 | 19.87 | 0.00749117 | 56441.2 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11456.092 | -999.000 | 1.266942 | 0.00032764 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6767 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.266942 | 1.23835700 | 4197.9300 | 999.8980 | 17.79096966 | 15.03 | 6.70 | 8.33 | 622128.09 | 1.8414 | 1.841402 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | 11456.09 | 11415.19 | 1.0000 | 1.23835700 | 1.266942 | 21.82 | 13.51 | 0.00851918 | 43573.2 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.32760325 | 6.70 | 13.38 | 8.33 | 0.000 | 11456.09 | 31.83 | 0.00543030 | 14.32 | 0.00000000 | 0.0000 | 21.11 | 0.00851918 | 21.11 | 0.00851918 | 44.3639 | 10504.28 | 0.00 | 8609.31 | 8609.31 | 1.23835700 | 21.82 | 15.61 | 0.00851918 | 43573.2 | 15.00 | 13.01 | 0.00851918 | 36621.0 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6311.229 | 6311.229 | 0.335198 | 0.00013944 | 143.684 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.266942 | 1.23835700 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 1.3786 | 1.302847 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 6812.59 | 6311.23 | 1.0000 | 0.32763499 | 0.335198 | 21.11 | 12.38 | 0.00749166 | 40241.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.13942466 | 60.00 | 49.00 | 11.00 | 0.000 | 6812.59 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00749166 | 21.11 | 0.00749166 | 39.0804 | 6311.31 | 0.00 | 6813.08 | 6813.08 | 0.32763499 | 16.60 | 12.64 | 0.00749166 | 35647.7 | 37.01 | 19.87 | 0.00749166 | 56442.5 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 52341.643 | -999.000 | 5.819585 | 0.00149694 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.5314 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.819585 | 5.68828124 | 4197.9300 | 999.8980 | 17.79096966 | 15.03 | 6.70 | 8.33 | 622128.09 | 8.4133 | 8.413165 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | unknown | unknown | unknown | 7/21 15:20:00 | 52341.64 | 52341.64 | 1.0000 | 5.68828124 | 5.819585 | 21.82 | 13.44 | 0.00844103 | 43375.0 | 12.80 | 10.21 | 0.00844103 | 34322.2 | 1.49678371 | 6.70 | 13.38 | 8.33 | 0.000 | 52341.64 | 33.60 | 0.00543030 | 14.90 | 0.00000000 | 0.0000 | 21.11 | 0.00844103 | 21.11 | 0.00844103 | 43.9617 | 48251.95 | 0.00 | 41841.15 | 41841.15 | 5.68828124 | 21.82 | 15.54 | 0.00844103 | 43375.0 | 14.61 | 12.78 | 0.00844103 | 36019.3 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35966.784 | 35966.784 | 1.910331 | 0.00079464 | 818.831 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.819585 | 5.68828124 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 7.8565 | 7.424738 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 38824.19 | 35966.78 | 1.0000 | 1.86722976 | 1.910331 | 21.11 | 12.41 | 0.00752472 | 40326.6 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.79456109 | 60.00 | 49.00 | 11.00 | 0.000 | 38824.19 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00752472 | 21.11 | 0.00752472 | 39.2487 | 35967.01 | 0.00 | 38827.33 | 38827.33 | 1.86722976 | 16.60 | 12.68 | 0.00752472 | 35731.4 | 37.01 | 19.89 | 0.00752472 | 56525.5 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 61025.791 | -999.000 | 6.409480 | 0.00174530 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0356 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.409480 | 6.26486644 | 4197.9300 | 999.8980 | 17.79096966 | 15.03 | 6.70 | 8.33 | 622128.09 | 9.8092 | 9.809017 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | unknown | unknown | unknown | 7/21 15:10:00 | 61025.79 | 58698.87 | 1.0000 | 6.26486644 | 6.409480 | 21.82 | 13.67 | 0.00871223 | 44063.2 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 1.74511925 | 6.70 | 13.38 | 8.33 | 0.000 | 61025.79 | 33.75 | 0.00543030 | 14.95 | 0.00000000 | 0.0000 | 21.11 | 0.00871223 | 21.11 | 0.00871223 | 45.3567 | 53138.35 | 0.00 | 46341.41 | 45500.52 | 6.26486644 | 21.82 | 15.78 | 0.00871223 | 44063.2 | 14.70 | 13.03 | 0.00865915 | 36666.1 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36086.859 | 36086.859 | 1.916709 | 0.00079730 | 821.564 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.409480 | 6.26486644 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 7.8827 | 7.449525 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 38953.79 | 36086.86 | 1.0000 | 1.87346347 | 1.916709 | 21.11 | 12.41 | 0.00752607 | 40330.0 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.79721372 | 60.00 | 49.00 | 11.00 | 0.000 | 38953.79 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00752607 | 21.11 | 0.00752607 | 39.2557 | 36087.09 | 0.00 | 38956.95 | 38956.95 | 1.87346347 | 16.60 | 12.68 | 0.00752607 | 35734.8 | 37.01 | 19.89 | 0.00752607 | 56528.9 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9968.274 | -999.000 | 1.101957 | 0.00028509 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6795 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.101957 | 1.07709441 | 4197.9300 | 999.8980 | 17.79096966 | 15.03 | 6.70 | 8.33 | 622128.09 | 1.6023 | 1.602256 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 9968.27 | 9929.97 | 1.0000 | 1.07709441 | 1.101957 | 21.82 | 13.51 | 0.00852065 | 43577.0 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.28505696 | 6.70 | 13.38 | 8.33 | 0.000 | 9968.27 | 25.76 | 0.00543031 | 12.23 | 0.00000000 | 0.0000 | 21.11 | 0.00852065 | 21.11 | 0.00852065 | 44.3715 | 9136.39 | 0.00 | 7491.81 | 7491.81 | 1.07709441 | 21.82 | 15.61 | 0.00852065 | 43577.0 | 15.00 | 13.01 | 0.00852065 | 36621.4 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6305.123 | 6305.123 | 0.334874 | 0.00013930 | 143.545 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.101957 | 1.07709441 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 1.3773 | 1.301587 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 6806.00 | 6305.12 | 1.0000 | 0.32731801 | 0.334874 | 21.11 | 12.38 | 0.00749117 | 40240.5 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.13928977 | 60.00 | 49.00 | 11.00 | 0.000 | 6806.00 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00749117 | 21.11 | 0.00749117 | 39.0778 | 6305.20 | 0.00 | 6806.49 | 6806.49 | 0.32731801 | 16.60 | 12.64 | 0.00749117 | 35646.5 | 37.01 | 19.87 | 0.00749117 | 56441.2 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9913.324 | -999.000 | 1.095838 | 0.00028351 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6797 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.095838 | 1.07111367 | 4197.9300 | 999.8980 | 17.79096966 | 15.03 | 6.70 | 8.33 | 622128.09 | 1.5935 | 1.593424 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 9913.32 | 9874.96 | 1.0000 | 1.07111367 | 1.095838 | 21.82 | 13.51 | 0.00852080 | 43577.4 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.28348560 | 6.70 | 13.38 | 8.33 | 0.000 | 9913.32 | 25.76 | 0.00543031 | 12.23 | 0.00000000 | 0.0000 | 21.11 | 0.00852080 | 21.11 | 0.00852080 | 44.3722 | 9085.66 | 0.00 | 7450.57 | 7450.57 | 1.07111367 | 21.82 | 15.61 | 0.00852080 | 43577.4 | 15.00 | 13.01 | 0.00852080 | 36621.4 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6311.229 | 6311.229 | 0.335198 | 0.00013944 | 143.684 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.095838 | 1.07111367 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 1.3786 | 1.302847 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 6812.59 | 6311.23 | 1.0000 | 0.32763499 | 0.335198 | 21.11 | 12.38 | 0.00749166 | 40241.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.13942466 | 60.00 | 49.00 | 11.00 | 0.000 | 6812.59 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00749166 | 21.11 | 0.00749166 | 39.0804 | 6311.31 | 0.00 | 6813.08 | 6813.08 | 0.32763499 | 16.60 | 12.64 | 0.00749166 | 35647.7 | 37.01 | 19.87 | 0.00749166 | 56442.5 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12596.835 | 12596.835 | 0.712143 | 0.00027831 | 258.186 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 2.5654 | 2.600405 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 12677.45 | 12596.84 | 1.0000 | 0.69607562 | 0.712143 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.27828330 | 60.00 | 49.00 | 11.00 | 0.000 | 12677.45 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00758530 | 21.00 | 0.00758530 | 39.8305 | 9547.23 | 0.00 | 12679.71 | 12679.71 | 0.69607562 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 34.46 | 19.46 | 0.00800000 | 55150.7 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3095.476 | -999.000 | 0.342462 | 0.00008853 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6742 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.342462 | 0.33473543 | 4197.9300 | 999.8980 | 17.79096966 | 15.03 | 6.70 | 8.33 | 622128.09 | 0.4976 | 0.497553 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | 3095.48 | 3085.22 | 1.0000 | 0.33473543 | 0.342462 | 21.82 | 13.51 | 0.00851780 | 43569.7 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.08851953 | 6.70 | 13.38 | 8.33 | 0.000 | 3095.48 | 31.83 | 0.00543030 | 14.32 | 0.00000000 | 0.0000 | 21.11 | 0.00851780 | 21.11 | 0.00851780 | 44.3568 | 2839.37 | 0.00 | 2326.09 | 2326.09 | 0.33473543 | 21.82 | 15.60 | 0.00851780 | 43569.7 | 15.01 | 13.01 | 0.00851780 | 36620.7 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1957.220 | 1957.220 | 0.103951 | 0.00004324 | 44.557 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.342462 | 0.33473543 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 0.4275 | 0.404035 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2112.65 | 1957.22 | 1.0000 | 0.10160539 | 0.103951 | 21.11 | 12.46 | 0.00758425 | 40477.0 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.04323797 | 60.00 | 49.00 | 11.00 | 0.000 | 2112.65 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758425 | 21.11 | 0.00758425 | 39.5575 | 1957.24 | 0.00 | 2112.85 | 2112.85 | 0.10160539 | 16.60 | 12.74 | 0.00758425 | 35882.1 | 37.01 | 19.94 | 0.00758425 | 56676.9 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3059.008 | -999.000 | 0.338410 | 0.00008749 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6745 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.338410 | 0.33077503 | 4197.9300 | 999.8980 | 17.79096966 | 15.03 | 6.70 | 8.33 | 622128.09 | 0.4917 | 0.491691 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | 3059.01 | 3048.77 | 1.0000 | 0.33077503 | 0.338410 | 21.82 | 13.51 | 0.00851798 | 43570.2 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.08747667 | 6.70 | 13.38 | 8.33 | 0.000 | 3059.01 | 31.83 | 0.00543030 | 14.32 | 0.00000000 | 0.0000 | 21.11 | 0.00851798 | 21.11 | 0.00851798 | 44.3578 | 2805.78 | 0.00 | 2298.71 | 2298.71 | 0.33077503 | 21.82 | 15.61 | 0.00851798 | 43570.2 | 15.01 | 13.01 | 0.00851798 | 36620.7 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1961.644 | 1961.644 | 0.104186 | 0.00004334 | 44.658 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.338410 | 0.33077503 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 0.4285 | 0.404948 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 2117.42 | 1961.64 | 1.0000 | 0.10183508 | 0.104186 | 21.11 | 12.46 | 0.00758517 | 40479.3 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.04333571 | 60.00 | 49.00 | 11.00 | 0.000 | 2117.42 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00758517 | 21.11 | 0.00758517 | 39.5622 | 1961.67 | 0.00 | 2117.63 | 2117.63 | 0.10183508 | 16.60 | 12.74 | 0.00758517 | 35884.5 | 37.01 | 19.94 | 0.00758517 | 56679.2 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11417.889 | -999.000 | 1.234427 | 0.00032654 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8321 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.234427 | 1.20657529 | 4197.9300 | 999.8980 | 17.79096966 | 15.03 | 6.70 | 8.33 | 622128.09 | 1.8353 | 1.835261 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | 11417.89 | 11202.85 | 1.0000 | 1.20657529 | 1.234427 | 21.82 | 13.58 | 0.00860277 | 43785.3 | 12.80 | 10.21 | 0.00850000 | 34322.2 | 0.32651076 | 6.70 | 13.38 | 8.33 | 0.000 | 11417.89 | 33.90 | 0.00543030 | 15.00 | 0.00000000 | 0.0000 | 21.11 | 0.00860277 | 21.11 | 0.00860277 | 44.7941 | 10234.33 | 0.00 | 8619.81 | 8619.81 | 1.20657529 | 21.82 | 15.68 | 0.00860277 | 43785.3 | 14.82 | 13.02 | 0.00860277 | 36641.2 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9430.936 | 9430.936 | 0.500899 | 0.00020837 | 214.700 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.234427 | 1.20657529 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 2.0600 | 1.946858 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 10179.88 | 9430.94 | 1.0000 | 0.48959741 | 0.500899 | 21.11 | 12.48 | 0.00760170 | 40521.6 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.20834375 | 60.00 | 49.00 | 11.00 | 0.000 | 10179.88 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.11 | 0.00760170 | 21.11 | 0.00760170 | 39.6466 | 9431.02 | 0.00 | 10180.92 | 10180.92 | 0.48959741 | 16.60 | 12.75 | 0.00760170 | 35926.3 | 37.01 | 19.95 | 0.00760170 | 56720.8 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14149.208 | 14149.208 | 1.779926 | 0.00031261 | 263.043 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 2.8796 | 2.920866 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 14229.86 | 14149.21 | 1.0000 | 1.73976648 | 1.779926 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.31257756 | 60.00 | 49.00 | 11.00 | 0.000 | 14229.86 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00768892 | 21.00 | 0.00768892 | 40.3686 | 6526.06 | 0.00 | 14231.73 | 14231.73 | 1.73976648 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.62 | 16.16 | 0.00800000 | 45115.0 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14286.772 | 14286.772 | 1.781847 | 0.00031565 | 265.854 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 2.9076 | 2.949264 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 14368.18 | 14286.77 | 1.0000 | 1.74164474 | 1.781847 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.31561658 | 60.00 | 49.00 | 11.00 | 0.000 | 14368.18 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00769470 | 21.00 | 0.00769470 | 40.3985 | 6655.31 | 0.00 | 14370.08 | 14370.08 | 1.74164474 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.69 | 16.19 | 0.00800000 | 45185.6 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5178.429 | 5178.429 | 0.551762 | 0.00011441 | 98.224 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 1.0537 | 1.069000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 5207.15 | 5178.43 | 1.0000 | 0.53931332 | 0.551762 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.11439940 | 60.00 | 49.00 | 11.00 | 0.000 | 5207.15 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.64 | 0.00708076 | 21.00 | 0.00708076 | 37.2167 | 2819.18 | 0.00 | 5207.96 | 5207.96 | 0.53931332 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.07 | 16.67 | 0.00800000 | 46591.4 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8535.409 | 8535.409 | 0.367569 | 0.00018858 | 185.010 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 1.7378 | 1.761992 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 8587.73 | 8535.41 | 1.0000 | 0.35927541 | 0.367569 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 40.00 | 18.73 | 0.00800000 | 60796.0 | 0.18856019 | 60.00 | 49.00 | 11.00 | 0.000 | 8587.73 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.00 | 0.00774241 | 21.00 | 0.00774241 | 40.6455 | 6960.95 | 0.00 | 8589.94 | 8589.94 | 0.35927541 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.05 | 21.16 | 0.00800000 | 60843.8 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 403126.320 | -999.000 | 23.224576 | 0.01152936 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6629 | 1004.8586 | 0.9774 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 23.224576 | 22.70057390 | 4197.9300 | 999.8980 | 17.79096966 | 15.03 | 6.70 | 8.33 | 622128.09 | 64.7980 | 64.797961 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 403126.32 | 403126.32 | 1.0000 | 22.70057390 | 23.224576 | 27.97 | 15.11 | 0.00797380 | 48459.7 | 10.55 | 8.80 | 0.00797380 | 30701.3 | 11.52818562 | 6.70 | 13.38 | 8.33 | 52037.881 | 351088.44 | 33.90 | 0.00543030 | 15.00 | 9.32560000 | 40.1540 | 23.99 | 0.00968037 | 23.99 | 0.00949254 | 41.4337 | 259264.35 | 0.00 | 344273.78 | 344273.78 | 22.70057390 | 27.97 | 17.31 | 0.00797380 | 48459.7 | 13.09 | 11.69 | 0.00797380 | 33293.9 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 236776.796 | 236776.796 | 6.967373 | 0.00523129 | 3168.567 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 23.224576 | 22.70057390 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 31.5666 | 48.878590 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 155991.69 | 236776.80 | 1.0000 | 6.81017217 | 6.967373 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 5.23076034 | 60.00 | 49.00 | 11.00 | 0.000 | 155991.69 | -17.90 | 0.00095524 | -17.90 | 9.32560000 | 133.8467 | 18.61 | 0.00627377 | 21.00 | 0.00753026 | 39.5461 | 68847.49 | 0.00 | 155665.62 | 155665.62 | 6.81017217 | 16.60 | 5.28 | 0.00095524 | 19098.8 | 39.31 | 15.17 | 0.00095524 | 41956.6 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 45130.466 | -999.000 | 2.051199 | 0.00129073 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1014.9347 | 1004.8586 | 0.9774 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.00491910 | 4197.9300 | 999.8980 | 17.79096966 | 15.03 | 6.70 | 8.33 | 622128.09 | 7.2542 | 7.254208 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 45130.47 | 45130.47 | 1.0000 | 2.00491910 | 2.051199 | 33.90 | 15.00 | 0.00543030 | 47987.2 | 10.54 | 7.12 | 0.00543030 | 26572.0 | 1.29059394 | 6.70 | 13.38 | 8.33 | 2194.880 | 42935.59 | 33.90 | 0.00543030 | 15.00 | 2.05119905 | 100.0000 | 21.11 | 0.00857127 | 21.11 | 0.00858210 | 44.6874 | 145774.93 | 0.00 | 49767.40 | 49767.40 | 2.00491910 | 33.90 | 17.20 | 0.00543030 | 47987.2 | 9.44 | 7.25 | 0.00543030 | 23164.5 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20912.173 | 20912.173 | 0.615360 | 0.00046203 | 279.848 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.00491910 | 4197.9300 | 999.8980 | 10.70153694 | 71.00 | 82.00 | 11.00 | 494167.33 | 2.7880 | 4.316967 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:40:00 | 13777.22 | 20912.17 | 1.0000 | 0.60147573 | 0.615360 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 16.70 | 11.23 | 0.00800000 | 37036.7 | 0.46198177 | 60.00 | 49.00 | 11.00 | 0.000 | 13777.22 | -17.90 | 0.00095524 | -17.90 | 2.05119905 | 333.3333 | 21.11 | 0.00752625 | 21.11 | 0.00752597 | 39.2552 | 110637.05 | 0.00 | 13748.42 | 13748.42 | 0.60147573 | 16.60 | 5.28 | 0.00095524 | 19098.8 | 39.31 | 15.17 | 0.00095524 | 41956.6 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 23.22 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.001447 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.003555 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000609 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4249.83 | 1435.83 | 187.33 |
RETAIL_1_FLR_1 | 3607.00 | 4156.33 | 1117.17 |
RETAIL_2_FLR_1 | 4126.67 | 1793.50 | 244.17 |
LAUNDRY_FLR_1 | 8760.00 | 7482.33 | 7482.33 |
CAFE_FLR_1 | 6270.00 | 2587.67 | 1309.67 |
LOBBY_FLR_1 | 6217.83 | 1035.17 | 512.50 |
ROOM_1_FLR_3 | 1440.83 | 8319.00 | 1357.83 |
ROOM_2_FLR_3 | 2510.33 | 8047.17 | 2198.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 810.33 | 8683.50 | 789.67 |
ROOM_5_FLR_3 | 1370.33 | 8210.83 | 1323.33 |
ROOM_6_FLR_3 | 2409.00 | 7955.17 | 2178.17 |
ROOM_1_FLR_6 | 2126.67 | 8034.83 | 1923.00 |
ROOM_2_FLR_6 | 3422.00 | 7763.50 | 2926.50 |
ROOM_3_MULT9_FLR_6 | 1248.67 | 7659.50 | 846.67 |
BANQUET_FLR_6 | 7690.33 | 1511.00 | 1310.50 |
DINING_FLR_6 | 8500.17 | 2776.17 | 2726.17 |
KITCHEN_FLR_6 | 8760.00 | 8607.83 | 8607.83 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 8760.00 | 8760.00 | 8756.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 3945.50 | 0.00 | 3945.50 |
RETAIL_1_FLR_1 | 58.50 | 1694.17 | 58.50 | 1694.17 |
RETAIL_2_FLR_1 | 0.00 | 2784.00 | 0.00 | 2784.00 |
LAUNDRY_FLR_1 | 0.00 | 8017.17 | 0.00 | 8017.17 |
CAFE_FLR_1 | 0.00 | 3815.67 | 0.00 | 3815.67 |
LOBBY_FLR_1 | 0.00 | 4423.17 | 0.00 | 4423.17 |
ROOM_1_FLR_3 | 0.67 | 97.00 | 0.67 | 97.00 |
ROOM_2_FLR_3 | 1.33 | 91.33 | 1.33 | 91.33 |
ROOM_3_MULT19_FLR_3 | 0.00 | 15.83 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 3.33 | 114.00 | 3.33 | 114.00 |
ROOM_5_FLR_3 | 1.00 | 111.00 | 1.00 | 111.00 |
ROOM_6_FLR_3 | 2.33 | 143.67 | 2.33 | 143.67 |
ROOM_1_FLR_6 | 0.83 | 133.33 | 0.83 | 133.33 |
ROOM_2_FLR_6 | 1.50 | 124.17 | 1.50 | 124.17 |
ROOM_3_MULT9_FLR_6 | 1.17 | 363.83 | 1.17 | 363.83 |
BANQUET_FLR_6 | 0.00 | 7046.00 | 0.00 | 7046.00 |
DINING_FLR_6 | 0.00 | 7967.17 | 0.00 | 7967.17 |
KITCHEN_FLR_6 | 0.00 | 8720.17 | 0.00 | 8720.17 |
MECH_FLR_1 | 0.00 | 261.50 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 33.33 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 323.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 36.67 | 776.67 | 0.00 | 0.00 |
Facility | 324.67 | 8757.33 | 61.50 | 8757.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.75 | 106.50 | 4826.41 | 0.976 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.592 | 0.275 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.436 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 22.535 | 0.154 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.51 | 142.30 | 748.35 | 3.515 | 0.247 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 1.762 | 0.071 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.339 | 0.179 | 0.000 | 0.065 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.340 | 0.179 | 0.000 | 0.059 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.386 | 0.080 | 0.000 | 0.103 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.339 | 0.179 | 0.000 | 0.065 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.340 | 0.179 | 0.000 | 0.062 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.339 | 0.179 | 0.000 | 0.078 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.340 | 0.179 | 0.000 | 0.062 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.386 | 0.146 | 0.000 | 0.124 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 4.738 | 0.052 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 5.032 | 0.052 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 16.539 | 0.152 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.75 | 106.50 | 4826.41 | 0.000 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 0.000 | 0.004 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.000 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 0.000 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.51 | 142.30 | 748.35 | 0.000 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.96 | 422.44 | 5183.56 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.91 | 249.90 | 1010.89 | 0.000 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.91 | 249.90 | 1010.89 | 0.000 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 0.000 | 0.002 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5094.68 | 75786.65 | 21-DEC-04:00 | 361118.72 | 26-JUN-19:30 |
Electricity:Building | 2181.57 | 28412.20 | 27-MAY-05:00 | 133760.38 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 277.26 | 3246.85 | 02-JAN-02:10 | 20603.11 | 02-JAN-20:10 |
InteriorLights:Electricity | 526.02 | 4377.38 | 27-MAY-05:00 | 47387.53 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 134.15 | 1218.95 | 02-JAN-02:10 | 10970.58 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 526.02 | 4377.38 | 27-MAY-05:00 | 47387.53 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 16.86 | 204.98 | 02-JAN-02:10 | 1231.40 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 6.67 | 60.64 | 02-JAN-02:10 | 545.79 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 19.52 | 237.37 | 02-JAN-02:10 | 1425.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 7.73 | 70.23 | 02-JAN-02:10 | 632.03 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.96 | 344.68 | 02-JAN-02:10 | 2351.00 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.48 | 167.95 | 02-JAN-02:10 | 1511.55 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.50 | 68.23 | 02-JAN-02:10 | 397.38 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 1.90 | 17.25 | 02-JAN-02:10 | 155.22 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 72.84 | 1007.22 | 02-JAN-02:10 | 4973.49 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 4.90 | 44.52 | 02-JAN-02:10 | 400.68 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 23.26 | 253.09 | 27-MAY-05:00 | 2063.03 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 8.92 | 49.87 | 27-MAY-05:00 | 1097.76 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 223.47 | 2778.11 | 27-MAY-05:00 | 16492.48 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 74.46 | 666.70 | 27-MAY-05:00 | 6463.27 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 15.99 | 160.87 | 02-JAN-10:10 | 1278.06 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.08 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 15.99 | 160.85 | 02-JAN-10:10 | 1277.91 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.01 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 260.83 | 2764.15 | 02-JAN-10:10 | 21347.99 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 65.84 | 411.27 | 01-JAN-11:10 | 6580.30 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 260.91 | 2764.90 | 02-JAN-10:10 | 21353.83 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 65.86 | 411.38 | 01-JAN-11:10 | 6582.10 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 15.99 | 160.87 | 02-JAN-10:10 | 1278.06 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.08 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 15.99 | 160.85 | 02-JAN-10:10 | 1277.91 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 5.51 | 34.44 | 01-JAN-11:10 | 551.01 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 41.03 | 372.78 | 02-JAN-02:10 | 3355.01 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 41.03 | 372.78 | 02-JAN-02:10 | 3355.01 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 4.00 | 40.22 | 02-JAN-10:10 | 319.51 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 1.38 | 8.61 | 01-JAN-11:10 | 137.77 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 4.00 | 40.21 | 02-JAN-10:10 | 319.48 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 1.38 | 8.61 | 01-JAN-11:10 | 137.75 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 30.90 | 327.42 | 02-JAN-10:10 | 2528.74 | 01-JAN-08:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 7.80 | 48.72 | 01-JAN-11:10 | 779.46 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 195.49 | 2377.82 | 27-MAY-05:00 | 8675.67 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 19.63 | 128.52 | 27-MAY-05:00 | 1927.76 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 195.49 | 2377.82 | 27-MAY-05:00 | 8675.67 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 19.63 | 128.52 | 27-MAY-05:00 | 1927.76 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 444.45 | 5944.83 | 02-JAN-02:10 | 18636.09 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 13.34 | 121.20 | 02-JAN-02:10 | 1090.83 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 10.86 | 98.63 | 02-JAN-02:10 | 887.69 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 10.86 | 98.63 | 02-JAN-02:10 | 887.69 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1648.47 | 23893.67 | 02-JAN-02:10 | 88863.15 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 872.73 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 424.02 | 5682.48 | 01-JAN-00:10 | 16179.04 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 8.75 | 277.50 | 01-JAN-00:10 | 277.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 4.94 | 156.70 | 01-JAN-00:10 | 156.70 | 01-JAN-00:10 |
Refrigeration:Electricity | 48.34 | 746.85 | 29-SEP-22:30 | 2828.32 | 01-JAN-11:10 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 818.53 | 2424.71 | 07-APR-03:00 | 138047.74 | 26-JUN-18:10 |
LowTempRefrigeration:Refrigeration:Electricity | 18.39 | 0.00 | 01-JAN-11:10 | 1589.16 | 26-JUN-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 22.86 | 636.46 | 14-JUN-03:20 | 734.88 | 01-JAN-07:50 |
WaterSystems:Electricity | 90.56 | 1086.01 | 21-JUN-01:40 | 4736.97 | 14-SEP-06:30 |
Water Heater:WaterSystems:Electricity | 90.56 | 1086.01 | 21-JUN-01:40 | 4736.97 | 14-SEP-06:30 |
Fans:Electricity | 836.53 | 9448.91 | 17-JUN-07:30 | 62000.46 | 16-AUG-22:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 961.43 | 9933.38 | 29-JUL-04:40 | 64332.63 | 16-AUG-22:00 |
ExteriorEquipment:Electricity | 971.97 | 6508.89 | 02-JAN-02:20 | 62573.78 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.51 | 378.95 | 10-JUN-05:00 | 1274.84 | 02-JAN-07:20 |
ElectricityPurchased:Facility | 5094.68 | 75786.65 | 21-DEC-04:00 | 361118.72 | 26-JUN-19:30 |
ElectricityPurchased:Plant | 5094.68 | 75786.65 | 21-DEC-04:00 | 361118.72 | 26-JUN-19:30 |
Cogeneration:ElectricityPurchased | 5094.68 | 75786.65 | 21-DEC-04:00 | 361118.72 | 26-JUN-19:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5094.68 | 75786.65 | 21-DEC-04:00 | 361118.72 | 26-JUN-19:30 |
ElectricityNet:Plant | 5094.68 | 75786.65 | 21-DEC-04:00 | 361118.72 | 26-JUN-19:30 |
Cogeneration:ElectricityNet | 5094.68 | 75786.65 | 21-DEC-04:00 | 361118.72 | 26-JUN-19:30 |
General:Fans:Electricity | 836.53 | 9448.91 | 17-JUN-07:30 | 62000.46 | 16-AUG-22:00 |
ExteriorLights:Electricity | 182.70 | 0.00 | 01-JAN-07:30 | 11632.50 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 182.70 | 0.00 | 01-JAN-07:30 | 11632.50 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.79 | 01-JAN-00:10 | 187.95 | 01-JAN-07:10 |
HeatRecovery:Electricity | 103.39 | 0.00 | 09-JAN-12:50 | 8251.33 | 10-AUG-04:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 640.99 | 0.00 | 01-JAN-00:20 | 129012.21 | 26-JUN-18:10 |
General:Cooling:Electricity | 640.99 | 0.00 | 01-JAN-00:20 | 129012.21 | 26-JUN-18:10 |
Pumps:Electricity | 45.72 | 47.91 | 19-FEB-12:00 | 3893.53 | 16-AUG-22:00 |
General:Pumps:Electricity | 45.72 | 47.91 | 19-FEB-12:00 | 3893.53 | 16-AUG-22:00 |
WIRED_LTG_ELECTRICITY | 18.52 | 0.00 | 01-JAN-00:10 | 1668.04 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 4342.04 | 29270.80 | 14-MAR-01:10 | 459494.25 | 21-DEC-17:40 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 2553.19 | 15908.90 | 09-JAN-15:00 | 369882.04 | 21-DEC-17:40 |
WaterSystems:Gas | 2185.81 | 15908.90 | 09-JAN-15:00 | 178470.72 | 13-FEB-21:50 |
Water Heater:WaterSystems:Gas | 2185.81 | 15908.90 | 09-JAN-15:00 | 178470.72 | 13-FEB-21:50 |
Heating:Gas | 367.38 | 0.00 | 01-JAN-09:00 | 198710.44 | 21-DEC-17:40 |
Boiler:Heating:Gas | 367.38 | 0.00 | 01-JAN-09:00 | 198710.44 | 21-DEC-17:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2049.47 | 0.00 | 01-JAN-00:20 | 366857.65 | 29-JUL-21:20 |
PlantLoopCoolingDemand:HVAC | 2049.47 | 0.00 | 01-JAN-00:20 | 366857.65 | 29-JUL-21:20 |
CoolingCoils:PlantLoopCoolingDemand | 2049.47 | 0.00 | 01-JAN-00:20 | 366857.65 | 29-JUL-21:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 05-MAY-00:10 | 0.00 | 05-MAY-21:00 |
Water:Plant | 22864.31 | 0.00 | 05-MAY-00:10 | 0.00 | 05-MAY-21:00 |
WaterSystems:Water | 22864.31 | 0.00 | 05-MAY-00:10 | 0.00 | 05-MAY-21:00 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 11-MAY-00:40 | 0.00 | 15-MAR-18:10 |
MainsWater:Facility | 22864.31 | 0.00 | 05-MAY-00:10 | 0.00 | 05-MAY-21:00 |
MainsWater:Plant | 22864.31 | 0.00 | 05-MAY-00:10 | 0.00 | 05-MAY-21:00 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 05-MAY-00:10 | 0.00 | 05-MAY-21:00 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 11-MAY-00:40 | 0.00 | 15-MAR-18:10 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 05-MAY-00:10 | 0.00 | 02-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 05-MAY-00:10 | 0.00 | 02-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 16367.57 | 117483.46 | 23-MAR-13:10 | 1562564.29 | 27-JUN-19:40 |
EnergyTransfer:Building | 4298.52 | 70393.22 | 06-FEB-11:00 | 311522.98 | 26-JUN-22:00 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 652.87 | 9070.75 | 24-JUN-03:00 | 37536.61 | 12-JUN-18:50 |
Refrigeration:EnergyTransfer | 209.90 | 4185.08 | 17-SEP-22:20 | 10745.76 | 01-JAN-11:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 104.95 | 2092.54 | 17-SEP-22:20 | 5372.88 | 01-JAN-11:40 |
EnergyTransfer:Plant | 5951.24 | 15856.85 | 13-OCT-00:30 | 865610.46 | 29-JUL-21:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 22.43 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 82.51 | 1999.52 | 14-JUN-03:20 | 2686.44 | 01-JAN-07:50 |
PlantLoopHeatingDemand:Facility | 1062.74 | 9296.32 | 01-AUG-00:10 | 198887.99 | 23-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 786.71 | 9296.31 | 23-AUG-00:10 | 58205.24 | 13-FEB-07:20 |
WaterSystems:PlantLoopHeatingDemand | 786.71 | 9296.31 | 23-AUG-00:10 | 58205.24 | 13-FEB-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 333.94 | 4768.84 | 18-MAY-12:30 | 29988.53 | 05-NOV-13:00 |
Heating:EnergyTransfer | 156.86 | 0.00 | 01-JAN-09:00 | 84584.66 | 21-DEC-09:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4036.72 | 57856.71 | 20-DEC-15:00 | 308544.98 | 26-JUN-22:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 333.94 | 4768.84 | 18-MAY-12:30 | 29988.53 | 05-NOV-13:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 30.15 | 0.75 | 14-JAN-05:10 | 4750.25 | 05-NOV-13:00 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.22 | 0.00 | 01-JAN-00:10 | 1191.86 | 21-DEC-09:30 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 28.93 | 0.00 | 03-JAN-07:10 | 4750.25 | 05-NOV-13:00 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.42 | 317.60 | 21-DEC-10:20 | 2545.36 | 26-JUN-22:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 30.42 | 317.60 | 21-DEC-10:20 | 2545.36 | 26-JUN-22:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 21.23 | 5.19 | 23-DEC-06:10 | 2531.34 | 26-JUN-22:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 21.23 | 5.19 | 23-DEC-06:10 | 2531.34 | 26-JUN-22:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 10.05 | 0.60 | 25-DEC-02:40 | 1005.43 | 26-JUN-22:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.07 | 0.00 | 01-JAN-00:10 | 333.90 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.98 | 0.00 | 05-JAN-13:30 | 1005.43 | 26-JUN-22:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 566.72 | 5620.09 | 29-JUL-04:40 | 42089.48 | 27-JUN-19:40 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 566.72 | 5620.09 | 29-JUL-04:40 | 42089.48 | 27-JUN-19:40 |
EnergyTransfer:Zone:CAFE_FLR_1 | 185.35 | 4.13 | 06-FEB-12:10 | 18746.57 | 05-NOV-13:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 2417.71 | 21-DEC-09:30 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 185.29 | 0.00 | 05-JAN-09:10 | 18746.57 | 05-NOV-13:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 649.63 | 7169.04 | 20-DEC-15:00 | 49484.44 | 26-JUN-22:00 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 649.63 | 7169.04 | 20-DEC-15:00 | 49484.44 | 26-JUN-22:00 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 54.59 | 0.00 | 01-JAN-08:00 | 9265.80 | 01-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 14.80 | 0.00 | 01-JAN-08:00 | 6953.20 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 39.79 | 0.00 | 01-JAN-00:10 | 9265.80 | 01-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 47.49 | 0.00 | 01-JAN-08:00 | 9210.10 | 01-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 20.18 | 0.00 | 01-JAN-08:00 | 7089.95 | 20-DEC-16:30 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 27.31 | 0.00 | 01-JAN-00:10 | 9210.10 | 01-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 277.95 | 0.00 | 01-JAN-00:10 | 57592.85 | 20-JAN-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 277.95 | 0.00 | 01-JAN-00:10 | 57592.85 | 20-JAN-15:10 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 312.44 | 0.00 | 01-JAN-08:00 | 53118.32 | 30-JUN-21:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 40.96 | 0.00 | 01-JAN-08:00 | 37328.77 | 21-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 271.48 | 0.00 | 01-JAN-00:10 | 53118.32 | 30-JUN-21:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 57.69 | 0.00 | 01-JAN-08:00 | 8233.07 | 01-JUL-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 15.06 | 0.00 | 01-JAN-08:00 | 6776.32 | 20-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 42.62 | 0.00 | 01-JAN-00:10 | 8233.07 | 01-JUL-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 50.89 | 0.00 | 01-JAN-08:00 | 9485.12 | 01-JUL-08:20 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 20.51 | 0.00 | 01-JAN-08:00 | 6830.12 | 21-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 30.38 | 0.00 | 01-JAN-00:10 | 9485.12 | 01-JUL-08:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 69.37 | 2.09 | 01-MAR-19:20 | 7148.22 | 22-JUL-21:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 16.27 | 0.00 | 01-JAN-08:30 | 3316.80 | 23-DEC-07:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 53.10 | 0.00 | 01-JAN-00:10 | 7148.22 | 22-JUL-21:50 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.36 | 0.00 | 01-JAN-08:00 | 2507.09 | 16-AUG-15:20 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.57 | 0.00 | 01-JAN-08:00 | 2112.18 | 21-DEC-09:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.79 | 0.00 | 01-JAN-00:10 | 2507.09 | 16-AUG-15:20 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 15.00 | 0.00 | 01-JAN-08:00 | 2485.82 | 01-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.35 | 0.00 | 01-JAN-08:00 | 2123.05 | 20-DEC-16:40 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 7.65 | 0.00 | 01-JAN-00:10 | 2485.82 | 01-JUL-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 92.09 | 0.00 | 01-JAN-08:00 | 11494.39 | 20-JAN-13:20 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 13.10 | 0.00 | 01-JAN-00:10 | 8961.86 | 20-DEC-16:40 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 78.99 | 0.00 | 01-JAN-02:00 | 11494.39 | 20-JAN-13:20 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 367.24 | 5316.65 | 21-DEC-11:10 | 25996.15 | 26-JUN-22:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 367.24 | 5316.65 | 21-DEC-11:10 | 25996.15 | 26-JUN-22:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 406.27 | 6100.45 | 21-DEC-09:40 | 27977.18 | 26-JUN-22:00 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 406.27 | 6100.45 | 21-DEC-09:40 | 27977.18 | 26-JUN-22:00 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 547.92 | 6403.93 | 21-JUN-03:00 | 33412.81 | 12-JUN-18:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 50.78 | 2.77 | 30-OCT-20:00 | 6609.85 | 26-JUN-22:00 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 1.70 | 0.00 | 01-JAN-00:10 | 2160.59 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 49.08 | 0.00 | 01-JAN-02:10 | 6609.85 | 26-JUN-22:00 |
WaterSystems:EnergyTransfer | 786.71 | 9296.31 | 23-AUG-00:10 | 58205.24 | 13-FEB-07:20 |
WaterUse:WaterSystems:EnergyTransfer | 786.71 | 9296.31 | 23-AUG-00:10 | 58205.24 | 13-FEB-07:20 |
EnergyTransfer:HVAC | 6117.80 | 480.58 | 28-APR-12:30 | 575205.31 | 21-DEC-22:10 |
HeatingCoils:EnergyTransfer | 276.03 | 0.00 | 01-JAN-09:00 | 163369.08 | 21-DEC-09:10 |
PlantLoopHeatingDemand:HVAC | 276.03 | 0.00 | 01-JAN-09:00 | 163369.08 | 21-DEC-09:10 |
HeatingCoils:PlantLoopHeatingDemand | 276.03 | 0.00 | 01-JAN-09:00 | 163369.08 | 21-DEC-09:10 |
CoolingCoils:EnergyTransfer | 2049.47 | 0.00 | 01-JAN-00:20 | 366857.65 | 29-JUL-21:20 |
HeatRecoveryForHeating:EnergyTransfer | 3780.33 | 0.00 | 09-JAN-12:50 | 459644.84 | 20-DEC-00:10 |
HeatRecoveryForCooling:EnergyTransfer | 11.98 | 0.00 | 01-JAN-00:10 | 82095.29 | 16-AUG-14:00 |
Boilers:EnergyTransfer | 265.00 | 0.00 | 01-JAN-09:00 | 159592.97 | 21-DEC-17:40 |
Chillers:EnergyTransfer | 2076.80 | 0.00 | 01-JAN-00:20 | 370980.26 | 29-JUL-21:20 |
HeatRejection:EnergyTransfer | 2717.79 | 0.00 | 01-JAN-00:20 | 468820.15 | 26-JUN-18:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -333.935 | 0.000 | 0.000 | 125.852 | 134.155 | 143.109 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -69.180 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 1.222 | -28.926 | 0.000 | 0.000 | 13.983 | 6.674 | 10.186 | 27.476 | 0.000 | 0.245 | 0.000 | 0.000 | -13.602 | 0.000 | -9.083 | -8.175 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -30.424 | 0.000 | 0.000 | 15.245 | 7.729 | 11.795 | 0.000 | 0.000 | 0.060 | 0.000 | 0.000 | 0.000 | 0.000 | -1.996 | -2.410 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -566.713 | 0.000 | 0.000 | 8.652 | 4.900 | 658.148 | 0.000 | 0.000 | 0.145 | 0.000 | 0.000 | 0.000 | 0.000 | -6.963 | -98.170 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.062 | -185.273 | 0.000 | 0.000 | 172.099 | 8.917 | 14.341 | 76.667 | 0.000 | 0.645 | 0.000 | 0.000 | -40.208 | 0.000 | -24.180 | -23.071 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -649.610 | 0.000 | 0.000 | 500.274 | 74.463 | 149.002 | 102.036 | 0.000 | 1.418 | 0.000 | 0.000 | -54.069 | 0.000 | -48.832 | -74.683 |
ROOM_1_FLR_3 | 14.800 | -30.993 | 0.000 | -8.797 | 0.000 | 0.000 | 9.687 | 5.514 | 10.478 | 50.800 | 0.000 | 0.734 | 0.000 | 0.000 | -28.363 | 0.000 | -9.816 | -14.044 |
ROOM_2_FLR_3 | 20.184 | -18.177 | 0.000 | -9.134 | 0.000 | 0.000 | 9.591 | 5.513 | 10.477 | 33.612 | 0.000 | 0.502 | 0.000 | 0.000 | -29.404 | 0.000 | -10.144 | -13.020 |
ROOM_3_MULT19_FLR_3 | 0.000 | -265.206 | 0.000 | -12.740 | 0.000 | 0.000 | 0.000 | 65.838 | 194.997 | 321.973 | 0.000 | 0.964 | 0.000 | 0.000 | -194.932 | 0.000 | -64.403 | -46.491 |
ROOM_4_MULT19_FLR_3 | 40.960 | -149.304 | 0.000 | -122.176 | 0.000 | 0.000 | 182.900 | 65.856 | 195.050 | 77.771 | 0.000 | 3.893 | 0.000 | 0.000 | -164.261 | 0.000 | -63.878 | -66.811 |
ROOM_5_FLR_3 | 15.064 | -33.815 | 0.000 | -8.809 | 0.000 | 0.000 | 9.679 | 5.514 | 10.478 | 53.397 | 0.000 | 0.739 | 0.000 | 0.000 | -27.877 | 0.000 | -9.867 | -14.504 |
ROOM_6_FLR_3 | 20.508 | -21.263 | 0.000 | -9.119 | 0.000 | 0.000 | 9.599 | 5.513 | 10.477 | 35.943 | 0.000 | 0.509 | 0.000 | 0.000 | -28.625 | 0.000 | -10.176 | -13.366 |
ROOM_1_FLR_6 | 5.568 | -8.586 | 0.000 | -2.202 | 0.000 | 0.000 | 2.423 | 1.378 | 2.620 | 12.639 | 0.000 | 0.189 | 0.000 | 0.000 | -7.089 | 0.000 | -2.485 | -4.455 |
ROOM_2_FLR_6 | 7.349 | -5.352 | 0.000 | -2.301 | 0.000 | 0.000 | 2.392 | 1.378 | 2.619 | 8.340 | 0.000 | 0.123 | 0.000 | 0.000 | -7.360 | 0.000 | -2.561 | -4.627 |
ROOM_3_MULT9_FLR_6 | 13.102 | -64.702 | 0.000 | -14.288 | 0.000 | 0.000 | 21.700 | 7.799 | 23.098 | 74.111 | 0.000 | 1.139 | 0.001 | 0.000 | -33.354 | 0.000 | -12.349 | -16.257 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -367.201 | 0.000 | 0.000 | 277.720 | 19.635 | 175.857 | 7.286 | 0.000 | 0.154 | 0.000 | 0.000 | -23.661 | 0.000 | -7.296 | -82.494 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -406.223 | 0.000 | 0.000 | 269.093 | 19.635 | 175.857 | 6.949 | 0.000 | 0.138 | 0.000 | 0.000 | -24.766 | 0.000 | -7.462 | -33.220 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -547.603 | 0.000 | 0.000 | 18.541 | 13.339 | 540.650 | 21.317 | 0.000 | 0.014 | 0.000 | 0.000 | -18.508 | 0.000 | -7.960 | -19.790 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -21.225 | 0.000 | 0.000 | 0.000 | 18.484 | 12.472 | 0.000 | 0.000 | 0.138 | 0.000 | 0.000 | 0.000 | 0.000 | -4.286 | -5.583 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.073 | -9.979 | 0.000 | 0.000 | 0.000 | 1.898 | 3.598 | 0.000 | 0.000 | 0.099 | 7.115 | 0.000 | 0.000 | 0.000 | -2.805 | 0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 16.266 | -53.104 | 0.000 | 0.000 | 0.000 | 41.027 | 0.000 | 47.648 | 0.000 | 0.566 | 0.000 | 0.000 | -34.686 | 0.000 | -11.268 | -6.449 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 1.696 | -49.081 | 0.000 | 0.000 | 0.000 | 10.855 | 0.000 | 22.586 | 0.000 | 0.155 | 36.800 | 0.000 | -17.382 | 0.000 | -5.628 | -0.000 |
Total Facility | 137.537 | -597.398 | 19.319 | -3438.863 | 0.000 | 0.000 | 1649.429 | 526.015 | 2355.308 | 980.549 | 0.000 | 12.569 | 43.917 | 0.000 | -748.147 | 0.000 | -323.437 | -616.796 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-DEC-13:35 | 0.00 | 0.00 | 0.00 | -33740.80 | 0.00 | 0.00 | 1334.66 | 3047.38 | 3548.83 | 0.00 | 0.00 | 0.00 | 25809.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 20-JAN-13:33 | 0.00 | 0.00 | 0.00 | -5677.07 | 0.00 | 0.00 | 99.50 | 151.61 | 252.59 | 6989.98 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -151.55 | -1665.07 |
RETAIL_2_FLR_1 | 26-JUN-22:19 | 0.00 | 0.00 | 0.00 | -3175.43 | 0.00 | 0.00 | 724.64 | 210.68 | 334.29 | 0.00 | 0.00 | 0.00 | 1907.95 | 0.00 | -0.00 | 0.00 | -2.13 | 0.00 |
LAUNDRY_FLR_1 | 08-AUG-20:52 | 0.00 | 0.00 | 0.00 | -75685.73 | 0.00 | 0.00 | 171.93 | 356.16 | 41967.83 | 0.00 | 0.00 | 0.00 | 33367.70 | 0.00 | -0.00 | 0.00 | -177.89 | 0.00 |
CAFE_FLR_1 | 20-JAN-13:33 | 0.00 | 0.00 | 0.00 | -23289.95 | 0.00 | 0.00 | 1477.04 | 67.09 | 355.63 | 19686.00 | 0.00 | 0.00 | 2041.60 | 0.00 | -0.00 | 0.00 | -337.41 | 0.00 |
LOBBY_FLR_1 | 18-JUL-01:29 | 0.00 | 0.00 | 0.00 | -62818.91 | 0.00 | 0.00 | 25365.69 | 718.14 | 2111.41 | 0.00 | 0.00 | 0.00 | 36042.77 | 0.00 | -983.75 | 0.00 | -435.35 | 0.00 |
ROOM_1_FLR_3 | 06-APR-18:31 | 0.00 | -9721.58 | 0.00 | -568.34 | 0.00 | 0.00 | 293.96 | 489.08 | 484.65 | 0.00 | 0.00 | 0.00 | 10505.43 | 0.00 | -1242.96 | 0.00 | -240.23 | 0.00 |
ROOM_2_FLR_3 | 31-MAR-18:01 | 0.00 | -10015.57 | 0.00 | -621.15 | 0.00 | 0.00 | 266.80 | 489.03 | 484.60 | 1548.21 | 0.00 | 0.00 | 8108.57 | 0.00 | -0.00 | 0.00 | -260.48 | 0.00 |
ROOM_3_MULT19_FLR_3 | 10-OCT-14:01 | 0.00 | -48257.66 | 0.00 | -11638.61 | 0.00 | 0.00 | 0.00 | 411.27 | 2352.88 | 51839.48 | 0.00 | 0.00 | 5497.14 | 0.00 | -0.00 | 0.00 | -204.50 | 0.00 |
ROOM_4_MULT19_FLR_3 | 07-JUL-21:11 | 0.00 | -49966.88 | 0.00 | -9390.55 | 0.00 | 0.00 | 7737.55 | 4442.92 | 6668.31 | 0.00 | 0.00 | 0.00 | 42809.08 | 0.00 | -1968.34 | 0.00 | -332.08 | 0.00 |
ROOM_5_FLR_3 | 04-MAY-08:11 | 0.00 | -8443.63 | 0.00 | -645.84 | 0.00 | 0.00 | 76.77 | 241.10 | 453.05 | 9269.71 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -144.66 | -806.49 |
ROOM_6_FLR_3 | 01-JUL-08:11 | 0.00 | -10151.82 | 0.00 | -965.82 | 0.00 | 0.00 | 75.73 | 128.57 | 653.15 | 10066.64 | 0.00 | 0.00 | 250.58 | 0.00 | -0.00 | 0.00 | -57.03 | 0.00 |
ROOM_1_FLR_6 | 06-APR-18:31 | 0.00 | -2805.22 | 0.00 | -163.50 | 0.00 | 0.00 | 64.55 | 122.27 | 121.16 | 0.00 | 0.00 | 0.00 | 3079.21 | 0.00 | -350.07 | 0.00 | -68.40 | 0.00 |
ROOM_2_FLR_6 | 31-MAR-18:01 | 0.00 | -2895.53 | 0.00 | -177.41 | 0.00 | 0.00 | 57.14 | 122.26 | 121.15 | 347.31 | 0.00 | 0.00 | 2498.81 | 0.00 | -0.00 | 0.00 | -73.74 | 0.00 |
ROOM_3_MULT9_FLR_6 | 20-JAN-13:04 | 0.00 | -10564.57 | 0.00 | -1296.17 | 0.00 | 0.00 | 157.13 | 48.72 | 278.71 | 19861.55 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -130.70 | -8354.66 |
BANQUET_FLR_6 | 16-AUG-22:33 | 0.00 | 0.00 | 0.00 | -34487.85 | 0.00 | 0.00 | 12213.29 | 642.59 | 6747.90 | 0.00 | 0.00 | 0.00 | 15291.84 | 0.00 | -337.54 | 0.00 | -70.22 | 0.00 |
DINING_FLR_6 | 16-AUG-22:33 | 0.00 | 0.00 | 0.00 | -36762.95 | 0.00 | 0.00 | 11916.11 | 642.59 | 6747.90 | 0.00 | 0.00 | 0.00 | 17899.41 | 0.00 | -370.14 | 0.00 | -72.92 | 0.00 |
KITCHEN_FLR_6 | 07-JUL-17:31 | 0.00 | 0.00 | 0.00 | -50211.43 | 0.00 | 0.00 | 102.86 | 727.22 | 26450.81 | 667.27 | 0.00 | 0.00 | 22335.24 | 0.00 | -0.00 | 0.00 | -71.97 | 0.00 |
MECH_FLR_1 | 17-JUL-22:55 | 0.00 | 0.00 | 0.00 | -3138.83 | 0.00 | 0.00 | 0.00 | 503.85 | 353.45 | 0.00 | 0.00 | 5.22 | 2276.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 17-JUL-23:07 | 0.00 | 0.00 | 0.00 | -1264.71 | 0.00 | 0.00 | 0.00 | 34.49 | 76.47 | 0.00 | 0.00 | 0.37 | 1153.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 25-JUL-14:09 | 0.00 | 0.00 | 0.00 | -8000.05 | 0.00 | 0.00 | 0.00 | 931.95 | 0.00 | 3951.87 | 0.00 | 46.48 | 3069.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 25-JUL-14:09 | 0.00 | 0.00 | 0.00 | -8606.38 | 0.00 | 0.00 | 0.00 | 246.58 | 0.00 | 1654.61 | 0.00 | 0.22 | 6704.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-AUG-19:18 | 0.00 | -95861.26 | 0.00 | -326861.70 | 0.00 | 0.00 | 53372.67 | 47387.53 | 131131.45 | 8051.06 | 0.00 | 3498.78 | 179353.19 | 0.00 | 0.00 | 0.00 | -71.72 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 21-DEC-08:10 | 0.00 | 0.00 | 2386.08 | -0.00 | 0.00 | 0.00 | 399.75 | 242.58 | 360.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1817.71 | 0.00 | -840.16 | -731.37 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 21-DEC-09:30 | 0.00 | 0.00 | 4848.61 | -0.00 | 0.00 | 0.00 | 2394.66 | 147.82 | 508.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3902.91 | 0.00 | -2250.24 | -1745.98 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 21-DEC-09:01 | 7387.26 | 223.58 | 0.00 | -223.58 | 0.00 | 0.00 | 108.88 | 241.10 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3243.47 | 0.00 | -1012.17 | -3934.66 |
ROOM_2_FLR_3 | 21-DEC-09:01 | 7365.99 | 223.21 | 0.00 | -223.21 | 0.00 | 0.00 | 108.88 | 241.07 | 452.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3233.21 | 0.00 | -1011.93 | -3923.79 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 21-DEC-16:11 | 39071.35 | 2951.23 | 0.00 | -2951.23 | 0.00 | 0.00 | 5585.67 | 526.57 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18447.58 | 0.00 | -5170.67 | -25291.75 |
ROOM_5_FLR_3 | 20-DEC-16:11 | 6999.83 | 221.11 | 0.00 | -221.11 | 0.00 | 0.00 | 293.98 | 44.09 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3318.50 | 0.00 | -930.34 | -3289.24 |
ROOM_6_FLR_3 | 21-DEC-16:11 | 7020.06 | 219.41 | 0.00 | -219.41 | 0.00 | 0.00 | 293.98 | 44.08 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3403.86 | 0.00 | -976.05 | -3178.37 |
ROOM_1_FLR_6 | 21-DEC-09:01 | 2176.34 | 55.96 | 0.00 | -55.96 | 0.00 | 0.00 | 27.22 | 60.27 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -813.55 | 0.00 | -253.52 | -1310.02 |
ROOM_2_FLR_6 | 20-DEC-16:11 | 2175.17 | 55.49 | 0.00 | -55.49 | 0.00 | 0.00 | 73.50 | 11.02 | 50.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -790.90 | 0.00 | -233.09 | -1285.73 |
ROOM_3_MULT9_FLR_6 | 20-DEC-16:11 | 9252.32 | 355.25 | 0.00 | -355.25 | 0.00 | 0.00 | 661.46 | 62.36 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3747.11 | 0.00 | -1072.71 | -5597.60 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 23-DEC-06:02 | 0.00 | 0.00 | 670.10 | -0.00 | 0.00 | 0.00 | 0.00 | 51.74 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -304.50 | -519.30 |
CORRIDOR_FLR_3 | 23-DEC-07:02 | 0.00 | 0.00 | 6640.89 | -0.00 | 0.00 | 0.00 | 0.00 | 1118.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4863.39 | 0.00 | -1302.97 | -1592.86 |
CORRIDOR_FLR_6 | 22-DEC-06:02 | 0.00 | 0.00 | 4322.47 | -0.00 | 0.00 | 0.00 | 0.00 | 394.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2076.56 | 0.00 | -562.57 | -2077.86 |
Total Facility | 21-DEC-09:02 | -48811.88 | 132276.09 | 17865.10 | -132276.09 | 0.00 | 0.00 | 20413.97 | 19886.52 | 87870.62 | 0.00 | 0.00 | 0.00 | 9062.10 | 0.00 | -76616.61 | 0.00 | -29669.83 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 23.6875 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 23.2246 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 13.6342 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 10.5355 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6186 | 2.6186 | 1.2805 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3441 | 0.3441 | 0.1187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2528 | 0.2528 | 0.1375 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0050 | 4.0050 | 0.0401 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4936 | 1.4936 | 1.0142 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9670 | 4.9670 | 2.8411 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4964 | 2.4964 | 1.7799 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6242 | 2.6242 | 1.7818 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6655 | 2.6655 | 0.5518 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2599 | 0.2599 | 0.0026 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1048 | 0.1048 | 0.0866 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 0.7121 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6685 | 0.6685 | 0.1885 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 23.6875 | 23.2246 | 23.6875 | 10.5355 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3093 | 1.3093 | 1.2805 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1721 | 0.1721 | 0.1187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1375 | 0.1375 | 0.1375 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0025 | 2.0025 | 0.0401 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0142 | 1.0142 | 1.0142 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8411 | 2.8411 | 2.8411 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7799 | 1.7799 | 1.7799 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7818 | 1.7818 | 1.7818 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3328 | 1.3328 | 0.5518 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1300 | 0.1300 | 0.0026 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0866 | 0.0866 | 0.0866 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7121 | 0.7121 | 0.7121 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3342 | 0.3342 | 0.1885 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 13.6342 | 10.5355 | 10.5355 | 10.5355 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:57
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 61.50 |
Number of hours cooling loads not met | 8757.33 |
Number of hours not met | 8757.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 367.38 | 198710.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 640.99 | 129012.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 526.02 | 47387.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 182.70 | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.73 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 8.75 | 277.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 4.94 | 156.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.51 | 1274.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 187.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 836.53 | 62000.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 45.72 | 3893.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 103.39 | 8251.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.56 | 4736.97 | 2185.81 | 178470.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 18.39 | 1589.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 22.86 | 734.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1696.81 | 5094.68 |
Natural Gas | 1788.85 | 4342.04 |
Additional | 0.00 | 0.00 |
Total | 3485.66 | 9436.72 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 46.36 |
Space Heating | 0.00 |
Space Cooling | 56.50 |
Fans (All) | 73.73 |
Service Water Heating | 7.98 |
Receptacle Equipment | 145.30 |
Miscellaneous (All) | 449.06 |
Subtotal | 449.06 |
Natural Gas [MJ/m2] | |
Space Heating | 32.38 |
Service Water Heating | 192.66 |
Miscellaneous (All) | 382.72 |
Subtotal | 382.72 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.57 |
Space Heating | 3.89 |
Space Cooling | 6.79 |
Fans (All) | 8.86 |
Service Water Heating | 24.12 |
Receptacle Equipment | 36.42 |
Miscellaneous | 14.33 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 1660. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 2221. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2737. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1362. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.610086E+11 |
February | 0.000 | 0.649013E+11 |
March | 0.000 | 0.381947E+11 |
April | 0.000 | 0.268948E+11 |
May | 0.000 | 0.279804E+10 |
June | 0.000 | 0.113802E+08 |
July | 0.000 | 0.103877E+08 |
August | 0.000 | 0.168289E+08 |
September | 0.000 | 0.782178E+09 |
October | 0.000 | 0.267358E+11 |
November | 0.000 | 0.422275E+11 |
December | 0.000 | 0.103796E+12 |
Annual Sum or Average | 0.367377E+12 | |
Minimum of Months | 0.000 | 0.103877E+08 |
Maximum of Months | 0.000 | 0.103796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.610086E+11 |
February | 0.000 | 0.649013E+11 |
March | 0.000 | 0.381947E+11 |
April | 0.000 | 0.268948E+11 |
May | 0.000 | 0.279804E+10 |
June | 0.000 | 0.113802E+08 |
July | 0.000 | 0.103877E+08 |
August | 0.000 | 0.168289E+08 |
September | 0.000 | 0.782178E+09 |
October | 0.000 | 0.267358E+11 |
November | 0.000 | 0.422275E+11 |
December | 0.000 | 0.103796E+12 |
Annual Sum or Average | 0.367377E+12 | |
Minimum of Months | 0.000 | 0.103877E+08 |
Maximum of Months | 0.000 | 0.103796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.610086E+11 |
February | 0.000 | 0.649013E+11 |
March | 0.000 | 0.381947E+11 |
April | 0.000 | 0.268948E+11 |
May | 0.000 | 0.279804E+10 |
June | 0.000 | 0.113802E+08 |
July | 0.000 | 0.103877E+08 |
August | 0.000 | 0.168289E+08 |
September | 0.000 | 0.782178E+09 |
October | 0.000 | 0.267358E+11 |
November | 0.000 | 0.422275E+11 |
December | 0.000 | 0.103796E+12 |
Annual Sum or Average | 0.367377E+12 | |
Minimum of Months | 0.000 | 0.103877E+08 |
Maximum of Months | 0.000 | 0.103796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.610086E+11 |
February | 0.000 | 0.649013E+11 |
March | 0.000 | 0.381947E+11 |
April | 0.000 | 0.268948E+11 |
May | 0.000 | 0.279804E+10 |
June | 0.000 | 0.113802E+08 |
July | 0.000 | 0.103877E+08 |
August | 0.000 | 0.168289E+08 |
September | 0.000 | 0.782178E+09 |
October | 0.000 | 0.267358E+11 |
November | 0.000 | 0.422275E+11 |
December | 0.000 | 0.103796E+12 |
Annual Sum or Average | 0.367377E+12 | |
Minimum of Months | 0.000 | 0.103877E+08 |
Maximum of Months | 0.000 | 0.103796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.610086E+11 |
February | 0.000 | 0.649013E+11 |
March | 0.000 | 0.381947E+11 |
April | 0.000 | 0.268948E+11 |
May | 0.000 | 0.279804E+10 |
June | 0.000 | 0.113802E+08 |
July | 0.000 | 0.103877E+08 |
August | 0.000 | 0.168289E+08 |
September | 0.000 | 0.782178E+09 |
October | 0.000 | 0.267358E+11 |
November | 0.000 | 0.422275E+11 |
December | 0.000 | 0.103796E+12 |
Annual Sum or Average | 0.367377E+12 | |
Minimum of Months | 0.000 | 0.103877E+08 |
Maximum of Months | 0.000 | 0.103796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.610086E+11 |
February | 0.000 | 0.649013E+11 |
March | 0.000 | 0.381947E+11 |
April | 0.000 | 0.268948E+11 |
May | 0.000 | 0.279804E+10 |
June | 0.000 | 0.113802E+08 |
July | 0.000 | 0.103877E+08 |
August | 0.000 | 0.168289E+08 |
September | 0.000 | 0.782178E+09 |
October | 0.000 | 0.267358E+11 |
November | 0.000 | 0.422275E+11 |
December | 0.000 | 0.103796E+12 |
Annual Sum or Average | 0.367377E+12 | |
Minimum of Months | 0.000 | 0.103877E+08 |
Maximum of Months | 0.000 | 0.103796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.610086E+11 |
February | 0.000 | 0.649013E+11 |
March | 0.000 | 0.381947E+11 |
April | 0.000 | 0.268948E+11 |
May | 0.000 | 0.279804E+10 |
June | 0.000 | 0.113802E+08 |
July | 0.000 | 0.103877E+08 |
August | 0.000 | 0.168289E+08 |
September | 0.000 | 0.782178E+09 |
October | 0.000 | 0.267358E+11 |
November | 0.000 | 0.422275E+11 |
December | 0.000 | 0.103796E+12 |
Annual Sum or Average | 0.367377E+12 | |
Minimum of Months | 0.000 | 0.103877E+08 |
Maximum of Months | 0.000 | 0.103796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.610086E+11 |
February | 0.000 | 0.649013E+11 |
March | 0.000 | 0.381947E+11 |
April | 0.000 | 0.268948E+11 |
May | 0.000 | 0.279804E+10 |
June | 0.000 | 0.113802E+08 |
July | 0.000 | 0.103877E+08 |
August | 0.000 | 0.168289E+08 |
September | 0.000 | 0.782178E+09 |
October | 0.000 | 0.267358E+11 |
November | 0.000 | 0.422275E+11 |
December | 0.000 | 0.103796E+12 |
Annual Sum or Average | 0.367377E+12 | |
Minimum of Months | 0.000 | 0.103877E+08 |
Maximum of Months | 0.000 | 0.103796E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.610086E+11 |
February | 0.000 | 0.649013E+11 |
March | 0.000 | 0.381947E+11 |
April | 0.000 | 0.268948E+11 |
May | 0.000 | 0.279804E+10 |
June | 0.000 | 0.113802E+08 |
July | 0.000 | 0.103877E+08 |
August | 0.000 | 0.168289E+08 |
September | 0.000 | 0.782178E+09 |
October | 0.000 | 0.267358E+11 |
November | 0.000 | 0.422275E+11 |
December | 0.000 | 0.103796E+12 |
Annual Sum or Average | 0.367377E+12 | |
Minimum of Months | 0.000 | 0.103877E+08 |
Maximum of Months | 0.000 | 0.103796E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259108E+11 | 30606.18 | 20-JAN-13:03 | 21.00 | 6.93 | 0.903978E+10 | 5704.97 | 13-JAN-22:10 | -6.3 | -7.8 |
February | 0.225166E+11 | 29497.67 | 18-FEB-13:33 | 20.00 | 7.70 | 0.799915E+10 | 5594.03 | 01-FEB-22:10 | -7.8 | -7.9 |
March | 0.237008E+11 | 26864.50 | 14-MAR-18:06 | 17.67 | 5.74 | 0.862233E+10 | 5475.49 | 01-MAR-22:10 | -4.2 | -4.2 |
April | 0.232802E+11 | 27643.07 | 19-APR-17:53 | 18.00 | 8.93 | 0.830901E+10 | 5350.28 | 14-APR-21:10 | 0.83 | -0.8 |
May | 0.245262E+11 | 29719.90 | 10-MAY-20:53 | 21.00 | 8.14 | 0.844962E+10 | 5316.85 | 02-MAY-21:10 | 3.20 | 0.33 |
June | 0.267963E+11 | 30119.13 | 29-JUN-20:33 | 21.23 | 11.87 | 0.804658E+10 | 5118.17 | 26-JUN-21:10 | 28.17 | 11.13 |
July | 0.283257E+11 | 30662.07 | 15-JUL-00:13 | 21.67 | 14.40 | 0.829142E+10 | 5284.46 | 17-JUL-21:10 | 28.50 | 13.41 |
August | 0.321369E+11 | 31216.95 | 11-AUG-00:53 | 21.00 | 14.58 | 0.838438E+10 | 5172.57 | 22-AUG-21:49 | 15.00 | 11.80 |
September | 0.342712E+11 | 33046.67 | 26-SEP-09:07 | 23.08 | 9.49 | 0.843357E+10 | 5864.45 | 22-SEP-21:10 | 8.90 | 3.53 |
October | 0.322185E+11 | 32822.37 | 07-OCT-10:52 | 21.00 | 9.12 | 0.976650E+10 | 6281.27 | 27-OCT-21:10 | 3.00 | 3.00 |
November | 0.302870E+11 | 33469.39 | 05-NOV-12:30 | 20.50 | 6.06 | 0.979173E+10 | 6342.93 | 17-NOV-22:10 | 6.00 | 2.20 |
December | 0.299682E+11 | 33741.24 | 01-DEC-13:35 | 21.67 | 7.85 | 0.986658E+10 | 6174.31 | 15-DEC-22:10 | 2.17 | -0.7 |
Annual Sum or Average | 0.333938E+12 | 0.105001E+12 | ||||||||
Minimum of Months | 0.225166E+11 | 26864.50 | 17.67 | 5.74 | 0.799915E+10 | 5118.17 | -7.8 | -7.9 | ||
Maximum of Months | 0.342712E+11 | 33741.24 | 23.08 | 14.58 | 0.986658E+10 | 6342.93 | 28.50 | 13.41 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196043E+10 | 5677.29 | 20-JAN-13:33 | 21.00 | 6.93 | 0.790067E+09 | 542.27 | 20-JAN-22:10 | 7.83 | 1.98 |
February | 0.153678E+10 | 5418.24 | 18-FEB-13:08 | 20.00 | 7.71 | 0.691487E+09 | 521.60 | 17-FEB-22:10 | 7.00 | 3.15 |
March | 0.176028E+10 | 5127.37 | 14-MAR-13:07 | 23.83 | 7.81 | 0.762362E+09 | 536.35 | 15-MAR-21:10 | 12.83 | 3.03 |
April | 0.122994E+10 | 4469.74 | 07-APR-12:47 | 20.83 | 8.37 | 0.722163E+09 | 502.67 | 07-APR-21:10 | 11.83 | 6.32 |
May | 0.210212E+10 | 4117.48 | 06-MAY-13:25 | 25.00 | 10.45 | 0.819528E+09 | 510.14 | 16-MAY-23:10 | 14.83 | 9.17 |
June | 0.342730E+10 | 4054.97 | 26-JUN-22:19 | 24.43 | 10.20 | 0.828711E+09 | 580.34 | 26-JUN-21:10 | 28.17 | 11.13 |
July | 0.361127E+10 | 4275.12 | 25-JUL-14:09 | 25.00 | 16.00 | 0.855415E+09 | 600.05 | 17-JUL-21:10 | 28.50 | 13.41 |
August | 0.362893E+10 | 4520.73 | 27-AUG-12:08 | 24.33 | 15.04 | 0.860755E+09 | 537.44 | 16-AUG-21:10 | 25.67 | 11.08 |
September | 0.348898E+10 | 4980.37 | 27-SEP-12:25 | 25.80 | 8.75 | 0.827953E+09 | 525.17 | 07-SEP-21:00 | 16.60 | 8.96 |
October | 0.243938E+10 | 5367.46 | 10-OCT-12:53 | 24.00 | 7.90 | 0.809994E+09 | 554.37 | 11-OCT-21:10 | 9.67 | 4.55 |
November | 0.210889E+10 | 5599.86 | 07-NOV-12:53 | 20.00 | 6.97 | 0.775578E+09 | 539.09 | 07-NOV-22:10 | 7.00 | 1.99 |
December | 0.163207E+10 | 5420.97 | 02-DEC-13:33 | 21.00 | 7.10 | 0.746694E+09 | 500.92 | 14-DEC-22:10 | 1.83 | -1.7 |
Annual Sum or Average | 0.289264E+11 | 0.949071E+10 | ||||||||
Minimum of Months | 0.122994E+10 | 4054.97 | 20.00 | 6.93 | 0.691487E+09 | 500.92 | 1.83 | -1.7 | ||
Maximum of Months | 0.362893E+10 | 5677.29 | 25.80 | 16.00 | 0.860755E+09 | 600.05 | 28.50 | 13.41 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217846E+10 | 3009.23 | 20-JAN-13:43 | 21.00 | 6.93 | 0.102085E+10 | 689.59 | 20-JAN-22:10 | 7.83 | 1.98 |
February | 0.183156E+10 | 2975.97 | 18-FEB-13:08 | 20.00 | 7.71 | 0.912718E+09 | 680.79 | 17-FEB-22:10 | 7.00 | 3.15 |
March | 0.215163E+10 | 3049.29 | 13-MAR-15:43 | 23.00 | 6.93 | 0.101667E+10 | 686.49 | 10-MAR-22:10 | 8.83 | 2.52 |
April | 0.198729E+10 | 2776.29 | 20-APR-17:13 | 18.33 | 8.38 | 0.973293E+09 | 661.16 | 07-APR-21:10 | 11.83 | 6.32 |
May | 0.262720E+10 | 2979.56 | 10-MAY-20:53 | 21.00 | 8.14 | 0.102152E+10 | 669.04 | 25-MAY-21:10 | 9.00 | 6.80 |
June | 0.322039E+10 | 3175.84 | 26-JUN-22:19 | 24.43 | 10.20 | 0.973182E+09 | 689.65 | 26-JUN-21:10 | 28.17 | 11.13 |
July | 0.332201E+10 | 3136.17 | 17-JUL-22:55 | 25.00 | 12.77 | 0.999721E+09 | 708.42 | 17-JUL-21:10 | 28.50 | 13.41 |
August | 0.331167E+10 | 3146.04 | 16-AUG-22:33 | 21.33 | 11.23 | 0.100286E+10 | 648.81 | 16-AUG-21:10 | 25.67 | 11.08 |
September | 0.308377E+10 | 3055.57 | 13-SEP-17:58 | 21.10 | 13.39 | 0.980043E+09 | 664.85 | 15-SEP-21:10 | 12.28 | 6.12 |
October | 0.247906E+10 | 3064.16 | 11-OCT-15:17 | 25.33 | 9.14 | 0.103778E+10 | 694.38 | 11-OCT-21:10 | 9.67 | 4.55 |
November | 0.223726E+10 | 3030.15 | 07-NOV-15:14 | 21.67 | 7.25 | 0.100069E+10 | 697.37 | 16-NOV-22:10 | 5.67 | 3.72 |
December | 0.199428E+10 | 3014.85 | 02-DEC-14:03 | 21.17 | 7.23 | 0.997783E+09 | 678.57 | 15-DEC-22:10 | 2.17 | -0.7 |
Annual Sum or Average | 0.304246E+11 | 0.119371E+11 | ||||||||
Minimum of Months | 0.183156E+10 | 2776.29 | 18.33 | 6.93 | 0.912718E+09 | 648.81 | 2.17 | -0.7 | ||
Maximum of Months | 0.332201E+10 | 3175.84 | 25.33 | 13.39 | 0.103778E+10 | 708.42 | 28.50 | 13.41 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.944828E+09 | 2319.18 | 20-JAN-13:20 | 21.00 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.706464E+09 | 2235.77 | 18-FEB-12:51 | 20.00 | 7.71 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.111061E+10 | 2708.47 | 14-MAR-17:53 | 18.00 | 5.88 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.111212E+10 | 2683.74 | 20-APR-18:59 | 17.00 | 8.16 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.210838E+10 | 3003.70 | 17-MAY-18:26 | 22.50 | 10.25 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.290464E+10 | 3132.25 | 14-JUN-21:14 | 22.57 | 12.21 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.303553E+10 | 3138.95 | 17-JUL-22:55 | 25.00 | 12.77 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.287800E+10 | 3083.01 | 16-AUG-22:06 | 23.33 | 13.04 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.256244E+10 | 3031.12 | 10-SEP-19:43 | 24.03 | 10.01 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.172924E+10 | 2724.21 | 11-OCT-15:31 | 24.67 | 8.86 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.130104E+10 | 2568.10 | 09-NOV-08:45 | 15.17 | 7.58 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.831815E+09 | 2277.38 | 02-DEC-12:42 | 20.83 | 7.07 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.212251E+11 | 0.00 | ||||||||
Minimum of Months | 0.706464E+09 | 2235.77 | 15.17 | 5.88 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.303553E+10 | 3138.95 | 25.00 | 13.04 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573634E+09 | 957.69 | 20-JAN-13:14 | 21.00 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.482444E+09 | 935.70 | 18-FEB-13:08 | 20.00 | 7.71 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.653574E+09 | 986.60 | 14-MAR-14:40 | 23.00 | 7.55 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.643244E+09 | 959.60 | 20-APR-12:49 | 21.67 | 9.11 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.907119E+09 | 1007.90 | 17-MAY-08:58 | 25.00 | 11.70 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.121738E+10 | 1249.68 | 26-JUN-22:19 | 24.43 | 10.20 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.128406E+10 | 1264.76 | 17-JUL-23:07 | 24.33 | 12.38 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.122887E+10 | 1224.89 | 16-AUG-22:06 | 23.33 | 13.04 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.108770E+10 | 1134.92 | 13-SEP-17:03 | 25.68 | 13.73 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.764055E+09 | 999.12 | 11-OCT-16:52 | 22.00 | 8.31 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.629204E+09 | 971.72 | 07-NOV-13:35 | 21.33 | 7.21 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.507433E+09 | 940.32 | 02-DEC-14:06 | 21.17 | 7.23 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.997872E+10 | 0.00 | ||||||||
Minimum of Months | 0.482444E+09 | 935.70 | 20.00 | 6.93 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.128406E+10 | 1264.76 | 25.68 | 13.73 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.461951E+11 | 62667.81 | 20-JAN-20:52 | 7.00 | 1.59 | 0.833765E+09 | 776.07 | 20-JAN-22:10 | 7.83 | 1.98 |
February | 0.415403E+11 | 62454.87 | 17-FEB-20:52 | 7.00 | 3.15 | 0.752154E+09 | 770.46 | 27-FEB-22:10 | 2.00 | -0.7 |
March | 0.468936E+11 | 62793.43 | 09-MAR-20:52 | 11.00 | 1.67 | 0.835122E+09 | 778.80 | 10-MAR-22:10 | 8.83 | 2.52 |
April | 0.453249E+11 | 62959.69 | 19-APR-19:52 | 15.00 | 7.29 | 0.800411E+09 | 793.60 | 20-APR-20:00 | 14.00 | 7.95 |
May | 0.488484E+11 | 68100.66 | 04-MAY-19:52 | 16.00 | 7.76 | 0.806449E+09 | 878.34 | 19-MAY-21:10 | 10.00 | 6.73 |
June | 0.494539E+11 | 74968.43 | 29-JUN-20:32 | 21.23 | 11.87 | 0.750996E+09 | 810.97 | 26-JUN-21:10 | 28.17 | 11.13 |
July | 0.507972E+11 | 70568.32 | 17-JUL-20:52 | 29.00 | 13.51 | 0.773637E+09 | 879.16 | 17-JUL-21:10 | 28.50 | 13.41 |
August | 0.508305E+11 | 75689.61 | 08-AUG-20:52 | 20.00 | 13.15 | 0.772576E+09 | 854.33 | 11-AUG-22:10 | 22.67 | 9.42 |
September | 0.483296E+11 | 66445.65 | 14-SEP-20:32 | 15.90 | 6.60 | 0.751784E+09 | 842.90 | 07-SEP-21:00 | 16.60 | 8.96 |
October | 0.475507E+11 | 69144.18 | 20-OCT-19:51 | 10.00 | 1.50 | 0.838127E+09 | 900.05 | 20-OCT-21:10 | 10.17 | 1.47 |
November | 0.452116E+11 | 62842.93 | 08-NOV-20:52 | 7.00 | 4.42 | 0.811528E+09 | 777.41 | 07-NOV-22:10 | 7.00 | 1.99 |
December | 0.457429E+11 | 68751.58 | 14-DEC-20:51 | 2.00 | -1.4 | 0.829794E+09 | 887.10 | 14-DEC-22:10 | 1.83 | -1.7 |
Annual Sum or Average | 0.566719E+12 | 0.955634E+10 | ||||||||
Minimum of Months | 0.415403E+11 | 62454.87 | 2.00 | -1.4 | 0.750996E+09 | 770.46 | 1.83 | -1.7 | ||
Maximum of Months | 0.508305E+11 | 75689.61 | 29.00 | 13.51 | 0.838127E+09 | 900.05 | 28.50 | 13.41 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141313E+11 | 23291.98 | 20-JAN-13:33 | 21.00 | 6.93 | 0.117848E+11 | 8054.67 | 20-JAN-22:19 | 7.67 | 1.90 |
February | 0.117514E+11 | 22719.76 | 18-FEB-12:43 | 19.67 | 7.56 | 0.104245E+11 | 7916.75 | 17-FEB-22:19 | 7.00 | 3.15 |
March | 0.133356E+11 | 21022.38 | 11-MAR-12:49 | 16.83 | 5.45 | 0.114892E+11 | 7906.20 | 10-MAR-22:19 | 8.67 | 2.43 |
April | 0.115875E+11 | 18733.87 | 07-APR-12:47 | 20.83 | 8.37 | 0.108446E+11 | 7595.78 | 07-APR-22:10 | 10.83 | 6.15 |
May | 0.150925E+11 | 17345.05 | 10-MAY-20:53 | 21.00 | 8.14 | 0.115331E+11 | 7500.62 | 10-MAY-22:30 | 17.50 | 6.80 |
June | 0.187220E+11 | 18851.07 | 14-JUN-03:23 | 22.20 | 8.78 | 0.111481E+11 | 8034.74 | 26-JUN-21:19 | 27.53 | 11.05 |
July | 0.196155E+11 | 18804.97 | 18-JUL-22:13 | 23.33 | 12.23 | 0.114824E+11 | 8338.47 | 17-JUL-21:10 | 28.50 | 13.41 |
August | 0.197920E+11 | 18992.61 | 16-AUG-22:33 | 21.33 | 11.23 | 0.115684E+11 | 7730.88 | 02-AUG-22:10 | 23.00 | 13.67 |
September | 0.188995E+11 | 20420.09 | 27-SEP-12:25 | 25.80 | 8.75 | 0.113594E+11 | 7727.11 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.153021E+11 | 21914.94 | 10-OCT-12:53 | 24.00 | 7.90 | 0.118520E+11 | 8081.71 | 11-OCT-21:19 | 9.33 | 4.47 |
November | 0.142028E+11 | 23002.83 | 07-NOV-12:53 | 20.00 | 6.97 | 0.115365E+11 | 8022.05 | 16-NOV-22:19 | 5.33 | 3.49 |
December | 0.128535E+11 | 22805.50 | 02-DEC-13:33 | 21.00 | 7.10 | 0.113339E+11 | 7778.77 | 14-DEC-22:19 | 1.67 | -1.7 |
Annual Sum or Average | 0.185286E+12 | 0.136357E+12 | ||||||||
Minimum of Months | 0.115875E+11 | 17345.05 | 16.83 | 5.45 | 0.104245E+11 | 7500.62 | 1.67 | -1.7 | ||
Maximum of Months | 0.197920E+11 | 23291.98 | 25.80 | 12.23 | 0.118520E+11 | 8338.47 | 28.50 | 13.67 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483023E+11 | 61939.28 | 20-JAN-13:33 | 21.00 | 6.93 | 0.358787E+11 | 23890.90 | 20-JAN-22:19 | 7.67 | 1.90 |
February | 0.414638E+11 | 61789.80 | 18-FEB-12:46 | 19.67 | 7.56 | 0.320186E+11 | 23649.65 | 17-FEB-22:19 | 7.00 | 3.15 |
March | 0.480983E+11 | 60780.75 | 13-MAR-15:43 | 23.00 | 6.93 | 0.356109E+11 | 23752.06 | 10-MAR-22:19 | 8.67 | 2.43 |
April | 0.447403E+11 | 56267.03 | 12-APR-15:25 | 19.50 | 7.67 | 0.340382E+11 | 23056.38 | 07-APR-22:10 | 10.83 | 6.15 |
May | 0.549762E+11 | 59157.18 | 10-MAY-20:53 | 21.00 | 8.14 | 0.355716E+11 | 23225.53 | 26-MAY-22:10 | 9.50 | 4.93 |
June | 0.653340E+11 | 62807.72 | 14-JUN-03:23 | 22.20 | 8.78 | 0.332936E+11 | 23357.57 | 26-JUN-21:19 | 27.53 | 11.05 |
July | 0.680832E+11 | 62824.50 | 18-JUL-01:29 | 20.50 | 10.83 | 0.341889E+11 | 24275.77 | 17-JUL-21:10 | 28.50 | 13.41 |
August | 0.678681E+11 | 62679.65 | 16-AUG-22:33 | 21.33 | 11.23 | 0.343011E+11 | 22281.23 | 17-AUG-04:00 | 12.00 | 4.79 |
September | 0.634432E+11 | 60451.13 | 13-SEP-00:59 | 20.00 | 12.03 | 0.337895E+11 | 23149.67 | 25-SEP-22:10 | 11.42 | 4.97 |
October | 0.530785E+11 | 61173.33 | 11-OCT-15:05 | 25.67 | 9.28 | 0.362765E+11 | 23929.62 | 11-OCT-21:19 | 9.33 | 4.47 |
November | 0.487119E+11 | 61754.72 | 06-NOV-12:53 | 22.00 | 7.06 | 0.351927E+11 | 24108.87 | 16-NOV-22:19 | 5.33 | 3.49 |
December | 0.455317E+11 | 62368.77 | 02-DEC-13:33 | 21.00 | 7.10 | 0.352551E+11 | 23629.27 | 15-DEC-22:30 | 2.50 | -0.7 |
Annual Sum or Average | 0.649631E+12 | 0.415415E+12 | ||||||||
Minimum of Months | 0.414638E+11 | 56267.03 | 19.50 | 6.93 | 0.320186E+11 | 22281.23 | 2.50 | -0.7 | ||
Maximum of Months | 0.680832E+11 | 62824.50 | 25.67 | 12.03 | 0.362765E+11 | 24275.77 | 28.50 | 13.41 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226396E+09 | 2303.14 | 21-JAN-16:11 | 9.67 | 3.98 | 96472530.83 | 56.69 | 20-JAN-22:10 | 7.83 | 1.98 |
February | 0.232426E+09 | 2323.21 | 17-FEB-16:11 | 13.67 | 6.71 | 86738471.76 | 56.69 | 17-FEB-22:10 | 7.00 | 3.15 |
March | 0.474719E+09 | 2384.44 | 13-MAR-15:11 | 23.00 | 6.93 | 96449701.99 | 56.69 | 13-MAR-21:10 | 10.83 | 2.01 |
April | 0.287037E+09 | 2572.47 | 06-APR-18:31 | 14.33 | 5.44 | 93451091.13 | 75.14 | 06-APR-18:10 | 16.33 | 6.22 |
May | 0.770006E+09 | 2356.33 | 10-MAY-15:11 | 25.00 | 8.94 | 98706186.76 | 56.69 | 16-MAY-22:10 | 15.83 | 9.67 |
June | 0.183209E+10 | 2412.89 | 14-JUN-15:11 | 35.90 | 13.42 | 96797636.41 | 56.69 | 16-JUN-22:19 | 20.33 | 14.72 |
July | 0.181074E+10 | 2423.34 | 01-JUL-18:01 | 27.67 | 10.43 | 99687373.78 | 56.69 | 02-JUL-00:10 | 13.83 | 4.17 |
August | 0.175741E+10 | 2444.59 | 26-AUG-16:45 | 31.33 | 11.60 | 99840527.68 | 56.69 | 15-AUG-21:00 | 22.00 | 12.38 |
September | 0.143900E+10 | 2413.48 | 28-SEP-15:11 | 29.60 | 11.00 | 96050688.49 | 56.69 | 30-SEP-00:20 | 17.70 | 7.34 |
October | 0.652035E+09 | 2409.30 | 11-OCT-15:11 | 25.33 | 9.14 | 97206245.68 | 56.69 | 10-OCT-21:10 | 13.83 | 4.08 |
November | 0.314482E+09 | 2348.23 | 05-NOV-15:11 | 20.33 | 6.36 | 93643948.13 | 56.69 | 07-NOV-23:10 | 7.17 | 2.01 |
December | 0.151218E+09 | 2269.95 | 29-DEC-16:11 | 11.00 | 4.47 | 95375914.48 | 56.69 | 04-DEC-22:10 | 7.17 | 0.70 |
Annual Sum or Average | 0.994755E+10 | 0.115042E+10 | ||||||||
Minimum of Months | 0.151218E+09 | 2269.95 | 9.67 | 3.98 | 86738471.76 | 56.69 | 7.00 | 0.70 | ||
Maximum of Months | 0.183209E+10 | 2572.47 | 35.90 | 13.42 | 99840527.68 | 75.14 | 22.00 | 14.72 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40951145.08 | 2279.41 | 23-JAN-16:51 | 14.00 | 5.31 | 94122161.19 | 56.69 | 20-JAN-22:10 | 7.83 | 1.98 |
February | 60762496.97 | 2259.38 | 26-FEB-17:11 | 14.67 | 4.32 | 85065601.59 | 56.69 | 06-FEB-01:49 | -10.5 | -10.5 |
March | 0.218488E+09 | 2659.53 | 31-MAR-18:01 | 14.33 | 7.59 | 96611140.17 | 71.90 | 31-MAR-18:10 | 14.33 | 7.59 |
April | 0.185962E+09 | 2651.66 | 08-APR-17:21 | 15.00 | 4.81 | 93550907.26 | 75.83 | 07-APR-18:10 | 16.50 | 6.85 |
May | 0.558130E+09 | 2428.39 | 27-MAY-15:31 | 15.00 | 7.95 | 0.102510E+09 | 78.05 | 09-MAY-18:10 | 19.50 | 8.39 |
June | 0.155566E+10 | 2532.98 | 30-JUN-21:11 | 26.13 | 11.10 | 0.104352E+09 | 91.64 | 08-JUN-18:10 | 26.05 | 14.42 |
July | 0.152340E+10 | 2513.94 | 01-JUL-21:11 | 19.47 | 7.30 | 0.106609E+09 | 82.09 | 03-JUL-18:10 | 21.83 | 11.22 |
August | 0.138546E+10 | 2445.63 | 13-AUG-21:11 | 17.33 | 8.45 | 0.106801E+09 | 82.82 | 02-AUG-21:10 | 24.67 | 15.10 |
September | 0.944916E+09 | 2475.21 | 09-SEP-16:11 | 27.17 | 13.18 | 0.101875E+09 | 79.41 | 12-SEP-21:10 | 22.93 | 12.79 |
October | 0.266690E+09 | 2400.98 | 11-OCT-18:11 | 14.67 | 6.77 | 97638593.32 | 60.62 | 11-OCT-18:19 | 14.67 | 6.77 |
November | 68088507.87 | 2233.72 | 03-NOV-15:11 | 14.67 | 5.87 | 91839858.22 | 56.69 | 06-NOV-22:10 | 7.83 | 1.69 |
December | 19176271.97 | 2214.48 | 03-DEC-16:11 | 14.33 | 5.67 | 93565421.41 | 56.69 | 23-DEC-02:49 | -20.3 | -20.5 |
Annual Sum or Average | 0.682769E+10 | 0.117454E+10 | ||||||||
Minimum of Months | 19176271.97 | 2214.48 | 14.00 | 4.32 | 85065601.59 | 56.69 | -20.3 | -20.5 | ||
Maximum of Months | 0.155566E+10 | 2659.53 | 27.17 | 13.18 | 0.106801E+09 | 91.64 | 26.05 | 15.10 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355384E+09 | 776.72 | 20-JAN-15:01 | 19.67 | 6.90 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.217993E+09 | 642.67 | 18-FEB-13:20 | 20.00 | 7.71 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.204529E+09 | 606.06 | 11-MAR-13:00 | 17.00 | 5.44 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 36449047.19 | 235.34 | 13-APR-12:23 | 17.00 | 8.87 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.159534E+09 | 242.23 | 06-MAY-15:02 | 24.17 | 10.68 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.387453E+09 | 332.47 | 26-JUN-17:11 | 37.70 | 15.16 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.432849E+09 | 324.32 | 18-JUL-17:12 | 30.67 | 14.99 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.459268E+09 | 402.83 | 31-AUG-12:31 | 30.00 | 12.21 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.490701E+09 | 610.85 | 28-SEP-13:10 | 30.50 | 11.26 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.366054E+09 | 788.17 | 10-OCT-14:01 | 25.00 | 8.63 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.323600E+09 | 772.32 | 16-NOV-15:01 | 15.83 | 6.81 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.223387E+09 | 744.11 | 17-DEC-15:01 | 17.25 | 5.51 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.365720E+10 | 0.00 | ||||||||
Minimum of Months | 36449047.19 | 235.34 | 15.83 | 5.44 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.490701E+09 | 788.17 | 37.70 | 15.16 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 52766210.60 | 655.99 | 21-JAN-09:01 | 13.00 | 3.73 | 94947468.81 | 56.69 | 19-JAN-22:10 | 7.67 | 1.93 |
February | 43605228.39 | 635.79 | 27-FEB-19:01 | 7.33 | 1.49 | 85643466.23 | 56.69 | 27-FEB-22:19 | 2.00 | -0.7 |
March | 0.135944E+09 | 690.33 | 14-MAR-20:11 | 15.00 | 4.59 | 96238490.18 | 60.74 | 14-MAR-20:19 | 15.00 | 4.59 |
April | 0.178408E+09 | 672.98 | 08-APR-08:61 | 9.33 | 1.67 | 93569903.86 | 56.69 | 19-APR-22:10 | 12.00 | 6.21 |
May | 0.415976E+09 | 744.59 | 17-MAY-21:11 | 17.33 | 8.52 | 0.100608E+09 | 75.01 | 17-MAY-21:19 | 17.33 | 8.52 |
June | 0.654045E+09 | 780.31 | 30-JUN-21:11 | 26.13 | 11.10 | 0.101852E+09 | 79.44 | 30-JUN-21:10 | 26.37 | 11.20 |
July | 0.686034E+09 | 781.14 | 07-JUL-21:11 | 21.33 | 11.77 | 0.105221E+09 | 79.11 | 18-JUL-21:10 | 24.00 | 12.63 |
August | 0.612920E+09 | 760.98 | 01-AUG-21:11 | 20.33 | 9.60 | 0.104635E+09 | 80.31 | 02-AUG-21:10 | 24.67 | 15.10 |
September | 0.477774E+09 | 755.01 | 08-SEP-21:11 | 21.60 | 10.45 | 99326527.58 | 75.72 | 12-SEP-21:10 | 22.93 | 12.79 |
October | 0.195233E+09 | 686.47 | 01-OCT-18:01 | 13.50 | 7.57 | 96751643.51 | 56.69 | 05-OCT-21:10 | 13.17 | 5.35 |
November | 78601101.79 | 652.70 | 06-NOV-19:01 | 13.33 | 3.88 | 92364011.81 | 56.69 | 09-NOV-22:10 | 8.00 | 6.42 |
December | 40800369.32 | 643.10 | 03-DEC-09:01 | 9.50 | 2.23 | 94505051.13 | 56.69 | 28-DEC-22:10 | 7.17 | 1.68 |
Annual Sum or Average | 0.357211E+10 | 0.116566E+10 | ||||||||
Minimum of Months | 40800369.32 | 635.79 | 7.33 | 1.49 | 85643466.23 | 56.69 | 2.00 | -0.7 | ||
Maximum of Months | 0.686034E+09 | 781.14 | 26.13 | 11.77 | 0.105221E+09 | 80.31 | 26.37 | 15.10 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223002E+09 | 2009.24 | 20-JAN-09:01 | 10.67 | 3.17 | 96700301.31 | 56.69 | 20-JAN-22:10 | 7.83 | 1.98 |
February | 0.258976E+09 | 1994.87 | 14-FEB-09:01 | 0.50 | -3.6 | 87049279.41 | 56.69 | 17-FEB-22:10 | 7.00 | 3.15 |
March | 0.494734E+09 | 2039.51 | 11-MAR-09:01 | 13.17 | 4.39 | 96867452.84 | 56.69 | 14-MAR-21:19 | 13.00 | 3.85 |
April | 0.353792E+09 | 2012.00 | 20-APR-15:11 | 20.00 | 8.59 | 93730980.73 | 56.96 | 19-APR-18:10 | 17.83 | 8.81 |
May | 0.845009E+09 | 2272.14 | 04-MAY-08:11 | 18.33 | 7.88 | 99125337.56 | 56.69 | 10-MAY-23:49 | 18.00 | 7.13 |
June | 0.194332E+10 | 2099.53 | 27-JUN-08:61 | 24.00 | 9.64 | 96618876.63 | 56.69 | 14-JUN-00:00 | 21.60 | 8.63 |
July | 0.202028E+10 | 2122.18 | 01-JUL-08:61 | 26.00 | 9.43 | 99768285.08 | 56.69 | 08-JUL-01:10 | 18.67 | 10.82 |
August | 0.193898E+10 | 2093.54 | 19-AUG-08:61 | 21.50 | 10.16 | 99776912.46 | 56.69 | 16-AUG-22:40 | 21.33 | 11.23 |
September | 0.150861E+10 | 2074.27 | 07-SEP-08:61 | 20.45 | 9.83 | 96259113.87 | 56.69 | 14-SEP-21:40 | 14.20 | 5.87 |
October | 0.618084E+09 | 2055.01 | 11-OCT-15:11 | 25.33 | 9.14 | 97478610.73 | 56.69 | 11-OCT-21:10 | 9.67 | 4.55 |
November | 0.297247E+09 | 2030.47 | 07-NOV-09:01 | 14.00 | 4.06 | 93677754.65 | 56.69 | 07-NOV-22:00 | 7.00 | 1.99 |
December | 0.153905E+09 | 1991.32 | 03-DEC-09:01 | 9.50 | 2.23 | 95519472.52 | 56.69 | 04-DEC-22:10 | 7.17 | 0.70 |
Annual Sum or Average | 0.106559E+11 | 0.115257E+10 | ||||||||
Minimum of Months | 0.153905E+09 | 1991.32 | 0.50 | -3.6 | 87049279.41 | 56.69 | 7.00 | 0.70 | ||
Maximum of Months | 0.202028E+10 | 2272.14 | 26.00 | 10.16 | 99776912.46 | 56.96 | 21.60 | 11.23 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43374200.88 | 1967.47 | 20-JAN-09:01 | 10.67 | 3.17 | 93980889.20 | 56.69 | 14-JAN-03:00 | -17.0 | -17.0 |
February | 84730770.25 | 1939.16 | 14-FEB-09:01 | 0.50 | -3.6 | 85229212.29 | 56.69 | 08-FEB-04:49 | -7.0 | -7.3 |
March | 0.258420E+09 | 2012.43 | 15-MAR-08:61 | 9.83 | 2.36 | 96349103.41 | 61.63 | 14-MAR-20:19 | 15.00 | 4.59 |
April | 0.262297E+09 | 1959.53 | 21-APR-15:11 | 13.67 | 5.25 | 93520491.55 | 56.69 | 20-APR-21:10 | 14.00 | 7.95 |
May | 0.673874E+09 | 2248.00 | 13-MAY-08:11 | 20.67 | 8.98 | 0.101834E+09 | 74.03 | 17-MAY-21:19 | 17.33 | 8.52 |
June | 0.163425E+10 | 2643.57 | 07-JUN-08:11 | 24.97 | 11.34 | 0.104155E+09 | 81.88 | 30-JUN-21:10 | 26.37 | 11.20 |
July | 0.168549E+10 | 2779.40 | 01-JUL-08:11 | 26.00 | 9.43 | 0.107501E+09 | 82.59 | 18-JUL-21:10 | 24.00 | 12.63 |
August | 0.153845E+10 | 2556.45 | 06-AUG-08:11 | 23.00 | 15.15 | 0.106915E+09 | 80.35 | 02-AUG-21:10 | 24.67 | 15.10 |
September | 0.104725E+10 | 2414.81 | 07-SEP-08:11 | 20.90 | 10.11 | 0.100934E+09 | 76.70 | 12-SEP-21:10 | 22.93 | 12.79 |
October | 0.267866E+09 | 2115.43 | 11-OCT-08:11 | 18.07 | 7.10 | 97049705.59 | 56.69 | 10-OCT-21:10 | 13.83 | 4.08 |
November | 75560592.68 | 1985.97 | 07-NOV-09:01 | 14.00 | 4.06 | 91565288.49 | 56.69 | 06-NOV-22:10 | 7.83 | 1.69 |
December | 24085559.76 | 1934.97 | 03-DEC-09:01 | 9.50 | 2.23 | 93429939.69 | 56.69 | 10-DEC-04:00 | -10.0 | -10.0 |
Annual Sum or Average | 0.759565E+10 | 0.117246E+10 | ||||||||
Minimum of Months | 24085559.76 | 1934.97 | 0.50 | -3.6 | 85229212.29 | 56.69 | -17.0 | -17.0 | ||
Maximum of Months | 0.168549E+10 | 2779.40 | 26.00 | 15.15 | 0.107501E+09 | 82.59 | 26.37 | 15.10 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453281E+09 | 1719.67 | 20-JAN-13:14 | 21.00 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.361960E+09 | 1687.21 | 18-FEB-13:59 | 20.00 | 7.70 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.591530E+09 | 1830.84 | 14-MAR-14:40 | 23.00 | 7.55 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.498502E+09 | 1684.27 | 07-APR-14:20 | 21.00 | 7.84 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.130324E+10 | 1782.02 | 18-MAY-14:03 | 23.83 | 11.30 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.204160E+10 | 1948.99 | 29-JUN-19:54 | 22.70 | 12.34 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.220894E+10 | 2000.02 | 25-JUL-14:09 | 25.00 | 16.00 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.212751E+10 | 1961.40 | 17-AUG-11:48 | 24.67 | 9.71 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.187733E+10 | 1991.98 | 14-SEP-14:13 | 22.93 | 11.99 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.969218E+09 | 1861.38 | 11-OCT-16:52 | 22.00 | 8.31 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.536543E+09 | 1740.88 | 07-NOV-15:14 | 21.67 | 7.25 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.306415E+09 | 1676.63 | 02-DEC-14:06 | 21.17 | 7.23 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.132761E+11 | 0.00 | ||||||||
Minimum of Months | 0.306415E+09 | 1676.63 | 20.00 | 6.93 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.220894E+10 | 2000.02 | 25.00 | 16.00 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226300E+09 | 2456.80 | 21-JAN-16:11 | 9.67 | 3.98 | 96045595.38 | 56.69 | 23-JAN-22:10 | 3.17 | -0.5 |
February | 0.243002E+09 | 2480.26 | 17-FEB-16:11 | 13.67 | 6.71 | 86505938.56 | 56.69 | 19-FEB-00:20 | 9.33 | 3.11 |
March | 0.510011E+09 | 2546.55 | 13-MAR-15:11 | 23.00 | 6.93 | 96221171.68 | 56.69 | 14-MAR-22:10 | 12.83 | 3.93 |
April | 0.331961E+09 | 2968.71 | 06-APR-18:31 | 14.33 | 5.44 | 93414334.08 | 84.39 | 06-APR-18:10 | 16.33 | 6.22 |
May | 0.876080E+09 | 2514.24 | 09-MAY-15:11 | 21.33 | 8.52 | 98821859.39 | 57.54 | 03-MAY-18:19 | 14.67 | 6.66 |
June | 0.204089E+10 | 2577.18 | 14-JUN-15:11 | 35.90 | 13.42 | 97087708.50 | 58.41 | 26-JUN-18:10 | 37.33 | 15.05 |
July | 0.195235E+10 | 2587.47 | 01-JUL-18:01 | 27.67 | 10.43 | 99795034.10 | 56.69 | 16-JUL-00:49 | 20.83 | 11.86 |
August | 0.193618E+10 | 2684.28 | 26-AUG-16:46 | 31.33 | 11.60 | 0.100014E+09 | 56.69 | 09-AUG-00:10 | 17.00 | 11.96 |
September | 0.152366E+10 | 2577.52 | 28-SEP-15:11 | 29.60 | 11.00 | 96021679.59 | 56.69 | 07-SEP-21:00 | 16.60 | 8.96 |
October | 0.674283E+09 | 2569.07 | 11-OCT-15:11 | 25.33 | 9.14 | 96989315.82 | 56.69 | 11-OCT-21:40 | 8.67 | 4.29 |
November | 0.324327E+09 | 2510.06 | 05-NOV-15:11 | 20.33 | 6.36 | 93364497.53 | 56.69 | 06-NOV-23:40 | 6.33 | 1.16 |
December | 0.148752E+09 | 2419.90 | 02-DEC-16:11 | 16.67 | 5.57 | 94972861.04 | 56.69 | 04-DEC-22:10 | 7.17 | 0.70 |
Annual Sum or Average | 0.107878E+11 | 0.114925E+10 | ||||||||
Minimum of Months | 0.148752E+09 | 2419.90 | 9.67 | 3.98 | 86505938.56 | 56.69 | 3.17 | -0.5 | ||
Maximum of Months | 0.204089E+10 | 2968.71 | 35.90 | 13.42 | 0.100014E+09 | 84.39 | 37.33 | 15.05 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37706474.46 | 2486.99 | 23-JAN-16:51 | 14.00 | 5.31 | 93659295.35 | 56.69 | 08-JAN-02:39 | -11.0 | -11.0 |
February | 61227711.44 | 2468.38 | 26-FEB-17:11 | 14.67 | 4.32 | 84828028.51 | 56.69 | 13-FEB-00:20 | -11.0 | -12.0 |
March | 0.235253E+09 | 3073.32 | 31-MAR-18:01 | 14.33 | 7.59 | 96679675.90 | 81.46 | 31-MAR-18:10 | 14.33 | 7.59 |
April | 0.218251E+09 | 2986.81 | 08-APR-17:21 | 15.00 | 4.81 | 93733078.28 | 85.08 | 07-APR-18:10 | 16.50 | 6.85 |
May | 0.650937E+09 | 2722.43 | 09-MAY-19:51 | 15.00 | 7.74 | 0.103845E+09 | 87.79 | 09-MAY-18:10 | 19.50 | 8.39 |
June | 0.179254E+10 | 2764.59 | 08-JUN-21:11 | 16.97 | 12.11 | 0.106093E+09 | 100.72 | 08-JUN-18:10 | 26.05 | 14.42 |
July | 0.169434E+10 | 2789.78 | 01-JUL-21:11 | 19.47 | 7.30 | 0.107534E+09 | 89.28 | 03-JUL-21:10 | 16.00 | 9.75 |
August | 0.158069E+10 | 2803.43 | 13-AUG-21:11 | 17.33 | 8.45 | 0.108049E+09 | 87.92 | 03-AUG-21:10 | 21.17 | 15.80 |
September | 0.102692E+10 | 2678.52 | 09-SEP-16:11 | 27.17 | 13.18 | 0.102939E+09 | 81.52 | 12-SEP-21:19 | 22.57 | 12.61 |
October | 0.269647E+09 | 2755.57 | 11-OCT-18:11 | 14.67 | 6.77 | 97838930.85 | 70.40 | 11-OCT-18:10 | 15.33 | 7.05 |
November | 68230248.00 | 2399.80 | 07-NOV-17:01 | 14.50 | 5.30 | 91537738.33 | 56.69 | 08-NOV-22:10 | 7.00 | 3.98 |
December | 17946099.52 | 2350.76 | 03-DEC-16:11 | 14.33 | 5.67 | 93183190.96 | 56.69 | 22-DEC-23:49 | -18.9 | -19.2 |
Annual Sum or Average | 0.765370E+10 | 0.117992E+10 | ||||||||
Minimum of Months | 17946099.52 | 2350.76 | 14.00 | 4.32 | 84828028.51 | 56.69 | -18.9 | -19.2 | ||
Maximum of Months | 0.179254E+10 | 3073.32 | 27.17 | 13.18 | 0.108049E+09 | 100.72 | 26.05 | 15.80 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.713745E+09 | 1317.96 | 20-JAN-13:04 | 21.00 | 6.93 | 98732251.36 | 56.69 | 19-JAN-22:40 | 6.67 | 1.44 |
February | 0.539759E+09 | 1193.79 | 17-FEB-13:30 | 14.50 | 5.99 | 88334850.82 | 56.69 | 19-FEB-00:30 | 9.50 | 3.20 |
March | 0.515415E+09 | 1192.44 | 11-MAR-13:26 | 17.50 | 5.66 | 97263915.86 | 56.69 | 15-MAR-21:19 | 12.67 | 3.02 |
April | 0.239531E+09 | 1055.17 | 07-APR-15:12 | 21.00 | 7.83 | 93811816.92 | 58.65 | 19-APR-18:10 | 17.83 | 8.81 |
May | 0.495043E+09 | 1085.23 | 04-MAY-15:11 | 24.67 | 9.99 | 98792824.50 | 56.69 | 16-MAY-21:40 | 16.33 | 9.87 |
June | 0.988117E+09 | 1092.81 | 07-JUN-15:11 | 31.47 | 11.66 | 96605460.75 | 57.20 | 28-JUN-21:10 | 22.93 | 11.25 |
July | 0.106760E+10 | 1075.70 | 03-JUL-18:01 | 21.83 | 11.22 | 99676761.71 | 56.69 | 01-JUL-02:49 | 18.62 | 7.37 |
August | 0.110345E+10 | 1088.29 | 20-AUG-15:11 | 28.00 | 13.93 | 99848866.54 | 58.74 | 31-AUG-21:10 | 23.70 | 11.83 |
September | 0.107821E+10 | 1148.82 | 27-SEP-12:10 | 26.00 | 8.77 | 96427498.40 | 58.82 | 12-SEP-21:10 | 22.93 | 12.79 |
October | 0.768123E+09 | 1198.71 | 10-OCT-15:13 | 25.00 | 8.34 | 98045009.53 | 56.69 | 10-OCT-21:10 | 13.83 | 4.08 |
November | 0.729251E+09 | 1279.44 | 05-NOV-12:18 | 20.33 | 5.90 | 95613089.19 | 56.69 | 07-NOV-22:10 | 7.00 | 1.99 |
December | 0.538438E+09 | 1290.08 | 17-DEC-13:20 | 18.00 | 5.74 | 97961155.03 | 56.69 | 01-DEC-22:30 | 6.00 | 1.08 |
Annual Sum or Average | 0.877669E+10 | 0.116111E+10 | ||||||||
Minimum of Months | 0.239531E+09 | 1055.17 | 14.50 | 5.66 | 88334850.82 | 56.69 | 6.00 | 1.08 | ||
Maximum of Months | 0.110345E+10 | 1317.96 | 31.47 | 13.93 | 99848866.54 | 58.82 | 23.70 | 12.79 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259336E+11 | 27207.94 | 23-JAN-16:08 | 18.17 | 6.11 | 0.223940E+11 | 15052.07 | 20-JAN-23:10 | 7.00 | 1.58 |
February | 0.233280E+11 | 28262.71 | 18-FEB-12:43 | 19.67 | 7.56 | 0.202238E+11 | 15053.05 | 27-FEB-22:19 | 2.00 | -0.7 |
March | 0.278976E+11 | 31409.26 | 13-MAR-15:43 | 23.00 | 6.93 | 0.229092E+11 | 15322.72 | 16-MAR-22:10 | 9.83 | 4.12 |
April | 0.276231E+11 | 31261.87 | 27-APR-15:17 | 20.67 | 10.38 | 0.222871E+11 | 15280.17 | 28-APR-22:10 | 9.00 | 7.74 |
May | 0.329967E+11 | 31868.83 | 10-MAY-22:43 | 17.83 | 7.02 | 0.230856E+11 | 15492.98 | 26-MAY-22:10 | 9.50 | 4.93 |
June | 0.374669E+11 | 34133.86 | 27-JUN-22:48 | 21.18 | 11.16 | 0.212881E+11 | 15622.58 | 01-JUN-22:00 | 16.10 | 11.91 |
July | 0.387723E+11 | 34404.94 | 18-JUL-22:13 | 23.33 | 12.23 | 0.218037E+11 | 15948.44 | 17-JUL-21:10 | 28.50 | 13.41 |
August | 0.382899E+11 | 34501.32 | 16-AUG-22:33 | 21.33 | 11.23 | 0.217293E+11 | 15416.39 | 17-AUG-22:40 | 17.67 | 8.15 |
September | 0.347533E+11 | 32200.08 | 08-SEP-22:33 | 21.27 | 11.07 | 0.212699E+11 | 15138.27 | 15-SEP-23:10 | 10.42 | 5.45 |
October | 0.290362E+11 | 30778.13 | 10-OCT-15:33 | 25.00 | 8.26 | 0.229651E+11 | 15324.21 | 20-OCT-21:19 | 10.33 | 1.56 |
November | 0.260217E+11 | 28534.95 | 05-NOV-09:53 | 18.00 | 6.29 | 0.219923E+11 | 15197.91 | 09-NOV-23:10 | 8.00 | 6.95 |
December | 0.251232E+11 | 27229.05 | 14-DEC-22:51 | 1.00 | -1.9 | 0.220179E+11 | 15027.76 | 04-DEC-23:10 | 7.83 | 0.78 |
Annual Sum or Average | 0.367242E+12 | 0.263966E+12 | ||||||||
Minimum of Months | 0.233280E+11 | 27207.94 | 1.00 | -1.9 | 0.202238E+11 | 15027.76 | 2.00 | -0.7 | ||
Maximum of Months | 0.387723E+11 | 34501.32 | 25.00 | 12.23 | 0.230856E+11 | 15948.44 | 28.50 | 13.41 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292275E+11 | 29997.55 | 20-JAN-12:07 | 20.17 | 7.43 | 0.233212E+11 | 15523.31 | 20-JAN-23:10 | 7.00 | 1.58 |
February | 0.264035E+11 | 30846.02 | 18-FEB-12:43 | 19.67 | 7.56 | 0.211017E+11 | 15571.05 | 27-FEB-22:19 | 2.00 | -0.7 |
March | 0.312868E+11 | 33758.29 | 13-MAR-15:43 | 23.00 | 6.93 | 0.238308E+11 | 15755.97 | 16-MAR-22:10 | 9.83 | 4.12 |
April | 0.309123E+11 | 33805.41 | 27-APR-15:17 | 20.67 | 10.38 | 0.231514E+11 | 15800.22 | 28-APR-22:10 | 9.00 | 7.74 |
May | 0.363351E+11 | 34246.77 | 16-MAY-16:53 | 25.00 | 11.93 | 0.237593E+11 | 16032.88 | 26-MAY-22:10 | 9.50 | 4.93 |
June | 0.406466E+11 | 36507.66 | 26-JUN-22:08 | 24.72 | 10.37 | 0.217445E+11 | 16081.31 | 26-JUN-21:19 | 27.53 | 11.05 |
July | 0.420261E+11 | 36672.80 | 18-JUL-22:13 | 23.33 | 12.23 | 0.222622E+11 | 16460.87 | 17-JUL-21:10 | 28.50 | 13.41 |
August | 0.415132E+11 | 36777.85 | 16-AUG-22:33 | 21.33 | 11.23 | 0.221577E+11 | 15747.03 | 17-AUG-22:40 | 17.67 | 8.15 |
September | 0.378282E+11 | 34396.42 | 08-SEP-22:33 | 21.27 | 11.07 | 0.217159E+11 | 15567.51 | 22-SEP-22:10 | 9.40 | 3.39 |
October | 0.323083E+11 | 32939.63 | 10-OCT-15:33 | 25.00 | 8.26 | 0.237344E+11 | 15834.84 | 03-OCT-21:19 | 4.67 | 4.13 |
November | 0.291895E+11 | 31360.01 | 05-NOV-09:53 | 18.00 | 6.29 | 0.228518E+11 | 15653.73 | 17-NOV-23:10 | 6.00 | 2.42 |
December | 0.285927E+11 | 31311.91 | 02-DEC-12:43 | 20.83 | 7.07 | 0.229626E+11 | 15497.92 | 14-DEC-22:19 | 1.67 | -1.7 |
Annual Sum or Average | 0.406270E+12 | 0.272594E+12 | ||||||||
Minimum of Months | 0.264035E+11 | 29997.55 | 18.00 | 6.29 | 0.211017E+11 | 15497.92 | 1.67 | -1.7 | ||
Maximum of Months | 0.420261E+11 | 36777.85 | 25.00 | 12.23 | 0.238308E+11 | 16460.87 | 28.50 | 13.41 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.426163E+11 | 42662.05 | 19-JAN-12:51 | 17.00 | 7.13 | 0.197362E+11 | 11977.72 | 21-JAN-18:00 | 8.00 | 3.20 |
February | 0.384728E+11 | 45512.74 | 26-FEB-11:51 | 17.00 | 4.41 | 0.178312E+11 | 11994.68 | 25-FEB-18:49 | 7.17 | 2.83 |
March | 0.442602E+11 | 44902.45 | 31-MAR-16:41 | 19.17 | 6.56 | 0.197544E+11 | 12077.00 | 11-MAR-18:49 | 14.17 | 4.21 |
April | 0.431196E+11 | 45072.84 | 19-APR-17:52 | 18.00 | 8.93 | 0.191167E+11 | 11979.73 | 29-APR-17:00 | 8.00 | 6.34 |
May | 0.481504E+11 | 48478.32 | 16-MAY-16:41 | 25.33 | 11.92 | 0.196859E+11 | 11940.55 | 20-MAY-17:00 | 19.00 | 11.41 |
June | 0.504159E+11 | 49937.68 | 30-JUN-16:51 | 32.70 | 13.01 | 0.189354E+11 | 11965.16 | 17-JUN-17:10 | 26.33 | 17.05 |
July | 0.518163E+11 | 50000.82 | 07-JUL-17:31 | 26.67 | 13.39 | 0.195505E+11 | 12113.84 | 15-JUL-17:00 | 33.00 | 13.20 |
August | 0.515824E+11 | 49384.02 | 26-AUG-16:51 | 31.00 | 11.49 | 0.195300E+11 | 12095.09 | 26-AUG-17:00 | 30.00 | 11.59 |
September | 0.484266E+11 | 49125.94 | 06-SEP-17:31 | 26.60 | 13.06 | 0.189071E+11 | 12042.13 | 02-SEP-17:40 | 26.23 | 13.41 |
October | 0.452374E+11 | 45660.31 | 11-OCT-16:41 | 22.33 | 8.36 | 0.197367E+11 | 12096.10 | 21-OCT-17:00 | 10.00 | 3.84 |
November | 0.419561E+11 | 44987.09 | 07-NOV-11:42 | 19.33 | 7.22 | 0.191151E+11 | 11973.26 | 18-NOV-18:00 | 3.00 | 3.00 |
December | 0.418679E+11 | 44577.84 | 14-DEC-19:01 | 4.75 | 0.40 | 0.196937E+11 | 11955.46 | 16-DEC-18:00 | 0.00 | -2.1 |
Annual Sum or Average | 0.547922E+12 | 0.231593E+12 | ||||||||
Minimum of Months | 0.384728E+11 | 42662.05 | 4.75 | 0.40 | 0.178312E+11 | 11940.55 | 0.00 | -2.1 | ||
Maximum of Months | 0.518163E+11 | 50000.82 | 32.70 | 13.39 | 0.197544E+11 | 12113.84 | 33.00 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173540E+10 | 8006.17 | 20-JAN-13:43 | 21.00 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.6 |
February | 0.153287E+10 | 7871.02 | 18-FEB-13:08 | 20.00 | 7.71 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.251360E+10 | 8239.38 | 14-MAR-13:23 | 23.50 | 7.71 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.221578E+10 | 8031.25 | 12-APR-13:07 | 21.00 | 7.75 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.09 |
May | 0.485259E+10 | 8172.36 | 24-MAY-14:13 | 21.33 | 11.96 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.760252E+10 | 8384.57 | 16-JUN-12:33 | 23.27 | 14.83 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.25 |
July | 0.794200E+10 | 8606.53 | 25-JUL-14:09 | 25.00 | 16.00 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.88 |
August | 0.751657E+10 | 8460.77 | 21-AUG-15:29 | 22.50 | 16.00 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.42 |
September | 0.617283E+10 | 8443.08 | 01-SEP-12:53 | 21.10 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.63 |
October | 0.349821E+10 | 8321.21 | 10-OCT-13:38 | 24.67 | 8.41 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.02 |
November | 0.221440E+10 | 8110.35 | 07-NOV-13:35 | 21.33 | 7.21 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.128417E+10 | 7273.94 | 17-DEC-13:13 | 18.00 | 5.74 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.3 |
Annual Sum or Average | 0.490810E+11 | 0.00 | ||||||||
Minimum of Months | 0.128417E+10 | 7273.94 | 18.00 | 5.74 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.794200E+10 | 8606.53 | 25.00 | 16.00 | 0.00 | 0.00 | 22.27 | 15.42 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115981E+09 | 2092.04 | 05-JAN-09:12 | -17.0 |
February | 0.272286E+09 | 1984.03 | 05-FEB-18:02 | -7.2 |
March | 0.130032E+09 | 2036.58 | 19-MAR-08:10 | -13.0 |
April | 0.100810E+09 | 1593.50 | 03-APR-06:02 | -7.7 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.147883E+09 | 1973.63 | 31-OCT-15:02 | -8.0 |
November | 0.105379E+09 | 1950.59 | 30-NOV-07:10 | -11.3 |
December | 0.349731E+09 | 2386.13 | 21-DEC-08:10 | -20.0 |
Annual Sum or Average | 0.122210E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.349731E+09 | 2386.13 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2057937.56 | 201.27 | 05-JAN-17:52 | -18.0 |
February | 416814.89 | 78.56 | 06-FEB-17:52 | -7.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 70845778.31 | 670.10 | 23-DEC-06:02 | -22.1 |
Annual Sum or Average | 73320530.75 | |||
Minimum of Months | 0.00 | 0.00 | -22.1 | |
Maximum of Months | 70845778.31 | 670.10 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2170910.45 | 2976.27 | 05-JAN-09:02 | -17.0 |
February | 3499823.75 | 938.69 | 05-FEB-15:52 | -6.0 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 4283368.57 | 1036.82 | 31-OCT-13:52 | -7.0 |
November | 30596.05 | 509.93 | 29-NOV-09:04 | -9.0 |
December | 52136268.59 | 4848.88 | 21-DEC-09:30 | -20.0 |
Annual Sum or Average | 62120967.41 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 52136268.59 | 4848.88 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.517385E+09 | 1821.18 | 05-JAN-09:01 | -17.0 |
February | 0.615969E+09 | 1819.49 | 05-FEB-16:11 | -6.3 |
March | 0.468125E+09 | 1817.43 | 19-MAR-08:61 | -13.0 |
April | 0.383178E+09 | 1796.40 | 02-APR-15:11 | -4.0 |
May | 36718157.12 | 1719.86 | 02-MAY-08:61 | 3.35 |
June | 435465.77 | 585.66 | 09-JUN-08:04 | 14.77 |
July | 287718.46 | 613.85 | 24-JUL-08:04 | 25.33 |
August | 781843.99 | 718.00 | 30-AUG-08:03 | 19.50 |
September | 13756412.06 | 1713.35 | 22-SEP-08:61 | 2.57 |
October | 0.327640E+09 | 1822.40 | 31-OCT-15:11 | -8.0 |
November | 0.439069E+09 | 1807.29 | 28-NOV-16:11 | -7.3 |
December | 0.896721E+09 | 1846.73 | 21-DEC-09:01 | -20.0 |
Annual Sum or Average | 0.370007E+10 | |||
Minimum of Months | 287718.46 | 585.66 | -20.0 | |
Maximum of Months | 0.896721E+09 | 1846.73 | 25.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.849663E+09 | 1817.59 | 05-JAN-19:01 | -18.7 |
February | 0.855526E+09 | 1814.54 | 05-FEB-16:11 | -6.3 |
March | 0.559195E+09 | 1811.30 | 19-MAR-08:61 | -13.0 |
April | 0.415220E+09 | 1791.49 | 02-APR-15:11 | -4.0 |
May | 37968185.34 | 1717.27 | 02-MAY-08:61 | 3.35 |
June | 125372.06 | 362.19 | 04-JUN-08:15 | 22.37 |
July | 223092.05 | 617.78 | 03-JUL-08:04 | 13.33 |
August | 490019.11 | 648.41 | 19-AUG-08:14 | 22.00 |
September | 16621176.04 | 1712.93 | 22-SEP-08:61 | 2.57 |
October | 0.394785E+09 | 1816.72 | 31-OCT-15:11 | -8.0 |
November | 0.671147E+09 | 1805.19 | 28-NOV-16:11 | -7.3 |
December | 0.124509E+10 | 1841.41 | 21-DEC-09:01 | -20.0 |
Annual Sum or Average | 0.504606E+10 | |||
Minimum of Months | 125372.06 | 362.19 | -20.0 | |
Maximum of Months | 0.124509E+10 | 1841.41 | 22.37 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102547E+09 | 511.07 | 05-JAN-16:11 | -15.3 |
February | 0.115502E+09 | 506.80 | 12-FEB-16:11 | -6.3 |
March | 39149673.25 | 495.14 | 04-MAR-16:11 | -9.0 |
April | 16243084.47 | 486.47 | 02-APR-15:11 | -4.0 |
May | 25144.01 | 141.97 | 03-MAY-08:04 | 6.33 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 105.57 | 1.76 | 31-JUL-08:17 | 21.33 |
August | 13846.29 | 117.11 | 30-AUG-08:15 | 20.00 |
September | 30688.50 | 143.77 | 21-SEP-15:14 | 1.63 |
October | 26558545.44 | 503.79 | 31-OCT-15:11 | -8.0 |
November | 61706612.32 | 502.09 | 29-NOV-16:11 | -9.7 |
December | 0.177176E+09 | 514.06 | 21-DEC-16:11 | -18.7 |
Annual Sum or Average | 0.538952E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.177176E+09 | 514.06 | 21.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.543917E+09 | 1727.74 | 05-JAN-19:01 | -18.7 |
February | 0.642691E+09 | 1726.08 | 05-FEB-16:11 | -6.3 |
March | 0.454944E+09 | 1723.85 | 19-MAR-08:61 | -13.0 |
April | 0.368423E+09 | 1706.29 | 02-APR-15:11 | -4.0 |
May | 32943540.62 | 703.89 | 01-MAY-18:02 | 9.67 |
June | 39640.41 | 384.52 | 17-JUN-08:05 | 17.28 |
July | 15278.23 | 172.54 | 28-JUL-08:04 | 18.00 |
August | 43845.23 | 460.52 | 15-AUG-08:04 | 14.17 |
September | 12164900.01 | 1603.67 | 22-SEP-08:61 | 2.57 |
October | 0.331909E+09 | 1728.00 | 31-OCT-15:11 | -8.0 |
November | 0.468085E+09 | 1715.96 | 28-NOV-16:11 | -7.3 |
December | 0.910950E+09 | 1749.95 | 20-DEC-16:11 | -17.3 |
Annual Sum or Average | 0.376613E+10 | |||
Minimum of Months | 15278.23 | 172.54 | -18.7 | |
Maximum of Months | 0.910950E+09 | 1749.95 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.878017E+09 | 1735.40 | 05-JAN-16:11 | -15.3 |
February | 0.877212E+09 | 1724.88 | 05-FEB-16:11 | -6.3 |
March | 0.543097E+09 | 1721.64 | 19-MAR-08:61 | -13.0 |
April | 0.405395E+09 | 1705.09 | 02-APR-15:11 | -4.0 |
May | 35061982.83 | 668.06 | 01-MAY-15:13 | 14.67 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 2066.83 | 17.22 | 28-JUL-08:16 | 18.00 |
August | 36197.29 | 243.24 | 27-AUG-08:14 | 17.33 |
September | 15004051.39 | 1606.34 | 22-SEP-08:61 | 2.57 |
October | 0.402205E+09 | 1726.11 | 31-OCT-15:11 | -8.0 |
November | 0.716312E+09 | 1721.86 | 29-NOV-16:11 | -9.7 |
December | 0.125474E+10 | 1755.00 | 21-DEC-16:11 | -18.7 |
Annual Sum or Average | 0.512708E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.7 | |
Maximum of Months | 0.125474E+10 | 1755.00 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527581E+09 | 1515.59 | 06-JAN-05:32 | -7.3 |
February | 0.710837E+09 | 1560.07 | 08-FEB-05:02 | -6.8 |
March | 0.577513E+09 | 1418.90 | 05-MAR-07:02 | -11.0 |
April | 0.471004E+09 | 1432.24 | 03-APR-05:02 | -8.0 |
May | 36254652.48 | 988.44 | 01-MAY-03:52 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.295382E+09 | 1515.19 | 31-OCT-24:00 | -5.8 |
November | 0.469857E+09 | 1521.19 | 01-NOV-04:52 | -3.0 |
December | 0.977944E+09 | 1660.23 | 23-DEC-07:02 | -22.3 |
Annual Sum or Average | 0.406637E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.3 | |
Maximum of Months | 0.977944E+09 | 1660.23 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.819335E+09 | 2149.08 | 05-JAN-09:01 | -17.0 |
February | 0.896441E+09 | 2145.81 | 05-FEB-16:11 | -6.3 |
March | 0.702822E+09 | 2141.37 | 19-MAR-08:61 | -13.0 |
April | 0.572794E+09 | 2116.20 | 02-APR-15:11 | -4.0 |
May | 71032468.54 | 2041.45 | 02-MAY-08:61 | 3.35 |
June | 509125.55 | 692.77 | 23-JUN-08:03 | 17.47 |
July | 298335.31 | 696.02 | 28-JUL-08:03 | 18.00 |
August | 640025.03 | 511.83 | 13-AUG-08:05 | 15.17 |
September | 29529674.15 | 2048.08 | 22-SEP-08:61 | 2.57 |
October | 0.519501E+09 | 2148.00 | 31-OCT-15:11 | -8.0 |
November | 0.685002E+09 | 2131.72 | 28-NOV-16:11 | -7.3 |
December | 0.127010E+10 | 2176.25 | 21-DEC-09:01 | -20.0 |
Annual Sum or Average | 0.556801E+10 | |||
Minimum of Months | 298335.31 | 511.83 | -20.0 | |
Maximum of Months | 0.127010E+10 | 2176.25 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126337E+10 | 2148.48 | 05-JAN-19:01 | -18.7 |
February | 0.120748E+10 | 2141.50 | 05-FEB-16:11 | -6.3 |
March | 0.824336E+09 | 2136.03 | 19-MAR-08:61 | -13.0 |
April | 0.614240E+09 | 2110.91 | 02-APR-15:11 | -4.0 |
May | 69813354.10 | 2039.79 | 02-MAY-08:61 | 3.35 |
June | 153835.98 | 441.33 | 17-JUN-08:14 | 17.37 |
July | 132441.21 | 340.33 | 31-JUL-08:14 | 21.33 |
August | 369430.68 | 595.34 | 22-AUG-08:13 | 16.67 |
September | 33067280.26 | 2048.28 | 22-SEP-08:61 | 2.57 |
October | 0.620034E+09 | 2142.96 | 31-OCT-15:11 | -8.0 |
November | 0.100202E+10 | 2132.03 | 28-NOV-16:11 | -7.3 |
December | 0.171437E+10 | 2175.16 | 20-DEC-16:11 | -17.3 |
Annual Sum or Average | 0.734940E+10 | |||
Minimum of Months | 132441.21 | 340.33 | -18.7 | |
Maximum of Months | 0.171437E+10 | 2175.16 | 21.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150986E+09 | 1015.34 | 05-JAN-09:01 | -17.0 |
February | 0.245701E+09 | 1018.76 | 05-FEB-16:11 | -6.3 |
March | 0.222092E+09 | 1012.54 | 19-MAR-08:61 | -13.0 |
April | 0.193852E+09 | 1008.22 | 02-APR-15:11 | -4.0 |
May | 16670139.22 | 954.29 | 02-MAY-08:61 | 3.35 |
June | 161118.50 | 139.44 | 01-JUN-08:04 | 18.77 |
July | 27692.88 | 155.82 | 28-JUL-08:04 | 18.00 |
August | 19655.17 | 195.70 | 02-AUG-08:05 | 20.00 |
September | 4797495.52 | 947.74 | 22-SEP-08:61 | 2.57 |
October | 0.157431E+09 | 1019.70 | 31-OCT-15:11 | -8.0 |
November | 0.148420E+09 | 1009.94 | 28-NOV-16:11 | -7.3 |
December | 0.315668E+09 | 1027.97 | 20-DEC-16:11 | -17.3 |
Annual Sum or Average | 0.145583E+10 | |||
Minimum of Months | 19655.17 | 139.44 | -17.3 | |
Maximum of Months | 0.315668E+09 | 1027.97 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251475E+09 | 3989.52 | 05-JAN-06:00 | -17.0 |
February | 0.415266E+09 | 3921.02 | 12-FEB-07:02 | -19.5 |
March | 6620927.01 | 1284.66 | 05-MAR-06:14 | -11.7 |
April | 2225887.08 | 378.69 | 17-APR-04:52 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 77927495.72 | 2315.75 | 31-OCT-04:52 | -8.0 |
November | 0.144986E+09 | 3866.71 | 30-NOV-04:52 | -13.0 |
December | 0.797056E+09 | 4322.45 | 22-DEC-06:02 | -20.8 |
Annual Sum or Average | 0.169556E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.8 | |
Maximum of Months | 0.797056E+09 | 4322.45 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.113897E+11 | 10970.58 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.102838E+11 | 10970.58 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.114292E+11 | 10970.58 | 01-MAR-20:10 | 0.121808E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.110035E+11 | 10970.58 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.114094E+11 | 10970.58 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.110540E+11 | 10970.58 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.113589E+11 | 10970.58 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.114292E+11 | 10970.58 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.110035E+11 | 10970.58 | 01-SEP-19:10 | 0.117446E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.113897E+11 | 10970.58 | 02-OCT-19:10 | 0.121516E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.110452E+11 | 10970.58 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.113589E+11 | 10970.58 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.134155E+12 | 0.143109E+12 | ||||
Minimum of Months | 0.102838E+11 | 10970.58 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.114292E+11 | 10970.58 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.566644E+09 | 545.79 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.511628E+09 | 545.79 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.568609E+09 | 545.79 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.547432E+09 | 545.79 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.567626E+09 | 545.79 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.549942E+09 | 545.79 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.565115E+09 | 545.79 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.568609E+09 | 545.79 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.547432E+09 | 545.79 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.566644E+09 | 545.79 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.549506E+09 | 545.79 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.565115E+09 | 545.79 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.667430E+10 | 0.101859E+11 | ||||
Minimum of Months | 0.511628E+09 | 545.79 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.568609E+09 | 545.79 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.656175E+09 | 632.03 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.592467E+09 | 632.03 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.658451E+09 | 632.03 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.633928E+09 | 632.03 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.657313E+09 | 632.03 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.636835E+09 | 632.03 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.654406E+09 | 632.03 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.658451E+09 | 632.03 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.633928E+09 | 632.03 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.656175E+09 | 632.03 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.636330E+09 | 632.03 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.654406E+09 | 632.03 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.772886E+10 | 0.117953E+11 | ||||
Minimum of Months | 0.592467E+09 | 632.03 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.658451E+09 | 632.03 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156929E+10 | 1511.55 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.141693E+10 | 1511.55 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.157474E+10 | 1511.55 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.151609E+10 | 1511.55 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.157202E+10 | 1511.55 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.152304E+10 | 1511.55 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.156506E+10 | 1511.55 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.157474E+10 | 1511.55 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.151609E+10 | 1511.55 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.156929E+10 | 1511.55 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.152183E+10 | 1511.55 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.156506E+10 | 1511.55 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | ||||
Minimum of Months | 0.141693E+10 | 1511.55 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.157474E+10 | 1511.55 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.161153E+09 | 155.22 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.145507E+09 | 155.22 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.161712E+09 | 155.22 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.155689E+09 | 155.22 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.161433E+09 | 155.22 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.156404E+09 | 155.22 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.160719E+09 | 155.22 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.161712E+09 | 155.22 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.155689E+09 | 155.22 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.161153E+09 | 155.22 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.156279E+09 | 155.22 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.160719E+09 | 155.22 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.189817E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.145507E+09 | 155.22 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.161712E+09 | 155.22 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.415991E+09 | 400.68 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.375602E+09 | 400.68 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.417433E+09 | 400.68 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.401887E+09 | 400.68 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.416712E+09 | 400.68 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.403730E+09 | 400.68 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.414869E+09 | 400.68 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.417433E+09 | 400.68 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.401887E+09 | 400.68 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.415991E+09 | 400.68 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.403409E+09 | 400.68 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.414869E+09 | 400.68 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.489981E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.375602E+09 | 400.68 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.417433E+09 | 400.68 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.858145E+09 | 1097.76 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.749859E+09 | 1097.76 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.781931E+09 | 1097.76 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.702676E+09 | 1097.76 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.658127E+09 | 1097.76 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.597921E+09 | 1097.76 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.628382E+09 | 1097.76 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.698999E+09 | 1097.76 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.723803E+09 | 1097.76 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.829205E+09 | 1097.76 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.820622E+09 | 1097.76 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.867234E+09 | 1097.76 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.891690E+10 | 0.143409E+11 | ||||
Minimum of Months | 0.597921E+09 | 1097.76 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.867234E+09 | 1097.76 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.641752E+10 | 6463.27 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.577081E+10 | 6463.27 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.636596E+10 | 6463.27 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.608323E+10 | 6463.27 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.623437E+10 | 6463.27 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.600388E+10 | 6463.27 | 01-JUN-19:19 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.618439E+10 | 6463.27 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.628419E+10 | 6463.27 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.610080E+10 | 6463.27 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.639233E+10 | 6463.27 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.621448E+10 | 6463.27 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.641149E+10 | 6463.27 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.744635E+11 | 0.149002E+12 | ||||
Minimum of Months | 0.577081E+10 | 6463.27 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.641752E+10 | 6463.27 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117159E+09 | 137.77 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.105814E+09 | 137.77 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.116728E+09 | 137.77 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.113449E+09 | 137.77 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.116943E+09 | 137.77 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113018E+09 | 137.77 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.117374E+09 | 137.77 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.116728E+09 | 137.77 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.113449E+09 | 137.77 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.117159E+09 | 137.77 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113234E+09 | 137.77 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.117374E+09 | 137.77 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.137843E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.105814E+09 | 137.77 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.117374E+09 | 137.77 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117145E+09 | 137.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.105801E+09 | 137.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.116714E+09 | 137.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.113436E+09 | 137.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.116930E+09 | 137.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113005E+09 | 137.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.117360E+09 | 137.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.116714E+09 | 137.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.113436E+09 | 137.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.117145E+09 | 137.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113220E+09 | 137.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.117360E+09 | 137.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.137827E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.105801E+09 | 137.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.117360E+09 | 137.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 73629799.21 | 86.58 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 66499969.88 | 86.58 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 73359176.20 | 86.58 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 71298293.27 | 86.58 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 73494487.70 | 86.58 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 71027670.26 | 86.58 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 73765110.71 | 86.58 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 73359176.20 | 86.58 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 71298293.27 | 86.58 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 73629799.21 | 86.58 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 71162981.76 | 86.58 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 73765110.71 | 86.58 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.866290E+09 | 0.256575E+10 | ||||
Minimum of Months | 66499969.88 | 86.58 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 73765110.71 | 86.58 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 73649933.14 | 86.61 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 66518154.18 | 86.61 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 73379236.13 | 86.61 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 71317789.65 | 86.61 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 73514584.64 | 86.61 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 71047092.65 | 86.61 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 73785281.65 | 86.61 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 73379236.13 | 86.61 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 71317789.65 | 86.61 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 73649933.14 | 86.61 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 71182441.15 | 86.61 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 73785281.65 | 86.61 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.866527E+09 | 0.256645E+10 | ||||
Minimum of Months | 66518154.18 | 86.61 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 73785281.65 | 86.61 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117159E+09 | 137.77 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.105814E+09 | 137.77 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.116728E+09 | 137.77 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.113449E+09 | 137.77 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.116943E+09 | 137.77 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113018E+09 | 137.77 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.117374E+09 | 137.77 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.116728E+09 | 137.77 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.113449E+09 | 137.77 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.117159E+09 | 137.77 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113234E+09 | 137.77 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.117374E+09 | 137.77 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.137843E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.105814E+09 | 137.77 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.117374E+09 | 137.77 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117145E+09 | 137.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.105801E+09 | 137.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.116714E+09 | 137.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.113436E+09 | 137.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.116930E+09 | 137.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113005E+09 | 137.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.117360E+09 | 137.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.116714E+09 | 137.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.113436E+09 | 137.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.117145E+09 | 137.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113220E+09 | 137.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.117360E+09 | 137.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.137827E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.105801E+09 | 137.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.117360E+09 | 137.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.870792E+09 | 838.75 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.786245E+09 | 838.75 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.873811E+09 | 838.75 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.841268E+09 | 838.75 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.872301E+09 | 838.75 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.845126E+09 | 838.75 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.868443E+09 | 838.75 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.873811E+09 | 838.75 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.841268E+09 | 838.75 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.870792E+09 | 838.75 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.844455E+09 | 838.75 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.868443E+09 | 838.75 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102568E+11 | ||||
Minimum of Months | 0.786245E+09 | 838.75 | 0.00 | 0.00 | |
Maximum of Months | 0.873811E+09 | 838.75 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117159E+09 | 137.77 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.105814E+09 | 137.77 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.116728E+09 | 137.77 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.113449E+09 | 137.77 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.116943E+09 | 137.77 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.113018E+09 | 137.77 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.117374E+09 | 137.77 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.116728E+09 | 137.77 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.113449E+09 | 137.77 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.117159E+09 | 137.77 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.113234E+09 | 137.77 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.117374E+09 | 137.77 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.137843E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.105814E+09 | 137.77 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.117374E+09 | 137.77 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.117145E+09 | 137.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.105801E+09 | 137.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.116714E+09 | 137.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.113436E+09 | 137.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.116930E+09 | 137.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.113005E+09 | 137.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.117360E+09 | 137.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.116714E+09 | 137.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.113436E+09 | 137.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.117145E+09 | 137.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.113220E+09 | 137.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.117360E+09 | 137.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.137827E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.105801E+09 | 137.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.117360E+09 | 137.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 73649933.14 | 86.61 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 66518154.18 | 86.61 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 73379236.13 | 86.61 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 71317789.65 | 86.61 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 73514584.64 | 86.61 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 71047092.65 | 86.61 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 73785281.65 | 86.61 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 73379236.13 | 86.61 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 71317789.65 | 86.61 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 73649933.14 | 86.61 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 71182441.15 | 86.61 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 73785281.65 | 86.61 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.866527E+09 | 0.256645E+10 | ||||
Minimum of Months | 66518154.18 | 86.61 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 73785281.65 | 86.61 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.178610E+10 | 1927.76 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.157365E+10 | 1927.76 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.169568E+10 | 1927.76 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.157841E+10 | 1927.76 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.156448E+10 | 1927.76 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.147107E+10 | 1927.76 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.152828E+10 | 1927.76 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.160508E+10 | 1927.76 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.160344E+10 | 1927.76 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.173887E+10 | 1927.76 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.170908E+10 | 1927.76 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.178083E+10 | 1927.76 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.196350E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.147107E+10 | 1927.76 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.178610E+10 | 1927.76 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.178610E+10 | 1927.76 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.157365E+10 | 1927.76 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.169568E+10 | 1927.76 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.157841E+10 | 1927.76 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.156448E+10 | 1927.76 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.147107E+10 | 1927.76 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.152828E+10 | 1927.76 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.160508E+10 | 1927.76 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.160344E+10 | 1927.76 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.173887E+10 | 1927.76 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.170908E+10 | 1927.76 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.178083E+10 | 1927.76 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.196350E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.147107E+10 | 1927.76 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.178610E+10 | 1927.76 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.113250E+10 | 1090.83 | 02-JAN-20:10 | 0.360126E+11 | 16179.04 | 01-JAN-07:10 |
February | 0.102255E+10 | 1090.83 | 01-FEB-20:10 | 0.325275E+11 | 16179.04 | 01-FEB-07:10 |
March | 0.113643E+10 | 1090.83 | 01-MAR-20:10 | 0.360126E+11 | 16179.04 | 01-MAR-07:10 |
April | 0.109411E+10 | 1090.83 | 03-APR-19:10 | 0.348509E+11 | 16179.04 | 01-APR-06:10 |
May | 0.113447E+10 | 1090.83 | 01-MAY-19:10 | 0.360126E+11 | 16179.04 | 01-MAY-06:10 |
June | 0.109912E+10 | 1090.83 | 01-JUN-19:10 | 0.348509E+11 | 16179.04 | 01-JUN-06:10 |
July | 0.112945E+10 | 1090.83 | 03-JUL-19:10 | 0.360126E+11 | 16179.04 | 01-JUL-06:10 |
August | 0.113643E+10 | 1090.83 | 01-AUG-19:10 | 0.360126E+11 | 16179.04 | 01-AUG-06:10 |
September | 0.109411E+10 | 1090.83 | 01-SEP-19:10 | 0.348509E+11 | 16179.04 | 01-SEP-06:10 |
October | 0.113250E+10 | 1090.83 | 02-OCT-19:10 | 0.360126E+11 | 16179.04 | 01-OCT-06:10 |
November | 0.109825E+10 | 1090.83 | 01-NOV-19:10 | 0.348509E+11 | 16179.04 | 01-NOV-06:10 |
December | 0.112945E+10 | 1090.83 | 01-DEC-20:10 | 0.360126E+11 | 16179.04 | 01-DEC-07:10 |
Annual Sum or Average | 0.133394E+11 | 0.424019E+12 | ||||
Minimum of Months | 0.102255E+10 | 1090.83 | 0.325275E+11 | 16179.04 | ||
Maximum of Months | 0.113643E+10 | 1090.83 | 0.360126E+11 | 16179.04 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.921598E+09 | 887.69 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.832119E+09 | 887.69 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.924794E+09 | 887.69 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.890352E+09 | 887.69 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.923196E+09 | 887.69 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.894435E+09 | 887.69 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.919113E+09 | 887.69 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.924794E+09 | 887.69 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.890352E+09 | 887.69 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.921598E+09 | 887.69 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.893725E+09 | 887.69 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.919113E+09 | 887.69 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.108552E+11 | ||||
Minimum of Months | 0.832119E+09 | 887.69 | 0.00 | 0.00 | |
Maximum of Months | 0.924794E+09 | 887.69 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.113897E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.102838E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.114292E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.110035E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.114094E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.110540E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.113589E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.114292E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.110035E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.113897E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.110452E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.113589E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.134155E+12 | 0.143109E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.102838E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.114292E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.566644E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125823E+10 |
February | 0.179968E+10 | 0.511628E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117911E+10 |
March | 0.199896E+10 | 0.568609E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992503E+09 |
April | 0.192973E+10 | 0.547432E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872973E+09 |
May | 0.199475E+10 | 0.567626E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4409491.62 | 0.538644E+09 |
June | 0.193394E+10 | 0.549942E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 78569573.76 | 0.188658E+09 |
July | 0.199054E+10 | 0.565115E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81228999.02 | 0.169246E+09 |
August | 0.199896E+10 | 0.568609E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59671648.99 | 0.201043E+09 |
September | 0.192973E+10 | 0.547432E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21560438.63 | 0.324303E+09 |
October | 0.199054E+10 | 0.566644E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4663.52 | 0.906492E+09 |
November | 0.192552E+10 | 0.549506E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110326E+10 |
December | 0.199054E+10 | 0.565115E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134901E+10 |
Annual Sum or Average | 0.234734E+11 | 0.667430E+10 | 0.101859E+11 | 0.245445E+09 | 0.908347E+10 | ||||
Minimum of Months | 0.179968E+10 | 0.511628E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169246E+09 |
Maximum of Months | 0.199896E+10 | 0.568609E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81228999.02 | 0.134901E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.656175E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271739E+09 |
February | 0.208403E+10 | 0.592467E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256983E+09 |
March | 0.231480E+10 | 0.658451E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.26 | 0.221896E+09 |
April | 0.223463E+10 | 0.633928E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199249E+09 |
May | 0.230993E+10 | 0.657313E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1045860.66 | 0.120000E+09 |
June | 0.223950E+10 | 0.636835E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17812521.07 | 41227437.23 |
July | 0.230505E+10 | 0.654406E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18787916.53 | 36887226.34 |
August | 0.231480E+10 | 0.658451E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15001395.08 | 43587120.82 |
September | 0.223463E+10 | 0.633928E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7388643.96 | 70475384.97 |
October | 0.230505E+10 | 0.656175E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115010.90 | 0.198935E+09 |
November | 0.222975E+10 | 0.636330E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238949E+09 |
December | 0.230505E+10 | 0.654406E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295587E+09 |
Annual Sum or Average | 0.271823E+11 | 0.772886E+10 | 0.117953E+11 | 60151358.45 | 0.199552E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.592467E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36887226.34 |
Maximum of Months | 0.231480E+10 | 0.658451E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18787916.53 | 0.295587E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922706E+09 |
February | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873155E+09 |
March | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770649E+09 |
April | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697604E+09 |
May | 0.154732E+10 | 0.416712E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 2204825.46 | 0.435080E+09 |
June | 0.150015E+10 | 0.403730E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 42531274.00 | 0.163028E+09 |
July | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 45168477.35 | 0.152032E+09 |
August | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 36307079.65 | 0.175211E+09 |
September | 0.149688E+10 | 0.401887E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 18617760.55 | 0.263134E+09 |
October | 0.154405E+10 | 0.415991E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 269432.32 | 0.690707E+09 |
November | 0.149361E+10 | 0.403409E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815910E+09 |
December | 0.154405E+10 | 0.414869E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100344E+10 |
Annual Sum or Average | 0.182082E+11 | 0.489981E+10 | 0.679373E+11 | 0.590211E+12 | 0.145099E+09 | 0.696266E+10 | |||
Minimum of Months | 0.139600E+10 | 0.375602E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152032E+09 |
Maximum of Months | 0.155059E+10 | 0.417433E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 45168477.35 | 0.100344E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.858145E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333386E+10 |
February | 0.236489E+11 | 0.749859E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312967E+10 |
March | 0.262677E+11 | 0.781931E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266814E+10 |
April | 0.253579E+11 | 0.702676E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235944E+10 |
May | 0.262123E+11 | 0.658127E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11571626.53 | 0.142977E+10 |
June | 0.254132E+11 | 0.597921E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203852E+09 | 0.496400E+09 |
July | 0.261570E+11 | 0.628382E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211491E+09 | 0.445694E+09 |
August | 0.262677E+11 | 0.698999E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157333E+09 | 0.528080E+09 |
September | 0.253579E+11 | 0.723803E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61197380.36 | 0.859457E+09 |
October | 0.261570E+11 | 0.829205E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27690.47 | 0.241125E+10 |
November | 0.253025E+11 | 0.820622E+09 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293156E+10 |
December | 0.261570E+11 | 0.867234E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358676E+10 |
Annual Sum or Average | 0.308456E+12 | 0.891690E+10 | 0.143409E+11 | 0.645472E+09 | 0.241801E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.597921E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445694E+09 |
Maximum of Months | 0.262677E+11 | 0.867234E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211491E+09 | 0.358676E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.641752E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664189E+10 |
February | 0.702046E+11 | 0.577081E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627215E+10 |
March | 0.779788E+11 | 0.636596E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.542285E+10 |
April | 0.752779E+11 | 0.608323E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486563E+10 |
May | 0.778146E+11 | 0.623437E+10 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24282105.30 | 0.294932E+10 |
June | 0.754422E+11 | 0.600388E+10 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423699E+09 | 0.101547E+10 |
July | 0.776503E+11 | 0.618439E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444591E+09 | 0.910145E+09 |
August | 0.779788E+11 | 0.628419E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353872E+09 | 0.107216E+10 |
September | 0.752779E+11 | 0.610080E+10 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169532E+09 | 0.173369E+10 |
October | 0.776503E+11 | 0.639233E+10 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2182639.03 | 0.486808E+10 |
November | 0.751137E+11 | 0.621448E+10 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585294E+10 |
December | 0.776503E+11 | 0.641149E+10 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722802E+10 |
Annual Sum or Average | 0.915690E+12 | 0.744635E+11 | 0.149002E+12 | 0.141816E+10 | 0.488324E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.577081E+10 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910145E+09 |
Maximum of Months | 0.779788E+11 | 0.641752E+10 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444591E+09 | 0.722802E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330652E+09 |
February | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315205E+09 |
March | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 72210.81 | 0.262589E+09 |
April | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233599E+09 |
May | 0.303504E+09 | 0.116943E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3101790.40 | 0.127169E+09 |
June | 0.293842E+09 | 0.113018E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35742564.71 | 33370200.53 |
July | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38698048.87 | 27467898.27 |
August | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31352508.04 | 34718294.62 |
September | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16454212.36 | 66608427.70 |
October | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 524710.57 | 0.229147E+09 |
November | 0.293661E+09 | 0.113234E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284958E+09 |
December | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364476E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137843E+10 | 0.261953E+10 | 0.125946E+09 | 0.230996E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27467898.27 |
Maximum of Months | 0.303685E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38698048.87 | 0.364476E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322854E+09 |
February | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309348E+09 |
March | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13162.05 | 0.260875E+09 |
April | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232789E+09 |
May | 0.303504E+09 | 0.116930E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2321391.97 | 0.131398E+09 |
June | 0.293842E+09 | 0.113005E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32227694.84 | 39142807.90 |
July | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35711678.75 | 33251662.26 |
August | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28585083.91 | 40421371.60 |
September | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14693220.85 | 72006653.82 |
October | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 331479.33 | 0.227907E+09 |
November | 0.293661E+09 | 0.113220E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278975E+09 |
December | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14074.26 | 0.358488E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137827E+10 | 0.261922E+10 | 0.113898E+09 | 0.230746E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33251662.26 |
Maximum of Months | 0.303685E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35711678.75 | 0.358488E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 73629799.21 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113060E+09 |
February | 0.00 | 66499969.88 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101821E+09 |
March | 0.00 | 73359176.20 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86871560.13 |
April | 0.00 | 71298293.27 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78624666.13 |
May | 0.00 | 73494487.70 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64353.28 | 54484304.78 |
June | 0.00 | 71027670.26 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4051229.50 | 23010542.91 |
July | 0.00 | 73765110.71 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4208089.85 | 21469288.59 |
August | 0.00 | 73359176.20 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3154575.73 | 24551174.02 |
September | 0.00 | 71298293.27 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1208794.34 | 35310781.74 |
October | 0.00 | 73629799.21 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.03 | 82919810.87 |
November | 0.00 | 71162981.76 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97962928.83 |
December | 0.00 | 73765110.71 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116054E+09 |
Annual Sum or Average | 0.00 | 0.866290E+09 | 0.256575E+10 | 12687129.71 | 0.836139E+09 | ||||
Minimum of Months | 0.00 | 66499969.88 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21469288.59 |
Maximum of Months | 0.00 | 73765110.71 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4208089.85 | 0.116054E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90746749.09 |
February | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86820744.18 |
March | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23772.98 | 72992402.10 |
April | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.36 | 65382308.80 |
May | 0.303504E+09 | 73514584.64 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 775876.32 | 36052067.52 |
June | 0.293842E+09 | 71047092.65 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9292337.43 | 10310043.94 |
July | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10082580.79 | 8879025.04 |
August | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8261140.17 | 10714945.28 |
September | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4394324.00 | 19319352.61 |
October | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 160026.89 | 63451286.94 |
November | 0.293661E+09 | 71182441.15 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5350.00 | 78272422.20 |
December | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7513.99 | 0.100758E+09 |
Annual Sum or Average | 0.357224E+10 | 0.866527E+09 | 0.256645E+10 | 33003117.93 | 0.643700E+09 | ||||
Minimum of Months | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8879025.04 |
Maximum of Months | 0.303685E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10082580.79 | 0.100758E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331267E+09 |
February | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316102E+09 |
March | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82126.46 | 0.264109E+09 |
April | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235133E+09 |
May | 0.303504E+09 | 0.116943E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3048439.05 | 0.128607E+09 |
June | 0.293842E+09 | 0.113018E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 36016822.66 | 33864033.64 |
July | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38402612.37 | 27736627.85 |
August | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31550741.33 | 35272297.90 |
September | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16502030.32 | 67325222.39 |
October | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 548846.37 | 0.229967E+09 |
November | 0.293661E+09 | 0.113234E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285104E+09 |
December | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364833E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137843E+10 | 0.261953E+10 | 0.126152E+09 | 0.231932E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27736627.85 |
Maximum of Months | 0.303685E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38402612.37 | 0.364833E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322685E+09 |
February | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310032E+09 |
March | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5896.20 | 0.261821E+09 |
April | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234186E+09 |
May | 0.303504E+09 | 0.116930E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2283781.44 | 0.131595E+09 |
June | 0.293842E+09 | 0.113005E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32352855.57 | 40649682.30 |
July | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35029711.51 | 35071191.72 |
August | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28498520.69 | 41882182.44 |
September | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14741867.76 | 71698475.96 |
October | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 352132.99 | 0.227915E+09 |
November | 0.293661E+09 | 0.113220E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278423E+09 |
December | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15968.40 | 0.358167E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137827E+10 | 0.261922E+10 | 0.113281E+09 | 0.231412E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35071191.72 |
Maximum of Months | 0.303685E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35029711.51 | 0.358167E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330542E+09 |
February | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315495E+09 |
March | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58125.04 | 0.262913E+09 |
April | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234307E+09 |
May | 0.303504E+09 | 0.116943E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2939162.78 | 0.128334E+09 |
June | 0.293842E+09 | 0.113018E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 34907624.82 | 33840390.06 |
July | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38038316.26 | 27884479.09 |
August | 0.303685E+09 | 0.116728E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30674591.11 | 35198349.64 |
September | 0.293479E+09 | 0.113449E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16087215.41 | 67047131.52 |
October | 0.303322E+09 | 0.117159E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 484012.66 | 0.229521E+09 |
November | 0.293661E+09 | 0.113234E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285196E+09 |
December | 0.303141E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364382E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137843E+10 | 0.261953E+10 | 0.123189E+09 | 0.231466E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105814E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27884479.09 |
Maximum of Months | 0.303685E+09 | 0.117374E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38038316.26 | 0.364382E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322532E+09 |
February | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309597E+09 |
March | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5045.74 | 0.261644E+09 |
April | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233859E+09 |
May | 0.303504E+09 | 0.116930E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2143344.46 | 0.134063E+09 |
June | 0.293842E+09 | 0.113005E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31431207.04 | 41126878.61 |
July | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35038364.13 | 34490716.34 |
August | 0.303685E+09 | 0.116714E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27854769.14 | 41969918.34 |
September | 0.293479E+09 | 0.113436E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14333720.84 | 73776325.08 |
October | 0.303322E+09 | 0.117145E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 287369.37 | 0.228873E+09 |
November | 0.293661E+09 | 0.113220E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279101E+09 |
December | 0.303141E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11729.03 | 0.358377E+09 |
Annual Sum or Average | 0.357224E+10 | 0.137827E+10 | 0.261922E+10 | 0.111106E+09 | 0.231941E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.105801E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34490716.34 |
Maximum of Months | 0.303685E+09 | 0.117360E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35038364.13 | 0.358377E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172810E+09 |
February | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164015E+09 |
March | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19308.36 | 0.136158E+09 |
April | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120850E+09 |
May | 0.303504E+09 | 73514584.64 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1514538.46 | 65796201.35 |
June | 0.293842E+09 | 71047092.65 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18185717.58 | 17283970.85 |
July | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19534469.83 | 14259801.83 |
August | 0.303685E+09 | 73379236.13 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15819349.88 | 18022731.64 |
September | 0.293479E+09 | 71317789.65 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8042293.41 | 34576285.45 |
October | 0.303322E+09 | 73649933.14 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 158212.85 | 0.118759E+09 |
November | 0.293661E+09 | 71182441.15 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149143E+09 |
December | 0.303141E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190899E+09 |
Annual Sum or Average | 0.357224E+10 | 0.866527E+09 | 0.256645E+10 | 63273890.37 | 0.120257E+10 | ||||
Minimum of Months | 0.273974E+09 | 66518154.18 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14259801.83 |
Maximum of Months | 0.303685E+09 | 73785281.65 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19534469.83 | 0.190899E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.178610E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970350E+09 |
February | 0.415303E+11 | 0.157365E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921135E+09 |
March | 0.461292E+11 | 0.169568E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 245.78 | 0.811633E+09 |
April | 0.445315E+11 | 0.157841E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739363E+09 |
May | 0.460320E+11 | 0.156448E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1921696.36 | 0.460816E+09 |
June | 0.446286E+11 | 0.147107E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45988235.99 | 0.164634E+09 |
July | 0.459349E+11 | 0.152828E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48156124.60 | 0.149204E+09 |
August | 0.461292E+11 | 0.160508E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38241646.83 | 0.172331E+09 |
September | 0.445315E+11 | 0.160344E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18941637.31 | 0.268709E+09 |
October | 0.459349E+11 | 0.173887E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 321940.19 | 0.725264E+09 |
November | 0.444343E+11 | 0.170908E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857903E+09 |
December | 0.459349E+11 | 0.178083E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105454E+10 |
Annual Sum or Average | 0.541686E+12 | 0.196350E+11 | 0.175857E+12 | 0.153572E+09 | 0.729588E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.147107E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149204E+09 |
Maximum of Months | 0.461292E+11 | 0.178610E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48156124.60 | 0.105454E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.178610E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990325E+09 |
February | 0.415303E+11 | 0.157365E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940046E+09 |
March | 0.461292E+11 | 0.169568E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136.16 | 0.831150E+09 |
April | 0.445315E+11 | 0.157841E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757548E+09 |
May | 0.460320E+11 | 0.156448E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1421111.87 | 0.473932E+09 |
June | 0.446286E+11 | 0.147107E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41786955.67 | 0.169866E+09 |
July | 0.459349E+11 | 0.152828E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43546609.67 | 0.154214E+09 |
August | 0.461292E+11 | 0.160508E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34448097.90 | 0.177576E+09 |
September | 0.445315E+11 | 0.160344E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16587589.96 | 0.275582E+09 |
October | 0.459349E+11 | 0.173887E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 250550.78 | 0.740970E+09 |
November | 0.444343E+11 | 0.170908E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876076E+09 |
December | 0.459349E+11 | 0.178083E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107498E+10 |
Annual Sum or Average | 0.541686E+12 | 0.196350E+11 | 0.175857E+12 | 0.138041E+09 | 0.746226E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.147107E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154214E+09 |
Maximum of Months | 0.461292E+11 | 0.178610E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43546609.67 | 0.107498E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102127E+10 |
February | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965010E+09 |
March | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870498E+09 |
April | 0.396281E+10 | 0.109411E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.797485E+09 |
May | 0.409635E+10 | 0.113447E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529902E+09 |
June | 0.397146E+10 | 0.109912E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 5727192.25 | 0.218503E+09 |
July | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4771071.45 | 0.205781E+09 |
August | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3095731.89 | 0.233709E+09 |
September | 0.396281E+10 | 0.109411E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 292616.58 | 0.328856E+09 |
October | 0.408770E+10 | 0.113250E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 516.13 | 0.783030E+09 |
November | 0.395417E+10 | 0.109825E+10 | 0.314783E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.910340E+09 |
December | 0.408770E+10 | 0.112945E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109565E+10 |
Annual Sum or Average | 0.482041E+11 | 0.133394E+11 | 0.382987E+12 | 0.359593E+12 | 13887128.29 | 0.796004E+10 | |||
Minimum of Months | 0.369574E+10 | 0.102255E+10 | 0.293798E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205781E+09 |
Maximum of Months | 0.410499E+10 | 0.113643E+10 | 0.325276E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 5727192.25 | 0.109565E+10 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583778E+09 |
February | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552500E+09 |
March | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479870E+09 |
April | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432675E+09 |
May | 0.00 | 0.157202E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2368363.29 | 0.256097E+09 |
June | 0.00 | 0.152304E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40551530.18 | 87695035.59 |
July | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42723938.88 | 78680218.70 |
August | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34783790.30 | 93042708.98 |
September | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17491953.59 | 0.149201E+09 |
October | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 355431.38 | 0.425210E+09 |
November | 0.00 | 0.152183E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511429E+09 |
December | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635677E+09 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | 0.138275E+09 | 0.428586E+10 | |||||
Minimum of Months | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78680218.70 |
Maximum of Months | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42723938.88 | 0.635677E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.161153E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381945E+09 |
February | 0.00 | 0.145507E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360812E+09 |
March | 0.00 | 0.161712E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3131.50 | 0.311458E+09 |
April | 0.00 | 0.155689E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279876E+09 |
May | 0.00 | 0.161433E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2114425.82 | 0.167775E+09 |
June | 0.00 | 0.156404E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28864245.33 | 57374308.57 |
July | 0.00 | 0.160719E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30272073.64 | 51142053.60 |
August | 0.00 | 0.161712E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25018252.74 | 59841336.37 |
September | 0.00 | 0.155689E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12690750.98 | 97362524.52 |
October | 0.00 | 0.161153E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 307211.97 | 0.281182E+09 |
November | 0.00 | 0.156279E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337267E+09 |
December | 0.00 | 0.160719E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418744E+09 |
Annual Sum or Average | 0.189817E+10 | 0.359769E+10 | 99270091.97 | 0.280478E+10 | |||||
Minimum of Months | 0.00 | 0.145507E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51142053.60 |
Maximum of Months | 0.00 | 0.161712E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30272073.64 | 0.418744E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.870792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395963E+09 |
February | 0.00 | 0.786245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376885E+09 |
March | 0.00 | 0.873811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107368.60 | 0.318210E+09 |
April | 0.00 | 0.841268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31093.50 | 0.279846E+09 |
May | 0.00 | 0.872301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5462819.20 | 0.152484E+09 |
June | 0.00 | 0.845126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40404361.44 | 49414059.91 |
July | 0.00 | 0.868443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40869740.00 | 45437966.75 |
August | 0.00 | 0.873811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34966370.99 | 52390152.71 |
September | 0.00 | 0.841268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18817395.87 | 90177482.17 |
October | 0.00 | 0.870792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 741078.26 | 0.280341E+09 |
November | 0.00 | 0.844455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3181.15 | 0.341154E+09 |
December | 0.00 | 0.868443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13682.67 | 0.434610E+09 |
Annual Sum or Average | 0.102568E+11 | 0.141417E+09 | 0.281691E+10 | ||||||
Minimum of Months | 0.00 | 0.786245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45437966.75 |
Maximum of Months | 0.00 | 0.873811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40869740.00 | 0.434610E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.921598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758320E+09 |
February | 0.00 | 0.832119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718903E+09 |
March | 0.00 | 0.924794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622001E+09 |
April | 0.00 | 0.890352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566796E+09 |
May | 0.00 | 0.923196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2431222.93 | 0.347814E+09 |
June | 0.00 | 0.894435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46267549.52 | 0.121548E+09 |
July | 0.00 | 0.919113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48722006.82 | 0.109179E+09 |
August | 0.00 | 0.924794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38564971.22 | 0.128916E+09 |
September | 0.00 | 0.890352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18429870.36 | 0.204049E+09 |
October | 0.00 | 0.921598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218705.30 | 0.561332E+09 |
November | 0.00 | 0.893725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669125E+09 |
December | 0.00 | 0.919113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820256E+09 |
Annual Sum or Average | 0.108552E+11 | 0.154634E+09 | 0.562824E+10 | ||||||
Minimum of Months | 0.00 | 0.832119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109179E+09 |
Maximum of Months | 0.00 | 0.924794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48722006.82 | 0.820256E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 10970.58 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 10970.58 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 10970.58 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 10970.58 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 10970.58 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 10970.58 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 10970.58 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 10970.58 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 10970.58 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 10970.58 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 10970.58 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 10970.58 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 10970.58 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 10970.58 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 545.79 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 864.26 | 05-JAN-18:52 |
February | 1169.53 | 01-FEB-00:10 | 545.79 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 904.61 | 12-FEB-06:54 |
March | 1169.53 | 01-MAR-00:10 | 545.79 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 784.94 | 19-MAR-06:52 |
April | 1169.53 | 01-APR-00:10 | 545.79 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 614.09 | 17-APR-02:56 |
May | 1169.53 | 01-MAY-00:10 | 545.79 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.12 | 17-MAY-14:00 | 470.37 | 03-MAY-01:51 |
June | 1169.53 | 01-JUN-00:10 | 545.79 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.50 | 26-JUN-14:53 | 346.83 | 09-JUN-04:59 |
July | 1169.53 | 01-JUL-00:10 | 545.79 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.29 | 16-JUL-12:52 | 299.04 | 02-JUL-04:51 |
August | 1169.53 | 01-AUG-00:10 | 545.79 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.50 | 16-AUG-15:52 | 259.56 | 12-AUG-23:01 |
September | 1169.53 | 01-SEP-00:10 | 545.79 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.35 | 10-SEP-15:53 | 498.63 | 21-SEP-21:51 |
October | 1169.53 | 02-OCT-00:10 | 545.79 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 | 10-OCT-16:59 | 659.00 | 30-OCT-06:12 |
November | 1169.53 | 01-NOV-00:10 | 545.79 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 773.36 | 29-NOV-20:54 |
December | 1169.53 | 01-DEC-00:10 | 545.79 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 947.09 | 23-DEC-23:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 545.79 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.56 | |||||
Maximum of Months | 1169.53 | 545.79 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 249.50 | 947.09 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 632.03 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 192.59 | 05-JAN-18:59 |
February | 1354.32 | 01-FEB-00:10 | 632.03 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 202.74 | 12-FEB-04:51 |
March | 1354.32 | 01-MAR-00:10 | 632.03 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 14-MAR-12:52 | 178.17 | 19-MAR-06:51 |
April | 1354.32 | 01-APR-00:10 | 632.03 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 141.72 | 17-APR-05:59 |
May | 1354.32 | 01-MAY-00:10 | 632.03 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.56 | 17-MAY-12:54 | 108.82 | 03-MAY-01:51 |
June | 1354.32 | 01-JUN-00:10 | 632.03 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.49 | 26-JUN-14:53 | 77.45 | 09-JUN-04:59 |
July | 1354.32 | 01-JUL-00:10 | 632.03 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.94 | 16-JUL-13:00 | 66.09 | 02-JUL-04:51 |
August | 1354.32 | 01-AUG-00:10 | 632.03 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.64 | 16-AUG-13:52 | 58.91 | 12-AUG-23:11 |
September | 1354.32 | 01-SEP-00:10 | 632.03 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 10-SEP-12:53 | 112.93 | 22-SEP-05:59 |
October | 1354.32 | 02-OCT-00:10 | 632.03 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 11-OCT-13:52 | 151.81 | 30-OCT-05:51 |
November | 1354.32 | 01-NOV-00:10 | 632.03 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 176.34 | 29-NOV-20:59 |
December | 1354.32 | 01-DEC-00:10 | 632.03 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 213.34 | 22-DEC-02:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 632.03 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.91 | |||||
Maximum of Months | 1354.32 | 632.03 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 57.49 | 213.34 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 400.68 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 713.55 | 05-JAN-20:53 |
February | 907.20 | 01-FEB-00:10 | 400.68 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 683.87 | 11-FEB-21:51 |
March | 907.20 | 01-MAR-00:10 | 400.68 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 596.93 | 19-MAR-06:53 |
April | 907.20 | 01-APR-00:10 | 400.68 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 514.65 | 02-APR-19:53 |
May | 907.20 | 01-MAY-00:10 | 400.68 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 56.85 | 17-MAY-12:54 | 411.75 | 02-MAY-20:51 |
June | 907.20 | 01-JUN-00:10 | 400.68 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 177.66 | 26-JUN-14:51 | 263.20 | 09-JUN-05:09 |
July | 907.20 | 01-JUL-00:10 | 400.68 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 150.81 | 16-JUL-12:54 | 249.02 | 05-JUL-21:53 |
August | 907.20 | 01-AUG-00:10 | 400.68 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 149.38 | 16-AUG-13:54 | 251.63 | 12-AUG-21:51 |
September | 907.20 | 01-SEP-00:10 | 400.68 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 102.17 | 10-SEP-12:51 | 467.01 | 21-SEP-19:53 |
October | 907.20 | 02-OCT-00:10 | 400.68 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 32.54 | 11-OCT-13:54 | 579.54 | 31-OCT-19:53 |
November | 907.20 | 01-NOV-00:10 | 400.68 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 686.77 | 29-NOV-20:53 |
December | 907.20 | 01-DEC-00:10 | 400.68 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 788.49 | 21-DEC-20:53 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 249.02 | ||||||
Maximum of Months | 907.20 | 400.68 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 177.66 | 788.49 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1097.76 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2228.47 | 14-JAN-04:53 |
February | 15368.40 | 01-FEB-00:10 | 1097.76 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 2357.32 | 12-FEB-06:51 |
March | 15368.40 | 01-MAR-00:10 | 1097.76 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 2047.27 | 19-MAR-06:51 |
April | 15368.40 | 01-APR-00:10 | 1097.76 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 1682.43 | 17-APR-02:51 |
May | 15368.40 | 01-MAY-00:10 | 1097.76 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.53 | 17-MAY-13:50 | 1304.11 | 03-MAY-01:51 |
June | 15368.40 | 01-JUN-00:10 | 1097.76 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 655.27 | 26-JUN-14:53 | 940.01 | 09-JUN-04:59 |
July | 15368.40 | 01-JUL-00:10 | 1097.76 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 567.02 | 16-JUL-12:52 | 783.52 | 02-JUL-04:51 |
August | 15368.40 | 01-AUG-00:10 | 1097.76 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.34 | 16-AUG-14:00 | 727.77 | 12-AUG-23:11 |
September | 15368.40 | 01-SEP-00:10 | 1097.76 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.60 | 10-SEP-15:53 | 1352.36 | 22-SEP-04:51 |
October | 15368.40 | 02-OCT-00:10 | 1097.76 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.65 | 10-OCT-16:59 | 1800.43 | 30-OCT-04:53 |
November | 15368.40 | 01-NOV-00:10 | 1097.76 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 2073.28 | 29-NOV-21:09 |
December | 15368.40 | 01-DEC-00:10 | 1097.76 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2515.74 | 22-DEC-02:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 1097.76 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.77 | |||||
Maximum of Months | 15368.40 | 1097.76 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 655.27 | 2515.74 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 6463.27 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4659.53 | 05-JAN-18:59 |
February | 45622.98 | 01-FEB-00:10 | 6463.27 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 4890.95 | 12-FEB-06:53 |
March | 45622.98 | 01-MAR-00:10 | 6463.27 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 4306.86 | 19-MAR-06:53 |
April | 45622.98 | 01-APR-00:10 | 6463.27 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 3423.63 | 17-APR-04:59 |
May | 45622.98 | 01-MAY-00:10 | 6463.27 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 468.98 | 17-MAY-12:54 | 2684.65 | 03-MAY-01:51 |
June | 45622.98 | 01-JUN-00:10 | 6463.27 | 01-JUN-19:19 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.35 | 26-JUN-14:53 | 1916.99 | 09-JUN-04:59 |
July | 45622.98 | 01-JUL-00:10 | 6463.27 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1179.47 | 16-JUL-13:00 | 1615.93 | 02-JUL-04:51 |
August | 45622.98 | 01-AUG-00:10 | 6463.27 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1169.31 | 16-AUG-14:00 | 1462.71 | 12-AUG-23:43 |
September | 45622.98 | 01-SEP-00:10 | 6463.27 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 768.08 | 10-SEP-13:53 | 2791.58 | 22-SEP-04:51 |
October | 45622.98 | 02-OCT-00:10 | 6463.27 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.60 | 11-OCT-14:00 | 3672.29 | 30-OCT-04:59 |
November | 45622.98 | 01-NOV-00:10 | 6463.27 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 4273.96 | 29-NOV-20:59 |
December | 45622.98 | 01-DEC-00:10 | 6463.27 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 5257.62 | 22-DEC-02:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 6463.27 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1462.71 | |||||
Maximum of Months | 45622.98 | 6463.27 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.35 | 5257.62 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.77 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 253.27 | 05-JAN-19:08 |
February | 180.00 | 01-FEB-00:10 | 137.77 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 266.95 | 12-FEB-04:54 |
March | 180.00 | 01-MAR-00:10 | 137.77 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 | 13-MAR-16:00 | 231.54 | 19-MAR-06:51 |
April | 180.00 | 01-APR-00:10 | 137.77 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 181.49 | 17-APR-02:54 |
May | 180.00 | 01-MAY-00:10 | 137.77 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.43 | 31-MAY-16:00 | 133.76 | 03-MAY-01:54 |
June | 180.00 | 01-JUN-00:10 | 137.77 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 26-JUN-15:20 | 86.14 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 137.77 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.59 | 16-JUL-15:20 | 71.14 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 137.77 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.81 | 16-AUG-15:31 | 59.34 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 137.77 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.13 | 10-SEP-16:00 | 139.35 | 22-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 137.77 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 | 10-OCT-15:49 | 194.70 | 30-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.77 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 228.33 | 29-NOV-20:54 |
December | 180.00 | 01-DEC-00:10 | 137.77 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 288.78 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.34 | |||||
Maximum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 | 288.78 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 253.25 | 05-JAN-19:08 |
February | 180.00 | 01-FEB-00:10 | 137.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 266.93 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 137.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 | 14-MAR-12:51 | 231.51 | 19-MAR-06:51 |
April | 180.00 | 01-APR-00:10 | 137.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 181.48 | 17-APR-02:54 |
May | 180.00 | 01-MAY-00:10 | 137.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.35 | 31-MAY-16:00 | 133.75 | 03-MAY-01:54 |
June | 180.00 | 01-JUN-00:10 | 137.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.02 | 26-JUN-15:20 | 86.14 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 137.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.36 | 16-JUL-15:20 | 71.13 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 137.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.00 | 16-AUG-15:32 | 59.34 | 13-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 137.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.87 | 10-SEP-16:00 | 139.34 | 22-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 137.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.89 | 11-OCT-13:53 | 194.68 | 30-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 228.31 | 29-NOV-20:54 |
December | 180.00 | 01-DEC-00:10 | 137.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 | 01-DEC-13:31 | 288.76 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.34 | |||||
Maximum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 87.02 | 288.76 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 86.58 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 73.97 | 14-JAN-03:51 |
February | 0.00 | 01-FEB-00:10 | 86.58 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 75.74 | 12-FEB-04:51 |
March | 0.00 | 01-MAR-00:10 | 86.58 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 66.53 | 19-MAR-06:51 |
April | 0.00 | 01-APR-00:10 | 86.58 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 51.07 | 17-APR-06:00 |
May | 0.00 | 01-MAY-00:10 | 86.58 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 17-MAY-13:00 | 41.32 | 12-MAY-02:51 |
June | 0.00 | 01-JUN-00:10 | 86.58 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 26-JUN-14:52 | 32.67 | 09-JUN-03:51 |
July | 0.00 | 01-JUL-00:10 | 86.58 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 | 16-JUL-13:00 | 28.69 | 02-JUL-04:51 |
August | 0.00 | 01-AUG-00:10 | 86.58 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 | 16-AUG-15:51 | 25.61 | 12-AUG-23:52 |
September | 0.00 | 01-SEP-00:10 | 86.58 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 10-SEP-12:51 | 46.35 | 22-SEP-06:00 |
October | 0.00 | 01-OCT-00:10 | 86.58 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 11-OCT-14:05 | 57.90 | 30-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 86.58 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 67.16 | 29-NOV-20:51 |
December | 0.00 | 01-DEC-00:10 | 86.58 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 75.81 | 21-DEC-16:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 86.58 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.61 | |||||
Maximum of Months | 0.00 | 86.58 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.84 | 75.81 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 86.61 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 70.68 | 05-JAN-19:09 |
February | 180.00 | 01-FEB-00:10 | 86.61 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 74.50 | 12-FEB-06:54 |
March | 180.00 | 01-MAR-00:10 | 86.61 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.39 | 14-MAR-12:51 | 65.00 | 19-MAR-06:51 |
April | 180.00 | 01-APR-00:10 | 86.61 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 19-APR-12:51 | 50.65 | 17-APR-02:54 |
May | 180.00 | 01-MAY-00:10 | 86.61 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 | 31-MAY-15:19 | 37.33 | 03-MAY-01:53 |
June | 180.00 | 01-JUN-00:10 | 86.61 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 | 26-JUN-15:20 | 24.04 | 09-JUN-04:51 |
July | 180.00 | 01-JUL-00:10 | 86.61 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 16-JUL-15:20 | 19.85 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 86.61 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 | 16-AUG-16:00 | 17.00 | 13-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 86.61 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.74 | 10-SEP-15:59 | 38.89 | 22-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 86.61 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | 11-OCT-13:51 | 54.34 | 30-OCT-06:03 |
November | 180.00 | 01-NOV-00:10 | 86.61 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 07-NOV-14:00 | 63.72 | 29-NOV-20:54 |
December | 180.00 | 01-DEC-00:10 | 86.61 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 | 01-DEC-14:00 | 80.59 | 22-DEC-02:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | |||||
Maximum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 | 80.59 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.77 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 253.27 | 05-JAN-19:08 |
February | 180.00 | 01-FEB-00:10 | 137.77 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 266.95 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 137.77 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.32 | 13-MAR-15:20 | 231.55 | 19-MAR-06:51 |
April | 180.00 | 01-APR-00:10 | 137.77 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 181.49 | 17-APR-02:54 |
May | 180.00 | 01-MAY-00:10 | 137.77 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.90 | 31-MAY-15:19 | 133.76 | 03-MAY-01:54 |
June | 180.00 | 01-JUN-00:10 | 137.77 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.02 | 26-JUN-15:20 | 86.14 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 137.77 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.39 | 16-JUL-13:00 | 71.14 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 137.77 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.09 | 16-AUG-15:21 | 66.24 | 13-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 137.77 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.07 | 10-SEP-16:00 | 139.35 | 22-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 137.77 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.07 | 11-OCT-15:20 | 194.70 | 30-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.77 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 228.33 | 29-NOV-20:54 |
December | 180.00 | 01-DEC-00:10 | 137.77 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 288.78 | 22-DEC-02:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.24 | |||||
Maximum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 92.02 | 288.78 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 253.25 | 05-JAN-19:10 |
February | 180.00 | 01-FEB-00:10 | 137.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 266.93 | 12-FEB-04:54 |
March | 180.00 | 01-MAR-00:10 | 137.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 | 14-MAR-13:00 | 231.51 | 19-MAR-06:51 |
April | 180.00 | 01-APR-00:10 | 137.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 181.48 | 17-APR-02:54 |
May | 180.00 | 01-MAY-00:10 | 137.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.89 | 31-MAY-15:19 | 133.75 | 03-MAY-01:54 |
June | 180.00 | 01-JUN-00:10 | 137.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.17 | 26-JUN-15:20 | 86.14 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 137.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.38 | 16-JUL-13:00 | 71.13 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 137.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.00 | 16-AUG-16:00 | 66.24 | 13-AUG-07:00 |
September | 180.00 | 01-SEP-00:10 | 137.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 | 10-SEP-16:00 | 139.34 | 22-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 137.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.89 | 11-OCT-13:53 | 194.68 | 30-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 228.31 | 29-NOV-20:54 |
December | 180.00 | 01-DEC-00:10 | 137.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.08 | 01-DEC-14:00 | 288.76 | 22-DEC-02:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.24 | |||||
Maximum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 91.17 | 288.76 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.77 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 253.72 | 05-JAN-19:08 |
February | 180.00 | 01-FEB-00:10 | 137.77 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 267.41 | 12-FEB-05:00 |
March | 180.00 | 01-MAR-00:10 | 137.77 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 | 14-MAR-15:19 | 231.51 | 19-MAR-06:51 |
April | 180.00 | 01-APR-00:10 | 137.77 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 181.91 | 17-APR-02:54 |
May | 180.00 | 01-MAY-00:10 | 137.77 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.60 | 31-MAY-16:00 | 134.15 | 03-MAY-01:54 |
June | 180.00 | 01-JUN-00:10 | 137.77 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.95 | 26-JUN-15:00 | 86.52 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 137.77 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.08 | 16-JUL-13:00 | 71.50 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 137.77 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 16-AUG-15:33 | 59.70 | 12-AUG-23:51 |
September | 180.00 | 01-SEP-00:10 | 137.77 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.19 | 10-SEP-16:00 | 139.75 | 22-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 137.77 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 10-OCT-16:00 | 195.12 | 30-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 137.77 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 228.77 | 29-NOV-20:54 |
December | 180.00 | 01-DEC-00:10 | 137.77 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 289.25 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 | |||||
Maximum of Months | 180.00 | 137.77 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 84.95 | 289.25 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 137.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 253.70 | 05-JAN-19:09 |
February | 180.00 | 01-FEB-00:10 | 137.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 267.39 | 12-FEB-04:53 |
March | 180.00 | 01-MAR-00:10 | 137.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 14-MAR-12:51 | 231.47 | 19-MAR-06:51 |
April | 180.00 | 01-APR-00:10 | 137.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 181.89 | 17-APR-02:54 |
May | 180.00 | 01-MAY-00:10 | 137.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.32 | 31-MAY-16:00 | 134.14 | 03-MAY-01:54 |
June | 180.00 | 01-JUN-00:10 | 137.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.94 | 26-JUN-15:00 | 86.51 | 09-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 137.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.08 | 16-JUL-13:00 | 71.50 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 137.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.46 | 16-AUG-15:31 | 59.70 | 12-AUG-24:00 |
September | 180.00 | 01-SEP-00:10 | 137.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.08 | 10-SEP-16:00 | 139.73 | 22-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 137.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.56 | 11-OCT-13:53 | 195.11 | 30-OCT-06:31 |
November | 180.00 | 01-NOV-00:10 | 137.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 228.75 | 29-NOV-21:00 |
December | 180.00 | 01-DEC-00:10 | 137.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 | 01-DEC-13:31 | 289.22 | 22-DEC-02:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 | |||||
Maximum of Months | 180.00 | 137.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 84.94 | 289.22 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 86.61 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 129.80 | 05-JAN-19:07 |
February | 180.00 | 01-FEB-00:10 | 86.61 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 136.80 | 12-FEB-04:51 |
March | 180.00 | 01-MAR-00:10 | 86.61 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 13-MAR-16:00 | 118.77 | 19-MAR-06:51 |
April | 180.00 | 01-APR-00:10 | 86.61 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 93.06 | 17-APR-02:54 |
May | 180.00 | 01-MAY-00:10 | 86.61 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 31-MAY-15:37 | 68.63 | 03-MAY-01:54 |
June | 180.00 | 01-JUN-00:10 | 86.61 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.13 | 26-JUN-15:20 | 44.26 | 09-JUN-04:54 |
July | 180.00 | 01-JUL-00:10 | 86.61 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.39 | 16-JUL-13:00 | 36.58 | 02-JUL-05:00 |
August | 180.00 | 01-AUG-00:10 | 86.61 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 | 16-AUG-16:00 | 30.54 | 12-AUG-23:51 |
September | 180.00 | 01-SEP-00:10 | 86.61 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.73 | 10-SEP-15:58 | 71.49 | 22-SEP-05:51 |
October | 180.00 | 01-OCT-00:10 | 86.61 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 11-OCT-14:00 | 99.82 | 30-OCT-05:51 |
November | 180.00 | 01-NOV-00:10 | 86.61 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 117.04 | 29-NOV-20:54 |
December | 180.00 | 01-DEC-00:10 | 86.61 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 147.98 | 22-DEC-03:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.54 | |||||
Maximum of Months | 180.00 | 86.61 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 46.13 | 147.98 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1927.76 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 678.86 | 05-JAN-19:09 |
February | 26988.77 | 01-FEB-00:10 | 1927.76 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 711.31 | 12-FEB-06:59 |
March | 26988.77 | 01-MAR-00:10 | 1927.76 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 | 14-MAR-12:52 | 638.75 | 19-MAR-06:51 |
April | 26988.77 | 01-APR-00:10 | 1927.76 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 511.98 | 17-APR-02:51 |
May | 26988.77 | 01-MAY-00:10 | 1927.76 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.97 | 17-MAY-14:00 | 405.25 | 03-MAY-01:51 |
June | 26988.77 | 01-JUN-00:10 | 1927.76 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.61 | 26-JUN-14:53 | 292.63 | 09-JUN-04:59 |
July | 26988.77 | 01-JUL-00:10 | 1927.76 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.67 | 16-JUL-13:00 | 246.79 | 02-JUL-04:59 |
August | 26988.77 | 01-AUG-00:10 | 1927.76 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.98 | 16-AUG-14:00 | 229.38 | 12-AUG-22:59 |
September | 26988.77 | 01-SEP-00:10 | 1927.76 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.04 | 10-SEP-13:53 | 417.73 | 22-SEP-04:51 |
October | 26988.77 | 02-OCT-00:10 | 1927.76 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.51 | 11-OCT-14:00 | 544.50 | 30-OCT-05:53 |
November | 26988.77 | 01-NOV-00:10 | 1927.76 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 628.60 | 29-NOV-21:09 |
December | 26988.77 | 01-DEC-00:10 | 1927.76 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 759.75 | 22-DEC-02:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.38 | |||||
Maximum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 176.61 | 759.75 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 1927.76 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 688.76 | 05-JAN-19:09 |
February | 26988.77 | 01-FEB-00:10 | 1927.76 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 719.17 | 12-FEB-06:59 |
March | 26988.77 | 01-MAR-00:10 | 1927.76 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 14-MAR-12:52 | 646.16 | 19-MAR-06:53 |
April | 26988.77 | 01-APR-00:10 | 1927.76 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 519.29 | 17-APR-05:59 |
May | 26988.77 | 01-MAY-00:10 | 1927.76 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.46 | 17-MAY-14:00 | 411.22 | 03-MAY-01:51 |
June | 26988.77 | 01-JUN-00:10 | 1927.76 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.39 | 26-JUN-14:53 | 296.03 | 09-JUN-04:59 |
July | 26988.77 | 01-JUL-00:10 | 1927.76 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.10 | 16-JUL-13:00 | 250.39 | 02-JUL-04:59 |
August | 26988.77 | 01-AUG-00:10 | 1927.76 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.44 | 16-AUG-14:00 | 233.95 | 12-AUG-22:59 |
September | 26988.77 | 01-SEP-00:10 | 1927.76 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.11 | 10-SEP-13:53 | 422.38 | 22-SEP-05:53 |
October | 26988.77 | 02-OCT-00:10 | 1927.76 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.23 | 11-OCT-14:00 | 551.88 | 30-OCT-05:59 |
November | 26988.77 | 01-NOV-00:10 | 1927.76 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 637.86 | 29-NOV-21:09 |
December | 26988.77 | 01-DEC-00:10 | 1927.76 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 767.58 | 22-DEC-02:51 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.95 | |||||
Maximum of Months | 26988.77 | 1927.76 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 171.39 | 767.58 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1090.83 | 02-JAN-20:10 | 14604.56 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 711.49 | 05-JAN-18:53 |
February | 2401.70 | 01-FEB-00:10 | 1090.83 | 01-FEB-20:10 | 14604.56 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 673.42 | 12-FEB-06:53 |
March | 2401.70 | 01-MAR-00:10 | 1090.83 | 01-MAR-20:10 | 14604.56 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 615.82 | 19-MAR-06:53 |
April | 2401.70 | 01-APR-00:10 | 1090.83 | 03-APR-19:10 | 14604.56 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 497.35 | 02-APR-18:51 |
May | 2401.70 | 01-MAY-00:10 | 1090.83 | 01-MAY-19:10 | 14604.56 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 403.29 | 02-MAY-06:29 |
June | 2401.70 | 01-JUN-00:10 | 1090.83 | 01-JUN-19:10 | 14604.56 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 97.27 | 26-JUN-14:51 | 293.57 | 09-JUN-05:19 |
July | 2401.70 | 01-JUL-00:10 | 1090.83 | 03-JUL-19:10 | 14604.56 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 73.07 | 16-JUL-13:00 | 250.33 | 03-JUL-06:59 |
August | 2401.70 | 01-AUG-00:10 | 1090.83 | 01-AUG-19:10 | 14604.56 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 80.67 | 16-AUG-14:00 | 260.88 | 12-AUG-22:41 |
September | 2401.70 | 01-SEP-00:10 | 1090.83 | 01-SEP-19:10 | 14604.56 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 31.12 | 10-SEP-13:53 | 442.31 | 21-SEP-18:51 |
October | 2401.70 | 02-OCT-00:10 | 1090.83 | 02-OCT-19:10 | 14604.56 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 7.74 | 10-OCT-13:53 | 552.51 | 30-OCT-18:11 |
November | 2401.70 | 01-NOV-00:10 | 1090.83 | 01-NOV-19:10 | 14604.56 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 651.44 | 29-NOV-20:53 |
December | 2401.70 | 01-DEC-00:10 | 1090.83 | 01-DEC-20:10 | 14604.56 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 758.78 | 21-DEC-17:53 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 250.33 | ||||||
Maximum of Months | 2401.70 | 1090.83 | 14604.56 | 22492.83 | 0.00 | 0.00 | 0.00 | 97.27 | 758.78 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1511.55 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 419.93 | 05-JAN-19:00 |
February | 0.00 | 1511.55 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 438.57 | 12-FEB-04:51 |
March | 0.00 | 1511.55 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 389.94 | 19-MAR-06:51 |
April | 0.00 | 1511.55 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 309.01 | 17-APR-06:00 |
May | 0.00 | 1511.55 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.07 | 17-MAY-12:54 | 237.28 | 03-MAY-01:53 |
June | 0.00 | 1511.55 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.28 | 26-JUN-14:53 | 162.08 | 09-JUN-04:01 |
July | 0.00 | 1511.55 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.29 | 16-JUL-13:00 | 139.59 | 02-JUL-04:51 |
August | 0.00 | 1511.55 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.22 | 16-AUG-13:52 | 123.26 | 12-AUG-22:51 |
September | 0.00 | 1511.55 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.41 | 10-SEP-12:51 | 246.43 | 22-SEP-05:01 |
October | 0.00 | 1511.55 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 | 11-OCT-13:54 | 333.67 | 30-OCT-07:00 |
November | 0.00 | 1511.55 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 387.20 | 29-NOV-20:51 |
December | 0.00 | 1511.55 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 458.22 | 22-DEC-02:51 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.26 | ||||
Maximum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 128.28 | 458.22 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 155.22 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 278.33 | 05-JAN-18:56 |
February | 0.00 | 155.22 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 290.66 | 12-FEB-04:53 |
March | 0.00 | 155.22 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 14-MAR-12:52 | 257.26 | 19-MAR-06:51 |
April | 0.00 | 155.22 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 200.97 | 17-APR-05:59 |
May | 0.00 | 155.22 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.93 | 17-MAY-12:52 | 156.26 | 03-MAY-01:51 |
June | 0.00 | 155.22 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.06 | 26-JUN-14:53 | 111.35 | 09-JUN-04:59 |
July | 0.00 | 155.22 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.04 | 16-JUL-12:52 | 96.03 | 02-JUL-04:57 |
August | 0.00 | 155.22 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.21 | 16-AUG-13:52 | 83.05 | 12-AUG-22:51 |
September | 0.00 | 155.22 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.57 | 10-SEP-12:53 | 164.16 | 22-SEP-05:59 |
October | 0.00 | 155.22 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.99 | 11-OCT-13:52 | 217.95 | 30-OCT-06:21 |
November | 0.00 | 155.22 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 252.55 | 29-NOV-20:59 |
December | 0.00 | 155.22 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 313.55 | 22-DEC-02:52 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 155.22 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.05 | ||||
Maximum of Months | 0.00 | 155.22 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 88.06 | 313.55 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 838.75 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 302.83 | 05-JAN-18:52 |
February | 0.00 | 838.75 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 316.98 | 12-FEB-04:52 |
March | 0.00 | 838.75 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 14-MAR-12:52 | 278.82 | 19-MAR-06:52 |
April | 0.00 | 838.75 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 19-APR-12:51 | 216.25 | 17-APR-02:52 |
May | 0.00 | 838.75 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.88 | 17-MAY-12:52 | 160.93 | 03-MAY-01:58 |
June | 0.00 | 838.75 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.02 | 26-JUN-14:51 | 112.57 | 09-JUN-03:51 |
July | 0.00 | 838.75 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.77 | 16-JUL-12:52 | 98.41 | 02-JUL-04:59 |
August | 0.00 | 838.75 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.55 | 16-AUG-13:52 | 82.49 | 12-AUG-22:51 |
September | 0.00 | 838.75 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.31 | 09-SEP-12:52 | 170.32 | 22-SEP-04:51 |
October | 0.00 | 838.75 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.65 | 11-OCT-13:52 | 231.88 | 30-OCT-07:00 |
November | 0.00 | 838.75 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | 06-NOV-13:58 | 272.17 | 29-NOV-20:52 |
December | 0.00 | 838.75 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 | 01-DEC-13:53 | 334.48 | 22-DEC-02:52 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 838.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.49 | |||
Maximum of Months | 0.00 | 838.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.02 | 334.48 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 887.69 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 546.52 | 05-JAN-18:56 |
February | 0.00 | 887.69 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 570.65 | 12-FEB-04:56 |
March | 0.00 | 887.69 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 498.48 | 19-MAR-07:00 |
April | 0.00 | 887.69 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 387.82 | 17-APR-02:53 |
May | 0.00 | 887.69 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.11 | 17-MAY-12:52 | 312.01 | 03-MAY-01:51 |
June | 0.00 | 887.69 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.74 | 26-JUN-14:53 | 221.87 | 09-JUN-04:51 |
July | 0.00 | 887.69 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.27 | 16-JUL-12:52 | 189.44 | 02-JUL-04:51 |
August | 0.00 | 887.69 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.18 | 16-AUG-13:52 | 164.46 | 12-AUG-22:51 |
September | 0.00 | 887.69 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.03 | 09-SEP-12:52 | 321.87 | 22-SEP-04:51 |
October | 0.00 | 887.69 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.36 | 11-OCT-13:52 | 417.34 | 30-OCT-03:51 |
November | 0.00 | 887.69 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 488.01 | 29-NOV-20:52 |
December | 0.00 | 887.69 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 601.34 | 22-DEC-02:52 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 887.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.46 | |||
Maximum of Months | 0.00 | 887.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.74 | 601.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 30606.18 | 20-JAN-13:03 | 25559.76 | 30473.84 | 35488.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29497.67 | 18-FEB-13:33 | 38339.64 | 30473.84 | 35488.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26864.50 | 14-MAR-18:06 | 80513.24 | 87764.66 | 82129.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27643.07 | 19-APR-17:53 | 63899.40 | 73137.22 | 70976.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29719.90 | 10-MAY-20:53 | 102239.04 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30119.13 | 29-JUN-20:33 | 102239.04 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30662.07 | 15-JUL-00:13 | 115018.92 | 24379.07 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31216.95 | 11-AUG-00:53 | 115018.92 | 18284.30 | 25348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33046.67 | 26-SEP-09:07 | 25559.76 | 30473.84 | 35488.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32822.37 | 07-OCT-10:52 | 38339.64 | 30473.84 | 35488.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33469.39 | 05-NOV-12:30 | 25559.76 | 24379.07 | 30418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33741.24 | 01-DEC-13:35 | 25559.76 | 30473.84 | 35488.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 26864.50 | 25559.76 | 18284.30 | 25348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33741.24 | 115018.92 | 97516.29 | 91255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5677.29 | 20-JAN-13:33 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.55 |
February | 5418.24 | 18-FEB-13:08 | 3898.44 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.45 |
March | 5127.37 | 14-MAR-13:07 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 |
April | 4469.74 | 07-APR-12:47 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.40 |
May | 4117.48 | 06-MAY-13:25 | 3898.44 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 0.00 |
June | 4054.97 | 26-JUN-22:19 | 10525.79 | 1637.38 | 2598.08 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 | 0.00 |
July | 4275.12 | 25-JUL-14:09 | 3898.44 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 | 0.00 |
August | 4520.73 | 27-AUG-12:08 | 2339.06 | 1091.59 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 |
September | 4980.37 | 27-SEP-12:25 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 |
October | 5367.46 | 10-OCT-12:53 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.08 |
November | 5599.86 | 07-NOV-12:53 | 2598.96 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.76 |
December | 5420.97 | 02-DEC-13:33 | 3898.44 | 1516.10 | 2525.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.87 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4054.97 | 2339.06 | 1091.59 | 1948.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5677.29 | 10525.79 | 1637.38 | 2598.08 | 0.00 | 0.00 | 0.00 | 0.00 | 15.03 | 173.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3009.23 | 20-JAN-13:43 | 2708.64 | 1580.08 | 2632.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.61 |
February | 2975.97 | 18-FEB-13:08 | 4514.40 | 1755.64 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 |
March | 3049.29 | 13-MAR-15:43 | 7524.00 | 1755.64 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 |
April | 2776.29 | 20-APR-17:13 | 7524.00 | 4213.55 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 |
May | 2979.56 | 10-MAY-20:53 | 12038.40 | 5618.06 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.56 |
June | 3175.84 | 26-JUN-22:19 | 12188.88 | 1896.10 | 3008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
July | 3136.17 | 17-JUL-22:55 | 10834.56 | 1685.42 | 2674.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 | 0.00 |
August | 3146.04 | 16-AUG-22:33 | 13543.20 | 2106.77 | 3342.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.84 |
September | 3055.57 | 13-SEP-17:58 | 7524.00 | 4213.55 | 5850.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 |
October | 3064.16 | 11-OCT-15:17 | 7524.00 | 1755.64 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | 0.00 |
November | 3030.15 | 07-NOV-15:14 | 4514.40 | 1755.64 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 |
December | 3014.85 | 02-DEC-14:03 | 4514.40 | 1755.64 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.13 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2776.29 | 2708.64 | 1580.08 | 2632.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3175.84 | 13543.20 | 5618.06 | 7521.46 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | 23.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2319.18 | 20-JAN-13:20 | 0.00 | 3778.88 | 2783.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.58 |
February | 2235.77 | 18-FEB-12:51 | 0.00 | 4198.76 | 3092.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.56 |
March | 2708.47 | 14-MAR-17:53 | 0.00 | 10077.02 | 6185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.18 |
April | 2683.74 | 20-APR-18:59 | 0.00 | 13436.03 | 7952.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.62 |
May | 3003.70 | 17-MAY-18:26 | 0.00 | 6718.02 | 3976.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.44 |
June | 3132.25 | 14-JUN-21:14 | 0.00 | 9069.32 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 |
July | 3138.95 | 17-JUL-22:55 | 0.00 | 4030.81 | 2827.61 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 0.00 |
August | 3083.01 | 16-AUG-22:06 | 0.00 | 2519.26 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 |
September | 3031.12 | 10-SEP-19:43 | 0.00 | 8061.62 | 4771.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 2724.21 | 11-OCT-15:31 | 0.00 | 4198.76 | 3092.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 | 0.00 |
November | 2568.10 | 09-NOV-08:45 | 0.00 | 6718.02 | 4418.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.58 |
December | 2277.38 | 02-DEC-12:42 | 0.00 | 4198.76 | 3092.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.91 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2235.77 | 0.00 | 2519.26 | 1767.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3138.95 | 0.00 | 13436.03 | 7952.65 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 | 79.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 957.69 | 20-JAN-13:14 | 0.00 | 388.06 | 802.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 |
February | 935.70 | 18-FEB-13:08 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
March | 986.60 | 14-MAR-14:40 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 |
April | 959.60 | 20-APR-12:49 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 |
May | 1007.90 | 17-MAY-08:58 | 0.00 | 689.88 | 1274.51 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 0.00 |
June | 1249.68 | 26-JUN-22:19 | 0.00 | 465.67 | 917.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 0.00 |
July | 1264.76 | 17-JUL-23:07 | 0.00 | 206.97 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 0.00 |
August | 1224.89 | 16-AUG-22:06 | 0.00 | 258.71 | 509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
September | 1134.92 | 13-SEP-17:03 | 0.00 | 1034.83 | 1784.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 | 0.00 |
October | 999.12 | 11-OCT-16:52 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 |
November | 971.72 | 07-NOV-13:35 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 |
December | 940.32 | 02-DEC-14:06 | 0.00 | 431.18 | 892.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 935.70 | 0.00 | 206.97 | 458.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1264.76 | 0.00 | 1034.83 | 1784.32 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 | 19.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 62667.81 | 20-JAN-20:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 341.62 |
February | 62454.87 | 17-FEB-20:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 343.92 |
March | 62793.43 | 09-MAR-20:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 285.74 |
April | 62959.69 | 19-APR-19:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 218.86 |
May | 68100.66 | 04-MAY-19:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 219.49 |
June | 74968.43 | 29-JUN-20:32 | 8064.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 156.13 |
July | 70568.32 | 17-JUL-20:52 | 8064.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 44.90 |
August | 75689.61 | 08-AUG-20:52 | 8064.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 177.89 |
September | 66445.65 | 14-SEP-20:32 | 8064.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 216.25 |
October | 69144.18 | 20-OCT-19:51 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 296.80 |
November | 62842.93 | 08-NOV-20:52 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 342.32 |
December | 68751.58 | 14-DEC-20:51 | 7056.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 410.14 |
Annual Sum or Average | |||||||||||
Minimum of Months | 62454.87 | 7056.00 | 3561.64 | 43321.27 | 376357.04 | 0.00 | 0.00 | 0.00 | 0.00 | 44.90 | |
Maximum of Months | 75689.61 | 8064.00 | 4006.85 | 45728.01 | 397265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 410.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23291.98 | 20-JAN-13:33 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.41 |
February | 22719.76 | 18-FEB-12:43 | 51228.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.90 |
March | 21022.38 | 11-MAR-12:49 | 51228.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.86 |
April | 18733.87 | 07-APR-12:47 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.61 |
May | 17345.05 | 10-MAY-20:53 | 136608.00 | 9757.88 | 9144.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.23 |
June | 18851.07 | 14-JUN-03:23 | 153684.00 | 1219.74 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.92 |
July | 18804.97 | 18-JUL-22:13 | 153684.00 | 3659.21 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.22 |
August | 18992.61 | 16-AUG-22:33 | 153684.00 | 3659.21 | 4064.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.38 |
September | 20420.09 | 27-SEP-12:25 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 |
October | 21914.94 | 10-OCT-12:53 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.94 |
November | 23002.83 | 07-NOV-12:53 | 34152.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.64 |
December | 22805.50 | 02-DEC-13:33 | 51228.00 | 670.85 | 3556.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.94 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17345.05 | 34152.00 | 670.85 | 2032.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | |
Maximum of Months | 23291.98 | 153684.00 | 9757.88 | 9144.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 61939.28 | 20-JAN-13:33 | 101384.40 | 15440.03 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.45 |
February | 61789.80 | 18-FEB-12:46 | 152076.60 | 15440.03 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.54 |
March | 60780.75 | 13-MAR-15:43 | 253461.00 | 15440.03 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.78 |
April | 56267.03 | 12-APR-15:25 | 253461.00 | 15440.03 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.20 |
May | 59157.18 | 10-MAY-20:53 | 405537.60 | 57451.29 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.42 |
June | 62807.72 | 14-JUN-03:23 | 456229.80 | 7181.41 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.72 |
July | 62824.50 | 18-JUL-01:29 | 456229.80 | 7181.41 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.35 |
August | 62679.65 | 16-AUG-22:33 | 456229.80 | 21544.23 | 42228.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.43 |
September | 60451.13 | 13-SEP-00:59 | 456229.80 | 10772.12 | 26392.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.68 |
October | 61173.33 | 11-OCT-15:05 | 253461.00 | 15440.03 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 74.27 | 0.00 |
November | 61754.72 | 06-NOV-12:53 | 101384.40 | 15440.03 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.91 |
December | 62368.77 | 02-DEC-13:33 | 152076.60 | 15440.03 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.13 |
Annual Sum or Average | |||||||||||
Minimum of Months | 56267.03 | 101384.40 | 7181.41 | 21114.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 62824.50 | 456229.80 | 57451.29 | 95013.56 | 0.00 | 0.00 | 0.00 | 0.00 | 74.27 | 512.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2303.14 | 21-JAN-16:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.14 |
February | 2323.21 | 17-FEB-16:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.28 |
March | 2384.44 | 13-MAR-15:11 | 874.80 | 99.19 | 450.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 2572.47 | 06-APR-18:31 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.06 |
May | 2356.33 | 10-MAY-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 0.00 |
June | 2412.89 | 14-JUN-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 0.00 |
July | 2423.34 | 01-JUL-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 | 0.00 |
August | 2444.59 | 26-AUG-16:45 | 954.00 | 142.07 | 1053.59 | 0.00 | 0.00 | 0.00 | 0.00 | 43.75 | 0.00 |
September | 2413.48 | 28-SEP-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 35.35 | 0.00 |
October | 2409.30 | 11-OCT-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 | 0.00 |
November | 2348.23 | 05-NOV-15:11 | 432.00 | 68.88 | 442.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 |
December | 2269.95 | 29-DEC-16:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2269.95 | 432.00 | 68.88 | 442.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2572.47 | 1386.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 77.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2279.41 | 23-JAN-16:51 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.02 |
February | 2259.38 | 26-FEB-17:11 | 954.00 | 142.06 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.48 |
March | 2659.53 | 31-MAR-18:01 | 1386.00 | 1222.56 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.12 |
April | 2651.66 | 08-APR-17:21 | 972.00 | 1170.91 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.19 |
May | 2428.39 | 27-MAY-15:31 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.59 |
June | 2532.98 | 30-JUN-21:11 | 1800.00 | 929.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 | 0.00 |
July | 2513.94 | 01-JUL-21:11 | 1386.00 | 1170.91 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.98 |
August | 2445.63 | 13-AUG-21:11 | 1386.00 | 1170.91 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.47 |
September | 2475.21 | 09-SEP-16:11 | 954.00 | 142.06 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 21.99 | 0.00 |
October | 2400.98 | 11-OCT-18:11 | 1386.00 | 1222.56 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.97 |
November | 2233.72 | 03-NOV-15:11 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 |
December | 2214.48 | 03-DEC-16:11 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.13 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2214.48 | 540.00 | 86.10 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2659.53 | 1800.00 | 1222.56 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 21.99 | 65.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 776.72 | 20-JAN-15:01 | 0.00 | 37.88 | 216.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.26 |
February | 642.67 | 18-FEB-13:20 | 0.00 | 54.11 | 335.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 |
March | 606.06 | 11-MAR-13:00 | 0.00 | 54.11 | 335.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 |
April | 235.34 | 13-APR-12:23 | 0.00 | 32.47 | 185.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 |
May | 242.23 | 06-MAY-15:02 | 0.00 | 54.11 | 541.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.95 |
June | 332.47 | 26-JUN-17:11 | 0.00 | 584.43 | 1238.36 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 | 0.00 |
July | 324.32 | 18-JUL-17:12 | 0.00 | 584.43 | 1238.36 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 | 0.00 |
August | 402.83 | 31-AUG-12:31 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 0.00 |
September | 610.85 | 28-SEP-13:10 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 | 0.00 |
October | 788.17 | 10-OCT-14:01 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.69 |
November | 772.32 | 16-NOV-15:01 | 0.00 | 54.11 | 309.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.39 |
December | 744.11 | 17-DEC-15:01 | 0.00 | 54.11 | 335.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 |
Annual Sum or Average | |||||||||||
Minimum of Months | 235.34 | 0.00 | 32.47 | 185.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 788.17 | 0.00 | 584.43 | 1238.36 | 0.00 | 0.00 | 0.00 | 0.00 | 16.38 | 17.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 655.99 | 21-JAN-09:01 | 540.00 | 202.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 |
February | 635.79 | 27-FEB-19:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 |
March | 690.33 | 14-MAR-20:11 | 1602.00 | 768.63 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 |
April | 672.98 | 08-APR-08:61 | 540.00 | 202.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 |
May | 744.59 | 17-MAY-21:11 | 1800.00 | 584.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 |
June | 780.31 | 30-JUN-21:11 | 1800.00 | 584.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 0.00 |
July | 781.14 | 07-JUL-21:11 | 1800.00 | 584.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 |
August | 760.98 | 01-AUG-21:11 | 1800.00 | 584.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 |
September | 755.01 | 08-SEP-21:11 | 1800.00 | 584.59 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 |
October | 686.47 | 01-OCT-18:01 | 1170.00 | 866.07 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 |
November | 652.70 | 06-NOV-19:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.29 |
December | 643.10 | 03-DEC-09:01 | 540.00 | 202.08 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 |
Annual Sum or Average | |||||||||||
Minimum of Months | 635.79 | 540.00 | 202.08 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 781.14 | 1800.00 | 866.07 | 1780.62 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 | 23.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2009.24 | 20-JAN-09:01 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.77 |
February | 1994.87 | 14-FEB-09:01 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.96 |
March | 2039.51 | 11-MAR-09:01 | 540.00 | 321.46 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.98 |
April | 2012.00 | 20-APR-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 |
May | 2272.14 | 04-MAY-08:11 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 |
June | 2099.53 | 27-JUN-08:61 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 0.00 |
July | 2122.18 | 01-JUL-08:61 | 540.00 | 321.46 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 0.00 |
August | 2093.54 | 19-AUG-08:61 | 540.00 | 321.46 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.31 |
September | 2074.27 | 07-SEP-08:61 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 |
October | 2055.01 | 11-OCT-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 | 0.00 |
November | 2030.47 | 07-NOV-09:01 | 360.00 | 602.74 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.44 |
December | 1991.32 | 03-DEC-09:01 | 540.00 | 321.46 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.12 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1991.32 | 360.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2272.14 | 972.00 | 602.74 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 134.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1967.47 | 20-JAN-09:01 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.13 |
February | 1939.16 | 14-FEB-09:01 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.13 |
March | 2012.43 | 15-MAR-08:61 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.40 |
April | 1959.53 | 21-APR-15:11 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.21 |
May | 2248.00 | 13-MAY-08:11 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.46 |
June | 2643.57 | 07-JUN-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.40 |
July | 2779.40 | 01-JUL-08:11 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.26 |
August | 2556.45 | 06-AUG-08:11 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 |
September | 2414.81 | 07-SEP-08:11 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.37 |
October | 2115.43 | 11-OCT-08:11 | 288.00 | 482.14 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.04 |
November | 1985.97 | 07-NOV-09:01 | 360.00 | 602.67 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.76 |
December | 1934.97 | 03-DEC-09:01 | 540.00 | 321.43 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.16 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1934.97 | 288.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.40 | |
Maximum of Months | 2779.40 | 972.00 | 602.67 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1719.67 | 20-JAN-13:14 | 0.00 | 2096.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 |
February | 1687.21 | 18-FEB-13:59 | 0.00 | 1630.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.78 |
March | 1830.84 | 14-MAR-14:40 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 0.00 |
April | 1684.27 | 07-APR-14:20 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 |
May | 1782.02 | 18-MAY-14:03 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.84 | 0.00 |
June | 1948.99 | 29-JUN-19:54 | 0.00 | 4193.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 |
July | 2000.02 | 25-JUL-14:09 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.62 | 0.00 |
August | 1961.40 | 17-AUG-11:48 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 | 0.00 |
September | 1991.98 | 14-SEP-14:13 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
October | 1861.38 | 11-OCT-16:52 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 |
November | 1740.88 | 07-NOV-15:14 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
December | 1676.63 | 02-DEC-14:06 | 0.00 | 2329.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1676.63 | 0.00 | 1630.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2000.02 | 0.00 | 4193.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 | 12.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2456.80 | 21-JAN-16:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.60 |
February | 2480.26 | 17-FEB-16:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 |
March | 2546.55 | 13-MAR-15:11 | 874.80 | 99.19 | 450.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.98 |
April | 2968.71 | 06-APR-18:31 | 1386.00 | 1222.71 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.40 |
May | 2514.24 | 09-MAY-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.90 |
June | 2577.18 | 14-JUN-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 | 0.00 |
July | 2587.47 | 01-JUL-18:01 | 1170.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 0.00 |
August | 2684.28 | 26-AUG-16:46 | 954.00 | 142.07 | 1053.59 | 0.00 | 0.00 | 0.00 | 0.00 | 40.75 | 0.00 |
September | 2577.52 | 28-SEP-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 34.86 | 0.00 |
October | 2569.07 | 11-OCT-15:11 | 972.00 | 110.22 | 500.46 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 0.00 |
November | 2510.06 | 05-NOV-15:11 | 432.00 | 68.88 | 442.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 |
December | 2419.90 | 02-DEC-16:11 | 540.00 | 86.11 | 553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2419.90 | 432.00 | 68.88 | 442.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2968.71 | 1386.00 | 1377.70 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 | 77.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2486.99 | 23-JAN-16:51 | 972.00 | 110.20 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.33 |
February | 2468.38 | 26-FEB-17:11 | 954.00 | 142.06 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.78 |
March | 3073.32 | 31-MAR-18:01 | 1386.00 | 1222.56 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.74 |
April | 2986.81 | 08-APR-17:21 | 972.00 | 1170.91 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.31 |
May | 2722.43 | 09-MAY-19:51 | 1386.00 | 1377.54 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.73 |
June | 2764.59 | 08-JUN-21:11 | 1800.00 | 929.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.26 |
July | 2789.78 | 01-JUL-21:11 | 1386.00 | 1170.91 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.42 |
August | 2803.43 | 13-AUG-21:11 | 1386.00 | 1170.91 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.84 |
September | 2678.52 | 09-SEP-16:11 | 954.00 | 142.06 | 1053.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20.37 | 0.00 |
October | 2755.57 | 11-OCT-18:11 | 1386.00 | 1222.56 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.36 |
November | 2399.80 | 07-NOV-17:01 | 972.00 | 120.53 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.45 |
December | 2350.76 | 03-DEC-16:11 | 540.00 | 86.10 | 553.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2350.76 | 540.00 | 86.10 | 500.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3073.32 | 1800.00 | 1377.54 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 20.37 | 73.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1317.96 | 20-JAN-13:04 | 360.00 | 54.13 | 309.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.52 |
February | 1193.79 | 17-FEB-13:30 | 360.00 | 54.13 | 309.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 |
March | 1192.44 | 11-MAR-13:26 | 540.00 | 54.13 | 335.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.56 |
April | 1055.17 | 07-APR-15:12 | 583.20 | 41.57 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 |
May | 1085.23 | 04-MAY-15:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 0.00 |
June | 1092.81 | 07-JUN-15:11 | 972.00 | 69.29 | 490.32 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 | 0.00 |
July | 1075.70 | 03-JUL-18:01 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
August | 1088.29 | 20-AUG-15:11 | 540.00 | 54.13 | 541.93 | 0.00 | 0.00 | 0.00 | 0.00 | 13.48 | 0.00 |
September | 1148.82 | 27-SEP-12:10 | 360.00 | 54.13 | 309.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 | 0.00 |
October | 1198.71 | 10-OCT-15:13 | 874.80 | 62.36 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 0.00 |
November | 1279.44 | 05-NOV-12:18 | 540.00 | 54.13 | 335.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 |
December | 1290.08 | 17-DEC-13:20 | 540.00 | 54.13 | 335.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1055.17 | 360.00 | 41.57 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1317.96 | 1386.00 | 768.63 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 | 30.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27207.94 | 23-JAN-16:08 | 119950.08 | 3395.69 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.94 |
February | 28262.71 | 18-FEB-12:43 | 89962.56 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.81 |
March | 31409.26 | 13-MAR-15:43 | 149937.60 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.04 |
April | 31261.87 | 27-APR-15:17 | 149937.60 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.25 |
May | 31868.83 | 10-MAY-22:43 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.65 |
June | 34133.86 | 27-JUN-22:48 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.93 |
July | 34404.94 | 18-JUL-22:13 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.92 |
August | 34501.32 | 16-AUG-22:33 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.22 |
September | 32200.08 | 08-SEP-22:33 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.73 |
October | 30778.13 | 10-OCT-15:33 | 149937.60 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 0.00 |
November | 28534.95 | 05-NOV-09:53 | 149937.60 | 3855.53 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.43 |
December | 27229.05 | 14-DEC-22:51 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.70 |
Annual Sum or Average | |||||||||||
Minimum of Months | 27207.94 | 89962.56 | 3212.94 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34501.32 | 269887.68 | 12851.75 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 380.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29997.55 | 20-JAN-12:07 | 59975.04 | 3470.32 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.26 |
February | 30846.02 | 18-FEB-12:43 | 89962.56 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.87 |
March | 33758.29 | 13-MAR-15:43 | 149937.60 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 |
April | 33805.41 | 27-APR-15:17 | 149937.60 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.21 |
May | 34246.77 | 16-MAY-16:53 | 149937.60 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 |
June | 36507.66 | 26-JUN-22:08 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 |
July | 36672.80 | 18-JUL-22:13 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.60 |
August | 36777.85 | 16-AUG-22:33 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.92 |
September | 34396.42 | 08-SEP-22:33 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.64 |
October | 32939.63 | 10-OCT-15:33 | 149937.60 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
November | 31360.01 | 05-NOV-09:53 | 149937.60 | 3855.53 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.73 |
December | 31311.91 | 02-DEC-12:43 | 89962.56 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.45 |
Annual Sum or Average | |||||||||||
Minimum of Months | 29997.55 | 59975.04 | 3212.94 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 | |
Maximum of Months | 36777.85 | 269887.68 | 6425.88 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 42662.05 | 19-JAN-12:51 | 5337.12 | 3030.09 | 146045.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 170.87 |
February | 45512.74 | 26-FEB-11:51 | 8005.68 | 3636.11 | 146045.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 183.05 |
March | 44902.45 | 31-MAR-16:41 | 13342.80 | 3030.09 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 149.18 |
April | 45072.84 | 19-APR-17:52 | 13342.80 | 7272.22 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 184.07 |
May | 48478.32 | 16-MAY-16:41 | 13342.80 | 3030.09 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 79.60 |
June | 49937.68 | 30-JUN-16:51 | 13342.80 | 3030.09 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 4.93 | 0.00 |
July | 50000.82 | 07-JUL-17:31 | 13342.80 | 7272.22 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 71.97 |
August | 49384.02 | 26-AUG-16:51 | 13342.80 | 3030.09 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 |
September | 49125.94 | 06-SEP-17:31 | 13342.80 | 7272.22 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 68.78 |
October | 45660.31 | 11-OCT-16:41 | 13342.80 | 3030.09 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 0.00 | 103.93 |
November | 44987.09 | 07-NOV-11:42 | 5337.12 | 3030.09 | 146045.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 163.93 |
December | 44577.84 | 14-DEC-19:01 | 18679.92 | 9696.29 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 363.23 |
Annual Sum or Average | |||||||||||
Minimum of Months | 42662.05 | 5337.12 | 3030.09 | 146045.56 | 149952.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50000.82 | 18679.92 | 9696.29 | 146045.56 | 224928.32 | 0.00 | 0.00 | 0.00 | 4.93 | 363.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8006.17 | 20-JAN-13:43 | 0.00 | 2219.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.99 |
February | 7871.02 | 18-FEB-13:08 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 |
March | 8239.38 | 14-MAR-13:23 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 |
April | 8031.25 | 12-APR-13:07 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.16 |
May | 8172.36 | 24-MAY-14:13 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 |
June | 8384.57 | 16-JUN-12:33 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 |
July | 8606.53 | 25-JUL-14:09 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
August | 8460.77 | 21-AUG-15:29 | 0.00 | 2219.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.78 |
September | 8443.08 | 01-SEP-12:53 | 0.00 | 2219.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.91 |
October | 8321.21 | 10-OCT-13:38 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 |
November | 8110.35 | 07-NOV-13:35 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 |
December | 7273.94 | 17-DEC-13:13 | 0.00 | 1972.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.27 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7273.94 | 0.00 | 1972.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8606.53 | 0.00 | 2465.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 74.27 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.398575E+12 | 250100.98 | 20-JAN-20:10 | 0.408220E+12 | 419051.15 | 05-JAN-19:19 |
February | 0.353817E+12 | 245412.12 | 27-FEB-20:10 | 0.380058E+12 | 360887.31 | 05-FEB-17:49 |
March | 0.393106E+12 | 274604.68 | 14-MAR-19:30 | 0.386140E+12 | 358456.06 | 04-MAR-17:49 |
April | 0.371256E+12 | 273458.32 | 19-APR-19:00 | 0.358933E+12 | 328998.75 | 02-APR-16:10 |
May | 0.415902E+12 | 300762.17 | 31-MAY-18:19 | 0.340452E+12 | 280483.36 | 03-MAY-17:49 |
June | 0.488602E+12 | 361118.72 | 26-JUN-19:30 | 0.321444E+12 | 279435.01 | 01-JUN-17:40 |
July | 0.515642E+12 | 350903.95 | 12-JUL-19:30 | 0.327705E+12 | 278658.08 | 03-JUL-17:00 |
August | 0.505621E+12 | 348705.94 | 11-AUG-19:40 | 0.326578E+12 | 278304.55 | 31-AUG-17:49 |
September | 0.462600E+12 | 343503.34 | 10-SEP-19:19 | 0.318014E+12 | 278708.68 | 29-SEP-17:40 |
October | 0.409624E+12 | 281270.62 | 10-OCT-19:00 | 0.358660E+12 | 364673.66 | 31-OCT-16:30 |
November | 0.387441E+12 | 251217.83 | 08-NOV-20:10 | 0.368757E+12 | 376805.38 | 29-NOV-17:30 |
December | 0.392495E+12 | 244372.25 | 04-DEC-20:10 | 0.447079E+12 | 459494.25 | 21-DEC-17:40 |
Annual Sum or Average | 0.509468E+13 | 0.434204E+13 | ||||
Minimum of Months | 0.353817E+12 | 244372.25 | 0.318014E+12 | 278304.55 | ||
Maximum of Months | 0.515642E+12 | 361118.72 | 0.447079E+12 | 459494.25 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.451089E+11 | 0.187679E+11 | 0.140003E+12 | 0.825502E+11 | 0.703543E+11 | 0.396119E+10 | 0.00 | 0.143334E+11 | 0.00 | 0.00 | 0.116826E+11 | 0.768691E+10 | 0.00 |
February | 0.406062E+11 | 0.158016E+11 | 0.126445E+12 | 0.745615E+11 | 0.618974E+11 | 0.355807E+10 | 0.00 | 0.957612E+10 | 0.00 | 0.00 | 0.106949E+11 | 0.694599E+10 | 0.00 |
March | 0.448193E+11 | 0.158714E+11 | 0.140067E+12 | 0.825526E+11 | 0.674685E+11 | 0.338127E+10 | 0.00 | 0.162845E+11 | 0.00 | 0.00 | 0.108487E+11 | 0.768709E+10 | 0.00 |
April | 0.430734E+11 | 0.137147E+11 | 0.135446E+12 | 0.798867E+11 | 0.623992E+11 | 0.305712E+10 | 0.00 | 0.120096E+11 | 0.00 | 0.00 | 0.102289E+11 | 0.744831E+10 | 0.00 |
May | 0.442920E+11 | 0.127446E+11 | 0.140035E+12 | 0.825510E+11 | 0.682436E+11 | 0.344379E+10 | 0.00 | 0.449498E+11 | 0.00 | 0.00 | 0.784397E+10 | 0.768908E+10 | 0.00 |
June | 0.427132E+11 | 0.115790E+11 | 0.135537E+12 | 0.798889E+11 | 0.721930E+11 | 0.432563E+10 | 0.00 | 0.126264E+12 | 0.00 | 0.00 | 0.469636E+10 | 0.744428E+10 | 0.00 |
July | 0.441013E+11 | 0.123049E+11 | 0.139944E+12 | 0.825485E+11 | 0.748359E+11 | 0.468544E+10 | 0.00 | 0.140730E+12 | 0.00 | 0.00 | 0.471976E+10 | 0.769932E+10 | 0.00 |
August | 0.444734E+11 | 0.135402E+11 | 0.140067E+12 | 0.825524E+11 | 0.761824E+11 | 0.458986E+10 | 0.00 | 0.128029E+12 | 0.00 | 0.00 | 0.441563E+10 | 0.769158E+10 | 0.00 |
September | 0.431622E+11 | 0.146430E+11 | 0.135446E+12 | 0.798868E+11 | 0.743852E+11 | 0.390846E+10 | 0.00 | 0.942527E+11 | 0.00 | 0.00 | 0.553407E+10 | 0.745256E+10 | 0.00 |
October | 0.449603E+11 | 0.168276E+11 | 0.140003E+12 | 0.825501E+11 | 0.719852E+11 | 0.338443E+10 | 0.00 | 0.279560E+11 | 0.00 | 0.00 | 0.101526E+11 | 0.768792E+10 | 0.00 |
November | 0.436326E+11 | 0.177349E+11 | 0.135531E+12 | 0.798880E+11 | 0.686934E+11 | 0.355580E+10 | 0.00 | 0.159817E+11 | 0.00 | 0.00 | 0.109968E+11 | 0.743202E+10 | 0.00 |
December | 0.450723E+11 | 0.191727E+11 | 0.139944E+12 | 0.825491E+11 | 0.678902E+11 | 0.387275E+10 | 0.00 | 0.106251E+11 | 0.00 | 0.00 | 0.115707E+11 | 0.769595E+10 | 0.00 |
Annual Sum or Average | 0.526015E+12 | 0.182702E+12 | 0.164847E+13 | 0.971966E+12 | 0.836528E+12 | 0.457238E+11 | 0.00 | 0.640991E+12 | 0.103385E+12 | 0.905610E+11 | |||
Minimum of Months | 0.406062E+11 | 0.115790E+11 | 0.126445E+12 | 0.745615E+11 | 0.618974E+11 | 0.305712E+10 | 0.00 | 0.957612E+10 | 0.00 | 0.00 | 0.441563E+10 | 0.694599E+10 | 0.00 |
Maximum of Months | 0.451089E+11 | 0.191727E+11 | 0.140067E+12 | 0.825526E+11 | 0.761824E+11 | 0.468544E+10 | 0.00 | 0.140730E+12 | 0.00 | 0.00 | 0.116826E+11 | 0.769932E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.610086E+11 | 0.00 | 0.195293E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.649013E+11 | 0.00 | 0.177953E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.381947E+11 | 0.00 | 0.195906E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.268948E+11 | 0.00 | 0.185083E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.279804E+10 | 0.00 | 0.185676E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 11380234.99 | 0.00 | 0.174318E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 10387674.11 | 0.00 | 0.175874E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 16828852.07 | 0.00 | 0.174523E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.782178E+09 | 0.00 | 0.170276E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.267358E+11 | 0.00 | 0.180006E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.422275E+11 | 0.00 | 0.179438E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.103796E+12 | 0.00 | 0.191463E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.367377E+12 | 0.218581E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 10387674.11 | 0.00 | 0.170276E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.103796E+12 | 0.00 | 0.195906E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 47387.53 | 02-JAN-20:10 | 11632.50 | 01-JAN-00:10 | 88863.15 | 02-JAN-07:10 | 62573.78 | 02-JAN-07:19 | 37961.96 | 20-JAN-16:19 | 2653.92 | 07-JAN-19:19 | 0.00 | 01-JAN-00:10 |
February | 47387.53 | 01-FEB-20:10 | 11632.50 | 01-FEB-00:10 | 88863.15 | 01-FEB-07:10 | 62573.78 | 01-FEB-07:19 | 39308.00 | 18-FEB-09:00 | 2698.26 | 12-FEB-09:09 | 0.00 | 01-FEB-00:10 |
March | 47387.53 | 01-MAR-20:10 | 11632.50 | 01-MAR-00:10 | 88863.15 | 01-MAR-07:10 | 62573.78 | 13-MAR-06:19 | 46228.13 | 14-MAR-20:19 | 2414.93 | 05-MAR-09:20 | 0.00 | 01-MAR-00:10 |
April | 47387.53 | 03-APR-19:10 | 11632.50 | 01-APR-00:10 | 88863.15 | 03-APR-06:10 | 62573.38 | 03-APR-06:19 | 43011.58 | 20-APR-20:30 | 2380.98 | 03-APR-20:30 | 0.00 | 01-APR-00:10 |
May | 47387.53 | 01-MAY-19:10 | 11632.50 | 01-MAY-00:10 | 88863.15 | 01-MAY-06:10 | 62572.59 | 19-MAY-06:19 | 48014.89 | 31-MAY-18:19 | 2796.56 | 31-MAY-18:19 | 0.00 | 01-MAY-00:10 |
June | 47387.53 | 01-JUN-19:19 | 11632.50 | 01-JUN-00:10 | 88863.15 | 01-JUN-06:10 | 62572.63 | 16-JUN-06:19 | 54510.39 | 14-JUN-20:49 | 3212.44 | 26-JUN-21:00 | 0.00 | 01-JUN-00:10 |
July | 47387.53 | 03-JUL-19:30 | 11632.50 | 01-JUL-00:10 | 88863.15 | 03-JUL-06:10 | 62572.64 | 28-JUL-06:19 | 50559.26 | 18-JUL-18:00 | 3205.79 | 18-JUL-18:49 | 0.00 | 01-JUL-00:10 |
August | 47387.53 | 01-AUG-19:10 | 11632.50 | 01-AUG-00:10 | 88863.15 | 01-AUG-06:10 | 62572.66 | 18-AUG-06:19 | 62000.46 | 16-AUG-21:00 | 3893.53 | 16-AUG-21:00 | 0.00 | 01-AUG-00:10 |
September | 47387.53 | 01-SEP-19:10 | 11632.50 | 01-SEP-00:10 | 88863.15 | 01-SEP-06:10 | 62573.13 | 19-SEP-06:19 | 48279.28 | 13-SEP-21:10 | 3138.24 | 12-SEP-18:19 | 0.00 | 01-SEP-00:10 |
October | 47387.53 | 02-OCT-19:10 | 11632.50 | 01-OCT-00:10 | 88863.15 | 02-OCT-06:10 | 62573.78 | 03-OCT-06:19 | 47900.43 | 10-OCT-20:10 | 2137.97 | 11-OCT-15:39 | 0.00 | 01-OCT-00:10 |
November | 47387.53 | 01-NOV-19:10 | 11632.50 | 01-NOV-00:10 | 88863.15 | 01-NOV-06:10 | 62573.78 | 01-NOV-06:19 | 39414.35 | 06-NOV-09:30 | 2608.34 | 29-NOV-10:39 | 0.00 | 01-NOV-00:10 |
December | 47387.53 | 01-DEC-20:10 | 11632.50 | 01-DEC-00:10 | 88863.15 | 01-DEC-07:10 | 62573.78 | 01-DEC-07:19 | 36785.76 | 17-DEC-10:00 | 2839.32 | 22-DEC-09:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 47387.53 | 11632.50 | 88863.15 | 62572.59 | 36785.76 | 2137.97 | 0.00 | |||||||
Maximum of Months | 47387.53 | 11632.50 | 88863.15 | 62573.78 | 62000.46 | 3893.53 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 59184.97 | 20-JAN-13:00 | 0.00 | 0.00 | 6004.29 | 01-JAN-00:10 | 4734.87 | 25-JAN-07:10 | 0.00 |
February | 53876.02 | 18-FEB-13:50 | 0.00 | 0.00 | 4880.77 | 01-FEB-00:10 | 4735.41 | 09-FEB-07:10 | 0.00 |
March | 66446.79 | 14-MAR-12:00 | 0.00 | 0.00 | 4880.77 | 01-MAR-00:10 | 4735.90 | 14-MAR-18:49 | 0.00 |
April | 43192.76 | 12-APR-12:00 | 0.00 | 0.00 | 4880.77 | 01-APR-00:10 | 4734.73 | 03-APR-06:30 | 0.00 |
May | 79369.69 | 31-MAY-15:30 | 0.00 | 0.00 | 5255.28 | 19-MAY-22:40 | 4735.73 | 18-MAY-06:19 | 0.00 |
June | 129012.21 | 26-JUN-18:10 | 0.00 | 0.00 | 5255.28 | 03-JUN-12:20 | 4736.76 | 15-JUN-06:10 | 0.00 |
July | 108385.01 | 16-JUL-15:20 | 0.00 | 0.00 | 5554.88 | 22-JUL-08:00 | 4736.43 | 31-JUL-06:30 | 0.00 |
August | 116894.24 | 16-AUG-15:20 | 0.00 | 0.00 | 8251.33 | 10-AUG-04:10 | 4736.57 | 28-AUG-06:10 | 0.00 |
September | 96882.64 | 10-SEP-15:00 | 0.00 | 0.00 | 8251.33 | 05-SEP-02:09 | 4736.97 | 14-SEP-06:30 | 0.00 |
October | 75992.37 | 10-OCT-15:39 | 0.00 | 0.00 | 5255.28 | 03-OCT-22:40 | 4735.23 | 25-OCT-06:10 | 0.00 |
November | 62933.41 | 05-NOV-12:00 | 0.00 | 0.00 | 4880.77 | 01-NOV-00:10 | 4735.55 | 30-NOV-07:10 | 0.00 |
December | 58920.18 | 02-DEC-14:50 | 0.00 | 0.00 | 5255.28 | 14-DEC-23:40 | 4735.71 | 21-DEC-07:00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 43192.76 | 0.00 | 0.00 | 4880.77 | 4734.73 | 0.00 | |||
Maximum of Months | 129012.21 | 0.00 | 0.00 | 8251.33 | 4736.97 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 250100.98 | 20-JAN-20:10 | 47387.53 | 86131.51 | 11632.50 | 50262.95 | 30078.16 | 1237.46 | 0.00 | 12884.15 | 0.00 |
February | 245412.12 | 27-FEB-20:10 | 47387.53 | 86131.51 | 11632.50 | 50262.95 | 29130.97 | 1671.12 | 0.00 | 8303.25 | 0.00 |
March | 274604.68 | 14-MAR-19:30 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 40446.95 | 1306.37 | 0.00 | 32435.18 | 0.00 |
April | 273458.32 | 19-APR-19:00 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 39735.85 | 1289.13 | 0.00 | 31270.39 | 0.00 |
May | 300762.17 | 31-MAY-18:19 | 39311.23 | 77265.07 | 0.00 | 50070.88 | 48014.89 | 2796.56 | 0.00 | 75259.56 | 0.00 |
June | 361118.72 | 26-JUN-19:30 | 47387.53 | 86131.51 | 11632.50 | 50266.51 | 38378.65 | 2503.25 | 0.00 | 114113.23 | 0.00 |
July | 350903.95 | 12-JUL-19:30 | 47387.53 | 86131.51 | 11632.50 | 50266.54 | 47134.15 | 2841.63 | 0.00 | 95448.64 | 0.00 |
August | 348705.94 | 11-AUG-19:40 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 47141.73 | 2785.22 | 0.00 | 94632.15 | 0.00 |
September | 343503.34 | 10-SEP-19:19 | 43946.87 | 84670.41 | 11632.50 | 50231.18 | 47300.92 | 2922.97 | 0.00 | 94229.47 | 0.00 |
October | 281270.62 | 10-OCT-19:00 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 43474.46 | 1393.59 | 0.00 | 35958.51 | 0.00 |
November | 251217.83 | 08-NOV-20:10 | 47387.53 | 86131.51 | 11632.50 | 50262.95 | 30464.20 | 1235.92 | 0.00 | 13227.99 | 0.00 |
December | 244372.25 | 04-DEC-20:10 | 47387.53 | 86131.51 | 11632.50 | 50262.95 | 28561.00 | 1256.18 | 0.00 | 8318.71 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 244372.25 | 39311.23 | 77265.07 | 0.00 | 50070.88 | 28561.00 | 1235.92 | 0.00 | 8303.25 | 0.00 | |
Maximum of Months | 361118.72 | 47387.53 | 86131.51 | 11632.50 | 50267.24 | 48014.89 | 2922.97 | 0.00 | 114113.23 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 160701.24 | 05-JAN-09:09 | 0.00 | 178415.29 | 31-JAN-21:49 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 156643.42 | 12-FEB-07:19 | 0.00 | 178470.72 | 13-FEB-21:49 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 125426.37 | 19-MAR-06:40 | 0.00 | 178393.48 | 01-MAR-21:49 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 84569.04 | 02-APR-15:20 | 0.00 | 177797.19 | 03-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 21476.90 | 01-MAY-03:39 | 0.00 | 176969.10 | 01-MAY-20:30 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 2024.34 | 03-JUN-05:40 | 0.00 | 175968.89 | 01-JUN-20:40 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 1187.70 | 29-JUL-05:10 | 0.00 | 175131.60 | 03-JUL-20:00 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 1646.19 | 30-AUG-08:20 | 0.00 | 174745.76 | 31-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 17747.54 | 22-SEP-04:00 | 0.00 | 175187.02 | 29-SEP-20:19 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 125680.24 | 31-OCT-15:39 | 0.00 | 176045.14 | 31-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 121625.95 | 29-NOV-23:00 | 0.00 | 177012.62 | 30-NOV-21:40 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 198710.44 | 21-DEC-17:40 | 0.00 | 177857.67 | 29-DEC-21:19 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 1187.70 | 0.00 | 174745.76 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 198710.44 | 0.00 | 178470.72 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 623.17 | 25.08 | 623.17 | 25.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 449.33 | 24.89 | 449.33 | 24.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 192.33 | 24.80 | 192.33 | 24.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 153.00 | 24.78 | 153.00 | 24.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 | 24.77 | 60.67 | 24.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.78 | 1.67 | 24.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 24.80 | 7.00 | 24.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 24.72 | 27.17 | 24.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 259.00 | 25.08 | 259.00 | 25.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 709.00 | 25.87 | 709.00 | 25.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 719.33 | 26.26 | 719.33 | 26.26 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 743.83 | 25.96 | 743.83 | 25.96 |
Annual Sum or Average | 0.00 | 0.00 | 3945.50 | 25.55 | 3945.50 | 25.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.72 | 1.67 | 24.72 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.83 | 26.26 | 743.83 | 26.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 20.17 | 2.67 | 20.17 | 197.83 | 26.55 | 197.83 | 26.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 157.50 | 26.39 | 157.50 | 26.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 127.00 | 25.74 | 127.00 | 25.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 24.87 | 15.50 | 24.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 24.71 | 6.50 | 24.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 132.83 | 25.10 | 132.83 | 25.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 163.50 | 25.18 | 163.50 | 25.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 177.83 | 25.41 | 177.83 | 25.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 174.17 | 25.78 | 174.17 | 25.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 201.67 | 25.96 | 201.67 | 25.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 205.17 | 26.50 | 205.17 | 26.50 |
December | 55.83 | 19.64 | 55.83 | 19.64 | 134.67 | 26.68 | 134.67 | 26.68 |
Annual Sum or Average | 58.50 | 19.67 | 58.50 | 19.67 | 1694.17 | 25.94 | 1694.17 | 25.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 24.71 | 6.50 | 24.71 |
Maximum of Months | 55.83 | 20.17 | 55.83 | 20.17 | 205.17 | 26.68 | 205.17 | 26.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 318.33 | 25.05 | 318.33 | 25.05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 249.67 | 25.04 | 249.67 | 25.04 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 231.00 | 25.10 | 231.00 | 25.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 177.50 | 24.96 | 177.50 | 24.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 278.00 | 24.88 | 278.00 | 24.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 121.17 | 24.88 | 121.17 | 24.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 115.83 | 24.94 | 115.83 | 24.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 113.67 | 24.90 | 113.67 | 24.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 201.17 | 24.88 | 201.17 | 24.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 375.00 | 25.13 | 375.00 | 25.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 362.67 | 25.15 | 362.67 | 25.15 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 240.00 | 25.02 | 240.00 | 25.02 |
Annual Sum or Average | 0.00 | 0.00 | 2784.00 | 25.02 | 2784.00 | 25.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 113.67 | 24.88 | 113.67 | 24.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 375.00 | 25.15 | 375.00 | 25.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 24.66 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 24.62 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 24.72 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 24.65 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 24.73 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 24.84 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 24.86 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 24.84 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 24.64 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 24.73 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 24.76 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.64 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 261.50 | 24.75 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.62 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 24.86 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 24.71 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 24.74 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.81 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 33.33 | 24.74 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 24.81 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 670.50 | 27.24 | 670.50 | 27.24 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 600.17 | 27.24 | 600.17 | 27.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 665.50 | 27.17 | 665.50 | 27.17 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 649.83 | 27.04 | 649.83 | 27.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 667.83 | 26.61 | 667.83 | 26.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 680.50 | 25.89 | 680.50 | 25.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 718.50 | 25.88 | 718.50 | 25.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 715.83 | 25.87 | 715.83 | 25.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 665.67 | 26.05 | 665.67 | 26.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 669.50 | 27.13 | 669.50 | 27.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 650.67 | 27.28 | 650.67 | 27.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 662.67 | 27.17 | 662.67 | 27.17 |
Annual Sum or Average | 0.00 | 0.00 | 8017.17 | 26.70 | 8017.17 | 26.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 600.17 | 25.87 | 600.17 | 25.87 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 718.50 | 27.28 | 718.50 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 426.00 | 25.93 | 426.00 | 25.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 353.17 | 25.88 | 353.17 | 25.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 318.67 | 25.49 | 318.67 | 25.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 182.50 | 25.01 | 182.50 | 25.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 249.33 | 24.98 | 249.33 | 24.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 221.67 | 24.99 | 221.67 | 24.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 226.83 | 25.07 | 226.83 | 25.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 275.83 | 25.12 | 275.83 | 25.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 346.83 | 25.31 | 346.83 | 25.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 443.50 | 25.63 | 443.50 | 25.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 440.67 | 25.96 | 440.67 | 25.96 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 330.67 | 25.87 | 330.67 | 25.87 |
Annual Sum or Average | 0.00 | 0.00 | 3815.67 | 25.52 | 3815.67 | 25.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 182.50 | 24.98 | 182.50 | 24.98 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 443.50 | 25.96 | 443.50 | 25.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 530.33 | 25.27 | 530.33 | 25.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 419.17 | 25.25 | 419.17 | 25.25 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 390.67 | 25.26 | 390.67 | 25.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 326.17 | 25.19 | 326.17 | 25.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 382.17 | 25.24 | 382.17 | 25.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 215.83 | 24.95 | 215.83 | 24.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 198.00 | 24.98 | 198.00 | 24.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 217.50 | 24.92 | 217.50 | 24.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 291.50 | 25.12 | 291.50 | 25.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 481.83 | 25.41 | 481.83 | 25.41 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 534.50 | 25.40 | 534.50 | 25.40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 435.50 | 25.24 | 435.50 | 25.24 |
Annual Sum or Average | 0.00 | 0.00 | 4423.17 | 25.23 | 4423.17 | 25.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 198.00 | 24.92 | 198.00 | 24.92 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 534.50 | 25.41 | 534.50 | 25.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.81 | 0.17 | 21.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.10 | 0.17 | 22.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.84 | 1.00 | 21.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.86 | 0.33 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.93 | 1.17 | 21.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 22.19 | 33.50 | 22.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 22.11 | 20.83 | 22.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 22.31 | 25.50 | 22.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 22.13 | 11.00 | 22.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 21.82 | 3.00 | 21.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.83 | 0.33 | 21.83 |
December | 0.67 | 20.46 | 0.67 | 20.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 20.46 | 0.67 | 20.46 | 97.00 | 22.18 | 97.00 | 22.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.46 | 0.67 | 20.46 | 33.50 | 22.31 | 33.50 | 22.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.87 | 1.17 | 21.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.54 | 0.50 | 22.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.94 | 0.67 | 21.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 22.20 | 35.67 | 22.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 22.14 | 22.83 | 22.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 22.27 | 24.17 | 22.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.14 | 6.17 | 22.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.33 | 20.44 | 1.33 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 20.44 | 1.33 | 20.44 | 91.33 | 22.19 | 91.33 | 22.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.44 | 1.33 | 20.44 | 35.67 | 22.54 | 35.67 | 22.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.46 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.43 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.29 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 15.83 | 27.40 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.46 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.33 | 0.33 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.44 | 0.67 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.86 | 5.50 | 21.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 41.17 | 21.97 | 41.17 | 21.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 | 21.99 | 34.83 | 21.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 21.96 | 21.33 | 21.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 21.91 | 10.83 | 21.91 |
October | 0.17 | 20.38 | 0.17 | 20.38 | 0.33 | 21.77 | 0.33 | 21.77 |
November | 0.17 | 20.44 | 0.17 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.24 | 2.00 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.33 | 20.31 | 3.33 | 20.31 | 114.00 | 21.96 | 114.00 | 21.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.44 | 2.00 | 20.44 | 41.17 | 21.99 | 41.17 | 21.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.81 | 0.50 | 21.81 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22.01 | 2.17 | 22.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.79 | 2.33 | 21.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 21.94 | 4.67 | 21.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.03 | 4.00 | 22.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 22.08 | 26.33 | 22.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 22.13 | 30.83 | 22.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 22.03 | 22.67 | 22.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 21.99 | 14.17 | 21.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 21.81 | 2.00 | 21.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.77 | 1.00 | 21.77 |
December | 1.00 | 20.38 | 1.00 | 20.38 | 0.33 | 21.72 | 0.33 | 21.72 |
Annual Sum or Average | 1.00 | 20.38 | 1.00 | 20.38 | 111.00 | 22.05 | 111.00 | 22.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
Maximum of Months | 1.00 | 20.38 | 1.00 | 20.38 | 30.83 | 22.13 | 30.83 | 22.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.48 | 0.33 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.86 | 0.50 | 21.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.73 | 1.00 | 21.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 21.93 | 3.50 | 21.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 22.32 | 5.50 | 22.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 22.43 | 42.17 | 22.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 22.48 | 44.50 | 22.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 22.51 | 31.50 | 22.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 22.31 | 14.00 | 22.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.80 | 1.00 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.33 | 2.00 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 20.35 | 2.33 | 20.35 | 143.67 | 22.42 | 143.67 | 22.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.48 | 2.00 | 20.48 | 44.50 | 22.51 | 44.50 | 22.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.33 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87.83 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26.17 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30.50 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 153.67 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.50 | 20.02 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 153.67 | 20.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.87 | 0.17 | 21.87 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.87 | 0.50 | 21.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.85 | 2.17 | 21.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.23 | 0.33 | 22.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.90 | 5.33 | 21.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 22.41 | 46.67 | 22.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 22.24 | 26.83 | 22.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 22.60 | 32.50 | 22.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 22.25 | 14.17 | 22.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 21.90 | 4.00 | 21.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.82 | 0.67 | 21.82 |
December | 0.83 | 20.43 | 0.83 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.43 | 0.83 | 20.43 | 133.33 | 22.35 | 133.33 | 22.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.43 | 0.83 | 20.43 | 46.67 | 22.60 | 46.67 | 22.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.50 | 1.33 | 22.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.40 | 1.00 | 22.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.94 | 4.33 | 21.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 22.48 | 46.17 | 22.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 22.26 | 30.67 | 22.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 22.54 | 31.50 | 22.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 22.21 | 9.00 | 22.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.10 | 0.17 | 22.10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 20.40 | 1.50 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 20.40 | 1.50 | 20.40 | 124.17 | 22.40 | 124.17 | 22.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.40 | 1.50 | 20.40 | 46.17 | 22.54 | 46.17 | 22.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 23.50 | 65.00 | 23.50 |
February | 0.33 | 20.52 | 0.33 | 20.52 | 26.00 | 23.37 | 26.00 | 23.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 22.61 | 8.50 | 22.61 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 21.92 | 3.33 | 21.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 21.99 | 25.67 | 21.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 21.94 | 22.17 | 21.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 22.07 | 26.83 | 22.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 22.07 | 33.50 | 22.07 |
October | 0.17 | 20.48 | 0.17 | 20.48 | 34.67 | 23.30 | 34.67 | 23.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 64.17 | 23.52 | 64.17 | 23.52 |
December | 0.67 | 20.33 | 0.67 | 20.33 | 53.50 | 23.68 | 53.50 | 23.68 |
Annual Sum or Average | 1.17 | 20.41 | 1.17 | 20.41 | 363.83 | 23.03 | 363.83 | 23.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
Maximum of Months | 0.67 | 20.52 | 0.67 | 20.52 | 65.00 | 23.68 | 65.00 | 23.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 595.67 | 25.72 | 595.67 | 25.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 538.00 | 25.73 | 538.00 | 25.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 615.50 | 25.87 | 615.50 | 25.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 618.67 | 25.93 | 618.67 | 25.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 605.17 | 26.00 | 605.17 | 26.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 599.83 | 25.46 | 599.83 | 25.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 630.33 | 25.41 | 630.33 | 25.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 593.67 | 25.38 | 593.67 | 25.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 531.83 | 25.55 | 531.83 | 25.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 592.00 | 26.01 | 592.00 | 26.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 604.33 | 25.85 | 604.33 | 25.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 521.00 | 25.68 | 521.00 | 25.68 |
Annual Sum or Average | 0.00 | 0.00 | 7046.00 | 25.72 | 7046.00 | 25.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 521.00 | 25.38 | 521.00 | 25.38 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 630.33 | 26.01 | 630.33 | 26.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 695.83 | 26.05 | 695.83 | 26.05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 639.33 | 26.05 | 639.33 | 26.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 701.00 | 26.20 | 701.00 | 26.20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 685.50 | 26.27 | 685.50 | 26.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 686.33 | 26.18 | 686.33 | 26.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 657.33 | 25.65 | 657.33 | 25.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 681.83 | 25.61 | 681.83 | 25.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 658.17 | 25.55 | 658.17 | 25.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 601.67 | 25.69 | 601.67 | 25.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 652.67 | 26.29 | 652.67 | 26.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 663.67 | 26.22 | 663.67 | 26.22 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 643.83 | 25.97 | 643.83 | 25.97 |
Annual Sum or Average | 0.00 | 0.00 | 7967.17 | 25.98 | 7967.17 | 25.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 601.67 | 25.55 | 601.67 | 25.55 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 701.00 | 26.29 | 701.00 | 26.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 736.00 | 29.86 | 736.00 | 29.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 666.83 | 29.91 | 666.83 | 29.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 743.67 | 29.78 | 743.67 | 29.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 29.78 | 720.00 | 29.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.23 | 744.00 | 29.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 719.50 | 28.66 | 719.50 | 28.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 742.83 | 28.64 | 742.83 | 28.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 742.50 | 28.55 | 742.50 | 28.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 718.83 | 28.49 | 718.83 | 28.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 743.67 | 29.55 | 743.67 | 29.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 718.17 | 29.84 | 718.17 | 29.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 724.17 | 29.65 | 724.17 | 29.65 |
Annual Sum or Average | 0.00 | 0.00 | 8720.17 | 29.32 | 8720.17 | 29.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 666.83 | 28.49 | 666.83 | 28.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.91 | 744.00 | 29.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.59 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 24.71 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 24.67 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.59 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 24.83 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 193.67 | 25.06 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 216.83 | 25.07 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 184.67 | 25.08 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 112.50 | 24.96 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 24.73 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 24.77 | 0.00 | 0.00 |
December | 36.67 | 20.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.67 | 20.00 | 0.00 | 776.67 | 25.02 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.67 | 20.00 | 0.00 | 0.00 | 216.83 | 25.08 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.83 | 24.13 | 454.83 | 25.18 | 0.00 | 0.00 |
February | 92.50 | 24.19 | 246.83 | 25.01 | 0.00 | 0.00 |
March | 262.17 | 24.08 | 72.50 | 24.79 | 0.00 | 0.00 |
April | 208.17 | 24.05 | 127.67 | 24.64 | 0.00 | 0.00 |
May | 258.00 | 24.01 | 129.00 | 24.42 | 0.17 | 24.08 |
June | 203.83 | 24.02 | 216.33 | 24.06 | 38.83 | 24.04 |
July | 200.83 | 24.04 | 291.17 | 24.07 | 88.50 | 24.06 |
August | 135.17 | 24.08 | 364.83 | 24.17 | 55.83 | 24.15 |
September | 14.33 | 24.08 | 280.00 | 24.90 | 0.00 | 0.00 |
October | 1.33 | 26.98 | 655.33 | 25.95 | 1.33 | 26.98 |
November | 2.67 | 27.04 | 693.50 | 26.30 | 2.67 | 27.04 |
December | 0.00 | 0.00 | 717.83 | 25.99 | 0.00 | 0.00 |
Annual Sum or Average | 1435.83 | 24.07 | 4249.83 | 25.32 | 187.33 | 24.15 |
Minimum of Months | 0.00 | 0.00 | 72.50 | 24.06 | 0.00 | 0.00 |
Maximum of Months | 262.17 | 27.04 | 717.83 | 26.30 | 88.50 | 27.04 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 513.33 | 23.46 | 244.83 | 25.57 | 134.50 | 25.74 |
February | 468.17 | 22.92 | 250.33 | 24.44 | 156.17 | 23.85 |
March | 529.50 | 22.57 | 136.00 | 24.83 | 63.83 | 24.19 |
April | 544.33 | 22.37 | 58.50 | 22.71 | 30.17 | 20.98 |
May | 265.00 | 23.39 | 145.83 | 24.09 | 8.83 | 23.89 |
June | 67.67 | 23.97 | 514.50 | 24.36 | 57.50 | 23.98 |
July | 116.00 | 24.01 | 552.67 | 24.42 | 105.83 | 24.01 |
August | 97.17 | 24.25 | 601.83 | 24.48 | 91.00 | 24.27 |
September | 122.83 | 24.66 | 355.83 | 24.94 | 41.33 | 26.92 |
October | 415.00 | 23.32 | 246.67 | 25.04 | 121.50 | 24.92 |
November | 439.83 | 23.58 | 264.00 | 25.57 | 132.33 | 25.97 |
December | 577.50 | 22.76 | 236.00 | 23.83 | 174.17 | 23.23 |
Annual Sum or Average | 4156.33 | 23.12 | 3607.00 | 24.61 | 1117.17 | 24.46 |
Minimum of Months | 67.67 | 22.37 | 58.50 | 22.71 | 8.83 | 20.98 |
Maximum of Months | 577.50 | 24.66 | 601.83 | 25.57 | 174.17 | 26.92 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 173.33 | 23.84 | 299.33 | 25.02 | 0.00 | 0.00 |
February | 233.67 | 23.70 | 219.17 | 25.05 | 0.00 | 0.00 |
March | 252.67 | 23.82 | 191.83 | 25.13 | 0.00 | 0.00 |
April | 259.17 | 23.84 | 211.50 | 24.83 | 0.00 | 0.00 |
May | 79.17 | 24.04 | 364.67 | 24.73 | 5.83 | 24.63 |
June | 53.00 | 24.25 | 499.67 | 24.35 | 53.00 | 24.25 |
July | 103.83 | 24.18 | 524.67 | 24.34 | 103.83 | 24.18 |
August | 84.00 | 24.20 | 549.83 | 24.33 | 79.00 | 24.22 |
September | 15.67 | 24.12 | 365.50 | 24.56 | 2.50 | 24.79 |
October | 90.83 | 23.62 | 359.00 | 25.10 | 0.00 | 0.00 |
November | 107.33 | 23.78 | 366.00 | 25.12 | 0.00 | 0.00 |
December | 340.83 | 23.65 | 175.50 | 25.13 | 0.00 | 0.00 |
Annual Sum or Average | 1793.50 | 23.83 | 4126.67 | 24.71 | 244.17 | 24.22 |
Minimum of Months | 15.67 | 23.62 | 175.50 | 24.33 | 0.00 | 0.00 |
Maximum of Months | 340.83 | 24.25 | 549.83 | 25.13 | 103.83 | 24.79 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 598.50 | 27.54 | 744.00 | 26.96 | 598.50 | 27.54 |
February | 528.33 | 27.59 | 672.00 | 26.95 | 528.33 | 27.59 |
March | 573.33 | 27.55 | 744.00 | 26.88 | 573.33 | 27.55 |
April | 582.33 | 27.30 | 720.00 | 26.79 | 582.33 | 27.30 |
May | 660.50 | 26.62 | 744.00 | 26.39 | 660.50 | 26.62 |
June | 689.17 | 25.86 | 720.00 | 25.81 | 689.17 | 25.86 |
July | 723.83 | 25.86 | 744.00 | 25.83 | 723.83 | 25.86 |
August | 724.17 | 25.85 | 744.00 | 25.82 | 724.17 | 25.85 |
September | 646.33 | 26.08 | 720.00 | 25.93 | 646.33 | 26.08 |
October | 609.33 | 27.37 | 744.00 | 26.87 | 609.33 | 27.37 |
November | 602.33 | 27.49 | 720.00 | 27.01 | 602.33 | 27.49 |
December | 544.17 | 27.70 | 744.00 | 26.87 | 544.17 | 27.70 |
Annual Sum or Average | 7482.33 | 26.83 | 8760.00 | 26.51 | 7482.33 | 26.83 |
Minimum of Months | 528.33 | 25.85 | 672.00 | 25.81 | 528.33 | 25.85 |
Maximum of Months | 724.17 | 27.70 | 744.00 | 27.01 | 724.17 | 27.70 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 250.50 | 25.27 | 496.67 | 25.70 | 129.33 | 27.38 |
February | 290.83 | 24.41 | 410.17 | 25.54 | 116.67 | 26.56 |
March | 271.33 | 23.50 | 364.83 | 25.34 | 42.00 | 26.66 |
April | 250.17 | 23.12 | 290.67 | 24.70 | 13.00 | 25.07 |
May | 84.83 | 24.38 | 520.33 | 24.50 | 49.17 | 24.99 |
June | 159.00 | 24.34 | 691.17 | 24.40 | 158.50 | 24.35 |
July | 197.00 | 24.40 | 723.33 | 24.42 | 197.00 | 24.40 |
August | 198.83 | 24.48 | 715.17 | 24.52 | 198.83 | 24.48 |
September | 65.17 | 25.85 | 649.50 | 24.79 | 60.00 | 26.07 |
October | 233.33 | 24.26 | 539.67 | 25.36 | 100.17 | 26.35 |
November | 250.17 | 25.35 | 498.33 | 25.77 | 136.67 | 27.31 |
December | 336.50 | 24.10 | 370.17 | 25.54 | 108.33 | 26.47 |
Annual Sum or Average | 2587.67 | 24.35 | 6270.00 | 24.97 | 1309.67 | 25.69 |
Minimum of Months | 65.17 | 23.12 | 290.67 | 24.40 | 13.00 | 24.35 |
Maximum of Months | 336.50 | 25.85 | 723.33 | 25.77 | 198.83 | 27.38 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.33 | 23.75 | 533.33 | 25.26 | 0.00 | 0.00 |
February | 99.17 | 23.69 | 419.67 | 25.23 | 0.00 | 0.00 |
March | 75.67 | 23.75 | 400.67 | 25.20 | 0.00 | 0.00 |
April | 76.83 | 23.95 | 368.83 | 25.07 | 7.50 | 25.47 |
May | 52.83 | 25.09 | 508.33 | 24.97 | 41.17 | 25.39 |
June | 126.83 | 24.46 | 605.50 | 24.47 | 126.83 | 24.46 |
July | 170.17 | 24.37 | 664.50 | 24.44 | 170.17 | 24.37 |
August | 155.83 | 24.44 | 658.17 | 24.45 | 155.83 | 24.44 |
September | 6.33 | 25.29 | 563.17 | 24.69 | 6.33 | 25.29 |
October | 43.67 | 23.52 | 536.33 | 25.29 | 0.17 | 25.44 |
November | 33.83 | 24.10 | 556.83 | 25.35 | 4.50 | 25.88 |
December | 149.67 | 23.74 | 402.50 | 25.28 | 0.00 | 0.00 |
Annual Sum or Average | 1035.17 | 24.13 | 6217.83 | 24.93 | 512.50 | 24.54 |
Minimum of Months | 6.33 | 23.52 | 368.83 | 24.44 | 0.00 | 0.00 |
Maximum of Months | 170.17 | 25.29 | 664.50 | 25.35 | 170.17 | 25.88 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.00 | 21.31 | 136.17 | 20.66 | 136.17 | 20.66 |
February | 667.50 | 21.22 | 222.50 | 20.64 | 222.50 | 20.64 |
March | 738.33 | 21.23 | 150.00 | 20.33 | 150.00 | 20.33 |
April | 716.00 | 21.21 | 152.83 | 20.48 | 150.33 | 20.38 |
May | 731.50 | 21.61 | 11.50 | 21.53 | 9.67 | 21.24 |
June | 622.50 | 21.64 | 49.33 | 22.80 | 18.50 | 22.19 |
July | 639.17 | 21.60 | 79.50 | 22.04 | 65.50 | 21.81 |
August | 636.83 | 21.59 | 59.50 | 22.20 | 35.33 | 21.49 |
September | 655.00 | 21.62 | 10.83 | 22.89 | 1.17 | 20.51 |
October | 719.67 | 21.34 | 102.67 | 20.30 | 102.67 | 20.30 |
November | 709.50 | 21.32 | 122.67 | 20.52 | 122.67 | 20.52 |
December | 744.00 | 21.12 | 343.33 | 20.64 | 343.33 | 20.64 |
Annual Sum or Average | 8319.00 | 21.39 | 1440.83 | 20.80 | 1357.83 | 20.65 |
Minimum of Months | 622.50 | 21.12 | 10.83 | 20.30 | 1.17 | 20.30 |
Maximum of Months | 744.00 | 21.64 | 343.33 | 22.89 | 343.33 | 22.19 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.83 | 338.17 | 20.43 | 338.17 | 20.43 |
February | 672.00 | 20.83 | 360.33 | 20.48 | 360.33 | 20.48 |
March | 727.17 | 21.04 | 243.50 | 20.60 | 233.17 | 20.35 |
April | 708.83 | 21.11 | 175.17 | 20.58 | 167.33 | 20.32 |
May | 684.50 | 21.73 | 36.50 | 24.32 | 10.00 | 21.24 |
June | 547.50 | 22.01 | 130.17 | 24.46 | 44.17 | 24.35 |
July | 573.17 | 21.99 | 158.00 | 23.59 | 96.33 | 23.03 |
August | 588.33 | 22.00 | 109.67 | 23.97 | 50.67 | 23.46 |
September | 619.33 | 21.89 | 51.50 | 25.19 | 1.67 | 23.23 |
October | 718.33 | 21.20 | 132.33 | 20.73 | 121.50 | 20.29 |
November | 720.00 | 20.96 | 235.83 | 20.40 | 235.83 | 20.40 |
December | 744.00 | 20.75 | 539.17 | 20.55 | 539.17 | 20.55 |
Annual Sum or Average | 8047.17 | 21.32 | 2510.33 | 21.22 | 2198.33 | 20.71 |
Minimum of Months | 547.50 | 20.75 | 36.50 | 20.40 | 1.67 | 20.29 |
Maximum of Months | 744.00 | 22.01 | 539.17 | 25.19 | 539.17 | 24.35 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.97 | 112.17 | 20.26 | 112.17 | 20.26 |
February | 672.00 | 20.94 | 149.83 | 20.31 | 149.83 | 20.31 |
March | 744.00 | 21.17 | 33.67 | 20.22 | 33.67 | 20.22 |
April | 720.00 | 21.27 | 13.50 | 20.19 | 13.50 | 20.19 |
May | 743.83 | 21.78 | 1.00 | 22.33 | 1.00 | 22.33 |
June | 694.67 | 22.19 | 48.17 | 23.38 | 42.00 | 23.23 |
July | 719.33 | 22.22 | 80.17 | 23.14 | 75.33 | 23.06 |
August | 720.83 | 22.11 | 46.67 | 23.28 | 37.00 | 22.99 |
September | 716.83 | 21.97 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 21.27 | 29.50 | 19.97 | 29.50 | 19.97 |
November | 720.00 | 21.05 | 66.17 | 20.25 | 66.17 | 20.25 |
December | 744.00 | 20.90 | 229.50 | 20.43 | 229.50 | 20.43 |
Annual Sum or Average | 8683.50 | 21.49 | 810.33 | 20.95 | 789.67 | 20.86 |
Minimum of Months | 672.00 | 20.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.22 | 229.50 | 23.38 | 229.50 | 23.23 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 134.50 | 20.68 | 134.50 | 20.68 |
February | 669.00 | 21.29 | 233.67 | 20.68 | 233.67 | 20.68 |
March | 741.33 | 21.33 | 151.33 | 20.40 | 151.33 | 20.40 |
April | 714.17 | 21.32 | 144.17 | 20.47 | 143.33 | 20.45 |
May | 735.83 | 21.71 | 6.83 | 21.46 | 6.50 | 21.34 |
June | 587.50 | 21.55 | 22.67 | 22.72 | 7.33 | 21.82 |
July | 592.33 | 21.51 | 61.33 | 22.03 | 51.67 | 21.82 |
August | 589.83 | 21.49 | 30.83 | 22.28 | 13.00 | 21.12 |
September | 646.50 | 21.64 | 2.67 | 23.11 | 0.00 | 0.00 |
October | 730.00 | 21.41 | 99.00 | 20.31 | 98.67 | 20.31 |
November | 716.33 | 21.36 | 133.17 | 20.58 | 133.17 | 20.58 |
December | 744.00 | 21.15 | 350.17 | 20.67 | 350.17 | 20.67 |
Annual Sum or Average | 8210.83 | 21.42 | 1370.33 | 20.73 | 1323.33 | 20.64 |
Minimum of Months | 587.50 | 21.15 | 2.67 | 20.31 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.71 | 350.17 | 23.11 | 350.17 | 21.82 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.82 | 346.67 | 20.47 | 346.67 | 20.47 |
February | 672.00 | 20.88 | 340.50 | 20.51 | 340.50 | 20.51 |
March | 743.67 | 21.20 | 214.00 | 20.50 | 214.00 | 20.50 |
April | 715.00 | 21.26 | 162.67 | 20.46 | 161.83 | 20.44 |
May | 721.17 | 21.90 | 12.00 | 22.92 | 6.50 | 21.30 |
June | 471.00 | 21.91 | 120.33 | 24.73 | 43.83 | 24.74 |
July | 499.17 | 21.98 | 166.33 | 24.05 | 95.33 | 23.61 |
August | 537.83 | 22.00 | 105.83 | 24.33 | 44.33 | 24.18 |
September | 645.67 | 22.03 | 15.50 | 24.77 | 0.00 | 0.00 |
October | 741.67 | 21.32 | 119.33 | 20.35 | 119.33 | 20.35 |
November | 720.00 | 20.92 | 261.33 | 20.45 | 261.33 | 20.45 |
December | 744.00 | 20.72 | 544.50 | 20.57 | 544.50 | 20.57 |
Annual Sum or Average | 7955.17 | 21.36 | 2409.00 | 21.16 | 2178.17 | 20.79 |
Minimum of Months | 471.00 | 20.72 | 12.00 | 20.35 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.03 | 544.50 | 24.77 | 544.50 | 24.74 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.17 | 21.22 | 234.67 | 20.69 | 234.67 | 20.69 |
February | 663.67 | 21.16 | 281.17 | 20.67 | 281.17 | 20.67 |
March | 729.83 | 21.16 | 254.83 | 20.55 | 254.83 | 20.55 |
April | 709.83 | 21.18 | 202.50 | 20.49 | 200.67 | 20.44 |
May | 708.67 | 21.58 | 23.17 | 21.26 | 20.67 | 21.02 |
June | 555.17 | 21.50 | 88.67 | 22.78 | 24.17 | 21.63 |
July | 595.00 | 21.49 | 123.33 | 22.33 | 71.33 | 21.72 |
August | 576.50 | 21.44 | 107.17 | 22.43 | 47.17 | 21.38 |
September | 616.00 | 21.51 | 25.17 | 22.74 | 5.17 | 20.95 |
October | 707.17 | 21.26 | 146.50 | 20.40 | 143.67 | 20.35 |
November | 700.17 | 21.25 | 197.33 | 20.61 | 197.33 | 20.61 |
December | 740.67 | 21.04 | 442.17 | 20.65 | 442.17 | 20.65 |
Annual Sum or Average | 8034.83 | 21.31 | 2126.67 | 20.92 | 1923.00 | 20.67 |
Minimum of Months | 555.17 | 21.04 | 23.17 | 20.40 | 5.17 | 20.35 |
Maximum of Months | 740.67 | 21.58 | 442.17 | 22.78 | 442.17 | 21.72 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.75 | 470.50 | 20.48 | 470.50 | 20.48 |
February | 672.00 | 20.78 | 432.50 | 20.51 | 432.50 | 20.51 |
March | 725.67 | 21.02 | 361.17 | 20.75 | 349.17 | 20.55 |
April | 707.83 | 21.12 | 236.67 | 20.67 | 228.33 | 20.47 |
May | 642.83 | 21.70 | 80.33 | 24.18 | 30.00 | 22.17 |
June | 484.50 | 22.03 | 177.83 | 24.59 | 51.83 | 25.40 |
July | 528.50 | 21.96 | 207.83 | 23.70 | 103.33 | 23.32 |
August | 513.17 | 21.88 | 165.50 | 24.00 | 61.33 | 23.61 |
September | 575.33 | 21.81 | 85.33 | 25.02 | 13.67 | 24.11 |
October | 706.67 | 21.13 | 203.00 | 20.91 | 184.50 | 20.39 |
November | 719.00 | 20.90 | 362.17 | 20.50 | 362.17 | 20.50 |
December | 744.00 | 20.67 | 639.17 | 20.55 | 639.17 | 20.55 |
Annual Sum or Average | 7763.50 | 21.25 | 3422.00 | 21.35 | 2926.50 | 20.79 |
Minimum of Months | 484.50 | 20.67 | 80.33 | 20.48 | 13.67 | 20.39 |
Maximum of Months | 744.00 | 22.03 | 639.17 | 25.02 | 639.17 | 25.40 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 619.00 | 21.31 | 138.33 | 22.55 | 58.83 | 20.69 |
February | 578.17 | 21.22 | 160.50 | 21.34 | 121.33 | 20.55 |
March | 684.17 | 21.24 | 93.67 | 20.31 | 87.33 | 20.06 |
April | 709.67 | 21.31 | 102.00 | 20.42 | 102.00 | 20.42 |
May | 732.83 | 21.65 | 36.67 | 21.69 | 36.67 | 21.69 |
June | 623.33 | 21.60 | 36.83 | 21.99 | 34.83 | 21.92 |
July | 628.00 | 21.56 | 84.83 | 21.85 | 77.50 | 21.72 |
August | 604.50 | 21.49 | 69.33 | 22.29 | 41.33 | 21.59 |
September | 594.00 | 21.49 | 53.00 | 23.33 | 2.00 | 22.04 |
October | 633.50 | 21.19 | 147.00 | 21.73 | 84.83 | 20.26 |
November | 591.33 | 21.30 | 136.50 | 22.45 | 60.17 | 20.58 |
December | 661.00 | 21.31 | 190.00 | 21.68 | 139.83 | 20.78 |
Annual Sum or Average | 7659.50 | 21.39 | 1248.67 | 21.74 | 846.67 | 20.77 |
Minimum of Months | 578.17 | 21.19 | 36.67 | 20.31 | 2.00 | 20.06 |
Maximum of Months | 732.83 | 21.65 | 190.00 | 23.33 | 139.83 | 22.04 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.33 | 25.65 | 569.83 | 25.76 | 31.17 | 27.01 |
February | 57.33 | 25.22 | 502.83 | 25.80 | 21.67 | 27.11 |
March | 46.17 | 27.04 | 602.83 | 25.88 | 45.83 | 27.06 |
April | 105.00 | 26.89 | 654.17 | 25.83 | 104.17 | 26.91 |
May | 181.17 | 26.78 | 737.00 | 25.70 | 181.17 | 26.78 |
June | 220.17 | 25.59 | 720.00 | 25.27 | 220.17 | 25.59 |
July | 262.17 | 25.53 | 744.00 | 25.25 | 262.17 | 25.53 |
August | 249.67 | 25.43 | 743.33 | 25.17 | 249.67 | 25.43 |
September | 55.50 | 26.45 | 706.67 | 25.23 | 55.50 | 26.45 |
October | 103.83 | 26.50 | 642.67 | 25.87 | 89.83 | 26.88 |
November | 60.00 | 26.22 | 603.67 | 25.84 | 43.50 | 27.03 |
December | 112.67 | 24.15 | 463.33 | 25.79 | 5.67 | 27.15 |
Annual Sum or Average | 1511.00 | 25.83 | 7690.33 | 25.59 | 1310.50 | 26.11 |
Minimum of Months | 46.17 | 24.15 | 463.33 | 25.17 | 5.67 | 25.43 |
Maximum of Months | 262.17 | 27.04 | 744.00 | 25.88 | 262.17 | 27.15 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 152.50 | 26.91 | 702.33 | 26.03 | 145.83 | 27.03 |
February | 131.00 | 27.05 | 636.33 | 26.05 | 131.00 | 27.05 |
March | 201.50 | 27.11 | 735.00 | 26.12 | 201.50 | 27.11 |
April | 274.33 | 27.02 | 715.67 | 26.19 | 274.33 | 27.02 |
May | 347.50 | 26.90 | 744.00 | 26.05 | 347.50 | 26.90 |
June | 308.67 | 25.94 | 720.00 | 25.54 | 308.67 | 25.94 |
July | 334.50 | 25.85 | 744.00 | 25.51 | 334.50 | 25.85 |
August | 319.67 | 25.78 | 744.00 | 25.41 | 319.67 | 25.78 |
September | 136.33 | 26.67 | 719.83 | 25.47 | 136.33 | 26.67 |
October | 250.67 | 27.02 | 721.17 | 26.11 | 250.67 | 27.02 |
November | 189.33 | 27.04 | 685.83 | 26.15 | 189.33 | 27.04 |
December | 130.17 | 26.12 | 632.00 | 25.98 | 86.83 | 27.12 |
Annual Sum or Average | 2776.17 | 26.54 | 8500.17 | 25.88 | 2726.17 | 26.59 |
Minimum of Months | 130.17 | 25.78 | 632.00 | 25.41 | 86.83 | 25.78 |
Maximum of Months | 347.50 | 27.11 | 744.00 | 26.19 | 347.50 | 27.12 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 712.67 | 30.02 | 744.00 | 29.80 | 712.67 | 30.02 |
February | 640.00 | 30.11 | 672.00 | 29.87 | 640.00 | 30.11 |
March | 734.67 | 29.84 | 744.00 | 29.78 | 734.67 | 29.84 |
April | 710.67 | 29.84 | 720.00 | 29.78 | 710.67 | 29.84 |
May | 744.00 | 29.23 | 744.00 | 29.23 | 744.00 | 29.23 |
June | 719.67 | 28.66 | 720.00 | 28.66 | 719.67 | 28.66 |
July | 744.00 | 28.64 | 744.00 | 28.64 | 744.00 | 28.64 |
August | 743.00 | 28.55 | 744.00 | 28.54 | 743.00 | 28.55 |
September | 717.83 | 28.50 | 720.00 | 28.49 | 717.83 | 28.50 |
October | 738.33 | 29.58 | 744.00 | 29.54 | 738.33 | 29.58 |
November | 705.00 | 29.93 | 720.00 | 29.83 | 705.00 | 29.93 |
December | 698.00 | 29.83 | 744.00 | 29.51 | 698.00 | 29.83 |
Annual Sum or Average | 8607.83 | 29.38 | 8760.00 | 29.30 | 8607.83 | 29.38 |
Minimum of Months | 640.00 | 28.50 | 672.00 | 28.49 | 640.00 | 28.50 |
Maximum of Months | 744.00 | 30.11 | 744.00 | 29.87 | 744.00 | 30.11 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.94735 | 25.71532 | 0.44304 | 9.37876 |
February | 672.00000 | 24.70996 | 24.68285 | 0.37485 | 8.14900 |
March | 744.00000 | 24.37905 | 24.02800 | 0.28606 | 6.89308 |
April | 720.00000 | 24.36058 | 27.90034 | 0.31026 | 7.18451 |
May | 744.00000 | 24.19994 | 31.17517 | -0.6110 | 13.04030 |
June | 720.00000 | 24.05359 | 37.71097 | -0.6012 | 12.70032 |
July | 744.00000 | 24.06552 | 39.68369 | -0.5803 | 12.18404 |
August | 744.00000 | 24.13002 | 38.90533 | -0.5455 | 11.38344 |
September | 720.00000 | 24.51842 | 28.82798 | -0.4692 | 10.00682 |
October | 744.00000 | 25.80140 | 24.38563 | 0.66145 | 14.70390 |
November | 720.00000 | 26.25422 | 25.17751 | 0.77545 | 17.99575 |
December | 744.00000 | 25.95502 | 20.36788 | 0.66048 | 14.38949 |
Annual Sum or Average | 8760.00000 | 24.78167 | 29.07319 | 0.05671 | 11.52317 |
Minimum of Months | 672.00000 | 24.05359 | 20.36788 | -0.6110 | 6.89308 |
Maximum of Months | 744.00000 | 26.25422 | 39.68369 | 0.77545 | 17.99575 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.84463 | 26.98125 | 0.24307 | 12.22139 |
February | 672.00000 | 23.46385 | 25.89787 | 0.12308 | 11.80606 |
March | 744.00000 | 23.16275 | 25.71203 | 0.04563 | 9.11329 |
April | 720.00000 | 22.80087 | 30.51246 | -0.0315 | 7.17542 |
May | 744.00000 | 23.80706 | 32.11243 | -0.6611 | 15.17015 |
June | 720.00000 | 24.26738 | 36.55998 | -0.3941 | 8.89511 |
July | 744.00000 | 24.32494 | 38.52877 | -0.3567 | 8.53798 |
August | 744.00000 | 24.39153 | 38.25045 | -0.3347 | 8.51332 |
September | 720.00000 | 24.43683 | 28.82086 | -0.3810 | 10.87624 |
October | 744.00000 | 23.86428 | 26.84763 | 0.25307 | 11.08350 |
November | 720.00000 | 23.97600 | 27.89669 | 0.28702 | 12.72581 |
December | 744.00000 | 23.19127 | 22.66458 | 0.03457 | 12.23793 |
Annual Sum or Average | 8760.00000 | 23.79616 | 30.09000 | -0.0992 | 10.69576 |
Minimum of Months | 672.00000 | 22.80087 | 22.66458 | -0.6611 | 7.17542 |
Maximum of Months | 744.00000 | 24.43683 | 38.52877 | 0.28702 | 15.17015 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.49014 | 27.24940 | 0.36998 | 8.39137 |
February | 672.00000 | 24.35582 | 26.47535 | 0.32388 | 7.89729 |
March | 744.00000 | 24.34221 | 25.32040 | 0.31496 | 7.50000 |
April | 720.00000 | 24.25386 | 29.29651 | 0.31755 | 7.53036 |
May | 744.00000 | 24.41825 | 31.26872 | -0.4662 | 10.07314 |
June | 720.00000 | 24.29022 | 37.22776 | -0.4272 | 9.09787 |
July | 744.00000 | 24.28362 | 39.34030 | -0.4145 | 8.87916 |
August | 744.00000 | 24.28251 | 39.15139 | -0.4172 | 8.90692 |
September | 720.00000 | 24.37664 | 29.79743 | -0.4565 | 9.63194 |
October | 744.00000 | 24.59287 | 26.81184 | 0.40398 | 8.98038 |
November | 720.00000 | 24.62176 | 28.09741 | 0.41396 | 9.17414 |
December | 744.00000 | 24.23107 | 23.31124 | 0.27052 | 7.34251 |
Annual Sum or Average | 8760.00000 | 24.37835 | 30.30119 | 0.01757 | 8.62036 |
Minimum of Months | 672.00000 | 24.23107 | 23.31124 | -0.4662 | 7.34251 |
Maximum of Months | 744.00000 | 24.62176 | 39.34030 | 0.41396 | 10.07314 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 26.96264 | 19.50326 | 1.46939 | 46.09267 |
February | 672.00000 | 26.94701 | 18.31132 | 1.45159 | 45.38368 |
March | 744.00000 | 26.88501 | 17.42282 | 1.44669 | 45.12145 |
April | 720.00000 | 26.78804 | 20.90986 | 1.45334 | 45.61901 |
May | 744.00000 | 26.39443 | 23.83016 | 1.01415 | 30.38945 |
June | 720.00000 | 25.80971 | 30.17438 | 0.94018 | 27.75570 |
July | 744.00000 | 25.83225 | 32.06986 | 0.95372 | 27.93991 |
August | 744.00000 | 25.81981 | 31.92511 | 0.94438 | 27.88388 |
September | 720.00000 | 25.93002 | 23.28828 | 0.89417 | 26.43360 |
October | 744.00000 | 26.86862 | 19.34249 | 1.47840 | 46.49808 |
November | 720.00000 | 27.01237 | 20.36411 | 1.50021 | 47.29692 |
December | 744.00000 | 26.87349 | 15.50750 | 1.40679 | 43.74626 |
Annual Sum or Average | 8760.00000 | 26.50807 | 22.74645 | 1.24493 | 38.30609 |
Minimum of Months | 672.00000 | 25.80971 | 15.50750 | 0.89417 | 26.43360 |
Maximum of Months | 744.00000 | 27.01237 | 32.06986 | 1.50021 | 47.29692 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.98986 | 31.01131 | 0.58322 | 15.98483 |
February | 672.00000 | 24.68690 | 30.40828 | 0.48246 | 14.55397 |
March | 744.00000 | 24.35518 | 29.73093 | 0.38890 | 10.73783 |
April | 720.00000 | 23.98236 | 34.07582 | 0.30417 | 8.23440 |
May | 744.00000 | 24.32645 | 35.72651 | -0.4029 | 8.96312 |
June | 720.00000 | 24.38058 | 41.24571 | -0.2576 | 6.85878 |
July | 744.00000 | 24.41454 | 43.23662 | -0.2245 | 6.72409 |
August | 744.00000 | 24.49526 | 42.84194 | -0.1967 | 6.62226 |
September | 720.00000 | 24.69701 | 33.49872 | -0.1931 | 7.37467 |
October | 744.00000 | 24.76399 | 31.07576 | 0.53613 | 14.25581 |
November | 720.00000 | 25.07848 | 32.01245 | 0.61886 | 16.83415 |
December | 744.00000 | 24.48992 | 27.25002 | 0.41003 | 13.31222 |
Annual Sum or Average | 8760.00000 | 24.55418 | 34.36569 | 0.16877 | 10.85254 |
Minimum of Months | 672.00000 | 23.98236 | 27.25002 | -0.4029 | 6.62226 |
Maximum of Months | 744.00000 | 25.07848 | 43.23662 | 0.61886 | 16.83415 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 24.94697 | 29.83958 | 0.51885 | 11.29734 |
February | 672.00000 | 24.79489 | 28.93472 | 0.46630 | 10.40258 |
March | 744.00000 | 24.71577 | 27.92346 | 0.44144 | 9.63163 |
April | 720.00000 | 24.58647 | 31.85723 | 0.43159 | 9.50173 |
May | 744.00000 | 24.68855 | 34.21377 | -0.3334 | 8.16489 |
June | 720.00000 | 24.40982 | 40.08344 | -0.3376 | 7.74131 |
July | 744.00000 | 24.40465 | 42.10094 | -0.3216 | 7.52283 |
August | 744.00000 | 24.40805 | 41.88092 | -0.3236 | 7.51697 |
September | 720.00000 | 24.57700 | 32.67776 | -0.3373 | 7.80442 |
October | 744.00000 | 24.95416 | 29.62107 | 0.53081 | 11.63082 |
November | 720.00000 | 25.08559 | 30.71621 | 0.56576 | 12.42755 |
December | 744.00000 | 24.73155 | 26.01257 | 0.42907 | 9.71623 |
Annual Sum or Average | 8760.00000 | 24.69141 | 33.01253 | 0.14225 | 9.43952 |
Minimum of Months | 672.00000 | 24.40465 | 26.01257 | -0.3376 | 7.51697 |
Maximum of Months | 744.00000 | 25.08559 | 42.10094 | 0.56576 | 12.42755 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.32430 | 35.95320 | -0.4180 | 9.87104 |
February | 672.00000 | 21.23417 | 34.09801 | -0.4598 | 10.89155 |
March | 744.00000 | 21.24442 | 33.67464 | -0.4312 | 10.17409 |
April | 720.00000 | 21.23442 | 38.28835 | -0.4164 | 9.84610 |
May | 744.00000 | 21.62981 | 40.92654 | -1.3698 | 44.82329 |
June | 720.00000 | 21.84156 | 45.47250 | -1.1470 | 34.41932 |
July | 744.00000 | 21.82091 | 47.18312 | -1.1508 | 34.50170 |
August | 744.00000 | 21.82053 | 47.54141 | -1.1547 | 34.75859 |
September | 720.00000 | 21.75824 | 38.47437 | -1.2580 | 39.73007 |
October | 744.00000 | 21.39639 | 36.51844 | -0.3493 | 9.21284 |
November | 720.00000 | 21.35348 | 37.58115 | -0.3894 | 9.53438 |
December | 744.00000 | 21.12475 | 30.49587 | -0.5337 | 12.42408 |
Annual Sum or Average | 8760.00000 | 21.48324 | 38.87760 | -0.7584 | 21.75231 |
Minimum of Months | 672.00000 | 21.12475 | 30.49587 | -1.3698 | 9.21284 |
Maximum of Months | 744.00000 | 21.84156 | 47.54141 | -0.3493 | 44.82329 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.83120 | 36.89743 | -0.5839 | 12.80424 |
February | 672.00000 | 20.82822 | 34.81006 | -0.5981 | 13.38827 |
March | 744.00000 | 21.14286 | 33.94331 | -0.4867 | 11.37161 |
April | 720.00000 | 21.18248 | 38.45343 | -0.4416 | 10.33755 |
May | 744.00000 | 21.96172 | 40.36053 | -1.2853 | 41.64572 |
June | 720.00000 | 22.47952 | 44.27630 | -0.9687 | 28.71195 |
July | 744.00000 | 22.40126 | 46.25974 | -0.9903 | 28.63630 |
August | 744.00000 | 22.38124 | 46.41951 | -1.0134 | 29.76459 |
September | 720.00000 | 22.24743 | 37.71174 | -1.1585 | 36.20170 |
October | 744.00000 | 21.33264 | 36.68612 | -0.4051 | 10.01241 |
November | 720.00000 | 20.96156 | 38.37190 | -0.5301 | 11.65607 |
December | 744.00000 | 20.74683 | 31.11382 | -0.6682 | 15.18071 |
Annual Sum or Average | 8760.00000 | 21.54534 | 38.79775 | -0.7620 | 20.86020 |
Minimum of Months | 672.00000 | 20.74683 | 31.11382 | -1.2853 | 10.01241 |
Maximum of Months | 744.00000 | 22.47952 | 46.41951 | -0.4051 | 41.64572 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.97158 | 40.25634 | -0.5004 | 10.45385 |
February | 672.00000 | 20.94361 | 38.55953 | -0.5194 | 10.90804 |
March | 744.00000 | 21.17068 | 37.02344 | -0.4484 | 9.36923 |
April | 720.00000 | 21.27096 | 41.00864 | -0.3870 | 8.35188 |
May | 744.00000 | 21.78309 | 41.62938 | -1.3566 | 43.77187 |
June | 720.00000 | 22.25398 | 45.88818 | -1.1263 | 33.14131 |
July | 744.00000 | 22.27820 | 47.62445 | -1.1043 | 32.19420 |
August | 744.00000 | 22.17835 | 47.63908 | -1.1543 | 34.34632 |
September | 720.00000 | 21.98395 | 39.07009 | -1.2943 | 40.83777 |
October | 744.00000 | 21.27143 | 39.37565 | -0.3977 | 8.58210 |
November | 720.00000 | 21.05129 | 41.47490 | -0.4649 | 9.70257 |
December | 744.00000 | 20.90041 | 35.02093 | -0.5576 | 11.85834 |
Annual Sum or Average | 8760.00000 | 21.50792 | 41.22895 | -0.7776 | 21.18982 |
Minimum of Months | 672.00000 | 20.90041 | 35.02093 | -1.3566 | 8.35188 |
Maximum of Months | 744.00000 | 22.27820 | 47.63908 | -0.3870 | 43.77187 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.36255 | 35.88669 | -0.4122 | 9.77339 |
February | 672.00000 | 21.29630 | 33.98506 | -0.4448 | 10.78668 |
March | 744.00000 | 21.33930 | 33.52466 | -0.4050 | 9.87813 |
April | 720.00000 | 21.33488 | 38.02354 | -0.3848 | 9.46274 |
May | 744.00000 | 21.72637 | 40.48358 | -1.3280 | 42.82745 |
June | 720.00000 | 21.85529 | 45.29481 | -1.1270 | 33.48884 |
July | 744.00000 | 21.85821 | 46.85705 | -1.1149 | 32.98687 |
August | 744.00000 | 21.84274 | 47.00949 | -1.1272 | 33.57500 |
September | 720.00000 | 21.80278 | 38.29986 | -1.2338 | 38.60247 |
October | 744.00000 | 21.44669 | 36.40846 | -0.3396 | 9.15134 |
November | 720.00000 | 21.36293 | 37.55468 | -0.3918 | 9.58466 |
December | 744.00000 | 21.14671 | 30.45263 | -0.5296 | 12.31345 |
Annual Sum or Average | 8760.00000 | 21.53253 | 38.67416 | -0.7384 | 21.10099 |
Minimum of Months | 672.00000 | 21.14671 | 30.45263 | -1.3280 | 9.15134 |
Maximum of Months | 744.00000 | 21.85821 | 47.00949 | -0.3396 | 42.82745 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.81915 | 36.88070 | -0.5887 | 12.83742 |
February | 672.00000 | 20.87542 | 34.65294 | -0.5858 | 13.20553 |
March | 744.00000 | 21.20065 | 33.70832 | -0.4682 | 10.68441 |
April | 720.00000 | 21.27349 | 38.14490 | -0.4124 | 9.78610 |
May | 744.00000 | 21.97537 | 40.00068 | -1.2680 | 40.18845 |
June | 720.00000 | 22.57244 | 44.09830 | -0.9261 | 27.21986 |
July | 744.00000 | 22.56736 | 45.84694 | -0.9165 | 26.63645 |
August | 744.00000 | 22.48203 | 45.89440 | -0.9616 | 28.12903 |
September | 720.00000 | 22.22211 | 37.56274 | -1.1538 | 35.19236 |
October | 744.00000 | 21.32928 | 36.53154 | -0.4079 | 9.67160 |
November | 720.00000 | 20.92418 | 38.39731 | -0.5423 | 11.87329 |
December | 744.00000 | 20.72496 | 31.09861 | -0.6732 | 15.24177 |
Annual Sum or Average | 8760.00000 | 21.58450 | 38.58953 | -0.7432 | 20.10128 |
Minimum of Months | 672.00000 | 20.72496 | 31.09861 | -1.2680 | 9.67160 |
Maximum of Months | 744.00000 | 22.57244 | 45.89440 | -0.4079 | 40.18845 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.25237 | 36.09949 | -0.4638 | 10.95146 |
February | 672.00000 | 21.18905 | 34.17925 | -0.4974 | 11.90938 |
March | 744.00000 | 21.20236 | 33.74911 | -0.4608 | 11.05826 |
April | 720.00000 | 21.21878 | 38.32280 | -0.4344 | 10.64196 |
May | 744.00000 | 21.65478 | 40.76684 | -1.3565 | 44.46560 |
June | 720.00000 | 21.87257 | 45.24972 | -1.1139 | 33.40774 |
July | 744.00000 | 21.83348 | 47.06737 | -1.1316 | 33.97608 |
August | 744.00000 | 21.83831 | 47.45012 | -1.1298 | 34.08265 |
September | 720.00000 | 21.75298 | 38.31121 | -1.2560 | 39.98753 |
October | 744.00000 | 21.35992 | 36.58160 | -0.3765 | 9.99949 |
November | 720.00000 | 21.30490 | 37.68653 | -0.4248 | 10.43855 |
December | 744.00000 | 21.05294 | 30.61990 | -0.5825 | 13.77636 |
Annual Sum or Average | 8760.00000 | 21.46244 | 38.86711 | -0.7708 | 22.12423 |
Minimum of Months | 672.00000 | 21.05294 | 30.61990 | -1.3565 | 9.99949 |
Maximum of Months | 744.00000 | 21.87257 | 47.45012 | -0.3765 | 44.46560 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.74560 | 37.08576 | -0.6386 | 14.30804 |
February | 672.00000 | 20.78031 | 34.90189 | -0.6414 | 14.61317 |
March | 744.00000 | 21.13016 | 34.02542 | -0.5120 | 12.43950 |
April | 720.00000 | 21.19193 | 38.48226 | -0.4551 | 11.17012 |
May | 744.00000 | 22.08669 | 40.13865 | -1.2377 | 40.61013 |
June | 720.00000 | 22.61147 | 43.90819 | -0.8981 | 27.61840 |
July | 744.00000 | 22.46892 | 45.98798 | -0.9488 | 27.89326 |
August | 744.00000 | 22.47308 | 46.12472 | -0.9605 | 28.79393 |
September | 720.00000 | 22.33217 | 37.56072 | -1.1242 | 35.84913 |
October | 744.00000 | 21.33572 | 36.76895 | -0.4263 | 10.98287 |
November | 720.00000 | 20.90598 | 38.50577 | -0.5727 | 12.81404 |
December | 744.00000 | 20.67362 | 31.24340 | -0.7219 | 16.83706 |
Annual Sum or Average | 8760.00000 | 21.56554 | 38.74954 | -0.7624 | 21.20692 |
Minimum of Months | 672.00000 | 20.67362 | 31.24340 | -1.2377 | 10.98287 |
Maximum of Months | 744.00000 | 22.61147 | 46.12472 | -0.4263 | 40.61013 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.70930 | 42.09821 | -0.2117 | 8.67739 |
February | 672.00000 | 21.54171 | 40.52576 | -0.2905 | 9.43357 |
March | 744.00000 | 21.40790 | 40.02938 | -0.3359 | 9.19722 |
April | 720.00000 | 21.34324 | 44.37096 | -0.3564 | 8.93621 |
May | 744.00000 | 21.67100 | 45.15486 | -1.3543 | 44.12669 |
June | 720.00000 | 21.82374 | 48.44474 | -1.1899 | 36.30451 |
July | 744.00000 | 21.82275 | 49.69155 | -1.1746 | 35.63710 |
August | 744.00000 | 21.82323 | 49.62594 | -1.1676 | 35.41595 |
September | 720.00000 | 21.81422 | 41.76690 | -1.2172 | 38.19531 |
October | 744.00000 | 21.53909 | 42.33168 | -0.2497 | 8.75994 |
November | 720.00000 | 21.71847 | 43.39465 | -0.1989 | 8.57863 |
December | 744.00000 | 21.59719 | 36.84410 | -0.3106 | 9.91997 |
Annual Sum or Average | 8760.00000 | 21.65162 | 43.70708 | -0.6738 | 21.17354 |
Minimum of Months | 672.00000 | 21.34324 | 36.84410 | -1.3543 | 8.57863 |
Maximum of Months | 744.00000 | 21.82374 | 49.69155 | -0.1989 | 44.12669 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 25.42133 | 31.21708 | 0.61208 | 13.94697 |
February | 672.00000 | 25.42796 | 29.97633 | 0.60379 | 13.77767 |
March | 744.00000 | 25.59254 | 28.73181 | 0.66434 | 15.26749 |
April | 720.00000 | 25.69410 | 32.17262 | 0.72834 | 17.22788 |
May | 744.00000 | 25.68459 | 34.49018 | 0.08613 | 6.70915 |
June | 720.00000 | 25.27316 | 40.08612 | 0.07272 | 5.88173 |
July | 744.00000 | 25.24673 | 42.01941 | 0.08006 | 5.94814 |
August | 744.00000 | 25.16513 | 41.92960 | 0.03977 | 5.83290 |
September | 720.00000 | 25.20960 | 33.50106 | -0.0450 | 6.08201 |
October | 744.00000 | 25.64203 | 30.67196 | 0.70938 | 16.71860 |
November | 720.00000 | 25.58401 | 32.05052 | 0.67520 | 15.60813 |
December | 744.00000 | 25.21209 | 27.18585 | 0.51703 | 11.86267 |
Annual Sum or Average | 8760.00000 | 25.42933 | 33.69115 | 0.39401 | 11.21817 |
Minimum of Months | 672.00000 | 25.16513 | 27.18585 | -0.0450 | 5.83290 |
Maximum of Months | 744.00000 | 25.69410 | 42.01941 | 0.72834 | 17.22788 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 25.93280 | 30.18504 | 0.78363 | 18.97481 |
February | 672.00000 | 25.96005 | 28.95953 | 0.78187 | 18.92546 |
March | 744.00000 | 26.09747 | 27.76732 | 0.83355 | 20.59548 |
April | 720.00000 | 26.18169 | 31.13946 | 0.89187 | 22.76181 |
May | 744.00000 | 26.04535 | 33.54005 | 0.26634 | 8.14526 |
June | 720.00000 | 25.53997 | 39.18881 | 0.21234 | 6.81832 |
July | 744.00000 | 25.50966 | 41.09572 | 0.21772 | 6.94458 |
August | 744.00000 | 25.41139 | 41.03361 | 0.17122 | 6.50980 |
September | 720.00000 | 25.46559 | 32.69648 | 0.09202 | 6.30022 |
October | 744.00000 | 26.05062 | 29.72310 | 0.85114 | 21.42360 |
November | 720.00000 | 26.06664 | 31.01855 | 0.83802 | 20.79722 |
December | 744.00000 | 25.72945 | 26.19097 | 0.69316 | 16.40157 |
Annual Sum or Average | 8760.00000 | 25.83172 | 32.73363 | 0.55134 | 14.51805 |
Minimum of Months | 672.00000 | 25.41139 | 26.19097 | 0.09202 | 6.30022 |
Maximum of Months | 744.00000 | 26.18169 | 41.09572 | 0.89187 | 22.76181 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 29.80350 | 28.91192 | 2.35818 | 79.23846 |
February | 672.00000 | 29.86530 | 27.97347 | 2.36440 | 79.10637 |
March | 744.00000 | 29.77880 | 26.99294 | 2.36890 | 80.14610 |
April | 720.00000 | 29.77889 | 29.83135 | 2.40481 | 81.22380 |
May | 744.00000 | 29.23281 | 32.21623 | 2.30366 | 75.48670 |
June | 720.00000 | 28.65687 | 37.50832 | 2.27138 | 71.71100 |
July | 744.00000 | 28.63638 | 39.15823 | 2.27076 | 71.22623 |
August | 744.00000 | 28.54427 | 39.22933 | 2.22446 | 70.84451 |
September | 720.00000 | 28.48734 | 32.08981 | 2.09717 | 69.57870 |
October | 744.00000 | 29.54420 | 28.76142 | 2.34862 | 80.22976 |
November | 720.00000 | 29.82599 | 29.56678 | 2.38820 | 80.14030 |
December | 744.00000 | 29.51238 | 26.02941 | 2.24075 | 76.60294 |
Annual Sum or Average | 8760.00000 | 29.30226 | 31.54364 | 2.30308 | 76.27838 |
Minimum of Months | 672.00000 | 28.48734 | 26.02941 | 2.09717 | 69.57870 |
Maximum of Months | 744.00000 | 29.86530 | 39.22933 | 2.40481 | 81.22380 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.143334E+11 | 78905.16 | 20-JAN-13:03 | 432.80 | 0.452407E+11 | 0.00 | 0.595741E+11 | 1.81 | 4.09 | 20-JAN-13:03 | 0.00 | 0.00 |
February | 0.957612E+10 | 73649.44 | 18-FEB-13:33 | 344.90 | 0.300208E+11 | 0.00 | 0.395969E+11 | 1.60 | 4.12 | 18-FEB-13:33 | 0.00 | 0.00 |
March | 0.162845E+11 | 91243.49 | 14-MAR-13:00 | 415.19 | 0.516736E+11 | 0.00 | 0.679580E+11 | 1.73 | 4.01 | 13-MAR-12:43 | 0.00 | 0.00 |
April | 0.120096E+11 | 67153.56 | 07-APR-15:23 | 412.36 | 0.368758E+11 | 0.00 | 0.488854E+11 | 1.76 | 3.87 | 07-APR-15:23 | 0.00 | 0.00 |
May | 0.449498E+11 | 116402.12 | 31-MAY-15:13 | 706.52 | 0.142619E+12 | 0.00 | 0.187569E+12 | 2.91 | 4.12 | 10-MAY-21:14 | 0.00 | 0.00 |
June | 0.126264E+12 | 193377.71 | 26-JUN-15:21 | 720.00 | 0.405168E+12 | 0.00 | 0.531432E+12 | 3.05 | 4.53 | 20-JUN-21:23 | 0.00 | 0.00 |
July | 0.140730E+12 | 158041.43 | 15-JUL-15:21 | 744.00 | 0.461592E+12 | 0.00 | 0.602321E+12 | 3.09 | 4.62 | 30-JUL-21:13 | 0.00 | 0.00 |
August | 0.128029E+12 | 162826.10 | 16-AUG-15:14 | 744.00 | 0.419324E+12 | 0.00 | 0.547354E+12 | 3.09 | 4.58 | 04-AUG-03:03 | 0.00 | 0.00 |
September | 0.942527E+11 | 143583.91 | 10-SEP-15:21 | 709.95 | 0.308080E+12 | 0.00 | 0.402332E+12 | 3.05 | 4.23 | 28-SEP-21:13 | 0.00 | 0.00 |
October | 0.279560E+11 | 114476.94 | 11-OCT-15:17 | 520.07 | 0.911366E+11 | 0.00 | 0.119093E+12 | 2.18 | 4.11 | 09-OCT-11:53 | 0.00 | 0.00 |
November | 0.159817E+11 | 84489.69 | 07-NOV-14:23 | 444.03 | 0.513192E+11 | 0.00 | 0.673009E+11 | 1.93 | 4.06 | 07-NOV-13:17 | 0.00 | 0.00 |
December | 0.106251E+11 | 79029.43 | 02-DEC-14:57 | 334.77 | 0.337516E+11 | 0.00 | 0.443767E+11 | 1.40 | 4.05 | 02-DEC-13:33 | 0.00 | 0.00 |
Annual Sum or Average | 0.640991E+12 | 6528.59 | 0.207680E+13 | 0.271779E+13 | 2.31 | |||||||
Minimum of Months | 0.957612E+10 | 67153.56 | 334.77 | 0.300208E+11 | 0.00 | 0.395969E+11 | 1.40 | 3.87 | 0.00 | 0.00 | ||
Maximum of Months | 0.140730E+12 | 193377.71 | 744.00 | 0.461592E+12 | 0.00 | 0.602321E+12 | 3.09 | 4.62 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.440897E+11 | 0.00 | 580.31 | 199876.62 | 05-JAN-09:04 | 0.00 | 57.76 | 59.66 | 1.37 | 0.00 | 0.03 | 0.41 | 05-JAN-09:04 |
February | 0.471081E+11 | 0.00 | 531.30 | 201971.91 | 12-FEB-05:26 | 0.00 | 57.65 | 59.70 | 1.53 | 0.00 | 0.04 | 0.42 | 12-FEB-05:26 |
March | 0.267896E+11 | 0.00 | 480.20 | 162921.36 | 19-MAR-06:34 | 0.00 | 57.88 | 59.32 | 0.97 | 0.00 | 0.02 | 0.34 | 19-MAR-06:34 |
April | 0.183262E+11 | 0.00 | 464.52 | 110594.76 | 02-APR-15:16 | 0.00 | 57.79 | 59.19 | 0.79 | 0.00 | 0.01 | 0.23 | 02-APR-15:16 |
May | 0.177164E+10 | 0.00 | 192.77 | 61107.74 | 29-MAY-22:21 | 0.00 | 58.04 | 58.59 | 0.11 | 0.00 | 0.00 | 0.13 | 29-MAY-22:21 |
June | 7084768.83 | 0.00 | 3.68 | 3750.51 | 28-JUN-08:17 | 0.00 | 57.23 | 57.25 | 0.00 | 0.00 | 0.00 | 0.01 | 28-JUN-08:17 |
July | 6466849.75 | 0.00 | 2.78 | 4471.92 | 31-JUL-08:17 | 0.00 | 56.95 | 56.96 | 0.00 | 0.00 | 0.00 | 0.01 | 31-JUL-08:17 |
August | 10476807.09 | 0.00 | 6.43 | 8544.82 | 30-AUG-08:15 | 0.00 | 56.74 | 56.77 | 0.00 | 0.00 | 0.00 | 0.02 | 30-AUG-08:15 |
September | 0.500294E+09 | 0.00 | 52.69 | 37961.97 | 30-SEP-22:31 | 0.00 | 56.94 | 57.10 | 0.03 | 0.00 | 0.00 | 0.08 | 30-SEP-22:31 |
October | 0.188284E+11 | 0.00 | 423.06 | 152583.35 | 31-OCT-15:34 | 0.00 | 57.86 | 59.14 | 0.64 | 0.00 | 0.01 | 0.31 | 31-OCT-15:34 |
November | 0.296851E+11 | 0.00 | 524.31 | 163075.99 | 29-NOV-19:04 | 0.00 | 57.71 | 59.41 | 1.04 | 0.00 | 0.02 | 0.34 | 29-NOV-19:04 |
December | 0.778729E+11 | 0.00 | 625.88 | 235295.64 | 21-DEC-09:06 | 0.00 | 56.76 | 59.60 | 1.65 | 0.00 | 0.06 | 0.49 | 21-DEC-09:06 |
Annual Sum or Average | 0.264996E+12 | 3887.94 | 57.44 | 58.55 | 0.67 | 0.00 | 0.02 | ||||||
Minimum of Months | 6466849.75 | 0.00 | 2.78 | 3750.51 | 0.00 | 56.74 | 56.77 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.778729E+11 | 0.00 | 625.88 | 235295.64 | 0.00 | 58.04 | 59.70 | 1.65 | 0.00 | 0.06 | 0.49 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.810940E+09 | 0.00 | 149.53 | 0.744785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10198.06 | 12-JAN-16:11 | 10198.06 | 12-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.851576E+09 | 0.00 | 133.88 | 0.815652E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10196.23 | 20-FEB-16:11 | 10196.23 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.179744E+10 | 0.00 | 237.91 | 0.178839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10197.62 | 26-MAR-15:11 | 10197.62 | 26-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.993951E+09 | 0.00 | 170.49 | 0.919358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11494.16 | 06-APR-18:31 | 11494.16 | 06-APR-18:31 | 0.00 | 0.00 | 0.00 |
May | 0.277123E+10 | 0.00 | 458.72 | 0.224146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11199.04 | 22-MAY-08:61 | 10197.90 | 05-MAY-15:11 | 0.00 | 0.00 | 0.00 |
June | 0.739327E+10 | 0.00 | 675.13 | 0.599751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11705.21 | 18-JUN-08:61 | 10217.84 | 02-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.735034E+10 | 0.00 | 703.17 | 0.552225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12066.92 | 28-JUL-15:11 | 10198.58 | 14-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.705429E+10 | 0.00 | 693.89 | 0.539393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12004.34 | 05-AUG-08:61 | 10267.91 | 26-AUG-16:45 | 0.00 | 0.00 | 0.00 |
September | 0.554128E+10 | 0.00 | 628.31 | 0.477574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10298.89 | 01-SEP-08:62 | 10198.55 | 09-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.247800E+10 | 0.00 | 334.52 | 0.232594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10198.54 | 01-OCT-18:01 | 10198.54 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.114501E+10 | 0.00 | 192.86 | 0.101186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10198.07 | 19-NOV-16:11 | 10198.07 | 19-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.531911E+09 | 0.00 | 112.84 | 0.526952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10195.26 | 29-DEC-16:11 | 10195.26 | 29-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.387192E+11 | 4491.26 | 0.320638E+11 | ||||||||||||
Minimum of Months | 0.531911E+09 | 0.00 | 112.84 | 0.526952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10195.26 | 10195.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.739327E+10 | 0.00 | 703.17 | 0.599751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12066.92 | 11494.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.117053E+09 | 0.00 | 27.42 | 0.111326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10261.90 | 20-JAN-16:31 | 10261.90 | 20-JAN-16:31 | 0.00 | 0.00 | 0.00 |
February | 0.197499E+09 | 0.00 | 36.58 | 0.195151E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10071.87 | 20-FEB-16:11 | 10071.87 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.720097E+09 | 0.00 | 134.72 | 0.716443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11986.16 | 15-MAR-17:51 | 11986.16 | 15-MAR-17:51 | 0.00 | 0.00 | 0.00 |
April | 0.572842E+09 | 0.00 | 122.53 | 0.513930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12294.85 | 08-APR-17:21 | 12294.85 | 08-APR-17:21 | 0.00 | 0.00 | 0.00 |
May | 0.176945E+10 | 0.00 | 373.18 | 0.128662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11035.32 | 22-MAY-08:61 | 10512.05 | 27-MAY-15:31 | 0.00 | 0.00 | 0.00 |
June | 0.604991E+10 | 0.00 | 535.87 | 0.490250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12063.62 | 20-JUN-21:11 | 11110.54 | 30-JUN-21:11 | 0.00 | 0.00 | 0.00 |
July | 0.591434E+10 | 0.00 | 538.88 | 0.451219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12569.11 | 31-JUL-21:11 | 11069.37 | 01-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.529696E+10 | 0.00 | 534.37 | 0.401588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12313.45 | 04-AUG-08:11 | 10858.51 | 13-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.330142E+10 | 0.00 | 452.73 | 0.269223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10547.07 | 10-SEP-21:11 | 10547.07 | 10-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.848999E+09 | 0.00 | 174.03 | 0.787412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11046.61 | 08-OCT-17:31 | 11046.61 | 08-OCT-17:31 | 0.00 | 0.00 | 0.00 |
November | 0.195962E+09 | 0.00 | 53.39 | 0.179647E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10072.69 | 15-NOV-16:11 | 10072.69 | 15-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 44160554.59 | 0.00 | 14.55 | 43999494.86 | 0.00 | 0.00 | 0.00 | 0.00 | 10068.04 | 03-DEC-16:11 | 10068.04 | 03-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250287E+11 | 2998.25 | 0.199573E+11 | ||||||||||||
Minimum of Months | 44160554.59 | 0.00 | 14.55 | 43999494.86 | 0.00 | 0.00 | 0.00 | 0.00 | 10068.04 | 10068.04 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.604991E+10 | 0.00 | 538.88 | 0.490250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12569.11 | 12294.85 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.281104E+11 | 0.00 | 365.30 | 0.234436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54612.85 | 19-JAN-13:30 | 54612.85 | 19-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.169668E+11 | 0.00 | 251.22 | 0.135863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52937.21 | 18-FEB-13:20 | 52937.21 | 18-FEB-13:20 | 0.00 | 0.00 | 0.00 |
March | 0.157503E+11 | 0.00 | 250.95 | 0.129865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50155.68 | 11-MAR-13:00 | 50155.68 | 11-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.206111E+10 | 0.00 | 90.75 | 0.911658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20892.13 | 13-APR-12:23 | 13590.61 | 13-APR-12:23 | 0.00 | 0.00 | 0.00 |
May | 0.119974E+11 | 0.00 | 425.78 | 0.504888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19463.03 | 06-MAY-15:02 | 15172.21 | 06-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.314725E+11 | 0.00 | 697.66 | 0.182609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27767.74 | 26-JUN-17:11 | 25346.89 | 26-JUN-17:11 | 0.00 | 0.00 | 0.00 |
July | 0.355914E+11 | 0.00 | 728.51 | 0.211793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27780.42 | 18-JUL-17:11 | 24317.78 | 18-JUL-17:11 | 0.00 | 0.00 | 0.00 |
August | 0.377251E+11 | 0.00 | 733.68 | 0.236387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33434.68 | 29-AUG-13:22 | 27811.69 | 16-AUG-12:31 | 0.00 | 0.00 | 0.00 |
September | 0.391918E+11 | 0.00 | 669.88 | 0.278599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 50523.60 | 28-SEP-13:12 | 50523.60 | 28-SEP-13:12 | 0.00 | 0.00 | 0.00 |
October | 0.289509E+11 | 0.00 | 403.20 | 0.234506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53578.10 | 10-OCT-11:21 | 53578.10 | 10-OCT-11:21 | 0.00 | 0.00 | 0.00 |
November | 0.255305E+11 | 0.00 | 346.75 | 0.209546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55075.59 | 19-NOV-12:10 | 55075.59 | 19-NOV-12:10 | 0.00 | 0.00 | 0.00 |
December | 0.173585E+11 | 0.00 | 231.57 | 0.147605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51826.97 | 16-DEC-13:52 | 51826.97 | 16-DEC-13:52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290707E+12 | 5195.26 | 0.206081E+12 | ||||||||||||
Minimum of Months | 0.206111E+10 | 0.00 | 90.75 | 0.911658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19463.03 | 13590.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.391918E+11 | 0.00 | 733.68 | 0.278599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55075.59 | 55075.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.123483E+10 | 0.00 | 87.25 | 0.937988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50451.11 | 21-JAN-09:01 | 50451.11 | 21-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.112664E+10 | 0.00 | 75.83 | 0.853288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49135.39 | 27-FEB-19:01 | 49135.39 | 27-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.551890E+10 | 0.00 | 205.73 | 0.505723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52072.75 | 16-MAR-18:01 | 52072.75 | 16-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.777735E+10 | 0.00 | 276.68 | 0.588447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51498.80 | 08-APR-08:61 | 51498.80 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.242338E+11 | 0.00 | 427.97 | 0.197491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 56713.87 | 22-MAY-15:11 | 54411.90 | 17-MAY-21:11 | 0.00 | 0.00 | 0.00 |
June | 0.435438E+11 | 0.00 | 484.86 | 0.373293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62159.89 | 20-JUN-21:11 | 57303.92 | 25-JUN-07:41 | 0.00 | 0.00 | 0.00 |
July | 0.460047E+11 | 0.00 | 496.98 | 0.387457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65144.49 | 30-JUL-21:11 | 56376.31 | 01-JUL-08:11 | 0.00 | 0.00 | 0.00 |
August | 0.402825E+11 | 0.00 | 471.48 | 0.328703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61826.40 | 04-AUG-08:11 | 54803.83 | 01-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.281115E+11 | 0.00 | 417.80 | 0.249336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54661.14 | 08-SEP-21:11 | 54661.14 | 08-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.840349E+10 | 0.00 | 292.62 | 0.684989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52233.41 | 01-OCT-18:01 | 52233.41 | 01-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.241313E+10 | 0.00 | 134.37 | 0.178667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50108.43 | 06-NOV-19:01 | 50108.43 | 06-NOV-19:01 | 0.00 | 0.00 | 0.00 |
December | 0.877203E+09 | 0.00 | 61.18 | 0.808385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49614.13 | 03-DEC-09:01 | 49614.13 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209528E+12 | 3432.76 | 0.175806E+12 | ||||||||||||
Minimum of Months | 0.877203E+09 | 0.00 | 61.18 | 0.808385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49135.39 | 49135.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.460047E+11 | 0.00 | 496.98 | 0.387457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65144.49 | 57303.92 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.800519E+09 | 0.00 | 145.90 | 0.747202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8765.64 | 20-JAN-09:01 | 8765.64 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.956964E+09 | 0.00 | 161.32 | 0.887551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8764.49 | 14-FEB-09:01 | 8764.49 | 14-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.187480E+10 | 0.00 | 261.55 | 0.185100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8765.52 | 13-MAR-08:61 | 8765.52 | 13-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.127767E+10 | 0.00 | 213.81 | 0.115209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8765.28 | 08-APR-08:61 | 8765.28 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.310293E+10 | 0.00 | 507.84 | 0.253414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9647.96 | 04-MAY-08:11 | 9647.96 | 04-MAY-08:11 | 0.00 | 0.00 | 0.00 |
June | 0.789647E+10 | 0.00 | 705.86 | 0.653350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9742.91 | 17-JUN-08:62 | 8765.14 | 28-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.830369E+10 | 0.00 | 725.08 | 0.664279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10313.11 | 31-JUL-18:01 | 8765.28 | 14-JUL-15:11 | 0.00 | 0.00 | 0.00 |
August | 0.789191E+10 | 0.00 | 724.99 | 0.627866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9291.14 | 29-AUG-18:01 | 8765.48 | 12-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.584705E+10 | 0.00 | 650.30 | 0.515238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8765.33 | 09-SEP-18:01 | 8765.33 | 09-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.234675E+10 | 0.00 | 337.83 | 0.218329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8765.62 | 15-OCT-08:61 | 8765.62 | 15-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.108291E+10 | 0.00 | 190.90 | 0.963093E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8764.65 | 07-NOV-09:01 | 8764.65 | 07-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 0.541510E+09 | 0.00 | 118.03 | 0.534641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8765.52 | 18-DEC-09:01 | 8765.52 | 18-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419232E+11 | 4743.40 | 0.354603E+11 | ||||||||||||
Minimum of Months | 0.541510E+09 | 0.00 | 118.03 | 0.534641E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8764.49 | 8764.49 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.830369E+10 | 0.00 | 725.08 | 0.664279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10313.11 | 9647.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.115045E+09 | 0.00 | 25.84 | 95163566.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8717.18 | 20-JAN-09:01 | 8717.18 | 20-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.278882E+09 | 0.00 | 53.17 | 0.243232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8564.03 | 14-FEB-09:01 | 8564.03 | 14-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.890432E+09 | 0.00 | 151.50 | 0.869240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8717.15 | 13-MAR-08:61 | 8717.15 | 13-MAR-08:61 | 0.00 | 0.00 | 0.00 |
April | 0.899302E+09 | 0.00 | 159.09 | 0.790852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8716.89 | 08-APR-08:61 | 8716.89 | 08-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.230845E+10 | 0.00 | 418.68 | 0.180716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9698.21 | 13-MAY-08:11 | 9698.21 | 13-MAY-08:11 | 0.00 | 0.00 | 0.00 |
June | 0.639601E+10 | 0.00 | 547.37 | 0.535192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11368.24 | 21-JUN-08:11 | 11214.30 | 27-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.663989E+10 | 0.00 | 548.73 | 0.542418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11928.89 | 01-JUL-08:11 | 11928.89 | 01-JUL-08:11 | 0.00 | 0.00 | 0.00 |
August | 0.599495E+10 | 0.00 | 556.72 | 0.475064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12466.76 | 05-AUG-08:11 | 10948.09 | 06-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.377731E+10 | 0.00 | 488.13 | 0.320900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10401.71 | 07-SEP-08:11 | 10401.71 | 07-SEP-08:11 | 0.00 | 0.00 | 0.00 |
October | 0.879365E+09 | 0.00 | 166.14 | 0.795245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9307.28 | 11-OCT-08:11 | 9307.28 | 11-OCT-08:11 | 0.00 | 0.00 | 0.00 |
November | 0.220269E+09 | 0.00 | 50.50 | 0.184599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8716.24 | 07-NOV-09:01 | 8716.24 | 07-NOV-09:01 | 0.00 | 0.00 | 0.00 |
December | 57608427.55 | 0.00 | 15.46 | 53025830.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8531.79 | 03-DEC-09:01 | 8531.79 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284575E+11 | 3181.34 | 0.235743E+11 | ||||||||||||
Minimum of Months | 57608427.55 | 0.00 | 15.46 | 53025830.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8531.79 | 8531.79 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.663989E+10 | 0.00 | 556.72 | 0.542418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12466.76 | 11928.89 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.211586E+09 | 0.00 | 126.09 | 0.198195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2722.24 | 12-JAN-16:11 | 2722.24 | 12-JAN-16:11 | 0.00 | 0.00 | 0.00 |
February | 0.232007E+09 | 0.00 | 116.36 | 0.226033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2721.76 | 20-FEB-16:11 | 2721.76 | 20-FEB-16:11 | 0.00 | 0.00 | 0.00 |
March | 0.498445E+09 | 0.00 | 212.27 | 0.496118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2722.13 | 26-MAR-15:11 | 2722.13 | 26-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.304301E+09 | 0.00 | 171.28 | 0.285758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3313.91 | 06-APR-18:31 | 3313.91 | 06-APR-18:31 | 0.00 | 0.00 | 0.00 |
May | 0.823031E+09 | 0.00 | 441.53 | 0.686826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2990.58 | 22-MAY-08:61 | 2796.31 | 03-MAY-18:11 | 0.00 | 0.00 | 0.00 |
June | 0.207676E+10 | 0.00 | 680.04 | 0.171507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3153.14 | 18-JUN-08:61 | 2732.47 | 16-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.199075E+10 | 0.00 | 703.81 | 0.153478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3235.55 | 30-JUL-08:61 | 2722.43 | 17-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.195647E+10 | 0.00 | 693.60 | 0.153629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3230.47 | 05-AUG-08:61 | 2823.43 | 26-AUG-16:46 | 0.00 | 0.00 | 0.00 |
September | 0.148292E+10 | 0.00 | 612.53 | 0.129803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2722.36 | 30-SEP-15:11 | 2722.36 | 30-SEP-15:11 | 0.00 | 0.00 | 0.00 |
October | 0.659839E+09 | 0.00 | 296.03 | 0.627077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2722.38 | 09-OCT-15:12 | 2722.38 | 09-OCT-15:12 | 0.00 | 0.00 | 0.00 |
November | 0.308524E+09 | 0.00 | 166.13 | 0.280347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2722.25 | 19-NOV-16:11 | 2722.25 | 19-NOV-16:11 | 0.00 | 0.00 | 0.00 |
December | 0.135421E+09 | 0.00 | 95.94 | 0.134926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2721.50 | 29-DEC-16:11 | 2721.50 | 29-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106801E+11 | 4315.62 | 0.901945E+10 | ||||||||||||
Minimum of Months | 0.135421E+09 | 0.00 | 95.94 | 0.134926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2721.50 | 2721.50 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.207676E+10 | 0.00 | 703.81 | 0.171507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3313.91 | 3313.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 29878789.81 | 0.00 | 21.47 | 28631910.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2781.01 | 20-JAN-16:31 | 2781.01 | 20-JAN-16:31 | 0.00 | 0.00 | 0.00 |
February | 52590742.15 | 0.00 | 32.95 | 52064924.44 | 0.00 | 0.00 | 0.00 | 0.00 | 2720.55 | 26-FEB-17:11 | 2720.55 | 26-FEB-17:11 | 0.00 | 0.00 | 0.00 |
March | 0.204625E+09 | 0.00 | 125.55 | 0.203416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3443.31 | 31-MAR-18:01 | 3443.31 | 31-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.182726E+09 | 0.00 | 122.66 | 0.167084E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3457.50 | 08-APR-17:21 | 3457.50 | 08-APR-17:21 | 0.00 | 0.00 | 0.00 |
May | 0.550575E+09 | 0.00 | 369.49 | 0.420113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3050.73 | 09-MAY-19:51 | 3050.73 | 09-MAY-19:51 | 0.00 | 0.00 | 0.00 |
June | 0.177325E+10 | 0.00 | 541.35 | 0.146249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3293.60 | 22-JUN-21:11 | 3066.05 | 08-JUN-21:11 | 0.00 | 0.00 | 0.00 |
July | 0.166547E+10 | 0.00 | 543.90 | 0.129895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3393.57 | 31-JUL-21:11 | 3085.14 | 01-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.153737E+10 | 0.00 | 541.30 | 0.119144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3335.82 | 05-AUG-21:11 | 3114.70 | 13-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.916457E+09 | 0.00 | 456.01 | 0.757803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2957.68 | 15-SEP-19:11 | 2957.68 | 15-SEP-19:11 | 0.00 | 0.00 | 0.00 |
October | 0.224960E+09 | 0.00 | 150.86 | 0.212302E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3230.95 | 08-OCT-17:31 | 3230.95 | 08-OCT-17:31 | 0.00 | 0.00 | 0.00 |
November | 52679308.56 | 0.00 | 48.23 | 49507002.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2729.37 | 07-NOV-17:01 | 2729.37 | 07-NOV-17:01 | 0.00 | 0.00 | 0.00 |
December | 12189134.42 | 0.00 | 13.58 | 12132092.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2688.56 | 03-DEC-16:11 | 2688.56 | 03-DEC-16:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.720276E+10 | 2967.34 | 0.585594E+10 | ||||||||||||
Minimum of Months | 12189134.42 | 0.00 | 13.58 | 12132092.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2688.56 | 2688.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.177325E+10 | 0.00 | 543.90 | 0.146249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3457.50 | 3457.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.646857E+10 | 0.00 | 377.38 | 0.607501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11655.15 | 20-JAN-13:04 | 11655.15 | 20-JAN-13:04 | 0.00 | 0.00 | 0.00 |
February | 0.487270E+10 | 0.00 | 310.18 | 0.455502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10868.15 | 17-FEB-13:30 | 10868.15 | 17-FEB-13:30 | 0.00 | 0.00 | 0.00 |
March | 0.447654E+10 | 0.00 | 340.63 | 0.430627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10775.68 | 11-MAR-13:26 | 10775.68 | 11-MAR-13:26 | 0.00 | 0.00 | 0.00 |
April | 0.181484E+10 | 0.00 | 240.74 | 0.150257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11051.66 | 28-APR-08:61 | 9989.30 | 12-APR-15:11 | 0.00 | 0.00 | 0.00 |
May | 0.390774E+10 | 0.00 | 501.97 | 0.299836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11991.82 | 29-MAY-08:61 | 9990.79 | 10-MAY-15:11 | 0.00 | 0.00 | 0.00 |
June | 0.879722E+10 | 0.00 | 674.16 | 0.696053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11819.25 | 18-JUN-08:61 | 9991.37 | 07-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.971724E+10 | 0.00 | 698.89 | 0.750090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12361.27 | 31-JUL-18:01 | 9990.97 | 03-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.100595E+11 | 0.00 | 696.26 | 0.792530E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11801.21 | 05-AUG-08:61 | 10015.48 | 04-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.947429E+10 | 0.00 | 646.34 | 0.841450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11009.22 | 21-SEP-08:61 | 10295.95 | 27-SEP-12:10 | 0.00 | 0.00 | 0.00 |
October | 0.684226E+10 | 0.00 | 445.73 | 0.638310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11598.42 | 09-OCT-08:61 | 10889.45 | 10-OCT-15:08 | 0.00 | 0.00 | 0.00 |
November | 0.656665E+10 | 0.00 | 408.53 | 0.603592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11329.59 | 05-NOV-12:18 | 11329.59 | 05-NOV-12:18 | 0.00 | 0.00 | 0.00 |
December | 0.482465E+10 | 0.00 | 300.03 | 0.464922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11518.28 | 17-DEC-13:20 | 11518.28 | 17-DEC-13:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.778222E+11 | 5640.85 | 0.673067E+11 | ||||||||||||
Minimum of Months | 0.181484E+10 | 0.00 | 240.74 | 0.150257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10775.68 | 9989.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.100595E+11 | 0.00 | 698.89 | 0.841450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12361.27 | 11655.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.554909E+10 | 0.00 | 18.22 | 0.554909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198207.36 | 20-JAN-13:03 | 198207.36 | 20-JAN-13:03 | 0.00 | 0.00 | 0.00 |
February | 0.308469E+10 | 0.00 | 10.21 | 0.308469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 188330.21 | 18-FEB-13:11 | 188330.21 | 18-FEB-13:11 | 0.00 | 0.00 | 0.00 |
March | 0.175496E+11 | 0.00 | 51.93 | 0.175496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 249341.96 | 14-MAR-13:11 | 249341.96 | 14-MAR-13:11 | 0.00 | 0.00 | 0.00 |
April | 0.184775E+11 | 0.00 | 57.84 | 0.184775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 208893.49 | 19-APR-13:32 | 208893.49 | 19-APR-13:32 | 0.00 | 0.00 | 0.00 |
May | 0.836052E+11 | 0.00 | 179.45 | 0.836052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 317872.50 | 31-MAY-17:19 | 317872.50 | 31-MAY-17:19 | 0.00 | 0.00 | 0.00 |
June | 0.269794E+12 | 0.00 | 385.50 | 0.259468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 418009.41 | 26-JUN-18:21 | 418009.41 | 26-JUN-18:21 | 0.00 | 0.00 | 0.00 |
July | 0.314666E+12 | 0.00 | 409.06 | 0.286294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 429065.47 | 30-JUL-11:52 | 389269.46 | 15-JUL-18:11 | 0.00 | 0.00 | 0.00 |
August | 0.280424E+12 | 0.00 | 406.79 | 0.265280E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 404407.35 | 05-AUG-14:18 | 394920.89 | 16-AUG-19:18 | 0.00 | 0.00 | 0.00 |
September | 0.196179E+12 | 0.00 | 312.66 | 0.196158E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 362388.22 | 10-SEP-18:21 | 362388.22 | 10-SEP-18:21 | 0.00 | 0.00 | 0.00 |
October | 0.359123E+11 | 0.00 | 84.47 | 0.359123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 305641.20 | 11-OCT-13:02 | 305641.20 | 11-OCT-13:02 | 0.00 | 0.00 | 0.00 |
November | 0.116818E+11 | 0.00 | 30.54 | 0.116818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 222156.71 | 07-NOV-15:11 | 222156.71 | 07-NOV-15:11 | 0.00 | 0.00 | 0.00 |
December | 0.785529E+10 | 0.00 | 22.94 | 0.785529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 209806.89 | 02-DEC-14:52 | 209806.89 | 02-DEC-14:52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124478E+13 | 1969.60 | 0.119092E+13 | ||||||||||||
Minimum of Months | 0.308469E+10 | 0.00 | 10.21 | 0.308469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 188330.21 | 188330.21 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.314666E+12 | 0.00 | 409.06 | 0.286294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 429065.47 | 418009.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.186069E+09 | 0.00 | 14.00 | 0.186069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11108.81 | 20-JAN-13:51 | 11108.81 | 20-JAN-13:51 | 0.00 | 0.00 | 0.00 |
February | 0.116738E+09 | 0.00 | 9.00 | 0.116738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9341.83 | 18-FEB-13:51 | 9341.83 | 18-FEB-13:51 | 0.00 | 0.00 | 0.00 |
March | 0.831179E+09 | 0.00 | 45.50 | 0.831179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13400.28 | 13-MAR-15:11 | 13400.28 | 13-MAR-15:11 | 0.00 | 0.00 | 0.00 |
April | 0.978180E+09 | 0.00 | 55.50 | 0.978180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12340.17 | 20-APR-12:51 | 12340.17 | 20-APR-12:51 | 0.00 | 0.00 | 0.00 |
May | 0.480898E+10 | 0.00 | 189.00 | 0.480898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15537.24 | 31-MAY-18:01 | 15537.24 | 31-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.165963E+11 | 0.00 | 494.83 | 0.161447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22860.68 | 18-JUN-12:02 | 18822.12 | 26-JUN-15:11 | 0.00 | 0.00 | 0.00 |
July | 0.201229E+11 | 0.00 | 531.50 | 0.183967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25564.18 | 30-JUL-15:21 | 18135.04 | 16-JUL-12:51 | 0.00 | 0.00 | 0.00 |
August | 0.174853E+11 | 0.00 | 518.50 | 0.165466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19997.93 | 05-AUG-15:12 | 17958.51 | 16-AUG-15:11 | 0.00 | 0.00 | 0.00 |
September | 0.111561E+11 | 0.00 | 370.67 | 0.111561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16717.38 | 10-SEP-13:00 | 16717.38 | 10-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.160868E+10 | 0.00 | 76.83 | 0.160868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14550.72 | 11-OCT-15:11 | 14550.72 | 11-OCT-15:11 | 0.00 | 0.00 | 0.00 |
November | 0.463723E+09 | 0.00 | 26.17 | 0.463723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12345.16 | 06-NOV-13:12 | 12345.16 | 06-NOV-13:12 | 0.00 | 0.00 | 0.00 |
December | 0.266625E+09 | 0.00 | 16.83 | 0.266625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11612.35 | 01-DEC-14:00 | 11612.35 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.746208E+11 | 2348.33 | 0.715042E+11 | ||||||||||||
Minimum of Months | 0.116738E+09 | 0.00 | 9.00 | 0.116738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9341.83 | 9341.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.201229E+11 | 0.00 | 531.50 | 0.183967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25564.18 | 18822.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1322.51 | 1088.69 | 233.81 | 1394.92 | 642.48 | 0.00 | 0.00 | 744.00 |
February | 1252.04 | 995.65 | 256.39 | 1228.83 | 672.33 | 0.00 | 0.00 | 672.00 |
March | 940.33 | 621.58 | 318.75 | 828.68 | 540.64 | 0.00 | 0.00 | 744.00 |
April | 615.42 | 254.55 | 360.87 | 418.54 | 485.99 | 0.00 | 0.00 | 720.00 |
May | 559.21 | 107.46 | 451.75 | 414.06 | 292.38 | 0.00 | 0.00 | 744.00 |
June | 508.32 | 91.61 | 416.71 | 494.73 | 153.45 | 0.00 | 0.00 | 720.00 |
July | 525.10 | 89.35 | 435.75 | 532.20 | 137.95 | 0.00 | 0.00 | 744.00 |
August | 668.14 | 274.80 | 393.34 | 621.52 | 159.40 | 0.00 | 0.00 | 744.00 |
September | 877.92 | 493.51 | 384.41 | 885.67 | 248.89 | 0.00 | 0.00 | 720.00 |
October | 1036.80 | 734.77 | 302.02 | 1037.85 | 529.85 | 0.00 | 0.00 | 744.00 |
November | 1270.38 | 1013.35 | 257.03 | 1352.18 | 608.52 | 0.00 | 0.00 | 720.00 |
December | 1211.98 | 981.11 | 230.87 | 1269.61 | 719.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 897.00 | 559.72 | 337.27 | 871.25 | 431.32 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 508.32 | 89.35 | 230.87 | 414.06 | 137.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1322.51 | 1088.69 | 451.75 | 1394.92 | 719.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3724.09 | 3065.69 | 658.40 | 3891.37 | 1894.88 | 0.00 | 0.00 | 744.00 |
February | 3525.67 | 2803.68 | 721.98 | 3423.30 | 1988.59 | 0.00 | 0.00 | 672.00 |
March | 2647.90 | 1750.33 | 897.57 | 2305.79 | 1620.07 | 0.00 | 0.00 | 744.00 |
April | 1732.98 | 716.79 | 1016.18 | 1152.60 | 1467.23 | 0.00 | 0.00 | 720.00 |
May | 1574.70 | 302.61 | 1272.09 | 1147.10 | 862.48 | 0.00 | 0.00 | 744.00 |
June | 1431.38 | 257.96 | 1173.43 | 1384.41 | 438.34 | 0.00 | 0.00 | 720.00 |
July | 1478.65 | 251.62 | 1227.03 | 1490.26 | 394.92 | 0.00 | 0.00 | 744.00 |
August | 1881.44 | 773.82 | 1107.62 | 1741.69 | 456.89 | 0.00 | 0.00 | 744.00 |
September | 2472.16 | 1389.70 | 1082.47 | 2485.30 | 723.95 | 0.00 | 0.00 | 720.00 |
October | 2919.55 | 2069.07 | 850.48 | 2904.19 | 1568.66 | 0.00 | 0.00 | 744.00 |
November | 3577.31 | 2853.52 | 723.79 | 3775.19 | 1799.80 | 0.00 | 0.00 | 720.00 |
December | 3412.85 | 2762.73 | 650.12 | 3537.97 | 2131.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2525.89 | 1576.15 | 949.74 | 2431.09 | 1274.99 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1431.38 | 251.62 | 650.12 | 1147.10 | 394.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3724.09 | 3065.69 | 1272.09 | 3891.37 | 2131.52 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4837.80 | 3982.50 | 855.30 | 5169.90 | 2524.13 | 0.00 | 0.00 | 744.00 |
February | 4580.04 | 3642.14 | 937.90 | 4552.91 | 2671.36 | 0.00 | 0.00 | 672.00 |
March | 3439.78 | 2273.78 | 1166.00 | 3060.39 | 2203.22 | 0.00 | 0.00 | 744.00 |
April | 2251.23 | 931.15 | 1320.08 | 1519.48 | 2017.65 | 0.00 | 0.00 | 720.00 |
May | 2045.63 | 393.10 | 1652.52 | 1519.24 | 1173.98 | 0.00 | 0.00 | 744.00 |
June | 1859.45 | 335.10 | 1524.35 | 1861.21 | 583.34 | 0.00 | 0.00 | 720.00 |
July | 1920.85 | 326.86 | 1593.99 | 2002.94 | 522.97 | 0.00 | 0.00 | 744.00 |
August | 2444.10 | 1005.24 | 1438.86 | 2341.02 | 599.14 | 0.00 | 0.00 | 744.00 |
September | 3211.48 | 1805.29 | 1406.18 | 3321.72 | 950.85 | 0.00 | 0.00 | 720.00 |
October | 3792.66 | 2687.85 | 1104.82 | 3861.21 | 2115.16 | 0.00 | 0.00 | 744.00 |
November | 4647.13 | 3706.89 | 940.24 | 5015.78 | 2406.66 | 0.00 | 0.00 | 720.00 |
December | 4433.49 | 3588.94 | 844.54 | 4688.79 | 2869.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 3281.27 | 2047.51 | 1233.76 | 3235.55 | 1714.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1859.45 | 326.86 | 844.54 | 1519.24 | 522.97 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 4837.80 | 3982.50 | 1652.52 | 5169.90 | 2869.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 260.95 | 214.81 | 46.13 | 284.85 | 119.96 | 0.00 | 0.00 | 744.00 |
February | 247.05 | 196.46 | 50.59 | 250.29 | 129.05 | 0.00 | 0.00 | 672.00 |
March | 185.54 | 122.65 | 62.89 | 169.61 | 102.70 | 0.00 | 0.00 | 744.00 |
April | 121.43 | 50.23 | 71.20 | 86.64 | 92.52 | 0.00 | 0.00 | 720.00 |
May | 110.34 | 21.20 | 89.14 | 88.34 | 50.66 | 0.00 | 0.00 | 744.00 |
June | 100.30 | 18.08 | 82.22 | 107.41 | 21.97 | 0.00 | 0.00 | 720.00 |
July | 103.61 | 17.63 | 85.98 | 115.78 | 18.64 | 0.00 | 0.00 | 744.00 |
August | 131.83 | 54.22 | 77.61 | 133.07 | 22.16 | 0.00 | 0.00 | 744.00 |
September | 173.23 | 97.38 | 75.85 | 185.32 | 39.07 | 0.00 | 0.00 | 720.00 |
October | 204.57 | 144.98 | 59.59 | 212.91 | 96.83 | 0.00 | 0.00 | 744.00 |
November | 250.66 | 199.95 | 50.72 | 276.30 | 112.54 | 0.00 | 0.00 | 720.00 |
December | 239.14 | 193.59 | 45.55 | 257.40 | 138.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 176.99 | 110.44 | 66.55 | 180.27 | 78.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 100.30 | 17.63 | 45.55 | 86.64 | 18.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 260.95 | 214.81 | 89.14 | 284.85 | 138.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 168.90 | 107.05 | 61.85 | 122.67 | 250.83 | 0.00 | 0.00 | 744.00 |
February | 204.00 | 126.54 | 77.46 | 153.15 | 257.94 | 0.00 | 0.00 | 672.00 |
March | 237.93 | 131.08 | 106.86 | 203.48 | 192.68 | 0.00 | 0.00 | 744.00 |
April | 224.41 | 95.07 | 129.34 | 183.35 | 168.60 | 0.00 | 0.00 | 720.00 |
May | 274.34 | 96.88 | 177.46 | 273.45 | 91.58 | 0.00 | 0.00 | 744.00 |
June | 334.90 | 160.98 | 173.92 | 413.56 | 40.70 | 0.00 | 0.00 | 720.00 |
July | 272.58 | 99.51 | 173.07 | 339.82 | 34.58 | 0.00 | 0.00 | 744.00 |
August | 285.45 | 141.06 | 144.39 | 348.95 | 40.69 | 0.00 | 0.00 | 744.00 |
September | 254.02 | 122.22 | 131.79 | 291.67 | 73.29 | 0.00 | 0.00 | 720.00 |
October | 212.69 | 121.56 | 91.12 | 195.21 | 184.48 | 0.00 | 0.00 | 744.00 |
November | 174.66 | 106.09 | 68.57 | 134.74 | 225.09 | 0.00 | 0.00 | 720.00 |
December | 140.88 | 83.20 | 57.68 | 90.16 | 287.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 232.13 | 115.79 | 116.34 | 229.52 | 153.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 140.88 | 83.20 | 57.68 | 90.16 | 34.58 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 334.90 | 160.98 | 177.46 | 413.56 | 287.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 0.00 | 27.13 | 3.67 | 139.06 | 0.00 | 0.00 | 744.00 |
February | 34.10 | 0.00 | 34.10 | 4.14 | 144.47 | 0.00 | 0.00 | 672.00 |
March | 46.41 | 0.00 | 46.41 | 15.64 | 107.36 | 0.00 | 0.00 | 744.00 |
April | 58.33 | 0.38 | 57.96 | 25.14 | 92.02 | 0.00 | 0.00 | 720.00 |
May | 79.68 | 2.66 | 77.02 | 59.58 | 48.47 | 0.00 | 0.00 | 744.00 |
June | 87.36 | 9.75 | 77.60 | 96.32 | 21.78 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 5.65 | 77.21 | 97.50 | 19.07 | 0.00 | 0.00 | 744.00 |
August | 65.97 | 1.78 | 64.20 | 75.44 | 23.30 | 0.00 | 0.00 | 744.00 |
September | 55.25 | 0.04 | 55.20 | 56.44 | 41.20 | 0.00 | 0.00 | 720.00 |
October | 39.53 | 0.00 | 39.53 | 17.56 | 100.27 | 0.00 | 0.00 | 744.00 |
November | 30.00 | 0.00 | 30.00 | 6.20 | 123.96 | 0.00 | 0.00 | 720.00 |
December | 25.38 | 0.00 | 25.38 | 3.24 | 159.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 52.76 | 1.69 | 51.07 | 38.60 | 84.72 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.38 | 0.00 | 25.38 | 3.24 | 19.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 87.36 | 9.75 | 77.60 | 97.50 | 159.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 168.90 | 107.05 | 61.85 | 129.02 | 243.47 | 0.00 | 0.00 | 744.00 |
February | 204.00 | 126.54 | 77.46 | 159.46 | 252.11 | 0.00 | 0.00 | 672.00 |
March | 237.93 | 131.08 | 106.86 | 207.42 | 190.59 | 0.00 | 0.00 | 744.00 |
April | 224.41 | 95.07 | 129.34 | 185.33 | 167.65 | 0.00 | 0.00 | 720.00 |
May | 274.34 | 96.88 | 177.46 | 271.81 | 92.90 | 0.00 | 0.00 | 744.00 |
June | 334.90 | 160.98 | 173.92 | 409.76 | 44.06 | 0.00 | 0.00 | 720.00 |
July | 272.58 | 99.51 | 173.07 | 336.60 | 37.60 | 0.00 | 0.00 | 744.00 |
August | 285.45 | 141.06 | 144.39 | 347.34 | 43.98 | 0.00 | 0.00 | 744.00 |
September | 254.02 | 122.22 | 131.79 | 292.15 | 76.02 | 0.00 | 0.00 | 720.00 |
October | 212.69 | 121.56 | 91.12 | 199.33 | 182.50 | 0.00 | 0.00 | 744.00 |
November | 174.66 | 106.09 | 68.57 | 141.20 | 219.36 | 0.00 | 0.00 | 720.00 |
December | 140.88 | 83.20 | 57.68 | 95.59 | 281.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 232.13 | 115.79 | 116.34 | 231.56 | 152.08 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 140.88 | 83.20 | 57.68 | 95.59 | 37.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 334.90 | 160.98 | 177.46 | 409.76 | 281.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.72 | 171.82 | 36.90 | 216.56 | 119.69 | 0.00 | 0.00 | 744.00 |
February | 197.60 | 157.13 | 40.46 | 191.25 | 121.38 | 0.00 | 0.00 | 672.00 |
March | 148.40 | 98.10 | 50.30 | 128.94 | 98.41 | 0.00 | 0.00 | 744.00 |
April | 97.13 | 40.17 | 56.95 | 63.73 | 91.42 | 0.00 | 0.00 | 720.00 |
May | 88.25 | 16.96 | 71.29 | 59.58 | 58.38 | 0.00 | 0.00 | 744.00 |
June | 80.22 | 14.46 | 65.77 | 73.62 | 32.59 | 0.00 | 0.00 | 720.00 |
July | 82.87 | 14.10 | 68.77 | 79.64 | 30.11 | 0.00 | 0.00 | 744.00 |
August | 105.45 | 43.37 | 62.08 | 94.60 | 34.16 | 0.00 | 0.00 | 744.00 |
September | 138.55 | 77.89 | 60.67 | 136.96 | 50.27 | 0.00 | 0.00 | 720.00 |
October | 163.63 | 115.96 | 47.67 | 161.84 | 99.93 | 0.00 | 0.00 | 744.00 |
November | 200.49 | 159.93 | 40.57 | 211.56 | 112.43 | 0.00 | 0.00 | 720.00 |
December | 191.27 | 154.84 | 36.44 | 197.63 | 129.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 141.56 | 88.34 | 53.23 | 134.34 | 81.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 80.22 | 14.10 | 36.44 | 59.58 | 30.11 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 208.72 | 171.82 | 71.29 | 216.56 | 129.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.70 | 0.00 | 21.70 | 2.75 | 113.90 | 0.00 | 0.00 | 744.00 |
February | 27.28 | 0.00 | 27.28 | 3.34 | 117.59 | 0.00 | 0.00 | 672.00 |
March | 37.13 | 0.00 | 37.13 | 13.12 | 86.94 | 0.00 | 0.00 | 744.00 |
April | 46.67 | 0.30 | 46.37 | 20.65 | 75.32 | 0.00 | 0.00 | 720.00 |
May | 63.76 | 2.13 | 61.62 | 49.92 | 38.63 | 0.00 | 0.00 | 744.00 |
June | 69.89 | 7.80 | 62.09 | 81.44 | 16.30 | 0.00 | 0.00 | 720.00 |
July | 66.30 | 4.52 | 61.78 | 81.54 | 14.41 | 0.00 | 0.00 | 744.00 |
August | 52.78 | 1.42 | 51.36 | 63.96 | 17.38 | 0.00 | 0.00 | 744.00 |
September | 44.20 | 0.03 | 44.17 | 48.10 | 31.55 | 0.00 | 0.00 | 720.00 |
October | 31.62 | 0.00 | 31.62 | 15.17 | 80.74 | 0.00 | 0.00 | 744.00 |
November | 24.01 | 0.00 | 24.01 | 4.97 | 101.15 | 0.00 | 0.00 | 720.00 |
December | 20.31 | 0.00 | 20.31 | 2.43 | 131.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 42.22 | 1.35 | 40.86 | 32.45 | 68.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 20.31 | 0.00 | 20.31 | 2.43 | 14.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.89 | 7.80 | 62.09 | 81.54 | 131.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.12 | 96.72 | 61.40 | 104.52 | 246.30 | 0.00 | 0.00 | 744.00 |
February | 211.94 | 134.13 | 77.80 | 161.82 | 256.82 | 0.00 | 0.00 | 672.00 |
March | 255.31 | 149.03 | 106.28 | 219.47 | 188.61 | 0.00 | 0.00 | 744.00 |
April | 260.64 | 126.95 | 133.69 | 224.26 | 164.33 | 0.00 | 0.00 | 720.00 |
May | 305.50 | 127.88 | 177.63 | 307.97 | 85.77 | 0.00 | 0.00 | 744.00 |
June | 371.71 | 195.05 | 176.66 | 457.49 | 36.68 | 0.00 | 0.00 | 720.00 |
July | 337.41 | 160.31 | 177.10 | 419.93 | 32.31 | 0.00 | 0.00 | 744.00 |
August | 341.21 | 187.98 | 153.22 | 415.90 | 39.03 | 0.00 | 0.00 | 744.00 |
September | 284.41 | 154.61 | 129.80 | 324.15 | 69.02 | 0.00 | 0.00 | 720.00 |
October | 205.77 | 112.85 | 92.92 | 181.45 | 180.47 | 0.00 | 0.00 | 744.00 |
November | 159.69 | 90.00 | 69.70 | 110.86 | 223.05 | 0.00 | 0.00 | 720.00 |
December | 138.52 | 79.84 | 58.69 | 83.51 | 285.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 252.67 | 134.54 | 118.13 | 251.37 | 150.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 138.52 | 79.84 | 58.69 | 83.51 | 32.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 371.71 | 195.05 | 177.63 | 457.49 | 285.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 260.95 | 214.81 | 46.13 | 284.27 | 119.48 | 0.00 | 0.00 | 744.00 |
February | 247.05 | 196.46 | 50.59 | 249.17 | 128.48 | 0.00 | 0.00 | 672.00 |
March | 185.54 | 122.65 | 62.89 | 168.16 | 102.35 | 0.00 | 0.00 | 744.00 |
April | 121.43 | 50.23 | 71.20 | 85.17 | 92.50 | 0.00 | 0.00 | 720.00 |
May | 110.34 | 21.20 | 89.14 | 86.92 | 50.66 | 0.00 | 0.00 | 744.00 |
June | 100.30 | 18.08 | 82.22 | 106.35 | 21.84 | 0.00 | 0.00 | 720.00 |
July | 103.61 | 17.63 | 85.98 | 114.26 | 18.69 | 0.00 | 0.00 | 744.00 |
August | 131.83 | 54.22 | 77.61 | 131.66 | 22.02 | 0.00 | 0.00 | 744.00 |
September | 173.23 | 97.38 | 75.85 | 184.28 | 38.88 | 0.00 | 0.00 | 720.00 |
October | 204.57 | 144.98 | 59.59 | 212.15 | 96.35 | 0.00 | 0.00 | 744.00 |
November | 250.66 | 199.95 | 50.72 | 275.93 | 111.92 | 0.00 | 0.00 | 720.00 |
December | 239.14 | 193.59 | 45.55 | 256.90 | 138.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 176.99 | 110.44 | 66.55 | 179.21 | 78.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 100.30 | 17.63 | 45.55 | 85.17 | 18.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 260.95 | 214.81 | 89.14 | 284.27 | 138.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 0.00 | 27.13 | 3.39 | 138.59 | 0.00 | 0.00 | 744.00 |
February | 34.10 | 0.00 | 34.10 | 3.61 | 144.46 | 0.00 | 0.00 | 672.00 |
March | 46.41 | 0.00 | 46.41 | 14.62 | 107.27 | 0.00 | 0.00 | 744.00 |
April | 58.33 | 0.38 | 57.96 | 23.82 | 92.11 | 0.00 | 0.00 | 720.00 |
May | 79.68 | 2.66 | 77.02 | 58.46 | 48.17 | 0.00 | 0.00 | 744.00 |
June | 87.36 | 9.75 | 77.60 | 94.37 | 21.17 | 0.00 | 0.00 | 720.00 |
July | 82.86 | 5.65 | 77.21 | 95.01 | 18.93 | 0.00 | 0.00 | 744.00 |
August | 65.97 | 1.78 | 64.20 | 73.24 | 22.91 | 0.00 | 0.00 | 744.00 |
September | 55.25 | 0.04 | 55.20 | 55.37 | 40.62 | 0.00 | 0.00 | 720.00 |
October | 39.53 | 0.00 | 39.53 | 17.01 | 99.54 | 0.00 | 0.00 | 744.00 |
November | 30.00 | 0.00 | 30.00 | 5.82 | 123.11 | 0.00 | 0.00 | 720.00 |
December | 25.38 | 0.00 | 25.38 | 2.99 | 159.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 52.76 | 1.69 | 51.07 | 37.50 | 84.35 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.38 | 0.00 | 25.38 | 2.99 | 18.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 87.36 | 9.75 | 77.60 | 95.01 | 159.16 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.12 | 96.72 | 61.40 | 108.66 | 236.12 | 0.00 | 0.00 | 744.00 |
February | 211.94 | 134.13 | 77.80 | 165.61 | 248.29 | 0.00 | 0.00 | 672.00 |
March | 255.31 | 149.03 | 106.28 | 223.18 | 185.71 | 0.00 | 0.00 | 744.00 |
April | 260.64 | 126.95 | 133.69 | 226.25 | 163.14 | 0.00 | 0.00 | 720.00 |
May | 305.50 | 127.88 | 177.63 | 307.29 | 86.87 | 0.00 | 0.00 | 744.00 |
June | 371.71 | 195.05 | 176.66 | 452.42 | 39.81 | 0.00 | 0.00 | 720.00 |
July | 337.41 | 160.31 | 177.10 | 415.01 | 35.40 | 0.00 | 0.00 | 744.00 |
August | 341.21 | 187.98 | 153.22 | 412.99 | 42.08 | 0.00 | 0.00 | 744.00 |
September | 284.41 | 154.61 | 129.80 | 324.80 | 71.00 | 0.00 | 0.00 | 720.00 |
October | 205.77 | 112.85 | 92.92 | 185.90 | 177.78 | 0.00 | 0.00 | 744.00 |
November | 159.69 | 90.00 | 69.70 | 115.38 | 214.94 | 0.00 | 0.00 | 720.00 |
December | 138.52 | 79.84 | 58.69 | 87.18 | 276.66 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 252.67 | 134.54 | 118.13 | 252.46 | 147.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 138.52 | 79.84 | 58.69 | 87.18 | 35.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 371.71 | 195.05 | 177.63 | 452.42 | 276.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.36 | 0.00 | 34.36 | 3.94 | 181.10 | 0.00 | 0.00 | 744.00 |
February | 43.18 | 0.00 | 43.18 | 4.78 | 185.15 | 0.00 | 0.00 | 672.00 |
March | 58.77 | 0.00 | 58.77 | 20.40 | 136.90 | 0.00 | 0.00 | 744.00 |
April | 73.88 | 0.48 | 73.40 | 34.01 | 116.22 | 0.00 | 0.00 | 720.00 |
May | 100.91 | 3.37 | 97.54 | 82.48 | 59.59 | 0.00 | 0.00 | 744.00 |
June | 110.63 | 12.35 | 98.28 | 128.68 | 26.90 | 0.00 | 0.00 | 720.00 |
July | 104.94 | 7.15 | 97.79 | 127.10 | 25.18 | 0.00 | 0.00 | 744.00 |
August | 83.55 | 2.25 | 81.30 | 100.15 | 29.58 | 0.00 | 0.00 | 744.00 |
September | 69.96 | 0.05 | 69.91 | 74.92 | 52.20 | 0.00 | 0.00 | 720.00 |
October | 50.06 | 0.00 | 50.06 | 22.99 | 128.88 | 0.00 | 0.00 | 744.00 |
November | 38.00 | 0.00 | 38.00 | 7.31 | 160.29 | 0.00 | 0.00 | 720.00 |
December | 32.14 | 0.00 | 32.14 | 3.54 | 206.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.82 | 2.14 | 64.68 | 51.12 | 108.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.14 | 0.00 | 32.14 | 3.54 | 25.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.63 | 12.35 | 98.28 | 128.68 | 206.04 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.66 | 0.00 | 12.66 | 1.45 | 66.76 | 0.00 | 0.00 | 744.00 |
February | 15.92 | 0.00 | 15.92 | 1.76 | 68.25 | 0.00 | 0.00 | 672.00 |
March | 21.67 | 0.00 | 21.66 | 7.52 | 50.47 | 0.00 | 0.00 | 744.00 |
April | 27.23 | 0.18 | 27.06 | 12.54 | 42.84 | 0.00 | 0.00 | 720.00 |
May | 37.20 | 1.24 | 35.96 | 30.41 | 21.97 | 0.00 | 0.00 | 744.00 |
June | 40.78 | 4.55 | 36.23 | 47.44 | 9.92 | 0.00 | 0.00 | 720.00 |
July | 38.68 | 2.64 | 36.05 | 46.85 | 9.28 | 0.00 | 0.00 | 744.00 |
August | 30.80 | 0.83 | 29.97 | 36.92 | 10.91 | 0.00 | 0.00 | 744.00 |
September | 25.79 | 0.02 | 25.77 | 27.62 | 19.24 | 0.00 | 0.00 | 720.00 |
October | 18.45 | 0.00 | 18.45 | 8.47 | 47.51 | 0.00 | 0.00 | 744.00 |
November | 14.01 | 0.00 | 14.01 | 2.69 | 59.09 | 0.00 | 0.00 | 720.00 |
December | 11.85 | 0.00 | 11.85 | 1.31 | 75.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 24.63 | 0.79 | 23.84 | 18.85 | 40.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.85 | 0.00 | 11.85 | 1.31 | 9.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 40.78 | 4.55 | 36.23 | 47.44 | 75.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 121.76 | 100.23 | 21.53 | 134.54 | 55.72 | 0.00 | 0.00 | 744.00 |
February | 115.27 | 91.67 | 23.60 | 118.43 | 59.71 | 0.00 | 0.00 | 672.00 |
March | 86.57 | 57.23 | 29.35 | 80.44 | 47.90 | 0.00 | 0.00 | 744.00 |
April | 56.66 | 23.44 | 33.22 | 41.71 | 42.74 | 0.00 | 0.00 | 720.00 |
May | 51.48 | 9.89 | 41.59 | 43.43 | 23.21 | 0.00 | 0.00 | 744.00 |
June | 46.80 | 8.43 | 38.36 | 51.76 | 10.88 | 0.00 | 0.00 | 720.00 |
July | 48.34 | 8.23 | 40.12 | 54.70 | 9.90 | 0.00 | 0.00 | 744.00 |
August | 61.51 | 25.30 | 36.21 | 63.46 | 11.19 | 0.00 | 0.00 | 744.00 |
September | 80.83 | 45.44 | 35.39 | 87.88 | 18.97 | 0.00 | 0.00 | 720.00 |
October | 95.45 | 67.65 | 27.81 | 100.75 | 45.53 | 0.00 | 0.00 | 744.00 |
November | 116.96 | 93.30 | 23.66 | 130.58 | 52.27 | 0.00 | 0.00 | 720.00 |
December | 111.58 | 90.33 | 21.26 | 121.48 | 64.31 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 82.58 | 51.53 | 31.05 | 85.58 | 36.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 46.80 | 8.23 | 21.26 | 41.71 | 9.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 121.76 | 100.23 | 41.59 | 134.54 | 64.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 330.48 | 272.05 | 58.43 | 365.16 | 151.24 | 0.00 | 0.00 | 744.00 |
February | 312.87 | 248.80 | 64.07 | 321.44 | 162.06 | 0.00 | 0.00 | 672.00 |
March | 234.97 | 155.32 | 79.65 | 218.34 | 130.01 | 0.00 | 0.00 | 744.00 |
April | 153.78 | 63.61 | 90.18 | 113.21 | 116.02 | 0.00 | 0.00 | 720.00 |
May | 139.74 | 26.85 | 112.89 | 117.88 | 62.99 | 0.00 | 0.00 | 744.00 |
June | 127.02 | 22.89 | 104.13 | 140.49 | 29.52 | 0.00 | 0.00 | 720.00 |
July | 131.22 | 22.33 | 108.89 | 148.46 | 26.88 | 0.00 | 0.00 | 744.00 |
August | 166.96 | 68.67 | 98.29 | 172.25 | 30.37 | 0.00 | 0.00 | 744.00 |
September | 219.38 | 123.32 | 96.06 | 238.51 | 51.49 | 0.00 | 0.00 | 720.00 |
October | 259.08 | 183.61 | 75.47 | 273.46 | 123.58 | 0.00 | 0.00 | 744.00 |
November | 317.45 | 253.22 | 64.23 | 354.42 | 141.87 | 0.00 | 0.00 | 720.00 |
December | 302.86 | 245.16 | 57.69 | 329.72 | 174.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 224.15 | 139.87 | 84.28 | 232.28 | 99.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 127.02 | 22.33 | 57.69 | 113.21 | 26.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 330.48 | 272.05 | 112.89 | 365.16 | 174.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 261.16 | 214.99 | 46.17 | 284.38 | 119.72 | 0.00 | 0.00 | 744.00 |
February | 247.25 | 196.62 | 50.63 | 249.45 | 129.44 | 0.00 | 0.00 | 672.00 |
March | 185.69 | 122.75 | 62.94 | 169.15 | 102.76 | 0.00 | 0.00 | 744.00 |
April | 121.53 | 50.27 | 71.26 | 86.17 | 92.80 | 0.00 | 0.00 | 720.00 |
May | 110.43 | 21.22 | 89.21 | 87.41 | 51.01 | 0.00 | 0.00 | 744.00 |
June | 100.38 | 18.09 | 82.29 | 106.54 | 21.93 | 0.00 | 0.00 | 720.00 |
July | 103.69 | 17.65 | 86.05 | 115.19 | 18.44 | 0.00 | 0.00 | 744.00 |
August | 131.94 | 54.27 | 77.68 | 132.37 | 22.08 | 0.00 | 0.00 | 744.00 |
September | 173.37 | 97.46 | 75.91 | 184.88 | 38.86 | 0.00 | 0.00 | 720.00 |
October | 204.74 | 145.10 | 59.64 | 212.39 | 96.69 | 0.00 | 0.00 | 744.00 |
November | 250.87 | 200.11 | 50.76 | 275.52 | 112.53 | 0.00 | 0.00 | 720.00 |
December | 239.34 | 193.74 | 45.59 | 256.56 | 139.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 177.14 | 110.53 | 66.60 | 179.61 | 78.51 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 100.38 | 17.65 | 45.59 | 86.17 | 18.44 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 261.16 | 214.99 | 89.21 | 284.38 | 139.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.04 | 107.14 | 61.90 | 122.30 | 249.75 | 0.00 | 0.00 | 744.00 |
February | 204.17 | 126.65 | 77.52 | 152.20 | 258.39 | 0.00 | 0.00 | 672.00 |
March | 238.13 | 131.18 | 106.94 | 202.36 | 192.63 | 0.00 | 0.00 | 744.00 |
April | 224.60 | 95.15 | 129.45 | 181.74 | 168.89 | 0.00 | 0.00 | 720.00 |
May | 274.57 | 96.96 | 177.61 | 270.85 | 91.99 | 0.00 | 0.00 | 744.00 |
June | 335.18 | 161.11 | 174.06 | 411.06 | 40.62 | 0.00 | 0.00 | 720.00 |
July | 272.80 | 99.59 | 173.22 | 338.11 | 34.20 | 0.00 | 0.00 | 744.00 |
August | 285.69 | 141.17 | 144.51 | 346.77 | 40.53 | 0.00 | 0.00 | 744.00 |
September | 254.22 | 122.33 | 131.90 | 290.39 | 72.83 | 0.00 | 0.00 | 720.00 |
October | 212.86 | 121.66 | 91.20 | 194.28 | 184.01 | 0.00 | 0.00 | 744.00 |
November | 174.80 | 106.17 | 68.63 | 134.00 | 224.80 | 0.00 | 0.00 | 720.00 |
December | 141.00 | 83.27 | 57.73 | 89.94 | 287.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 232.32 | 115.89 | 116.43 | 228.17 | 153.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 141.00 | 83.27 | 57.73 | 89.94 | 34.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 335.18 | 161.11 | 177.61 | 411.06 | 287.68 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.15 | 0.00 | 27.15 | 3.79 | 138.00 | 0.00 | 0.00 | 744.00 |
February | 34.12 | 0.00 | 34.12 | 4.12 | 144.26 | 0.00 | 0.00 | 672.00 |
March | 46.45 | 0.00 | 46.44 | 15.43 | 107.36 | 0.00 | 0.00 | 744.00 |
April | 58.38 | 0.38 | 58.00 | 24.55 | 92.26 | 0.00 | 0.00 | 720.00 |
May | 79.75 | 2.67 | 77.08 | 58.01 | 49.21 | 0.00 | 0.00 | 744.00 |
June | 87.43 | 9.76 | 77.67 | 94.84 | 22.46 | 0.00 | 0.00 | 720.00 |
July | 82.93 | 5.65 | 77.28 | 96.54 | 19.40 | 0.00 | 0.00 | 744.00 |
August | 66.03 | 1.78 | 64.25 | 74.25 | 23.89 | 0.00 | 0.00 | 744.00 |
September | 55.29 | 0.04 | 55.25 | 55.81 | 41.69 | 0.00 | 0.00 | 720.00 |
October | 39.56 | 0.00 | 39.56 | 17.40 | 100.23 | 0.00 | 0.00 | 744.00 |
November | 30.03 | 0.00 | 30.03 | 6.19 | 123.35 | 0.00 | 0.00 | 720.00 |
December | 25.40 | 0.00 | 25.40 | 3.36 | 159.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 52.81 | 1.69 | 51.11 | 38.05 | 84.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.40 | 0.00 | 25.40 | 3.36 | 19.40 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 87.43 | 9.76 | 77.67 | 96.54 | 159.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 169.04 | 107.14 | 61.90 | 129.41 | 242.16 | 0.00 | 0.00 | 744.00 |
February | 204.17 | 126.65 | 77.52 | 159.13 | 252.40 | 0.00 | 0.00 | 672.00 |
March | 238.13 | 131.18 | 106.94 | 206.36 | 190.67 | 0.00 | 0.00 | 744.00 |
April | 224.60 | 95.15 | 129.45 | 183.65 | 168.05 | 0.00 | 0.00 | 720.00 |
May | 274.57 | 96.96 | 177.61 | 268.35 | 94.21 | 0.00 | 0.00 | 744.00 |
June | 335.18 | 161.11 | 174.06 | 406.47 | 45.27 | 0.00 | 0.00 | 720.00 |
July | 272.80 | 99.59 | 173.22 | 334.39 | 38.11 | 0.00 | 0.00 | 744.00 |
August | 285.69 | 141.17 | 144.51 | 344.68 | 44.96 | 0.00 | 0.00 | 744.00 |
September | 254.22 | 122.33 | 131.90 | 290.41 | 76.77 | 0.00 | 0.00 | 720.00 |
October | 212.86 | 121.66 | 91.20 | 198.48 | 182.25 | 0.00 | 0.00 | 744.00 |
November | 174.80 | 106.17 | 68.63 | 141.07 | 218.80 | 0.00 | 0.00 | 720.00 |
December | 141.00 | 83.27 | 57.73 | 95.94 | 281.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 232.32 | 115.89 | 116.43 | 230.16 | 152.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 141.00 | 83.27 | 57.73 | 95.94 | 38.11 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 335.18 | 161.11 | 177.61 | 406.47 | 281.08 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 383.02 | 315.30 | 67.72 | 408.42 | 182.16 | 0.00 | 0.00 | 744.00 |
February | 362.61 | 288.36 | 74.26 | 358.95 | 195.33 | 0.00 | 0.00 | 672.00 |
March | 272.34 | 180.02 | 92.31 | 244.52 | 153.42 | 0.33 | 0.00 | 744.00 |
April | 178.24 | 73.72 | 104.51 | 125.05 | 137.60 | 0.00 | 0.00 | 720.00 |
May | 161.96 | 31.12 | 130.83 | 129.59 | 74.06 | 0.00 | 0.00 | 744.00 |
June | 147.22 | 26.53 | 120.69 | 161.21 | 30.37 | 0.00 | 0.00 | 720.00 |
July | 152.08 | 25.88 | 126.20 | 172.38 | 25.90 | 0.00 | 0.00 | 744.00 |
August | 193.51 | 79.59 | 113.92 | 196.85 | 31.19 | 0.00 | 0.00 | 744.00 |
September | 254.26 | 142.93 | 111.33 | 270.91 | 56.89 | 0.00 | 0.00 | 720.00 |
October | 300.27 | 212.80 | 87.47 | 308.09 | 145.07 | 0.00 | 0.00 | 744.00 |
November | 367.93 | 293.48 | 74.44 | 396.73 | 171.12 | 0.00 | 0.00 | 720.00 |
December | 351.01 | 284.15 | 66.86 | 367.25 | 212.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 259.79 | 162.11 | 97.68 | 261.12 | 117.52 | 0.33 | 0.00 | 8760.00 |
Minimum of Months | 147.22 | 25.88 | 66.86 | 125.05 | 25.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 383.02 | 315.30 | 130.83 | 408.42 | 212.24 | 0.33 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.04 | 0.00 | 190.04 | 9.01 | 1192.31 | 0.00 | 0.00 | 744.00 |
February | 238.86 | 0.00 | 238.86 | 12.55 | 1236.40 | 0.00 | 0.00 | 672.00 |
March | 325.11 | 0.02 | 325.09 | 72.95 | 948.14 | 0.00 | 0.00 | 744.00 |
April | 408.66 | 2.65 | 406.01 | 126.60 | 839.93 | 0.00 | 0.00 | 720.00 |
May | 558.23 | 18.66 | 539.56 | 352.11 | 461.57 | 0.00 | 0.00 | 744.00 |
June | 611.97 | 68.33 | 543.64 | 615.55 | 212.86 | 0.00 | 0.00 | 720.00 |
July | 580.47 | 39.55 | 540.93 | 618.62 | 198.03 | 0.00 | 0.00 | 744.00 |
August | 462.16 | 12.44 | 449.72 | 476.03 | 233.92 | 0.00 | 0.00 | 744.00 |
September | 387.02 | 0.30 | 386.72 | 352.69 | 381.45 | 0.00 | 0.00 | 720.00 |
October | 276.90 | 0.00 | 276.90 | 87.88 | 885.99 | 0.00 | 0.00 | 744.00 |
November | 210.20 | 0.00 | 210.20 | 23.94 | 1090.10 | 0.00 | 0.00 | 720.00 |
December | 177.81 | 0.00 | 177.81 | 9.73 | 1354.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 369.63 | 11.86 | 357.77 | 231.04 | 750.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 177.81 | 0.00 | 177.81 | 9.01 | 198.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 611.97 | 68.33 | 543.64 | 618.62 | 1354.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 190.04 | 0.00 | 190.04 | 6.84 | 1244.01 | 0.00 | 0.00 | 744.00 |
February | 238.86 | 0.00 | 238.86 | 10.08 | 1291.20 | 0.00 | 0.00 | 672.00 |
March | 325.11 | 0.02 | 325.09 | 64.43 | 994.97 | 0.00 | 0.00 | 744.00 |
April | 408.66 | 2.65 | 406.01 | 114.41 | 881.95 | 0.00 | 0.00 | 720.00 |
May | 558.23 | 18.66 | 539.56 | 333.50 | 485.08 | 0.00 | 0.00 | 744.00 |
June | 611.97 | 68.33 | 543.64 | 595.22 | 225.82 | 0.00 | 0.00 | 720.00 |
July | 580.47 | 39.55 | 540.93 | 598.90 | 211.31 | 0.00 | 0.00 | 744.00 |
August | 462.16 | 12.44 | 449.72 | 459.32 | 248.70 | 0.00 | 0.00 | 744.00 |
September | 387.02 | 0.30 | 386.72 | 338.85 | 400.58 | 0.00 | 0.00 | 720.00 |
October | 276.90 | 0.00 | 276.90 | 79.45 | 924.10 | 0.00 | 0.00 | 744.00 |
November | 210.20 | 0.00 | 210.20 | 20.98 | 1138.90 | 0.00 | 0.00 | 720.00 |
December | 177.81 | 0.00 | 177.81 | 7.78 | 1410.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 369.63 | 11.86 | 357.77 | 220.34 | 785.32 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 177.81 | 0.00 | 177.81 | 6.84 | 211.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 611.97 | 68.33 | 543.64 | 598.90 | 1410.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.15 | 0.00 | 27.15 | 1.56 | 174.36 | 0.00 | 0.00 | 744.00 |
February | 34.12 | 0.00 | 34.12 | 1.76 | 183.87 | 0.00 | 0.00 | 672.00 |
March | 46.45 | 0.00 | 46.44 | 10.60 | 142.62 | 0.00 | 0.00 | 744.00 |
April | 58.38 | 0.38 | 58.00 | 17.89 | 126.66 | 0.00 | 0.00 | 720.00 |
May | 79.75 | 2.67 | 77.08 | 54.51 | 70.97 | 0.00 | 0.00 | 744.00 |
June | 87.43 | 9.76 | 77.67 | 92.67 | 34.67 | 0.00 | 0.00 | 720.00 |
July | 82.93 | 5.65 | 77.28 | 93.34 | 32.66 | 0.00 | 0.00 | 744.00 |
August | 66.03 | 1.78 | 64.25 | 72.84 | 36.76 | 0.00 | 0.00 | 744.00 |
September | 55.29 | 0.04 | 55.25 | 54.95 | 57.32 | 0.00 | 0.00 | 720.00 |
October | 39.56 | 0.00 | 39.56 | 13.90 | 130.80 | 0.00 | 0.00 | 744.00 |
November | 30.03 | 0.00 | 30.03 | 4.06 | 160.04 | 0.00 | 0.00 | 720.00 |
December | 25.40 | 0.00 | 25.40 | 1.51 | 199.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 52.81 | 1.69 | 51.11 | 35.16 | 112.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 25.40 | 0.00 | 25.40 | 1.51 | 32.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 87.43 | 9.76 | 77.67 | 93.34 | 199.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.48 | 193.59 | 122.89 | 200.72 | 598.73 | 0.00 | 0.00 | 744.00 |
February | 424.19 | 268.47 | 155.73 | 311.88 | 638.00 | 0.00 | 0.00 | 672.00 |
March | 511.01 | 298.29 | 212.72 | 422.35 | 497.84 | 0.00 | 0.00 | 744.00 |
April | 521.66 | 254.09 | 267.57 | 423.31 | 453.25 | 0.00 | 0.00 | 720.00 |
May | 611.46 | 255.94 | 355.52 | 595.27 | 257.29 | 0.00 | 0.00 | 744.00 |
June | 743.98 | 390.40 | 353.58 | 897.17 | 131.32 | 0.00 | 0.00 | 720.00 |
July | 675.32 | 320.85 | 354.47 | 823.57 | 124.09 | 0.00 | 0.00 | 744.00 |
August | 682.92 | 376.25 | 306.68 | 823.17 | 137.06 | 0.00 | 0.00 | 744.00 |
September | 569.24 | 309.45 | 259.78 | 645.68 | 205.15 | 0.00 | 0.00 | 720.00 |
October | 411.86 | 225.87 | 185.99 | 355.12 | 470.23 | 0.00 | 0.00 | 744.00 |
November | 319.63 | 180.13 | 139.50 | 213.48 | 561.24 | 0.00 | 0.00 | 720.00 |
December | 277.25 | 159.79 | 117.46 | 157.54 | 698.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 505.72 | 269.28 | 236.44 | 489.95 | 396.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 277.25 | 159.79 | 117.46 | 157.54 | 124.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 743.98 | 390.40 | 355.52 | 897.17 | 698.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 261.16 | 214.99 | 46.17 | 280.64 | 144.79 | 0.00 | 0.00 | 744.00 |
February | 247.25 | 196.62 | 50.63 | 243.67 | 158.17 | 0.00 | 0.00 | 672.00 |
March | 185.69 | 122.75 | 62.94 | 163.48 | 133.54 | 0.00 | 0.00 | 744.00 |
April | 121.53 | 50.27 | 71.26 | 79.43 | 126.40 | 0.00 | 0.00 | 720.00 |
May | 110.43 | 21.22 | 89.21 | 83.05 | 75.10 | 0.00 | 0.00 | 744.00 |
June | 100.38 | 18.09 | 82.29 | 102.39 | 38.25 | 0.00 | 0.00 | 720.00 |
July | 103.69 | 17.65 | 86.05 | 110.36 | 35.14 | 0.00 | 0.00 | 744.00 |
August | 131.94 | 54.27 | 77.68 | 129.40 | 38.11 | 0.00 | 0.00 | 744.00 |
September | 173.37 | 97.46 | 75.91 | 184.00 | 57.39 | 0.00 | 0.00 | 720.00 |
October | 204.74 | 145.10 | 59.64 | 210.72 | 124.94 | 0.00 | 0.00 | 744.00 |
November | 250.87 | 200.11 | 50.76 | 272.42 | 139.68 | 0.00 | 0.00 | 720.00 |
December | 239.34 | 193.74 | 45.59 | 251.72 | 168.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 177.14 | 110.53 | 66.60 | 175.56 | 103.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 100.38 | 17.65 | 45.59 | 79.43 | 35.14 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 261.16 | 214.99 | 89.21 | 280.64 | 168.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.38 | 0.00 | 34.38 | 1.78 | 199.84 | 0.00 | 0.00 | 744.00 |
February | 43.22 | 0.00 | 43.22 | 2.40 | 204.97 | 0.00 | 0.00 | 672.00 |
March | 58.82 | 0.00 | 58.82 | 14.43 | 154.03 | 0.00 | 0.00 | 744.00 |
April | 73.94 | 0.48 | 73.46 | 25.51 | 135.60 | 0.00 | 0.00 | 720.00 |
May | 101.00 | 3.38 | 97.62 | 67.17 | 74.94 | 0.00 | 0.00 | 744.00 |
June | 110.72 | 12.36 | 98.36 | 113.63 | 35.59 | 0.00 | 0.00 | 720.00 |
July | 105.02 | 7.16 | 97.87 | 113.98 | 33.05 | 0.00 | 0.00 | 744.00 |
August | 83.62 | 2.25 | 81.37 | 87.09 | 39.49 | 0.00 | 0.00 | 744.00 |
September | 70.02 | 0.05 | 69.97 | 64.06 | 64.30 | 0.00 | 0.00 | 720.00 |
October | 50.10 | 0.00 | 50.10 | 16.18 | 146.82 | 0.00 | 0.00 | 744.00 |
November | 38.03 | 0.00 | 38.03 | 4.33 | 181.93 | 0.00 | 0.00 | 720.00 |
December | 32.17 | 0.00 | 32.17 | 1.87 | 224.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 66.88 | 2.15 | 64.73 | 42.93 | 124.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 32.17 | 0.00 | 32.17 | 1.78 | 33.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 110.72 | 12.36 | 98.36 | 113.98 | 224.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.76 | 0.00 | 30.76 | 1.60 | 178.79 | 0.00 | 0.00 | 744.00 |
February | 38.67 | 0.00 | 38.67 | 2.15 | 183.38 | 0.00 | 0.00 | 672.00 |
March | 52.63 | 0.00 | 52.62 | 12.91 | 137.81 | 0.00 | 0.00 | 744.00 |
April | 66.15 | 0.43 | 65.72 | 22.82 | 121.32 | 0.00 | 0.00 | 720.00 |
May | 90.36 | 3.02 | 87.34 | 60.10 | 67.05 | 0.00 | 0.00 | 744.00 |
June | 99.06 | 11.06 | 88.00 | 101.67 | 31.84 | 0.00 | 0.00 | 720.00 |
July | 93.96 | 6.40 | 87.56 | 101.98 | 29.57 | 0.00 | 0.00 | 744.00 |
August | 74.81 | 2.01 | 72.80 | 77.92 | 35.33 | 0.00 | 0.00 | 744.00 |
September | 62.65 | 0.05 | 62.60 | 57.32 | 57.53 | 0.00 | 0.00 | 720.00 |
October | 44.82 | 0.00 | 44.82 | 14.48 | 131.36 | 0.00 | 0.00 | 744.00 |
November | 34.03 | 0.00 | 34.03 | 3.87 | 162.77 | 0.00 | 0.00 | 720.00 |
December | 28.78 | 0.00 | 28.78 | 1.67 | 200.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 59.83 | 1.92 | 57.91 | 38.41 | 111.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 28.78 | 0.00 | 28.78 | 1.60 | 29.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 99.06 | 11.06 | 88.00 | 101.98 | 200.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 975.00 | 802.62 | 172.38 | 1049.02 | 483.69 | 0.00 | 0.00 | 744.00 |
February | 923.05 | 734.03 | 189.02 | 919.69 | 519.68 | 0.00 | 0.00 | 672.00 |
March | 693.24 | 458.25 | 234.99 | 618.20 | 427.75 | 0.00 | 0.00 | 744.00 |
April | 453.71 | 187.66 | 266.05 | 307.19 | 398.92 | 0.00 | 0.00 | 720.00 |
May | 412.27 | 79.23 | 333.05 | 305.05 | 234.36 | 0.00 | 0.00 | 744.00 |
June | 374.75 | 67.54 | 307.21 | 373.65 | 116.52 | 0.00 | 0.00 | 720.00 |
July | 387.12 | 65.88 | 321.25 | 401.49 | 105.00 | 0.00 | 0.00 | 744.00 |
August | 492.58 | 202.59 | 289.99 | 470.91 | 120.02 | 0.00 | 0.00 | 744.00 |
September | 647.23 | 363.83 | 283.40 | 670.05 | 187.27 | 0.00 | 0.00 | 720.00 |
October | 764.37 | 541.70 | 222.66 | 779.58 | 412.40 | 0.00 | 0.00 | 744.00 |
November | 936.57 | 747.08 | 189.49 | 1015.47 | 465.28 | 0.00 | 0.00 | 720.00 |
December | 893.52 | 723.31 | 170.21 | 947.25 | 554.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 661.30 | 412.65 | 248.65 | 653.31 | 334.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 374.75 | 65.88 | 170.21 | 305.05 | 105.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 975.00 | 802.62 | 333.05 | 1049.02 | 554.64 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.354220E+10 | 0.291595E+10 | 0.626244E+09 | 0.373616E+10 | 0.172082E+10 |
February | 0.302894E+10 | 0.240868E+10 | 0.620264E+09 | 0.297278E+10 | 0.162650E+10 |
March | 0.251858E+10 | 0.166484E+10 | 0.853733E+09 | 0.221955E+10 | 0.144806E+10 |
April | 0.159516E+10 | 0.659791E+09 | 0.935372E+09 | 0.108487E+10 | 0.125970E+10 |
May | 0.149779E+10 | 0.287827E+09 | 0.120996E+10 | 0.110901E+10 | 0.783102E+09 |
June | 0.131756E+10 | 0.237445E+09 | 0.108011E+10 | 0.128233E+10 | 0.397743E+09 |
July | 0.140643E+10 | 0.239327E+09 | 0.116710E+10 | 0.142544E+10 | 0.369481E+09 |
August | 0.178955E+10 | 0.736026E+09 | 0.105352E+10 | 0.166467E+10 | 0.426924E+09 |
September | 0.227557E+10 | 0.127918E+10 | 0.996383E+09 | 0.229566E+10 | 0.645115E+09 |
October | 0.277696E+10 | 0.196802E+10 | 0.808939E+09 | 0.277978E+10 | 0.141916E+10 |
November | 0.329283E+10 | 0.262660E+10 | 0.666231E+09 | 0.350484E+10 | 0.157729E+10 |
December | 0.324616E+10 | 0.262779E+10 | 0.618368E+09 | 0.340053E+10 | 0.192806E+10 |
Annual Sum or Average | 0.282877E+11 | 0.176515E+11 | 0.106362E+11 | 0.274756E+11 | 0.136020E+11 |
Minimum of Months | 0.131756E+10 | 0.237445E+09 | 0.618368E+09 | 0.108487E+10 | 0.369481E+09 |
Maximum of Months | 0.354220E+10 | 0.291595E+10 | 0.120996E+10 | 0.373616E+10 | 0.192806E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.997460E+10 | 0.821113E+10 | 0.176346E+10 | 0.104227E+11 | 0.507525E+10 |
February | 0.852929E+10 | 0.678267E+10 | 0.174662E+10 | 0.828164E+10 | 0.481081E+10 |
March | 0.709214E+10 | 0.468809E+10 | 0.240406E+10 | 0.617582E+10 | 0.433919E+10 |
April | 0.449187E+10 | 0.185793E+10 | 0.263395E+10 | 0.298754E+10 | 0.380307E+10 |
May | 0.421768E+10 | 0.810503E+09 | 0.340718E+10 | 0.307240E+10 | 0.231007E+10 |
June | 0.371015E+10 | 0.668629E+09 | 0.304152E+10 | 0.358839E+10 | 0.113618E+10 |
July | 0.396041E+10 | 0.673929E+09 | 0.328648E+10 | 0.399151E+10 | 0.105776E+10 |
August | 0.503925E+10 | 0.207260E+10 | 0.296665E+10 | 0.466493E+10 | 0.122375E+10 |
September | 0.640784E+10 | 0.360209E+10 | 0.280575E+10 | 0.644190E+10 | 0.187647E+10 |
October | 0.781973E+10 | 0.554181E+10 | 0.227792E+10 | 0.777858E+10 | 0.420149E+10 |
November | 0.927240E+10 | 0.739634E+10 | 0.187606E+10 | 0.978528E+10 | 0.466509E+10 |
December | 0.914098E+10 | 0.739970E+10 | 0.174128E+10 | 0.947610E+10 | 0.570906E+10 |
Annual Sum or Average | 0.796564E+11 | 0.497054E+11 | 0.299509E+11 | 0.766667E+11 | 0.402082E+11 |
Minimum of Months | 0.371015E+10 | 0.668629E+09 | 0.174128E+10 | 0.298754E+10 | 0.105776E+10 |
Maximum of Months | 0.997460E+10 | 0.821113E+10 | 0.340718E+10 | 0.104227E+11 | 0.570906E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129576E+11 | 0.106667E+11 | 0.229084E+10 | 0.138471E+11 | 0.676064E+10 |
February | 0.110800E+11 | 0.881108E+10 | 0.226896E+10 | 0.110144E+11 | 0.646256E+10 |
March | 0.921310E+10 | 0.609009E+10 | 0.312301E+10 | 0.819695E+10 | 0.590110E+10 |
April | 0.583520E+10 | 0.241355E+10 | 0.342165E+10 | 0.393850E+10 | 0.522974E+10 |
May | 0.547901E+10 | 0.105289E+10 | 0.442612E+10 | 0.406913E+10 | 0.314439E+10 |
June | 0.481970E+10 | 0.868587E+09 | 0.395111E+10 | 0.482427E+10 | 0.151201E+10 |
July | 0.514480E+10 | 0.875473E+09 | 0.426933E+10 | 0.536469E+10 | 0.140074E+10 |
August | 0.654628E+10 | 0.269243E+10 | 0.385385E+10 | 0.627018E+10 | 0.160473E+10 |
September | 0.832415E+10 | 0.467932E+10 | 0.364483E+10 | 0.860991E+10 | 0.246460E+10 |
October | 0.101583E+11 | 0.719913E+10 | 0.295915E+10 | 0.103419E+11 | 0.566525E+10 |
November | 0.120454E+11 | 0.960826E+10 | 0.243711E+10 | 0.130009E+11 | 0.623807E+10 |
December | 0.118747E+11 | 0.961263E+10 | 0.226203E+10 | 0.125585E+11 | 0.768481E+10 |
Annual Sum or Average | 0.103478E+12 | 0.645702E+11 | 0.389080E+11 | 0.102036E+12 | 0.540686E+11 |
Minimum of Months | 0.481970E+10 | 0.868587E+09 | 0.226203E+10 | 0.393850E+10 | 0.140074E+10 |
Maximum of Months | 0.129576E+11 | 0.106667E+11 | 0.442612E+10 | 0.138471E+11 | 0.768481E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.698926E+09 | 0.575359E+09 | 0.123567E+09 | 0.762941E+09 | 0.321309E+09 |
February | 0.597653E+09 | 0.475266E+09 | 0.122387E+09 | 0.605505E+09 | 0.312193E+09 |
March | 0.496951E+09 | 0.328497E+09 | 0.168454E+09 | 0.454282E+09 | 0.275078E+09 |
April | 0.314748E+09 | 0.130186E+09 | 0.184562E+09 | 0.224574E+09 | 0.239812E+09 |
May | 0.295535E+09 | 56792424.01 | 0.238743E+09 | 0.236615E+09 | 0.135693E+09 |
June | 0.259972E+09 | 46851245.39 | 0.213121E+09 | 0.278398E+09 | 56941908.01 |
July | 0.277509E+09 | 47222633.95 | 0.230286E+09 | 0.310094E+09 | 49916372.39 |
August | 0.353104E+09 | 0.145228E+09 | 0.207875E+09 | 0.356425E+09 | 59355638.14 |
September | 0.449001E+09 | 0.252401E+09 | 0.196601E+09 | 0.480361E+09 | 0.101268E+09 |
October | 0.547933E+09 | 0.388318E+09 | 0.159615E+09 | 0.570246E+09 | 0.259344E+09 |
November | 0.649723E+09 | 0.518266E+09 | 0.131457E+09 | 0.716176E+09 | 0.291696E+09 |
December | 0.640514E+09 | 0.518501E+09 | 0.122013E+09 | 0.689408E+09 | 0.372220E+09 |
Annual Sum or Average | 0.558157E+10 | 0.348289E+10 | 0.209868E+10 | 0.568502E+10 | 0.247483E+10 |
Minimum of Months | 0.259972E+09 | 46851245.39 | 0.122013E+09 | 0.224574E+09 | 49916372.39 |
Maximum of Months | 0.698926E+09 | 0.575359E+09 | 0.238743E+09 | 0.762941E+09 | 0.372220E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.452376E+09 | 0.286724E+09 | 0.165652E+09 | 0.328568E+09 | 0.671820E+09 |
February | 0.493516E+09 | 0.306130E+09 | 0.187386E+09 | 0.370497E+09 | 0.624007E+09 |
March | 0.637281E+09 | 0.351077E+09 | 0.286204E+09 | 0.545007E+09 | 0.516075E+09 |
April | 0.581674E+09 | 0.246425E+09 | 0.335249E+09 | 0.475234E+09 | 0.437002E+09 |
May | 0.734792E+09 | 0.259482E+09 | 0.475311E+09 | 0.732399E+09 | 0.245289E+09 |
June | 0.868070E+09 | 0.417264E+09 | 0.450806E+09 | 0.107194E+10 | 0.105501E+09 |
July | 0.730077E+09 | 0.266515E+09 | 0.463561E+09 | 0.910166E+09 | 92628581.36 |
August | 0.764553E+09 | 0.377809E+09 | 0.386745E+09 | 0.934619E+09 | 0.108993E+09 |
September | 0.658410E+09 | 0.316807E+09 | 0.341602E+09 | 0.755997E+09 | 0.189961E+09 |
October | 0.569660E+09 | 0.325597E+09 | 0.244063E+09 | 0.522838E+09 | 0.494110E+09 |
November | 0.452718E+09 | 0.274974E+09 | 0.177744E+09 | 0.349252E+09 | 0.583443E+09 |
December | 0.377342E+09 | 0.222845E+09 | 0.154497E+09 | 0.241493E+09 | 0.770221E+09 |
Annual Sum or Average | 0.732047E+10 | 0.365165E+10 | 0.366882E+10 | 0.723801E+10 | 0.483905E+10 |
Minimum of Months | 0.377342E+09 | 0.222845E+09 | 0.154497E+09 | 0.241493E+09 | 92628581.36 |
Maximum of Months | 0.868070E+09 | 0.417264E+09 | 0.475311E+09 | 0.107194E+10 | 0.770221E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72658291.54 | 0.00 | 72658291.54 | 9823208.18 | 0.372457E+09 |
February | 82485039.56 | 0.00 | 82485039.56 | 10008966.72 | 0.349490E+09 |
March | 0.124299E+09 | 6112.49 | 0.124293E+09 | 41883114.89 | 0.287559E+09 |
April | 0.151201E+09 | 980005.28 | 0.150221E+09 | 65161905.46 | 0.238519E+09 |
May | 0.213426E+09 | 7136116.74 | 0.206290E+09 | 0.159566E+09 | 0.129810E+09 |
June | 0.226427E+09 | 25280986.20 | 0.201146E+09 | 0.249652E+09 | 56446054.45 |
July | 0.221933E+09 | 15120085.49 | 0.206813E+09 | 0.261148E+09 | 51084615.06 |
August | 0.176699E+09 | 4757236.46 | 0.171942E+09 | 0.202046E+09 | 62398097.45 |
September | 0.143196E+09 | 111874.65 | 0.143084E+09 | 0.146299E+09 | 0.106785E+09 |
October | 0.105866E+09 | 0.00 | 0.105866E+09 | 47037122.21 | 0.268552E+09 |
November | 77772900.00 | 0.00 | 77772900.00 | 16077541.11 | 0.321306E+09 |
December | 67980921.99 | 0.00 | 67980921.99 | 8669964.36 | 0.427420E+09 |
Annual Sum or Average | 0.166394E+10 | 53392417.31 | 0.161055E+10 | 0.121737E+10 | 0.267183E+10 |
Minimum of Months | 67980921.99 | 0.00 | 67980921.99 | 8669964.36 | 51084615.06 |
Maximum of Months | 0.226427E+09 | 25280986.20 | 0.206813E+09 | 0.261148E+09 | 0.427420E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.452376E+09 | 0.286724E+09 | 0.165652E+09 | 0.345555E+09 | 0.652102E+09 |
February | 0.493516E+09 | 0.306130E+09 | 0.187386E+09 | 0.385769E+09 | 0.609907E+09 |
March | 0.637281E+09 | 0.351077E+09 | 0.286204E+09 | 0.555541E+09 | 0.510485E+09 |
April | 0.581674E+09 | 0.246425E+09 | 0.335249E+09 | 0.480378E+09 | 0.434537E+09 |
May | 0.734792E+09 | 0.259482E+09 | 0.475311E+09 | 0.728008E+09 | 0.248830E+09 |
June | 0.868070E+09 | 0.417264E+09 | 0.450806E+09 | 0.106210E+10 | 0.114193E+09 |
July | 0.730077E+09 | 0.266515E+09 | 0.463561E+09 | 0.901546E+09 | 0.100718E+09 |
August | 0.764553E+09 | 0.377809E+09 | 0.386745E+09 | 0.930312E+09 | 0.117806E+09 |
September | 0.658410E+09 | 0.316807E+09 | 0.341602E+09 | 0.757258E+09 | 0.197052E+09 |
October | 0.569660E+09 | 0.325597E+09 | 0.244063E+09 | 0.533884E+09 | 0.488810E+09 |
November | 0.452718E+09 | 0.274974E+09 | 0.177744E+09 | 0.365998E+09 | 0.568586E+09 |
December | 0.377342E+09 | 0.222845E+09 | 0.154497E+09 | 0.256025E+09 | 0.752985E+09 |
Annual Sum or Average | 0.732047E+10 | 0.365165E+10 | 0.366882E+10 | 0.730238E+10 | 0.479601E+10 |
Minimum of Months | 0.377342E+09 | 0.222845E+09 | 0.154497E+09 | 0.256025E+09 | 0.100718E+09 |
Maximum of Months | 0.868070E+09 | 0.417264E+09 | 0.475311E+09 | 0.106210E+10 | 0.752985E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559030E+09 | 0.460196E+09 | 98833846.23 | 0.580031E+09 | 0.320575E+09 |
February | 0.478027E+09 | 0.380137E+09 | 97889987.60 | 0.462675E+09 | 0.293643E+09 |
March | 0.397482E+09 | 0.262745E+09 | 0.134736E+09 | 0.345354E+09 | 0.263580E+09 |
April | 0.251749E+09 | 0.104128E+09 | 0.147620E+09 | 0.165178E+09 | 0.236971E+09 |
May | 0.236381E+09 | 45424905.42 | 0.190956E+09 | 0.159587E+09 | 0.156373E+09 |
June | 0.207937E+09 | 37473543.83 | 0.170463E+09 | 0.190815E+09 | 84476483.63 |
July | 0.221963E+09 | 37770595.60 | 0.184192E+09 | 0.213312E+09 | 80640843.81 |
August | 0.282427E+09 | 0.116160E+09 | 0.166267E+09 | 0.253386E+09 | 91482570.53 |
September | 0.359130E+09 | 0.201880E+09 | 0.157249E+09 | 0.354992E+09 | 0.130293E+09 |
October | 0.438259E+09 | 0.310593E+09 | 0.127667E+09 | 0.433479E+09 | 0.267657E+09 |
November | 0.519675E+09 | 0.414530E+09 | 0.105145E+09 | 0.548351E+09 | 0.291428E+09 |
December | 0.512309E+09 | 0.414719E+09 | 97590842.16 | 0.529322E+09 | 0.347767E+09 |
Annual Sum or Average | 0.446437E+10 | 0.278576E+10 | 0.167861E+10 | 0.423648E+10 | 0.256489E+10 |
Minimum of Months | 0.207937E+09 | 37473543.83 | 97590842.16 | 0.159587E+09 | 80640843.81 |
Maximum of Months | 0.559030E+09 | 0.460196E+09 | 0.190956E+09 | 0.580031E+09 | 0.347767E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58134338.25 | 0.00 | 58134338.25 | 7371143.39 | 0.305066E+09 |
February | 65996778.74 | 0.00 | 65996778.74 | 8074911.26 | 0.284477E+09 |
March | 99452333.57 | 4890.64 | 99447442.93 | 35129912.40 | 0.232851E+09 |
April | 0.120977E+09 | 784108.15 | 0.120193E+09 | 53537507.80 | 0.195235E+09 |
May | 0.170763E+09 | 5709650.14 | 0.165054E+09 | 0.133704E+09 | 0.103476E+09 |
June | 0.181166E+09 | 20227469.87 | 0.160938E+09 | 0.211082E+09 | 42243020.20 |
July | 0.177570E+09 | 12097671.79 | 0.165472E+09 | 0.218388E+09 | 38606231.68 |
August | 0.141378E+09 | 3806293.64 | 0.137571E+09 | 0.171323E+09 | 46544221.72 |
September | 0.114572E+09 | 89511.58 | 0.114483E+09 | 0.124679E+09 | 81780216.09 |
October | 84703640.46 | 0.00 | 84703640.46 | 40625970.33 | 0.216266E+09 |
November | 62226567.39 | 0.00 | 62226567.39 | 12890645.15 | 0.262191E+09 |
December | 54391946.60 | 0.00 | 54391946.60 | 6496494.33 | 0.352591E+09 |
Annual Sum or Average | 0.133133E+10 | 42719595.82 | 0.128861E+10 | 0.102330E+10 | 0.216133E+10 |
Minimum of Months | 54391946.60 | 0.00 | 54391946.60 | 6496494.33 | 38606231.68 |
Maximum of Months | 0.181166E+09 | 20227469.87 | 0.165472E+09 | 0.218388E+09 | 0.352591E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423510E+09 | 0.259061E+09 | 0.164449E+09 | 0.279959E+09 | 0.659701E+09 |
February | 0.512719E+09 | 0.324494E+09 | 0.188224E+09 | 0.391483E+09 | 0.621295E+09 |
March | 0.683831E+09 | 0.399165E+09 | 0.284666E+09 | 0.587836E+09 | 0.505161E+09 |
April | 0.675568E+09 | 0.329054E+09 | 0.346514E+09 | 0.581285E+09 | 0.425952E+09 |
May | 0.818259E+09 | 0.342503E+09 | 0.475755E+09 | 0.824876E+09 | 0.229733E+09 |
June | 0.963473E+09 | 0.505580E+09 | 0.457892E+09 | 0.118582E+10 | 95081606.36 |
July | 0.903709E+09 | 0.429361E+09 | 0.474348E+09 | 0.112474E+10 | 86551567.86 |
August | 0.913885E+09 | 0.503491E+09 | 0.410394E+09 | 0.111396E+10 | 0.104537E+09 |
September | 0.737181E+09 | 0.400752E+09 | 0.336429E+09 | 0.840202E+09 | 0.178887E+09 |
October | 0.551144E+09 | 0.302257E+09 | 0.248887E+09 | 0.486004E+09 | 0.483383E+09 |
November | 0.413927E+09 | 0.233275E+09 | 0.180651E+09 | 0.287356E+09 | 0.578138E+09 |
December | 0.371019E+09 | 0.213832E+09 | 0.157187E+09 | 0.223666E+09 | 0.764223E+09 |
Annual Sum or Average | 0.796822E+10 | 0.424283E+10 | 0.372540E+10 | 0.792719E+10 | 0.473265E+10 |
Minimum of Months | 0.371019E+09 | 0.213832E+09 | 0.157187E+09 | 0.223666E+09 | 86551567.86 |
Maximum of Months | 0.963473E+09 | 0.505580E+09 | 0.475755E+09 | 0.118582E+10 | 0.764223E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.698926E+09 | 0.575359E+09 | 0.123567E+09 | 0.761386E+09 | 0.320025E+09 |
February | 0.597653E+09 | 0.475266E+09 | 0.122387E+09 | 0.602796E+09 | 0.310822E+09 |
March | 0.496951E+09 | 0.328497E+09 | 0.168454E+09 | 0.450412E+09 | 0.274127E+09 |
April | 0.314748E+09 | 0.130186E+09 | 0.184562E+09 | 0.220773E+09 | 0.239762E+09 |
May | 0.295535E+09 | 56792424.01 | 0.238743E+09 | 0.232807E+09 | 0.135689E+09 |
June | 0.259972E+09 | 46851245.39 | 0.213121E+09 | 0.275650E+09 | 56607442.39 |
July | 0.277509E+09 | 47222633.95 | 0.230286E+09 | 0.306026E+09 | 50050779.79 |
August | 0.353104E+09 | 0.145228E+09 | 0.207875E+09 | 0.352648E+09 | 58968021.09 |
September | 0.449001E+09 | 0.252401E+09 | 0.196601E+09 | 0.477650E+09 | 0.100767E+09 |
October | 0.547933E+09 | 0.388318E+09 | 0.159615E+09 | 0.568227E+09 | 0.258059E+09 |
November | 0.649723E+09 | 0.518266E+09 | 0.131457E+09 | 0.715222E+09 | 0.290110E+09 |
December | 0.640514E+09 | 0.518501E+09 | 0.122013E+09 | 0.688070E+09 | 0.371148E+09 |
Annual Sum or Average | 0.558157E+10 | 0.348289E+10 | 0.209868E+10 | 0.565167E+10 | 0.246614E+10 |
Minimum of Months | 0.259972E+09 | 46851245.39 | 0.122013E+09 | 0.220773E+09 | 50050779.79 |
Maximum of Months | 0.698926E+09 | 0.575359E+09 | 0.238743E+09 | 0.761386E+09 | 0.371148E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72658291.54 | 0.00 | 72658291.54 | 9091680.11 | 0.371212E+09 |
February | 82485039.56 | 0.00 | 82485039.56 | 8734866.34 | 0.349481E+09 |
March | 0.124299E+09 | 6112.49 | 0.124293E+09 | 39169017.00 | 0.287316E+09 |
April | 0.151201E+09 | 980005.28 | 0.150221E+09 | 61752792.81 | 0.238752E+09 |
May | 0.213426E+09 | 7136116.74 | 0.206290E+09 | 0.156576E+09 | 0.129021E+09 |
June | 0.226427E+09 | 25280986.20 | 0.201146E+09 | 0.244615E+09 | 54862802.05 |
July | 0.221933E+09 | 15120085.49 | 0.206813E+09 | 0.254471E+09 | 50696422.92 |
August | 0.176699E+09 | 4757236.46 | 0.171942E+09 | 0.196174E+09 | 61374127.66 |
September | 0.143196E+09 | 111874.65 | 0.143084E+09 | 0.143518E+09 | 0.105297E+09 |
October | 0.105866E+09 | 0.00 | 0.105866E+09 | 45551619.81 | 0.266612E+09 |
November | 77772900.00 | 0.00 | 77772900.00 | 15085949.58 | 0.319102E+09 |
December | 67980921.99 | 0.00 | 67980921.99 | 8002947.99 | 0.426302E+09 |
Annual Sum or Average | 0.166394E+10 | 53392417.31 | 0.161055E+10 | 0.118274E+10 | 0.266003E+10 |
Minimum of Months | 67980921.99 | 0.00 | 67980921.99 | 8002947.99 | 50696422.92 |
Maximum of Months | 0.226427E+09 | 25280986.20 | 0.206813E+09 | 0.254471E+09 | 0.426302E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.423510E+09 | 0.259061E+09 | 0.164449E+09 | 0.291030E+09 | 0.632422E+09 |
February | 0.512719E+09 | 0.324494E+09 | 0.188224E+09 | 0.400642E+09 | 0.600673E+09 |
March | 0.683831E+09 | 0.399165E+09 | 0.284666E+09 | 0.597764E+09 | 0.497413E+09 |
April | 0.675568E+09 | 0.329054E+09 | 0.346514E+09 | 0.586434E+09 | 0.422848E+09 |
May | 0.818259E+09 | 0.342503E+09 | 0.475755E+09 | 0.823059E+09 | 0.232661E+09 |
June | 0.963473E+09 | 0.505580E+09 | 0.457892E+09 | 0.117268E+10 | 0.103190E+09 |
July | 0.903709E+09 | 0.429361E+09 | 0.474348E+09 | 0.111156E+10 | 94822535.05 |
August | 0.913885E+09 | 0.503491E+09 | 0.410394E+09 | 0.110616E+10 | 0.112719E+09 |
September | 0.737181E+09 | 0.400752E+09 | 0.336429E+09 | 0.841884E+09 | 0.184020E+09 |
October | 0.551144E+09 | 0.302257E+09 | 0.248887E+09 | 0.497922E+09 | 0.476172E+09 |
November | 0.413927E+09 | 0.233275E+09 | 0.180651E+09 | 0.299058E+09 | 0.557121E+09 |
December | 0.371019E+09 | 0.213832E+09 | 0.157187E+09 | 0.233511E+09 | 0.741006E+09 |
Annual Sum or Average | 0.796822E+10 | 0.424283E+10 | 0.372540E+10 | 0.796170E+10 | 0.465506E+10 |
Minimum of Months | 0.371019E+09 | 0.213832E+09 | 0.157187E+09 | 0.233511E+09 | 94822535.05 |
Maximum of Months | 0.963473E+09 | 0.505580E+09 | 0.475755E+09 | 0.117268E+10 | 0.741006E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92017141.76 | 0.00 | 92017141.76 | 10548344.56 | 0.485055E+09 |
February | 0.104462E+09 | 0.00 | 0.104462E+09 | 11559296.73 | 0.447907E+09 |
March | 0.157417E+09 | 7741.09 | 0.157409E+09 | 54641171.95 | 0.366684E+09 |
April | 0.191486E+09 | 1241114.86 | 0.190245E+09 | 88162778.50 | 0.301243E+09 |
May | 0.270291E+09 | 9037441.59 | 0.261253E+09 | 0.220926E+09 | 0.159613E+09 |
June | 0.286756E+09 | 32016773.88 | 0.254739E+09 | 0.333538E+09 | 69730580.31 |
July | 0.281064E+09 | 19148634.25 | 0.261915E+09 | 0.340426E+09 | 67439842.03 |
August | 0.223778E+09 | 6024739.81 | 0.217753E+09 | 0.268240E+09 | 79237825.06 |
September | 0.181349E+09 | 141682.18 | 0.181207E+09 | 0.194185E+09 | 0.135301E+09 |
October | 0.134072E+09 | 0.00 | 0.134072E+09 | 61575849.22 | 0.345190E+09 |
November | 98494470.65 | 0.00 | 98494470.65 | 18938875.21 | 0.415473E+09 |
December | 86093548.34 | 0.00 | 86093548.34 | 9491387.85 | 0.551848E+09 |
Annual Sum or Average | 0.210728E+10 | 67618127.65 | 0.203966E+10 | 0.161223E+10 | 0.342472E+10 |
Minimum of Months | 86093548.34 | 0.00 | 86093548.34 | 9491387.85 | 67439842.03 |
Maximum of Months | 0.286756E+09 | 32016773.88 | 0.261915E+09 | 0.340426E+09 | 0.551848E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33921328.58 | 0.00 | 33921328.58 | 3888556.58 | 0.178811E+09 |
February | 38509054.79 | 0.00 | 38509054.79 | 4261235.41 | 0.165117E+09 |
March | 58030337.78 | 2853.69 | 58027484.09 | 20142998.49 | 0.135175E+09 |
April | 70589830.28 | 457526.33 | 70132303.96 | 32500450.69 | 0.111051E+09 |
May | 99640291.71 | 3331575.18 | 96308716.53 | 81442352.13 | 58840033.29 |
June | 0.105710E+09 | 11802708.56 | 93907297.07 | 0.122956E+09 | 25705579.22 |
July | 0.103612E+09 | 7058979.47 | 96552719.65 | 0.125495E+09 | 24861118.24 |
August | 82493768.33 | 2220968.56 | 80272799.78 | 98884246.57 | 29210343.30 |
September | 66852760.83 | 52229.92 | 66800530.91 | 71584787.32 | 49877584.20 |
October | 49424490.01 | 0.00 | 49424490.01 | 22699407.68 | 0.127252E+09 |
November | 36309140.22 | 0.00 | 36309140.22 | 6981653.60 | 0.153160E+09 |
December | 31737646.77 | 0.00 | 31737646.77 | 3498918.57 | 0.203434E+09 |
Annual Sum or Average | 0.776830E+09 | 24926841.70 | 0.751904E+09 | 0.594336E+09 | 0.126249E+10 |
Minimum of Months | 31737646.77 | 0.00 | 31737646.77 | 3498918.57 | 24861118.24 |
Maximum of Months | 0.105710E+09 | 11802708.56 | 96552719.65 | 0.125495E+09 | 0.203434E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326116E+09 | 0.268460E+09 | 57655806.88 | 0.360340E+09 | 0.149248E+09 |
February | 0.278862E+09 | 0.221757E+09 | 57105196.61 | 0.286506E+09 | 0.144444E+09 |
March | 0.231875E+09 | 0.153275E+09 | 78599786.37 | 0.215458E+09 | 0.128291E+09 |
April | 0.146860E+09 | 60744282.75 | 86115970.50 | 0.108113E+09 | 0.110792E+09 |
May | 0.137896E+09 | 26499116.19 | 0.111397E+09 | 0.116323E+09 | 62155656.66 |
June | 0.121302E+09 | 21860602.30 | 99441478.55 | 0.134160E+09 | 28191510.59 |
July | 0.129484E+09 | 22033890.71 | 0.107451E+09 | 0.146502E+09 | 26527013.30 |
August | 0.164757E+09 | 67762963.18 | 96993726.33 | 0.169976E+09 | 29971639.23 |
September | 0.209502E+09 | 0.117769E+09 | 91733042.06 | 0.227774E+09 | 49176402.33 |
October | 0.255663E+09 | 0.181188E+09 | 74475768.96 | 0.269852E+09 | 0.121955E+09 |
November | 0.303158E+09 | 0.241821E+09 | 61337202.72 | 0.338462E+09 | 0.135483E+09 |
December | 0.298861E+09 | 0.241931E+09 | 56930686.84 | 0.325367E+09 | 0.172235E+09 |
Annual Sum or Average | 0.260434E+10 | 0.162510E+10 | 0.979236E+09 | 0.269883E+10 | 0.115847E+10 |
Minimum of Months | 0.121302E+09 | 21860602.30 | 56930686.84 | 0.108113E+09 | 26527013.30 |
Maximum of Months | 0.326116E+09 | 0.268460E+09 | 0.111397E+09 | 0.360340E+09 | 0.172235E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.885146E+09 | 0.728656E+09 | 0.156490E+09 | 0.978038E+09 | 0.405090E+09 |
February | 0.756889E+09 | 0.601894E+09 | 0.154995E+09 | 0.777636E+09 | 0.392050E+09 |
March | 0.629357E+09 | 0.416021E+09 | 0.213336E+09 | 0.584798E+09 | 0.348209E+09 |
April | 0.398609E+09 | 0.164872E+09 | 0.233736E+09 | 0.293440E+09 | 0.300711E+09 |
May | 0.374277E+09 | 71924021.61 | 0.302353E+09 | 0.315724E+09 | 0.168703E+09 |
June | 0.329239E+09 | 59334146.13 | 0.269905E+09 | 0.364138E+09 | 76517526.19 |
July | 0.351447E+09 | 59804486.31 | 0.291643E+09 | 0.397636E+09 | 71999740.07 |
August | 0.447183E+09 | 0.183923E+09 | 0.263261E+09 | 0.461351E+09 | 81349159.42 |
September | 0.568632E+09 | 0.319650E+09 | 0.248982E+09 | 0.618224E+09 | 0.133475E+09 |
October | 0.693923E+09 | 0.491780E+09 | 0.202142E+09 | 0.732435E+09 | 0.331010E+09 |
November | 0.822833E+09 | 0.656351E+09 | 0.166482E+09 | 0.918656E+09 | 0.367727E+09 |
December | 0.811171E+09 | 0.656649E+09 | 0.154522E+09 | 0.883112E+09 | 0.467481E+09 |
Annual Sum or Average | 0.706870E+10 | 0.441086E+10 | 0.265785E+10 | 0.732519E+10 | 0.314432E+10 |
Minimum of Months | 0.329239E+09 | 59334146.13 | 0.154522E+09 | 0.293440E+09 | 71999740.07 |
Maximum of Months | 0.885146E+09 | 0.728656E+09 | 0.302353E+09 | 0.978038E+09 | 0.467481E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.699499E+09 | 0.575831E+09 | 0.123668E+09 | 0.761680E+09 | 0.320664E+09 |
February | 0.598143E+09 | 0.475656E+09 | 0.122487E+09 | 0.603474E+09 | 0.313148E+09 |
March | 0.497358E+09 | 0.328767E+09 | 0.168592E+09 | 0.453053E+09 | 0.275229E+09 |
April | 0.315006E+09 | 0.130293E+09 | 0.184714E+09 | 0.223346E+09 | 0.240528E+09 |
May | 0.295778E+09 | 56839013.37 | 0.238939E+09 | 0.234108E+09 | 0.136618E+09 |
June | 0.260186E+09 | 46889679.55 | 0.213296E+09 | 0.276152E+09 | 56846127.21 |
July | 0.277736E+09 | 47261372.78 | 0.230475E+09 | 0.308536E+09 | 49382017.93 |
August | 0.353393E+09 | 0.145347E+09 | 0.208046E+09 | 0.354547E+09 | 59147850.43 |
September | 0.449370E+09 | 0.252608E+09 | 0.196762E+09 | 0.479200E+09 | 0.100726E+09 |
October | 0.548383E+09 | 0.388636E+09 | 0.159746E+09 | 0.568871E+09 | 0.258979E+09 |
November | 0.650256E+09 | 0.518691E+09 | 0.131565E+09 | 0.714160E+09 | 0.291690E+09 |
December | 0.641039E+09 | 0.518927E+09 | 0.122113E+09 | 0.687178E+09 | 0.373040E+09 |
Annual Sum or Average | 0.558615E+10 | 0.348575E+10 | 0.210040E+10 | 0.566430E+10 | 0.247600E+10 |
Minimum of Months | 0.260186E+09 | 46889679.55 | 0.122113E+09 | 0.223346E+09 | 49382017.93 |
Maximum of Months | 0.699499E+09 | 0.575831E+09 | 0.238939E+09 | 0.761680E+09 | 0.373040E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.452747E+09 | 0.286959E+09 | 0.165788E+09 | 0.327574E+09 | 0.668928E+09 |
February | 0.493921E+09 | 0.306381E+09 | 0.187540E+09 | 0.368203E+09 | 0.625104E+09 |
March | 0.637804E+09 | 0.351365E+09 | 0.286439E+09 | 0.541999E+09 | 0.515930E+09 |
April | 0.582151E+09 | 0.246627E+09 | 0.335524E+09 | 0.471081E+09 | 0.437756E+09 |
May | 0.735395E+09 | 0.259695E+09 | 0.475701E+09 | 0.725438E+09 | 0.246395E+09 |
June | 0.868782E+09 | 0.417606E+09 | 0.451175E+09 | 0.106547E+10 | 0.105278E+09 |
July | 0.730676E+09 | 0.266734E+09 | 0.463941E+09 | 0.905601E+09 | 91602912.70 |
August | 0.765180E+09 | 0.378119E+09 | 0.387062E+09 | 0.928794E+09 | 0.108558E+09 |
September | 0.658950E+09 | 0.317067E+09 | 0.341883E+09 | 0.752684E+09 | 0.188775E+09 |
October | 0.570127E+09 | 0.325864E+09 | 0.244263E+09 | 0.520346E+09 | 0.492847E+09 |
November | 0.453089E+09 | 0.275199E+09 | 0.177890E+09 | 0.347324E+09 | 0.582683E+09 |
December | 0.377651E+09 | 0.223028E+09 | 0.154623E+09 | 0.240902E+09 | 0.770510E+09 |
Annual Sum or Average | 0.732647E+10 | 0.365464E+10 | 0.367183E+10 | 0.719542E+10 | 0.483437E+10 |
Minimum of Months | 0.377651E+09 | 0.223028E+09 | 0.154623E+09 | 0.240902E+09 | 91602912.70 |
Maximum of Months | 0.868782E+09 | 0.417606E+09 | 0.475701E+09 | 0.106547E+10 | 0.770510E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72717896.38 | 0.00 | 72717896.38 | 10149997.76 | 0.369623E+09 |
February | 82552705.71 | 0.00 | 82552705.71 | 9962852.02 | 0.348986E+09 |
March | 0.124401E+09 | 6117.51 | 0.124395E+09 | 41333685.94 | 0.287542E+09 |
April | 0.151325E+09 | 980809.22 | 0.150344E+09 | 63631872.71 | 0.239128E+09 |
May | 0.213601E+09 | 7141970.82 | 0.206459E+09 | 0.155364E+09 | 0.131810E+09 |
June | 0.226613E+09 | 25301725.32 | 0.201311E+09 | 0.245836E+09 | 58217961.78 |
July | 0.222115E+09 | 15132489.17 | 0.206982E+09 | 0.258571E+09 | 51973480.04 |
August | 0.176844E+09 | 4761139.03 | 0.172083E+09 | 0.198880E+09 | 63976108.66 |
September | 0.143314E+09 | 111966.42 | 0.143202E+09 | 0.144661E+09 | 0.108056E+09 |
October | 0.105952E+09 | 0.00 | 0.105952E+09 | 46591347.91 | 0.268448E+09 |
November | 77836700.57 | 0.00 | 77836700.57 | 16054804.74 | 0.319727E+09 |
December | 68036689.77 | 0.00 | 68036689.77 | 9006496.57 | 0.426189E+09 |
Annual Sum or Average | 0.166531E+10 | 53436217.49 | 0.161187E+10 | 0.120004E+10 | 0.267368E+10 |
Minimum of Months | 68036689.77 | 0.00 | 68036689.77 | 9006496.57 | 51973480.04 |
Maximum of Months | 0.226613E+09 | 25301725.32 | 0.206982E+09 | 0.258571E+09 | 0.426189E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.452747E+09 | 0.286959E+09 | 0.165788E+09 | 0.346623E+09 | 0.648612E+09 |
February | 0.493921E+09 | 0.306381E+09 | 0.187540E+09 | 0.384979E+09 | 0.610601E+09 |
March | 0.637804E+09 | 0.351365E+09 | 0.286439E+09 | 0.552702E+09 | 0.510680E+09 |
April | 0.582151E+09 | 0.246627E+09 | 0.335524E+09 | 0.476029E+09 | 0.435581E+09 |
May | 0.735395E+09 | 0.259695E+09 | 0.475701E+09 | 0.718756E+09 | 0.252344E+09 |
June | 0.868782E+09 | 0.417606E+09 | 0.451175E+09 | 0.105357E+10 | 0.117341E+09 |
July | 0.730676E+09 | 0.266734E+09 | 0.463941E+09 | 0.895629E+09 | 0.102085E+09 |
August | 0.765180E+09 | 0.378119E+09 | 0.387062E+09 | 0.923178E+09 | 0.120414E+09 |
September | 0.658950E+09 | 0.317067E+09 | 0.341883E+09 | 0.752743E+09 | 0.198995E+09 |
October | 0.570127E+09 | 0.325864E+09 | 0.244263E+09 | 0.531613E+09 | 0.488135E+09 |
November | 0.453089E+09 | 0.275199E+09 | 0.177890E+09 | 0.365657E+09 | 0.567130E+09 |
December | 0.377651E+09 | 0.223028E+09 | 0.154623E+09 | 0.256976E+09 | 0.752831E+09 |
Annual Sum or Average | 0.732647E+10 | 0.365464E+10 | 0.367183E+10 | 0.725845E+10 | 0.480475E+10 |
Minimum of Months | 0.377651E+09 | 0.223028E+09 | 0.154623E+09 | 0.256976E+09 | 0.102085E+09 |
Maximum of Months | 0.868782E+09 | 0.417606E+09 | 0.475701E+09 | 0.105357E+10 | 0.752831E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102588E+10 | 0.844511E+09 | 0.181371E+09 | 0.109390E+10 | 0.487899E+09 |
February | 0.877234E+09 | 0.697595E+09 | 0.179639E+09 | 0.868370E+09 | 0.472551E+09 |
March | 0.729424E+09 | 0.482168E+09 | 0.247256E+09 | 0.654932E+09 | 0.410909E+09 |
April | 0.461987E+09 | 0.191087E+09 | 0.270900E+09 | 0.324125E+09 | 0.356654E+09 |
May | 0.433787E+09 | 83359867.96 | 0.350427E+09 | 0.347093E+09 | 0.198366E+09 |
June | 0.381587E+09 | 68768215.08 | 0.312819E+09 | 0.417859E+09 | 78712844.60 |
July | 0.407327E+09 | 69313338.87 | 0.338014E+09 | 0.461692E+09 | 69383762.38 |
August | 0.518285E+09 | 0.213166E+09 | 0.305119E+09 | 0.527244E+09 | 83552130.70 |
September | 0.659044E+09 | 0.370474E+09 | 0.288570E+09 | 0.702201E+09 | 0.147451E+09 |
October | 0.804256E+09 | 0.569973E+09 | 0.234283E+09 | 0.825188E+09 | 0.388551E+09 |
November | 0.953662E+09 | 0.760710E+09 | 0.192952E+09 | 0.102832E+10 | 0.443549E+09 |
December | 0.940146E+09 | 0.761056E+09 | 0.179090E+09 | 0.983636E+09 | 0.568463E+09 |
Annual Sum or Average | 0.819262E+10 | 0.511218E+10 | 0.308044E+10 | 0.823456E+10 | 0.370604E+10 |
Minimum of Months | 0.381587E+09 | 68768215.08 | 0.179090E+09 | 0.324125E+09 | 69383762.38 |
Maximum of Months | 0.102588E+10 | 0.844511E+09 | 0.350427E+09 | 0.109390E+10 | 0.568463E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.509006E+09 | 0.00 | 0.509006E+09 | 24134937.71 | 0.319347E+10 |
February | 0.577847E+09 | 0.00 | 0.577847E+09 | 30371651.79 | 0.299110E+10 |
March | 0.870773E+09 | 42820.93 | 0.870731E+09 | 0.195401E+09 | 0.253949E+10 |
April | 0.105923E+10 | 6865404.55 | 0.105237E+10 | 0.328147E+09 | 0.217709E+10 |
May | 0.149515E+10 | 49991902.31 | 0.144516E+10 | 0.943088E+09 | 0.123628E+10 |
June | 0.158623E+10 | 0.177105E+09 | 0.140912E+10 | 0.159550E+10 | 0.551740E+09 |
July | 0.155474E+10 | 0.105923E+09 | 0.144882E+10 | 0.165690E+10 | 0.530392E+09 |
August | 0.123786E+10 | 33326710.97 | 0.120453E+10 | 0.127501E+10 | 0.626543E+09 |
September | 0.100316E+10 | 783735.27 | 0.100237E+10 | 0.914176E+09 | 0.988730E+09 |
October | 0.741638E+09 | 0.00 | 0.741638E+09 | 0.235381E+09 | 0.237305E+10 |
November | 0.544836E+09 | 0.00 | 0.544836E+09 | 62043032.90 | 0.282553E+10 |
December | 0.476239E+09 | 0.00 | 0.476239E+09 | 26053535.44 | 0.362766E+10 |
Annual Sum or Average | 0.116567E+11 | 0.374039E+09 | 0.112827E+11 | 0.728621E+10 | 0.236611E+11 |
Minimum of Months | 0.476239E+09 | 0.00 | 0.476239E+09 | 24134937.71 | 0.530392E+09 |
Maximum of Months | 0.158623E+10 | 0.177105E+09 | 0.144882E+10 | 0.165690E+10 | 0.362766E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.509006E+09 | 0.00 | 0.509006E+09 | 18321223.16 | 0.333195E+10 |
February | 0.577847E+09 | 0.00 | 0.577847E+09 | 24395890.66 | 0.312367E+10 |
March | 0.870773E+09 | 42820.93 | 0.870731E+09 | 0.172571E+09 | 0.266492E+10 |
April | 0.105923E+10 | 6865404.55 | 0.105237E+10 | 0.296546E+09 | 0.228602E+10 |
May | 0.149515E+10 | 49991902.31 | 0.144516E+10 | 0.893240E+09 | 0.129923E+10 |
June | 0.158623E+10 | 0.177105E+09 | 0.140912E+10 | 0.154282E+10 | 0.585328E+09 |
July | 0.155474E+10 | 0.105923E+09 | 0.144882E+10 | 0.160409E+10 | 0.565978E+09 |
August | 0.123786E+10 | 33326710.97 | 0.120453E+10 | 0.123025E+10 | 0.666116E+09 |
September | 0.100316E+10 | 783735.27 | 0.100237E+10 | 0.878294E+09 | 0.103829E+10 |
October | 0.741638E+09 | 0.00 | 0.741638E+09 | 0.212809E+09 | 0.247510E+10 |
November | 0.544836E+09 | 0.00 | 0.544836E+09 | 54380123.30 | 0.295203E+10 |
December | 0.476239E+09 | 0.00 | 0.476239E+09 | 20824836.90 | 0.377718E+10 |
Annual Sum or Average | 0.116567E+11 | 0.374039E+09 | 0.112827E+11 | 0.694854E+10 | 0.247658E+11 |
Minimum of Months | 0.476239E+09 | 0.00 | 0.476239E+09 | 18321223.16 | 0.565978E+09 |
Maximum of Months | 0.158623E+10 | 0.177105E+09 | 0.144882E+10 | 0.160409E+10 | 0.377718E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72717896.38 | 0.00 | 72717896.38 | 4168872.09 | 0.467014E+09 |
February | 82552705.71 | 0.00 | 82552705.71 | 4251975.04 | 0.444821E+09 |
March | 0.124401E+09 | 6117.51 | 0.124395E+09 | 28382587.27 | 0.381989E+09 |
April | 0.151325E+09 | 980809.22 | 0.150344E+09 | 46381387.28 | 0.328311E+09 |
May | 0.213601E+09 | 7141970.82 | 0.206459E+09 | 0.146007E+09 | 0.190081E+09 |
June | 0.226613E+09 | 25301725.32 | 0.201311E+09 | 0.240196E+09 | 89877234.77 |
July | 0.222115E+09 | 15132489.17 | 0.206982E+09 | 0.249995E+09 | 87475522.70 |
August | 0.176844E+09 | 4761139.03 | 0.172083E+09 | 0.195100E+09 | 98463341.14 |
September | 0.143314E+09 | 111966.42 | 0.143202E+09 | 0.142441E+09 | 0.148571E+09 |
October | 0.105952E+09 | 0.00 | 0.105952E+09 | 37229761.86 | 0.350327E+09 |
November | 77836700.57 | 0.00 | 77836700.57 | 10521706.28 | 0.414833E+09 |
December | 68036689.77 | 0.00 | 68036689.77 | 4045038.32 | 0.534727E+09 |
Annual Sum or Average | 0.166531E+10 | 53436217.49 | 0.161187E+10 | 0.110872E+10 | 0.353649E+10 |
Minimum of Months | 68036689.77 | 0.00 | 68036689.77 | 4045038.32 | 87475522.70 |
Maximum of Months | 0.226613E+09 | 25301725.32 | 0.206982E+09 | 0.249995E+09 | 0.534727E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.847654E+09 | 0.518510E+09 | 0.329144E+09 | 0.537612E+09 | 0.160363E+10 |
February | 0.102621E+10 | 0.649475E+09 | 0.376730E+09 | 0.754496E+09 | 0.154346E+10 |
March | 0.136869E+10 | 0.798927E+09 | 0.569759E+09 | 0.113122E+10 | 0.133342E+10 |
April | 0.135215E+10 | 0.658600E+09 | 0.693548E+09 | 0.109721E+10 | 0.117481E+10 |
May | 0.163774E+10 | 0.685520E+09 | 0.952223E+09 | 0.159437E+10 | 0.689132E+09 |
June | 0.192839E+10 | 0.101192E+10 | 0.916471E+09 | 0.232546E+10 | 0.340377E+09 |
July | 0.180877E+10 | 0.859366E+09 | 0.949406E+09 | 0.220585E+10 | 0.332371E+09 |
August | 0.182914E+10 | 0.100774E+10 | 0.821403E+09 | 0.220478E+10 | 0.367092E+09 |
September | 0.147547E+10 | 0.802104E+09 | 0.673362E+09 | 0.167360E+10 | 0.531746E+09 |
October | 0.110311E+10 | 0.604968E+09 | 0.498146E+09 | 0.951148E+09 | 0.125948E+10 |
November | 0.828474E+09 | 0.466900E+09 | 0.361573E+09 | 0.553346E+09 | 0.145473E+10 |
December | 0.742595E+09 | 0.427985E+09 | 0.314610E+09 | 0.421942E+09 | 0.187138E+10 |
Annual Sum or Average | 0.159484E+11 | 0.849201E+10 | 0.745638E+10 | 0.154510E+11 | 0.125016E+11 |
Minimum of Months | 0.742595E+09 | 0.427985E+09 | 0.314610E+09 | 0.421942E+09 | 0.332371E+09 |
Maximum of Months | 0.192839E+10 | 0.101192E+10 | 0.952223E+09 | 0.232546E+10 | 0.187138E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.699499E+09 | 0.575831E+09 | 0.123668E+09 | 0.751666E+09 | 0.387799E+09 |
February | 0.598143E+09 | 0.475656E+09 | 0.122487E+09 | 0.589494E+09 | 0.382642E+09 |
March | 0.497358E+09 | 0.328767E+09 | 0.168592E+09 | 0.437854E+09 | 0.357675E+09 |
April | 0.315006E+09 | 0.130293E+09 | 0.184714E+09 | 0.205886E+09 | 0.327637E+09 |
May | 0.295778E+09 | 56839013.37 | 0.238939E+09 | 0.222433E+09 | 0.201155E+09 |
June | 0.260186E+09 | 46889679.55 | 0.213296E+09 | 0.265388E+09 | 99140416.95 |
July | 0.277736E+09 | 47261372.78 | 0.230475E+09 | 0.295582E+09 | 94130901.35 |
August | 0.353393E+09 | 0.145347E+09 | 0.208046E+09 | 0.346588E+09 | 0.102065E+09 |
September | 0.449370E+09 | 0.252608E+09 | 0.196762E+09 | 0.476918E+09 | 0.148757E+09 |
October | 0.548383E+09 | 0.388636E+09 | 0.159746E+09 | 0.564381E+09 | 0.334645E+09 |
November | 0.650256E+09 | 0.518691E+09 | 0.131565E+09 | 0.706113E+09 | 0.362063E+09 |
December | 0.641039E+09 | 0.518927E+09 | 0.122113E+09 | 0.674204E+09 | 0.451597E+09 |
Annual Sum or Average | 0.558615E+10 | 0.348575E+10 | 0.210040E+10 | 0.553651E+10 | 0.324931E+10 |
Minimum of Months | 0.260186E+09 | 46889679.55 | 0.122113E+09 | 0.205886E+09 | 94130901.35 |
Maximum of Months | 0.699499E+09 | 0.575831E+09 | 0.238939E+09 | 0.751666E+09 | 0.451597E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92092627.52 | 0.00 | 92092627.52 | 4779392.15 | 0.535249E+09 |
February | 0.104548E+09 | 0.00 | 0.104548E+09 | 5809371.34 | 0.495855E+09 |
March | 0.157546E+09 | 7747.44 | 0.157538E+09 | 38644145.62 | 0.412546E+09 |
April | 0.191644E+09 | 1242133.00 | 0.190401E+09 | 66109684.83 | 0.351469E+09 |
May | 0.270512E+09 | 9044855.41 | 0.261467E+09 | 0.179903E+09 | 0.200719E+09 |
June | 0.286991E+09 | 32043038.67 | 0.254948E+09 | 0.294538E+09 | 92240754.76 |
July | 0.281294E+09 | 19164342.72 | 0.262130E+09 | 0.305287E+09 | 88509190.50 |
August | 0.223961E+09 | 6029682.17 | 0.217932E+09 | 0.233265E+09 | 0.105773E+09 |
September | 0.181498E+09 | 141798.41 | 0.181356E+09 | 0.166046E+09 | 0.166664E+09 |
October | 0.134182E+09 | 0.00 | 0.134182E+09 | 43334981.11 | 0.393234E+09 |
November | 98575270.05 | 0.00 | 98575270.05 | 11216597.21 | 0.471556E+09 |
December | 86164174.72 | 0.00 | 86164174.72 | 5011290.11 | 0.601169E+09 |
Annual Sum or Average | 0.210901E+10 | 67673597.81 | 0.204133E+10 | 0.135394E+10 | 0.391498E+10 |
Minimum of Months | 86164174.72 | 0.00 | 86164174.72 | 4779392.15 | 88509190.50 |
Maximum of Months | 0.286991E+09 | 32043038.67 | 0.262130E+09 | 0.305287E+09 | 0.601169E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82395622.78 | 0.00 | 82395622.78 | 4276140.27 | 0.478881E+09 |
February | 93539306.53 | 0.00 | 93539306.53 | 5197666.55 | 0.443640E+09 |
March | 0.140957E+09 | 6931.66 | 0.140950E+09 | 34575063.51 | 0.369107E+09 |
April | 0.171464E+09 | 1111341.10 | 0.170353E+09 | 59148585.50 | 0.314461E+09 |
May | 0.242028E+09 | 8092466.40 | 0.233936E+09 | 0.160959E+09 | 0.179584E+09 |
June | 0.256772E+09 | 28669028.11 | 0.228103E+09 | 0.263524E+09 | 82528152.78 |
July | 0.251675E+09 | 17146410.05 | 0.234529E+09 | 0.273142E+09 | 79189508.10 |
August | 0.200379E+09 | 5394779.48 | 0.194984E+09 | 0.208703E+09 | 94635059.33 |
September | 0.162387E+09 | 126867.57 | 0.162260E+09 | 0.148562E+09 | 0.149115E+09 |
October | 0.120053E+09 | 0.00 | 0.120053E+09 | 38771971.79 | 0.351828E+09 |
November | 88195667.61 | 0.00 | 88195667.61 | 10035532.02 | 0.421905E+09 |
December | 77091413.59 | 0.00 | 77091413.59 | 4483620.25 | 0.537856E+09 |
Annual Sum or Average | 0.188694E+10 | 60547824.38 | 0.182639E+10 | 0.121138E+10 | 0.350273E+10 |
Minimum of Months | 77091413.59 | 0.00 | 77091413.59 | 4276140.27 | 79189508.10 |
Maximum of Months | 0.256772E+09 | 28669028.11 | 0.234529E+09 | 0.273142E+09 | 0.537856E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.261144E+10 | 0.214975E+10 | 0.461690E+09 | 0.280969E+10 | 0.129552E+10 |
February | 0.223305E+10 | 0.177576E+10 | 0.457281E+09 | 0.222491E+10 | 0.125720E+10 |
March | 0.185679E+10 | 0.122738E+10 | 0.629404E+09 | 0.165579E+10 | 0.114569E+10 |
April | 0.117601E+10 | 0.486422E+09 | 0.689591E+09 | 0.796246E+09 | 0.103401E+10 |
May | 0.110423E+10 | 0.212197E+09 | 0.892030E+09 | 0.817034E+09 | 0.627706E+09 |
June | 0.971351E+09 | 0.175053E+09 | 0.796298E+09 | 0.968514E+09 | 0.302023E+09 |
July | 0.103687E+10 | 0.176441E+09 | 0.860431E+09 | 0.107534E+10 | 0.281219E+09 |
August | 0.131932E+10 | 0.542625E+09 | 0.776697E+09 | 0.126129E+10 | 0.321463E+09 |
September | 0.167763E+10 | 0.943060E+09 | 0.734571E+09 | 0.173676E+10 | 0.485397E+09 |
October | 0.204728E+10 | 0.145090E+10 | 0.596380E+09 | 0.208802E+10 | 0.110458E+10 |
November | 0.242760E+10 | 0.193643E+10 | 0.491170E+09 | 0.263210E+10 | 0.120602E+10 |
December | 0.239319E+10 | 0.193731E+10 | 0.455884E+09 | 0.253711E+10 | 0.148553E+10 |
Annual Sum or Average | 0.208548E+11 | 0.130133E+11 | 0.784143E+10 | 0.206028E+11 | 0.105464E+11 |
Minimum of Months | 0.971351E+09 | 0.175053E+09 | 0.455884E+09 | 0.796246E+09 | 0.281219E+09 |
Maximum of Months | 0.261144E+10 | 0.214975E+10 | 0.892030E+09 | 0.280969E+10 | 0.148553E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1394.92 | 642.48 | 1322.51 | 1088.69 | 233.81 | 0.00 | 0.00 |
February | 1228.83 | 672.33 | 1252.04 | 995.65 | 256.39 | 0.00 | 0.00 |
March | 828.68 | 540.64 | 940.33 | 621.58 | 318.75 | 0.00 | 0.00 |
April | 418.54 | 485.99 | 615.42 | 254.55 | 360.87 | 0.00 | 0.00 |
May | 414.06 | 292.38 | 559.21 | 107.46 | 451.75 | 0.00 | 0.00 |
June | 494.73 | 153.45 | 508.32 | 91.61 | 416.71 | 0.00 | 0.00 |
July | 532.20 | 137.95 | 525.10 | 89.35 | 435.75 | 0.00 | 0.00 |
August | 621.52 | 159.40 | 668.14 | 274.80 | 393.34 | 0.00 | 0.00 |
September | 885.67 | 248.89 | 877.92 | 493.51 | 384.41 | 0.00 | 0.00 |
October | 1037.85 | 529.85 | 1036.80 | 734.77 | 302.02 | 0.00 | 0.00 |
November | 1352.18 | 608.52 | 1270.38 | 1013.35 | 257.03 | 0.00 | 0.00 |
December | 1269.61 | 719.86 | 1211.98 | 981.11 | 230.87 | 0.00 | 0.00 |
Annual Sum or Average | 871.25 | 431.32 | 897.00 | 559.72 | 337.27 | 0.00 | 0.00 |
Minimum of Months | 414.06 | 137.95 | 508.32 | 89.35 | 230.87 | 0.00 | 0.00 |
Maximum of Months | 1394.92 | 719.86 | 1322.51 | 1088.69 | 451.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3891.37 | 1894.88 | 3724.09 | 3065.69 | 658.40 | 0.00 | 0.00 |
February | 3423.30 | 1988.59 | 3525.67 | 2803.68 | 721.98 | 0.00 | 0.00 |
March | 2305.79 | 1620.07 | 2647.90 | 1750.33 | 897.57 | 0.00 | 0.00 |
April | 1152.60 | 1467.23 | 1732.98 | 716.79 | 1016.18 | 0.00 | 0.00 |
May | 1147.10 | 862.48 | 1574.70 | 302.61 | 1272.09 | 0.00 | 0.00 |
June | 1384.41 | 438.34 | 1431.38 | 257.96 | 1173.43 | 0.00 | 0.00 |
July | 1490.26 | 394.92 | 1478.65 | 251.62 | 1227.03 | 0.00 | 0.00 |
August | 1741.69 | 456.89 | 1881.44 | 773.82 | 1107.62 | 0.00 | 0.00 |
September | 2485.30 | 723.95 | 2472.16 | 1389.70 | 1082.47 | 0.00 | 0.00 |
October | 2904.19 | 1568.66 | 2919.55 | 2069.07 | 850.48 | 0.00 | 0.00 |
November | 3775.19 | 1799.80 | 3577.31 | 2853.52 | 723.79 | 0.00 | 0.00 |
December | 3537.97 | 2131.52 | 3412.85 | 2762.73 | 650.12 | 0.00 | 0.00 |
Annual Sum or Average | 2431.09 | 1274.99 | 2525.89 | 1576.15 | 949.74 | 0.00 | 0.00 |
Minimum of Months | 1147.10 | 394.92 | 1431.38 | 251.62 | 650.12 | 0.00 | 0.00 |
Maximum of Months | 3891.37 | 2131.52 | 3724.09 | 3065.69 | 1272.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5169.90 | 2524.13 | 4837.80 | 3982.50 | 855.30 | 0.00 | 0.00 |
February | 4552.91 | 2671.36 | 4580.04 | 3642.14 | 937.90 | 0.00 | 0.00 |
March | 3060.39 | 2203.22 | 3439.78 | 2273.78 | 1166.00 | 0.00 | 0.00 |
April | 1519.48 | 2017.65 | 2251.23 | 931.15 | 1320.08 | 0.00 | 0.00 |
May | 1519.24 | 1173.98 | 2045.63 | 393.10 | 1652.52 | 0.00 | 0.00 |
June | 1861.21 | 583.34 | 1859.45 | 335.10 | 1524.35 | 0.00 | 0.00 |
July | 2002.94 | 522.97 | 1920.85 | 326.86 | 1593.99 | 0.00 | 0.00 |
August | 2341.02 | 599.14 | 2444.10 | 1005.24 | 1438.86 | 0.00 | 0.00 |
September | 3321.72 | 950.85 | 3211.48 | 1805.29 | 1406.18 | 0.00 | 0.00 |
October | 3861.21 | 2115.16 | 3792.66 | 2687.85 | 1104.82 | 0.00 | 0.00 |
November | 5015.78 | 2406.66 | 4647.13 | 3706.89 | 940.24 | 0.00 | 0.00 |
December | 4688.79 | 2869.18 | 4433.49 | 3588.94 | 844.54 | 0.00 | 0.00 |
Annual Sum or Average | 3235.55 | 1714.51 | 3281.27 | 2047.51 | 1233.76 | 0.00 | 0.00 |
Minimum of Months | 1519.24 | 522.97 | 1859.45 | 326.86 | 844.54 | 0.00 | 0.00 |
Maximum of Months | 5169.90 | 2869.18 | 4837.80 | 3982.50 | 1652.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 386.42 | 349.69 | 429.85 | 321.86 | 107.98 | 0.00 | 0.00 |
February | 387.35 | 370.90 | 451.05 | 323.00 | 128.05 | 0.00 | 0.00 |
March | 367.40 | 289.69 | 423.47 | 253.72 | 169.75 | 0.00 | 0.00 |
April | 267.13 | 258.26 | 345.84 | 145.30 | 200.54 | 0.00 | 0.00 |
May | 360.57 | 141.02 | 384.68 | 118.08 | 266.60 | 0.00 | 0.00 |
June | 520.77 | 62.48 | 435.20 | 179.06 | 256.14 | 0.00 | 0.00 |
July | 455.46 | 53.09 | 376.19 | 117.14 | 259.05 | 0.00 | 0.00 |
August | 481.64 | 62.48 | 417.29 | 195.28 | 222.01 | 0.00 | 0.00 |
September | 476.46 | 111.82 | 427.24 | 219.60 | 207.64 | 0.00 | 0.00 |
October | 405.09 | 278.29 | 417.26 | 266.55 | 150.72 | 0.00 | 0.00 |
November | 398.94 | 325.53 | 425.32 | 306.03 | 119.29 | 0.00 | 0.00 |
December | 325.52 | 404.50 | 380.02 | 276.79 | 103.24 | 0.00 | 0.00 |
Annual Sum or Average | 402.71 | 224.85 | 409.12 | 226.23 | 182.89 | 0.00 | 0.00 |
Minimum of Months | 267.13 | 53.09 | 345.84 | 117.14 | 103.24 | 0.00 | 0.00 |
Maximum of Months | 520.77 | 404.50 | 451.05 | 323.00 | 266.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 124.54 | 374.38 | 196.03 | 107.05 | 88.97 | 0.00 | 0.00 |
February | 154.34 | 387.32 | 238.10 | 126.54 | 111.55 | 0.00 | 0.00 |
March | 218.39 | 293.29 | 284.34 | 131.08 | 153.26 | 0.00 | 0.00 |
April | 207.88 | 257.07 | 282.74 | 95.45 | 187.30 | 0.00 | 0.00 |
May | 330.51 | 140.50 | 354.02 | 99.54 | 254.48 | 0.00 | 0.00 |
June | 504.63 | 64.39 | 422.26 | 170.73 | 251.52 | 0.00 | 0.00 |
July | 433.17 | 55.74 | 355.44 | 105.15 | 250.29 | 0.00 | 0.00 |
August | 422.36 | 66.87 | 351.42 | 142.83 | 208.59 | 0.00 | 0.00 |
September | 347.92 | 116.54 | 309.26 | 122.27 | 186.99 | 0.00 | 0.00 |
October | 214.34 | 280.22 | 252.21 | 121.56 | 130.65 | 0.00 | 0.00 |
November | 141.36 | 337.27 | 204.66 | 106.09 | 98.58 | 0.00 | 0.00 |
December | 91.56 | 433.44 | 166.26 | 83.20 | 83.06 | 0.00 | 0.00 |
Annual Sum or Average | 266.45 | 233.10 | 284.89 | 117.49 | 167.41 | 0.00 | 0.00 |
Minimum of Months | 91.56 | 55.74 | 166.26 | 83.20 | 83.06 | 0.00 | 0.00 |
Maximum of Months | 504.63 | 433.44 | 422.26 | 170.73 | 254.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 216.56 | 119.69 | 208.72 | 171.82 | 36.90 | 0.00 | 0.00 |
February | 191.25 | 121.38 | 197.60 | 157.13 | 40.46 | 0.00 | 0.00 |
March | 128.94 | 98.41 | 148.40 | 98.10 | 50.30 | 0.00 | 0.00 |
April | 63.73 | 91.42 | 97.13 | 40.17 | 56.95 | 0.00 | 0.00 |
May | 59.58 | 58.38 | 88.25 | 16.96 | 71.29 | 0.00 | 0.00 |
June | 73.62 | 32.59 | 80.22 | 14.46 | 65.77 | 0.00 | 0.00 |
July | 79.64 | 30.11 | 82.87 | 14.10 | 68.77 | 0.00 | 0.00 |
August | 94.60 | 34.16 | 105.45 | 43.37 | 62.08 | 0.00 | 0.00 |
September | 136.96 | 50.27 | 138.55 | 77.89 | 60.67 | 0.00 | 0.00 |
October | 161.84 | 99.93 | 163.63 | 115.96 | 47.67 | 0.00 | 0.00 |
November | 211.56 | 112.43 | 200.49 | 159.93 | 40.57 | 0.00 | 0.00 |
December | 197.63 | 129.84 | 191.27 | 154.84 | 36.44 | 0.00 | 0.00 |
Annual Sum or Average | 134.34 | 81.33 | 141.56 | 88.34 | 53.23 | 0.00 | 0.00 |
Minimum of Months | 59.58 | 30.11 | 80.22 | 14.10 | 36.44 | 0.00 | 0.00 |
Maximum of Months | 216.56 | 129.84 | 208.72 | 171.82 | 71.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.75 | 113.90 | 21.70 | 0.00 | 21.70 | 0.00 | 0.00 |
February | 3.34 | 117.59 | 27.28 | 0.00 | 27.28 | 0.00 | 0.00 |
March | 13.12 | 86.94 | 37.13 | 0.00 | 37.13 | 0.00 | 0.00 |
April | 20.65 | 75.32 | 46.67 | 0.30 | 46.37 | 0.00 | 0.00 |
May | 49.92 | 38.63 | 63.76 | 2.13 | 61.62 | 0.00 | 0.00 |
June | 81.44 | 16.30 | 69.89 | 7.80 | 62.09 | 0.00 | 0.00 |
July | 81.54 | 14.41 | 66.30 | 4.52 | 61.78 | 0.00 | 0.00 |
August | 63.96 | 17.38 | 52.78 | 1.42 | 51.36 | 0.00 | 0.00 |
September | 48.10 | 31.55 | 44.20 | 0.03 | 44.17 | 0.00 | 0.00 |
October | 15.17 | 80.74 | 31.62 | 0.00 | 31.62 | 0.00 | 0.00 |
November | 4.97 | 101.15 | 24.01 | 0.00 | 24.01 | 0.00 | 0.00 |
December | 2.43 | 131.64 | 20.31 | 0.00 | 20.31 | 0.00 | 0.00 |
Annual Sum or Average | 32.45 | 68.54 | 42.22 | 1.35 | 40.86 | 0.00 | 0.00 |
Minimum of Months | 2.43 | 14.41 | 20.31 | 0.00 | 20.31 | 0.00 | 0.00 |
Maximum of Months | 81.54 | 131.64 | 69.89 | 7.80 | 62.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 369.08 | 346.07 | 419.07 | 311.54 | 107.53 | 0.00 | 0.00 |
February | 395.09 | 369.40 | 458.98 | 330.59 | 128.39 | 0.00 | 0.00 |
March | 382.86 | 286.17 | 440.85 | 271.68 | 169.18 | 0.00 | 0.00 |
April | 305.19 | 252.59 | 382.07 | 177.18 | 204.89 | 0.00 | 0.00 |
May | 390.83 | 132.37 | 415.84 | 149.08 | 266.76 | 0.00 | 0.00 |
June | 561.73 | 56.41 | 472.01 | 213.13 | 258.88 | 0.00 | 0.00 |
July | 532.89 | 49.71 | 441.02 | 177.94 | 263.08 | 0.00 | 0.00 |
August | 546.49 | 59.97 | 473.04 | 242.20 | 230.84 | 0.00 | 0.00 |
September | 506.62 | 106.09 | 457.63 | 251.99 | 205.64 | 0.00 | 0.00 |
October | 391.29 | 274.51 | 410.35 | 257.83 | 152.52 | 0.00 | 0.00 |
November | 375.40 | 323.58 | 410.36 | 289.95 | 120.41 | 0.00 | 0.00 |
December | 321.21 | 404.71 | 377.66 | 273.42 | 104.24 | 0.00 | 0.00 |
Annual Sum or Average | 423.30 | 220.99 | 429.66 | 244.98 | 184.68 | 0.00 | 0.00 |
Minimum of Months | 305.19 | 49.71 | 377.66 | 149.08 | 104.24 | 0.00 | 0.00 |
Maximum of Months | 561.73 | 404.71 | 473.04 | 330.59 | 266.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 101.43 | 364.09 | 185.25 | 96.72 | 88.53 | 0.00 | 0.00 |
February | 158.12 | 381.66 | 246.03 | 134.13 | 111.90 | 0.00 | 0.00 |
March | 230.31 | 285.49 | 301.72 | 149.03 | 152.69 | 0.00 | 0.00 |
April | 245.62 | 250.79 | 318.97 | 127.33 | 191.64 | 0.00 | 0.00 |
May | 363.52 | 132.81 | 385.19 | 130.54 | 254.65 | 0.00 | 0.00 |
June | 546.45 | 60.64 | 459.07 | 204.81 | 254.26 | 0.00 | 0.00 |
July | 509.81 | 54.13 | 420.27 | 165.95 | 254.32 | 0.00 | 0.00 |
August | 485.59 | 64.35 | 407.18 | 189.76 | 217.42 | 0.00 | 0.00 |
September | 377.77 | 109.22 | 339.65 | 154.65 | 185.00 | 0.00 | 0.00 |
October | 198.57 | 272.99 | 245.30 | 112.85 | 132.45 | 0.00 | 0.00 |
November | 113.89 | 330.74 | 189.70 | 90.00 | 99.70 | 0.00 | 0.00 |
December | 80.49 | 426.14 | 163.90 | 79.84 | 84.07 | 0.00 | 0.00 |
Annual Sum or Average | 284.93 | 226.93 | 305.43 | 136.23 | 169.20 | 0.00 | 0.00 |
Minimum of Months | 80.49 | 54.13 | 163.90 | 79.84 | 84.07 | 0.00 | 0.00 |
Maximum of Months | 546.45 | 426.14 | 459.07 | 204.81 | 254.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 471.73 | 421.47 | 499.25 | 372.28 | 126.97 | 0.00 | 0.00 |
February | 422.48 | 451.23 | 487.24 | 340.46 | 146.77 | 0.00 | 0.00 |
March | 322.76 | 361.34 | 401.99 | 212.55 | 189.43 | 0.00 | 0.00 |
April | 201.17 | 317.52 | 311.55 | 87.70 | 223.85 | 0.00 | 0.00 |
May | 273.78 | 167.33 | 329.34 | 41.37 | 287.97 | 0.00 | 0.00 |
June | 366.39 | 75.24 | 325.23 | 48.23 | 277.00 | 0.00 | 0.00 |
July | 375.85 | 69.99 | 323.18 | 40.34 | 282.84 | 0.00 | 0.00 |
August | 372.59 | 81.86 | 342.82 | 97.05 | 245.77 | 0.00 | 0.00 |
September | 428.73 | 141.72 | 395.96 | 168.83 | 227.13 | 0.00 | 0.00 |
October | 402.43 | 342.26 | 423.04 | 251.26 | 171.79 | 0.00 | 0.00 |
November | 475.70 | 394.22 | 486.42 | 346.52 | 139.90 | 0.00 | 0.00 |
December | 422.18 | 486.97 | 458.43 | 335.49 | 122.94 | 0.00 | 0.00 |
Annual Sum or Average | 377.73 | 274.97 | 398.18 | 194.33 | 203.85 | 0.00 | 0.00 |
Minimum of Months | 201.17 | 69.99 | 311.55 | 40.34 | 122.94 | 0.00 | 0.00 |
Maximum of Months | 475.70 | 486.97 | 499.25 | 372.28 | 287.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 386.04 | 348.83 | 430.20 | 322.13 | 108.07 | 0.00 | 0.00 |
February | 385.68 | 371.86 | 451.42 | 323.26 | 128.15 | 0.00 | 0.00 |
March | 365.78 | 289.65 | 423.82 | 253.93 | 169.89 | 0.00 | 0.00 |
April | 264.96 | 258.73 | 346.13 | 145.42 | 200.71 | 0.00 | 0.00 |
May | 356.97 | 141.71 | 385.00 | 118.18 | 266.82 | 0.00 | 0.00 |
June | 517.38 | 62.33 | 435.56 | 179.20 | 256.35 | 0.00 | 0.00 |
July | 453.17 | 52.50 | 376.50 | 117.23 | 259.27 | 0.00 | 0.00 |
August | 478.74 | 62.21 | 417.63 | 195.44 | 222.19 | 0.00 | 0.00 |
September | 474.71 | 111.13 | 427.59 | 219.78 | 207.81 | 0.00 | 0.00 |
October | 403.73 | 277.76 | 417.60 | 266.76 | 150.84 | 0.00 | 0.00 |
November | 397.58 | 325.40 | 425.67 | 306.28 | 119.39 | 0.00 | 0.00 |
December | 324.77 | 405.22 | 380.34 | 277.01 | 103.32 | 0.00 | 0.00 |
Annual Sum or Average | 400.77 | 224.81 | 409.46 | 226.42 | 183.04 | 0.00 | 0.00 |
Minimum of Months | 264.96 | 52.50 | 346.13 | 117.23 | 103.32 | 0.00 | 0.00 |
Maximum of Months | 517.38 | 405.22 | 451.42 | 323.26 | 266.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 125.18 | 372.14 | 196.19 | 107.14 | 89.05 | 0.00 | 0.00 |
February | 153.97 | 387.37 | 238.29 | 126.65 | 111.65 | 0.00 | 0.00 |
March | 216.96 | 293.19 | 284.57 | 131.19 | 153.39 | 0.00 | 0.00 |
April | 205.47 | 257.57 | 282.98 | 95.53 | 187.45 | 0.00 | 0.00 |
May | 325.37 | 142.44 | 354.31 | 99.63 | 254.69 | 0.00 | 0.00 |
June | 499.86 | 66.27 | 422.61 | 170.88 | 251.73 | 0.00 | 0.00 |
July | 430.00 | 56.59 | 355.73 | 105.24 | 250.49 | 0.00 | 0.00 |
August | 418.45 | 68.36 | 351.71 | 142.95 | 208.76 | 0.00 | 0.00 |
September | 345.41 | 117.65 | 309.52 | 122.37 | 187.15 | 0.00 | 0.00 |
October | 213.17 | 279.77 | 252.42 | 121.66 | 130.76 | 0.00 | 0.00 |
November | 141.24 | 336.12 | 204.83 | 106.17 | 98.66 | 0.00 | 0.00 |
December | 92.16 | 433.05 | 166.40 | 83.27 | 83.13 | 0.00 | 0.00 |
Annual Sum or Average | 264.47 | 233.39 | 285.13 | 117.58 | 167.55 | 0.00 | 0.00 |
Minimum of Months | 92.16 | 56.59 | 166.40 | 83.27 | 83.13 | 0.00 | 0.00 |
Maximum of Months | 499.86 | 433.05 | 422.61 | 170.88 | 254.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 408.42 | 182.16 | 383.02 | 315.30 | 67.72 | 0.00 | 0.00 |
February | 358.95 | 195.33 | 362.61 | 288.36 | 74.26 | 0.00 | 0.00 |
March | 244.52 | 153.42 | 272.34 | 180.02 | 92.31 | 0.00 | 0.00 |
April | 125.05 | 137.60 | 178.24 | 73.72 | 104.51 | 0.00 | 0.00 |
May | 129.59 | 74.06 | 161.96 | 31.12 | 130.83 | 0.00 | 0.00 |
June | 161.21 | 30.37 | 147.22 | 26.53 | 120.69 | 0.00 | 0.00 |
July | 172.38 | 25.90 | 152.08 | 25.88 | 126.20 | 0.00 | 0.00 |
August | 196.85 | 31.19 | 193.51 | 79.59 | 113.92 | 0.00 | 0.00 |
September | 270.91 | 56.89 | 254.26 | 142.93 | 111.33 | 0.00 | 0.00 |
October | 308.09 | 145.07 | 300.27 | 212.80 | 87.47 | 0.00 | 0.00 |
November | 396.73 | 171.12 | 367.93 | 293.48 | 74.44 | 0.00 | 0.00 |
December | 367.25 | 212.24 | 351.01 | 284.15 | 66.86 | 0.00 | 0.00 |
Annual Sum or Average | 261.12 | 117.52 | 259.79 | 162.11 | 97.68 | 0.00 | 0.00 |
Minimum of Months | 125.05 | 25.90 | 147.22 | 25.88 | 66.86 | 0.00 | 0.00 |
Maximum of Months | 408.42 | 212.24 | 383.02 | 315.30 | 130.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.01 | 1192.31 | 190.04 | 0.00 | 190.04 | 0.00 | 0.00 |
February | 12.55 | 1236.40 | 238.86 | 0.00 | 238.86 | 0.00 | 0.00 |
March | 72.95 | 948.14 | 325.11 | 0.02 | 325.09 | 0.00 | 0.00 |
April | 126.60 | 839.93 | 408.66 | 2.65 | 406.01 | 0.00 | 0.00 |
May | 352.11 | 461.57 | 558.23 | 18.66 | 539.56 | 0.00 | 0.00 |
June | 615.55 | 212.86 | 611.97 | 68.33 | 543.64 | 0.00 | 0.00 |
July | 618.62 | 198.03 | 580.47 | 39.55 | 540.93 | 0.00 | 0.00 |
August | 476.03 | 233.92 | 462.16 | 12.44 | 449.72 | 0.00 | 0.00 |
September | 352.69 | 381.45 | 387.02 | 0.30 | 386.72 | 0.00 | 0.00 |
October | 87.88 | 885.99 | 276.90 | 0.00 | 276.90 | 0.00 | 0.00 |
November | 23.94 | 1090.10 | 210.20 | 0.00 | 210.20 | 0.00 | 0.00 |
December | 9.73 | 1354.41 | 177.81 | 0.00 | 177.81 | 0.00 | 0.00 |
Annual Sum or Average | 231.04 | 750.29 | 369.63 | 11.86 | 357.77 | 0.00 | 0.00 |
Minimum of Months | 9.01 | 198.03 | 177.81 | 0.00 | 177.81 | 0.00 | 0.00 |
Maximum of Months | 618.62 | 1354.41 | 611.97 | 68.33 | 543.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.84 | 1244.01 | 190.04 | 0.00 | 190.04 | 0.00 | 0.00 |
February | 10.08 | 1291.20 | 238.86 | 0.00 | 238.86 | 0.00 | 0.00 |
March | 64.43 | 994.97 | 325.11 | 0.02 | 325.09 | 0.00 | 0.00 |
April | 114.41 | 881.95 | 408.66 | 2.65 | 406.01 | 0.00 | 0.00 |
May | 333.50 | 485.08 | 558.23 | 18.66 | 539.56 | 0.00 | 0.00 |
June | 595.22 | 225.82 | 611.97 | 68.33 | 543.64 | 0.00 | 0.00 |
July | 598.90 | 211.31 | 580.47 | 39.55 | 540.93 | 0.00 | 0.00 |
August | 459.32 | 248.70 | 462.16 | 12.44 | 449.72 | 0.00 | 0.00 |
September | 338.85 | 400.58 | 387.02 | 0.30 | 386.72 | 0.00 | 0.00 |
October | 79.45 | 924.10 | 276.90 | 0.00 | 276.90 | 0.00 | 0.00 |
November | 20.98 | 1138.90 | 210.20 | 0.00 | 210.20 | 0.00 | 0.00 |
December | 7.78 | 1410.24 | 177.81 | 0.00 | 177.81 | 0.00 | 0.00 |
Annual Sum or Average | 220.34 | 785.32 | 369.63 | 11.86 | 357.77 | 0.00 | 0.00 |
Minimum of Months | 6.84 | 211.31 | 177.81 | 0.00 | 177.81 | 0.00 | 0.00 |
Maximum of Months | 598.90 | 1410.24 | 611.97 | 68.33 | 543.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 415.77 | 850.72 | 604.79 | 408.58 | 196.21 | 0.00 | 0.00 |
February | 498.49 | 921.22 | 705.56 | 465.08 | 240.48 | 0.00 | 0.00 |
March | 575.08 | 752.66 | 743.15 | 421.03 | 322.11 | 0.00 | 0.00 |
April | 509.17 | 694.85 | 701.57 | 304.74 | 396.84 | 0.00 | 0.00 |
May | 724.29 | 394.82 | 801.64 | 279.83 | 521.81 | 0.00 | 0.00 |
June | 1088.51 | 200.52 | 931.79 | 418.25 | 513.53 | 0.00 | 0.00 |
July | 1025.03 | 189.66 | 861.94 | 344.15 | 517.80 | 0.00 | 0.00 |
August | 1022.96 | 209.47 | 880.89 | 432.29 | 448.60 | 0.00 | 0.00 |
September | 879.28 | 314.51 | 797.90 | 406.95 | 390.94 | 0.00 | 0.00 |
October | 569.89 | 716.13 | 656.16 | 370.97 | 285.19 | 0.00 | 0.00 |
November | 447.02 | 818.02 | 600.53 | 380.24 | 220.28 | 0.00 | 0.00 |
December | 345.79 | 1001.97 | 541.99 | 353.54 | 188.46 | 0.00 | 0.00 |
Annual Sum or Average | 675.94 | 586.88 | 735.66 | 381.51 | 354.16 | 0.00 | 0.00 |
Minimum of Months | 345.79 | 189.66 | 541.99 | 279.83 | 188.46 | 0.00 | 0.00 |
Maximum of Months | 1088.51 | 1001.97 | 931.79 | 465.08 | 521.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 994.29 | 804.22 | 1040.15 | 802.62 | 237.52 | 0.00 | 0.00 |
February | 879.79 | 863.58 | 1004.93 | 734.03 | 270.90 | 0.00 | 0.00 |
March | 636.40 | 710.45 | 804.69 | 458.26 | 346.44 | 0.00 | 0.00 |
April | 354.84 | 655.16 | 593.80 | 188.57 | 405.23 | 0.00 | 0.00 |
May | 431.72 | 375.75 | 603.63 | 85.62 | 518.01 | 0.00 | 0.00 |
June | 584.91 | 179.90 | 584.53 | 90.96 | 493.58 | 0.00 | 0.00 |
July | 614.96 | 165.12 | 586.11 | 79.43 | 506.68 | 0.00 | 0.00 |
August | 635.50 | 194.42 | 651.01 | 206.86 | 444.15 | 0.00 | 0.00 |
September | 790.95 | 308.63 | 779.91 | 363.94 | 415.97 | 0.00 | 0.00 |
October | 803.02 | 683.37 | 859.29 | 541.70 | 317.58 | 0.00 | 0.00 |
November | 985.87 | 772.19 | 1008.63 | 747.08 | 261.55 | 0.00 | 0.00 |
December | 893.25 | 922.35 | 954.47 | 723.31 | 231.16 | 0.00 | 0.00 |
Annual Sum or Average | 716.20 | 551.19 | 788.01 | 416.72 | 371.29 | 0.00 | 0.00 |
Minimum of Months | 354.84 | 165.12 | 584.53 | 79.43 | 231.16 | 0.00 | 0.00 |
Maximum of Months | 994.29 | 922.35 | 1040.15 | 802.62 | 518.01 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.373616E+10 | 0.172082E+10 | 0.354220E+10 | 0.291595E+10 | 0.626244E+09 | 0.00 | 0.00 |
February | 0.297278E+10 | 0.162650E+10 | 0.302894E+10 | 0.240868E+10 | 0.620264E+09 | 0.00 | 0.00 |
March | 0.221955E+10 | 0.144806E+10 | 0.251858E+10 | 0.166484E+10 | 0.853733E+09 | 0.00 | 0.00 |
April | 0.108487E+10 | 0.125970E+10 | 0.159516E+10 | 0.659791E+09 | 0.935372E+09 | 0.00 | 0.00 |
May | 0.110901E+10 | 0.783102E+09 | 0.149779E+10 | 0.287827E+09 | 0.120996E+10 | 0.00 | 0.00 |
June | 0.128233E+10 | 0.397743E+09 | 0.131756E+10 | 0.237445E+09 | 0.108011E+10 | 0.00 | 0.00 |
July | 0.142544E+10 | 0.369481E+09 | 0.140643E+10 | 0.239327E+09 | 0.116710E+10 | 0.00 | 0.00 |
August | 0.166467E+10 | 0.426924E+09 | 0.178955E+10 | 0.736026E+09 | 0.105352E+10 | 0.00 | 0.00 |
September | 0.229566E+10 | 0.645115E+09 | 0.227557E+10 | 0.127918E+10 | 0.996383E+09 | 0.00 | 0.00 |
October | 0.277978E+10 | 0.141916E+10 | 0.277696E+10 | 0.196802E+10 | 0.808939E+09 | 0.00 | 0.00 |
November | 0.350484E+10 | 0.157729E+10 | 0.329283E+10 | 0.262660E+10 | 0.666231E+09 | 0.00 | 0.00 |
December | 0.340053E+10 | 0.192806E+10 | 0.324616E+10 | 0.262779E+10 | 0.618368E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.274756E+11 | 0.136020E+11 | 0.282877E+11 | 0.176515E+11 | 0.106362E+11 | 0.00 | 0.00 |
Minimum of Months | 0.108487E+10 | 0.369481E+09 | 0.131756E+10 | 0.237445E+09 | 0.618368E+09 | 0.00 | 0.00 |
Maximum of Months | 0.373616E+10 | 0.192806E+10 | 0.354220E+10 | 0.291595E+10 | 0.120996E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104227E+11 | 0.507525E+10 | 0.997460E+10 | 0.821113E+10 | 0.176346E+10 | 0.00 | 0.00 |
February | 0.828164E+10 | 0.481081E+10 | 0.852929E+10 | 0.678267E+10 | 0.174662E+10 | 0.00 | 0.00 |
March | 0.617582E+10 | 0.433919E+10 | 0.709214E+10 | 0.468809E+10 | 0.240406E+10 | 0.00 | 0.00 |
April | 0.298754E+10 | 0.380307E+10 | 0.449187E+10 | 0.185793E+10 | 0.263395E+10 | 0.00 | 0.00 |
May | 0.307240E+10 | 0.231007E+10 | 0.421768E+10 | 0.810503E+09 | 0.340718E+10 | 0.00 | 0.00 |
June | 0.358839E+10 | 0.113618E+10 | 0.371015E+10 | 0.668629E+09 | 0.304152E+10 | 0.00 | 0.00 |
July | 0.399151E+10 | 0.105776E+10 | 0.396041E+10 | 0.673929E+09 | 0.328648E+10 | 0.00 | 0.00 |
August | 0.466493E+10 | 0.122375E+10 | 0.503925E+10 | 0.207260E+10 | 0.296665E+10 | 0.00 | 0.00 |
September | 0.644190E+10 | 0.187647E+10 | 0.640784E+10 | 0.360209E+10 | 0.280575E+10 | 0.00 | 0.00 |
October | 0.777858E+10 | 0.420149E+10 | 0.781973E+10 | 0.554181E+10 | 0.227792E+10 | 0.00 | 0.00 |
November | 0.978528E+10 | 0.466509E+10 | 0.927240E+10 | 0.739634E+10 | 0.187606E+10 | 0.00 | 0.00 |
December | 0.947610E+10 | 0.570906E+10 | 0.914098E+10 | 0.739970E+10 | 0.174128E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.766667E+11 | 0.402082E+11 | 0.796564E+11 | 0.497054E+11 | 0.299509E+11 | 0.00 | 0.00 |
Minimum of Months | 0.298754E+10 | 0.105776E+10 | 0.371015E+10 | 0.668629E+09 | 0.174128E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104227E+11 | 0.570906E+10 | 0.997460E+10 | 0.821113E+10 | 0.340718E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138471E+11 | 0.676064E+10 | 0.129576E+11 | 0.106667E+11 | 0.229084E+10 | 0.00 | 0.00 |
February | 0.110144E+11 | 0.646256E+10 | 0.110800E+11 | 0.881108E+10 | 0.226896E+10 | 0.00 | 0.00 |
March | 0.819695E+10 | 0.590110E+10 | 0.921310E+10 | 0.609009E+10 | 0.312301E+10 | 0.00 | 0.00 |
April | 0.393850E+10 | 0.522974E+10 | 0.583520E+10 | 0.241355E+10 | 0.342165E+10 | 0.00 | 0.00 |
May | 0.406913E+10 | 0.314439E+10 | 0.547901E+10 | 0.105289E+10 | 0.442612E+10 | 0.00 | 0.00 |
June | 0.482427E+10 | 0.151201E+10 | 0.481970E+10 | 0.868587E+09 | 0.395111E+10 | 0.00 | 0.00 |
July | 0.536469E+10 | 0.140074E+10 | 0.514480E+10 | 0.875473E+09 | 0.426933E+10 | 0.00 | 0.00 |
August | 0.627018E+10 | 0.160473E+10 | 0.654628E+10 | 0.269243E+10 | 0.385385E+10 | 0.00 | 0.00 |
September | 0.860991E+10 | 0.246460E+10 | 0.832415E+10 | 0.467932E+10 | 0.364483E+10 | 0.00 | 0.00 |
October | 0.103419E+11 | 0.566525E+10 | 0.101583E+11 | 0.719913E+10 | 0.295915E+10 | 0.00 | 0.00 |
November | 0.130009E+11 | 0.623807E+10 | 0.120454E+11 | 0.960826E+10 | 0.243711E+10 | 0.00 | 0.00 |
December | 0.125585E+11 | 0.768481E+10 | 0.118747E+11 | 0.961263E+10 | 0.226203E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.102036E+12 | 0.540686E+11 | 0.103478E+12 | 0.645702E+11 | 0.389080E+11 | 0.00 | 0.00 |
Minimum of Months | 0.393850E+10 | 0.140074E+10 | 0.481970E+10 | 0.868587E+09 | 0.226203E+10 | 0.00 | 0.00 |
Maximum of Months | 0.138471E+11 | 0.768481E+10 | 0.129576E+11 | 0.106667E+11 | 0.442612E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103499E+10 | 0.936615E+09 | 0.115130E+10 | 0.862083E+09 | 0.289219E+09 | 0.00 | 0.00 |
February | 0.937071E+09 | 0.897270E+09 | 0.109117E+10 | 0.781395E+09 | 0.309773E+09 | 0.00 | 0.00 |
March | 0.984048E+09 | 0.775912E+09 | 0.113423E+10 | 0.679574E+09 | 0.454658E+09 | 0.00 | 0.00 |
April | 0.692394E+09 | 0.669399E+09 | 0.896422E+09 | 0.376611E+09 | 0.519811E+09 | 0.00 | 0.00 |
May | 0.965747E+09 | 0.377716E+09 | 0.103033E+10 | 0.316274E+09 | 0.714054E+09 | 0.00 | 0.00 |
June | 0.134983E+10 | 0.161941E+09 | 0.112804E+10 | 0.464115E+09 | 0.663927E+09 | 0.00 | 0.00 |
July | 0.121992E+10 | 0.142200E+09 | 0.100759E+10 | 0.313738E+09 | 0.693847E+09 | 0.00 | 0.00 |
August | 0.129003E+10 | 0.167339E+09 | 0.111766E+10 | 0.523037E+09 | 0.594620E+09 | 0.00 | 0.00 |
September | 0.123498E+10 | 0.289846E+09 | 0.110741E+10 | 0.569208E+09 | 0.538203E+09 | 0.00 | 0.00 |
October | 0.108500E+10 | 0.745373E+09 | 0.111759E+10 | 0.713915E+09 | 0.403678E+09 | 0.00 | 0.00 |
November | 0.103406E+10 | 0.843770E+09 | 0.110244E+10 | 0.793240E+09 | 0.309201E+09 | 0.00 | 0.00 |
December | 0.871880E+09 | 0.108342E+10 | 0.101786E+10 | 0.741346E+09 | 0.276510E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.127000E+11 | 0.709080E+10 | 0.129020E+11 | 0.713454E+10 | 0.576750E+10 | 0.00 | 0.00 |
Minimum of Months | 0.692394E+09 | 0.142200E+09 | 0.896422E+09 | 0.313738E+09 | 0.276510E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134983E+10 | 0.108342E+10 | 0.115130E+10 | 0.862083E+09 | 0.714054E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.333555E+09 | 0.100274E+10 | 0.525034E+09 | 0.286724E+09 | 0.238310E+09 | 0.00 | 0.00 |
February | 0.373381E+09 | 0.937000E+09 | 0.576001E+09 | 0.306130E+09 | 0.269871E+09 | 0.00 | 0.00 |
March | 0.584932E+09 | 0.785552E+09 | 0.761580E+09 | 0.351083E+09 | 0.410497E+09 | 0.00 | 0.00 |
April | 0.538818E+09 | 0.666335E+09 | 0.732875E+09 | 0.247405E+09 | 0.485470E+09 | 0.00 | 0.00 |
May | 0.885242E+09 | 0.376308E+09 | 0.948218E+09 | 0.266618E+09 | 0.681600E+09 | 0.00 | 0.00 |
June | 0.130801E+10 | 0.166893E+09 | 0.109450E+10 | 0.442545E+09 | 0.651952E+09 | 0.00 | 0.00 |
July | 0.116019E+10 | 0.149300E+09 | 0.952009E+09 | 0.281636E+09 | 0.670374E+09 | 0.00 | 0.00 |
August | 0.113126E+10 | 0.179107E+09 | 0.941252E+09 | 0.382566E+09 | 0.558686E+09 | 0.00 | 0.00 |
September | 0.901802E+09 | 0.302082E+09 | 0.801606E+09 | 0.316919E+09 | 0.484687E+09 | 0.00 | 0.00 |
October | 0.574090E+09 | 0.750530E+09 | 0.675526E+09 | 0.325597E+09 | 0.349929E+09 | 0.00 | 0.00 |
November | 0.366393E+09 | 0.874210E+09 | 0.530491E+09 | 0.274974E+09 | 0.255517E+09 | 0.00 | 0.00 |
December | 0.245221E+09 | 0.116093E+10 | 0.445323E+09 | 0.222845E+09 | 0.222478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.840290E+10 | 0.735098E+10 | 0.898441E+10 | 0.370504E+10 | 0.527937E+10 | 0.00 | 0.00 |
Minimum of Months | 0.245221E+09 | 0.149300E+09 | 0.445323E+09 | 0.222845E+09 | 0.222478E+09 | 0.00 | 0.00 |
Maximum of Months | 0.130801E+10 | 0.116093E+10 | 0.109450E+10 | 0.442545E+09 | 0.681600E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.580031E+09 | 0.320575E+09 | 0.559030E+09 | 0.460196E+09 | 98833846.23 | 0.00 | 0.00 |
February | 0.462675E+09 | 0.293643E+09 | 0.478027E+09 | 0.380137E+09 | 97889987.60 | 0.00 | 0.00 |
March | 0.345354E+09 | 0.263580E+09 | 0.397482E+09 | 0.262745E+09 | 0.134736E+09 | 0.00 | 0.00 |
April | 0.165178E+09 | 0.236971E+09 | 0.251749E+09 | 0.104128E+09 | 0.147620E+09 | 0.00 | 0.00 |
May | 0.159587E+09 | 0.156373E+09 | 0.236381E+09 | 45424905.42 | 0.190956E+09 | 0.00 | 0.00 |
June | 0.190815E+09 | 84476483.63 | 0.207937E+09 | 37473543.83 | 0.170463E+09 | 0.00 | 0.00 |
July | 0.213312E+09 | 80640843.81 | 0.221963E+09 | 37770595.60 | 0.184192E+09 | 0.00 | 0.00 |
August | 0.253386E+09 | 91482570.53 | 0.282427E+09 | 0.116160E+09 | 0.166267E+09 | 0.00 | 0.00 |
September | 0.354992E+09 | 0.130293E+09 | 0.359130E+09 | 0.201880E+09 | 0.157249E+09 | 0.00 | 0.00 |
October | 0.433479E+09 | 0.267657E+09 | 0.438259E+09 | 0.310593E+09 | 0.127667E+09 | 0.00 | 0.00 |
November | 0.548351E+09 | 0.291428E+09 | 0.519675E+09 | 0.414530E+09 | 0.105145E+09 | 0.00 | 0.00 |
December | 0.529322E+09 | 0.347767E+09 | 0.512309E+09 | 0.414719E+09 | 97590842.16 | 0.00 | 0.00 |
Annual Sum or Average | 0.423648E+10 | 0.256489E+10 | 0.446437E+10 | 0.278576E+10 | 0.167861E+10 | 0.00 | 0.00 |
Minimum of Months | 0.159587E+09 | 80640843.81 | 0.207937E+09 | 37473543.83 | 97590842.16 | 0.00 | 0.00 |
Maximum of Months | 0.580031E+09 | 0.347767E+09 | 0.559030E+09 | 0.460196E+09 | 0.190956E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 7371143.39 | 0.305066E+09 | 58134338.25 | 0.00 | 58134338.25 | 0.00 | 0.00 |
February | 8074911.26 | 0.284477E+09 | 65996778.74 | 0.00 | 65996778.74 | 0.00 | 0.00 |
March | 35129912.40 | 0.232851E+09 | 99452333.57 | 4890.64 | 99447442.93 | 0.00 | 0.00 |
April | 53537507.80 | 0.195235E+09 | 0.120977E+09 | 784108.15 | 0.120193E+09 | 0.00 | 0.00 |
May | 0.133704E+09 | 0.103476E+09 | 0.170763E+09 | 5709650.14 | 0.165054E+09 | 0.00 | 0.00 |
June | 0.211082E+09 | 42243020.20 | 0.181166E+09 | 20227469.87 | 0.160938E+09 | 0.00 | 0.00 |
July | 0.218388E+09 | 38606231.68 | 0.177570E+09 | 12097671.79 | 0.165472E+09 | 0.00 | 0.00 |
August | 0.171323E+09 | 46544221.72 | 0.141378E+09 | 3806293.64 | 0.137571E+09 | 0.00 | 0.00 |
September | 0.124679E+09 | 81780216.09 | 0.114572E+09 | 89511.58 | 0.114483E+09 | 0.00 | 0.00 |
October | 40625970.33 | 0.216266E+09 | 84703640.46 | 0.00 | 84703640.46 | 0.00 | 0.00 |
November | 12890645.15 | 0.262191E+09 | 62226567.39 | 0.00 | 62226567.39 | 0.00 | 0.00 |
December | 6496494.33 | 0.352591E+09 | 54391946.60 | 0.00 | 54391946.60 | 0.00 | 0.00 |
Annual Sum or Average | 0.102330E+10 | 0.216133E+10 | 0.133133E+10 | 42719595.82 | 0.128861E+10 | 0.00 | 0.00 |
Minimum of Months | 6496494.33 | 38606231.68 | 54391946.60 | 0.00 | 54391946.60 | 0.00 | 0.00 |
Maximum of Months | 0.218388E+09 | 0.352591E+09 | 0.181166E+09 | 20227469.87 | 0.165472E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.988535E+09 | 0.926916E+09 | 0.112244E+10 | 0.834420E+09 | 0.288015E+09 | 0.00 | 0.00 |
February | 0.955814E+09 | 0.893651E+09 | 0.111037E+10 | 0.799760E+09 | 0.310611E+09 | 0.00 | 0.00 |
March | 0.102545E+10 | 0.766490E+09 | 0.118078E+10 | 0.727662E+09 | 0.453120E+09 | 0.00 | 0.00 |
April | 0.791057E+09 | 0.654713E+09 | 0.990316E+09 | 0.459240E+09 | 0.531077E+09 | 0.00 | 0.00 |
May | 0.104681E+10 | 0.354551E+09 | 0.111379E+10 | 0.399296E+09 | 0.714498E+09 | 0.00 | 0.00 |
June | 0.145599E+10 | 0.146207E+09 | 0.122345E+10 | 0.552432E+09 | 0.671013E+09 | 0.00 | 0.00 |
July | 0.142729E+10 | 0.133130E+09 | 0.118122E+10 | 0.476584E+09 | 0.704634E+09 | 0.00 | 0.00 |
August | 0.146373E+10 | 0.160628E+09 | 0.126699E+10 | 0.648719E+09 | 0.618269E+09 | 0.00 | 0.00 |
September | 0.131317E+10 | 0.274973E+09 | 0.118618E+10 | 0.653152E+09 | 0.533030E+09 | 0.00 | 0.00 |
October | 0.104803E+10 | 0.735246E+09 | 0.109908E+10 | 0.690575E+09 | 0.408502E+09 | 0.00 | 0.00 |
November | 0.973044E+09 | 0.838713E+09 | 0.106365E+10 | 0.751541E+09 | 0.312108E+09 | 0.00 | 0.00 |
December | 0.860328E+09 | 0.108396E+10 | 0.101153E+10 | 0.732334E+09 | 0.279200E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.133493E+11 | 0.696918E+10 | 0.135498E+11 | 0.772571E+10 | 0.582408E+10 | 0.00 | 0.00 |
Minimum of Months | 0.791057E+09 | 0.133130E+09 | 0.990316E+09 | 0.399296E+09 | 0.279200E+09 | 0.00 | 0.00 |
Maximum of Months | 0.146373E+10 | 0.108396E+10 | 0.126699E+10 | 0.834420E+09 | 0.714498E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.271677E+09 | 0.975188E+09 | 0.496168E+09 | 0.259061E+09 | 0.237107E+09 | 0.00 | 0.00 |
February | 0.382534E+09 | 0.923311E+09 | 0.595204E+09 | 0.324494E+09 | 0.270709E+09 | 0.00 | 0.00 |
March | 0.616853E+09 | 0.764649E+09 | 0.808130E+09 | 0.399171E+09 | 0.408959E+09 | 0.00 | 0.00 |
April | 0.636646E+09 | 0.650059E+09 | 0.826769E+09 | 0.330034E+09 | 0.496735E+09 | 0.00 | 0.00 |
May | 0.973665E+09 | 0.355712E+09 | 0.103168E+10 | 0.349640E+09 | 0.682045E+09 | 0.00 | 0.00 |
June | 0.141641E+10 | 0.157172E+09 | 0.118990E+10 | 0.530861E+09 | 0.659038E+09 | 0.00 | 0.00 |
July | 0.136549E+10 | 0.144979E+09 | 0.112564E+10 | 0.444481E+09 | 0.681160E+09 | 0.00 | 0.00 |
August | 0.130060E+10 | 0.172361E+09 | 0.109058E+10 | 0.508248E+09 | 0.582336E+09 | 0.00 | 0.00 |
September | 0.979181E+09 | 0.283096E+09 | 0.880377E+09 | 0.400863E+09 | 0.479513E+09 | 0.00 | 0.00 |
October | 0.531860E+09 | 0.731171E+09 | 0.657009E+09 | 0.302257E+09 | 0.354752E+09 | 0.00 | 0.00 |
November | 0.295190E+09 | 0.857270E+09 | 0.491700E+09 | 0.233275E+09 | 0.258424E+09 | 0.00 | 0.00 |
December | 0.215585E+09 | 0.114138E+10 | 0.439000E+09 | 0.213832E+09 | 0.225168E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.898569E+10 | 0.715635E+10 | 0.963217E+10 | 0.429622E+10 | 0.533595E+10 | 0.00 | 0.00 |
Minimum of Months | 0.215585E+09 | 0.144979E+09 | 0.439000E+09 | 0.213832E+09 | 0.225168E+09 | 0.00 | 0.00 |
Maximum of Months | 0.141641E+10 | 0.114138E+10 | 0.118990E+10 | 0.530861E+09 | 0.682045E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.126349E+10 | 0.112888E+10 | 0.133720E+10 | 0.997116E+09 | 0.340084E+09 | 0.00 | 0.00 |
February | 0.102205E+10 | 0.109161E+10 | 0.117872E+10 | 0.823651E+09 | 0.355072E+09 | 0.00 | 0.00 |
March | 0.864485E+09 | 0.967804E+09 | 0.107668E+10 | 0.569307E+09 | 0.507372E+09 | 0.00 | 0.00 |
April | 0.521432E+09 | 0.823012E+09 | 0.807545E+09 | 0.227315E+09 | 0.580230E+09 | 0.00 | 0.00 |
May | 0.733285E+09 | 0.448182E+09 | 0.882104E+09 | 0.110792E+09 | 0.771311E+09 | 0.00 | 0.00 |
June | 0.949679E+09 | 0.195031E+09 | 0.843006E+09 | 0.125014E+09 | 0.717992E+09 | 0.00 | 0.00 |
July | 0.100669E+10 | 0.187455E+09 | 0.865607E+09 | 0.108046E+09 | 0.757561E+09 | 0.00 | 0.00 |
August | 0.997949E+09 | 0.219267E+09 | 0.918212E+09 | 0.259931E+09 | 0.658280E+09 | 0.00 | 0.00 |
September | 0.111127E+10 | 0.367331E+09 | 0.102634E+10 | 0.437613E+09 | 0.588723E+09 | 0.00 | 0.00 |
October | 0.107786E+10 | 0.916704E+09 | 0.113308E+10 | 0.672968E+09 | 0.460115E+09 | 0.00 | 0.00 |
November | 0.123302E+10 | 0.102182E+10 | 0.126079E+10 | 0.898172E+09 | 0.362623E+09 | 0.00 | 0.00 |
December | 0.113078E+10 | 0.130431E+10 | 0.122786E+10 | 0.898580E+09 | 0.329283E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.119120E+11 | 0.867140E+10 | 0.125572E+11 | 0.612851E+10 | 0.642865E+10 | 0.00 | 0.00 |
Minimum of Months | 0.521432E+09 | 0.187455E+09 | 0.807545E+09 | 0.108046E+09 | 0.329283E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126349E+10 | 0.130431E+10 | 0.133720E+10 | 0.997116E+09 | 0.771311E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103396E+10 | 0.934296E+09 | 0.115225E+10 | 0.862790E+09 | 0.289456E+09 | 0.00 | 0.00 |
February | 0.933028E+09 | 0.899601E+09 | 0.109206E+10 | 0.782036E+09 | 0.310027E+09 | 0.00 | 0.00 |
March | 0.979703E+09 | 0.775809E+09 | 0.113516E+10 | 0.680132E+09 | 0.455031E+09 | 0.00 | 0.00 |
April | 0.686765E+09 | 0.670621E+09 | 0.897157E+09 | 0.376920E+09 | 0.520238E+09 | 0.00 | 0.00 |
May | 0.956101E+09 | 0.379568E+09 | 0.103117E+10 | 0.316534E+09 | 0.714639E+09 | 0.00 | 0.00 |
June | 0.134105E+10 | 0.161551E+09 | 0.112897E+10 | 0.464496E+09 | 0.664471E+09 | 0.00 | 0.00 |
July | 0.121376E+10 | 0.140607E+09 | 0.100841E+10 | 0.313995E+09 | 0.694416E+09 | 0.00 | 0.00 |
August | 0.128226E+10 | 0.166620E+09 | 0.111857E+10 | 0.523466E+09 | 0.595108E+09 | 0.00 | 0.00 |
September | 0.123045E+10 | 0.288062E+09 | 0.110832E+10 | 0.569675E+09 | 0.538645E+09 | 0.00 | 0.00 |
October | 0.108135E+10 | 0.743956E+09 | 0.111851E+10 | 0.714500E+09 | 0.404009E+09 | 0.00 | 0.00 |
November | 0.103054E+10 | 0.843427E+09 | 0.110334E+10 | 0.793890E+09 | 0.309454E+09 | 0.00 | 0.00 |
December | 0.869869E+09 | 0.108534E+10 | 0.101869E+10 | 0.741955E+09 | 0.276736E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.126388E+11 | 0.708946E+10 | 0.129126E+11 | 0.714039E+10 | 0.577223E+10 | 0.00 | 0.00 |
Minimum of Months | 0.686765E+09 | 0.140607E+09 | 0.897157E+09 | 0.313995E+09 | 0.276736E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134105E+10 | 0.108534E+10 | 0.115225E+10 | 0.862790E+09 | 0.714639E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.335277E+09 | 0.996739E+09 | 0.525465E+09 | 0.286959E+09 | 0.238506E+09 | 0.00 | 0.00 |
February | 0.372486E+09 | 0.937132E+09 | 0.576473E+09 | 0.306381E+09 | 0.270093E+09 | 0.00 | 0.00 |
March | 0.581096E+09 | 0.785283E+09 | 0.762205E+09 | 0.351371E+09 | 0.410834E+09 | 0.00 | 0.00 |
April | 0.532569E+09 | 0.667616E+09 | 0.733476E+09 | 0.247608E+09 | 0.485868E+09 | 0.00 | 0.00 |
May | 0.871482E+09 | 0.381517E+09 | 0.948996E+09 | 0.266837E+09 | 0.682160E+09 | 0.00 | 0.00 |
June | 0.129563E+10 | 0.171782E+09 | 0.109539E+10 | 0.442908E+09 | 0.652487E+09 | 0.00 | 0.00 |
July | 0.115171E+10 | 0.151572E+09 | 0.952790E+09 | 0.281867E+09 | 0.670924E+09 | 0.00 | 0.00 |
August | 0.112077E+10 | 0.183103E+09 | 0.942024E+09 | 0.382880E+09 | 0.559144E+09 | 0.00 | 0.00 |
September | 0.895295E+09 | 0.304941E+09 | 0.802263E+09 | 0.317179E+09 | 0.485084E+09 | 0.00 | 0.00 |
October | 0.570956E+09 | 0.749335E+09 | 0.676080E+09 | 0.325864E+09 | 0.350216E+09 | 0.00 | 0.00 |
November | 0.366090E+09 | 0.871235E+09 | 0.530926E+09 | 0.275199E+09 | 0.255726E+09 | 0.00 | 0.00 |
December | 0.246834E+09 | 0.115987E+10 | 0.445688E+09 | 0.223028E+09 | 0.222660E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.834020E+10 | 0.736013E+10 | 0.899178E+10 | 0.370808E+10 | 0.528370E+10 | 0.00 | 0.00 |
Minimum of Months | 0.246834E+09 | 0.151572E+09 | 0.445688E+09 | 0.223028E+09 | 0.222660E+09 | 0.00 | 0.00 |
Maximum of Months | 0.129563E+10 | 0.115987E+10 | 0.109539E+10 | 0.442908E+09 | 0.682160E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109390E+10 | 0.487899E+09 | 0.102588E+10 | 0.844511E+09 | 0.181371E+09 | 0.00 | 0.00 |
February | 0.868370E+09 | 0.472551E+09 | 0.877234E+09 | 0.697595E+09 | 0.179639E+09 | 0.00 | 0.00 |
March | 0.654932E+09 | 0.410909E+09 | 0.729424E+09 | 0.482168E+09 | 0.247256E+09 | 0.00 | 0.00 |
April | 0.324125E+09 | 0.356654E+09 | 0.461987E+09 | 0.191087E+09 | 0.270900E+09 | 0.00 | 0.00 |
May | 0.347093E+09 | 0.198366E+09 | 0.433787E+09 | 83359867.96 | 0.350427E+09 | 0.00 | 0.00 |
June | 0.417859E+09 | 78712844.60 | 0.381587E+09 | 68768215.08 | 0.312819E+09 | 0.00 | 0.00 |
July | 0.461692E+09 | 69383762.38 | 0.407327E+09 | 69313338.87 | 0.338014E+09 | 0.00 | 0.00 |
August | 0.527244E+09 | 83552130.70 | 0.518285E+09 | 0.213166E+09 | 0.305119E+09 | 0.00 | 0.00 |
September | 0.702201E+09 | 0.147451E+09 | 0.659044E+09 | 0.370474E+09 | 0.288570E+09 | 0.00 | 0.00 |
October | 0.825188E+09 | 0.388551E+09 | 0.804256E+09 | 0.569973E+09 | 0.234283E+09 | 0.00 | 0.00 |
November | 0.102832E+10 | 0.443549E+09 | 0.953662E+09 | 0.760710E+09 | 0.192952E+09 | 0.00 | 0.00 |
December | 0.983636E+09 | 0.568463E+09 | 0.940146E+09 | 0.761056E+09 | 0.179090E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.823456E+10 | 0.370604E+10 | 0.819262E+10 | 0.511218E+10 | 0.308044E+10 | 0.00 | 0.00 |
Minimum of Months | 0.324125E+09 | 69383762.38 | 0.381587E+09 | 68768215.08 | 0.179090E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109390E+10 | 0.568463E+09 | 0.102588E+10 | 0.844511E+09 | 0.350427E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 24134937.71 | 0.319347E+10 | 0.509006E+09 | 0.00 | 0.509006E+09 | 0.00 | 0.00 |
February | 30371651.79 | 0.299110E+10 | 0.577847E+09 | 0.00 | 0.577847E+09 | 0.00 | 0.00 |
March | 0.195401E+09 | 0.253949E+10 | 0.870773E+09 | 42820.93 | 0.870731E+09 | 0.00 | 0.00 |
April | 0.328147E+09 | 0.217709E+10 | 0.105923E+10 | 6865404.55 | 0.105237E+10 | 0.00 | 0.00 |
May | 0.943088E+09 | 0.123628E+10 | 0.149515E+10 | 49991902.31 | 0.144516E+10 | 0.00 | 0.00 |
June | 0.159550E+10 | 0.551740E+09 | 0.158623E+10 | 0.177105E+09 | 0.140912E+10 | 0.00 | 0.00 |
July | 0.165690E+10 | 0.530392E+09 | 0.155474E+10 | 0.105923E+09 | 0.144882E+10 | 0.00 | 0.00 |
August | 0.127501E+10 | 0.626543E+09 | 0.123786E+10 | 33326710.97 | 0.120453E+10 | 0.00 | 0.00 |
September | 0.914176E+09 | 0.988730E+09 | 0.100316E+10 | 783735.27 | 0.100237E+10 | 0.00 | 0.00 |
October | 0.235381E+09 | 0.237305E+10 | 0.741638E+09 | 0.00 | 0.741638E+09 | 0.00 | 0.00 |
November | 62043032.90 | 0.282553E+10 | 0.544836E+09 | 0.00 | 0.544836E+09 | 0.00 | 0.00 |
December | 26053535.44 | 0.362766E+10 | 0.476239E+09 | 0.00 | 0.476239E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.728621E+10 | 0.236611E+11 | 0.116567E+11 | 0.374039E+09 | 0.112827E+11 | 0.00 | 0.00 |
Minimum of Months | 24134937.71 | 0.530392E+09 | 0.476239E+09 | 0.00 | 0.476239E+09 | 0.00 | 0.00 |
Maximum of Months | 0.165690E+10 | 0.362766E+10 | 0.158623E+10 | 0.177105E+09 | 0.144882E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 18321223.16 | 0.333195E+10 | 0.509006E+09 | 0.00 | 0.509006E+09 | 0.00 | 0.00 |
February | 24395890.66 | 0.312367E+10 | 0.577847E+09 | 0.00 | 0.577847E+09 | 0.00 | 0.00 |
March | 0.172571E+09 | 0.266492E+10 | 0.870773E+09 | 42820.93 | 0.870731E+09 | 0.00 | 0.00 |
April | 0.296546E+09 | 0.228602E+10 | 0.105923E+10 | 6865404.55 | 0.105237E+10 | 0.00 | 0.00 |
May | 0.893240E+09 | 0.129923E+10 | 0.149515E+10 | 49991902.31 | 0.144516E+10 | 0.00 | 0.00 |
June | 0.154282E+10 | 0.585328E+09 | 0.158623E+10 | 0.177105E+09 | 0.140912E+10 | 0.00 | 0.00 |
July | 0.160409E+10 | 0.565978E+09 | 0.155474E+10 | 0.105923E+09 | 0.144882E+10 | 0.00 | 0.00 |
August | 0.123025E+10 | 0.666116E+09 | 0.123786E+10 | 33326710.97 | 0.120453E+10 | 0.00 | 0.00 |
September | 0.878294E+09 | 0.103829E+10 | 0.100316E+10 | 783735.27 | 0.100237E+10 | 0.00 | 0.00 |
October | 0.212809E+09 | 0.247510E+10 | 0.741638E+09 | 0.00 | 0.741638E+09 | 0.00 | 0.00 |
November | 54380123.30 | 0.295203E+10 | 0.544836E+09 | 0.00 | 0.544836E+09 | 0.00 | 0.00 |
December | 20824836.90 | 0.377718E+10 | 0.476239E+09 | 0.00 | 0.476239E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.694854E+10 | 0.247658E+11 | 0.116567E+11 | 0.374039E+09 | 0.112827E+11 | 0.00 | 0.00 |
Minimum of Months | 18321223.16 | 0.565978E+09 | 0.476239E+09 | 0.00 | 0.476239E+09 | 0.00 | 0.00 |
Maximum of Months | 0.160409E+10 | 0.377718E+10 | 0.158623E+10 | 0.177105E+09 | 0.144882E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111359E+10 | 0.227858E+10 | 0.161987E+10 | 0.109434E+10 | 0.525530E+09 | 0.00 | 0.00 |
February | 0.120595E+10 | 0.222863E+10 | 0.170690E+10 | 0.112513E+10 | 0.581770E+09 | 0.00 | 0.00 |
March | 0.154031E+10 | 0.201593E+10 | 0.199045E+10 | 0.112770E+10 | 0.862745E+09 | 0.00 | 0.00 |
April | 0.131977E+10 | 0.180105E+10 | 0.181848E+10 | 0.789874E+09 | 0.102861E+10 | 0.00 | 0.00 |
May | 0.193993E+10 | 0.105749E+10 | 0.214712E+10 | 0.749501E+09 | 0.139762E+10 | 0.00 | 0.00 |
June | 0.282141E+10 | 0.519757E+09 | 0.241519E+10 | 0.108411E+10 | 0.133108E+10 | 0.00 | 0.00 |
July | 0.274544E+10 | 0.507991E+09 | 0.230862E+10 | 0.921760E+09 | 0.138686E+10 | 0.00 | 0.00 |
August | 0.273989E+10 | 0.561041E+09 | 0.235938E+10 | 0.115784E+10 | 0.120153E+10 | 0.00 | 0.00 |
September | 0.227909E+10 | 0.815213E+09 | 0.206815E+10 | 0.105482E+10 | 0.101333E+10 | 0.00 | 0.00 |
October | 0.152639E+10 | 0.191808E+10 | 0.175745E+10 | 0.993604E+09 | 0.763845E+09 | 0.00 | 0.00 |
November | 0.115867E+10 | 0.212032E+10 | 0.155657E+10 | 0.985591E+09 | 0.570975E+09 | 0.00 | 0.00 |
December | 0.926156E+09 | 0.268366E+10 | 0.145167E+10 | 0.946912E+09 | 0.504759E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.213166E+11 | 0.185077E+11 | 0.231998E+11 | 0.120312E+11 | 0.111686E+11 | 0.00 | 0.00 |
Minimum of Months | 0.926156E+09 | 0.507991E+09 | 0.145167E+10 | 0.749501E+09 | 0.504759E+09 | 0.00 | 0.00 |
Maximum of Months | 0.282141E+10 | 0.268366E+10 | 0.241519E+10 | 0.115784E+10 | 0.139762E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.266311E+10 | 0.215401E+10 | 0.278593E+10 | 0.214975E+10 | 0.636179E+09 | 0.00 | 0.00 |
February | 0.212840E+10 | 0.208918E+10 | 0.243113E+10 | 0.177576E+10 | 0.655368E+09 | 0.00 | 0.00 |
March | 0.170453E+10 | 0.190287E+10 | 0.215529E+10 | 0.122740E+10 | 0.927892E+09 | 0.00 | 0.00 |
April | 0.919737E+09 | 0.169817E+10 | 0.153912E+10 | 0.488775E+09 | 0.105035E+10 | 0.00 | 0.00 |
May | 0.115631E+10 | 0.100642E+10 | 0.161677E+10 | 0.229334E+09 | 0.138743E+10 | 0.00 | 0.00 |
June | 0.151609E+10 | 0.466308E+09 | 0.151511E+10 | 0.235765E+09 | 0.127935E+10 | 0.00 | 0.00 |
July | 0.164711E+10 | 0.442258E+09 | 0.156984E+10 | 0.212752E+09 | 0.135709E+10 | 0.00 | 0.00 |
August | 0.170212E+10 | 0.520736E+09 | 0.174366E+10 | 0.554050E+09 | 0.118961E+10 | 0.00 | 0.00 |
September | 0.205015E+10 | 0.799957E+09 | 0.202152E+10 | 0.943329E+09 | 0.107819E+10 | 0.00 | 0.00 |
October | 0.215081E+10 | 0.183033E+10 | 0.230151E+10 | 0.145090E+10 | 0.850615E+09 | 0.00 | 0.00 |
November | 0.255538E+10 | 0.200151E+10 | 0.261437E+10 | 0.193643E+10 | 0.677941E+09 | 0.00 | 0.00 |
December | 0.239247E+10 | 0.247043E+10 | 0.255645E+10 | 0.193731E+10 | 0.619139E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.225862E+11 | 0.173822E+11 | 0.248507E+11 | 0.131415E+11 | 0.117091E+11 | 0.00 | 0.00 |
Minimum of Months | 0.919737E+09 | 0.442258E+09 | 0.151511E+10 | 0.212752E+09 | 0.619139E+09 | 0.00 | 0.00 |
Maximum of Months | 0.266311E+10 | 0.247043E+10 | 0.278593E+10 | 0.214975E+10 | 0.138743E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.40 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.31 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.51 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.44 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.23 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.78 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.33 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.32 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.39 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.23 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.93 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.71 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.86 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.46 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.89 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.59 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.86 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.32 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.01 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.69 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.06 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.90 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.93 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.32 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.3 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.44 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.29 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.21 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.8 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.21 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.52 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.95 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 7.98 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.48 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.84 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.63 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.73 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.79 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.51 | 196.33 | 4.00 |
September | 14.93 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.69 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.31 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.90 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.52 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.73 | 29.40 | 16.00 | 9.80 | 20.51 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.48 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.72 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.63 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.91 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.89 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.39 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.05 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.05 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.63 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.442736E+11 | -.737369E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.142087E+10 | 58.99 | 0.00 | 0.00 |
February | 0.408894E+11 | -.674278E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.129146E+10 | 58.97 | 0.00 | 0.00 |
March | 0.441769E+11 | -.736220E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.144479E+10 | 58.99 | 0.00 | 0.00 |
April | 0.397072E+11 | -.684199E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.140118E+10 | 59.05 | 0.00 | 0.00 |
May | 0.368242E+11 | -.667897E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.145760E+10 | 59.11 | 0.00 | 0.00 |
June | 0.315976E+11 | -.608783E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.142056E+10 | 59.19 | 0.00 | 0.00 |
July | 0.295343E+11 | -.600167E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.146870E+10 | 59.23 | 0.00 | 0.00 |
August | 0.285254E+11 | -.590810E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.146678E+10 | 59.25 | 0.00 | 0.00 |
September | 0.287430E+11 | -.582483E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.140335E+10 | 59.24 | 0.00 | 0.00 |
October | 0.327827E+11 | -.631055E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.139266E+10 | 59.17 | 0.00 | 0.00 |
November | 0.358142E+11 | -.648837E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.132649E+10 | 59.11 | 0.00 | 0.00 |
December | 0.411877E+11 | -.709136E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.138000E+10 | 59.03 | 0.00 | 0.00 |
Annual Sum or Average | 0.434056E+12 | -.787124E+12 | 8760.00 | -.168744E+11 | 59.11 | |||||
Minimum of Months | 0.285254E+11 | -.737369E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.146870E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.442736E+11 | -.582483E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129146E+10 | 59.25 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.768577E+10 | -.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -143008932.2 | 81.21 | 0.00 | 0.00 |
February | 0.694494E+10 | -.681595E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -128991824.7 | 81.21 | 0.00 | 0.00 |
March | 0.768598E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -143189095.0 | 81.21 | 0.00 | 0.00 |
April | 0.744718E+10 | -.730857E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -138607830.0 | 81.21 | 0.00 | 0.00 |
May | 0.768809E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -145306080.4 | 81.21 | 0.00 | 0.00 |
June | 0.744340E+10 | -.730051E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -142894592.7 | 81.21 | 0.00 | 0.00 |
July | 0.769843E+10 | -.755083E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -147599353.4 | 81.21 | 0.00 | 0.00 |
August | 0.769062E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -147825434.7 | 81.21 | 0.00 | 0.00 |
September | 0.745160E+10 | -.730857E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -143026943.1 | 81.21 | 0.00 | 0.00 |
October | 0.768690E+10 | -.754276E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -144141154.1 | 81.21 | 0.00 | 0.00 |
November | 0.743081E+10 | -.729241E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -138398058.2 | 81.21 | 0.00 | 0.00 |
December | 0.769477E+10 | -.755083E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -143941419.9 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.905485E+11 | -.888416E+11 | 8760.00 | -.170693E+10 | 81.21 | |||||
Minimum of Months | 0.694494E+10 | -.755083E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -147825434.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.769843E+10 | -.681595E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -128991824.7 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.787081E+11 | -.775785E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.112961E+10 | 62.47 | 0.00 | 0.00 |
February | 0.711685E+11 | -.701484E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.102011E+10 | 62.22 | 0.00 | 0.00 |
March | 0.786853E+11 | -.775397E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.114560E+10 | 62.42 | 0.00 | 0.00 |
April | 0.758647E+11 | -.747358E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.112897E+10 | 63.10 | 0.00 | 0.00 |
May | 0.781366E+11 | -.769385E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.119806E+10 | 63.97 | 0.00 | 0.00 |
June | 0.753359E+11 | -.741466E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.118932E+10 | 64.84 | 0.00 | 0.00 |
July | 0.775615E+11 | -.763143E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.124719E+10 | 65.45 | 0.00 | 0.00 |
August | 0.774611E+11 | -.762094E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.125170E+10 | 65.67 | 0.00 | 0.00 |
September | 0.749572E+11 | -.737647E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.119242E+10 | 65.42 | 0.00 | 0.00 |
October | 0.776236E+11 | -.764498E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.117384E+10 | 64.78 | 0.00 | 0.00 |
November | 0.755090E+11 | -.744106E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.109845E+10 | 63.96 | 0.00 | 0.00 |
December | 0.784118E+11 | -.772946E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.111721E+10 | 63.07 | 0.00 | 0.00 |
Annual Sum or Average | 0.919423E+12 | -.905531E+12 | 8760.00 | -.138925E+11 | 63.96 | |||||
Minimum of Months | 0.711685E+11 | -.775785E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.125170E+10 | 62.22 | 0.00 | 0.00 |
Maximum of Months | 0.787081E+11 | -.701484E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.102011E+10 | 65.67 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.86 | 0.86 | 01-JAN-07:49 | 9361.96 | 39.80 | 274.00 | 270.83 | 3570.11 | 33.82 | 232.33 | 260.17 |
February | 245.50 | 0.86 | 0.86 | 01-FEB-10:39 | 12768.96 | 39.19 | 238.17 | 266.17 | 1084.57 | 26.09 | 172.67 | 233.83 |
March | 296.17 | 0.87 | 0.86 | 01-MAR-06:00 | 4557.42 | 25.78 | 133.83 | 332.33 | 659.33 | 22.45 | 239.33 | 275.50 |
April | 296.67 | 0.87 | 0.86 | 03-APR-09:39 | 1455.09 | 20.45 | 91.17 | 344.83 | 585.04 | 22.18 | 219.17 | 280.00 |
May | 415.33 | 0.87 | 0.86 | 01-MAY-06:19 | 1374.20 | 20.09 | 122.50 | 395.83 | 538.98 | 21.82 | 295.33 | 338.67 |
June | 421.50 | 0.87 | 0.86 | 01-JUN-05:00 | 1058.68 | 20.14 | 55.50 | 396.00 | 445.80 | 21.92 | 310.00 | 325.83 |
July | 430.33 | 0.87 | 0.86 | 01-JUL-07:19 | 1230.19 | 19.97 | 96.00 | 401.50 | 492.15 | 21.73 | 287.83 | 334.00 |
August | 394.50 | 0.87 | 0.86 | 01-AUG-06:19 | 1227.94 | 20.21 | 93.83 | 374.33 | 513.15 | 21.97 | 295.67 | 320.17 |
September | 354.00 | 0.87 | 0.86 | 01-SEP-06:40 | 1521.74 | 20.47 | 98.67 | 336.67 | 626.14 | 22.26 | 273.33 | 291.67 |
October | 262.67 | 0.86 | 0.86 | 01-OCT-06:49 | 10284.78 | 35.55 | 229.33 | 302.50 | 838.47 | 24.10 | 237.33 | 258.00 |
November | 257.67 | 0.86 | 0.86 | 01-NOV-08:39 | 10811.93 | 39.68 | 254.00 | 267.50 | 1973.27 | 30.28 | 210.17 | 240.17 |
December | 251.17 | 0.86 | 0.86 | 01-DEC-07:40 | 8675.70 | 40.22 | 250.83 | 260.17 | 5314.75 | 38.33 | 239.33 | 244.17 |
Annual Sum or Average | 3902.00 | 0.87 | 4546.56 | 26.82 | 1937.83 | 3948.67 | 1213.08 | 24.84 | 3012.50 | 3402.17 | ||
Minimum of Months | 245.50 | 0.86 | 0.86 | 1058.68 | 19.97 | 55.50 | 260.17 | 445.80 | 21.73 | 172.67 | 233.83 | |
Maximum of Months | 430.33 | 0.87 | 0.86 | 12768.96 | 40.22 | 274.00 | 401.50 | 5314.75 | 38.33 | 310.00 | 338.67 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.24 | 0.22 | 01-JAN-07:40 | 10020.72 | 39.86 | 274.00 | 276.83 | 4228.09 | 33.39 | 225.17 | 268.50 |
February | 245.50 | 0.23 | 0.22 | 01-FEB-10:39 | 13428.45 | 39.27 | 238.17 | 272.67 | 1742.61 | 25.29 | 127.17 | 256.83 |
March | 296.17 | 0.24 | 0.22 | 01-MAR-06:49 | 5033.43 | 25.75 | 134.33 | 340.83 | 1133.76 | 22.16 | 183.17 | 312.17 |
April | 296.67 | 0.25 | 0.22 | 03-APR-09:39 | 1770.44 | 20.75 | 104.50 | 355.17 | 899.36 | 22.32 | 219.83 | 323.67 |
May | 415.33 | 0.25 | 0.22 | 01-MAY-05:00 | 1607.54 | 20.64 | 176.50 | 406.00 | 771.39 | 22.19 | 320.83 | 378.17 |
June | 421.50 | 0.25 | 0.22 | 01-JUN-05:40 | 1269.42 | 20.70 | 136.17 | 411.67 | 655.85 | 22.29 | 330.17 | 376.00 |
July | 430.33 | 0.25 | 0.22 | 01-JUL-05:40 | 1446.92 | 20.56 | 162.83 | 417.67 | 708.05 | 22.13 | 323.17 | 379.67 |
August | 394.50 | 0.26 | 0.22 | 01-AUG-05:00 | 1514.16 | 20.55 | 117.33 | 383.50 | 798.54 | 22.14 | 292.33 | 356.67 |
September | 354.00 | 0.25 | 0.22 | 01-SEP-06:10 | 1905.30 | 20.54 | 116.50 | 347.00 | 1008.61 | 22.20 | 247.83 | 321.33 |
October | 262.67 | 0.24 | 0.22 | 01-OCT-06:30 | 10866.33 | 35.52 | 223.50 | 311.83 | 1418.13 | 23.62 | 181.83 | 289.33 |
November | 257.67 | 0.24 | 0.22 | 01-NOV-08:39 | 11490.03 | 39.74 | 254.00 | 274.83 | 2648.53 | 29.61 | 176.00 | 258.83 |
December | 251.17 | 0.24 | 0.22 | 01-DEC-07:40 | 9341.23 | 40.26 | 250.83 | 264.17 | 5978.32 | 38.17 | 231.50 | 257.33 |
Annual Sum or Average | 3902.00 | 0.25 | 4956.84 | 27.08 | 2188.67 | 4062.17 | 1622.13 | 24.80 | 2859.00 | 3778.50 | ||
Minimum of Months | 245.50 | 0.23 | 0.22 | 1269.42 | 20.54 | 104.50 | 264.17 | 655.85 | 22.13 | 127.17 | 256.83 | |
Maximum of Months | 430.33 | 0.26 | 0.22 | 13428.45 | 40.26 | 274.00 | 417.67 | 5978.32 | 38.17 | 330.17 | 379.67 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.66 | 0.60 | 01-JAN-09:09 | 347.59 | 14.25 | 0.00 | 224.50 | 183.27 | 17.96 | 0.00 | 90.67 |
February | 245.50 | 0.63 | 0.60 | 01-FEB-10:39 | 393.08 | 15.59 | 0.00 | 252.00 | 212.85 | 19.20 | 1.50 | 117.67 |
March | 296.17 | 0.62 | 0.60 | 01-MAR-07:19 | 542.46 | 16.85 | 0.00 | 328.33 | 271.24 | 20.20 | 24.67 | 261.50 |
April | 296.67 | 0.62 | 0.60 | 03-APR-09:39 | 767.50 | 17.99 | 0.00 | 355.17 | 349.56 | 21.17 | 113.83 | 304.17 |
May | 415.33 | 0.61 | 0.60 | 01-MAY-05:00 | 978.86 | 18.32 | 0.00 | 413.50 | 413.77 | 21.97 | 258.67 | 386.17 |
June | 421.50 | 0.61 | 0.60 | 01-JUN-04:00 | 1039.44 | 19.01 | 11.00 | 422.17 | 445.25 | 24.25 | 291.00 | 409.00 |
July | 430.33 | 0.61 | 0.60 | 01-JUL-04:00 | 1011.10 | 18.46 | 1.83 | 427.33 | 426.54 | 22.84 | 278.83 | 401.17 |
August | 394.50 | 0.62 | 0.60 | 01-AUG-05:00 | 760.41 | 17.98 | 0.00 | 389.67 | 344.89 | 21.23 | 163.33 | 350.67 |
September | 354.00 | 0.62 | 0.60 | 01-SEP-06:10 | 608.19 | 17.25 | 0.00 | 339.00 | 296.16 | 20.54 | 58.50 | 281.00 |
October | 262.67 | 0.63 | 0.60 | 01-OCT-06:49 | 493.71 | 16.62 | 0.00 | 293.33 | 263.13 | 20.09 | 3.83 | 212.17 |
November | 257.67 | 0.64 | 0.60 | 01-NOV-08:50 | 383.28 | 15.05 | 0.00 | 244.00 | 208.52 | 18.72 | 0.17 | 109.83 |
December | 251.17 | 0.65 | 0.60 | 01-DEC-08:30 | 364.30 | 14.67 | 0.00 | 229.00 | 194.25 | 18.37 | 0.00 | 90.33 |
Annual Sum or Average | 3902.00 | 0.62 | 690.92 | 17.12 | 12.83 | 3918.00 | 318.45 | 20.88 | 1194.33 | 3014.33 | ||
Minimum of Months | 245.50 | 0.61 | 0.60 | 347.59 | 14.25 | 0.00 | 224.50 | 183.27 | 17.96 | 0.00 | 90.33 | |
Maximum of Months | 430.33 | 0.66 | 0.60 | 1039.44 | 19.01 | 11.00 | 427.33 | 445.25 | 24.25 | 291.00 | 409.00 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.66 | 0.60 | 01-JAN-09:09 | 347.59 | 14.25 | 0.00 | 224.50 | 183.27 | 17.96 | 0.00 | 90.67 |
February | 245.50 | 0.63 | 0.60 | 01-FEB-10:39 | 393.08 | 15.59 | 0.00 | 252.00 | 212.85 | 19.20 | 1.50 | 117.67 |
March | 296.17 | 0.62 | 0.60 | 01-MAR-07:19 | 542.46 | 16.85 | 0.00 | 328.33 | 271.24 | 20.20 | 24.67 | 261.50 |
April | 296.67 | 0.62 | 0.60 | 03-APR-09:39 | 767.50 | 17.99 | 0.00 | 355.17 | 349.56 | 21.17 | 113.83 | 304.17 |
May | 415.33 | 0.61 | 0.60 | 01-MAY-05:00 | 978.86 | 18.32 | 0.00 | 413.50 | 413.77 | 21.97 | 258.67 | 386.17 |
June | 421.50 | 0.61 | 0.60 | 01-JUN-04:00 | 1039.44 | 19.01 | 11.00 | 422.17 | 445.25 | 24.25 | 291.00 | 409.00 |
July | 430.33 | 0.61 | 0.60 | 01-JUL-04:00 | 1011.10 | 18.46 | 1.83 | 427.33 | 426.54 | 22.84 | 278.83 | 401.17 |
August | 394.50 | 0.62 | 0.60 | 01-AUG-05:00 | 760.41 | 17.98 | 0.00 | 389.67 | 344.89 | 21.23 | 163.33 | 350.67 |
September | 354.00 | 0.62 | 0.60 | 01-SEP-06:10 | 608.19 | 17.25 | 0.00 | 339.00 | 296.16 | 20.54 | 58.50 | 281.00 |
October | 262.67 | 0.63 | 0.60 | 01-OCT-06:49 | 493.71 | 16.62 | 0.00 | 293.33 | 263.13 | 20.09 | 3.83 | 212.17 |
November | 257.67 | 0.64 | 0.60 | 01-NOV-08:50 | 383.28 | 15.05 | 0.00 | 244.00 | 208.52 | 18.72 | 0.17 | 109.83 |
December | 251.17 | 0.65 | 0.60 | 01-DEC-08:30 | 364.30 | 14.67 | 0.00 | 229.00 | 194.25 | 18.37 | 0.00 | 90.33 |
Annual Sum or Average | 3902.00 | 0.62 | 690.92 | 17.12 | 12.83 | 3918.00 | 318.45 | 20.88 | 1194.33 | 3014.33 | ||
Minimum of Months | 245.50 | 0.61 | 0.60 | 347.59 | 14.25 | 0.00 | 224.50 | 183.27 | 17.96 | 0.00 | 90.33 | |
Maximum of Months | 430.33 | 0.66 | 0.60 | 1039.44 | 19.01 | 11.00 | 427.33 | 445.25 | 24.25 | 291.00 | 409.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170339E+09 | 2580.34 | 05-JAN-11:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.390744E+09 | 2586.20 | 05-FEB-15:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235532E+09 | 2573.88 | 19-MAR-09:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185049E+09 | 2028.85 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222815E+09 | 2582.37 | 31-OCT-13:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155541E+09 | 2573.17 | 30-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.458751E+09 | 2588.86 | 22-DEC-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181877E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.458751E+09 | 2588.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 14358293.15 | 520.47 | 06-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17628455.64 | 399.30 | 06-FEB-17:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 153121.07 | 57.02 | 31-OCT-16:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 44794.38 | 46.64 | 30-NOV-04:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135331E+09 | 978.14 | 22-DEC-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167516E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135331E+09 | 978.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 25025322.83 | 6765.39 | 05-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104864E+09 | 4891.21 | 05-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22274429.37 | 2953.37 | 19-MAR-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14738784.56 | 3153.46 | 03-APR-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87858778.88 | 4919.83 | 31-OCT-13:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8416833.41 | 4338.82 | 29-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169680E+09 | 8331.46 | 20-DEC-11:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432858E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169680E+09 | 8331.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.232680E+10 | 7043.63 | 31-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.265920E+10 | 7042.02 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207653E+10 | 7044.80 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176107E+10 | 7041.97 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.238800E+09 | 6849.15 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2380748.02 | 2521.51 | 22-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1582346.23 | 2722.39 | 24-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3749754.15 | 3084.94 | 30-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79530415.70 | 6849.79 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148161E+10 | 7043.38 | 24-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198838E+10 | 7043.35 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374996E+10 | 7039.90 | 19-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163696E+11 | |||||||
Minimum of Months | 1582346.23 | 2521.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.374996E+10 | 7044.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.365326E+10 | 7026.60 | 12-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362299E+10 | 7019.92 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246036E+10 | 7022.73 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.190294E+10 | 7019.88 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.236259E+09 | 6834.16 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 826702.26 | 1776.00 | 04-JUN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1467921.38 | 2582.12 | 03-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2489985.49 | 2846.97 | 19-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92725920.82 | 6841.61 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.179491E+10 | 7021.29 | 24-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.294996E+10 | 7042.46 | 10-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.510442E+10 | 7019.56 | 09-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218226E+11 | |||||||
Minimum of Months | 826702.26 | 1776.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.510442E+10 | 7042.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126887E+11 | 38567.46 | 05-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133772E+11 | 38468.94 | 12-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.615724E+10 | 38015.18 | 04-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.321911E+10 | 37694.97 | 02-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88786866.34 | 14317.52 | 03-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 868228.33 | 5074.26 | 01-JUN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1003010.45 | 6422.47 | 31-JUL-08:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3108510.21 | 14309.57 | 30-AUG-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39384706.72 | 14390.88 | 21-SEP-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.371402E+10 | 38513.22 | 31-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.877621E+10 | 38415.81 | 29-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183190E+11 | 38571.83 | 24-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.663847E+11 | |||||||
Minimum of Months | 868228.33 | 5074.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183190E+11 | 38571.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.244826E+10 | 6706.57 | 31-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276492E+10 | 6704.86 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203515E+10 | 6707.80 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171095E+10 | 6704.82 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.223046E+09 | 2941.03 | 01-MAY-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 205859.25 | 1759.84 | 17-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 113545.09 | 1001.58 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 242696.94 | 1994.30 | 15-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 71836289.60 | 6462.75 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151983E+10 | 6706.30 | 24-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212020E+10 | 6706.27 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.382300E+10 | 6702.95 | 09-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167178E+11 | |||||||
Minimum of Months | 113545.09 | 1001.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.382300E+10 | 6707.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.378244E+10 | 6787.38 | 12-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370394E+10 | 6793.34 | 02-FEB-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240941E+10 | 6699.48 | 21-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186925E+10 | 6696.48 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.228739E+09 | 2798.37 | 01-MAY-15:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 25320.81 | 271.52 | 16-JUN-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 63821.21 | 409.66 | 28-JUL-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 299128.18 | 1232.09 | 27-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 89479737.12 | 6467.00 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183996E+10 | 6697.97 | 24-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.313252E+10 | 6791.87 | 21-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.515961E+10 | 6763.24 | 07-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222157E+11 | |||||||
Minimum of Months | 25320.81 | 271.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.515961E+10 | 6793.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.376188E+10 | 7947.87 | 05-JAN-13:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.437686E+10 | 7957.66 | 05-FEB-15:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.393650E+10 | 7969.90 | 19-MAR-14:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362459E+10 | 7955.36 | 02-APR-14:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.378713E+09 | 6413.93 | 01-MAY-03:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193322E+10 | 7946.23 | 31-OCT-13:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326099E+10 | 7936.04 | 29-NOV-09:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.595150E+10 | 7965.64 | 22-DEC-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272242E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.595150E+10 | 7969.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.873450E+09 | 2082.81 | 30-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.934947E+09 | 2082.27 | 04-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.749060E+09 | 2082.98 | 24-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.625351E+09 | 2082.98 | 30-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102522E+09 | 2047.18 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 855073.68 | 729.24 | 23-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 575113.92 | 738.17 | 28-JUL-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1288804.79 | 578.01 | 07-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 37761410.19 | 2058.34 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.562397E+09 | 2089.23 | 22-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.737418E+09 | 2090.68 | 10-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129342E+10 | 2081.94 | 09-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.591904E+10 | |||||||
Minimum of Months | 575113.92 | 578.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.129342E+10 | 2090.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130838E+10 | 2085.23 | 12-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123938E+10 | 2081.45 | 15-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.870365E+09 | 2086.93 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.668139E+09 | 2077.70 | 30-APR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96403412.01 | 2044.09 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 256571.82 | 490.09 | 17-JUN-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 225079.26 | 423.30 | 31-JUL-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 784674.39 | 634.90 | 22-AUG-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40982440.06 | 2056.62 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.667668E+09 | 2091.51 | 22-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105195E+10 | 2085.37 | 10-NOV-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171778E+10 | 2082.83 | 15-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.766232E+10 | |||||||
Minimum of Months | 225079.26 | 423.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171778E+10 | 2091.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170275E+10 | 9021.16 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.252252E+10 | 9023.08 | 06-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234171E+10 | 9024.55 | 18-MAR-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.213153E+10 | 9024.79 | 03-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.282662E+09 | 8717.25 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3321746.21 | 1816.99 | 01-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1724013.08 | 1920.84 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 548749.60 | 2329.00 | 02-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72046422.53 | 8698.75 | 22-SEP-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163571E+10 | 9023.94 | 31-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161677E+10 | 9027.09 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318046E+10 | 9020.37 | 20-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154917E+11 | |||||||
Minimum of Months | 548749.60 | 1816.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.318046E+10 | 9027.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.351311E+09 | 5114.93 | 05-JAN-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.578279E+09 | 5108.80 | 06-FEB-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22548177.38 | 1946.03 | 05-MAR-06:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14765162.77 | 1025.20 | 17-APR-04:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120019E+09 | 2977.07 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201227E+09 | 5055.34 | 30-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104596E+10 | 5132.46 | 22-DEC-03:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233411E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104596E+10 | 5132.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112504E+11 | 126785.31 | 05-JAN-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109431E+11 | 142862.41 | 12-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.416588E+10 | 105953.73 | 19-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140779E+10 | 46492.29 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79022960.52 | 74404.30 | 29-MAY-22:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 51036249.43 | 51962.30 | 30-SEP-22:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.366409E+10 | 77139.50 | 03-OCT-14:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.433077E+10 | 88048.26 | 29-NOV-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269507E+11 | 162161.18 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.628429E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.269507E+11 | 162161.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160126E+10 | 7932.53 | 05-JAN-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172454E+10 | 6768.70 | 12-FEB-04:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687791E+09 | 5064.89 | 19-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.314726E+09 | 2460.42 | 03-APR-02:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36619.47 | 0.48 | 16-MAY-20:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 103452.22 | 0.49 | 17-JUN-15:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 108726.14 | 0.48 | 27-JUL-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91356.03 | 0.49 | 28-AUG-12:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 986526.90 | 187.02 | 22-SEP-05:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.490817E+09 | 4287.16 | 31-OCT-15:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.803279E+09 | 5637.42 | 29-NOV-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.300106E+10 | 8691.81 | 21-DEC-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.862480E+10 | |||||||
Minimum of Months | 36619.47 | 0.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.300106E+10 | 8691.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.810940E+09 | 0.744785E+09 | 10198.06 | 12-JAN-16:11 | 10198.06 | 0.05 |
February | 0.00 | 0.00 | 0.851576E+09 | 0.815652E+09 | 10196.23 | 20-FEB-16:11 | 10196.23 | 0.04 |
March | 0.00 | 0.00 | 0.179744E+10 | 0.178839E+10 | 10197.62 | 26-MAR-15:11 | 10197.62 | 0.01 |
April | 0.00 | 0.00 | 0.993951E+09 | 0.919358E+09 | 11494.16 | 06-APR-18:31 | 11494.16 | 0.07 |
May | 0.00 | 0.00 | 0.277123E+10 | 0.224146E+10 | 11199.04 | 22-MAY-08:61 | 8354.45 | 0.37 |
June | 0.00 | 0.00 | 0.739327E+10 | 0.599751E+10 | 11705.21 | 18-JUN-08:61 | 9124.75 | 0.73 |
July | 0.00 | 0.00 | 0.735034E+10 | 0.552225E+10 | 12066.92 | 28-JUL-15:11 | 8882.98 | 0.82 |
August | 0.00 | 0.00 | 0.705429E+10 | 0.539393E+10 | 12004.34 | 05-AUG-08:61 | 8924.90 | 0.75 |
September | 0.00 | 0.00 | 0.554128E+10 | 0.477574E+10 | 10298.89 | 01-SEP-08:62 | 9179.87 | 0.44 |
October | 0.00 | 0.00 | 0.247800E+10 | 0.232594E+10 | 10198.54 | 01-OCT-18:01 | 10198.54 | 0.11 |
November | 0.00 | 0.00 | 0.114501E+10 | 0.101186E+10 | 10198.07 | 19-NOV-16:11 | 10198.07 | 0.10 |
December | 0.00 | 0.00 | 0.531911E+09 | 0.526952E+09 | 10195.26 | 29-DEC-16:11 | 10195.26 | 0.00 |
Annual Sum or Average | 0.387192E+11 | 0.320638E+11 | 0.29 | |||||
Minimum of Months | 0.00 | 0.00 | 0.531911E+09 | 0.526952E+09 | 10195.26 | 8354.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.739327E+10 | 0.599751E+10 | 12066.92 | 11494.16 | 0.82 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.117053E+09 | 0.111326E+09 | 10261.90 | 20-JAN-16:31 | 10261.90 | 0.01 |
February | 0.00 | 0.00 | 0.197499E+09 | 0.195151E+09 | 10071.87 | 20-FEB-16:11 | 10071.87 | 0.00 |
March | 0.00 | 0.00 | 0.720097E+09 | 0.716443E+09 | 11986.16 | 15-MAR-17:51 | 11986.16 | 0.00 |
April | 0.00 | 0.00 | 0.572842E+09 | 0.513930E+09 | 12294.85 | 08-APR-17:21 | 12294.85 | 0.06 |
May | 0.00 | 0.00 | 0.176945E+10 | 0.128662E+10 | 11035.32 | 22-MAY-08:61 | 8387.80 | 0.33 |
June | 0.00 | 0.00 | 0.604991E+10 | 0.490250E+10 | 12063.62 | 20-JUN-21:11 | 9015.22 | 0.58 |
July | 0.00 | 0.00 | 0.591434E+10 | 0.451219E+10 | 12569.11 | 31-JUL-21:11 | 8520.93 | 0.64 |
August | 0.00 | 0.00 | 0.529696E+10 | 0.401588E+10 | 12313.45 | 04-AUG-08:11 | 8875.79 | 0.58 |
September | 0.00 | 0.00 | 0.330142E+10 | 0.269223E+10 | 10547.07 | 10-SEP-21:11 | 10547.07 | 0.35 |
October | 0.00 | 0.00 | 0.848999E+09 | 0.787412E+09 | 11046.61 | 08-OCT-17:31 | 11046.61 | 0.06 |
November | 0.00 | 0.00 | 0.195962E+09 | 0.179647E+09 | 10072.69 | 15-NOV-16:11 | 10072.69 | 0.02 |
December | 0.00 | 0.00 | 44160554.59 | 43999494.86 | 10068.04 | 03-DEC-16:11 | 10068.04 | 0.00 |
Annual Sum or Average | 0.250287E+11 | 0.199573E+11 | 0.22 | |||||
Minimum of Months | 0.00 | 0.00 | 44160554.59 | 43999494.86 | 10068.04 | 8387.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.604991E+10 | 0.490250E+10 | 12569.11 | 12294.85 | 0.64 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.281104E+11 | 0.234436E+11 | 54612.85 | 19-JAN-13:30 | 54612.85 | 0.49 |
February | 0.00 | 0.00 | 0.169668E+11 | 0.135863E+11 | 52937.21 | 18-FEB-13:20 | 52937.21 | 0.37 |
March | 0.00 | 0.00 | 0.157503E+11 | 0.129865E+11 | 50155.68 | 11-MAR-13:00 | 50155.68 | 0.30 |
April | 0.00 | 0.00 | 0.206111E+10 | 0.911658E+09 | 20892.13 | 13-APR-12:23 | 13590.61 | 0.12 |
May | 0.00 | 0.00 | 0.119974E+11 | 0.504888E+10 | 19463.03 | 06-MAY-15:02 | 15172.21 | 0.57 |
June | 0.00 | 0.00 | 0.314725E+11 | 0.182609E+11 | 27767.74 | 26-JUN-17:11 | 25346.89 | 0.97 |
July | 0.00 | 0.00 | 0.355914E+11 | 0.211793E+11 | 27780.42 | 18-JUL-17:11 | 24317.78 | 0.98 |
August | 0.00 | 0.00 | 0.377251E+11 | 0.236387E+11 | 33434.68 | 29-AUG-13:22 | 25435.77 | 0.99 |
September | 0.00 | 0.00 | 0.391918E+11 | 0.278599E+11 | 50523.60 | 28-SEP-13:12 | 50523.60 | 0.93 |
October | 0.00 | 0.00 | 0.289509E+11 | 0.234506E+11 | 53578.10 | 10-OCT-11:21 | 53578.10 | 0.53 |
November | 0.00 | 0.00 | 0.255305E+11 | 0.209546E+11 | 55075.59 | 19-NOV-12:10 | 55075.59 | 0.47 |
December | 0.00 | 0.00 | 0.173585E+11 | 0.147605E+11 | 51826.97 | 16-DEC-13:52 | 51826.97 | 0.30 |
Annual Sum or Average | 0.290707E+12 | 0.206081E+12 | 0.59 | |||||
Minimum of Months | 0.00 | 0.00 | 0.206111E+10 | 0.911658E+09 | 19463.03 | 13590.61 | 0.12 | |
Maximum of Months | 0.00 | 0.00 | 0.391918E+11 | 0.278599E+11 | 55075.59 | 55075.59 | 0.99 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.123483E+10 | 0.937988E+09 | 50451.11 | 21-JAN-09:01 | 50451.11 | 0.06 |
February | 0.00 | 0.00 | 0.112664E+10 | 0.853288E+09 | 49135.39 | 27-FEB-19:01 | 49135.39 | 0.06 |
March | 0.00 | 0.00 | 0.551890E+10 | 0.505723E+10 | 52072.75 | 16-MAR-18:01 | 52072.75 | 0.07 |
April | 0.00 | 0.00 | 0.777735E+10 | 0.588447E+10 | 51498.80 | 08-APR-08:61 | 51498.80 | 0.26 |
May | 0.00 | 0.00 | 0.242338E+11 | 0.197491E+11 | 56713.87 | 22-MAY-15:11 | 47940.80 | 0.42 |
June | 0.00 | 0.00 | 0.435438E+11 | 0.373293E+11 | 62159.89 | 20-JUN-21:11 | 48010.48 | 0.59 |
July | 0.00 | 0.00 | 0.460047E+11 | 0.387457E+11 | 65144.49 | 30-JUL-21:11 | 45139.18 | 0.61 |
August | 0.00 | 0.00 | 0.402825E+11 | 0.328703E+11 | 61826.40 | 04-AUG-08:11 | 48209.25 | 0.55 |
September | 0.00 | 0.00 | 0.281115E+11 | 0.249336E+11 | 54661.14 | 08-SEP-21:11 | 54661.14 | 0.39 |
October | 0.00 | 0.00 | 0.840349E+10 | 0.684989E+10 | 52233.41 | 01-OCT-18:01 | 52233.41 | 0.21 |
November | 0.00 | 0.00 | 0.241313E+10 | 0.178667E+10 | 50108.43 | 06-NOV-19:01 | 50108.43 | 0.11 |
December | 0.00 | 0.00 | 0.877203E+09 | 0.808385E+09 | 49614.13 | 03-DEC-09:01 | 49614.13 | 0.02 |
Annual Sum or Average | 0.209528E+12 | 0.175806E+12 | 0.28 | |||||
Minimum of Months | 0.00 | 0.00 | 0.877203E+09 | 0.808385E+09 | 49135.39 | 45139.18 | 0.02 | |
Maximum of Months | 0.00 | 0.00 | 0.460047E+11 | 0.387457E+11 | 65144.49 | 54661.14 | 0.61 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.800519E+09 | 0.747202E+09 | 8765.64 | 20-JAN-09:01 | 8765.64 | 0.06 |
February | 0.00 | 0.00 | 0.956964E+09 | 0.887551E+09 | 8764.49 | 14-FEB-09:01 | 8764.49 | 0.07 |
March | 0.00 | 0.00 | 0.187480E+10 | 0.185100E+10 | 8765.52 | 13-MAR-08:61 | 8765.52 | 0.02 |
April | 0.00 | 0.00 | 0.127767E+10 | 0.115209E+10 | 8765.28 | 08-APR-08:61 | 8765.28 | 0.11 |
May | 0.00 | 0.00 | 0.310293E+10 | 0.253414E+10 | 9647.96 | 04-MAY-08:11 | 9647.96 | 0.42 |
June | 0.00 | 0.00 | 0.789647E+10 | 0.653350E+10 | 9742.91 | 17-JUN-08:62 | 7622.74 | 0.76 |
July | 0.00 | 0.00 | 0.830369E+10 | 0.664279E+10 | 10313.11 | 31-JUL-18:01 | 7673.84 | 0.85 |
August | 0.00 | 0.00 | 0.789191E+10 | 0.627866E+10 | 9291.14 | 29-AUG-18:01 | 8281.35 | 0.79 |
September | 0.00 | 0.00 | 0.584705E+10 | 0.515238E+10 | 8765.33 | 09-SEP-18:01 | 8765.33 | 0.47 |
October | 0.00 | 0.00 | 0.234675E+10 | 0.218329E+10 | 8765.62 | 15-OCT-08:61 | 8765.62 | 0.14 |
November | 0.00 | 0.00 | 0.108291E+10 | 0.963093E+09 | 8764.65 | 07-NOV-09:01 | 8764.65 | 0.11 |
December | 0.00 | 0.00 | 0.541510E+09 | 0.534641E+09 | 8765.52 | 18-DEC-09:01 | 8765.52 | 0.01 |
Annual Sum or Average | 0.419232E+11 | 0.354603E+11 | 0.32 | |||||
Minimum of Months | 0.00 | 0.00 | 0.541510E+09 | 0.534641E+09 | 8764.49 | 7622.74 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.830369E+10 | 0.664279E+10 | 10313.11 | 9647.96 | 0.85 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115045E+09 | 95163566.00 | 8717.18 | 20-JAN-09:01 | 8717.18 | 0.02 |
February | 0.00 | 0.00 | 0.278882E+09 | 0.243232E+09 | 8564.03 | 14-FEB-09:01 | 8564.03 | 0.03 |
March | 0.00 | 0.00 | 0.890432E+09 | 0.869240E+09 | 8717.15 | 13-MAR-08:61 | 8717.15 | 0.02 |
April | 0.00 | 0.00 | 0.899302E+09 | 0.790852E+09 | 8716.89 | 08-APR-08:61 | 8716.89 | 0.10 |
May | 0.00 | 0.00 | 0.230845E+10 | 0.180716E+10 | 9698.21 | 13-MAY-08:11 | 9698.21 | 0.37 |
June | 0.00 | 0.00 | 0.639601E+10 | 0.535192E+10 | 11368.24 | 21-JUN-08:11 | 9629.34 | 0.60 |
July | 0.00 | 0.00 | 0.663989E+10 | 0.542418E+10 | 11928.89 | 01-JUL-08:11 | 11928.89 | 0.66 |
August | 0.00 | 0.00 | 0.599495E+10 | 0.475064E+10 | 12466.76 | 05-AUG-08:11 | 10641.48 | 0.61 |
September | 0.00 | 0.00 | 0.377731E+10 | 0.320900E+10 | 10401.71 | 07-SEP-08:11 | 10401.71 | 0.38 |
October | 0.00 | 0.00 | 0.879365E+09 | 0.795245E+09 | 9307.28 | 11-OCT-08:11 | 9307.28 | 0.08 |
November | 0.00 | 0.00 | 0.220269E+09 | 0.184599E+09 | 8716.24 | 07-NOV-09:01 | 8716.24 | 0.03 |
December | 0.00 | 0.00 | 57608427.55 | 53025830.77 | 8531.79 | 03-DEC-09:01 | 8531.79 | 0.00 |
Annual Sum or Average | 0.284575E+11 | 0.235743E+11 | 0.24 | |||||
Minimum of Months | 0.00 | 0.00 | 57608427.55 | 53025830.77 | 8531.79 | 8531.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.663989E+10 | 0.542418E+10 | 12466.76 | 11928.89 | 0.66 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.211586E+09 | 0.198195E+09 | 2722.24 | 12-JAN-16:11 | 2722.24 | 0.04 |
February | 0.00 | 0.00 | 0.232007E+09 | 0.226033E+09 | 2721.76 | 20-FEB-16:11 | 2721.76 | 0.03 |
March | 0.00 | 0.00 | 0.498445E+09 | 0.496118E+09 | 2722.13 | 26-MAR-15:11 | 2722.13 | 0.01 |
April | 0.00 | 0.00 | 0.304301E+09 | 0.285758E+09 | 3313.91 | 06-APR-18:31 | 3313.91 | 0.06 |
May | 0.00 | 0.00 | 0.823031E+09 | 0.686826E+09 | 2990.58 | 22-MAY-08:61 | 2198.08 | 0.35 |
June | 0.00 | 0.00 | 0.207676E+10 | 0.171507E+10 | 3153.14 | 18-JUN-08:61 | 2412.09 | 0.72 |
July | 0.00 | 0.00 | 0.199075E+10 | 0.153478E+10 | 3235.55 | 30-JUL-08:61 | 2358.93 | 0.81 |
August | 0.00 | 0.00 | 0.195647E+10 | 0.153629E+10 | 3230.47 | 05-AUG-08:61 | 2364.87 | 0.75 |
September | 0.00 | 0.00 | 0.148292E+10 | 0.129803E+10 | 2722.36 | 30-SEP-15:11 | 2722.36 | 0.43 |
October | 0.00 | 0.00 | 0.659839E+09 | 0.627077E+09 | 2722.38 | 09-OCT-15:12 | 2722.38 | 0.09 |
November | 0.00 | 0.00 | 0.308524E+09 | 0.280347E+09 | 2722.25 | 19-NOV-16:11 | 2722.25 | 0.08 |
December | 0.00 | 0.00 | 0.135421E+09 | 0.134926E+09 | 2721.50 | 29-DEC-16:11 | 2721.50 | 0.00 |
Annual Sum or Average | 0.106801E+11 | 0.901945E+10 | 0.28 | |||||
Minimum of Months | 0.00 | 0.00 | 0.135421E+09 | 0.134926E+09 | 2721.50 | 2198.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207676E+10 | 0.171507E+10 | 3313.91 | 3313.91 | 0.81 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 29878789.81 | 28631910.68 | 2781.01 | 20-JAN-16:31 | 2781.01 | 0.00 |
February | 0.00 | 0.00 | 52590742.15 | 52064924.44 | 2720.55 | 26-FEB-17:11 | 2720.55 | 0.00 |
March | 0.00 | 0.00 | 0.204625E+09 | 0.203416E+09 | 3443.31 | 31-MAR-18:01 | 3443.31 | 0.00 |
April | 0.00 | 0.00 | 0.182726E+09 | 0.167084E+09 | 3457.50 | 08-APR-17:21 | 3457.50 | 0.05 |
May | 0.00 | 0.00 | 0.550575E+09 | 0.420113E+09 | 3050.73 | 09-MAY-19:51 | 3050.73 | 0.32 |
June | 0.00 | 0.00 | 0.177325E+10 | 0.146249E+10 | 3293.60 | 22-JUN-21:11 | 2707.30 | 0.58 |
July | 0.00 | 0.00 | 0.166547E+10 | 0.129895E+10 | 3393.57 | 31-JUL-21:11 | 2366.59 | 0.64 |
August | 0.00 | 0.00 | 0.153737E+10 | 0.119144E+10 | 3335.82 | 05-AUG-21:11 | 2967.12 | 0.58 |
September | 0.00 | 0.00 | 0.916457E+09 | 0.757803E+09 | 2957.68 | 15-SEP-19:11 | 2957.68 | 0.35 |
October | 0.00 | 0.00 | 0.224960E+09 | 0.212302E+09 | 3230.95 | 08-OCT-17:31 | 3230.95 | 0.04 |
November | 0.00 | 0.00 | 52679308.56 | 49507002.98 | 2729.37 | 07-NOV-17:01 | 2729.37 | 0.01 |
December | 0.00 | 0.00 | 12189134.42 | 12132092.63 | 2688.56 | 03-DEC-16:11 | 2688.56 | 0.00 |
Annual Sum or Average | 0.720276E+10 | 0.585594E+10 | 0.22 | |||||
Minimum of Months | 0.00 | 0.00 | 12189134.42 | 12132092.63 | 2688.56 | 2366.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.177325E+10 | 0.146249E+10 | 3457.50 | 3457.50 | 0.64 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.646857E+10 | 0.607501E+10 | 11655.15 | 20-JAN-13:04 | 11655.15 | 0.38 |
February | 0.00 | 0.00 | 0.487270E+10 | 0.455502E+10 | 10868.15 | 17-FEB-13:30 | 10868.15 | 0.30 |
March | 0.00 | 0.00 | 0.447654E+10 | 0.430627E+10 | 10775.68 | 11-MAR-13:26 | 10775.68 | 0.13 |
April | 0.00 | 0.00 | 0.181484E+10 | 0.150257E+10 | 11051.66 | 28-APR-08:61 | 8050.93 | 0.21 |
May | 0.00 | 0.00 | 0.390774E+10 | 0.299836E+10 | 11991.82 | 29-MAY-08:61 | 8184.37 | 0.52 |
June | 0.00 | 0.00 | 0.879722E+10 | 0.696053E+10 | 11819.25 | 18-JUN-08:61 | 8508.77 | 0.84 |
July | 0.00 | 0.00 | 0.971724E+10 | 0.750090E+10 | 12361.27 | 31-JUL-18:01 | 8336.18 | 0.88 |
August | 0.00 | 0.00 | 0.100595E+11 | 0.792530E+10 | 11801.21 | 05-AUG-08:61 | 8710.20 | 0.83 |
September | 0.00 | 0.00 | 0.947429E+10 | 0.841450E+10 | 11009.22 | 21-SEP-08:61 | 8898.71 | 0.63 |
October | 0.00 | 0.00 | 0.684226E+10 | 0.638310E+10 | 11598.42 | 09-OCT-08:61 | 8714.92 | 0.36 |
November | 0.00 | 0.00 | 0.656665E+10 | 0.603592E+10 | 11329.59 | 05-NOV-12:18 | 11329.59 | 0.44 |
December | 0.00 | 0.00 | 0.482465E+10 | 0.464922E+10 | 11518.28 | 17-DEC-13:20 | 11518.28 | 0.20 |
Annual Sum or Average | 0.778222E+11 | 0.673067E+11 | 0.48 | |||||
Minimum of Months | 0.00 | 0.00 | 0.181484E+10 | 0.150257E+10 | 10775.68 | 8050.93 | 0.13 | |
Maximum of Months | 0.00 | 0.00 | 0.100595E+11 | 0.841450E+10 | 12361.27 | 11655.15 | 0.88 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.554909E+10 | 0.554909E+10 | 198207.36 | 20-JAN-13:03 | 198207.36 | 0.00 |
February | 0.00 | 0.00 | 0.308469E+10 | 0.308469E+10 | 188330.21 | 18-FEB-13:11 | 188330.21 | 0.00 |
March | 0.00 | 0.00 | 0.175496E+11 | 0.175496E+11 | 249341.96 | 14-MAR-13:11 | 249341.96 | 0.00 |
April | 0.00 | 0.00 | 0.184775E+11 | 0.184775E+11 | 208893.49 | 19-APR-13:32 | 208893.49 | 0.00 |
May | 0.00 | 0.00 | 0.836052E+11 | 0.836052E+11 | 317872.50 | 31-MAY-17:19 | 317872.50 | 0.04 |
June | 0.00 | 0.00 | 0.269794E+12 | 0.259468E+12 | 418009.41 | 26-JUN-18:21 | 418009.41 | 0.26 |
July | 0.00 | 0.00 | 0.314666E+12 | 0.286294E+12 | 429065.47 | 30-JUL-11:52 | 257387.36 | 0.29 |
August | 0.00 | 0.00 | 0.280424E+12 | 0.265280E+12 | 404407.35 | 05-AUG-14:18 | 251622.09 | 0.34 |
September | 0.00 | 0.00 | 0.196179E+12 | 0.196158E+12 | 362388.22 | 10-SEP-18:21 | 362388.22 | 0.09 |
October | 0.00 | 0.00 | 0.359123E+11 | 0.359123E+11 | 305641.20 | 11-OCT-13:02 | 305641.20 | 0.00 |
November | 0.00 | 0.00 | 0.116818E+11 | 0.116818E+11 | 222156.71 | 07-NOV-15:11 | 222156.71 | 0.00 |
December | 0.00 | 0.00 | 0.785529E+10 | 0.785529E+10 | 209806.89 | 02-DEC-14:52 | 209806.89 | 0.00 |
Annual Sum or Average | 0.124478E+13 | 0.119092E+13 | 0.09 | |||||
Minimum of Months | 0.00 | 0.00 | 0.308469E+10 | 0.308469E+10 | 188330.21 | 188330.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.314666E+12 | 0.286294E+12 | 429065.47 | 418009.41 | 0.34 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.186069E+09 | 0.186069E+09 | 11108.81 | 20-JAN-13:51 | 11108.81 | 0.00 |
February | 0.00 | 0.00 | 0.116738E+09 | 0.116738E+09 | 9341.83 | 18-FEB-13:51 | 9341.83 | 0.00 |
March | 0.00 | 0.00 | 0.831179E+09 | 0.831179E+09 | 13400.28 | 13-MAR-15:11 | 13400.28 | 0.00 |
April | 0.00 | 0.00 | 0.978180E+09 | 0.978180E+09 | 12340.17 | 20-APR-12:51 | 12340.17 | 0.00 |
May | 0.00 | 0.00 | 0.480898E+10 | 0.480898E+10 | 15537.24 | 31-MAY-18:01 | 15537.24 | 0.06 |
June | 0.00 | 0.00 | 0.165963E+11 | 0.161447E+11 | 22860.68 | 18-JUN-12:02 | 15859.31 | 0.37 |
July | 0.00 | 0.00 | 0.201229E+11 | 0.183967E+11 | 25564.18 | 30-JUL-15:21 | 13791.05 | 0.44 |
August | 0.00 | 0.00 | 0.174853E+11 | 0.165466E+11 | 19997.93 | 05-AUG-15:12 | 10119.98 | 0.49 |
September | 0.00 | 0.00 | 0.111561E+11 | 0.111561E+11 | 16717.38 | 10-SEP-13:00 | 16717.38 | 0.15 |
October | 0.00 | 0.00 | 0.160868E+10 | 0.160868E+10 | 14550.72 | 11-OCT-15:11 | 14550.72 | 0.00 |
November | 0.00 | 0.00 | 0.463723E+09 | 0.463723E+09 | 12345.16 | 06-NOV-13:12 | 12345.16 | 0.00 |
December | 0.00 | 0.00 | 0.266625E+09 | 0.266625E+09 | 11612.35 | 01-DEC-14:00 | 11612.35 | 0.00 |
Annual Sum or Average | 0.746208E+11 | 0.715042E+11 | 0.13 | |||||
Minimum of Months | 0.00 | 0.00 | 0.116738E+09 | 0.116738E+09 | 9341.83 | 9341.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201229E+11 | 0.183967E+11 | 25564.18 | 16717.38 | 0.49 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 28980.04 | 59805.12 | 31-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 29351.83 | 59963.67 | 13-FEB-07:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 28944.36 | 59733.15 | 01-MAR-07:16 |
April | 0.00 | 0.00 | 01-APR-00:01 | 27788.85 | 57896.36 | 03-APR-06:34 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 26254.19 | 55288.12 | 01-MAY-06:34 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 24705.41 | 53597.76 | 05-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 23584.03 | 52972.03 | 11-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 23210.59 | 51710.01 | 29-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 23624.35 | 49398.86 | 29-SEP-06:43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 24804.43 | 52317.85 | 31-OCT-06:32 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 26353.03 | 55461.58 | 30-NOV-07:09 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 27894.15 | 58107.53 | 29-DEC-07:35 |
Annual Sum or Average | 0.00 | 26273.49 | ||||
Minimum of Months | 0.00 | 0.00 | 23210.59 | 49398.86 | ||
Maximum of Months | 0.00 | 0.00 | 29351.83 | 59963.67 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27.83 | 6161.93 | 02-JAN-13:30 | 16461.21 | 199876.62 | 05-JAN-09:04 |
February | 13.35 | 5934.77 | 02-FEB-16:10 | 19472.59 | 201971.91 | 12-FEB-05:26 |
March | 12.05 | 4522.83 | 29-MAR-15:10 | 10002.09 | 162921.36 | 19-MAR-06:34 |
April | 1.39 | 1637.63 | 10-APR-20:50 | 7070.31 | 110594.76 | 02-APR-15:16 |
May | 2.24 | 2280.62 | 19-MAY-01:12 | 661.45 | 61107.74 | 29-MAY-22:21 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 2.73 | 3750.51 | 28-JUN-08:17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 2.41 | 4471.92 | 31-JUL-08:17 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 3.91 | 8544.82 | 30-AUG-08:15 |
September | 0.04 | 455.17 | 21-SEP-16:10 | 193.01 | 37961.97 | 30-SEP-22:31 |
October | 1.19 | 3120.07 | 22-OCT-15:10 | 7029.71 | 152583.35 | 31-OCT-15:34 |
November | 12.93 | 6615.34 | 21-NOV-15:30 | 11452.57 | 163075.99 | 29-NOV-19:04 |
December | 7.51 | 3973.49 | 07-DEC-16:02 | 29074.40 | 235295.64 | 21-DEC-09:06 |
Annual Sum or Average | 6.52 | 8402.96 | ||||
Minimum of Months | 0.00 | 0.00 | 2.41 | 3750.51 | ||
Maximum of Months | 27.83 | 6615.34 | 29074.40 | 235295.64 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16890.95 | 322487.07 | 20-JAN-13:03 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 12409.38 | 303074.86 | 18-FEB-13:33 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 19292.70 | 359185.46 | 13-MAR-15:43 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 14226.79 | 260189.07 | 07-APR-15:23 | 0.00 | 0.00 | 01-APR-00:01 |
May | 53247.89 | 418304.51 | 31-MAY-15:13 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 156314.80 | 529935.59 | 26-JUN-18:11 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 172338.58 | 503691.56 | 01-JUL-18:40 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 156557.79 | 506476.21 | 16-AUG-20:13 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 118857.86 | 495173.81 | 12-SEP-18:17 | 0.00 | 0.00 | 01-SEP-00:01 |
October | 34026.50 | 443538.57 | 11-OCT-15:17 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 19799.08 | 341838.80 | 07-NOV-14:23 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 12601.39 | 314317.22 | 02-DEC-14:57 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 65854.93 | 0.00 | ||||
Minimum of Months | 12409.38 | 260189.07 | 0.00 | 0.00 | ||
Maximum of Months | 172338.58 | 529935.59 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261252E+10 | 0.82 | 1298.89 | 01-JAN-09:01 | 1.08 |
February | 0.235970E+10 | 0.82 | 1298.89 | 01-FEB-09:01 | 1.08 |
March | 0.261252E+10 | 0.82 | 1298.89 | 01-MAR-09:01 | 1.08 |
April | 0.252825E+10 | 0.82 | 1298.89 | 01-APR-08:02 | 1.08 |
May | 0.261252E+10 | 0.82 | 1298.89 | 01-MAY-08:61 | 1.08 |
June | 0.252825E+10 | 0.82 | 1298.89 | 01-JUN-06:09 | 1.07 |
July | 0.261252E+10 | 0.82 | 1298.89 | 01-JUL-00:01 | 1.08 |
August | 0.261252E+10 | 0.82 | 1298.89 | 01-AUG-00:03 | 1.07 |
September | 0.252825E+10 | 0.82 | 1298.89 | 01-SEP-00:01 | 1.08 |
October | 0.261252E+10 | 0.82 | 1298.89 | 01-OCT-08:61 | 1.08 |
November | 0.252825E+10 | 0.82 | 1298.89 | 01-NOV-08:61 | 1.08 |
December | 0.261252E+10 | 0.83 | 1298.89 | 01-DEC-16:31 | 1.08 |
Annual Sum or Average | 0.307604E+11 | 0.82 | |||
Minimum of Months | 0.235970E+10 | 0.82 | 1298.89 | 1.07 | |
Maximum of Months | 0.261252E+10 | 0.83 | 1298.89 | 1.08 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.607456E+11 | 1.04 | 51830.32 | 20-JAN-10:22 | 2.26 |
February | 0.536129E+11 | 1.02 | 51830.32 | 18-FEB-09:58 | 2.26 |
March | 0.591451E+11 | 1.02 | 51943.44 | 15-MAR-20:52 | 2.27 |
April | 0.557701E+11 | 1.01 | 51830.32 | 08-APR-14:42 | 2.26 |
May | 0.597785E+11 | 1.04 | 51943.44 | 18-MAY-19:32 | 2.25 |
June | 0.590400E+11 | 1.08 | 51943.44 | 01-JUN-17:13 | 2.25 |
July | 0.611690E+11 | 1.08 | 51943.44 | 01-JUL-00:02 | 2.26 |
August | 0.633699E+11 | 1.11 | 51943.44 | 02-AUG-15:22 | 2.25 |
September | 0.628836E+11 | 1.12 | 51943.44 | 02-SEP-17:08 | 2.25 |
October | 0.626655E+11 | 1.07 | 51943.44 | 11-OCT-19:10 | 2.26 |
November | 0.598520E+11 | 1.05 | 51906.73 | 18-NOV-14:02 | 2.26 |
December | 0.578750E+11 | 1.01 | 51830.32 | 02-DEC-12:42 | 2.27 |
Annual Sum or Average | 0.715907E+12 | 1.05 | |||
Minimum of Months | 0.536129E+11 | 1.01 | 51830.32 | 2.25 | |
Maximum of Months | 0.633699E+11 | 1.12 | 51943.44 | 2.27 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.33 | 76.61 | 01-JAN-00:03 | 0.33 |
February | 0.185347E+09 | 0.33 | 76.61 | 01-FEB-00:01 | 0.33 |
March | 0.205205E+09 | 0.33 | 76.61 | 01-MAR-00:01 | 0.33 |
April | 0.198586E+09 | 0.33 | 76.61 | 01-APR-00:01 | 0.33 |
May | 0.205205E+09 | 0.33 | 76.61 | 01-MAY-00:01 | 0.33 |
June | 0.198586E+09 | 0.33 | 76.61 | 01-JUN-00:02 | 0.33 |
July | 0.205205E+09 | 0.33 | 76.61 | 01-JUL-00:01 | 0.33 |
August | 0.205205E+09 | 0.33 | 76.61 | 01-AUG-00:01 | 0.32 |
September | 0.198586E+09 | 0.33 | 76.61 | 01-SEP-00:01 | 0.33 |
October | 0.205205E+09 | 0.33 | 76.61 | 01-OCT-00:01 | 0.33 |
November | 0.198586E+09 | 0.33 | 76.61 | 01-NOV-00:01 | 0.33 |
December | 0.205205E+09 | 0.33 | 76.61 | 01-DEC-00:01 | 0.33 |
Annual Sum or Average | 0.241613E+10 | 0.33 | |||
Minimum of Months | 0.185347E+09 | 0.33 | 76.61 | 0.32 | |
Maximum of Months | 0.205205E+09 | 0.33 | 76.61 | 0.33 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:02 | -0.0 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | -0.0 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | -0.0 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | -0.0 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:02 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.23 | 612.92 | 01-JAN-07:01 | 0.32 |
February | 0.105030E+10 | 0.23 | 612.92 | 01-FEB-07:01 | 0.32 |
March | 0.116283E+10 | 0.23 | 612.92 | 01-MAR-07:01 | 0.32 |
April | 0.112532E+10 | 0.23 | 612.92 | 01-APR-06:01 | 0.32 |
May | 0.116283E+10 | 0.23 | 612.92 | 01-MAY-06:01 | 0.32 |
June | 0.112532E+10 | 0.23 | 612.92 | 01-JUN-06:01 | 0.32 |
July | 0.116283E+10 | 0.23 | 612.92 | 01-JUL-06:01 | 0.33 |
August | 0.116283E+10 | 0.23 | 612.92 | 01-AUG-06:01 | 0.32 |
September | 0.112532E+10 | 0.23 | 612.92 | 01-SEP-06:01 | 0.32 |
October | 0.116283E+10 | 0.23 | 612.92 | 01-OCT-06:01 | 0.32 |
November | 0.112532E+10 | 0.23 | 612.92 | 01-NOV-06:01 | 0.32 |
December | 0.116283E+10 | 0.23 | 612.92 | 01-DEC-07:01 | 0.33 |
Annual Sum or Average | 0.136914E+11 | 0.23 | |||
Minimum of Months | 0.105030E+10 | 0.23 | 612.92 | 0.32 | |
Maximum of Months | 0.116283E+10 | 0.23 | 612.92 | 0.33 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.319869E+09 | 0.55 | 902.49 | 01-JAN-16:11 | 0.71 |
February | 0.332440E+09 | 0.56 | 902.49 | 01-FEB-09:01 | 0.71 |
March | 0.368311E+09 | 0.58 | 902.49 | 01-MAR-09:01 | 0.71 |
April | 0.277427E+09 | 0.52 | 902.49 | 01-APR-15:11 | 0.71 |
May | 0.304121E+09 | 0.56 | 902.49 | 01-MAY-08:61 | 0.70 |
June | 0.674571E+09 | 0.66 | 902.49 | 01-JUN-08:61 | 0.70 |
July | 0.649107E+09 | 0.67 | 902.49 | 01-JUL-08:61 | 0.71 |
August | 0.613266E+09 | 0.66 | 902.49 | 01-AUG-08:61 | 0.71 |
September | 0.515852E+09 | 0.65 | 902.49 | 01-SEP-08:62 | 0.70 |
October | 0.382400E+09 | 0.61 | 902.49 | 01-OCT-08:61 | 0.70 |
November | 0.308458E+09 | 0.56 | 902.49 | 01-NOV-08:61 | 0.71 |
December | 0.434738E+09 | 0.56 | 902.49 | 01-DEC-16:11 | 0.71 |
Annual Sum or Average | 0.518056E+10 | 0.60 | |||
Minimum of Months | 0.277427E+09 | 0.52 | 902.49 | 0.70 | |
Maximum of Months | 0.674571E+09 | 0.67 | 902.49 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.362065E+09 | 0.52 | 891.47 | 01-JAN-09:01 | 0.71 |
February | 0.352549E+09 | 0.55 | 891.47 | 01-FEB-09:01 | 0.71 |
March | 0.304204E+09 | 0.52 | 891.47 | 01-MAR-09:01 | 0.71 |
April | 0.250301E+09 | 0.49 | 891.47 | 01-APR-15:11 | 0.71 |
May | 0.207392E+09 | 0.47 | 891.47 | 01-MAY-08:61 | 0.70 |
June | 0.541954E+09 | 0.52 | 891.47 | 01-JUN-08:11 | 0.70 |
July | 0.520815E+09 | 0.51 | 891.47 | 01-JUL-08:11 | 0.71 |
August | 0.456172E+09 | 0.51 | 891.47 | 01-AUG-08:12 | 0.71 |
September | 0.318367E+09 | 0.48 | 891.47 | 01-SEP-08:11 | 0.70 |
October | 0.266732E+09 | 0.51 | 891.47 | 01-OCT-08:61 | 0.70 |
November | 0.307245E+09 | 0.52 | 891.47 | 01-NOV-08:61 | 0.71 |
December | 0.508573E+09 | 0.56 | 891.47 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.439637E+10 | 0.51 | |||
Minimum of Months | 0.207392E+09 | 0.47 | 891.47 | 0.70 | |
Maximum of Months | 0.541954E+09 | 0.56 | 891.47 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.197570E+10 | 0.35 | 4094.87 | 01-JAN-09:41 | 0.71 |
February | 0.111792E+10 | 0.26 | 4094.87 | 17-FEB-12:11 | 0.70 |
March | 0.107026E+10 | 0.24 | 4094.87 | 10-MAR-12:01 | 0.70 |
April | 0.146313E+09 | 0.09 | 973.79 | 13-APR-12:23 | 0.70 |
May | 0.735085E+09 | 0.40 | 1053.40 | 06-MAY-15:02 | 0.70 |
June | 0.166713E+10 | 0.68 | 1296.23 | 14-JUN-17:11 | 0.70 |
July | 0.184417E+10 | 0.69 | 1267.96 | 18-JUL-17:11 | 0.70 |
August | 0.196212E+10 | 0.69 | 2130.24 | 31-AUG-12:21 | 0.70 |
September | 0.224516E+10 | 0.65 | 4094.87 | 28-SEP-11:21 | 0.70 |
October | 0.190236E+10 | 0.38 | 4094.87 | 08-OCT-11:41 | 0.70 |
November | 0.170836E+10 | 0.34 | 4094.87 | 05-NOV-11:01 | 0.70 |
December | 0.126198E+10 | 0.22 | 4094.87 | 02-DEC-11:43 | 0.70 |
Annual Sum or Average | 0.176366E+11 | 0.42 | |||
Minimum of Months | 0.146313E+09 | 0.09 | 973.79 | 0.70 | |
Maximum of Months | 0.224516E+10 | 0.69 | 4094.87 | 0.71 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132781E+10 | 0.48 | 4509.94 | 01-JAN-09:01 | 0.71 |
February | 0.132348E+10 | 0.48 | 4509.94 | 01-FEB-09:01 | 0.71 |
March | 0.115553E+10 | 0.46 | 4509.94 | 01-MAR-16:11 | 0.71 |
April | 0.107309E+10 | 0.46 | 4509.94 | 01-APR-08:61 | 0.70 |
May | 0.212993E+10 | 0.42 | 4509.94 | 01-MAY-08:61 | 0.71 |
June | 0.401833E+10 | 0.47 | 4509.94 | 01-JUN-08:11 | 0.70 |
July | 0.420136E+10 | 0.47 | 4509.94 | 01-JUL-08:11 | 0.71 |
August | 0.346761E+10 | 0.45 | 4509.94 | 01-AUG-08:12 | 0.71 |
September | 0.255325E+10 | 0.42 | 4509.94 | 01-SEP-08:11 | 0.70 |
October | 0.117381E+10 | 0.45 | 4509.94 | 01-OCT-08:61 | 0.70 |
November | 0.112237E+10 | 0.48 | 4509.94 | 01-NOV-08:61 | 0.71 |
December | 0.190074E+10 | 0.50 | 4509.94 | 01-DEC-16:31 | 0.71 |
Annual Sum or Average | 0.254473E+11 | 0.46 | |||
Minimum of Months | 0.107309E+10 | 0.42 | 4509.94 | 0.70 | |
Maximum of Months | 0.420136E+10 | 0.50 | 4509.94 | 0.71 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.308146E+09 | 0.54 | 775.38 | 01-JAN-09:01 | 0.71 |
February | 0.333150E+09 | 0.58 | 775.38 | 01-FEB-09:01 | 0.71 |
March | 0.354867E+09 | 0.59 | 775.38 | 01-MAR-09:01 | 0.71 |
April | 0.283658E+09 | 0.55 | 775.38 | 01-APR-15:11 | 0.71 |
May | 0.323039E+09 | 0.60 | 775.38 | 01-MAY-08:61 | 0.70 |
June | 0.714871E+09 | 0.69 | 775.38 | 01-JUN-08:61 | 0.70 |
July | 0.739800E+09 | 0.69 | 775.38 | 01-JUL-06:12 | 0.71 |
August | 0.675176E+09 | 0.69 | 775.38 | 01-AUG-08:61 | 0.71 |
September | 0.538947E+09 | 0.67 | 775.38 | 01-SEP-08:62 | 0.70 |
October | 0.364915E+09 | 0.62 | 775.38 | 01-OCT-08:61 | 0.70 |
November | 0.299141E+09 | 0.56 | 775.38 | 01-NOV-08:61 | 0.71 |
December | 0.416856E+09 | 0.56 | 775.38 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.535257E+10 | 0.61 | |||
Minimum of Months | 0.283658E+09 | 0.54 | 775.38 | 0.70 | |
Maximum of Months | 0.739800E+09 | 0.69 | 775.38 | 0.71 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.335875E+09 | 0.51 | 771.07 | 01-JAN-09:01 | 0.71 |
February | 0.343956E+09 | 0.55 | 771.07 | 01-FEB-09:01 | 0.71 |
March | 0.298351E+09 | 0.52 | 771.07 | 01-MAR-09:01 | 0.71 |
April | 0.262353E+09 | 0.51 | 771.07 | 01-APR-15:11 | 0.71 |
May | 0.253191E+09 | 0.51 | 771.07 | 01-MAY-08:61 | 0.70 |
June | 0.567347E+09 | 0.54 | 771.07 | 01-JUN-08:11 | 0.70 |
July | 0.585344E+09 | 0.52 | 771.07 | 01-JUL-08:11 | 0.71 |
August | 0.507998E+09 | 0.53 | 771.07 | 01-AUG-08:12 | 0.71 |
September | 0.367106E+09 | 0.52 | 771.07 | 01-SEP-08:11 | 0.70 |
October | 0.264558E+09 | 0.51 | 771.07 | 01-OCT-08:61 | 0.70 |
November | 0.298591E+09 | 0.51 | 771.07 | 01-NOV-08:61 | 0.71 |
December | 0.484940E+09 | 0.55 | 771.07 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.456961E+10 | 0.52 | |||
Minimum of Months | 0.253191E+09 | 0.51 | 771.07 | 0.70 | |
Maximum of Months | 0.585344E+09 | 0.55 | 771.07 | 0.71 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 99363838.04 | 0.55 | 240.97 | 01-JAN-16:11 | 0.71 |
February | 0.102230E+09 | 0.57 | 240.97 | 01-FEB-09:01 | 0.71 |
March | 0.110815E+09 | 0.59 | 240.97 | 01-MAR-09:01 | 0.71 |
April | 85177367.71 | 0.55 | 240.97 | 01-APR-15:11 | 0.71 |
May | 92369390.37 | 0.59 | 240.97 | 01-MAY-08:61 | 0.70 |
June | 0.191135E+09 | 0.67 | 240.97 | 01-JUN-08:61 | 0.70 |
July | 0.177276E+09 | 0.67 | 240.97 | 01-JUL-08:61 | 0.71 |
August | 0.172043E+09 | 0.66 | 240.97 | 01-AUG-08:61 | 0.71 |
September | 0.140898E+09 | 0.65 | 240.97 | 01-SEP-15:11 | 0.70 |
October | 0.113909E+09 | 0.62 | 240.97 | 01-OCT-08:61 | 0.70 |
November | 95368274.48 | 0.57 | 240.97 | 01-NOV-08:61 | 0.71 |
December | 0.131258E+09 | 0.58 | 240.97 | 01-DEC-16:11 | 0.71 |
Annual Sum or Average | 0.151184E+10 | 0.61 | |||
Minimum of Months | 85177367.71 | 0.55 | 240.97 | 0.70 | |
Maximum of Months | 0.191135E+09 | 0.67 | 240.97 | 0.71 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113336E+09 | 0.55 | 238.12 | 01-JAN-09:01 | 0.71 |
February | 0.109474E+09 | 0.57 | 238.12 | 01-FEB-09:01 | 0.71 |
March | 94297738.16 | 0.54 | 238.12 | 01-MAR-09:01 | 0.71 |
April | 77185880.18 | 0.52 | 238.12 | 01-APR-08:61 | 0.70 |
May | 64148258.23 | 0.49 | 238.12 | 01-MAY-08:61 | 0.70 |
June | 0.158627E+09 | 0.53 | 238.12 | 01-JUN-08:11 | 0.70 |
July | 0.147862E+09 | 0.52 | 238.12 | 01-JUL-08:11 | 0.71 |
August | 0.133143E+09 | 0.52 | 238.12 | 01-AUG-08:12 | 0.71 |
September | 89608164.55 | 0.49 | 238.12 | 01-SEP-08:11 | 0.70 |
October | 83593823.98 | 0.52 | 238.12 | 01-OCT-08:61 | 0.70 |
November | 97080109.88 | 0.54 | 238.12 | 01-NOV-08:61 | 0.71 |
December | 0.157391E+09 | 0.58 | 238.12 | 01-DEC-09:01 | 0.71 |
Annual Sum or Average | 0.132575E+10 | 0.53 | |||
Minimum of Months | 64148258.23 | 0.49 | 238.12 | 0.70 | |
Maximum of Months | 0.158627E+09 | 0.58 | 238.12 | 0.71 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.785914E+09 | 0.62 | 868.59 | 01-JAN-09:01 | 0.70 |
February | 0.673964E+09 | 0.63 | 868.59 | 01-FEB-09:01 | 0.70 |
March | 0.586179E+09 | 0.61 | 868.59 | 01-MAR-09:01 | 0.70 |
April | 0.321459E+09 | 0.54 | 868.59 | 01-APR-08:61 | 0.70 |
May | 0.375338E+09 | 0.58 | 868.59 | 01-MAY-15:11 | 0.71 |
June | 0.766902E+09 | 0.66 | 868.59 | 01-JUN-08:61 | 0.70 |
July | 0.820547E+09 | 0.66 | 868.59 | 01-JUL-08:61 | 0.71 |
August | 0.844360E+09 | 0.66 | 868.59 | 01-AUG-08:61 | 0.71 |
September | 0.880256E+09 | 0.66 | 868.59 | 01-SEP-08:62 | 0.70 |
October | 0.786797E+09 | 0.63 | 868.59 | 01-OCT-08:61 | 0.70 |
November | 0.752575E+09 | 0.63 | 868.59 | 01-NOV-08:61 | 0.70 |
December | 0.738160E+09 | 0.61 | 868.59 | 01-DEC-09:01 | 0.70 |
Annual Sum or Average | 0.833245E+10 | 0.62 | |||
Minimum of Months | 0.321459E+09 | 0.54 | 868.59 | 0.70 | |
Maximum of Months | 0.880256E+09 | 0.66 | 868.59 | 0.71 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.204916E+10 | 0.186268E+10 | 2133.95 | 05-JAN-19:02 | 1939.76 | 1939.76 | 53.23 | 6.36 |
February | 0.202419E+10 | 0.183999E+10 | 2117.57 | 12-FEB-06:26 | 1924.88 | 1924.88 | 53.64 | 6.14 |
March | 0.150926E+10 | 0.137191E+10 | 2071.58 | 19-MAR-08:04 | 1883.07 | 1883.07 | 53.19 | 5.58 |
April | 0.122942E+10 | 0.111755E+10 | 1985.64 | 03-APR-04:00 | 1804.95 | 1804.95 | 56.26 | 4.78 |
May | 0.199948E+09 | 0.181753E+09 | 1642.62 | 03-MAY-01:56 | 1493.14 | 1493.14 | 58.02 | 3.07 |
June | 521842.85 | 474355.15 | 252.22 | 01-JUN-08:15 | 229.26 | 229.26 | 57.48 | 0.32 |
July | 419373.13 | 381210.17 | 287.56 | 31-JUL-08:17 | 261.39 | 261.39 | 57.05 | 0.36 |
August | 617795.87 | 561576.45 | 450.23 | 30-AUG-08:15 | 409.26 | 409.26 | 56.51 | 0.59 |
September | 56315567.23 | 51190850.62 | 1642.20 | 22-SEP-05:00 | 1492.76 | 1492.76 | 58.38 | 3.07 |
October | 0.101713E+10 | 0.924568E+09 | 2024.45 | 30-OCT-08:02 | 1840.22 | 1840.22 | 54.50 | 5.11 |
November | 0.158464E+10 | 0.144044E+10 | 2059.35 | 30-NOV-04:00 | 1871.95 | 1871.95 | 54.34 | 5.45 |
December | 0.236170E+10 | 0.214679E+10 | 2157.19 | 23-DEC-07:02 | 1960.88 | 1960.88 | 52.79 | 6.68 |
Annual Sum or Average | 0.120333E+11 | 0.109383E+11 | ||||||
Minimum of Months | 419373.13 | 381210.17 | 252.22 | 229.26 | 229.26 | 52.79 | 0.32 | |
Maximum of Months | 0.236170E+10 | 0.214679E+10 | 2157.19 | 1960.88 | 1960.88 | 58.38 | 6.68 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 33561573.59 | 30507470.39 | 890.85 | 20-JAN-13:03 | 809.78 | 809.78 | 6.71 | 10.36 |
February | 23271963.82 | 21154215.11 | 723.61 | 18-FEB-13:33 | 657.77 | 657.77 | 6.71 | 9.49 |
March | 64762564.00 | 58869170.67 | 1182.25 | 13-MAR-15:43 | 1074.67 | 1074.67 | 6.71 | 11.65 |
April | 36001862.48 | 32725693.00 | 524.11 | 07-APR-15:23 | 476.42 | 476.42 | 6.71 | 8.26 |
May | 0.258507E+09 | 0.234983E+09 | 2723.70 | 31-MAY-15:11 | 2475.84 | 2475.84 | 6.71 | 16.32 |
June | 0.128939E+10 | 0.117206E+10 | 3041.99 | 25-JUN-18:01 | 2765.17 | 2765.17 | 6.71 | 17.05 |
July | 0.154811E+10 | 0.140724E+10 | 3015.49 | 16-JUL-08:02 | 2741.08 | 2741.08 | 6.71 | 16.99 |
August | 0.145234E+10 | 0.132018E+10 | 3121.57 | 16-AUG-16:12 | 2837.51 | 2837.51 | 6.71 | 17.22 |
September | 0.857065E+09 | 0.779072E+09 | 3052.91 | 12-SEP-16:40 | 2775.10 | 2775.10 | 6.71 | 17.07 |
October | 0.135943E+09 | 0.123572E+09 | 2158.44 | 11-OCT-15:05 | 1962.02 | 1962.02 | 6.71 | 14.88 |
November | 51400729.54 | 46723263.16 | 1112.48 | 07-NOV-14:23 | 1011.25 | 1011.25 | 6.71 | 11.36 |
December | 29002798.03 | 26363543.41 | 897.26 | 02-DEC-14:57 | 815.61 | 815.61 | 6.71 | 10.39 |
Annual Sum or Average | 0.577936E+10 | 0.525344E+10 | ||||||
Minimum of Months | 23271963.82 | 21154215.11 | 524.11 | 476.42 | 476.42 | 6.71 | 8.26 | |
Maximum of Months | 0.154811E+10 | 0.140724E+10 | 3121.57 | 2837.51 | 2837.51 | 6.71 | 17.22 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 47.52 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:01 | 14.37 | 14.37 | 42.61 | 0.08 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:01 | 14.37 | 14.37 | 42.31 | 0.08 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:01 | 14.37 | 14.37 | 47.99 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:01 | 14.37 | 14.37 | 44.01 | 0.06 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:02 | 14.37 | 14.37 | 51.51 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:01 | 14.37 | 14.37 | 51.30 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:01 | 14.37 | 14.37 | 50.25 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:01 | 14.37 | 14.37 | 52.25 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:01 | 14.37 | 14.37 | 48.74 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:01 | 14.37 | 14.37 | 46.53 | 0.06 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:01 | 14.37 | 14.37 | 47.57 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 42.31 | 0.06 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.25 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.175016E+10 | 0.159090E+10 | 1123.28 | 01-JAN-00:03 | 1021.06 | 1021.06 | 6.72 | 17.79 |
February | 0.139471E+10 | 0.126779E+10 | 1123.28 | 01-FEB-09:03 | 1021.06 | 1021.06 | 6.92 | 17.79 |
March | 0.167894E+10 | 0.152615E+10 | 1123.28 | 01-MAR-07:11 | 1021.06 | 1021.06 | 6.73 | 17.79 |
April | 0.166752E+10 | 0.151577E+10 | 1123.28 | 01-APR-00:01 | 1021.06 | 1021.06 | 6.76 | 17.79 |
May | 0.285702E+10 | 0.259704E+10 | 1123.28 | 01-MAY-05:01 | 1021.06 | 1021.06 | 6.75 | 17.79 |
June | 0.291154E+10 | 0.264659E+10 | 1123.28 | 01-JUN-00:02 | 1021.06 | 1021.06 | 7.20 | 17.79 |
July | 0.300859E+10 | 0.273481E+10 | 1123.28 | 01-JUL-00:01 | 1021.06 | 1021.06 | 8.14 | 17.79 |
August | 0.300859E+10 | 0.273481E+10 | 1123.28 | 01-AUG-00:01 | 1021.06 | 1021.06 | 7.79 | 17.79 |
September | 0.287090E+10 | 0.260965E+10 | 1123.28 | 01-SEP-00:01 | 1021.06 | 1021.06 | 8.85 | 17.79 |
October | 0.210305E+10 | 0.191167E+10 | 1123.28 | 01-OCT-00:01 | 1021.06 | 1021.06 | 6.94 | 17.79 |
November | 0.179559E+10 | 0.163219E+10 | 1123.28 | 01-NOV-10:52 | 1021.06 | 1021.06 | 6.72 | 17.79 |
December | 0.135373E+10 | 0.123054E+10 | 1123.28 | 01-DEC-07:01 | 1021.06 | 1021.06 | 6.73 | 17.79 |
Annual Sum or Average | 0.264003E+11 | 0.239979E+11 | ||||||
Minimum of Months | 0.135373E+10 | 0.123054E+10 | 1123.28 | 1021.06 | 1021.06 | 6.72 | 17.79 | |
Maximum of Months | 0.300859E+10 | 0.273481E+10 | 1123.28 | 1021.06 | 1021.06 | 8.85 | 17.79 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 47.52 | 59.92 | 28980.04 | 59805.12 | 31-JAN-07:55 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 42.61 | 58.82 | 29351.83 | 59963.67 | 13-FEB-07:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 42.31 | 58.37 | 28944.36 | 59733.15 | 01-MAR-07:16 |
April | 0.00 | 0.00 | 01-APR-00:01 | 47.99 | 59.15 | 27788.85 | 57896.36 | 03-APR-06:34 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 44.01 | 59.86 | 26254.19 | 55288.12 | 01-MAY-06:34 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 51.51 | 59.09 | 24705.41 | 53597.76 | 05-JUN-06:03 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 51.30 | 59.24 | 23584.03 | 52972.03 | 11-JUL-06:03 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.25 | 58.04 | 23210.59 | 51710.01 | 29-AUG-06:03 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.25 | 59.47 | 23624.35 | 49398.86 | 29-SEP-06:43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 48.74 | 58.45 | 24804.43 | 52317.85 | 31-OCT-06:32 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 46.53 | 58.11 | 26353.03 | 55461.58 | 30-NOV-07:09 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 47.57 | 58.28 | 27894.15 | 58107.53 | 29-DEC-07:35 |
Annual Sum or Average | 0.00 | 26273.49 | ||||||
Minimum of Months | 0.00 | 0.00 | 42.31 | 58.04 | 23210.59 | 49398.86 | ||
Maximum of Months | 0.00 | 0.00 | 52.25 | 59.92 | 29351.83 | 59963.67 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27.83 | 6161.93 | 02-JAN-13:30 | 60.56 | 60.56 | 16461.21 | 199876.62 | 05-JAN-09:04 |
February | 13.35 | 5934.77 | 02-FEB-16:10 | 60.58 | 60.58 | 19472.59 | 201971.91 | 12-FEB-05:26 |
March | 12.05 | 4522.83 | 29-MAR-15:10 | 60.47 | 60.47 | 10002.09 | 162921.36 | 19-MAR-06:34 |
April | 1.39 | 1637.63 | 10-APR-20:50 | 60.19 | 60.19 | 7070.31 | 110594.76 | 02-APR-15:16 |
May | 2.24 | 2280.62 | 19-MAY-01:12 | 60.31 | 60.31 | 661.45 | 61107.74 | 29-MAY-22:21 |
June | 0.00 | 0.00 | 01-JUN-00:02 | 57.51 | 57.51 | 2.73 | 3750.51 | 28-JUN-08:17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 57.04 | 57.04 | 2.41 | 4471.92 | 31-JUL-08:17 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 57.03 | 57.03 | 3.91 | 8544.82 | 30-AUG-08:15 |
September | 0.04 | 455.17 | 21-SEP-16:10 | 60.05 | 60.05 | 193.01 | 37961.97 | 30-SEP-22:31 |
October | 1.19 | 3120.07 | 22-OCT-15:10 | 60.32 | 60.32 | 7029.71 | 152583.35 | 31-OCT-15:34 |
November | 12.93 | 6615.34 | 21-NOV-15:30 | 60.68 | 60.68 | 11452.57 | 163075.99 | 29-NOV-19:04 |
December | 7.51 | 3973.49 | 07-DEC-16:02 | 60.42 | 60.42 | 29074.40 | 235295.64 | 21-DEC-09:06 |
Annual Sum or Average | 6.52 | 8402.96 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.03 | 57.03 | 2.41 | 3750.51 | ||
Maximum of Months | 27.83 | 6615.34 | 60.68 | 60.68 | 29074.40 | 235295.64 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16890.95 | 322487.07 | 20-JAN-13:03 | 11.03 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 12409.38 | 303074.86 | 18-FEB-13:33 | 10.77 | 6.70 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 19292.70 | 359185.46 | 13-MAR-15:43 | 11.52 | 6.70 | 0.00 | 0.00 | 01-MAR-00:01 |
April | 14226.79 | 260189.07 | 07-APR-15:23 | 10.19 | 6.70 | 0.00 | 0.00 | 01-APR-00:01 |
May | 53247.89 | 418304.51 | 31-MAY-15:13 | 12.31 | 6.70 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 156314.80 | 529935.59 | 26-JUN-18:11 | 13.82 | 6.70 | 0.00 | 0.00 | 01-JUN-00:02 |
July | 172338.58 | 503691.56 | 01-JUL-18:40 | 13.46 | 6.70 | 0.00 | 0.00 | 01-JUL-00:01 |
August | 156557.79 | 506476.21 | 16-AUG-20:13 | 13.50 | 6.70 | 0.00 | 0.00 | 01-AUG-00:01 |
September | 118857.86 | 495173.81 | 12-SEP-18:17 | 13.35 | 6.70 | 0.00 | 0.00 | 01-SEP-00:01 |
October | 34026.50 | 443538.57 | 11-OCT-15:17 | 12.65 | 6.70 | 0.00 | 0.00 | 01-OCT-00:01 |
November | 19799.08 | 341838.80 | 07-NOV-14:23 | 11.29 | 6.70 | 0.00 | 0.00 | 01-NOV-00:01 |
December | 12601.39 | 314317.22 | 02-DEC-14:57 | 10.92 | 6.70 | 0.00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 65854.93 | 0.00 | ||||||
Minimum of Months | 12409.38 | 260189.07 | 10.19 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 172338.58 | 529935.59 | 13.82 | 6.70 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 31.95 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.06 | 74.55 |
May | 0.08 | 79.87 |
June | 3.88 | 85.04 |
July | 5.88 | 85.99 |
August | 5.32 | 88.23 |
September | 6.42 | 76.35 |
October | 0.83 | 27.60 |
November | 0.62 | 25.47 |
December | 0.13 | 27.42 |
Annual Sum or Average | 23.27 | 79.49 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 6.42 | 88.23 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.26 | 2.39 |
February | 0.71 | 2.97 |
March | 1.90 | 3.47 |
April | 1.01 | 4.79 |
May | 5.53 | 5.12 |
June | 22.52 | 8.21 |
July | 27.18 | 8.13 |
August | 26.71 | 8.27 |
September | 25.38 | 6.69 |
October | 5.44 | 3.06 |
November | 3.07 | 2.73 |
December | 2.02 | 2.72 |
Annual Sum or Average | 122.70 | 7.10 |
Minimum of Months | 0.71 | 2.39 |
Maximum of Months | 27.18 | 8.27 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.23 | 2.99 |
February | 0.17 | 3.46 |
March | 0.26 | 5.14 |
April | 0.27 | 8.97 |
May | 1.73 | 8.37 |
June | 14.22 | 9.85 |
July | 17.32 | 9.91 |
August | 16.61 | 10.18 |
September | 11.70 | 8.90 |
October | 0.96 | 3.97 |
November | 0.84 | 2.78 |
December | 0.25 | 3.35 |
Annual Sum or Average | 64.58 | 9.47 |
Minimum of Months | 0.17 | 2.78 |
Maximum of Months | 17.32 | 10.18 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.04 | 0.00 |
June | 2.23 | 0.00 |
July | 2.66 | 0.00 |
August | 1.51 | 0.00 |
September | 1.28 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 7.72 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.66 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.06 | 0.00 |
July | 0.11 | 0.00 |
August | 0.00 | 0.00 |
September | 0.06 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.22 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.11 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 730.15 | 4.85 |
February | 663.70 | 4.84 |
March | 707.03 | 4.92 |
April | 685.88 | 4.88 |
May | 637.19 | 4.92 |
June | 529.52 | 4.48 |
July | 545.48 | 4.43 |
August | 530.71 | 4.44 |
September | 538.90 | 4.73 |
October | 677.66 | 4.98 |
November | 696.24 | 4.88 |
December | 727.94 | 4.86 |
Annual Sum or Average | 7670.39 | 4.79 |
Minimum of Months | 529.52 | 4.43 |
Maximum of Months | 730.15 | 4.98 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 82.58 | 40.53 |
February | 66.63 | 35.40 |
March | 34.41 | 71.29 |
April | 11.93 | 69.61 |
May | 36.88 | 66.46 |
June | 222.05 | 71.16 |
July | 247.41 | 68.56 |
August | 220.93 | 70.14 |
September | 187.51 | 71.68 |
October | 59.89 | 67.76 |
November | 81.84 | 46.22 |
December | 49.60 | 35.81 |
Annual Sum or Average | 1301.66 | 63.58 |
Minimum of Months | 11.93 | 35.40 |
Maximum of Months | 247.41 | 71.68 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.46 | 101.25 |
February | 0.24 | 114.54 |
March | 0.71 | 153.55 |
April | 0.49 | 251.89 |
May | 2.96 | 242.60 |
June | 19.07 | 327.67 |
July | 23.14 | 331.16 |
August | 22.15 | 337.47 |
September | 17.83 | 305.21 |
October | 1.68 | 145.78 |
November | 1.49 | 102.33 |
December | 0.69 | 116.70 |
Annual Sum or Average | 90.90 | 311.65 |
Minimum of Months | 0.24 | 101.25 |
Maximum of Months | 23.14 | 337.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.02 | 0.81 |
June | 0.03 | 0.65 |
July | 0.05 | 0.80 |
August | 0.07 | 0.73 |
September | 0.06 | 0.65 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.02 | 0.45 |
Annual Sum or Average | 0.24 | 0.70 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.07 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.06 | 0.65 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.06 | 0.65 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.06 | 0.65 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.06 | 1.16 |
June | 0.37 | 1.35 |
July | 0.33 | 1.32 |
August | 0.45 | 1.31 |
September | 0.17 | 1.10 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.38 | 1.29 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.45 | 1.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.02 | 0.81 |
June | 0.02 | 0.30 |
July | 0.03 | 0.80 |
August | 0.05 | 0.65 |
September | 0.20 | 0.60 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.02 | 0.45 |
Annual Sum or Average | 0.34 | 0.61 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.20 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.08 | 0.40 |
June | 0.54 | 0.72 |
July | 0.37 | 0.58 |
August | 0.34 | 0.48 |
September | 0.30 | 0.44 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.63 | 0.57 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.54 | 0.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.03 | 0.65 |
July | 0.05 | 0.80 |
August | 0.00 | 0.00 |
September | 0.06 | 0.65 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.14 | 0.70 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.06 | 0.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.02 | 1.16 |
July | 0.03 | 1.16 |
August | 0.00 | 0.00 |
September | 0.11 | 0.78 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 0.90 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.11 | 1.16 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.02 | 0.45 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.03 | 0.45 |
June | 0.03 | 0.65 |
July | 0.03 | 0.80 |
August | 0.08 | 0.65 |
September | 0.11 | 0.73 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.32 | 0.65 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.11 | 0.80 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 596.77 | 159.61 |
February | 523.98 | 161.23 |
March | 601.74 | 157.38 |
April | 598.08 | 153.09 |
May | 495.67 | 157.23 |
June | 355.21 | 125.39 |
July | 364.12 | 119.80 |
August | 343.49 | 122.32 |
September | 382.18 | 144.25 |
October | 562.07 | 159.35 |
November | 589.50 | 157.76 |
December | 523.93 | 168.56 |
Annual Sum or Average | 5936.73 | 151.62 |
Minimum of Months | 343.49 | 119.80 |
Maximum of Months | 601.74 | 168.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 690.94 | 147.30 |
February | 633.97 | 145.91 |
March | 652.00 | 150.72 |
April | 622.41 | 150.41 |
May | 501.29 | 157.78 |
June | 359.18 | 126.48 |
July | 370.16 | 120.68 |
August | 349.55 | 123.42 |
September | 389.48 | 144.77 |
October | 605.59 | 154.31 |
November | 658.26 | 148.14 |
December | 656.76 | 151.30 |
Annual Sum or Average | 6489.58 | 145.65 |
Minimum of Months | 349.55 | 120.68 |
Maximum of Months | 690.94 | 157.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 726.24 | 12.89 |
February | 662.06 | 12.83 |
March | 692.95 | 13.15 |
April | 672.21 | 13.04 |
May | 604.24 | 13.24 |
June | 496.41 | 11.92 |
July | 508.86 | 11.77 |
August | 491.82 | 11.87 |
September | 495.97 | 12.84 |
October | 658.33 | 13.37 |
November | 689.33 | 13.01 |
December | 722.68 | 12.93 |
Annual Sum or Average | 7421.09 | 12.79 |
Minimum of Months | 491.82 | 11.77 |
Maximum of Months | 726.24 | 13.37 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.06 | 0.00 |
February | 0.00 | 0.00 |
March | 0.06 | 0.00 |
April | 0.00 | 0.00 |
May | 0.07 | 0.00 |
June | 2.32 | 0.00 |
July | 3.44 | 0.00 |
August | 1.08 | 0.00 |
September | 0.98 | 0.00 |
October | 0.47 | 0.00 |
November | 0.32 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 8.80 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.44 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.155733E+11 | 0.00 | 0.554909E+10 | 0.607456E+11 | 0.00 | 0.00 |
February | 0.164115E+11 | 0.00 | 0.308469E+10 | 0.536129E+11 | 0.00 | 0.00 |
March | 0.838274E+10 | 0.00 | 0.175496E+11 | 0.591451E+11 | 0.00 | 0.00 |
April | 0.524693E+10 | 0.00 | 0.184775E+11 | 0.557701E+11 | 0.00 | 0.00 |
May | 0.457736E+09 | 0.00 | 0.836052E+11 | 0.597785E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.269794E+12 | 0.590400E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.314666E+12 | 0.611690E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.280424E+12 | 0.633699E+11 | 0.00 | 0.00 |
September | 51036249.43 | 0.00 | 0.196179E+12 | 0.628836E+11 | 0.00 | 0.00 |
October | 0.602816E+10 | 0.00 | 0.359123E+11 | 0.626655E+11 | 0.00 | 0.00 |
November | 0.795698E+10 | 0.00 | 0.116818E+11 | 0.598520E+11 | 0.00 | 0.00 |
December | 0.347120E+11 | 0.00 | 0.785529E+10 | 0.578750E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.948204E+11 | 0.00 | 0.124478E+13 | 0.715907E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.308469E+10 | 0.536129E+11 | 0.00 | 0.00 |
Maximum of Months | 0.347120E+11 | 0.00 | 0.314666E+12 | 0.633699E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.160126E+10 | 0.00 | 0.186069E+09 | 0.261252E+10 | 0.00 | 0.00 |
February | 0.172454E+10 | 0.00 | 0.116738E+09 | 0.235970E+10 | 0.00 | 0.00 |
March | 0.687791E+09 | 0.00 | 0.831179E+09 | 0.261252E+10 | 0.00 | 0.00 |
April | 0.314726E+09 | 0.00 | 0.978180E+09 | 0.252825E+10 | 0.00 | 0.00 |
May | 36619.47 | 0.00 | 0.480898E+10 | 0.261252E+10 | 0.00 | 0.00 |
June | 103452.22 | 0.00 | 0.165963E+11 | 0.252825E+10 | 0.00 | 0.00 |
July | 108726.14 | 0.00 | 0.201229E+11 | 0.261252E+10 | 0.00 | 0.00 |
August | 91356.03 | 0.00 | 0.174853E+11 | 0.261252E+10 | 0.00 | 0.00 |
September | 986526.90 | 0.00 | 0.111561E+11 | 0.252825E+10 | 0.00 | 0.00 |
October | 0.490817E+09 | 0.00 | 0.160868E+10 | 0.261252E+10 | 0.00 | 0.00 |
November | 0.803279E+09 | 0.00 | 0.463723E+09 | 0.252825E+10 | 0.00 | 0.00 |
December | 0.300106E+10 | 0.00 | 0.266625E+09 | 0.261252E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.862480E+10 | 0.00 | 0.746208E+11 | 0.307604E+11 | 0.00 | 0.00 |
Minimum of Months | 36619.47 | 0.00 | 0.116738E+09 | 0.235970E+10 | 0.00 | 0.00 |
Maximum of Months | 0.300106E+10 | 0.00 | 0.201229E+11 | 0.261252E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.607456E+11 | 0.554909E+10 | 0.155733E+11 | 0.544816E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.536129E+11 | 0.308469E+10 | 0.164115E+11 | 0.521692E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.591451E+11 | 0.175496E+11 | 0.838274E+10 | 0.411784E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.557701E+11 | 0.184775E+11 | 0.524693E+10 | 0.359162E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.597785E+11 | 0.836052E+11 | 0.457736E+09 | 0.141099E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.590400E+11 | 0.269794E+12 | 0.00 | 0.208007E+11 | 0.406095E+10 | 0.00 | 0.00 | 0.00 |
July | 0.611690E+11 | 0.314666E+12 | 0.00 | 0.199392E+11 | 0.375078E+10 | 0.00 | 0.00 | 0.00 |
August | 0.633699E+11 | 0.280424E+12 | 0.00 | 0.202300E+11 | 0.243896E+10 | 0.00 | 0.00 | 0.00 |
September | 0.628836E+11 | 0.196179E+12 | 51036249.43 | 0.621193E+11 | 0.188571E+09 | 0.00 | 0.00 | 0.00 |
October | 0.626655E+11 | 0.359123E+11 | 0.602816E+10 | 0.338282E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.598520E+11 | 0.116818E+11 | 0.795698E+10 | 0.466153E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.578750E+11 | 0.785529E+10 | 0.347120E+11 | 0.567787E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.715907E+12 | 0.124478E+13 | 0.948204E+11 | 0.347386E+13 | 0.104393E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.536129E+11 | 0.308469E+10 | 0.00 | 0.199392E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.633699E+11 | 0.314666E+12 | 0.347120E+11 | 0.567787E+12 | 0.406095E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261252E+10 | 0.186069E+09 | 0.160126E+10 | 0.473312E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235970E+10 | 0.116738E+09 | 0.172454E+10 | 0.452317E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261252E+10 | 0.831179E+09 | 0.687791E+09 | 0.366103E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252825E+10 | 0.978180E+09 | 0.314726E+09 | 0.320018E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261252E+10 | 0.480898E+10 | 36619.47 | 0.130652E+11 | 4268050.31 | 0.00 | 0.00 | 0.00 |
June | 0.252825E+10 | 0.165963E+11 | 103452.22 | 0.190039E+10 | 0.464446E+09 | 0.00 | 0.00 | 0.00 |
July | 0.261252E+10 | 0.201229E+11 | 108726.14 | 0.154884E+10 | 0.693373E+09 | 0.00 | 0.00 | 0.00 |
August | 0.261252E+10 | 0.174853E+11 | 91356.03 | 0.161913E+10 | 0.328839E+09 | 0.00 | 0.00 | 0.00 |
September | 0.252825E+10 | 0.111561E+11 | 986526.90 | 0.567254E+10 | 52439829.62 | 0.00 | 0.00 | 0.00 |
October | 0.261252E+10 | 0.160868E+10 | 0.490817E+09 | 0.301168E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252825E+10 | 0.463723E+09 | 0.803279E+09 | 0.407324E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261252E+10 | 0.266625E+09 | 0.300106E+10 | 0.506319E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307604E+11 | 0.746208E+11 | 0.862480E+10 | 0.306462E+12 | 0.154337E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.235970E+10 | 0.116738E+09 | 36619.47 | 0.154884E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261252E+10 | 0.201229E+11 | 0.300106E+10 | 0.506319E+11 | 0.693373E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.607456E+11 | 0.155733E+11 | 0.554909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.536129E+11 | 0.164115E+11 | 0.308469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.591451E+11 | 0.838274E+10 | 0.175496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.557701E+11 | 0.524693E+10 | 0.184775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.597785E+11 | 0.457736E+09 | 0.836052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.590400E+11 | 0.00 | 0.269794E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.611690E+11 | 0.00 | 0.314666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.633699E+11 | 0.00 | 0.280424E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.628836E+11 | 51036249.43 | 0.196179E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.626655E+11 | 0.602816E+10 | 0.359123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.598520E+11 | 0.795698E+10 | 0.116818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.578750E+11 | 0.347120E+11 | 0.785529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.715907E+12 | 0.948204E+11 | 0.124478E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.536129E+11 | 0.00 | 0.308469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.633699E+11 | 0.347120E+11 | 0.314666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.261252E+10 | 0.160126E+10 | 0.186069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235970E+10 | 0.172454E+10 | 0.116738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261252E+10 | 0.687791E+09 | 0.831179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.252825E+10 | 0.314726E+09 | 0.978180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261252E+10 | 36619.47 | 0.480898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252825E+10 | 103452.22 | 0.165963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.261252E+10 | 108726.14 | 0.201229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.261252E+10 | 91356.03 | 0.174853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252825E+10 | 986526.90 | 0.111561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261252E+10 | 0.490817E+09 | 0.160868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252825E+10 | 0.803279E+09 | 0.463723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261252E+10 | 0.300106E+10 | 0.266625E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307604E+11 | 0.862480E+10 | 0.746208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.235970E+10 | 36619.47 | 0.116738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261252E+10 | 0.300106E+10 | 0.201229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3106399.05 | 0.00 | 0.00 | 0.354590E+10 | 0.00 | 0.00 | 0.505669E+11 | 0.00 | 1.00 |
February | 0.00 | 0.00 | 0.00 | 0.247406E+10 | 0.00 | 0.00 | 0.463108E+11 | 0.00 | 1.00 |
March | 0.154344E+09 | 0.00 | 0.00 | 0.160399E+10 | 0.00 | 0.00 | 0.491600E+11 | 0.00 | 0.96 |
April | 35140427.99 | 0.00 | 0.00 | 0.149974E+10 | 0.00 | 0.00 | 0.473969E+11 | 0.00 | 0.97 |
May | 0.528791E+09 | 0.00 | 0.00 | 0.101431E+10 | 0.00 | 0.00 | 0.424746E+11 | 0.00 | 0.90 |
June | 0.200999E+09 | 28440764.68 | 0.00 | 0.472640E+09 | 527342.96 | 0.00 | 0.248524E+11 | 0.00 | 0.87 |
July | 0.108723E+09 | 0.113014E+09 | 0.00 | 0.530423E+09 | 11317040.10 | 0.00 | 0.224488E+11 | 0.00 | 0.88 |
August | 27193430.24 | 36862447.30 | 0.00 | 0.779659E+09 | 368974.00 | 0.00 | 0.281685E+11 | 0.00 | 0.99 |
September | 911691.01 | 0.00 | 0.00 | 0.208599E+10 | 0.00 | 0.00 | 0.359710E+11 | 0.00 | 1.08 |
October | 0.00 | 0.00 | 0.00 | 0.654024E+10 | 0.00 | 0.00 | 0.472748E+11 | 0.00 | 1.04 |
November | 0.00 | 0.00 | 0.00 | 0.775990E+10 | 0.00 | 0.00 | 0.450035E+11 | 0.00 | 1.02 |
December | 0.00 | 0.00 | 0.00 | 0.700850E+10 | 0.00 | 0.00 | 0.493326E+11 | 0.00 | 1.01 |
Annual Sum or Average | 0.105921E+10 | 0.178317E+09 | 0.00 | 0.353153E+11 | 12213357.07 | 0.00 | 0.488961E+12 | 0.00 | 0.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.472640E+09 | 0.00 | 0.00 | 0.224488E+11 | 0.00 | 0.87 |
Maximum of Months | 0.528791E+09 | 0.113014E+09 | 0.00 | 0.775990E+10 | 11317040.10 | 0.00 | 0.505669E+11 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112512E+10 | 0.00 | 0.00 | 0.154290E+09 | 0.00 | 0.239504E+09 | 0.267886E+10 | 0.00 | 1.45 |
February | 0.812857E+09 | 0.00 | 0.00 | 0.117636E+09 | 0.00 | 0.496728E+09 | 0.225908E+10 | 0.00 | 1.40 |
March | 0.101053E+10 | 0.00 | 0.00 | 83315666.62 | 0.00 | 0.391334E+09 | 0.238817E+10 | 0.00 | 1.39 |
April | 0.129199E+10 | 0.00 | 0.00 | 18294099.03 | 0.00 | 0.304136E+09 | 0.138113E+10 | 0.00 | 1.12 |
May | 0.782741E+09 | 0.00 | 0.00 | 29840015.23 | 0.00 | 0.00 | 0.245622E+10 | 0.00 | 1.37 |
June | 76068899.13 | 5893996.13 | 0.00 | 82536738.49 | 0.00 | 0.00 | 0.232572E+10 | 0.00 | 1.94 |
July | 54809076.86 | 24472010.48 | 0.00 | 97413099.63 | 0.00 | 0.00 | 0.212579E+10 | 0.00 | 1.96 |
August | 57311167.90 | 5918443.44 | 0.00 | 0.112627E+09 | 0.00 | 0.00 | 0.250687E+10 | 0.00 | 1.97 |
September | 0.169109E+09 | 0.00 | 0.00 | 0.129715E+09 | 0.00 | 0.00 | 0.309432E+10 | 0.00 | 1.97 |
October | 0.749985E+09 | 0.00 | 0.00 | 0.137299E+09 | 0.00 | 0.305330E+09 | 0.333589E+10 | 0.00 | 1.64 |
November | 0.887096E+09 | 0.00 | 0.00 | 0.159875E+09 | 0.00 | 0.217004E+09 | 0.307178E+10 | 0.00 | 1.55 |
December | 0.113658E+10 | 0.00 | 0.00 | 0.113706E+09 | 0.00 | 0.662255E+09 | 0.210028E+10 | 0.00 | 1.34 |
Annual Sum or Average | 0.815421E+10 | 36284450.05 | 0.00 | 0.123655E+10 | 0.00 | 0.261629E+10 | 0.297241E+11 | 0.00 | 1.59 |
Minimum of Months | 54809076.86 | 0.00 | 0.00 | 18294099.03 | 0.00 | 0.00 | 0.138113E+10 | 0.00 | 1.12 |
Maximum of Months | 0.129199E+10 | 24472010.48 | 0.00 | 0.159875E+09 | 0.00 | 0.662255E+09 | 0.333589E+10 | 0.00 | 1.97 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219758E+09 | 0.00 | 0.00 | 0.143526E+09 | 0.00 | 0.00 | 0.444999E+10 | 0.00 | 1.40 |
February | 0.428719E+09 | 0.00 | 0.00 | 0.113994E+09 | 0.00 | 0.00 | 0.357200E+10 | 0.00 | 1.32 |
March | 0.364158E+09 | 0.00 | 0.00 | 0.116047E+09 | 0.00 | 0.00 | 0.401213E+10 | 0.00 | 1.34 |
April | 0.343718E+09 | 0.00 | 0.00 | 90692145.36 | 0.00 | 0.00 | 0.375988E+10 | 0.00 | 1.29 |
May | 28876833.43 | 0.00 | 0.00 | 0.125687E+09 | 0.00 | 0.00 | 0.424065E+10 | 0.00 | 1.44 |
June | 1533380.33 | 4171514.60 | 0.00 | 94192050.75 | 3095.89 | 0.00 | 0.270569E+10 | 0.00 | 1.57 |
July | 2138984.62 | 14729894.49 | 0.00 | 95868390.77 | 416293.05 | 0.00 | 0.240073E+10 | 0.00 | 1.56 |
August | 2362829.49 | 4113117.62 | 0.00 | 96087058.18 | 39632.65 | 0.00 | 0.277072E+10 | 0.00 | 1.57 |
September | 5478520.29 | 0.00 | 0.00 | 0.114380E+09 | 0.00 | 0.00 | 0.340460E+10 | 0.00 | 1.57 |
October | 0.213192E+09 | 0.00 | 0.00 | 0.170856E+09 | 0.00 | 0.00 | 0.442159E+10 | 0.00 | 1.45 |
November | 0.217838E+09 | 0.00 | 0.00 | 0.166578E+09 | 0.00 | 0.00 | 0.438237E+10 | 0.00 | 1.43 |
December | 0.649240E+09 | 0.00 | 0.00 | 0.111270E+09 | 0.00 | 0.00 | 0.382983E+10 | 0.00 | 1.29 |
Annual Sum or Average | 0.247701E+10 | 23014526.71 | 0.00 | 0.143918E+10 | 459021.60 | 0.00 | 0.439502E+11 | 0.00 | 1.44 |
Minimum of Months | 1533380.33 | 0.00 | 0.00 | 90692145.36 | 0.00 | 0.00 | 0.240073E+10 | 0.00 | 1.29 |
Maximum of Months | 0.649240E+09 | 14729894.49 | 0.00 | 0.170856E+09 | 416293.05 | 0.00 | 0.444999E+10 | 0.00 | 1.57 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14945562.25 | 0.00 | 0.00 | 32570930.55 | 0.00 | 0.00 | 0.225616E+10 | 0.00 | 0.31 |
February | 20986838.37 | 0.00 | 0.00 | 24075156.51 | 0.00 | 0.00 | 0.168907E+10 | 0.00 | 0.26 |
March | 11674153.22 | 0.00 | 0.00 | 41344647.38 | 0.00 | 0.00 | 0.244518E+10 | 0.00 | 0.34 |
April | 8351181.11 | 0.00 | 0.00 | 35768880.19 | 0.00 | 0.00 | 0.245840E+10 | 0.00 | 0.35 |
May | 10713.91 | 0.00 | 0.00 | 66512767.44 | 0.00 | 0.00 | 0.369837E+10 | 0.00 | 0.58 |
June | 6799.58 | 4221463.03 | 0.00 | 75257283.69 | 0.00 | 0.00 | 0.242462E+10 | 0.00 | 0.69 |
July | 14450.43 | 14350988.08 | 0.00 | 86813300.23 | 260.49 | 0.00 | 0.216953E+10 | 0.00 | 0.69 |
August | 15411.83 | 4146343.92 | 0.00 | 71075631.84 | 0.00 | 0.00 | 0.241795E+10 | 0.00 | 0.67 |
September | 1360.81 | 0.00 | 0.00 | 60066262.76 | 0.00 | 0.00 | 0.300957E+10 | 0.00 | 0.65 |
October | 4932280.08 | 0.00 | 0.00 | 71871732.90 | 0.00 | 0.00 | 0.364973E+10 | 0.00 | 0.52 |
November | 7738365.32 | 0.00 | 0.00 | 53122509.26 | 0.00 | 0.00 | 0.302514E+10 | 0.00 | 0.43 |
December | 21964875.08 | 0.00 | 0.00 | 26258967.65 | 0.00 | 0.00 | 0.197573E+10 | 0.00 | 0.27 |
Annual Sum or Average | 90641991.98 | 22718795.03 | 0.00 | 0.644738E+09 | 260.49 | 0.00 | 0.312194E+11 | 0.00 | 0.48 |
Minimum of Months | 1360.81 | 0.00 | 0.00 | 24075156.51 | 0.00 | 0.00 | 0.168907E+10 | 0.00 | 0.26 |
Maximum of Months | 21964875.08 | 14350988.08 | 0.00 | 86813300.23 | 260.49 | 0.00 | 0.369837E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.176948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28297039.51 | 0.00 | 0.00 | 0.43 |
February | 0.160334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14179473.33 | 0.00 | 0.00 | 0.42 |
March | 0.173891E+10 | 0.00 | 0.00 | 97434.22 | 0.00 | 0.00 | 21464451.67 | 0.00 | 0.43 |
April | 0.168090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.159259E+10 | 0.00 | 0.00 | 205280.54 | 0.00 | 0.00 | 34234594.22 | 0.00 | 0.45 |
June | 0.803638E+09 | 1157168.25 | 0.00 | 15376058.90 | 513870.37 | 0.00 | 0.247863E+09 | 0.00 | 0.50 |
July | 0.653115E+09 | 886383.87 | 0.00 | 21890640.83 | 6546077.45 | 0.00 | 0.291539E+09 | 0.00 | 0.51 |
August | 0.934717E+09 | 1218536.44 | 0.00 | 9810574.00 | 567160.88 | 0.00 | 0.158831E+09 | 0.00 | 0.50 |
September | 0.121303E+10 | 0.00 | 0.00 | 2796559.45 | 0.00 | 0.00 | 84556159.59 | 0.00 | 0.48 |
October | 0.171380E+10 | 0.00 | 0.00 | 499786.04 | 0.00 | 0.00 | 69698089.11 | 0.00 | 0.44 |
November | 0.168942E+10 | 0.00 | 0.00 | 309116.16 | 0.00 | 0.00 | 59250720.79 | 0.00 | 0.43 |
December | 0.155800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304655E+09 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.169510E+11 | 3262088.56 | 0.00 | 50985450.14 | 7627108.70 | 0.347132E+09 | 0.967437E+09 | 0.00 | 0.45 |
Minimum of Months | 0.653115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.176948E+10 | 1218536.44 | 0.00 | 21890640.83 | 6546077.45 | 0.304655E+09 | 0.291539E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.132013E+10 | 0.00 | 0.00 | 0.787263E+11 | 0.00 | 23.22 |
February | 0.00 | 0.00 | 0.00 | 0.118930E+10 | 0.00 | 0.00 | 0.708543E+11 | 0.00 | 23.11 |
March | 0.00 | 0.00 | 0.00 | 0.130955E+10 | 0.00 | 0.00 | 0.759321E+11 | 0.00 | 23.06 |
April | 0.00 | 0.00 | 0.00 | 0.124425E+10 | 0.00 | 0.00 | 0.725164E+11 | 0.00 | 23.00 |
May | 0.00 | 0.00 | 0.00 | 0.119365E+10 | 0.00 | 0.00 | 0.672172E+11 | 0.00 | 22.56 |
June | 0.00 | 60618420.03 | 0.00 | 0.932918E+09 | 0.00 | 0.00 | 0.358951E+11 | 0.00 | 21.66 |
July | 0.00 | 0.243197E+09 | 0.00 | 0.954084E+09 | 0.00 | 0.00 | 0.315671E+11 | 0.00 | 21.41 |
August | 0.00 | 58511948.30 | 0.00 | 0.966493E+09 | 0.00 | 0.00 | 0.371729E+11 | 0.00 | 21.67 |
September | 0.00 | 0.00 | 0.00 | 0.978508E+09 | 0.00 | 0.00 | 0.487157E+11 | 0.00 | 21.97 |
October | 0.00 | 0.00 | 0.00 | 0.130433E+10 | 0.00 | 0.00 | 0.757234E+11 | 0.00 | 22.82 |
November | 0.00 | 0.00 | 0.00 | 0.129185E+10 | 0.00 | 0.00 | 0.760737E+11 | 0.00 | 23.13 |
December | 0.00 | 0.00 | 0.00 | 0.129437E+10 | 0.00 | 0.00 | 0.808335E+11 | 0.00 | 22.85 |
Annual Sum or Average | 0.00 | 0.362327E+09 | 0.00 | 0.139794E+11 | 0.00 | 0.00 | 0.751228E+12 | 0.00 | 22.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.932918E+09 | 0.00 | 0.00 | 0.315671E+11 | 0.00 | 21.41 |
Maximum of Months | 0.00 | 0.243197E+09 | 0.00 | 0.132013E+10 | 0.00 | 0.00 | 0.808335E+11 | 0.00 | 23.22 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.283807E+10 | 0.00 | 0.00 | 0.801381E+09 | 0.00 | 23880472.14 | 0.251079E+11 | 0.00 | 3.46 |
February | 0.396350E+10 | 0.00 | 0.00 | 0.641139E+09 | 0.00 | 0.114416E+09 | 0.202941E+11 | 0.00 | 3.32 |
March | 0.448967E+10 | 0.00 | 0.00 | 0.535339E+09 | 0.00 | 0.00 | 0.221362E+11 | 0.00 | 3.37 |
April | 0.529405E+10 | 0.00 | 0.00 | 0.293726E+09 | 0.00 | 0.00 | 0.192131E+11 | 0.00 | 3.18 |
May | 0.142323E+10 | 0.00 | 0.00 | 0.388838E+09 | 0.00 | 0.00 | 0.233822E+11 | 0.00 | 3.44 |
June | 0.447012E+09 | 25244622.91 | 0.00 | 0.394124E+09 | 91467.64 | 0.00 | 0.151535E+11 | 0.00 | 3.73 |
July | 0.328717E+09 | 92811166.32 | 0.00 | 0.427796E+09 | 11970266.92 | 0.00 | 0.136685E+11 | 0.00 | 3.74 |
August | 0.495635E+09 | 25133872.04 | 0.00 | 0.475079E+09 | 265940.37 | 0.00 | 0.156557E+11 | 0.00 | 3.79 |
September | 0.451451E+09 | 0.00 | 0.00 | 0.587895E+09 | 0.00 | 0.00 | 0.195737E+11 | 0.00 | 3.81 |
October | 0.325900E+10 | 0.00 | 0.00 | 0.736690E+09 | 0.00 | 0.106898E+09 | 0.242635E+11 | 0.00 | 3.54 |
November | 0.273019E+10 | 0.00 | 0.00 | 0.822062E+09 | 0.00 | 1051141.06 | 0.244612E+11 | 0.00 | 3.48 |
December | 0.552785E+10 | 0.00 | 0.00 | 0.625950E+09 | 0.00 | 0.393721E+09 | 0.217833E+11 | 0.00 | 3.29 |
Annual Sum or Average | 0.312484E+11 | 0.143190E+09 | 0.00 | 0.673002E+10 | 12327674.93 | 0.639966E+09 | 0.244693E+12 | 0.00 | 3.51 |
Minimum of Months | 0.328717E+09 | 0.00 | 0.00 | 0.293726E+09 | 0.00 | 0.00 | 0.136685E+11 | 0.00 | 3.18 |
Maximum of Months | 0.552785E+10 | 92811166.32 | 0.00 | 0.822062E+09 | 11970266.92 | 0.393721E+09 | 0.251079E+11 | 0.00 | 3.81 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189890E+10 | 0.00 | 0.00 | 0.412410E+10 | 0.00 | 0.00 | 0.941495E+11 | 0.00 | 1.74 |
February | 0.318102E+10 | 0.00 | 0.00 | 0.330377E+10 | 0.00 | 0.00 | 0.815251E+11 | 0.00 | 1.68 |
March | 0.264037E+10 | 0.00 | 0.00 | 0.331505E+10 | 0.00 | 0.00 | 0.896737E+11 | 0.00 | 1.70 |
April | 0.226453E+10 | 0.00 | 0.00 | 0.271415E+10 | 0.00 | 0.00 | 0.847572E+11 | 0.00 | 1.66 |
May | 84697213.49 | 0.00 | 0.00 | 0.320663E+10 | 0.00 | 0.00 | 0.848573E+11 | 0.00 | 1.73 |
June | 31663364.48 | 82928622.74 | 0.00 | 0.205835E+10 | 0.00 | 0.00 | 0.542385E+11 | 0.00 | 1.86 |
July | 42605748.49 | 0.308909E+09 | 0.00 | 0.211064E+10 | 9316098.58 | 0.00 | 0.486518E+11 | 0.00 | 1.86 |
August | 38040139.94 | 81559693.35 | 0.00 | 0.212933E+10 | 818646.97 | 0.00 | 0.559354E+11 | 0.00 | 1.88 |
September | 53955093.98 | 0.00 | 0.00 | 0.271310E+10 | 0.00 | 0.00 | 0.679490E+11 | 0.00 | 1.87 |
October | 0.272559E+10 | 0.00 | 0.00 | 0.425122E+10 | 0.00 | 0.00 | 0.911048E+11 | 0.00 | 1.76 |
November | 0.102595E+10 | 0.00 | 0.00 | 0.447298E+10 | 0.00 | 0.00 | 0.921111E+11 | 0.00 | 1.75 |
December | 0.626003E+10 | 0.00 | 0.00 | 0.343639E+10 | 0.00 | 0.00 | 0.884506E+11 | 0.00 | 1.65 |
Annual Sum or Average | 0.202473E+11 | 0.473397E+09 | 0.00 | 0.378357E+11 | 10134745.55 | 0.00 | 0.933404E+12 | 0.00 | 1.76 |
Minimum of Months | 31663364.48 | 0.00 | 0.00 | 0.205835E+10 | 0.00 | 0.00 | 0.486518E+11 | 0.00 | 1.65 |
Maximum of Months | 0.626003E+10 | 0.308909E+09 | 0.00 | 0.447298E+10 | 9316098.58 | 0.00 | 0.941495E+11 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 55239058.22 | 0.00 | 0.00 | 11106015.10 | 0.00 | 0.103877E+10 | 0.330851E+09 | 0.00 | 0.34 |
February | 46801164.47 | 0.00 | 0.00 | 12154792.22 | 0.00 | 0.950451E+09 | 0.294226E+09 | 0.00 | 0.34 |
March | 40512702.30 | 0.00 | 0.00 | 25739071.06 | 0.00 | 0.816953E+09 | 0.512044E+09 | 0.00 | 0.34 |
April | 82581229.78 | 0.00 | 0.00 | 16408176.13 | 0.00 | 0.793701E+09 | 0.418894E+09 | 0.00 | 0.34 |
May | 63291247.09 | 0.00 | 0.00 | 44169081.18 | 0.00 | 0.201514E+09 | 0.896620E+09 | 0.00 | 0.34 |
June | 940397.21 | 2378878.88 | 0.00 | 79702488.08 | 4741.55 | 513019.17 | 0.569287E+09 | 0.00 | 0.34 |
July | 0.00 | 10559489.60 | 0.00 | 72252182.56 | 642293.51 | 376832.35 | 0.462842E+09 | 0.00 | 0.34 |
August | 0.00 | 16919442.78 | 0.00 | 77394775.40 | 0.00 | 964947.70 | 0.529948E+09 | 0.00 | 0.34 |
September | 6143491.15 | 55226.02 | 0.00 | 67487619.81 | 0.00 | 59326266.89 | 0.776551E+09 | 0.00 | 0.34 |
October | 23198517.69 | 0.00 | 0.00 | 34450710.81 | 0.00 | 0.595197E+09 | 0.707279E+09 | 0.00 | 0.34 |
November | 39786232.55 | 0.00 | 0.00 | 15636452.89 | 0.00 | 0.848614E+09 | 0.446499E+09 | 0.00 | 0.34 |
December | 46340683.45 | 0.00 | 0.00 | 6660325.62 | 0.00 | 0.122179E+10 | 0.229584E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.404835E+09 | 29913037.28 | 0.00 | 0.463162E+09 | 647035.06 | 0.652817E+10 | 0.617462E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6660325.62 | 0.00 | 376832.35 | 0.229584E+09 | 0.00 | 0.34 |
Maximum of Months | 82581229.78 | 16919442.78 | 0.00 | 79702488.08 | 642293.51 | 0.122179E+10 | 0.896620E+09 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 67919790.63 | 0.00 | 0.00 | 2335111.87 | 0.00 | 0.127664E+10 | 89073853.45 | 0.00 | 0.34 |
February | 51392879.43 | 0.00 | 0.00 | 3883685.34 | 0.00 | 0.113574E+10 | 0.112620E+09 | 0.00 | 0.34 |
March | 0.100108E+09 | 0.00 | 0.00 | 12665816.68 | 0.00 | 0.926758E+09 | 0.355717E+09 | 0.00 | 0.34 |
April | 0.105183E+09 | 0.00 | 0.00 | 10681259.05 | 0.00 | 0.849199E+09 | 0.346520E+09 | 0.00 | 0.34 |
May | 0.176506E+09 | 0.00 | 0.00 | 29849917.36 | 0.00 | 0.188967E+09 | 0.810271E+09 | 0.00 | 0.34 |
June | 0.121372E+09 | 2186010.11 | 0.00 | 64474213.77 | 197610.32 | 130064.92 | 0.464466E+09 | 0.00 | 0.34 |
July | 0.128311E+09 | 9009402.08 | 630.60 | 55074126.32 | 2191743.61 | 212039.37 | 0.351874E+09 | 6.82 | 0.34 |
August | 0.139971E+09 | 16196724.41 | 0.00 | 55483310.83 | 722718.37 | 673466.03 | 0.412180E+09 | 0.00 | 0.34 |
September | 0.168459E+09 | 53419.59 | 0.00 | 42372171.50 | 1806.44 | 70026519.32 | 0.628651E+09 | 0.00 | 0.34 |
October | 0.121173E+09 | 0.00 | 0.00 | 14101338.88 | 0.00 | 0.771270E+09 | 0.453581E+09 | 0.00 | 0.34 |
November | 74494752.18 | 0.00 | 0.00 | 3627672.13 | 0.00 | 0.112936E+10 | 0.143050E+09 | 0.00 | 0.34 |
December | 51645543.60 | 0.00 | 0.00 | 824348.84 | 0.00 | 0.140073E+10 | 51169943.09 | 0.00 | 0.34 |
Annual Sum or Average | 0.130654E+10 | 27445556.18 | 630.60 | 0.295373E+09 | 3113878.74 | 0.774971E+10 | 0.421917E+10 | 6.82 | 0.34 |
Minimum of Months | 51392879.43 | 0.00 | 0.00 | 824348.84 | 0.00 | 130064.92 | 51169943.09 | 0.00 | 0.34 |
Maximum of Months | 0.176506E+09 | 16196724.41 | 630.60 | 64474213.77 | 2191743.61 | 0.140073E+10 | 0.810271E+09 | 6.82 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.458310E+09 | 0.00 | 0.00 | 48307119.69 | 0.00 | 0.00 | 0.147912E+10 | 0.00 | 0.02 |
February | 0.561795E+09 | 0.00 | 0.00 | 23764128.41 | 0.00 | 0.00 | 0.104732E+10 | 0.00 | 0.02 |
March | 0.886290E+09 | 0.00 | 0.00 | 18479783.81 | 0.00 | 0.00 | 0.881849E+09 | 0.00 | 0.02 |
April | 0.148812E+10 | 0.00 | 0.00 | 1198576.85 | 0.00 | 0.00 | 0.172783E+09 | 0.00 | 0.02 |
May | 0.135162E+10 | 0.00 | 0.00 | 5104659.58 | 0.00 | 0.00 | 0.372397E+09 | 0.00 | 0.02 |
June | 42762436.28 | 0.00 | 0.00 | 26606808.33 | 0.00 | 0.00 | 0.455944E+09 | 0.00 | 0.02 |
July | 7900836.98 | 9076194.07 | 0.00 | 29084199.39 | 0.00 | 0.00 | 0.355857E+09 | 0.00 | 0.02 |
August | 0.00 | 11321341.32 | 0.00 | 32481166.07 | 0.00 | 0.00 | 0.428434E+09 | 0.00 | 0.02 |
September | 0.134128E+09 | 0.00 | 0.00 | 40869050.55 | 0.00 | 0.00 | 0.798984E+09 | 0.00 | 0.02 |
October | 0.531866E+09 | 0.00 | 0.00 | 36277567.18 | 0.00 | 0.00 | 0.139518E+10 | 0.00 | 0.02 |
November | 0.504810E+09 | 0.00 | 0.00 | 32199486.60 | 0.00 | 0.00 | 0.132372E+10 | 0.00 | 0.02 |
December | 0.712601E+09 | 0.00 | 0.00 | 26704559.90 | 0.00 | 0.00 | 0.111331E+10 | 0.00 | 0.02 |
Annual Sum or Average | 0.668021E+10 | 20397535.39 | 0.00 | 0.321077E+09 | 0.00 | 0.00 | 0.982490E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1198576.85 | 0.00 | 0.00 | 0.172783E+09 | 0.00 | 0.02 |
Maximum of Months | 0.148812E+10 | 11321341.32 | 0.00 | 48307119.69 | 0.00 | 0.00 | 0.147912E+10 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107248E+10 | 0.00 | 0.00 | 61184677.09 | 0.00 | 0.110687E+11 | 0.726580E+10 | 0.00 | 0.39 |
February | 0.104316E+10 | 0.00 | 0.00 | 50587170.69 | 0.00 | 0.112410E+11 | 0.533936E+10 | 0.00 | 0.39 |
March | 0.151697E+10 | 0.00 | 0.00 | 0.167033E+09 | 0.00 | 0.625158E+10 | 0.109806E+11 | 0.00 | 0.39 |
April | 0.154293E+10 | 0.00 | 0.00 | 0.223279E+09 | 0.00 | 0.321651E+10 | 0.127992E+11 | 0.00 | 0.39 |
May | 0.245245E+10 | 0.00 | 0.00 | 0.528829E+09 | 0.00 | 3453388.86 | 0.133602E+11 | 0.00 | 0.38 |
June | 0.178930E+10 | 25376467.55 | 0.00 | 0.837144E+09 | 6939685.27 | 0.00 | 0.619199E+10 | 0.00 | 0.38 |
July | 0.185335E+10 | 0.107350E+09 | 0.00 | 0.740907E+09 | 44519137.15 | 10102.41 | 0.466543E+10 | 0.00 | 0.38 |
August | 0.212997E+10 | 0.219317E+09 | 0.00 | 0.626754E+09 | 10069603.53 | 1583365.02 | 0.548888E+10 | 0.00 | 0.38 |
September | 0.242098E+10 | 724240.95 | 0.00 | 0.537971E+09 | 24490.94 | 3395595.97 | 0.936840E+10 | 0.00 | 0.38 |
October | 0.180040E+10 | 0.00 | 0.00 | 0.242638E+09 | 0.00 | 0.291086E+10 | 0.134861E+11 | 0.00 | 0.38 |
November | 0.118384E+10 | 0.00 | 0.00 | 94073283.67 | 0.00 | 0.834748E+10 | 0.868463E+10 | 0.00 | 0.39 |
December | 0.942875E+09 | 0.00 | 0.00 | 46562174.81 | 0.00 | 0.133343E+11 | 0.607198E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.197487E+11 | 0.352768E+09 | 0.00 | 0.415696E+10 | 61552916.89 | 0.563789E+11 | 0.103703E+12 | 0.00 | 0.39 |
Minimum of Months | 0.942875E+09 | 0.00 | 0.00 | 46562174.81 | 0.00 | 0.00 | 0.466543E+10 | 0.00 | 0.38 |
Maximum of Months | 0.245245E+10 | 0.219317E+09 | 0.00 | 0.837144E+09 | 44519137.15 | 0.133343E+11 | 0.134861E+11 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 51702393.94 | 0.00 | 0.00 | 13833275.20 | 0.00 | 0.105510E+10 | 0.315324E+09 | 0.00 | 0.34 |
February | 35660425.76 | 0.00 | 0.00 | 16940285.35 | 0.00 | 0.923156E+09 | 0.327876E+09 | 0.00 | 0.34 |
March | 31945708.58 | 0.00 | 0.00 | 29043982.36 | 0.00 | 0.797176E+09 | 0.537083E+09 | 0.00 | 0.34 |
April | 65956265.18 | 0.00 | 0.00 | 24361555.21 | 0.00 | 0.765577E+09 | 0.455689E+09 | 0.00 | 0.34 |
May | 45677748.16 | 0.00 | 0.00 | 51545709.63 | 0.00 | 0.177635E+09 | 0.930735E+09 | 0.00 | 0.34 |
June | 0.00 | 2383620.43 | 0.00 | 86409481.10 | 0.00 | 88431.96 | 0.563945E+09 | 0.00 | 0.34 |
July | 0.00 | 10576237.24 | 0.00 | 77028006.36 | 625545.87 | 44592.92 | 0.458398E+09 | 0.00 | 0.34 |
August | 0.00 | 16919442.78 | 0.00 | 84341678.22 | 0.00 | 130343.96 | 0.523836E+09 | 0.00 | 0.34 |
September | 6093339.80 | 55226.02 | 0.00 | 74114506.35 | 0.00 | 54079529.77 | 0.775221E+09 | 0.00 | 0.34 |
October | 18424098.73 | 0.00 | 0.00 | 36104134.47 | 0.00 | 0.638870E+09 | 0.666728E+09 | 0.00 | 0.34 |
November | 39900964.93 | 0.00 | 0.00 | 17098356.68 | 0.00 | 0.871333E+09 | 0.422204E+09 | 0.00 | 0.34 |
December | 42467163.91 | 0.00 | 0.00 | 9123904.38 | 0.00 | 0.122250E+10 | 0.230284E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.337828E+09 | 29934526.47 | 0.00 | 0.519945E+09 | 625545.87 | 0.650569E+10 | 0.620732E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 9123904.38 | 0.00 | 44592.92 | 0.230284E+09 | 0.00 | 0.34 |
Maximum of Months | 65956265.18 | 16919442.78 | 0.00 | 86409481.10 | 625545.87 | 0.122250E+10 | 0.930735E+09 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 71620790.71 | 0.00 | 0.00 | 2800816.38 | 0.00 | 0.124925E+10 | 0.112294E+09 | 0.00 | 0.34 |
February | 54035307.60 | 0.00 | 0.00 | 5846355.67 | 0.00 | 0.109104E+10 | 0.152710E+09 | 0.00 | 0.34 |
March | 96903965.53 | 0.00 | 0.00 | 16209293.39 | 0.00 | 0.903767E+09 | 0.378368E+09 | 0.00 | 0.34 |
April | 0.100205E+09 | 0.00 | 0.00 | 18610731.70 | 0.00 | 0.820716E+09 | 0.372053E+09 | 0.00 | 0.34 |
May | 0.161935E+09 | 0.00 | 0.00 | 39648392.18 | 0.00 | 0.181833E+09 | 0.822178E+09 | 0.00 | 0.34 |
June | 0.120821E+09 | 2186010.11 | 0.00 | 71092488.38 | 197610.32 | 0.00 | 0.458530E+09 | 0.00 | 0.34 |
July | 0.128311E+09 | 9525072.76 | 0.00 | 58904347.67 | 1676710.35 | 26364.88 | 0.348229E+09 | 0.00 | 0.34 |
August | 0.136646E+09 | 16196724.41 | 0.00 | 63468924.19 | 722718.37 | 140778.25 | 0.408052E+09 | 0.00 | 0.34 |
September | 0.161527E+09 | 53419.59 | 0.00 | 50426038.93 | 1806.44 | 63873601.58 | 0.633682E+09 | 0.00 | 0.34 |
October | 0.119829E+09 | 0.00 | 0.00 | 16743121.83 | 0.00 | 0.768220E+09 | 0.455334E+09 | 0.00 | 0.34 |
November | 75796330.03 | 0.00 | 0.00 | 4705531.62 | 0.00 | 0.110859E+10 | 0.161448E+09 | 0.00 | 0.34 |
December | 52099567.76 | 0.00 | 0.00 | 1444933.53 | 0.00 | 0.139031E+10 | 60517577.88 | 0.00 | 0.34 |
Annual Sum or Average | 0.127973E+10 | 27961226.87 | 0.00 | 0.349901E+09 | 2598845.47 | 0.757776E+10 | 0.436340E+10 | 0.00 | 0.34 |
Minimum of Months | 52099567.76 | 0.00 | 0.00 | 1444933.53 | 0.00 | 0.00 | 60517577.88 | 0.00 | 0.34 |
Maximum of Months | 0.161935E+09 | 16196724.41 | 0.00 | 71092488.38 | 1676710.35 | 0.139031E+10 | 0.822178E+09 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.773484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705352E+10 | 0.00 | 0.00 | 0.28 |
February | 0.613369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717187E+10 | 0.00 | 0.00 | 0.27 |
March | 0.776468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670259E+10 | 0.00 | 0.00 | 0.28 |
April | 0.727610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655085E+10 | 0.00 | 0.00 | 0.28 |
May | 0.126233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735856E+09 | 0.00 | 0.00 | 0.29 |
June | 0.857947E+10 | 0.00 | 0.00 | 0.00 | 12400258.58 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.771430E+10 | 0.00 | 0.00 | 0.00 | 59874648.87 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.894310E+10 | 0.00 | 0.00 | 0.00 | 13231910.14 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.106550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
October | 0.112689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336851E+10 | 0.00 | 0.00 | 0.28 |
November | 0.847319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587588E+10 | 0.00 | 0.00 | 0.28 |
December | 0.489843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104236E+11 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.102065E+12 | 0.00 | 0.00 | 0.00 | 85506817.59 | 0.478827E+11 | 0.00 | 0.00 | 0.29 |
Minimum of Months | 0.489843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.126233E+11 | 0.00 | 0.00 | 0.00 | 59874648.87 | 0.104236E+11 | 0.00 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13788074.53 | 0.00 | 0.00 | 2572692.95 | 0.00 | 0.283281E+09 | 59349521.43 | 0.00 | 0.34 |
February | 11164041.56 | 0.00 | 0.00 | 3030092.58 | 0.00 | 0.255419E+09 | 56294801.80 | 0.00 | 0.34 |
March | 8886479.74 | 0.00 | 0.00 | 6659518.74 | 0.00 | 0.226536E+09 | 0.106730E+09 | 0.00 | 0.34 |
April | 16756701.79 | 0.00 | 0.00 | 4554478.59 | 0.00 | 0.214602E+09 | 91982764.00 | 0.00 | 0.34 |
May | 12740718.71 | 0.00 | 0.00 | 11853786.16 | 0.00 | 72443145.05 | 0.204361E+09 | 0.00 | 0.34 |
June | 0.00 | 595905.11 | 0.00 | 20965569.03 | 0.00 | 374232.79 | 0.141271E+09 | 0.00 | 0.34 |
July | 0.00 | 2670871.35 | 0.00 | 18257284.63 | 129574.39 | 91136.90 | 0.115519E+09 | 0.00 | 0.34 |
August | 0.00 | 4229860.69 | 0.00 | 20228907.99 | 0.00 | 653335.89 | 0.131195E+09 | 0.00 | 0.34 |
September | 1535872.79 | 13806.51 | 0.00 | 16908285.85 | 0.00 | 21893844.49 | 0.187039E+09 | 0.00 | 0.34 |
October | 5291116.84 | 0.00 | 0.00 | 8529312.27 | 0.00 | 0.185408E+09 | 0.140803E+09 | 0.00 | 0.34 |
November | 8479105.12 | 0.00 | 0.00 | 3710586.91 | 0.00 | 0.242623E+09 | 82821084.12 | 0.00 | 0.34 |
December | 9900438.77 | 0.00 | 0.00 | 1454832.42 | 0.00 | 0.320357E+09 | 44381460.59 | 0.00 | 0.34 |
Annual Sum or Average | 88542549.85 | 7510443.66 | 0.00 | 0.118725E+09 | 129574.39 | 0.182368E+10 | 0.136175E+10 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1454832.42 | 0.00 | 91136.90 | 44381460.59 | 0.00 | 0.34 |
Maximum of Months | 16756701.79 | 4229860.69 | 0.00 | 20965569.03 | 129574.39 | 0.320357E+09 | 0.204361E+09 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13643903.30 | 0.00 | 0.00 | 536955.38 | 0.00 | 0.330683E+09 | 14127550.53 | 0.00 | 0.34 |
February | 12061019.45 | 0.00 | 0.00 | 970647.10 | 0.00 | 0.293624E+09 | 19252912.57 | 0.00 | 0.34 |
March | 23650869.45 | 0.00 | 0.00 | 3310342.74 | 0.00 | 0.247935E+09 | 73916009.32 | 0.00 | 0.34 |
April | 24940714.53 | 0.00 | 0.00 | 3020121.28 | 0.00 | 0.224659E+09 | 75276422.96 | 0.00 | 0.34 |
May | 41700003.20 | 0.00 | 0.00 | 8186080.71 | 0.00 | 65553226.90 | 0.185959E+09 | 0.00 | 0.34 |
June | 30205144.32 | 546502.53 | 0.00 | 17512264.96 | 49402.58 | 48074.79 | 0.114845E+09 | 0.00 | 0.34 |
July | 32077698.73 | 2418766.63 | 0.00 | 14303110.04 | 381679.12 | 48530.62 | 87438370.82 | 0.00 | 0.34 |
August | 34161571.43 | 4049181.10 | 0.00 | 14761591.36 | 180679.59 | 251302.59 | 0.102902E+09 | 0.00 | 0.34 |
September | 40786364.55 | 13354.90 | 0.00 | 10917260.63 | 451.61 | 21427124.61 | 0.154246E+09 | 0.00 | 0.34 |
October | 30098098.45 | 0.00 | 0.00 | 3349137.18 | 0.00 | 0.217703E+09 | 88881378.08 | 0.00 | 0.34 |
November | 17087703.82 | 0.00 | 0.00 | 859762.06 | 0.00 | 0.292168E+09 | 27518706.51 | 0.00 | 0.34 |
December | 10345539.86 | 0.00 | 0.00 | 195334.91 | 0.00 | 0.358755E+09 | 6797431.81 | 0.00 | 0.34 |
Annual Sum or Average | 0.310759E+09 | 7027805.15 | 0.00 | 77922608.34 | 612212.90 | 0.205285E+10 | 0.951162E+09 | 0.00 | 0.34 |
Minimum of Months | 10345539.86 | 0.00 | 0.00 | 195334.91 | 0.00 | 48074.79 | 6797431.81 | 0.00 | 0.34 |
Maximum of Months | 41700003.20 | 4049181.10 | 0.00 | 17512264.96 | 381679.12 | 0.358755E+09 | 0.185959E+09 | 0.00 | 0.34 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13587247.67 | 0.00 | 0.00 | 0.129526E+09 | 0.00 | 0.991736E+09 | 0.117060E+10 | 0.00 | 0.39 |
February | 7173124.61 | 0.00 | 0.00 | 79893686.08 | 0.00 | 0.109877E+10 | 0.907151E+09 | 0.00 | 0.39 |
March | 29059665.61 | 0.00 | 0.00 | 65297526.24 | 0.00 | 0.103969E+10 | 0.110603E+10 | 0.00 | 0.39 |
April | 88117176.73 | 0.00 | 0.00 | 30296402.17 | 0.00 | 0.103329E+10 | 0.954048E+09 | 0.00 | 0.39 |
May | 76702560.27 | 0.00 | 0.00 | 67970603.60 | 0.00 | 0.222137E+09 | 0.156878E+10 | 0.00 | 0.38 |
June | 0.00 | 3826912.83 | 0.00 | 0.111628E+09 | 0.00 | 2055512.35 | 0.930606E+09 | 0.00 | 0.38 |
July | 0.00 | 16980194.31 | 0.00 | 0.105531E+09 | 1004316.59 | 185850.28 | 0.753984E+09 | 0.00 | 0.38 |
August | 0.00 | 27164238.05 | 0.00 | 0.121292E+09 | 0.00 | 111519.36 | 0.855237E+09 | 0.00 | 0.38 |
September | 7334711.13 | 88665.62 | 0.00 | 0.125849E+09 | 0.00 | 58937544.42 | 0.126810E+10 | 0.00 | 0.38 |
October | 15070605.44 | 0.00 | 0.00 | 0.106507E+09 | 0.00 | 0.648541E+09 | 0.141357E+10 | 0.00 | 0.39 |
November | 18069506.16 | 0.00 | 0.00 | 0.137536E+09 | 0.00 | 0.809148E+09 | 0.120354E+10 | 0.00 | 0.39 |
December | 36925335.49 | 0.00 | 0.00 | 0.102190E+09 | 0.00 | 0.136166E+10 | 0.914505E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.292040E+09 | 48060010.82 | 0.00 | 0.118352E+10 | 1004316.59 | 0.726627E+10 | 0.130461E+11 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 30296402.17 | 0.00 | 111519.36 | 0.753984E+09 | 0.00 | 0.38 |
Maximum of Months | 88117176.73 | 27164238.05 | 0.00 | 0.137536E+09 | 1004316.59 | 0.136166E+10 | 0.156878E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 67959546.01 | 0.00 | 0.00 | 0.136790E+10 | 0.00 | 0.00 | 0.497912E+11 | 0.00 | 4.55 |
February | 10949721.12 | 0.00 | 0.00 | 0.124106E+10 | 0.00 | 0.00 | 0.448912E+11 | 0.00 | 4.52 |
March | 17442958.47 | 0.00 | 0.00 | 0.151692E+10 | 0.00 | 0.00 | 0.487475E+11 | 0.00 | 4.62 |
April | 0.00 | 0.00 | 0.00 | 0.155029E+10 | 0.00 | 0.00 | 0.465442E+11 | 0.00 | 4.62 |
May | 0.00 | 0.00 | 0.00 | 0.164808E+10 | 0.00 | 0.00 | 0.446539E+11 | 0.00 | 4.78 |
June | 0.00 | 43236464.26 | 0.00 | 0.123119E+10 | 0.00 | 0.00 | 0.281374E+11 | 0.00 | 5.06 |
July | 0.00 | 0.197838E+09 | 0.00 | 0.125256E+10 | 0.00 | 0.00 | 0.250847E+11 | 0.00 | 5.05 |
August | 0.00 | 45408218.20 | 0.00 | 0.120794E+10 | 0.00 | 0.00 | 0.291457E+11 | 0.00 | 5.08 |
September | 25679185.17 | 0.00 | 0.00 | 0.123085E+10 | 0.00 | 0.00 | 0.349706E+11 | 0.00 | 4.95 |
October | 70225583.76 | 0.00 | 0.00 | 0.156564E+10 | 0.00 | 0.00 | 0.487062E+11 | 0.00 | 4.63 |
November | 63630252.16 | 0.00 | 0.00 | 0.144838E+10 | 0.00 | 0.00 | 0.481854E+11 | 0.00 | 4.56 |
December | 0.137290E+10 | 0.00 | 0.00 | 0.121736E+10 | 0.00 | 0.00 | 0.494488E+11 | 0.00 | 4.44 |
Annual Sum or Average | 0.162879E+10 | 0.286483E+09 | 0.00 | 0.164782E+11 | 0.00 | 0.00 | 0.498307E+12 | 0.00 | 4.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120794E+10 | 0.00 | 0.00 | 0.250847E+11 | 0.00 | 4.44 |
Maximum of Months | 0.137290E+10 | 0.197838E+09 | 0.00 | 0.164808E+10 | 0.00 | 0.00 | 0.497912E+11 | 0.00 | 5.08 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7668190.09 | 0.00 | 0.00 | 0.178530E+10 | 0.00 | 0.00 | 0.524578E+11 | 0.00 | 4.83 |
February | 0.00 | 0.00 | 0.00 | 0.163383E+10 | 0.00 | 0.00 | 0.473017E+11 | 0.00 | 4.81 |
March | 723920.45 | 0.00 | 0.00 | 0.193614E+10 | 0.00 | 0.00 | 0.511863E+11 | 0.00 | 4.89 |
April | 0.00 | 0.00 | 0.00 | 0.194532E+10 | 0.00 | 0.00 | 0.488854E+11 | 0.00 | 4.89 |
May | 0.00 | 0.00 | 0.00 | 0.196390E+10 | 0.00 | 0.00 | 0.469953E+11 | 0.00 | 5.07 |
June | 0.00 | 45540591.96 | 0.00 | 0.143812E+10 | 0.00 | 0.00 | 0.296415E+11 | 0.00 | 5.36 |
July | 0.00 | 0.211321E+09 | 0.00 | 0.146285E+10 | 0.00 | 0.00 | 0.263956E+11 | 0.00 | 5.34 |
August | 0.00 | 48325889.02 | 0.00 | 0.141350E+10 | 0.00 | 0.00 | 0.307501E+11 | 0.00 | 5.39 |
September | 3981780.00 | 0.00 | 0.00 | 0.144546E+10 | 0.00 | 0.00 | 0.369213E+11 | 0.00 | 5.25 |
October | 7427124.06 | 0.00 | 0.00 | 0.191307E+10 | 0.00 | 0.00 | 0.515039E+11 | 0.00 | 4.92 |
November | 6342129.77 | 0.00 | 0.00 | 0.183324E+10 | 0.00 | 0.00 | 0.507740E+11 | 0.00 | 4.84 |
December | 25748211.17 | 0.00 | 0.00 | 0.163507E+10 | 0.00 | 0.00 | 0.540246E+11 | 0.00 | 4.76 |
Annual Sum or Average | 51891355.53 | 0.305187E+09 | 0.00 | 0.204058E+11 | 0.00 | 0.00 | 0.526837E+12 | 0.00 | 5.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.141350E+10 | 0.00 | 0.00 | 0.263956E+11 | 0.00 | 4.76 |
Maximum of Months | 25748211.17 | 0.211321E+09 | 0.00 | 0.196390E+10 | 0.00 | 0.00 | 0.540246E+11 | 0.00 | 5.39 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.195716E+10 | 0.00 | 0.00 | 0.533660E+11 | 0.00 | 16.04 |
February | 0.00 | 0.00 | 0.00 | 0.178400E+10 | 0.00 | 0.00 | 0.480141E+11 | 0.00 | 15.94 |
March | 0.00 | 0.00 | 0.00 | 0.198174E+10 | 0.00 | 0.00 | 0.521663E+11 | 0.00 | 16.25 |
April | 0.00 | 0.00 | 0.00 | 0.192198E+10 | 0.00 | 0.00 | 0.498316E+11 | 0.00 | 16.21 |
May | 0.00 | 0.00 | 0.00 | 0.188772E+10 | 0.00 | 0.00 | 0.479917E+11 | 0.00 | 16.84 |
June | 0.00 | 46413585.79 | 0.00 | 0.155949E+10 | 0.00 | 0.00 | 0.284419E+11 | 0.00 | 17.20 |
July | 0.00 | 0.224015E+09 | 0.00 | 0.158421E+10 | 0.00 | 0.00 | 0.249481E+11 | 0.00 | 17.03 |
August | 0.00 | 49526418.54 | 0.00 | 0.162247E+10 | 0.00 | 0.00 | 0.293866E+11 | 0.00 | 17.19 |
September | 0.00 | 0.00 | 0.00 | 0.160145E+10 | 0.00 | 0.00 | 0.367046E+11 | 0.00 | 17.22 |
October | 0.00 | 0.00 | 0.00 | 0.192779E+10 | 0.00 | 0.00 | 0.528497E+11 | 0.00 | 16.50 |
November | 0.00 | 0.00 | 0.00 | 0.190513E+10 | 0.00 | 0.00 | 0.517930E+11 | 0.00 | 16.11 |
December | 0.00 | 0.00 | 0.00 | 0.188004E+10 | 0.00 | 0.00 | 0.553021E+11 | 0.00 | 15.91 |
Annual Sum or Average | 0.00 | 0.319955E+09 | 0.00 | 0.216132E+11 | 0.00 | 0.00 | 0.530796E+12 | 0.00 | 16.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.155949E+10 | 0.00 | 0.00 | 0.249481E+11 | 0.00 | 15.91 |
Maximum of Months | 0.00 | 0.224015E+09 | 0.00 | 0.198174E+10 | 0.00 | 0.00 | 0.553021E+11 | 0.00 | 17.22 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.291080E+10 | 0.00 | 0.00 | 25138918.21 | 0.00 | 0.471610E+09 | 0.147170E+10 | 0.00 | 0.36 |
February | 0.223730E+10 | 0.00 | 0.00 | 31704516.89 | 0.00 | 0.682230E+09 | 0.166231E+10 | 0.00 | 0.37 |
March | 0.267353E+10 | 0.00 | 0.00 | 47957445.52 | 0.00 | 44131036.13 | 0.271039E+10 | 0.00 | 0.42 |
April | 0.260769E+10 | 0.00 | 0.00 | 24627928.69 | 0.00 | 29460993.04 | 0.215548E+10 | 0.00 | 0.38 |
May | 0.818720E+09 | 0.00 | 0.00 | 0.104753E+09 | 0.00 | 0.00 | 0.632939E+10 | 0.00 | 0.65 |
June | 13974746.36 | 11564360.75 | 0.00 | 0.343422E+09 | 0.00 | 0.00 | 0.531078E+10 | 0.00 | 0.90 |
July | 21666356.85 | 53339393.22 | 0.00 | 0.375634E+09 | 0.00 | 0.00 | 0.480177E+10 | 0.00 | 0.90 |
August | 22146976.42 | 12420755.72 | 0.00 | 0.352079E+09 | 0.00 | 0.00 | 0.531510E+10 | 0.00 | 0.87 |
September | 0.297912E+09 | 0.00 | 0.00 | 0.242338E+09 | 0.00 | 0.00 | 0.542594E+10 | 0.00 | 0.76 |
October | 0.192191E+10 | 0.00 | 0.00 | 94473500.52 | 0.00 | 0.184518E+09 | 0.453745E+10 | 0.00 | 0.53 |
November | 0.251222E+10 | 0.00 | 0.00 | 49104743.88 | 0.00 | 0.260657E+09 | 0.252129E+10 | 0.00 | 0.41 |
December | 0.279098E+10 | 0.00 | 0.00 | 8572245.91 | 0.00 | 0.142155E+10 | 0.698480E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.188288E+11 | 77324509.70 | 0.00 | 0.169981E+10 | 0.00 | 0.309415E+10 | 0.429401E+11 | 0.00 | 0.57 |
Minimum of Months | 13974746.36 | 0.00 | 0.00 | 8572245.91 | 0.00 | 0.00 | 0.698480E+09 | 0.00 | 0.34 |
Maximum of Months | 0.291080E+10 | 53339393.22 | 0.00 | 0.375634E+09 | 0.00 | 0.142155E+10 | 0.632939E+10 | 0.00 | 0.90 |