Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:59
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2020-06-03 19:59:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31695.29 | 684.26 | 684.26 |
Net Site Energy | 31695.29 | 684.26 | 684.26 |
Total Source Energy | 99041.68 | 2138.19 | 2138.19 |
Net Source Energy | 99041.68 | 2138.19 | 2138.19 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 159.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5469.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3406.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 679.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1980.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2139.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 624.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2005.08 | 0.00 | 0.00 | 0.00 | 0.00 | 13249.60 |
Humidification | 5.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 |
Heat Recovery | 65.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 482.83 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31053.28 | 642.01 | 0.00 | 0.00 | 0.00 | 15531.64 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 159.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2642.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 2827.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 3406.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 679.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 79.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2139.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 624.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 591.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 1413.85 | 0.00 | 0.00 | 0.00 | 0.00 | 13249.60 | |
Humidification | General | 5.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 |
Heat Recovery | General | 65.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 482.83 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 221.16 | 13.86 | 0.00 | 0.00 | 0.00 | 0.34 |
Other | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 670.40 | 13.86 | 0.00 | 0.00 | 0.00 | 0.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 221.16 | 13.86 | 0.00 | 0.00 | 0.00 | 0.34 |
Other | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 670.40 | 13.86 | 0.00 | 0.00 | 0.00 | 0.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31053.281 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31053.281 | 100.00 |
Total On-Site and Utility Electric Sources | 31053.281 | 100.00 |
Total Electricity End Uses | 31053.281 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 3964.32 | 97.08 |
Air to Air Heat Recovery for Heating | 119.44 | 2.92 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4083.75 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 15531.64 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 15531.64 | 100.00 |
Total Water End Uses | 15531.64 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2.33 |
Time Setpoint Not Met During Occupied Cooling | 312.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2515.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:59 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.8264 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8264 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8264 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8264 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.8264 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.8264 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.8264 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.8264 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.8264 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.8264 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.8264 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.8264 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.8264 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.8264 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.8264 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.8264 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8264 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8264 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.8264 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.8264 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.8264 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.8264 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-15:50 | 21-JAN-07:10 | - | - | - | 30-AUG-15:00 |
Heating | 0.00 | 858604.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 456069.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 286578.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 90798.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 142765.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 47257.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 94088.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1901542.21 | 866751.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 858604.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 270516.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 286578.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 4980.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 142765.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 47257.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 44840.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 8146.58 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 172.56 | 0.00 | 0.00 | 0.00 |
Cooling | 17323.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10788.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2152.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46479.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6273.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6776.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1977.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6350.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 15.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 208.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 523.39 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 98345.74 | 695.94 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.73 | 0.00 | 0.00 | 0.00 |
Cooling | 373.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 46.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 135.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 146.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 42.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 137.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 11.30 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2123.16 | 15.02 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 3.73 | 0.00 | 0.00 | 0.00 |
Cooling | 373.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 232.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 46.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 135.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 146.29 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 42.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 137.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 11.30 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2123.16 | 15.02 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.75 |
DATACENTER BOT DIRECT AIR | 0.462352 |
DATACENTER MID DIRECT AIR | 4.39 |
DATACENTER TOP DIRECT AIR | 0.445774 |
DATACENTER BASEMENT DIRECT AIR | 21.27 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.81 | 0.327172 | 0.326000 | 1.90 | 0.872460 | 0.500000 | 0.001165 | 0.000421 | 1.90 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 54.46 | 0.349225 | 0.340000 | 18.52 | 0.931266 | 0.500000 | 0.001091 | 0.007832 | 18.52 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.39 | 0.352637 | 0.349000 | 1.88 | 0.940364 | 0.500000 | 0.001080 | 0.001294 | 1.88 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.881313 | 0.270983 | 0.270000 | 0.237955 | 0.722620 | 0.500000 | 0.001406 | 0.000115 | 0.237955 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.02 | 0.150830 | 0.200000 | 0.204078 | 0.402213 | 0.500000 | 0.002526 | 0.000092 | 0.204078 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.01 | 0.235986 | 0.235000 | 0.237828 | 0.629296 | 0.500000 | 0.001615 | 0.000153 | 0.237828 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.28 | 0.120058 | 0.200000 | 0.256385 | 0.320154 | 0.500000 | 0.003173 | 0.000077 | 0.256385 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.97 | 0.299519 | 0.291000 | 2.32 | 0.798717 | 0.500000 | 0.001272 | 0.003098 | 4.18 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.39 | 0.148192 | 0.200000 | 2.08 | 0.395178 | 0.500000 | 0.002571 | 0.002085 | 2.81 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 9.28 | 0.257423 | 0.250000 | 2.32 | 0.686461 | 0.500000 | 0.001480 | 0.003092 | 4.17 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.91 | 0.141104 | 0.200000 | 2.18 | 0.376278 | 0.500000 | 0.002700 | 0.001861 | 2.51 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.905045 | 0.263877 | 0.261000 | 0.236217 | 0.703672 | 0.500000 | 0.001444 | 0.000399 | 0.539031 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.05 | 0.147229 | 0.200000 | 0.209069 | 0.392610 | 0.500000 | 0.002588 | 0.000265 | 0.357600 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.03 | 0.232800 | 0.230000 | 0.235953 | 0.620800 | 0.500000 | 0.001637 | 0.000398 | 0.537463 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.16 | 0.132838 | 0.200000 | 0.231718 | 0.354235 | 0.500000 | 0.002868 | 0.000248 | 0.334465 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19066.83 | 0.000421 | 331.86 |
CORE_MID VAV BOX REHEAT COIL | 354502.61 | 0.007832 | 6619.13 |
CORE_TOP VAV BOX REHEAT COIL | 58549.11 | 0.001294 | 1195.95 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5220.56 | 0.000115 | 99.33 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4173.83 | 0.000092 | 78.61 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6934.70 | 0.000153 | 139.37 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3463.19 | 0.000077 | 62.57 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 140241.84 | 0.003098 | 2926.62 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 94382.88 | 0.002085 | 1969.56 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 139932.92 | 0.003092 | 2920.18 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 84249.03 | 0.001861 | 1758.23 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18068.70 | 0.000399 | 377.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11986.15 | 0.000265 | 250.08 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18016.29 | 0.000398 | 375.90 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11212.40 | 0.000248 | 233.95 |
CAV_BAS_HEATC | 271496.63 | 0.005998 | 5088.50 |
VAV_BOT WITH REHEAT_HEATC | 26456.38 | 0.000585 | 403.64 |
VAV_MID WITH REHEAT_HEATC | 247908.09 | 0.005477 | 3780.46 |
VAV_TOP WITH REHEAT_HEATC | 24075.00 | 0.000532 | 367.96 |
DATACENTER_EXTRAWATERHEATC | 1026626.59 | 0.022682 | 19120.02 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.75 | 5.75 | 5.75 | 5.75 | 5.75 | 5.75 | 1.00 | 1.00 | 5.75 |
VAV_BOT WITH REHEAT | 5.00 | 2.83 | 10.01 | 2.83 | 9.04 | 9.04 | 0.300000 | 0.313200 | 9.04 |
VAV_MID WITH REHEAT | 46.50 | 27.42 | 93.01 | 27.42 | 83.35 | 83.35 | 0.300000 | 0.328915 | 83.35 |
VAV_TOP WITH REHEAT | 4.76 | 2.80 | 9.53 | 3.45 | 8.83 | 8.83 | 0.300000 | 0.390555 | 8.83 |
AIRLOOP DATACENTER BASEMENT | 21.27 | 21.27 | 21.27 | 21.27 | 21.27 | 21.27 | 1.00 | 1.00 | 21.27 |
AIRLOOP DATACENTER BOT | 0.462352 | 0.462352 | 0.462352 | 0.462352 | 0.462352 | 0.462352 | 1.00 | 1.00 | 0.462352 |
AIRLOOP DATACENTER MID | 4.39 | 4.39 | 4.39 | 4.39 | 4.39 | 4.39 | 1.00 | 1.00 | 4.39 |
AIRLOOP DATACENTER TOP | 0.445774 | 0.445774 | 0.445774 | 0.445774 | 0.445774 | 0.445774 | 1.00 | 1.00 | 0.445774 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.75 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.04 | 2.54 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 83.35 | 25.38 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.83 | 2.54 |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.27 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.462352 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.39 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.445774 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 131315.43 | 0.005586 | 5.75 | 0.010526 | 24.95 | 6.67 | 11.42 | 0.008284 |
VAV_BOT WITH REHEAT_COOLC | 249829.26 | 0.010628 | 9.04 | 0.011144 | 26.94 | 6.67 | 11.43 | 0.008284 |
VAV_MID WITH REHEAT_COOLC | 2432309.94 | 0.103476 | 83.35 | 0.011490 | 27.33 | 6.67 | 11.43 | 0.008284 |
VAV_TOP WITH REHEAT_COOLC | 241127.22 | 0.010258 | 8.83 | 0.011092 | 26.81 | 6.67 | 11.43 | 0.008284 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.75 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.005586 | 0.000085 |
CAV_BAS_HEATC_CONTROLLER | 0.005998 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010628 | 0.000045 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000585 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.103476 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.005477 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.010258 | 0.000046 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000532 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022682 | 0.000021 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.04 |
VAV_MID WITH REHEAT FAN | 83.35 |
VAV_TOP WITH REHEAT FAN | 8.83 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.27 | 430942.18 | 310125.91 | 0.010554 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.462352 | 9336.22 | 6727.05 | 0.000229 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.39 | 88786.14 | 63897.39 | 0.002174 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.445774 | 9017.27 | 6491.14 | 0.000221 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.27 | 21.27 | 21.27 | 21.27 | 430942.18 | 430942.18 | 14481.98 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.462352 | 0.462352 | 0.462352 | 0.462352 | 9336.22 | 9336.22 | 669.01 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.39 | 4.39 | 4.39 | 4.39 | 88786.14 | 88786.14 | 6690.08 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.445774 | 0.445774 | 0.445774 | 0.445774 | 9017.27 | 9017.27 | 669.01 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.27 |
DATACENTER BOT SUPPLY FAN | 0.462352 |
DATACENTER MID SUPPLY FAN | 4.39 |
DATACENTER TOP SUPPLY FAN | 0.445774 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.27 | 430942.18 | 0.010554 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.462352 | 9336.22 | 0.000229 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.39 | 88786.14 | 0.002174 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.445774 | 9017.27 | 0.000221 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 14481.98 | |
DATACENTER_EXTRAELECHEATC | 430942.18 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 669.01 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 6690.08 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 669.01 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000080 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.129949 | 24857.61 |
HEATSYS1 PUMP | 0.056705 | 14487.42 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.129949 | 15.59 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.056705 | 6.80 |
COOLSYS1_SUPPLY | 0.129949 | 15.59 |
SINGLE WATER PLANT LOOP | 0.013178 | 1.58 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.129949 | 0.129949 | 545461.04 | 5.60 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 56.21 |
COOLSYS1 CHILLER1 PUMP | 0.064974 | 4142.94 |
COOLSYS1 CHILLER2 PUMP | 0.064974 | 4142.94 |
PLANT CIRC PUMP | 0.013178 | 3360.94 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2566563.71 | 1283281.85 | 0.056705 |
DUMMY BOILER | 542803.69 | 93894.07 | 0.013178 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.129949 | 0.065510 | 1543661.37 | 1550931.45 | 0.076750 |
COOLSYS1 CHILLER2 | 0.129949 | 0.065510 | 1543661.37 | 1550931.45 | 0.076750 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013178 | 139666.47 | 59749.46 | 69833.23 | 7879.72 | 21461.44 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.153500 | 18.42 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.153500 | 32483.47 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 59.06 | 1472134.32 | 11.81 | 184016.79 |
TOWERWATERSYS COOLTOWER 2 | 59.06 | 1472134.32 | 11.81 | 184016.79 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.063776 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.826 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.668 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.826 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.896 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 8.826 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.126 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 8.826 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.126 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 8.826 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 224.126 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 8.826 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.250 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 24532.349 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24532.349 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 22031.774 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22031.774 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 22031.774 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22031.774 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 22031.774 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22031.774 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2766.309 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.309 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1782.715 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.715 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2766.370 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.370 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1782.715 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.715 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2766.309 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.309 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1782.715 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.715 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2766.370 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.370 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1782.715 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.715 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2766.309 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.309 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1782.715 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.715 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2766.370 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.370 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1782.715 | 8.826 | 163.984 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1782.715 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 6917.073 | 8.826 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6917.073 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 319.540 | 8.826 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 319.540 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 319.540 | 8.826 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 319.540 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 319.540 | 8.826 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 319.540 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.9837 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8493 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9750000 | 3.9750000 | 3.9750000 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.31844121E-15 | 0.33891907E-16 | -0.14717764E-09 | -0.34085343E-17 |
51 | 8 | 0.21517510E-07 | 0.13210865E-12 | 0.37403321E-03 | -0.24466149E-09 |
52 | 7 | -0.12129356E-01 | 0.68855956E-08 | -0.22924263E-01 | 0.13791520E-03 |
53 | 6 | 0.40230169 | 0.24029480E-05 | 0.46949424 | -0.47118258E-02 |
54 | 5 | -5.1608121 | 0.89965799E-04 | -4.4213154 | 0.62814943E-01 |
55 | 4 | 32.871256 | 0.73775273E-03 | 21.362378 | -0.42037561 |
56 | 3 | -110.94624 | 0.16114037E-02 | -55.469893 | 1.5111496 |
57 | 2 | 196.85374 | 0.90819125E-03 | 77.733479 | -2.8963115 |
58 | 1 | -171.06207 | 0.97128343E-04 | -55.213590 | 2.7437919 |
59 | 0 | 57.057407 | 0.55402955E-06 | 15.565444 | |
60 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
61 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
62 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
63 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
64 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
65 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
66 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
67 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
68 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
69 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
70 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
71 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
72 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
73 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
74 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
75 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
76 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
77 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
78 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
79 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
80 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
81 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
82 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
83 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
84 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
85 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
86 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
87 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
88 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
89 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
90 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
91 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
92 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
93 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
94 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
95 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
96 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
97 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
98 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
99 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
100 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
101 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
102 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
103 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
104 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
105 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
106 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
107 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.57_SHGC_0.25 | 29 | 1 | VerySmooth | 3.241 | 0.252 | 0.162 | 0.276 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 79819.27127 | 79819.27127 | 5.75203 | 5.75203 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 80688.27595 | 80688.27595 | 5.81358 | 5.81358 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 756142.33740 | 756142.33740 | 54.46476 | 54.46476 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 168203.14953 | 168203.14953 | 7.03425 | 10.77757 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 74884.94711 | 74884.94711 | 5.39378 | 5.39378 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 39611.03369 | 39611.03369 | 1.67832 | 1.67832 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12119.86683 | 12119.86683 | 0.88131 | 0.88131 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.90000 | 1.65138E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 2830.99276 | 2830.99276 | 0.11906 | 0.13532 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14032.52789 | 14032.52789 | 1.02039 | 1.02039 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 30.00267 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2124.02296 | 2124.02296 | 8.95162E-002 | 8.95162E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 13917.57413 | 13917.57413 | 1.01203 | 1.01203 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 33.70250 | 1.65138E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 4544.95953 | 4544.95953 | 0.19242 | 0.19242 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 17629.31292 | 17629.31292 | 1.28193 | 1.28193 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 889.90702 | 889.90702 | 3.77712E-002 | 8.72074E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 109649.80908 | 109649.80908 | 7.97348 | 7.97348 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 33.90000 | 1.65138E-002 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 98200.33094 | 98200.33094 | 4.18121 | 4.18121 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 142821.35815 | 142821.35815 | 10.38554 | 10.38554 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 30.45033 | 1.65138E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 66084.74707 | 66084.74707 | 2.81425 | 2.81425 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 127583.57640 | 127583.57640 | 9.27756 | 9.27756 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65138E-002 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 97984.40327 | 97984.40327 | 4.17197 | 4.17197 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 149995.25043 | 149995.25043 | 10.90720 | 10.90720 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 32.66233 | 1.65138E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 59000.23515 | 59000.23515 | 2.51140 | 2.51140 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12445.95802 | 12445.95802 | 0.90504 | 0.90504 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65138E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 12647.42364 | 12647.42364 | 0.53903 | 0.53903 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14375.46706 | 14375.46706 | 1.04535 | 1.04535 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 30.67417 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 8389.54902 | 8389.54902 | 0.35760 | 0.35760 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 14107.74044 | 14107.74044 | 1.02588 | 1.02588 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65138E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 12610.79790 | 12610.79790 | 0.53746 | 0.53746 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 15932.83107 | 15932.83107 | 1.15859 | 1.15859 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 32.66233 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 7848.73516 | 7848.73516 | 0.33447 | 0.33447 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8062.32194 | 8062.32194 | 0.46235 | 0.46235 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 26.05267 | 1.65138E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76501.19389 | 76501.19389 | 4.38713 | 4.38713 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 26.05267 | 1.65138E-002 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7773.23229 | 7773.23229 | 0.44577 | 0.44577 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65138E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370855.13907 | 370855.13907 | 21.26753 | 21.26753 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 26.25017 | 1.65138E-002 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 84111.82 | 5.75203 | 5.75203 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 51362.34 | 1.20008 | 1.20008 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 146202.64 | 9.04047 | 9.04047 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 15686.01 | 1.58222 | 1.58222 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1326178.73 | 83.35368 | 83.35368 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 242458.43 | 24.45640 | 24.45640 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 148930.74 | 8.82558 | 8.82558 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 25156.95 | 3.44688 | 3.44688 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 10:50:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 367312.84 | 21.26753 | 21.26753 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14481.98 | 0.33837 | 0.33837 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7978.01 | 0.46235 | 0.46235 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 669.01 | 1.56314E-002 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 75926.86 | 4.38713 | 4.38713 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6690.08 | 0.15631 | 0.15631 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7733.72 | 0.44577 | 0.44577 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 669.01 | 1.56314E-002 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.75203 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.81358 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32717 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32600 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.89523 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87246 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16452E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.21258E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.89523 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19066.82817 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.21258E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 331.86305 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 54.46476 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34922 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.51802 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93127 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09099E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.83230E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.51802 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 354502.60503 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.83230E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6619.12796 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.39378 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35264 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34900 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.88243 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94036 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08043E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29357E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.88243 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 58549.10544 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29357E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1195.94820 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88131 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27098 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23795 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72262 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40599E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15342E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23795 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5220.56428 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15342E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 99.32612 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02039 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15083 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20408 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40221 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52603E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.22156E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20408 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4173.82726 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.22156E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 78.60647 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01203 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23599 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23500 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23783 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62930 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61450E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53214E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23783 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6934.69548 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53214E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 139.37247 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28193 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12006 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25639 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32015 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17348E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.65149E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25639 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3463.18801 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.65149E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 62.56791 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.97348 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29952 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29100 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.32028 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79872 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27204E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.09847E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.18121 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 140241.83781 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.09847E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2926.61863 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.38554 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14819 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.07711 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39518 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57099E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.08527E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.81425 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 94382.88434 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.08527E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1969.55520 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.27756 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25742 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.31939 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68646 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.48005E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.09165E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.17197 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 139932.91588 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.09165E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2920.17824 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.90720 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14110 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.18144 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37628 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.70013E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.86138E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.51140 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 84249.03215 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86138E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1758.22978 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90504 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26388 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26100 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23622 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70367 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44385E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.99206E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53903 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18068.70054 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.99206E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 376.99549 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04535 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14723 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20907 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39261 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58781E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.64819E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35760 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11986.15024 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.64819E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 250.08033 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02588 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23280 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23595 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62080 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.63660E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.98048E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.53746 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18016.29250 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.98048E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 375.90290 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15859 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13284 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23172 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35423 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.86816E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.47724E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33447 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11212.40132 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.47724E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 233.94740 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46235 |
213 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.38713 |
214 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44577 |
215 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.26753 |
216 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.75203 |
217 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.75203 |
218 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.75203 |
219 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.75203 |
220 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.75203 |
221 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.75203 |
222 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
223 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.00462 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.83147 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.00924 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.83147 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.04047 |
229 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.04047 |
230 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31320 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 46.50427 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 27.41624 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 93.00853 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 27.41624 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 83.35368 |
237 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 83.35368 |
238 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32891 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.76432 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.79539 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.52865 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.44688 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.82558 |
245 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.82558 |
246 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
247 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.39056 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.26753 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.26753 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.26753 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.26753 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.26753 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.26753 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46235 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46235 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46235 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46235 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46235 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46235 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.38713 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.38713 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.38713 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.38713 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.38713 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.38713 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44577 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44577 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44577 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44577 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44577 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.44577 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.75203 |
281 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.04047 |
282 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 83.35368 |
283 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.82558 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.26753 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46235 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.38713 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.44577 |
288 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.75203 |
289 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 131315.43065 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 5.58646E-003 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.75203 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.05259E-002 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 24.95374 |
295 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
296 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42425 |
297 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
298 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 271496.62794 |
299 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.99839E-003 |
300 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 5088.50315 |
301 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.75203 |
302 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.58646E-003 |
303 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.52401E-005 |
304 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.99839E-003 |
305 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.04047 |
306 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53804 |
307 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53804 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 249829.26065 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.06283E-002 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 9.04047 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.11436E-002 |
312 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.93641 |
313 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
314 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42579 |
315 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
316 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 26456.37746 |
317 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.84521E-004 |
318 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 403.63589 |
319 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.04047 |
320 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.06283E-002 |
321 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.48040E-005 |
322 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.84521E-004 |
323 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 83.35368 |
324 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.38036 |
325 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38036 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 2432309.93591 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 0.10348 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 83.35368 |
329 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.14903E-002 |
330 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 27.32667 |
331 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
332 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42666 |
333 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
334 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 247908.09401 |
335 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.47723E-003 |
336 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 3780.46469 |
337 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 83.35368 |
338 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10348 |
339 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.60194E-006 |
340 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.47723E-003 |
341 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.82558 |
342 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53804 |
343 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53804 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 241127.21647 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.02581E-002 |
346 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.82558 |
347 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.10918E-002 |
348 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.81141 |
349 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
350 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42566 |
351 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
352 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 24074.99645 |
353 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.31908E-004 |
354 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 367.96403 |
355 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.82558 |
356 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.02581E-002 |
357 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.64209E-005 |
358 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.31908E-004 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.26753 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.26753 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 430942.18281 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 310125.90604 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.05537E-002 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.26753 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.26753 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.26753 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.26753 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 430942.18281 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 430942.18281 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14481.98191 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
373 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.26753 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.26753 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 430942.18281 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.05537E-002 |
377 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 14481.98191 |
378 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 7.99074E-005 |
379 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
380 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
381 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
382 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 430942.18281 |
383 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
384 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1026626.59008 |
385 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.26821E-002 |
386 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19120.02401 |
387 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.26821E-002 |
388 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.09941E-005 |
389 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46235 |
390 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.46235 |
391 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9336.22164 |
392 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6727.05069 |
393 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.28643E-004 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46235 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46235 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46235 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46235 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9336.22164 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9336.22164 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.00757 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
402 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46235 |
403 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.46235 |
404 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9336.22164 |
405 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.28643E-004 |
406 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 669.00757 |
407 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.38713 |
408 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.38713 |
409 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 88786.13956 |
410 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 63897.39042 |
411 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.17437E-003 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.38713 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.38713 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.38713 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.38713 |
416 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 88786.13956 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 88786.13956 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6690.07569 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
420 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.38713 |
421 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.38713 |
422 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 88786.13956 |
423 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.17437E-003 |
424 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 6690.07569 |
425 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44577 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.44577 |
427 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 9017.26802 |
428 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 6491.13629 |
429 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.20832E-004 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.44577 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.44577 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.44577 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.44577 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9017.26802 |
435 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9017.26802 |
436 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.00757 |
437 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
438 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44577 |
439 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.44577 |
440 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 9017.26802 |
441 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.20832E-004 |
442 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 669.00757 |
443 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12995 |
444 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 24857.61492 |
445 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12995 |
446 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.59388 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12995 |
448 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12995 |
449 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 545461.04351 |
450 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
451 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
452 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
453 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
454 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 56.20535 |
455 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
456 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.67051E-002 |
457 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 6.80461 |
458 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.67051E-002 |
459 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 14487.42313 |
460 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2566563.71440 |
461 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1283281.85500 |
462 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.67051E-002 |
463 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12995 |
464 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.59388 |
465 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 6.49745E-002 |
466 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4142.93582 |
467 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 6.49745E-002 |
468 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4142.93582 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12995 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.55100E-002 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1543661.37255 |
472 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1550931.45000 |
473 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.67499E-002 |
474 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12995 |
475 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.55100E-002 |
476 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1543661.37255 |
477 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1550931.45000 |
478 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.67499E-002 |
479 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.31776E-002 |
480 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.58131 |
481 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.31776E-002 |
482 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3360.94416 |
483 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.31776E-002 |
484 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
485 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59749.46381 |
486 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
487 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
488 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21461.43802 |
489 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 542803.69241 |
490 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
491 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.31776E-002 |
492 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15350 |
493 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.41996 |
494 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15350 |
495 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 32483.47257 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 59.05691 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1472134.32178 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.81138 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 184016.79022 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 59.05691 |
501 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1472134.32178 |
502 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.81138 |
503 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 184016.79022 |
504 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 6.37760E-002 |
505 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 6.37760E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18088.84 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 336571.32 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 55554.61 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4955.88 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3962.46 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6580.93 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3289.15 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 133058.46 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 89548.48 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 132765.36 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 79933.67 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17143.21 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11372.21 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17093.48 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10638.09 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 220589.78 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 22485.78 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 210336.64 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 20607.29 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 825564.44 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 160505.42 | 108538.51 | 51966.91 | 0.68 | 19627.60 | 199.07 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 269863.52 | 178588.61 | 91274.91 | 0.66 | 33077.10 | 335.49 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2527612.10 | 1664537.47 | 863074.63 | 0.66 | 309413.26 | 3138.24 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 262609.58 | 173965.44 | 88644.15 | 0.66 | 32214.61 | 326.74 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.08 | 24.16 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.08 | 24.16 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 23 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2221101510 | 0.2199398187 | Pass | Pass | 0.6988434812 | 0.6410468710 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2079267809 | 0.2488494635 | Pass | Pass | 0.2317059331 | 0.4203343144 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1391256525 | 0.2051345641 | Pass | Pass | 0.1890659940 | 0.3904764238 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1272311657 | 0.2056621549 | Pass | Pass | 0.1751806406 | 0.3786339013 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1740373702 | 0.2219157515 | Pass | Pass | 0.2310260106 | 0.4192423561 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2570822409 | 0.3307705086 | Pass | Pass | 0.2333106796 | 0.4200529041 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3658059251 | 0.5938674592 | Pass | Pass | 0.2455339273 | 0.4264702143 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3153978322 | 0.4419037033 | Pass | Pass | 0.2347099755 | 0.4173182233 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1251030584 | 0.1842360157 | Pass | Pass | 0.1885511266 | 0.3892087765 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2101820245 | 0.2725943357 | Pass | Pass | 0.2002214401 | 0.4094696954 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3362906389 | 0.5744038871 | Pass | Pass | 0.2065446035 | 0.4057554220 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1895447476 | 0.3057232639 | Pass | Pass | 0.1889193160 | 0.3880319018 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1208476984 | 0.1847534975 | Pass | Pass | 0.1749222548 | 0.3774850570 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2038285330 | 0.2701105850 | Pass | Pass | 0.1763083443 | 0.3799227329 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3349188542 | 0.5671585430 | Pass | Pass | 0.1858324498 | 0.3848996636 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1909489379 | 0.3136913100 | Pass | Pass | 0.1751252035 | 0.3760986392 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.6737888837E-002 | 3.7221167996E-002 | Pass | Pass | 0.2572646285 | 0.4459171004 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.3183795038E-002 | 4.1459701102E-002 | Pass | Pass | 0.2389368640 | 0.5241588822 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.6479928211E-002 | 7.3268578598E-002 | Pass | Pass | 0.1790215764 | 0.3727063112 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5823196261E-014 | 3.1937394234E-014 | Pass | Pass | 3.2815871437E-003 | 4.6274630689E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.8227841473E-012 | 3.5640388663E-011 | Pass | Pass | 5.0658892335E-003 | 5.9087106920E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.2694689774E-012 | 4.9186929939E-011 | Pass | Pass | 8.1774608175E-003 | 6.2651317640E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.5421150806E-014 | 5.2381143811E-014 | Pass | Pass | 3.4460996765E-005 | 3.3539844246E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.57_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.57_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.57_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.57_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.57_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.57_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.57_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.57_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.57_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.57_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.57_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.57_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.57_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.57_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.57_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.57_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.241 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.241 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.241 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.57_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.57_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.57_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.241 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.57_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.241 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 4635.80 | 3.241 | 0.252 | 0.276 | ||||||||||||
North Total or Average | 1390.74 | 3.241 | 0.252 | 0.276 | ||||||||||||
Non-North Total or Average | 3245.06 | 3.241 | 0.252 | 0.276 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 8.8264 | 2779.43 | 24532.35 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 230.28 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 8.8264 | 2496.12 | 22031.77 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 206.80 |
CORE_MID_LIGHTS | CORE_MID | 8.8264 | 24961.20 | 220317.74 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 2068.04 |
CORE_TOP_LIGHTS | CORE_TOP | 8.8264 | 2496.12 | 22031.77 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 206.80 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 8.8264 | 313.41 | 2766.31 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 29.29 | 0.0000 | Y | 15.21 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 8.8264 | 201.98 | 1782.71 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 29.02 | 0.0000 | Y | 9.71 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 8.8264 | 313.42 | 2766.37 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.74 | 0.0000 | Y | 14.92 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 8.8264 | 201.98 | 1782.71 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 29.06 | 0.0000 | Y | 9.73 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 8.8264 | 3134.13 | 27663.09 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 29.20 | 0.0000 | Y | 151.65 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 8.8264 | 2019.75 | 17827.15 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.97 | 0.0000 | Y | 96.93 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 8.8264 | 3134.20 | 27663.70 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.70 | 0.0000 | Y | 149.03 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 8.8264 | 2019.75 | 17827.15 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.99 | 0.0000 | Y | 97.01 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 8.8264 | 313.41 | 2766.31 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 29.20 | 0.0000 | Y | 15.16 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 8.8264 | 201.98 | 1782.71 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.96 | 0.0000 | Y | 9.69 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 8.8264 | 313.42 | 2766.37 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.70 | 0.0000 | Y | 14.90 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 8.8264 | 201.98 | 1782.71 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 28.99 | 0.0000 | Y | 9.70 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 8.8264 | 783.68 | 6917.07 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 64.93 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 8.8264 | 36.20 | 319.54 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 3.00 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 8.8264 | 362.03 | 3195.40 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 29.99 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 8.8264 | 36.20 | 319.54 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 3.00 |
Interior Lighting Total | 8.8264 | 46320.38 | 408842.49 | 1073.11 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2766.31 | 1066.97 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2766.31 | 383.13 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1782.71 | 687.59 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1782.71 | 246.91 |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2766.37 | 1066.99 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2766.37 | 383.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1782.71 | 687.59 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1782.71 | 246.91 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2766.31 | 1066.97 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2766.31 | 383.13 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1782.71 | 687.59 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1782.71 | 246.91 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2766.37 | 1066.99 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2766.37 | 383.14 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1782.71 | 687.59 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1782.71 | 246.91 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2766.31 | 1066.97 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2766.31 | 383.13 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1782.71 | 687.59 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1782.71 | 246.91 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2766.37 | 1066.99 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2766.37 | 383.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1782.71 | 687.59 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1782.71 | 246.91 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12979.20 | AstronomicalClock | - | 41.73 | 41.73 | 101.66 | |
EXTERIOR_LIGHTS_B | 43301.50 | AstronomicalClock | - | 83.73 | 71.13 | 578.13 | |
Exterior Lighting Total | 56280.70 | 679.79 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3047557.21 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1283281.85 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1550931.45 | 6.28 | 7.08 | 24.16 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1550931.45 | 6.28 | 7.08 | 24.16 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1472134.32 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1472134.32 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 131315.43 | 160505.42 | 108538.51 | 51966.91 | 0.68 | - | 19627.60 | 199.07 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 249829.26 | 269863.52 | 178588.61 | 91274.91 | 0.66 | - | 33077.10 | 335.49 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 2432309.94 | 2527612.10 | 1664537.47 | 863074.63 | 0.66 | - | 309413.26 | 3138.24 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 241127.22 | 262609.58 | 173965.44 | 88644.15 | 0.66 | - | 32214.61 | 326.74 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 430942.18 | 310125.91 | 120816.28 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9336.22 | 6727.05 | 2609.17 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 88786.14 | 63897.39 | 24888.75 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9017.27 | 6491.14 | 2526.13 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19066.83 | 18088.84 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 354502.61 | 336571.32 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 58549.11 | 55554.61 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5220.56 | 4955.88 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4173.83 | 3962.46 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6934.70 | 6580.93 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3463.19 | 3289.15 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 140241.84 | 133058.46 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 94382.88 | 89548.48 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 139932.92 | 132765.36 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 84249.03 | 79933.67 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18068.70 | 17143.21 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11986.15 | 11372.21 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18016.29 | 17093.48 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11212.40 | 10638.09 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 271496.63 | 220589.78 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 26456.38 | 22485.78 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 247908.09 | 210336.64 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 24075.00 | 20607.29 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 430942.18 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9336.22 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 88786.14 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 9017.27 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 14481.98 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1026626.59 | 825564.44 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 669.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 6690.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 669.01 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.75 | 9753.45 | 1695.65 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.04 | 19535.97 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 83.35 | 180122.86 | 2160.95 | 1.00 | 1.08 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.83 | 19071.61 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.27 | 35260.99 | 1657.97 | 1.00 | 1.13 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 517.88 | 1120.11 | 1.00 | 1.64 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.39 | 4914.06 | 1120.11 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 499.31 | 1120.11 | 1.00 | 1.66 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 134283.83 | 0.129949 | 24857.61 | 191287.51 | 0.90 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.056705 | 14487.42 | 255487.18 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.064974 | 4142.94 | 63762.50 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.064974 | 4142.94 | 63762.50 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013178 | 3360.94 | 255050.01 | 0.90 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.153500 | 32483.47 | 211619.12 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 79819.27 | 79819.27 | 28.72 | 5.752 | 5.752 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 28.05 | 0.01651 | 1.200 | 0.00 |
CORE_BOTTOM | 80688.28 | 80688.28 | 32.33 | 5.814 | 5.814 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 28.05 | 0.01651 | 1.078 | 0.00 |
CORE_MID | 756142.34 | 756142.34 | 302.93 | 54.465 | 54.465 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 28.05 | 0.01651 | 10.778 | 0.00 |
CORE_TOP | 74884.95 | 74884.95 | 30.00 | 5.394 | 5.394 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 28.05 | 0.01651 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12119.87 | 12119.87 | 38.67 | 0.881 | 0.881 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00885 | 33.90 | 0.01651 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14032.53 | 14032.53 | 69.48 | 1.020 | 1.020 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00870 | 30.00 | 0.01651 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 13917.57 | 13917.57 | 44.41 | 1.012 | 1.012 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00881 | 33.70 | 0.01651 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 17629.31 | 17629.31 | 87.28 | 1.282 | 1.282 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00866 | 32.79 | 0.01651 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 109649.81 | 109649.81 | 349.86 | 7.973 | 7.973 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00894 | 33.90 | 0.01651 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 142821.36 | 142821.36 | 707.12 | 10.386 | 10.386 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 24.00 | 24.00 | 0.00872 | 30.45 | 0.01651 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 127583.58 | 127583.58 | 407.07 | 9.278 | 9.278 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00888 | 33.77 | 0.01651 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 149995.25 | 149995.25 | 742.64 | 10.907 | 10.907 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00871 | 32.66 | 0.01651 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12445.96 | 12445.96 | 39.71 | 0.905 | 0.905 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00891 | 33.82 | 0.01651 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14375.47 | 14375.47 | 71.17 | 1.045 | 1.045 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 24.00 | 24.00 | 0.00873 | 30.67 | 0.01651 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14107.74 | 14107.74 | 45.01 | 1.026 | 1.026 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00886 | 33.90 | 0.01651 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15932.83 | 15932.83 | 78.89 | 1.159 | 1.159 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00871 | 32.66 | 0.01651 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8062.32 | 8062.32 | 222.70 | 0.462 | 0.462 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.05 | 0.01651 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76501.19 | 76501.19 | 2113.13 | 4.387 | 4.387 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.05 | 0.01651 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7773.23 | 7773.23 | 214.71 | 0.446 | 0.446 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 31.21 | 0.01651 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370855.14 | 370855.14 | 473.22 | 21.268 | 21.268 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 27.00 | 27.00 | 0.00850 | 26.25 | 0.01651 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.078 | 0.00 | |
CORE_MID | 168203.15 | 168203.15 | 67.39 | 7.034 | 10.778 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 10.778 | 0.00 |
CORE_TOP | 39611.03 | 39611.03 | 15.87 | 1.678 | 1.678 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 2830.99 | 2830.99 | 9.03 | 0.119 | 0.135 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00706 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2124.02 | 2124.02 | 10.52 | 0.090 | 0.090 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00718 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 4544.96 | 4544.96 | 14.50 | 0.192 | 0.192 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00739 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 889.91 | 889.91 | 4.41 | 0.038 | 0.087 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00675 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 98200.33 | 98200.33 | 313.33 | 4.181 | 4.181 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 66084.75 | 66084.75 | 327.19 | 2.814 | 2.814 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 97984.40 | 97984.40 | 312.63 | 4.172 | 4.172 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 59000.24 | 59000.24 | 292.12 | 2.511 | 2.511 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00770 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12647.42 | 12647.42 | 40.35 | 0.539 | 0.539 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 8389.55 | 8389.55 | 41.54 | 0.358 | 0.358 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 12610.80 | 12610.80 | 40.24 | 0.537 | 0.537 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 7848.74 | 7848.74 | 38.86 | 0.334 | 0.334 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 4.60 | 0.00526 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.75 | 5.75 | 1.20 | 1.20 | 5.7520 | 5.7520 | 5.7520 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 9.04 | 9.04 | 1.58 | 1.58 | 9.0405 | 2.8315 | 9.0405 | 0.3132 | 0.3000 |
VAV_MID WITH REHEAT | 83.35 | 83.35 | 24.46 | 24.46 | 83.3537 | 27.4162 | 83.3537 | 0.3289 | 0.3000 |
VAV_TOP WITH REHEAT | 8.83 | 8.83 | 3.45 | 3.45 | 8.8256 | 3.4469 | 8.8256 | 0.3906 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.27 | 21.27 | 0.34 | 0.34 | 21.2675 | 21.2675 | 21.2675 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.46 | 0.46 | 0.02 | 0.02 | 0.4624 | 0.4624 | 0.4624 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.39 | 4.39 | 0.16 | 0.16 | 4.3871 | 4.3871 | 4.3871 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4458 | 0.4458 | 0.4458 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19066.828 | 19066.828 | 1.895228 | 0.00042126 | 331.863 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 18088.84 | 19066.83 | 1.895228 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 19143.53 | 19143.53 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 354502.605 | 354502.605 | 18.518017 | 0.00783230 | 6619.128 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 336571.32 | 354502.61 | 18.518017 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 168203.15 | 0.00 | 356204.99 | 356204.99 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 58549.105 | 58549.105 | 1.882429 | 0.00129357 | 1195.948 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 55554.61 | 58549.11 | 1.882429 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 39611.03 | 0.00 | 58816.52 | 58816.52 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5220.564 | 5220.564 | 0.237955 | 0.00011534 | 99.326 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4955.88 | 5220.56 | 0.237955 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00705940 | 45.6694 | 2830.99 | 0.00 | 5245.40 | 5245.40 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4173.827 | 4173.827 | 0.204078 | 0.00009222 | 78.606 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3962.46 | 4173.83 | 0.204078 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00718118 | 46.4486 | 2124.02 | 0.00 | 4193.77 | 4193.77 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6934.695 | 6934.695 | 0.237828 | 0.00015321 | 139.372 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6580.93 | 6934.70 | 0.237828 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00739388 | 47.8081 | 4544.96 | 0.00 | 6966.90 | 6966.90 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3463.188 | 3463.188 | 0.256385 | 0.00007651 | 62.568 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3289.15 | 3463.19 | 0.256385 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00674548 | 43.6595 | 889.91 | 0.00 | 3480.47 | 3480.47 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 140241.838 | 140241.838 | 4.181210 | 0.00309847 | 2926.619 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 133058.46 | 140241.84 | 4.181210 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00775173 | 50.0931 | 98200.33 | 0.00 | 140882.12 | 140882.12 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 94382.884 | 94382.884 | 2.814250 | 0.00208527 | 1969.555 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 89548.48 | 94382.88 | 2.814250 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00777270 | 50.2268 | 66084.75 | 0.00 | 94813.79 | 94813.79 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 139932.916 | 139932.916 | 4.171970 | 0.00309165 | 2920.178 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 132765.36 | 139932.92 | 4.171970 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00775069 | 50.0864 | 97984.40 | 0.00 | 140571.79 | 140571.79 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 84249.032 | 84249.032 | 2.511400 | 0.00186138 | 1758.230 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 79933.67 | 84249.03 | 2.511400 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00769508 | 49.7318 | 59000.24 | 0.00 | 84633.68 | 84633.68 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 18068.701 | 18068.701 | 0.539031 | 0.00039921 | 376.995 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17143.21 | 18068.70 | 0.539031 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00787196 | 50.8594 | 12647.42 | 0.00 | 18151.19 | 18151.19 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11986.150 | 11986.150 | 0.357600 | 0.00026482 | 250.080 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11372.21 | 11986.15 | 0.357600 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00787908 | 50.9047 | 8389.55 | 0.00 | 12040.87 | 12040.87 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 18016.293 | 18016.293 | 0.537463 | 0.00039805 | 375.903 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17093.48 | 18016.29 | 0.537463 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00787065 | 50.8510 | 12610.80 | 0.00 | 18098.54 | 18098.54 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11212.401 | 11212.401 | 0.334465 | 0.00024772 | 233.947 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10638.09 | 11212.40 | 0.334465 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00784532 | 50.6897 | 7848.74 | 0.00 | 11263.59 | 11263.59 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 131315.431 | -999.000 | 5.752025 | 0.00558646 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 131315.43 | 93324.92 | 5.752025 | 24.95 | 18.37 | 0.01052585 | 11.42 | 11.42 | 0.00828381 | 28.55 | 0.01651377 | 23.71 | 20.8636 | 24.00 | 0.00893744 | 48.0416 | 79819.27 | 0.00 | 145001.25 | 99914.84 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 271496.628 | 271496.628 | 5.752025 | 0.00599839 | 5088.503 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 220589.78 | 249820.04 | 5.752025 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 20.8636 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 232806.30 | 232806.30 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 249829.261 | -999.000 | 9.040466 | 0.01062831 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 249829.26 | 171766.44 | 9.040466 | 26.94 | 19.49 | 0.01114363 | 11.43 | 12.09 | 0.00828381 | 33.90 | 0.01651378 | 25.10 | 28.0742 | 24.00 | 0.00882778 | 47.4601 | 117639.48 | 0.00 | 271354.03 | 181428.11 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 26456.377 | 26456.377 | 2.712140 | 0.00058452 | 403.636 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22485.78 | 26456.38 | 2.712140 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.58 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 93.5807 | 21.00 | 0.00773037 | 49.9550 | 10389.88 | 0.00 | 23785.49 | 23785.49 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2432309.936 | -999.000 | 83.353679 | 0.10347609 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2432309.94 | 1624378.56 | 83.353679 | 27.33 | 19.87 | 0.01149035 | 11.43 | 12.09 | 0.00828381 | 33.90 | 0.01651378 | 25.10 | 30.4490 | 24.00 | 0.00886791 | 47.6730 | 1038410.93 | 0.00 | 2630944.69 | 1715043.37 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 247908.094 | 247908.094 | 25.006104 | 0.00547723 | 3780.465 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 210336.64 | 247908.09 | 25.006104 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.58 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 101.4967 | 21.00 | 0.00785756 | 50.7673 | 489472.87 | 0.00 | 222500.49 | 222500.49 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 241127.216 | -999.000 | 8.825580 | 0.01025811 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 241127.22 | 166320.52 | 8.825580 | 26.81 | 19.41 | 0.01109185 | 11.43 | 12.09 | 0.00828381 | 33.74 | 0.01651377 | 25.06 | 28.7578 | 24.00 | 0.00886576 | 47.6617 | 120902.55 | 0.00 | 262136.92 | 175728.14 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 24074.996 | 24074.996 | 2.647674 | 0.00053191 | 367.964 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 10:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20607.29 | 24075.00 | 2.647674 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.58 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 95.8592 | 21.00 | 0.00793225 | 51.2432 | 59152.43 | 0.00 | 21799.51 | 21799.51 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 430942.183 | 310125.906 | 21.267529 | 0.01055375 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 460613.96 | 452077.73 | -999.0 | 28.51 | 18.02 | 0.00862772 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 370214.82 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9336.222 | 6727.051 | 0.462352 | 0.00022864 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 9985.27 | 9589.52 | -999.0 | 28.09 | 18.00 | 0.00877228 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01651378 | 24.41 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 8022.42 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 88786.140 | 63897.390 | 4.387135 | 0.00217437 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 94922.98 | 90977.62 | -999.0 | 28.10 | 18.01 | 0.00878624 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01651378 | 24.41 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 76310.49 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9017.268 | 6491.136 | 0.445774 | 0.00022083 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9641.26 | 9247.52 | -999.0 | 28.10 | 18.01 | 0.00878111 | 12.80 | 12.09 | 0.00850000 | 31.41 | 0.01651378 | 24.46 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 7770.51 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 430942.183 | 430942.183 | 21.267529 | 0.01055375 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 430942.18 | 430942.18 | 21.267529 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5910 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9336.222 | 9336.222 | 0.462352 | 0.00022864 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9336.22 | 9336.22 | 0.462352 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.3808 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 88786.140 | 88786.140 | 4.387135 | 0.00217437 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 88786.14 | 88786.14 | 4.387135 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5630 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9017.268 | 9017.268 | 0.445774 | 0.00022083 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9017.27 | 9017.27 | 0.445774 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5066 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14481.982 | 14481.982 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14481.98 | 14481.98 | 21.267529 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5910 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 923684.25 | 21.267529 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5910 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1026626.590 | 1026626.590 | 21.267529 | 0.02268206 | 19120.024 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 825564.44 | 923684.25 | 21.267529 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5910 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 0.462352 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.3808 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6690.076 | 6690.076 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6690.08 | 6690.08 | 4.387135 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5630 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 0.445774 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5066 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19066.828 | 19066.828 | 1.895228 | 0.00042126 | 331.863 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 0.6909 | 0.742893 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 18088.84 | 19066.83 | 1.0000 | 2.28027508 | 1.895228 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.42121530 | 60.00 | 49.00 | 11.00 | 0.000 | 18088.84 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 19143.53 | 19143.53 | 2.28027508 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 354502.605 | 354502.605 | 18.518017 | 0.00783230 | 6619.128 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 12.8550 | 13.812344 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 336571.32 | 354502.61 | 1.0000 | 22.28026482 | 18.518017 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 7.83150290 | 60.00 | 49.00 | 11.00 | 0.000 | 336571.32 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 168203.15 | 0.00 | 356204.99 | 356204.99 | 22.28026482 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 28.48 | 17.50 | 0.00800000 | 49047.3 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 58549.105 | 58549.105 | 1.882429 | 0.00129357 | 1195.948 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 2.1218 | 2.281225 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 55554.61 | 58549.11 | 1.0000 | 2.26487660 | 1.882429 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 1.29343898 | 60.00 | 49.00 | 11.00 | 0.000 | 55554.61 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 39611.03 | 0.00 | 58816.52 | 58816.52 | 2.26487660 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 38.27 | 20.63 | 0.00800000 | 59028.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5220.564 | 5220.564 | 0.237955 | 0.00011534 | 99.326 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 0.1893 | 0.203407 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4955.88 | 5220.56 | 1.0000 | 0.28629905 | 0.237955 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.11533022 | 60.00 | 49.00 | 11.00 | 0.000 | 4955.88 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.83 | 0.00705940 | 21.00 | 0.00705940 | 45.6694 | 2830.99 | 0.00 | 5245.40 | 5245.40 | 0.28629905 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 30.77 | 18.27 | 0.00800000 | 51381.2 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4173.827 | 4173.827 | 0.204078 | 0.00009222 | 78.606 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 0.1513 | 0.162623 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3962.46 | 4173.83 | 1.0000 | 0.24553963 | 0.204078 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.09220621 | 60.00 | 49.00 | 11.00 | 0.000 | 3962.46 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.81 | 0.00718118 | 21.00 | 0.00718118 | 46.4486 | 2124.02 | 0.00 | 4193.77 | 4193.77 | 0.24553963 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 29.55 | 17.86 | 0.00800000 | 50139.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6934.695 | 6934.695 | 0.237828 | 0.00015321 | 139.372 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 0.2514 | 0.270194 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6580.93 | 6934.70 | 1.0000 | 0.28614689 | 0.237828 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.15319799 | 60.00 | 49.00 | 11.00 | 0.000 | 6580.93 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00739388 | 21.00 | 0.00739388 | 47.8081 | 4544.96 | 0.00 | 6966.90 | 6966.90 | 0.28614689 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 36.68 | 20.15 | 0.00800000 | 57407.1 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3463.188 | 3463.188 | 0.256385 | 0.00007651 | 62.568 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 0.1256 | 0.134935 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3289.15 | 3463.19 | 1.0000 | 0.30847429 | 0.256385 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.07650710 | 60.00 | 49.00 | 11.00 | 0.000 | 3289.15 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.92 | 0.00674548 | 21.00 | 0.00674548 | 43.6595 | 889.91 | 0.00 | 3480.47 | 3480.47 | 0.30847429 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 23.86 | 15.89 | 0.00800000 | 44342.7 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 140241.838 | 140241.838 | 4.181210 | 0.00309847 | 2926.619 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 5.0820 | 5.464187 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 133058.46 | 140241.84 | 1.0000 | 5.03069333 | 4.181210 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 3.09815596 | 60.00 | 49.00 | 11.00 | 0.000 | 133058.46 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00775173 | 21.00 | 0.00775173 | 50.0931 | 98200.33 | 0.00 | 140882.12 | 140882.12 | 5.03069333 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.26 | 21.23 | 0.00800000 | 61064.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 94382.884 | 94382.884 | 2.814250 | 0.00208527 | 1969.555 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 3.4202 | 3.677403 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 89548.48 | 94382.88 | 1.0000 | 3.38601276 | 2.814250 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 2.08506178 | 60.00 | 49.00 | 11.00 | 0.000 | 89548.48 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00777270 | 21.00 | 0.00777270 | 50.2268 | 66084.75 | 0.00 | 94813.79 | 94813.79 | 3.38601276 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.26 | 21.23 | 0.00800000 | 61061.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 139932.916 | 139932.916 | 4.171970 | 0.00309165 | 2920.178 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 5.0708 | 5.452150 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 132765.36 | 139932.92 | 1.0000 | 5.01957600 | 4.171970 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 3.09133141 | 60.00 | 49.00 | 11.00 | 0.000 | 132765.36 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00775069 | 21.00 | 0.00775069 | 50.0864 | 97984.40 | 0.00 | 140571.79 | 140571.79 | 5.01957600 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.26 | 21.23 | 0.00800000 | 61064.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 84249.032 | 84249.032 | 2.511400 | 0.00186138 | 1758.230 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 3.0530 | 3.282561 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 79933.67 | 84249.03 | 1.0000 | 3.02163371 | 2.511400 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 1.86118954 | 60.00 | 49.00 | 11.00 | 0.000 | 79933.67 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00769508 | 21.00 | 0.00769508 | 49.7318 | 59000.24 | 0.00 | 84633.68 | 84633.68 | 3.02163371 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61069.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18068.701 | 18068.701 | 0.539031 | 0.00039921 | 376.995 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 0.6548 | 0.704004 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17143.21 | 18068.70 | 1.0000 | 0.64854441 | 0.539031 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.39916514 | 60.00 | 49.00 | 11.00 | 0.000 | 17143.21 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00787196 | 21.00 | 0.00787196 | 50.8594 | 12647.42 | 0.00 | 18151.19 | 18151.19 | 0.64854441 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61047.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11986.150 | 11986.150 | 0.357600 | 0.00026482 | 250.080 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 0.4343 | 0.467012 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11372.21 | 11986.15 | 1.0000 | 0.43025277 | 0.357600 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.26479233 | 60.00 | 49.00 | 11.00 | 0.000 | 11372.21 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00787908 | 21.00 | 0.00787908 | 50.9047 | 8389.55 | 0.00 | 12040.87 | 12040.87 | 0.43025277 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61045.4 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18016.293 | 18016.293 | 0.537463 | 0.00039805 | 375.903 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 0.6529 | 0.701962 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17093.48 | 18016.29 | 1.0000 | 0.64665825 | 0.537463 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.39800736 | 60.00 | 49.00 | 11.00 | 0.000 | 17093.48 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00787065 | 21.00 | 0.00787065 | 50.8510 | 12610.80 | 0.00 | 18098.54 | 18098.54 | 0.64665825 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61047.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11212.401 | 11212.401 | 0.334465 | 0.00024772 | 233.947 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 0.4063 | 0.436864 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10638.09 | 11212.40 | 1.0000 | 0.40241775 | 0.334465 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.24769904 | 60.00 | 49.00 | 11.00 | 0.000 | 10638.09 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00784532 | 21.00 | 0.00784532 | 50.6897 | 7848.74 | 0.00 | 11263.59 | 11263.59 | 0.40241775 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61049.6 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 131315.431 | -999.000 | 5.752025 | 0.00558646 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4070 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.752025 | 6.92064617 | 4197.9300 | 999.8980 | 129.93571677 | 12.27 | 6.67 | 5.60 | 3054581.84 | 4.2990 | 4.298966 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 131315.43 | 93324.92 | 1.0000 | 6.92064617 | 5.752025 | 24.95 | 18.37 | 0.01052585 | 51887.3 | 11.42 | 11.42 | 0.00828381 | 32918.1 | 5.58589210 | 6.67 | 10.65 | 5.60 | 9753.446 | 121561.98 | 28.55 | 0.01651377 | 23.71 | 1.20008137 | 20.8636 | 24.00 | 0.00893749 | 24.00 | 0.00893744 | 48.0416 | 79819.27 | 0.00 | 145001.25 | 99914.84 | 6.92064617 | 24.95 | 18.38 | 0.01052585 | 51887.3 | 10.86 | 10.71 | 0.00794179 | 30935.3 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 271496.628 | 271496.628 | 5.752025 | 0.00599839 | 5088.503 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.752025 | 6.92064617 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 8.4252 | 10.578215 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 220589.78 | 249820.04 | 1.0000 | 6.92064617 | 5.752025 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 5.99777435 | 60.00 | 49.00 | 11.00 | 0.000 | 220589.78 | 4.60 | 0.00525715 | 4.60 | 1.20008137 | 20.8636 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 232806.30 | 232806.30 | 6.92064617 | 12.80 | 3.47 | 0.00109683 | 15631.2 | 46.21 | 17.72 | 0.00109683 | 49270.5 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 249829.261 | -999.000 | 9.040466 | 0.01062831 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5554 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.040466 | 10.87718998 | 4197.9300 | 999.8980 | 129.93571677 | 12.27 | 6.67 | 5.60 | 3054581.84 | 8.1788 | 8.178837 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 249829.26 | 171766.44 | 1.0000 | 10.87718998 | 9.040466 | 26.94 | 19.49 | 0.01114363 | 55494.3 | 11.43 | 12.09 | 0.00828381 | 34322.2 | 10.62723008 | 6.67 | 10.65 | 5.60 | 19535.967 | 230293.29 | 33.90 | 0.01651378 | 25.10 | 2.53804000 | 28.0742 | 24.00 | 0.00887816 | 24.00 | 0.00882778 | 47.4601 | 117639.48 | 0.00 | 271354.03 | 181428.11 | 10.87718998 | 26.94 | 19.50 | 0.01114363 | 55494.3 | 10.67 | 10.54 | 0.00786393 | 30547.3 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 26456.377 | 26456.377 | 2.712140 | 0.00058452 | 403.636 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.040466 | 10.87718998 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 0.8588 | 1.030809 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22485.78 | 26456.38 | 1.0000 | 3.26315699 | 2.712140 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.58446170 | 60.00 | 49.00 | 11.00 | 0.000 | 22485.78 | 4.60 | 0.00525715 | 4.60 | 2.53804000 | 93.5807 | 6.65 | 0.00228104 | 21.00 | 0.00773037 | 49.9550 | 10389.88 | 0.00 | 23785.49 | 23785.49 | 3.26315699 | 12.80 | 8.42 | 0.00506610 | 25652.5 | 19.99 | 11.59 | 0.00506610 | 32941.6 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2432309.936 | -999.000 | 83.353679 | 0.10347609 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2000 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 83.353679 | 100.28838787 | 4197.9300 | 999.8980 | 129.93571677 | 12.27 | 6.67 | 5.60 | 3054581.84 | 79.6282 | 79.628246 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2432309.94 | 1624378.56 | 1.0000 | 100.28838787 | 83.353679 | 27.33 | 19.87 | 0.01149035 | 56779.3 | 11.43 | 12.09 | 0.00828381 | 34322.2 | 103.46553182 | 6.67 | 10.65 | 5.60 | 180122.862 | 2252187.07 | 33.90 | 0.01651378 | 25.10 | 25.38036000 | 30.4490 | 24.00 | 0.00894702 | 24.00 | 0.00886791 | 47.6730 | 1038410.93 | 0.00 | 2630944.69 | 1715043.37 | 100.28838787 | 27.33 | 19.88 | 0.01149035 | 56779.3 | 10.66 | 10.54 | 0.00786737 | 30545.5 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 247908.094 | 247908.094 | 25.006104 | 0.00547723 | 3780.465 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 83.353679 | 100.28838787 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 8.0336 | 9.659144 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 210336.64 | 247908.09 | 1.0000 | 30.08651636 | 25.006104 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 5.47666768 | 60.00 | 49.00 | 11.00 | 0.000 | 210336.64 | 4.60 | 0.00525715 | 4.60 | 25.38036000 | 101.4967 | 20.76 | 0.00785756 | 21.00 | 0.00785756 | 50.7673 | 489472.87 | 0.00 | 222500.49 | 222500.49 | 30.08651636 | 12.80 | 8.63 | 0.00525715 | 26134.9 | 20.09 | 11.83 | 0.00525715 | 33530.2 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 241127.216 | -999.000 | 8.825580 | 0.01025811 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.4592 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.825580 | 10.61864582 | 4197.9300 | 999.8980 | 129.93571677 | 12.27 | 6.67 | 5.60 | 3054581.84 | 7.8940 | 7.893952 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 241127.22 | 166320.52 | 1.0000 | 10.61864582 | 8.825580 | 26.81 | 19.41 | 0.01109185 | 55234.1 | 11.43 | 12.09 | 0.00828381 | 34322.2 | 10.25706277 | 6.67 | 10.65 | 5.60 | 19071.609 | 222055.61 | 33.74 | 0.01651377 | 25.06 | 2.53804000 | 28.7578 | 24.00 | 0.00889136 | 24.00 | 0.00886576 | 47.6617 | 120902.55 | 0.00 | 262136.92 | 175728.14 | 10.61864582 | 26.81 | 19.42 | 0.01109185 | 55234.1 | 10.67 | 10.54 | 0.00786370 | 30547.6 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 24074.996 | 24074.996 | 2.647674 | 0.00053191 | 367.964 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.825580 | 10.61864582 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 0.7871 | 0.938025 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 10:50:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20607.29 | 24075.00 | 1.0000 | 3.18559375 | 2.647674 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.53185337 | 60.00 | 49.00 | 11.00 | 0.000 | 20607.29 | 4.60 | 0.00525715 | 4.60 | 2.53804000 | 95.8592 | 21.00 | 0.00796074 | 21.00 | 0.00793225 | 51.2432 | 59152.43 | 0.00 | 21799.51 | 21799.51 | 3.18559375 | 12.80 | 8.76 | 0.00536910 | 26417.5 | 19.54 | 11.71 | 0.00536910 | 33260.7 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 430942.183 | 310125.906 | 21.267529 | 0.01055375 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8785 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 460613.96 | 452077.73 | 0.9356 | -999.0 | -999.0 | 28.51 | 18.02 | 0.00862772 | 50684.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 460613.96 | 33.90 | 0.01651378 | 25.10 | 0.33837161 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 370214.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9336.222 | 6727.051 | 0.462352 | 0.00022864 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1472 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 9985.27 | 9589.52 | 0.9350 | -999.0 | -999.0 | 28.09 | 18.00 | 0.00877228 | 50623.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9985.27 | 31.21 | 0.01651378 | 24.41 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 8022.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 88786.140 | 63897.390 | 4.387135 | 0.00217437 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1732 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 94922.98 | 90977.62 | 0.9353 | -999.0 | -999.0 | 28.10 | 18.01 | 0.00878624 | 50666.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94922.98 | 31.21 | 0.01651378 | 24.41 | 0.15631366 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 76310.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9017.268 | 6491.136 | 0.445774 | 0.00022083 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1636 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9641.26 | 9247.52 | 0.9353 | -999.0 | -999.0 | 28.10 | 18.01 | 0.00878111 | 50657.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9641.26 | 31.41 | 0.01651378 | 24.46 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 7770.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 430942.183 | 430942.183 | 21.267529 | 0.01055375 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 430942.18 | 430942.18 | 1.0000 | 25.58838727 | 21.267529 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 430942.18 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5910 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9336.222 | 9336.222 | 0.462352 | 0.00022864 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9336.22 | 9336.22 | 1.0000 | 0.55628679 | 0.462352 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9336.22 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.3808 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 88786.140 | 88786.140 | 4.387135 | 0.00217437 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 88786.14 | 88786.14 | 1.0000 | 5.27845503 | 4.387135 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88786.14 | 4.60 | 0.00525715 | 4.60 | 0.15631366 | 3.5630 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9017.268 | 9017.268 | 0.445774 | 0.00022083 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9017.27 | 9017.27 | 1.0000 | 0.53634009 | 0.445774 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9017.27 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.5066 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14481.982 | 14481.982 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.267529 | 25.58838727 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14481.98 | 14481.98 | 1.0000 | 25.58838727 | 21.267529 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14481.98 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5910 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.267529 | 25.58838727 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 923684.25 | 1.0000 | 25.58838727 | 21.267529 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5910 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1026626.590 | 1026626.590 | 21.267529 | 0.02268206 | 19120.024 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.267529 | 25.58838727 | 4197.9300 | 999.8980 | 56.69930459 | 71.00 | 82.00 | 11.00 | 2618216.83 | 31.5316 | 40.000043 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 825564.44 | 923684.25 | 1.0000 | 25.58838727 | 21.267529 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 22.67974623 | 60.00 | 49.00 | 11.00 | 0.000 | 825564.44 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5910 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | 0.00 | 0.00 | 25.58838727 | 16.60 | 4.14 | 0.00008364 | 16892.1 | 16.60 | 4.14 | 0.00008364 | 16892.1 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.462352 | 0.55628679 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 1.0000 | 0.55628679 | 0.462352 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.01 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.3808 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6690.076 | 6690.076 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.387135 | 5.27845503 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6690.08 | 6690.08 | 1.0000 | 5.27845503 | 4.387135 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6690.08 | 4.60 | 0.00525715 | 4.60 | 0.15631366 | 3.5630 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.445774 | 0.53634009 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 1.0000 | 0.53634009 | 0.445774 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.01 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.5066 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 5.75 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 9.04 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 25.38 | 83.35 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 8.83 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4965.17 | 1832.50 | 1785.83 |
CORE_BOTTOM | 4731.50 | 213.00 | 0.00 |
CORE_MID | 2814.17 | 1399.17 | 0.00 |
CORE_TOP | 3029.67 | 1821.17 | 46.00 |
PERIMETER_BOT_ZN_3 | 4056.50 | 1313.83 | 41.17 |
PERIMETER_BOT_ZN_2 | 3752.17 | 1542.67 | 152.50 |
PERIMETER_BOT_ZN_1 | 4583.67 | 1001.00 | 227.33 |
PERIMETER_BOT_ZN_4 | 4939.17 | 851.50 | 308.17 |
PERIMETER_MID_ZN_3 | 3462.67 | 2393.17 | 367.17 |
PERIMETER_MID_ZN_2 | 2888.67 | 2036.83 | 391.83 |
PERIMETER_MID_ZN_1 | 4230.50 | 1520.33 | 407.50 |
PERIMETER_MID_ZN_4 | 3715.00 | 2020.83 | 347.33 |
PERIMETER_TOP_ZN_3 | 3678.50 | 2590.50 | 730.83 |
PERIMETER_TOP_ZN_2 | 3685.33 | 2426.50 | 633.83 |
PERIMETER_TOP_ZN_1 | 4180.83 | 1796.50 | 582.00 |
PERIMETER_TOP_ZN_4 | 3682.67 | 2278.00 | 547.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5587.50 | 4115.33 | 2515.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 126.33 | 0.00 | 22.17 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.17 | 0.00 | 0.17 |
PERIMETER_BOT_ZN_2 | 0.00 | 23.83 | 0.00 | 23.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 110.00 | 0.00 | 109.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 124.33 | 0.00 | 57.17 |
PERIMETER_MID_ZN_3 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.50 | 29.00 | 0.00 | 29.00 |
PERIMETER_MID_ZN_1 | 0.00 | 148.50 | 0.00 | 148.00 |
PERIMETER_MID_ZN_4 | 0.00 | 34.50 | 0.00 | 23.17 |
PERIMETER_TOP_ZN_3 | 10.00 | 8.00 | 2.33 | 7.50 |
PERIMETER_TOP_ZN_2 | 7.00 | 47.17 | 0.50 | 46.33 |
PERIMETER_TOP_ZN_1 | 4.00 | 101.17 | 0.67 | 99.33 |
PERIMETER_TOP_ZN_4 | 3.67 | 41.17 | 0.50 | 27.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.33 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 250.50 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 10.67 | 716.83 | 2.33 | 312.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.19 | 149.60 | 6779.02 | 1.032 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.95 | 134.35 | 6849.35 | 0.756 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.95 | 134.35 | 6849.35 | 0.685 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.95 | 134.35 | 6849.35 | 0.673 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.90 | 16.87 | 860.00 | 0.818 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 1.044 | 0.036 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.90 | 16.87 | 860.02 | 1.084 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 1.515 | 0.036 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.90 | 16.87 | 860.00 | 0.780 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 1.018 | 0.086 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.90 | 16.87 | 860.02 | 1.061 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 1.166 | 0.082 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.90 | 16.87 | 860.00 | 0.780 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 1.092 | 0.101 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.90 | 16.87 | 860.02 | 1.027 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 1.169 | 0.101 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.19 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.95 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.90 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.90 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31053.28 | 352631.04 | 22-JAN-00:10 | 1901542.21 | 03-AUG-15:50 |
Electricity:Building | 18082.82 | 224836.74 | 28-MAY-17:10 | 1111595.09 | 12-DEC-08:10 |
Electricity:Zone:BASEMENT | 654.67 | 14568.37 | 01-JAN-06:10 | 33452.42 | 02-JAN-08:10 |
InteriorLights:Electricity | 3406.51 | 15921.00 | 01-JAN-09:30 | 333223.40 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 230.28 | 1110.83 | 01-JAN-06:10 | 19994.87 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3406.51 | 15921.00 | 01-JAN-09:30 | 333223.40 | 25-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 496.41 | 5554.82 | 01-JAN-00:10 | 35163.43 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 206.80 | 997.60 | 01-JAN-06:10 | 17956.80 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4964.12 | 55548.06 | 01-JAN-00:10 | 351633.62 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 2068.05 | 9976.00 | 01-JAN-06:10 | 179568.00 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 496.41 | 5554.81 | 01-JAN-00:10 | 35163.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 206.80 | 997.60 | 01-JAN-06:10 | 17956.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 51.58 | 624.98 | 26-MAR-17:10 | 4415.21 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 15.21 | 59.60 | 01-JAN-09:30 | 2254.66 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 33.15 | 402.76 | 28-MAY-17:10 | 2845.33 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.71 | 38.41 | 01-JAN-07:50 | 1452.99 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 51.29 | 624.99 | 12-MAR-17:10 | 4415.29 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 14.92 | 59.60 | 01-JAN-07:50 | 2254.70 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 33.16 | 402.76 | 26-FEB-18:10 | 2845.32 | 01-FEB-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.73 | 38.41 | 01-JAN-09:30 | 1452.99 | 01-FEB-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 515.30 | 6249.81 | 26-MAR-17:10 | 44152.07 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 151.65 | 595.98 | 01-JAN-09:20 | 22546.55 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 331.28 | 4027.62 | 23-APR-17:10 | 28453.28 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 96.93 | 384.07 | 01-JAN-07:50 | 14529.86 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 512.68 | 6249.91 | 12-MAR-17:10 | 44152.90 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 149.03 | 595.99 | 01-JAN-07:50 | 22547.05 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 331.36 | 4027.59 | 26-FEB-18:10 | 28453.18 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 97.01 | 384.07 | 01-JAN-09:20 | 14529.86 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 51.53 | 624.98 | 26-MAR-17:10 | 4415.21 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 15.16 | 59.60 | 01-JAN-09:20 | 2254.66 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 33.13 | 402.76 | 23-APR-17:10 | 2845.33 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.69 | 38.41 | 01-JAN-07:50 | 1452.99 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 51.27 | 624.99 | 12-MAR-17:10 | 4415.29 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 14.90 | 59.60 | 01-JAN-07:50 | 2254.70 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 33.14 | 402.76 | 26-FEB-18:10 | 2845.32 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.70 | 38.41 | 01-JAN-09:20 | 1452.99 | 25-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7559.79 | 95221.34 | 01-JAN-06:10 | 385270.22 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 64.93 | 313.21 | 01-JAN-06:10 | 5637.70 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 156.88 | 1963.07 | 01-JAN-06:10 | 8054.86 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.00 | 14.47 | 01-JAN-06:10 | 260.44 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1568.80 | 19630.74 | 01-JAN-06:10 | 80548.60 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 29.99 | 144.69 | 01-JAN-06:10 | 2604.38 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 156.88 | 1963.07 | 01-JAN-06:10 | 8054.86 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.00 | 14.47 | 01-JAN-06:10 | 260.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.31 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.88 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.07 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.36 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.65 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.36 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 5118.13 | 74458.02 | 22-JAN-06:00 | 343842.09 | 30-AUG-16:00 |
ExteriorEquipment:Electricity | 1980.75 | 13680.83 | 01-JAN-00:10 | 127614.37 | 25-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 79.85 | 1421.04 | 01-JAN-00:10 | 5016.40 | 12-DEC-08:20 |
ElectricityPurchased:Facility | 31053.28 | 352631.04 | 22-JAN-00:10 | 1901542.21 | 03-AUG-15:50 |
ElectricityPurchased:Plant | 31053.28 | 352631.04 | 22-JAN-00:10 | 1901542.21 | 03-AUG-15:50 |
Cogeneration:ElectricityPurchased | 31053.28 | 352631.04 | 22-JAN-00:10 | 1901542.21 | 03-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31053.28 | 352631.04 | 22-JAN-00:10 | 1901542.21 | 03-AUG-15:50 |
ElectricityNet:Plant | 31053.28 | 352631.04 | 22-JAN-00:10 | 1901542.21 | 03-AUG-15:50 |
Cogeneration:ElectricityNet | 31053.28 | 352631.04 | 22-JAN-00:10 | 1901542.21 | 03-AUG-15:50 |
Fans:Electricity | 2139.59 | 41192.26 | 02-JAN-22:40 | 148215.82 | 18-APR-14:00 |
General:Fans:Electricity | 2139.59 | 41192.26 | 02-JAN-22:40 | 148215.82 | 18-APR-14:00 |
ExteriorLights:Electricity | 679.79 | 0.00 | 01-JAN-07:30 | 56280.70 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 679.79 | 0.00 | 01-JAN-07:30 | 56280.70 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 65.81 | 0.00 | 01-JAN-00:10 | 5613.05 | 02-JAN-10:10 |
Cooling:Electricity | 5469.92 | 29941.54 | 10-JAN-07:10 | 465448.05 | 07-AUG-12:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 5.05 | 0.00 | 01-JAN-00:10 | 5084.88 | 09-MAR-08:00 |
Electricity:Plant | 5271.64 | 6898.19 | 05-JAN-04:40 | 448093.06 | 06-OCT-14:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 2642.08 | 0.00 | 01-JAN-00:10 | 306226.29 | 06-OCT-14:00 |
HeatRejection:Electricity | 2005.08 | 3128.81 | 05-JAN-08:00 | 94088.97 | 02-JAN-10:50 |
General:HeatRejection:Electricity | 591.23 | 0.00 | 01-JAN-00:10 | 44840.69 | 10-MAY-04:30 |
Pumps:Electricity | 624.48 | 3360.94 | 01-JAN-00:10 | 48358.64 | 12-OCT-15:00 |
General:Pumps:Electricity | 624.48 | 3360.94 | 01-JAN-00:10 | 48358.64 | 12-OCT-15:00 |
WIRED_LTG_ELECTRICITY | 95.72 | 0.00 | 01-JAN-00:10 | 9363.58 | 25-OCT-07:20 |
WIRED_INT_EQUIP | 5334.88 | 88964.76 | 01-APR-00:10 | 305206.10 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 642.01 | 8146.58 | 01-JAN-00:20 | 866751.28 | 21-JAN-07:10 |
Gas:Plant | 642.01 | 8146.58 | 01-JAN-00:20 | 866751.28 | 21-JAN-07:10 |
WaterSystems:Gas | 482.83 | 8146.58 | 01-JAN-00:20 | 67990.36 | 23-JAN-13:00 |
Water Heater:WaterSystems:Gas | 482.83 | 8146.58 | 01-JAN-00:20 | 67990.36 | 23-JAN-13:00 |
Heating:Gas | 159.18 | 0.00 | 01-JAN-00:10 | 858604.70 | 21-JAN-07:10 |
Boiler:Heating:Gas | 159.18 | 0.00 | 01-JAN-00:10 | 858604.70 | 21-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 28899.81 | 143302.91 | 10-JAN-07:10 | 2637460.68 | 07-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 28899.81 | 143302.91 | 10-JAN-07:10 | 2637460.68 | 07-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 28899.81 | 143302.91 | 10-JAN-07:10 | 2637460.68 | 07-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 15531.64 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
Water:Plant | 15529.77 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 15531.64 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
MainsWater:Plant | 15529.77 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 1.88 | 0.00 | 01-JAN-00:10 | 0.00 | 09-MAR-08:00 |
Humidifier:Water | 1.88 | 0.00 | 01-JAN-00:10 | 0.00 | 09-MAR-08:00 |
MainsWater:HVAC | 1.88 | 0.00 | 01-JAN-00:10 | 0.00 | 09-MAR-08:00 |
Humidifier:MainsWater | 1.88 | 0.00 | 01-JAN-00:10 | 0.00 | 09-MAR-08:00 |
HeatRejection:Water | 13249.60 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
HeatRejection:MainsWater | 13249.60 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 441.90 | 0.00 | 01-JAN-00:10 | 603475.87 | 21-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 324.29 | 0.00 | 01-JAN-00:10 | 40614.72 | 24-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 324.29 | 0.00 | 01-JAN-00:10 | 40614.72 | 24-JAN-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 106511.18 | 217507.59 | 22-JAN-06:00 | 10422049.50 | 06-OCT-14:00 |
EnergyTransfer:Building | 21353.15 | 90882.04 | 22-JAN-07:40 | 1596954.90 | 30-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 789.16 | 0.00 | 01-JAN-00:10 | 81632.02 | 16-APR-23:00 |
Heating:EnergyTransfer | 45.72 | 0.00 | 01-JAN-00:10 | 281528.46 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 11.40 | 0.00 | 01-JAN-00:10 | 64802.81 | 16-JUL-13:40 |
Cooling:EnergyTransfer | 21307.43 | 90375.52 | 22-JAN-07:40 | 1596954.90 | 30-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 777.76 | 0.00 | 01-JAN-00:10 | 80086.57 | 02-JAN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 745.56 | 0.00 | 01-JAN-00:10 | 52859.13 | 13-NOV-10:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 745.56 | 0.00 | 01-JAN-00:10 | 52859.13 | 13-NOV-10:20 |
EnergyTransfer:Zone:CORE_MID | 5574.22 | 0.00 | 01-JAN-00:10 | 455916.31 | 29-NOV-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5574.22 | 0.00 | 01-JAN-00:10 | 455916.31 | 29-NOV-06:10 |
EnergyTransfer:Zone:CORE_TOP | 565.58 | 0.00 | 01-JAN-00:10 | 51986.88 | 07-JUL-15:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.41 | 0.00 | 01-JAN-00:10 | 44329.39 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 565.17 | 0.00 | 01-JAN-00:10 | 51986.88 | 07-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 104.15 | 0.00 | 01-JAN-00:10 | 11373.41 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 356.74 | 05-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 104.15 | 0.00 | 01-JAN-00:10 | 11373.41 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 84.47 | 0.00 | 01-JAN-00:10 | 11795.66 | 03-MAY-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 768.04 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 84.46 | 0.00 | 01-JAN-00:10 | 11795.66 | 03-MAY-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 131.39 | 0.00 | 01-JAN-00:10 | 15802.02 | 06-NOV-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.01 | 0.00 | 01-JAN-00:10 | 1699.41 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 131.38 | 0.00 | 01-JAN-00:10 | 15802.02 | 06-NOV-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 123.10 | 0.00 | 01-JAN-00:10 | 16738.05 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 123.10 | 0.00 | 01-JAN-00:10 | 16738.05 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 795.22 | 0.00 | 01-JAN-00:10 | 102438.29 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 7.01 | 0.00 | 01-JAN-00:10 | 75134.50 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 788.21 | 0.00 | 01-JAN-00:10 | 102438.29 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 726.63 | 0.00 | 01-JAN-00:10 | 120233.26 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 3.62 | 0.00 | 01-JAN-00:10 | 44080.50 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 723.02 | 0.00 | 01-JAN-00:10 | 120233.26 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1095.31 | 0.00 | 01-JAN-00:10 | 157382.62 | 01-JAN-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 2.36 | 0.00 | 01-JAN-00:10 | 44640.36 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1092.95 | 0.00 | 01-JAN-00:10 | 157382.62 | 01-JAN-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 767.69 | 0.00 | 01-JAN-00:10 | 139061.55 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.07 | 0.00 | 01-JAN-00:10 | 32637.87 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 765.62 | 0.00 | 01-JAN-00:10 | 139061.55 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 83.70 | 0.00 | 01-JAN-00:10 | 12426.61 | 06-FEB-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.16 | 0.00 | 01-JAN-00:10 | 12426.61 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 80.54 | 0.00 | 01-JAN-00:10 | 11214.29 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 75.46 | 0.00 | 01-JAN-00:10 | 12106.47 | 03-MAY-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.51 | 0.00 | 01-JAN-00:10 | 10268.23 | 06-FEB-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 73.95 | 0.00 | 01-JAN-00:10 | 12106.47 | 03-MAY-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 111.17 | 0.00 | 01-JAN-00:10 | 16200.31 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.53 | 0.00 | 01-JAN-00:10 | 13483.95 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 109.64 | 0.00 | 01-JAN-00:10 | 16200.31 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 79.38 | 0.00 | 01-JAN-00:10 | 14594.06 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.09 | 0.00 | 01-JAN-00:10 | 8391.41 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 78.29 | 0.00 | 01-JAN-00:10 | 14594.06 | 30-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 84.77 | 0.00 | 01-JAN-00:10 | 8253.67 | 10-OCT-15:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.63 | 0.00 | 01-JAN-00:10 | 3311.73 | 12-MAR-14:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 84.14 | 0.00 | 01-JAN-00:10 | 8253.67 | 10-OCT-15:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 606.69 | 0.00 | 01-JAN-00:10 | 65566.59 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.60 | 0.00 | 01-JAN-00:10 | 23775.86 | 20-FEB-13:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 601.09 | 0.00 | 01-JAN-00:10 | 65566.59 | 10-OCT-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 102.31 | 0.00 | 01-JAN-00:10 | 18689.41 | 07-JUL-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 5.13 | 0.00 | 01-JAN-00:10 | 16636.03 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 97.18 | 0.00 | 01-JAN-00:10 | 18689.41 | 07-JUL-14:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.20 | 871.04 | 05-JAN-08:00 | 7993.14 | 16-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.20 | 871.04 | 05-JAN-08:00 | 7993.14 | 16-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1273.64 | 1297.42 | 10-JAN-06:20 | 74502.71 | 16-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1273.64 | 1297.42 | 10-JAN-06:20 | 74502.71 | 16-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 124.29 | 2.08 | 07-JAN-11:30 | 7552.71 | 23-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.19 | 0.00 | 01-JAN-00:10 | 521.07 | 23-JAN-04:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 124.10 | 0.00 | 04-JAN-03:00 | 7552.71 | 23-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7169.07 | 87814.72 | 22-JAN-08:50 | 368416.51 | 03-AUG-20:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7169.07 | 87814.72 | 22-JAN-08:50 | 368416.51 | 03-AUG-20:00 |
EnergyTransfer:Plant | 54743.52 | 0.00 | 01-JAN-00:10 | 6394544.16 | 16-AUG-14:00 |
WaterSystems:EnergyTransfer | 324.29 | 0.00 | 01-JAN-00:10 | 40614.72 | 24-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 324.29 | 0.00 | 01-JAN-00:10 | 40614.72 | 24-JAN-12:30 |
EnergyTransfer:HVAC | 30414.50 | 126110.42 | 22-JAN-07:40 | 3106163.01 | 07-AUG-13:00 |
HeatingCoils:EnergyTransfer | 117.60 | 0.00 | 01-JAN-00:10 | 589887.63 | 21-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 117.60 | 0.00 | 01-JAN-00:10 | 589887.63 | 21-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 117.60 | 0.00 | 01-JAN-00:10 | 589887.63 | 21-DEC-07:10 |
CoolingCoils:EnergyTransfer | 26213.15 | 117667.05 | 10-JAN-07:10 | 2489948.28 | 07-AUG-14:40 |
HeatRecoveryForHeating:EnergyTransfer | 119.44 | 0.00 | 01-JAN-00:10 | 464849.57 | 20-DEC-08:00 |
HeatRecoveryForCooling:EnergyTransfer | 3964.32 | 0.00 | 01-JAN-00:10 | 918357.63 | 07-OCT-08:00 |
LoopToLoop:EnergyTransfer | 17413.87 | 0.00 | 01-JAN-00:10 | 2002157.97 | 07-AUG-14:40 |
Boilers:EnergyTransfer | 116.18 | 0.00 | 01-JAN-00:10 | 714651.07 | 21-JAN-07:10 |
Chillers:EnergyTransfer | 17123.55 | 0.00 | 01-JAN-00:10 | 2096866.76 | 16-AUG-14:00 |
HeatRejection:EnergyTransfer | 19765.63 | 0.00 | 01-JAN-00:10 | 2399938.74 | 16-AUG-14:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 11.396 | -777.777 | 0.000 | 0.000 | 92.661 | 230.277 | 424.397 | 0.000 | 0.000 | 0.000 | 19.046 | 0.000 | 0.000 | 0.000 | 0.000 | -0.005 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -745.559 | 0.000 | 0.000 | 83.516 | 206.805 | 289.609 | 0.000 | 0.000 | 0.000 | 165.630 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5574.203 | 0.000 | 0.000 | 841.662 | 2068.045 | 2896.074 | 0.000 | 0.000 | 0.000 | 0.046 | 0.000 | 0.000 | 0.000 | 0.000 | -231.578 |
CORE_TOP | 0.000 | 0.000 | 0.409 | -565.164 | 0.000 | 0.000 | 85.439 | 206.805 | 289.607 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -17.096 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -104.153 | 0.000 | 0.000 | 10.602 | 15.211 | 36.365 | 38.096 | 0.000 | 0.425 | 42.062 | 0.000 | -36.781 | 0.000 | -1.828 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.005 | -84.463 | 0.000 | 0.000 | 6.836 | 9.713 | 23.435 | 56.195 | 0.000 | 0.296 | 10.722 | 0.000 | -21.563 | 0.000 | -1.177 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.007 | -131.382 | 0.000 | 0.000 | 10.513 | 14.924 | 36.365 | 94.075 | 0.000 | 0.401 | 10.848 | 0.000 | -33.826 | 0.000 | -1.926 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -123.097 | 0.000 | 0.000 | 6.784 | 9.725 | 23.435 | 53.406 | 0.000 | 0.245 | 58.785 | 0.000 | -27.846 | 0.000 | -1.436 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 7.014 | -788.188 | 0.000 | 0.000 | 108.733 | 151.648 | 363.647 | 396.283 | 0.000 | 9.174 | 108.069 | 0.000 | -321.179 | 0.000 | -35.201 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 3.617 | -722.998 | 0.000 | 0.000 | 51.122 | 96.933 | 234.348 | 561.774 | 0.000 | 5.767 | 0.006 | 0.000 | -201.791 | 0.000 | -24.760 | -4.012 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 2.360 | -1092.919 | 0.000 | 0.000 | 105.753 | 149.031 | 363.653 | 940.120 | 0.000 | 8.320 | 0.013 | 0.000 | -324.552 | 0.000 | -41.554 | -110.211 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.071 | -765.598 | 0.000 | 0.000 | 69.819 | 97.014 | 234.347 | 552.438 | 0.000 | 5.591 | 59.222 | 0.000 | -228.306 | 0.000 | -26.596 | -0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 3.163 | -80.538 | 0.000 | 0.000 | 10.967 | 15.163 | 36.365 | 39.300 | 0.000 | 1.067 | 9.038 | 0.000 | -30.441 | 0.000 | -4.083 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.512 | -73.943 | 0.000 | 0.000 | 6.991 | 9.693 | 23.435 | 56.025 | 0.000 | 0.676 | 0.002 | 0.000 | -19.319 | 0.000 | -2.890 | -2.181 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.529 | -109.638 | 0.000 | 0.000 | 10.667 | 14.902 | 36.365 | 93.790 | 0.000 | 0.973 | 0.001 | 0.000 | -31.034 | 0.000 | -4.861 | -12.694 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 1.087 | -78.288 | 0.000 | 0.000 | 7.045 | 9.701 | 23.435 | 55.013 | 0.000 | 0.676 | 6.308 | 0.000 | -21.848 | 0.000 | -3.128 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -140.198 | 0.000 | 0.000 | 0.000 | 2.999 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.682 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1273.642 | 0.000 | 0.000 | 0.000 | 29.994 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -295.158 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.185 | -124.103 | 0.000 | 0.000 | 0.000 | 2.999 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -32.962 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7169.077 | 0.000 | 0.000 | 0.000 | 64.928 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -390.708 |
GROUNDFLOOR_PLENUM | 0.633 | -84.138 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.705 | 86.798 | 0.000 | 0.000 | 0.000 | -3.998 | 0.000 |
MIDFLOOR_PLENUM | 5.604 | -601.075 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.145 | 648.249 | 0.000 | 0.000 | 0.000 | -65.923 | 0.000 |
TOPFLOOR_PLENUM | 5.130 | -97.173 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.157 | 97.653 | 0.000 | 0.000 | 0.000 | -6.767 | 0.000 |
Total Facility | 11.368 | -782.386 | 34.355 | -20524.928 | 0.000 | 0.000 | 1509.109 | 3406.510 | 14676.305 | 2936.515 | 0.000 | 48.619 | 1322.499 | 0.000 | -1298.485 | 0.000 | -226.129 | -1113.291 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 16-APR-23:00 | 0.00 | 0.00 | 0.00 | -125372.84 | 0.00 | 0.00 | 0.00 | 1226.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 110688.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 06-SEP-03:02 | 0.00 | 0.00 | 0.00 | -97048.34 | 0.00 | 0.00 | 0.00 | 1101.59 | 5937.65 | 0.00 | 0.00 | 0.00 | 90009.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 12-MAY-04:12 | 0.00 | 0.00 | 0.00 | -881821.86 | 0.00 | 0.00 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 800413.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-JUN-03:02 | 0.00 | 0.00 | 0.00 | -89803.65 | 0.00 | 0.00 | 0.00 | 1101.59 | 5937.62 | 0.00 | 0.00 | 0.00 | 82764.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 20-AUG-13:51 | 0.00 | 0.00 | 0.00 | -14883.72 | 0.00 | 0.00 | 42.75 | 59.60 | 720.18 | 6624.33 | 0.00 | 321.08 | 7115.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-08:41 | 0.00 | 0.00 | 0.00 | -20006.67 | 0.00 | 0.00 | 20.87 | 38.41 | 464.11 | 14433.90 | 0.00 | 0.00 | 5056.48 | 0.00 | -0.00 | 0.00 | -7.11 | 0.00 |
PERIMETER_BOT_ZN_1 | 11-NOV-11:42 | 0.00 | 0.00 | 0.00 | -19728.06 | 0.00 | 0.00 | 34.69 | 59.60 | 720.19 | 20505.78 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -62.06 | -1530.14 |
PERIMETER_BOT_ZN_4 | 29-MAY-16:41 | 0.00 | 0.00 | 0.00 | -25085.58 | 0.00 | 0.00 | 19.39 | 38.41 | 464.11 | 13244.25 | 0.00 | 30.61 | 11288.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 10-SEP-15:11 | 0.00 | 0.00 | 0.00 | -135615.50 | 0.00 | 0.00 | 438.70 | 595.98 | 7201.84 | 49246.90 | 0.00 | 2665.16 | 75466.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10-SEP-08:32 | 0.00 | 0.00 | 0.00 | -195277.20 | 0.00 | 0.00 | 226.79 | 384.07 | 4641.14 | 139082.61 | 0.00 | 1777.04 | 49165.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 01-JAN-13:11 | 0.00 | 0.00 | 0.00 | -191372.92 | 0.00 | 0.00 | 309.21 | 595.99 | 7201.95 | 220868.22 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1629.04 | -35973.41 |
PERIMETER_MID_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -215961.93 | 0.00 | 0.00 | 202.34 | 384.07 | 4641.11 | 130450.27 | 0.00 | 866.03 | 79418.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 10-SEP-15:11 | 0.00 | 0.00 | 0.00 | -16109.00 | 0.00 | 0.00 | 40.56 | 59.60 | 720.18 | 4651.40 | 0.00 | 301.26 | 10335.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 10-SEP-08:32 | 0.00 | 0.00 | 0.00 | -19817.95 | 0.00 | 0.00 | 22.24 | 38.41 | 464.11 | 13820.24 | 0.00 | 210.37 | 5262.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-JAN-14:31 | 0.00 | 0.00 | 0.00 | -20980.77 | 0.00 | 0.00 | 31.15 | 59.60 | 720.19 | 18293.56 | 0.00 | 0.00 | 2047.20 | 0.00 | -0.00 | 0.00 | -170.94 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -22959.05 | 0.00 | 0.00 | 19.01 | 38.41 | 464.11 | 12916.09 | 0.00 | 96.24 | 9425.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-18:20 | 0.00 | 0.00 | 0.00 | -7993.14 | 0.00 | 0.00 | 0.00 | 15.98 | 7794.42 | 0.00 | 0.00 | 0.00 | 182.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-18:20 | 0.00 | 0.00 | 0.00 | -74502.71 | 0.00 | 0.00 | 0.00 | 159.77 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3601.28 |
DATACENTER_TOP_ZN_6 | 23-APR-18:08 | 0.00 | 0.00 | 0.00 | -7552.71 | 0.00 | 0.00 | 0.00 | 15.98 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -257.69 |
DATACENTER_BASEMENT_ZN_6 | 28-AUG-21:02 | 0.00 | 0.00 | 0.00 | -369934.30 | 0.00 | 0.00 | 0.00 | 626.41 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10324.64 |
GROUNDFLOOR_PLENUM | 10-OCT-05:02 | 0.00 | -12093.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12158.23 | 0.00 | -0.00 | 0.00 | -64.51 | 0.00 |
MIDFLOOR_PLENUM | 07-OCT-05:01 | 0.00 | -103058.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.28 | 102984.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 07-JUL-14:50 | 0.00 | -18688.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.94 | 18562.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-AUG-04:11 | 0.00 | 53667.61 | 0.00 | -1966789.67 | 0.00 | 0.00 | 0.00 | 40884.25 | 587299.42 | 0.00 | 0.00 | 0.00 | 1331158.17 | 0.00 | -31751.48 | 0.00 | -14468.29 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 28-MAY-17:14 | 0.00 | 0.00 | 137511.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1226.62 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -152195.30 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-05:21 | 0.00 | 0.00 | 54285.99 | -0.00 | 0.00 | 0.00 | 0.00 | 2203.18 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -62426.79 |
PERIMETER_BOT_ZN_3 | 05-JAN-06:01 | 0.00 | 0.00 | 3018.78 | -0.00 | 0.00 | 0.00 | 140.64 | 250.52 | 960.25 | 0.00 | 0.00 | 0.00 | 2369.46 | 0.00 | -6655.66 | 0.00 | -83.99 | 0.00 |
PERIMETER_BOT_ZN_2 | 21-JAN-06:03 | 0.00 | 0.00 | 1997.81 | -0.00 | 0.00 | 0.00 | 90.78 | 161.44 | 618.82 | 0.00 | 0.00 | 0.00 | 1606.88 | 0.00 | -4372.78 | 0.00 | -102.95 | 0.00 |
PERIMETER_BOT_ZN_1 | 06-FEB-06:01 | 0.00 | 0.00 | 5508.07 | -0.00 | 0.00 | 0.00 | 142.82 | 250.52 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5321.88 | 0.00 | -53.99 | -1485.80 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-FEB-05:11 | 0.00 | 0.00 | 106739.14 | -0.00 | 0.00 | 0.00 | 0.00 | 2766.31 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47408.31 | 0.00 | -4342.21 | -65210.54 |
PERIMETER_MID_ZN_2 | 06-FEB-05:11 | 0.00 | 0.00 | 94069.21 | -0.00 | 0.00 | 0.00 | 0.00 | 1782.71 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -32287.32 | 0.00 | -2984.93 | -65384.36 |
PERIMETER_MID_ZN_1 | 06-FEB-05:11 | 0.00 | 0.00 | 109871.78 | -0.00 | 0.00 | 0.00 | 0.00 | 2766.37 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -51136.97 | 0.00 | -4831.05 | -64125.84 |
PERIMETER_MID_ZN_4 | 06-FEB-05:11 | 0.00 | 0.00 | 81172.07 | -0.00 | 0.00 | 0.00 | 0.00 | 1782.71 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34164.04 | 0.00 | -3148.39 | -50447.00 |
PERIMETER_TOP_ZN_3 | 05-FEB-07:03 | 0.00 | 0.00 | 13698.26 | -0.00 | 0.00 | 0.00 | 88.68 | 125.26 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6047.02 | 0.00 | -2041.93 | -6543.44 |
PERIMETER_TOP_ZN_2 | 06-FEB-05:21 | 0.00 | 0.00 | 12975.68 | -0.00 | 0.00 | 0.00 | 0.00 | 178.27 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2595.70 | 0.00 | -301.92 | -10736.79 |
PERIMETER_TOP_ZN_1 | 05-FEB-07:03 | 0.00 | 0.00 | 15296.04 | -0.00 | 0.00 | 0.00 | 88.24 | 125.26 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5933.19 | 0.00 | -2084.28 | -8212.26 |
PERIMETER_TOP_ZN_4 | 06-FEB-04:01 | 0.00 | 0.00 | 12462.93 | -0.00 | 0.00 | 0.00 | 0.00 | 89.14 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2794.41 | 0.00 | -354.25 | -9883.87 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 23-JAN-04:50 | 0.00 | 0.00 | 521.07 | 0.00 | 0.00 | 0.00 | 0.00 | 15.98 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2485.65 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 25-DEC-09:41 | 12877.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -429.29 | -12448.49 |
MIDFLOOR_PLENUM | 16-JAN-10:17 | 68529.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2677.97 | -65851.04 |
TOPFLOOR_PLENUM | 06-FEB-06:12 | 18935.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -182.50 | -18752.74 |
Total Facility | 06-FEB-06:01 | -610890.08 | 586331.24 | 461881.28 | -586331.24 | 0.00 | 0.00 | 19621.86 | 37024.82 | 379706.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -204903.29 | 0.00 | -6936.70 | -75504.26 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.7520 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.7520 | 0.2086 | 1.0000 | 1.2001 | 0.2086 | ||
VAV_BOT WITH REHEAT | 10.0092 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 9.0405 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 93.0085 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 83.3537 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.5286 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.8256 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.2675 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.2675 | 0.0159 | 1.0000 | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4624 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4624 | 0.0338 | 1.0000 | 0.0156 | 0.0338 | ||
AIRLOOP DATACENTER MID | 4.3871 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.3871 | 0.0356 | 1.0000 | 0.1563 | 0.0356 | ||
AIRLOOP DATACENTER TOP | 0.4458 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4458 | 0.0351 | 1.0000 | 0.0156 | 0.0351 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.7520 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.7520 | 1.0000 | 1.0000 | 1.2001 | 0.2086 | ||
VAV_BOT WITH REHEAT | 5.0046 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.8315 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 46.5043 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 27.4162 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.7643 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.7954 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.2675 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.2675 | 1.0000 | 1.0000 | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4624 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4624 | 1.0000 | 1.0000 | 0.0156 | 0.0338 | ||
AIRLOOP DATACENTER MID | 4.3871 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.3871 | 1.0000 | 1.0000 | 0.1563 | 0.0356 | ||
AIRLOOP DATACENTER TOP | 0.4458 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4458 | 1.0000 | 1.0000 | 0.0156 | 0.0351 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.7520 | 5.7520 | 5.7520 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8136 | 5.8136 | 1.8952 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 54.4648 | 54.4648 | 18.5180 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3938 | 5.3938 | 1.8824 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8813 | 0.8813 | 0.2380 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0204 | 1.0204 | 0.2041 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0120 | 1.0120 | 0.2378 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2819 | 1.2819 | 0.2564 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.9735 | 7.9735 | 2.3203 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.3855 | 10.3855 | 2.0771 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.2776 | 9.2776 | 2.3194 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.9072 | 10.9072 | 2.1814 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9050 | 0.9050 | 0.2362 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0453 | 1.0453 | 0.2091 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0259 | 1.0259 | 0.2360 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1586 | 1.1586 | 0.2317 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4624 | 0.4624 | 0.4624 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.3871 | 4.3871 | 4.3871 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4458 | 0.4458 | 0.4458 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.2675 | 21.2675 | 21.2675 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.7520 | 5.7520 | 5.7520 | 5.7520 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 10.0092 | 9.0405 | 10.0092 | 2.8315 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 93.0085 | 83.3537 | 93.0085 | 27.4162 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.5286 | 8.8256 | 9.5286 | 2.7954 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2675 | 21.2675 | 21.2675 | 21.2675 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4624 | 0.4624 | 0.4624 | 0.4624 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3871 | 4.3871 | 4.3871 | 4.3871 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4458 | 0.4458 | 0.4458 | 0.4458 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.7520 | 5.7520 | 5.7520 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9068 | 2.9068 | 1.8952 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.2324 | 27.2324 | 18.5180 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6969 | 2.6969 | 1.8824 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4407 | 0.4407 | 0.2380 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5102 | 0.5102 | 0.2041 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5060 | 0.5060 | 0.2378 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6410 | 0.6410 | 0.2564 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9867 | 3.9867 | 2.3203 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1928 | 5.1928 | 2.0771 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6388 | 4.6388 | 2.3194 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4536 | 5.4536 | 2.1814 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4525 | 0.4525 | 0.2362 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5227 | 0.5227 | 0.2091 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5129 | 0.5129 | 0.2360 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5793 | 0.5793 | 0.2317 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4624 | 0.4624 | 0.4624 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.3871 | 4.3871 | 4.3871 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4458 | 0.4458 | 0.4458 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.2675 | 21.2675 | 21.2675 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.7520 | 5.7520 | 5.7520 | 5.7520 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 5.0046 | 2.8315 | 2.8315 | 2.8315 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 46.5043 | 27.4162 | 27.4162 | 27.4162 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.7643 | 2.7954 | 2.7954 | 2.7954 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2675 | 21.2675 | 21.2675 | 21.2675 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4624 | 0.4624 | 0.4624 | 0.4624 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3871 | 4.3871 | 4.3871 | 4.3871 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4458 | 0.4458 | 0.4458 | 0.4458 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:51
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 2.33 |
Number of hours cooling loads not met | 312.33 |
Number of hours not met | 314.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 159.18 | 858604.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2642.08 | 306226.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 2827.84 | 159221.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3406.51 | 333223.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 679.79 | 56280.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.88 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 79.85 | 5016.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2139.59 | 148215.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 624.48 | 48358.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 591.23 | 44840.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 1413.85 | 49248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 5.05 | 5084.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 65.81 | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 482.83 | 67990.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.31 | 31053.28 |
Natural Gas | 0.00 | 642.01 |
Additional | 0.00 | 0.00 |
Total | 14676.31 | 31695.29 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 73.54 |
Space Heating | 0.00 |
Space Cooling | 118.09 |
Fans (All) | 46.19 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.84 |
Miscellaneous (All) | 670.40 |
Subtotal | 670.40 |
Natural Gas [MJ/m2] | |
Space Heating | 3.44 |
Service Water Heating | 10.42 |
Miscellaneous (All) | 13.86 |
Subtotal | 13.86 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.75 |
Space Heating | 0.50 |
Space Cooling | 17.26 |
Fans (All) | 6.75 |
Service Water Heating | 1.52 |
Receptacle Equipment | 46.30 |
Miscellaneous | 16.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2676. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.530191E+11 |
February | 0.000 | 0.279359E+11 |
March | 0.000 | 0.244574E+11 |
April | 0.000 | 0.124578E+10 |
May | 0.000 | 0.110717E+10 |
June | 0.000 | 0.922120E+09 |
July | 0.000 | 0.142155E+10 |
August | 0.000 | 0.978295E+09 |
September | 0.000 | 0.150109E+10 |
October | 0.000 | 0.201230E+10 |
November | 0.000 | 0.567381E+10 |
December | 0.000 | 0.389102E+11 |
Annual Sum or Average | 0.159185E+12 | |
Minimum of Months | 0.000 | 0.922120E+09 |
Maximum of Months | 0.000 | 0.530191E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.530191E+11 |
February | 0.000 | 0.279359E+11 |
March | 0.000 | 0.244574E+11 |
April | 0.000 | 0.124578E+10 |
May | 0.000 | 0.110717E+10 |
June | 0.000 | 0.922120E+09 |
July | 0.000 | 0.142155E+10 |
August | 0.000 | 0.978295E+09 |
September | 0.000 | 0.150109E+10 |
October | 0.000 | 0.201230E+10 |
November | 0.000 | 0.567381E+10 |
December | 0.000 | 0.389102E+11 |
Annual Sum or Average | 0.159185E+12 | |
Minimum of Months | 0.000 | 0.922120E+09 |
Maximum of Months | 0.000 | 0.530191E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.530191E+11 |
February | 0.000 | 0.279359E+11 |
March | 0.000 | 0.244574E+11 |
April | 0.000 | 0.124578E+10 |
May | 0.000 | 0.110717E+10 |
June | 0.000 | 0.922120E+09 |
July | 0.000 | 0.142155E+10 |
August | 0.000 | 0.978295E+09 |
September | 0.000 | 0.150109E+10 |
October | 0.000 | 0.201230E+10 |
November | 0.000 | 0.567381E+10 |
December | 0.000 | 0.389102E+11 |
Annual Sum or Average | 0.159185E+12 | |
Minimum of Months | 0.000 | 0.922120E+09 |
Maximum of Months | 0.000 | 0.530191E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.530191E+11 |
February | 0.000 | 0.279359E+11 |
March | 0.000 | 0.244574E+11 |
April | 0.000 | 0.124578E+10 |
May | 0.000 | 0.110717E+10 |
June | 0.000 | 0.922120E+09 |
July | 0.000 | 0.142155E+10 |
August | 0.000 | 0.978295E+09 |
September | 0.000 | 0.150109E+10 |
October | 0.000 | 0.201230E+10 |
November | 0.000 | 0.567381E+10 |
December | 0.000 | 0.389102E+11 |
Annual Sum or Average | 0.159185E+12 | |
Minimum of Months | 0.000 | 0.922120E+09 |
Maximum of Months | 0.000 | 0.530191E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.530191E+11 |
February | 0.000 | 0.279359E+11 |
March | 0.000 | 0.244574E+11 |
April | 0.000 | 0.124578E+10 |
May | 0.000 | 0.110717E+10 |
June | 0.000 | 0.922120E+09 |
July | 0.000 | 0.142155E+10 |
August | 0.000 | 0.978295E+09 |
September | 0.000 | 0.150109E+10 |
October | 0.000 | 0.201230E+10 |
November | 0.000 | 0.567381E+10 |
December | 0.000 | 0.389102E+11 |
Annual Sum or Average | 0.159185E+12 | |
Minimum of Months | 0.000 | 0.922120E+09 |
Maximum of Months | 0.000 | 0.530191E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.530191E+11 |
February | 0.000 | 0.279359E+11 |
March | 0.000 | 0.244574E+11 |
April | 0.000 | 0.124578E+10 |
May | 0.000 | 0.110717E+10 |
June | 0.000 | 0.922120E+09 |
July | 0.000 | 0.142155E+10 |
August | 0.000 | 0.978295E+09 |
September | 0.000 | 0.150109E+10 |
October | 0.000 | 0.201230E+10 |
November | 0.000 | 0.567381E+10 |
December | 0.000 | 0.389102E+11 |
Annual Sum or Average | 0.159185E+12 | |
Minimum of Months | 0.000 | 0.922120E+09 |
Maximum of Months | 0.000 | 0.530191E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.530191E+11 |
February | 0.000 | 0.279359E+11 |
March | 0.000 | 0.244574E+11 |
April | 0.000 | 0.124578E+10 |
May | 0.000 | 0.110717E+10 |
June | 0.000 | 0.922120E+09 |
July | 0.000 | 0.142155E+10 |
August | 0.000 | 0.978295E+09 |
September | 0.000 | 0.150109E+10 |
October | 0.000 | 0.201230E+10 |
November | 0.000 | 0.567381E+10 |
December | 0.000 | 0.389102E+11 |
Annual Sum or Average | 0.159185E+12 | |
Minimum of Months | 0.000 | 0.922120E+09 |
Maximum of Months | 0.000 | 0.530191E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.530191E+11 |
February | 0.000 | 0.279359E+11 |
March | 0.000 | 0.244574E+11 |
April | 0.000 | 0.124578E+10 |
May | 0.000 | 0.110717E+10 |
June | 0.000 | 0.922120E+09 |
July | 0.000 | 0.142155E+10 |
August | 0.000 | 0.978295E+09 |
September | 0.000 | 0.150109E+10 |
October | 0.000 | 0.201230E+10 |
November | 0.000 | 0.567381E+10 |
December | 0.000 | 0.389102E+11 |
Annual Sum or Average | 0.159185E+12 | |
Minimum of Months | 0.000 | 0.922120E+09 |
Maximum of Months | 0.000 | 0.530191E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.530191E+11 |
February | 0.000 | 0.279359E+11 |
March | 0.000 | 0.244574E+11 |
April | 0.000 | 0.124578E+10 |
May | 0.000 | 0.110717E+10 |
June | 0.000 | 0.922120E+09 |
July | 0.000 | 0.142155E+10 |
August | 0.000 | 0.978295E+09 |
September | 0.000 | 0.150109E+10 |
October | 0.000 | 0.201230E+10 |
November | 0.000 | 0.567381E+10 |
December | 0.000 | 0.389102E+11 |
Annual Sum or Average | 0.159185E+12 | |
Minimum of Months | 0.000 | 0.922120E+09 |
Maximum of Months | 0.000 | 0.530191E+11 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.610772E+11 | 119027.67 | 09-JAN-01:11 | 12.67 | 12.48 | 0.566930E+10 | 7499.43 | 12-JAN-10:09 | 18.17 | 17.41 |
February | 0.540332E+11 | 121304.44 | 13-FEB-01:12 | 8.57 | 4.53 | 0.514172E+10 | 7499.11 | 09-FEB-10:00 | 15.00 | 12.67 |
March | 0.626773E+11 | 119603.42 | 19-MAR-15:31 | 17.37 | 11.05 | 0.613509E+10 | 7499.71 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.583496E+11 | 125432.28 | 16-APR-23:00 | 14.20 | 11.82 | 0.545245E+10 | 7499.33 | 12-APR-09:20 | 21.23 | 16.80 |
May | 0.637035E+11 | 112154.93 | 29-MAY-21:00 | 26.10 | 23.69 | 0.590476E+10 | 7498.82 | 26-MAY-09:20 | 28.33 | 25.47 |
June | 0.633767E+11 | 109630.55 | 25-JUN-21:13 | 25.77 | 22.72 | 0.588440E+10 | 7498.82 | 29-JUN-09:20 | 29.63 | 25.44 |
July | 0.653941E+11 | 109689.25 | 09-JUL-20:50 | 27.30 | 24.64 | 0.547689E+10 | 7498.81 | 14-JUL-09:20 | 24.27 | 23.35 |
August | 0.744562E+11 | 115652.12 | 20-AUG-04:57 | 23.00 | 16.70 | 0.613977E+10 | 7498.77 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.676610E+11 | 112346.49 | 17-SEP-21:43 | 26.10 | 24.11 | 0.545485E+10 | 7498.79 | 15-SEP-09:20 | 26.83 | 23.91 |
October | 0.711889E+11 | 118398.64 | 17-OCT-04:11 | 17.33 | 12.71 | 0.567398E+10 | 7499.08 | 17-OCT-13:20 | 22.33 | 15.55 |
November | 0.689606E+11 | 124431.39 | 23-NOV-15:08 | 18.05 | 9.69 | 0.561808E+10 | 7499.18 | 13-NOV-14:20 | 23.30 | 17.14 |
December | 0.668865E+11 | 122206.85 | 03-DEC-20:52 | 12.00 | 9.79 | 0.547502E+10 | 7499.57 | 08-DEC-10:00 | 24.00 | 18.76 |
Annual Sum or Average | 0.777765E+12 | 0.680263E+11 | ||||||||
Minimum of Months | 0.540332E+11 | 109630.55 | 8.57 | 4.53 | 0.514172E+10 | 7498.77 | 15.00 | 12.67 | ||
Maximum of Months | 0.744562E+11 | 125432.28 | 27.30 | 24.64 | 0.613977E+10 | 7499.71 | 29.63 | 25.47 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.501032E+11 | 96147.72 | 01-JAN-03:31 | 17.00 | 14.71 | 0.504951E+10 | 6734.80 | 11-JAN-10:09 | 14.67 | 12.05 |
February | 0.478873E+11 | 90176.27 | 28-FEB-05:12 | 18.50 | 18.07 | 0.459189E+10 | 6734.71 | 07-FEB-10:30 | 14.40 | 10.15 |
March | 0.597219E+11 | 93800.91 | 28-MAR-03:02 | 19.00 | 18.65 | 0.549166E+10 | 6734.94 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.640182E+11 | 93999.27 | 04-APR-03:02 | 16.87 | 14.68 | 0.487642E+10 | 6734.88 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.619592E+11 | 96688.05 | 31-MAY-03:02 | 23.22 | 21.33 | 0.528041E+10 | 6734.43 | 22-MAY-09:09 | 26.93 | 23.34 |
June | 0.667808E+11 | 91749.64 | 06-JUN-04:12 | 22.97 | 22.12 | 0.526191E+10 | 6734.43 | 01-JUN-13:09 | 23.90 | 20.93 |
July | 0.717547E+11 | 82320.14 | 12-JUL-04:11 | 23.50 | 23.01 | 0.488599E+10 | 6734.42 | 13-JUL-09:30 | 24.45 | 23.19 |
August | 0.787722E+11 | 83395.11 | 01-AUG-05:02 | 23.90 | 22.91 | 0.548881E+10 | 6734.43 | 07-AUG-09:09 | 27.50 | 25.10 |
September | 0.603088E+11 | 97055.40 | 06-SEP-03:02 | 24.70 | 23.43 | 0.487476E+10 | 6734.42 | 26-SEP-09:09 | 22.80 | 22.01 |
October | 0.646726E+11 | 95220.80 | 03-OCT-03:02 | 22.00 | 19.94 | 0.507166E+10 | 6734.76 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.600835E+11 | 96406.59 | 20-NOV-04:02 | 16.37 | 14.27 | 0.502492E+10 | 6734.72 | 13-NOV-10:09 | 16.47 | 13.02 |
December | 0.594973E+11 | 95286.42 | 04-DEC-04:01 | 6.00 | 5.05 | 0.489476E+10 | 6784.94 | 20-DEC-10:09 | 3.33 | 0.09 |
Annual Sum or Average | 0.745560E+12 | 0.607927E+11 | ||||||||
Minimum of Months | 0.478873E+11 | 82320.14 | 6.00 | 5.05 | 0.459189E+10 | 6734.42 | 3.33 | 0.09 | ||
Maximum of Months | 0.787722E+11 | 97055.40 | 24.70 | 23.43 | 0.549166E+10 | 6784.94 | 27.50 | 25.10 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379649E+11 | 79199.59 | 20-JAN-05:11 | 17.00 | 17.00 | 0.491716E+10 | 6734.75 | 05-JAN-14:09 | 14.17 | 9.62 |
February | 0.354060E+11 | 81034.76 | 27-FEB-06:02 | 17.70 | 17.70 | 0.448684E+10 | 6734.62 | 23-FEB-10:09 | 17.75 | 17.47 |
March | 0.431362E+11 | 81861.26 | 27-MAR-05:02 | 19.82 | 18.59 | 0.540296E+10 | 6734.99 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.440365E+11 | 87267.66 | 28-APR-04:12 | 22.77 | 21.59 | 0.484030E+10 | 6734.78 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.529719E+11 | 88188.19 | 12-MAY-04:12 | 22.97 | 20.20 | 0.525821E+10 | 6734.46 | 31-MAY-13:09 | 23.27 | 21.48 |
June | 0.531688E+11 | 87588.31 | 06-JUN-04:12 | 22.97 | 22.12 | 0.524253E+10 | 6734.48 | 01-JUN-13:09 | 23.90 | 20.93 |
July | 0.529478E+11 | 87762.89 | 12-JUL-04:12 | 23.50 | 23.01 | 0.486565E+10 | 6734.46 | 12-JUL-13:09 | 25.32 | 23.34 |
August | 0.552883E+11 | 86975.10 | 26-AUG-04:02 | 23.85 | 23.13 | 0.547177E+10 | 6734.47 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.502144E+11 | 87455.64 | 26-SEP-04:12 | 23.63 | 22.89 | 0.484754E+10 | 6734.45 | 15-SEP-13:09 | 26.60 | 23.38 |
October | 0.499321E+11 | 87942.23 | 12-OCT-04:12 | 21.93 | 21.34 | 0.504331E+10 | 6734.79 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.428101E+11 | 86324.18 | 03-NOV-04:12 | 22.50 | 22.14 | 0.497246E+10 | 6735.35 | 27-NOV-14:20 | 25.53 | 17.42 |
December | 0.395450E+11 | 80524.34 | 15-DEC-05:11 | 21.00 | 21.00 | 0.479359E+10 | 6734.60 | 18-DEC-14:09 | 16.17 | 10.33 |
Annual Sum or Average | 0.557422E+12 | 0.601423E+11 | ||||||||
Minimum of Months | 0.354060E+11 | 79199.59 | 17.00 | 17.00 | 0.448684E+10 | 6734.45 | 14.17 | 9.62 | ||
Maximum of Months | 0.552883E+11 | 88188.19 | 23.85 | 23.13 | 0.547177E+10 | 6735.35 | 27.80 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.332809E+11 | 74830.17 | 20-JAN-06:03 | 17.00 | 17.00 | 0.455056E+10 | 6734.45 | 03-JAN-14:09 | 13.83 | 6.59 |
February | 0.329587E+11 | 73977.59 | 28-FEB-06:03 | 18.38 | 17.90 | 0.426706E+10 | 6734.56 | 09-FEB-14:00 | 22.20 | 14.68 |
March | 0.405163E+11 | 82329.63 | 27-MAR-05:02 | 19.82 | 18.59 | 0.520120E+10 | 6734.53 | 15-MAR-13:09 | 22.20 | 16.08 |
April | 0.442497E+11 | 84239.80 | 29-APR-04:12 | 23.30 | 21.86 | 0.479756E+10 | 6734.76 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.576850E+11 | 87686.88 | 12-MAY-04:12 | 22.97 | 20.20 | 0.526356E+10 | 6734.42 | 26-MAY-13:09 | 26.97 | 24.63 |
June | 0.587156E+11 | 89809.31 | 14-JUN-03:02 | 25.00 | 22.65 | 0.525170E+10 | 6734.44 | 01-JUN-13:09 | 23.90 | 20.93 |
July | 0.583381E+11 | 88310.46 | 07-JUL-03:02 | 26.02 | 24.08 | 0.487672E+10 | 6734.42 | 03-JUL-13:09 | 31.70 | 25.89 |
August | 0.603111E+11 | 84477.79 | 16-AUG-04:12 | 23.53 | 22.00 | 0.547743E+10 | 6734.42 | 22-AUG-13:09 | 31.28 | 25.58 |
September | 0.531250E+11 | 87129.52 | 26-SEP-04:12 | 23.63 | 22.89 | 0.484878E+10 | 6734.42 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.512773E+11 | 87515.89 | 13-OCT-04:02 | 23.83 | 21.68 | 0.501948E+10 | 6734.74 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.395661E+11 | 79328.97 | 08-NOV-05:11 | 19.80 | 19.09 | 0.482373E+10 | 6734.58 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.351433E+11 | 78928.75 | 11-DEC-06:02 | 20.83 | 20.26 | 0.449155E+10 | 6734.50 | 07-DEC-14:00 | 21.00 | 12.04 |
Annual Sum or Average | 0.565167E+12 | 0.588693E+11 | ||||||||
Minimum of Months | 0.329587E+11 | 73977.59 | 17.00 | 17.00 | 0.426706E+10 | 6734.42 | 13.83 | 6.59 | ||
Maximum of Months | 0.603111E+11 | 89809.31 | 26.02 | 24.08 | 0.547743E+10 | 6734.76 | 31.70 | 25.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491589E+10 | 7230.30 | 02-JAN-13:30 | 26.00 | 18.62 | 0.589031E+09 | 845.60 | 27-JAN-14:00 | 18.00 | 12.41 |
February | 0.504144E+10 | 7224.46 | 22-FEB-14:30 | 25.55 | 20.40 | 0.554190E+09 | 845.62 | 09-FEB-14:00 | 22.20 | 14.68 |
March | 0.660462E+10 | 10544.79 | 30-MAR-04:11 | 20.83 | 19.79 | 0.670796E+09 | 845.61 | 24-MAR-09:09 | 19.03 | 14.06 |
April | 0.849701E+10 | 9239.44 | 26-APR-14:30 | 28.00 | 22.40 | 0.609255E+09 | 845.65 | 18-APR-13:50 | 27.62 | 15.12 |
May | 0.104081E+11 | 14671.00 | 29-MAY-16:01 | 32.43 | 23.40 | 0.664400E+09 | 845.60 | 31-MAY-13:09 | 23.27 | 21.48 |
June | 0.117044E+11 | 14845.62 | 25-JUN-15:21 | 32.50 | 24.36 | 0.662051E+09 | 845.60 | 01-JUN-13:09 | 23.90 | 20.93 |
July | 0.123032E+11 | 13011.55 | 03-JUL-04:31 | 26.30 | 23.84 | 0.615484E+09 | 845.59 | 12-JUL-13:39 | 24.47 | 22.46 |
August | 0.131012E+11 | 14884.57 | 20-AUG-13:51 | 34.00 | 25.31 | 0.690372E+09 | 845.60 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.940581E+10 | 13203.77 | 05-SEP-04:12 | 22.73 | 22.73 | 0.613184E+09 | 845.59 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.936564E+10 | 12558.17 | 13-OCT-04:02 | 23.83 | 21.68 | 0.635420E+09 | 845.64 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.678487E+10 | 11923.25 | 03-NOV-04:11 | 22.50 | 22.14 | 0.622340E+09 | 845.63 | 13-NOV-10:09 | 16.47 | 13.02 |
December | 0.602192E+10 | 11087.20 | 11-DEC-06:01 | 20.83 | 20.26 | 0.590894E+09 | 845.62 | 18-DEC-14:09 | 16.17 | 10.33 |
Annual Sum or Average | 0.104154E+12 | 0.751742E+10 | ||||||||
Minimum of Months | 0.491589E+10 | 7224.46 | 20.83 | 18.62 | 0.554190E+09 | 845.59 | 16.17 | 10.33 | ||
Maximum of Months | 0.131012E+11 | 14884.57 | 34.00 | 25.31 | 0.690372E+09 | 845.65 | 27.80 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420100E+10 | 9200.62 | 01-JAN-10:03 | 20.33 | 16.40 | 0.388013E+09 | 544.95 | 11-JAN-10:09 | 14.67 | 12.05 |
February | 0.435287E+10 | 8392.76 | 27-FEB-10:10 | 21.37 | 19.23 | 0.359297E+09 | 544.96 | 09-FEB-10:00 | 15.00 | 12.67 |
March | 0.584747E+10 | 17656.19 | 26-MAR-09:43 | 25.13 | 20.12 | 0.429906E+09 | 544.97 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.718539E+10 | 18766.40 | 23-APR-09:12 | 24.97 | 20.75 | 0.390686E+09 | 544.97 | 03-APR-09:09 | 19.27 | 14.10 |
May | 0.881028E+10 | 20007.17 | 29-MAY-08:41 | 27.62 | 23.18 | 0.428006E+09 | 544.93 | 31-MAY-13:09 | 23.27 | 21.48 |
June | 0.938812E+10 | 17614.46 | 04-JUN-09:32 | 29.27 | 24.88 | 0.426250E+09 | 544.93 | 01-JUN-13:09 | 23.90 | 20.93 |
July | 0.963282E+10 | 17570.33 | 23-JUL-09:02 | 29.68 | 25.88 | 0.396075E+09 | 544.93 | 12-JUL-13:39 | 24.47 | 22.46 |
August | 0.979414E+10 | 17671.85 | 06-AUG-08:51 | 29.00 | 26.74 | 0.443740E+09 | 544.94 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.751497E+10 | 19169.16 | 24-SEP-09:32 | 29.03 | 24.99 | 0.394468E+09 | 544.93 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.757716E+10 | 17802.65 | 15-OCT-08:53 | 23.00 | 19.56 | 0.408361E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.550671E+10 | 17535.28 | 11-NOV-09:02 | 24.40 | 21.68 | 0.400740E+09 | 544.96 | 09-NOV-10:09 | 15.27 | 8.87 |
December | 0.465281E+10 | 13028.35 | 10-DEC-08:56 | 20.00 | 17.44 | 0.375237E+09 | 544.95 | 04-DEC-10:00 | 13.00 | 9.82 |
Annual Sum or Average | 0.844637E+11 | 0.484078E+10 | ||||||||
Minimum of Months | 0.420100E+10 | 8392.76 | 20.00 | 16.40 | 0.359297E+09 | 544.93 | 13.00 | 8.87 | ||
Maximum of Months | 0.979414E+10 | 20007.17 | 29.68 | 26.74 | 0.443740E+09 | 544.97 | 27.80 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.921682E+10 | 18867.73 | 01-JAN-13:22 | 25.50 | 18.22 | 0.622642E+09 | 936.74 | 19-JAN-14:09 | 25.00 | 21.53 |
February | 0.867795E+10 | 19118.38 | 26-FEB-13:52 | 26.60 | 19.71 | 0.569142E+09 | 919.58 | 27-FEB-14:20 | 25.70 | 20.07 |
March | 0.863559E+10 | 17968.74 | 05-MAR-13:32 | 27.70 | 18.30 | 0.671244E+09 | 845.65 | 13-MAR-13:09 | 19.68 | 10.41 |
April | 0.929935E+10 | 11034.68 | 28-APR-13:20 | 32.37 | 22.87 | 0.608387E+09 | 845.68 | 18-APR-13:50 | 27.62 | 15.12 |
May | 0.105116E+11 | 16466.52 | 28-MAY-16:31 | 32.03 | 24.84 | 0.664352E+09 | 845.61 | 31-MAY-13:09 | 23.27 | 21.48 |
June | 0.114973E+11 | 17023.04 | 25-JUN-15:21 | 32.50 | 24.36 | 0.661971E+09 | 845.62 | 01-JUN-13:09 | 23.90 | 20.93 |
July | 0.122845E+11 | 14927.73 | 03-JUL-04:31 | 26.30 | 23.84 | 0.615524E+09 | 845.61 | 12-JUL-13:39 | 24.47 | 22.46 |
August | 0.138661E+11 | 17407.94 | 20-AUG-13:51 | 34.00 | 25.31 | 0.690570E+09 | 845.62 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.110160E+11 | 18233.72 | 10-SEP-12:02 | 35.17 | 27.75 | 0.613814E+09 | 845.62 | 20-SEP-13:39 | 26.60 | 22.71 |
October | 0.135116E+11 | 18483.97 | 08-OCT-12:01 | 31.17 | 25.80 | 0.642188E+09 | 915.98 | 13-OCT-13:39 | 32.73 | 23.23 |
November | 0.118361E+11 | 19727.90 | 11-NOV-11:42 | 26.52 | 22.19 | 0.636362E+09 | 965.71 | 06-NOV-14:09 | 28.30 | 21.02 |
December | 0.110305E+11 | 18843.47 | 17-DEC-15:12 | 17.67 | 11.87 | 0.610096E+09 | 951.74 | 15-DEC-14:20 | 29.00 | 21.90 |
Annual Sum or Average | 0.131383E+12 | 0.760629E+10 | ||||||||
Minimum of Months | 0.863559E+10 | 11034.68 | 17.67 | 11.87 | 0.569142E+09 | 845.61 | 19.68 | 10.41 | ||
Maximum of Months | 0.138661E+11 | 19727.90 | 35.17 | 27.75 | 0.690570E+09 | 965.71 | 32.73 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.591415E+10 | 21929.17 | 16-JAN-16:11 | 24.33 | 18.33 | 0.385251E+09 | 544.94 | 27-JAN-14:00 | 18.00 | 12.41 |
February | 0.654767E+10 | 22981.57 | 26-FEB-15:52 | 25.50 | 19.90 | 0.364023E+09 | 544.96 | 09-FEB-14:00 | 22.20 | 14.68 |
March | 0.886627E+10 | 22780.25 | 05-MAR-15:32 | 26.47 | 18.75 | 0.441105E+09 | 544.97 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.118851E+11 | 23263.60 | 23-APR-16:32 | 27.37 | 21.79 | 0.396033E+09 | 544.99 | 18-APR-13:50 | 27.62 | 15.12 |
May | 0.103708E+11 | 25088.90 | 29-MAY-16:41 | 30.97 | 23.74 | 0.428663E+09 | 544.93 | 31-MAY-13:09 | 23.27 | 21.48 |
June | 0.123816E+11 | 24150.15 | 25-JUN-15:21 | 32.50 | 24.36 | 0.427439E+09 | 544.93 | 01-JUN-13:09 | 23.90 | 20.93 |
July | 0.135423E+11 | 23327.68 | 30-JUL-15:41 | 27.38 | 24.30 | 0.397708E+09 | 544.93 | 12-JUL-13:39 | 24.47 | 22.46 |
August | 0.157394E+11 | 22996.48 | 20-AUG-17:11 | 30.33 | 24.27 | 0.446019E+09 | 544.94 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.964478E+10 | 24374.87 | 17-SEP-15:31 | 32.00 | 25.61 | 0.395728E+09 | 544.93 | 07-SEP-13:39 | 26.07 | 23.43 |
October | 0.107448E+11 | 22995.52 | 22-OCT-16:21 | 28.60 | 23.82 | 0.411274E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.881217E+10 | 23580.90 | 11-NOV-15:02 | 26.52 | 22.98 | 0.406204E+09 | 544.97 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.864923E+10 | 22336.18 | 25-DEC-15:41 | 18.00 | 10.00 | 0.393839E+09 | 544.97 | 26-DEC-14:00 | 13.30 | 6.25 |
Annual Sum or Average | 0.123098E+12 | 0.489328E+10 | ||||||||
Minimum of Months | 0.591415E+10 | 21929.17 | 18.00 | 10.00 | 0.364023E+09 | 544.93 | 13.30 | 6.25 | ||
Maximum of Months | 0.157394E+11 | 25088.90 | 32.50 | 25.61 | 0.446019E+09 | 544.99 | 27.80 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313542E+10 | 5093.17 | 31-JAN-14:40 | 25.00 | 21.54 | 0.532776E+09 | 845.59 | 02-JAN-14:39 | 26.67 | 18.56 |
February | 0.343034E+10 | 5332.83 | 28-FEB-15:00 | 25.00 | 20.37 | 0.509030E+09 | 845.58 | 01-FEB-14:09 | 24.77 | 20.39 |
March | 0.449336E+10 | 7473.01 | 27-MAR-05:01 | 19.82 | 18.59 | 0.621000E+09 | 845.59 | 24-MAR-13:09 | 23.67 | 15.71 |
April | 0.572466E+10 | 8864.53 | 28-APR-04:11 | 22.77 | 21.59 | 0.593865E+09 | 845.62 | 12-APR-13:30 | 24.70 | 17.48 |
May | 0.911659E+10 | 12927.63 | 21-MAY-15:47 | 28.40 | 22.86 | 0.663646E+09 | 845.59 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.979965E+10 | 12383.61 | 05-JUN-03:02 | 26.52 | 24.30 | 0.661907E+09 | 845.59 | 12-JUN-13:09 | 31.78 | 20.54 |
July | 0.972444E+10 | 12523.28 | 05-JUL-03:02 | 25.60 | 23.97 | 0.615600E+09 | 845.59 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.980023E+10 | 12520.44 | 14-AUG-03:02 | 26.52 | 24.51 | 0.690325E+09 | 845.59 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.795117E+10 | 13561.04 | 10-SEP-15:11 | 35.17 | 27.18 | 0.611477E+09 | 845.59 | 07-SEP-13:39 | 26.07 | 23.43 |
October | 0.729239E+10 | 11448.83 | 26-OCT-05:02 | 22.83 | 14.22 | 0.628040E+09 | 845.63 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.468467E+10 | 8999.46 | 29-NOV-06:02 | 21.60 | 21.25 | 0.588236E+09 | 845.61 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.366819E+10 | 5994.81 | 15-DEC-15:00 | 29.00 | 21.55 | 0.530194E+09 | 845.59 | 08-DEC-14:20 | 26.67 | 19.25 |
Annual Sum or Average | 0.788211E+11 | 0.724609E+10 | ||||||||
Minimum of Months | 0.313542E+10 | 5093.17 | 19.82 | 14.22 | 0.509030E+09 | 845.58 | 22.17 | 15.13 | ||
Maximum of Months | 0.980023E+10 | 13561.04 | 35.17 | 27.18 | 0.690325E+09 | 845.63 | 31.88 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312352E+10 | 7058.36 | 19-JAN-09:40 | 22.33 | 20.72 | 0.261499E+09 | 521.19 | 02-JAN-15:20 | 26.67 | 18.56 |
February | 0.339799E+10 | 7364.61 | 26-FEB-10:30 | 22.75 | 19.67 | 0.248217E+09 | 521.21 | 09-FEB-11:09 | 16.10 | 12.99 |
March | 0.461277E+10 | 11915.62 | 27-MAR-05:01 | 19.82 | 18.59 | 0.302306E+09 | 521.24 | 23-MAR-08:50 | 15.87 | 14.00 |
April | 0.587990E+10 | 18869.72 | 23-APR-08:22 | 23.30 | 19.91 | 0.283954E+09 | 521.23 | 18-APR-14:09 | 27.70 | 15.14 |
May | 0.838434E+10 | 19341.69 | 29-MAY-08:51 | 27.80 | 23.35 | 0.314664E+09 | 521.20 | 09-MAY-14:20 | 31.33 | 21.91 |
June | 0.868724E+10 | 19080.21 | 11-JUN-08:42 | 27.33 | 20.83 | 0.313362E+09 | 521.20 | 12-JUN-12:09 | 31.70 | 20.33 |
July | 0.859847E+10 | 18699.20 | 09-JUL-08:52 | 30.60 | 26.05 | 0.292429E+09 | 521.20 | 05-JUL-12:09 | 32.20 | 26.45 |
August | 0.844039E+10 | 18741.43 | 06-AUG-09:52 | 30.00 | 26.94 | 0.326321E+09 | 521.19 | 30-AUG-12:09 | 31.18 | 24.69 |
September | 0.691031E+10 | 19517.70 | 10-SEP-08:32 | 33.30 | 26.75 | 0.289262E+09 | 521.20 | 01-SEP-10:20 | 30.17 | 24.71 |
October | 0.662690E+10 | 18730.93 | 09-OCT-09:11 | 27.73 | 22.39 | 0.297620E+09 | 521.21 | 17-OCT-12:39 | 21.67 | 15.10 |
November | 0.436104E+10 | 14270.63 | 11-NOV-09:32 | 24.40 | 21.68 | 0.284873E+09 | 521.20 | 14-NOV-11:20 | 19.60 | 12.03 |
December | 0.327885E+10 | 5751.42 | 16-DEC-09:40 | 23.33 | 20.99 | 0.255000E+09 | 521.20 | 01-DEC-11:20 | 19.67 | 14.55 |
Annual Sum or Average | 0.723017E+11 | 0.346951E+10 | ||||||||
Minimum of Months | 0.312352E+10 | 5751.42 | 19.82 | 18.59 | 0.248217E+09 | 521.19 | 15.87 | 12.03 | ||
Maximum of Months | 0.868724E+10 | 19517.70 | 33.30 | 26.94 | 0.326321E+09 | 521.24 | 32.20 | 26.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.815770E+10 | 19138.99 | 01-JAN-13:11 | 25.33 | 18.33 | 0.613556E+09 | 986.32 | 19-JAN-14:39 | 25.00 | 21.53 |
February | 0.747338E+10 | 17706.41 | 26-FEB-14:22 | 26.35 | 19.91 | 0.559900E+09 | 952.79 | 27-FEB-14:39 | 25.90 | 20.25 |
March | 0.673241E+10 | 13151.09 | 27-MAR-05:02 | 19.82 | 18.59 | 0.650411E+09 | 845.63 | 13-MAR-13:09 | 19.68 | 10.41 |
April | 0.676932E+10 | 12181.82 | 29-APR-04:11 | 23.30 | 21.86 | 0.598618E+09 | 845.66 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.927834E+10 | 13965.34 | 08-MAY-03:01 | 24.40 | 22.09 | 0.663586E+09 | 845.61 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.957713E+10 | 13727.84 | 29-JUN-05:02 | 25.18 | 24.55 | 0.661667E+09 | 845.61 | 13-JUN-13:09 | 32.98 | 21.36 |
July | 0.970821E+10 | 14462.53 | 05-JUL-03:02 | 25.60 | 23.97 | 0.615531E+09 | 845.61 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.106538E+11 | 14533.76 | 14-AUG-03:02 | 26.52 | 24.51 | 0.690667E+09 | 847.45 | 31-AUG-13:39 | 31.80 | 24.89 |
September | 0.980129E+10 | 16903.25 | 10-SEP-15:11 | 35.17 | 27.18 | 0.612993E+09 | 845.61 | 20-SEP-13:39 | 26.60 | 22.71 |
October | 0.118883E+11 | 17530.61 | 09-OCT-13:11 | 31.00 | 23.40 | 0.644521E+09 | 955.01 | 13-OCT-13:50 | 32.87 | 23.23 |
November | 0.102010E+11 | 18432.86 | 11-NOV-12:52 | 26.60 | 22.71 | 0.635280E+09 | 1011.90 | 06-NOV-14:09 | 28.30 | 21.02 |
December | 0.905359E+10 | 19048.15 | 10-DEC-13:21 | 27.00 | 20.21 | 0.597750E+09 | 981.91 | 15-DEC-14:39 | 29.00 | 21.73 |
Annual Sum or Average | 0.109295E+12 | 0.754448E+10 | ||||||||
Minimum of Months | 0.673241E+10 | 12181.82 | 19.82 | 18.33 | 0.559900E+09 | 845.61 | 19.68 | 10.41 | ||
Maximum of Months | 0.118883E+11 | 19138.99 | 35.17 | 27.18 | 0.690667E+09 | 1011.90 | 32.98 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358599E+10 | 9013.24 | 31-JAN-16:30 | 24.00 | 21.23 | 0.353259E+09 | 544.93 | 02-JAN-14:39 | 26.67 | 18.56 |
February | 0.394587E+10 | 18862.91 | 26-FEB-17:01 | 24.22 | 19.75 | 0.333562E+09 | 544.94 | 09-FEB-14:00 | 22.20 | 14.68 |
March | 0.489265E+10 | 13172.09 | 27-MAR-05:01 | 19.82 | 18.59 | 0.401606E+09 | 544.93 | 03-MAR-14:00 | 23.30 | 11.80 |
April | 0.637600E+10 | 19036.95 | 23-APR-16:42 | 27.28 | 21.75 | 0.383346E+09 | 544.95 | 12-APR-13:30 | 24.70 | 17.48 |
May | 0.812321E+10 | 20431.07 | 29-MAY-16:51 | 30.60 | 23.79 | 0.427316E+09 | 544.93 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.871591E+10 | 21598.42 | 11-JUN-16:41 | 33.12 | 21.80 | 0.426493E+09 | 544.93 | 13-JUN-13:09 | 32.98 | 21.36 |
July | 0.845788E+10 | 19281.88 | 16-JUL-17:12 | 29.40 | 24.63 | 0.396825E+09 | 544.93 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.894595E+10 | 19331.35 | 06-AUG-16:31 | 25.33 | 22.97 | 0.445021E+09 | 544.93 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.729554E+10 | 20637.96 | 10-SEP-15:11 | 35.17 | 27.18 | 0.393506E+09 | 544.93 | 07-SEP-13:39 | 26.07 | 23.43 |
October | 0.716854E+10 | 19568.42 | 09-OCT-16:31 | 28.00 | 21.40 | 0.404488E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.494469E+10 | 18245.89 | 11-NOV-16:11 | 25.53 | 22.88 | 0.380557E+09 | 545.01 | 27-NOV-14:20 | 25.53 | 17.42 |
December | 0.410969E+10 | 14773.94 | 10-DEC-16:01 | 26.67 | 20.13 | 0.348948E+09 | 544.94 | 07-DEC-14:00 | 21.00 | 12.04 |
Annual Sum or Average | 0.765619E+11 | 0.469493E+10 | ||||||||
Minimum of Months | 0.358599E+10 | 9013.24 | 19.82 | 18.59 | 0.333562E+09 | 544.93 | 21.00 | 11.80 | ||
Maximum of Months | 0.894595E+10 | 21598.42 | 35.17 | 27.18 | 0.445021E+09 | 545.01 | 32.98 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252726E+10 | 5466.32 | 31-JAN-15:00 | 25.00 | 21.54 | 0.517663E+09 | 845.59 | 02-JAN-14:50 | 26.83 | 18.61 |
February | 0.311024E+10 | 5792.20 | 22-FEB-14:30 | 25.55 | 20.40 | 0.495930E+09 | 845.58 | 01-FEB-14:09 | 24.77 | 20.39 |
March | 0.425133E+10 | 7519.73 | 30-MAR-13:20 | 28.83 | 22.62 | 0.604294E+09 | 845.59 | 24-MAR-13:09 | 23.67 | 15.71 |
April | 0.583988E+10 | 9203.61 | 28-APR-15:00 | 33.30 | 23.04 | 0.585724E+09 | 845.62 | 12-APR-13:30 | 24.70 | 17.48 |
May | 0.977318E+10 | 15121.09 | 29-MAY-16:11 | 32.07 | 23.50 | 0.663544E+09 | 845.59 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.106049E+11 | 15452.97 | 11-JUN-16:41 | 33.12 | 21.80 | 0.661969E+09 | 845.59 | 12-JUN-13:09 | 31.78 | 20.54 |
July | 0.105233E+11 | 15555.41 | 02-JUL-16:12 | 29.27 | 25.10 | 0.615848E+09 | 845.59 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.105165E+11 | 15234.03 | 20-AUG-15:42 | 32.17 | 25.82 | 0.690190E+09 | 845.59 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.836562E+10 | 16106.65 | 10-SEP-15:11 | 35.17 | 27.18 | 0.610904E+09 | 845.59 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.752119E+10 | 15317.87 | 08-OCT-14:02 | 32.67 | 26.17 | 0.622978E+09 | 845.63 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.439455E+10 | 9463.02 | 01-NOV-05:02 | 22.62 | 22.36 | 0.570186E+09 | 845.61 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.311252E+10 | 6555.04 | 15-DEC-15:00 | 29.00 | 21.55 | 0.513392E+09 | 845.58 | 08-DEC-14:50 | 26.17 | 19.34 |
Annual Sum or Average | 0.805405E+11 | 0.715262E+10 | ||||||||
Minimum of Months | 0.252726E+10 | 5466.32 | 22.62 | 20.40 | 0.495930E+09 | 845.58 | 22.17 | 15.13 | ||
Maximum of Months | 0.106049E+11 | 16106.65 | 35.17 | 27.18 | 0.690190E+09 | 845.63 | 31.88 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272673E+10 | 6543.68 | 19-JAN-10:10 | 23.28 | 20.98 | 0.344877E+09 | 544.93 | 02-JAN-14:39 | 26.67 | 18.56 |
February | 0.313489E+10 | 6683.67 | 27-FEB-10:30 | 21.90 | 19.27 | 0.333210E+09 | 544.95 | 09-FEB-10:00 | 15.00 | 12.67 |
March | 0.440449E+10 | 10373.79 | 27-MAR-05:01 | 19.82 | 18.59 | 0.408416E+09 | 544.98 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.596403E+10 | 18840.78 | 23-APR-08:22 | 23.30 | 19.91 | 0.386006E+09 | 544.97 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.893751E+10 | 19577.08 | 29-MAY-08:51 | 27.80 | 23.35 | 0.427808E+09 | 544.93 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.934397E+10 | 19198.09 | 11-JUN-08:42 | 27.33 | 20.83 | 0.426578E+09 | 544.93 | 12-JUN-13:09 | 31.78 | 20.54 |
July | 0.925236E+10 | 18966.78 | 09-JUL-08:52 | 30.60 | 26.05 | 0.396810E+09 | 544.93 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.903775E+10 | 18091.23 | 27-AUG-11:41 | 30.83 | 23.85 | 0.444347E+09 | 544.93 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.729491E+10 | 19806.39 | 10-SEP-08:32 | 33.30 | 26.75 | 0.393225E+09 | 544.93 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.684868E+10 | 18907.40 | 09-OCT-09:51 | 29.00 | 22.61 | 0.403453E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.411938E+10 | 8280.06 | 02-NOV-09:40 | 26.97 | 23.89 | 0.382177E+09 | 544.95 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.288091E+10 | 5265.23 | 16-DEC-09:50 | 23.67 | 21.08 | 0.338649E+09 | 544.94 | 01-DEC-10:50 | 18.50 | 14.02 |
Annual Sum or Average | 0.739456E+11 | 0.468555E+10 | ||||||||
Minimum of Months | 0.272673E+10 | 5265.23 | 19.82 | 18.59 | 0.333210E+09 | 544.93 | 15.00 | 10.89 | ||
Maximum of Months | 0.934397E+10 | 19806.39 | 33.30 | 26.75 | 0.444347E+09 | 544.98 | 31.88 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.707237E+10 | 20983.48 | 01-JAN-14:31 | 25.33 | 18.33 | 0.598314E+09 | 957.46 | 19-JAN-14:39 | 25.00 | 21.53 |
February | 0.692781E+10 | 18737.40 | 26-FEB-12:43 | 26.10 | 18.68 | 0.547292E+09 | 923.69 | 27-FEB-14:39 | 25.90 | 20.25 |
March | 0.639677E+10 | 13240.65 | 27-MAR-05:01 | 19.82 | 18.59 | 0.634510E+09 | 845.63 | 03-MAR-14:00 | 23.30 | 11.80 |
April | 0.687928E+10 | 11195.05 | 28-APR-13:50 | 32.62 | 22.97 | 0.590838E+09 | 845.66 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.992849E+10 | 17195.21 | 07-MAY-14:53 | 32.80 | 23.09 | 0.663450E+09 | 845.61 | 04-MAY-13:00 | 32.20 | 21.97 |
June | 0.103768E+11 | 17261.04 | 11-JUN-16:41 | 33.12 | 21.80 | 0.661637E+09 | 845.61 | 12-JUN-13:09 | 31.78 | 20.54 |
July | 0.104988E+11 | 17446.86 | 02-JUL-16:12 | 29.27 | 25.10 | 0.615732E+09 | 845.61 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.113718E+11 | 16769.68 | 20-AUG-15:42 | 32.17 | 25.82 | 0.690494E+09 | 845.61 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.102586E+11 | 19227.41 | 10-SEP-15:11 | 35.17 | 27.18 | 0.612346E+09 | 845.61 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.121525E+11 | 19402.92 | 09-OCT-13:11 | 31.00 | 23.40 | 0.637498E+09 | 936.03 | 13-OCT-13:50 | 32.87 | 23.23 |
November | 0.959290E+10 | 18863.99 | 11-NOV-13:52 | 26.10 | 22.84 | 0.621715E+09 | 980.75 | 06-NOV-14:09 | 28.30 | 21.02 |
December | 0.818465E+10 | 20898.77 | 10-DEC-13:11 | 27.00 | 20.21 | 0.578678E+09 | 955.41 | 15-DEC-14:39 | 29.00 | 21.73 |
Annual Sum or Average | 0.109641E+12 | 0.745250E+10 | ||||||||
Minimum of Months | 0.639677E+10 | 11195.05 | 19.82 | 18.33 | 0.547292E+09 | 845.61 | 20.50 | 10.89 | ||
Maximum of Months | 0.121525E+11 | 20983.48 | 35.17 | 27.18 | 0.690494E+09 | 980.75 | 32.87 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318431E+10 | 9342.63 | 31-JAN-16:30 | 24.00 | 21.23 | 0.344441E+09 | 544.93 | 02-JAN-14:39 | 26.67 | 18.56 |
February | 0.376673E+10 | 19877.11 | 26-FEB-18:01 | 22.83 | 19.14 | 0.325216E+09 | 544.92 | 22-FEB-14:09 | 25.92 | 20.62 |
March | 0.477870E+10 | 14917.28 | 27-MAR-05:01 | 19.82 | 18.59 | 0.390922E+09 | 544.93 | 03-MAR-14:00 | 23.30 | 11.80 |
April | 0.653692E+10 | 20996.95 | 23-APR-17:01 | 26.92 | 21.64 | 0.376615E+09 | 544.95 | 12-APR-13:30 | 24.70 | 17.48 |
May | 0.862261E+10 | 21596.48 | 29-MAY-16:51 | 30.60 | 23.79 | 0.426511E+09 | 544.93 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.930894E+10 | 22961.90 | 11-JUN-16:41 | 33.12 | 21.80 | 0.425867E+09 | 544.93 | 12-JUN-13:09 | 31.78 | 20.54 |
July | 0.905472E+10 | 20760.06 | 30-JUL-16:21 | 27.20 | 24.52 | 0.396430E+09 | 544.93 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.946670E+10 | 20202.47 | 06-AUG-16:41 | 25.67 | 23.42 | 0.444343E+09 | 544.93 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.766418E+10 | 22457.36 | 10-SEP-15:11 | 35.17 | 27.18 | 0.391818E+09 | 544.93 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.739217E+10 | 20898.87 | 09-OCT-16:31 | 28.00 | 21.40 | 0.400214E+09 | 544.94 | 26-OCT-13:20 | 24.13 | 14.28 |
November | 0.478042E+10 | 11173.65 | 06-NOV-16:10 | 28.02 | 20.16 | 0.370130E+09 | 544.95 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.373410E+10 | 19805.17 | 10-DEC-16:31 | 25.67 | 19.84 | 0.339036E+09 | 544.94 | 01-DEC-14:00 | 24.00 | 16.59 |
Annual Sum or Average | 0.782905E+11 | 0.463154E+10 | ||||||||
Minimum of Months | 0.318431E+10 | 9342.63 | 19.82 | 18.59 | 0.325216E+09 | 544.92 | 22.20 | 11.80 | ||
Maximum of Months | 0.946670E+10 | 22961.90 | 35.17 | 27.18 | 0.444343E+09 | 544.95 | 31.88 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423992E+10 | 9957.45 | 02-JAN-06:13 | 16.00 | 15.39 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.433594E+10 | 7394.93 | 27-FEB-06:01 | 17.70 | 17.70 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.560814E+10 | 8882.47 | 27-MAR-05:01 | 19.82 | 18.59 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.683777E+10 | 7116.20 | 28-APR-05:03 | 22.80 | 21.69 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.809794E+10 | 10935.01 | 23-MAY-05:01 | 23.90 | 23.41 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.862229E+10 | 10533.77 | 29-JUN-05:01 | 25.18 | 24.55 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.903144E+10 | 10265.61 | 19-JUL-05:01 | 27.12 | 24.30 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.976374E+10 | 9706.55 | 22-AUG-05:01 | 25.52 | 24.77 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.769546E+10 | 10873.64 | 05-SEP-05:03 | 22.80 | 22.80 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.808478E+10 | 12094.07 | 10-OCT-05:02 | 21.98 | 20.05 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.631356E+10 | 7965.73 | 03-NOV-05:03 | 22.28 | 21.91 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.550705E+10 | 10589.09 | 11-DEC-06:01 | 20.83 | 20.26 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.841380E+11 | 0.00 | ||||||||
Minimum of Months | 0.423992E+10 | 7116.20 | 16.00 | 15.39 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.976374E+10 | 12094.07 | 27.12 | 24.77 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236033E+10 | 7674.65 | 04-JAN-06:03 | 1.83 | -1.0 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.247618E+10 | 6560.44 | 17-FEB-06:03 | 1.52 | -1.1 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.332635E+10 | 7545.87 | 09-MAR-06:03 | 1.10 | -1.9 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.439494E+10 | 5387.54 | 28-APR-16:00 | 32.20 | 25.54 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.680352E+10 | 8170.01 | 06-MAY-05:01 | 24.40 | 21.68 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.705457E+10 | 9835.69 | 14-JUN-05:01 | 25.00 | 22.88 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.715713E+10 | 9683.01 | 08-JUL-05:01 | 24.90 | 23.43 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.736679E+10 | 9298.67 | 05-AUG-05:01 | 25.63 | 23.91 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.623848E+10 | 9405.27 | 12-SEP-05:01 | 26.77 | 24.21 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.610829E+10 | 10306.39 | 07-OCT-05:01 | 26.17 | 26.04 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.380201E+10 | 5120.11 | 09-NOV-06:10 | 10.42 | 5.51 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.301993E+10 | 5989.40 | 20-DEC-06:03 | 2.83 | 1.60 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.601085E+11 | 0.00 | ||||||||
Minimum of Months | 0.236033E+10 | 5120.11 | 1.10 | -1.9 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.736679E+10 | 10306.39 | 32.20 | 26.04 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250459E+10 | 9308.96 | 19-JAN-15:00 | 25.00 | 21.53 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.346035E+10 | 11030.87 | 24-FEB-15:00 | 25.50 | 20.82 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.473795E+10 | 11512.81 | 29-MAR-14:40 | 26.47 | 21.32 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.763813E+10 | 17363.49 | 18-APR-15:00 | 27.70 | 15.31 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.121890E+11 | 17522.47 | 10-MAY-14:50 | 32.80 | 23.12 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.134256E+11 | 18234.03 | 28-JUN-14:30 | 33.60 | 26.18 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.128754E+11 | 18689.41 | 07-JUL-14:50 | 34.82 | 23.94 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.129863E+11 | 17852.28 | 03-AUG-15:00 | 35.00 | 24.83 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.100154E+11 | 16246.32 | 01-SEP-14:00 | 32.20 | 22.61 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.948130E+10 | 15942.94 | 05-OCT-15:00 | 34.00 | 24.03 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.473102E+10 | 12630.32 | 02-NOV-14:00 | 29.40 | 24.47 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.313008E+10 | 10897.28 | 15-DEC-15:00 | 29.00 | 21.55 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.971752E+11 | 0.00 | ||||||||
Minimum of Months | 0.250459E+10 | 9308.96 | 25.00 | 15.31 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.134256E+11 | 18689.41 | 35.00 | 26.18 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370013E+10 | 2050.68 | 01-JAN-17:20 | 22.67 | 18.99 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.817286E+10 | 4159.39 | 26-FEB-17:54 | 23.30 | 19.28 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.142677E+11 | 5776.03 | 05-MAR-17:45 | 24.18 | 18.26 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.188921E+11 | 7993.14 | 16-APR-18:20 | 18.07 | 13.18 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.450494E+10 | 2092.84 | 29-MAY-18:19 | 29.03 | 23.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.921737E+10 | 3956.41 | 11-JUN-18:25 | 31.40 | 21.45 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.145539E+11 | 5758.46 | 23-JUL-18:58 | 30.60 | 25.71 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.196354E+11 | 7671.94 | 06-AUG-17:45 | 25.17 | 23.64 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.437100E+10 | 2178.71 | 03-SEP-18:00 | 29.90 | 24.07 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.953969E+10 | 4045.04 | 01-OCT-17:33 | 25.67 | 17.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.139820E+11 | 5953.93 | 12-NOV-17:03 | 14.53 | 8.51 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.193607E+11 | 7857.03 | 10-DEC-17:03 | 24.83 | 19.68 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.140198E+12 | 0.00 | ||||||||
Minimum of Months | 0.370013E+10 | 2050.68 | 14.53 | 8.51 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.196354E+11 | 7993.14 | 31.40 | 25.71 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229942E+10 | 1791.10 | 31-JAN-17:50 | 22.17 | 20.10 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.678129E+10 | 3761.79 | 26-FEB-17:52 | 23.30 | 19.28 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.127286E+11 | 5414.03 | 06-MAR-18:00 | 23.80 | 20.71 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.177081E+11 | 7450.27 | 16-APR-18:20 | 18.07 | 13.18 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.404987E+10 | 1889.22 | 14-MAY-18:23 | 27.75 | 22.50 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.868762E+10 | 3719.95 | 11-JUN-18:30 | 31.40 | 21.45 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.138416E+11 | 5389.40 | 16-JUL-18:55 | 28.90 | 24.50 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.186984E+11 | 7228.01 | 30-AUG-18:40 | 31.90 | 23.11 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.384387E+10 | 2006.22 | 03-SEP-17:55 | 29.90 | 24.07 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.876185E+10 | 3769.32 | 09-OCT-17:28 | 27.00 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.125810E+11 | 5572.68 | 06-NOV-17:00 | 26.60 | 19.71 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.173827E+11 | 7301.23 | 15-DEC-17:00 | 28.00 | 21.23 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.127364E+12 | 0.00 | ||||||||
Minimum of Months | 0.229942E+10 | 1791.10 | 18.07 | 13.18 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.186984E+11 | 7450.27 | 31.90 | 24.50 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147603E+10 | 1864.57 | 31-JAN-17:50 | 22.17 | 20.10 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.602089E+10 | 3754.73 | 26-FEB-17:56 | 23.30 | 19.28 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.121807E+11 | 5482.09 | 06-MAR-17:50 | 24.00 | 20.78 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.175408E+11 | 7552.71 | 23-APR-18:05 | 25.13 | 21.18 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.415853E+10 | 2152.93 | 29-MAY-17:58 | 29.40 | 23.46 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.881547E+10 | 3967.87 | 11-JUN-18:23 | 31.40 | 21.45 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.139785E+11 | 5613.57 | 16-JUL-18:50 | 28.98 | 24.52 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.187915E+11 | 7419.60 | 06-AUG-17:34 | 25.33 | 23.69 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.390936E+10 | 2227.51 | 03-SEP-18:00 | 29.90 | 24.07 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.866256E+10 | 3973.37 | 09-OCT-17:30 | 27.00 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.120260E+11 | 5636.59 | 06-NOV-17:00 | 26.60 | 19.71 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.165425E+11 | 7369.71 | 15-DEC-17:00 | 28.00 | 21.23 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.124103E+12 | 0.00 | ||||||||
Minimum of Months | 0.147603E+10 | 1864.57 | 22.17 | 19.28 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.187915E+11 | 7552.71 | 31.40 | 24.52 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239548E+12 | 91853.82 | 02-JAN-17:00 | 26.00 | 18.37 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.435988E+12 | 182619.74 | 27-FEB-17:00 | 24.40 | 20.27 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.727544E+12 | 273772.86 | 06-MAR-17:00 | 25.00 | 21.10 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.941606E+12 | 365331.15 | 28-APR-18:50 | 23.72 | 22.13 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.239801E+12 | 102996.50 | 01-MAY-00:10 | 22.45 | 19.10 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.468204E+12 | 182271.88 | 06-JUN-16:00 | 26.70 | 21.57 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.730243E+12 | 274513.53 | 06-JUL-16:00 | 31.70 | 24.74 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.976688E+12 | 369960.91 | 28-AUG-21:02 | 26.03 | 23.70 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.235833E+12 | 106766.67 | 01-SEP-00:10 | 24.85 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.487600E+12 | 183920.88 | 11-OCT-16:00 | 30.00 | 22.37 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.708876E+12 | 275597.15 | 06-NOV-17:00 | 26.60 | 19.71 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.977136E+12 | 367068.02 | 14-DEC-17:00 | 26.00 | 22.47 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.716907E+13 | 0.00 | ||||||||
Minimum of Months | 0.235833E+12 | 91853.82 | 22.45 | 18.37 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.977136E+12 | 369960.91 | 31.70 | 24.74 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.649034E+09 | 126632.62 | 16-JAN-15:00 | 27.00 |
February | 0.720672E+09 | 131565.23 | 26-FEB-17:10 | 24.22 |
March | 0.624384E+09 | 130317.79 | 26-MAR-15:48 | 25.72 |
April | 0.725150E+09 | 131757.50 | 23-APR-17:38 | 26.07 |
May | 0.935654E+09 | 137567.11 | 28-MAY-17:14 | 30.53 |
June | 0.838406E+09 | 137224.57 | 25-JUN-14:47 | 32.30 |
July | 0.110160E+10 | 135929.99 | 02-JUL-14:08 | 29.90 |
August | 0.817385E+09 | 135157.63 | 06-AUG-07:55 | 28.00 |
September | 0.115616E+10 | 137545.94 | 10-SEP-09:10 | 33.87 |
October | 0.117088E+10 | 133549.90 | 08-OCT-08:50 | 26.67 |
November | 0.130188E+10 | 132657.17 | 11-NOV-12:58 | 26.60 |
December | 0.135776E+10 | 130208.97 | 10-DEC-12:04 | 27.00 |
Annual Sum or Average | 0.113990E+11 | |||
Minimum of Months | 0.624384E+09 | 126632.62 | 24.22 | |
Maximum of Months | 0.135776E+10 | 137567.11 | 33.87 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84513485.29 | 46740.66 | 09-JAN-06:01 | 6.67 |
February | 0.284504E+09 | 54286.20 | 06-FEB-05:21 | 2.90 |
March | 21095766.45 | 46399.93 | 13-MAR-05:02 | 6.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 19344455.63 | 46210.64 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.409458E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.284504E+09 | 54286.20 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 313411.09 | 3018.77 | 05-JAN-06:01 | 0.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 313411.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 313411.09 | 3018.77 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2289647.59 | 1997.85 | 21-JAN-06:03 | 1.00 |
February | 251945.35 | 1755.32 | 06-FEB-06:01 | 2.88 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 2676755.66 | 1894.17 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 5218348.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 2676755.66 | 1997.85 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2723586.37 | 5360.74 | 05-JAN-06:01 | 0.17 |
February | 2020463.73 | 5508.01 | 06-FEB-06:01 | 2.88 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 2067785.50 | 5093.34 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 6811835.59 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 2723586.37 | 5508.01 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304845E+09 | 10315.96 | 10-JAN-05:01 | 1.33 |
February | 0.142705E+09 | 10673.96 | 06-FEB-05:11 | 2.97 |
March | 89799507.66 | 9839.52 | 13-MAR-04:11 | 7.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 1159354.67 | 3766.46 | 16-NOV-06:03 | 9.40 |
December | 0.162853E+09 | 10259.73 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.701362E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.304845E+09 | 10673.96 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148795E+09 | 9094.03 | 10-JAN-05:01 | 1.33 |
February | 63015774.78 | 9407.01 | 06-FEB-05:11 | 2.97 |
March | 50682532.32 | 8649.03 | 10-MAR-06:02 | 5.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 456992.25 | 1647.08 | 16-NOV-06:03 | 9.40 |
December | 98705369.40 | 9097.39 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.361656E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.148795E+09 | 9407.01 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89479362.26 | 10913.16 | 10-JAN-05:01 | 1.33 |
February | 40404801.43 | 10987.24 | 06-FEB-05:11 | 2.97 |
March | 44485504.31 | 10759.08 | 10-MAR-06:02 | 5.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 61620455.91 | 10896.18 | 20-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.235990E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 89479362.26 | 10987.24 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98141955.10 | 8052.32 | 10-JAN-05:01 | 1.33 |
February | 42184524.71 | 8117.29 | 06-FEB-05:11 | 2.97 |
March | 23695689.43 | 7591.73 | 10-MAR-06:02 | 5.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 43048002.37 | 7900.14 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.207070E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 98141955.10 | 8117.29 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117335E+10 | 12882.10 | 23-JAN-05:11 | 7.67 |
February | 0.710218E+09 | 13698.39 | 05-FEB-07:03 | -3.4 |
March | 0.428831E+09 | 12256.36 | 13-MAR-04:11 | 7.00 |
April | 2366137.01 | 10590.63 | 03-APR-05:01 | 12.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 5485765.50 | 8084.61 | 28-OCT-05:03 | 10.00 |
November | 0.100726E+09 | 11345.21 | 16-NOV-05:11 | 9.27 |
December | 0.741684E+09 | 12668.89 | 21-DEC-04:01 | 1.67 |
Annual Sum or Average | 0.316266E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.4 | |
Maximum of Months | 0.117335E+10 | 13698.39 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.539053E+09 | 11987.08 | 23-JAN-05:11 | 7.67 |
February | 0.299773E+09 | 12975.60 | 06-FEB-05:21 | 2.90 |
March | 0.236560E+09 | 11334.69 | 10-MAR-05:11 | 5.77 |
April | 129237.51 | 1839.63 | 03-APR-05:01 | 12.28 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 3340433.13 | 5297.52 | 28-OCT-05:03 | 10.00 |
November | 37706797.42 | 10355.45 | 16-NOV-05:11 | 9.27 |
December | 0.395679E+09 | 11951.91 | 21-DEC-04:01 | 1.67 |
Annual Sum or Average | 0.151224E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.67 | |
Maximum of Months | 0.539053E+09 | 12975.60 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530834E+09 | 13621.69 | 09-JAN-05:11 | 7.67 |
February | 0.332707E+09 | 15296.08 | 05-FEB-07:03 | -3.4 |
March | 0.303715E+09 | 13371.98 | 10-MAR-05:11 | 5.77 |
April | 101209.05 | 489.33 | 11-APR-05:08 | 10.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 206857.23 | 1357.13 | 28-OCT-05:03 | 10.00 |
November | 16116237.66 | 11985.62 | 16-NOV-06:03 | 9.40 |
December | 0.345464E+09 | 13859.34 | 20-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.152914E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.4 | |
Maximum of Months | 0.530834E+09 | 15296.08 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.436211E+09 | 11136.69 | 23-JAN-05:11 | 7.67 |
February | 0.246204E+09 | 12462.94 | 06-FEB-04:01 | 3.35 |
March | 0.146594E+09 | 10688.09 | 09-MAR-05:11 | 1.77 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 17216466.56 | 8724.48 | 16-NOV-06:03 | 9.40 |
December | 0.240356E+09 | 11077.99 | 20-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.108658E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.77 | |
Maximum of Months | 0.436211E+09 | 12462.94 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48508204.16 | 9449.61 | 09-JAN-05:11 | 7.67 |
February | 47443106.69 | 9056.20 | 06-FEB-05:11 | 2.97 |
March | 53151390.43 | 9670.90 | 13-MAR-04:11 | 7.00 |
April | 71351982.40 | 9435.66 | 04-APR-03:01 | 16.87 |
May | 38569391.19 | 7575.90 | 02-MAY-03:01 | 24.13 |
June | 46176103.13 | 7125.64 | 02-JUN-03:01 | 24.40 |
July | 42153729.21 | 3831.09 | 23-JUL-15:02 | 31.78 |
August | 35760755.61 | 6359.26 | 20-AUG-13:51 | 34.00 |
September | 38391666.50 | 7807.77 | 29-SEP-03:01 | 23.80 |
October | 59644375.74 | 8097.14 | 31-OCT-03:01 | 18.83 |
November | 68465533.71 | 9837.17 | 20-NOV-04:01 | 16.37 |
December | 83626909.73 | 12877.22 | 25-DEC-09:41 | 11.83 |
Annual Sum or Average | 0.633243E+09 | |||
Minimum of Months | 35760755.61 | 3831.09 | 2.97 | |
Maximum of Months | 83626909.73 | 12877.22 | 34.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140665E+09 | 6852.72 | 16-JAN-10:17 | 20.33 |
February | 0.104243E+09 | 5698.86 | 16-FEB-06:03 | 16.33 |
March | 69313343.97 | 5422.58 | 20-MAR-05:02 | 12.10 |
April | 20016201.86 | 4968.97 | 10-APR-05:01 | 12.20 |
May | 23580204.03 | 6399.64 | 22-MAY-03:02 | 26.10 |
June | 15186297.54 | 6082.04 | 29-JUN-03:01 | 25.60 |
July | 19699917.41 | 6189.03 | 19-JUL-03:01 | 27.20 |
August | 16928932.40 | 6022.19 | 23-AUG-03:01 | 26.48 |
September | 24552622.87 | 6231.06 | 10-SEP-15:11 | 35.17 |
October | 25104688.50 | 5955.09 | 23-OCT-03:01 | 24.98 |
November | 32088200.21 | 5362.18 | 29-NOV-06:02 | 21.60 |
December | 69017018.58 | 5628.11 | 28-DEC-06:03 | 17.83 |
Annual Sum or Average | 0.560395E+09 | |||
Minimum of Months | 15186297.54 | 4968.97 | 12.10 | |
Maximum of Months | 0.140665E+09 | 6852.72 | 35.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155959E+10 | 12035.59 | 10-JAN-06:03 | 3.00 |
February | 0.992927E+09 | 18935.22 | 06-FEB-06:12 | 3.07 |
March | 0.795375E+09 | 13168.92 | 08-MAR-06:03 | 11.00 |
April | 0.149282E+09 | 15187.42 | 17-APR-05:01 | 12.70 |
May | 25753695.14 | 9634.55 | 01-MAY-04:01 | 26.10 |
June | 23284222.18 | 8644.28 | 07-JUN-04:11 | 21.10 |
July | 18935198.04 | 7411.49 | 21-JUL-03:01 | 25.60 |
August | 20308286.39 | 7615.27 | 17-AUG-04:11 | 21.93 |
September | 23164249.41 | 8091.71 | 08-SEP-05:02 | 24.58 |
October | 80318939.54 | 12461.48 | 27-OCT-05:03 | 15.00 |
November | 0.331750E+09 | 10904.24 | 30-NOV-06:03 | 15.08 |
December | 0.110967E+10 | 11918.32 | 21-DEC-06:13 | 0.67 |
Annual Sum or Average | 0.513036E+10 | |||
Minimum of Months | 18935198.04 | 7411.49 | 0.67 | |
Maximum of Months | 0.155959E+10 | 18935.22 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184240E+09 | 521.07 | 23-JAN-04:50 | 8.00 |
February | 766479.57 | 398.49 | 05-FEB-07:38 | -3.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.185007E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.4 | |
Maximum of Months | 0.184240E+09 | 521.07 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.192167E+11 | 19994.87 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.174303E+11 | 19994.87 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.207002E+11 | 19994.87 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.185016E+11 | 19994.87 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.199585E+11 | 19994.87 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.198575E+11 | 19994.87 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.186026E+11 | 19994.87 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.207002E+11 | 19994.87 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.185016E+11 | 19994.87 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.192167E+11 | 19994.87 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.189882E+11 | 19994.87 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.186026E+11 | 19994.87 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.230277E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.174303E+11 | 19994.87 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.207002E+11 | 19994.87 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.172580E+11 | 17956.80 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.156537E+11 | 17956.80 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.185902E+11 | 17956.80 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.166157E+11 | 17956.80 | 03-APR-07:10 | 0.235253E+11 | 17206.63 | 03-APR-07:10 |
May | 0.179241E+11 | 17956.80 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.178334E+11 | 17956.80 | 01-JUN-07:10 | 0.244214E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.167064E+11 | 17956.80 | 03-JUL-07:10 | 0.239654E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.185902E+11 | 17956.80 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.166157E+11 | 17956.80 | 01-SEP-07:10 | 0.235253E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.172580E+11 | 17956.80 | 02-OCT-07:10 | 0.243681E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.170527E+11 | 17956.80 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.167064E+11 | 17956.80 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.206805E+12 | 0.289609E+12 | ||||
Minimum of Months | 0.156537E+11 | 17956.80 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.185902E+11 | 17956.80 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.172580E+11 | 17956.80 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.156537E+11 | 17956.80 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.185902E+11 | 17956.80 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.166157E+11 | 17956.80 | 03-APR-07:10 | 0.235252E+11 | 17206.56 | 03-APR-07:10 |
May | 0.179241E+11 | 17956.80 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.178334E+11 | 17956.80 | 01-JUN-07:10 | 0.244213E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.167064E+11 | 17956.80 | 03-JUL-07:10 | 0.239653E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.185902E+11 | 17956.80 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.166157E+11 | 17956.80 | 01-SEP-07:10 | 0.235252E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.172580E+11 | 17956.80 | 02-OCT-07:10 | 0.243680E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.170527E+11 | 17956.80 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.167064E+11 | 17956.80 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.206805E+12 | 0.289607E+12 | ||||
Minimum of Months | 0.156537E+11 | 17956.80 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.185902E+11 | 17956.80 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.172580E+11 | 17956.80 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.156537E+11 | 17956.80 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.185902E+11 | 17956.80 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.166157E+11 | 17956.80 | 03-APR-07:10 | 0.235252E+11 | 17206.56 | 03-APR-07:10 |
May | 0.179241E+11 | 17956.80 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.178334E+11 | 17956.80 | 01-JUN-07:10 | 0.244213E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.167064E+11 | 17956.80 | 03-JUL-07:10 | 0.239653E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.185902E+11 | 17956.80 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.166157E+11 | 17956.80 | 01-SEP-07:10 | 0.235252E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.172580E+11 | 17956.80 | 02-OCT-07:10 | 0.243680E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.170527E+11 | 17956.80 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.167064E+11 | 17956.80 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.206805E+12 | 0.289607E+12 | ||||
Minimum of Months | 0.156537E+11 | 17956.80 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.185902E+11 | 17956.80 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.137185E+10 | 1964.78 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.119352E+10 | 1964.78 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.136777E+10 | 1964.78 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.118669E+10 | 1964.78 | 06-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.123482E+10 | 1570.82 | 23-MAY-07:19 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.121049E+10 | 1176.85 | 16-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.114941E+10 | 1280.94 | 14-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.129882E+10 | 1570.82 | 08-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.120280E+10 | 1964.78 | 26-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.128464E+10 | 2254.66 | 25-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.134914E+10 | 1964.78 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.136100E+10 | 2254.66 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.152109E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.114941E+10 | 1176.85 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.137185E+10 | 2254.66 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.859768E+09 | 1266.18 | 03-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.754620E+09 | 1266.18 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.866819E+09 | 1266.18 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.761161E+09 | 1266.18 | 14-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.801650E+09 | 1012.30 | 30-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.788373E+09 | 758.41 | 16-JUN-14:30 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.746759E+09 | 758.41 | 11-JUL-15:39 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.838609E+09 | 825.49 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.770544E+09 | 1266.18 | 26-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.817947E+09 | 1452.99 | 25-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.849609E+09 | 1452.99 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.857139E+09 | 1452.99 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.971300E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.746759E+09 | 758.41 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.866819E+09 | 1452.99 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.128679E+10 | 1964.82 | 13-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.114571E+10 | 1964.82 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.134268E+10 | 1964.82 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.118974E+10 | 1964.82 | 06-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.125206E+10 | 1570.85 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.123067E+10 | 1176.88 | 02-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.116420E+10 | 1570.85 | 14-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.130701E+10 | 1570.85 | 08-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.119613E+10 | 1964.82 | 26-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.126110E+10 | 2254.70 | 25-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.127475E+10 | 1964.82 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.127356E+10 | 2254.70 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.149244E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.114571E+10 | 1176.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.134268E+10 | 2254.70 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.851326E+09 | 1266.18 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.753189E+09 | 1452.99 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.878302E+09 | 1266.18 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.769251E+09 | 1266.18 | 06-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.804952E+09 | 1012.30 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.789890E+09 | 1012.30 | 16-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.749896E+09 | 1012.30 | 11-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.845952E+09 | 1266.18 | 08-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.780553E+09 | 1266.18 | 13-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.823701E+09 | 1452.99 | 25-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.838561E+09 | 1452.99 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.839749E+09 | 1452.99 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.972532E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.749896E+09 | 1012.30 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.878302E+09 | 1452.99 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.136371E+10 | 1964.78 | 13-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.118841E+10 | 1964.78 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.136250E+10 | 1964.78 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.118400E+10 | 1964.78 | 14-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.123315E+10 | 1570.82 | 23-MAY-07:19 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.120799E+10 | 1072.77 | 01-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.114862E+10 | 1280.94 | 14-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.129759E+10 | 1570.82 | 08-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.120015E+10 | 1964.78 | 26-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.128178E+10 | 2254.66 | 25-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.134227E+10 | 1964.78 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.135463E+10 | 2254.66 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.151648E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.114862E+10 | 1072.77 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.136371E+10 | 2254.66 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.856623E+09 | 1266.18 | 31-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.753064E+09 | 1266.18 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.865021E+09 | 1199.10 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.760392E+09 | 1266.18 | 14-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.799901E+09 | 825.49 | 23-MAY-07:19 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.787396E+09 | 758.41 | 27-JUN-13:30 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.745486E+09 | 758.41 | 11-JUL-15:39 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.837556E+09 | 825.49 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.769611E+09 | 1012.30 | 26-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.816598E+09 | 1452.99 | 25-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.847407E+09 | 1452.99 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.854233E+09 | 1452.99 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.969329E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.745486E+09 | 758.41 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.865021E+09 | 1452.99 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.128606E+10 | 1964.82 | 13-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.114480E+10 | 1964.82 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.134031E+10 | 1964.82 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.118775E+10 | 1964.82 | 06-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.124975E+10 | 1570.85 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.122879E+10 | 1176.88 | 02-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.116235E+10 | 1280.97 | 11-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.130505E+10 | 1570.85 | 08-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.119429E+10 | 1964.82 | 26-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.125930E+10 | 2254.70 | 25-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.127233E+10 | 1964.82 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.127230E+10 | 2254.70 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.149031E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.114480E+10 | 1176.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.134031E+10 | 2254.70 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.848804E+09 | 1266.18 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.751569E+09 | 1266.18 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.875687E+09 | 1266.18 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.767710E+09 | 1266.18 | 06-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.803735E+09 | 1012.30 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.788473E+09 | 1012.30 | 16-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.748296E+09 | 1012.30 | 11-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.842939E+09 | 1199.10 | 08-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.778673E+09 | 1266.18 | 13-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.822083E+09 | 1452.99 | 25-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.836408E+09 | 1452.99 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.837004E+09 | 1452.99 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.970138E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.748296E+09 | 1012.30 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.875687E+09 | 1452.99 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.136358E+10 | 1964.78 | 13-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.118837E+10 | 1964.78 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.136225E+10 | 1964.78 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.118400E+10 | 1964.78 | 14-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.123303E+10 | 1570.82 | 23-MAY-07:19 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.120795E+10 | 1072.77 | 01-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.114845E+10 | 1280.94 | 14-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.129759E+10 | 1570.82 | 08-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.119977E+10 | 1964.78 | 26-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.128173E+10 | 2254.66 | 25-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.134209E+10 | 1964.78 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.135463E+10 | 2254.66 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.151634E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.114845E+10 | 1072.77 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.136358E+10 | 2254.66 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.856576E+09 | 1266.18 | 31-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.753024E+09 | 1266.18 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.864919E+09 | 1199.10 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.760377E+09 | 1266.18 | 14-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.799859E+09 | 825.49 | 23-MAY-07:19 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.787354E+09 | 758.41 | 27-JUN-13:30 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.745372E+09 | 758.41 | 11-JUL-15:39 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.837489E+09 | 825.49 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.769535E+09 | 1012.30 | 26-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.816516E+09 | 1452.99 | 25-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.847358E+09 | 1452.99 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.854233E+09 | 1452.99 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.969261E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.745372E+09 | 758.41 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.864919E+09 | 1452.99 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.128602E+10 | 1964.82 | 13-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.114480E+10 | 1964.82 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.134019E+10 | 1964.82 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.118759E+10 | 1964.82 | 06-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.124952E+10 | 1570.85 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.122872E+10 | 1176.88 | 02-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.116229E+10 | 1280.97 | 11-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.130488E+10 | 1570.85 | 08-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.119420E+10 | 1964.82 | 26-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.125930E+10 | 2254.70 | 25-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.127233E+10 | 1964.82 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.127230E+10 | 2254.70 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.149021E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.114480E+10 | 1176.88 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.134019E+10 | 2254.70 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.848804E+09 | 1266.18 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.751516E+09 | 1266.18 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.875640E+09 | 1266.18 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.767707E+09 | 1266.18 | 06-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.803709E+09 | 1012.30 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.788470E+09 | 1012.30 | 16-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.748218E+09 | 1012.30 | 11-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.842939E+09 | 1199.10 | 08-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.778521E+09 | 1266.18 | 13-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.822083E+09 | 1452.99 | 25-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.836314E+09 | 1452.99 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.836843E+09 | 1452.99 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.970076E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.748218E+09 | 1012.30 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.875640E+09 | 1452.99 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.541830E+10 | 5637.70 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.491461E+10 | 5637.70 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.583657E+10 | 5637.70 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.521665E+10 | 5637.70 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.562743E+10 | 5637.70 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.559896E+10 | 5637.70 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.524512E+10 | 5637.70 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.583657E+10 | 5637.70 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.521665E+10 | 5637.70 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.541830E+10 | 5637.70 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.535386E+10 | 5637.70 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.524512E+10 | 5637.70 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.649281E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.491461E+10 | 5637.70 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.583657E+10 | 5637.70 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.250303E+09 | 260.44 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.227035E+09 | 260.44 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.269625E+09 | 260.44 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.240988E+09 | 260.44 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.259964E+09 | 260.44 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.258649E+09 | 260.44 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.242303E+09 | 260.44 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.269625E+09 | 260.44 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.240988E+09 | 260.44 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.250303E+09 | 260.44 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.247326E+09 | 260.44 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.242303E+09 | 260.44 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.299941E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.227035E+09 | 260.44 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.269625E+09 | 260.44 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.250303E+09 | 260.44 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.227035E+09 | 260.44 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.269625E+09 | 260.44 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.240988E+09 | 260.44 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.259964E+09 | 260.44 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.258649E+09 | 260.44 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.242303E+09 | 260.44 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.269625E+09 | 260.44 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.240988E+09 | 260.44 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.250303E+09 | 260.44 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.247326E+09 | 260.44 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.242303E+09 | 260.44 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.299941E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.227035E+09 | 260.44 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.269625E+09 | 260.44 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.250303E+09 | 260.44 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.227035E+09 | 260.44 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.269625E+09 | 260.44 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.240988E+09 | 260.44 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.259964E+09 | 260.44 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.258649E+09 | 260.44 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.242303E+09 | 260.44 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.269625E+09 | 260.44 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.240988E+09 | 260.44 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.250303E+09 | 260.44 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.247326E+09 | 260.44 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.242303E+09 | 260.44 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.299941E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.227035E+09 | 260.44 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.269625E+09 | 260.44 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.192167E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.174303E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.207002E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.185016E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.199585E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.198575E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.186026E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.207002E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.185016E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.192167E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.189882E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.186026E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.230277E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.174303E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.207002E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.172580E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.156537E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.185902E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.166157E+11 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.179241E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.178334E+11 | 0.244214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.167064E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.185902E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.166157E+11 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.172580E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.170527E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.167064E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.206805E+12 | 0.289609E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.156537E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.185902E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.172580E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.156537E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.185902E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.166157E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.179241E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.178334E+11 | 0.244213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.167064E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.185902E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.166157E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.172580E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.170527E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.167064E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.206805E+12 | 0.289607E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.156537E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.185902E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.172580E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.156537E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.185902E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.166157E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.179241E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.178334E+11 | 0.244213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.167064E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.185902E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.166157E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.172580E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.170527E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.167064E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.206805E+12 | 0.289607E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.156537E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.185902E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.137185E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1133224.26 | 0.374534E+09 |
February | 0.136985E+10 | 0.119352E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2110183.86 | 0.291386E+09 |
March | 0.163685E+10 | 0.136777E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6458063.20 | 0.307348E+09 |
April | 0.145243E+10 | 0.118669E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14077729.51 | 0.129748E+09 |
May | 0.157338E+10 | 0.123482E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57536696.19 | 19341247.03 |
June | 0.156900E+10 | 0.121049E+10 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54733923.33 | 11890326.57 |
July | 0.145680E+10 | 0.114941E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82108894.88 | 2068623.80 |
August | 0.163685E+10 | 0.129882E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78682606.48 | 10818215.66 |
September | 0.145243E+10 | 0.120280E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64989319.57 | 32703370.38 |
October | 0.150991E+10 | 0.128464E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54360218.32 | 0.109221E+09 |
November | 0.149516E+10 | 0.134914E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5659429.27 | 0.194268E+09 |
December | 0.145680E+10 | 0.136100E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3611816.02 | 0.344522E+09 |
Annual Sum or Average | 0.181194E+11 | 0.152109E+11 | 0.363647E+11 | 0.425462E+09 | 0.182785E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.114941E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1133224.26 | 2068623.80 |
Maximum of Months | 0.163685E+10 | 0.137185E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82108894.88 | 0.374534E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.859768E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 675789.79 | 0.249820E+09 |
February | 0.882782E+09 | 0.754620E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1383472.91 | 0.192838E+09 |
March | 0.105485E+10 | 0.866819E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4035770.69 | 0.198777E+09 |
April | 0.936002E+09 | 0.761161E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9832008.47 | 80906135.70 |
May | 0.101394E+10 | 0.801650E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38214570.18 | 12033049.38 |
June | 0.101113E+10 | 0.788373E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38155005.53 | 6388590.08 |
July | 0.938820E+09 | 0.746759E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59660459.64 | 793749.61 |
August | 0.105485E+10 | 0.838609E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58966560.86 | 4127021.85 |
September | 0.936002E+09 | 0.770544E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42817469.30 | 19767302.01 |
October | 0.973041E+09 | 0.817947E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36524292.79 | 68372774.92 |
November | 0.963541E+09 | 0.849609E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3763271.29 | 0.125732E+09 |
December | 0.938820E+09 | 0.857139E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2390934.35 | 0.217492E+09 |
Annual Sum or Average | 0.116768E+11 | 0.971300E+10 | 0.234348E+11 | 0.296420E+09 | 0.117705E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.746759E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 675789.79 | 793749.61 |
Maximum of Months | 0.105485E+10 | 0.866819E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59660459.64 | 0.249820E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.128679E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 481723.32 | 0.402365E+09 |
February | 0.136988E+10 | 0.114571E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1413635.91 | 0.307869E+09 |
March | 0.163688E+10 | 0.134268E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4862803.63 | 0.308853E+09 |
April | 0.145246E+10 | 0.118974E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13201237.73 | 0.130195E+09 |
May | 0.157341E+10 | 0.125206E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57627881.73 | 18953193.27 |
June | 0.156904E+10 | 0.123067E+10 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55033385.26 | 11573621.74 |
July | 0.145684E+10 | 0.116420E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81297263.14 | 2140744.26 |
August | 0.163688E+10 | 0.130701E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76703474.71 | 11283253.43 |
September | 0.145246E+10 | 0.119613E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60405273.07 | 34867088.24 |
October | 0.150994E+10 | 0.126110E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43977903.06 | 0.122604E+09 |
November | 0.149520E+10 | 0.127475E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3802851.63 | 0.210695E+09 |
December | 0.145684E+10 | 0.127356E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2429567.23 | 0.364838E+09 |
Annual Sum or Average | 0.181198E+11 | 0.149244E+11 | 0.363653E+11 | 0.401237E+09 | 0.192624E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.114571E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 481723.32 | 2140744.26 |
Maximum of Months | 0.163688E+10 | 0.134268E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81297263.14 | 0.402365E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.851326E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 616735.89 | 0.268968E+09 |
February | 0.882782E+09 | 0.753189E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1168809.14 | 0.216317E+09 |
March | 0.105485E+10 | 0.878302E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3500386.54 | 0.236188E+09 |
April | 0.936002E+09 | 0.769251E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7225457.01 | 0.111356E+09 |
May | 0.101394E+10 | 0.804952E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36376168.54 | 20567064.49 |
June | 0.101113E+10 | 0.789890E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32333571.21 | 13765698.10 |
July | 0.938820E+09 | 0.749896E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44785872.83 | 5407774.78 |
August | 0.105485E+10 | 0.845952E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43483681.26 | 17156440.17 |
September | 0.936002E+09 | 0.780553E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39599820.98 | 31056467.52 |
October | 0.973041E+09 | 0.823701E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31044419.74 | 93428009.81 |
November | 0.963541E+09 | 0.838561E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3020975.02 | 0.152208E+09 |
December | 0.938820E+09 | 0.839749E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1921435.94 | 0.270030E+09 |
Annual Sum or Average | 0.116768E+11 | 0.972532E+10 | 0.234347E+11 | 0.245077E+09 | 0.143645E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.749896E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 616735.89 | 5407774.78 |
Maximum of Months | 0.105485E+10 | 0.878302E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44785872.83 | 0.270030E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.136371E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6143235.25 | 0.711720E+09 |
February | 0.136985E+10 | 0.118841E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7203348.74 | 0.544935E+09 |
March | 0.163685E+10 | 0.136250E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19770414.57 | 0.586109E+09 |
April | 0.145243E+10 | 0.118400E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30964690.74 | 0.260050E+09 |
May | 0.157338E+10 | 0.123315E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126730E+09 | 41840094.31 |
June | 0.156900E+10 | 0.120799E+10 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115042E+09 | 32422950.36 |
July | 0.145680E+10 | 0.114862E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161194E+09 | 12367063.40 |
August | 0.163685E+10 | 0.129759E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154056E+09 | 41615045.17 |
September | 0.145243E+10 | 0.120015E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145841E+09 | 64685195.65 |
October | 0.150991E+10 | 0.128178E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121896E+09 | 0.220315E+09 |
November | 0.149516E+10 | 0.134227E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17119392.42 | 0.366009E+09 |
December | 0.145680E+10 | 0.135463E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11465733.80 | 0.638050E+09 |
Annual Sum or Average | 0.181194E+11 | 0.151648E+11 | 0.363647E+11 | 0.917427E+09 | 0.352012E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.114862E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6143235.25 | 12367063.40 |
Maximum of Months | 0.163685E+10 | 0.136371E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161194E+09 | 0.711720E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.856623E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2550160.48 | 0.497524E+09 |
February | 0.649041E+09 | 0.753064E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3875223.05 | 0.384417E+09 |
March | 0.773965E+09 | 0.865021E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9536836.35 | 0.412878E+09 |
April | 0.688021E+09 | 0.760392E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19063779.94 | 0.187369E+09 |
May | 0.744847E+09 | 0.799901E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79757231.66 | 31017866.15 |
June | 0.742030E+09 | 0.787396E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75186872.22 | 22900295.16 |
July | 0.690839E+09 | 0.745486E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104243E+09 | 10069554.33 |
August | 0.773965E+09 | 0.837556E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101148E+09 | 28975885.78 |
September | 0.688021E+09 | 0.769611E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91866816.04 | 45103535.01 |
October | 0.715730E+09 | 0.816598E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74566857.72 | 0.156244E+09 |
November | 0.708685E+09 | 0.847407E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8888798.16 | 0.260755E+09 |
December | 0.690839E+09 | 0.854233E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6000410.79 | 0.438704E+09 |
Annual Sum or Average | 0.858171E+10 | 0.969329E+10 | 0.234348E+11 | 0.576685E+09 | 0.247596E+10 | ||||
Minimum of Months | 0.649041E+09 | 0.745486E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2550160.48 | 10069554.33 |
Maximum of Months | 0.773965E+09 | 0.865021E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104243E+09 | 0.497524E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.128606E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 869755.58 | 0.865492E+09 |
February | 0.136988E+10 | 0.114480E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2674046.67 | 0.651084E+09 |
March | 0.163688E+10 | 0.134031E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10734531.08 | 0.639624E+09 |
April | 0.145246E+10 | 0.118775E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28374777.89 | 0.279505E+09 |
May | 0.157341E+10 | 0.124975E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126523E+09 | 42875545.06 |
June | 0.156904E+10 | 0.122879E+10 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116543E+09 | 31622226.81 |
July | 0.145684E+10 | 0.116235E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161502E+09 | 12636711.60 |
August | 0.163688E+10 | 0.130505E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150034E+09 | 44460740.84 |
September | 0.145246E+10 | 0.119429E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130557E+09 | 76278671.21 |
October | 0.150994E+10 | 0.125930E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91701067.16 | 0.282506E+09 |
November | 0.149520E+10 | 0.127233E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7627675.52 | 0.455025E+09 |
December | 0.145684E+10 | 0.127230E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4825616.32 | 0.774309E+09 |
Annual Sum or Average | 0.181198E+11 | 0.149031E+11 | 0.363653E+11 | 0.831966E+09 | 0.415542E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.114480E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 869755.58 | 12636711.60 |
Maximum of Months | 0.163688E+10 | 0.134031E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161502E+09 | 0.865492E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.848804E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2440771.89 | 0.520102E+09 |
February | 0.882782E+09 | 0.751569E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3445065.18 | 0.398922E+09 |
March | 0.105485E+10 | 0.875687E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10708738.01 | 0.427749E+09 |
April | 0.936002E+09 | 0.767710E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16879843.99 | 0.208967E+09 |
May | 0.101394E+10 | 0.803735E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81265278.74 | 37921818.02 |
June | 0.101113E+10 | 0.788473E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71375013.18 | 30581397.99 |
July | 0.938820E+09 | 0.748296E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98995153.78 | 16109962.51 |
August | 0.105485E+10 | 0.842939E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97296851.46 | 41169923.71 |
September | 0.936002E+09 | 0.778673E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88480473.77 | 56827869.59 |
October | 0.973041E+09 | 0.822083E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72657928.11 | 0.179906E+09 |
November | 0.963541E+09 | 0.836408E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9599955.04 | 0.270776E+09 |
December | 0.938820E+09 | 0.837004E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5906663.40 | 0.470554E+09 |
Annual Sum or Average | 0.116768E+11 | 0.970138E+10 | 0.234347E+11 | 0.559052E+09 | 0.265959E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.748296E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2440771.89 | 16109962.51 |
Maximum of Months | 0.105485E+10 | 0.875687E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98995153.78 | 0.520102E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.136358E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9435084.28 | 0.807197E+09 |
February | 0.136985E+10 | 0.118837E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9453295.73 | 0.618074E+09 |
March | 0.163685E+10 | 0.136225E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23112969.73 | 0.680547E+09 |
April | 0.145243E+10 | 0.118400E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35646507.10 | 0.311023E+09 |
May | 0.157338E+10 | 0.123303E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147073E+09 | 58405897.30 |
June | 0.156900E+10 | 0.120795E+10 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133362E+09 | 44802673.86 |
July | 0.145680E+10 | 0.114845E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184261E+09 | 19939542.67 |
August | 0.163685E+10 | 0.129759E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180499E+09 | 55950196.58 |
September | 0.145243E+10 | 0.119977E+10 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167077E+09 | 85344919.98 |
October | 0.150991E+10 | 0.128173E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139774E+09 | 0.261256E+09 |
November | 0.149516E+10 | 0.134209E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22230652.41 | 0.413805E+09 |
December | 0.145680E+10 | 0.135463E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15518224.91 | 0.727014E+09 |
Annual Sum or Average | 0.181194E+11 | 0.151634E+11 | 0.363647E+11 | 0.106744E+10 | 0.408336E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.114845E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9435084.28 | 19939542.67 |
Maximum of Months | 0.163685E+10 | 0.136358E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184261E+09 | 0.807197E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.856576E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3801779.92 | 0.565892E+09 |
February | 0.882782E+09 | 0.753024E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4684838.10 | 0.436395E+09 |
March | 0.105485E+10 | 0.864919E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10956486.95 | 0.484613E+09 |
April | 0.936002E+09 | 0.760377E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21901162.52 | 0.226481E+09 |
May | 0.101394E+10 | 0.799859E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93890895.59 | 42508210.32 |
June | 0.101113E+10 | 0.787354E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88132884.24 | 31388187.35 |
July | 0.938820E+09 | 0.745372E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121126E+09 | 15510194.19 |
August | 0.105485E+10 | 0.837489E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119750E+09 | 38689961.07 |
September | 0.936002E+09 | 0.769535E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106840E+09 | 59306053.56 |
October | 0.973041E+09 | 0.816516E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86623014.58 | 0.186768E+09 |
November | 0.963541E+09 | 0.847358E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10890213.65 | 0.299352E+09 |
December | 0.938820E+09 | 0.854233E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7639662.21 | 0.502824E+09 |
Annual Sum or Average | 0.116768E+11 | 0.969261E+10 | 0.234348E+11 | 0.676237E+09 | 0.288973E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.745372E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3801779.92 | 15510194.19 |
Maximum of Months | 0.105485E+10 | 0.864919E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121126E+09 | 0.565892E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.128602E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1013507.91 | 0.996865E+09 |
February | 0.136988E+10 | 0.114480E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3392586.07 | 0.741193E+09 |
March | 0.163688E+10 | 0.134019E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12591892.13 | 0.746268E+09 |
April | 0.145246E+10 | 0.118759E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32736665.01 | 0.334872E+09 |
May | 0.157341E+10 | 0.124952E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147141E+09 | 59632591.51 |
June | 0.156904E+10 | 0.122872E+10 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135118E+09 | 43777110.82 |
July | 0.145684E+10 | 0.116229E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184929E+09 | 20268160.31 |
August | 0.163688E+10 | 0.130488E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177194E+09 | 59393367.18 |
September | 0.145246E+10 | 0.119420E+10 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153439E+09 | 99325379.00 |
October | 0.150994E+10 | 0.125930E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109624E+09 | 0.338278E+09 |
November | 0.149520E+10 | 0.127233E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9727164.52 | 0.528949E+09 |
December | 0.145684E+10 | 0.127230E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6267483.41 | 0.892617E+09 |
Annual Sum or Average | 0.181198E+11 | 0.149021E+11 | 0.363653E+11 | 0.973174E+09 | 0.486144E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.114480E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1013507.91 | 20268160.31 |
Maximum of Months | 0.163688E+10 | 0.134019E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184929E+09 | 0.996865E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.848804E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3442887.60 | 0.603976E+09 |
February | 0.882782E+09 | 0.751516E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4339572.68 | 0.460977E+09 |
March | 0.105485E+10 | 0.875640E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12773848.06 | 0.502920E+09 |
April | 0.936002E+09 | 0.767707E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20348093.32 | 0.250806E+09 |
May | 0.101394E+10 | 0.803709E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98192660.94 | 49556623.88 |
June | 0.101113E+10 | 0.788470E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86108179.95 | 39752242.43 |
July | 0.938820E+09 | 0.748218E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118914E+09 | 22277444.71 |
August | 0.105485E+10 | 0.842939E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117664E+09 | 52275189.65 |
September | 0.936002E+09 | 0.778521E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106614E+09 | 71697227.63 |
October | 0.973041E+09 | 0.822083E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86980020.71 | 0.214057E+09 |
November | 0.963541E+09 | 0.836314E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12622962.62 | 0.313087E+09 |
December | 0.938820E+09 | 0.836843E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7750547.93 | 0.546872E+09 |
Annual Sum or Average | 0.116768E+11 | 0.970076E+10 | 0.234347E+11 | 0.675751E+09 | 0.312825E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.748218E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3442887.60 | 22277444.71 |
Maximum of Months | 0.105485E+10 | 0.875640E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118914E+09 | 0.603976E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.541830E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.491461E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.583657E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.521665E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.562743E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.559896E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.524512E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.583657E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.521665E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.541830E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.535386E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.524512E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.649281E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.491461E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.583657E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.250303E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.227035E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.269625E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.240988E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.259964E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.258649E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.242303E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.269625E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.240988E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.250303E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.247326E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.242303E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299941E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.227035E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.269625E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.250303E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.227035E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.269625E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.240988E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.259964E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.258649E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.242303E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.269625E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.240988E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.250303E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.247326E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.242303E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299941E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.227035E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.269625E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.250303E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.227035E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.269625E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.240988E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.259964E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.258649E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.242303E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.269625E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.240988E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.250303E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.247326E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.242303E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.299941E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.227035E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.269625E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811625.71 | 0.821623E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2162137.78 | 0.637385E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8564722.36 | 0.661171E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20580274.83 | 0.285666E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97819931.19 | 35194123.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91987105.83 | 26843216.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143276E+09 | 6433313.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129184E+09 | 32651190.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111866E+09 | 67069307.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86712248.55 | 0.244680E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7144512.47 | 0.428589E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4574013.56 | 0.750678E+09 |
Annual Sum or Average | 0.704683E+09 | 0.399798E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811625.71 | 6433313.13 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143276E+09 | 0.821623E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3530901.89 | 0.135730E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6266455.85 | 0.105074E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22347704.38 | 0.108957E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39665358.73 | 0.475672E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185380E+09 | 56361975.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168431E+09 | 46970387.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255274E+09 | 13015492.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228817E+09 | 64397886.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214675E+09 | 0.104842E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163669E+09 | 0.406710E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15890244.62 | 0.707319E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10559370.81 | 0.121939E+10 |
Annual Sum or Average | 0.131451E+10 | 0.659230E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3530901.89 | 13015492.59 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255274E+09 | 0.135730E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2040744.22 | 0.135270E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2598868.89 | 0.104656E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12145700.73 | 0.114225E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26169418.49 | 0.529893E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162085E+09 | 71235217.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152464E+09 | 55957912.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227514E+09 | 20732206.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216392E+09 | 76467262.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201660E+09 | 0.119169E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133866E+09 | 0.424941E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11679078.04 | 0.708114E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8508340.10 | 0.121885E+10 |
Annual Sum or Average | 0.115713E+10 | 0.676687E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2040744.22 | 20732206.94 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227514E+09 | 0.135270E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19994.87 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19994.87 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19994.87 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19994.87 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19994.87 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19994.87 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19994.87 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19994.87 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19994.87 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19994.87 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19994.87 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19994.87 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 19994.87 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19994.87 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17956.80 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17956.80 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17956.80 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17956.80 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17956.80 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17956.80 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17956.80 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17956.80 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17956.80 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17956.80 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17956.80 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17956.80 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 17956.80 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17956.80 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17956.80 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17956.80 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17956.80 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17956.80 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17956.80 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17956.80 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17956.80 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17956.80 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17956.80 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17956.80 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17956.80 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17956.80 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 17956.80 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17956.80 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17956.80 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17956.80 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17956.80 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17956.80 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17956.80 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17956.80 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17956.80 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17956.80 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17956.80 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17956.80 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17956.80 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17956.80 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 17956.80 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17956.80 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1964.78 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.63 | 16-JAN-15:00 | 713.76 | 09-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1964.78 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 | 02-FEB-13:00 | 989.13 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 1964.78 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.54 | 05-MAR-12:35 | 842.76 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1964.78 | 06-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.65 | 29-APR-17:01 | 513.40 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 1570.82 | 23-MAY-07:19 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.47 | 21-MAY-14:00 | 106.05 | 14-MAY-12:00 |
June | 2010.79 | 01-JUN-09:09 | 1176.85 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.47 | 10-JUN-17:02 | 153.35 | 06-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1280.94 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.96 | 22-JUL-18:50 | 86.20 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 1570.82 | 08-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.02 | 20-AUG-14:00 | 182.80 | 25-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1964.78 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.67 | 09-SEP-23:00 | 212.40 | 05-SEP-02:51 |
October | 2010.79 | 02-OCT-09:09 | 2254.66 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.95 | 09-OCT-13:51 | 418.82 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1964.78 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 | 11-NOV-12:30 | 606.12 | 12-NOV-08:00 |
December | 2010.79 | 01-DEC-10:09 | 2254.66 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.11 | 10-DEC-15:00 | 915.03 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1176.85 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 | 86.20 | |||||
Maximum of Months | 2010.79 | 2254.66 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 398.95 | 989.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1266.18 | 03-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.34 | 16-JAN-15:00 | 477.61 | 22-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1266.18 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 | 02-FEB-13:00 | 715.23 | 05-FEB-10:00 |
March | 1295.83 | 01-MAR-10:09 | 1266.18 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.64 | 05-MAR-13:00 | 543.32 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1266.18 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.41 | 29-APR-17:50 | 323.76 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 1012.30 | 30-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.59 | 21-MAY-14:00 | 92.93 | 14-MAY-12:00 |
June | 1295.83 | 01-JUN-09:09 | 758.41 | 16-JUN-14:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.97 | 10-JUN-17:02 | 91.76 | 06-JUN-22:10 |
July | 1295.83 | 03-JUL-09:09 | 758.41 | 11-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.01 | 22-JUL-18:50 | 87.97 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 825.49 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.38 | 20-AUG-14:00 | 107.19 | 25-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1266.18 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.20 | 09-SEP-22:53 | 138.36 | 05-SEP-02:51 |
October | 1295.83 | 02-OCT-09:09 | 1452.99 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.87 | 09-OCT-14:10 | 270.29 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1452.99 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 05-NOV-13:00 | 469.43 | 12-NOV-08:20 |
December | 1295.83 | 01-DEC-10:09 | 1452.99 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.41 | 10-DEC-15:00 | 578.30 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 758.41 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 | 87.97 | |||||
Maximum of Months | 1295.83 | 1452.99 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 264.87 | 715.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1964.82 | 13-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 31-JAN-14:30 | 702.59 | 22-JAN-16:55 |
February | 2010.83 | 01-FEB-10:09 | 1964.82 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.85 | 02-FEB-13:00 | 975.70 | 05-FEB-10:00 |
March | 2010.83 | 01-MAR-10:09 | 1964.82 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.62 | 26-MAR-13:48 | 841.04 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1964.82 | 06-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.26 | 29-APR-17:01 | 511.03 | 01-APR-21:00 |
May | 2010.83 | 01-MAY-09:09 | 1570.85 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.27 | 21-MAY-14:00 | 109.54 | 14-MAY-12:00 |
June | 2010.83 | 01-JUN-09:09 | 1176.88 | 02-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.52 | 10-JUN-17:02 | 150.85 | 06-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1570.85 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.82 | 22-JUL-18:50 | 91.01 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 1570.85 | 08-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.35 | 20-AUG-13:54 | 184.12 | 25-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1964.82 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.34 | 09-SEP-22:57 | 218.99 | 05-SEP-02:51 |
October | 2010.83 | 02-OCT-09:09 | 2254.70 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.92 | 09-OCT-13:44 | 427.20 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1964.82 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 | 28-NOV-13:00 | 655.64 | 12-NOV-08:20 |
December | 2010.83 | 01-DEC-10:09 | 2254.70 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.92 | 16-DEC-15:00 | 888.32 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1176.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 91.01 | |||||
Maximum of Months | 2010.83 | 2254.70 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 343.34 | 975.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1266.18 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.93 | 16-JAN-13:40 | 490.21 | 26-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1452.99 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 | 02-FEB-13:00 | 688.16 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 1266.18 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.43 | 26-MAR-13:50 | 619.68 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1266.18 | 06-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.82 | 29-APR-18:27 | 421.98 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 1012.30 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.86 | 21-MAY-14:00 | 89.56 | 09-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1012.30 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.08 | 10-JUN-17:07 | 142.36 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 1012.30 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.61 | 02-JUL-11:55 | 88.79 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 1266.18 | 08-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.00 | 20-AUG-13:53 | 165.03 | 25-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1266.18 | 13-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.19 | 09-SEP-22:53 | 161.16 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1452.99 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.99 | 09-OCT-12:10 | 321.67 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1452.99 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.71 | 11-NOV-12:30 | 439.81 | 12-NOV-08:00 |
December | 1295.83 | 01-DEC-10:09 | 1452.99 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.87 | 13-DEC-14:00 | 688.29 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1012.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 22.93 | 88.79 | |||||
Maximum of Months | 1295.83 | 1452.99 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 249.99 | 688.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1964.78 | 13-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.77 | 16-JAN-15:00 | 1432.75 | 21-JAN-05:59 |
February | 2010.79 | 01-FEB-10:09 | 1964.78 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 258.87 | 20-FEB-14:52 | 1885.55 | 05-FEB-07:55 |
March | 2010.79 | 01-MAR-10:09 | 1964.78 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 353.24 | 05-MAR-12:43 | 1656.10 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1964.78 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 419.93 | 29-APR-17:01 | 954.65 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 1570.82 | 23-MAY-07:19 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 549.68 | 07-MAY-13:52 | 190.27 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1072.77 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.90 | 10-JUN-17:02 | 288.46 | 06-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1280.94 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 622.39 | 22-JUL-18:50 | 173.86 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 1570.82 | 08-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 755.88 | 20-AUG-14:00 | 432.56 | 25-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1964.78 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 768.34 | 09-SEP-17:02 | 403.24 | 05-SEP-02:51 |
October | 2010.79 | 02-OCT-09:09 | 2254.66 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 919.51 | 09-OCT-14:00 | 776.58 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1964.78 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.52 | 05-NOV-13:00 | 1185.01 | 12-NOV-06:55 |
December | 2010.79 | 01-DEC-10:09 | 2254.66 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 202.55 | 10-DEC-14:50 | 1702.90 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 201.77 | 173.86 | |||||
Maximum of Months | 2010.79 | 2254.66 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 919.51 | 1885.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1266.18 | 31-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.47 | 16-JAN-15:00 | 955.16 | 21-JAN-06:00 |
February | 1239.33 | 01-FEB-08:09 | 1266.18 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 163.87 | 20-FEB-14:52 | 1398.48 | 05-FEB-10:00 |
March | 1239.33 | 01-MAR-08:09 | 1199.10 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 170.42 | 05-MAR-13:10 | 1113.50 | 20-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 1266.18 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.14 | 29-APR-17:50 | 650.17 | 01-APR-21:00 |
May | 1239.33 | 01-MAY-07:10 | 825.49 | 23-MAY-07:19 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.04 | 21-MAY-13:50 | 177.69 | 14-MAY-12:10 |
June | 1239.33 | 01-JUN-07:10 | 758.41 | 27-JUN-13:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 465.29 | 10-JUN-17:02 | 206.54 | 11-JUN-08:00 |
July | 1239.33 | 03-JUL-07:10 | 758.41 | 11-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 443.34 | 22-JUL-18:50 | 242.77 | 30-JUL-11:00 |
August | 1239.33 | 01-AUG-07:10 | 825.49 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 509.83 | 20-AUG-13:51 | 292.14 | 25-AUG-23:53 |
September | 1239.33 | 01-SEP-07:10 | 1012.30 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.52 | 09-SEP-22:53 | 284.16 | 05-SEP-02:51 |
October | 1239.33 | 02-OCT-07:10 | 1452.99 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 627.57 | 09-OCT-14:00 | 529.41 | 29-OCT-02:00 |
November | 1239.33 | 01-NOV-07:10 | 1452.99 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.47 | 05-NOV-13:00 | 966.29 | 12-NOV-09:00 |
December | 1239.33 | 01-DEC-08:09 | 1452.99 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.53 | 10-DEC-14:50 | 1133.32 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 758.41 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 111.47 | 177.69 | |||||
Maximum of Months | 1239.33 | 1452.99 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 627.57 | 1398.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1964.82 | 13-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.11 | 31-JAN-14:30 | 1589.96 | 22-JAN-16:55 |
February | 2010.83 | 01-FEB-10:09 | 1964.82 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 103.83 | 02-FEB-13:00 | 1982.53 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 1964.82 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 170.93 | 26-MAR-14:00 | 1725.54 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1964.82 | 06-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.19 | 29-APR-17:01 | 1027.25 | 01-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 1570.85 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 536.15 | 07-MAY-13:52 | 195.90 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1176.88 | 02-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 679.01 | 10-JUN-17:02 | 290.07 | 06-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1280.97 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 631.18 | 22-JUL-18:50 | 179.52 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 1570.85 | 08-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 745.35 | 20-AUG-13:51 | 442.73 | 25-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1964.82 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.03 | 09-SEP-17:02 | 439.82 | 05-SEP-02:51 |
October | 2010.83 | 02-OCT-09:09 | 2254.70 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.05 | 09-OCT-13:56 | 890.78 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1964.82 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.74 | 28-NOV-13:00 | 1460.25 | 12-NOV-10:55 |
December | 2010.83 | 01-DEC-10:09 | 2254.70 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.05 | 13-DEC-14:00 | 1760.70 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1176.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 23.11 | 179.52 | |||||
Maximum of Months | 2010.83 | 2254.70 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 780.05 | 1982.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1266.18 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.51 | 16-JAN-13:00 | 955.88 | 21-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 1266.18 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.81 | 26-FEB-13:52 | 1281.08 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 1266.18 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 227.82 | 05-MAR-12:35 | 1170.48 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1266.18 | 06-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.37 | 23-APR-13:35 | 756.77 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 1012.30 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.58 | 21-MAY-13:50 | 170.85 | 06-MAY-19:53 |
June | 1295.83 | 01-JUN-09:09 | 1012.30 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.21 | 10-JUN-17:07 | 227.35 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 1012.30 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.62 | 16-JUL-13:20 | 158.71 | 31-JUL-01:53 |
August | 1295.83 | 01-AUG-09:09 | 1199.10 | 08-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 509.78 | 20-AUG-14:00 | 327.33 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 1266.18 | 13-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.55 | 09-SEP-22:53 | 304.02 | 05-SEP-02:51 |
October | 1295.83 | 02-OCT-09:09 | 1452.99 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 609.47 | 09-OCT-12:00 | 580.21 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1452.99 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.44 | 05-NOV-13:00 | 830.23 | 12-NOV-06:55 |
December | 1295.83 | 01-DEC-10:09 | 1452.99 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.65 | 10-DEC-11:10 | 1168.82 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1012.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 94.51 | 158.71 | |||||
Maximum of Months | 1295.83 | 1452.99 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 609.47 | 1281.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1964.78 | 13-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 266.44 | 15-JAN-13:53 | 1789.07 | 21-JAN-05:56 |
February | 2010.79 | 01-FEB-10:09 | 1964.78 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.02 | 20-FEB-14:52 | 2287.47 | 05-FEB-07:55 |
March | 2010.79 | 01-MAR-10:09 | 1964.78 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 429.12 | 05-MAR-12:45 | 1971.19 | 20-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1964.78 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.24 | 29-APR-17:01 | 1154.48 | 01-APR-17:53 |
May | 2010.79 | 01-MAY-09:09 | 1570.82 | 23-MAY-07:19 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 618.83 | 07-MAY-13:52 | 244.11 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1072.77 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 771.35 | 10-JUN-17:02 | 364.64 | 06-JUN-21:20 |
July | 2010.79 | 03-JUL-09:09 | 1280.94 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 670.66 | 22-JUL-18:50 | 275.69 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 1570.82 | 08-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 911.57 | 20-AUG-13:51 | 524.83 | 25-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1964.78 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 926.69 | 09-SEP-23:00 | 539.54 | 05-SEP-02:51 |
October | 2010.79 | 02-OCT-09:09 | 2254.66 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.48 | 09-OCT-14:00 | 842.98 | 28-OCT-04:51 |
November | 2010.79 | 01-NOV-09:09 | 1964.78 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 05-NOV-13:00 | 1378.07 | 12-NOV-06:55 |
December | 2010.79 | 01-DEC-10:09 | 2254.66 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.40 | 10-DEC-10:53 | 1867.31 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 266.44 | 244.11 | |||||
Maximum of Months | 2010.79 | 2254.66 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.48 | 2287.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1266.18 | 31-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 150.85 | 16-JAN-15:00 | 1192.71 | 21-JAN-05:58 |
February | 1295.83 | 01-FEB-10:09 | 1266.18 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 218.49 | 20-FEB-14:52 | 1524.97 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 1199.10 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 216.83 | 05-MAR-13:10 | 1328.77 | 20-MAR-21:25 |
April | 1295.83 | 03-APR-09:09 | 1266.18 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.35 | 29-APR-17:50 | 790.02 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 825.49 | 23-MAY-07:19 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 442.35 | 21-MAY-13:50 | 239.91 | 14-MAY-12:10 |
June | 1295.83 | 01-JUN-09:09 | 758.41 | 27-JUN-13:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.17 | 10-JUN-17:02 | 264.06 | 18-JUN-14:00 |
July | 1295.83 | 03-JUL-09:09 | 758.41 | 11-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.15 | 22-JUL-18:50 | 327.52 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 825.49 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 624.14 | 20-AUG-13:51 | 354.77 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 1012.30 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 653.81 | 09-SEP-22:57 | 373.62 | 05-SEP-02:51 |
October | 1295.83 | 02-OCT-09:09 | 1452.99 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 762.55 | 09-OCT-14:00 | 567.56 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1452.99 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.72 | 05-NOV-13:00 | 1122.06 | 12-NOV-08:40 |
December | 1295.83 | 01-DEC-10:09 | 1452.99 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 142.43 | 10-DEC-15:00 | 1246.67 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 758.41 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 142.43 | 239.91 | |||||
Maximum of Months | 1295.83 | 1452.99 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 762.55 | 1524.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1964.82 | 13-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 | 19-JAN-12:00 | 1845.43 | 22-JAN-16:55 |
February | 2010.83 | 01-FEB-10:09 | 1964.82 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.07 | 02-FEB-13:00 | 2287.34 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 1964.82 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 204.50 | 26-MAR-14:00 | 2045.98 | 20-MAR-21:13 |
April | 2010.83 | 03-APR-09:09 | 1964.82 | 06-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.21 | 29-APR-17:01 | 1250.12 | 01-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 1570.85 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 602.92 | 07-MAY-13:52 | 250.75 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1176.88 | 02-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 783.00 | 10-JUN-17:02 | 366.87 | 06-JUN-21:20 |
July | 2010.83 | 03-JUL-09:09 | 1280.97 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 682.74 | 22-JUL-18:50 | 281.46 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 1570.85 | 08-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 910.03 | 20-AUG-13:51 | 537.09 | 25-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1964.82 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 891.18 | 09-SEP-23:00 | 577.39 | 05-SEP-02:51 |
October | 2010.83 | 02-OCT-09:09 | 2254.70 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 943.31 | 09-OCT-13:56 | 977.57 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1964.82 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.43 | 28-NOV-13:00 | 1780.28 | 12-NOV-11:00 |
December | 2010.83 | 01-DEC-10:09 | 2254.70 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.04 | 13-DEC-14:00 | 1926.30 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1176.88 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 | 250.75 | |||||
Maximum of Months | 2010.83 | 2254.70 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 943.31 | 2287.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1266.18 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 130.80 | 16-JAN-13:00 | 1192.72 | 21-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1266.18 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.08 | 26-FEB-13:30 | 1524.89 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 1266.18 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 281.27 | 05-MAR-12:35 | 1382.23 | 20-MAR-21:17 |
April | 1295.83 | 03-APR-09:09 | 1266.18 | 06-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.10 | 23-APR-13:50 | 915.77 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 1012.30 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.71 | 21-MAY-13:50 | 252.82 | 06-MAY-19:53 |
June | 1295.83 | 01-JUN-09:09 | 1012.30 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 447.45 | 10-JUN-17:07 | 280.16 | 06-JUN-21:20 |
July | 1295.83 | 03-JUL-09:09 | 1012.30 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.19 | 02-JUL-11:40 | 208.25 | 31-JUL-01:53 |
August | 1295.83 | 01-AUG-09:09 | 1199.10 | 08-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 622.94 | 20-AUG-13:51 | 396.18 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 1266.18 | 13-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 618.15 | 09-SEP-22:53 | 390.16 | 05-SEP-02:51 |
October | 1295.83 | 02-OCT-09:09 | 1452.99 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 718.30 | 09-OCT-12:00 | 646.01 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1452.99 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.55 | 05-NOV-13:00 | 972.35 | 12-NOV-06:55 |
December | 1295.83 | 01-DEC-10:09 | 1452.99 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 170.78 | 10-DEC-11:20 | 1315.31 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1012.30 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 122.08 | 208.25 | |||||
Maximum of Months | 1295.83 | 1452.99 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 718.30 | 1524.89 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 5637.70 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 5637.70 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 5637.70 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 5637.70 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 5637.70 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 5637.70 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 5637.70 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 5637.70 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 5637.70 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 5637.70 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 5637.70 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 5637.70 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 5637.70 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 5637.70 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 260.44 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 260.44 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 260.44 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 260.44 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 260.44 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 260.44 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 260.44 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 260.44 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 260.44 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 260.44 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 260.44 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 260.44 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 260.44 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 260.44 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 260.44 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 260.44 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 260.44 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 260.44 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 260.44 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 260.44 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 260.44 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 260.44 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 260.44 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 260.44 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 260.44 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 260.44 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 260.44 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 260.44 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 260.44 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 260.44 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 260.44 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 260.44 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 260.44 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 260.44 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 260.44 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 260.44 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 260.44 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 260.44 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 260.44 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 260.44 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 260.44 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 260.44 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.66 | 16-JAN-14:52 | 1521.75 | 09-JAN-05:14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.32 | 02-FEB-13:00 | 2187.02 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.02 | 26-MAR-14:00 | 1848.75 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.87 | 29-APR-17:01 | 1073.43 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.21 | 21-MAY-14:00 | 167.63 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.75 | 10-JUN-17:02 | 283.27 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.68 | 22-JUL-18:53 | 113.27 | 31-JUL-02:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 704.79 | 20-AUG-14:00 | 389.87 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 665.13 | 09-SEP-17:02 | 377.84 | 05-SEP-03:04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.91 | 09-OCT-13:51 | 903.22 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.44 | 05-NOV-13:00 | 1282.58 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.49 | 10-DEC-15:00 | 2032.74 | 20-DEC-01:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.66 | 113.27 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.91 | 2187.02 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.31 | 16-JAN-14:52 | 2585.62 | 21-JAN-05:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.94 | 20-FEB-15:00 | 3735.57 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.57 | 05-MAR-12:53 | 3138.14 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 607.63 | 29-APR-17:01 | 1773.29 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896.23 | 07-MAY-14:00 | 258.32 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1092.17 | 10-JUN-17:02 | 475.22 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 986.70 | 22-JUL-18:53 | 197.82 | 31-JUL-02:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1298.52 | 20-AUG-14:00 | 727.86 | 25-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1224.35 | 09-SEP-17:02 | 572.60 | 05-SEP-02:51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.58 | 09-OCT-14:00 | 1513.55 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.42 | 05-NOV-13:00 | 2181.43 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.95 | 10-DEC-15:00 | 3412.31 | 20-DEC-01:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.31 | 197.82 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1446.58 | 3735.57 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.06 | 16-JAN-15:00 | 2595.19 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.38 | 02-FEB-13:00 | 3395.61 | 05-FEB-08:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.62 | 26-MAR-14:00 | 3277.49 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.52 | 29-APR-17:01 | 1912.59 | 01-APR-17:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.54 | 07-MAY-14:00 | 556.00 | 14-MAY-11:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1027.16 | 10-JUN-17:02 | 483.59 | 07-JUN-01:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.99 | 22-JUL-18:50 | 518.41 | 30-JUL-11:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1198.44 | 20-AUG-14:00 | 783.54 | 25-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1383.87 | 09-SEP-23:00 | 769.68 | 05-SEP-03:04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.72 | 09-OCT-14:00 | 1385.96 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.73 | 05-NOV-13:00 | 2225.85 | 12-NOV-06:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.42 | 10-DEC-15:00 | 3233.16 | 20-DEC-01:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.38 | 483.59 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1383.87 | 3395.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 119027.67 | 09-JAN-01:11 | 0.00 | 12266.17 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 121304.44 | 13-FEB-01:12 | 0.00 | 6133.09 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 119603.42 | 19-MAR-15:31 | 8976.13 | 11108.26 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 125432.28 | 16-APR-23:00 | 0.00 | 3679.85 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 112154.93 | 29-MAY-21:00 | 0.00 | 3679.85 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 109630.55 | 25-JUN-21:13 | 0.00 | 3679.85 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 109689.25 | 09-JUL-20:50 | 0.00 | 3679.85 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 115652.12 | 20-AUG-04:57 | 0.00 | 4906.47 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 112346.49 | 17-SEP-21:43 | 0.00 | 3679.85 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 118398.64 | 17-OCT-04:11 | 0.00 | 24532.35 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 124431.39 | 23-NOV-15:08 | 3590.45 | 4443.30 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 122206.85 | 03-DEC-20:52 | 0.00 | 6133.09 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 109630.55 | 0.00 | 3679.85 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 125432.28 | 8976.13 | 24532.35 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 96147.72 | 01-JAN-03:31 | 0.00 | 11015.89 | 44532.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90176.27 | 28-FEB-05:12 | 0.00 | 22031.77 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93800.91 | 28-MAR-03:02 | 0.00 | 11015.89 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 93999.27 | 04-APR-03:02 | 0.00 | 11015.89 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 96688.05 | 31-MAY-03:02 | 0.00 | 11015.89 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 91749.64 | 06-JUN-04:12 | 0.00 | 22031.77 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82320.14 | 12-JUL-04:11 | 0.00 | 22031.77 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83395.11 | 01-AUG-05:02 | 16122.38 | 19952.00 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97055.40 | 06-SEP-03:02 | 0.00 | 11015.89 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95220.80 | 03-OCT-03:02 | 0.00 | 11015.89 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 96406.59 | 20-NOV-04:02 | 0.00 | 11015.89 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 95286.42 | 04-DEC-04:01 | 0.00 | 11015.89 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 82320.14 | 0.00 | 11015.89 | 44532.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97055.40 | 16122.38 | 22031.77 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 79199.59 | 20-JAN-05:11 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81034.76 | 27-FEB-06:02 | 16122.38 | 19952.00 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81861.26 | 27-MAR-05:02 | 16122.38 | 19952.00 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 87267.66 | 28-APR-04:12 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88188.19 | 12-MAY-04:12 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87588.31 | 06-JUN-04:12 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87762.89 | 12-JUL-04:12 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86975.10 | 26-AUG-04:02 | 0.00 | 11015.89 | 44532.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87455.64 | 26-SEP-04:12 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87942.23 | 12-OCT-04:12 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86324.18 | 03-NOV-04:12 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80524.34 | 15-DEC-05:11 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 79199.59 | 0.00 | 11015.89 | 44532.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88188.19 | 16122.38 | 22031.77 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 74830.17 | 20-JAN-06:03 | 6448.95 | 7980.80 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73977.59 | 28-FEB-06:03 | 6448.95 | 7980.80 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82329.63 | 27-MAR-05:02 | 16122.38 | 19952.00 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84239.80 | 29-APR-04:12 | 0.00 | 11015.89 | 44532.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87686.88 | 12-MAY-04:12 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89809.31 | 14-JUN-03:02 | 0.00 | 11015.89 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88310.46 | 07-JUL-03:02 | 0.00 | 11015.89 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84477.79 | 16-AUG-04:12 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87129.52 | 26-SEP-04:12 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87515.89 | 13-OCT-04:02 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79328.97 | 08-NOV-05:11 | 0.00 | 22031.77 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78928.75 | 11-DEC-06:02 | 16122.38 | 19952.00 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 73977.59 | 0.00 | 7980.80 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89809.31 | 16122.38 | 22031.77 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7230.30 | 02-JAN-13:30 | 1923.11 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 | 0.00 |
February | 7224.46 | 22-FEB-14:30 | 2010.79 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 | 0.00 |
March | 10544.79 | 30-MAR-04:11 | 0.00 | 2766.31 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9239.44 | 26-APR-14:30 | 1923.11 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 31.85 | 0.00 |
May | 14671.00 | 29-MAY-16:01 | 809.73 | 476.78 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 96.82 | 0.00 |
June | 14845.62 | 25-JUN-15:21 | 708.51 | 417.19 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 51.23 | 0.00 |
July | 13011.55 | 03-JUL-04:31 | 0.00 | 2766.31 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 0.00 |
August | 14884.57 | 20-AUG-13:51 | 1012.16 | 595.98 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 321.08 | 0.00 |
September | 13203.77 | 05-SEP-04:12 | 0.00 | 2766.31 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.44 |
October | 12558.17 | 13-OCT-04:02 | 0.00 | 2766.31 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.22 |
November | 11923.25 | 03-NOV-04:11 | 0.00 | 2766.31 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11087.20 | 11-DEC-06:01 | 2024.33 | 2505.17 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7224.46 | 0.00 | 417.19 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14884.57 | 2024.33 | 2766.31 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 321.08 | 116.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9200.62 | 01-JAN-10:03 | 195.68 | 115.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.45 |
February | 8392.76 | 27-FEB-10:10 | 1295.83 | 691.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
March | 17656.19 | 26-MAR-09:43 | 260.91 | 153.63 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 |
April | 18766.40 | 23-APR-09:12 | 326.14 | 192.04 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.78 |
May | 20007.17 | 29-MAY-08:41 | 456.59 | 268.85 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
June | 17614.46 | 04-JUN-09:32 | 391.37 | 230.44 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 0.00 |
July | 17570.33 | 23-JUL-09:02 | 326.14 | 192.04 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 11.39 | 0.00 |
August | 17671.85 | 06-AUG-08:51 | 652.28 | 384.07 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 31.08 | 0.00 |
September | 19169.16 | 24-SEP-09:32 | 391.37 | 230.44 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 | 0.00 |
October | 17802.65 | 15-OCT-08:53 | 260.91 | 153.63 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.55 |
November | 17535.28 | 11-NOV-09:02 | 260.91 | 153.63 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.11 |
December | 13028.35 | 10-DEC-08:56 | 652.28 | 384.07 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8392.76 | 195.68 | 115.22 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20007.17 | 1295.83 | 691.33 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 31.96 | 128.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18867.73 | 01-JAN-13:22 | 506.09 | 298.00 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.54 |
February | 19118.38 | 26-FEB-13:52 | 506.09 | 298.00 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.08 |
March | 17968.74 | 05-MAR-13:32 | 404.87 | 238.40 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 | 0.00 |
April | 11034.68 | 28-APR-13:20 | 2010.83 | 1072.79 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 51.46 | 0.00 |
May | 16466.52 | 28-MAY-16:31 | 809.75 | 476.79 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 138.99 | 0.00 |
June | 17023.04 | 25-JUN-15:21 | 708.53 | 417.20 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 51.41 | 0.00 |
July | 14927.73 | 03-JUL-04:31 | 0.00 | 2766.37 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 | 0.00 |
August | 17407.94 | 20-AUG-13:51 | 1012.19 | 595.99 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 309.74 | 0.00 |
September | 18233.72 | 10-SEP-12:02 | 404.87 | 238.40 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 156.93 | 0.00 |
October | 18483.97 | 08-OCT-12:01 | 1012.19 | 595.99 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 159.66 | 0.00 |
November | 19727.90 | 11-NOV-11:42 | 607.31 | 357.60 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.06 |
December | 18843.47 | 17-DEC-15:12 | 506.09 | 298.00 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11034.68 | 0.00 | 238.40 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19727.90 | 2010.83 | 2766.37 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 309.74 | 392.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21929.17 | 16-JAN-16:11 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 |
February | 22981.57 | 26-FEB-15:52 | 326.14 | 192.04 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 |
March | 22780.25 | 05-MAR-15:32 | 326.14 | 192.04 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 |
April | 23263.60 | 23-APR-16:32 | 391.37 | 230.44 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.28 |
May | 25088.90 | 29-MAY-16:41 | 521.82 | 307.26 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 | 0.00 |
June | 24150.15 | 25-JUN-15:21 | 456.59 | 268.85 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 | 0.00 |
July | 23327.68 | 30-JUL-15:41 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 |
August | 22996.48 | 20-AUG-17:11 | 0.00 | 424.11 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 55.88 | 0.00 |
September | 24374.87 | 17-SEP-15:31 | 456.59 | 268.85 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 89.96 | 0.00 |
October | 22995.52 | 22-OCT-16:21 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 | 0.00 |
November | 23580.90 | 11-NOV-15:02 | 391.37 | 230.44 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 |
December | 22336.18 | 25-DEC-15:41 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 21929.17 | 0.00 | 192.04 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25088.90 | 652.28 | 424.11 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 89.96 | 105.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5093.17 | 31-JAN-14:40 | 2010.79 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 0.00 |
February | 5332.83 | 28-FEB-15:00 | 2010.79 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.56 | 0.00 |
March | 7473.01 | 27-MAR-05:01 | 2024.33 | 2505.17 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.75 |
April | 8864.53 | 28-APR-04:11 | 0.00 | 2766.31 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.18 |
May | 12927.63 | 21-MAY-15:47 | 1012.16 | 595.98 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 172.50 | 0.00 |
June | 12383.61 | 05-JUN-03:02 | 0.00 | 829.89 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 0.00 |
July | 12523.28 | 05-JUL-03:02 | 0.00 | 691.58 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 |
August | 12520.44 | 14-AUG-03:02 | 0.00 | 691.58 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 0.00 |
September | 13561.04 | 10-SEP-15:11 | 708.51 | 417.19 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 266.52 | 0.00 |
October | 11448.83 | 26-OCT-05:02 | 2024.33 | 2505.17 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.59 |
November | 8999.46 | 29-NOV-06:02 | 1012.16 | 1252.59 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 |
December | 5994.81 | 15-DEC-15:00 | 2010.79 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 52.68 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5093.17 | 0.00 | 417.19 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13561.04 | 2024.33 | 2766.31 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 266.52 | 53.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7058.36 | 19-JAN-09:40 | 1239.33 | 691.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.93 |
February | 7364.61 | 26-FEB-10:30 | 260.91 | 153.63 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 |
March | 11915.62 | 27-MAR-05:01 | 1304.55 | 1614.43 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.39 |
April | 18869.72 | 23-APR-08:22 | 326.14 | 192.04 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.32 |
May | 19341.69 | 29-MAY-08:51 | 652.28 | 384.07 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 |
June | 19080.21 | 11-JUN-08:42 | 326.14 | 192.04 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.39 |
July | 18699.20 | 09-JUL-08:52 | 326.14 | 192.04 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 103.08 | 0.00 |
August | 18741.43 | 06-AUG-09:52 | 326.14 | 192.04 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 55.73 | 0.00 |
September | 19517.70 | 10-SEP-08:32 | 391.37 | 230.44 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 177.70 | 0.00 |
October | 18730.93 | 09-OCT-09:11 | 652.28 | 384.07 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 | 0.00 |
November | 14270.63 | 11-NOV-09:32 | 260.91 | 153.63 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.38 |
December | 5751.42 | 16-DEC-09:40 | 391.37 | 230.44 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5751.42 | 260.91 | 153.63 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19517.70 | 1304.55 | 1614.43 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 177.70 | 149.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19138.99 | 01-JAN-13:11 | 708.53 | 417.20 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.90 |
February | 17706.41 | 26-FEB-14:22 | 506.09 | 298.00 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.55 |
March | 13151.09 | 27-MAR-05:02 | 2024.37 | 2505.23 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.64 |
April | 12181.82 | 29-APR-04:11 | 0.00 | 1383.18 | 5591.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.17 |
May | 13965.34 | 08-MAY-03:01 | 0.00 | 1383.18 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.35 |
June | 13727.84 | 29-JUN-05:02 | 2024.37 | 2505.23 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 | 0.00 |
July | 14462.53 | 05-JUL-03:02 | 0.00 | 691.59 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 |
August | 14533.76 | 14-AUG-03:02 | 0.00 | 691.59 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 0.00 |
September | 16903.25 | 10-SEP-15:11 | 708.53 | 417.20 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 233.33 | 0.00 |
October | 17530.61 | 09-OCT-13:11 | 1012.19 | 595.99 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 421.51 | 0.00 |
November | 18432.86 | 11-NOV-12:52 | 607.31 | 357.60 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.57 |
December | 19048.15 | 10-DEC-13:21 | 708.53 | 417.20 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.66 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12181.82 | 0.00 | 298.00 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19138.99 | 2024.37 | 2505.23 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 421.51 | 187.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9013.24 | 31-JAN-16:30 | 1239.33 | 691.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 |
February | 18862.91 | 26-FEB-17:01 | 456.59 | 268.85 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.01 |
March | 13172.09 | 27-MAR-05:01 | 1304.55 | 1614.43 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.85 |
April | 19036.95 | 23-APR-16:42 | 326.14 | 192.04 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 | 0.00 |
May | 20431.07 | 29-MAY-16:51 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | 0.00 |
June | 21598.42 | 11-JUN-16:41 | 521.82 | 307.26 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 86.60 | 0.00 |
July | 19281.88 | 16-JUL-17:12 | 0.00 | 212.05 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 97.38 | 0.00 |
August | 19331.35 | 06-AUG-16:31 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.24 |
September | 20637.96 | 10-SEP-15:11 | 456.59 | 268.85 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 143.00 | 0.00 |
October | 19568.42 | 09-OCT-16:31 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 | 0.00 |
November | 18245.89 | 11-NOV-16:11 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.19 |
December | 14773.94 | 10-DEC-16:01 | 456.59 | 268.85 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9013.24 | 0.00 | 192.04 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21598.42 | 1304.55 | 1614.43 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 143.00 | 78.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5466.32 | 31-JAN-15:00 | 2010.79 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 25.19 | 0.00 |
February | 5792.20 | 22-FEB-14:30 | 2010.79 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 | 0.00 |
March | 7519.73 | 30-MAR-13:20 | 2010.79 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 62.85 | 0.00 |
April | 9203.61 | 28-APR-15:00 | 1923.11 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 187.91 | 0.00 |
May | 15121.09 | 29-MAY-16:11 | 1012.16 | 595.98 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 268.99 | 0.00 |
June | 15452.97 | 11-JUN-16:41 | 809.73 | 476.78 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 234.78 | 0.00 |
July | 15555.41 | 02-JUL-16:12 | 506.08 | 297.99 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 184.38 | 0.00 |
August | 15234.03 | 20-AUG-15:42 | 607.30 | 357.59 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.60 | 0.00 |
September | 16106.65 | 10-SEP-15:11 | 708.51 | 417.19 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 301.26 | 0.00 |
October | 15317.87 | 08-OCT-14:02 | 607.30 | 357.59 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 786.29 | 0.00 |
November | 9463.02 | 01-NOV-05:02 | 1012.16 | 1252.59 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 |
December | 6555.04 | 15-DEC-15:00 | 2010.79 | 1072.77 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 63.95 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5466.32 | 506.08 | 297.99 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16106.65 | 2010.79 | 1252.59 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 786.29 | 12.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6543.68 | 19-JAN-10:10 | 1295.83 | 691.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 |
February | 6683.67 | 27-FEB-10:30 | 1295.83 | 691.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 |
March | 10373.79 | 27-MAR-05:01 | 1304.55 | 1614.43 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.55 |
April | 18840.78 | 23-APR-08:22 | 326.14 | 192.04 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.45 |
May | 19577.08 | 29-MAY-08:51 | 652.28 | 384.07 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 |
June | 19198.09 | 11-JUN-08:42 | 326.14 | 192.04 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.22 |
July | 18966.78 | 09-JUL-08:52 | 326.14 | 192.04 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 119.03 | 0.00 |
August | 18091.23 | 27-AUG-11:41 | 652.28 | 384.07 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 152.53 | 0.00 |
September | 19806.39 | 10-SEP-08:32 | 391.37 | 230.44 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 210.37 | 0.00 |
October | 18907.40 | 09-OCT-09:51 | 652.28 | 384.07 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 163.16 | 0.00 |
November | 8280.06 | 02-NOV-09:40 | 1295.83 | 691.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 0.00 |
December | 5265.23 | 16-DEC-09:50 | 391.37 | 230.44 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5265.23 | 326.14 | 192.04 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19806.39 | 1304.55 | 1614.43 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 210.37 | 184.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20983.48 | 01-JAN-14:31 | 708.53 | 417.20 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.94 |
February | 18737.40 | 26-FEB-12:43 | 404.87 | 238.40 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.76 |
March | 13240.65 | 27-MAR-05:01 | 2024.37 | 2505.23 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.82 |
April | 11195.05 | 28-APR-13:50 | 2010.83 | 1072.79 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 131.84 | 0.00 |
May | 17195.21 | 07-MAY-14:53 | 404.87 | 238.40 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 306.59 | 0.00 |
June | 17261.04 | 11-JUN-16:41 | 809.75 | 476.79 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 242.95 | 0.00 |
July | 17446.86 | 02-JUL-16:12 | 506.09 | 298.00 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 198.12 | 0.00 |
August | 16769.68 | 20-AUG-15:42 | 607.31 | 357.60 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 388.76 | 0.00 |
September | 19227.41 | 10-SEP-15:11 | 708.53 | 417.20 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 268.99 | 0.00 |
October | 19402.92 | 09-OCT-13:11 | 1012.19 | 595.99 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 473.48 | 0.00 |
November | 18863.99 | 11-NOV-13:52 | 506.09 | 298.00 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.70 |
December | 20898.77 | 10-DEC-13:11 | 708.53 | 417.20 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11195.05 | 404.87 | 238.40 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20983.48 | 2024.37 | 2505.23 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 473.48 | 170.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9342.63 | 31-JAN-16:30 | 1239.33 | 691.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
February | 19877.11 | 26-FEB-18:01 | 0.00 | 424.11 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.27 |
March | 14917.28 | 27-MAR-05:01 | 1304.55 | 1614.43 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.96 |
April | 20996.95 | 23-APR-17:01 | 0.00 | 339.29 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.23 |
May | 21596.48 | 29-MAY-16:51 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 101.51 | 0.00 |
June | 22961.90 | 11-JUN-16:41 | 521.82 | 307.26 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 96.24 | 0.00 |
July | 20760.06 | 30-JUL-16:21 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.92 |
August | 20202.47 | 06-AUG-16:41 | 456.59 | 268.85 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.25 |
September | 22457.36 | 10-SEP-15:11 | 456.59 | 268.85 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 165.10 | 0.00 |
October | 20898.87 | 09-OCT-16:31 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 | 0.00 |
November | 11173.65 | 06-NOV-16:10 | 1239.33 | 691.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 16.30 | 0.00 |
December | 19805.17 | 10-DEC-16:31 | 652.28 | 384.07 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9342.63 | 0.00 | 268.85 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22961.90 | 1304.55 | 1614.43 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 165.10 | 102.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9957.45 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.92 |
February | 7394.93 | 27-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8882.47 | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.42 |
April | 7116.20 | 28-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 |
May | 10935.01 | 23-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.31 |
June | 10533.77 | 29-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
July | 10265.61 | 19-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 0.00 |
August | 9706.55 | 22-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 0.00 |
September | 10873.64 | 05-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.74 |
October | 12094.07 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.51 |
November | 7965.73 | 03-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10589.09 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7116.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 64.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7674.65 | 04-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.92 |
February | 6560.44 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.14 |
March | 7545.87 | 09-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.07 |
April | 5387.54 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.31 | 0.00 |
May | 8170.01 | 06-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 |
June | 9835.69 | 14-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 |
July | 9683.01 | 08-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 |
August | 9298.67 | 05-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 | 0.00 |
September | 9405.27 | 12-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.20 | 0.00 |
October | 10306.39 | 07-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 | 0.00 |
November | 5120.11 | 09-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.32 |
December | 5989.40 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.10 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5120.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10306.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.31 | 578.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9308.96 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 |
February | 11030.87 | 24-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 |
March | 11512.81 | 29-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 | 0.00 |
April | 17363.49 | 18-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 0.00 |
May | 17522.47 | 10-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.30 | 0.00 |
June | 18234.03 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.26 | 0.00 |
July | 18689.41 | 07-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.94 | 0.00 |
August | 17852.28 | 03-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.05 | 0.00 |
September | 16246.32 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.60 | 0.00 |
October | 15942.94 | 05-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.41 | 0.00 |
November | 12630.32 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.03 | 0.00 |
December | 10897.28 | 15-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.32 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9308.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18689.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.05 | 44.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2050.68 | 01-JAN-17:20 | 0.00 | 57.88 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4159.39 | 26-FEB-17:54 | 0.00 | 72.34 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5776.03 | 05-MAR-17:45 | 0.00 | 28.94 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7993.14 | 16-APR-18:20 | 0.00 | 15.98 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2092.84 | 29-MAY-18:19 | 0.00 | 159.77 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3956.41 | 11-JUN-18:25 | 0.00 | 159.77 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5758.46 | 23-JUL-18:58 | 0.00 | 79.89 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7671.94 | 06-AUG-17:45 | 0.00 | 63.91 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2178.71 | 03-SEP-18:00 | 0.00 | 31.95 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4045.04 | 01-OCT-17:33 | 0.00 | 63.91 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5953.93 | 12-NOV-17:03 | 0.00 | 43.41 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7857.03 | 10-DEC-17:03 | 0.00 | 43.41 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2050.68 | 0.00 | 15.98 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7993.14 | 0.00 | 159.77 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1791.10 | 31-JAN-17:50 | 0.00 | 144.69 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3761.79 | 26-FEB-17:52 | 0.00 | 72.34 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5414.03 | 06-MAR-18:00 | 0.00 | 144.69 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7450.27 | 16-APR-18:20 | 0.00 | 15.98 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1889.22 | 14-MAY-18:23 | 0.00 | 63.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3719.95 | 11-JUN-18:30 | 0.00 | 159.77 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5389.40 | 16-JUL-18:55 | 0.00 | 31.95 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7228.01 | 30-AUG-18:40 | 0.00 | 86.81 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2006.22 | 03-SEP-17:55 | 0.00 | 31.95 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3769.32 | 09-OCT-17:28 | 0.00 | 79.89 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5572.68 | 06-NOV-17:00 | 0.00 | 260.44 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7301.23 | 15-DEC-17:00 | 0.00 | 260.44 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1791.10 | 0.00 | 15.98 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7450.27 | 0.00 | 260.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1864.57 | 31-JAN-17:50 | 0.00 | 144.69 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3754.73 | 26-FEB-17:56 | 0.00 | 72.34 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5482.09 | 06-MAR-17:50 | 0.00 | 144.69 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7552.71 | 23-APR-18:05 | 0.00 | 63.91 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2152.93 | 29-MAY-17:58 | 0.00 | 79.89 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3967.87 | 11-JUN-18:23 | 0.00 | 159.77 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5613.57 | 16-JUL-18:50 | 0.00 | 63.91 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7419.60 | 06-AUG-17:34 | 0.00 | 79.89 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2227.51 | 03-SEP-18:00 | 0.00 | 31.95 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3973.37 | 09-OCT-17:30 | 0.00 | 79.89 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5636.59 | 06-NOV-17:00 | 0.00 | 260.44 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7369.71 | 15-DEC-17:00 | 0.00 | 260.44 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1864.57 | 0.00 | 31.95 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7552.71 | 0.00 | 260.44 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91853.82 | 02-JAN-17:00 | 0.00 | 5637.70 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182619.74 | 27-FEB-17:00 | 0.00 | 5637.70 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 273772.86 | 06-MAR-17:00 | 0.00 | 5637.70 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 365331.15 | 28-APR-18:50 | 0.00 | 1879.23 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 102996.50 | 01-MAY-00:10 | 0.00 | 1383.41 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 182271.88 | 06-JUN-16:00 | 0.00 | 5637.70 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 274513.53 | 06-JUL-16:00 | 0.00 | 5637.70 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369960.91 | 28-AUG-21:02 | 0.00 | 3132.05 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 106766.67 | 01-SEP-00:10 | 0.00 | 345.85 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 183920.88 | 11-OCT-16:00 | 0.00 | 5637.70 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275597.15 | 06-NOV-17:00 | 0.00 | 5637.70 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367068.02 | 14-DEC-17:00 | 0.00 | 5637.70 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 91853.82 | 0.00 | 345.85 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369960.91 | 0.00 | 5637.70 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.173801E+13 | 1362763.86 | 19-JAN-16:30 | 0.981470E+11 | 866751.28 | 21-JAN-07:10 |
February | 0.199741E+13 | 1509383.96 | 27-FEB-16:00 | 0.685465E+11 | 842485.95 | 17-FEB-07:10 |
March | 0.267559E+13 | 1665454.90 | 29-MAR-15:39 | 0.699169E+11 | 808123.99 | 09-MAR-07:10 |
April | 0.306579E+13 | 1876628.57 | 28-APR-15:00 | 0.410031E+11 | 187120.15 | 10-APR-00:10 |
May | 0.218278E+13 | 1403732.52 | 02-MAY-15:09 | 0.409479E+11 | 153255.15 | 21-MAY-19:00 |
June | 0.256569E+13 | 1578883.88 | 28-JUN-15:09 | 0.380143E+11 | 105138.42 | 25-JUN-21:10 |
July | 0.303994E+13 | 1750842.97 | 21-JUL-15:00 | 0.369517E+11 | 153135.61 | 16-JUL-13:39 |
August | 0.352621E+13 | 1901542.21 | 03-AUG-15:50 | 0.388696E+11 | 104607.32 | 13-AUG-09:20 |
September | 0.211667E+13 | 1402613.04 | 18-SEP-15:00 | 0.380238E+11 | 154514.51 | 24-SEP-22:19 |
October | 0.251391E+13 | 1590210.61 | 06-OCT-15:09 | 0.421193E+11 | 253321.83 | 29-OCT-18:49 |
November | 0.263700E+13 | 1692438.78 | 07-NOV-16:49 | 0.472350E+11 | 248661.95 | 19-NOV-10:30 |
December | 0.299428E+13 | 1841632.86 | 12-DEC-16:40 | 0.822373E+11 | 846587.79 | 21-DEC-07:10 |
Annual Sum or Average | 0.310533E+14 | 0.642012E+12 | ||||
Minimum of Months | 0.173801E+13 | 1362763.86 | 0.369517E+11 | 104607.32 | ||
Maximum of Months | 0.352621E+13 | 1901542.21 | 0.981470E+11 | 866751.28 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.287011E+12 | 0.675721E+11 | 0.766053E+12 | 0.168173E+12 | 0.164295E+12 | 0.308869E+11 | 0.00 | 0.174209E+12 | 0.747334E+11 | 0.145804E+10 | 0.361570E+10 | 0.00 | 0.00 |
February | 0.258977E+12 | 0.576723E+11 | 0.978954E+12 | 0.151908E+12 | 0.150256E+12 | 0.335107E+11 | 0.00 | 0.258093E+12 | 0.103812E+12 | 0.755426E+09 | 0.346811E+10 | 0.00 | 0.00 |
March | 0.306189E+12 | 0.587923E+11 | 0.141645E+13 | 0.168424E+12 | 0.169533E+12 | 0.409469E+11 | 0.00 | 0.376859E+12 | 0.133809E+12 | 0.947514E+09 | 0.364464E+10 | 0.00 | 0.00 |
April | 0.272804E+12 | 0.519917E+11 | 0.166021E+13 | 0.162724E+12 | 0.169580E+12 | 0.493936E+11 | 0.00 | 0.532054E+12 | 0.161761E+12 | 0.273431E+09 | 0.499561E+10 | 0.00 | 0.00 |
May | 0.292840E+12 | 0.493034E+11 | 0.774418E+12 | 0.168297E+12 | 0.191990E+12 | 0.600511E+11 | 0.00 | 0.429206E+12 | 0.209120E+12 | 0.00 | 0.755740E+10 | 0.00 | 0.00 |
June | 0.290720E+12 | 0.453056E+11 | 0.106218E+13 | 0.162960E+12 | 0.190681E+12 | 0.640649E+11 | 0.00 | 0.534541E+12 | 0.207676E+12 | 0.00 | 0.755740E+10 | 0.00 | 0.00 |
July | 0.272894E+12 | 0.480877E+11 | 0.139289E+13 | 0.168061E+12 | 0.193418E+12 | 0.704221E+11 | 0.00 | 0.664548E+12 | 0.222448E+12 | 0.00 | 0.717347E+10 | 0.00 | 0.00 |
August | 0.304259E+12 | 0.516671E+11 | 0.173328E+13 | 0.168424E+12 | 0.199747E+12 | 0.731265E+11 | 0.00 | 0.765641E+12 | 0.222209E+12 | 0.00 | 0.786051E+10 | 0.00 | 0.00 |
September | 0.273318E+12 | 0.548283E+11 | 0.740378E+12 | 0.162724E+12 | 0.182260E+12 | 0.603268E+11 | 0.00 | 0.429399E+12 | 0.206264E+12 | 0.00 | 0.717347E+10 | 0.00 | 0.00 |
October | 0.284899E+12 | 0.617977E+11 | 0.108288E+13 | 0.168173E+12 | 0.189696E+12 | 0.586543E+11 | 0.00 | 0.474366E+12 | 0.187319E+12 | 0.205760E+09 | 0.591447E+10 | 0.00 | 0.00 |
November | 0.283537E+12 | 0.640808E+11 | 0.135889E+13 | 0.162820E+12 | 0.169721E+12 | 0.450976E+11 | 0.00 | 0.406450E+12 | 0.142779E+12 | 0.435195E+09 | 0.318877E+10 | 0.00 | 0.00 |
December | 0.279063E+12 | 0.686864E+11 | 0.170972E+13 | 0.168064E+12 | 0.168413E+12 | 0.380014E+11 | 0.00 | 0.424555E+12 | 0.133150E+12 | 0.973129E+09 | 0.365671E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.340651E+13 | 0.679785E+12 | 0.146763E+14 | 0.198075E+13 | 0.213959E+13 | 0.624483E+12 | 0.00 | 0.546992E+13 | 0.200508E+13 | 0.504849E+10 | 0.658063E+11 | ||
Minimum of Months | 0.258977E+12 | 0.453056E+11 | 0.740378E+12 | 0.151908E+12 | 0.150256E+12 | 0.308869E+11 | 0.00 | 0.174209E+12 | 0.747334E+11 | 0.00 | 0.318877E+10 | 0.00 | 0.00 |
Maximum of Months | 0.306189E+12 | 0.686864E+11 | 0.173328E+13 | 0.168424E+12 | 0.199747E+12 | 0.731265E+11 | 0.00 | 0.765641E+12 | 0.222448E+12 | 0.145804E+10 | 0.786051E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.530191E+11 | 0.00 | 0.451279E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.279359E+11 | 0.00 | 0.406106E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.244574E+11 | 0.00 | 0.454595E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.124578E+10 | 0.00 | 0.397573E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.110717E+10 | 0.00 | 0.398407E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.922120E+09 | 0.00 | 0.370922E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.142155E+10 | 0.00 | 0.355301E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.978295E+09 | 0.00 | 0.378913E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.150109E+10 | 0.00 | 0.365227E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.201230E+10 | 0.00 | 0.401070E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.567381E+10 | 0.00 | 0.415612E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.389102E+11 | 0.00 | 0.433271E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.159185E+12 | 0.482828E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.922120E+09 | 0.00 | 0.355301E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.530191E+11 | 0.00 | 0.454595E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 321783.03 | 31-JAN-08:09 | 56280.70 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 127605.48 | 31-JAN-08:20 | 109621.20 | 03-JAN-08:39 | 47477.51 | 19-JAN-10:39 | 0.00 | 01-JAN-00:10 |
February | 321969.83 | 01-FEB-08:09 | 56280.70 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 127605.62 | 01-FEB-08:20 | 115753.48 | 27-FEB-16:19 | 47519.43 | 24-FEB-11:30 | 0.00 | 01-FEB-00:10 |
March | 321045.15 | 27-MAR-07:10 | 56280.70 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 127604.90 | 27-MAR-07:19 | 111140.70 | 27-MAR-05:10 | 47311.15 | 07-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 321783.03 | 14-APR-07:10 | 56280.70 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 127605.48 | 14-APR-07:19 | 148215.82 | 18-APR-13:00 | 47392.73 | 27-APR-10:39 | 0.00 | 01-APR-00:10 |
May | 303992.90 | 23-MAY-07:19 | 56280.70 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 127591.67 | 23-MAY-07:30 | 132084.37 | 04-MAY-15:00 | 47962.21 | 30-MAY-12:30 | 0.00 | 01-MAY-00:10 |
June | 291782.77 | 16-JUN-07:10 | 56280.70 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 127582.21 | 16-JUN-07:19 | 133574.46 | 28-JUN-15:00 | 48259.86 | 02-JUN-15:09 | 0.00 | 01-JUN-00:10 |
July | 296520.78 | 14-JUL-07:10 | 56280.70 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 127585.88 | 14-JUL-07:19 | 139070.46 | 07-JUL-15:00 | 47673.04 | 31-JUL-08:00 | 0.00 | 01-JUL-00:10 |
August | 304691.73 | 08-AUG-07:30 | 56280.70 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 127592.21 | 08-AUG-07:40 | 145484.62 | 30-AUG-15:00 | 47922.64 | 07-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 318990.29 | 26-SEP-07:10 | 56280.70 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 127603.31 | 26-SEP-07:19 | 133725.59 | 01-SEP-14:00 | 48232.19 | 25-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 333223.40 | 25-OCT-07:10 | 56280.70 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 127614.37 | 25-OCT-07:19 | 142205.46 | 05-OCT-15:30 | 48358.64 | 12-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 324024.70 | 01-NOV-07:10 | 56280.70 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 127607.22 | 01-NOV-07:19 | 126075.09 | 02-NOV-15:30 | 47429.57 | 29-NOV-16:49 | 0.00 | 01-NOV-00:10 |
December | 333223.40 | 12-DEC-08:09 | 56280.70 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 127614.37 | 12-DEC-08:20 | 120001.20 | 15-DEC-15:30 | 47429.79 | 15-DEC-11:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 291782.77 | 56280.70 | 423497.50 | 127582.21 | 109621.20 | 47311.15 | 0.00 | |||||||
Maximum of Months | 333223.40 | 56280.70 | 778371.69 | 127614.37 | 148215.82 | 48358.64 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 306100.18 | 19-JAN-16:49 | 94088.97 | 02-JAN-10:50 | 4435.75 | 10-JAN-09:09 | 5613.05 | 02-JAN-10:09 | 0.00 | 0.00 |
February | 340901.45 | 24-FEB-11:30 | 94088.97 | 01-FEB-13:20 | 5081.44 | 13-FEB-12:00 | 5613.05 | 01-FEB-11:30 | 0.00 | 0.00 |
March | 384823.54 | 30-MAR-12:30 | 94088.97 | 06-MAR-09:09 | 5084.88 | 09-MAR-07:00 | 5613.05 | 03-MAR-07:10 | 0.00 | 0.00 |
April | 450715.85 | 28-APR-14:50 | 94088.97 | 01-APR-06:19 | 4131.32 | 10-APR-11:50 | 5613.05 | 01-APR-06:10 | 0.00 | 0.00 |
May | 339038.26 | 01-MAY-14:30 | 94088.97 | 01-MAY-04:30 | 0.00 | 01-MAY-00:10 | 5613.05 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 384073.78 | 28-JUN-14:30 | 94088.97 | 01-JUN-06:19 | 0.00 | 01-JUN-00:10 | 5613.05 | 01-JUN-06:10 | 0.00 | 0.00 |
July | 445000.97 | 24-JUL-12:09 | 94088.97 | 01-JUL-03:30 | 0.00 | 01-JUL-00:10 | 5613.05 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 465448.05 | 07-AUG-12:20 | 94088.97 | 01-AUG-05:19 | 0.00 | 01-AUG-00:10 | 5613.05 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 348146.33 | 29-SEP-15:00 | 94088.97 | 01-SEP-04:19 | 0.00 | 01-SEP-00:10 | 5613.05 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 404561.33 | 06-OCT-13:00 | 94088.97 | 02-OCT-09:30 | 3770.92 | 27-OCT-11:00 | 5613.05 | 02-OCT-08:50 | 0.00 | 0.00 |
November | 399051.24 | 07-NOV-13:09 | 94088.97 | 01-NOV-06:10 | 4431.01 | 22-NOV-11:20 | 5613.05 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 440415.58 | 11-DEC-14:50 | 94088.97 | 08-DEC-11:09 | 5082.15 | 26-DEC-12:00 | 5613.05 | 02-DEC-13:30 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||
Minimum of Months | 306100.18 | 94088.97 | 0.00 | 5613.05 | 0.00 | 0.00 | ||||
Maximum of Months | 465448.05 | 94088.97 | 5084.88 | 5613.05 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1362763.86 | 19-JAN-16:30 | 288632.03 | 423497.50 | 0.00 | 90800.38 | 108942.19 | 46549.55 | 0.00 | 304640.19 | 94088.97 |
February | 1509383.96 | 27-FEB-16:00 | 288632.03 | 541788.89 | 0.00 | 90800.38 | 113515.84 | 46308.18 | 0.00 | 328636.62 | 94088.97 |
March | 1665454.90 | 29-MAR-15:39 | 286578.00 | 660080.29 | 0.00 | 90798.79 | 108039.89 | 46546.96 | 0.00 | 373708.96 | 94088.97 |
April | 1876628.57 | 28-APR-15:00 | 286578.00 | 778371.69 | 0.00 | 90798.79 | 129736.80 | 47027.37 | 0.00 | 444413.92 | 94088.97 |
May | 1403732.52 | 02-MAY-15:09 | 286578.00 | 423497.50 | 0.00 | 90798.79 | 125086.53 | 46640.10 | 0.00 | 331429.59 | 94088.97 |
June | 1578883.88 | 28-JUN-15:09 | 286578.00 | 541788.89 | 0.00 | 90798.79 | 131316.73 | 47137.38 | 0.00 | 381562.08 | 94088.97 |
July | 1750842.97 | 21-JUL-15:00 | 286578.00 | 660080.29 | 0.00 | 90798.79 | 133589.58 | 47132.22 | 0.00 | 432962.09 | 94088.97 |
August | 1901542.21 | 03-AUG-15:50 | 286578.00 | 778371.69 | 0.00 | 90798.79 | 142765.05 | 47257.65 | 0.00 | 456069.03 | 94088.97 |
September | 1402613.04 | 18-SEP-15:00 | 286578.00 | 423497.50 | 0.00 | 90798.79 | 118627.21 | 47035.07 | 0.00 | 336374.46 | 94088.97 |
October | 1590210.61 | 06-OCT-15:09 | 286578.00 | 541788.89 | 0.00 | 90798.79 | 133950.32 | 47561.84 | 0.00 | 389830.76 | 94088.97 |
November | 1692438.78 | 07-NOV-16:49 | 292927.73 | 660080.29 | 0.00 | 90801.08 | 113530.57 | 46502.35 | 0.00 | 388894.75 | 94088.97 |
December | 1841632.86 | 12-DEC-16:40 | 296406.22 | 778371.69 | 0.00 | 90806.39 | 106815.08 | 46741.75 | 0.00 | 422789.72 | 94088.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1362763.86 | 286578.00 | 423497.50 | 0.00 | 90798.79 | 106815.08 | 46308.18 | 0.00 | 304640.19 | 94088.97 | |
Maximum of Months | 1901542.21 | 296406.22 | 778371.69 | 0.00 | 90806.39 | 142765.05 | 47561.84 | 0.00 | 456069.03 | 94088.97 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 858604.70 | 21-JAN-07:10 | 0.00 | 67990.36 | 23-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 834339.37 | 17-FEB-07:10 | 0.00 | 67883.73 | 01-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 799977.41 | 09-MAR-07:10 | 0.00 | 66489.64 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 178973.57 | 10-APR-00:10 | 0.00 | 62691.29 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 145108.57 | 21-MAY-19:00 | 0.00 | 58160.78 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 96991.84 | 25-JUN-21:10 | 0.00 | 52628.55 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 144989.03 | 16-JUL-13:39 | 0.00 | 46922.22 | 03-JUL-11:00 | 0.00 |
August | 0.00 | 0.00 | 96460.74 | 13-AUG-09:20 | 0.00 | 50053.23 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 146367.93 | 24-SEP-22:19 | 0.00 | 54981.67 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 245175.25 | 29-OCT-18:49 | 0.00 | 60703.03 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 240515.37 | 19-NOV-10:30 | 0.00 | 64847.58 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 838441.21 | 21-DEC-07:10 | 0.00 | 67096.57 | 26-DEC-12:39 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 96460.74 | 0.00 | 46922.22 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 858604.70 | 0.00 | 67990.36 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 26.69 | 0.67 | 27.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.73 | 1.17 | 27.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.51 | 0.33 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.54 | 0.17 | 27.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.43 | 0.83 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.30 | 0.50 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 26.53 | 2.83 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.41 | 3.00 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.67 | 4.50 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.77 | 2.83 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.04 | 2.83 | 27.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.01 | 2.50 | 27.61 |
Annual Sum or Average | 0.00 | 0.00 | 126.33 | 26.63 | 22.17 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.30 | 0.17 | 27.45 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.04 | 4.50 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 18.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 18.68 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.57 | 1.17 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.87 | 1.17 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.08 | 4.50 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.81 | 2.00 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.86 | 4.00 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.68 | 1.67 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.87 | 5.00 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.74 | 3.00 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.83 | 27.83 | 23.83 | 27.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.08 | 5.00 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 26.69 | 10.83 | 26.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.03 | 8.33 | 26.03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.56 | 1.67 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.37 | 0.50 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.36 | 1.50 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.64 | 5.83 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 26.25 | 20.67 | 26.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 25.75 | 32.00 | 25.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 25.71 | 28.17 | 25.71 |
Annual Sum or Average | 0.00 | 0.00 | 110.00 | 26.11 | 109.50 | 26.10 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 27.64 | 32.00 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.70 | 1.33 | 27.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.90 | 1.83 | 27.90 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.51 | 3.00 | 27.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.44 | 5.33 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.88 | 3.17 | 28.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.30 | 5.17 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.21 | 10.50 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.11 | 7.83 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.91 | 3.83 | 28.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.46 | 6.50 | 28.02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.61 | 3.83 | 28.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.38 | 4.83 | 27.88 |
Annual Sum or Average | 0.00 | 0.00 | 124.33 | 27.37 | 57.17 | 27.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.11 | 1.33 | 27.70 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.91 | 10.50 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.32 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.47 | 0.67 | 27.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.08 | 1.00 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.96 | 6.00 | 27.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.83 | 3.00 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.89 | 6.00 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.69 | 3.33 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.96 | 5.33 | 27.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.74 | 3.33 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.37 | 0.33 | 27.37 |
December | 0.17 | 19.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.35 | 0.00 | 29.00 | 27.86 | 29.00 | 27.86 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.39 | 0.00 | 0.00 | 6.00 | 28.08 | 6.00 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.57 | 12.33 | 26.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 25.46 | 12.50 | 25.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.49 | 1.00 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.38 | 0.33 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.64 | 5.50 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 25.62 | 36.83 | 25.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 25.67 | 41.83 | 25.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 37.67 | 25.57 | 37.67 | 25.57 |
Annual Sum or Average | 0.00 | 0.00 | 148.50 | 25.78 | 148.00 | 25.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 27.64 | 41.83 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 28.04 | 0.50 | 28.04 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.87 | 1.83 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.18 | 2.00 | 28.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.97 | 2.83 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.67 | 5.00 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.69 | 2.67 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.25 | 3.00 | 28.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.95 | 3.33 | 27.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.67 | 0.33 | 27.67 |
Annual Sum or Average | 0.00 | 0.00 | 34.50 | 27.90 | 23.17 | 27.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.25 | 5.00 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.05 | 0.17 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.50 | 17.51 | 2.00 | 17.34 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.83 | 19.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.44 | 0.83 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.44 | 2.50 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.40 | 1.67 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.53 | 1.33 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.41 | 0.83 | 27.41 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.83 | 19.00 | 0.17 | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10.00 | 18.36 | 2.33 | 17.78 | 8.00 | 27.44 | 7.50 | 27.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 19.19 | 2.00 | 20.44 | 2.67 | 27.53 | 2.50 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 18.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.50 | 17.47 | 0.50 | 16.62 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 19.17 | 0.00 | 0.00 | 0.33 | 27.40 | 0.33 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.08 | 1.00 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.98 | 8.33 | 27.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.68 | 6.83 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.81 | 10.33 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.72 | 6.33 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.87 | 8.17 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.73 | 5.00 | 27.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 18.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.00 | 18.42 | 0.50 | 16.62 | 47.17 | 27.82 | 46.33 | 27.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.17 | 0.50 | 16.62 | 10.50 | 28.08 | 10.33 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.08 | 0.00 | 0.00 | 9.50 | 26.53 | 9.50 | 26.53 |
February | 1.50 | 17.33 | 0.67 | 16.27 | 6.17 | 25.60 | 6.17 | 25.60 |
March | 0.50 | 19.29 | 0.00 | 0.00 | 1.17 | 27.48 | 1.17 | 27.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.34 | 0.83 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.83 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.41 | 3.33 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.47 | 3.83 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.78 | 6.67 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 26.04 | 23.00 | 25.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 25.74 | 26.50 | 25.74 |
December | 0.50 | 18.83 | 0.00 | 0.00 | 17.50 | 25.90 | 17.50 | 25.90 |
Annual Sum or Average | 4.00 | 18.42 | 0.67 | 16.27 | 101.17 | 26.23 | 99.33 | 26.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.29 | 0.67 | 16.27 | 26.50 | 27.78 | 26.50 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.04 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
February | 1.17 | 16.77 | 0.50 | 14.95 | 0.67 | 27.83 | 0.67 | 27.83 |
March | 0.50 | 19.37 | 0.00 | 0.00 | 0.83 | 27.60 | 0.67 | 27.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.97 | 2.00 | 27.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.18 | 3.00 | 28.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.18 | 3.00 | 28.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.84 | 6.00 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.82 | 3.83 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.24 | 3.83 | 28.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.09 | 3.50 | 28.18 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.46 | 0.83 | 27.46 |
December | 0.50 | 18.87 | 0.00 | 0.00 | 0.33 | 27.66 | 0.33 | 27.66 |
Annual Sum or Average | 3.67 | 18.34 | 0.50 | 14.95 | 41.17 | 28.01 | 27.83 | 28.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
Maximum of Months | 1.50 | 19.37 | 0.50 | 14.95 | 9.00 | 28.24 | 6.00 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.56 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 27.56 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.56 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.90 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 237.33 | 28.20 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 250.50 | 28.18 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 237.33 | 28.20 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.33 | 24.57 | 241.83 | 25.14 | 41.00 | 24.75 |
February | 81.33 | 24.60 | 317.33 | 24.75 | 65.50 | 24.73 |
March | 93.50 | 24.71 | 316.33 | 24.69 | 78.33 | 24.84 |
April | 162.83 | 24.84 | 432.17 | 24.61 | 162.83 | 24.84 |
May | 280.83 | 24.84 | 508.00 | 24.53 | 280.83 | 24.84 |
June | 253.50 | 24.90 | 496.00 | 24.48 | 253.50 | 24.90 |
July | 252.83 | 25.21 | 497.00 | 24.63 | 252.83 | 25.21 |
August | 194.50 | 25.04 | 514.00 | 24.49 | 194.50 | 25.04 |
September | 203.17 | 24.99 | 485.00 | 24.57 | 203.17 | 24.99 |
October | 139.33 | 25.17 | 453.00 | 24.69 | 139.33 | 25.17 |
November | 64.83 | 25.14 | 389.00 | 24.79 | 64.83 | 25.14 |
December | 51.50 | 24.73 | 315.50 | 24.96 | 49.17 | 24.76 |
Annual Sum or Average | 1832.50 | 24.94 | 4965.17 | 24.66 | 1785.83 | 24.97 |
Minimum of Months | 51.50 | 24.57 | 241.83 | 24.48 | 41.00 | 24.73 |
Maximum of Months | 280.83 | 25.21 | 514.00 | 25.14 | 280.83 | 25.21 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 114.83 | 23.52 | 196.00 | 24.50 | 0.00 | 0.00 |
February | 50.17 | 23.62 | 274.17 | 24.36 | 0.00 | 0.00 |
March | 30.50 | 23.64 | 306.00 | 24.41 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 423.33 | 24.26 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 485.00 | 24.24 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 473.33 | 24.16 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 478.17 | 24.14 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 510.33 | 24.11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 458.17 | 24.24 | 0.00 | 0.00 |
October | 2.50 | 23.66 | 441.17 | 24.31 | 0.00 | 0.00 |
November | 1.17 | 23.92 | 376.50 | 24.40 | 0.00 | 0.00 |
December | 13.83 | 23.68 | 309.33 | 24.48 | 0.00 | 0.00 |
Annual Sum or Average | 213.00 | 23.57 | 4731.50 | 24.27 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 196.00 | 24.11 | 0.00 | 0.00 |
Maximum of Months | 114.83 | 23.92 | 510.33 | 24.50 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.33 | 23.12 | 76.50 | 24.17 | 0.00 | 0.00 |
February | 231.83 | 23.13 | 129.17 | 24.17 | 0.00 | 0.00 |
March | 216.33 | 23.18 | 156.00 | 24.23 | 0.00 | 0.00 |
April | 75.83 | 23.23 | 244.67 | 24.35 | 0.00 | 0.00 |
May | 28.50 | 23.25 | 333.17 | 24.23 | 0.00 | 0.00 |
June | 24.50 | 23.24 | 323.00 | 24.21 | 0.00 | 0.00 |
July | 30.67 | 23.23 | 309.33 | 24.23 | 0.00 | 0.00 |
August | 16.83 | 23.17 | 348.17 | 24.22 | 0.00 | 0.00 |
September | 37.33 | 23.21 | 286.83 | 24.21 | 0.00 | 0.00 |
October | 44.00 | 23.23 | 291.00 | 24.26 | 0.00 | 0.00 |
November | 135.67 | 23.24 | 191.83 | 24.26 | 0.00 | 0.00 |
December | 236.33 | 23.12 | 124.50 | 24.28 | 0.00 | 0.00 |
Annual Sum or Average | 1399.17 | 23.16 | 2814.17 | 24.24 | 0.00 | |
Minimum of Months | 16.83 | 23.12 | 76.50 | 24.17 | 0.00 | 0.00 |
Maximum of Months | 321.33 | 23.25 | 348.17 | 24.35 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 406.17 | 22.16 | 71.50 | 23.47 | 13.00 | 20.67 |
February | 306.50 | 22.30 | 109.50 | 23.31 | 18.00 | 19.52 |
March | 293.00 | 22.64 | 141.50 | 23.99 | 6.33 | 20.10 |
April | 113.83 | 23.12 | 238.50 | 24.27 | 0.00 | 0.00 |
May | 9.17 | 23.16 | 390.50 | 24.24 | 0.00 | 0.00 |
June | 0.17 | 23.31 | 406.17 | 24.21 | 0.00 | 0.00 |
July | 1.50 | 23.25 | 399.50 | 24.25 | 0.00 | 0.00 |
August | 0.67 | 23.32 | 404.17 | 24.24 | 0.00 | 0.00 |
September | 9.17 | 23.30 | 335.33 | 24.21 | 0.00 | 0.00 |
October | 65.17 | 22.88 | 308.50 | 24.26 | 0.00 | 0.00 |
November | 252.33 | 22.82 | 135.50 | 24.11 | 0.00 | 0.00 |
December | 363.50 | 22.41 | 89.00 | 23.79 | 8.67 | 20.55 |
Annual Sum or Average | 1821.17 | 22.50 | 3029.67 | 24.16 | 46.00 | 20.12 |
Minimum of Months | 0.17 | 22.16 | 71.50 | 23.31 | 0.00 | 0.00 |
Maximum of Months | 406.17 | 23.32 | 406.17 | 24.27 | 18.00 | 20.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 350.67 | 22.44 | 96.00 | 24.18 | 0.17 | 20.99 |
February | 235.33 | 22.67 | 136.33 | 24.03 | 5.17 | 20.29 |
March | 217.17 | 22.94 | 192.83 | 24.25 | 0.00 | 0.00 |
April | 43.33 | 23.39 | 340.50 | 24.19 | 0.00 | 0.00 |
May | 8.83 | 25.94 | 508.00 | 24.37 | 8.83 | 25.94 |
June | 1.00 | 26.19 | 493.83 | 24.31 | 1.00 | 26.19 |
July | 5.33 | 26.36 | 496.00 | 24.38 | 5.33 | 26.36 |
August | 3.50 | 26.36 | 514.00 | 24.26 | 3.50 | 26.36 |
September | 11.00 | 25.74 | 475.33 | 24.37 | 11.00 | 25.74 |
October | 43.67 | 23.64 | 416.50 | 24.35 | 6.17 | 25.72 |
November | 151.00 | 23.30 | 227.83 | 24.20 | 0.00 | 0.00 |
December | 243.00 | 22.89 | 159.33 | 24.18 | 0.00 | 0.00 |
Annual Sum or Average | 1313.83 | 22.90 | 4056.50 | 24.30 | 41.17 | 25.22 |
Minimum of Months | 1.00 | 22.44 | 96.00 | 24.03 | 0.00 | 0.00 |
Maximum of Months | 350.67 | 26.36 | 514.00 | 24.38 | 11.00 | 26.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 324.17 | 22.44 | 109.67 | 24.36 | 3.83 | 24.07 |
February | 240.33 | 22.61 | 135.83 | 24.20 | 4.83 | 21.63 |
March | 229.17 | 22.64 | 199.17 | 24.36 | 5.17 | 26.62 |
April | 101.50 | 23.19 | 297.00 | 24.22 | 5.33 | 26.83 |
May | 32.50 | 26.48 | 478.83 | 24.43 | 31.50 | 26.58 |
June | 12.83 | 26.26 | 467.50 | 24.32 | 11.50 | 26.63 |
July | 22.17 | 26.49 | 461.33 | 24.39 | 21.00 | 26.68 |
August | 17.50 | 25.27 | 458.83 | 24.22 | 10.83 | 26.55 |
September | 34.50 | 26.25 | 415.50 | 24.46 | 31.00 | 26.59 |
October | 71.00 | 24.03 | 372.83 | 24.41 | 21.33 | 26.41 |
November | 172.00 | 23.03 | 222.50 | 24.33 | 3.83 | 26.56 |
December | 285.00 | 22.56 | 133.17 | 24.23 | 2.33 | 22.92 |
Annual Sum or Average | 1542.67 | 23.00 | 3752.17 | 24.34 | 152.50 | 26.31 |
Minimum of Months | 12.83 | 22.44 | 109.67 | 24.20 | 2.33 | 21.63 |
Maximum of Months | 324.17 | 26.49 | 478.83 | 24.46 | 31.50 | 26.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 216.33 | 23.06 | 208.83 | 24.61 | 25.00 | 26.65 |
February | 151.83 | 23.01 | 237.67 | 24.39 | 16.33 | 24.69 |
March | 182.50 | 22.85 | 231.50 | 24.34 | 8.00 | 25.75 |
April | 51.33 | 23.29 | 341.17 | 24.24 | 0.00 | 0.00 |
May | 10.00 | 25.88 | 507.00 | 24.37 | 10.00 | 25.88 |
June | 1.17 | 26.20 | 492.33 | 24.31 | 1.17 | 26.20 |
July | 8.00 | 26.41 | 495.00 | 24.39 | 8.00 | 26.41 |
August | 11.00 | 26.58 | 514.00 | 24.28 | 11.00 | 26.58 |
September | 37.67 | 26.50 | 476.67 | 24.44 | 37.67 | 26.50 |
October | 69.00 | 25.63 | 448.00 | 24.57 | 45.67 | 26.82 |
November | 96.17 | 24.48 | 353.33 | 24.63 | 34.00 | 26.83 |
December | 166.00 | 23.51 | 278.17 | 24.70 | 30.50 | 26.88 |
Annual Sum or Average | 1001.00 | 23.64 | 4583.67 | 24.42 | 227.33 | 26.50 |
Minimum of Months | 1.17 | 22.85 | 208.83 | 24.24 | 0.00 | 0.00 |
Maximum of Months | 216.33 | 26.58 | 514.00 | 24.70 | 45.67 | 26.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 258.17 | 22.59 | 170.50 | 24.42 | 5.33 | 26.63 |
February | 116.33 | 22.97 | 266.67 | 24.45 | 7.00 | 26.70 |
March | 86.67 | 23.51 | 348.67 | 24.51 | 10.83 | 26.83 |
April | 28.83 | 26.67 | 464.83 | 24.54 | 28.33 | 26.73 |
May | 23.33 | 26.65 | 508.00 | 24.48 | 23.33 | 26.65 |
June | 28.00 | 26.61 | 496.00 | 24.46 | 28.00 | 26.61 |
July | 56.67 | 26.63 | 497.00 | 24.58 | 56.67 | 26.63 |
August | 45.50 | 26.64 | 514.00 | 24.46 | 45.50 | 26.64 |
September | 29.17 | 26.72 | 483.83 | 24.48 | 29.17 | 26.72 |
October | 46.33 | 25.94 | 464.67 | 24.56 | 36.00 | 26.73 |
November | 40.33 | 24.89 | 397.33 | 24.53 | 18.00 | 26.81 |
December | 92.17 | 23.97 | 327.67 | 24.69 | 20.00 | 26.73 |
Annual Sum or Average | 851.50 | 24.19 | 4939.17 | 24.52 | 308.17 | 26.69 |
Minimum of Months | 23.33 | 22.59 | 170.50 | 24.42 | 5.33 | 26.61 |
Maximum of Months | 258.17 | 26.72 | 514.00 | 24.69 | 56.67 | 26.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 449.67 | 21.57 | 104.67 | 21.68 | 72.83 | 20.67 |
February | 378.00 | 21.87 | 96.33 | 22.01 | 47.67 | 19.97 |
March | 379.00 | 22.21 | 102.00 | 23.21 | 23.17 | 20.43 |
April | 197.33 | 23.07 | 215.83 | 24.18 | 11.67 | 25.28 |
May | 30.83 | 25.36 | 495.00 | 24.32 | 30.83 | 25.36 |
June | 13.33 | 25.50 | 490.17 | 24.32 | 12.00 | 25.76 |
July | 34.50 | 25.82 | 486.17 | 24.43 | 34.50 | 25.82 |
August | 26.17 | 25.44 | 499.33 | 24.32 | 26.17 | 25.44 |
September | 42.17 | 24.86 | 427.33 | 24.31 | 39.00 | 24.98 |
October | 122.17 | 23.43 | 358.83 | 24.29 | 32.50 | 25.20 |
November | 311.50 | 22.39 | 103.33 | 24.04 | 2.33 | 23.47 |
December | 408.50 | 21.86 | 83.67 | 22.81 | 34.50 | 21.08 |
Annual Sum or Average | 2393.17 | 22.33 | 3462.67 | 24.10 | 367.17 | 23.01 |
Minimum of Months | 13.33 | 21.57 | 83.67 | 21.68 | 2.33 | 19.97 |
Maximum of Months | 449.67 | 25.82 | 499.33 | 24.43 | 72.83 | 25.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.50 | 21.79 | 73.00 | 22.65 | 37.67 | 20.93 |
February | 297.33 | 21.99 | 88.83 | 22.95 | 28.33 | 20.30 |
March | 272.17 | 22.19 | 126.67 | 23.97 | 17.50 | 21.57 |
April | 144.33 | 23.06 | 214.33 | 24.46 | 16.67 | 25.85 |
May | 52.33 | 26.24 | 393.33 | 24.53 | 51.17 | 26.30 |
June | 31.50 | 26.23 | 397.83 | 24.46 | 29.33 | 26.48 |
July | 56.00 | 26.40 | 399.67 | 24.60 | 54.00 | 26.51 |
August | 42.00 | 25.85 | 395.33 | 24.45 | 37.17 | 26.20 |
September | 73.67 | 25.19 | 322.50 | 24.56 | 50.83 | 26.14 |
October | 119.50 | 23.79 | 287.17 | 24.55 | 38.67 | 26.16 |
November | 238.67 | 22.50 | 116.33 | 24.42 | 4.67 | 25.94 |
December | 337.83 | 21.96 | 73.67 | 23.26 | 25.83 | 21.50 |
Annual Sum or Average | 2036.83 | 22.71 | 2888.67 | 24.36 | 391.83 | 24.80 |
Minimum of Months | 31.50 | 21.79 | 73.00 | 22.65 | 4.67 | 20.30 |
Maximum of Months | 371.50 | 26.40 | 399.67 | 24.60 | 54.00 | 26.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 258.83 | 22.71 | 194.00 | 24.45 | 41.83 | 24.73 |
February | 199.00 | 22.54 | 199.67 | 24.25 | 20.50 | 23.10 |
March | 258.67 | 22.42 | 178.50 | 24.01 | 16.50 | 22.07 |
April | 145.50 | 23.14 | 264.17 | 24.27 | 11.67 | 25.42 |
May | 30.83 | 25.33 | 492.67 | 24.32 | 30.83 | 25.33 |
June | 13.50 | 25.41 | 486.33 | 24.31 | 12.17 | 25.66 |
July | 35.00 | 25.78 | 484.67 | 24.43 | 35.00 | 25.78 |
August | 31.83 | 25.70 | 503.17 | 24.35 | 31.83 | 25.70 |
September | 63.50 | 25.90 | 456.33 | 24.42 | 62.67 | 25.94 |
October | 96.67 | 25.12 | 431.67 | 24.61 | 60.50 | 26.45 |
November | 157.33 | 23.82 | 302.50 | 24.72 | 40.33 | 26.57 |
December | 229.67 | 22.95 | 236.83 | 24.71 | 43.67 | 25.58 |
Annual Sum or Average | 1520.33 | 23.33 | 4230.50 | 24.41 | 407.50 | 25.51 |
Minimum of Months | 13.50 | 22.42 | 178.50 | 24.01 | 11.67 | 22.07 |
Maximum of Months | 258.83 | 25.90 | 503.17 | 24.72 | 62.67 | 26.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 391.17 | 21.81 | 96.83 | 23.10 | 35.83 | 21.11 |
February | 302.50 | 21.99 | 121.00 | 23.35 | 26.50 | 20.40 |
March | 299.17 | 22.19 | 153.67 | 23.93 | 17.67 | 21.85 |
April | 136.67 | 23.36 | 296.50 | 24.41 | 21.33 | 26.42 |
May | 35.17 | 25.98 | 478.17 | 24.39 | 35.17 | 25.98 |
June | 27.00 | 26.28 | 483.00 | 24.40 | 24.50 | 26.61 |
July | 47.33 | 26.42 | 486.00 | 24.51 | 47.33 | 26.42 |
August | 34.00 | 26.25 | 501.33 | 24.40 | 34.00 | 26.25 |
September | 52.50 | 25.33 | 425.50 | 24.41 | 41.50 | 25.92 |
October | 99.83 | 23.97 | 383.67 | 24.40 | 38.33 | 26.04 |
November | 259.50 | 22.51 | 164.83 | 24.28 | 6.17 | 25.75 |
December | 336.00 | 21.98 | 124.50 | 23.93 | 19.00 | 22.09 |
Annual Sum or Average | 2020.83 | 22.63 | 3715.00 | 24.31 | 347.33 | 24.78 |
Minimum of Months | 27.00 | 21.81 | 96.83 | 23.10 | 6.17 | 20.40 |
Maximum of Months | 391.17 | 26.42 | 501.33 | 24.51 | 47.33 | 26.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 456.83 | 21.21 | 184.67 | 20.92 | 155.17 | 20.34 |
February | 386.83 | 21.52 | 140.83 | 21.32 | 92.00 | 19.90 |
March | 389.17 | 21.90 | 140.50 | 22.41 | 62.00 | 20.34 |
April | 209.67 | 22.79 | 213.50 | 24.18 | 12.00 | 25.23 |
May | 40.83 | 25.47 | 486.83 | 24.35 | 40.83 | 25.47 |
June | 26.33 | 25.62 | 488.00 | 24.36 | 23.33 | 25.95 |
July | 58.67 | 26.13 | 483.83 | 24.48 | 58.67 | 26.13 |
August | 48.50 | 25.62 | 491.67 | 24.35 | 46.83 | 25.71 |
September | 68.00 | 24.81 | 420.83 | 24.35 | 53.50 | 25.24 |
October | 140.00 | 23.24 | 352.33 | 24.26 | 45.33 | 24.70 |
November | 344.33 | 22.00 | 117.33 | 23.26 | 30.00 | 20.99 |
December | 421.33 | 21.50 | 158.17 | 21.64 | 111.17 | 20.64 |
Annual Sum or Average | 2590.50 | 22.15 | 3678.50 | 23.84 | 730.83 | 22.34 |
Minimum of Months | 26.33 | 21.21 | 117.33 | 20.92 | 12.00 | 19.90 |
Maximum of Months | 456.83 | 26.13 | 491.67 | 24.48 | 155.17 | 26.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 442.33 | 21.45 | 139.17 | 21.57 | 95.67 | 20.36 |
February | 344.67 | 21.69 | 137.00 | 22.33 | 55.00 | 19.76 |
March | 315.00 | 21.97 | 191.83 | 23.46 | 44.83 | 20.85 |
April | 155.00 | 22.86 | 278.00 | 24.32 | 17.50 | 25.81 |
May | 62.67 | 26.22 | 474.00 | 24.45 | 60.50 | 26.33 |
June | 44.67 | 26.27 | 477.00 | 24.41 | 41.33 | 26.55 |
July | 74.33 | 26.33 | 475.33 | 24.54 | 69.17 | 26.57 |
August | 59.67 | 25.79 | 478.83 | 24.39 | 51.67 | 26.22 |
September | 96.83 | 25.14 | 403.17 | 24.46 | 67.17 | 26.09 |
October | 140.83 | 23.58 | 357.50 | 24.41 | 50.00 | 25.63 |
November | 291.67 | 22.26 | 140.83 | 23.96 | 15.33 | 22.10 |
December | 398.83 | 21.65 | 132.67 | 22.47 | 65.67 | 20.79 |
Annual Sum or Average | 2426.50 | 22.51 | 3685.33 | 24.11 | 633.83 | 23.73 |
Minimum of Months | 44.67 | 21.45 | 132.67 | 21.57 | 15.33 | 19.76 |
Maximum of Months | 442.33 | 26.33 | 478.83 | 24.54 | 95.67 | 26.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 291.67 | 22.19 | 197.00 | 23.64 | 71.67 | 22.30 |
February | 230.83 | 22.06 | 203.33 | 23.62 | 45.83 | 21.14 |
March | 290.83 | 22.12 | 198.67 | 23.44 | 47.83 | 21.14 |
April | 167.00 | 22.84 | 255.67 | 24.26 | 12.33 | 25.39 |
May | 41.83 | 25.48 | 483.50 | 24.36 | 41.83 | 25.48 |
June | 27.00 | 25.49 | 482.50 | 24.35 | 23.33 | 25.87 |
July | 60.50 | 26.03 | 482.83 | 24.47 | 59.00 | 26.10 |
August | 53.00 | 25.81 | 496.00 | 24.37 | 51.50 | 25.89 |
September | 77.17 | 25.68 | 443.83 | 24.44 | 71.17 | 25.88 |
October | 108.17 | 24.64 | 420.67 | 24.56 | 60.33 | 26.35 |
November | 191.67 | 23.16 | 279.83 | 24.58 | 37.83 | 25.66 |
December | 256.83 | 22.35 | 237.00 | 24.12 | 59.33 | 23.09 |
Annual Sum or Average | 1796.50 | 23.01 | 4180.83 | 24.28 | 582.00 | 24.41 |
Minimum of Months | 27.00 | 22.06 | 197.00 | 23.44 | 12.33 | 21.14 |
Maximum of Months | 291.67 | 26.03 | 496.00 | 24.58 | 71.67 | 26.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.17 | 21.52 | 144.00 | 21.99 | 91.67 | 20.68 |
February | 329.00 | 21.70 | 144.17 | 22.52 | 61.00 | 20.24 |
March | 327.17 | 21.92 | 167.33 | 23.34 | 43.67 | 21.05 |
April | 170.83 | 23.02 | 272.50 | 24.39 | 22.00 | 26.33 |
May | 45.67 | 25.63 | 460.67 | 24.40 | 40.83 | 25.93 |
June | 33.33 | 26.03 | 469.83 | 24.41 | 28.67 | 26.55 |
July | 57.50 | 26.18 | 474.33 | 24.53 | 53.33 | 26.42 |
August | 43.33 | 26.03 | 487.50 | 24.41 | 41.00 | 26.21 |
September | 79.33 | 24.78 | 406.50 | 24.42 | 51.17 | 25.78 |
October | 124.33 | 23.61 | 360.83 | 24.41 | 41.67 | 25.98 |
November | 293.33 | 22.15 | 148.17 | 24.11 | 14.33 | 23.23 |
December | 362.00 | 21.69 | 146.83 | 22.99 | 57.83 | 21.13 |
Annual Sum or Average | 2278.00 | 22.40 | 3682.67 | 24.14 | 547.17 | 23.56 |
Minimum of Months | 33.33 | 21.52 | 144.00 | 21.99 | 14.33 | 20.24 |
Maximum of Months | 412.17 | 26.18 | 487.50 | 24.53 | 91.67 | 26.55 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.55509 | 38.23368 | 0.50102 | 11.19843 |
February | 454.00000 | 24.52899 | 46.43935 | 0.55064 | 12.20922 |
March | 514.00000 | 24.43294 | 45.10002 | 0.52236 | 11.53250 |
April | 485.00000 | 24.53532 | 56.64840 | 0.62654 | 14.05337 |
May | 508.00000 | 24.52516 | 64.29224 | -0.1648 | 6.85655 |
June | 496.00000 | 24.47689 | 64.12637 | -0.1785 | 6.82476 |
July | 497.00000 | 24.62878 | 63.37048 | -0.1306 | 7.02832 |
August | 514.00000 | 24.48688 | 61.43740 | -0.1700 | 6.74964 |
September | 485.00000 | 24.56405 | 61.36206 | -0.1531 | 6.78701 |
October | 502.00000 | 24.61381 | 55.51028 | 0.65649 | 14.93772 |
November | 489.00000 | 24.62027 | 47.21835 | 0.59719 | 13.31773 |
December | 497.00000 | 24.60910 | 42.21789 | 0.55377 | 12.37716 |
Annual Sum or Average | 5943.00000 | 24.54767 | 53.87390 | 0.26449 | 10.29666 |
Minimum of Months | 454.00000 | 24.43294 | 38.23368 | -0.1785 | 6.74964 |
Maximum of Months | 514.00000 | 24.62878 | 64.29224 | 0.65649 | 14.93772 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.10038 | 37.71262 | 0.39533 | 8.75898 |
February | 454.00000 | 24.18783 | 41.46053 | 0.44857 | 9.64387 |
March | 514.00000 | 24.21003 | 40.69400 | 0.45798 | 9.74487 |
April | 485.00000 | 24.21796 | 46.22758 | 0.51031 | 10.65454 |
May | 508.00000 | 24.20666 | 49.28387 | -0.3410 | 7.77078 |
June | 496.00000 | 24.13645 | 49.24868 | -0.3559 | 7.83051 |
July | 497.00000 | 24.12528 | 49.11788 | -0.3542 | 7.75395 |
August | 514.00000 | 24.10908 | 49.10592 | -0.3471 | 7.59949 |
September | 485.00000 | 24.19699 | 49.23086 | -0.3415 | 7.77290 |
October | 502.00000 | 24.25635 | 46.70837 | 0.52287 | 10.97382 |
November | 489.00000 | 24.30535 | 43.24915 | 0.50799 | 10.72909 |
December | 497.00000 | 24.28457 | 39.81522 | 0.47466 | 10.12103 |
Annual Sum or Average | 5943.00000 | 24.19440 | 45.17400 | 0.12822 | 9.10287 |
Minimum of Months | 454.00000 | 24.10038 | 37.71262 | -0.3559 | 7.59949 |
Maximum of Months | 514.00000 | 24.30535 | 49.28387 | 0.52287 | 10.97382 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.44435 | 39.96861 | 0.21789 | 6.71808 |
February | 454.00000 | 23.56227 | 43.76035 | 0.27684 | 7.37623 |
March | 514.00000 | 23.69432 | 42.99534 | 0.31132 | 7.61467 |
April | 485.00000 | 23.96308 | 48.00296 | 0.42120 | 9.01852 |
May | 508.00000 | 24.00794 | 50.16081 | -0.4261 | 9.19120 |
June | 496.00000 | 23.99334 | 50.08664 | -0.4285 | 9.19079 |
July | 497.00000 | 23.98891 | 50.10472 | -0.4323 | 9.31223 |
August | 514.00000 | 24.02313 | 50.12892 | -0.4176 | 9.00383 |
September | 485.00000 | 23.94787 | 50.35007 | -0.4471 | 9.58631 |
October | 502.00000 | 24.00936 | 47.95574 | 0.44471 | 9.42761 |
November | 489.00000 | 23.85501 | 45.34501 | 0.37398 | 8.31139 |
December | 497.00000 | 23.61799 | 42.51612 | 0.28536 | 7.42980 |
Annual Sum or Average | 5943.00000 | 23.84403 | 46.79509 | 0.01211 | 8.51961 |
Minimum of Months | 454.00000 | 23.44435 | 39.96861 | -0.4471 | 6.71808 |
Maximum of Months | 514.00000 | 24.02313 | 50.35007 | 0.44471 | 9.58631 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.49080 | 42.12613 | -0.0157 | 7.00268 |
February | 454.00000 | 22.82967 | 45.36564 | 0.09967 | 7.88667 |
March | 514.00000 | 23.23456 | 44.18428 | 0.19955 | 7.48957 |
April | 485.00000 | 23.85575 | 48.34080 | 0.39998 | 8.83250 |
May | 508.00000 | 24.09509 | 49.67670 | -0.3803 | 8.38885 |
June | 496.00000 | 24.11567 | 49.42881 | -0.3685 | 8.13925 |
July | 497.00000 | 24.13375 | 49.42127 | -0.3660 | 8.15864 |
August | 514.00000 | 24.11092 | 49.62960 | -0.3716 | 8.23332 |
September | 485.00000 | 24.01852 | 50.04432 | -0.4120 | 8.90297 |
October | 502.00000 | 23.94860 | 48.07555 | 0.43536 | 9.56878 |
November | 489.00000 | 23.38376 | 46.86937 | 0.25911 | 7.37134 |
December | 497.00000 | 22.82820 | 44.50241 | 0.09142 | 7.07078 |
Annual Sum or Average | 5943.00000 | 23.59217 | 47.31045 | -0.0377 | 8.08597 |
Minimum of Months | 454.00000 | 22.49080 | 42.12613 | -0.4120 | 7.00268 |
Maximum of Months | 514.00000 | 24.13375 | 50.04432 | 0.43536 | 9.56878 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.91845 | 39.87567 | 0.08898 | 7.07376 |
February | 454.00000 | 23.31727 | 42.38832 | 0.21356 | 7.74482 |
March | 514.00000 | 23.61447 | 41.45349 | 0.28921 | 8.05685 |
April | 485.00000 | 24.05643 | 46.16644 | 0.46030 | 9.73428 |
May | 508.00000 | 24.36199 | 49.44791 | -0.2526 | 7.06351 |
June | 496.00000 | 24.30124 | 48.45673 | -0.2560 | 6.87952 |
July | 497.00000 | 24.37518 | 48.58265 | -0.2269 | 6.82602 |
August | 514.00000 | 24.25694 | 48.67048 | -0.2612 | 6.94715 |
September | 485.00000 | 24.34542 | 49.90301 | -0.2690 | 7.31647 |
October | 502.00000 | 24.22758 | 47.46370 | 0.52324 | 11.37707 |
November | 489.00000 | 23.83867 | 43.99297 | 0.36886 | 8.51538 |
December | 497.00000 | 23.49420 | 41.44902 | 0.25307 | 7.65931 |
Annual Sum or Average | 5943.00000 | 23.92927 | 45.67027 | 0.07564 | 7.92931 |
Minimum of Months | 454.00000 | 22.91845 | 39.87567 | -0.2690 | 6.82602 |
Maximum of Months | 514.00000 | 24.37518 | 49.90301 | 0.52324 | 11.37707 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.04614 | 39.12137 | 0.14282 | 7.64030 |
February | 454.00000 | 23.29998 | 42.06394 | 0.23816 | 8.10369 |
March | 514.00000 | 23.47524 | 41.21968 | 0.29264 | 8.83522 |
April | 485.00000 | 23.88342 | 46.20879 | 0.45795 | 10.16862 |
May | 508.00000 | 24.37189 | 48.80836 | -0.1921 | 7.29199 |
June | 496.00000 | 24.26355 | 48.17755 | -0.2199 | 6.94867 |
July | 497.00000 | 24.31594 | 48.36547 | -0.2041 | 7.18073 |
August | 514.00000 | 24.13899 | 48.72523 | -0.2678 | 7.40951 |
September | 485.00000 | 24.31266 | 49.36758 | -0.2386 | 7.92236 |
October | 502.00000 | 24.15910 | 47.08327 | 0.53674 | 12.11278 |
November | 489.00000 | 23.74628 | 43.85348 | 0.37461 | 9.06422 |
December | 497.00000 | 23.20148 | 41.72815 | 0.20510 | 7.73327 |
Annual Sum or Average | 5943.00000 | 23.85458 | 45.40965 | 0.09178 | 8.36523 |
Minimum of Months | 454.00000 | 23.04614 | 39.12137 | -0.2678 | 6.94867 |
Maximum of Months | 514.00000 | 24.37189 | 49.36758 | 0.53674 | 12.11278 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.69763 | 37.41434 | 0.32947 | 10.16065 |
February | 454.00000 | 23.82507 | 40.57280 | 0.38583 | 10.50698 |
March | 514.00000 | 23.69312 | 40.80275 | 0.33479 | 9.27259 |
April | 485.00000 | 24.06595 | 46.02837 | 0.47381 | 10.15332 |
May | 508.00000 | 24.35553 | 49.46547 | -0.2533 | 7.06821 |
June | 496.00000 | 24.29352 | 48.51720 | -0.2637 | 6.98515 |
July | 497.00000 | 24.37879 | 48.57960 | -0.2270 | 6.89542 |
August | 514.00000 | 24.27894 | 48.52609 | -0.2401 | 6.86675 |
September | 485.00000 | 24.42022 | 49.40868 | -0.2113 | 7.28953 |
October | 502.00000 | 24.46106 | 46.24505 | 0.63371 | 14.67660 |
November | 489.00000 | 24.33173 | 42.08912 | 0.55485 | 13.01003 |
December | 497.00000 | 24.03443 | 39.49672 | 0.44844 | 11.87952 |
Annual Sum or Average | 5943.00000 | 24.15404 | 44.78673 | 0.16096 | 9.54774 |
Minimum of Months | 454.00000 | 23.69312 | 37.41434 | -0.2637 | 6.86675 |
Maximum of Months | 514.00000 | 24.46106 | 49.46547 | 0.63371 | 14.67660 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.35221 | 37.91316 | 0.24725 | 8.49502 |
February | 454.00000 | 23.91568 | 40.08229 | 0.42601 | 10.64884 |
March | 514.00000 | 24.17993 | 39.14002 | 0.50818 | 11.76900 |
April | 485.00000 | 24.50511 | 44.12954 | 0.68628 | 15.70590 |
May | 508.00000 | 24.45867 | 48.31690 | -0.1258 | 6.62760 |
June | 496.00000 | 24.44317 | 47.37416 | -0.0864 | 6.44205 |
July | 497.00000 | 24.56862 | 47.18817 | -0.0279 | 6.64306 |
August | 514.00000 | 24.45566 | 47.20549 | -0.0236 | 6.29977 |
September | 485.00000 | 24.46491 | 48.49438 | -0.1327 | 6.93722 |
October | 502.00000 | 24.48161 | 45.69159 | 0.66765 | 15.37234 |
November | 489.00000 | 24.38096 | 41.71190 | 0.58318 | 13.06008 |
December | 497.00000 | 24.32765 | 38.44671 | 0.53806 | 12.51761 |
Annual Sum or Average | 5943.00000 | 24.29615 | 43.82826 | 0.26959 | 10.02129 |
Minimum of Months | 454.00000 | 23.35221 | 37.91316 | -0.1327 | 6.29977 |
Maximum of Months | 514.00000 | 24.56862 | 48.49438 | 0.68628 | 15.70590 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.80280 | 43.22381 | -0.1958 | 8.21730 |
February | 454.00000 | 22.20479 | 45.60822 | -0.0661 | 8.38280 |
March | 514.00000 | 22.65381 | 44.53824 | 0.04588 | 7.47513 |
April | 485.00000 | 23.63828 | 49.14054 | 0.34348 | 8.43813 |
May | 508.00000 | 24.29543 | 51.67260 | -0.2833 | 7.34172 |
June | 496.00000 | 24.30197 | 50.25523 | -0.2718 | 7.13063 |
July | 497.00000 | 24.40700 | 51.44830 | -0.2315 | 7.19026 |
August | 514.00000 | 24.29439 | 51.75156 | -0.2731 | 7.31773 |
September | 485.00000 | 24.23143 | 53.03377 | -0.3148 | 7.88248 |
October | 502.00000 | 23.96619 | 50.76312 | 0.45743 | 10.59710 |
November | 489.00000 | 22.94252 | 47.33190 | 0.14288 | 7.13140 |
December | 497.00000 | 22.21618 | 45.74224 | -0.0663 | 7.65613 |
Annual Sum or Average | 5943.00000 | 23.42111 | 48.72293 | -0.0603 | 7.89196 |
Minimum of Months | 454.00000 | 21.80280 | 43.22381 | -0.3148 | 7.13063 |
Maximum of Months | 514.00000 | 24.40700 | 53.03377 | 0.45743 | 10.59710 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.08401 | 41.84131 | -0.1049 | 7.80640 |
February | 385.00000 | 22.44827 | 43.91950 | 0.01520 | 7.93053 |
March | 433.00000 | 22.90882 | 42.71361 | 0.13459 | 8.47007 |
April | 410.00000 | 23.78224 | 47.85732 | 0.41327 | 10.04110 |
May | 430.00000 | 24.43250 | 50.47967 | -0.1860 | 7.77597 |
June | 418.00000 | 24.39635 | 49.35009 | -0.1952 | 7.26806 |
July | 422.00000 | 24.53319 | 50.34228 | -0.1464 | 7.70145 |
August | 433.00000 | 24.35162 | 50.90023 | -0.2158 | 7.59952 |
September | 410.00000 | 24.30312 | 51.86832 | -0.2543 | 8.84451 |
October | 427.00000 | 24.05092 | 49.72811 | 0.50553 | 12.31065 |
November | 417.00000 | 23.18579 | 45.62729 | 0.22423 | 7.93494 |
December | 422.00000 | 22.35524 | 44.55647 | -0.0159 | 7.78104 |
Annual Sum or Average | 5034.00000 | 23.57569 | 47.44535 | 0.01397 | 8.45623 |
Minimum of Months | 385.00000 | 22.08401 | 41.84131 | -0.2543 | 7.26806 |
Maximum of Months | 433.00000 | 24.53319 | 51.86832 | 0.50553 | 12.31065 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.42172 | 38.72259 | 0.25727 | 10.12660 |
February | 454.00000 | 23.49069 | 41.77598 | 0.29696 | 10.28343 |
March | 514.00000 | 23.25155 | 42.56813 | 0.21665 | 8.72731 |
April | 485.00000 | 23.82205 | 48.34727 | 0.40126 | 9.33255 |
May | 508.00000 | 24.29767 | 51.63418 | -0.2798 | 7.33016 |
June | 496.00000 | 24.28679 | 50.36563 | -0.2821 | 7.24423 |
July | 497.00000 | 24.40221 | 51.47321 | -0.2340 | 7.22375 |
August | 514.00000 | 24.32621 | 51.47397 | -0.2466 | 7.17211 |
September | 485.00000 | 24.37075 | 52.04635 | -0.2317 | 7.63835 |
October | 502.00000 | 24.42669 | 48.37283 | 0.62522 | 14.85362 |
November | 489.00000 | 24.14644 | 43.24203 | 0.50005 | 12.54615 |
December | 497.00000 | 23.68416 | 41.33599 | 0.35344 | 11.63736 |
Annual Sum or Average | 5943.00000 | 23.99615 | 46.81134 | 0.11215 | 9.49652 |
Minimum of Months | 454.00000 | 23.25155 | 38.72259 | -0.2821 | 7.17211 |
Maximum of Months | 514.00000 | 24.42669 | 52.04635 | 0.62522 | 14.85362 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.29052 | 41.20714 | -0.0429 | 8.01101 |
February | 454.00000 | 22.66048 | 43.62147 | 0.08470 | 8.75819 |
March | 514.00000 | 22.95488 | 42.92291 | 0.16024 | 8.37717 |
April | 485.00000 | 23.90837 | 47.52324 | 0.46404 | 10.93170 |
May | 508.00000 | 24.32382 | 50.70947 | -0.2135 | 7.20486 |
June | 496.00000 | 24.35916 | 49.39009 | -0.1874 | 6.99672 |
July | 497.00000 | 24.47019 | 50.30442 | -0.1528 | 7.13764 |
August | 514.00000 | 24.36536 | 50.50560 | -0.1797 | 6.90474 |
September | 485.00000 | 24.27995 | 51.62166 | -0.2382 | 7.89415 |
October | 502.00000 | 24.10341 | 49.20223 | 0.53733 | 12.56543 |
November | 489.00000 | 23.23334 | 45.64053 | 0.25395 | 8.28829 |
December | 497.00000 | 22.65070 | 43.72645 | 0.07637 | 8.19719 |
Annual Sum or Average | 5943.00000 | 23.63964 | 47.21633 | 0.04560 | 8.42939 |
Minimum of Months | 454.00000 | 22.29052 | 41.20714 | -0.2382 | 6.90474 |
Maximum of Months | 514.00000 | 24.47019 | 51.62166 | 0.53733 | 12.56543 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.44185 | 44.33600 | -0.3074 | 10.24856 |
February | 454.00000 | 21.86354 | 46.63291 | -0.1615 | 9.99836 |
March | 514.00000 | 22.38345 | 45.23796 | -0.0269 | 8.50265 |
April | 485.00000 | 23.49225 | 49.63957 | 0.31455 | 8.56285 |
May | 508.00000 | 24.31539 | 51.87605 | -0.2586 | 7.32309 |
June | 496.00000 | 24.33365 | 50.29106 | -0.2408 | 7.08258 |
July | 497.00000 | 24.44713 | 51.51083 | -0.1976 | 7.26630 |
August | 514.00000 | 24.31052 | 51.96700 | -0.2492 | 7.32508 |
September | 485.00000 | 24.24379 | 53.44901 | -0.2960 | 8.05206 |
October | 502.00000 | 23.87488 | 51.33489 | 0.44323 | 10.99867 |
November | 489.00000 | 22.56485 | 48.41006 | 0.04874 | 7.63388 |
December | 497.00000 | 21.85602 | 47.00892 | -0.1709 | 9.01116 |
Annual Sum or Average | 5943.00000 | 23.27045 | 49.31746 | -0.0922 | 8.48982 |
Minimum of Months | 454.00000 | 21.44185 | 44.33600 | -0.3074 | 7.08258 |
Maximum of Months | 514.00000 | 24.44713 | 53.44901 | 0.44323 | 10.99867 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.75708 | 42.90815 | -0.1975 | 8.96980 |
February | 454.00000 | 22.22772 | 45.07063 | -0.0408 | 9.17715 |
March | 514.00000 | 22.80008 | 43.45360 | 0.10812 | 9.16150 |
April | 485.00000 | 23.71496 | 48.12248 | 0.41414 | 10.25965 |
May | 508.00000 | 24.37834 | 50.54547 | -0.1661 | 7.53795 |
June | 496.00000 | 24.35826 | 49.37233 | -0.1643 | 7.03307 |
July | 497.00000 | 24.48002 | 50.31495 | -0.1217 | 7.53611 |
August | 514.00000 | 24.31087 | 50.93401 | -0.1902 | 7.36341 |
September | 485.00000 | 24.26296 | 52.03146 | -0.2364 | 8.65074 |
October | 502.00000 | 23.95975 | 49.93338 | 0.50148 | 12.58748 |
November | 489.00000 | 22.96935 | 46.68822 | 0.17367 | 7.95061 |
December | 497.00000 | 22.09988 | 45.69442 | -0.0890 | 8.57707 |
Annual Sum or Average | 5943.00000 | 23.45174 | 47.93394 | -0.0013 | 8.72746 |
Minimum of Months | 454.00000 | 21.75708 | 42.90815 | -0.2364 | 7.03307 |
Maximum of Months | 514.00000 | 24.48002 | 52.03146 | 0.50148 | 12.58748 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.02602 | 39.97148 | 0.14098 | 10.37166 |
February | 454.00000 | 23.10724 | 42.87321 | 0.19423 | 10.67402 |
March | 514.00000 | 22.96974 | 43.35200 | 0.14208 | 9.35125 |
April | 485.00000 | 23.67081 | 48.89290 | 0.37144 | 9.38858 |
May | 508.00000 | 24.31546 | 51.84939 | -0.2558 | 7.32655 |
June | 496.00000 | 24.31623 | 50.40812 | -0.2517 | 7.19030 |
July | 497.00000 | 24.44001 | 51.54826 | -0.2009 | 7.30217 |
August | 514.00000 | 24.33531 | 51.71295 | -0.2250 | 7.20513 |
September | 485.00000 | 24.35776 | 52.51204 | -0.2206 | 7.87618 |
October | 502.00000 | 24.30764 | 49.01417 | 0.60465 | 14.77834 |
November | 489.00000 | 23.84107 | 44.18754 | 0.42020 | 11.75544 |
December | 497.00000 | 23.28410 | 42.68995 | 0.24264 | 11.32182 |
Annual Sum or Average | 5943.00000 | 23.83495 | 47.44507 | 0.07815 | 9.53180 |
Minimum of Months | 454.00000 | 22.96974 | 39.97148 | -0.2558 | 7.19030 |
Maximum of Months | 514.00000 | 24.44001 | 52.51204 | 0.60465 | 14.77834 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.95982 | 42.17090 | -0.1404 | 9.08874 |
February | 454.00000 | 22.33134 | 44.57858 | -0.0024 | 9.65400 |
March | 514.00000 | 22.67487 | 43.64324 | 0.08963 | 8.97343 |
April | 485.00000 | 23.71349 | 48.11463 | 0.42603 | 10.79966 |
May | 508.00000 | 24.29711 | 50.97407 | -0.2042 | 7.39212 |
June | 496.00000 | 24.34519 | 49.50761 | -0.1719 | 7.14892 |
July | 497.00000 | 24.46152 | 50.45475 | -0.1357 | 7.34173 |
August | 514.00000 | 24.34442 | 50.76593 | -0.1687 | 7.06944 |
September | 485.00000 | 24.22680 | 52.10963 | -0.2398 | 8.32654 |
October | 502.00000 | 23.97503 | 49.79659 | 0.51540 | 12.63443 |
November | 489.00000 | 22.88852 | 46.59611 | 0.17019 | 8.30041 |
December | 497.00000 | 22.31437 | 44.84976 | -0.0166 | 8.78951 |
Annual Sum or Average | 5943.00000 | 23.46877 | 47.81152 | 0.00932 | 8.78132 |
Minimum of Months | 454.00000 | 21.95982 | 42.17090 | -0.2398 | 7.06944 |
Maximum of Months | 514.00000 | 24.46152 | 52.10963 | 0.51540 | 12.63443 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.792238E+11 | 214721.56 | 19-JAN-17:00 | 284.60 | 0.476010E+12 | 0.00 | 0.555233E+12 | 1.89 | 7.42 | 19-JAN-06:05 | 0.00 | 0.00 |
February | 0.105694E+12 | 213580.98 | 28-FEB-16:30 | 330.74 | 0.667624E+12 | 0.00 | 0.773319E+12 | 2.67 | 7.53 | 27-FEB-06:03 | 0.00 | 0.00 |
March | 0.125460E+12 | 217252.14 | 30-MAR-12:10 | 408.70 | 0.783467E+12 | 0.00 | 0.908927E+12 | 2.90 | 7.53 | 27-MAR-05:03 | 0.00 | 0.00 |
April | 0.183729E+12 | 219395.64 | 27-APR-11:20 | 515.39 | 0.122595E+13 | 0.00 | 0.140968E+13 | 4.15 | 7.49 | 22-APR-04:13 | 0.00 | 0.00 |
May | 0.251213E+12 | 232627.11 | 26-MAY-11:30 | 545.74 | 0.168069E+13 | 0.00 | 0.193190E+13 | 4.58 | 7.53 | 12-MAY-04:12 | 0.00 | 0.00 |
June | 0.252539E+12 | 236362.18 | 19-JUN-07:50 | 578.77 | 0.165936E+13 | 0.00 | 0.191190E+13 | 4.82 | 7.53 | 07-JUN-04:13 | 0.00 | 0.00 |
July | 0.261975E+12 | 239348.33 | 22-JUL-11:20 | 637.04 | 0.167523E+13 | 0.00 | 0.193721E+13 | 4.86 | 7.33 | 12-JUL-04:12 | 0.00 | 0.00 |
August | 0.267812E+12 | 240954.51 | 09-AUG-18:30 | 655.77 | 0.173190E+13 | 0.00 | 0.199972E+13 | 5.01 | 7.46 | 17-AUG-04:13 | 0.00 | 0.00 |
September | 0.246793E+12 | 232821.36 | 18-SEP-11:10 | 533.19 | 0.163857E+13 | 0.00 | 0.188536E+13 | 4.59 | 7.53 | 23-SEP-04:12 | 0.00 | 0.00 |
October | 0.217464E+12 | 235542.49 | 24-OCT-16:10 | 539.78 | 0.141943E+13 | 0.00 | 0.163689E+13 | 4.25 | 7.53 | 03-OCT-04:13 | 0.00 | 0.00 |
November | 0.145487E+12 | 227611.25 | 01-NOV-13:30 | 448.76 | 0.904981E+12 | 0.00 | 0.105047E+13 | 3.37 | 7.54 | 08-NOV-05:13 | 0.00 | 0.00 |
December | 0.106792E+12 | 223201.73 | 15-DEC-12:40 | 363.83 | 0.661433E+12 | 0.00 | 0.768225E+12 | 2.48 | 7.52 | 11-DEC-06:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.224418E+13 | 5842.31 | 0.145246E+14 | 0.167688E+14 | 3.80 | |||||||
Minimum of Months | 0.792238E+11 | 213580.98 | 284.60 | 0.476010E+12 | 0.00 | 0.555233E+12 | 1.89 | 7.33 | 0.00 | 0.00 | ||
Maximum of Months | 0.267812E+12 | 240954.51 | 655.77 | 0.173190E+13 | 0.00 | 0.199972E+13 | 5.01 | 7.54 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.145443E+10 | 130531.29 | 19-JAN-10:40 | 3.50 | 0.992311E+10 | 0.00 | 0.113775E+11 | 0.03 | 7.07 | 18-JAN-17:00 | 0.00 | 0.00 |
February | 0.151761E+10 | 131264.84 | 24-FEB-11:30 | 3.67 | 0.104113E+11 | 0.00 | 0.119289E+11 | 0.04 | 7.12 | 23-FEB-16:40 | 0.00 | 0.00 |
March | 0.564370E+10 | 130585.41 | 07-MAR-15:10 | 13.50 | 0.383482E+11 | 0.00 | 0.439919E+11 | 0.12 | 7.12 | 17-MAR-15:50 | 0.00 | 0.00 |
April | 0.824344E+10 | 145280.73 | 28-APR-07:20 | 19.50 | 0.550692E+11 | 0.00 | 0.633126E+11 | 0.18 | 7.04 | 06-APR-14:20 | 0.00 | 0.00 |
May | 0.462728E+11 | 223203.83 | 24-MAY-05:03 | 105.78 | 0.304856E+12 | 0.00 | 0.351128E+12 | 0.93 | 7.31 | 09-MAY-05:01 | 0.00 | 0.00 |
June | 0.590007E+11 | 182885.91 | 24-JUN-05:04 | 131.22 | 0.384272E+12 | 0.00 | 0.443272E+12 | 1.18 | 7.10 | 24-JUN-05:04 | 0.00 | 0.00 |
July | 0.727162E+11 | 173073.87 | 01-JUL-05:04 | 158.07 | 0.468560E+12 | 0.00 | 0.541276E+12 | 1.36 | 7.06 | 12-JUL-15:10 | 0.00 | 0.00 |
August | 0.787530E+11 | 184918.17 | 15-AUG-05:04 | 173.60 | 0.511139E+12 | 0.00 | 0.589892E+12 | 1.51 | 7.13 | 12-AUG-05:05 | 0.00 | 0.00 |
September | 0.566510E+11 | 190170.04 | 06-SEP-05:04 | 127.75 | 0.371897E+12 | 0.00 | 0.428548E+12 | 1.16 | 7.20 | 06-SEP-05:04 | 0.00 | 0.00 |
October | 0.466352E+11 | 164567.29 | 24-OCT-05:05 | 103.72 | 0.305229E+12 | 0.00 | 0.351864E+12 | 0.91 | 7.14 | 10-OCT-05:06 | 0.00 | 0.00 |
November | 0.137274E+11 | 136340.20 | 07-NOV-13:10 | 31.32 | 0.909370E+11 | 0.00 | 0.104664E+12 | 0.29 | 7.12 | 29-NOV-06:06 | 0.00 | 0.00 |
December | 0.727993E+10 | 147180.46 | 11-DEC-14:50 | 17.33 | 0.482683E+11 | 0.00 | 0.555482E+11 | 0.15 | 6.94 | 13-DEC-09:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.397895E+12 | 888.95 | 0.259891E+13 | 0.299680E+13 | 0.66 | |||||||
Minimum of Months | 0.145443E+10 | 130531.29 | 3.50 | 0.992311E+10 | 0.00 | 0.113775E+11 | 0.03 | 6.94 | 0.00 | 0.00 | ||
Maximum of Months | 0.787530E+11 | 223203.83 | 173.60 | 0.511139E+12 | 0.00 | 0.589892E+12 | 1.51 | 7.31 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.653005E+11 | 744.00 | 49248.27 | 01-JAN-00:05 | 262365.38 | 09-JAN-17:10 | 22.97 | 19.51 | 14.01 |
February | 0.901998E+11 | 672.00 | 49248.27 | 01-FEB-00:10 | 363906.13 | 17-FEB-08:17 | 26.88 | 20.60 | 14.03 |
March | 0.115352E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 513986.92 | 26-MAR-14:12 | 31.45 | 22.30 | 14.03 |
April | 0.127188E+12 | 720.00 | 49248.27 | 01-APR-00:10 | 672918.83 | 28-APR-17:20 | 38.81 | 26.52 | 14.04 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 403141.65 | 01-MAY-00:03 | 32.49 | 28.56 | 14.04 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 381093.13 | 29-JUN-14:20 | 37.42 | 30.54 | 14.04 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 540914.40 | 21-JUL-16:10 | 42.08 | 32.19 | 14.04 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 691654.46 | 06-AUG-15:11 | 45.83 | 32.99 | 14.04 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:10 | 279876.14 | 01-SEP-00:10 | 31.85 | 27.90 | 14.04 |
October | 0.129577E+12 | 744.00 | 49248.27 | 01-OCT-00:10 | 373523.81 | 05-OCT-15:20 | 33.94 | 27.21 | 14.04 |
November | 0.119768E+12 | 720.00 | 49248.27 | 01-NOV-00:10 | 510785.43 | 01-NOV-14:20 | 32.71 | 23.45 | 14.04 |
December | 0.115445E+12 | 744.00 | 49248.27 | 01-DEC-00:10 | 656648.77 | 13-DEC-17:10 | 34.30 | 22.38 | 14.03 |
Annual Sum or Average | 0.141385E+13 | 8760.00 | 34.28 | 26.22 | 14.03 | ||||
Minimum of Months | 0.653005E+11 | 672.00 | 49248.27 | 262365.38 | 22.97 | 19.51 | 14.01 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 691654.46 | 45.83 | 32.99 | 14.04 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.642501E+10 | 212.54 | 22420.35 | 01-JAN-12:52 | 1370396.90 | 20-JAN-04:02 | 22.19 | 21.44 | 20.99 |
February | 0.902487E+10 | 280.01 | 22420.35 | 01-FEB-11:55 | 1306944.00 | 01-FEB-04:01 | 22.85 | 21.70 | 27.55 |
March | 0.119159E+11 | 341.13 | 22420.35 | 06-MAR-08:65 | 1387013.75 | 24-MAR-16:00 | 22.89 | 21.67 | 30.26 |
April | 0.226749E+11 | 473.17 | 22420.35 | 01-APR-03:01 | 1476249.48 | 18-APR-14:00 | 23.99 | 22.07 | 39.72 |
May | 0.438377E+11 | 545.74 | 22420.35 | 01-MAY-00:53 | 1132126.36 | 26-MAY-15:20 | 27.51 | 25.10 | 36.32 |
June | 0.460517E+11 | 578.77 | 22420.35 | 01-JUN-03:01 | 1168514.66 | 07-JUN-03:03 | 27.55 | 25.06 | 41.16 |
July | 0.514179E+11 | 637.04 | 22420.35 | 01-JUL-00:42 | 1153751.24 | 31-JUL-11:00 | 28.33 | 25.90 | 43.53 |
August | 0.523028E+11 | 655.77 | 22420.35 | 01-AUG-00:23 | 1145723.04 | 07-AUG-14:40 | 27.83 | 25.30 | 46.11 |
September | 0.429683E+11 | 533.19 | 22420.35 | 01-SEP-00:10 | 1155631.13 | 29-SEP-16:00 | 28.16 | 25.74 | 36.25 |
October | 0.338990E+11 | 525.53 | 22420.35 | 02-OCT-08:40 | 1343238.84 | 26-OCT-15:10 | 26.11 | 23.99 | 39.51 |
November | 0.149869E+11 | 400.59 | 22420.35 | 01-NOV-03:01 | 1252795.44 | 08-NOV-11:10 | 23.63 | 22.16 | 35.91 |
December | 0.110798E+11 | 289.85 | 22420.35 | 08-DEC-10:40 | 1197036.12 | 08-DEC-12:00 | 22.69 | 21.67 | 26.40 |
Annual Sum or Average | 0.346585E+12 | 5473.33 | 25.33 | 23.50 | 35.34 | ||||
Minimum of Months | 0.642501E+10 | 212.54 | 22420.35 | 1132126.36 | 22.19 | 21.44 | 20.99 | ||
Maximum of Months | 0.523028E+11 | 655.77 | 22420.35 | 1476249.48 | 28.33 | 25.90 | 46.11 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.300791E+10 | 37.27 | 22420.35 | 02-JAN-10:50 | 1019574.11 | 19-JAN-16:30 | 22.19 | 21.97 | 2.06 |
February | 0.458720E+10 | 56.83 | 22420.35 | 01-FEB-13:20 | 1019835.05 | 24-FEB-11:30 | 22.85 | 22.46 | 3.38 |
March | 0.654114E+10 | 81.04 | 22420.35 | 06-MAR-09:10 | 1025683.80 | 07-MAR-15:10 | 22.89 | 22.43 | 4.66 |
April | 0.118975E+11 | 147.41 | 22420.35 | 01-APR-06:20 | 1036185.76 | 28-APR-08:00 | 23.99 | 23.12 | 8.53 |
May | 0.333756E+11 | 413.51 | 22420.35 | 01-MAY-03:22 | 1132126.36 | 26-MAY-15:20 | 27.51 | 25.37 | 24.99 |
June | 0.339731E+11 | 420.91 | 22420.35 | 01-JUN-03:01 | 1050034.10 | 28-JUN-15:10 | 27.55 | 25.34 | 27.18 |
July | 0.391239E+11 | 484.73 | 22420.35 | 01-JUL-03:09 | 1153751.24 | 31-JUL-11:00 | 28.33 | 26.02 | 30.47 |
August | 0.379998E+11 | 470.80 | 22420.35 | 01-AUG-04:05 | 1145723.04 | 07-AUG-14:40 | 27.83 | 25.49 | 30.26 |
September | 0.356439E+11 | 441.61 | 22420.35 | 01-SEP-03:25 | 1155631.13 | 29-SEP-16:00 | 28.16 | 25.91 | 28.14 |
October | 0.238429E+11 | 295.43 | 22420.35 | 02-OCT-09:30 | 1127465.28 | 06-OCT-14:10 | 26.11 | 24.58 | 18.83 |
November | 0.802411E+10 | 99.42 | 22420.35 | 01-NOV-05:06 | 1024709.95 | 03-NOV-08:50 | 23.63 | 23.07 | 6.42 |
December | 0.662521E+10 | 82.08 | 22420.35 | 08-DEC-11:10 | 1088336.22 | 12-DEC-16:40 | 22.69 | 22.23 | 4.83 |
Annual Sum or Average | 0.244642E+12 | 3031.03 | 25.33 | 24.01 | 15.89 | ||||
Minimum of Months | 0.300791E+10 | 37.27 | 22420.35 | 1019574.11 | 22.19 | 21.97 | 2.06 | ||
Maximum of Months | 0.391239E+11 | 484.73 | 22420.35 | 1155631.13 | 28.33 | 26.02 | 30.47 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.384668E+11 | 0.00 | 216.96 | 1539938.23 | 09-JAN-06:01 | 0.00 | 53.72 | 62.75 | 0.13 | 0.00 | 0.01 | 1.20 | 09-JAN-06:01 |
February | 0.203034E+11 | 0.00 | 127.66 | 1344478.96 | 18-FEB-06:02 | 0.00 | 55.55 | 61.52 | 0.08 | 0.00 | 0.01 | 1.05 | 18-FEB-06:02 |
March | 0.178686E+11 | 0.00 | 108.75 | 1447843.81 | 11-MAR-06:02 | 0.00 | 56.50 | 60.71 | 0.06 | 0.00 | 0.01 | 1.13 | 11-MAR-06:02 |
April | 0.966409E+09 | 0.00 | 13.71 | 415528.47 | 16-APR-21:10 | 0.00 | 68.58 | 68.85 | 0.01 | 0.00 | 0.00 | 0.32 | 16-APR-21:10 |
May | 0.883148E+09 | 0.00 | 1.05 | 248039.09 | 01-MAY-00:10 | 0.00 | 72.59 | 72.60 | 0.01 | 0.00 | 0.00 | 0.19 | 01-MAY-00:10 |
June | 0.734740E+09 | 0.00 | 0.88 | 232569.33 | 04-JUN-14:56 | 0.00 | 72.78 | 72.79 | 0.01 | 0.00 | 0.00 | 0.18 | 04-JUN-14:56 |
July | 0.113231E+10 | 0.00 | 1.36 | 231776.65 | 09-JUL-20:47 | 0.00 | 72.81 | 72.82 | 0.01 | 0.00 | 0.00 | 0.18 | 09-JUL-20:47 |
August | 0.779476E+09 | 0.00 | 1.10 | 232702.29 | 27-AUG-21:00 | 0.00 | 72.81 | 72.82 | 0.01 | 0.00 | 0.00 | 0.18 | 27-AUG-21:00 |
September | 0.119635E+10 | 0.00 | 1.43 | 233460.84 | 24-SEP-22:20 | 0.00 | 72.74 | 72.76 | 0.01 | 0.00 | 0.00 | 0.18 | 24-SEP-22:20 |
October | 0.159262E+10 | 0.00 | 12.27 | 490037.04 | 29-OCT-13:58 | 0.00 | 71.99 | 72.23 | 0.01 | 0.00 | 0.00 | 0.38 | 29-OCT-13:58 |
November | 0.420913E+10 | 0.00 | 55.32 | 797899.72 | 19-NOV-10:30 | 0.00 | 64.80 | 66.61 | 0.02 | 0.00 | 0.00 | 0.62 | 19-NOV-10:30 |
December | 0.280476E+11 | 0.00 | 172.55 | 1539938.23 | 20-DEC-05:11 | 0.00 | 56.27 | 63.35 | 0.10 | 0.00 | 0.01 | 1.20 | 20-DEC-05:11 |
Annual Sum or Average | 0.116181E+12 | 713.06 | 65.97 | 68.35 | 0.04 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.734740E+09 | 0.00 | 0.88 | 231776.65 | 0.00 | 53.72 | 60.71 | 0.01 | 0.00 | 0.00 | 0.18 | ||
Maximum of Months | 0.384668E+11 | 0.00 | 216.96 | 1539938.23 | 0.00 | 72.81 | 72.82 | 0.13 | 0.00 | 0.01 | 1.20 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 22.97 | 22.97 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 26.88 | 26.88 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 31.45 | 31.45 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 38.81 | 38.81 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 32.49 | 32.49 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 37.42 | 37.42 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 42.08 | 42.08 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 45.83 | 45.83 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 31.85 | 31.85 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 33.94 | 33.94 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 32.71 | 32.71 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 34.30 | 34.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 34.28 | 34.28 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.97 | 22.97 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 45.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.234629E+11 | 0.00 | 152.41 | 0.181295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153544.06 | 01-JAN-16:51 | 114499.52 | 01-JAN-16:51 | 0.00 | 0.00 | 0.00 |
February | 0.284499E+11 | 0.00 | 197.40 | 0.227837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165478.04 | 26-FEB-16:10 | 125310.33 | 20-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.395541E+11 | 0.00 | 252.26 | 0.338863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176346.40 | 07-MAR-04:01 | 123802.99 | 05-MAR-23:20 | 0.00 | 0.00 | 0.00 |
April | 0.614734E+11 | 0.00 | 361.99 | 0.539286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180448.83 | 28-APR-03:01 | 121990.26 | 23-APR-22:40 | 0.00 | 0.00 | 0.00 |
May | 0.112542E+12 | 0.00 | 470.48 | 0.893279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207432.68 | 21-MAY-16:47 | 126642.98 | 29-MAY-21:00 | 0.00 | 0.00 | 0.00 |
June | 0.117088E+12 | 0.00 | 458.44 | 0.903051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206336.76 | 18-JUN-15:18 | 122905.29 | 18-JUN-21:20 | 0.00 | 0.00 | 0.00 |
July | 0.125999E+12 | 0.00 | 469.12 | 0.922066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 211997.68 | 02-JUL-14:10 | 124083.84 | 09-JUL-20:50 | 0.00 | 0.00 | 0.00 |
August | 0.137052E+12 | 0.00 | 499.64 | 0.102466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 207763.50 | 06-AUG-07:57 | 122967.97 | 27-AUG-19:40 | 0.00 | 0.00 | 0.00 |
September | 0.119202E+12 | 0.00 | 469.46 | 0.897627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 204113.34 | 17-SEP-09:00 | 124934.39 | 24-SEP-22:22 | 0.00 | 0.00 | 0.00 |
October | 0.103346E+12 | 0.00 | 447.96 | 0.817848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 199871.15 | 08-OCT-07:51 | 126343.54 | 22-OCT-21:10 | 0.00 | 0.00 | 0.00 |
November | 0.577016E+11 | 0.00 | 323.45 | 0.484264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182388.66 | 11-NOV-10:11 | 119604.25 | 05-NOV-12:48 | 0.00 | 0.00 | 0.00 |
December | 0.384024E+11 | 0.00 | 225.08 | 0.319913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 175581.52 | 15-DEC-05:11 | 131591.74 | 31-DEC-18:53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.964274E+12 | 4327.69 | 0.754999E+12 | ||||||||||||
Minimum of Months | 0.234629E+11 | 0.00 | 152.41 | 0.181295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153544.06 | 114499.52 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.137052E+12 | 0.00 | 499.64 | 0.102466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 211997.68 | 131591.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.450995E+11 | 0.00 | 270.57 | 0.324025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142157.48 | 31-JAN-05:12 | 119169.35 | 31-JAN-05:11 | 0.00 | 0.00 | 0.00 |
February | 0.634073E+11 | 0.00 | 319.84 | 0.439974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153720.36 | 03-FEB-04:01 | 130162.17 | 28-FEB-05:11 | 0.00 | 0.00 | 0.00 |
March | 0.787557E+11 | 0.00 | 397.49 | 0.591429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163642.80 | 27-MAR-04:11 | 149161.45 | 27-MAR-04:11 | 0.00 | 0.00 | 0.00 |
April | 0.125623E+12 | 0.00 | 503.72 | 0.955073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159430.49 | 24-APR-11:00 | 135852.03 | 28-APR-04:11 | 0.00 | 0.00 | 0.00 |
May | 0.164748E+12 | 0.00 | 500.44 | 0.120238E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 212799.67 | 23-MAY-03:01 | 151907.80 | 31-MAY-03:01 | 0.00 | 0.00 | 0.00 |
June | 0.176548E+12 | 0.00 | 546.96 | 0.132398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 178735.26 | 08-JUN-04:11 | 149570.60 | 05-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.191522E+12 | 0.00 | 597.81 | 0.140815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 194064.67 | 26-JUL-05:02 | 159045.57 | 11-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.207654E+12 | 0.00 | 628.74 | 0.154276E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 190380.97 | 08-AUG-05:02 | 158104.48 | 08-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.167214E+12 | 0.00 | 489.09 | 0.112855E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 229352.57 | 05-SEP-03:02 | 155148.14 | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.152029E+12 | 0.00 | 504.99 | 0.113321E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 209969.85 | 13-OCT-04:02 | 162918.67 | 13-OCT-04:02 | 0.00 | 0.00 | 0.00 |
November | 0.956431E+11 | 0.00 | 429.43 | 0.738582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176098.29 | 01-NOV-04:11 | 149125.88 | 03-NOV-04:11 | 0.00 | 0.00 | 0.00 |
December | 0.706727E+11 | 0.00 | 340.44 | 0.527899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160788.39 | 15-DEC-06:02 | 145867.95 | 11-DEC-05:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153892E+13 | 5529.54 | 0.113160E+13 | ||||||||||||
Minimum of Months | 0.450995E+11 | 0.00 | 270.57 | 0.324025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142157.48 | 119169.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.207654E+12 | 0.00 | 628.74 | 0.154276E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 229352.57 | 162918.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.356664E+12 | 0.00 | 260.78 | 0.245289E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1225284.84 | 19-JAN-06:03 | 948862.18 | 19-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.503432E+12 | 0.00 | 301.65 | 0.331853E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1326345.22 | 27-FEB-06:02 | 1216387.56 | 27-FEB-06:01 | 0.00 | 0.00 | 0.00 |
March | 0.600063E+12 | 0.00 | 361.36 | 0.425378E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1676226.98 | 27-MAR-05:02 | 1289569.49 | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 |
April | 0.938140E+12 | 0.00 | 409.25 | 0.660507E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1714941.47 | 29-APR-04:11 | 1344885.31 | 29-APR-04:11 | 0.00 | 0.00 | 0.00 |
May | 0.148979E+13 | 0.00 | 469.50 | 0.104054E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2416038.87 | 22-MAY-03:02 | 1469170.15 | 09-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.152111E+13 | 0.00 | 473.10 | 0.107698E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1993644.94 | 10-JUN-05:02 | 1460773.78 | 28-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.158918E+13 | 0.00 | 482.69 | 0.106850E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1952866.27 | 25-JUL-04:03 | 1444520.63 | 28-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.164942E+13 | 0.00 | 487.75 | 0.110960E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2231522.10 | 16-AUG-04:11 | 1450955.93 | 24-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.149734E+13 | 0.00 | 456.77 | 0.949184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2452091.72 | 05-SEP-04:11 | 1430436.80 | 02-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.127741E+13 | 0.00 | 443.82 | 0.893342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2097272.41 | 21-OCT-04:11 | 1383145.32 | 24-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.737943E+12 | 0.00 | 389.30 | 0.541630E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1603597.28 | 08-NOV-05:12 | 1339126.49 | 03-NOV-04:11 | 0.00 | 0.00 | 0.00 |
December | 0.522920E+12 | 0.00 | 299.41 | 0.358669E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1586007.44 | 11-DEC-06:02 | 1206412.25 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126834E+14 | 4835.40 | 0.870148E+13 | ||||||||||||
Minimum of Months | 0.356664E+12 | 0.00 | 260.78 | 0.245289E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1225284.84 | 948862.18 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.164942E+13 | 0.00 | 487.75 | 0.110960E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2452091.72 | 1469170.15 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.361328E+11 | 0.00 | 251.61 | 0.241018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141847.18 | 19-JAN-15:00 | 89334.83 | 19-JAN-15:50 | 0.00 | 0.00 | 0.00 |
February | 0.515349E+11 | 0.00 | 293.15 | 0.335145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140790.51 | 24-FEB-16:00 | 93758.32 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.625148E+11 | 0.00 | 357.69 | 0.437949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 171069.13 | 27-MAR-05:01 | 128645.69 | 27-MAR-05:01 | 0.00 | 0.00 | 0.00 |
April | 0.989662E+11 | 0.00 | 402.26 | 0.705300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 166446.38 | 29-APR-04:11 | 125942.29 | 29-APR-04:11 | 0.00 | 0.00 | 0.00 |
May | 0.162768E+12 | 0.00 | 473.03 | 0.116608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 258447.25 | 22-MAY-03:02 | 148629.58 | 26-MAY-03:01 | 0.00 | 0.00 | 0.00 |
June | 0.168205E+12 | 0.00 | 476.89 | 0.122574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 202943.05 | 05-JUN-03:02 | 151133.12 | 29-JUN-03:01 | 0.00 | 0.00 | 0.00 |
July | 0.175074E+12 | 0.00 | 488.99 | 0.120838E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 239477.14 | 31-JUL-03:01 | 150412.90 | 07-JUL-03:01 | 0.00 | 0.00 | 0.00 |
August | 0.179868E+12 | 0.00 | 492.40 | 0.124230E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 231211.80 | 16-AUG-04:11 | 150876.72 | 23-AUG-03:01 | 0.00 | 0.00 | 0.00 |
September | 0.159507E+12 | 0.00 | 458.44 | 0.103199E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 265812.50 | 05-SEP-04:11 | 145330.86 | 07-SEP-03:01 | 0.00 | 0.00 | 0.00 |
October | 0.135147E+12 | 0.00 | 442.04 | 0.960374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 213891.78 | 14-OCT-05:02 | 148639.26 | 06-OCT-03:01 | 0.00 | 0.00 | 0.00 |
November | 0.733722E+11 | 0.00 | 383.69 | 0.536459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182520.58 | 01-NOV-05:02 | 128607.18 | 01-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.517422E+11 | 0.00 | 295.62 | 0.351332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165635.39 | 11-DEC-06:01 | 119851.01 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135483E+13 | 4815.83 | 0.944206E+12 | ||||||||||||
Minimum of Months | 0.361328E+11 | 0.00 | 251.61 | 0.241018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140790.51 | 89334.83 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.179868E+12 | 0.00 | 492.40 | 0.124230E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 265812.50 | 151133.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.316839E+12 | 0.823893E+11 | 744.00 | 0.314939E+12 | 0.189975E+10 | 0.00 | 0.35 | 19-JAN-12:00 | 0.30 | 03-JAN-07:20 | 127581.15 | 31-JAN-16:40 | 121829.85 | 02-JAN-15:00 | 7759.60 | 19-JAN-22:00 | 41565.22 | 02-JAN-15:00 | 0.00 |
February | 0.500132E+12 | 0.127302E+12 | 672.00 | 0.496529E+12 | 0.360214E+10 | 0.00 | 0.58 | 02-FEB-13:10 | 0.51 | 13-FEB-07:20 | 215083.62 | 24-FEB-17:00 | 208540.57 | 24-FEB-13:00 | 7555.70 | 02-FEB-21:00 | 72406.47 | 02-FEB-13:00 | 0.00 |
March | 0.788936E+12 | 0.203934E+12 | 744.00 | 0.785295E+12 | 0.364183E+10 | 0.00 | 0.81 | 05-MAR-14:00 | 0.71 | 03-MAR-07:05 | 303935.16 | 30-MAR-14:10 | 296832.84 | 30-MAR-13:00 | 9331.31 | 30-MAR-18:50 | 105904.54 | 26-MAR-14:00 | 0.00 |
April | 0.994431E+12 | 0.278664E+12 | 720.00 | 0.989738E+12 | 0.469239E+10 | 0.00 | 1.00 | 14-APR-13:30 | 0.89 | 10-APR-06:20 | 402062.68 | 28-APR-17:40 | 387115.39 | 18-APR-16:50 | 16165.98 | 28-APR-17:50 | 144243.92 | 28-APR-15:00 | 0.00 |
May | 0.331388E+12 | 0.110566E+12 | 744.00 | 0.321387E+12 | 0.100004E+11 | 0.00 | 0.39 | 01-MAY-15:30 | 0.33 | 07-MAY-01:00 | 134672.10 | 01-MAY-16:00 | 132711.36 | 01-MAY-00:10 | 12200.81 | 23-MAY-16:00 | 51002.24 | 01-MAY-15:10 | 0.00 |
June | 0.549217E+12 | 0.184002E+12 | 720.00 | 0.538045E+12 | 0.111721E+11 | 0.00 | 0.62 | 28-JUN-14:10 | 0.54 | 01-JUN-05:00 | 223543.96 | 29-JUN-15:00 | 211414.62 | 14-JUN-14:00 | 15036.55 | 29-JUN-15:00 | 87802.10 | 14-JUN-14:00 | 0.00 |
July | 0.804575E+12 | 0.270468E+12 | 744.00 | 0.792175E+12 | 0.123994E+11 | 0.00 | 0.86 | 21-JUL-16:00 | 0.75 | 01-JUL-00:03 | 311176.14 | 12-JUL-12:30 | 300415.27 | 21-JUL-16:00 | 14101.32 | 12-JUL-12:40 | 127010.32 | 21-JUL-16:00 | 0.00 |
August | 0.103780E+13 | 0.341884E+12 | 744.00 | 0.102639E+13 | 0.114031E+11 | 0.00 | 1.00 | 01-AUG-08:30 | 0.94 | 16-AUG-23:00 | 404848.78 | 07-AUG-13:50 | 390631.65 | 06-AUG-15:34 | 17022.80 | 07-AUG-14:00 | 151604.69 | 30-AUG-16:00 | 0.00 |
September | 0.324792E+12 | 0.106127E+12 | 720.00 | 0.313844E+12 | 0.109486E+11 | 0.00 | 0.39 | 01-SEP-12:10 | 0.33 | 22-SEP-06:10 | 137807.16 | 01-SEP-00:10 | 136295.64 | 01-SEP-00:10 | 11836.89 | 05-SEP-13:00 | 56067.59 | 09-SEP-17:00 | 0.00 |
October | 0.566541E+12 | 0.174186E+12 | 744.00 | 0.558070E+12 | 0.847099E+10 | 0.00 | 0.62 | 06-OCT-11:20 | 0.52 | 17-OCT-06:50 | 224430.08 | 24-OCT-14:20 | 212618.88 | 05-OCT-15:00 | 14025.31 | 24-OCT-20:00 | 86379.94 | 05-OCT-15:00 | 0.00 |
November | 0.769678E+12 | 0.204655E+12 | 720.00 | 0.765750E+12 | 0.392884E+10 | 0.00 | 0.82 | 02-NOV-13:10 | 0.71 | 22-NOV-07:10 | 308225.63 | 03-NOV-17:00 | 298555.53 | 06-NOV-16:00 | 11366.04 | 03-NOV-17:30 | 108366.28 | 02-NOV-13:00 | 0.00 |
December | 0.102763E+13 | 0.256728E+12 | 744.00 | 0.102496E+13 | 0.267176E+10 | 0.00 | 1.00 | 10-DEC-14:41 | 0.89 | 18-DEC-07:20 | 395087.45 | 12-DEC-15:00 | 386812.18 | 13-DEC-17:00 | 9844.70 | 12-DEC-15:00 | 135628.81 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.801195E+13 | 0.234091E+13 | 8760.00 | 0.792712E+13 | 0.848313E+11 | ||||||||||||||
Minimum of Months | 0.316839E+12 | 0.823893E+11 | 672.00 | 0.313844E+12 | 0.189975E+10 | 0.00 | 0.35 | 0.30 | 127581.15 | 121829.85 | 7555.70 | 41565.22 | 0.00 | ||||||
Maximum of Months | 0.103780E+13 | 0.341884E+12 | 744.00 | 0.102639E+13 | 0.123994E+11 | 0.00 | 1.00 | 0.94 | 404848.78 | 390631.65 | 17022.80 | 151604.69 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.489459E+10 | 0.125696E+10 | 744.00 | 0.489441E+10 | 180804.34 | 0.00 | 0.32 | 01-JAN-17:03 | 0.17 | 10-JAN-08:00 | 2470.84 | 01-JAN-17:15 | 2470.84 | 01-JAN-17:15 | 3.48 | 02-JAN-02:13 | 744.05 | 01-JAN-16:51 | 0.00 |
February | 0.907001E+10 | 0.227384E+10 | 672.00 | 0.906991E+10 | 105604.41 | 0.00 | 0.56 | 26-FEB-17:42 | 0.38 | 05-FEB-08:10 | 4500.81 | 26-FEB-17:54 | 4500.81 | 26-FEB-17:54 | 4.87 | 04-FEB-22:00 | 1339.30 | 02-FEB-13:00 | 0.00 |
March | 0.150642E+11 | 0.382303E+10 | 744.00 | 0.150642E+11 | 0.00 | 0.00 | 0.75 | 26-MAR-14:00 | 0.59 | 11-MAR-18:20 | 6056.46 | 05-MAR-17:45 | 6056.46 | 05-MAR-17:45 | 0.00 | 01-MAR-00:10 | 2059.96 | 26-MAR-14:00 | 0.00 |
April | 0.194710E+11 | 0.541044E+10 | 720.00 | 0.194710E+11 | 0.00 | 0.00 | 0.99 | 28-APR-15:30 | 0.81 | 11-APR-07:00 | 8189.92 | 16-APR-18:20 | 8189.92 | 16-APR-18:20 | 0.00 | 01-APR-00:10 | 2979.81 | 28-APR-15:00 | 0.00 |
May | 0.566975E+10 | 0.190779E+10 | 744.00 | 0.566975E+10 | 0.00 | 0.00 | 0.35 | 29-MAY-17:45 | 0.26 | 22-MAY-21:20 | 2512.23 | 29-MAY-18:13 | 2512.23 | 29-MAY-18:13 | 0.00 | 01-MAY-00:03 | 952.91 | 28-MAY-16:02 | 0.00 |
June | 0.101613E+11 | 0.341967E+10 | 720.00 | 0.101613E+11 | 0.00 | 0.00 | 0.58 | 11-JUN-17:51 | 0.47 | 01-JUN-06:00 | 4305.48 | 11-JUN-18:25 | 4305.48 | 11-JUN-18:25 | 0.00 | 01-JUN-00:10 | 1648.99 | 14-JUN-14:00 | 0.00 |
July | 0.153396E+11 | 0.517642E+10 | 744.00 | 0.153396E+11 | 0.00 | 0.00 | 0.80 | 21-JUL-16:00 | 0.69 | 11-JUL-21:03 | 6039.55 | 23-JUL-18:54 | 6039.55 | 23-JUL-18:54 | 0.00 | 01-JUL-00:03 | 2486.44 | 21-JUL-16:00 | 0.00 |
August | 0.202291E+11 | 0.672425E+10 | 744.00 | 0.202291E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-15:20 | 0.87 | 16-AUG-21:10 | 7880.84 | 06-AUG-17:47 | 7880.84 | 06-AUG-17:47 | 0.00 | 01-AUG-00:05 | 3151.00 | 30-AUG-16:00 | 0.00 |
September | 0.549780E+10 | 0.181431E+10 | 720.00 | 0.549780E+10 | 0.00 | 0.00 | 0.36 | 03-SEP-17:55 | 0.25 | 07-SEP-21:13 | 2594.86 | 03-SEP-17:55 | 2594.86 | 03-SEP-17:55 | 0.00 | 01-SEP-00:10 | 1002.12 | 09-SEP-17:55 | 0.00 |
October | 0.105145E+11 | 0.322105E+10 | 744.00 | 0.105145E+11 | 0.00 | 0.00 | 0.57 | 09-OCT-17:02 | 0.42 | 28-OCT-07:00 | 4390.77 | 01-OCT-17:33 | 4390.77 | 01-OCT-17:33 | 0.00 | 01-OCT-00:10 | 1636.64 | 05-OCT-15:00 | 0.00 |
November | 0.147462E+11 | 0.386796E+10 | 720.00 | 0.147462E+11 | 0.00 | 0.00 | 0.77 | 06-NOV-17:00 | 0.62 | 16-NOV-08:00 | 6227.64 | 12-NOV-17:07 | 6227.64 | 12-NOV-17:07 | 0.00 | 01-NOV-00:10 | 2061.37 | 02-NOV-13:00 | 0.00 |
December | 0.199650E+11 | 0.489296E+10 | 744.00 | 0.199650E+11 | 0.00 | 0.00 | 0.97 | 15-DEC-17:00 | 0.78 | 21-DEC-08:00 | 8058.94 | 10-DEC-17:10 | 8058.94 | 10-DEC-17:10 | 0.00 | 01-DEC-00:10 | 2713.00 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.150623E+12 | 0.437887E+11 | 8760.00 | 0.150623E+12 | 286408.75 | ||||||||||||||
Minimum of Months | 0.489459E+10 | 0.125696E+10 | 672.00 | 0.489441E+10 | 0.00 | 0.00 | 0.32 | 0.17 | 2470.84 | 2470.84 | 0.00 | 744.05 | 0.00 | ||||||
Maximum of Months | 0.202291E+11 | 0.672425E+10 | 744.00 | 0.202291E+11 | 180804.34 | 0.00 | 1.00 | 0.87 | 8189.92 | 8189.92 | 4.87 | 3151.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.347878E+11 | 0.919241E+10 | 744.00 | 0.347861E+11 | 1615904.57 | 0.00 | 0.30 | 31-JAN-17:50 | 0.09 | 10-JAN-06:20 | 21960.75 | 31-JAN-17:50 | 21960.75 | 31-JAN-17:50 | 28.36 | 02-JAN-02:13 | 6775.79 | 02-JAN-17:00 | 0.00 |
February | 0.766950E+11 | 0.195105E+11 | 672.00 | 0.766939E+11 | 1041782.19 | 0.00 | 0.54 | 26-FEB-17:52 | 0.25 | 05-FEB-08:30 | 40928.23 | 26-FEB-18:00 | 40928.23 | 26-FEB-18:00 | 41.28 | 04-FEB-22:00 | 12388.06 | 02-FEB-13:10 | 0.00 |
March | 0.135152E+12 | 0.346337E+11 | 744.00 | 0.135152E+12 | 0.00 | 0.00 | 0.74 | 30-MAR-13:00 | 0.50 | 12-MAR-07:30 | 56827.66 | 06-MAR-18:00 | 56827.66 | 06-MAR-18:00 | 0.00 | 01-MAR-00:10 | 19226.70 | 30-MAR-13:00 | 0.00 |
April | 0.182661E+12 | 0.509302E+11 | 720.00 | 0.182661E+12 | 0.00 | 0.00 | 0.99 | 28-APR-15:10 | 0.78 | 11-APR-07:00 | 76422.26 | 16-APR-18:20 | 76422.26 | 16-APR-18:20 | 0.00 | 01-APR-00:10 | 28361.82 | 28-APR-15:00 | 0.00 |
May | 0.516372E+11 | 0.174564E+11 | 744.00 | 0.516372E+11 | 0.00 | 0.00 | 0.33 | 29-MAY-17:52 | 0.24 | 22-MAY-21:20 | 22908.65 | 14-MAY-18:23 | 22908.65 | 14-MAY-18:23 | 0.00 | 01-MAY-00:03 | 8659.90 | 18-MAY-16:00 | 0.00 |
June | 0.958574E+11 | 0.323003E+11 | 720.00 | 0.958574E+11 | 0.00 | 0.00 | 0.57 | 11-JUN-18:12 | 0.46 | 07-JUN-06:50 | 40525.58 | 11-JUN-18:27 | 40525.58 | 11-JUN-18:27 | 0.00 | 01-JUN-00:10 | 15709.80 | 14-JUN-14:00 | 0.00 |
July | 0.145862E+12 | 0.492337E+11 | 744.00 | 0.145862E+12 | 0.00 | 0.00 | 0.81 | 21-JUL-16:00 | 0.68 | 11-JUL-21:12 | 56590.60 | 16-JUL-19:00 | 56590.60 | 16-JUL-19:00 | 0.00 | 01-JUL-00:03 | 23687.35 | 21-JUL-16:00 | 0.00 |
August | 0.192596E+12 | 0.640199E+11 | 744.00 | 0.192596E+12 | 0.00 | 0.00 | 1.00 | 01-AUG-15:10 | 0.86 | 16-AUG-21:12 | 74820.41 | 30-AUG-18:40 | 74820.41 | 30-AUG-18:40 | 0.00 | 01-AUG-00:05 | 29965.22 | 30-AUG-16:00 | 0.00 |
September | 0.492463E+11 | 0.163489E+11 | 720.00 | 0.492463E+11 | 0.00 | 0.00 | 0.35 | 03-SEP-17:55 | 0.22 | 07-SEP-21:13 | 24034.55 | 03-SEP-17:55 | 24034.55 | 03-SEP-17:55 | 0.00 | 01-SEP-00:10 | 9225.00 | 09-SEP-18:10 | 0.00 |
October | 0.969803E+11 | 0.298788E+11 | 744.00 | 0.969803E+11 | 0.00 | 0.00 | 0.57 | 05-OCT-17:30 | 0.38 | 28-OCT-07:40 | 41000.71 | 09-OCT-17:28 | 41000.71 | 09-OCT-17:28 | 0.00 | 01-OCT-00:10 | 15518.20 | 05-OCT-15:00 | 0.00 |
November | 0.133324E+12 | 0.352877E+11 | 720.00 | 0.133324E+12 | 0.00 | 0.00 | 0.77 | 06-NOV-17:00 | 0.57 | 16-NOV-08:00 | 58354.37 | 06-NOV-17:00 | 58354.37 | 06-NOV-17:00 | 0.00 | 01-NOV-00:10 | 19583.18 | 02-NOV-13:00 | 0.00 |
December | 0.179938E+12 | 0.445542E+11 | 744.00 | 0.179938E+12 | 0.00 | 0.00 | 0.97 | 15-DEC-17:00 | 0.70 | 31-DEC-04:00 | 74988.06 | 15-DEC-17:00 | 74988.06 | 15-DEC-17:00 | 0.00 | 01-DEC-00:10 | 25714.14 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.137474E+13 | 0.403347E+12 | 8760.00 | 0.137473E+13 | 2657686.76 | ||||||||||||||
Minimum of Months | 0.347878E+11 | 0.919241E+10 | 672.00 | 0.347861E+11 | 0.00 | 0.00 | 0.30 | 0.09 | 21960.75 | 21960.75 | 0.00 | 6775.79 | 0.00 | ||||||
Maximum of Months | 0.192596E+12 | 0.640199E+11 | 744.00 | 0.192596E+12 | 1615904.57 | 0.00 | 1.00 | 0.86 | 76422.26 | 76422.26 | 41.28 | 29965.22 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.253000E+10 | 0.692169E+09 | 705.04 | 0.252986E+10 | 148052.56 | 0.00 | 0.31 | 31-JAN-17:50 | 0.00 | 04-JAN-02:35 | 2274.33 | 31-JAN-17:50 | 2274.33 | 31-JAN-17:50 | 2.77 | 03-JAN-11:00 | 683.93 | 02-JAN-17:00 | 0.00 |
February | 0.695537E+10 | 0.179467E+10 | 671.79 | 0.695527E+10 | 107027.39 | 0.00 | 0.53 | 26-FEB-17:42 | 0.00 | 05-FEB-07:15 | 4093.56 | 26-FEB-18:00 | 4093.56 | 26-FEB-18:00 | 3.29 | 04-FEB-22:00 | 1254.69 | 02-FEB-14:00 | 0.00 |
March | 0.130081E+11 | 0.336438E+10 | 744.00 | 0.130081E+11 | 0.00 | 0.00 | 0.74 | 30-MAR-13:00 | 0.37 | 12-MAR-07:45 | 5755.77 | 06-MAR-17:50 | 5755.77 | 06-MAR-17:50 | 0.00 | 01-MAR-00:10 | 1945.11 | 30-MAR-13:00 | 0.00 |
April | 0.181245E+11 | 0.507648E+10 | 720.00 | 0.181245E+11 | 0.00 | 0.00 | 0.99 | 28-APR-15:40 | 0.72 | 11-APR-06:55 | 7748.27 | 23-APR-18:08 | 7748.27 | 23-APR-18:08 | 0.00 | 01-APR-00:10 | 2878.02 | 28-APR-15:00 | 0.00 |
May | 0.528857E+10 | 0.178890E+10 | 744.00 | 0.528857E+10 | 0.00 | 0.00 | 0.36 | 29-MAY-17:52 | 0.23 | 13-MAY-07:00 | 2552.19 | 29-MAY-17:56 | 2552.19 | 29-MAY-17:56 | 0.00 | 01-MAY-00:03 | 962.20 | 28-MAY-16:02 | 0.00 |
June | 0.972832E+10 | 0.327979E+10 | 720.00 | 0.972832E+10 | 0.00 | 0.00 | 0.60 | 11-JUN-18:12 | 0.43 | 07-JUN-07:00 | 4298.66 | 11-JUN-18:30 | 4298.66 | 11-JUN-18:30 | 0.00 | 01-JUN-00:10 | 1630.38 | 11-JUN-17:05 | 0.00 |
July | 0.147381E+11 | 0.497846E+10 | 744.00 | 0.147381E+11 | 0.00 | 0.00 | 0.81 | 21-JUL-16:00 | 0.66 | 11-JUL-21:12 | 5882.29 | 16-JUL-18:47 | 5882.29 | 16-JUL-18:47 | 0.00 | 01-JUL-00:03 | 2414.19 | 21-JUL-16:00 | 0.00 |
August | 0.193693E+11 | 0.644815E+10 | 744.00 | 0.193693E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-15:10 | 0.85 | 16-AUG-21:12 | 7620.19 | 06-AUG-17:34 | 7620.19 | 06-AUG-17:34 | 0.00 | 01-AUG-00:05 | 3043.31 | 30-AUG-16:00 | 0.00 |
September | 0.500729E+10 | 0.166493E+10 | 720.00 | 0.500729E+10 | 0.00 | 0.00 | 0.38 | 10-SEP-17:35 | 0.21 | 07-SEP-21:25 | 2623.96 | 03-SEP-17:55 | 2623.96 | 03-SEP-17:55 | 0.00 | 01-SEP-00:10 | 1000.70 | 10-SEP-16:02 | 0.00 |
October | 0.962269E+10 | 0.298027E+10 | 744.00 | 0.962269E+10 | 0.00 | 0.00 | 0.58 | 08-OCT-16:15 | 0.31 | 29-OCT-07:30 | 4303.96 | 09-OCT-17:24 | 4303.96 | 09-OCT-17:24 | 0.00 | 01-OCT-00:10 | 1585.95 | 05-OCT-15:00 | 0.00 |
November | 0.128177E+11 | 0.342472E+10 | 720.00 | 0.128177E+11 | 0.00 | 0.00 | 0.77 | 06-NOV-17:00 | 0.48 | 16-NOV-07:00 | 5904.43 | 06-NOV-17:00 | 5904.43 | 06-NOV-17:00 | 0.00 | 01-NOV-00:10 | 1985.92 | 02-NOV-13:00 | 0.00 |
December | 0.172053E+11 | 0.430677E+10 | 744.00 | 0.172053E+11 | 0.00 | 0.00 | 0.97 | 15-DEC-17:00 | 0.59 | 31-DEC-06:30 | 7572.17 | 15-DEC-17:00 | 7572.17 | 15-DEC-17:00 | 0.00 | 01-DEC-00:10 | 2589.80 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.134395E+12 | 0.397997E+11 | 8720.83 | 0.134395E+12 | 255079.95 | ||||||||||||||
Minimum of Months | 0.253000E+10 | 0.692169E+09 | 671.79 | 0.252986E+10 | 0.00 | 0.00 | 0.31 | 0.00 | 2274.33 | 2274.33 | 0.00 | 683.93 | 0.00 | ||||||
Maximum of Months | 0.193693E+11 | 0.644815E+10 | 744.00 | 0.193693E+11 | 148052.56 | 0.00 | 1.00 | 0.85 | 7748.27 | 7748.27 | 3.29 | 3043.31 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.77 | 0.00 | 110.77 | 55.23 | 531.90 | 0.00 | 0.00 | 744.00 |
February | 130.69 | 0.00 | 130.69 | 78.36 | 452.12 | 0.00 | 0.00 | 672.00 |
March | 151.61 | 0.00 | 151.61 | 122.25 | 384.96 | 0.00 | 0.00 | 744.00 |
April | 178.92 | 0.72 | 178.19 | 212.29 | 230.02 | 0.00 | 0.00 | 720.00 |
May | 202.64 | 7.38 | 195.26 | 383.79 | 60.76 | 0.00 | 0.00 | 744.00 |
June | 230.43 | 15.91 | 214.52 | 451.79 | 48.42 | 0.00 | 0.00 | 720.00 |
July | 223.63 | 8.49 | 215.15 | 441.99 | 29.92 | 0.00 | 0.00 | 744.00 |
August | 200.29 | 1.56 | 198.72 | 407.01 | 44.21 | 0.00 | 0.00 | 744.00 |
September | 173.01 | 0.01 | 173.00 | 322.21 | 73.42 | 0.00 | 0.00 | 720.00 |
October | 150.34 | 0.00 | 150.34 | 253.99 | 141.54 | 0.00 | 0.00 | 744.00 |
November | 114.14 | 0.00 | 114.14 | 96.99 | 342.99 | 0.00 | 0.00 | 720.00 |
December | 102.98 | 0.00 | 102.98 | 61.33 | 472.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 164.29 | 2.85 | 161.44 | 241.61 | 233.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 55.23 | 29.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 230.43 | 15.91 | 215.15 | 451.79 | 531.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.77 | 0.00 | 110.77 | 55.23 | 531.90 | 0.00 | 0.00 | 744.00 |
February | 130.69 | 0.00 | 130.69 | 78.36 | 452.12 | 0.00 | 0.00 | 672.00 |
March | 151.61 | 0.00 | 151.61 | 122.25 | 384.96 | 0.00 | 0.00 | 744.00 |
April | 178.92 | 0.72 | 178.19 | 212.29 | 230.02 | 0.00 | 0.00 | 720.00 |
May | 202.64 | 7.38 | 195.26 | 383.79 | 60.76 | 0.00 | 0.00 | 744.00 |
June | 230.43 | 15.91 | 214.52 | 451.79 | 48.42 | 0.00 | 0.00 | 720.00 |
July | 223.63 | 8.49 | 215.15 | 441.99 | 29.92 | 0.00 | 0.00 | 744.00 |
August | 200.29 | 1.56 | 198.72 | 407.01 | 44.21 | 0.00 | 0.00 | 744.00 |
September | 173.01 | 0.01 | 173.00 | 322.21 | 73.42 | 0.00 | 0.00 | 720.00 |
October | 150.34 | 0.00 | 150.34 | 253.99 | 141.54 | 0.00 | 0.00 | 744.00 |
November | 114.14 | 0.00 | 114.14 | 96.99 | 342.99 | 0.00 | 0.00 | 720.00 |
December | 102.98 | 0.00 | 102.98 | 61.33 | 472.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 164.28 | 2.85 | 161.44 | 241.61 | 233.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 55.23 | 29.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 230.43 | 15.91 | 215.15 | 451.79 | 531.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.77 | 0.00 | 110.77 | 55.23 | 531.90 | 0.00 | 0.00 | 744.00 |
February | 130.69 | 0.00 | 130.69 | 78.36 | 452.12 | 0.00 | 0.00 | 672.00 |
March | 151.61 | 0.00 | 151.61 | 122.25 | 384.96 | 0.00 | 0.00 | 744.00 |
April | 178.92 | 0.72 | 178.19 | 212.29 | 230.02 | 0.00 | 0.00 | 720.00 |
May | 202.64 | 7.38 | 195.26 | 383.79 | 60.76 | 0.00 | 0.00 | 744.00 |
June | 230.43 | 15.91 | 214.52 | 451.79 | 48.42 | 0.00 | 0.00 | 720.00 |
July | 223.63 | 8.49 | 215.15 | 441.99 | 29.92 | 0.00 | 0.00 | 744.00 |
August | 200.29 | 1.56 | 198.72 | 407.01 | 44.21 | 0.00 | 0.00 | 744.00 |
September | 173.01 | 0.01 | 173.00 | 322.21 | 73.42 | 0.00 | 0.00 | 720.00 |
October | 150.34 | 0.00 | 150.34 | 253.99 | 141.54 | 0.00 | 0.00 | 744.00 |
November | 114.14 | 0.00 | 114.14 | 96.99 | 342.99 | 0.00 | 0.00 | 720.00 |
December | 102.98 | 0.00 | 102.98 | 61.33 | 472.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 164.29 | 2.85 | 161.44 | 241.61 | 233.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 55.23 | 29.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 230.43 | 15.91 | 215.15 | 451.79 | 531.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.77 | 0.00 | 110.77 | 55.23 | 531.90 | 0.00 | 0.00 | 744.00 |
February | 130.69 | 0.00 | 130.69 | 78.36 | 452.12 | 0.00 | 0.00 | 672.00 |
March | 151.61 | 0.00 | 151.61 | 122.25 | 384.96 | 0.00 | 0.00 | 744.00 |
April | 178.92 | 0.72 | 178.19 | 212.29 | 230.02 | 0.00 | 0.00 | 720.00 |
May | 202.64 | 7.38 | 195.26 | 383.79 | 60.76 | 0.00 | 0.00 | 744.00 |
June | 230.43 | 15.91 | 214.52 | 451.79 | 48.42 | 0.00 | 0.00 | 720.00 |
July | 223.63 | 8.49 | 215.15 | 441.99 | 29.92 | 0.00 | 0.00 | 744.00 |
August | 200.29 | 1.56 | 198.72 | 407.01 | 44.21 | 0.00 | 0.00 | 744.00 |
September | 173.01 | 0.01 | 173.00 | 322.21 | 73.42 | 0.00 | 0.00 | 720.00 |
October | 150.34 | 0.00 | 150.34 | 253.99 | 141.54 | 0.00 | 0.00 | 744.00 |
November | 114.14 | 0.00 | 114.14 | 96.99 | 342.99 | 0.00 | 0.00 | 720.00 |
December | 102.98 | 0.00 | 102.98 | 61.33 | 472.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 164.28 | 2.85 | 161.44 | 241.61 | 233.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 55.23 | 29.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 230.43 | 15.91 | 215.15 | 451.79 | 531.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.77 | 0.00 | 110.77 | 55.23 | 531.88 | 0.00 | 0.00 | 744.00 |
February | 130.68 | 0.00 | 130.68 | 78.35 | 452.10 | 0.00 | 0.00 | 672.00 |
March | 151.60 | 0.00 | 151.60 | 122.25 | 384.95 | 0.00 | 0.00 | 744.00 |
April | 178.91 | 0.72 | 178.19 | 212.28 | 230.01 | 0.00 | 0.00 | 720.00 |
May | 202.63 | 7.38 | 195.25 | 383.77 | 60.76 | 0.00 | 0.00 | 744.00 |
June | 230.42 | 15.91 | 214.51 | 451.77 | 48.42 | 0.00 | 0.00 | 720.00 |
July | 223.62 | 8.49 | 215.14 | 441.98 | 29.92 | 0.00 | 0.00 | 744.00 |
August | 200.28 | 1.56 | 198.71 | 406.99 | 44.21 | 0.00 | 0.00 | 744.00 |
September | 173.00 | 0.01 | 172.99 | 322.19 | 73.41 | 0.00 | 0.00 | 720.00 |
October | 150.34 | 0.00 | 150.34 | 253.98 | 141.54 | 0.00 | 0.00 | 744.00 |
November | 114.13 | 0.00 | 114.13 | 96.99 | 342.98 | 0.00 | 0.00 | 720.00 |
December | 102.97 | 0.00 | 102.97 | 61.33 | 472.36 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 164.28 | 2.85 | 161.43 | 241.60 | 233.25 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.97 | 0.00 | 102.97 | 55.23 | 29.92 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 230.42 | 15.91 | 215.14 | 451.77 | 531.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.75 | 161.29 | 155.47 | 309.97 | 524.62 | 0.00 | 0.00 | 744.00 |
February | 352.71 | 170.27 | 182.44 | 371.58 | 440.85 | 0.00 | 0.00 | 672.00 |
March | 414.95 | 200.14 | 214.81 | 501.95 | 375.92 | 0.00 | 0.00 | 744.00 |
April | 455.34 | 205.95 | 249.39 | 644.86 | 226.04 | 0.00 | 0.00 | 720.00 |
May | 469.31 | 203.50 | 265.81 | 837.63 | 64.72 | 0.00 | 0.00 | 744.00 |
June | 475.95 | 188.74 | 287.21 | 882.01 | 47.56 | 0.00 | 0.00 | 720.00 |
July | 458.89 | 167.92 | 290.97 | 856.22 | 24.98 | 0.00 | 0.00 | 744.00 |
August | 422.86 | 145.39 | 277.48 | 789.01 | 37.42 | 0.00 | 0.00 | 744.00 |
September | 374.59 | 128.79 | 245.80 | 656.18 | 75.42 | 0.00 | 0.00 | 720.00 |
October | 370.16 | 156.21 | 213.95 | 606.10 | 140.95 | 0.00 | 0.00 | 744.00 |
November | 327.71 | 167.17 | 160.54 | 396.08 | 331.00 | 0.00 | 0.00 | 720.00 |
December | 258.02 | 116.87 | 141.15 | 261.23 | 458.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 391.57 | 167.61 | 223.96 | 593.98 | 227.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 258.02 | 116.87 | 141.15 | 261.23 | 24.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 475.95 | 205.95 | 290.97 | 882.01 | 524.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.75 | 161.29 | 155.47 | 309.97 | 524.62 | 0.00 | 0.00 | 744.00 |
February | 352.71 | 170.27 | 182.44 | 371.58 | 440.85 | 0.00 | 0.00 | 672.00 |
March | 414.95 | 200.14 | 214.81 | 501.95 | 375.92 | 0.00 | 0.00 | 744.00 |
April | 455.34 | 205.95 | 249.39 | 644.86 | 226.04 | 0.00 | 0.00 | 720.00 |
May | 469.31 | 203.50 | 265.81 | 837.63 | 64.72 | 0.00 | 0.00 | 744.00 |
June | 475.95 | 188.74 | 287.21 | 882.01 | 47.56 | 0.00 | 0.00 | 720.00 |
July | 458.89 | 167.92 | 290.97 | 856.22 | 24.98 | 0.00 | 0.00 | 744.00 |
August | 422.86 | 145.39 | 277.48 | 789.01 | 37.42 | 0.00 | 0.00 | 744.00 |
September | 374.59 | 128.79 | 245.80 | 656.18 | 75.42 | 0.00 | 0.00 | 720.00 |
October | 370.16 | 156.21 | 213.95 | 606.10 | 140.95 | 0.00 | 0.00 | 744.00 |
November | 327.71 | 167.17 | 160.54 | 396.08 | 331.00 | 0.00 | 0.00 | 720.00 |
December | 258.02 | 116.87 | 141.15 | 261.23 | 458.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 391.57 | 167.61 | 223.96 | 593.98 | 227.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 258.02 | 116.87 | 141.15 | 261.23 | 24.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 475.95 | 205.95 | 290.97 | 882.01 | 524.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.75 | 161.29 | 155.46 | 309.97 | 524.61 | 0.00 | 0.00 | 744.00 |
February | 352.70 | 170.27 | 182.43 | 371.57 | 440.85 | 0.00 | 0.00 | 672.00 |
March | 414.94 | 200.13 | 214.81 | 501.94 | 375.91 | 0.00 | 0.00 | 744.00 |
April | 455.33 | 205.94 | 249.39 | 644.85 | 226.04 | 0.00 | 0.00 | 720.00 |
May | 469.30 | 203.49 | 265.81 | 837.61 | 64.72 | 0.00 | 0.00 | 744.00 |
June | 475.94 | 188.74 | 287.21 | 881.99 | 47.56 | 0.00 | 0.00 | 720.00 |
July | 458.88 | 167.92 | 290.96 | 856.21 | 24.98 | 0.00 | 0.00 | 744.00 |
August | 422.86 | 145.38 | 277.47 | 789.00 | 37.42 | 0.00 | 0.00 | 744.00 |
September | 374.59 | 128.79 | 245.80 | 656.17 | 75.42 | 0.00 | 0.00 | 720.00 |
October | 370.15 | 156.20 | 213.95 | 606.09 | 140.94 | 0.00 | 0.00 | 744.00 |
November | 327.70 | 167.17 | 160.54 | 396.07 | 330.99 | 0.00 | 0.00 | 720.00 |
December | 258.02 | 116.87 | 141.15 | 261.22 | 458.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 391.56 | 167.61 | 223.96 | 593.97 | 227.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 258.02 | 116.87 | 141.15 | 261.22 | 24.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 475.94 | 205.94 | 290.96 | 881.99 | 524.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.48 | 456.83 | 183.65 | 845.97 | 459.76 | 0.00 | 0.00 | 744.00 |
February | 580.76 | 375.93 | 204.83 | 756.11 | 400.08 | 0.00 | 0.00 | 672.00 |
March | 370.63 | 167.20 | 203.42 | 452.24 | 361.49 | 0.00 | 0.00 | 744.00 |
April | 274.66 | 64.27 | 210.40 | 343.77 | 227.22 | 0.00 | 0.00 | 720.00 |
May | 209.87 | 8.84 | 201.03 | 390.19 | 62.27 | 0.00 | 0.00 | 744.00 |
June | 207.36 | 1.89 | 205.47 | 419.25 | 50.35 | 0.00 | 0.00 | 720.00 |
July | 217.06 | 3.94 | 213.12 | 430.99 | 30.20 | 0.00 | 0.00 | 744.00 |
August | 255.34 | 30.57 | 224.77 | 480.78 | 46.81 | 0.00 | 0.00 | 744.00 |
September | 306.39 | 80.69 | 225.70 | 524.45 | 76.25 | 0.00 | 0.00 | 720.00 |
October | 475.44 | 247.64 | 227.80 | 779.91 | 143.86 | 0.00 | 0.00 | 744.00 |
November | 605.23 | 416.75 | 188.48 | 871.14 | 311.28 | 0.00 | 0.00 | 720.00 |
December | 625.84 | 449.50 | 176.34 | 872.80 | 416.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 396.45 | 191.05 | 205.40 | 596.63 | 214.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 207.36 | 1.89 | 176.34 | 343.77 | 30.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 640.48 | 456.83 | 227.80 | 872.80 | 459.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.48 | 456.83 | 183.65 | 845.97 | 459.76 | 0.00 | 0.00 | 744.00 |
February | 580.76 | 375.93 | 204.83 | 756.11 | 400.08 | 0.00 | 0.00 | 672.00 |
March | 370.63 | 167.20 | 203.42 | 452.24 | 361.49 | 0.00 | 0.00 | 744.00 |
April | 274.66 | 64.27 | 210.40 | 343.77 | 227.22 | 0.00 | 0.00 | 720.00 |
May | 209.87 | 8.84 | 201.03 | 390.19 | 62.27 | 0.00 | 0.00 | 744.00 |
June | 207.36 | 1.89 | 205.47 | 419.25 | 50.35 | 0.00 | 0.00 | 720.00 |
July | 217.06 | 3.94 | 213.12 | 430.99 | 30.20 | 0.00 | 0.00 | 744.00 |
August | 255.34 | 30.57 | 224.77 | 480.78 | 46.81 | 0.00 | 0.00 | 744.00 |
September | 306.39 | 80.69 | 225.70 | 524.45 | 76.25 | 0.00 | 0.00 | 720.00 |
October | 475.44 | 247.64 | 227.80 | 779.91 | 143.86 | 0.00 | 0.00 | 744.00 |
November | 605.23 | 416.75 | 188.48 | 871.13 | 311.27 | 0.00 | 0.00 | 720.00 |
December | 625.84 | 449.50 | 176.34 | 872.79 | 416.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 396.45 | 191.05 | 205.40 | 596.63 | 214.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 207.36 | 1.89 | 176.34 | 343.77 | 30.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 640.48 | 456.83 | 227.80 | 872.79 | 459.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.48 | 456.83 | 183.65 | 845.97 | 459.76 | 0.00 | 0.00 | 744.00 |
February | 580.76 | 375.93 | 204.83 | 756.11 | 400.08 | 0.00 | 0.00 | 672.00 |
March | 370.63 | 167.20 | 203.42 | 452.24 | 361.49 | 0.00 | 0.00 | 744.00 |
April | 274.66 | 64.27 | 210.40 | 343.77 | 227.22 | 0.00 | 0.00 | 720.00 |
May | 209.87 | 8.84 | 201.03 | 390.19 | 62.27 | 0.00 | 0.00 | 744.00 |
June | 207.36 | 1.89 | 205.47 | 419.25 | 50.35 | 0.00 | 0.00 | 720.00 |
July | 217.06 | 3.94 | 213.12 | 430.99 | 30.20 | 0.00 | 0.00 | 744.00 |
August | 255.34 | 30.57 | 224.77 | 480.78 | 46.81 | 0.00 | 0.00 | 744.00 |
September | 306.39 | 80.69 | 225.70 | 524.45 | 76.25 | 0.00 | 0.00 | 720.00 |
October | 475.44 | 247.64 | 227.80 | 779.91 | 143.86 | 0.00 | 0.00 | 744.00 |
November | 605.23 | 416.75 | 188.48 | 871.14 | 311.28 | 0.00 | 0.00 | 720.00 |
December | 625.84 | 449.50 | 176.34 | 872.80 | 416.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 396.45 | 191.05 | 205.40 | 596.63 | 214.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 207.36 | 1.89 | 176.34 | 343.77 | 30.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 640.48 | 456.83 | 227.80 | 872.80 | 459.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.48 | 456.83 | 183.65 | 845.97 | 459.76 | 0.00 | 0.00 | 744.00 |
February | 580.76 | 375.93 | 204.83 | 756.11 | 400.08 | 0.00 | 0.00 | 672.00 |
March | 370.63 | 167.20 | 203.42 | 452.24 | 361.49 | 0.00 | 0.00 | 744.00 |
April | 274.66 | 64.27 | 210.40 | 343.77 | 227.22 | 0.00 | 0.00 | 720.00 |
May | 209.87 | 8.84 | 201.03 | 390.19 | 62.27 | 0.00 | 0.00 | 744.00 |
June | 207.36 | 1.89 | 205.47 | 419.25 | 50.35 | 0.00 | 0.00 | 720.00 |
July | 217.06 | 3.94 | 213.12 | 430.99 | 30.20 | 0.00 | 0.00 | 744.00 |
August | 255.34 | 30.57 | 224.77 | 480.78 | 46.81 | 0.00 | 0.00 | 744.00 |
September | 306.39 | 80.69 | 225.70 | 524.45 | 76.25 | 0.00 | 0.00 | 720.00 |
October | 475.44 | 247.64 | 227.80 | 779.91 | 143.86 | 0.00 | 0.00 | 744.00 |
November | 605.23 | 416.75 | 188.48 | 871.13 | 311.27 | 0.00 | 0.00 | 720.00 |
December | 625.84 | 449.50 | 176.34 | 872.79 | 416.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 396.45 | 191.05 | 205.40 | 596.63 | 214.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 207.36 | 1.89 | 176.34 | 343.77 | 30.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 640.48 | 456.83 | 227.80 | 872.79 | 459.76 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.45 | 456.81 | 183.65 | 845.94 | 459.74 | 0.00 | 0.00 | 744.00 |
February | 580.73 | 375.92 | 204.82 | 756.08 | 400.06 | 0.00 | 0.00 | 672.00 |
March | 370.61 | 167.20 | 203.41 | 452.22 | 361.48 | 0.00 | 0.00 | 744.00 |
April | 274.65 | 64.27 | 210.39 | 343.76 | 227.21 | 0.00 | 0.00 | 720.00 |
May | 209.86 | 8.84 | 201.02 | 390.17 | 62.27 | 0.00 | 0.00 | 744.00 |
June | 207.35 | 1.89 | 205.46 | 419.23 | 50.35 | 0.00 | 0.00 | 720.00 |
July | 217.05 | 3.94 | 213.12 | 430.97 | 30.20 | 0.00 | 0.00 | 744.00 |
August | 255.33 | 30.57 | 224.76 | 480.76 | 46.81 | 0.00 | 0.00 | 744.00 |
September | 306.38 | 80.69 | 225.69 | 524.43 | 76.25 | 0.00 | 0.00 | 720.00 |
October | 475.42 | 247.63 | 227.79 | 779.88 | 143.85 | 0.00 | 0.00 | 744.00 |
November | 605.20 | 416.74 | 188.47 | 871.10 | 311.26 | 0.00 | 0.00 | 720.00 |
December | 625.82 | 449.48 | 176.33 | 872.76 | 416.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 396.44 | 191.05 | 205.39 | 596.60 | 214.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 207.35 | 1.89 | 176.33 | 343.76 | 30.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 640.45 | 456.81 | 227.79 | 872.76 | 459.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 336.92 | 182.18 | 154.73 | 361.40 | 592.55 | 0.00 | 0.00 | 744.00 |
February | 381.46 | 193.07 | 188.40 | 424.51 | 529.17 | 0.00 | 0.00 | 672.00 |
March | 376.00 | 166.45 | 209.54 | 440.24 | 475.45 | 0.00 | 0.00 | 744.00 |
April | 467.00 | 214.84 | 252.16 | 647.57 | 311.99 | 0.00 | 0.00 | 720.00 |
May | 388.34 | 126.49 | 261.84 | 695.40 | 93.05 | 0.00 | 0.00 | 744.00 |
June | 431.40 | 151.26 | 280.14 | 787.78 | 83.83 | 0.00 | 0.00 | 720.00 |
July | 393.79 | 109.22 | 284.56 | 709.94 | 63.45 | 0.00 | 0.00 | 744.00 |
August | 398.18 | 121.89 | 276.29 | 716.89 | 90.58 | 0.00 | 0.00 | 744.00 |
September | 366.67 | 125.79 | 240.87 | 634.78 | 106.57 | 0.00 | 0.00 | 720.00 |
October | 375.38 | 162.20 | 213.18 | 610.79 | 193.07 | 0.00 | 0.00 | 744.00 |
November | 321.73 | 161.68 | 160.05 | 397.71 | 428.31 | 0.00 | 0.00 | 720.00 |
December | 309.49 | 164.58 | 144.91 | 340.16 | 578.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 378.65 | 156.26 | 222.38 | 564.50 | 294.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 309.49 | 109.22 | 144.91 | 340.16 | 63.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 467.00 | 214.84 | 284.56 | 787.78 | 592.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 336.92 | 182.18 | 154.73 | 361.40 | 592.55 | 0.00 | 0.00 | 744.00 |
February | 381.46 | 193.07 | 188.40 | 424.51 | 529.17 | 0.00 | 0.00 | 672.00 |
March | 376.00 | 166.45 | 209.54 | 440.24 | 475.45 | 0.00 | 0.00 | 744.00 |
April | 467.00 | 214.84 | 252.16 | 647.57 | 311.99 | 0.00 | 0.00 | 720.00 |
May | 388.34 | 126.49 | 261.84 | 695.40 | 93.05 | 0.00 | 0.00 | 744.00 |
June | 431.40 | 151.26 | 280.14 | 787.78 | 83.83 | 0.00 | 0.00 | 720.00 |
July | 393.79 | 109.22 | 284.56 | 709.94 | 63.45 | 0.00 | 0.00 | 744.00 |
August | 398.18 | 121.89 | 276.29 | 716.89 | 90.58 | 0.00 | 0.00 | 744.00 |
September | 366.67 | 125.79 | 240.87 | 634.78 | 106.57 | 0.00 | 0.00 | 720.00 |
October | 375.38 | 162.20 | 213.18 | 610.79 | 193.07 | 0.00 | 0.00 | 744.00 |
November | 321.73 | 161.68 | 160.05 | 397.71 | 428.31 | 0.00 | 0.00 | 720.00 |
December | 309.49 | 164.58 | 144.91 | 340.16 | 578.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 378.65 | 156.26 | 222.38 | 564.50 | 294.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 309.49 | 109.22 | 144.91 | 340.16 | 63.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 467.00 | 214.84 | 284.56 | 787.78 | 592.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 336.91 | 182.18 | 154.73 | 361.39 | 592.54 | 0.00 | 0.00 | 744.00 |
February | 381.45 | 193.06 | 188.39 | 424.50 | 529.16 | 0.00 | 0.00 | 672.00 |
March | 375.99 | 166.45 | 209.54 | 440.23 | 475.44 | 0.00 | 0.00 | 744.00 |
April | 466.99 | 214.84 | 252.16 | 647.56 | 311.98 | 0.00 | 0.00 | 720.00 |
May | 388.33 | 126.49 | 261.84 | 695.39 | 93.05 | 0.00 | 0.00 | 744.00 |
June | 431.39 | 151.26 | 280.13 | 787.77 | 83.83 | 0.00 | 0.00 | 720.00 |
July | 393.78 | 109.22 | 284.56 | 709.93 | 63.45 | 0.00 | 0.00 | 744.00 |
August | 398.17 | 121.89 | 276.29 | 716.88 | 90.58 | 0.00 | 0.00 | 744.00 |
September | 366.66 | 125.79 | 240.87 | 634.77 | 106.57 | 0.00 | 0.00 | 720.00 |
October | 375.38 | 162.20 | 213.18 | 610.78 | 193.07 | 0.00 | 0.00 | 744.00 |
November | 321.73 | 161.68 | 160.05 | 397.71 | 428.30 | 0.00 | 0.00 | 720.00 |
December | 309.48 | 164.58 | 144.91 | 340.15 | 578.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 378.64 | 156.26 | 222.38 | 564.49 | 294.32 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 309.48 | 109.22 | 144.91 | 340.15 | 63.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 466.99 | 214.84 | 284.56 | 787.77 | 592.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 553.86 | 0.00 | 553.86 | 341.98 | 2332.73 | 0.00 | 0.00 | 744.00 |
February | 653.42 | 0.00 | 653.42 | 465.63 | 1946.30 | 0.00 | 0.00 | 672.00 |
March | 758.02 | 0.00 | 758.02 | 688.17 | 1672.45 | 0.00 | 0.00 | 744.00 |
April | 894.59 | 3.62 | 890.96 | 1115.29 | 1026.56 | 0.00 | 0.00 | 720.00 |
May | 1013.18 | 36.90 | 976.28 | 1943.43 | 278.57 | 0.00 | 0.00 | 744.00 |
June | 1152.13 | 79.54 | 1072.60 | 2281.61 | 239.68 | 0.00 | 0.00 | 720.00 |
July | 1118.15 | 42.44 | 1075.71 | 2232.26 | 156.42 | 0.00 | 0.00 | 744.00 |
August | 1001.42 | 7.82 | 993.60 | 2067.79 | 223.24 | 0.00 | 0.00 | 744.00 |
September | 865.05 | 0.06 | 864.98 | 1639.21 | 321.16 | 0.00 | 0.00 | 720.00 |
October | 751.71 | 0.00 | 751.71 | 1311.54 | 629.84 | 0.00 | 0.00 | 744.00 |
November | 570.67 | 0.00 | 570.67 | 555.12 | 1461.99 | 0.00 | 0.00 | 720.00 |
December | 514.87 | 0.00 | 514.87 | 378.93 | 1989.23 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 821.42 | 14.24 | 807.17 | 1256.61 | 1018.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 514.87 | 0.00 | 514.87 | 341.98 | 156.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1152.13 | 79.54 | 1075.71 | 2281.61 | 2332.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 950.25 | 483.86 | 466.39 | 966.40 | 1423.51 | 0.00 | 0.00 | 744.00 |
February | 1058.12 | 510.81 | 547.31 | 1149.25 | 1194.05 | 0.00 | 0.00 | 672.00 |
March | 1244.84 | 600.40 | 644.44 | 1517.69 | 1042.42 | 0.00 | 0.00 | 744.00 |
April | 1366.01 | 617.84 | 748.17 | 1922.35 | 664.04 | 0.00 | 0.00 | 720.00 |
May | 1407.91 | 610.48 | 797.43 | 2491.72 | 193.23 | 0.00 | 0.00 | 744.00 |
June | 1427.84 | 566.21 | 861.63 | 2622.38 | 165.12 | 0.00 | 0.00 | 720.00 |
July | 1376.66 | 503.76 | 872.89 | 2534.79 | 107.02 | 0.00 | 0.00 | 744.00 |
August | 1268.58 | 436.15 | 832.43 | 2337.86 | 152.04 | 0.00 | 0.00 | 744.00 |
September | 1123.77 | 386.38 | 737.39 | 1958.71 | 214.45 | 0.00 | 0.00 | 720.00 |
October | 1110.47 | 468.62 | 641.86 | 1809.72 | 408.40 | 0.00 | 0.00 | 744.00 |
November | 983.12 | 501.51 | 481.61 | 1206.64 | 909.01 | 0.00 | 0.00 | 720.00 |
December | 774.05 | 350.61 | 423.44 | 816.65 | 1239.25 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1174.70 | 502.83 | 671.87 | 1781.37 | 639.88 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 774.05 | 350.61 | 423.44 | 816.65 | 107.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1427.84 | 617.84 | 872.89 | 2622.38 | 1423.51 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3202.35 | 2284.10 | 918.25 | 4188.72 | 2232.70 | 0.00 | 0.00 | 744.00 |
February | 2903.75 | 1879.63 | 1024.12 | 3759.46 | 1918.30 | 0.00 | 0.00 | 672.00 |
March | 1853.11 | 836.01 | 1017.10 | 2270.24 | 1696.19 | 0.00 | 0.00 | 744.00 |
April | 1373.31 | 321.34 | 1051.97 | 1742.73 | 1069.44 | 0.00 | 0.00 | 720.00 |
May | 1049.35 | 44.20 | 1005.15 | 1970.70 | 293.01 | 0.00 | 0.00 | 744.00 |
June | 1036.79 | 9.46 | 1027.32 | 2117.56 | 250.92 | 0.00 | 0.00 | 720.00 |
July | 1085.29 | 19.69 | 1065.61 | 2178.20 | 157.93 | 0.00 | 0.00 | 744.00 |
August | 1276.67 | 152.86 | 1123.81 | 2423.66 | 243.00 | 0.00 | 0.00 | 744.00 |
September | 1531.93 | 403.45 | 1128.48 | 2622.54 | 358.96 | 0.00 | 0.00 | 720.00 |
October | 2377.18 | 1238.18 | 1139.00 | 3872.00 | 705.84 | 0.00 | 0.00 | 744.00 |
November | 3026.11 | 2083.73 | 942.38 | 4326.95 | 1498.08 | 0.00 | 0.00 | 720.00 |
December | 3129.17 | 2247.49 | 881.69 | 4339.81 | 1981.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1982.23 | 955.25 | 1026.98 | 2981.10 | 1029.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1036.79 | 9.46 | 881.69 | 1742.73 | 157.93 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3202.35 | 2284.10 | 1139.00 | 4339.81 | 2232.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1010.74 | 546.54 | 464.20 | 1134.02 | 1559.59 | 0.00 | 0.00 | 744.00 |
February | 1144.37 | 579.19 | 565.18 | 1342.26 | 1330.61 | 0.00 | 0.00 | 672.00 |
March | 1127.98 | 499.35 | 628.63 | 1395.11 | 1160.01 | 0.00 | 0.00 | 744.00 |
April | 1400.99 | 644.52 | 756.47 | 2013.10 | 763.05 | 0.00 | 0.00 | 720.00 |
May | 1164.99 | 379.47 | 785.52 | 2113.66 | 235.58 | 0.00 | 0.00 | 744.00 |
June | 1294.18 | 453.77 | 840.40 | 2402.31 | 211.36 | 0.00 | 0.00 | 720.00 |
July | 1181.34 | 327.66 | 853.68 | 2192.31 | 144.99 | 0.00 | 0.00 | 744.00 |
August | 1194.52 | 365.66 | 828.86 | 2225.05 | 199.11 | 0.00 | 0.00 | 744.00 |
September | 1099.99 | 377.37 | 722.62 | 1931.02 | 259.78 | 0.00 | 0.00 | 720.00 |
October | 1126.14 | 486.60 | 639.54 | 1878.00 | 480.74 | 0.00 | 0.00 | 744.00 |
November | 965.19 | 485.05 | 480.14 | 1269.79 | 1027.39 | 0.00 | 0.00 | 720.00 |
December | 928.45 | 493.73 | 434.72 | 1104.61 | 1353.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1135.92 | 468.79 | 667.13 | 1751.77 | 723.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 928.45 | 327.66 | 434.72 | 1104.61 | 144.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1400.99 | 644.52 | 853.68 | 2402.31 | 1559.59 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 553.86 | 0.00 | 553.86 | 370.33 | 2164.45 | 0.00 | 0.00 | 744.00 |
February | 653.42 | 0.00 | 653.42 | 485.59 | 1804.47 | 0.00 | 0.00 | 672.00 |
March | 758.02 | 0.00 | 758.02 | 700.33 | 1579.58 | 0.00 | 0.00 | 744.00 |
April | 894.59 | 3.62 | 890.96 | 1108.21 | 996.51 | 0.00 | 0.00 | 720.00 |
May | 1013.18 | 36.90 | 976.28 | 1905.14 | 293.64 | 0.00 | 0.00 | 744.00 |
June | 1152.13 | 79.54 | 1072.60 | 2237.33 | 255.89 | 0.00 | 0.00 | 720.00 |
July | 1118.15 | 42.44 | 1075.71 | 2182.39 | 172.13 | 0.00 | 0.00 | 744.00 |
August | 1001.42 | 7.82 | 993.60 | 2028.92 | 235.45 | 0.00 | 0.00 | 744.00 |
September | 865.05 | 0.06 | 864.98 | 1603.11 | 330.15 | 0.00 | 0.00 | 720.00 |
October | 751.71 | 0.00 | 751.71 | 1295.79 | 611.88 | 0.00 | 0.00 | 744.00 |
November | 570.67 | 0.00 | 570.67 | 578.32 | 1350.33 | 0.00 | 0.00 | 720.00 |
December | 514.87 | 0.00 | 514.87 | 402.70 | 1840.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 821.42 | 14.24 | 807.17 | 1246.19 | 965.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 514.87 | 0.00 | 514.87 | 370.33 | 172.13 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1152.13 | 79.54 | 1075.71 | 2237.33 | 2164.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 950.25 | 483.86 | 466.39 | 1000.16 | 1327.88 | 0.00 | 0.00 | 744.00 |
February | 1058.12 | 510.81 | 547.31 | 1173.13 | 1116.77 | 0.00 | 0.00 | 672.00 |
March | 1244.84 | 600.40 | 644.44 | 1525.35 | 995.97 | 0.00 | 0.00 | 744.00 |
April | 1366.01 | 617.84 | 748.17 | 1914.03 | 651.95 | 0.00 | 0.00 | 720.00 |
May | 1407.91 | 610.48 | 797.43 | 2463.85 | 203.20 | 0.00 | 0.00 | 744.00 |
June | 1427.84 | 566.21 | 861.63 | 2592.50 | 176.25 | 0.00 | 0.00 | 720.00 |
July | 1376.66 | 503.76 | 872.89 | 2501.80 | 117.21 | 0.00 | 0.00 | 744.00 |
August | 1268.58 | 436.15 | 832.43 | 2310.87 | 160.31 | 0.00 | 0.00 | 744.00 |
September | 1123.77 | 386.38 | 737.39 | 1934.29 | 221.25 | 0.00 | 0.00 | 720.00 |
October | 1110.47 | 468.62 | 641.86 | 1796.87 | 399.92 | 0.00 | 0.00 | 744.00 |
November | 983.12 | 501.51 | 481.61 | 1225.31 | 853.23 | 0.00 | 0.00 | 720.00 |
December | 774.05 | 350.61 | 423.44 | 840.15 | 1158.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1174.70 | 502.83 | 671.87 | 1776.56 | 612.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 774.05 | 350.61 | 423.44 | 840.15 | 117.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1427.84 | 617.84 | 872.89 | 2592.50 | 1327.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3202.35 | 2284.10 | 918.25 | 4224.49 | 2087.69 | 0.00 | 0.00 | 744.00 |
February | 2903.75 | 1879.63 | 1024.12 | 3791.51 | 1793.95 | 0.00 | 0.00 | 672.00 |
March | 1853.11 | 836.01 | 1017.10 | 2281.19 | 1609.53 | 0.00 | 0.00 | 744.00 |
April | 1373.31 | 321.34 | 1051.97 | 1736.52 | 1041.31 | 0.00 | 0.00 | 720.00 |
May | 1049.35 | 44.20 | 1005.15 | 1935.33 | 308.73 | 0.00 | 0.00 | 744.00 |
June | 1036.79 | 9.46 | 1027.32 | 2077.63 | 268.66 | 0.00 | 0.00 | 720.00 |
July | 1085.29 | 19.69 | 1065.61 | 2130.29 | 173.63 | 0.00 | 0.00 | 744.00 |
August | 1276.67 | 152.86 | 1123.81 | 2387.73 | 255.65 | 0.00 | 0.00 | 744.00 |
September | 1531.93 | 403.45 | 1128.48 | 2591.33 | 367.67 | 0.00 | 0.00 | 720.00 |
October | 2377.18 | 1238.18 | 1139.00 | 3856.34 | 688.87 | 0.00 | 0.00 | 744.00 |
November | 3026.11 | 2083.73 | 942.38 | 4347.93 | 1413.16 | 0.00 | 0.00 | 720.00 |
December | 3129.17 | 2247.49 | 881.69 | 4370.57 | 1851.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1982.23 | 955.25 | 1026.98 | 2974.05 | 984.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1036.79 | 9.46 | 881.69 | 1736.52 | 173.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3202.35 | 2284.10 | 1139.00 | 4370.57 | 2087.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1010.74 | 546.54 | 464.20 | 1146.02 | 1470.41 | 0.00 | 0.00 | 744.00 |
February | 1144.37 | 579.19 | 565.18 | 1350.30 | 1252.16 | 0.00 | 0.00 | 672.00 |
March | 1127.98 | 499.35 | 628.63 | 1397.26 | 1105.75 | 0.00 | 0.00 | 744.00 |
April | 1400.99 | 644.52 | 756.47 | 2004.85 | 740.88 | 0.00 | 0.00 | 720.00 |
May | 1164.99 | 379.47 | 785.52 | 2092.77 | 240.55 | 0.00 | 0.00 | 744.00 |
June | 1294.18 | 453.77 | 840.40 | 2378.06 | 217.08 | 0.00 | 0.00 | 720.00 |
July | 1181.34 | 327.66 | 853.68 | 2165.68 | 150.73 | 0.00 | 0.00 | 744.00 |
August | 1194.52 | 365.66 | 828.86 | 2202.89 | 203.41 | 0.00 | 0.00 | 744.00 |
September | 1099.99 | 377.37 | 722.62 | 1913.36 | 261.10 | 0.00 | 0.00 | 720.00 |
October | 1126.14 | 486.60 | 639.54 | 1868.19 | 467.36 | 0.00 | 0.00 | 744.00 |
November | 965.19 | 485.05 | 480.14 | 1279.73 | 966.07 | 0.00 | 0.00 | 720.00 |
December | 928.45 | 493.73 | 434.72 | 1115.30 | 1273.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1135.92 | 468.79 | 667.13 | 1744.44 | 692.79 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 928.45 | 327.66 | 434.72 | 1115.30 | 150.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1400.99 | 644.52 | 853.68 | 2378.06 | 1470.41 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296695E+09 | 0.00 | 0.296695E+09 | 0.147938E+09 | 0.142464E+10 |
February | 0.316154E+09 | 0.00 | 0.316154E+09 | 0.189561E+09 | 0.109377E+10 |
March | 0.406063E+09 | 0.00 | 0.406063E+09 | 0.327444E+09 | 0.103109E+10 |
April | 0.463760E+09 | 1879069.97 | 0.461881E+09 | 0.550251E+09 | 0.596216E+09 |
May | 0.542745E+09 | 19765215.61 | 0.522979E+09 | 0.102794E+10 | 0.162750E+09 |
June | 0.597273E+09 | 41232738.58 | 0.556040E+09 | 0.117103E+10 | 0.125508E+09 |
July | 0.598980E+09 | 22734255.21 | 0.576246E+09 | 0.118383E+10 | 80148714.55 |
August | 0.536445E+09 | 4187625.18 | 0.532257E+09 | 0.109013E+10 | 0.118424E+09 |
September | 0.448446E+09 | 33570.01 | 0.448413E+09 | 0.835159E+09 | 0.190299E+09 |
October | 0.402681E+09 | 0.00 | 0.402681E+09 | 0.680294E+09 | 0.379109E+09 |
November | 0.295838E+09 | 0.00 | 0.295838E+09 | 0.251397E+09 | 0.889039E+09 |
December | 0.275812E+09 | 0.00 | 0.275812E+09 | 0.164277E+09 | 0.126522E+10 |
Annual Sum or Average | 0.518089E+10 | 89832474.54 | 0.509106E+10 | 0.761926E+10 | 0.735622E+10 |
Minimum of Months | 0.275812E+09 | 0.00 | 0.275812E+09 | 0.147938E+09 | 80148714.55 |
Maximum of Months | 0.598980E+09 | 41232738.58 | 0.576246E+09 | 0.118383E+10 | 0.142464E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296695E+09 | 0.00 | 0.296695E+09 | 0.147938E+09 | 0.142464E+10 |
February | 0.316154E+09 | 0.00 | 0.316154E+09 | 0.189561E+09 | 0.109377E+10 |
March | 0.406063E+09 | 0.00 | 0.406063E+09 | 0.327444E+09 | 0.103109E+10 |
April | 0.463760E+09 | 1879067.71 | 0.461881E+09 | 0.550251E+09 | 0.596216E+09 |
May | 0.542744E+09 | 19765191.89 | 0.522979E+09 | 0.102794E+10 | 0.162749E+09 |
June | 0.597272E+09 | 41232689.10 | 0.556040E+09 | 0.117103E+10 | 0.125508E+09 |
July | 0.598979E+09 | 22734227.93 | 0.576245E+09 | 0.118383E+10 | 80148617.15 |
August | 0.536445E+09 | 4187620.15 | 0.532257E+09 | 0.109013E+10 | 0.118424E+09 |
September | 0.448446E+09 | 33569.97 | 0.448412E+09 | 0.835159E+09 | 0.190299E+09 |
October | 0.402681E+09 | 0.00 | 0.402681E+09 | 0.680294E+09 | 0.379109E+09 |
November | 0.295838E+09 | 0.00 | 0.295838E+09 | 0.251397E+09 | 0.889039E+09 |
December | 0.275811E+09 | 0.00 | 0.275811E+09 | 0.164276E+09 | 0.126522E+10 |
Annual Sum or Average | 0.518089E+10 | 89832366.75 | 0.509106E+10 | 0.761926E+10 | 0.735621E+10 |
Minimum of Months | 0.275811E+09 | 0.00 | 0.275811E+09 | 0.147938E+09 | 80148617.15 |
Maximum of Months | 0.598979E+09 | 41232689.10 | 0.576245E+09 | 0.118383E+10 | 0.142464E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296695E+09 | 0.00 | 0.296695E+09 | 0.147938E+09 | 0.142464E+10 |
February | 0.316154E+09 | 0.00 | 0.316154E+09 | 0.189561E+09 | 0.109377E+10 |
March | 0.406063E+09 | 0.00 | 0.406063E+09 | 0.327444E+09 | 0.103109E+10 |
April | 0.463760E+09 | 1879069.97 | 0.461881E+09 | 0.550251E+09 | 0.596216E+09 |
May | 0.542745E+09 | 19765215.61 | 0.522979E+09 | 0.102794E+10 | 0.162750E+09 |
June | 0.597273E+09 | 41232738.58 | 0.556040E+09 | 0.117103E+10 | 0.125508E+09 |
July | 0.598980E+09 | 22734255.21 | 0.576246E+09 | 0.118383E+10 | 80148714.55 |
August | 0.536445E+09 | 4187625.18 | 0.532257E+09 | 0.109013E+10 | 0.118424E+09 |
September | 0.448446E+09 | 33570.01 | 0.448413E+09 | 0.835159E+09 | 0.190299E+09 |
October | 0.402681E+09 | 0.00 | 0.402681E+09 | 0.680294E+09 | 0.379109E+09 |
November | 0.295838E+09 | 0.00 | 0.295838E+09 | 0.251397E+09 | 0.889039E+09 |
December | 0.275812E+09 | 0.00 | 0.275812E+09 | 0.164277E+09 | 0.126522E+10 |
Annual Sum or Average | 0.518089E+10 | 89832474.54 | 0.509106E+10 | 0.761926E+10 | 0.735622E+10 |
Minimum of Months | 0.275812E+09 | 0.00 | 0.275812E+09 | 0.147938E+09 | 80148714.55 |
Maximum of Months | 0.598980E+09 | 41232738.58 | 0.576246E+09 | 0.118383E+10 | 0.142464E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296695E+09 | 0.00 | 0.296695E+09 | 0.147938E+09 | 0.142464E+10 |
February | 0.316154E+09 | 0.00 | 0.316154E+09 | 0.189561E+09 | 0.109377E+10 |
March | 0.406063E+09 | 0.00 | 0.406063E+09 | 0.327444E+09 | 0.103109E+10 |
April | 0.463760E+09 | 1879067.71 | 0.461881E+09 | 0.550251E+09 | 0.596216E+09 |
May | 0.542744E+09 | 19765191.89 | 0.522979E+09 | 0.102794E+10 | 0.162749E+09 |
June | 0.597272E+09 | 41232689.10 | 0.556040E+09 | 0.117103E+10 | 0.125508E+09 |
July | 0.598979E+09 | 22734227.93 | 0.576245E+09 | 0.118383E+10 | 80148617.15 |
August | 0.536445E+09 | 4187620.15 | 0.532257E+09 | 0.109013E+10 | 0.118424E+09 |
September | 0.448446E+09 | 33569.97 | 0.448412E+09 | 0.835159E+09 | 0.190299E+09 |
October | 0.402681E+09 | 0.00 | 0.402681E+09 | 0.680294E+09 | 0.379109E+09 |
November | 0.295838E+09 | 0.00 | 0.295838E+09 | 0.251397E+09 | 0.889039E+09 |
December | 0.275811E+09 | 0.00 | 0.275811E+09 | 0.164276E+09 | 0.126522E+10 |
Annual Sum or Average | 0.518089E+10 | 89832366.75 | 0.509106E+10 | 0.761926E+10 | 0.735621E+10 |
Minimum of Months | 0.275811E+09 | 0.00 | 0.275811E+09 | 0.147938E+09 | 80148617.15 |
Maximum of Months | 0.598979E+09 | 41232689.10 | 0.576245E+09 | 0.118383E+10 | 0.142464E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296683E+09 | 0.00 | 0.296683E+09 | 0.147932E+09 | 0.142458E+10 |
February | 0.316142E+09 | 0.00 | 0.316142E+09 | 0.189553E+09 | 0.109373E+10 |
March | 0.406047E+09 | 0.00 | 0.406047E+09 | 0.327431E+09 | 0.103105E+10 |
April | 0.463741E+09 | 1878994.23 | 0.461862E+09 | 0.550229E+09 | 0.596192E+09 |
May | 0.542723E+09 | 19764418.98 | 0.522958E+09 | 0.102790E+10 | 0.162743E+09 |
June | 0.597249E+09 | 41231076.72 | 0.556018E+09 | 0.117099E+10 | 0.125503E+09 |
July | 0.598956E+09 | 22733338.92 | 0.576222E+09 | 0.118379E+10 | 80145484.20 |
August | 0.536423E+09 | 4187456.40 | 0.532236E+09 | 0.109009E+10 | 0.118420E+09 |
September | 0.448428E+09 | 33568.66 | 0.448395E+09 | 0.835125E+09 | 0.190291E+09 |
October | 0.402665E+09 | 0.00 | 0.402665E+09 | 0.680267E+09 | 0.379094E+09 |
November | 0.295826E+09 | 0.00 | 0.295826E+09 | 0.251387E+09 | 0.889003E+09 |
December | 0.275800E+09 | 0.00 | 0.275800E+09 | 0.164270E+09 | 0.126517E+10 |
Annual Sum or Average | 0.518068E+10 | 89828853.90 | 0.509085E+10 | 0.761896E+10 | 0.735592E+10 |
Minimum of Months | 0.275800E+09 | 0.00 | 0.275800E+09 | 0.147932E+09 | 80145484.20 |
Maximum of Months | 0.598956E+09 | 41231076.72 | 0.576222E+09 | 0.118379E+10 | 0.142458E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.848392E+09 | 0.431995E+09 | 0.416398E+09 | 0.830236E+09 | 0.140513E+10 |
February | 0.853275E+09 | 0.411921E+09 | 0.441354E+09 | 0.898924E+09 | 0.106652E+10 |
March | 0.111141E+10 | 0.536045E+09 | 0.575360E+09 | 0.134442E+10 | 0.100687E+10 |
April | 0.118025E+10 | 0.533818E+09 | 0.646429E+09 | 0.167148E+10 | 0.585906E+09 |
May | 0.125700E+10 | 0.545047E+09 | 0.711953E+09 | 0.224350E+10 | 0.173337E+09 |
June | 0.123366E+10 | 0.489211E+09 | 0.744453E+09 | 0.228617E+10 | 0.123283E+09 |
July | 0.122909E+10 | 0.449764E+09 | 0.779328E+09 | 0.229331E+10 | 66896021.31 |
August | 0.113260E+10 | 0.389400E+09 | 0.743200E+09 | 0.211329E+10 | 0.100216E+09 |
September | 0.970948E+09 | 0.333835E+09 | 0.637113E+09 | 0.170082E+10 | 0.195481E+09 |
October | 0.991440E+09 | 0.418385E+09 | 0.573055E+09 | 0.162337E+10 | 0.377508E+09 |
November | 0.849426E+09 | 0.433309E+09 | 0.416117E+09 | 0.102664E+10 | 0.857948E+09 |
December | 0.691082E+09 | 0.313029E+09 | 0.378053E+09 | 0.699676E+09 | 0.122854E+10 |
Annual Sum or Average | 0.123486E+11 | 0.528576E+10 | 0.706281E+10 | 0.187318E+11 | 0.718763E+10 |
Minimum of Months | 0.691082E+09 | 0.313029E+09 | 0.378053E+09 | 0.699676E+09 | 66896021.31 |
Maximum of Months | 0.125700E+10 | 0.545047E+09 | 0.779328E+09 | 0.229331E+10 | 0.140513E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.848392E+09 | 0.431995E+09 | 0.416398E+09 | 0.830236E+09 | 0.140513E+10 |
February | 0.853275E+09 | 0.411921E+09 | 0.441354E+09 | 0.898924E+09 | 0.106652E+10 |
March | 0.111141E+10 | 0.536045E+09 | 0.575360E+09 | 0.134442E+10 | 0.100687E+10 |
April | 0.118025E+10 | 0.533818E+09 | 0.646429E+09 | 0.167148E+10 | 0.585906E+09 |
May | 0.125700E+10 | 0.545047E+09 | 0.711953E+09 | 0.224350E+10 | 0.173337E+09 |
June | 0.123366E+10 | 0.489211E+09 | 0.744453E+09 | 0.228617E+10 | 0.123283E+09 |
July | 0.122909E+10 | 0.449764E+09 | 0.779328E+09 | 0.229331E+10 | 66896021.31 |
August | 0.113260E+10 | 0.389400E+09 | 0.743200E+09 | 0.211329E+10 | 0.100216E+09 |
September | 0.970948E+09 | 0.333835E+09 | 0.637113E+09 | 0.170082E+10 | 0.195481E+09 |
October | 0.991440E+09 | 0.418385E+09 | 0.573055E+09 | 0.162337E+10 | 0.377508E+09 |
November | 0.849426E+09 | 0.433309E+09 | 0.416117E+09 | 0.102664E+10 | 0.857948E+09 |
December | 0.691082E+09 | 0.313029E+09 | 0.378053E+09 | 0.699676E+09 | 0.122854E+10 |
Annual Sum or Average | 0.123486E+11 | 0.528576E+10 | 0.706281E+10 | 0.187318E+11 | 0.718763E+10 |
Minimum of Months | 0.691082E+09 | 0.313029E+09 | 0.378053E+09 | 0.699676E+09 | 66896021.31 |
Maximum of Months | 0.125700E+10 | 0.545047E+09 | 0.779328E+09 | 0.229331E+10 | 0.140513E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.848377E+09 | 0.431987E+09 | 0.416390E+09 | 0.830221E+09 | 0.140510E+10 |
February | 0.853259E+09 | 0.411913E+09 | 0.441346E+09 | 0.898907E+09 | 0.106650E+10 |
March | 0.111139E+10 | 0.536035E+09 | 0.575350E+09 | 0.134439E+10 | 0.100685E+10 |
April | 0.118023E+10 | 0.533809E+09 | 0.646418E+09 | 0.167145E+10 | 0.585896E+09 |
May | 0.125698E+10 | 0.545037E+09 | 0.711940E+09 | 0.224346E+10 | 0.173334E+09 |
June | 0.123364E+10 | 0.489202E+09 | 0.744439E+09 | 0.228613E+10 | 0.123280E+09 |
July | 0.122907E+10 | 0.449755E+09 | 0.779313E+09 | 0.229327E+10 | 66894798.98 |
August | 0.113258E+10 | 0.389393E+09 | 0.743187E+09 | 0.211325E+10 | 0.100214E+09 |
September | 0.970930E+09 | 0.333829E+09 | 0.637101E+09 | 0.170079E+10 | 0.195478E+09 |
October | 0.991421E+09 | 0.418377E+09 | 0.573044E+09 | 0.162334E+10 | 0.377501E+09 |
November | 0.849411E+09 | 0.433301E+09 | 0.416110E+09 | 0.102662E+10 | 0.857932E+09 |
December | 0.691069E+09 | 0.313024E+09 | 0.378046E+09 | 0.699664E+09 | 0.122852E+10 |
Annual Sum or Average | 0.123483E+11 | 0.528566E+10 | 0.706268E+10 | 0.187315E+11 | 0.718749E+10 |
Minimum of Months | 0.691069E+09 | 0.313024E+09 | 0.378046E+09 | 0.699664E+09 | 66894798.98 |
Maximum of Months | 0.125698E+10 | 0.545037E+09 | 0.779313E+09 | 0.229327E+10 | 0.140510E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171546E+10 | 0.122356E+10 | 0.491895E+09 | 0.226586E+10 | 0.123141E+10 |
February | 0.140497E+10 | 0.909452E+09 | 0.495514E+09 | 0.182919E+10 | 0.967872E+09 |
March | 0.992684E+09 | 0.447837E+09 | 0.544847E+09 | 0.121127E+10 | 0.968225E+09 |
April | 0.711930E+09 | 0.166583E+09 | 0.545347E+09 | 0.891051E+09 | 0.588942E+09 |
May | 0.562122E+09 | 23675206.03 | 0.538447E+09 | 0.104508E+10 | 0.166795E+09 |
June | 0.537477E+09 | 4905599.62 | 0.532571E+09 | 0.108669E+10 | 0.130519E+09 |
July | 0.581378E+09 | 10546313.97 | 0.570831E+09 | 0.115435E+10 | 80882230.12 |
August | 0.683894E+09 | 81882563.40 | 0.602011E+09 | 0.128771E+10 | 0.125383E+09 |
September | 0.794161E+09 | 0.209149E+09 | 0.585012E+09 | 0.135939E+10 | 0.197645E+09 |
October | 0.127342E+10 | 0.663276E+09 | 0.610145E+09 | 0.208892E+10 | 0.385304E+09 |
November | 0.156875E+10 | 0.108022E+10 | 0.488533E+09 | 0.225798E+10 | 0.806825E+09 |
December | 0.167626E+10 | 0.120395E+10 | 0.472308E+09 | 0.233770E+10 | 0.111551E+10 |
Annual Sum or Average | 0.125025E+11 | 0.602504E+10 | 0.647746E+10 | 0.188152E+11 | 0.676532E+10 |
Minimum of Months | 0.537477E+09 | 4905599.62 | 0.472308E+09 | 0.891051E+09 | 80882230.12 |
Maximum of Months | 0.171546E+10 | 0.122356E+10 | 0.610145E+09 | 0.233770E+10 | 0.123141E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171546E+10 | 0.122356E+10 | 0.491894E+09 | 0.226585E+10 | 0.123141E+10 |
February | 0.140496E+10 | 0.909451E+09 | 0.495514E+09 | 0.182919E+10 | 0.967872E+09 |
March | 0.992683E+09 | 0.447836E+09 | 0.544847E+09 | 0.121127E+10 | 0.968225E+09 |
April | 0.711930E+09 | 0.166583E+09 | 0.545347E+09 | 0.891050E+09 | 0.588941E+09 |
May | 0.562121E+09 | 23675177.63 | 0.538446E+09 | 0.104508E+10 | 0.166795E+09 |
June | 0.537476E+09 | 4905593.74 | 0.532571E+09 | 0.108669E+10 | 0.130518E+09 |
July | 0.581377E+09 | 10546301.31 | 0.570831E+09 | 0.115435E+10 | 80882135.25 |
August | 0.683893E+09 | 81882465.15 | 0.602011E+09 | 0.128771E+10 | 0.125383E+09 |
September | 0.794160E+09 | 0.209149E+09 | 0.585011E+09 | 0.135938E+10 | 0.197645E+09 |
October | 0.127342E+10 | 0.663276E+09 | 0.610144E+09 | 0.208892E+10 | 0.385304E+09 |
November | 0.156875E+10 | 0.108022E+10 | 0.488533E+09 | 0.225798E+10 | 0.806825E+09 |
December | 0.167625E+10 | 0.120395E+10 | 0.472307E+09 | 0.233769E+10 | 0.111551E+10 |
Annual Sum or Average | 0.125025E+11 | 0.602503E+10 | 0.647746E+10 | 0.188152E+11 | 0.676532E+10 |
Minimum of Months | 0.537476E+09 | 4905593.74 | 0.472307E+09 | 0.891050E+09 | 80882135.25 |
Maximum of Months | 0.171546E+10 | 0.122356E+10 | 0.610144E+09 | 0.233769E+10 | 0.123141E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171546E+10 | 0.122356E+10 | 0.491895E+09 | 0.226586E+10 | 0.123141E+10 |
February | 0.140497E+10 | 0.909452E+09 | 0.495514E+09 | 0.182919E+10 | 0.967872E+09 |
March | 0.992684E+09 | 0.447837E+09 | 0.544847E+09 | 0.121127E+10 | 0.968225E+09 |
April | 0.711930E+09 | 0.166583E+09 | 0.545347E+09 | 0.891051E+09 | 0.588942E+09 |
May | 0.562122E+09 | 23675206.03 | 0.538447E+09 | 0.104508E+10 | 0.166795E+09 |
June | 0.537477E+09 | 4905599.62 | 0.532571E+09 | 0.108669E+10 | 0.130519E+09 |
July | 0.581378E+09 | 10546313.97 | 0.570831E+09 | 0.115435E+10 | 80882230.12 |
August | 0.683894E+09 | 81882563.40 | 0.602011E+09 | 0.128771E+10 | 0.125383E+09 |
September | 0.794161E+09 | 0.209149E+09 | 0.585012E+09 | 0.135939E+10 | 0.197645E+09 |
October | 0.127342E+10 | 0.663276E+09 | 0.610145E+09 | 0.208892E+10 | 0.385304E+09 |
November | 0.156875E+10 | 0.108022E+10 | 0.488533E+09 | 0.225798E+10 | 0.806825E+09 |
December | 0.167626E+10 | 0.120395E+10 | 0.472308E+09 | 0.233770E+10 | 0.111551E+10 |
Annual Sum or Average | 0.125025E+11 | 0.602504E+10 | 0.647746E+10 | 0.188152E+11 | 0.676532E+10 |
Minimum of Months | 0.537477E+09 | 4905599.62 | 0.472308E+09 | 0.891051E+09 | 80882230.12 |
Maximum of Months | 0.171546E+10 | 0.122356E+10 | 0.610145E+09 | 0.233770E+10 | 0.123141E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171546E+10 | 0.122356E+10 | 0.491894E+09 | 0.226585E+10 | 0.123141E+10 |
February | 0.140496E+10 | 0.909451E+09 | 0.495514E+09 | 0.182919E+10 | 0.967872E+09 |
March | 0.992683E+09 | 0.447836E+09 | 0.544847E+09 | 0.121127E+10 | 0.968225E+09 |
April | 0.711930E+09 | 0.166583E+09 | 0.545347E+09 | 0.891050E+09 | 0.588941E+09 |
May | 0.562121E+09 | 23675177.63 | 0.538446E+09 | 0.104508E+10 | 0.166795E+09 |
June | 0.537476E+09 | 4905593.74 | 0.532571E+09 | 0.108669E+10 | 0.130518E+09 |
July | 0.581377E+09 | 10546301.31 | 0.570831E+09 | 0.115435E+10 | 80882135.25 |
August | 0.683893E+09 | 81882465.15 | 0.602011E+09 | 0.128771E+10 | 0.125383E+09 |
September | 0.794160E+09 | 0.209149E+09 | 0.585011E+09 | 0.135938E+10 | 0.197645E+09 |
October | 0.127342E+10 | 0.663276E+09 | 0.610144E+09 | 0.208892E+10 | 0.385304E+09 |
November | 0.156875E+10 | 0.108022E+10 | 0.488533E+09 | 0.225798E+10 | 0.806825E+09 |
December | 0.167625E+10 | 0.120395E+10 | 0.472307E+09 | 0.233769E+10 | 0.111551E+10 |
Annual Sum or Average | 0.125025E+11 | 0.602503E+10 | 0.647746E+10 | 0.188152E+11 | 0.676532E+10 |
Minimum of Months | 0.537476E+09 | 4905593.74 | 0.472307E+09 | 0.891050E+09 | 80882135.25 |
Maximum of Months | 0.171546E+10 | 0.122356E+10 | 0.610144E+09 | 0.233769E+10 | 0.123141E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171539E+10 | 0.122351E+10 | 0.491875E+09 | 0.226576E+10 | 0.123136E+10 |
February | 0.140491E+10 | 0.909415E+09 | 0.495494E+09 | 0.182912E+10 | 0.967833E+09 |
March | 0.992644E+09 | 0.447819E+09 | 0.544825E+09 | 0.121122E+10 | 0.968186E+09 |
April | 0.711902E+09 | 0.166576E+09 | 0.545325E+09 | 0.891015E+09 | 0.588918E+09 |
May | 0.562099E+09 | 23674251.82 | 0.538425E+09 | 0.104504E+10 | 0.166788E+09 |
June | 0.537455E+09 | 4905401.90 | 0.532550E+09 | 0.108664E+10 | 0.130513E+09 |
July | 0.581354E+09 | 10545888.91 | 0.570808E+09 | 0.115431E+10 | 80878970.21 |
August | 0.683866E+09 | 81879263.17 | 0.601987E+09 | 0.128766E+10 | 0.125378E+09 |
September | 0.794129E+09 | 0.209141E+09 | 0.584988E+09 | 0.135933E+10 | 0.197637E+09 |
October | 0.127337E+10 | 0.663250E+09 | 0.610120E+09 | 0.208884E+10 | 0.385288E+09 |
November | 0.156869E+10 | 0.108018E+10 | 0.488514E+09 | 0.225789E+10 | 0.806792E+09 |
December | 0.167619E+10 | 0.120390E+10 | 0.472288E+09 | 0.233760E+10 | 0.111547E+10 |
Annual Sum or Average | 0.125020E+11 | 0.602480E+10 | 0.647720E+10 | 0.188144E+11 | 0.676505E+10 |
Minimum of Months | 0.537455E+09 | 4905401.90 | 0.472288E+09 | 0.891015E+09 | 80878970.21 |
Maximum of Months | 0.171539E+10 | 0.122351E+10 | 0.610120E+09 | 0.233760E+10 | 0.123136E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.902397E+09 | 0.487956E+09 | 0.414441E+09 | 0.967964E+09 | 0.158709E+10 |
February | 0.922832E+09 | 0.467066E+09 | 0.455767E+09 | 0.102698E+10 | 0.128018E+10 |
March | 0.100707E+10 | 0.445824E+09 | 0.561242E+09 | 0.117914E+10 | 0.127345E+10 |
April | 0.121047E+10 | 0.556873E+09 | 0.653598E+09 | 0.167851E+10 | 0.808666E+09 |
May | 0.104012E+10 | 0.338797E+09 | 0.701320E+09 | 0.186257E+10 | 0.249233E+09 |
June | 0.111818E+10 | 0.392064E+09 | 0.726116E+09 | 0.204194E+10 | 0.217281E+09 |
July | 0.105472E+10 | 0.292540E+09 | 0.762176E+09 | 0.190150E+10 | 0.169952E+09 |
August | 0.106648E+10 | 0.326464E+09 | 0.740017E+09 | 0.192011E+10 | 0.242617E+09 |
September | 0.950401E+09 | 0.326054E+09 | 0.624347E+09 | 0.164534E+10 | 0.276226E+09 |
October | 0.100543E+10 | 0.434440E+09 | 0.570987E+09 | 0.163595E+10 | 0.517120E+09 |
November | 0.833932E+09 | 0.419086E+09 | 0.414846E+09 | 0.103087E+10 | 0.111018E+10 |
December | 0.828929E+09 | 0.440808E+09 | 0.388121E+09 | 0.911075E+09 | 0.154999E+10 |
Annual Sum or Average | 0.119409E+11 | 0.492797E+10 | 0.701298E+10 | 0.178020E+11 | 0.928199E+10 |
Minimum of Months | 0.828929E+09 | 0.292540E+09 | 0.388121E+09 | 0.911075E+09 | 0.169952E+09 |
Maximum of Months | 0.121047E+10 | 0.556873E+09 | 0.762176E+09 | 0.204194E+10 | 0.158709E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.902397E+09 | 0.487956E+09 | 0.414441E+09 | 0.967964E+09 | 0.158709E+10 |
February | 0.922832E+09 | 0.467066E+09 | 0.455767E+09 | 0.102698E+10 | 0.128018E+10 |
March | 0.100707E+10 | 0.445824E+09 | 0.561242E+09 | 0.117914E+10 | 0.127345E+10 |
April | 0.121047E+10 | 0.556873E+09 | 0.653598E+09 | 0.167851E+10 | 0.808666E+09 |
May | 0.104012E+10 | 0.338797E+09 | 0.701320E+09 | 0.186257E+10 | 0.249233E+09 |
June | 0.111818E+10 | 0.392064E+09 | 0.726116E+09 | 0.204194E+10 | 0.217281E+09 |
July | 0.105472E+10 | 0.292540E+09 | 0.762176E+09 | 0.190150E+10 | 0.169952E+09 |
August | 0.106648E+10 | 0.326464E+09 | 0.740017E+09 | 0.192011E+10 | 0.242617E+09 |
September | 0.950401E+09 | 0.326054E+09 | 0.624347E+09 | 0.164534E+10 | 0.276226E+09 |
October | 0.100543E+10 | 0.434440E+09 | 0.570987E+09 | 0.163595E+10 | 0.517120E+09 |
November | 0.833932E+09 | 0.419086E+09 | 0.414846E+09 | 0.103087E+10 | 0.111018E+10 |
December | 0.828929E+09 | 0.440808E+09 | 0.388121E+09 | 0.911075E+09 | 0.154999E+10 |
Annual Sum or Average | 0.119409E+11 | 0.492797E+10 | 0.701298E+10 | 0.178020E+11 | 0.928199E+10 |
Minimum of Months | 0.828929E+09 | 0.292540E+09 | 0.388121E+09 | 0.911075E+09 | 0.169952E+09 |
Maximum of Months | 0.121047E+10 | 0.556873E+09 | 0.762176E+09 | 0.204194E+10 | 0.158709E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.902381E+09 | 0.487947E+09 | 0.414433E+09 | 0.967946E+09 | 0.158706E+10 |
February | 0.922815E+09 | 0.467057E+09 | 0.455758E+09 | 0.102696E+10 | 0.128015E+10 |
March | 0.100705E+10 | 0.445816E+09 | 0.561232E+09 | 0.117912E+10 | 0.127343E+10 |
April | 0.121045E+10 | 0.556863E+09 | 0.653586E+09 | 0.167848E+10 | 0.808651E+09 |
May | 0.104010E+10 | 0.338791E+09 | 0.701307E+09 | 0.186254E+10 | 0.249228E+09 |
June | 0.111816E+10 | 0.392057E+09 | 0.726103E+09 | 0.204190E+10 | 0.217277E+09 |
July | 0.105470E+10 | 0.292534E+09 | 0.762162E+09 | 0.190146E+10 | 0.169949E+09 |
August | 0.106646E+10 | 0.326458E+09 | 0.740004E+09 | 0.192008E+10 | 0.242613E+09 |
September | 0.950384E+09 | 0.326048E+09 | 0.624336E+09 | 0.164531E+10 | 0.276221E+09 |
October | 0.100541E+10 | 0.434432E+09 | 0.570976E+09 | 0.163592E+10 | 0.517110E+09 |
November | 0.833917E+09 | 0.419078E+09 | 0.414839E+09 | 0.103085E+10 | 0.111016E+10 |
December | 0.828913E+09 | 0.440800E+09 | 0.388114E+09 | 0.911059E+09 | 0.154996E+10 |
Annual Sum or Average | 0.119407E+11 | 0.492788E+10 | 0.701285E+10 | 0.178016E+11 | 0.928182E+10 |
Minimum of Months | 0.828913E+09 | 0.292534E+09 | 0.388114E+09 | 0.911059E+09 | 0.169949E+09 |
Maximum of Months | 0.121045E+10 | 0.556863E+09 | 0.762162E+09 | 0.204190E+10 | 0.158706E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148346E+10 | 0.00 | 0.148346E+10 | 0.915956E+09 | 0.624799E+10 |
February | 0.158075E+10 | 0.00 | 0.158075E+10 | 0.112646E+10 | 0.470850E+10 |
March | 0.203029E+10 | 0.00 | 0.203029E+10 | 0.184320E+10 | 0.447949E+10 |
April | 0.231877E+10 | 9395236.22 | 0.230938E+10 | 0.289084E+10 | 0.266083E+10 |
May | 0.271369E+10 | 98824883.04 | 0.261487E+10 | 0.520527E+10 | 0.746115E+09 |
June | 0.298633E+10 | 0.206161E+09 | 0.278017E+10 | 0.591392E+10 | 0.621245E+09 |
July | 0.299486E+10 | 0.113670E+09 | 0.288119E+10 | 0.597889E+10 | 0.418947E+09 |
August | 0.268219E+10 | 20937872.69 | 0.266126E+10 | 0.553836E+10 | 0.597916E+09 |
September | 0.224220E+10 | 167848.03 | 0.224204E+10 | 0.424883E+10 | 0.832449E+09 |
October | 0.201338E+10 | 0.00 | 0.201338E+10 | 0.351283E+10 | 0.168697E+10 |
November | 0.147917E+10 | 0.00 | 0.147917E+10 | 0.143886E+10 | 0.378949E+10 |
December | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.101493E+10 | 0.532795E+10 |
Annual Sum or Average | 0.259041E+11 | 0.449157E+09 | 0.254550E+11 | 0.396283E+11 | 0.321179E+11 |
Minimum of Months | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.915956E+09 | 0.418947E+09 |
Maximum of Months | 0.299486E+10 | 0.206161E+09 | 0.288119E+10 | 0.597889E+10 | 0.624799E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254515E+10 | 0.129597E+10 | 0.124918E+10 | 0.258841E+10 | 0.381274E+10 |
February | 0.255980E+10 | 0.123575E+10 | 0.132405E+10 | 0.278027E+10 | 0.288865E+10 |
March | 0.333418E+10 | 0.160812E+10 | 0.172606E+10 | 0.406499E+10 | 0.279202E+10 |
April | 0.354071E+10 | 0.160144E+10 | 0.193927E+10 | 0.498274E+10 | 0.172119E+10 |
May | 0.377096E+10 | 0.163512E+10 | 0.213584E+10 | 0.667383E+10 | 0.517537E+09 |
June | 0.370095E+10 | 0.146762E+10 | 0.223334E+10 | 0.679722E+10 | 0.427989E+09 |
July | 0.368724E+10 | 0.134928E+10 | 0.233796E+10 | 0.678917E+10 | 0.286646E+09 |
August | 0.339777E+10 | 0.116819E+10 | 0.222958E+10 | 0.626172E+10 | 0.407225E+09 |
September | 0.291281E+10 | 0.100149E+10 | 0.191132E+10 | 0.507698E+10 | 0.555867E+09 |
October | 0.297429E+10 | 0.125514E+10 | 0.171915E+10 | 0.484715E+10 | 0.109386E+10 |
November | 0.254825E+10 | 0.129991E+10 | 0.124834E+10 | 0.312760E+10 | 0.235616E+10 |
December | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.218733E+10 | 0.331921E+10 |
Annual Sum or Average | 0.370453E+11 | 0.158571E+11 | 0.211882E+11 | 0.561774E+11 | 0.201791E+11 |
Minimum of Months | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.218733E+10 | 0.286646E+09 |
Maximum of Months | 0.377096E+10 | 0.163512E+10 | 0.233796E+10 | 0.679722E+10 | 0.381274E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.857718E+10 | 0.611774E+10 | 0.245944E+10 | 0.112191E+11 | 0.598007E+10 |
February | 0.702474E+10 | 0.454720E+10 | 0.247754E+10 | 0.909489E+10 | 0.464074E+10 |
March | 0.496336E+10 | 0.223916E+10 | 0.272420E+10 | 0.608062E+10 | 0.454308E+10 |
April | 0.355961E+10 | 0.832905E+09 | 0.272670E+10 | 0.451716E+10 | 0.277198E+10 |
May | 0.281058E+10 | 0.118375E+09 | 0.269220E+10 | 0.527833E+10 | 0.784800E+09 |
June | 0.268735E+10 | 24527701.52 | 0.266282E+10 | 0.548872E+10 | 0.650381E+09 |
July | 0.290685E+10 | 52730932.22 | 0.285412E+10 | 0.583408E+10 | 0.422994E+09 |
August | 0.341943E+10 | 0.409408E+09 | 0.301002E+10 | 0.649153E+10 | 0.650855E+09 |
September | 0.397076E+10 | 0.104573E+10 | 0.292502E+10 | 0.679763E+10 | 0.930416E+09 |
October | 0.636703E+10 | 0.331634E+10 | 0.305069E+10 | 0.103708E+11 | 0.189052E+10 |
November | 0.784368E+10 | 0.540104E+10 | 0.244264E+10 | 0.112155E+11 | 0.388303E+10 |
December | 0.838118E+10 | 0.601967E+10 | 0.236151E+10 | 0.116237E+11 | 0.530632E+10 |
Annual Sum or Average | 0.625117E+11 | 0.301248E+11 | 0.323869E+11 | 0.940120E+11 | 0.324552E+11 |
Minimum of Months | 0.268735E+10 | 24527701.52 | 0.236151E+10 | 0.451716E+10 | 0.422994E+09 |
Maximum of Months | 0.857718E+10 | 0.611774E+10 | 0.305069E+10 | 0.116237E+11 | 0.598007E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270716E+10 | 0.146385E+10 | 0.124331E+10 | 0.303737E+10 | 0.417721E+10 |
February | 0.276847E+10 | 0.140118E+10 | 0.136729E+10 | 0.324720E+10 | 0.321902E+10 |
March | 0.302117E+10 | 0.133746E+10 | 0.168371E+10 | 0.373665E+10 | 0.310696E+10 |
April | 0.363138E+10 | 0.167060E+10 | 0.196077E+10 | 0.521796E+10 | 0.197783E+10 |
May | 0.312032E+10 | 0.101638E+10 | 0.210394E+10 | 0.566123E+10 | 0.630971E+09 |
June | 0.335451E+10 | 0.117618E+10 | 0.217833E+10 | 0.622679E+10 | 0.547847E+09 |
July | 0.316411E+10 | 0.877610E+09 | 0.228650E+10 | 0.587189E+10 | 0.388332E+09 |
August | 0.319941E+10 | 0.979382E+09 | 0.222003E+10 | 0.595958E+10 | 0.533287E+09 |
September | 0.285118E+10 | 0.978152E+09 | 0.187302E+10 | 0.500520E+10 | 0.673357E+09 |
October | 0.301625E+10 | 0.130331E+10 | 0.171294E+10 | 0.503004E+10 | 0.128760E+10 |
November | 0.250177E+10 | 0.125724E+10 | 0.124453E+10 | 0.329130E+10 | 0.266298E+10 |
December | 0.248676E+10 | 0.132241E+10 | 0.116435E+10 | 0.295859E+10 | 0.362519E+10 |
Annual Sum or Average | 0.358225E+11 | 0.147838E+11 | 0.210387E+11 | 0.552438E+11 | 0.228306E+11 |
Minimum of Months | 0.248676E+10 | 0.877610E+09 | 0.116435E+10 | 0.295859E+10 | 0.388332E+09 |
Maximum of Months | 0.363138E+10 | 0.167060E+10 | 0.228650E+10 | 0.622679E+10 | 0.417721E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148346E+10 | 0.00 | 0.148346E+10 | 0.991898E+09 | 0.579726E+10 |
February | 0.158075E+10 | 0.00 | 0.158075E+10 | 0.117475E+10 | 0.436538E+10 |
March | 0.203029E+10 | 0.00 | 0.203029E+10 | 0.187576E+10 | 0.423075E+10 |
April | 0.231877E+10 | 9395236.22 | 0.230938E+10 | 0.287249E+10 | 0.258296E+10 |
May | 0.271369E+10 | 98824883.04 | 0.261487E+10 | 0.510274E+10 | 0.786481E+09 |
June | 0.298633E+10 | 0.206161E+09 | 0.278017E+10 | 0.579917E+10 | 0.663276E+09 |
July | 0.299486E+10 | 0.113670E+09 | 0.288119E+10 | 0.584531E+10 | 0.461042E+09 |
August | 0.268219E+10 | 20937872.69 | 0.266126E+10 | 0.543426E+10 | 0.630625E+09 |
September | 0.224220E+10 | 167848.03 | 0.224204E+10 | 0.415525E+10 | 0.855747E+09 |
October | 0.201338E+10 | 0.00 | 0.201338E+10 | 0.347064E+10 | 0.163886E+10 |
November | 0.147917E+10 | 0.00 | 0.147917E+10 | 0.149899E+10 | 0.350006E+10 |
December | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.107858E+10 | 0.492902E+10 |
Annual Sum or Average | 0.259041E+11 | 0.449157E+09 | 0.254550E+11 | 0.392999E+11 | 0.304415E+11 |
Minimum of Months | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.991898E+09 | 0.461042E+09 |
Maximum of Months | 0.299486E+10 | 0.206161E+09 | 0.288119E+10 | 0.584531E+10 | 0.579726E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254515E+10 | 0.129597E+10 | 0.124918E+10 | 0.267882E+10 | 0.355659E+10 |
February | 0.255980E+10 | 0.123575E+10 | 0.132405E+10 | 0.283804E+10 | 0.270169E+10 |
March | 0.333418E+10 | 0.160812E+10 | 0.172606E+10 | 0.408550E+10 | 0.266761E+10 |
April | 0.354071E+10 | 0.160144E+10 | 0.193927E+10 | 0.496118E+10 | 0.168985E+10 |
May | 0.377096E+10 | 0.163512E+10 | 0.213584E+10 | 0.659919E+10 | 0.544245E+09 |
June | 0.370095E+10 | 0.146762E+10 | 0.223334E+10 | 0.671977E+10 | 0.456847E+09 |
July | 0.368724E+10 | 0.134928E+10 | 0.233796E+10 | 0.670082E+10 | 0.313934E+09 |
August | 0.339777E+10 | 0.116819E+10 | 0.222958E+10 | 0.618944E+10 | 0.429368E+09 |
September | 0.291281E+10 | 0.100149E+10 | 0.191132E+10 | 0.501367E+10 | 0.573491E+09 |
October | 0.297429E+10 | 0.125514E+10 | 0.171915E+10 | 0.481275E+10 | 0.107116E+10 |
November | 0.254825E+10 | 0.129991E+10 | 0.124834E+10 | 0.317601E+10 | 0.221158E+10 |
December | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.225027E+10 | 0.310218E+10 |
Annual Sum or Average | 0.370453E+11 | 0.158571E+11 | 0.211882E+11 | 0.560254E+11 | 0.193185E+11 |
Minimum of Months | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.225027E+10 | 0.313934E+09 |
Maximum of Months | 0.377096E+10 | 0.163512E+10 | 0.233796E+10 | 0.671977E+10 | 0.355659E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.857718E+10 | 0.611774E+10 | 0.245944E+10 | 0.113149E+11 | 0.559166E+10 |
February | 0.702474E+10 | 0.454720E+10 | 0.247754E+10 | 0.917243E+10 | 0.433992E+10 |
March | 0.496336E+10 | 0.223916E+10 | 0.272420E+10 | 0.610995E+10 | 0.431098E+10 |
April | 0.355961E+10 | 0.832905E+09 | 0.272670E+10 | 0.450107E+10 | 0.269908E+10 |
May | 0.281058E+10 | 0.118375E+09 | 0.269220E+10 | 0.518358E+10 | 0.826903E+09 |
June | 0.268735E+10 | 24527701.52 | 0.266282E+10 | 0.538522E+10 | 0.696360E+09 |
July | 0.290685E+10 | 52730932.22 | 0.285412E+10 | 0.570576E+10 | 0.465053E+09 |
August | 0.341943E+10 | 0.409408E+09 | 0.301002E+10 | 0.639530E+10 | 0.684730E+09 |
September | 0.397076E+10 | 0.104573E+10 | 0.292502E+10 | 0.671674E+10 | 0.952996E+09 |
October | 0.636703E+10 | 0.331634E+10 | 0.305069E+10 | 0.103288E+11 | 0.184507E+10 |
November | 0.784368E+10 | 0.540104E+10 | 0.244264E+10 | 0.112698E+11 | 0.366292E+10 |
December | 0.838118E+10 | 0.601967E+10 | 0.236151E+10 | 0.117061E+11 | 0.495811E+10 |
Annual Sum or Average | 0.625117E+11 | 0.301248E+11 | 0.323869E+11 | 0.937897E+11 | 0.310338E+11 |
Minimum of Months | 0.268735E+10 | 24527701.52 | 0.236151E+10 | 0.450107E+10 | 0.465053E+09 |
Maximum of Months | 0.857718E+10 | 0.611774E+10 | 0.305069E+10 | 0.117061E+11 | 0.559166E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270716E+10 | 0.146385E+10 | 0.124331E+10 | 0.306951E+10 | 0.393835E+10 |
February | 0.276847E+10 | 0.140118E+10 | 0.136729E+10 | 0.326663E+10 | 0.302922E+10 |
March | 0.302117E+10 | 0.133746E+10 | 0.168371E+10 | 0.374241E+10 | 0.296164E+10 |
April | 0.363138E+10 | 0.167060E+10 | 0.196077E+10 | 0.519658E+10 | 0.192035E+10 |
May | 0.312032E+10 | 0.101638E+10 | 0.210394E+10 | 0.560528E+10 | 0.644300E+09 |
June | 0.335451E+10 | 0.117618E+10 | 0.217833E+10 | 0.616393E+10 | 0.562675E+09 |
July | 0.316411E+10 | 0.877610E+09 | 0.228650E+10 | 0.580057E+10 | 0.403710E+09 |
August | 0.319941E+10 | 0.979382E+09 | 0.222003E+10 | 0.590022E+10 | 0.544809E+09 |
September | 0.285118E+10 | 0.978152E+09 | 0.187302E+10 | 0.495943E+10 | 0.676771E+09 |
October | 0.301625E+10 | 0.130331E+10 | 0.171294E+10 | 0.500376E+10 | 0.125178E+10 |
November | 0.250177E+10 | 0.125724E+10 | 0.124453E+10 | 0.331705E+10 | 0.250406E+10 |
December | 0.248676E+10 | 0.132241E+10 | 0.116435E+10 | 0.298722E+10 | 0.341005E+10 |
Annual Sum or Average | 0.358225E+11 | 0.147838E+11 | 0.210387E+11 | 0.550126E+11 | 0.218477E+11 |
Minimum of Months | 0.248676E+10 | 0.877610E+09 | 0.116435E+10 | 0.298722E+10 | 0.403710E+09 |
Maximum of Months | 0.363138E+10 | 0.167060E+10 | 0.228650E+10 | 0.616393E+10 | 0.393835E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 276.17 | 2659.47 | 553.86 | 0.00 | 553.86 | 0.00 | 0.00 |
February | 391.78 | 2260.59 | 653.42 | 0.00 | 653.42 | 0.00 | 0.00 |
March | 611.26 | 1924.80 | 758.03 | 0.00 | 758.03 | 0.00 | 0.00 |
April | 1061.43 | 1150.10 | 894.59 | 3.62 | 890.97 | 0.00 | 0.00 |
May | 1918.94 | 303.82 | 1013.18 | 36.90 | 976.28 | 0.00 | 0.00 |
June | 2258.92 | 242.11 | 1152.14 | 79.54 | 1072.60 | 0.00 | 0.00 |
July | 2209.95 | 149.62 | 1118.16 | 42.44 | 1075.72 | 0.00 | 0.00 |
August | 2035.02 | 221.07 | 1001.42 | 7.82 | 993.60 | 0.00 | 0.00 |
September | 1611.02 | 367.09 | 865.05 | 0.06 | 864.99 | 0.00 | 0.00 |
October | 1269.95 | 707.71 | 751.71 | 0.00 | 751.71 | 0.00 | 0.00 |
November | 484.94 | 1714.95 | 570.67 | 0.00 | 570.67 | 0.00 | 0.00 |
December | 306.67 | 2361.89 | 514.88 | 0.00 | 514.88 | 0.00 | 0.00 |
Annual Sum or Average | 1208.02 | 1166.31 | 821.42 | 14.24 | 807.18 | 0.00 | 0.00 |
Minimum of Months | 276.17 | 149.62 | 514.88 | 0.00 | 514.88 | 0.00 | 0.00 |
Maximum of Months | 2258.92 | 2659.47 | 1152.14 | 79.54 | 1075.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 929.92 | 1573.84 | 950.25 | 483.86 | 466.39 | 0.00 | 0.00 |
February | 1114.73 | 1322.56 | 1058.12 | 510.81 | 547.31 | 0.00 | 0.00 |
March | 1505.84 | 1127.76 | 1244.85 | 600.41 | 644.44 | 0.00 | 0.00 |
April | 1934.57 | 678.13 | 1366.02 | 617.84 | 748.18 | 0.00 | 0.00 |
May | 2512.86 | 194.15 | 1407.92 | 610.49 | 797.43 | 0.00 | 0.00 |
June | 2646.01 | 142.69 | 1427.84 | 566.21 | 861.63 | 0.00 | 0.00 |
July | 2568.66 | 74.93 | 1376.66 | 503.76 | 872.90 | 0.00 | 0.00 |
August | 2367.03 | 112.25 | 1268.59 | 436.15 | 832.43 | 0.00 | 0.00 |
September | 1968.53 | 226.25 | 1123.77 | 386.38 | 737.39 | 0.00 | 0.00 |
October | 1818.28 | 422.83 | 1110.48 | 468.62 | 641.86 | 0.00 | 0.00 |
November | 1188.24 | 992.99 | 983.13 | 501.51 | 481.61 | 0.00 | 0.00 |
December | 783.68 | 1376.04 | 774.06 | 350.61 | 423.44 | 0.00 | 0.00 |
Annual Sum or Average | 1781.94 | 683.75 | 1174.70 | 502.83 | 671.88 | 0.00 | 0.00 |
Minimum of Months | 783.68 | 74.93 | 774.06 | 350.61 | 423.44 | 0.00 | 0.00 |
Maximum of Months | 2646.01 | 1573.84 | 1427.84 | 617.84 | 872.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4229.83 | 2298.77 | 3202.36 | 2284.11 | 918.25 | 0.00 | 0.00 |
February | 3780.53 | 2000.38 | 2903.76 | 1879.64 | 1024.12 | 0.00 | 0.00 |
March | 2261.17 | 1807.45 | 1853.11 | 836.01 | 1017.10 | 0.00 | 0.00 |
April | 1718.83 | 1136.07 | 1373.31 | 321.34 | 1051.97 | 0.00 | 0.00 |
May | 1950.93 | 311.37 | 1049.35 | 44.20 | 1005.16 | 0.00 | 0.00 |
June | 2096.21 | 251.77 | 1036.79 | 9.46 | 1027.33 | 0.00 | 0.00 |
July | 2154.92 | 150.99 | 1085.30 | 19.69 | 1065.61 | 0.00 | 0.00 |
August | 2403.86 | 234.06 | 1276.67 | 152.86 | 1123.82 | 0.00 | 0.00 |
September | 2622.25 | 381.26 | 1531.93 | 403.45 | 1128.49 | 0.00 | 0.00 |
October | 3899.54 | 719.27 | 2377.18 | 1238.18 | 1139.00 | 0.00 | 0.00 |
November | 4355.64 | 1556.36 | 3026.12 | 2083.74 | 942.38 | 0.00 | 0.00 |
December | 4363.94 | 2082.41 | 3129.19 | 2247.50 | 881.69 | 0.00 | 0.00 |
Annual Sum or Average | 2983.10 | 1072.63 | 1982.24 | 955.26 | 1026.99 | 0.00 | 0.00 |
Minimum of Months | 1718.83 | 150.99 | 1036.79 | 9.46 | 881.69 | 0.00 | 0.00 |
Maximum of Months | 4363.94 | 2298.77 | 3202.36 | 2284.11 | 1139.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1084.18 | 1777.65 | 1010.74 | 546.54 | 464.20 | 0.00 | 0.00 |
February | 1273.53 | 1587.51 | 1144.38 | 579.19 | 565.18 | 0.00 | 0.00 |
March | 1320.72 | 1426.35 | 1127.98 | 499.35 | 628.63 | 0.00 | 0.00 |
April | 1942.71 | 935.95 | 1401.00 | 644.53 | 756.47 | 0.00 | 0.00 |
May | 2086.20 | 279.16 | 1165.00 | 379.48 | 785.52 | 0.00 | 0.00 |
June | 2363.34 | 251.48 | 1294.18 | 453.78 | 840.41 | 0.00 | 0.00 |
July | 2129.80 | 190.36 | 1181.35 | 327.66 | 853.69 | 0.00 | 0.00 |
August | 2150.65 | 271.75 | 1194.53 | 365.66 | 828.87 | 0.00 | 0.00 |
September | 1904.32 | 319.70 | 1099.99 | 377.38 | 722.62 | 0.00 | 0.00 |
October | 1832.37 | 579.21 | 1126.14 | 486.60 | 639.54 | 0.00 | 0.00 |
November | 1193.13 | 1284.92 | 965.19 | 485.05 | 480.14 | 0.00 | 0.00 |
December | 1020.46 | 1736.09 | 928.45 | 493.73 | 434.72 | 0.00 | 0.00 |
Annual Sum or Average | 1693.48 | 882.98 | 1135.93 | 468.79 | 667.14 | 0.00 | 0.00 |
Minimum of Months | 1020.46 | 190.36 | 928.45 | 327.66 | 434.72 | 0.00 | 0.00 |
Maximum of Months | 2363.34 | 1777.65 | 1401.00 | 644.53 | 853.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 341.98 | 2332.73 | 553.86 | 0.00 | 553.86 | 0.00 | 0.00 |
February | 465.63 | 1946.30 | 653.42 | 0.00 | 653.42 | 0.00 | 0.00 |
March | 688.17 | 1672.45 | 758.02 | 0.00 | 758.02 | 0.00 | 0.00 |
April | 1115.29 | 1026.56 | 894.59 | 3.62 | 890.96 | 0.00 | 0.00 |
May | 1943.43 | 278.57 | 1013.18 | 36.90 | 976.28 | 0.00 | 0.00 |
June | 2281.61 | 239.68 | 1152.13 | 79.54 | 1072.60 | 0.00 | 0.00 |
July | 2232.26 | 156.42 | 1118.15 | 42.44 | 1075.71 | 0.00 | 0.00 |
August | 2067.79 | 223.24 | 1001.42 | 7.82 | 993.60 | 0.00 | 0.00 |
September | 1639.21 | 321.16 | 865.05 | 0.06 | 864.98 | 0.00 | 0.00 |
October | 1311.54 | 629.84 | 751.71 | 0.00 | 751.71 | 0.00 | 0.00 |
November | 555.12 | 1461.99 | 570.67 | 0.00 | 570.67 | 0.00 | 0.00 |
December | 378.93 | 1989.23 | 514.87 | 0.00 | 514.87 | 0.00 | 0.00 |
Annual Sum or Average | 1256.61 | 1018.45 | 821.42 | 14.24 | 807.17 | 0.00 | 0.00 |
Minimum of Months | 341.98 | 156.42 | 514.87 | 0.00 | 514.87 | 0.00 | 0.00 |
Maximum of Months | 2281.61 | 2332.73 | 1152.13 | 79.54 | 1075.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 966.40 | 1423.51 | 950.25 | 483.86 | 466.39 | 0.00 | 0.00 |
February | 1149.25 | 1194.05 | 1058.12 | 510.81 | 547.31 | 0.00 | 0.00 |
March | 1517.69 | 1042.42 | 1244.84 | 600.40 | 644.44 | 0.00 | 0.00 |
April | 1922.35 | 664.04 | 1366.01 | 617.84 | 748.17 | 0.00 | 0.00 |
May | 2491.72 | 193.23 | 1407.91 | 610.48 | 797.43 | 0.00 | 0.00 |
June | 2622.38 | 165.12 | 1427.84 | 566.21 | 861.63 | 0.00 | 0.00 |
July | 2534.79 | 107.02 | 1376.66 | 503.76 | 872.89 | 0.00 | 0.00 |
August | 2337.86 | 152.04 | 1268.58 | 436.15 | 832.43 | 0.00 | 0.00 |
September | 1958.71 | 214.45 | 1123.77 | 386.38 | 737.39 | 0.00 | 0.00 |
October | 1809.72 | 408.40 | 1110.47 | 468.62 | 641.86 | 0.00 | 0.00 |
November | 1206.64 | 909.01 | 983.12 | 501.51 | 481.61 | 0.00 | 0.00 |
December | 816.65 | 1239.25 | 774.05 | 350.61 | 423.44 | 0.00 | 0.00 |
Annual Sum or Average | 1781.37 | 639.88 | 1174.70 | 502.83 | 671.87 | 0.00 | 0.00 |
Minimum of Months | 816.65 | 107.02 | 774.05 | 350.61 | 423.44 | 0.00 | 0.00 |
Maximum of Months | 2622.38 | 1423.51 | 1427.84 | 617.84 | 872.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4188.72 | 2232.70 | 3202.35 | 2284.10 | 918.25 | 0.00 | 0.00 |
February | 3759.46 | 1918.30 | 2903.75 | 1879.63 | 1024.12 | 0.00 | 0.00 |
March | 2270.24 | 1696.19 | 1853.11 | 836.01 | 1017.10 | 0.00 | 0.00 |
April | 1742.73 | 1069.44 | 1373.31 | 321.34 | 1051.97 | 0.00 | 0.00 |
May | 1970.70 | 293.01 | 1049.35 | 44.20 | 1005.15 | 0.00 | 0.00 |
June | 2117.56 | 250.92 | 1036.79 | 9.46 | 1027.32 | 0.00 | 0.00 |
July | 2178.20 | 157.93 | 1085.29 | 19.69 | 1065.61 | 0.00 | 0.00 |
August | 2423.66 | 243.00 | 1276.67 | 152.86 | 1123.81 | 0.00 | 0.00 |
September | 2622.54 | 358.96 | 1531.93 | 403.45 | 1128.48 | 0.00 | 0.00 |
October | 3872.00 | 705.84 | 2377.18 | 1238.18 | 1139.00 | 0.00 | 0.00 |
November | 4326.95 | 1498.08 | 3026.11 | 2083.73 | 942.38 | 0.00 | 0.00 |
December | 4339.81 | 1981.15 | 3129.17 | 2247.49 | 881.69 | 0.00 | 0.00 |
Annual Sum or Average | 2981.10 | 1029.15 | 1982.23 | 955.25 | 1026.98 | 0.00 | 0.00 |
Minimum of Months | 1742.73 | 157.93 | 1036.79 | 9.46 | 881.69 | 0.00 | 0.00 |
Maximum of Months | 4339.81 | 2232.70 | 3202.35 | 2284.10 | 1139.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1134.02 | 1559.59 | 1010.74 | 546.54 | 464.20 | 0.00 | 0.00 |
February | 1342.26 | 1330.61 | 1144.37 | 579.19 | 565.18 | 0.00 | 0.00 |
March | 1395.11 | 1160.01 | 1127.98 | 499.35 | 628.63 | 0.00 | 0.00 |
April | 2013.10 | 763.05 | 1400.99 | 644.52 | 756.47 | 0.00 | 0.00 |
May | 2113.66 | 235.58 | 1164.99 | 379.47 | 785.52 | 0.00 | 0.00 |
June | 2402.31 | 211.36 | 1294.18 | 453.77 | 840.40 | 0.00 | 0.00 |
July | 2192.31 | 144.99 | 1181.34 | 327.66 | 853.68 | 0.00 | 0.00 |
August | 2225.05 | 199.11 | 1194.52 | 365.66 | 828.86 | 0.00 | 0.00 |
September | 1931.02 | 259.78 | 1099.99 | 377.37 | 722.62 | 0.00 | 0.00 |
October | 1878.00 | 480.74 | 1126.14 | 486.60 | 639.54 | 0.00 | 0.00 |
November | 1269.79 | 1027.39 | 965.19 | 485.05 | 480.14 | 0.00 | 0.00 |
December | 1104.61 | 1353.49 | 928.45 | 493.73 | 434.72 | 0.00 | 0.00 |
Annual Sum or Average | 1751.77 | 723.95 | 1135.92 | 468.79 | 667.13 | 0.00 | 0.00 |
Minimum of Months | 1104.61 | 144.99 | 928.45 | 327.66 | 434.72 | 0.00 | 0.00 |
Maximum of Months | 2402.31 | 1559.59 | 1400.99 | 644.52 | 853.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 370.33 | 2164.45 | 553.86 | 0.00 | 553.86 | 0.00 | 0.00 |
February | 485.59 | 1804.47 | 653.42 | 0.00 | 653.42 | 0.00 | 0.00 |
March | 700.33 | 1579.58 | 758.02 | 0.00 | 758.02 | 0.00 | 0.00 |
April | 1108.21 | 996.51 | 894.59 | 3.62 | 890.96 | 0.00 | 0.00 |
May | 1905.14 | 293.64 | 1013.18 | 36.90 | 976.28 | 0.00 | 0.00 |
June | 2237.33 | 255.89 | 1152.13 | 79.54 | 1072.60 | 0.00 | 0.00 |
July | 2182.39 | 172.13 | 1118.15 | 42.44 | 1075.71 | 0.00 | 0.00 |
August | 2028.92 | 235.45 | 1001.42 | 7.82 | 993.60 | 0.00 | 0.00 |
September | 1603.11 | 330.15 | 865.05 | 0.06 | 864.98 | 0.00 | 0.00 |
October | 1295.79 | 611.88 | 751.71 | 0.00 | 751.71 | 0.00 | 0.00 |
November | 578.32 | 1350.33 | 570.67 | 0.00 | 570.67 | 0.00 | 0.00 |
December | 402.70 | 1840.28 | 514.87 | 0.00 | 514.87 | 0.00 | 0.00 |
Annual Sum or Average | 1246.19 | 965.29 | 821.42 | 14.24 | 807.17 | 0.00 | 0.00 |
Minimum of Months | 370.33 | 172.13 | 514.87 | 0.00 | 514.87 | 0.00 | 0.00 |
Maximum of Months | 2237.33 | 2164.45 | 1152.13 | 79.54 | 1075.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1000.16 | 1327.88 | 950.25 | 483.86 | 466.39 | 0.00 | 0.00 |
February | 1173.13 | 1116.77 | 1058.12 | 510.81 | 547.31 | 0.00 | 0.00 |
March | 1525.35 | 995.97 | 1244.84 | 600.40 | 644.44 | 0.00 | 0.00 |
April | 1914.03 | 651.95 | 1366.01 | 617.84 | 748.17 | 0.00 | 0.00 |
May | 2463.85 | 203.20 | 1407.91 | 610.48 | 797.43 | 0.00 | 0.00 |
June | 2592.50 | 176.25 | 1427.84 | 566.21 | 861.63 | 0.00 | 0.00 |
July | 2501.80 | 117.21 | 1376.66 | 503.76 | 872.89 | 0.00 | 0.00 |
August | 2310.87 | 160.31 | 1268.58 | 436.15 | 832.43 | 0.00 | 0.00 |
September | 1934.29 | 221.25 | 1123.77 | 386.38 | 737.39 | 0.00 | 0.00 |
October | 1796.87 | 399.92 | 1110.47 | 468.62 | 641.86 | 0.00 | 0.00 |
November | 1225.31 | 853.23 | 983.12 | 501.51 | 481.61 | 0.00 | 0.00 |
December | 840.15 | 1158.22 | 774.05 | 350.61 | 423.44 | 0.00 | 0.00 |
Annual Sum or Average | 1776.56 | 612.59 | 1174.70 | 502.83 | 671.87 | 0.00 | 0.00 |
Minimum of Months | 840.15 | 117.21 | 774.05 | 350.61 | 423.44 | 0.00 | 0.00 |
Maximum of Months | 2592.50 | 1327.88 | 1427.84 | 617.84 | 872.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4224.49 | 2087.69 | 3202.35 | 2284.10 | 918.25 | 0.00 | 0.00 |
February | 3791.51 | 1793.95 | 2903.75 | 1879.63 | 1024.12 | 0.00 | 0.00 |
March | 2281.19 | 1609.53 | 1853.11 | 836.01 | 1017.10 | 0.00 | 0.00 |
April | 1736.52 | 1041.31 | 1373.31 | 321.34 | 1051.97 | 0.00 | 0.00 |
May | 1935.33 | 308.73 | 1049.35 | 44.20 | 1005.15 | 0.00 | 0.00 |
June | 2077.63 | 268.66 | 1036.79 | 9.46 | 1027.32 | 0.00 | 0.00 |
July | 2130.29 | 173.63 | 1085.29 | 19.69 | 1065.61 | 0.00 | 0.00 |
August | 2387.73 | 255.65 | 1276.67 | 152.86 | 1123.81 | 0.00 | 0.00 |
September | 2591.33 | 367.67 | 1531.93 | 403.45 | 1128.48 | 0.00 | 0.00 |
October | 3856.34 | 688.87 | 2377.18 | 1238.18 | 1139.00 | 0.00 | 0.00 |
November | 4347.93 | 1413.16 | 3026.11 | 2083.73 | 942.38 | 0.00 | 0.00 |
December | 4370.57 | 1851.14 | 3129.17 | 2247.49 | 881.69 | 0.00 | 0.00 |
Annual Sum or Average | 2974.05 | 984.07 | 1982.23 | 955.25 | 1026.98 | 0.00 | 0.00 |
Minimum of Months | 1736.52 | 173.63 | 1036.79 | 9.46 | 881.69 | 0.00 | 0.00 |
Maximum of Months | 4370.57 | 2087.69 | 3202.35 | 2284.10 | 1139.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1146.02 | 1470.41 | 1010.74 | 546.54 | 464.20 | 0.00 | 0.00 |
February | 1350.30 | 1252.16 | 1144.37 | 579.19 | 565.18 | 0.00 | 0.00 |
March | 1397.26 | 1105.75 | 1127.98 | 499.35 | 628.63 | 0.00 | 0.00 |
April | 2004.85 | 740.88 | 1400.99 | 644.52 | 756.47 | 0.00 | 0.00 |
May | 2092.77 | 240.55 | 1164.99 | 379.47 | 785.52 | 0.00 | 0.00 |
June | 2378.06 | 217.08 | 1294.18 | 453.77 | 840.40 | 0.00 | 0.00 |
July | 2165.68 | 150.73 | 1181.34 | 327.66 | 853.68 | 0.00 | 0.00 |
August | 2202.89 | 203.41 | 1194.52 | 365.66 | 828.86 | 0.00 | 0.00 |
September | 1913.36 | 261.10 | 1099.99 | 377.37 | 722.62 | 0.00 | 0.00 |
October | 1868.19 | 467.36 | 1126.14 | 486.60 | 639.54 | 0.00 | 0.00 |
November | 1279.73 | 966.07 | 965.19 | 485.05 | 480.14 | 0.00 | 0.00 |
December | 1115.30 | 1273.17 | 928.45 | 493.73 | 434.72 | 0.00 | 0.00 |
Annual Sum or Average | 1744.44 | 692.79 | 1135.92 | 468.79 | 667.13 | 0.00 | 0.00 |
Minimum of Months | 1115.30 | 150.73 | 928.45 | 327.66 | 434.72 | 0.00 | 0.00 |
Maximum of Months | 2378.06 | 1470.41 | 1400.99 | 644.52 | 853.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.739685E+09 | 0.712313E+10 | 0.148346E+10 | 0.00 | 0.148346E+10 | 0.00 | 0.00 |
February | 0.947796E+09 | 0.546881E+10 | 0.158076E+10 | 0.00 | 0.158076E+10 | 0.00 | 0.00 |
March | 0.163721E+10 | 0.515540E+10 | 0.203030E+10 | 0.00 | 0.203030E+10 | 0.00 | 0.00 |
April | 0.275123E+10 | 0.298106E+10 | 0.231878E+10 | 9395269.58 | 0.230939E+10 | 0.00 | 0.00 |
May | 0.513968E+10 | 0.813741E+09 | 0.271370E+10 | 98825233.97 | 0.261488E+10 | 0.00 | 0.00 |
June | 0.585512E+10 | 0.627537E+09 | 0.298634E+10 | 0.206162E+09 | 0.278018E+10 | 0.00 | 0.00 |
July | 0.591912E+10 | 0.400740E+09 | 0.299487E+10 | 0.113670E+09 | 0.288120E+10 | 0.00 | 0.00 |
August | 0.545060E+10 | 0.592117E+09 | 0.268220E+10 | 20937947.05 | 0.266127E+10 | 0.00 | 0.00 |
September | 0.417576E+10 | 0.951486E+09 | 0.224221E+10 | 167848.63 | 0.224204E+10 | 0.00 | 0.00 |
October | 0.340144E+10 | 0.189553E+10 | 0.201339E+10 | 0.00 | 0.201339E+10 | 0.00 | 0.00 |
November | 0.125697E+10 | 0.444516E+10 | 0.147918E+10 | 0.00 | 0.147918E+10 | 0.00 | 0.00 |
December | 0.821376E+09 | 0.632607E+10 | 0.137905E+10 | 0.00 | 0.137905E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.380960E+11 | 0.367808E+11 | 0.259042E+11 | 0.449159E+09 | 0.254551E+11 | 0.00 | 0.00 |
Minimum of Months | 0.739685E+09 | 0.400740E+09 | 0.137905E+10 | 0.00 | 0.137905E+10 | 0.00 | 0.00 |
Maximum of Months | 0.591912E+10 | 0.712313E+10 | 0.299487E+10 | 0.206162E+09 | 0.288120E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.249069E+10 | 0.421536E+10 | 0.254516E+10 | 0.129598E+10 | 0.124919E+10 | 0.00 | 0.00 |
February | 0.269675E+10 | 0.319953E+10 | 0.255981E+10 | 0.123575E+10 | 0.132405E+10 | 0.00 | 0.00 |
March | 0.403323E+10 | 0.302058E+10 | 0.333420E+10 | 0.160813E+10 | 0.172607E+10 | 0.00 | 0.00 |
April | 0.501441E+10 | 0.175771E+10 | 0.354072E+10 | 0.160145E+10 | 0.193928E+10 | 0.00 | 0.00 |
May | 0.673046E+10 | 0.520008E+09 | 0.377097E+10 | 0.163513E+10 | 0.213585E+10 | 0.00 | 0.00 |
June | 0.685847E+10 | 0.369845E+09 | 0.370097E+10 | 0.146762E+10 | 0.223335E+10 | 0.00 | 0.00 |
July | 0.687990E+10 | 0.200687E+09 | 0.368725E+10 | 0.134928E+10 | 0.233797E+10 | 0.00 | 0.00 |
August | 0.633984E+10 | 0.300646E+09 | 0.339778E+10 | 0.116819E+10 | 0.222959E+10 | 0.00 | 0.00 |
September | 0.510242E+10 | 0.586440E+09 | 0.291282E+10 | 0.100150E+10 | 0.191133E+10 | 0.00 | 0.00 |
October | 0.487007E+10 | 0.113252E+10 | 0.297430E+10 | 0.125515E+10 | 0.171915E+10 | 0.00 | 0.00 |
November | 0.307991E+10 | 0.257383E+10 | 0.254826E+10 | 0.129992E+10 | 0.124834E+10 | 0.00 | 0.00 |
December | 0.209902E+10 | 0.368560E+10 | 0.207323E+10 | 0.939083E+09 | 0.113415E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.561952E+11 | 0.215627E+11 | 0.370455E+11 | 0.158572E+11 | 0.211883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209902E+10 | 0.200687E+09 | 0.207323E+10 | 0.939083E+09 | 0.113415E+10 | 0.00 | 0.00 |
Maximum of Months | 0.687990E+10 | 0.421536E+10 | 0.377097E+10 | 0.163513E+10 | 0.233797E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113292E+11 | 0.615701E+10 | 0.857721E+10 | 0.611776E+10 | 0.245945E+10 | 0.00 | 0.00 |
February | 0.914587E+10 | 0.483932E+10 | 0.702477E+10 | 0.454722E+10 | 0.247755E+10 | 0.00 | 0.00 |
March | 0.605632E+10 | 0.484109E+10 | 0.496338E+10 | 0.223916E+10 | 0.272421E+10 | 0.00 | 0.00 |
April | 0.445522E+10 | 0.294468E+10 | 0.355962E+10 | 0.832908E+09 | 0.272671E+10 | 0.00 | 0.00 |
May | 0.522537E+10 | 0.833968E+09 | 0.281059E+10 | 0.118375E+09 | 0.269221E+10 | 0.00 | 0.00 |
June | 0.543339E+10 | 0.652587E+09 | 0.268736E+10 | 24527788.62 | 0.266283E+10 | 0.00 | 0.00 |
July | 0.577172E+10 | 0.404408E+09 | 0.290686E+10 | 52731119.47 | 0.285413E+10 | 0.00 | 0.00 |
August | 0.643850E+10 | 0.626908E+09 | 0.341944E+10 | 0.409409E+09 | 0.301003E+10 | 0.00 | 0.00 |
September | 0.679687E+10 | 0.988217E+09 | 0.397077E+10 | 0.104574E+10 | 0.292503E+10 | 0.00 | 0.00 |
October | 0.104445E+11 | 0.192650E+10 | 0.636705E+10 | 0.331635E+10 | 0.305070E+10 | 0.00 | 0.00 |
November | 0.112898E+11 | 0.403409E+10 | 0.784371E+10 | 0.540106E+10 | 0.244265E+10 | 0.00 | 0.00 |
December | 0.116884E+11 | 0.557753E+10 | 0.838121E+10 | 0.601969E+10 | 0.236152E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.940752E+11 | 0.338263E+11 | 0.625120E+11 | 0.301249E+11 | 0.323870E+11 | 0.00 | 0.00 |
Minimum of Months | 0.445522E+10 | 0.404408E+09 | 0.268736E+10 | 24527788.62 | 0.236152E+10 | 0.00 | 0.00 |
Maximum of Months | 0.116884E+11 | 0.615701E+10 | 0.857721E+10 | 0.611776E+10 | 0.305070E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.290387E+10 | 0.476125E+10 | 0.270717E+10 | 0.146386E+10 | 0.124332E+10 | 0.00 | 0.00 |
February | 0.308092E+10 | 0.384051E+10 | 0.276848E+10 | 0.140119E+10 | 0.136729E+10 | 0.00 | 0.00 |
March | 0.353741E+10 | 0.382033E+10 | 0.302118E+10 | 0.133746E+10 | 0.168372E+10 | 0.00 | 0.00 |
April | 0.503551E+10 | 0.242598E+10 | 0.363139E+10 | 0.167061E+10 | 0.196078E+10 | 0.00 | 0.00 |
May | 0.558767E+10 | 0.747694E+09 | 0.312033E+10 | 0.101639E+10 | 0.210395E+10 | 0.00 | 0.00 |
June | 0.612577E+10 | 0.651840E+09 | 0.335452E+10 | 0.117619E+10 | 0.217834E+10 | 0.00 | 0.00 |
July | 0.570446E+10 | 0.509854E+09 | 0.316413E+10 | 0.877613E+09 | 0.228651E+10 | 0.00 | 0.00 |
August | 0.576031E+10 | 0.727848E+09 | 0.319942E+10 | 0.979386E+09 | 0.222004E+10 | 0.00 | 0.00 |
September | 0.493600E+10 | 0.828673E+09 | 0.285119E+10 | 0.978156E+09 | 0.187303E+10 | 0.00 | 0.00 |
October | 0.490783E+10 | 0.155135E+10 | 0.301626E+10 | 0.130331E+10 | 0.171295E+10 | 0.00 | 0.00 |
November | 0.309260E+10 | 0.333052E+10 | 0.250178E+10 | 0.125725E+10 | 0.124453E+10 | 0.00 | 0.00 |
December | 0.273321E+10 | 0.464994E+10 | 0.248677E+10 | 0.132241E+10 | 0.116436E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.534056E+11 | 0.278458E+11 | 0.358226E+11 | 0.147838E+11 | 0.210388E+11 | 0.00 | 0.00 |
Minimum of Months | 0.273321E+10 | 0.509854E+09 | 0.248677E+10 | 0.877613E+09 | 0.116436E+10 | 0.00 | 0.00 |
Maximum of Months | 0.612577E+10 | 0.476125E+10 | 0.363139E+10 | 0.167061E+10 | 0.228651E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.915956E+09 | 0.624799E+10 | 0.148346E+10 | 0.00 | 0.148346E+10 | 0.00 | 0.00 |
February | 0.112646E+10 | 0.470850E+10 | 0.158075E+10 | 0.00 | 0.158075E+10 | 0.00 | 0.00 |
March | 0.184320E+10 | 0.447949E+10 | 0.203029E+10 | 0.00 | 0.203029E+10 | 0.00 | 0.00 |
April | 0.289084E+10 | 0.266083E+10 | 0.231877E+10 | 9395236.22 | 0.230938E+10 | 0.00 | 0.00 |
May | 0.520527E+10 | 0.746115E+09 | 0.271369E+10 | 98824883.04 | 0.261487E+10 | 0.00 | 0.00 |
June | 0.591392E+10 | 0.621245E+09 | 0.298633E+10 | 0.206161E+09 | 0.278017E+10 | 0.00 | 0.00 |
July | 0.597889E+10 | 0.418947E+09 | 0.299486E+10 | 0.113670E+09 | 0.288119E+10 | 0.00 | 0.00 |
August | 0.553836E+10 | 0.597916E+09 | 0.268219E+10 | 20937872.69 | 0.266126E+10 | 0.00 | 0.00 |
September | 0.424883E+10 | 0.832449E+09 | 0.224220E+10 | 167848.03 | 0.224204E+10 | 0.00 | 0.00 |
October | 0.351283E+10 | 0.168697E+10 | 0.201338E+10 | 0.00 | 0.201338E+10 | 0.00 | 0.00 |
November | 0.143886E+10 | 0.378949E+10 | 0.147917E+10 | 0.00 | 0.147917E+10 | 0.00 | 0.00 |
December | 0.101493E+10 | 0.532795E+10 | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.396283E+11 | 0.321179E+11 | 0.259041E+11 | 0.449157E+09 | 0.254550E+11 | 0.00 | 0.00 |
Minimum of Months | 0.915956E+09 | 0.418947E+09 | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.00 | 0.00 |
Maximum of Months | 0.597889E+10 | 0.624799E+10 | 0.299486E+10 | 0.206161E+09 | 0.288119E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.258841E+10 | 0.381274E+10 | 0.254515E+10 | 0.129597E+10 | 0.124918E+10 | 0.00 | 0.00 |
February | 0.278027E+10 | 0.288865E+10 | 0.255980E+10 | 0.123575E+10 | 0.132405E+10 | 0.00 | 0.00 |
March | 0.406499E+10 | 0.279202E+10 | 0.333418E+10 | 0.160812E+10 | 0.172606E+10 | 0.00 | 0.00 |
April | 0.498274E+10 | 0.172119E+10 | 0.354071E+10 | 0.160144E+10 | 0.193927E+10 | 0.00 | 0.00 |
May | 0.667383E+10 | 0.517537E+09 | 0.377096E+10 | 0.163512E+10 | 0.213584E+10 | 0.00 | 0.00 |
June | 0.679722E+10 | 0.427989E+09 | 0.370095E+10 | 0.146762E+10 | 0.223334E+10 | 0.00 | 0.00 |
July | 0.678917E+10 | 0.286646E+09 | 0.368724E+10 | 0.134928E+10 | 0.233796E+10 | 0.00 | 0.00 |
August | 0.626172E+10 | 0.407225E+09 | 0.339777E+10 | 0.116819E+10 | 0.222958E+10 | 0.00 | 0.00 |
September | 0.507698E+10 | 0.555867E+09 | 0.291281E+10 | 0.100149E+10 | 0.191132E+10 | 0.00 | 0.00 |
October | 0.484715E+10 | 0.109386E+10 | 0.297429E+10 | 0.125514E+10 | 0.171915E+10 | 0.00 | 0.00 |
November | 0.312760E+10 | 0.235616E+10 | 0.254825E+10 | 0.129991E+10 | 0.124834E+10 | 0.00 | 0.00 |
December | 0.218733E+10 | 0.331921E+10 | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.561774E+11 | 0.201791E+11 | 0.370453E+11 | 0.158571E+11 | 0.211882E+11 | 0.00 | 0.00 |
Minimum of Months | 0.218733E+10 | 0.286646E+09 | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.00 | 0.00 |
Maximum of Months | 0.679722E+10 | 0.381274E+10 | 0.377096E+10 | 0.163512E+10 | 0.233796E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112191E+11 | 0.598007E+10 | 0.857718E+10 | 0.611774E+10 | 0.245944E+10 | 0.00 | 0.00 |
February | 0.909489E+10 | 0.464074E+10 | 0.702474E+10 | 0.454720E+10 | 0.247754E+10 | 0.00 | 0.00 |
March | 0.608062E+10 | 0.454308E+10 | 0.496336E+10 | 0.223916E+10 | 0.272420E+10 | 0.00 | 0.00 |
April | 0.451716E+10 | 0.277198E+10 | 0.355961E+10 | 0.832905E+09 | 0.272670E+10 | 0.00 | 0.00 |
May | 0.527833E+10 | 0.784800E+09 | 0.281058E+10 | 0.118375E+09 | 0.269220E+10 | 0.00 | 0.00 |
June | 0.548872E+10 | 0.650381E+09 | 0.268735E+10 | 24527701.52 | 0.266282E+10 | 0.00 | 0.00 |
July | 0.583408E+10 | 0.422994E+09 | 0.290685E+10 | 52730932.22 | 0.285412E+10 | 0.00 | 0.00 |
August | 0.649153E+10 | 0.650855E+09 | 0.341943E+10 | 0.409408E+09 | 0.301002E+10 | 0.00 | 0.00 |
September | 0.679763E+10 | 0.930416E+09 | 0.397076E+10 | 0.104573E+10 | 0.292502E+10 | 0.00 | 0.00 |
October | 0.103708E+11 | 0.189052E+10 | 0.636703E+10 | 0.331634E+10 | 0.305069E+10 | 0.00 | 0.00 |
November | 0.112155E+11 | 0.388303E+10 | 0.784368E+10 | 0.540104E+10 | 0.244264E+10 | 0.00 | 0.00 |
December | 0.116237E+11 | 0.530632E+10 | 0.838118E+10 | 0.601967E+10 | 0.236151E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.940120E+11 | 0.324552E+11 | 0.625117E+11 | 0.301248E+11 | 0.323869E+11 | 0.00 | 0.00 |
Minimum of Months | 0.451716E+10 | 0.422994E+09 | 0.268735E+10 | 24527701.52 | 0.236151E+10 | 0.00 | 0.00 |
Maximum of Months | 0.116237E+11 | 0.598007E+10 | 0.857718E+10 | 0.611774E+10 | 0.305069E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.303737E+10 | 0.417721E+10 | 0.270716E+10 | 0.146385E+10 | 0.124331E+10 | 0.00 | 0.00 |
February | 0.324720E+10 | 0.321902E+10 | 0.276847E+10 | 0.140118E+10 | 0.136729E+10 | 0.00 | 0.00 |
March | 0.373665E+10 | 0.310696E+10 | 0.302117E+10 | 0.133746E+10 | 0.168371E+10 | 0.00 | 0.00 |
April | 0.521796E+10 | 0.197783E+10 | 0.363138E+10 | 0.167060E+10 | 0.196077E+10 | 0.00 | 0.00 |
May | 0.566123E+10 | 0.630971E+09 | 0.312032E+10 | 0.101638E+10 | 0.210394E+10 | 0.00 | 0.00 |
June | 0.622679E+10 | 0.547847E+09 | 0.335451E+10 | 0.117618E+10 | 0.217833E+10 | 0.00 | 0.00 |
July | 0.587189E+10 | 0.388332E+09 | 0.316411E+10 | 0.877610E+09 | 0.228650E+10 | 0.00 | 0.00 |
August | 0.595958E+10 | 0.533287E+09 | 0.319941E+10 | 0.979382E+09 | 0.222003E+10 | 0.00 | 0.00 |
September | 0.500520E+10 | 0.673357E+09 | 0.285118E+10 | 0.978152E+09 | 0.187302E+10 | 0.00 | 0.00 |
October | 0.503004E+10 | 0.128760E+10 | 0.301625E+10 | 0.130331E+10 | 0.171294E+10 | 0.00 | 0.00 |
November | 0.329130E+10 | 0.266298E+10 | 0.250177E+10 | 0.125724E+10 | 0.124453E+10 | 0.00 | 0.00 |
December | 0.295859E+10 | 0.362519E+10 | 0.248676E+10 | 0.132241E+10 | 0.116435E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.552438E+11 | 0.228306E+11 | 0.358225E+11 | 0.147838E+11 | 0.210387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.295859E+10 | 0.388332E+09 | 0.248676E+10 | 0.877610E+09 | 0.116435E+10 | 0.00 | 0.00 |
Maximum of Months | 0.622679E+10 | 0.417721E+10 | 0.363138E+10 | 0.167060E+10 | 0.228650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.991898E+09 | 0.579726E+10 | 0.148346E+10 | 0.00 | 0.148346E+10 | 0.00 | 0.00 |
February | 0.117475E+10 | 0.436538E+10 | 0.158075E+10 | 0.00 | 0.158075E+10 | 0.00 | 0.00 |
March | 0.187576E+10 | 0.423075E+10 | 0.203029E+10 | 0.00 | 0.203029E+10 | 0.00 | 0.00 |
April | 0.287249E+10 | 0.258296E+10 | 0.231877E+10 | 9395236.22 | 0.230938E+10 | 0.00 | 0.00 |
May | 0.510274E+10 | 0.786481E+09 | 0.271369E+10 | 98824883.04 | 0.261487E+10 | 0.00 | 0.00 |
June | 0.579917E+10 | 0.663276E+09 | 0.298633E+10 | 0.206161E+09 | 0.278017E+10 | 0.00 | 0.00 |
July | 0.584531E+10 | 0.461042E+09 | 0.299486E+10 | 0.113670E+09 | 0.288119E+10 | 0.00 | 0.00 |
August | 0.543426E+10 | 0.630625E+09 | 0.268219E+10 | 20937872.69 | 0.266126E+10 | 0.00 | 0.00 |
September | 0.415525E+10 | 0.855747E+09 | 0.224220E+10 | 167848.03 | 0.224204E+10 | 0.00 | 0.00 |
October | 0.347064E+10 | 0.163886E+10 | 0.201338E+10 | 0.00 | 0.201338E+10 | 0.00 | 0.00 |
November | 0.149899E+10 | 0.350006E+10 | 0.147917E+10 | 0.00 | 0.147917E+10 | 0.00 | 0.00 |
December | 0.107858E+10 | 0.492902E+10 | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.392999E+11 | 0.304415E+11 | 0.259041E+11 | 0.449157E+09 | 0.254550E+11 | 0.00 | 0.00 |
Minimum of Months | 0.991898E+09 | 0.461042E+09 | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.00 | 0.00 |
Maximum of Months | 0.584531E+10 | 0.579726E+10 | 0.299486E+10 | 0.206161E+09 | 0.288119E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.267882E+10 | 0.355659E+10 | 0.254515E+10 | 0.129597E+10 | 0.124918E+10 | 0.00 | 0.00 |
February | 0.283804E+10 | 0.270169E+10 | 0.255980E+10 | 0.123575E+10 | 0.132405E+10 | 0.00 | 0.00 |
March | 0.408550E+10 | 0.266761E+10 | 0.333418E+10 | 0.160812E+10 | 0.172606E+10 | 0.00 | 0.00 |
April | 0.496118E+10 | 0.168985E+10 | 0.354071E+10 | 0.160144E+10 | 0.193927E+10 | 0.00 | 0.00 |
May | 0.659919E+10 | 0.544245E+09 | 0.377096E+10 | 0.163512E+10 | 0.213584E+10 | 0.00 | 0.00 |
June | 0.671977E+10 | 0.456847E+09 | 0.370095E+10 | 0.146762E+10 | 0.223334E+10 | 0.00 | 0.00 |
July | 0.670082E+10 | 0.313934E+09 | 0.368724E+10 | 0.134928E+10 | 0.233796E+10 | 0.00 | 0.00 |
August | 0.618944E+10 | 0.429368E+09 | 0.339777E+10 | 0.116819E+10 | 0.222958E+10 | 0.00 | 0.00 |
September | 0.501367E+10 | 0.573491E+09 | 0.291281E+10 | 0.100149E+10 | 0.191132E+10 | 0.00 | 0.00 |
October | 0.481275E+10 | 0.107116E+10 | 0.297429E+10 | 0.125514E+10 | 0.171915E+10 | 0.00 | 0.00 |
November | 0.317601E+10 | 0.221158E+10 | 0.254825E+10 | 0.129991E+10 | 0.124834E+10 | 0.00 | 0.00 |
December | 0.225027E+10 | 0.310218E+10 | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.560254E+11 | 0.193185E+11 | 0.370453E+11 | 0.158571E+11 | 0.211882E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225027E+10 | 0.313934E+09 | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.00 | 0.00 |
Maximum of Months | 0.671977E+10 | 0.355659E+10 | 0.377096E+10 | 0.163512E+10 | 0.233796E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113149E+11 | 0.559166E+10 | 0.857718E+10 | 0.611774E+10 | 0.245944E+10 | 0.00 | 0.00 |
February | 0.917243E+10 | 0.433992E+10 | 0.702474E+10 | 0.454720E+10 | 0.247754E+10 | 0.00 | 0.00 |
March | 0.610995E+10 | 0.431098E+10 | 0.496336E+10 | 0.223916E+10 | 0.272420E+10 | 0.00 | 0.00 |
April | 0.450107E+10 | 0.269908E+10 | 0.355961E+10 | 0.832905E+09 | 0.272670E+10 | 0.00 | 0.00 |
May | 0.518358E+10 | 0.826903E+09 | 0.281058E+10 | 0.118375E+09 | 0.269220E+10 | 0.00 | 0.00 |
June | 0.538522E+10 | 0.696360E+09 | 0.268735E+10 | 24527701.52 | 0.266282E+10 | 0.00 | 0.00 |
July | 0.570576E+10 | 0.465053E+09 | 0.290685E+10 | 52730932.22 | 0.285412E+10 | 0.00 | 0.00 |
August | 0.639530E+10 | 0.684730E+09 | 0.341943E+10 | 0.409408E+09 | 0.301002E+10 | 0.00 | 0.00 |
September | 0.671674E+10 | 0.952996E+09 | 0.397076E+10 | 0.104573E+10 | 0.292502E+10 | 0.00 | 0.00 |
October | 0.103288E+11 | 0.184507E+10 | 0.636703E+10 | 0.331634E+10 | 0.305069E+10 | 0.00 | 0.00 |
November | 0.112698E+11 | 0.366292E+10 | 0.784368E+10 | 0.540104E+10 | 0.244264E+10 | 0.00 | 0.00 |
December | 0.117061E+11 | 0.495811E+10 | 0.838118E+10 | 0.601967E+10 | 0.236151E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.937897E+11 | 0.310338E+11 | 0.625117E+11 | 0.301248E+11 | 0.323869E+11 | 0.00 | 0.00 |
Minimum of Months | 0.450107E+10 | 0.465053E+09 | 0.268735E+10 | 24527701.52 | 0.236151E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117061E+11 | 0.559166E+10 | 0.857718E+10 | 0.611774E+10 | 0.305069E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.306951E+10 | 0.393835E+10 | 0.270716E+10 | 0.146385E+10 | 0.124331E+10 | 0.00 | 0.00 |
February | 0.326663E+10 | 0.302922E+10 | 0.276847E+10 | 0.140118E+10 | 0.136729E+10 | 0.00 | 0.00 |
March | 0.374241E+10 | 0.296164E+10 | 0.302117E+10 | 0.133746E+10 | 0.168371E+10 | 0.00 | 0.00 |
April | 0.519658E+10 | 0.192035E+10 | 0.363138E+10 | 0.167060E+10 | 0.196077E+10 | 0.00 | 0.00 |
May | 0.560528E+10 | 0.644300E+09 | 0.312032E+10 | 0.101638E+10 | 0.210394E+10 | 0.00 | 0.00 |
June | 0.616393E+10 | 0.562675E+09 | 0.335451E+10 | 0.117618E+10 | 0.217833E+10 | 0.00 | 0.00 |
July | 0.580057E+10 | 0.403710E+09 | 0.316411E+10 | 0.877610E+09 | 0.228650E+10 | 0.00 | 0.00 |
August | 0.590022E+10 | 0.544809E+09 | 0.319941E+10 | 0.979382E+09 | 0.222003E+10 | 0.00 | 0.00 |
September | 0.495943E+10 | 0.676771E+09 | 0.285118E+10 | 0.978152E+09 | 0.187302E+10 | 0.00 | 0.00 |
October | 0.500376E+10 | 0.125178E+10 | 0.301625E+10 | 0.130331E+10 | 0.171294E+10 | 0.00 | 0.00 |
November | 0.331705E+10 | 0.250406E+10 | 0.250177E+10 | 0.125724E+10 | 0.124453E+10 | 0.00 | 0.00 |
December | 0.298722E+10 | 0.341005E+10 | 0.248676E+10 | 0.132241E+10 | 0.116435E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.550126E+11 | 0.218477E+11 | 0.358225E+11 | 0.147838E+11 | 0.210387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.298722E+10 | 0.403710E+09 | 0.248676E+10 | 0.877610E+09 | 0.116435E+10 | 0.00 | 0.00 |
Maximum of Months | 0.616393E+10 | 0.393835E+10 | 0.363138E+10 | 0.167060E+10 | 0.228650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.01 | 8.64 | 3.24 | 3.12 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.57 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.53 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.81 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.36 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.89 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.01 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.46 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.87 | 10.53 | 3.17 | 6.00 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.01 | 8.64 | 2.44 | 3.12 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.65 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.77 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.86 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.04 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.75 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.93 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.95 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.72 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.63 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.03 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.82 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.65 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.63 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.2 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -1.8 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.94 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.57 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 17.99 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.55 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.11 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.8 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.2 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.10 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.48 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.76 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.54 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.83 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.16 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.78 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.48 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.10 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.54 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.08 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.78 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.160848E+11 | -.308291E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.132247E+10 | 68.99 | 0.00 | 0.00 |
February | 0.144680E+11 | -.277972E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.119158E+10 | 68.86 | 0.00 | 0.00 |
March | 0.166979E+11 | -.314435E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130140E+10 | 68.16 | 0.00 | 0.00 |
April | 0.123033E+11 | -.268014E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.128375E+10 | 69.12 | 0.00 | 0.00 |
May | 0.115910E+11 | -.266413E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.133155E+10 | 69.24 | 0.00 | 0.00 |
June | 0.101040E+11 | -.247602E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.128442E+10 | 69.05 | 0.00 | 0.00 |
July | 0.755330E+10 | -.228320E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.136004E+10 | 70.31 | 0.00 | 0.00 |
August | 0.100685E+11 | -.252400E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.132658E+10 | 69.08 | 0.00 | 0.00 |
September | 0.941629E+10 | -.240947E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.129615E+10 | 69.59 | 0.00 | 0.00 |
October | 0.116054E+11 | -.266318E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.133960E+10 | 69.65 | 0.00 | 0.00 |
November | 0.136168E+11 | -.280020E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.128910E+10 | 69.41 | 0.00 | 0.00 |
December | 0.145396E+11 | -.293881E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.132563E+10 | 69.19 | 0.00 | 0.00 |
Annual Sum or Average | 0.148049E+12 | -.324461E+12 | 8760.00 | -.156523E+11 | 69.22 | |||||
Minimum of Months | 0.755330E+10 | -.314435E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.136004E+10 | 68.16 | 0.00 | 0.00 |
Maximum of Months | 0.166979E+11 | -.228320E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.119158E+10 | 70.31 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7770.35 | 36.97 | 300.33 | 296.17 | 1442.47 | 25.96 | 215.67 | 278.83 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 3377.81 | 28.24 | 173.67 | 279.83 | 1251.63 | 23.20 | 185.17 | 266.50 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1588.31 | 20.00 | 54.67 | 319.67 | 929.06 | 21.32 | 172.33 | 281.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:00 | 1263.17 | 19.19 | 28.67 | 323.83 | 729.49 | 20.50 | 171.00 | 284.50 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 1128.80 | 19.44 | 8.00 | 349.67 | 636.24 | 20.79 | 163.83 | 300.17 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:10 | 1072.53 | 19.08 | 1.83 | 350.50 | 608.30 | 20.45 | 161.50 | 304.00 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1182.57 | 19.45 | 12.50 | 360.00 | 650.65 | 20.79 | 192.83 | 313.50 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1372.67 | 19.74 | 40.00 | 346.67 | 740.16 | 21.06 | 239.17 | 307.67 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:30 | 1614.76 | 20.03 | 85.83 | 317.67 | 855.94 | 21.26 | 224.50 | 282.00 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2783.08 | 23.92 | 164.00 | 314.50 | 1161.12 | 22.35 | 236.33 | 283.33 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:09 | 7841.85 | 36.40 | 297.17 | 288.67 | 1374.30 | 24.15 | 201.00 | 271.17 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7920.99 | 37.74 | 279.33 | 284.33 | 1830.22 | 27.85 | 205.50 | 267.17 |
Annual Sum or Average | 4027.67 | 0.52 | 3035.85 | 24.44 | 1446.00 | 3831.50 | 982.92 | 22.29 | 2368.83 | 3440.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1072.53 | 19.08 | 1.83 | 279.83 | 608.30 | 20.45 | 161.50 | 266.50 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 7920.99 | 37.74 | 300.33 | 360.00 | 1830.22 | 27.85 | 239.17 | 313.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-07:49 | 1997.48 | 23.64 | 104.17 | 271.17 | 1078.48 | 23.71 | 124.83 | 224.00 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 2211.39 | 23.72 | 91.00 | 261.50 | 1174.70 | 23.87 | 113.33 | 228.17 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2303.85 | 23.68 | 86.00 | 315.67 | 1219.50 | 23.82 | 121.50 | 276.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 2357.53 | 22.77 | 96.00 | 326.33 | 1253.38 | 23.13 | 120.17 | 293.50 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2667.04 | 24.06 | 112.00 | 360.50 | 1071.81 | 23.03 | 125.67 | 315.17 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:10 | 2398.91 | 23.68 | 122.83 | 359.17 | 1014.36 | 22.93 | 143.50 | 321.50 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 2309.74 | 23.14 | 112.83 | 365.17 | 996.01 | 22.40 | 156.17 | 318.83 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:49 | 2128.04 | 23.05 | 106.17 | 347.17 | 1109.76 | 23.46 | 170.17 | 308.50 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 2032.74 | 23.18 | 100.33 | 314.50 | 1040.49 | 23.47 | 169.00 | 278.83 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2115.38 | 23.40 | 92.67 | 303.00 | 1083.58 | 23.54 | 158.83 | 269.83 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-07:00 | 1757.24 | 22.78 | 85.67 | 267.33 | 902.07 | 22.82 | 123.50 | 230.83 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1890.20 | 23.38 | 91.50 | 257.50 | 1008.87 | 23.40 | 110.33 | 208.50 |
Annual Sum or Average | 4027.67 | 0.52 | 2194.13 | 23.37 | 1201.17 | 3749.00 | 1077.91 | 23.27 | 1637.00 | 3274.33 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1757.24 | 22.77 | 85.67 | 257.50 | 902.07 | 22.40 | 110.33 | 208.50 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2667.04 | 24.06 | 122.83 | 365.17 | 1253.38 | 23.87 | 170.17 | 321.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.57 | 0.48 | 01-JAN-09:30 | 546.89 | 16.23 | 0.00 | 251.83 | 354.45 | 17.91 | 0.00 | 165.67 |
February | 295.50 | 0.55 | 0.48 | 01-FEB-11:00 | 631.62 | 17.40 | 0.00 | 248.50 | 410.83 | 19.00 | 2.67 | 185.00 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:50 | 738.16 | 18.40 | 0.00 | 306.50 | 464.66 | 19.79 | 10.17 | 237.17 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 878.52 | 18.81 | 0.00 | 326.67 | 535.85 | 20.10 | 77.00 | 285.17 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 1077.65 | 21.03 | 55.17 | 370.33 | 621.31 | 22.20 | 186.17 | 330.67 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:40 | 1246.12 | 22.14 | 107.00 | 374.00 | 658.32 | 21.33 | 213.67 | 338.33 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 1218.83 | 20.84 | 79.33 | 376.67 | 662.93 | 22.12 | 238.00 | 340.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1069.93 | 19.57 | 10.50 | 353.33 | 602.11 | 20.87 | 169.83 | 318.17 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:40 | 896.34 | 18.79 | 0.17 | 316.00 | 516.43 | 20.08 | 73.33 | 265.50 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-08:09 | 773.92 | 18.56 | 0.00 | 297.00 | 474.37 | 20.01 | 12.17 | 244.67 |
November | 308.00 | 0.57 | 0.48 | 01-NOV-10:20 | 562.03 | 16.84 | 0.00 | 243.33 | 366.18 | 18.49 | 0.00 | 170.33 |
December | 282.83 | 0.56 | 0.48 | 01-DEC-09:20 | 547.38 | 16.49 | 0.00 | 242.83 | 356.45 | 18.22 | 0.00 | 149.50 |
Annual Sum or Average | 4027.67 | 0.53 | 874.77 | 18.93 | 252.17 | 3707.00 | 513.40 | 20.14 | 983.00 | 3030.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 546.89 | 16.23 | 0.00 | 242.83 | 354.45 | 17.91 | 0.00 | 149.50 | |
Maximum of Months | 394.00 | 0.57 | 0.48 | 1246.12 | 22.14 | 107.00 | 376.67 | 662.93 | 22.20 | 238.00 | 340.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-09:30 | 2286.03 | 24.56 | 112.50 | 275.83 | 1268.23 | 24.46 | 127.67 | 230.50 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 2042.97 | 23.82 | 89.33 | 266.17 | 1078.44 | 23.81 | 127.67 | 234.33 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2191.03 | 23.20 | 81.00 | 311.83 | 1151.71 | 23.51 | 113.50 | 269.83 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:39 | 2475.52 | 21.68 | 82.83 | 327.00 | 1301.08 | 22.09 | 107.33 | 293.83 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-08:09 | 2051.40 | 18.21 | 1.00 | 356.50 | 909.30 | 20.32 | 100.83 | 318.00 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:30 | 2171.45 | 18.07 | 0.67 | 359.00 | 927.78 | 20.12 | 101.33 | 318.67 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:30 | 2009.37 | 18.56 | 6.50 | 366.00 | 895.11 | 20.37 | 120.50 | 322.50 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:00 | 2074.95 | 20.50 | 59.17 | 349.50 | 952.14 | 20.60 | 135.67 | 309.83 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:00 | 1925.32 | 21.92 | 82.33 | 314.83 | 988.07 | 22.31 | 151.50 | 279.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:20 | 2462.04 | 24.56 | 110.67 | 309.50 | 1019.42 | 23.43 | 165.67 | 273.17 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-09:00 | 1983.89 | 23.72 | 96.33 | 267.17 | 1067.58 | 23.77 | 124.33 | 232.00 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-09:20 | 2129.80 | 25.18 | 106.00 | 271.00 | 1151.99 | 24.94 | 124.00 | 219.83 |
Annual Sum or Average | 4027.67 | 0.52 | 2148.70 | 21.76 | 828.33 | 3774.33 | 1050.05 | 22.30 | 1500.00 | 3301.67 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1925.32 | 18.07 | 0.67 | 266.17 | 895.11 | 20.12 | 100.83 | 219.83 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2475.52 | 25.18 | 112.50 | 366.00 | 1301.08 | 24.94 | 165.67 | 322.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7834.86 | 36.47 | 297.33 | 296.17 | 1544.53 | 21.71 | 92.17 | 281.67 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 3434.34 | 24.64 | 165.33 | 280.00 | 1345.10 | 18.88 | 36.50 | 268.17 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1627.82 | 13.73 | 0.00 | 320.33 | 997.59 | 17.33 | 0.00 | 286.50 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:00 | 1288.92 | 13.31 | 0.00 | 324.00 | 779.67 | 16.75 | 0.00 | 290.00 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 1146.96 | 13.53 | 0.00 | 350.50 | 677.52 | 17.01 | 0.00 | 305.83 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:10 | 1089.53 | 13.18 | 0.00 | 351.00 | 647.64 | 16.63 | 0.00 | 308.33 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-06:00 | 1199.42 | 13.41 | 0.00 | 360.33 | 692.10 | 16.84 | 0.00 | 319.00 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1391.52 | 13.68 | 0.00 | 346.83 | 787.64 | 17.07 | 0.00 | 313.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:30 | 1635.18 | 13.84 | 3.67 | 318.17 | 911.49 | 17.08 | 0.00 | 286.83 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2823.25 | 18.71 | 80.67 | 314.83 | 1248.57 | 18.22 | 10.50 | 288.33 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:09 | 7899.02 | 35.88 | 296.00 | 289.17 | 1505.35 | 21.52 | 90.83 | 276.50 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7984.10 | 37.34 | 279.33 | 284.33 | 1937.80 | 23.94 | 110.83 | 268.67 |
Annual Sum or Average | 4027.67 | 0.52 | 3070.55 | 19.89 | 1122.33 | 3835.67 | 1052.36 | 18.40 | 340.83 | 3492.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1089.53 | 13.18 | 0.00 | 280.00 | 647.64 | 16.63 | 0.00 | 268.17 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 7984.10 | 37.34 | 297.33 | 360.33 | 1937.80 | 23.94 | 110.83 | 319.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-07:49 | 2031.25 | 21.13 | 100.17 | 273.00 | 1123.20 | 21.80 | 72.33 | 230.17 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 2253.58 | 20.95 | 89.67 | 262.67 | 1224.15 | 21.77 | 64.33 | 232.17 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2329.30 | 19.41 | 74.33 | 316.33 | 1281.11 | 21.35 | 56.50 | 282.50 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 2387.95 | 19.70 | 95.67 | 327.17 | 1310.10 | 20.70 | 68.00 | 297.17 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2686.51 | 20.36 | 106.00 | 361.33 | 1131.38 | 20.35 | 55.00 | 321.17 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:10 | 2427.19 | 19.81 | 114.00 | 359.50 | 1069.69 | 20.31 | 62.67 | 326.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 2340.26 | 20.05 | 112.33 | 366.67 | 1050.83 | 19.71 | 53.67 | 323.83 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:49 | 2151.22 | 19.97 | 105.17 | 347.83 | 1162.20 | 21.07 | 75.50 | 313.00 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 2069.38 | 20.16 | 96.00 | 314.67 | 1090.79 | 21.10 | 67.50 | 282.17 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2162.62 | 20.40 | 87.67 | 303.33 | 1136.17 | 21.20 | 57.00 | 273.67 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-07:00 | 1792.19 | 19.92 | 84.00 | 267.83 | 947.39 | 20.62 | 55.50 | 235.17 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1920.08 | 20.87 | 89.17 | 258.67 | 1050.52 | 21.54 | 61.67 | 214.83 |
Annual Sum or Average | 4027.67 | 0.52 | 2225.68 | 20.20 | 1154.17 | 3759.00 | 1130.25 | 20.91 | 749.67 | 3332.67 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1792.19 | 19.41 | 74.33 | 258.67 | 947.39 | 19.71 | 53.67 | 214.83 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2686.51 | 21.13 | 114.00 | 366.67 | 1310.10 | 21.80 | 75.50 | 326.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.57 | 0.48 | 01-JAN-09:20 | 556.86 | 10.68 | 0.00 | 253.00 | 377.85 | 14.34 | 0.00 | 181.00 |
February | 295.50 | 0.55 | 0.48 | 01-FEB-11:00 | 644.13 | 11.90 | 0.00 | 249.67 | 438.23 | 15.56 | 0.00 | 194.33 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:39 | 753.78 | 13.09 | 0.00 | 307.83 | 495.88 | 16.63 | 0.00 | 249.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:00 | 897.00 | 13.36 | 0.00 | 327.33 | 571.74 | 16.82 | 0.00 | 292.00 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:10 | 1097.54 | 15.61 | 27.17 | 370.83 | 661.97 | 18.95 | 27.50 | 336.17 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1267.18 | 17.13 | 58.00 | 374.67 | 710.85 | 20.27 | 59.33 | 349.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 1238.40 | 15.24 | 23.50 | 376.67 | 705.25 | 18.57 | 24.50 | 343.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1087.55 | 13.79 | 0.00 | 353.67 | 640.66 | 17.22 | 0.00 | 322.00 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:30 | 911.87 | 13.18 | 0.00 | 316.00 | 549.71 | 16.55 | 0.00 | 271.67 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-07:00 | 787.96 | 13.11 | 0.00 | 297.33 | 505.40 | 16.64 | 0.00 | 252.67 |
November | 308.00 | 0.56 | 0.48 | 01-NOV-10:09 | 572.56 | 11.20 | 0.00 | 245.00 | 390.44 | 14.92 | 0.00 | 182.00 |
December | 282.83 | 0.56 | 0.48 | 01-DEC-09:09 | 556.86 | 10.84 | 0.00 | 244.17 | 379.85 | 14.58 | 0.00 | 162.83 |
Annual Sum or Average | 4027.67 | 0.53 | 890.50 | 13.44 | 108.67 | 3716.17 | 547.90 | 16.92 | 111.33 | 3137.00 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 556.86 | 10.68 | 0.00 | 244.17 | 377.85 | 14.34 | 0.00 | 162.83 | |
Maximum of Months | 394.00 | 0.57 | 0.48 | 1267.18 | 17.13 | 58.00 | 376.67 | 710.85 | 20.27 | 59.33 | 349.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-09:20 | 2320.30 | 22.13 | 109.33 | 277.17 | 1314.89 | 22.66 | 81.83 | 237.67 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 2062.75 | 19.81 | 79.17 | 267.33 | 1132.06 | 21.60 | 60.17 | 237.67 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2242.21 | 20.13 | 81.00 | 313.33 | 1206.06 | 21.10 | 56.67 | 277.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:39 | 2504.94 | 18.35 | 82.00 | 327.67 | 1358.94 | 19.38 | 53.00 | 297.83 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:00 | 2076.07 | 13.66 | 0.00 | 357.33 | 960.29 | 17.09 | 0.00 | 321.33 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:30 | 2199.68 | 13.55 | 0.00 | 359.17 | 979.28 | 16.91 | 0.00 | 324.50 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:19 | 2033.02 | 14.12 | 3.67 | 366.83 | 944.46 | 17.21 | 0.00 | 328.17 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:49 | 2099.03 | 16.80 | 59.00 | 350.83 | 1003.01 | 17.49 | 5.50 | 316.67 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:00 | 1960.43 | 18.69 | 80.50 | 315.67 | 1037.16 | 19.76 | 51.67 | 283.50 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:09 | 2509.10 | 21.87 | 108.83 | 310.17 | 1072.07 | 21.04 | 53.50 | 277.17 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-09:00 | 2019.46 | 21.02 | 95.17 | 268.33 | 1113.25 | 21.73 | 66.67 | 236.33 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-09:09 | 2165.81 | 22.81 | 103.00 | 271.50 | 1199.64 | 23.15 | 74.00 | 226.50 |
Annual Sum or Average | 4027.67 | 0.52 | 2180.65 | 18.27 | 801.67 | 3785.33 | 1100.95 | 19.70 | 503.00 | 3364.50 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1960.43 | 13.55 | 0.00 | 267.33 | 944.46 | 16.91 | 0.00 | 226.50 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2509.10 | 22.81 | 109.33 | 366.83 | 1358.94 | 23.15 | 81.83 | 328.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 7836.49 | 36.46 | 297.33 | 296.17 | 1546.19 | 21.70 | 92.17 | 281.67 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 3436.56 | 24.62 | 165.33 | 280.00 | 1346.70 | 18.87 | 36.33 | 268.17 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1629.92 | 13.70 | 0.00 | 320.50 | 998.93 | 17.31 | 0.00 | 286.50 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:00 | 1290.60 | 13.28 | 0.00 | 324.17 | 780.75 | 16.74 | 0.00 | 290.17 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 1148.50 | 13.50 | 0.00 | 350.83 | 678.51 | 16.99 | 0.00 | 306.00 |
June | 394.00 | 0.53 | 0.48 | 01-JUN-07:10 | 1090.97 | 13.15 | 0.00 | 351.00 | 648.57 | 16.62 | 0.00 | 308.50 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-06:00 | 1201.16 | 13.38 | 0.00 | 360.50 | 693.17 | 16.82 | 0.00 | 319.00 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1393.67 | 13.65 | 0.00 | 347.00 | 788.91 | 17.06 | 0.00 | 313.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:30 | 1637.78 | 13.81 | 3.67 | 318.17 | 913.02 | 17.07 | 0.00 | 287.17 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2826.10 | 18.69 | 80.67 | 314.83 | 1250.42 | 18.21 | 10.50 | 288.33 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:09 | 7900.93 | 35.88 | 296.00 | 289.17 | 1507.00 | 21.51 | 90.83 | 276.50 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7985.69 | 37.33 | 279.33 | 284.33 | 1939.59 | 23.93 | 110.83 | 268.67 |
Annual Sum or Average | 4027.67 | 0.52 | 3072.50 | 19.87 | 1122.33 | 3836.67 | 1053.73 | 18.38 | 340.67 | 3493.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1090.97 | 13.15 | 0.00 | 280.00 | 648.57 | 16.62 | 0.00 | 268.17 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 7985.69 | 37.33 | 297.33 | 360.50 | 1939.59 | 23.93 | 110.83 | 319.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-07:49 | 2031.97 | 21.10 | 100.17 | 273.00 | 1124.05 | 21.78 | 72.33 | 230.50 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 2254.39 | 20.93 | 89.67 | 262.67 | 1225.12 | 21.76 | 64.33 | 232.33 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2330.42 | 19.38 | 74.33 | 316.33 | 1282.27 | 21.34 | 56.50 | 282.67 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 2389.35 | 19.68 | 95.67 | 327.17 | 1311.29 | 20.68 | 68.00 | 297.33 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2688.14 | 20.34 | 106.00 | 361.33 | 1132.72 | 20.34 | 55.00 | 321.33 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:10 | 2428.98 | 19.78 | 114.00 | 359.50 | 1071.06 | 20.30 | 62.67 | 327.17 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 2342.29 | 20.03 | 112.33 | 366.67 | 1052.31 | 19.69 | 53.67 | 324.50 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:49 | 2153.24 | 19.94 | 105.17 | 348.00 | 1163.66 | 21.06 | 75.50 | 313.33 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-06:49 | 2071.33 | 20.14 | 96.00 | 314.67 | 1092.21 | 21.09 | 67.50 | 282.33 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2163.97 | 20.38 | 87.67 | 303.33 | 1137.44 | 21.19 | 57.00 | 273.67 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-07:00 | 1792.96 | 19.89 | 84.00 | 267.83 | 948.28 | 20.60 | 55.50 | 235.67 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1920.79 | 20.84 | 89.17 | 258.67 | 1051.36 | 21.52 | 61.67 | 214.83 |
Annual Sum or Average | 4027.67 | 0.52 | 2227.09 | 20.18 | 1154.17 | 3759.17 | 1131.46 | 20.89 | 749.67 | 3335.67 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1792.96 | 19.38 | 74.33 | 258.67 | 948.28 | 19.69 | 53.67 | 214.83 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2688.14 | 21.10 | 114.00 | 366.67 | 1311.29 | 21.78 | 75.50 | 327.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.57 | 0.48 | 01-JAN-09:20 | 557.19 | 10.65 | 0.00 | 253.00 | 378.25 | 14.33 | 0.00 | 181.17 |
February | 295.50 | 0.55 | 0.48 | 01-FEB-11:00 | 644.51 | 11.87 | 0.00 | 249.67 | 438.68 | 15.55 | 0.00 | 194.33 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:39 | 754.37 | 13.06 | 0.00 | 307.83 | 496.44 | 16.61 | 0.00 | 250.17 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:00 | 897.84 | 13.33 | 0.00 | 327.33 | 572.44 | 16.81 | 0.00 | 292.00 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:10 | 1098.84 | 15.58 | 27.17 | 370.83 | 662.90 | 18.94 | 27.50 | 336.17 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1268.68 | 17.10 | 58.00 | 374.67 | 711.88 | 20.26 | 59.33 | 349.33 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 1240.04 | 15.21 | 23.50 | 376.67 | 706.34 | 18.56 | 24.50 | 343.83 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1088.94 | 13.76 | 0.00 | 353.67 | 641.63 | 17.21 | 0.00 | 322.00 |
September | 342.17 | 0.53 | 0.48 | 01-SEP-07:30 | 912.94 | 13.15 | 0.00 | 316.17 | 550.50 | 16.54 | 0.00 | 272.00 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-07:00 | 788.64 | 13.08 | 0.00 | 297.50 | 506.03 | 16.62 | 0.00 | 252.67 |
November | 308.00 | 0.56 | 0.48 | 01-NOV-10:09 | 572.88 | 11.17 | 0.00 | 245.17 | 390.85 | 14.91 | 0.00 | 182.17 |
December | 282.83 | 0.56 | 0.48 | 01-DEC-09:09 | 557.15 | 10.81 | 0.00 | 244.17 | 380.25 | 14.56 | 0.00 | 162.83 |
Annual Sum or Average | 4027.67 | 0.53 | 891.41 | 13.41 | 108.67 | 3716.67 | 548.63 | 16.90 | 111.33 | 3138.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 557.15 | 10.65 | 0.00 | 244.17 | 378.25 | 14.33 | 0.00 | 162.83 | |
Maximum of Months | 394.00 | 0.57 | 0.48 | 1268.68 | 17.10 | 58.00 | 376.67 | 711.88 | 20.26 | 59.33 | 349.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-09:20 | 2321.02 | 22.10 | 109.33 | 277.17 | 1315.74 | 22.65 | 81.83 | 237.67 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 2063.64 | 19.78 | 79.17 | 267.33 | 1133.06 | 21.59 | 60.17 | 237.67 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 2243.37 | 20.10 | 81.00 | 313.33 | 1207.16 | 21.08 | 56.67 | 277.33 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:39 | 2506.37 | 18.32 | 82.00 | 327.67 | 1360.17 | 19.37 | 53.00 | 298.00 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:00 | 2077.79 | 13.62 | 0.00 | 357.33 | 1143.15 | 17.07 | 0.00 | 321.50 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:30 | 2201.42 | 13.52 | 0.00 | 359.17 | 980.57 | 16.89 | 0.00 | 324.67 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:19 | 2035.05 | 14.08 | 3.67 | 366.83 | 953.48 | 17.19 | 0.00 | 328.17 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:49 | 2101.10 | 16.77 | 59.00 | 350.83 | 1130.82 | 17.48 | 5.50 | 316.67 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:00 | 1962.27 | 18.66 | 80.50 | 315.83 | 1038.51 | 19.75 | 51.67 | 283.67 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:09 | 2510.50 | 21.84 | 108.83 | 310.17 | 1073.35 | 21.03 | 53.50 | 277.17 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-09:00 | 2020.19 | 20.99 | 95.17 | 268.33 | 1114.12 | 21.71 | 66.67 | 236.83 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-09:09 | 2166.51 | 22.79 | 103.00 | 271.50 | 1200.49 | 23.14 | 74.00 | 226.50 |
Annual Sum or Average | 4027.67 | 0.52 | 2182.06 | 18.24 | 801.67 | 3785.50 | 1130.76 | 19.69 | 503.00 | 3365.83 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1962.27 | 13.52 | 0.00 | 267.33 | 953.48 | 16.89 | 0.00 | 226.50 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2510.50 | 22.79 | 109.33 | 366.83 | 1360.17 | 23.14 | 81.83 | 328.17 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126095E+10 | 70961.58 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102910E+10 | 71005.69 | 06-FEB-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.574575E+09 | 70832.13 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10439782.92 | 2444.89 | 24-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.705939E+09 | 70957.94 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.358100E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126095E+10 | 71005.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 52283153.89 | 6968.36 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13346711.51 | 1521.15 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1002318.34 | 445.54 | 09-MAR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14579485.08 | 2410.56 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81211668.81 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52283153.89 | 6968.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 84709376.00 | 6444.37 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26843511.14 | 6376.29 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35059865.14 | 1612.99 | 11-MAR-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53030740.46 | 6460.71 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199643E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84709376.00 | 6460.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 71078952.08 | 9914.01 | 10-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28545042.09 | 9912.80 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21418294.77 | 1515.79 | 09-MAR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31547591.98 | 8061.94 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152590E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 71078952.08 | 9914.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 20052863.29 | 1787.44 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20052863.29 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20052863.29 | 1787.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112083E+11 | 133260.58 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.542197E+10 | 135822.38 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.391140E+10 | 136279.89 | 10-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25654926.01 | 6170.79 | 03-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36772048.35 | 7262.05 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.676699E+09 | 59284.14 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.687259E+10 | 133085.32 | 04-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281534E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112083E+11 | 136279.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.657744E+10 | 129701.11 | 10-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.297522E+10 | 130964.16 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.307789E+10 | 129582.51 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27423121.07 | 7036.15 | 11-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57680818.68 | 14864.53 | 28-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.409882E+09 | 35812.01 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.518146E+10 | 129711.85 | 21-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183070E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.657744E+10 | 130964.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342634E+10 | 148638.17 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168468E+10 | 148457.54 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248734E+10 | 148624.53 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18516180.28 | 8107.41 | 16-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.226035E+10 | 148627.30 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.987723E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342634E+10 | 148638.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.620012E+10 | 124178.57 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285529E+10 | 124200.19 | 06-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239890E+10 | 124062.78 | 11-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31259770.67 | 5537.75 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.303650E+09 | 18509.44 | 16-NOV-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.370569E+10 | 124173.33 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154949E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.620012E+10 | 124200.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.261936E+10 | 15159.66 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145927E+10 | 15123.75 | 07-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101696E+10 | 15127.97 | 13-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 55138651.18 | 15074.16 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 48825865.47 | 11561.17 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.363944E+09 | 15114.29 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.179425E+10 | 15057.75 | 04-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.735775E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.261936E+10 | 15159.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137399E+10 | 14747.89 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.764244E+09 | 14742.70 | 18-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.665929E+09 | 14740.82 | 13-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32665553.83 | 3934.71 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31286421.35 | 7571.24 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193905E+09 | 14744.92 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115325E+10 | 14747.06 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421527E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137399E+10 | 14747.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103437E+10 | 17194.46 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.651490E+09 | 17048.72 | 06-FEB-05:29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.737848E+09 | 17048.06 | 11-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34247318.97 | 2853.42 | 11-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19434256.69 | 3711.10 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106202E+09 | 16979.26 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798834E+09 | 17094.19 | 30-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.338243E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103437E+10 | 17194.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144077E+10 | 14979.18 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.763406E+09 | 14962.26 | 18-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.606498E+09 | 14964.42 | 11-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15698319.09 | 1447.95 | 11-APR-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29406676.73 | 2100.68 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199914E+09 | 13099.13 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.984194E+09 | 14978.45 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.403988E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144077E+10 | 14979.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.605173E+09 | 240839.01 | 16-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.773563E+09 | 240379.25 | 13-FEB-01:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.556525E+09 | 238745.32 | 05-MAR-20:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.646316E+09 | 240831.99 | 09-APR-19:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.889694E+09 | 238709.88 | 29-MAY-20:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.747866E+09 | 237753.71 | 25-JUN-21:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115253E+10 | 237840.62 | 16-JUL-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.795159E+09 | 240559.73 | 20-AUG-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.121903E+10 | 238953.57 | 24-SEP-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136297E+10 | 240824.68 | 01-OCT-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172334E+10 | 240834.81 | 26-NOV-22:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178776E+10 | 240835.21 | 24-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122599E+11 | |||||||
Minimum of Months | 0.556525E+09 | 237753.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178776E+10 | 240839.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.250875E+09 | 26852.49 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120084E+09 | 26774.98 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96751084.64 | 26788.34 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8938309.03 | 5976.43 | 18-APR-14:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 50364.64 | 83.94 | 06-AUG-23:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1934895.78 | 2731.21 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7786735.95 | 9075.20 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123741E+09 | 26965.85 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.610161E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.250875E+09 | 26965.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.271718E+10 | 259734.55 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165665E+10 | 259018.03 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181696E+10 | 259154.57 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118733E+09 | 79815.45 | 18-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25141416.02 | 41640.02 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.324263E+09 | 110621.28 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.275981E+10 | 260958.85 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.941874E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.275981E+10 | 260958.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180549E+09 | 25174.19 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74749908.84 | 24878.39 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 73028907.68 | 24861.86 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4678799.18 | 7770.85 | 11-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2574022.73 | 4224.90 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9101712.98 | 11265.83 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106411E+09 | 25545.57 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451093E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180549E+09 | 25545.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.234629E+11 | 0.181295E+11 | 153544.06 | 01-JAN-16:51 | 114499.52 | 0.18 |
February | 0.00 | 0.00 | 0.284499E+11 | 0.227837E+11 | 165478.04 | 26-FEB-16:10 | 97487.10 | 0.28 |
March | 0.00 | 0.00 | 0.395541E+11 | 0.338863E+11 | 176346.40 | 07-MAR-04:01 | 103264.36 | 0.28 |
April | 0.00 | 0.00 | 0.614734E+11 | 0.539286E+11 | 180448.83 | 28-APR-03:01 | 100691.04 | 0.46 |
May | 0.00 | 0.00 | 0.112542E+12 | 0.893279E+11 | 207432.68 | 21-MAY-16:47 | 109100.87 | 0.63 |
June | 0.00 | 0.00 | 0.117088E+12 | 0.903051E+11 | 206336.76 | 18-JUN-15:18 | 109510.05 | 0.64 |
July | 0.00 | 0.00 | 0.125999E+12 | 0.922066E+11 | 211997.68 | 02-JUL-14:10 | 108119.43 | 0.63 |
August | 0.00 | 0.00 | 0.137052E+12 | 0.102466E+12 | 207763.50 | 06-AUG-07:57 | 109359.62 | 0.67 |
September | 0.00 | 0.00 | 0.119202E+12 | 0.897627E+11 | 204113.34 | 17-SEP-09:00 | 108860.92 | 0.65 |
October | 0.00 | 0.00 | 0.103346E+12 | 0.817848E+11 | 199871.15 | 08-OCT-07:51 | 102674.11 | 0.57 |
November | 0.00 | 0.00 | 0.577016E+11 | 0.484264E+11 | 182388.66 | 11-NOV-10:11 | 107122.43 | 0.41 |
December | 0.00 | 0.00 | 0.384024E+11 | 0.319913E+11 | 175581.52 | 15-DEC-05:11 | 106670.45 | 0.27 |
Annual Sum or Average | 0.964274E+12 | 0.754999E+12 | 0.47 | |||||
Minimum of Months | 0.00 | 0.00 | 0.234629E+11 | 0.181295E+11 | 153544.06 | 97487.10 | 0.18 | |
Maximum of Months | 0.00 | 0.00 | 0.137052E+12 | 0.102466E+12 | 211997.68 | 114499.52 | 0.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.450995E+11 | 0.324025E+11 | 142157.48 | 31-JAN-05:12 | 113312.22 | 0.28 |
February | 0.00 | 0.00 | 0.634073E+11 | 0.439974E+11 | 153720.36 | 03-FEB-04:01 | 119551.70 | 0.43 |
March | 0.00 | 0.00 | 0.787557E+11 | 0.591429E+11 | 163642.80 | 27-MAR-04:11 | 149161.45 | 0.41 |
April | 0.00 | 0.00 | 0.125623E+12 | 0.955073E+11 | 159430.49 | 24-APR-11:00 | 85837.02 | 0.65 |
May | 0.00 | 0.00 | 0.164748E+12 | 0.120238E+12 | 212799.67 | 23-MAY-03:01 | 149605.52 | 0.67 |
June | 0.00 | 0.00 | 0.176548E+12 | 0.132398E+12 | 178735.26 | 08-JUN-04:11 | 142816.74 | 0.76 |
July | 0.00 | 0.00 | 0.191522E+12 | 0.140815E+12 | 194064.67 | 26-JUL-05:02 | 157844.39 | 0.80 |
August | 0.00 | 0.00 | 0.207654E+12 | 0.154276E+12 | 190380.97 | 08-AUG-05:02 | 158104.48 | 0.85 |
September | 0.00 | 0.00 | 0.167214E+12 | 0.112855E+12 | 229352.57 | 05-SEP-03:02 | 155148.14 | 0.68 |
October | 0.00 | 0.00 | 0.152029E+12 | 0.113321E+12 | 209969.85 | 13-OCT-04:02 | 162918.67 | 0.63 |
November | 0.00 | 0.00 | 0.956431E+11 | 0.738582E+11 | 176098.29 | 01-NOV-04:11 | 146816.95 | 0.51 |
December | 0.00 | 0.00 | 0.706727E+11 | 0.527899E+11 | 160788.39 | 15-DEC-06:02 | 141214.03 | 0.37 |
Annual Sum or Average | 0.153892E+13 | 0.113160E+13 | 0.59 | |||||
Minimum of Months | 0.00 | 0.00 | 0.450995E+11 | 0.324025E+11 | 142157.48 | 85837.02 | 0.28 | |
Maximum of Months | 0.00 | 0.00 | 0.207654E+12 | 0.154276E+12 | 229352.57 | 162918.67 | 0.85 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.356664E+12 | 0.245289E+12 | 1225284.84 | 19-JAN-06:03 | 948862.18 | 0.26 |
February | 0.00 | 0.00 | 0.503432E+12 | 0.331853E+12 | 1326345.22 | 27-FEB-06:02 | 1127376.59 | 0.40 |
March | 0.00 | 0.00 | 0.600063E+12 | 0.425378E+12 | 1676226.98 | 27-MAR-05:02 | 1217134.51 | 0.37 |
April | 0.00 | 0.00 | 0.938140E+12 | 0.660507E+12 | 1714941.47 | 29-APR-04:11 | 1344885.31 | 0.52 |
May | 0.00 | 0.00 | 0.148979E+13 | 0.104054E+13 | 2416038.87 | 22-MAY-03:02 | 1348588.78 | 0.63 |
June | 0.00 | 0.00 | 0.152111E+13 | 0.107698E+13 | 1993644.94 | 10-JUN-05:02 | 1459198.08 | 0.66 |
July | 0.00 | 0.00 | 0.158918E+13 | 0.106850E+13 | 1952866.27 | 25-JUL-04:03 | 1360377.60 | 0.65 |
August | 0.00 | 0.00 | 0.164942E+13 | 0.110960E+13 | 2231522.10 | 16-AUG-04:11 | 1353369.09 | 0.66 |
September | 0.00 | 0.00 | 0.149734E+13 | 0.949184E+12 | 2452091.72 | 05-SEP-04:11 | 1352467.29 | 0.63 |
October | 0.00 | 0.00 | 0.127741E+13 | 0.893342E+12 | 2097272.41 | 21-OCT-04:11 | 1316074.65 | 0.55 |
November | 0.00 | 0.00 | 0.737943E+12 | 0.541630E+12 | 1603597.28 | 08-NOV-05:12 | 637162.20 | 0.46 |
December | 0.00 | 0.00 | 0.522920E+12 | 0.358669E+12 | 1586007.44 | 11-DEC-06:02 | 1163524.92 | 0.31 |
Annual Sum or Average | 0.126834E+14 | 0.870148E+13 | 0.51 | |||||
Minimum of Months | 0.00 | 0.00 | 0.356664E+12 | 0.245289E+12 | 1225284.84 | 637162.20 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.164942E+13 | 0.110960E+13 | 2452091.72 | 1459198.08 | 0.66 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.361328E+11 | 0.241018E+11 | 141847.18 | 19-JAN-15:00 | 87274.80 | 0.25 |
February | 0.00 | 0.00 | 0.515349E+11 | 0.335145E+11 | 140790.51 | 24-FEB-16:00 | 92249.70 | 0.39 |
March | 0.00 | 0.00 | 0.625148E+11 | 0.437949E+11 | 171069.13 | 27-MAR-05:01 | 128645.69 | 0.37 |
April | 0.00 | 0.00 | 0.989662E+11 | 0.705300E+11 | 166446.38 | 29-APR-04:11 | 125942.29 | 0.51 |
May | 0.00 | 0.00 | 0.162768E+12 | 0.116608E+12 | 258447.25 | 22-MAY-03:02 | 145797.42 | 0.64 |
June | 0.00 | 0.00 | 0.168205E+12 | 0.122574E+12 | 202943.05 | 05-JUN-03:02 | 147163.87 | 0.66 |
July | 0.00 | 0.00 | 0.175074E+12 | 0.120838E+12 | 239477.14 | 31-JUL-03:01 | 144766.18 | 0.66 |
August | 0.00 | 0.00 | 0.179868E+12 | 0.124230E+12 | 231211.80 | 16-AUG-04:11 | 132917.75 | 0.66 |
September | 0.00 | 0.00 | 0.159507E+12 | 0.103199E+12 | 265812.50 | 05-SEP-04:11 | 143335.08 | 0.64 |
October | 0.00 | 0.00 | 0.135147E+12 | 0.960374E+11 | 213891.78 | 14-OCT-05:02 | 137029.55 | 0.55 |
November | 0.00 | 0.00 | 0.733722E+11 | 0.536459E+11 | 182520.58 | 01-NOV-05:02 | 128607.18 | 0.45 |
December | 0.00 | 0.00 | 0.517422E+11 | 0.351332E+11 | 165635.39 | 11-DEC-06:01 | 119851.01 | 0.31 |
Annual Sum or Average | 0.135483E+13 | 0.944206E+12 | 0.51 | |||||
Minimum of Months | 0.00 | 0.00 | 0.361328E+11 | 0.241018E+11 | 140790.51 | 87274.80 | 0.25 | |
Maximum of Months | 0.00 | 0.00 | 0.179868E+12 | 0.124230E+12 | 265812.50 | 147163.87 | 0.66 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.316839E+12 | 0.314939E+12 | 127581.15 | 31-JAN-16:40 | 120161.77 | 0.00 |
February | 0.00 | 0.00 | 0.500132E+12 | 0.496529E+12 | 215083.62 | 24-FEB-17:00 | 207844.15 | 0.00 |
March | 0.00 | 0.00 | 0.788936E+12 | 0.785295E+12 | 303935.16 | 30-MAR-14:10 | 296207.97 | 0.00 |
April | 0.00 | 0.00 | 0.994431E+12 | 0.989738E+12 | 402062.68 | 28-APR-17:40 | 386655.04 | 0.00 |
May | 0.00 | 0.00 | 0.331388E+12 | 0.321387E+12 | 134672.10 | 01-MAY-16:00 | 125753.74 | 0.00 |
June | 0.00 | 0.00 | 0.549217E+12 | 0.538045E+12 | 223543.96 | 29-JUN-15:00 | 208507.41 | 0.00 |
July | 0.00 | 0.00 | 0.804575E+12 | 0.792175E+12 | 311176.14 | 12-JUL-12:30 | 297199.41 | 0.00 |
August | 0.00 | 0.00 | 0.103780E+13 | 0.102639E+13 | 404848.78 | 07-AUG-13:50 | 388130.73 | 0.00 |
September | 0.00 | 0.00 | 0.324792E+12 | 0.313844E+12 | 137807.16 | 01-SEP-00:10 | 136295.64 | 0.00 |
October | 0.00 | 0.00 | 0.566541E+12 | 0.558070E+12 | 224430.08 | 24-OCT-14:20 | 211214.94 | 0.00 |
November | 0.00 | 0.00 | 0.769678E+12 | 0.765750E+12 | 308225.63 | 03-NOV-17:00 | 297167.32 | 0.00 |
December | 0.00 | 0.00 | 0.102763E+13 | 0.102496E+13 | 395087.45 | 12-DEC-15:00 | 385242.75 | 0.00 |
Annual Sum or Average | 0.801195E+13 | 0.792712E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.316839E+12 | 0.313844E+12 | 127581.15 | 120161.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103780E+13 | 0.102639E+13 | 404848.78 | 388130.73 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.489459E+10 | 0.489441E+10 | 2470.84 | 01-JAN-17:15 | 2470.84 | 0.00 |
February | 0.00 | 0.00 | 0.907001E+10 | 0.906991E+10 | 4500.81 | 26-FEB-17:54 | 4500.81 | 0.00 |
March | 0.00 | 0.00 | 0.150642E+11 | 0.150642E+11 | 6056.46 | 05-MAR-17:45 | 6056.46 | 0.00 |
April | 0.00 | 0.00 | 0.194710E+11 | 0.194710E+11 | 8189.92 | 16-APR-18:20 | 8189.92 | 0.00 |
May | 0.00 | 0.00 | 0.566975E+10 | 0.566975E+10 | 2512.23 | 29-MAY-18:13 | 2512.23 | 0.00 |
June | 0.00 | 0.00 | 0.101613E+11 | 0.101613E+11 | 4305.48 | 11-JUN-18:25 | 4305.48 | 0.00 |
July | 0.00 | 0.00 | 0.153396E+11 | 0.153396E+11 | 6039.55 | 23-JUL-18:54 | 6039.55 | 0.00 |
August | 0.00 | 0.00 | 0.202291E+11 | 0.202291E+11 | 7880.84 | 06-AUG-17:47 | 7880.84 | 0.00 |
September | 0.00 | 0.00 | 0.549780E+10 | 0.549780E+10 | 2594.86 | 03-SEP-17:55 | 2594.86 | 0.00 |
October | 0.00 | 0.00 | 0.105145E+11 | 0.105145E+11 | 4390.77 | 01-OCT-17:33 | 4390.77 | 0.00 |
November | 0.00 | 0.00 | 0.147462E+11 | 0.147462E+11 | 6227.64 | 12-NOV-17:07 | 6227.64 | 0.00 |
December | 0.00 | 0.00 | 0.199650E+11 | 0.199650E+11 | 8058.94 | 10-DEC-17:10 | 8058.94 | 0.00 |
Annual Sum or Average | 0.150623E+12 | 0.150623E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.489459E+10 | 0.489441E+10 | 2470.84 | 2470.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202291E+11 | 0.202291E+11 | 8189.92 | 8189.92 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.347878E+11 | 0.347861E+11 | 21960.75 | 31-JAN-17:50 | 21960.75 | 0.00 |
February | 0.00 | 0.00 | 0.766950E+11 | 0.766939E+11 | 40928.23 | 26-FEB-18:00 | 40928.23 | 0.00 |
March | 0.00 | 0.00 | 0.135152E+12 | 0.135152E+12 | 56827.66 | 06-MAR-18:00 | 56827.66 | 0.00 |
April | 0.00 | 0.00 | 0.182661E+12 | 0.182661E+12 | 76422.26 | 16-APR-18:20 | 76422.26 | 0.00 |
May | 0.00 | 0.00 | 0.516372E+11 | 0.516372E+11 | 22908.65 | 14-MAY-18:23 | 22908.65 | 0.00 |
June | 0.00 | 0.00 | 0.958574E+11 | 0.958574E+11 | 40525.58 | 11-JUN-18:27 | 40525.58 | 0.00 |
July | 0.00 | 0.00 | 0.145862E+12 | 0.145862E+12 | 56590.60 | 16-JUL-19:00 | 56590.60 | 0.00 |
August | 0.00 | 0.00 | 0.192596E+12 | 0.192596E+12 | 74820.41 | 30-AUG-18:40 | 74820.41 | 0.00 |
September | 0.00 | 0.00 | 0.492463E+11 | 0.492463E+11 | 24034.55 | 03-SEP-17:55 | 24034.55 | 0.00 |
October | 0.00 | 0.00 | 0.969803E+11 | 0.969803E+11 | 41000.71 | 09-OCT-17:28 | 41000.71 | 0.00 |
November | 0.00 | 0.00 | 0.133324E+12 | 0.133324E+12 | 58354.37 | 06-NOV-17:00 | 58354.37 | 0.00 |
December | 0.00 | 0.00 | 0.179938E+12 | 0.179938E+12 | 74988.06 | 15-DEC-17:00 | 74988.06 | 0.00 |
Annual Sum or Average | 0.137474E+13 | 0.137473E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.347878E+11 | 0.347861E+11 | 21960.75 | 21960.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.192596E+12 | 0.192596E+12 | 76422.26 | 76422.26 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.253000E+10 | 0.252986E+10 | 2274.33 | 31-JAN-17:50 | 2274.33 | 0.00 |
February | 0.00 | 0.00 | 0.695537E+10 | 0.695527E+10 | 4093.56 | 26-FEB-18:00 | 4093.56 | 0.00 |
March | 0.00 | 0.00 | 0.130081E+11 | 0.130081E+11 | 5755.77 | 06-MAR-17:50 | 5755.77 | 0.00 |
April | 0.00 | 0.00 | 0.181245E+11 | 0.181245E+11 | 7748.27 | 23-APR-18:08 | 7748.27 | 0.00 |
May | 0.00 | 0.00 | 0.528857E+10 | 0.528857E+10 | 2552.19 | 29-MAY-17:56 | 2552.19 | 0.00 |
June | 0.00 | 0.00 | 0.972832E+10 | 0.972832E+10 | 4298.66 | 11-JUN-18:30 | 4298.66 | 0.00 |
July | 0.00 | 0.00 | 0.147381E+11 | 0.147381E+11 | 5882.29 | 16-JUL-18:47 | 5882.29 | 0.00 |
August | 0.00 | 0.00 | 0.193693E+11 | 0.193693E+11 | 7620.19 | 06-AUG-17:34 | 7620.19 | 0.00 |
September | 0.00 | 0.00 | 0.500729E+10 | 0.500729E+10 | 2623.96 | 03-SEP-17:55 | 2623.96 | 0.00 |
October | 0.00 | 0.00 | 0.962269E+10 | 0.962269E+10 | 4303.96 | 09-OCT-17:24 | 4303.96 | 0.00 |
November | 0.00 | 0.00 | 0.128177E+11 | 0.128177E+11 | 5904.43 | 06-NOV-17:00 | 5904.43 | 0.00 |
December | 0.00 | 0.00 | 0.172053E+11 | 0.172053E+11 | 7572.17 | 15-DEC-17:00 | 7572.17 | 0.00 |
Annual Sum or Average | 0.134395E+12 | 0.134395E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.253000E+10 | 0.252986E+10 | 2274.33 | 2274.33 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.193693E+11 | 0.193693E+11 | 7748.27 | 7748.27 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7565.14 | 38177.88 | 01-JAN-07:50 | 10271.27 | 42420.95 | 23-JAN-12:20 |
February | 7245.91 | 38213.85 | 26-FEB-07:50 | 10221.54 | 42349.11 | 01-FEB-12:20 |
March | 6096.37 | 38339.74 | 26-MAR-06:50 | 10531.02 | 41390.56 | 01-MAR-12:40 |
April | 7389.21 | 38547.41 | 30-APR-06:35 | 8938.20 | 39156.80 | 03-APR-11:30 |
May | 7374.83 | 38712.80 | 29-MAY-06:36 | 8564.00 | 36761.71 | 01-MAY-11:20 |
June | 6942.06 | 38823.06 | 25-JUN-06:35 | 8144.72 | 34286.14 | 01-JUN-11:20 |
July | 8775.71 | 38867.19 | 23-JUL-06:35 | 6924.07 | 32626.32 | 03-JUL-11:50 |
August | 6937.02 | 38858.67 | 06-AUG-06:37 | 7997.52 | 33274.29 | 31-AUG-12:00 |
September | 7785.40 | 38782.93 | 03-SEP-06:35 | 7791.12 | 35299.25 | 29-SEP-11:30 |
October | 8097.76 | 38645.10 | 01-OCT-06:40 | 8535.70 | 38016.58 | 31-OCT-11:20 |
November | 7956.29 | 38434.12 | 05-NOV-06:50 | 9497.83 | 40409.79 | 30-NOV-12:30 |
December | 7736.09 | 38281.19 | 03-DEC-07:50 | 9615.66 | 42941.31 | 29-DEC-13:30 |
Annual Sum or Average | 7493.55 | 8912.26 | ||||
Minimum of Months | 6096.37 | 38177.88 | 6924.07 | 32626.32 | ||
Maximum of Months | 8775.71 | 38867.19 | 10531.02 | 42941.31 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 14362.40 | 1563974.32 | 09-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 8392.59 | 1344478.96 | 18-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 6671.38 | 1447843.81 | 11-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 372.84 | 415528.47 | 16-APR-21:10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 329.73 | 248039.09 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 283.46 | 232569.33 | 04-JUN-14:56 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 422.76 | 231776.65 | 09-JUL-20:47 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 291.02 | 232702.29 | 27-AUG-21:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 461.56 | 233460.84 | 24-SEP-22:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 594.62 | 490037.04 | 29-OCT-13:58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1623.89 | 797899.72 | 19-NOV-10:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10474.27 | 1651973.81 | 20-DEC-05:11 |
Annual Sum or Average | 0.00 | 3684.32 | ||||
Minimum of Months | 0.00 | 0.00 | 283.46 | 231776.65 | ||
Maximum of Months | 0.00 | 0.00 | 14362.40 | 1651973.81 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 183487.74 | 1830957.91 | 19-JAN-10:40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 286051.52 | 1844440.86 | 24-FEB-11:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 312707.62 | 1811946.48 | 29-MAR-10:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 508503.65 | 2014684.78 | 28-APR-07:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 778250.78 | 3496498.90 | 23-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 819275.23 | 2595468.45 | 24-JUN-05:04 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 821023.52 | 2430930.51 | 01-JUL-05:04 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 860611.71 | 2612782.17 | 15-AUG-05:04 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 802901.17 | 2736798.68 | 06-SEP-05:04 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 661520.79 | 2250781.31 | 24-OCT-05:05 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 393619.09 | 1847563.14 | 29-NOV-06:06 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 273220.00 | 2021136.54 | 11-DEC-14:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 559873.71 | 0.00 | ||||
Minimum of Months | 183487.74 | 1811946.48 | 0.00 | 0.00 | ||
Maximum of Months | 860611.71 | 3496498.90 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 181952.87 | 1895836.63 | 19-JAN-10:40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 284033.93 | 1909011.23 | 24-FEB-11:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 310221.93 | 2692892.92 | 27-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 504843.98 | 2405963.77 | 29-APR-04:11 | 0.00 | 0.00 | 01-APR-00:10 |
May | 773287.77 | 4564125.94 | 22-MAY-03:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 813971.22 | 4075239.49 | 30-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 815386.83 | 3465324.18 | 25-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 855360.55 | 4155865.94 | 18-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 798793.80 | 4232203.52 | 06-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 657587.92 | 4162282.87 | 24-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 390584.78 | 2314646.78 | 08-NOV-05:12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 270782.03 | 2509682.63 | 11-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 556166.41 | 0.00 | ||||
Minimum of Months | 181952.87 | 1895836.63 | 0.00 | 0.00 | ||
Maximum of Months | 855360.55 | 4564125.94 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 225872.78 | 703776.68 | 02-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 419434.94 | 980078.83 | 02-FEB-13:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 646642.40 | 1281492.32 | 26-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1015991.12 | 1697082.77 | 28-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 698105.66 | 1058429.00 | 28-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 945177.06 | 1355988.35 | 14-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1181381.04 | 1659350.66 | 21-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1372919.37 | 1846589.28 | 30-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 666025.79 | 1213064.99 | 09-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 771002.79 | 1308682.65 | 05-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 709670.54 | 1309466.13 | 02-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 789159.55 | 1514615.69 | 13-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 789281.38 | 0.00 | ||||
Minimum of Months | 225872.78 | 703776.68 | 0.00 | 0.00 | ||
Maximum of Months | 1372919.37 | 1846589.28 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 296400.18 | 4240777.65 | 19-JAN-10:40 | 1168.73 | 152878.09 | 04-JAN-21:20 |
February | 446567.60 | 4237033.72 | 24-FEB-11:30 | 836.16 | 125903.66 | 04-FEB-07:00 |
March | 536781.06 | 4902696.09 | 30-MAR-12:30 | 1355.86 | 165801.56 | 09-MAR-07:20 |
April | 923012.54 | 6525035.18 | 28-APR-16:00 | 350.03 | 101147.48 | 03-APR-06:10 |
May | 2030864.46 | 6710097.50 | 26-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 2386324.89 | 7146512.82 | 28-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2790822.20 | 7456839.03 | 03-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 2741375.12 | 7383134.53 | 07-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2282470.22 | 7257384.14 | 18-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 1748019.55 | 7642382.03 | 06-OCT-14:10 | 75.57 | 50101.02 | 27-OCT-19:40 |
November | 788210.81 | 6172350.21 | 01-NOV-13:40 | 421.34 | 121404.78 | 22-NOV-08:40 |
December | 506184.27 | 5707150.84 | 12-DEC-14:20 | 1303.96 | 155175.64 | 18-DEC-09:10 |
Annual Sum or Average | 1463200.82 | 459.13 | ||||
Minimum of Months | 296400.18 | 4237033.72 | 0.00 | 0.00 | ||
Maximum of Months | 2790822.20 | 7642382.03 | 1355.86 | 165801.56 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.162290E+11 | 0.86 | 9753.45 | 01-JAN-00:11 | 1.38 |
February | 0.143126E+11 | 0.84 | 9753.45 | 01-FEB-04:01 | 1.38 |
March | 0.164039E+11 | 0.87 | 9753.45 | 01-MAR-04:01 | 1.38 |
April | 0.152456E+11 | 0.83 | 9753.45 | 01-APR-03:01 | 1.38 |
May | 0.169214E+11 | 0.89 | 9753.45 | 01-MAY-00:10 | 1.38 |
June | 0.164078E+11 | 0.89 | 9753.45 | 01-JUN-03:01 | 1.38 |
July | 0.167606E+11 | 0.88 | 9753.45 | 01-JUL-03:01 | 1.38 |
August | 0.178224E+11 | 0.94 | 9753.45 | 01-AUG-03:01 | 1.38 |
September | 0.169083E+11 | 0.92 | 9753.45 | 01-SEP-03:01 | 1.38 |
October | 0.175086E+11 | 0.92 | 9753.45 | 01-OCT-07:51 | 1.38 |
November | 0.168409E+11 | 0.92 | 9753.45 | 01-NOV-03:01 | 1.38 |
December | 0.168575E+11 | 0.89 | 9753.45 | 01-DEC-04:01 | 1.39 |
Annual Sum or Average | 0.198219E+12 | 0.89 | |||
Minimum of Months | 0.143126E+11 | 0.83 | 9753.45 | 1.38 | |
Maximum of Months | 0.178224E+11 | 0.94 | 9753.45 | 1.39 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.407037E+10 | 0.33 | 12368.98 | 02-JAN-05:12 | 1.32 |
February | 0.413941E+10 | 0.35 | 13909.20 | 28-FEB-05:11 | 1.42 |
March | 0.513503E+10 | 0.39 | 19528.15 | 27-MAR-04:11 | 1.76 |
April | 0.598217E+10 | 0.44 | 16339.98 | 28-APR-04:11 | 1.57 |
May | 0.613684E+10 | 0.43 | 19528.15 | 02-MAY-03:01 | 1.76 |
June | 0.676698E+10 | 0.49 | 19528.15 | 02-JUN-05:01 | 1.76 |
July | 0.718932E+10 | 0.51 | 19528.15 | 01-JUL-05:01 | 1.76 |
August | 0.829194E+10 | 0.56 | 19528.15 | 01-AUG-05:01 | 1.76 |
September | 0.581197E+10 | 0.43 | 19528.15 | 01-SEP-04:11 | 1.76 |
October | 0.660985E+10 | 0.45 | 19528.15 | 04-OCT-04:11 | 1.76 |
November | 0.565623E+10 | 0.41 | 19528.15 | 01-NOV-04:11 | 1.76 |
December | 0.527697E+10 | 0.39 | 19051.66 | 11-DEC-06:01 | 1.73 |
Annual Sum or Average | 0.710671E+11 | 0.43 | |||
Minimum of Months | 0.407037E+10 | 0.33 | 12368.98 | 1.32 | |
Maximum of Months | 0.829194E+10 | 0.56 | 19528.15 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.307216E+11 | 0.30 | 102282.22 | 02-JAN-06:03 | 1.23 |
February | 0.292255E+11 | 0.30 | 155543.38 | 27-FEB-06:01 | 1.60 |
March | 0.342934E+11 | 0.32 | 180050.81 | 27-MAR-05:01 | 1.76 |
April | 0.376983E+11 | 0.33 | 180050.81 | 28-APR-04:11 | 1.76 |
May | 0.527052E+11 | 0.40 | 180050.81 | 06-MAY-03:01 | 1.76 |
June | 0.544898E+11 | 0.42 | 180050.81 | 06-JUN-04:11 | 1.76 |
July | 0.531142E+11 | 0.41 | 180050.81 | 08-JUL-05:01 | 1.76 |
August | 0.569166E+11 | 0.42 | 180050.81 | 02-AUG-03:01 | 1.76 |
September | 0.476834E+11 | 0.39 | 180050.81 | 01-SEP-03:01 | 1.76 |
October | 0.500215E+11 | 0.38 | 180050.81 | 04-OCT-04:11 | 1.76 |
November | 0.369961E+11 | 0.33 | 180050.81 | 03-NOV-04:11 | 1.76 |
December | 0.328313E+11 | 0.30 | 155543.38 | 11-DEC-06:01 | 1.60 |
Annual Sum or Average | 0.516697E+12 | 0.36 | |||
Minimum of Months | 0.292255E+11 | 0.30 | 102282.22 | 1.23 | |
Maximum of Months | 0.569166E+11 | 0.42 | 180050.81 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.294521E+10 | 0.29 | 9106.31 | 02-JAN-06:03 | 1.11 |
February | 0.292593E+10 | 0.30 | 8667.72 | 27-FEB-06:01 | 1.07 |
March | 0.337110E+10 | 0.31 | 18609.06 | 27-MAR-05:01 | 1.73 |
April | 0.388351E+10 | 0.33 | 14663.97 | 29-APR-04:11 | 1.49 |
May | 0.589754E+10 | 0.41 | 19063.98 | 05-MAY-05:01 | 1.76 |
June | 0.624653E+10 | 0.44 | 19063.98 | 02-JUN-05:01 | 1.76 |
July | 0.602484E+10 | 0.42 | 19063.98 | 01-JUL-05:01 | 1.76 |
August | 0.638668E+10 | 0.44 | 19063.98 | 01-AUG-05:01 | 1.76 |
September | 0.508566E+10 | 0.39 | 19063.98 | 02-SEP-05:01 | 1.76 |
October | 0.522653E+10 | 0.38 | 19063.98 | 06-OCT-03:01 | 1.76 |
November | 0.345792E+10 | 0.31 | 16949.90 | 01-NOV-05:02 | 1.63 |
December | 0.311746E+10 | 0.29 | 15447.88 | 11-DEC-06:01 | 1.54 |
Annual Sum or Average | 0.545689E+11 | 0.36 | |||
Minimum of Months | 0.292593E+10 | 0.29 | 8667.72 | 1.07 | |
Maximum of Months | 0.638668E+10 | 0.44 | 19063.98 | 1.76 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.944430E+11 | 1.35 | 35260.99 | 01-JAN-00:05 | 1.35 |
February | 0.853034E+11 | 1.35 | 35260.99 | 01-FEB-00:10 | 1.35 |
March | 0.944430E+11 | 1.35 | 35260.99 | 01-MAR-00:10 | 1.35 |
April | 0.913965E+11 | 1.35 | 35260.99 | 01-APR-00:10 | 1.35 |
May | 0.944430E+11 | 1.35 | 35260.99 | 01-MAY-00:03 | 1.35 |
June | 0.913965E+11 | 1.35 | 35260.99 | 01-JUN-00:10 | 1.35 |
July | 0.944430E+11 | 1.35 | 35260.99 | 01-JUL-00:03 | 1.35 |
August | 0.944430E+11 | 1.35 | 35260.99 | 01-AUG-00:05 | 1.35 |
September | 0.913965E+11 | 1.35 | 35260.99 | 01-SEP-00:12 | 1.35 |
October | 0.944430E+11 | 1.35 | 35260.99 | 01-OCT-00:30 | 1.35 |
November | 0.913965E+11 | 1.35 | 35260.99 | 01-NOV-00:10 | 1.35 |
December | 0.944430E+11 | 1.35 | 35260.99 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.111199E+13 | 1.35 | |||
Minimum of Months | 0.853034E+11 | 1.35 | 35260.99 | 1.35 | |
Maximum of Months | 0.944430E+11 | 1.35 | 35260.99 | 1.35 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138710E+10 | 0.91 | 517.88 | 01-JAN-00:05 | 0.91 |
February | 0.125287E+10 | 0.91 | 517.88 | 01-FEB-00:10 | 0.91 |
March | 0.138710E+10 | 0.91 | 517.88 | 01-MAR-00:10 | 0.91 |
April | 0.134236E+10 | 0.91 | 517.88 | 01-APR-00:10 | 0.91 |
May | 0.138710E+10 | 0.91 | 517.88 | 01-MAY-00:03 | 0.91 |
June | 0.134236E+10 | 0.91 | 517.88 | 01-JUN-00:10 | 0.91 |
July | 0.138710E+10 | 0.91 | 517.88 | 01-JUL-00:03 | 0.91 |
August | 0.138710E+10 | 0.91 | 517.88 | 01-AUG-00:05 | 0.91 |
September | 0.134236E+10 | 0.91 | 517.88 | 01-SEP-00:10 | 0.91 |
October | 0.138710E+10 | 0.91 | 517.88 | 01-OCT-00:10 | 0.91 |
November | 0.134236E+10 | 0.91 | 517.88 | 01-NOV-00:10 | 0.91 |
December | 0.138710E+10 | 0.91 | 517.88 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.163320E+11 | 0.91 | |||
Minimum of Months | 0.125287E+10 | 0.91 | 517.88 | 0.91 | |
Maximum of Months | 0.138710E+10 | 0.91 | 517.88 | 0.91 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131618E+11 | 0.91 | 4914.06 | 01-JAN-00:05 | 0.91 |
February | 0.118881E+11 | 0.91 | 4914.06 | 01-FEB-00:10 | 0.91 |
March | 0.131618E+11 | 0.91 | 4914.06 | 01-MAR-00:10 | 0.91 |
April | 0.127373E+11 | 0.91 | 4914.06 | 01-APR-00:10 | 0.91 |
May | 0.131618E+11 | 0.91 | 4914.06 | 01-MAY-00:03 | 0.91 |
June | 0.127373E+11 | 0.91 | 4914.06 | 01-JUN-00:10 | 0.91 |
July | 0.131618E+11 | 0.91 | 4914.06 | 01-JUL-00:03 | 0.91 |
August | 0.131618E+11 | 0.91 | 4914.06 | 01-AUG-00:05 | 0.91 |
September | 0.127373E+11 | 0.91 | 4914.06 | 01-SEP-00:10 | 0.91 |
October | 0.131618E+11 | 0.91 | 4914.06 | 01-OCT-00:10 | 0.91 |
November | 0.127373E+11 | 0.91 | 4914.06 | 01-NOV-00:10 | 0.91 |
December | 0.131618E+11 | 0.91 | 4914.06 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.154970E+12 | 0.91 | |||
Minimum of Months | 0.118881E+11 | 0.91 | 4914.06 | 0.91 | |
Maximum of Months | 0.131618E+11 | 0.91 | 4914.06 | 0.91 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133736E+10 | 0.91 | 499.31 | 01-JAN-00:05 | 0.91 |
February | 0.120794E+10 | 0.91 | 499.31 | 01-FEB-00:10 | 0.91 |
March | 0.133736E+10 | 0.91 | 499.31 | 01-MAR-00:10 | 0.91 |
April | 0.129422E+10 | 0.91 | 499.31 | 01-APR-00:10 | 0.91 |
May | 0.133736E+10 | 0.91 | 499.31 | 01-MAY-00:03 | 0.91 |
June | 0.129422E+10 | 0.91 | 499.31 | 01-JUN-00:10 | 0.91 |
July | 0.133736E+10 | 0.91 | 499.31 | 01-JUL-00:03 | 0.91 |
August | 0.133736E+10 | 0.91 | 499.31 | 01-AUG-00:05 | 0.91 |
September | 0.129422E+10 | 0.91 | 499.31 | 01-SEP-00:10 | 0.91 |
October | 0.133736E+10 | 0.91 | 499.31 | 01-OCT-00:10 | 0.91 |
November | 0.129422E+10 | 0.91 | 499.31 | 01-NOV-00:10 | 0.91 |
December | 0.133736E+10 | 0.91 | 499.31 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.157464E+11 | 0.91 | |||
Minimum of Months | 0.120794E+10 | 0.91 | 499.31 | 0.91 | |
Maximum of Months | 0.133736E+10 | 0.91 | 499.31 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.279425E+09 | 0.251482E+09 | 7555.07 | 05-JAN-06:01 | 6799.56 | 6799.56 | 60.39 | 12.61 |
February | 0.152660E+09 | 0.137394E+09 | 7524.06 | 06-FEB-06:01 | 6771.65 | 6771.65 | 64.64 | 12.51 |
March | 0.128111E+09 | 0.115300E+09 | 7408.12 | 13-MAR-05:02 | 6667.31 | 6667.31 | 54.29 | 12.28 |
April | 14144028.34 | 12729625.51 | 4337.82 | 02-APR-21:10 | 3904.03 | 3904.03 | 72.07 | 6.00 |
May | 16383479.22 | 14745131.30 | 4339.47 | 28-MAY-20:00 | 3905.52 | 3905.52 | 72.84 | 6.00 |
June | 13780667.12 | 12402600.41 | 4339.44 | 25-JUN-18:45 | 3905.50 | 3905.50 | 72.83 | 6.00 |
July | 21306726.82 | 19176054.14 | 4339.53 | 09-JUL-12:40 | 3905.58 | 3905.58 | 72.87 | 6.00 |
August | 14623958.79 | 13161562.91 | 4339.52 | 13-AUG-11:35 | 3905.56 | 3905.56 | 72.86 | 6.00 |
September | 22384815.39 | 20146333.85 | 4339.46 | 17-SEP-10:55 | 3905.52 | 3905.52 | 72.84 | 6.00 |
October | 26232146.71 | 23608932.04 | 4339.39 | 08-OCT-13:59 | 3905.45 | 3905.45 | 72.80 | 6.00 |
November | 45660772.19 | 41094694.97 | 4338.05 | 05-NOV-21:38 | 3904.25 | 3904.25 | 72.18 | 6.00 |
December | 0.217456E+09 | 0.195711E+09 | 7512.10 | 21-DEC-06:01 | 6760.89 | 6760.89 | 61.09 | 12.50 |
Annual Sum or Average | 0.952169E+09 | 0.856952E+09 | ||||||
Minimum of Months | 13780667.12 | 12402600.41 | 4337.82 | 3904.03 | 3904.03 | 54.29 | 6.00 | |
Maximum of Months | 0.279425E+09 | 0.251482E+09 | 7555.07 | 6799.56 | 6799.56 | 72.87 | 12.61 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.371793E+09 | 0.334614E+09 | 3365.64 | 19-JAN-10:40 | 3029.08 | 3029.08 | 7.31 | 56.80 |
February | 0.574870E+09 | 0.517383E+09 | 3640.67 | 27-FEB-06:02 | 3276.60 | 3276.60 | 6.71 | 58.78 |
March | 0.689014E+09 | 0.620113E+09 | 9241.73 | 27-MAR-05:02 | 8317.56 | 8317.56 | 7.39 | 87.14 |
April | 0.115164E+10 | 0.103647E+10 | 5406.65 | 29-APR-04:12 | 4865.99 | 4865.99 | 6.94 | 69.65 |
May | 0.227595E+10 | 0.204835E+10 | 25004.27 | 10-MAY-05:02 | 22503.85 | 22503.85 | 9.10 | 129.94 |
June | 0.235735E+10 | 0.212162E+10 | 24266.89 | 30-JUN-05:02 | 21840.20 | 21840.20 | 8.49 | 128.40 |
July | 0.242395E+10 | 0.218155E+10 | 15977.87 | 25-JUL-05:02 | 14380.08 | 14380.08 | 8.14 | 108.81 |
August | 0.264093E+10 | 0.237683E+10 | 24793.76 | 18-AUG-05:02 | 22314.38 | 22314.38 | 8.65 | 129.49 |
September | 0.230214E+10 | 0.207193E+10 | 25004.27 | 06-SEP-05:02 | 22503.85 | 22503.85 | 9.01 | 129.94 |
October | 0.192359E+10 | 0.173123E+10 | 25004.27 | 24-OCT-05:02 | 22503.85 | 22503.85 | 8.72 | 129.94 |
November | 0.896420E+09 | 0.806778E+09 | 5429.02 | 08-NOV-05:12 | 4886.12 | 4886.12 | 6.83 | 69.78 |
December | 0.630361E+09 | 0.567324E+09 | 6932.30 | 11-DEC-06:02 | 6239.07 | 6239.07 | 7.01 | 77.34 |
Annual Sum or Average | 0.182380E+11 | 0.164142E+11 | ||||||
Minimum of Months | 0.371793E+09 | 0.334614E+09 | 3365.64 | 3029.08 | 3029.08 | 6.71 | 56.80 | |
Maximum of Months | 0.264093E+10 | 0.237683E+10 | 25004.27 | 22503.85 | 22503.85 | 9.10 | 129.94 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871592.27 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 75.46 | 0.44 |
February | 0.101979E+09 | 30593696.24 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 67.65 | 0.44 |
March | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 68.15 | 0.44 |
April | 0.109263E+09 | 32778960.26 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 68.32 | 0.44 |
May | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 78.87 | 0.44 |
June | 0.109263E+09 | 32778960.26 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 69.73 | 0.44 |
July | 0.112905E+09 | 33871592.27 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 66.12 | 0.44 |
August | 0.112905E+09 | 33871592.27 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 65.77 | 0.44 |
September | 0.109263E+09 | 32778960.26 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 69.93 | 0.44 |
October | 0.112905E+09 | 33871592.27 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 75.64 | 0.44 |
November | 0.109263E+09 | 32778960.26 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 67.48 | 0.44 |
December | 0.112905E+09 | 33871592.27 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 66.73 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398811E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593696.24 | 56.21 | 16.86 | 16.86 | 65.77 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871592.27 | 56.21 | 16.86 | 16.86 | 78.87 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.424464E+10 | 0.382018E+10 | 4142.94 | 01-JAN-00:11 | 3728.64 | 3728.64 | 7.30 | 64.97 |
February | 0.493279E+10 | 0.443951E+10 | 4142.94 | 01-FEB-04:01 | 3728.64 | 3728.64 | 9.42 | 64.97 |
March | 0.609554E+10 | 0.548599E+10 | 4142.94 | 01-MAR-04:01 | 3728.64 | 3728.64 | 9.10 | 64.97 |
April | 0.768682E+10 | 0.691814E+10 | 4142.94 | 01-APR-03:01 | 3728.64 | 3728.64 | 9.15 | 64.97 |
May | 0.813950E+10 | 0.732555E+10 | 4142.94 | 01-MAY-00:03 | 3728.64 | 3728.64 | 6.87 | 64.97 |
June | 0.863218E+10 | 0.776896E+10 | 4142.94 | 01-JUN-03:01 | 3728.64 | 3728.64 | 10.17 | 64.97 |
July | 0.950124E+10 | 0.855112E+10 | 4142.94 | 01-JUL-00:42 | 3728.64 | 3728.64 | 6.90 | 64.97 |
August | 0.978048E+10 | 0.880243E+10 | 4142.94 | 01-AUG-00:23 | 3728.64 | 3728.64 | 6.90 | 64.97 |
September | 0.795223E+10 | 0.715701E+10 | 4142.94 | 01-SEP-00:10 | 3728.64 | 3728.64 | 6.89 | 64.97 |
October | 0.805065E+10 | 0.724558E+10 | 4142.94 | 01-OCT-07:32 | 3728.64 | 3728.64 | 8.77 | 64.97 |
November | 0.669312E+10 | 0.602381E+10 | 4142.94 | 01-NOV-03:01 | 3728.64 | 3728.64 | 9.41 | 64.97 |
December | 0.542642E+10 | 0.488378E+10 | 4142.94 | 01-DEC-04:01 | 3728.64 | 3728.64 | 7.10 | 64.97 |
Annual Sum or Average | 0.871356E+11 | 0.784220E+11 | ||||||
Minimum of Months | 0.424464E+10 | 0.382018E+10 | 4142.94 | 3728.64 | 3728.64 | 6.87 | 64.97 | |
Maximum of Months | 0.978048E+10 | 0.880243E+10 | 4142.94 | 3728.64 | 3728.64 | 10.17 | 64.97 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 87001652.20 | 78301486.98 | 4142.94 | 18-JAN-14:50 | 3728.64 | 3728.64 | 12.42 | 32.48 |
February | 0.159089E+09 | 0.143180E+09 | 4142.94 | 02-FEB-17:00 | 3728.64 | 3728.64 | 12.35 | 32.48 |
March | 0.313206E+09 | 0.281885E+09 | 4142.94 | 06-MAR-15:20 | 3728.64 | 3728.64 | 12.30 | 32.48 |
April | 0.566754E+09 | 0.510078E+09 | 4142.94 | 06-APR-12:50 | 3728.64 | 3728.64 | 12.23 | 32.48 |
May | 0.230194E+10 | 0.207175E+10 | 4142.94 | 01-MAY-08:00 | 3728.64 | 3728.64 | 12.21 | 32.48 |
June | 0.252379E+10 | 0.227141E+10 | 4142.94 | 01-JUN-08:20 | 3728.64 | 3728.64 | 12.28 | 32.48 |
July | 0.272787E+10 | 0.245509E+10 | 4142.94 | 01-JUL-05:03 | 3728.64 | 3728.64 | 12.74 | 32.48 |
August | 0.301175E+10 | 0.271057E+10 | 4142.94 | 01-AUG-06:20 | 3728.64 | 3728.64 | 12.18 | 32.48 |
September | 0.239130E+10 | 0.215217E+10 | 4142.94 | 01-SEP-06:20 | 3728.64 | 3728.64 | 12.19 | 32.48 |
October | 0.187501E+10 | 0.168751E+10 | 4142.94 | 02-OCT-14:10 | 3728.64 | 3728.64 | 12.38 | 32.48 |
November | 0.646049E+09 | 0.581444E+09 | 4142.94 | 01-NOV-07:20 | 3728.64 | 3728.64 | 12.13 | 32.48 |
December | 0.410151E+09 | 0.369136E+09 | 4142.94 | 11-DEC-09:50 | 3728.64 | 3728.64 | 12.25 | 32.48 |
Annual Sum or Average | 0.170139E+11 | 0.153125E+11 | ||||||
Minimum of Months | 87001652.20 | 78301486.98 | 4142.94 | 3728.64 | 3728.64 | 12.13 | 32.48 | |
Maximum of Months | 0.301175E+10 | 0.271057E+10 | 4142.94 | 3728.64 | 3728.64 | 12.74 | 32.48 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.900195E+10 | 0.810176E+10 | 3360.94 | 01-JAN-00:05 | 3024.85 | 3024.85 | 22.17 | 14.04 |
February | 0.813080E+10 | 0.731772E+10 | 3360.94 | 01-FEB-00:10 | 3024.85 | 3024.85 | 26.51 | 14.04 |
March | 0.900195E+10 | 0.810176E+10 | 3360.94 | 01-MAR-00:10 | 3024.85 | 3024.85 | 29.86 | 14.04 |
April | 0.871157E+10 | 0.784041E+10 | 3360.94 | 01-APR-00:10 | 3024.85 | 3024.85 | 37.16 | 14.04 |
May | 0.900195E+10 | 0.810176E+10 | 3360.94 | 01-MAY-00:03 | 3024.85 | 3024.85 | 34.09 | 14.04 |
June | 0.871157E+10 | 0.784041E+10 | 3360.94 | 01-JUN-00:10 | 3024.85 | 3024.85 | 31.27 | 14.04 |
July | 0.900195E+10 | 0.810176E+10 | 3360.94 | 01-JUL-00:03 | 3024.85 | 3024.85 | 36.80 | 14.04 |
August | 0.900195E+10 | 0.810176E+10 | 3360.94 | 01-AUG-00:05 | 3024.85 | 3024.85 | 41.57 | 14.04 |
September | 0.871157E+10 | 0.784041E+10 | 3360.94 | 01-SEP-00:10 | 3024.85 | 3024.85 | 32.93 | 14.04 |
October | 0.900195E+10 | 0.810176E+10 | 3360.94 | 01-OCT-00:10 | 3024.85 | 3024.85 | 30.51 | 14.04 |
November | 0.871157E+10 | 0.784041E+10 | 3360.94 | 01-NOV-00:10 | 3024.85 | 3024.85 | 33.88 | 14.04 |
December | 0.900195E+10 | 0.810176E+10 | 3360.94 | 01-DEC-00:10 | 3024.85 | 3024.85 | 30.01 | 14.04 |
Annual Sum or Average | 0.105991E+12 | 0.953917E+11 | ||||||
Minimum of Months | 0.813080E+10 | 0.731772E+10 | 3360.94 | 3024.85 | 3024.85 | 22.17 | 14.04 | |
Maximum of Months | 0.900195E+10 | 0.810176E+10 | 3360.94 | 3024.85 | 3024.85 | 41.57 | 14.04 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.167892E+11 | 0.151102E+11 | 32408.84 | 19-JAN-10:40 | 29167.96 | 29167.96 | 27.74 | 152.88 |
February | 0.194586E+11 | 0.175127E+11 | 32408.68 | 24-FEB-11:30 | 29167.82 | 29167.82 | 27.73 | 152.88 |
March | 0.246062E+11 | 0.221456E+11 | 32437.05 | 30-MAR-12:30 | 29193.34 | 29193.34 | 28.77 | 152.88 |
April | 0.311534E+11 | 0.280380E+11 | 32438.00 | 24-APR-10:00 | 29194.20 | 29194.20 | 28.95 | 152.88 |
May | 0.382025E+11 | 0.343823E+11 | 32438.00 | 01-MAY-08:20 | 29194.20 | 29194.20 | 28.90 | 152.88 |
June | 0.417170E+11 | 0.375453E+11 | 32438.00 | 01-JUN-08:50 | 29194.20 | 29194.20 | 29.16 | 152.88 |
July | 0.466328E+11 | 0.419696E+11 | 32438.00 | 03-JUL-08:70 | 29194.20 | 29194.20 | 30.41 | 152.88 |
August | 0.485638E+11 | 0.437074E+11 | 32438.00 | 01-AUG-08:20 | 29194.20 | 29194.20 | 30.41 | 152.88 |
September | 0.388379E+11 | 0.349541E+11 | 32438.00 | 01-SEP-06:40 | 29194.20 | 29194.20 | 29.16 | 152.88 |
October | 0.376640E+11 | 0.338976E+11 | 32438.00 | 04-OCT-07:15 | 29194.20 | 29194.20 | 29.31 | 152.88 |
November | 0.279956E+11 | 0.251960E+11 | 32438.00 | 01-NOV-07:40 | 29194.20 | 29194.20 | 28.83 | 152.88 |
December | 0.222022E+11 | 0.199820E+11 | 32438.00 | 11-DEC-13:50 | 29194.20 | 29194.20 | 28.94 | 152.88 |
Annual Sum or Average | 0.393823E+12 | 0.354441E+12 | ||||||
Minimum of Months | 0.167892E+11 | 0.151102E+11 | 32408.68 | 29167.82 | 29167.82 | 27.73 | 152.88 | |
Maximum of Months | 0.485638E+11 | 0.437074E+11 | 32438.00 | 29194.20 | 29194.20 | 30.41 | 152.88 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7565.14 | 38177.88 | 01-JAN-07:50 | 80.66 | 82.22 | 10271.27 | 42420.95 | 23-JAN-12:20 |
February | 7245.91 | 38213.85 | 26-FEB-07:50 | 80.68 | 82.22 | 10221.54 | 42349.11 | 01-FEB-12:20 |
March | 6096.37 | 38339.74 | 26-MAR-06:50 | 80.75 | 82.22 | 10531.02 | 41390.56 | 01-MAR-12:40 |
April | 7389.21 | 38547.41 | 30-APR-06:35 | 80.86 | 82.22 | 8938.20 | 39156.80 | 03-APR-11:30 |
May | 7374.83 | 38712.80 | 29-MAY-06:36 | 80.95 | 82.22 | 8564.00 | 36761.71 | 01-MAY-11:20 |
June | 6942.06 | 38823.06 | 25-JUN-06:35 | 81.01 | 82.22 | 8144.72 | 34286.14 | 01-JUN-11:20 |
July | 8775.71 | 38867.19 | 23-JUL-06:35 | 81.03 | 82.22 | 6924.07 | 32626.32 | 03-JUL-11:50 |
August | 6937.02 | 38858.67 | 06-AUG-06:37 | 81.03 | 82.22 | 7997.52 | 33274.29 | 31-AUG-12:00 |
September | 7785.40 | 38782.93 | 03-SEP-06:35 | 80.99 | 82.22 | 7791.12 | 35299.25 | 29-SEP-11:30 |
October | 8097.76 | 38645.10 | 01-OCT-06:40 | 80.91 | 82.22 | 8535.70 | 38016.58 | 31-OCT-11:20 |
November | 7956.29 | 38434.12 | 05-NOV-06:50 | 80.80 | 82.22 | 9497.83 | 40409.79 | 30-NOV-12:30 |
December | 7736.09 | 38281.19 | 03-DEC-07:50 | 80.71 | 82.22 | 9615.66 | 42941.31 | 29-DEC-13:30 |
Annual Sum or Average | 7493.55 | 8912.26 | ||||||
Minimum of Months | 6096.37 | 38177.88 | 80.66 | 82.22 | 6924.07 | 32626.32 | ||
Maximum of Months | 8775.71 | 38867.19 | 81.03 | 82.22 | 10531.02 | 42941.31 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 72.91 | 72.91 | 14362.40 | 1563974.32 | 09-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.30 | 56.30 | 8392.59 | 1344478.96 | 18-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 72.30 | 72.30 | 6671.38 | 1447843.81 | 11-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 71.23 | 71.23 | 372.84 | 415528.47 | 16-APR-21:10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 72.06 | 72.06 | 329.73 | 248039.09 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 72.74 | 72.74 | 283.46 | 232569.33 | 04-JUN-14:56 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 72.77 | 72.77 | 422.76 | 231776.65 | 09-JUL-20:47 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 72.83 | 72.83 | 291.02 | 232702.29 | 27-AUG-21:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 72.74 | 72.74 | 461.56 | 233460.84 | 24-SEP-22:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 72.71 | 72.71 | 594.62 | 490037.04 | 29-OCT-13:58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 70.76 | 70.76 | 1623.89 | 797899.72 | 19-NOV-10:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 64.93 | 64.93 | 10474.27 | 1651973.81 | 20-DEC-05:11 |
Annual Sum or Average | 0.00 | 3684.32 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.30 | 56.30 | 283.46 | 231776.65 | ||
Maximum of Months | 0.00 | 0.00 | 72.91 | 72.91 | 14362.40 | 1651973.81 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 183487.74 | 1830957.91 | 19-JAN-10:40 | 13.43 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 286051.52 | 1844440.86 | 24-FEB-11:30 | 13.48 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 312707.62 | 1811946.48 | 29-MAR-10:40 | 13.36 | 8.22 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 508503.65 | 2014684.78 | 28-APR-07:20 | 10.40 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 778250.78 | 3496498.90 | 23-MAY-05:03 | 13.13 | 7.43 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 819275.23 | 2595468.45 | 24-JUN-05:04 | 11.47 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 821023.52 | 2430930.51 | 01-JUL-05:04 | 11.17 | 6.70 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 860611.71 | 2612782.17 | 15-AUG-05:04 | 11.50 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 802901.17 | 2736798.68 | 06-SEP-05:04 | 11.73 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 661520.79 | 2250781.31 | 24-OCT-05:05 | 10.83 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 393619.09 | 1847563.14 | 29-NOV-06:06 | 10.09 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 273220.00 | 2021136.54 | 11-DEC-14:50 | 10.41 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 559873.71 | 0.00 | ||||||
Minimum of Months | 183487.74 | 1811946.48 | 10.09 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 860611.71 | 3496498.90 | 13.48 | 8.22 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 181952.87 | 1895836.63 | 19-JAN-10:40 | 14.68 | 7.08 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 284033.93 | 1909011.23 | 24-FEB-11:30 | 14.69 | 7.09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 310221.93 | 2692892.92 | 27-MAR-05:02 | 14.08 | 8.57 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 504843.98 | 2405963.77 | 29-APR-04:11 | 15.33 | 6.90 | 0.00 | 0.00 | 01-APR-00:10 |
May | 773287.77 | 4564125.94 | 22-MAY-03:02 | 15.28 | 10.88 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 813971.22 | 4075239.49 | 30-JUN-05:02 | 14.28 | 10.44 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 815386.83 | 3465324.18 | 25-JUL-05:02 | 14.31 | 9.75 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 855360.55 | 4155865.94 | 18-AUG-05:02 | 14.37 | 10.51 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 798793.80 | 4232203.52 | 06-SEP-05:02 | 14.48 | 10.58 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 657587.92 | 4162282.87 | 24-OCT-05:02 | 14.35 | 10.52 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 390584.78 | 2314646.78 | 08-NOV-05:12 | 14.63 | 7.23 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 270782.03 | 2509682.63 | 11-DEC-06:02 | 14.45 | 7.92 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 556166.41 | 0.00 | ||||||
Minimum of Months | 181952.87 | 1895836.63 | 14.08 | 6.90 | 0.00 | 0.00 | ||
Maximum of Months | 855360.55 | 4564125.94 | 15.33 | 10.88 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 225872.78 | 703776.68 | 02-JAN-15:00 | 32.61 | 28.67 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 419434.94 | 980078.83 | 02-FEB-13:10 | 38.12 | 31.17 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 646642.40 | 1281492.32 | 26-MAR-14:00 | 44.06 | 34.24 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1015991.12 | 1697082.77 | 28-APR-15:00 | 52.14 | 39.03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 698105.66 | 1058429.00 | 28-MAY-16:00 | 39.67 | 35.63 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 945177.06 | 1355988.35 | 14-JUN-14:00 | 45.51 | 38.17 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1181381.04 | 1659350.66 | 21-JUL-16:00 | 51.41 | 40.75 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1372919.37 | 1846589.28 | 30-AUG-16:10 | 55.02 | 41.85 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 666025.79 | 1213064.99 | 09-SEP-17:00 | 42.71 | 38.30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 771002.79 | 1308682.65 | 05-OCT-15:00 | 44.59 | 37.19 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 709670.54 | 1309466.13 | 02-NOV-13:00 | 44.60 | 34.40 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 789159.55 | 1514615.69 | 13-DEC-15:00 | 48.60 | 35.64 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 789281.38 | 0.00 | ||||||
Minimum of Months | 225872.78 | 703776.68 | 32.61 | 28.67 | 0.00 | 0.00 | ||
Maximum of Months | 1372919.37 | 1846589.28 | 55.02 | 41.85 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 296400.18 | 4240777.65 | 19-JAN-10:40 | 27.74 | 24.59 | 1168.73 | 152878.09 | 04-JAN-21:20 |
February | 446567.60 | 4237033.72 | 24-FEB-11:30 | 27.73 | 24.54 | 836.16 | 125903.66 | 04-FEB-07:00 |
March | 536781.06 | 4902696.09 | 30-MAR-12:30 | 28.77 | 25.69 | 1355.86 | 165801.56 | 09-MAR-07:20 |
April | 923012.54 | 6525035.18 | 28-APR-16:00 | 31.31 | 28.20 | 350.03 | 101147.48 | 03-APR-06:10 |
May | 2030864.46 | 6710097.50 | 26-MAY-11:00 | 31.60 | 28.46 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 2386324.89 | 7146512.82 | 28-JUN-14:00 | 32.28 | 29.07 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2790822.20 | 7456839.03 | 03-JUL-16:00 | 32.77 | 29.40 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 2741375.12 | 7383134.53 | 07-AUG-13:00 | 32.65 | 29.35 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2282470.22 | 7257384.14 | 18-SEP-14:00 | 32.46 | 29.24 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 1748019.55 | 7642382.03 | 06-OCT-14:10 | 33.06 | 29.53 | 75.57 | 50101.02 | 27-OCT-19:40 |
November | 788210.81 | 6172350.21 | 01-NOV-13:40 | 30.76 | 27.66 | 421.34 | 121404.78 | 22-NOV-08:40 |
December | 506184.27 | 5707150.84 | 12-DEC-14:20 | 30.03 | 26.92 | 1303.96 | 155175.64 | 18-DEC-09:10 |
Annual Sum or Average | 1463200.82 | 459.13 | ||||||
Minimum of Months | 296400.18 | 4237033.72 | 27.73 | 24.54 | 0.00 | 0.00 | ||
Maximum of Months | 2790822.20 | 7642382.03 | 33.06 | 29.53 | 1355.86 | 165801.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.60 | 4.17 |
February | 0.82 | 4.69 |
March | 1.51 | 3.09 |
April | 2.12 | 2.79 |
May | 1.35 | 4.24 |
June | 0.77 | 5.06 |
July | 0.77 | 7.48 |
August | 0.61 | 6.80 |
September | 1.38 | 7.71 |
October | 1.25 | 7.23 |
November | 1.47 | 7.06 |
December | 1.08 | 6.62 |
Annual Sum or Average | 13.74 | 5.36 |
Minimum of Months | 0.60 | 2.79 |
Maximum of Months | 2.12 | 7.71 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.95 | 3.47 |
February | 3.83 | 2.82 |
March | 8.07 | 2.50 |
April | 16.37 | 2.09 |
May | 8.39 | 2.22 |
June | 15.89 | 1.88 |
July | 16.43 | 1.81 |
August | 12.47 | 1.43 |
September | 9.13 | 1.83 |
October | 12.32 | 1.77 |
November | 7.16 | 2.20 |
December | 9.62 | 1.86 |
Annual Sum or Average | 123.65 | 2.00 |
Minimum of Months | 3.83 | 1.43 |
Maximum of Months | 16.43 | 3.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.14 | 7.20 |
February | 1.29 | 9.03 |
March | 1.99 | 6.86 |
April | 2.18 | 4.53 |
May | 4.91 | 4.76 |
June | 5.46 | 2.83 |
July | 7.46 | 2.29 |
August | 6.46 | 3.45 |
September | 5.52 | 4.70 |
October | 3.74 | 5.31 |
November | 1.83 | 6.72 |
December | 1.98 | 18.89 |
Annual Sum or Average | 44.96 | 4.99 |
Minimum of Months | 1.29 | 2.29 |
Maximum of Months | 7.46 | 18.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.86 | 11.05 |
February | 0.90 | 11.26 |
March | 1.44 | 12.27 |
April | 2.35 | 6.72 |
May | 5.27 | 4.38 |
June | 6.97 | 3.30 |
July | 9.72 | 2.17 |
August | 7.03 | 2.89 |
September | 5.21 | 3.47 |
October | 4.19 | 5.75 |
November | 2.58 | 9.57 |
December | 1.18 | 10.51 |
Annual Sum or Average | 47.70 | 4.61 |
Minimum of Months | 0.86 | 2.17 |
Maximum of Months | 9.72 | 12.27 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.83 | 2.19 |
February | 0.71 | 0.65 |
March | 2.33 | 0.35 |
April | 7.07 | 0.31 |
May | 4.85 | 0.32 |
June | 10.90 | 0.25 |
July | 14.10 | 0.22 |
August | 10.41 | 0.18 |
September | 5.06 | 0.16 |
October | 7.07 | 0.24 |
November | 2.97 | 0.35 |
December | 2.86 | 0.29 |
Annual Sum or Average | 69.17 | 0.27 |
Minimum of Months | 0.71 | 0.16 |
Maximum of Months | 14.10 | 2.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.82 | 2.58 |
February | 2.36 | 1.18 |
March | 3.82 | 0.48 |
April | 9.27 | 0.21 |
May | 8.05 | 0.15 |
June | 14.16 | 0.17 |
July | 18.13 | 0.18 |
August | 12.52 | 0.16 |
September | 8.73 | 0.11 |
October | 9.51 | 0.22 |
November | 4.61 | 0.24 |
December | 4.50 | 0.25 |
Annual Sum or Average | 98.48 | 0.28 |
Minimum of Months | 2.36 | 0.11 |
Maximum of Months | 18.13 | 2.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.79 | 8.86 |
February | 0.64 | 0.50 |
March | 2.24 | 0.33 |
April | 7.31 | 0.31 |
May | 4.60 | 0.28 |
June | 10.99 | 0.24 |
July | 14.44 | 0.22 |
August | 10.59 | 0.18 |
September | 5.11 | 0.14 |
October | 6.86 | 0.23 |
November | 2.66 | 0.29 |
December | 3.12 | 0.29 |
Annual Sum or Average | 69.36 | 0.34 |
Minimum of Months | 0.64 | 0.14 |
Maximum of Months | 14.44 | 8.86 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.26 | 0.79 |
February | 3.38 | 0.37 |
March | 6.70 | 0.22 |
April | 17.59 | 0.21 |
May | 7.41 | 0.20 |
June | 17.46 | 0.16 |
July | 23.21 | 0.16 |
August | 18.15 | 0.16 |
September | 9.48 | 0.17 |
October | 11.83 | 0.16 |
November | 7.65 | 0.21 |
December | 11.26 | 0.57 |
Annual Sum or Average | 138.40 | 0.23 |
Minimum of Months | 3.38 | 0.16 |
Maximum of Months | 23.21 | 0.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.43 | 1.17 |
February | 0.54 | 1.36 |
March | 0.57 | 1.34 |
April | 1.47 | 0.85 |
May | 3.28 | 0.57 |
June | 3.08 | 0.40 |
July | 5.35 | 0.34 |
August | 3.58 | 0.38 |
September | 4.30 | 0.40 |
October | 1.56 | 0.47 |
November | 0.50 | 1.31 |
December | 0.22 | 1.27 |
Annual Sum or Average | 24.88 | 0.52 |
Minimum of Months | 0.22 | 0.34 |
Maximum of Months | 5.35 | 1.36 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.29 | 1.27 |
February | 1.29 | 0.68 |
March | 2.31 | 0.64 |
April | 3.65 | 0.55 |
May | 5.86 | 0.35 |
June | 6.43 | 0.20 |
July | 7.94 | 0.13 |
August | 6.41 | 0.20 |
September | 6.31 | 0.29 |
October | 4.23 | 0.42 |
November | 2.77 | 0.63 |
December | 1.45 | 1.22 |
Annual Sum or Average | 49.94 | 0.38 |
Minimum of Months | 1.29 | 0.13 |
Maximum of Months | 7.94 | 1.27 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.36 | 4.74 |
February | 0.51 | 1.32 |
March | 0.93 | 1.20 |
April | 1.33 | 0.82 |
May | 3.57 | 0.60 |
June | 3.09 | 0.37 |
July | 5.22 | 0.27 |
August | 2.86 | 0.32 |
September | 3.57 | 0.50 |
October | 1.03 | 0.43 |
November | 0.72 | 1.15 |
December | 0.39 | 4.46 |
Annual Sum or Average | 23.60 | 0.64 |
Minimum of Months | 0.36 | 0.27 |
Maximum of Months | 5.22 | 4.74 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.00 | 1.49 |
February | 0.99 | 0.72 |
March | 1.83 | 0.66 |
April | 2.66 | 0.56 |
May | 4.93 | 0.47 |
June | 5.52 | 0.26 |
July | 7.88 | 0.23 |
August | 5.49 | 0.30 |
September | 5.98 | 0.47 |
October | 2.75 | 0.56 |
November | 2.19 | 0.66 |
December | 1.01 | 0.77 |
Annual Sum or Average | 42.23 | 0.44 |
Minimum of Months | 0.99 | 0.23 |
Maximum of Months | 7.88 | 1.49 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.47 | 1.49 |
February | 0.63 | 1.18 |
March | 0.64 | 1.58 |
April | 1.56 | 1.14 |
May | 2.86 | 0.47 |
June | 4.18 | 0.48 |
July | 5.39 | 0.28 |
August | 3.91 | 0.35 |
September | 4.38 | 0.53 |
October | 1.75 | 0.54 |
November | 0.79 | 1.52 |
December | 0.61 | 1.42 |
Annual Sum or Average | 27.17 | 0.58 |
Minimum of Months | 0.47 | 0.28 |
Maximum of Months | 5.39 | 1.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.82 | 0.73 |
February | 0.91 | 0.75 |
March | 1.60 | 0.70 |
April | 2.84 | 0.61 |
May | 5.56 | 0.39 |
June | 6.64 | 0.25 |
July | 7.70 | 0.13 |
August | 5.72 | 0.19 |
September | 5.94 | 0.32 |
October | 3.50 | 0.39 |
November | 2.05 | 0.68 |
December | 0.98 | 0.71 |
Annual Sum or Average | 44.26 | 0.35 |
Minimum of Months | 0.82 | 0.13 |
Maximum of Months | 7.70 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.32 | 1.58 |
February | 0.59 | 1.24 |
March | 0.93 | 1.26 |
April | 1.47 | 1.08 |
May | 2.57 | 0.37 |
June | 4.18 | 0.47 |
July | 5.10 | 0.18 |
August | 2.96 | 0.27 |
September | 3.41 | 0.48 |
October | 1.46 | 0.76 |
November | 0.60 | 1.28 |
December | 0.40 | 1.43 |
Annual Sum or Average | 23.99 | 0.53 |
Minimum of Months | 0.32 | 0.18 |
Maximum of Months | 5.10 | 1.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.88 | 0.75 |
February | 0.71 | 0.81 |
March | 1.22 | 0.77 |
April | 3.07 | 0.59 |
May | 5.99 | 0.56 |
June | 6.96 | 0.33 |
July | 9.22 | 0.23 |
August | 6.72 | 0.35 |
September | 7.01 | 0.48 |
October | 4.00 | 0.64 |
November | 1.60 | 0.73 |
December | 0.88 | 0.73 |
Annual Sum or Average | 48.26 | 0.45 |
Minimum of Months | 0.71 | 0.23 |
Maximum of Months | 9.22 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.605173E+09 | 0.00 | 0.234629E+11 | 0.162290E+11 | 0.00 | 0.00 |
February | 0.773563E+09 | 0.00 | 0.284499E+11 | 0.143126E+11 | 0.00 | 0.00 |
March | 0.556525E+09 | 0.00 | 0.395541E+11 | 0.164039E+11 | 0.00 | 0.00 |
April | 0.646316E+09 | 0.00 | 0.614734E+11 | 0.152456E+11 | 0.00 | 0.00 |
May | 0.889694E+09 | 0.00 | 0.112542E+12 | 0.169214E+11 | 0.00 | 0.00 |
June | 0.747866E+09 | 0.00 | 0.117088E+12 | 0.164078E+11 | 0.00 | 0.00 |
July | 0.115253E+10 | 0.00 | 0.125999E+12 | 0.167606E+11 | 0.00 | 0.00 |
August | 0.795159E+09 | 0.00 | 0.137052E+12 | 0.178224E+11 | 0.00 | 0.00 |
September | 0.121903E+10 | 0.00 | 0.119202E+12 | 0.169083E+11 | 0.00 | 0.00 |
October | 0.136297E+10 | 0.00 | 0.103346E+12 | 0.175086E+11 | 0.00 | 0.00 |
November | 0.172334E+10 | 0.00 | 0.577016E+11 | 0.168409E+11 | 0.00 | 0.00 |
December | 0.178776E+10 | 0.00 | 0.384024E+11 | 0.168575E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.122599E+11 | 0.00 | 0.964274E+12 | 0.198219E+12 | 0.00 | 0.00 |
Minimum of Months | 0.556525E+09 | 0.00 | 0.234629E+11 | 0.143126E+11 | 0.00 | 0.00 |
Maximum of Months | 0.178776E+10 | 0.00 | 0.137052E+12 | 0.178224E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.478999E+09 | 0.00 | 0.450995E+11 | 0.407037E+10 | 0.00 | 0.00 |
February | 0.188819E+09 | 0.00 | 0.634073E+11 | 0.413941E+10 | 0.00 | 0.00 |
March | 0.154232E+09 | 0.00 | 0.787557E+11 | 0.513503E+10 | 0.00 | 0.00 |
April | 8938309.03 | 0.00 | 0.125623E+12 | 0.598217E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.164748E+12 | 0.613684E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.176548E+12 | 0.676698E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191522E+12 | 0.718932E+10 | 0.00 | 0.00 |
August | 50364.64 | 0.00 | 0.207654E+12 | 0.829194E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.167214E+12 | 0.581197E+10 | 0.00 | 0.00 |
October | 1934895.78 | 0.00 | 0.152029E+12 | 0.660985E+10 | 0.00 | 0.00 |
November | 7786735.95 | 0.00 | 0.956431E+11 | 0.565623E+10 | 0.00 | 0.00 |
December | 0.222899E+09 | 0.00 | 0.706727E+11 | 0.527697E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.106366E+10 | 0.00 | 0.153892E+13 | 0.710671E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.450995E+11 | 0.407037E+10 | 0.00 | 0.00 |
Maximum of Months | 0.478999E+09 | 0.00 | 0.207654E+12 | 0.829194E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.301294E+11 | 0.00 | 0.356664E+12 | 0.307216E+11 | 0.00 | 0.00 |
February | 0.145938E+11 | 0.00 | 0.503432E+12 | 0.292255E+11 | 0.00 | 0.00 |
March | 0.136925E+11 | 0.00 | 0.600063E+12 | 0.342934E+11 | 0.00 | 0.00 |
April | 0.171811E+09 | 0.00 | 0.938140E+12 | 0.376983E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.148979E+13 | 0.527052E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.152111E+13 | 0.544898E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.158918E+13 | 0.531142E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.164942E+13 | 0.569166E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.149734E+13 | 0.476834E+11 | 0.00 | 0.00 |
October | 0.150854E+09 | 0.00 | 0.127741E+13 | 0.500215E+11 | 0.00 | 0.00 |
November | 0.173301E+10 | 0.00 | 0.737943E+12 | 0.369961E+11 | 0.00 | 0.00 |
December | 0.207799E+11 | 0.00 | 0.522920E+12 | 0.328313E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.812513E+11 | 0.00 | 0.126834E+14 | 0.516697E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.356664E+12 | 0.292255E+11 | 0.00 | 0.00 |
Maximum of Months | 0.301294E+11 | 0.00 | 0.164942E+13 | 0.569166E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.790998E+10 | 0.00 | 0.361328E+11 | 0.294521E+10 | 0.00 | 0.00 |
February | 0.474226E+10 | 0.00 | 0.515349E+11 | 0.292593E+10 | 0.00 | 0.00 |
March | 0.367484E+10 | 0.00 | 0.625148E+11 | 0.337110E+10 | 0.00 | 0.00 |
April | 0.142429E+09 | 0.00 | 0.989662E+11 | 0.388351E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.162768E+12 | 0.589754E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.168205E+12 | 0.624653E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.175074E+12 | 0.602484E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.179868E+12 | 0.638668E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.159507E+12 | 0.508566E+10 | 0.00 | 0.00 |
October | 0.131527E+09 | 0.00 | 0.135147E+12 | 0.522653E+10 | 0.00 | 0.00 |
November | 0.883507E+09 | 0.00 | 0.733722E+11 | 0.345792E+10 | 0.00 | 0.00 |
December | 0.554288E+10 | 0.00 | 0.517422E+11 | 0.311746E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.230274E+11 | 0.00 | 0.135483E+13 | 0.545689E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.361328E+11 | 0.292593E+10 | 0.00 | 0.00 |
Maximum of Months | 0.790998E+10 | 0.00 | 0.179868E+12 | 0.638668E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.388302E+12 | 0.178290E+12 | 0.00 | 0.54 |
February | 0.00 | 0.00 | 0.616500E+12 | 0.213361E+12 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.983474E+12 | 0.299324E+12 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.127081E+13 | 0.370334E+12 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.428026E+12 | 0.205009E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.718910E+12 | 0.275398E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.106507E+13 | 0.364911E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.137903E+13 | 0.436327E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.417601E+12 | 0.197524E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.726854E+12 | 0.268835E+12 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.965162E+12 | 0.296487E+12 | 0.00 | 0.16 |
December | 0.00 | 0.00 | 0.128150E+13 | 0.352144E+12 | 0.00 | 0.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.102412E+14 | 0.345795E+13 | 0.00 | 1.88 |
Minimum of Months | 0.00 | 0.00 | 0.388302E+12 | 0.178290E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.137903E+13 | 0.436327E+12 | 0.00 | 0.54 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.595512E+10 | 0.264406E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.111135E+11 | 0.352670E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.186581E+11 | 0.521013E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.247747E+11 | 0.675280E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.730849E+10 | 0.329489E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132732E+11 | 0.476203E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202642E+11 | 0.656352E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.268763E+11 | 0.811135E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.705578E+10 | 0.315667E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.134384E+11 | 0.460815E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.183909E+11 | 0.521032E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.247334E+11 | 0.628006E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.191842E+12 | 0.601207E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.595512E+10 | 0.264406E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.268763E+11 | 0.811135E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.423736E+11 | 0.223542E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.940564E+11 | 0.313986E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.167515E+12 | 0.477955E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.232510E+12 | 0.636675E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.665806E+11 | 0.306182E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125228E+12 | 0.450375E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.192702E+12 | 0.623955E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.255895E+12 | 0.771817E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.632184E+11 | 0.290862E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.124033E+12 | 0.430406E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.166400E+12 | 0.480249E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.223080E+12 | 0.577161E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.175359E+13 | 0.558317E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.423736E+11 | 0.223542E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.255895E+12 | 0.771817E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.309047E+10 | 0.202953E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.854076E+10 | 0.300261E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.161368E+11 | 0.470175E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.230793E+11 | 0.637071E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.682147E+10 | 0.312627E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127109E+11 | 0.457401E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.194717E+11 | 0.631583E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.257361E+11 | 0.778551E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.643088E+10 | 0.295916E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.123169E+11 | 0.431764E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.160108E+11 | 0.471895E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.213473E+11 | 0.564413E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171693E+12 | 0.555461E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.309047E+10 | 0.202953E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.257361E+11 | 0.778551E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.162290E+11 | 0.234629E+11 | 0.605173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143126E+11 | 0.284499E+11 | 0.773563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164039E+11 | 0.395541E+11 | 0.556525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152456E+11 | 0.614734E+11 | 0.646316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169214E+11 | 0.112542E+12 | 0.889694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164078E+11 | 0.117088E+12 | 0.747866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167606E+11 | 0.125999E+12 | 0.115253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178224E+11 | 0.137052E+12 | 0.795159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169083E+11 | 0.119202E+12 | 0.121903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175086E+11 | 0.103346E+12 | 0.136297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168409E+11 | 0.577016E+11 | 0.172334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168575E+11 | 0.384024E+11 | 0.178776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198219E+12 | 0.964274E+12 | 0.122599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143126E+11 | 0.234629E+11 | 0.556525E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178224E+11 | 0.137052E+12 | 0.178776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.407037E+10 | 0.450995E+11 | 0.478999E+09 | 0.278918E+10 | 0.123361E+10 | 0.00 | 0.00 | 0.00 |
February | 0.413941E+10 | 0.634073E+11 | 0.188819E+09 | 0.139555E+10 | 0.205905E+10 | 0.00 | 0.00 | 0.00 |
March | 0.513503E+10 | 0.787557E+11 | 0.154232E+09 | 0.895350E+09 | 0.395791E+10 | 0.00 | 0.00 | 0.00 |
April | 0.598217E+10 | 0.125623E+12 | 8938309.03 | 538831.81 | 0.107374E+11 | 0.00 | 0.00 | 0.00 |
May | 0.613684E+10 | 0.164748E+12 | 0.00 | 0.00 | 0.465410E+11 | 0.00 | 0.00 | 0.00 |
June | 0.676698E+10 | 0.176548E+12 | 0.00 | 0.00 | 0.562720E+11 | 0.00 | 0.00 | 0.00 |
July | 0.718932E+10 | 0.191522E+12 | 0.00 | 0.00 | 0.615319E+11 | 0.00 | 0.00 | 0.00 |
August | 0.829194E+10 | 0.207654E+12 | 50364.64 | 0.00 | 0.608303E+11 | 0.00 | 0.00 | 0.00 |
September | 0.581197E+10 | 0.167214E+12 | 0.00 | 0.00 | 0.404694E+11 | 0.00 | 0.00 | 0.00 |
October | 0.660985E+10 | 0.152029E+12 | 1934895.78 | 19322281.18 | 0.341465E+11 | 0.00 | 0.00 | 0.00 |
November | 0.565623E+10 | 0.956431E+11 | 7786735.95 | 0.102577E+09 | 0.845565E+10 | 0.00 | 0.00 | 0.00 |
December | 0.527697E+10 | 0.706727E+11 | 0.222899E+09 | 0.117964E+10 | 0.445573E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710671E+11 | 0.153892E+13 | 0.106366E+10 | 0.638215E+10 | 0.330691E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.407037E+10 | 0.450995E+11 | 0.00 | 0.00 | 0.123361E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.829194E+10 | 0.207654E+12 | 0.478999E+09 | 0.278918E+10 | 0.615319E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.307216E+11 | 0.356664E+12 | 0.301294E+11 | 0.410279E+11 | 0.142100E+11 | 0.00 | 0.00 | 0.00 |
February | 0.292255E+11 | 0.503432E+12 | 0.145938E+11 | 0.197249E+11 | 0.234098E+11 | 0.00 | 0.00 | 0.00 |
March | 0.342934E+11 | 0.600063E+12 | 0.136925E+11 | 0.142976E+11 | 0.464857E+11 | 0.00 | 0.00 | 0.00 |
April | 0.376983E+11 | 0.938140E+12 | 0.171811E+09 | 72155832.44 | 0.107241E+12 | 0.00 | 0.00 | 0.00 |
May | 0.527052E+11 | 0.148979E+13 | 0.00 | 0.00 | 0.466344E+12 | 0.00 | 0.00 | 0.00 |
June | 0.544898E+11 | 0.152111E+13 | 0.00 | 0.00 | 0.560635E+12 | 0.00 | 0.00 | 0.00 |
July | 0.531142E+11 | 0.158918E+13 | 0.00 | 0.00 | 0.610963E+12 | 0.00 | 0.00 | 0.00 |
August | 0.569166E+11 | 0.164942E+13 | 0.00 | 0.00 | 0.603339E+12 | 0.00 | 0.00 | 0.00 |
September | 0.476834E+11 | 0.149734E+13 | 0.00 | 0.00 | 0.408255E+12 | 0.00 | 0.00 | 0.00 |
October | 0.500215E+11 | 0.127741E+13 | 0.150854E+09 | 0.316935E+09 | 0.340700E+12 | 0.00 | 0.00 | 0.00 |
November | 0.369961E+11 | 0.737943E+12 | 0.173301E+10 | 0.205489E+10 | 0.895870E+11 | 0.00 | 0.00 | 0.00 |
December | 0.328313E+11 | 0.522920E+12 | 0.207799E+11 | 0.243020E+11 | 0.459871E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516697E+12 | 0.126834E+14 | 0.812513E+11 | 0.101796E+12 | 0.331716E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.292255E+11 | 0.356664E+12 | 0.00 | 0.00 | 0.142100E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.569166E+11 | 0.164942E+13 | 0.301294E+11 | 0.410279E+11 | 0.610963E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.294521E+10 | 0.361328E+11 | 0.790998E+10 | 0.437510E+10 | 0.330801E+09 | 0.00 | 0.00 | 0.00 |
February | 0.292593E+10 | 0.515349E+11 | 0.474226E+10 | 0.214680E+10 | 0.108744E+10 | 0.00 | 0.00 | 0.00 |
March | 0.337110E+10 | 0.625148E+11 | 0.367484E+10 | 0.151532E+10 | 0.306023E+10 | 0.00 | 0.00 | 0.00 |
April | 0.388351E+10 | 0.989662E+11 | 0.142429E+09 | 7095535.53 | 0.915488E+10 | 0.00 | 0.00 | 0.00 |
May | 0.589754E+10 | 0.162768E+12 | 0.00 | 0.00 | 0.453410E+11 | 0.00 | 0.00 | 0.00 |
June | 0.624653E+10 | 0.168205E+12 | 0.00 | 0.00 | 0.543638E+11 | 0.00 | 0.00 | 0.00 |
July | 0.602484E+10 | 0.175074E+12 | 0.00 | 0.00 | 0.590669E+11 | 0.00 | 0.00 | 0.00 |
August | 0.638668E+10 | 0.179868E+12 | 0.00 | 0.00 | 0.587122E+11 | 0.00 | 0.00 | 0.00 |
September | 0.508566E+10 | 0.159507E+12 | 0.00 | 0.00 | 0.396067E+11 | 0.00 | 0.00 | 0.00 |
October | 0.522653E+10 | 0.135147E+12 | 0.131527E+09 | 32652808.53 | 0.332437E+11 | 0.00 | 0.00 | 0.00 |
November | 0.345792E+10 | 0.733722E+11 | 0.883507E+09 | 0.228732E+09 | 0.840671E+10 | 0.00 | 0.00 | 0.00 |
December | 0.311746E+10 | 0.517422E+11 | 0.554288E+10 | 0.295081E+10 | 0.409751E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545689E+11 | 0.135483E+13 | 0.230274E+11 | 0.112565E+11 | 0.316472E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.292593E+10 | 0.361328E+11 | 0.00 | 0.00 | 0.330801E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.638668E+10 | 0.179868E+12 | 0.790998E+10 | 0.437510E+10 | 0.590669E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.944430E+11 | 0.329488E+12 | 0.00 | 0.00 | 0.00 | 0.145151E+10 | 0.00 | 0.00 |
February | 0.853034E+11 | 0.520405E+12 | 0.00 | 0.00 | 0.00 | 0.752041E+09 | 0.00 | 0.00 |
March | 0.944430E+11 | 0.820889E+12 | 0.00 | 0.00 | 0.00 | 0.943268E+09 | 0.00 | 0.00 |
April | 0.913965E+11 | 0.103594E+13 | 0.00 | 0.00 | 0.00 | 0.272206E+09 | 0.00 | 0.00 |
May | 0.944430E+11 | 0.345536E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.913965E+11 | 0.572661E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.944430E+11 | 0.838901E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.944430E+11 | 0.108373E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.913965E+11 | 0.338658E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.944430E+11 | 0.590283E+12 | 0.00 | 0.00 | 0.00 | 0.204838E+09 | 0.00 | 0.00 |
November | 0.913965E+11 | 0.801291E+12 | 0.00 | 0.00 | 0.00 | 0.433245E+09 | 0.00 | 0.00 |
December | 0.944430E+11 | 0.106918E+13 | 0.00 | 0.00 | 0.00 | 0.968768E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111199E+13 | 0.834696E+13 | 0.00 | 0.00 | 0.00 | 0.502587E+10 | 0.00 | 0.00 |
Minimum of Months | 0.853034E+11 | 0.329488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944430E+11 | 0.108373E+13 | 0.00 | 0.00 | 0.00 | 0.145151E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138710E+10 | 0.508742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125287E+10 | 0.942583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138710E+10 | 0.156548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134236E+10 | 0.202344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138710E+10 | 0.589204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134236E+10 | 0.105597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138710E+10 | 0.159410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138710E+10 | 0.210225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134236E+10 | 0.571335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138710E+10 | 0.109268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134236E+10 | 0.153244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138710E+10 | 0.207478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163320E+11 | 0.156530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125287E+10 | 0.508742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138710E+10 | 0.210225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131618E+11 | 0.361577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118881E+11 | 0.797021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131618E+11 | 0.140448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127373E+11 | 0.189818E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131618E+11 | 0.536605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127373E+11 | 0.996134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131618E+11 | 0.151578E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131618E+11 | 0.200145E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127373E+11 | 0.511760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131618E+11 | 0.100780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127373E+11 | 0.138548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131618E+11 | 0.186989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154970E+12 | 0.142862E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118881E+11 | 0.361577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131618E+11 | 0.200145E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133736E+10 | 0.262969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120794E+10 | 0.722822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133736E+10 | 0.135180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129422E+10 | 0.188350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133736E+10 | 0.549589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129422E+10 | 0.101097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133736E+10 | 0.153158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133736E+10 | 0.201288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129422E+10 | 0.520359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133736E+10 | 0.999993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129422E+10 | 0.133202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133736E+10 | 0.178798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157464E+11 | 0.139665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120794E+10 | 0.262969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133736E+10 | 0.201288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.162290E+11 | 0.605173E+09 | 0.234629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143126E+11 | 0.773563E+09 | 0.284499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164039E+11 | 0.556525E+09 | 0.395541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152456E+11 | 0.646316E+09 | 0.614734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169214E+11 | 0.889694E+09 | 0.112542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164078E+11 | 0.747866E+09 | 0.117088E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167606E+11 | 0.115253E+10 | 0.125999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178224E+11 | 0.795159E+09 | 0.137052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169083E+11 | 0.121903E+10 | 0.119202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175086E+11 | 0.136297E+10 | 0.103346E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168409E+11 | 0.172334E+10 | 0.577016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168575E+11 | 0.178776E+10 | 0.384024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198219E+12 | 0.122599E+11 | 0.964274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.143126E+11 | 0.556525E+09 | 0.234629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178224E+11 | 0.178776E+10 | 0.137052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.407037E+10 | 0.478999E+09 | 0.450995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.413941E+10 | 0.188819E+09 | 0.634073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.513503E+10 | 0.154232E+09 | 0.787557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.598217E+10 | 8938309.03 | 0.125623E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.613684E+10 | 0.00 | 0.164748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.676698E+10 | 0.00 | 0.176548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.718932E+10 | 0.00 | 0.191522E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.829194E+10 | 50364.64 | 0.207654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.581197E+10 | 0.00 | 0.167214E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.660985E+10 | 1934895.78 | 0.152029E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.565623E+10 | 7786735.95 | 0.956431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.527697E+10 | 0.222899E+09 | 0.706727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710671E+11 | 0.106366E+10 | 0.153892E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.407037E+10 | 0.00 | 0.450995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.829194E+10 | 0.478999E+09 | 0.207654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.307216E+11 | 0.301294E+11 | 0.356664E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292255E+11 | 0.145938E+11 | 0.503432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342934E+11 | 0.136925E+11 | 0.600063E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.376983E+11 | 0.171811E+09 | 0.938140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.527052E+11 | 0.00 | 0.148979E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.544898E+11 | 0.00 | 0.152111E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.531142E+11 | 0.00 | 0.158918E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.569166E+11 | 0.00 | 0.164942E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.476834E+11 | 0.00 | 0.149734E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.500215E+11 | 0.150854E+09 | 0.127741E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.369961E+11 | 0.173301E+10 | 0.737943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.328313E+11 | 0.207799E+11 | 0.522920E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516697E+12 | 0.812513E+11 | 0.126834E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.292255E+11 | 0.00 | 0.356664E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.569166E+11 | 0.301294E+11 | 0.164942E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.294521E+10 | 0.790998E+10 | 0.361328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292593E+10 | 0.474226E+10 | 0.515349E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337110E+10 | 0.367484E+10 | 0.625148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388351E+10 | 0.142429E+09 | 0.989662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.589754E+10 | 0.00 | 0.162768E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.624653E+10 | 0.00 | 0.168205E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.602484E+10 | 0.00 | 0.175074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.638668E+10 | 0.00 | 0.179868E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.508566E+10 | 0.00 | 0.159507E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.522653E+10 | 0.131527E+09 | 0.135147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.345792E+10 | 0.883507E+09 | 0.733722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311746E+10 | 0.554288E+10 | 0.517422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.545689E+11 | 0.230274E+11 | 0.135483E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.292593E+10 | 0.00 | 0.361328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.638668E+10 | 0.790998E+10 | 0.179868E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.944430E+11 | 0.00 | 0.388302E+12 | 0.00 | 0.823893E+11 | 0.00 | 0.00 | 0.00 | 0.145804E+10 | 0.00 | 0.00 | 0.00 |
February | 0.853034E+11 | 0.00 | 0.616500E+12 | 0.00 | 0.127302E+12 | 0.00 | 0.00 | 0.00 | 0.755426E+09 | 0.00 | 0.00 | 0.00 |
March | 0.944430E+11 | 0.00 | 0.983474E+12 | 0.00 | 0.203934E+12 | 0.00 | 0.00 | 0.00 | 0.947514E+09 | 0.00 | 0.00 | 0.00 |
April | 0.913965E+11 | 0.00 | 0.127081E+13 | 0.00 | 0.278664E+12 | 0.00 | 0.00 | 0.00 | 0.273431E+09 | 0.00 | 0.00 | 0.00 |
May | 0.944430E+11 | 0.00 | 0.428026E+12 | 0.00 | 0.110566E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.913965E+11 | 0.00 | 0.718910E+12 | 0.00 | 0.184002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.944430E+11 | 0.00 | 0.106507E+13 | 0.00 | 0.270468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.944430E+11 | 0.00 | 0.137903E+13 | 0.00 | 0.341884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.913965E+11 | 0.00 | 0.417601E+12 | 0.00 | 0.106127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.944430E+11 | 0.00 | 0.726854E+12 | 0.00 | 0.174186E+12 | 0.00 | 0.00 | 0.00 | 0.205760E+09 | 0.00 | 0.00 | 0.00 |
November | 0.913965E+11 | 0.00 | 0.965162E+12 | 0.00 | 0.204655E+12 | 0.00 | 0.00 | 0.00 | 0.435195E+09 | 0.00 | 0.00 | 0.00 |
December | 0.944430E+11 | 0.00 | 0.128150E+13 | 0.00 | 0.256728E+12 | 0.00 | 0.00 | 0.00 | 0.973129E+09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111199E+13 | 0.00 | 0.102412E+14 | 0.00 | 0.234091E+13 | 0.00 | 0.00 | 0.00 | 0.504849E+10 | 0.00 | 0.00 | |
Minimum of Months | 0.853034E+11 | 0.00 | 0.388302E+12 | 0.00 | 0.823893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944430E+11 | 0.00 | 0.137903E+13 | 0.00 | 0.341884E+12 | 0.00 | 0.00 | 0.00 | 0.145804E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.138710E+10 | 0.00 | 0.595512E+10 | 0.00 | 0.125696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125287E+10 | 0.00 | 0.111135E+11 | 0.00 | 0.227384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138710E+10 | 0.00 | 0.186581E+11 | 0.00 | 0.382303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134236E+10 | 0.00 | 0.247747E+11 | 0.00 | 0.541044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138710E+10 | 0.00 | 0.730849E+10 | 0.00 | 0.190779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134236E+10 | 0.00 | 0.132732E+11 | 0.00 | 0.341967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138710E+10 | 0.00 | 0.202642E+11 | 0.00 | 0.517642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138710E+10 | 0.00 | 0.268763E+11 | 0.00 | 0.672425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134236E+10 | 0.00 | 0.705578E+10 | 0.00 | 0.181431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138710E+10 | 0.00 | 0.134384E+11 | 0.00 | 0.322105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134236E+10 | 0.00 | 0.183909E+11 | 0.00 | 0.386796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138710E+10 | 0.00 | 0.247334E+11 | 0.00 | 0.489296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163320E+11 | 0.00 | 0.191842E+12 | 0.00 | 0.437887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.125287E+10 | 0.00 | 0.595512E+10 | 0.00 | 0.125696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138710E+10 | 0.00 | 0.268763E+11 | 0.00 | 0.672425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.131618E+11 | 0.00 | 0.423736E+11 | 0.00 | 0.919241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118881E+11 | 0.00 | 0.940564E+11 | 0.00 | 0.195105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131618E+11 | 0.00 | 0.167515E+12 | 0.00 | 0.346337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127373E+11 | 0.00 | 0.232510E+12 | 0.00 | 0.509302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131618E+11 | 0.00 | 0.665806E+11 | 0.00 | 0.174564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127373E+11 | 0.00 | 0.125228E+12 | 0.00 | 0.323003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131618E+11 | 0.00 | 0.192702E+12 | 0.00 | 0.492337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131618E+11 | 0.00 | 0.255895E+12 | 0.00 | 0.640199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127373E+11 | 0.00 | 0.632184E+11 | 0.00 | 0.163489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131618E+11 | 0.00 | 0.124033E+12 | 0.00 | 0.298788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127373E+11 | 0.00 | 0.166400E+12 | 0.00 | 0.352877E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131618E+11 | 0.00 | 0.223080E+12 | 0.00 | 0.445542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154970E+12 | 0.00 | 0.175359E+13 | 0.00 | 0.403347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118881E+11 | 0.00 | 0.423736E+11 | 0.00 | 0.919241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131618E+11 | 0.00 | 0.255895E+12 | 0.00 | 0.640199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.133736E+10 | 0.00 | 0.309047E+10 | 0.00 | 0.692169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120794E+10 | 0.00 | 0.854076E+10 | 0.00 | 0.179467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133736E+10 | 0.00 | 0.161368E+11 | 0.00 | 0.336438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129422E+10 | 0.00 | 0.230793E+11 | 0.00 | 0.507648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133736E+10 | 0.00 | 0.682147E+10 | 0.00 | 0.178890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129422E+10 | 0.00 | 0.127109E+11 | 0.00 | 0.327979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133736E+10 | 0.00 | 0.194717E+11 | 0.00 | 0.497846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133736E+10 | 0.00 | 0.257361E+11 | 0.00 | 0.644815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129422E+10 | 0.00 | 0.643088E+10 | 0.00 | 0.166493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133736E+10 | 0.00 | 0.123169E+11 | 0.00 | 0.298027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129422E+10 | 0.00 | 0.160108E+11 | 0.00 | 0.342472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133736E+10 | 0.00 | 0.213473E+11 | 0.00 | 0.430677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157464E+11 | 0.00 | 0.171693E+12 | 0.00 | 0.397997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.120794E+10 | 0.00 | 0.309047E+10 | 0.00 | 0.692169E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133736E+10 | 0.00 | 0.257361E+11 | 0.00 | 0.644815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.241396E+09 | 0.143707E+10 | 0.00 | 0.168089E+09 | 0.00 | 0.00 | 0.601307E+11 | 0.00 | 1.06 |
February | 0.279041E+09 | 0.148550E+10 | 0.00 | 0.135663E+09 | 3722111.68 | 0.00 | 0.459176E+11 | 0.00 | 1.17 |
March | 0.182223E+09 | 0.319513E+10 | 0.00 | 0.137322E+09 | 4226603.20 | 0.00 | 0.485204E+11 | 0.00 | 1.14 |
April | 0.184416E+09 | 0.561043E+10 | 0.00 | 0.105690E+09 | 70948077.01 | 0.00 | 0.228655E+11 | 0.00 | 0.99 |
May | 1499485.33 | 0.260834E+11 | 0.00 | 4420693.27 | 0.142587E+09 | 0.00 | 19790066.85 | 0.00 | 0.33 |
June | 208042.84 | 0.314859E+11 | 0.00 | 4546221.58 | 0.201679E+09 | 0.00 | 89502338.88 | 0.00 | 0.35 |
July | 0.00 | 0.380034E+11 | 0.00 | 0.00 | 0.396220E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.386196E+11 | 0.00 | 494463.72 | 0.220290E+09 | 0.00 | 78099845.09 | 0.00 | 0.34 |
September | 511077.21 | 0.290316E+11 | 0.00 | 3513945.72 | 0.281435E+09 | 0.00 | 99642324.45 | 0.00 | 0.34 |
October | 50075412.50 | 0.219266E+11 | 0.00 | 63272680.10 | 0.225988E+09 | 0.00 | 0.132833E+11 | 0.00 | 0.69 |
November | 94457245.59 | 0.654656E+10 | 0.00 | 0.163442E+09 | 5987262.79 | 0.00 | 0.405065E+11 | 0.00 | 1.21 |
December | 0.199227E+09 | 0.416488E+10 | 0.00 | 0.167542E+09 | 8848300.88 | 0.00 | 0.550821E+11 | 0.00 | 1.02 |
Annual Sum or Average | 0.123305E+10 | 0.207590E+12 | 0.00 | 0.953995E+09 | 0.156193E+10 | 0.00 | 0.286593E+12 | 0.00 | 0.74 |
Minimum of Months | 0.00 | 0.143707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.279041E+09 | 0.386196E+11 | 0.00 | 0.168089E+09 | 0.396220E+09 | 0.00 | 0.601307E+11 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.400996E+10 | 0.357753E+10 | 0.00 | 56960429.15 | 0.00 | 0.00 | 0.315357E+11 | 0.00 | 0.60 |
February | 0.288922E+10 | 0.412718E+10 | 0.00 | 49924060.83 | 59657589.95 | 0.00 | 0.195282E+11 | 0.00 | 0.61 |
March | 0.249792E+10 | 0.639330E+10 | 0.00 | 72148094.37 | 0.135776E+09 | 0.00 | 0.271445E+11 | 0.00 | 0.68 |
April | 0.244672E+10 | 0.998447E+10 | 0.00 | 41041194.40 | 0.130366E+09 | 0.00 | 0.753077E+10 | 0.00 | 0.61 |
May | 0.00 | 0.212403E+11 | 0.00 | 0.00 | 0.227403E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.216204E+11 | 0.00 | 0.00 | 0.234204E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.247317E+11 | 0.00 | 0.00 | 0.401483E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 3000620.98 | 0.259283E+11 | 0.00 | 0.00 | 0.255752E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.259458E+11 | 0.00 | 0.00 | 0.451585E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.760840E+09 | 0.166930E+11 | 0.00 | 23609995.68 | 0.278580E+09 | 0.00 | 0.586571E+10 | 0.00 | 0.48 |
November | 0.328547E+10 | 0.796004E+10 | 0.00 | 66976570.15 | 75549682.83 | 0.00 | 0.182191E+11 | 0.00 | 0.68 |
December | 0.328356E+10 | 0.665906E+10 | 0.00 | 78327120.33 | 0.126399E+09 | 0.00 | 0.315190E+11 | 0.00 | 0.65 |
Annual Sum or Average | 0.191767E+11 | 0.174861E+12 | 0.00 | 0.388987E+09 | 0.237676E+10 | 0.00 | 0.141343E+12 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.357753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.400996E+10 | 0.259458E+11 | 0.00 | 78327120.33 | 0.451585E+09 | 0.00 | 0.315357E+11 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140545E+12 | 0.251550E+11 | 0.00 | 0.199236E+09 | 0.890393E+10 | 0.00 | 0.134036E+12 | 0.00 | 0.50 |
February | 0.842685E+11 | 0.318378E+11 | 0.00 | 0.172757E+09 | 0.833044E+10 | 0.00 | 0.771246E+11 | 0.00 | 0.50 |
March | 0.832294E+11 | 0.460626E+11 | 0.00 | 0.278624E+09 | 0.142846E+11 | 0.00 | 0.128359E+12 | 0.00 | 0.55 |
April | 0.212540E+11 | 0.852860E+11 | 0.00 | 0.200412E+09 | 0.155180E+11 | 0.00 | 0.393179E+11 | 0.00 | 0.51 |
May | 0.00 | 0.196935E+12 | 0.00 | 0.00 | 0.132192E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.204353E+12 | 0.00 | 0.00 | 0.120144E+11 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.229748E+12 | 0.00 | 0.00 | 0.184361E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.244364E+12 | 0.00 | 0.00 | 0.115856E+11 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.238006E+12 | 0.00 | 0.00 | 0.185441E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.117903E+11 | 0.151528E+12 | 0.00 | 0.131000E+09 | 0.133651E+11 | 0.00 | 0.404428E+11 | 0.00 | 0.45 |
November | 0.556813E+11 | 0.683220E+11 | 0.00 | 0.279199E+09 | 0.702031E+10 | 0.00 | 0.916521E+11 | 0.00 | 0.54 |
December | 0.107608E+12 | 0.564292E+11 | 0.00 | 0.234760E+09 | 0.966454E+10 | 0.00 | 0.120701E+12 | 0.00 | 0.50 |
Annual Sum or Average | 0.504377E+12 | 0.157803E+13 | 0.00 | 0.149599E+10 | 0.150886E+12 | 0.00 | 0.631633E+12 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.251550E+11 | 0.00 | 0.00 | 0.702031E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.140545E+12 | 0.244364E+12 | 0.00 | 0.279199E+09 | 0.185441E+11 | 0.00 | 0.134036E+12 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.190627E+11 | 0.268786E+10 | 0.00 | 5182631.10 | 0.121889E+10 | 0.184326E+09 | 0.440190E+10 | 0.00 | 0.49 |
February | 0.102499E+11 | 0.332617E+10 | 0.00 | 7419049.94 | 0.127006E+10 | 0.159674E+09 | 0.410650E+10 | 0.00 | 0.49 |
March | 0.115814E+11 | 0.500916E+10 | 0.00 | 13435075.69 | 0.162290E+10 | 46775822.94 | 0.708515E+10 | 0.00 | 0.54 |
April | 0.250442E+10 | 0.838435E+10 | 0.00 | 13656205.86 | 0.189476E+10 | 0.00 | 0.317534E+10 | 0.00 | 0.50 |
May | 0.00 | 0.197954E+11 | 0.00 | 0.00 | 0.903182E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.211341E+11 | 0.00 | 0.00 | 0.293265E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.244010E+11 | 0.00 | 0.00 | 0.592812E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.248187E+11 | 0.00 | 0.00 | 0.647499E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.233774E+11 | 0.00 | 0.00 | 0.208816E+10 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 0.173841E+10 | 0.150472E+11 | 0.00 | 9337959.15 | 0.113958E+10 | 0.00 | 0.272118E+10 | 0.00 | 0.44 |
November | 0.723294E+10 | 0.589412E+10 | 0.00 | 14119379.77 | 0.179581E+10 | 0.00 | 0.535098E+10 | 0.00 | 0.51 |
December | 0.165032E+11 | 0.482197E+10 | 0.00 | 4607159.07 | 0.191668E+10 | 38019475.36 | 0.277636E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.688729E+11 | 0.158697E+12 | 0.00 | 67757460.59 | 0.153836E+11 | 0.428795E+09 | 0.296174E+11 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.268786E+10 | 0.00 | 0.00 | 0.293265E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.190627E+11 | 0.248187E+11 | 0.00 | 14119379.77 | 0.208816E+10 | 0.184326E+09 | 0.708515E+10 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.310667E+10 | 0.406695E+09 | 0.00 | 733781.75 | 34991917.91 | 6359915.50 | 0.535287E+09 | 0.00 | 0.51 |
February | 0.168112E+10 | 0.505784E+09 | 0.00 | 1375273.43 | 19194045.71 | 0.00 | 0.605661E+09 | 0.00 | 0.52 |
March | 0.174047E+10 | 0.868099E+09 | 0.00 | 2728594.70 | 19419915.28 | 0.00 | 0.120983E+10 | 0.00 | 0.60 |
April | 0.579456E+09 | 0.144705E+10 | 0.00 | 2461750.16 | 17867542.23 | 0.00 | 0.500053E+09 | 0.00 | 0.63 |
May | 0.00 | 0.363050E+10 | 0.00 | 0.00 | 28551500.35 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.406256E+10 | 0.00 | 0.00 | 29405435.80 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.463097E+10 | 0.00 | 0.00 | 50408102.35 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 376741.81 | 0.458736E+10 | 0.00 | 0.00 | 32110819.75 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.406756E+10 | 0.00 | 0.00 | 56698636.85 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.330354E+09 | 0.265397E+10 | 0.00 | 1386366.97 | 34976953.59 | 0.00 | 0.396564E+09 | 0.00 | 0.55 |
November | 0.123892E+10 | 0.105041E+10 | 0.00 | 2950432.00 | 9485611.18 | 0.00 | 0.963514E+09 | 0.00 | 0.60 |
December | 0.234018E+10 | 0.826733E+09 | 0.00 | 1731664.34 | 19716638.48 | 0.00 | 0.934258E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.110176E+11 | 0.287377E+11 | 0.00 | 13367863.35 | 0.352827E+09 | 6359915.50 | 0.514516E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.406695E+09 | 0.00 | 0.00 | 9485611.18 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.310667E+10 | 0.463097E+10 | 0.00 | 2950432.00 | 56698636.85 | 6359915.50 | 0.120983E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208796E+10 | 0.261639E+09 | 0.00 | 1615655.51 | 90931539.42 | 21336000.11 | 0.114188E+10 | 0.00 | 0.68 |
February | 0.123232E+10 | 0.365259E+09 | 0.00 | 1788933.77 | 68260070.02 | 1102482.12 | 0.847780E+09 | 0.00 | 0.72 |
March | 0.154201E+10 | 0.647917E+09 | 0.00 | 3050643.79 | 87236364.24 | 0.00 | 0.123511E+10 | 0.00 | 0.84 |
April | 0.516455E+09 | 0.112149E+10 | 0.00 | 2355385.99 | 0.113779E+09 | 0.00 | 0.592130E+09 | 0.00 | 0.85 |
May | 0.00 | 0.302178E+10 | 0.00 | 0.00 | 25636992.71 | 0.00 | 0.00 | 0.00 | 0.74 |
June | 0.00 | 0.319302E+10 | 0.00 | 0.00 | 31074192.81 | 0.00 | 0.00 | 0.00 | 0.76 |
July | 0.00 | 0.354726E+10 | 0.00 | 0.00 | 43231671.05 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 323106.35 | 0.329067E+10 | 0.00 | 0.00 | 66151517.04 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.314954E+10 | 0.00 | 0.00 | 97796200.74 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.298112E+09 | 0.207065E+10 | 0.00 | 1223900.80 | 66738426.81 | 0.00 | 0.326088E+09 | 0.00 | 0.68 |
November | 0.105494E+10 | 0.718499E+09 | 0.00 | 2826374.37 | 0.106103E+09 | 0.00 | 0.929145E+09 | 0.00 | 0.78 |
December | 0.202060E+10 | 0.435806E+09 | 0.00 | 1734401.23 | 0.160363E+09 | 32801017.09 | 0.822686E+09 | 0.00 | 0.67 |
Annual Sum or Average | 0.875271E+10 | 0.218235E+11 | 0.00 | 14595295.46 | 0.957302E+09 | 55239499.32 | 0.589483E+10 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.261639E+09 | 0.00 | 0.00 | 25636992.71 | 0.00 | 0.00 | 0.00 | 0.64 |
Maximum of Months | 0.208796E+10 | 0.354726E+10 | 0.00 | 3050643.79 | 0.160363E+09 | 32801017.09 | 0.123511E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.170113E+10 | 0.643289E+09 | 0.00 | 9681341.01 | 12190505.38 | 15882834.71 | 0.452729E+10 | 0.00 | 0.89 |
February | 0.108999E+10 | 0.927449E+09 | 0.00 | 5816300.14 | 10413313.34 | 11795458.95 | 0.240751E+10 | 0.00 | 0.85 |
March | 0.160243E+10 | 0.110070E+10 | 0.00 | 5124987.07 | 21762982.71 | 0.00 | 0.199651E+10 | 0.00 | 0.78 |
April | 0.597458E+09 | 0.157997E+10 | 0.00 | 2650401.15 | 24345526.09 | 0.00 | 0.521832E+09 | 0.00 | 0.69 |
May | 0.00 | 0.364101E+10 | 0.00 | 0.00 | 28536326.02 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.395816E+10 | 0.00 | 0.00 | 29389807.63 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.460129E+10 | 0.00 | 0.00 | 50381311.84 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 376541.58 | 0.485987E+10 | 0.00 | 0.00 | 32093753.74 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 0.00 | 0.473392E+10 | 0.00 | 0.00 | 56668503.10 | 0.00 | 0.00 | 0.00 | 0.62 |
October | 0.267793E+09 | 0.368817E+10 | 0.00 | 2804757.13 | 34958364.31 | 0.00 | 0.668024E+09 | 0.00 | 0.79 |
November | 0.762417E+09 | 0.160258E+10 | 0.00 | 11988083.78 | 9480569.84 | 0.00 | 0.289572E+10 | 0.00 | 1.03 |
December | 0.147848E+10 | 0.127209E+10 | 0.00 | 11995559.84 | 16130513.04 | 20298641.49 | 0.393630E+10 | 0.00 | 0.95 |
Annual Sum or Average | 0.750007E+10 | 0.326085E+11 | 0.00 | 50061430.12 | 0.326351E+09 | 47976935.16 | 0.169532E+11 | 0.00 | 0.75 |
Minimum of Months | 0.00 | 0.643289E+09 | 0.00 | 0.00 | 9480569.84 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.170113E+10 | 0.485987E+10 | 0.00 | 11995559.84 | 56668503.10 | 20298641.49 | 0.452729E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.267754E+10 | 0.492671E+09 | 0.00 | 2726875.16 | 2762023.35 | 0.00 | 0.159907E+10 | 0.00 | 0.92 |
February | 0.122645E+10 | 0.668911E+09 | 0.00 | 3827012.70 | 3909750.94 | 0.00 | 0.156541E+10 | 0.00 | 1.02 |
March | 0.923133E+09 | 0.108049E+10 | 0.00 | 7471504.15 | 9171325.76 | 0.00 | 0.289931E+10 | 0.00 | 1.24 |
April | 0.267299E+09 | 0.207185E+10 | 0.00 | 7623305.00 | 5138865.27 | 0.00 | 0.117861E+10 | 0.00 | 1.37 |
May | 0.00 | 0.354894E+10 | 0.00 | 0.00 | 23470569.58 | 0.00 | 0.00 | 0.00 | 0.87 |
June | 0.00 | 0.419653E+10 | 0.00 | 0.00 | 9041534.70 | 0.00 | 0.00 | 0.00 | 1.00 |
July | 0.00 | 0.504799E+10 | 0.00 | 0.00 | 14852422.70 | 0.00 | 0.00 | 0.00 | 0.95 |
August | 368556.81 | 0.554731E+10 | 0.00 | 4564.97 | 9537881.61 | 0.00 | 34330.36 | 0.00 | 1.11 |
September | 0.00 | 0.411516E+10 | 0.00 | 0.00 | 37801847.21 | 0.00 | 0.00 | 0.00 | 0.82 |
October | 0.179260E+09 | 0.294423E+10 | 0.00 | 2427283.19 | 27758971.21 | 0.00 | 0.667434E+09 | 0.00 | 0.97 |
November | 0.623735E+09 | 0.131015E+10 | 0.00 | 7577850.61 | 1664623.41 | 0.00 | 0.213379E+10 | 0.00 | 1.19 |
December | 0.911924E+09 | 0.112927E+10 | 0.00 | 7555486.60 | 17099209.20 | 0.00 | 0.332643E+10 | 0.00 | 1.13 |
Annual Sum or Average | 0.680972E+10 | 0.321535E+11 | 0.00 | 39213882.39 | 0.162209E+09 | 0.00 | 0.133701E+11 | 0.00 | 1.05 |
Minimum of Months | 0.00 | 0.492671E+09 | 0.00 | 0.00 | 1664623.41 | 0.00 | 0.00 | 0.00 | 0.82 |
Maximum of Months | 0.267754E+10 | 0.554731E+10 | 0.00 | 7623305.00 | 37801847.21 | 0.00 | 0.332643E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.265313E+11 | 0.209280E+10 | 0.00 | 152723.18 | 0.203154E+10 | 0.630771E+10 | 55226236.05 | 0.00 | 0.48 |
February | 0.160175E+11 | 0.292145E+10 | 0.00 | 746852.77 | 0.192383E+10 | 0.264282E+10 | 0.590780E+09 | 0.00 | 0.48 |
March | 0.202663E+11 | 0.560617E+10 | 0.00 | 3664341.63 | 0.215801E+10 | 0.249678E+10 | 0.143771E+10 | 0.00 | 0.52 |
April | 0.529704E+10 | 0.113626E+11 | 0.00 | 9717126.17 | 0.240695E+10 | 0.00 | 0.155228E+10 | 0.00 | 0.52 |
May | 0.00 | 0.350979E+11 | 0.00 | 0.00 | 0.286961E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.400465E+11 | 0.00 | 0.00 | 0.372765E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
July | 0.00 | 0.460465E+11 | 0.00 | 0.00 | 0.512433E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.449489E+11 | 0.00 | 0.00 | 0.366412E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.380911E+11 | 0.00 | 0.00 | 0.134661E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.375417E+10 | 0.243994E+11 | 0.00 | 7420570.95 | 0.111042E+10 | 0.00 | 0.207707E+10 | 0.00 | 0.51 |
November | 0.143616E+11 | 0.748348E+10 | 0.00 | 6320210.17 | 0.213947E+10 | 95120380.60 | 0.217688E+10 | 0.00 | 0.50 |
December | 0.229294E+11 | 0.493153E+10 | 0.00 | 621473.60 | 0.307267E+10 | 0.379033E+10 | 0.292005E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.109157E+12 | 0.263028E+12 | 0.00 | 28643298.47 | 0.177281E+11 | 0.153328E+11 | 0.818195E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.209280E+10 | 0.00 | 0.00 | 0.286961E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.265313E+11 | 0.460465E+11 | 0.00 | 9717126.17 | 0.307267E+10 | 0.630771E+10 | 0.217688E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.237065E+11 | 0.176164E+10 | 0.00 | 1779744.04 | 0.199287E+10 | 0.398421E+10 | 0.178728E+10 | 0.00 | 0.66 |
February | 0.138930E+11 | 0.311590E+10 | 0.00 | 5863165.62 | 0.152273E+10 | 0.129022E+10 | 0.231757E+10 | 0.00 | 0.69 |
March | 0.143412E+11 | 0.598233E+10 | 0.00 | 16975597.42 | 0.183275E+10 | 0.202793E+10 | 0.659845E+10 | 0.00 | 0.80 |
April | 0.333800E+10 | 0.116411E+11 | 0.00 | 18498863.50 | 0.230205E+10 | 0.00 | 0.466873E+10 | 0.00 | 0.84 |
May | 0.00 | 0.318771E+11 | 0.00 | 0.00 | 0.436849E+09 | 0.00 | 0.00 | 0.00 | 0.81 |
June | 0.00 | 0.352029E+11 | 0.00 | 0.00 | 0.333698E+09 | 0.00 | 0.00 | 0.00 | 0.85 |
July | 0.00 | 0.402748E+11 | 0.00 | 0.00 | 0.611354E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
August | 0.00 | 0.377855E+11 | 0.00 | 0.00 | 0.102205E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
September | 0.00 | 0.305654E+11 | 0.00 | 0.00 | 0.337575E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 0.314086E+10 | 0.216539E+11 | 0.00 | 8584775.65 | 0.137043E+10 | 0.00 | 0.215895E+10 | 0.00 | 0.71 |
November | 0.102302E+11 | 0.655739E+10 | 0.00 | 13116053.50 | 0.218113E+10 | 41288257.09 | 0.502756E+10 | 0.00 | 0.71 |
December | 0.196407E+11 | 0.365534E+10 | 0.00 | 3645312.76 | 0.305113E+10 | 0.281689E+10 | 0.182821E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.882904E+11 | 0.230073E+12 | 0.00 | 68463512.49 | 0.200328E+11 | 0.101605E+11 | 0.243867E+11 | 0.00 | 0.75 |
Minimum of Months | 0.00 | 0.176164E+10 | 0.00 | 0.00 | 0.333698E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
Maximum of Months | 0.237065E+11 | 0.402748E+11 | 0.00 | 18498863.50 | 0.337575E+10 | 0.398421E+10 | 0.659845E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141142E+11 | 0.609258E+10 | 0.00 | 83321329.34 | 0.684050E+09 | 0.253278E+10 | 0.383236E+11 | 0.00 | 0.85 |
February | 0.940104E+10 | 0.961448E+10 | 0.00 | 46402936.40 | 0.369555E+09 | 0.109319E+10 | 0.181025E+11 | 0.00 | 0.81 |
March | 0.153151E+11 | 0.939561E+10 | 0.00 | 34494768.56 | 0.116367E+10 | 0.178895E+10 | 0.117839E+11 | 0.00 | 0.70 |
April | 0.455953E+10 | 0.139857E+11 | 0.00 | 16392775.75 | 0.165154E+10 | 0.00 | 0.287780E+10 | 0.00 | 0.61 |
May | 0.00 | 0.356146E+11 | 0.00 | 0.00 | 0.286851E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.389132E+11 | 0.00 | 0.00 | 0.391876E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.458609E+11 | 0.00 | 0.00 | 0.512236E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.486636E+11 | 0.00 | 0.00 | 0.350826E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.468627E+11 | 0.00 | 0.00 | 0.921937E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.269039E+10 | 0.375105E+11 | 0.00 | 22243028.87 | 0.422664E+09 | 0.00 | 0.512050E+10 | 0.00 | 0.80 |
November | 0.664517E+10 | 0.155955E+11 | 0.00 | 0.106847E+09 | 0.734378E+09 | 0.00 | 0.229139E+11 | 0.00 | 0.97 |
December | 0.140555E+11 | 0.126223E+11 | 0.00 | 96887440.75 | 0.844897E+09 | 0.128975E+10 | 0.281207E+11 | 0.00 | 0.88 |
Annual Sum or Average | 0.667809E+11 | 0.320732E+12 | 0.00 | 0.406589E+09 | 0.833448E+10 | 0.670468E+10 | 0.127243E+12 | 0.00 | 0.72 |
Minimum of Months | 0.00 | 0.609258E+10 | 0.00 | 0.00 | 0.286851E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.153151E+11 | 0.486636E+11 | 0.00 | 0.106847E+09 | 0.165154E+10 | 0.253278E+10 | 0.383236E+11 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231838E+11 | 0.297483E+10 | 0.00 | 8249544.70 | 0.144536E+10 | 0.355614E+10 | 0.495624E+10 | 0.00 | 0.73 |
February | 0.138369E+11 | 0.428875E+10 | 0.00 | 8453988.77 | 0.126131E+10 | 0.149974E+10 | 0.351704E+10 | 0.00 | 0.77 |
March | 0.173105E+11 | 0.608388E+10 | 0.00 | 18137638.51 | 0.142046E+10 | 0.125967E+10 | 0.622223E+10 | 0.00 | 0.85 |
April | 0.400851E+10 | 0.134360E+11 | 0.00 | 19187386.63 | 0.142270E+10 | 0.00 | 0.322918E+10 | 0.00 | 0.89 |
May | 0.00 | 0.309309E+11 | 0.00 | 0.00 | 0.228556E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
June | 0.00 | 0.346395E+11 | 0.00 | 0.00 | 0.326542E+09 | 0.00 | 0.00 | 0.00 | 0.86 |
July | 0.00 | 0.396543E+11 | 0.00 | 0.00 | 0.230013E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.408298E+11 | 0.00 | 0.00 | 0.407049E+09 | 0.00 | 0.00 | 0.00 | 0.86 |
September | 0.00 | 0.334544E+11 | 0.00 | 0.00 | 0.203514E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 0.329849E+10 | 0.230683E+11 | 0.00 | 8608041.57 | 0.713947E+09 | 0.00 | 0.244506E+10 | 0.00 | 0.77 |
November | 0.122994E+11 | 0.765414E+10 | 0.00 | 14880532.79 | 0.171440E+10 | 0.00 | 0.448005E+10 | 0.00 | 0.80 |
December | 0.212034E+11 | 0.602948E+10 | 0.00 | 8503152.75 | 0.195645E+10 | 0.152964E+10 | 0.339733E+10 | 0.00 | 0.73 |
Annual Sum or Average | 0.951410E+11 | 0.243044E+12 | 0.00 | 86020285.72 | 0.131619E+11 | 0.784520E+10 | 0.282471E+11 | 0.00 | 0.79 |
Minimum of Months | 0.00 | 0.297483E+10 | 0.00 | 0.00 | 0.228556E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
Maximum of Months | 0.231838E+11 | 0.408298E+11 | 0.00 | 19187386.63 | 0.203514E+10 | 0.355614E+10 | 0.622223E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183750E+10 | 0.237223E+09 | 0.00 | 11391.28 | 0.246734E+09 | 0.115084E+10 | 3296861.84 | 0.00 | 0.49 |
February | 0.118449E+10 | 0.315196E+09 | 0.00 | 60643.74 | 0.250330E+09 | 0.593822E+09 | 29121895.61 | 0.00 | 0.48 |
March | 0.173799E+10 | 0.606555E+09 | 0.00 | 372426.72 | 0.253912E+09 | 0.422746E+09 | 0.121822E+09 | 0.00 | 0.53 |
April | 0.459566E+09 | 0.110225E+10 | 0.00 | 1024852.71 | 0.310932E+09 | 21738393.61 | 0.201130E+09 | 0.00 | 0.52 |
May | 0.00 | 0.343403E+10 | 0.00 | 0.00 | 31301495.63 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.390049E+10 | 0.00 | 0.00 | 49225523.54 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.456093E+10 | 0.00 | 0.00 | 60380200.38 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.438944E+10 | 0.00 | 0.00 | 74484273.99 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.366755E+10 | 0.00 | 0.00 | 0.249899E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.317711E+09 | 0.233357E+10 | 0.00 | 666498.96 | 0.161301E+09 | 29983716.83 | 0.179543E+09 | 0.00 | 0.51 |
November | 0.121811E+10 | 0.696530E+09 | 2208603.66 | 460777.25 | 0.291231E+09 | 0.142704E+09 | 0.158551E+09 | 8878.47 | 0.50 |
December | 0.159029E+10 | 0.460207E+09 | 444136.55 | 35469.51 | 0.373116E+09 | 0.838226E+09 | 17206889.77 | 5442.93 | 0.48 |
Annual Sum or Average | 0.834566E+10 | 0.257040E+11 | 2652740.21 | 2632060.16 | 0.235285E+10 | 0.320006E+10 | 0.710671E+09 | 14321.40 | 0.53 |
Minimum of Months | 0.00 | 0.237223E+09 | 0.00 | 0.00 | 31301495.63 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.183750E+10 | 0.456093E+10 | 2208603.66 | 1024852.71 | 0.373116E+09 | 0.115084E+10 | 0.201130E+09 | 8878.47 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201723E+10 | 0.221345E+09 | 0.00 | 16937.52 | 0.212328E+09 | 0.592747E+09 | 11175463.08 | 0.00 | 0.66 |
February | 0.115240E+10 | 0.360277E+09 | 0.00 | 429325.68 | 0.170361E+09 | 0.319362E+09 | 0.124967E+09 | 0.00 | 0.68 |
March | 0.116855E+10 | 0.670342E+09 | 0.00 | 1353427.40 | 0.190887E+09 | 0.307862E+09 | 0.605487E+09 | 0.00 | 0.79 |
April | 0.287671E+09 | 0.118682E+10 | 0.00 | 1816153.42 | 0.240545E+09 | 658661.64 | 0.474970E+09 | 0.00 | 0.83 |
May | 0.00 | 0.308226E+10 | 0.00 | 0.00 | 45337015.80 | 0.00 | 0.00 | 0.00 | 0.80 |
June | 0.00 | 0.341617E+10 | 0.00 | 0.00 | 39793243.65 | 0.00 | 0.00 | 0.00 | 0.85 |
July | 0.00 | 0.396744E+10 | 0.00 | 0.00 | 82698314.13 | 0.00 | 0.00 | 0.00 | 0.77 |
August | 0.00 | 0.369402E+10 | 0.00 | 0.00 | 0.127346E+09 | 0.00 | 0.00 | 0.00 | 0.80 |
September | 0.00 | 0.303099E+10 | 0.00 | 0.00 | 0.346728E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 0.252799E+09 | 0.206207E+10 | 0.00 | 743017.15 | 0.200253E+09 | 17317105.45 | 0.198007E+09 | 0.00 | 0.71 |
November | 0.905194E+09 | 0.654038E+09 | 850769.04 | 898438.07 | 0.249002E+09 | 69270093.56 | 0.376127E+09 | 766.84 | 0.70 |
December | 0.153984E+10 | 0.366964E+09 | 0.00 | 158511.18 | 0.336710E+09 | 0.524050E+09 | 88203117.91 | 0.00 | 0.65 |
Annual Sum or Average | 0.732367E+10 | 0.227127E+11 | 850769.04 | 5415810.43 | 0.224199E+10 | 0.183127E+10 | 0.187894E+10 | 766.84 | 0.74 |
Minimum of Months | 0.00 | 0.221345E+09 | 0.00 | 0.00 | 39793243.65 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.201723E+10 | 0.396744E+10 | 850769.04 | 1816153.42 | 0.346728E+09 | 0.592747E+09 | 0.605487E+09 | 766.84 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123474E+10 | 0.710812E+09 | 0.00 | 6131769.95 | 0.101799E+09 | 0.440212E+09 | 0.285329E+10 | 0.00 | 0.78 |
February | 0.826836E+09 | 0.104144E+10 | 0.00 | 3623350.40 | 85785999.28 | 0.225956E+09 | 0.149270E+10 | 0.00 | 0.77 |
March | 0.128146E+10 | 0.102178E+10 | 0.00 | 3090888.41 | 0.146693E+09 | 0.337052E+09 | 0.113229E+10 | 0.00 | 0.69 |
April | 0.413654E+09 | 0.136011E+10 | 0.00 | 1714161.69 | 0.228003E+09 | 824204.05 | 0.342018E+09 | 0.00 | 0.60 |
May | 0.00 | 0.347326E+10 | 0.00 | 0.00 | 35989071.63 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.378675E+10 | 0.00 | 0.00 | 58973695.58 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.453115E+10 | 0.00 | 0.00 | 67941965.41 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.471863E+10 | 0.00 | 0.00 | 75257989.36 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.449779E+10 | 0.00 | 0.00 | 0.200073E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
October | 0.251024E+09 | 0.360594E+10 | 0.00 | 1938408.10 | 52886052.56 | 2139268.22 | 0.456095E+09 | 0.00 | 0.78 |
November | 0.621411E+09 | 0.150154E+10 | 0.00 | 8193005.71 | 0.133321E+09 | 41369153.11 | 0.202795E+10 | 0.00 | 0.93 |
December | 0.110217E+10 | 0.121673E+10 | 0.00 | 7425245.43 | 0.145081E+09 | 0.381273E+09 | 0.219095E+10 | 0.00 | 0.84 |
Annual Sum or Average | 0.573129E+10 | 0.314659E+11 | 0.00 | 32116829.68 | 0.133180E+10 | 0.142883E+10 | 0.104953E+11 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 0.710812E+09 | 0.00 | 0.00 | 35989071.63 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.128146E+10 | 0.471863E+10 | 0.00 | 8193005.71 | 0.228003E+09 | 0.440212E+09 | 0.285329E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192273E+10 | 0.313326E+09 | 0.00 | 609294.80 | 0.214618E+09 | 0.615978E+09 | 0.403632E+09 | 0.00 | 0.76 |
February | 0.118487E+10 | 0.445964E+09 | 0.00 | 732015.26 | 0.206332E+09 | 0.312509E+09 | 0.322152E+09 | 0.00 | 0.79 |
March | 0.150422E+10 | 0.618990E+09 | 0.00 | 1762725.53 | 0.220183E+09 | 0.280669E+09 | 0.666019E+09 | 0.00 | 0.88 |
April | 0.392468E+09 | 0.129539E+10 | 0.00 | 1950978.25 | 0.229632E+09 | 0.00 | 0.371427E+09 | 0.00 | 0.89 |
May | 0.00 | 0.292101E+10 | 0.00 | 0.00 | 86463018.92 | 0.00 | 0.00 | 0.00 | 0.77 |
June | 0.00 | 0.330625E+10 | 0.00 | 0.00 | 45819401.88 | 0.00 | 0.00 | 0.00 | 0.83 |
July | 0.00 | 0.383750E+10 | 0.00 | 0.00 | 56582998.90 | 0.00 | 0.00 | 0.00 | 0.74 |
August | 0.00 | 0.393008E+10 | 0.00 | 0.00 | 74327110.73 | 0.00 | 0.00 | 0.00 | 0.83 |
September | 0.00 | 0.321512E+10 | 0.00 | 0.00 | 0.306964E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
October | 0.343434E+09 | 0.216567E+10 | 0.00 | 768089.98 | 0.153690E+09 | 0.00 | 0.197976E+09 | 0.00 | 0.77 |
November | 0.108800E+10 | 0.728152E+09 | 0.00 | 1355323.98 | 0.256991E+09 | 59782864.83 | 0.443222E+09 | 0.00 | 0.81 |
December | 0.169236E+10 | 0.560242E+09 | 440255.91 | 677323.64 | 0.295439E+09 | 0.438546E+09 | 0.298335E+09 | 762.25 | 0.76 |
Annual Sum or Average | 0.812809E+10 | 0.233377E+11 | 440255.91 | 7855751.45 | 0.214704E+10 | 0.170748E+10 | 0.270276E+10 | 762.25 | 0.80 |
Minimum of Months | 0.00 | 0.313326E+09 | 0.00 | 0.00 | 45819401.88 | 0.00 | 0.00 | 0.00 | 0.72 |
Maximum of Months | 0.192273E+10 | 0.393008E+10 | 440255.91 | 1950978.25 | 0.306964E+09 | 0.615978E+09 | 0.666019E+09 | 762.25 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.908988E+09 | 0.00 | 0.168661E+09 | 0.00 | 0.00 | 0.712132E+10 | 0.00 | 0.32 |
February | 0.00 | 0.120340E+10 | 0.00 | 0.224894E+09 | 0.00 | 0.00 | 0.378164E+10 | 0.00 | 0.32 |
March | 0.00 | 0.190941E+10 | 0.00 | 0.445735E+09 | 0.00 | 0.00 | 0.443312E+10 | 0.00 | 0.34 |
April | 0.00 | 0.351578E+10 | 0.00 | 0.223438E+09 | 0.00 | 0.00 | 0.937199E+09 | 0.00 | 0.32 |
May | 0.00 | 0.102319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.118754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.134470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.128265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.104310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 0.00 | 0.802150E+10 | 0.00 | 77941019.18 | 0.00 | 0.00 | 0.903386E+09 | 0.00 | 0.32 |
November | 0.00 | 0.281497E+10 | 0.00 | 0.332913E+09 | 0.00 | 0.00 | 0.242122E+10 | 0.00 | 0.32 |
December | 0.00 | 0.201369E+10 | 0.00 | 0.576797E+09 | 0.00 | 0.00 | 0.488568E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.791995E+11 | 0.00 | 0.205038E+10 | 0.00 | 0.00 | 0.244836E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.908988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |