Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:59
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2020-06-03 19:59:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31666.51 | 683.64 | 683.64 |
Net Site Energy | 31666.51 | 683.64 | 683.64 |
Total Source Energy | 99202.10 | 2141.65 | 2141.65 |
Net Source Energy | 99202.10 | 2141.65 | 2141.65 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 87.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6684.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2580.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 341.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1955.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2247.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 694.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1858.19 | 0.00 | 0.00 | 0.00 | 0.00 | 20649.13 |
Humidification | 106.87 | 0.00 | 0.00 | 0.00 | 0.00 | 39.76 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 433.65 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31145.27 | 521.23 | 0.00 | 0.00 | 0.00 | 22969.05 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 87.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3689.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 2994.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 2580.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 341.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2247.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 694.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 1287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 20649.13 | |
Humidification | General | 106.87 | 0.00 | 0.00 | 0.00 | 0.00 | 39.76 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 433.65 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 250.25 | 11.25 | 0.00 | 0.00 | 0.00 | 0.50 |
Other | 359.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 672.39 | 11.25 | 0.00 | 0.00 | 0.00 | 0.50 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 250.25 | 11.25 | 0.00 | 0.00 | 0.00 | 0.50 |
Other | 359.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 672.39 | 11.25 | 0.00 | 0.00 | 0.00 | 0.50 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31145.274 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31145.274 | 100.00 |
Total On-Site and Utility Electric Sources | 31145.274 | 100.00 |
Total Electricity End Uses | 31145.274 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22969.05 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22969.05 | 100.00 |
Total Water End Uses | 22969.05 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 306.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2135.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:59 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.8889 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.8889 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.8889 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.8889 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-AUG-15:30 | 02-JAN-06:10 | - | - | - | 03-MAY-15:09 |
Heating | 0.00 | 711408.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 613552.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 223670.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 89219.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 130004.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 42810.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 83553.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1961182.27 | 718689.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 711408.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 437341.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 223670.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3400.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 130004.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 42810.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 39777.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 94.94 | 0.00 | 0.00 | 0.00 |
Cooling | 21169.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8170.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1082.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46479.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6193.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7118.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2199.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5884.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 338.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 470.08 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 98637.08 | 565.02 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.05 | 0.00 | 0.00 | 0.00 |
Cooling | 457.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 176.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 133.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 153.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 47.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 127.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.15 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2129.45 | 12.20 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.05 | 0.00 | 0.00 | 0.00 |
Cooling | 457.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 176.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 133.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 153.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 47.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 127.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.15 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2129.45 | 12.20 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.42 |
DATACENTER BOT DIRECT AIR | 0.478997 |
DATACENTER MID DIRECT AIR | 4.57 |
DATACENTER TOP DIRECT AIR | 0.458475 |
DATACENTER BASEMENT DIRECT AIR | 21.77 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.99 | 0.317799 | 0.270000 | 1.62 | 0.847464 | 0.500000 | 0.001199 | 0.000350 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 57.19 | 0.332593 | 0.283000 | 16.18 | 0.886913 | 0.500000 | 0.001146 | 0.008525 | 16.18 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.76 | 0.330190 | 0.281000 | 1.62 | 0.880507 | 0.500000 | 0.001154 | 0.001495 | 2.06 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.20 | 0.198969 | 0.169000 | 0.202849 | 0.530585 | 0.500000 | 0.001915 | 0.000146 | 0.202849 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.953133 | 0.161473 | 0.137000 | 0.130579 | 0.430594 | 0.500000 | 0.002360 | 0.000109 | 0.150847 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.22 | 0.196355 | 0.167000 | 0.203121 | 0.523613 | 0.500000 | 0.001940 | 0.000202 | 0.278614 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.27 | 0.121277 | 0.103000 | 0.130711 | 0.323405 | 0.500000 | 0.003142 | 0.000073 | 0.130711 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.71 | 0.204002 | 0.173000 | 2.03 | 0.544005 | 0.500000 | 0.001868 | 0.003505 | 4.85 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.89 | 0.415048 | 0.500000 | 0.002448 | 0.002333 | 3.23 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 11.72 | 0.203846 | 0.173000 | 2.03 | 0.543589 | 0.500000 | 0.001869 | 0.003533 | 4.89 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.94 | 0.140651 | 0.120000 | 1.31 | 0.375069 | 0.500000 | 0.002709 | 0.002136 | 2.95 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.32 | 0.181386 | 0.154000 | 0.202763 | 0.483695 | 0.500000 | 0.002100 | 0.000434 | 0.601378 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.02 | 0.150956 | 0.128000 | 0.130500 | 0.402550 | 0.500000 | 0.002524 | 0.000286 | 0.396490 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.32 | 0.181528 | 0.154000 | 0.202609 | 0.484074 | 0.500000 | 0.002099 | 0.000437 | 0.604431 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.19 | 0.129646 | 0.110000 | 0.130583 | 0.345723 | 0.500000 | 0.002939 | 0.000272 | 0.376135 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 15860.32 | 0.000350 | 276.05 |
CORE_MID VAV BOX REHEAT COIL | 385836.26 | 0.008525 | 7474.23 |
CORE_TOP VAV BOX REHEAT COIL | 67664.03 | 0.001495 | 1413.05 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6612.52 | 0.000146 | 137.84 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4950.20 | 0.000109 | 103.39 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9133.78 | 0.000202 | 190.71 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3285.42 | 0.000073 | 64.28 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 158651.01 | 0.003505 | 3310.50 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 105586.54 | 0.002333 | 2203.16 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 159920.28 | 0.003533 | 3336.96 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 96670.32 | 0.002136 | 2017.26 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19661.90 | 0.000434 | 410.21 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12962.46 | 0.000286 | 270.43 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19761.49 | 0.000437 | 412.29 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12298.41 | 0.000272 | 256.59 |
CAV_BAS_HEATC | 246829.43 | 0.005453 | 4641.69 |
VAV_BOT WITH REHEAT_HEATC | 20353.77 | 0.000450 | 312.90 |
VAV_MID WITH REHEAT_HEATC | 95609.41 | 0.002112 | 1486.31 |
VAV_TOP WITH REHEAT_HEATC | 9061.27 | 0.000200 | 141.13 |
DATACENTER_EXTRAWATERHEATC | 1024418.06 | 0.022633 | 19082.50 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.42 | 5.42 | 5.42 | 5.42 | 5.42 | 5.42 | 1.00 | 1.00 | 5.42 |
VAV_BOT WITH REHEAT | 5.31 | 2.28 | 10.62 | 2.28 | 9.80 | 9.80 | 0.300000 | 0.232883 | 9.80 |
VAV_MID WITH REHEAT | 50.72 | 22.85 | 101.44 | 26.70 | 93.34 | 93.34 | 0.300000 | 0.286034 | 93.34 |
VAV_TOP WITH REHEAT | 5.30 | 2.29 | 10.60 | 4.04 | 10.51 | 10.51 | 0.300000 | 0.384531 | 10.51 |
AIRLOOP DATACENTER BASEMENT | 21.77 | 21.77 | 21.77 | 21.77 | 21.77 | 21.77 | 1.00 | 1.00 | 21.77 |
AIRLOOP DATACENTER BOT | 0.478997 | 0.478997 | 0.478997 | 0.478997 | 0.478997 | 0.478997 | 1.00 | 1.00 | 0.478997 |
AIRLOOP DATACENTER MID | 4.57 | 4.57 | 4.57 | 4.57 | 4.57 | 4.57 | 1.00 | 1.00 | 4.57 |
AIRLOOP DATACENTER TOP | 0.458475 | 0.458475 | 0.458475 | 0.458475 | 0.458475 | 0.458475 | 1.00 | 1.00 | 0.458475 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.42 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.80 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 93.34 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.51 | |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.77 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.478997 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.57 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.458475 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 120910.52 | 0.003458 | 5.42 | 0.007894 | 27.81 | 6.67 | 11.38 | 0.007894 |
VAV_BOT WITH REHEAT_COOLC | 217490.26 | 0.006220 | 9.80 | 0.007708 | 27.78 | 6.67 | 11.38 | 0.007708 |
VAV_MID WITH REHEAT_COOLC | 2124121.71 | 0.060750 | 93.34 | 0.007766 | 28.12 | 6.67 | 11.38 | 0.007766 |
VAV_TOP WITH REHEAT_COOLC | 227290.20 | 0.006500 | 10.51 | 0.007661 | 27.45 | 6.67 | 11.38 | 0.007661 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.42 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.003458 | 0.000138 |
CAV_BAS_HEATC_CONTROLLER | 0.005453 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006220 | 0.000077 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000450 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.060750 | 0.000008 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002112 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006500 | 0.000073 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000200 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022633 | 0.000021 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.80 |
VAV_MID WITH REHEAT FAN | 93.34 |
VAV_TOP WITH REHEAT FAN | 10.51 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.77 | 446285.30 | 278110.91 | 0.010929 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.478997 | 9599.66 | 6036.62 | 0.000235 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.57 | 91726.35 | 57655.25 | 0.002246 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.458475 | 9338.07 | 5829.27 | 0.000229 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.77 | 21.77 | 21.77 | 21.77 | 446285.30 | 446285.30 | 13449.85 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.478997 | 0.478997 | 0.478997 | 0.478997 | 9599.66 | 9599.66 | 621.33 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.57 | 4.57 | 4.57 | 4.57 | 91726.35 | 91726.35 | 6213.27 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.458475 | 0.458475 | 0.458475 | 0.458475 | 9338.07 | 9338.07 | 621.33 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.77 |
DATACENTER BOT SUPPLY FAN | 0.478997 |
DATACENTER MID SUPPLY FAN | 4.57 |
DATACENTER TOP SUPPLY FAN | 0.458475 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.77 | 446285.30 | 0.010929 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.478997 | 9599.66 | 0.000235 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.57 | 91726.35 | 0.002246 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.458475 | 9338.07 | 0.000229 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 13449.85 | |
DATACENTER_EXTRAELECHEATC | 446285.30 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 621.33 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 6213.27 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 621.33 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000048 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.076928 | 14569.73 |
HEATSYS1 PUMP | 0.054685 | 13832.96 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.076928 | 9.23 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.054685 | 6.56 |
COOLSYS1_SUPPLY | 0.076928 | 9.23 |
SINGLE WATER PLANT LOOP | 0.013640 | 1.64 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.076928 | 0.076928 | 322906.69 | 8.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 56.21 |
COOLSYS1 CHILLER1 PUMP | 0.038464 | 2428.29 |
COOLSYS1 CHILLER2 PUMP | 0.038464 | 2428.29 |
PLANT CIRC PUMP | 0.013640 | 3444.35 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2475126.87 | 1237563.44 | 0.054685 |
DUMMY BOILER | 561836.83 | 93894.07 | 0.013640 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.076928 | 0.038858 | 1362030.66 | 1368491.13 | 0.067722 |
COOLSYS1 CHILLER2 | 0.076928 | 0.038858 | 1362030.66 | 1368491.13 | 0.067722 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013640 | 139666.47 | 57964.60 | 69833.23 | 7004.20 | 21283.03 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.135443 | 16.25 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.135443 | 28378.57 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 53.70 | 1298966.49 | 10.74 | 162370.81 |
TOWERWATERSYS COOLTOWER 2 | 53.70 | 1298966.49 | 10.74 | 162370.81 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.056274 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.889 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.731 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 6.889 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.188 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 6.889 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.188 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 6.889 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.188 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 6.889 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.312 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 19147.199 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19147.199 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 17195.531 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17195.531 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 17195.531 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17195.531 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 17195.531 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17195.531 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2159.071 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.071 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2159.118 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.118 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2159.071 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.071 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2159.118 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.118 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2159.071 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.071 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2159.118 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.118 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 5398.691 | 6.889 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5398.691 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 249.397 | 6.889 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 249.397 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 249.397 | 6.889 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 249.397 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 249.397 | 6.889 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 249.397 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
61 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
62 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
63 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
64 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
65 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
66 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
67 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
68 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
69 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
70 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
71 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
72 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
73 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
74 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
75 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
76 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
77 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
78 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
79 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
80 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
81 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
82 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
83 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
84 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
85 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
86 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
87 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
88 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
89 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
90 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
91 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
92 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
93 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
94 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
95 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
96 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
97 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
98 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
99 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
100 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
101 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
102 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
103 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
104 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
105 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
106 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
107 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5_SHGC_0.23 | 29 | 1 | VerySmooth | 2.843 | 0.232 | 0.142 | 0.254 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.14129 | 0.63099 | 0.63099 | 0.25300 | 0.16079 | 0.23715 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 73199.77334 | 73199.77334 | 5.42072 | 5.42072 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30000 | 6.07234E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 80810.79526 | 80810.79526 | 5.98506 | 5.98506 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 772318.52624 | 772318.52624 | 57.18841 | 57.18841 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 226990.86178 | 226990.86178 | 9.80632 | 10.77757 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 77790.74714 | 77790.74714 | 5.76045 | 5.76045 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 47416.57713 | 47416.57713 | 2.06296 | 2.06296 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 16059.54839 | 16059.54839 | 1.20029 | 1.20029 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.70900 | 9.11022E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 4621.96931 | 4621.96931 | 0.20069 | 0.20069 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12752.69363 | 12752.69363 | 0.95313 | 0.95313 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:00:00 | 38.31400 | 9.11022E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3469.89377 | 3469.89377 | 0.15085 | 0.15085 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 16273.72252 | 16273.72252 | 1.21630 | 1.21630 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 42.00000 | 9.11023E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6399.56412 | 6399.56412 | 0.27861 | 0.27861 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16979.49725 | 16979.49725 | 1.26904 | 1.26904 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.11023E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2002.89020 | 2002.89020 | 8.65315E-002 | 8.72074E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 156633.06725 | 156633.06725 | 11.70679 | 11.70679 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.11023E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 111053.47111 | 111053.47111 | 4.84988 | 4.84988 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 132303.19146 | 132303.19146 | 9.88833 | 9.88833 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:10:00 | 38.55650 | 9.11022E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 73906.10353 | 73906.10353 | 3.22802 | 3.22802 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 156756.31211 | 156756.31211 | 11.71600 | 11.71600 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.11022E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 111940.78142 | 111940.78142 | 4.88879 | 4.88879 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 146405.92316 | 146405.92316 | 10.94236 | 10.94236 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | 40.90067 | 9.11023E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 67672.17570 | 67672.17570 | 2.95476 | 2.95476 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 17616.29358 | 17616.29358 | 1.31665 | 1.31665 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.11023E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 13759.70642 | 13759.70642 | 0.60138 | 0.60138 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 13641.07894 | 13641.07894 | 1.01953 | 1.01953 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 38.79900 | 9.11022E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9071.12654 | 9071.12654 | 0.39649 | 0.39649 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 17602.90437 | 17602.90437 | 1.31564 | 1.31564 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 41.80600 | 9.11023E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 13829.33220 | 13829.33220 | 0.60443 | 0.60443 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 15883.33404 | 15883.33404 | 1.18712 | 1.18712 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | 40.90067 | 9.11023E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8606.87895 | 8606.87895 | 0.37614 | 0.37614 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8126.32829 | 8126.32829 | 0.47900 | 0.47900 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.11022E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30000 | 6.07234E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 77580.88950 | 77580.88950 | 4.57291 | 4.57291 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.11022E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30000 | 6.07234E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7778.18142 | 7778.18142 | 0.45848 | 0.45848 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:10:00 | 32.33233 | 9.11022E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30000 | 6.07234E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369275.23426 | 369275.23426 | 21.76648 | 21.76648 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 06:10:00 | 32.60717 | 9.11022E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30000 | 6.07234E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 87954.73 | 5.42072 | 5.42072 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 47701.75 | 1.20008 | 1.20008 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 170662.05 | 9.80417 | 9.80417 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 13762.54 | 1.79511 | 1.79511 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1603603.14 | 93.34221 | 93.34221 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 154186.93 | 26.69903 | 26.69903 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 181212.17 | 10.50994 | 10.50994 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 15206.19 | 4.04139 | 4.04139 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 369946.01 | 21.76648 | 21.76648 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 13449.85 | 0.33837 | 0.33837 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8121.49 | 0.47900 | 0.47900 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 621.33 | 1.56314E-002 | 1.56314E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 77579.56 | 4.57291 | 4.57291 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6213.27 | 0.15631 | 0.15631 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7860.27 | 0.45848 | 0.45848 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 621.33 | 1.56314E-002 | 1.56314E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.42072 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.98506 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31780 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61597 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84746 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19887E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.50414E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61597 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15860.31927 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.50414E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 276.05294 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 57.18841 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33259 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18432 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88691 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14555E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.52458E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.18432 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 385836.25828 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.52458E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7474.22622 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.76045 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33019 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28100 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61869 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88051 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15388E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49495E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.06296 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 67664.03176 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49495E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1413.05156 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20029 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19897 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16900 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20285 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53058 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.91487E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.46096E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20285 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6612.52185 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.46096E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 137.83530 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95313 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16147 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13700 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13058 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43059 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35953E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09369E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15085 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4950.19814 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09369E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 103.39242 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.21630 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19635 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.16700 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20312 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52361 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94036E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.01800E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27861 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9133.77847 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01800E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 190.71453 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.26904 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12128 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10300 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13071 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32341 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14157E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.25873E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13071 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3285.41961 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.25873E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 64.27604 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.70679 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20400 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17300 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02527 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54400 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.86763E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.50520E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.84988 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 158651.01134 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.50520E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3310.49676 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.88833 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41505 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44791E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.33281E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.22802 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 105586.53978 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.33281E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2203.16480 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.71600 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20385 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17300 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02687 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54359 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.86906E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.53324E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.88879 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 159920.27995 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.53324E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3336.95901 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.94236 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14065 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12000 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31308 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37507 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.70884E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.13581E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.95476 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 96670.32019 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13581E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2017.25628 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31665 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18139 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15400 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20276 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48370 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10050E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.34406E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.60138 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19661.89650 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.34406E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 410.20890 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01953 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15096 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12800 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13050 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40255 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52391E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.86390E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39649 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12962.46220 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.86390E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.43337 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31564 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18153 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15400 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20261 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48407 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09885E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.36606E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.60443 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19761.49204 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.36606E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 412.28532 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18712 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12965 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11000 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13058 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34572 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93877E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.71718E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37614 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12298.41232 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.71718E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 256.58827 |
209 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47900 |
210 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.57291 |
211 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45848 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.76648 |
213 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.42072 |
214 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.42072 |
215 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.42072 |
216 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.42072 |
217 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.42072 |
218 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.42072 |
219 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
220 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.31191 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28323 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.62381 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28323 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.80417 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.80417 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.23288 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 50.72094 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.85481 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 101.44189 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.69903 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 93.34221 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 93.34221 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28603 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.29970 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28514 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.59939 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.04139 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.50994 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.50994 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.38453 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.76648 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.76648 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.76648 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.76648 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.76648 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.76648 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47900 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47900 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47900 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47900 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47900 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.47900 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.57291 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.57291 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.57291 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.57291 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.57291 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.57291 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45848 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45848 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45848 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45848 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45848 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45848 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.42072 |
278 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.80417 |
279 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 93.34221 |
280 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.50994 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.76648 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.47900 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.57291 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45848 |
285 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.42072 |
286 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
287 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 120910.52488 |
288 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 3.45803E-003 |
289 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.42072 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 7.89429E-003 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 27.80753 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.38305 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 7.89429E-003 |
295 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 246829.43254 |
296 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.45339E-003 |
297 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 4641.69285 |
298 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.42072 |
299 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.45803E-003 |
300 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.37706E-004 |
301 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.45339E-003 |
302 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.80417 |
303 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 217490.26173 |
304 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 6.22019E-003 |
305 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 9.80417 |
306 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 7.70784E-003 |
307 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 27.78374 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.38257 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 7.70784E-003 |
311 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 20353.76593 |
312 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 4.49692E-004 |
313 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 312.90107 |
314 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.80417 |
315 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.22019E-003 |
316 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.65556E-005 |
317 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.49692E-004 |
318 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 93.34221 |
319 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 2124121.71159 |
320 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 6.07496E-002 |
321 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 93.34221 |
322 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 7.76625E-003 |
323 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 28.11625 |
324 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
325 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.38272 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 7.76625E-003 |
327 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 95609.40520 |
328 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.11237E-003 |
329 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 1486.30899 |
330 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 93.34221 |
331 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.07496E-002 |
332 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.83858E-006 |
333 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.11237E-003 |
334 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.50994 |
335 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 227290.19534 |
336 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 6.50047E-003 |
337 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 10.50994 |
338 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 7.66080E-003 |
339 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 27.44530 |
340 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
341 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.38245 |
342 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 7.66080E-003 |
343 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 9061.26655 |
344 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.00198E-004 |
345 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 141.13014 |
346 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.50994 |
347 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.50047E-003 |
348 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.32548E-005 |
349 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.00198E-004 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.76648 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.76648 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 446285.30307 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 278110.91373 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.09295E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.76648 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.76648 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.76648 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.76648 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 446285.30307 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 446285.30307 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 13449.85154 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.76648 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.76648 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 446285.30307 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.09295E-002 |
368 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 13449.85154 |
369 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 4.75275E-005 |
370 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 446285.30307 |
374 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
375 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1024418.06115 |
376 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.26333E-002 |
377 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19082.50170 |
378 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.26333E-002 |
379 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.10394E-005 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47900 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.47900 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9599.65750 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6036.61805 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.35095E-004 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47900 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47900 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47900 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47900 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9599.65750 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9599.65750 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.32742 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47900 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.47900 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9599.65750 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.35095E-004 |
397 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 621.32742 |
398 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.57291 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.57291 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 91726.34945 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 57655.24582 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.24637E-003 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.57291 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.57291 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.57291 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.57291 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 91726.34945 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 91726.34945 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6213.27422 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
411 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.57291 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.57291 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 91726.34945 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.24637E-003 |
415 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 6213.27422 |
416 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45848 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.45848 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 9338.06962 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 5829.27127 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.28689E-004 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45848 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45848 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45848 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45848 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9338.06962 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9338.06962 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.32742 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
429 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45848 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.45848 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 9338.06962 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.28689E-004 |
433 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 621.32742 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.69283E-002 |
435 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 14569.72586 |
436 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.69283E-002 |
437 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.23140 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.69283E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.69283E-002 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 322906.68590 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
442 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
443 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
444 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
445 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 56.20535 |
446 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
447 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.46849E-002 |
448 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 6.56219 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.46849E-002 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 13832.96207 |
451 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2475126.87307 |
452 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1237563.43500 |
453 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.46849E-002 |
454 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.69283E-002 |
455 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.23140 |
456 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.84642E-002 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 2428.28764 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.84642E-002 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 2428.28764 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.69283E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.88585E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1362030.66387 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1368491.13000 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.77216E-002 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.69283E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.88585E-002 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1362030.66387 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1368491.13000 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.77216E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.36397E-002 |
471 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.63676 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.36397E-002 |
473 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3444.35047 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.36397E-002 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 57964.59643 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21283.03275 |
480 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 561836.83038 |
481 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
482 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.36397E-002 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13544 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.25317 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13544 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 28378.56693 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 53.69973 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1298966.48933 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.73995 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 162370.81117 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 53.69973 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1298966.48933 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.73995 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 162370.81117 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 5.62740E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 5.62740E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15047.18 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 366257.03 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 64201.74 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6274.20 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4696.90 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8666.42 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3118.31 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 150533.34 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 100184.02 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 151737.67 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 91723.99 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18655.87 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12299.22 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18750.37 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11669.15 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 201616.82 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 17807.71 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 87106.57 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 8308.95 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 824094.05 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 144787.27 | 98656.11 | 46131.17 | 0.68 | 27773.43 | 281.69 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 271234.82 | 182520.11 | 88714.72 | 0.67 | 62270.88 | 631.59 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2586836.60 | 1739249.57 | 847587.03 | 0.67 | 558095.32 | 5660.51 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 289724.28 | 195253.09 | 94471.19 | 0.67 | 70652.35 | 716.60 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.34 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.34 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.23 | N/A | 2.843 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 24 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.5606892502 | 0.4969499163 | Pass | Pass | 1.6035678521 | 3.0806910484 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.7466263502E-003 | 5.0210977412E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.2135587710E-003 | 5.4161556312E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.2563347810E-002 | 5.2917285951E-002 | Pass | Pass | 0.1412233839 | 0.3474942086 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.5270196328E-002 | 1.6719714745E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.3601706237E-002 | 3.6041885709E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.8215780663E-002 | 4.3989412831E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.9580405115E-002 | 3.3560058329E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.8344565854E-002 | 1.9097831361E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.7660998535E-002 | 3.5681165206E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.6493530977E-002 | 4.8830358085E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.3136888852E-002 | 3.5032021108E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.0069558239E-002 | 0.1233336724 | Pass | Pass | 0.4158574159 | 1.3193852412 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.9460740385E-002 | 8.4642867858E-002 | Pass | Pass | 0.3635220815 | 1.1552804680 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.0463134073E-002 | 6.0628994567E-002 | Pass | Pass | 0.6184511600 | 4.0937932659 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.1539860394E-002 | 5.0069797604E-002 | Pass | Pass | 0.2851873950 | 0.9910266573 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.8982634944E-003 | 4.7543110016E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.0875360746E-003 | 5.0710166468E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.9911821391E-002 | 5.0959181263E-002 | Pass | Pass | 0.1472976299 | 0.3516968906 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.7188128292E-014 | 2.3078664641E-014 | Pass | Pass | 4.1938740750E-003 | 2.3179320283E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1538079134E-011 | 3.6633494325E-011 | Pass | Pass | 0.1719102550 | 0.8072151047 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.6548507970E-002 | 1.8132625425E-002 | Pass | Pass | 1.1798105029E-002 | 9.0418880729E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.8824318790E-004 | 2.4574777186E-004 | Pass | Pass | 6.2457186071E-005 | 3.8445789881E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5_SHGC_0.23 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5_SHGC_0.23 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5_SHGC_0.23 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.5_SHGC_0.23 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.5_SHGC_0.23 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5_SHGC_0.23 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5_SHGC_0.23 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.5_SHGC_0.23 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5_SHGC_0.23 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5_SHGC_0.23 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5_SHGC_0.23 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.5_SHGC_0.23 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.5_SHGC_0.23 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5_SHGC_0.23 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5_SHGC_0.23 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.5_SHGC_0.23 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.843 | 0.232 | 0.254 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5_SHGC_0.23 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.843 | 0.232 | 0.254 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5_SHGC_0.23 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.843 | 0.232 | 0.254 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5_SHGC_0.23 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.843 | 0.232 | 0.254 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5_SHGC_0.23 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.843 | 0.232 | 0.254 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5_SHGC_0.23 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.843 | 0.232 | 0.254 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5_SHGC_0.23 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.843 | 0.232 | 0.254 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5_SHGC_0.23 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.843 | 0.232 | 0.254 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5_SHGC_0.23 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.843 | 0.232 | 0.254 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 4635.80 | 2.843 | 0.232 | 0.254 | ||||||||||||
North Total or Average | 1390.74 | 2.843 | 0.232 | 0.254 | ||||||||||||
Non-North Total or Average | 3245.06 | 2.843 | 0.232 | 0.254 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 6.8889 | 2779.43 | 19147.20 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.71 | 0.0000 | Y | 175.08 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 6.8889 | 2496.12 | 17195.53 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.71 | 0.0000 | Y | 157.23 |
CORE_MID_LIGHTS | CORE_MID | 6.8889 | 24961.20 | 171955.31 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.71 | 0.0000 | Y | 1572.35 |
CORE_TOP_LIGHTS | CORE_TOP | 6.8889 | 2496.12 | 17195.53 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.71 | 0.0000 | Y | 157.23 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 6.8889 | 313.41 | 2159.07 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.65 | 0.0000 | Y | 11.20 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 6.8889 | 201.98 | 1391.39 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.52 | 0.0000 | Y | 7.19 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 6.8889 | 313.42 | 2159.12 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.35 | 0.0000 | Y | 11.08 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 6.8889 | 201.98 | 1391.39 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.50 | 0.0000 | Y | 7.18 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 6.8889 | 3134.13 | 21590.71 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.60 | 0.0000 | Y | 111.85 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 6.8889 | 2019.75 | 13913.87 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.48 | 0.0000 | Y | 71.79 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 6.8889 | 3134.20 | 21591.18 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.32 | 0.0000 | Y | 110.73 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 6.8889 | 2019.75 | 13913.87 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.46 | 0.0000 | Y | 71.73 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 6.8889 | 313.41 | 2159.07 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.60 | 0.0000 | Y | 11.18 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 6.8889 | 201.98 | 1391.39 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.48 | 0.0000 | Y | 7.18 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 6.8889 | 313.42 | 2159.12 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.32 | 0.0000 | Y | 11.07 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 6.8889 | 201.98 | 1391.39 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.46 | 0.0000 | Y | 7.17 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 6.8889 | 783.68 | 5398.69 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 50.68 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 6.8889 | 36.20 | 249.40 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 2.34 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 6.8889 | 362.03 | 2493.97 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 23.41 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 6.8889 | 36.20 | 249.40 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 2.34 |
Interior Lighting Total | 6.8889 | 46320.38 | 319096.58 | 814.36 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.07 | 832.75 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.07 | 299.03 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.12 | 832.77 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.12 | 299.04 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.07 | 832.75 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.07 | 299.03 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.12 | 832.77 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.12 | 299.04 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.07 | 832.75 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.07 | 299.03 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.12 | 832.77 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.12 | 299.04 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12979.20 | AstronomicalClock | - | 41.75 | 41.75 | 101.73 | |
EXTERIOR_LIGHTS_B | 968.00 | AstronomicalClock | - | 83.75 | 62.75 | 11.40 | |
EXTERIOR_LIGHTS_C | 26027.00 | AstronomicalClock | - | 83.75 | 46.80 | 228.64 | |
Exterior Lighting Total | 39974.20 | 341.78 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2681527.83 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1237563.44 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1368491.13 | 6.28 | 6.84 | 23.34 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1368491.13 | 6.28 | 6.84 | 23.34 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1298966.49 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1298966.49 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 120910.52 | 144787.27 | 98656.11 | 46131.17 | 0.68 | - | 27773.43 | 281.69 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 217490.26 | 271234.82 | 182520.11 | 88714.72 | 0.67 | - | 62270.88 | 631.59 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 2124121.71 | 2586836.60 | 1739249.57 | 847587.03 | 0.67 | - | 558095.32 | 5660.51 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 227290.20 | 289724.28 | 195253.09 | 94471.19 | 0.67 | - | 70652.35 | 716.60 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 446285.30 | 278110.91 | 168174.39 | 0.62 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9599.66 | 6036.62 | 3563.04 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 91726.35 | 57655.25 | 34071.10 | 0.63 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9338.07 | 5829.27 | 3508.80 | 0.62 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 15860.32 | 15047.18 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 385836.26 | 366257.03 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 67664.03 | 64201.74 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 6612.52 | 6274.20 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4950.20 | 4696.90 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9133.78 | 8666.42 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3285.42 | 3118.31 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 158651.01 | 150533.34 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 105586.54 | 100184.02 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 159920.28 | 151737.67 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 96670.32 | 91723.99 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19661.90 | 18655.87 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12962.46 | 12299.22 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19761.49 | 18750.37 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12298.41 | 11669.15 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 246829.43 | 201616.82 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 20353.77 | 17807.71 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 95609.41 | 87106.57 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 9061.27 | 8308.95 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 446285.30 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9599.66 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 91726.35 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 9338.07 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 13449.85 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1024418.06 | 824094.05 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 621.33 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 6213.27 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 621.33 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.42 | 9191.66 | 1695.65 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.80 | 21186.29 | 2160.95 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 93.34 | 201707.54 | 2160.95 | 1.00 | 1.08 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.51 | 22590.75 | 2149.46 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.77 | 35898.30 | 1649.25 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 536.53 | 1120.11 | 1.00 | 1.63 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.57 | 5122.15 | 1120.11 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 513.54 | 1120.11 | 1.00 | 1.65 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 134283.83 | 0.076928 | 14569.73 | 189393.57 | 0.91 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.054685 | 13832.96 | 252957.60 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.038464 | 2428.29 | 63131.19 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.038464 | 2428.29 | 63131.19 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013640 | 3444.35 | 252524.76 | 0.91 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.135443 | 28378.57 | 209523.88 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 73199.77 | 73199.77 | 26.34 | 5.421 | 5.421 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00748 | 34.82 | 0.00911 | 1.200 | 0.00 |
CORE_BOTTOM | 80810.80 | 80810.80 | 32.37 | 5.985 | 5.985 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 34.82 | 0.00911 | 1.078 | 0.00 |
CORE_MID | 772318.53 | 772318.53 | 309.41 | 57.188 | 57.188 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 34.82 | 0.00911 | 10.778 | 0.00 |
CORE_TOP | 77790.75 | 77790.75 | 31.16 | 5.760 | 5.760 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 34.82 | 0.00911 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 16059.55 | 16059.55 | 51.24 | 1.200 | 1.200 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 24.00 | 24.00 | 0.00724 | 41.71 | 0.00911 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12752.69 | 12752.69 | 63.14 | 0.953 | 0.953 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:00:00 | 24.00 | 24.00 | 0.00720 | 38.31 | 0.00911 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16273.72 | 16273.72 | 51.92 | 1.216 | 1.216 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 24.00 | 24.00 | 0.00724 | 42.00 | 0.00911 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16979.50 | 16979.50 | 84.07 | 1.269 | 1.269 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00715 | 41.03 | 0.00911 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 156633.07 | 156633.07 | 499.77 | 11.707 | 11.707 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 24.00 | 24.00 | 0.00726 | 41.61 | 0.00911 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 132303.19 | 132303.19 | 655.05 | 9.888 | 9.888 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:10:00 | 24.00 | 24.00 | 0.00720 | 38.56 | 0.00911 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 156756.31 | 156756.31 | 500.15 | 11.716 | 11.716 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 24.00 | 24.00 | 0.00726 | 41.90 | 0.00911 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 146405.92 | 146405.92 | 724.87 | 10.942 | 10.942 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | 24.00 | 24.00 | 0.00718 | 40.90 | 0.00911 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17616.29 | 17616.29 | 56.21 | 1.317 | 1.317 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 24.00 | 24.00 | 0.00723 | 41.61 | 0.00911 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13641.08 | 13641.08 | 67.54 | 1.020 | 1.020 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 24.00 | 24.00 | 0.00720 | 38.80 | 0.00911 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 17602.90 | 17602.90 | 56.16 | 1.316 | 1.316 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 24.00 | 24.00 | 0.00723 | 41.81 | 0.00911 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15883.33 | 15883.33 | 78.64 | 1.187 | 1.187 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | 24.00 | 24.00 | 0.00717 | 40.90 | 0.00911 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8126.33 | 8126.33 | 224.47 | 0.479 | 0.479 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00911 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 77580.89 | 77580.89 | 2142.96 | 4.573 | 4.573 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00911 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7778.18 | 7778.18 | 214.85 | 0.458 | 0.458 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:10:00 | 27.00 | 27.00 | 0.00700 | 32.33 | 0.00911 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369275.23 | 369275.23 | 471.21 | 21.766 | 21.766 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 06:10:00 | 27.00 | 27.00 | 0.00700 | 32.61 | 0.00911 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 1.078 | 0.00 | |
CORE_MID | 226990.86 | 226990.86 | 90.94 | 9.806 | 10.778 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 10.778 | 0.00 |
CORE_TOP | 47416.58 | 47416.58 | 19.00 | 2.063 | 2.063 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 4621.97 | 4621.97 | 14.75 | 0.201 | 0.201 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3469.89 | 3469.89 | 17.18 | 0.151 | 0.151 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6399.56 | 6399.56 | 20.42 | 0.279 | 0.279 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2002.89 | 2002.89 | 9.92 | 0.087 | 0.087 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 111053.47 | 111053.47 | 354.34 | 4.850 | 4.850 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 73906.10 | 73906.10 | 365.92 | 3.228 | 3.228 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 111940.78 | 111940.78 | 357.16 | 4.889 | 4.889 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 67672.18 | 67672.18 | 335.05 | 2.955 | 2.955 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13759.71 | 13759.71 | 43.90 | 0.601 | 0.601 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9071.13 | 9071.13 | 44.91 | 0.396 | 0.396 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13829.33 | 13829.33 | 44.12 | 0.604 | 0.604 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8606.88 | 8606.88 | 42.61 | 0.376 | 0.376 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | 6.30 | 0.00607 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 6.30 | 0.00607 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 6.30 | 0.00607 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.42 | 5.42 | 1.20 | 1.20 | 5.4207 | 5.4207 | 5.4207 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 9.80 | 9.80 | 1.80 | 1.80 | 9.8042 | 2.2832 | 9.8042 | 0.2329 | 0.3000 |
VAV_MID WITH REHEAT | 93.34 | 93.34 | 26.70 | 26.70 | 93.3422 | 26.6990 | 93.3422 | 0.2860 | 0.3000 |
VAV_TOP WITH REHEAT | 10.51 | 10.51 | 4.04 | 4.04 | 10.5099 | 4.0414 | 10.5099 | 0.3845 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.77 | 21.77 | 0.34 | 0.34 | 21.7665 | 21.7665 | 21.7665 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.48 | 0.48 | 0.02 | 0.02 | 0.4790 | 0.4790 | 0.4790 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.57 | 4.57 | 0.16 | 0.16 | 4.5729 | 4.5729 | 4.5729 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4585 | 0.4585 | 0.4585 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 15860.319 | 15860.319 | 1.615965 | 0.00035041 | 276.053 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 15047.18 | 15860.32 | 1.615965 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 15924.12 | 15924.12 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 385836.258 | 385836.258 | 16.184321 | 0.00852458 | 7474.226 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 366257.03 | 385836.26 | 16.184321 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 226990.86 | 0.00 | 387667.83 | 387667.83 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 67664.032 | 67664.032 | 2.062959 | 0.00149495 | 1413.052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 64201.74 | 67664.03 | 2.062959 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 47416.58 | 0.00 | 67972.99 | 67972.99 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6612.522 | 6612.522 | 0.202849 | 0.00014610 | 137.835 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6274.20 | 6612.52 | 0.202849 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00791064 | 49.8570 | 4621.97 | 0.00 | 6642.71 | 6642.71 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4950.198 | 4950.198 | 0.150847 | 0.00010937 | 103.392 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4696.90 | 4950.20 | 0.150847 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00792563 | 49.9503 | 3469.89 | 0.00 | 4972.80 | 4972.80 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9133.778 | 9133.778 | 0.278614 | 0.00020180 | 190.715 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8666.42 | 9133.78 | 0.278614 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794449 | 50.0675 | 6399.56 | 0.00 | 9175.48 | 9175.48 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3285.420 | 3285.420 | 0.130711 | 0.00007259 | 64.276 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3118.31 | 3285.42 | 0.130711 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00785323 | 49.4996 | 2002.89 | 0.00 | 3300.73 | 3300.73 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 158651.011 | 158651.011 | 4.849878 | 0.00350520 | 3310.497 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 150533.34 | 158651.01 | 4.849878 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797409 | 50.2517 | 111053.47 | 0.00 | 159375.33 | 159375.33 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 105586.540 | 105586.540 | 3.228018 | 0.00233281 | 2203.165 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 100184.02 | 105586.54 | 3.228018 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797577 | 50.2621 | 73906.10 | 0.00 | 106068.59 | 106068.59 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 159920.280 | 159920.280 | 4.888791 | 0.00353324 | 3336.959 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 151737.67 | 159920.28 | 4.888791 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00797473 | 50.2556 | 111940.78 | 0.00 | 160650.39 | 160650.39 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 96670.320 | 96670.320 | 2.954765 | 0.00213581 | 2017.256 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 91723.99 | 96670.32 | 2.954765 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796743 | 50.2103 | 67672.18 | 0.00 | 97111.67 | 97111.67 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19661.897 | 19661.897 | 0.601378 | 0.00043441 | 410.209 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18655.87 | 19661.90 | 0.601378 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798652 | 50.3289 | 13759.71 | 0.00 | 19751.66 | 19751.66 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12962.462 | 12962.462 | 0.396490 | 0.00028639 | 270.433 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12299.22 | 12962.46 | 0.396490 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798709 | 50.3324 | 9071.13 | 0.00 | 13021.64 | 13021.64 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19761.492 | 19761.492 | 0.604431 | 0.00043661 | 412.285 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18750.37 | 19761.49 | 0.604431 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798676 | 50.3303 | 13829.33 | 0.00 | 19851.71 | 19851.71 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12298.412 | 12298.412 | 0.376135 | 0.00027172 | 256.588 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11669.15 | 12298.41 | 0.376135 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00798341 | 50.3096 | 8606.88 | 0.00 | 12354.56 | 12354.56 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 120910.525 | -999.000 | 5.420718 | 0.00345803 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 120910.52 | 120910.52 | 5.420718 | 27.81 | 16.92 | 0.00789429 | 11.38 | 9.72 | 0.00789429 | 39.77 | 0.00911022 | 21.57 | 22.1388 | 24.00 | 0.00747726 | 39.3022 | 66480.81 | 0.00 | 118073.58 | 114498.39 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 246829.433 | 246829.433 | 5.420718 | 0.00545339 | 4641.693 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 201616.82 | 218651.68 | 5.420718 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 22.1388 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 212797.80 | 212797.80 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 217490.262 | -999.000 | 9.804170 | 0.00622019 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 217490.26 | 217490.26 | 9.804170 | 27.78 | 16.75 | 0.00770784 | 11.38 | 10.33 | 0.00770784 | 42.00 | 0.00911023 | 22.20 | 20.7096 | 24.00 | 0.00730819 | 38.4234 | 129201.54 | 0.00 | 217891.09 | 211496.78 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 20353.766 | 20353.766 | 2.941251 | 0.00044969 | 312.901 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17807.71 | 20353.77 | 2.941251 | 6.30 | 6.30 | 0.00607234 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 69.0318 | 21.00 | 0.00796802 | 50.2137 | 16494.32 | 0.00 | 18837.53 | 18837.53 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2124121.712 | -999.000 | 93.342209 | 0.06074961 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 2124121.71 | 2124121.69 | 93.342209 | 28.12 | 16.92 | 0.00776625 | 11.38 | 10.33 | 0.00776625 | 42.00 | 0.00911023 | 22.20 | 21.7522 | 24.00 | 0.00732607 | 38.5164 | 1187665.15 | 0.00 | 2111815.26 | 2043236.19 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 95609.405 | 95609.405 | 28.002663 | 0.00211237 | 1486.309 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 87106.57 | 95609.41 | 28.002663 | 6.42 | 6.38 | 0.00608957 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 72.5074 | 21.00 | 0.00798413 | 50.3140 | 297173.82 | 0.00 | 92155.30 | 92155.30 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 227290.195 | -999.000 | 10.509941 | 0.00650047 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 227290.20 | 227290.20 | 10.509941 | 27.45 | 16.60 | 0.00766080 | 11.38 | 10.33 | 0.00766080 | 41.81 | 0.00911023 | 22.15 | 19.3189 | 24.00 | 0.00731361 | 38.4517 | 140358.65 | 0.00 | 229218.78 | 223100.46 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 9061.267 | 9061.267 | 3.152982 | 0.00020020 | 141.130 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8308.95 | 9061.27 | 3.152982 | 6.30 | 6.30 | 0.00607234 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 64.3962 | 21.00 | 0.00799320 | 50.3703 | 35637.02 | 0.00 | 8789.93 | 8789.93 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 446285.303 | 278110.914 | 21.766480 | 0.01092950 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 06:10:00 | 497694.91 | 495682.35 | -999.0 | 28.66 | 16.49 | 0.00703286 | 12.80 | 10.33 | 0.00700000 | 42.00 | 0.00911023 | 22.20 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 368665.87 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9599.657 | 6036.618 | 0.478997 | 0.00023509 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 10750.84 | 10657.81 | -999.0 | 28.15 | 16.34 | 0.00706886 | 12.80 | 10.33 | 0.00700000 | 32.36 | 0.00911022 | 19.37 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 8126.33 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91726.349 | 57655.246 | 4.572911 | 0.00224637 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 102709.49 | 101779.33 | -999.0 | 28.15 | 16.34 | 0.00707213 | 12.80 | 10.33 | 0.00700000 | 32.36 | 0.00911022 | 19.37 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 77580.89 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9338.070 | 5829.271 | 0.458475 | 0.00022869 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:10:00 | 10425.09 | 10331.37 | -999.0 | 28.46 | 16.45 | 0.00707268 | 12.80 | 10.33 | 0.00700000 | 41.03 | 0.00911023 | 21.93 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 7699.89 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 446285.303 | 446285.303 | 21.766480 | 0.01092950 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 446285.30 | 446285.30 | 21.766480 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5546 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9599.657 | 9599.657 | 0.478997 | 0.00023509 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9599.66 | 9599.66 | 0.478997 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2634 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91726.349 | 91726.349 | 4.572911 | 0.00224637 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 91726.35 | 91726.35 | 4.572911 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.4183 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9338.070 | 9338.070 | 0.458475 | 0.00022869 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9338.07 | 9338.07 | 0.458475 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.4094 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 13449.852 | 13449.852 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 13449.85 | 13449.85 | 21.766480 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5546 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 877979.12 | 21.766480 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5546 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1024418.061 | 1024418.061 | 21.766480 | 0.02263327 | 19082.502 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 824094.05 | 877979.12 | 21.766480 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5546 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 621.327 | 621.327 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.33 | 621.33 | 0.478997 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2634 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6213.274 | 6213.274 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6213.27 | 6213.27 | 4.572911 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.4183 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 621.327 | 621.327 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.33 | 621.33 | 0.458475 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.4094 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 15860.319 | 15860.319 | 1.615965 | 0.00035041 | 276.053 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 0.5959 | 0.640788 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 15047.18 | 15860.32 | 1.0000 | 1.89679639 | 1.615965 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 0.35037863 | 60.00 | 49.00 | 11.00 | 0.000 | 15047.18 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 15924.12 | 15924.12 | 1.89679639 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 385836.258 | 385836.258 | 16.184321 | 0.00852458 | 7474.226 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 14.5056 | 15.588545 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 366257.03 | 385836.26 | 1.0000 | 18.99692030 | 16.184321 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 8.52371106 | 60.00 | 49.00 | 11.00 | 0.000 | 366257.03 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.88 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 226990.86 | 0.00 | 387667.83 | 387667.83 | 18.99692030 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 32.81 | 18.93 | 0.00800000 | 53466.7 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 67664.032 | 67664.032 | 2.062959 | 0.00149495 | 1413.052 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 2.5427 | 2.733760 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 64201.74 | 67664.03 | 1.0000 | 2.42147072 | 2.062959 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 1.49480160 | 60.00 | 49.00 | 11.00 | 0.000 | 64201.74 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 47416.58 | 0.00 | 67972.99 | 67972.99 | 2.42147072 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.33 | 21.25 | 0.00800000 | 61130.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6612.522 | 6612.522 | 0.202849 | 0.00014610 | 137.835 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 0.2485 | 0.267159 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6274.20 | 6612.52 | 1.0000 | 0.23810102 | 0.202849 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 0.14608069 | 60.00 | 49.00 | 11.00 | 0.000 | 6274.20 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00791064 | 21.00 | 0.00791064 | 49.8570 | 4621.97 | 0.00 | 6642.71 | 6642.71 | 0.23810102 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.16 | 21.20 | 0.00800000 | 60958.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4950.198 | 4950.198 | 0.150847 | 0.00010937 | 103.392 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 0.1860 | 0.199998 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4696.90 | 4950.20 | 1.0000 | 0.17706249 | 0.150847 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 0.10935742 | 60.00 | 49.00 | 11.00 | 0.000 | 4696.90 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00792563 | 21.00 | 0.00792563 | 49.9503 | 3469.89 | 0.00 | 4972.80 | 4972.80 | 0.17706249 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.34 | 21.25 | 0.00800000 | 61144.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9133.778 | 9133.778 | 0.278614 | 0.00020180 | 190.715 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 0.3432 | 0.369023 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8666.42 | 9133.78 | 1.0000 | 0.32703344 | 0.278614 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 0.20177909 | 60.00 | 49.00 | 11.00 | 0.000 | 8666.42 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.92 | 0.00794449 | 21.00 | 0.00794449 | 50.0675 | 6399.56 | 0.00 | 9175.48 | 9175.48 | 0.32703344 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.31 | 21.24 | 0.00800000 | 61116.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3285.420 | 3285.420 | 0.130711 | 0.00007259 | 64.276 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 0.1235 | 0.132737 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3118.31 | 3285.42 | 1.0000 | 0.15342646 | 0.130711 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 0.07257993 | 60.00 | 49.00 | 11.00 | 0.000 | 3118.31 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.83 | 0.00785323 | 21.00 | 0.00785323 | 49.4996 | 2002.89 | 0.00 | 3300.73 | 3300.73 | 0.15342646 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 33.90 | 19.28 | 0.00800000 | 54573.2 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 158651.011 | 158651.011 | 4.849878 | 0.00350520 | 3310.497 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 5.9619 | 6.409813 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 150533.34 | 158651.01 | 1.0000 | 5.69271673 | 4.849878 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 3.50484267 | 60.00 | 49.00 | 11.00 | 0.000 | 150533.34 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00797409 | 21.00 | 0.00797409 | 50.2517 | 111053.47 | 0.00 | 159375.33 | 159375.33 | 5.69271673 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.26 | 21.22 | 0.00800000 | 61056.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 105586.540 | 105586.540 | 3.228018 | 0.00233281 | 2203.165 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 3.9678 | 4.265904 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 100184.02 | 105586.54 | 1.0000 | 3.78900058 | 3.228018 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 2.33256761 | 60.00 | 49.00 | 11.00 | 0.000 | 100184.02 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00797577 | 21.00 | 0.00797577 | 50.2621 | 73906.10 | 0.00 | 106068.59 | 106068.59 | 3.78900058 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61053.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 159920.280 | 159920.280 | 4.888791 | 0.00353324 | 3336.959 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 6.0096 | 6.461094 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 151737.67 | 159920.28 | 1.0000 | 5.73839149 | 4.888791 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 3.53288275 | 60.00 | 49.00 | 11.00 | 0.000 | 151737.67 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00797473 | 21.00 | 0.00797473 | 50.2556 | 111940.78 | 0.00 | 160650.39 | 160650.39 | 5.73839149 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61055.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 96670.320 | 96670.320 | 2.954765 | 0.00213581 | 2017.256 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 3.6327 | 3.905671 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 91723.99 | 96670.32 | 1.0000 | 3.46825998 | 2.954765 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 2.13559472 | 60.00 | 49.00 | 11.00 | 0.000 | 91723.99 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00796743 | 21.00 | 0.00796743 | 50.2103 | 67672.18 | 0.00 | 97111.67 | 97111.67 | 3.46825998 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.26 | 21.23 | 0.00800000 | 61059.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19661.897 | 19661.897 | 0.601378 | 0.00043441 | 410.209 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 0.7389 | 0.794379 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18655.87 | 19661.90 | 1.0000 | 0.70588853 | 0.601378 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 0.43436126 | 60.00 | 49.00 | 11.00 | 0.000 | 18655.87 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798652 | 21.00 | 0.00798652 | 50.3289 | 13759.71 | 0.00 | 19751.66 | 19751.66 | 0.70588853 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61041.1 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12962.462 | 12962.462 | 0.396490 | 0.00028639 | 270.433 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 0.4871 | 0.523709 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12299.22 | 12962.46 | 1.0000 | 0.46539430 | 0.396490 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 0.28636055 | 60.00 | 49.00 | 11.00 | 0.000 | 12299.22 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798709 | 21.00 | 0.00798709 | 50.3324 | 9071.13 | 0.00 | 13021.64 | 13021.64 | 0.46539430 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61039.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19761.492 | 19761.492 | 0.604431 | 0.00043661 | 412.285 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 0.7426 | 0.798403 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18750.37 | 19761.49 | 1.0000 | 0.70947245 | 0.604431 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 0.43656148 | 60.00 | 49.00 | 11.00 | 0.000 | 18750.37 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798676 | 21.00 | 0.00798676 | 50.3303 | 13829.33 | 0.00 | 19851.71 | 19851.71 | 0.70947245 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61040.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12298.412 | 12298.412 | 0.376135 | 0.00027172 | 256.588 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 0.4622 | 0.496880 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11669.15 | 12298.41 | 1.0000 | 0.44150231 | 0.376135 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 0.27169067 | 60.00 | 49.00 | 11.00 | 0.000 | 11669.15 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00798341 | 21.00 | 0.00798341 | 50.3096 | 8606.88 | 0.00 | 12354.56 | 12354.56 | 0.44150231 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61042.8 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 120910.525 | -999.000 | 5.420718 | 0.00345803 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5151 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 5.420718 | 6.36276020 | 4197.9300 | 999.8980 | 76.92045506 | 15.00 | 6.67 | 8.33 | 2689812.69 | 4.4951 | 4.495128 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 120910.52 | 120910.52 | 1.0000 | 6.36276020 | 5.420718 | 27.81 | 16.92 | 0.00789429 | 48093.3 | 11.38 | 9.72 | 0.00789429 | 29092.8 | 3.45767295 | 6.67 | 13.38 | 8.33 | 9191.664 | 111718.86 | 39.77 | 0.00911022 | 21.57 | 1.20008137 | 22.1388 | 24.00 | 0.00750710 | 24.00 | 0.00747726 | 39.3022 | 66480.81 | 0.00 | 118073.58 | 114498.39 | 6.36276020 | 27.81 | 17.18 | 0.00789429 | 48093.3 | 10.16 | 10.11 | 0.00767130 | 29536.4 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 246829.433 | 246829.433 | 5.420718 | 0.00545339 | 4641.693 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 5.420718 | 6.36276020 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 7.9850 | 9.972395 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 201616.82 | 218651.68 | 1.0000 | 6.36276020 | 5.420718 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 5.45283840 | 60.00 | 49.00 | 11.00 | 0.000 | 201616.82 | 6.30 | 0.00607234 | 6.30 | 1.20008137 | 22.1388 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 212797.80 | 212797.80 | 6.36276020 | 12.80 | 3.80 | 0.00134434 | 16256.1 | 46.00 | 17.86 | 0.00134434 | 49700.3 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 217490.262 | -999.000 | 9.804170 | 0.00622019 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1685 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.804170 | 11.50799246 | 4197.9300 | 999.8980 | 76.92045506 | 15.00 | 6.67 | 8.33 | 2689812.69 | 8.0857 | 8.085703 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 217490.26 | 217490.26 | 1.0000 | 11.50799246 | 9.804170 | 27.78 | 16.75 | 0.00770784 | 47593.1 | 11.38 | 10.33 | 0.00770784 | 30535.1 | 6.21955943 | 6.67 | 13.38 | 8.33 | 21186.290 | 196303.97 | 42.00 | 0.00911023 | 22.20 | 2.03040000 | 20.7096 | 24.00 | 0.00733447 | 24.00 | 0.00730819 | 38.4234 | 129201.54 | 0.00 | 217891.09 | 211496.78 | 11.50799246 | 27.78 | 17.02 | 0.00770784 | 47593.1 | 9.75 | 9.73 | 0.00748726 | 28659.3 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20353.766 | 20353.766 | 2.941251 | 0.00044969 | 312.901 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.804170 | 11.50799246 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 0.7053 | 0.822332 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17807.71 | 20353.77 | 1.0000 | 3.45239774 | 2.941251 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.44964571 | 60.00 | 49.00 | 11.00 | 0.000 | 17807.71 | 6.30 | 0.00607234 | 6.30 | 2.03040000 | 69.0318 | 8.34 | 0.00316494 | 21.00 | 0.00796802 | 50.2137 | 16494.32 | 0.00 | 18837.53 | 18837.53 | 3.45239774 | 12.80 | 8.54 | 0.00517197 | 25919.8 | 18.18 | 10.93 | 0.00517197 | 31376.2 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2124121.712 | -999.000 | 93.342209 | 0.06074961 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2771 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 93.342209 | 109.56372730 | 4197.9300 | 999.8980 | 76.92045506 | 15.00 | 6.67 | 8.33 | 2689812.69 | 78.9691 | 78.969131 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 2124121.71 | 2124121.69 | 1.0000 | 109.56372730 | 93.342209 | 28.12 | 16.92 | 0.00776625 | 48081.2 | 11.38 | 10.33 | 0.00776625 | 30535.1 | 60.74341498 | 6.67 | 13.38 | 8.33 | 201707.542 | 1922414.17 | 42.00 | 0.00911023 | 22.20 | 20.30400000 | 21.7522 | 24.00 | 0.00736767 | 24.00 | 0.00732607 | 38.5164 | 1187665.15 | 0.00 | 2111815.26 | 2043236.19 | 109.56372730 | 28.12 | 17.18 | 0.00776625 | 48081.2 | 9.82 | 9.80 | 0.00751779 | 28806.4 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 95609.405 | 95609.405 | 28.002663 | 0.00211237 | 1486.309 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 93.342209 | 109.56372730 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 3.4498 | 3.862808 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 87106.57 | 95609.41 | 1.0000 | 32.86911819 | 28.002663 | 6.42 | 6.38 | 0.00608957 | 21754.6 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 2.11215750 | 60.00 | 49.00 | 11.00 | 0.000 | 87106.57 | 6.30 | 0.00607234 | 6.30 | 20.30400000 | 72.5074 | 19.41 | 0.00793698 | 21.00 | 0.00798413 | 50.3140 | 297173.82 | 0.00 | 92155.30 | 92155.30 | 32.86911819 | 12.80 | 10.11 | 0.00658498 | 29487.3 | 15.56 | 11.30 | 0.00658498 | 32291.0 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 227290.195 | -999.000 | 10.509941 | 0.00650047 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.0811 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.509941 | 12.33641585 | 4197.9300 | 999.8980 | 76.92045506 | 15.00 | 6.67 | 8.33 | 2689812.69 | 8.4500 | 8.450038 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 227290.20 | 227290.20 | 1.0000 | 12.33641585 | 10.509941 | 27.45 | 16.60 | 0.00766080 | 47128.2 | 11.38 | 10.33 | 0.00766080 | 30535.1 | 6.49980770 | 6.67 | 13.38 | 8.33 | 22590.746 | 204699.45 | 41.81 | 0.00911023 | 22.15 | 2.03040000 | 19.3189 | 24.00 | 0.00731295 | 24.00 | 0.00731361 | 38.4517 | 140358.65 | 0.00 | 229218.78 | 223100.46 | 12.33641585 | 27.45 | 16.86 | 0.00766080 | 47128.2 | 9.70 | 9.69 | 0.00746392 | 28547.5 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9061.267 | 9061.267 | 3.152982 | 0.00020020 | 141.130 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.509941 | 12.33641585 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 0.3291 | 0.366093 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8308.95 | 9061.27 | 1.0000 | 3.70092476 | 3.152982 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.20017719 | 60.00 | 49.00 | 11.00 | 0.000 | 8308.95 | 6.30 | 0.00607234 | 6.30 | 2.03040000 | 64.3962 | 17.71 | 0.00361160 | 21.00 | 0.00799320 | 50.3703 | 35637.02 | 0.00 | 8789.93 | 8789.93 | 3.70092476 | 12.80 | 8.57 | 0.00519622 | 25981.0 | 15.14 | 9.63 | 0.00519622 | 28356.1 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 446285.303 | 278110.914 | 21.766480 | 0.01092950 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9137 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 06:10:00 | 497694.91 | 495682.35 | 0.8967 | -999.0 | -999.0 | 28.66 | 16.49 | 0.00703286 | 46766.2 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 497694.91 | 42.00 | 0.00911023 | 22.20 | 0.33837161 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 368665.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9599.657 | 6036.618 | 0.478997 | 0.00023509 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9807 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 10750.84 | 10657.81 | 0.8929 | -999.0 | -999.0 | 28.15 | 16.34 | 0.00706886 | 46331.2 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10750.84 | 32.36 | 0.00911022 | 19.37 | 0.01563137 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 8126.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 91726.349 | 57655.246 | 4.572911 | 0.00224637 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9867 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 102709.49 | 101779.33 | 0.8931 | -999.0 | -999.0 | 28.15 | 16.34 | 0.00707213 | 46348.1 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 102709.49 | 32.36 | 0.00911022 | 19.37 | 0.15631366 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 77580.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9338.070 | 5829.271 | 0.458475 | 0.00022869 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9878 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:10:00 | 10425.09 | 10331.37 | 0.8957 | -999.0 | -999.0 | 28.46 | 16.45 | 0.00707268 | 46655.7 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10425.09 | 41.03 | 0.00911023 | 21.93 | 0.01563137 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 7699.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 446285.303 | 446285.303 | 21.766480 | 0.01092950 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 446285.30 | 446285.30 | 1.0000 | 25.54917766 | 21.766480 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 446285.30 | 6.30 | 0.00607234 | 6.30 | 0.33837161 | 1.5546 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9599.657 | 9599.657 | 0.478997 | 0.00023509 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9599.66 | 9599.66 | 1.0000 | 0.56223918 | 0.478997 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9599.66 | 6.30 | 0.00607234 | 6.30 | 0.01563137 | 3.2634 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91726.349 | 91726.349 | 4.572911 | 0.00224637 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 91726.35 | 91726.35 | 1.0000 | 5.36761674 | 4.572911 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91726.35 | 6.30 | 0.00607234 | 6.30 | 0.15631366 | 3.4183 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9338.070 | 9338.070 | 0.458475 | 0.00022869 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9338.07 | 9338.07 | 1.0000 | 0.53815182 | 0.458475 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9338.07 | 6.30 | 0.00607234 | 6.30 | 0.01563137 | 3.4094 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13449.852 | 13449.852 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.766480 | 25.54917766 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 13449.85 | 13449.85 | 1.0000 | 25.54917766 | 21.766480 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13449.85 | 6.30 | 0.00607234 | 6.30 | 0.33837161 | 1.5546 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.766480 | 25.54917766 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 877979.12 | 1.0000 | 25.54917766 | 21.766480 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | 6.30 | 0.00607234 | 6.30 | 0.33837161 | 1.5546 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1024418.061 | 1024418.061 | 21.766480 | 0.02263327 | 19082.502 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.766480 | 25.54917766 | 4197.9300 | 999.8980 | 54.67932539 | 71.00 | 82.00 | 11.00 | 2524939.78 | 32.6382 | 41.388507 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 824094.05 | 877979.12 | 1.0000 | 25.54917766 | 21.766480 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | 22.63095646 | 60.00 | 49.00 | 11.00 | 0.000 | 824094.05 | 6.30 | 0.00607234 | 6.30 | 0.33837161 | 1.5546 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | 0.00 | 0.00 | 25.54917766 | 16.60 | 4.16 | 0.00009440 | 16919.3 | 16.60 | 4.16 | 0.00009440 | 16919.3 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.327 | 621.327 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.478997 | 0.56223918 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.33 | 621.33 | 1.0000 | 0.56223918 | 0.478997 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.33 | 6.30 | 0.00607234 | 6.30 | 0.01563137 | 3.2634 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6213.274 | 6213.274 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.572911 | 5.36761674 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6213.27 | 6213.27 | 1.0000 | 5.36761674 | 4.572911 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6213.27 | 6.30 | 0.00607234 | 6.30 | 0.15631366 | 3.4183 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.327 | 621.327 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.458475 | 0.53815182 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.33 | 621.33 | 1.0000 | 0.53815182 | 0.458475 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.33 | 6.30 | 0.00607234 | 6.30 | 0.01563137 | 3.4094 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 60.7519 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5295.33 | 1574.17 | 1573.00 |
CORE_BOTTOM | 5252.50 | 46.83 | 13.17 |
CORE_MID | 3984.67 | 662.33 | 12.83 |
CORE_TOP | 3868.83 | 1386.00 | 29.83 |
PERIMETER_BOT_ZN_3 | 4296.50 | 1143.00 | 147.83 |
PERIMETER_BOT_ZN_2 | 4531.67 | 996.17 | 260.33 |
PERIMETER_BOT_ZN_1 | 5079.67 | 740.83 | 300.33 |
PERIMETER_BOT_ZN_4 | 5313.83 | 831.50 | 637.00 |
PERIMETER_MID_ZN_3 | 3802.50 | 1991.00 | 253.83 |
PERIMETER_MID_ZN_2 | 3545.00 | 1457.17 | 367.33 |
PERIMETER_MID_ZN_1 | 4834.83 | 981.83 | 333.33 |
PERIMETER_MID_ZN_4 | 4317.83 | 1587.50 | 403.33 |
PERIMETER_TOP_ZN_3 | 3899.00 | 2212.83 | 498.33 |
PERIMETER_TOP_ZN_2 | 4206.17 | 1867.00 | 503.67 |
PERIMETER_TOP_ZN_1 | 4675.67 | 1288.67 | 445.50 |
PERIMETER_TOP_ZN_4 | 4269.50 | 1847.00 | 546.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5724.33 | 3784.50 | 2135.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 133.17 | 0.00 | 27.50 |
CORE_BOTTOM | 0.00 | 3.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.33 | 0.17 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 84.00 | 0.00 | 31.67 |
PERIMETER_BOT_ZN_2 | 0.00 | 116.83 | 0.00 | 60.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 152.17 | 0.00 | 78.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 437.00 | 0.00 | 138.67 |
PERIMETER_MID_ZN_3 | 0.17 | 69.67 | 0.00 | 27.83 |
PERIMETER_MID_ZN_2 | 0.17 | 143.17 | 0.00 | 69.17 |
PERIMETER_MID_ZN_1 | 0.00 | 145.17 | 0.00 | 82.00 |
PERIMETER_MID_ZN_4 | 0.00 | 217.33 | 0.00 | 66.67 |
PERIMETER_TOP_ZN_3 | 2.50 | 108.17 | 0.00 | 40.00 |
PERIMETER_TOP_ZN_2 | 1.50 | 173.83 | 0.00 | 76.00 |
PERIMETER_TOP_ZN_1 | 0.50 | 162.67 | 0.00 | 76.33 |
PERIMETER_TOP_ZN_4 | 0.50 | 240.67 | 0.00 | 75.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 225.83 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 172.83 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 171.33 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1080.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.83 | 1711.67 | 0.00 | 306.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.09 | 149.60 | 6779.02 | 0.545 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.86 | 134.35 | 6849.35 | 0.502 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.86 | 134.35 | 6849.35 | 0.477 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.86 | 134.35 | 6849.35 | 0.463 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.89 | 16.87 | 860.00 | 0.613 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.44 | 10.87 | 554.22 | 0.723 | 0.018 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.89 | 16.87 | 860.02 | 0.820 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.44 | 10.87 | 554.22 | 1.077 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.89 | 16.87 | 860.00 | 0.656 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.87 | 10.87 | 554.22 | 0.811 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.89 | 16.87 | 860.02 | 0.923 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.44 | 10.87 | 554.22 | 0.892 | 0.041 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.89 | 16.87 | 860.00 | 0.635 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.44 | 10.87 | 554.22 | 0.809 | 0.050 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.89 | 16.87 | 860.02 | 0.870 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.44 | 10.87 | 554.22 | 0.842 | 0.050 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.09 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.87 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31145.27 | 329561.23 | 01-JAN-03:10 | 1961182.27 | 28-AUG-15:30 |
Electricity:Building | 17256.34 | 216749.59 | 21-MAY-17:20 | 1027245.44 | 29-DEC-17:00 |
Electricity:Zone:BASEMENT | 599.48 | 14055.89 | 01-JAN-00:10 | 29063.30 | 02-JAN-08:10 |
InteriorLights:Electricity | 2580.03 | 9493.43 | 30-APR-17:20 | 251437.78 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 175.08 | 598.35 | 01-JAN-00:10 | 15605.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 2580.03 | 9493.43 | 30-APR-17:20 | 251437.78 | 11-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 446.84 | 4990.59 | 01-JAN-00:10 | 31221.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 157.23 | 537.36 | 01-JAN-00:10 | 14015.06 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4468.42 | 49905.77 | 01-JAN-00:10 | 312216.26 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1572.35 | 5373.60 | 01-JAN-00:10 | 140150.63 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 446.84 | 4990.58 | 01-JAN-00:10 | 31221.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 157.23 | 537.36 | 01-JAN-00:10 | 14015.06 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.57 | 610.54 | 12-MAR-17:10 | 3711.24 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.20 | 46.52 | 01-JAN-09:20 | 1550.69 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.62 | 393.45 | 23-APR-17:10 | 2388.48 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.19 | 29.98 | 01-JAN-07:50 | 996.14 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.45 | 610.54 | 12-MAR-17:10 | 3702.56 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.08 | 46.52 | 01-JAN-08:00 | 1541.98 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.62 | 393.45 | 12-MAR-17:10 | 2396.97 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.18 | 29.98 | 01-JAN-09:20 | 1004.63 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 475.50 | 6105.35 | 12-MAR-17:10 | 37087.99 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 111.85 | 465.16 | 01-JAN-09:10 | 15482.47 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 306.13 | 3934.52 | 23-APR-17:10 | 23849.06 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 71.79 | 299.76 | 01-JAN-07:50 | 9925.64 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 474.38 | 6105.45 | 12-MAR-17:10 | 37000.66 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 110.73 | 465.17 | 01-JAN-08:00 | 15394.81 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 306.07 | 3934.50 | 12-MAR-17:10 | 23935.53 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 71.73 | 299.76 | 01-JAN-09:10 | 10012.20 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.55 | 610.54 | 12-MAR-17:10 | 3708.36 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.18 | 46.52 | 01-JAN-09:10 | 1547.81 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.61 | 393.45 | 23-APR-17:10 | 2384.67 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.18 | 29.98 | 01-JAN-07:50 | 992.33 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.44 | 610.54 | 12-MAR-17:10 | 3699.61 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 11.07 | 46.52 | 01-JAN-08:00 | 1539.03 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.61 | 393.45 | 12-MAR-17:10 | 2393.28 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.17 | 29.98 | 01-JAN-09:10 | 1000.95 | 11-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7545.53 | 95152.58 | 01-JAN-06:10 | 384032.68 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.68 | 244.45 | 01-JAN-06:10 | 4400.15 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 156.22 | 1959.90 | 01-JAN-06:10 | 7997.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.34 | 11.29 | 01-JAN-06:10 | 203.27 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1562.22 | 19598.98 | 01-JAN-06:10 | 79976.91 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 23.41 | 112.93 | 01-JAN-06:10 | 2032.69 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 156.22 | 1959.90 | 01-JAN-06:10 | 7997.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.34 | 11.29 | 01-JAN-06:10 | 203.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.31 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.88 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.07 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.36 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.65 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.36 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 5403.89 | 77239.50 | 16-JAN-04:50 | 354510.52 | 27-APR-15:30 |
ExteriorEquipment:Electricity | 1955.63 | 13239.62 | 01-JAN-00:10 | 126013.19 | 11-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.73 | 979.82 | 01-JAN-00:10 | 3415.21 | 11-OCT-07:20 |
ElectricityPurchased:Facility | 31145.27 | 329561.23 | 01-JAN-03:10 | 1961182.27 | 28-AUG-15:30 |
ElectricityPurchased:Plant | 31145.27 | 329561.23 | 01-JAN-03:10 | 1961182.27 | 28-AUG-15:30 |
Cogeneration:ElectricityPurchased | 31145.27 | 329561.23 | 01-JAN-03:10 | 1961182.27 | 28-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31145.27 | 329561.23 | 01-JAN-03:10 | 1961182.27 | 28-AUG-15:30 |
ElectricityNet:Plant | 31145.27 | 329561.23 | 01-JAN-03:10 | 1961182.27 | 28-AUG-15:30 |
Cogeneration:ElectricityNet | 31145.27 | 329561.23 | 01-JAN-03:10 | 1961182.27 | 28-AUG-15:30 |
Fans:Electricity | 2247.56 | 42070.53 | 01-JAN-17:40 | 176999.35 | 12-JUN-16:00 |
General:Fans:Electricity | 2247.56 | 42070.53 | 01-JAN-17:40 | 176999.35 | 12-JUN-16:00 |
ExteriorLights:Electricity | 341.78 | 0.00 | 01-JAN-07:20 | 39974.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 341.78 | 0.00 | 01-JAN-07:20 | 39974.20 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 6684.40 | 28127.99 | 01-JAN-06:30 | 613552.41 | 28-AUG-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 106.87 | 0.00 | 07-FEB-14:20 | 30730.10 | 22-DEC-06:30 |
Electricity:Plant | 6242.37 | 7340.34 | 05-JAN-05:50 | 563705.14 | 28-AUG-15:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 3689.67 | 0.00 | 01-JAN-00:20 | 437406.29 | 21-JUN-15:10 |
HeatRejection:Electricity | 1858.19 | 3794.96 | 05-JAN-07:00 | 83553.66 | 16-APR-15:00 |
General:HeatRejection:Electricity | 570.48 | 0.00 | 01-JAN-00:10 | 39777.42 | 16-APR-15:00 |
Pumps:Electricity | 694.50 | 3444.35 | 01-JAN-00:20 | 50860.62 | 27-MAR-14:50 |
General:Pumps:Electricity | 694.50 | 3444.35 | 01-JAN-00:20 | 50860.62 | 27-MAR-14:50 |
WIRED_LTG_ELECTRICITY | 72.50 | 0.00 | 01-JAN-00:10 | 7065.40 | 11-OCT-07:20 |
WIRED_INT_EQUIP | 5334.88 | 88964.76 | 01-APR-00:10 | 305206.10 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 521.23 | 7280.88 | 01-JAN-00:10 | 718689.81 | 02-JAN-06:10 |
Gas:Plant | 521.23 | 7280.88 | 01-JAN-00:10 | 718689.81 | 02-JAN-06:10 |
WaterSystems:Gas | 433.65 | 7280.88 | 01-JAN-00:10 | 67389.36 | 18-JAN-12:30 |
Water Heater:WaterSystems:Gas | 433.65 | 7280.88 | 01-JAN-00:10 | 67389.36 | 18-JAN-12:30 |
Heating:Gas | 87.58 | 0.00 | 01-JAN-00:10 | 711408.93 | 02-JAN-06:10 |
Boiler:Heating:Gas | 87.58 | 0.00 | 01-JAN-00:10 | 711408.93 | 02-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 36015.32 | 144375.84 | 01-JAN-06:30 | 3136125.50 | 28-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 36015.32 | 144375.84 | 01-JAN-06:30 | 3136125.50 | 28-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 36015.32 | 144375.84 | 01-JAN-06:30 | 3136125.50 | 28-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22969.05 | 0.00 | 11-MAR-00:40 | 0.00 | 03-MAY-15:10 |
Water:Plant | 22929.30 | 0.00 | 01-JAN-00:20 | 0.00 | 03-MAY-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 22969.05 | 0.00 | 11-MAR-00:40 | 0.00 | 03-MAY-15:10 |
MainsWater:Plant | 22929.30 | 0.00 | 01-JAN-00:20 | 0.00 | 03-MAY-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 39.76 | 0.00 | 07-FEB-14:20 | 0.00 | 22-DEC-06:30 |
Humidifier:Water | 39.76 | 0.00 | 07-FEB-14:20 | 0.00 | 22-DEC-06:30 |
MainsWater:HVAC | 39.76 | 0.00 | 07-FEB-14:20 | 0.00 | 22-DEC-06:30 |
Humidifier:MainsWater | 39.76 | 0.00 | 07-FEB-14:20 | 0.00 | 22-DEC-06:30 |
HeatRejection:Water | 20649.13 | 0.00 | 01-JAN-00:20 | 0.00 | 03-MAY-15:10 |
HeatRejection:MainsWater | 20649.13 | 0.00 | 01-JAN-00:20 | 0.00 | 03-MAY-15:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 362.22 | 0.00 | 01-JAN-00:10 | 607187.45 | 02-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 295.76 | 0.00 | 01-JAN-00:10 | 40151.44 | 17-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 295.76 | 0.00 | 01-JAN-00:10 | 40151.44 | 17-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 131772.37 | 214841.76 | 03-JAN-05:50 | 12791880.31 | 28-AUG-15:20 |
EnergyTransfer:Building | 23156.18 | 90489.37 | 03-JAN-03:00 | 1733517.87 | 28-APR-16:00 |
EnergyTransfer:Zone:BASEMENT | 781.33 | 0.00 | 01-JAN-00:40 | 78234.31 | 24-NOV-06:10 |
Heating:EnergyTransfer | 44.47 | 0.00 | 03-JAN-22:10 | 403866.66 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 11.59 | 0.00 | 01-JAN-00:10 | 62056.44 | 10-SEP-09:00 |
Cooling:EnergyTransfer | 23111.71 | 89749.01 | 01-JAN-07:50 | 1733517.87 | 28-APR-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 769.74 | 0.00 | 01-JAN-00:40 | 78234.31 | 24-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 761.23 | 0.00 | 01-JAN-00:10 | 57951.79 | 07-AUG-09:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 761.23 | 0.00 | 01-JAN-00:10 | 57951.79 | 07-AUG-09:10 |
EnergyTransfer:Zone:CORE_MID | 5818.44 | 0.00 | 01-JAN-00:10 | 437013.04 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.02 | 0.00 | 01-JAN-00:10 | 30525.86 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5818.42 | 0.00 | 01-JAN-00:10 | 437013.04 | 12-JUN-16:00 |
EnergyTransfer:Zone:CORE_TOP | 599.93 | 0.00 | 01-JAN-00:10 | 60495.28 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.57 | 0.00 | 01-JAN-00:10 | 60495.28 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 599.36 | 0.00 | 01-JAN-00:10 | 57447.15 | 12-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 122.61 | 0.00 | 01-JAN-00:10 | 14085.27 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 122.61 | 0.00 | 01-JAN-00:10 | 14085.27 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 93.22 | 0.00 | 01-JAN-00:10 | 13265.49 | 12-JUN-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 93.22 | 0.00 | 01-JAN-00:10 | 13265.49 | 12-JUN-09:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 159.43 | 0.00 | 01-JAN-00:10 | 17311.82 | 02-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 462.24 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 159.43 | 0.00 | 01-JAN-00:10 | 17311.82 | 02-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 138.31 | 0.00 | 01-JAN-00:10 | 17585.74 | 27-APR-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 138.31 | 0.00 | 01-JAN-00:10 | 17585.74 | 27-APR-16:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1044.54 | 0.00 | 01-JAN-00:10 | 138916.78 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.69 | 0.00 | 01-JAN-00:10 | 82258.02 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1040.85 | 0.00 | 01-JAN-00:10 | 138916.78 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 856.77 | 0.00 | 01-JAN-00:10 | 136733.06 | 12-JUN-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.22 | 0.00 | 01-JAN-00:10 | 50721.20 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 855.54 | 0.00 | 01-JAN-00:10 | 136733.06 | 12-JUN-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1443.54 | 0.00 | 01-JAN-00:10 | 170516.06 | 02-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.57 | 0.00 | 01-JAN-00:10 | 52806.74 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1442.97 | 0.00 | 01-JAN-00:10 | 170516.06 | 02-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 941.05 | 0.00 | 01-JAN-00:10 | 152714.70 | 06-JUN-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.63 | 0.00 | 01-JAN-00:10 | 37713.51 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 940.42 | 0.00 | 01-JAN-00:10 | 152714.70 | 06-JUN-16:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 110.43 | 0.00 | 01-JAN-00:10 | 15716.86 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.11 | 0.00 | 01-JAN-00:10 | 15716.86 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 108.32 | 0.00 | 01-JAN-00:10 | 15460.75 | 12-JUN-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 92.13 | 0.00 | 01-JAN-00:10 | 14224.81 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.80 | 0.00 | 01-JAN-00:10 | 10082.85 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 91.32 | 0.00 | 01-JAN-00:10 | 14224.81 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 146.85 | 0.00 | 01-JAN-00:10 | 18690.56 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.62 | 0.00 | 01-JAN-00:10 | 12763.43 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 146.23 | 0.00 | 01-JAN-00:10 | 18690.56 | 02-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 97.36 | 0.00 | 01-JAN-00:10 | 16462.82 | 06-JUN-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.56 | 0.00 | 01-JAN-00:10 | 8264.09 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 96.80 | 0.00 | 01-JAN-00:10 | 16462.82 | 06-JUN-16:10 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 117.75 | 0.00 | 01-JAN-00:10 | 15419.40 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.56 | 0.00 | 01-JAN-00:10 | 3757.65 | 31-DEC-12:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 117.19 | 0.00 | 01-JAN-00:10 | 15419.40 | 12-JUN-16:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 937.39 | 0.00 | 01-JAN-00:10 | 130512.72 | 12-JUN-15:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 14.11 | 0.00 | 01-JAN-00:10 | 36325.42 | 02-JAN-15:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 923.28 | 0.00 | 01-JAN-00:10 | 130512.72 | 12-JUN-15:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 156.08 | 0.00 | 01-JAN-00:10 | 31183.33 | 12-JUN-14:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 6.77 | 0.00 | 01-JAN-00:10 | 20857.81 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 149.31 | 0.00 | 01-JAN-00:10 | 31183.33 | 12-JUN-14:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.53 | 1020.01 | 03-JAN-08:00 | 7774.14 | 16-APR-22:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.53 | 1020.01 | 03-JAN-08:00 | 7774.14 | 16-APR-22:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1300.51 | 18.44 | 03-JAN-03:00 | 72798.29 | 16-APR-20:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.37 | 0.00 | 01-JAN-15:50 | 5044.43 | 01-JAN-07:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1300.14 | 0.00 | 01-JAN-00:10 | 72798.29 | 16-APR-20:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 127.60 | 5.20 | 06-JAN-03:30 | 7519.04 | 16-APR-21:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.28 | 0.00 | 02-JAN-14:00 | 531.23 | 03-JAN-04:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 127.32 | 0.00 | 01-JAN-00:10 | 7519.04 | 16-APR-21:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7168.18 | 88113.66 | 08-JAN-09:20 | 370606.54 | 15-AUG-24:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7168.18 | 88113.66 | 08-JAN-09:20 | 370606.54 | 15-AUG-24:00 |
EnergyTransfer:Plant | 75394.24 | 0.00 | 01-JAN-00:20 | 8292593.85 | 23-JUN-14:10 |
WaterSystems:EnergyTransfer | 295.76 | 0.00 | 01-JAN-00:10 | 40151.44 | 17-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 295.76 | 0.00 | 01-JAN-00:10 | 40151.44 | 17-JAN-12:10 |
EnergyTransfer:HVAC | 33221.96 | 120205.35 | 01-JAN-06:30 | 2960849.16 | 28-AUG-14:30 |
HeatingCoils:EnergyTransfer | 66.46 | 0.00 | 01-JAN-00:10 | 602177.17 | 02-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 66.46 | 0.00 | 01-JAN-00:10 | 602177.17 | 02-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 66.46 | 0.00 | 01-JAN-00:10 | 602177.17 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 33155.50 | 120205.35 | 01-JAN-06:30 | 2960849.16 | 28-AUG-14:30 |
LoopToLoop:EnergyTransfer | 23865.20 | 0.00 | 01-JAN-00:20 | 2610753.16 | 23-JUN-14:10 |
Boilers:EnergyTransfer | 65.53 | 0.00 | 01-JAN-00:10 | 587160.66 | 02-JAN-06:10 |
Chillers:EnergyTransfer | 23739.04 | 0.00 | 01-JAN-00:20 | 2622325.41 | 22-JUN-16:00 |
HeatRejection:EnergyTransfer | 27428.71 | 0.00 | 01-JAN-00:20 | 3056074.60 | 21-JUN-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 11.593 | -769.738 | 0.000 | 0.000 | 92.656 | 175.081 | 424.397 | 0.000 | 0.000 | 0.000 | 66.010 | 0.000 | 0.000 | 0.000 | 0.000 | -0.009 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -761.233 | 0.000 | 0.000 | 83.447 | 157.235 | 289.609 | 0.000 | 0.000 | 0.000 | 230.943 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_MID | 0.000 | 0.000 | 0.018 | -5818.417 | 0.000 | 0.000 | 837.779 | 1572.350 | 2896.074 | 0.000 | 0.000 | 0.000 | 512.196 | 0.000 | 0.000 | 0.000 | 0.000 | -0.012 |
CORE_TOP | 0.000 | 0.000 | 0.570 | -599.361 | 0.000 | 0.000 | 84.744 | 157.235 | 289.607 | 0.000 | 0.000 | 0.000 | 67.204 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -122.607 | 0.000 | 0.000 | 10.540 | 11.204 | 36.365 | 48.204 | 0.000 | 0.648 | 43.606 | 0.000 | -27.602 | 0.000 | -0.358 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -93.216 | 0.000 | 0.000 | 6.766 | 7.187 | 23.435 | 56.224 | 0.000 | 0.423 | 16.261 | 0.000 | -16.839 | 0.000 | -0.241 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -159.429 | 0.000 | 0.000 | 10.484 | 11.085 | 36.365 | 99.349 | 0.000 | 0.634 | 28.854 | 0.000 | -26.946 | 0.000 | -0.397 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -138.304 | 0.000 | 0.000 | 6.740 | 7.183 | 23.435 | 54.780 | 0.000 | 0.394 | 67.577 | 0.000 | -21.511 | 0.000 | -0.293 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.690 | -1040.837 | 0.000 | 0.000 | 107.724 | 111.854 | 363.647 | 499.694 | 0.000 | 14.388 | 190.428 | 0.000 | -243.800 | 0.000 | -6.786 | -0.003 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.222 | -855.538 | 0.000 | 0.000 | 49.997 | 71.786 | 234.348 | 561.277 | 0.000 | 9.082 | 93.269 | 0.000 | -160.279 | 0.000 | -5.164 | -0.003 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.565 | -1442.956 | 0.000 | 0.000 | 105.158 | 110.731 | 363.653 | 996.492 | 0.000 | 13.873 | 125.255 | 0.000 | -264.011 | 0.000 | -8.762 | -0.010 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.628 | -940.406 | 0.000 | 0.000 | 68.519 | 71.725 | 234.347 | 568.521 | 0.000 | 9.005 | 173.721 | 0.000 | -180.673 | 0.000 | -5.386 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.112 | -108.315 | 0.000 | 0.000 | 10.872 | 11.185 | 36.365 | 49.571 | 0.000 | 1.735 | 20.055 | 0.000 | -22.816 | 0.000 | -0.764 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.802 | -91.323 | 0.000 | 0.000 | 6.879 | 7.178 | 23.435 | 56.295 | 0.000 | 1.111 | 11.316 | 0.000 | -15.113 | 0.000 | -0.580 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.621 | -146.225 | 0.000 | 0.000 | 10.585 | 11.073 | 36.365 | 99.323 | 0.000 | 1.675 | 12.687 | 0.000 | -25.087 | 0.000 | -1.016 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.560 | -96.802 | 0.000 | 0.000 | 6.906 | 7.172 | 23.435 | 56.587 | 0.000 | 1.095 | 18.853 | 0.000 | -17.180 | 0.000 | -0.625 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -141.531 | 0.000 | 0.000 | 0.000 | 2.341 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -14.691 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.367 | -1300.144 | 0.000 | 0.000 | 0.000 | 23.410 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -262.439 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.277 | -127.320 | 0.000 | 0.000 | 0.000 | 2.341 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -29.179 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7168.185 | 0.000 | 0.000 | 0.000 | 50.676 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -377.348 |
GROUNDFLOOR_PLENUM | 0.558 | -117.189 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.103 | 116.318 | 0.000 | 0.000 | 0.000 | -0.791 | -0.000 |
MIDFLOOR_PLENUM | 14.114 | -923.270 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20.217 | 902.071 | 0.000 | 0.000 | 0.000 | -13.133 | -0.005 |
TOPFLOOR_PLENUM | 6.768 | -149.307 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.065 | 141.780 | 0.000 | 0.000 | 0.000 | -1.307 | -0.000 |
Total Facility | 21.441 | -1189.766 | 23.025 | -21921.885 | 0.000 | 0.000 | 1499.796 | 2580.031 | 14676.305 | 3146.316 | 0.000 | 77.450 | 2838.404 | 0.000 | -1021.857 | 0.000 | -45.603 | -683.710 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-FEB-13:52 | 0.00 | 0.00 | 0.00 | -113927.70 | 0.00 | 0.00 | 359.19 | 866.99 | 13457.54 | 0.00 | 0.00 | 0.00 | 99243.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-OCT-04:12 | 0.00 | 0.00 | 0.00 | -95383.59 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 88908.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 12-APR-04:12 | 0.00 | 0.00 | 0.00 | -893386.20 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 828636.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-MAR-04:12 | 0.00 | 0.00 | 0.00 | -88244.73 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 81769.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 29-MAY-16:01 | 0.00 | 0.00 | 0.00 | -21565.57 | 0.00 | 0.00 | 38.25 | 46.52 | 720.18 | 5912.82 | 0.00 | 205.56 | 14642.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 28-MAY-08:41 | 0.00 | 0.00 | 0.00 | -18131.14 | 0.00 | 0.00 | 21.09 | 29.98 | 464.11 | 13991.67 | 0.00 | 45.73 | 3578.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-13:01 | 0.00 | 0.00 | 0.00 | -23218.59 | 0.00 | 0.00 | 32.65 | 46.52 | 720.19 | 16693.63 | 0.00 | 65.60 | 5660.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-APR-16:21 | 0.00 | 0.00 | 0.00 | -26700.90 | 0.00 | 0.00 | 14.34 | 29.98 | 464.11 | 13573.64 | 0.00 | 117.97 | 12500.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUN-16:51 | 0.00 | 0.00 | 0.00 | -208252.21 | 0.00 | 0.00 | 390.09 | 465.16 | 7201.84 | 61788.02 | 0.00 | 4585.48 | 133821.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-09:32 | 0.00 | 0.00 | 0.00 | -178433.00 | 0.00 | 0.00 | 184.68 | 299.76 | 4641.14 | 115323.28 | 0.00 | 6167.54 | 51816.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-13:51 | 0.00 | 0.00 | 0.00 | -230066.15 | 0.00 | 0.00 | 308.67 | 465.17 | 7201.95 | 147180.72 | 0.00 | 1478.89 | 73430.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUN-16:11 | 0.00 | 0.00 | 0.00 | -223314.37 | 0.00 | 0.00 | 170.83 | 299.76 | 4641.11 | 134559.28 | 0.00 | 2803.37 | 80840.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 28-MAY-16:31 | 0.00 | 0.00 | 0.00 | -24938.06 | 0.00 | 0.00 | 33.98 | 46.52 | 720.18 | 5561.05 | 0.00 | 1304.74 | 17271.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 29-MAY-15:11 | 0.00 | 0.00 | 0.00 | -19915.12 | 0.00 | 0.00 | 19.95 | 29.98 | 464.11 | 3738.91 | 0.00 | 476.62 | 15185.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 05-NOV-13:51 | 0.00 | 0.00 | 0.00 | -25190.65 | 0.00 | 0.00 | 33.26 | 46.52 | 720.19 | 15605.89 | 0.00 | 4.62 | 8780.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 28-MAY-16:31 | 0.00 | 0.00 | 0.00 | -25773.16 | 0.00 | 0.00 | 12.91 | 29.98 | 464.11 | 13550.90 | 0.00 | 712.03 | 11003.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-22:23 | 0.00 | 0.00 | 0.00 | -7776.88 | 0.00 | 0.00 | 0.00 | 12.47 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30.01 |
DATACENTER_MID_ZN_6 | 16-APR-20:22 | 0.00 | 0.00 | 0.00 | -72938.32 | 0.00 | 0.00 | 0.00 | 124.70 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5130.60 |
DATACENTER_TOP_ZN_6 | 16-APR-21:31 | 0.00 | 0.00 | 0.00 | -7524.38 | 0.00 | 0.00 | 0.00 | 12.47 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -282.52 |
DATACENTER_BASEMENT_ZN_6 | 16-AUG-00:05 | 0.00 | 0.00 | 0.00 | -370783.26 | 0.00 | 0.00 | 0.00 | 269.93 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9119.20 |
GROUNDFLOOR_PLENUM | 05-JUL-05:15 | 0.00 | -22037.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.06 | 21986.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 06-JUL-05:01 | 0.00 | -181231.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.31 | 180929.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-14:30 | 0.00 | -31182.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.45 | 30854.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:01 | 0.00 | -130616.85 | 0.00 | -2055237.63 | 0.00 | 0.00 | 15382.79 | 10469.47 | 616289.16 | 10201.66 | 0.00 | 1080.83 | 1532542.35 | 0.00 | -111.77 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 09-JUL-04:20 | 0.00 | 0.00 | 133192.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -147247.89 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-06:03 | 0.00 | 0.00 | 122091.87 | -0.00 | 0.00 | 0.00 | 11325.33 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -215264.42 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 71707.33 | -0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -78182.31 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 02-JAN-06:03 | 0.00 | 0.00 | 1817.51 | -0.00 | 0.00 | 0.00 | 140.15 | 67.47 | 960.26 | 0.00 | 0.00 | 0.00 | 1197.58 | 0.00 | -4182.97 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 153087.99 | -0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34221.17 | 0.00 | 0.00 | -126997.14 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 111859.08 | -0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23140.69 | 0.00 | 0.00 | -93957.88 |
PERIMETER_MID_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 144451.27 | -0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37424.84 | 0.00 | 0.00 | -115156.87 |
PERIMETER_MID_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 103756.56 | -0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24787.36 | 0.00 | 0.00 | -84208.66 |
PERIMETER_TOP_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 18966.09 | -0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2764.63 | 0.00 | 0.00 | -17014.49 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 13707.55 | -0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1865.76 | 0.00 | 0.00 | -12365.74 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 18510.68 | -0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2956.97 | 0.00 | 0.00 | -16366.76 |
PERIMETER_TOP_ZN_4 | 02-JAN-04:01 | 0.00 | 0.00 | 13879.60 | -0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1963.20 | 0.00 | 0.00 | -12440.34 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-07:50 | 0.00 | 0.00 | 5044.43 | 0.00 | 0.00 | 0.00 | 0.00 | 112.93 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24643.42 |
DATACENTER_TOP_ZN_6 | 01-JAN-19:45 | 0.00 | 0.00 | 531.36 | 0.00 | 0.00 | 0.00 | 0.00 | 12.47 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2492.43 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 22-DEC-05:11 | 12137.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -553.61 | -11584.27 |
MIDFLOOR_PLENUM | 10-FEB-06:03 | 70731.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1019.39 | -69712.31 |
TOPFLOOR_PLENUM | 02-JAN-05:51 | 22797.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22797.66 |
Total Facility | 02-JAN-06:03 | -210935.53 | 242412.20 | 709601.33 | -242412.20 | 0.00 | 0.00 | 20021.55 | 10469.47 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -150962.69 | 0.00 | 0.00 | -639609.09 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.4207 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.4207 | 0.2214 | 1.0000 | 1.2001 | 0.2214 | ||
VAV_BOT WITH REHEAT | 10.6238 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 9.8042 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 101.4419 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 93.3422 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.5994 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 10.5099 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.7665 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.7665 | 0.0155 | 1.0000 | 0.3384 | 0.0155 | ||
AIRLOOP DATACENTER BOT | 0.4790 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4790 | 0.0326 | 1.0000 | 0.0156 | 0.0326 | ||
AIRLOOP DATACENTER MID | 4.5729 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.5729 | 0.0342 | 1.0000 | 0.1563 | 0.0342 | ||
AIRLOOP DATACENTER TOP | 0.4585 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4585 | 0.0341 | 1.0000 | 0.0156 | 0.0341 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.4207 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.4207 | 1.0000 | 1.0000 | 1.2001 | 0.2214 | ||
VAV_BOT WITH REHEAT | 5.3119 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.2832 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 50.7209 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 22.8548 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.2997 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.2851 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.7665 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.7665 | 1.0000 | 1.0000 | 0.3384 | 0.0155 | ||
AIRLOOP DATACENTER BOT | 0.4790 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4790 | 1.0000 | 1.0000 | 0.0156 | 0.0326 | ||
AIRLOOP DATACENTER MID | 4.5729 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.5729 | 1.0000 | 1.0000 | 0.1563 | 0.0342 | ||
AIRLOOP DATACENTER TOP | 0.4585 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4585 | 1.0000 | 1.0000 | 0.0156 | 0.0341 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.4207 | 5.4207 | 5.4207 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9851 | 5.9851 | 1.6160 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 57.1884 | 57.1884 | 16.1843 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7605 | 5.7605 | 1.6187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2003 | 1.2003 | 0.2028 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9531 | 0.9531 | 0.1306 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2163 | 1.2163 | 0.2031 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2690 | 1.2690 | 0.1307 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.7068 | 11.7068 | 2.0253 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.8883 | 9.8883 | 1.3053 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.7160 | 11.7160 | 2.0269 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.9424 | 10.9424 | 1.3131 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3166 | 1.3166 | 0.2028 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0195 | 1.0195 | 0.1305 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3156 | 1.3156 | 0.2026 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1871 | 1.1871 | 0.1306 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4790 | 0.4790 | 0.4790 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.5729 | 4.5729 | 4.5729 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4585 | 0.4585 | 0.4585 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.7665 | 21.7665 | 21.7665 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.4207 | 5.4207 | 5.4207 | 5.4207 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 10.6238 | 9.8042 | 10.6238 | 2.2832 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 101.4419 | 93.3422 | 101.4419 | 22.8548 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.5994 | 10.5099 | 10.5994 | 2.2851 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.7665 | 21.7665 | 21.7665 | 21.7665 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4790 | 0.4790 | 0.4790 | 0.4790 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5729 | 4.5729 | 4.5729 | 4.5729 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4585 | 0.4585 | 0.4585 | 0.4585 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.4207 | 5.4207 | 5.4207 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9925 | 2.9925 | 1.6160 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.5942 | 28.5942 | 16.1843 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8802 | 2.8802 | 1.6187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6001 | 0.6001 | 0.2028 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4766 | 0.4766 | 0.1306 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6081 | 0.6081 | 0.2031 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6345 | 0.6345 | 0.1307 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8534 | 5.8534 | 2.0253 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9442 | 4.9442 | 1.3053 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8580 | 5.8580 | 2.0269 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4712 | 5.4712 | 1.3131 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6583 | 0.6583 | 0.2028 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5098 | 0.5098 | 0.1305 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6578 | 0.6578 | 0.2026 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5936 | 0.5936 | 0.1306 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4790 | 0.4790 | 0.4790 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.5729 | 4.5729 | 4.5729 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4585 | 0.4585 | 0.4585 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.7665 | 21.7665 | 21.7665 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.4207 | 5.4207 | 5.4207 | 5.4207 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 5.3119 | 2.2832 | 2.2832 | 2.2832 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 50.7209 | 22.8548 | 22.8548 | 22.8548 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.2997 | 2.2851 | 2.2851 | 2.2851 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.7665 | 21.7665 | 21.7665 | 21.7665 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4790 | 0.4790 | 0.4790 | 0.4790 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5729 | 4.5729 | 4.5729 | 4.5729 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4585 | 0.4585 | 0.4585 | 0.4585 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 306.83 |
Number of hours not met | 306.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 87.58 | 711408.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3689.67 | 437406.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 2994.73 | 176146.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2580.03 | 251437.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 341.78 | 39974.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.88 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.73 | 3415.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2247.56 | 176999.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 694.50 | 50860.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 570.48 | 39777.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 1287.72 | 43776.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 106.87 | 30730.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 433.65 | 67389.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.31 | 31145.27 |
Natural Gas | 0.00 | 521.23 |
Additional | 0.00 | 0.00 |
Total | 14676.31 | 31666.51 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 55.70 |
Space Heating | 0.00 |
Space Cooling | 144.31 |
Fans (All) | 48.52 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.84 |
Miscellaneous (All) | 672.39 |
Subtotal | 672.39 |
Natural Gas [MJ/m2] | |
Space Heating | 1.89 |
Service Water Heating | 9.36 |
Miscellaneous (All) | 11.25 |
Subtotal | 11.25 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.15 |
Space Heating | 0.28 |
Space Cooling | 21.11 |
Fans (All) | 7.10 |
Service Water Heating | 1.37 |
Receptacle Equipment | 46.35 |
Miscellaneous | 15.65 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2676. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1033. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUALSPSCHED | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.481807E+11 |
February | 0.000 | 0.903926E+10 |
March | 0.000 | 0.193708E+10 |
April | 0.000 | 0.944233E+09 |
May | 0.000 | 0.961075E+09 |
June | 0.000 | 0.692434E+09 |
July | 0.000 | 0.105835E+10 |
August | 0.000 | 0.709158E+09 |
September | 0.000 | 0.122915E+10 |
October | 0.000 | 0.135889E+10 |
November | 0.000 | 0.307743E+10 |
December | 0.000 | 0.183920E+11 |
Annual Sum or Average | 0.875797E+11 | |
Minimum of Months | 0.000 | 0.692434E+09 |
Maximum of Months | 0.000 | 0.481807E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.481807E+11 |
February | 0.000 | 0.903926E+10 |
March | 0.000 | 0.193708E+10 |
April | 0.000 | 0.944233E+09 |
May | 0.000 | 0.961075E+09 |
June | 0.000 | 0.692434E+09 |
July | 0.000 | 0.105835E+10 |
August | 0.000 | 0.709158E+09 |
September | 0.000 | 0.122915E+10 |
October | 0.000 | 0.135889E+10 |
November | 0.000 | 0.307743E+10 |
December | 0.000 | 0.183920E+11 |
Annual Sum or Average | 0.875797E+11 | |
Minimum of Months | 0.000 | 0.692434E+09 |
Maximum of Months | 0.000 | 0.481807E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.481807E+11 |
February | 0.000 | 0.903926E+10 |
March | 0.000 | 0.193708E+10 |
April | 0.000 | 0.944233E+09 |
May | 0.000 | 0.961075E+09 |
June | 0.000 | 0.692434E+09 |
July | 0.000 | 0.105835E+10 |
August | 0.000 | 0.709158E+09 |
September | 0.000 | 0.122915E+10 |
October | 0.000 | 0.135889E+10 |
November | 0.000 | 0.307743E+10 |
December | 0.000 | 0.183920E+11 |
Annual Sum or Average | 0.875797E+11 | |
Minimum of Months | 0.000 | 0.692434E+09 |
Maximum of Months | 0.000 | 0.481807E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.481807E+11 |
February | 0.000 | 0.903926E+10 |
March | 0.000 | 0.193708E+10 |
April | 0.000 | 0.944233E+09 |
May | 0.000 | 0.961075E+09 |
June | 0.000 | 0.692434E+09 |
July | 0.000 | 0.105835E+10 |
August | 0.000 | 0.709158E+09 |
September | 0.000 | 0.122915E+10 |
October | 0.000 | 0.135889E+10 |
November | 0.000 | 0.307743E+10 |
December | 0.000 | 0.183920E+11 |
Annual Sum or Average | 0.875797E+11 | |
Minimum of Months | 0.000 | 0.692434E+09 |
Maximum of Months | 0.000 | 0.481807E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.481807E+11 |
February | 0.000 | 0.903926E+10 |
March | 0.000 | 0.193708E+10 |
April | 0.000 | 0.944233E+09 |
May | 0.000 | 0.961075E+09 |
June | 0.000 | 0.692434E+09 |
July | 0.000 | 0.105835E+10 |
August | 0.000 | 0.709158E+09 |
September | 0.000 | 0.122915E+10 |
October | 0.000 | 0.135889E+10 |
November | 0.000 | 0.307743E+10 |
December | 0.000 | 0.183920E+11 |
Annual Sum or Average | 0.875797E+11 | |
Minimum of Months | 0.000 | 0.692434E+09 |
Maximum of Months | 0.000 | 0.481807E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.481807E+11 |
February | 0.000 | 0.903926E+10 |
March | 0.000 | 0.193708E+10 |
April | 0.000 | 0.944233E+09 |
May | 0.000 | 0.961075E+09 |
June | 0.000 | 0.692434E+09 |
July | 0.000 | 0.105835E+10 |
August | 0.000 | 0.709158E+09 |
September | 0.000 | 0.122915E+10 |
October | 0.000 | 0.135889E+10 |
November | 0.000 | 0.307743E+10 |
December | 0.000 | 0.183920E+11 |
Annual Sum or Average | 0.875797E+11 | |
Minimum of Months | 0.000 | 0.692434E+09 |
Maximum of Months | 0.000 | 0.481807E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.481807E+11 |
February | 0.000 | 0.903926E+10 |
March | 0.000 | 0.193708E+10 |
April | 0.000 | 0.944233E+09 |
May | 0.000 | 0.961075E+09 |
June | 0.000 | 0.692434E+09 |
July | 0.000 | 0.105835E+10 |
August | 0.000 | 0.709158E+09 |
September | 0.000 | 0.122915E+10 |
October | 0.000 | 0.135889E+10 |
November | 0.000 | 0.307743E+10 |
December | 0.000 | 0.183920E+11 |
Annual Sum or Average | 0.875797E+11 | |
Minimum of Months | 0.000 | 0.692434E+09 |
Maximum of Months | 0.000 | 0.481807E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.481807E+11 |
February | 0.000 | 0.903926E+10 |
March | 0.000 | 0.193708E+10 |
April | 0.000 | 0.944233E+09 |
May | 0.000 | 0.961075E+09 |
June | 0.000 | 0.692434E+09 |
July | 0.000 | 0.105835E+10 |
August | 0.000 | 0.709158E+09 |
September | 0.000 | 0.122915E+10 |
October | 0.000 | 0.135889E+10 |
November | 0.000 | 0.307743E+10 |
December | 0.000 | 0.183920E+11 |
Annual Sum or Average | 0.875797E+11 | |
Minimum of Months | 0.000 | 0.692434E+09 |
Maximum of Months | 0.000 | 0.481807E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.481807E+11 |
February | 0.000 | 0.903926E+10 |
March | 0.000 | 0.193708E+10 |
April | 0.000 | 0.944233E+09 |
May | 0.000 | 0.961075E+09 |
June | 0.000 | 0.692434E+09 |
July | 0.000 | 0.105835E+10 |
August | 0.000 | 0.709158E+09 |
September | 0.000 | 0.122915E+10 |
October | 0.000 | 0.135889E+10 |
November | 0.000 | 0.307743E+10 |
December | 0.000 | 0.183920E+11 |
Annual Sum or Average | 0.875797E+11 | |
Minimum of Months | 0.000 | 0.692434E+09 |
Maximum of Months | 0.000 | 0.481807E+11 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.574514E+11 | 108356.52 | 23-JAN-00:31 | 7.73 | 6.57 | 0.566968E+10 | 7499.24 | 04-JAN-10:30 | 13.65 | 10.88 |
February | 0.515352E+11 | 113920.62 | 20-FEB-13:52 | 26.40 | 13.44 | 0.514177E+10 | 7499.25 | 02-FEB-10:20 | 13.73 | 11.67 |
March | 0.602608E+11 | 104026.36 | 20-MAR-00:22 | 17.80 | 11.50 | 0.613570E+10 | 7499.19 | 16-MAR-09:20 | 18.63 | 14.20 |
April | 0.574894E+11 | 113181.13 | 09-APR-18:50 | 24.98 | 15.07 | 0.545340E+10 | 7499.21 | 04-APR-09:20 | 27.13 | 18.11 |
May | 0.617184E+11 | 103890.00 | 29-MAY-06:03 | 29.10 | 17.75 | 0.590521E+10 | 7499.06 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.646532E+11 | 98937.40 | 04-JUN-20:56 | 35.40 | 21.10 | 0.588567E+10 | 7499.06 | 07-JUN-09:20 | 37.90 | 20.67 |
July | 0.697409E+11 | 86109.32 | 30-JUL-08:30 | 30.00 | 26.59 | 0.547682E+10 | 7498.92 | 28-JUL-09:20 | 28.17 | 25.73 |
August | 0.776931E+11 | 85733.87 | 06-AUG-03:47 | 28.85 | 25.20 | 0.614016E+10 | 7498.91 | 11-AUG-09:20 | 27.57 | 26.11 |
September | 0.675283E+11 | 86732.46 | 03-SEP-08:20 | 27.27 | 24.97 | 0.545607E+10 | 7498.92 | 08-SEP-09:20 | 26.67 | 25.19 |
October | 0.703543E+11 | 102945.37 | 15-OCT-11:26 | 31.50 | 18.06 | 0.567360E+10 | 7499.06 | 24-OCT-09:20 | 24.07 | 16.06 |
November | 0.676405E+11 | 105772.27 | 23-NOV-23:52 | 13.00 | 11.09 | 0.561822E+10 | 7602.27 | 13-NOV-14:00 | 28.20 | 16.14 |
December | 0.636730E+11 | 112605.44 | 25-DEC-09:02 | 15.57 | 10.01 | 0.547473E+10 | 7499.15 | 18-DEC-10:20 | 20.37 | 13.78 |
Annual Sum or Average | 0.769739E+12 | 0.680310E+11 | ||||||||
Minimum of Months | 0.515352E+11 | 85733.87 | 7.73 | 6.57 | 0.514177E+10 | 7498.91 | 13.65 | 10.88 | ||
Maximum of Months | 0.776931E+11 | 113920.62 | 35.40 | 26.59 | 0.614016E+10 | 7602.27 | 37.90 | 26.11 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403294E+11 | 75448.98 | 14-JAN-05:11 | 14.63 | 12.54 | 0.507505E+10 | 6734.82 | 04-JAN-10:30 | 13.65 | 10.88 |
February | 0.441161E+11 | 83269.86 | 25-FEB-05:12 | 17.23 | 15.54 | 0.460360E+10 | 6734.81 | 02-FEB-10:20 | 13.73 | 11.67 |
March | 0.639662E+11 | 87856.02 | 15-MAR-04:12 | 18.53 | 15.11 | 0.549658E+10 | 6734.78 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.730114E+11 | 86608.10 | 24-APR-05:03 | 21.85 | 19.28 | 0.487566E+10 | 6734.74 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.713447E+11 | 86781.62 | 13-MAY-04:12 | 22.77 | 20.20 | 0.527854E+10 | 6734.69 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.723837E+11 | 84278.12 | 01-JUN-05:02 | 27.57 | 21.40 | 0.526401E+10 | 6734.60 | 27-JUN-09:20 | 26.80 | 25.04 |
July | 0.753688E+11 | 85796.20 | 05-JUL-05:04 | 32.57 | 24.72 | 0.489188E+10 | 6734.60 | 18-JUL-09:20 | 27.40 | 26.41 |
August | 0.820097E+11 | 86408.82 | 14-AUG-05:04 | 28.58 | 26.20 | 0.549343E+10 | 6734.60 | 16-AUG-09:20 | 25.07 | 24.43 |
September | 0.638692E+11 | 87638.74 | 09-SEP-03:01 | 24.35 | 23.85 | 0.487729E+10 | 6734.61 | 05-SEP-09:20 | 26.90 | 25.33 |
October | 0.653939E+11 | 95389.85 | 13-OCT-04:12 | 21.03 | 19.89 | 0.507508E+10 | 6734.65 | 24-OCT-09:20 | 24.07 | 16.06 |
November | 0.579053E+11 | 88636.61 | 09-NOV-04:02 | 17.55 | 16.05 | 0.502990E+10 | 6734.72 | 27-NOV-10:20 | 18.93 | 13.29 |
December | 0.515336E+11 | 83396.00 | 29-DEC-05:12 | 16.43 | 12.55 | 0.490087E+10 | 6734.76 | 26-DEC-10:20 | 17.10 | 11.89 |
Annual Sum or Average | 0.761232E+12 | 0.608619E+11 | ||||||||
Minimum of Months | 0.403294E+11 | 75448.98 | 14.63 | 12.54 | 0.460360E+10 | 6734.60 | 13.65 | 10.88 | ||
Maximum of Months | 0.820097E+11 | 95389.85 | 32.57 | 26.20 | 0.549658E+10 | 6734.82 | 35.77 | 26.41 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282418E+11 | 62957.55 | 14-JAN-06:03 | 14.50 | 12.49 | 0.493936E+10 | 6734.76 | 09-JAN-10:20 | 12.40 | 10.75 |
February | 0.323499E+11 | 75686.22 | 25-FEB-05:11 | 17.23 | 15.54 | 0.456505E+10 | 6734.79 | 02-FEB-10:20 | 13.73 | 11.67 |
March | 0.480385E+11 | 85320.84 | 30-MAR-04:12 | 21.60 | 16.65 | 0.548291E+10 | 6734.77 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.549311E+11 | 89338.79 | 12-APR-04:12 | 21.33 | 15.48 | 0.486442E+10 | 6734.74 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.622399E+11 | 83068.07 | 13-MAY-03:01 | 22.88 | 19.89 | 0.526752E+10 | 6734.69 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.602996E+11 | 75812.89 | 01-JUN-03:01 | 27.32 | 22.01 | 0.525583E+10 | 6734.62 | 20-JUN-13:20 | 33.33 | 27.52 |
July | 0.587882E+11 | 85012.01 | 19-JUL-03:01 | 23.42 | 23.42 | 0.487969E+10 | 6734.62 | 18-JUL-13:20 | 25.73 | 25.08 |
August | 0.594210E+11 | 75187.32 | 22-AUG-03:01 | 25.88 | 25.10 | 0.548627E+10 | 6734.62 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.523002E+11 | 82641.54 | 09-SEP-05:02 | 24.90 | 24.28 | 0.487059E+10 | 6734.62 | 11-SEP-13:20 | 31.00 | 26.98 |
October | 0.511055E+11 | 88180.56 | 19-OCT-04:12 | 20.60 | 18.55 | 0.506805E+10 | 6734.70 | 24-OCT-09:20 | 24.07 | 16.06 |
November | 0.420156E+11 | 79428.55 | 09-NOV-05:12 | 17.33 | 15.90 | 0.500870E+10 | 6734.70 | 27-NOV-10:20 | 18.93 | 13.29 |
December | 0.321108E+11 | 69373.97 | 29-DEC-06:03 | 16.53 | 12.54 | 0.484218E+10 | 6734.73 | 26-DEC-10:20 | 17.10 | 11.89 |
Annual Sum or Average | 0.581842E+12 | 0.605306E+11 | ||||||||
Minimum of Months | 0.282418E+11 | 62957.55 | 14.50 | 12.49 | 0.456505E+10 | 6734.62 | 12.40 | 10.75 | ||
Maximum of Months | 0.622399E+11 | 89338.79 | 27.32 | 25.10 | 0.548627E+10 | 6734.79 | 35.77 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230798E+11 | 31316.64 | 26-JAN-16:50 | 18.87 | 12.77 | 0.451904E+10 | 6734.61 | 13-JAN-14:20 | 21.30 | 15.26 |
February | 0.280327E+11 | 63791.68 | 25-FEB-06:03 | 17.60 | 15.66 | 0.440905E+10 | 6734.67 | 24-FEB-10:20 | 20.97 | 15.03 |
March | 0.469660E+11 | 88249.26 | 14-MAR-04:12 | 20.77 | 16.47 | 0.545767E+10 | 6734.77 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.599541E+11 | 84415.21 | 12-APR-03:01 | 22.27 | 16.43 | 0.486557E+10 | 6734.73 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.711563E+11 | 81055.37 | 23-MAY-03:01 | 28.47 | 24.77 | 0.527618E+10 | 6734.68 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.695077E+11 | 82108.24 | 28-JUN-03:01 | 26.40 | 25.45 | 0.526310E+10 | 6734.60 | 27-JUN-09:20 | 26.80 | 25.04 |
July | 0.662617E+11 | 82328.35 | 25-JUL-03:01 | 28.00 | 26.05 | 0.489018E+10 | 6734.60 | 18-JUL-09:20 | 27.40 | 26.41 |
August | 0.656395E+11 | 81706.77 | 22-AUG-03:01 | 25.88 | 25.10 | 0.549302E+10 | 6734.60 | 16-AUG-09:20 | 25.07 | 24.43 |
September | 0.560749E+11 | 85560.30 | 09-SEP-05:02 | 24.90 | 24.28 | 0.487274E+10 | 6734.60 | 07-SEP-09:20 | 24.87 | 24.32 |
October | 0.507211E+11 | 84680.78 | 12-OCT-04:11 | 21.00 | 20.42 | 0.505473E+10 | 6734.69 | 23-OCT-09:20 | 24.30 | 16.36 |
November | 0.366693E+11 | 71604.59 | 09-NOV-06:03 | 17.53 | 15.94 | 0.493095E+10 | 6734.67 | 03-NOV-09:20 | 21.27 | 14.45 |
December | 0.252999E+11 | 33350.52 | 01-DEC-16:30 | 21.75 | 13.99 | 0.453221E+10 | 6734.64 | 29-DEC-14:20 | 19.70 | 14.82 |
Annual Sum or Average | 0.599363E+12 | 0.595645E+11 | ||||||||
Minimum of Months | 0.230798E+11 | 31316.64 | 17.53 | 12.77 | 0.440905E+10 | 6734.60 | 19.70 | 14.45 | ||
Maximum of Months | 0.711563E+11 | 88249.26 | 28.47 | 26.05 | 0.549302E+10 | 6734.77 | 35.77 | 26.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318202E+10 | 4289.15 | 26-JAN-14:20 | 22.20 | 13.78 | 0.598288E+09 | 845.61 | 27-JAN-14:20 | 16.10 | 11.95 |
February | 0.424548E+10 | 6364.57 | 23-FEB-14:30 | 26.10 | 13.97 | 0.564830E+09 | 845.62 | 27-FEB-10:20 | 16.50 | 13.70 |
March | 0.844799E+10 | 13773.77 | 11-MAR-06:01 | 23.80 | 17.14 | 0.688338E+09 | 845.63 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.129461E+11 | 20837.93 | 30-APR-16:21 | 37.45 | 17.96 | 0.613691E+09 | 845.62 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.153064E+11 | 21563.65 | 29-MAY-16:01 | 41.23 | 21.50 | 0.665389E+09 | 845.62 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.159833E+11 | 21138.55 | 04-JUN-16:51 | 41.80 | 22.58 | 0.663082E+09 | 845.61 | 12-JUN-13:20 | 43.50 | 22.36 |
July | 0.155590E+11 | 20566.17 | 04-JUL-16:21 | 39.80 | 24.46 | 0.616965E+09 | 845.61 | 10-JUL-13:20 | 39.20 | 26.71 |
August | 0.157480E+11 | 20007.91 | 06-AUG-15:41 | 36.30 | 26.22 | 0.691560E+09 | 845.61 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.113907E+11 | 19995.47 | 24-SEP-15:01 | 35.05 | 24.89 | 0.613840E+09 | 845.61 | 08-SEP-13:20 | 28.50 | 25.85 |
October | 0.952621E+10 | 19417.33 | 01-OCT-15:01 | 35.92 | 19.93 | 0.637229E+09 | 845.61 | 24-OCT-09:20 | 24.07 | 16.06 |
November | 0.614224E+10 | 7039.92 | 09-NOV-14:30 | 29.30 | 17.76 | 0.627265E+09 | 845.62 | 27-NOV-10:20 | 18.93 | 13.29 |
December | 0.413038E+10 | 5194.96 | 26-DEC-14:10 | 22.68 | 14.37 | 0.598577E+09 | 845.62 | 15-DEC-10:30 | 15.25 | 12.50 |
Annual Sum or Average | 0.122608E+12 | 0.757906E+10 | ||||||||
Minimum of Months | 0.318202E+10 | 4289.15 | 22.20 | 13.78 | 0.564830E+09 | 845.61 | 15.25 | 11.95 | ||
Maximum of Months | 0.159833E+11 | 21563.65 | 41.80 | 26.22 | 0.691560E+09 | 845.63 | 43.50 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248977E+10 | 3984.28 | 26-JAN-10:10 | 17.70 | 12.84 | 0.401293E+09 | 544.95 | 04-JAN-10:50 | 14.88 | 11.64 |
February | 0.356689E+10 | 7126.95 | 21-FEB-09:40 | 18.10 | 12.97 | 0.367850E+09 | 544.96 | 02-FEB-10:20 | 13.73 | 11.67 |
March | 0.705338E+10 | 11537.03 | 26-MAR-09:13 | 23.83 | 14.48 | 0.444336E+09 | 544.96 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.106321E+11 | 17948.97 | 30-APR-09:01 | 28.90 | 14.95 | 0.395855E+09 | 544.95 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.127470E+11 | 18130.39 | 28-MAY-08:41 | 33.67 | 19.65 | 0.429351E+09 | 558.14 | 04-MAY-09:09 | 38.12 | 21.19 |
June | 0.118406E+11 | 16804.48 | 04-JUN-16:11 | 42.13 | 22.31 | 0.427631E+09 | 565.85 | 12-JUN-09:30 | 39.25 | 21.95 |
July | 0.106605E+11 | 16721.66 | 04-JUL-09:41 | 34.98 | 25.15 | 0.397615E+09 | 544.94 | 10-JUL-13:20 | 39.20 | 26.71 |
August | 0.102450E+11 | 15800.70 | 06-AUG-15:01 | 36.30 | 26.23 | 0.445539E+09 | 544.94 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.854993E+10 | 16140.20 | 17-SEP-09:21 | 29.80 | 25.35 | 0.395746E+09 | 544.94 | 08-SEP-13:20 | 28.50 | 25.85 |
October | 0.760613E+10 | 16630.76 | 01-OCT-09:42 | 29.28 | 19.24 | 0.411259E+09 | 544.94 | 24-OCT-09:09 | 23.63 | 15.88 |
November | 0.484466E+10 | 6711.60 | 13-NOV-09:40 | 21.37 | 14.08 | 0.405257E+09 | 544.95 | 13-NOV-10:20 | 23.03 | 14.76 |
December | 0.298027E+10 | 4597.13 | 01-DEC-09:30 | 17.35 | 11.07 | 0.389319E+09 | 544.95 | 18-DEC-10:20 | 20.37 | 13.78 |
Annual Sum or Average | 0.932162E+11 | 0.491105E+10 | ||||||||
Minimum of Months | 0.248977E+10 | 3984.28 | 17.35 | 11.07 | 0.367850E+09 | 544.94 | 13.73 | 11.64 | ||
Maximum of Months | 0.127470E+11 | 18130.39 | 42.13 | 26.23 | 0.445539E+09 | 565.85 | 39.25 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.697175E+10 | 15984.99 | 08-JAN-13:53 | 22.30 | 13.07 | 0.622851E+09 | 845.64 | 09-JAN-10:20 | 12.40 | 10.75 |
February | 0.817305E+10 | 21199.46 | 20-FEB-12:13 | 24.97 | 13.24 | 0.571619E+09 | 845.64 | 02-FEB-10:20 | 13.73 | 11.67 |
March | 0.127715E+11 | 21161.51 | 12-MAR-12:32 | 30.37 | 18.83 | 0.690193E+09 | 845.65 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.152017E+11 | 21780.78 | 30-APR-15:01 | 37.88 | 18.21 | 0.614291E+09 | 845.64 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.159481E+11 | 22075.20 | 29-MAY-15:21 | 41.30 | 21.72 | 0.665545E+09 | 845.64 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.160637E+11 | 21537.21 | 04-JUN-16:11 | 42.13 | 22.31 | 0.663125E+09 | 845.63 | 12-JUN-13:20 | 43.50 | 22.36 |
July | 0.157461E+11 | 20884.36 | 04-JUL-16:21 | 39.80 | 24.46 | 0.617004E+09 | 845.62 | 10-JUL-13:20 | 39.20 | 26.71 |
August | 0.164203E+11 | 20450.30 | 06-AUG-15:41 | 36.30 | 26.22 | 0.691698E+09 | 845.63 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.137689E+11 | 21558.75 | 24-SEP-15:01 | 35.05 | 24.89 | 0.614451E+09 | 859.08 | 28-SEP-13:39 | 35.37 | 22.73 |
October | 0.158003E+11 | 23216.90 | 01-OCT-13:01 | 35.32 | 19.92 | 0.641346E+09 | 899.67 | 02-OCT-13:39 | 36.33 | 21.07 |
November | 0.136023E+11 | 21847.50 | 05-NOV-14:01 | 29.33 | 17.22 | 0.633486E+09 | 875.43 | 01-NOV-13:39 | 28.37 | 15.90 |
December | 0.896204E+10 | 21301.98 | 03-DEC-12:13 | 23.13 | 14.20 | 0.610160E+09 | 845.64 | 28-DEC-14:20 | 24.57 | 15.31 |
Annual Sum or Average | 0.159430E+12 | 0.763577E+10 | ||||||||
Minimum of Months | 0.697175E+10 | 15984.99 | 22.30 | 13.07 | 0.571619E+09 | 845.62 | 12.40 | 10.75 | ||
Maximum of Months | 0.164203E+11 | 23216.90 | 42.13 | 26.22 | 0.691698E+09 | 899.67 | 43.50 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348047E+10 | 7006.29 | 31-JAN-16:00 | 21.10 | 11.21 | 0.404123E+09 | 544.95 | 13-JAN-10:20 | 15.90 | 12.85 |
February | 0.537001E+10 | 18631.48 | 19-FEB-16:12 | 25.17 | 13.57 | 0.372472E+09 | 544.95 | 02-FEB-10:20 | 13.73 | 11.67 |
March | 0.111158E+11 | 21973.68 | 19-MAR-16:42 | 24.48 | 14.99 | 0.446241E+09 | 544.96 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.170565E+11 | 26699.25 | 30-APR-16:21 | 37.45 | 17.96 | 0.397025E+09 | 544.95 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.151447E+11 | 25980.86 | 28-MAY-16:01 | 42.20 | 19.45 | 0.429628E+09 | 544.95 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.162017E+11 | 25772.83 | 04-JUN-16:11 | 42.13 | 22.31 | 0.428128E+09 | 544.94 | 12-JUN-13:20 | 43.50 | 22.36 |
July | 0.157246E+11 | 23493.36 | 04-JUL-16:21 | 39.80 | 24.46 | 0.398499E+09 | 544.94 | 10-JUL-09:20 | 33.27 | 26.52 |
August | 0.176538E+11 | 23060.19 | 06-AUG-16:21 | 36.15 | 26.33 | 0.446703E+09 | 544.94 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.109430E+11 | 23232.65 | 24-SEP-15:01 | 35.05 | 24.89 | 0.396527E+09 | 544.94 | 08-SEP-13:20 | 28.50 | 25.85 |
October | 0.107035E+11 | 23776.07 | 01-OCT-15:01 | 35.92 | 19.93 | 0.412473E+09 | 544.94 | 24-OCT-09:09 | 23.63 | 15.88 |
November | 0.839846E+10 | 22045.66 | 05-NOV-15:21 | 28.45 | 17.57 | 0.408121E+09 | 544.95 | 03-NOV-09:20 | 21.27 | 14.45 |
December | 0.651264E+10 | 17259.42 | 25-DEC-14:51 | 24.10 | 14.38 | 0.397140E+09 | 544.95 | 18-DEC-10:20 | 20.37 | 13.78 |
Annual Sum or Average | 0.138305E+12 | 0.493708E+10 | ||||||||
Minimum of Months | 0.348047E+10 | 7006.29 | 21.10 | 11.21 | 0.372472E+09 | 544.94 | 13.73 | 11.67 | ||
Maximum of Months | 0.176538E+11 | 26699.25 | 42.20 | 26.33 | 0.446703E+09 | 544.96 | 43.50 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221638E+10 | 2676.51 | 26-JAN-15:10 | 21.37 | 13.56 | 0.517916E+09 | 830.80 | 26-JAN-14:00 | 21.60 | 13.64 |
February | 0.302191E+10 | 5111.79 | 24-FEB-15:00 | 26.40 | 17.36 | 0.522859E+09 | 845.61 | 22-FEB-14:20 | 27.03 | 16.26 |
March | 0.625861E+10 | 12971.80 | 11-MAR-06:01 | 23.80 | 17.14 | 0.678517E+09 | 845.63 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.107503E+11 | 19611.52 | 16-APR-16:01 | 39.13 | 22.68 | 0.613109E+09 | 845.62 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.149754E+11 | 19890.19 | 28-MAY-16:11 | 42.10 | 19.47 | 0.665526E+09 | 845.62 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.151692E+11 | 20827.58 | 04-JUN-16:51 | 41.80 | 22.58 | 0.663211E+09 | 845.61 | 07-JUN-13:20 | 43.30 | 21.73 |
July | 0.138970E+11 | 19799.03 | 02-JUL-16:21 | 40.35 | 26.44 | 0.617129E+09 | 845.61 | 10-JUL-09:20 | 33.27 | 26.52 |
August | 0.130900E+11 | 19490.03 | 27-AUG-14:41 | 35.52 | 29.12 | 0.691817E+09 | 845.61 | 28-AUG-09:20 | 31.07 | 27.58 |
September | 0.101245E+11 | 19127.07 | 24-SEP-15:11 | 35.00 | 24.96 | 0.614016E+09 | 845.61 | 08-SEP-13:20 | 28.50 | 25.85 |
October | 0.765387E+10 | 15078.01 | 01-OCT-13:51 | 35.90 | 19.83 | 0.634655E+09 | 845.62 | 24-OCT-09:20 | 24.07 | 16.06 |
November | 0.430942E+10 | 5763.36 | 09-NOV-14:40 | 29.27 | 17.74 | 0.605102E+09 | 845.61 | 13-NOV-14:20 | 28.20 | 16.00 |
December | 0.261830E+10 | 2660.03 | 01-DEC-15:10 | 23.22 | 13.40 | 0.523153E+09 | 825.07 | 01-DEC-14:00 | 23.40 | 13.33 |
Annual Sum or Average | 0.104085E+12 | 0.734701E+10 | ||||||||
Minimum of Months | 0.221638E+10 | 2660.03 | 21.37 | 13.40 | 0.517916E+09 | 825.07 | 21.60 | 13.33 | ||
Maximum of Months | 0.151692E+11 | 20827.58 | 42.10 | 29.12 | 0.691817E+09 | 845.63 | 43.30 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147152E+10 | 4580.11 | 26-JAN-11:05 | 19.98 | 13.26 | 0.273640E+09 | 548.49 | 25-JAN-11:09 | 18.70 | 11.51 |
February | 0.258452E+10 | 7204.87 | 23-FEB-11:05 | 23.97 | 14.21 | 0.264640E+09 | 548.49 | 02-FEB-11:09 | 16.18 | 12.86 |
March | 0.613594E+10 | 16697.66 | 12-MAR-10:13 | 26.67 | 17.45 | 0.326727E+09 | 548.50 | 16-MAR-10:09 | 20.22 | 15.34 |
April | 0.102760E+11 | 17639.87 | 16-APR-09:22 | 33.85 | 21.40 | 0.293001E+09 | 548.50 | 12-APR-10:09 | 28.30 | 17.09 |
May | 0.130565E+11 | 17843.96 | 29-MAY-09:32 | 35.10 | 21.75 | 0.317456E+09 | 548.50 | 05-MAY-10:09 | 37.92 | 20.08 |
June | 0.118557E+11 | 17765.75 | 04-JUN-16:11 | 42.13 | 22.31 | 0.315745E+09 | 548.49 | 07-JUN-12:09 | 42.00 | 21.55 |
July | 0.102226E+11 | 17126.02 | 02-JUL-09:42 | 35.17 | 25.98 | 0.294765E+09 | 548.48 | 10-JUL-12:09 | 38.28 | 26.73 |
August | 0.950903E+10 | 16773.60 | 27-AUG-10:01 | 32.00 | 28.62 | 0.329160E+09 | 548.48 | 24-AUG-10:09 | 30.98 | 27.37 |
September | 0.799319E+10 | 16837.14 | 17-SEP-09:21 | 29.80 | 25.35 | 0.292833E+09 | 548.48 | 14-SEP-12:09 | 32.90 | 26.80 |
October | 0.686577E+10 | 17234.17 | 01-OCT-09:51 | 29.70 | 19.32 | 0.304052E+09 | 548.49 | 24-OCT-12:09 | 29.75 | 17.81 |
November | 0.382638E+10 | 7873.43 | 01-NOV-10:05 | 23.77 | 14.99 | 0.296543E+09 | 548.49 | 13-NOV-11:09 | 24.98 | 15.42 |
December | 0.175738E+10 | 4819.80 | 01-DEC-15:05 | 23.22 | 13.40 | 0.273451E+09 | 548.49 | 20-DEC-11:09 | 17.32 | 9.52 |
Annual Sum or Average | 0.855545E+11 | 0.358201E+10 | ||||||||
Minimum of Months | 0.147152E+10 | 4580.11 | 19.98 | 13.26 | 0.264640E+09 | 548.48 | 16.18 | 9.52 | ||
Maximum of Months | 0.130565E+11 | 17843.96 | 42.13 | 28.62 | 0.329160E+09 | 548.50 | 42.00 | 27.37 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.619684E+10 | 17485.45 | 08-JAN-14:13 | 22.50 | 13.33 | 0.608242E+09 | 845.64 | 04-JAN-10:50 | 14.88 | 11.64 |
February | 0.723605E+10 | 21301.44 | 20-FEB-14:02 | 26.38 | 13.53 | 0.562480E+09 | 845.64 | 22-FEB-14:20 | 27.03 | 16.26 |
March | 0.111629E+11 | 20986.23 | 12-MAR-12:52 | 30.70 | 19.00 | 0.688030E+09 | 848.93 | 28-MAR-13:00 | 35.00 | 18.11 |
April | 0.133096E+11 | 20269.00 | 16-APR-15:21 | 39.50 | 22.46 | 0.614269E+09 | 845.64 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.155665E+11 | 20041.54 | 07-MAY-15:41 | 42.32 | 21.42 | 0.665673E+09 | 845.64 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.151458E+11 | 20851.19 | 04-JUN-16:11 | 42.13 | 22.31 | 0.663233E+09 | 845.63 | 07-JUN-13:20 | 43.30 | 21.73 |
July | 0.140805E+11 | 19845.16 | 02-JUL-16:21 | 40.35 | 26.44 | 0.617181E+09 | 845.63 | 10-JUL-09:20 | 33.27 | 26.52 |
August | 0.138910E+11 | 19765.07 | 27-AUG-14:41 | 35.52 | 29.12 | 0.692034E+09 | 845.62 | 28-AUG-09:20 | 31.07 | 27.58 |
September | 0.127748E+11 | 20359.51 | 24-SEP-13:51 | 35.10 | 24.59 | 0.615244E+09 | 885.89 | 28-SEP-13:50 | 35.43 | 22.74 |
October | 0.148828E+11 | 23004.50 | 01-OCT-13:51 | 35.90 | 19.83 | 0.643838E+09 | 921.56 | 02-OCT-13:50 | 36.37 | 21.05 |
November | 0.126420E+11 | 22313.20 | 12-NOV-12:42 | 27.52 | 16.25 | 0.633487E+09 | 897.17 | 01-NOV-13:50 | 28.43 | 15.91 |
December | 0.740840E+10 | 20584.27 | 03-DEC-12:32 | 23.57 | 14.18 | 0.600226E+09 | 845.64 | 29-DEC-14:20 | 19.70 | 14.82 |
Annual Sum or Average | 0.144297E+12 | 0.760394E+10 | ||||||||
Minimum of Months | 0.619684E+10 | 17485.45 | 22.50 | 13.33 | 0.562480E+09 | 845.62 | 14.88 | 11.64 | ||
Maximum of Months | 0.155665E+11 | 23004.50 | 42.32 | 29.12 | 0.692034E+09 | 921.56 | 43.30 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198333E+10 | 4661.54 | 31-JAN-16:20 | 20.80 | 11.16 | 0.360158E+09 | 544.94 | 13-JAN-14:20 | 21.30 | 15.26 |
February | 0.289369E+10 | 9396.40 | 20-FEB-15:22 | 25.95 | 14.07 | 0.351952E+09 | 544.95 | 24-FEB-10:20 | 20.97 | 15.03 |
March | 0.665433E+10 | 19551.31 | 12-MAR-16:52 | 30.60 | 19.78 | 0.443089E+09 | 544.95 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.111336E+11 | 20042.21 | 30-APR-16:31 | 37.33 | 17.89 | 0.396378E+09 | 544.95 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.136031E+11 | 20586.89 | 28-MAY-16:11 | 42.10 | 19.47 | 0.429592E+09 | 544.95 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.132589E+11 | 22333.50 | 04-JUN-16:11 | 42.13 | 22.31 | 0.428016E+09 | 544.94 | 07-JUN-13:20 | 43.30 | 21.73 |
July | 0.111257E+11 | 20115.95 | 02-JUL-16:21 | 40.35 | 26.44 | 0.398173E+09 | 544.94 | 10-JUL-09:20 | 33.27 | 26.52 |
August | 0.105580E+11 | 19320.48 | 06-AUG-16:21 | 36.15 | 26.33 | 0.446308E+09 | 544.94 | 28-AUG-09:20 | 31.07 | 27.58 |
September | 0.870914E+10 | 19461.94 | 24-SEP-15:51 | 34.80 | 25.24 | 0.396344E+09 | 544.94 | 08-SEP-13:20 | 28.50 | 25.85 |
October | 0.735198E+10 | 19940.07 | 15-OCT-15:21 | 32.35 | 19.24 | 0.411379E+09 | 544.95 | 24-OCT-09:20 | 24.07 | 16.06 |
November | 0.441017E+10 | 18221.64 | 05-NOV-15:21 | 28.45 | 17.57 | 0.400578E+09 | 544.95 | 13-NOV-10:20 | 23.03 | 14.76 |
December | 0.235980E+10 | 5370.13 | 01-DEC-15:30 | 22.85 | 13.53 | 0.362990E+09 | 544.95 | 29-DEC-14:20 | 19.70 | 14.82 |
Annual Sum or Average | 0.940417E+11 | 0.482496E+10 | ||||||||
Minimum of Months | 0.198333E+10 | 4661.54 | 20.80 | 11.16 | 0.351952E+09 | 544.94 | 19.70 | 14.76 | ||
Maximum of Months | 0.136031E+11 | 22333.50 | 42.13 | 26.44 | 0.446308E+09 | 544.95 | 43.30 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165760E+10 | 2659.40 | 26-JAN-15:00 | 21.60 | 13.64 | 0.497955E+09 | 824.31 | 26-JAN-14:00 | 21.60 | 13.64 |
February | 0.270339E+10 | 5357.05 | 23-FEB-15:00 | 25.80 | 14.07 | 0.502903E+09 | 845.61 | 22-FEB-14:20 | 27.03 | 16.26 |
March | 0.628593E+10 | 13994.54 | 11-MAR-06:01 | 23.80 | 17.14 | 0.668989E+09 | 845.63 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.114818E+11 | 22667.65 | 16-APR-15:21 | 39.50 | 22.46 | 0.612836E+09 | 845.62 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.163402E+11 | 24938.66 | 28-MAY-16:31 | 41.90 | 19.49 | 0.665725E+09 | 845.62 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.164887E+11 | 24424.66 | 04-JUN-16:51 | 41.80 | 22.58 | 0.663402E+09 | 845.61 | 07-JUN-13:20 | 43.30 | 21.73 |
July | 0.150493E+11 | 22804.41 | 02-JUL-16:21 | 40.35 | 26.44 | 0.617355E+09 | 845.60 | 10-JUL-09:20 | 33.27 | 26.52 |
August | 0.139706E+11 | 22187.54 | 06-AUG-15:41 | 36.30 | 26.22 | 0.691938E+09 | 845.60 | 28-AUG-09:20 | 31.07 | 27.58 |
September | 0.106348E+11 | 22734.84 | 24-SEP-15:01 | 35.05 | 24.89 | 0.614144E+09 | 845.60 | 08-SEP-13:20 | 28.50 | 25.85 |
October | 0.769077E+10 | 21758.24 | 01-OCT-15:21 | 35.75 | 20.01 | 0.631040E+09 | 845.62 | 23-OCT-09:20 | 24.30 | 16.36 |
November | 0.396185E+10 | 6209.16 | 09-NOV-14:50 | 29.23 | 17.71 | 0.585591E+09 | 845.61 | 13-NOV-14:20 | 28.20 | 16.00 |
December | 0.205085E+10 | 2647.89 | 28-DEC-16:30 | 23.30 | 15.04 | 0.495014E+09 | 811.99 | 28-DEC-14:00 | 24.50 | 15.37 |
Annual Sum or Average | 0.108316E+12 | 0.724689E+10 | ||||||||
Minimum of Months | 0.165760E+10 | 2647.89 | 21.60 | 13.64 | 0.495014E+09 | 811.99 | 21.60 | 13.64 | ||
Maximum of Months | 0.164887E+11 | 24938.66 | 41.90 | 26.44 | 0.691938E+09 | 845.63 | 43.30 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151374E+10 | 2677.73 | 26-JAN-14:30 | 22.05 | 13.75 | 0.350225E+09 | 544.94 | 12-JAN-14:20 | 23.40 | 14.03 |
February | 0.252062E+10 | 5477.65 | 23-FEB-10:30 | 22.35 | 14.31 | 0.351231E+09 | 544.95 | 22-FEB-14:20 | 27.03 | 16.26 |
March | 0.632740E+10 | 17164.79 | 12-MAR-16:21 | 30.95 | 19.83 | 0.441899E+09 | 544.96 | 27-MAR-09:39 | 24.63 | 16.63 |
April | 0.110386E+11 | 18259.83 | 16-APR-09:22 | 33.85 | 21.40 | 0.396214E+09 | 544.95 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.142173E+11 | 19914.64 | 29-MAY-15:11 | 41.30 | 21.78 | 0.429670E+09 | 563.25 | 04-MAY-09:30 | 38.55 | 21.37 |
June | 0.130011E+11 | 19100.82 | 04-JUN-16:11 | 42.13 | 22.31 | 0.428000E+09 | 567.56 | 12-JUN-09:50 | 39.75 | 22.06 |
July | 0.112504E+11 | 17821.05 | 02-JUL-09:42 | 35.17 | 25.98 | 0.398092E+09 | 544.94 | 10-JUL-09:20 | 33.27 | 26.52 |
August | 0.103775E+11 | 17340.68 | 06-AUG-15:01 | 36.30 | 26.23 | 0.446125E+09 | 544.94 | 28-AUG-09:20 | 31.07 | 27.58 |
September | 0.860755E+10 | 18023.72 | 24-SEP-15:01 | 35.05 | 24.89 | 0.396110E+09 | 544.94 | 12-SEP-09:20 | 30.03 | 27.20 |
October | 0.710068E+10 | 17306.99 | 01-OCT-14:41 | 35.98 | 19.88 | 0.410245E+09 | 544.95 | 23-OCT-09:20 | 24.30 | 16.36 |
November | 0.367659E+10 | 5665.18 | 09-NOV-10:00 | 24.50 | 17.88 | 0.398025E+09 | 544.95 | 27-NOV-10:20 | 18.93 | 13.29 |
December | 0.169257E+10 | 2790.40 | 01-DEC-15:00 | 23.40 | 13.33 | 0.351539E+09 | 544.95 | 28-DEC-14:20 | 24.57 | 15.31 |
Annual Sum or Average | 0.913241E+11 | 0.479737E+10 | ||||||||
Minimum of Months | 0.151374E+10 | 2677.73 | 22.05 | 13.33 | 0.350225E+09 | 544.94 | 18.93 | 13.29 | ||
Maximum of Months | 0.142173E+11 | 19914.64 | 42.13 | 26.23 | 0.446125E+09 | 567.56 | 39.75 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.509862E+10 | 12581.79 | 12-JAN-14:30 | 23.45 | 14.07 | 0.587849E+09 | 845.63 | 27-JAN-14:20 | 16.10 | 11.95 |
February | 0.652188E+10 | 23440.21 | 20-FEB-13:52 | 26.40 | 13.44 | 0.548986E+09 | 845.64 | 22-FEB-14:20 | 27.03 | 16.26 |
March | 0.110711E+11 | 24010.40 | 12-MAR-14:22 | 31.35 | 19.47 | 0.682831E+09 | 845.64 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.140668E+11 | 23324.50 | 16-APR-15:21 | 39.50 | 22.46 | 0.614155E+09 | 845.64 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.169195E+11 | 25023.61 | 28-MAY-15:51 | 42.30 | 19.44 | 0.665850E+09 | 845.64 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.164516E+11 | 24403.74 | 04-JUN-16:11 | 42.13 | 22.31 | 0.663418E+09 | 845.63 | 07-JUN-13:20 | 43.30 | 21.73 |
July | 0.152265E+11 | 22806.73 | 02-JUL-16:21 | 40.35 | 26.44 | 0.617399E+09 | 845.62 | 10-JUL-09:20 | 33.27 | 26.52 |
August | 0.147752E+11 | 22409.65 | 06-AUG-15:41 | 36.30 | 26.22 | 0.692124E+09 | 845.62 | 28-AUG-09:20 | 31.07 | 27.58 |
September | 0.133326E+11 | 24240.63 | 24-SEP-15:01 | 35.05 | 24.89 | 0.614876E+09 | 863.49 | 28-SEP-13:50 | 35.43 | 22.74 |
October | 0.148802E+11 | 24477.30 | 22-OCT-12:42 | 29.45 | 17.87 | 0.639764E+09 | 897.99 | 02-OCT-13:50 | 36.37 | 21.05 |
November | 0.118324E+11 | 25189.38 | 05-NOV-13:51 | 29.40 | 17.20 | 0.624355E+09 | 862.07 | 01-NOV-13:50 | 28.43 | 15.91 |
December | 0.605070E+10 | 22144.78 | 03-DEC-14:13 | 24.20 | 14.17 | 0.583580E+09 | 845.64 | 28-DEC-14:20 | 24.57 | 15.31 |
Annual Sum or Average | 0.146227E+12 | 0.753519E+10 | ||||||||
Minimum of Months | 0.509862E+10 | 12581.79 | 23.45 | 13.44 | 0.548986E+09 | 845.62 | 16.10 | 11.95 | ||
Maximum of Months | 0.169195E+11 | 25189.38 | 42.30 | 26.44 | 0.692124E+09 | 897.99 | 43.30 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169710E+10 | 4529.03 | 12-JAN-16:00 | 23.30 | 14.47 | 0.346822E+09 | 544.94 | 26-JAN-14:20 | 22.20 | 13.78 |
February | 0.269393E+10 | 7783.55 | 20-FEB-16:33 | 24.93 | 14.42 | 0.340349E+09 | 544.94 | 22-FEB-14:20 | 27.03 | 16.26 |
March | 0.664133E+10 | 21822.47 | 12-MAR-16:21 | 30.95 | 19.83 | 0.439414E+09 | 544.95 | 27-MAR-09:20 | 23.77 | 16.21 |
April | 0.116357E+11 | 22124.60 | 16-APR-15:21 | 39.50 | 22.46 | 0.396382E+09 | 544.95 | 06-APR-09:20 | 26.20 | 16.90 |
May | 0.144778E+11 | 25774.17 | 28-MAY-16:31 | 41.90 | 19.49 | 0.429605E+09 | 544.95 | 05-MAY-09:20 | 35.77 | 19.24 |
June | 0.141201E+11 | 24953.38 | 04-JUN-16:11 | 42.13 | 22.31 | 0.428017E+09 | 544.94 | 07-JUN-13:20 | 43.30 | 21.73 |
July | 0.118736E+11 | 22204.82 | 02-JUL-16:21 | 40.35 | 26.44 | 0.398237E+09 | 544.94 | 10-JUL-09:20 | 33.27 | 26.52 |
August | 0.111282E+11 | 21296.84 | 06-AUG-16:21 | 36.15 | 26.33 | 0.446322E+09 | 544.94 | 28-AUG-09:20 | 31.07 | 27.58 |
September | 0.906238E+10 | 22317.52 | 24-SEP-15:01 | 35.05 | 24.89 | 0.396380E+09 | 544.94 | 12-SEP-09:20 | 30.03 | 27.20 |
October | 0.735849E+10 | 21506.17 | 01-OCT-16:01 | 35.32 | 20.14 | 0.410419E+09 | 544.95 | 23-OCT-09:20 | 24.30 | 16.36 |
November | 0.413821E+10 | 19803.95 | 05-NOV-15:12 | 28.63 | 17.50 | 0.391933E+09 | 544.94 | 13-NOV-14:20 | 28.20 | 16.00 |
December | 0.197627E+10 | 5219.66 | 28-DEC-16:00 | 23.80 | 15.18 | 0.346792E+09 | 544.95 | 29-DEC-14:20 | 19.70 | 14.82 |
Annual Sum or Average | 0.968031E+11 | 0.477067E+10 | ||||||||
Minimum of Months | 0.169710E+10 | 4529.03 | 23.30 | 14.42 | 0.340349E+09 | 544.94 | 19.70 | 13.78 | ||
Maximum of Months | 0.144778E+11 | 25774.17 | 42.13 | 26.44 | 0.446322E+09 | 544.95 | 43.30 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149353E+10 | 2581.00 | 26-JAN-17:00 | 18.60 | 12.68 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.339869E+10 | 7506.13 | 21-FEB-06:15 | 11.70 | 10.89 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.809308E+10 | 9668.07 | 13-MAR-05:03 | 20.77 | 15.49 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.131294E+11 | 15454.05 | 18-APR-05:01 | 24.27 | 18.77 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.154735E+11 | 18174.08 | 31-MAY-05:01 | 31.72 | 21.10 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.153940E+11 | 19690.67 | 12-JUN-05:04 | 34.12 | 19.10 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.145323E+11 | 22039.08 | 05-JUL-05:15 | 32.63 | 24.67 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.147137E+11 | 20577.90 | 07-AUG-05:13 | 29.57 | 24.73 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.106872E+11 | 15323.41 | 26-SEP-05:01 | 25.12 | 20.62 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.101179E+11 | 13194.03 | 02-OCT-05:03 | 21.60 | 17.46 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.680722E+10 | 9552.74 | 13-NOV-06:15 | 15.27 | 12.05 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.334883E+10 | 6081.92 | 04-DEC-06:04 | 8.25 | 7.68 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.117189E+12 | 0.00 | ||||||||
Minimum of Months | 0.149353E+10 | 2581.00 | 8.25 | 7.68 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.154735E+11 | 22039.08 | 34.12 | 24.73 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.610127E+09 | 2392.43 | 04-JAN-06:02 | 5.65 | 5.26 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.179615E+10 | 3823.13 | 23-FEB-15:30 | 25.30 | 14.21 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.580024E+10 | 9370.81 | 11-MAR-06:01 | 23.80 | 17.14 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.105142E+11 | 11128.18 | 22-APR-05:03 | 21.90 | 16.70 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.139707E+11 | 13726.98 | 30-MAY-05:03 | 30.25 | 21.55 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.135847E+11 | 16461.26 | 30-JUN-05:01 | 30.23 | 23.49 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.120554E+11 | 18123.52 | 06-JUL-05:01 | 31.18 | 25.95 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.112502E+11 | 14828.88 | 03-AUG-05:01 | 28.40 | 23.49 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.915698E+10 | 12414.06 | 06-SEP-05:01 | 25.10 | 24.35 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.808900E+10 | 12761.28 | 03-OCT-05:03 | 22.92 | 17.51 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.432040E+10 | 5806.90 | 01-NOV-15:40 | 28.03 | 15.88 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.117944E+10 | 2969.50 | 01-DEC-06:10 | 11.02 | 8.78 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.923275E+11 | 0.00 | ||||||||
Minimum of Months | 0.610127E+09 | 2392.43 | 5.65 | 5.26 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.139707E+11 | 18123.52 | 31.18 | 25.95 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108912E+10 | 4545.40 | 12-JAN-15:30 | 23.45 | 14.33 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.302115E+10 | 11384.20 | 22-FEB-14:50 | 27.08 | 16.20 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.924909E+10 | 20759.52 | 28-MAR-15:10 | 35.58 | 18.51 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.179417E+11 | 25912.77 | 27-APR-15:00 | 40.00 | 19.37 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.243314E+11 | 29586.42 | 04-MAY-14:40 | 42.07 | 22.17 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.242092E+11 | 31183.33 | 12-JUN-14:30 | 44.05 | 22.21 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.195939E+11 | 27036.16 | 07-JUL-14:20 | 40.33 | 24.54 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.176652E+11 | 23948.27 | 07-AUG-14:30 | 37.25 | 26.41 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.136821E+11 | 20732.32 | 26-SEP-14:40 | 35.97 | 22.74 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.114729E+11 | 21375.28 | 02-OCT-14:30 | 36.40 | 21.02 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.560384E+10 | 13722.53 | 09-NOV-14:05 | 29.37 | 17.81 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.144944E+10 | 6237.09 | 01-DEC-14:50 | 23.42 | 13.28 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.149309E+12 | 0.00 | ||||||||
Minimum of Months | 0.108912E+10 | 4545.40 | 23.42 | 13.28 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.243314E+11 | 31183.33 | 44.05 | 26.41 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361495E+10 | 1709.08 | 12-JAN-17:00 | 22.30 | 14.51 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.823702E+10 | 3901.77 | 20-FEB-17:25 | 23.80 | 14.40 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.144903E+11 | 5900.67 | 26-MAR-18:05 | 27.40 | 15.69 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.190602E+11 | 7776.88 | 16-APR-22:23 | 27.65 | 19.98 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.473200E+10 | 2670.04 | 01-MAY-00:12 | 30.47 | 18.20 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.944811E+10 | 4155.77 | 11-JUN-17:30 | 42.45 | 23.14 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.148132E+11 | 6078.75 | 04-JUL-18:00 | 40.20 | 24.14 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.198263E+11 | 7679.83 | 14-AUG-04:11 | 28.80 | 26.08 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.444757E+10 | 2200.40 | 01-SEP-00:10 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.960348E+10 | 4048.62 | 01-OCT-17:12 | 33.73 | 20.31 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.140217E+11 | 5825.16 | 12-NOV-16:28 | 26.95 | 15.47 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.192357E+11 | 7498.43 | 24-DEC-17:00 | 20.70 | 13.27 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.141531E+12 | 0.00 | ||||||||
Minimum of Months | 0.361495E+10 | 1709.08 | 20.70 | 13.27 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.198263E+11 | 7776.88 | 42.45 | 26.08 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199999E+10 | 1523.10 | 12-JAN-17:30 | 21.50 | 14.26 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.707963E+10 | 3455.34 | 22-FEB-17:00 | 25.70 | 15.73 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.136000E+11 | 5512.39 | 12-MAR-17:48 | 29.35 | 19.35 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.180927E+11 | 7293.83 | 16-APR-20:22 | 29.30 | 20.39 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.438886E+10 | 2140.80 | 29-MAY-17:52 | 40.20 | 21.22 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.894174E+10 | 3886.46 | 11-JUN-18:00 | 41.80 | 23.25 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.140228E+11 | 5666.95 | 02-JUL-18:05 | 39.48 | 26.61 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.187462E+11 | 7175.46 | 20-AUG-15:02 | 28.88 | 26.43 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.406428E+10 | 1955.36 | 17-SEP-18:13 | 35.87 | 26.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.897458E+10 | 3826.86 | 01-OCT-16:56 | 34.40 | 20.18 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.128855E+11 | 5317.83 | 12-NOV-16:33 | 26.77 | 15.41 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.172183E+11 | 7027.39 | 01-DEC-17:00 | 21.20 | 14.24 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.130014E+12 | 0.00 | ||||||||
Minimum of Months | 0.199999E+10 | 1523.10 | 21.20 | 14.24 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.187462E+11 | 7293.83 | 41.80 | 26.91 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104442E+10 | 1541.93 | 12-JAN-17:00 | 22.30 | 14.51 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.640897E+10 | 3514.72 | 22-FEB-17:00 | 25.70 | 15.73 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.134184E+11 | 5756.73 | 12-MAR-17:26 | 29.85 | 19.53 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.181882E+11 | 7524.38 | 16-APR-21:31 | 28.07 | 20.02 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.460325E+10 | 2620.31 | 29-MAY-18:01 | 39.97 | 21.19 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.913390E+10 | 4382.02 | 11-JUN-17:25 | 42.45 | 23.14 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.142266E+11 | 6126.18 | 02-JUL-18:00 | 39.60 | 26.57 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.188805E+11 | 7374.01 | 20-AUG-15:02 | 28.88 | 26.43 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.414910E+10 | 2235.10 | 17-SEP-17:59 | 35.70 | 26.84 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.888297E+10 | 4117.67 | 01-OCT-17:05 | 34.07 | 20.25 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.123517E+11 | 5358.50 | 09-NOV-16:40 | 27.67 | 17.51 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.160317E+11 | 7029.91 | 01-DEC-17:00 | 21.20 | 14.24 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.127320E+12 | 0.00 | ||||||||
Minimum of Months | 0.104442E+10 | 1541.93 | 21.20 | 14.24 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.188805E+11 | 7524.38 | 42.45 | 26.84 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238780E+12 | 90525.60 | 26-JAN-17:00 | 18.60 | 12.68 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.435741E+12 | 182018.64 | 21-FEB-17:00 | 25.40 | 15.68 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.727224E+12 | 272989.00 | 27-MAR-16:00 | 33.10 | 17.76 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.937764E+12 | 368422.69 | 29-APR-04:52 | 25.80 | 17.75 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.240352E+12 | 121590.87 | 01-MAY-00:12 | 30.47 | 18.20 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.470019E+12 | 183025.30 | 12-JUN-16:00 | 44.30 | 22.15 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.733326E+12 | 275652.22 | 05-JUL-16:00 | 37.30 | 26.55 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.973048E+12 | 370787.49 | 16-AUG-00:05 | 23.47 | 22.97 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.237324E+12 | 115328.44 | 01-SEP-00:23 | 28.30 | 25.83 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.488435E+12 | 183801.74 | 10-OCT-16:00 | 30.80 | 21.39 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.709301E+12 | 275288.75 | 13-NOV-17:00 | 26.40 | 16.63 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.976864E+12 | 366350.61 | 18-DEC-17:00 | 20.00 | 14.41 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.716818E+13 | 0.00 | ||||||||
Minimum of Months | 0.237324E+12 | 90525.60 | 18.60 | 12.68 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.976864E+12 | 370787.49 | 44.30 | 26.55 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121581E+10 | 107795.73 | 02-JAN-01:47 | 7.25 |
February | 0.588073E+09 | 114897.73 | 20-FEB-11:47 | 24.15 |
March | 0.923616E+09 | 122846.32 | 11-MAR-04:50 | 24.00 |
April | 0.845007E+09 | 123995.65 | 27-APR-03:50 | 28.52 |
May | 0.932178E+09 | 128332.90 | 21-MAY-15:20 | 34.20 |
June | 0.698500E+09 | 129365.98 | 11-JUN-13:40 | 42.40 |
July | 0.932085E+09 | 133262.81 | 09-JUL-04:20 | 30.70 |
August | 0.664940E+09 | 132725.86 | 20-AUG-12:20 | 30.80 |
September | 0.977293E+09 | 129463.04 | 17-SEP-10:05 | 30.73 |
October | 0.957307E+09 | 118331.23 | 01-OCT-05:07 | 21.53 |
November | 0.130133E+10 | 119902.99 | 26-NOV-11:46 | 24.83 |
December | 0.155879E+10 | 115452.85 | 03-DEC-14:15 | 24.20 |
Annual Sum or Average | 0.115949E+11 | |||
Minimum of Months | 0.588073E+09 | 107795.73 | 7.25 | |
Maximum of Months | 0.155879E+10 | 133262.81 | 42.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1831551.48 | 12210.34 | 02-JAN-06:03 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 1831551.48 | |||
Minimum of Months | 0.00 | 0.00 | 6.45 | |
Maximum of Months | 1831551.48 | 12210.34 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.569193E+09 | 71707.42 | 02-JAN-04:01 | 6.67 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 786040.20 | 5240.27 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.569979E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.569193E+09 | 71707.42 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 277344.77 | 1817.58 | 02-JAN-06:03 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 277344.77 | |||
Minimum of Months | 0.00 | 0.00 | 6.45 | |
Maximum of Months | 277344.77 | 1817.58 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.302412E+09 | 15310.08 | 02-JAN-05:11 | 6.47 |
February | 19133221.51 | 9869.01 | 11-FEB-06:03 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 47448859.22 | 13486.90 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.368994E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.302412E+09 | 15310.08 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105747E+09 | 11187.17 | 02-JAN-05:11 | 6.47 |
February | 3749456.50 | 7404.75 | 11-FEB-06:03 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 12712150.35 | 7052.52 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.122208E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.105747E+09 | 11187.17 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50613445.21 | 14446.54 | 02-JAN-05:11 | 6.47 |
February | 5930867.55 | 9816.61 | 11-FEB-06:03 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 10465.07 | 45.56 | 30-DEC-06:06 | 10.48 |
Annual Sum or Average | 56554777.83 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 50613445.21 | 14446.54 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55999964.06 | 10376.99 | 02-JAN-05:11 | 6.47 |
February | 2333492.11 | 4035.11 | 11-FEB-06:03 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 4496692.54 | 4382.84 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 62830148.71 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 55999964.06 | 10376.99 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127127E+10 | 18966.22 | 02-JAN-05:11 | 6.47 |
February | 0.234801E+09 | 16325.49 | 11-FEB-05:11 | 9.07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 20004132.02 | 12506.47 | 27-NOV-06:03 | 9.55 |
December | 0.585541E+09 | 16746.38 | 22-DEC-05:11 | 11.37 |
Annual Sum or Average | 0.211162E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 0.127127E+10 | 18966.22 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506465E+09 | 13707.67 | 02-JAN-05:11 | 6.47 |
February | 81114318.32 | 12186.61 | 11-FEB-05:11 | 9.07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 2261462.94 | 2714.03 | 27-NOV-06:03 | 9.55 |
December | 0.211956E+09 | 12200.36 | 22-DEC-05:11 | 11.37 |
Annual Sum or Average | 0.801797E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 0.506465E+09 | 13707.67 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.433583E+09 | 18510.83 | 02-JAN-05:11 | 6.47 |
February | 77973067.55 | 16305.96 | 11-FEB-05:11 | 9.07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.109590E+09 | 15687.20 | 23-DEC-05:11 | 5.10 |
Annual Sum or Average | 0.621147E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.10 | |
Maximum of Months | 0.433583E+09 | 18510.83 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.385784E+09 | 13879.77 | 02-JAN-04:01 | 6.67 |
February | 54496526.93 | 12130.53 | 11-FEB-05:11 | 9.07 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.119408E+09 | 12050.78 | 22-DEC-05:11 | 11.37 |
Annual Sum or Average | 0.559689E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.67 | |
Maximum of Months | 0.385784E+09 | 13879.77 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72742651.40 | 11762.69 | 02-JAN-05:11 | 6.47 |
February | 72012702.04 | 9993.71 | 10-FEB-05:11 | 12.30 |
March | 51337923.45 | 8067.65 | 22-MAR-03:01 | 17.73 |
April | 27605724.80 | 5870.44 | 02-APR-15:41 | 33.88 |
May | 14428760.22 | 4850.10 | 28-MAY-16:02 | 42.20 |
June | 15043967.54 | 6628.58 | 04-JUN-16:12 | 42.13 |
July | 19969259.86 | 4872.76 | 30-JUL-15:02 | 34.78 |
August | 21142776.73 | 5384.49 | 27-AUG-14:22 | 35.55 |
September | 15891179.92 | 6806.39 | 13-SEP-03:01 | 25.90 |
October | 37380279.99 | 6620.57 | 13-OCT-03:01 | 21.62 |
November | 72376471.57 | 8471.96 | 28-NOV-04:01 | 15.28 |
December | 0.138379E+09 | 12137.64 | 22-DEC-05:11 | 11.37 |
Annual Sum or Average | 0.558310E+09 | |||
Minimum of Months | 14428760.22 | 4850.10 | 6.47 | |
Maximum of Months | 0.138379E+09 | 12137.64 | 42.20 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.908859E+09 | 6879.33 | 12-JAN-06:03 | 12.75 |
February | 0.127083E+09 | 7072.61 | 10-FEB-06:03 | 12.33 |
March | 21431726.98 | 5253.76 | 01-MAR-06:02 | 13.67 |
April | 14831524.63 | 5107.63 | 02-APR-15:51 | 33.90 |
May | 19263103.37 | 6117.81 | 14-MAY-15:21 | 36.15 |
June | 13573513.45 | 6470.50 | 04-JUN-16:12 | 42.13 |
July | 19630082.12 | 4690.55 | 25-JUL-03:01 | 28.00 |
August | 15367523.29 | 5095.85 | 27-AUG-14:01 | 35.58 |
September | 13809739.01 | 6165.51 | 11-SEP-03:02 | 26.07 |
October | 24479632.15 | 4619.08 | 15-OCT-14:01 | 32.85 |
November | 36306541.46 | 5485.18 | 28-NOV-06:03 | 15.22 |
December | 0.196754E+09 | 6841.54 | 19-DEC-06:02 | 10.22 |
Annual Sum or Average | 0.141139E+10 | |||
Minimum of Months | 13573513.45 | 4619.08 | 10.22 | |
Maximum of Months | 0.908859E+09 | 7072.61 | 42.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255192E+10 | 22797.75 | 02-JAN-05:51 | 6.40 |
February | 0.115562E+10 | 13701.85 | 24-FEB-06:03 | 15.00 |
March | 0.374465E+09 | 15630.83 | 06-MAR-06:01 | 15.58 |
April | 35203259.08 | 12139.52 | 11-APR-04:11 | 18.13 |
May | 3774751.71 | 6663.35 | 23-MAY-03:01 | 28.47 |
June | 3142553.94 | 8181.69 | 28-JUN-03:01 | 26.40 |
July | 3654880.09 | 5106.98 | 19-JUL-04:03 | 24.72 |
August | 3850794.73 | 6768.06 | 24-AUG-03:01 | 25.58 |
September | 10823992.96 | 7995.17 | 11-SEP-03:02 | 26.07 |
October | 0.148325E+09 | 14177.01 | 30-OCT-05:03 | 16.20 |
November | 0.674135E+09 | 15547.30 | 06-NOV-06:01 | 14.70 |
December | 0.180345E+10 | 8312.99 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.676837E+10 | |||
Minimum of Months | 3142553.94 | 5106.98 | 5.43 | |
Maximum of Months | 0.255192E+10 | 22797.75 | 28.47 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36686784.98 | 504.44 | 01-JAN-07:45 | 7.85 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 36686784.98 | |||
Minimum of Months | 0.00 | 0.00 | 7.85 | |
Maximum of Months | 36686784.98 | 504.44 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276771E+09 | 531.36 | 01-JAN-19:45 | 10.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.276771E+09 | |||
Minimum of Months | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 0.276771E+09 | 531.36 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.146017E+11 | 15605.75 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.132465E+11 | 15605.75 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.157676E+11 | 15605.75 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.140562E+11 | 15605.75 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.151846E+11 | 15605.75 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.151213E+11 | 15605.75 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.141196E+11 | 15605.75 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.157673E+11 | 15605.75 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.140562E+11 | 15605.75 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.146020E+11 | 15605.75 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.144381E+11 | 15605.75 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.141198E+11 | 15605.75 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.175081E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.132465E+11 | 15605.75 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.157676E+11 | 15605.75 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.131134E+11 | 14015.06 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.118963E+11 | 14015.06 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.141604E+11 | 14015.06 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.126235E+11 | 14015.06 | 03-APR-07:10 | 0.235253E+11 | 17206.63 | 03-APR-07:10 |
May | 0.136369E+11 | 14015.06 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.135800E+11 | 14015.06 | 01-JUN-07:10 | 0.244214E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.126804E+11 | 14015.06 | 03-JUL-07:10 | 0.239654E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.141602E+11 | 14015.06 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.126235E+11 | 14015.06 | 01-SEP-07:10 | 0.235253E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.131136E+11 | 14015.06 | 02-OCT-07:10 | 0.243681E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.129664E+11 | 14015.06 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.126806E+11 | 14015.06 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.157235E+12 | 0.289609E+12 | ||||
Minimum of Months | 0.118963E+11 | 14015.06 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.141604E+11 | 14015.06 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.131134E+11 | 14015.06 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.118963E+11 | 14015.06 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.141604E+11 | 14015.06 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.126235E+11 | 14015.06 | 03-APR-07:10 | 0.235252E+11 | 17206.56 | 03-APR-07:10 |
May | 0.136369E+11 | 14015.06 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.135800E+11 | 14015.06 | 01-JUN-07:10 | 0.244213E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.126804E+11 | 14015.06 | 03-JUL-07:10 | 0.239653E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.141602E+11 | 14015.06 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.126235E+11 | 14015.06 | 01-SEP-07:10 | 0.235252E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.131136E+11 | 14015.06 | 02-OCT-07:10 | 0.243680E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.129664E+11 | 14015.06 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.126806E+11 | 14015.06 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.157235E+12 | 0.289607E+12 | ||||
Minimum of Months | 0.118963E+11 | 14015.06 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.141604E+11 | 14015.06 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.131134E+11 | 14015.06 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.118963E+11 | 14015.06 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.141604E+11 | 14015.06 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.126235E+11 | 14015.06 | 03-APR-07:10 | 0.235252E+11 | 17206.56 | 03-APR-07:10 |
May | 0.136369E+11 | 14015.06 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.135800E+11 | 14015.06 | 01-JUN-07:10 | 0.244213E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.126804E+11 | 14015.06 | 03-JUL-07:10 | 0.239653E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.141602E+11 | 14015.06 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.126235E+11 | 14015.06 | 01-SEP-07:10 | 0.235252E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.131136E+11 | 14015.06 | 02-OCT-07:10 | 0.243680E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.129664E+11 | 14015.06 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.126806E+11 | 14015.06 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.157235E+12 | 0.289607E+12 | ||||
Minimum of Months | 0.118963E+11 | 14015.06 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.141604E+11 | 14015.06 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.991663E+09 | 1444.18 | 18-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.874796E+09 | 1411.50 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.992601E+09 | 1425.43 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.867172E+09 | 921.15 | 03-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.917194E+09 | 980.59 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.913946E+09 | 978.79 | 23-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.872144E+09 | 1366.21 | 26-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.982718E+09 | 1414.94 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.893141E+09 | 1463.78 | 08-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.951001E+09 | 1550.69 | 11-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.974541E+09 | 1509.24 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.973439E+09 | 1525.22 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.112044E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.867172E+09 | 921.15 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.992601E+09 | 1550.69 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.630088E+09 | 920.00 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.559262E+09 | 914.92 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.636675E+09 | 796.99 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.558125E+09 | 539.58 | 03-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.593799E+09 | 611.46 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.591316E+09 | 611.86 | 23-JUN-07:10 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.562625E+09 | 846.00 | 26-JUL-07:10 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.632284E+09 | 880.12 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.573360E+09 | 914.52 | 08-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.606881E+09 | 981.50 | 11-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.623689E+09 | 996.14 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.619314E+09 | 991.12 | 29-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.718742E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.558125E+09 | 539.58 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.636675E+09 | 996.14 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.956192E+09 | 1381.97 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.856603E+09 | 1361.79 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.986775E+09 | 1406.67 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.868946E+09 | 930.72 | 03-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.924556E+09 | 1129.89 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.921023E+09 | 1142.10 | 23-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.878265E+09 | 1388.77 | 26-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.985265E+09 | 1424.97 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.890707E+09 | 1460.84 | 08-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.938672E+09 | 1541.98 | 11-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.944894E+09 | 1331.80 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.932803E+09 | 1445.98 | 29-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.110847E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.856603E+09 | 930.72 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.986775E+09 | 1541.98 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.625516E+09 | 938.54 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.555370E+09 | 921.43 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.639362E+09 | 952.24 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.559763E+09 | 736.94 | 03-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.594957E+09 | 776.19 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.592285E+09 | 777.91 | 23-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.566230E+09 | 907.86 | 26-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.637565E+09 | 931.89 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.576383E+09 | 956.21 | 08-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.612947E+09 | 1004.63 | 11-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.613583E+09 | 890.94 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.609168E+09 | 906.48 | 29-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.718313E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.555370E+09 | 736.94 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.639362E+09 | 1004.63 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.988661E+09 | 1440.15 | 18-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.872759E+09 | 1407.11 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.991258E+09 | 1421.12 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.866610E+09 | 911.44 | 03-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.916693E+09 | 974.82 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.912693E+09 | 972.93 | 23-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.871095E+09 | 1361.46 | 26-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.981439E+09 | 1410.82 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.891850E+09 | 1460.27 | 08-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.949419E+09 | 1548.25 | 11-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.972194E+09 | 1505.63 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.970695E+09 | 1522.26 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.111854E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.866610E+09 | 911.44 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.991258E+09 | 1548.25 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.628877E+09 | 914.37 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.558335E+09 | 909.13 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.636163E+09 | 789.41 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.557855E+09 | 539.58 | 03-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.593402E+09 | 607.35 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.590789E+09 | 607.84 | 23-JUN-07:10 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.561868E+09 | 839.16 | 26-JUL-07:10 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.631353E+09 | 874.48 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.572691E+09 | 909.75 | 08-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.606162E+09 | 977.83 | 11-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.622803E+09 | 992.56 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.618252E+09 | 987.38 | 29-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.717855E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.557855E+09 | 539.58 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.636163E+09 | 992.56 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.955737E+09 | 1377.66 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.855869E+09 | 1357.03 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.985894E+09 | 1402.20 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.868411E+09 | 921.68 | 03-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.923873E+09 | 1121.46 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.919976E+09 | 1133.73 | 23-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.877049E+09 | 1384.22 | 26-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.983858E+09 | 1420.93 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.889791E+09 | 1457.30 | 08-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.937263E+09 | 1539.48 | 11-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.942976E+09 | 1326.06 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.932441E+09 | 1442.17 | 29-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.110731E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.855869E+09 | 921.68 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.985894E+09 | 1539.48 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.624474E+09 | 933.42 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.554539E+09 | 915.82 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.638631E+09 | 947.35 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.559203E+09 | 726.97 | 03-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.594306E+09 | 766.61 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.591377E+09 | 768.38 | 23-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.565060E+09 | 901.87 | 26-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.636190E+09 | 926.53 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.575425E+09 | 951.51 | 08-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.611864E+09 | 1001.22 | 11-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.613054E+09 | 885.15 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.608413E+09 | 900.98 | 29-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.717254E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.554539E+09 | 726.97 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.638631E+09 | 1001.22 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.988559E+09 | 1439.51 | 18-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.872659E+09 | 1406.40 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.991223E+09 | 1420.49 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.866594E+09 | 911.12 | 03-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.916662E+09 | 974.59 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.912652E+09 | 972.70 | 23-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.871043E+09 | 1360.65 | 26-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.981377E+09 | 1410.11 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.891802E+09 | 1459.65 | 08-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.949324E+09 | 1547.81 | 11-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.972105E+09 | 1505.21 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.970603E+09 | 1521.79 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.111846E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.866594E+09 | 911.12 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.991223E+09 | 1547.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.628856E+09 | 913.96 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.558257E+09 | 908.68 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.636148E+09 | 788.92 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.557841E+09 | 539.58 | 03-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.593383E+09 | 607.16 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.590768E+09 | 607.64 | 23-JUN-07:10 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.561800E+09 | 838.60 | 26-JUL-07:10 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.631293E+09 | 873.99 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.572663E+09 | 909.32 | 08-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.606143E+09 | 977.53 | 11-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.622775E+09 | 992.33 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.618226E+09 | 987.10 | 29-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.717815E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.557841E+09 | 539.58 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.636148E+09 | 992.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.955723E+09 | 1376.94 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.855825E+09 | 1356.25 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.985841E+09 | 1401.53 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.868384E+09 | 921.38 | 03-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.923794E+09 | 1120.20 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.919924E+09 | 1132.50 | 23-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.876909E+09 | 1383.45 | 26-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.983764E+09 | 1420.23 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.889747E+09 | 1456.68 | 08-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.937235E+09 | 1539.03 | 11-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.942960E+09 | 1325.47 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.932431E+09 | 1441.64 | 29-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.110725E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.855825E+09 | 921.38 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.985841E+09 | 1539.03 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.624438E+09 | 933.02 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.554490E+09 | 915.38 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.638610E+09 | 946.99 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.559192E+09 | 726.49 | 03-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.594287E+09 | 765.89 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.591348E+09 | 767.66 | 23-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.565020E+09 | 901.40 | 26-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.636091E+09 | 926.11 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.575375E+09 | 951.13 | 08-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.611833E+09 | 1000.95 | 11-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.613038E+09 | 884.81 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.608397E+09 | 900.63 | 29-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.717212E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.554490E+09 | 726.49 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.638610E+09 | 1000.95 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.422891E+10 | 4400.15 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.383579E+10 | 4400.15 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.455537E+10 | 4400.15 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.407153E+10 | 4400.15 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.439214E+10 | 4400.15 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.436992E+10 | 4400.15 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.409376E+10 | 4400.15 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.455537E+10 | 4400.15 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.407153E+10 | 4400.15 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.422891E+10 | 4400.15 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.417862E+10 | 4400.15 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.409376E+10 | 4400.15 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.506756E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.383579E+10 | 4400.15 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.455537E+10 | 4400.15 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195358E+09 | 203.27 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.177198E+09 | 203.27 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.210439E+09 | 203.27 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.188088E+09 | 203.27 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.202899E+09 | 203.27 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.201872E+09 | 203.27 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.189115E+09 | 203.27 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.210439E+09 | 203.27 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.188088E+09 | 203.27 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.195358E+09 | 203.27 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.193035E+09 | 203.27 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.189115E+09 | 203.27 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.177198E+09 | 203.27 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.210439E+09 | 203.27 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195358E+09 | 203.27 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.177198E+09 | 203.27 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.210439E+09 | 203.27 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.188088E+09 | 203.27 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.202899E+09 | 203.27 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.201872E+09 | 203.27 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.189115E+09 | 203.27 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.210439E+09 | 203.27 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.188088E+09 | 203.27 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.195358E+09 | 203.27 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.193035E+09 | 203.27 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.189115E+09 | 203.27 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.177198E+09 | 203.27 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.210439E+09 | 203.27 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195358E+09 | 203.27 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.177198E+09 | 203.27 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.210439E+09 | 203.27 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.188088E+09 | 203.27 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.202899E+09 | 203.27 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.201872E+09 | 203.27 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.189115E+09 | 203.27 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.210439E+09 | 203.27 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.188088E+09 | 203.27 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.195358E+09 | 203.27 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.193035E+09 | 203.27 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.189115E+09 | 203.27 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.177198E+09 | 203.27 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.210439E+09 | 203.27 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.146017E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.132465E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.157676E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.140562E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.151846E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.151213E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.141196E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.157673E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.140562E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.146020E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.144381E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.141198E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.175081E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.132465E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.157676E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.131134E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.141604E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.126235E+11 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.136369E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.135800E+11 | 0.244214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.126804E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.141602E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.126235E+11 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.131136E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.129664E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.126806E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.157235E+12 | 0.289609E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.141604E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.131134E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.141604E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.126235E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.136369E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.135800E+11 | 0.244213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.126804E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.141602E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.126235E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.131136E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.129664E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.126806E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.157235E+12 | 0.289607E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.141604E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.131134E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.141604E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.126235E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.136369E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.135800E+11 | 0.244213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.126804E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.141602E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.126235E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.131136E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.129664E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.126806E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.157235E+12 | 0.289607E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.141604E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.991663E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1556.40 | 89777184.79 |
February | 0.136985E+10 | 0.874796E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1503035.15 | 95522033.01 |
March | 0.163685E+10 | 0.992601E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18691044.05 | 57717267.59 |
April | 0.145243E+10 | 0.867172E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72874061.78 | 3634679.94 |
May | 0.157338E+10 | 0.917194E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159366E+09 | 1135257.24 |
June | 0.156900E+10 | 0.913946E+09 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107702E+09 | 552677.98 |
July | 0.145680E+10 | 0.872144E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135976E+09 | 233795.01 |
August | 0.163685E+10 | 0.982718E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77280473.51 | 468741.43 |
September | 0.145243E+10 | 0.893141E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45846018.41 | 1155156.19 |
October | 0.150991E+10 | 0.951001E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23717197.25 | 4850027.51 |
November | 0.149516E+10 | 0.974541E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5088308.23 | 20277051.77 |
December | 0.145680E+10 | 0.973439E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105840.22 | 82876131.46 |
Annual Sum or Average | 0.181194E+11 | 0.112044E+11 | 0.363647E+11 | 0.648152E+09 | 0.358200E+09 | ||||
Minimum of Months | 0.136985E+10 | 0.867172E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1556.40 | 233795.01 |
Maximum of Months | 0.163685E+10 | 0.992601E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159366E+09 | 95522033.01 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.630088E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60806902.93 |
February | 0.882782E+09 | 0.559262E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 684769.06 | 64983374.86 |
March | 0.105485E+10 | 0.636675E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11269468.95 | 38672747.61 |
April | 0.936002E+09 | 0.558125E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46727628.63 | 2469729.02 |
May | 0.101394E+10 | 0.593799E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102874E+09 | 794725.13 |
June | 0.101113E+10 | 0.591316E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70775877.91 | 328630.22 |
July | 0.938820E+09 | 0.562625E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90499075.19 | 113975.26 |
August | 0.105485E+10 | 0.632284E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52110888.19 | 243636.68 |
September | 0.936002E+09 | 0.573360E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29917205.90 | 638697.72 |
October | 0.973041E+09 | 0.606881E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14787665.70 | 3363539.60 |
November | 0.963541E+09 | 0.623689E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3029715.95 | 13875685.64 |
December | 0.938820E+09 | 0.619314E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30510.55 | 54754912.07 |
Annual Sum or Average | 0.116768E+11 | 0.718742E+10 | 0.234348E+11 | 0.422707E+09 | 0.241047E+09 | ||||
Minimum of Months | 0.882782E+09 | 0.558125E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113975.26 |
Maximum of Months | 0.105485E+10 | 0.636675E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102874E+09 | 64983374.86 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.956192E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96847757.91 |
February | 0.136988E+10 | 0.856603E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 905294.68 | 0.106061E+09 |
March | 0.163688E+10 | 0.986775E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16007914.60 | 64441547.81 |
April | 0.145246E+10 | 0.868946E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70469403.95 | 4264452.03 |
May | 0.157341E+10 | 0.924556E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157961E+09 | 1169977.31 |
June | 0.156904E+10 | 0.921023E+09 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107429E+09 | 570137.64 |
July | 0.145684E+10 | 0.878265E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135543E+09 | 229450.60 |
August | 0.163688E+10 | 0.985265E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76665642.75 | 505598.90 |
September | 0.145246E+10 | 0.890707E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44298035.87 | 1131585.86 |
October | 0.150994E+10 | 0.938672E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21164062.80 | 5578059.50 |
November | 0.149520E+10 | 0.944894E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3816501.17 | 23684876.15 |
December | 0.145684E+10 | 0.932803E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17971.42 | 92360593.84 |
Annual Sum or Average | 0.181198E+11 | 0.110847E+11 | 0.363653E+11 | 0.634279E+09 | 0.396845E+09 | ||||
Minimum of Months | 0.136988E+10 | 0.856603E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229450.60 |
Maximum of Months | 0.163688E+10 | 0.986775E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157961E+09 | 0.106061E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.625516E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66955018.37 |
February | 0.882782E+09 | 0.555370E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 599158.75 | 75990675.97 |
March | 0.105485E+10 | 0.639362E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10310404.04 | 52167099.27 |
April | 0.936002E+09 | 0.559763E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44328777.20 | 5498051.34 |
May | 0.101394E+10 | 0.594957E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99161687.01 | 1373514.87 |
June | 0.101113E+10 | 0.592285E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66911009.16 | 849548.81 |
July | 0.938820E+09 | 0.566230E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82483673.75 | 410632.51 |
August | 0.105485E+10 | 0.637565E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45925920.77 | 813179.63 |
September | 0.936002E+09 | 0.576383E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27430991.24 | 1665074.35 |
October | 0.973041E+09 | 0.612947E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14133780.84 | 4354013.81 |
November | 0.963541E+09 | 0.613583E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2601482.30 | 16629768.87 |
December | 0.938820E+09 | 0.609168E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11870.58 | 66466846.87 |
Annual Sum or Average | 0.116768E+11 | 0.718313E+10 | 0.234347E+11 | 0.393899E+09 | 0.293173E+09 | ||||
Minimum of Months | 0.882782E+09 | 0.555370E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410632.51 |
Maximum of Months | 0.105485E+10 | 0.639362E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99161687.01 | 75990675.97 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.988661E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 329674.89 | 0.159371E+09 |
February | 0.136985E+10 | 0.872759E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7164611.17 | 0.178843E+09 |
March | 0.163685E+10 | 0.991258E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44661920.75 | 0.122572E+09 |
April | 0.145243E+10 | 0.866610E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165508E+09 | 10905927.71 |
May | 0.157338E+10 | 0.916693E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351080E+09 | 2765882.08 |
June | 0.156900E+10 | 0.912693E+09 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236951E+09 | 2197547.92 |
July | 0.145680E+10 | 0.871095E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293811E+09 | 830611.92 |
August | 0.163685E+10 | 0.981439E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168471E+09 | 2020200.49 |
September | 0.145243E+10 | 0.891850E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99305629.88 | 2896607.76 |
October | 0.150991E+10 | 0.949419E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54478418.39 | 10712666.98 |
November | 0.149516E+10 | 0.972194E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14627413.54 | 38485206.30 |
December | 0.145680E+10 | 0.970695E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2430657.89 | 0.147049E+09 |
Annual Sum or Average | 0.181194E+11 | 0.111854E+11 | 0.363647E+11 | 0.143882E+10 | 0.678649E+09 | ||||
Minimum of Months | 0.136985E+10 | 0.866610E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 329674.89 | 830611.92 |
Maximum of Months | 0.163685E+10 | 0.991258E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351080E+09 | 0.178843E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.628877E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18753.58 | 0.120377E+09 |
February | 0.649041E+09 | 0.558335E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1547040.73 | 0.136649E+09 |
March | 0.773965E+09 | 0.636163E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23598796.65 | 92981165.74 |
April | 0.688021E+09 | 0.557855E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101985E+09 | 9493793.79 |
May | 0.744847E+09 | 0.593402E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225618E+09 | 2226685.52 |
June | 0.742030E+09 | 0.590789E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153950E+09 | 1638909.94 |
July | 0.690839E+09 | 0.561868E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191039E+09 | 592152.31 |
August | 0.773965E+09 | 0.631353E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108354E+09 | 1498299.44 |
September | 0.688021E+09 | 0.572691E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62808799.38 | 2108731.00 |
October | 0.715730E+09 | 0.606162E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32170308.76 | 8342442.16 |
November | 0.708685E+09 | 0.622803E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6631261.13 | 29809032.97 |
December | 0.690839E+09 | 0.618252E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 525909.53 | 0.110700E+09 |
Annual Sum or Average | 0.858171E+10 | 0.717855E+10 | 0.234348E+11 | 0.908246E+09 | 0.516417E+09 | ||||
Minimum of Months | 0.649041E+09 | 0.557855E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18753.58 | 592152.31 |
Maximum of Months | 0.773965E+09 | 0.636163E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225618E+09 | 0.136649E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.955737E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206946E+09 |
February | 0.136988E+10 | 0.855869E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1853428.16 | 0.230392E+09 |
March | 0.163688E+10 | 0.985894E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34849517.20 | 0.149083E+09 |
April | 0.145246E+10 | 0.868411E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157484E+09 | 13393876.43 |
May | 0.157341E+10 | 0.923873E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348414E+09 | 2908314.27 |
June | 0.156904E+10 | 0.919976E+09 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236653E+09 | 2205600.85 |
July | 0.145684E+10 | 0.877049E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292956E+09 | 842649.10 |
August | 0.163688E+10 | 0.983858E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165996E+09 | 2173357.38 |
September | 0.145246E+10 | 0.889791E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94862048.22 | 3322950.35 |
October | 0.150994E+10 | 0.937263E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46191054.31 | 13411278.57 |
November | 0.149520E+10 | 0.942976E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8004903.52 | 52772797.55 |
December | 0.145684E+10 | 0.932441E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29354.01 | 0.198707E+09 |
Annual Sum or Average | 0.181198E+11 | 0.110731E+11 | 0.363653E+11 | 0.138729E+10 | 0.876159E+09 | ||||
Minimum of Months | 0.136988E+10 | 0.855869E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 842649.10 |
Maximum of Months | 0.163688E+10 | 0.985894E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348414E+09 | 0.230392E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.624474E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5135.24 | 0.123167E+09 |
February | 0.882782E+09 | 0.554539E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1770803.52 | 0.140140E+09 |
March | 0.105485E+10 | 0.638631E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24539519.01 | 0.101861E+09 |
April | 0.936002E+09 | 0.559203E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102025E+09 | 11042380.66 |
May | 0.101394E+10 | 0.594306E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223390E+09 | 2970597.96 |
June | 0.101113E+10 | 0.591377E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151895E+09 | 2068042.27 |
July | 0.938820E+09 | 0.565060E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188206E+09 | 768020.35 |
August | 0.105485E+10 | 0.636190E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106521E+09 | 1868519.53 |
September | 0.936002E+09 | 0.575425E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61769268.62 | 2895324.72 |
October | 0.973041E+09 | 0.611864E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32856497.47 | 8408381.83 |
November | 0.963541E+09 | 0.613054E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7057939.90 | 30002079.57 |
December | 0.938820E+09 | 0.608413E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 432553.67 | 0.113451E+09 |
Annual Sum or Average | 0.116768E+11 | 0.717254E+10 | 0.234347E+11 | 0.900470E+09 | 0.538642E+09 | ||||
Minimum of Months | 0.882782E+09 | 0.554539E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5135.24 | 768020.35 |
Maximum of Months | 0.105485E+10 | 0.638631E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223390E+09 | 0.140140E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.988559E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 641972.38 | 0.171693E+09 |
February | 0.136985E+10 | 0.872659E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10201549.51 | 0.200820E+09 |
March | 0.163685E+10 | 0.991223E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52363834.07 | 0.148030E+09 |
April | 0.145243E+10 | 0.866594E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196829E+09 | 13947340.61 |
May | 0.157338E+10 | 0.916662E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423740E+09 | 3722354.75 |
June | 0.156900E+10 | 0.912652E+09 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286889E+09 | 2829662.11 |
July | 0.145680E+10 | 0.871043E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354390E+09 | 1188162.00 |
August | 0.163685E+10 | 0.981377E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202225E+09 | 2607254.94 |
September | 0.145243E+10 | 0.891802E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118588E+09 | 3760145.27 |
October | 0.150991E+10 | 0.949324E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65347668.08 | 12876386.56 |
November | 0.149516E+10 | 0.972105E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19518175.17 | 42842814.27 |
December | 0.145680E+10 | 0.970603E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4593431.41 | 0.159339E+09 |
Annual Sum or Average | 0.181194E+11 | 0.111846E+11 | 0.363647E+11 | 0.173533E+10 | 0.763656E+09 | ||||
Minimum of Months | 0.136985E+10 | 0.866594E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 641972.38 | 1188162.00 |
Maximum of Months | 0.163685E+10 | 0.991223E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423740E+09 | 0.200820E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.628856E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126466.81 | 0.127926E+09 |
February | 0.882782E+09 | 0.558257E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2602022.04 | 0.153880E+09 |
March | 0.105485E+10 | 0.636148E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28833947.33 | 0.112728E+09 |
April | 0.936002E+09 | 0.557841E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124729E+09 | 12113822.06 |
May | 0.101394E+10 | 0.593383E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275141E+09 | 2983614.76 |
June | 0.101113E+10 | 0.590768E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188285E+09 | 2058122.45 |
July | 0.938820E+09 | 0.561800E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232845E+09 | 845234.73 |
August | 0.105485E+10 | 0.631293E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132029E+09 | 1907691.55 |
September | 0.936002E+09 | 0.572663E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76730588.99 | 2710167.68 |
October | 0.973041E+09 | 0.606143E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39564193.33 | 10066564.62 |
November | 0.963541E+09 | 0.622775E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9102969.24 | 33672263.08 |
December | 0.938820E+09 | 0.618226E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1249803.11 | 0.119577E+09 |
Annual Sum or Average | 0.116768E+11 | 0.717815E+10 | 0.234348E+11 | 0.111124E+10 | 0.580468E+09 | ||||
Minimum of Months | 0.882782E+09 | 0.557841E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126466.81 | 845234.73 |
Maximum of Months | 0.105485E+10 | 0.636148E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275141E+09 | 0.153880E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.955723E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232570E+09 |
February | 0.136988E+10 | 0.855825E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2075072.92 | 0.266724E+09 |
March | 0.163688E+10 | 0.985841E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41702681.85 | 0.181317E+09 |
April | 0.145246E+10 | 0.868384E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190018E+09 | 17127640.64 |
May | 0.157341E+10 | 0.923794E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421062E+09 | 3915260.80 |
June | 0.156904E+10 | 0.919924E+09 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286571E+09 | 2842257.49 |
July | 0.145684E+10 | 0.876909E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353452E+09 | 1211649.14 |
August | 0.163688E+10 | 0.983764E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199673E+09 | 2804664.03 |
September | 0.145246E+10 | 0.889747E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114318E+09 | 4347687.79 |
October | 0.150994E+10 | 0.937235E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56462903.06 | 16358056.09 |
November | 0.149520E+10 | 0.942960E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9881957.04 | 62003863.00 |
December | 0.145684E+10 | 0.932431E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24834.81 | 0.225218E+09 |
Annual Sum or Average | 0.181198E+11 | 0.110725E+11 | 0.363653E+11 | 0.167524E+10 | 0.101644E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.855825E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1211649.14 |
Maximum of Months | 0.163688E+10 | 0.985841E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421062E+09 | 0.266724E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.624438E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37752.49 | 0.138544E+09 |
February | 0.882782E+09 | 0.554490E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2399676.88 | 0.162037E+09 |
March | 0.105485E+10 | 0.638610E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29381271.96 | 0.123941E+09 |
April | 0.936002E+09 | 0.559192E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123846E+09 | 14003001.33 |
May | 0.101394E+10 | 0.594287E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272063E+09 | 3914784.17 |
June | 0.101113E+10 | 0.591348E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185265E+09 | 2500734.60 |
July | 0.938820E+09 | 0.565020E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228531E+09 | 1105349.29 |
August | 0.105485E+10 | 0.636091E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128755E+09 | 2395783.27 |
September | 0.936002E+09 | 0.575375E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74636303.15 | 3771286.64 |
October | 0.973041E+09 | 0.611833E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39958555.66 | 10291481.59 |
November | 0.963541E+09 | 0.613038E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8935606.88 | 34559269.07 |
December | 0.938820E+09 | 0.608397E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 836218.56 | 0.127933E+09 |
Annual Sum or Average | 0.116768E+11 | 0.717212E+10 | 0.234347E+11 | 0.109465E+10 | 0.624996E+09 | ||||
Minimum of Months | 0.882782E+09 | 0.554490E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37752.49 | 1105349.29 |
Maximum of Months | 0.105485E+10 | 0.638610E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272063E+09 | 0.162037E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.422891E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.383579E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.455537E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.407153E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.439214E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.436992E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.409376E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.455537E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.407153E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.422891E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.417862E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.409376E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.506756E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.383579E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.455537E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.195358E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.177198E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.210439E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.188088E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.202899E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.201872E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.189115E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.188088E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.195358E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.193035E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.189115E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.177198E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.195358E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.177198E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.210439E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.188088E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.202899E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.201872E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.189115E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.188088E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.195358E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.193035E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.189115E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.177198E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.195358E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.177198E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.210439E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.188088E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.202899E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.201872E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.189115E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.188088E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.195358E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.193035E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.189115E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.177198E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192011E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020310.50 | 0.207790E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27930070.88 | 0.132668E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124413E+09 | 11413252.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277365E+09 | 3248255.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188808E+09 | 1752471.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234709E+09 | 769528.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128325E+09 | 1375170.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75613411.65 | 2252418.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38739994.20 | 11900043.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6467255.29 | 45897623.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.76 | 0.179457E+09 |
Annual Sum or Average | 0.110339E+10 | 0.790534E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769528.56 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277365E+09 | 0.207790E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311706E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3443449.91 | 0.343926E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53326537.64 | 0.230388E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230750E+09 | 21588240.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505666E+09 | 5576559.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342043E+09 | 3543201.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429417E+09 | 1439419.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235169E+09 | 2725660.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136785E+09 | 3839225.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70941230.33 | 21263418.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13466450.03 | 76489797.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727318.97 | 0.290774E+09 |
Annual Sum or Average | 0.202173E+10 | 0.131326E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1439419.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505666E+09 | 0.343926E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301256E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549998.90 | 0.349800E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41080157.35 | 0.244560E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222457E+09 | 21203034.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531916E+09 | 5888382.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366168E+09 | 3305315.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446658E+09 | 1325387.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242830E+09 | 4305158.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136738E+09 | 4088949.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65907785.33 | 20242375.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10044403.62 | 73801748.10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 959662.12 | 0.277013E+09 |
Annual Sum or Average | 0.206531E+10 | 0.130679E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1325387.83 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531916E+09 | 0.349800E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 15605.75 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 15605.75 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 15605.75 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 15605.75 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 15605.75 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 15605.75 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 15605.75 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 15605.75 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 15605.75 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 15605.75 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 15605.75 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 15605.75 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 15605.75 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 15605.75 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 14015.06 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 14015.06 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 14015.06 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 14015.06 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 14015.06 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 14015.06 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 14015.06 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 14015.06 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 14015.06 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 14015.06 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 14015.06 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 14015.06 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 14015.06 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 14015.06 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 14015.06 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 14015.06 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 14015.06 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 14015.06 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 14015.06 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 14015.06 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 14015.06 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 14015.06 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 14015.06 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 14015.06 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 14015.06 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 14015.06 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 14015.06 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 14015.06 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 14015.06 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 14015.06 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 14015.06 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 14015.06 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 14015.06 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 14015.06 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 14015.06 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 14015.06 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 14015.06 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 14015.06 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 14015.06 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 14015.06 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 14015.06 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 14015.06 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1444.18 | 18-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 08-JAN-15:00 | 231.35 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1411.50 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.28 | 19-FEB-15:05 | 313.47 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1425.43 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 198.65 | 26-MAR-15:00 | 687.89 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 921.15 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.97 | 15-APR-17:01 | 97.68 | 22-APR-18:50 |
May | 2010.79 | 01-MAY-09:09 | 980.59 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 623.98 | 28-MAY-14:43 | 46.63 | 13-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 978.79 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.06 | 03-JUN-17:10 | 49.55 | 18-JUN-04:50 |
July | 2010.79 | 03-JUL-09:09 | 1366.21 | 26-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 307.66 | 02-JUL-11:46 | 39.54 | 19-JUL-02:50 |
August | 2010.79 | 01-AUG-09:09 | 1414.94 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.27 | 06-AUG-13:46 | 46.50 | 15-AUG-23:50 |
September | 2010.79 | 01-SEP-09:09 | 1463.78 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.81 | 24-SEP-14:25 | 27.57 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 1550.69 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.46 | 15-OCT-12:10 | 98.14 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1509.24 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.02 | 12-NOV-14:20 | 161.65 | 28-NOV-05:10 |
December | 2010.79 | 01-DEC-10:09 | 1525.22 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 | 24-DEC-14:10 | 357.50 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 921.15 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 27.57 | |||||
Maximum of Months | 2010.79 | 1550.69 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 623.98 | 687.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 920.00 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 149.02 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 914.92 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 | 19-FEB-15:05 | 199.13 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 796.99 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.07 | 26-MAR-14:40 | 455.16 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 539.58 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.43 | 15-APR-17:04 | 62.83 | 22-APR-18:50 |
May | 1295.83 | 01-MAY-09:09 | 611.46 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 413.40 | 28-MAY-14:43 | 31.84 | 15-MAY-03:30 |
June | 1295.83 | 01-JUN-09:09 | 611.86 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.17 | 17-JUN-20:30 | 30.18 | 18-JUN-04:50 |
July | 1295.83 | 03-JUL-09:09 | 846.00 | 26-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.55 | 02-JUL-11:44 | 22.23 | 19-JUL-02:50 |
August | 1295.83 | 01-AUG-09:09 | 880.12 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.97 | 06-AUG-14:25 | 27.27 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 914.52 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.37 | 24-SEP-14:25 | 16.34 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 981.50 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.41 | 15-OCT-13:24 | 60.96 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 996.14 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.32 | 12-NOV-14:20 | 104.31 | 28-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 991.12 | 29-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.12 | 24-DEC-14:10 | 222.34 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | |||||
Maximum of Months | 1295.83 | 996.14 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 413.40 | 455.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1381.97 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 252.85 | 22-JAN-14:23 |
February | 2010.83 | 01-FEB-10:09 | 1361.79 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 | 21-FEB-15:00 | 307.52 | 09-FEB-22:10 |
March | 2010.83 | 01-MAR-10:09 | 1406.67 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 159.31 | 26-MAR-15:16 | 762.93 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 930.72 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.64 | 15-APR-17:04 | 103.32 | 22-APR-18:50 |
May | 2010.83 | 01-MAY-09:09 | 1129.89 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 625.24 | 28-MAY-14:43 | 45.93 | 15-MAY-03:30 |
June | 2010.83 | 01-JUN-09:09 | 1142.10 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.50 | 03-JUN-17:10 | 50.51 | 18-JUN-04:50 |
July | 2010.83 | 03-JUL-09:09 | 1388.77 | 26-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.76 | 02-JUL-11:46 | 39.14 | 19-JUL-02:50 |
August | 2010.83 | 01-AUG-09:09 | 1424.97 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.70 | 06-AUG-13:44 | 48.34 | 15-AUG-23:50 |
September | 2010.83 | 01-SEP-09:09 | 1460.84 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.53 | 24-SEP-14:25 | 26.77 | 08-SEP-22:10 |
October | 2010.83 | 02-OCT-09:09 | 1541.98 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.87 | 15-OCT-12:44 | 97.55 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1331.80 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.95 | 12-NOV-13:53 | 173.43 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1445.98 | 29-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 | 28-DEC-14:00 | 415.84 | 31-DEC-14:30 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 930.72 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.77 | |||||
Maximum of Months | 2010.83 | 1541.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 625.24 | 762.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 938.54 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 165.19 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 921.43 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.66 | 21-FEB-15:00 | 233.60 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 952.24 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.27 | 26-MAR-13:55 | 623.16 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 736.94 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.58 | 15-APR-17:10 | 109.13 | 22-APR-18:10 |
May | 1295.83 | 01-MAY-09:09 | 776.19 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 414.77 | 28-MAY-14:43 | 50.58 | 15-MAY-02:50 |
June | 1295.83 | 01-JUN-09:09 | 777.91 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.45 | 17-JUN-20:27 | 49.87 | 18-JUN-04:50 |
July | 1295.83 | 03-JUL-09:09 | 907.86 | 26-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.63 | 02-JUL-11:44 | 42.77 | 19-JUL-02:50 |
August | 1295.83 | 01-AUG-09:09 | 931.89 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.19 | 06-AUG-13:44 | 51.59 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 956.21 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.79 | 24-SEP-14:25 | 26.49 | 08-SEP-22:10 |
October | 1295.83 | 02-OCT-09:09 | 1004.63 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.01 | 15-OCT-12:44 | 80.39 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 890.94 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 12-NOV-14:14 | 128.51 | 28-NOV-05:10 |
December | 1295.83 | 01-DEC-10:09 | 906.48 | 29-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28-DEC-14:00 | 283.44 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 736.94 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.49 | |||||
Maximum of Months | 1295.83 | 1004.63 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 414.77 | 623.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1440.15 | 18-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.88 | 08-JAN-14:33 | 425.27 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1407.11 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.69 | 19-FEB-15:00 | 614.35 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1421.12 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 505.49 | 26-MAR-14:40 | 1280.49 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 911.44 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 790.22 | 15-APR-17:01 | 205.48 | 22-APR-18:03 |
May | 2010.79 | 01-MAY-09:09 | 974.82 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.25 | 28-MAY-14:57 | 101.89 | 13-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 972.93 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.11 | 03-JUN-17:02 | 112.14 | 18-JUN-04:53 |
July | 2010.79 | 03-JUL-09:09 | 1361.46 | 26-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 686.74 | 02-JUL-11:44 | 99.14 | 19-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 1410.82 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.83 | 06-AUG-14:25 | 129.97 | 15-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1460.27 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.84 | 24-SEP-14:50 | 52.01 | 08-SEP-22:20 |
October | 2010.79 | 02-OCT-09:09 | 1548.25 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 470.39 | 15-OCT-12:10 | 194.18 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1505.63 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.07 | 12-NOV-14:10 | 301.99 | 28-NOV-04:55 |
December | 2010.79 | 01-DEC-10:09 | 1522.26 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 166.96 | 24-DEC-14:00 | 650.61 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 911.44 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 43.88 | 52.01 | |||||
Maximum of Months | 2010.79 | 1548.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.25 | 1280.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 914.37 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 08-JAN-15:10 | 283.28 | 15-JAN-17:00 |
February | 1239.33 | 01-FEB-08:09 | 909.13 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.53 | 19-FEB-15:00 | 409.46 | 09-FEB-22:10 |
March | 1239.33 | 01-MAR-08:09 | 789.41 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 260.78 | 26-MAR-15:00 | 937.80 | 24-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 539.58 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 522.49 | 15-APR-17:06 | 170.25 | 22-APR-17:55 |
May | 1239.33 | 01-MAY-07:10 | 607.35 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 929.50 | 28-MAY-14:57 | 83.12 | 15-MAY-03:00 |
June | 1239.33 | 01-JUN-07:10 | 607.84 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.96 | 17-JUN-20:27 | 78.73 | 18-JUN-04:05 |
July | 1239.33 | 03-JUL-07:10 | 839.16 | 26-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.12 | 02-JUL-11:44 | 66.18 | 19-JUL-02:55 |
August | 1239.33 | 01-AUG-07:10 | 874.48 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.61 | 06-AUG-14:23 | 91.40 | 15-AUG-23:53 |
September | 1239.33 | 01-SEP-07:10 | 909.75 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.14 | 24-SEP-13:53 | 35.34 | 08-SEP-22:20 |
October | 1239.33 | 02-OCT-07:10 | 977.83 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.80 | 15-OCT-13:24 | 131.08 | 12-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 992.56 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.86 | 12-NOV-14:10 | 213.21 | 28-NOV-04:55 |
December | 1239.33 | 01-DEC-08:09 | 987.38 | 29-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.11 | 24-DEC-14:10 | 436.86 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 35.34 | |||||
Maximum of Months | 1239.33 | 992.56 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 929.50 | 937.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1377.66 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 570.26 | 22-JAN-14:30 |
February | 2010.83 | 01-FEB-10:09 | 1357.03 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 21-FEB-15:00 | 650.91 | 18-FEB-05:51 |
March | 2010.83 | 01-MAR-10:09 | 1402.20 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 330.80 | 26-MAR-14:58 | 1519.68 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 921.68 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 783.96 | 15-APR-17:07 | 236.52 | 22-APR-17:55 |
May | 2010.83 | 01-MAY-09:09 | 1121.46 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.25 | 28-MAY-14:57 | 108.45 | 15-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 1133.73 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 646.41 | 03-JUN-17:02 | 112.69 | 18-JUN-04:53 |
July | 2010.83 | 03-JUL-09:09 | 1384.22 | 26-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 687.35 | 02-JUL-11:46 | 99.26 | 19-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 1420.93 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.18 | 06-AUG-13:46 | 135.23 | 15-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1457.30 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.59 | 24-SEP-14:33 | 53.35 | 08-SEP-22:20 |
October | 2010.83 | 02-OCT-09:09 | 1539.48 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.04 | 15-OCT-13:00 | 201.60 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1326.06 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.60 | 12-NOV-14:05 | 367.13 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1442.17 | 29-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 28-DEC-14:00 | 957.89 | 31-DEC-15:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 921.68 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | |||||
Maximum of Months | 2010.83 | 1539.48 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.25 | 1519.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 933.42 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 08-JAN-13:53 | 300.90 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 915.82 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.79 | 19-FEB-14:02 | 428.60 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 947.35 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 266.40 | 26-MAR-13:13 | 1039.56 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 726.97 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 511.39 | 15-APR-17:10 | 167.79 | 22-APR-17:55 |
May | 1295.83 | 01-MAY-09:09 | 766.61 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 929.50 | 28-MAY-15:00 | 113.09 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 768.38 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.86 | 17-JUN-20:27 | 95.07 | 18-JUN-02:33 |
July | 1295.83 | 03-JUL-09:09 | 901.87 | 26-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 459.10 | 02-JUL-11:44 | 71.28 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 926.53 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.72 | 06-AUG-13:44 | 98.31 | 15-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 951.51 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 246.85 | 24-SEP-14:33 | 39.12 | 08-SEP-22:10 |
October | 1295.83 | 02-OCT-09:09 | 1001.22 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.08 | 15-OCT-12:10 | 137.43 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 885.15 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.03 | 12-NOV-13:10 | 225.19 | 28-NOV-04:55 |
December | 1295.83 | 01-DEC-10:09 | 900.98 | 29-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.92 | 24-DEC-13:55 | 459.09 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 726.97 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 | 39.12 | |||||
Maximum of Months | 1295.83 | 1001.22 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 929.50 | 1039.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1439.51 | 18-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 79.74 | 08-JAN-14:33 | 454.92 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1406.40 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 262.62 | 19-FEB-14:53 | 710.31 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1420.49 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 587.69 | 26-MAR-14:55 | 1503.42 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 911.12 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 965.32 | 15-APR-17:07 | 238.48 | 22-APR-18:03 |
May | 2010.79 | 01-MAY-09:09 | 974.59 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1730.09 | 28-MAY-14:34 | 134.89 | 15-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 972.70 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 784.03 | 17-JUN-20:27 | 147.07 | 18-JUN-04:05 |
July | 2010.79 | 03-JUL-09:09 | 1360.65 | 26-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 847.66 | 02-JUL-11:44 | 117.72 | 19-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 1410.11 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.11 | 06-AUG-13:46 | 163.62 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1459.65 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 456.75 | 24-SEP-14:25 | 61.11 | 08-SEP-22:10 |
October | 2010.79 | 02-OCT-09:09 | 1547.81 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 579.09 | 15-OCT-11:52 | 226.28 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1505.21 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.37 | 12-NOV-14:00 | 341.18 | 29-NOV-24:00 |
December | 2010.79 | 01-DEC-10:09 | 1521.79 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 269.16 | 24-DEC-14:00 | 732.99 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 911.12 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 79.74 | 61.11 | |||||
Maximum of Months | 2010.79 | 1547.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1730.09 | 1503.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 913.96 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 | 08-JAN-14:37 | 302.59 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 908.68 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.29 | 19-FEB-15:00 | 471.68 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 788.92 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 307.47 | 26-MAR-15:26 | 1099.00 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 539.58 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 642.69 | 15-APR-17:06 | 195.57 | 22-APR-17:55 |
May | 1295.83 | 01-MAY-09:09 | 607.16 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.77 | 28-MAY-14:34 | 110.32 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 607.64 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 522.96 | 17-JUN-20:27 | 101.75 | 18-JUN-02:45 |
July | 1295.83 | 03-JUL-09:09 | 838.60 | 26-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 559.79 | 02-JUL-11:44 | 78.27 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 873.99 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.10 | 06-AUG-13:44 | 114.24 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 909.32 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.27 | 24-SEP-14:25 | 41.08 | 08-SEP-22:10 |
October | 1295.83 | 02-OCT-09:09 | 977.53 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.99 | 15-OCT-12:56 | 152.48 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 992.33 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.02 | 12-NOV-14:00 | 242.82 | 29-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 987.10 | 29-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 121.04 | 24-DEC-14:10 | 490.87 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 | 41.08 | |||||
Maximum of Months | 1295.83 | 992.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.77 | 1099.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1376.94 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 654.92 | 22-JAN-14:50 |
February | 2010.83 | 01-FEB-10:09 | 1356.25 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.28 | 21-FEB-15:00 | 737.83 | 18-FEB-05:51 |
March | 2010.83 | 01-MAR-10:09 | 1401.53 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 415.65 | 26-MAR-14:45 | 1789.98 | 24-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 921.38 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 957.53 | 15-APR-17:06 | 276.14 | 22-APR-17:55 |
May | 2010.83 | 01-MAY-09:09 | 1120.20 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1731.91 | 28-MAY-14:34 | 147.94 | 15-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 1132.50 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 783.81 | 17-JUN-20:27 | 148.04 | 18-JUN-04:05 |
July | 2010.83 | 03-JUL-09:09 | 1383.45 | 26-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 849.03 | 02-JUL-11:44 | 117.94 | 19-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 1420.23 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 554.78 | 06-AUG-13:46 | 169.78 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1456.68 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 469.90 | 24-SEP-14:25 | 62.86 | 08-SEP-22:10 |
October | 2010.83 | 02-OCT-09:09 | 1539.03 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.90 | 15-OCT-13:00 | 235.76 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1325.47 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.93 | 13-NOV-14:00 | 433.45 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1441.64 | 29-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 28-DEC-14:00 | 1070.22 | 31-DEC-14:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 921.38 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.86 | |||||
Maximum of Months | 2010.83 | 1539.03 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1731.91 | 1789.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 933.02 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 08-JAN-13:53 | 335.04 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 915.38 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.34 | 19-FEB-13:32 | 498.08 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 946.99 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 309.18 | 26-MAR-13:10 | 1224.38 | 24-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 726.49 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 628.82 | 15-APR-17:10 | 197.00 | 22-APR-17:55 |
May | 1295.83 | 01-MAY-09:09 | 765.89 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1146.62 | 28-MAY-14:34 | 142.21 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 767.66 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 525.96 | 17-JUN-20:27 | 121.44 | 18-JUN-02:33 |
July | 1295.83 | 03-JUL-09:09 | 901.40 | 26-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 566.67 | 02-JUL-11:44 | 85.15 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 926.11 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.73 | 06-AUG-13:44 | 123.01 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 951.13 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 305.09 | 24-SEP-14:25 | 46.77 | 08-SEP-22:10 |
October | 1295.83 | 02-OCT-09:09 | 1000.95 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.15 | 15-OCT-11:52 | 161.86 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 884.81 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.07 | 12-NOV-12:52 | 265.11 | 29-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 900.63 | 29-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.37 | 24-DEC-13:55 | 526.87 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 726.49 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 46.77 | |||||
Maximum of Months | 1295.83 | 1000.95 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1146.62 | 1224.38 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 4400.15 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 4400.15 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 4400.15 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 4400.15 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 4400.15 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 4400.15 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 4400.15 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 4400.15 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 4400.15 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 4400.15 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 4400.15 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 4400.15 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 4400.15 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 4400.15 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 203.27 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 203.27 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 203.27 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 203.27 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 203.27 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 203.27 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 203.27 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 203.27 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 203.27 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 203.27 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 203.27 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 203.27 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 203.27 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 203.27 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 203.27 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 203.27 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 203.27 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 203.27 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 203.27 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 203.27 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 203.27 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 203.27 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 203.27 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 203.27 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 203.27 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 203.27 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 203.27 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 203.27 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 203.27 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 203.27 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 203.27 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 203.27 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 203.27 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 203.27 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 203.27 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 203.27 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 203.27 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 203.27 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 203.27 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 203.27 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 203.27 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 203.27 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 466.76 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.40 | 19-FEB-14:43 | 681.32 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.73 | 26-MAR-15:00 | 1477.19 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.63 | 15-APR-17:01 | 207.00 | 22-APR-18:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1183.93 | 28-MAY-15:00 | 90.33 | 13-MAY-03:02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.64 | 03-JUN-17:02 | 103.85 | 18-JUN-04:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.75 | 02-JUL-12:00 | 81.68 | 19-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.84 | 06-AUG-14:00 | 95.99 | 15-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.06 | 24-SEP-14:10 | 44.00 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.73 | 15-OCT-12:32 | 189.39 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.93 | 12-NOV-14:00 | 347.48 | 28-NOV-05:13 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 28-DEC-14:00 | 742.12 | 29-DEC-24:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1183.93 | 1477.19 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 763.50 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.07 | 19-FEB-15:00 | 1167.91 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.16 | 26-MAR-14:43 | 2487.73 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1240.88 | 15-APR-17:01 | 377.08 | 22-APR-18:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2151.45 | 28-MAY-14:40 | 162.02 | 13-MAY-03:02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 997.17 | 03-JUN-17:02 | 184.61 | 18-JUN-04:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.06 | 02-JUL-12:00 | 152.34 | 19-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.57 | 06-AUG-14:00 | 178.36 | 15-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.62 | 24-SEP-14:20 | 73.45 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.49 | 15-OCT-12:30 | 327.75 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.91 | 12-NOV-13:51 | 570.72 | 28-NOV-04:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.34 | 24-DEC-14:10 | 1234.87 | 29-DEC-24:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.45 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2151.45 | 2487.73 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 740.38 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.07 | 19-FEB-15:00 | 1193.54 | 09-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.31 | 26-MAR-15:00 | 2513.11 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1240.57 | 15-APR-17:01 | 293.81 | 22-APR-18:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2086.06 | 28-MAY-15:00 | 172.15 | 13-MAY-03:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1036.88 | 03-JUN-17:10 | 187.45 | 18-JUN-04:05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 989.99 | 02-JUL-10:51 | 147.87 | 19-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.56 | 06-AUG-08:52 | 238.28 | 15-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.52 | 24-SEP-14:10 | 61.05 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.21 | 15-OCT-11:52 | 331.85 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.30 | 12-NOV-13:41 | 533.78 | 28-NOV-04:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.09 | 24-DEC-14:10 | 1168.20 | 29-DEC-24:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.05 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2086.06 | 2513.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 108356.52 | 23-JAN-00:31 | 0.00 | 5385.15 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 113920.62 | 20-FEB-13:52 | 4488.06 | 4334.93 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 104026.36 | 20-MAR-00:22 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 113181.13 | 09-APR-18:50 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 103890.00 | 29-MAY-06:03 | 2692.84 | 2600.96 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98937.40 | 04-JUN-20:56 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 86109.32 | 30-JUL-08:30 | 2692.84 | 2600.96 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85733.87 | 06-AUG-03:47 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86732.46 | 03-SEP-08:20 | 2692.84 | 2600.96 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 102945.37 | 15-OCT-11:26 | 4488.06 | 4334.93 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 105772.27 | 23-NOV-23:52 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 112605.44 | 25-DEC-09:02 | 4488.06 | 4334.93 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 85733.87 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 113920.62 | 4488.06 | 5385.15 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 75448.98 | 14-JAN-05:11 | 0.00 | 5373.60 | 44532.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83269.86 | 25-FEB-05:12 | 0.00 | 5373.60 | 44532.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 87856.02 | 15-MAR-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86608.10 | 24-APR-05:03 | 16122.38 | 5373.60 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86781.62 | 13-MAY-04:12 | 0.00 | 5373.60 | 44532.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84278.12 | 01-JUN-05:02 | 16122.38 | 5373.60 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85796.20 | 05-JUL-05:04 | 16122.38 | 5373.60 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86408.82 | 14-AUG-05:04 | 11285.67 | 3761.52 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 87638.74 | 09-SEP-03:01 | 0.00 | 5373.60 | 44532.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95389.85 | 13-OCT-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 88636.61 | 09-NOV-04:02 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83396.00 | 29-DEC-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 75448.98 | 0.00 | 3761.52 | 44532.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95389.85 | 16122.38 | 5373.60 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 62957.55 | 14-JAN-06:03 | 4836.72 | 1612.08 | 22942.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 75686.22 | 25-FEB-05:11 | 0.00 | 5373.60 | 44532.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85320.84 | 30-MAR-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89338.79 | 12-APR-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83068.07 | 13-MAY-03:01 | 0.00 | 5373.60 | 44532.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75812.89 | 01-JUN-03:01 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85012.01 | 19-JUL-03:01 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75187.32 | 22-AUG-03:01 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82641.54 | 09-SEP-05:02 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88180.56 | 19-OCT-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79428.55 | 09-NOV-05:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 69373.97 | 29-DEC-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 62957.55 | 0.00 | 1612.08 | 22942.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89338.79 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 31316.64 | 26-JAN-16:50 | 15316.26 | 14015.06 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 63791.68 | 25-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88249.26 | 14-MAR-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84415.21 | 12-APR-03:01 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81055.37 | 23-MAY-03:01 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82108.24 | 28-JUN-03:01 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82328.35 | 25-JUL-03:01 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81706.77 | 22-AUG-03:01 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85560.30 | 09-SEP-05:02 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84680.78 | 12-OCT-04:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 71604.59 | 09-NOV-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33350.52 | 01-DEC-16:30 | 15316.26 | 14015.06 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 31316.64 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88249.26 | 16122.38 | 14015.06 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4289.15 | 26-JAN-14:20 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 |
February | 6364.57 | 23-FEB-14:30 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 0.00 |
March | 13773.77 | 11-MAR-06:01 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.46 |
April | 20837.93 | 30-APR-16:21 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 260.95 | 0.00 |
May | 21563.65 | 29-MAY-16:01 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 205.56 | 0.00 |
June | 21138.55 | 04-JUN-16:51 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 206.77 | 0.00 |
July | 20566.17 | 04-JUL-16:21 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 125.49 | 0.00 |
August | 20007.91 | 06-AUG-15:41 | 708.51 | 325.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 169.07 | 0.00 |
September | 19995.47 | 24-SEP-15:01 | 708.51 | 325.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 150.95 | 0.00 |
October | 19417.33 | 01-OCT-15:01 | 708.51 | 325.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 79.32 | 0.00 |
November | 7039.92 | 09-NOV-14:30 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 | 0.00 |
December | 5194.96 | 26-DEC-14:10 | 4021.58 | 1674.56 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4289.15 | 708.51 | 325.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21563.65 | 4021.58 | 1674.56 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 260.95 | 9.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3984.28 | 26-JAN-10:10 | 2591.66 | 1079.15 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 |
February | 7126.95 | 21-FEB-09:40 | 1239.33 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.73 |
March | 11537.03 | 26-MAR-09:13 | 195.68 | 89.93 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 |
April | 17948.97 | 30-APR-09:01 | 456.59 | 209.83 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 | 0.00 |
May | 18130.39 | 28-MAY-08:41 | 456.59 | 209.83 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 45.73 | 0.00 |
June | 16804.48 | 04-JUN-16:11 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 147.96 | 0.00 |
July | 16721.66 | 04-JUL-09:41 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 62.68 | 0.00 |
August | 15800.70 | 06-AUG-15:01 | 456.59 | 209.83 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 121.09 | 0.00 |
September | 16140.20 | 17-SEP-09:21 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 | 0.00 |
October | 16630.76 | 01-OCT-09:42 | 326.14 | 149.88 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 | 0.00 |
November | 6711.60 | 13-NOV-09:40 | 1239.33 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 |
December | 4597.13 | 01-DEC-09:30 | 1239.33 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3984.28 | 195.68 | 89.93 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18130.39 | 2591.66 | 1079.15 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 147.96 | 28.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15984.99 | 08-JAN-13:53 | 303.66 | 139.55 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.68 |
February | 21199.46 | 20-FEB-12:13 | 404.87 | 186.07 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.15 |
March | 21161.51 | 12-MAR-12:32 | 404.87 | 186.07 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 0.00 |
April | 21780.78 | 30-APR-15:01 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 247.79 | 0.00 |
May | 22075.20 | 29-MAY-15:21 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 267.15 | 0.00 |
June | 21537.21 | 04-JUN-16:11 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 223.04 | 0.00 |
July | 20884.36 | 04-JUL-16:21 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 125.19 | 0.00 |
August | 20450.30 | 06-AUG-15:41 | 708.53 | 325.62 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 166.85 | 0.00 |
September | 21558.75 | 24-SEP-15:01 | 708.53 | 325.62 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 134.15 | 0.00 |
October | 23216.90 | 01-OCT-13:01 | 708.53 | 325.62 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 65.60 | 0.00 |
November | 21847.50 | 05-NOV-14:01 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 0.00 |
December | 21301.98 | 03-DEC-12:13 | 404.87 | 186.07 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 |
Annual Sum or Average | |||||||||||
Minimum of Months | 15984.99 | 303.66 | 139.55 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23216.90 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 267.15 | 45.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7006.29 | 31-JAN-16:00 | 1239.33 | 539.58 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 |
February | 18631.48 | 19-FEB-16:12 | 260.91 | 119.91 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.87 |
March | 21973.68 | 19-MAR-16:42 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 |
April | 26699.25 | 30-APR-16:21 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 117.97 | 0.00 |
May | 25980.86 | 28-MAY-16:01 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 297.22 | 0.00 |
June | 25772.83 | 04-JUN-16:11 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 124.90 | 0.00 |
July | 23493.36 | 04-JUL-16:21 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 75.20 | 0.00 |
August | 23060.19 | 06-AUG-16:21 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 87.59 | 0.00 |
September | 23232.65 | 24-SEP-15:01 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 82.57 | 0.00 |
October | 23776.07 | 01-OCT-15:01 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 40.78 | 0.00 |
November | 22045.66 | 05-NOV-15:21 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 0.00 |
December | 17259.42 | 25-DEC-14:51 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7006.29 | 260.91 | 119.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26699.25 | 1239.33 | 539.58 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 297.22 | 64.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2676.51 | 26-JAN-15:10 | 3846.22 | 1674.56 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.38 |
February | 5111.79 | 24-FEB-15:00 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 | 0.00 |
March | 12971.80 | 11-MAR-06:01 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 |
April | 19611.52 | 16-APR-16:01 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 82.49 | 0.00 |
May | 19890.19 | 28-MAY-16:11 | 708.51 | 325.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.53 | 0.00 |
June | 20827.58 | 04-JUN-16:51 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 458.55 | 0.00 |
July | 19799.03 | 02-JUL-16:21 | 708.51 | 325.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 415.51 | 0.00 |
August | 19490.03 | 27-AUG-14:41 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 184.67 | 0.00 |
September | 19127.07 | 24-SEP-15:11 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 335.29 | 0.00 |
October | 15078.01 | 01-OCT-13:51 | 809.73 | 372.12 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 212.54 | 0.00 |
November | 5763.36 | 09-NOV-14:40 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 17.13 | 0.00 |
December | 2660.03 | 01-DEC-15:10 | 3846.22 | 1674.56 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2660.03 | 708.51 | 325.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20827.58 | 3846.22 | 1674.56 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.53 | 28.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4580.11 | 26-JAN-11:05 | 2478.65 | 1079.15 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.29 |
February | 7204.87 | 23-FEB-11:05 | 2478.65 | 1079.15 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
March | 16697.66 | 12-MAR-10:13 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 |
April | 17639.87 | 16-APR-09:22 | 391.37 | 179.86 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 22.09 | 0.00 |
May | 17843.96 | 29-MAY-09:32 | 391.37 | 179.86 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 616.75 | 0.00 |
June | 17765.75 | 04-JUN-16:11 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 328.28 | 0.00 |
July | 17126.02 | 02-JUL-09:42 | 391.37 | 179.86 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 335.97 | 0.00 |
August | 16773.60 | 27-AUG-10:01 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 77.93 | 0.00 |
September | 16837.14 | 17-SEP-09:21 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 40.02 | 0.00 |
October | 17234.17 | 01-OCT-09:51 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 | 0.00 |
November | 7873.43 | 01-NOV-10:05 | 2478.65 | 1079.15 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 |
December | 4819.80 | 01-DEC-15:05 | 2478.65 | 1079.15 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4580.11 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17843.96 | 2478.65 | 1079.15 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 616.75 | 35.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17485.45 | 08-JAN-14:13 | 303.66 | 139.55 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.83 |
February | 21301.44 | 20-FEB-14:02 | 506.09 | 232.58 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 |
March | 20986.23 | 12-MAR-12:52 | 506.09 | 232.58 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 35.57 | 0.00 |
April | 20269.00 | 16-APR-15:21 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 118.16 | 0.00 |
May | 20041.54 | 07-MAY-15:41 | 809.75 | 372.13 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 542.51 | 0.00 |
June | 20851.19 | 04-JUN-16:11 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 497.40 | 0.00 |
July | 19845.16 | 02-JUL-16:21 | 708.53 | 325.62 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 414.81 | 0.00 |
August | 19765.07 | 27-AUG-14:41 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 180.48 | 0.00 |
September | 20359.51 | 24-SEP-13:51 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 324.50 | 0.00 |
October | 23004.50 | 01-OCT-13:51 | 809.75 | 372.13 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 147.89 | 0.00 |
November | 22313.20 | 12-NOV-12:42 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.09 |
December | 20584.27 | 03-DEC-12:32 | 404.87 | 186.07 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17485.45 | 303.66 | 139.55 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23004.50 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 542.51 | 98.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4661.54 | 31-JAN-16:20 | 1239.33 | 539.58 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.26 |
February | 9396.40 | 20-FEB-15:22 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 |
March | 19551.31 | 12-MAR-16:52 | 391.37 | 179.86 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 74.87 | 0.00 |
April | 20042.21 | 30-APR-16:31 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 353.84 | 0.00 |
May | 20586.89 | 28-MAY-16:11 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 738.56 | 0.00 |
June | 22333.50 | 04-JUN-16:11 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 280.34 | 0.00 |
July | 20115.95 | 02-JUL-16:21 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 250.83 | 0.00 |
August | 19320.48 | 06-AUG-16:21 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 207.35 | 0.00 |
September | 19461.94 | 24-SEP-15:51 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 162.00 | 0.00 |
October | 19940.07 | 15-OCT-15:21 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 137.91 | 0.00 |
November | 18221.64 | 05-NOV-15:21 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 5.80 | 0.00 |
December | 5370.13 | 01-DEC-15:30 | 1239.33 | 539.58 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4661.54 | 326.14 | 149.88 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22333.50 | 1239.33 | 539.58 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 738.56 | 21.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2659.40 | 26-JAN-15:00 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.57 |
February | 5357.05 | 23-FEB-15:00 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 13.49 | 0.00 |
March | 13994.54 | 11-MAR-06:01 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 |
April | 22667.65 | 16-APR-15:21 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 146.85 | 0.00 |
May | 24938.66 | 28-MAY-16:31 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.74 | 0.00 |
June | 24424.66 | 04-JUN-16:51 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 540.92 | 0.00 |
July | 22804.41 | 02-JUL-16:21 | 708.51 | 325.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 499.95 | 0.00 |
August | 22187.54 | 06-AUG-15:41 | 708.51 | 325.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 457.29 | 0.00 |
September | 22734.84 | 24-SEP-15:01 | 708.51 | 325.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 388.35 | 0.00 |
October | 21758.24 | 01-OCT-15:21 | 1012.16 | 465.16 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 192.89 | 0.00 |
November | 6209.16 | 09-NOV-14:50 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.27 | 0.00 |
December | 2647.89 | 28-DEC-16:30 | 1923.11 | 950.00 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2647.89 | 708.51 | 325.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24938.66 | 2024.33 | 950.00 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1304.74 | 33.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2677.73 | 26-JAN-14:30 | 1295.83 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.98 |
February | 5477.65 | 23-FEB-10:30 | 1295.83 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
March | 17164.79 | 12-MAR-16:21 | 456.59 | 209.83 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 107.88 | 0.00 |
April | 18259.83 | 16-APR-09:22 | 391.37 | 179.86 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 0.00 |
May | 19914.64 | 29-MAY-15:11 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 476.62 | 0.00 |
June | 19100.82 | 04-JUN-16:11 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 387.31 | 0.00 |
July | 17821.05 | 02-JUL-09:42 | 391.37 | 179.86 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 404.03 | 0.00 |
August | 17340.68 | 06-AUG-15:01 | 456.59 | 209.83 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 322.94 | 0.00 |
September | 18023.72 | 24-SEP-15:01 | 456.59 | 209.83 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 246.64 | 0.00 |
October | 17306.99 | 01-OCT-14:41 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 146.54 | 0.00 |
November | 5665.18 | 09-NOV-10:00 | 1239.33 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 0.00 |
December | 2790.40 | 01-DEC-15:00 | 1295.83 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2677.73 | 391.37 | 179.86 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19914.64 | 1295.83 | 539.58 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 476.62 | 21.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12581.79 | 12-JAN-14:30 | 2010.83 | 837.30 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 |
February | 23440.21 | 20-FEB-13:52 | 506.09 | 232.58 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 |
March | 24010.40 | 12-MAR-14:22 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 43.40 | 0.00 |
April | 23324.50 | 16-APR-15:21 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 141.56 | 0.00 |
May | 25023.61 | 28-MAY-15:51 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1403.80 | 0.00 |
June | 24403.74 | 04-JUN-16:11 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 587.76 | 0.00 |
July | 22806.73 | 02-JUL-16:21 | 708.53 | 325.62 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 499.46 | 0.00 |
August | 22409.65 | 06-AUG-15:41 | 708.53 | 325.62 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 449.39 | 0.00 |
September | 24240.63 | 24-SEP-15:01 | 708.53 | 325.62 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 337.03 | 0.00 |
October | 24477.30 | 22-OCT-12:42 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 19.15 | 0.00 |
November | 25189.38 | 05-NOV-13:51 | 708.53 | 325.62 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 4.62 | 0.00 |
December | 22144.78 | 03-DEC-14:13 | 404.87 | 186.07 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12581.79 | 404.87 | 186.07 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25189.38 | 2010.83 | 837.30 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1403.80 | 23.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4529.03 | 12-JAN-16:00 | 1239.33 | 539.58 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 |
February | 7783.55 | 20-FEB-16:33 | 260.91 | 119.91 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 |
March | 21822.47 | 12-MAR-16:21 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 69.85 | 0.00 |
April | 22124.60 | 16-APR-15:21 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 88.13 | 0.00 |
May | 25774.17 | 28-MAY-16:31 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 712.03 | 0.00 |
June | 24953.38 | 04-JUN-16:11 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 331.65 | 0.00 |
July | 22204.82 | 02-JUL-16:21 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 302.77 | 0.00 |
August | 21296.84 | 06-AUG-16:21 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 248.28 | 0.00 |
September | 22317.52 | 24-SEP-15:01 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 213.73 | 0.00 |
October | 21506.17 | 01-OCT-16:01 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 84.62 | 0.00 |
November | 19803.95 | 05-NOV-15:12 | 391.37 | 179.86 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 | 0.00 |
December | 5219.66 | 28-DEC-16:00 | 1239.33 | 539.58 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4529.03 | 260.91 | 119.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25774.17 | 1239.33 | 539.58 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 712.03 | 32.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2581.00 | 26-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.21 |
February | 7506.13 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.05 |
March | 9668.07 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.62 |
April | 15454.05 | 18-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
May | 18174.08 | 31-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 0.00 |
June | 19690.67 | 12-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.76 | 0.00 |
July | 22039.08 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.06 | 0.00 |
August | 20577.90 | 07-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 | 0.00 |
September | 15323.41 | 26-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.88 |
October | 13194.03 | 02-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
November | 9552.74 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 |
December | 6081.92 | 04-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2581.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22039.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 59.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2392.43 | 04-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3823.13 | 23-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 0.00 |
March | 9370.81 | 11-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.43 |
April | 11128.18 | 22-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 |
May | 13726.98 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.07 | 0.00 |
June | 16461.26 | 30-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.46 | 0.00 |
July | 18123.52 | 06-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.13 | 0.00 |
August | 14828.88 | 03-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 0.00 |
September | 12414.06 | 06-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 |
October | 12761.28 | 03-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 |
November | 5806.90 | 01-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.37 | 0.00 |
December | 2969.50 | 01-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2392.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18123.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.46 | 86.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4545.40 | 12-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.13 |
February | 11384.20 | 22-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 0.00 |
March | 20759.52 | 28-MAR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25912.77 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.89 | 0.00 |
May | 29586.42 | 04-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.81 | 0.00 |
June | 31183.33 | 12-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.45 | 0.00 |
July | 27036.16 | 07-JUL-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.26 | 0.00 |
August | 23948.27 | 07-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.97 | 0.00 |
September | 20732.32 | 26-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.00 | 0.00 |
October | 21375.28 | 02-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.15 | 0.00 |
November | 13722.53 | 09-NOV-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 | 0.00 |
December | 6237.09 | 01-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.49 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4545.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31183.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.89 | 47.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1709.08 | 12-JAN-17:00 | 0.00 | 203.27 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3901.77 | 20-FEB-17:25 | 0.00 | 45.17 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5900.67 | 26-MAR-18:05 | 0.00 | 49.88 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7776.88 | 16-APR-22:23 | 0.00 | 49.88 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2670.04 | 01-MAY-00:12 | 0.00 | 62.35 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4155.77 | 11-JUN-17:30 | 0.00 | 24.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6078.75 | 04-JUL-18:00 | 0.00 | 74.82 | 35074.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7679.83 | 14-AUG-04:11 | 0.00 | 249.40 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2200.40 | 01-SEP-00:10 | 0.00 | 24.94 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4048.62 | 01-OCT-17:12 | 0.00 | 74.82 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5825.16 | 12-NOV-16:28 | 0.00 | 112.93 | 58458.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7498.43 | 24-DEC-17:00 | 0.00 | 33.88 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1709.08 | 0.00 | 24.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7776.88 | 0.00 | 249.40 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1523.10 | 12-JAN-17:30 | 0.00 | 112.93 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3455.34 | 22-FEB-17:00 | 0.00 | 203.27 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5512.39 | 12-MAR-17:48 | 0.00 | 62.35 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7293.83 | 16-APR-20:22 | 0.00 | 62.35 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2140.80 | 29-MAY-17:52 | 0.00 | 124.70 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3886.46 | 11-JUN-18:00 | 0.00 | 24.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5666.95 | 02-JUL-18:05 | 0.00 | 24.94 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7175.46 | 20-AUG-15:02 | 0.00 | 45.17 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1955.36 | 17-SEP-18:13 | 0.00 | 74.82 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3826.86 | 01-OCT-16:56 | 0.00 | 79.05 | 27280.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5317.83 | 12-NOV-16:33 | 0.00 | 45.17 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7027.39 | 01-DEC-17:00 | 0.00 | 203.27 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1523.10 | 0.00 | 24.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7293.83 | 0.00 | 203.27 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1541.93 | 12-JAN-17:00 | 0.00 | 203.27 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3514.72 | 22-FEB-17:00 | 0.00 | 203.27 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5756.73 | 12-MAR-17:26 | 0.00 | 62.35 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7524.38 | 16-APR-21:31 | 0.00 | 124.70 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2620.31 | 29-MAY-18:01 | 0.00 | 99.76 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4382.02 | 11-JUN-17:25 | 0.00 | 24.94 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6126.18 | 02-JUL-18:00 | 0.00 | 24.94 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7374.01 | 20-AUG-15:02 | 0.00 | 45.17 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2235.10 | 17-SEP-17:59 | 0.00 | 124.70 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4117.67 | 01-OCT-17:05 | 0.00 | 74.82 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5358.50 | 09-NOV-16:40 | 0.00 | 203.27 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7029.91 | 01-DEC-17:00 | 0.00 | 203.27 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1541.93 | 0.00 | 24.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7524.38 | 0.00 | 203.27 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90525.60 | 26-JAN-17:00 | 0.00 | 4400.15 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182018.64 | 21-FEB-17:00 | 0.00 | 4400.15 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 272989.00 | 27-MAR-16:00 | 0.00 | 4400.15 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368422.69 | 29-APR-04:52 | 0.00 | 1619.61 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 121590.87 | 01-MAY-00:12 | 0.00 | 1349.67 | 474540.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 183025.30 | 12-JUN-16:00 | 0.00 | 4400.15 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 275652.22 | 05-JUL-16:00 | 0.00 | 4400.15 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370787.49 | 16-AUG-00:05 | 0.00 | 539.87 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 115328.44 | 01-SEP-00:23 | 0.00 | 1079.74 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 183801.74 | 10-OCT-16:00 | 0.00 | 4400.15 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275288.75 | 13-NOV-17:00 | 0.00 | 4400.15 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366350.61 | 18-DEC-17:00 | 0.00 | 4400.15 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 90525.60 | 0.00 | 539.87 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370787.49 | 0.00 | 4400.15 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.160570E+13 | 1025174.20 | 12-JAN-16:10 | 0.916093E+11 | 718689.81 | 02-JAN-06:10 |
February | 0.188687E+13 | 1285736.16 | 24-FEB-16:40 | 0.476730E+11 | 397683.22 | 20-FEB-02:20 |
March | 0.268022E+13 | 1588205.24 | 28-MAR-15:39 | 0.441037E+11 | 157424.18 | 05-MAR-23:30 |
April | 0.316681E+13 | 1837534.56 | 18-APR-15:39 | 0.363945E+11 | 142055.96 | 09-APR-20:10 |
May | 0.226668E+13 | 1443286.28 | 30-MAY-15:30 | 0.350796E+11 | 96779.44 | 12-MAY-03:49 |
June | 0.273385E+13 | 1672363.23 | 21-JUN-15:39 | 0.313844E+11 | 139167.40 | 18-JUN-13:09 |
July | 0.324117E+13 | 1812646.60 | 05-JUL-15:00 | 0.303978E+11 | 137456.23 | 04-JUL-04:10 |
August | 0.367104E+13 | 1961182.27 | 28-AUG-15:30 | 0.322747E+11 | 93813.66 | 13-AUG-02:30 |
September | 0.216078E+13 | 1442784.20 | 14-SEP-15:30 | 0.328736E+11 | 137474.28 | 03-SEP-09:50 |
October | 0.237610E+13 | 1506017.90 | 03-OCT-15:09 | 0.376154E+11 | 142223.11 | 29-OCT-08:20 |
November | 0.251425E+13 | 1545405.74 | 08-NOV-16:00 | 0.420287E+11 | 152133.61 | 26-NOV-16:19 |
December | 0.284181E+13 | 1486268.83 | 28-DEC-16:10 | 0.597997E+11 | 458242.69 | 23-DEC-06:10 |
Annual Sum or Average | 0.311453E+14 | 0.521234E+12 | ||||
Minimum of Months | 0.160570E+13 | 1025174.20 | 0.303978E+11 | 93813.66 | ||
Maximum of Months | 0.367104E+13 | 1961182.27 | 0.916093E+11 | 718689.81 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.216914E+12 | 0.354027E+11 | 0.766053E+12 | 0.166057E+12 | 0.157098E+12 | 0.351133E+11 | 0.00 | 0.157185E+12 | 0.562939E+11 | 0.155854E+11 | 0.00 | 0.00 | 0.00 |
February | 0.196066E+12 | 0.296904E+11 | 0.978954E+12 | 0.149994E+12 | 0.147643E+12 | 0.334797E+11 | 0.00 | 0.244523E+12 | 0.894749E+11 | 0.170471E+11 | 0.00 | 0.00 | 0.00 |
March | 0.231799E+12 | 0.295415E+11 | 0.141645E+13 | 0.166228E+12 | 0.182140E+12 | 0.470628E+11 | 0.00 | 0.462164E+12 | 0.134582E+12 | 0.102498E+11 | 0.00 | 0.00 | 0.00 |
April | 0.206093E+12 | 0.254748E+11 | 0.166021E+13 | 0.160684E+12 | 0.197645E+12 | 0.606694E+11 | 0.00 | 0.696993E+12 | 0.157333E+12 | 0.170422E+10 | 0.00 | 0.00 | 0.00 |
May | 0.221996E+12 | 0.235704E+11 | 0.774418E+12 | 0.166142E+12 | 0.218487E+12 | 0.727024E+11 | 0.00 | 0.589582E+12 | 0.199758E+12 | 21343631.06 | 0.00 | 0.00 | 0.00 |
June | 0.221055E+12 | 0.214275E+11 | 0.106218E+13 | 0.160845E+12 | 0.213816E+12 | 0.762219E+11 | 0.00 | 0.773810E+12 | 0.204493E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207152E+12 | 0.230823E+11 | 0.139289E+13 | 0.165982E+12 | 0.207811E+12 | 0.829400E+11 | 0.00 | 0.945209E+12 | 0.216102E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.231569E+12 | 0.251958E+11 | 0.173328E+13 | 0.166228E+12 | 0.208245E+12 | 0.837267E+11 | 0.00 | 0.100779E+13 | 0.215009E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207027E+12 | 0.270846E+11 | 0.740378E+12 | 0.160684E+12 | 0.190326E+12 | 0.696668E+11 | 0.00 | 0.568550E+12 | 0.197059E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.215799E+12 | 0.313253E+11 | 0.108288E+13 | 0.166057E+12 | 0.192108E+12 | 0.547170E+11 | 0.00 | 0.469370E+12 | 0.161588E+12 | 0.225079E+10 | 0.00 | 0.00 | 0.00 |
November | 0.214348E+12 | 0.334506E+11 | 0.135889E+13 | 0.160750E+12 | 0.171007E+12 | 0.413959E+11 | 0.00 | 0.397015E+12 | 0.119502E+12 | 0.178931E+11 | 0.00 | 0.00 | 0.00 |
December | 0.210212E+12 | 0.365300E+11 | 0.170972E+13 | 0.165982E+12 | 0.161236E+12 | 0.368055E+11 | 0.00 | 0.372215E+12 | 0.106998E+12 | 0.421169E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258003E+13 | 0.341776E+12 | 0.146763E+14 | 0.195563E+13 | 0.224756E+13 | 0.694501E+12 | 0.00 | 0.668440E+13 | 0.185819E+13 | 0.106869E+12 | |||
Minimum of Months | 0.196066E+12 | 0.214275E+11 | 0.740378E+12 | 0.149994E+12 | 0.147643E+12 | 0.334797E+11 | 0.00 | 0.157185E+12 | 0.562939E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.231799E+12 | 0.365300E+11 | 0.173328E+13 | 0.166228E+12 | 0.218487E+12 | 0.837267E+11 | 0.00 | 0.100779E+13 | 0.216102E+12 | 0.421169E+11 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.481807E+11 | 0.00 | 0.434286E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.903926E+10 | 0.00 | 0.386337E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.193708E+10 | 0.00 | 0.421666E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.944233E+09 | 0.00 | 0.354503E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.961075E+09 | 0.00 | 0.341185E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.692434E+09 | 0.00 | 0.306919E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.105835E+10 | 0.00 | 0.293395E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.709158E+09 | 0.00 | 0.315656E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.122915E+10 | 0.00 | 0.316445E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.135889E+10 | 0.00 | 0.362565E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.307743E+10 | 0.00 | 0.389513E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.183920E+11 | 0.00 | 0.414077E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.875797E+11 | 0.433655E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.692434E+09 | 0.00 | 0.293395E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.481807E+11 | 0.00 | 0.434286E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 246033.94 | 18-JAN-08:09 | 39974.20 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 126010.32 | 18-JAN-08:20 | 91263.08 | 26-JAN-06:10 | 26141.45 | 02-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 244865.70 | 10-FEB-08:09 | 39974.20 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 126009.70 | 10-FEB-08:20 | 102403.00 | 22-FEB-15:09 | 22004.94 | 20-FEB-09:50 | 0.00 | 01-FEB-00:10 |
March | 245365.99 | 14-MAR-07:10 | 39974.20 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 126009.97 | 14-MAR-07:19 | 150283.81 | 27-MAR-14:50 | 50860.62 | 27-MAR-14:50 | 0.00 | 01-MAR-00:10 |
April | 227849.42 | 03-APR-07:10 | 39974.20 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 126000.68 | 03-APR-07:19 | 156616.70 | 28-APR-15:39 | 49498.81 | 28-APR-08:09 | 0.00 | 01-APR-00:10 |
May | 232294.28 | 24-MAY-07:10 | 39974.20 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 126003.04 | 24-MAY-07:19 | 168077.49 | 04-MAY-15:30 | 42012.68 | 27-MAY-12:39 | 0.00 | 01-MAY-00:10 |
June | 232445.87 | 23-JUN-07:10 | 39974.20 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 126003.12 | 23-JUN-07:19 | 176999.35 | 12-JUN-15:00 | 47084.77 | 22-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 244485.88 | 26-JUL-07:10 | 39974.20 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 126009.50 | 26-JUL-07:19 | 158302.71 | 07-JUL-15:39 | 42212.79 | 05-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 246235.86 | 16-AUG-07:10 | 39974.20 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 126010.43 | 16-AUG-07:19 | 148274.23 | 07-AUG-15:30 | 42810.07 | 28-AUG-15:30 | 0.00 | 01-AUG-00:10 |
September | 247986.32 | 08-SEP-07:10 | 39974.20 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 126011.36 | 08-SEP-07:19 | 141967.84 | 28-SEP-15:30 | 41444.72 | 14-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 251437.78 | 11-OCT-07:10 | 39974.20 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 126013.19 | 11-OCT-07:19 | 146096.94 | 02-OCT-15:30 | 44080.93 | 31-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 246233.28 | 27-NOV-16:00 | 39974.20 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 126004.13 | 03-NOV-07:19 | 115991.00 | 09-NOV-15:09 | 50210.71 | 02-NOV-15:09 | 0.00 | 01-NOV-00:10 |
December | 248873.75 | 29-DEC-16:00 | 39974.20 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 126003.17 | 29-DEC-08:20 | 95769.60 | 01-DEC-06:10 | 23130.53 | 23-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 227849.42 | 39974.20 | 423497.50 | 126000.68 | 91263.08 | 22004.94 | 0.00 | |||||||
Maximum of Months | 251437.78 | 39974.20 | 778371.69 | 126013.19 | 176999.35 | 50860.62 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 142939.27 | 25-JAN-14:39 | 45454.02 | 13-JAN-15:30 | 8277.99 | 31-JAN-10:50 | 0.00 | 0.00 | 0.00 |
February | 247199.14 | 22-FEB-15:30 | 83553.66 | 24-FEB-13:00 | 12167.28 | 05-FEB-09:00 | 0.00 | 0.00 | 0.00 |
March | 374478.96 | 27-MAR-14:00 | 83553.66 | 06-MAR-10:50 | 15574.98 | 03-MAR-06:19 | 0.00 | 0.00 | 0.00 |
April | 478261.65 | 18-APR-15:30 | 83553.66 | 16-APR-14:00 | 10357.58 | 11-APR-04:00 | 0.00 | 0.00 | 0.00 |
May | 429980.28 | 17-MAY-15:00 | 83553.66 | 01-MAY-21:00 | 2277.48 | 28-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 553821.26 | 21-JUN-15:39 | 83553.66 | 01-JUN-03:20 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 559856.85 | 05-JUL-15:00 | 83553.66 | 01-JUL-00:40 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 613552.41 | 28-AUG-15:30 | 83553.66 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 453452.57 | 14-SEP-15:30 | 83553.66 | 01-SEP-00:40 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 384512.53 | 03-OCT-14:00 | 83553.66 | 03-OCT-22:19 | 8549.37 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 |
November | 348444.89 | 14-NOV-14:00 | 83553.66 | 03-NOV-14:00 | 16720.92 | 30-NOV-22:00 | 0.00 | 0.00 | 0.00 |
December | 249359.94 | 01-DEC-13:30 | 46250.56 | 28-DEC-14:00 | 30730.10 | 22-DEC-06:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 142939.27 | 45454.02 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 613552.41 | 83553.66 | 30730.10 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1025174.20 | 12-JAN-16:10 | 224881.14 | 423497.50 | 0.00 | 89219.08 | 82243.89 | 20628.13 | 0.00 | 137339.95 | 45417.69 |
February | 1285736.16 | 24-FEB-16:40 | 224978.20 | 541788.89 | 0.00 | 89219.36 | 91907.51 | 21329.85 | 0.00 | 232958.69 | 83553.66 |
March | 1588205.24 | 28-MAR-15:39 | 223670.64 | 660080.29 | 0.00 | 89219.08 | 133923.62 | 38853.01 | 0.00 | 358904.95 | 83553.66 |
April | 1837534.56 | 18-APR-15:39 | 223670.64 | 778371.69 | 0.00 | 89219.08 | 144486.95 | 40153.28 | 0.00 | 478079.28 | 83553.66 |
May | 1443286.28 | 30-MAY-15:30 | 223670.64 | 423497.50 | 0.00 | 89219.08 | 161959.92 | 41339.67 | 0.00 | 420045.82 | 83553.66 |
June | 1672363.23 | 21-JUN-15:39 | 223670.64 | 541788.89 | 0.00 | 89219.08 | 137554.29 | 42755.42 | 0.00 | 553821.26 | 83553.66 |
July | 1812646.60 | 05-JUL-15:00 | 223670.64 | 660080.29 | 0.00 | 89219.08 | 154053.29 | 42212.79 | 0.00 | 559856.85 | 83553.66 |
August | 1961182.27 | 28-AUG-15:30 | 223670.64 | 778371.69 | 0.00 | 89219.08 | 130004.73 | 42810.07 | 0.00 | 613552.41 | 83553.66 |
September | 1442784.20 | 14-SEP-15:30 | 223670.64 | 423497.50 | 0.00 | 89219.08 | 127946.04 | 41444.72 | 0.00 | 453452.57 | 83553.66 |
October | 1506017.90 | 03-OCT-15:09 | 223670.64 | 541788.89 | 0.00 | 89219.08 | 143624.45 | 39953.54 | 0.00 | 384207.64 | 83553.66 |
November | 1545405.74 | 08-NOV-16:00 | 235097.33 | 660080.29 | 0.00 | 89223.45 | 101355.27 | 39445.94 | 0.00 | 336649.80 | 83553.66 |
December | 1486268.83 | 28-DEC-16:10 | 225046.10 | 778371.69 | 0.00 | 89219.63 | 86234.44 | 20650.38 | 0.00 | 240748.55 | 45998.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1025174.20 | 223670.64 | 423497.50 | 0.00 | 89219.08 | 82243.89 | 20628.13 | 0.00 | 137339.95 | 45417.69 | |
Maximum of Months | 1961182.27 | 235097.33 | 778371.69 | 0.00 | 89223.45 | 161959.92 | 42810.07 | 0.00 | 613552.41 | 83553.66 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 711408.93 | 02-JAN-06:10 | 0.00 | 67389.36 | 18-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 390402.34 | 20-FEB-02:20 | 0.00 | 67040.31 | 01-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 150143.30 | 05-MAR-23:30 | 0.00 | 64383.91 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 134775.08 | 09-APR-20:10 | 0.00 | 57773.67 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 89498.56 | 12-MAY-03:49 | 0.00 | 49144.12 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 131886.52 | 18-JUN-13:09 | 0.00 | 36593.47 | 05-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 130175.35 | 04-JUL-04:10 | 0.00 | 34516.39 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 86532.78 | 13-AUG-02:30 | 0.00 | 36039.81 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 130193.40 | 03-SEP-09:50 | 0.00 | 46775.03 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 134942.23 | 29-OCT-08:20 | 0.00 | 57072.15 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 144852.73 | 26-NOV-16:19 | 0.00 | 63325.89 | 29-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 450961.81 | 23-DEC-06:10 | 0.00 | 66648.98 | 28-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 86532.78 | 0.00 | 34516.39 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 711408.93 | 0.00 | 67389.36 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.76 | 4.00 | 28.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.07 | 1.00 | 28.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.43 | 0.67 | 27.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.27 | 0.83 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 26.21 | 1.00 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 26.45 | 3.83 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 26.31 | 2.00 | 27.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 26.50 | 3.83 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.73 | 3.50 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.22 | 3.67 | 27.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.36 | 3.17 | 28.03 |
Annual Sum or Average | 0.00 | 0.00 | 133.17 | 26.73 | 27.50 | 27.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.21 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.76 | 4.00 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.64 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.63 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.64 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.71 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 25.66 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.71 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.85 | 0.00 | 0.17 | 25.56 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.85 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.91 | 3.17 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.12 | 7.00 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 26.86 | 4.00 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.23 | 10.17 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 26.98 | 5.50 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.72 | 1.83 | 27.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 84.00 | 27.05 | 31.67 | 27.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.23 | 10.17 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.48 | 2.17 | 27.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.52 | 8.67 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.47 | 12.17 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.10 | 7.00 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 27.39 | 12.17 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.18 | 6.67 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.32 | 4.50 | 27.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.52 | 7.00 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.39 | 0.17 | 27.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 116.83 | 27.36 | 60.50 | 27.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.52 | 12.17 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.43 | 0.83 | 27.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.73 | 4.33 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.66 | 4.83 | 27.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.20 | 6.50 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.19 | 8.00 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 26.90 | 4.50 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.25 | 10.50 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 27.05 | 6.50 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.14 | 3.50 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.53 | 12.83 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.98 | 10.50 | 27.99 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.57 | 5.33 | 27.57 |
Annual Sum or Average | 0.00 | 0.00 | 152.17 | 27.29 | 78.17 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.90 | 0.83 | 27.43 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.98 | 12.83 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.69 | 2.83 | 27.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.28 | 6.17 | 27.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 74.33 | 27.77 | 23.00 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 27.57 | 17.67 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 63.00 | 27.61 | 16.67 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 76.17 | 27.75 | 23.00 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 76.67 | 27.73 | 20.17 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 27.04 | 9.17 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 27.40 | 9.83 | 28.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.48 | 6.67 | 27.82 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.43 | 3.50 | 27.51 |
Annual Sum or Average | 0.00 | 0.00 | 437.00 | 27.61 | 138.67 | 27.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 76.67 | 27.77 | 23.00 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.40 | 2.00 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.25 | 8.00 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 26.94 | 3.83 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.15 | 9.00 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.79 | 3.83 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.94 | 1.17 | 27.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.18 | 0.00 | 69.67 | 27.09 | 27.83 | 27.62 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.18 | 0.00 | 0.00 | 22.00 | 27.40 | 9.00 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.50 | 3.00 | 27.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.64 | 10.83 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 27.52 | 13.00 | 28.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.19 | 8.50 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.37 | 13.17 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.10 | 7.83 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.45 | 4.33 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.59 | 8.50 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.25 | 0.00 | 143.17 | 27.39 | 69.17 | 27.88 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.25 | 0.00 | 0.00 | 33.00 | 27.64 | 13.17 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.46 | 0.83 | 27.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.76 | 4.00 | 27.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.71 | 4.17 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.38 | 4.67 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.26 | 8.50 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 26.92 | 4.17 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 27.14 | 9.00 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 26.89 | 5.33 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.20 | 3.50 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 26.77 | 20.50 | 26.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.10 | 14.17 | 27.10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.64 | 3.17 | 27.64 |
Annual Sum or Average | 0.00 | 0.00 | 145.17 | 27.11 | 82.00 | 27.34 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.77 | 0.83 | 26.64 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 27.76 | 20.50 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.45 | 0.50 | 27.45 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.71 | 2.50 | 27.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.46 | 7.50 | 28.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 27.53 | 14.17 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 43.00 | 27.46 | 10.67 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | 27.45 | 14.00 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 27.14 | 7.33 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.00 | 3.67 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.75 | 5.00 | 28.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.47 | 1.33 | 27.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 217.33 | 27.43 | 66.67 | 28.01 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 27.75 | 14.17 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.58 | 3.83 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 27.44 | 9.00 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.20 | 6.33 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 27.35 | 11.00 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.06 | 6.33 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.30 | 2.67 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.47 | 0.83 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 19.12 | 0.00 | 108.17 | 27.31 | 40.00 | 27.82 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.37 | 0.00 | 0.00 | 30.00 | 27.58 | 11.00 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.56 | 2.67 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.72 | 12.33 | 27.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 | 27.66 | 13.17 | 28.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 27.36 | 10.67 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 | 27.51 | 14.33 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.28 | 8.33 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.52 | 5.67 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.67 | 8.83 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 19.08 | 0.00 | 173.83 | 27.52 | 76.00 | 28.02 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.40 | 0.00 | 0.00 | 38.33 | 27.72 | 14.33 | 28.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.72 | 3.00 | 27.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.79 | 4.17 | 27.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.56 | 7.17 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 27.44 | 9.50 | 27.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 27.19 | 6.17 | 27.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 27.38 | 11.00 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 27.15 | 6.83 | 27.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.39 | 4.83 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 27.76 | 12.50 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.91 | 9.83 | 27.93 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.50 | 1.33 | 27.50 |
Annual Sum or Average | 0.50 | 18.86 | 0.00 | 162.67 | 27.45 | 76.33 | 27.89 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.86 | 0.00 | 0.00 | 30.50 | 27.91 | 12.50 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.50 | 27.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.80 | 3.00 | 27.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.62 | 8.67 | 28.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 27.66 | 15.17 | 28.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 47.00 | 27.57 | 12.17 | 28.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 27.57 | 15.33 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 27.30 | 8.33 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.16 | 5.83 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.91 | 5.67 | 28.22 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 18.95 | 0.00 | 240.67 | 27.55 | 75.83 | 28.12 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.95 | 0.00 | 0.00 | 54.00 | 27.91 | 15.33 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 125.83 | 28.24 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 100.00 | 28.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 225.83 | 28.13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 125.83 | 28.24 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 111.00 | 28.18 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 27.86 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 172.83 | 28.07 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 111.00 | 28.18 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 110.17 | 28.30 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 28.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 171.33 | 28.19 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 110.17 | 28.30 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 369.50 | 28.89 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.75 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 710.83 | 28.86 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.71 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1080.67 | 28.87 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 710.83 | 28.89 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.83 | 26.14 | 280.00 | 24.99 | 3.67 | 26.80 |
February | 12.50 | 26.84 | 352.33 | 24.69 | 12.50 | 26.84 |
March | 33.83 | 25.13 | 431.67 | 24.53 | 33.83 | 25.13 |
April | 31.33 | 24.22 | 410.33 | 24.64 | 31.33 | 24.22 |
May | 279.17 | 24.50 | 492.33 | 24.55 | 279.17 | 24.50 |
June | 324.83 | 24.60 | 496.00 | 24.50 | 324.83 | 24.60 |
July | 285.83 | 25.10 | 497.00 | 24.63 | 285.83 | 25.10 |
August | 240.83 | 25.05 | 514.00 | 24.49 | 240.83 | 25.05 |
September | 276.17 | 25.02 | 485.00 | 24.58 | 276.17 | 25.02 |
October | 82.33 | 24.96 | 502.00 | 24.62 | 82.33 | 24.96 |
November | 1.50 | 26.82 | 466.50 | 24.66 | 1.50 | 26.82 |
December | 1.00 | 26.79 | 368.17 | 24.83 | 1.00 | 26.79 |
Annual Sum or Average | 1574.17 | 24.86 | 5295.33 | 24.62 | 1573.00 | 24.86 |
Minimum of Months | 1.00 | 24.22 | 280.00 | 24.49 | 1.00 | 24.22 |
Maximum of Months | 324.83 | 26.84 | 514.00 | 24.99 | 324.83 | 26.84 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.67 | 24.55 | 220.00 | 24.72 | 13.17 | 25.84 |
February | 11.50 | 23.57 | 341.50 | 24.40 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 454.33 | 24.27 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 441.17 | 24.20 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 495.00 | 24.15 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 496.00 | 24.15 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 497.00 | 24.21 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 514.00 | 24.18 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 484.00 | 24.22 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 502.00 | 24.31 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 464.00 | 24.41 | 0.00 | 0.00 |
December | 4.67 | 24.00 | 343.50 | 24.51 | 0.00 | 0.00 |
Annual Sum or Average | 46.83 | 24.26 | 5252.50 | 24.28 | 13.17 | 25.84 |
Minimum of Months | 0.00 | 0.00 | 220.00 | 24.15 | 0.00 | 0.00 |
Maximum of Months | 30.67 | 24.55 | 514.00 | 24.72 | 13.17 | 25.84 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 282.83 | 23.15 | 67.67 | 23.71 | 12.83 | 21.62 |
February | 120.50 | 23.36 | 166.83 | 24.26 | 0.00 | 0.00 |
March | 25.17 | 23.47 | 347.00 | 24.23 | 0.00 | 0.00 |
April | 7.50 | 23.72 | 330.33 | 24.13 | 0.00 | 0.00 |
May | 0.50 | 23.60 | 423.00 | 24.06 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 448.67 | 24.10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 427.67 | 24.10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 470.33 | 24.13 | 0.00 | 0.00 |
September | 1.17 | 23.28 | 440.67 | 24.19 | 0.00 | 0.00 |
October | 0.17 | 23.85 | 466.17 | 24.24 | 0.00 | 0.00 |
November | 32.83 | 23.41 | 320.83 | 24.26 | 0.00 | 0.00 |
December | 191.67 | 23.36 | 75.50 | 24.29 | 0.00 | 0.00 |
Annual Sum or Average | 662.33 | 23.28 | 3984.67 | 24.16 | 12.83 | 21.62 |
Minimum of Months | 0.00 | 0.00 | 67.67 | 23.71 | 0.00 | 0.00 |
Maximum of Months | 282.83 | 23.85 | 470.33 | 24.29 | 12.83 | 21.62 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 453.17 | 22.20 | 30.00 | 20.29 | 20.83 | 18.67 |
February | 261.33 | 22.80 | 101.67 | 24.11 | 0.00 | 0.00 |
March | 86.00 | 23.38 | 309.67 | 24.19 | 0.00 | 0.00 |
April | 1.67 | 23.64 | 374.83 | 24.21 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 477.50 | 24.18 | 0.00 | 0.00 |
June | 0.50 | 23.44 | 481.83 | 24.18 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 491.17 | 24.20 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 510.33 | 24.19 | 0.00 | 0.00 |
September | 5.00 | 23.15 | 448.33 | 24.25 | 0.00 | 0.00 |
October | 9.17 | 23.32 | 415.00 | 24.25 | 0.00 | 0.00 |
November | 160.00 | 23.08 | 196.67 | 24.12 | 0.00 | 0.00 |
December | 409.17 | 22.53 | 31.83 | 23.01 | 9.00 | 20.55 |
Annual Sum or Average | 1386.00 | 22.60 | 3868.83 | 24.16 | 29.83 | 19.24 |
Minimum of Months | 0.00 | 0.00 | 30.00 | 20.29 | 0.00 | 0.00 |
Maximum of Months | 453.17 | 23.64 | 510.33 | 24.25 | 20.83 | 20.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 408.83 | 22.87 | 17.17 | 23.99 | 0.00 | 0.00 |
February | 194.83 | 23.15 | 135.33 | 24.16 | 0.00 | 0.00 |
March | 27.83 | 23.47 | 370.33 | 24.24 | 0.00 | 0.00 |
April | 9.67 | 26.79 | 450.67 | 24.42 | 9.67 | 26.79 |
May | 28.50 | 26.85 | 508.00 | 24.47 | 28.50 | 26.85 |
June | 20.83 | 26.78 | 496.00 | 24.42 | 20.83 | 26.78 |
July | 46.50 | 26.82 | 497.00 | 24.55 | 46.50 | 26.82 |
August | 26.33 | 26.82 | 514.00 | 24.40 | 26.33 | 26.82 |
September | 14.50 | 26.46 | 485.00 | 24.41 | 14.50 | 26.46 |
October | 1.50 | 26.30 | 479.67 | 24.36 | 1.50 | 26.30 |
November | 70.50 | 23.46 | 295.00 | 24.25 | 0.00 | 0.00 |
December | 293.17 | 23.19 | 48.33 | 24.05 | 0.00 | 0.00 |
Annual Sum or Average | 1143.00 | 23.56 | 4296.50 | 24.39 | 147.83 | 26.78 |
Minimum of Months | 1.50 | 22.87 | 17.17 | 23.99 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 26.85 | 514.00 | 24.55 | 46.50 | 26.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 279.00 | 22.97 | 39.67 | 24.08 | 0.00 | 0.00 |
February | 126.67 | 23.09 | 199.00 | 24.34 | 0.00 | 0.00 |
March | 34.00 | 24.14 | 412.67 | 24.34 | 8.17 | 26.73 |
April | 36.00 | 26.89 | 461.17 | 24.48 | 35.67 | 26.92 |
May | 49.83 | 27.00 | 508.00 | 24.54 | 49.83 | 27.00 |
June | 33.67 | 26.83 | 496.00 | 24.45 | 33.67 | 26.83 |
July | 52.67 | 26.90 | 497.00 | 24.55 | 52.67 | 26.90 |
August | 28.00 | 26.88 | 514.00 | 24.37 | 28.00 | 26.88 |
September | 24.67 | 26.64 | 485.00 | 24.44 | 24.67 | 26.64 |
October | 27.33 | 26.66 | 479.17 | 24.48 | 26.50 | 26.76 |
November | 56.83 | 23.42 | 348.83 | 24.37 | 1.17 | 26.59 |
December | 247.50 | 23.09 | 91.17 | 24.31 | 0.00 | 0.00 |
Annual Sum or Average | 996.17 | 24.06 | 4531.67 | 24.44 | 260.33 | 26.87 |
Minimum of Months | 24.67 | 22.97 | 39.67 | 24.08 | 0.00 | 0.00 |
Maximum of Months | 279.00 | 27.00 | 514.00 | 24.55 | 52.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 204.50 | 23.00 | 191.67 | 24.34 | 0.83 | 26.48 |
February | 99.67 | 23.38 | 289.00 | 24.47 | 10.33 | 26.89 |
March | 38.33 | 25.09 | 434.00 | 24.39 | 17.83 | 26.87 |
April | 24.17 | 26.89 | 469.17 | 24.48 | 24.17 | 26.89 |
May | 31.83 | 26.87 | 508.00 | 24.49 | 31.83 | 26.87 |
June | 22.17 | 26.78 | 496.00 | 24.42 | 22.17 | 26.78 |
July | 47.17 | 26.83 | 497.00 | 24.55 | 47.17 | 26.83 |
August | 29.00 | 26.86 | 514.00 | 24.41 | 29.00 | 26.86 |
September | 21.83 | 26.63 | 485.00 | 24.48 | 21.83 | 26.63 |
October | 45.50 | 27.07 | 499.83 | 24.59 | 45.50 | 27.07 |
November | 57.00 | 25.93 | 424.33 | 24.60 | 39.67 | 27.00 |
December | 119.67 | 23.47 | 271.67 | 24.54 | 10.00 | 26.83 |
Annual Sum or Average | 740.83 | 24.62 | 5079.67 | 24.49 | 300.33 | 26.89 |
Minimum of Months | 21.83 | 23.00 | 191.67 | 24.34 | 0.83 | 26.48 |
Maximum of Months | 204.50 | 27.07 | 514.00 | 24.60 | 47.17 | 27.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 161.50 | 23.33 | 160.33 | 24.37 | 0.00 | 0.00 |
February | 34.00 | 24.55 | 337.17 | 24.53 | 10.50 | 26.86 |
March | 28.67 | 26.87 | 499.00 | 24.53 | 28.67 | 26.87 |
April | 91.67 | 26.86 | 485.00 | 24.66 | 91.67 | 26.86 |
May | 82.50 | 26.91 | 508.00 | 24.62 | 82.50 | 26.91 |
June | 80.50 | 26.89 | 496.00 | 24.57 | 80.50 | 26.89 |
July | 108.83 | 26.93 | 497.00 | 24.71 | 108.83 | 26.93 |
August | 91.67 | 26.94 | 514.00 | 24.58 | 91.67 | 26.94 |
September | 58.67 | 26.77 | 485.00 | 24.59 | 58.67 | 26.77 |
October | 47.17 | 26.89 | 502.00 | 24.65 | 47.17 | 26.89 |
November | 27.33 | 26.88 | 467.83 | 24.63 | 27.33 | 26.88 |
December | 19.00 | 25.33 | 362.50 | 24.65 | 9.50 | 26.78 |
Annual Sum or Average | 831.50 | 26.07 | 5313.83 | 24.60 | 637.00 | 26.89 |
Minimum of Months | 19.00 | 23.33 | 160.33 | 24.37 | 0.00 | 0.00 |
Maximum of Months | 161.50 | 26.94 | 514.00 | 24.71 | 108.83 | 26.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.83 | 21.52 | 46.17 | 19.97 | 46.17 | 19.97 |
February | 375.67 | 22.39 | 30.50 | 23.87 | 2.33 | 20.48 |
March | 136.83 | 23.17 | 255.83 | 24.19 | 0.00 | 0.00 |
April | 11.50 | 25.55 | 423.50 | 24.41 | 7.17 | 26.76 |
May | 30.33 | 26.87 | 508.00 | 24.49 | 30.33 | 26.87 |
June | 32.67 | 26.49 | 496.00 | 24.44 | 32.67 | 26.49 |
July | 50.83 | 26.64 | 497.00 | 24.58 | 50.83 | 26.64 |
August | 23.83 | 26.72 | 514.00 | 24.43 | 23.83 | 26.72 |
September | 36.00 | 26.23 | 485.00 | 24.44 | 36.00 | 26.23 |
October | 27.00 | 23.33 | 420.67 | 24.32 | 0.83 | 25.83 |
November | 271.67 | 22.88 | 102.17 | 24.02 | 0.00 | 0.00 |
December | 493.83 | 21.90 | 23.67 | 20.20 | 23.67 | 20.20 |
Annual Sum or Average | 1991.00 | 22.57 | 3802.50 | 24.33 | 253.83 | 24.73 |
Minimum of Months | 11.50 | 21.52 | 23.67 | 19.97 | 0.00 | 0.00 |
Maximum of Months | 500.83 | 26.87 | 514.00 | 24.58 | 50.83 | 26.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 395.50 | 22.16 | 24.83 | 20.58 | 21.50 | 20.05 |
February | 201.17 | 22.73 | 101.50 | 24.31 | 0.17 | 21.06 |
March | 55.67 | 23.78 | 308.67 | 24.47 | 9.33 | 26.77 |
April | 40.50 | 26.92 | 385.33 | 24.68 | 40.17 | 26.94 |
May | 56.67 | 27.03 | 430.00 | 24.68 | 56.67 | 27.03 |
June | 50.17 | 26.75 | 418.00 | 24.59 | 50.17 | 26.75 |
July | 66.33 | 26.81 | 422.00 | 24.74 | 66.33 | 26.81 |
August | 34.67 | 26.86 | 433.00 | 24.57 | 34.67 | 26.86 |
September | 51.33 | 26.51 | 410.00 | 24.60 | 51.33 | 26.51 |
October | 42.17 | 26.00 | 392.00 | 24.63 | 32.50 | 26.81 |
November | 114.67 | 23.08 | 211.67 | 24.40 | 0.33 | 26.79 |
December | 348.33 | 22.47 | 8.00 | 22.06 | 4.17 | 20.09 |
Annual Sum or Average | 1457.17 | 23.52 | 3545.00 | 24.57 | 367.33 | 26.34 |
Minimum of Months | 34.67 | 22.16 | 8.00 | 20.58 | 0.17 | 20.05 |
Maximum of Months | 395.50 | 27.03 | 433.00 | 24.74 | 66.33 | 27.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 255.67 | 22.46 | 156.50 | 24.20 | 6.00 | 20.60 |
February | 142.83 | 22.90 | 235.67 | 24.50 | 9.33 | 26.94 |
March | 60.83 | 24.20 | 394.17 | 24.41 | 15.33 | 26.91 |
April | 21.00 | 26.86 | 453.67 | 24.50 | 20.83 | 26.88 |
May | 32.33 | 26.89 | 508.00 | 24.50 | 32.33 | 26.89 |
June | 32.17 | 26.49 | 496.00 | 24.44 | 32.17 | 26.49 |
July | 51.50 | 26.65 | 497.00 | 24.58 | 51.50 | 26.65 |
August | 26.83 | 26.79 | 514.00 | 24.46 | 26.83 | 26.79 |
September | 47.17 | 26.49 | 485.00 | 24.52 | 47.17 | 26.49 |
October | 45.00 | 27.10 | 486.33 | 24.66 | 45.00 | 27.10 |
November | 80.00 | 25.02 | 397.33 | 24.61 | 38.50 | 27.05 |
December | 186.50 | 22.89 | 211.17 | 24.57 | 8.33 | 25.72 |
Annual Sum or Average | 981.83 | 24.04 | 4834.83 | 24.51 | 333.33 | 26.65 |
Minimum of Months | 21.00 | 22.46 | 156.50 | 24.20 | 6.00 | 20.60 |
Maximum of Months | 255.67 | 27.10 | 514.00 | 24.66 | 51.50 | 27.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 428.33 | 22.13 | 28.00 | 22.06 | 13.67 | 20.02 |
February | 234.67 | 22.67 | 126.00 | 24.37 | 0.33 | 26.54 |
March | 55.83 | 24.02 | 376.33 | 24.39 | 10.67 | 26.92 |
April | 34.67 | 26.93 | 476.50 | 24.57 | 34.67 | 26.93 |
May | 63.50 | 26.96 | 508.00 | 24.61 | 63.50 | 26.96 |
June | 66.00 | 26.79 | 496.00 | 24.54 | 66.00 | 26.79 |
July | 81.50 | 26.80 | 497.00 | 24.66 | 81.50 | 26.80 |
August | 47.67 | 26.84 | 514.00 | 24.51 | 47.67 | 26.84 |
September | 54.00 | 26.62 | 485.00 | 24.56 | 54.00 | 26.62 |
October | 25.17 | 26.61 | 481.33 | 24.52 | 22.67 | 26.97 |
November | 112.50 | 23.26 | 278.50 | 24.33 | 4.50 | 26.75 |
December | 383.67 | 22.52 | 51.17 | 23.80 | 4.17 | 20.43 |
Annual Sum or Average | 1587.50 | 23.55 | 4317.83 | 24.50 | 403.33 | 26.53 |
Minimum of Months | 25.17 | 22.13 | 28.00 | 22.06 | 0.33 | 20.02 |
Maximum of Months | 428.33 | 26.96 | 514.00 | 24.66 | 81.50 | 26.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.01 | 136.67 | 19.82 | 136.67 | 19.82 |
February | 389.33 | 21.96 | 51.33 | 22.11 | 25.83 | 20.22 |
March | 169.00 | 22.86 | 241.50 | 24.21 | 0.33 | 26.24 |
April | 32.17 | 25.12 | 420.50 | 24.45 | 15.67 | 26.88 |
May | 40.50 | 26.94 | 507.33 | 24.51 | 40.50 | 26.94 |
June | 44.83 | 26.56 | 496.00 | 24.46 | 44.83 | 26.56 |
July | 63.17 | 26.68 | 497.00 | 24.60 | 63.17 | 26.68 |
August | 30.83 | 26.75 | 514.00 | 24.45 | 30.83 | 26.75 |
September | 46.50 | 26.35 | 479.67 | 24.46 | 46.50 | 26.35 |
October | 66.67 | 23.32 | 383.67 | 24.34 | 5.00 | 26.41 |
November | 330.83 | 22.49 | 86.33 | 23.82 | 4.00 | 19.89 |
December | 497.00 | 21.31 | 85.00 | 19.82 | 85.00 | 19.82 |
Annual Sum or Average | 2212.83 | 22.31 | 3899.00 | 24.15 | 498.33 | 23.23 |
Minimum of Months | 30.83 | 21.01 | 51.33 | 19.82 | 0.33 | 19.82 |
Maximum of Months | 502.00 | 26.94 | 514.00 | 24.60 | 136.67 | 26.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.00 | 21.60 | 73.17 | 19.75 | 71.83 | 19.67 |
February | 271.83 | 22.40 | 106.83 | 23.71 | 11.33 | 20.39 |
March | 82.00 | 23.39 | 363.83 | 24.37 | 9.50 | 26.77 |
April | 49.17 | 26.69 | 457.67 | 24.57 | 45.17 | 26.97 |
May | 59.50 | 27.06 | 508.00 | 24.59 | 59.50 | 27.06 |
June | 57.17 | 26.77 | 496.00 | 24.51 | 57.17 | 26.77 |
July | 74.17 | 26.80 | 497.00 | 24.64 | 74.17 | 26.80 |
August | 38.83 | 26.86 | 514.00 | 24.48 | 38.83 | 26.86 |
September | 56.33 | 26.53 | 482.50 | 24.52 | 56.33 | 26.53 |
October | 62.17 | 25.20 | 445.50 | 24.52 | 35.00 | 26.81 |
November | 166.83 | 22.71 | 218.50 | 24.19 | 1.67 | 20.14 |
December | 463.00 | 21.99 | 43.17 | 20.09 | 43.17 | 20.09 |
Annual Sum or Average | 1867.00 | 23.04 | 4206.17 | 24.36 | 503.67 | 25.06 |
Minimum of Months | 38.83 | 21.60 | 43.17 | 19.75 | 1.67 | 19.67 |
Maximum of Months | 486.00 | 27.06 | 514.00 | 24.64 | 74.17 | 27.06 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 310.83 | 21.90 | 164.33 | 22.87 | 53.17 | 19.86 |
February | 187.83 | 22.44 | 207.00 | 24.31 | 14.83 | 23.70 |
March | 93.00 | 23.63 | 365.00 | 24.39 | 16.17 | 26.93 |
April | 33.17 | 26.28 | 445.67 | 24.52 | 26.83 | 26.93 |
May | 41.50 | 26.94 | 507.17 | 24.53 | 41.50 | 26.94 |
June | 45.83 | 26.54 | 496.00 | 24.46 | 45.83 | 26.54 |
July | 63.33 | 26.68 | 497.00 | 24.60 | 63.33 | 26.68 |
August | 32.00 | 26.82 | 514.00 | 24.47 | 32.00 | 26.82 |
September | 53.83 | 26.53 | 482.33 | 24.53 | 53.83 | 26.53 |
October | 59.33 | 26.17 | 462.83 | 24.63 | 45.00 | 27.09 |
November | 119.50 | 23.95 | 353.83 | 24.54 | 33.17 | 27.01 |
December | 248.50 | 22.28 | 180.50 | 24.05 | 19.83 | 20.55 |
Annual Sum or Average | 1288.67 | 23.55 | 4675.67 | 24.44 | 445.50 | 25.58 |
Minimum of Months | 32.00 | 21.90 | 164.33 | 22.87 | 14.83 | 19.86 |
Maximum of Months | 310.83 | 26.94 | 514.00 | 24.63 | 63.33 | 27.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.50 | 21.63 | 88.17 | 20.48 | 76.00 | 19.91 |
February | 275.33 | 22.28 | 115.83 | 24.02 | 9.00 | 20.63 |
March | 96.50 | 23.54 | 353.33 | 24.38 | 12.17 | 26.94 |
April | 40.50 | 26.88 | 463.50 | 24.59 | 39.33 | 26.97 |
May | 69.67 | 26.99 | 508.00 | 24.61 | 69.67 | 26.99 |
June | 74.83 | 26.73 | 496.00 | 24.54 | 74.83 | 26.73 |
July | 87.50 | 26.80 | 497.00 | 24.67 | 87.50 | 26.80 |
August | 51.00 | 26.85 | 514.00 | 24.52 | 51.00 | 26.85 |
September | 59.00 | 26.64 | 485.00 | 24.57 | 59.00 | 26.64 |
October | 47.67 | 25.33 | 452.17 | 24.52 | 26.83 | 26.92 |
November | 185.50 | 22.89 | 228.67 | 24.31 | 4.50 | 26.76 |
December | 415.00 | 21.99 | 67.83 | 21.93 | 36.67 | 20.11 |
Annual Sum or Average | 1847.00 | 23.20 | 4269.50 | 24.40 | 546.50 | 25.31 |
Minimum of Months | 40.50 | 21.63 | 67.83 | 20.48 | 4.50 | 19.91 |
Maximum of Months | 444.50 | 26.99 | 514.00 | 24.67 | 87.50 | 26.99 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.55502 | 39.64774 | 0.50165 | 10.89779 |
February | 454.00000 | 24.52965 | 44.31845 | 0.53005 | 11.43952 |
March | 514.00000 | 24.43990 | 48.06682 | 0.54035 | 11.61579 |
April | 485.00000 | 24.54344 | 47.43593 | 0.55921 | 12.15182 |
May | 508.00000 | 24.52828 | 58.15076 | -0.2134 | 7.05510 |
June | 496.00000 | 24.48972 | 61.54056 | -0.1865 | 6.98677 |
July | 497.00000 | 24.62389 | 62.48120 | -0.1216 | 7.26033 |
August | 514.00000 | 24.48583 | 61.41989 | -0.1574 | 7.09651 |
September | 485.00000 | 24.57429 | 62.50543 | -0.1385 | 7.20650 |
October | 502.00000 | 24.61175 | 54.94420 | 0.65120 | 14.55478 |
November | 489.00000 | 24.62246 | 46.73494 | 0.59235 | 13.03090 |
December | 497.00000 | 24.60663 | 39.79300 | 0.52841 | 11.50315 |
Annual Sum or Average | 5943.00000 | 24.55045 | 52.32237 | 0.25429 | 10.04958 |
Minimum of Months | 454.00000 | 24.43990 | 39.64774 | -0.2134 | 6.98677 |
Maximum of Months | 514.00000 | 24.62389 | 62.50543 | 0.65120 | 14.55478 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.31174 | 42.59668 | 0.45554 | 9.93749 |
February | 454.00000 | 24.29432 | 44.35164 | 0.48556 | 10.19672 |
March | 514.00000 | 24.23248 | 46.31600 | 0.50928 | 10.59664 |
April | 485.00000 | 24.18935 | 45.68042 | 0.51430 | 10.63844 |
May | 508.00000 | 24.14613 | 48.53786 | -0.3506 | 7.69091 |
June | 496.00000 | 24.15070 | 49.07128 | -0.3362 | 7.46919 |
July | 497.00000 | 24.20909 | 48.76365 | -0.3140 | 7.23967 |
August | 514.00000 | 24.17675 | 48.81086 | -0.3111 | 7.17597 |
September | 485.00000 | 24.21817 | 49.25642 | -0.3327 | 7.55675 |
October | 502.00000 | 24.30347 | 48.88147 | 0.54972 | 11.52543 |
November | 489.00000 | 24.37854 | 46.47094 | 0.54452 | 11.53624 |
December | 497.00000 | 24.36359 | 40.63004 | 0.48267 | 10.18679 |
Annual Sum or Average | 5943.00000 | 24.24721 | 46.63416 | 0.15486 | 9.30125 |
Minimum of Months | 454.00000 | 24.14613 | 40.63004 | -0.3506 | 7.17597 |
Maximum of Months | 514.00000 | 24.37854 | 49.25642 | 0.54972 | 11.53624 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.55561 | 44.72372 | 0.24441 | 6.74224 |
February | 454.00000 | 23.90949 | 45.51107 | 0.36472 | 8.14840 |
March | 514.00000 | 24.09129 | 46.85277 | 0.44923 | 9.41447 |
April | 485.00000 | 24.05268 | 46.28274 | 0.45038 | 9.35573 |
May | 508.00000 | 24.01883 | 49.17746 | -0.4182 | 8.78243 |
June | 496.00000 | 24.06239 | 49.83219 | -0.3977 | 8.46420 |
July | 497.00000 | 24.04912 | 49.89940 | -0.4087 | 8.66675 |
August | 514.00000 | 24.09868 | 49.96398 | -0.3916 | 8.40249 |
September | 485.00000 | 24.14559 | 49.87817 | -0.3852 | 8.39494 |
October | 502.00000 | 24.20487 | 49.65208 | 0.50442 | 10.49059 |
November | 489.00000 | 24.10553 | 47.32373 | 0.44742 | 9.42565 |
December | 497.00000 | 23.79895 | 42.56104 | 0.30796 | 7.32783 |
Annual Sum or Average | 5943.00000 | 24.00826 | 47.65835 | 0.06088 | 8.63796 |
Minimum of Months | 454.00000 | 23.55561 | 42.56104 | -0.4182 | 6.74224 |
Maximum of Months | 514.00000 | 24.20487 | 49.96398 | 0.50442 | 10.49059 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35186 | 46.56805 | -0.0597 | 7.24433 |
February | 454.00000 | 23.30381 | 47.52376 | 0.21456 | 7.06171 |
March | 514.00000 | 23.98746 | 47.31976 | 0.42587 | 9.09085 |
April | 485.00000 | 24.12815 | 46.08772 | 0.48387 | 10.04585 |
May | 508.00000 | 24.15077 | 48.55224 | -0.3413 | 7.68641 |
June | 496.00000 | 24.16290 | 49.20228 | -0.3295 | 7.53130 |
July | 497.00000 | 24.19156 | 49.23794 | -0.3344 | 7.57813 |
August | 514.00000 | 24.18379 | 49.53207 | -0.3407 | 7.65594 |
September | 485.00000 | 24.20727 | 49.58834 | -0.3498 | 7.92510 |
October | 502.00000 | 24.14583 | 49.92082 | 0.49351 | 10.26460 |
November | 489.00000 | 23.71040 | 48.84652 | 0.34587 | 8.02589 |
December | 497.00000 | 22.76199 | 45.72313 | 0.05035 | 6.44158 |
Annual Sum or Average | 5943.00000 | 23.77724 | 48.18247 | 0.01937 | 8.05182 |
Minimum of Months | 454.00000 | 22.35186 | 45.72313 | -0.3498 | 6.44158 |
Maximum of Months | 514.00000 | 24.20727 | 49.92082 | 0.49351 | 10.26460 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.06022 | 44.07246 | 0.11498 | 6.06561 |
February | 454.00000 | 23.66795 | 45.43565 | 0.30049 | 7.51150 |
March | 514.00000 | 24.13709 | 45.68440 | 0.46917 | 9.85033 |
April | 485.00000 | 24.38042 | 44.09719 | 0.58715 | 12.69155 |
May | 508.00000 | 24.46237 | 46.51759 | -0.1554 | 6.60218 |
June | 496.00000 | 24.41218 | 47.39560 | -0.1458 | 6.37351 |
July | 497.00000 | 24.54405 | 47.53816 | -0.1143 | 6.75952 |
August | 514.00000 | 24.38963 | 47.69057 | -0.1684 | 6.58258 |
September | 485.00000 | 24.40466 | 48.35949 | -0.2244 | 6.90548 |
October | 502.00000 | 24.32511 | 47.94534 | 0.55013 | 11.64087 |
November | 489.00000 | 24.05330 | 46.75958 | 0.42841 | 9.11003 |
December | 497.00000 | 23.51544 | 42.41743 | 0.23121 | 6.69454 |
Annual Sum or Average | 5943.00000 | 24.11562 | 46.16683 | 0.15433 | 8.06101 |
Minimum of Months | 454.00000 | 23.06022 | 42.41743 | -0.2244 | 6.06561 |
Maximum of Months | 514.00000 | 24.54405 | 48.35949 | 0.58715 | 12.69155 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.42077 | 42.90404 | 0.20881 | 6.64572 |
February | 454.00000 | 23.88142 | 44.53480 | 0.37257 | 8.64717 |
March | 514.00000 | 24.23000 | 45.05151 | 0.52646 | 11.35195 |
April | 485.00000 | 24.44826 | 43.62976 | 0.65168 | 14.66044 |
May | 508.00000 | 24.53110 | 46.08341 | -0.0554 | 6.73688 |
June | 496.00000 | 24.43712 | 47.18669 | -0.0968 | 6.37972 |
July | 497.00000 | 24.54348 | 47.49128 | -0.0971 | 6.94814 |
August | 514.00000 | 24.36443 | 47.74333 | -0.1733 | 6.69397 |
September | 485.00000 | 24.43459 | 48.09976 | -0.1792 | 6.71468 |
October | 502.00000 | 24.43538 | 47.35503 | 0.60756 | 13.39589 |
November | 489.00000 | 24.16773 | 46.10521 | 0.47760 | 10.30659 |
December | 497.00000 | 23.59182 | 42.05255 | 0.25992 | 7.14519 |
Annual Sum or Average | 5943.00000 | 24.20925 | 45.69711 | 0.20662 | 8.79358 |
Minimum of Months | 454.00000 | 23.42077 | 42.05255 | -0.1792 | 6.37972 |
Maximum of Months | 514.00000 | 24.54348 | 48.09976 | 0.65168 | 14.66044 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.70381 | 41.43929 | 0.31535 | 8.42493 |
February | 454.00000 | 24.08683 | 43.60437 | 0.45848 | 10.60870 |
March | 514.00000 | 24.30090 | 44.75626 | 0.56570 | 12.33055 |
April | 485.00000 | 24.44946 | 43.77726 | 0.63281 | 14.02355 |
May | 508.00000 | 24.47867 | 46.44140 | -0.1400 | 6.59843 |
June | 496.00000 | 24.41533 | 47.38434 | -0.1441 | 6.40213 |
July | 497.00000 | 24.54668 | 47.51609 | -0.1108 | 6.76652 |
August | 514.00000 | 24.40313 | 47.60110 | -0.1529 | 6.56846 |
September | 485.00000 | 24.46642 | 47.99008 | -0.1590 | 6.69320 |
October | 502.00000 | 24.57397 | 46.80480 | 0.69192 | 16.03737 |
November | 489.00000 | 24.48427 | 44.67404 | 0.63389 | 14.51912 |
December | 497.00000 | 24.10945 | 40.07400 | 0.43774 | 10.27531 |
Annual Sum or Average | 5943.00000 | 24.33603 | 45.18703 | 0.24998 | 9.92011 |
Minimum of Months | 454.00000 | 23.70381 | 40.07400 | -0.1590 | 6.40213 |
Maximum of Months | 514.00000 | 24.57397 | 47.99008 | 0.69192 | 16.03737 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.90791 | 41.23104 | 0.33956 | 8.02468 |
February | 454.00000 | 24.36081 | 42.85410 | 0.52192 | 11.35612 |
March | 514.00000 | 24.50017 | 44.05573 | 0.66442 | 15.02814 |
April | 485.00000 | 24.64576 | 43.00439 | 0.80211 | 19.56110 |
May | 508.00000 | 24.60471 | 45.84931 | 0.01911 | 7.05674 |
June | 496.00000 | 24.55427 | 46.67718 | 0.04335 | 6.85033 |
July | 497.00000 | 24.69816 | 46.59748 | 0.06818 | 7.48637 |
August | 514.00000 | 24.56250 | 46.66260 | 0.05726 | 6.97244 |
September | 485.00000 | 24.58201 | 47.45177 | -0.0668 | 6.72935 |
October | 502.00000 | 24.63533 | 46.62029 | 0.71264 | 16.59709 |
November | 489.00000 | 24.59064 | 44.49785 | 0.64701 | 14.60402 |
December | 497.00000 | 24.47693 | 38.98554 | 0.53211 | 11.57535 |
Annual Sum or Average | 5943.00000 | 24.51037 | 44.55580 | 0.35987 | 10.96628 |
Minimum of Months | 454.00000 | 23.90791 | 38.98554 | -0.0668 | 6.72935 |
Maximum of Months | 514.00000 | 24.69816 | 47.45177 | 0.80211 | 19.56110 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.51384 | 47.28199 | -0.2699 | 7.71176 |
February | 454.00000 | 22.65238 | 47.99212 | 0.04464 | 6.41951 |
March | 514.00000 | 23.85114 | 46.61727 | 0.37851 | 8.53648 |
April | 485.00000 | 24.33874 | 44.17647 | 0.55035 | 11.76198 |
May | 508.00000 | 24.47839 | 46.81671 | -0.1582 | 6.70054 |
June | 496.00000 | 24.43016 | 48.30158 | -0.1491 | 6.50117 |
July | 497.00000 | 24.56599 | 49.18988 | -0.1243 | 6.91034 |
August | 514.00000 | 24.42311 | 49.15309 | -0.1911 | 6.83761 |
September | 485.00000 | 24.42987 | 49.85496 | -0.2272 | 7.14789 |
October | 502.00000 | 24.20115 | 48.75963 | 0.50214 | 10.60347 |
November | 489.00000 | 23.35070 | 48.77717 | 0.24134 | 6.99079 |
December | 497.00000 | 21.90191 | 46.03860 | -0.1655 | 6.69350 |
Annual Sum or Average | 5943.00000 | 23.68572 | 47.74585 | 0.03527 | 7.73857 |
Minimum of Months | 454.00000 | 21.51384 | 44.17647 | -0.2699 | 6.41951 |
Maximum of Months | 514.00000 | 24.56599 | 49.85496 | 0.55035 | 11.76198 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.30111 | 45.05793 | -0.0808 | 6.66974 |
February | 385.00000 | 23.41626 | 45.02068 | 0.23408 | 7.51663 |
March | 433.00000 | 24.25826 | 44.40800 | 0.50695 | 11.23411 |
April | 410.00000 | 24.63826 | 42.54497 | 0.67524 | 15.56192 |
May | 430.00000 | 24.68554 | 45.84535 | -0.0153 | 7.15851 |
June | 418.00000 | 24.59670 | 47.59836 | -0.0525 | 6.69039 |
July | 422.00000 | 24.74317 | 48.53245 | -0.0420 | 7.35417 |
August | 433.00000 | 24.57166 | 48.44941 | -0.1240 | 6.92031 |
September | 410.00000 | 24.60988 | 49.17835 | -0.1358 | 7.01350 |
October | 427.00000 | 24.55177 | 47.11226 | 0.61400 | 13.79930 |
November | 417.00000 | 23.93898 | 46.13304 | 0.39564 | 9.12559 |
December | 422.00000 | 22.73480 | 43.68082 | 0.03243 | 6.38484 |
Annual Sum or Average | 5034.00000 | 24.09039 | 46.13916 | 0.16631 | 8.78604 |
Minimum of Months | 385.00000 | 22.30111 | 42.54497 | -0.1358 | 6.38484 |
Maximum of Months | 433.00000 | 24.74317 | 49.17835 | 0.67524 | 15.56192 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.30410 | 41.99864 | 0.20822 | 8.16164 |
February | 454.00000 | 23.84277 | 43.92944 | 0.38623 | 9.96029 |
March | 514.00000 | 24.23732 | 44.81817 | 0.53466 | 11.79470 |
April | 485.00000 | 24.45660 | 43.67612 | 0.61250 | 13.49550 |
May | 508.00000 | 24.49372 | 46.73552 | -0.1439 | 6.67743 |
June | 496.00000 | 24.43114 | 48.29614 | -0.1500 | 6.51574 |
July | 497.00000 | 24.57049 | 49.14309 | -0.1201 | 6.91742 |
August | 514.00000 | 24.44540 | 48.96453 | -0.1702 | 6.81340 |
September | 485.00000 | 24.51377 | 49.29406 | -0.1490 | 6.95060 |
October | 502.00000 | 24.61565 | 46.93208 | 0.69506 | 16.27097 |
November | 489.00000 | 24.40452 | 44.45723 | 0.60202 | 13.96224 |
December | 497.00000 | 23.77865 | 40.51531 | 0.33934 | 9.43489 |
Annual Sum or Average | 5943.00000 | 24.26012 | 45.74766 | 0.21820 | 9.73358 |
Minimum of Months | 454.00000 | 23.30410 | 40.51531 | -0.1702 | 6.51574 |
Maximum of Months | 514.00000 | 24.61565 | 49.29406 | 0.69506 | 16.27097 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.39386 | 44.87869 | -0.0476 | 6.72896 |
February | 454.00000 | 23.38670 | 45.63714 | 0.23810 | 7.75684 |
March | 514.00000 | 24.20790 | 45.10915 | 0.51559 | 11.28360 |
April | 485.00000 | 24.54661 | 43.38086 | 0.68189 | 15.68403 |
May | 508.00000 | 24.59231 | 46.26715 | -0.0259 | 7.13030 |
June | 496.00000 | 24.52342 | 47.78375 | -0.0321 | 6.80379 |
July | 497.00000 | 24.64742 | 48.57625 | -0.0449 | 7.30439 |
August | 514.00000 | 24.50362 | 48.53943 | -0.1116 | 6.87200 |
September | 485.00000 | 24.55095 | 49.14711 | -0.1253 | 7.05425 |
October | 502.00000 | 24.47167 | 47.61455 | 0.61529 | 13.70079 |
November | 489.00000 | 23.97258 | 46.42471 | 0.42116 | 9.50759 |
December | 497.00000 | 22.85374 | 43.37790 | 0.07144 | 6.58630 |
Annual Sum or Average | 5943.00000 | 24.05877 | 46.40243 | 0.17847 | 8.86541 |
Minimum of Months | 454.00000 | 22.39386 | 43.37790 | -0.1253 | 6.58630 |
Maximum of Months | 514.00000 | 24.64742 | 49.14711 | 0.68189 | 15.68403 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.99743 | 48.15372 | -0.4231 | 10.83832 |
February | 454.00000 | 22.22351 | 49.11822 | -0.0675 | 7.15830 |
March | 514.00000 | 23.69441 | 47.12771 | 0.34454 | 8.49313 |
April | 485.00000 | 24.35362 | 44.35081 | 0.56862 | 12.39912 |
May | 508.00000 | 24.50121 | 46.82466 | -0.1214 | 6.80117 |
June | 496.00000 | 24.45079 | 48.32191 | -0.1131 | 6.56499 |
July | 497.00000 | 24.58996 | 49.35415 | -0.0902 | 7.09405 |
August | 514.00000 | 24.43645 | 49.31333 | -0.1658 | 6.86560 |
September | 485.00000 | 24.44828 | 50.06632 | -0.2068 | 7.21132 |
October | 502.00000 | 24.12127 | 49.09948 | 0.48661 | 10.55277 |
November | 489.00000 | 22.94553 | 49.94230 | 0.14111 | 6.87646 |
December | 497.00000 | 21.29438 | 47.47779 | -0.3331 | 9.12832 |
Annual Sum or Average | 5943.00000 | 23.51444 | 48.25604 | 0.00158 | 8.33417 |
Minimum of Months | 454.00000 | 20.99743 | 44.35081 | -0.4231 | 6.56499 |
Maximum of Months | 514.00000 | 24.58996 | 50.06632 | 0.56862 | 12.39912 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.66349 | 46.53887 | -0.2460 | 8.70749 |
February | 454.00000 | 23.04097 | 46.58990 | 0.14487 | 7.40627 |
March | 514.00000 | 24.10039 | 45.34655 | 0.48701 | 10.98077 |
April | 485.00000 | 24.52471 | 43.46714 | 0.68363 | 15.77044 |
May | 508.00000 | 24.57771 | 46.29037 | 0.00069 | 7.13666 |
June | 496.00000 | 24.49689 | 47.91743 | -0.0363 | 6.67216 |
July | 497.00000 | 24.62942 | 48.97123 | -0.0370 | 7.38085 |
August | 514.00000 | 24.47089 | 48.91287 | -0.1197 | 6.85995 |
September | 485.00000 | 24.50743 | 49.55053 | -0.1364 | 7.00161 |
October | 502.00000 | 24.39232 | 47.81179 | 0.59536 | 13.35529 |
November | 489.00000 | 23.63586 | 47.36732 | 0.32682 | 8.48981 |
December | 497.00000 | 22.10299 | 45.46793 | -0.1295 | 7.36596 |
Annual Sum or Average | 5943.00000 | 23.85104 | 47.02342 | 0.12699 | 8.92950 |
Minimum of Months | 454.00000 | 21.66349 | 43.46714 | -0.2460 | 6.67216 |
Maximum of Months | 514.00000 | 24.62942 | 49.55053 | 0.68363 | 15.77044 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.74468 | 43.09589 | 0.04808 | 8.93540 |
February | 454.00000 | 23.48480 | 44.96237 | 0.28876 | 9.53959 |
March | 514.00000 | 24.11474 | 45.30431 | 0.50728 | 11.59568 |
April | 485.00000 | 24.46023 | 43.89937 | 0.62800 | 14.06940 |
May | 508.00000 | 24.51396 | 46.75540 | -0.1083 | 6.80113 |
June | 496.00000 | 24.45100 | 48.31950 | -0.1143 | 6.57695 |
July | 497.00000 | 24.59340 | 49.31526 | -0.0865 | 7.10569 |
August | 514.00000 | 24.45549 | 49.14046 | -0.1462 | 6.86407 |
September | 485.00000 | 24.51856 | 49.54093 | -0.1333 | 7.08470 |
October | 502.00000 | 24.53718 | 47.26853 | 0.67913 | 15.94847 |
November | 489.00000 | 24.15909 | 45.22489 | 0.53292 | 12.91115 |
December | 497.00000 | 23.27390 | 41.81941 | 0.19489 | 8.97741 |
Annual Sum or Average | 5943.00000 | 24.11274 | 46.23357 | 0.18921 | 9.69119 |
Minimum of Months | 454.00000 | 22.74468 | 41.81941 | -0.1462 | 6.57695 |
Maximum of Months | 514.00000 | 24.59340 | 49.54093 | 0.67913 | 15.94847 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.87852 | 45.74782 | -0.1906 | 8.63928 |
February | 454.00000 | 23.00230 | 46.65314 | 0.14042 | 7.80360 |
March | 514.00000 | 24.08961 | 45.57228 | 0.48985 | 11.12129 |
April | 485.00000 | 24.54885 | 43.60799 | 0.69590 | 16.23133 |
May | 508.00000 | 24.59757 | 46.34104 | 0.00255 | 7.39113 |
June | 496.00000 | 24.52641 | 47.86834 | -0.0036 | 6.99923 |
July | 497.00000 | 24.65591 | 48.79339 | -0.0177 | 7.53809 |
August | 514.00000 | 24.50642 | 48.73936 | -0.0912 | 6.96699 |
September | 485.00000 | 24.55583 | 49.38686 | -0.1102 | 7.17520 |
October | 502.00000 | 24.41212 | 47.91618 | 0.60409 | 13.57828 |
November | 489.00000 | 23.67012 | 47.34649 | 0.34468 | 8.95292 |
December | 497.00000 | 22.30151 | 44.68107 | -0.0748 | 7.51426 |
Annual Sum or Average | 5943.00000 | 23.90178 | 46.89075 | 0.14847 | 9.15883 |
Minimum of Months | 454.00000 | 21.87852 | 43.60799 | -0.1906 | 6.96699 |
Maximum of Months | 514.00000 | 24.65591 | 49.38686 | 0.69590 | 16.23133 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.705884E+11 | 102236.58 | 25-JAN-14:40 | 423.65 | 0.341299E+12 | 0.00 | 0.411887E+12 | 2.39 | 7.16 | 25-JAN-14:40 | 0.00 | 0.00 |
February | 0.960918E+11 | 166653.58 | 22-FEB-15:30 | 413.29 | 0.571013E+12 | 0.00 | 0.667105E+12 | 3.18 | 7.54 | 22-FEB-14:00 | 0.00 | 0.00 |
March | 0.174938E+12 | 185821.87 | 30-MAR-10:50 | 564.42 | 0.117495E+13 | 0.00 | 0.134989E+13 | 4.55 | 7.56 | 22-MAR-15:50 | 0.00 | 0.00 |
April | 0.233312E+12 | 193231.75 | 26-APR-18:50 | 672.04 | 0.159908E+13 | 0.00 | 0.183240E+13 | 5.86 | 7.56 | 06-APR-16:30 | 0.00 | 0.00 |
May | 0.292657E+12 | 202046.52 | 24-MAY-05:02 | 687.77 | 0.198126E+13 | 0.00 | 0.227392E+13 | 6.09 | 7.50 | 08-MAY-05:03 | 0.00 | 0.00 |
June | 0.319129E+12 | 218703.14 | 21-JUN-15:10 | 665.12 | 0.207427E+13 | 0.00 | 0.239340E+13 | 5.83 | 7.52 | 12-JUN-05:03 | 0.00 | 0.00 |
July | 0.350514E+12 | 219140.27 | 15-JUL-21:42 | 706.50 | 0.218568E+13 | 0.00 | 0.253620E+13 | 5.65 | 7.19 | 11-JUL-03:03 | 0.00 | 0.00 |
August | 0.339033E+12 | 218825.07 | 05-AUG-18:22 | 712.18 | 0.209694E+13 | 0.00 | 0.243597E+13 | 5.57 | 7.18 | 16-AUG-03:02 | 0.00 | 0.00 |
September | 0.276755E+12 | 213924.48 | 17-SEP-17:40 | 624.17 | 0.177544E+13 | 0.00 | 0.205219E+13 | 5.22 | 7.46 | 29-SEP-03:03 | 0.00 | 0.00 |
October | 0.208072E+12 | 190372.66 | 13-OCT-16:10 | 590.49 | 0.142368E+13 | 0.00 | 0.163175E+13 | 4.96 | 7.54 | 27-OCT-09:50 | 0.00 | 0.00 |
November | 0.145353E+12 | 183948.84 | 13-NOV-13:30 | 499.51 | 0.946563E+12 | 0.00 | 0.109192E+13 | 3.98 | 7.54 | 13-NOV-17:00 | 0.00 | 0.00 |
December | 0.854621E+11 | 121193.85 | 01-DEC-13:10 | 454.84 | 0.449423E+12 | 0.00 | 0.534885E+12 | 2.79 | 7.38 | 01-DEC-13:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.259191E+13 | 7013.97 | 0.166196E+14 | 0.192115E+14 | 4.68 | |||||||
Minimum of Months | 0.705884E+11 | 102236.58 | 413.29 | 0.341299E+12 | 0.00 | 0.411887E+12 | 2.39 | 7.16 | 0.00 | 0.00 | ||
Maximum of Months | 0.350514E+12 | 219140.27 | 712.18 | 0.218568E+13 | 0.00 | 0.253620E+13 | 6.09 | 7.56 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.163826E+11 | 132793.31 | 29-MAR-11:05 | 43.92 | 0.116139E+12 | 0.00 | 0.132522E+12 | 0.42 | 7.31 | 27-MAR-14:05 | 0.00 | 0.00 |
April | 0.591207E+11 | 147201.64 | 18-APR-15:30 | 150.13 | 0.412936E+12 | 0.00 | 0.472057E+12 | 1.45 | 7.43 | 07-APR-14:10 | 0.00 | 0.00 |
May | 0.141071E+12 | 202046.52 | 24-MAY-05:02 | 312.99 | 0.949360E+12 | 0.00 | 0.109043E+13 | 2.83 | 7.27 | 28-MAY-17:43 | 0.00 | 0.00 |
June | 0.194079E+12 | 218703.14 | 21-JUN-15:10 | 388.14 | 0.125451E+13 | 0.00 | 0.144859E+13 | 3.48 | 7.16 | 06-JUN-05:02 | 0.00 | 0.00 |
July | 0.233440E+12 | 219140.27 | 15-JUL-21:42 | 449.97 | 0.146350E+13 | 0.00 | 0.169694E+13 | 3.76 | 6.89 | 01-JUL-05:01 | 0.00 | 0.00 |
August | 0.238836E+12 | 218825.07 | 05-AUG-18:22 | 454.43 | 0.150037E+13 | 0.00 | 0.173920E+13 | 3.83 | 6.94 | 31-AUG-03:01 | 0.00 | 0.00 |
September | 0.154990E+12 | 212645.59 | 13-SEP-03:02 | 330.84 | 0.100480E+13 | 0.00 | 0.115979E+13 | 2.97 | 7.22 | 29-SEP-05:01 | 0.00 | 0.00 |
October | 0.520688E+11 | 177817.19 | 04-OCT-05:02 | 131.18 | 0.362519E+12 | 0.00 | 0.414588E+12 | 1.23 | 7.33 | 24-OCT-14:05 | 0.00 | 0.00 |
November | 0.777955E+10 | 123924.22 | 15-NOV-15:05 | 22.50 | 0.552995E+11 | 0.00 | 0.630791E+11 | 0.21 | 7.35 | 15-NOV-15:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.109777E+13 | 2284.10 | 0.711943E+13 | 0.821720E+13 | 1.69 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.238836E+12 | 219140.27 | 454.43 | 0.150037E+13 | 0.00 | 0.173920E+13 | 3.83 | 7.43 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.559544E+11 | 744.00 | 43776.24 | 02-JAN-13:40 | 189114.87 | 12-JAN-17:10 | 22.31 | 19.00 | 14.53 |
February | 0.877723E+11 | 672.00 | 43776.24 | 01-FEB-10:15 | 344724.61 | 20-FEB-00:11 | 27.39 | 21.21 | 14.53 |
March | 0.117165E+12 | 744.00 | 43776.24 | 01-MAR-00:10 | 520685.84 | 28-MAR-16:00 | 35.92 | 26.74 | 14.53 |
April | 0.113468E+12 | 720.00 | 43776.24 | 01-APR-00:05 | 672633.36 | 16-APR-18:01 | 47.40 | 35.09 | 14.53 |
May | 0.117250E+12 | 744.00 | 43776.24 | 01-MAY-00:10 | 309982.76 | 01-MAY-00:10 | 39.03 | 34.93 | 14.53 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:03 | 402565.21 | 11-JUN-17:31 | 44.14 | 37.02 | 14.53 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:05 | 561734.09 | 02-JUL-17:31 | 46.56 | 36.52 | 14.53 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:03 | 668731.94 | 27-AUG-16:01 | 48.73 | 36.14 | 14.53 |
September | 0.113468E+12 | 720.00 | 43776.24 | 01-SEP-00:05 | 381485.85 | 01-SEP-00:05 | 34.81 | 30.70 | 14.53 |
October | 0.117250E+12 | 744.00 | 43776.24 | 01-OCT-00:05 | 374394.31 | 03-OCT-15:20 | 34.85 | 28.23 | 14.53 |
November | 0.111011E+12 | 720.00 | 43776.24 | 01-NOV-00:10 | 500963.51 | 08-NOV-16:10 | 33.26 | 24.14 | 14.53 |
December | 0.106408E+12 | 744.00 | 43776.24 | 01-DEC-07:15 | 622118.02 | 28-DEC-15:05 | 32.74 | 21.13 | 14.53 |
Annual Sum or Average | 0.128772E+13 | 8760.00 | 37.31 | 29.28 | 14.53 | ||||
Minimum of Months | 0.559544E+11 | 672.00 | 43776.24 | 189114.87 | 22.31 | 19.00 | 14.53 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 672633.36 | 48.73 | 37.02 | 14.53 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.339423E+09 | 282.43 | 1677.78 | 13-JAN-15:30 | 809370.51 | 25-JAN-14:40 | 21.98 | 21.30 | 26.59 |
February | 0.161392E+10 | 336.94 | 19888.71 | 15-FEB-15:30 | 1314513.28 | 22-FEB-16:40 | 22.68 | 21.47 | 31.99 |
March | 0.123944E+11 | 512.19 | 19888.71 | 06-MAR-10:20 | 1353332.51 | 15-MAR-13:40 | 23.60 | 21.49 | 40.63 |
April | 0.289262E+11 | 632.03 | 19888.71 | 01-APR-08:70 | 1353110.34 | 10-APR-12:20 | 24.95 | 22.03 | 49.28 |
May | 0.468048E+11 | 687.77 | 19888.71 | 01-MAY-03:17 | 1321327.45 | 17-MAY-16:00 | 28.07 | 24.62 | 46.48 |
June | 0.475488E+11 | 665.12 | 19888.71 | 01-JUN-00:03 | 1539096.03 | 21-JUN-15:40 | 30.37 | 26.63 | 45.17 |
July | 0.505848E+11 | 706.50 | 19888.71 | 01-JUL-00:05 | 1442658.07 | 05-JUL-16:00 | 32.02 | 28.17 | 46.67 |
August | 0.509917E+11 | 712.18 | 19888.71 | 01-AUG-00:03 | 1539049.09 | 28-AUG-15:30 | 31.69 | 27.95 | 47.92 |
September | 0.446316E+11 | 624.17 | 19888.71 | 01-SEP-00:05 | 1407435.96 | 14-SEP-15:30 | 30.10 | 26.93 | 42.26 |
October | 0.281524E+11 | 575.11 | 19888.71 | 01-OCT-00:05 | 1257974.63 | 24-OCT-16:30 | 24.81 | 22.32 | 41.55 |
November | 0.665948E+10 | 439.96 | 19888.71 | 01-NOV-12:30 | 1353407.25 | 13-NOV-11:30 | 23.26 | 21.48 | 36.68 |
December | 0.589623E+09 | 324.34 | 2474.32 | 28-DEC-15:00 | 946330.17 | 01-DEC-13:30 | 22.15 | 21.27 | 30.19 |
Annual Sum or Average | 0.319237E+12 | 6498.75 | 26.33 | 23.82 | 40.49 | ||||
Minimum of Months | 0.339423E+09 | 282.43 | 1677.78 | 809370.51 | 21.98 | 21.27 | 26.59 | ||
Maximum of Months | 0.509917E+11 | 712.18 | 19888.71 | 1539096.03 | 32.02 | 28.17 | 49.28 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 21.98 | 21.98 | 0.00 |
February | 88687727.67 | 2.08 | 19888.71 | 24-FEB-14:00 | 821463.49 | 22-FEB-14:40 | 22.68 | 22.66 | 0.10 |
March | 0.502303E+10 | 77.28 | 19888.71 | 06-MAR-10:50 | 1011844.61 | 27-MAR-14:05 | 23.60 | 23.16 | 4.86 |
April | 0.149384E+11 | 228.65 | 19888.71 | 01-APR-09:40 | 1154806.16 | 18-APR-15:30 | 24.95 | 23.64 | 15.50 |
May | 0.357031E+11 | 498.91 | 19888.71 | 01-MAY-05:04 | 1321327.45 | 17-MAY-16:00 | 28.07 | 25.31 | 32.20 |
June | 0.434764E+11 | 607.22 | 19888.71 | 01-JUN-03:06 | 1539096.03 | 21-JUN-15:40 | 30.37 | 26.77 | 40.65 |
July | 0.482668E+11 | 674.12 | 19888.71 | 01-JUL-00:05 | 1442658.07 | 05-JUL-16:00 | 32.02 | 28.20 | 44.22 |
August | 0.467671E+11 | 653.18 | 19888.71 | 01-AUG-00:03 | 1539049.09 | 28-AUG-15:30 | 31.69 | 28.01 | 43.46 |
September | 0.389590E+11 | 544.12 | 19888.71 | 01-SEP-00:05 | 1407435.96 | 14-SEP-15:30 | 30.10 | 27.04 | 36.01 |
October | 0.161857E+11 | 230.08 | 19888.71 | 01-OCT-00:05 | 1109913.76 | 03-OCT-15:20 | 24.81 | 23.53 | 14.53 |
November | 0.183102E+10 | 34.42 | 19888.71 | 03-NOV-15:00 | 1014787.27 | 07-NOV-15:05 | 23.26 | 23.05 | 2.27 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 22.15 | 22.15 | 0.00 |
Annual Sum or Average | 0.251239E+12 | 3550.06 | 26.33 | 24.64 | 19.60 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.98 | 21.98 | 0.00 | ||
Maximum of Months | 0.482668E+11 | 674.12 | 19888.71 | 1539096.03 | 32.02 | 28.20 | 44.22 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.362601E+11 | 0.00 | 221.54 | 1116347.16 | 03-JAN-05:11 | 0.00 | 59.05 | 65.39 | 0.21 | 0.00 | 0.01 | 0.90 | 03-JAN-05:11 |
February | 0.641002E+10 | 0.00 | 74.31 | 900209.61 | 11-FEB-06:03 | 0.00 | 59.56 | 62.30 | 0.03 | 0.00 | 0.00 | 0.73 | 11-FEB-06:03 |
March | 0.153993E+10 | 0.00 | 4.04 | 254122.30 | 05-MAR-20:20 | 0.00 | 72.26 | 72.32 | 0.01 | 0.00 | 0.00 | 0.21 | 05-MAR-20:20 |
April | 0.749032E+09 | 0.00 | 0.97 | 215123.62 | 02-APR-16:59 | 0.00 | 72.66 | 72.67 | 0.01 | 0.00 | 0.00 | 0.17 | 02-APR-16:59 |
May | 0.761619E+09 | 0.00 | 1.00 | 213378.15 | 07-MAY-20:58 | 0.00 | 72.75 | 72.76 | 0.01 | 0.00 | 0.00 | 0.17 | 07-MAY-20:58 |
June | 0.548037E+09 | 0.00 | 0.73 | 211875.71 | 04-JUN-20:54 | 0.00 | 72.84 | 72.85 | 0.01 | 0.00 | 0.00 | 0.17 | 04-JUN-20:54 |
July | 0.835930E+09 | 0.00 | 1.13 | 206018.25 | 04-JUL-07:45 | 0.00 | 73.04 | 73.06 | 0.01 | 0.00 | 0.00 | 0.17 | 04-JUL-07:45 |
August | 0.559928E+09 | 0.00 | 0.76 | 205490.91 | 06-AUG-02:28 | 0.00 | 73.06 | 73.07 | 0.01 | 0.00 | 0.00 | 0.17 | 06-AUG-02:28 |
September | 0.970701E+09 | 0.00 | 1.32 | 206166.68 | 03-SEP-13:07 | 0.00 | 73.05 | 73.07 | 0.01 | 0.00 | 0.00 | 0.17 | 03-SEP-13:07 |
October | 0.107736E+10 | 0.00 | 1.41 | 214262.29 | 29-OCT-13:30 | 0.00 | 72.70 | 72.72 | 0.01 | 0.00 | 0.00 | 0.17 | 29-OCT-13:30 |
November | 0.242787E+10 | 0.00 | 22.27 | 276471.36 | 26-NOV-11:46 | 0.00 | 71.66 | 72.02 | 0.02 | 0.00 | 0.00 | 0.22 | 26-NOV-11:46 |
December | 0.133903E+11 | 0.00 | 157.66 | 748887.75 | 23-DEC-06:03 | 0.00 | 58.71 | 63.63 | 0.07 | 0.00 | 0.00 | 0.61 | 23-DEC-06:03 |
Annual Sum or Average | 0.655308E+11 | 487.13 | 69.32 | 70.53 | 0.03 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.548037E+09 | 0.00 | 0.73 | 205490.91 | 0.00 | 58.71 | 62.30 | 0.01 | 0.00 | 0.00 | 0.17 | ||
Maximum of Months | 0.362601E+11 | 0.00 | 221.54 | 1116347.16 | 0.00 | 73.06 | 73.07 | 0.21 | 0.00 | 0.01 | 0.90 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 22.31 | 22.31 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 27.39 | 27.39 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 35.92 | 35.92 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 47.40 | 47.40 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 39.03 | 39.03 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 44.14 | 44.14 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 46.56 | 46.56 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 48.73 | 48.73 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 34.81 | 34.81 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 34.85 | 34.85 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 33.26 | 33.26 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 32.74 | 32.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 37.31 | 37.31 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 | 22.31 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.73 | 48.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.513482E+11 | 0.00 | 406.96 | 0.509976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120929.24 | 16-JAN-19:22 | 103496.31 | 01-JAN-13:52 | 0.00 | 0.00 | 0.00 |
February | 0.529643E+11 | 0.00 | 378.59 | 0.527764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143617.94 | 26-FEB-19:31 | 119088.78 | 20-FEB-13:52 | 0.00 | 0.00 | 0.00 |
March | 0.751096E+11 | 0.00 | 446.49 | 0.745583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146828.42 | 11-MAR-04:53 | 107045.37 | 26-MAR-18:20 | 0.00 | 0.00 | 0.00 |
April | 0.884959E+11 | 0.00 | 440.34 | 0.862386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153784.07 | 27-APR-03:01 | 127473.05 | 16-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.114756E+12 | 0.00 | 481.06 | 0.102080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 187818.22 | 21-MAY-21:17 | 126925.54 | 07-MAY-14:54 | 0.00 | 0.00 | 0.00 |
June | 0.134895E+12 | 0.00 | 478.26 | 0.106096E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 208274.11 | 25-JUN-18:51 | 122561.04 | 04-JUN-14:11 | 0.00 | 0.00 | 0.00 |
July | 0.158483E+12 | 0.00 | 507.74 | 0.107071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 215207.07 | 16-JUL-12:31 | 111609.05 | 04-JUL-19:01 | 0.00 | 0.00 | 0.00 |
August | 0.173444E+12 | 0.00 | 523.54 | 0.112235E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 221208.93 | 27-AUG-12:41 | 98322.23 | 08-AUG-03:01 | 0.00 | 0.00 | 0.00 |
September | 0.137059E+12 | 0.00 | 488.60 | 0.966054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 210723.13 | 10-SEP-20:52 | 105279.71 | 24-SEP-12:30 | 0.00 | 0.00 | 0.00 |
October | 0.995298E+11 | 0.00 | 489.21 | 0.919286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157731.82 | 04-OCT-03:41 | 119301.17 | 15-OCT-11:26 | 0.00 | 0.00 | 0.00 |
November | 0.766402E+11 | 0.00 | 448.09 | 0.759399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137180.68 | 09-NOV-04:01 | 116718.06 | 05-NOV-13:30 | 0.00 | 0.00 | 0.00 |
December | 0.602384E+11 | 0.00 | 417.07 | 0.600706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118219.78 | 17-DEC-13:01 | 110081.60 | 25-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.122296E+13 | 5505.95 | 0.101660E+13 | ||||||||||||
Minimum of Months | 0.513482E+11 | 0.00 | 378.59 | 0.509976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 118219.78 | 98322.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.173444E+12 | 0.00 | 523.54 | 0.112235E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 221208.93 | 127473.05 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.353038E+11 | 0.00 | 356.33 | 0.349963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67195.15 | 12-JAN-15:00 | 67195.15 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.567291E+11 | 0.00 | 383.89 | 0.552632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97413.16 | 21-FEB-15:00 | 97413.16 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.119287E+12 | 0.00 | 543.46 | 0.111973E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 163051.85 | 11-MAR-06:02 | 153131.52 | 11-MAR-06:01 | 0.00 | 0.00 | 0.00 |
April | 0.182938E+12 | 0.00 | 624.98 | 0.168870E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 213823.32 | 27-APR-05:02 | 186085.70 | 27-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.239960E+12 | 0.00 | 640.17 | 0.191163E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 247303.06 | 24-MAY-05:02 | 194235.92 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.281154E+12 | 0.00 | 623.34 | 0.195510E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256335.43 | 08-JUN-05:02 | 195637.09 | 13-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.320552E+12 | 0.00 | 647.76 | 0.186249E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 268992.06 | 08-JUL-05:02 | 198035.87 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.334493E+12 | 0.00 | 660.40 | 0.189751E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 272023.32 | 28-AUG-05:03 | 191911.21 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.242419E+12 | 0.00 | 571.60 | 0.142564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 255055.73 | 05-SEP-05:02 | 176418.71 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.157288E+12 | 0.00 | 550.20 | 0.129864E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 222765.59 | 04-OCT-05:02 | 173042.11 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.945785E+11 | 0.00 | 461.52 | 0.909254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119864.16 | 06-NOV-14:40 | 112526.22 | 13-NOV-14:50 | 0.00 | 0.00 | 0.00 |
December | 0.544789E+11 | 0.00 | 422.81 | 0.543324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85160.93 | 04-DEC-14:30 | 85160.93 | 04-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211918E+13 | 6486.45 | 0.155146E+13 | ||||||||||||
Minimum of Months | 0.353038E+11 | 0.00 | 356.33 | 0.349963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67195.15 | 67195.15 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.334493E+12 | 0.00 | 660.40 | 0.195510E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 272023.32 | 198035.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.231093E+12 | 0.00 | 324.86 | 0.229363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 548331.23 | 12-JAN-15:05 | 548331.23 | 12-JAN-15:05 | 0.00 | 0.00 | 0.00 |
February | 0.403832E+12 | 0.00 | 352.39 | 0.393556E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 811647.68 | 24-FEB-15:05 | 804583.25 | 22-FEB-15:05 | 0.00 | 0.00 | 0.00 |
March | 0.916989E+12 | 0.00 | 470.03 | 0.862028E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1628699.36 | 29-MAR-03:01 | 1444652.45 | 11-MAR-06:01 | 0.00 | 0.00 | 0.00 |
April | 0.149973E+13 | 0.00 | 552.77 | 0.137572E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1683879.56 | 25-APR-05:01 | 1538693.81 | 21-APR-05:01 | 0.00 | 0.00 | 0.00 |
May | 0.227329E+13 | 0.00 | 625.88 | 0.179181E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2188503.15 | 24-MAY-05:01 | 1575482.05 | 23-MAY-03:01 | 0.00 | 0.00 | 0.00 |
June | 0.259906E+13 | 0.00 | 594.30 | 0.176674E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2325512.98 | 27-JUN-05:01 | 1761309.58 | 12-JUN-05:01 | 0.00 | 0.00 | 0.00 |
July | 0.284947E+13 | 0.00 | 596.93 | 0.157161E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2688171.83 | 25-JUL-05:02 | 1669458.68 | 06-JUL-05:01 | 0.00 | 0.00 | 0.00 |
August | 0.278385E+13 | 0.00 | 577.60 | 0.147527E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2617308.92 | 11-AUG-05:02 | 1667680.65 | 15-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.214881E+13 | 0.00 | 512.86 | 0.123413E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2565219.20 | 08-SEP-05:02 | 1628146.05 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.130690E+13 | 0.00 | 485.19 | 0.107268E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2134055.52 | 04-OCT-05:02 | 1627988.95 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.701350E+12 | 0.00 | 422.99 | 0.673069E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1012484.18 | 08-NOV-15:05 | 957365.21 | 08-NOV-15:05 | 0.00 | 0.00 | 0.00 |
December | 0.306683E+12 | 0.00 | 366.33 | 0.305759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 634332.78 | 01-DEC-15:05 | 634332.78 | 01-DEC-15:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180210E+14 | 5882.12 | 0.127517E+14 | ||||||||||||
Minimum of Months | 0.231093E+12 | 0.00 | 324.86 | 0.229363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 548331.23 | 548331.23 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.284947E+13 | 0.00 | 625.88 | 0.179181E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2688171.83 | 1761309.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.202031E+11 | 0.00 | 300.92 | 0.200362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51086.92 | 12-JAN-15:40 | 51086.92 | 12-JAN-15:40 | 0.00 | 0.00 | 0.00 |
February | 0.374761E+11 | 0.00 | 339.36 | 0.364263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88518.22 | 22-FEB-15:00 | 88518.22 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.940052E+11 | 0.00 | 458.63 | 0.884076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178349.18 | 11-MAR-06:01 | 157828.02 | 11-MAR-06:01 | 0.00 | 0.00 | 0.00 |
April | 0.163212E+12 | 0.00 | 548.46 | 0.150521E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 184904.00 | 16-APR-16:41 | 169675.76 | 16-APR-14:42 | 0.00 | 0.00 | 0.00 |
May | 0.248366E+12 | 0.00 | 628.28 | 0.199907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 244501.51 | 24-MAY-05:01 | 198762.64 | 29-MAY-16:31 | 0.00 | 0.00 | 0.00 |
June | 0.280793E+12 | 0.00 | 596.59 | 0.197785E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 261307.95 | 16-JUN-05:02 | 203688.30 | 12-JUN-05:01 | 0.00 | 0.00 | 0.00 |
July | 0.301821E+12 | 0.00 | 601.83 | 0.173658E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 299079.88 | 25-JUL-03:01 | 202986.66 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.292655E+12 | 0.00 | 583.27 | 0.161324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 279592.58 | 27-AUG-15:31 | 199105.54 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.224037E+12 | 0.00 | 514.82 | 0.132339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 272591.16 | 09-SEP-05:01 | 176874.05 | 05-SEP-03:01 | 0.00 | 0.00 | 0.00 |
October | 0.133112E+12 | 0.00 | 474.65 | 0.109983E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 206729.35 | 11-OCT-03:01 | 171687.37 | 11-OCT-03:01 | 0.00 | 0.00 | 0.00 |
November | 0.655365E+11 | 0.00 | 404.76 | 0.627709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111560.80 | 09-NOV-14:30 | 106164.16 | 09-NOV-14:30 | 0.00 | 0.00 | 0.00 |
December | 0.251525E+11 | 0.00 | 335.66 | 0.250516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60837.58 | 01-DEC-15:00 | 60837.58 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188637E+13 | 5787.21 | 0.135821E+13 | ||||||||||||
Minimum of Months | 0.202031E+11 | 0.00 | 300.92 | 0.200362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51086.92 | 51086.92 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.301821E+12 | 0.00 | 628.28 | 0.199907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 299079.88 | 203688.30 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.323343E+12 | 0.768740E+11 | 744.00 | 0.309017E+12 | 0.143257E+11 | 0.00 | 0.34 | 12-JAN-15:05 | 0.31 | 22-JAN-06:10 | 123610.72 | 02-JAN-17:00 | 120184.20 | 12-JAN-15:05 | 6206.96 | 02-JAN-11:00 | 35426.74 | 12-JAN-15:00 | 0.00 |
February | 0.512131E+12 | 0.124521E+12 | 672.00 | 0.494327E+12 | 0.178038E+11 | 0.00 | 0.58 | 24-FEB-16:00 | 0.52 | 01-FEB-00:10 | 215512.38 | 27-FEB-09:50 | 209183.70 | 22-FEB-15:00 | 10788.41 | 09-FEB-21:00 | 66704.96 | 22-FEB-15:00 | 0.00 |
March | 0.802134E+12 | 0.222261E+12 | 744.00 | 0.787603E+12 | 0.145307E+11 | 0.00 | 0.85 | 28-MAR-16:00 | 0.73 | 01-MAR-04:01 | 305547.38 | 05-MAR-05:10 | 300000.44 | 28-MAR-16:00 | 14670.22 | 05-MAR-05:50 | 119523.90 | 28-MAR-15:10 | 0.00 |
April | 0.993731E+12 | 0.328228E+12 | 720.00 | 0.987961E+12 | 0.577025E+10 | 0.00 | 1.00 | 01-APR-09:40 | 0.94 | 11-APR-05:00 | 393720.14 | 26-APR-02:13 | 388303.15 | 29-APR-04:52 | 10910.86 | 11-APR-05:00 | 154884.16 | 15-APR-15:00 | 0.00 |
May | 0.344531E+12 | 0.129609E+12 | 744.00 | 0.329377E+12 | 0.151545E+11 | 0.00 | 0.47 | 01-MAY-00:12 | 0.34 | 28-MAY-05:00 | 166989.66 | 01-MAY-00:12 | 162890.39 | 01-MAY-00:12 | 14641.45 | 22-MAY-23:10 | 66129.96 | 01-MAY-15:00 | 0.00 |
June | 0.570985E+12 | 0.214116E+12 | 720.00 | 0.547215E+12 | 0.237698E+11 | 0.00 | 0.68 | 07-JUN-16:00 | 0.57 | 18-JUN-04:53 | 228157.53 | 28-JUN-14:00 | 216568.41 | 12-JUN-16:00 | 16104.58 | 28-JUN-12:10 | 107725.10 | 07-JUN-16:00 | 0.00 |
July | 0.835482E+12 | 0.295720E+12 | 744.00 | 0.801291E+12 | 0.341919E+11 | 0.00 | 0.90 | 02-JUL-16:51 | 0.79 | 19-JUL-02:55 | 315897.93 | 17-JUL-12:05 | 303561.89 | 03-JUL-16:00 | 16853.62 | 18-JUL-07:30 | 136642.27 | 02-JUL-16:10 | 0.00 |
August | 0.105402E+13 | 0.348668E+12 | 744.00 | 0.102109E+13 | 0.329305E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 1.00 | 16-AUG-00:10 | 402387.10 | 15-AUG-22:55 | 389895.77 | 15-AUG-23:57 | 16810.13 | 25-AUG-16:30 | 147990.62 | 07-AUG-15:00 | 0.00 |
September | 0.348370E+12 | 0.115092E+12 | 720.00 | 0.319099E+12 | 0.292713E+11 | 0.00 | 0.46 | 01-SEP-00:05 | 0.35 | 27-SEP-05:10 | 165837.56 | 01-SEP-00:05 | 158995.50 | 01-SEP-00:05 | 15476.36 | 12-SEP-18:20 | 56774.97 | 17-SEP-20:00 | 0.00 |
October | 0.575305E+12 | 0.172632E+12 | 744.00 | 0.560163E+12 | 0.151423E+11 | 0.00 | 0.63 | 02-OCT-15:00 | 0.54 | 31-OCT-05:00 | 220299.02 | 03-OCT-16:00 | 214346.86 | 02-OCT-15:00 | 13547.11 | 01-OCT-00:05 | 87917.53 | 02-OCT-15:00 | 0.00 |
November | 0.786001E+12 | 0.201199E+12 | 720.00 | 0.765404E+12 | 0.205966E+11 | 0.00 | 0.81 | 08-NOV-15:40 | 0.74 | 26-NOV-06:00 | 309015.32 | 24-NOV-08:25 | 299708.02 | 08-NOV-15:00 | 15338.52 | 23-NOV-08:00 | 103046.87 | 04-NOV-14:00 | 0.00 |
December | 0.106033E+13 | 0.237608E+12 | 744.00 | 0.102199E+13 | 0.383384E+11 | 0.00 | 0.98 | 28-DEC-14:00 | 0.92 | 01-DEC-00:10 | 407706.75 | 22-DEC-06:30 | 385562.71 | 28-DEC-15:00 | 26421.59 | 22-DEC-06:15 | 114051.97 | 28-DEC-14:05 | 0.00 |
Annual Sum or Average | 0.820636E+13 | 0.246653E+13 | 8760.00 | 0.794454E+13 | 0.261826E+12 | ||||||||||||||
Minimum of Months | 0.323343E+12 | 0.768740E+11 | 672.00 | 0.309017E+12 | 0.577025E+10 | 0.00 | 0.34 | 0.31 | 123610.72 | 120184.20 | 6206.96 | 35426.74 | 0.00 | ||||||
Maximum of Months | 0.106033E+13 | 0.348668E+12 | 744.00 | 0.102199E+13 | 0.383384E+11 | 0.00 | 1.00 | 1.00 | 407706.75 | 389895.77 | 26421.59 | 154884.16 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.487075E+10 | 0.117360E+10 | 744.00 | 0.487074E+10 | 10614.02 | 0.00 | 0.29 | 12-JAN-17:00 | 0.20 | 03-JAN-08:00 | 2165.05 | 12-JAN-17:00 | 2165.05 | 12-JAN-17:00 | 1.17 | 02-JAN-08:00 | 609.70 | 12-JAN-16:00 | 0.00 |
February | 0.919292E+10 | 0.224522E+10 | 672.00 | 0.919292E+10 | 0.00 | 0.00 | 0.55 | 20-FEB-17:13 | 0.41 | 11-FEB-08:00 | 4279.07 | 20-FEB-17:30 | 4279.07 | 20-FEB-17:30 | 0.00 | 01-FEB-00:10 | 1270.59 | 22-FEB-15:00 | 0.00 |
March | 0.153559E+11 | 0.427326E+10 | 744.00 | 0.153559E+11 | 0.00 | 0.00 | 0.82 | 28-MAR-16:00 | 0.64 | 01-MAR-07:20 | 6206.26 | 26-MAR-18:05 | 6206.26 | 26-MAR-18:05 | 0.00 | 01-MAR-00:10 | 2379.15 | 28-MAR-16:00 | 0.00 |
April | 0.197008E+11 | 0.665358E+10 | 720.00 | 0.197008E+11 | 0.00 | 0.00 | 1.00 | 01-APR-14:50 | 0.87 | 11-APR-06:00 | 8019.10 | 16-APR-22:23 | 8019.10 | 16-APR-22:23 | 0.00 | 01-APR-00:05 | 3214.53 | 15-APR-15:00 | 0.00 |
May | 0.594781E+10 | 0.231494E+10 | 744.00 | 0.594781E+10 | 0.00 | 0.00 | 0.44 | 01-MAY-00:12 | 0.27 | 13-MAY-07:00 | 3167.01 | 01-MAY-00:12 | 3167.01 | 01-MAY-00:12 | 0.00 | 01-MAY-00:10 | 1273.55 | 29-MAY-17:41 | 0.00 |
June | 0.104499E+11 | 0.405789E+10 | 720.00 | 0.104499E+11 | 0.00 | 0.00 | 0.69 | 11-JUN-16:45 | 0.50 | 24-JUN-13:05 | 4523.96 | 11-JUN-17:25 | 4523.96 | 11-JUN-17:25 | 0.00 | 01-JUN-00:03 | 2219.86 | 11-JUN-16:45 | 0.00 |
July | 0.156673E+11 | 0.572507E+10 | 744.00 | 0.156673E+11 | 0.00 | 0.00 | 0.91 | 04-JUL-18:10 | 0.72 | 19-JUL-03:00 | 6377.95 | 04-JUL-17:53 | 6377.95 | 04-JUL-17:53 | 0.00 | 01-JUL-00:05 | 2886.24 | 02-JUL-16:45 | 0.00 |
August | 0.204875E+11 | 0.709878E+10 | 744.00 | 0.204875E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-11:30 | 0.92 | 16-AUG-07:00 | 7925.15 | 14-AUG-04:24 | 7925.15 | 14-AUG-04:24 | 0.00 | 01-AUG-00:03 | 3069.58 | 07-AUG-15:00 | 0.00 |
September | 0.562880E+10 | 0.193684E+10 | 720.00 | 0.562880E+10 | 0.00 | 0.00 | 0.38 | 17-SEP-18:20 | 0.26 | 08-SEP-21:13 | 2638.74 | 01-SEP-00:10 | 2638.74 | 01-SEP-00:10 | 0.00 | 01-SEP-00:05 | 1055.88 | 17-SEP-18:20 | 0.00 |
October | 0.106444E+11 | 0.322841E+10 | 744.00 | 0.106444E+11 | 0.00 | 0.00 | 0.62 | 01-OCT-16:41 | 0.46 | 28-OCT-07:00 | 4420.65 | 01-OCT-17:17 | 4420.65 | 01-OCT-17:17 | 0.00 | 01-OCT-00:05 | 1736.58 | 01-OCT-16:01 | 0.00 |
November | 0.148595E+11 | 0.381754E+10 | 720.00 | 0.148595E+11 | 0.00 | 0.00 | 0.78 | 12-NOV-15:52 | 0.64 | 25-NOV-08:00 | 6133.46 | 12-NOV-16:27 | 6133.46 | 12-NOV-16:27 | 0.00 | 01-NOV-00:10 | 2007.61 | 08-NOV-15:00 | 0.00 |
December | 0.199367E+11 | 0.449161E+10 | 744.00 | 0.199362E+11 | 508327.38 | 0.00 | 0.94 | 25-DEC-14:51 | 0.81 | 23-DEC-08:00 | 7752.74 | 24-DEC-16:57 | 7752.74 | 24-DEC-16:57 | 19.54 | 22-DEC-03:00 | 2255.36 | 25-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.152742E+12 | 0.470167E+11 | 8760.00 | 0.152742E+12 | 518941.39 | ||||||||||||||
Minimum of Months | 0.487075E+10 | 0.117360E+10 | 672.00 | 0.487074E+10 | 0.00 | 0.00 | 0.29 | 0.20 | 2165.05 | 2165.05 | 0.00 | 609.70 | 0.00 | ||||||
Maximum of Months | 0.204875E+11 | 0.709878E+10 | 744.00 | 0.204875E+11 | 508327.38 | 0.00 | 1.00 | 0.92 | 8019.10 | 8019.10 | 19.54 | 3214.53 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.321558E+11 | 0.801246E+10 | 744.00 | 0.321557E+11 | 57431.46 | 0.00 | 0.27 | 12-JAN-17:00 | 0.01 | 01-JAN-07:45 | 19622.99 | 12-JAN-17:30 | 19622.99 | 12-JAN-17:30 | 3.95 | 02-JAN-10:30 | 5522.96 | 12-JAN-17:00 | 0.00 |
February | 0.802036E+11 | 0.198135E+11 | 672.00 | 0.802036E+11 | 0.00 | 0.00 | 0.52 | 22-FEB-17:00 | 0.35 | 11-FEB-08:00 | 38252.27 | 22-FEB-17:00 | 38252.27 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 | 11932.03 | 22-FEB-15:00 | 0.00 |
March | 0.144348E+12 | 0.402977E+11 | 744.00 | 0.144348E+12 | 0.00 | 0.00 | 0.82 | 28-MAR-16:00 | 0.61 | 01-MAR-07:50 | 58084.77 | 12-MAR-17:42 | 58084.77 | 12-MAR-17:42 | 0.00 | 01-MAR-00:10 | 22697.00 | 28-MAR-16:00 | 0.00 |
April | 0.187104E+12 | 0.632900E+11 | 720.00 | 0.187104E+12 | 0.00 | 0.00 | 1.00 | 01-APR-15:00 | 0.87 | 11-APR-06:00 | 75399.19 | 16-APR-20:24 | 75399.19 | 16-APR-20:24 | 0.00 | 01-APR-00:05 | 30712.47 | 15-APR-15:00 | 0.00 |
May | 0.555412E+11 | 0.216747E+11 | 744.00 | 0.555412E+11 | 0.00 | 0.00 | 0.41 | 29-MAY-17:51 | 0.26 | 13-MAY-07:00 | 25578.37 | 29-MAY-17:59 | 25578.37 | 29-MAY-17:59 | 0.00 | 01-MAY-00:10 | 11914.33 | 28-MAY-17:01 | 0.00 |
June | 0.990100E+11 | 0.384933E+11 | 720.00 | 0.990100E+11 | 0.00 | 0.00 | 0.67 | 11-JUN-16:45 | 0.49 | 24-JUN-14:00 | 42408.75 | 11-JUN-18:00 | 42408.75 | 11-JUN-18:00 | 0.00 | 01-JUN-00:03 | 20797.09 | 11-JUN-16:45 | 0.00 |
July | 0.148424E+12 | 0.542906E+11 | 744.00 | 0.148424E+12 | 0.00 | 0.00 | 0.89 | 04-JUL-18:10 | 0.72 | 19-JUL-02:50 | 59574.98 | 02-JUL-18:05 | 59574.98 | 02-JUL-18:05 | 0.00 | 01-JUL-00:05 | 27016.68 | 02-JUL-16:45 | 0.00 |
August | 0.193895E+12 | 0.673473E+11 | 744.00 | 0.193895E+12 | 0.00 | 0.00 | 1.00 | 01-AUG-11:30 | 0.92 | 16-AUG-07:00 | 74118.84 | 20-AUG-15:05 | 74118.84 | 20-AUG-15:05 | 0.00 | 01-AUG-00:03 | 29326.58 | 07-AUG-15:00 | 0.00 |
September | 0.519852E+11 | 0.179462E+11 | 720.00 | 0.519852E+11 | 0.00 | 0.00 | 0.37 | 17-SEP-18:20 | 0.24 | 09-SEP-17:20 | 23790.50 | 17-SEP-18:17 | 23790.50 | 17-SEP-18:17 | 0.00 | 01-SEP-00:05 | 9860.12 | 17-SEP-18:20 | 0.00 |
October | 0.997533E+11 | 0.303391E+11 | 744.00 | 0.997533E+11 | 0.00 | 0.00 | 0.61 | 01-OCT-16:51 | 0.44 | 31-OCT-07:00 | 41834.13 | 01-OCT-16:56 | 41834.13 | 01-OCT-16:56 | 0.00 | 01-OCT-00:05 | 16416.40 | 01-OCT-16:01 | 0.00 |
November | 0.137033E+12 | 0.354160E+11 | 720.00 | 0.137033E+12 | 0.00 | 0.00 | 0.76 | 08-NOV-16:10 | 0.59 | 27-NOV-08:00 | 56209.03 | 12-NOV-16:33 | 56209.03 | 12-NOV-16:33 | 0.00 | 01-NOV-00:10 | 19076.42 | 08-NOV-15:00 | 0.00 |
December | 0.179283E+12 | 0.407785E+11 | 744.00 | 0.179278E+12 | 4966321.81 | 0.00 | 0.93 | 28-DEC-16:30 | 0.74 | 31-DEC-08:70 | 72691.28 | 01-DEC-17:00 | 72691.28 | 01-DEC-17:00 | 187.48 | 22-DEC-03:00 | 21256.89 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.140874E+13 | 0.437699E+12 | 8760.00 | 0.140873E+13 | 5023753.27 | ||||||||||||||
Minimum of Months | 0.321558E+11 | 0.801246E+10 | 672.00 | 0.321557E+11 | 0.00 | 0.00 | 0.27 | 0.01 | 19622.99 | 19622.99 | 0.00 | 5522.96 | 0.00 | ||||||
Maximum of Months | 0.193895E+12 | 0.673473E+11 | 744.00 | 0.193895E+12 | 4966321.81 | 0.00 | 1.00 | 0.92 | 75399.19 | 75399.19 | 187.48 | 30712.47 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.206583E+10 | 0.536742E+09 | 666.53 | 0.206578E+10 | 55257.44 | 0.00 | 0.27 | 12-JAN-17:00 | 0.00 | 01-JAN-00:01 | 1981.95 | 12-JAN-17:00 | 1981.95 | 12-JAN-17:00 | 3.03 | 02-JAN-17:20 | 559.67 | 12-JAN-17:00 | 0.00 |
February | 0.737767E+10 | 0.185102E+10 | 672.00 | 0.737767E+10 | 0.00 | 0.00 | 0.52 | 22-FEB-17:00 | 0.25 | 12-FEB-08:20 | 3884.19 | 22-FEB-17:00 | 3884.19 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 | 1218.44 | 22-FEB-15:00 | 0.00 |
March | 0.142647E+11 | 0.401222E+10 | 744.00 | 0.142647E+11 | 0.00 | 0.00 | 0.82 | 28-MAR-16:00 | 0.55 | 01-MAR-08:00 | 6046.01 | 12-MAR-17:28 | 6046.01 | 12-MAR-17:28 | 0.00 | 01-MAR-00:10 | 2319.19 | 28-MAR-16:00 | 0.00 |
April | 0.188069E+11 | 0.638857E+10 | 720.00 | 0.188069E+11 | 0.00 | 0.00 | 1.00 | 01-APR-14:50 | 0.82 | 23-APR-05:00 | 7754.16 | 16-APR-21:23 | 7754.16 | 16-APR-21:23 | 0.00 | 01-APR-00:05 | 3126.70 | 15-APR-15:00 | 0.00 |
May | 0.576488E+10 | 0.225565E+10 | 744.00 | 0.576488E+10 | 0.00 | 0.00 | 0.47 | 29-MAY-18:01 | 0.24 | 13-MAY-07:00 | 3021.77 | 29-MAY-18:08 | 3021.77 | 29-MAY-18:08 | 0.00 | 01-MAY-00:10 | 1384.09 | 29-MAY-17:31 | 0.00 |
June | 0.100907E+11 | 0.393461E+10 | 720.00 | 0.100907E+11 | 0.00 | 0.00 | 0.73 | 11-JUN-16:45 | 0.47 | 24-JUN-14:00 | 4720.46 | 11-JUN-17:30 | 4720.46 | 11-JUN-17:30 | 0.00 | 01-JUN-00:03 | 2300.09 | 11-JUN-16:45 | 0.00 |
July | 0.150440E+11 | 0.551863E+10 | 744.00 | 0.150440E+11 | 0.00 | 0.00 | 0.94 | 02-JUL-17:15 | 0.70 | 19-JUL-03:00 | 6402.24 | 02-JUL-17:55 | 6402.24 | 02-JUL-17:55 | 0.00 | 01-JUL-00:05 | 2889.90 | 02-JUL-16:45 | 0.00 |
August | 0.195244E+11 | 0.680512E+10 | 744.00 | 0.195244E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-12:10 | 0.91 | 16-AUG-07:00 | 7605.45 | 20-AUG-15:02 | 7605.45 | 20-AUG-15:02 | 0.00 | 01-AUG-00:03 | 2985.41 | 07-AUG-15:00 | 0.00 |
September | 0.528419E+10 | 0.183039E+10 | 720.00 | 0.528419E+10 | 0.00 | 0.00 | 0.40 | 17-SEP-18:00 | 0.23 | 09-SEP-17:20 | 2650.33 | 17-SEP-17:53 | 2650.33 | 17-SEP-17:53 | 0.00 | 01-SEP-00:05 | 1087.94 | 17-SEP-18:10 | 0.00 |
October | 0.989153E+10 | 0.302921E+10 | 744.00 | 0.989153E+10 | 0.00 | 0.00 | 0.64 | 01-OCT-16:51 | 0.40 | 31-OCT-07:00 | 4465.57 | 01-OCT-17:07 | 4465.57 | 01-OCT-17:07 | 0.00 | 01-OCT-00:05 | 1741.80 | 01-OCT-16:11 | 0.00 |
November | 0.131934E+11 | 0.344883E+10 | 720.00 | 0.131934E+11 | 0.00 | 0.00 | 0.76 | 08-NOV-16:00 | 0.50 | 26-NOV-07:55 | 5662.02 | 09-NOV-16:40 | 5662.02 | 09-NOV-16:40 | 0.00 | 01-NOV-00:10 | 1929.30 | 08-NOV-15:00 | 0.00 |
December | 0.167897E+11 | 0.387464E+10 | 744.00 | 0.167892E+11 | 507296.58 | 0.00 | 0.92 | 28-DEC-16:20 | 0.61 | 31-DEC-08:40 | 7275.57 | 28-DEC-17:00 | 7275.57 | 28-DEC-17:00 | 18.47 | 22-DEC-03:00 | 2139.01 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.138098E+12 | 0.434856E+11 | 8682.53 | 0.138097E+12 | 562554.02 | ||||||||||||||
Minimum of Months | 0.206583E+10 | 0.536742E+09 | 666.53 | 0.206578E+10 | 0.00 | 0.00 | 0.27 | 0.00 | 1981.95 | 1981.95 | 0.00 | 559.67 | 0.00 | ||||||
Maximum of Months | 0.195244E+11 | 0.680512E+10 | 744.00 | 0.195244E+11 | 507296.58 | 0.00 | 1.00 | 0.91 | 7754.16 | 7754.16 | 18.47 | 3126.70 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 106.04 | 0.00 | 106.04 | 44.91 | 470.05 | 0.00 | 0.00 | 744.00 |
February | 125.74 | 0.00 | 125.74 | 103.14 | 360.98 | 0.00 | 0.00 | 672.00 |
March | 151.52 | 0.00 | 151.52 | 216.70 | 209.03 | 0.00 | 0.00 | 744.00 |
April | 164.40 | 0.55 | 163.85 | 392.75 | 70.71 | 0.00 | 0.00 | 720.00 |
May | 182.13 | 5.08 | 177.04 | 552.00 | 10.96 | 0.00 | 0.00 | 744.00 |
June | 188.53 | 6.95 | 181.58 | 598.25 | 8.17 | 0.00 | 0.00 | 720.00 |
July | 185.95 | 2.93 | 183.02 | 531.92 | 1.77 | 0.00 | 0.00 | 744.00 |
August | 170.72 | 0.53 | 170.19 | 445.25 | 7.03 | 0.00 | 0.00 | 744.00 |
September | 152.12 | 0.01 | 152.11 | 350.44 | 26.82 | 0.00 | 0.00 | 720.00 |
October | 131.78 | 0.00 | 131.78 | 248.10 | 158.92 | 0.00 | 0.00 | 744.00 |
November | 111.62 | 0.00 | 111.62 | 124.21 | 321.78 | 0.00 | 0.00 | 720.00 |
December | 103.44 | 0.00 | 103.44 | 49.07 | 463.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 147.94 | 1.34 | 146.60 | 305.71 | 175.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 103.44 | 0.00 | 103.44 | 44.91 | 1.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.53 | 6.95 | 183.02 | 598.25 | 470.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 106.04 | 0.00 | 106.04 | 44.91 | 470.05 | 0.00 | 0.00 | 744.00 |
February | 125.74 | 0.00 | 125.74 | 103.14 | 360.98 | 0.00 | 0.00 | 672.00 |
March | 151.52 | 0.00 | 151.52 | 216.70 | 209.03 | 0.00 | 0.00 | 744.00 |
April | 164.40 | 0.55 | 163.85 | 392.75 | 70.71 | 0.00 | 0.00 | 720.00 |
May | 182.13 | 5.08 | 177.04 | 552.00 | 10.96 | 0.00 | 0.00 | 744.00 |
June | 188.52 | 6.95 | 181.58 | 598.25 | 8.17 | 0.00 | 0.00 | 720.00 |
July | 185.95 | 2.93 | 183.02 | 531.92 | 1.77 | 0.00 | 0.00 | 744.00 |
August | 170.72 | 0.53 | 170.19 | 445.25 | 7.03 | 0.00 | 0.00 | 744.00 |
September | 152.12 | 0.01 | 152.11 | 350.44 | 26.82 | 0.00 | 0.00 | 720.00 |
October | 131.78 | 0.00 | 131.78 | 248.10 | 158.92 | 0.00 | 0.00 | 744.00 |
November | 111.62 | 0.00 | 111.62 | 124.21 | 321.78 | 0.00 | 0.00 | 720.00 |
December | 103.44 | 0.00 | 103.44 | 49.07 | 463.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 147.94 | 1.34 | 146.60 | 305.71 | 175.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 103.44 | 0.00 | 103.44 | 44.91 | 1.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.52 | 6.95 | 183.02 | 598.25 | 470.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 106.04 | 0.00 | 106.04 | 44.91 | 470.05 | 0.00 | 0.00 | 744.00 |
February | 125.74 | 0.00 | 125.74 | 103.14 | 360.98 | 0.00 | 0.00 | 672.00 |
March | 151.52 | 0.00 | 151.52 | 216.70 | 209.03 | 0.00 | 0.00 | 744.00 |
April | 164.40 | 0.55 | 163.85 | 392.75 | 70.71 | 0.00 | 0.00 | 720.00 |
May | 182.13 | 5.08 | 177.04 | 552.00 | 10.96 | 0.00 | 0.00 | 744.00 |
June | 188.53 | 6.95 | 181.58 | 598.25 | 8.17 | 0.00 | 0.00 | 720.00 |
July | 185.95 | 2.93 | 183.02 | 531.92 | 1.77 | 0.00 | 0.00 | 744.00 |
August | 170.72 | 0.53 | 170.19 | 445.25 | 7.03 | 0.00 | 0.00 | 744.00 |
September | 152.12 | 0.01 | 152.11 | 350.44 | 26.82 | 0.00 | 0.00 | 720.00 |
October | 131.78 | 0.00 | 131.78 | 248.10 | 158.92 | 0.00 | 0.00 | 744.00 |
November | 111.62 | 0.00 | 111.62 | 124.21 | 321.78 | 0.00 | 0.00 | 720.00 |
December | 103.44 | 0.00 | 103.44 | 49.07 | 463.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 147.94 | 1.34 | 146.60 | 305.71 | 175.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 103.44 | 0.00 | 103.44 | 44.91 | 1.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.53 | 6.95 | 183.02 | 598.25 | 470.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 106.04 | 0.00 | 106.04 | 44.91 | 470.05 | 0.00 | 0.00 | 744.00 |
February | 125.74 | 0.00 | 125.74 | 103.14 | 360.98 | 0.00 | 0.00 | 672.00 |
March | 151.52 | 0.00 | 151.52 | 216.70 | 209.03 | 0.00 | 0.00 | 744.00 |
April | 164.40 | 0.55 | 163.85 | 392.75 | 70.71 | 0.00 | 0.00 | 720.00 |
May | 182.13 | 5.08 | 177.04 | 552.00 | 10.96 | 0.00 | 0.00 | 744.00 |
June | 188.52 | 6.95 | 181.58 | 598.25 | 8.17 | 0.00 | 0.00 | 720.00 |
July | 185.95 | 2.93 | 183.02 | 531.92 | 1.77 | 0.00 | 0.00 | 744.00 |
August | 170.72 | 0.53 | 170.19 | 445.25 | 7.03 | 0.00 | 0.00 | 744.00 |
September | 152.12 | 0.01 | 152.11 | 350.44 | 26.82 | 0.00 | 0.00 | 720.00 |
October | 131.78 | 0.00 | 131.78 | 248.10 | 158.92 | 0.00 | 0.00 | 744.00 |
November | 111.62 | 0.00 | 111.62 | 124.21 | 321.78 | 0.00 | 0.00 | 720.00 |
December | 103.44 | 0.00 | 103.44 | 49.07 | 463.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 147.94 | 1.34 | 146.60 | 305.71 | 175.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 103.44 | 0.00 | 103.44 | 44.91 | 1.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.52 | 6.95 | 183.02 | 598.25 | 470.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 106.03 | 0.00 | 106.03 | 44.91 | 470.03 | 0.00 | 0.00 | 744.00 |
February | 125.74 | 0.00 | 125.74 | 103.14 | 360.97 | 0.00 | 0.00 | 672.00 |
March | 151.51 | 0.00 | 151.51 | 216.69 | 209.02 | 0.00 | 0.00 | 744.00 |
April | 164.40 | 0.55 | 163.85 | 392.74 | 70.70 | 0.00 | 0.00 | 720.00 |
May | 182.12 | 5.08 | 177.04 | 551.97 | 10.96 | 0.00 | 0.00 | 744.00 |
June | 188.52 | 6.95 | 181.57 | 598.22 | 8.16 | 0.00 | 0.00 | 720.00 |
July | 185.94 | 2.93 | 183.01 | 531.90 | 1.77 | 0.00 | 0.00 | 744.00 |
August | 170.71 | 0.53 | 170.18 | 445.24 | 7.03 | 0.00 | 0.00 | 744.00 |
September | 152.11 | 0.01 | 152.10 | 350.43 | 26.81 | 0.00 | 0.00 | 720.00 |
October | 131.78 | 0.00 | 131.78 | 248.09 | 158.91 | 0.00 | 0.00 | 744.00 |
November | 111.62 | 0.00 | 111.62 | 124.21 | 321.77 | 0.00 | 0.00 | 720.00 |
December | 103.44 | 0.00 | 103.44 | 49.07 | 463.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 147.94 | 1.34 | 146.60 | 305.70 | 175.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 103.44 | 0.00 | 103.44 | 44.91 | 1.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 188.52 | 6.95 | 183.01 | 598.22 | 470.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 252.38 | 101.29 | 151.08 | 217.25 | 469.86 | 0.00 | 0.00 | 744.00 |
February | 306.61 | 126.58 | 180.03 | 358.38 | 365.92 | 0.00 | 0.00 | 672.00 |
March | 374.06 | 154.40 | 219.65 | 575.66 | 215.69 | 0.00 | 0.00 | 744.00 |
April | 445.03 | 207.50 | 237.53 | 885.15 | 75.36 | 0.00 | 0.00 | 720.00 |
May | 438.00 | 194.18 | 243.82 | 1017.57 | 12.93 | 0.00 | 0.00 | 744.00 |
June | 356.47 | 118.27 | 238.21 | 921.20 | 8.73 | 0.00 | 0.00 | 720.00 |
July | 299.61 | 63.27 | 236.35 | 759.88 | 1.42 | 0.00 | 0.00 | 744.00 |
August | 269.97 | 46.98 | 222.99 | 641.49 | 5.79 | 0.00 | 0.00 | 744.00 |
September | 288.44 | 80.44 | 208.00 | 591.75 | 29.60 | 0.00 | 0.00 | 720.00 |
October | 315.50 | 127.44 | 188.07 | 553.32 | 170.14 | 0.00 | 0.00 | 744.00 |
November | 279.73 | 120.07 | 159.67 | 371.64 | 328.34 | 0.00 | 0.00 | 720.00 |
December | 243.92 | 96.64 | 147.28 | 227.95 | 461.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 322.39 | 119.57 | 202.82 | 594.28 | 177.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 243.92 | 46.98 | 147.28 | 217.25 | 1.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 445.03 | 207.50 | 243.82 | 1017.57 | 469.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 252.38 | 101.29 | 151.08 | 217.25 | 469.86 | 0.00 | 0.00 | 744.00 |
February | 306.61 | 126.58 | 180.03 | 358.38 | 365.92 | 0.00 | 0.00 | 672.00 |
March | 374.06 | 154.40 | 219.65 | 575.66 | 215.69 | 0.00 | 0.00 | 744.00 |
April | 445.03 | 207.50 | 237.53 | 885.15 | 75.36 | 0.00 | 0.00 | 720.00 |
May | 438.00 | 194.18 | 243.82 | 1017.57 | 12.93 | 0.00 | 0.00 | 744.00 |
June | 356.47 | 118.27 | 238.21 | 921.20 | 8.73 | 0.00 | 0.00 | 720.00 |
July | 299.61 | 63.27 | 236.35 | 759.88 | 1.42 | 0.00 | 0.00 | 744.00 |
August | 269.97 | 46.98 | 222.99 | 641.49 | 5.79 | 0.00 | 0.00 | 744.00 |
September | 288.44 | 80.44 | 208.00 | 591.75 | 29.60 | 0.00 | 0.00 | 720.00 |
October | 315.50 | 127.44 | 188.07 | 553.32 | 170.14 | 0.00 | 0.00 | 744.00 |
November | 279.73 | 120.07 | 159.67 | 371.64 | 328.34 | 0.00 | 0.00 | 720.00 |
December | 243.92 | 96.64 | 147.28 | 227.95 | 461.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 322.39 | 119.57 | 202.82 | 594.28 | 177.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 243.92 | 46.98 | 147.28 | 217.25 | 1.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 445.03 | 207.50 | 243.82 | 1017.57 | 469.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 252.37 | 101.29 | 151.08 | 217.25 | 469.85 | 0.00 | 0.00 | 744.00 |
February | 306.61 | 126.58 | 180.03 | 358.37 | 365.91 | 0.00 | 0.00 | 672.00 |
March | 374.05 | 154.40 | 219.65 | 575.65 | 215.68 | 0.00 | 0.00 | 744.00 |
April | 445.02 | 207.50 | 237.52 | 885.14 | 75.36 | 0.00 | 0.00 | 720.00 |
May | 438.00 | 194.18 | 243.82 | 1017.55 | 12.93 | 0.00 | 0.00 | 744.00 |
June | 356.47 | 118.27 | 238.20 | 921.18 | 8.73 | 0.00 | 0.00 | 720.00 |
July | 299.61 | 63.27 | 236.34 | 759.87 | 1.42 | 0.00 | 0.00 | 744.00 |
August | 269.96 | 46.98 | 222.98 | 641.47 | 5.79 | 0.00 | 0.00 | 744.00 |
September | 288.43 | 80.44 | 207.99 | 591.74 | 29.60 | 0.00 | 0.00 | 720.00 |
October | 315.50 | 127.43 | 188.06 | 553.31 | 170.14 | 0.00 | 0.00 | 744.00 |
November | 279.73 | 120.06 | 159.66 | 371.64 | 328.34 | 0.00 | 0.00 | 720.00 |
December | 243.91 | 96.63 | 147.28 | 227.95 | 461.49 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 322.38 | 119.57 | 202.82 | 594.27 | 177.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 243.91 | 46.98 | 147.28 | 217.25 | 1.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 445.02 | 207.50 | 243.82 | 1017.55 | 469.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.38 | 293.16 | 189.22 | 642.37 | 429.32 | 0.00 | 0.00 | 744.00 |
February | 458.60 | 254.74 | 203.86 | 646.81 | 350.87 | 0.00 | 0.00 | 672.00 |
March | 391.98 | 173.08 | 218.90 | 602.79 | 216.53 | 0.00 | 0.00 | 744.00 |
April | 275.27 | 77.60 | 197.67 | 531.61 | 77.10 | 0.00 | 0.00 | 720.00 |
May | 197.92 | 14.54 | 183.38 | 558.70 | 11.48 | 0.00 | 0.00 | 744.00 |
June | 181.10 | 3.03 | 178.07 | 583.20 | 8.29 | 0.00 | 0.00 | 720.00 |
July | 188.94 | 2.57 | 186.37 | 535.46 | 1.68 | 0.00 | 0.00 | 744.00 |
August | 200.42 | 10.67 | 189.75 | 486.77 | 7.44 | 0.00 | 0.00 | 744.00 |
September | 268.68 | 69.70 | 198.98 | 529.68 | 31.14 | 0.00 | 0.00 | 720.00 |
October | 462.30 | 258.14 | 204.16 | 808.10 | 172.37 | 0.00 | 0.00 | 744.00 |
November | 577.62 | 381.85 | 195.77 | 919.79 | 323.72 | 0.00 | 0.00 | 720.00 |
December | 515.51 | 323.09 | 192.42 | 718.67 | 430.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 349.44 | 154.60 | 194.83 | 630.08 | 170.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 181.10 | 2.57 | 178.07 | 486.77 | 1.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 577.62 | 381.85 | 218.90 | 919.79 | 430.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.38 | 293.16 | 189.22 | 642.37 | 429.32 | 0.00 | 0.00 | 744.00 |
February | 458.60 | 254.74 | 203.86 | 646.81 | 350.87 | 0.00 | 0.00 | 672.00 |
March | 391.98 | 173.08 | 218.90 | 602.79 | 216.53 | 0.00 | 0.00 | 744.00 |
April | 275.27 | 77.60 | 197.67 | 531.61 | 77.10 | 0.00 | 0.00 | 720.00 |
May | 197.92 | 14.54 | 183.38 | 558.70 | 11.48 | 0.00 | 0.00 | 744.00 |
June | 181.10 | 3.03 | 178.07 | 583.20 | 8.29 | 0.00 | 0.00 | 720.00 |
July | 188.94 | 2.57 | 186.37 | 535.46 | 1.68 | 0.00 | 0.00 | 744.00 |
August | 200.42 | 10.67 | 189.75 | 486.77 | 7.44 | 0.00 | 0.00 | 744.00 |
September | 268.68 | 69.70 | 198.98 | 529.68 | 31.14 | 0.00 | 0.00 | 720.00 |
October | 462.30 | 258.14 | 204.16 | 808.10 | 172.37 | 0.00 | 0.00 | 744.00 |
November | 577.62 | 381.85 | 195.77 | 919.79 | 323.72 | 0.00 | 0.00 | 720.00 |
December | 515.51 | 323.08 | 192.42 | 718.67 | 430.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 349.44 | 154.60 | 194.83 | 630.07 | 170.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 181.10 | 2.57 | 178.07 | 486.77 | 1.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 577.62 | 381.85 | 218.90 | 919.79 | 430.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.38 | 293.16 | 189.22 | 642.37 | 429.32 | 0.00 | 0.00 | 744.00 |
February | 458.60 | 254.74 | 203.86 | 646.81 | 350.87 | 0.00 | 0.00 | 672.00 |
March | 391.98 | 173.08 | 218.90 | 602.79 | 216.53 | 0.00 | 0.00 | 744.00 |
April | 275.27 | 77.60 | 197.67 | 531.61 | 77.10 | 0.00 | 0.00 | 720.00 |
May | 197.92 | 14.54 | 183.38 | 558.70 | 11.48 | 0.00 | 0.00 | 744.00 |
June | 181.10 | 3.03 | 178.07 | 583.20 | 8.29 | 0.00 | 0.00 | 720.00 |
July | 188.94 | 2.57 | 186.37 | 535.46 | 1.68 | 0.00 | 0.00 | 744.00 |
August | 200.42 | 10.67 | 189.75 | 486.77 | 7.44 | 0.00 | 0.00 | 744.00 |
September | 268.68 | 69.70 | 198.98 | 529.68 | 31.14 | 0.00 | 0.00 | 720.00 |
October | 462.30 | 258.14 | 204.16 | 808.10 | 172.37 | 0.00 | 0.00 | 744.00 |
November | 577.62 | 381.85 | 195.77 | 919.79 | 323.72 | 0.00 | 0.00 | 720.00 |
December | 515.51 | 323.09 | 192.42 | 718.67 | 430.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 349.44 | 154.60 | 194.83 | 630.08 | 170.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 181.10 | 2.57 | 178.07 | 486.77 | 1.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 577.62 | 381.85 | 218.90 | 919.79 | 430.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.38 | 293.16 | 189.22 | 642.37 | 429.32 | 0.00 | 0.00 | 744.00 |
February | 458.60 | 254.74 | 203.86 | 646.81 | 350.87 | 0.00 | 0.00 | 672.00 |
March | 391.98 | 173.08 | 218.90 | 602.79 | 216.53 | 0.00 | 0.00 | 744.00 |
April | 275.27 | 77.60 | 197.67 | 531.61 | 77.10 | 0.00 | 0.00 | 720.00 |
May | 197.92 | 14.54 | 183.38 | 558.70 | 11.48 | 0.00 | 0.00 | 744.00 |
June | 181.10 | 3.03 | 178.07 | 583.20 | 8.29 | 0.00 | 0.00 | 720.00 |
July | 188.94 | 2.57 | 186.37 | 535.46 | 1.68 | 0.00 | 0.00 | 744.00 |
August | 200.42 | 10.67 | 189.75 | 486.77 | 7.44 | 0.00 | 0.00 | 744.00 |
September | 268.68 | 69.70 | 198.98 | 529.68 | 31.14 | 0.00 | 0.00 | 720.00 |
October | 462.30 | 258.14 | 204.16 | 808.10 | 172.37 | 0.00 | 0.00 | 744.00 |
November | 577.62 | 381.85 | 195.77 | 919.79 | 323.72 | 0.00 | 0.00 | 720.00 |
December | 515.51 | 323.08 | 192.42 | 718.67 | 430.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 349.44 | 154.60 | 194.83 | 630.07 | 170.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 181.10 | 2.57 | 178.07 | 486.77 | 1.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 577.62 | 381.85 | 218.90 | 919.79 | 430.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 482.36 | 293.14 | 189.22 | 642.34 | 429.30 | 0.00 | 0.00 | 744.00 |
February | 458.58 | 254.73 | 203.85 | 646.79 | 350.86 | 0.00 | 0.00 | 672.00 |
March | 391.97 | 173.08 | 218.89 | 602.77 | 216.52 | 0.00 | 0.00 | 744.00 |
April | 275.26 | 77.59 | 197.66 | 531.59 | 77.10 | 0.00 | 0.00 | 720.00 |
May | 197.92 | 14.54 | 183.38 | 558.67 | 11.48 | 0.00 | 0.00 | 744.00 |
June | 181.10 | 3.03 | 178.06 | 583.18 | 8.29 | 0.00 | 0.00 | 720.00 |
July | 188.93 | 2.57 | 186.36 | 535.44 | 1.68 | 0.00 | 0.00 | 744.00 |
August | 200.41 | 10.67 | 189.74 | 486.75 | 7.44 | 0.00 | 0.00 | 744.00 |
September | 268.67 | 69.70 | 198.97 | 529.66 | 31.14 | 0.00 | 0.00 | 720.00 |
October | 462.28 | 258.13 | 204.15 | 808.07 | 172.37 | 0.00 | 0.00 | 744.00 |
November | 577.60 | 381.83 | 195.76 | 919.76 | 323.71 | 0.00 | 0.00 | 720.00 |
December | 515.49 | 323.07 | 192.42 | 718.64 | 430.33 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 349.42 | 154.60 | 194.82 | 630.05 | 170.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 181.10 | 2.57 | 178.06 | 486.75 | 1.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 577.60 | 381.83 | 218.89 | 919.76 | 430.33 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 246.91 | 96.08 | 150.83 | 241.34 | 552.91 | 0.00 | 0.00 | 744.00 |
February | 282.35 | 104.05 | 178.30 | 335.48 | 448.36 | 0.00 | 0.00 | 672.00 |
March | 366.17 | 146.38 | 219.79 | 559.60 | 282.82 | 0.00 | 0.00 | 744.00 |
April | 445.07 | 208.73 | 236.34 | 857.18 | 121.86 | 0.00 | 0.00 | 720.00 |
May | 421.41 | 178.74 | 242.66 | 969.49 | 24.16 | 0.00 | 0.00 | 744.00 |
June | 395.82 | 153.74 | 242.08 | 954.74 | 18.04 | 0.00 | 0.00 | 720.00 |
July | 293.72 | 57.12 | 236.60 | 697.56 | 8.78 | 0.00 | 0.00 | 744.00 |
August | 269.76 | 47.94 | 221.81 | 588.58 | 26.90 | 0.00 | 0.00 | 744.00 |
September | 296.54 | 87.06 | 209.48 | 590.53 | 51.40 | 0.00 | 0.00 | 720.00 |
October | 308.63 | 122.89 | 185.74 | 537.22 | 216.60 | 0.00 | 0.00 | 744.00 |
November | 279.21 | 118.99 | 160.22 | 381.18 | 411.30 | 0.00 | 0.00 | 720.00 |
December | 238.92 | 91.10 | 147.82 | 226.94 | 576.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 320.32 | 117.58 | 202.74 | 579.03 | 227.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 238.92 | 47.94 | 147.82 | 226.94 | 8.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 445.07 | 208.73 | 242.66 | 969.49 | 576.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 246.91 | 96.08 | 150.83 | 241.34 | 552.91 | 0.00 | 0.00 | 744.00 |
February | 282.35 | 104.05 | 178.30 | 335.48 | 448.36 | 0.00 | 0.00 | 672.00 |
March | 366.17 | 146.38 | 219.79 | 559.60 | 282.82 | 0.00 | 0.00 | 744.00 |
April | 445.07 | 208.73 | 236.34 | 857.18 | 121.86 | 0.00 | 0.00 | 720.00 |
May | 421.41 | 178.74 | 242.66 | 969.49 | 24.16 | 0.00 | 0.00 | 744.00 |
June | 395.82 | 153.74 | 242.08 | 954.74 | 18.04 | 0.00 | 0.00 | 720.00 |
July | 293.72 | 57.12 | 236.60 | 697.56 | 8.78 | 0.00 | 0.00 | 744.00 |
August | 269.76 | 47.94 | 221.81 | 588.58 | 26.90 | 0.00 | 0.00 | 744.00 |
September | 296.54 | 87.06 | 209.48 | 590.53 | 51.40 | 0.00 | 0.00 | 720.00 |
October | 308.63 | 122.89 | 185.74 | 537.22 | 216.60 | 0.00 | 0.00 | 744.00 |
November | 279.21 | 118.99 | 160.22 | 381.18 | 411.30 | 0.00 | 0.00 | 720.00 |
December | 238.92 | 91.10 | 147.82 | 226.94 | 576.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 320.32 | 117.58 | 202.74 | 579.03 | 227.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 238.92 | 47.94 | 147.82 | 226.94 | 8.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 445.07 | 208.73 | 242.66 | 969.49 | 576.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 246.91 | 96.08 | 150.83 | 241.33 | 552.90 | 0.00 | 0.00 | 744.00 |
February | 282.35 | 104.05 | 178.30 | 335.48 | 448.36 | 0.00 | 0.00 | 672.00 |
March | 366.16 | 146.38 | 219.78 | 559.59 | 282.81 | 0.00 | 0.00 | 744.00 |
April | 445.06 | 208.72 | 236.34 | 857.16 | 121.86 | 0.00 | 0.00 | 720.00 |
May | 421.40 | 178.74 | 242.66 | 969.48 | 24.16 | 0.00 | 0.00 | 744.00 |
June | 395.81 | 153.73 | 242.07 | 954.73 | 18.03 | 0.00 | 0.00 | 720.00 |
July | 293.71 | 57.12 | 236.59 | 697.55 | 8.78 | 0.00 | 0.00 | 744.00 |
August | 269.75 | 47.94 | 221.81 | 588.57 | 26.90 | 0.00 | 0.00 | 744.00 |
September | 296.54 | 87.06 | 209.48 | 590.52 | 51.40 | 0.00 | 0.00 | 720.00 |
October | 308.63 | 122.89 | 185.74 | 537.21 | 216.60 | 0.00 | 0.00 | 744.00 |
November | 279.20 | 118.99 | 160.22 | 381.18 | 411.29 | 0.00 | 0.00 | 720.00 |
December | 238.92 | 91.10 | 147.82 | 226.93 | 576.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 320.31 | 117.58 | 202.73 | 579.02 | 227.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 238.92 | 47.94 | 147.82 | 226.93 | 8.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 445.06 | 208.72 | 242.66 | 969.48 | 576.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 530.18 | 0.00 | 530.18 | 321.97 | 1995.57 | 0.00 | 0.00 | 744.00 |
February | 628.70 | 0.00 | 628.70 | 599.14 | 1580.88 | 0.00 | 0.00 | 672.00 |
March | 757.59 | 0.00 | 757.59 | 1127.52 | 969.26 | 0.00 | 0.00 | 744.00 |
April | 822.01 | 2.75 | 819.26 | 2021.54 | 332.35 | 0.00 | 0.00 | 720.00 |
May | 910.62 | 25.41 | 885.21 | 2790.64 | 55.48 | 0.00 | 0.00 | 744.00 |
June | 942.61 | 34.75 | 907.87 | 3023.36 | 43.72 | 0.00 | 0.00 | 720.00 |
July | 929.74 | 14.66 | 915.08 | 2700.83 | 11.39 | 0.00 | 0.00 | 744.00 |
August | 853.57 | 2.64 | 850.93 | 2279.75 | 38.68 | 0.00 | 0.00 | 744.00 |
September | 760.57 | 0.05 | 760.52 | 1770.58 | 134.51 | 0.00 | 0.00 | 720.00 |
October | 658.90 | 0.00 | 658.90 | 1276.76 | 760.58 | 0.00 | 0.00 | 744.00 |
November | 558.10 | 0.00 | 558.10 | 690.64 | 1438.99 | 0.00 | 0.00 | 720.00 |
December | 517.20 | 0.00 | 517.20 | 353.81 | 1956.93 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 739.71 | 6.71 | 733.00 | 1584.52 | 773.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 517.20 | 0.00 | 517.20 | 321.97 | 11.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 942.61 | 34.75 | 915.08 | 3023.36 | 1995.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 757.13 | 303.88 | 453.25 | 704.28 | 1258.66 | 0.00 | 0.00 | 744.00 |
February | 919.83 | 379.74 | 540.09 | 1092.39 | 1026.96 | 0.00 | 0.00 | 672.00 |
March | 1122.16 | 463.21 | 658.95 | 1714.12 | 647.43 | 0.00 | 0.00 | 744.00 |
April | 1335.07 | 622.49 | 712.57 | 2633.91 | 244.28 | 0.00 | 0.00 | 720.00 |
May | 1314.00 | 582.53 | 731.47 | 3030.38 | 44.57 | 0.00 | 0.00 | 744.00 |
June | 1069.41 | 354.80 | 714.61 | 2739.19 | 32.66 | 0.00 | 0.00 | 720.00 |
July | 898.83 | 189.80 | 709.04 | 2256.94 | 7.61 | 0.00 | 0.00 | 744.00 |
August | 809.90 | 140.94 | 668.96 | 1900.13 | 28.81 | 0.00 | 0.00 | 744.00 |
September | 865.31 | 241.33 | 623.98 | 1756.48 | 102.79 | 0.00 | 0.00 | 720.00 |
October | 946.50 | 382.31 | 564.19 | 1648.06 | 521.63 | 0.00 | 0.00 | 744.00 |
November | 839.19 | 360.19 | 478.99 | 1124.57 | 944.22 | 0.00 | 0.00 | 720.00 |
December | 731.74 | 289.90 | 441.84 | 727.22 | 1266.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 967.16 | 358.70 | 608.45 | 1779.80 | 508.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 731.74 | 140.94 | 441.84 | 704.28 | 7.61 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1335.07 | 622.49 | 731.47 | 3030.38 | 1266.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2411.88 | 1465.77 | 946.11 | 3212.16 | 2062.63 | 0.00 | 0.00 | 744.00 |
February | 2292.97 | 1273.68 | 1019.29 | 3223.81 | 1701.56 | 0.00 | 0.00 | 672.00 |
March | 1959.90 | 865.41 | 1094.48 | 3009.24 | 1072.00 | 0.00 | 0.00 | 744.00 |
April | 1376.32 | 387.98 | 988.34 | 2684.46 | 383.40 | 0.00 | 0.00 | 720.00 |
May | 989.61 | 72.70 | 916.91 | 2823.06 | 58.13 | 0.00 | 0.00 | 744.00 |
June | 905.51 | 15.17 | 890.34 | 2947.56 | 44.54 | 0.00 | 0.00 | 720.00 |
July | 944.67 | 12.84 | 931.83 | 2715.97 | 10.65 | 0.00 | 0.00 | 744.00 |
August | 1002.10 | 53.37 | 948.73 | 2471.53 | 42.09 | 0.00 | 0.00 | 744.00 |
September | 1343.37 | 348.50 | 994.88 | 2644.87 | 167.48 | 0.00 | 0.00 | 720.00 |
October | 2311.46 | 1290.67 | 1020.79 | 4021.61 | 880.63 | 0.00 | 0.00 | 744.00 |
November | 2888.06 | 1909.22 | 978.84 | 4577.67 | 1599.82 | 0.00 | 0.00 | 720.00 |
December | 2577.51 | 1615.41 | 962.10 | 3599.45 | 2069.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1747.16 | 773.01 | 974.14 | 3159.86 | 837.17 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 905.51 | 12.84 | 890.34 | 2471.53 | 10.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2888.06 | 1909.22 | 1094.48 | 4577.67 | 2069.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 740.73 | 288.25 | 452.48 | 792.11 | 1415.77 | 0.00 | 0.00 | 744.00 |
February | 847.05 | 312.14 | 534.91 | 1068.07 | 1149.86 | 0.00 | 0.00 | 672.00 |
March | 1098.49 | 439.13 | 659.36 | 1726.30 | 734.91 | 0.00 | 0.00 | 744.00 |
April | 1335.19 | 626.17 | 709.01 | 2643.28 | 292.26 | 0.00 | 0.00 | 720.00 |
May | 1264.21 | 536.23 | 727.99 | 2944.05 | 61.78 | 0.00 | 0.00 | 744.00 |
June | 1187.44 | 461.21 | 726.23 | 2927.89 | 42.22 | 0.00 | 0.00 | 720.00 |
July | 881.15 | 171.37 | 709.78 | 2188.24 | 12.36 | 0.00 | 0.00 | 744.00 |
August | 809.26 | 143.83 | 665.43 | 1881.87 | 37.27 | 0.00 | 0.00 | 744.00 |
September | 889.61 | 261.18 | 628.43 | 1799.29 | 128.30 | 0.00 | 0.00 | 720.00 |
October | 925.89 | 368.67 | 557.22 | 1648.81 | 581.37 | 0.00 | 0.00 | 744.00 |
November | 837.61 | 356.96 | 480.65 | 1205.14 | 1057.21 | 0.00 | 0.00 | 720.00 |
December | 716.75 | 273.30 | 443.46 | 781.06 | 1392.56 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 960.94 | 352.74 | 608.20 | 1802.77 | 572.91 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 716.75 | 143.83 | 443.46 | 781.06 | 12.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1335.19 | 626.17 | 727.99 | 2944.05 | 1415.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 530.18 | 0.00 | 530.18 | 365.46 | 1808.92 | 0.00 | 0.00 | 744.00 |
February | 628.70 | 0.00 | 628.70 | 632.63 | 1467.27 | 0.00 | 0.00 | 672.00 |
March | 757.59 | 0.00 | 757.59 | 1124.49 | 936.24 | 0.00 | 0.00 | 744.00 |
April | 822.01 | 2.75 | 819.26 | 1983.36 | 337.40 | 0.00 | 0.00 | 720.00 |
May | 910.62 | 25.41 | 885.21 | 2736.16 | 62.32 | 0.00 | 0.00 | 744.00 |
June | 942.61 | 34.75 | 907.87 | 2965.67 | 47.23 | 0.00 | 0.00 | 720.00 |
July | 929.74 | 14.66 | 915.08 | 2639.01 | 12.03 | 0.00 | 0.00 | 744.00 |
August | 853.57 | 2.64 | 850.93 | 2231.18 | 41.69 | 0.00 | 0.00 | 744.00 |
September | 760.57 | 0.05 | 760.52 | 1738.05 | 143.09 | 0.00 | 0.00 | 720.00 |
October | 658.90 | 0.00 | 658.90 | 1264.68 | 744.24 | 0.00 | 0.00 | 744.00 |
November | 558.10 | 0.00 | 558.10 | 719.34 | 1344.66 | 0.00 | 0.00 | 720.00 |
December | 517.20 | 0.00 | 517.20 | 407.60 | 1775.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 739.71 | 6.71 | 733.00 | 1571.87 | 723.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 517.20 | 0.00 | 517.20 | 365.46 | 12.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 942.61 | 34.75 | 915.08 | 2965.67 | 1808.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 757.13 | 303.88 | 453.25 | 766.32 | 1141.40 | 0.00 | 0.00 | 744.00 |
February | 919.83 | 379.74 | 540.09 | 1129.13 | 962.45 | 0.00 | 0.00 | 672.00 |
March | 1122.16 | 463.21 | 658.95 | 1719.49 | 631.01 | 0.00 | 0.00 | 744.00 |
April | 1335.07 | 622.49 | 712.57 | 2619.29 | 247.39 | 0.00 | 0.00 | 720.00 |
May | 1314.00 | 582.53 | 731.47 | 3005.16 | 48.81 | 0.00 | 0.00 | 744.00 |
June | 1069.41 | 354.80 | 714.61 | 2712.40 | 34.69 | 0.00 | 0.00 | 720.00 |
July | 898.83 | 189.80 | 709.04 | 2227.45 | 7.84 | 0.00 | 0.00 | 744.00 |
August | 809.90 | 140.94 | 668.96 | 1879.00 | 30.67 | 0.00 | 0.00 | 744.00 |
September | 865.31 | 241.33 | 623.98 | 1744.66 | 107.66 | 0.00 | 0.00 | 720.00 |
October | 946.50 | 382.31 | 564.19 | 1648.83 | 513.18 | 0.00 | 0.00 | 744.00 |
November | 839.19 | 360.19 | 478.99 | 1151.64 | 894.31 | 0.00 | 0.00 | 720.00 |
December | 731.74 | 289.90 | 441.84 | 789.41 | 1157.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 967.16 | 358.70 | 608.45 | 1785.10 | 479.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 731.74 | 140.94 | 441.84 | 766.32 | 7.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1335.07 | 622.49 | 731.47 | 3005.16 | 1157.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2411.88 | 1465.77 | 946.11 | 3271.00 | 1892.85 | 0.00 | 0.00 | 744.00 |
February | 2292.97 | 1273.68 | 1019.29 | 3251.91 | 1603.86 | 0.00 | 0.00 | 672.00 |
March | 1959.90 | 865.41 | 1094.48 | 3002.57 | 1043.44 | 0.00 | 0.00 | 744.00 |
April | 1376.32 | 387.98 | 988.34 | 2652.56 | 389.23 | 0.00 | 0.00 | 720.00 |
May | 989.61 | 72.70 | 916.91 | 2773.65 | 65.09 | 0.00 | 0.00 | 744.00 |
June | 905.51 | 15.17 | 890.34 | 2893.34 | 48.47 | 0.00 | 0.00 | 720.00 |
July | 944.67 | 12.84 | 931.83 | 2657.58 | 11.22 | 0.00 | 0.00 | 744.00 |
August | 1002.10 | 53.37 | 948.73 | 2427.08 | 45.37 | 0.00 | 0.00 | 744.00 |
September | 1343.37 | 348.50 | 994.88 | 2616.58 | 176.19 | 0.00 | 0.00 | 720.00 |
October | 2311.46 | 1290.67 | 1020.79 | 4010.71 | 866.87 | 0.00 | 0.00 | 744.00 |
November | 2888.06 | 1909.22 | 978.84 | 4594.15 | 1526.80 | 0.00 | 0.00 | 720.00 |
December | 2577.51 | 1615.41 | 962.10 | 3657.97 | 1921.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1747.16 | 773.01 | 974.14 | 3149.51 | 795.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 905.51 | 12.84 | 890.34 | 2427.08 | 11.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2888.06 | 1909.22 | 1094.48 | 4594.15 | 1921.26 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 740.73 | 288.25 | 452.48 | 815.91 | 1308.29 | 0.00 | 0.00 | 744.00 |
February | 847.05 | 312.14 | 534.91 | 1081.94 | 1084.97 | 0.00 | 0.00 | 672.00 |
March | 1098.49 | 439.13 | 659.36 | 1719.30 | 714.82 | 0.00 | 0.00 | 744.00 |
April | 1335.19 | 626.17 | 709.01 | 2621.45 | 294.10 | 0.00 | 0.00 | 720.00 |
May | 1264.21 | 536.23 | 727.99 | 2915.46 | 65.71 | 0.00 | 0.00 | 744.00 |
June | 1187.44 | 461.21 | 726.23 | 2896.34 | 44.16 | 0.00 | 0.00 | 720.00 |
July | 881.15 | 171.37 | 709.78 | 2154.98 | 13.17 | 0.00 | 0.00 | 744.00 |
August | 809.26 | 143.83 | 665.43 | 1855.61 | 39.96 | 0.00 | 0.00 | 744.00 |
September | 889.61 | 261.18 | 628.43 | 1781.04 | 133.26 | 0.00 | 0.00 | 720.00 |
October | 925.89 | 368.67 | 557.22 | 1640.04 | 571.55 | 0.00 | 0.00 | 744.00 |
November | 837.61 | 356.96 | 480.65 | 1215.19 | 1004.99 | 0.00 | 0.00 | 720.00 |
December | 716.75 | 273.30 | 443.46 | 809.17 | 1291.94 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 960.94 | 352.74 | 608.20 | 1794.35 | 544.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 716.75 | 143.83 | 443.46 | 809.17 | 13.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1335.19 | 626.17 | 727.99 | 2915.46 | 1308.29 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284010E+09 | 0.00 | 0.284010E+09 | 0.120283E+09 | 0.125898E+10 |
February | 0.304195E+09 | 0.00 | 0.304195E+09 | 0.249524E+09 | 0.873282E+09 |
March | 0.405830E+09 | 0.00 | 0.405830E+09 | 0.580399E+09 | 0.559864E+09 |
April | 0.426135E+09 | 1426653.88 | 0.424708E+09 | 0.101802E+10 | 0.183269E+09 |
May | 0.487806E+09 | 13611042.92 | 0.474195E+09 | 0.147846E+10 | 29353561.61 |
June | 0.488657E+09 | 18012515.22 | 0.470644E+09 | 0.155066E+10 | 21164518.08 |
July | 0.498049E+09 | 7851931.65 | 0.490197E+09 | 0.142471E+10 | 4748561.07 |
August | 0.457246E+09 | 1414549.17 | 0.455831E+09 | 0.119257E+10 | 18817052.72 |
September | 0.394284E+09 | 26946.60 | 0.394257E+09 | 0.908351E+09 | 69507025.75 |
October | 0.352964E+09 | 0.00 | 0.352964E+09 | 0.664508E+09 | 0.425643E+09 |
November | 0.289320E+09 | 0.00 | 0.289320E+09 | 0.321955E+09 | 0.834049E+09 |
December | 0.277057E+09 | 0.00 | 0.277057E+09 | 0.131424E+09 | 0.124178E+10 |
Annual Sum or Average | 0.466555E+10 | 42343639.44 | 0.462321E+10 | 0.964086E+10 | 0.552046E+10 |
Minimum of Months | 0.277057E+09 | 0.00 | 0.277057E+09 | 0.120283E+09 | 4748561.07 |
Maximum of Months | 0.498049E+09 | 18012515.22 | 0.490197E+09 | 0.155066E+10 | 0.125898E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284010E+09 | 0.00 | 0.284010E+09 | 0.120283E+09 | 0.125898E+10 |
February | 0.304195E+09 | 0.00 | 0.304195E+09 | 0.249524E+09 | 0.873282E+09 |
March | 0.405830E+09 | 0.00 | 0.405830E+09 | 0.580399E+09 | 0.559864E+09 |
April | 0.426134E+09 | 1426652.17 | 0.424708E+09 | 0.101802E+10 | 0.183269E+09 |
May | 0.487805E+09 | 13611026.59 | 0.474194E+09 | 0.147846E+10 | 29353504.52 |
June | 0.488657E+09 | 18012493.61 | 0.470644E+09 | 0.155066E+10 | 21164498.11 |
July | 0.498048E+09 | 7851922.23 | 0.490197E+09 | 0.142471E+10 | 4748550.04 |
August | 0.457245E+09 | 1414547.47 | 0.455831E+09 | 0.119257E+10 | 18817022.28 |
September | 0.394284E+09 | 26946.57 | 0.394257E+09 | 0.908351E+09 | 69506926.56 |
October | 0.352964E+09 | 0.00 | 0.352964E+09 | 0.664508E+09 | 0.425643E+09 |
November | 0.289320E+09 | 0.00 | 0.289320E+09 | 0.321955E+09 | 0.834048E+09 |
December | 0.277056E+09 | 0.00 | 0.277056E+09 | 0.131423E+09 | 0.124178E+10 |
Annual Sum or Average | 0.466555E+10 | 42343588.63 | 0.462321E+10 | 0.964085E+10 | 0.552046E+10 |
Minimum of Months | 0.277056E+09 | 0.00 | 0.277056E+09 | 0.120283E+09 | 4748550.04 |
Maximum of Months | 0.498048E+09 | 18012493.61 | 0.490197E+09 | 0.155066E+10 | 0.125898E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284010E+09 | 0.00 | 0.284010E+09 | 0.120283E+09 | 0.125898E+10 |
February | 0.304195E+09 | 0.00 | 0.304195E+09 | 0.249524E+09 | 0.873282E+09 |
March | 0.405830E+09 | 0.00 | 0.405830E+09 | 0.580399E+09 | 0.559864E+09 |
April | 0.426135E+09 | 1426653.88 | 0.424708E+09 | 0.101802E+10 | 0.183269E+09 |
May | 0.487806E+09 | 13611042.92 | 0.474195E+09 | 0.147846E+10 | 29353561.61 |
June | 0.488657E+09 | 18012515.22 | 0.470644E+09 | 0.155066E+10 | 21164518.08 |
July | 0.498049E+09 | 7851931.65 | 0.490197E+09 | 0.142471E+10 | 4748561.07 |
August | 0.457246E+09 | 1414549.17 | 0.455831E+09 | 0.119257E+10 | 18817052.72 |
September | 0.394284E+09 | 26946.60 | 0.394257E+09 | 0.908351E+09 | 69507025.75 |
October | 0.352964E+09 | 0.00 | 0.352964E+09 | 0.664508E+09 | 0.425643E+09 |
November | 0.289320E+09 | 0.00 | 0.289320E+09 | 0.321955E+09 | 0.834049E+09 |
December | 0.277057E+09 | 0.00 | 0.277057E+09 | 0.131424E+09 | 0.124178E+10 |
Annual Sum or Average | 0.466555E+10 | 42343639.44 | 0.462321E+10 | 0.964086E+10 | 0.552046E+10 |
Minimum of Months | 0.277057E+09 | 0.00 | 0.277057E+09 | 0.120283E+09 | 4748561.07 |
Maximum of Months | 0.498049E+09 | 18012515.22 | 0.490197E+09 | 0.155066E+10 | 0.125898E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.284010E+09 | 0.00 | 0.284010E+09 | 0.120283E+09 | 0.125898E+10 |
February | 0.304195E+09 | 0.00 | 0.304195E+09 | 0.249524E+09 | 0.873282E+09 |
March | 0.405830E+09 | 0.00 | 0.405830E+09 | 0.580399E+09 | 0.559864E+09 |
April | 0.426134E+09 | 1426652.17 | 0.424708E+09 | 0.101802E+10 | 0.183269E+09 |
May | 0.487805E+09 | 13611026.59 | 0.474194E+09 | 0.147846E+10 | 29353504.52 |
June | 0.488657E+09 | 18012493.61 | 0.470644E+09 | 0.155066E+10 | 21164498.11 |
July | 0.498048E+09 | 7851922.23 | 0.490197E+09 | 0.142471E+10 | 4748550.04 |
August | 0.457245E+09 | 1414547.47 | 0.455831E+09 | 0.119257E+10 | 18817022.28 |
September | 0.394284E+09 | 26946.57 | 0.394257E+09 | 0.908351E+09 | 69506926.56 |
October | 0.352964E+09 | 0.00 | 0.352964E+09 | 0.664508E+09 | 0.425643E+09 |
November | 0.289320E+09 | 0.00 | 0.289320E+09 | 0.321955E+09 | 0.834048E+09 |
December | 0.277056E+09 | 0.00 | 0.277056E+09 | 0.131423E+09 | 0.124178E+10 |
Annual Sum or Average | 0.466555E+10 | 42343588.63 | 0.462321E+10 | 0.964085E+10 | 0.552046E+10 |
Minimum of Months | 0.277056E+09 | 0.00 | 0.277056E+09 | 0.120283E+09 | 4748550.04 |
Maximum of Months | 0.498048E+09 | 18012493.61 | 0.490197E+09 | 0.155066E+10 | 0.125898E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.283998E+09 | 0.00 | 0.283998E+09 | 0.120278E+09 | 0.125893E+10 |
February | 0.304183E+09 | 0.00 | 0.304183E+09 | 0.249514E+09 | 0.873247E+09 |
March | 0.405814E+09 | 0.00 | 0.405814E+09 | 0.580376E+09 | 0.559841E+09 |
April | 0.426117E+09 | 1426596.38 | 0.424691E+09 | 0.101797E+10 | 0.183262E+09 |
May | 0.487786E+09 | 13610494.34 | 0.474176E+09 | 0.147840E+10 | 29352378.53 |
June | 0.488637E+09 | 18011789.24 | 0.470625E+09 | 0.155060E+10 | 21163665.06 |
July | 0.498029E+09 | 7851615.18 | 0.490177E+09 | 0.142465E+10 | 4748369.68 |
August | 0.457227E+09 | 1414492.15 | 0.455813E+09 | 0.119252E+10 | 18816294.31 |
September | 0.394268E+09 | 26945.52 | 0.394242E+09 | 0.908314E+09 | 69504224.31 |
October | 0.352950E+09 | 0.00 | 0.352950E+09 | 0.664481E+09 | 0.425626E+09 |
November | 0.289309E+09 | 0.00 | 0.289309E+09 | 0.321942E+09 | 0.834015E+09 |
December | 0.277046E+09 | 0.00 | 0.277046E+09 | 0.131418E+09 | 0.124173E+10 |
Annual Sum or Average | 0.466536E+10 | 42341932.81 | 0.462302E+10 | 0.964047E+10 | 0.552024E+10 |
Minimum of Months | 0.277046E+09 | 0.00 | 0.277046E+09 | 0.120278E+09 | 4748369.68 |
Maximum of Months | 0.498029E+09 | 18011789.24 | 0.490177E+09 | 0.155060E+10 | 0.125893E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.675970E+09 | 0.271308E+09 | 0.404662E+09 | 0.581880E+09 | 0.125848E+10 |
February | 0.741758E+09 | 0.306221E+09 | 0.435536E+09 | 0.866991E+09 | 0.885226E+09 |
March | 0.100187E+10 | 0.413556E+09 | 0.588316E+09 | 0.154185E+10 | 0.577693E+09 |
April | 0.115351E+10 | 0.537839E+09 | 0.615670E+09 | 0.229432E+10 | 0.195331E+09 |
May | 0.117315E+10 | 0.520090E+09 | 0.653060E+09 | 0.272546E+10 | 34641314.84 |
June | 0.923981E+09 | 0.306550E+09 | 0.617431E+09 | 0.238774E+10 | 22617555.24 |
July | 0.802487E+09 | 0.169452E+09 | 0.633035E+09 | 0.203526E+10 | 3804840.19 |
August | 0.723085E+09 | 0.125832E+09 | 0.597253E+09 | 0.171816E+10 | 15517457.79 |
September | 0.747632E+09 | 0.208507E+09 | 0.539125E+09 | 0.153382E+10 | 76733275.55 |
October | 0.845041E+09 | 0.341327E+09 | 0.503714E+09 | 0.148201E+10 | 0.455713E+09 |
November | 0.725065E+09 | 0.311210E+09 | 0.413855E+09 | 0.963303E+09 | 0.851061E+09 |
December | 0.653307E+09 | 0.258828E+09 | 0.394479E+09 | 0.610551E+09 | 0.123607E+10 |
Annual Sum or Average | 0.101669E+11 | 0.377072E+10 | 0.639614E+10 | 0.187413E+11 | 0.561288E+10 |
Minimum of Months | 0.653307E+09 | 0.125832E+09 | 0.394479E+09 | 0.581880E+09 | 3804840.19 |
Maximum of Months | 0.117315E+10 | 0.537839E+09 | 0.653060E+09 | 0.272546E+10 | 0.125848E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.675970E+09 | 0.271308E+09 | 0.404662E+09 | 0.581880E+09 | 0.125848E+10 |
February | 0.741758E+09 | 0.306221E+09 | 0.435536E+09 | 0.866991E+09 | 0.885226E+09 |
March | 0.100187E+10 | 0.413556E+09 | 0.588316E+09 | 0.154185E+10 | 0.577693E+09 |
April | 0.115351E+10 | 0.537839E+09 | 0.615670E+09 | 0.229432E+10 | 0.195331E+09 |
May | 0.117315E+10 | 0.520090E+09 | 0.653060E+09 | 0.272546E+10 | 34641314.84 |
June | 0.923981E+09 | 0.306550E+09 | 0.617431E+09 | 0.238774E+10 | 22617555.24 |
July | 0.802487E+09 | 0.169452E+09 | 0.633035E+09 | 0.203526E+10 | 3804840.19 |
August | 0.723085E+09 | 0.125832E+09 | 0.597253E+09 | 0.171816E+10 | 15517457.79 |
September | 0.747632E+09 | 0.208507E+09 | 0.539125E+09 | 0.153382E+10 | 76733275.55 |
October | 0.845041E+09 | 0.341327E+09 | 0.503714E+09 | 0.148201E+10 | 0.455713E+09 |
November | 0.725065E+09 | 0.311210E+09 | 0.413855E+09 | 0.963303E+09 | 0.851061E+09 |
December | 0.653307E+09 | 0.258828E+09 | 0.394479E+09 | 0.610551E+09 | 0.123607E+10 |
Annual Sum or Average | 0.101669E+11 | 0.377072E+10 | 0.639614E+10 | 0.187413E+11 | 0.561288E+10 |
Minimum of Months | 0.653307E+09 | 0.125832E+09 | 0.394479E+09 | 0.581880E+09 | 3804840.19 |
Maximum of Months | 0.117315E+10 | 0.537839E+09 | 0.653060E+09 | 0.272546E+10 | 0.125848E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.675957E+09 | 0.271303E+09 | 0.404655E+09 | 0.581869E+09 | 0.125846E+10 |
February | 0.741744E+09 | 0.306216E+09 | 0.435528E+09 | 0.866975E+09 | 0.885210E+09 |
March | 0.100185E+10 | 0.413548E+09 | 0.588305E+09 | 0.154183E+10 | 0.577682E+09 |
April | 0.115349E+10 | 0.537830E+09 | 0.615658E+09 | 0.229428E+10 | 0.195328E+09 |
May | 0.117313E+10 | 0.520080E+09 | 0.653048E+09 | 0.272541E+10 | 34640681.86 |
June | 0.923964E+09 | 0.306545E+09 | 0.617419E+09 | 0.238770E+10 | 22617141.97 |
July | 0.802472E+09 | 0.169449E+09 | 0.633023E+09 | 0.203522E+10 | 3804770.67 |
August | 0.723072E+09 | 0.125830E+09 | 0.597242E+09 | 0.171813E+10 | 15517174.26 |
September | 0.747618E+09 | 0.208504E+09 | 0.539115E+09 | 0.153379E+10 | 76731873.47 |
October | 0.845025E+09 | 0.341321E+09 | 0.503705E+09 | 0.148198E+10 | 0.455705E+09 |
November | 0.725052E+09 | 0.311204E+09 | 0.413848E+09 | 0.963285E+09 | 0.851045E+09 |
December | 0.653295E+09 | 0.258823E+09 | 0.394472E+09 | 0.610539E+09 | 0.123604E+10 |
Annual Sum or Average | 0.101667E+11 | 0.377065E+10 | 0.639602E+10 | 0.187410E+11 | 0.561278E+10 |
Minimum of Months | 0.653295E+09 | 0.125830E+09 | 0.394472E+09 | 0.581869E+09 | 3804770.67 |
Maximum of Months | 0.117313E+10 | 0.537830E+09 | 0.653048E+09 | 0.272541E+10 | 0.125846E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129201E+10 | 0.785191E+09 | 0.506819E+09 | 0.172052E+10 | 0.114988E+10 |
February | 0.110945E+10 | 0.616266E+09 | 0.493179E+09 | 0.156477E+10 | 0.848825E+09 |
March | 0.104989E+10 | 0.463591E+09 | 0.586299E+09 | 0.161452E+10 | 0.579958E+09 |
April | 0.713494E+09 | 0.201133E+09 | 0.512361E+09 | 0.137793E+10 | 0.199839E+09 |
May | 0.530122E+09 | 38943904.85 | 0.491178E+09 | 0.149641E+10 | 30756498.90 |
June | 0.469421E+09 | 7865298.37 | 0.461555E+09 | 0.151166E+10 | 21495811.97 |
July | 0.506049E+09 | 6879086.05 | 0.499170E+09 | 0.143417E+10 | 4498901.67 |
August | 0.536813E+09 | 28588753.01 | 0.508224E+09 | 0.130375E+10 | 19919457.49 |
September | 0.696412E+09 | 0.180662E+09 | 0.515750E+09 | 0.137292E+10 | 80709509.91 |
October | 0.123822E+10 | 0.691396E+09 | 0.546823E+09 | 0.216441E+10 | 0.461688E+09 |
November | 0.149719E+10 | 0.989752E+09 | 0.507435E+09 | 0.238411E+10 | 0.839080E+09 |
December | 0.138074E+10 | 0.865351E+09 | 0.515386E+09 | 0.192488E+10 | 0.115263E+10 |
Annual Sum or Average | 0.110198E+11 | 0.487562E+10 | 0.614418E+10 | 0.198701E+11 | 0.538929E+10 |
Minimum of Months | 0.469421E+09 | 6879086.05 | 0.461555E+09 | 0.130375E+10 | 4498901.67 |
Maximum of Months | 0.149719E+10 | 0.989752E+09 | 0.586299E+09 | 0.238411E+10 | 0.115263E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129201E+10 | 0.785190E+09 | 0.506819E+09 | 0.172052E+10 | 0.114988E+10 |
February | 0.110944E+10 | 0.616265E+09 | 0.493179E+09 | 0.156477E+10 | 0.848824E+09 |
March | 0.104989E+10 | 0.463590E+09 | 0.586299E+09 | 0.161451E+10 | 0.579958E+09 |
April | 0.713494E+09 | 0.201133E+09 | 0.512361E+09 | 0.137793E+10 | 0.199839E+09 |
May | 0.530121E+09 | 38943858.13 | 0.491177E+09 | 0.149641E+10 | 30756440.37 |
June | 0.469420E+09 | 7865288.93 | 0.461555E+09 | 0.151166E+10 | 21495793.23 |
July | 0.506049E+09 | 6879077.80 | 0.499169E+09 | 0.143417E+10 | 4498891.67 |
August | 0.536812E+09 | 28588718.71 | 0.508223E+09 | 0.130375E+10 | 19919426.71 |
September | 0.696411E+09 | 0.180662E+09 | 0.515749E+09 | 0.137292E+10 | 80709402.89 |
October | 0.123822E+10 | 0.691395E+09 | 0.546822E+09 | 0.216441E+10 | 0.461687E+09 |
November | 0.149719E+10 | 0.989751E+09 | 0.507435E+09 | 0.238410E+10 | 0.839080E+09 |
December | 0.138074E+10 | 0.865350E+09 | 0.515385E+09 | 0.192487E+10 | 0.115263E+10 |
Annual Sum or Average | 0.110198E+11 | 0.487561E+10 | 0.614417E+10 | 0.198700E+11 | 0.538928E+10 |
Minimum of Months | 0.469420E+09 | 6879077.80 | 0.461555E+09 | 0.130375E+10 | 4498891.67 |
Maximum of Months | 0.149719E+10 | 0.989751E+09 | 0.586299E+09 | 0.238410E+10 | 0.115263E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129201E+10 | 0.785191E+09 | 0.506819E+09 | 0.172052E+10 | 0.114988E+10 |
February | 0.110945E+10 | 0.616266E+09 | 0.493179E+09 | 0.156477E+10 | 0.848825E+09 |
March | 0.104989E+10 | 0.463591E+09 | 0.586299E+09 | 0.161452E+10 | 0.579958E+09 |
April | 0.713494E+09 | 0.201133E+09 | 0.512361E+09 | 0.137793E+10 | 0.199839E+09 |
May | 0.530122E+09 | 38943904.85 | 0.491178E+09 | 0.149641E+10 | 30756498.90 |
June | 0.469421E+09 | 7865298.37 | 0.461555E+09 | 0.151166E+10 | 21495811.97 |
July | 0.506049E+09 | 6879086.05 | 0.499170E+09 | 0.143417E+10 | 4498901.67 |
August | 0.536813E+09 | 28588753.01 | 0.508224E+09 | 0.130375E+10 | 19919457.49 |
September | 0.696412E+09 | 0.180662E+09 | 0.515750E+09 | 0.137292E+10 | 80709509.91 |
October | 0.123822E+10 | 0.691396E+09 | 0.546823E+09 | 0.216441E+10 | 0.461688E+09 |
November | 0.149719E+10 | 0.989752E+09 | 0.507435E+09 | 0.238411E+10 | 0.839080E+09 |
December | 0.138074E+10 | 0.865351E+09 | 0.515386E+09 | 0.192488E+10 | 0.115263E+10 |
Annual Sum or Average | 0.110198E+11 | 0.487562E+10 | 0.614418E+10 | 0.198701E+11 | 0.538929E+10 |
Minimum of Months | 0.469421E+09 | 6879086.05 | 0.461555E+09 | 0.130375E+10 | 4498901.67 |
Maximum of Months | 0.149719E+10 | 0.989752E+09 | 0.586299E+09 | 0.238411E+10 | 0.115263E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129201E+10 | 0.785190E+09 | 0.506819E+09 | 0.172052E+10 | 0.114988E+10 |
February | 0.110944E+10 | 0.616265E+09 | 0.493179E+09 | 0.156477E+10 | 0.848824E+09 |
March | 0.104989E+10 | 0.463590E+09 | 0.586299E+09 | 0.161451E+10 | 0.579958E+09 |
April | 0.713494E+09 | 0.201133E+09 | 0.512361E+09 | 0.137793E+10 | 0.199839E+09 |
May | 0.530121E+09 | 38943858.13 | 0.491177E+09 | 0.149641E+10 | 30756440.37 |
June | 0.469420E+09 | 7865288.93 | 0.461555E+09 | 0.151166E+10 | 21495793.23 |
July | 0.506049E+09 | 6879077.80 | 0.499169E+09 | 0.143417E+10 | 4498891.67 |
August | 0.536812E+09 | 28588718.71 | 0.508223E+09 | 0.130375E+10 | 19919426.71 |
September | 0.696411E+09 | 0.180662E+09 | 0.515749E+09 | 0.137292E+10 | 80709402.89 |
October | 0.123822E+10 | 0.691395E+09 | 0.546822E+09 | 0.216441E+10 | 0.461687E+09 |
November | 0.149719E+10 | 0.989751E+09 | 0.507435E+09 | 0.238410E+10 | 0.839080E+09 |
December | 0.138074E+10 | 0.865350E+09 | 0.515385E+09 | 0.192487E+10 | 0.115263E+10 |
Annual Sum or Average | 0.110198E+11 | 0.487561E+10 | 0.614417E+10 | 0.198700E+11 | 0.538928E+10 |
Minimum of Months | 0.469420E+09 | 6879077.80 | 0.461555E+09 | 0.130375E+10 | 4498891.67 |
Maximum of Months | 0.149719E+10 | 0.989751E+09 | 0.586299E+09 | 0.238410E+10 | 0.115263E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129196E+10 | 0.785159E+09 | 0.506799E+09 | 0.172046E+10 | 0.114984E+10 |
February | 0.110940E+10 | 0.616241E+09 | 0.493159E+09 | 0.156470E+10 | 0.848790E+09 |
March | 0.104985E+10 | 0.463572E+09 | 0.586276E+09 | 0.161445E+10 | 0.579935E+09 |
April | 0.713466E+09 | 0.201125E+09 | 0.512340E+09 | 0.137788E+10 | 0.199831E+09 |
May | 0.530100E+09 | 38942335.24 | 0.491158E+09 | 0.149635E+10 | 30755259.28 |
June | 0.469402E+09 | 7864981.36 | 0.461537E+09 | 0.151160E+10 | 21494945.59 |
July | 0.506029E+09 | 6878808.80 | 0.499150E+09 | 0.143411E+10 | 4498720.34 |
August | 0.536791E+09 | 28587600.76 | 0.508203E+09 | 0.130370E+10 | 19918654.65 |
September | 0.696384E+09 | 0.180655E+09 | 0.515729E+09 | 0.137287E+10 | 80706256.96 |
October | 0.123817E+10 | 0.691368E+09 | 0.546801E+09 | 0.216433E+10 | 0.461669E+09 |
November | 0.149713E+10 | 0.989712E+09 | 0.507415E+09 | 0.238401E+10 | 0.839046E+09 |
December | 0.138068E+10 | 0.865316E+09 | 0.515365E+09 | 0.192480E+10 | 0.115259E+10 |
Annual Sum or Average | 0.110194E+11 | 0.487542E+10 | 0.614393E+10 | 0.198693E+11 | 0.538907E+10 |
Minimum of Months | 0.469402E+09 | 6878808.80 | 0.461537E+09 | 0.130370E+10 | 4498720.34 |
Maximum of Months | 0.149713E+10 | 0.989712E+09 | 0.586276E+09 | 0.238401E+10 | 0.115259E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.661329E+09 | 0.257348E+09 | 0.403981E+09 | 0.646396E+09 | 0.148091E+10 |
February | 0.683067E+09 | 0.251715E+09 | 0.431353E+09 | 0.811602E+09 | 0.108468E+10 |
March | 0.980739E+09 | 0.392060E+09 | 0.588679E+09 | 0.149883E+10 | 0.757493E+09 |
April | 0.115361E+10 | 0.541018E+09 | 0.612594E+09 | 0.222180E+10 | 0.315862E+09 |
May | 0.112870E+10 | 0.478750E+09 | 0.649952E+09 | 0.259669E+10 | 64720603.53 |
June | 0.102596E+10 | 0.398488E+09 | 0.627468E+09 | 0.247470E+10 | 46746720.25 |
July | 0.786699E+09 | 0.153001E+09 | 0.633698E+09 | 0.186834E+10 | 23504550.85 |
August | 0.722515E+09 | 0.128413E+09 | 0.594102E+09 | 0.157646E+10 | 72048933.78 |
September | 0.768633E+09 | 0.225663E+09 | 0.542970E+09 | 0.153067E+10 | 0.133222E+09 |
October | 0.826647E+09 | 0.329152E+09 | 0.497494E+09 | 0.143889E+10 | 0.580147E+09 |
November | 0.723701E+09 | 0.308415E+09 | 0.415286E+09 | 0.988029E+09 | 0.106608E+10 |
December | 0.639925E+09 | 0.244002E+09 | 0.395924E+09 | 0.607825E+09 | 0.154509E+10 |
Annual Sum or Average | 0.101015E+11 | 0.370802E+10 | 0.639350E+10 | 0.182602E+11 | 0.717051E+10 |
Minimum of Months | 0.639925E+09 | 0.128413E+09 | 0.395924E+09 | 0.607825E+09 | 23504550.85 |
Maximum of Months | 0.115361E+10 | 0.541018E+09 | 0.649952E+09 | 0.259669E+10 | 0.154509E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.661329E+09 | 0.257348E+09 | 0.403981E+09 | 0.646396E+09 | 0.148091E+10 |
February | 0.683067E+09 | 0.251715E+09 | 0.431353E+09 | 0.811602E+09 | 0.108468E+10 |
March | 0.980739E+09 | 0.392060E+09 | 0.588679E+09 | 0.149883E+10 | 0.757493E+09 |
April | 0.115361E+10 | 0.541018E+09 | 0.612594E+09 | 0.222180E+10 | 0.315862E+09 |
May | 0.112870E+10 | 0.478750E+09 | 0.649952E+09 | 0.259669E+10 | 64720603.53 |
June | 0.102596E+10 | 0.398488E+09 | 0.627468E+09 | 0.247470E+10 | 46746720.25 |
July | 0.786699E+09 | 0.153001E+09 | 0.633698E+09 | 0.186834E+10 | 23504550.85 |
August | 0.722515E+09 | 0.128413E+09 | 0.594102E+09 | 0.157646E+10 | 72048933.78 |
September | 0.768633E+09 | 0.225663E+09 | 0.542970E+09 | 0.153067E+10 | 0.133222E+09 |
October | 0.826647E+09 | 0.329152E+09 | 0.497494E+09 | 0.143889E+10 | 0.580147E+09 |
November | 0.723701E+09 | 0.308415E+09 | 0.415286E+09 | 0.988029E+09 | 0.106608E+10 |
December | 0.639925E+09 | 0.244002E+09 | 0.395924E+09 | 0.607825E+09 | 0.154509E+10 |
Annual Sum or Average | 0.101015E+11 | 0.370802E+10 | 0.639350E+10 | 0.182602E+11 | 0.717051E+10 |
Minimum of Months | 0.639925E+09 | 0.128413E+09 | 0.395924E+09 | 0.607825E+09 | 23504550.85 |
Maximum of Months | 0.115361E+10 | 0.541018E+09 | 0.649952E+09 | 0.259669E+10 | 0.154509E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.661317E+09 | 0.257343E+09 | 0.403974E+09 | 0.646384E+09 | 0.148088E+10 |
February | 0.683055E+09 | 0.251710E+09 | 0.431345E+09 | 0.811587E+09 | 0.108466E+10 |
March | 0.980721E+09 | 0.392052E+09 | 0.588669E+09 | 0.149880E+10 | 0.757480E+09 |
April | 0.115359E+10 | 0.541008E+09 | 0.612583E+09 | 0.222176E+10 | 0.315856E+09 |
May | 0.112868E+10 | 0.478741E+09 | 0.649940E+09 | 0.259665E+10 | 64719420.94 |
June | 0.102594E+10 | 0.398481E+09 | 0.627456E+09 | 0.247465E+10 | 46745866.09 |
July | 0.786685E+09 | 0.152998E+09 | 0.633687E+09 | 0.186831E+10 | 23504121.37 |
August | 0.722502E+09 | 0.128411E+09 | 0.594091E+09 | 0.157643E+10 | 72047617.29 |
September | 0.768619E+09 | 0.225659E+09 | 0.542960E+09 | 0.153064E+10 | 0.133220E+09 |
October | 0.826631E+09 | 0.329146E+09 | 0.497485E+09 | 0.143886E+10 | 0.580136E+09 |
November | 0.723688E+09 | 0.308409E+09 | 0.415278E+09 | 0.988011E+09 | 0.106606E+10 |
December | 0.639914E+09 | 0.243997E+09 | 0.395917E+09 | 0.607814E+09 | 0.154506E+10 |
Annual Sum or Average | 0.101013E+11 | 0.370796E+10 | 0.639338E+10 | 0.182599E+11 | 0.717038E+10 |
Minimum of Months | 0.639914E+09 | 0.128411E+09 | 0.395917E+09 | 0.607814E+09 | 23504121.37 |
Maximum of Months | 0.115359E+10 | 0.541008E+09 | 0.649940E+09 | 0.259665E+10 | 0.154506E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142003E+10 | 0.00 | 0.142003E+10 | 0.862371E+09 | 0.534495E+10 |
February | 0.152096E+10 | 0.00 | 0.152096E+10 | 0.144944E+10 | 0.382447E+10 |
March | 0.202913E+10 | 0.00 | 0.202913E+10 | 0.301995E+10 | 0.259607E+10 |
April | 0.213065E+10 | 7133183.15 | 0.212351E+10 | 0.523984E+10 | 0.861460E+09 |
May | 0.243900E+10 | 68054391.70 | 0.237094E+10 | 0.747446E+10 | 0.148605E+09 |
June | 0.244325E+10 | 90061487.09 | 0.235319E+10 | 0.783656E+10 | 0.113310E+09 |
July | 0.249021E+10 | 39259183.52 | 0.245096E+10 | 0.723390E+10 | 30499989.17 |
August | 0.228620E+10 | 7072660.31 | 0.227913E+10 | 0.610609E+10 | 0.103595E+09 |
September | 0.197140E+10 | 134731.39 | 0.197126E+10 | 0.458934E+10 | 0.348641E+09 |
October | 0.176480E+10 | 0.00 | 0.176480E+10 | 0.341967E+10 | 0.203715E+10 |
November | 0.144658E+10 | 0.00 | 0.144658E+10 | 0.179014E+10 | 0.372986E+10 |
December | 0.138527E+10 | 0.00 | 0.138527E+10 | 0.947637E+09 | 0.524143E+10 |
Annual Sum or Average | 0.233275E+11 | 0.211716E+09 | 0.231158E+11 | 0.499694E+11 | 0.243800E+11 |
Minimum of Months | 0.138527E+10 | 0.00 | 0.138527E+10 | 0.862371E+09 | 30499989.17 |
Maximum of Months | 0.249021E+10 | 90061487.09 | 0.245096E+10 | 0.783656E+10 | 0.534495E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202789E+10 | 0.813915E+09 | 0.121397E+10 | 0.188634E+10 | 0.337120E+10 |
February | 0.222525E+10 | 0.918655E+09 | 0.130660E+10 | 0.264272E+10 | 0.248442E+10 |
March | 0.300558E+10 | 0.124066E+10 | 0.176493E+10 | 0.459111E+10 | 0.173409E+10 |
April | 0.346049E+10 | 0.161350E+10 | 0.184699E+10 | 0.682709E+10 | 0.633177E+09 |
May | 0.351941E+10 | 0.156025E+10 | 0.195916E+10 | 0.811658E+10 | 0.119368E+09 |
June | 0.277191E+10 | 0.919641E+09 | 0.185227E+10 | 0.709998E+10 | 84645281.48 |
July | 0.240744E+10 | 0.508352E+09 | 0.189909E+10 | 0.604499E+10 | 20369368.18 |
August | 0.216923E+10 | 0.377493E+09 | 0.179174E+10 | 0.508931E+10 | 77169590.09 |
September | 0.224287E+10 | 0.625516E+09 | 0.161736E+10 | 0.455279E+10 | 0.266433E+09 |
October | 0.253510E+10 | 0.102397E+10 | 0.151113E+10 | 0.441415E+10 | 0.139714E+10 |
November | 0.217517E+10 | 0.933620E+09 | 0.124155E+10 | 0.291488E+10 | 0.244743E+10 |
December | 0.195990E+10 | 0.776476E+09 | 0.118343E+10 | 0.194777E+10 | 0.339246E+10 |
Annual Sum or Average | 0.305003E+11 | 0.113120E+11 | 0.191882E+11 | 0.561277E+11 | 0.160279E+11 |
Minimum of Months | 0.195990E+10 | 0.377493E+09 | 0.118343E+10 | 0.188634E+10 | 20369368.18 |
Maximum of Months | 0.351941E+10 | 0.161350E+10 | 0.195916E+10 | 0.811658E+10 | 0.339246E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.645997E+10 | 0.392591E+10 | 0.253407E+10 | 0.860346E+10 | 0.552454E+10 |
February | 0.554716E+10 | 0.308129E+10 | 0.246587E+10 | 0.779903E+10 | 0.411641E+10 |
March | 0.524939E+10 | 0.231792E+10 | 0.293146E+10 | 0.805995E+10 | 0.287125E+10 |
April | 0.356743E+10 | 0.100565E+10 | 0.256177E+10 | 0.695812E+10 | 0.993784E+09 |
May | 0.265058E+10 | 0.194717E+09 | 0.245586E+10 | 0.756129E+10 | 0.155695E+09 |
June | 0.234707E+10 | 39326016.30 | 0.230775E+10 | 0.764009E+10 | 0.115444E+09 |
July | 0.253021E+10 | 34395014.37 | 0.249582E+10 | 0.727446E+10 | 28522860.43 |
August | 0.268403E+10 | 0.142942E+09 | 0.254109E+10 | 0.661975E+10 | 0.112737E+09 |
September | 0.348202E+10 | 0.903301E+09 | 0.257872E+10 | 0.685549E+10 | 0.434115E+09 |
October | 0.619102E+10 | 0.345694E+10 | 0.273408E+10 | 0.107715E+11 | 0.235868E+10 |
November | 0.748585E+10 | 0.494870E+10 | 0.253715E+10 | 0.118653E+11 | 0.414675E+10 |
December | 0.690360E+10 | 0.432670E+10 | 0.257690E+10 | 0.964077E+10 | 0.554314E+10 |
Annual Sum or Average | 0.550983E+11 | 0.243778E+11 | 0.307205E+11 | 0.996492E+11 | 0.264011E+11 |
Minimum of Months | 0.234707E+10 | 34395014.37 | 0.230775E+10 | 0.661975E+10 | 28522860.43 |
Maximum of Months | 0.748585E+10 | 0.494870E+10 | 0.293146E+10 | 0.118653E+11 | 0.554314E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198397E+10 | 0.772036E+09 | 0.121193E+10 | 0.212160E+10 | 0.379199E+10 |
February | 0.204918E+10 | 0.755137E+09 | 0.129404E+10 | 0.258388E+10 | 0.278174E+10 |
March | 0.294219E+10 | 0.117617E+10 | 0.176602E+10 | 0.462373E+10 | 0.196838E+10 |
April | 0.346080E+10 | 0.162304E+10 | 0.183776E+10 | 0.685137E+10 | 0.757548E+09 |
May | 0.338607E+10 | 0.143623E+10 | 0.194984E+10 | 0.788535E+10 | 0.165458E+09 |
June | 0.307783E+10 | 0.119545E+10 | 0.188238E+10 | 0.758910E+10 | 0.109437E+09 |
July | 0.236007E+10 | 0.458998E+09 | 0.190108E+10 | 0.586097E+10 | 33108366.64 |
August | 0.216752E+10 | 0.385235E+09 | 0.178229E+10 | 0.504041E+10 | 99821378.15 |
September | 0.230588E+10 | 0.676982E+09 | 0.162889E+10 | 0.466376E+10 | 0.332544E+09 |
October | 0.247991E+10 | 0.987447E+09 | 0.149247E+10 | 0.441616E+10 | 0.155713E+10 |
November | 0.217108E+10 | 0.925235E+09 | 0.124585E+10 | 0.312372E+10 | 0.274030E+10 |
December | 0.191976E+10 | 0.731997E+09 | 0.118776E+10 | 0.209199E+10 | 0.372984E+10 |
Annual Sum or Average | 0.303043E+11 | 0.111240E+11 | 0.191803E+11 | 0.568521E+11 | 0.180673E+11 |
Minimum of Months | 0.191976E+10 | 0.385235E+09 | 0.118776E+10 | 0.209199E+10 | 33108366.64 |
Maximum of Months | 0.346080E+10 | 0.162304E+10 | 0.194984E+10 | 0.788535E+10 | 0.379199E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.142003E+10 | 0.00 | 0.142003E+10 | 0.978856E+09 | 0.484501E+10 |
February | 0.152096E+10 | 0.00 | 0.152096E+10 | 0.153045E+10 | 0.354962E+10 |
March | 0.202913E+10 | 0.00 | 0.202913E+10 | 0.301183E+10 | 0.250761E+10 |
April | 0.213065E+10 | 7133183.15 | 0.212351E+10 | 0.514088E+10 | 0.874534E+09 |
May | 0.243900E+10 | 68054391.70 | 0.237094E+10 | 0.732854E+10 | 0.166923E+09 |
June | 0.244325E+10 | 90061487.09 | 0.235319E+10 | 0.768703E+10 | 0.122433E+09 |
July | 0.249021E+10 | 39259183.52 | 0.245096E+10 | 0.706833E+10 | 32212264.99 |
August | 0.228620E+10 | 7072660.31 | 0.227913E+10 | 0.597600E+10 | 0.111671E+09 |
September | 0.197140E+10 | 134731.39 | 0.197126E+10 | 0.450503E+10 | 0.370892E+09 |
October | 0.176480E+10 | 0.00 | 0.176480E+10 | 0.338731E+10 | 0.199337E+10 |
November | 0.144658E+10 | 0.00 | 0.144658E+10 | 0.186453E+10 | 0.348536E+10 |
December | 0.138527E+10 | 0.00 | 0.138527E+10 | 0.109171E+10 | 0.475635E+10 |
Annual Sum or Average | 0.233275E+11 | 0.211716E+09 | 0.231158E+11 | 0.495705E+11 | 0.228160E+11 |
Minimum of Months | 0.138527E+10 | 0.00 | 0.138527E+10 | 0.978856E+09 | 32212264.99 |
Maximum of Months | 0.249021E+10 | 90061487.09 | 0.245096E+10 | 0.768703E+10 | 0.484501E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202789E+10 | 0.813915E+09 | 0.121397E+10 | 0.205250E+10 | 0.305713E+10 |
February | 0.222525E+10 | 0.918655E+09 | 0.130660E+10 | 0.273160E+10 | 0.232835E+10 |
March | 0.300558E+10 | 0.124066E+10 | 0.176493E+10 | 0.460548E+10 | 0.169009E+10 |
April | 0.346049E+10 | 0.161350E+10 | 0.184699E+10 | 0.678920E+10 | 0.641236E+09 |
May | 0.351941E+10 | 0.156025E+10 | 0.195916E+10 | 0.804902E+10 | 0.130731E+09 |
June | 0.277191E+10 | 0.919641E+09 | 0.185227E+10 | 0.703053E+10 | 89904725.73 |
July | 0.240744E+10 | 0.508352E+09 | 0.189909E+10 | 0.596599E+10 | 20997419.01 |
August | 0.216923E+10 | 0.377493E+09 | 0.179174E+10 | 0.503271E+10 | 82151623.58 |
September | 0.224287E+10 | 0.625516E+09 | 0.161736E+10 | 0.452217E+10 | 0.279066E+09 |
October | 0.253510E+10 | 0.102397E+10 | 0.151113E+10 | 0.441622E+10 | 0.137451E+10 |
November | 0.217517E+10 | 0.933620E+09 | 0.124155E+10 | 0.298505E+10 | 0.231805E+10 |
December | 0.195990E+10 | 0.776476E+09 | 0.118343E+10 | 0.211436E+10 | 0.310048E+10 |
Annual Sum or Average | 0.305003E+11 | 0.113120E+11 | 0.191882E+11 | 0.562948E+11 | 0.151127E+11 |
Minimum of Months | 0.195990E+10 | 0.377493E+09 | 0.118343E+10 | 0.205250E+10 | 20997419.01 |
Maximum of Months | 0.351941E+10 | 0.161350E+10 | 0.195916E+10 | 0.804902E+10 | 0.310048E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.645997E+10 | 0.392591E+10 | 0.253407E+10 | 0.876106E+10 | 0.506981E+10 |
February | 0.554716E+10 | 0.308129E+10 | 0.246587E+10 | 0.786702E+10 | 0.388005E+10 |
March | 0.524939E+10 | 0.231792E+10 | 0.293146E+10 | 0.804210E+10 | 0.279476E+10 |
April | 0.356743E+10 | 0.100565E+10 | 0.256177E+10 | 0.687544E+10 | 0.100887E+10 |
May | 0.265058E+10 | 0.194717E+09 | 0.245586E+10 | 0.742895E+10 | 0.174336E+09 |
June | 0.234707E+10 | 39326016.30 | 0.230775E+10 | 0.749954E+10 | 0.125633E+09 |
July | 0.253021E+10 | 34395014.37 | 0.249582E+10 | 0.711806E+10 | 30063826.29 |
August | 0.268403E+10 | 0.142942E+09 | 0.254109E+10 | 0.650069E+10 | 0.121519E+09 |
September | 0.348202E+10 | 0.903301E+09 | 0.257872E+10 | 0.678217E+10 | 0.456672E+09 |
October | 0.619102E+10 | 0.345694E+10 | 0.273408E+10 | 0.107423E+11 | 0.232183E+10 |
November | 0.748585E+10 | 0.494870E+10 | 0.253715E+10 | 0.119080E+11 | 0.395746E+10 |
December | 0.690360E+10 | 0.432670E+10 | 0.257690E+10 | 0.979750E+10 | 0.514590E+10 |
Annual Sum or Average | 0.550983E+11 | 0.243778E+11 | 0.307205E+11 | 0.993229E+11 | 0.250869E+11 |
Minimum of Months | 0.234707E+10 | 34395014.37 | 0.230775E+10 | 0.650069E+10 | 30063826.29 |
Maximum of Months | 0.748585E+10 | 0.494870E+10 | 0.293146E+10 | 0.119080E+11 | 0.514590E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198397E+10 | 0.772036E+09 | 0.121193E+10 | 0.218532E+10 | 0.350413E+10 |
February | 0.204918E+10 | 0.755137E+09 | 0.129404E+10 | 0.261743E+10 | 0.262477E+10 |
March | 0.294219E+10 | 0.117617E+10 | 0.176602E+10 | 0.460497E+10 | 0.191457E+10 |
April | 0.346080E+10 | 0.162304E+10 | 0.183776E+10 | 0.679480E+10 | 0.762308E+09 |
May | 0.338607E+10 | 0.143623E+10 | 0.194984E+10 | 0.780876E+10 | 0.175986E+09 |
June | 0.307783E+10 | 0.119545E+10 | 0.188238E+10 | 0.750731E+10 | 0.114473E+09 |
July | 0.236007E+10 | 0.458998E+09 | 0.190108E+10 | 0.577190E+10 | 35275653.41 |
August | 0.216752E+10 | 0.385235E+09 | 0.178229E+10 | 0.497006E+10 | 0.107019E+09 |
September | 0.230588E+10 | 0.676982E+09 | 0.162889E+10 | 0.461645E+10 | 0.345422E+09 |
October | 0.247991E+10 | 0.987447E+09 | 0.149247E+10 | 0.439269E+10 | 0.153084E+10 |
November | 0.217108E+10 | 0.925235E+09 | 0.124585E+10 | 0.314977E+10 | 0.260493E+10 |
December | 0.191976E+10 | 0.731997E+09 | 0.118776E+10 | 0.216729E+10 | 0.346033E+10 |
Annual Sum or Average | 0.303043E+11 | 0.111240E+11 | 0.191803E+11 | 0.565867E+11 | 0.171800E+11 |
Minimum of Months | 0.191976E+10 | 0.385235E+09 | 0.118776E+10 | 0.216729E+10 | 35275653.41 |
Maximum of Months | 0.346080E+10 | 0.162304E+10 | 0.194984E+10 | 0.780876E+10 | 0.350413E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 224.54 | 2350.22 | 530.18 | 0.00 | 530.18 | 0.00 | 0.00 |
February | 515.71 | 1804.88 | 628.70 | 0.00 | 628.70 | 0.00 | 0.00 |
March | 1083.47 | 1045.14 | 757.59 | 0.00 | 757.59 | 0.00 | 0.00 |
April | 1963.75 | 353.53 | 822.01 | 2.75 | 819.26 | 0.00 | 0.00 |
May | 2759.95 | 54.80 | 910.62 | 25.41 | 885.21 | 0.00 | 0.00 |
June | 2991.22 | 40.83 | 942.62 | 34.75 | 907.87 | 0.00 | 0.00 |
July | 2659.60 | 8.86 | 929.74 | 14.66 | 915.09 | 0.00 | 0.00 |
August | 2226.25 | 35.13 | 853.57 | 2.64 | 850.93 | 0.00 | 0.00 |
September | 1752.21 | 134.08 | 760.57 | 0.05 | 760.52 | 0.00 | 0.00 |
October | 1240.48 | 794.58 | 658.90 | 0.00 | 658.90 | 0.00 | 0.00 |
November | 621.05 | 1608.88 | 558.10 | 0.00 | 558.10 | 0.00 | 0.00 |
December | 245.34 | 2318.13 | 517.20 | 0.00 | 517.20 | 0.00 | 0.00 |
Annual Sum or Average | 1528.54 | 875.26 | 739.71 | 6.71 | 733.00 | 0.00 | 0.00 |
Minimum of Months | 224.54 | 8.86 | 517.20 | 0.00 | 517.20 | 0.00 | 0.00 |
Maximum of Months | 2991.22 | 2350.22 | 942.62 | 34.75 | 915.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 651.74 | 1409.58 | 757.13 | 303.88 | 453.25 | 0.00 | 0.00 |
February | 1075.13 | 1097.74 | 919.83 | 379.74 | 540.10 | 0.00 | 0.00 |
March | 1726.98 | 647.05 | 1122.16 | 463.21 | 658.95 | 0.00 | 0.00 |
April | 2655.45 | 226.08 | 1335.07 | 622.50 | 712.58 | 0.00 | 0.00 |
May | 3052.69 | 38.80 | 1314.00 | 582.53 | 731.47 | 0.00 | 0.00 |
June | 2763.57 | 26.18 | 1069.42 | 354.80 | 714.61 | 0.00 | 0.00 |
July | 2279.62 | 4.26 | 898.84 | 189.80 | 709.04 | 0.00 | 0.00 |
August | 1924.45 | 17.38 | 809.90 | 140.94 | 668.96 | 0.00 | 0.00 |
September | 1775.25 | 88.81 | 865.31 | 241.33 | 623.98 | 0.00 | 0.00 |
October | 1659.94 | 510.43 | 946.50 | 382.31 | 564.19 | 0.00 | 0.00 |
November | 1114.93 | 985.02 | 839.19 | 360.19 | 479.00 | 0.00 | 0.00 |
December | 683.86 | 1384.48 | 731.75 | 289.90 | 441.84 | 0.00 | 0.00 |
Annual Sum or Average | 1782.84 | 533.95 | 967.16 | 358.70 | 608.46 | 0.00 | 0.00 |
Minimum of Months | 651.74 | 4.26 | 731.75 | 140.94 | 441.84 | 0.00 | 0.00 |
Maximum of Months | 3052.69 | 1409.58 | 1335.07 | 622.50 | 731.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3211.82 | 2146.57 | 2411.89 | 1465.77 | 946.12 | 0.00 | 0.00 |
February | 3234.03 | 1754.34 | 2292.98 | 1273.69 | 1019.29 | 0.00 | 0.00 |
March | 3013.93 | 1082.65 | 1959.90 | 865.42 | 1094.49 | 0.00 | 0.00 |
April | 2658.03 | 385.49 | 1376.33 | 387.99 | 988.34 | 0.00 | 0.00 |
May | 2793.46 | 57.42 | 989.62 | 72.70 | 916.92 | 0.00 | 0.00 |
June | 2915.99 | 41.47 | 905.51 | 15.17 | 890.34 | 0.00 | 0.00 |
July | 2677.26 | 8.40 | 944.68 | 12.84 | 931.84 | 0.00 | 0.00 |
August | 2433.81 | 37.19 | 1002.11 | 53.37 | 948.74 | 0.00 | 0.00 |
September | 2648.36 | 155.69 | 1343.38 | 348.50 | 994.88 | 0.00 | 0.00 |
October | 4040.46 | 861.86 | 2311.47 | 1290.68 | 1020.79 | 0.00 | 0.00 |
November | 4598.93 | 1618.58 | 2888.07 | 1909.23 | 978.84 | 0.00 | 0.00 |
December | 3593.30 | 2151.70 | 2577.52 | 1615.41 | 962.11 | 0.00 | 0.00 |
Annual Sum or Average | 3150.35 | 854.46 | 1747.16 | 773.02 | 974.14 | 0.00 | 0.00 |
Minimum of Months | 2433.81 | 8.40 | 905.51 | 12.84 | 890.34 | 0.00 | 0.00 |
Maximum of Months | 4598.93 | 2151.70 | 2888.07 | 1909.23 | 1094.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 724.01 | 1658.71 | 740.73 | 288.25 | 452.49 | 0.00 | 0.00 |
February | 1006.44 | 1345.08 | 847.05 | 312.14 | 534.91 | 0.00 | 0.00 |
March | 1678.79 | 848.44 | 1098.49 | 439.13 | 659.36 | 0.00 | 0.00 |
April | 2571.51 | 365.58 | 1335.19 | 626.17 | 709.02 | 0.00 | 0.00 |
May | 2908.47 | 72.49 | 1264.22 | 536.23 | 727.99 | 0.00 | 0.00 |
June | 2864.22 | 54.10 | 1187.44 | 461.21 | 726.23 | 0.00 | 0.00 |
July | 2092.66 | 26.33 | 881.15 | 171.37 | 709.78 | 0.00 | 0.00 |
August | 1765.74 | 80.70 | 809.26 | 143.83 | 665.43 | 0.00 | 0.00 |
September | 1771.59 | 154.19 | 889.62 | 261.18 | 628.43 | 0.00 | 0.00 |
October | 1611.65 | 649.80 | 925.90 | 368.67 | 557.23 | 0.00 | 0.00 |
November | 1143.54 | 1233.88 | 837.61 | 356.96 | 480.65 | 0.00 | 0.00 |
December | 680.80 | 1730.60 | 716.76 | 273.30 | 443.46 | 0.00 | 0.00 |
Annual Sum or Average | 1737.07 | 682.12 | 960.95 | 352.74 | 608.21 | 0.00 | 0.00 |
Minimum of Months | 680.80 | 26.33 | 716.76 | 143.83 | 443.46 | 0.00 | 0.00 |
Maximum of Months | 2908.47 | 1730.60 | 1335.19 | 626.17 | 727.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 321.97 | 1995.57 | 530.18 | 0.00 | 530.18 | 0.00 | 0.00 |
February | 599.14 | 1580.88 | 628.70 | 0.00 | 628.70 | 0.00 | 0.00 |
March | 1127.52 | 969.26 | 757.59 | 0.00 | 757.59 | 0.00 | 0.00 |
April | 2021.54 | 332.35 | 822.01 | 2.75 | 819.26 | 0.00 | 0.00 |
May | 2790.64 | 55.48 | 910.62 | 25.41 | 885.21 | 0.00 | 0.00 |
June | 3023.36 | 43.72 | 942.61 | 34.75 | 907.87 | 0.00 | 0.00 |
July | 2700.83 | 11.39 | 929.74 | 14.66 | 915.08 | 0.00 | 0.00 |
August | 2279.75 | 38.68 | 853.57 | 2.64 | 850.93 | 0.00 | 0.00 |
September | 1770.58 | 134.51 | 760.57 | 0.05 | 760.52 | 0.00 | 0.00 |
October | 1276.76 | 760.58 | 658.90 | 0.00 | 658.90 | 0.00 | 0.00 |
November | 690.64 | 1438.99 | 558.10 | 0.00 | 558.10 | 0.00 | 0.00 |
December | 353.81 | 1956.93 | 517.20 | 0.00 | 517.20 | 0.00 | 0.00 |
Annual Sum or Average | 1584.52 | 773.09 | 739.71 | 6.71 | 733.00 | 0.00 | 0.00 |
Minimum of Months | 321.97 | 11.39 | 517.20 | 0.00 | 517.20 | 0.00 | 0.00 |
Maximum of Months | 3023.36 | 1995.57 | 942.61 | 34.75 | 915.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 704.28 | 1258.66 | 757.13 | 303.88 | 453.25 | 0.00 | 0.00 |
February | 1092.39 | 1026.96 | 919.83 | 379.74 | 540.09 | 0.00 | 0.00 |
March | 1714.12 | 647.43 | 1122.16 | 463.21 | 658.95 | 0.00 | 0.00 |
April | 2633.91 | 244.28 | 1335.07 | 622.49 | 712.57 | 0.00 | 0.00 |
May | 3030.38 | 44.57 | 1314.00 | 582.53 | 731.47 | 0.00 | 0.00 |
June | 2739.19 | 32.66 | 1069.41 | 354.80 | 714.61 | 0.00 | 0.00 |
July | 2256.94 | 7.61 | 898.83 | 189.80 | 709.04 | 0.00 | 0.00 |
August | 1900.13 | 28.81 | 809.90 | 140.94 | 668.96 | 0.00 | 0.00 |
September | 1756.48 | 102.79 | 865.31 | 241.33 | 623.98 | 0.00 | 0.00 |
October | 1648.06 | 521.63 | 946.50 | 382.31 | 564.19 | 0.00 | 0.00 |
November | 1124.57 | 944.22 | 839.19 | 360.19 | 478.99 | 0.00 | 0.00 |
December | 727.22 | 1266.60 | 731.74 | 289.90 | 441.84 | 0.00 | 0.00 |
Annual Sum or Average | 1779.80 | 508.24 | 967.16 | 358.70 | 608.45 | 0.00 | 0.00 |
Minimum of Months | 704.28 | 7.61 | 731.74 | 140.94 | 441.84 | 0.00 | 0.00 |
Maximum of Months | 3030.38 | 1266.60 | 1335.07 | 622.49 | 731.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3212.16 | 2062.63 | 2411.88 | 1465.77 | 946.11 | 0.00 | 0.00 |
February | 3223.81 | 1701.56 | 2292.97 | 1273.68 | 1019.29 | 0.00 | 0.00 |
March | 3009.24 | 1072.00 | 1959.90 | 865.41 | 1094.48 | 0.00 | 0.00 |
April | 2684.46 | 383.40 | 1376.32 | 387.98 | 988.34 | 0.00 | 0.00 |
May | 2823.06 | 58.13 | 989.61 | 72.70 | 916.91 | 0.00 | 0.00 |
June | 2947.56 | 44.54 | 905.51 | 15.17 | 890.34 | 0.00 | 0.00 |
July | 2715.97 | 10.65 | 944.67 | 12.84 | 931.83 | 0.00 | 0.00 |
August | 2471.53 | 42.09 | 1002.10 | 53.37 | 948.73 | 0.00 | 0.00 |
September | 2644.87 | 167.48 | 1343.37 | 348.50 | 994.88 | 0.00 | 0.00 |
October | 4021.61 | 880.63 | 2311.46 | 1290.67 | 1020.79 | 0.00 | 0.00 |
November | 4577.67 | 1599.82 | 2888.06 | 1909.22 | 978.84 | 0.00 | 0.00 |
December | 3599.45 | 2069.57 | 2577.51 | 1615.41 | 962.10 | 0.00 | 0.00 |
Annual Sum or Average | 3159.86 | 837.17 | 1747.16 | 773.01 | 974.14 | 0.00 | 0.00 |
Minimum of Months | 2471.53 | 10.65 | 905.51 | 12.84 | 890.34 | 0.00 | 0.00 |
Maximum of Months | 4577.67 | 2069.57 | 2888.06 | 1909.22 | 1094.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 792.11 | 1415.77 | 740.73 | 288.25 | 452.48 | 0.00 | 0.00 |
February | 1068.07 | 1149.86 | 847.05 | 312.14 | 534.91 | 0.00 | 0.00 |
March | 1726.30 | 734.91 | 1098.49 | 439.13 | 659.36 | 0.00 | 0.00 |
April | 2643.28 | 292.26 | 1335.19 | 626.17 | 709.01 | 0.00 | 0.00 |
May | 2944.05 | 61.78 | 1264.21 | 536.23 | 727.99 | 0.00 | 0.00 |
June | 2927.89 | 42.22 | 1187.44 | 461.21 | 726.23 | 0.00 | 0.00 |
July | 2188.24 | 12.36 | 881.15 | 171.37 | 709.78 | 0.00 | 0.00 |
August | 1881.87 | 37.27 | 809.26 | 143.83 | 665.43 | 0.00 | 0.00 |
September | 1799.29 | 128.30 | 889.61 | 261.18 | 628.43 | 0.00 | 0.00 |
October | 1648.81 | 581.37 | 925.89 | 368.67 | 557.22 | 0.00 | 0.00 |
November | 1205.14 | 1057.21 | 837.61 | 356.96 | 480.65 | 0.00 | 0.00 |
December | 781.06 | 1392.56 | 716.75 | 273.30 | 443.46 | 0.00 | 0.00 |
Annual Sum or Average | 1802.77 | 572.91 | 960.94 | 352.74 | 608.20 | 0.00 | 0.00 |
Minimum of Months | 781.06 | 12.36 | 716.75 | 143.83 | 443.46 | 0.00 | 0.00 |
Maximum of Months | 2944.05 | 1415.77 | 1335.19 | 626.17 | 727.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.46 | 1808.92 | 530.18 | 0.00 | 530.18 | 0.00 | 0.00 |
February | 632.63 | 1467.27 | 628.70 | 0.00 | 628.70 | 0.00 | 0.00 |
March | 1124.49 | 936.24 | 757.59 | 0.00 | 757.59 | 0.00 | 0.00 |
April | 1983.36 | 337.40 | 822.01 | 2.75 | 819.26 | 0.00 | 0.00 |
May | 2736.16 | 62.32 | 910.62 | 25.41 | 885.21 | 0.00 | 0.00 |
June | 2965.67 | 47.23 | 942.61 | 34.75 | 907.87 | 0.00 | 0.00 |
July | 2639.01 | 12.03 | 929.74 | 14.66 | 915.08 | 0.00 | 0.00 |
August | 2231.18 | 41.69 | 853.57 | 2.64 | 850.93 | 0.00 | 0.00 |
September | 1738.05 | 143.09 | 760.57 | 0.05 | 760.52 | 0.00 | 0.00 |
October | 1264.68 | 744.24 | 658.90 | 0.00 | 658.90 | 0.00 | 0.00 |
November | 719.34 | 1344.66 | 558.10 | 0.00 | 558.10 | 0.00 | 0.00 |
December | 407.60 | 1775.82 | 517.20 | 0.00 | 517.20 | 0.00 | 0.00 |
Annual Sum or Average | 1571.87 | 723.49 | 739.71 | 6.71 | 733.00 | 0.00 | 0.00 |
Minimum of Months | 365.46 | 12.03 | 517.20 | 0.00 | 517.20 | 0.00 | 0.00 |
Maximum of Months | 2965.67 | 1808.92 | 942.61 | 34.75 | 915.08 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 766.32 | 1141.40 | 757.13 | 303.88 | 453.25 | 0.00 | 0.00 |
February | 1129.13 | 962.45 | 919.83 | 379.74 | 540.09 | 0.00 | 0.00 |
March | 1719.49 | 631.01 | 1122.16 | 463.21 | 658.95 | 0.00 | 0.00 |
April | 2619.29 | 247.39 | 1335.07 | 622.49 | 712.57 | 0.00 | 0.00 |
May | 3005.16 | 48.81 | 1314.00 | 582.53 | 731.47 | 0.00 | 0.00 |
June | 2712.40 | 34.69 | 1069.41 | 354.80 | 714.61 | 0.00 | 0.00 |
July | 2227.45 | 7.84 | 898.83 | 189.80 | 709.04 | 0.00 | 0.00 |
August | 1879.00 | 30.67 | 809.90 | 140.94 | 668.96 | 0.00 | 0.00 |
September | 1744.66 | 107.66 | 865.31 | 241.33 | 623.98 | 0.00 | 0.00 |
October | 1648.83 | 513.18 | 946.50 | 382.31 | 564.19 | 0.00 | 0.00 |
November | 1151.64 | 894.31 | 839.19 | 360.19 | 478.99 | 0.00 | 0.00 |
December | 789.41 | 1157.58 | 731.74 | 289.90 | 441.84 | 0.00 | 0.00 |
Annual Sum or Average | 1785.10 | 479.22 | 967.16 | 358.70 | 608.45 | 0.00 | 0.00 |
Minimum of Months | 766.32 | 7.84 | 731.74 | 140.94 | 441.84 | 0.00 | 0.00 |
Maximum of Months | 3005.16 | 1157.58 | 1335.07 | 622.49 | 731.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3271.00 | 1892.85 | 2411.88 | 1465.77 | 946.11 | 0.00 | 0.00 |
February | 3251.91 | 1603.86 | 2292.97 | 1273.68 | 1019.29 | 0.00 | 0.00 |
March | 3002.57 | 1043.44 | 1959.90 | 865.41 | 1094.48 | 0.00 | 0.00 |
April | 2652.56 | 389.23 | 1376.32 | 387.98 | 988.34 | 0.00 | 0.00 |
May | 2773.65 | 65.09 | 989.61 | 72.70 | 916.91 | 0.00 | 0.00 |
June | 2893.34 | 48.47 | 905.51 | 15.17 | 890.34 | 0.00 | 0.00 |
July | 2657.58 | 11.22 | 944.67 | 12.84 | 931.83 | 0.00 | 0.00 |
August | 2427.08 | 45.37 | 1002.10 | 53.37 | 948.73 | 0.00 | 0.00 |
September | 2616.58 | 176.19 | 1343.37 | 348.50 | 994.88 | 0.00 | 0.00 |
October | 4010.71 | 866.87 | 2311.46 | 1290.67 | 1020.79 | 0.00 | 0.00 |
November | 4594.15 | 1526.80 | 2888.06 | 1909.22 | 978.84 | 0.00 | 0.00 |
December | 3657.97 | 1921.26 | 2577.51 | 1615.41 | 962.10 | 0.00 | 0.00 |
Annual Sum or Average | 3149.51 | 795.50 | 1747.16 | 773.01 | 974.14 | 0.00 | 0.00 |
Minimum of Months | 2427.08 | 11.22 | 905.51 | 12.84 | 890.34 | 0.00 | 0.00 |
Maximum of Months | 4594.15 | 1921.26 | 2888.06 | 1909.22 | 1094.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 815.91 | 1308.29 | 740.73 | 288.25 | 452.48 | 0.00 | 0.00 |
February | 1081.94 | 1084.97 | 847.05 | 312.14 | 534.91 | 0.00 | 0.00 |
March | 1719.30 | 714.82 | 1098.49 | 439.13 | 659.36 | 0.00 | 0.00 |
April | 2621.45 | 294.10 | 1335.19 | 626.17 | 709.01 | 0.00 | 0.00 |
May | 2915.46 | 65.71 | 1264.21 | 536.23 | 727.99 | 0.00 | 0.00 |
June | 2896.34 | 44.16 | 1187.44 | 461.21 | 726.23 | 0.00 | 0.00 |
July | 2154.98 | 13.17 | 881.15 | 171.37 | 709.78 | 0.00 | 0.00 |
August | 1855.61 | 39.96 | 809.26 | 143.83 | 665.43 | 0.00 | 0.00 |
September | 1781.04 | 133.26 | 889.61 | 261.18 | 628.43 | 0.00 | 0.00 |
October | 1640.04 | 571.55 | 925.89 | 368.67 | 557.22 | 0.00 | 0.00 |
November | 1215.19 | 1004.99 | 837.61 | 356.96 | 480.65 | 0.00 | 0.00 |
December | 809.17 | 1291.94 | 716.75 | 273.30 | 443.46 | 0.00 | 0.00 |
Annual Sum or Average | 1794.35 | 544.78 | 960.94 | 352.74 | 608.20 | 0.00 | 0.00 |
Minimum of Months | 809.17 | 13.17 | 716.75 | 143.83 | 443.46 | 0.00 | 0.00 |
Maximum of Months | 2915.46 | 1308.29 | 1335.19 | 626.17 | 727.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.601408E+09 | 0.629483E+10 | 0.142004E+10 | 0.00 | 0.142004E+10 | 0.00 | 0.00 |
February | 0.124761E+10 | 0.436638E+10 | 0.152096E+10 | 0.00 | 0.152096E+10 | 0.00 | 0.00 |
March | 0.290197E+10 | 0.279930E+10 | 0.202913E+10 | 0.00 | 0.202913E+10 | 0.00 | 0.00 |
April | 0.509004E+10 | 0.916340E+09 | 0.213065E+10 | 7133208.48 | 0.212352E+10 | 0.00 | 0.00 |
May | 0.739226E+10 | 0.146767E+09 | 0.243901E+10 | 68054633.37 | 0.237095E+10 | 0.00 | 0.00 |
June | 0.775323E+10 | 0.105822E+09 | 0.244326E+10 | 90061806.90 | 0.235320E+10 | 0.00 | 0.00 |
July | 0.712347E+10 | 23742591.90 | 0.249022E+10 | 39259322.93 | 0.245096E+10 | 0.00 | 0.00 |
August | 0.596280E+10 | 94084444.33 | 0.228621E+10 | 7072685.43 | 0.227914E+10 | 0.00 | 0.00 |
September | 0.454172E+10 | 0.347532E+09 | 0.197141E+10 | 134731.86 | 0.197127E+10 | 0.00 | 0.00 |
October | 0.332251E+10 | 0.212820E+10 | 0.176481E+10 | 0.00 | 0.176481E+10 | 0.00 | 0.00 |
November | 0.160976E+10 | 0.417021E+10 | 0.144659E+10 | 0.00 | 0.144659E+10 | 0.00 | 0.00 |
December | 0.657113E+09 | 0.620887E+10 | 0.138527E+10 | 0.00 | 0.138527E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.482039E+11 | 0.276021E+11 | 0.233276E+11 | 0.211716E+09 | 0.231159E+11 | 0.00 | 0.00 |
Minimum of Months | 0.601408E+09 | 23742591.90 | 0.138527E+10 | 0.00 | 0.138527E+10 | 0.00 | 0.00 |
Maximum of Months | 0.775323E+10 | 0.629483E+10 | 0.249022E+10 | 90061806.90 | 0.245096E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.174563E+10 | 0.377541E+10 | 0.202790E+10 | 0.813918E+09 | 0.121398E+10 | 0.00 | 0.00 |
February | 0.260096E+10 | 0.265566E+10 | 0.222526E+10 | 0.918659E+09 | 0.130660E+10 | 0.00 | 0.00 |
March | 0.462553E+10 | 0.173307E+10 | 0.300560E+10 | 0.124066E+10 | 0.176494E+10 | 0.00 | 0.00 |
April | 0.688292E+10 | 0.585990E+09 | 0.346051E+10 | 0.161351E+10 | 0.184700E+10 | 0.00 | 0.00 |
May | 0.817632E+10 | 0.103923E+09 | 0.351943E+10 | 0.156026E+10 | 0.195917E+10 | 0.00 | 0.00 |
June | 0.716318E+10 | 67852252.45 | 0.277193E+10 | 0.919645E+09 | 0.185228E+10 | 0.00 | 0.00 |
July | 0.610575E+10 | 11414451.06 | 0.240745E+10 | 0.508354E+09 | 0.189909E+10 | 0.00 | 0.00 |
August | 0.515444E+10 | 46552089.84 | 0.216924E+10 | 0.377494E+09 | 0.179175E+10 | 0.00 | 0.00 |
September | 0.460144E+10 | 0.230198E+09 | 0.224288E+10 | 0.625518E+09 | 0.161736E+10 | 0.00 | 0.00 |
October | 0.444599E+10 | 0.136713E+10 | 0.253511E+10 | 0.102397E+10 | 0.151113E+10 | 0.00 | 0.00 |
November | 0.288989E+10 | 0.255317E+10 | 0.217518E+10 | 0.933624E+09 | 0.124156E+10 | 0.00 | 0.00 |
December | 0.183164E+10 | 0.370818E+10 | 0.195991E+10 | 0.776480E+09 | 0.118343E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.562237E+11 | 0.168386E+11 | 0.305004E+11 | 0.113121E+11 | 0.191883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.174563E+10 | 11414451.06 | 0.195991E+10 | 0.377494E+09 | 0.118343E+10 | 0.00 | 0.00 |
Maximum of Months | 0.817632E+10 | 0.377541E+10 | 0.351943E+10 | 0.161351E+10 | 0.195917E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.860255E+10 | 0.574937E+10 | 0.646000E+10 | 0.392592E+10 | 0.253408E+10 | 0.00 | 0.00 |
February | 0.782377E+10 | 0.424409E+10 | 0.554718E+10 | 0.308130E+10 | 0.246588E+10 | 0.00 | 0.00 |
March | 0.807251E+10 | 0.289977E+10 | 0.524940E+10 | 0.231793E+10 | 0.293147E+10 | 0.00 | 0.00 |
April | 0.688961E+10 | 0.999187E+09 | 0.356744E+10 | 0.100566E+10 | 0.256178E+10 | 0.00 | 0.00 |
May | 0.748201E+10 | 0.153781E+09 | 0.265059E+10 | 0.194718E+09 | 0.245587E+10 | 0.00 | 0.00 |
June | 0.755825E+10 | 0.107478E+09 | 0.234708E+10 | 39326155.95 | 0.230776E+10 | 0.00 | 0.00 |
July | 0.717078E+10 | 22494307.02 | 0.253022E+10 | 34395136.51 | 0.249583E+10 | 0.00 | 0.00 |
August | 0.651871E+10 | 99596423.04 | 0.268404E+10 | 0.142943E+09 | 0.254110E+10 | 0.00 | 0.00 |
September | 0.686455E+10 | 0.403544E+09 | 0.348203E+10 | 0.903304E+09 | 0.257873E+10 | 0.00 | 0.00 |
October | 0.108220E+11 | 0.230842E+10 | 0.619104E+10 | 0.345695E+10 | 0.273409E+10 | 0.00 | 0.00 |
November | 0.119204E+11 | 0.419536E+10 | 0.748587E+10 | 0.494872E+10 | 0.253715E+10 | 0.00 | 0.00 |
December | 0.962430E+10 | 0.576312E+10 | 0.690362E+10 | 0.432672E+10 | 0.257691E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.993494E+11 | 0.269462E+11 | 0.550985E+11 | 0.243779E+11 | 0.307206E+11 | 0.00 | 0.00 |
Minimum of Months | 0.651871E+10 | 22494307.02 | 0.234708E+10 | 34395136.51 | 0.230776E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119204E+11 | 0.576312E+10 | 0.748587E+10 | 0.494872E+10 | 0.293147E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193918E+10 | 0.444270E+10 | 0.198398E+10 | 0.772039E+09 | 0.121194E+10 | 0.00 | 0.00 |
February | 0.243479E+10 | 0.325403E+10 | 0.204919E+10 | 0.755140E+09 | 0.129405E+10 | 0.00 | 0.00 |
March | 0.449646E+10 | 0.227247E+10 | 0.294220E+10 | 0.117617E+10 | 0.176603E+10 | 0.00 | 0.00 |
April | 0.666536E+10 | 0.947579E+09 | 0.346082E+10 | 0.162304E+10 | 0.183777E+10 | 0.00 | 0.00 |
May | 0.779003E+10 | 0.194161E+09 | 0.338609E+10 | 0.143624E+10 | 0.194984E+10 | 0.00 | 0.00 |
June | 0.742405E+10 | 0.140239E+09 | 0.307785E+10 | 0.119546E+10 | 0.188239E+10 | 0.00 | 0.00 |
July | 0.560499E+10 | 70513223.08 | 0.236008E+10 | 0.459000E+09 | 0.190108E+10 | 0.00 | 0.00 |
August | 0.472935E+10 | 0.216145E+09 | 0.216753E+10 | 0.385236E+09 | 0.178230E+10 | 0.00 | 0.00 |
September | 0.459197E+10 | 0.399664E+09 | 0.230589E+10 | 0.676985E+09 | 0.162890E+10 | 0.00 | 0.00 |
October | 0.431664E+10 | 0.174043E+10 | 0.247992E+10 | 0.987451E+09 | 0.149247E+10 | 0.00 | 0.00 |
November | 0.296407E+10 | 0.319822E+10 | 0.217109E+10 | 0.925239E+09 | 0.124585E+10 | 0.00 | 0.00 |
December | 0.182346E+10 | 0.463525E+10 | 0.191976E+10 | 0.732000E+09 | 0.118776E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.547803E+11 | 0.215114E+11 | 0.303044E+11 | 0.111240E+11 | 0.191804E+11 | 0.00 | 0.00 |
Minimum of Months | 0.182346E+10 | 70513223.08 | 0.191976E+10 | 0.385236E+09 | 0.118776E+10 | 0.00 | 0.00 |
Maximum of Months | 0.779003E+10 | 0.463525E+10 | 0.346082E+10 | 0.162304E+10 | 0.194984E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.862371E+09 | 0.534495E+10 | 0.142003E+10 | 0.00 | 0.142003E+10 | 0.00 | 0.00 |
February | 0.144944E+10 | 0.382447E+10 | 0.152096E+10 | 0.00 | 0.152096E+10 | 0.00 | 0.00 |
March | 0.301995E+10 | 0.259607E+10 | 0.202913E+10 | 0.00 | 0.202913E+10 | 0.00 | 0.00 |
April | 0.523984E+10 | 0.861460E+09 | 0.213065E+10 | 7133183.15 | 0.212351E+10 | 0.00 | 0.00 |
May | 0.747446E+10 | 0.148605E+09 | 0.243900E+10 | 68054391.70 | 0.237094E+10 | 0.00 | 0.00 |
June | 0.783656E+10 | 0.113310E+09 | 0.244325E+10 | 90061487.09 | 0.235319E+10 | 0.00 | 0.00 |
July | 0.723390E+10 | 30499989.17 | 0.249021E+10 | 39259183.52 | 0.245096E+10 | 0.00 | 0.00 |
August | 0.610609E+10 | 0.103595E+09 | 0.228620E+10 | 7072660.31 | 0.227913E+10 | 0.00 | 0.00 |
September | 0.458934E+10 | 0.348641E+09 | 0.197140E+10 | 134731.39 | 0.197126E+10 | 0.00 | 0.00 |
October | 0.341967E+10 | 0.203715E+10 | 0.176480E+10 | 0.00 | 0.176480E+10 | 0.00 | 0.00 |
November | 0.179014E+10 | 0.372986E+10 | 0.144658E+10 | 0.00 | 0.144658E+10 | 0.00 | 0.00 |
December | 0.947637E+09 | 0.524143E+10 | 0.138527E+10 | 0.00 | 0.138527E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.499694E+11 | 0.243800E+11 | 0.233275E+11 | 0.211716E+09 | 0.231158E+11 | 0.00 | 0.00 |
Minimum of Months | 0.862371E+09 | 30499989.17 | 0.138527E+10 | 0.00 | 0.138527E+10 | 0.00 | 0.00 |
Maximum of Months | 0.783656E+10 | 0.534495E+10 | 0.249021E+10 | 90061487.09 | 0.245096E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.188634E+10 | 0.337120E+10 | 0.202789E+10 | 0.813915E+09 | 0.121397E+10 | 0.00 | 0.00 |
February | 0.264272E+10 | 0.248442E+10 | 0.222525E+10 | 0.918655E+09 | 0.130660E+10 | 0.00 | 0.00 |
March | 0.459111E+10 | 0.173409E+10 | 0.300558E+10 | 0.124066E+10 | 0.176493E+10 | 0.00 | 0.00 |
April | 0.682709E+10 | 0.633177E+09 | 0.346049E+10 | 0.161350E+10 | 0.184699E+10 | 0.00 | 0.00 |
May | 0.811658E+10 | 0.119368E+09 | 0.351941E+10 | 0.156025E+10 | 0.195916E+10 | 0.00 | 0.00 |
June | 0.709998E+10 | 84645281.48 | 0.277191E+10 | 0.919641E+09 | 0.185227E+10 | 0.00 | 0.00 |
July | 0.604499E+10 | 20369368.18 | 0.240744E+10 | 0.508352E+09 | 0.189909E+10 | 0.00 | 0.00 |
August | 0.508931E+10 | 77169590.09 | 0.216923E+10 | 0.377493E+09 | 0.179174E+10 | 0.00 | 0.00 |
September | 0.455279E+10 | 0.266433E+09 | 0.224287E+10 | 0.625516E+09 | 0.161736E+10 | 0.00 | 0.00 |
October | 0.441415E+10 | 0.139714E+10 | 0.253510E+10 | 0.102397E+10 | 0.151113E+10 | 0.00 | 0.00 |
November | 0.291488E+10 | 0.244743E+10 | 0.217517E+10 | 0.933620E+09 | 0.124155E+10 | 0.00 | 0.00 |
December | 0.194777E+10 | 0.339246E+10 | 0.195990E+10 | 0.776476E+09 | 0.118343E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.561277E+11 | 0.160279E+11 | 0.305003E+11 | 0.113120E+11 | 0.191882E+11 | 0.00 | 0.00 |
Minimum of Months | 0.188634E+10 | 20369368.18 | 0.195990E+10 | 0.377493E+09 | 0.118343E+10 | 0.00 | 0.00 |
Maximum of Months | 0.811658E+10 | 0.339246E+10 | 0.351941E+10 | 0.161350E+10 | 0.195916E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.860346E+10 | 0.552454E+10 | 0.645997E+10 | 0.392591E+10 | 0.253407E+10 | 0.00 | 0.00 |
February | 0.779903E+10 | 0.411641E+10 | 0.554716E+10 | 0.308129E+10 | 0.246587E+10 | 0.00 | 0.00 |
March | 0.805995E+10 | 0.287125E+10 | 0.524939E+10 | 0.231792E+10 | 0.293146E+10 | 0.00 | 0.00 |
April | 0.695812E+10 | 0.993784E+09 | 0.356743E+10 | 0.100565E+10 | 0.256177E+10 | 0.00 | 0.00 |
May | 0.756129E+10 | 0.155695E+09 | 0.265058E+10 | 0.194717E+09 | 0.245586E+10 | 0.00 | 0.00 |
June | 0.764009E+10 | 0.115444E+09 | 0.234707E+10 | 39326016.30 | 0.230775E+10 | 0.00 | 0.00 |
July | 0.727446E+10 | 28522860.43 | 0.253021E+10 | 34395014.37 | 0.249582E+10 | 0.00 | 0.00 |
August | 0.661975E+10 | 0.112737E+09 | 0.268403E+10 | 0.142942E+09 | 0.254109E+10 | 0.00 | 0.00 |
September | 0.685549E+10 | 0.434115E+09 | 0.348202E+10 | 0.903301E+09 | 0.257872E+10 | 0.00 | 0.00 |
October | 0.107715E+11 | 0.235868E+10 | 0.619102E+10 | 0.345694E+10 | 0.273408E+10 | 0.00 | 0.00 |
November | 0.118653E+11 | 0.414675E+10 | 0.748585E+10 | 0.494870E+10 | 0.253715E+10 | 0.00 | 0.00 |
December | 0.964077E+10 | 0.554314E+10 | 0.690360E+10 | 0.432670E+10 | 0.257690E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.996492E+11 | 0.264011E+11 | 0.550983E+11 | 0.243778E+11 | 0.307205E+11 | 0.00 | 0.00 |
Minimum of Months | 0.661975E+10 | 28522860.43 | 0.234707E+10 | 34395014.37 | 0.230775E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118653E+11 | 0.554314E+10 | 0.748585E+10 | 0.494870E+10 | 0.293146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.212160E+10 | 0.379199E+10 | 0.198397E+10 | 0.772036E+09 | 0.121193E+10 | 0.00 | 0.00 |
February | 0.258388E+10 | 0.278174E+10 | 0.204918E+10 | 0.755137E+09 | 0.129404E+10 | 0.00 | 0.00 |
March | 0.462373E+10 | 0.196838E+10 | 0.294219E+10 | 0.117617E+10 | 0.176602E+10 | 0.00 | 0.00 |
April | 0.685137E+10 | 0.757548E+09 | 0.346080E+10 | 0.162304E+10 | 0.183776E+10 | 0.00 | 0.00 |
May | 0.788535E+10 | 0.165458E+09 | 0.338607E+10 | 0.143623E+10 | 0.194984E+10 | 0.00 | 0.00 |
June | 0.758910E+10 | 0.109437E+09 | 0.307783E+10 | 0.119545E+10 | 0.188238E+10 | 0.00 | 0.00 |
July | 0.586097E+10 | 33108366.64 | 0.236007E+10 | 0.458998E+09 | 0.190108E+10 | 0.00 | 0.00 |
August | 0.504041E+10 | 99821378.15 | 0.216752E+10 | 0.385235E+09 | 0.178229E+10 | 0.00 | 0.00 |
September | 0.466376E+10 | 0.332544E+09 | 0.230588E+10 | 0.676982E+09 | 0.162889E+10 | 0.00 | 0.00 |
October | 0.441616E+10 | 0.155713E+10 | 0.247991E+10 | 0.987447E+09 | 0.149247E+10 | 0.00 | 0.00 |
November | 0.312372E+10 | 0.274030E+10 | 0.217108E+10 | 0.925235E+09 | 0.124585E+10 | 0.00 | 0.00 |
December | 0.209199E+10 | 0.372984E+10 | 0.191976E+10 | 0.731997E+09 | 0.118776E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.568521E+11 | 0.180673E+11 | 0.303043E+11 | 0.111240E+11 | 0.191803E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209199E+10 | 33108366.64 | 0.191976E+10 | 0.385235E+09 | 0.118776E+10 | 0.00 | 0.00 |
Maximum of Months | 0.788535E+10 | 0.379199E+10 | 0.346080E+10 | 0.162304E+10 | 0.194984E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.978856E+09 | 0.484501E+10 | 0.142003E+10 | 0.00 | 0.142003E+10 | 0.00 | 0.00 |
February | 0.153045E+10 | 0.354962E+10 | 0.152096E+10 | 0.00 | 0.152096E+10 | 0.00 | 0.00 |
March | 0.301183E+10 | 0.250761E+10 | 0.202913E+10 | 0.00 | 0.202913E+10 | 0.00 | 0.00 |
April | 0.514088E+10 | 0.874534E+09 | 0.213065E+10 | 7133183.15 | 0.212351E+10 | 0.00 | 0.00 |
May | 0.732854E+10 | 0.166923E+09 | 0.243900E+10 | 68054391.70 | 0.237094E+10 | 0.00 | 0.00 |
June | 0.768703E+10 | 0.122433E+09 | 0.244325E+10 | 90061487.09 | 0.235319E+10 | 0.00 | 0.00 |
July | 0.706833E+10 | 32212264.99 | 0.249021E+10 | 39259183.52 | 0.245096E+10 | 0.00 | 0.00 |
August | 0.597600E+10 | 0.111671E+09 | 0.228620E+10 | 7072660.31 | 0.227913E+10 | 0.00 | 0.00 |
September | 0.450503E+10 | 0.370892E+09 | 0.197140E+10 | 134731.39 | 0.197126E+10 | 0.00 | 0.00 |
October | 0.338731E+10 | 0.199337E+10 | 0.176480E+10 | 0.00 | 0.176480E+10 | 0.00 | 0.00 |
November | 0.186453E+10 | 0.348536E+10 | 0.144658E+10 | 0.00 | 0.144658E+10 | 0.00 | 0.00 |
December | 0.109171E+10 | 0.475635E+10 | 0.138527E+10 | 0.00 | 0.138527E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.495705E+11 | 0.228160E+11 | 0.233275E+11 | 0.211716E+09 | 0.231158E+11 | 0.00 | 0.00 |
Minimum of Months | 0.978856E+09 | 32212264.99 | 0.138527E+10 | 0.00 | 0.138527E+10 | 0.00 | 0.00 |
Maximum of Months | 0.768703E+10 | 0.484501E+10 | 0.249021E+10 | 90061487.09 | 0.245096E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205250E+10 | 0.305713E+10 | 0.202789E+10 | 0.813915E+09 | 0.121397E+10 | 0.00 | 0.00 |
February | 0.273160E+10 | 0.232835E+10 | 0.222525E+10 | 0.918655E+09 | 0.130660E+10 | 0.00 | 0.00 |
March | 0.460548E+10 | 0.169009E+10 | 0.300558E+10 | 0.124066E+10 | 0.176493E+10 | 0.00 | 0.00 |
April | 0.678920E+10 | 0.641236E+09 | 0.346049E+10 | 0.161350E+10 | 0.184699E+10 | 0.00 | 0.00 |
May | 0.804902E+10 | 0.130731E+09 | 0.351941E+10 | 0.156025E+10 | 0.195916E+10 | 0.00 | 0.00 |
June | 0.703053E+10 | 89904725.73 | 0.277191E+10 | 0.919641E+09 | 0.185227E+10 | 0.00 | 0.00 |
July | 0.596599E+10 | 20997419.01 | 0.240744E+10 | 0.508352E+09 | 0.189909E+10 | 0.00 | 0.00 |
August | 0.503271E+10 | 82151623.58 | 0.216923E+10 | 0.377493E+09 | 0.179174E+10 | 0.00 | 0.00 |
September | 0.452217E+10 | 0.279066E+09 | 0.224287E+10 | 0.625516E+09 | 0.161736E+10 | 0.00 | 0.00 |
October | 0.441622E+10 | 0.137451E+10 | 0.253510E+10 | 0.102397E+10 | 0.151113E+10 | 0.00 | 0.00 |
November | 0.298505E+10 | 0.231805E+10 | 0.217517E+10 | 0.933620E+09 | 0.124155E+10 | 0.00 | 0.00 |
December | 0.211436E+10 | 0.310048E+10 | 0.195990E+10 | 0.776476E+09 | 0.118343E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.562948E+11 | 0.151127E+11 | 0.305003E+11 | 0.113120E+11 | 0.191882E+11 | 0.00 | 0.00 |
Minimum of Months | 0.205250E+10 | 20997419.01 | 0.195990E+10 | 0.377493E+09 | 0.118343E+10 | 0.00 | 0.00 |
Maximum of Months | 0.804902E+10 | 0.310048E+10 | 0.351941E+10 | 0.161350E+10 | 0.195916E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.876106E+10 | 0.506981E+10 | 0.645997E+10 | 0.392591E+10 | 0.253407E+10 | 0.00 | 0.00 |
February | 0.786702E+10 | 0.388005E+10 | 0.554716E+10 | 0.308129E+10 | 0.246587E+10 | 0.00 | 0.00 |
March | 0.804210E+10 | 0.279476E+10 | 0.524939E+10 | 0.231792E+10 | 0.293146E+10 | 0.00 | 0.00 |
April | 0.687544E+10 | 0.100887E+10 | 0.356743E+10 | 0.100565E+10 | 0.256177E+10 | 0.00 | 0.00 |
May | 0.742895E+10 | 0.174336E+09 | 0.265058E+10 | 0.194717E+09 | 0.245586E+10 | 0.00 | 0.00 |
June | 0.749954E+10 | 0.125633E+09 | 0.234707E+10 | 39326016.30 | 0.230775E+10 | 0.00 | 0.00 |
July | 0.711806E+10 | 30063826.29 | 0.253021E+10 | 34395014.37 | 0.249582E+10 | 0.00 | 0.00 |
August | 0.650069E+10 | 0.121519E+09 | 0.268403E+10 | 0.142942E+09 | 0.254109E+10 | 0.00 | 0.00 |
September | 0.678217E+10 | 0.456672E+09 | 0.348202E+10 | 0.903301E+09 | 0.257872E+10 | 0.00 | 0.00 |
October | 0.107423E+11 | 0.232183E+10 | 0.619102E+10 | 0.345694E+10 | 0.273408E+10 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.395746E+10 | 0.748585E+10 | 0.494870E+10 | 0.253715E+10 | 0.00 | 0.00 |
December | 0.979750E+10 | 0.514590E+10 | 0.690360E+10 | 0.432670E+10 | 0.257690E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.993229E+11 | 0.250869E+11 | 0.550983E+11 | 0.243778E+11 | 0.307205E+11 | 0.00 | 0.00 |
Minimum of Months | 0.650069E+10 | 30063826.29 | 0.234707E+10 | 34395014.37 | 0.230775E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119080E+11 | 0.514590E+10 | 0.748585E+10 | 0.494870E+10 | 0.293146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.218532E+10 | 0.350413E+10 | 0.198397E+10 | 0.772036E+09 | 0.121193E+10 | 0.00 | 0.00 |
February | 0.261743E+10 | 0.262477E+10 | 0.204918E+10 | 0.755137E+09 | 0.129404E+10 | 0.00 | 0.00 |
March | 0.460497E+10 | 0.191457E+10 | 0.294219E+10 | 0.117617E+10 | 0.176602E+10 | 0.00 | 0.00 |
April | 0.679480E+10 | 0.762308E+09 | 0.346080E+10 | 0.162304E+10 | 0.183776E+10 | 0.00 | 0.00 |
May | 0.780876E+10 | 0.175986E+09 | 0.338607E+10 | 0.143623E+10 | 0.194984E+10 | 0.00 | 0.00 |
June | 0.750731E+10 | 0.114473E+09 | 0.307783E+10 | 0.119545E+10 | 0.188238E+10 | 0.00 | 0.00 |
July | 0.577190E+10 | 35275653.41 | 0.236007E+10 | 0.458998E+09 | 0.190108E+10 | 0.00 | 0.00 |
August | 0.497006E+10 | 0.107019E+09 | 0.216752E+10 | 0.385235E+09 | 0.178229E+10 | 0.00 | 0.00 |
September | 0.461645E+10 | 0.345422E+09 | 0.230588E+10 | 0.676982E+09 | 0.162889E+10 | 0.00 | 0.00 |
October | 0.439269E+10 | 0.153084E+10 | 0.247991E+10 | 0.987447E+09 | 0.149247E+10 | 0.00 | 0.00 |
November | 0.314977E+10 | 0.260493E+10 | 0.217108E+10 | 0.925235E+09 | 0.124585E+10 | 0.00 | 0.00 |
December | 0.216729E+10 | 0.346033E+10 | 0.191976E+10 | 0.731997E+09 | 0.118776E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.565867E+11 | 0.171800E+11 | 0.303043E+11 | 0.111240E+11 | 0.191803E+11 | 0.00 | 0.00 |
Minimum of Months | 0.216729E+10 | 35275653.41 | 0.191976E+10 | 0.385235E+09 | 0.118776E+10 | 0.00 | 0.00 |
Maximum of Months | 0.780876E+10 | 0.350413E+10 | 0.346080E+10 | 0.162304E+10 | 0.194984E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.37 | 7.87 | 1.20 | 0.37 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.77 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.59 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.31 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.95 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.37 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.28 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.69 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.73 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.45 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.87 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.75 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.37 | 7.87 | 0.66 | 0.37 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.18 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.17 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.47 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.63 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.60 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.49 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.34 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.56 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.67 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.02 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.14 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.28 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.18 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.67 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.55 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.57 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.73 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.61 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.36 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.40 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.17 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.16 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.05 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.91 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.61 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.17 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.47 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.24 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.03 | 0.00 | 15.60 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.69 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.40 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.58 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.47 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.174377E+11 | -.304568E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130730E+10 | 68.45 | 0.00 | 0.00 |
February | 0.153070E+11 | -.271010E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.117752E+10 | 68.32 | 0.00 | 0.00 |
March | 0.166391E+11 | -.297454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128743E+10 | 67.69 | 0.00 | 0.00 |
April | 0.113216E+11 | -.242609E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.127527E+10 | 68.81 | 0.00 | 0.00 |
May | 0.943116E+10 | -.229221E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.133134E+10 | 69.23 | 0.00 | 0.00 |
June | 0.724128E+10 | -.204162E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.129312E+10 | 69.37 | 0.00 | 0.00 |
July | 0.488694E+10 | -.185869E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.137690E+10 | 70.89 | 0.00 | 0.00 |
August | 0.736999E+10 | -.209934E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.133486E+10 | 69.36 | 0.00 | 0.00 |
September | 0.793393E+10 | -.210579E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.129338E+10 | 69.49 | 0.00 | 0.00 |
October | 0.111626E+11 | -.245430E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.132797E+10 | 69.28 | 0.00 | 0.00 |
November | 0.141312E+11 | -.268841E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.127528E+10 | 68.93 | 0.00 | 0.00 |
December | 0.157614E+11 | -.288888E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130669E+10 | 68.52 | 0.00 | 0.00 |
Annual Sum or Average | 0.138624E+12 | -.295857E+12 | 8760.00 | -.155871E+11 | 69.03 | |||||
Minimum of Months | 0.488694E+10 | -.304568E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.137690E+10 | 67.69 | 0.00 | 0.00 |
Maximum of Months | 0.174377E+11 | -.185869E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.117752E+10 | 70.89 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5601.45 | 35.39 | 298.33 | 287.33 | 1249.45 | 25.69 | 289.50 | 266.50 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3371.38 | 29.29 | 203.17 | 271.17 | 1107.51 | 21.62 | 212.17 | 244.50 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1753.77 | 20.42 | 74.67 | 323.67 | 953.34 | 21.47 | 244.83 | 291.83 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 1191.11 | 18.84 | 8.17 | 329.17 | 705.18 | 20.14 | 177.00 | 296.17 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:10 | 1010.75 | 18.66 | 0.00 | 350.00 | 594.01 | 20.04 | 139.67 | 310.17 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1000.14 | 18.31 | 0.00 | 334.50 | 574.22 | 19.67 | 131.33 | 292.67 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1117.58 | 18.82 | 0.17 | 333.50 | 582.41 | 20.08 | 142.67 | 281.83 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1255.37 | 18.81 | 16.00 | 322.00 | 631.30 | 20.05 | 171.17 | 271.83 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:19 | 1529.35 | 19.54 | 64.00 | 302.50 | 793.18 | 20.86 | 210.33 | 263.50 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2584.30 | 21.50 | 106.50 | 305.50 | 1069.84 | 21.10 | 225.00 | 278.50 |
November | 317.83 | 0.51 | 0.48 | 01-NOV-07:19 | 7574.05 | 36.61 | 310.50 | 288.00 | 1306.40 | 23.59 | 257.00 | 265.00 |
December | 315.50 | 0.50 | 0.48 | 01-DEC-07:30 | 5915.13 | 36.71 | 308.83 | 286.17 | 1468.52 | 27.87 | 307.67 | 278.83 |
Annual Sum or Average | 4237.50 | 0.52 | 2664.70 | 23.84 | 1390.33 | 3733.50 | 895.26 | 21.68 | 2508.33 | 3341.33 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 1000.14 | 18.31 | 0.00 | 271.17 | 574.22 | 19.67 | 131.33 | 244.50 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 7574.05 | 36.71 | 310.50 | 350.00 | 1468.52 | 27.87 | 307.67 | 310.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1659.50 | 23.81 | 107.17 | 268.17 | 877.46 | 23.87 | 165.50 | 224.00 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2055.65 | 23.95 | 100.33 | 257.67 | 1086.45 | 24.05 | 153.33 | 222.00 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:30 | 1978.28 | 23.42 | 101.50 | 319.17 | 1026.00 | 23.67 | 162.50 | 287.67 |
April | 379.83 | 0.52 | 0.48 | 01-APR-06:49 | 2396.12 | 22.85 | 110.33 | 328.50 | 1263.43 | 23.19 | 115.67 | 300.67 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2484.96 | 23.23 | 128.50 | 357.50 | 971.83 | 22.39 | 122.50 | 324.00 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 1985.33 | 21.97 | 108.00 | 338.00 | 836.90 | 21.47 | 124.00 | 300.50 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1643.12 | 21.93 | 102.00 | 337.50 | 735.99 | 21.51 | 124.00 | 287.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1505.12 | 21.40 | 98.33 | 323.00 | 696.56 | 21.05 | 132.67 | 268.50 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1680.94 | 22.41 | 90.50 | 298.00 | 853.17 | 22.81 | 150.33 | 258.33 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-06:49 | 1848.97 | 23.14 | 102.67 | 297.50 | 938.26 | 23.21 | 159.33 | 265.17 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-07:10 | 1669.54 | 23.55 | 94.83 | 268.83 | 851.27 | 23.54 | 152.33 | 239.33 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-07:30 | 1735.12 | 24.44 | 112.50 | 262.83 | 924.42 | 24.42 | 168.50 | 227.50 |
Annual Sum or Average | 4237.50 | 0.52 | 1898.79 | 22.95 | 1256.67 | 3656.67 | 921.12 | 22.86 | 1730.67 | 3205.00 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1505.12 | 21.40 | 90.50 | 257.67 | 696.56 | 21.05 | 115.67 | 222.00 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2484.96 | 24.44 | 128.50 | 357.50 | 1263.43 | 24.42 | 168.50 | 324.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:20 | 557.25 | 16.45 | 0.00 | 248.50 | 343.06 | 17.98 | 0.00 | 168.67 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-08:50 | 642.87 | 17.33 | 0.00 | 249.17 | 394.68 | 18.79 | 0.00 | 184.83 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:20 | 760.24 | 18.43 | 0.00 | 314.00 | 466.00 | 19.81 | 0.33 | 264.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 821.71 | 18.45 | 0.00 | 332.83 | 511.73 | 19.75 | 45.83 | 298.83 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:30 | 975.17 | 19.14 | 5.83 | 365.67 | 573.90 | 20.47 | 147.33 | 336.67 |
June | 386.67 | 0.51 | 0.48 | 01-JUN-07:19 | 1077.54 | 20.75 | 61.83 | 348.33 | 603.85 | 20.31 | 168.17 | 311.83 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1090.70 | 20.40 | 39.50 | 345.17 | 571.66 | 20.97 | 141.33 | 298.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 975.40 | 18.50 | 0.00 | 325.67 | 511.10 | 19.70 | 88.00 | 272.17 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 851.67 | 18.37 | 0.00 | 299.17 | 474.74 | 19.62 | 32.67 | 246.00 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:40 | 674.59 | 17.28 | 0.00 | 288.67 | 423.26 | 18.76 | 0.00 | 236.17 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:09 | 575.32 | 16.86 | 0.00 | 253.00 | 374.29 | 18.53 | 0.00 | 193.50 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-08:39 | 549.34 | 16.55 | 0.00 | 243.67 | 341.25 | 18.14 | 0.00 | 166.00 |
Annual Sum or Average | 4237.50 | 0.52 | 810.96 | 18.31 | 107.17 | 3613.83 | 473.11 | 19.47 | 623.67 | 2977.00 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 549.34 | 16.45 | 0.00 | 243.67 | 341.25 | 17.98 | 0.00 | 166.00 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1090.70 | 20.75 | 61.83 | 365.67 | 603.85 | 20.97 | 168.17 | 336.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:20 | 1662.70 | 23.59 | 104.33 | 266.67 | 864.57 | 23.60 | 165.33 | 224.00 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-09:09 | 1968.49 | 23.58 | 103.67 | 262.00 | 793.41 | 22.37 | 148.33 | 224.17 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:30 | 1930.17 | 23.33 | 101.17 | 319.83 | 996.83 | 23.56 | 172.83 | 289.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:00 | 2196.78 | 21.11 | 84.50 | 332.17 | 1149.58 | 21.58 | 89.00 | 302.67 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:19 | 2108.57 | 17.36 | 0.00 | 352.17 | 1096.19 | 19.49 | 79.33 | 322.67 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:00 | 2097.29 | 17.37 | 0.00 | 337.83 | 870.99 | 19.33 | 86.17 | 303.00 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-07:30 | 1591.48 | 18.08 | 3.67 | 336.50 | 727.35 | 19.66 | 95.50 | 288.50 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1485.31 | 19.36 | 54.17 | 322.00 | 741.31 | 19.52 | 96.00 | 274.00 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-08:09 | 1650.06 | 21.60 | 81.00 | 301.50 | 832.90 | 21.96 | 149.17 | 258.33 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:49 | 1961.28 | 23.23 | 105.00 | 293.67 | 992.15 | 23.31 | 147.83 | 264.17 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-08:20 | 1719.77 | 23.67 | 97.17 | 270.00 | 867.88 | 23.64 | 154.50 | 240.50 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-08:39 | 1515.46 | 23.74 | 101.00 | 269.17 | 785.60 | 23.71 | 169.33 | 232.33 |
Annual Sum or Average | 4237.50 | 0.52 | 1832.67 | 21.14 | 835.67 | 3663.50 | 898.29 | 21.69 | 1553.33 | 3223.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1485.31 | 17.36 | 0.00 | 262.00 | 727.35 | 19.33 | 79.33 | 224.00 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2196.78 | 23.74 | 105.00 | 352.17 | 1149.58 | 23.71 | 172.83 | 322.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5637.28 | 34.87 | 296.67 | 287.33 | 1332.53 | 21.49 | 84.50 | 268.33 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3411.49 | 26.53 | 195.33 | 271.33 | 1186.35 | 16.74 | 0.00 | 246.83 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1788.26 | 14.20 | 7.50 | 323.67 | 1020.62 | 17.34 | 0.00 | 295.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 1218.90 | 13.09 | 0.00 | 329.33 | 754.80 | 16.51 | 0.00 | 300.00 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:10 | 1030.59 | 12.71 | 0.00 | 350.17 | 633.71 | 16.18 | 0.00 | 315.67 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1017.53 | 12.27 | 0.00 | 334.83 | 611.67 | 15.67 | 0.00 | 296.67 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1129.88 | 12.34 | 0.00 | 333.83 | 618.58 | 15.68 | 0.00 | 287.67 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1265.68 | 12.30 | 0.00 | 322.33 | 669.62 | 15.57 | 0.00 | 277.83 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-07:19 | 1547.63 | 13.06 | 0.00 | 302.67 | 843.70 | 16.46 | 0.00 | 268.00 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2634.11 | 15.59 | 42.67 | 307.67 | 1149.70 | 16.81 | 10.00 | 282.17 |
November | 317.83 | 0.50 | 0.48 | 01-NOV-07:19 | 7629.89 | 36.20 | 310.33 | 288.00 | 1411.23 | 20.68 | 74.33 | 272.83 |
December | 315.50 | 0.50 | 0.48 | 01-DEC-07:30 | 5951.60 | 36.30 | 308.00 | 286.50 | 1557.35 | 24.11 | 123.17 | 279.83 |
Annual Sum or Average | 4237.50 | 0.51 | 2693.70 | 19.21 | 1160.50 | 3737.67 | 956.37 | 17.61 | 292.00 | 3391.00 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 1017.53 | 12.27 | 0.00 | 271.33 | 611.67 | 15.57 | 0.00 | 246.83 | |
Maximum of Months | 406.00 | 0.52 | 0.48 | 7629.89 | 36.30 | 310.33 | 350.17 | 1557.35 | 24.11 | 123.17 | 315.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1686.00 | 21.34 | 106.83 | 269.33 | 915.16 | 22.01 | 77.33 | 229.17 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2092.45 | 21.28 | 100.00 | 258.83 | 1130.56 | 22.03 | 74.00 | 226.67 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:30 | 2027.20 | 20.42 | 101.50 | 320.17 | 1077.39 | 21.32 | 70.67 | 291.50 |
April | 379.83 | 0.52 | 0.48 | 01-APR-06:49 | 2423.94 | 19.92 | 110.17 | 329.17 | 1318.65 | 20.85 | 81.17 | 304.67 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2503.92 | 19.26 | 117.00 | 357.83 | 1027.05 | 19.72 | 66.50 | 328.00 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 2014.08 | 18.87 | 107.17 | 339.00 | 884.71 | 18.81 | 51.33 | 304.50 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1664.59 | 18.29 | 96.33 | 339.67 | 781.24 | 18.88 | 48.17 | 294.50 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1526.50 | 18.27 | 97.50 | 324.33 | 793.37 | 19.46 | 69.00 | 275.50 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1714.10 | 19.37 | 90.00 | 299.17 | 894.82 | 20.46 | 64.50 | 264.00 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-06:49 | 1888.32 | 20.21 | 100.83 | 298.33 | 984.21 | 21.11 | 72.17 | 269.17 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1694.12 | 19.98 | 87.83 | 269.83 | 894.32 | 21.55 | 64.83 | 243.33 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-07:30 | 1760.69 | 22.04 | 112.50 | 264.00 | 961.88 | 22.67 | 81.67 | 233.00 |
Annual Sum or Average | 4237.50 | 0.52 | 1928.04 | 19.86 | 1227.67 | 3669.67 | 971.88 | 20.65 | 821.33 | 3264.00 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1526.50 | 18.27 | 87.83 | 258.83 | 781.24 | 18.81 | 48.17 | 226.67 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2503.92 | 22.04 | 117.00 | 357.83 | 1318.65 | 22.67 | 81.67 | 328.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:09 | 565.85 | 10.80 | 0.00 | 249.33 | 365.11 | 14.34 | 0.00 | 180.83 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-08:39 | 653.67 | 11.70 | 0.00 | 249.67 | 420.29 | 15.24 | 0.00 | 194.17 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:09 | 774.40 | 13.02 | 0.00 | 315.00 | 496.61 | 16.52 | 0.00 | 270.83 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 839.62 | 13.18 | 0.00 | 332.83 | 546.22 | 16.62 | 0.00 | 305.33 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:30 | 995.24 | 13.24 | 1.17 | 365.83 | 612.20 | 16.80 | 1.17 | 340.00 |
June | 386.67 | 0.51 | 0.48 | 01-JUN-07:19 | 1097.35 | 15.51 | 39.17 | 348.33 | 645.93 | 18.70 | 40.50 | 317.83 |
July | 379.83 | 0.50 | 0.48 | 01-JUL-06:30 | 1105.10 | 14.59 | 29.17 | 345.50 | 607.82 | 17.77 | 29.67 | 303.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 987.90 | 12.21 | 0.00 | 325.83 | 542.71 | 15.50 | 0.00 | 280.00 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:19 | 864.28 | 12.49 | 0.00 | 299.50 | 504.75 | 15.83 | 0.00 | 253.00 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:30 | 686.80 | 11.81 | 0.00 | 289.33 | 451.03 | 15.27 | 0.00 | 243.00 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-08:09 | 585.05 | 11.21 | 0.00 | 253.67 | 398.79 | 14.90 | 0.00 | 205.00 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-08:30 | 557.63 | 10.85 | 0.00 | 245.17 | 363.13 | 14.48 | 0.00 | 179.50 |
Annual Sum or Average | 4237.50 | 0.52 | 824.69 | 12.65 | 69.50 | 3620.00 | 504.05 | 16.09 | 71.33 | 3072.83 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 557.63 | 10.80 | 0.00 | 245.17 | 363.13 | 14.34 | 0.00 | 179.50 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1105.10 | 15.51 | 39.17 | 365.83 | 645.93 | 18.70 | 40.50 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:09 | 1689.14 | 21.13 | 104.00 | 267.83 | 902.14 | 21.72 | 74.17 | 227.33 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:00 | 2001.49 | 21.02 | 103.17 | 263.50 | 834.97 | 20.06 | 48.00 | 228.67 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1977.17 | 20.35 | 101.17 | 320.17 | 1047.18 | 21.22 | 69.33 | 293.00 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:49 | 2224.42 | 17.84 | 84.50 | 332.67 | 1204.02 | 18.94 | 54.67 | 306.00 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-07:19 | 2133.77 | 12.72 | 0.00 | 352.83 | 1150.38 | 16.18 | 0.00 | 327.00 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:49 | 2128.43 | 12.81 | 0.00 | 338.17 | 922.82 | 16.06 | 0.00 | 307.00 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-07:19 | 1614.04 | 13.55 | 3.50 | 337.50 | 767.91 | 16.44 | 0.00 | 294.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:30 | 1506.77 | 15.59 | 52.00 | 323.00 | 779.22 | 16.41 | 4.50 | 278.17 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-07:00 | 1683.19 | 18.39 | 80.17 | 302.67 | 875.10 | 19.44 | 52.00 | 263.33 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:49 | 2001.27 | 20.56 | 104.67 | 294.67 | 1037.43 | 21.25 | 74.17 | 267.33 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-08:20 | 1749.49 | 20.89 | 95.83 | 270.83 | 910.63 | 21.70 | 67.17 | 244.67 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-08:30 | 1529.82 | 20.12 | 90.17 | 269.50 | 822.62 | 21.88 | 70.00 | 237.00 |
Annual Sum or Average | 4237.50 | 0.52 | 1861.98 | 17.67 | 819.17 | 3673.33 | 943.30 | 19.11 | 514.00 | 3273.83 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1506.77 | 12.72 | 0.00 | 263.50 | 767.91 | 16.06 | 0.00 | 227.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2224.42 | 21.13 | 104.67 | 352.83 | 1204.02 | 21.88 | 74.17 | 327.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5639.31 | 34.86 | 296.67 | 287.33 | 1334.50 | 21.48 | 84.50 | 268.67 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3414.16 | 26.52 | 195.33 | 271.33 | 1188.16 | 16.72 | 0.00 | 246.83 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1790.70 | 14.17 | 7.50 | 323.83 | 1022.13 | 17.33 | 0.00 | 295.33 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 1220.35 | 13.06 | 0.00 | 329.50 | 755.79 | 16.49 | 0.00 | 300.17 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-06:00 | 1031.81 | 12.68 | 0.00 | 350.17 | 634.56 | 16.17 | 0.00 | 315.67 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1018.83 | 12.24 | 0.00 | 335.00 | 612.54 | 15.66 | 0.00 | 296.83 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1131.82 | 12.31 | 0.00 | 334.00 | 619.65 | 15.67 | 0.00 | 287.83 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1268.01 | 12.28 | 0.00 | 322.33 | 670.88 | 15.56 | 0.00 | 277.83 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-07:19 | 1550.23 | 13.03 | 0.00 | 302.67 | 845.20 | 16.45 | 0.00 | 268.33 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2636.55 | 15.57 | 42.67 | 307.67 | 1151.32 | 16.79 | 10.00 | 282.17 |
November | 317.83 | 0.50 | 0.48 | 01-NOV-07:19 | 7631.98 | 36.19 | 310.33 | 288.00 | 1413.09 | 20.67 | 74.33 | 273.00 |
December | 315.50 | 0.50 | 0.48 | 01-DEC-07:30 | 5953.60 | 36.29 | 308.00 | 286.50 | 1559.43 | 24.10 | 123.17 | 279.83 |
Annual Sum or Average | 4237.50 | 0.51 | 2695.72 | 19.18 | 1160.50 | 3738.33 | 957.78 | 17.59 | 292.00 | 3392.50 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 1018.83 | 12.24 | 0.00 | 271.33 | 612.54 | 15.56 | 0.00 | 246.83 | |
Maximum of Months | 406.00 | 0.52 | 0.48 | 7631.98 | 36.29 | 310.33 | 350.17 | 1559.43 | 24.10 | 123.17 | 315.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1686.95 | 21.32 | 106.83 | 269.33 | 916.12 | 21.99 | 77.33 | 229.33 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2093.63 | 21.25 | 99.67 | 258.83 | 1131.66 | 22.02 | 74.00 | 226.67 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:30 | 2028.48 | 20.40 | 101.50 | 320.33 | 1078.59 | 21.31 | 70.67 | 291.50 |
April | 379.83 | 0.52 | 0.48 | 01-APR-06:49 | 2425.18 | 19.90 | 110.17 | 329.17 | 1319.81 | 20.84 | 81.17 | 304.67 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2505.27 | 19.23 | 117.00 | 357.83 | 1028.21 | 19.70 | 66.50 | 328.00 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 2015.71 | 18.84 | 107.17 | 339.00 | 885.90 | 18.80 | 51.33 | 304.83 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1666.74 | 18.26 | 96.33 | 340.00 | 782.53 | 18.87 | 48.17 | 294.67 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1528.69 | 18.24 | 97.50 | 324.33 | 794.67 | 19.45 | 69.00 | 275.50 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1715.97 | 19.35 | 90.00 | 299.17 | 896.13 | 20.45 | 64.50 | 264.33 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-06:49 | 1889.42 | 20.19 | 100.83 | 298.33 | 985.30 | 21.09 | 72.17 | 269.17 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1694.97 | 19.95 | 87.83 | 269.83 | 895.25 | 21.54 | 64.83 | 243.33 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-07:30 | 1761.61 | 22.02 | 112.50 | 264.17 | 962.83 | 22.66 | 81.67 | 233.00 |
Annual Sum or Average | 4237.50 | 0.52 | 1929.45 | 19.83 | 1227.33 | 3670.33 | 973.03 | 20.63 | 821.33 | 3265.00 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1528.69 | 18.24 | 87.83 | 258.83 | 782.53 | 18.80 | 48.17 | 226.67 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2505.27 | 22.02 | 117.00 | 357.83 | 1319.81 | 22.66 | 81.67 | 328.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:09 | 566.30 | 10.77 | 0.00 | 249.33 | 365.55 | 14.33 | 0.00 | 181.00 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-08:39 | 654.22 | 11.67 | 0.00 | 249.67 | 420.81 | 15.22 | 0.00 | 194.67 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:09 | 775.07 | 12.99 | 0.00 | 315.17 | 497.22 | 16.51 | 0.00 | 270.83 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 840.31 | 13.15 | 0.00 | 332.83 | 546.86 | 16.60 | 0.00 | 305.33 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:30 | 996.26 | 13.21 | 1.17 | 365.83 | 613.00 | 16.79 | 1.17 | 340.00 |
June | 386.67 | 0.51 | 0.48 | 01-JUN-07:19 | 1098.69 | 15.48 | 39.17 | 348.33 | 646.86 | 18.69 | 40.50 | 317.83 |
July | 379.83 | 0.50 | 0.48 | 01-JUL-06:30 | 1106.87 | 14.57 | 29.17 | 345.67 | 608.86 | 17.76 | 29.67 | 303.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 989.52 | 12.18 | 0.00 | 325.83 | 543.67 | 15.49 | 0.00 | 280.17 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:19 | 865.43 | 12.46 | 0.00 | 299.50 | 505.53 | 15.82 | 0.00 | 253.00 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:30 | 687.30 | 11.78 | 0.00 | 289.33 | 451.55 | 15.26 | 0.00 | 243.00 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-08:09 | 585.35 | 11.18 | 0.00 | 253.67 | 399.21 | 14.89 | 0.00 | 205.00 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-08:30 | 558.03 | 10.82 | 0.00 | 245.17 | 363.57 | 14.46 | 0.00 | 179.67 |
Annual Sum or Average | 4237.50 | 0.52 | 825.59 | 12.62 | 69.50 | 3620.33 | 504.74 | 16.08 | 71.33 | 3073.83 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 558.03 | 10.77 | 0.00 | 245.17 | 363.57 | 14.33 | 0.00 | 179.67 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1106.87 | 15.48 | 39.17 | 365.83 | 646.86 | 18.69 | 40.50 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:09 | 1690.10 | 21.11 | 103.83 | 267.83 | 903.10 | 21.71 | 74.17 | 227.33 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:00 | 2002.70 | 21.00 | 103.17 | 263.50 | 836.05 | 20.05 | 48.00 | 229.00 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1978.46 | 20.32 | 101.17 | 320.17 | 1048.37 | 21.20 | 69.33 | 293.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:49 | 2225.64 | 17.81 | 84.50 | 332.67 | 1205.16 | 18.92 | 54.67 | 306.17 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-07:19 | 2135.13 | 12.69 | 0.00 | 353.17 | 1151.56 | 16.16 | 0.00 | 327.00 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:49 | 2130.07 | 12.77 | 0.00 | 338.33 | 924.05 | 16.05 | 0.00 | 307.17 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-07:19 | 1616.22 | 13.52 | 3.50 | 337.50 | 769.22 | 16.43 | 0.00 | 294.83 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:30 | 1508.97 | 15.56 | 52.00 | 323.17 | 780.53 | 16.40 | 4.50 | 278.33 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-07:00 | 1685.10 | 18.37 | 80.00 | 302.67 | 876.41 | 19.43 | 52.00 | 263.67 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:49 | 2002.43 | 20.53 | 104.67 | 294.67 | 1038.51 | 21.24 | 74.17 | 267.67 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-08:20 | 1750.32 | 20.86 | 95.83 | 270.83 | 911.56 | 21.68 | 67.17 | 244.83 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-08:30 | 1530.76 | 20.10 | 90.17 | 269.50 | 823.56 | 21.86 | 70.00 | 237.00 |
Annual Sum or Average | 4237.50 | 0.52 | 1863.41 | 17.64 | 818.83 | 3674.00 | 944.45 | 19.09 | 514.00 | 3276.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1508.97 | 12.69 | 0.00 | 263.50 | 769.22 | 16.05 | 0.00 | 227.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2225.64 | 21.11 | 104.67 | 353.17 | 1205.16 | 21.86 | 74.17 | 327.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.309985E+09 | 224309.15 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309985E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309985E+09 | 224309.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146833E+10 | 79895.15 | 02-JAN-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 751184.69 | 743.86 | 11-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102888E+09 | 18244.34 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157197E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146833E+10 | 79895.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5097377.65 | 3078.86 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5097377.65 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5097377.65 | 3078.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.686102E+10 | 172044.44 | 03-JAN-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.981938E+09 | 126126.21 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233098E+10 | 170612.79 | 22-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101739E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.686102E+10 | 172044.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225016E+10 | 129145.66 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.233642E+09 | 94590.37 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.457481E+09 | 89981.98 | 22-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294128E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225016E+10 | 129145.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125568E+10 | 171374.92 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207173E+09 | 125455.45 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137344E+09 | 13934.00 | 23-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160020E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125568E+10 | 171374.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182342E+10 | 128600.92 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149359E+09 | 51613.52 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334637E+09 | 55615.48 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230741E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182342E+10 | 128600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.223442E+10 | 20570.84 | 05-JAN-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.505110E+09 | 19950.70 | 02-FEB-05:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2807953.01 | 599.43 | 01-MAR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77813906.29 | 16075.16 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117910E+10 | 20601.17 | 21-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.399926E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.223442E+10 | 20601.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.826223E+09 | 14754.36 | 03-JAN-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171026E+09 | 14409.20 | 11-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14807292.97 | 3566.75 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.406001E+09 | 14792.18 | 21-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.141806E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.826223E+09 | 14792.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.781349E+09 | 20533.54 | 03-JAN-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187074E+09 | 19279.47 | 11-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307294E+09 | 20504.16 | 23-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127572E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.781349E+09 | 20533.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.714582E+09 | 15532.83 | 03-JAN-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135529E+09 | 15165.51 | 11-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4217073.49 | 612.31 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.310217E+09 | 15511.47 | 23-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116455E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.714582E+09 | 15532.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.252244E+10 | 220114.22 | 01-JAN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112118E+10 | 220117.97 | 27-FEB-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153976E+10 | 220121.97 | 19-MAR-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.761638E+09 | 220091.97 | 10-APR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774754E+09 | 218930.71 | 29-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.554940E+09 | 217000.08 | 04-JUN-20:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.851813E+09 | 211020.46 | 04-JUL-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.569596E+09 | 210826.55 | 06-AUG-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.990280E+09 | 211194.09 | 24-SEP-12:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110232E+10 | 219047.68 | 15-OCT-11:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.233749E+10 | 220122.78 | 23-NOV-20:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318230E+10 | 220117.97 | 17-DEC-21:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163085E+11 | |||||||
Minimum of Months | 0.554940E+09 | 210826.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.318230E+10 | 220122.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.855322E+09 | 11054.37 | 05-JAN-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137942E+09 | 6642.64 | 02-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 323522.37 | 692.41 | 27-NOV-05:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213746E+09 | 10104.46 | 23-DEC-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120733E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.855322E+09 | 11054.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128727E+11 | 107192.88 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206589E+10 | 74679.56 | 02-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 72010545.31 | 19265.59 | 27-NOV-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365591E+10 | 86135.81 | 21-DEC-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186665E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128727E+11 | 107192.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208782E+10 | 11233.75 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.502130E+09 | 9564.99 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 42735418.90 | 5530.63 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.878148E+09 | 10072.56 | 23-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.351083E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.208782E+10 | 11233.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.513482E+11 | 0.509976E+11 | 120929.24 | 16-JAN-19:22 | 98001.28 | 0.48 |
February | 0.00 | 0.00 | 0.529643E+11 | 0.527764E+11 | 143617.94 | 26-FEB-19:31 | 88109.48 | 0.54 |
March | 0.00 | 0.00 | 0.751096E+11 | 0.745583E+11 | 146828.42 | 11-MAR-04:53 | 93026.36 | 0.59 |
April | 0.00 | 0.00 | 0.884959E+11 | 0.862386E+11 | 153784.07 | 27-APR-03:01 | 94314.10 | 0.58 |
May | 0.00 | 0.00 | 0.114756E+12 | 0.102080E+12 | 187818.22 | 21-MAY-21:17 | 102063.15 | 0.65 |
June | 0.00 | 0.00 | 0.134895E+12 | 0.106096E+12 | 208274.11 | 25-JUN-18:51 | 86326.25 | 0.66 |
July | 0.00 | 0.00 | 0.158483E+12 | 0.107071E+12 | 215207.07 | 16-JUL-12:31 | 84528.45 | 0.68 |
August | 0.00 | 0.00 | 0.173444E+12 | 0.112235E+12 | 221208.93 | 27-AUG-12:41 | 85641.94 | 0.70 |
September | 0.00 | 0.00 | 0.137059E+12 | 0.966054E+11 | 210723.13 | 10-SEP-20:52 | 85806.13 | 0.68 |
October | 0.00 | 0.00 | 0.995298E+11 | 0.919286E+11 | 157731.82 | 04-OCT-03:41 | 87699.08 | 0.66 |
November | 0.00 | 0.00 | 0.766402E+11 | 0.759399E+11 | 137180.68 | 09-NOV-04:01 | 85894.79 | 0.62 |
December | 0.00 | 0.00 | 0.602384E+11 | 0.600706E+11 | 118219.78 | 17-DEC-13:01 | 98808.12 | 0.48 |
Annual Sum or Average | 0.122296E+13 | 0.101660E+13 | 0.61 | |||||
Minimum of Months | 0.00 | 0.00 | 0.513482E+11 | 0.509976E+11 | 118219.78 | 84528.45 | 0.48 | |
Maximum of Months | 0.00 | 0.00 | 0.173444E+12 | 0.112235E+12 | 221208.93 | 102063.15 | 0.70 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.353038E+11 | 0.349963E+11 | 67195.15 | 12-JAN-15:00 | 67195.15 | 0.37 |
February | 0.00 | 0.00 | 0.567291E+11 | 0.552632E+11 | 97413.16 | 21-FEB-15:00 | 97413.16 | 0.52 |
March | 0.00 | 0.00 | 0.119287E+12 | 0.111973E+12 | 163051.85 | 11-MAR-06:02 | 139127.58 | 0.72 |
April | 0.00 | 0.00 | 0.182938E+12 | 0.168870E+12 | 213823.32 | 27-APR-05:02 | 186085.70 | 0.82 |
May | 0.00 | 0.00 | 0.239960E+12 | 0.191163E+12 | 247303.06 | 24-MAY-05:02 | 172726.39 | 0.86 |
June | 0.00 | 0.00 | 0.281154E+12 | 0.195510E+12 | 256335.43 | 08-JUN-05:02 | 192991.95 | 0.87 |
July | 0.00 | 0.00 | 0.320552E+12 | 0.186249E+12 | 268992.06 | 08-JUL-05:02 | 189206.30 | 0.87 |
August | 0.00 | 0.00 | 0.334493E+12 | 0.189751E+12 | 272023.32 | 28-AUG-05:03 | 185733.25 | 0.89 |
September | 0.00 | 0.00 | 0.242419E+12 | 0.142564E+12 | 255055.73 | 05-SEP-05:02 | 176418.71 | 0.79 |
October | 0.00 | 0.00 | 0.157288E+12 | 0.129864E+12 | 222765.59 | 04-OCT-05:02 | 173042.11 | 0.74 |
November | 0.00 | 0.00 | 0.945785E+11 | 0.909254E+11 | 119864.16 | 06-NOV-14:40 | 109894.23 | 0.63 |
December | 0.00 | 0.00 | 0.544789E+11 | 0.543324E+11 | 85160.93 | 04-DEC-14:30 | 85160.93 | 0.47 |
Annual Sum or Average | 0.211918E+13 | 0.155146E+13 | 0.71 | |||||
Minimum of Months | 0.00 | 0.00 | 0.353038E+11 | 0.349963E+11 | 67195.15 | 67195.15 | 0.37 | |
Maximum of Months | 0.00 | 0.00 | 0.334493E+12 | 0.195510E+12 | 272023.32 | 192991.95 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.231093E+12 | 0.229363E+12 | 548331.23 | 12-JAN-15:05 | 548331.23 | 0.32 |
February | 0.00 | 0.00 | 0.403832E+12 | 0.393556E+12 | 811647.68 | 24-FEB-15:05 | 739915.41 | 0.47 |
March | 0.00 | 0.00 | 0.916989E+12 | 0.862028E+12 | 1628699.36 | 29-MAR-03:01 | 1332314.76 | 0.61 |
April | 0.00 | 0.00 | 0.149973E+13 | 0.137572E+13 | 1683879.56 | 25-APR-05:01 | 1437145.30 | 0.72 |
May | 0.00 | 0.00 | 0.227329E+13 | 0.179181E+13 | 2188503.15 | 24-MAY-05:01 | 1508214.42 | 0.84 |
June | 0.00 | 0.00 | 0.259906E+13 | 0.176674E+13 | 2325512.98 | 27-JUN-05:01 | 1573558.49 | 0.83 |
July | 0.00 | 0.00 | 0.284947E+13 | 0.157161E+13 | 2688171.83 | 25-JUL-05:02 | 1606827.62 | 0.80 |
August | 0.00 | 0.00 | 0.278385E+13 | 0.147527E+13 | 2617308.92 | 11-AUG-05:02 | 1603810.22 | 0.78 |
September | 0.00 | 0.00 | 0.214881E+13 | 0.123413E+13 | 2565219.20 | 08-SEP-05:02 | 1567420.05 | 0.71 |
October | 0.00 | 0.00 | 0.130690E+13 | 0.107268E+13 | 2134055.52 | 04-OCT-05:02 | 1627988.95 | 0.65 |
November | 0.00 | 0.00 | 0.701350E+12 | 0.673069E+12 | 1012484.18 | 08-NOV-15:05 | 957365.21 | 0.57 |
December | 0.00 | 0.00 | 0.306683E+12 | 0.305759E+12 | 634332.78 | 01-DEC-15:05 | 634332.78 | 0.40 |
Annual Sum or Average | 0.180210E+14 | 0.127517E+14 | 0.64 | |||||
Minimum of Months | 0.00 | 0.00 | 0.231093E+12 | 0.229363E+12 | 548331.23 | 548331.23 | 0.32 | |
Maximum of Months | 0.00 | 0.00 | 0.284947E+13 | 0.179181E+13 | 2688171.83 | 1627988.95 | 0.84 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.202031E+11 | 0.200362E+11 | 51086.92 | 12-JAN-15:40 | 51086.92 | 0.30 |
February | 0.00 | 0.00 | 0.374761E+11 | 0.364263E+11 | 88518.22 | 22-FEB-15:00 | 88518.22 | 0.45 |
March | 0.00 | 0.00 | 0.940052E+11 | 0.884076E+11 | 178349.18 | 11-MAR-06:01 | 157828.02 | 0.60 |
April | 0.00 | 0.00 | 0.163212E+12 | 0.150521E+12 | 184904.00 | 16-APR-16:41 | 164160.55 | 0.72 |
May | 0.00 | 0.00 | 0.248366E+12 | 0.199907E+12 | 244501.51 | 24-MAY-05:01 | 168521.27 | 0.84 |
June | 0.00 | 0.00 | 0.280793E+12 | 0.197785E+12 | 261307.95 | 16-JUN-05:02 | 189928.52 | 0.83 |
July | 0.00 | 0.00 | 0.301821E+12 | 0.173658E+12 | 299079.88 | 25-JUL-03:01 | 180605.95 | 0.81 |
August | 0.00 | 0.00 | 0.292655E+12 | 0.161324E+12 | 279592.58 | 27-AUG-15:31 | 151844.66 | 0.78 |
September | 0.00 | 0.00 | 0.224037E+12 | 0.132339E+12 | 272591.16 | 09-SEP-05:01 | 159293.03 | 0.72 |
October | 0.00 | 0.00 | 0.133112E+12 | 0.109983E+12 | 206729.35 | 11-OCT-03:01 | 171687.37 | 0.64 |
November | 0.00 | 0.00 | 0.655365E+11 | 0.627709E+11 | 111560.80 | 09-NOV-14:30 | 106164.16 | 0.55 |
December | 0.00 | 0.00 | 0.251525E+11 | 0.250516E+11 | 60837.58 | 01-DEC-15:00 | 60837.58 | 0.37 |
Annual Sum or Average | 0.188637E+13 | 0.135821E+13 | 0.63 | |||||
Minimum of Months | 0.00 | 0.00 | 0.202031E+11 | 0.200362E+11 | 51086.92 | 51086.92 | 0.30 | |
Maximum of Months | 0.00 | 0.00 | 0.301821E+12 | 0.199907E+12 | 299079.88 | 189928.52 | 0.84 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.323343E+12 | 0.309017E+12 | 123610.72 | 02-JAN-17:00 | 117686.97 | 0.00 |
February | 0.00 | 0.00 | 0.512131E+12 | 0.494327E+12 | 215512.38 | 27-FEB-09:50 | 204726.18 | 0.00 |
March | 0.00 | 0.00 | 0.802134E+12 | 0.787603E+12 | 305547.38 | 05-MAR-05:10 | 290902.92 | 0.00 |
April | 0.00 | 0.00 | 0.993731E+12 | 0.987961E+12 | 393720.14 | 26-APR-02:13 | 386359.36 | 0.00 |
May | 0.00 | 0.00 | 0.344531E+12 | 0.329377E+12 | 166989.66 | 01-MAY-00:12 | 162890.39 | 0.00 |
June | 0.00 | 0.00 | 0.570985E+12 | 0.547215E+12 | 228157.53 | 28-JUN-14:00 | 212367.82 | 0.00 |
July | 0.00 | 0.00 | 0.835482E+12 | 0.801291E+12 | 315897.93 | 17-JUL-12:05 | 301472.62 | 0.00 |
August | 0.00 | 0.00 | 0.105402E+13 | 0.102109E+13 | 402387.10 | 15-AUG-22:55 | 389095.63 | 0.00 |
September | 0.00 | 0.00 | 0.348370E+12 | 0.319099E+12 | 165837.56 | 01-SEP-00:05 | 158995.50 | 0.00 |
October | 0.00 | 0.00 | 0.575305E+12 | 0.560163E+12 | 220299.02 | 03-OCT-16:00 | 213700.80 | 0.00 |
November | 0.00 | 0.00 | 0.786001E+12 | 0.765404E+12 | 309015.32 | 24-NOV-08:25 | 294223.60 | 0.00 |
December | 0.00 | 0.00 | 0.106033E+13 | 0.102199E+13 | 407706.75 | 22-DEC-06:30 | 381373.60 | 0.00 |
Annual Sum or Average | 0.820636E+13 | 0.794454E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.323343E+12 | 0.309017E+12 | 123610.72 | 117686.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106033E+13 | 0.102199E+13 | 407706.75 | 389095.63 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.487075E+10 | 0.487074E+10 | 2165.05 | 12-JAN-17:00 | 2165.05 | 0.00 |
February | 0.00 | 0.00 | 0.919292E+10 | 0.919292E+10 | 4279.07 | 20-FEB-17:30 | 4279.07 | 0.00 |
March | 0.00 | 0.00 | 0.153559E+11 | 0.153559E+11 | 6206.26 | 26-MAR-18:05 | 6206.26 | 0.00 |
April | 0.00 | 0.00 | 0.197008E+11 | 0.197008E+11 | 8019.10 | 16-APR-22:23 | 8019.10 | 0.00 |
May | 0.00 | 0.00 | 0.594781E+10 | 0.594781E+10 | 3167.01 | 01-MAY-00:12 | 3167.01 | 0.00 |
June | 0.00 | 0.00 | 0.104499E+11 | 0.104499E+11 | 4523.96 | 11-JUN-17:25 | 4523.96 | 0.00 |
July | 0.00 | 0.00 | 0.156673E+11 | 0.156673E+11 | 6377.95 | 04-JUL-17:53 | 6377.95 | 0.00 |
August | 0.00 | 0.00 | 0.204875E+11 | 0.204875E+11 | 7925.15 | 14-AUG-04:24 | 7925.15 | 0.00 |
September | 0.00 | 0.00 | 0.562880E+10 | 0.562880E+10 | 2638.74 | 01-SEP-00:10 | 2638.74 | 0.00 |
October | 0.00 | 0.00 | 0.106444E+11 | 0.106444E+11 | 4420.65 | 01-OCT-17:17 | 4420.65 | 0.00 |
November | 0.00 | 0.00 | 0.148595E+11 | 0.148595E+11 | 6133.46 | 12-NOV-16:27 | 6133.46 | 0.00 |
December | 0.00 | 0.00 | 0.199367E+11 | 0.199362E+11 | 7752.74 | 24-DEC-16:57 | 7752.74 | 0.00 |
Annual Sum or Average | 0.152742E+12 | 0.152742E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.487075E+10 | 0.487074E+10 | 2165.05 | 2165.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204875E+11 | 0.204875E+11 | 8019.10 | 8019.10 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.321558E+11 | 0.321557E+11 | 19622.99 | 12-JAN-17:30 | 19622.99 | 0.00 |
February | 0.00 | 0.00 | 0.802036E+11 | 0.802036E+11 | 38252.27 | 22-FEB-17:00 | 38252.27 | 0.00 |
March | 0.00 | 0.00 | 0.144348E+12 | 0.144348E+12 | 58084.77 | 12-MAR-17:42 | 58084.77 | 0.00 |
April | 0.00 | 0.00 | 0.187104E+12 | 0.187104E+12 | 75399.19 | 16-APR-20:24 | 75399.19 | 0.00 |
May | 0.00 | 0.00 | 0.555412E+11 | 0.555412E+11 | 25578.37 | 29-MAY-17:59 | 25578.37 | 0.00 |
June | 0.00 | 0.00 | 0.990100E+11 | 0.990100E+11 | 42408.75 | 11-JUN-18:00 | 42408.75 | 0.00 |
July | 0.00 | 0.00 | 0.148424E+12 | 0.148424E+12 | 59574.98 | 02-JUL-18:05 | 59574.98 | 0.00 |
August | 0.00 | 0.00 | 0.193895E+12 | 0.193895E+12 | 74118.84 | 20-AUG-15:05 | 74118.84 | 0.00 |
September | 0.00 | 0.00 | 0.519852E+11 | 0.519852E+11 | 23790.50 | 17-SEP-18:17 | 23790.50 | 0.00 |
October | 0.00 | 0.00 | 0.997533E+11 | 0.997533E+11 | 41834.13 | 01-OCT-16:56 | 41834.13 | 0.00 |
November | 0.00 | 0.00 | 0.137033E+12 | 0.137033E+12 | 56209.03 | 12-NOV-16:33 | 56209.03 | 0.00 |
December | 0.00 | 0.00 | 0.179283E+12 | 0.179278E+12 | 72691.28 | 01-DEC-17:00 | 72691.28 | 0.00 |
Annual Sum or Average | 0.140874E+13 | 0.140873E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.321558E+11 | 0.321557E+11 | 19622.99 | 19622.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.193895E+12 | 0.193895E+12 | 75399.19 | 75399.19 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.206583E+10 | 0.206578E+10 | 1981.95 | 12-JAN-17:00 | 1981.95 | 0.00 |
February | 0.00 | 0.00 | 0.737767E+10 | 0.737767E+10 | 3884.19 | 22-FEB-17:00 | 3884.19 | 0.00 |
March | 0.00 | 0.00 | 0.142647E+11 | 0.142647E+11 | 6046.01 | 12-MAR-17:28 | 6046.01 | 0.00 |
April | 0.00 | 0.00 | 0.188069E+11 | 0.188069E+11 | 7754.16 | 16-APR-21:23 | 7754.16 | 0.00 |
May | 0.00 | 0.00 | 0.576488E+10 | 0.576488E+10 | 3021.77 | 29-MAY-18:08 | 3021.77 | 0.00 |
June | 0.00 | 0.00 | 0.100907E+11 | 0.100907E+11 | 4720.46 | 11-JUN-17:30 | 4720.46 | 0.00 |
July | 0.00 | 0.00 | 0.150440E+11 | 0.150440E+11 | 6402.24 | 02-JUL-17:55 | 6402.24 | 0.00 |
August | 0.00 | 0.00 | 0.195244E+11 | 0.195244E+11 | 7605.45 | 20-AUG-15:02 | 7605.45 | 0.00 |
September | 0.00 | 0.00 | 0.528419E+10 | 0.528419E+10 | 2650.33 | 17-SEP-17:53 | 2650.33 | 0.00 |
October | 0.00 | 0.00 | 0.989153E+10 | 0.989153E+10 | 4465.57 | 01-OCT-17:07 | 4465.57 | 0.00 |
November | 0.00 | 0.00 | 0.131934E+11 | 0.131934E+11 | 5662.02 | 09-NOV-16:40 | 5662.02 | 0.00 |
December | 0.00 | 0.00 | 0.167897E+11 | 0.167892E+11 | 7275.57 | 28-DEC-17:00 | 7275.57 | 0.00 |
Annual Sum or Average | 0.138098E+12 | 0.138097E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.206583E+10 | 0.206578E+10 | 1981.95 | 1981.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.195244E+11 | 0.195244E+11 | 7754.16 | 7754.16 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7418.93 | 38208.81 | 01-JAN-08:10 | 10317.75 | 41966.28 | 18-JAN-12:15 |
February | 7132.79 | 38309.87 | 26-FEB-08:20 | 10145.23 | 41717.64 | 01-FEB-12:15 |
March | 6043.63 | 38517.31 | 26-MAR-06:55 | 10055.07 | 39973.77 | 01-MAR-12:10 |
April | 7463.93 | 38838.62 | 30-APR-06:37 | 8092.29 | 36262.85 | 03-APR-11:30 |
May | 7723.74 | 39081.25 | 29-MAY-06:35 | 7218.89 | 32581.38 | 01-MAY-11:50 |
June | 7674.65 | 39231.54 | 25-JUN-06:40 | 6362.70 | 28912.26 | 01-JUN-12:00 |
July | 9873.34 | 39276.08 | 16-JUL-06:35 | 5237.81 | 26775.83 | 03-JUL-11:50 |
August | 7685.16 | 39250.36 | 06-AUG-06:34 | 6334.65 | 28531.55 | 31-AUG-11:10 |
September | 8114.68 | 39113.75 | 03-SEP-06:45 | 6670.26 | 31718.55 | 29-SEP-11:40 |
October | 8096.97 | 38890.25 | 01-OCT-06:43 | 7905.34 | 35948.38 | 31-OCT-11:10 |
November | 7847.96 | 38567.18 | 05-NOV-07:00 | 9236.85 | 39418.32 | 30-NOV-13:00 |
December | 7566.42 | 38345.46 | 03-DEC-08:70 | 9693.49 | 41513.68 | 29-DEC-12:40 |
Annual Sum or Average | 7724.41 | 8094.75 | ||||
Minimum of Months | 6043.63 | 38208.81 | 5237.81 | 26775.83 | ||
Maximum of Months | 9873.34 | 39276.08 | 10317.75 | 41966.28 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 13537.99 | 1116347.16 | 03-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2649.64 | 900209.61 | 11-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 574.94 | 254122.30 | 05-MAR-20:20 |
April | 0.00 | 0.00 | 01-APR-00:05 | 288.98 | 215123.62 | 02-APR-16:59 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 284.36 | 213378.15 | 07-MAY-20:58 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 211.43 | 211875.71 | 04-JUN-20:54 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 312.10 | 206018.25 | 04-JUL-07:45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 209.05 | 205490.91 | 06-AUG-02:28 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 374.50 | 206166.68 | 03-SEP-13:07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 402.24 | 214262.29 | 29-OCT-13:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 936.68 | 276471.36 | 26-NOV-11:46 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4999.35 | 748887.75 | 23-DEC-06:03 |
Annual Sum or Average | 0.00 | 2077.97 | ||||
Minimum of Months | 0.00 | 0.00 | 209.05 | 205490.91 | ||
Maximum of Months | 0.00 | 0.00 | 13537.99 | 1116347.16 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 127426.30 | 731916.77 | 25-JAN-14:40 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 236033.93 | 1240579.29 | 22-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 488154.48 | 1909521.02 | 29-MAR-11:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 789871.07 | 1986332.37 | 18-APR-15:30 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1106336.83 | 2763234.24 | 24-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1300955.82 | 3137368.70 | 11-JUN-12:22 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1377079.33 | 3194113.22 | 18-JUL-05:01 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1353881.27 | 2886103.14 | 06-AUG-01:41 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1092504.99 | 3264020.69 | 08-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 681994.35 | 2526663.91 | 04-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 393742.63 | 1820553.19 | 15-NOV-15:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 167795.23 | 894173.97 | 01-DEC-13:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 762476.40 | 0.00 | ||||
Minimum of Months | 127426.30 | 731916.77 | 0.00 | 0.00 | ||
Maximum of Months | 1377079.33 | 3264020.69 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 126260.15 | 762560.95 | 25-JAN-14:40 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 234962.27 | 1243100.50 | 22-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 489248.19 | 3359461.57 | 27-MAR-14:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 793700.25 | 3020431.01 | 18-APR-05:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1106268.12 | 3602485.14 | 23-MAY-03:01 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1298333.12 | 3814780.59 | 28-JUN-05:01 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1373336.26 | 3885510.22 | 28-JUL-03:01 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1352028.59 | 3799231.10 | 12-AUG-05:01 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1089999.72 | 4101937.21 | 11-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 685375.31 | 3061616.40 | 05-OCT-04:12 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 395440.83 | 2745068.48 | 02-NOV-15:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 166587.04 | 982956.98 | 01-DEC-13:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 762124.31 | 0.00 | ||||
Minimum of Months | 126260.15 | 762560.95 | 0.00 | 0.00 | ||
Maximum of Months | 1373336.26 | 4101937.21 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 201260.35 | 538711.37 | 12-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 460522.68 | 945090.90 | 22-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 901172.31 | 1667359.75 | 28-MAR-15:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1504897.89 | 2124922.48 | 15-APR-15:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1063237.61 | 1701845.50 | 03-MAY-15:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1331853.45 | 1962500.76 | 07-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1459390.17 | 1980918.45 | 02-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1574877.45 | 1976972.09 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 842882.27 | 1327260.91 | 17-SEP-20:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 845547.94 | 1487259.57 | 02-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 763053.06 | 1345110.31 | 04-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 735625.72 | 1239148.34 | 28-DEC-14:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 976410.12 | 0.00 | ||||
Minimum of Months | 201260.35 | 538711.37 | 0.00 | 0.00 | ||
Maximum of Months | 1574877.45 | 2124922.48 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 180685.79 | 970155.48 | 25-JAN-14:40 | 3397.29 | 115588.93 | 21-JAN-07:50 |
February | 332241.02 | 1680692.50 | 24-FEB-15:00 | 1230.10 | 104310.04 | 02-FEB-07:40 |
March | 711511.50 | 3688543.93 | 10-MAR-17:00 | 230.29 | 70084.97 | 20-MAR-01:20 |
April | 1398121.83 | 5721223.02 | 18-APR-14:40 | 121.45 | 26806.97 | 09-APR-22:10 |
May | 2879183.43 | 7440396.32 | 17-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 4093987.97 | 8657092.11 | 21-JUN-15:40 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 5003806.87 | 8290439.17 | 17-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 4978158.41 | 8656932.29 | 28-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3598509.80 | 8205531.33 | 14-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1248709.43 | 5183203.46 | 03-OCT-15:10 | 29.27 | 24686.43 | 31-OCT-03:25 |
November | 544875.12 | 2781910.97 | 06-NOV-13:05 | 581.61 | 94513.17 | 25-NOV-05:40 |
December | 235729.42 | 1134322.78 | 01-DEC-13:30 | 2111.33 | 123628.42 | 20-DEC-07:10 |
Annual Sum or Average | 2111613.48 | 642.05 | ||||
Minimum of Months | 180685.79 | 970155.48 | 0.00 | 0.00 | ||
Maximum of Months | 5003806.87 | 8657092.11 | 3397.29 | 123628.42 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150826E+11 | 0.87 | 9191.66 | 01-JAN-00:01 | 1.42 |
February | 0.134779E+11 | 0.86 | 9191.66 | 01-FEB-04:01 | 1.42 |
March | 0.154255E+11 | 0.89 | 9191.66 | 01-MAR-04:01 | 1.42 |
April | 0.149009E+11 | 0.88 | 9191.66 | 01-APR-03:01 | 1.42 |
May | 0.160691E+11 | 0.92 | 9191.66 | 01-MAY-00:10 | 1.42 |
June | 0.159295E+11 | 0.94 | 9191.66 | 01-JUN-03:01 | 1.41 |
July | 0.169121E+11 | 0.96 | 9191.66 | 01-JUL-03:01 | 1.41 |
August | 0.174333E+11 | 1.00 | 9191.66 | 01-AUG-03:01 | 1.41 |
September | 0.163150E+11 | 0.96 | 9191.66 | 01-SEP-03:01 | 1.41 |
October | 0.167248E+11 | 0.96 | 9191.66 | 01-OCT-05:07 | 1.41 |
November | 0.158207E+11 | 0.94 | 9191.66 | 01-NOV-03:01 | 1.42 |
December | 0.155330E+11 | 0.89 | 9191.66 | 01-DEC-04:01 | 1.42 |
Annual Sum or Average | 0.189624E+12 | 0.92 | |||
Minimum of Months | 0.134779E+11 | 0.86 | 9191.66 | 1.41 | |
Maximum of Months | 0.174333E+11 | 1.00 | 9191.66 | 1.42 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.329732E+10 | 0.30 | 8075.72 | 26-JAN-06:03 | 0.99 |
February | 0.381446E+10 | 0.35 | 11402.40 | 21-FEB-05:11 | 1.22 |
March | 0.616567E+10 | 0.46 | 21177.82 | 11-MAR-06:01 | 1.80 |
April | 0.830619E+10 | 0.58 | 21177.82 | 03-APR-05:02 | 1.80 |
May | 0.827225E+10 | 0.57 | 21177.82 | 01-MAY-04:22 | 1.80 |
June | 0.870256E+10 | 0.59 | 21177.82 | 01-JUN-05:01 | 1.80 |
July | 0.850446E+10 | 0.58 | 21177.82 | 01-JUL-05:01 | 1.80 |
August | 0.944501E+10 | 0.61 | 21177.82 | 01-AUG-05:01 | 1.80 |
September | 0.641995E+10 | 0.50 | 21177.82 | 01-SEP-05:01 | 1.80 |
October | 0.668533E+10 | 0.48 | 21177.82 | 04-OCT-05:01 | 1.80 |
November | 0.568134E+10 | 0.41 | 15769.88 | 06-NOV-06:01 | 1.49 |
December | 0.463832E+10 | 0.36 | 11402.40 | 04-DEC-06:01 | 1.23 |
Annual Sum or Average | 0.799329E+11 | 0.48 | |||
Minimum of Months | 0.329732E+10 | 0.30 | 8075.72 | 0.99 | |
Maximum of Months | 0.944501E+10 | 0.61 | 21177.82 | 1.80 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.235801E+11 | 0.28 | 87956.94 | 21-JAN-06:02 | 1.08 |
February | 0.260824E+11 | 0.30 | 79107.47 | 21-FEB-06:03 | 1.01 |
March | 0.435810E+11 | 0.37 | 201626.86 | 11-MAR-06:01 | 1.80 |
April | 0.589244E+11 | 0.48 | 201626.86 | 04-APR-03:01 | 1.80 |
May | 0.730638E+11 | 0.54 | 201626.86 | 03-MAY-05:01 | 1.80 |
June | 0.718006E+11 | 0.54 | 201626.86 | 01-JUN-03:01 | 1.80 |
July | 0.626710E+11 | 0.50 | 201626.86 | 06-JUL-05:01 | 1.80 |
August | 0.619577E+11 | 0.48 | 201626.86 | 01-AUG-05:01 | 1.80 |
September | 0.529442E+11 | 0.44 | 201626.86 | 02-SEP-05:01 | 1.80 |
October | 0.510201E+11 | 0.40 | 201626.86 | 02-OCT-04:11 | 1.80 |
November | 0.371599E+11 | 0.34 | 115118.81 | 06-NOV-06:01 | 1.27 |
December | 0.259546E+11 | 0.29 | 86786.56 | 21-DEC-06:03 | 1.07 |
Annual Sum or Average | 0.588740E+12 | 0.41 | |||
Minimum of Months | 0.235801E+11 | 0.28 | 79107.47 | 1.01 | |
Maximum of Months | 0.730638E+11 | 0.54 | 201626.86 | 1.80 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.245640E+10 | 0.31 | 4238.89 | 02-JAN-05:22 | 0.67 |
February | 0.249091E+10 | 0.31 | 5791.78 | 24-FEB-06:03 | 0.79 |
March | 0.428624E+10 | 0.36 | 22214.80 | 11-MAR-06:01 | 1.77 |
April | 0.646618E+10 | 0.48 | 22581.71 | 17-APR-05:01 | 1.79 |
May | 0.840048E+10 | 0.56 | 22581.71 | 03-MAY-05:01 | 1.79 |
June | 0.833662E+10 | 0.56 | 22581.71 | 26-JUN-05:02 | 1.79 |
July | 0.704213E+10 | 0.51 | 22581.71 | 03-JUL-05:01 | 1.79 |
August | 0.672738E+10 | 0.49 | 22581.71 | 02-AUG-05:01 | 1.79 |
September | 0.560032E+10 | 0.44 | 22581.71 | 07-SEP-03:01 | 1.79 |
October | 0.499657E+10 | 0.39 | 22581.71 | 04-OCT-05:01 | 1.79 |
November | 0.329788E+10 | 0.33 | 8063.97 | 09-NOV-06:03 | 0.95 |
December | 0.242797E+10 | 0.30 | 2826.22 | 01-DEC-15:00 | 0.56 |
Annual Sum or Average | 0.625291E+11 | 0.42 | |||
Minimum of Months | 0.242797E+10 | 0.30 | 2826.22 | 0.56 | |
Maximum of Months | 0.840048E+10 | 0.56 | 22581.71 | 1.79 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.961500E+11 | 1.38 | 35898.30 | 01-JAN-00:01 | 1.38 |
February | 0.868452E+11 | 1.38 | 35898.30 | 01-FEB-00:10 | 1.38 |
March | 0.961500E+11 | 1.38 | 35898.30 | 01-MAR-00:10 | 1.38 |
April | 0.930484E+11 | 1.38 | 35898.30 | 01-APR-00:05 | 1.38 |
May | 0.961500E+11 | 1.38 | 35898.30 | 01-MAY-00:10 | 1.38 |
June | 0.930484E+11 | 1.38 | 35898.30 | 01-JUN-00:03 | 1.38 |
July | 0.961500E+11 | 1.38 | 35898.30 | 01-JUL-00:05 | 1.38 |
August | 0.961500E+11 | 1.38 | 35898.30 | 01-AUG-00:03 | 1.38 |
September | 0.930484E+11 | 1.38 | 35898.30 | 01-SEP-00:05 | 1.38 |
October | 0.961500E+11 | 1.38 | 35898.30 | 01-OCT-00:05 | 1.38 |
November | 0.930484E+11 | 1.38 | 35898.30 | 01-NOV-00:10 | 1.38 |
December | 0.961500E+11 | 1.38 | 35898.30 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.113209E+13 | 1.38 | |||
Minimum of Months | 0.868452E+11 | 1.38 | 35898.30 | 1.38 | |
Maximum of Months | 0.961500E+11 | 1.38 | 35898.30 | 1.38 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143704E+10 | 0.94 | 536.53 | 01-JAN-00:01 | 0.94 |
February | 0.129797E+10 | 0.94 | 536.53 | 01-FEB-00:10 | 0.94 |
March | 0.143704E+10 | 0.94 | 536.53 | 01-MAR-00:10 | 0.94 |
April | 0.139068E+10 | 0.94 | 536.53 | 01-APR-00:05 | 0.94 |
May | 0.143704E+10 | 0.94 | 536.53 | 01-MAY-00:12 | 0.94 |
June | 0.139068E+10 | 0.94 | 536.53 | 01-JUN-00:03 | 0.94 |
July | 0.143704E+10 | 0.94 | 536.53 | 01-JUL-00:05 | 0.94 |
August | 0.143704E+10 | 0.94 | 536.53 | 01-AUG-00:03 | 0.94 |
September | 0.139068E+10 | 0.94 | 536.53 | 01-SEP-00:10 | 0.94 |
October | 0.143704E+10 | 0.94 | 536.53 | 01-OCT-00:05 | 0.94 |
November | 0.139068E+10 | 0.94 | 536.53 | 01-NOV-00:10 | 0.94 |
December | 0.143704E+10 | 0.94 | 536.53 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.169199E+11 | 0.94 | |||
Minimum of Months | 0.129797E+10 | 0.94 | 536.53 | 0.94 | |
Maximum of Months | 0.143704E+10 | 0.94 | 536.53 | 0.94 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137192E+11 | 0.94 | 5122.15 | 01-JAN-00:01 | 0.94 |
February | 0.123915E+11 | 0.94 | 5122.15 | 01-FEB-00:10 | 0.94 |
March | 0.137192E+11 | 0.94 | 5122.15 | 01-MAR-00:10 | 0.94 |
April | 0.132766E+11 | 0.94 | 5122.15 | 01-APR-00:05 | 0.94 |
May | 0.137192E+11 | 0.94 | 5122.15 | 01-MAY-00:10 | 0.94 |
June | 0.132766E+11 | 0.94 | 5122.15 | 01-JUN-00:03 | 0.94 |
July | 0.137192E+11 | 0.94 | 5122.15 | 01-JUL-00:05 | 0.94 |
August | 0.137192E+11 | 0.94 | 5122.15 | 01-AUG-00:03 | 0.94 |
September | 0.132766E+11 | 0.94 | 5122.15 | 01-SEP-00:05 | 0.94 |
October | 0.137192E+11 | 0.94 | 5122.15 | 01-OCT-00:05 | 0.94 |
November | 0.132766E+11 | 0.94 | 5122.15 | 01-NOV-00:10 | 0.94 |
December | 0.137192E+11 | 0.94 | 5122.15 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.161532E+12 | 0.94 | |||
Minimum of Months | 0.123915E+11 | 0.94 | 5122.15 | 0.94 | |
Maximum of Months | 0.137192E+11 | 0.94 | 5122.15 | 0.94 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137547E+10 | 0.94 | 513.54 | 01-JAN-00:01 | 0.94 |
February | 0.124236E+10 | 0.94 | 513.54 | 01-FEB-00:10 | 0.94 |
March | 0.137547E+10 | 0.94 | 513.54 | 01-MAR-00:10 | 0.94 |
April | 0.133110E+10 | 0.94 | 513.54 | 01-APR-00:05 | 0.94 |
May | 0.137547E+10 | 0.94 | 513.54 | 01-MAY-00:10 | 0.94 |
June | 0.133110E+10 | 0.94 | 513.54 | 01-JUN-00:03 | 0.94 |
July | 0.137547E+10 | 0.94 | 513.54 | 01-JUL-00:05 | 0.94 |
August | 0.137547E+10 | 0.94 | 513.54 | 01-AUG-00:07 | 0.94 |
September | 0.133110E+10 | 0.94 | 513.54 | 01-SEP-00:05 | 0.94 |
October | 0.137547E+10 | 0.94 | 513.54 | 01-OCT-00:05 | 0.94 |
November | 0.133110E+10 | 0.94 | 513.54 | 01-NOV-00:10 | 0.94 |
December | 0.137547E+10 | 0.94 | 513.54 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.161951E+11 | 0.94 | |||
Minimum of Months | 0.124236E+10 | 0.94 | 513.54 | 0.94 | |
Maximum of Months | 0.137547E+10 | 0.94 | 513.54 | 0.94 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.417514E+09 | 0.379520E+09 | 9181.50 | 02-JAN-06:03 | 8345.99 | 8345.99 | 68.49 | 18.70 |
February | 66046572.59 | 60036334.48 | 5675.67 | 11-FEB-06:03 | 5159.19 | 5159.19 | 57.16 | 8.66 |
March | 27804349.27 | 25274153.49 | 3942.77 | 19-MAR-20:00 | 3583.98 | 3583.98 | 72.68 | 5.45 |
April | 13822047.00 | 12564240.73 | 3942.79 | 30-APR-13:50 | 3583.99 | 3583.99 | 72.69 | 5.45 |
May | 14194444.64 | 12902750.18 | 3943.10 | 28-MAY-15:09 | 3584.28 | 3584.28 | 72.85 | 5.45 |
June | 10339432.11 | 9398543.79 | 3943.36 | 25-JUN-20:57 | 3584.52 | 3584.52 | 72.98 | 5.45 |
July | 16078082.23 | 14614976.75 | 3943.55 | 16-JUL-07:07 | 3584.68 | 3584.68 | 73.08 | 5.45 |
August | 10805262.71 | 9821983.81 | 3943.58 | 20-AUG-13:00 | 3584.72 | 3584.72 | 73.09 | 5.45 |
September | 18692136.47 | 16991152.06 | 3943.59 | 17-SEP-10:05 | 3584.73 | 3584.73 | 73.10 | 5.45 |
October | 19990097.89 | 18170998.98 | 3943.36 | 01-OCT-05:07 | 3584.51 | 3584.51 | 72.98 | 5.45 |
November | 43443233.02 | 39489898.81 | 3942.69 | 05-NOV-09:30 | 3583.91 | 3583.91 | 72.64 | 5.45 |
December | 0.153237E+09 | 0.139292E+09 | 5315.31 | 23-DEC-06:03 | 4831.62 | 4831.62 | 59.46 | 7.94 |
Annual Sum or Average | 0.811966E+09 | 0.738077E+09 | ||||||
Minimum of Months | 10339432.11 | 9398543.79 | 3942.69 | 3583.91 | 3583.91 | 57.16 | 5.45 | |
Maximum of Months | 0.417514E+09 | 0.379520E+09 | 9181.50 | 8345.99 | 8345.99 | 73.10 | 18.70 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.156197E+09 | 0.141983E+09 | 768.08 | 25-JAN-15:05 | 698.19 | 698.19 | 6.71 | 21.97 |
February | 0.381654E+09 | 0.346924E+09 | 1805.77 | 22-FEB-15:30 | 1641.45 | 1641.45 | 6.71 | 32.35 |
March | 0.127184E+10 | 0.115610E+10 | 14251.43 | 27-MAR-14:50 | 12954.55 | 12954.55 | 11.80 | 76.05 |
April | 0.225583E+10 | 0.205055E+10 | 13159.58 | 18-APR-05:02 | 11962.06 | 11962.06 | 9.51 | 73.72 |
May | 0.329158E+10 | 0.299205E+10 | 14655.69 | 11-MAY-05:02 | 13322.02 | 13322.02 | 10.10 | 76.92 |
June | 0.403286E+10 | 0.366587E+10 | 14655.69 | 12-JUN-05:03 | 13322.02 | 13322.02 | 10.94 | 76.92 |
July | 0.439026E+10 | 0.399075E+10 | 14597.52 | 11-JUL-05:02 | 13269.14 | 13269.14 | 7.24 | 76.79 |
August | 0.447879E+10 | 0.407122E+10 | 14655.69 | 04-AUG-05:01 | 13322.02 | 13322.02 | 10.13 | 76.92 |
September | 0.312580E+10 | 0.284135E+10 | 14655.69 | 07-SEP-03:01 | 13322.02 | 13322.02 | 8.97 | 76.92 |
October | 0.190682E+10 | 0.173330E+10 | 13858.13 | 05-OCT-04:12 | 12597.04 | 12597.04 | 9.49 | 75.24 |
November | 0.102571E+10 | 0.932372E+09 | 13614.87 | 02-NOV-15:10 | 12375.92 | 12375.92 | 11.28 | 74.70 |
December | 0.252818E+09 | 0.229812E+09 | 1347.78 | 01-DEC-14:00 | 1225.13 | 1225.13 | 6.71 | 28.41 |
Annual Sum or Average | 0.265702E+11 | 0.241523E+11 | ||||||
Minimum of Months | 0.156197E+09 | 0.141983E+09 | 768.08 | 698.19 | 698.19 | 6.71 | 21.97 | |
Maximum of Months | 0.447879E+10 | 0.407122E+10 | 14655.69 | 13322.02 | 13322.02 | 11.80 | 76.92 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871592.27 | 56.21 | 01-JAN-06:10 | 16.86 | 16.86 | 71.33 | 0.44 |
February | 0.101979E+09 | 30593696.24 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 67.46 | 0.44 |
March | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 65.79 | 0.44 |
April | 0.109263E+09 | 32778960.26 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 68.14 | 0.44 |
May | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 80.14 | 0.44 |
June | 0.109263E+09 | 32778960.26 | 56.21 | 01-JUN-05:01 | 16.86 | 16.86 | 65.90 | 0.44 |
July | 0.112905E+09 | 33871592.27 | 56.21 | 01-JUL-05:01 | 16.86 | 16.86 | 64.94 | 0.44 |
August | 0.112905E+09 | 33871592.27 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 65.87 | 0.44 |
September | 0.109263E+09 | 32778960.26 | 56.21 | 01-SEP-05:01 | 16.86 | 16.86 | 64.83 | 0.44 |
October | 0.112905E+09 | 33871592.27 | 56.21 | 01-OCT-05:03 | 16.86 | 16.86 | 65.02 | 0.44 |
November | 0.109263E+09 | 32778960.26 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 68.73 | 0.44 |
December | 0.112905E+09 | 33871592.27 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 67.67 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398811E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593696.24 | 56.21 | 16.86 | 16.86 | 64.83 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871592.27 | 56.21 | 16.86 | 16.86 | 80.14 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.370344E+10 | 0.336643E+10 | 2428.29 | 01-JAN-00:01 | 2207.31 | 2207.31 | 7.07 | 38.46 |
February | 0.361289E+10 | 0.328411E+10 | 2428.29 | 01-FEB-04:01 | 2207.31 | 2207.31 | 6.99 | 38.46 |
March | 0.493404E+10 | 0.448504E+10 | 2428.29 | 01-MAR-04:01 | 2207.31 | 2207.31 | 8.08 | 38.46 |
April | 0.587483E+10 | 0.534022E+10 | 2428.29 | 01-APR-00:05 | 2207.31 | 2207.31 | 6.90 | 38.46 |
May | 0.601242E+10 | 0.546529E+10 | 2428.29 | 01-MAY-00:10 | 2207.31 | 2207.31 | 10.27 | 38.46 |
June | 0.581436E+10 | 0.528525E+10 | 2428.29 | 01-JUN-00:03 | 2207.31 | 2207.31 | 7.15 | 38.46 |
July | 0.617609E+10 | 0.561407E+10 | 2428.29 | 01-JUL-00:05 | 2207.31 | 2207.31 | 13.58 | 38.46 |
August | 0.622577E+10 | 0.565923E+10 | 2428.29 | 01-AUG-00:03 | 2207.31 | 2207.31 | 13.84 | 38.46 |
September | 0.545636E+10 | 0.495983E+10 | 2428.29 | 01-SEP-00:05 | 2207.31 | 2207.31 | 9.86 | 38.46 |
October | 0.516195E+10 | 0.469221E+10 | 2428.29 | 01-OCT-00:05 | 2207.31 | 2207.31 | 11.63 | 38.46 |
November | 0.436667E+10 | 0.396930E+10 | 2428.29 | 01-NOV-03:01 | 2207.31 | 2207.31 | 9.54 | 38.46 |
December | 0.397615E+10 | 0.361432E+10 | 2428.29 | 01-DEC-04:01 | 2207.31 | 2207.31 | 7.68 | 38.46 |
Annual Sum or Average | 0.613150E+11 | 0.557353E+11 | ||||||
Minimum of Months | 0.361289E+10 | 0.328411E+10 | 2428.29 | 2207.31 | 2207.31 | 6.90 | 38.46 | |
Maximum of Months | 0.622577E+10 | 0.565923E+10 | 2428.29 | 2207.31 | 2207.31 | 13.84 | 38.46 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 7.07 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.83 | 0.00 |
March | 0.448748E+09 | 0.407912E+09 | 2428.29 | 06-MAR-13:05 | 2207.31 | 2207.31 | 11.05 | 38.46 |
April | 0.144595E+10 | 0.131437E+10 | 2428.29 | 01-APR-14:30 | 2207.31 | 2207.31 | 14.92 | 19.23 |
May | 0.287212E+10 | 0.261076E+10 | 2428.29 | 01-MAY-07:10 | 2207.31 | 2207.31 | 15.23 | 19.23 |
June | 0.352674E+10 | 0.320581E+10 | 2428.29 | 01-JUN-07:10 | 2207.31 | 2207.31 | 16.01 | 19.23 |
July | 0.398238E+10 | 0.361998E+10 | 2428.29 | 01-JUL-04:05 | 2207.31 | 2207.31 | 15.12 | 19.23 |
August | 0.403734E+10 | 0.366994E+10 | 2428.29 | 01-AUG-04:05 | 2207.31 | 2207.31 | 11.59 | 38.46 |
September | 0.306579E+10 | 0.278680E+10 | 2428.29 | 01-SEP-04:05 | 2207.31 | 2207.31 | 15.62 | 19.23 |
October | 0.131943E+10 | 0.119937E+10 | 2428.29 | 02-OCT-07:50 | 2207.31 | 2207.31 | 15.39 | 19.23 |
November | 0.259341E+09 | 0.235741E+09 | 2428.29 | 01-NOV-12:40 | 2207.31 | 2207.31 | 15.26 | 19.23 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 7.58 | 0.00 |
Annual Sum or Average | 0.209578E+11 | 0.190507E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 0.00 | |
Maximum of Months | 0.403734E+10 | 0.366994E+10 | 2428.29 | 2207.31 | 2207.31 | 16.01 | 38.46 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.922535E+10 | 0.838584E+10 | 3444.35 | 01-JAN-00:01 | 3130.91 | 3130.91 | 21.33 | 14.53 |
February | 0.833257E+10 | 0.757431E+10 | 3444.35 | 01-FEB-00:10 | 3130.91 | 3130.91 | 23.95 | 14.53 |
March | 0.922535E+10 | 0.838584E+10 | 3444.35 | 01-MAR-00:10 | 3130.91 | 3130.91 | 27.83 | 14.53 |
April | 0.892776E+10 | 0.811533E+10 | 3444.35 | 01-APR-00:05 | 3130.91 | 3130.91 | 39.93 | 14.53 |
May | 0.922535E+10 | 0.838584E+10 | 3444.35 | 01-MAY-00:10 | 3130.91 | 3130.91 | 39.46 | 14.53 |
June | 0.892776E+10 | 0.811533E+10 | 3444.35 | 01-JUN-00:03 | 3130.91 | 3130.91 | 36.27 | 14.53 |
July | 0.922535E+10 | 0.838584E+10 | 3444.35 | 01-JUL-00:05 | 3130.91 | 3130.91 | 46.36 | 14.53 |
August | 0.922535E+10 | 0.838584E+10 | 3444.35 | 01-AUG-00:03 | 3130.91 | 3130.91 | 46.14 | 14.53 |
September | 0.892776E+10 | 0.811533E+10 | 3444.35 | 01-SEP-00:05 | 3130.91 | 3130.91 | 39.42 | 14.53 |
October | 0.922535E+10 | 0.838584E+10 | 3444.35 | 01-OCT-00:05 | 3130.91 | 3130.91 | 35.18 | 14.53 |
November | 0.892776E+10 | 0.811533E+10 | 3444.35 | 01-NOV-00:10 | 3130.91 | 3130.91 | 30.23 | 14.53 |
December | 0.922535E+10 | 0.838584E+10 | 3444.35 | 01-DEC-00:10 | 3130.91 | 3130.91 | 29.50 | 14.53 |
Annual Sum or Average | 0.108621E+12 | 0.987365E+11 | ||||||
Minimum of Months | 0.833257E+10 | 0.757431E+10 | 3444.35 | 3130.91 | 3130.91 | 21.33 | 14.53 | |
Maximum of Months | 0.922535E+10 | 0.838584E+10 | 3444.35 | 3130.91 | 3130.91 | 46.36 | 14.53 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.214979E+11 | 0.195416E+11 | 14119.52 | 25-JAN-14:40 | 12834.64 | 12834.64 | 24.54 | 67.45 |
February | 0.209845E+11 | 0.190749E+11 | 14148.66 | 24-FEB-15:00 | 12861.13 | 12861.13 | 27.06 | 67.45 |
March | 0.310421E+11 | 0.282173E+11 | 28311.12 | 10-MAR-17:00 | 25734.81 | 25734.81 | 27.64 | 134.89 |
April | 0.420420E+11 | 0.382161E+11 | 28338.84 | 16-APR-15:01 | 25760.00 | 25760.00 | 28.94 | 134.89 |
May | 0.511738E+11 | 0.465170E+11 | 28338.84 | 01-MAY-09:50 | 25760.00 | 25760.00 | 28.98 | 134.89 |
June | 0.538006E+11 | 0.489047E+11 | 28338.84 | 02-JUN-15:50 | 25760.00 | 25760.00 | 28.84 | 134.89 |
July | 0.590369E+11 | 0.536645E+11 | 28338.84 | 01-JUL-04:15 | 25760.00 | 25760.00 | 30.10 | 134.89 |
August | 0.596357E+11 | 0.542089E+11 | 28338.84 | 01-AUG-04:05 | 25760.00 | 25760.00 | 30.94 | 134.89 |
September | 0.489631E+11 | 0.445075E+11 | 28338.84 | 01-SEP-04:05 | 25760.00 | 25760.00 | 29.29 | 134.89 |
October | 0.369706E+11 | 0.336062E+11 | 28338.84 | 02-OCT-15:40 | 25760.00 | 25760.00 | 28.84 | 134.89 |
November | 0.266637E+11 | 0.242373E+11 | 28272.96 | 06-NOV-13:05 | 25700.12 | 25700.12 | 26.03 | 134.89 |
December | 0.230851E+11 | 0.209843E+11 | 14125.65 | 01-DEC-13:30 | 12840.22 | 12840.22 | 25.12 | 67.45 |
Annual Sum or Average | 0.474896E+12 | 0.431680E+12 | ||||||
Minimum of Months | 0.209845E+11 | 0.190749E+11 | 14119.52 | 12834.64 | 12834.64 | 24.54 | 67.45 | |
Maximum of Months | 0.596357E+11 | 0.542089E+11 | 28338.84 | 25760.00 | 25760.00 | 30.94 | 134.89 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7418.93 | 38208.81 | 01-JAN-08:10 | 80.68 | 82.22 | 10317.75 | 41966.28 | 18-JAN-12:15 |
February | 7132.79 | 38309.87 | 26-FEB-08:20 | 80.73 | 82.22 | 10145.23 | 41717.64 | 01-FEB-12:15 |
March | 6043.63 | 38517.31 | 26-MAR-06:55 | 80.84 | 82.22 | 10055.07 | 39973.77 | 01-MAR-12:10 |
April | 7463.93 | 38838.62 | 30-APR-06:37 | 81.02 | 82.22 | 8092.29 | 36262.85 | 03-APR-11:30 |
May | 7723.74 | 39081.25 | 29-MAY-06:35 | 81.15 | 82.22 | 7218.89 | 32581.38 | 01-MAY-11:50 |
June | 7674.65 | 39231.54 | 25-JUN-06:40 | 81.23 | 82.22 | 6362.70 | 28912.26 | 01-JUN-12:00 |
July | 9873.34 | 39276.08 | 16-JUL-06:35 | 81.25 | 82.22 | 5237.81 | 26775.83 | 03-JUL-11:50 |
August | 7685.16 | 39250.36 | 06-AUG-06:34 | 81.24 | 82.22 | 6334.65 | 28531.55 | 31-AUG-11:10 |
September | 8114.68 | 39113.75 | 03-SEP-06:45 | 81.16 | 82.22 | 6670.26 | 31718.55 | 29-SEP-11:40 |
October | 8096.97 | 38890.25 | 01-OCT-06:43 | 81.04 | 82.22 | 7905.34 | 35948.38 | 31-OCT-11:10 |
November | 7847.96 | 38567.18 | 05-NOV-07:00 | 80.87 | 82.22 | 9236.85 | 39418.32 | 30-NOV-13:00 |
December | 7566.42 | 38345.46 | 03-DEC-08:70 | 80.75 | 82.22 | 9693.49 | 41513.68 | 29-DEC-12:40 |
Annual Sum or Average | 7724.41 | 8094.75 | ||||||
Minimum of Months | 6043.63 | 38208.81 | 80.68 | 82.22 | 5237.81 | 26775.83 | ||
Maximum of Months | 9873.34 | 39276.08 | 81.25 | 82.22 | 10317.75 | 41966.28 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 72.54 | 72.54 | 13537.99 | 1116347.16 | 03-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 63.95 | 63.95 | 2649.64 | 900209.61 | 11-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 70.75 | 70.75 | 574.94 | 254122.30 | 05-MAR-20:20 |
April | 0.00 | 0.00 | 01-APR-00:05 | 72.58 | 72.58 | 288.98 | 215123.62 | 02-APR-16:59 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 72.67 | 72.67 | 284.36 | 213378.15 | 07-MAY-20:58 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 72.75 | 72.75 | 211.43 | 211875.71 | 04-JUN-20:54 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 73.00 | 73.00 | 312.10 | 206018.25 | 04-JUL-07:45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 73.01 | 73.01 | 209.05 | 205490.91 | 06-AUG-02:28 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 73.08 | 73.08 | 374.50 | 206166.68 | 03-SEP-13:07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 73.01 | 73.01 | 402.24 | 214262.29 | 29-OCT-13:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 72.65 | 72.65 | 936.68 | 276471.36 | 26-NOV-11:46 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 67.02 | 67.02 | 4999.35 | 748887.75 | 23-DEC-06:03 |
Annual Sum or Average | 0.00 | 2077.97 | ||||||
Minimum of Months | 0.00 | 0.00 | 63.95 | 63.95 | 209.05 | 205490.91 | ||
Maximum of Months | 0.00 | 0.00 | 73.08 | 73.08 | 13537.99 | 1116347.16 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 127426.30 | 731916.77 | 25-JAN-14:40 | 11.24 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 236033.93 | 1240579.29 | 22-FEB-15:30 | 14.41 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 488154.48 | 1909521.02 | 29-MAR-11:05 | 12.63 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 789871.07 | 1986332.37 | 18-APR-15:30 | 12.87 | 6.70 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1106336.83 | 2763234.24 | 24-MAY-05:02 | 15.28 | 6.78 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1300955.82 | 3137368.70 | 11-JUN-12:22 | 16.45 | 7.94 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1377079.33 | 3194113.22 | 18-JUL-05:01 | 16.63 | 8.12 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1353881.27 | 2886103.14 | 06-AUG-01:41 | 15.67 | 7.16 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1092504.99 | 3264020.69 | 08-SEP-03:02 | 16.84 | 8.34 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 681994.35 | 2526663.91 | 04-OCT-05:02 | 14.55 | 6.70 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 393742.63 | 1820553.19 | 15-NOV-15:05 | 12.35 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 167795.23 | 894173.97 | 01-DEC-13:10 | 12.25 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 762476.40 | 0.00 | ||||||
Minimum of Months | 127426.30 | 731916.77 | 11.24 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1377079.33 | 3264020.69 | 16.84 | 8.34 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 126260.15 | 762560.95 | 25-JAN-14:40 | 15.13 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 234962.27 | 1243100.50 | 22-FEB-15:30 | 15.88 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 489248.19 | 3359461.57 | 27-MAR-14:50 | 17.26 | 12.12 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 793700.25 | 3020431.01 | 18-APR-05:02 | 16.49 | 11.37 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1106268.12 | 3602485.14 | 23-MAY-03:01 | 19.06 | 12.22 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1298333.12 | 3814780.59 | 28-JUN-05:01 | 18.58 | 12.61 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1373336.26 | 3885510.22 | 28-JUL-03:01 | 19.27 | 12.71 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1352028.59 | 3799231.10 | 12-AUG-05:01 | 18.55 | 6.71 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1089999.72 | 4101937.21 | 11-SEP-03:02 | 19.45 | 13.06 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 685375.31 | 3061616.40 | 05-OCT-04:12 | 16.43 | 11.44 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 395440.83 | 2745068.48 | 02-NOV-15:10 | 15.48 | 11.29 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 166587.04 | 982956.98 | 01-DEC-13:10 | 16.04 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 762124.31 | 0.00 | ||||||
Minimum of Months | 126260.15 | 762560.95 | 15.13 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1373336.26 | 4101937.21 | 19.45 | 13.06 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 201260.35 | 538711.37 | 12-JAN-15:00 | 28.93 | 25.30 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 460522.68 | 945090.90 | 22-FEB-15:00 | 36.79 | 30.22 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 901172.31 | 1667359.75 | 28-MAR-15:10 | 50.47 | 40.45 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1504897.89 | 2124922.48 | 15-APR-15:00 | 58.97 | 46.46 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1063237.61 | 1701845.50 | 03-MAY-15:10 | 51.12 | 46.64 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1331853.45 | 1962500.76 | 07-JUN-16:00 | 55.97 | 48.34 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1459390.17 | 1980918.45 | 02-JUL-16:10 | 56.31 | 45.63 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1574877.45 | 1976972.09 | 07-AUG-15:00 | 56.24 | 43.53 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 842882.27 | 1327260.91 | 17-SEP-20:00 | 44.07 | 39.64 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 845547.94 | 1487259.57 | 02-OCT-15:00 | 47.09 | 39.89 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 763053.06 | 1345110.31 | 04-NOV-14:00 | 44.41 | 34.89 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 735625.72 | 1239148.34 | 28-DEC-14:10 | 42.40 | 30.36 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 976410.12 | 0.00 | ||||||
Minimum of Months | 201260.35 | 538711.37 | 28.93 | 25.30 | 0.00 | 0.00 | ||
Maximum of Months | 1574877.45 | 2124922.48 | 58.97 | 48.34 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 180685.79 | 970155.48 | 25-JAN-14:40 | 24.54 | 21.67 | 3397.29 | 115588.93 | 21-JAN-07:50 |
February | 332241.02 | 1680692.50 | 24-FEB-15:00 | 27.06 | 21.55 | 1230.10 | 104310.04 | 02-FEB-07:40 |
March | 711511.50 | 3688543.93 | 10-MAR-17:00 | 27.64 | 24.54 | 230.29 | 70084.97 | 20-MAR-01:20 |
April | 1398121.83 | 5721223.02 | 18-APR-14:40 | 31.25 | 27.18 | 121.45 | 26806.97 | 09-APR-22:10 |
May | 2879183.43 | 7440396.32 | 17-MAY-16:00 | 34.30 | 29.61 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 4093987.97 | 8657092.11 | 21-JUN-15:40 | 36.45 | 30.99 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 5003806.87 | 8290439.17 | 17-JUL-16:00 | 35.80 | 30.72 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 4978158.41 | 8656932.29 | 28-AUG-15:30 | 36.45 | 30.99 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3598509.80 | 8205531.33 | 14-SEP-15:30 | 35.65 | 30.66 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1248709.43 | 5183203.46 | 03-OCT-15:10 | 30.29 | 26.36 | 29.27 | 24686.43 | 31-OCT-03:25 |
November | 544875.12 | 2781910.97 | 06-NOV-13:05 | 26.03 | 22.60 | 581.61 | 94513.17 | 25-NOV-05:40 |
December | 235729.42 | 1134322.78 | 01-DEC-13:30 | 25.12 | 21.77 | 2111.33 | 123628.42 | 20-DEC-07:10 |
Annual Sum or Average | 2111613.48 | 642.05 | ||||||
Minimum of Months | 180685.79 | 970155.48 | 24.54 | 21.55 | 0.00 | 0.00 | ||
Maximum of Months | 5003806.87 | 8657092.11 | 36.45 | 30.99 | 3397.29 | 123628.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.64 | 2.91 |
February | 0.65 | 7.00 |
March | 1.22 | 5.95 |
April | 0.46 | 7.48 |
May | 0.57 | 8.14 |
June | 0.12 | 12.47 |
July | 0.48 | 7.48 |
August | 0.48 | 7.48 |
September | 0.78 | 7.48 |
October | 1.04 | 7.48 |
November | 1.14 | 6.93 |
December | 2.21 | 6.95 |
Annual Sum or Average | 9.80 | 6.88 |
Minimum of Months | 0.12 | 2.91 |
Maximum of Months | 2.21 | 12.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.42 | 11.06 |
February | 1.42 | 5.66 |
March | 5.40 | 2.97 |
April | 4.24 | 1.43 |
May | 2.68 | 1.60 |
June | 4.44 | 1.55 |
July | 2.75 | 0.68 |
August | 2.53 | 0.66 |
September | 10.16 | 2.14 |
October | 7.77 | 2.42 |
November | 2.26 | 2.10 |
December | 1.26 | 3.17 |
Annual Sum or Average | 46.33 | 2.37 |
Minimum of Months | 1.26 | 0.66 |
Maximum of Months | 10.16 | 11.06 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.56 | 11.76 |
February | 1.39 | 11.15 |
March | 2.03 | 5.15 |
April | 7.29 | 1.83 |
May | 2.81 | 1.79 |
June | 1.44 | 1.81 |
July | 3.66 | 2.72 |
August | 6.26 | 2.07 |
September | 6.84 | 2.52 |
October | 3.49 | 0.83 |
November | 1.99 | 8.22 |
December | 1.17 | 9.12 |
Annual Sum or Average | 38.92 | 3.17 |
Minimum of Months | 0.56 | 0.83 |
Maximum of Months | 7.29 | 11.76 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.67 | 11.76 |
February | 1.29 | 12.35 |
March | 2.56 | 7.52 |
April | 5.99 | 1.64 |
May | 3.62 | 1.37 |
June | 2.59 | 1.88 |
July | 4.39 | 1.54 |
August | 7.69 | 2.04 |
September | 6.66 | 2.08 |
October | 2.25 | 4.40 |
November | 1.47 | 10.90 |
December | 0.72 | 12.14 |
Annual Sum or Average | 39.90 | 3.35 |
Minimum of Months | 0.67 | 1.37 |
Maximum of Months | 7.69 | 12.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.14 | 0.34 |
February | 0.56 | 0.59 |
March | 3.07 | 0.30 |
April | 4.32 | 0.04 |
May | 5.54 | 0.17 |
June | 2.72 | 0.19 |
July | 3.22 | 0.14 |
August | 3.42 | 0.00 |
September | 11.79 | 0.24 |
October | 4.56 | 0.15 |
November | 0.94 | 0.00 |
December | 0.25 | 0.56 |
Annual Sum or Average | 40.53 | 0.17 |
Minimum of Months | 0.14 | 0.00 |
Maximum of Months | 11.79 | 0.59 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.19 | 0.31 |
February | 0.75 | 0.38 |
March | 3.41 | 0.15 |
April | 5.49 | 0.01 |
May | 6.32 | 0.09 |
June | 2.33 | 0.15 |
July | 2.64 | 0.04 |
August | 3.53 | 0.06 |
September | 11.66 | 0.13 |
October | 4.64 | 0.10 |
November | 1.28 | 0.12 |
December | 0.44 | 0.44 |
Annual Sum or Average | 42.68 | 0.11 |
Minimum of Months | 0.19 | 0.01 |
Maximum of Months | 11.66 | 0.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.31 | 0.84 |
February | 0.81 | 0.61 |
March | 4.08 | 0.29 |
April | 5.35 | 0.05 |
May | 5.32 | 0.16 |
June | 2.83 | 0.19 |
July | 1.47 | 0.21 |
August | 3.58 | 0.02 |
September | 11.86 | 0.18 |
October | 6.34 | 0.29 |
November | 1.75 | 0.20 |
December | 0.78 | 0.69 |
Annual Sum or Average | 44.47 | 0.20 |
Minimum of Months | 0.31 | 0.02 |
Maximum of Months | 11.86 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.28 | 0.38 |
February | 0.89 | 0.46 |
March | 5.34 | 0.22 |
April | 0.68 | 0.21 |
May | 3.00 | 0.14 |
June | 1.94 | 0.19 |
July | 1.82 | 0.16 |
August | 0.70 | 0.35 |
September | 11.64 | 0.14 |
October | 5.98 | 0.14 |
November | 1.67 | 0.16 |
December | 0.72 | 0.36 |
Annual Sum or Average | 34.66 | 0.18 |
Minimum of Months | 0.28 | 0.14 |
Maximum of Months | 11.64 | 0.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.76 | 0.37 |
April | 6.93 | 0.21 |
May | 6.17 | 0.19 |
June | 3.32 | 0.24 |
July | 4.92 | 0.32 |
August | 7.72 | 0.26 |
September | 7.34 | 0.34 |
October | 1.67 | 0.04 |
November | 0.35 | 0.44 |
December | 0.17 | 0.84 |
Annual Sum or Average | 39.36 | 0.26 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.72 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.17 | 0.54 |
March | 0.72 | 0.30 |
April | 7.79 | 0.14 |
May | 4.76 | 0.16 |
June | 4.23 | 0.13 |
July | 4.39 | 0.19 |
August | 7.86 | 0.15 |
September | 7.51 | 0.20 |
October | 1.89 | 0.05 |
November | 0.83 | 0.38 |
December | 0.28 | 0.54 |
Annual Sum or Average | 40.44 | 0.17 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.86 | 0.54 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.61 | 0.96 |
February | 0.19 | 1.20 |
March | 0.87 | 0.51 |
April | 8.12 | 0.22 |
May | 6.20 | 0.19 |
June | 3.57 | 0.23 |
July | 5.22 | 0.31 |
August | 7.74 | 0.26 |
September | 8.16 | 0.32 |
October | 2.70 | 0.34 |
November | 0.73 | 0.32 |
December | 0.72 | 0.84 |
Annual Sum or Average | 44.85 | 0.29 |
Minimum of Months | 0.19 | 0.19 |
Maximum of Months | 8.16 | 1.20 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 0.82 |
February | 0.25 | 0.36 |
March | 1.33 | 0.41 |
April | 5.66 | 0.20 |
May | 5.38 | 0.11 |
June | 4.31 | 0.18 |
July | 4.48 | 0.25 |
August | 7.90 | 0.19 |
September | 8.43 | 0.19 |
October | 3.37 | 0.25 |
November | 0.64 | 0.15 |
December | 0.22 | 0.54 |
Annual Sum or Average | 42.12 | 0.20 |
Minimum of Months | 0.17 | 0.11 |
Maximum of Months | 8.43 | 0.82 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.04 | 0.00 |
February | 0.08 | 1.69 |
March | 1.65 | 0.86 |
April | 6.37 | 0.19 |
May | 7.73 | 0.17 |
June | 4.52 | 0.18 |
July | 4.62 | 0.29 |
August | 9.41 | 0.32 |
September | 7.01 | 0.24 |
October | 1.39 | 0.89 |
November | 0.54 | 1.23 |
December | 0.17 | 0.84 |
Annual Sum or Average | 43.54 | 0.30 |
Minimum of Months | 0.04 | 0.00 |
Maximum of Months | 9.41 | 1.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.21 | 0.43 |
February | 0.18 | 0.79 |
March | 1.94 | 0.59 |
April | 6.64 | 0.14 |
May | 4.77 | 0.15 |
June | 3.56 | 0.17 |
July | 3.56 | 0.26 |
August | 8.55 | 0.20 |
September | 7.47 | 0.16 |
October | 1.44 | 0.51 |
November | 0.73 | 0.73 |
December | 0.14 | 0.54 |
Annual Sum or Average | 39.19 | 0.22 |
Minimum of Months | 0.14 | 0.14 |
Maximum of Months | 8.55 | 0.79 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.84 |
February | 0.44 | 1.16 |
March | 1.91 | 0.81 |
April | 6.91 | 0.25 |
May | 6.34 | 0.17 |
June | 4.49 | 0.19 |
July | 4.29 | 0.30 |
August | 8.77 | 0.32 |
September | 8.13 | 0.27 |
October | 2.19 | 0.58 |
November | 1.14 | 1.07 |
December | 0.25 | 0.84 |
Annual Sum or Average | 44.94 | 0.33 |
Minimum of Months | 0.08 | 0.17 |
Maximum of Months | 8.77 | 1.16 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.22 | 0.75 |
March | 1.91 | 0.53 |
April | 5.00 | 0.21 |
May | 4.49 | 0.14 |
June | 2.95 | 0.17 |
July | 3.23 | 0.30 |
August | 8.34 | 0.24 |
September | 7.99 | 0.18 |
October | 2.13 | 0.41 |
November | 0.74 | 0.75 |
December | 0.11 | 0.54 |
Annual Sum or Average | 37.11 | 0.25 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 8.34 | 0.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.252244E+10 | 0.00 | 0.513482E+11 | 0.150826E+11 | 0.00 | 0.00 |
February | 0.112118E+10 | 0.00 | 0.529643E+11 | 0.134779E+11 | 0.00 | 0.00 |
March | 0.153976E+10 | 0.00 | 0.751096E+11 | 0.154255E+11 | 0.00 | 0.00 |
April | 0.761638E+09 | 0.00 | 0.884959E+11 | 0.149009E+11 | 0.00 | 0.00 |
May | 0.774754E+09 | 0.00 | 0.114756E+12 | 0.160691E+11 | 0.00 | 0.00 |
June | 0.554940E+09 | 0.00 | 0.134895E+12 | 0.159295E+11 | 0.00 | 0.00 |
July | 0.851813E+09 | 0.00 | 0.158483E+12 | 0.169121E+11 | 0.00 | 0.00 |
August | 0.569596E+09 | 0.00 | 0.173444E+12 | 0.174333E+11 | 0.00 | 0.00 |
September | 0.990280E+09 | 0.00 | 0.137059E+12 | 0.163150E+11 | 0.00 | 0.00 |
October | 0.110232E+10 | 0.00 | 0.995298E+11 | 0.167248E+11 | 0.00 | 0.00 |
November | 0.233749E+10 | 0.00 | 0.766402E+11 | 0.158207E+11 | 0.00 | 0.00 |
December | 0.318230E+10 | 0.00 | 0.602384E+11 | 0.155330E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.163085E+11 | 0.00 | 0.122296E+13 | 0.189624E+12 | 0.00 | 0.00 |
Minimum of Months | 0.554940E+09 | 0.00 | 0.513482E+11 | 0.134779E+11 | 0.00 | 0.00 |
Maximum of Months | 0.318230E+10 | 0.00 | 0.173444E+12 | 0.174333E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.860419E+09 | 0.00 | 0.353038E+11 | 0.329732E+10 | 0.00 | 0.00 |
February | 0.137942E+09 | 0.00 | 0.567291E+11 | 0.381446E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.119287E+12 | 0.616567E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.182938E+12 | 0.830619E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.239960E+12 | 0.827225E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.281154E+12 | 0.870256E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.320552E+12 | 0.850446E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.334493E+12 | 0.944501E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.242419E+12 | 0.641995E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.157288E+12 | 0.668533E+10 | 0.00 | 0.00 |
November | 323522.37 | 0.00 | 0.945785E+11 | 0.568134E+10 | 0.00 | 0.00 |
December | 0.213746E+09 | 0.00 | 0.544789E+11 | 0.463832E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.121243E+10 | 0.00 | 0.211918E+13 | 0.799329E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.353038E+11 | 0.329732E+10 | 0.00 | 0.00 |
Maximum of Months | 0.860419E+09 | 0.00 | 0.334493E+12 | 0.944501E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.253730E+11 | 0.00 | 0.231093E+12 | 0.235801E+11 | 0.00 | 0.00 |
February | 0.363800E+10 | 0.00 | 0.403832E+12 | 0.260824E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.916989E+12 | 0.435810E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.149973E+13 | 0.589244E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.227329E+13 | 0.730638E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.259906E+13 | 0.718006E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.284947E+13 | 0.626710E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.278385E+13 | 0.619577E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.214881E+13 | 0.529442E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.130690E+13 | 0.510201E+11 | 0.00 | 0.00 |
November | 72010545.31 | 0.00 | 0.701350E+12 | 0.371599E+11 | 0.00 | 0.00 |
December | 0.691635E+10 | 0.00 | 0.306683E+12 | 0.259546E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.359993E+11 | 0.00 | 0.180210E+14 | 0.588740E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.231093E+12 | 0.235801E+11 | 0.00 | 0.00 |
Maximum of Months | 0.253730E+11 | 0.00 | 0.284947E+13 | 0.730638E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.811273E+10 | 0.00 | 0.202031E+11 | 0.245640E+10 | 0.00 | 0.00 |
February | 0.150162E+10 | 0.00 | 0.374761E+11 | 0.249091E+10 | 0.00 | 0.00 |
March | 2807953.01 | 0.00 | 0.940052E+11 | 0.428624E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.163212E+12 | 0.646618E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.248366E+12 | 0.840048E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.280793E+12 | 0.833662E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.301821E+12 | 0.704213E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.292655E+12 | 0.672738E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.224037E+12 | 0.560032E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.133112E+12 | 0.499657E+10 | 0.00 | 0.00 |
November | 0.139574E+09 | 0.00 | 0.655365E+11 | 0.329788E+10 | 0.00 | 0.00 |
December | 0.318365E+10 | 0.00 | 0.251525E+11 | 0.242797E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.129404E+11 | 0.00 | 0.188637E+13 | 0.625291E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.202031E+11 | 0.242797E+10 | 0.00 | 0.00 |
Maximum of Months | 0.811273E+10 | 0.00 | 0.301821E+12 | 0.840048E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.389993E+12 | 0.188609E+12 | 0.00 | 5.80 |
February | 0.00 | 0.00 | 0.626143E+12 | 0.228414E+12 | 0.00 | 6.34 |
March | 0.00 | 0.00 | 0.101521E+13 | 0.328660E+12 | 0.00 | 3.81 |
April | 0.00 | 0.00 | 0.132156E+13 | 0.422981E+12 | 0.00 | 0.63 |
May | 0.00 | 0.00 | 0.458723E+12 | 0.225780E+12 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.770382E+12 | 0.307164E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.112287E+13 | 0.391870E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.140269E+13 | 0.444818E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.449722E+12 | 0.208140E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.734558E+12 | 0.271033E+12 | 0.00 | 0.84 |
November | 0.00 | 0.00 | 0.978665E+12 | 0.312141E+12 | 0.00 | 6.66 |
December | 0.00 | 0.00 | 0.129546E+13 | 0.375875E+12 | 0.00 | 15.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.105660E+14 | 0.370549E+13 | 0.00 | 39.76 |
Minimum of Months | 0.00 | 0.00 | 0.389993E+12 | 0.188609E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.140269E+13 | 0.444818E+12 | 0.00 | 15.67 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.586034E+10 | 0.261063E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112160E+11 | 0.354319E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.194071E+11 | 0.571030E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.263182E+11 | 0.804426E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.795851E+10 | 0.375198E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.141865E+11 | 0.544857E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211717E+11 | 0.716211E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.275625E+11 | 0.853582E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.730090E+10 | 0.332752E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.135857E+11 | 0.466545E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.184680E+11 | 0.520822E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.243124E+11 | 0.592864E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.197348E+12 | 0.639367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.586034E+10 | 0.261063E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.275625E+11 | 0.853582E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.387222E+11 | 0.217316E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.979133E+11 | 0.322050E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.182485E+12 | 0.540169E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.250002E+12 | 0.765666E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.743321E+11 | 0.353939E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.134424E+12 | 0.517699E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.200561E+12 | 0.680097E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.260934E+12 | 0.810665E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.674353E+11 | 0.312228E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.127343E+12 | 0.440582E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.170380E+12 | 0.486926E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.218701E+12 | 0.544977E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182323E+13 | 0.599232E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.387222E+11 | 0.217316E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.260934E+12 | 0.810665E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.249349E+10 | 0.191221E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.901957E+10 | 0.309338E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.180514E+11 | 0.538769E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.251473E+11 | 0.771968E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.772519E+10 | 0.363112E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.137132E+11 | 0.526571E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203433E+11 | 0.689410E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.262899E+11 | 0.818060E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.686061E+10 | 0.316149E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126410E+11 | 0.440468E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.164231E+11 | 0.477993E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.204986E+11 | 0.525011E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.179207E+12 | 0.596807E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.249349E+10 | 0.191221E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262899E+11 | 0.818060E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150826E+11 | 0.513482E+11 | 0.252244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134779E+11 | 0.529643E+11 | 0.112118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154255E+11 | 0.751096E+11 | 0.153976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149009E+11 | 0.884959E+11 | 0.761638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160691E+11 | 0.114756E+12 | 0.774754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159295E+11 | 0.134895E+12 | 0.554940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169121E+11 | 0.158483E+12 | 0.851813E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174333E+11 | 0.173444E+12 | 0.569596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163150E+11 | 0.137059E+12 | 0.990280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167248E+11 | 0.995298E+11 | 0.110232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158207E+11 | 0.766402E+11 | 0.233749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155330E+11 | 0.602384E+11 | 0.318230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189624E+12 | 0.122296E+13 | 0.163085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134779E+11 | 0.513482E+11 | 0.554940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174333E+11 | 0.173444E+12 | 0.318230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.329732E+10 | 0.353038E+11 | 0.860419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.381446E+10 | 0.567291E+11 | 0.137942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.616567E+10 | 0.119287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.830619E+10 | 0.182938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.827225E+10 | 0.239960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.870256E+10 | 0.281154E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.850446E+10 | 0.320552E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.944501E+10 | 0.334493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.641995E+10 | 0.242419E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.668533E+10 | 0.157288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568134E+10 | 0.945785E+11 | 323522.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.463832E+10 | 0.544789E+11 | 0.213746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.799329E+11 | 0.211918E+13 | 0.121243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.329732E+10 | 0.353038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944501E+10 | 0.334493E+12 | 0.860419E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.235801E+11 | 0.231093E+12 | 0.253730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260824E+11 | 0.403832E+12 | 0.363800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.435810E+11 | 0.916989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.589244E+11 | 0.149973E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.730638E+11 | 0.227329E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.718006E+11 | 0.259906E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.626710E+11 | 0.284947E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.619577E+11 | 0.278385E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529442E+11 | 0.214881E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.510201E+11 | 0.130690E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371599E+11 | 0.701350E+12 | 72010545.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.259546E+11 | 0.306683E+12 | 0.691635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.588740E+12 | 0.180210E+14 | 0.359993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.235801E+11 | 0.231093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.730638E+11 | 0.284947E+13 | 0.253730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.245640E+10 | 0.202031E+11 | 0.811273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249091E+10 | 0.374761E+11 | 0.150162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428624E+10 | 0.940052E+11 | 2807953.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.646618E+10 | 0.163212E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.840048E+10 | 0.248366E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.833662E+10 | 0.280793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.704213E+10 | 0.301821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.672738E+10 | 0.292655E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.560032E+10 | 0.224037E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.499657E+10 | 0.133112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.329788E+10 | 0.655365E+11 | 0.139574E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.242797E+10 | 0.251525E+11 | 0.318365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625291E+11 | 0.188637E+13 | 0.129404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.242797E+10 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.840048E+10 | 0.301821E+12 | 0.811273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.961500E+11 | 0.335977E+12 | 0.00 | 0.00 | 0.00 | 0.155156E+11 | 0.00 | 0.00 |
February | 0.868452E+11 | 0.532269E+12 | 0.00 | 0.00 | 0.00 | 0.169707E+11 | 0.00 | 0.00 |
March | 0.961500E+11 | 0.834087E+12 | 0.00 | 0.00 | 0.00 | 0.102039E+11 | 0.00 | 0.00 |
April | 0.930484E+11 | 0.103802E+13 | 0.00 | 0.00 | 0.00 | 0.169658E+10 | 0.00 | 0.00 |
May | 0.961500E+11 | 0.358983E+12 | 0.00 | 0.00 | 0.00 | 21247985.27 | 0.00 | 0.00 |
June | 0.930484E+11 | 0.595091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.961500E+11 | 0.870627E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.961500E+11 | 0.110533E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.930484E+11 | 0.363059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.961500E+11 | 0.598514E+12 | 0.00 | 0.00 | 0.00 | 0.224070E+10 | 0.00 | 0.00 |
November | 0.930484E+11 | 0.817084E+12 | 0.00 | 0.00 | 0.00 | 0.178130E+11 | 0.00 | 0.00 |
December | 0.961500E+11 | 0.110177E+13 | 0.00 | 0.00 | 0.00 | 0.419281E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.113209E+13 | 0.855081E+13 | 0.00 | 0.00 | 0.00 | 0.106390E+12 | 0.00 | 0.00 |
Minimum of Months | 0.868452E+11 | 0.335977E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.961500E+11 | 0.110533E+13 | 0.00 | 0.00 | 0.00 | 0.419281E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143704E+10 | 0.505199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129797E+10 | 0.953499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143704E+10 | 0.159273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139068E+10 | 0.204509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143704E+10 | 0.616913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139068E+10 | 0.108388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143704E+10 | 0.162503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143704E+10 | 0.212635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139068E+10 | 0.583825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143704E+10 | 0.110405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139068E+10 | 0.154124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143704E+10 | 0.206733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169199E+11 | 0.158451E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129797E+10 | 0.505199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143704E+10 | 0.212635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137192E+11 | 0.333522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123915E+11 | 0.831878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137192E+11 | 0.149719E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132766E+11 | 0.194204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137192E+11 | 0.576078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132766E+11 | 0.102694E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137192E+11 | 0.153947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137192E+11 | 0.201183E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132766E+11 | 0.539195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137192E+11 | 0.103465E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132766E+11 | 0.142132E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137192E+11 | 0.185907E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161532E+12 | 0.146132E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123915E+11 | 0.333522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137192E+11 | 0.201183E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137547E+10 | 0.214248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124236E+10 | 0.765133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137547E+10 | 0.147938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133110E+10 | 0.195194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137547E+10 | 0.597872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133110E+10 | 0.104650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137547E+10 | 0.156021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137547E+10 | 0.202562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133110E+10 | 0.548020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137547E+10 | 0.102584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133110E+10 | 0.136828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137547E+10 | 0.174077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161951E+11 | 0.143238E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124236E+10 | 0.214248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137547E+10 | 0.202562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.150826E+11 | 0.252244E+10 | 0.513482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134779E+11 | 0.112118E+10 | 0.529643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154255E+11 | 0.153976E+10 | 0.751096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149009E+11 | 0.761638E+09 | 0.884959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160691E+11 | 0.774754E+09 | 0.114756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159295E+11 | 0.554940E+09 | 0.134895E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169121E+11 | 0.851813E+09 | 0.158483E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174333E+11 | 0.569596E+09 | 0.173444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163150E+11 | 0.990280E+09 | 0.137059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167248E+11 | 0.110232E+10 | 0.995298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158207E+11 | 0.233749E+10 | 0.766402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155330E+11 | 0.318230E+10 | 0.602384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189624E+12 | 0.163085E+11 | 0.122296E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.134779E+11 | 0.554940E+09 | 0.513482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174333E+11 | 0.318230E+10 | 0.173444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.329732E+10 | 0.860419E+09 | 0.353038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.381446E+10 | 0.137942E+09 | 0.567291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.616567E+10 | 0.00 | 0.119287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.830619E+10 | 0.00 | 0.182938E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.827225E+10 | 0.00 | 0.239960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.870256E+10 | 0.00 | 0.281154E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.850446E+10 | 0.00 | 0.320552E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.944501E+10 | 0.00 | 0.334493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.641995E+10 | 0.00 | 0.242419E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.668533E+10 | 0.00 | 0.157288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568134E+10 | 323522.37 | 0.945785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.463832E+10 | 0.213746E+09 | 0.544789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.799329E+11 | 0.121243E+10 | 0.211918E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.329732E+10 | 0.00 | 0.353038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.944501E+10 | 0.860419E+09 | 0.334493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.235801E+11 | 0.253730E+11 | 0.231093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260824E+11 | 0.363800E+10 | 0.403832E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.435810E+11 | 0.00 | 0.916989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.589244E+11 | 0.00 | 0.149973E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.730638E+11 | 0.00 | 0.227329E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.718006E+11 | 0.00 | 0.259906E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.626710E+11 | 0.00 | 0.284947E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.619577E+11 | 0.00 | 0.278385E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529442E+11 | 0.00 | 0.214881E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.510201E+11 | 0.00 | 0.130690E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.371599E+11 | 72010545.31 | 0.701350E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.259546E+11 | 0.691635E+10 | 0.306683E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.588740E+12 | 0.359993E+11 | 0.180210E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.235801E+11 | 0.00 | 0.231093E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.730638E+11 | 0.253730E+11 | 0.284947E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.245640E+10 | 0.811273E+10 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249091E+10 | 0.150162E+10 | 0.374761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.428624E+10 | 2807953.01 | 0.940052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.646618E+10 | 0.00 | 0.163212E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.840048E+10 | 0.00 | 0.248366E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.833662E+10 | 0.00 | 0.280793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.704213E+10 | 0.00 | 0.301821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.672738E+10 | 0.00 | 0.292655E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.560032E+10 | 0.00 | 0.224037E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.499657E+10 | 0.00 | 0.133112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.329788E+10 | 0.139574E+09 | 0.655365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.242797E+10 | 0.318365E+10 | 0.251525E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.625291E+11 | 0.129404E+11 | 0.188637E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.242797E+10 | 0.00 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.840048E+10 | 0.811273E+10 | 0.301821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.961500E+11 | 0.00 | 0.389993E+12 | 0.00 | 0.768740E+11 | 0.00 | 0.00 | 0.00 | 0.155854E+11 | 0.00 | 0.00 | 0.00 |
February | 0.868452E+11 | 0.00 | 0.626143E+12 | 0.00 | 0.124521E+12 | 0.00 | 0.00 | 0.00 | 0.170471E+11 | 0.00 | 0.00 | 0.00 |
March | 0.961500E+11 | 0.00 | 0.101521E+13 | 0.00 | 0.222261E+12 | 0.00 | 0.00 | 0.00 | 0.102498E+11 | 0.00 | 0.00 | 0.00 |
April | 0.930484E+11 | 0.00 | 0.132156E+13 | 0.00 | 0.328228E+12 | 0.00 | 0.00 | 0.00 | 0.170422E+10 | 0.00 | 0.00 | 0.00 |
May | 0.961500E+11 | 0.00 | 0.458723E+12 | 0.00 | 0.129609E+12 | 0.00 | 0.00 | 0.00 | 21343631.06 | 0.00 | 0.00 | 0.00 |
June | 0.930484E+11 | 0.00 | 0.770382E+12 | 0.00 | 0.214116E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.961500E+11 | 0.00 | 0.112287E+13 | 0.00 | 0.295720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.961500E+11 | 0.00 | 0.140269E+13 | 0.00 | 0.348668E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.930484E+11 | 0.00 | 0.449722E+12 | 0.00 | 0.115092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.961500E+11 | 0.00 | 0.734558E+12 | 0.00 | 0.172632E+12 | 0.00 | 0.00 | 0.00 | 0.225079E+10 | 0.00 | 0.00 | 0.00 |
November | 0.930484E+11 | 0.00 | 0.978665E+12 | 0.00 | 0.201199E+12 | 0.00 | 0.00 | 0.00 | 0.178931E+11 | 0.00 | 0.00 | 0.00 |
December | 0.961500E+11 | 0.00 | 0.129546E+13 | 0.00 | 0.237608E+12 | 0.00 | 0.00 | 0.00 | 0.421169E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113209E+13 | 0.00 | 0.105660E+14 | 0.00 | 0.246653E+13 | 0.00 | 0.00 | 0.00 | 0.106869E+12 | 0.00 | 0.00 | |
Minimum of Months | 0.868452E+11 | 0.00 | 0.389993E+12 | 0.00 | 0.768740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.961500E+11 | 0.00 | 0.140269E+13 | 0.00 | 0.348668E+12 | 0.00 | 0.00 | 0.00 | 0.421169E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.143704E+10 | 0.00 | 0.586034E+10 | 0.00 | 0.117360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129797E+10 | 0.00 | 0.112160E+11 | 0.00 | 0.224522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143704E+10 | 0.00 | 0.194071E+11 | 0.00 | 0.427326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139068E+10 | 0.00 | 0.263182E+11 | 0.00 | 0.665358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143704E+10 | 0.00 | 0.795851E+10 | 0.00 | 0.231494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139068E+10 | 0.00 | 0.141865E+11 | 0.00 | 0.405789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143704E+10 | 0.00 | 0.211717E+11 | 0.00 | 0.572507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143704E+10 | 0.00 | 0.275625E+11 | 0.00 | 0.709878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139068E+10 | 0.00 | 0.730090E+10 | 0.00 | 0.193684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143704E+10 | 0.00 | 0.135857E+11 | 0.00 | 0.322841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139068E+10 | 0.00 | 0.184680E+11 | 0.00 | 0.381754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143704E+10 | 0.00 | 0.243124E+11 | 0.00 | 0.449161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169199E+11 | 0.00 | 0.197348E+12 | 0.00 | 0.470167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.129797E+10 | 0.00 | 0.586034E+10 | 0.00 | 0.117360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143704E+10 | 0.00 | 0.275625E+11 | 0.00 | 0.709878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.137192E+11 | 0.00 | 0.387222E+11 | 0.00 | 0.801246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123915E+11 | 0.00 | 0.979133E+11 | 0.00 | 0.198135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137192E+11 | 0.00 | 0.182485E+12 | 0.00 | 0.402977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132766E+11 | 0.00 | 0.250002E+12 | 0.00 | 0.632900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137192E+11 | 0.00 | 0.743321E+11 | 0.00 | 0.216747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132766E+11 | 0.00 | 0.134424E+12 | 0.00 | 0.384933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137192E+11 | 0.00 | 0.200561E+12 | 0.00 | 0.542906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137192E+11 | 0.00 | 0.260934E+12 | 0.00 | 0.673473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132766E+11 | 0.00 | 0.674353E+11 | 0.00 | 0.179462E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137192E+11 | 0.00 | 0.127343E+12 | 0.00 | 0.303391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132766E+11 | 0.00 | 0.170380E+12 | 0.00 | 0.354160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137192E+11 | 0.00 | 0.218701E+12 | 0.00 | 0.407785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161532E+12 | 0.00 | 0.182323E+13 | 0.00 | 0.437699E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.123915E+11 | 0.00 | 0.387222E+11 | 0.00 | 0.801246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137192E+11 | 0.00 | 0.260934E+12 | 0.00 | 0.673473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.137547E+10 | 0.00 | 0.249349E+10 | 0.00 | 0.536742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124236E+10 | 0.00 | 0.901957E+10 | 0.00 | 0.185102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137547E+10 | 0.00 | 0.180514E+11 | 0.00 | 0.401222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133110E+10 | 0.00 | 0.251473E+11 | 0.00 | 0.638857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137547E+10 | 0.00 | 0.772519E+10 | 0.00 | 0.225565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133110E+10 | 0.00 | 0.137132E+11 | 0.00 | 0.393461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137547E+10 | 0.00 | 0.203433E+11 | 0.00 | 0.551863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137547E+10 | 0.00 | 0.262899E+11 | 0.00 | 0.680512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133110E+10 | 0.00 | 0.686061E+10 | 0.00 | 0.183039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137547E+10 | 0.00 | 0.126410E+11 | 0.00 | 0.302921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133110E+10 | 0.00 | 0.164231E+11 | 0.00 | 0.344883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137547E+10 | 0.00 | 0.204986E+11 | 0.00 | 0.387464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161951E+11 | 0.00 | 0.179207E+12 | 0.00 | 0.434856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.124236E+10 | 0.00 | 0.249349E+10 | 0.00 | 0.536742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137547E+10 | 0.00 | 0.262899E+11 | 0.00 | 0.680512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.285367E+10 | 0.00 | 0.00 | 0.159774E+09 | 0.00 | 0.00 | 0.254253E+11 | 0.00 | 0.40 |
February | 0.122833E+10 | 0.00 | 0.00 | 0.142906E+09 | 0.00 | 0.00 | 0.163853E+11 | 0.00 | 0.40 |
March | 0.598068E+09 | 0.152681E+10 | 0.00 | 0.140845E+09 | 30190844.90 | 0.00 | 0.824793E+10 | 0.00 | 0.41 |
April | 47244755.19 | 0.113869E+11 | 0.00 | 34449567.43 | 0.292658E+09 | 0.00 | 0.614836E+09 | 0.00 | 0.41 |
May | 5484853.03 | 0.314728E+11 | 0.00 | 4778627.66 | 0.489763E+09 | 0.00 | 9744227.90 | 0.00 | 0.43 |
June | 37208.23 | 0.486814E+11 | 0.00 | 620268.53 | 0.592213E+09 | 0.00 | 33382.65 | 0.00 | 0.45 |
July | 0.00 | 0.673626E+11 | 0.00 | 0.00 | 0.117329E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.732764E+11 | 0.00 | 0.00 | 0.988575E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.482187E+11 | 0.00 | 0.00 | 0.842098E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.318956E+09 | 0.955404E+10 | 0.00 | 0.103914E+09 | 0.143794E+09 | 0.00 | 0.251717E+10 | 0.00 | 0.45 |
November | 0.104608E+10 | 0.260080E+09 | 0.00 | 0.206662E+09 | 22325252.49 | 0.00 | 0.128420E+11 | 0.00 | 0.44 |
December | 0.251439E+10 | 0.00 | 0.00 | 0.187372E+09 | 0.00 | 0.00 | 0.235872E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.861226E+10 | 0.291740E+12 | 0.00 | 0.981320E+09 | 0.457491E+10 | 0.00 | 0.896295E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.285367E+10 | 0.732764E+11 | 0.00 | 0.206662E+09 | 0.117329E+10 | 0.00 | 0.254253E+11 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133933E+10 | 0.00 | 0.00 | 79493269.97 | 0.00 | 0.00 | 0.247740E+11 | 0.00 | 0.37 |
February | 0.124745E+10 | 22095587.98 | 0.00 | 88481670.93 | 15761062.31 | 0.00 | 0.157751E+11 | 0.00 | 0.38 |
March | 0.146197E+10 | 0.207078E+10 | 0.00 | 84581598.78 | 0.720910E+09 | 0.00 | 0.736006E+10 | 0.00 | 0.42 |
April | 0.621052E+09 | 0.873361E+10 | 0.00 | 19133361.33 | 0.566315E+10 | 0.00 | 0.697895E+09 | 0.00 | 0.46 |
May | 3599471.20 | 0.276438E+11 | 0.00 | 0.00 | 0.146025E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.400686E+11 | 0.00 | 0.00 | 0.243239E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.501640E+11 | 0.00 | 0.00 | 0.387626E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.567341E+11 | 0.00 | 0.00 | 0.354734E+11 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.404328E+11 | 0.00 | 0.00 | 0.238196E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.307053E+09 | 0.108109E+11 | 0.00 | 27411608.04 | 0.378993E+10 | 0.00 | 0.151212E+10 | 0.00 | 0.41 |
November | 0.190521E+10 | 0.392489E+09 | 0.00 | 0.106674E+09 | 96619624.23 | 0.00 | 0.111462E+11 | 0.00 | 0.39 |
December | 0.214208E+10 | 0.00 | 0.00 | 0.113904E+09 | 0.00 | 0.00 | 0.240016E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.902775E+10 | 0.237073E+12 | 0.00 | 0.519680E+09 | 0.147268E+12 | 0.00 | 0.852670E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.214208E+10 | 0.567341E+11 | 0.00 | 0.113904E+09 | 0.387626E+11 | 0.00 | 0.247740E+11 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105286E+12 | 0.00 | 0.00 | 0.293912E+09 | 0.00 | 37937133.11 | 0.100095E+12 | 0.00 | 0.32 |
February | 0.319717E+11 | 901978.49 | 0.00 | 0.453068E+09 | 0.538770E+09 | 0.00 | 0.106866E+12 | 0.00 | 0.35 |
March | 0.523919E+10 | 0.189478E+11 | 0.00 | 0.573337E+09 | 0.682924E+10 | 0.00 | 0.680624E+11 | 0.00 | 0.37 |
April | 0.216653E+10 | 0.861182E+11 | 0.00 | 0.158233E+09 | 0.540646E+11 | 0.00 | 0.563359E+10 | 0.00 | 0.40 |
May | 16530248.10 | 0.269681E+12 | 0.00 | 0.00 | 0.137924E+12 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.391780E+12 | 0.00 | 0.00 | 0.214587E+12 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.485244E+12 | 0.00 | 0.00 | 0.323993E+12 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.551972E+12 | 0.00 | 0.00 | 0.249715E+12 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.396207E+12 | 0.00 | 0.00 | 0.171856E+12 | 0.00 | 0.00 | 0.00 | 0.38 |
October | 0.199467E+10 | 0.105383E+12 | 0.00 | 0.179166E+09 | 0.255978E+11 | 0.00 | 0.136642E+11 | 0.00 | 0.36 |
November | 0.952018E+10 | 0.297656E+10 | 0.00 | 0.607269E+09 | 0.183177E+10 | 0.00 | 0.913269E+11 | 0.00 | 0.36 |
December | 0.586485E+11 | 0.00 | 0.00 | 0.419715E+09 | 44606425.99 | 0.00 | 0.136224E+12 | 0.00 | 0.34 |
Annual Sum or Average | 0.214844E+12 | 0.230831E+13 | 0.00 | 0.268470E+10 | 0.118698E+13 | 37937133.11 | 0.521872E+12 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.105286E+12 | 0.551972E+12 | 0.00 | 0.607269E+09 | 0.323993E+12 | 37937133.11 | 0.136224E+12 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146580E+11 | 0.00 | 0.00 | 7067426.32 | 0.00 | 0.499081E+09 | 0.300572E+10 | 0.00 | 0.31 |
February | 0.645774E+10 | 0.00 | 0.00 | 25646095.01 | 44018754.54 | 0.00 | 0.555010E+10 | 0.00 | 0.32 |
March | 0.140889E+10 | 0.156753E+10 | 0.00 | 46633469.20 | 0.524006E+09 | 0.00 | 0.508423E+10 | 0.00 | 0.35 |
April | 0.179882E+09 | 0.778441E+10 | 0.00 | 19868582.65 | 0.497902E+10 | 0.00 | 0.573311E+09 | 0.00 | 0.40 |
May | 617186.49 | 0.263286E+11 | 0.00 | 0.00 | 0.129273E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.382092E+11 | 0.00 | 0.00 | 0.209983E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.481212E+11 | 0.00 | 0.00 | 0.313696E+11 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.546580E+11 | 0.00 | 0.00 | 0.246937E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.387157E+11 | 0.00 | 0.00 | 0.172515E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
October | 0.286504E+09 | 0.998670E+10 | 0.00 | 12394220.79 | 0.230038E+10 | 0.00 | 0.732689E+09 | 0.00 | 0.35 |
November | 0.344720E+10 | 0.165215E+09 | 0.00 | 38176989.40 | 0.134254E+09 | 0.00 | 0.468514E+10 | 0.00 | 0.33 |
December | 0.116714E+11 | 0.00 | 0.00 | 12820129.41 | 2006782.12 | 2542338.53 | 0.449116E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.381102E+11 | 0.225537E+12 | 0.00 | 0.162607E+09 | 0.115224E+12 | 0.501624E+09 | 0.241224E+11 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.146580E+11 | 0.546580E+11 | 0.00 | 46633469.20 | 0.313696E+11 | 0.499081E+09 | 0.555010E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192320E+10 | 0.00 | 0.00 | 1576675.45 | 0.00 | 0.00 | 0.446334E+09 | 0.00 | 0.27 |
February | 0.912791E+09 | 2875459.21 | 0.00 | 4623224.56 | 1978454.31 | 0.00 | 0.678343E+09 | 0.00 | 0.30 |
March | 0.332521E+09 | 0.365997E+09 | 0.00 | 6831329.59 | 90494381.44 | 0.00 | 0.623441E+09 | 0.00 | 0.43 |
April | 80043970.22 | 0.200769E+10 | 0.00 | 2762647.10 | 0.599094E+09 | 0.00 | 86961345.08 | 0.00 | 0.60 |
May | 451834.35 | 0.727298E+10 | 0.00 | 0.00 | 0.135157E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
June | 0.00 | 0.109655E+11 | 0.00 | 0.00 | 0.215325E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.137311E+11 | 0.00 | 0.00 | 0.330772E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.131719E+11 | 0.00 | 0.00 | 0.348856E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.814600E+10 | 0.00 | 0.00 | 0.278778E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 55549830.51 | 0.178182E+10 | 0.00 | 1813984.07 | 0.479644E+09 | 0.00 | 0.125659E+09 | 0.00 | 0.46 |
November | 0.570856E+09 | 53165505.83 | 0.00 | 6448735.82 | 12128466.21 | 0.00 | 0.643900E+09 | 0.00 | 0.33 |
December | 0.145921E+10 | 0.00 | 0.00 | 3877288.97 | 0.00 | 0.00 | 0.722923E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.533462E+10 | 0.574990E+11 | 0.00 | 27933885.56 | 0.142722E+11 | 0.00 | 0.332756E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.192320E+10 | 0.137311E+11 | 0.00 | 6831329.59 | 0.348856E+10 | 0.00 | 0.722923E+09 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.928021E+09 | 0.00 | 0.00 | 2889206.52 | 0.00 | 0.00 | 0.780120E+09 | 0.00 | 0.30 |
February | 0.471532E+09 | 1908460.85 | 0.00 | 5074664.42 | 1273583.55 | 0.00 | 0.813552E+09 | 0.00 | 0.37 |
March | 0.205870E+09 | 0.291604E+09 | 0.00 | 6623456.78 | 56161017.29 | 0.00 | 0.587171E+09 | 0.00 | 0.54 |
April | 47433306.54 | 0.173494E+10 | 0.00 | 2989678.39 | 0.338439E+09 | 0.00 | 90903006.86 | 0.00 | 0.74 |
May | 290857.76 | 0.615530E+10 | 0.00 | 0.00 | 0.734471E+09 | 0.00 | 0.00 | 0.00 | 0.88 |
June | 0.00 | 0.810563E+10 | 0.00 | 0.00 | 0.131167E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
July | 0.00 | 0.937802E+10 | 0.00 | 0.00 | 0.215939E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
August | 0.00 | 0.834791E+10 | 0.00 | 0.00 | 0.237113E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.621249E+10 | 0.00 | 0.00 | 0.169111E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 39757375.62 | 0.143326E+10 | 0.00 | 1867864.64 | 0.270925E+09 | 0.00 | 0.105740E+09 | 0.00 | 0.54 |
November | 0.351345E+09 | 39541031.84 | 0.00 | 5863577.52 | 7807415.60 | 0.00 | 0.583743E+09 | 0.00 | 0.39 |
December | 0.881789E+09 | 0.00 | 0.00 | 3490621.82 | 0.00 | 0.00 | 0.648454E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.292604E+10 | 0.417006E+11 | 0.00 | 28799070.11 | 0.894237E+10 | 0.00 | 0.360968E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.928021E+09 | 0.937802E+10 | 0.00 | 6623456.78 | 0.237113E+10 | 0.00 | 0.813552E+09 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105916E+10 | 0.00 | 0.00 | 11745016.42 | 0.00 | 932436.73 | 0.280727E+10 | 0.00 | 0.49 |
February | 0.629511E+09 | 5754700.73 | 0.00 | 14689274.06 | 1680136.30 | 0.00 | 0.183496E+10 | 0.00 | 0.52 |
March | 0.274042E+09 | 0.627455E+09 | 0.00 | 11650586.89 | 60672213.19 | 0.00 | 0.100393E+10 | 0.00 | 0.61 |
April | 78658735.58 | 0.258885E+10 | 0.00 | 3432823.44 | 0.464860E+09 | 0.00 | 0.101644E+09 | 0.00 | 0.69 |
May | 452441.59 | 0.771628E+10 | 0.00 | 0.00 | 0.125576E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
June | 0.00 | 0.110764E+11 | 0.00 | 0.00 | 0.211826E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
July | 0.00 | 0.139937E+11 | 0.00 | 0.00 | 0.325017E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.140014E+11 | 0.00 | 0.00 | 0.332896E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 0.00 | 0.103489E+11 | 0.00 | 0.00 | 0.242005E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 44441935.19 | 0.319934E+10 | 0.00 | 3540824.53 | 0.306783E+09 | 0.00 | 0.185867E+09 | 0.00 | 0.72 |
November | 0.339280E+09 | 0.138003E+09 | 0.00 | 23929943.46 | 4711250.71 | 0.00 | 0.174791E+10 | 0.00 | 0.66 |
December | 0.820900E+09 | 0.00 | 0.00 | 16405379.10 | 0.00 | 0.00 | 0.284929E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.324645E+10 | 0.636960E+11 | 0.00 | 85393847.89 | 0.132119E+11 | 932436.73 | 0.105309E+11 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.105916E+10 | 0.140014E+11 | 0.00 | 23929943.46 | 0.332896E+10 | 932436.73 | 0.284929E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.607619E+09 | 0.00 | 0.00 | 5292744.38 | 0.00 | 0.00 | 0.141401E+10 | 0.00 | 0.39 |
February | 0.195020E+09 | 6311063.67 | 0.00 | 9780032.13 | 1023602.82 | 0.00 | 0.147925E+10 | 0.00 | 0.54 |
March | 86217537.85 | 0.572454E+09 | 0.00 | 14115357.02 | 12133166.84 | 0.00 | 0.115238E+10 | 0.00 | 0.85 |
April | 10506229.45 | 0.340552E+10 | 0.00 | 7018311.71 | 52945366.88 | 0.00 | 0.186968E+09 | 0.00 | 1.22 |
May | 33134.42 | 0.826230E+10 | 0.00 | 36357.55 | 0.281512E+09 | 0.00 | 261933.54 | 0.00 | 1.08 |
June | 0.00 | 0.129335E+11 | 0.00 | 0.00 | 0.417025E+09 | 0.00 | 0.00 | 0.00 | 1.15 |
July | 0.00 | 0.169907E+11 | 0.00 | 0.00 | 0.439207E+09 | 0.00 | 0.00 | 0.00 | 1.10 |
August | 0.00 | 0.186534E+11 | 0.00 | 0.00 | 0.304266E+09 | 0.00 | 0.00 | 0.00 | 1.18 |
September | 0.00 | 0.953565E+10 | 0.00 | 0.00 | 0.789253E+09 | 0.00 | 0.00 | 0.00 | 0.84 |
October | 21406977.81 | 0.232588E+10 | 0.00 | 3452158.68 | 0.135853E+09 | 0.00 | 0.187319E+09 | 0.00 | 0.78 |
November | 0.126292E+09 | 90245039.74 | 0.00 | 14785581.71 | 1474682.14 | 0.00 | 0.140954E+10 | 0.00 | 0.67 |
December | 0.190001E+09 | 0.00 | 0.00 | 12814583.96 | 0.00 | 0.00 | 0.274193E+10 | 0.00 | 0.62 |
Annual Sum or Average | 0.123710E+10 | 0.727759E+11 | 0.00 | 67295127.15 | 0.243469E+10 | 0.00 | 0.857167E+10 | 0.00 | 0.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.607619E+09 | 0.186534E+11 | 0.00 | 14785581.71 | 0.789253E+09 | 0.00 | 0.274193E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185055E+11 | 0.00 | 0.00 | 325206.37 | 0.00 | 0.547705E+10 | 0.145579E+09 | 0.00 | 0.30 |
February | 0.121868E+11 | 122943.63 | 0.00 | 13188204.27 | 67420635.54 | 0.965542E+09 | 0.166643E+10 | 0.00 | 0.30 |
March | 0.392118E+10 | 0.360625E+10 | 0.00 | 40115136.68 | 0.681577E+09 | 0.00 | 0.405287E+10 | 0.00 | 0.37 |
April | 0.322621E+09 | 0.218589E+11 | 0.00 | 21288947.97 | 0.594666E+10 | 0.00 | 0.691784E+09 | 0.00 | 0.59 |
May | 2068562.80 | 0.807839E+11 | 0.00 | 0.00 | 0.117053E+11 | 0.00 | 0.00 | 0.00 | 0.75 |
June | 0.00 | 0.122714E+12 | 0.00 | 0.00 | 0.176817E+11 | 0.00 | 0.00 | 0.00 | 0.78 |
July | 0.00 | 0.151088E+12 | 0.00 | 0.00 | 0.260043E+11 | 0.00 | 0.00 | 0.00 | 0.73 |
August | 0.00 | 0.143549E+12 | 0.00 | 0.00 | 0.243284E+11 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.858645E+11 | 0.00 | 0.00 | 0.191598E+11 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 0.106509E+10 | 0.177831E+11 | 0.00 | 9286883.06 | 0.329631E+10 | 0.00 | 0.601441E+09 | 0.00 | 0.41 |
November | 0.838049E+10 | 0.399387E+09 | 0.00 | 26165752.49 | 0.195423E+09 | 0.00 | 0.211780E+10 | 0.00 | 0.31 |
December | 0.196311E+11 | 0.00 | 0.00 | 619851.84 | 5581960.60 | 0.134017E+10 | 0.227714E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.640149E+11 | 0.627646E+12 | 0.00 | 0.110990E+09 | 0.109072E+12 | 0.778276E+10 | 0.950361E+10 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.196311E+11 | 0.151088E+12 | 0.00 | 40115136.68 | 0.260043E+11 | 0.547705E+10 | 0.405287E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.925028E+10 | 0.00 | 0.00 | 7182678.24 | 0.00 | 0.202646E+10 | 0.231535E+10 | 0.00 | 0.25 |
February | 0.489809E+10 | 20327960.95 | 0.00 | 32356937.91 | 22668368.72 | 0.106607E+09 | 0.570268E+10 | 0.00 | 0.34 |
March | 0.149489E+10 | 0.338113E+10 | 0.00 | 58590983.09 | 0.352356E+09 | 0.00 | 0.604173E+10 | 0.00 | 0.54 |
April | 0.130199E+09 | 0.224607E+11 | 0.00 | 28818672.92 | 0.274062E+10 | 0.00 | 0.940352E+09 | 0.00 | 0.84 |
May | 1128881.64 | 0.717800E+11 | 0.00 | 14931.12 | 0.538428E+10 | 0.00 | 189346.16 | 0.00 | 0.99 |
June | 0.00 | 0.978107E+11 | 0.00 | 0.00 | 0.825946E+10 | 0.00 | 0.00 | 0.00 | 0.92 |
July | 0.00 | 0.115509E+12 | 0.00 | 0.00 | 0.129607E+11 | 0.00 | 0.00 | 0.00 | 0.82 |
August | 0.00 | 0.106634E+12 | 0.00 | 0.00 | 0.130054E+11 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 0.00 | 0.698862E+11 | 0.00 | 0.00 | 0.969917E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.477201E+09 | 0.160129E+11 | 0.00 | 16408780.41 | 0.151841E+10 | 0.00 | 0.100828E+10 | 0.00 | 0.55 |
November | 0.353707E+10 | 0.383493E+09 | 0.00 | 42859530.70 | 0.104980E+09 | 0.00 | 0.471885E+10 | 0.00 | 0.39 |
December | 0.881964E+10 | 0.00 | 0.00 | 12098099.12 | 3597493.16 | 0.326036E+09 | 0.314026E+10 | 0.00 | 0.26 |
Annual Sum or Average | 0.286085E+11 | 0.503879E+12 | 0.00 | 0.198331E+09 | 0.540517E+11 | 0.245910E+10 | 0.238677E+11 | 0.00 | 0.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.925028E+10 | 0.115509E+12 | 0.00 | 58590983.09 | 0.130054E+11 | 0.202646E+10 | 0.604173E+10 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116421E+11 | 0.00 | 0.00 | 0.100442E+09 | 0.00 | 0.101736E+10 | 0.255427E+11 | 0.00 | 0.53 |
February | 0.673233E+10 | 78837142.15 | 0.00 | 0.127883E+09 | 22479847.26 | 0.174399E+09 | 0.176638E+11 | 0.00 | 0.58 |
March | 0.233827E+10 | 0.704005E+10 | 0.00 | 0.103044E+09 | 0.306212E+09 | 0.00 | 0.981016E+10 | 0.00 | 0.62 |
April | 0.266721E+09 | 0.292796E+11 | 0.00 | 29896011.19 | 0.465855E+10 | 0.00 | 0.904661E+09 | 0.00 | 0.71 |
May | 2004755.57 | 0.850453E+11 | 0.00 | 3269.68 | 0.109481E+11 | 0.00 | 62165.12 | 0.00 | 0.78 |
June | 0.00 | 0.122643E+12 | 0.00 | 0.00 | 0.177178E+11 | 0.00 | 0.00 | 0.00 | 0.78 |
July | 0.00 | 0.154261E+12 | 0.00 | 0.00 | 0.251272E+11 | 0.00 | 0.00 | 0.00 | 0.74 |
August | 0.00 | 0.155824E+12 | 0.00 | 0.00 | 0.218767E+11 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 0.00 | 0.114340E+12 | 0.00 | 0.00 | 0.134562E+11 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 0.296048E+09 | 0.360715E+11 | 0.00 | 32384135.68 | 0.128602E+10 | 0.00 | 0.205346E+10 | 0.00 | 0.76 |
November | 0.321983E+10 | 0.161082E+10 | 0.00 | 0.232937E+09 | 49528549.25 | 0.00 | 0.178518E+11 | 0.00 | 0.77 |
December | 0.913690E+10 | 4632141.28 | 0.00 | 0.129938E+09 | 1864626.87 | 8044142.90 | 0.276056E+11 | 0.00 | 0.59 |
Annual Sum or Average | 0.336342E+11 | 0.706199E+12 | 0.00 | 0.756527E+09 | 0.954506E+11 | 0.119980E+10 | 0.101432E+12 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.116421E+11 | 0.155824E+12 | 0.00 | 0.232937E+09 | 0.251272E+11 | 0.101736E+10 | 0.276056E+11 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116229E+11 | 0.00 | 0.00 | 12045053.91 | 0.00 | 0.172626E+10 | 0.315023E+10 | 0.00 | 0.33 |
February | 0.627173E+10 | 50781770.07 | 0.00 | 32187370.44 | 15727637.54 | 0.114694E+09 | 0.464901E+10 | 0.00 | 0.38 |
March | 0.146017E+10 | 0.442479E+10 | 0.00 | 60093695.40 | 0.210170E+09 | 0.00 | 0.576212E+10 | 0.00 | 0.59 |
April | 0.143935E+09 | 0.269655E+11 | 0.00 | 26592994.30 | 0.172161E+10 | 0.00 | 0.735183E+09 | 0.00 | 0.93 |
May | 487936.66 | 0.813061E+11 | 0.00 | 192841.44 | 0.274922E+10 | 0.00 | 808668.23 | 0.00 | 1.06 |
June | 0.00 | 0.117390E+12 | 0.00 | 0.00 | 0.462319E+10 | 0.00 | 0.00 | 0.00 | 1.06 |
July | 0.00 | 0.133147E+12 | 0.00 | 0.00 | 0.892073E+10 | 0.00 | 0.00 | 0.00 | 0.91 |
August | 0.00 | 0.126953E+12 | 0.00 | 0.00 | 0.924920E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
September | 0.00 | 0.823917E+11 | 0.00 | 0.00 | 0.690003E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
October | 0.289783E+09 | 0.184349E+11 | 0.00 | 14453965.25 | 0.131226E+10 | 0.00 | 0.100650E+10 | 0.00 | 0.60 |
November | 0.351450E+10 | 0.605454E+09 | 0.00 | 48234585.36 | 82436271.76 | 0.00 | 0.448318E+10 | 0.00 | 0.43 |
December | 0.109394E+11 | 0.00 | 0.00 | 17341257.38 | 3619053.85 | 0.240350E+09 | 0.368904E+10 | 0.00 | 0.33 |
Annual Sum or Average | 0.342429E+11 | 0.591670E+12 | 0.00 | 0.211142E+09 | 0.357882E+11 | 0.208130E+10 | 0.234761E+11 | 0.00 | 0.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.116229E+11 | 0.133147E+12 | 0.00 | 60093695.40 | 0.924920E+10 | 0.172626E+10 | 0.576212E+10 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139412E+10 | 0.00 | 0.00 | 22532.29 | 0.00 | 0.927920E+09 | 14986906.44 | 0.00 | 0.32 |
February | 0.103602E+10 | 0.00 | 0.00 | 1188770.31 | 5513969.09 | 0.230304E+09 | 0.167985E+09 | 0.00 | 0.30 |
March | 0.367601E+09 | 0.283058E+09 | 0.00 | 4159981.15 | 57240838.50 | 0.00 | 0.395038E+09 | 0.00 | 0.36 |
April | 29886452.99 | 0.190661E+10 | 0.00 | 3064682.86 | 0.511954E+09 | 0.00 | 77857585.80 | 0.00 | 0.56 |
May | 77311.30 | 0.740285E+10 | 0.00 | 0.00 | 0.100957E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
June | 0.00 | 0.114552E+11 | 0.00 | 0.00 | 0.144694E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
July | 0.00 | 0.146183E+11 | 0.00 | 0.00 | 0.218368E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
August | 0.00 | 0.138750E+11 | 0.00 | 0.00 | 0.218244E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.832505E+10 | 0.00 | 0.00 | 0.175298E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 86051223.27 | 0.159799E+10 | 0.00 | 993271.85 | 0.340637E+09 | 0.00 | 32997241.13 | 0.00 | 0.40 |
November | 0.736739E+09 | 21398931.51 | 0.00 | 2371341.42 | 15488907.63 | 34834205.78 | 0.174804E+09 | 0.00 | 0.30 |
December | 0.141926E+10 | 0.00 | 0.00 | 22299.53 | 251377.73 | 0.572716E+09 | 10653478.02 | 0.00 | 0.30 |
Annual Sum or Average | 0.506975E+10 | 0.594854E+11 | 0.00 | 11822879.40 | 0.950669E+10 | 0.176577E+10 | 0.874322E+09 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.141926E+10 | 0.146183E+11 | 0.00 | 4159981.15 | 0.218368E+10 | 0.927920E+09 | 0.395038E+09 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101794E+10 | 0.00 | 0.00 | 262526.88 | 0.00 | 0.369642E+09 | 0.107667E+09 | 0.00 | 0.31 |
February | 0.472558E+09 | 1299498.68 | 0.00 | 2828888.42 | 2249345.64 | 97798269.36 | 0.519021E+09 | 0.00 | 0.36 |
March | 0.123627E+09 | 0.275624E+09 | 0.00 | 6216388.96 | 25681672.47 | 0.00 | 0.631353E+09 | 0.00 | 0.55 |
April | 9987084.79 | 0.199427E+10 | 0.00 | 4074224.03 | 0.243589E+09 | 0.00 | 0.107088E+09 | 0.00 | 0.83 |
May | 48804.04 | 0.660171E+10 | 0.00 | 954.27 | 0.476139E+09 | 0.00 | 0.00 | 0.00 | 0.96 |
June | 0.00 | 0.917903E+10 | 0.00 | 0.00 | 0.718553E+09 | 0.00 | 0.00 | 0.00 | 0.89 |
July | 0.00 | 0.112836E+11 | 0.00 | 0.00 | 0.112088E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
August | 0.00 | 0.105480E+11 | 0.00 | 0.00 | 0.118538E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 0.00 | 0.699468E+10 | 0.00 | 0.00 | 0.896269E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 36663948.60 | 0.153376E+10 | 0.00 | 1742440.71 | 0.144894E+09 | 0.00 | 75266226.91 | 0.00 | 0.56 |
November | 0.311183E+09 | 23488036.95 | 0.00 | 4237919.21 | 7458326.68 | 8259779.57 | 0.430767E+09 | 0.00 | 0.39 |
December | 0.901070E+09 | 0.00 | 0.00 | 432583.06 | 161789.16 | 0.240949E+09 | 0.149545E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.287308E+10 | 0.484355E+11 | 0.00 | 19795925.54 | 0.482126E+10 | 0.716649E+09 | 0.202071E+10 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.101794E+10 | 0.112836E+11 | 0.00 | 6216388.96 | 0.118538E+10 | 0.369642E+09 | 0.631353E+09 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.948728E+09 | 0.00 | 0.00 | 7676345.68 | 0.00 | 0.426351E+09 | 0.200768E+10 | 0.00 | 0.49 |
February | 0.605067E+09 | 5374173.21 | 0.00 | 11114329.59 | 2032847.98 | 0.108960E+09 | 0.167382E+10 | 0.00 | 0.54 |
March | 0.222558E+09 | 0.525218E+09 | 0.00 | 10628439.91 | 26771233.19 | 0.00 | 0.995197E+09 | 0.00 | 0.59 |
April | 23864402.76 | 0.248667E+10 | 0.00 | 4477294.72 | 0.408368E+09 | 0.00 | 0.105210E+09 | 0.00 | 0.68 |
May | 77252.54 | 0.777061E+10 | 0.00 | 0.00 | 0.920825E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
June | 0.00 | 0.114538E+11 | 0.00 | 0.00 | 0.143457E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
July | 0.00 | 0.148620E+11 | 0.00 | 0.00 | 0.213167E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 0.00 | 0.149659E+11 | 0.00 | 0.00 | 0.195703E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
September | 0.00 | 0.108927E+11 | 0.00 | 0.00 | 0.125603E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 39708744.96 | 0.317303E+10 | 0.00 | 4267864.49 | 0.137178E+09 | 0.00 | 0.129149E+09 | 0.00 | 0.73 |
November | 0.297696E+09 | 90511899.87 | 0.00 | 21874036.50 | 4936770.50 | 0.00 | 0.173729E+10 | 0.00 | 0.75 |
December | 0.837276E+09 | 297772.04 | 0.00 | 9761575.66 | 37639.79 | 0.192522E+09 | 0.218881E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.297498E+10 | 0.662261E+11 | 0.00 | 69799886.55 | 0.827944E+10 | 0.727833E+09 | 0.883716E+10 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.948728E+09 | 0.149659E+11 | 0.00 | 21874036.50 | 0.213167E+10 | 0.426351E+09 | 0.218881E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.890947E+09 | 0.00 | 0.00 | 980501.42 | 0.00 | 0.367484E+09 | 0.298708E+09 | 0.00 | 0.33 |
February | 0.561847E+09 | 3938341.21 | 0.00 | 2859586.19 | 1324033.29 | 82992123.40 | 0.445146E+09 | 0.00 | 0.38 |
March | 0.147912E+09 | 0.337521E+09 | 0.00 | 6075546.53 | 16572105.40 | 0.00 | 0.561595E+09 | 0.00 | 0.56 |
April | 11104628.12 | 0.223752E+10 | 0.00 | 4089696.44 | 0.152028E+09 | 0.00 | 82844497.39 | 0.00 | 0.87 |
May | 5136.82 | 0.713436E+10 | 0.00 | 12025.52 | 0.270094E+09 | 0.00 | 35256.75 | 0.00 | 0.99 |
June | 0.00 | 0.105269E+11 | 0.00 | 0.00 | 0.426755E+09 | 0.00 | 0.00 | 0.00 | 0.98 |
July | 0.00 | 0.123973E+11 | 0.00 | 0.00 | 0.886570E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
August | 0.00 | 0.119795E+11 | 0.00 | 0.00 | 0.853411E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
September | 0.00 | 0.779965E+10 | 0.00 | 0.00 | 0.650822E+09 | 0.00 | 0.00 | 0.00 | 0.71 |
October | 33576359.30 | 0.165813E+10 | 0.00 | 1702136.13 | 0.117058E+09 | 0.00 | 57317579.51 | 0.00 | 0.57 |
November | 0.346545E+09 | 35084749.96 | 0.00 | 4614375.33 | 6535221.53 | 0.00 | 0.394539E+09 | 0.00 | 0.42 |
December | 0.844900E+09 | 0.00 | 0.00 | 1315362.57 | 161891.46 | 0.202969E+09 | 0.335849E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.283684E+10 | 0.541098E+11 | 0.00 | 21649230.14 | 0.338133E+10 | 0.653444E+09 | 0.217603E+10 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.890947E+09 | 0.123973E+11 | 0.00 | 6075546.53 | 0.886570E+09 | 0.367484E+09 | 0.561595E+09 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.607035E+09 | 0.00 | 0.00 | 0.138587E+11 | 0.00 | 0.66 |
February | 0.00 | 0.184771E+09 | 0.00 | 0.994581E+09 | 0.00 | 0.00 | 0.657799E+10 | 0.00 | 0.66 |
March | 0.00 | 0.260477E+10 | 0.00 | 0.843053E+09 | 0.00 | 0.00 | 0.199513E+10 | 0.00 | 0.66 |
April | 0.00 | 0.632200E+10 | 0.00 | 0.385338E+09 | 0.00 | 0.00 | 0.155777E+09 | 0.00 | 0.67 |
May | 0.00 | 0.200938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
June | 0.00 | 0.292965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.393636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.364072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.302029E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.974921E+10 | 0.00 | 84100084.81 | 0.00 | 0.00 | 91025100.06 | 0.00 | 0.66 |
November | 0.00 | 0.982772E+09 | 0.00 | 0.125387E+10 | 0.00 | 0.00 | 0.316410E+10 | 0.00 | 0.66 |
December | 0.00 | 12406.87 | 0.00 | 0.251304E+10 | 0.00 | 0.00 | 0.106899E+11 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.175208E+12 | 0.00 | 0.668101E+10 | 0.00 | 0.00 | 0.365326E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.393636E+11 | 0.00 | 0.251304E+10 | 0.00 | 0.00 | 0.138587E+11 | 0.00 | 0.67 |