Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2020-06-03 19:56:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 29305.09 | 632.66 | 632.66 |
Net Site Energy | 29305.09 | 632.66 | 632.66 |
Total Source Energy | 91668.48 | 1979.01 | 1979.01 |
Net Source Energy | 91668.48 | 1979.01 | 1979.01 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 80.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4595.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2576.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 342.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1955.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2073.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 548.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1661.34 | 0.00 | 0.00 | 0.00 | 0.00 | 11985.02 |
Humidification | 276.91 | 0.00 | 0.00 | 0.00 | 0.00 | 103.01 |
Heat Recovery | 50.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 467.55 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28757.45 | 547.64 | 0.00 | 0.00 | 0.00 | 14368.20 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 80.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2398.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 2196.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 2576.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 342.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2073.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 548.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 535.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 1125.61 | 0.00 | 0.00 | 0.00 | 0.00 | 11985.02 | |
Humidification | General | 276.91 | 0.00 | 0.00 | 0.00 | 0.00 | 103.01 |
Heat Recovery | General | 50.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 467.55 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 197.66 | 11.82 | 0.00 | 0.00 | 0.00 | 0.31 |
Other | 360.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 620.84 | 11.82 | 0.00 | 0.00 | 0.00 | 0.31 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 63.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 197.66 | 11.82 | 0.00 | 0.00 | 0.00 | 0.31 |
Other | 360.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 620.84 | 11.82 | 0.00 | 0.00 | 0.00 | 0.31 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28757.450 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28757.450 | 100.00 |
Total On-Site and Utility Electric Sources | 28757.450 | 100.00 |
Total Electricity End Uses | 28757.450 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 2613.10 | 99.38 |
Air to Air Heat Recovery for Heating | 16.34 | 0.62 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2629.44 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 14368.20 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 14368.20 | 100.00 |
Total Water End Uses | 14368.20 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.33 |
Time Setpoint Not Met During Occupied Cooling | 400.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2671.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.8889 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.8889 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.8889 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.8889 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.8889 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.8889 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.8889 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-15:50 | 06-JAN-09:39 | - | - | - | 30-AUG-15:00 |
Heating | 0.00 | 709867.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 410188.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 223670.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 89219.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 136903.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 39130.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 83768.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4520.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 36724.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1765772.50 | 746592.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 709867.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 241060.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 223670.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3400.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 136903.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 39130.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 39992.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 4520.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 36724.79 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 86.81 | 0.00 | 0.00 | 0.00 |
Cooling | 14553.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8160.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1086.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46479.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6193.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6566.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1736.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5261.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 876.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 159.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 506.83 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 91074.85 | 593.64 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.87 | 0.00 | 0.00 | 0.00 |
Cooling | 314.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 176.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 133.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 141.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 37.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 113.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 18.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.94 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1966.19 | 12.82 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.87 | 0.00 | 0.00 | 0.00 |
Cooling | 314.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 176.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 133.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 141.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 37.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 113.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 18.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.94 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1966.19 | 12.82 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.27 |
DATACENTER BOT DIRECT AIR | 0.456596 |
DATACENTER MID DIRECT AIR | 4.33 |
DATACENTER TOP DIRECT AIR | 0.441132 |
DATACENTER BASEMENT DIRECT AIR | 21.19 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.42 | 0.351222 | 0.299000 | 1.62 | 0.936592 | 0.500000 | 0.001085 | 0.000360 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 50.58 | 0.376021 | 0.320000 | 16.19 | 1.00 | 0.500000 | 0.001013 | 0.007200 | 16.19 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.02 | 0.379255 | 0.322000 | 1.61 | 1.00 | 0.500000 | 0.001005 | 0.001225 | 1.65 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.827849 | 0.288483 | 0.245000 | 0.202823 | 0.769289 | 0.500000 | 0.001321 | 0.000080 | 0.202823 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.973042 | 0.158169 | 0.134000 | 0.130388 | 0.421784 | 0.500000 | 0.002409 | 0.000061 | 0.130388 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.947193 | 0.252141 | 0.214000 | 0.202699 | 0.672375 | 0.500000 | 0.001511 | 0.000121 | 0.202699 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.23 | 0.125078 | 0.106000 | 0.130430 | 0.333541 | 0.500000 | 0.003046 | 0.000034 | 0.130430 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.51 | 0.318108 | 0.270000 | 2.03 | 0.848287 | 0.500000 | 0.001198 | 0.002811 | 3.79 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.01 | 0.410081 | 0.500000 | 0.002478 | 0.001893 | 2.55 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 8.74 | 0.273184 | 0.232000 | 2.03 | 0.728491 | 0.500000 | 0.001395 | 0.002816 | 3.80 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.50 | 0.146571 | 0.125000 | 1.31 | 0.390855 | 0.500000 | 0.002599 | 0.001656 | 2.23 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.860173 | 0.277643 | 0.236000 | 0.203001 | 0.740380 | 0.500000 | 0.001372 | 0.000375 | 0.506376 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.01 | 0.152557 | 0.130000 | 0.131149 | 0.406819 | 0.500000 | 0.002497 | 0.000249 | 0.335801 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.974248 | 0.245139 | 0.208000 | 0.202644 | 0.653703 | 0.500000 | 0.001554 | 0.000375 | 0.506242 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.12 | 0.137399 | 0.117000 | 0.131056 | 0.366396 | 0.500000 | 0.002773 | 0.000230 | 0.310626 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16290.23 | 0.000360 | 283.54 |
CORE_MID VAV BOX REHEAT COIL | 325894.20 | 0.007200 | 6124.57 |
CORE_TOP VAV BOX REHEAT COIL | 55446.54 | 0.001225 | 1158.38 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 3606.32 | 0.000080 | 66.76 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 2759.04 | 0.000061 | 52.21 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5491.40 | 0.000121 | 108.54 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 1546.48 | 0.000034 | 27.44 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 127212.47 | 0.002811 | 2654.94 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 85672.18 | 0.001893 | 1787.92 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 127440.31 | 0.002816 | 2659.69 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 74961.78 | 0.001656 | 1564.59 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16976.79 | 0.000375 | 354.23 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11257.24 | 0.000249 | 234.88 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16972.31 | 0.000375 | 354.14 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10415.22 | 0.000230 | 217.33 |
CAV_BAS_HEATC | 248111.33 | 0.005482 | 4653.17 |
VAV_BOT WITH REHEAT_HEATC | 24264.33 | 0.000536 | 370.47 |
VAV_MID WITH REHEAT_HEATC | 169949.86 | 0.003755 | 2611.36 |
VAV_TOP WITH REHEAT_HEATC | 16439.81 | 0.000363 | 253.10 |
DATACENTER_EXTRAWATERHEATC | 1022953.20 | 0.022601 | 19051.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.27 | 5.27 | 5.27 | 5.27 | 5.27 | 5.27 | 1.00 | 1.00 | 5.27 |
VAV_BOT WITH REHEAT | 4.70 | 2.29 | 9.39 | 2.29 | 8.50 | 8.50 | 0.300000 | 0.268949 | 8.50 |
VAV_MID WITH REHEAT | 43.67 | 22.87 | 87.34 | 23.16 | 78.22 | 78.22 | 0.300000 | 0.296036 | 78.22 |
VAV_TOP WITH REHEAT | 4.49 | 2.28 | 8.98 | 3.31 | 8.33 | 8.33 | 0.300000 | 0.397079 | 8.33 |
AIRLOOP DATACENTER BASEMENT | 21.19 | 21.19 | 21.19 | 21.19 | 21.19 | 21.19 | 1.00 | 1.00 | 21.19 |
AIRLOOP DATACENTER BOT | 0.456596 | 0.456596 | 0.456596 | 0.456596 | 0.456596 | 0.456596 | 1.00 | 1.00 | 0.456596 |
AIRLOOP DATACENTER MID | 4.33 | 4.33 | 4.33 | 4.33 | 4.33 | 4.33 | 1.00 | 1.00 | 4.33 |
AIRLOOP DATACENTER TOP | 0.441132 | 0.441132 | 0.441132 | 0.441132 | 0.441132 | 0.441132 | 1.00 | 1.00 | 0.441132 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.27 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.50 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 78.22 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.33 | |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.19 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.456596 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.33 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.441132 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 123671.01 | 0.003537 | 5.27 | 0.010701 | 25.04 | 6.67 | 11.42 | 0.008284 |
VAV_BOT WITH REHEAT_COOLC | 222096.20 | 0.006352 | 8.50 | 0.010834 | 26.49 | 6.67 | 11.43 | 0.008284 |
VAV_MID WITH REHEAT_COOLC | 2148163.88 | 0.061437 | 78.22 | 0.011143 | 26.80 | 6.67 | 11.43 | 0.008284 |
VAV_TOP WITH REHEAT_COOLC | 214699.63 | 0.006140 | 8.33 | 0.010773 | 26.36 | 6.67 | 11.42 | 0.008284 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.27 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.003537 | 0.000135 |
CAV_BAS_HEATC_CONTROLLER | 0.005482 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006352 | 0.000075 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000536 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.061437 | 0.000008 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.003755 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006140 | 0.000078 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000363 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022601 | 0.000021 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.03 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 20.30 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.03 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.50 |
VAV_MID WITH REHEAT FAN | 78.22 |
VAV_TOP WITH REHEAT FAN | 8.33 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.19 | 429437.13 | 309029.25 | 0.010517 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.456596 | 9224.84 | 6644.93 | 0.000226 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.33 | 87757.62 | 63140.37 | 0.002149 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.441132 | 8927.63 | 6424.98 | 0.000219 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.19 | 21.19 | 21.19 | 21.19 | 429437.13 | 429437.13 | 14481.98 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.456596 | 0.456596 | 0.456596 | 0.456596 | 9224.84 | 9224.84 | 669.01 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.33 | 4.33 | 4.33 | 4.33 | 87757.62 | 87757.62 | 6690.08 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.441132 | 0.441132 | 0.441132 | 0.441132 | 8927.63 | 8927.63 | 669.01 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.19 |
DATACENTER BOT SUPPLY FAN | 0.456596 |
DATACENTER MID SUPPLY FAN | 4.33 |
DATACENTER TOP SUPPLY FAN | 0.441132 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.19 | 429437.13 | 0.010517 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.456596 | 9224.84 | 0.000226 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.33 | 87757.62 | 0.002149 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.441132 | 8927.63 | 0.000219 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 14481.98 | |
DATACENTER_EXTRAELECHEATC | 429437.13 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 669.01 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 6690.08 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 669.01 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000080 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.077466 | 14671.66 |
HEATSYS1 PUMP | 0.052222 | 13210.00 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.077466 | 9.30 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.052222 | 6.27 |
COOLSYS1_SUPPLY | 0.077466 | 9.30 |
SINGLE WATER PLANT LOOP | 0.013111 | 1.57 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.077466 | 0.077466 | 325165.75 | 8.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 56.21 |
COOLSYS1 CHILLER1 PUMP | 0.038733 | 2445.28 |
COOLSYS1 CHILLER2 PUMP | 0.038733 | 2445.28 |
PLANT CIRC PUMP | 0.013111 | 3310.76 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2363661.03 | 1181830.51 | 0.052222 |
DUMMY BOILER | 540045.10 | 93894.07 | 0.013111 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.077466 | 0.039069 | 1369396.65 | 1375892.86 | 0.068088 |
COOLSYS1 CHILLER2 | 0.077466 | 0.039069 | 1369396.65 | 1375892.86 | 0.068088 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013111 | 139666.47 | 60034.16 | 69833.23 | 7004.20 | 21488.72 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.136176 | 16.34 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.136176 | 28532.06 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 52.67 | 1305983.69 | 10.53 | 163247.96 |
TOWERWATERSYS COOLTOWER 2 | 52.67 | 1305983.69 | 10.53 | 163247.96 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.056578 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.889 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.731 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.889 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.959 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 6.889 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.188 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 6.889 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.188 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 6.889 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.188 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 6.889 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.312 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 19147.199 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19147.199 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 17195.531 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17195.531 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 17195.531 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17195.531 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 17195.531 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17195.531 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2159.071 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.071 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2159.118 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.118 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2159.071 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.071 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2159.118 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.118 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2159.071 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.071 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2159.118 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2159.118 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1391.387 | 6.889 | 127.988 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1391.387 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 5398.691 | 6.889 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5398.691 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 249.397 | 6.889 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 249.397 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 249.397 | 6.889 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 249.397 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 249.397 | 6.889 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 249.397 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.9837 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8493 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.31844121E-15 | 0.33891907E-16 | -0.14717764E-09 | -0.34085343E-17 |
51 | 8 | 0.21517510E-07 | 0.13210865E-12 | 0.37403321E-03 | -0.24466149E-09 |
52 | 7 | -0.12129356E-01 | 0.68855956E-08 | -0.22924263E-01 | 0.13791520E-03 |
53 | 6 | 0.40230169 | 0.24029480E-05 | 0.46949424 | -0.47118258E-02 |
54 | 5 | -5.1608121 | 0.89965799E-04 | -4.4213154 | 0.62814943E-01 |
55 | 4 | 32.871256 | 0.73775273E-03 | 21.362378 | -0.42037561 |
56 | 3 | -110.94624 | 0.16114037E-02 | -55.469893 | 1.5111496 |
57 | 2 | 196.85374 | 0.90819125E-03 | 77.733479 | -2.8963115 |
58 | 1 | -171.06207 | 0.97128343E-04 | -55.213590 | 2.7437919 |
59 | 0 | 57.057407 | 0.55402955E-06 | 15.565444 | |
60 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
61 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
62 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
63 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
64 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
65 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
66 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
67 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
68 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
69 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
70 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
71 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
72 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
73 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
74 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
75 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
76 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
77 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
78 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
79 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
80 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
81 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
82 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
83 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
84 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
85 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
86 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
87 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
88 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
89 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
90 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
91 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
92 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
93 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
94 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
95 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
96 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
97 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
98 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
99 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
100 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
101 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
102 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
103 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
104 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
105 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
106 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
107 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.46_SHGC_0.25 | 29 | 1 | VerySmooth | 2.615 | 0.252 | 0.162 | 0.276 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.53892E-002 | 0.16139 | 0.61607 | 0.61607 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 73132.29152 | 73132.29152 | 5.26846 | 5.26846 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 75182.97745 | 75182.97745 | 5.41550 | 5.41550 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 702466.03789 | 702466.03789 | 50.58350 | 50.58350 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 163048.63382 | 163048.63382 | 6.81272 | 10.77757 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 69649.53220 | 69649.53220 | 5.01521 | 5.01521 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 38877.31147 | 38877.31147 | 1.64697 | 1.64697 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11384.61413 | 11384.61413 | 0.82785 | 0.82785 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.90000 | 1.65138E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 1570.37120 | 1570.37120 | 6.65121E-002 | 0.13532 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 13381.39951 | 13381.39951 | 0.97304 | 0.97304 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 30.00267 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 1449.95019 | 1449.95019 | 6.11555E-002 | 8.72074E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 13025.85807 | 13025.85807 | 0.94719 | 0.94719 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 33.70250 | 1.65138E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 3455.28014 | 3455.28014 | 0.14572 | 0.14572 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16921.69154 | 16921.69154 | 1.23047 | 1.23047 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 238.13393 | 238.13393 | 1.02155E-002 | 8.72074E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 103242.25166 | 103242.25166 | 7.50754 | 7.50754 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 33.90000 | 1.65138E-002 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 89092.70771 | 89092.70771 | 3.79171 | 3.79171 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 137630.79352 | 137630.79352 | 10.00810 | 10.00810 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 30.45033 | 1.65138E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 59995.42318 | 59995.42318 | 2.55389 | 2.55389 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 120222.63384 | 120222.63384 | 8.74230 | 8.74230 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65138E-002 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 89251.98077 | 89251.98077 | 3.79852 | 3.79852 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 144400.90908 | 144400.90908 | 10.50040 | 10.50040 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 32.66233 | 1.65138E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 52509.31216 | 52509.31216 | 2.23369 | 2.23369 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11828.87319 | 11828.87319 | 0.86017 | 0.86017 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65138E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 11884.25932 | 11884.25932 | 0.50638 | 0.50638 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 13873.35295 | 13873.35295 | 1.00884 | 1.00884 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 30.67417 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 7880.08746 | 7880.08746 | 0.33580 | 0.33580 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 13397.63037 | 13397.63037 | 0.97425 | 0.97425 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65138E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 11881.13418 | 11881.13418 | 0.50624 | 0.50624 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 15403.96443 | 15403.96443 | 1.12014 | 1.12014 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 32.66233 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 7291.58425 | 7291.58425 | 0.31063 | 0.31063 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 7961.95340 | 7961.95340 | 0.45660 | 0.45660 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 26.05267 | 1.65138E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 75577.22997 | 75577.22997 | 4.33415 | 4.33415 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 26.05267 | 1.65138E-002 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7692.29602 | 7692.29602 | 0.44113 | 0.44113 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65138E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369530.60534 | 369530.60534 | 21.19157 | 21.19157 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 26.25017 | 1.65138E-002 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 77669.87 | 5.26846 | 5.26846 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 51362.34 | 1.20008 | 1.20008 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 132489.61 | 8.49817 | 8.49817 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 15200.18 | 1.53322 | 1.53322 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1195712.07 | 78.21819 | 78.21819 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 201112.34 | 23.15539 | 23.15539 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 136144.18 | 8.32582 | 8.32582 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 19956.49 | 3.30601 | 3.30601 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 366031.03 | 21.19157 | 21.19157 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14481.98 | 0.33837 | 0.33837 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7883.63 | 0.45660 | 0.45660 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 669.01 | 1.56314E-002 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 75111.38 | 4.33415 | 4.33415 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6690.08 | 0.15631 | 0.15631 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7653.68 | 0.44113 | 0.44113 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 669.01 | 1.56314E-002 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.26846 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.41550 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35122 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29900 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61924 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93659 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08478E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.59913E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61924 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16290.22827 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.59913E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 283.53562 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 50.58350 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37602 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18672 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01324E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.20023E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.18672 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 325894.19939 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.20023E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6124.57380 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.01521 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37925 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32200 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61490 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00460E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.22502E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.64697 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 55446.53634 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22502E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1158.38315 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82785 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28848 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24500 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20282 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76929 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.32070E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.96772E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20282 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3606.31635 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.96772E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 66.76313 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97304 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15817 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13400 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13039 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42178 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.40882E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.09576E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13039 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2759.04039 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.09576E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 52.21143 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94719 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25214 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21400 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20270 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67237 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51106E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21326E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20270 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5491.40018 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21326E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 108.54464 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23047 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12508 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10600 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13043 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33354 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04610E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.41676E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13043 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1546.47969 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.41676E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 27.44356 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.50754 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31811 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02704 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84829 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19771E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.81060E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.79171 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 127212.47317 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.81060E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2654.93699 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.00810 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41008 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.47756E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.89282E-003 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.55389 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 85672.18349 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89282E-003 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1787.91557 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.74230 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27318 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23200 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02821 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72849 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.39466E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.81564E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.79852 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 127440.31059 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.81564E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2659.68830 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.50040 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14657 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12500 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.31255 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39086 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59943E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.65619E-003 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.23369 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 74961.78313 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.65619E-003 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1564.59221 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86017 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27764 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23600 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20300 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74038 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37227E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.75081E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50638 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16976.78759 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.75081E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 354.23027 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00884 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15256 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13000 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13115 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40682 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49742E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.48715E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33580 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11257.24400 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.48715E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 234.88350 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97425 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24514 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20800 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20264 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65370 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55422E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.74982E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50624 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16972.31012 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.74982E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 354.13700 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12014 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13740 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11700 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13106 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36640 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77295E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.30111E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31063 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10415.21674 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.30111E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 217.32670 |
209 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45660 |
210 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.33415 |
211 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44113 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.19157 |
213 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.26846 |
214 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.26846 |
215 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.26846 |
216 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.26846 |
217 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.26846 |
218 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.26846 |
219 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
220 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.69703 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28558 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.39406 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28558 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.49817 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.49817 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.26895 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 43.67092 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.86558 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 87.34184 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 23.15539 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 78.21819 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 78.21819 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29604 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.48930 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28275 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.97861 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.30601 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.32582 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.32582 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.39708 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.19157 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.19157 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.19157 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.19157 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.19157 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.19157 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45660 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45660 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45660 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45660 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45660 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.45660 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.33415 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.33415 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.33415 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.33415 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.33415 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.33415 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44113 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44113 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44113 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44113 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44113 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.44113 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.26846 |
278 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.49817 |
279 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 78.21819 |
280 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.32582 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.19157 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.45660 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.33415 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.44113 |
285 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.26846 |
286 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
287 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 123671.01467 |
288 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 3.53698E-003 |
289 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.26846 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.07013E-002 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 25.04031 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42469 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
295 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 248111.32565 |
296 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.48172E-003 |
297 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 4653.16504 |
298 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.26846 |
299 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.53698E-003 |
300 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.34632E-004 |
301 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.48172E-003 |
302 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.49817 |
303 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03040 |
304 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 222096.20085 |
305 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 6.35192E-003 |
306 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.49817 |
307 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.08342E-002 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.49017 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42502 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
312 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 24264.33029 |
313 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.36091E-004 |
314 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 370.46515 |
315 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.49817 |
316 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.35192E-003 |
317 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.49679E-005 |
318 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.36091E-004 |
319 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 78.21819 |
320 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 20.30400 |
321 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 2148163.88085 |
322 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 6.14372E-002 |
323 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 78.21819 |
324 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.11433E-002 |
325 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.79881 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42579 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
329 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 169949.85660 |
330 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 3.75483E-003 |
331 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 2611.35732 |
332 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 78.21819 |
333 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.14372E-002 |
334 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.75085E-006 |
335 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.75483E-003 |
336 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.32582 |
337 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03040 |
338 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 214699.63135 |
339 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 6.14038E-003 |
340 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.32582 |
341 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.07726E-002 |
342 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.36185 |
343 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42487 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
346 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 16439.80889 |
347 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 3.63217E-004 |
348 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 253.10177 |
349 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.32582 |
350 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.14038E-003 |
351 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.75506E-005 |
352 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.63217E-004 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.19157 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.19157 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 429437.13488 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 309029.24759 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.05169E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.19157 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.19157 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.19157 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.19157 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 429437.13488 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 429437.13488 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14481.98191 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.19157 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.19157 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 429437.13488 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.05169E-002 |
371 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 14481.98191 |
372 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 7.96218E-005 |
373 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 429437.13488 |
377 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
378 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1022953.20398 |
379 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.26009E-002 |
380 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19051.64573 |
381 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.26009E-002 |
382 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.10695E-005 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45660 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.45660 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9224.83603 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6644.93059 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.25916E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45660 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45660 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45660 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45660 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9224.83603 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9224.83603 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.00757 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45660 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.45660 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9224.83603 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.25916E-004 |
400 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 669.00757 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.33415 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.33415 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 87757.61544 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 63140.37024 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.14918E-003 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.33415 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.33415 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.33415 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.33415 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 87757.61544 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 87757.61544 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6690.07569 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
414 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.33415 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.33415 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 87757.61544 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.14918E-003 |
418 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 6690.07569 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44113 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.44113 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 8927.63239 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 6424.97600 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.18637E-004 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.44113 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.44113 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.44113 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.44113 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 8927.63239 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 8927.63239 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.00757 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
432 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44113 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.44113 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 8927.63239 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.18637E-004 |
436 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 669.00757 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.74665E-002 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 14671.65623 |
439 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.74665E-002 |
440 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.29598 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.74665E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.74665E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 325165.75363 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
445 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
446 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
447 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
448 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 56.20535 |
449 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
450 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.22222E-002 |
451 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 6.26666 |
452 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.22222E-002 |
453 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 13210.00301 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2363661.03486 |
455 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1181830.51500 |
456 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.22222E-002 |
457 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.74665E-002 |
458 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.29598 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.87332E-002 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 2445.27604 |
461 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.87332E-002 |
462 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 2445.27604 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.74665E-002 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.90686E-002 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1369396.64846 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1375892.86000 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.80878E-002 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.74665E-002 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.90686E-002 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1369396.64846 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1375892.86000 |
472 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.80878E-002 |
473 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.31106E-002 |
474 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.57327 |
475 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.31106E-002 |
476 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3310.75590 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.31106E-002 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 60034.15906 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21488.72160 |
483 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 540045.10198 |
484 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
485 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.31106E-002 |
486 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13618 |
487 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.34108 |
488 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13618 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 28532.05750 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 52.67139 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1305983.68756 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.53428 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 163247.96094 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 52.67139 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1305983.68756 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.53428 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 163247.96094 |
498 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 5.65780E-002 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 5.65780E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15454.66 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 309395.36 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 52606.32 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 3424.37 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 2619.24 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5211.61 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 1466.89 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 120696.45 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 81283.93 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 120912.62 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 71122.11 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16107.22 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10680.64 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16102.97 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9881.74 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 201797.72 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 20676.77 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 148436.21 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 14464.06 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 822612.97 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 148216.65 | 100886.28 | 47330.37 | 0.68 | 31327.71 | 317.74 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 249382.98 | 167136.75 | 82246.23 | 0.67 | 50196.28 | 509.12 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2331670.91 | 1553950.17 | 777720.73 | 0.67 | 455467.13 | 4619.60 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 243278.78 | 163299.53 | 79979.25 | 0.67 | 49403.00 | 501.07 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.34 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.34 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.46_SHGC_0.25 | N/A | 2.615 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 25 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2134342594 | 0.2107382842 | Pass | Pass | 0.6848243366 | 0.6271172475 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2298774314 | 0.2471063139 | Pass | Pass | 0.2486339090 | 0.4311523240 | Pass | Fail |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1315538848 | 0.1806543624 | Pass | Pass | 0.2024027402 | 0.4003501937 | Pass | Fail |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1158158444 | 0.1724821504 | Pass | Pass | 0.1887972210 | 0.3898017372 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1918819549 | 0.2176566975 | Pass | Pass | 0.2450596088 | 0.4280617434 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2371513765 | 0.2845095345 | Pass | Pass | 0.2548762532 | 0.4350729637 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3927504483 | 0.5869014075 | Pass | Pass | 0.2726599848 | 0.4482334663 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2664802969 | 0.3797700247 | Pass | Pass | 0.2625655580 | 0.4563750638 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1182292524 | 0.1679715971 | Pass | Pass | 0.2023158754 | 0.3992506423 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1623837756 | 0.1971476487 | Pass | Pass | 0.2024783048 | 0.4009446389 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3394346345 | 0.5943049101 | Pass | Pass | 0.2172261650 | 0.4081350159 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1565210805 | 0.2599181901 | Pass | Pass | 0.2056234627 | 0.4017408151 | Pass | Fail |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1128868329 | 0.1657041539 | Pass | Pass | 0.1888548594 | 0.3886268662 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1589131490 | 0.1830220742 | Pass | Pass | 0.1886311598 | 0.3905935165 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3352383491 | 0.5925965713 | Pass | Pass | 0.2037222878 | 0.4023584781 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1549829854 | 0.2653263580 | Pass | Pass | 0.1934026816 | 0.3932352963 | Pass | Fail |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.7367348002E-002 | 3.5033219554E-002 | Pass | Pass | 0.2757035362 | 0.4537310169 | Pass | Fail |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2702020900E-002 | 2.4257016624E-002 | Pass | Pass | 0.2288836154 | 0.4186119329 | Fail | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.7305198582E-002 | 6.0682406581E-002 | Pass | Pass | 0.2347651124 | 0.6150269326 | Fail | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.9918685641E-014 | 3.9691818353E-014 | Pass | Pass | 3.0995978859E-003 | 4.4195420965E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.6020569243E-014 | 3.1322507730E-014 | Pass | Pass | 4.4123824412E-003 | 5.3316817487E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.8173512905E-012 | 1.7070961573E-011 | Pass | Pass | 7.6023533965E-003 | 5.3125485410E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.9998991849E-004 | 3.2137930397E-004 | Pass | Pass | 4.8562763392E-005 | 5.3083239541E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.46_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.46_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.46_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.46_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.46_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.46_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.46_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.46_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.46_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.46_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.46_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.46_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.46_SHGC_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.46_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.46_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.46_SHGC_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.615 | 0.252 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.615 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.615 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.615 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.615 | 0.252 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.615 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.615 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.615 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.46_SHGC_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.615 | 0.252 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 4635.80 | 2.615 | 0.252 | 0.276 | ||||||||||||
North Total or Average | 1390.74 | 2.615 | 0.252 | 0.276 | ||||||||||||
Non-North Total or Average | 3245.06 | 2.615 | 0.252 | 0.276 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 6.8889 | 2779.43 | 19147.20 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.71 | 0.0000 | Y | 175.08 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 6.8889 | 2496.12 | 17195.53 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.71 | 0.0000 | Y | 157.23 |
CORE_MID_LIGHTS | CORE_MID | 6.8889 | 24961.20 | 171955.31 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.71 | 0.0000 | Y | 1572.35 |
CORE_TOP_LIGHTS | CORE_TOP | 6.8889 | 2496.12 | 17195.53 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 48.71 | 0.0000 | Y | 157.23 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 6.8889 | 313.41 | 2159.07 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.45 | 0.0000 | Y | 11.12 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 6.8889 | 201.98 | 1391.39 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.31 | 0.0000 | Y | 7.13 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 6.8889 | 313.42 | 2159.12 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.14 | 0.0000 | Y | 11.00 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 6.8889 | 201.98 | 1391.39 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.30 | 0.0000 | Y | 7.13 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 6.8889 | 3134.13 | 21590.71 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.39 | 0.0000 | Y | 111.02 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 6.8889 | 2019.75 | 13913.87 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.28 | 0.0000 | Y | 71.24 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 6.8889 | 3134.20 | 21591.18 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.12 | 0.0000 | Y | 109.90 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 6.8889 | 2019.75 | 13913.87 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.26 | 0.0000 | Y | 71.19 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 6.8889 | 313.41 | 2159.07 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.39 | 0.0000 | Y | 11.10 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 6.8889 | 201.98 | 1391.39 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.27 | 0.0000 | Y | 7.12 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 6.8889 | 313.42 | 2159.12 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.12 | 0.0000 | Y | 10.99 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 6.8889 | 201.98 | 1391.39 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 27.26 | 0.0000 | Y | 7.12 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 6.8889 | 783.68 | 5398.69 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 50.68 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 6.8889 | 36.20 | 249.40 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 2.34 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 6.8889 | 362.03 | 2493.97 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 23.41 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 6.8889 | 36.20 | 249.40 | LightsWired | BLDG_LIGHT_SCH | 51.32 | 168.00 | 50.00 | 0.0000 | Y | 2.34 |
Interior Lighting Total | 6.8889 | 46320.38 | 319096.58 | 813.54 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.07 | 832.75 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.07 | 299.03 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.12 | 832.77 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.12 | 299.04 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.07 | 832.75 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.07 | 299.03 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.12 | 832.77 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.12 | 299.04 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.07 | 832.75 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.07 | 299.03 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2159.12 | 832.77 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2159.12 | 299.04 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1391.39 | 536.66 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1391.39 | 192.71 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 12979.20 | AstronomicalClock | - | 41.73 | 41.73 | 101.66 | |
EXTERIOR_LIGHTS_B | 968.00 | AstronomicalClock | - | 83.73 | 62.73 | 11.40 | |
EXTERIOR_LIGHTS_C | 26027.00 | AstronomicalClock | - | 83.73 | 47.05 | 229.88 | |
Exterior Lighting Total | 39974.20 | 342.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2700287.90 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1181830.51 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1375892.86 | 6.28 | 6.84 | 23.34 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1375892.86 | 6.28 | 6.84 | 23.34 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1305983.69 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1305983.69 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 123671.01 | 148216.65 | 100886.28 | 47330.37 | 0.68 | - | 31327.71 | 317.74 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 222096.20 | 249382.98 | 167136.75 | 82246.23 | 0.67 | - | 50196.28 | 509.12 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 2148163.88 | 2331670.91 | 1553950.17 | 777720.73 | 0.67 | - | 455467.13 | 4619.60 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 214699.63 | 243278.78 | 163299.53 | 79979.25 | 0.67 | - | 49403.00 | 501.07 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 429437.13 | 309029.25 | 120407.89 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9224.84 | 6644.93 | 2579.91 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 87757.62 | 63140.37 | 24617.25 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 8927.63 | 6424.98 | 2502.66 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16290.23 | 15454.66 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 325894.20 | 309395.36 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 55446.54 | 52606.32 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 3606.32 | 3424.37 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 2759.04 | 2619.24 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5491.40 | 5211.61 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 1546.48 | 1466.89 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 127212.47 | 120696.45 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 85672.18 | 81283.93 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 127440.31 | 120912.62 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 74961.78 | 71122.11 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16976.79 | 16107.22 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11257.24 | 10680.64 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16972.31 | 16102.97 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10415.22 | 9881.74 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 248111.33 | 201797.72 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 24264.33 | 20676.77 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 169949.86 | 148436.21 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 16439.81 | 14464.06 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 429437.13 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9224.84 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 87757.62 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 8927.63 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 14481.98 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1022953.20 | 822612.97 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 669.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 6690.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 669.01 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.27 | 8933.49 | 1695.65 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.50 | 18364.10 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 78.22 | 169025.33 | 2160.95 | 1.00 | 1.08 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.33 | 17991.66 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.19 | 35135.06 | 1657.97 | 1.00 | 1.13 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 511.44 | 1120.11 | 1.00 | 1.65 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.33 | 4854.71 | 1120.11 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.44 | 494.12 | 1120.11 | 1.00 | 1.67 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 134283.83 | 0.077466 | 14671.66 | 189393.57 | 0.91 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.052222 | 13210.00 | 252957.60 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.038733 | 2445.28 | 63131.19 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.038733 | 2445.28 | 63131.19 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013111 | 3310.76 | 252524.76 | 0.91 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.136176 | 28532.06 | 209523.88 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 73132.29 | 73132.29 | 26.31 | 5.268 | 5.268 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00898 | 28.05 | 0.01651 | 1.200 | 0.00 |
CORE_BOTTOM | 75182.98 | 75182.98 | 30.12 | 5.416 | 5.416 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 28.05 | 0.01651 | 1.078 | 0.00 |
CORE_MID | 702466.04 | 702466.04 | 281.42 | 50.583 | 50.583 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 28.05 | 0.01651 | 10.778 | 0.00 |
CORE_TOP | 69649.53 | 69649.53 | 27.90 | 5.015 | 5.015 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 28.05 | 0.01651 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11384.61 | 11384.61 | 36.32 | 0.828 | 0.828 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00888 | 33.90 | 0.01651 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 13381.40 | 13381.40 | 66.25 | 0.973 | 0.973 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00871 | 30.00 | 0.01651 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 13025.86 | 13025.86 | 41.56 | 0.947 | 0.947 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00883 | 33.70 | 0.01651 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16921.69 | 16921.69 | 83.78 | 1.230 | 1.230 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00866 | 32.79 | 0.01651 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 103242.25 | 103242.25 | 329.41 | 7.508 | 7.508 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00897 | 33.90 | 0.01651 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 137630.79 | 137630.79 | 681.42 | 10.008 | 10.008 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 24.00 | 24.00 | 0.00873 | 30.45 | 0.01651 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 120222.63 | 120222.63 | 383.58 | 8.742 | 8.742 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00891 | 33.77 | 0.01651 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 144400.91 | 144400.91 | 714.94 | 10.500 | 10.500 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00872 | 32.66 | 0.01651 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11828.87 | 11828.87 | 37.74 | 0.860 | 0.860 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00893 | 33.82 | 0.01651 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13873.35 | 13873.35 | 68.69 | 1.009 | 1.009 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 24.00 | 24.00 | 0.00874 | 30.67 | 0.01651 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13397.63 | 13397.63 | 42.75 | 0.974 | 0.974 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00888 | 33.90 | 0.01651 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15403.96 | 15403.96 | 76.27 | 1.120 | 1.120 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00872 | 32.66 | 0.01651 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 7961.95 | 7961.95 | 219.93 | 0.457 | 0.457 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.05 | 0.01651 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 75577.23 | 75577.23 | 2087.61 | 4.334 | 4.334 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.05 | 0.01651 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7692.30 | 7692.30 | 212.48 | 0.441 | 0.441 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 31.21 | 0.01651 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369530.61 | 369530.61 | 471.53 | 21.192 | 21.192 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 27.00 | 27.00 | 0.00850 | 26.25 | 0.01651 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.078 | 0.00 | |
CORE_MID | 163048.63 | 163048.63 | 65.32 | 6.813 | 10.778 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 10.778 | 0.00 |
CORE_TOP | 38877.31 | 38877.31 | 15.58 | 1.647 | 1.647 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 1570.37 | 1570.37 | 5.01 | 0.067 | 0.135 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00682 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 1449.95 | 1449.95 | 7.18 | 0.061 | 0.087 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00694 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 3455.28 | 3455.28 | 11.02 | 0.146 | 0.146 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00722 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 238.13 | 238.13 | 1.18 | 0.010 | 0.087 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 21.00 | 21.00 | 0.00641 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 89092.71 | 89092.71 | 284.27 | 3.792 | 3.792 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 59995.42 | 59995.42 | 297.04 | 2.554 | 2.554 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00771 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 89251.98 | 89251.98 | 284.77 | 3.799 | 3.799 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 52509.31 | 52509.31 | 259.98 | 2.234 | 2.234 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00760 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11884.26 | 11884.26 | 37.92 | 0.506 | 0.506 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 7880.09 | 7880.09 | 39.02 | 0.336 | 0.336 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 11881.13 | 11881.13 | 37.91 | 0.506 | 0.506 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 7291.58 | 7291.58 | 36.10 | 0.311 | 0.311 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | 4.60 | 0.00526 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.27 | 5.27 | 1.20 | 1.20 | 5.2685 | 5.2685 | 5.2685 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 8.50 | 8.50 | 1.53 | 1.53 | 8.4982 | 2.2856 | 8.4982 | 0.2689 | 0.3000 |
VAV_MID WITH REHEAT | 78.22 | 78.22 | 23.16 | 23.16 | 78.2182 | 23.1554 | 78.2182 | 0.2960 | 0.3000 |
VAV_TOP WITH REHEAT | 8.33 | 8.33 | 3.31 | 3.31 | 8.3258 | 3.3060 | 8.3258 | 0.3971 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.19 | 21.19 | 0.34 | 0.34 | 21.1916 | 21.1916 | 21.1916 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.46 | 0.46 | 0.02 | 0.02 | 0.4566 | 0.4566 | 0.4566 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.33 | 4.33 | 0.16 | 0.16 | 4.3341 | 4.3341 | 4.3341 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.44 | 0.44 | 0.02 | 0.02 | 0.4411 | 0.4411 | 0.4411 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16290.228 | 16290.228 | 1.619236 | 0.00035991 | 283.536 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 15454.66 | 16290.23 | 1.619236 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 16355.76 | 16355.76 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 325894.199 | 325894.199 | 16.186719 | 0.00720023 | 6124.574 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 309395.36 | 325894.20 | 16.186719 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 163048.63 | 0.00 | 327453.05 | 327453.05 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 55446.536 | 55446.536 | 1.646968 | 0.00122502 | 1158.383 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52606.32 | 55446.54 | 1.646968 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 38877.31 | 0.00 | 55699.72 | 55699.72 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 3606.316 | 3606.316 | 0.202823 | 0.00007968 | 66.763 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3424.37 | 3606.32 | 0.202823 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00681694 | 44.1171 | 1570.37 | 0.00 | 3623.98 | 3623.98 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 2759.040 | 2759.040 | 0.130388 | 0.00006096 | 52.211 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2619.24 | 2759.04 | 0.130388 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00693506 | 44.8736 | 1449.95 | 0.00 | 2772.19 | 2772.19 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5491.400 | 5491.400 | 0.202699 | 0.00012133 | 108.545 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5211.61 | 5491.40 | 0.202699 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00722072 | 46.7012 | 3455.28 | 0.00 | 5516.92 | 5516.92 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 1546.480 | 1546.480 | 0.130430 | 0.00003417 | 27.444 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 1466.89 | 1546.48 | 0.130430 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00640968 | 41.5074 | 238.13 | 0.00 | 1552.53 | 1552.53 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 127212.473 | 127212.473 | 3.791709 | 0.00281060 | 2654.937 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 120696.45 | 127212.47 | 3.791709 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00768324 | 49.6563 | 89092.71 | 0.00 | 127793.28 | 127793.28 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 85672.183 | 85672.183 | 2.553892 | 0.00189282 | 1787.916 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 81283.93 | 85672.18 | 2.553892 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00770873 | 49.8189 | 59995.42 | 0.00 | 86063.33 | 86063.33 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 127440.311 | 127440.311 | 3.798518 | 0.00281564 | 2659.688 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 120912.62 | 127440.31 | 3.798518 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00768472 | 49.6657 | 89251.98 | 0.00 | 128022.15 | 128022.15 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 74961.783 | 74961.783 | 2.233695 | 0.00165619 | 1564.592 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 71122.11 | 74961.78 | 2.233695 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00759934 | 49.1210 | 52509.31 | 0.00 | 75304.03 | 75304.03 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 16976.788 | 16976.788 | 0.506376 | 0.00037508 | 354.230 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16107.22 | 16976.79 | 0.506376 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00784311 | 50.6755 | 11884.26 | 0.00 | 17054.29 | 17054.29 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11257.244 | 11257.244 | 0.335801 | 0.00024872 | 234.884 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10680.64 | 11257.24 | 0.335801 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00785262 | 50.7362 | 7880.09 | 0.00 | 11308.64 | 11308.64 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 16972.310 | 16972.310 | 0.506242 | 0.00037498 | 354.137 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16102.97 | 16972.31 | 0.506242 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00784290 | 50.6742 | 11881.13 | 0.00 | 17049.80 | 17049.80 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10415.217 | 10415.217 | 0.310626 | 0.00023011 | 217.327 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9881.74 | 10415.22 | 0.310626 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00780369 | 50.4244 | 7291.58 | 0.00 | 10462.77 | 10462.77 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 123671.015 | -999.000 | 5.268463 | 0.00353698 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 123671.01 | 86109.16 | 5.268463 | 25.04 | 18.54 | 0.01070129 | 11.42 | 11.42 | 0.00828381 | 28.55 | 0.01651377 | 23.71 | 22.7786 | 24.00 | 0.00897937 | 48.2638 | 72176.01 | 0.00 | 136232.08 | 93004.72 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 248111.326 | 248111.326 | 5.268463 | 0.00548172 | 4653.165 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 201797.72 | 228818.13 | 5.268463 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 22.7786 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 212985.31 | 212985.31 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 222096.201 | -999.000 | 8.498173 | 0.00635192 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 222096.20 | 156737.36 | 8.498173 | 26.49 | 19.11 | 0.01083422 | 11.43 | 12.09 | 0.00828381 | 33.82 | 0.01651377 | 25.08 | 23.8922 | 24.00 | 0.00884933 | 47.5744 | 110080.30 | 0.00 | 242400.83 | 166959.12 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 24264.330 | 24264.330 | 2.549452 | 0.00053609 | 370.465 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20676.77 | 24264.33 | 2.549452 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.58 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 79.6406 | 21.00 | 0.00767049 | 49.5725 | 6655.94 | 0.00 | 21870.49 | 21870.49 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2148163.881 | -999.000 | 78.218185 | 0.06143721 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2148163.88 | 1472978.36 | 78.218185 | 26.80 | 19.44 | 0.01114329 | 11.43 | 12.09 | 0.00828381 | 33.74 | 0.01651377 | 25.06 | 25.9582 | 24.00 | 0.00889160 | 47.7986 | 971557.19 | 0.00 | 2334982.47 | 1567256.89 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 169949.857 | 169949.857 | 23.465456 | 0.00375483 | 2611.357 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 148436.21 | 169949.86 | 23.465456 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.58 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 86.5272 | 21.00 | 0.00782563 | 50.5638 | 327578.84 | 0.00 | 157030.47 | 157030.47 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 214699.631 | -999.000 | 8.325823 | 0.00614038 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 214699.63 | 152234.49 | 8.325823 | 26.36 | 19.02 | 0.01077257 | 11.42 | 12.09 | 0.00828381 | 33.66 | 0.01651378 | 25.04 | 24.3868 | 24.00 | 0.00888797 | 47.7794 | 114185.96 | 0.00 | 234545.74 | 162220.70 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 16439.809 | 16439.809 | 2.497747 | 0.00036322 | 253.102 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14464.06 | 16439.81 | 2.497747 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.58 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 81.2893 | 21.00 | 0.00791850 | 51.1556 | 37469.59 | 0.00 | 15301.70 | 15301.70 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 429437.135 | 309029.248 | 21.191571 | 0.01051689 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 458999.20 | 450463.61 | -999.0 | 28.51 | 18.02 | 0.00862817 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 368912.88 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9224.836 | 6644.931 | 0.456596 | 0.00022592 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 9865.27 | 9469.78 | -999.0 | 28.09 | 18.00 | 0.00877557 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01651378 | 24.41 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 7926.57 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 87757.615 | 63140.370 | 4.334148 | 0.00214918 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 93815.48 | 89875.53 | -999.0 | 28.10 | 18.01 | 0.00878939 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01651378 | 24.41 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 75482.20 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8927.632 | 6424.976 | 0.441132 | 0.00021864 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9544.65 | 9150.95 | -999.0 | 28.10 | 18.01 | 0.00878408 | 12.80 | 12.09 | 0.00850000 | 31.41 | 0.01651378 | 24.46 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 7689.21 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 429437.135 | 429437.135 | 21.191571 | 0.01051689 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 429437.13 | 429437.13 | 21.191571 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5967 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9224.836 | 9224.836 | 0.456596 | 0.00022592 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9224.84 | 9224.84 | 0.456596 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.4235 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 87757.615 | 87757.615 | 4.334148 | 0.00214918 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 87757.62 | 87757.62 | 4.334148 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.6066 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8927.632 | 8927.632 | 0.441132 | 0.00021864 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8927.63 | 8927.63 | 0.441132 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5435 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14481.982 | 14481.982 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14481.98 | 14481.98 | 21.191571 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5967 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 920385.25 | 21.191571 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5967 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1022953.204 | 1022953.204 | 21.191571 | 0.02260090 | 19051.646 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 822612.97 | 920385.25 | 21.191571 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5967 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 0.456596 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.4235 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6690.076 | 6690.076 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6690.08 | 6690.08 | 4.334148 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.6066 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 0.441132 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5435 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16290.228 | 16290.228 | 1.619236 | 0.00035991 | 283.536 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 0.6409 | 0.689195 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 15454.66 | 16290.23 | 1.0000 | 1.94821085 | 1.619236 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.35987597 | 60.00 | 49.00 | 11.00 | 0.000 | 15454.66 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 16355.76 | 16355.76 | 1.94821085 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 325894.199 | 325894.199 | 16.186719 | 0.00720023 | 6124.574 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 12.8314 | 13.787688 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 309395.36 | 325894.20 | 1.0000 | 19.47532430 | 16.186719 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 7.19949962 | 60.00 | 49.00 | 11.00 | 0.000 | 309395.36 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 163048.63 | 0.00 | 327453.05 | 327453.05 | 19.47532430 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 29.29 | 17.78 | 0.00800000 | 49873.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 55446.536 | 55446.536 | 1.646968 | 0.00122502 | 1158.383 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 2.1817 | 2.345791 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52606.32 | 55446.54 | 1.0000 | 1.98157712 | 1.646968 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 1.22489850 | 60.00 | 49.00 | 11.00 | 0.000 | 52606.32 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 38877.31 | 0.00 | 55699.72 | 55699.72 | 1.98157712 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.37 | 21.26 | 0.00800000 | 61168.6 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3606.316 | 3606.316 | 0.202823 | 0.00007968 | 66.763 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 0.1420 | 0.152573 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3424.37 | 3606.32 | 1.0000 | 0.24402993 | 0.202823 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.07966903 | 60.00 | 49.00 | 11.00 | 0.000 | 3424.37 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00681694 | 21.00 | 0.00681694 | 44.1171 | 1570.37 | 0.00 | 3623.98 | 3623.98 | 0.24402993 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 27.36 | 17.12 | 0.00800000 | 47910.4 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2759.040 | 2759.040 | 0.130388 | 0.00006096 | 52.211 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 0.1086 | 0.116727 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2619.24 | 2759.04 | 1.0000 | 0.15687810 | 0.130388 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.06095141 | 60.00 | 49.00 | 11.00 | 0.000 | 2619.24 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00693506 | 21.00 | 0.00693506 | 44.8736 | 1449.95 | 0.00 | 2772.19 | 2772.19 | 0.15687810 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 30.13 | 18.06 | 0.00800000 | 50730.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5491.400 | 5491.400 | 0.202699 | 0.00012133 | 108.545 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 0.2161 | 0.232326 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5211.61 | 5491.40 | 1.0000 | 0.24388111 | 0.202699 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.12131340 | 60.00 | 49.00 | 11.00 | 0.000 | 5211.61 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00722072 | 21.00 | 0.00722072 | 46.7012 | 3455.28 | 0.00 | 5516.92 | 5516.92 | 0.24388111 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 34.98 | 19.62 | 0.00800000 | 55681.2 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1546.480 | 1546.480 | 0.130430 | 0.00003417 | 27.444 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 0.0608 | 0.065427 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 1466.89 | 1546.48 | 1.0000 | 0.15692911 | 0.130430 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03416409 | 60.00 | 49.00 | 11.00 | 0.000 | 1466.89 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00640968 | 21.00 | 0.00640968 | 41.5074 | 238.13 | 0.00 | 1552.53 | 1552.53 | 0.15692911 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 22.50 | 15.39 | 0.00800000 | 42953.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 127212.473 | 127212.473 | 3.791709 | 0.00281060 | 2654.937 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 5.0056 | 5.382010 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 120696.45 | 127212.47 | 1.0000 | 4.56205918 | 3.791709 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 2.81031744 | 60.00 | 49.00 | 11.00 | 0.000 | 120696.45 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00768324 | 21.00 | 0.00768324 | 49.6563 | 89092.71 | 0.00 | 127793.28 | 127793.28 | 4.56205918 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61072.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 85672.183 | 85672.183 | 2.553892 | 0.00189282 | 1787.916 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 3.3711 | 3.624555 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 81283.93 | 85672.18 | 1.0000 | 3.07275862 | 2.553892 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 1.89262912 | 60.00 | 49.00 | 11.00 | 0.000 | 81283.93 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00770873 | 21.00 | 0.00770873 | 49.8189 | 59995.42 | 0.00 | 86063.33 | 86063.33 | 3.07275862 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61068.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 127440.311 | 127440.311 | 3.798518 | 0.00281564 | 2659.688 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 5.0146 | 5.391649 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 120912.62 | 127440.31 | 1.0000 | 4.57025074 | 3.798518 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 2.81535071 | 60.00 | 49.00 | 11.00 | 0.000 | 120912.62 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00768472 | 21.00 | 0.00768472 | 49.6657 | 89251.98 | 0.00 | 128022.15 | 128022.15 | 4.57025074 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61071.9 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 74961.783 | 74961.783 | 2.233695 | 0.00165619 | 1564.592 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 2.9496 | 3.171427 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 71122.11 | 74961.78 | 1.0000 | 2.68750742 | 2.233695 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 1.65602005 | 60.00 | 49.00 | 11.00 | 0.000 | 71122.11 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00759934 | 21.00 | 0.00759934 | 49.1210 | 52509.31 | 0.00 | 75304.03 | 75304.03 | 2.68750742 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.28 | 21.23 | 0.00800000 | 61079.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16976.788 | 16976.788 | 0.506376 | 0.00037508 | 354.230 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 0.6680 | 0.718241 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16107.22 | 16976.79 | 1.0000 | 0.60925485 | 0.506376 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.37504311 | 60.00 | 49.00 | 11.00 | 0.000 | 16107.22 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00784311 | 21.00 | 0.00784311 | 50.6755 | 11884.26 | 0.00 | 17054.29 | 17054.29 | 0.60925485 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61051.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11257.244 | 11257.244 | 0.335801 | 0.00024872 | 234.884 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 0.4430 | 0.476263 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10680.64 | 11257.24 | 1.0000 | 0.40402457 | 0.335801 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.24868968 | 60.00 | 49.00 | 11.00 | 0.000 | 10680.64 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00785262 | 21.00 | 0.00785262 | 50.7362 | 7880.09 | 0.00 | 11308.64 | 11308.64 | 0.40402457 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61049.8 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16972.310 | 16972.310 | 0.506242 | 0.00037498 | 354.137 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 0.6678 | 0.718052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16102.97 | 16972.31 | 1.0000 | 0.60909333 | 0.506242 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.37494420 | 60.00 | 49.00 | 11.00 | 0.000 | 16102.97 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00784290 | 21.00 | 0.00784290 | 50.6742 | 11881.13 | 0.00 | 17049.80 | 17049.80 | 0.60909333 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61051.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10415.217 | 10415.217 | 0.310626 | 0.00023011 | 217.327 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 0.4098 | 0.440639 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9881.74 | 10415.22 | 1.0000 | 0.37373467 | 0.310626 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.23008801 | 60.00 | 49.00 | 11.00 | 0.000 | 9881.74 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00780369 | 21.00 | 0.00780369 | 50.4244 | 7291.58 | 0.00 | 10462.77 | 10462.77 | 0.37373467 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61055.0 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 123671.015 | -999.000 | 5.268463 | 0.00353698 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7332 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.268463 | 6.33884037 | 4197.9300 | 999.8980 | 77.45859355 | 15.00 | 6.67 | 8.33 | 2708630.73 | 4.5658 | 4.565813 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 123671.01 | 86109.16 | 1.0000 | 6.33884037 | 5.268463 | 25.04 | 18.54 | 0.01070129 | 52422.9 | 11.42 | 11.42 | 0.00828381 | 32918.5 | 3.53661456 | 6.67 | 13.38 | 8.33 | 8933.492 | 114737.52 | 28.55 | 0.01651377 | 23.71 | 1.20008137 | 22.7786 | 24.00 | 0.00897825 | 24.00 | 0.00897937 | 48.2638 | 72176.01 | 0.00 | 136232.08 | 93004.72 | 6.33884037 | 25.04 | 18.55 | 0.01070129 | 52422.9 | 10.72 | 10.70 | 0.00799609 | 30931.3 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 248111.326 | 248111.326 | 5.268463 | 0.00548172 | 4653.165 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.268463 | 6.33884037 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 8.3691 | 10.496908 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 201797.72 | 228818.13 | 1.0000 | 6.33884037 | 5.268463 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 5.48115737 | 60.00 | 49.00 | 11.00 | 0.000 | 201797.72 | 4.60 | 0.00525715 | 4.60 | 1.20008137 | 22.7786 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 212985.31 | 212985.31 | 6.33884037 | 12.80 | 3.60 | 0.00119750 | 15885.3 | 46.16 | 17.79 | 0.00119750 | 49485.4 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 222096.201 | -999.000 | 8.498173 | 0.00635192 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9803 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.498173 | 10.22472053 | 4197.9300 | 999.8980 | 77.45859355 | 15.00 | 6.67 | 8.33 | 2708630.73 | 8.1996 | 8.199575 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 222096.20 | 156737.36 | 1.0000 | 10.22472053 | 8.498173 | 26.49 | 19.11 | 0.01083422 | 54247.6 | 11.43 | 12.09 | 0.00828381 | 34322.2 | 6.35127527 | 6.67 | 13.38 | 8.33 | 18364.099 | 203732.10 | 33.82 | 0.01651377 | 25.08 | 2.03040000 | 23.8922 | 24.00 | 0.00890398 | 24.00 | 0.00884933 | 47.5744 | 110080.30 | 0.00 | 242400.83 | 166959.12 | 10.22472053 | 26.49 | 19.12 | 0.01083422 | 54247.6 | 10.56 | 10.54 | 0.00790696 | 30540.3 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 24264.330 | 24264.330 | 2.549452 | 0.00053609 | 370.465 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.498173 | 10.22472053 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 0.8575 | 1.026557 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20676.77 | 24264.33 | 1.0000 | 3.06741616 | 2.549452 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.53603604 | 60.00 | 49.00 | 11.00 | 0.000 | 20676.77 | 4.60 | 0.00525715 | 4.60 | 2.03040000 | 79.6406 | 6.21 | 0.00202639 | 21.00 | 0.00767049 | 49.5725 | 6655.94 | 0.00 | 21870.49 | 21870.49 | 3.06741616 | 12.80 | 7.88 | 0.00459939 | 24474.2 | 19.84 | 11.04 | 0.00459939 | 31604.1 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2148163.881 | -999.000 | 78.218185 | 0.06143721 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5548 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.218185 | 94.10953116 | 4197.9300 | 999.8980 | 77.45859355 | 15.00 | 6.67 | 8.33 | 2708630.73 | 79.3081 | 79.308112 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2148163.88 | 1472978.36 | 1.0000 | 94.10953116 | 78.218185 | 26.80 | 19.44 | 0.01114329 | 55352.4 | 11.43 | 12.09 | 0.00828381 | 34322.2 | 61.43094783 | 6.67 | 13.38 | 8.33 | 169025.333 | 1979138.55 | 33.74 | 0.01651377 | 25.06 | 20.30400000 | 25.9582 | 24.00 | 0.00897739 | 24.00 | 0.00889160 | 47.7986 | 971557.19 | 0.00 | 2334982.47 | 1567256.89 | 94.10953116 | 26.80 | 19.45 | 0.01114329 | 55352.4 | 10.56 | 10.54 | 0.00790681 | 30541.0 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 169949.857 | 169949.857 | 23.465456 | 0.00375483 | 2611.357 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 78.218185 | 94.10953116 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 6.1560 | 7.190111 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 148436.21 | 169949.86 | 1.0000 | 28.23285935 | 23.465456 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 3.75445138 | 60.00 | 49.00 | 11.00 | 0.000 | 148436.21 | 4.60 | 0.00525715 | 4.60 | 20.30400000 | 86.5272 | 21.00 | 0.00795975 | 21.00 | 0.00782563 | 50.5638 | 327578.84 | 0.00 | 157030.47 | 157030.47 | 28.23285935 | 12.80 | 9.05 | 0.00562126 | 27054.2 | 18.28 | 11.44 | 0.00562126 | 32616.1 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 214699.631 | -999.000 | 8.325823 | 0.00614038 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8657 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.325823 | 10.01735512 | 4197.9300 | 999.8980 | 77.45859355 | 15.00 | 6.67 | 8.33 | 2708630.73 | 7.9265 | 7.926501 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 214699.63 | 152234.49 | 1.0000 | 10.01735512 | 8.325823 | 26.36 | 19.02 | 0.01077257 | 53958.9 | 11.42 | 12.09 | 0.00828381 | 34322.2 | 6.13975590 | 6.67 | 13.38 | 8.33 | 17991.661 | 196707.97 | 33.66 | 0.01651378 | 25.04 | 2.03040000 | 24.3868 | 24.00 | 0.00891426 | 24.00 | 0.00888797 | 47.7794 | 114185.96 | 0.00 | 234545.74 | 162220.70 | 10.01735512 | 26.36 | 19.03 | 0.01077257 | 53958.9 | 10.56 | 10.54 | 0.00790815 | 30545.0 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16439.809 | 16439.809 | 2.497747 | 0.00036322 | 253.102 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.325823 | 10.01735512 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 0.5999 | 0.695523 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14464.06 | 16439.81 | 1.0000 | 3.00520653 | 2.497747 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.36318044 | 60.00 | 49.00 | 11.00 | 0.000 | 14464.06 | 4.60 | 0.00525715 | 4.60 | 2.03040000 | 81.2893 | 19.33 | 0.00771701 | 21.00 | 0.00791850 | 51.1556 | 37469.59 | 0.00 | 15301.70 | 15301.70 | 3.00520653 | 12.80 | 9.15 | 0.00571741 | 27296.9 | 17.81 | 11.35 | 0.00571741 | 32388.6 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 429437.135 | 309029.248 | 21.191571 | 0.01051689 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8793 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 458999.20 | 450463.61 | 0.9356 | -999.0 | -999.0 | 28.51 | 18.02 | 0.00862817 | 50685.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 458999.20 | 33.90 | 0.01651378 | 25.10 | 0.33837161 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 368912.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9224.836 | 6644.931 | 0.456596 | 0.00022592 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1534 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 9865.27 | 9469.78 | 0.9351 | -999.0 | -999.0 | 28.09 | 18.00 | 0.00877557 | 50633.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9865.27 | 31.21 | 0.01651378 | 24.41 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 7926.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 87757.615 | 63140.370 | 4.334148 | 0.00214918 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1790 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 93815.48 | 89875.53 | 0.9354 | -999.0 | -999.0 | 28.10 | 18.01 | 0.00878939 | 50676.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93815.48 | 31.21 | 0.01651378 | 24.41 | 0.15631366 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 75482.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 8927.632 | 6424.976 | 0.441132 | 0.00021864 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1692 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9544.65 | 9150.95 | 0.9354 | -999.0 | -999.0 | 28.10 | 18.01 | 0.00878408 | 50666.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9544.65 | 31.41 | 0.01651378 | 24.46 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 7689.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 429437.135 | 429437.135 | 21.191571 | 0.01051689 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 429437.13 | 429437.13 | 1.0000 | 25.49699665 | 21.191571 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 429437.13 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5967 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9224.836 | 9224.836 | 0.456596 | 0.00022592 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9224.84 | 9224.84 | 1.0000 | 0.54936153 | 0.456596 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9224.84 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.4235 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87757.615 | 87757.615 | 4.334148 | 0.00214918 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 87757.62 | 87757.62 | 1.0000 | 5.21470306 | 4.334148 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87757.62 | 4.60 | 0.00525715 | 4.60 | 0.15631366 | 3.6066 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8927.632 | 8927.632 | 0.441132 | 0.00021864 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8927.63 | 8927.63 | 1.0000 | 0.53075562 | 0.441132 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8927.63 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.5435 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14481.982 | 14481.982 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.191571 | 25.49699665 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14481.98 | 14481.98 | 1.0000 | 25.49699665 | 21.191571 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14481.98 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5967 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.191571 | 25.49699665 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 920385.25 | 1.0000 | 25.49699665 | 21.191571 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5967 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1022953.204 | 1022953.204 | 21.191571 | 0.02260090 | 19051.646 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.191571 | 25.49699665 | 4197.9300 | 999.8980 | 52.21687512 | 71.00 | 82.00 | 11.00 | 2411230.65 | 34.1159 | 43.278338 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 822612.97 | 920385.25 | 1.0000 | 25.49699665 | 21.191571 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 22.59859553 | 60.00 | 49.00 | 11.00 | 0.000 | 822612.97 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5967 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49699665 | 16.60 | 4.14 | 0.00008394 | 16892.9 | 16.60 | 4.14 | 0.00008394 | 16892.9 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.456596 | 0.54936153 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 1.0000 | 0.54936153 | 0.456596 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.01 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.4235 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6690.076 | 6690.076 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.334148 | 5.21470306 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6690.08 | 6690.08 | 1.0000 | 5.21470306 | 4.334148 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6690.08 | 4.60 | 0.00525715 | 4.60 | 0.15631366 | 3.6066 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.441132 | 0.53075562 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 1.0000 | 0.53075562 | 0.441132 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.01 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.5435 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 5.27 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.50 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 78.22 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.33 | - | |||
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | DifferentialEnthalpy | 0.34 | 21.19 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4938.33 | 2108.33 | 2042.83 |
CORE_BOTTOM | 4861.83 | 140.50 | 0.00 |
CORE_MID | 3218.83 | 1056.33 | 0.00 |
CORE_TOP | 3414.83 | 1607.33 | 40.33 |
PERIMETER_BOT_ZN_3 | 4197.83 | 1104.33 | 41.00 |
PERIMETER_BOT_ZN_2 | 4257.33 | 1151.83 | 202.17 |
PERIMETER_BOT_ZN_1 | 4708.17 | 882.33 | 237.00 |
PERIMETER_BOT_ZN_4 | 5126.33 | 774.17 | 484.67 |
PERIMETER_MID_ZN_3 | 3581.50 | 2213.00 | 322.67 |
PERIMETER_MID_ZN_2 | 3340.00 | 1659.17 | 435.00 |
PERIMETER_MID_ZN_1 | 4421.67 | 1374.00 | 432.50 |
PERIMETER_MID_ZN_4 | 4250.00 | 1620.50 | 411.67 |
PERIMETER_TOP_ZN_3 | 3785.33 | 2467.00 | 692.83 |
PERIMETER_TOP_ZN_2 | 4049.00 | 2093.83 | 636.00 |
PERIMETER_TOP_ZN_1 | 4314.67 | 1682.83 | 595.67 |
PERIMETER_TOP_ZN_4 | 4207.83 | 1911.00 | 601.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5570.00 | 4165.50 | 2671.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 117.67 | 0.00 | 15.50 |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.83 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 36.17 | 0.00 | 36.17 |
PERIMETER_BOT_ZN_1 | 0.00 | 145.50 | 0.00 | 143.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 215.67 | 0.00 | 91.33 |
PERIMETER_MID_ZN_3 | 0.17 | 0.33 | 0.00 | 0.33 |
PERIMETER_MID_ZN_2 | 0.00 | 51.67 | 0.00 | 51.17 |
PERIMETER_MID_ZN_1 | 0.00 | 204.67 | 0.00 | 203.83 |
PERIMETER_MID_ZN_4 | 0.00 | 56.67 | 0.00 | 34.33 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.67 | 1.33 | 14.33 |
PERIMETER_TOP_ZN_2 | 3.67 | 69.67 | 0.17 | 62.17 |
PERIMETER_TOP_ZN_1 | 2.00 | 128.67 | 0.00 | 124.83 |
PERIMETER_TOP_ZN_4 | 1.83 | 72.50 | 0.00 | 43.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 2.17 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.67 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 258.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 7.00 | 866.00 | 1.33 | 400.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.973 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.591 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.515 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.492 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.618 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.747 | 0.036 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.868 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.182 | 0.036 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.579 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.707 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.846 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.819 | 0.082 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.571 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.741 | 0.101 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.809 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.786 | 0.101 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28757.45 | 292889.46 | 15-JAN-03:50 | 1765772.50 | 03-AUG-15:50 |
Electricity:Building | 17253.05 | 216749.59 | 14-MAY-17:20 | 1029479.61 | 12-DEC-08:10 |
Electricity:Zone:BASEMENT | 599.48 | 14055.89 | 01-JAN-00:10 | 29063.30 | 02-JAN-08:10 |
InteriorLights:Electricity | 2576.74 | 9493.43 | 23-APR-17:20 | 251694.63 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 175.08 | 598.35 | 01-JAN-00:10 | 15605.75 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 2576.74 | 9493.43 | 23-APR-17:20 | 251694.63 | 25-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 446.84 | 4990.59 | 01-JAN-00:10 | 31221.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 157.23 | 537.36 | 01-JAN-00:10 | 14015.06 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4468.42 | 49905.77 | 01-JAN-00:10 | 312216.26 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1572.35 | 5373.60 | 01-JAN-00:10 | 140150.63 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 446.84 | 4990.58 | 01-JAN-00:10 | 31221.63 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 157.23 | 537.36 | 01-JAN-00:10 | 14015.06 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 47.49 | 610.54 | 26-MAR-17:10 | 3720.23 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 11.12 | 46.52 | 01-JAN-08:50 | 1559.68 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.57 | 393.45 | 26-MAR-17:10 | 2372.09 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 7.13 | 29.98 | 01-JAN-07:50 | 979.75 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 47.37 | 610.54 | 12-MAR-17:10 | 3707.73 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 11.00 | 46.52 | 01-JAN-07:50 | 1547.14 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.56 | 393.45 | 26-FEB-18:10 | 2406.99 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 7.13 | 29.98 | 01-JAN-08:50 | 1014.66 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 474.67 | 6105.35 | 12-MAR-17:10 | 37178.25 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 111.02 | 465.16 | 01-JAN-08:50 | 15572.74 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 305.59 | 3934.52 | 26-MAR-17:10 | 23683.11 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 71.24 | 299.76 | 01-JAN-07:50 | 9759.69 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 473.56 | 6105.45 | 12-MAR-17:10 | 37052.53 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 109.90 | 465.17 | 01-JAN-07:50 | 15446.68 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 305.54 | 3934.50 | 26-FEB-18:10 | 24038.40 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 71.19 | 299.76 | 01-JAN-08:50 | 10115.07 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 47.47 | 610.54 | 12-MAR-17:10 | 3717.42 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 11.10 | 46.52 | 01-JAN-08:50 | 1556.87 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.56 | 393.45 | 26-MAR-17:10 | 2368.00 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 7.12 | 29.98 | 01-JAN-07:50 | 975.66 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 47.36 | 610.54 | 12-MAR-17:10 | 3704.83 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.99 | 46.52 | 01-JAN-07:50 | 1544.24 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.55 | 393.45 | 26-FEB-18:10 | 2403.59 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 7.12 | 29.98 | 01-JAN-08:50 | 1011.26 | 25-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7545.53 | 95152.58 | 01-JAN-06:10 | 384032.68 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.68 | 244.45 | 01-JAN-06:10 | 4400.15 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 156.22 | 1959.90 | 01-JAN-06:10 | 7997.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.34 | 11.29 | 01-JAN-06:10 | 203.27 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1562.22 | 19598.98 | 01-JAN-06:10 | 79976.91 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 23.41 | 112.93 | 01-JAN-06:10 | 2032.69 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 156.22 | 1959.90 | 01-JAN-06:10 | 7997.69 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.34 | 11.29 | 01-JAN-06:10 | 203.27 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.31 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.88 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.07 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.36 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.65 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.36 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.43 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 4652.11 | 45595.25 | 15-JAN-05:50 | 366368.47 | 18-APR-14:20 |
ExteriorEquipment:Electricity | 1955.63 | 13239.62 | 01-JAN-00:10 | 126013.33 | 25-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.73 | 979.82 | 01-JAN-00:10 | 3415.35 | 25-OCT-07:20 |
ElectricityPurchased:Facility | 28757.45 | 292889.46 | 15-JAN-03:50 | 1765772.50 | 03-AUG-15:50 |
ElectricityPurchased:Plant | 28757.45 | 292889.46 | 15-JAN-03:50 | 1765772.50 | 03-AUG-15:50 |
Cogeneration:ElectricityPurchased | 28757.45 | 292889.46 | 15-JAN-03:50 | 1765772.50 | 03-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28757.45 | 292889.46 | 15-JAN-03:50 | 1765772.50 | 03-AUG-15:50 |
ElectricityNet:Plant | 28757.45 | 292889.46 | 15-JAN-03:50 | 1765772.50 | 03-AUG-15:50 |
Cogeneration:ElectricityNet | 28757.45 | 292889.46 | 15-JAN-03:50 | 1765772.50 | 03-AUG-15:50 |
Fans:Electricity | 2073.42 | 40995.32 | 01-JAN-00:10 | 139647.03 | 30-AUG-16:00 |
General:Fans:Electricity | 2073.42 | 40995.32 | 01-JAN-00:10 | 139647.03 | 30-AUG-16:00 |
ExteriorLights:Electricity | 342.93 | 0.00 | 01-JAN-07:30 | 39974.20 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 342.93 | 0.00 | 01-JAN-07:30 | 39974.20 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 50.26 | 0.00 | 01-JAN-00:10 | 4520.44 | 22-APR-16:10 |
Cooling:Electricity | 4595.48 | 3391.44 | 11-JAN-08:00 | 432723.34 | 07-AUG-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 276.91 | 0.00 | 01-JAN-00:10 | 100000.00 | 12-FEB-12:20 |
Electricity:Plant | 4608.45 | 3710.91 | 10-JAN-04:50 | 422335.39 | 05-JUL-12:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 2398.70 | 0.00 | 01-JAN-00:10 | 298641.30 | 05-JUL-12:10 |
HeatRejection:Electricity | 1661.34 | 394.15 | 10-JAN-05:00 | 83768.54 | 29-MAY-17:20 |
General:HeatRejection:Electricity | 535.72 | 0.00 | 01-JAN-00:10 | 39992.30 | 29-MAY-17:20 |
Pumps:Electricity | 548.41 | 3310.76 | 03-JAN-04:20 | 50957.67 | 26-MAY-15:00 |
General:Pumps:Electricity | 548.41 | 3310.76 | 03-JAN-04:20 | 50957.67 | 26-MAY-15:00 |
WIRED_LTG_ELECTRICITY | 72.41 | 0.00 | 01-JAN-00:10 | 7072.62 | 25-OCT-07:20 |
WIRED_INT_EQUIP | 5334.88 | 88964.76 | 01-APR-00:10 | 305206.10 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 547.64 | 7280.88 | 01-JAN-00:20 | 746592.51 | 06-JAN-09:40 |
Gas:Plant | 547.64 | 7280.88 | 01-JAN-00:20 | 746592.51 | 06-JAN-09:40 |
WaterSystems:Gas | 467.55 | 7280.88 | 01-JAN-00:20 | 68072.44 | 23-JAN-13:00 |
Water Heater:WaterSystems:Gas | 467.55 | 7280.88 | 01-JAN-00:20 | 68072.44 | 23-JAN-13:00 |
Heating:Gas | 80.08 | 0.00 | 01-JAN-00:10 | 709867.73 | 06-JAN-09:40 |
Boiler:Heating:Gas | 80.08 | 0.00 | 01-JAN-00:10 | 709867.73 | 06-JAN-09:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 24442.69 | 12664.13 | 11-JAN-08:00 | 2303653.08 | 07-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 24442.69 | 12664.13 | 11-JAN-08:00 | 2303653.08 | 07-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 24442.69 | 12664.13 | 11-JAN-08:00 | 2303653.08 | 07-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 14368.20 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
Water:Plant | 14265.19 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 14368.20 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
MainsWater:Plant | 14265.19 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 103.01 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-05:30 |
Humidifier:Water | 103.01 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-05:30 |
MainsWater:HVAC | 103.01 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-05:30 |
Humidifier:MainsWater | 103.01 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-05:30 |
HeatRejection:Water | 11985.02 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
HeatRejection:MainsWater | 11985.02 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 383.42 | 0.00 | 01-JAN-00:10 | 351671.59 | 06-FEB-06:10 |
PlantLoopHeatingDemand:Plant | 324.14 | 0.00 | 01-JAN-00:10 | 40628.81 | 25-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 324.14 | 0.00 | 01-JAN-00:10 | 40628.81 | 25-JAN-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 95351.22 | 105688.82 | 10-JAN-04:50 | 9407417.74 | 05-JUL-12:10 |
EnergyTransfer:Building | 20570.66 | 92949.38 | 22-JAN-07:50 | 1529489.96 | 30-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 738.37 | 0.00 | 01-JAN-00:10 | 78109.33 | 13-NOV-06:10 |
Heating:EnergyTransfer | 36.78 | 0.00 | 01-JAN-00:10 | 227422.27 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 13.05 | 0.00 | 01-JAN-00:10 | 60016.94 | 03-JUN-03:50 |
Cooling:EnergyTransfer | 20533.88 | 92448.20 | 22-JAN-07:50 | 1529489.96 | 30-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 725.33 | 0.00 | 01-JAN-00:10 | 78109.33 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 708.46 | 0.00 | 01-JAN-00:10 | 51530.03 | 26-DEC-10:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 708.46 | 0.00 | 01-JAN-00:10 | 51530.03 | 26-DEC-10:10 |
EnergyTransfer:Zone:CORE_MID | 5217.42 | 0.00 | 01-JAN-00:10 | 419646.95 | 25-FEB-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5217.42 | 0.00 | 01-JAN-00:10 | 419646.95 | 25-FEB-06:10 |
EnergyTransfer:Zone:CORE_TOP | 526.20 | 0.00 | 01-JAN-00:10 | 48937.68 | 07-JUL-15:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.31 | 0.00 | 01-JAN-00:10 | 37121.68 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 525.89 | 0.00 | 01-JAN-00:10 | 48937.68 | 07-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 100.24 | 0.00 | 01-JAN-00:10 | 10853.62 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 100.24 | 0.00 | 01-JAN-00:10 | 10853.62 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 76.71 | 0.00 | 01-JAN-00:10 | 11469.28 | 03-MAY-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 76.71 | 0.00 | 01-JAN-00:10 | 11469.28 | 03-MAY-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 128.05 | 0.00 | 01-JAN-00:10 | 14940.04 | 06-NOV-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 128.05 | 0.00 | 01-JAN-00:10 | 14940.04 | 06-NOV-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 116.56 | 0.00 | 01-JAN-00:10 | 16079.60 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 116.56 | 0.00 | 01-JAN-00:10 | 16079.60 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 765.34 | 0.00 | 01-JAN-00:10 | 96858.42 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.22 | 0.00 | 01-JAN-00:10 | 55341.94 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 762.12 | 0.00 | 01-JAN-00:10 | 96858.42 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 649.49 | 0.00 | 01-JAN-00:10 | 118901.06 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.47 | 0.00 | 01-JAN-00:10 | 31566.30 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 648.02 | 0.00 | 01-JAN-00:10 | 118901.06 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1076.13 | 0.00 | 01-JAN-00:10 | 151558.59 | 01-JAN-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.72 | 0.00 | 01-JAN-00:10 | 32829.64 | 20-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1075.41 | 0.00 | 01-JAN-00:10 | 151558.59 | 01-JAN-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 711.96 | 0.00 | 01-JAN-00:10 | 133555.73 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.65 | 0.00 | 01-JAN-00:10 | 23021.10 | 05-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 711.31 | 0.00 | 01-JAN-00:10 | 133555.73 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 80.12 | 0.00 | 01-JAN-00:10 | 11644.08 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.32 | 0.00 | 01-JAN-00:10 | 11644.08 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 77.80 | 0.00 | 01-JAN-00:10 | 10615.66 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 69.92 | 0.00 | 01-JAN-00:10 | 11953.84 | 03-MAY-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.07 | 0.00 | 01-JAN-00:10 | 9187.51 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 68.85 | 0.00 | 01-JAN-00:10 | 11953.84 | 03-MAY-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 108.77 | 0.00 | 01-JAN-00:10 | 15617.14 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.07 | 0.00 | 01-JAN-00:10 | 11332.63 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 107.70 | 0.00 | 01-JAN-00:10 | 15617.14 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 73.07 | 0.00 | 01-JAN-00:10 | 14058.75 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.69 | 0.00 | 01-JAN-00:10 | 6783.45 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 72.38 | 0.00 | 01-JAN-00:10 | 14058.75 | 30-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 77.27 | 0.00 | 01-JAN-00:10 | 8189.63 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.70 | 0.00 | 01-JAN-00:10 | 3145.39 | 31-DEC-10:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 76.56 | 0.00 | 01-JAN-00:10 | 8189.63 | 02-JAN-06:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 539.99 | 0.00 | 01-JAN-00:10 | 64612.35 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 6.39 | 0.00 | 01-JAN-00:10 | 24886.42 | 16-JAN-10:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 533.60 | 0.00 | 01-JAN-00:10 | 64612.35 | 10-OCT-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 94.14 | 0.00 | 01-JAN-00:10 | 17860.15 | 07-JUL-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.97 | 0.00 | 01-JAN-00:10 | 13681.56 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 89.17 | 0.00 | 01-JAN-00:10 | 17860.15 | 07-JUL-14:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.42 | 1001.61 | 05-JAN-08:00 | 7991.50 | 16-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.42 | 1001.61 | 05-JAN-08:00 | 7991.50 | 16-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1286.23 | 2573.63 | 10-JAN-06:30 | 74957.66 | 16-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1286.23 | 2573.63 | 10-JAN-06:30 | 74957.66 | 16-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.55 | 1.62 | 24-JAN-01:50 | 7663.99 | 23-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.16 | 0.00 | 01-JAN-00:10 | 513.38 | 23-JAN-05:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.39 | 0.00 | 04-JAN-04:20 | 7663.99 | 23-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7160.26 | 88007.62 | 22-JAN-08:50 | 368059.97 | 28-AUG-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7160.26 | 88007.62 | 22-JAN-08:50 | 368059.97 | 28-AUG-21:10 |
EnergyTransfer:Plant | 49707.67 | 0.00 | 01-JAN-00:10 | 5792511.57 | 26-MAY-15:10 |
WaterSystems:EnergyTransfer | 324.14 | 0.00 | 01-JAN-00:10 | 40628.81 | 25-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 324.14 | 0.00 | 01-JAN-00:10 | 40628.81 | 25-JAN-12:30 |
EnergyTransfer:HVAC | 25072.89 | 11197.03 | 23-JAN-05:50 | 2597414.89 | 07-AUG-13:00 |
HeatingCoils:EnergyTransfer | 59.28 | 0.00 | 01-JAN-00:10 | 346588.11 | 06-FEB-06:10 |
PlantLoopHeatingDemand:HVAC | 59.28 | 0.00 | 01-JAN-00:10 | 346588.11 | 06-FEB-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 59.28 | 0.00 | 01-JAN-00:10 | 346588.11 | 06-FEB-06:10 |
CoolingCoils:EnergyTransfer | 22384.18 | 10635.29 | 11-JAN-08:00 | 2169129.84 | 07-AUG-14:40 |
HeatRecoveryForHeating:EnergyTransfer | 16.34 | 0.00 | 01-JAN-00:10 | 176864.87 | 20-DEC-08:00 |
HeatRecoveryForCooling:EnergyTransfer | 2613.10 | 0.00 | 01-JAN-00:10 | 680693.77 | 22-JUL-16:00 |
LoopToLoop:EnergyTransfer | 15796.68 | 0.00 | 01-JAN-00:10 | 1730812.75 | 26-MAY-15:10 |
Boilers:EnergyTransfer | 58.35 | 0.00 | 01-JAN-00:10 | 577969.23 | 06-JAN-09:40 |
Chillers:EnergyTransfer | 15564.89 | 0.00 | 01-JAN-00:10 | 1885703.17 | 05-JUL-12:10 |
HeatRejection:EnergyTransfer | 17963.60 | 0.00 | 01-JAN-00:10 | 2184344.46 | 05-JUL-12:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 13.043 | -725.336 | 0.000 | 0.000 | 92.672 | 175.081 | 424.397 | 0.000 | 0.000 | 0.000 | 20.143 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -708.461 | 0.000 | 0.000 | 83.470 | 157.235 | 289.609 | 0.000 | 0.000 | 0.000 | 178.148 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5217.411 | 0.000 | 0.000 | 838.879 | 1572.350 | 2896.074 | 0.000 | 0.000 | 0.000 | 0.039 | 0.000 | 0.000 | 0.000 | 0.000 | -89.892 |
CORE_TOP | 0.000 | 0.000 | 0.313 | -525.889 | 0.000 | 0.000 | 85.005 | 157.235 | 289.607 | 0.000 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -6.271 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -100.242 | 0.000 | 0.000 | 10.552 | 11.123 | 36.365 | 37.343 | 0.000 | 0.423 | 37.348 | 0.000 | -31.043 | 0.000 | -1.868 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -76.708 | 0.000 | 0.000 | 6.779 | 7.133 | 23.435 | 55.365 | 0.000 | 0.271 | 3.696 | 0.000 | -18.737 | 0.000 | -1.233 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -128.049 | 0.000 | 0.000 | 10.481 | 11.000 | 36.365 | 92.969 | 0.000 | 0.399 | 7.686 | 0.000 | -28.892 | 0.000 | -1.960 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -116.559 | 0.000 | 0.000 | 6.741 | 7.130 | 23.435 | 52.626 | 0.000 | 0.224 | 51.919 | 0.000 | -24.009 | 0.000 | -1.507 | -0.001 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.222 | -762.095 | 0.000 | 0.000 | 107.889 | 111.019 | 363.647 | 385.470 | 0.000 | 9.012 | 93.468 | 0.000 | -274.851 | 0.000 | -36.782 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.468 | -648.006 | 0.000 | 0.000 | 50.095 | 71.239 | 234.348 | 549.834 | 0.000 | 5.233 | 0.008 | 0.000 | -179.026 | 0.000 | -26.736 | -58.448 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.719 | -1075.382 | 0.000 | 0.000 | 105.176 | 109.904 | 363.653 | 928.278 | 0.000 | 8.269 | 0.038 | 0.000 | -279.772 | 0.000 | -42.988 | -117.858 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.651 | -711.295 | 0.000 | 0.000 | 68.618 | 71.193 | 234.347 | 540.293 | 0.000 | 5.185 | 19.062 | 0.000 | -199.700 | 0.000 | -28.354 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.317 | -77.802 | 0.000 | 0.000 | 10.897 | 11.101 | 36.365 | 38.305 | 0.000 | 1.036 | 8.012 | 0.000 | -25.978 | 0.000 | -4.254 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.069 | -68.845 | 0.000 | 0.000 | 6.890 | 7.123 | 23.435 | 55.143 | 0.000 | 0.628 | 0.002 | 0.000 | -16.965 | 0.000 | -3.082 | -5.396 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.072 | -107.696 | 0.000 | 0.000 | 10.617 | 10.990 | 36.365 | 92.678 | 0.000 | 0.960 | 0.000 | 0.000 | -26.730 | 0.000 | -5.026 | -13.229 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.691 | -72.377 | 0.000 | 0.000 | 6.920 | 7.119 | 23.435 | 53.814 | 0.000 | 0.616 | 2.224 | 0.000 | -19.105 | 0.000 | -3.336 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -140.418 | 0.000 | 0.000 | 0.000 | 2.341 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -15.803 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1286.226 | 0.000 | 0.000 | 0.000 | 23.410 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -275.990 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.156 | -125.390 | 0.000 | 0.000 | 0.000 | 2.341 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -30.988 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7160.268 | 0.000 | 0.000 | 0.000 | 50.676 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -385.265 |
GROUNDFLOOR_PLENUM | 0.702 | -76.565 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.696 | 79.190 | 0.000 | 0.000 | 0.000 | -4.023 | 0.000 |
MIDFLOOR_PLENUM | 6.386 | -533.593 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.784 | 581.886 | 0.000 | 0.000 | 0.000 | -67.463 | 0.000 |
TOPFLOOR_PLENUM | 4.969 | -89.165 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.090 | 90.058 | 0.000 | 0.000 | 0.000 | -6.952 | 0.000 |
Total Facility | 12.057 | -699.323 | 24.721 | -19834.456 | 0.000 | 0.000 | 1501.681 | 2576.743 | 14676.305 | 2882.117 | 0.000 | 46.825 | 1172.934 | 0.000 | -1124.807 | 0.000 | -235.562 | -999.147 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-MAR-03:33 | 0.00 | 0.00 | 0.00 | -115450.38 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 101394.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 26-DEC-04:02 | 0.00 | 0.00 | 0.00 | -90992.03 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 84517.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 12-MAY-04:12 | 0.00 | 0.00 | 0.00 | -822328.71 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 757578.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-JUN-03:02 | 0.00 | 0.00 | 0.00 | -83593.64 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 77118.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 23-JUL-15:22 | 0.00 | 0.00 | 0.00 | -14010.75 | 0.00 | 0.00 | 43.24 | 46.52 | 720.18 | 5224.87 | 0.00 | 149.82 | 7826.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-08:31 | 0.00 | 0.00 | 0.00 | -19085.08 | 0.00 | 0.00 | 21.03 | 29.98 | 464.11 | 14667.32 | 0.00 | 0.00 | 3912.71 | 0.00 | -0.00 | 0.00 | -10.07 | 0.00 |
PERIMETER_BOT_ZN_1 | 17-DEC-12:52 | 0.00 | 0.00 | 0.00 | -18481.39 | 0.00 | 0.00 | 34.42 | 46.52 | 720.19 | 20673.60 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -377.21 | -2616.13 |
PERIMETER_BOT_ZN_4 | 11-NOV-15:12 | 0.00 | 0.00 | 0.00 | -22966.16 | 0.00 | 0.00 | 21.86 | 29.98 | 464.11 | 10197.13 | 0.00 | 0.00 | 12282.71 | 0.00 | -0.00 | 0.00 | -29.63 | 0.00 |
PERIMETER_MID_ZN_3 | 23-JUL-15:12 | 0.00 | 0.00 | 0.00 | -128046.40 | 0.00 | 0.00 | 429.18 | 465.16 | 7201.84 | 54506.71 | 0.00 | 3037.93 | 62405.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 24-SEP-09:42 | 0.00 | 0.00 | 0.00 | -188769.26 | 0.00 | 0.00 | 224.90 | 299.76 | 4641.14 | 111072.10 | 0.00 | 290.05 | 72241.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 17-DEC-13:02 | 0.00 | 0.00 | 0.00 | -172907.08 | 0.00 | 0.00 | 337.98 | 465.17 | 7201.95 | 202255.34 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9087.06 | -28266.30 |
PERIMETER_MID_ZN_4 | 08-OCT-15:21 | 0.00 | 0.00 | 0.00 | -198179.68 | 0.00 | 0.00 | 219.15 | 299.76 | 4641.11 | 112035.70 | 0.00 | 2062.94 | 78921.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 10-SEP-14:51 | 0.00 | 0.00 | 0.00 | -15367.21 | 0.00 | 0.00 | 40.56 | 46.52 | 720.18 | 4670.08 | 0.00 | 296.30 | 9593.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 10-SEP-09:31 | 0.00 | 0.00 | 0.00 | -19578.24 | 0.00 | 0.00 | 20.70 | 29.98 | 464.11 | 12519.00 | 0.00 | 231.38 | 6313.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-DEC-12:51 | 0.00 | 0.00 | 0.00 | -19913.10 | 0.00 | 0.00 | 31.60 | 46.52 | 720.19 | 22164.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -141.27 | -2908.77 |
PERIMETER_TOP_ZN_4 | 29-MAY-16:01 | 0.00 | 0.00 | 0.00 | -22478.13 | 0.00 | 0.00 | 18.63 | 29.98 | 464.11 | 14152.32 | 0.00 | 86.66 | 7726.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-18:12 | 0.00 | 0.00 | 0.00 | -7991.50 | 0.00 | 0.00 | 0.00 | 12.47 | 7794.42 | 0.00 | 0.00 | 0.00 | 184.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-18:15 | 0.00 | 0.00 | 0.00 | -74957.66 | 0.00 | 0.00 | 0.00 | 124.70 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3111.26 |
DATACENTER_TOP_ZN_6 | 23-APR-18:06 | 0.00 | 0.00 | 0.00 | -7663.99 | 0.00 | 0.00 | 0.00 | 12.47 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -142.90 |
DATACENTER_BASEMENT_ZN_6 | 06-AUG-15:42 | 0.00 | 0.00 | 0.00 | -370618.64 | 0.00 | 0.00 | 0.00 | 244.45 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9258.33 |
GROUNDFLOOR_PLENUM | 02-JAN-06:03 | 0.00 | -11479.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11526.02 | 0.00 | -0.00 | 0.00 | -46.23 | 0.00 |
MIDFLOOR_PLENUM | 05-OCT-05:01 | 0.00 | -94557.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94780.53 | 0.00 | -0.00 | 0.00 | -223.15 | 0.00 |
TOPFLOOR_PLENUM | 07-JUL-14:50 | 0.00 | -17859.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.62 | 17733.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 01-AUG-05:02 | 0.00 | -43153.94 | 0.00 | -1856170.18 | 0.00 | 0.00 | 15675.53 | 10469.47 | 616289.16 | 0.00 | 0.00 | 0.00 | 1286652.77 | 0.00 | -29762.79 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-JUL-15:38 | 0.00 | 0.00 | 127139.93 | 0.00 | 0.00 | 0.00 | 399.63 | 866.99 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -141864.09 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-05:11 | 0.00 | 0.00 | 51949.88 | -0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -58424.86 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-FEB-05:11 | 0.00 | 0.00 | 97045.68 | -0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41835.27 | 0.00 | -4539.96 | -58800.77 |
PERIMETER_MID_ZN_2 | 06-FEB-05:11 | 0.00 | 0.00 | 81909.01 | -0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28552.42 | 0.00 | -3121.27 | -55474.80 |
PERIMETER_MID_ZN_1 | 20-DEC-06:02 | 0.00 | 0.00 | 100111.33 | -0.00 | 0.00 | 0.00 | 1466.75 | 674.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46364.86 | 0.00 | -3307.11 | -62183.44 |
PERIMETER_MID_ZN_4 | 20-DEC-06:02 | 0.00 | 0.00 | 68491.35 | -0.00 | 0.00 | 0.00 | 942.62 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30934.49 | 0.00 | -2217.14 | -42905.30 |
PERIMETER_TOP_ZN_3 | 05-FEB-08:63 | 0.00 | 0.00 | 12955.79 | -0.00 | 0.00 | 0.00 | 88.48 | 64.47 | 720.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4176.50 | 0.00 | -2175.37 | -7477.05 |
PERIMETER_TOP_ZN_2 | 06-FEB-05:11 | 0.00 | 0.00 | 12061.49 | -0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2276.27 | 0.00 | -313.73 | -9995.43 |
PERIMETER_TOP_ZN_1 | 06-FEB-04:01 | 0.00 | 0.00 | 13845.69 | -0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3564.10 | 0.00 | -541.05 | -10553.58 |
PERIMETER_TOP_ZN_4 | 06-FEB-04:01 | 0.00 | 0.00 | 11248.42 | -0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2480.75 | 0.00 | -372.61 | -8919.00 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 25-JAN-05:12 | 0.00 | 0.00 | 524.39 | 0.00 | 0.00 | 0.00 | 0.00 | 24.94 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2497.93 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 22-DEC-05:11 | 9951.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -542.43 | -9408.81 |
MIDFLOOR_PLENUM | 22-MAY-03:02 | 57746.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.77 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -58042.23 |
TOPFLOOR_PLENUM | 06-FEB-06:15 | 15981.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -188.48 | -15792.52 |
Total Facility | 21-DEC-06:01 | -859085.88 | 816351.59 | 419977.46 | -816351.59 | 0.00 | 0.00 | 18700.38 | 10469.47 | 616289.16 | 0.00 | 0.00 | 0.00 | 17538.92 | 0.00 | -210210.83 | 0.00 | -13678.68 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.2685 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.2685 | 0.2278 | 1.0000 | 1.2001 | 0.2278 | ||
VAV_BOT WITH REHEAT | 9.3941 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.4982 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 87.3418 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 78.2182 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 8.9786 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.3258 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.1916 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.1916 | 0.0160 | 1.0000 | 0.3384 | 0.0160 | ||
AIRLOOP DATACENTER BOT | 0.4566 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4566 | 0.0342 | 1.0000 | 0.0156 | 0.0342 | ||
AIRLOOP DATACENTER MID | 4.3341 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.3341 | 0.0361 | 1.0000 | 0.1563 | 0.0361 | ||
AIRLOOP DATACENTER TOP | 0.4411 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4411 | 0.0354 | 1.0000 | 0.0156 | 0.0354 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.2685 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.2685 | 1.0000 | 1.0000 | 1.2001 | 0.2278 | ||
VAV_BOT WITH REHEAT | 4.6970 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.2856 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 43.6709 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 22.8656 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.4893 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.2827 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.1916 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.1916 | 1.0000 | 1.0000 | 0.3384 | 0.0160 | ||
AIRLOOP DATACENTER BOT | 0.4566 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4566 | 1.0000 | 1.0000 | 0.0156 | 0.0342 | ||
AIRLOOP DATACENTER MID | 4.3341 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.3341 | 1.0000 | 1.0000 | 0.1563 | 0.0361 | ||
AIRLOOP DATACENTER TOP | 0.4411 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4411 | 1.0000 | 1.0000 | 0.0156 | 0.0354 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.2685 | 5.2685 | 5.2685 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4155 | 5.4155 | 1.6192 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 50.5835 | 50.5835 | 16.1867 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0152 | 5.0152 | 1.6149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8278 | 0.8278 | 0.2028 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9730 | 0.9730 | 0.1304 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9472 | 0.9472 | 0.2027 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2305 | 1.2305 | 0.1304 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5075 | 7.5075 | 2.0270 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0081 | 10.0081 | 1.3111 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.7423 | 8.7423 | 2.0282 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.5004 | 10.5004 | 1.3126 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8602 | 0.8602 | 0.2030 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0088 | 1.0088 | 0.1311 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9742 | 0.9742 | 0.2026 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1201 | 1.1201 | 0.1311 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4566 | 0.4566 | 0.4566 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.3341 | 4.3341 | 4.3341 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4411 | 0.4411 | 0.4411 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.1916 | 21.1916 | 21.1916 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.2685 | 5.2685 | 5.2685 | 5.2685 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 9.3941 | 8.4982 | 9.3941 | 2.2856 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 87.3418 | 78.2182 | 87.3418 | 22.8656 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 8.9786 | 8.3258 | 8.9786 | 2.2827 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.1916 | 21.1916 | 21.1916 | 21.1916 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4566 | 0.4566 | 0.4566 | 0.4566 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3341 | 4.3341 | 4.3341 | 4.3341 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4411 | 0.4411 | 0.4411 | 0.4411 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.2685 | 5.2685 | 5.2685 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7078 | 2.7078 | 1.6192 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 25.2917 | 25.2917 | 16.1867 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5076 | 2.5076 | 1.6149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4139 | 0.4139 | 0.2028 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4865 | 0.4865 | 0.1304 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4736 | 0.4736 | 0.2027 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6152 | 0.6152 | 0.1304 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7538 | 3.7538 | 2.0270 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0041 | 5.0041 | 1.3111 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.3712 | 4.3712 | 2.0282 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2502 | 5.2502 | 1.3126 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4301 | 0.4301 | 0.2030 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5044 | 0.5044 | 0.1311 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4871 | 0.4871 | 0.2026 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5601 | 0.5601 | 0.1311 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4566 | 0.4566 | 0.4566 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.3341 | 4.3341 | 4.3341 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4411 | 0.4411 | 0.4411 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.1916 | 21.1916 | 21.1916 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.2685 | 5.2685 | 5.2685 | 5.2685 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 4.6970 | 2.2856 | 2.2856 | 2.2856 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 43.6709 | 22.8656 | 22.8656 | 22.8656 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.4893 | 2.2827 | 2.2827 | 2.2827 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.1916 | 21.1916 | 21.1916 | 21.1916 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4566 | 0.4566 | 0.4566 | 0.4566 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3341 | 4.3341 | 4.3341 | 4.3341 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4411 | 0.4411 | 0.4411 | 0.4411 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:56:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 1.33 |
Number of hours cooling loads not met | 400.00 |
Number of hours not met | 401.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 80.08 | 709867.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2398.70 | 298641.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 2196.78 | 134082.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2576.74 | 251694.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 342.93 | 39974.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.88 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.73 | 3415.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2073.42 | 139647.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 548.41 | 50957.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 535.72 | 39992.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 1125.61 | 43776.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 276.91 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 50.26 | 4520.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 467.55 | 68072.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.31 | 28757.45 |
Natural Gas | 0.00 | 547.64 |
Additional | 0.00 | 0.00 |
Total | 14676.31 | 29305.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 55.63 |
Space Heating | 0.00 |
Space Cooling | 99.21 |
Fans (All) | 44.76 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.84 |
Miscellaneous (All) | 620.84 |
Subtotal | 620.84 |
Natural Gas [MJ/m2] | |
Space Heating | 1.73 |
Service Water Heating | 10.09 |
Miscellaneous (All) | 11.82 |
Subtotal | 11.82 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.79 |
Space Heating | 0.27 |
Space Cooling | 15.68 |
Fans (All) | 7.08 |
Service Water Heating | 1.60 |
Receptacle Equipment | 50.08 |
Miscellaneous | 16.50 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2676. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1025. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUALSPSCHED | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241482E+11 |
February | 0.000 | 0.125984E+11 |
March | 0.000 | 0.111939E+11 |
April | 0.000 | 0.109675E+10 |
May | 0.000 | 0.214362E+10 |
June | 0.000 | 0.187640E+10 |
July | 0.000 | 0.204830E+10 |
August | 0.000 | 0.114979E+10 |
September | 0.000 | 0.196278E+10 |
October | 0.000 | 0.243208E+10 |
November | 0.000 | 0.281262E+10 |
December | 0.000 | 0.166202E+11 |
Annual Sum or Average | 0.800830E+11 | |
Minimum of Months | 0.000 | 0.109675E+10 |
Maximum of Months | 0.000 | 0.241482E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241482E+11 |
February | 0.000 | 0.125984E+11 |
March | 0.000 | 0.111939E+11 |
April | 0.000 | 0.109675E+10 |
May | 0.000 | 0.214362E+10 |
June | 0.000 | 0.187640E+10 |
July | 0.000 | 0.204830E+10 |
August | 0.000 | 0.114979E+10 |
September | 0.000 | 0.196278E+10 |
October | 0.000 | 0.243208E+10 |
November | 0.000 | 0.281262E+10 |
December | 0.000 | 0.166202E+11 |
Annual Sum or Average | 0.800830E+11 | |
Minimum of Months | 0.000 | 0.109675E+10 |
Maximum of Months | 0.000 | 0.241482E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241482E+11 |
February | 0.000 | 0.125984E+11 |
March | 0.000 | 0.111939E+11 |
April | 0.000 | 0.109675E+10 |
May | 0.000 | 0.214362E+10 |
June | 0.000 | 0.187640E+10 |
July | 0.000 | 0.204830E+10 |
August | 0.000 | 0.114979E+10 |
September | 0.000 | 0.196278E+10 |
October | 0.000 | 0.243208E+10 |
November | 0.000 | 0.281262E+10 |
December | 0.000 | 0.166202E+11 |
Annual Sum or Average | 0.800830E+11 | |
Minimum of Months | 0.000 | 0.109675E+10 |
Maximum of Months | 0.000 | 0.241482E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241482E+11 |
February | 0.000 | 0.125984E+11 |
March | 0.000 | 0.111939E+11 |
April | 0.000 | 0.109675E+10 |
May | 0.000 | 0.214362E+10 |
June | 0.000 | 0.187640E+10 |
July | 0.000 | 0.204830E+10 |
August | 0.000 | 0.114979E+10 |
September | 0.000 | 0.196278E+10 |
October | 0.000 | 0.243208E+10 |
November | 0.000 | 0.281262E+10 |
December | 0.000 | 0.166202E+11 |
Annual Sum or Average | 0.800830E+11 | |
Minimum of Months | 0.000 | 0.109675E+10 |
Maximum of Months | 0.000 | 0.241482E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241482E+11 |
February | 0.000 | 0.125984E+11 |
March | 0.000 | 0.111939E+11 |
April | 0.000 | 0.109675E+10 |
May | 0.000 | 0.214362E+10 |
June | 0.000 | 0.187640E+10 |
July | 0.000 | 0.204830E+10 |
August | 0.000 | 0.114979E+10 |
September | 0.000 | 0.196278E+10 |
October | 0.000 | 0.243208E+10 |
November | 0.000 | 0.281262E+10 |
December | 0.000 | 0.166202E+11 |
Annual Sum or Average | 0.800830E+11 | |
Minimum of Months | 0.000 | 0.109675E+10 |
Maximum of Months | 0.000 | 0.241482E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241482E+11 |
February | 0.000 | 0.125984E+11 |
March | 0.000 | 0.111939E+11 |
April | 0.000 | 0.109675E+10 |
May | 0.000 | 0.214362E+10 |
June | 0.000 | 0.187640E+10 |
July | 0.000 | 0.204830E+10 |
August | 0.000 | 0.114979E+10 |
September | 0.000 | 0.196278E+10 |
October | 0.000 | 0.243208E+10 |
November | 0.000 | 0.281262E+10 |
December | 0.000 | 0.166202E+11 |
Annual Sum or Average | 0.800830E+11 | |
Minimum of Months | 0.000 | 0.109675E+10 |
Maximum of Months | 0.000 | 0.241482E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241482E+11 |
February | 0.000 | 0.125984E+11 |
March | 0.000 | 0.111939E+11 |
April | 0.000 | 0.109675E+10 |
May | 0.000 | 0.214362E+10 |
June | 0.000 | 0.187640E+10 |
July | 0.000 | 0.204830E+10 |
August | 0.000 | 0.114979E+10 |
September | 0.000 | 0.196278E+10 |
October | 0.000 | 0.243208E+10 |
November | 0.000 | 0.281262E+10 |
December | 0.000 | 0.166202E+11 |
Annual Sum or Average | 0.800830E+11 | |
Minimum of Months | 0.000 | 0.109675E+10 |
Maximum of Months | 0.000 | 0.241482E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241482E+11 |
February | 0.000 | 0.125984E+11 |
March | 0.000 | 0.111939E+11 |
April | 0.000 | 0.109675E+10 |
May | 0.000 | 0.214362E+10 |
June | 0.000 | 0.187640E+10 |
July | 0.000 | 0.204830E+10 |
August | 0.000 | 0.114979E+10 |
September | 0.000 | 0.196278E+10 |
October | 0.000 | 0.243208E+10 |
November | 0.000 | 0.281262E+10 |
December | 0.000 | 0.166202E+11 |
Annual Sum or Average | 0.800830E+11 | |
Minimum of Months | 0.000 | 0.109675E+10 |
Maximum of Months | 0.000 | 0.241482E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.241482E+11 |
February | 0.000 | 0.125984E+11 |
March | 0.000 | 0.111939E+11 |
April | 0.000 | 0.109675E+10 |
May | 0.000 | 0.214362E+10 |
June | 0.000 | 0.187640E+10 |
July | 0.000 | 0.204830E+10 |
August | 0.000 | 0.114979E+10 |
September | 0.000 | 0.196278E+10 |
October | 0.000 | 0.243208E+10 |
November | 0.000 | 0.281262E+10 |
December | 0.000 | 0.166202E+11 |
Annual Sum or Average | 0.800830E+11 | |
Minimum of Months | 0.000 | 0.109675E+10 |
Maximum of Months | 0.000 | 0.241482E+11 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.581769E+11 | 108958.05 | 16-JAN-06:12 | 14.00 | 14.00 | 0.566870E+10 | 7499.32 | 05-JAN-14:20 | 14.33 | 9.83 |
February | 0.508710E+11 | 111230.51 | 13-FEB-03:32 | 6.77 | 2.88 | 0.514095E+10 | 7499.15 | 09-FEB-14:20 | 22.20 | 14.16 |
March | 0.582405E+11 | 115460.94 | 20-MAR-03:33 | 12.40 | 8.18 | 0.613371E+10 | 7499.57 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.535680E+11 | 114875.73 | 02-APR-23:10 | 13.58 | 11.45 | 0.545041E+10 | 7499.32 | 13-APR-09:20 | 22.53 | 18.64 |
May | 0.590350E+11 | 106067.87 | 29-MAY-22:43 | 25.60 | 23.86 | 0.590331E+10 | 7498.97 | 26-MAY-09:20 | 28.33 | 25.47 |
June | 0.583306E+11 | 98800.87 | 12-JUN-02:22 | 23.90 | 21.61 | 0.588282E+10 | 7498.97 | 16-JUN-09:20 | 29.80 | 24.49 |
July | 0.610928E+11 | 103722.07 | 04-JUL-19:30 | 28.85 | 25.16 | 0.547540E+10 | 7498.96 | 28-JUL-09:20 | 28.67 | 25.28 |
August | 0.692168E+11 | 100634.45 | 20-AUG-22:23 | 27.50 | 24.29 | 0.613943E+10 | 7498.94 | 02-AUG-09:20 | 29.97 | 25.09 |
September | 0.631104E+11 | 105920.32 | 04-SEP-12:50 | 26.63 | 24.74 | 0.545468E+10 | 7507.17 | 05-SEP-09:30 | 27.15 | 25.12 |
October | 0.663995E+11 | 107627.36 | 17-OCT-04:11 | 17.33 | 12.71 | 0.567369E+10 | 7499.23 | 18-OCT-09:20 | 21.00 | 16.77 |
November | 0.646240E+11 | 113715.29 | 23-NOV-17:23 | 14.55 | 8.55 | 0.561765E+10 | 7499.18 | 13-NOV-14:20 | 23.30 | 17.14 |
December | 0.626600E+11 | 115329.26 | 17-DEC-17:40 | 13.00 | 9.81 | 0.547453E+10 | 7499.63 | 08-DEC-10:00 | 24.00 | 18.76 |
Annual Sum or Average | 0.725326E+12 | 0.680153E+11 | ||||||||
Minimum of Months | 0.508710E+11 | 98800.87 | 6.77 | 2.88 | 0.514095E+10 | 7498.94 | 14.33 | 9.83 | ||
Maximum of Months | 0.692168E+11 | 115460.94 | 28.85 | 25.16 | 0.613943E+10 | 7507.17 | 29.97 | 25.47 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471961E+11 | 86622.30 | 02-JAN-05:14 | 16.67 | 15.63 | 0.506382E+10 | 6734.82 | 05-JAN-14:20 | 14.33 | 9.83 |
February | 0.452104E+11 | 87495.94 | 28-FEB-05:12 | 18.50 | 18.07 | 0.460074E+10 | 6734.72 | 07-FEB-10:20 | 14.03 | 9.96 |
March | 0.567719E+11 | 87400.61 | 28-MAR-03:02 | 19.00 | 18.65 | 0.549633E+10 | 6734.95 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.616986E+11 | 85039.68 | 11-APR-04:12 | 11.23 | 8.55 | 0.487631E+10 | 6734.87 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.579427E+11 | 90251.45 | 31-MAY-03:02 | 23.22 | 21.33 | 0.528351E+10 | 6734.61 | 09-MAY-09:20 | 28.33 | 23.08 |
June | 0.631862E+11 | 87604.42 | 01-JUN-04:12 | 21.50 | 20.44 | 0.526382E+10 | 6734.61 | 23-JUN-09:20 | 29.80 | 25.86 |
July | 0.681187E+11 | 79536.45 | 15-JUL-05:02 | 24.32 | 23.57 | 0.488860E+10 | 6734.61 | 24-JUL-09:20 | 30.37 | 25.94 |
August | 0.747241E+11 | 78209.31 | 01-AUG-05:02 | 23.90 | 22.91 | 0.549006E+10 | 6734.61 | 07-AUG-09:20 | 28.00 | 25.35 |
September | 0.567490E+11 | 90393.64 | 26-SEP-03:02 | 23.80 | 23.06 | 0.487803E+10 | 6734.61 | 25-SEP-09:20 | 25.17 | 23.40 |
October | 0.617380E+11 | 90294.17 | 02-OCT-03:02 | 18.83 | 15.24 | 0.507353E+10 | 6734.81 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.575076E+11 | 89912.61 | 27-NOV-04:02 | 14.30 | 13.51 | 0.502662E+10 | 6734.78 | 13-NOV-10:20 | 16.83 | 13.23 |
December | 0.576176E+11 | 91001.32 | 26-DEC-04:02 | 6.82 | 3.25 | 0.489715E+10 | 6734.76 | 26-DEC-14:00 | 13.30 | 6.25 |
Annual Sum or Average | 0.708461E+12 | 0.608385E+11 | ||||||||
Minimum of Months | 0.452104E+11 | 78209.31 | 6.82 | 3.25 | 0.460074E+10 | 6734.61 | 13.30 | 6.25 | ||
Maximum of Months | 0.747241E+11 | 91001.32 | 24.32 | 23.57 | 0.549633E+10 | 6734.95 | 30.37 | 25.94 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356206E+11 | 74349.67 | 20-JAN-05:11 | 17.00 | 17.00 | 0.498075E+10 | 6734.80 | 05-JAN-14:20 | 14.33 | 9.83 |
February | 0.333278E+11 | 74774.86 | 28-FEB-05:11 | 18.50 | 18.07 | 0.453086E+10 | 6737.48 | 17-FEB-10:30 | 6.35 | 1.88 |
March | 0.405738E+11 | 74920.09 | 31-MAR-04:11 | 16.90 | 16.90 | 0.543489E+10 | 6735.00 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.413632E+11 | 80977.64 | 29-APR-04:12 | 23.30 | 21.86 | 0.485499E+10 | 6734.77 | 03-APR-09:20 | 19.73 | 14.34 |
May | 0.494604E+11 | 82238.05 | 12-MAY-04:12 | 22.97 | 20.20 | 0.526905E+10 | 6734.63 | 26-MAY-13:20 | 27.23 | 24.58 |
June | 0.494712E+11 | 81331.71 | 01-JUN-04:12 | 21.50 | 20.44 | 0.525265E+10 | 6734.64 | 01-JUN-13:20 | 25.00 | 21.39 |
July | 0.492886E+11 | 81959.98 | 12-JUL-04:12 | 23.50 | 23.01 | 0.487744E+10 | 6734.63 | 12-JUL-13:20 | 25.03 | 23.05 |
August | 0.514866E+11 | 77853.08 | 17-AUG-04:12 | 21.93 | 21.62 | 0.548256E+10 | 6734.64 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.467409E+11 | 81559.45 | 22-SEP-04:12 | 21.70 | 20.02 | 0.485928E+10 | 6734.63 | 07-SEP-13:20 | 27.73 | 23.85 |
October | 0.467267E+11 | 79854.33 | 03-OCT-04:12 | 22.00 | 19.94 | 0.505676E+10 | 6734.83 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.404340E+11 | 80466.92 | 02-NOV-04:12 | 23.53 | 22.67 | 0.499018E+10 | 6734.79 | 13-NOV-10:20 | 16.83 | 13.23 |
December | 0.372483E+11 | 75042.62 | 14-DEC-05:11 | 20.00 | 20.00 | 0.483117E+10 | 6765.39 | 04-DEC-10:20 | 11.00 | 8.28 |
Annual Sum or Average | 0.521742E+12 | 0.604206E+11 | ||||||||
Minimum of Months | 0.333278E+11 | 74349.67 | 16.90 | 16.90 | 0.453086E+10 | 6734.63 | 6.35 | 1.88 | ||
Maximum of Months | 0.514866E+11 | 82238.05 | 23.53 | 23.01 | 0.548256E+10 | 6765.39 | 27.90 | 24.58 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.303527E+11 | 70097.24 | 20-JAN-06:03 | 17.00 | 17.00 | 0.462423E+10 | 6734.62 | 31-JAN-10:20 | 22.67 | 20.78 |
February | 0.301785E+11 | 69384.79 | 03-FEB-06:03 | 18.90 | 18.50 | 0.432316E+10 | 6734.62 | 02-FEB-10:20 | 23.63 | 20.37 |
March | 0.373313E+11 | 74429.92 | 27-MAR-05:04 | 19.82 | 18.59 | 0.526451E+10 | 6734.68 | 15-MAR-13:20 | 22.20 | 16.13 |
April | 0.413017E+11 | 80023.00 | 29-APR-04:12 | 23.30 | 21.86 | 0.482924E+10 | 6734.74 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.540976E+11 | 81900.93 | 12-MAY-04:12 | 22.97 | 20.20 | 0.527574E+10 | 6734.61 | 22-MAY-09:20 | 26.67 | 23.41 |
June | 0.550670E+11 | 83598.45 | 14-JUN-03:02 | 25.00 | 22.65 | 0.526204E+10 | 6734.61 | 01-JUN-13:20 | 25.00 | 21.39 |
July | 0.548475E+11 | 80837.50 | 12-JUL-04:12 | 23.50 | 23.01 | 0.488967E+10 | 6734.61 | 03-JUL-13:20 | 31.70 | 25.94 |
August | 0.564736E+11 | 79188.24 | 29-AUG-04:12 | 23.03 | 22.95 | 0.548919E+10 | 6734.61 | 22-AUG-13:20 | 31.47 | 25.50 |
September | 0.495723E+11 | 79830.05 | 29-SEP-04:12 | 23.80 | 22.30 | 0.486404E+10 | 6734.61 | 25-SEP-09:20 | 25.17 | 23.40 |
October | 0.479469E+11 | 81946.27 | 12-OCT-04:12 | 21.93 | 21.34 | 0.504108E+10 | 6734.79 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.365612E+11 | 74854.33 | 01-NOV-05:04 | 22.62 | 22.36 | 0.487864E+10 | 6734.61 | 14-NOV-14:20 | 19.20 | 12.65 |
December | 0.321613E+11 | 72006.25 | 11-DEC-06:02 | 20.83 | 20.26 | 0.456211E+10 | 6734.71 | 18-DEC-14:20 | 16.33 | 10.40 |
Annual Sum or Average | 0.525891E+12 | 0.593036E+11 | ||||||||
Minimum of Months | 0.301785E+11 | 69384.79 | 17.00 | 17.00 | 0.432316E+10 | 6734.61 | 16.33 | 10.40 | ||
Maximum of Months | 0.564736E+11 | 83598.45 | 25.00 | 23.01 | 0.548919E+10 | 6734.79 | 31.70 | 25.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.463524E+10 | 8556.81 | 02-JAN-06:03 | 16.00 | 15.39 | 0.605468E+09 | 845.61 | 26-JAN-14:20 | 17.33 | 9.41 |
February | 0.482011E+10 | 7244.92 | 28-FEB-05:11 | 18.50 | 18.07 | 0.563067E+09 | 845.62 | 09-FEB-14:00 | 22.20 | 14.68 |
March | 0.640225E+10 | 10421.11 | 07-MAR-05:11 | 21.30 | 20.56 | 0.678923E+09 | 845.64 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.836915E+10 | 10223.95 | 28-APR-05:02 | 22.80 | 21.69 | 0.610698E+09 | 845.64 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.992801E+10 | 11767.71 | 23-MAY-05:02 | 23.90 | 23.41 | 0.664502E+09 | 845.61 | 31-MAY-13:20 | 23.73 | 21.76 |
June | 0.112013E+11 | 11848.38 | 13-JUN-05:02 | 23.90 | 21.96 | 0.662110E+09 | 845.61 | 27-JUN-13:20 | 28.50 | 24.66 |
July | 0.117977E+11 | 14011.65 | 23-JUL-15:22 | 31.95 | 25.51 | 0.615588E+09 | 845.61 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.125495E+11 | 12172.38 | 14-AUG-04:21 | 26.10 | 23.90 | 0.690457E+09 | 845.61 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.902526E+10 | 12548.82 | 11-SEP-03:01 | 25.70 | 23.86 | 0.613498E+09 | 845.61 | 20-SEP-13:20 | 26.60 | 22.71 |
October | 0.905254E+10 | 11869.32 | 24-OCT-05:02 | 24.83 | 24.83 | 0.636455E+09 | 845.64 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.657654E+10 | 11129.87 | 02-NOV-04:11 | 23.53 | 22.67 | 0.626156E+09 | 845.63 | 13-NOV-10:20 | 16.83 | 13.23 |
December | 0.588549E+10 | 9917.79 | 11-DEC-06:01 | 20.83 | 20.26 | 0.600647E+09 | 845.62 | 18-DEC-14:20 | 16.33 | 10.40 |
Annual Sum or Average | 0.100243E+12 | 0.756757E+10 | ||||||||
Minimum of Months | 0.463524E+10 | 7244.92 | 16.00 | 15.39 | 0.563067E+09 | 845.61 | 16.33 | 9.41 | ||
Maximum of Months | 0.125495E+11 | 14011.65 | 31.95 | 25.51 | 0.690457E+09 | 845.64 | 28.50 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360991E+10 | 12006.66 | 01-JAN-10:32 | 21.33 | 17.03 | 0.402016E+09 | 544.96 | 24-JAN-14:20 | 17.00 | 10.43 |
February | 0.382338E+10 | 13355.96 | 26-FEB-10:32 | 23.50 | 19.84 | 0.367821E+09 | 544.96 | 09-FEB-10:00 | 15.00 | 12.67 |
March | 0.528388E+10 | 16897.96 | 26-MAR-09:32 | 24.77 | 20.02 | 0.439155E+09 | 544.97 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.659091E+10 | 17126.71 | 23-APR-08:62 | 22.57 | 19.46 | 0.393560E+09 | 544.97 | 03-APR-09:09 | 19.27 | 14.10 |
May | 0.821431E+10 | 19085.67 | 29-MAY-08:31 | 27.43 | 23.02 | 0.428691E+09 | 544.94 | 31-MAY-13:20 | 23.73 | 21.76 |
June | 0.867210E+10 | 16990.57 | 11-JUN-08:62 | 25.47 | 21.09 | 0.426912E+09 | 544.94 | 27-JUN-13:20 | 28.50 | 24.66 |
July | 0.878249E+10 | 17147.59 | 09-JUL-09:22 | 30.85 | 26.27 | 0.396973E+09 | 544.94 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.890874E+10 | 16968.94 | 27-AUG-10:22 | 30.00 | 24.50 | 0.444965E+09 | 544.94 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.691145E+10 | 18265.65 | 24-SEP-09:32 | 29.03 | 24.99 | 0.395790E+09 | 544.94 | 20-SEP-13:20 | 26.60 | 22.71 |
October | 0.694987E+10 | 17036.54 | 15-OCT-08:53 | 23.00 | 19.56 | 0.410593E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.493663E+10 | 16762.04 | 11-NOV-09:13 | 24.40 | 21.68 | 0.404702E+09 | 544.96 | 09-NOV-10:09 | 15.27 | 8.87 |
December | 0.402542E+10 | 7099.56 | 11-DEC-06:01 | 20.83 | 20.26 | 0.386919E+09 | 544.96 | 04-DEC-10:00 | 13.00 | 9.82 |
Annual Sum or Average | 0.767091E+11 | 0.489810E+10 | ||||||||
Minimum of Months | 0.360991E+10 | 7099.56 | 20.83 | 17.03 | 0.367821E+09 | 544.94 | 13.00 | 8.87 | ||
Maximum of Months | 0.890874E+10 | 19085.67 | 30.85 | 26.27 | 0.444965E+09 | 544.97 | 28.50 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.926415E+10 | 18189.80 | 16-JAN-14:42 | 26.83 | 18.69 | 0.628216E+09 | 951.59 | 19-JAN-14:09 | 25.00 | 21.53 |
February | 0.858528E+10 | 17752.58 | 26-FEB-12:32 | 26.10 | 18.91 | 0.574089E+09 | 934.07 | 27-FEB-14:09 | 25.60 | 19.99 |
March | 0.846083E+10 | 16398.50 | 05-MAR-12:43 | 27.52 | 18.31 | 0.677991E+09 | 845.66 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.916427E+10 | 11744.15 | 28-APR-05:02 | 22.80 | 21.69 | 0.610409E+09 | 845.67 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.100514E+11 | 12982.58 | 24-MAY-03:01 | 25.00 | 23.72 | 0.664517E+09 | 845.63 | 31-MAY-13:20 | 23.73 | 21.76 |
June | 0.110298E+11 | 13185.39 | 28-JUN-05:02 | 26.70 | 24.69 | 0.662103E+09 | 845.63 | 27-JUN-13:20 | 28.50 | 24.66 |
July | 0.118022E+11 | 16059.05 | 23-JUL-15:22 | 31.95 | 25.51 | 0.615666E+09 | 845.63 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.132923E+11 | 15932.90 | 20-AUG-13:02 | 33.17 | 24.45 | 0.690660E+09 | 845.63 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.105955E+11 | 17009.44 | 10-SEP-12:23 | 35.10 | 27.76 | 0.614082E+09 | 845.63 | 20-SEP-13:20 | 26.60 | 22.71 |
October | 0.131271E+11 | 18048.88 | 15-OCT-12:52 | 29.00 | 22.07 | 0.643767E+09 | 918.72 | 13-OCT-13:39 | 32.73 | 23.23 |
November | 0.116617E+11 | 18473.70 | 11-NOV-14:32 | 26.43 | 22.95 | 0.640572E+09 | 976.65 | 06-NOV-14:09 | 28.30 | 21.02 |
December | 0.110153E+11 | 18479.74 | 17-DEC-12:52 | 19.00 | 12.83 | 0.616950E+09 | 961.08 | 08-DEC-14:09 | 26.83 | 19.22 |
Annual Sum or Average | 0.128050E+12 | 0.763902E+10 | ||||||||
Minimum of Months | 0.846083E+10 | 11744.15 | 19.00 | 12.83 | 0.574089E+09 | 845.63 | 16.97 | 10.89 | ||
Maximum of Months | 0.132923E+11 | 18479.74 | 35.10 | 27.76 | 0.690660E+09 | 976.65 | 32.73 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505007E+10 | 21450.82 | 16-JAN-16:01 | 24.67 | 18.12 | 0.405266E+09 | 544.96 | 05-JAN-14:20 | 14.33 | 9.83 |
February | 0.612918E+10 | 21612.99 | 26-FEB-15:12 | 25.90 | 20.04 | 0.371972E+09 | 544.96 | 09-FEB-14:00 | 22.20 | 14.68 |
March | 0.860508E+10 | 21925.91 | 26-MAR-16:52 | 25.50 | 19.90 | 0.445535E+09 | 544.97 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.115725E+11 | 22460.40 | 23-APR-16:42 | 27.28 | 21.75 | 0.396557E+09 | 544.98 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.971811E+10 | 22821.67 | 29-MAY-16:31 | 31.33 | 23.67 | 0.429246E+09 | 544.94 | 31-MAY-13:20 | 23.73 | 21.76 |
June | 0.116012E+11 | 22223.57 | 11-JUN-16:42 | 33.12 | 21.80 | 0.427885E+09 | 544.94 | 27-JUN-13:20 | 28.50 | 24.66 |
July | 0.127386E+11 | 22605.63 | 16-JUL-16:11 | 30.93 | 25.21 | 0.398210E+09 | 544.94 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.148811E+11 | 21379.45 | 06-AUG-15:42 | 25.33 | 21.89 | 0.446483E+09 | 544.94 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.905064E+10 | 22341.98 | 24-SEP-16:11 | 30.13 | 25.89 | 0.396434E+09 | 544.94 | 26-SEP-13:20 | 25.53 | 23.20 |
October | 0.102022E+11 | 22545.24 | 08-OCT-15:31 | 31.00 | 25.39 | 0.412257E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.855423E+10 | 22966.00 | 11-NOV-15:12 | 26.43 | 22.95 | 0.407928E+09 | 544.96 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.845732E+10 | 21813.85 | 17-DEC-15:31 | 17.33 | 11.72 | 0.397584E+09 | 544.97 | 26-DEC-14:00 | 13.30 | 6.25 |
Annual Sum or Average | 0.116560E+12 | 0.493536E+10 | ||||||||
Minimum of Months | 0.505007E+10 | 21379.45 | 17.33 | 11.72 | 0.371972E+09 | 544.94 | 13.30 | 6.25 | ||
Maximum of Months | 0.148811E+11 | 22966.00 | 33.12 | 25.89 | 0.446483E+09 | 544.98 | 28.50 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317941E+10 | 5168.09 | 02-JAN-13:30 | 26.00 | 18.62 | 0.548684E+09 | 845.61 | 02-JAN-14:20 | 26.33 | 18.47 |
February | 0.336912E+10 | 5386.36 | 22-FEB-14:30 | 25.55 | 20.40 | 0.522801E+09 | 845.61 | 03-FEB-14:20 | 13.30 | 11.68 |
March | 0.434595E+10 | 6823.35 | 30-MAR-13:20 | 28.83 | 22.62 | 0.636867E+09 | 845.62 | 20-MAR-13:20 | 17.53 | 11.32 |
April | 0.555579E+10 | 9459.07 | 29-APR-04:11 | 23.30 | 21.86 | 0.600354E+09 | 845.62 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.880485E+10 | 11164.00 | 22-MAY-04:31 | 26.10 | 22.45 | 0.664113E+09 | 845.61 | 03-MAY-13:20 | 32.07 | 22.00 |
June | 0.942594E+10 | 11689.77 | 05-JUN-03:02 | 26.52 | 24.30 | 0.662145E+09 | 845.61 | 12-JUN-13:20 | 31.87 | 20.56 |
July | 0.935376E+10 | 12804.61 | 23-JUL-15:12 | 31.87 | 25.19 | 0.615903E+09 | 845.61 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.941859E+10 | 11768.95 | 14-AUG-03:01 | 26.52 | 24.51 | 0.690766E+09 | 845.61 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.764976E+10 | 11633.86 | 11-SEP-03:01 | 25.70 | 23.86 | 0.612417E+09 | 845.61 | 20-SEP-13:20 | 26.60 | 22.71 |
October | 0.702169E+10 | 12729.02 | 08-OCT-15:21 | 31.00 | 25.48 | 0.631356E+09 | 845.64 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.448725E+10 | 9616.02 | 02-NOV-04:11 | 23.53 | 22.67 | 0.600227E+09 | 845.61 | 27-NOV-14:09 | 25.82 | 17.50 |
December | 0.359953E+10 | 5827.31 | 15-DEC-15:00 | 29.00 | 21.55 | 0.544823E+09 | 845.61 | 01-DEC-14:20 | 24.00 | 16.26 |
Annual Sum or Average | 0.762116E+11 | 0.733046E+10 | ||||||||
Minimum of Months | 0.317941E+10 | 5168.09 | 23.30 | 18.62 | 0.522801E+09 | 845.61 | 13.30 | 10.89 | ||
Maximum of Months | 0.942594E+10 | 12804.61 | 31.87 | 25.48 | 0.690766E+09 | 845.64 | 32.07 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234253E+10 | 11525.09 | 01-JAN-08:55 | 19.00 | 15.90 | 0.284241E+09 | 548.49 | 24-JAN-13:09 | 17.00 | 9.98 |
February | 0.276488E+10 | 8473.80 | 27-FEB-11:05 | 22.80 | 19.34 | 0.263661E+09 | 548.50 | 07-FEB-13:09 | 19.53 | 13.92 |
March | 0.404057E+10 | 17117.03 | 26-MAR-09:32 | 24.77 | 20.02 | 0.315905E+09 | 548.52 | 15-MAR-12:09 | 21.70 | 15.86 |
April | 0.537297E+10 | 17559.96 | 23-APR-09:02 | 24.68 | 20.66 | 0.289561E+09 | 548.51 | 10-APR-14:09 | 20.42 | 10.76 |
May | 0.783256E+10 | 18139.46 | 28-MAY-10:42 | 30.92 | 23.95 | 0.316743E+09 | 548.50 | 17-MAY-14:09 | 32.62 | 23.79 |
June | 0.807696E+10 | 17582.17 | 11-JUN-08:62 | 25.47 | 21.09 | 0.315228E+09 | 548.49 | 12-JUN-12:09 | 31.70 | 20.33 |
July | 0.795606E+10 | 18172.02 | 23-JUL-07:52 | 28.30 | 25.78 | 0.294367E+09 | 548.49 | 05-JUL-12:09 | 32.20 | 26.45 |
August | 0.782690E+10 | 18084.55 | 06-AUG-09:52 | 30.00 | 26.94 | 0.328727E+09 | 548.48 | 30-AUG-12:09 | 31.18 | 24.69 |
September | 0.628113E+10 | 18871.94 | 24-SEP-09:42 | 29.22 | 24.97 | 0.292438E+09 | 548.48 | 01-SEP-10:09 | 30.08 | 24.69 |
October | 0.603614E+10 | 18122.68 | 09-OCT-09:51 | 29.00 | 22.61 | 0.302427E+09 | 548.51 | 17-OCT-12:09 | 21.17 | 14.62 |
November | 0.371267E+10 | 9897.84 | 02-NOV-10:05 | 27.88 | 24.04 | 0.295320E+09 | 548.49 | 13-NOV-11:09 | 18.77 | 14.37 |
December | 0.255886E+10 | 8643.33 | 11-DEC-06:01 | 20.83 | 20.26 | 0.273636E+09 | 548.49 | 01-DEC-11:09 | 19.33 | 14.42 |
Annual Sum or Average | 0.648022E+11 | 0.357225E+10 | ||||||||
Minimum of Months | 0.234253E+10 | 8473.80 | 19.00 | 15.90 | 0.263661E+09 | 548.48 | 17.00 | 9.98 | ||
Maximum of Months | 0.807696E+10 | 18871.94 | 30.92 | 26.94 | 0.328727E+09 | 548.52 | 32.62 | 26.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.841473E+10 | 16987.38 | 01-JAN-13:31 | 25.67 | 18.10 | 0.623222E+09 | 1009.42 | 19-JAN-14:39 | 25.00 | 21.53 |
February | 0.759175E+10 | 16730.22 | 26-FEB-14:42 | 26.18 | 20.04 | 0.568130E+09 | 974.06 | 27-FEB-14:39 | 25.90 | 20.25 |
March | 0.672665E+10 | 14110.06 | 05-MAR-14:32 | 27.37 | 18.53 | 0.660135E+09 | 845.66 | 06-MAR-14:09 | 26.52 | 21.54 |
April | 0.661901E+10 | 11121.05 | 29-APR-04:11 | 23.30 | 21.86 | 0.603819E+09 | 845.66 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.896624E+10 | 12950.97 | 22-MAY-04:31 | 26.10 | 22.45 | 0.664128E+09 | 845.63 | 03-MAY-13:20 | 32.07 | 22.00 |
June | 0.920504E+10 | 13501.55 | 05-JUN-03:02 | 26.52 | 24.30 | 0.662006E+09 | 845.63 | 14-JUN-13:20 | 33.87 | 23.64 |
July | 0.933960E+10 | 14829.22 | 23-JUL-15:12 | 31.87 | 25.19 | 0.615869E+09 | 845.62 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.102572E+11 | 13742.34 | 14-AUG-03:01 | 26.52 | 24.51 | 0.691052E+09 | 850.29 | 31-AUG-13:39 | 31.80 | 24.89 |
September | 0.948044E+10 | 15870.27 | 10-SEP-12:23 | 35.10 | 27.76 | 0.613570E+09 | 845.69 | 01-SEP-13:20 | 31.80 | 23.10 |
October | 0.116270E+11 | 17016.40 | 15-OCT-13:32 | 29.67 | 22.64 | 0.648101E+09 | 961.95 | 13-OCT-13:50 | 32.87 | 23.23 |
November | 0.101811E+11 | 17083.46 | 05-NOV-13:22 | 27.20 | 20.72 | 0.642913E+09 | 1030.56 | 06-NOV-14:09 | 28.30 | 21.02 |
December | 0.913192E+10 | 17288.54 | 17-DEC-13:02 | 19.00 | 12.76 | 0.609189E+09 | 1000.50 | 01-DEC-14:09 | 24.00 | 16.18 |
Annual Sum or Average | 0.107541E+12 | 0.760213E+10 | ||||||||
Minimum of Months | 0.661901E+10 | 11121.05 | 19.00 | 12.76 | 0.568130E+09 | 845.62 | 20.50 | 10.89 | ||
Maximum of Months | 0.116270E+11 | 17288.54 | 35.10 | 27.76 | 0.691052E+09 | 1030.56 | 33.87 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313903E+10 | 18110.46 | 01-JAN-16:11 | 24.67 | 18.83 | 0.374641E+09 | 544.95 | 24-JAN-14:00 | 17.00 | 10.69 |
February | 0.350480E+10 | 19088.91 | 26-FEB-16:42 | 24.58 | 19.86 | 0.351909E+09 | 544.95 | 14-FEB-14:00 | 18.80 | 14.23 |
March | 0.439773E+10 | 18004.98 | 26-MAR-16:52 | 25.50 | 19.90 | 0.424027E+09 | 544.95 | 15-MAR-13:20 | 22.20 | 16.13 |
April | 0.602501E+10 | 18729.49 | 23-APR-17:02 | 26.92 | 21.64 | 0.392938E+09 | 544.96 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.771250E+10 | 19135.78 | 29-MAY-16:52 | 30.60 | 23.79 | 0.428653E+09 | 544.94 | 03-MAY-13:20 | 32.07 | 22.00 |
June | 0.827776E+10 | 19054.08 | 11-JUN-16:42 | 33.12 | 21.80 | 0.427420E+09 | 544.94 | 14-JUN-13:20 | 33.87 | 23.64 |
July | 0.799419E+10 | 18202.25 | 16-JUL-15:52 | 31.70 | 25.47 | 0.397706E+09 | 544.94 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.851706E+10 | 18746.77 | 06-AUG-16:31 | 25.33 | 22.97 | 0.445919E+09 | 544.94 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.683118E+10 | 18983.71 | 03-SEP-16:12 | 31.83 | 24.72 | 0.395792E+09 | 544.94 | 20-SEP-13:20 | 26.60 | 22.71 |
October | 0.675141E+10 | 19808.83 | 08-OCT-15:21 | 31.00 | 25.48 | 0.409834E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.437197E+10 | 18288.92 | 05-NOV-15:22 | 27.20 | 19.79 | 0.396912E+09 | 544.95 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.360875E+10 | 13575.60 | 11-DEC-06:01 | 20.83 | 20.26 | 0.369213E+09 | 544.95 | 18-DEC-14:20 | 16.33 | 10.40 |
Annual Sum or Average | 0.711314E+11 | 0.481496E+10 | ||||||||
Minimum of Months | 0.313903E+10 | 13575.60 | 20.83 | 18.83 | 0.351909E+09 | 544.94 | 16.33 | 10.40 | ||
Maximum of Months | 0.851706E+10 | 19808.83 | 33.12 | 25.48 | 0.445919E+09 | 544.96 | 33.87 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249836E+10 | 5484.65 | 31-JAN-15:00 | 25.00 | 21.54 | 0.527270E+09 | 845.60 | 02-JAN-14:20 | 26.33 | 18.47 |
February | 0.299053E+10 | 5820.76 | 22-FEB-14:30 | 25.55 | 20.40 | 0.506678E+09 | 845.61 | 10-FEB-14:20 | 22.70 | 17.14 |
March | 0.408645E+10 | 7302.52 | 30-MAR-13:30 | 28.55 | 22.54 | 0.617589E+09 | 845.61 | 24-MAR-13:20 | 24.03 | 15.86 |
April | 0.566661E+10 | 9492.73 | 28-APR-05:02 | 22.80 | 21.69 | 0.593072E+09 | 845.63 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.946370E+10 | 15066.85 | 29-MAY-16:01 | 32.43 | 23.40 | 0.664252E+09 | 845.60 | 03-MAY-13:20 | 32.07 | 22.00 |
June | 0.102451E+11 | 14787.62 | 04-JUN-15:42 | 29.50 | 24.77 | 0.662351E+09 | 845.61 | 12-JUN-13:20 | 31.87 | 20.56 |
July | 0.101889E+11 | 15145.11 | 23-JUL-15:12 | 31.87 | 25.19 | 0.616303E+09 | 845.61 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.101452E+11 | 14172.44 | 20-AUG-13:02 | 33.17 | 24.45 | 0.690803E+09 | 845.60 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.808439E+10 | 15364.36 | 10-SEP-14:51 | 35.60 | 27.27 | 0.612264E+09 | 845.61 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.724738E+10 | 15178.72 | 08-OCT-15:21 | 31.00 | 25.48 | 0.627032E+09 | 845.64 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.416818E+10 | 10743.11 | 01-NOV-05:02 | 22.62 | 22.36 | 0.582048E+09 | 845.61 | 20-NOV-14:20 | 21.60 | 17.35 |
December | 0.301933E+10 | 6373.05 | 15-DEC-15:00 | 29.00 | 21.55 | 0.522973E+09 | 845.60 | 08-DEC-14:20 | 26.67 | 19.25 |
Annual Sum or Average | 0.778041E+11 | 0.722263E+10 | ||||||||
Minimum of Months | 0.249836E+10 | 5484.65 | 22.62 | 20.40 | 0.506678E+09 | 845.60 | 20.50 | 10.89 | ||
Maximum of Months | 0.102451E+11 | 15364.36 | 35.60 | 27.27 | 0.690803E+09 | 845.64 | 32.07 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223150E+10 | 10812.07 | 01-JAN-09:37 | 19.67 | 16.10 | 0.368968E+09 | 544.94 | 02-JAN-14:20 | 26.33 | 18.47 |
February | 0.271239E+10 | 7061.48 | 27-FEB-10:20 | 21.63 | 19.26 | 0.349273E+09 | 544.95 | 09-FEB-10:00 | 15.00 | 12.67 |
March | 0.403661E+10 | 11810.48 | 26-MAR-10:33 | 26.63 | 20.13 | 0.421723E+09 | 544.98 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.564490E+10 | 17651.72 | 23-APR-09:42 | 25.82 | 20.98 | 0.391046E+09 | 544.97 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.855632E+10 | 18972.17 | 29-MAY-08:41 | 27.62 | 23.18 | 0.428797E+09 | 544.94 | 03-MAY-13:20 | 32.07 | 22.00 |
June | 0.892406E+10 | 18388.65 | 04-JUN-10:22 | 30.00 | 23.97 | 0.427299E+09 | 544.94 | 12-JUN-13:20 | 31.87 | 20.56 |
July | 0.881060E+10 | 18385.52 | 23-JUL-07:52 | 28.30 | 25.78 | 0.397699E+09 | 544.94 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.860460E+10 | 18364.26 | 27-AUG-10:22 | 30.00 | 24.50 | 0.445647E+09 | 544.94 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.686478E+10 | 19573.24 | 10-SEP-09:31 | 33.77 | 27.15 | 0.395542E+09 | 544.94 | 27-SEP-13:20 | 23.30 | 22.57 |
October | 0.641515E+10 | 18356.68 | 09-OCT-09:51 | 29.00 | 22.61 | 0.407856E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.360321E+10 | 12274.77 | 11-NOV-09:02 | 24.40 | 21.68 | 0.396102E+09 | 544.95 | 24-NOV-10:20 | 20.87 | 16.30 |
December | 0.244258E+10 | 5620.04 | 16-DEC-09:40 | 23.33 | 20.99 | 0.356815E+09 | 544.95 | 07-DEC-14:20 | 21.00 | 11.72 |
Annual Sum or Average | 0.688467E+11 | 0.478677E+10 | ||||||||
Minimum of Months | 0.223150E+10 | 5620.04 | 19.67 | 16.10 | 0.349273E+09 | 544.94 | 15.00 | 10.89 | ||
Maximum of Months | 0.892406E+10 | 19573.24 | 33.77 | 27.15 | 0.445647E+09 | 544.98 | 32.07 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.718269E+10 | 18830.42 | 01-JAN-14:11 | 25.67 | 18.11 | 0.605275E+09 | 976.14 | 19-JAN-14:39 | 25.00 | 21.53 |
February | 0.694953E+10 | 17725.09 | 26-FEB-12:13 | 26.10 | 19.35 | 0.553843E+09 | 941.76 | 27-FEB-14:39 | 25.90 | 20.25 |
March | 0.634122E+10 | 16839.09 | 26-MAR-13:53 | 30.00 | 19.86 | 0.643655E+09 | 845.63 | 15-MAR-13:20 | 22.20 | 16.13 |
April | 0.672090E+10 | 12061.03 | 29-APR-04:11 | 23.30 | 21.86 | 0.597134E+09 | 845.66 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.961792E+10 | 16955.59 | 29-MAY-16:01 | 32.43 | 23.40 | 0.664201E+09 | 845.62 | 03-MAY-13:20 | 32.07 | 22.00 |
June | 0.100126E+11 | 16636.44 | 04-JUN-15:02 | 29.90 | 25.35 | 0.662171E+09 | 845.62 | 12-JUN-13:20 | 31.87 | 20.56 |
July | 0.101637E+11 | 17035.35 | 23-JUL-15:12 | 31.87 | 25.19 | 0.616236E+09 | 845.62 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.109906E+11 | 16665.62 | 27-AUG-13:02 | 33.17 | 23.62 | 0.691037E+09 | 845.62 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.997442E+10 | 18359.76 | 10-SEP-14:51 | 35.60 | 27.27 | 0.613313E+09 | 845.63 | 26-SEP-13:20 | 25.53 | 23.20 |
October | 0.119077E+11 | 18842.21 | 08-OCT-15:21 | 31.00 | 25.48 | 0.640812E+09 | 941.66 | 13-OCT-13:50 | 32.87 | 23.23 |
November | 0.960238E+10 | 19161.79 | 11-NOV-12:22 | 26.60 | 22.49 | 0.627799E+09 | 997.23 | 06-NOV-14:09 | 28.30 | 21.02 |
December | 0.823556E+10 | 19912.31 | 10-DEC-12:51 | 27.00 | 20.21 | 0.586965E+09 | 965.95 | 15-DEC-14:50 | 29.00 | 21.64 |
Annual Sum or Average | 0.107699E+12 | 0.750244E+10 | ||||||||
Minimum of Months | 0.634122E+10 | 12061.03 | 23.30 | 18.11 | 0.553843E+09 | 845.62 | 20.50 | 10.89 | ||
Maximum of Months | 0.119077E+11 | 19912.31 | 35.60 | 27.27 | 0.691037E+09 | 997.23 | 32.87 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272292E+10 | 19290.40 | 01-JAN-16:11 | 24.67 | 18.83 | 0.362748E+09 | 544.94 | 02-JAN-14:20 | 26.33 | 18.47 |
February | 0.326756E+10 | 20151.64 | 26-FEB-17:32 | 23.67 | 19.47 | 0.343454E+09 | 544.94 | 14-FEB-14:00 | 18.80 | 14.23 |
March | 0.423847E+10 | 18232.82 | 05-MAR-16:23 | 26.10 | 18.79 | 0.412885E+09 | 544.95 | 15-MAR-13:20 | 22.20 | 16.13 |
April | 0.611299E+10 | 20907.99 | 16-APR-17:02 | 19.30 | 13.52 | 0.389630E+09 | 544.96 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.816710E+10 | 22479.26 | 29-MAY-16:01 | 32.43 | 23.40 | 0.428724E+09 | 544.94 | 03-MAY-13:20 | 32.07 | 22.00 |
June | 0.884986E+10 | 20572.28 | 04-JUN-16:22 | 29.70 | 24.64 | 0.427450E+09 | 544.94 | 12-JUN-13:20 | 31.87 | 20.56 |
July | 0.858410E+10 | 19696.91 | 23-JUL-15:12 | 31.87 | 25.19 | 0.397800E+09 | 544.94 | 14-JUL-13:20 | 26.67 | 25.30 |
August | 0.900471E+10 | 17790.99 | 06-AUG-16:42 | 25.67 | 23.42 | 0.445951E+09 | 544.94 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.716327E+10 | 21440.14 | 10-SEP-14:51 | 35.60 | 27.27 | 0.395720E+09 | 544.94 | 26-SEP-13:20 | 25.53 | 23.20 |
October | 0.690496E+10 | 21538.39 | 08-OCT-15:21 | 31.00 | 25.48 | 0.407938E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.413546E+10 | 19939.52 | 11-NOV-15:42 | 26.18 | 22.87 | 0.388228E+09 | 544.95 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.322765E+10 | 20091.52 | 10-DEC-15:31 | 27.33 | 20.15 | 0.356584E+09 | 544.94 | 07-DEC-14:20 | 21.00 | 11.72 |
Annual Sum or Average | 0.723790E+11 | 0.475711E+10 | ||||||||
Minimum of Months | 0.272292E+10 | 17790.99 | 19.30 | 13.52 | 0.343454E+09 | 544.94 | 18.80 | 10.89 | ||
Maximum of Months | 0.900471E+10 | 22479.26 | 35.60 | 27.27 | 0.445951E+09 | 544.96 | 32.07 | 25.30 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363712E+10 | 11479.99 | 02-JAN-06:03 | 16.00 | 15.39 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.386327E+10 | 6539.40 | 28-FEB-06:03 | 18.38 | 17.90 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.502901E+10 | 7108.36 | 27-MAR-05:02 | 19.82 | 18.59 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.617874E+10 | 7594.95 | 24-APR-05:01 | 20.08 | 20.03 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.739713E+10 | 8378.09 | 08-MAY-05:02 | 23.90 | 21.88 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.787445E+10 | 8677.48 | 19-JUN-05:01 | 25.00 | 24.24 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.832988E+10 | 9542.37 | 06-JUL-05:02 | 25.10 | 23.75 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.912429E+10 | 9182.88 | 22-AUG-05:01 | 25.52 | 24.77 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.704152E+10 | 10094.00 | 11-SEP-05:02 | 25.42 | 23.91 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.740572E+10 | 10438.05 | 23-OCT-05:01 | 24.50 | 23.87 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.577344E+10 | 7981.38 | 13-NOV-06:13 | 9.60 | 8.03 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.491026E+10 | 8652.24 | 11-DEC-06:01 | 20.83 | 20.26 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.765648E+11 | 0.00 | ||||||||
Minimum of Months | 0.363712E+10 | 6539.40 | 9.60 | 8.03 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.912429E+10 | 11479.99 | 25.52 | 24.77 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188878E+10 | 7017.12 | 05-JAN-06:02 | 0.17 | 0.10 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.206421E+10 | 4451.95 | 06-FEB-06:03 | 2.88 | 0.91 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.279415E+10 | 3658.25 | 01-MAR-06:17 | 15.53 | 13.90 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.391424E+10 | 5064.30 | 28-APR-16:00 | 32.20 | 25.54 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.619315E+10 | 7352.47 | 06-MAY-05:01 | 24.40 | 21.68 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.641656E+10 | 7480.85 | 16-JUN-05:02 | 24.50 | 23.34 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.649558E+10 | 8167.34 | 08-JUL-05:02 | 24.90 | 23.43 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.670070E+10 | 8442.06 | 05-AUG-05:01 | 25.63 | 23.91 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.563609E+10 | 8188.84 | 01-SEP-05:02 | 24.42 | 23.28 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.551325E+10 | 9455.89 | 05-OCT-05:01 | 24.00 | 22.62 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.328772E+10 | 4840.04 | 07-NOV-16:50 | 26.28 | 23.37 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.245573E+10 | 5836.74 | 21-DEC-06:01 | 0.83 | 0.01 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.533602E+11 | 0.00 | ||||||||
Minimum of Months | 0.188878E+10 | 3658.25 | 0.17 | 0.01 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.670070E+10 | 9455.89 | 32.20 | 25.54 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201950E+10 | 8911.24 | 19-JAN-15:05 | 25.00 | 21.42 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.299760E+10 | 10600.38 | 24-FEB-15:05 | 25.50 | 20.90 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.418976E+10 | 11169.48 | 06-MAR-14:40 | 26.27 | 21.24 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.704506E+10 | 15752.74 | 28-APR-15:00 | 33.30 | 23.04 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.113845E+11 | 17709.56 | 17-MAY-14:00 | 32.80 | 23.70 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.125801E+11 | 17452.26 | 28-JUN-14:30 | 33.60 | 26.18 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.120249E+11 | 17860.15 | 07-JUL-14:50 | 34.82 | 23.94 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.121229E+11 | 17051.68 | 03-AUG-15:00 | 35.00 | 24.83 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.924085E+10 | 15552.52 | 01-SEP-14:00 | 32.20 | 22.61 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.877035E+10 | 15183.25 | 05-OCT-15:00 | 34.00 | 24.03 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.416043E+10 | 12030.19 | 02-NOV-14:20 | 29.40 | 24.36 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.263092E+10 | 10353.08 | 15-DEC-15:00 | 29.00 | 21.55 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.891668E+11 | 0.00 | ||||||||
Minimum of Months | 0.201950E+10 | 8911.24 | 25.00 | 20.90 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.125801E+11 | 17860.15 | 35.00 | 26.18 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388425E+10 | 2129.44 | 01-JAN-17:30 | 22.00 | 18.78 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.826932E+10 | 4199.47 | 26-FEB-18:00 | 23.30 | 19.28 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.142983E+11 | 5807.49 | 05-MAR-17:47 | 24.18 | 18.26 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.188632E+11 | 7991.50 | 16-APR-18:12 | 18.07 | 13.18 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.447340E+10 | 2109.51 | 29-MAY-18:06 | 29.22 | 23.46 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.918631E+10 | 3969.25 | 11-JUN-18:30 | 31.40 | 21.45 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.145536E+11 | 5796.99 | 23-JUL-19:00 | 30.60 | 25.71 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.196240E+11 | 7706.21 | 06-AUG-17:57 | 25.00 | 23.59 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.434779E+10 | 2200.71 | 03-SEP-18:05 | 29.72 | 24.13 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.952681E+10 | 4099.96 | 01-OCT-17:38 | 25.67 | 17.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.139946E+11 | 6009.17 | 12-NOV-17:10 | 14.53 | 8.51 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.193966E+11 | 7893.22 | 25-DEC-16:55 | 16.00 | 9.53 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.140418E+12 | 0.00 | ||||||||
Minimum of Months | 0.388425E+10 | 2109.51 | 14.53 | 8.51 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.196240E+11 | 7991.50 | 31.40 | 25.71 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259725E+10 | 1796.21 | 01-JAN-17:12 | 22.67 | 18.99 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.702121E+10 | 3845.86 | 26-FEB-17:52 | 23.30 | 19.28 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.129158E+11 | 5397.72 | 06-MAR-18:00 | 23.80 | 20.71 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.177962E+11 | 7495.77 | 16-APR-18:17 | 18.07 | 13.18 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.405060E+10 | 1925.99 | 28-MAY-18:30 | 29.15 | 24.65 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.867352E+10 | 3744.88 | 11-JUN-18:30 | 31.40 | 21.45 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.138378E+11 | 5458.77 | 23-JUL-19:00 | 30.60 | 25.71 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.186833E+11 | 7254.47 | 06-AUG-17:33 | 25.33 | 23.69 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.386285E+10 | 2053.69 | 03-SEP-17:54 | 29.90 | 24.07 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.881183E+10 | 3819.18 | 09-OCT-17:26 | 27.00 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.127556E+11 | 5539.72 | 06-NOV-17:00 | 26.60 | 19.71 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.176166E+11 | 7277.82 | 17-DEC-17:05 | 14.50 | 10.50 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.128623E+12 | 0.00 | ||||||||
Minimum of Months | 0.259725E+10 | 1796.21 | 14.50 | 10.50 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.186833E+11 | 7495.77 | 31.40 | 25.71 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165421E+10 | 1846.89 | 01-JAN-17:20 | 22.67 | 18.99 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.623433E+10 | 3865.13 | 26-FEB-18:00 | 23.30 | 19.28 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.123736E+11 | 5460.43 | 06-MAR-17:50 | 24.00 | 20.78 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.176626E+11 | 7663.99 | 23-APR-18:02 | 25.13 | 21.18 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.417372E+10 | 2250.48 | 29-MAY-18:20 | 29.03 | 23.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.881585E+10 | 4018.52 | 11-JUN-18:30 | 31.40 | 21.45 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.139956E+11 | 5717.28 | 23-JUL-19:00 | 30.60 | 25.71 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.187888E+11 | 7507.98 | 06-AUG-17:46 | 25.17 | 23.64 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.395034E+10 | 2321.28 | 03-SEP-17:58 | 29.90 | 24.07 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.874181E+10 | 4057.37 | 09-OCT-17:22 | 27.00 | 20.64 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.122397E+11 | 5601.28 | 06-NOV-17:00 | 26.60 | 19.71 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.167591E+11 | 7357.71 | 10-DEC-17:08 | 24.83 | 19.68 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.125390E+12 | 0.00 | ||||||||
Minimum of Months | 0.165421E+10 | 1846.89 | 22.67 | 18.99 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.187888E+11 | 7663.99 | 31.40 | 25.71 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239339E+12 | 91354.23 | 02-JAN-17:00 | 26.00 | 18.37 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.435621E+12 | 182014.71 | 27-FEB-17:00 | 24.40 | 20.27 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.726845E+12 | 273049.29 | 06-MAR-17:00 | 25.00 | 21.10 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.940645E+12 | 364767.52 | 28-APR-19:00 | 23.80 | 22.30 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.238951E+12 | 102969.62 | 01-MAY-00:03 | 22.45 | 19.10 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.467244E+12 | 181565.42 | 12-JUN-16:00 | 33.30 | 21.01 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.729422E+12 | 273855.65 | 05-JUL-16:00 | 30.00 | 24.67 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.975679E+12 | 370618.64 | 06-AUG-15:42 | 25.33 | 21.89 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.235024E+12 | 106454.83 | 01-SEP-00:10 | 24.85 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.486750E+12 | 183247.81 | 10-OCT-16:00 | 30.00 | 22.38 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.708174E+12 | 274889.91 | 06-NOV-17:00 | 26.60 | 19.71 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.976563E+12 | 366630.93 | 26-DEC-17:00 | 12.70 | 5.58 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.716026E+13 | 0.00 | ||||||||
Minimum of Months | 0.235024E+12 | 91354.23 | 12.70 | 5.58 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.976563E+12 | 370618.64 | 33.30 | 24.67 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.740655E+09 | 114335.96 | 16-JAN-14:45 | 26.83 |
February | 0.662825E+09 | 112505.28 | 20-FEB-12:27 | 23.25 |
March | 0.607264E+09 | 116681.01 | 04-MAR-04:07 | 14.98 |
April | 0.713463E+09 | 113134.17 | 30-APR-23:10 | 21.47 |
May | 0.137608E+10 | 120301.74 | 21-MAY-23:10 | 26.10 |
June | 0.120400E+10 | 123941.28 | 15-JUN-04:30 | 25.60 |
July | 0.138438E+10 | 127200.75 | 02-JUL-15:38 | 29.07 |
August | 0.877024E+09 | 124396.60 | 06-AUG-11:30 | 31.00 |
September | 0.134386E+10 | 125755.67 | 10-SEP-13:30 | 35.40 |
October | 0.147713E+10 | 125685.50 | 08-OCT-13:27 | 32.50 |
November | 0.131882E+10 | 121392.61 | 11-NOV-14:50 | 26.52 |
December | 0.134163E+10 | 119190.43 | 10-DEC-15:30 | 27.50 |
Annual Sum or Average | 0.130471E+11 | |||
Minimum of Months | 0.607264E+09 | 112505.28 | 14.98 | |
Maximum of Months | 0.147713E+10 | 127200.75 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59992833.52 | 46795.65 | 23-JAN-06:02 | 6.83 |
February | 0.224303E+09 | 51949.83 | 06-FEB-05:11 | 2.97 |
March | 16672418.44 | 46401.02 | 13-MAR-05:03 | 6.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 12077127.05 | 46491.26 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.313045E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.224303E+09 | 51949.83 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142443E+09 | 9414.27 | 10-JAN-05:01 | 1.33 |
February | 72702998.58 | 9704.61 | 06-FEB-05:11 | 2.97 |
March | 33139507.74 | 8911.22 | 09-MAR-06:03 | 1.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 73936165.71 | 9375.65 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.322222E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.142443E+09 | 9704.61 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61364906.85 | 7917.34 | 10-JAN-05:01 | 1.33 |
February | 29494178.97 | 8190.98 | 06-FEB-05:11 | 2.97 |
March | 14777221.59 | 7501.51 | 09-MAR-06:03 | 1.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 41146689.25 | 7942.41 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.146783E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 61364906.85 | 8190.98 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26358314.11 | 9791.42 | 21-JAN-06:03 | 1.00 |
February | 12107248.86 | 9631.94 | 06-FEB-06:03 | 2.88 |
March | 8252621.10 | 8525.43 | 11-MAR-06:03 | 6.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 25197415.37 | 10011.03 | 20-DEC-06:02 | 2.83 |
Annual Sum or Average | 71915599.45 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 26358314.11 | 10011.03 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32416484.09 | 6646.01 | 21-JAN-06:03 | 1.00 |
February | 13149104.92 | 6431.29 | 06-FEB-06:03 | 2.88 |
March | 2897522.09 | 4250.79 | 11-MAR-06:03 | 6.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 16596375.74 | 6849.01 | 20-DEC-06:02 | 2.83 |
Annual Sum or Average | 65059486.83 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 32416484.09 | 6849.01 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.886419E+09 | 12022.82 | 23-JAN-05:11 | 7.67 |
February | 0.521568E+09 | 12955.90 | 05-FEB-08:63 | -2.9 |
March | 0.309194E+09 | 11454.06 | 13-MAR-04:11 | 7.00 |
April | 15225.15 | 253.75 | 03-APR-05:03 | 12.28 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 391105.99 | 3089.85 | 28-OCT-05:02 | 10.00 |
November | 54314614.84 | 10561.51 | 16-NOV-05:16 | 9.27 |
December | 0.545231E+09 | 11788.82 | 21-DEC-04:01 | 1.67 |
Annual Sum or Average | 0.231713E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.9 | |
Maximum of Months | 0.886419E+09 | 12955.90 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.392249E+09 | 11085.15 | 23-JAN-05:11 | 7.67 |
February | 0.210124E+09 | 12061.50 | 06-FEB-05:11 | 2.97 |
March | 0.164444E+09 | 10426.00 | 10-MAR-05:11 | 5.77 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 154040.68 | 1283.67 | 28-OCT-05:02 | 10.00 |
November | 16439741.85 | 9251.50 | 16-NOV-06:02 | 9.40 |
December | 0.285440E+09 | 11068.67 | 21-DEC-04:01 | 1.67 |
Annual Sum or Average | 0.106885E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.67 | |
Maximum of Months | 0.392249E+09 | 12061.50 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381355E+09 | 12855.96 | 10-JAN-05:01 | 1.33 |
February | 0.235895E+09 | 13845.69 | 06-FEB-04:01 | 3.35 |
March | 0.211408E+09 | 12497.41 | 11-MAR-05:11 | 7.13 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 4272545.76 | 11341.30 | 16-NOV-06:02 | 9.40 |
December | 0.238685E+09 | 12927.71 | 20-DEC-05:11 | 4.33 |
Annual Sum or Average | 0.107162E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 0.381355E+09 | 13845.69 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290054E+09 | 10330.12 | 10-JAN-05:01 | 1.33 |
February | 0.158919E+09 | 11248.42 | 06-FEB-04:01 | 3.35 |
March | 90322218.45 | 9634.55 | 10-MAR-05:11 | 5.77 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 3318837.14 | 8375.13 | 16-NOV-06:02 | 9.40 |
December | 0.148666E+09 | 10330.18 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.691279E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.290054E+09 | 11248.42 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56546397.72 | 8805.98 | 09-JAN-05:11 | 7.67 |
February | 56502890.04 | 8613.14 | 06-FEB-05:11 | 2.97 |
March | 61523088.11 | 8976.76 | 13-MAR-04:11 | 7.00 |
April | 72279423.44 | 9188.37 | 03-APR-03:01 | 12.58 |
May | 37717372.48 | 7090.93 | 02-MAY-03:01 | 24.13 |
June | 40574565.78 | 6482.11 | 07-JUN-03:01 | 21.10 |
July | 41605374.31 | 5762.25 | 23-JUL-15:22 | 31.95 |
August | 34737532.35 | 4689.28 | 20-AUG-13:02 | 33.17 |
September | 41480850.22 | 7184.39 | 29-SEP-03:01 | 23.80 |
October | 70897015.88 | 7741.62 | 30-OCT-03:02 | 17.00 |
November | 80549752.69 | 9695.44 | 12-NOV-08:14 | 7.57 |
December | 0.107665E+09 | 9951.11 | 22-DEC-05:11 | 8.67 |
Annual Sum or Average | 0.702079E+09 | |||
Minimum of Months | 34737532.35 | 4689.28 | 2.97 | |
Maximum of Months | 0.107665E+09 | 9951.11 | 33.17 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169437E+09 | 5270.01 | 13-JAN-06:03 | 7.17 |
February | 0.108918E+09 | 5198.54 | 16-FEB-06:03 | 16.33 |
March | 73466502.50 | 5213.74 | 20-MAR-04:12 | 12.27 |
April | 20392991.36 | 4714.39 | 10-APR-04:12 | 12.60 |
May | 24956261.71 | 5776.41 | 22-MAY-03:02 | 26.10 |
June | 16629747.36 | 5513.48 | 29-JUN-03:01 | 25.60 |
July | 22814405.06 | 5606.11 | 19-JUL-03:01 | 27.20 |
August | 18521451.13 | 5432.79 | 23-AUG-03:01 | 26.48 |
September | 28416021.74 | 5181.96 | 10-SEP-15:42 | 34.52 |
October | 32247766.99 | 5237.21 | 23-OCT-03:01 | 24.98 |
November | 35389317.20 | 4839.84 | 02-NOV-04:11 | 23.53 |
December | 87410960.70 | 5412.15 | 27-DEC-06:02 | 12.00 |
Annual Sum or Average | 0.638600E+09 | |||
Minimum of Months | 16629747.36 | 4714.39 | 7.17 | |
Maximum of Months | 0.169437E+09 | 5776.41 | 34.52 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145946E+10 | 9940.27 | 10-JAN-06:03 | 3.00 |
February | 0.899636E+09 | 15980.96 | 06-FEB-06:15 | 3.07 |
March | 0.791423E+09 | 13347.45 | 08-MAR-06:03 | 11.00 |
April | 0.176790E+09 | 13534.53 | 17-APR-05:02 | 12.70 |
May | 30163959.01 | 8095.95 | 17-MAY-04:11 | 22.20 |
June | 21928293.35 | 7915.08 | 07-JUN-04:11 | 21.10 |
July | 17536438.30 | 8010.81 | 17-JUL-03:01 | 24.90 |
August | 18712370.90 | 7256.86 | 31-AUG-03:01 | 25.20 |
September | 22371727.67 | 7575.25 | 08-SEP-05:02 | 24.58 |
October | 99319885.02 | 12254.53 | 18-OCT-05:02 | 15.17 |
November | 0.349814E+09 | 10532.76 | 06-NOV-06:03 | 18.80 |
December | 0.108133E+10 | 11092.80 | 21-DEC-06:02 | 0.83 |
Annual Sum or Average | 0.496849E+10 | |||
Minimum of Months | 17536438.30 | 7256.86 | 0.83 | |
Maximum of Months | 0.145946E+10 | 15980.96 | 25.20 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156065E+09 | 524.39 | 25-JAN-05:12 | 9.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.156065E+09 | |||
Minimum of Months | 0.00 | 0.00 | 9.00 | |
Maximum of Months | 0.156065E+09 | 524.39 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.146017E+11 | 15605.75 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.132465E+11 | 15605.75 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.157676E+11 | 15605.75 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.140562E+11 | 15605.75 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.151846E+11 | 15605.75 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.151213E+11 | 15605.75 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.141196E+11 | 15605.75 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.157673E+11 | 15605.75 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.140562E+11 | 15605.75 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.146020E+11 | 15605.75 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.144381E+11 | 15605.75 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.141198E+11 | 15605.75 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.175081E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.132465E+11 | 15605.75 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.157676E+11 | 15605.75 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.131134E+11 | 14015.06 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.118963E+11 | 14015.06 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.141604E+11 | 14015.06 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.126235E+11 | 14015.06 | 03-APR-07:10 | 0.235253E+11 | 17206.63 | 03-APR-07:10 |
May | 0.136369E+11 | 14015.06 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.135800E+11 | 14015.06 | 01-JUN-07:10 | 0.244214E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.126804E+11 | 14015.06 | 03-JUL-07:10 | 0.239654E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.141602E+11 | 14015.06 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.126235E+11 | 14015.06 | 01-SEP-07:10 | 0.235253E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.131136E+11 | 14015.06 | 02-OCT-07:10 | 0.243681E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.129664E+11 | 14015.06 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.126806E+11 | 14015.06 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.157235E+12 | 0.289609E+12 | ||||
Minimum of Months | 0.118963E+11 | 14015.06 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.141604E+11 | 14015.06 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.131134E+11 | 14015.06 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.118963E+11 | 14015.06 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.141604E+11 | 14015.06 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.126235E+11 | 14015.06 | 03-APR-07:10 | 0.235252E+11 | 17206.56 | 03-APR-07:10 |
May | 0.136369E+11 | 14015.06 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.135800E+11 | 14015.06 | 01-JUN-07:10 | 0.244213E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.126804E+11 | 14015.06 | 03-JUL-07:10 | 0.239653E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.141602E+11 | 14015.06 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.126235E+11 | 14015.06 | 01-SEP-07:10 | 0.235252E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.131136E+11 | 14015.06 | 02-OCT-07:10 | 0.243680E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.129664E+11 | 14015.06 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.126806E+11 | 14015.06 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.157235E+12 | 0.289607E+12 | ||||
Minimum of Months | 0.118963E+11 | 14015.06 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.141604E+11 | 14015.06 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.131134E+11 | 14015.06 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.118963E+11 | 14015.06 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.141604E+11 | 14015.06 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.126235E+11 | 14015.06 | 03-APR-07:10 | 0.235252E+11 | 17206.56 | 03-APR-07:10 |
May | 0.136369E+11 | 14015.06 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.135800E+11 | 14015.06 | 01-JUN-07:10 | 0.244213E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.126804E+11 | 14015.06 | 03-JUL-07:10 | 0.239653E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.141602E+11 | 14015.06 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.126235E+11 | 14015.06 | 01-SEP-07:10 | 0.235252E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.131136E+11 | 14015.06 | 02-OCT-07:10 | 0.243680E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.129664E+11 | 14015.06 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.126806E+11 | 14015.06 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.157235E+12 | 0.289607E+12 | ||||
Minimum of Months | 0.118963E+11 | 14015.06 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.141604E+11 | 14015.06 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.991545E+09 | 1428.41 | 31-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.867260E+09 | 1482.30 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.999679E+09 | 1354.96 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.871283E+09 | 1397.05 | 14-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.911467E+09 | 971.14 | 23-MAY-07:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.896938E+09 | 837.28 | 01-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.846297E+09 | 941.35 | 14-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.960531E+09 | 975.99 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.881821E+09 | 1350.95 | 26-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.939841E+09 | 1559.68 | 25-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.976267E+09 | 1491.27 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.980296E+09 | 1546.07 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.111232E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.846297E+09 | 837.28 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.999679E+09 | 1559.68 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.628303E+09 | 856.72 | 31-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.552649E+09 | 914.96 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.638825E+09 | 798.98 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.560213E+09 | 858.96 | 14-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.590453E+09 | 607.56 | 30-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.582368E+09 | 539.58 | 01-JUN-07:10 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.548131E+09 | 539.58 | 03-JUL-07:10 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.619454E+09 | 603.11 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.566676E+09 | 793.48 | 26-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.601112E+09 | 978.27 | 25-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.621421E+09 | 973.50 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.622985E+09 | 979.75 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.713259E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.548131E+09 | 539.58 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.638825E+09 | 979.75 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.952596E+09 | 1380.38 | 31-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.846436E+09 | 1452.25 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.990796E+09 | 1338.52 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.873562E+09 | 1403.46 | 14-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.919852E+09 | 978.30 | 23-MAY-07:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.907015E+09 | 911.74 | 16-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.853715E+09 | 962.43 | 14-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.964511E+09 | 984.71 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.879686E+09 | 1346.05 | 26-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.929123E+09 | 1547.14 | 25-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.943007E+09 | 1443.59 | 21-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.940184E+09 | 1528.41 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.110005E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.846436E+09 | 911.74 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.990796E+09 | 1547.14 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.623338E+09 | 935.25 | 31-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.551823E+09 | 964.12 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.643085E+09 | 910.83 | 27-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.563518E+09 | 925.48 | 14-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.591863E+09 | 755.66 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.581920E+09 | 616.27 | 16-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.549329E+09 | 631.74 | 14-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.622240E+09 | 825.12 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.570757E+09 | 911.89 | 26-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.603609E+09 | 1014.66 | 25-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.614469E+09 | 984.27 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.613688E+09 | 997.43 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.712964E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.549329E+09 | 616.27 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.643085E+09 | 1014.66 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.988015E+09 | 1424.19 | 31-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.865095E+09 | 1478.90 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.997630E+09 | 1349.97 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.870333E+09 | 1392.70 | 14-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.910695E+09 | 964.82 | 23-MAY-07:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.895690E+09 | 837.28 | 01-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.845781E+09 | 933.43 | 14-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.959768E+09 | 970.02 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.880499E+09 | 1345.78 | 26-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.938386E+09 | 1557.27 | 25-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.973144E+09 | 1487.66 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.976895E+09 | 1543.58 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.111019E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.845781E+09 | 837.28 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.997630E+09 | 1557.27 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.627224E+09 | 850.15 | 31-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.551629E+09 | 909.66 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.638103E+09 | 792.50 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.559718E+09 | 853.35 | 14-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.589933E+09 | 602.98 | 23-MAY-07:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.581966E+09 | 539.58 | 01-JUN-07:10 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.547594E+09 | 539.58 | 03-JUL-07:10 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.619039E+09 | 598.74 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.566049E+09 | 787.48 | 26-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.600471E+09 | 974.77 | 25-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.620384E+09 | 969.29 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.621745E+09 | 975.97 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.712385E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.547594E+09 | 539.58 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.638103E+09 | 975.97 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.952126E+09 | 1375.86 | 31-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.846019E+09 | 1448.66 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.989751E+09 | 1333.44 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.872681E+09 | 1399.14 | 14-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.918880E+09 | 972.33 | 23-MAY-07:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.906033E+09 | 901.91 | 16-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.852925E+09 | 955.56 | 14-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.963650E+09 | 979.16 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.878830E+09 | 1340.83 | 26-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.928346E+09 | 1544.67 | 25-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.941801E+09 | 1440.17 | 21-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.939397E+09 | 1525.85 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.109904E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.846019E+09 | 901.91 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.989751E+09 | 1544.67 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.622349E+09 | 930.02 | 31-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.551048E+09 | 959.66 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.642067E+09 | 904.88 | 27-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.562681E+09 | 919.95 | 14-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.591083E+09 | 744.84 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.581339E+09 | 611.69 | 16-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.548596E+09 | 628.09 | 14-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.621449E+09 | 817.14 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.569840E+09 | 905.97 | 26-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.602742E+09 | 1011.51 | 25-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.613493E+09 | 980.37 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.612624E+09 | 993.86 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.711931E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.548596E+09 | 611.69 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.642067E+09 | 1011.51 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.987931E+09 | 1423.52 | 31-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.864975E+09 | 1478.33 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.997556E+09 | 1349.19 | 27-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.870307E+09 | 1391.96 | 14-APR-07:10 | 0.295395E+10 | 2160.55 | 03-APR-07:10 |
May | 0.910670E+09 | 964.57 | 23-MAY-07:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.895665E+09 | 837.28 | 01-JUN-07:10 | 0.306647E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.845748E+09 | 933.11 | 14-JUL-07:10 | 0.300922E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.959739E+09 | 969.78 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.880464E+09 | 1344.98 | 26-SEP-07:10 | 0.295395E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.938340E+09 | 1556.87 | 25-OCT-07:10 | 0.305979E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.973083E+09 | 1487.17 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.976761E+09 | 1543.13 | 12-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.111012E+11 | 0.363647E+11 | ||||
Minimum of Months | 0.845748E+09 | 837.28 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.997556E+09 | 1556.87 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.627189E+09 | 849.65 | 31-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.551612E+09 | 909.25 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.637984E+09 | 791.92 | 27-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.559680E+09 | 852.84 | 14-APR-07:10 | 0.190364E+10 | 1392.34 | 03-APR-07:10 |
May | 0.589907E+09 | 602.77 | 23-MAY-07:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.581944E+09 | 539.58 | 01-JUN-07:10 | 0.197615E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.547576E+09 | 539.58 | 03-JUL-07:10 | 0.193926E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.619005E+09 | 598.53 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.566030E+09 | 786.88 | 26-SEP-07:10 | 0.190364E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.600434E+09 | 974.47 | 25-OCT-07:10 | 0.197184E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.620358E+09 | 968.97 | 21-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.621695E+09 | 975.66 | 12-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.712341E+10 | 0.234348E+11 | ||||
Minimum of Months | 0.547576E+09 | 539.58 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.637984E+09 | 975.66 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.952116E+09 | 1375.12 | 31-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.845991E+09 | 1448.04 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.989707E+09 | 1332.63 | 27-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.872646E+09 | 1398.41 | 14-APR-07:10 | 0.295400E+10 | 2160.58 | 03-APR-07:10 |
May | 0.918816E+09 | 972.09 | 23-MAY-07:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.905976E+09 | 901.55 | 16-JUN-07:10 | 0.306652E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.852881E+09 | 955.30 | 14-JUL-07:10 | 0.300927E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.963589E+09 | 978.94 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.878797E+09 | 1340.03 | 26-SEP-07:10 | 0.295400E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.928316E+09 | 1544.24 | 25-OCT-07:10 | 0.305983E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.941780E+09 | 1439.57 | 21-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.939371E+09 | 1525.37 | 12-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.109900E+11 | 0.363653E+11 | ||||
Minimum of Months | 0.845991E+09 | 901.55 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.989707E+09 | 1544.24 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.622327E+09 | 929.62 | 31-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.551028E+09 | 959.30 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.642042E+09 | 904.43 | 27-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.562613E+09 | 919.52 | 14-APR-07:10 | 0.190363E+10 | 1392.33 | 03-APR-07:10 |
May | 0.591023E+09 | 744.20 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.581322E+09 | 611.54 | 16-JUN-07:10 | 0.197614E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.548556E+09 | 627.95 | 14-JUL-07:10 | 0.193924E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.621426E+09 | 816.72 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.569814E+09 | 905.52 | 26-SEP-07:10 | 0.190363E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.602697E+09 | 1011.26 | 25-OCT-07:10 | 0.197183E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.613454E+09 | 980.08 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.612574E+09 | 993.57 | 12-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.711888E+10 | 0.234347E+11 | ||||
Minimum of Months | 0.548556E+09 | 611.54 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.642042E+09 | 1011.26 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.422891E+10 | 4400.15 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.383579E+10 | 4400.15 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.455537E+10 | 4400.15 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.407153E+10 | 4400.15 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.439214E+10 | 4400.15 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.436992E+10 | 4400.15 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.409376E+10 | 4400.15 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.455537E+10 | 4400.15 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.407153E+10 | 4400.15 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.422891E+10 | 4400.15 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.417862E+10 | 4400.15 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.409376E+10 | 4400.15 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.506756E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.383579E+10 | 4400.15 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.455537E+10 | 4400.15 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195358E+09 | 203.27 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.177198E+09 | 203.27 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.210439E+09 | 203.27 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.188088E+09 | 203.27 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.202899E+09 | 203.27 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.201872E+09 | 203.27 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.189115E+09 | 203.27 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.210439E+09 | 203.27 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.188088E+09 | 203.27 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.195358E+09 | 203.27 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.193035E+09 | 203.27 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.189115E+09 | 203.27 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.177198E+09 | 203.27 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.210439E+09 | 203.27 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195358E+09 | 203.27 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.177198E+09 | 203.27 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.210439E+09 | 203.27 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.188088E+09 | 203.27 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.202899E+09 | 203.27 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.201872E+09 | 203.27 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.189115E+09 | 203.27 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.210439E+09 | 203.27 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.188088E+09 | 203.27 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.195358E+09 | 203.27 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.193035E+09 | 203.27 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.189115E+09 | 203.27 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.177198E+09 | 203.27 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.210439E+09 | 203.27 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195358E+09 | 203.27 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.177198E+09 | 203.27 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.210439E+09 | 203.27 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.188088E+09 | 203.27 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.202899E+09 | 203.27 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.201872E+09 | 203.27 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.189115E+09 | 203.27 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.210439E+09 | 203.27 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.188088E+09 | 203.27 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.195358E+09 | 203.27 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.193035E+09 | 203.27 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.189115E+09 | 203.27 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.177198E+09 | 203.27 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.210439E+09 | 203.27 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.146017E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.132465E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.157676E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.140562E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.151846E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.151213E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.141196E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.157673E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.140562E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.146020E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.144381E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.141198E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.175081E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.132465E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.157676E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.131134E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.141604E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.126235E+11 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.136369E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.135800E+11 | 0.244214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.126804E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.141602E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.126235E+11 | 0.235253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.131136E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.129664E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.126806E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.157235E+12 | 0.289609E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.141604E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.131134E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.141604E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.126235E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.136369E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.135800E+11 | 0.244213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.126804E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.141602E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.126235E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.131136E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.129664E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.126806E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.157235E+12 | 0.289607E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.141604E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.131134E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.141604E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.126235E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.136369E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.135800E+11 | 0.244213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.126804E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.141602E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.126235E+11 | 0.235252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.131136E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.129664E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.126806E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.157235E+12 | 0.289607E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.118963E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.141604E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.991545E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 966606.58 | 0.387841E+09 |
February | 0.136985E+10 | 0.867260E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1977753.11 | 0.301497E+09 |
March | 0.163685E+10 | 0.999679E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6241309.45 | 0.313815E+09 |
April | 0.145243E+10 | 0.871283E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13747142.17 | 0.129831E+09 |
May | 0.157338E+10 | 0.911467E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57809534.04 | 18902300.15 |
June | 0.156900E+10 | 0.896938E+09 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55202594.91 | 11164412.75 |
July | 0.145680E+10 | 0.846297E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81278592.56 | 1589338.09 |
August | 0.163685E+10 | 0.960531E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78101614.05 | 10083027.47 |
September | 0.145243E+10 | 0.881821E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64883500.97 | 32027762.81 |
October | 0.150991E+10 | 0.939841E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53580559.98 | 0.109762E+09 |
November | 0.149516E+10 | 0.976267E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5360024.16 | 0.198982E+09 |
December | 0.145680E+10 | 0.980296E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3516858.02 | 0.352265E+09 |
Annual Sum or Average | 0.181194E+11 | 0.111232E+11 | 0.363647E+11 | 0.422666E+09 | 0.186776E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.846297E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 966606.58 | 1589338.09 |
Maximum of Months | 0.163685E+10 | 0.999679E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81278592.56 | 0.387841E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.628303E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 523726.77 | 0.261868E+09 |
February | 0.882782E+09 | 0.552649E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1158365.06 | 0.201977E+09 |
March | 0.105485E+10 | 0.638825E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3559385.96 | 0.206499E+09 |
April | 0.936002E+09 | 0.560213E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8821447.75 | 84521163.81 |
May | 0.101394E+10 | 0.590453E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36173574.34 | 12703746.14 |
June | 0.101113E+10 | 0.582368E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35889252.42 | 6923339.91 |
July | 0.938820E+09 | 0.548131E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53547731.16 | 978577.24 |
August | 0.105485E+10 | 0.619454E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53152132.44 | 5146736.78 |
September | 0.936002E+09 | 0.566676E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40097558.96 | 20926802.40 |
October | 0.973041E+09 | 0.601112E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32959284.83 | 72264353.70 |
November | 0.963541E+09 | 0.621421E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3203004.41 | 0.131756E+09 |
December | 0.938820E+09 | 0.622985E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2135849.17 | 0.227343E+09 |
Annual Sum or Average | 0.116768E+11 | 0.713259E+10 | 0.234348E+11 | 0.271221E+09 | 0.123291E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.548131E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 523726.77 | 978577.24 |
Maximum of Months | 0.105485E+10 | 0.638825E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53547731.16 | 0.261868E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.952596E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 455541.54 | 0.412204E+09 |
February | 0.136988E+10 | 0.846436E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1339611.89 | 0.316167E+09 |
March | 0.163688E+10 | 0.990796E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4853769.24 | 0.315253E+09 |
April | 0.145246E+10 | 0.873562E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12842116.26 | 0.131186E+09 |
May | 0.157341E+10 | 0.919852E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57546145.28 | 18719141.93 |
June | 0.156904E+10 | 0.907015E+09 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55178167.61 | 10990847.98 |
July | 0.145684E+10 | 0.853715E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80205764.52 | 1700142.05 |
August | 0.163688E+10 | 0.964511E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76185370.04 | 10648022.53 |
September | 0.145246E+10 | 0.879686E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60483508.12 | 34303887.02 |
October | 0.150994E+10 | 0.929123E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43731311.82 | 0.122632E+09 |
November | 0.149520E+10 | 0.943007E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3700378.95 | 0.214726E+09 |
December | 0.145684E+10 | 0.940184E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2344937.95 | 0.371154E+09 |
Annual Sum or Average | 0.181198E+11 | 0.110005E+11 | 0.363653E+11 | 0.398867E+09 | 0.195968E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.846436E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 455541.54 | 1700142.05 |
Maximum of Months | 0.163688E+10 | 0.990796E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80205764.52 | 0.412204E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.623338E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 457239.46 | 0.284029E+09 |
February | 0.882782E+09 | 0.551823E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1039109.86 | 0.226377E+09 |
March | 0.105485E+10 | 0.643085E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3161334.10 | 0.244026E+09 |
April | 0.936002E+09 | 0.563518E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7028090.17 | 0.115554E+09 |
May | 0.101394E+10 | 0.591863E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32858975.28 | 22136308.44 |
June | 0.101113E+10 | 0.581920E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30024320.71 | 15669373.07 |
July | 0.938820E+09 | 0.549329E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39948763.11 | 7383801.28 |
August | 0.105485E+10 | 0.622240E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40479555.85 | 21636675.82 |
September | 0.936002E+09 | 0.570757E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36158953.32 | 32830255.59 |
October | 0.973041E+09 | 0.603609E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28256390.16 | 99575560.83 |
November | 0.963541E+09 | 0.614469E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2825660.23 | 0.158258E+09 |
December | 0.938820E+09 | 0.613688E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1823034.95 | 0.279215E+09 |
Annual Sum or Average | 0.116768E+11 | 0.712964E+10 | 0.234347E+11 | 0.224061E+09 | 0.150669E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.549329E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 457239.46 | 7383801.28 |
Maximum of Months | 0.105485E+10 | 0.643085E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40479555.85 | 0.284029E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.988015E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4893834.43 | 0.743389E+09 |
February | 0.136985E+10 | 0.865095E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6150580.03 | 0.571556E+09 |
March | 0.163685E+10 | 0.997630E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17951530.41 | 0.611862E+09 |
April | 0.145243E+10 | 0.870333E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30365459.57 | 0.273247E+09 |
May | 0.157338E+10 | 0.910695E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125082E+09 | 42654086.01 |
June | 0.156900E+10 | 0.895690E+09 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114436E+09 | 32819078.40 |
July | 0.145680E+10 | 0.845781E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160864E+09 | 12401146.28 |
August | 0.163685E+10 | 0.959768E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154173E+09 | 42395138.85 |
September | 0.145243E+10 | 0.880499E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144925E+09 | 66979087.25 |
October | 0.150991E+10 | 0.938386E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116462E+09 | 0.229934E+09 |
November | 0.149516E+10 | 0.973144E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15486358.71 | 0.384158E+09 |
December | 0.145680E+10 | 0.976895E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10423506.39 | 0.666768E+09 |
Annual Sum or Average | 0.181194E+11 | 0.111019E+11 | 0.363647E+11 | 0.901213E+09 | 0.367816E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.845781E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4893834.43 | 12401146.28 |
Maximum of Months | 0.163685E+10 | 0.997630E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160864E+09 | 0.743389E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.627224E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1271695.64 | 0.537427E+09 |
February | 0.649041E+09 | 0.551629E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2386374.36 | 0.413772E+09 |
March | 0.773965E+09 | 0.638103E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7164735.18 | 0.440422E+09 |
April | 0.688021E+09 | 0.559718E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16887890.91 | 0.202327E+09 |
May | 0.744847E+09 | 0.589933E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73793870.52 | 34169909.85 |
June | 0.742030E+09 | 0.581966E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70268104.23 | 25033571.46 |
July | 0.690839E+09 | 0.547594E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96205676.27 | 11389888.19 |
August | 0.773965E+09 | 0.619039E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95084608.79 | 32081361.15 |
September | 0.688021E+09 | 0.566049E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83887975.93 | 50971165.25 |
October | 0.715730E+09 | 0.600471E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65334799.67 | 0.170479E+09 |
November | 0.708685E+09 | 0.620384E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6578596.17 | 0.282337E+09 |
December | 0.690839E+09 | 0.621745E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4395755.05 | 0.473195E+09 |
Annual Sum or Average | 0.858171E+10 | 0.712385E+10 | 0.234348E+11 | 0.523260E+09 | 0.267360E+10 | ||||
Minimum of Months | 0.649041E+09 | 0.547594E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1271695.64 | 11389888.19 |
Maximum of Months | 0.773965E+09 | 0.638103E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96205676.27 | 0.537427E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.952126E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 818125.03 | 0.896154E+09 |
February | 0.136988E+10 | 0.846019E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2390266.89 | 0.676179E+09 |
March | 0.163688E+10 | 0.989751E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10487138.16 | 0.662255E+09 |
April | 0.145246E+10 | 0.872681E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27913248.78 | 0.291471E+09 |
May | 0.157341E+10 | 0.918880E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124856E+09 | 43679138.72 |
June | 0.156904E+10 | 0.906033E+09 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115890E+09 | 32068753.79 |
July | 0.145684E+10 | 0.852925E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161240E+09 | 12654585.81 |
August | 0.163688E+10 | 0.963650E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150426E+09 | 45155797.46 |
September | 0.145246E+10 | 0.878830E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130678E+09 | 78176815.22 |
October | 0.150994E+10 | 0.928346E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90464430.64 | 0.290120E+09 |
November | 0.149520E+10 | 0.941801E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7267932.05 | 0.469566E+09 |
December | 0.145684E+10 | 0.939397E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4518562.66 | 0.801310E+09 |
Annual Sum or Average | 0.181198E+11 | 0.109904E+11 | 0.363653E+11 | 0.826949E+09 | 0.429879E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.846019E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 818125.03 | 12654585.81 |
Maximum of Months | 0.163688E+10 | 0.989751E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161240E+09 | 0.896154E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.622349E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1532605.77 | 0.553257E+09 |
February | 0.882782E+09 | 0.551048E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2730478.84 | 0.425649E+09 |
March | 0.105485E+10 | 0.642067E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8697727.94 | 0.453641E+09 |
April | 0.936002E+09 | 0.562681E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15953825.66 | 0.222008E+09 |
May | 0.101394E+10 | 0.591083E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75590854.80 | 40726920.36 |
June | 0.101113E+10 | 0.581339E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68198057.21 | 32269816.37 |
July | 0.938820E+09 | 0.548596E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92211102.65 | 17103988.44 |
August | 0.105485E+10 | 0.621449E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93026206.58 | 43180781.42 |
September | 0.936002E+09 | 0.569840E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82183223.27 | 61563185.33 |
October | 0.973041E+09 | 0.602742E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65967250.76 | 0.192720E+09 |
November | 0.963541E+09 | 0.613493E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7489139.90 | 0.291555E+09 |
December | 0.938820E+09 | 0.612624E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4910747.36 | 0.501680E+09 |
Annual Sum or Average | 0.116768E+11 | 0.711931E+10 | 0.234347E+11 | 0.518491E+09 | 0.283536E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.548596E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1532605.77 | 17103988.44 |
Maximum of Months | 0.105485E+10 | 0.642067E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93026206.58 | 0.553257E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.987931E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7743349.10 | 0.835608E+09 |
February | 0.136985E+10 | 0.864975E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8310521.17 | 0.640543E+09 |
March | 0.163685E+10 | 0.997556E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20424480.89 | 0.709928E+09 |
April | 0.145243E+10 | 0.870307E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33849136.55 | 0.330113E+09 |
May | 0.157338E+10 | 0.910670E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143996E+09 | 58981107.17 |
June | 0.156900E+10 | 0.895665E+09 | 0.306647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131974E+09 | 45416309.13 |
July | 0.145680E+10 | 0.845748E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180317E+09 | 20126222.37 |
August | 0.163685E+10 | 0.959739E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180061E+09 | 57367584.97 |
September | 0.145243E+10 | 0.880464E+09 | 0.295395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164274E+09 | 88280163.29 |
October | 0.150991E+10 | 0.938340E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132003E+09 | 0.275459E+09 |
November | 0.149516E+10 | 0.973083E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19353655.82 | 0.436338E+09 |
December | 0.145680E+10 | 0.976761E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13699050.44 | 0.755616E+09 |
Annual Sum or Average | 0.181194E+11 | 0.111012E+11 | 0.363647E+11 | 0.103600E+10 | 0.425378E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.845748E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7743349.10 | 20126222.37 |
Maximum of Months | 0.163685E+10 | 0.997556E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180317E+09 | 0.835608E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.627189E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2249832.29 | 0.599277E+09 |
February | 0.882782E+09 | 0.551612E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3460194.32 | 0.460979E+09 |
March | 0.105485E+10 | 0.637984E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8661272.03 | 0.512225E+09 |
April | 0.936002E+09 | 0.559680E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20133467.69 | 0.244560E+09 |
May | 0.101394E+10 | 0.589907E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88668907.41 | 45694530.84 |
June | 0.101113E+10 | 0.581944E+09 | 0.197615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84200132.72 | 33810699.10 |
July | 0.938820E+09 | 0.547576E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112886E+09 | 16979201.19 |
August | 0.105485E+10 | 0.619005E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114779E+09 | 42301023.06 |
September | 0.936002E+09 | 0.566030E+09 | 0.190364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100111E+09 | 65703198.94 |
October | 0.973041E+09 | 0.600434E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78302842.08 | 0.203761E+09 |
November | 0.963541E+09 | 0.620358E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8334529.31 | 0.323777E+09 |
December | 0.938820E+09 | 0.621695E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5767201.31 | 0.532970E+09 |
Annual Sum or Average | 0.116768E+11 | 0.712341E+10 | 0.234348E+11 | 0.627554E+09 | 0.308204E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.547576E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2249832.29 | 16979201.19 |
Maximum of Months | 0.105485E+10 | 0.637984E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114779E+09 | 0.599277E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.952116E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 978617.58 | 0.102753E+10 |
February | 0.136988E+10 | 0.845991E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3195100.20 | 0.766196E+09 |
March | 0.163688E+10 | 0.989707E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12181597.55 | 0.772692E+09 |
April | 0.145246E+10 | 0.872646E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31339525.30 | 0.352584E+09 |
May | 0.157341E+10 | 0.918816E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143986E+09 | 60202739.04 |
June | 0.156904E+10 | 0.905976E+09 | 0.306652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133511E+09 | 44478308.07 |
July | 0.145684E+10 | 0.852881E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181213E+09 | 20417419.77 |
August | 0.163688E+10 | 0.963589E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177121E+09 | 60675919.49 |
September | 0.145246E+10 | 0.878797E+09 | 0.295400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152521E+09 | 0.101517E+09 |
October | 0.150994E+10 | 0.928316E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108454E+09 | 0.350490E+09 |
November | 0.149520E+10 | 0.941780E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9423863.58 | 0.548051E+09 |
December | 0.145684E+10 | 0.939371E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5974689.21 | 0.921523E+09 |
Annual Sum or Average | 0.181198E+11 | 0.109900E+11 | 0.363653E+11 | 0.959899E+09 | 0.502636E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.845991E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 978617.58 | 20417419.77 |
Maximum of Months | 0.163688E+10 | 0.989707E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181213E+09 | 0.102753E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.622327E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2121911.22 | 0.637557E+09 |
February | 0.882782E+09 | 0.551028E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3286990.06 | 0.487665E+09 |
March | 0.105485E+10 | 0.642042E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10107960.27 | 0.534111E+09 |
April | 0.936002E+09 | 0.562613E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18763691.24 | 0.269429E+09 |
May | 0.101394E+10 | 0.591023E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89349937.51 | 53629001.37 |
June | 0.101113E+10 | 0.581322E+09 | 0.197614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81444538.05 | 42468624.52 |
July | 0.938820E+09 | 0.548556E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108809E+09 | 24041218.16 |
August | 0.105485E+10 | 0.621426E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111295E+09 | 55798334.40 |
September | 0.936002E+09 | 0.569814E+09 | 0.190363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97601377.85 | 78401467.04 |
October | 0.973041E+09 | 0.602697E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77836445.09 | 0.233041E+09 |
November | 0.963541E+09 | 0.613454E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9045726.34 | 0.339649E+09 |
December | 0.938820E+09 | 0.612574E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6014722.41 | 0.580061E+09 |
Annual Sum or Average | 0.116768E+11 | 0.711888E+10 | 0.234347E+11 | 0.615678E+09 | 0.333585E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.548556E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2121911.22 | 24041218.16 |
Maximum of Months | 0.105485E+10 | 0.642042E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111295E+09 | 0.637557E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.422891E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.383579E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.455537E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.407153E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.439214E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.436992E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.409376E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.455537E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.407153E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.422891E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.417862E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.409376E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.506756E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.383579E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.455537E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.195358E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.177198E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.210439E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.188088E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.202899E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.201872E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.189115E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.188088E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.195358E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.193035E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.189115E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.177198E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.195358E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.177198E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.210439E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.188088E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.202899E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.201872E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.189115E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.188088E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.195358E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.193035E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.189115E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.177198E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.195358E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.177198E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.210439E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.188088E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.202899E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.201872E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.189115E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.188088E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.195358E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.193035E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.189115E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234100E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.177198E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.210439E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657007.99 | 0.833273E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2000686.37 | 0.645139E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8375544.64 | 0.664002E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20273111.61 | 0.284226E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97618855.40 | 34885745.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91943492.13 | 26237256.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140273E+09 | 6410954.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127495E+09 | 32581181.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110415E+09 | 66487693.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85444991.75 | 0.244809E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6926552.83 | 0.430587E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4540250.11 | 0.754571E+09 |
Annual Sum or Average | 0.695963E+09 | 0.402321E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657007.99 | 6410954.57 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140273E+09 | 0.833273E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2723243.85 | 0.139252E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5156382.81 | 0.107571E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20275902.59 | 0.111116E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38092530.87 | 0.486302E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180265E+09 | 58073221.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165170E+09 | 47613277.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250961E+09 | 13899274.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225653E+09 | 65243410.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209821E+09 | 0.107858E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155906E+09 | 0.417303E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14646914.79 | 0.722296E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9683720.92 | 0.124828E+10 |
Annual Sum or Average | 0.127836E+10 | 0.674625E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2723243.85 | 13899274.12 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250961E+09 | 0.139252E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1461579.54 | 0.138216E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1917438.48 | 0.106957E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9764707.03 | 0.116870E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23069818.89 | 0.549643E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153190E+09 | 73303194.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145949E+09 | 57572015.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214450E+09 | 22574809.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209698E+09 | 79129369.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191471E+09 | 0.124094E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122113E+09 | 0.445300E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10016121.08 | 0.731135E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6819980.81 | 0.124843E+10 |
Annual Sum or Average | 0.108992E+10 | 0.695162E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1461579.54 | 22574809.64 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214450E+09 | 0.138216E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 15605.75 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 15605.75 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 15605.75 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 15605.75 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 15605.75 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 15605.75 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 15605.75 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 15605.75 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 15605.75 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 15605.75 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 15605.75 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 15605.75 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 15605.75 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 15605.75 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 14015.06 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 14015.06 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 14015.06 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 14015.06 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 14015.06 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 14015.06 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 14015.06 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 14015.06 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 14015.06 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 14015.06 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 14015.06 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 14015.06 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 14015.06 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 14015.06 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 14015.06 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 14015.06 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 14015.06 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 14015.06 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 14015.06 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 14015.06 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 14015.06 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 14015.06 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 14015.06 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 14015.06 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 14015.06 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 14015.06 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 14015.06 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 14015.06 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 14015.06 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 14015.06 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 14015.06 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 14015.06 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 14015.06 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 14015.06 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 14015.06 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 14015.06 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 14015.06 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 14015.06 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 14015.06 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 14015.06 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 14015.06 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 14015.06 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1428.41 | 31-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 16-JAN-15:00 | 736.03 | 09-JAN-04:51 |
February | 2010.79 | 01-FEB-10:09 | 1482.30 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 | 02-FEB-13:00 | 1019.38 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 1354.96 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.15 | 05-MAR-12:57 | 869.98 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1397.05 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.76 | 29-APR-17:01 | 525.08 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 971.14 | 23-MAY-07:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.51 | 21-MAY-14:00 | 106.11 | 14-MAY-12:00 |
June | 2010.79 | 01-JUN-09:09 | 837.28 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.80 | 10-JUN-17:02 | 153.76 | 06-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 941.35 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.09 | 22-JUL-18:50 | 84.31 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 975.99 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.71 | 20-AUG-14:00 | 193.77 | 25-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1350.95 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.96 | 09-SEP-22:53 | 204.75 | 05-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1559.68 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 395.40 | 09-OCT-13:51 | 430.45 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1491.27 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.62 | 05-NOV-13:10 | 619.32 | 12-NOV-08:00 |
December | 2010.79 | 01-DEC-10:09 | 1546.07 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.79 | 10-DEC-15:10 | 948.56 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 44.64 | 84.31 | |||||
Maximum of Months | 2010.79 | 1559.68 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 395.40 | 1019.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 856.72 | 31-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 | 16-JAN-15:00 | 493.31 | 22-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 914.96 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 | 02-FEB-13:00 | 733.68 | 05-FEB-10:00 |
March | 1295.83 | 01-MAR-10:09 | 798.98 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.24 | 26-MAR-14:00 | 565.07 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 858.96 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.46 | 29-APR-17:01 | 333.49 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 607.56 | 30-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.51 | 21-MAY-14:00 | 96.72 | 14-MAY-12:00 |
June | 1295.83 | 01-JUN-09:09 | 539.58 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.21 | 10-JUN-17:02 | 94.97 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 539.58 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.11 | 22-JUL-18:50 | 92.71 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 603.11 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.66 | 20-AUG-13:55 | 119.40 | 25-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 793.48 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 224.25 | 09-SEP-22:53 | 136.22 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 978.27 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.89 | 09-OCT-13:41 | 278.85 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 973.50 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.05 | 05-NOV-13:10 | 474.47 | 12-NOV-08:10 |
December | 1295.83 | 01-DEC-10:09 | 979.75 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.25 | 10-DEC-15:10 | 603.57 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 | 92.71 | |||||
Maximum of Months | 1295.83 | 979.75 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 245.89 | 733.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1380.38 | 31-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 31-JAN-14:30 | 722.85 | 26-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1452.25 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.29 | 02-FEB-13:00 | 998.65 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 1338.52 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 72.25 | 26-MAR-13:53 | 869.87 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1403.46 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.34 | 29-APR-17:01 | 524.83 | 01-APR-21:00 |
May | 2010.83 | 01-MAY-09:09 | 978.30 | 23-MAY-07:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.21 | 21-MAY-14:00 | 110.23 | 14-MAY-12:00 |
June | 2010.83 | 01-JUN-09:09 | 911.74 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.92 | 10-JUN-17:02 | 152.05 | 06-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 962.43 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.25 | 22-JUL-18:50 | 91.46 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 984.71 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.08 | 20-AUG-13:55 | 194.95 | 25-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1346.05 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 328.48 | 09-SEP-22:53 | 213.21 | 05-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1547.14 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.92 | 09-OCT-13:41 | 438.91 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1443.59 | 21-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 | 28-NOV-13:00 | 664.19 | 12-NOV-08:10 |
December | 2010.83 | 01-DEC-10:09 | 1528.41 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.45 | 16-DEC-15:00 | 922.03 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 911.74 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | 91.46 | |||||
Maximum of Months | 2010.83 | 1547.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 340.92 | 998.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 935.25 | 31-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 19-JAN-12:05 | 508.17 | 26-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 964.12 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 | 02-FEB-13:00 | 711.28 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 910.83 | 27-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.71 | 26-MAR-13:53 | 639.87 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 925.48 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.03 | 29-APR-17:10 | 432.77 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 755.66 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.09 | 07-MAY-14:08 | 91.19 | 14-MAY-12:00 |
June | 1295.83 | 01-JUN-09:09 | 616.27 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.21 | 10-JUN-17:07 | 142.54 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 631.74 | 14-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.48 | 02-JUL-11:08 | 103.58 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 825.12 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.25 | 20-AUG-13:55 | 183.45 | 25-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 911.89 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.57 | 09-SEP-17:07 | 162.98 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1014.66 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.47 | 09-OCT-14:04 | 330.92 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 984.27 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.54 | 07-NOV-13:00 | 451.11 | 12-NOV-08:00 |
December | 1295.83 | 01-DEC-10:09 | 997.43 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.87 | 13-DEC-14:00 | 713.68 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 616.27 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 91.19 | |||||
Maximum of Months | 1295.83 | 1014.66 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 232.47 | 713.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1424.19 | 31-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.81 | 16-JAN-15:00 | 1424.60 | 21-JAN-05:51 |
February | 2010.79 | 01-FEB-10:09 | 1478.90 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 193.17 | 20-FEB-14:53 | 1959.95 | 05-FEB-07:53 |
March | 2010.79 | 01-MAR-10:09 | 1349.97 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 328.24 | 05-MAR-12:53 | 1732.84 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1392.70 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 402.80 | 29-APR-17:01 | 999.20 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 964.82 | 23-MAY-07:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 544.30 | 07-MAY-13:53 | 192.25 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 837.28 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 660.58 | 10-JUN-17:02 | 296.58 | 06-JUN-21:20 |
July | 2010.79 | 03-JUL-09:09 | 933.43 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 593.72 | 22-JUL-18:50 | 169.86 | 31-JUL-02:25 |
August | 2010.79 | 01-AUG-09:09 | 970.02 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 747.78 | 20-AUG-14:00 | 440.66 | 25-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1345.78 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 763.49 | 09-SEP-17:02 | 409.96 | 05-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1557.27 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 867.95 | 09-OCT-14:00 | 814.15 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1487.66 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.16 | 05-NOV-12:52 | 1219.58 | 12-NOV-06:55 |
December | 2010.79 | 01-DEC-10:09 | 1543.58 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 191.58 | 10-DEC-15:10 | 1775.76 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 182.81 | 169.86 | |||||
Maximum of Months | 2010.79 | 1557.27 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 867.95 | 1959.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 850.15 | 31-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.44 | 16-JAN-15:00 | 947.88 | 21-JAN-05:51 |
February | 1239.33 | 01-FEB-08:09 | 909.66 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.99 | 20-FEB-14:53 | 1454.75 | 05-FEB-10:00 |
March | 1239.33 | 01-MAR-08:09 | 792.50 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 125.76 | 05-MAR-13:00 | 1181.25 | 20-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 853.35 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.68 | 29-APR-17:01 | 699.42 | 01-APR-17:53 |
May | 1239.33 | 01-MAY-07:10 | 602.98 | 23-MAY-07:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.46 | 07-MAY-13:53 | 196.71 | 14-MAY-11:55 |
June | 1239.33 | 01-JUN-07:10 | 539.58 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.56 | 10-JUN-17:02 | 228.91 | 18-JUN-13:53 |
July | 1239.33 | 03-JUL-07:10 | 539.58 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.79 | 22-JUL-18:50 | 202.83 | 30-JUL-11:10 |
August | 1239.33 | 01-AUG-07:10 | 598.74 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 483.60 | 20-AUG-13:55 | 302.61 | 25-AUG-23:53 |
September | 1239.33 | 01-SEP-07:10 | 787.48 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 497.27 | 09-SEP-17:02 | 295.82 | 05-SEP-03:00 |
October | 1239.33 | 02-OCT-07:10 | 974.77 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 576.29 | 09-OCT-13:53 | 563.45 | 29-OCT-02:00 |
November | 1239.33 | 01-NOV-07:10 | 969.29 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.90 | 05-NOV-13:00 | 994.45 | 12-NOV-09:00 |
December | 1239.33 | 01-DEC-08:09 | 975.97 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.46 | 10-DEC-15:10 | 1196.79 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 77.90 | 196.71 | |||||
Maximum of Months | 1239.33 | 975.97 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 576.29 | 1454.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1375.86 | 31-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.11 | 31-JAN-14:30 | 1617.89 | 22-JAN-16:55 |
February | 2010.83 | 01-FEB-10:09 | 1448.66 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.48 | 02-FEB-13:00 | 2058.55 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 1333.44 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.70 | 26-MAR-13:57 | 1795.36 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1399.14 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.22 | 29-APR-17:01 | 1063.83 | 01-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 972.33 | 23-MAY-07:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 531.35 | 07-MAY-13:53 | 197.94 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 901.91 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.04 | 10-JUN-17:02 | 297.74 | 06-JUN-21:20 |
July | 2010.83 | 03-JUL-09:09 | 955.56 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 602.72 | 22-JUL-18:50 | 176.82 | 31-JUL-02:25 |
August | 2010.83 | 01-AUG-09:09 | 979.16 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 726.53 | 20-AUG-13:55 | 450.14 | 25-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1340.83 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 733.31 | 09-SEP-17:02 | 445.94 | 05-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1544.67 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.03 | 09-OCT-13:57 | 925.11 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1440.17 | 21-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.74 | 28-NOV-13:00 | 1436.54 | 12-NOV-10:50 |
December | 2010.83 | 01-DEC-10:09 | 1525.85 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.98 | 13-DEC-14:00 | 1848.92 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 901.91 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 23.11 | 176.82 | |||||
Maximum of Months | 2010.83 | 1544.67 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 780.03 | 2058.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 930.02 | 31-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.62 | 16-JAN-13:13 | 984.46 | 22-JAN-16:55 |
February | 1295.83 | 01-FEB-10:09 | 959.66 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.96 | 02-FEB-13:00 | 1334.56 | 05-FEB-07:53 |
March | 1295.83 | 01-MAR-10:09 | 904.88 | 27-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.11 | 05-MAR-12:53 | 1235.69 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 919.95 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.09 | 29-APR-16:00 | 809.21 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 744.84 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.78 | 07-MAY-13:53 | 189.51 | 06-MAY-19:55 |
June | 1295.83 | 01-JUN-09:09 | 611.69 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.31 | 10-JUN-17:07 | 240.05 | 18-JUN-13:53 |
July | 1295.83 | 03-JUL-09:09 | 628.09 | 14-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.08 | 02-JUL-11:40 | 168.43 | 31-JUL-01:55 |
August | 1295.83 | 01-AUG-09:09 | 817.14 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 483.44 | 20-AUG-13:55 | 333.25 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 905.97 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 443.33 | 09-SEP-17:10 | 317.53 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1011.51 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 537.18 | 09-OCT-13:53 | 608.97 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 980.37 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.02 | 05-NOV-12:52 | 858.46 | 12-NOV-06:55 |
December | 1295.83 | 01-DEC-10:09 | 993.86 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.89 | 10-DEC-11:10 | 1238.93 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 611.69 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 60.62 | 168.43 | |||||
Maximum of Months | 1295.83 | 1011.51 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 537.18 | 1334.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1423.52 | 31-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 239.84 | 15-JAN-14:00 | 1789.06 | 21-JAN-05:58 |
February | 2010.79 | 01-FEB-10:09 | 1478.33 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 290.26 | 20-FEB-14:53 | 2250.02 | 05-FEB-07:50 |
March | 2010.79 | 01-MAR-10:09 | 1349.19 | 27-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 401.43 | 05-MAR-12:43 | 2036.96 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1391.96 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.70 | 29-APR-17:01 | 1232.66 | 01-APR-17:53 |
May | 2010.79 | 01-MAY-09:09 | 964.57 | 23-MAY-07:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 606.78 | 07-MAY-13:53 | 245.51 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 837.28 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 753.42 | 10-JUN-17:02 | 378.09 | 06-JUN-21:20 |
July | 2010.79 | 03-JUL-09:09 | 933.11 | 14-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 624.56 | 22-JUL-18:50 | 244.71 | 31-JUL-02:61 |
August | 2010.79 | 01-AUG-09:09 | 969.78 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 886.77 | 20-AUG-13:55 | 535.46 | 25-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1344.98 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 900.40 | 09-SEP-17:02 | 544.87 | 05-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1556.87 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 977.96 | 09-OCT-13:54 | 874.88 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1487.17 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.76 | 05-NOV-13:00 | 1425.25 | 12-NOV-06:55 |
December | 2010.79 | 01-DEC-10:09 | 1543.13 | 12-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 231.12 | 10-DEC-11:00 | 1937.45 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 231.12 | 244.71 | |||||
Maximum of Months | 2010.79 | 1556.87 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 977.96 | 2250.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 849.65 | 31-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.34 | 16-JAN-15:00 | 1192.87 | 21-JAN-05:53 |
February | 1295.83 | 01-FEB-10:09 | 909.25 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 138.39 | 20-FEB-14:53 | 1531.74 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 791.92 | 27-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.57 | 26-MAR-14:00 | 1395.57 | 20-MAR-21:25 |
April | 1295.83 | 03-APR-09:09 | 852.84 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.11 | 29-APR-17:01 | 859.43 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 602.77 | 23-MAY-07:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.15 | 07-MAY-13:53 | 259.11 | 14-MAY-12:10 |
June | 1295.83 | 01-JUN-09:09 | 539.58 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 487.92 | 10-JUN-17:02 | 271.40 | 11-JUN-08:00 |
July | 1295.83 | 03-JUL-09:09 | 539.58 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 393.34 | 16-JUL-15:16 | 275.87 | 30-JUL-11:10 |
August | 1295.83 | 01-AUG-09:09 | 598.53 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 591.64 | 20-AUG-13:55 | 366.30 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 786.88 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 589.31 | 09-SEP-17:02 | 384.52 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 974.47 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 665.75 | 09-OCT-13:53 | 606.59 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 968.97 | 21-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.42 | 05-NOV-13:00 | 1158.15 | 12-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 975.66 | 12-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.79 | 10-DEC-15:00 | 1298.10 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 97.42 | 259.11 | |||||
Maximum of Months | 1295.83 | 975.66 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 665.75 | 1531.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1375.12 | 31-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.19 | 31-JAN-14:30 | 1876.79 | 22-JAN-16:55 |
February | 2010.83 | 01-FEB-10:09 | 1448.04 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 131.33 | 02-FEB-13:00 | 2266.49 | 05-FEB-07:53 |
March | 2010.83 | 01-MAR-10:09 | 1332.63 | 27-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 218.04 | 26-MAR-14:00 | 2120.85 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1398.41 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.82 | 29-APR-17:01 | 1313.36 | 01-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 972.09 | 23-MAY-07:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 598.26 | 07-MAY-13:53 | 252.33 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 901.55 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 764.22 | 10-JUN-17:02 | 380.01 | 06-JUN-21:20 |
July | 2010.83 | 03-JUL-09:09 | 955.30 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 636.47 | 22-JUL-18:50 | 251.81 | 31-JUL-02:61 |
August | 2010.83 | 01-AUG-09:09 | 978.94 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 887.03 | 20-AUG-13:55 | 547.07 | 25-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1340.03 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 864.39 | 09-SEP-17:02 | 581.20 | 05-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1544.24 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 943.30 | 09-OCT-13:56 | 1020.84 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1439.57 | 21-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.43 | 28-NOV-13:00 | 1818.37 | 12-NOV-10:59 |
December | 2010.83 | 01-DEC-10:09 | 1525.37 | 12-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.45 | 13-DEC-14:00 | 2004.99 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 901.55 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 25.19 | 251.81 | |||||
Maximum of Months | 2010.83 | 1544.24 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 943.30 | 2266.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 929.62 | 31-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.67 | 16-JAN-13:13 | 1192.71 | 21-JAN-05:59 |
February | 1295.83 | 01-FEB-10:09 | 959.30 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.86 | 02-FEB-13:00 | 1509.10 | 05-FEB-07:53 |
March | 1295.83 | 01-MAR-10:09 | 904.43 | 27-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 205.74 | 05-MAR-12:43 | 1466.78 | 20-MAR-21:25 |
April | 1295.83 | 03-APR-09:09 | 919.52 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.22 | 29-APR-16:00 | 996.38 | 01-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 744.20 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.09 | 07-MAY-13:53 | 241.81 | 06-MAY-19:55 |
June | 1295.83 | 01-JUN-09:09 | 611.54 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 437.16 | 10-JUN-17:10 | 296.56 | 06-JUN-21:20 |
July | 1295.83 | 03-JUL-09:09 | 627.95 | 14-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 400.17 | 02-JUL-11:08 | 220.47 | 31-JUL-01:55 |
August | 1295.83 | 01-AUG-09:09 | 816.72 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 591.38 | 20-AUG-13:55 | 404.73 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 905.52 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 544.03 | 09-SEP-17:10 | 405.41 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1011.26 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 638.77 | 09-OCT-13:53 | 679.96 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 980.08 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.52 | 05-NOV-13:00 | 1009.24 | 12-NOV-06:55 |
December | 1295.83 | 01-DEC-10:09 | 993.57 | 12-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.33 | 10-DEC-11:00 | 1371.92 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 611.54 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 87.67 | 220.47 | |||||
Maximum of Months | 1295.83 | 1011.26 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 638.77 | 1509.10 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 4400.15 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 4400.15 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 4400.15 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 4400.15 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 4400.15 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 4400.15 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 4400.15 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 4400.15 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 4400.15 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 4400.15 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 4400.15 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 4400.15 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 4400.15 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 4400.15 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 203.27 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 203.27 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 203.27 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 203.27 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 203.27 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 203.27 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 203.27 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 203.27 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 203.27 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 203.27 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 203.27 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 203.27 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 203.27 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 203.27 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 203.27 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 203.27 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 203.27 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 203.27 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 203.27 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 203.27 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 203.27 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 203.27 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 203.27 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 203.27 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 203.27 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 203.27 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 203.27 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 203.27 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 203.27 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 203.27 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 203.27 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 203.27 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 203.27 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 203.27 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 203.27 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 203.27 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 203.27 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 203.27 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 203.27 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 203.27 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 203.27 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 203.27 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.96 | 16-JAN-15:00 | 1537.59 | 09-JAN-05:14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.65 | 02-FEB-13:00 | 2203.73 | 05-FEB-07:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.82 | 26-MAR-14:00 | 1849.29 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.15 | 29-APR-17:01 | 1076.54 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.07 | 21-MAY-14:00 | 165.79 | 14-MAY-12:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.38 | 10-JUN-17:02 | 280.08 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.01 | 22-JUL-18:53 | 105.90 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 697.85 | 20-AUG-14:00 | 396.87 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 658.63 | 09-SEP-17:02 | 368.67 | 05-SEP-03:04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.99 | 09-OCT-13:51 | 908.88 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.63 | 05-NOV-12:52 | 1284.43 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.02 | 10-DEC-14:51 | 2041.49 | 20-DEC-01:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.96 | 105.90 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 768.99 | 2203.73 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.48 | 16-JAN-14:52 | 2630.32 | 21-JAN-05:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.08 | 20-FEB-14:53 | 3778.32 | 05-FEB-07:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.69 | 05-MAR-13:00 | 3170.19 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 578.93 | 29-APR-17:01 | 1801.57 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.96 | 07-MAY-14:00 | 261.76 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1070.18 | 10-JUN-17:02 | 482.28 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947.60 | 22-JUL-18:53 | 210.40 | 31-JUL-02:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1272.66 | 20-AUG-14:00 | 726.70 | 25-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1206.86 | 09-SEP-17:02 | 585.31 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1380.72 | 09-OCT-14:00 | 1540.02 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.62 | 05-NOV-13:00 | 2196.16 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.06 | 10-DEC-14:51 | 3461.08 | 20-DEC-01:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.08 | 210.40 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1380.72 | 3778.32 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.71 | 16-JAN-15:00 | 2609.05 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.10 | 02-FEB-13:00 | 3419.19 | 05-FEB-07:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.63 | 26-MAR-14:00 | 3340.18 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.01 | 29-APR-17:01 | 2017.26 | 01-APR-17:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716.80 | 07-MAY-13:55 | 582.10 | 14-MAY-11:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 977.35 | 10-JUN-17:02 | 502.56 | 18-JUN-13:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 730.68 | 22-JUL-18:50 | 536.51 | 30-JUL-10:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1149.50 | 20-AUG-14:00 | 787.81 | 25-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.66 | 09-SEP-22:53 | 771.88 | 05-SEP-03:04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951.48 | 08-OCT-13:51 | 1428.39 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.64 | 05-NOV-13:00 | 2254.73 | 12-NOV-06:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.11 | 10-DEC-15:00 | 3276.82 | 20-DEC-01:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.11 | 502.56 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1326.66 | 3419.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 108958.05 | 16-JAN-06:12 | 4488.06 | 4334.93 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 111230.51 | 13-FEB-03:32 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 115460.94 | 20-MAR-03:33 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 114875.73 | 02-APR-23:10 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 106067.87 | 29-MAY-22:43 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98800.87 | 12-JUN-02:22 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 103722.07 | 04-JUL-19:30 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 100634.45 | 20-AUG-22:23 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 105920.32 | 04-SEP-12:50 | 2692.84 | 2600.96 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 107627.36 | 17-OCT-04:11 | 0.00 | 5385.15 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 113715.29 | 23-NOV-17:23 | 2692.84 | 2600.96 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 115329.26 | 17-DEC-17:40 | 2692.84 | 2600.96 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 98800.87 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 115460.94 | 4488.06 | 5385.15 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 86622.30 | 02-JAN-05:14 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87495.94 | 28-FEB-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 87400.61 | 28-MAR-03:02 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85039.68 | 11-APR-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 90251.45 | 31-MAY-03:02 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87604.42 | 01-JUN-04:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79536.45 | 15-JUL-05:02 | 16122.38 | 5373.60 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78209.31 | 01-AUG-05:02 | 16122.38 | 5373.60 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 90393.64 | 26-SEP-03:02 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90294.17 | 02-OCT-03:02 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 89912.61 | 27-NOV-04:02 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 91001.32 | 26-DEC-04:02 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 78209.31 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91001.32 | 16122.38 | 5373.60 | 76473.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 74349.67 | 20-JAN-05:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74774.86 | 28-FEB-05:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74920.09 | 31-MAR-04:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80977.64 | 29-APR-04:12 | 0.00 | 5373.60 | 44532.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82238.05 | 12-MAY-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81331.71 | 01-JUN-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81959.98 | 12-JUL-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77853.08 | 17-AUG-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81559.45 | 22-SEP-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79854.33 | 03-OCT-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80466.92 | 02-NOV-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 75042.62 | 14-DEC-05:11 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 74349.67 | 0.00 | 5373.60 | 44532.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82238.05 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 70097.24 | 20-JAN-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69384.79 | 03-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74429.92 | 27-MAR-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80023.00 | 29-APR-04:12 | 0.00 | 5373.60 | 44532.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81900.93 | 12-MAY-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83598.45 | 14-JUN-03:02 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80837.50 | 12-JUL-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79188.24 | 29-AUG-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79830.05 | 29-SEP-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81946.27 | 12-OCT-04:12 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74854.33 | 01-NOV-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72006.25 | 11-DEC-06:02 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 69384.79 | 0.00 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83598.45 | 16122.38 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8556.81 | 02-JAN-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 |
February | 7244.92 | 28-FEB-05:11 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.18 |
March | 10421.11 | 07-MAR-05:11 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.99 |
April | 10223.95 | 28-APR-05:02 | 1214.60 | 404.83 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 |
May | 11767.71 | 23-MAY-05:02 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 11848.38 | 13-JUN-05:02 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
July | 14011.65 | 23-JUL-15:22 | 506.08 | 232.58 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 149.82 | 0.00 |
August | 12172.38 | 14-AUG-04:21 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 13.58 | 0.00 |
September | 12548.82 | 11-SEP-03:01 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 | 0.00 |
October | 11869.32 | 24-OCT-05:02 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 0.00 |
November | 11129.87 | 02-NOV-04:11 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 |
December | 9917.79 | 11-DEC-06:01 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.66 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7244.92 | 0.00 | 232.58 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14011.65 | 2024.33 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 149.82 | 107.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12006.66 | 01-JAN-10:32 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.64 |
February | 13355.96 | 26-FEB-10:32 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.77 |
March | 16897.96 | 26-MAR-09:32 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 |
April | 17126.71 | 23-APR-08:62 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.29 |
May | 19085.67 | 29-MAY-08:31 | 456.59 | 209.83 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 |
June | 16990.57 | 11-JUN-08:62 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.79 |
July | 17147.59 | 09-JUL-09:22 | 326.14 | 149.88 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 62.15 | 0.00 |
August | 16968.94 | 27-AUG-10:22 | 326.14 | 149.88 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.60 | 0.00 |
September | 18265.65 | 24-SEP-09:32 | 391.37 | 179.86 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 | 0.00 |
October | 17036.54 | 15-OCT-08:53 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.67 |
November | 16762.04 | 11-NOV-09:13 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.77 |
December | 7099.56 | 11-DEC-06:01 | 1304.55 | 434.81 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.64 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7099.56 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19085.67 | 1304.55 | 434.81 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 62.15 | 113.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18189.80 | 16-JAN-14:42 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.21 |
February | 17752.58 | 26-FEB-12:32 | 506.09 | 232.58 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.37 |
March | 16398.50 | 05-MAR-12:43 | 303.66 | 139.55 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 | 0.00 |
April | 11744.15 | 28-APR-05:02 | 1214.62 | 404.83 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 |
May | 12982.58 | 24-MAY-03:01 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 |
June | 13185.39 | 28-JUN-05:02 | 2024.37 | 674.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 | 0.00 |
July | 16059.05 | 23-JUL-15:22 | 506.09 | 232.58 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 149.10 | 0.00 |
August | 15932.90 | 20-AUG-13:02 | 404.87 | 186.07 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 187.16 | 0.00 |
September | 17009.44 | 10-SEP-12:23 | 404.87 | 186.07 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 156.39 | 0.00 |
October | 18048.88 | 15-OCT-12:52 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 | 0.00 |
November | 18473.70 | 11-NOV-14:32 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 |
December | 18479.74 | 17-DEC-12:52 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.21 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11744.15 | 0.00 | 139.55 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18479.74 | 2024.37 | 674.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 187.16 | 377.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21450.82 | 16-JAN-16:01 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 |
February | 21612.99 | 26-FEB-15:12 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 |
March | 21925.91 | 26-MAR-16:52 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.84 |
April | 22460.40 | 23-APR-16:42 | 391.37 | 179.86 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 |
May | 22821.67 | 29-MAY-16:31 | 587.05 | 269.79 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 0.00 |
June | 22223.57 | 11-JUN-16:42 | 391.37 | 179.86 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 53.09 | 0.00 |
July | 22605.63 | 16-JUL-16:11 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 73.25 | 0.00 |
August | 21379.45 | 06-AUG-15:42 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.20 |
September | 22341.98 | 24-SEP-16:11 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 41.62 | 0.00 |
October | 22545.24 | 08-OCT-15:31 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 120.56 | 0.00 |
November | 22966.00 | 11-NOV-15:12 | 391.37 | 179.86 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 |
December | 21813.85 | 17-DEC-15:31 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.99 |
Annual Sum or Average | |||||||||||
Minimum of Months | 21379.45 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22966.00 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 120.56 | 240.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5168.09 | 02-JAN-13:30 | 1923.11 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | 0.00 |
February | 5386.36 | 22-FEB-14:30 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.02 | 0.00 |
March | 6823.35 | 30-MAR-13:20 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 51.82 | 0.00 |
April | 9459.07 | 29-APR-04:11 | 0.00 | 674.71 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.23 |
May | 11164.00 | 22-MAY-04:31 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 110.08 | 0.00 |
June | 11689.77 | 05-JUN-03:02 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 | 0.00 |
July | 12804.61 | 23-JUL-15:12 | 506.08 | 232.58 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 303.79 | 0.00 |
August | 11768.95 | 14-AUG-03:01 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 0.00 |
September | 11633.86 | 11-SEP-03:01 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.16 |
October | 12729.02 | 08-OCT-15:21 | 708.51 | 325.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 511.05 | 0.00 |
November | 9616.02 | 02-NOV-04:11 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.14 |
December | 5827.31 | 15-DEC-15:00 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 52.68 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5168.09 | 0.00 | 232.58 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12804.61 | 2010.79 | 837.28 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 511.05 | 89.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11525.09 | 01-JAN-08:55 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.61 |
February | 8473.80 | 27-FEB-11:05 | 2478.65 | 1079.15 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.85 |
March | 17117.03 | 26-MAR-09:32 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.15 |
April | 17559.96 | 23-APR-09:02 | 326.14 | 149.88 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.73 |
May | 18139.46 | 28-MAY-10:42 | 326.14 | 149.88 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 155.88 | 0.00 |
June | 17582.17 | 11-JUN-08:62 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.41 |
July | 18172.02 | 23-JUL-07:52 | 326.14 | 149.88 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18084.55 | 06-AUG-09:52 | 326.14 | 149.88 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 54.96 | 0.00 |
September | 18871.94 | 24-SEP-09:42 | 391.37 | 179.86 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 29.01 | 0.00 |
October | 18122.68 | 09-OCT-09:51 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 141.77 | 0.00 |
November | 9897.84 | 02-NOV-10:05 | 2478.65 | 1079.15 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 11.97 | 0.00 |
December | 8643.33 | 11-DEC-06:01 | 1304.55 | 434.81 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8473.80 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18871.94 | 2478.65 | 1079.15 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 155.88 | 410.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16987.38 | 01-JAN-13:31 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.21 |
February | 16730.22 | 26-FEB-14:42 | 506.09 | 232.58 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.89 |
March | 14110.06 | 05-MAR-14:32 | 506.09 | 232.58 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 24.52 | 0.00 |
April | 11121.05 | 29-APR-04:11 | 0.00 | 674.72 | 5591.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.37 |
May | 12950.97 | 22-MAY-04:31 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 115.53 | 0.00 |
June | 13501.55 | 05-JUN-03:02 | 0.00 | 404.83 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 37.09 | 0.00 |
July | 14829.22 | 23-JUL-15:12 | 506.09 | 232.58 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 308.61 | 0.00 |
August | 13742.34 | 14-AUG-03:01 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 | 0.00 |
September | 15870.27 | 10-SEP-12:23 | 404.87 | 186.07 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 339.85 | 0.00 |
October | 17016.40 | 15-OCT-13:32 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 72.36 | 0.00 |
November | 17083.46 | 05-NOV-13:22 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.64 |
December | 17288.54 | 17-DEC-13:02 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 908.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11121.05 | 0.00 | 186.07 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17288.54 | 1012.19 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 339.85 | 908.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18110.46 | 01-JAN-16:11 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.34 |
February | 19088.91 | 26-FEB-16:42 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.61 |
March | 18004.98 | 26-MAR-16:52 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.61 |
April | 18729.49 | 23-APR-17:02 | 0.00 | 198.61 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.27 |
May | 19135.78 | 29-MAY-16:52 | 391.37 | 179.86 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 110.35 | 0.00 |
June | 19054.08 | 11-JUN-16:42 | 391.37 | 179.86 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 116.88 | 0.00 |
July | 18202.25 | 16-JUL-15:52 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 259.47 | 0.00 |
August | 18746.77 | 06-AUG-16:31 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.09 |
September | 18983.71 | 03-SEP-16:12 | 391.37 | 179.86 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 196.78 | 0.00 |
October | 19808.83 | 08-OCT-15:21 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 206.29 | 0.00 |
November | 18288.92 | 05-NOV-15:22 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 0.00 |
December | 13575.60 | 11-DEC-06:01 | 1304.55 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.59 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13575.60 | 0.00 | 149.88 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19808.83 | 1304.55 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 259.47 | 89.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5484.65 | 31-JAN-15:00 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 25.19 | 0.00 |
February | 5820.76 | 22-FEB-14:30 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 | 0.00 |
March | 7302.52 | 30-MAR-13:30 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 60.88 | 0.00 |
April | 9492.73 | 28-APR-05:02 | 1214.60 | 404.83 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 |
May | 15066.85 | 29-MAY-16:01 | 809.73 | 372.12 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 229.23 | 0.00 |
June | 14787.62 | 04-JUN-15:42 | 607.30 | 279.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.99 | 0.00 |
July | 15145.11 | 23-JUL-15:12 | 506.08 | 232.58 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 334.88 | 0.00 |
August | 14172.44 | 20-AUG-13:02 | 404.87 | 186.06 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 507.87 | 0.00 |
September | 15364.36 | 10-SEP-14:51 | 708.51 | 325.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 296.30 | 0.00 |
October | 15178.72 | 08-OCT-15:21 | 708.51 | 325.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 533.01 | 0.00 |
November | 10743.11 | 01-NOV-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 |
December | 6373.05 | 15-DEC-15:00 | 2010.79 | 837.28 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 63.95 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5484.65 | 404.87 | 186.06 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15364.36 | 2010.79 | 837.28 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 533.01 | 12.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10812.07 | 01-JAN-09:37 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.05 |
February | 7061.48 | 27-FEB-10:20 | 1295.83 | 539.58 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 |
March | 11810.48 | 26-MAR-10:33 | 195.68 | 89.93 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.77 |
April | 17651.72 | 23-APR-09:42 | 326.14 | 149.88 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.22 |
May | 18972.17 | 29-MAY-08:41 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 |
June | 18388.65 | 04-JUN-10:22 | 326.14 | 149.88 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 59.30 | 0.00 |
July | 18385.52 | 23-JUL-07:52 | 326.14 | 149.88 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18364.26 | 27-AUG-10:22 | 326.14 | 149.88 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 90.86 | 0.00 |
September | 19573.24 | 10-SEP-09:31 | 456.59 | 209.83 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 231.38 | 0.00 |
October | 18356.68 | 09-OCT-09:51 | 652.28 | 299.76 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 153.32 | 0.00 |
November | 12274.77 | 11-NOV-09:02 | 260.91 | 119.91 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.14 |
December | 5620.04 | 16-DEC-09:40 | 391.37 | 179.86 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5620.04 | 195.68 | 89.93 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19573.24 | 1295.83 | 539.58 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 231.38 | 438.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18830.42 | 01-JAN-14:11 | 1012.19 | 465.17 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 |
February | 17725.09 | 26-FEB-12:13 | 404.87 | 186.07 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 |
March | 16839.09 | 26-MAR-13:53 | 303.66 | 139.55 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 176.76 | 0.00 |
April | 12061.03 | 29-APR-04:11 | 0.00 | 674.72 | 5591.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.63 |
May | 16955.59 | 29-MAY-16:01 | 809.75 | 372.13 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 233.56 | 0.00 |
June | 16636.44 | 04-JUN-15:02 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 140.01 | 0.00 |
July | 17035.35 | 23-JUL-15:12 | 506.09 | 232.58 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 342.71 | 0.00 |
August | 16665.62 | 27-AUG-13:02 | 404.87 | 186.07 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 376.21 | 0.00 |
September | 18359.76 | 10-SEP-14:51 | 708.53 | 325.62 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 265.01 | 0.00 |
October | 18842.21 | 08-OCT-15:21 | 708.53 | 325.62 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 310.10 | 0.00 |
November | 19161.79 | 11-NOV-12:22 | 607.31 | 279.10 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.17 |
December | 19912.31 | 10-DEC-12:51 | 708.53 | 325.62 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.27 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12061.03 | 0.00 | 139.55 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19912.31 | 1012.19 | 674.72 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 376.21 | 215.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19290.40 | 01-JAN-16:11 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.55 |
February | 20151.64 | 26-FEB-17:32 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.43 |
March | 18232.82 | 05-MAR-16:23 | 260.91 | 119.91 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.79 |
April | 20907.99 | 16-APR-17:02 | 0.00 | 198.61 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.51 |
May | 22479.26 | 29-MAY-16:01 | 521.82 | 239.81 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 86.66 | 0.00 |
June | 20572.28 | 04-JUN-16:22 | 391.37 | 179.86 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 43.65 | 0.00 |
July | 19696.91 | 23-JUL-15:12 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 223.74 | 0.00 |
August | 17790.99 | 06-AUG-16:42 | 326.14 | 149.88 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.56 |
September | 21440.14 | 10-SEP-14:51 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 170.62 | 0.00 |
October | 21538.39 | 08-OCT-15:21 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 216.73 | 0.00 |
November | 19939.52 | 11-NOV-15:42 | 391.37 | 179.86 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.35 |
December | 20091.52 | 10-DEC-15:31 | 456.59 | 209.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17790.99 | 0.00 | 119.91 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22479.26 | 652.28 | 299.76 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 223.74 | 626.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11479.99 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.23 |
February | 6539.40 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.02 |
March | 7108.36 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.21 |
April | 7594.95 | 24-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.16 |
May | 8378.09 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 |
June | 8677.48 | 19-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 |
July | 9542.37 | 06-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
August | 9182.88 | 22-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | 0.00 |
September | 10094.00 | 11-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
October | 10438.05 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 |
November | 7981.38 | 13-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.44 |
December | 8652.24 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.94 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6539.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11479.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | 97.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7017.12 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.45 |
February | 4451.95 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.30 |
March | 3658.25 | 01-MAR-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.34 |
April | 5064.30 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.38 | 0.00 |
May | 7352.47 | 06-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.51 |
June | 7480.85 | 16-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8167.34 | 08-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 |
August | 8442.06 | 05-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 0.00 |
September | 8188.84 | 01-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9455.89 | 05-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.31 |
November | 4840.04 | 07-NOV-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 0.00 |
December | 5836.74 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3658.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9455.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.38 | 402.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8911.24 | 19-JAN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.57 |
February | 10600.38 | 24-FEB-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.69 |
March | 11169.48 | 06-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 0.00 |
April | 15752.74 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.93 | 0.00 |
May | 17709.56 | 17-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.28 | 0.00 |
June | 17452.26 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.83 | 0.00 |
July | 17860.15 | 07-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.62 | 0.00 |
August | 17051.68 | 03-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.43 | 0.00 |
September | 15552.52 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.37 | 0.00 |
October | 15183.25 | 05-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.13 | 0.00 |
November | 12030.19 | 02-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.05 | 0.00 |
December | 10353.08 | 15-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.07 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8911.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17860.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.43 | 45.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2129.44 | 01-JAN-17:30 | 0.00 | 33.88 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4199.47 | 26-FEB-18:00 | 0.00 | 56.46 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5807.49 | 05-MAR-17:47 | 0.00 | 33.88 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7991.50 | 16-APR-18:12 | 0.00 | 49.88 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2109.51 | 29-MAY-18:06 | 0.00 | 62.35 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3969.25 | 11-JUN-18:30 | 0.00 | 12.47 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5796.99 | 23-JUL-19:00 | 0.00 | 24.94 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7706.21 | 06-AUG-17:57 | 0.00 | 124.70 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2200.71 | 03-SEP-18:05 | 0.00 | 124.70 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4099.96 | 01-OCT-17:38 | 0.00 | 49.88 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6009.17 | 12-NOV-17:10 | 0.00 | 22.59 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7893.22 | 25-DEC-16:55 | 0.00 | 22.59 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2109.51 | 0.00 | 12.47 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7991.50 | 0.00 | 124.70 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1796.21 | 01-JAN-17:12 | 0.00 | 45.17 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3845.86 | 26-FEB-17:52 | 0.00 | 56.46 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5397.72 | 06-MAR-18:00 | 0.00 | 112.93 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7495.77 | 16-APR-18:17 | 0.00 | 49.88 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1925.99 | 28-MAY-18:30 | 0.00 | 12.47 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3744.88 | 11-JUN-18:30 | 0.00 | 12.47 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5458.77 | 23-JUL-19:00 | 0.00 | 24.94 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7254.47 | 06-AUG-17:33 | 0.00 | 74.82 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2053.69 | 03-SEP-17:54 | 0.00 | 62.35 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3819.18 | 09-OCT-17:26 | 0.00 | 62.35 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5539.72 | 06-NOV-17:00 | 0.00 | 203.27 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7277.82 | 17-DEC-17:05 | 0.00 | 22.59 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1796.21 | 0.00 | 12.47 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7495.77 | 0.00 | 203.27 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1846.89 | 01-JAN-17:20 | 0.00 | 45.17 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3865.13 | 26-FEB-18:00 | 0.00 | 56.46 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5460.43 | 06-MAR-17:50 | 0.00 | 112.93 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7663.99 | 23-APR-18:02 | 0.00 | 62.35 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2250.48 | 29-MAY-18:20 | 0.00 | 62.35 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4018.52 | 11-JUN-18:30 | 0.00 | 12.47 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5717.28 | 23-JUL-19:00 | 0.00 | 24.94 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7507.98 | 06-AUG-17:46 | 0.00 | 62.35 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2321.28 | 03-SEP-17:58 | 0.00 | 62.35 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4057.37 | 09-OCT-17:22 | 0.00 | 62.35 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5601.28 | 06-NOV-17:00 | 0.00 | 203.27 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7357.71 | 10-DEC-17:08 | 0.00 | 56.46 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1846.89 | 0.00 | 12.47 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7663.99 | 0.00 | 203.27 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91354.23 | 02-JAN-17:00 | 0.00 | 4400.15 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182014.71 | 27-FEB-17:00 | 0.00 | 4400.15 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 273049.29 | 06-MAR-17:00 | 0.00 | 4400.15 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 364767.52 | 28-APR-19:00 | 0.00 | 1466.72 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 102969.62 | 01-MAY-00:03 | 0.00 | 2699.35 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 181565.42 | 12-JUN-16:00 | 0.00 | 4400.15 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 273855.65 | 05-JUL-16:00 | 0.00 | 4400.15 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370618.64 | 06-AUG-15:42 | 0.00 | 1222.27 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 106454.83 | 01-SEP-00:10 | 0.00 | 539.87 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 183247.81 | 10-OCT-16:00 | 0.00 | 4400.15 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 274889.91 | 06-NOV-17:00 | 0.00 | 4400.15 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366630.93 | 26-DEC-17:00 | 0.00 | 4400.15 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 91354.23 | 0.00 | 539.87 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370618.64 | 0.00 | 4400.15 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.156863E+13 | 1245805.95 | 19-JAN-16:49 | 0.680316E+11 | 746592.51 | 06-JAN-09:39 |
February | 0.182284E+13 | 1400358.66 | 24-FEB-16:49 | 0.520397E+11 | 505641.61 | 06-FEB-06:10 |
March | 0.247540E+13 | 1536516.29 | 29-MAR-15:20 | 0.554370E+11 | 408522.58 | 20-MAR-00:10 |
April | 0.288865E+13 | 1740463.54 | 28-APR-15:00 | 0.395987E+11 | 179844.41 | 03-APR-02:00 |
May | 0.200847E+13 | 1290350.04 | 26-MAY-15:09 | 0.406985E+11 | 140410.64 | 09-MAY-03:49 |
June | 0.238351E+13 | 1453560.87 | 19-JUN-07:00 | 0.377167E+11 | 141573.31 | 03-JUN-03:49 |
July | 0.284447E+13 | 1615042.20 | 21-JUL-15:50 | 0.362312E+11 | 141707.73 | 04-JUL-20:19 |
August | 0.331120E+13 | 1765772.50 | 03-AUG-15:50 | 0.377605E+11 | 140787.83 | 27-AUG-21:30 |
September | 0.193845E+13 | 1280110.47 | 01-SEP-15:09 | 0.371808E+11 | 142058.16 | 04-SEP-20:49 |
October | 0.232828E+13 | 1457126.17 | 06-OCT-15:09 | 0.412004E+11 | 153948.19 | 29-OCT-17:00 |
November | 0.242134E+13 | 1572777.64 | 02-NOV-07:00 | 0.431112E+11 | 207978.59 | 19-NOV-12:39 |
December | 0.276622E+13 | 1712188.14 | 14-DEC-16:30 | 0.586298E+11 | 453497.82 | 20-DEC-06:10 |
Annual Sum or Average | 0.287575E+14 | 0.547636E+12 | ||||
Minimum of Months | 0.156863E+13 | 1245805.95 | 0.362312E+11 | 140410.64 | ||
Maximum of Months | 0.331120E+13 | 1765772.50 | 0.680316E+11 | 746592.51 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.216818E+12 | 0.353547E+11 | 0.766053E+12 | 0.166057E+12 | 0.158554E+12 | 0.273306E+11 | 0.00 | 0.115690E+12 | 0.474265E+11 | 0.333854E+11 | 0.195825E+10 | 0.00 | 0.00 |
February | 0.195734E+12 | 0.295464E+11 | 0.978954E+12 | 0.149994E+12 | 0.145730E+12 | 0.299940E+11 | 0.00 | 0.195993E+12 | 0.694969E+11 | 0.249895E+11 | 0.240773E+10 | 0.00 | 0.00 |
March | 0.231988E+12 | 0.296341E+11 | 0.141645E+13 | 0.166228E+12 | 0.164149E+12 | 0.363563E+11 | 0.00 | 0.267848E+12 | 0.933635E+11 | 0.668994E+11 | 0.248443E+10 | 0.00 | 0.00 |
April | 0.206255E+12 | 0.257660E+11 | 0.166021E+13 | 0.160684E+12 | 0.164972E+12 | 0.453164E+11 | 0.00 | 0.463774E+12 | 0.141325E+12 | 0.163986E+11 | 0.395267E+10 | 0.00 | 0.00 |
May | 0.221784E+12 | 0.239173E+11 | 0.774418E+12 | 0.166142E+12 | 0.186148E+12 | 0.521526E+11 | 0.00 | 0.391881E+12 | 0.185942E+12 | 0.00 | 0.608632E+10 | 0.00 | 0.00 |
June | 0.220457E+12 | 0.217666E+11 | 0.106218E+13 | 0.160845E+12 | 0.184460E+12 | 0.560261E+11 | 0.00 | 0.485882E+12 | 0.185800E+12 | 0.00 | 0.608632E+10 | 0.00 | 0.00 |
July | 0.206188E+12 | 0.234052E+11 | 0.139289E+13 | 0.165981E+12 | 0.187350E+12 | 0.609696E+11 | 0.00 | 0.601603E+12 | 0.200303E+12 | 0.00 | 0.577712E+10 | 0.00 | 0.00 |
August | 0.230740E+12 | 0.254947E+11 | 0.173328E+13 | 0.166228E+12 | 0.193457E+12 | 0.633889E+11 | 0.00 | 0.692729E+12 | 0.199553E+12 | 0.00 | 0.633042E+10 | 0.00 | 0.00 |
September | 0.206613E+12 | 0.273356E+11 | 0.740378E+12 | 0.160684E+12 | 0.176764E+12 | 0.515458E+11 | 0.00 | 0.385277E+12 | 0.184079E+12 | 0.00 | 0.577712E+10 | 0.00 | 0.00 |
October | 0.215381E+12 | 0.312846E+11 | 0.108288E+13 | 0.166057E+12 | 0.184301E+12 | 0.518106E+11 | 0.00 | 0.418162E+12 | 0.162452E+12 | 0.112147E+11 | 0.472883E+10 | 0.00 | 0.00 |
November | 0.214322E+12 | 0.332827E+11 | 0.135889E+13 | 0.160750E+12 | 0.164855E+12 | 0.395089E+11 | 0.00 | 0.295542E+12 | 0.104666E+12 | 0.471320E+11 | 0.239071E+10 | 0.00 | 0.00 |
December | 0.210464E+12 | 0.361462E+11 | 0.170972E+13 | 0.165982E+12 | 0.162683E+12 | 0.340108E+11 | 0.00 | 0.281101E+12 | 0.869295E+11 | 0.768951E+11 | 0.228478E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.257674E+13 | 0.342934E+12 | 0.146763E+14 | 0.195563E+13 | 0.207342E+13 | 0.548411E+12 | 0.00 | 0.459548E+13 | 0.166134E+13 | 0.276915E+12 | 0.502647E+11 | ||
Minimum of Months | 0.195734E+12 | 0.217666E+11 | 0.740378E+12 | 0.149994E+12 | 0.145730E+12 | 0.273306E+11 | 0.00 | 0.115690E+12 | 0.474265E+11 | 0.00 | 0.195825E+10 | 0.00 | 0.00 |
Maximum of Months | 0.231988E+12 | 0.361462E+11 | 0.173328E+13 | 0.166228E+12 | 0.193457E+12 | 0.633889E+11 | 0.00 | 0.692729E+12 | 0.200303E+12 | 0.768951E+11 | 0.633042E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.241482E+11 | 0.00 | 0.438834E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.125984E+11 | 0.00 | 0.394413E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.111939E+11 | 0.00 | 0.442430E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.109675E+10 | 0.00 | 0.385019E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.214362E+10 | 0.00 | 0.385549E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.187640E+10 | 0.00 | 0.358403E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.204830E+10 | 0.00 | 0.341829E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.114979E+10 | 0.00 | 0.366108E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.196278E+10 | 0.00 | 0.352180E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.243208E+10 | 0.00 | 0.387684E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.281262E+10 | 0.00 | 0.402986E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.166202E+11 | 0.00 | 0.420097E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.800830E+11 | 0.467553E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.109675E+10 | 0.00 | 0.341829E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.241482E+11 | 0.00 | 0.442430E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 245606.76 | 31-JAN-08:09 | 39974.20 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 126010.10 | 31-JAN-08:20 | 108277.29 | 19-JAN-15:00 | 41038.63 | 31-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 248203.22 | 01-FEB-08:09 | 39974.20 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 126011.47 | 01-FEB-08:20 | 115802.81 | 27-FEB-16:19 | 41537.73 | 24-FEB-11:30 | 0.00 | 01-FEB-00:10 |
March | 243215.29 | 27-MAR-07:10 | 39974.20 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 126008.83 | 27-MAR-07:19 | 107204.54 | 29-MAR-15:20 | 41330.57 | 29-MAR-12:30 | 0.00 | 01-MAR-00:10 |
April | 245424.95 | 14-APR-07:10 | 39974.20 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 126010.00 | 14-APR-07:19 | 125796.78 | 28-APR-15:30 | 46138.82 | 26-APR-15:30 | 0.00 | 01-APR-00:10 |
May | 229828.89 | 23-MAY-07:30 | 39974.20 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 126001.73 | 23-MAY-07:40 | 130971.10 | 17-MAY-13:00 | 50957.67 | 26-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 225325.27 | 16-JUN-07:10 | 39974.20 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 125999.35 | 16-JUN-07:19 | 128672.12 | 28-JUN-15:00 | 47103.58 | 14-JUN-09:50 | 0.00 | 01-JUN-00:10 |
July | 227323.54 | 14-JUL-07:10 | 39974.20 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 126000.41 | 14-JUL-07:19 | 133230.84 | 07-JUL-15:00 | 47392.85 | 31-JUL-13:00 | 0.00 | 01-JUL-00:10 |
August | 230615.27 | 21-AUG-07:10 | 39974.20 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 126002.15 | 21-AUG-07:19 | 139647.03 | 30-AUG-15:00 | 46650.86 | 16-AUG-13:50 | 0.00 | 01-AUG-00:10 |
September | 243206.24 | 26-SEP-07:10 | 39974.20 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 126008.82 | 26-SEP-07:19 | 129389.03 | 01-SEP-14:00 | 46917.19 | 08-SEP-12:00 | 0.00 | 01-SEP-00:10 |
October | 251694.63 | 25-OCT-07:10 | 39974.20 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 126013.33 | 25-OCT-07:19 | 137013.94 | 11-OCT-15:39 | 42859.91 | 25-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 248179.70 | 21-NOV-16:00 | 39974.20 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 126011.20 | 01-NOV-07:19 | 123911.78 | 06-NOV-15:30 | 41351.46 | 07-NOV-12:00 | 0.00 | 01-NOV-00:10 |
December | 251107.93 | 12-DEC-08:09 | 39974.20 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 126013.02 | 12-DEC-08:20 | 117749.03 | 15-DEC-15:30 | 41646.12 | 12-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 225325.27 | 39974.20 | 423497.50 | 125999.35 | 107204.54 | 41038.63 | 0.00 | |||||||
Maximum of Months | 251694.63 | 39974.20 | 778371.69 | 126013.33 | 139647.03 | 50957.67 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 278099.89 | 19-JAN-11:00 | 83768.54 | 02-JAN-10:20 | 100000.00 | 06-JAN-12:00 | 4520.44 | 02-JAN-10:09 | 0.00 | 0.00 |
February | 309821.69 | 24-FEB-16:49 | 83768.54 | 01-FEB-13:20 | 100000.00 | 12-FEB-12:20 | 4520.44 | 01-FEB-11:50 | 0.00 | 0.00 |
March | 343454.80 | 28-MAR-13:30 | 83768.54 | 06-MAR-08:00 | 100000.00 | 03-MAR-22:10 | 4520.44 | 06-MAR-07:10 | 0.00 | 0.00 |
April | 406431.90 | 28-APR-14:30 | 83768.54 | 04-APR-12:30 | 100000.00 | 10-APR-04:19 | 4520.44 | 22-APR-16:10 | 0.00 | 0.00 |
May | 324378.63 | 23-MAY-14:09 | 83768.54 | 29-MAY-17:19 | 0.00 | 01-MAY-00:10 | 4520.44 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 365677.25 | 29-JUN-12:09 | 83768.54 | 17-JUN-16:10 | 0.00 | 01-JUN-00:10 | 4520.44 | 17-JUN-16:10 | 0.00 | 0.00 |
July | 427129.88 | 05-JUL-12:09 | 83768.54 | 22-JUL-16:10 | 0.00 | 01-JUL-00:10 | 4520.44 | 22-JUL-16:10 | 0.00 | 0.00 |
August | 432723.34 | 07-AUG-12:09 | 83768.54 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 | 4520.44 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 343258.12 | 01-SEP-12:09 | 83768.54 | 10-SEP-15:30 | 0.00 | 01-SEP-00:10 | 4520.44 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 370060.65 | 05-OCT-12:09 | 83768.54 | 07-OCT-16:10 | 100000.00 | 27-OCT-03:09 | 4520.44 | 07-OCT-16:10 | 0.00 | 0.00 |
November | 367664.48 | 07-NOV-13:09 | 83768.54 | 01-NOV-05:30 | 100000.00 | 09-NOV-04:10 | 4520.44 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 386237.83 | 12-DEC-14:00 | 83768.54 | 08-DEC-11:20 | 100000.00 | 06-DEC-05:19 | 4520.44 | 02-DEC-13:39 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||
Minimum of Months | 278099.89 | 83768.54 | 0.00 | 4520.44 | 0.00 | 0.00 | ||||
Maximum of Months | 432723.34 | 83768.54 | 100000.00 | 4520.44 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1245805.95 | 19-JAN-16:49 | 225095.17 | 423497.50 | 0.00 | 89219.13 | 105469.65 | 38634.01 | 0.00 | 275601.53 | 83768.54 |
February | 1400358.66 | 24-FEB-16:49 | 223670.64 | 541788.89 | 0.00 | 89219.08 | 108685.39 | 38884.00 | 0.00 | 309821.69 | 83768.54 |
March | 1536516.29 | 29-MAR-15:20 | 223670.64 | 660080.29 | 0.00 | 89219.08 | 107204.54 | 39989.52 | 0.00 | 328063.24 | 83768.54 |
April | 1740463.54 | 28-APR-15:00 | 223670.64 | 778371.69 | 0.00 | 89219.08 | 124934.41 | 38910.64 | 0.00 | 397068.10 | 83768.54 |
May | 1290350.04 | 26-MAY-15:09 | 223670.64 | 423497.50 | 0.00 | 89219.08 | 101732.42 | 39660.62 | 0.00 | 324280.81 | 83768.54 |
June | 1453560.87 | 19-JUN-07:00 | 223670.64 | 541788.89 | 0.00 | 125998.47 | 99960.69 | 38598.17 | 0.00 | 335255.03 | 83768.54 |
July | 1615042.20 | 21-JUL-15:50 | 223670.64 | 660080.29 | 0.00 | 89219.08 | 129924.51 | 39004.97 | 0.00 | 384853.73 | 83768.54 |
August | 1765772.50 | 03-AUG-15:50 | 223670.64 | 778371.69 | 0.00 | 89219.08 | 136903.03 | 39130.95 | 0.00 | 410188.14 | 83768.54 |
September | 1280110.47 | 01-SEP-15:09 | 223670.64 | 423497.50 | 0.00 | 89219.08 | 128201.81 | 38913.57 | 0.00 | 288318.91 | 83768.54 |
October | 1457126.17 | 06-OCT-15:09 | 223670.64 | 541788.89 | 0.00 | 89219.08 | 129308.39 | 39252.84 | 0.00 | 345597.36 | 83768.54 |
November | 1572777.64 | 02-NOV-07:00 | 225003.99 | 660080.29 | 0.00 | 125999.37 | 87163.52 | 38517.40 | 0.00 | 347724.10 | 83768.54 |
December | 1712188.14 | 14-DEC-16:30 | 225727.52 | 778371.69 | 0.00 | 89219.87 | 113537.82 | 38664.43 | 0.00 | 378377.84 | 83768.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1245805.95 | 223670.64 | 423497.50 | 0.00 | 89219.08 | 87163.52 | 38517.40 | 0.00 | 275601.53 | 83768.54 | |
Maximum of Months | 1765772.50 | 225727.52 | 778371.69 | 0.00 | 125999.37 | 136903.03 | 39989.52 | 0.00 | 410188.14 | 83768.54 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 709867.73 | 06-JAN-09:39 | 0.00 | 68072.44 | 23-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 498360.73 | 06-FEB-06:10 | 0.00 | 67934.82 | 01-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 401241.70 | 20-MAR-00:10 | 0.00 | 66596.66 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 172563.53 | 03-APR-02:00 | 0.00 | 63008.77 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 133129.76 | 09-MAY-03:49 | 0.00 | 58755.36 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 134292.43 | 03-JUN-03:49 | 0.00 | 53415.92 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 134426.85 | 04-JUL-20:19 | 0.00 | 49337.44 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 133506.95 | 27-AUG-21:30 | 0.00 | 51158.64 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 134777.28 | 04-SEP-20:49 | 0.00 | 55610.01 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 146667.31 | 29-OCT-17:00 | 0.00 | 61043.24 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 200697.71 | 19-NOV-12:39 | 0.00 | 64927.05 | 29-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 446216.94 | 20-DEC-06:10 | 0.00 | 67453.67 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 133129.76 | 0.00 | 49337.44 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 709867.73 | 0.00 | 68072.44 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.03 | 1.50 | 27.68 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.95 | 0.83 | 27.86 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.71 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.06 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.95 | 1.00 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.70 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 26.71 | 2.17 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.42 | 1.67 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.74 | 1.83 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.94 | 2.50 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.06 | 2.50 | 27.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.97 | 1.50 | 27.58 |
Annual Sum or Average | 0.00 | 0.00 | 117.67 | 26.83 | 15.50 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.42 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.06 | 2.50 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 25.59 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.53 | 0.67 | 27.53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.49 | 0.50 | 27.49 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 1.50 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.70 | 1.83 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.78 | 7.67 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.73 | 2.50 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.70 | 5.83 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.53 | 3.17 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.72 | 7.33 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.66 | 4.17 | 27.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.56 | 0.83 | 27.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
Annual Sum or Average | 0.00 | 0.00 | 36.17 | 27.69 | 36.17 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.78 | 7.67 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.72 | 11.83 | 26.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 25.65 | 13.50 | 25.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.55 | 1.67 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.62 | 0.50 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.86 | 2.00 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.52 | 6.33 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 26.01 | 25.00 | 25.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 25.64 | 41.00 | 25.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 25.49 | 41.83 | 25.49 |
Annual Sum or Average | 0.00 | 0.00 | 145.50 | 25.88 | 143.67 | 25.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 27.55 | 41.83 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.75 | 2.67 | 27.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.55 | 3.33 | 27.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.30 | 4.00 | 27.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.35 | 8.00 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 26.93 | 5.17 | 27.89 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 27.04 | 9.50 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 27.29 | 15.50 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 39.33 | 27.34 | 12.17 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.20 | 7.67 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.27 | 8.67 | 27.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.39 | 7.33 | 27.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.43 | 7.33 | 27.87 |
Annual Sum or Average | 0.00 | 0.00 | 215.67 | 27.27 | 91.33 | 27.87 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.93 | 2.67 | 27.72 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 27.75 | 15.50 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.44 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.44 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.56 | 1.00 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.88 | 1.67 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.85 | 8.67 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.63 | 6.17 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.70 | 11.00 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.61 | 6.50 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.76 | 9.00 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.65 | 6.33 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 51.67 | 27.71 | 51.17 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.88 | 11.00 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 26.00 | 22.00 | 26.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 25.46 | 19.67 | 25.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.45 | 1.33 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.35 | 0.83 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.59 | 5.83 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 25.58 | 43.67 | 25.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 54.83 | 25.60 | 54.83 | 25.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 | 25.46 | 55.33 | 25.46 |
Annual Sum or Average | 0.00 | 0.00 | 204.67 | 25.67 | 203.83 | 25.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 | 27.59 | 55.33 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.51 | 1.00 | 27.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.95 | 0.83 | 27.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.65 | 1.50 | 27.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.90 | 2.50 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.82 | 3.17 | 28.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.62 | 3.17 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.45 | 6.67 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.30 | 3.83 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.85 | 4.17 | 28.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.89 | 4.83 | 27.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.57 | 1.83 | 27.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.83 | 27.63 |
Annual Sum or Average | 0.00 | 0.00 | 56.67 | 27.65 | 34.33 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.30 | 0.83 | 27.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.95 | 6.67 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 18.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.00 | 18.03 | 1.33 | 17.48 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 19.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.35 | 1.33 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.39 | 1.83 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.44 | 4.83 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.41 | 3.00 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.50 | 1.50 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.43 | 1.83 | 27.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 19.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.00 | 18.61 | 1.33 | 17.48 | 16.67 | 27.42 | 14.33 | 27.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 19.29 | 1.33 | 17.48 | 5.83 | 27.50 | 4.83 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 17.77 | 0.17 | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 19.34 | 0.00 | 0.00 | 0.83 | 27.53 | 0.83 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.75 | 2.33 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.88 | 9.17 | 27.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.74 | 7.67 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.69 | 14.00 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.69 | 8.50 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.79 | 11.50 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.66 | 7.67 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.40 | 0.50 | 27.40 |
December | 0.67 | 18.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.67 | 18.87 | 0.17 | 14.93 | 69.67 | 27.74 | 62.17 | 27.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.34 | 0.17 | 14.93 | 16.67 | 27.88 | 14.00 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.22 | 0.00 | 0.00 | 10.33 | 26.60 | 10.33 | 26.60 |
February | 0.33 | 18.74 | 0.00 | 0.00 | 9.33 | 25.38 | 9.33 | 25.38 |
March | 0.17 | 19.38 | 0.00 | 0.00 | 1.50 | 27.49 | 1.50 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.36 | 1.83 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.38 | 1.83 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.43 | 5.17 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.51 | 4.33 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.75 | 7.33 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 26.00 | 27.17 | 25.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 25.76 | 32.17 | 25.76 |
December | 0.50 | 18.99 | 0.00 | 0.00 | 23.83 | 25.75 | 23.83 | 25.75 |
Annual Sum or Average | 2.00 | 19.10 | 0.00 | 128.67 | 26.19 | 124.83 | 26.16 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.38 | 0.00 | 0.00 | 32.17 | 27.75 | 32.17 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.21 | 0.00 | 0.00 | 0.83 | 27.53 | 0.83 | 27.53 |
February | 0.33 | 19.04 | 0.00 | 0.00 | 0.83 | 27.97 | 0.67 | 28.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.67 | 1.67 | 27.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.94 | 2.83 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.87 | 4.17 | 28.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.69 | 4.83 | 28.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.52 | 9.17 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.52 | 5.67 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.89 | 6.33 | 28.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.97 | 5.33 | 28.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.70 | 1.50 | 27.70 |
December | 0.50 | 19.05 | 0.00 | 0.00 | 0.83 | 27.67 | 0.83 | 27.67 |
Annual Sum or Average | 1.83 | 19.14 | 0.00 | 72.50 | 27.72 | 43.83 | 27.95 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.52 | 0.67 | 27.53 |
Maximum of Months | 1.00 | 19.21 | 0.00 | 0.00 | 17.50 | 27.97 | 9.17 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.60 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 27.60 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.60 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.58 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.67 | 27.58 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.58 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 28.01 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 243.83 | 28.21 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 258.00 | 28.20 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 243.83 | 28.21 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.33 | 24.55 | 238.00 | 25.13 | 37.17 | 24.79 |
February | 87.83 | 24.59 | 311.33 | 24.74 | 67.00 | 24.77 |
March | 113.83 | 24.54 | 312.67 | 24.67 | 89.83 | 24.69 |
April | 217.83 | 24.63 | 430.67 | 24.58 | 217.83 | 24.63 |
May | 351.00 | 24.66 | 508.00 | 24.52 | 351.00 | 24.66 |
June | 308.17 | 24.72 | 496.00 | 24.46 | 308.17 | 24.72 |
July | 257.83 | 25.17 | 497.00 | 24.62 | 257.83 | 25.17 |
August | 210.83 | 25.15 | 514.00 | 24.49 | 210.83 | 25.15 |
September | 214.67 | 25.07 | 485.00 | 24.57 | 214.67 | 25.07 |
October | 156.67 | 25.31 | 452.67 | 24.68 | 156.67 | 25.31 |
November | 74.00 | 25.29 | 381.50 | 24.80 | 74.00 | 25.29 |
December | 61.33 | 25.01 | 311.50 | 24.96 | 57.83 | 25.06 |
Annual Sum or Average | 2108.33 | 24.89 | 4938.33 | 24.65 | 2042.83 | 24.91 |
Minimum of Months | 54.33 | 24.54 | 238.00 | 24.46 | 37.17 | 24.63 |
Maximum of Months | 351.00 | 25.31 | 514.00 | 25.13 | 351.00 | 25.31 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.67 | 23.73 | 210.17 | 24.55 | 0.00 | 0.00 |
February | 33.33 | 23.80 | 295.00 | 24.38 | 0.00 | 0.00 |
March | 17.33 | 23.80 | 315.00 | 24.39 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 430.33 | 24.23 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 493.33 | 24.25 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 489.67 | 24.15 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 495.17 | 24.16 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 514.00 | 24.12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 475.83 | 24.25 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 448.83 | 24.32 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 381.33 | 24.41 | 0.00 | 0.00 |
December | 9.17 | 23.90 | 313.17 | 24.47 | 0.00 | 0.00 |
Annual Sum or Average | 140.50 | 23.76 | 4861.83 | 24.28 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 210.17 | 24.12 | 0.00 | 0.00 |
Maximum of Months | 80.67 | 23.90 | 514.00 | 24.55 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 275.17 | 23.31 | 93.17 | 24.17 | 0.00 | 0.00 |
February | 189.33 | 23.34 | 141.67 | 24.20 | 0.00 | 0.00 |
March | 177.33 | 23.36 | 162.83 | 24.24 | 0.00 | 0.00 |
April | 44.33 | 23.42 | 260.83 | 24.35 | 0.00 | 0.00 |
May | 6.50 | 23.33 | 385.50 | 24.20 | 0.00 | 0.00 |
June | 6.67 | 23.35 | 367.67 | 24.19 | 0.00 | 0.00 |
July | 7.00 | 23.34 | 364.50 | 24.21 | 0.00 | 0.00 |
August | 4.67 | 23.39 | 405.50 | 24.20 | 0.00 | 0.00 |
September | 18.50 | 23.35 | 338.17 | 24.19 | 0.00 | 0.00 |
October | 28.67 | 23.43 | 350.17 | 24.27 | 0.00 | 0.00 |
November | 104.00 | 23.44 | 215.67 | 24.27 | 0.00 | 0.00 |
December | 194.17 | 23.30 | 133.17 | 24.30 | 0.00 | 0.00 |
Annual Sum or Average | 1056.33 | 23.35 | 3218.83 | 24.23 | 0.00 | |
Minimum of Months | 4.67 | 23.30 | 93.17 | 24.17 | 0.00 | 0.00 |
Maximum of Months | 275.17 | 23.44 | 405.50 | 24.35 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 390.17 | 22.31 | 79.50 | 23.66 | 10.50 | 20.72 |
February | 286.33 | 22.45 | 120.83 | 23.48 | 16.83 | 19.74 |
March | 261.67 | 22.79 | 156.50 | 24.04 | 6.00 | 20.14 |
April | 82.33 | 23.29 | 275.00 | 24.28 | 0.00 | 0.00 |
May | 0.67 | 23.43 | 437.83 | 24.25 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 450.50 | 24.23 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 454.67 | 24.28 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 455.67 | 24.24 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 378.50 | 24.24 | 0.00 | 0.00 |
October | 52.00 | 23.05 | 353.33 | 24.30 | 0.00 | 0.00 |
November | 209.00 | 22.98 | 154.33 | 24.13 | 0.00 | 0.00 |
December | 325.17 | 22.52 | 98.17 | 23.90 | 7.00 | 20.62 |
Annual Sum or Average | 1607.33 | 22.62 | 3414.83 | 24.19 | 40.33 | 20.21 |
Minimum of Months | 0.00 | 0.00 | 79.50 | 23.48 | 0.00 | 0.00 |
Maximum of Months | 390.17 | 23.43 | 455.67 | 24.30 | 16.83 | 20.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 320.67 | 22.78 | 114.17 | 24.26 | 0.00 | 0.00 |
February | 195.50 | 22.92 | 155.50 | 24.14 | 3.33 | 20.73 |
March | 183.50 | 23.19 | 209.33 | 24.25 | 0.00 | 0.00 |
April | 26.17 | 23.56 | 360.50 | 24.19 | 0.00 | 0.00 |
May | 10.33 | 25.88 | 507.83 | 24.38 | 10.33 | 25.88 |
June | 1.00 | 26.36 | 495.83 | 24.31 | 1.00 | 26.36 |
July | 6.33 | 26.42 | 497.00 | 24.39 | 6.33 | 26.42 |
August | 5.83 | 26.53 | 513.83 | 24.27 | 5.83 | 26.53 |
September | 10.33 | 25.77 | 482.67 | 24.38 | 10.33 | 25.77 |
October | 33.83 | 23.79 | 424.67 | 24.37 | 3.83 | 25.78 |
November | 116.17 | 23.51 | 254.00 | 24.24 | 0.00 | 0.00 |
December | 194.67 | 23.11 | 182.50 | 24.20 | 0.00 | 0.00 |
Annual Sum or Average | 1104.33 | 23.16 | 4197.83 | 24.31 | 41.00 | 25.61 |
Minimum of Months | 1.00 | 22.78 | 114.17 | 24.14 | 0.00 | 0.00 |
Maximum of Months | 320.67 | 26.53 | 513.83 | 24.39 | 10.33 | 26.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 264.67 | 22.98 | 142.00 | 24.54 | 4.17 | 26.75 |
February | 169.83 | 23.05 | 183.50 | 24.31 | 3.50 | 23.97 |
March | 169.33 | 23.14 | 232.50 | 24.39 | 6.33 | 26.81 |
April | 48.33 | 23.83 | 349.67 | 24.27 | 6.17 | 26.88 |
May | 40.33 | 26.70 | 506.67 | 24.46 | 40.33 | 26.70 |
June | 16.00 | 26.70 | 492.00 | 24.36 | 16.00 | 26.70 |
July | 34.67 | 26.76 | 494.00 | 24.45 | 34.67 | 26.76 |
August | 16.33 | 26.71 | 506.83 | 24.27 | 16.33 | 26.71 |
September | 42.17 | 26.73 | 479.67 | 24.47 | 42.17 | 26.73 |
October | 50.50 | 25.06 | 425.00 | 24.45 | 26.17 | 26.59 |
November | 97.83 | 23.53 | 273.83 | 24.41 | 5.00 | 26.70 |
December | 201.83 | 22.96 | 171.67 | 24.33 | 1.33 | 26.73 |
Annual Sum or Average | 1151.83 | 23.67 | 4257.33 | 24.39 | 202.17 | 26.67 |
Minimum of Months | 16.00 | 22.96 | 142.00 | 24.27 | 1.33 | 23.97 |
Maximum of Months | 264.67 | 26.76 | 506.83 | 24.54 | 42.17 | 26.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 194.00 | 23.39 | 225.50 | 24.63 | 26.67 | 26.93 |
February | 123.83 | 23.28 | 256.50 | 24.46 | 15.17 | 25.63 |
March | 159.17 | 23.10 | 247.50 | 24.36 | 7.00 | 26.76 |
April | 36.67 | 23.50 | 363.33 | 24.25 | 0.00 | 0.00 |
May | 12.00 | 25.87 | 508.00 | 24.38 | 12.00 | 25.87 |
June | 1.17 | 26.40 | 494.50 | 24.31 | 1.17 | 26.40 |
July | 10.00 | 26.46 | 497.00 | 24.40 | 10.00 | 26.46 |
August | 13.50 | 26.68 | 513.83 | 24.29 | 13.50 | 26.68 |
September | 38.17 | 26.56 | 482.83 | 24.45 | 38.17 | 26.56 |
October | 62.33 | 25.91 | 452.33 | 24.58 | 44.00 | 26.88 |
November | 81.50 | 24.90 | 374.67 | 24.66 | 35.83 | 26.85 |
December | 150.00 | 23.88 | 292.17 | 24.73 | 33.50 | 26.89 |
Annual Sum or Average | 882.33 | 23.99 | 4708.17 | 24.44 | 237.00 | 26.67 |
Minimum of Months | 1.17 | 23.10 | 225.50 | 24.25 | 0.00 | 0.00 |
Maximum of Months | 194.00 | 26.68 | 513.83 | 24.73 | 44.00 | 26.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 184.00 | 23.62 | 219.83 | 24.58 | 11.33 | 26.89 |
February | 76.83 | 24.08 | 320.33 | 24.53 | 11.67 | 26.91 |
March | 49.17 | 24.90 | 369.00 | 24.57 | 17.33 | 26.89 |
April | 43.17 | 26.87 | 467.83 | 24.63 | 43.17 | 26.87 |
May | 43.83 | 26.77 | 508.00 | 24.56 | 43.83 | 26.77 |
June | 46.33 | 26.81 | 496.00 | 24.53 | 46.33 | 26.81 |
July | 79.50 | 26.85 | 497.00 | 24.67 | 79.50 | 26.85 |
August | 67.83 | 26.84 | 514.00 | 24.54 | 67.83 | 26.84 |
September | 53.83 | 26.81 | 485.00 | 24.58 | 53.83 | 26.81 |
October | 52.83 | 26.69 | 470.33 | 24.65 | 49.83 | 26.85 |
November | 31.50 | 26.62 | 424.33 | 24.65 | 28.17 | 26.92 |
December | 45.33 | 25.97 | 354.67 | 24.80 | 31.83 | 26.89 |
Annual Sum or Average | 774.17 | 25.60 | 5126.33 | 24.61 | 484.67 | 26.85 |
Minimum of Months | 31.50 | 23.62 | 219.83 | 24.53 | 11.33 | 26.77 |
Maximum of Months | 184.00 | 26.87 | 514.00 | 24.80 | 79.50 | 26.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 434.33 | 21.81 | 84.50 | 22.35 | 43.83 | 20.82 |
February | 345.50 | 22.08 | 94.83 | 22.64 | 31.50 | 19.91 |
March | 338.00 | 22.40 | 111.83 | 23.56 | 15.83 | 20.55 |
April | 157.00 | 23.29 | 243.83 | 24.22 | 11.00 | 25.44 |
May | 32.17 | 25.43 | 506.67 | 24.34 | 32.17 | 25.43 |
June | 13.50 | 25.80 | 492.67 | 24.33 | 13.50 | 25.80 |
July | 40.83 | 25.93 | 492.33 | 24.45 | 40.83 | 25.93 |
August | 31.83 | 25.57 | 508.17 | 24.33 | 31.83 | 25.57 |
September | 40.67 | 25.01 | 453.83 | 24.32 | 40.67 | 25.01 |
October | 112.17 | 23.74 | 379.67 | 24.33 | 35.83 | 25.36 |
November | 283.00 | 22.64 | 127.00 | 24.08 | 2.17 | 23.84 |
December | 384.00 | 22.08 | 86.17 | 23.28 | 23.50 | 21.28 |
Annual Sum or Average | 2213.00 | 22.56 | 3581.50 | 24.19 | 322.67 | 23.74 |
Minimum of Months | 13.50 | 21.81 | 84.50 | 22.35 | 2.17 | 19.91 |
Maximum of Months | 434.33 | 25.93 | 508.17 | 24.45 | 43.83 | 25.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 312.17 | 22.31 | 86.33 | 23.78 | 20.17 | 21.47 |
February | 224.67 | 22.44 | 108.83 | 23.70 | 17.67 | 20.82 |
March | 206.50 | 22.63 | 156.67 | 24.29 | 12.50 | 23.46 |
April | 83.83 | 23.82 | 270.17 | 24.48 | 19.17 | 26.15 |
May | 61.67 | 26.43 | 429.83 | 24.56 | 61.67 | 26.43 |
June | 40.67 | 26.64 | 416.00 | 24.51 | 40.67 | 26.64 |
July | 69.17 | 26.71 | 420.00 | 24.67 | 69.17 | 26.71 |
August | 51.83 | 26.39 | 431.50 | 24.49 | 51.83 | 26.39 |
September | 67.33 | 26.24 | 400.83 | 24.55 | 67.33 | 26.24 |
October | 95.50 | 24.74 | 340.33 | 24.58 | 50.17 | 26.30 |
November | 173.00 | 23.08 | 173.83 | 24.47 | 6.00 | 26.07 |
December | 272.83 | 22.40 | 105.67 | 23.90 | 18.67 | 22.09 |
Annual Sum or Average | 1659.17 | 23.41 | 3340.00 | 24.47 | 435.00 | 25.70 |
Minimum of Months | 40.67 | 22.31 | 86.33 | 23.70 | 6.00 | 20.82 |
Maximum of Months | 312.17 | 26.71 | 431.50 | 24.67 | 69.17 | 26.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 237.17 | 23.04 | 216.83 | 24.59 | 40.33 | 25.54 |
February | 175.67 | 22.86 | 221.83 | 24.39 | 23.00 | 24.18 |
March | 225.83 | 22.60 | 196.50 | 24.15 | 13.33 | 22.89 |
April | 111.00 | 23.36 | 291.00 | 24.29 | 11.00 | 25.59 |
May | 32.00 | 25.42 | 506.00 | 24.34 | 32.00 | 25.42 |
June | 13.50 | 25.70 | 491.83 | 24.32 | 13.50 | 25.70 |
July | 40.00 | 25.90 | 489.67 | 24.44 | 40.00 | 25.90 |
August | 38.67 | 25.85 | 511.00 | 24.36 | 38.67 | 25.85 |
September | 65.50 | 25.93 | 475.33 | 24.42 | 65.50 | 25.93 |
October | 91.83 | 25.42 | 440.33 | 24.64 | 63.50 | 26.46 |
November | 135.67 | 24.24 | 325.17 | 24.76 | 45.00 | 26.58 |
December | 207.17 | 23.29 | 256.17 | 24.80 | 46.67 | 25.97 |
Annual Sum or Average | 1374.00 | 23.67 | 4421.67 | 24.45 | 432.50 | 25.79 |
Minimum of Months | 13.50 | 22.60 | 196.50 | 24.15 | 11.00 | 22.89 |
Maximum of Months | 237.17 | 25.93 | 511.00 | 24.80 | 65.50 | 26.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 325.33 | 22.26 | 127.83 | 23.95 | 22.67 | 22.49 |
February | 220.00 | 22.37 | 179.67 | 23.90 | 18.17 | 20.80 |
March | 220.33 | 22.71 | 221.50 | 24.17 | 15.67 | 23.40 |
April | 70.67 | 24.41 | 370.83 | 24.43 | 23.83 | 26.64 |
May | 47.33 | 26.15 | 508.00 | 24.46 | 47.33 | 26.15 |
June | 34.00 | 26.65 | 495.17 | 24.45 | 34.00 | 26.65 |
July | 67.83 | 26.57 | 497.00 | 24.58 | 67.83 | 26.57 |
August | 45.17 | 26.44 | 514.00 | 24.46 | 45.17 | 26.44 |
September | 63.17 | 26.09 | 482.00 | 24.47 | 63.17 | 26.09 |
October | 86.83 | 24.96 | 429.50 | 24.48 | 51.50 | 26.22 |
November | 174.50 | 23.17 | 242.50 | 24.34 | 9.83 | 26.22 |
December | 265.33 | 22.45 | 182.00 | 24.25 | 12.50 | 23.45 |
Annual Sum or Average | 1620.50 | 23.36 | 4250.00 | 24.40 | 411.67 | 25.70 |
Minimum of Months | 34.00 | 22.26 | 127.83 | 23.90 | 9.83 | 20.80 |
Maximum of Months | 325.33 | 26.65 | 514.00 | 24.58 | 67.83 | 26.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 446.17 | 21.34 | 166.67 | 21.23 | 128.83 | 20.41 |
February | 368.83 | 21.68 | 139.50 | 21.63 | 81.33 | 19.94 |
March | 357.17 | 22.03 | 151.17 | 22.81 | 51.67 | 20.36 |
April | 175.83 | 22.99 | 241.50 | 24.22 | 11.67 | 25.35 |
May | 48.17 | 25.66 | 501.00 | 24.37 | 48.17 | 25.66 |
June | 30.33 | 25.96 | 491.33 | 24.37 | 28.83 | 26.10 |
July | 67.00 | 26.28 | 488.33 | 24.51 | 67.00 | 26.28 |
August | 52.17 | 25.85 | 504.33 | 24.36 | 52.17 | 25.85 |
September | 67.83 | 25.33 | 445.67 | 24.37 | 65.33 | 25.40 |
October | 133.83 | 23.57 | 370.83 | 24.36 | 45.33 | 25.48 |
November | 317.33 | 22.21 | 134.33 | 23.61 | 23.33 | 21.33 |
December | 402.33 | 21.62 | 150.67 | 22.08 | 89.17 | 20.73 |
Annual Sum or Average | 2467.00 | 22.37 | 3785.33 | 23.96 | 692.83 | 22.89 |
Minimum of Months | 30.33 | 21.34 | 134.33 | 21.23 | 11.67 | 19.94 |
Maximum of Months | 446.17 | 26.28 | 504.33 | 24.51 | 128.83 | 26.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.33 | 21.87 | 143.83 | 22.31 | 75.83 | 20.53 |
February | 292.50 | 22.05 | 142.83 | 22.82 | 42.50 | 19.77 |
March | 253.67 | 22.26 | 219.17 | 23.74 | 41.17 | 21.44 |
April | 108.17 | 23.51 | 325.83 | 24.37 | 22.67 | 26.13 |
May | 68.33 | 26.41 | 506.50 | 24.48 | 68.33 | 26.41 |
June | 49.67 | 26.56 | 492.67 | 24.44 | 48.50 | 26.64 |
July | 74.00 | 26.74 | 493.50 | 24.59 | 74.00 | 26.74 |
August | 60.00 | 26.27 | 510.50 | 24.42 | 60.00 | 26.27 |
September | 78.50 | 26.11 | 466.50 | 24.47 | 77.67 | 26.14 |
October | 125.17 | 24.38 | 402.50 | 24.49 | 59.83 | 26.24 |
November | 228.00 | 22.73 | 193.67 | 24.19 | 13.67 | 23.31 |
December | 352.50 | 21.97 | 151.50 | 23.13 | 51.83 | 21.01 |
Annual Sum or Average | 2093.83 | 23.00 | 4049.00 | 24.23 | 636.00 | 24.42 |
Minimum of Months | 49.67 | 21.87 | 142.83 | 22.31 | 13.67 | 19.77 |
Maximum of Months | 403.33 | 26.74 | 510.50 | 24.59 | 77.67 | 26.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 270.83 | 22.40 | 202.67 | 23.88 | 65.67 | 22.88 |
February | 212.33 | 22.27 | 212.67 | 23.82 | 40.00 | 21.56 |
March | 265.17 | 22.28 | 207.33 | 23.64 | 41.17 | 21.42 |
April | 139.33 | 23.07 | 280.33 | 24.30 | 13.00 | 25.58 |
May | 48.67 | 25.66 | 499.50 | 24.37 | 48.67 | 25.66 |
June | 29.67 | 25.89 | 489.67 | 24.36 | 28.17 | 26.03 |
July | 66.50 | 26.25 | 487.17 | 24.50 | 66.50 | 26.25 |
August | 54.33 | 25.96 | 508.00 | 24.38 | 54.33 | 25.96 |
September | 77.50 | 25.86 | 461.17 | 24.44 | 76.33 | 25.89 |
October | 104.50 | 24.92 | 430.00 | 24.59 | 64.33 | 26.35 |
November | 174.67 | 23.52 | 290.83 | 24.65 | 40.83 | 26.24 |
December | 239.33 | 22.58 | 245.33 | 24.29 | 56.67 | 23.67 |
Annual Sum or Average | 1682.83 | 23.30 | 4314.67 | 24.34 | 595.67 | 24.85 |
Minimum of Months | 29.67 | 22.27 | 202.67 | 23.64 | 13.00 | 21.42 |
Maximum of Months | 270.83 | 26.25 | 508.00 | 24.65 | 76.33 | 26.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 359.83 | 21.84 | 154.33 | 22.83 | 68.50 | 21.03 |
February | 258.33 | 22.00 | 175.67 | 23.22 | 45.33 | 20.40 |
March | 254.17 | 22.33 | 220.33 | 23.79 | 36.33 | 21.72 |
April | 103.83 | 23.85 | 347.33 | 24.42 | 25.33 | 26.53 |
May | 57.83 | 26.16 | 508.00 | 24.47 | 57.83 | 26.16 |
June | 45.67 | 26.61 | 493.17 | 24.47 | 45.67 | 26.61 |
July | 77.33 | 26.64 | 497.00 | 24.60 | 77.33 | 26.64 |
August | 56.00 | 26.41 | 514.00 | 24.46 | 56.00 | 26.41 |
September | 75.17 | 26.06 | 479.83 | 24.47 | 75.17 | 26.06 |
October | 102.83 | 24.59 | 419.67 | 24.48 | 56.50 | 26.16 |
November | 218.33 | 22.71 | 215.00 | 24.30 | 14.00 | 25.09 |
December | 301.67 | 22.01 | 183.50 | 23.66 | 43.00 | 21.64 |
Annual Sum or Average | 1911.00 | 23.05 | 4207.83 | 24.29 | 601.00 | 24.65 |
Minimum of Months | 45.67 | 21.84 | 154.33 | 22.83 | 14.00 | 20.40 |
Maximum of Months | 359.83 | 26.64 | 514.00 | 24.60 | 77.33 | 26.64 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54764 | 38.13722 | 0.49407 | 11.02890 |
February | 454.00000 | 24.51857 | 46.53209 | 0.54330 | 12.02351 |
March | 514.00000 | 24.41550 | 45.31193 | 0.51287 | 11.28839 |
April | 485.00000 | 24.50676 | 57.04816 | 0.61472 | 13.68312 |
May | 508.00000 | 24.50788 | 64.64492 | -0.1783 | 6.89463 |
June | 496.00000 | 24.45677 | 64.58822 | -0.1925 | 6.86447 |
July | 497.00000 | 24.61410 | 63.73146 | -0.1434 | 7.07706 |
August | 514.00000 | 24.48374 | 62.08072 | -0.1775 | 6.92158 |
September | 485.00000 | 24.56057 | 62.02373 | -0.1597 | 6.96218 |
October | 502.00000 | 24.61169 | 56.34190 | 0.65493 | 15.01356 |
November | 489.00000 | 24.61550 | 47.53450 | 0.59136 | 13.21626 |
December | 497.00000 | 24.60470 | 42.70568 | 0.54983 | 12.35207 |
Annual Sum or Average | 5943.00000 | 24.53652 | 54.26936 | 0.25604 | 10.25259 |
Minimum of Months | 454.00000 | 24.41550 | 38.13722 | -0.1925 | 6.86447 |
Maximum of Months | 514.00000 | 24.61550 | 64.64492 | 0.65493 | 15.01356 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.20686 | 37.85047 | 0.41520 | 9.04316 |
February | 454.00000 | 24.26447 | 41.61863 | 0.46151 | 9.83450 |
March | 514.00000 | 24.23707 | 40.88749 | 0.45895 | 9.70632 |
April | 485.00000 | 24.20216 | 46.53705 | 0.50109 | 10.41626 |
May | 508.00000 | 24.23299 | 49.69796 | -0.3416 | 7.74293 |
June | 496.00000 | 24.15040 | 49.69346 | -0.3610 | 7.87406 |
July | 497.00000 | 24.15724 | 49.45855 | -0.3527 | 7.71084 |
August | 514.00000 | 24.12115 | 49.51575 | -0.3511 | 7.65197 |
September | 485.00000 | 24.23415 | 49.54876 | -0.3394 | 7.71187 |
October | 502.00000 | 24.27775 | 47.03393 | 0.52227 | 10.93599 |
November | 489.00000 | 24.32662 | 43.43049 | 0.50759 | 10.70164 |
December | 497.00000 | 24.30512 | 40.00928 | 0.47492 | 10.06989 |
Annual Sum or Average | 5943.00000 | 24.22574 | 45.46075 | 0.12962 | 9.10614 |
Minimum of Months | 454.00000 | 24.12115 | 37.85047 | -0.3610 | 7.65197 |
Maximum of Months | 514.00000 | 24.32662 | 49.69796 | 0.52227 | 10.93599 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.66080 | 39.95249 | 0.26551 | 7.03089 |
February | 454.00000 | 23.74767 | 43.68784 | 0.31648 | 7.68605 |
March | 514.00000 | 23.82491 | 43.02364 | 0.33746 | 7.84146 |
April | 485.00000 | 24.05731 | 47.98087 | 0.43792 | 9.26161 |
May | 508.00000 | 24.08252 | 50.45889 | -0.4110 | 8.83169 |
June | 496.00000 | 24.06006 | 50.41417 | -0.4164 | 8.88964 |
July | 497.00000 | 24.07342 | 50.34036 | -0.4153 | 8.90635 |
August | 514.00000 | 24.09465 | 50.41761 | -0.4047 | 8.69599 |
September | 485.00000 | 24.03100 | 50.55210 | -0.4295 | 9.15363 |
October | 502.00000 | 24.11042 | 48.10031 | 0.46257 | 9.72066 |
November | 489.00000 | 23.96679 | 45.35016 | 0.39634 | 8.58990 |
December | 497.00000 | 23.78132 | 42.53586 | 0.32051 | 7.72534 |
Annual Sum or Average | 5943.00000 | 23.95884 | 46.91710 | 0.03535 | 8.52979 |
Minimum of Months | 454.00000 | 23.66080 | 39.95249 | -0.4295 | 7.03089 |
Maximum of Months | 514.00000 | 24.11042 | 50.55210 | 0.46257 | 9.72066 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.67841 | 42.39234 | 0.02364 | 6.93565 |
February | 454.00000 | 23.00650 | 45.41566 | 0.13603 | 7.87168 |
March | 514.00000 | 23.40455 | 44.23614 | 0.23327 | 7.68766 |
April | 485.00000 | 23.99436 | 48.34817 | 0.42664 | 9.19112 |
May | 508.00000 | 24.17991 | 49.94189 | -0.3621 | 8.04907 |
June | 496.00000 | 24.18309 | 49.74635 | -0.3556 | 7.90930 |
July | 497.00000 | 24.23333 | 49.61028 | -0.3439 | 7.80885 |
August | 514.00000 | 24.18835 | 49.90434 | -0.3565 | 7.96398 |
September | 485.00000 | 24.12915 | 50.18182 | -0.3861 | 8.39241 |
October | 502.00000 | 24.07462 | 48.17269 | 0.45885 | 9.93802 |
November | 489.00000 | 23.56508 | 46.73825 | 0.29560 | 7.61500 |
December | 497.00000 | 23.02068 | 44.63433 | 0.13139 | 7.20093 |
Annual Sum or Average | 5943.00000 | 23.72613 | 47.45025 | -0.0103 | 8.04523 |
Minimum of Months | 454.00000 | 22.67841 | 42.39234 | -0.3861 | 6.93565 |
Maximum of Months | 514.00000 | 24.23333 | 50.18182 | 0.45885 | 9.93802 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.25959 | 39.63131 | 0.16478 | 7.13178 |
February | 454.00000 | 23.57642 | 42.11656 | 0.27051 | 7.92225 |
March | 514.00000 | 23.79684 | 41.24002 | 0.32837 | 8.22486 |
April | 485.00000 | 24.10808 | 46.17845 | 0.46919 | 9.84264 |
May | 508.00000 | 24.36868 | 49.81149 | -0.2567 | 7.12294 |
June | 496.00000 | 24.30252 | 48.78913 | -0.2642 | 6.95898 |
July | 497.00000 | 24.38692 | 48.92305 | -0.2305 | 6.92943 |
August | 514.00000 | 24.26185 | 49.05514 | -0.2661 | 7.04086 |
September | 485.00000 | 24.36758 | 50.17885 | -0.2680 | 7.34122 |
October | 502.00000 | 24.28140 | 47.54927 | 0.53096 | 11.47476 |
November | 489.00000 | 23.98799 | 43.81491 | 0.39987 | 8.86361 |
December | 497.00000 | 23.71830 | 41.18666 | 0.30137 | 7.86438 |
Annual Sum or Average | 5943.00000 | 24.03734 | 45.72509 | 0.09607 | 8.05568 |
Minimum of Months | 454.00000 | 23.25959 | 39.63131 | -0.2680 | 6.92943 |
Maximum of Months | 514.00000 | 24.38692 | 50.17885 | 0.53096 | 11.47476 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.57809 | 38.60872 | 0.25330 | 8.13659 |
February | 454.00000 | 23.75488 | 41.48002 | 0.33086 | 8.72060 |
March | 514.00000 | 23.83989 | 40.75371 | 0.36532 | 9.30219 |
April | 485.00000 | 24.11894 | 45.81384 | 0.50018 | 10.79795 |
May | 508.00000 | 24.44843 | 49.10613 | -0.1778 | 7.19563 |
June | 496.00000 | 24.34665 | 48.38290 | -0.2063 | 6.85415 |
July | 497.00000 | 24.43384 | 48.55381 | -0.1789 | 7.08832 |
August | 514.00000 | 24.26502 | 48.91051 | -0.2398 | 7.10422 |
September | 485.00000 | 24.44818 | 49.51451 | -0.2073 | 7.58563 |
October | 502.00000 | 24.34572 | 47.03400 | 0.57004 | 12.74192 |
November | 489.00000 | 24.08535 | 43.32173 | 0.44030 | 9.90606 |
December | 497.00000 | 23.66890 | 41.21095 | 0.29898 | 8.23537 |
Annual Sum or Average | 5943.00000 | 24.11307 | 45.24440 | 0.14344 | 8.63269 |
Minimum of Months | 454.00000 | 23.57809 | 38.60872 | -0.2398 | 6.85415 |
Maximum of Months | 514.00000 | 24.44843 | 49.51451 | 0.57004 | 12.74192 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.87878 | 37.21890 | 0.37320 | 10.40427 |
February | 454.00000 | 23.99390 | 40.37845 | 0.42473 | 10.79590 |
March | 514.00000 | 23.84767 | 40.61674 | 0.36813 | 9.39649 |
April | 485.00000 | 24.13133 | 45.99986 | 0.48596 | 10.30789 |
May | 508.00000 | 24.36801 | 49.80820 | -0.2550 | 7.12134 |
June | 496.00000 | 24.30128 | 48.82952 | -0.2691 | 7.05665 |
July | 497.00000 | 24.39419 | 48.90172 | -0.2287 | 6.99073 |
August | 514.00000 | 24.28308 | 48.89923 | -0.2451 | 6.94376 |
September | 485.00000 | 24.43541 | 49.66400 | -0.2128 | 7.29530 |
October | 502.00000 | 24.49234 | 46.33864 | 0.63617 | 14.65498 |
November | 489.00000 | 24.43850 | 41.95997 | 0.57747 | 13.39660 |
December | 497.00000 | 24.18601 | 39.26327 | 0.48242 | 12.18195 |
Annual Sum or Average | 5943.00000 | 24.22965 | 44.85013 | 0.17512 | 9.69460 |
Minimum of Months | 454.00000 | 23.84767 | 37.21890 | -0.2691 | 6.94376 |
Maximum of Months | 514.00000 | 24.49234 | 49.80820 | 0.63617 | 14.65498 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04834 | 37.12600 | 0.39006 | 9.60497 |
February | 454.00000 | 24.31772 | 39.60185 | 0.51091 | 11.70496 |
March | 514.00000 | 24.40230 | 38.88836 | 0.55690 | 12.50575 |
April | 485.00000 | 24.58908 | 44.10966 | 0.70400 | 16.35940 |
May | 508.00000 | 24.54934 | 48.63456 | -0.1048 | 6.86853 |
June | 496.00000 | 24.52002 | 47.56646 | -0.0712 | 6.66629 |
July | 497.00000 | 24.65851 | 47.36494 | -0.0061 | 7.01500 |
August | 514.00000 | 24.53132 | 47.38001 | -0.0062 | 6.58945 |
September | 485.00000 | 24.56605 | 48.73890 | -0.1073 | 7.16308 |
October | 502.00000 | 24.59872 | 45.76392 | 0.69001 | 16.09033 |
November | 489.00000 | 24.55115 | 41.55674 | 0.62048 | 14.01474 |
December | 497.00000 | 24.56922 | 38.15751 | 0.59231 | 13.61391 |
Annual Sum or Average | 5943.00000 | 24.49232 | 43.76387 | 0.31177 | 10.65756 |
Minimum of Months | 454.00000 | 24.04834 | 37.12600 | -0.1073 | 6.58945 |
Maximum of Months | 514.00000 | 24.65851 | 48.73890 | 0.70400 | 16.35940 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.08329 | 43.00771 | -0.1240 | 7.65960 |
February | 454.00000 | 22.51096 | 45.22556 | 0.00718 | 8.04939 |
March | 514.00000 | 22.92982 | 44.22136 | 0.10995 | 7.45457 |
April | 485.00000 | 23.80597 | 48.89237 | 0.38062 | 8.79686 |
May | 508.00000 | 24.32477 | 52.00526 | -0.2774 | 7.32487 |
June | 496.00000 | 24.31614 | 50.58808 | -0.2721 | 7.18008 |
July | 497.00000 | 24.43160 | 51.79589 | -0.2286 | 7.24030 |
August | 514.00000 | 24.31829 | 52.04867 | -0.2710 | 7.32629 |
September | 485.00000 | 24.28056 | 53.30121 | -0.3022 | 7.69691 |
October | 502.00000 | 24.07443 | 50.87310 | 0.48068 | 10.93632 |
November | 489.00000 | 23.20370 | 46.96881 | 0.20158 | 7.26175 |
December | 497.00000 | 22.49015 | 45.43024 | 0.00014 | 7.39644 |
Annual Sum or Average | 5943.00000 | 23.57112 | 48.71391 | -0.0258 | 7.85701 |
Minimum of Months | 454.00000 | 22.08329 | 43.00771 | -0.3022 | 7.18008 |
Maximum of Months | 514.00000 | 24.43160 | 53.30121 | 0.48068 | 10.93632 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.83393 | 41.08791 | 0.06184 | 7.73563 |
February | 385.00000 | 23.14775 | 42.95257 | 0.16744 | 8.24372 |
March | 433.00000 | 23.45511 | 41.94020 | 0.25297 | 8.98113 |
April | 410.00000 | 24.16685 | 47.12721 | 0.49363 | 11.20101 |
May | 430.00000 | 24.56601 | 50.68621 | -0.1472 | 7.49609 |
June | 418.00000 | 24.50928 | 49.52084 | -0.1640 | 7.11215 |
July | 422.00000 | 24.67038 | 50.54049 | -0.1080 | 7.63455 |
August | 433.00000 | 24.49522 | 51.08014 | -0.1756 | 7.26328 |
September | 410.00000 | 24.53918 | 51.95446 | -0.1858 | 8.00600 |
October | 427.00000 | 24.35874 | 49.55061 | 0.57051 | 13.49009 |
November | 417.00000 | 23.77083 | 44.66677 | 0.34736 | 8.99491 |
December | 422.00000 | 23.01654 | 43.84551 | 0.12982 | 7.99162 |
Annual Sum or Average | 5034.00000 | 23.96498 | 47.09821 | 0.10259 | 8.67843 |
Minimum of Months | 385.00000 | 22.83393 | 41.08791 | -0.1858 | 7.11215 |
Maximum of Months | 433.00000 | 24.67038 | 51.95446 | 0.57051 | 13.49009 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.65242 | 38.38296 | 0.31771 | 10.46717 |
February | 454.00000 | 23.72184 | 41.42068 | 0.35453 | 10.65981 |
March | 514.00000 | 23.44982 | 42.26883 | 0.26404 | 8.85097 |
April | 485.00000 | 23.96380 | 48.13178 | 0.43264 | 9.69832 |
May | 508.00000 | 24.32766 | 51.96192 | -0.2735 | 7.30598 |
June | 496.00000 | 24.30363 | 50.70041 | -0.2815 | 7.27299 |
July | 497.00000 | 24.42715 | 51.81945 | -0.2309 | 7.26631 |
August | 514.00000 | 24.34587 | 51.75980 | -0.2459 | 7.19067 |
September | 485.00000 | 24.39795 | 52.29935 | -0.2262 | 7.53225 |
October | 502.00000 | 24.49395 | 48.46020 | 0.63897 | 15.12480 |
November | 489.00000 | 24.31210 | 42.96799 | 0.53953 | 13.15099 |
December | 497.00000 | 23.91138 | 40.98589 | 0.40972 | 12.14806 |
Annual Sum or Average | 5943.00000 | 24.11031 | 46.79787 | 0.13878 | 9.70681 |
Minimum of Months | 454.00000 | 23.44982 | 38.38296 | -0.2815 | 7.19067 |
Maximum of Months | 514.00000 | 24.49395 | 52.29935 | 0.63897 | 15.12480 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.90393 | 40.64265 | 0.09346 | 8.05445 |
February | 454.00000 | 23.27211 | 42.79864 | 0.21742 | 9.21788 |
March | 514.00000 | 23.51273 | 42.24491 | 0.27976 | 9.01006 |
April | 485.00000 | 24.23026 | 47.05890 | 0.53215 | 11.93442 |
May | 508.00000 | 24.44304 | 51.05707 | -0.1809 | 7.06811 |
June | 496.00000 | 24.44095 | 49.71290 | -0.1673 | 6.99792 |
July | 497.00000 | 24.57357 | 50.70191 | -0.1252 | 7.30943 |
August | 514.00000 | 24.44307 | 50.81766 | -0.1606 | 6.94078 |
September | 485.00000 | 24.45146 | 51.94511 | -0.1889 | 7.49004 |
October | 502.00000 | 24.33557 | 49.25634 | 0.58615 | 13.49566 |
November | 489.00000 | 23.79952 | 44.79285 | 0.37218 | 9.29588 |
December | 497.00000 | 23.25464 | 43.06793 | 0.20753 | 8.58539 |
Annual Sum or Average | 5943.00000 | 23.97578 | 47.03229 | 0.12041 | 8.77161 |
Minimum of Months | 454.00000 | 22.90393 | 40.64265 | -0.1889 | 6.94078 |
Maximum of Months | 514.00000 | 24.57357 | 51.94511 | 0.58615 | 13.49566 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.62541 | 44.35101 | -0.2579 | 9.67394 |
February | 454.00000 | 22.09311 | 46.42639 | -0.1051 | 9.65504 |
March | 514.00000 | 22.62477 | 45.01667 | 0.02999 | 8.43059 |
April | 485.00000 | 23.67726 | 49.43308 | 0.35605 | 8.91328 |
May | 508.00000 | 24.35304 | 52.22513 | -0.2494 | 7.28920 |
June | 496.00000 | 24.35294 | 50.63829 | -0.2387 | 7.13270 |
July | 497.00000 | 24.48481 | 51.84175 | -0.1898 | 7.37357 |
August | 514.00000 | 24.33891 | 52.28924 | -0.2448 | 7.32006 |
September | 485.00000 | 24.30934 | 53.74447 | -0.2775 | 7.85323 |
October | 502.00000 | 23.99342 | 51.45870 | 0.46943 | 11.36114 |
November | 489.00000 | 22.82268 | 48.08735 | 0.10730 | 7.58864 |
December | 497.00000 | 22.05803 | 46.86486 | -0.1200 | 8.72260 |
Annual Sum or Average | 5943.00000 | 23.40337 | 49.37729 | -0.0606 | 8.43378 |
Minimum of Months | 454.00000 | 21.62541 | 44.35101 | -0.2775 | 7.13270 |
Maximum of Months | 514.00000 | 24.48481 | 53.74447 | 0.46943 | 11.36114 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.30952 | 42.66896 | -0.0752 | 8.54526 |
February | 454.00000 | 22.74418 | 44.52503 | 0.07145 | 9.09647 |
March | 514.00000 | 23.21418 | 42.98150 | 0.19836 | 9.42555 |
April | 485.00000 | 24.01721 | 47.65744 | 0.47777 | 11.08017 |
May | 508.00000 | 24.46744 | 50.88380 | -0.1420 | 7.34274 |
June | 496.00000 | 24.42499 | 49.69545 | -0.1483 | 6.96908 |
July | 497.00000 | 24.57105 | 50.60914 | -0.0982 | 7.55296 |
August | 514.00000 | 24.40501 | 51.26069 | -0.1660 | 7.12369 |
September | 485.00000 | 24.43493 | 52.27310 | -0.1872 | 7.98566 |
October | 502.00000 | 24.20237 | 49.92106 | 0.55255 | 13.38904 |
November | 489.00000 | 23.48351 | 45.93948 | 0.28180 | 8.60978 |
December | 497.00000 | 22.58381 | 45.37706 | 0.01788 | 8.58958 |
Annual Sum or Average | 5943.00000 | 23.74458 | 47.83254 | 0.06425 | 8.80260 |
Minimum of Months | 454.00000 | 22.30952 | 42.66896 | -0.1872 | 6.96908 |
Maximum of Months | 514.00000 | 24.57105 | 52.27310 | 0.55255 | 13.38904 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.21257 | 39.75474 | 0.18963 | 10.36020 |
February | 454.00000 | 23.29995 | 42.60204 | 0.24222 | 10.74027 |
March | 514.00000 | 23.15235 | 43.13504 | 0.18623 | 9.39001 |
April | 485.00000 | 23.83344 | 48.71346 | 0.40790 | 9.76354 |
May | 508.00000 | 24.35320 | 52.19699 | -0.2465 | 7.28246 |
June | 496.00000 | 24.33983 | 50.75733 | -0.2482 | 7.21251 |
July | 497.00000 | 24.47768 | 51.87759 | -0.1930 | 7.38988 |
August | 514.00000 | 24.35930 | 52.02395 | -0.2221 | 7.20288 |
September | 485.00000 | 24.40005 | 52.79415 | -0.2097 | 7.73706 |
October | 502.00000 | 24.37787 | 49.13123 | 0.61985 | 15.03143 |
November | 489.00000 | 23.99884 | 43.92653 | 0.45854 | 12.18206 |
December | 497.00000 | 23.46628 | 42.44484 | 0.28856 | 11.51652 |
Annual Sum or Average | 5943.00000 | 23.94251 | 47.47687 | 0.10389 | 9.63648 |
Minimum of Months | 454.00000 | 23.15235 | 39.75474 | -0.2482 | 7.20288 |
Maximum of Months | 514.00000 | 24.47768 | 52.79415 | 0.61985 | 15.03143 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.47743 | 41.90020 | -0.0245 | 8.99816 |
February | 454.00000 | 22.89748 | 43.88237 | 0.12031 | 9.98018 |
March | 514.00000 | 23.22163 | 43.05427 | 0.20685 | 9.45799 |
April | 485.00000 | 24.11193 | 47.62552 | 0.51014 | 11.86996 |
May | 508.00000 | 24.45485 | 51.34232 | -0.1593 | 7.12498 |
June | 496.00000 | 24.45200 | 49.84896 | -0.1432 | 7.06720 |
July | 497.00000 | 24.59069 | 50.84641 | -0.0988 | 7.49005 |
August | 514.00000 | 24.44937 | 51.10706 | -0.1404 | 6.99964 |
September | 485.00000 | 24.45477 | 52.46697 | -0.1729 | 7.69359 |
October | 502.00000 | 24.26000 | 49.83678 | 0.57588 | 13.70580 |
November | 489.00000 | 23.49307 | 45.71888 | 0.29618 | 9.12168 |
December | 497.00000 | 22.84770 | 44.40179 | 0.09992 | 9.03560 |
Annual Sum or Average | 5943.00000 | 23.81485 | 47.68975 | 0.08793 | 9.03155 |
Minimum of Months | 454.00000 | 22.47743 | 41.90020 | -0.1729 | 6.99964 |
Maximum of Months | 514.00000 | 24.59069 | 52.46697 | 0.57588 | 13.70580 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.715399E+11 | 193931.73 | 31-JAN-14:30 | 288.81 | 0.429517E+12 | 0.00 | 0.501057E+12 | 1.93 | 7.53 | 19-JAN-06:04 | 0.00 | 0.00 |
February | 0.921247E+11 | 191015.18 | 02-FEB-13:30 | 330.80 | 0.577349E+12 | 0.00 | 0.669474E+12 | 2.68 | 7.45 | 03-FEB-06:05 | 0.00 | 0.00 |
March | 0.112382E+12 | 193944.22 | 06-MAR-11:40 | 420.41 | 0.701037E+12 | 0.00 | 0.813419E+12 | 2.96 | 7.56 | 24-MAR-15:20 | 0.00 | 0.00 |
April | 0.164516E+12 | 199247.81 | 28-APR-10:50 | 551.42 | 0.109500E+13 | 0.00 | 0.125951E+13 | 4.30 | 7.51 | 12-APR-14:50 | 0.00 | 0.00 |
May | 0.221174E+12 | 209347.67 | 24-MAY-11:10 | 542.30 | 0.148164E+13 | 0.00 | 0.170281E+13 | 4.62 | 7.51 | 12-MAY-04:13 | 0.00 | 0.00 |
June | 0.223301E+12 | 208627.74 | 27-JUN-09:20 | 594.17 | 0.146707E+13 | 0.00 | 0.169038E+13 | 4.92 | 7.52 | 08-JUN-04:13 | 0.00 | 0.00 |
July | 0.233369E+12 | 214216.05 | 03-JUL-16:10 | 661.27 | 0.148849E+13 | 0.00 | 0.172186E+13 | 5.00 | 7.28 | 12-JUL-04:13 | 0.00 | 0.00 |
August | 0.237673E+12 | 210023.64 | 09-AUG-17:50 | 680.12 | 0.153563E+13 | 0.00 | 0.177330E+13 | 5.14 | 7.45 | 17-AUG-04:13 | 0.00 | 0.00 |
September | 0.217885E+12 | 209005.93 | 09-SEP-15:10 | 540.76 | 0.144306E+13 | 0.00 | 0.166094E+13 | 4.65 | 7.51 | 23-SEP-04:13 | 0.00 | 0.00 |
October | 0.192416E+12 | 210393.75 | 07-OCT-07:50 | 557.24 | 0.125396E+13 | 0.00 | 0.144637E+13 | 4.35 | 7.51 | 03-OCT-04:13 | 0.00 | 0.00 |
November | 0.131124E+12 | 204863.11 | 01-NOV-13:50 | 458.43 | 0.818180E+12 | 0.00 | 0.949304E+12 | 3.43 | 7.52 | 08-NOV-05:13 | 0.00 | 0.00 |
December | 0.945657E+11 | 195955.62 | 12-DEC-15:40 | 380.26 | 0.583161E+12 | 0.00 | 0.677726E+12 | 2.56 | 7.50 | 11-DEC-06:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.199207E+13 | 6006.00 | 0.128741E+14 | 0.148662E+14 | 3.88 | |||||||
Minimum of Months | 0.715399E+11 | 191015.18 | 288.81 | 0.429517E+12 | 0.00 | 0.501057E+12 | 1.93 | 7.28 | 0.00 | 0.00 | ||
Maximum of Months | 0.237673E+12 | 214216.05 | 680.12 | 0.153563E+13 | 0.00 | 0.177330E+13 | 5.14 | 7.56 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.333656E+10 | 129886.09 | 19-JAN-15:05 | 8.58 | 0.232116E+11 | 0.00 | 0.265481E+11 | 0.08 | 7.16 | 02-JAN-11:40 | 0.00 | 0.00 |
February | 0.823166E+10 | 126143.20 | 24-FEB-11:05 | 22.58 | 0.573764E+11 | 0.00 | 0.656081E+11 | 0.23 | 7.17 | 27-FEB-11:00 | 0.00 | 0.00 |
March | 0.881852E+10 | 125517.69 | 07-MAR-14:05 | 23.17 | 0.607097E+11 | 0.00 | 0.695282E+11 | 0.21 | 7.13 | 17-MAR-14:05 | 0.00 | 0.00 |
April | 0.144690E+11 | 137292.95 | 28-APR-14:05 | 38.08 | 0.991410E+11 | 0.00 | 0.113610E+12 | 0.36 | 7.19 | 19-APR-15:40 | 0.00 | 0.00 |
May | 0.502240E+11 | 184838.06 | 23-MAY-05:03 | 124.82 | 0.336411E+12 | 0.00 | 0.386635E+12 | 1.12 | 7.08 | 23-MAY-05:01 | 0.00 | 0.00 |
June | 0.586229E+11 | 160396.69 | 27-JUN-10:05 | 145.08 | 0.385835E+12 | 0.00 | 0.444458E+12 | 1.32 | 7.09 | 12-JUN-12:30 | 0.00 | 0.00 |
July | 0.665956E+11 | 171628.65 | 05-JUL-12:05 | 161.40 | 0.431418E+12 | 0.00 | 0.498014E+12 | 1.40 | 7.13 | 25-JUL-05:02 | 0.00 | 0.00 |
August | 0.723542E+11 | 157462.13 | 07-AUG-12:05 | 177.04 | 0.472260E+12 | 0.00 | 0.544614E+12 | 1.55 | 7.20 | 01-AUG-05:02 | 0.00 | 0.00 |
September | 0.521180E+11 | 165835.66 | 01-SEP-12:05 | 129.58 | 0.345167E+12 | 0.00 | 0.397285E+12 | 1.19 | 7.06 | 21-SEP-09:00 | 0.00 | 0.00 |
October | 0.475231E+11 | 165528.66 | 24-OCT-05:02 | 118.30 | 0.314577E+12 | 0.00 | 0.362100E+12 | 1.05 | 7.23 | 02-OCT-09:50 | 0.00 | 0.00 |
November | 0.149861E+11 | 141939.72 | 03-NOV-12:05 | 37.75 | 0.100815E+12 | 0.00 | 0.115801E+12 | 0.35 | 7.12 | 10-NOV-15:05 | 0.00 | 0.00 |
December | 0.935461E+10 | 137301.04 | 13-DEC-11:05 | 23.58 | 0.638847E+11 | 0.00 | 0.732393E+11 | 0.22 | 7.20 | 08-DEC-16:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.406634E+12 | 1009.97 | 0.269081E+13 | 0.309744E+13 | 0.76 | |||||||
Minimum of Months | 0.333656E+10 | 125517.69 | 8.58 | 0.232116E+11 | 0.00 | 0.265481E+11 | 0.08 | 7.06 | 0.00 | 0.00 | ||
Maximum of Months | 0.723542E+11 | 184838.06 | 177.04 | 0.472260E+12 | 0.00 | 0.544614E+12 | 1.55 | 7.23 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.386254E+11 | 744.00 | 43776.24 | 01-JAN-08:45 | 257322.13 | 31-JAN-13:00 | 20.75 | 19.30 | 13.96 |
February | 0.569727E+11 | 672.00 | 43776.24 | 01-FEB-00:10 | 400129.35 | 24-FEB-10:30 | 23.92 | 20.21 | 13.96 |
March | 0.770088E+11 | 744.00 | 43776.24 | 01-MAR-00:10 | 511960.63 | 29-MAR-08:40 | 27.30 | 21.78 | 13.97 |
April | 0.109894E+12 | 720.00 | 43776.24 | 01-APR-00:10 | 656866.51 | 28-APR-17:20 | 36.85 | 25.98 | 13.97 |
May | 0.117250E+12 | 744.00 | 43776.24 | 01-MAY-00:01 | 487756.40 | 01-MAY-00:01 | 32.37 | 28.51 | 13.97 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:10 | 377962.96 | 29-JUN-14:05 | 37.20 | 30.44 | 13.97 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:05 | 526015.55 | 21-JUL-16:10 | 41.78 | 32.05 | 13.97 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:10 | 677091.94 | 06-AUG-15:11 | 45.42 | 32.80 | 13.97 |
September | 0.113468E+12 | 720.00 | 43776.24 | 01-SEP-00:05 | 333017.41 | 01-SEP-00:05 | 31.73 | 27.85 | 13.97 |
October | 0.109527E+12 | 744.00 | 43776.24 | 01-OCT-00:10 | 370291.68 | 31-OCT-11:00 | 32.88 | 26.96 | 13.97 |
November | 0.833565E+11 | 720.00 | 43776.24 | 01-NOV-00:10 | 498953.85 | 03-NOV-14:05 | 28.45 | 22.76 | 13.97 |
December | 0.715435E+11 | 744.00 | 43776.24 | 01-DEC-10:00 | 641256.47 | 13-DEC-17:10 | 28.69 | 21.89 | 13.96 |
Annual Sum or Average | 0.112561E+13 | 8760.00 | 32.33 | 25.91 | 13.96 | ||||
Minimum of Months | 0.386254E+11 | 672.00 | 43776.24 | 257322.13 | 20.75 | 19.30 | 13.96 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 677091.94 | 45.42 | 32.80 | 13.97 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.571770E+10 | 219.70 | 19996.15 | 01-JAN-16:22 | 1222406.23 | 20-JAN-04:01 | 22.18 | 21.42 | 19.23 |
February | 0.819897E+10 | 285.96 | 19996.15 | 01-FEB-11:50 | 1187240.07 | 10-FEB-16:10 | 22.83 | 21.70 | 25.27 |
March | 0.105434E+11 | 351.18 | 19996.15 | 06-MAR-08:65 | 1240281.10 | 24-MAR-14:40 | 22.86 | 21.63 | 27.79 |
April | 0.207532E+11 | 489.39 | 19996.15 | 01-APR-03:01 | 1349808.39 | 18-APR-13:50 | 23.96 | 22.03 | 37.99 |
May | 0.388712E+11 | 542.30 | 19996.15 | 01-MAY-01:01 | 1061114.58 | 26-MAY-15:10 | 27.49 | 25.10 | 32.79 |
June | 0.419411E+11 | 594.17 | 19996.15 | 01-JUN-03:01 | 1043347.25 | 07-JUN-03:02 | 27.54 | 25.07 | 38.31 |
July | 0.476024E+11 | 661.27 | 19996.15 | 01-JUL-00:05 | 1064142.12 | 24-JUL-12:05 | 28.31 | 25.86 | 40.40 |
August | 0.482387E+11 | 679.57 | 19996.15 | 01-AUG-00:10 | 1083528.09 | 30-AUG-12:05 | 27.80 | 25.28 | 42.99 |
September | 0.388615E+11 | 540.76 | 19996.15 | 01-SEP-00:05 | 1072185.30 | 11-SEP-12:05 | 28.06 | 25.65 | 32.93 |
October | 0.311467E+11 | 539.45 | 19996.15 | 02-OCT-08:30 | 1333881.66 | 26-OCT-15:10 | 25.99 | 23.88 | 36.65 |
November | 0.139766E+11 | 409.47 | 19996.15 | 01-NOV-03:01 | 1217133.31 | 13-NOV-15:30 | 23.60 | 22.10 | 32.70 |
December | 0.997260E+10 | 305.47 | 19996.15 | 08-DEC-10:40 | 1063013.39 | 08-DEC-10:50 | 22.64 | 21.61 | 25.09 |
Annual Sum or Average | 0.315824E+12 | 5618.68 | 25.29 | 23.46 | 32.71 | ||||
Minimum of Months | 0.571770E+10 | 219.70 | 19996.15 | 1043347.25 | 22.18 | 21.42 | 19.23 | ||
Maximum of Months | 0.482387E+11 | 679.57 | 19996.15 | 1349808.39 | 28.31 | 25.86 | 42.99 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.308341E+10 | 42.83 | 19996.15 | 02-JAN-10:20 | 962347.36 | 19-JAN-15:05 | 22.18 | 21.93 | 2.22 |
February | 0.432517E+10 | 60.08 | 19996.15 | 01-FEB-13:10 | 954676.72 | 27-FEB-13:05 | 22.83 | 22.44 | 3.82 |
March | 0.581128E+10 | 80.73 | 19996.15 | 06-MAR-09:00 | 984395.55 | 28-MAR-12:05 | 22.86 | 22.40 | 4.42 |
April | 0.106777E+11 | 148.47 | 19996.15 | 04-APR-12:30 | 1009004.29 | 27-APR-09:05 | 23.96 | 23.09 | 8.26 |
May | 0.298208E+11 | 414.26 | 19996.15 | 01-MAY-03:22 | 1061114.58 | 26-MAY-15:10 | 27.49 | 25.39 | 23.06 |
June | 0.303905E+11 | 422.17 | 19996.15 | 01-JUN-06:20 | 1030057.54 | 26-JUN-10:05 | 27.54 | 25.37 | 24.80 |
July | 0.354505E+11 | 492.46 | 19996.15 | 01-JUL-03:10 | 1064142.12 | 24-JUL-12:05 | 28.31 | 26.00 | 27.56 |
August | 0.340642E+11 | 473.20 | 19996.15 | 01-AUG-04:08 | 1083528.09 | 30-AUG-12:05 | 27.80 | 25.48 | 27.25 |
September | 0.317496E+11 | 441.05 | 19996.15 | 01-SEP-04:18 | 1072185.30 | 11-SEP-12:05 | 28.06 | 25.84 | 25.10 |
October | 0.217790E+11 | 302.54 | 19996.15 | 02-OCT-08:50 | 1044185.36 | 05-OCT-12:05 | 25.99 | 24.46 | 17.63 |
November | 0.733253E+10 | 101.86 | 19996.15 | 01-NOV-05:06 | 1026822.86 | 03-NOV-10:05 | 23.60 | 23.03 | 6.07 |
December | 0.541336E+10 | 75.20 | 19996.15 | 08-DEC-11:05 | 983904.40 | 15-DEC-15:05 | 22.64 | 22.23 | 4.21 |
Annual Sum or Average | 0.219898E+12 | 3054.87 | 25.29 | 23.98 | 14.60 | ||||
Minimum of Months | 0.308341E+10 | 42.83 | 19996.15 | 954676.72 | 22.18 | 21.93 | 2.22 | ||
Maximum of Months | 0.354505E+11 | 492.46 | 19996.15 | 1083528.09 | 28.31 | 26.00 | 27.56 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.172188E+11 | 0.00 | 180.99 | 1418196.62 | 09-JAN-03:07 | 0.00 | 59.23 | 65.45 | 0.07 | 0.00 | 0.01 | 1.20 | 09-JAN-03:07 |
February | 0.906830E+10 | 0.00 | 97.99 | 1010333.12 | 17-FEB-06:03 | 0.00 | 58.81 | 62.97 | 0.04 | 0.00 | 0.00 | 0.85 | 17-FEB-06:03 |
March | 0.783522E+10 | 0.00 | 73.79 | 1019463.79 | 11-MAR-06:03 | 0.00 | 59.36 | 61.81 | 0.03 | 0.00 | 0.00 | 0.86 | 11-MAR-06:03 |
April | 0.842720E+09 | 0.00 | 9.19 | 317145.69 | 02-APR-23:07 | 0.00 | 72.84 | 72.97 | 0.01 | 0.00 | 0.00 | 0.27 | 02-APR-23:07 |
May | 0.170557E+10 | 0.00 | 2.26 | 214727.95 | 29-MAY-22:40 | 0.00 | 72.89 | 72.92 | 0.02 | 0.00 | 0.00 | 0.18 | 29-MAY-22:40 |
June | 0.149431E+10 | 0.00 | 1.96 | 214111.68 | 03-JUN-03:50 | 0.00 | 72.77 | 72.79 | 0.01 | 0.00 | 0.00 | 0.18 | 03-JUN-03:50 |
July | 0.163120E+10 | 0.00 | 2.14 | 214334.32 | 04-JUL-20:20 | 0.00 | 72.74 | 72.77 | 0.02 | 0.00 | 0.00 | 0.18 | 04-JUL-20:20 |
August | 0.915645E+09 | 0.00 | 1.20 | 212822.21 | 30-AUG-03:47 | 0.00 | 72.77 | 72.78 | 0.01 | 0.00 | 0.00 | 0.18 | 30-AUG-03:47 |
September | 0.156355E+10 | 0.00 | 2.04 | 214970.05 | 04-SEP-20:50 | 0.00 | 72.73 | 72.76 | 0.02 | 0.00 | 0.00 | 0.18 | 04-SEP-20:50 |
October | 0.193892E+10 | 0.00 | 8.46 | 265228.99 | 29-OCT-13:50 | 0.00 | 72.58 | 72.69 | 0.02 | 0.00 | 0.00 | 0.22 | 29-OCT-13:50 |
November | 0.221023E+10 | 0.00 | 35.51 | 503164.48 | 19-NOV-12:37 | 0.00 | 69.68 | 70.43 | 0.02 | 0.00 | 0.00 | 0.43 | 19-NOV-12:37 |
December | 0.119305E+11 | 0.00 | 138.80 | 991786.13 | 20-DEC-06:02 | 0.00 | 60.83 | 65.71 | 0.05 | 0.00 | 0.00 | 0.84 | 20-DEC-06:02 |
Annual Sum or Average | 0.583549E+11 | 554.32 | 68.14 | 69.70 | 0.03 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.842720E+09 | 0.00 | 1.20 | 212822.21 | 0.00 | 58.81 | 61.81 | 0.01 | 0.00 | 0.00 | 0.18 | ||
Maximum of Months | 0.172188E+11 | 0.00 | 180.99 | 1418196.62 | 0.00 | 72.89 | 72.97 | 0.07 | 0.00 | 0.01 | 1.20 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 20.75 | 20.75 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 23.92 | 23.92 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.30 | 27.30 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 36.85 | 36.85 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 32.37 | 32.37 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 37.20 | 37.20 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 41.78 | 41.78 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 45.42 | 45.42 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 31.73 | 31.73 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 32.88 | 32.88 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 28.45 | 28.45 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 28.69 | 28.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 32.33 | 32.33 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.75 | 20.75 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 | 45.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.234518E+11 | 0.00 | 157.62 | 0.179693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140607.25 | 16-JAN-11:28 | 115543.08 | 16-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.273129E+11 | 0.00 | 198.98 | 0.216786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144421.93 | 20-FEB-12:30 | 115258.58 | 20-FEB-12:30 | 0.00 | 0.00 | 0.00 |
March | 0.367363E+11 | 0.00 | 250.97 | 0.314359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161373.10 | 07-MAR-04:01 | 114708.34 | 06-MAR-03:52 | 0.00 | 0.00 | 0.00 |
April | 0.569252E+11 | 0.00 | 360.00 | 0.498734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 166033.79 | 29-APR-03:01 | 111124.68 | 24-APR-03:53 | 0.00 | 0.00 | 0.00 |
May | 0.106281E+12 | 0.00 | 456.28 | 0.831457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188472.68 | 21-MAY-21:31 | 115051.09 | 29-MAY-12:30 | 0.00 | 0.00 | 0.00 |
June | 0.110376E+12 | 0.00 | 444.64 | 0.837752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 187816.31 | 18-JUN-21:21 | 113719.46 | 12-JUN-02:22 | 0.00 | 0.00 | 0.00 |
July | 0.120105E+12 | 0.00 | 455.54 | 0.863210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192861.26 | 02-JUL-15:40 | 117015.43 | 04-JUL-19:30 | 0.00 | 0.00 | 0.00 |
August | 0.129906E+12 | 0.00 | 487.36 | 0.954257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 189887.40 | 06-AUG-11:32 | 112675.70 | 06-AUG-22:52 | 0.00 | 0.00 | 0.00 |
September | 0.113197E+12 | 0.00 | 460.42 | 0.837496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 187128.35 | 17-SEP-09:40 | 118871.14 | 04-SEP-12:50 | 0.00 | 0.00 | 0.00 |
October | 0.983517E+11 | 0.00 | 439.27 | 0.766437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 187766.70 | 08-OCT-11:51 | 113988.50 | 22-OCT-23:12 | 0.00 | 0.00 | 0.00 |
November | 0.552133E+11 | 0.00 | 325.02 | 0.461215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169753.03 | 11-NOV-14:52 | 110968.78 | 05-NOV-22:33 | 0.00 | 0.00 | 0.00 |
December | 0.361559E+11 | 0.00 | 223.25 | 0.298053E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160770.60 | 15-DEC-05:11 | 119516.02 | 31-DEC-20:21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.914013E+12 | 4259.35 | 0.705945E+12 | ||||||||||||
Minimum of Months | 0.234518E+11 | 0.00 | 157.62 | 0.179693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140607.25 | 110968.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.129906E+12 | 0.00 | 487.36 | 0.954257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192861.26 | 119516.02 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.410183E+11 | 0.00 | 274.35 | 0.310617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145357.69 | 30-JAN-06:01 | 117602.85 | 19-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.582290E+11 | 0.00 | 322.16 | 0.427584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148390.63 | 28-FEB-05:11 | 135535.45 | 28-FEB-05:11 | 0.00 | 0.00 | 0.00 |
March | 0.722455E+11 | 0.00 | 410.12 | 0.574066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158266.94 | 07-MAR-05:11 | 137788.86 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.115444E+12 | 0.00 | 538.77 | 0.921142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167870.99 | 18-APR-14:50 | 167870.99 | 18-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.144738E+12 | 0.00 | 510.84 | 0.111716E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 197306.34 | 23-MAY-03:01 | 145937.55 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.156274E+12 | 0.00 | 571.02 | 0.123610E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 171970.42 | 28-JUN-05:02 | 148867.77 | 28-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.169299E+12 | 0.00 | 622.23 | 0.131966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 186193.81 | 03-JUL-05:02 | 151189.04 | 03-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.184129E+12 | 0.00 | 651.35 | 0.144817E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 173358.48 | 07-AUG-05:03 | 149103.20 | 14-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.145260E+12 | 0.00 | 502.47 | 0.105950E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 200981.95 | 13-SEP-04:11 | 145470.02 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.136556E+12 | 0.00 | 527.55 | 0.107489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 177326.40 | 21-OCT-04:11 | 142557.75 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 |
November | 0.876655E+11 | 0.00 | 442.41 | 0.711021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 164794.16 | 01-NOV-04:11 | 138807.60 | 01-NOV-04:11 | 0.00 | 0.00 | 0.00 |
December | 0.652578E+11 | 0.00 | 361.13 | 0.516044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152137.66 | 11-DEC-06:02 | 137800.78 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137612E+13 | 5734.39 | 0.107160E+13 | ||||||||||||
Minimum of Months | 0.410183E+11 | 0.00 | 274.35 | 0.310617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145357.69 | 117602.85 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.184129E+12 | 0.00 | 651.35 | 0.144817E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 200981.95 | 167870.99 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.324027E+12 | 0.00 | 261.09 | 0.238106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1197050.18 | 19-JAN-06:04 | 905491.82 | 19-JAN-06:04 | 0.00 | 0.00 | 0.00 |
February | 0.456705E+12 | 0.00 | 299.85 | 0.321633E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1290152.55 | 03-FEB-05:11 | 1030211.08 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.540026E+12 | 0.00 | 364.26 | 0.407088E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1418892.22 | 27-MAR-05:02 | 1150204.00 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.837535E+12 | 0.00 | 414.01 | 0.627183E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1606311.37 | 29-APR-05:03 | 1260854.93 | 29-APR-04:11 | 0.00 | 0.00 | 0.00 |
May | 0.130905E+13 | 0.00 | 478.27 | 0.967001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2241229.52 | 23-MAY-05:02 | 1361786.51 | 23-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.133158E+13 | 0.00 | 481.53 | 0.995584E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1915320.31 | 08-JUN-04:11 | 1329233.58 | 16-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.138134E+13 | 0.00 | 492.31 | 0.988039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2051565.76 | 25-JUL-05:02 | 1377851.96 | 25-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.143464E+13 | 0.00 | 496.03 | 0.102814E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2056590.86 | 16-AUG-04:11 | 1360166.69 | 01-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.128848E+13 | 0.00 | 463.48 | 0.883055E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2234216.82 | 05-SEP-04:11 | 1363447.55 | 02-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.113187E+13 | 0.00 | 449.12 | 0.836754E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2102587.54 | 21-OCT-04:11 | 1383623.05 | 14-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.662167E+12 | 0.00 | 392.46 | 0.512324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1557079.52 | 02-NOV-04:11 | 1259760.46 | 03-NOV-05:03 | 0.00 | 0.00 | 0.00 |
December | 0.463392E+12 | 0.00 | 299.89 | 0.340239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1550630.66 | 11-DEC-06:01 | 1217302.23 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111608E+14 | 4892.29 | 0.814515E+13 | ||||||||||||
Minimum of Months | 0.324027E+12 | 0.00 | 261.09 | 0.238106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1197050.18 | 905491.82 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.143464E+13 | 0.00 | 496.03 | 0.102814E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2241229.52 | 1383623.05 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.312384E+11 | 0.00 | 252.58 | 0.223451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125478.96 | 19-JAN-15:00 | 86783.84 | 19-JAN-15:50 | 0.00 | 0.00 | 0.00 |
February | 0.453487E+11 | 0.00 | 295.11 | 0.316974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124951.46 | 24-FEB-16:00 | 92646.46 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.552785E+11 | 0.00 | 360.16 | 0.413319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161486.59 | 27-MAR-05:02 | 123071.41 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.884136E+11 | 0.00 | 406.63 | 0.669879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165689.30 | 29-APR-04:11 | 127462.22 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.144684E+12 | 0.00 | 482.32 | 0.109273E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 235403.60 | 23-MAY-05:02 | 139765.65 | 26-MAY-03:01 | 0.00 | 0.00 | 0.00 |
June | 0.149240E+12 | 0.00 | 486.97 | 0.114654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 185292.25 | 06-JUN-04:11 | 142326.78 | 29-JUN-03:01 | 0.00 | 0.00 | 0.00 |
July | 0.154221E+12 | 0.00 | 501.58 | 0.113248E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 217963.68 | 25-JUL-05:02 | 141314.69 | 07-JUL-03:01 | 0.00 | 0.00 | 0.00 |
August | 0.158123E+12 | 0.00 | 503.14 | 0.116166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 220755.63 | 16-AUG-04:11 | 141753.43 | 23-AUG-03:01 | 0.00 | 0.00 | 0.00 |
September | 0.138698E+12 | 0.00 | 467.16 | 0.966453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 234859.69 | 05-SEP-04:11 | 136835.07 | 07-SEP-03:01 | 0.00 | 0.00 | 0.00 |
October | 0.120338E+12 | 0.00 | 447.09 | 0.901074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 215794.39 | 14-OCT-05:02 | 139983.76 | 06-OCT-03:01 | 0.00 | 0.00 | 0.00 |
November | 0.646515E+11 | 0.00 | 385.90 | 0.498302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 181779.99 | 01-NOV-05:02 | 127559.39 | 01-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.447232E+11 | 0.00 | 293.39 | 0.325670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152864.97 | 11-DEC-06:01 | 114367.40 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119496E+13 | 4882.02 | 0.884853E+12 | ||||||||||||
Minimum of Months | 0.312384E+11 | 0.00 | 252.58 | 0.223451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124951.46 | 86783.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.158123E+12 | 0.00 | 503.14 | 0.116166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 235403.60 | 142326.78 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.105867E+12 | 0.299702E+11 | 528.91 | 0.102241E+12 | 0.362576E+10 | 0.00 | 0.79 | 28-JAN-09:30 | 0.00 | 07-JAN-16:10 | 199054.48 | 31-JAN-12:50 | 121226.39 | 02-JAN-15:00 | 80073.32 | 31-JAN-12:50 | 66118.92 | 28-JAN-10:00 | 0.00 |
February | 0.256864E+12 | 0.736730E+11 | 496.48 | 0.246020E+12 | 0.108443E+11 | 0.00 | 0.71 | 24-FEB-10:30 | 0.01 | 16-FEB-10:03 | 297349.31 | 24-FEB-10:30 | 210509.85 | 12-FEB-12:33 | 111393.96 | 24-FEB-10:20 | 72411.66 | 24-FEB-10:30 | 0.00 |
March | 0.412470E+12 | 0.108387E+12 | 704.37 | 0.388263E+12 | 0.242072E+11 | 0.00 | 0.85 | 29-MAR-08:40 | 0.01 | 02-MAR-23:00 | 361156.47 | 29-MAR-08:40 | 296024.26 | 30-MAR-13:00 | 159383.80 | 29-MAR-08:30 | 96217.83 | 26-MAR-14:00 | 0.00 |
April | 0.866307E+12 | 0.228866E+12 | 719.83 | 0.804186E+12 | 0.621208E+11 | 0.00 | 1.00 | 14-APR-13:30 | 0.01 | 11-APR-06:35 | 405803.29 | 06-APR-07:00 | 386632.62 | 18-APR-16:50 | 205258.02 | 06-APR-06:50 | 131520.58 | 28-APR-15:00 | 0.00 |
May | 0.330249E+12 | 0.101040E+12 | 744.00 | 0.320250E+12 | 0.999929E+10 | 0.00 | 0.39 | 01-MAY-15:30 | 0.33 | 07-MAY-01:00 | 133909.02 | 01-MAY-09:05 | 132556.34 | 01-MAY-00:10 | 12150.46 | 23-MAY-16:00 | 46492.24 | 01-MAY-15:10 | 0.00 |
June | 0.547952E+12 | 0.168147E+12 | 720.00 | 0.536814E+12 | 0.111372E+11 | 0.00 | 0.62 | 28-JUN-14:05 | 0.54 | 01-JUN-05:00 | 222616.09 | 29-JUN-15:00 | 210640.60 | 14-JUN-14:00 | 14939.39 | 29-JUN-15:00 | 80084.88 | 14-JUN-14:00 | 0.00 |
July | 0.803452E+12 | 0.247086E+12 | 744.00 | 0.791072E+12 | 0.123798E+11 | 0.00 | 0.85 | 21-JUL-16:00 | 0.75 | 01-JUL-00:05 | 310076.70 | 12-JUL-12:30 | 299547.29 | 21-JUL-16:00 | 13903.02 | 29-JUL-13:00 | 115787.79 | 21-JUL-16:00 | 0.00 |
August | 0.103653E+13 | 0.311928E+12 | 744.00 | 0.102483E+13 | 0.116977E+11 | 0.00 | 1.00 | 01-AUG-08:30 | 0.92 | 20-AUG-05:00 | 404798.07 | 07-AUG-14:05 | 391615.96 | 06-AUG-15:42 | 86047.03 | 20-AUG-04:20 | 138235.20 | 30-AUG-16:00 | 0.00 |
September | 0.323688E+12 | 0.969859E+11 | 720.00 | 0.312755E+12 | 0.109327E+11 | 0.00 | 0.39 | 09-SEP-17:00 | 0.33 | 22-SEP-06:10 | 137411.94 | 01-SEP-00:10 | 135877.34 | 01-SEP-00:10 | 11772.36 | 05-SEP-13:00 | 51283.11 | 09-SEP-17:00 | 0.00 |
October | 0.490608E+12 | 0.145085E+12 | 701.49 | 0.477880E+12 | 0.127287E+11 | 0.00 | 0.65 | 31-OCT-11:00 | 0.01 | 17-OCT-04:54 | 259895.64 | 31-OCT-11:00 | 211794.87 | 05-OCT-15:00 | 79034.57 | 31-OCT-10:50 | 78772.13 | 05-OCT-15:00 | 0.00 |
November | 0.405650E+12 | 0.110554E+12 | 684.57 | 0.369679E+12 | 0.359714E+11 | 0.00 | 0.83 | 28-NOV-08:50 | 0.01 | 17-NOV-07:40 | 342819.58 | 28-NOV-08:50 | 297786.76 | 06-NOV-16:00 | 126204.68 | 28-NOV-08:40 | 98830.01 | 02-NOV-13:00 | 0.00 |
December | 0.487442E+12 | 0.127883E+12 | 715.77 | 0.436522E+12 | 0.509203E+11 | 0.00 | 1.00 | 12-DEC-14:00 | 0.01 | 29-DEC-15:00 | 412849.02 | 28-DEC-09:50 | 385967.89 | 13-DEC-17:00 | 236526.40 | 28-DEC-09:40 | 123663.10 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.606708E+13 | 0.174961E+13 | 8223.41 | 0.581052E+13 | 0.256565E+12 | ||||||||||||||
Minimum of Months | 0.105867E+12 | 0.299702E+11 | 496.48 | 0.102241E+12 | 0.362576E+10 | 0.00 | 0.39 | 0.00 | 133909.02 | 121226.39 | 11772.36 | 46492.24 | 0.00 | ||||||
Maximum of Months | 0.103653E+13 | 0.311928E+12 | 744.00 | 0.102483E+13 | 0.621208E+11 | 0.00 | 1.00 | 0.92 | 412849.02 | 391615.96 | 236526.40 | 138235.20 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.505520E+10 | 0.118257E+10 | 744.00 | 0.505511E+10 | 89389.85 | 0.00 | 0.33 | 01-JAN-16:51 | 0.19 | 05-JAN-07:40 | 2540.50 | 01-JAN-17:30 | 2540.50 | 01-JAN-17:30 | 3.26 | 03-JAN-05:10 | 692.59 | 01-JAN-16:51 | 0.00 |
February | 0.914798E+10 | 0.208536E+10 | 672.00 | 0.914798E+10 | 236.32 | 0.00 | 0.57 | 26-FEB-17:42 | 0.40 | 05-FEB-08:10 | 4533.21 | 26-FEB-17:52 | 4533.21 | 26-FEB-17:52 | 0.07 | 05-FEB-07:00 | 1227.37 | 26-FEB-17:32 | 0.00 |
March | 0.150771E+11 | 0.346633E+10 | 744.00 | 0.150771E+11 | 0.00 | 0.00 | 0.76 | 26-MAR-14:00 | 0.61 | 11-MAR-18:20 | 6080.56 | 05-MAR-17:50 | 6080.56 | 05-MAR-17:50 | 0.00 | 01-MAR-00:10 | 1903.94 | 26-MAR-14:00 | 0.00 |
April | 0.194272E+11 | 0.490281E+10 | 720.00 | 0.194272E+11 | 0.00 | 0.00 | 1.00 | 28-APR-15:30 | 0.82 | 11-APR-07:00 | 8182.19 | 16-APR-18:12 | 8182.19 | 16-APR-18:12 | 0.00 | 01-APR-00:10 | 2715.66 | 28-APR-15:00 | 0.00 |
May | 0.562281E+10 | 0.174519E+10 | 744.00 | 0.562281E+10 | 0.00 | 0.00 | 0.35 | 29-MAY-18:02 | 0.26 | 22-MAY-21:20 | 2522.08 | 29-MAY-18:04 | 2522.08 | 29-MAY-18:04 | 0.00 | 01-MAY-00:01 | 879.81 | 28-MAY-16:00 | 0.00 |
June | 0.101154E+11 | 0.313548E+10 | 720.00 | 0.101154E+11 | 0.00 | 0.00 | 0.59 | 11-JUN-18:15 | 0.48 | 01-JUN-06:00 | 4311.67 | 11-JUN-18:30 | 4311.67 | 11-JUN-18:30 | 0.00 | 01-JUN-00:10 | 1519.62 | 11-JUN-17:00 | 0.00 |
July | 0.153228E+11 | 0.475456E+10 | 744.00 | 0.153228E+11 | 0.00 | 0.00 | 0.80 | 21-JUL-16:00 | 0.69 | 11-JUL-20:10 | 6070.46 | 23-JUL-18:55 | 6070.46 | 23-JUL-18:55 | 0.00 | 01-JUL-00:05 | 2263.21 | 21-JUL-16:00 | 0.00 |
August | 0.202015E+11 | 0.616473E+10 | 744.00 | 0.202015E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-15:10 | 0.87 | 16-AUG-21:10 | 7907.66 | 06-AUG-18:00 | 7907.66 | 06-AUG-18:00 | 0.00 | 01-AUG-00:10 | 2867.13 | 30-AUG-16:00 | 0.00 |
September | 0.545942E+10 | 0.166216E+10 | 720.00 | 0.545942E+10 | 0.00 | 0.00 | 0.36 | 03-SEP-18:01 | 0.25 | 07-SEP-21:03 | 2609.84 | 03-SEP-18:06 | 2609.84 | 03-SEP-18:06 | 0.00 | 01-SEP-00:05 | 921.10 | 09-SEP-17:55 | 0.00 |
October | 0.104856E+11 | 0.294344E+10 | 744.00 | 0.104856E+11 | 0.00 | 0.00 | 0.58 | 09-OCT-17:02 | 0.44 | 28-OCT-07:00 | 4437.45 | 01-OCT-17:33 | 4437.45 | 01-OCT-17:33 | 0.00 | 01-OCT-00:10 | 1489.19 | 05-OCT-15:00 | 0.00 |
November | 0.147423E+11 | 0.349839E+10 | 720.00 | 0.147423E+11 | 0.00 | 0.00 | 0.77 | 06-NOV-17:00 | 0.64 | 16-NOV-07:50 | 6274.64 | 12-NOV-17:10 | 6274.64 | 12-NOV-17:10 | 0.00 | 01-NOV-00:10 | 1881.60 | 02-NOV-13:00 | 0.00 |
December | 0.199831E+11 | 0.445042E+10 | 744.00 | 0.199831E+11 | 0.00 | 0.00 | 0.98 | 10-DEC-16:42 | 0.81 | 21-DEC-08:00 | 8087.62 | 25-DEC-16:55 | 8087.62 | 25-DEC-16:55 | 0.00 | 01-DEC-00:10 | 2473.60 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.150641E+12 | 0.399915E+11 | 8760.00 | 0.150640E+12 | 89626.17 | ||||||||||||||
Minimum of Months | 0.505520E+10 | 0.118257E+10 | 672.00 | 0.505511E+10 | 0.00 | 0.00 | 0.33 | 0.19 | 2522.08 | 2522.08 | 0.00 | 692.59 | 0.00 | ||||||
Maximum of Months | 0.202015E+11 | 0.616473E+10 | 744.00 | 0.202015E+11 | 89389.85 | 0.00 | 1.00 | 0.87 | 8182.19 | 8182.19 | 3.26 | 2867.13 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.375009E+11 | 0.898907E+10 | 744.00 | 0.375000E+11 | 854265.36 | 0.00 | 0.30 | 01-JAN-17:03 | 0.11 | 10-JAN-06:30 | 21950.08 | 01-JAN-17:20 | 21950.08 | 01-JAN-17:20 | 27.44 | 03-JAN-05:10 | 6172.37 | 02-JAN-17:00 | 0.00 |
February | 0.788668E+11 | 0.182047E+11 | 672.00 | 0.788667E+11 | 52151.89 | 0.00 | 0.56 | 26-FEB-17:42 | 0.28 | 05-FEB-08:40 | 41680.43 | 26-FEB-17:58 | 41680.43 | 26-FEB-17:58 | 9.27 | 05-FEB-07:00 | 11416.98 | 02-FEB-13:00 | 0.00 |
March | 0.136802E+12 | 0.317102E+11 | 744.00 | 0.136802E+12 | 0.00 | 0.00 | 0.75 | 30-MAR-13:00 | 0.52 | 12-MAR-07:30 | 56613.99 | 06-MAR-18:00 | 56613.99 | 06-MAR-18:00 | 0.00 | 01-MAR-00:10 | 17580.16 | 30-MAR-13:00 | 0.00 |
April | 0.183361E+12 | 0.463878E+11 | 720.00 | 0.183361E+12 | 0.00 | 0.00 | 1.00 | 28-APR-15:10 | 0.80 | 11-APR-06:55 | 76803.45 | 16-APR-18:17 | 76803.45 | 16-APR-18:17 | 0.00 | 01-APR-00:10 | 25894.54 | 28-APR-15:00 | 0.00 |
May | 0.514916E+11 | 0.160488E+11 | 744.00 | 0.514916E+11 | 0.00 | 0.00 | 0.34 | 29-MAY-17:51 | 0.25 | 22-MAY-21:20 | 23205.49 | 28-MAY-18:30 | 23205.49 | 28-MAY-18:30 | 0.00 | 01-MAY-00:01 | 8087.25 | 28-MAY-16:02 | 0.00 |
June | 0.955743E+11 | 0.296588E+11 | 720.00 | 0.955743E+11 | 0.00 | 0.00 | 0.58 | 11-JUN-18:15 | 0.47 | 07-JUN-06:00 | 40708.70 | 11-JUN-18:30 | 40708.70 | 11-JUN-18:30 | 0.00 | 01-JUN-00:10 | 14298.14 | 14-JUN-14:00 | 0.00 |
July | 0.145674E+12 | 0.452184E+11 | 744.00 | 0.145674E+12 | 0.00 | 0.00 | 0.81 | 21-JUL-16:00 | 0.68 | 11-JUL-21:03 | 57201.45 | 23-JUL-19:00 | 57201.45 | 23-JUL-19:00 | 0.00 | 01-JUL-00:05 | 21606.24 | 21-JUL-16:00 | 0.00 |
August | 0.192298E+12 | 0.586916E+11 | 744.00 | 0.192298E+12 | 0.00 | 0.00 | 1.00 | 01-AUG-14:40 | 0.87 | 16-AUG-21:12 | 74481.47 | 06-AUG-17:38 | 74481.47 | 06-AUG-17:38 | 0.00 | 01-AUG-00:10 | 27275.56 | 30-AUG-16:00 | 0.00 |
September | 0.492813E+11 | 0.150825E+11 | 720.00 | 0.492813E+11 | 0.00 | 0.00 | 0.36 | 03-SEP-17:52 | 0.23 | 07-SEP-21:13 | 24434.30 | 03-SEP-17:58 | 24434.30 | 03-SEP-17:58 | 0.00 | 01-SEP-00:05 | 8545.86 | 09-SEP-18:10 | 0.00 |
October | 0.973089E+11 | 0.274486E+11 | 744.00 | 0.973089E+11 | 0.00 | 0.00 | 0.57 | 09-OCT-17:11 | 0.40 | 28-OCT-07:30 | 41423.62 | 09-OCT-17:28 | 41423.62 | 09-OCT-17:28 | 0.00 | 01-OCT-00:10 | 14126.50 | 05-OCT-15:00 | 0.00 |
November | 0.134856E+12 | 0.322392E+11 | 720.00 | 0.134856E+12 | 0.00 | 0.00 | 0.77 | 06-NOV-17:00 | 0.58 | 16-NOV-08:00 | 57980.39 | 06-NOV-17:00 | 57980.39 | 06-NOV-17:00 | 0.00 | 01-NOV-00:10 | 17893.95 | 02-NOV-13:00 | 0.00 |
December | 0.182038E+12 | 0.408940E+11 | 744.00 | 0.182038E+12 | 0.00 | 0.00 | 0.98 | 15-DEC-17:00 | 0.73 | 31-DEC-04:10 | 74706.16 | 17-DEC-17:05 | 74706.16 | 17-DEC-17:05 | 0.00 | 01-DEC-00:10 | 23519.88 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.138505E+13 | 0.370574E+12 | 8760.00 | 0.138505E+13 | 906417.25 | ||||||||||||||
Minimum of Months | 0.375009E+11 | 0.898907E+10 | 672.00 | 0.375000E+11 | 0.00 | 0.00 | 0.30 | 0.11 | 21950.08 | 21950.08 | 0.00 | 6172.37 | 0.00 | ||||||
Maximum of Months | 0.192298E+12 | 0.586916E+11 | 744.00 | 0.192298E+12 | 854265.36 | 0.00 | 1.00 | 0.87 | 76803.45 | 76803.45 | 27.44 | 27275.56 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.271425E+10 | 0.671385E+09 | 679.16 | 0.271418E+10 | 75144.96 | 0.00 | 0.31 | 31-JAN-17:50 | 0.00 | 04-JAN-03:45 | 2252.35 | 31-JAN-17:50 | 2252.35 | 31-JAN-17:50 | 2.47 | 03-JAN-11:00 | 622.50 | 02-JAN-17:00 | 0.00 |
February | 0.714950E+10 | 0.167384E+10 | 672.00 | 0.714949E+10 | 12766.11 | 0.00 | 0.55 | 26-FEB-17:52 | 0.08 | 05-FEB-08:50 | 4194.86 | 26-FEB-17:56 | 4194.86 | 26-FEB-17:56 | 0.69 | 05-FEB-02:00 | 1156.58 | 02-FEB-13:20 | 0.00 |
March | 0.131805E+11 | 0.308400E+10 | 744.00 | 0.131805E+11 | 0.00 | 0.00 | 0.74 | 30-MAR-13:00 | 0.38 | 12-MAR-07:50 | 5729.99 | 06-MAR-17:50 | 5729.99 | 06-MAR-17:50 | 0.00 | 01-MAR-00:10 | 1784.22 | 26-MAR-14:00 | 0.00 |
April | 0.182290E+11 | 0.463299E+10 | 720.00 | 0.182290E+11 | 0.00 | 0.00 | 1.00 | 28-APR-15:40 | 0.74 | 11-APR-07:00 | 7850.46 | 23-APR-18:04 | 7850.46 | 23-APR-18:04 | 0.00 | 01-APR-00:10 | 2627.12 | 28-APR-15:00 | 0.00 |
May | 0.528986E+10 | 0.164968E+10 | 744.00 | 0.528986E+10 | 0.00 | 0.00 | 0.38 | 29-MAY-17:41 | 0.24 | 13-MAY-07:00 | 2641.10 | 29-MAY-18:14 | 2641.10 | 29-MAY-18:14 | 0.00 | 01-MAY-00:01 | 906.80 | 28-MAY-16:02 | 0.00 |
June | 0.971585E+10 | 0.301687E+10 | 720.00 | 0.971585E+10 | 0.00 | 0.00 | 0.61 | 11-JUN-18:15 | 0.45 | 07-JUN-06:40 | 4342.46 | 11-JUN-18:30 | 4342.46 | 11-JUN-18:30 | 0.00 | 01-JUN-00:10 | 1519.84 | 11-JUN-17:00 | 0.00 |
July | 0.147414E+11 | 0.457984E+10 | 744.00 | 0.147414E+11 | 0.00 | 0.00 | 0.81 | 21-JUL-16:00 | 0.67 | 11-JUL-21:12 | 5977.15 | 23-JUL-19:00 | 5977.15 | 23-JUL-19:00 | 0.00 | 01-JUL-00:05 | 2200.73 | 21-JUL-16:00 | 0.00 |
August | 0.193533E+11 | 0.591690E+10 | 744.00 | 0.193533E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-15:00 | 0.86 | 16-AUG-21:12 | 7700.33 | 06-AUG-17:42 | 7700.33 | 06-AUG-17:42 | 0.00 | 01-AUG-00:10 | 2774.70 | 30-AUG-16:00 | 0.00 |
September | 0.503382E+10 | 0.154289E+10 | 720.00 | 0.503382E+10 | 0.00 | 0.00 | 0.39 | 03-SEP-17:52 | 0.22 | 07-SEP-21:25 | 2709.22 | 03-SEP-17:56 | 2709.22 | 03-SEP-17:56 | 0.00 | 01-SEP-00:05 | 939.70 | 10-SEP-15:42 | 0.00 |
October | 0.968569E+10 | 0.274645E+10 | 744.00 | 0.968569E+10 | 0.00 | 0.00 | 0.59 | 08-OCT-16:11 | 0.33 | 29-OCT-07:30 | 4379.84 | 09-OCT-17:30 | 4379.84 | 09-OCT-17:30 | 0.00 | 01-OCT-00:10 | 1451.43 | 08-OCT-14:02 | 0.00 |
November | 0.130107E+11 | 0.313970E+10 | 720.00 | 0.130107E+11 | 0.00 | 0.00 | 0.77 | 06-NOV-17:00 | 0.50 | 16-NOV-07:00 | 5865.55 | 06-NOV-17:00 | 5865.55 | 06-NOV-17:00 | 0.00 | 01-NOV-00:10 | 1816.49 | 02-NOV-13:00 | 0.00 |
December | 0.174007E+11 | 0.395373E+10 | 744.00 | 0.174007E+11 | 0.00 | 0.00 | 0.97 | 15-DEC-17:00 | 0.60 | 31-DEC-06:30 | 7555.75 | 10-DEC-17:04 | 7555.75 | 10-DEC-17:04 | 0.00 | 01-DEC-00:10 | 2369.93 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.135505E+12 | 0.366083E+11 | 8695.16 | 0.135504E+12 | 87911.08 | ||||||||||||||
Minimum of Months | 0.271425E+10 | 0.671385E+09 | 672.00 | 0.271418E+10 | 0.00 | 0.00 | 0.31 | 0.00 | 2252.35 | 2252.35 | 0.00 | 622.50 | 0.00 | ||||||
Maximum of Months | 0.193533E+11 | 0.591690E+10 | 744.00 | 0.193533E+11 | 75144.96 | 0.00 | 1.00 | 0.86 | 7850.46 | 7850.46 | 2.47 | 2774.70 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.77 | 0.00 | 110.77 | 59.04 | 451.98 | 0.00 | 0.00 | 744.00 |
February | 130.69 | 0.00 | 130.69 | 84.62 | 383.62 | 0.00 | 0.00 | 672.00 |
March | 151.61 | 0.00 | 151.61 | 129.16 | 324.24 | 0.00 | 0.00 | 744.00 |
April | 178.92 | 0.72 | 178.19 | 216.56 | 193.10 | 0.00 | 0.00 | 720.00 |
May | 202.64 | 7.38 | 195.26 | 369.94 | 50.76 | 0.00 | 0.00 | 744.00 |
June | 230.43 | 15.91 | 214.52 | 432.98 | 39.73 | 0.00 | 0.00 | 720.00 |
July | 223.63 | 8.49 | 215.15 | 423.62 | 24.90 | 0.00 | 0.00 | 744.00 |
August | 200.29 | 1.56 | 198.72 | 389.50 | 36.94 | 0.00 | 0.00 | 744.00 |
September | 173.01 | 0.01 | 173.00 | 311.40 | 61.15 | 0.00 | 0.00 | 720.00 |
October | 150.34 | 0.00 | 150.34 | 247.40 | 119.16 | 0.00 | 0.00 | 744.00 |
November | 114.14 | 0.00 | 114.14 | 101.42 | 290.54 | 0.00 | 0.00 | 720.00 |
December | 102.98 | 0.00 | 102.98 | 65.24 | 397.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 164.29 | 2.85 | 161.44 | 236.83 | 196.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 59.04 | 24.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 230.43 | 15.91 | 215.15 | 432.98 | 451.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.77 | 0.00 | 110.77 | 59.04 | 451.98 | 0.00 | 0.00 | 744.00 |
February | 130.69 | 0.00 | 130.69 | 84.62 | 383.62 | 0.00 | 0.00 | 672.00 |
March | 151.61 | 0.00 | 151.61 | 129.16 | 324.24 | 0.00 | 0.00 | 744.00 |
April | 178.92 | 0.72 | 178.19 | 216.56 | 193.10 | 0.00 | 0.00 | 720.00 |
May | 202.64 | 7.38 | 195.26 | 369.94 | 50.76 | 0.00 | 0.00 | 744.00 |
June | 230.43 | 15.91 | 214.52 | 432.98 | 39.73 | 0.00 | 0.00 | 720.00 |
July | 223.63 | 8.49 | 215.15 | 423.62 | 24.90 | 0.00 | 0.00 | 744.00 |
August | 200.29 | 1.56 | 198.72 | 389.50 | 36.94 | 0.00 | 0.00 | 744.00 |
September | 173.01 | 0.01 | 173.00 | 311.40 | 61.15 | 0.00 | 0.00 | 720.00 |
October | 150.34 | 0.00 | 150.34 | 247.40 | 119.16 | 0.00 | 0.00 | 744.00 |
November | 114.14 | 0.00 | 114.14 | 101.42 | 290.54 | 0.00 | 0.00 | 720.00 |
December | 102.98 | 0.00 | 102.98 | 65.24 | 397.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 164.28 | 2.85 | 161.44 | 236.83 | 196.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 59.04 | 24.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 230.43 | 15.91 | 215.15 | 432.98 | 451.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.77 | 0.00 | 110.77 | 59.04 | 451.98 | 0.00 | 0.00 | 744.00 |
February | 130.69 | 0.00 | 130.69 | 84.62 | 383.62 | 0.00 | 0.00 | 672.00 |
March | 151.61 | 0.00 | 151.61 | 129.16 | 324.24 | 0.00 | 0.00 | 744.00 |
April | 178.92 | 0.72 | 178.19 | 216.56 | 193.10 | 0.00 | 0.00 | 720.00 |
May | 202.64 | 7.38 | 195.26 | 369.94 | 50.76 | 0.00 | 0.00 | 744.00 |
June | 230.43 | 15.91 | 214.52 | 432.98 | 39.73 | 0.00 | 0.00 | 720.00 |
July | 223.63 | 8.49 | 215.15 | 423.62 | 24.90 | 0.00 | 0.00 | 744.00 |
August | 200.29 | 1.56 | 198.72 | 389.50 | 36.94 | 0.00 | 0.00 | 744.00 |
September | 173.01 | 0.01 | 173.00 | 311.40 | 61.15 | 0.00 | 0.00 | 720.00 |
October | 150.34 | 0.00 | 150.34 | 247.40 | 119.16 | 0.00 | 0.00 | 744.00 |
November | 114.14 | 0.00 | 114.14 | 101.42 | 290.54 | 0.00 | 0.00 | 720.00 |
December | 102.98 | 0.00 | 102.98 | 65.24 | 397.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 164.29 | 2.85 | 161.44 | 236.83 | 196.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 59.04 | 24.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 230.43 | 15.91 | 215.15 | 432.98 | 451.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.77 | 0.00 | 110.77 | 59.04 | 451.98 | 0.00 | 0.00 | 744.00 |
February | 130.69 | 0.00 | 130.69 | 84.62 | 383.62 | 0.00 | 0.00 | 672.00 |
March | 151.61 | 0.00 | 151.61 | 129.16 | 324.24 | 0.00 | 0.00 | 744.00 |
April | 178.92 | 0.72 | 178.19 | 216.56 | 193.10 | 0.00 | 0.00 | 720.00 |
May | 202.64 | 7.38 | 195.26 | 369.94 | 50.76 | 0.00 | 0.00 | 744.00 |
June | 230.43 | 15.91 | 214.52 | 432.98 | 39.73 | 0.00 | 0.00 | 720.00 |
July | 223.63 | 8.49 | 215.15 | 423.62 | 24.90 | 0.00 | 0.00 | 744.00 |
August | 200.29 | 1.56 | 198.72 | 389.50 | 36.94 | 0.00 | 0.00 | 744.00 |
September | 173.01 | 0.01 | 173.00 | 311.40 | 61.15 | 0.00 | 0.00 | 720.00 |
October | 150.34 | 0.00 | 150.34 | 247.40 | 119.16 | 0.00 | 0.00 | 744.00 |
November | 114.14 | 0.00 | 114.14 | 101.42 | 290.54 | 0.00 | 0.00 | 720.00 |
December | 102.98 | 0.00 | 102.98 | 65.24 | 397.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 164.28 | 2.85 | 161.44 | 236.83 | 196.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 59.04 | 24.90 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 230.43 | 15.91 | 215.15 | 432.98 | 451.98 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.77 | 0.00 | 110.77 | 59.04 | 451.96 | 0.00 | 0.00 | 744.00 |
February | 130.68 | 0.00 | 130.68 | 84.62 | 383.60 | 0.00 | 0.00 | 672.00 |
March | 151.60 | 0.00 | 151.60 | 129.15 | 324.22 | 0.00 | 0.00 | 744.00 |
April | 178.91 | 0.72 | 178.19 | 216.56 | 193.10 | 0.00 | 0.00 | 720.00 |
May | 202.63 | 7.38 | 195.25 | 369.93 | 50.76 | 0.00 | 0.00 | 744.00 |
June | 230.42 | 15.91 | 214.51 | 432.97 | 39.73 | 0.00 | 0.00 | 720.00 |
July | 223.62 | 8.49 | 215.14 | 423.60 | 24.89 | 0.00 | 0.00 | 744.00 |
August | 200.28 | 1.56 | 198.71 | 389.49 | 36.93 | 0.00 | 0.00 | 744.00 |
September | 173.00 | 0.01 | 172.99 | 311.39 | 61.15 | 0.00 | 0.00 | 720.00 |
October | 150.34 | 0.00 | 150.34 | 247.39 | 119.15 | 0.00 | 0.00 | 744.00 |
November | 114.13 | 0.00 | 114.13 | 101.42 | 290.53 | 0.00 | 0.00 | 720.00 |
December | 102.97 | 0.00 | 102.97 | 65.24 | 397.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 164.28 | 2.85 | 161.43 | 236.82 | 196.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.97 | 0.00 | 102.97 | 59.04 | 24.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 230.42 | 15.91 | 215.14 | 432.97 | 451.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.75 | 161.29 | 155.47 | 320.81 | 454.15 | 0.00 | 0.00 | 744.00 |
February | 352.71 | 170.27 | 182.44 | 382.93 | 382.39 | 0.00 | 0.00 | 672.00 |
March | 414.95 | 200.14 | 214.81 | 510.76 | 324.00 | 0.00 | 0.00 | 744.00 |
April | 455.34 | 205.95 | 249.39 | 644.55 | 196.36 | 0.00 | 0.00 | 720.00 |
May | 469.31 | 203.50 | 265.81 | 813.47 | 56.04 | 0.00 | 0.00 | 744.00 |
June | 475.95 | 188.74 | 287.21 | 851.07 | 41.90 | 0.00 | 0.00 | 720.00 |
July | 458.89 | 167.92 | 290.97 | 823.61 | 24.00 | 0.00 | 0.00 | 744.00 |
August | 422.86 | 145.39 | 277.48 | 759.92 | 35.34 | 0.00 | 0.00 | 744.00 |
September | 374.59 | 128.79 | 245.80 | 637.28 | 65.91 | 0.00 | 0.00 | 720.00 |
October | 370.16 | 156.21 | 213.95 | 593.23 | 123.30 | 0.00 | 0.00 | 744.00 |
November | 327.71 | 167.17 | 160.54 | 402.69 | 288.22 | 0.00 | 0.00 | 720.00 |
December | 258.02 | 116.87 | 141.15 | 268.90 | 396.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 391.57 | 167.61 | 223.96 | 585.21 | 198.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 258.02 | 116.87 | 141.15 | 268.90 | 24.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 475.95 | 205.95 | 290.97 | 851.07 | 454.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.75 | 161.29 | 155.47 | 320.81 | 454.15 | 0.00 | 0.00 | 744.00 |
February | 352.71 | 170.27 | 182.44 | 382.93 | 382.39 | 0.00 | 0.00 | 672.00 |
March | 414.95 | 200.14 | 214.81 | 510.76 | 324.00 | 0.00 | 0.00 | 744.00 |
April | 455.34 | 205.95 | 249.39 | 644.55 | 196.36 | 0.00 | 0.00 | 720.00 |
May | 469.31 | 203.50 | 265.81 | 813.47 | 56.04 | 0.00 | 0.00 | 744.00 |
June | 475.95 | 188.74 | 287.21 | 851.07 | 41.90 | 0.00 | 0.00 | 720.00 |
July | 458.89 | 167.92 | 290.97 | 823.61 | 24.00 | 0.00 | 0.00 | 744.00 |
August | 422.86 | 145.39 | 277.48 | 759.92 | 35.34 | 0.00 | 0.00 | 744.00 |
September | 374.59 | 128.79 | 245.80 | 637.28 | 65.91 | 0.00 | 0.00 | 720.00 |
October | 370.16 | 156.21 | 213.95 | 593.23 | 123.30 | 0.00 | 0.00 | 744.00 |
November | 327.71 | 167.17 | 160.54 | 402.69 | 288.22 | 0.00 | 0.00 | 720.00 |
December | 258.02 | 116.87 | 141.15 | 268.90 | 396.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 391.57 | 167.61 | 223.96 | 585.21 | 198.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 258.02 | 116.87 | 141.15 | 268.90 | 24.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 475.95 | 205.95 | 290.97 | 851.07 | 454.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 316.75 | 161.29 | 155.46 | 320.80 | 454.14 | 0.00 | 0.00 | 744.00 |
February | 352.70 | 170.27 | 182.43 | 382.92 | 382.39 | 0.00 | 0.00 | 672.00 |
March | 414.94 | 200.13 | 214.81 | 510.75 | 323.99 | 0.00 | 0.00 | 744.00 |
April | 455.33 | 205.94 | 249.39 | 644.53 | 196.36 | 0.00 | 0.00 | 720.00 |
May | 469.30 | 203.49 | 265.81 | 813.46 | 56.03 | 0.00 | 0.00 | 744.00 |
June | 475.94 | 188.74 | 287.21 | 851.05 | 41.90 | 0.00 | 0.00 | 720.00 |
July | 458.88 | 167.92 | 290.96 | 823.59 | 24.00 | 0.00 | 0.00 | 744.00 |
August | 422.86 | 145.38 | 277.47 | 759.91 | 35.34 | 0.00 | 0.00 | 744.00 |
September | 374.59 | 128.79 | 245.80 | 637.26 | 65.91 | 0.00 | 0.00 | 720.00 |
October | 370.15 | 156.20 | 213.95 | 593.22 | 123.30 | 0.00 | 0.00 | 744.00 |
November | 327.70 | 167.17 | 160.54 | 402.68 | 288.22 | 0.00 | 0.00 | 720.00 |
December | 258.02 | 116.87 | 141.15 | 268.90 | 396.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 391.56 | 167.61 | 223.96 | 585.20 | 198.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 258.02 | 116.87 | 141.15 | 268.90 | 24.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 475.94 | 205.94 | 290.96 | 851.05 | 454.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.48 | 456.83 | 183.65 | 857.52 | 395.85 | 0.00 | 0.00 | 744.00 |
February | 580.76 | 375.93 | 204.83 | 764.43 | 344.36 | 0.00 | 0.00 | 672.00 |
March | 370.63 | 167.20 | 203.42 | 452.55 | 307.27 | 0.00 | 0.00 | 744.00 |
April | 274.66 | 64.27 | 210.40 | 342.02 | 192.71 | 0.00 | 0.00 | 720.00 |
May | 209.87 | 8.84 | 201.03 | 376.21 | 52.16 | 0.00 | 0.00 | 744.00 |
June | 207.36 | 1.89 | 205.47 | 401.35 | 41.57 | 0.00 | 0.00 | 720.00 |
July | 217.06 | 3.94 | 213.12 | 413.03 | 25.11 | 0.00 | 0.00 | 744.00 |
August | 255.34 | 30.57 | 224.77 | 460.70 | 39.24 | 0.00 | 0.00 | 744.00 |
September | 306.39 | 80.69 | 225.70 | 506.28 | 63.91 | 0.00 | 0.00 | 720.00 |
October | 475.44 | 247.64 | 227.80 | 760.93 | 122.32 | 0.00 | 0.00 | 744.00 |
November | 605.23 | 416.75 | 188.48 | 871.21 | 267.78 | 0.00 | 0.00 | 720.00 |
December | 625.84 | 449.50 | 176.34 | 878.39 | 356.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 396.45 | 191.05 | 205.40 | 589.61 | 183.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 207.36 | 1.89 | 176.34 | 342.02 | 25.11 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 640.48 | 456.83 | 227.80 | 878.39 | 395.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.48 | 456.83 | 183.65 | 857.52 | 395.85 | 0.00 | 0.00 | 744.00 |
February | 580.76 | 375.93 | 204.83 | 764.43 | 344.36 | 0.00 | 0.00 | 672.00 |
March | 370.63 | 167.20 | 203.42 | 452.55 | 307.27 | 0.00 | 0.00 | 744.00 |
April | 274.66 | 64.27 | 210.40 | 342.02 | 192.71 | 0.00 | 0.00 | 720.00 |
May | 209.87 | 8.84 | 201.03 | 376.21 | 52.16 | 0.00 | 0.00 | 744.00 |
June | 207.36 | 1.89 | 205.47 | 401.35 | 41.57 | 0.00 | 0.00 | 720.00 |
July | 217.06 | 3.94 | 213.12 | 413.03 | 25.11 | 0.00 | 0.00 | 744.00 |
August | 255.34 | 30.57 | 224.77 | 460.70 | 39.24 | 0.00 | 0.00 | 744.00 |
September | 306.39 | 80.69 | 225.70 | 506.28 | 63.91 | 0.00 | 0.00 | 720.00 |
October | 475.44 | 247.64 | 227.80 | 760.93 | 122.32 | 0.00 | 0.00 | 744.00 |
November | 605.23 | 416.75 | 188.48 | 871.21 | 267.78 | 0.00 | 0.00 | 720.00 |
December | 625.84 | 449.50 | 176.34 | 878.39 | 356.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 396.45 | 191.05 | 205.40 | 589.61 | 183.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 207.36 | 1.89 | 176.34 | 342.02 | 25.11 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 640.48 | 456.83 | 227.80 | 878.39 | 395.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.48 | 456.83 | 183.65 | 857.52 | 395.85 | 0.00 | 0.00 | 744.00 |
February | 580.76 | 375.93 | 204.83 | 764.43 | 344.36 | 0.00 | 0.00 | 672.00 |
March | 370.63 | 167.20 | 203.42 | 452.55 | 307.27 | 0.00 | 0.00 | 744.00 |
April | 274.66 | 64.27 | 210.40 | 342.02 | 192.71 | 0.00 | 0.00 | 720.00 |
May | 209.87 | 8.84 | 201.03 | 376.21 | 52.16 | 0.00 | 0.00 | 744.00 |
June | 207.36 | 1.89 | 205.47 | 401.35 | 41.57 | 0.00 | 0.00 | 720.00 |
July | 217.06 | 3.94 | 213.12 | 413.03 | 25.11 | 0.00 | 0.00 | 744.00 |
August | 255.34 | 30.57 | 224.77 | 460.70 | 39.24 | 0.00 | 0.00 | 744.00 |
September | 306.39 | 80.69 | 225.70 | 506.28 | 63.91 | 0.00 | 0.00 | 720.00 |
October | 475.44 | 247.64 | 227.80 | 760.93 | 122.32 | 0.00 | 0.00 | 744.00 |
November | 605.23 | 416.75 | 188.48 | 871.21 | 267.78 | 0.00 | 0.00 | 720.00 |
December | 625.84 | 449.50 | 176.34 | 878.39 | 356.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 396.45 | 191.05 | 205.40 | 589.61 | 183.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 207.36 | 1.89 | 176.34 | 342.02 | 25.11 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 640.48 | 456.83 | 227.80 | 878.39 | 395.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.48 | 456.83 | 183.65 | 857.52 | 395.85 | 0.00 | 0.00 | 744.00 |
February | 580.76 | 375.93 | 204.83 | 764.43 | 344.36 | 0.00 | 0.00 | 672.00 |
March | 370.63 | 167.20 | 203.42 | 452.55 | 307.27 | 0.00 | 0.00 | 744.00 |
April | 274.66 | 64.27 | 210.40 | 342.02 | 192.71 | 0.00 | 0.00 | 720.00 |
May | 209.87 | 8.84 | 201.03 | 376.21 | 52.16 | 0.00 | 0.00 | 744.00 |
June | 207.36 | 1.89 | 205.47 | 401.35 | 41.57 | 0.00 | 0.00 | 720.00 |
July | 217.06 | 3.94 | 213.12 | 413.03 | 25.11 | 0.00 | 0.00 | 744.00 |
August | 255.34 | 30.57 | 224.77 | 460.70 | 39.24 | 0.00 | 0.00 | 744.00 |
September | 306.39 | 80.69 | 225.70 | 506.28 | 63.91 | 0.00 | 0.00 | 720.00 |
October | 475.44 | 247.64 | 227.80 | 760.93 | 122.32 | 0.00 | 0.00 | 744.00 |
November | 605.23 | 416.75 | 188.48 | 871.21 | 267.78 | 0.00 | 0.00 | 720.00 |
December | 625.84 | 449.50 | 176.34 | 878.39 | 356.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 396.45 | 191.05 | 205.40 | 589.61 | 183.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 207.36 | 1.89 | 176.34 | 342.02 | 25.11 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 640.48 | 456.83 | 227.80 | 878.39 | 395.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 640.45 | 456.81 | 183.65 | 857.49 | 395.84 | 0.00 | 0.00 | 744.00 |
February | 580.73 | 375.92 | 204.82 | 764.40 | 344.35 | 0.00 | 0.00 | 672.00 |
March | 370.61 | 167.20 | 203.41 | 452.53 | 307.26 | 0.00 | 0.00 | 744.00 |
April | 274.65 | 64.27 | 210.39 | 342.01 | 192.71 | 0.00 | 0.00 | 720.00 |
May | 209.86 | 8.84 | 201.02 | 376.20 | 52.16 | 0.00 | 0.00 | 744.00 |
June | 207.35 | 1.89 | 205.46 | 401.33 | 41.57 | 0.00 | 0.00 | 720.00 |
July | 217.05 | 3.94 | 213.12 | 413.01 | 25.11 | 0.00 | 0.00 | 744.00 |
August | 255.33 | 30.57 | 224.76 | 460.68 | 39.24 | 0.00 | 0.00 | 744.00 |
September | 306.38 | 80.69 | 225.69 | 506.26 | 63.91 | 0.00 | 0.00 | 720.00 |
October | 475.42 | 247.63 | 227.79 | 760.90 | 122.32 | 0.00 | 0.00 | 744.00 |
November | 605.20 | 416.74 | 188.47 | 871.17 | 267.77 | 0.00 | 0.00 | 720.00 |
December | 625.82 | 449.48 | 176.33 | 878.36 | 356.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 396.44 | 191.05 | 205.39 | 589.59 | 183.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 207.35 | 1.89 | 176.33 | 342.01 | 25.11 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 640.45 | 456.81 | 227.79 | 878.36 | 395.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 336.92 | 182.18 | 154.73 | 367.57 | 516.06 | 0.00 | 0.00 | 744.00 |
February | 381.46 | 193.07 | 188.40 | 433.83 | 455.81 | 0.00 | 0.00 | 672.00 |
March | 376.00 | 166.45 | 209.54 | 448.18 | 404.54 | 0.00 | 0.00 | 744.00 |
April | 467.00 | 214.84 | 252.16 | 648.22 | 266.18 | 0.00 | 0.00 | 720.00 |
May | 388.34 | 126.49 | 261.84 | 672.30 | 80.80 | 0.00 | 0.00 | 744.00 |
June | 431.40 | 151.26 | 280.14 | 760.42 | 74.35 | 0.00 | 0.00 | 720.00 |
July | 393.79 | 109.22 | 284.56 | 686.04 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 398.18 | 121.89 | 276.29 | 693.54 | 82.31 | 0.00 | 0.00 | 744.00 |
September | 366.67 | 125.79 | 240.87 | 615.89 | 92.42 | 0.00 | 0.00 | 720.00 |
October | 375.38 | 162.20 | 213.18 | 596.88 | 167.48 | 0.00 | 0.00 | 744.00 |
November | 321.73 | 161.68 | 160.05 | 400.79 | 366.53 | 0.00 | 0.00 | 720.00 |
December | 309.49 | 164.58 | 144.91 | 346.03 | 492.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 378.65 | 156.26 | 222.38 | 556.26 | 253.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 309.49 | 109.22 | 144.91 | 346.03 | 58.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 467.00 | 214.84 | 284.56 | 760.42 | 516.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 336.92 | 182.18 | 154.73 | 367.57 | 516.06 | 0.00 | 0.00 | 744.00 |
February | 381.46 | 193.07 | 188.40 | 433.83 | 455.81 | 0.00 | 0.00 | 672.00 |
March | 376.00 | 166.45 | 209.54 | 448.18 | 404.54 | 0.00 | 0.00 | 744.00 |
April | 467.00 | 214.84 | 252.16 | 648.22 | 266.18 | 0.00 | 0.00 | 720.00 |
May | 388.34 | 126.49 | 261.84 | 672.30 | 80.80 | 0.00 | 0.00 | 744.00 |
June | 431.40 | 151.26 | 280.14 | 760.42 | 74.35 | 0.00 | 0.00 | 720.00 |
July | 393.79 | 109.22 | 284.56 | 686.04 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 398.18 | 121.89 | 276.29 | 693.54 | 82.31 | 0.00 | 0.00 | 744.00 |
September | 366.67 | 125.79 | 240.87 | 615.89 | 92.42 | 0.00 | 0.00 | 720.00 |
October | 375.38 | 162.20 | 213.18 | 596.88 | 167.48 | 0.00 | 0.00 | 744.00 |
November | 321.73 | 161.68 | 160.05 | 400.79 | 366.53 | 0.00 | 0.00 | 720.00 |
December | 309.49 | 164.58 | 144.91 | 346.03 | 492.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 378.65 | 156.26 | 222.38 | 556.26 | 253.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 309.49 | 109.22 | 144.91 | 346.03 | 58.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 467.00 | 214.84 | 284.56 | 760.42 | 516.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 336.91 | 182.18 | 154.73 | 367.57 | 516.05 | 0.00 | 0.00 | 744.00 |
February | 381.45 | 193.06 | 188.39 | 433.82 | 455.80 | 0.00 | 0.00 | 672.00 |
March | 375.99 | 166.45 | 209.54 | 448.17 | 404.54 | 0.00 | 0.00 | 744.00 |
April | 466.99 | 214.84 | 252.16 | 648.21 | 266.17 | 0.00 | 0.00 | 720.00 |
May | 388.33 | 126.49 | 261.84 | 672.29 | 80.80 | 0.00 | 0.00 | 744.00 |
June | 431.39 | 151.26 | 280.13 | 760.41 | 74.35 | 0.00 | 0.00 | 720.00 |
July | 393.78 | 109.22 | 284.56 | 686.03 | 58.94 | 0.00 | 0.00 | 744.00 |
August | 398.17 | 121.89 | 276.29 | 693.53 | 82.31 | 0.00 | 0.00 | 744.00 |
September | 366.66 | 125.79 | 240.87 | 615.88 | 92.42 | 0.00 | 0.00 | 720.00 |
October | 375.38 | 162.20 | 213.18 | 596.87 | 167.48 | 0.00 | 0.00 | 744.00 |
November | 321.73 | 161.68 | 160.05 | 400.78 | 366.52 | 0.00 | 0.00 | 720.00 |
December | 309.48 | 164.58 | 144.91 | 346.02 | 492.40 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 378.64 | 156.26 | 222.38 | 556.25 | 253.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 309.48 | 109.22 | 144.91 | 346.02 | 58.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 466.99 | 214.84 | 284.56 | 760.41 | 516.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 553.86 | 0.00 | 553.86 | 355.44 | 1992.24 | 0.00 | 0.00 | 744.00 |
February | 653.42 | 0.00 | 653.42 | 484.43 | 1670.58 | 0.00 | 0.00 | 672.00 |
March | 758.02 | 0.00 | 758.02 | 705.07 | 1427.20 | 0.00 | 0.00 | 744.00 |
April | 894.59 | 3.62 | 890.96 | 1120.10 | 886.73 | 0.00 | 0.00 | 720.00 |
May | 1013.18 | 36.90 | 976.28 | 1865.78 | 235.88 | 0.00 | 0.00 | 744.00 |
June | 1152.13 | 79.54 | 1072.60 | 2179.53 | 200.67 | 0.00 | 0.00 | 720.00 |
July | 1118.15 | 42.44 | 1075.71 | 2135.01 | 130.62 | 0.00 | 0.00 | 744.00 |
August | 1001.42 | 7.82 | 993.60 | 1973.30 | 187.14 | 0.00 | 0.00 | 744.00 |
September | 865.05 | 0.06 | 864.98 | 1578.24 | 273.37 | 0.00 | 0.00 | 720.00 |
October | 751.71 | 0.00 | 751.71 | 1267.11 | 540.58 | 0.00 | 0.00 | 744.00 |
November | 570.67 | 0.00 | 570.67 | 562.62 | 1262.98 | 0.00 | 0.00 | 720.00 |
December | 514.87 | 0.00 | 514.87 | 387.55 | 1700.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 821.42 | 14.24 | 807.17 | 1222.32 | 871.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 514.87 | 0.00 | 514.87 | 355.44 | 130.62 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1152.13 | 79.54 | 1075.71 | 2179.53 | 1992.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 950.25 | 483.86 | 466.39 | 977.88 | 1259.50 | 0.00 | 0.00 | 744.00 |
February | 1058.12 | 510.81 | 547.31 | 1161.42 | 1060.62 | 0.00 | 0.00 | 672.00 |
March | 1244.84 | 600.40 | 644.44 | 1528.41 | 915.65 | 0.00 | 0.00 | 744.00 |
April | 1366.01 | 617.84 | 748.17 | 1910.49 | 590.84 | 0.00 | 0.00 | 720.00 |
May | 1407.91 | 610.48 | 797.43 | 2412.65 | 170.69 | 0.00 | 0.00 | 744.00 |
June | 1427.84 | 566.21 | 861.63 | 2523.74 | 145.16 | 0.00 | 0.00 | 720.00 |
July | 1376.66 | 503.76 | 872.89 | 2436.79 | 96.02 | 0.00 | 0.00 | 744.00 |
August | 1268.58 | 436.15 | 832.43 | 2249.28 | 135.06 | 0.00 | 0.00 | 744.00 |
September | 1123.77 | 386.38 | 737.39 | 1892.65 | 194.18 | 0.00 | 0.00 | 720.00 |
October | 1110.47 | 468.62 | 641.86 | 1760.92 | 364.86 | 0.00 | 0.00 | 744.00 |
November | 983.12 | 501.51 | 481.61 | 1208.81 | 812.80 | 0.00 | 0.00 | 720.00 |
December | 774.05 | 350.61 | 423.44 | 820.88 | 1097.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1174.70 | 502.83 | 671.87 | 1743.51 | 567.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 774.05 | 350.61 | 423.44 | 820.88 | 96.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1427.84 | 617.84 | 872.89 | 2523.74 | 1259.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3202.35 | 2284.10 | 918.25 | 4249.38 | 1935.11 | 0.00 | 0.00 | 744.00 |
February | 2903.75 | 1879.63 | 1024.12 | 3799.63 | 1664.45 | 0.00 | 0.00 | 672.00 |
March | 1853.11 | 836.01 | 1017.10 | 2267.83 | 1452.69 | 0.00 | 0.00 | 744.00 |
April | 1373.31 | 321.34 | 1051.97 | 1725.98 | 924.35 | 0.00 | 0.00 | 720.00 |
May | 1049.35 | 44.20 | 1005.15 | 1894.69 | 247.46 | 0.00 | 0.00 | 744.00 |
June | 1036.79 | 9.46 | 1027.32 | 2021.73 | 209.88 | 0.00 | 0.00 | 720.00 |
July | 1085.29 | 19.69 | 1065.61 | 2084.44 | 131.10 | 0.00 | 0.00 | 744.00 |
August | 1276.67 | 152.86 | 1123.81 | 2319.47 | 203.55 | 0.00 | 0.00 | 744.00 |
September | 1531.93 | 403.45 | 1128.48 | 2531.29 | 304.14 | 0.00 | 0.00 | 720.00 |
October | 2377.18 | 1238.18 | 1139.00 | 3779.07 | 605.81 | 0.00 | 0.00 | 744.00 |
November | 3026.11 | 2083.73 | 942.38 | 4327.76 | 1300.61 | 0.00 | 0.00 | 720.00 |
December | 3129.17 | 2247.49 | 881.69 | 4366.51 | 1715.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1982.23 | 955.25 | 1026.98 | 2943.55 | 887.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1036.79 | 9.46 | 881.69 | 1725.98 | 131.10 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3202.35 | 2284.10 | 1139.00 | 4366.51 | 1935.11 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1010.74 | 546.54 | 464.20 | 1142.43 | 1360.90 | 0.00 | 0.00 | 744.00 |
February | 1144.37 | 579.19 | 565.18 | 1350.80 | 1165.50 | 0.00 | 0.00 | 672.00 |
March | 1127.98 | 499.35 | 628.63 | 1395.70 | 1010.13 | 0.00 | 0.00 | 744.00 |
April | 1400.99 | 644.52 | 756.47 | 1996.90 | 667.22 | 0.00 | 0.00 | 720.00 |
May | 1164.99 | 379.47 | 785.52 | 2038.99 | 204.54 | 0.00 | 0.00 | 744.00 |
June | 1294.18 | 453.77 | 840.40 | 2313.59 | 181.91 | 0.00 | 0.00 | 720.00 |
July | 1181.34 | 327.66 | 853.68 | 2109.83 | 126.55 | 0.00 | 0.00 | 744.00 |
August | 1194.52 | 365.66 | 828.86 | 2142.73 | 171.90 | 0.00 | 0.00 | 744.00 |
September | 1099.99 | 377.37 | 722.62 | 1868.95 | 229.23 | 0.00 | 0.00 | 720.00 |
October | 1126.14 | 486.60 | 639.54 | 1825.43 | 421.63 | 0.00 | 0.00 | 744.00 |
November | 965.19 | 485.05 | 480.14 | 1255.84 | 908.73 | 0.00 | 0.00 | 720.00 |
December | 928.45 | 493.73 | 434.72 | 1101.60 | 1184.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1135.92 | 468.79 | 667.13 | 1713.26 | 633.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 928.45 | 327.66 | 434.72 | 1101.60 | 126.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1400.99 | 644.52 | 853.68 | 2313.59 | 1360.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 553.86 | 0.00 | 553.86 | 388.09 | 1832.90 | 0.00 | 0.00 | 744.00 |
February | 653.42 | 0.00 | 653.42 | 509.68 | 1538.71 | 0.00 | 0.00 | 672.00 |
March | 758.02 | 0.00 | 758.02 | 718.70 | 1344.34 | 0.00 | 0.00 | 744.00 |
April | 894.59 | 3.62 | 890.96 | 1112.50 | 862.90 | 0.00 | 0.00 | 720.00 |
May | 1013.18 | 36.90 | 976.28 | 1832.13 | 248.83 | 0.00 | 0.00 | 744.00 |
June | 1152.13 | 79.54 | 1072.60 | 2140.72 | 215.28 | 0.00 | 0.00 | 720.00 |
July | 1118.15 | 42.44 | 1075.71 | 2089.25 | 145.42 | 0.00 | 0.00 | 744.00 |
August | 1001.42 | 7.82 | 993.60 | 1938.65 | 197.78 | 0.00 | 0.00 | 744.00 |
September | 865.05 | 0.06 | 864.98 | 1544.99 | 281.92 | 0.00 | 0.00 | 720.00 |
October | 751.71 | 0.00 | 751.71 | 1252.69 | 528.09 | 0.00 | 0.00 | 744.00 |
November | 570.67 | 0.00 | 570.67 | 583.83 | 1169.93 | 0.00 | 0.00 | 720.00 |
December | 514.87 | 0.00 | 514.87 | 413.31 | 1563.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 821.42 | 14.24 | 807.17 | 1214.66 | 823.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 514.87 | 0.00 | 514.87 | 388.09 | 145.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1152.13 | 79.54 | 1075.71 | 2140.72 | 1832.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 950.25 | 483.86 | 466.39 | 1019.79 | 1155.03 | 0.00 | 0.00 | 744.00 |
February | 1058.12 | 510.81 | 547.31 | 1194.89 | 979.22 | 0.00 | 0.00 | 672.00 |
March | 1244.84 | 600.40 | 644.44 | 1544.58 | 867.18 | 0.00 | 0.00 | 744.00 |
April | 1366.01 | 617.84 | 748.17 | 1911.03 | 577.47 | 0.00 | 0.00 | 720.00 |
May | 1407.91 | 610.48 | 797.43 | 2397.66 | 177.47 | 0.00 | 0.00 | 744.00 |
June | 1427.84 | 566.21 | 861.63 | 2507.11 | 153.66 | 0.00 | 0.00 | 720.00 |
July | 1376.66 | 503.76 | 872.89 | 2417.09 | 104.83 | 0.00 | 0.00 | 744.00 |
August | 1268.58 | 436.15 | 832.43 | 2235.06 | 141.16 | 0.00 | 0.00 | 744.00 |
September | 1123.77 | 386.38 | 737.39 | 1880.24 | 198.33 | 0.00 | 0.00 | 720.00 |
October | 1110.47 | 468.62 | 641.86 | 1757.95 | 356.56 | 0.00 | 0.00 | 744.00 |
November | 983.12 | 501.51 | 481.61 | 1230.23 | 762.04 | 0.00 | 0.00 | 720.00 |
December | 774.05 | 350.61 | 423.44 | 850.98 | 1010.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1174.70 | 502.83 | 671.87 | 1748.58 | 537.96 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 774.05 | 350.61 | 423.44 | 850.98 | 104.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1427.84 | 617.84 | 872.89 | 2507.11 | 1155.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3202.35 | 2284.10 | 918.25 | 4287.38 | 1802.30 | 0.00 | 0.00 | 744.00 |
February | 2903.75 | 1879.63 | 1024.12 | 3833.37 | 1552.40 | 0.00 | 0.00 | 672.00 |
March | 1853.11 | 836.01 | 1017.10 | 2279.59 | 1376.40 | 0.00 | 0.00 | 744.00 |
April | 1373.31 | 321.34 | 1051.97 | 1719.02 | 901.99 | 0.00 | 0.00 | 720.00 |
May | 1049.35 | 44.20 | 1005.15 | 1863.55 | 260.97 | 0.00 | 0.00 | 744.00 |
June | 1036.79 | 9.46 | 1027.32 | 1986.21 | 225.95 | 0.00 | 0.00 | 720.00 |
July | 1085.29 | 19.69 | 1065.61 | 2040.20 | 145.69 | 0.00 | 0.00 | 744.00 |
August | 1276.67 | 152.86 | 1123.81 | 2287.86 | 214.74 | 0.00 | 0.00 | 744.00 |
September | 1531.93 | 403.45 | 1128.48 | 2503.49 | 312.50 | 0.00 | 0.00 | 720.00 |
October | 2377.18 | 1238.18 | 1139.00 | 3766.58 | 593.69 | 0.00 | 0.00 | 744.00 |
November | 3026.11 | 2083.73 | 942.38 | 4347.81 | 1230.18 | 0.00 | 0.00 | 720.00 |
December | 3129.17 | 2247.49 | 881.69 | 4398.44 | 1599.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1982.23 | 955.25 | 1026.98 | 2938.80 | 847.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1036.79 | 9.46 | 881.69 | 1719.02 | 145.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3202.35 | 2284.10 | 1139.00 | 4398.44 | 1802.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1010.74 | 546.54 | 464.20 | 1157.56 | 1273.96 | 0.00 | 0.00 | 744.00 |
February | 1144.37 | 579.19 | 565.18 | 1361.35 | 1092.87 | 0.00 | 0.00 | 672.00 |
March | 1127.98 | 499.35 | 628.63 | 1398.20 | 961.39 | 0.00 | 0.00 | 744.00 |
April | 1400.99 | 644.52 | 756.47 | 1986.38 | 650.33 | 0.00 | 0.00 | 720.00 |
May | 1164.99 | 379.47 | 785.52 | 2018.91 | 210.35 | 0.00 | 0.00 | 744.00 |
June | 1294.18 | 453.77 | 840.40 | 2291.05 | 188.73 | 0.00 | 0.00 | 720.00 |
July | 1181.34 | 327.66 | 853.68 | 2085.20 | 133.79 | 0.00 | 0.00 | 744.00 |
August | 1194.52 | 365.66 | 828.86 | 2122.01 | 177.63 | 0.00 | 0.00 | 744.00 |
September | 1099.99 | 377.37 | 722.62 | 1850.85 | 232.51 | 0.00 | 0.00 | 720.00 |
October | 1126.14 | 486.60 | 639.54 | 1814.62 | 413.35 | 0.00 | 0.00 | 744.00 |
November | 965.19 | 485.05 | 480.14 | 1262.67 | 858.16 | 0.00 | 0.00 | 720.00 |
December | 928.45 | 493.73 | 434.72 | 1113.05 | 1107.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1135.92 | 468.79 | 667.13 | 1706.42 | 605.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 928.45 | 327.66 | 434.72 | 1113.05 | 133.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1400.99 | 644.52 | 853.68 | 2291.05 | 1273.96 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296695E+09 | 0.00 | 0.296695E+09 | 0.158130E+09 | 0.121058E+10 |
February | 0.316154E+09 | 0.00 | 0.316154E+09 | 0.204720E+09 | 0.928042E+09 |
March | 0.406063E+09 | 0.00 | 0.406063E+09 | 0.345930E+09 | 0.868439E+09 |
April | 0.463760E+09 | 1879069.97 | 0.461881E+09 | 0.561336E+09 | 0.500526E+09 |
May | 0.542745E+09 | 19765215.61 | 0.522979E+09 | 0.990856E+09 | 0.135962E+09 |
June | 0.597273E+09 | 41232738.58 | 0.556040E+09 | 0.112230E+10 | 0.102973E+09 |
July | 0.598980E+09 | 22734255.21 | 0.576246E+09 | 0.113463E+10 | 66680395.24 |
August | 0.536445E+09 | 4187625.18 | 0.532257E+09 | 0.104324E+10 | 98927213.62 |
September | 0.448446E+09 | 33570.01 | 0.448413E+09 | 0.807155E+09 | 0.158496E+09 |
October | 0.402681E+09 | 0.00 | 0.402681E+09 | 0.662649E+09 | 0.319151E+09 |
November | 0.295838E+09 | 0.00 | 0.295838E+09 | 0.262891E+09 | 0.753074E+09 |
December | 0.275812E+09 | 0.00 | 0.275812E+09 | 0.174751E+09 | 0.106577E+10 |
Annual Sum or Average | 0.518089E+10 | 89832474.54 | 0.509106E+10 | 0.746858E+10 | 0.620862E+10 |
Minimum of Months | 0.275812E+09 | 0.00 | 0.275812E+09 | 0.158130E+09 | 66680395.24 |
Maximum of Months | 0.598980E+09 | 41232738.58 | 0.576246E+09 | 0.113463E+10 | 0.121058E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296695E+09 | 0.00 | 0.296695E+09 | 0.158130E+09 | 0.121058E+10 |
February | 0.316154E+09 | 0.00 | 0.316154E+09 | 0.204720E+09 | 0.928042E+09 |
March | 0.406063E+09 | 0.00 | 0.406063E+09 | 0.345930E+09 | 0.868439E+09 |
April | 0.463760E+09 | 1879067.71 | 0.461881E+09 | 0.561335E+09 | 0.500525E+09 |
May | 0.542744E+09 | 19765191.89 | 0.522979E+09 | 0.990855E+09 | 0.135962E+09 |
June | 0.597272E+09 | 41232689.10 | 0.556040E+09 | 0.112230E+10 | 0.102973E+09 |
July | 0.598979E+09 | 22734227.93 | 0.576245E+09 | 0.113462E+10 | 66680312.03 |
August | 0.536445E+09 | 4187620.15 | 0.532257E+09 | 0.104324E+10 | 98927124.00 |
September | 0.448446E+09 | 33569.97 | 0.448412E+09 | 0.807155E+09 | 0.158496E+09 |
October | 0.402681E+09 | 0.00 | 0.402681E+09 | 0.662648E+09 | 0.319151E+09 |
November | 0.295838E+09 | 0.00 | 0.295838E+09 | 0.262891E+09 | 0.753074E+09 |
December | 0.275811E+09 | 0.00 | 0.275811E+09 | 0.174751E+09 | 0.106577E+10 |
Annual Sum or Average | 0.518089E+10 | 89832366.75 | 0.509106E+10 | 0.746858E+10 | 0.620862E+10 |
Minimum of Months | 0.275811E+09 | 0.00 | 0.275811E+09 | 0.158130E+09 | 66680312.03 |
Maximum of Months | 0.598979E+09 | 41232689.10 | 0.576245E+09 | 0.113462E+10 | 0.121058E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296695E+09 | 0.00 | 0.296695E+09 | 0.158130E+09 | 0.121058E+10 |
February | 0.316154E+09 | 0.00 | 0.316154E+09 | 0.204720E+09 | 0.928042E+09 |
March | 0.406063E+09 | 0.00 | 0.406063E+09 | 0.345930E+09 | 0.868439E+09 |
April | 0.463760E+09 | 1879069.97 | 0.461881E+09 | 0.561336E+09 | 0.500526E+09 |
May | 0.542745E+09 | 19765215.61 | 0.522979E+09 | 0.990856E+09 | 0.135962E+09 |
June | 0.597273E+09 | 41232738.58 | 0.556040E+09 | 0.112230E+10 | 0.102973E+09 |
July | 0.598980E+09 | 22734255.21 | 0.576246E+09 | 0.113463E+10 | 66680395.24 |
August | 0.536445E+09 | 4187625.18 | 0.532257E+09 | 0.104324E+10 | 98927213.62 |
September | 0.448446E+09 | 33570.01 | 0.448413E+09 | 0.807155E+09 | 0.158496E+09 |
October | 0.402681E+09 | 0.00 | 0.402681E+09 | 0.662649E+09 | 0.319151E+09 |
November | 0.295838E+09 | 0.00 | 0.295838E+09 | 0.262891E+09 | 0.753074E+09 |
December | 0.275812E+09 | 0.00 | 0.275812E+09 | 0.174751E+09 | 0.106577E+10 |
Annual Sum or Average | 0.518089E+10 | 89832474.54 | 0.509106E+10 | 0.746858E+10 | 0.620862E+10 |
Minimum of Months | 0.275812E+09 | 0.00 | 0.275812E+09 | 0.158130E+09 | 66680395.24 |
Maximum of Months | 0.598980E+09 | 41232738.58 | 0.576246E+09 | 0.113463E+10 | 0.121058E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296695E+09 | 0.00 | 0.296695E+09 | 0.158130E+09 | 0.121058E+10 |
February | 0.316154E+09 | 0.00 | 0.316154E+09 | 0.204720E+09 | 0.928042E+09 |
March | 0.406063E+09 | 0.00 | 0.406063E+09 | 0.345930E+09 | 0.868439E+09 |
April | 0.463760E+09 | 1879067.71 | 0.461881E+09 | 0.561335E+09 | 0.500525E+09 |
May | 0.542744E+09 | 19765191.89 | 0.522979E+09 | 0.990855E+09 | 0.135962E+09 |
June | 0.597272E+09 | 41232689.10 | 0.556040E+09 | 0.112230E+10 | 0.102973E+09 |
July | 0.598979E+09 | 22734227.93 | 0.576245E+09 | 0.113462E+10 | 66680312.03 |
August | 0.536445E+09 | 4187620.15 | 0.532257E+09 | 0.104324E+10 | 98927124.00 |
September | 0.448446E+09 | 33569.97 | 0.448412E+09 | 0.807155E+09 | 0.158496E+09 |
October | 0.402681E+09 | 0.00 | 0.402681E+09 | 0.662648E+09 | 0.319151E+09 |
November | 0.295838E+09 | 0.00 | 0.295838E+09 | 0.262891E+09 | 0.753074E+09 |
December | 0.275811E+09 | 0.00 | 0.275811E+09 | 0.174751E+09 | 0.106577E+10 |
Annual Sum or Average | 0.518089E+10 | 89832366.75 | 0.509106E+10 | 0.746858E+10 | 0.620862E+10 |
Minimum of Months | 0.275811E+09 | 0.00 | 0.275811E+09 | 0.158130E+09 | 66680312.03 |
Maximum of Months | 0.598979E+09 | 41232689.10 | 0.576245E+09 | 0.113462E+10 | 0.121058E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296683E+09 | 0.00 | 0.296683E+09 | 0.158124E+09 | 0.121053E+10 |
February | 0.316142E+09 | 0.00 | 0.316142E+09 | 0.204712E+09 | 0.928005E+09 |
March | 0.406047E+09 | 0.00 | 0.406047E+09 | 0.345916E+09 | 0.868404E+09 |
April | 0.463741E+09 | 1878994.23 | 0.461862E+09 | 0.561313E+09 | 0.500505E+09 |
May | 0.542723E+09 | 19764418.98 | 0.522958E+09 | 0.990816E+09 | 0.135957E+09 |
June | 0.597249E+09 | 41231076.72 | 0.556018E+09 | 0.112225E+10 | 0.102969E+09 |
July | 0.598956E+09 | 22733338.92 | 0.576222E+09 | 0.113458E+10 | 66677707.73 |
August | 0.536423E+09 | 4187456.40 | 0.532236E+09 | 0.104320E+10 | 98923226.42 |
September | 0.448428E+09 | 33568.66 | 0.448395E+09 | 0.807122E+09 | 0.158490E+09 |
October | 0.402665E+09 | 0.00 | 0.402665E+09 | 0.662622E+09 | 0.319138E+09 |
November | 0.295826E+09 | 0.00 | 0.295826E+09 | 0.262880E+09 | 0.753043E+09 |
December | 0.275800E+09 | 0.00 | 0.275800E+09 | 0.174744E+09 | 0.106573E+10 |
Annual Sum or Average | 0.518068E+10 | 89828853.90 | 0.509085E+10 | 0.746828E+10 | 0.620837E+10 |
Minimum of Months | 0.275800E+09 | 0.00 | 0.275800E+09 | 0.158124E+09 | 66677707.73 |
Maximum of Months | 0.598956E+09 | 41231076.72 | 0.576222E+09 | 0.113458E+10 | 0.121053E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.848392E+09 | 0.431995E+09 | 0.416398E+09 | 0.859246E+09 | 0.121639E+10 |
February | 0.853275E+09 | 0.411921E+09 | 0.441354E+09 | 0.926380E+09 | 0.925083E+09 |
March | 0.111141E+10 | 0.536045E+09 | 0.575360E+09 | 0.136802E+10 | 0.867799E+09 |
April | 0.118025E+10 | 0.533818E+09 | 0.646429E+09 | 0.167066E+10 | 0.508974E+09 |
May | 0.125700E+10 | 0.545047E+09 | 0.711953E+09 | 0.217880E+10 | 0.150086E+09 |
June | 0.123366E+10 | 0.489211E+09 | 0.744453E+09 | 0.220597E+10 | 0.108603E+09 |
July | 0.122909E+10 | 0.449764E+09 | 0.779328E+09 | 0.220596E+10 | 64283735.80 |
August | 0.113260E+10 | 0.389400E+09 | 0.743200E+09 | 0.203537E+10 | 94665119.70 |
September | 0.970948E+09 | 0.333835E+09 | 0.637113E+09 | 0.165182E+10 | 0.170843E+09 |
October | 0.991440E+09 | 0.418385E+09 | 0.573055E+09 | 0.158892E+10 | 0.330254E+09 |
November | 0.849426E+09 | 0.433309E+09 | 0.416117E+09 | 0.104377E+10 | 0.747079E+09 |
December | 0.691082E+09 | 0.313029E+09 | 0.378053E+09 | 0.720232E+09 | 0.106165E+10 |
Annual Sum or Average | 0.123486E+11 | 0.528576E+10 | 0.706281E+10 | 0.184551E+11 | 0.624571E+10 |
Minimum of Months | 0.691082E+09 | 0.313029E+09 | 0.378053E+09 | 0.720232E+09 | 64283735.80 |
Maximum of Months | 0.125700E+10 | 0.545047E+09 | 0.779328E+09 | 0.220597E+10 | 0.121639E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.848392E+09 | 0.431995E+09 | 0.416398E+09 | 0.859246E+09 | 0.121639E+10 |
February | 0.853275E+09 | 0.411921E+09 | 0.441354E+09 | 0.926380E+09 | 0.925083E+09 |
March | 0.111141E+10 | 0.536045E+09 | 0.575360E+09 | 0.136802E+10 | 0.867799E+09 |
April | 0.118025E+10 | 0.533818E+09 | 0.646429E+09 | 0.167066E+10 | 0.508974E+09 |
May | 0.125700E+10 | 0.545047E+09 | 0.711953E+09 | 0.217880E+10 | 0.150086E+09 |
June | 0.123366E+10 | 0.489211E+09 | 0.744453E+09 | 0.220597E+10 | 0.108603E+09 |
July | 0.122909E+10 | 0.449764E+09 | 0.779328E+09 | 0.220596E+10 | 64283735.80 |
August | 0.113260E+10 | 0.389400E+09 | 0.743200E+09 | 0.203537E+10 | 94665119.70 |
September | 0.970948E+09 | 0.333835E+09 | 0.637113E+09 | 0.165182E+10 | 0.170843E+09 |
October | 0.991440E+09 | 0.418385E+09 | 0.573055E+09 | 0.158892E+10 | 0.330254E+09 |
November | 0.849426E+09 | 0.433309E+09 | 0.416117E+09 | 0.104377E+10 | 0.747079E+09 |
December | 0.691082E+09 | 0.313029E+09 | 0.378053E+09 | 0.720232E+09 | 0.106165E+10 |
Annual Sum or Average | 0.123486E+11 | 0.528576E+10 | 0.706281E+10 | 0.184551E+11 | 0.624571E+10 |
Minimum of Months | 0.691082E+09 | 0.313029E+09 | 0.378053E+09 | 0.720232E+09 | 64283735.80 |
Maximum of Months | 0.125700E+10 | 0.545047E+09 | 0.779328E+09 | 0.220597E+10 | 0.121639E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.848377E+09 | 0.431987E+09 | 0.416390E+09 | 0.859230E+09 | 0.121636E+10 |
February | 0.853259E+09 | 0.411913E+09 | 0.441346E+09 | 0.926364E+09 | 0.925067E+09 |
March | 0.111139E+10 | 0.536035E+09 | 0.575350E+09 | 0.136799E+10 | 0.867783E+09 |
April | 0.118023E+10 | 0.533809E+09 | 0.646418E+09 | 0.167063E+10 | 0.508965E+09 |
May | 0.125698E+10 | 0.545037E+09 | 0.711940E+09 | 0.217876E+10 | 0.150084E+09 |
June | 0.123364E+10 | 0.489202E+09 | 0.744439E+09 | 0.220593E+10 | 0.108601E+09 |
July | 0.122907E+10 | 0.449755E+09 | 0.779313E+09 | 0.220592E+10 | 64282561.20 |
August | 0.113258E+10 | 0.389393E+09 | 0.743187E+09 | 0.203533E+10 | 94663389.97 |
September | 0.970930E+09 | 0.333829E+09 | 0.637101E+09 | 0.165179E+10 | 0.170840E+09 |
October | 0.991421E+09 | 0.418377E+09 | 0.573044E+09 | 0.158889E+10 | 0.330248E+09 |
November | 0.849411E+09 | 0.433301E+09 | 0.416110E+09 | 0.104375E+10 | 0.747065E+09 |
December | 0.691069E+09 | 0.313024E+09 | 0.378046E+09 | 0.720219E+09 | 0.106163E+10 |
Annual Sum or Average | 0.123483E+11 | 0.528566E+10 | 0.706268E+10 | 0.184548E+11 | 0.624560E+10 |
Minimum of Months | 0.691069E+09 | 0.313024E+09 | 0.378046E+09 | 0.720219E+09 | 64282561.20 |
Maximum of Months | 0.125698E+10 | 0.545037E+09 | 0.779313E+09 | 0.220593E+10 | 0.121636E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171546E+10 | 0.122356E+10 | 0.491895E+09 | 0.229679E+10 | 0.106026E+10 |
February | 0.140497E+10 | 0.909452E+09 | 0.495514E+09 | 0.184931E+10 | 0.833082E+09 |
March | 0.992684E+09 | 0.447837E+09 | 0.544847E+09 | 0.121211E+10 | 0.822986E+09 |
April | 0.711930E+09 | 0.166583E+09 | 0.545347E+09 | 0.886524E+09 | 0.499512E+09 |
May | 0.562122E+09 | 23675206.03 | 0.538447E+09 | 0.100764E+10 | 0.139713E+09 |
June | 0.537477E+09 | 4905599.62 | 0.532571E+09 | 0.104030E+10 | 0.107755E+09 |
July | 0.581378E+09 | 10546313.97 | 0.570831E+09 | 0.110625E+10 | 67260752.44 |
August | 0.683894E+09 | 81882563.40 | 0.602011E+09 | 0.123393E+10 | 0.105112E+09 |
September | 0.794161E+09 | 0.209149E+09 | 0.585012E+09 | 0.131228E+10 | 0.165660E+09 |
October | 0.127342E+10 | 0.663276E+09 | 0.610145E+09 | 0.203806E+10 | 0.327625E+09 |
November | 0.156875E+10 | 0.108022E+10 | 0.488533E+09 | 0.225817E+10 | 0.694085E+09 |
December | 0.167626E+10 | 0.120395E+10 | 0.472308E+09 | 0.235268E+10 | 0.955384E+09 |
Annual Sum or Average | 0.125025E+11 | 0.602504E+10 | 0.647746E+10 | 0.185940E+11 | 0.577843E+10 |
Minimum of Months | 0.537477E+09 | 4905599.62 | 0.472308E+09 | 0.886524E+09 | 67260752.44 |
Maximum of Months | 0.171546E+10 | 0.122356E+10 | 0.610145E+09 | 0.235268E+10 | 0.106026E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171546E+10 | 0.122356E+10 | 0.491894E+09 | 0.229679E+10 | 0.106026E+10 |
February | 0.140496E+10 | 0.909451E+09 | 0.495514E+09 | 0.184931E+10 | 0.833082E+09 |
March | 0.992683E+09 | 0.447836E+09 | 0.544847E+09 | 0.121211E+10 | 0.822986E+09 |
April | 0.711930E+09 | 0.166583E+09 | 0.545347E+09 | 0.886524E+09 | 0.499512E+09 |
May | 0.562121E+09 | 23675177.63 | 0.538446E+09 | 0.100764E+10 | 0.139713E+09 |
June | 0.537476E+09 | 4905593.74 | 0.532571E+09 | 0.104030E+10 | 0.107755E+09 |
July | 0.581377E+09 | 10546301.31 | 0.570831E+09 | 0.110625E+10 | 67260671.59 |
August | 0.683893E+09 | 81882465.15 | 0.602011E+09 | 0.123393E+10 | 0.105112E+09 |
September | 0.794160E+09 | 0.209149E+09 | 0.585011E+09 | 0.131228E+10 | 0.165660E+09 |
October | 0.127342E+10 | 0.663276E+09 | 0.610144E+09 | 0.203806E+10 | 0.327624E+09 |
November | 0.156875E+10 | 0.108022E+10 | 0.488533E+09 | 0.225817E+10 | 0.694085E+09 |
December | 0.167625E+10 | 0.120395E+10 | 0.472307E+09 | 0.235268E+10 | 0.955384E+09 |
Annual Sum or Average | 0.125025E+11 | 0.602503E+10 | 0.647746E+10 | 0.185940E+11 | 0.577843E+10 |
Minimum of Months | 0.537476E+09 | 4905593.74 | 0.472307E+09 | 0.886524E+09 | 67260671.59 |
Maximum of Months | 0.171546E+10 | 0.122356E+10 | 0.610144E+09 | 0.235268E+10 | 0.106026E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171546E+10 | 0.122356E+10 | 0.491895E+09 | 0.229679E+10 | 0.106026E+10 |
February | 0.140497E+10 | 0.909452E+09 | 0.495514E+09 | 0.184931E+10 | 0.833082E+09 |
March | 0.992684E+09 | 0.447837E+09 | 0.544847E+09 | 0.121211E+10 | 0.822986E+09 |
April | 0.711930E+09 | 0.166583E+09 | 0.545347E+09 | 0.886524E+09 | 0.499512E+09 |
May | 0.562122E+09 | 23675206.03 | 0.538447E+09 | 0.100764E+10 | 0.139713E+09 |
June | 0.537477E+09 | 4905599.62 | 0.532571E+09 | 0.104030E+10 | 0.107755E+09 |
July | 0.581378E+09 | 10546313.97 | 0.570831E+09 | 0.110625E+10 | 67260752.44 |
August | 0.683894E+09 | 81882563.40 | 0.602011E+09 | 0.123393E+10 | 0.105112E+09 |
September | 0.794161E+09 | 0.209149E+09 | 0.585012E+09 | 0.131228E+10 | 0.165660E+09 |
October | 0.127342E+10 | 0.663276E+09 | 0.610145E+09 | 0.203806E+10 | 0.327625E+09 |
November | 0.156875E+10 | 0.108022E+10 | 0.488533E+09 | 0.225817E+10 | 0.694085E+09 |
December | 0.167626E+10 | 0.120395E+10 | 0.472308E+09 | 0.235268E+10 | 0.955384E+09 |
Annual Sum or Average | 0.125025E+11 | 0.602504E+10 | 0.647746E+10 | 0.185940E+11 | 0.577843E+10 |
Minimum of Months | 0.537477E+09 | 4905599.62 | 0.472308E+09 | 0.886524E+09 | 67260752.44 |
Maximum of Months | 0.171546E+10 | 0.122356E+10 | 0.610145E+09 | 0.235268E+10 | 0.106026E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171546E+10 | 0.122356E+10 | 0.491894E+09 | 0.229679E+10 | 0.106026E+10 |
February | 0.140496E+10 | 0.909451E+09 | 0.495514E+09 | 0.184931E+10 | 0.833082E+09 |
March | 0.992683E+09 | 0.447836E+09 | 0.544847E+09 | 0.121211E+10 | 0.822986E+09 |
April | 0.711930E+09 | 0.166583E+09 | 0.545347E+09 | 0.886524E+09 | 0.499512E+09 |
May | 0.562121E+09 | 23675177.63 | 0.538446E+09 | 0.100764E+10 | 0.139713E+09 |
June | 0.537476E+09 | 4905593.74 | 0.532571E+09 | 0.104030E+10 | 0.107755E+09 |
July | 0.581377E+09 | 10546301.31 | 0.570831E+09 | 0.110625E+10 | 67260671.59 |
August | 0.683893E+09 | 81882465.15 | 0.602011E+09 | 0.123393E+10 | 0.105112E+09 |
September | 0.794160E+09 | 0.209149E+09 | 0.585011E+09 | 0.131228E+10 | 0.165660E+09 |
October | 0.127342E+10 | 0.663276E+09 | 0.610144E+09 | 0.203806E+10 | 0.327624E+09 |
November | 0.156875E+10 | 0.108022E+10 | 0.488533E+09 | 0.225817E+10 | 0.694085E+09 |
December | 0.167625E+10 | 0.120395E+10 | 0.472307E+09 | 0.235268E+10 | 0.955384E+09 |
Annual Sum or Average | 0.125025E+11 | 0.602503E+10 | 0.647746E+10 | 0.185940E+11 | 0.577843E+10 |
Minimum of Months | 0.537476E+09 | 4905593.74 | 0.472307E+09 | 0.886524E+09 | 67260671.59 |
Maximum of Months | 0.171546E+10 | 0.122356E+10 | 0.610144E+09 | 0.235268E+10 | 0.106026E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.171539E+10 | 0.122351E+10 | 0.491875E+09 | 0.229670E+10 | 0.106021E+10 |
February | 0.140491E+10 | 0.909415E+09 | 0.495494E+09 | 0.184924E+10 | 0.833048E+09 |
March | 0.992644E+09 | 0.447819E+09 | 0.544825E+09 | 0.121206E+10 | 0.822953E+09 |
April | 0.711902E+09 | 0.166576E+09 | 0.545325E+09 | 0.886489E+09 | 0.499492E+09 |
May | 0.562099E+09 | 23674251.82 | 0.538425E+09 | 0.100760E+10 | 0.139708E+09 |
June | 0.537455E+09 | 4905401.90 | 0.532550E+09 | 0.104025E+10 | 0.107751E+09 |
July | 0.581354E+09 | 10545888.91 | 0.570808E+09 | 0.110620E+10 | 67258041.54 |
August | 0.683866E+09 | 81879263.17 | 0.601987E+09 | 0.123388E+10 | 0.105108E+09 |
September | 0.794129E+09 | 0.209141E+09 | 0.584988E+09 | 0.131223E+10 | 0.165654E+09 |
October | 0.127337E+10 | 0.663250E+09 | 0.610120E+09 | 0.203798E+10 | 0.327611E+09 |
November | 0.156869E+10 | 0.108018E+10 | 0.488514E+09 | 0.225808E+10 | 0.694057E+09 |
December | 0.167619E+10 | 0.120390E+10 | 0.472288E+09 | 0.235259E+10 | 0.955346E+09 |
Annual Sum or Average | 0.125020E+11 | 0.602480E+10 | 0.647720E+10 | 0.185933E+11 | 0.577820E+10 |
Minimum of Months | 0.537455E+09 | 4905401.90 | 0.472288E+09 | 0.886489E+09 | 67258041.54 |
Maximum of Months | 0.171539E+10 | 0.122351E+10 | 0.610120E+09 | 0.235259E+10 | 0.106021E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.902397E+09 | 0.487956E+09 | 0.414441E+09 | 0.984510E+09 | 0.138220E+10 |
February | 0.922832E+09 | 0.467066E+09 | 0.455767E+09 | 0.104952E+10 | 0.110268E+10 |
March | 0.100707E+10 | 0.445824E+09 | 0.561242E+09 | 0.120039E+10 | 0.108353E+10 |
April | 0.121047E+10 | 0.556873E+09 | 0.653598E+09 | 0.168019E+10 | 0.689929E+09 |
May | 0.104012E+10 | 0.338797E+09 | 0.701320E+09 | 0.180069E+10 | 0.216418E+09 |
June | 0.111818E+10 | 0.392064E+09 | 0.726116E+09 | 0.197102E+10 | 0.192725E+09 |
July | 0.105472E+10 | 0.292540E+09 | 0.762176E+09 | 0.183749E+10 | 0.157872E+09 |
August | 0.106648E+10 | 0.326464E+09 | 0.740017E+09 | 0.185758E+10 | 0.220465E+09 |
September | 0.950401E+09 | 0.326054E+09 | 0.624347E+09 | 0.159640E+10 | 0.239554E+09 |
October | 0.100543E+10 | 0.434440E+09 | 0.570987E+09 | 0.159867E+10 | 0.448585E+09 |
November | 0.833932E+09 | 0.419086E+09 | 0.414846E+09 | 0.103884E+10 | 0.950043E+09 |
December | 0.828929E+09 | 0.440808E+09 | 0.388121E+09 | 0.926807E+09 | 0.131888E+10 |
Annual Sum or Average | 0.119409E+11 | 0.492797E+10 | 0.701298E+10 | 0.175421E+11 | 0.800288E+10 |
Minimum of Months | 0.828929E+09 | 0.292540E+09 | 0.388121E+09 | 0.926807E+09 | 0.157872E+09 |
Maximum of Months | 0.121047E+10 | 0.556873E+09 | 0.762176E+09 | 0.197102E+10 | 0.138220E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.902397E+09 | 0.487956E+09 | 0.414441E+09 | 0.984510E+09 | 0.138220E+10 |
February | 0.922832E+09 | 0.467066E+09 | 0.455767E+09 | 0.104952E+10 | 0.110268E+10 |
March | 0.100707E+10 | 0.445824E+09 | 0.561242E+09 | 0.120039E+10 | 0.108353E+10 |
April | 0.121047E+10 | 0.556873E+09 | 0.653598E+09 | 0.168019E+10 | 0.689929E+09 |
May | 0.104012E+10 | 0.338797E+09 | 0.701320E+09 | 0.180069E+10 | 0.216418E+09 |
June | 0.111818E+10 | 0.392064E+09 | 0.726116E+09 | 0.197102E+10 | 0.192725E+09 |
July | 0.105472E+10 | 0.292540E+09 | 0.762176E+09 | 0.183749E+10 | 0.157872E+09 |
August | 0.106648E+10 | 0.326464E+09 | 0.740017E+09 | 0.185758E+10 | 0.220465E+09 |
September | 0.950401E+09 | 0.326054E+09 | 0.624347E+09 | 0.159640E+10 | 0.239554E+09 |
October | 0.100543E+10 | 0.434440E+09 | 0.570987E+09 | 0.159867E+10 | 0.448585E+09 |
November | 0.833932E+09 | 0.419086E+09 | 0.414846E+09 | 0.103884E+10 | 0.950043E+09 |
December | 0.828929E+09 | 0.440808E+09 | 0.388121E+09 | 0.926807E+09 | 0.131888E+10 |
Annual Sum or Average | 0.119409E+11 | 0.492797E+10 | 0.701298E+10 | 0.175421E+11 | 0.800288E+10 |
Minimum of Months | 0.828929E+09 | 0.292540E+09 | 0.388121E+09 | 0.926807E+09 | 0.157872E+09 |
Maximum of Months | 0.121047E+10 | 0.556873E+09 | 0.762176E+09 | 0.197102E+10 | 0.138220E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.902381E+09 | 0.487947E+09 | 0.414433E+09 | 0.984492E+09 | 0.138218E+10 |
February | 0.922815E+09 | 0.467057E+09 | 0.455758E+09 | 0.104950E+10 | 0.110266E+10 |
March | 0.100705E+10 | 0.445816E+09 | 0.561232E+09 | 0.120037E+10 | 0.108351E+10 |
April | 0.121045E+10 | 0.556863E+09 | 0.653586E+09 | 0.168016E+10 | 0.689916E+09 |
May | 0.104010E+10 | 0.338791E+09 | 0.701307E+09 | 0.180066E+10 | 0.216414E+09 |
June | 0.111816E+10 | 0.392057E+09 | 0.726103E+09 | 0.197098E+10 | 0.192721E+09 |
July | 0.105470E+10 | 0.292534E+09 | 0.762162E+09 | 0.183746E+10 | 0.157869E+09 |
August | 0.106646E+10 | 0.326458E+09 | 0.740004E+09 | 0.185755E+10 | 0.220461E+09 |
September | 0.950384E+09 | 0.326048E+09 | 0.624336E+09 | 0.159637E+10 | 0.239550E+09 |
October | 0.100541E+10 | 0.434432E+09 | 0.570976E+09 | 0.159865E+10 | 0.448577E+09 |
November | 0.833917E+09 | 0.419078E+09 | 0.414839E+09 | 0.103882E+10 | 0.950026E+09 |
December | 0.828913E+09 | 0.440800E+09 | 0.388114E+09 | 0.926790E+09 | 0.131885E+10 |
Annual Sum or Average | 0.119407E+11 | 0.492788E+10 | 0.701285E+10 | 0.175418E+11 | 0.800274E+10 |
Minimum of Months | 0.828913E+09 | 0.292534E+09 | 0.388114E+09 | 0.926790E+09 | 0.157869E+09 |
Maximum of Months | 0.121045E+10 | 0.556863E+09 | 0.762162E+09 | 0.197098E+10 | 0.138218E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148346E+10 | 0.00 | 0.148346E+10 | 0.952018E+09 | 0.533600E+10 |
February | 0.158075E+10 | 0.00 | 0.158075E+10 | 0.117192E+10 | 0.404148E+10 |
March | 0.203029E+10 | 0.00 | 0.203029E+10 | 0.188845E+10 | 0.382261E+10 |
April | 0.231877E+10 | 9395236.22 | 0.230938E+10 | 0.290329E+10 | 0.229841E+10 |
May | 0.271369E+10 | 98824883.04 | 0.261487E+10 | 0.499729E+10 | 0.631783E+09 |
June | 0.298633E+10 | 0.206161E+09 | 0.278017E+10 | 0.564935E+10 | 0.520143E+09 |
July | 0.299486E+10 | 0.113670E+09 | 0.288119E+10 | 0.571842E+10 | 0.349851E+09 |
August | 0.268219E+10 | 20937872.69 | 0.266126E+10 | 0.528528E+10 | 0.501237E+09 |
September | 0.224220E+10 | 167848.03 | 0.224204E+10 | 0.409079E+10 | 0.708575E+09 |
October | 0.201338E+10 | 0.00 | 0.201338E+10 | 0.339382E+10 | 0.144789E+10 |
November | 0.147917E+10 | 0.00 | 0.147917E+10 | 0.145832E+10 | 0.327365E+10 |
December | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.103802E+10 | 0.455350E+10 |
Annual Sum or Average | 0.259041E+11 | 0.449157E+09 | 0.254550E+11 | 0.385470E+11 | 0.274851E+11 |
Minimum of Months | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.952018E+09 | 0.349851E+09 |
Maximum of Months | 0.299486E+10 | 0.206161E+09 | 0.288119E+10 | 0.571842E+10 | 0.533600E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254515E+10 | 0.129597E+10 | 0.124918E+10 | 0.261916E+10 | 0.337344E+10 |
February | 0.255980E+10 | 0.123575E+10 | 0.132405E+10 | 0.280971E+10 | 0.256585E+10 |
March | 0.333418E+10 | 0.160812E+10 | 0.172606E+10 | 0.409369E+10 | 0.245247E+10 |
April | 0.354071E+10 | 0.160144E+10 | 0.193927E+10 | 0.495199E+10 | 0.153147E+10 |
May | 0.377096E+10 | 0.163512E+10 | 0.213584E+10 | 0.646205E+10 | 0.457170E+09 |
June | 0.370095E+10 | 0.146762E+10 | 0.223334E+10 | 0.654152E+10 | 0.376251E+09 |
July | 0.368724E+10 | 0.134928E+10 | 0.233796E+10 | 0.652669E+10 | 0.257169E+09 |
August | 0.339777E+10 | 0.116819E+10 | 0.222958E+10 | 0.602448E+10 | 0.361757E+09 |
September | 0.291281E+10 | 0.100149E+10 | 0.191132E+10 | 0.490575E+10 | 0.503323E+09 |
October | 0.297429E+10 | 0.125514E+10 | 0.171915E+10 | 0.471646E+10 | 0.977236E+09 |
November | 0.254825E+10 | 0.129991E+10 | 0.124834E+10 | 0.313323E+10 | 0.210679E+10 |
December | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.219865E+10 | 0.293965E+10 |
Annual Sum or Average | 0.370453E+11 | 0.158571E+11 | 0.211882E+11 | 0.549834E+11 | 0.179026E+11 |
Minimum of Months | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.219865E+10 | 0.257169E+09 |
Maximum of Months | 0.377096E+10 | 0.163512E+10 | 0.233796E+10 | 0.654152E+10 | 0.337344E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.857718E+10 | 0.611774E+10 | 0.245944E+10 | 0.113815E+11 | 0.518301E+10 |
February | 0.702474E+10 | 0.454720E+10 | 0.247754E+10 | 0.919207E+10 | 0.402664E+10 |
March | 0.496336E+10 | 0.223916E+10 | 0.272420E+10 | 0.607416E+10 | 0.389088E+10 |
April | 0.355961E+10 | 0.832905E+09 | 0.272670E+10 | 0.447375E+10 | 0.239592E+10 |
May | 0.281058E+10 | 0.118375E+09 | 0.269220E+10 | 0.507474E+10 | 0.662789E+09 |
June | 0.268735E+10 | 24527701.52 | 0.266282E+10 | 0.524031E+10 | 0.544002E+09 |
July | 0.290685E+10 | 52730932.22 | 0.285412E+10 | 0.558296E+10 | 0.351133E+09 |
August | 0.341943E+10 | 0.409408E+09 | 0.301002E+10 | 0.621246E+10 | 0.545184E+09 |
September | 0.397076E+10 | 0.104573E+10 | 0.292502E+10 | 0.656110E+10 | 0.788334E+09 |
October | 0.636703E+10 | 0.331634E+10 | 0.305069E+10 | 0.101219E+11 | 0.162261E+10 |
November | 0.784368E+10 | 0.540104E+10 | 0.244264E+10 | 0.112175E+11 | 0.337119E+10 |
December | 0.838118E+10 | 0.601967E+10 | 0.236151E+10 | 0.116953E+11 | 0.459548E+10 |
Annual Sum or Average | 0.625117E+11 | 0.301248E+11 | 0.323869E+11 | 0.928278E+11 | 0.279772E+11 |
Minimum of Months | 0.268735E+10 | 24527701.52 | 0.236151E+10 | 0.447375E+10 | 0.351133E+09 |
Maximum of Months | 0.857718E+10 | 0.611774E+10 | 0.305069E+10 | 0.116953E+11 | 0.518301E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270716E+10 | 0.146385E+10 | 0.124331E+10 | 0.305988E+10 | 0.364505E+10 |
February | 0.276847E+10 | 0.140118E+10 | 0.136729E+10 | 0.326786E+10 | 0.281958E+10 |
March | 0.302117E+10 | 0.133746E+10 | 0.168371E+10 | 0.373824E+10 | 0.270553E+10 |
April | 0.363138E+10 | 0.167060E+10 | 0.196077E+10 | 0.517597E+10 | 0.172943E+10 |
May | 0.312032E+10 | 0.101638E+10 | 0.210394E+10 | 0.546124E+10 | 0.547842E+09 |
June | 0.335451E+10 | 0.117618E+10 | 0.217833E+10 | 0.599683E+10 | 0.471510E+09 |
July | 0.316411E+10 | 0.877610E+09 | 0.228650E+10 | 0.565098E+10 | 0.338960E+09 |
August | 0.319941E+10 | 0.979382E+09 | 0.222003E+10 | 0.573908E+10 | 0.460406E+09 |
September | 0.285118E+10 | 0.978152E+09 | 0.187302E+10 | 0.484431E+10 | 0.594174E+09 |
October | 0.301625E+10 | 0.130331E+10 | 0.171294E+10 | 0.488922E+10 | 0.112929E+10 |
November | 0.250177E+10 | 0.125724E+10 | 0.124453E+10 | 0.325515E+10 | 0.235543E+10 |
December | 0.248676E+10 | 0.132241E+10 | 0.116435E+10 | 0.295053E+10 | 0.317279E+10 |
Annual Sum or Average | 0.358225E+11 | 0.147838E+11 | 0.210387E+11 | 0.540293E+11 | 0.199700E+11 |
Minimum of Months | 0.248676E+10 | 0.877610E+09 | 0.116435E+10 | 0.295053E+10 | 0.338960E+09 |
Maximum of Months | 0.363138E+10 | 0.167060E+10 | 0.228650E+10 | 0.599683E+10 | 0.364505E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148346E+10 | 0.00 | 0.148346E+10 | 0.103946E+10 | 0.490924E+10 |
February | 0.158075E+10 | 0.00 | 0.158075E+10 | 0.123303E+10 | 0.372245E+10 |
March | 0.203029E+10 | 0.00 | 0.203029E+10 | 0.192496E+10 | 0.360068E+10 |
April | 0.231877E+10 | 9395236.22 | 0.230938E+10 | 0.288359E+10 | 0.223663E+10 |
May | 0.271369E+10 | 98824883.04 | 0.261487E+10 | 0.490718E+10 | 0.666458E+09 |
June | 0.298633E+10 | 0.206161E+09 | 0.278017E+10 | 0.554875E+10 | 0.557994E+09 |
July | 0.299486E+10 | 0.113670E+09 | 0.288119E+10 | 0.559584E+10 | 0.389482E+09 |
August | 0.268219E+10 | 20937872.69 | 0.266126E+10 | 0.519247E+10 | 0.529746E+09 |
September | 0.224220E+10 | 167848.03 | 0.224204E+10 | 0.400461E+10 | 0.730746E+09 |
October | 0.201338E+10 | 0.00 | 0.201338E+10 | 0.335520E+10 | 0.141445E+10 |
November | 0.147917E+10 | 0.00 | 0.147917E+10 | 0.151330E+10 | 0.303245E+10 |
December | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.110701E+10 | 0.418796E+10 |
Annual Sum or Average | 0.259041E+11 | 0.449157E+09 | 0.254550E+11 | 0.383054E+11 | 0.259783E+11 |
Minimum of Months | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.103946E+10 | 0.389482E+09 |
Maximum of Months | 0.299486E+10 | 0.206161E+09 | 0.288119E+10 | 0.559584E+10 | 0.490924E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.254515E+10 | 0.129597E+10 | 0.124918E+10 | 0.273141E+10 | 0.309362E+10 |
February | 0.255980E+10 | 0.123575E+10 | 0.132405E+10 | 0.289067E+10 | 0.236893E+10 |
March | 0.333418E+10 | 0.160812E+10 | 0.172606E+10 | 0.413700E+10 | 0.232266E+10 |
April | 0.354071E+10 | 0.160144E+10 | 0.193927E+10 | 0.495339E+10 | 0.149680E+10 |
May | 0.377096E+10 | 0.163512E+10 | 0.213584E+10 | 0.642189E+10 | 0.475343E+09 |
June | 0.370095E+10 | 0.146762E+10 | 0.223334E+10 | 0.649843E+10 | 0.398299E+09 |
July | 0.368724E+10 | 0.134928E+10 | 0.233796E+10 | 0.647393E+10 | 0.280766E+09 |
August | 0.339777E+10 | 0.116819E+10 | 0.222958E+10 | 0.598638E+10 | 0.378080E+09 |
September | 0.291281E+10 | 0.100149E+10 | 0.191132E+10 | 0.487359E+10 | 0.514062E+09 |
October | 0.297429E+10 | 0.125514E+10 | 0.171915E+10 | 0.470849E+10 | 0.954998E+09 |
November | 0.254825E+10 | 0.129991E+10 | 0.124834E+10 | 0.318876E+10 | 0.197521E+10 |
December | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.227927E+10 | 0.270631E+10 |
Annual Sum or Average | 0.370453E+11 | 0.158571E+11 | 0.211882E+11 | 0.551432E+11 | 0.169651E+11 |
Minimum of Months | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.227927E+10 | 0.280766E+09 |
Maximum of Months | 0.377096E+10 | 0.163512E+10 | 0.233796E+10 | 0.649843E+10 | 0.309362E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.857718E+10 | 0.611774E+10 | 0.245944E+10 | 0.114833E+11 | 0.482728E+10 |
February | 0.702474E+10 | 0.454720E+10 | 0.247754E+10 | 0.927370E+10 | 0.375558E+10 |
March | 0.496336E+10 | 0.223916E+10 | 0.272420E+10 | 0.610565E+10 | 0.368655E+10 |
April | 0.355961E+10 | 0.832905E+09 | 0.272670E+10 | 0.445571E+10 | 0.233795E+10 |
May | 0.281058E+10 | 0.118375E+09 | 0.269220E+10 | 0.499132E+10 | 0.698981E+09 |
June | 0.268735E+10 | 24527701.52 | 0.266282E+10 | 0.514827E+10 | 0.585654E+09 |
July | 0.290685E+10 | 52730932.22 | 0.285412E+10 | 0.546448E+10 | 0.390214E+09 |
August | 0.341943E+10 | 0.409408E+09 | 0.301002E+10 | 0.612780E+10 | 0.575164E+09 |
September | 0.397076E+10 | 0.104573E+10 | 0.292502E+10 | 0.648904E+10 | 0.809995E+09 |
October | 0.636703E+10 | 0.331634E+10 | 0.305069E+10 | 0.100884E+11 | 0.159014E+10 |
November | 0.784368E+10 | 0.540104E+10 | 0.244264E+10 | 0.112695E+11 | 0.318862E+10 |
December | 0.838118E+10 | 0.601967E+10 | 0.236151E+10 | 0.117808E+11 | 0.428395E+10 |
Annual Sum or Average | 0.625117E+11 | 0.301248E+11 | 0.323869E+11 | 0.926780E+11 | 0.267301E+11 |
Minimum of Months | 0.268735E+10 | 24527701.52 | 0.236151E+10 | 0.445571E+10 | 0.390214E+09 |
Maximum of Months | 0.857718E+10 | 0.611774E+10 | 0.305069E+10 | 0.117808E+11 | 0.482728E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270716E+10 | 0.146385E+10 | 0.124331E+10 | 0.310040E+10 | 0.341219E+10 |
February | 0.276847E+10 | 0.140118E+10 | 0.136729E+10 | 0.329337E+10 | 0.264388E+10 |
March | 0.302117E+10 | 0.133746E+10 | 0.168371E+10 | 0.374494E+10 | 0.257498E+10 |
April | 0.363138E+10 | 0.167060E+10 | 0.196077E+10 | 0.514869E+10 | 0.168565E+10 |
May | 0.312032E+10 | 0.101638E+10 | 0.210394E+10 | 0.540746E+10 | 0.563391E+09 |
June | 0.335451E+10 | 0.117618E+10 | 0.217833E+10 | 0.593840E+10 | 0.489198E+09 |
July | 0.316411E+10 | 0.877610E+09 | 0.228650E+10 | 0.558499E+10 | 0.358343E+09 |
August | 0.319941E+10 | 0.979382E+09 | 0.222003E+10 | 0.568360E+10 | 0.475769E+09 |
September | 0.285118E+10 | 0.978152E+09 | 0.187302E+10 | 0.479740E+10 | 0.602661E+09 |
October | 0.301625E+10 | 0.130331E+10 | 0.171294E+10 | 0.486027E+10 | 0.110713E+10 |
November | 0.250177E+10 | 0.125724E+10 | 0.124453E+10 | 0.327284E+10 | 0.222435E+10 |
December | 0.248676E+10 | 0.132241E+10 | 0.116435E+10 | 0.298120E+10 | 0.296757E+10 |
Annual Sum or Average | 0.358225E+11 | 0.147838E+11 | 0.210387E+11 | 0.538136E+11 | 0.191051E+11 |
Minimum of Months | 0.248676E+10 | 0.877610E+09 | 0.116435E+10 | 0.298120E+10 | 0.358343E+09 |
Maximum of Months | 0.363138E+10 | 0.167060E+10 | 0.228650E+10 | 0.593840E+10 | 0.341219E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 295.19 | 2259.87 | 553.86 | 0.00 | 553.86 | 0.00 | 0.00 |
February | 423.11 | 1918.06 | 653.42 | 0.00 | 653.42 | 0.00 | 0.00 |
March | 645.77 | 1621.18 | 758.03 | 0.00 | 758.03 | 0.00 | 0.00 |
April | 1082.81 | 965.51 | 894.59 | 3.62 | 890.97 | 0.00 | 0.00 |
May | 1849.70 | 253.81 | 1013.18 | 36.90 | 976.28 | 0.00 | 0.00 |
June | 2164.90 | 198.63 | 1152.14 | 79.54 | 1072.60 | 0.00 | 0.00 |
July | 2118.09 | 124.48 | 1118.16 | 42.44 | 1075.72 | 0.00 | 0.00 |
August | 1947.50 | 184.67 | 1001.42 | 7.82 | 993.60 | 0.00 | 0.00 |
September | 1557.00 | 305.74 | 865.05 | 0.06 | 864.99 | 0.00 | 0.00 |
October | 1237.01 | 595.78 | 751.71 | 0.00 | 751.71 | 0.00 | 0.00 |
November | 507.12 | 1452.68 | 570.67 | 0.00 | 570.67 | 0.00 | 0.00 |
December | 326.22 | 1989.55 | 514.88 | 0.00 | 514.88 | 0.00 | 0.00 |
Annual Sum or Average | 1184.13 | 984.36 | 821.42 | 14.24 | 807.18 | 0.00 | 0.00 |
Minimum of Months | 295.19 | 124.48 | 514.88 | 0.00 | 514.88 | 0.00 | 0.00 |
Maximum of Months | 2164.90 | 2259.87 | 1152.14 | 79.54 | 1075.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 962.41 | 1362.43 | 950.25 | 483.86 | 466.39 | 0.00 | 0.00 |
February | 1148.78 | 1147.17 | 1058.12 | 510.81 | 547.31 | 0.00 | 0.00 |
March | 1532.27 | 971.99 | 1244.85 | 600.41 | 644.44 | 0.00 | 0.00 |
April | 1933.62 | 589.09 | 1366.02 | 617.84 | 748.18 | 0.00 | 0.00 |
May | 2440.40 | 168.11 | 1407.92 | 610.49 | 797.43 | 0.00 | 0.00 |
June | 2553.19 | 125.70 | 1427.84 | 566.21 | 861.63 | 0.00 | 0.00 |
July | 2470.81 | 72.00 | 1376.66 | 503.76 | 872.90 | 0.00 | 0.00 |
August | 2279.75 | 106.03 | 1268.59 | 436.15 | 832.43 | 0.00 | 0.00 |
September | 1911.81 | 197.73 | 1123.77 | 386.38 | 737.39 | 0.00 | 0.00 |
October | 1779.69 | 369.91 | 1110.48 | 468.62 | 641.86 | 0.00 | 0.00 |
November | 1208.06 | 864.67 | 983.13 | 501.51 | 481.61 | 0.00 | 0.00 |
December | 806.71 | 1189.12 | 774.06 | 350.61 | 423.44 | 0.00 | 0.00 |
Annual Sum or Average | 1755.62 | 594.15 | 1174.70 | 502.83 | 671.88 | 0.00 | 0.00 |
Minimum of Months | 806.71 | 72.00 | 774.06 | 350.61 | 423.44 | 0.00 | 0.00 |
Maximum of Months | 2553.19 | 1362.43 | 1427.84 | 617.84 | 872.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4287.58 | 1979.26 | 3202.36 | 2284.11 | 918.25 | 0.00 | 0.00 |
February | 3822.12 | 1721.80 | 2903.76 | 1879.64 | 1024.12 | 0.00 | 0.00 |
March | 2262.73 | 1536.33 | 1853.11 | 836.01 | 1017.10 | 0.00 | 0.00 |
April | 1710.10 | 963.56 | 1373.31 | 321.34 | 1051.97 | 0.00 | 0.00 |
May | 1881.04 | 260.81 | 1049.35 | 44.20 | 1005.16 | 0.00 | 0.00 |
June | 2006.73 | 207.86 | 1036.79 | 9.46 | 1027.33 | 0.00 | 0.00 |
July | 2065.11 | 125.56 | 1085.30 | 19.69 | 1065.61 | 0.00 | 0.00 |
August | 2303.46 | 196.22 | 1276.67 | 152.86 | 1123.82 | 0.00 | 0.00 |
September | 2531.39 | 319.56 | 1531.93 | 403.45 | 1128.49 | 0.00 | 0.00 |
October | 3804.60 | 611.60 | 2377.18 | 1238.18 | 1139.00 | 0.00 | 0.00 |
November | 4356.00 | 1338.89 | 3026.12 | 2083.74 | 942.38 | 0.00 | 0.00 |
December | 4391.92 | 1783.48 | 3129.19 | 2247.50 | 881.69 | 0.00 | 0.00 |
Annual Sum or Average | 2948.04 | 916.16 | 1982.24 | 955.26 | 1026.99 | 0.00 | 0.00 |
Minimum of Months | 1710.10 | 125.56 | 1036.79 | 9.46 | 881.69 | 0.00 | 0.00 |
Maximum of Months | 4391.92 | 1979.26 | 3202.36 | 2284.11 | 1139.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1102.71 | 1548.16 | 1010.74 | 546.54 | 464.20 | 0.00 | 0.00 |
February | 1301.48 | 1367.41 | 1144.38 | 579.19 | 565.18 | 0.00 | 0.00 |
March | 1344.52 | 1213.62 | 1127.98 | 499.35 | 628.63 | 0.00 | 0.00 |
April | 1944.65 | 798.52 | 1401.00 | 644.53 | 756.47 | 0.00 | 0.00 |
May | 2016.89 | 242.40 | 1165.00 | 379.48 | 785.52 | 0.00 | 0.00 |
June | 2281.26 | 223.06 | 1294.18 | 453.78 | 840.41 | 0.00 | 0.00 |
July | 2058.11 | 176.83 | 1181.35 | 327.66 | 853.69 | 0.00 | 0.00 |
August | 2080.61 | 246.93 | 1194.53 | 365.66 | 828.87 | 0.00 | 0.00 |
September | 1847.67 | 277.26 | 1099.99 | 377.38 | 722.62 | 0.00 | 0.00 |
October | 1790.62 | 502.44 | 1126.14 | 486.60 | 639.54 | 0.00 | 0.00 |
November | 1202.36 | 1099.58 | 965.19 | 485.05 | 480.14 | 0.00 | 0.00 |
December | 1038.08 | 1477.23 | 928.45 | 493.73 | 434.72 | 0.00 | 0.00 |
Annual Sum or Average | 1668.76 | 761.30 | 1135.93 | 468.79 | 667.14 | 0.00 | 0.00 |
Minimum of Months | 1038.08 | 176.83 | 928.45 | 327.66 | 434.72 | 0.00 | 0.00 |
Maximum of Months | 2281.26 | 1548.16 | 1401.00 | 644.53 | 853.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 355.44 | 1992.24 | 553.86 | 0.00 | 553.86 | 0.00 | 0.00 |
February | 484.43 | 1670.58 | 653.42 | 0.00 | 653.42 | 0.00 | 0.00 |
March | 705.07 | 1427.20 | 758.02 | 0.00 | 758.02 | 0.00 | 0.00 |
April | 1120.10 | 886.73 | 894.59 | 3.62 | 890.96 | 0.00 | 0.00 |
May | 1865.78 | 235.88 | 1013.18 | 36.90 | 976.28 | 0.00 | 0.00 |
June | 2179.53 | 200.67 | 1152.13 | 79.54 | 1072.60 | 0.00 | 0.00 |
July | 2135.01 | 130.62 | 1118.15 | 42.44 | 1075.71 | 0.00 | 0.00 |
August | 1973.30 | 187.14 | 1001.42 | 7.82 | 993.60 | 0.00 | 0.00 |
September | 1578.24 | 273.37 | 865.05 | 0.06 | 864.98 | 0.00 | 0.00 |
October | 1267.11 | 540.58 | 751.71 | 0.00 | 751.71 | 0.00 | 0.00 |
November | 562.62 | 1262.98 | 570.67 | 0.00 | 570.67 | 0.00 | 0.00 |
December | 387.55 | 1700.08 | 514.87 | 0.00 | 514.87 | 0.00 | 0.00 |
Annual Sum or Average | 1222.32 | 871.55 | 821.42 | 14.24 | 807.17 | 0.00 | 0.00 |
Minimum of Months | 355.44 | 130.62 | 514.87 | 0.00 | 514.87 | 0.00 | 0.00 |
Maximum of Months | 2179.53 | 1992.24 | 1152.13 | 79.54 | 1075.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 977.88 | 1259.50 | 950.25 | 483.86 | 466.39 | 0.00 | 0.00 |
February | 1161.42 | 1060.62 | 1058.12 | 510.81 | 547.31 | 0.00 | 0.00 |
March | 1528.41 | 915.65 | 1244.84 | 600.40 | 644.44 | 0.00 | 0.00 |
April | 1910.49 | 590.84 | 1366.01 | 617.84 | 748.17 | 0.00 | 0.00 |
May | 2412.65 | 170.69 | 1407.91 | 610.48 | 797.43 | 0.00 | 0.00 |
June | 2523.74 | 145.16 | 1427.84 | 566.21 | 861.63 | 0.00 | 0.00 |
July | 2436.79 | 96.02 | 1376.66 | 503.76 | 872.89 | 0.00 | 0.00 |
August | 2249.28 | 135.06 | 1268.58 | 436.15 | 832.43 | 0.00 | 0.00 |
September | 1892.65 | 194.18 | 1123.77 | 386.38 | 737.39 | 0.00 | 0.00 |
October | 1760.92 | 364.86 | 1110.47 | 468.62 | 641.86 | 0.00 | 0.00 |
November | 1208.81 | 812.80 | 983.12 | 501.51 | 481.61 | 0.00 | 0.00 |
December | 820.88 | 1097.54 | 774.05 | 350.61 | 423.44 | 0.00 | 0.00 |
Annual Sum or Average | 1743.51 | 567.69 | 1174.70 | 502.83 | 671.87 | 0.00 | 0.00 |
Minimum of Months | 820.88 | 96.02 | 774.05 | 350.61 | 423.44 | 0.00 | 0.00 |
Maximum of Months | 2523.74 | 1259.50 | 1427.84 | 617.84 | 872.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4249.38 | 1935.11 | 3202.35 | 2284.10 | 918.25 | 0.00 | 0.00 |
February | 3799.63 | 1664.45 | 2903.75 | 1879.63 | 1024.12 | 0.00 | 0.00 |
March | 2267.83 | 1452.69 | 1853.11 | 836.01 | 1017.10 | 0.00 | 0.00 |
April | 1725.98 | 924.35 | 1373.31 | 321.34 | 1051.97 | 0.00 | 0.00 |
May | 1894.69 | 247.46 | 1049.35 | 44.20 | 1005.15 | 0.00 | 0.00 |
June | 2021.73 | 209.88 | 1036.79 | 9.46 | 1027.32 | 0.00 | 0.00 |
July | 2084.44 | 131.10 | 1085.29 | 19.69 | 1065.61 | 0.00 | 0.00 |
August | 2319.47 | 203.55 | 1276.67 | 152.86 | 1123.81 | 0.00 | 0.00 |
September | 2531.29 | 304.14 | 1531.93 | 403.45 | 1128.48 | 0.00 | 0.00 |
October | 3779.07 | 605.81 | 2377.18 | 1238.18 | 1139.00 | 0.00 | 0.00 |
November | 4327.76 | 1300.61 | 3026.11 | 2083.73 | 942.38 | 0.00 | 0.00 |
December | 4366.51 | 1715.76 | 3129.17 | 2247.49 | 881.69 | 0.00 | 0.00 |
Annual Sum or Average | 2943.55 | 887.15 | 1982.23 | 955.25 | 1026.98 | 0.00 | 0.00 |
Minimum of Months | 1725.98 | 131.10 | 1036.79 | 9.46 | 881.69 | 0.00 | 0.00 |
Maximum of Months | 4366.51 | 1935.11 | 3202.35 | 2284.10 | 1139.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1142.43 | 1360.90 | 1010.74 | 546.54 | 464.20 | 0.00 | 0.00 |
February | 1350.80 | 1165.50 | 1144.37 | 579.19 | 565.18 | 0.00 | 0.00 |
March | 1395.70 | 1010.13 | 1127.98 | 499.35 | 628.63 | 0.00 | 0.00 |
April | 1996.90 | 667.22 | 1400.99 | 644.52 | 756.47 | 0.00 | 0.00 |
May | 2038.99 | 204.54 | 1164.99 | 379.47 | 785.52 | 0.00 | 0.00 |
June | 2313.59 | 181.91 | 1294.18 | 453.77 | 840.40 | 0.00 | 0.00 |
July | 2109.83 | 126.55 | 1181.34 | 327.66 | 853.68 | 0.00 | 0.00 |
August | 2142.73 | 171.90 | 1194.52 | 365.66 | 828.86 | 0.00 | 0.00 |
September | 1868.95 | 229.23 | 1099.99 | 377.37 | 722.62 | 0.00 | 0.00 |
October | 1825.43 | 421.63 | 1126.14 | 486.60 | 639.54 | 0.00 | 0.00 |
November | 1255.84 | 908.73 | 965.19 | 485.05 | 480.14 | 0.00 | 0.00 |
December | 1101.60 | 1184.58 | 928.45 | 493.73 | 434.72 | 0.00 | 0.00 |
Annual Sum or Average | 1713.26 | 633.24 | 1135.92 | 468.79 | 667.13 | 0.00 | 0.00 |
Minimum of Months | 1101.60 | 126.55 | 928.45 | 327.66 | 434.72 | 0.00 | 0.00 |
Maximum of Months | 2313.59 | 1360.90 | 1400.99 | 644.52 | 853.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 388.09 | 1832.90 | 553.86 | 0.00 | 553.86 | 0.00 | 0.00 |
February | 509.68 | 1538.71 | 653.42 | 0.00 | 653.42 | 0.00 | 0.00 |
March | 718.70 | 1344.34 | 758.02 | 0.00 | 758.02 | 0.00 | 0.00 |
April | 1112.50 | 862.90 | 894.59 | 3.62 | 890.96 | 0.00 | 0.00 |
May | 1832.13 | 248.83 | 1013.18 | 36.90 | 976.28 | 0.00 | 0.00 |
June | 2140.72 | 215.28 | 1152.13 | 79.54 | 1072.60 | 0.00 | 0.00 |
July | 2089.25 | 145.42 | 1118.15 | 42.44 | 1075.71 | 0.00 | 0.00 |
August | 1938.65 | 197.78 | 1001.42 | 7.82 | 993.60 | 0.00 | 0.00 |
September | 1544.99 | 281.92 | 865.05 | 0.06 | 864.98 | 0.00 | 0.00 |
October | 1252.69 | 528.09 | 751.71 | 0.00 | 751.71 | 0.00 | 0.00 |
November | 583.83 | 1169.93 | 570.67 | 0.00 | 570.67 | 0.00 | 0.00 |
December | 413.31 | 1563.61 | 514.87 | 0.00 | 514.87 | 0.00 | 0.00 |
Annual Sum or Average | 1214.66 | 823.77 | 821.42 | 14.24 | 807.17 | 0.00 | 0.00 |
Minimum of Months | 388.09 | 145.42 | 514.87 | 0.00 | 514.87 | 0.00 | 0.00 |
Maximum of Months | 2140.72 | 1832.90 | 1152.13 | 79.54 | 1075.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1019.79 | 1155.03 | 950.25 | 483.86 | 466.39 | 0.00 | 0.00 |
February | 1194.89 | 979.22 | 1058.12 | 510.81 | 547.31 | 0.00 | 0.00 |
March | 1544.58 | 867.18 | 1244.84 | 600.40 | 644.44 | 0.00 | 0.00 |
April | 1911.03 | 577.47 | 1366.01 | 617.84 | 748.17 | 0.00 | 0.00 |
May | 2397.66 | 177.47 | 1407.91 | 610.48 | 797.43 | 0.00 | 0.00 |
June | 2507.11 | 153.66 | 1427.84 | 566.21 | 861.63 | 0.00 | 0.00 |
July | 2417.09 | 104.83 | 1376.66 | 503.76 | 872.89 | 0.00 | 0.00 |
August | 2235.06 | 141.16 | 1268.58 | 436.15 | 832.43 | 0.00 | 0.00 |
September | 1880.24 | 198.33 | 1123.77 | 386.38 | 737.39 | 0.00 | 0.00 |
October | 1757.95 | 356.56 | 1110.47 | 468.62 | 641.86 | 0.00 | 0.00 |
November | 1230.23 | 762.04 | 983.12 | 501.51 | 481.61 | 0.00 | 0.00 |
December | 850.98 | 1010.42 | 774.05 | 350.61 | 423.44 | 0.00 | 0.00 |
Annual Sum or Average | 1748.58 | 537.96 | 1174.70 | 502.83 | 671.87 | 0.00 | 0.00 |
Minimum of Months | 850.98 | 104.83 | 774.05 | 350.61 | 423.44 | 0.00 | 0.00 |
Maximum of Months | 2507.11 | 1155.03 | 1427.84 | 617.84 | 872.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4287.38 | 1802.30 | 3202.35 | 2284.10 | 918.25 | 0.00 | 0.00 |
February | 3833.37 | 1552.40 | 2903.75 | 1879.63 | 1024.12 | 0.00 | 0.00 |
March | 2279.59 | 1376.40 | 1853.11 | 836.01 | 1017.10 | 0.00 | 0.00 |
April | 1719.02 | 901.99 | 1373.31 | 321.34 | 1051.97 | 0.00 | 0.00 |
May | 1863.55 | 260.97 | 1049.35 | 44.20 | 1005.15 | 0.00 | 0.00 |
June | 1986.21 | 225.95 | 1036.79 | 9.46 | 1027.32 | 0.00 | 0.00 |
July | 2040.20 | 145.69 | 1085.29 | 19.69 | 1065.61 | 0.00 | 0.00 |
August | 2287.86 | 214.74 | 1276.67 | 152.86 | 1123.81 | 0.00 | 0.00 |
September | 2503.49 | 312.50 | 1531.93 | 403.45 | 1128.48 | 0.00 | 0.00 |
October | 3766.58 | 593.69 | 2377.18 | 1238.18 | 1139.00 | 0.00 | 0.00 |
November | 4347.81 | 1230.18 | 3026.11 | 2083.73 | 942.38 | 0.00 | 0.00 |
December | 4398.44 | 1599.44 | 3129.17 | 2247.49 | 881.69 | 0.00 | 0.00 |
Annual Sum or Average | 2938.80 | 847.61 | 1982.23 | 955.25 | 1026.98 | 0.00 | 0.00 |
Minimum of Months | 1719.02 | 145.69 | 1036.79 | 9.46 | 881.69 | 0.00 | 0.00 |
Maximum of Months | 4398.44 | 1802.30 | 3202.35 | 2284.10 | 1139.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1157.56 | 1273.96 | 1010.74 | 546.54 | 464.20 | 0.00 | 0.00 |
February | 1361.35 | 1092.87 | 1144.37 | 579.19 | 565.18 | 0.00 | 0.00 |
March | 1398.20 | 961.39 | 1127.98 | 499.35 | 628.63 | 0.00 | 0.00 |
April | 1986.38 | 650.33 | 1400.99 | 644.52 | 756.47 | 0.00 | 0.00 |
May | 2018.91 | 210.35 | 1164.99 | 379.47 | 785.52 | 0.00 | 0.00 |
June | 2291.05 | 188.73 | 1294.18 | 453.77 | 840.40 | 0.00 | 0.00 |
July | 2085.20 | 133.79 | 1181.34 | 327.66 | 853.68 | 0.00 | 0.00 |
August | 2122.01 | 177.63 | 1194.52 | 365.66 | 828.86 | 0.00 | 0.00 |
September | 1850.85 | 232.51 | 1099.99 | 377.37 | 722.62 | 0.00 | 0.00 |
October | 1814.62 | 413.35 | 1126.14 | 486.60 | 639.54 | 0.00 | 0.00 |
November | 1262.67 | 858.16 | 965.19 | 485.05 | 480.14 | 0.00 | 0.00 |
December | 1113.05 | 1107.97 | 928.45 | 493.73 | 434.72 | 0.00 | 0.00 |
Annual Sum or Average | 1706.42 | 605.82 | 1135.92 | 468.79 | 667.13 | 0.00 | 0.00 |
Minimum of Months | 1113.05 | 133.79 | 928.45 | 327.66 | 434.72 | 0.00 | 0.00 |
Maximum of Months | 2291.05 | 1273.96 | 1400.99 | 644.52 | 853.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.790643E+09 | 0.605283E+10 | 0.148346E+10 | 0.00 | 0.148346E+10 | 0.00 | 0.00 |
February | 0.102359E+10 | 0.464017E+10 | 0.158076E+10 | 0.00 | 0.158076E+10 | 0.00 | 0.00 |
March | 0.172964E+10 | 0.434216E+10 | 0.203030E+10 | 0.00 | 0.203030E+10 | 0.00 | 0.00 |
April | 0.280666E+10 | 0.250261E+10 | 0.231878E+10 | 9395269.58 | 0.230939E+10 | 0.00 | 0.00 |
May | 0.495424E+10 | 0.679805E+09 | 0.271370E+10 | 98825233.97 | 0.261488E+10 | 0.00 | 0.00 |
June | 0.561143E+10 | 0.514860E+09 | 0.298634E+10 | 0.206162E+09 | 0.278018E+10 | 0.00 | 0.00 |
July | 0.567308E+10 | 0.333399E+09 | 0.299487E+10 | 0.113670E+09 | 0.288120E+10 | 0.00 | 0.00 |
August | 0.521617E+10 | 0.494632E+09 | 0.268220E+10 | 20937947.05 | 0.266127E+10 | 0.00 | 0.00 |
September | 0.403574E+10 | 0.792474E+09 | 0.224221E+10 | 167848.63 | 0.224204E+10 | 0.00 | 0.00 |
October | 0.331322E+10 | 0.159574E+10 | 0.201339E+10 | 0.00 | 0.201339E+10 | 0.00 | 0.00 |
November | 0.131444E+10 | 0.376534E+10 | 0.147918E+10 | 0.00 | 0.147918E+10 | 0.00 | 0.00 |
December | 0.873748E+09 | 0.532881E+10 | 0.137905E+10 | 0.00 | 0.137905E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.373426E+11 | 0.310428E+11 | 0.259042E+11 | 0.449159E+09 | 0.254551E+11 | 0.00 | 0.00 |
Minimum of Months | 0.790643E+09 | 0.333399E+09 | 0.137905E+10 | 0.00 | 0.137905E+10 | 0.00 | 0.00 |
Maximum of Months | 0.567308E+10 | 0.605283E+10 | 0.299487E+10 | 0.206162E+09 | 0.288120E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.257772E+10 | 0.364914E+10 | 0.254516E+10 | 0.129598E+10 | 0.124919E+10 | 0.00 | 0.00 |
February | 0.277912E+10 | 0.277523E+10 | 0.255981E+10 | 0.123575E+10 | 0.132405E+10 | 0.00 | 0.00 |
March | 0.410403E+10 | 0.260338E+10 | 0.333420E+10 | 0.160813E+10 | 0.172607E+10 | 0.00 | 0.00 |
April | 0.501195E+10 | 0.152691E+10 | 0.354072E+10 | 0.160145E+10 | 0.193928E+10 | 0.00 | 0.00 |
May | 0.653636E+10 | 0.450256E+09 | 0.377097E+10 | 0.163513E+10 | 0.213585E+10 | 0.00 | 0.00 |
June | 0.661786E+10 | 0.325808E+09 | 0.370097E+10 | 0.146762E+10 | 0.223335E+10 | 0.00 | 0.00 |
July | 0.661783E+10 | 0.192850E+09 | 0.368725E+10 | 0.134928E+10 | 0.233797E+10 | 0.00 | 0.00 |
August | 0.610607E+10 | 0.283994E+09 | 0.339778E+10 | 0.116819E+10 | 0.222959E+10 | 0.00 | 0.00 |
September | 0.495542E+10 | 0.512525E+09 | 0.291282E+10 | 0.100150E+10 | 0.191133E+10 | 0.00 | 0.00 |
October | 0.476673E+10 | 0.990756E+09 | 0.297430E+10 | 0.125515E+10 | 0.171915E+10 | 0.00 | 0.00 |
November | 0.313130E+10 | 0.224122E+10 | 0.254826E+10 | 0.129992E+10 | 0.124834E+10 | 0.00 | 0.00 |
December | 0.216068E+10 | 0.318494E+10 | 0.207323E+10 | 0.939083E+09 | 0.113415E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.553651E+11 | 0.187370E+11 | 0.370455E+11 | 0.158572E+11 | 0.211883E+11 | 0.00 | 0.00 |
Minimum of Months | 0.216068E+10 | 0.192850E+09 | 0.207323E+10 | 0.939083E+09 | 0.113415E+10 | 0.00 | 0.00 |
Maximum of Months | 0.661786E+10 | 0.364914E+10 | 0.377097E+10 | 0.163513E+10 | 0.233797E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114839E+11 | 0.530124E+10 | 0.857721E+10 | 0.611776E+10 | 0.245945E+10 | 0.00 | 0.00 |
February | 0.924647E+10 | 0.416538E+10 | 0.702477E+10 | 0.454722E+10 | 0.247755E+10 | 0.00 | 0.00 |
March | 0.606050E+10 | 0.411490E+10 | 0.496338E+10 | 0.223916E+10 | 0.272421E+10 | 0.00 | 0.00 |
April | 0.443259E+10 | 0.249754E+10 | 0.355962E+10 | 0.832908E+09 | 0.272671E+10 | 0.00 | 0.00 |
May | 0.503817E+10 | 0.698560E+09 | 0.281059E+10 | 0.118375E+09 | 0.269221E+10 | 0.00 | 0.00 |
June | 0.520144E+10 | 0.538770E+09 | 0.268736E+10 | 24527788.62 | 0.266283E+10 | 0.00 | 0.00 |
July | 0.553119E+10 | 0.336301E+09 | 0.290686E+10 | 52731119.47 | 0.285413E+10 | 0.00 | 0.00 |
August | 0.616958E+10 | 0.525557E+09 | 0.341944E+10 | 0.409409E+09 | 0.301003E+10 | 0.00 | 0.00 |
September | 0.656136E+10 | 0.828295E+09 | 0.397077E+10 | 0.104574E+10 | 0.292503E+10 | 0.00 | 0.00 |
October | 0.101902E+11 | 0.163811E+10 | 0.636705E+10 | 0.331635E+10 | 0.305070E+10 | 0.00 | 0.00 |
November | 0.112908E+11 | 0.347040E+10 | 0.784371E+10 | 0.540106E+10 | 0.244265E+10 | 0.00 | 0.00 |
December | 0.117633E+11 | 0.477688E+10 | 0.838121E+10 | 0.601969E+10 | 0.236152E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.929695E+11 | 0.288919E+11 | 0.625120E+11 | 0.301249E+11 | 0.323870E+11 | 0.00 | 0.00 |
Minimum of Months | 0.443259E+10 | 0.336301E+09 | 0.268736E+10 | 24527788.62 | 0.236152E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117633E+11 | 0.530124E+10 | 0.857721E+10 | 0.611776E+10 | 0.305070E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.295351E+10 | 0.414659E+10 | 0.270717E+10 | 0.146386E+10 | 0.124332E+10 | 0.00 | 0.00 |
February | 0.314854E+10 | 0.330803E+10 | 0.276848E+10 | 0.140119E+10 | 0.136729E+10 | 0.00 | 0.00 |
March | 0.360116E+10 | 0.325056E+10 | 0.302118E+10 | 0.133746E+10 | 0.168372E+10 | 0.00 | 0.00 |
April | 0.504053E+10 | 0.206977E+10 | 0.363139E+10 | 0.167061E+10 | 0.196078E+10 | 0.00 | 0.00 |
May | 0.540204E+10 | 0.649251E+09 | 0.312033E+10 | 0.101639E+10 | 0.210395E+10 | 0.00 | 0.00 |
June | 0.591302E+10 | 0.578171E+09 | 0.335452E+10 | 0.117619E+10 | 0.217834E+10 | 0.00 | 0.00 |
July | 0.551244E+10 | 0.473614E+09 | 0.316413E+10 | 0.877613E+09 | 0.228651E+10 | 0.00 | 0.00 |
August | 0.557272E+10 | 0.661391E+09 | 0.319942E+10 | 0.979386E+09 | 0.222004E+10 | 0.00 | 0.00 |
September | 0.478916E+10 | 0.718659E+09 | 0.285119E+10 | 0.978156E+09 | 0.187303E+10 | 0.00 | 0.00 |
October | 0.479600E+10 | 0.134575E+10 | 0.301626E+10 | 0.130331E+10 | 0.171295E+10 | 0.00 | 0.00 |
November | 0.311651E+10 | 0.285011E+10 | 0.250178E+10 | 0.125725E+10 | 0.124453E+10 | 0.00 | 0.00 |
December | 0.278040E+10 | 0.395660E+10 | 0.248677E+10 | 0.132241E+10 | 0.116436E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.526260E+11 | 0.240085E+11 | 0.358226E+11 | 0.147838E+11 | 0.210388E+11 | 0.00 | 0.00 |
Minimum of Months | 0.278040E+10 | 0.473614E+09 | 0.248677E+10 | 0.877613E+09 | 0.116436E+10 | 0.00 | 0.00 |
Maximum of Months | 0.591302E+10 | 0.414659E+10 | 0.363139E+10 | 0.167061E+10 | 0.228651E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.952018E+09 | 0.533600E+10 | 0.148346E+10 | 0.00 | 0.148346E+10 | 0.00 | 0.00 |
February | 0.117192E+10 | 0.404148E+10 | 0.158075E+10 | 0.00 | 0.158075E+10 | 0.00 | 0.00 |
March | 0.188845E+10 | 0.382261E+10 | 0.203029E+10 | 0.00 | 0.203029E+10 | 0.00 | 0.00 |
April | 0.290329E+10 | 0.229841E+10 | 0.231877E+10 | 9395236.22 | 0.230938E+10 | 0.00 | 0.00 |
May | 0.499729E+10 | 0.631783E+09 | 0.271369E+10 | 98824883.04 | 0.261487E+10 | 0.00 | 0.00 |
June | 0.564935E+10 | 0.520143E+09 | 0.298633E+10 | 0.206161E+09 | 0.278017E+10 | 0.00 | 0.00 |
July | 0.571842E+10 | 0.349851E+09 | 0.299486E+10 | 0.113670E+09 | 0.288119E+10 | 0.00 | 0.00 |
August | 0.528528E+10 | 0.501237E+09 | 0.268219E+10 | 20937872.69 | 0.266126E+10 | 0.00 | 0.00 |
September | 0.409079E+10 | 0.708575E+09 | 0.224220E+10 | 167848.03 | 0.224204E+10 | 0.00 | 0.00 |
October | 0.339382E+10 | 0.144789E+10 | 0.201338E+10 | 0.00 | 0.201338E+10 | 0.00 | 0.00 |
November | 0.145832E+10 | 0.327365E+10 | 0.147917E+10 | 0.00 | 0.147917E+10 | 0.00 | 0.00 |
December | 0.103802E+10 | 0.455350E+10 | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.385470E+11 | 0.274851E+11 | 0.259041E+11 | 0.449157E+09 | 0.254550E+11 | 0.00 | 0.00 |
Minimum of Months | 0.952018E+09 | 0.349851E+09 | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.00 | 0.00 |
Maximum of Months | 0.571842E+10 | 0.533600E+10 | 0.299486E+10 | 0.206161E+09 | 0.288119E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.261916E+10 | 0.337344E+10 | 0.254515E+10 | 0.129597E+10 | 0.124918E+10 | 0.00 | 0.00 |
February | 0.280971E+10 | 0.256585E+10 | 0.255980E+10 | 0.123575E+10 | 0.132405E+10 | 0.00 | 0.00 |
March | 0.409369E+10 | 0.245247E+10 | 0.333418E+10 | 0.160812E+10 | 0.172606E+10 | 0.00 | 0.00 |
April | 0.495199E+10 | 0.153147E+10 | 0.354071E+10 | 0.160144E+10 | 0.193927E+10 | 0.00 | 0.00 |
May | 0.646205E+10 | 0.457170E+09 | 0.377096E+10 | 0.163512E+10 | 0.213584E+10 | 0.00 | 0.00 |
June | 0.654152E+10 | 0.376251E+09 | 0.370095E+10 | 0.146762E+10 | 0.223334E+10 | 0.00 | 0.00 |
July | 0.652669E+10 | 0.257169E+09 | 0.368724E+10 | 0.134928E+10 | 0.233796E+10 | 0.00 | 0.00 |
August | 0.602448E+10 | 0.361757E+09 | 0.339777E+10 | 0.116819E+10 | 0.222958E+10 | 0.00 | 0.00 |
September | 0.490575E+10 | 0.503323E+09 | 0.291281E+10 | 0.100149E+10 | 0.191132E+10 | 0.00 | 0.00 |
October | 0.471646E+10 | 0.977236E+09 | 0.297429E+10 | 0.125514E+10 | 0.171915E+10 | 0.00 | 0.00 |
November | 0.313323E+10 | 0.210679E+10 | 0.254825E+10 | 0.129991E+10 | 0.124834E+10 | 0.00 | 0.00 |
December | 0.219865E+10 | 0.293965E+10 | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.549834E+11 | 0.179026E+11 | 0.370453E+11 | 0.158571E+11 | 0.211882E+11 | 0.00 | 0.00 |
Minimum of Months | 0.219865E+10 | 0.257169E+09 | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.00 | 0.00 |
Maximum of Months | 0.654152E+10 | 0.337344E+10 | 0.377096E+10 | 0.163512E+10 | 0.233796E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113815E+11 | 0.518301E+10 | 0.857718E+10 | 0.611774E+10 | 0.245944E+10 | 0.00 | 0.00 |
February | 0.919207E+10 | 0.402664E+10 | 0.702474E+10 | 0.454720E+10 | 0.247754E+10 | 0.00 | 0.00 |
March | 0.607416E+10 | 0.389088E+10 | 0.496336E+10 | 0.223916E+10 | 0.272420E+10 | 0.00 | 0.00 |
April | 0.447375E+10 | 0.239592E+10 | 0.355961E+10 | 0.832905E+09 | 0.272670E+10 | 0.00 | 0.00 |
May | 0.507474E+10 | 0.662789E+09 | 0.281058E+10 | 0.118375E+09 | 0.269220E+10 | 0.00 | 0.00 |
June | 0.524031E+10 | 0.544002E+09 | 0.268735E+10 | 24527701.52 | 0.266282E+10 | 0.00 | 0.00 |
July | 0.558296E+10 | 0.351133E+09 | 0.290685E+10 | 52730932.22 | 0.285412E+10 | 0.00 | 0.00 |
August | 0.621246E+10 | 0.545184E+09 | 0.341943E+10 | 0.409408E+09 | 0.301002E+10 | 0.00 | 0.00 |
September | 0.656110E+10 | 0.788334E+09 | 0.397076E+10 | 0.104573E+10 | 0.292502E+10 | 0.00 | 0.00 |
October | 0.101219E+11 | 0.162261E+10 | 0.636703E+10 | 0.331634E+10 | 0.305069E+10 | 0.00 | 0.00 |
November | 0.112175E+11 | 0.337119E+10 | 0.784368E+10 | 0.540104E+10 | 0.244264E+10 | 0.00 | 0.00 |
December | 0.116953E+11 | 0.459548E+10 | 0.838118E+10 | 0.601967E+10 | 0.236151E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.928278E+11 | 0.279772E+11 | 0.625117E+11 | 0.301248E+11 | 0.323869E+11 | 0.00 | 0.00 |
Minimum of Months | 0.447375E+10 | 0.351133E+09 | 0.268735E+10 | 24527701.52 | 0.236151E+10 | 0.00 | 0.00 |
Maximum of Months | 0.116953E+11 | 0.518301E+10 | 0.857718E+10 | 0.611774E+10 | 0.305069E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.305988E+10 | 0.364505E+10 | 0.270716E+10 | 0.146385E+10 | 0.124331E+10 | 0.00 | 0.00 |
February | 0.326786E+10 | 0.281958E+10 | 0.276847E+10 | 0.140118E+10 | 0.136729E+10 | 0.00 | 0.00 |
March | 0.373824E+10 | 0.270553E+10 | 0.302117E+10 | 0.133746E+10 | 0.168371E+10 | 0.00 | 0.00 |
April | 0.517597E+10 | 0.172943E+10 | 0.363138E+10 | 0.167060E+10 | 0.196077E+10 | 0.00 | 0.00 |
May | 0.546124E+10 | 0.547842E+09 | 0.312032E+10 | 0.101638E+10 | 0.210394E+10 | 0.00 | 0.00 |
June | 0.599683E+10 | 0.471510E+09 | 0.335451E+10 | 0.117618E+10 | 0.217833E+10 | 0.00 | 0.00 |
July | 0.565098E+10 | 0.338960E+09 | 0.316411E+10 | 0.877610E+09 | 0.228650E+10 | 0.00 | 0.00 |
August | 0.573908E+10 | 0.460406E+09 | 0.319941E+10 | 0.979382E+09 | 0.222003E+10 | 0.00 | 0.00 |
September | 0.484431E+10 | 0.594174E+09 | 0.285118E+10 | 0.978152E+09 | 0.187302E+10 | 0.00 | 0.00 |
October | 0.488922E+10 | 0.112929E+10 | 0.301625E+10 | 0.130331E+10 | 0.171294E+10 | 0.00 | 0.00 |
November | 0.325515E+10 | 0.235543E+10 | 0.250177E+10 | 0.125724E+10 | 0.124453E+10 | 0.00 | 0.00 |
December | 0.295053E+10 | 0.317279E+10 | 0.248676E+10 | 0.132241E+10 | 0.116435E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.540293E+11 | 0.199700E+11 | 0.358225E+11 | 0.147838E+11 | 0.210387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.295053E+10 | 0.338960E+09 | 0.248676E+10 | 0.877610E+09 | 0.116435E+10 | 0.00 | 0.00 |
Maximum of Months | 0.599683E+10 | 0.364505E+10 | 0.363138E+10 | 0.167060E+10 | 0.228650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103946E+10 | 0.490924E+10 | 0.148346E+10 | 0.00 | 0.148346E+10 | 0.00 | 0.00 |
February | 0.123303E+10 | 0.372245E+10 | 0.158075E+10 | 0.00 | 0.158075E+10 | 0.00 | 0.00 |
March | 0.192496E+10 | 0.360068E+10 | 0.203029E+10 | 0.00 | 0.203029E+10 | 0.00 | 0.00 |
April | 0.288359E+10 | 0.223663E+10 | 0.231877E+10 | 9395236.22 | 0.230938E+10 | 0.00 | 0.00 |
May | 0.490718E+10 | 0.666458E+09 | 0.271369E+10 | 98824883.04 | 0.261487E+10 | 0.00 | 0.00 |
June | 0.554875E+10 | 0.557994E+09 | 0.298633E+10 | 0.206161E+09 | 0.278017E+10 | 0.00 | 0.00 |
July | 0.559584E+10 | 0.389482E+09 | 0.299486E+10 | 0.113670E+09 | 0.288119E+10 | 0.00 | 0.00 |
August | 0.519247E+10 | 0.529746E+09 | 0.268219E+10 | 20937872.69 | 0.266126E+10 | 0.00 | 0.00 |
September | 0.400461E+10 | 0.730746E+09 | 0.224220E+10 | 167848.03 | 0.224204E+10 | 0.00 | 0.00 |
October | 0.335520E+10 | 0.141445E+10 | 0.201338E+10 | 0.00 | 0.201338E+10 | 0.00 | 0.00 |
November | 0.151330E+10 | 0.303245E+10 | 0.147917E+10 | 0.00 | 0.147917E+10 | 0.00 | 0.00 |
December | 0.110701E+10 | 0.418796E+10 | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.383054E+11 | 0.259783E+11 | 0.259041E+11 | 0.449157E+09 | 0.254550E+11 | 0.00 | 0.00 |
Minimum of Months | 0.103946E+10 | 0.389482E+09 | 0.137904E+10 | 0.00 | 0.137904E+10 | 0.00 | 0.00 |
Maximum of Months | 0.559584E+10 | 0.490924E+10 | 0.299486E+10 | 0.206161E+09 | 0.288119E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.273141E+10 | 0.309362E+10 | 0.254515E+10 | 0.129597E+10 | 0.124918E+10 | 0.00 | 0.00 |
February | 0.289067E+10 | 0.236893E+10 | 0.255980E+10 | 0.123575E+10 | 0.132405E+10 | 0.00 | 0.00 |
March | 0.413700E+10 | 0.232266E+10 | 0.333418E+10 | 0.160812E+10 | 0.172606E+10 | 0.00 | 0.00 |
April | 0.495339E+10 | 0.149680E+10 | 0.354071E+10 | 0.160144E+10 | 0.193927E+10 | 0.00 | 0.00 |
May | 0.642189E+10 | 0.475343E+09 | 0.377096E+10 | 0.163512E+10 | 0.213584E+10 | 0.00 | 0.00 |
June | 0.649843E+10 | 0.398299E+09 | 0.370095E+10 | 0.146762E+10 | 0.223334E+10 | 0.00 | 0.00 |
July | 0.647393E+10 | 0.280766E+09 | 0.368724E+10 | 0.134928E+10 | 0.233796E+10 | 0.00 | 0.00 |
August | 0.598638E+10 | 0.378080E+09 | 0.339777E+10 | 0.116819E+10 | 0.222958E+10 | 0.00 | 0.00 |
September | 0.487359E+10 | 0.514062E+09 | 0.291281E+10 | 0.100149E+10 | 0.191132E+10 | 0.00 | 0.00 |
October | 0.470849E+10 | 0.954998E+09 | 0.297429E+10 | 0.125514E+10 | 0.171915E+10 | 0.00 | 0.00 |
November | 0.318876E+10 | 0.197521E+10 | 0.254825E+10 | 0.129991E+10 | 0.124834E+10 | 0.00 | 0.00 |
December | 0.227927E+10 | 0.270631E+10 | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.551432E+11 | 0.169651E+11 | 0.370453E+11 | 0.158571E+11 | 0.211882E+11 | 0.00 | 0.00 |
Minimum of Months | 0.227927E+10 | 0.280766E+09 | 0.207322E+10 | 0.939079E+09 | 0.113415E+10 | 0.00 | 0.00 |
Maximum of Months | 0.649843E+10 | 0.309362E+10 | 0.377096E+10 | 0.163512E+10 | 0.233796E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114833E+11 | 0.482728E+10 | 0.857718E+10 | 0.611774E+10 | 0.245944E+10 | 0.00 | 0.00 |
February | 0.927370E+10 | 0.375558E+10 | 0.702474E+10 | 0.454720E+10 | 0.247754E+10 | 0.00 | 0.00 |
March | 0.610565E+10 | 0.368655E+10 | 0.496336E+10 | 0.223916E+10 | 0.272420E+10 | 0.00 | 0.00 |
April | 0.445571E+10 | 0.233795E+10 | 0.355961E+10 | 0.832905E+09 | 0.272670E+10 | 0.00 | 0.00 |
May | 0.499132E+10 | 0.698981E+09 | 0.281058E+10 | 0.118375E+09 | 0.269220E+10 | 0.00 | 0.00 |
June | 0.514827E+10 | 0.585654E+09 | 0.268735E+10 | 24527701.52 | 0.266282E+10 | 0.00 | 0.00 |
July | 0.546448E+10 | 0.390214E+09 | 0.290685E+10 | 52730932.22 | 0.285412E+10 | 0.00 | 0.00 |
August | 0.612780E+10 | 0.575164E+09 | 0.341943E+10 | 0.409408E+09 | 0.301002E+10 | 0.00 | 0.00 |
September | 0.648904E+10 | 0.809995E+09 | 0.397076E+10 | 0.104573E+10 | 0.292502E+10 | 0.00 | 0.00 |
October | 0.100884E+11 | 0.159014E+10 | 0.636703E+10 | 0.331634E+10 | 0.305069E+10 | 0.00 | 0.00 |
November | 0.112695E+11 | 0.318862E+10 | 0.784368E+10 | 0.540104E+10 | 0.244264E+10 | 0.00 | 0.00 |
December | 0.117808E+11 | 0.428395E+10 | 0.838118E+10 | 0.601967E+10 | 0.236151E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.926780E+11 | 0.267301E+11 | 0.625117E+11 | 0.301248E+11 | 0.323869E+11 | 0.00 | 0.00 |
Minimum of Months | 0.445571E+10 | 0.390214E+09 | 0.268735E+10 | 24527701.52 | 0.236151E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117808E+11 | 0.482728E+10 | 0.857718E+10 | 0.611774E+10 | 0.305069E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.310040E+10 | 0.341219E+10 | 0.270716E+10 | 0.146385E+10 | 0.124331E+10 | 0.00 | 0.00 |
February | 0.329337E+10 | 0.264388E+10 | 0.276847E+10 | 0.140118E+10 | 0.136729E+10 | 0.00 | 0.00 |
March | 0.374494E+10 | 0.257498E+10 | 0.302117E+10 | 0.133746E+10 | 0.168371E+10 | 0.00 | 0.00 |
April | 0.514869E+10 | 0.168565E+10 | 0.363138E+10 | 0.167060E+10 | 0.196077E+10 | 0.00 | 0.00 |
May | 0.540746E+10 | 0.563391E+09 | 0.312032E+10 | 0.101638E+10 | 0.210394E+10 | 0.00 | 0.00 |
June | 0.593840E+10 | 0.489198E+09 | 0.335451E+10 | 0.117618E+10 | 0.217833E+10 | 0.00 | 0.00 |
July | 0.558499E+10 | 0.358343E+09 | 0.316411E+10 | 0.877610E+09 | 0.228650E+10 | 0.00 | 0.00 |
August | 0.568360E+10 | 0.475769E+09 | 0.319941E+10 | 0.979382E+09 | 0.222003E+10 | 0.00 | 0.00 |
September | 0.479740E+10 | 0.602661E+09 | 0.285118E+10 | 0.978152E+09 | 0.187302E+10 | 0.00 | 0.00 |
October | 0.486027E+10 | 0.110713E+10 | 0.301625E+10 | 0.130331E+10 | 0.171294E+10 | 0.00 | 0.00 |
November | 0.327284E+10 | 0.222435E+10 | 0.250177E+10 | 0.125724E+10 | 0.124453E+10 | 0.00 | 0.00 |
December | 0.298120E+10 | 0.296757E+10 | 0.248676E+10 | 0.132241E+10 | 0.116435E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.538136E+11 | 0.191051E+11 | 0.358225E+11 | 0.147838E+11 | 0.210387E+11 | 0.00 | 0.00 |
Minimum of Months | 0.298120E+10 | 0.358343E+09 | 0.248676E+10 | 0.877610E+09 | 0.116435E+10 | 0.00 | 0.00 |
Maximum of Months | 0.593840E+10 | 0.341219E+10 | 0.363138E+10 | 0.167060E+10 | 0.228650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.01 | 8.64 | 3.24 | 3.12 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.57 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.53 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.81 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.36 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.89 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.01 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.46 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.87 | 10.53 | 3.17 | 6.00 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.01 | 8.64 | 2.44 | 3.12 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.65 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.77 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.86 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.04 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.75 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.93 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.95 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.72 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.63 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.03 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.82 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.65 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.63 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.2 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -1.8 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.94 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.57 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 17.99 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.55 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.11 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.8 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.2 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.10 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.48 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.76 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.54 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.83 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.16 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.78 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.48 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.10 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.54 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.08 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.78 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.178248E+11 | -.308216E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130542E+10 | 68.41 | 0.00 | 0.00 |
February | 0.160277E+11 | -.277826E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.117369E+10 | 68.17 | 0.00 | 0.00 |
March | 0.184296E+11 | -.314318E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128093E+10 | 67.45 | 0.00 | 0.00 |
April | 0.139998E+11 | -.267883E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.126351E+10 | 68.38 | 0.00 | 0.00 |
May | 0.133337E+11 | -.266069E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131277E+10 | 68.60 | 0.00 | 0.00 |
June | 0.118222E+11 | -.247513E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.126472E+10 | 68.35 | 0.00 | 0.00 |
July | 0.933809E+10 | -.228161E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.134091E+10 | 69.65 | 0.00 | 0.00 |
August | 0.118448E+11 | -.252274E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130698E+10 | 68.40 | 0.00 | 0.00 |
September | 0.111130E+11 | -.240641E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.127586E+10 | 68.88 | 0.00 | 0.00 |
October | 0.133586E+11 | -.266128E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.132053E+10 | 69.00 | 0.00 | 0.00 |
November | 0.153066E+11 | -.279920E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.127103E+10 | 68.77 | 0.00 | 0.00 |
December | 0.162774E+11 | -.293743E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130504E+10 | 68.48 | 0.00 | 0.00 |
Annual Sum or Average | 0.168676E+12 | -.324269E+12 | 8760.00 | -.154214E+11 | 68.55 | |||||
Minimum of Months | 0.933809E+10 | -.314318E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.134091E+10 | 67.45 | 0.00 | 0.00 |
Maximum of Months | 0.184296E+11 | -.228161E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.117369E+10 | 69.65 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.50 | 0.48 | 01-JAN-07:49 | 7770.35 | 36.97 | 300.33 | 296.17 | 1442.47 | 25.96 | 215.67 | 278.83 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3377.81 | 28.24 | 173.67 | 279.83 | 1251.63 | 23.20 | 185.17 | 266.50 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 1588.31 | 20.00 | 54.67 | 319.67 | 929.06 | 21.32 | 172.33 | 281.67 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1263.17 | 19.19 | 28.67 | 323.83 | 729.49 | 20.50 | 171.00 | 284.50 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-07:19 | 1128.80 | 19.44 | 8.00 | 349.67 | 636.24 | 20.79 | 163.83 | 300.17 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:00 | 1072.53 | 19.08 | 1.83 | 350.50 | 608.30 | 20.45 | 161.50 | 304.00 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1182.57 | 19.45 | 12.50 | 360.00 | 650.65 | 20.79 | 192.83 | 313.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 1372.67 | 19.74 | 40.00 | 346.67 | 740.16 | 21.06 | 239.17 | 307.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1614.76 | 20.03 | 85.83 | 317.67 | 855.94 | 21.26 | 224.50 | 282.00 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:10 | 2783.08 | 23.92 | 164.00 | 314.50 | 1161.12 | 22.35 | 236.33 | 283.33 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-07:00 | 7841.85 | 36.40 | 297.17 | 288.67 | 1374.30 | 24.15 | 201.00 | 271.17 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7920.99 | 37.74 | 279.33 | 284.33 | 1830.22 | 27.85 | 205.50 | 267.17 |
Annual Sum or Average | 4027.67 | 0.51 | 3035.85 | 24.44 | 1446.00 | 3831.50 | 982.92 | 22.29 | 2368.83 | 3440.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1072.53 | 19.08 | 1.83 | 279.83 | 608.30 | 20.45 | 161.50 | 266.50 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7920.99 | 37.74 | 300.33 | 360.00 | 1830.22 | 27.85 | 239.17 | 313.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1997.48 | 23.64 | 104.17 | 271.17 | 1078.48 | 23.71 | 124.83 | 224.00 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2211.39 | 23.72 | 91.00 | 261.50 | 1174.70 | 23.87 | 113.33 | 228.17 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 2303.85 | 23.68 | 86.00 | 315.67 | 1219.50 | 23.82 | 121.50 | 276.67 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:10 | 2357.53 | 22.77 | 96.00 | 326.33 | 1253.38 | 23.13 | 120.17 | 293.50 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2667.04 | 24.06 | 112.00 | 360.50 | 1071.81 | 23.03 | 125.67 | 315.17 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2398.91 | 23.68 | 122.83 | 359.17 | 1014.36 | 22.93 | 143.50 | 321.50 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2309.74 | 23.14 | 112.83 | 365.17 | 996.01 | 22.40 | 156.17 | 318.83 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2128.04 | 23.05 | 106.17 | 347.17 | 1109.76 | 23.46 | 170.17 | 308.50 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2032.74 | 23.18 | 100.33 | 314.50 | 1040.49 | 23.47 | 169.00 | 278.83 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-06:49 | 2115.38 | 23.40 | 92.67 | 303.00 | 1083.58 | 23.54 | 158.83 | 269.83 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-07:49 | 1757.24 | 22.78 | 85.67 | 267.33 | 902.07 | 22.82 | 123.50 | 230.83 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-07:40 | 1890.20 | 23.38 | 91.50 | 257.50 | 1008.87 | 23.40 | 110.33 | 208.50 |
Annual Sum or Average | 4027.67 | 0.51 | 2194.13 | 23.37 | 1201.17 | 3749.00 | 1077.91 | 23.27 | 1637.00 | 3274.33 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1757.24 | 22.77 | 85.67 | 257.50 | 902.07 | 22.40 | 110.33 | 208.50 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 2667.04 | 24.06 | 122.83 | 365.17 | 1253.38 | 23.87 | 170.17 | 321.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.55 | 0.48 | 01-JAN-08:50 | 546.89 | 16.23 | 0.00 | 251.83 | 354.45 | 17.91 | 0.00 | 165.67 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:50 | 631.62 | 17.40 | 0.00 | 248.50 | 410.83 | 19.00 | 2.67 | 185.00 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 738.16 | 18.40 | 0.00 | 306.50 | 464.66 | 19.79 | 10.17 | 237.17 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:49 | 878.52 | 18.81 | 0.00 | 326.67 | 535.85 | 20.10 | 77.00 | 285.17 |
May | 353.67 | 0.49 | 0.48 | 01-MAY-06:00 | 1077.65 | 21.03 | 55.17 | 370.33 | 621.31 | 22.20 | 186.17 | 330.67 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1246.12 | 22.14 | 107.00 | 374.00 | 658.32 | 21.33 | 213.67 | 338.33 |
July | 390.00 | 0.49 | 0.48 | 01-JUL-06:40 | 1218.83 | 20.84 | 79.33 | 376.67 | 662.93 | 22.12 | 238.00 | 340.50 |
August | 380.83 | 0.50 | 0.48 | 01-AUG-07:10 | 1069.93 | 19.57 | 10.50 | 353.33 | 602.11 | 20.87 | 169.83 | 318.17 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 896.34 | 18.79 | 0.17 | 316.00 | 516.43 | 20.08 | 73.33 | 265.50 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:30 | 773.92 | 18.56 | 0.00 | 297.00 | 474.37 | 20.01 | 12.17 | 244.67 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-09:50 | 562.03 | 16.84 | 0.00 | 243.33 | 366.18 | 18.49 | 0.00 | 170.33 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-08:39 | 547.38 | 16.49 | 0.00 | 242.83 | 356.45 | 18.22 | 0.00 | 149.50 |
Annual Sum or Average | 4027.67 | 0.51 | 874.77 | 18.93 | 252.17 | 3707.00 | 513.40 | 20.14 | 983.00 | 3030.67 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 546.89 | 16.23 | 0.00 | 242.83 | 354.45 | 17.91 | 0.00 | 149.50 | |
Maximum of Months | 394.00 | 0.55 | 0.48 | 1246.12 | 22.14 | 107.00 | 376.67 | 662.93 | 22.20 | 238.00 | 340.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-08:50 | 2286.03 | 24.56 | 112.50 | 275.83 | 1268.23 | 24.46 | 127.67 | 230.50 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2042.97 | 23.82 | 89.33 | 266.17 | 1078.44 | 23.81 | 127.67 | 234.33 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2191.03 | 23.20 | 81.00 | 311.83 | 1151.71 | 23.51 | 113.50 | 269.83 |
April | 347.33 | 0.51 | 0.48 | 01-APR-08:20 | 2475.52 | 21.68 | 82.83 | 327.00 | 1301.08 | 22.09 | 107.33 | 293.83 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:40 | 2051.40 | 18.21 | 1.00 | 356.50 | 909.30 | 20.32 | 100.83 | 318.00 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-07:19 | 2171.45 | 18.07 | 0.67 | 359.00 | 927.78 | 20.12 | 101.33 | 318.67 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-07:10 | 2009.37 | 18.56 | 6.50 | 366.00 | 895.11 | 20.37 | 120.50 | 322.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:40 | 2074.95 | 20.50 | 59.17 | 349.50 | 952.14 | 20.60 | 135.67 | 309.83 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1925.32 | 21.92 | 82.33 | 314.83 | 988.07 | 22.31 | 151.50 | 279.17 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:49 | 2462.04 | 24.56 | 110.67 | 309.50 | 1019.42 | 23.43 | 165.67 | 273.17 |
November | 308.00 | 0.52 | 0.48 | 01-NOV-09:50 | 1983.89 | 23.72 | 96.33 | 267.17 | 1067.58 | 23.77 | 124.33 | 232.00 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-08:30 | 2129.80 | 25.18 | 106.00 | 271.00 | 1151.99 | 24.94 | 124.00 | 219.83 |
Annual Sum or Average | 4027.67 | 0.51 | 2148.70 | 21.76 | 828.33 | 3774.33 | 1050.05 | 22.30 | 1500.00 | 3301.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1925.32 | 18.07 | 0.67 | 266.17 | 895.11 | 20.12 | 100.83 | 219.83 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2475.52 | 25.18 | 112.50 | 366.00 | 1301.08 | 24.94 | 165.67 | 322.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.50 | 0.48 | 01-JAN-07:49 | 7834.86 | 36.47 | 297.33 | 296.17 | 1544.53 | 21.71 | 92.17 | 281.67 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3434.34 | 24.64 | 165.33 | 280.00 | 1345.10 | 18.88 | 36.50 | 268.17 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 1627.82 | 13.73 | 0.00 | 320.33 | 997.59 | 17.33 | 0.00 | 286.50 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1288.92 | 13.31 | 0.00 | 324.00 | 779.67 | 16.75 | 0.00 | 290.00 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 1146.96 | 13.53 | 0.00 | 350.50 | 677.52 | 17.01 | 0.00 | 305.83 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:49 | 1089.53 | 13.18 | 0.00 | 351.00 | 647.64 | 16.63 | 0.00 | 308.33 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 1199.42 | 13.41 | 0.00 | 360.33 | 692.10 | 16.84 | 0.00 | 319.00 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 1391.52 | 13.68 | 0.00 | 346.83 | 787.64 | 17.07 | 0.00 | 313.00 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:10 | 1635.18 | 13.84 | 3.67 | 318.17 | 911.49 | 17.08 | 0.00 | 286.83 |
October | 330.00 | 0.49 | 0.48 | 01-OCT-07:10 | 2823.25 | 18.71 | 80.67 | 314.83 | 1248.57 | 18.22 | 10.50 | 288.33 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-07:00 | 7899.02 | 35.88 | 296.00 | 289.17 | 1505.35 | 21.52 | 90.83 | 276.50 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7984.10 | 37.34 | 279.33 | 284.33 | 1937.80 | 23.94 | 110.83 | 268.67 |
Annual Sum or Average | 4027.67 | 0.50 | 3070.55 | 19.89 | 1122.33 | 3835.67 | 1052.36 | 18.40 | 340.83 | 3492.83 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 1089.53 | 13.18 | 0.00 | 280.00 | 647.64 | 16.63 | 0.00 | 268.17 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7984.10 | 37.34 | 297.33 | 360.33 | 1937.80 | 23.94 | 110.83 | 319.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-07:49 | 2031.25 | 21.13 | 100.17 | 273.00 | 1123.20 | 21.80 | 72.33 | 230.17 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2253.58 | 20.95 | 89.67 | 262.67 | 1224.15 | 21.77 | 64.33 | 232.17 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 2329.30 | 19.41 | 74.33 | 316.33 | 1281.11 | 21.35 | 56.50 | 282.50 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:10 | 2387.95 | 19.70 | 95.67 | 327.17 | 1310.10 | 20.70 | 68.00 | 297.17 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2686.51 | 20.36 | 106.00 | 361.33 | 1131.38 | 20.35 | 55.00 | 321.17 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2427.19 | 19.81 | 114.00 | 359.50 | 1069.69 | 20.31 | 62.67 | 326.83 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2340.26 | 20.05 | 112.33 | 366.67 | 1050.83 | 19.71 | 53.67 | 323.83 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2151.22 | 19.97 | 105.17 | 347.83 | 1162.20 | 21.07 | 75.50 | 313.00 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2069.38 | 20.16 | 96.00 | 314.67 | 1090.79 | 21.10 | 67.50 | 282.17 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-06:49 | 2162.62 | 20.40 | 87.67 | 303.33 | 1136.17 | 21.20 | 57.00 | 273.67 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-07:49 | 1792.19 | 19.92 | 84.00 | 267.83 | 947.39 | 20.62 | 55.50 | 235.17 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-07:40 | 1920.08 | 20.87 | 89.17 | 258.67 | 1050.52 | 21.54 | 61.67 | 214.83 |
Annual Sum or Average | 4027.67 | 0.51 | 2225.68 | 20.20 | 1154.17 | 3759.00 | 1130.25 | 20.91 | 749.67 | 3332.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1792.19 | 19.41 | 74.33 | 258.67 | 947.39 | 19.71 | 53.67 | 214.83 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2686.51 | 21.13 | 114.00 | 366.67 | 1310.10 | 21.80 | 75.50 | 326.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-08:50 | 556.86 | 10.68 | 0.00 | 253.00 | 377.85 | 14.34 | 0.00 | 181.00 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 644.13 | 11.90 | 0.00 | 249.67 | 438.23 | 15.56 | 0.00 | 194.33 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 753.78 | 13.09 | 0.00 | 307.83 | 495.88 | 16.63 | 0.00 | 249.67 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:49 | 897.00 | 13.36 | 0.00 | 327.33 | 571.74 | 16.82 | 0.00 | 292.00 |
May | 353.67 | 0.49 | 0.48 | 01-MAY-06:00 | 1097.54 | 15.61 | 27.17 | 370.83 | 661.97 | 18.95 | 27.50 | 336.17 |
June | 394.00 | 0.49 | 0.48 | 01-JUN-06:19 | 1267.18 | 17.13 | 58.00 | 374.67 | 710.85 | 20.27 | 59.33 | 349.17 |
July | 390.00 | 0.49 | 0.48 | 01-JUL-06:40 | 1238.40 | 15.24 | 23.50 | 376.67 | 705.25 | 18.57 | 24.50 | 343.50 |
August | 380.83 | 0.50 | 0.48 | 01-AUG-06:00 | 1087.55 | 13.79 | 0.00 | 353.67 | 640.66 | 17.22 | 0.00 | 322.00 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 911.87 | 13.18 | 0.00 | 316.00 | 549.71 | 16.55 | 0.00 | 271.67 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:30 | 787.96 | 13.11 | 0.00 | 297.33 | 505.40 | 16.64 | 0.00 | 252.67 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-09:39 | 572.56 | 11.20 | 0.00 | 245.00 | 390.44 | 14.92 | 0.00 | 182.00 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-08:30 | 556.86 | 10.84 | 0.00 | 244.17 | 379.85 | 14.58 | 0.00 | 162.83 |
Annual Sum or Average | 4027.67 | 0.51 | 890.50 | 13.44 | 108.67 | 3716.17 | 547.90 | 16.92 | 111.33 | 3137.00 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 556.86 | 10.68 | 0.00 | 244.17 | 377.85 | 14.34 | 0.00 | 162.83 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 1267.18 | 17.13 | 58.00 | 376.67 | 710.85 | 20.27 | 59.33 | 349.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-08:50 | 2320.30 | 22.13 | 109.33 | 277.17 | 1314.89 | 22.66 | 81.83 | 237.67 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2062.75 | 19.81 | 79.17 | 267.33 | 1132.06 | 21.60 | 60.17 | 237.67 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2242.21 | 20.13 | 81.00 | 313.33 | 1206.06 | 21.10 | 56.67 | 277.17 |
April | 347.33 | 0.51 | 0.48 | 01-APR-08:09 | 2504.94 | 18.35 | 82.00 | 327.67 | 1358.94 | 19.38 | 53.00 | 297.83 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:40 | 2076.07 | 13.66 | 0.00 | 357.33 | 960.29 | 17.09 | 0.00 | 321.33 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-07:10 | 2199.68 | 13.55 | 0.00 | 359.17 | 979.28 | 16.91 | 0.00 | 324.50 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-07:10 | 2033.02 | 14.12 | 3.67 | 366.83 | 944.46 | 17.21 | 0.00 | 328.17 |
August | 380.83 | 0.50 | 0.48 | 01-AUG-07:40 | 2099.03 | 16.80 | 59.00 | 350.83 | 1003.01 | 17.49 | 5.50 | 316.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1960.43 | 18.69 | 80.50 | 315.67 | 1037.16 | 19.76 | 51.67 | 283.50 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:40 | 2509.10 | 21.87 | 108.83 | 310.17 | 1072.07 | 21.04 | 53.50 | 277.17 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-09:39 | 2019.46 | 21.02 | 95.17 | 268.33 | 1113.25 | 21.73 | 66.67 | 236.33 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-08:30 | 2165.81 | 22.81 | 103.00 | 271.50 | 1199.64 | 23.15 | 74.00 | 226.50 |
Annual Sum or Average | 4027.67 | 0.51 | 2180.65 | 18.27 | 801.67 | 3785.33 | 1100.95 | 19.70 | 503.00 | 3364.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1960.43 | 13.55 | 0.00 | 267.33 | 944.46 | 16.91 | 0.00 | 226.50 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2509.10 | 22.81 | 109.33 | 366.83 | 1358.94 | 23.15 | 81.83 | 328.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.50 | 0.48 | 01-JAN-07:49 | 7836.49 | 36.46 | 297.33 | 296.17 | 1546.19 | 21.70 | 92.17 | 281.67 |
February | 295.50 | 0.50 | 0.48 | 01-FEB-11:39 | 3436.56 | 24.62 | 165.33 | 280.00 | 1346.70 | 18.87 | 36.33 | 268.17 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 1629.92 | 13.70 | 0.00 | 320.50 | 998.93 | 17.31 | 0.00 | 286.50 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:49 | 1290.60 | 13.28 | 0.00 | 324.17 | 780.75 | 16.74 | 0.00 | 290.17 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 1148.50 | 13.50 | 0.00 | 350.83 | 678.51 | 16.99 | 0.00 | 306.00 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:49 | 1090.97 | 13.15 | 0.00 | 351.00 | 648.57 | 16.62 | 0.00 | 308.50 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 1201.16 | 13.38 | 0.00 | 360.50 | 693.17 | 16.82 | 0.00 | 319.00 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:10 | 1393.67 | 13.65 | 0.00 | 347.00 | 788.91 | 17.06 | 0.00 | 313.00 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:10 | 1637.78 | 13.81 | 3.67 | 318.17 | 913.02 | 17.07 | 0.00 | 287.17 |
October | 330.00 | 0.49 | 0.48 | 01-OCT-07:10 | 2826.10 | 18.69 | 80.67 | 314.83 | 1250.42 | 18.21 | 10.50 | 288.33 |
November | 308.00 | 0.50 | 0.48 | 01-NOV-07:00 | 7900.93 | 35.88 | 296.00 | 289.17 | 1507.00 | 21.51 | 90.83 | 276.50 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7985.69 | 37.33 | 279.33 | 284.33 | 1939.59 | 23.93 | 110.83 | 268.67 |
Annual Sum or Average | 4027.67 | 0.50 | 3072.50 | 19.87 | 1122.33 | 3836.67 | 1053.73 | 18.38 | 340.67 | 3493.67 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 1090.97 | 13.15 | 0.00 | 280.00 | 648.57 | 16.62 | 0.00 | 268.17 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 7985.69 | 37.33 | 297.33 | 360.50 | 1939.59 | 23.93 | 110.83 | 319.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-07:49 | 2031.97 | 21.10 | 100.17 | 273.00 | 1124.05 | 21.78 | 72.33 | 230.50 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2254.39 | 20.93 | 89.67 | 262.67 | 1225.12 | 21.76 | 64.33 | 232.33 |
March | 296.00 | 0.50 | 0.48 | 02-MAR-12:39 | 2330.42 | 19.38 | 74.33 | 316.33 | 1282.27 | 21.34 | 56.50 | 282.67 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:10 | 2389.35 | 19.68 | 95.67 | 327.17 | 1311.29 | 20.68 | 68.00 | 297.33 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-06:40 | 2688.14 | 20.34 | 106.00 | 361.33 | 1132.72 | 20.34 | 55.00 | 321.33 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:10 | 2428.98 | 19.78 | 114.00 | 359.50 | 1071.06 | 20.30 | 62.67 | 327.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:19 | 2342.29 | 20.03 | 112.33 | 366.67 | 1052.31 | 19.69 | 53.67 | 324.50 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-06:49 | 2153.24 | 19.94 | 105.17 | 348.00 | 1163.66 | 21.06 | 75.50 | 313.33 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-06:49 | 2071.33 | 20.14 | 96.00 | 314.67 | 1092.21 | 21.09 | 67.50 | 282.33 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-06:49 | 2163.97 | 20.38 | 87.67 | 303.33 | 1137.44 | 21.19 | 57.00 | 273.67 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-07:49 | 1792.96 | 19.89 | 84.00 | 267.83 | 948.28 | 20.60 | 55.50 | 235.67 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-07:40 | 1920.79 | 20.84 | 89.17 | 258.67 | 1051.36 | 21.52 | 61.67 | 214.83 |
Annual Sum or Average | 4027.67 | 0.51 | 2227.09 | 20.18 | 1154.17 | 3759.17 | 1131.46 | 20.89 | 749.67 | 3335.67 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1792.96 | 19.38 | 74.33 | 258.67 | 948.28 | 19.69 | 53.67 | 214.83 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2688.14 | 21.10 | 114.00 | 366.67 | 1311.29 | 21.78 | 75.50 | 327.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-08:50 | 557.19 | 10.65 | 0.00 | 253.00 | 378.25 | 14.33 | 0.00 | 181.17 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 644.51 | 11.87 | 0.00 | 249.67 | 438.68 | 15.55 | 0.00 | 194.33 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 754.37 | 13.06 | 0.00 | 307.83 | 496.44 | 16.61 | 0.00 | 250.17 |
April | 347.33 | 0.51 | 0.48 | 01-APR-07:49 | 897.84 | 13.33 | 0.00 | 327.33 | 572.44 | 16.81 | 0.00 | 292.00 |
May | 353.67 | 0.49 | 0.48 | 01-MAY-06:00 | 1098.84 | 15.58 | 27.17 | 370.83 | 662.90 | 18.94 | 27.50 | 336.17 |
June | 394.00 | 0.49 | 0.48 | 01-JUN-06:19 | 1268.68 | 17.10 | 58.00 | 374.67 | 711.88 | 20.26 | 59.33 | 349.33 |
July | 390.00 | 0.49 | 0.48 | 01-JUL-06:40 | 1240.04 | 15.21 | 23.50 | 376.67 | 706.34 | 18.56 | 24.50 | 343.83 |
August | 380.83 | 0.50 | 0.48 | 01-AUG-06:00 | 1088.94 | 13.76 | 0.00 | 353.67 | 641.63 | 17.21 | 0.00 | 322.00 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:19 | 912.94 | 13.15 | 0.00 | 316.17 | 550.50 | 16.54 | 0.00 | 272.00 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-07:30 | 788.64 | 13.08 | 0.00 | 297.50 | 506.03 | 16.62 | 0.00 | 252.67 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-09:39 | 572.88 | 11.17 | 0.00 | 245.17 | 390.85 | 14.91 | 0.00 | 182.17 |
December | 282.83 | 0.53 | 0.48 | 01-DEC-08:30 | 557.15 | 10.81 | 0.00 | 244.17 | 380.25 | 14.56 | 0.00 | 162.83 |
Annual Sum or Average | 4027.67 | 0.51 | 891.41 | 13.41 | 108.67 | 3716.67 | 548.63 | 16.90 | 111.33 | 3138.67 | ||
Minimum of Months | 282.83 | 0.49 | 0.48 | 557.15 | 10.65 | 0.00 | 244.17 | 378.25 | 14.33 | 0.00 | 162.83 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 1268.68 | 17.10 | 58.00 | 376.67 | 711.88 | 20.26 | 59.33 | 349.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.52 | 0.48 | 01-JAN-08:50 | 2321.02 | 22.10 | 109.33 | 277.17 | 1315.74 | 22.65 | 81.83 | 237.67 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2063.64 | 19.78 | 79.17 | 267.33 | 1133.06 | 21.59 | 60.17 | 237.67 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 2243.37 | 20.10 | 81.00 | 313.33 | 1207.16 | 21.08 | 56.67 | 277.33 |
April | 347.33 | 0.51 | 0.48 | 01-APR-08:09 | 2506.37 | 18.32 | 82.00 | 327.67 | 1360.17 | 19.37 | 53.00 | 298.00 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:40 | 2077.79 | 13.62 | 0.00 | 357.33 | 1143.15 | 17.07 | 0.00 | 321.50 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-07:10 | 2201.42 | 13.52 | 0.00 | 359.17 | 980.57 | 16.89 | 0.00 | 324.67 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-07:10 | 2035.05 | 14.08 | 3.67 | 366.83 | 953.48 | 17.19 | 0.00 | 328.17 |
August | 380.83 | 0.50 | 0.48 | 01-AUG-07:40 | 2101.10 | 16.77 | 59.00 | 350.83 | 1130.82 | 17.48 | 5.50 | 316.67 |
September | 342.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1962.27 | 18.66 | 80.50 | 315.83 | 1038.51 | 19.75 | 51.67 | 283.67 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:40 | 2510.50 | 21.84 | 108.83 | 310.17 | 1073.35 | 21.03 | 53.50 | 277.17 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-09:39 | 2020.19 | 20.99 | 95.17 | 268.33 | 1114.12 | 21.71 | 66.67 | 236.83 |
December | 282.83 | 0.51 | 0.48 | 01-DEC-08:30 | 2166.51 | 22.79 | 103.00 | 271.50 | 1200.49 | 23.14 | 74.00 | 226.50 |
Annual Sum or Average | 4027.67 | 0.51 | 2182.06 | 18.24 | 801.67 | 3785.50 | 1130.76 | 19.69 | 503.00 | 3365.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 1962.27 | 13.52 | 0.00 | 267.33 | 953.48 | 16.89 | 0.00 | 226.50 | |
Maximum of Months | 394.00 | 0.52 | 0.48 | 2510.50 | 22.79 | 109.33 | 366.83 | 1360.17 | 23.14 | 81.83 | 328.17 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.684053E+09 | 69674.43 | 23-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.650566E+09 | 69568.73 | 06-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.382885E+09 | 69416.92 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.335580E+09 | 69545.10 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205308E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.684053E+09 | 69674.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3797930.75 | 1106.72 | 05-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3797930.75 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3797930.75 | 1106.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5155902.45 | 883.14 | 05-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 369376.18 | 205.94 | 17-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6489791.95 | 1060.13 | 21-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 12015070.57 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6489791.95 | 1060.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 12451281.04 | 1418.89 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5351598.83 | 1233.02 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7075417.51 | 1220.05 | 20-DEC-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24878297.39 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12451281.04 | 1418.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.586943E+10 | 124802.19 | 23-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283164E+10 | 124809.70 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196258E+10 | 124739.95 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148793E+09 | 19731.83 | 16-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.355404E+10 | 127878.36 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143665E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.586943E+10 | 127878.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203341E+10 | 120819.42 | 11-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.844401E+09 | 120789.53 | 06-FEB-05:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.855429E+09 | 120626.47 | 11-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15168969.38 | 7522.51 | 16-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154569E+10 | 120850.65 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.529409E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203341E+10 | 120850.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150081E+10 | 137851.21 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.759833E+09 | 137814.55 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121299E+10 | 121028.15 | 11-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.971681E+09 | 137979.67 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444531E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.150081E+10 | 137979.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.165778E+10 | 114056.25 | 23-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.712215E+09 | 113968.60 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.594513E+09 | 60357.73 | 11-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.748648E+09 | 114103.26 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371315E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.165778E+10 | 114103.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.194564E+10 | 14426.16 | 09-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106322E+10 | 14332.48 | 06-FEB-05:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.700706E+09 | 14399.33 | 13-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19279182.57 | 2291.55 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24258399.70 | 5115.27 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205779E+09 | 14381.23 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129559E+10 | 14330.50 | 27-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.525447E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.194564E+10 | 14426.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.763990E+09 | 14038.13 | 07-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411554E+09 | 14046.59 | 06-FEB-05:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350487E+09 | 14034.84 | 11-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3973899.42 | 737.79 | 11-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8180695.87 | 2592.65 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63110442.05 | 14028.56 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.621056E+09 | 14044.08 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222235E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.763990E+09 | 14046.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.749286E+09 | 16211.18 | 14-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.453461E+09 | 16169.98 | 06-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.506356E+09 | 16218.03 | 11-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9305150.82 | 1040.59 | 11-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8746534.72 | 1395.64 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45503289.71 | 16114.02 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.554120E+09 | 16222.65 | 30-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232678E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.749286E+09 | 16222.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.660495E+09 | 14159.41 | 23-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.346947E+09 | 14151.41 | 17-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248731E+09 | 14148.35 | 11-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3751658.33 | 570.53 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40761156.10 | 13055.49 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.402871E+09 | 14177.11 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170356E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.660495E+09 | 14177.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.890839E+09 | 220319.46 | 16-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.679676E+09 | 219889.30 | 13-FEB-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.592073E+09 | 220095.20 | 04-MAR-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.680720E+09 | 220314.64 | 16-APR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175230E+10 | 219895.07 | 29-MAY-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152004E+10 | 218482.79 | 12-JUN-02:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166144E+10 | 219407.64 | 04-JUL-20:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.933318E+09 | 217905.08 | 06-AUG-22:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159255E+10 | 220119.77 | 04-SEP-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193296E+10 | 220318.50 | 01-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174189E+10 | 220319.17 | 26-NOV-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175518E+10 | 220319.22 | 24-DEC-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157330E+11 | |||||||
Minimum of Months | 0.592073E+09 | 217905.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.193296E+10 | 220319.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 41866813.40 | 11049.84 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15713675.03 | 10399.22 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21113894.41 | 10454.97 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20819933.98 | 9598.86 | 18-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33397.57 | 46.57 | 27-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20492749.17 | 12046.72 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120040E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41866813.40 | 12046.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.637701E+09 | 116162.30 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.275095E+09 | 110124.15 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.543077E+09 | 111107.95 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33859468.44 | 15731.59 | 18-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 80598.31 | 268.66 | 27-NOV-13:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.355926E+09 | 129781.89 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184574E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.637701E+09 | 129781.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 67293516.01 | 15339.69 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25939684.05 | 14538.56 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 18927048.17 | 14724.00 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6475320.87 | 9919.68 | 18-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 577753.19 | 914.78 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39370700.62 | 16223.72 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158584E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 67293516.01 | 16223.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.234518E+11 | 0.179693E+11 | 140607.25 | 16-JAN-11:28 | 114764.84 | 0.19 |
February | 0.00 | 0.00 | 0.273129E+11 | 0.216786E+11 | 144421.93 | 20-FEB-12:30 | 115258.58 | 0.29 |
March | 0.00 | 0.00 | 0.367363E+11 | 0.314359E+11 | 161373.10 | 07-MAR-04:01 | 94953.56 | 0.27 |
April | 0.00 | 0.00 | 0.569252E+11 | 0.498734E+11 | 166033.79 | 29-APR-03:01 | 92019.28 | 0.46 |
May | 0.00 | 0.00 | 0.106281E+12 | 0.831457E+11 | 188472.68 | 21-MAY-21:31 | 91797.13 | 0.61 |
June | 0.00 | 0.00 | 0.110376E+12 | 0.837752E+11 | 187816.31 | 18-JUN-21:21 | 92282.10 | 0.62 |
July | 0.00 | 0.00 | 0.120105E+12 | 0.863210E+11 | 192861.26 | 02-JUL-15:40 | 96129.35 | 0.61 |
August | 0.00 | 0.00 | 0.129906E+12 | 0.954257E+11 | 189887.40 | 06-AUG-11:32 | 93855.56 | 0.66 |
September | 0.00 | 0.00 | 0.113197E+12 | 0.837496E+11 | 187128.35 | 17-SEP-09:40 | 92739.76 | 0.64 |
October | 0.00 | 0.00 | 0.983517E+11 | 0.766437E+11 | 187766.70 | 08-OCT-11:51 | 92577.28 | 0.56 |
November | 0.00 | 0.00 | 0.552133E+11 | 0.461215E+11 | 169753.03 | 11-NOV-14:52 | 99383.88 | 0.41 |
December | 0.00 | 0.00 | 0.361559E+11 | 0.298053E+11 | 160770.60 | 15-DEC-05:11 | 96858.04 | 0.26 |
Annual Sum or Average | 0.914013E+12 | 0.705945E+12 | 0.46 | |||||
Minimum of Months | 0.00 | 0.00 | 0.234518E+11 | 0.179693E+11 | 140607.25 | 91797.13 | 0.19 | |
Maximum of Months | 0.00 | 0.00 | 0.129906E+12 | 0.954257E+11 | 192861.26 | 115258.58 | 0.66 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.410183E+11 | 0.310617E+11 | 145357.69 | 30-JAN-06:01 | 59899.07 | 0.28 |
February | 0.00 | 0.00 | 0.582290E+11 | 0.427584E+11 | 148390.63 | 28-FEB-05:11 | 135535.45 | 0.43 |
March | 0.00 | 0.00 | 0.722455E+11 | 0.574066E+11 | 158266.94 | 07-MAR-05:11 | 137754.45 | 0.42 |
April | 0.00 | 0.00 | 0.115444E+12 | 0.921142E+11 | 167870.99 | 18-APR-14:50 | 167870.99 | 0.69 |
May | 0.00 | 0.00 | 0.144738E+12 | 0.111716E+12 | 197306.34 | 23-MAY-03:01 | 140003.87 | 0.69 |
June | 0.00 | 0.00 | 0.156274E+12 | 0.123610E+12 | 171970.42 | 28-JUN-05:02 | 148867.77 | 0.79 |
July | 0.00 | 0.00 | 0.169299E+12 | 0.131966E+12 | 186193.81 | 03-JUL-05:02 | 151189.04 | 0.84 |
August | 0.00 | 0.00 | 0.184129E+12 | 0.144817E+12 | 173358.48 | 07-AUG-05:03 | 141215.57 | 0.88 |
September | 0.00 | 0.00 | 0.145260E+12 | 0.105950E+12 | 200981.95 | 13-SEP-04:11 | 140262.66 | 0.70 |
October | 0.00 | 0.00 | 0.136556E+12 | 0.107489E+12 | 177326.40 | 21-OCT-04:11 | 138484.75 | 0.66 |
November | 0.00 | 0.00 | 0.876655E+11 | 0.711021E+11 | 164794.16 | 01-NOV-04:11 | 138807.60 | 0.53 |
December | 0.00 | 0.00 | 0.652578E+11 | 0.516044E+11 | 152137.66 | 11-DEC-06:02 | 129202.16 | 0.39 |
Annual Sum or Average | 0.137612E+13 | 0.107160E+13 | 0.61 | |||||
Minimum of Months | 0.00 | 0.00 | 0.410183E+11 | 0.310617E+11 | 145357.69 | 59899.07 | 0.28 | |
Maximum of Months | 0.00 | 0.00 | 0.184129E+12 | 0.144817E+12 | 200981.95 | 167870.99 | 0.88 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.324027E+12 | 0.238106E+12 | 1197050.18 | 19-JAN-06:04 | 905491.82 | 0.26 |
February | 0.00 | 0.00 | 0.456705E+12 | 0.321633E+12 | 1290152.55 | 03-FEB-05:11 | 878366.07 | 0.40 |
March | 0.00 | 0.00 | 0.540026E+12 | 0.407088E+12 | 1418892.22 | 27-MAR-05:02 | 1150204.00 | 0.38 |
April | 0.00 | 0.00 | 0.837535E+12 | 0.627183E+12 | 1606311.37 | 29-APR-05:03 | 1259796.40 | 0.52 |
May | 0.00 | 0.00 | 0.130905E+13 | 0.967001E+12 | 2241229.52 | 23-MAY-05:02 | 1361786.51 | 0.64 |
June | 0.00 | 0.00 | 0.133158E+13 | 0.995584E+12 | 1915320.31 | 08-JUN-04:11 | 1259599.89 | 0.67 |
July | 0.00 | 0.00 | 0.138134E+13 | 0.988039E+12 | 2051565.76 | 25-JUL-05:02 | 1377851.96 | 0.66 |
August | 0.00 | 0.00 | 0.143464E+13 | 0.102814E+13 | 2056590.86 | 16-AUG-04:11 | 1266930.06 | 0.67 |
September | 0.00 | 0.00 | 0.128848E+13 | 0.883055E+12 | 2234216.82 | 05-SEP-04:11 | 1240544.25 | 0.64 |
October | 0.00 | 0.00 | 0.113187E+13 | 0.836754E+12 | 2102587.54 | 21-OCT-04:11 | 1260403.37 | 0.55 |
November | 0.00 | 0.00 | 0.662167E+12 | 0.512324E+12 | 1557079.52 | 02-NOV-04:11 | 1235323.19 | 0.46 |
December | 0.00 | 0.00 | 0.463392E+12 | 0.340239E+12 | 1550630.66 | 11-DEC-06:01 | 1217302.23 | 0.32 |
Annual Sum or Average | 0.111608E+14 | 0.814515E+13 | 0.52 | |||||
Minimum of Months | 0.00 | 0.00 | 0.324027E+12 | 0.238106E+12 | 1197050.18 | 878366.07 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.143464E+13 | 0.102814E+13 | 2241229.52 | 1377851.96 | 0.67 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.312384E+11 | 0.223451E+11 | 125478.96 | 19-JAN-15:00 | 85101.83 | 0.26 |
February | 0.00 | 0.00 | 0.453487E+11 | 0.316974E+11 | 124951.46 | 24-FEB-16:00 | 89103.52 | 0.40 |
March | 0.00 | 0.00 | 0.552785E+11 | 0.413319E+11 | 161486.59 | 27-MAR-05:02 | 123071.41 | 0.37 |
April | 0.00 | 0.00 | 0.884136E+11 | 0.669879E+11 | 165689.30 | 29-APR-04:11 | 127088.83 | 0.51 |
May | 0.00 | 0.00 | 0.144684E+12 | 0.109273E+12 | 235403.60 | 23-MAY-05:02 | 136073.29 | 0.65 |
June | 0.00 | 0.00 | 0.149240E+12 | 0.114654E+12 | 185292.25 | 06-JUN-04:11 | 131458.95 | 0.68 |
July | 0.00 | 0.00 | 0.154221E+12 | 0.113248E+12 | 217963.68 | 25-JUL-05:02 | 139293.36 | 0.67 |
August | 0.00 | 0.00 | 0.158123E+12 | 0.116166E+12 | 220755.63 | 16-AUG-04:11 | 128817.92 | 0.68 |
September | 0.00 | 0.00 | 0.138698E+12 | 0.966453E+11 | 234859.69 | 05-SEP-04:11 | 129402.11 | 0.65 |
October | 0.00 | 0.00 | 0.120338E+12 | 0.901074E+11 | 215794.39 | 14-OCT-05:02 | 135879.96 | 0.55 |
November | 0.00 | 0.00 | 0.646515E+11 | 0.498302E+11 | 181779.99 | 01-NOV-05:02 | 127559.39 | 0.45 |
December | 0.00 | 0.00 | 0.447232E+11 | 0.325670E+11 | 152864.97 | 11-DEC-06:01 | 114367.40 | 0.31 |
Annual Sum or Average | 0.119496E+13 | 0.884853E+12 | 0.51 | |||||
Minimum of Months | 0.00 | 0.00 | 0.312384E+11 | 0.223451E+11 | 124951.46 | 85101.83 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.158123E+12 | 0.116166E+12 | 235403.60 | 139293.36 | 0.68 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.105867E+12 | 0.102241E+12 | 199054.48 | 31-JAN-12:50 | 118981.16 | 0.00 |
February | 0.00 | 0.00 | 0.256864E+12 | 0.246020E+12 | 297349.31 | 24-FEB-10:30 | 205088.84 | 0.00 |
March | 0.00 | 0.00 | 0.412470E+12 | 0.388263E+12 | 361156.47 | 29-MAR-08:40 | 291882.23 | 0.00 |
April | 0.00 | 0.00 | 0.866307E+12 | 0.804186E+12 | 405803.29 | 06-APR-07:00 | 378484.90 | 0.00 |
May | 0.00 | 0.00 | 0.330249E+12 | 0.320250E+12 | 133909.02 | 01-MAY-09:05 | 125675.08 | 0.00 |
June | 0.00 | 0.00 | 0.547952E+12 | 0.536814E+12 | 222616.09 | 29-JUN-15:00 | 207676.70 | 0.00 |
July | 0.00 | 0.00 | 0.803452E+12 | 0.791072E+12 | 310076.70 | 12-JUL-12:30 | 296398.87 | 0.00 |
August | 0.00 | 0.00 | 0.103653E+13 | 0.102483E+13 | 404798.07 | 07-AUG-14:05 | 389422.34 | 0.00 |
September | 0.00 | 0.00 | 0.323688E+12 | 0.312755E+12 | 137411.94 | 01-SEP-00:10 | 135877.34 | 0.00 |
October | 0.00 | 0.00 | 0.490608E+12 | 0.477880E+12 | 259895.64 | 31-OCT-11:00 | 207301.05 | 0.00 |
November | 0.00 | 0.00 | 0.405650E+12 | 0.369679E+12 | 342819.58 | 28-NOV-08:50 | 294102.34 | 0.00 |
December | 0.00 | 0.00 | 0.487442E+12 | 0.436522E+12 | 412849.02 | 28-DEC-09:50 | 380680.74 | 0.00 |
Annual Sum or Average | 0.606708E+13 | 0.581052E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.105867E+12 | 0.102241E+12 | 133909.02 | 118981.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103653E+13 | 0.102483E+13 | 412849.02 | 389422.34 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.505520E+10 | 0.505511E+10 | 2540.50 | 01-JAN-17:30 | 2540.50 | 0.00 |
February | 0.00 | 0.00 | 0.914798E+10 | 0.914798E+10 | 4533.21 | 26-FEB-17:52 | 4533.21 | 0.00 |
March | 0.00 | 0.00 | 0.150771E+11 | 0.150771E+11 | 6080.56 | 05-MAR-17:50 | 6080.56 | 0.00 |
April | 0.00 | 0.00 | 0.194272E+11 | 0.194272E+11 | 8182.19 | 16-APR-18:12 | 8182.19 | 0.00 |
May | 0.00 | 0.00 | 0.562281E+10 | 0.562281E+10 | 2522.08 | 29-MAY-18:04 | 2522.08 | 0.00 |
June | 0.00 | 0.00 | 0.101154E+11 | 0.101154E+11 | 4311.67 | 11-JUN-18:30 | 4311.67 | 0.00 |
July | 0.00 | 0.00 | 0.153228E+11 | 0.153228E+11 | 6070.46 | 23-JUL-18:55 | 6070.46 | 0.00 |
August | 0.00 | 0.00 | 0.202015E+11 | 0.202015E+11 | 7907.66 | 06-AUG-18:00 | 7907.66 | 0.00 |
September | 0.00 | 0.00 | 0.545942E+10 | 0.545942E+10 | 2609.84 | 03-SEP-18:06 | 2609.84 | 0.00 |
October | 0.00 | 0.00 | 0.104856E+11 | 0.104856E+11 | 4437.45 | 01-OCT-17:33 | 4437.45 | 0.00 |
November | 0.00 | 0.00 | 0.147423E+11 | 0.147423E+11 | 6274.64 | 12-NOV-17:10 | 6274.64 | 0.00 |
December | 0.00 | 0.00 | 0.199831E+11 | 0.199831E+11 | 8087.62 | 25-DEC-16:55 | 8087.62 | 0.00 |
Annual Sum or Average | 0.150641E+12 | 0.150640E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.505520E+10 | 0.505511E+10 | 2522.08 | 2522.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202015E+11 | 0.202015E+11 | 8182.19 | 8182.19 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.375009E+11 | 0.375000E+11 | 21950.08 | 01-JAN-17:20 | 21950.08 | 0.00 |
February | 0.00 | 0.00 | 0.788668E+11 | 0.788667E+11 | 41680.43 | 26-FEB-17:58 | 41680.43 | 0.00 |
March | 0.00 | 0.00 | 0.136802E+12 | 0.136802E+12 | 56613.99 | 06-MAR-18:00 | 56613.99 | 0.00 |
April | 0.00 | 0.00 | 0.183361E+12 | 0.183361E+12 | 76803.45 | 16-APR-18:17 | 76803.45 | 0.00 |
May | 0.00 | 0.00 | 0.514916E+11 | 0.514916E+11 | 23205.49 | 28-MAY-18:30 | 23205.49 | 0.00 |
June | 0.00 | 0.00 | 0.955743E+11 | 0.955743E+11 | 40708.70 | 11-JUN-18:30 | 40708.70 | 0.00 |
July | 0.00 | 0.00 | 0.145674E+12 | 0.145674E+12 | 57201.45 | 23-JUL-19:00 | 57201.45 | 0.00 |
August | 0.00 | 0.00 | 0.192298E+12 | 0.192298E+12 | 74481.47 | 06-AUG-17:38 | 74481.47 | 0.00 |
September | 0.00 | 0.00 | 0.492813E+11 | 0.492813E+11 | 24434.30 | 03-SEP-17:58 | 24434.30 | 0.00 |
October | 0.00 | 0.00 | 0.973089E+11 | 0.973089E+11 | 41423.62 | 09-OCT-17:28 | 41423.62 | 0.00 |
November | 0.00 | 0.00 | 0.134856E+12 | 0.134856E+12 | 57980.39 | 06-NOV-17:00 | 57980.39 | 0.00 |
December | 0.00 | 0.00 | 0.182038E+12 | 0.182038E+12 | 74706.16 | 17-DEC-17:05 | 74706.16 | 0.00 |
Annual Sum or Average | 0.138505E+13 | 0.138505E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.375009E+11 | 0.375000E+11 | 21950.08 | 21950.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.192298E+12 | 0.192298E+12 | 76803.45 | 76803.45 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.271425E+10 | 0.271418E+10 | 2252.35 | 31-JAN-17:50 | 2252.35 | 0.00 |
February | 0.00 | 0.00 | 0.714950E+10 | 0.714949E+10 | 4194.86 | 26-FEB-17:56 | 4194.86 | 0.00 |
March | 0.00 | 0.00 | 0.131805E+11 | 0.131805E+11 | 5729.99 | 06-MAR-17:50 | 5729.99 | 0.00 |
April | 0.00 | 0.00 | 0.182290E+11 | 0.182290E+11 | 7850.46 | 23-APR-18:04 | 7850.46 | 0.00 |
May | 0.00 | 0.00 | 0.528986E+10 | 0.528986E+10 | 2641.10 | 29-MAY-18:14 | 2641.10 | 0.00 |
June | 0.00 | 0.00 | 0.971585E+10 | 0.971585E+10 | 4342.46 | 11-JUN-18:30 | 4342.46 | 0.00 |
July | 0.00 | 0.00 | 0.147414E+11 | 0.147414E+11 | 5977.15 | 23-JUL-19:00 | 5977.15 | 0.00 |
August | 0.00 | 0.00 | 0.193533E+11 | 0.193533E+11 | 7700.33 | 06-AUG-17:42 | 7700.33 | 0.00 |
September | 0.00 | 0.00 | 0.503382E+10 | 0.503382E+10 | 2709.22 | 03-SEP-17:56 | 2709.22 | 0.00 |
October | 0.00 | 0.00 | 0.968569E+10 | 0.968569E+10 | 4379.84 | 09-OCT-17:30 | 4379.84 | 0.00 |
November | 0.00 | 0.00 | 0.130107E+11 | 0.130107E+11 | 5865.55 | 06-NOV-17:00 | 5865.55 | 0.00 |
December | 0.00 | 0.00 | 0.174007E+11 | 0.174007E+11 | 7555.75 | 10-DEC-17:04 | 7555.75 | 0.00 |
Annual Sum or Average | 0.135505E+12 | 0.135504E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.271425E+10 | 0.271418E+10 | 2252.35 | 2252.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.193533E+11 | 0.193533E+11 | 7850.46 | 7850.46 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7395.95 | 38177.88 | 01-JAN-08:00 | 10490.88 | 42476.03 | 23-JAN-12:20 |
February | 7053.27 | 38213.85 | 26-FEB-08:20 | 10497.17 | 42355.36 | 01-FEB-12:50 |
March | 5872.20 | 38339.74 | 26-MAR-07:10 | 10779.96 | 41449.88 | 01-MAR-12:10 |
April | 7109.33 | 38547.41 | 30-APR-06:47 | 9181.83 | 39157.27 | 03-APR-11:30 |
May | 7109.33 | 38712.80 | 29-MAY-06:47 | 8760.47 | 36761.20 | 01-MAY-12:00 |
June | 6651.64 | 38823.06 | 25-JUN-06:35 | 8342.98 | 34264.87 | 01-JUN-11:20 |
July | 8444.12 | 38867.19 | 23-JUL-06:37 | 7104.48 | 32640.50 | 03-JUL-11:40 |
August | 6632.74 | 38858.67 | 06-AUG-06:50 | 8177.56 | 33398.35 | 31-AUG-11:10 |
September | 7500.28 | 38782.93 | 03-SEP-06:35 | 7998.77 | 35293.85 | 29-SEP-11:30 |
October | 7841.24 | 38645.10 | 01-OCT-06:50 | 8730.94 | 38014.12 | 31-OCT-12:00 |
November | 7738.89 | 38434.12 | 05-NOV-07:05 | 9712.74 | 40404.38 | 30-NOV-12:30 |
December | 7515.22 | 38281.19 | 03-DEC-08:20 | 9876.97 | 41971.73 | 29-DEC-13:00 |
Annual Sum or Average | 7240.08 | 9130.33 | ||||
Minimum of Months | 5872.20 | 38177.88 | 7104.48 | 32640.50 | ||
Maximum of Months | 8444.12 | 38867.19 | 10779.96 | 42476.03 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6514.13 | 2609805.65 | 25-JAN-05:12 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 3748.47 | 1010333.12 | 17-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2925.34 | 1019463.79 | 11-MAR-06:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 325.12 | 317145.69 | 02-APR-23:07 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 636.79 | 214727.95 | 29-MAY-22:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 576.51 | 214111.68 | 03-JUN-03:50 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 609.02 | 214334.32 | 04-JUL-20:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 341.86 | 212822.21 | 30-AUG-03:47 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 603.22 | 214970.05 | 04-SEP-20:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 723.91 | 265228.99 | 29-OCT-13:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 852.71 | 503164.48 | 19-NOV-12:37 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4454.33 | 991786.13 | 20-DEC-06:02 |
Annual Sum or Average | 0.00 | 1857.67 | ||||
Minimum of Months | 0.00 | 0.00 | 325.12 | 212822.21 | ||
Maximum of Months | 0.00 | 0.00 | 6514.13 | 2609805.65 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 170055.39 | 1822570.81 | 19-JAN-15:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 265198.87 | 1771414.57 | 24-FEB-11:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 286969.31 | 1730079.58 | 07-MAR-14:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 466804.92 | 1898676.61 | 28-APR-14:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 702569.66 | 2551978.72 | 23-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 736176.61 | 2091043.77 | 27-JUN-10:05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 730486.51 | 2359843.46 | 25-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 767157.39 | 2186932.68 | 01-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 708188.18 | 2157204.77 | 01-SEP-12:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 599095.88 | 2283183.89 | 14-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 360556.51 | 1916848.31 | 07-NOV-11:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 246640.97 | 1894628.71 | 13-DEC-11:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 504574.20 | 0.00 | ||||
Minimum of Months | 170055.39 | 1730079.58 | 0.00 | 0.00 | ||
Maximum of Months | 767157.39 | 2551978.72 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 169773.11 | 1935807.00 | 19-JAN-10:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 264735.84 | 2002026.63 | 24-FEB-11:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 286614.60 | 2095581.31 | 27-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 467009.34 | 2476626.22 | 29-APR-05:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 711698.43 | 3441721.50 | 20-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 740995.66 | 3186540.42 | 30-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 733762.90 | 3266979.32 | 26-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 769770.75 | 3427937.41 | 16-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 712941.67 | 3598427.69 | 05-SEP-04:11 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 601702.22 | 3419092.85 | 21-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 360791.99 | 2367561.29 | 02-NOV-04:12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 246441.15 | 2980192.49 | 11-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 506787.46 | 0.00 | ||||
Minimum of Months | 169773.11 | 1935807.00 | 0.00 | 0.00 | ||
Maximum of Months | 769770.75 | 3598427.69 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 117663.44 | 705315.63 | 02-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 272958.74 | 963942.46 | 02-FEB-13:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 439745.11 | 1260126.86 | 26-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 913537.79 | 1663242.42 | 28-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 688606.01 | 1047695.30 | 28-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 929787.39 | 1334040.86 | 14-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1159987.10 | 1628770.53 | 21-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1345034.09 | 1810136.21 | 30-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 656839.48 | 1199328.53 | 09-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 714971.44 | 1287082.45 | 05-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 496687.24 | 1284326.93 | 02-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 509566.25 | 1483616.55 | 13-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 689838.84 | 0.00 | ||||
Minimum of Months | 117663.44 | 705315.63 | 0.00 | 0.00 | ||
Maximum of Months | 1345034.09 | 1810136.21 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 278758.24 | 4131603.51 | 19-JAN-15:05 | 710.74 | 100398.65 | 23-JAN-17:40 |
February | 435514.50 | 3995259.13 | 24-FEB-11:05 | 624.37 | 119126.79 | 04-FEB-08:30 |
March | 504016.89 | 4715186.98 | 28-MAR-12:05 | 1155.01 | 111517.11 | 21-MAR-10:40 |
April | 871415.56 | 5769775.57 | 28-APR-16:00 | 485.04 | 72202.92 | 03-APR-06:10 |
May | 1871467.12 | 5997086.86 | 24-MAY-10:05 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 2181696.44 | 6427938.08 | 29-JUN-12:05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2522857.57 | 6896351.22 | 05-JUL-12:05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 2477270.42 | 6498369.56 | 07-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 2042839.53 | 6432778.84 | 18-SEP-14:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1602568.69 | 6739045.25 | 06-OCT-14:05 | 129.59 | 79556.16 | 27-OCT-20:40 |
November | 728192.93 | 5921844.37 | 01-NOV-13:05 | 568.03 | 110664.84 | 15-NOV-07:40 |
December | 469357.97 | 5307436.95 | 12-DEC-14:05 | 976.80 | 125346.41 | 18-DEC-09:10 |
Annual Sum or Average | 1338175.19 | 386.88 | ||||
Minimum of Months | 278758.24 | 3995259.13 | 0.00 | 0.00 | ||
Maximum of Months | 2522857.57 | 6896351.22 | 1155.01 | 125346.41 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147270E+11 | 0.85 | 8933.49 | 01-JAN-00:11 | 1.38 |
February | 0.129634E+11 | 0.83 | 8933.49 | 01-FEB-04:01 | 1.38 |
March | 0.146697E+11 | 0.85 | 8933.49 | 01-MAR-04:01 | 1.38 |
April | 0.135423E+11 | 0.80 | 8933.49 | 01-APR-03:01 | 1.38 |
May | 0.150853E+11 | 0.87 | 8933.49 | 01-MAY-00:01 | 1.38 |
June | 0.145692E+11 | 0.86 | 8933.49 | 01-JUN-03:01 | 1.38 |
July | 0.149392E+11 | 0.86 | 8933.49 | 01-JUL-03:01 | 1.38 |
August | 0.159386E+11 | 0.92 | 8933.49 | 01-AUG-03:01 | 1.38 |
September | 0.152245E+11 | 0.90 | 8933.49 | 01-SEP-03:01 | 1.38 |
October | 0.156647E+11 | 0.90 | 8933.49 | 01-OCT-09:40 | 1.38 |
November | 0.150702E+11 | 0.90 | 8933.49 | 01-NOV-03:01 | 1.38 |
December | 0.151073E+11 | 0.87 | 8933.49 | 01-DEC-04:01 | 1.39 |
Annual Sum or Average | 0.177501E+12 | 0.87 | |||
Minimum of Months | 0.129634E+11 | 0.80 | 8933.49 | 1.38 | |
Maximum of Months | 0.159386E+11 | 0.92 | 8933.49 | 1.39 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.381805E+10 | 0.34 | 18342.72 | 30-JAN-06:01 | 1.76 |
February | 0.396834E+10 | 0.36 | 16933.91 | 28-FEB-05:11 | 1.67 |
March | 0.494720E+10 | 0.40 | 18356.75 | 27-MAR-05:02 | 1.76 |
April | 0.577047E+10 | 0.47 | 18356.75 | 24-APR-05:01 | 1.76 |
May | 0.581491E+10 | 0.44 | 18356.75 | 02-MAY-03:01 | 1.76 |
June | 0.642765E+10 | 0.50 | 18356.75 | 01-JUN-04:11 | 1.76 |
July | 0.690974E+10 | 0.53 | 18356.75 | 01-JUL-05:02 | 1.76 |
August | 0.799868E+10 | 0.58 | 18356.75 | 01-AUG-05:01 | 1.76 |
September | 0.552775E+10 | 0.44 | 18356.75 | 01-SEP-05:02 | 1.76 |
October | 0.635211E+10 | 0.47 | 18356.75 | 02-OCT-05:01 | 1.76 |
November | 0.551387E+10 | 0.42 | 18356.75 | 01-NOV-04:11 | 1.76 |
December | 0.512318E+10 | 0.40 | 18356.75 | 11-DEC-06:01 | 1.76 |
Annual Sum or Average | 0.681719E+11 | 0.45 | |||
Minimum of Months | 0.381805E+10 | 0.34 | 16933.91 | 1.67 | |
Maximum of Months | 0.799868E+10 | 0.58 | 18356.75 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.276664E+11 | 0.30 | 119753.32 | 21-JAN-06:03 | 1.43 |
February | 0.270256E+11 | 0.31 | 108396.22 | 27-FEB-06:03 | 1.33 |
March | 0.316779E+11 | 0.32 | 150053.38 | 27-MAR-05:02 | 1.63 |
April | 0.357292E+11 | 0.34 | 168957.72 | 28-APR-05:02 | 1.76 |
May | 0.497960E+11 | 0.41 | 168957.72 | 01-MAY-04:01 | 1.76 |
June | 0.512439E+11 | 0.43 | 168957.72 | 02-JUN-05:02 | 1.76 |
July | 0.499415E+11 | 0.41 | 168957.72 | 01-JUL-05:02 | 1.76 |
August | 0.536433E+11 | 0.43 | 168957.72 | 01-AUG-05:01 | 1.76 |
September | 0.449277E+11 | 0.40 | 168957.72 | 01-SEP-04:11 | 1.76 |
October | 0.474947E+11 | 0.39 | 168957.72 | 04-OCT-04:11 | 1.76 |
November | 0.348368E+11 | 0.33 | 168957.72 | 03-NOV-04:11 | 1.76 |
December | 0.299128E+11 | 0.31 | 168957.72 | 11-DEC-06:01 | 1.76 |
Annual Sum or Average | 0.483896E+12 | 0.36 | |||
Minimum of Months | 0.270256E+11 | 0.30 | 108396.22 | 1.33 | |
Maximum of Months | 0.536433E+11 | 0.43 | 168957.72 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.254119E+10 | 0.29 | 9451.46 | 02-JAN-06:03 | 1.17 |
February | 0.259657E+10 | 0.30 | 8807.17 | 28-FEB-06:03 | 1.12 |
March | 0.305277E+10 | 0.32 | 17328.49 | 27-MAR-05:02 | 1.72 |
April | 0.366989E+10 | 0.33 | 17984.46 | 24-APR-05:01 | 1.76 |
May | 0.565043E+10 | 0.42 | 17984.46 | 02-MAY-04:11 | 1.76 |
June | 0.595926E+10 | 0.45 | 17984.46 | 02-JUN-05:02 | 1.76 |
July | 0.575775E+10 | 0.43 | 17984.46 | 01-JUL-05:02 | 1.76 |
August | 0.607452E+10 | 0.45 | 17984.46 | 01-AUG-05:01 | 1.76 |
September | 0.482424E+10 | 0.40 | 17984.46 | 01-SEP-04:11 | 1.76 |
October | 0.498767E+10 | 0.39 | 17984.46 | 06-OCT-03:01 | 1.76 |
November | 0.317439E+10 | 0.32 | 17984.46 | 01-NOV-05:02 | 1.76 |
December | 0.273779E+10 | 0.30 | 14653.08 | 11-DEC-06:01 | 1.54 |
Annual Sum or Average | 0.510265E+11 | 0.37 | |||
Minimum of Months | 0.254119E+10 | 0.29 | 8807.17 | 1.12 | |
Maximum of Months | 0.607452E+10 | 0.45 | 17984.46 | 1.76 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.941057E+11 | 1.35 | 35135.06 | 01-JAN-00:05 | 1.34 |
February | 0.849987E+11 | 1.35 | 35135.06 | 01-FEB-00:10 | 1.35 |
March | 0.941057E+11 | 1.35 | 35135.06 | 01-MAR-00:10 | 1.35 |
April | 0.910701E+11 | 1.35 | 35135.06 | 01-APR-00:20 | 1.35 |
May | 0.941057E+11 | 1.35 | 35135.06 | 01-MAY-00:01 | 1.35 |
June | 0.910701E+11 | 1.35 | 35135.06 | 01-JUN-00:10 | 1.35 |
July | 0.941057E+11 | 1.35 | 35135.06 | 01-JUL-00:05 | 1.35 |
August | 0.941057E+11 | 1.35 | 35135.06 | 01-AUG-00:10 | 1.35 |
September | 0.910701E+11 | 1.35 | 35135.06 | 01-SEP-00:05 | 1.35 |
October | 0.941057E+11 | 1.35 | 35135.06 | 01-OCT-00:10 | 1.35 |
November | 0.910701E+11 | 1.35 | 35135.06 | 01-NOV-00:10 | 1.35 |
December | 0.941057E+11 | 1.35 | 35135.06 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.110802E+13 | 1.35 | |||
Minimum of Months | 0.849987E+11 | 1.35 | 35135.06 | 1.34 | |
Maximum of Months | 0.941057E+11 | 1.35 | 35135.06 | 1.35 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136983E+10 | 0.91 | 511.44 | 01-JAN-00:05 | 0.91 |
February | 0.123727E+10 | 0.91 | 511.44 | 01-FEB-00:10 | 0.91 |
March | 0.136983E+10 | 0.91 | 511.44 | 01-MAR-00:10 | 0.91 |
April | 0.132565E+10 | 0.91 | 511.44 | 01-APR-00:10 | 0.91 |
May | 0.136983E+10 | 0.91 | 511.44 | 01-MAY-00:01 | 0.91 |
June | 0.132565E+10 | 0.91 | 511.44 | 01-JUN-00:10 | 0.91 |
July | 0.136983E+10 | 0.91 | 511.44 | 01-JUL-00:05 | 0.91 |
August | 0.136983E+10 | 0.91 | 511.44 | 01-AUG-00:10 | 0.91 |
September | 0.132565E+10 | 0.91 | 511.44 | 01-SEP-00:05 | 0.91 |
October | 0.136983E+10 | 0.91 | 511.44 | 01-OCT-00:10 | 0.91 |
November | 0.132565E+10 | 0.91 | 511.44 | 01-NOV-00:10 | 0.91 |
December | 0.136983E+10 | 0.91 | 511.44 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.161287E+11 | 0.91 | |||
Minimum of Months | 0.123727E+10 | 0.91 | 511.44 | 0.91 | |
Maximum of Months | 0.136983E+10 | 0.91 | 511.44 | 0.91 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130029E+11 | 0.91 | 4854.71 | 01-JAN-00:05 | 0.91 |
February | 0.117445E+11 | 0.91 | 4854.71 | 01-FEB-00:10 | 0.91 |
March | 0.130029E+11 | 0.91 | 4854.71 | 01-MAR-00:10 | 0.91 |
April | 0.125834E+11 | 0.91 | 4854.71 | 01-APR-00:10 | 0.91 |
May | 0.130029E+11 | 0.91 | 4854.71 | 01-MAY-00:01 | 0.91 |
June | 0.125834E+11 | 0.91 | 4854.71 | 01-JUN-00:10 | 0.91 |
July | 0.130029E+11 | 0.91 | 4854.71 | 01-JUL-00:05 | 0.91 |
August | 0.130029E+11 | 0.91 | 4854.71 | 01-AUG-00:10 | 0.91 |
September | 0.125834E+11 | 0.91 | 4854.71 | 01-SEP-00:05 | 0.91 |
October | 0.130029E+11 | 0.91 | 4854.71 | 01-OCT-00:10 | 0.91 |
November | 0.125834E+11 | 0.91 | 4854.71 | 01-NOV-00:10 | 0.91 |
December | 0.130029E+11 | 0.91 | 4854.71 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.153098E+12 | 0.91 | |||
Minimum of Months | 0.117445E+11 | 0.91 | 4854.71 | 0.91 | |
Maximum of Months | 0.130029E+11 | 0.91 | 4854.71 | 0.91 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132344E+10 | 0.91 | 494.12 | 01-JAN-00:05 | 0.91 |
February | 0.119536E+10 | 0.91 | 494.12 | 01-FEB-00:10 | 0.91 |
March | 0.132344E+10 | 0.91 | 494.12 | 01-MAR-00:10 | 0.91 |
April | 0.128075E+10 | 0.91 | 494.12 | 01-APR-00:10 | 0.91 |
May | 0.132344E+10 | 0.91 | 494.12 | 01-MAY-00:01 | 0.91 |
June | 0.128075E+10 | 0.91 | 494.12 | 01-JUN-00:20 | 0.91 |
July | 0.132344E+10 | 0.91 | 494.12 | 01-JUL-00:05 | 0.91 |
August | 0.132344E+10 | 0.91 | 494.12 | 01-AUG-00:10 | 0.91 |
September | 0.128075E+10 | 0.91 | 494.12 | 01-SEP-00:05 | 0.91 |
October | 0.132344E+10 | 0.91 | 494.12 | 01-OCT-00:10 | 0.91 |
November | 0.128075E+10 | 0.91 | 494.12 | 01-NOV-00:10 | 0.91 |
December | 0.132344E+10 | 0.91 | 494.12 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.155824E+11 | 0.91 | |||
Minimum of Months | 0.119536E+10 | 0.91 | 494.12 | 0.91 | |
Maximum of Months | 0.132344E+10 | 0.91 | 494.12 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.146466E+09 | 0.133137E+09 | 9627.92 | 25-JAN-05:12 | 8751.78 | 8751.78 | 54.75 | 22.89 |
February | 75692007.48 | 68804034.80 | 6788.73 | 06-FEB-06:03 | 6170.95 | 6170.95 | 64.23 | 11.33 |
March | 62050294.06 | 56403717.30 | 5967.12 | 11-MAR-06:03 | 5424.11 | 5424.11 | 56.16 | 9.43 |
April | 15871634.88 | 14427316.10 | 3937.93 | 24-APR-02:20 | 3579.58 | 3579.58 | 76.14 | 5.48 |
May | 31923298.07 | 29018277.95 | 3932.81 | 01-MAY-02:50 | 3574.92 | 3574.92 | 73.56 | 5.48 |
June | 27715507.59 | 25193396.40 | 3931.40 | 26-JUN-00:20 | 3573.64 | 3573.64 | 72.84 | 5.48 |
July | 30253987.02 | 27500874.20 | 3931.44 | 02-JUL-18:25 | 3573.68 | 3573.68 | 72.86 | 5.48 |
August | 16983120.83 | 15437656.84 | 3931.39 | 06-AUG-13:08 | 3573.63 | 3573.63 | 72.84 | 5.48 |
September | 28916976.33 | 26285531.48 | 3931.40 | 17-SEP-13:20 | 3573.65 | 3573.65 | 72.84 | 5.48 |
October | 35040395.27 | 31851719.30 | 3931.31 | 22-OCT-14:45 | 3573.56 | 3573.56 | 72.80 | 5.48 |
November | 34080158.25 | 30978863.85 | 3931.06 | 05-NOV-21:10 | 3573.33 | 3573.33 | 72.67 | 5.48 |
December | 0.105358E+09 | 95770815.15 | 6791.75 | 21-DEC-06:02 | 6173.70 | 6173.70 | 63.24 | 11.35 |
Annual Sum or Average | 0.610351E+09 | 0.554809E+09 | ||||||
Minimum of Months | 15871634.88 | 14427316.10 | 3931.06 | 3573.33 | 3573.33 | 54.75 | 5.48 | |
Maximum of Months | 0.146466E+09 | 0.133137E+09 | 9627.92 | 8751.78 | 8751.78 | 76.14 | 22.89 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.367747E+09 | 0.334282E+09 | 4327.68 | 31-JAN-17:00 | 3933.86 | 3933.86 | 8.96 | 47.19 |
February | 0.580539E+09 | 0.527710E+09 | 4822.41 | 24-FEB-11:30 | 4383.57 | 4383.57 | 9.24 | 49.37 |
March | 0.661468E+09 | 0.601274E+09 | 4635.83 | 27-MAR-05:02 | 4213.97 | 4213.97 | 7.60 | 48.57 |
April | 0.111578E+10 | 0.101424E+10 | 9580.20 | 26-APR-15:20 | 8708.40 | 8708.40 | 11.75 | 65.26 |
May | 0.217535E+10 | 0.197740E+10 | 14758.22 | 09-MAY-05:02 | 13415.22 | 13415.22 | 9.97 | 77.46 |
June | 0.212263E+10 | 0.192947E+10 | 14758.22 | 20-JUN-05:02 | 13415.22 | 13415.22 | 9.28 | 77.46 |
July | 0.206316E+10 | 0.187541E+10 | 14758.22 | 06-JUL-05:02 | 13415.22 | 13415.22 | 9.69 | 77.46 |
August | 0.224218E+10 | 0.203814E+10 | 14758.22 | 08-AUG-05:02 | 13415.22 | 13415.22 | 9.76 | 77.46 |
September | 0.196769E+10 | 0.178863E+10 | 14758.22 | 06-SEP-05:02 | 13415.22 | 13415.22 | 10.05 | 77.46 |
October | 0.171698E+10 | 0.156074E+10 | 14758.22 | 11-OCT-04:12 | 13415.22 | 13415.22 | 9.88 | 77.46 |
November | 0.849810E+09 | 0.772477E+09 | 6633.90 | 02-NOV-04:12 | 6030.22 | 6030.22 | 8.41 | 56.28 |
December | 0.575753E+09 | 0.523360E+09 | 13493.99 | 11-DEC-06:02 | 12266.04 | 12266.04 | 9.10 | 74.77 |
Annual Sum or Average | 0.164391E+11 | 0.149431E+11 | ||||||
Minimum of Months | 0.367747E+09 | 0.334282E+09 | 4327.68 | 3933.86 | 3933.86 | 7.60 | 47.19 | |
Maximum of Months | 0.224218E+10 | 0.203814E+10 | 14758.22 | 13415.22 | 13415.22 | 11.75 | 77.46 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871592.27 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 77.40 | 0.44 |
February | 0.101979E+09 | 30593696.24 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 65.77 | 0.44 |
March | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 69.09 | 0.44 |
April | 0.109263E+09 | 32778960.26 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 67.71 | 0.44 |
May | 0.112905E+09 | 33871592.27 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 78.02 | 0.44 |
June | 0.109263E+09 | 32778960.26 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 70.88 | 0.44 |
July | 0.112905E+09 | 33871592.27 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 67.25 | 0.44 |
August | 0.112905E+09 | 33871592.27 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 64.91 | 0.44 |
September | 0.109263E+09 | 32778960.26 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 65.79 | 0.44 |
October | 0.112905E+09 | 33871592.27 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 76.60 | 0.44 |
November | 0.109263E+09 | 32778960.26 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 65.94 | 0.44 |
December | 0.112905E+09 | 33871592.27 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 66.48 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398811E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593696.24 | 56.21 | 16.86 | 16.86 | 64.91 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871592.27 | 56.21 | 16.86 | 16.86 | 78.02 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.254241E+10 | 0.231105E+10 | 2445.28 | 01-JAN-00:11 | 2222.76 | 2222.76 | 7.52 | 38.73 |
February | 0.291201E+10 | 0.264702E+10 | 2445.28 | 01-FEB-04:01 | 2222.76 | 2222.76 | 10.15 | 38.73 |
March | 0.370085E+10 | 0.336407E+10 | 2445.28 | 01-MAR-04:01 | 2222.76 | 2222.76 | 9.91 | 38.73 |
April | 0.485415E+10 | 0.441242E+10 | 2445.28 | 01-APR-03:01 | 2222.76 | 2222.76 | 9.98 | 38.73 |
May | 0.477386E+10 | 0.433944E+10 | 2445.28 | 01-MAY-00:01 | 2222.76 | 2222.76 | 7.13 | 38.73 |
June | 0.523047E+10 | 0.475450E+10 | 2445.28 | 01-JUN-03:01 | 2222.76 | 2222.76 | 11.16 | 38.73 |
July | 0.582118E+10 | 0.529145E+10 | 2445.28 | 01-JUL-00:05 | 2222.76 | 2222.76 | 6.96 | 38.73 |
August | 0.598711E+10 | 0.544228E+10 | 2445.28 | 01-AUG-00:10 | 2222.76 | 2222.76 | 6.97 | 38.73 |
September | 0.476032E+10 | 0.432713E+10 | 2445.28 | 01-SEP-00:05 | 2222.76 | 2222.76 | 6.95 | 38.73 |
October | 0.490537E+10 | 0.445898E+10 | 2445.28 | 01-OCT-07:30 | 2222.76 | 2222.76 | 8.33 | 38.73 |
November | 0.403559E+10 | 0.366835E+10 | 2445.28 | 01-NOV-03:01 | 2222.76 | 2222.76 | 10.31 | 38.73 |
December | 0.334744E+10 | 0.304282E+10 | 2445.28 | 01-DEC-04:01 | 2222.76 | 2222.76 | 7.26 | 38.73 |
Annual Sum or Average | 0.528708E+11 | 0.480595E+11 | ||||||
Minimum of Months | 0.254241E+10 | 0.231105E+10 | 2445.28 | 2222.76 | 2222.76 | 6.95 | 38.73 | |
Maximum of Months | 0.598711E+10 | 0.544228E+10 | 2445.28 | 2222.76 | 2222.76 | 11.16 | 38.73 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 88029937.39 | 80019213.09 | 2445.28 | 02-JAN-11:05 | 2222.76 | 2222.76 | 11.19 | 38.73 |
February | 0.217874E+09 | 0.198048E+09 | 2445.28 | 01-FEB-13:50 | 2222.76 | 2222.76 | 15.46 | 19.36 |
March | 0.228878E+09 | 0.208050E+09 | 2445.28 | 06-MAR-09:40 | 2222.76 | 2222.76 | 15.45 | 19.36 |
April | 0.393200E+09 | 0.357419E+09 | 2445.28 | 04-APR-15:30 | 2222.76 | 2222.76 | 15.48 | 19.36 |
May | 0.137385E+10 | 0.124883E+10 | 2445.28 | 01-MAY-07:50 | 2222.76 | 2222.76 | 15.44 | 19.36 |
June | 0.150751E+10 | 0.137033E+10 | 2445.28 | 01-JUN-08:00 | 2222.76 | 2222.76 | 15.58 | 19.36 |
July | 0.157632E+10 | 0.143288E+10 | 2445.28 | 03-JUL-07:50 | 2222.76 | 2222.76 | 15.66 | 19.36 |
August | 0.175238E+10 | 0.159292E+10 | 2445.28 | 01-AUG-05:01 | 2222.76 | 2222.76 | 11.45 | 38.73 |
September | 0.134136E+10 | 0.121929E+10 | 2445.28 | 01-SEP-07:30 | 2222.76 | 2222.76 | 15.58 | 19.36 |
October | 0.118811E+10 | 0.107999E+10 | 2445.28 | 02-OCT-09:40 | 2222.76 | 2222.76 | 15.49 | 19.36 |
November | 0.399803E+09 | 0.363421E+09 | 2445.28 | 01-NOV-07:20 | 2222.76 | 2222.76 | 15.59 | 19.36 |
December | 0.265557E+09 | 0.241391E+09 | 2445.28 | 08-DEC-15:05 | 2222.76 | 2222.76 | 11.11 | 38.73 |
Annual Sum or Average | 0.103329E+11 | 0.939259E+10 | ||||||
Minimum of Months | 88029937.39 | 80019213.09 | 2445.28 | 2222.76 | 2222.76 | 11.11 | 19.36 | |
Maximum of Months | 0.175238E+10 | 0.159292E+10 | 2445.28 | 2222.76 | 2222.76 | 15.66 | 38.73 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.886753E+10 | 0.806058E+10 | 3310.76 | 01-JAN-00:05 | 3009.48 | 3009.48 | 18.95 | 13.97 |
February | 0.800938E+10 | 0.728053E+10 | 3310.76 | 01-FEB-00:10 | 3009.48 | 3009.48 | 26.40 | 13.97 |
March | 0.886753E+10 | 0.806058E+10 | 3310.76 | 01-MAR-00:10 | 3009.48 | 3009.48 | 29.43 | 13.97 |
April | 0.858148E+10 | 0.780056E+10 | 3310.76 | 01-APR-00:10 | 3009.48 | 3009.48 | 36.77 | 13.97 |
May | 0.886753E+10 | 0.806058E+10 | 3310.76 | 01-MAY-00:01 | 3009.48 | 3009.48 | 36.52 | 13.97 |
June | 0.858148E+10 | 0.780056E+10 | 3310.76 | 01-JUN-00:10 | 3009.48 | 3009.48 | 31.13 | 13.97 |
July | 0.886753E+10 | 0.806058E+10 | 3310.76 | 01-JUL-00:05 | 3009.48 | 3009.48 | 36.95 | 13.97 |
August | 0.886753E+10 | 0.806058E+10 | 3310.76 | 01-AUG-00:10 | 3009.48 | 3009.48 | 41.76 | 13.97 |
September | 0.858148E+10 | 0.780056E+10 | 3310.76 | 01-SEP-00:05 | 3009.48 | 3009.48 | 34.46 | 13.97 |
October | 0.886753E+10 | 0.806058E+10 | 3310.76 | 01-OCT-00:10 | 3009.48 | 3009.48 | 30.37 | 13.97 |
November | 0.858148E+10 | 0.780056E+10 | 3310.76 | 01-NOV-00:10 | 3009.48 | 3009.48 | 33.92 | 13.97 |
December | 0.886753E+10 | 0.806058E+10 | 3310.76 | 01-DEC-00:10 | 3009.48 | 3009.48 | 22.57 | 13.97 |
Annual Sum or Average | 0.104408E+12 | 0.949069E+11 | ||||||
Minimum of Months | 0.800938E+10 | 0.728053E+10 | 3310.76 | 3009.48 | 3009.48 | 18.95 | 13.97 | |
Maximum of Months | 0.886753E+10 | 0.806058E+10 | 3310.76 | 3009.48 | 3009.48 | 41.76 | 13.97 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.152056E+11 | 0.138219E+11 | 28482.09 | 19-JAN-15:05 | 25890.22 | 25890.22 | 28.39 | 135.62 |
February | 0.180966E+11 | 0.164498E+11 | 28476.34 | 24-FEB-11:05 | 25884.99 | 25884.99 | 28.15 | 135.62 |
March | 0.227226E+11 | 0.206548E+11 | 28492.11 | 07-MAR-13:05 | 25899.33 | 25899.33 | 28.81 | 135.62 |
April | 0.302466E+11 | 0.274942E+11 | 28492.11 | 24-APR-10:50 | 25899.33 | 25899.33 | 28.82 | 135.62 |
May | 0.348171E+11 | 0.316488E+11 | 28492.11 | 01-MAY-07:50 | 25899.33 | 25899.33 | 29.90 | 135.62 |
June | 0.384470E+11 | 0.349483E+11 | 28492.11 | 01-JUN-08:30 | 25899.33 | 25899.33 | 29.12 | 135.62 |
July | 0.424982E+11 | 0.386309E+11 | 28492.11 | 03-JUL-07:50 | 25899.33 | 25899.33 | 30.22 | 135.62 |
August | 0.444098E+11 | 0.403685E+11 | 28492.11 | 01-AUG-07:50 | 25899.33 | 25899.33 | 29.82 | 135.62 |
September | 0.347568E+11 | 0.315939E+11 | 28492.11 | 01-SEP-07:40 | 25899.33 | 25899.33 | 29.76 | 135.62 |
October | 0.349847E+11 | 0.318011E+11 | 28492.11 | 04-OCT-08:00 | 25899.33 | 25899.33 | 28.85 | 135.62 |
November | 0.254988E+11 | 0.231784E+11 | 28492.11 | 01-NOV-08:30 | 25899.33 | 25899.33 | 29.01 | 135.62 |
December | 0.207362E+11 | 0.188492E+11 | 28492.11 | 11-DEC-13:05 | 25899.33 | 25899.33 | 29.35 | 135.62 |
Annual Sum or Average | 0.362420E+12 | 0.329440E+12 | ||||||
Minimum of Months | 0.152056E+11 | 0.138219E+11 | 28476.34 | 25884.99 | 25884.99 | 28.15 | 135.62 | |
Maximum of Months | 0.444098E+11 | 0.403685E+11 | 28492.11 | 25899.33 | 25899.33 | 30.22 | 135.62 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7395.95 | 38177.88 | 01-JAN-08:00 | 80.66 | 82.22 | 10490.88 | 42476.03 | 23-JAN-12:20 |
February | 7053.27 | 38213.85 | 26-FEB-08:20 | 80.68 | 82.22 | 10497.17 | 42355.36 | 01-FEB-12:50 |
March | 5872.20 | 38339.74 | 26-MAR-07:10 | 80.75 | 82.22 | 10779.96 | 41449.88 | 01-MAR-12:10 |
April | 7109.33 | 38547.41 | 30-APR-06:47 | 80.86 | 82.22 | 9181.83 | 39157.27 | 03-APR-11:30 |
May | 7109.33 | 38712.80 | 29-MAY-06:47 | 80.95 | 82.22 | 8760.47 | 36761.20 | 01-MAY-12:00 |
June | 6651.64 | 38823.06 | 25-JUN-06:35 | 81.01 | 82.22 | 8342.98 | 34264.87 | 01-JUN-11:20 |
July | 8444.12 | 38867.19 | 23-JUL-06:37 | 81.03 | 82.22 | 7104.48 | 32640.50 | 03-JUL-11:40 |
August | 6632.74 | 38858.67 | 06-AUG-06:50 | 81.03 | 82.22 | 8177.56 | 33398.35 | 31-AUG-11:10 |
September | 7500.28 | 38782.93 | 03-SEP-06:35 | 80.99 | 82.22 | 7998.77 | 35293.85 | 29-SEP-11:30 |
October | 7841.24 | 38645.10 | 01-OCT-06:50 | 80.91 | 82.22 | 8730.94 | 38014.12 | 31-OCT-12:00 |
November | 7738.89 | 38434.12 | 05-NOV-07:05 | 80.80 | 82.22 | 9712.74 | 40404.38 | 30-NOV-12:30 |
December | 7515.22 | 38281.19 | 03-DEC-08:20 | 80.71 | 82.22 | 9876.97 | 41971.73 | 29-DEC-13:00 |
Annual Sum or Average | 7240.08 | 9130.33 | ||||||
Minimum of Months | 5872.20 | 38177.88 | 80.66 | 82.22 | 7104.48 | 32640.50 | ||
Maximum of Months | 8444.12 | 38867.19 | 81.03 | 82.22 | 10779.96 | 42476.03 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 72.86 | 72.86 | 6514.13 | 2609805.65 | 25-JAN-05:12 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 65.62 | 65.62 | 3748.47 | 1010333.12 | 17-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 72.35 | 72.35 | 2925.34 | 1019463.79 | 11-MAR-06:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 67.38 | 67.38 | 325.12 | 317145.69 | 02-APR-23:07 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 73.78 | 73.78 | 636.79 | 214727.95 | 29-MAY-22:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 72.65 | 72.65 | 576.51 | 214111.68 | 03-JUN-03:50 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 72.80 | 72.80 | 609.02 | 214334.32 | 04-JUL-20:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 72.80 | 72.80 | 341.86 | 212822.21 | 30-AUG-03:47 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 72.75 | 72.75 | 603.22 | 214970.05 | 04-SEP-20:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 72.75 | 72.75 | 723.91 | 265228.99 | 29-OCT-13:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 72.46 | 72.46 | 852.71 | 503164.48 | 19-NOV-12:37 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 71.28 | 71.28 | 4454.33 | 991786.13 | 20-DEC-06:02 |
Annual Sum or Average | 0.00 | 1857.67 | ||||||
Minimum of Months | 0.00 | 0.00 | 65.62 | 65.62 | 325.12 | 212822.21 | ||
Maximum of Months | 0.00 | 0.00 | 73.78 | 73.78 | 6514.13 | 2609805.65 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 170055.39 | 1822570.81 | 19-JAN-15:05 | 12.32 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 265198.87 | 1771414.57 | 24-FEB-11:05 | 12.16 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 286969.31 | 1730079.58 | 07-MAR-14:05 | 12.03 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 466804.92 | 1898676.61 | 28-APR-14:05 | 12.55 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 702569.66 | 2551978.72 | 23-MAY-05:02 | 14.57 | 6.70 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 736176.61 | 2091043.77 | 27-JUN-10:05 | 13.15 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 730486.51 | 2359843.46 | 25-JUL-05:03 | 13.98 | 6.70 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 767157.39 | 2186932.68 | 01-AUG-05:03 | 13.44 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 708188.18 | 2157204.77 | 01-SEP-12:05 | 13.35 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 599095.88 | 2283183.89 | 14-OCT-05:03 | 13.74 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 360556.51 | 1916848.31 | 07-NOV-11:05 | 12.61 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 246640.97 | 1894628.71 | 13-DEC-11:05 | 12.54 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 504574.20 | 0.00 | ||||||
Minimum of Months | 170055.39 | 1730079.58 | 12.03 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 767157.39 | 2551978.72 | 14.57 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 169773.11 | 1935807.00 | 19-JAN-10:30 | 16.52 | 8.96 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 264735.84 | 2002026.63 | 24-FEB-11:30 | 16.39 | 9.28 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 286614.60 | 2095581.31 | 27-MAR-05:02 | 17.01 | 8.77 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 467009.34 | 2476626.22 | 29-APR-05:03 | 17.05 | 10.02 | 0.00 | 0.00 | 01-APR-00:10 |
May | 711698.43 | 3441721.50 | 20-MAY-05:02 | 17.32 | 12.00 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 740995.66 | 3186540.42 | 30-JUN-05:02 | 16.53 | 11.60 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 733762.90 | 3266979.32 | 26-JUL-05:02 | 16.78 | 11.73 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 769770.75 | 3427937.41 | 16-AUG-05:02 | 17.28 | 11.97 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 712941.67 | 3598427.69 | 05-SEP-04:11 | 17.88 | 12.24 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 601702.22 | 3419092.85 | 21-OCT-05:03 | 17.25 | 11.96 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 360791.99 | 2367561.29 | 02-NOV-04:12 | 16.76 | 9.82 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 246441.15 | 2980192.49 | 11-DEC-06:02 | 16.23 | 11.28 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 506787.46 | 0.00 | ||||||
Minimum of Months | 169773.11 | 1935807.00 | 16.23 | 8.77 | 0.00 | 0.00 | ||
Maximum of Months | 769770.75 | 3598427.69 | 17.88 | 12.24 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 117663.44 | 705315.63 | 02-JAN-15:00 | 32.72 | 28.68 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 272958.74 | 963942.46 | 02-FEB-13:00 | 37.90 | 31.14 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 439745.11 | 1260126.86 | 26-MAR-14:00 | 43.76 | 34.10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 913537.79 | 1663242.42 | 28-APR-15:00 | 51.65 | 38.81 | 0.00 | 0.00 | 01-APR-00:10 |
May | 688606.01 | 1047695.30 | 28-MAY-16:00 | 39.56 | 35.58 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 929787.39 | 1334040.86 | 14-JUN-14:00 | 45.22 | 38.05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1159987.10 | 1628770.53 | 21-JUL-16:00 | 50.98 | 40.57 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1345034.09 | 1810136.21 | 30-AUG-16:10 | 54.50 | 41.62 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 656839.48 | 1199328.53 | 09-SEP-17:00 | 42.56 | 38.23 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 714971.44 | 1287082.45 | 05-OCT-15:00 | 44.29 | 37.07 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 496687.24 | 1284326.93 | 02-NOV-13:00 | 44.24 | 34.24 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 509566.25 | 1483616.55 | 13-DEC-15:00 | 48.15 | 35.43 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 689838.84 | 0.00 | ||||||
Minimum of Months | 117663.44 | 705315.63 | 32.72 | 28.68 | 0.00 | 0.00 | ||
Maximum of Months | 1345034.09 | 1810136.21 | 54.50 | 41.62 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 278758.24 | 4131603.51 | 19-JAN-15:05 | 28.39 | 24.99 | 710.74 | 100398.65 | 23-JAN-17:40 |
February | 435514.50 | 3995259.13 | 24-FEB-11:05 | 28.15 | 24.79 | 624.37 | 119126.79 | 04-FEB-08:30 |
March | 504016.89 | 4715186.98 | 28-MAR-12:05 | 29.42 | 25.94 | 1155.01 | 111517.11 | 21-MAR-10:40 |
April | 871415.56 | 5769775.57 | 28-APR-16:00 | 31.28 | 28.18 | 485.04 | 72202.92 | 03-APR-06:10 |
May | 1871467.12 | 5997086.86 | 24-MAY-10:05 | 31.68 | 28.24 | 0.00 | 0.00 | 01-MAY-00:01 |
June | 2181696.44 | 6427938.08 | 29-JUN-12:05 | 32.44 | 28.81 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2522857.57 | 6896351.22 | 05-JUL-12:05 | 33.27 | 29.52 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 2477270.42 | 6498369.56 | 07-AUG-13:00 | 32.56 | 29.31 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 2042839.53 | 6432778.84 | 18-SEP-14:05 | 32.45 | 29.17 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1602568.69 | 6739045.25 | 06-OCT-14:05 | 32.99 | 29.50 | 129.59 | 79556.16 | 27-OCT-20:40 |
November | 728192.93 | 5921844.37 | 01-NOV-13:05 | 31.55 | 27.97 | 568.03 | 110664.84 | 15-NOV-07:40 |
December | 469357.97 | 5307436.95 | 12-DEC-14:05 | 30.46 | 27.14 | 976.80 | 125346.41 | 18-DEC-09:10 |
Annual Sum or Average | 1338175.19 | 386.88 | ||||||
Minimum of Months | 278758.24 | 3995259.13 | 28.15 | 24.79 | 0.00 | 0.00 | ||
Maximum of Months | 2522857.57 | 6896351.22 | 33.27 | 29.52 | 1155.01 | 125346.41 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.47 | 5.28 |
February | 0.47 | 6.82 |
March | 0.85 | 6.01 |
April | 0.67 | 7.48 |
May | 0.46 | 7.48 |
June | 0.56 | 7.48 |
July | 0.60 | 7.48 |
August | 0.60 | 6.44 |
September | 0.91 | 7.48 |
October | 1.15 | 7.48 |
November | 1.35 | 7.25 |
December | 1.39 | 7.26 |
Annual Sum or Average | 9.46 | 7.07 |
Minimum of Months | 0.46 | 5.28 |
Maximum of Months | 1.39 | 7.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.92 | 4.09 |
February | 2.29 | 1.81 |
March | 4.96 | 1.30 |
April | 10.97 | 1.76 |
May | 5.11 | 1.28 |
June | 11.03 | 2.30 |
July | 4.45 | 2.79 |
August | 1.28 | 3.82 |
September | 5.03 | 1.18 |
October | 10.37 | 2.26 |
November | 7.42 | 1.51 |
December | 8.69 | 2.06 |
Annual Sum or Average | 73.52 | 1.98 |
Minimum of Months | 1.28 | 1.18 |
Maximum of Months | 11.03 | 4.09 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.60 | 10.62 |
February | 0.75 | 8.46 |
March | 0.72 | 9.82 |
April | 1.25 | 2.99 |
May | 3.72 | 2.34 |
June | 4.27 | 1.10 |
July | 4.63 | 2.72 |
August | 4.16 | 2.59 |
September | 3.30 | 4.76 |
October | 2.62 | 3.67 |
November | 0.88 | 7.23 |
December | 0.85 | 8.59 |
Annual Sum or Average | 27.75 | 3.57 |
Minimum of Months | 0.60 | 1.10 |
Maximum of Months | 4.63 | 10.62 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.46 | 8.35 |
February | 0.69 | 10.48 |
March | 1.21 | 11.04 |
April | 1.19 | 5.55 |
May | 5.14 | 3.98 |
June | 4.29 | 0.79 |
July | 4.84 | 1.82 |
August | 3.94 | 2.59 |
September | 3.49 | 2.50 |
October | 2.86 | 4.73 |
November | 1.13 | 9.87 |
December | 1.10 | 8.49 |
Annual Sum or Average | 30.33 | 3.85 |
Minimum of Months | 0.46 | 0.79 |
Maximum of Months | 5.14 | 11.04 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.53 | 0.18 |
February | 0.64 | 0.73 |
March | 1.08 | 0.32 |
April | 4.78 | 0.25 |
May | 4.31 | 0.18 |
June | 11.58 | 0.26 |
July | 7.36 | 0.25 |
August | 1.99 | 0.20 |
September | 3.61 | 0.14 |
October | 7.37 | 0.35 |
November | 2.86 | 0.28 |
December | 3.34 | 0.25 |
Annual Sum or Average | 49.45 | 0.26 |
Minimum of Months | 0.53 | 0.14 |
Maximum of Months | 11.58 | 0.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.78 | 0.31 |
February | 0.85 | 0.51 |
March | 1.12 | 0.24 |
April | 4.13 | 0.16 |
May | 4.09 | 0.11 |
June | 9.12 | 0.15 |
July | 6.22 | 0.15 |
August | 1.74 | 0.15 |
September | 3.45 | 0.07 |
October | 6.52 | 0.22 |
November | 3.03 | 0.23 |
December | 2.92 | 0.10 |
Annual Sum or Average | 43.96 | 0.17 |
Minimum of Months | 0.78 | 0.07 |
Maximum of Months | 9.12 | 0.51 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.69 | 0.34 |
February | 0.28 | 0.42 |
March | 1.28 | 0.31 |
April | 4.93 | 0.22 |
May | 4.19 | 0.17 |
June | 11.30 | 0.27 |
July | 7.83 | 0.25 |
August | 1.65 | 0.28 |
September | 3.76 | 0.17 |
October | 7.81 | 0.31 |
November | 3.49 | 0.28 |
December | 3.92 | 0.25 |
Annual Sum or Average | 51.15 | 0.25 |
Minimum of Months | 0.28 | 0.17 |
Maximum of Months | 11.30 | 0.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.72 | 0.19 |
February | 0.56 | 0.49 |
March | 1.88 | 0.22 |
April | 9.81 | 0.15 |
May | 3.58 | 0.19 |
June | 7.99 | 0.11 |
July | 11.17 | 0.11 |
August | 2.07 | 0.16 |
September | 3.46 | 0.15 |
October | 6.58 | 0.21 |
November | 2.90 | 0.15 |
December | 5.10 | 0.19 |
Annual Sum or Average | 55.82 | 0.16 |
Minimum of Months | 0.56 | 0.11 |
Maximum of Months | 11.17 | 0.49 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 1.12 |
February | 0.50 | 1.22 |
March | 0.58 | 1.20 |
April | 0.75 | 0.56 |
May | 2.81 | 0.44 |
June | 3.49 | 0.11 |
July | 3.56 | 0.21 |
August | 2.35 | 0.14 |
September | 2.45 | 0.16 |
October | 0.72 | 0.00 |
November | 0.35 | 0.87 |
December | 0.11 | 1.69 |
Annual Sum or Average | 17.85 | 0.31 |
Minimum of Months | 0.11 | 0.00 |
Maximum of Months | 3.56 | 1.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.64 | 0.52 |
February | 0.94 | 0.58 |
March | 0.72 | 0.73 |
April | 0.94 | 0.32 |
May | 1.97 | 0.20 |
June | 3.26 | 0.08 |
July | 2.81 | 0.05 |
August | 1.91 | 0.09 |
September | 2.72 | 0.06 |
October | 0.99 | 0.02 |
November | 0.57 | 0.63 |
December | 0.33 | 0.72 |
Annual Sum or Average | 17.81 | 0.19 |
Minimum of Months | 0.33 | 0.02 |
Maximum of Months | 3.26 | 0.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.65 | 2.97 |
February | 0.64 | 1.17 |
March | 0.72 | 1.14 |
April | 0.79 | 0.49 |
May | 2.71 | 0.50 |
June | 3.52 | 0.09 |
July | 3.42 | 0.24 |
August | 1.86 | 0.08 |
September | 2.74 | 0.15 |
October | 1.25 | 0.26 |
November | 0.53 | 0.95 |
December | 0.19 | 1.33 |
Annual Sum or Average | 19.03 | 0.42 |
Minimum of Months | 0.19 | 0.08 |
Maximum of Months | 3.52 | 2.97 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.42 | 0.62 |
February | 0.74 | 0.73 |
March | 0.79 | 0.68 |
April | 0.51 | 0.19 |
May | 1.97 | 0.28 |
June | 3.32 | 0.14 |
July | 3.28 | 0.15 |
August | 2.32 | 0.19 |
September | 2.48 | 0.18 |
October | 1.31 | 0.14 |
November | 0.71 | 0.55 |
December | 0.36 | 0.71 |
Annual Sum or Average | 18.20 | 0.26 |
Minimum of Months | 0.36 | 0.14 |
Maximum of Months | 3.32 | 0.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.31 | 1.46 |
February | 0.53 | 1.02 |
March | 0.67 | 1.48 |
April | 1.04 | 1.00 |
May | 2.97 | 0.31 |
June | 2.74 | 0.18 |
July | 4.10 | 0.11 |
August | 2.16 | 0.10 |
September | 3.74 | 0.19 |
October | 1.23 | 0.42 |
November | 0.17 | 1.69 |
December | 0.61 | 1.30 |
Annual Sum or Average | 20.25 | 0.36 |
Minimum of Months | 0.17 | 0.10 |
Maximum of Months | 4.10 | 1.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.47 | 0.80 |
February | 0.58 | 0.67 |
March | 0.79 | 0.89 |
April | 1.17 | 0.45 |
May | 2.58 | 0.07 |
June | 3.01 | 0.08 |
July | 3.96 | 0.09 |
August | 1.81 | 0.09 |
September | 3.24 | 0.11 |
October | 1.06 | 0.14 |
November | 0.26 | 1.00 |
December | 0.59 | 0.85 |
Annual Sum or Average | 19.54 | 0.21 |
Minimum of Months | 0.26 | 0.07 |
Maximum of Months | 3.96 | 1.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.33 | 1.27 |
February | 0.72 | 1.17 |
March | 0.74 | 1.35 |
April | 1.01 | 0.70 |
May | 2.42 | 0.09 |
June | 2.74 | 0.16 |
July | 3.96 | 0.11 |
August | 2.07 | 0.10 |
September | 3.54 | 0.20 |
October | 1.20 | 0.33 |
November | 0.26 | 1.20 |
December | 0.39 | 1.45 |
Annual Sum or Average | 19.39 | 0.32 |
Minimum of Months | 0.26 | 0.09 |
Maximum of Months | 3.96 | 1.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.39 | 0.78 |
February | 0.50 | 0.91 |
March | 0.72 | 0.84 |
April | 0.64 | 0.35 |
May | 2.28 | 0.14 |
June | 2.58 | 0.15 |
July | 3.51 | 0.11 |
August | 2.50 | 0.15 |
September | 2.96 | 0.17 |
October | 1.31 | 0.21 |
November | 0.38 | 0.58 |
December | 0.49 | 0.67 |
Annual Sum or Average | 18.26 | 0.24 |
Minimum of Months | 0.38 | 0.11 |
Maximum of Months | 3.51 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 20.86 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 20.86 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 20.86 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.890839E+09 | 0.00 | 0.234518E+11 | 0.147270E+11 | 0.00 | 0.00 |
February | 0.679676E+09 | 0.00 | 0.273129E+11 | 0.129634E+11 | 0.00 | 0.00 |
March | 0.592073E+09 | 0.00 | 0.367363E+11 | 0.146697E+11 | 0.00 | 0.00 |
April | 0.680720E+09 | 0.00 | 0.569252E+11 | 0.135423E+11 | 0.00 | 0.00 |
May | 0.175230E+10 | 0.00 | 0.106281E+12 | 0.150853E+11 | 0.00 | 0.00 |
June | 0.152004E+10 | 0.00 | 0.110376E+12 | 0.145692E+11 | 0.00 | 0.00 |
July | 0.166144E+10 | 0.00 | 0.120105E+12 | 0.149392E+11 | 0.00 | 0.00 |
August | 0.933318E+09 | 0.00 | 0.129906E+12 | 0.159386E+11 | 0.00 | 0.00 |
September | 0.159255E+10 | 0.00 | 0.113197E+12 | 0.152245E+11 | 0.00 | 0.00 |
October | 0.193296E+10 | 0.00 | 0.983517E+11 | 0.156647E+11 | 0.00 | 0.00 |
November | 0.174189E+10 | 0.00 | 0.552133E+11 | 0.150702E+11 | 0.00 | 0.00 |
December | 0.175518E+10 | 0.00 | 0.361559E+11 | 0.151073E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.157330E+11 | 0.00 | 0.914013E+12 | 0.177501E+12 | 0.00 | 0.00 |
Minimum of Months | 0.592073E+09 | 0.00 | 0.234518E+11 | 0.129634E+11 | 0.00 | 0.00 |
Maximum of Months | 0.193296E+10 | 0.00 | 0.129906E+12 | 0.159386E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 63271927.64 | 0.00 | 0.410183E+11 | 0.381805E+10 | 0.00 | 0.00 |
February | 21434650.04 | 0.00 | 0.582290E+11 | 0.396834E+10 | 0.00 | 0.00 |
March | 21113894.41 | 0.00 | 0.722455E+11 | 0.494720E+10 | 0.00 | 0.00 |
April | 20819933.98 | 0.00 | 0.115444E+12 | 0.577047E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.144738E+12 | 0.581491E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.156274E+12 | 0.642765E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.169299E+12 | 0.690974E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.184129E+12 | 0.799868E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.145260E+12 | 0.552775E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.136556E+12 | 0.635211E+10 | 0.00 | 0.00 |
November | 33397.57 | 0.00 | 0.876655E+11 | 0.551387E+10 | 0.00 | 0.00 |
December | 34057958.63 | 0.00 | 0.652578E+11 | 0.512318E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.160732E+09 | 0.00 | 0.137612E+13 | 0.681719E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.410183E+11 | 0.381805E+10 | 0.00 | 0.00 |
Maximum of Months | 63271927.64 | 0.00 | 0.184129E+12 | 0.799868E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.116991E+11 | 0.00 | 0.324027E+12 | 0.276664E+11 | 0.00 | 0.00 |
February | 0.542318E+10 | 0.00 | 0.456705E+12 | 0.270256E+11 | 0.00 | 0.00 |
March | 0.516858E+10 | 0.00 | 0.540026E+12 | 0.316779E+11 | 0.00 | 0.00 |
April | 33859468.44 | 0.00 | 0.837535E+12 | 0.357292E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.130905E+13 | 0.497960E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.133158E+13 | 0.512439E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.138134E+13 | 0.499415E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.143464E+13 | 0.536433E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.128848E+13 | 0.449277E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.113187E+13 | 0.474947E+11 | 0.00 | 0.00 |
November | 0.164042E+09 | 0.00 | 0.662167E+12 | 0.348368E+11 | 0.00 | 0.00 |
December | 0.717598E+10 | 0.00 | 0.463392E+12 | 0.299128E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.296648E+11 | 0.00 | 0.111608E+14 | 0.483896E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.324027E+12 | 0.270256E+11 | 0.00 | 0.00 |
Maximum of Months | 0.116991E+11 | 0.00 | 0.143464E+13 | 0.536433E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.487076E+10 | 0.00 | 0.312384E+11 | 0.254119E+10 | 0.00 | 0.00 |
February | 0.295169E+10 | 0.00 | 0.453487E+11 | 0.259657E+10 | 0.00 | 0.00 |
March | 0.220809E+10 | 0.00 | 0.552785E+11 | 0.305277E+10 | 0.00 | 0.00 |
April | 39033553.69 | 0.00 | 0.884136E+11 | 0.366989E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.144684E+12 | 0.565043E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149240E+12 | 0.595926E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.154221E+12 | 0.575775E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.158123E+12 | 0.607452E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.138698E+12 | 0.482424E+10 | 0.00 | 0.00 |
October | 44937288.62 | 0.00 | 0.120338E+12 | 0.498767E+10 | 0.00 | 0.00 |
November | 0.355732E+09 | 0.00 | 0.646515E+11 | 0.317439E+10 | 0.00 | 0.00 |
December | 0.324859E+10 | 0.00 | 0.447232E+11 | 0.273779E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.137188E+11 | 0.00 | 0.119496E+13 | 0.510265E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.312384E+11 | 0.254119E+10 | 0.00 | 0.00 |
Maximum of Months | 0.487076E+10 | 0.00 | 0.158123E+12 | 0.607452E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.128059E+12 | 0.157461E+12 | 0.00 | 12.42 |
February | 0.00 | 0.00 | 0.313374E+12 | 0.183661E+12 | 0.00 | 9.30 |
March | 0.00 | 0.00 | 0.512415E+12 | 0.269392E+12 | 0.00 | 24.89 |
April | 0.00 | 0.00 | 0.109133E+13 | 0.336334E+12 | 0.00 | 6.10 |
May | 0.00 | 0.00 | 0.418556E+12 | 0.195145E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.703029E+12 | 0.259218E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.104146E+13 | 0.341192E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.134790E+13 | 0.406034E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.408500E+12 | 0.188056E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.620948E+12 | 0.250405E+12 | 0.00 | 4.17 |
November | 0.00 | 0.00 | 0.508832E+12 | 0.248756E+12 | 0.00 | 17.53 |
December | 0.00 | 0.00 | 0.610607E+12 | 0.298884E+12 | 0.00 | 28.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.770501E+13 | 0.313454E+13 | 0.00 | 103.01 |
Minimum of Months | 0.00 | 0.00 | 0.128059E+12 | 0.157461E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.134790E+13 | 0.406034E+12 | 0.00 | 28.60 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.605611E+10 | 0.255240E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.110250E+11 | 0.332263E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.183386E+11 | 0.483616E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.242372E+11 | 0.622846E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.712223E+10 | 0.311502E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.129705E+11 | 0.446112E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.198515E+11 | 0.612440E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.263032E+11 | 0.753457E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.688731E+10 | 0.298781E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131594E+11 | 0.431327E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.180413E+11 | 0.482403E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.243253E+11 | 0.582026E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188318E+12 | 0.561201E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.605611E+10 | 0.255240E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.263032E+11 | 0.753457E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.449671E+11 | 0.219919E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.951157E+11 | 0.299492E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.166494E+12 | 0.447131E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.228835E+12 | 0.589712E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.652386E+11 | 0.290516E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.122564E+12 | 0.422422E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.188742E+12 | 0.582212E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.250398E+12 | 0.716945E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.621833E+11 | 0.276660E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.122192E+12 | 0.404515E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.165135E+12 | 0.448227E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.221732E+12 | 0.538969E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.173360E+13 | 0.523672E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.449671E+11 | 0.219919E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.250398E+12 | 0.716945E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.326272E+10 | 0.199482E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.863193E+10 | 0.286920E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.160540E+11 | 0.440744E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.227580E+11 | 0.591373E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.670453E+10 | 0.297312E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124614E+11 | 0.429762E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191010E+11 | 0.590328E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.252018E+11 | 0.724034E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.635465E+10 | 0.282364E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.121718E+11 | 0.406989E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.159441E+11 | 0.442045E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.212114E+11 | 0.527717E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169857E+12 | 0.521907E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.326272E+10 | 0.199482E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.252018E+11 | 0.724034E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147270E+11 | 0.234518E+11 | 0.890839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129634E+11 | 0.273129E+11 | 0.679676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146697E+11 | 0.367363E+11 | 0.592073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135423E+11 | 0.569252E+11 | 0.680720E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150853E+11 | 0.106281E+12 | 0.175230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145692E+11 | 0.110376E+12 | 0.152004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149392E+11 | 0.120105E+12 | 0.166144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159386E+11 | 0.129906E+12 | 0.933318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152245E+11 | 0.113197E+12 | 0.159255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156647E+11 | 0.983517E+11 | 0.193296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150702E+11 | 0.552133E+11 | 0.174189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151073E+11 | 0.361559E+11 | 0.175518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177501E+12 | 0.914013E+12 | 0.157330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129634E+11 | 0.234518E+11 | 0.592073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159386E+11 | 0.129906E+12 | 0.193296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.381805E+10 | 0.410183E+11 | 63271927.64 | 0.350900E+09 | 0.756527E+09 | 0.00 | 0.00 | 0.00 |
February | 0.396834E+10 | 0.582290E+11 | 21434650.04 | 0.111985E+09 | 0.128260E+10 | 0.00 | 0.00 | 0.00 |
March | 0.494720E+10 | 0.722455E+11 | 21113894.41 | 65921576.51 | 0.250747E+10 | 0.00 | 0.00 | 0.00 |
April | 0.577047E+10 | 0.115444E+12 | 20819933.98 | 0.00 | 0.710570E+10 | 0.00 | 0.00 | 0.00 |
May | 0.581491E+10 | 0.144738E+12 | 0.00 | 0.00 | 0.302888E+11 | 0.00 | 0.00 | 0.00 |
June | 0.642765E+10 | 0.156274E+12 | 0.00 | 0.00 | 0.371040E+11 | 0.00 | 0.00 | 0.00 |
July | 0.690974E+10 | 0.169299E+12 | 0.00 | 0.00 | 0.406229E+11 | 0.00 | 0.00 | 0.00 |
August | 0.799868E+10 | 0.184129E+12 | 0.00 | 0.00 | 0.397616E+11 | 0.00 | 0.00 | 0.00 |
September | 0.552775E+10 | 0.145260E+12 | 0.00 | 0.00 | 0.264868E+11 | 0.00 | 0.00 | 0.00 |
October | 0.635211E+10 | 0.136556E+12 | 0.00 | 0.00 | 0.224282E+11 | 0.00 | 0.00 | 0.00 |
November | 0.551387E+10 | 0.876655E+11 | 33397.57 | 0.00 | 0.539407E+10 | 0.00 | 0.00 | 0.00 |
December | 0.512318E+10 | 0.652578E+11 | 34057958.63 | 0.174367E+09 | 0.292543E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.681719E+11 | 0.137612E+13 | 0.160732E+09 | 0.703173E+09 | 0.216664E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.381805E+10 | 0.410183E+11 | 0.00 | 0.00 | 0.756527E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.799868E+10 | 0.184129E+12 | 63271927.64 | 0.350900E+09 | 0.406229E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.276664E+11 | 0.324027E+12 | 0.116991E+11 | 0.549704E+10 | 0.883308E+10 | 0.00 | 0.00 | 0.00 |
February | 0.270256E+11 | 0.456705E+12 | 0.542318E+10 | 0.240642E+10 | 0.147421E+11 | 0.00 | 0.00 | 0.00 |
March | 0.316779E+11 | 0.540026E+12 | 0.516858E+10 | 0.137817E+10 | 0.283585E+11 | 0.00 | 0.00 | 0.00 |
April | 0.357292E+11 | 0.837535E+12 | 33859468.44 | 3308757.92 | 0.705257E+11 | 0.00 | 0.00 | 0.00 |
May | 0.497960E+11 | 0.130905E+13 | 0.00 | 0.00 | 0.304970E+12 | 0.00 | 0.00 | 0.00 |
June | 0.512439E+11 | 0.133158E+13 | 0.00 | 0.00 | 0.372822E+12 | 0.00 | 0.00 | 0.00 |
July | 0.499415E+11 | 0.138134E+13 | 0.00 | 0.00 | 0.408401E+12 | 0.00 | 0.00 | 0.00 |
August | 0.536433E+11 | 0.143464E+13 | 0.00 | 0.00 | 0.399728E+12 | 0.00 | 0.00 | 0.00 |
September | 0.449277E+11 | 0.128848E+13 | 0.00 | 0.00 | 0.268514E+12 | 0.00 | 0.00 | 0.00 |
October | 0.474947E+11 | 0.113187E+13 | 0.00 | 0.00 | 0.226018E+12 | 0.00 | 0.00 | 0.00 |
November | 0.348368E+11 | 0.662167E+12 | 0.164042E+09 | 3969347.32 | 0.567562E+11 | 0.00 | 0.00 | 0.00 |
December | 0.299128E+11 | 0.463392E+12 | 0.717598E+10 | 0.396441E+10 | 0.310069E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.483896E+12 | 0.111608E+14 | 0.296648E+11 | 0.132533E+11 | 0.219067E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.270256E+11 | 0.324027E+12 | 0.00 | 0.00 | 0.883308E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.536433E+11 | 0.143464E+13 | 0.116991E+11 | 0.549704E+10 | 0.408401E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.254119E+10 | 0.312384E+11 | 0.487076E+10 | 0.966229E+09 | 0.182424E+09 | 0.00 | 0.00 | 0.00 |
February | 0.259657E+10 | 0.453487E+11 | 0.295169E+10 | 0.444642E+09 | 0.664223E+09 | 0.00 | 0.00 | 0.00 |
March | 0.305277E+10 | 0.552785E+11 | 0.220809E+10 | 0.283300E+09 | 0.181168E+10 | 0.00 | 0.00 | 0.00 |
April | 0.366989E+10 | 0.884136E+11 | 39033553.69 | 0.00 | 0.595245E+10 | 0.00 | 0.00 | 0.00 |
May | 0.565043E+10 | 0.144684E+12 | 0.00 | 0.00 | 0.290653E+11 | 0.00 | 0.00 | 0.00 |
June | 0.595926E+10 | 0.149240E+12 | 0.00 | 0.00 | 0.355154E+11 | 0.00 | 0.00 | 0.00 |
July | 0.575775E+10 | 0.154221E+12 | 0.00 | 0.00 | 0.388938E+11 | 0.00 | 0.00 | 0.00 |
August | 0.607452E+10 | 0.158123E+12 | 0.00 | 0.00 | 0.382684E+11 | 0.00 | 0.00 | 0.00 |
September | 0.482424E+10 | 0.138698E+12 | 0.00 | 0.00 | 0.256357E+11 | 0.00 | 0.00 | 0.00 |
October | 0.498767E+10 | 0.120338E+12 | 44937288.62 | 0.00 | 0.217537E+11 | 0.00 | 0.00 | 0.00 |
November | 0.317439E+10 | 0.646515E+11 | 0.355732E+09 | 1698296.67 | 0.534283E+10 | 0.00 | 0.00 | 0.00 |
December | 0.273779E+10 | 0.447232E+11 | 0.324859E+10 | 0.686308E+09 | 0.267207E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.510265E+11 | 0.119496E+13 | 0.137188E+11 | 0.238218E+10 | 0.205758E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.254119E+10 | 0.312384E+11 | 0.00 | 0.00 | 0.182424E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.607452E+10 | 0.158123E+12 | 0.487076E+10 | 0.966229E+09 | 0.388938E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.941057E+11 | 0.110115E+12 | 0.00 | 0.00 | 0.00 | 0.332358E+11 | 0.00 | 0.00 |
February | 0.849987E+11 | 0.267219E+12 | 0.00 | 0.00 | 0.00 | 0.248775E+11 | 0.00 | 0.00 |
March | 0.941057E+11 | 0.427469E+12 | 0.00 | 0.00 | 0.00 | 0.665996E+11 | 0.00 | 0.00 |
April | 0.910701E+11 | 0.897363E+12 | 0.00 | 0.00 | 0.00 | 0.163251E+11 | 0.00 | 0.00 |
May | 0.941057E+11 | 0.344348E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.910701E+11 | 0.571337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.941057E+11 | 0.837721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.941057E+11 | 0.108243E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.910701E+11 | 0.337506E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.941057E+11 | 0.511052E+12 | 0.00 | 0.00 | 0.00 | 0.111645E+11 | 0.00 | 0.00 |
November | 0.910701E+11 | 0.419630E+12 | 0.00 | 0.00 | 0.00 | 0.469207E+11 | 0.00 | 0.00 |
December | 0.941057E+11 | 0.502247E+12 | 0.00 | 0.00 | 0.00 | 0.765505E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.110802E+13 | 0.630843E+13 | 0.00 | 0.00 | 0.00 | 0.275674E+12 | 0.00 | 0.00 |
Minimum of Months | 0.849987E+11 | 0.110115E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.941057E+11 | 0.108243E+13 | 0.00 | 0.00 | 0.00 | 0.765505E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136983E+10 | 0.525418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123727E+10 | 0.950659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136983E+10 | 0.156682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132565E+10 | 0.201888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136983E+10 | 0.584323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132565E+10 | 0.105120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136983E+10 | 0.159235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136983E+10 | 0.209938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132565E+10 | 0.567343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136983E+10 | 0.108966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132565E+10 | 0.153202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136983E+10 | 0.207665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161287E+11 | 0.156547E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123727E+10 | 0.525418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136983E+10 | 0.209938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.130029E+11 | 0.389763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117445E+11 | 0.819567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130029E+11 | 0.142161E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125834E+11 | 0.190545E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130029E+11 | 0.535089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125834E+11 | 0.993186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130029E+11 | 0.151381E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130029E+11 | 0.199836E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125834E+11 | 0.512120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130029E+11 | 0.101121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125834E+11 | 0.140140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130029E+11 | 0.189169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153098E+12 | 0.143933E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117445E+11 | 0.389763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130029E+11 | 0.199836E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132344E+10 | 0.282114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119536E+10 | 0.742971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132344E+10 | 0.136970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128075E+10 | 0.189433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132344E+10 | 0.549716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128075E+10 | 0.100966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132344E+10 | 0.153191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132344E+10 | 0.201122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128075E+10 | 0.523109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132344E+10 | 0.100653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128075E+10 | 0.135205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132344E+10 | 0.180826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155824E+11 | 0.140816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119536E+10 | 0.282114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132344E+10 | 0.201122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.147270E+11 | 0.890839E+09 | 0.234518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129634E+11 | 0.679676E+09 | 0.273129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146697E+11 | 0.592073E+09 | 0.367363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135423E+11 | 0.680720E+09 | 0.569252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150853E+11 | 0.175230E+10 | 0.106281E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145692E+11 | 0.152004E+10 | 0.110376E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149392E+11 | 0.166144E+10 | 0.120105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159386E+11 | 0.933318E+09 | 0.129906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152245E+11 | 0.159255E+10 | 0.113197E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156647E+11 | 0.193296E+10 | 0.983517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150702E+11 | 0.174189E+10 | 0.552133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151073E+11 | 0.175518E+10 | 0.361559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177501E+12 | 0.157330E+11 | 0.914013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.129634E+11 | 0.592073E+09 | 0.234518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159386E+11 | 0.193296E+10 | 0.129906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.381805E+10 | 63271927.64 | 0.410183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396834E+10 | 21434650.04 | 0.582290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.494720E+10 | 21113894.41 | 0.722455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.577047E+10 | 20819933.98 | 0.115444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.581491E+10 | 0.00 | 0.144738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.642765E+10 | 0.00 | 0.156274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.690974E+10 | 0.00 | 0.169299E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.799868E+10 | 0.00 | 0.184129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.552775E+10 | 0.00 | 0.145260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.635211E+10 | 0.00 | 0.136556E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.551387E+10 | 33397.57 | 0.876655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.512318E+10 | 34057958.63 | 0.652578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.681719E+11 | 0.160732E+09 | 0.137612E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.381805E+10 | 0.00 | 0.410183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.799868E+10 | 63271927.64 | 0.184129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.276664E+11 | 0.116991E+11 | 0.324027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.270256E+11 | 0.542318E+10 | 0.456705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.316779E+11 | 0.516858E+10 | 0.540026E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.357292E+11 | 33859468.44 | 0.837535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.497960E+11 | 0.00 | 0.130905E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.512439E+11 | 0.00 | 0.133158E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.499415E+11 | 0.00 | 0.138134E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.536433E+11 | 0.00 | 0.143464E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.449277E+11 | 0.00 | 0.128848E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.474947E+11 | 0.00 | 0.113187E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348368E+11 | 0.164042E+09 | 0.662167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299128E+11 | 0.717598E+10 | 0.463392E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.483896E+12 | 0.296648E+11 | 0.111608E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.270256E+11 | 0.00 | 0.324027E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.536433E+11 | 0.116991E+11 | 0.143464E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.254119E+10 | 0.487076E+10 | 0.312384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259657E+10 | 0.295169E+10 | 0.453487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305277E+10 | 0.220809E+10 | 0.552785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.366989E+10 | 39033553.69 | 0.884136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.565043E+10 | 0.00 | 0.144684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.595926E+10 | 0.00 | 0.149240E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.575775E+10 | 0.00 | 0.154221E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.607452E+10 | 0.00 | 0.158123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.482424E+10 | 0.00 | 0.138698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.498767E+10 | 44937288.62 | 0.120338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317439E+10 | 0.355732E+09 | 0.646515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273779E+10 | 0.324859E+10 | 0.447232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.510265E+11 | 0.137188E+11 | 0.119496E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.254119E+10 | 0.00 | 0.312384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.607452E+10 | 0.487076E+10 | 0.158123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.941057E+11 | 0.00 | 0.128059E+12 | 0.00 | 0.299702E+11 | 0.00 | 0.00 | 0.00 | 0.333854E+11 | 0.00 | 0.00 | 0.00 |
February | 0.849987E+11 | 0.00 | 0.313374E+12 | 0.00 | 0.736730E+11 | 0.00 | 0.00 | 0.00 | 0.249895E+11 | 0.00 | 0.00 | 0.00 |
March | 0.941057E+11 | 0.00 | 0.512415E+12 | 0.00 | 0.108387E+12 | 0.00 | 0.00 | 0.00 | 0.668994E+11 | 0.00 | 0.00 | 0.00 |
April | 0.910701E+11 | 0.00 | 0.109133E+13 | 0.00 | 0.228866E+12 | 0.00 | 0.00 | 0.00 | 0.163986E+11 | 0.00 | 0.00 | 0.00 |
May | 0.941057E+11 | 0.00 | 0.418556E+12 | 0.00 | 0.101040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.910701E+11 | 0.00 | 0.703029E+12 | 0.00 | 0.168147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.941057E+11 | 0.00 | 0.104146E+13 | 0.00 | 0.247086E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.941057E+11 | 0.00 | 0.134790E+13 | 0.00 | 0.311928E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.910701E+11 | 0.00 | 0.408500E+12 | 0.00 | 0.969859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.941057E+11 | 0.00 | 0.620948E+12 | 0.00 | 0.145085E+12 | 0.00 | 0.00 | 0.00 | 0.112147E+11 | 0.00 | 0.00 | 0.00 |
November | 0.910701E+11 | 0.00 | 0.508832E+12 | 0.00 | 0.110554E+12 | 0.00 | 0.00 | 0.00 | 0.471320E+11 | 0.00 | 0.00 | 0.00 |
December | 0.941057E+11 | 0.00 | 0.610607E+12 | 0.00 | 0.127883E+12 | 0.00 | 0.00 | 0.00 | 0.768951E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110802E+13 | 0.00 | 0.770501E+13 | 0.00 | 0.174961E+13 | 0.00 | 0.00 | 0.00 | 0.276915E+12 | 0.00 | 0.00 | |
Minimum of Months | 0.849987E+11 | 0.00 | 0.128059E+12 | 0.00 | 0.299702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.941057E+11 | 0.00 | 0.134790E+13 | 0.00 | 0.311928E+12 | 0.00 | 0.00 | 0.00 | 0.768951E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.136983E+10 | 0.00 | 0.605611E+10 | 0.00 | 0.118257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123727E+10 | 0.00 | 0.110250E+11 | 0.00 | 0.208536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136983E+10 | 0.00 | 0.183386E+11 | 0.00 | 0.346633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132565E+10 | 0.00 | 0.242372E+11 | 0.00 | 0.490281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136983E+10 | 0.00 | 0.712223E+10 | 0.00 | 0.174519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132565E+10 | 0.00 | 0.129705E+11 | 0.00 | 0.313548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136983E+10 | 0.00 | 0.198515E+11 | 0.00 | 0.475456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136983E+10 | 0.00 | 0.263032E+11 | 0.00 | 0.616473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132565E+10 | 0.00 | 0.688731E+10 | 0.00 | 0.166216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136983E+10 | 0.00 | 0.131594E+11 | 0.00 | 0.294344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132565E+10 | 0.00 | 0.180413E+11 | 0.00 | 0.349839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136983E+10 | 0.00 | 0.243253E+11 | 0.00 | 0.445042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161287E+11 | 0.00 | 0.188318E+12 | 0.00 | 0.399915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.123727E+10 | 0.00 | 0.605611E+10 | 0.00 | 0.118257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136983E+10 | 0.00 | 0.263032E+11 | 0.00 | 0.616473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.130029E+11 | 0.00 | 0.449671E+11 | 0.00 | 0.898907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117445E+11 | 0.00 | 0.951157E+11 | 0.00 | 0.182047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130029E+11 | 0.00 | 0.166494E+12 | 0.00 | 0.317102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125834E+11 | 0.00 | 0.228835E+12 | 0.00 | 0.463878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130029E+11 | 0.00 | 0.652386E+11 | 0.00 | 0.160488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125834E+11 | 0.00 | 0.122564E+12 | 0.00 | 0.296588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.130029E+11 | 0.00 | 0.188742E+12 | 0.00 | 0.452184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130029E+11 | 0.00 | 0.250398E+12 | 0.00 | 0.586916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125834E+11 | 0.00 | 0.621833E+11 | 0.00 | 0.150825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130029E+11 | 0.00 | 0.122192E+12 | 0.00 | 0.274486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125834E+11 | 0.00 | 0.165135E+12 | 0.00 | 0.322392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130029E+11 | 0.00 | 0.221732E+12 | 0.00 | 0.408940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153098E+12 | 0.00 | 0.173360E+13 | 0.00 | 0.370574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.117445E+11 | 0.00 | 0.449671E+11 | 0.00 | 0.898907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130029E+11 | 0.00 | 0.250398E+12 | 0.00 | 0.586916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.132344E+10 | 0.00 | 0.326272E+10 | 0.00 | 0.671385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119536E+10 | 0.00 | 0.863193E+10 | 0.00 | 0.167384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132344E+10 | 0.00 | 0.160540E+11 | 0.00 | 0.308400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128075E+10 | 0.00 | 0.227580E+11 | 0.00 | 0.463299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132344E+10 | 0.00 | 0.670453E+10 | 0.00 | 0.164968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128075E+10 | 0.00 | 0.124614E+11 | 0.00 | 0.301687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132344E+10 | 0.00 | 0.191010E+11 | 0.00 | 0.457984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132344E+10 | 0.00 | 0.252018E+11 | 0.00 | 0.591690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128075E+10 | 0.00 | 0.635465E+10 | 0.00 | 0.154289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132344E+10 | 0.00 | 0.121718E+11 | 0.00 | 0.274645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128075E+10 | 0.00 | 0.159441E+11 | 0.00 | 0.313970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132344E+10 | 0.00 | 0.212114E+11 | 0.00 | 0.395373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155824E+11 | 0.00 | 0.169857E+12 | 0.00 | 0.366083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.119536E+10 | 0.00 | 0.326272E+10 | 0.00 | 0.671385E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132344E+10 | 0.00 | 0.252018E+11 | 0.00 | 0.591690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.271642E+09 | 0.147694E+10 | 0.00 | 0.155248E+09 | 0.00 | 0.00 | 0.561086E+11 | 0.00 | 0.97 |
February | 0.238005E+09 | 0.146552E+10 | 0.00 | 0.126709E+09 | 4070190.21 | 0.00 | 0.427412E+11 | 0.00 | 1.08 |
March | 0.110797E+09 | 0.310840E+10 | 0.00 | 0.121005E+09 | 5344190.88 | 0.00 | 0.452267E+11 | 0.00 | 1.05 |
April | 0.163684E+09 | 0.536907E+10 | 0.00 | 90727487.25 | 70808939.17 | 0.00 | 0.207681E+11 | 0.00 | 0.92 |
May | 640250.99 | 0.257691E+11 | 0.00 | 4886587.34 | 0.142707E+09 | 0.00 | 62002896.73 | 0.00 | 0.34 |
June | 1451506.13 | 0.311721E+11 | 0.00 | 4364641.68 | 0.203772E+09 | 0.00 | 78723082.24 | 0.00 | 0.35 |
July | 0.00 | 0.378935E+11 | 0.00 | 0.00 | 0.397196E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.385070E+11 | 0.00 | 33817.96 | 0.223731E+09 | 0.00 | 60784.06 | 0.00 | 0.34 |
September | 0.00 | 0.289733E+11 | 0.00 | 2702232.99 | 0.284626E+09 | 0.00 | 74413008.78 | 0.00 | 0.33 |
October | 51323770.04 | 0.218520E+11 | 0.00 | 61152672.99 | 0.227056E+09 | 0.00 | 0.119319E+11 | 0.00 | 0.64 |
November | 98400295.61 | 0.650982E+10 | 0.00 | 0.148045E+09 | 6620195.93 | 0.00 | 0.369136E+11 | 0.00 | 1.10 |
December | 0.173958E+09 | 0.411768E+10 | 0.00 | 0.154598E+09 | 10703016.40 | 0.00 | 0.513256E+11 | 0.00 | 0.94 |
Annual Sum or Average | 0.110990E+10 | 0.206214E+12 | 0.00 | 0.869473E+09 | 0.157663E+10 | 0.00 | 0.265231E+12 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 0.146552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.271642E+09 | 0.385070E+11 | 0.00 | 0.155248E+09 | 0.397196E+09 | 0.00 | 0.561086E+11 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.244296E+10 | 0.223073E+10 | 0.00 | 65478036.16 | 0.00 | 0.00 | 0.314539E+11 | 0.00 | 0.52 |
February | 0.188407E+10 | 0.260140E+10 | 0.00 | 58642620.09 | 34885566.55 | 0.00 | 0.195197E+11 | 0.00 | 0.52 |
March | 0.200182E+10 | 0.401809E+10 | 0.00 | 76070823.78 | 83430780.27 | 0.00 | 0.263285E+11 | 0.00 | 0.59 |
April | 0.283713E+10 | 0.641081E+10 | 0.00 | 39357233.63 | 80414007.15 | 0.00 | 0.720653E+10 | 0.00 | 0.51 |
May | 0.00 | 0.135046E+11 | 0.00 | 0.00 | 0.143344E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.139503E+11 | 0.00 | 0.00 | 0.147461E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.160351E+11 | 0.00 | 0.00 | 0.253391E+09 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 4482729.47 | 0.167319E+11 | 0.00 | 0.00 | 0.160690E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.164843E+11 | 0.00 | 0.00 | 0.284439E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
October | 0.652398E+09 | 0.107456E+11 | 0.00 | 25251000.63 | 0.176527E+09 | 0.00 | 0.570142E+10 | 0.00 | 0.37 |
November | 0.310922E+10 | 0.511503E+10 | 0.00 | 70864046.35 | 48254773.10 | 0.00 | 0.177987E+11 | 0.00 | 0.59 |
December | 0.322568E+10 | 0.444422E+10 | 0.00 | 82287811.99 | 78504372.40 | 0.00 | 0.305572E+11 | 0.00 | 0.58 |
Annual Sum or Average | 0.161578E+11 | 0.112272E+12 | 0.00 | 0.417952E+09 | 0.149134E+10 | 0.00 | 0.138566E+12 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.223073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.322568E+10 | 0.167319E+11 | 0.00 | 82287811.99 | 0.284439E+09 | 0.00 | 0.314539E+11 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106520E+12 | 0.189119E+11 | 0.00 | 0.279931E+09 | 0.318757E+10 | 0.00 | 0.150555E+12 | 0.00 | 0.41 |
February | 0.662957E+11 | 0.226855E+11 | 0.00 | 0.225384E+09 | 0.307941E+10 | 0.00 | 0.867706E+11 | 0.00 | 0.41 |
March | 0.600115E+11 | 0.338202E+11 | 0.00 | 0.327947E+09 | 0.482694E+10 | 0.00 | 0.142028E+12 | 0.00 | 0.46 |
April | 0.139230E+11 | 0.586155E+11 | 0.00 | 0.217447E+09 | 0.472324E+10 | 0.00 | 0.469156E+11 | 0.00 | 0.40 |
May | 0.00 | 0.128836E+12 | 0.00 | 0.00 | 0.532811E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.135269E+12 | 0.00 | 521343.74 | 0.454939E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.155253E+12 | 0.00 | 0.00 | 0.665224E+10 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.161188E+12 | 0.00 | 0.00 | 0.469361E+10 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.154195E+12 | 0.00 | 0.00 | 0.922455E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
October | 0.664116E+10 | 0.101982E+12 | 0.00 | 0.145968E+09 | 0.437606E+10 | 0.00 | 0.427048E+11 | 0.00 | 0.33 |
November | 0.395933E+11 | 0.473512E+11 | 0.00 | 0.322157E+09 | 0.173365E+10 | 0.00 | 0.102767E+12 | 0.00 | 0.46 |
December | 0.799430E+11 | 0.410358E+11 | 0.00 | 0.287269E+09 | 0.241694E+10 | 0.00 | 0.136466E+12 | 0.00 | 0.41 |
Annual Sum or Average | 0.372928E+12 | 0.105914E+13 | 0.00 | 0.180662E+10 | 0.547917E+11 | 0.00 | 0.708206E+12 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.189119E+11 | 0.00 | 0.00 | 0.173365E+10 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.106520E+12 | 0.161188E+12 | 0.00 | 0.327947E+09 | 0.922455E+10 | 0.00 | 0.150555E+12 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164651E+11 | 0.188701E+10 | 0.00 | 6763306.36 | 0.525096E+09 | 0.111599E+09 | 0.483277E+10 | 0.00 | 0.38 |
February | 0.881400E+10 | 0.223417E+10 | 0.00 | 9458919.88 | 0.594022E+09 | 0.122467E+09 | 0.442016E+10 | 0.00 | 0.39 |
March | 0.960106E+10 | 0.332884E+10 | 0.00 | 16533816.94 | 0.815968E+09 | 28997949.33 | 0.769008E+10 | 0.00 | 0.43 |
April | 0.199779E+10 | 0.593352E+10 | 0.00 | 16116197.97 | 0.464301E+09 | 0.00 | 0.355139E+10 | 0.00 | 0.38 |
May | 0.00 | 0.129617E+11 | 0.00 | 0.00 | 0.229985E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.135780E+11 | 0.00 | 0.00 | 0.140093E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.157579E+11 | 0.00 | 0.00 | 0.329193E+09 | 0.00 | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.161003E+11 | 0.00 | 0.00 | 0.213989E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.158741E+11 | 0.00 | 0.00 | 0.297378E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
October | 0.142124E+10 | 0.101097E+11 | 0.00 | 10392375.23 | 0.268570E+09 | 0.00 | 0.281439E+10 | 0.00 | 0.32 |
November | 0.604377E+10 | 0.430242E+10 | 0.00 | 17058997.86 | 0.606353E+09 | 0.00 | 0.587696E+10 | 0.00 | 0.42 |
December | 0.140919E+11 | 0.353563E+10 | 0.00 | 6228096.25 | 0.742110E+09 | 21755670.01 | 0.337214E+10 | 0.00 | 0.38 |
Annual Sum or Average | 0.584348E+11 | 0.105603E+12 | 0.00 | 82551710.49 | 0.522706E+10 | 0.284820E+09 | 0.325579E+11 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.188701E+10 | 0.00 | 0.00 | 0.140093E+09 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.164651E+11 | 0.161003E+11 | 0.00 | 17058997.86 | 0.815968E+09 | 0.122467E+09 | 0.769008E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.241836E+10 | 0.275734E+09 | 0.00 | 1429341.99 | 3057067.35 | 0.00 | 0.842714E+09 | 0.00 | 0.42 |
February | 0.135543E+10 | 0.332358E+09 | 0.00 | 2080864.51 | 4873945.35 | 0.00 | 0.757144E+09 | 0.00 | 0.44 |
March | 0.135542E+10 | 0.563690E+09 | 0.00 | 3702855.47 | 10674629.87 | 0.00 | 0.141046E+10 | 0.00 | 0.51 |
April | 0.528554E+09 | 0.963891E+09 | 0.00 | 2888375.27 | 10272624.11 | 0.00 | 0.571170E+09 | 0.00 | 0.53 |
May | 0.00 | 0.239888E+10 | 0.00 | 0.00 | 17955107.94 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.269651E+10 | 0.00 | 0.00 | 18470790.16 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.308177E+10 | 0.00 | 0.00 | 31739400.72 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 561499.88 | 0.301765E+10 | 0.00 | 0.00 | 20127766.47 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.268213E+10 | 0.00 | 0.00 | 35628434.58 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.228587E+09 | 0.175660E+10 | 0.00 | 1689717.66 | 22111470.46 | 0.00 | 0.459601E+09 | 0.00 | 0.41 |
November | 0.955649E+09 | 0.687008E+09 | 0.00 | 3911238.23 | 6044319.56 | 0.00 | 0.113415E+10 | 0.00 | 0.52 |
December | 0.185369E+10 | 0.563415E+09 | 0.00 | 2627725.28 | 10340502.14 | 0.00 | 0.117569E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.869625E+10 | 0.190196E+11 | 0.00 | 18330118.40 | 0.191296E+09 | 0.00 | 0.635093E+10 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.275734E+09 | 0.00 | 0.00 | 3057067.35 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.241836E+10 | 0.308177E+10 | 0.00 | 3911238.23 | 35628434.58 | 0.00 | 0.141046E+10 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109155E+10 | 0.200507E+09 | 0.00 | 3151711.11 | 4566097.81 | 0.00 | 0.144841E+10 | 0.00 | 0.50 |
February | 0.698643E+09 | 0.256755E+09 | 0.00 | 2741572.56 | 3829236.28 | 0.00 | 0.991061E+09 | 0.00 | 0.53 |
March | 0.785252E+09 | 0.436840E+09 | 0.00 | 4100051.48 | 10766568.37 | 0.00 | 0.149402E+10 | 0.00 | 0.66 |
April | 0.337148E+09 | 0.758926E+09 | 0.00 | 2810657.98 | 10677152.19 | 0.00 | 0.661698E+09 | 0.00 | 0.66 |
May | 0.00 | 0.197566E+10 | 0.00 | 0.00 | 11542695.83 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.212107E+10 | 0.00 | 0.00 | 11874209.46 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.235663E+10 | 0.00 | 0.00 | 20404123.96 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 360968.16 | 0.216180E+10 | 0.00 | 0.00 | 12939420.18 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.203301E+10 | 0.00 | 0.00 | 22904244.55 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.143637E+09 | 0.136050E+10 | 0.00 | 1589599.21 | 14214672.43 | 0.00 | 0.387507E+09 | 0.00 | 0.49 |
November | 0.577799E+09 | 0.491017E+09 | 0.00 | 3739448.74 | 6371261.74 | 0.00 | 0.109492E+10 | 0.00 | 0.61 |
December | 0.118337E+10 | 0.348289E+09 | 0.00 | 2539589.42 | 12461472.82 | 0.00 | 0.103374E+10 | 0.00 | 0.50 |
Annual Sum or Average | 0.481775E+10 | 0.145010E+11 | 0.00 | 20672630.51 | 0.142551E+09 | 0.00 | 0.711135E+10 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.200507E+09 | 0.00 | 0.00 | 3829236.28 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.118337E+10 | 0.235663E+10 | 0.00 | 4100051.48 | 22904244.55 | 0.00 | 0.149402E+10 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136411E+10 | 0.422215E+09 | 0.00 | 12355176.70 | 4583692.22 | 0.00 | 0.495572E+10 | 0.00 | 0.83 |
February | 0.868206E+09 | 0.609825E+09 | 0.00 | 7265859.07 | 4721424.04 | 0.00 | 0.265079E+10 | 0.00 | 0.75 |
March | 0.126612E+10 | 0.726437E+09 | 0.00 | 6180231.93 | 10833202.64 | 0.00 | 0.218892E+10 | 0.00 | 0.68 |
April | 0.546888E+09 | 0.106355E+10 | 0.00 | 3117395.73 | 10282226.40 | 0.00 | 0.591368E+09 | 0.00 | 0.58 |
May | 0.00 | 0.241441E+10 | 0.00 | 0.00 | 17944158.12 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.263517E+10 | 0.00 | 0.00 | 18459525.85 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.306976E+10 | 0.00 | 0.00 | 31720044.62 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 561157.45 | 0.320078E+10 | 0.00 | 0.00 | 20115491.67 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.314692E+10 | 0.00 | 0.00 | 35606706.78 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 0.189298E+09 | 0.246058E+10 | 0.00 | 3323899.71 | 20983403.54 | 0.00 | 0.721306E+09 | 0.00 | 0.60 |
November | 0.576664E+09 | 0.106047E+10 | 0.00 | 13973523.16 | 6040633.46 | 0.00 | 0.306083E+10 | 0.00 | 0.93 |
December | 0.117703E+10 | 0.878715E+09 | 0.00 | 14386421.22 | 9827341.59 | 0.00 | 0.421959E+10 | 0.00 | 0.87 |
Annual Sum or Average | 0.598888E+10 | 0.216888E+11 | 0.00 | 60602507.52 | 0.191118E+09 | 0.00 | 0.183885E+11 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.422215E+09 | 0.00 | 0.00 | 4583692.22 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.136411E+10 | 0.320078E+10 | 0.00 | 14386421.22 | 35606706.78 | 0.00 | 0.495572E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.773218E+09 | 0.319304E+09 | 0.00 | 5175424.66 | 0.00 | 0.00 | 0.237249E+10 | 0.00 | 0.68 |
February | 0.265414E+09 | 0.447896E+09 | 0.00 | 6258910.11 | 1128434.02 | 0.00 | 0.206840E+10 | 0.00 | 0.83 |
March | 0.176327E+09 | 0.729530E+09 | 0.00 | 9915015.74 | 2179260.48 | 0.00 | 0.338479E+10 | 0.00 | 1.09 |
April | 0.128340E+09 | 0.143286E+10 | 0.00 | 8993910.41 | 1160811.07 | 0.00 | 0.131281E+10 | 0.00 | 1.16 |
May | 0.00 | 0.239993E+10 | 0.00 | 0.00 | 7093517.76 | 0.00 | 0.00 | 0.00 | 0.60 |
June | 0.00 | 0.287123E+10 | 0.00 | 0.00 | 2580775.32 | 0.00 | 0.00 | 0.00 | 0.69 |
July | 0.00 | 0.346153E+10 | 0.00 | 0.00 | 3324193.42 | 0.00 | 0.00 | 0.00 | 0.65 |
August | 0.00 | 0.375849E+10 | 0.00 | 8789.02 | 2556369.27 | 0.00 | 375224.67 | 0.00 | 0.76 |
September | 0.00 | 0.277226E+10 | 0.00 | 0.00 | 11612682.19 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 49538384.25 | 0.200543E+10 | 0.00 | 3286575.71 | 10462318.78 | 0.00 | 0.728612E+09 | 0.00 | 0.74 |
November | 0.218851E+09 | 0.890156E+09 | 0.00 | 9916762.43 | 358505.34 | 0.00 | 0.238929E+10 | 0.00 | 1.06 |
December | 0.230413E+09 | 0.805240E+09 | 0.00 | 11015674.04 | 3143014.52 | 0.00 | 0.383901E+10 | 0.00 | 1.02 |
Annual Sum or Average | 0.184210E+10 | 0.218939E+11 | 0.00 | 54571062.12 | 45599882.15 | 0.00 | 0.160958E+11 | 0.00 | 0.82 |
Minimum of Months | 0.00 | 0.319304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.773218E+09 | 0.375849E+10 | 0.00 | 11015674.04 | 11612682.19 | 0.00 | 0.383901E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.253523E+11 | 0.171007E+10 | 0.00 | 408252.94 | 0.944045E+09 | 0.344996E+10 | 0.555856E+09 | 0.00 | 0.38 |
February | 0.149845E+11 | 0.226101E+10 | 0.00 | 2588853.45 | 0.880933E+09 | 0.129919E+10 | 0.113796E+10 | 0.00 | 0.38 |
March | 0.186120E+11 | 0.410209E+10 | 0.00 | 6834988.92 | 0.968555E+09 | 0.104430E+10 | 0.231106E+10 | 0.00 | 0.42 |
April | 0.446567E+10 | 0.821587E+10 | 0.00 | 12790162.31 | 0.850028E+09 | 0.00 | 0.225405E+10 | 0.00 | 0.41 |
May | 0.00 | 0.237665E+11 | 0.00 | 0.00 | 0.179020E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 20891.85 | 0.274620E+11 | 0.00 | 0.00 | 0.215966E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.318761E+11 | 0.00 | 0.00 | 0.321080E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.307247E+11 | 0.00 | 0.00 | 0.203557E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.260736E+11 | 0.00 | 0.00 | 0.365266E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.307189E+10 | 0.168084E+11 | 0.00 | 9207866.17 | 0.469790E+09 | 0.00 | 0.239240E+10 | 0.00 | 0.38 |
November | 0.125504E+11 | 0.554541E+10 | 0.00 | 10841417.37 | 0.830094E+09 | 0.00 | 0.286780E+10 | 0.00 | 0.41 |
December | 0.217336E+11 | 0.398706E+10 | 0.00 | 1444327.62 | 0.128704E+10 | 0.196131E+10 | 0.559617E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.100770E+12 | 0.182533E+12 | 0.00 | 44115868.78 | 0.751537E+10 | 0.775475E+10 | 0.120787E+11 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.171007E+10 | 0.00 | 0.00 | 0.179020E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.253523E+11 | 0.318761E+11 | 0.00 | 12790162.31 | 0.128704E+10 | 0.344996E+10 | 0.286780E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106630E+11 | 0.160305E+10 | 0.00 | 10891780.05 | 0.377127E+09 | 0.135519E+10 | 0.551752E+10 | 0.00 | 0.36 |
February | 0.612035E+10 | 0.244606E+10 | 0.00 | 13185442.36 | 0.223692E+09 | 0.495743E+09 | 0.466522E+10 | 0.00 | 0.42 |
March | 0.727728E+10 | 0.436318E+10 | 0.00 | 25094046.97 | 0.286256E+09 | 0.449086E+09 | 0.862480E+10 | 0.00 | 0.55 |
April | 0.192699E+10 | 0.835563E+10 | 0.00 | 22932214.14 | 0.185018E+09 | 0.00 | 0.535159E+10 | 0.00 | 0.61 |
May | 0.00 | 0.209687E+11 | 0.00 | 0.00 | 0.115788E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 13512.58 | 0.234673E+11 | 0.00 | 0.00 | 0.124172E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.271796E+11 | 0.00 | 0.00 | 0.207670E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.253438E+11 | 0.00 | 0.00 | 0.131658E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.209820E+11 | 0.00 | 0.00 | 0.223612E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.145473E+10 | 0.145343E+11 | 0.00 | 11935986.91 | 0.204816E+09 | 0.00 | 0.275264E+10 | 0.00 | 0.49 |
November | 0.533687E+10 | 0.486315E+10 | 0.00 | 22458935.73 | 0.332638E+09 | 0.00 | 0.639638E+10 | 0.00 | 0.50 |
December | 0.978243E+10 | 0.315874E+10 | 0.00 | 10450377.47 | 0.465799E+09 | 0.100162E+10 | 0.381271E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.425617E+11 | 0.157266E+12 | 0.00 | 0.116949E+09 | 0.287825E+10 | 0.330164E+10 | 0.371209E+11 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.160305E+10 | 0.00 | 0.00 | 0.115788E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.106630E+11 | 0.271796E+11 | 0.00 | 25094046.97 | 0.465799E+09 | 0.135519E+10 | 0.862480E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125176E+11 | 0.450641E+10 | 0.00 | 0.114309E+09 | 0.238551E+09 | 0.845641E+09 | 0.428986E+11 | 0.00 | 0.77 |
February | 0.821996E+10 | 0.680986E+10 | 0.00 | 61057878.96 | 84592592.63 | 0.365332E+09 | 0.208817E+11 | 0.00 | 0.70 |
March | 0.135903E+11 | 0.674661E+10 | 0.00 | 42169440.71 | 0.473370E+09 | 0.564786E+09 | 0.140834E+11 | 0.00 | 0.60 |
April | 0.400242E+10 | 0.994406E+10 | 0.00 | 20144167.48 | 0.514063E+09 | 0.00 | 0.351576E+10 | 0.00 | 0.48 |
May | 0.00 | 0.240879E+11 | 0.00 | 0.00 | 0.179124E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 20903.98 | 0.266278E+11 | 0.00 | 0.00 | 0.227112E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.317275E+11 | 0.00 | 0.00 | 0.321267E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.333433E+11 | 0.00 | 0.00 | 0.203675E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.321342E+11 | 0.00 | 0.00 | 0.345929E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.208419E+10 | 0.259671E+11 | 0.00 | 26719777.29 | 0.197283E+09 | 0.00 | 0.558019E+10 | 0.00 | 0.60 |
November | 0.505082E+10 | 0.111638E+11 | 0.00 | 0.127964E+09 | 0.158723E+09 | 0.00 | 0.252326E+11 | 0.00 | 0.86 |
December | 0.116032E+11 | 0.916204E+10 | 0.00 | 0.124664E+09 | 0.286609E+09 | 0.710720E+09 | 0.313988E+11 | 0.00 | 0.77 |
Annual Sum or Average | 0.570685E+11 | 0.222221E+12 | 0.00 | 0.517028E+09 | 0.323030E+10 | 0.248648E+10 | 0.143591E+12 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.450641E+10 | 0.00 | 0.00 | 84592592.63 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.135903E+11 | 0.333433E+11 | 0.00 | 0.127964E+09 | 0.514063E+09 | 0.845641E+09 | 0.428986E+11 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134371E+11 | 0.252776E+10 | 0.00 | 15193178.94 | 0.110371E+09 | 0.109426E+10 | 0.767285E+10 | 0.00 | 0.48 |
February | 0.776731E+10 | 0.339036E+10 | 0.00 | 15459825.95 | 0.106780E+09 | 0.310757E+09 | 0.556086E+10 | 0.00 | 0.52 |
March | 0.909681E+10 | 0.458655E+10 | 0.00 | 26338318.27 | 0.112135E+09 | 0.143105E+09 | 0.942464E+10 | 0.00 | 0.62 |
April | 0.163135E+10 | 0.978781E+10 | 0.00 | 30936286.51 | 95557557.53 | 0.00 | 0.453016E+10 | 0.00 | 0.68 |
May | 0.00 | 0.209135E+11 | 0.00 | 0.00 | 77968622.98 | 0.00 | 0.00 | 0.00 | 0.54 |
June | 2485.50 | 0.241959E+11 | 0.00 | 29451.32 | 40075206.60 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.278073E+11 | 0.00 | 0.00 | 71564591.13 | 0.00 | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.284557E+11 | 0.00 | 0.00 | 73825299.54 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.233394E+11 | 0.00 | 0.00 | 0.130794E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.142530E+10 | 0.159728E+11 | 0.00 | 12762143.04 | 0.105022E+09 | 0.00 | 0.305680E+10 | 0.00 | 0.56 |
November | 0.594568E+10 | 0.594332E+10 | 0.00 | 25688211.76 | 18752538.85 | 0.00 | 0.671820E+10 | 0.00 | 0.58 |
December | 0.124381E+11 | 0.483438E+10 | 0.00 | 14479677.87 | 0.107226E+09 | 0.349429E+09 | 0.511741E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.517417E+11 | 0.171755E+12 | 0.00 | 0.140887E+09 | 0.105007E+10 | 0.189755E+10 | 0.420809E+11 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 0.252776E+10 | 0.00 | 0.00 | 18752538.85 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.134371E+11 | 0.284557E+11 | 0.00 | 30936286.51 | 0.130794E+09 | 0.109426E+10 | 0.942464E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184244E+10 | 0.176483E+09 | 0.00 | 18693.53 | 0.124096E+09 | 0.832239E+09 | 7165223.39 | 0.00 | 0.38 |
February | 0.108751E+10 | 0.227387E+09 | 0.00 | 153438.10 | 0.126687E+09 | 0.449788E+09 | 96150480.98 | 0.00 | 0.38 |
March | 0.153114E+10 | 0.435106E+09 | 0.00 | 575101.27 | 0.112710E+09 | 0.324712E+09 | 0.207018E+09 | 0.00 | 0.42 |
April | 0.420883E+09 | 0.805773E+09 | 0.00 | 1329638.85 | 0.115691E+09 | 179751.36 | 0.241719E+09 | 0.00 | 0.41 |
May | 0.00 | 0.230402E+10 | 0.00 | 0.00 | 18157672.20 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.263002E+10 | 0.00 | 0.00 | 23903243.64 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.308824E+10 | 0.00 | 0.00 | 39410392.25 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.296225E+10 | 0.00 | 0.00 | 35711743.47 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.251572E+10 | 0.00 | 0.00 | 0.104463E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.290574E+09 | 0.161735E+10 | 0.00 | 807205.96 | 57736752.00 | 875801.20 | 0.206726E+09 | 0.00 | 0.37 |
November | 0.110394E+10 | 0.495534E+09 | 1897551.92 | 760795.57 | 0.139559E+09 | 56997361.02 | 0.246184E+09 | 4768.46 | 0.40 |
December | 0.153961E+10 | 0.354285E+09 | 301139.35 | 81597.06 | 0.173649E+09 | 0.621243E+09 | 36375877.28 | 3821.33 | 0.37 |
Annual Sum or Average | 0.781610E+10 | 0.176122E+11 | 2198691.27 | 3726470.33 | 0.107178E+10 | 0.228604E+10 | 0.104134E+10 | 8589.79 | 0.39 |
Minimum of Months | 0.00 | 0.176483E+09 | 0.00 | 0.00 | 18157672.20 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.184244E+10 | 0.308824E+10 | 1897551.92 | 1329638.85 | 0.173649E+09 | 0.832239E+09 | 0.246184E+09 | 4768.46 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125120E+10 | 0.191427E+09 | 0.00 | 247802.30 | 50547229.59 | 0.302096E+09 | 0.188399E+09 | 0.00 | 0.40 |
February | 0.650425E+09 | 0.272576E+09 | 0.00 | 869034.26 | 44733031.63 | 0.137675E+09 | 0.325911E+09 | 0.00 | 0.44 |
March | 0.725037E+09 | 0.495800E+09 | 0.00 | 2136970.83 | 37526629.65 | 0.155654E+09 | 0.719664E+09 | 0.00 | 0.57 |
April | 0.167334E+09 | 0.870256E+09 | 0.00 | 2346629.35 | 34754286.34 | 0.00 | 0.564630E+09 | 0.00 | 0.63 |
May | 0.00 | 0.207771E+10 | 0.00 | 0.00 | 11730759.74 | 0.00 | 0.00 | 0.00 | 0.54 |
June | 0.00 | 0.230497E+10 | 0.00 | 0.00 | 14359228.26 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.271442E+10 | 0.00 | 0.00 | 23919988.45 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.252855E+10 | 0.00 | 0.00 | 19497566.19 | 0.00 | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.214921E+10 | 0.00 | 0.00 | 32442922.57 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 0.144679E+09 | 0.145834E+10 | 0.00 | 1090826.00 | 25826867.53 | 209050.40 | 0.247355E+09 | 0.00 | 0.50 |
November | 0.508753E+09 | 0.491695E+09 | 0.00 | 1735472.98 | 54728047.07 | 18920938.71 | 0.519002E+09 | 0.00 | 0.49 |
December | 0.101168E+10 | 0.312981E+09 | 0.00 | 491312.31 | 79657741.14 | 0.273486E+09 | 0.167981E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.445911E+10 | 0.158679E+11 | 0.00 | 8918048.02 | 0.429724E+09 | 0.888040E+09 | 0.273294E+10 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.191427E+09 | 0.00 | 0.00 | 11730759.74 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.125120E+10 | 0.271442E+10 | 0.00 | 2346629.35 | 79657741.14 | 0.302096E+09 | 0.719664E+09 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.993930E+09 | 0.501776E+09 | 0.00 | 8169378.03 | 41454421.43 | 0.337189E+09 | 0.334556E+10 | 0.00 | 0.70 |
February | 0.690548E+09 | 0.723927E+09 | 0.00 | 4644247.09 | 29673509.58 | 0.165616E+09 | 0.175852E+10 | 0.00 | 0.66 |
March | 0.112808E+10 | 0.710711E+09 | 0.00 | 3664812.42 | 65623070.72 | 0.226077E+09 | 0.132054E+10 | 0.00 | 0.58 |
April | 0.358022E+09 | 0.954188E+09 | 0.00 | 2092601.89 | 95624299.84 | 0.00 | 0.400682E+09 | 0.00 | 0.48 |
May | 0.00 | 0.233299E+10 | 0.00 | 0.00 | 18125725.50 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.254929E+10 | 0.00 | 0.00 | 28936333.04 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.306767E+10 | 0.00 | 0.00 | 41973715.25 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.318996E+10 | 0.00 | 0.00 | 35648912.05 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.312832E+10 | 0.00 | 0.00 | 47467086.33 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.211407E+09 | 0.247550E+10 | 0.00 | 2326478.85 | 23133810.25 | 0.00 | 0.491602E+09 | 0.00 | 0.59 |
November | 0.508672E+09 | 0.106905E+10 | 0.00 | 10218504.37 | 46232012.40 | 9212902.12 | 0.230092E+10 | 0.00 | 0.83 |
December | 0.987143E+09 | 0.871049E+09 | 0.00 | 9288880.98 | 64007604.79 | 0.250228E+09 | 0.249000E+10 | 0.00 | 0.74 |
Annual Sum or Average | 0.487781E+10 | 0.215744E+11 | 0.00 | 40404903.63 | 0.537901E+09 | 0.988323E+09 | 0.121078E+11 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.501776E+09 | 0.00 | 0.00 | 18125725.50 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.112808E+10 | 0.318996E+10 | 0.00 | 10218504.37 | 95624299.84 | 0.337189E+09 | 0.334556E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106386E+10 | 0.266774E+09 | 0.00 | 1109534.82 | 27118380.83 | 0.293743E+09 | 0.599834E+09 | 0.00 | 0.46 |
February | 0.624120E+09 | 0.352578E+09 | 0.00 | 1265204.44 | 29376435.13 | 0.133645E+09 | 0.505774E+09 | 0.00 | 0.50 |
March | 0.795305E+09 | 0.469595E+09 | 0.00 | 2423569.37 | 30014103.93 | 0.114229E+09 | 0.902148E+09 | 0.00 | 0.61 |
April | 0.159267E+09 | 0.954571E+09 | 0.00 | 3129967.69 | 21112118.29 | 0.00 | 0.493427E+09 | 0.00 | 0.66 |
May | 0.00 | 0.197419E+10 | 0.00 | 0.00 | 7000006.47 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.00 | 0.225290E+10 | 0.00 | 0.00 | 4352747.75 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.264073E+10 | 0.00 | 0.00 | 6948733.76 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.269156E+10 | 0.00 | 0.00 | 7888705.46 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.227013E+10 | 0.00 | 0.00 | 12841103.46 | 0.00 | 0.00 | 0.00 | 0.48 |
October | 0.140957E+09 | 0.151106E+10 | 0.00 | 1146108.78 | 13131013.88 | 0.00 | 0.273188E+09 | 0.00 | 0.54 |
November | 0.567529E+09 | 0.559494E+09 | 0.00 | 2144379.12 | 22223664.14 | 8719554.55 | 0.606033E+09 | 0.00 | 0.56 |
December | 0.100096E+10 | 0.447265E+09 | 0.00 | 1107861.79 | 36828821.15 | 0.183436E+09 | 0.411040E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.435199E+10 | 0.163908E+11 | 0.00 | 12326626.02 | 0.218836E+09 | 0.733772E+09 | 0.379144E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.266774E+09 | 0.00 | 0.00 | 4352747.75 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.106386E+10 | 0.269156E+10 | 0.00 | 3129967.69 | 36828821.15 | 0.293743E+09 | 0.902148E+09 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:56:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.561369E+09 | 0.00 | 0.512103E+09 | 0.00 | 0.00 | 0.257116E+12 | 0.00 | 12.60 |
February | 0.00 | 0.990392E+09 | 0.00 | 0.621162E+09 | 0.00 | 0.00 | 0.279192E+12 | 0.00 | 16.15 |
March | 0.00 | 0.185040E+10 | 0.00 | 0.107274E+10 | 0.00 | 0.00 | 0.461604E+12 | 0.00 | 21.76 |
April | 0.00 | 0.350356E+10 | 0.00 | 0.107120E+10 | 0.00 | 0.00 | 0.153300E+12 | 0.00 | 14.39 |
May | 0.00 | 0.102400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.118852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.134581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.128268E+11 | 0.00 | 2918017.64 | 0.00 | 0.00 | 63470267.07 | 0.00 | 0.39 |
September | 0.00 | 0.104352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 0.00 | 0.797706E+10 | 0.00 | 0.275067E+09 | 0.00 | 0.00 | 0.899349E+11 | 0.00 | 6.55 |
November | 0.00 | 0.277946E+10 | 0.00 | 0.141493E+10 | 0.00 | 0.00 | 0.428700E+12 | 0.00 | 24.98 |
December | 0.00 | 0.200322E+10 | 0.00 | 0.211368E+10 | 0.00 | 0.00 | 0.645026E+12 | 0.00 | 26.99 |
Annual Sum or Average | 0.00 | 0.785107E+11 | 0.00 | 0.708381E+10 | 0.00 | 0.00 | 0.231494E+13 | 0.00 | 10.38 |
Minimum of Months | 0.00 | 0.561369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |