Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2020-06-03 19:13:00
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1587.15 | 691.87 | 691.87 |
Net Site Energy | 1587.15 | 691.87 | 691.87 |
Total Source Energy | 4852.54 | 2115.33 | 2115.33 |
Net Source Energy | 4852.54 | 2115.33 | 2115.33 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 722.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 335.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 26.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 83.52 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1503.63 | 83.52 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 722.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 335.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 163.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 26.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 83.52 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 386.34 | 36.41 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 96.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 655.47 | 36.41 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 386.34 | 36.41 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 96.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 655.47 | 36.41 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1503.633 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1503.633 | 100.00 |
Total On-Site and Utility Electric Sources | 1503.633 | 100.00 |
Total Electricity End Uses | 1503.633 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 748.37 | 100.00 |
Air to Air Heat Recovery for Heating | 0.01 | 0.00 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 748.38 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 243.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.5670 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 15.5000 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 15.5000 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 15.5000 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.6875 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 14.1559 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 14.1559 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-MAY-15:30 | 10-JAN-12:20 | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 59553.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26716.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 11483.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1406.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4789.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 109899.86 | 4789.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 59553.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26716.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 11483.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 1406.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 4789.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2288.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1064.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 191.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 615.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 517.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 84.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 90.54 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4762.01 | 90.54 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 997.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 463.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 225.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 36.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.47 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2075.86 | 39.47 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 997.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 463.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 225.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 36.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 39.47 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2075.86 | 39.47 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 2.42 |
CORE_RETAIL DIRECT AIR | 7.92 |
POINT_OF_SALE DIRECT AIR | 1.18 |
FRONT_RETAIL DIRECT AIR | 1.02 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.014172 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 0.014172 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 417.46 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 55999.25 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 183353.53 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 27270.14 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 23591.80 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 2.42 | 2.42 | 2.42 | 2.42 | 2.42 | 2.42 | 1.00 | 1.00 | 2.42 |
PSZ-AC:2 | 7.92 | 7.92 | 7.92 | 7.92 | 8.11 | 8.11 | 1.00 | 0.977045 | 8.11 |
PSZ-AC:3 | 1.18 | 1.18 | 1.18 | 1.18 | 1.21 | 1.21 | 1.00 | 0.982393 | 1.21 |
PSZ-AC:4 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.02 | 1.00 | 1.00 | 1.02 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 2.42 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 8.11 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.21 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.02 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 2.42 | 2.42 | 2.42 | 1.59 | 49481.12 | 55999.25 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.11 | 8.11 | 8.11 | 5.35 | 201406.30 | 183353.53 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.21 | 1.21 | 1.21 | 0.795526 | 26499.57 | 27270.14 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 0.675255 | 23491.97 | 23591.80 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 2.42 | 1.21 | 1.61 | 46386.54 | 49481.12 | 24740.56 | 24740.56 | 0.728068 | 0.728070 | 0.728070 | 0.728070 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 8.11 | 4.06 | 5.41 | 193183.95 | 201406.30 | 100703.15 | 100703.15 | 0.676083 | 0.676080 | 0.676080 | 0.676080 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.21 | 0.602670 | 0.803560 | 24984.97 | 26499.57 | 13249.78 | 13249.78 | 0.707823 | 0.707820 | 0.707820 | 0.707820 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.02 | 0.511555 | 0.682073 | 22223.62 | 23491.97 | 11745.99 | 11745.99 | 0.696054 | 0.696060 | 0.696060 | 0.696060 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.42 | 2584.45 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.11 | 13664.10 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.21 | 1334.50 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1132.75 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PSZ-AC:2 OA HEAT RECOVERY | 1.89 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.567 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.637 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 15.500 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.730 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 15.500 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 37.020 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 15.500 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.730 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.688 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.688 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2874.639 | 7.567 | 46.863 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2874.639 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 24807.535 | 15.500 | 95.992 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24807.535 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2337.560 | 15.500 | 95.992 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2337.560 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2337.560 | 15.500 | 95.992 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2337.560 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 116.250 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 116.250 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9750000 | 3.9750000 | 3.9750000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
25 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
26 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
27 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
28 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
29 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
30 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
31 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
32 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
33 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 30 | 1 | VerySmooth | 3.241 | 0.252 | 0.162 | 0.276 |
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 31 | 1 | VerySmooth | 4.262 | 0.355 | 0.203 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 27414.79411 | 32897.75294 | 2.01272 | 2.41526 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 34.77500 | 1.71339E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 6134.12227 | 7360.94673 | 0.25755 | 0.30906 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 93516.68526 | 112220.02231 | 6.60371 | 7.92445 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71339E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 19807.38182 | 23768.85818 | 0.82867 | 1.89021 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 13796.02358 | 16555.22830 | 0.98677 | 1.18412 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71339E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 2857.38358 | 3428.86030 | 0.11986 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 11613.05133 | 13935.66160 | 0.85260 | 1.02311 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71339E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 2857.38358 | 3428.86030 | 0.11986 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20000 | 1.71339E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10000 | 1.47983E-002 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 35457.24 | 2.41526 | 2.41526 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 7362.84 | 0.30906 | 0.30906 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 132153.05 | 8.11063 | 8.11063 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 45493.45 | 1.89021 | 1.89021 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 18547.37 | 1.20534 | 1.20534 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 4286.75 | 0.17811 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 16156.96 | 1.02311 | 1.02311 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 4286.75 | 0.17811 | 0.17811 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.41526 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 7.92445 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.18412 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02311 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.41723E-002 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 1.41723E-002 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 417.45501 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.41526 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.41526 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.41526 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.41526 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.41526 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.41526 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 7.92445 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 7.92445 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 7.92445 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 7.92445 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.11063 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.11063 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.97705 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.18412 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.18412 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.18412 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.18412 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.20534 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.20534 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 0.98239 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02311 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02311 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02311 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02311 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02311 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02311 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 2.41526 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.11063 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.20534 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.02311 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.41526 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.41526 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.41526 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.41526 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.59407 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.41526 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.20763 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.61017 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 46386.53601 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 49481.12000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 24740.56000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 24740.56000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72807 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72807 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72807 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72807 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 49481.12000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 55999.24711 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.41526 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2584.44746 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 55999.24711 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.11063 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | HeatExchanger:AirToAir:SensibleAndLatent | PSZ-AC:2 OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.89021 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.11063 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.11063 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.11063 |
74 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.35302 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.11063 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.05532 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.40709 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 193183.95332 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 201406.30000 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 100703.15000 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 100703.15000 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67608 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67608 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67608 |
85 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67608 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 201406.30000 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 183353.52754 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
89 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.11063 |
91 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 13664.10018 |
92 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 183353.52754 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.20534 |
94 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.20534 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.20534 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.20534 |
98 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.79553 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.20534 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.60267 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.80356 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 24984.96889 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 26499.57000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 13249.78500 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 13249.78500 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70782 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70782 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70782 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70782 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 26499.57000 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27270.14011 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
113 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.20534 |
115 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1334.50457 |
116 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 27270.14011 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02311 |
118 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02311 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02311 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02311 |
122 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67526 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02311 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51156 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.68207 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 22223.62285 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 23491.97000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 11745.98500 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 11745.98500 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.69605 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.69606 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.69606 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.69606 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23491.97000 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 23591.79996 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
137 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02311 |
139 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1132.74970 |
140 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 23591.79996 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 47582.3 | 11.41 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 195007.7 | 13.51 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 25550.8 | 123.01 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 22686.0 | 151.33 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 0.1312884055 | 0.2071621465 | Pass | Pass | 0.2654438707 | 0.6619108237 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.1050106490E-002 | 0.1439784303 | Pass | Pass | 7.5694406833E-002 | 0.3445678479 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 0.1760559690 | 0.2721944433 | Pass | Pass | 0.4117877666 | 0.8147035930 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 0.1516408425 | 0.2348450600 | Pass | Pass | 0.4211684715 | 0.8437926540 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 7.2271605198E-002 | 0.1013576200 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.57_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.241 | 0.252 | 0.276 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.57_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.241 | 0.252 | 0.276 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 3.241 | 0.252 | 0.276 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 3.466 | 0.275 | 0.303 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 3.466 | 0.275 | 0.303 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.5670 | 379.89 | 2874.64 | LightsWired | BLDG_LIGHT_BACK_SCH | 55.08 | 168.00 | 54.34 | 0.0000 | Y | 29.32 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 15.5000 | 1600.48 | 24807.53 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 52.91 | 0.0000 | Y | 246.40 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 15.5000 | 150.81 | 2337.56 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.95 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 15.5000 | 150.81 | 2337.56 | LightsWired | BLDG_LIGHT_FRONT_SCH | 67.15 | 168.00 | 66.22 | 0.0000 | Y | 29.06 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.6875 | 12.00 | 116.25 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 56.76 | 0.0000 | Y | 1.24 |
Interior Lighting Total | 14.1559 | 2293.99 | 32473.54 | 335.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24807.53 | 6201.88 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24807.53 | 6201.88 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 41.93 | 41.93 | 2.49 | |
EXTERIOR_LIGHTS_B | 4328.00 | AstronomicalClock | - | 83.83 | 71.26 | 57.89 | |
Exterior Lighting Total | 4644.30 | 60.38 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 49481.12 | 36025.72 | 13455.40 | 0.73 | 3.73 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 201406.30 | 136166.77 | 65239.53 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 26499.57 | 18756.93 | 7742.64 | 0.71 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 23491.97 | 16351.82 | 7140.15 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 47582.3 | 11.41 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 195007.7 | 13.51 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 25550.8 | 123.01 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 22686.0 | 151.33 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 417.46 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 55999.25 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 183353.53 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 27270.14 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 23591.80 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.01 | 15.87 | 1120.11 | 1.00 | 15.42 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.42 | 2584.45 | 1070.05 | 1.00 | 1.29 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 1018.41 | 8.11 | 13664.10 | 1684.71 | 1.00 | 1.15 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.21 | 1334.50 | 1107.16 | 1.00 | 1.36 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1132.75 | 1107.16 | 1.00 | 1.40 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 27414.79 | 32897.75 | 86.60 | 2.013 | 2.415 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 23.89 | 23.89 | 0.00906 | 34.78 | 0.01713 | 0.232 | 0.00 |
CORE_RETAIL | 93516.69 | 112220.02 | 70.12 | 6.604 | 7.924 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 23.89 | 23.89 | 0.00956 | 28.91 | 0.01713 | 1.890 | 0.00 |
POINT_OF_SALE | 13796.02 | 16555.23 | 109.78 | 0.987 | 1.184 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 23.89 | 23.89 | 0.00901 | 28.91 | 0.01713 | 0.178 | 0.00 |
FRONT_RETAIL | 11613.05 | 13935.66 | 92.41 | 0.853 | 1.023 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 23.89 | 23.89 | 0.00903 | 35.20 | 0.01713 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 34.71 | 100.00 | 0.00001 | 35.20 | 0.01713 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 6134.12 | 7360.95 | 19.38 | 0.258 | 0.309 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01001 | 20.10 | 0.01480 | 0.232 | 0.00 |
CORE_RETAIL | 19807.38 | 23768.86 | 14.85 | 0.829 | 1.890 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.00857 | 20.10 | 0.01480 | 1.890 | 0.00 |
POINT_OF_SALE | 2857.38 | 3428.86 | 22.74 | 0.120 | 0.178 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01000 | 20.10 | 0.01480 | 0.178 | 0.00 |
FRONT_RETAIL | 2857.38 | 3428.86 | 22.74 | 0.120 | 0.178 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.11 | 21.11 | 0.01000 | 20.10 | 0.01480 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 0.00 | 16.00 | 0.00800 | 20.10 | 0.01480 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 2.42 | 2.42 | 0.31 | 0.31 | 2.4153 | 2.4153 | 2.4153 | 1.0000 | 1.0000 |
PSZ-AC:2 | 8.11 | 8.11 | 1.89 | 1.89 | 8.1106 | 7.9245 | 8.1106 | 0.9770 | 1.0000 |
PSZ-AC:3 | 1.21 | 1.21 | 0.18 | 0.18 | 1.2053 | 1.1841 | 1.2053 | 0.9824 | 1.0000 |
PSZ-AC:4 | 1.02 | 1.02 | 0.18 | 0.18 | 1.0231 | 1.0231 | 1.0231 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 417.455 | 417.455 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 417.46 | 417.46 | 0.014172 | 16.00 | 12.90 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 16.00 | 0.00800000 | 70.7169 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 24740.560 | 0.000 | 2.415260 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 24740.56 | 19797.20 | 2.415260 | 24.95 | 17.81 | 0.00983640 | 12.80 | 12.09 | 0.00850000 | 34.95 | 0.01713393 | 25.74 | 9.5876 | 23.89 | 0.00906123 | 49.0402 | 27390.64 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 55999.247 | 55999.247 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 55999.25 | 55999.25 | 2.415265 | 20.30 | 19.26 | 0.01359676 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 9.5876 | 21.11 | 0.01000638 | 64.0129 | 6134.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 100703.150 | 0.000 | 8.110630 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | 100703.15 | 70620.28 | 8.110630 | 26.52 | 19.29 | 0.01104558 | 12.80 | 12.09 | 0.00850000 | 34.99 | 0.01713393 | 25.75 | 23.3054 | 23.89 | 0.00956364 | 51.7247 | 90379.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 183353.528 | 183353.528 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 183353.53 | 183353.53 | 8.110632 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 23.3054 | 21.11 | 0.00857124 | 54.9602 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 13249.785 | 0.000 | 1.205340 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 13249.78 | 10210.11 | 1.205340 | 25.57 | 18.29 | 0.01016611 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 14.7768 | 23.89 | 0.00900935 | 48.7647 | 13636.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 27270.140 | 27270.140 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 18:30:00 | 27270.14 | 27270.14 | 1.205342 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 14.7768 | 21.11 | 0.00999626 | 63.9482 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 11745.985 | 0.000 | 1.023110 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 11745.99 | 8765.62 | 1.023110 | 25.86 | 18.60 | 0.01044218 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01713393 | 25.80 | 17.4087 | 23.89 | 0.00903168 | 48.8824 | 11613.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 23591.800 | 23591.800 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 18:30:00 | 23591.80 | 23591.80 | 1.023114 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.14 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.4087 | 21.11 | 0.00999626 | 63.9482 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 417.455 | 417.455 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.014172 | 0.01705772 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 417.46 | 417.46 | 1.0000 | 0.01705772 | 0.014172 | 16.00 | 12.90 | 0.00800000 | 36322.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 417.46 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 16.00 | 0.00800000 | 16.00 | 0.00800000 | 70.7169 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24740.560 | 0.000 | 2.415260 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.1254 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:50:00 | 24740.56 | 19797.20 | 1.0000 | 2.90699482 | 2.415260 | 24.95 | 17.81 | 0.00983640 | 50126.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24740.56 | 34.95 | 0.01713393 | 25.74 | 0.23156651 | 9.5876 | 23.89 | 0.00906180 | 23.89 | 0.00906123 | 49.0402 | 27390.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 55999.247 | 55999.247 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.415265 | 2.90700054 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 55999.25 | 55999.25 | 1.0000 | 2.90700054 | 2.415265 | 20.30 | 19.26 | 0.01359676 | 54918.4 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55999.25 | 20.10 | 0.01479830 | 20.10 | 0.23156651 | 9.5876 | 20.91 | 0.01000638 | 21.11 | 0.01000638 | 64.0129 | 6134.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 100703.150 | 0.000 | 8.110630 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.3732 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | 100703.15 | 70620.28 | 1.0000 | 9.76191357 | 8.110630 | 26.52 | 19.29 | 0.01104558 | 54820.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 100703.15 | 34.99 | 0.01713393 | 25.75 | 1.89021192 | 23.3054 | 23.89 | 0.00915036 | 23.89 | 0.00956364 | 51.7247 | 90379.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 183353.528 | 183353.528 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.110632 | 9.76191576 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 183353.53 | 183353.53 | 1.0000 | 9.76191576 | 8.110632 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 183353.53 | 20.10 | 0.01479830 | 20.10 | 1.89021192 | 23.3054 | 21.11 | 0.00000000 | 21.11 | 0.00857124 | 54.9602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 13249.785 | 0.000 | 1.205340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7383 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:00:00 | 13249.78 | 10210.11 | 1.0000 | 1.45074118 | 1.205340 | 25.57 | 18.29 | 0.01016611 | 51596.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13249.78 | 35.20 | 0.01713393 | 25.80 | 0.17811053 | 14.7768 | 23.89 | 0.00895328 | 23.89 | 0.00900935 | 48.7647 | 13636.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27270.140 | 27270.140 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.205342 | 1.45074320 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 18:30:00 | 27270.14 | 27270.14 | 1.0000 | 1.45074320 | 1.205342 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27270.14 | 20.10 | 0.01479830 | 20.10 | 0.17811053 | 14.7768 | 21.11 | 0.00000000 | 21.11 | 0.00999626 | 63.9482 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 11745.985 | 0.000 | 1.023110 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2515 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 11745.99 | 8765.62 | 1.0000 | 1.23141006 | 1.023110 | 25.86 | 18.60 | 0.01044218 | 52599.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11745.99 | 35.20 | 0.01713393 | 25.80 | 0.17811053 | 17.4087 | 23.89 | 0.00903168 | 23.89 | 0.00903168 | 48.8824 | 11613.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23591.800 | 23591.800 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.023114 | 1.23141498 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 18:30:00 | 23591.80 | 23591.80 | 1.0000 | 1.23141498 | 1.023114 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23591.80 | 20.10 | 0.01479830 | 20.10 | 0.17811053 | 17.4087 | 21.11 | 0.00000000 | 21.11 | 0.00999626 | 63.9482 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 4905.50 | 37.17 | 37.17 |
CORE_RETAIL | 4913.00 | 10.33 | 10.33 |
POINT_OF_SALE | 4913.00 | 69.67 | 69.67 |
FRONT_RETAIL | 4913.00 | 243.50 | 243.50 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 4913.00 | 243.83 | 243.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 0.00 | 621.83 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.00 | 795.17 | 0.00 | 0.00 |
FRONT_RETAIL | 0.00 | 743.50 | 0.00 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 795.67 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.372 | 0.020 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.719 | 0.004 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.720 | 0.021 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.720 | 0.021 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.364 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.705 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.705 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.705 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1503.63 | 3188.54 | 08-JAN-08:00 | 109899.86 | 06-MAY-15:30 |
Electricity:Building | 530.26 | 2878.44 | 05-FEB-08:50 | 39317.46 | 02-JAN-16:10 |
Electricity:Zone:BACK_SPACE | 79.09 | 597.55 | 01-JAN-00:10 | 4774.71 | 02-JAN-09:10 |
InteriorLights:Electricity | 335.97 | 1106.85 | 05-FEB-08:50 | 28576.57 | 02-JAN-16:10 |
InteriorLights:Electricity:Zone:BACK_SPACE | 29.32 | 143.73 | 01-JAN-00:10 | 2023.29 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 335.97 | 1106.85 | 05-FEB-08:50 | 28576.57 | 02-JAN-16:10 |
Electricity:Zone:CORE_RETAIL | 330.32 | 1488.80 | 05-FEB-08:50 | 26966.36 | 02-JAN-16:10 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 246.40 | 723.55 | 05-FEB-08:50 | 22326.78 | 02-JAN-16:10 |
Electricity:Zone:POINT_OF_SALE | 82.64 | 597.30 | 01-JAN-00:10 | 5016.52 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 29.95 | 116.88 | 01-JAN-00:10 | 2103.80 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 36.97 | 188.99 | 01-JAN-00:10 | 2474.08 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 29.06 | 116.88 | 01-JAN-00:10 | 2036.90 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.77 | 453.82 | 01-JAN-00:10 | 2751.42 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 83.93 | 765.25 | 01-JAN-00:10 | 4639.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.69 | 480.42 | 01-JAN-00:10 | 2912.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.91 | 72.11 | 01-JAN-00:10 | 437.18 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1503.63 | 3188.54 | 08-JAN-08:00 | 109899.86 | 06-MAY-15:30 |
ElectricityPurchased:Plant | 1503.63 | 3188.54 | 08-JAN-08:00 | 109899.86 | 06-MAY-15:30 |
Cogeneration:ElectricityPurchased | 1503.63 | 3188.54 | 08-JAN-08:00 | 109899.86 | 06-MAY-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1503.63 | 3188.54 | 08-JAN-08:00 | 109899.86 | 06-MAY-15:30 |
ElectricityNet:Plant | 1503.63 | 3188.54 | 08-JAN-08:00 | 109899.86 | 06-MAY-15:30 |
Cogeneration:ElectricityNet | 1503.63 | 3188.54 | 08-JAN-08:00 | 109899.86 | 06-MAY-15:30 |
Electricity:HVAC | 912.99 | 0.00 | 01-JAN-19:40 | 73180.68 | 06-MAY-15:00 |
Fans:Electricity | 163.52 | 0.00 | 01-JAN-19:40 | 11584.80 | 13-JUN-15:00 |
General:Fans:Electricity | 163.52 | 0.00 | 01-JAN-19:40 | 11584.80 | 13-JUN-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 722.75 | 0.00 | 01-JAN-19:40 | 60306.66 | 06-MAY-15:00 |
ExteriorLights:Electricity | 60.38 | 0.00 | 01-JAN-06:20 | 4644.30 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.38 | 0.00 | 01-JAN-06:20 | 4644.30 | 01-JAN-06:10 |
HeatRecovery:Electricity | 26.72 | 0.00 | 01-JAN-00:10 | 1406.23 | 01-JAN-08:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 83.52 | 1860.00 | 16-JAN-08:10 | 4789.88 | 10-JAN-12:20 |
Gas:Plant | 83.52 | 1860.00 | 16-JAN-08:10 | 4789.88 | 10-JAN-12:20 |
WaterSystems:Gas | 83.52 | 1860.00 | 16-JAN-08:10 | 4789.88 | 10-JAN-12:20 |
Water Heater:WaterSystems:Gas | 83.52 | 1860.00 | 16-JAN-08:10 | 4789.88 | 10-JAN-12:20 |
Gas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Gas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 4967.27 | 0.00 | 01-JAN-19:40 | 385321.69 | 13-JUN-15:00 |
EnergyTransfer:Building | 1491.09 | 0.00 | 01-JAN-19:40 | 117043.45 | 06-MAY-15:30 |
EnergyTransfer:Zone:BACK_SPACE | 330.64 | 0.00 | 01-JAN-00:10 | 26273.47 | 13-JUN-16:00 |
Heating:EnergyTransfer | 2.62 | 0.00 | 01-JAN-00:10 | 8177.09 | 21-MAY-07:20 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 0.02 | 0.00 | 01-JAN-00:10 | 997.44 | 20-OCT-05:10 |
Cooling:EnergyTransfer | 1488.47 | 0.00 | 01-JAN-19:40 | 117043.45 | 06-MAY-15:30 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 330.62 | 0.00 | 01-JAN-00:10 | 26273.47 | 13-JUN-16:00 |
EnergyTransfer:Zone:CORE_RETAIL | 801.90 | 0.00 | 01-JAN-00:10 | 68596.10 | 06-MAY-15:30 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 2.59 | 0.00 | 01-JAN-00:10 | 8177.09 | 21-MAY-07:20 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 799.31 | 0.00 | 01-JAN-00:10 | 68596.10 | 06-MAY-15:30 |
EnergyTransfer:Zone:POINT_OF_SALE | 197.16 | 0.00 | 01-JAN-00:40 | 14230.24 | 07-DEC-15:30 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.01 | 0.00 | 01-JAN-00:10 | 527.17 | 14-MAY-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 197.15 | 0.00 | 01-JAN-00:40 | 14230.24 | 07-DEC-15:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 161.39 | 0.00 | 01-JAN-00:40 | 12372.88 | 07-DEC-15:20 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.01 | 0.00 | 01-JAN-00:10 | 467.34 | 14-MAY-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 161.38 | 0.00 | 01-JAN-00:40 | 12372.88 | 07-DEC-15:20 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 3476.18 | 0.00 | 01-JAN-19:40 | 271771.99 | 13-JUN-15:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 2727.80 | 0.00 | 01-JAN-19:40 | 208568.50 | 13-JUN-15:00 |
HeatRecoveryForHeating:EnergyTransfer | 0.01 | 0.00 | 01-JAN-00:10 | 2371.87 | 23-JAN-06:10 |
HeatRecoveryForCooling:EnergyTransfer | 748.37 | 0.00 | 01-JAN-00:10 | 71767.62 | 15-JUN-10:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 0.017 | -330.617 | 0.000 | 0.000 | 36.671 | 29.322 | 49.772 | 0.000 | 0.000 | 2.641 | 212.295 | 0.000 | 0.000 | 0.000 | -0.100 | -0.000 |
CORE_RETAIL | 0.000 | 0.000 | 2.590 | -799.295 | 0.000 | 0.000 | 154.449 | 246.397 | 83.927 | 53.549 | 0.000 | 1.487 | 263.087 | 0.000 | -5.749 | 0.000 | -0.442 | -0.002 |
POINT_OF_SALE | 0.000 | 0.000 | 0.008 | -197.146 | 0.000 | 0.000 | 14.558 | 29.949 | 52.689 | 29.007 | 0.000 | 1.136 | 72.303 | 0.000 | -2.457 | 0.000 | -0.048 | -0.000 |
FRONT_RETAIL | 0.000 | 0.000 | 0.007 | -161.380 | 0.000 | 0.000 | 14.558 | 29.059 | 7.908 | 28.860 | 0.000 | 1.142 | 82.235 | 0.000 | -2.343 | 0.000 | -0.046 | -0.000 |
FRONT_ENTRY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.239 | 0.000 | 4.810 | 0.000 | 2.350 | 0.000 | 0.000 | -1.067 | 0.000 | -1.382 | -5.950 |
Total Facility | 0.000 | 0.000 | 2.622 | -1488.439 | 0.000 | 0.000 | 220.236 | 335.966 | 194.297 | 116.226 | 0.000 | 8.755 | 629.921 | 0.000 | -11.616 | 0.000 | -2.017 | -5.953 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 20-JUL-02:63 | 0.00 | 0.00 | 0.00 | -37251.20 | 0.00 | 0.00 | 0.00 | 143.73 | 605.09 | 0.00 | 0.00 | 0.00 | 36502.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 23-FEB-06:03 | 0.00 | 0.00 | 0.00 | -149970.04 | 0.00 | 0.00 | 0.00 | 1240.38 | 1020.33 | 0.00 | 0.00 | 0.00 | 148467.57 | 0.00 | -744.01 | 0.00 | -14.23 | 0.00 |
POINT_OF_SALE | 20-DEC-21:06 | 0.00 | 0.00 | 0.00 | -20399.43 | 0.00 | 0.00 | 0.00 | 467.51 | 640.56 | 0.00 | 0.00 | 0.00 | 19839.59 | 0.00 | -504.01 | 0.00 | -44.22 | 0.00 |
FRONT_RETAIL | 20-DEC-21:06 | 0.00 | 0.00 | 0.00 | -17534.46 | 0.00 | 0.00 | 0.00 | 467.51 | 96.14 | 0.00 | 0.00 | 0.00 | 17499.43 | 0.00 | -485.77 | 0.00 | -42.86 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-MAY-07:02 | 0.00 | 0.00 | 0.00 | -193138.97 | 0.00 | 0.00 | 0.00 | 1416.95 | 1771.59 | 3594.55 | 0.00 | 357.15 | 185998.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 30-APR-07:04 | 0.00 | 0.00 | 2363.73 | 0.00 | 0.00 | 0.00 | 0.00 | 143.73 | 453.82 | 0.00 | 0.00 | 42.40 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3003.68 |
CORE_RETAIL | 28-MAY-07:05 | 0.00 | 0.00 | 11406.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1033.65 | 765.25 | 1873.64 | 0.00 | 37.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15116.34 |
POINT_OF_SALE | 14-MAY-07:07 | 0.00 | 0.00 | 1582.03 | 0.00 | 0.00 | 0.00 | 0.00 | 116.88 | 480.42 | 745.26 | 0.00 | 14.98 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2939.57 |
FRONT_RETAIL | 30-APR-07:04 | 0.00 | 0.00 | 1453.87 | 0.00 | 0.00 | 0.00 | 0.00 | 116.88 | 72.11 | 769.31 | 0.00 | 18.54 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2430.71 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-MAY-07:07 | 0.00 | 0.00 | 14360.72 | 0.00 | 0.00 | 0.00 | 0.00 | 1416.95 | 1771.59 | 3158.27 | 0.00 | 116.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20824.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.4153 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.4153 | 0.0959 | 1.0000 | 0.2316 | 0.0959 | ||
PSZ-AC:2 | 7.9245 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.1106 | 0.2331 | 1.0000 | 1.8902 | 0.2331 | ||
PSZ-AC:3 | 1.1841 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.2053 | 0.1478 | 1.0000 | 0.1781 | 0.1478 | ||
PSZ-AC:4 | 1.0231 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0231 | 0.1741 | 1.0000 | 0.1781 | 0.1741 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.4153 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.4153 | 1.0000 | 1.0000 | 0.2316 | 0.0959 | ||
PSZ-AC:2 | 7.9245 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 7.9245 | 1.0000 | 1.0000 | 1.8902 | 0.2385 | ||
PSZ-AC:3 | 1.1841 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.1841 | 1.0000 | 1.0000 | 0.1781 | 0.1504 | ||
PSZ-AC:4 | 1.0231 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.0231 | 1.0000 | 1.0000 | 0.1781 | 0.1741 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.4153 | 2.4153 | 2.4153 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.9245 | 7.9245 | 7.9245 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1841 | 1.1841 | 1.1841 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0231 | 1.0231 | 1.0231 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.4153 | 2.4153 | 2.4153 | 2.4153 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.9245 | 8.1106 | 7.9245 | 7.9245 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1841 | 1.2053 | 1.1841 | 1.1841 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0231 | 1.0231 | 1.0231 | 1.0231 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.4153 | 2.4153 | 2.4153 | 0.2316 | 0.7493 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 7.9245 | 7.9245 | 7.9245 | 1.8902 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.1841 | 1.1841 | 1.1841 | 0.1781 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.0231 | 1.0231 | 1.0231 | 0.1781 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.4153 | 2.4153 | 2.4153 | 2.4153 | 0.2316 | 1.0000 |
PSZ-AC:2 | 7.9245 | 7.9245 | 7.9245 | 7.9245 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.1841 | 1.1841 | 1.1841 | 1.1841 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.0231 | 1.0231 | 1.0231 | 1.0231 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:13:00
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 2293.99 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 722.75 | 60306.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 335.97 | 28576.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.38 | 4644.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.30 | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 163.52 | 11584.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 26.72 | 1406.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 83.52 | 4789.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.30 | 1503.63 |
Natural Gas | 0.00 | 83.52 |
Additional | 0.00 | 0.00 |
Total | 194.30 | 1587.15 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 146.45 |
Space Heating | 0.00 |
Space Cooling | 315.06 |
Fans (All) | 71.28 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.70 |
Miscellaneous (All) | 655.47 |
Subtotal | 655.47 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 36.41 |
Miscellaneous (All) | 36.41 |
Subtotal | 36.41 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 21.17 |
Space Heating | 0.00 |
Space Cooling | 45.54 |
Fans (All) | 10.30 |
Service Water Heating | 5.26 |
Receptacle Equipment | 12.24 |
Miscellaneous | 5.49 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 2872. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3501. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4552. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_SETBACK | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.000 |
February | 0.000 | 0.000 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 0.000 |
December | 0.000 | 0.000 |
Annual Sum or Average | 0.000 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231714E+11 | 36092.87 | 15-JAN-19:08 | 26.75 | 20.92 | 0.218397E+10 | 2451.31 | 04-JAN-15:20 | 32.57 | 24.30 |
February | 0.237100E+11 | 36917.98 | 24-FEB-21:07 | 27.38 | 21.31 | 0.199426E+10 | 2451.29 | 21-FEB-15:00 | 31.90 | 23.95 |
March | 0.288844E+11 | 35703.66 | 21-MAR-20:05 | 27.00 | 22.86 | 0.228100E+10 | 2451.29 | 16-MAR-14:09 | 31.83 | 24.83 |
April | 0.303993E+11 | 35175.98 | 22-APR-00:43 | 24.17 | 23.00 | 0.215632E+10 | 2451.25 | 20-APR-14:00 | 30.60 | 25.87 |
May | 0.333807E+11 | 35906.63 | 31-MAY-20:06 | 24.07 | 23.94 | 0.223240E+10 | 2451.30 | 06-MAY-14:39 | 37.00 | 27.33 |
June | 0.364276E+11 | 36336.68 | 27-JUN-02:63 | 24.00 | 24.00 | 0.220151E+10 | 2451.33 | 15-JUN-14:00 | 35.00 | 28.15 |
July | 0.311540E+11 | 37253.27 | 20-JUL-02:63 | 23.70 | 22.58 | 0.218722E+10 | 2451.23 | 12-JUL-14:00 | 27.00 | 25.53 |
August | 0.284836E+11 | 36207.63 | 24-AUG-02:63 | 23.17 | 23.17 | 0.228097E+10 | 2451.24 | 30-AUG-14:09 | 29.83 | 25.72 |
September | 0.264968E+11 | 35016.06 | 06-SEP-04:43 | 25.18 | 24.25 | 0.215634E+10 | 2451.24 | 20-SEP-14:09 | 29.00 | 26.74 |
October | 0.235186E+11 | 33995.12 | 10-OCT-00:03 | 24.03 | 23.62 | 0.218395E+10 | 2451.24 | 25-OCT-14:09 | 28.42 | 26.54 |
November | 0.228406E+11 | 33263.68 | 22-NOV-21:06 | 25.10 | 23.60 | 0.210124E+10 | 2451.31 | 21-NOV-15:00 | 30.30 | 25.43 |
December | 0.221544E+11 | 37133.28 | 20-DEC-21:08 | 22.83 | 18.42 | 0.218728E+10 | 2451.25 | 30-DEC-15:30 | 30.65 | 25.41 |
Annual Sum or Average | 0.330621E+12 | 0.261465E+11 | ||||||||
Minimum of Months | 0.221544E+11 | 33263.68 | 22.83 | 18.42 | 0.199426E+10 | 2451.23 | 27.00 | 23.95 | ||
Maximum of Months | 0.364276E+11 | 37253.27 | 27.38 | 24.25 | 0.228100E+10 | 2451.33 | 37.00 | 28.15 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.631994E+11 | 140378.43 | 23-JAN-07:02 | 19.82 | 17.48 | 0.920490E+10 | 10327.11 | 28-JAN-16:00 | 28.00 | 23.68 |
February | 0.617394E+11 | 149989.64 | 23-FEB-06:03 | 22.85 | 19.63 | 0.840533E+10 | 10327.03 | 25-FEB-11:50 | 28.83 | 21.33 |
March | 0.744432E+11 | 143315.52 | 14-MAR-05:02 | 25.00 | 22.78 | 0.961382E+10 | 10327.00 | 11-MAR-11:09 | 30.17 | 24.21 |
April | 0.731261E+11 | 140970.32 | 27-APR-05:02 | 26.00 | 23.87 | 0.908861E+10 | 10327.16 | 28-APR-14:09 | 33.92 | 26.16 |
May | 0.723313E+11 | 135531.16 | 31-MAY-05:02 | 24.17 | 24.17 | 0.940937E+10 | 10327.17 | 25-MAY-14:09 | 28.33 | 27.08 |
June | 0.733794E+11 | 136752.14 | 20-JUN-05:02 | 24.00 | 24.00 | 0.927907E+10 | 10327.05 | 24-JUN-11:20 | 33.00 | 27.75 |
July | 0.663058E+11 | 138175.51 | 15-JUL-05:02 | 25.10 | 23.71 | 0.921886E+10 | 10327.10 | 12-JUL-14:00 | 27.00 | 25.53 |
August | 0.672254E+11 | 134326.82 | 28-AUG-05:02 | 25.00 | 25.00 | 0.961385E+10 | 10327.01 | 25-AUG-14:09 | 29.17 | 26.77 |
September | 0.652198E+11 | 136307.70 | 13-SEP-05:03 | 24.17 | 24.04 | 0.908862E+10 | 10327.12 | 05-SEP-14:09 | 32.17 | 27.21 |
October | 0.607463E+11 | 132544.87 | 09-OCT-07:03 | 25.50 | 24.67 | 0.920490E+10 | 10326.87 | 21-OCT-12:30 | 30.70 | 25.87 |
November | 0.599822E+11 | 134972.06 | 25-NOV-07:02 | 21.17 | 18.83 | 0.885627E+10 | 10327.10 | 24-NOV-15:09 | 28.95 | 22.45 |
December | 0.616160E+11 | 140296.99 | 21-DEC-07:02 | 18.83 | 17.79 | 0.921874E+10 | 10327.07 | 01-DEC-15:09 | 30.75 | 24.80 |
Annual Sum or Average | 0.799314E+12 | 0.110202E+12 | ||||||||
Minimum of Months | 0.599822E+11 | 132544.87 | 18.83 | 17.48 | 0.840533E+10 | 10326.87 | 27.00 | 21.33 | ||
Maximum of Months | 0.744432E+11 | 149989.64 | 26.00 | 25.00 | 0.961385E+10 | 10327.17 | 33.92 | 27.75 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184825E+11 | 19620.98 | 16-JAN-19:05 | 26.33 | 21.45 | 0.866962E+09 | 973.21 | 04-JAN-15:39 | 32.13 | 24.52 |
February | 0.170546E+11 | 19855.60 | 24-FEB-21:05 | 27.38 | 21.31 | 0.791650E+09 | 973.14 | 25-FEB-11:00 | 29.00 | 21.35 |
March | 0.178485E+11 | 18747.43 | 03-MAR-02:23 | 24.00 | 20.61 | 0.905493E+09 | 973.13 | 04-MAR-12:50 | 33.08 | 22.09 |
April | 0.160945E+11 | 17645.75 | 22-APR-00:43 | 24.17 | 23.00 | 0.856013E+09 | 973.08 | 15-APR-10:09 | 31.42 | 25.66 |
May | 0.162856E+11 | 17893.06 | 10-MAY-20:06 | 22.17 | 22.17 | 0.886224E+09 | 973.08 | 01-MAY-14:09 | 34.83 | 27.34 |
June | 0.162402E+11 | 17435.49 | 27-JUN-01:23 | 24.25 | 24.19 | 0.873961E+09 | 973.14 | 30-JUN-14:30 | 28.00 | 26.50 |
July | 0.149928E+11 | 17919.86 | 20-JUL-00:03 | 23.72 | 22.60 | 0.868287E+09 | 973.12 | 03-JUL-14:00 | 25.60 | 23.63 |
August | 0.148023E+11 | 17736.80 | 24-AUG-01:23 | 23.50 | 23.13 | 0.905494E+09 | 973.10 | 19-AUG-14:50 | 25.00 | 24.56 |
September | 0.151980E+11 | 17638.02 | 29-SEP-02:43 | 24.08 | 23.27 | 0.856016E+09 | 973.10 | 16-SEP-10:00 | 29.50 | 26.46 |
October | 0.154136E+11 | 17941.78 | 11-OCT-02:63 | 24.00 | 23.26 | 0.866964E+09 | 973.16 | 19-OCT-14:09 | 28.00 | 25.71 |
November | 0.166306E+11 | 18675.02 | 24-NOV-21:08 | 23.38 | 21.12 | 0.834126E+09 | 973.16 | 25-NOV-15:09 | 25.82 | 22.38 |
December | 0.181064E+11 | 20401.20 | 20-DEC-21:06 | 22.83 | 18.42 | 0.868277E+09 | 973.12 | 23-DEC-11:39 | 28.67 | 24.28 |
Annual Sum or Average | 0.197150E+12 | 0.103795E+11 | ||||||||
Minimum of Months | 0.148023E+11 | 17435.49 | 22.17 | 18.42 | 0.791650E+09 | 973.08 | 25.00 | 21.35 | ||
Maximum of Months | 0.184825E+11 | 20401.20 | 27.38 | 24.19 | 0.905494E+09 | 973.21 | 34.83 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154228E+11 | 16900.79 | 16-JAN-19:05 | 26.33 | 21.45 | 0.866961E+09 | 973.18 | 04-JAN-15:09 | 32.78 | 24.18 |
February | 0.142959E+11 | 16996.18 | 24-FEB-21:05 | 27.38 | 21.31 | 0.791648E+09 | 973.11 | 25-FEB-12:09 | 29.43 | 21.53 |
March | 0.146440E+11 | 15894.89 | 02-MAR-21:06 | 26.83 | 21.45 | 0.905492E+09 | 973.10 | 03-MAR-15:09 | 32.97 | 23.33 |
April | 0.131265E+11 | 14985.43 | 22-APR-00:43 | 24.17 | 23.00 | 0.856014E+09 | 973.11 | 14-APR-14:00 | 27.00 | 25.11 |
May | 0.132934E+11 | 15002.97 | 10-MAY-20:06 | 22.17 | 22.17 | 0.886226E+09 | 973.14 | 06-MAY-15:20 | 36.30 | 27.34 |
June | 0.133472E+11 | 14944.88 | 21-JUN-03:23 | 23.70 | 23.58 | 0.873963E+09 | 973.12 | 30-JUN-14:50 | 28.67 | 27.14 |
July | 0.120348E+11 | 15391.33 | 03-JUL-00:03 | 25.73 | 22.78 | 0.868287E+09 | 973.13 | 12-JUL-14:09 | 27.42 | 25.11 |
August | 0.117769E+11 | 15146.11 | 24-AUG-01:23 | 23.50 | 23.13 | 0.905498E+09 | 973.12 | 16-AUG-14:30 | 27.50 | 26.56 |
September | 0.123114E+11 | 15132.16 | 29-SEP-02:43 | 24.08 | 23.27 | 0.856018E+09 | 973.11 | 16-SEP-15:00 | 27.40 | 25.35 |
October | 0.123550E+11 | 15395.20 | 08-OCT-03:03 | 23.93 | 23.23 | 0.866964E+09 | 973.10 | 26-OCT-14:20 | 25.67 | 24.63 |
November | 0.137049E+11 | 16426.04 | 25-NOV-01:03 | 24.07 | 20.46 | 0.834125E+09 | 973.13 | 08-NOV-15:50 | 26.83 | 25.09 |
December | 0.150702E+11 | 17536.35 | 20-DEC-21:06 | 22.83 | 18.42 | 0.868277E+09 | 973.15 | 07-DEC-15:39 | 31.53 | 22.79 |
Annual Sum or Average | 0.161383E+12 | 0.103795E+11 | ||||||||
Minimum of Months | 0.117769E+11 | 14944.88 | 22.17 | 18.42 | 0.791648E+09 | 973.10 | 25.67 | 21.53 | ||
Maximum of Months | 0.154228E+11 | 17536.35 | 27.38 | 23.58 | 0.905498E+09 | 973.18 | 36.30 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 | 23.60 | 0.00 | 0.00 | 01-JAN-00:10 | 25.03 | 23.60 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 | 22.46 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 22.97 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 | 25.10 | 0.00 | 0.00 | 01-APR-00:10 | 27.53 | 25.10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 | 26.40 | 0.00 | 0.00 | 01-MAY-00:10 | 28.62 | 26.40 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 | 23.91 | 0.00 | 0.00 | 01-JUN-00:10 | 24.05 | 23.91 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.40 | 24.33 | 0.00 | 0.00 | 01-JUL-00:10 | 25.40 | 24.33 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 | 24.75 | 0.00 | 0.00 | 01-AUG-00:10 | 25.63 | 24.75 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.53 | 25.66 | 0.00 | 0.00 | 01-SEP-00:10 | 26.53 | 25.66 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 | 25.35 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 | 24.37 | 0.00 | 0.00 | 01-NOV-00:10 | 25.22 | 24.37 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 | 23.43 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 23.80 | 22.46 | 0.00 | 0.00 | 23.80 | 22.46 | ||
Maximum of Months | 0.00 | 0.00 | 28.62 | 26.40 | 0.00 | 0.00 | 28.62 | 26.40 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 826029.72 | 1251.01 | 29-JAN-08:04 | 24.17 |
February | 1185726.96 | 2162.70 | 19-FEB-08:07 | 26.17 |
March | 592234.04 | 2070.26 | 26-MAR-07:05 | 27.17 |
April | 1664635.43 | 2363.52 | 30-APR-07:04 | 28.10 |
May | 903790.09 | 1825.14 | 18-MAY-05:05 | 24.00 |
June | 919801.18 | 2134.83 | 04-JUN-07:07 | 25.92 |
July | 1950361.96 | 2352.41 | 09-JUL-07:07 | 26.50 |
August | 2105546.68 | 2318.64 | 27-AUG-07:07 | 26.67 |
September | 789272.57 | 2291.50 | 10-SEP-07:07 | 26.50 |
October | 3240772.87 | 2006.84 | 08-OCT-07:07 | 25.75 |
November | 1424963.55 | 1915.26 | 19-NOV-08:07 | 25.50 |
December | 1021740.87 | 2163.16 | 10-DEC-08:07 | 26.33 |
Annual Sum or Average | 16624875.94 | |||
Minimum of Months | 592234.04 | 1251.01 | 24.00 | |
Maximum of Months | 3240772.87 | 2363.52 | 28.10 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219726E+09 | 8576.42 | 03-JAN-07:06 | 25.27 |
February | 0.217534E+09 | 9664.13 | 20-FEB-09:06 | 28.23 |
March | 0.228058E+09 | 9843.79 | 05-MAR-09:06 | 28.25 |
April | 0.204633E+09 | 9451.06 | 09-APR-07:05 | 27.78 |
May | 0.193771E+09 | 11406.75 | 28-MAY-07:05 | 32.25 |
June | 0.175139E+09 | 9524.34 | 11-JUN-07:06 | 28.50 |
July | 0.252380E+09 | 9525.70 | 09-JUL-08:06 | 27.67 |
August | 0.216221E+09 | 9166.17 | 13-AUG-07:05 | 27.67 |
September | 0.212257E+09 | 9092.49 | 17-SEP-08:06 | 26.32 |
October | 0.234515E+09 | 9737.24 | 08-OCT-08:06 | 28.25 |
November | 0.228011E+09 | 9828.54 | 23-NOV-09:06 | 28.57 |
December | 0.207745E+09 | 9995.12 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.258999E+10 | |||
Minimum of Months | 0.175139E+09 | 8576.42 | 25.27 | |
Maximum of Months | 0.252380E+09 | 11406.75 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 297994.27 | 737.18 | 29-JAN-08:04 | 24.17 |
February | 694963.86 | 1342.25 | 19-FEB-08:07 | 26.17 |
March | 322223.37 | 1086.17 | 19-MAR-07:05 | 26.50 |
April | 896234.37 | 1573.42 | 30-APR-07:04 | 28.10 |
May | 447041.02 | 1581.50 | 14-MAY-07:07 | 27.50 |
June | 531036.38 | 1234.10 | 04-JUN-07:07 | 25.92 |
July | 1130217.86 | 1367.33 | 09-JUL-07:07 | 26.50 |
August | 934237.60 | 1407.74 | 27-AUG-07:07 | 26.67 |
September | 421257.30 | 1375.01 | 10-SEP-07:07 | 26.50 |
October | 749833.91 | 1221.78 | 08-OCT-07:07 | 25.75 |
November | 517741.36 | 1215.69 | 19-NOV-08:07 | 25.50 |
December | 595431.47 | 1327.75 | 10-DEC-08:07 | 26.33 |
Annual Sum or Average | 7538212.77 | |||
Minimum of Months | 297994.27 | 737.18 | 24.17 | |
Maximum of Months | 1130217.86 | 1581.50 | 28.10 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 241132.68 | 620.58 | 29-JAN-08:04 | 24.17 |
February | 597988.61 | 1165.97 | 19-FEB-08:07 | 26.17 |
March | 316460.88 | 1056.35 | 26-MAR-07:05 | 27.17 |
April | 834074.26 | 1453.60 | 30-APR-07:04 | 28.10 |
May | 281259.26 | 1402.01 | 14-MAY-07:07 | 27.50 |
June | 470529.14 | 1090.15 | 04-JUN-07:07 | 25.92 |
July | 995323.58 | 1210.72 | 09-JUL-07:07 | 26.50 |
August | 1398200.30 | 1253.88 | 27-AUG-07:07 | 26.67 |
September | 389979.55 | 1221.48 | 10-SEP-07:07 | 26.50 |
October | 764444.41 | 1070.15 | 08-OCT-07:07 | 25.75 |
November | 427823.09 | 1050.33 | 19-NOV-08:07 | 25.50 |
December | 504604.29 | 1145.85 | 10-DEC-08:07 | 26.33 |
Annual Sum or Average | 7221820.05 | |||
Minimum of Months | 241132.68 | 620.58 | 24.17 | |
Maximum of Months | 1398200.30 | 1453.60 | 28.10 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.245973E+10 | 2023.29 | 02-JAN-09:09 | 0.419292E+10 | 2751.42 | 02-JAN-09:09 |
February | 0.223751E+10 | 2023.29 | 01-FEB-09:09 | 0.380401E+10 | 2751.42 | 01-FEB-09:09 |
March | 0.255095E+10 | 2023.29 | 01-MAR-09:09 | 0.429860E+10 | 2751.42 | 01-MAR-09:09 |
April | 0.240752E+10 | 2023.29 | 01-APR-09:09 | 0.408483E+10 | 2751.42 | 01-APR-09:09 |
May | 0.250534E+10 | 2023.29 | 01-MAY-08:09 | 0.424576E+10 | 2751.42 | 01-MAY-08:09 |
June | 0.246168E+10 | 2023.29 | 01-JUN-08:09 | 0.415135E+10 | 2751.42 | 01-JUN-08:09 |
July | 0.245118E+10 | 2023.29 | 01-JUL-09:09 | 0.417924E+10 | 2751.42 | 01-JUL-09:09 |
August | 0.255095E+10 | 2023.29 | 01-AUG-08:09 | 0.429860E+10 | 2751.42 | 01-AUG-08:09 |
September | 0.240752E+10 | 2023.29 | 01-SEP-08:09 | 0.408483E+10 | 2751.42 | 01-SEP-08:09 |
October | 0.245973E+10 | 2023.29 | 02-OCT-08:09 | 0.419292E+10 | 2751.42 | 02-OCT-08:09 |
November | 0.237899E+10 | 2023.29 | 01-NOV-08:09 | 0.405935E+10 | 2751.42 | 01-NOV-08:09 |
December | 0.245118E+10 | 2023.29 | 01-DEC-09:09 | 0.417924E+10 | 2751.42 | 01-DEC-09:09 |
Annual Sum or Average | 0.293223E+11 | 0.497716E+11 | ||||
Minimum of Months | 0.223751E+10 | 2023.29 | 0.380401E+10 | 2751.42 | ||
Maximum of Months | 0.255095E+10 | 2023.29 | 0.429860E+10 | 2751.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.211593E+11 | 22326.78 | 02-JAN-16:10 | 0.707031E+10 | 4639.58 | 02-JAN-09:09 |
February | 0.183665E+11 | 22326.78 | 01-FEB-16:40 | 0.641452E+10 | 4639.58 | 01-FEB-09:09 |
March | 0.217987E+11 | 22326.78 | 01-MAR-16:30 | 0.724851E+10 | 4639.58 | 01-MAR-09:09 |
April | 0.205233E+11 | 22326.78 | 01-APR-16:49 | 0.688804E+10 | 4639.58 | 01-APR-09:09 |
May | 0.211450E+11 | 22326.78 | 01-MAY-16:49 | 0.715941E+10 | 4639.58 | 01-MAY-08:09 |
June | 0.200686E+11 | 22326.78 | 01-JUN-16:00 | 0.700021E+10 | 4639.58 | 01-JUN-08:09 |
July | 0.204191E+11 | 22326.78 | 01-JUL-16:49 | 0.704724E+10 | 4639.58 | 01-JUL-09:09 |
August | 0.213208E+11 | 22326.78 | 01-AUG-16:49 | 0.724851E+10 | 4639.58 | 01-AUG-08:09 |
September | 0.198945E+11 | 22326.78 | 01-SEP-16:40 | 0.688804E+10 | 4639.58 | 01-SEP-08:09 |
October | 0.199253E+11 | 22326.78 | 02-OCT-16:30 | 0.707031E+10 | 4639.58 | 02-OCT-08:09 |
November | 0.201783E+11 | 22326.78 | 01-NOV-15:00 | 0.684509E+10 | 4639.58 | 01-NOV-08:09 |
December | 0.215976E+11 | 22326.78 | 01-DEC-16:10 | 0.704724E+10 | 4639.58 | 01-DEC-09:09 |
Annual Sum or Average | 0.246397E+12 | 0.839274E+11 | ||||
Minimum of Months | 0.183665E+11 | 22326.78 | 0.641452E+10 | 4639.58 | ||
Maximum of Months | 0.217987E+11 | 22326.78 | 0.724851E+10 | 4639.58 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.251152E+10 | 2103.80 | 02-JAN-09:09 | 0.443872E+10 | 2912.71 | 02-JAN-09:09 |
February | 0.228515E+10 | 2103.80 | 01-FEB-09:09 | 0.402701E+10 | 2912.71 | 01-FEB-09:09 |
March | 0.260661E+10 | 2103.80 | 01-MAR-09:09 | 0.455059E+10 | 2912.71 | 01-MAR-09:09 |
April | 0.245935E+10 | 2103.80 | 01-APR-09:09 | 0.432429E+10 | 2912.71 | 01-APR-09:09 |
May | 0.255907E+10 | 2103.80 | 01-MAY-08:09 | 0.449465E+10 | 2912.71 | 01-MAY-08:09 |
June | 0.251531E+10 | 2103.80 | 01-JUN-08:09 | 0.439471E+10 | 2912.71 | 01-JUN-08:09 |
July | 0.250311E+10 | 2103.80 | 01-JUL-09:09 | 0.442423E+10 | 2912.71 | 01-JUL-09:09 |
August | 0.260661E+10 | 2103.80 | 01-AUG-08:09 | 0.455059E+10 | 2912.71 | 01-AUG-08:09 |
September | 0.245935E+10 | 2103.80 | 01-SEP-08:09 | 0.432429E+10 | 2912.71 | 01-SEP-08:09 |
October | 0.251152E+10 | 2103.80 | 02-OCT-08:09 | 0.443872E+10 | 2912.71 | 02-OCT-08:09 |
November | 0.242863E+10 | 2103.80 | 01-NOV-08:09 | 0.429732E+10 | 2912.71 | 01-NOV-08:09 |
December | 0.250311E+10 | 2103.80 | 01-DEC-09:09 | 0.442423E+10 | 2912.71 | 01-DEC-09:09 |
Annual Sum or Average | 0.299493E+11 | 0.526893E+11 | ||||
Minimum of Months | 0.228515E+10 | 2103.80 | 0.402701E+10 | 2912.71 | ||
Maximum of Months | 0.260661E+10 | 2103.80 | 0.455059E+10 | 2912.71 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.243691E+10 | 2036.90 | 02-JAN-09:09 | 0.666220E+09 | 437.18 | 02-JAN-09:09 |
February | 0.221721E+10 | 2036.90 | 01-FEB-09:09 | 0.604426E+09 | 437.18 | 01-FEB-09:09 |
March | 0.252895E+10 | 2036.90 | 01-MAR-09:09 | 0.683011E+09 | 437.18 | 01-MAR-09:09 |
April | 0.238616E+10 | 2036.90 | 01-APR-09:09 | 0.649045E+09 | 437.18 | 01-APR-09:09 |
May | 0.248293E+10 | 2036.90 | 01-MAY-08:09 | 0.674616E+09 | 437.18 | 01-MAY-08:09 |
June | 0.244038E+10 | 2036.90 | 01-JUN-08:09 | 0.659615E+09 | 437.18 | 01-JUN-08:09 |
July | 0.242871E+10 | 2036.90 | 01-JUL-09:09 | 0.664046E+09 | 437.18 | 01-JUL-09:09 |
August | 0.252895E+10 | 2036.90 | 01-AUG-08:09 | 0.683011E+09 | 437.18 | 01-AUG-08:09 |
September | 0.238616E+10 | 2036.90 | 01-SEP-08:09 | 0.649045E+09 | 437.18 | 01-SEP-08:09 |
October | 0.243691E+10 | 2036.90 | 02-OCT-08:09 | 0.666220E+09 | 437.18 | 02-OCT-08:09 |
November | 0.235654E+10 | 2036.90 | 01-NOV-08:09 | 0.644998E+09 | 437.18 | 01-NOV-08:09 |
December | 0.242871E+10 | 2036.90 | 01-DEC-09:09 | 0.664046E+09 | 437.18 | 01-DEC-09:09 |
Annual Sum or Average | 0.290585E+11 | 0.790830E+10 | ||||
Minimum of Months | 0.221721E+10 | 2036.90 | 0.604426E+09 | 437.18 | ||
Maximum of Months | 0.252895E+10 | 2036.90 | 0.683011E+09 | 437.18 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.103900E+09 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 94517577.03 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.107770E+09 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.101704E+09 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.105835E+09 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.103997E+09 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.103541E+09 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.107770E+09 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.101704E+09 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.103900E+09 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.100485E+09 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.103541E+09 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123866E+10 | ||||
Minimum of Months | 94517577.03 | 85.79 | 0.00 | 0.00 | |
Maximum of Months | 0.107770E+09 | 85.79 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.245973E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129173E+09 | 30987509.42 |
February | 0.479114E+10 | 0.223751E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174916E+09 | 1692771.31 |
March | 0.548013E+10 | 0.255095E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340655E+09 | 3362075.88 |
April | 0.518069E+10 | 0.240752E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343804E+09 | 129995.66 |
May | 0.536353E+10 | 0.250534E+10 | 0.424576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370690E+09 | 1272095.17 |
June | 0.528933E+10 | 0.246168E+10 | 0.415135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338159E+09 | 2743270.51 |
July | 0.525489E+10 | 0.245118E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185176E+09 | 1477494.40 |
August | 0.548013E+10 | 0.255095E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248173E+09 | 2694675.57 |
September | 0.518069E+10 | 0.240752E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175071E+09 | 1466574.15 |
October | 0.524694E+10 | 0.245973E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137393E+09 | 2241612.30 |
November | 0.504819E+10 | 0.237899E+10 | 0.405935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108227E+09 | 8920284.22 |
December | 0.525489E+10 | 0.245118E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89178728.05 | 43314034.72 |
Annual Sum or Average | 0.628175E+11 | 0.293223E+11 | 0.497716E+11 | 0.264062E+10 | 0.100302E+09 | ||||
Minimum of Months | 0.479114E+10 | 0.223751E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89178728.05 | 129995.66 |
Maximum of Months | 0.548013E+10 | 0.255095E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370690E+09 | 43314034.72 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.211593E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81691359.10 | 74725696.02 |
February | 0.201852E+11 | 0.183665E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107437E+09 | 25445154.17 |
March | 0.230879E+11 | 0.217987E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175758E+09 | 51873412.52 |
April | 0.218263E+11 | 0.205233E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173887E+09 | 9929841.46 |
May | 0.225967E+11 | 0.211450E+11 | 0.715941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204545E+09 | 21597212.24 |
June | 0.222841E+11 | 0.200686E+11 | 0.700021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179260E+09 | 23675780.49 |
July | 0.221389E+11 | 0.204191E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114696E+09 | 21542892.60 |
August | 0.230879E+11 | 0.213208E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137572E+09 | 36019419.44 |
September | 0.218263E+11 | 0.198945E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100815E+09 | 21110313.81 |
October | 0.221054E+11 | 0.199253E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82610739.62 | 31861302.91 |
November | 0.212681E+11 | 0.201783E+11 | 0.684509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65853601.64 | 40347327.15 |
December | 0.221389E+11 | 0.215976E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63161420.86 | 83546085.28 |
Annual Sum or Average | 0.264651E+12 | 0.246397E+12 | 0.839274E+11 | 0.148729E+10 | 0.441674E+09 | ||||
Minimum of Months | 0.201852E+11 | 0.183665E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63161420.86 | 9929841.46 |
Maximum of Months | 0.230879E+11 | 0.217987E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204545E+09 | 83546085.28 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.251152E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54930493.36 | 14591637.82 |
February | 0.190200E+10 | 0.228515E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74497899.92 | 1100589.15 |
March | 0.217552E+10 | 0.260661E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145321E+09 | 1788805.72 |
April | 0.205665E+10 | 0.245935E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147965E+09 | 77520.64 |
May | 0.212923E+10 | 0.255907E+10 | 0.449465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160307E+09 | 602867.70 |
June | 0.209978E+10 | 0.251531E+10 | 0.439471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146854E+09 | 1176114.25 |
July | 0.208610E+10 | 0.250311E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80244259.00 | 665764.76 |
August | 0.217552E+10 | 0.260661E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107149E+09 | 1219660.28 |
September | 0.205665E+10 | 0.245935E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75220647.49 | 718610.63 |
October | 0.208295E+10 | 0.251152E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58784719.85 | 1199518.31 |
November | 0.200405E+10 | 0.242863E+10 | 0.429732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46175910.36 | 4381298.55 |
December | 0.208610E+10 | 0.250311E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38140172.67 | 20017496.52 |
Annual Sum or Average | 0.249375E+11 | 0.299493E+11 | 0.526893E+11 | 0.113559E+10 | 47539884.32 | ||||
Minimum of Months | 0.190200E+10 | 0.228515E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38140172.67 | 77520.64 |
Maximum of Months | 0.217552E+10 | 0.260661E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160307E+09 | 20017496.52 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.243691E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55185317.58 | 14198302.46 |
February | 0.190200E+10 | 0.221721E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 74846991.83 | 944411.29 |
March | 0.217552E+10 | 0.252895E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146370E+09 | 1599668.33 |
April | 0.205665E+10 | 0.238616E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148868E+09 | 53726.89 |
May | 0.212923E+10 | 0.248293E+10 | 0.674616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161069E+09 | 508427.13 |
June | 0.209978E+10 | 0.244038E+10 | 0.659615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147605E+09 | 1085989.33 |
July | 0.208610E+10 | 0.242871E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80591204.87 | 576979.36 |
August | 0.217552E+10 | 0.252895E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107771E+09 | 1151716.33 |
September | 0.205665E+10 | 0.238616E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75596351.42 | 665942.50 |
October | 0.208295E+10 | 0.243691E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 59062182.03 | 1070529.18 |
November | 0.200405E+10 | 0.235654E+10 | 0.644998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46394143.59 | 4168307.11 |
December | 0.208610E+10 | 0.242871E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38229171.75 | 19593500.32 |
Annual Sum or Average | 0.249375E+11 | 0.290585E+11 | 0.790830E+10 | 0.114159E+10 | 45617500.23 | ||||
Minimum of Months | 0.190200E+10 | 0.221721E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38229171.75 | 53726.89 |
Maximum of Months | 0.217552E+10 | 0.252895E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161069E+09 | 19593500.32 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33492630.53 | 0.231920E+09 |
February | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102640E+09 | 0.119142E+09 |
March | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295071E+09 | 68116838.65 |
April | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375667E+09 | 22129268.68 |
May | 0.00 | 0.105835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419524E+09 | 50674676.54 |
June | 0.00 | 0.103997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382065E+09 | 42949040.38 |
July | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189658E+09 | 88877717.50 |
August | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242912E+09 | 81863206.95 |
September | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182421E+09 | 87745121.54 |
October | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83749494.70 | 0.122350E+09 |
November | 0.00 | 0.100485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29643217.27 | 0.202976E+09 |
December | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13158028.91 | 0.262811E+09 |
Annual Sum or Average | 0.00 | 0.123866E+10 | 0.235000E+10 | 0.138155E+10 | |||||
Minimum of Months | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13158028.91 | 22129268.68 |
Maximum of Months | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419524E+09 | 0.262811E+09 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2023.29 | 02-JAN-09:09 | 2751.42 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 364.67 | 08-JAN-19:10 | 878.58 | 07-JAN-05:00 |
February | 5888.82 | 01-FEB-15:09 | 2023.29 | 01-FEB-09:09 | 2751.42 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 465.66 | 20-FEB-19:45 | 60.35 | 26-FEB-06:40 |
March | 5888.82 | 01-MAR-15:09 | 2023.29 | 01-MAR-09:09 | 2751.42 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.11 | 19-MAR-18:10 | 159.91 | 14-MAR-22:00 |
April | 5888.82 | 01-APR-10:09 | 2023.29 | 01-APR-09:09 | 2751.42 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 629.19 | 02-APR-19:00 | 42.31 | 22-APR-02:40 |
May | 5888.82 | 01-MAY-14:09 | 2023.29 | 01-MAY-08:09 | 2751.42 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 806.94 | 07-MAY-18:10 | 313.59 | 08-MAY-22:00 |
June | 5888.82 | 01-JUN-14:09 | 2023.29 | 01-JUN-08:09 | 2751.42 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 755.19 | 11-JUN-19:00 | 275.33 | 20-JUN-23:20 |
July | 5888.82 | 01-JUL-10:09 | 2023.29 | 01-JUL-09:09 | 2751.42 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 415.29 | 25-JUL-20:20 | 176.21 | 19-JUL-20:40 |
August | 5888.82 | 01-AUG-14:09 | 2023.29 | 01-AUG-08:09 | 2751.42 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 606.25 | 01-AUG-21:00 | 210.80 | 23-AUG-20:05 |
September | 5888.82 | 01-SEP-14:09 | 2023.29 | 01-SEP-08:09 | 2751.42 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 358.06 | 10-SEP-14:55 | 153.69 | 15-SEP-22:00 |
October | 5888.82 | 02-OCT-14:09 | 2023.29 | 02-OCT-08:09 | 2751.42 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 515.99 | 08-OCT-18:10 | 112.80 | 23-OCT-05:00 |
November | 5888.82 | 01-NOV-14:09 | 2023.29 | 01-NOV-08:09 | 2751.42 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 216.41 | 02-NOV-20:10 | 183.78 | 25-NOV-05:00 |
December | 5888.82 | 01-DEC-15:09 | 2023.29 | 01-DEC-09:09 | 2751.42 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 245.38 | 10-DEC-19:10 | 374.07 | 21-DEC-04:40 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 216.41 | 42.31 | |||||
Maximum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.11 | 878.58 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 22326.78 | 02-JAN-16:10 | 4639.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.60 | 08-JAN-19:02 | 1236.75 | 07-JAN-04:53 |
February | 24809.68 | 01-FEB-15:09 | 22326.78 | 01-FEB-16:40 | 4639.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 371.90 | 20-FEB-19:02 | 124.22 | 20-FEB-07:00 |
March | 24809.68 | 01-MAR-15:09 | 22326.78 | 01-MAR-16:30 | 4639.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.10 | 19-MAR-18:02 | 246.32 | 14-MAR-22:00 |
April | 24809.68 | 01-APR-10:09 | 22326.78 | 01-APR-16:49 | 4639.58 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 481.55 | 02-APR-18:02 | 111.05 | 13-APR-05:00 |
May | 24809.68 | 01-MAY-14:09 | 22326.78 | 01-MAY-16:49 | 4639.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 642.20 | 07-MAY-18:02 | 443.45 | 08-MAY-22:00 |
June | 24809.68 | 01-JUN-14:09 | 22326.78 | 01-JUN-16:00 | 4639.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 597.88 | 11-JUN-18:02 | 500.97 | 20-JUN-23:00 |
July | 24809.68 | 01-JUL-10:09 | 22326.78 | 01-JUL-16:49 | 4639.58 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 328.18 | 25-JUL-20:02 | 150.24 | 19-JUL-21:10 |
August | 24809.68 | 01-AUG-14:09 | 22326.78 | 01-AUG-16:49 | 4639.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 411.56 | 01-AUG-20:02 | 282.81 | 04-AUG-03:00 |
September | 24809.68 | 01-SEP-14:09 | 22326.78 | 01-SEP-16:40 | 4639.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 293.07 | 10-SEP-15:00 | 266.74 | 15-SEP-22:00 |
October | 24809.68 | 02-OCT-14:09 | 22326.78 | 02-OCT-16:30 | 4639.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 406.47 | 08-OCT-18:02 | 154.84 | 23-OCT-22:50 |
November | 24809.68 | 01-NOV-14:09 | 22326.78 | 01-NOV-15:00 | 4639.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 172.06 | 10-NOV-13:00 | 205.59 | 25-NOV-04:53 |
December | 24809.68 | 01-DEC-15:09 | 22326.78 | 01-DEC-16:10 | 4639.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.56 | 09-DEC-14:00 | 390.38 | 21-DEC-04:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 22326.78 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 172.06 | 111.05 | |||||
Maximum of Months | 24809.68 | 22326.78 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 810.10 | 1236.75 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2103.80 | 02-JAN-09:09 | 2912.71 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 157.99 | 08-JAN-19:10 | 463.38 | 07-JAN-05:00 |
February | 2337.76 | 01-FEB-15:09 | 2103.80 | 01-FEB-09:09 | 2912.71 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.65 | 20-FEB-19:10 | 38.30 | 24-FEB-01:00 |
March | 2337.76 | 01-MAR-15:09 | 2103.80 | 01-MAR-09:09 | 2912.71 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 441.17 | 19-MAR-18:10 | 88.19 | 14-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 2103.80 | 01-APR-09:09 | 2912.71 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 272.63 | 02-APR-19:00 | 22.42 | 22-APR-02:40 |
May | 2337.76 | 01-MAY-14:09 | 2103.80 | 01-MAY-08:09 | 2912.71 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 350.21 | 07-MAY-18:10 | 146.77 | 08-MAY-22:00 |
June | 2337.76 | 01-JUN-14:09 | 2103.80 | 01-JUN-08:09 | 2912.71 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 327.27 | 11-JUN-19:00 | 123.08 | 20-JUN-23:20 |
July | 2337.76 | 01-JUL-10:09 | 2103.80 | 01-JUL-09:09 | 2912.71 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.95 | 25-JUL-20:30 | 75.85 | 19-JUL-20:40 |
August | 2337.76 | 01-AUG-14:09 | 2103.80 | 01-AUG-08:09 | 2912.71 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 262.70 | 01-AUG-21:00 | 98.21 | 23-AUG-20:05 |
September | 2337.76 | 01-SEP-14:09 | 2103.80 | 01-SEP-08:09 | 2912.71 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 155.16 | 10-SEP-14:55 | 79.42 | 15-SEP-22:00 |
October | 2337.76 | 02-OCT-14:09 | 2103.80 | 02-OCT-08:09 | 2912.71 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 223.56 | 08-OCT-18:10 | 51.18 | 23-OCT-04:55 |
November | 2337.76 | 01-NOV-14:09 | 2103.80 | 01-NOV-08:09 | 2912.71 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.79 | 02-NOV-20:10 | 87.13 | 25-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 2103.80 | 01-DEC-09:09 | 2912.71 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.31 | 10-DEC-19:10 | 178.95 | 21-DEC-05:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2103.80 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 93.79 | 22.42 | |||||
Maximum of Months | 2337.76 | 2103.80 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 441.17 | 463.38 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2036.90 | 02-JAN-09:09 | 437.18 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.00 | 08-JAN-19:10 | 438.34 | 07-JAN-05:00 |
February | 2337.76 | 01-FEB-15:09 | 2036.90 | 01-FEB-09:09 | 437.18 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.65 | 20-FEB-19:10 | 33.73 | 24-FEB-01:00 |
March | 2337.76 | 01-MAR-15:09 | 2036.90 | 01-MAR-09:09 | 437.18 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 441.17 | 19-MAR-18:10 | 79.73 | 14-MAR-22:00 |
April | 2337.76 | 01-APR-10:09 | 2036.90 | 01-APR-09:09 | 437.18 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 272.64 | 02-APR-19:00 | 17.74 | 22-APR-02:40 |
May | 2337.76 | 01-MAY-14:09 | 2036.90 | 01-MAY-08:09 | 437.18 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 350.10 | 07-MAY-18:10 | 132.43 | 08-MAY-22:00 |
June | 2337.76 | 01-JUN-14:09 | 2036.90 | 01-JUN-08:09 | 437.18 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 327.28 | 11-JUN-19:00 | 109.42 | 20-JUN-23:20 |
July | 2337.76 | 01-JUL-10:09 | 2036.90 | 01-JUL-09:09 | 437.18 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.96 | 25-JUL-20:30 | 64.96 | 19-JUL-20:40 |
August | 2337.76 | 01-AUG-14:09 | 2036.90 | 01-AUG-08:09 | 437.18 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 262.71 | 01-AUG-21:00 | 89.66 | 23-AUG-20:05 |
September | 2337.76 | 01-SEP-14:09 | 2036.90 | 01-SEP-08:09 | 437.18 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 155.16 | 10-SEP-14:55 | 70.38 | 15-SEP-22:00 |
October | 2337.76 | 02-OCT-14:09 | 2036.90 | 02-OCT-08:09 | 437.18 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 223.58 | 08-OCT-18:10 | 40.73 | 23-OCT-05:00 |
November | 2337.76 | 01-NOV-14:09 | 2036.90 | 01-NOV-08:09 | 437.18 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.79 | 02-NOV-20:10 | 84.44 | 25-NOV-05:00 |
December | 2337.76 | 01-DEC-15:09 | 2036.90 | 01-DEC-09:09 | 437.18 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 | 10-DEC-19:10 | 174.27 | 21-DEC-05:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2036.90 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 93.79 | 17.74 | |||||
Maximum of Months | 2337.76 | 2036.90 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 441.17 | 438.34 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 640.20 | 04-JAN-12:03 | 1528.77 | 24-JAN-08:61 |
February | 0.00 | 01-FEB-00:10 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.81 | 26-FEB-12:02 | 1097.19 | 21-FEB-09:53 |
March | 0.00 | 01-MAR-00:10 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2331.66 | 19-MAR-11:02 | 1121.26 | 14-MAR-11:03 |
April | 0.00 | 01-APR-00:10 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1797.76 | 09-APR-11:02 | 1245.26 | 14-APR-15:53 |
May | 0.00 | 01-MAY-00:10 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2877.97 | 05-MAY-11:01 | 1882.71 | 21-MAY-12:52 |
June | 0.00 | 01-JUN-00:10 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1783.91 | 16-JUN-11:02 | 1603.34 | 30-JUN-12:53 |
July | 0.00 | 01-JUL-00:10 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1279.15 | 01-JUL-11:02 | 1418.71 | 03-JUL-12:53 |
August | 0.00 | 01-AUG-00:10 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1848.43 | 16-AUG-11:02 | 1648.91 | 25-AUG-11:02 |
September | 0.00 | 01-SEP-00:10 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1174.68 | 09-SEP-11:02 | 1673.69 | 15-SEP-16:53 |
October | 0.00 | 01-OCT-00:10 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1119.46 | 27-OCT-11:02 | 1120.11 | 29-OCT-16:53 |
November | 0.00 | 01-NOV-00:10 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.34 | 18-NOV-12:55 | 1081.10 | 09-NOV-15:55 |
December | 0.00 | 01-DEC-00:10 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.98 | 11-DEC-12:05 | 1191.54 | 21-DEC-08:61 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.98 | 1081.10 | ||||
Maximum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2877.97 | 1882.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36092.87 | 15-JAN-19:08 | 0.00 | 718.66 | 2269.08 | 0.00 | 0.00 | 0.00 | 0.00 | 158.38 | 0.00 |
February | 36917.98 | 24-FEB-21:07 | 0.00 | 3449.57 | 3630.52 | 0.00 | 0.00 | 0.00 | 0.00 | 62.28 | 0.00 |
March | 35703.66 | 21-MAR-20:05 | 0.00 | 3449.57 | 3630.52 | 0.00 | 0.00 | 0.00 | 0.00 | 277.73 | 0.00 |
April | 35175.98 | 22-APR-00:43 | 0.00 | 431.20 | 1361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 0.00 |
May | 35906.63 | 31-MAY-20:06 | 0.00 | 2874.64 | 3025.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 |
June | 36336.68 | 27-JUN-02:63 | 0.00 | 431.20 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
July | 37253.27 | 20-JUL-02:63 | 0.00 | 431.20 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36207.63 | 24-AUG-02:63 | 0.00 | 431.20 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 |
September | 35016.06 | 06-SEP-04:43 | 0.00 | 431.20 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 18.21 | 0.00 |
October | 33995.12 | 10-OCT-00:03 | 0.00 | 431.20 | 1815.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
November | 33263.68 | 22-NOV-21:06 | 0.00 | 2874.64 | 3025.44 | 0.00 | 0.00 | 0.00 | 0.00 | 30.92 | 0.00 |
December | 37133.28 | 20-DEC-21:08 | 0.00 | 2874.64 | 3025.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.91 |
Annual Sum or Average | |||||||||||
Minimum of Months | 33263.68 | 0.00 | 431.20 | 1361.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37253.27 | 0.00 | 3449.57 | 3630.52 | 0.00 | 0.00 | 0.00 | 0.00 | 277.73 | 86.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 140378.43 | 23-JAN-07:02 | 15506.05 | 24807.53 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.45 |
February | 149989.64 | 23-FEB-06:03 | 0.00 | 4961.51 | 4081.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.23 |
March | 143315.52 | 14-MAR-05:02 | 0.00 | 6201.88 | 5101.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.89 |
April | 140970.32 | 27-APR-05:02 | 0.00 | 6201.88 | 5101.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 |
May | 135531.16 | 31-MAY-05:02 | 0.00 | 6201.88 | 5101.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.93 |
June | 136752.14 | 20-JUN-05:02 | 0.00 | 6201.88 | 5101.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 |
July | 138175.51 | 15-JUL-05:02 | 0.00 | 6201.88 | 3826.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.46 |
August | 134326.82 | 28-AUG-05:02 | 0.00 | 6201.88 | 5101.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
September | 136307.70 | 13-SEP-05:03 | 0.00 | 4961.51 | 4081.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 |
October | 132544.87 | 09-OCT-07:03 | 0.00 | 3721.13 | 3060.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 |
November | 134972.06 | 25-NOV-07:02 | 15506.05 | 12403.77 | 7732.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.72 |
December | 140296.99 | 21-DEC-07:02 | 15506.05 | 24807.53 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 132544.87 | 0.00 | 3721.13 | 3060.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | |
Maximum of Months | 149989.64 | 15506.05 | 24807.53 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19620.98 | 16-JAN-19:05 | 0.00 | 701.27 | 2882.52 | 0.00 | 0.00 | 0.00 | 0.00 | 64.31 | 0.00 |
February | 19855.60 | 24-FEB-21:05 | 0.00 | 2805.07 | 3843.35 | 0.00 | 0.00 | 0.00 | 0.00 | 24.76 | 0.00 |
March | 18747.43 | 03-MAR-02:23 | 0.00 | 350.63 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17645.75 | 22-APR-00:43 | 0.00 | 350.63 | 1441.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 0.00 |
May | 17893.06 | 10-MAY-20:06 | 0.00 | 2337.56 | 3202.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 |
June | 17435.49 | 27-JUN-01:23 | 0.00 | 350.63 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17919.86 | 20-JUL-00:03 | 0.00 | 350.63 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.76 |
August | 17736.80 | 24-AUG-01:23 | 0.00 | 350.63 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17638.02 | 29-SEP-02:43 | 0.00 | 350.63 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 0.00 |
October | 17941.78 | 11-OCT-02:63 | 0.00 | 350.63 | 1921.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18675.02 | 24-NOV-21:08 | 0.00 | 1870.05 | 2562.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 |
December | 20401.20 | 20-DEC-21:06 | 0.00 | 2337.56 | 3202.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.22 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17435.49 | 0.00 | 350.63 | 1441.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20401.20 | 0.00 | 2805.07 | 3843.35 | 0.00 | 0.00 | 0.00 | 0.00 | 64.31 | 44.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16900.79 | 16-JAN-19:05 | 0.00 | 701.27 | 432.65 | 0.00 | 0.00 | 0.00 | 0.00 | 65.72 | 0.00 |
February | 16996.18 | 24-FEB-21:05 | 0.00 | 2805.07 | 576.86 | 0.00 | 0.00 | 0.00 | 0.00 | 25.44 | 0.00 |
March | 15894.89 | 02-MAR-21:06 | 0.00 | 2337.56 | 480.72 | 0.00 | 0.00 | 0.00 | 0.00 | 90.80 | 0.00 |
April | 14985.43 | 22-APR-00:43 | 0.00 | 350.63 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 | 0.00 |
May | 15002.97 | 10-MAY-20:06 | 0.00 | 2337.56 | 480.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 |
June | 14944.88 | 21-JUN-03:23 | 0.00 | 350.63 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
July | 15391.33 | 03-JUL-00:03 | 0.00 | 350.63 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 | 0.00 |
August | 15146.11 | 24-AUG-01:23 | 0.00 | 350.63 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15132.16 | 29-SEP-02:43 | 0.00 | 350.63 | 288.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
October | 15395.20 | 08-OCT-03:03 | 0.00 | 350.63 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
November | 16426.04 | 25-NOV-01:03 | 0.00 | 350.63 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 0.00 |
December | 17536.35 | 20-DEC-21:06 | 0.00 | 2337.56 | 480.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.86 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14944.88 | 0.00 | 350.63 | 216.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17536.35 | 0.00 | 2805.07 | 576.86 | 0.00 | 0.00 | 0.00 | 0.00 | 90.80 | 42.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.16 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 |
April | 0.00 | 01-APR-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 01-JUN-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 |
August | 0.00 | 01-AUG-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.65 |
September | 0.00 | 01-SEP-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 |
November | 0.00 | 01-NOV-00:03 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | |
Maximum of Months | 0.00 | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.120260E+12 | 93519.12 | 04-JAN-17:40 | 0.714372E+10 | 4789.88 | 10-JAN-12:20 |
February | 0.112150E+12 | 94788.57 | 17-FEB-15:50 | 0.645534E+10 | 4788.74 | 03-FEB-12:00 |
March | 0.130740E+12 | 97138.21 | 28-MAR-15:50 | 0.716231E+10 | 4784.33 | 01-MAR-12:00 |
April | 0.129843E+12 | 101167.54 | 01-APR-15:50 | 0.686717E+10 | 4775.47 | 03-APR-11:09 |
May | 0.137048E+12 | 109899.86 | 06-MAY-15:30 | 0.706251E+10 | 4766.85 | 02-MAY-11:50 |
June | 0.135992E+12 | 106910.67 | 13-JUN-14:00 | 0.683053E+10 | 4759.17 | 01-JUN-11:20 |
July | 0.123841E+12 | 95910.58 | 15-JUL-15:00 | 0.700398E+10 | 4755.69 | 31-JUL-11:30 |
August | 0.130223E+12 | 98344.07 | 12-AUG-15:50 | 0.706646E+10 | 4760.67 | 31-AUG-11:00 |
September | 0.123777E+12 | 97014.09 | 02-SEP-15:30 | 0.683738E+10 | 4768.24 | 29-SEP-11:20 |
October | 0.121465E+12 | 93831.72 | 04-OCT-15:20 | 0.707726E+10 | 4777.66 | 31-OCT-11:39 |
November | 0.118028E+12 | 93490.35 | 18-NOV-17:30 | 0.687585E+10 | 4784.48 | 30-NOV-12:20 |
December | 0.120265E+12 | 93110.66 | 08-DEC-17:30 | 0.713926E+10 | 4789.24 | 28-DEC-12:20 |
Annual Sum or Average | 0.150363E+13 | 0.835218E+11 | ||||
Minimum of Months | 0.112150E+12 | 93110.66 | 0.645534E+10 | 4755.69 | ||
Maximum of Months | 0.137048E+12 | 109899.86 | 0.716231E+10 | 4789.88 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.286713E+11 | 0.542825E+10 | 0.163682E+11 | 0.00 | 0.133828E+11 | 0.00 | 0.00 | 0.541572E+11 | 0.00 | 0.00 | 0.225277E+10 | 0.00 | 0.00 |
February | 0.252009E+11 | 0.481116E+10 | 0.148500E+11 | 0.00 | 0.123291E+11 | 0.00 | 0.00 | 0.529137E+11 | 0.00 | 0.00 | 0.204521E+10 | 0.00 | 0.00 |
March | 0.295930E+11 | 0.513008E+10 | 0.167807E+11 | 0.00 | 0.139319E+11 | 0.00 | 0.00 | 0.630113E+11 | 0.00 | 0.00 | 0.229327E+10 | 0.00 | 0.00 |
April | 0.278781E+11 | 0.482221E+10 | 0.159462E+11 | 0.00 | 0.137716E+11 | 0.00 | 0.00 | 0.652224E+11 | 0.00 | 0.00 | 0.220215E+10 | 0.00 | 0.00 |
May | 0.287982E+11 | 0.487929E+10 | 0.165744E+11 | 0.00 | 0.146585E+11 | 0.00 | 0.00 | 0.698648E+11 | 0.00 | 0.00 | 0.227302E+10 | 0.00 | 0.00 |
June | 0.275899E+11 | 0.465502E+10 | 0.162059E+11 | 0.00 | 0.147069E+11 | 0.00 | 0.00 | 0.706172E+11 | 0.00 | 0.00 | 0.221734E+10 | 0.00 | 0.00 |
July | 0.279056E+11 | 0.485700E+10 | 0.163148E+11 | 0.00 | 0.135675E+11 | 0.00 | 0.00 | 0.589386E+11 | 0.00 | 0.00 | 0.225784E+10 | 0.00 | 0.00 |
August | 0.291151E+11 | 0.493224E+10 | 0.167807E+11 | 0.00 | 0.140478E+11 | 0.00 | 0.00 | 0.630540E+11 | 0.00 | 0.00 | 0.229327E+10 | 0.00 | 0.00 |
September | 0.272492E+11 | 0.492253E+10 | 0.159462E+11 | 0.00 | 0.133953E+11 | 0.00 | 0.00 | 0.600619E+11 | 0.00 | 0.00 | 0.220215E+10 | 0.00 | 0.00 |
October | 0.274374E+11 | 0.524712E+10 | 0.163682E+11 | 0.00 | 0.133930E+11 | 0.00 | 0.00 | 0.567663E+11 | 0.00 | 0.00 | 0.225277E+10 | 0.00 | 0.00 |
November | 0.274430E+11 | 0.522831E+10 | 0.158468E+11 | 0.00 | 0.129716E+11 | 0.00 | 0.00 | 0.543669E+11 | 0.00 | 0.00 | 0.217177E+10 | 0.00 | 0.00 |
December | 0.290841E+11 | 0.547102E+10 | 0.163148E+11 | 0.00 | 0.133652E+11 | 0.00 | 0.00 | 0.537716E+11 | 0.00 | 0.00 | 0.225784E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.335966E+12 | 0.603842E+11 | 0.194297E+12 | 0.163521E+12 | 0.00 | 0.722746E+12 | 0.267194E+11 | ||||||
Minimum of Months | 0.252009E+11 | 0.465502E+10 | 0.148500E+11 | 0.00 | 0.123291E+11 | 0.00 | 0.00 | 0.529137E+11 | 0.00 | 0.00 | 0.204521E+10 | 0.00 | 0.00 |
Maximum of Months | 0.295930E+11 | 0.547102E+10 | 0.167807E+11 | 0.00 | 0.147069E+11 | 0.00 | 0.00 | 0.706172E+11 | 0.00 | 0.00 | 0.229327E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.714372E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.645534E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.716231E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.686717E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.706251E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.683053E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.700398E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.706646E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.683738E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.707726E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.687585E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.713926E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.835218E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.645534E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.716231E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28576.57 | 02-JAN-16:10 | 4644.30 | 01-JAN-06:10 | 10740.89 | 02-JAN-09:09 | 0.00 | 10765.70 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28576.57 | 01-FEB-16:40 | 4644.30 | 01-FEB-06:10 | 10740.89 | 01-FEB-09:09 | 0.00 | 10765.70 | 05-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28576.57 | 01-MAR-16:30 | 4644.30 | 01-MAR-06:10 | 10740.89 | 01-MAR-09:09 | 0.00 | 10765.70 | 21-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28576.57 | 01-APR-16:49 | 4644.30 | 01-APR-05:10 | 10740.89 | 01-APR-09:09 | 0.00 | 10765.70 | 09-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28576.57 | 01-MAY-16:49 | 4644.30 | 01-MAY-05:10 | 10740.89 | 01-MAY-08:09 | 0.00 | 11491.46 | 06-MAY-15:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28576.57 | 01-JUN-16:00 | 4644.30 | 01-JUN-05:10 | 10740.89 | 01-JUN-08:09 | 0.00 | 11584.80 | 13-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28576.57 | 01-JUL-16:49 | 4644.30 | 01-JUL-05:10 | 10740.89 | 01-JUL-09:09 | 0.00 | 10765.70 | 23-JUL-08:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28576.57 | 01-AUG-16:49 | 4644.30 | 01-AUG-05:10 | 10740.89 | 01-AUG-08:09 | 0.00 | 10765.70 | 02-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28576.57 | 01-SEP-16:40 | 4644.30 | 01-SEP-05:10 | 10740.89 | 01-SEP-08:09 | 0.00 | 10765.70 | 02-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28576.57 | 02-OCT-16:30 | 4644.30 | 01-OCT-05:10 | 10740.89 | 02-OCT-08:09 | 0.00 | 10765.70 | 01-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28576.57 | 01-NOV-15:00 | 4644.30 | 01-NOV-05:10 | 10740.89 | 01-NOV-08:09 | 0.00 | 10765.70 | 11-NOV-09:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28576.57 | 01-DEC-16:10 | 4644.30 | 01-DEC-17:30 | 10740.89 | 01-DEC-09:09 | 0.00 | 10765.70 | 11-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 28576.57 | 4644.30 | 10740.89 | 0.00 | 10765.70 | 0.00 | 0.00 | |||||
Maximum of Months | 28576.57 | 4644.30 | 10740.89 | 0.00 | 11584.80 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 45467.62 | 05-JAN-15:09 | 0.00 | 0.00 | 1406.23 | 01-JAN-08:09 | 0.00 | 0.00 |
February | 48039.05 | 28-FEB-15:09 | 0.00 | 0.00 | 1406.23 | 01-FEB-06:10 | 0.00 | 0.00 |
March | 50828.36 | 28-MAR-14:00 | 0.00 | 0.00 | 1406.23 | 01-MAR-08:09 | 0.00 | 0.00 |
April | 53333.95 | 01-APR-13:00 | 0.00 | 0.00 | 1406.23 | 03-APR-11:09 | 0.00 | 0.00 |
May | 60306.66 | 06-MAY-14:00 | 0.00 | 0.00 | 1406.23 | 01-MAY-05:10 | 0.00 | 0.00 |
June | 60183.88 | 13-JUN-14:00 | 0.00 | 0.00 | 1406.23 | 01-JUN-07:10 | 0.00 | 0.00 |
July | 48023.59 | 15-JUL-15:00 | 0.00 | 0.00 | 1406.23 | 02-JUL-07:10 | 0.00 | 0.00 |
August | 52298.39 | 11-AUG-14:30 | 0.00 | 0.00 | 1406.23 | 01-AUG-05:10 | 0.00 | 0.00 |
September | 50669.11 | 06-SEP-14:09 | 0.00 | 0.00 | 1406.23 | 01-SEP-05:10 | 0.00 | 0.00 |
October | 47222.20 | 04-OCT-14:30 | 0.00 | 0.00 | 1406.23 | 02-OCT-05:10 | 0.00 | 0.00 |
November | 45716.18 | 18-NOV-12:00 | 0.00 | 0.00 | 1406.23 | 03-NOV-07:10 | 0.00 | 0.00 |
December | 44532.07 | 30-DEC-13:00 | 0.00 | 0.00 | 1406.23 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 44532.07 | 0.00 | 0.00 | 1406.23 | 0.00 | 0.00 | ||
Maximum of Months | 60306.66 | 0.00 | 0.00 | 1406.23 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 93519.12 | 04-JAN-17:40 | 28576.57 | 10740.89 | 4644.30 | 0.00 | 8292.40 | 0.00 | 0.00 | 39858.73 | 0.00 |
February | 94788.57 | 17-FEB-15:50 | 26716.01 | 10740.89 | 0.00 | 0.00 | 8768.61 | 0.00 | 0.00 | 47156.84 | 0.00 |
March | 97138.21 | 28-MAR-15:50 | 26716.01 | 10740.89 | 0.00 | 0.00 | 9252.88 | 0.00 | 0.00 | 49022.22 | 0.00 |
April | 101167.54 | 01-APR-15:50 | 26716.01 | 10740.89 | 0.00 | 0.00 | 9956.60 | 0.00 | 0.00 | 52347.83 | 0.00 |
May | 109899.86 | 06-MAY-15:30 | 26716.01 | 10740.89 | 0.00 | 0.00 | 11483.49 | 0.00 | 0.00 | 59553.26 | 0.00 |
June | 106910.67 | 13-JUN-14:00 | 22994.88 | 10740.89 | 0.00 | 0.00 | 11584.80 | 0.00 | 0.00 | 60183.88 | 0.00 |
July | 95910.58 | 15-JUL-15:00 | 26716.01 | 10740.89 | 0.00 | 0.00 | 9023.86 | 0.00 | 0.00 | 48023.59 | 0.00 |
August | 98344.07 | 12-AUG-15:50 | 26716.01 | 10740.89 | 0.00 | 0.00 | 9693.04 | 0.00 | 0.00 | 49787.91 | 0.00 |
September | 97014.09 | 02-SEP-15:30 | 26716.01 | 10740.89 | 0.00 | 0.00 | 9321.94 | 0.00 | 0.00 | 48829.03 | 0.00 |
October | 93831.72 | 04-OCT-15:20 | 26716.01 | 10740.89 | 0.00 | 0.00 | 8688.54 | 0.00 | 0.00 | 46280.06 | 0.00 |
November | 93490.35 | 18-NOV-17:30 | 28576.57 | 10740.89 | 4644.30 | 0.00 | 8221.94 | 0.00 | 0.00 | 39900.43 | 0.00 |
December | 93110.66 | 08-DEC-17:30 | 28576.57 | 10740.89 | 4644.30 | 0.00 | 8250.10 | 0.00 | 0.00 | 39492.58 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 93110.66 | 22994.88 | 10740.89 | 0.00 | 0.00 | 8221.94 | 0.00 | 0.00 | 39492.58 | 0.00 | |
Maximum of Months | 109899.86 | 28576.57 | 10740.89 | 4644.30 | 0.00 | 11584.80 | 0.00 | 0.00 | 60183.88 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 4789.88 | 10-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 4788.74 | 03-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4784.33 | 01-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4775.47 | 03-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4766.85 | 02-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4759.17 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4755.69 | 31-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4760.67 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4768.24 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4777.66 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 4784.48 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 4789.24 | 28-DEC-12:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4755.69 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4789.88 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 24.55 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 24.59 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 24.67 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 60.50 | 24.77 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 61.50 | 24.84 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 | 24.93 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 69.50 | 24.73 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 53.33 | 24.73 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 55.83 | 24.66 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | 24.59 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 24.56 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 24.53 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 621.83 | 24.70 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 24.53 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 69.50 | 24.93 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 70.33 | 24.92 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 24.96 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 69.33 | 24.96 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 | 24.92 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 68.67 | 24.87 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 24.91 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 71.17 | 24.77 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 59.50 | 24.80 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 64.00 | 24.83 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 | 24.84 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 24.85 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 70.33 | 24.87 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 795.17 | 24.88 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 59.50 | 24.77 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 71.17 | 24.96 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 66.00 | 24.80 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 64.50 | 24.82 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 24.81 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 61.67 | 24.78 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 24.77 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 63.17 | 24.79 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 | 24.66 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 24.69 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 | 24.72 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 56.33 | 24.73 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 59.17 | 24.76 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 64.00 | 24.77 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 743.50 | 24.76 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 24.66 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 24.82 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 408.67 | 23.89 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 405.00 | 23.89 | 0.00 | 0.00 |
May | 9.00 | 23.89 | 418.00 | 23.89 | 9.00 | 23.89 |
June | 0.00 | 0.00 | 408.00 | 23.89 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 415.00 | 23.89 | 0.00 | 0.00 |
August | 17.50 | 23.89 | 422.00 | 23.89 | 17.50 | 23.89 |
September | 1.67 | 23.89 | 405.00 | 23.89 | 1.67 | 23.89 |
October | 9.00 | 23.89 | 414.00 | 23.89 | 9.00 | 23.89 |
November | 0.00 | 0.00 | 399.00 | 23.89 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 412.83 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 37.17 | 23.89 | 4905.50 | 23.89 | 37.17 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 17.50 | 23.89 | 422.00 | 23.89 | 17.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 414.00 | 23.89 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 405.00 | 23.89 | 0.00 | 0.00 |
May | 2.33 | 24.00 | 418.00 | 23.89 | 2.33 | 24.00 |
June | 0.50 | 24.10 | 408.00 | 23.89 | 0.50 | 24.10 |
July | 0.17 | 24.12 | 415.00 | 23.89 | 0.17 | 24.12 |
August | 6.00 | 23.96 | 422.00 | 23.89 | 6.00 | 23.96 |
September | 0.50 | 23.97 | 405.00 | 23.89 | 0.50 | 23.97 |
October | 0.83 | 24.10 | 414.00 | 23.89 | 0.83 | 24.10 |
November | 0.00 | 0.00 | 399.00 | 23.89 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 415.00 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 10.33 | 23.99 | 4913.00 | 23.89 | 10.33 | 23.99 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 24.12 | 422.00 | 23.89 | 6.00 | 24.12 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 414.00 | 23.89 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 0.00 |
April | 2.67 | 23.89 | 405.00 | 23.89 | 2.67 | 23.89 |
May | 15.33 | 23.89 | 418.00 | 23.89 | 15.33 | 23.89 |
June | 7.00 | 23.89 | 408.00 | 23.89 | 7.00 | 23.89 |
July | 2.00 | 23.89 | 415.00 | 23.89 | 2.00 | 23.89 |
August | 22.83 | 23.89 | 422.00 | 23.89 | 22.83 | 23.89 |
September | 6.17 | 23.89 | 405.00 | 23.89 | 6.17 | 23.89 |
October | 13.67 | 23.89 | 414.00 | 23.89 | 13.67 | 23.89 |
November | 0.00 | 0.00 | 399.00 | 23.89 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 415.00 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 69.67 | 23.89 | 4913.00 | 23.89 | 69.67 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 22.83 | 23.89 | 422.00 | 23.89 | 22.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 23.89 | 414.00 | 23.89 | 0.83 | 23.89 |
February | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 0.00 |
April | 7.00 | 23.89 | 405.00 | 23.89 | 7.00 | 23.89 |
May | 55.50 | 23.89 | 418.00 | 23.89 | 55.50 | 23.89 |
June | 25.67 | 23.89 | 408.00 | 23.89 | 25.67 | 23.89 |
July | 6.00 | 23.89 | 415.00 | 23.89 | 6.00 | 23.89 |
August | 76.50 | 23.89 | 422.00 | 23.89 | 76.50 | 23.89 |
September | 33.83 | 23.89 | 405.00 | 23.89 | 33.83 | 23.89 |
October | 35.00 | 23.89 | 414.00 | 23.89 | 35.00 | 23.89 |
November | 1.67 | 23.89 | 399.00 | 23.89 | 1.67 | 23.89 |
December | 1.50 | 23.89 | 415.00 | 23.89 | 1.50 | 23.89 |
Annual Sum or Average | 243.50 | 23.89 | 4913.00 | 23.89 | 243.50 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 376.00 | 23.89 | 0.00 | 0.00 |
Maximum of Months | 76.50 | 23.89 | 422.00 | 23.89 | 76.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.88964 | 51.91310 | 0.55530 | 11.49861 |
February | 376.00000 | 23.88969 | 51.18983 | 0.57617 | 11.99878 |
March | 422.00000 | 23.88951 | 51.78728 | 0.59695 | 12.51704 |
April | 405.00000 | 23.88937 | 53.25223 | 0.62819 | 13.32027 |
May | 418.00000 | 23.88927 | 54.75525 | -0.1725 | 5.75418 |
June | 408.00000 | 23.88923 | 53.36093 | -0.1373 | 5.54608 |
July | 415.00000 | 23.88948 | 52.07938 | -0.2151 | 6.06234 |
August | 422.00000 | 23.88940 | 56.43847 | -0.2194 | 6.12769 |
September | 405.00000 | 23.88948 | 55.78004 | -0.2308 | 6.19285 |
October | 414.00000 | 23.88958 | 56.90291 | 0.58841 | 12.29137 |
November | 399.00000 | 23.88966 | 54.63117 | 0.57839 | 12.04257 |
December | 415.00000 | 23.88965 | 53.29692 | 0.55685 | 11.52814 |
Annual Sum or Average | 4913.00000 | 23.88950 | 53.79900 | 0.25542 | 9.54703 |
Minimum of Months | 376.00000 | 23.88923 | 51.18983 | -0.2308 | 5.54608 |
Maximum of Months | 422.00000 | 23.88969 | 56.90291 | 0.62819 | 13.32027 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.91206 | 48.58657 | 0.56492 | 11.71866 |
February | 376.00000 | 23.91259 | 48.12148 | 0.57946 | 12.07026 |
March | 422.00000 | 23.91289 | 48.17514 | 0.59736 | 12.52188 |
April | 405.00000 | 23.91393 | 50.33048 | 0.61914 | 13.07946 |
May | 418.00000 | 23.91437 | 53.08823 | -0.2074 | 5.96928 |
June | 408.00000 | 23.91407 | 52.59600 | -0.1963 | 5.87607 |
July | 415.00000 | 23.91334 | 50.90635 | -0.2471 | 6.32637 |
August | 422.00000 | 23.91382 | 54.17725 | -0.2295 | 6.18013 |
September | 405.00000 | 23.91380 | 53.22120 | -0.2295 | 6.16625 |
October | 414.00000 | 23.91366 | 53.97612 | 0.59175 | 12.37338 |
November | 399.00000 | 23.91320 | 51.82326 | 0.58288 | 12.15234 |
December | 415.00000 | 23.91191 | 49.99700 | 0.56774 | 11.78485 |
Annual Sum or Average | 4913.00000 | 23.91331 | 51.26973 | 0.24600 | 9.65944 |
Minimum of Months | 376.00000 | 23.91191 | 48.12148 | -0.2471 | 5.87607 |
Maximum of Months | 422.00000 | 23.91437 | 54.17725 | 0.61914 | 13.07946 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.88933 | 48.16026 | 0.68323 | 14.90748 |
February | 376.00000 | 23.88932 | 48.53733 | 0.68987 | 15.09253 |
March | 422.00000 | 23.88928 | 50.46938 | 0.67382 | 14.61187 |
April | 405.00000 | 23.88927 | 53.92858 | 0.67651 | 14.66153 |
May | 418.00000 | 23.88924 | 56.36219 | -0.1280 | 5.45063 |
June | 408.00000 | 23.88920 | 56.19101 | -0.1187 | 5.39912 |
July | 415.00000 | 23.88946 | 53.72155 | -0.1772 | 5.73908 |
August | 422.00000 | 23.88929 | 57.35458 | -0.1632 | 5.67373 |
September | 405.00000 | 23.88932 | 55.71039 | -0.1450 | 5.55841 |
October | 414.00000 | 23.88933 | 55.15959 | 0.66570 | 14.37387 |
November | 399.00000 | 23.88935 | 51.61247 | 0.68223 | 14.85638 |
December | 415.00000 | 23.88934 | 49.18504 | 0.68475 | 14.94348 |
Annual Sum or Average | 4913.00000 | 23.88931 | 53.06633 | 0.33166 | 10.89742 |
Minimum of Months | 376.00000 | 23.88920 | 48.16026 | -0.1772 | 5.39912 |
Maximum of Months | 422.00000 | 23.88946 | 57.35458 | 0.68987 | 15.09253 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.88932 | 49.28887 | 0.66706 | 14.43390 |
February | 376.00000 | 23.88930 | 49.57454 | 0.67366 | 14.61745 |
March | 422.00000 | 23.88928 | 51.93327 | 0.65896 | 14.18678 |
April | 405.00000 | 23.88929 | 55.72999 | 0.66558 | 14.34587 |
May | 418.00000 | 23.88927 | 58.48084 | -0.1466 | 5.54439 |
June | 408.00000 | 23.88924 | 58.12720 | -0.1370 | 5.48836 |
July | 415.00000 | 23.88945 | 55.92358 | -0.1963 | 5.87804 |
August | 422.00000 | 23.88933 | 59.98739 | -0.1787 | 5.76952 |
September | 405.00000 | 23.88934 | 57.95835 | -0.1631 | 5.65959 |
October | 414.00000 | 23.88934 | 57.58013 | 0.65722 | 14.12510 |
November | 399.00000 | 23.88933 | 53.23787 | 0.66911 | 14.46999 |
December | 415.00000 | 23.88934 | 50.45205 | 0.66939 | 14.49272 |
Annual Sum or Average | 4913.00000 | 23.88932 | 54.89655 | 0.31627 | 10.71190 |
Minimum of Months | 376.00000 | 23.88924 | 49.28887 | -0.1963 | 5.48836 |
Maximum of Months | 422.00000 | 23.88945 | 59.98739 | 0.67366 | 14.61745 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.376359E+11 | 0.963209E+10 | 649.30 | 0.275243E+11 | 0.101116E+11 | 0.00 | 1.00 | 02-JAN-21:08 | 0.00 | 01-JAN-00:03 | 51700.29 | 09-JAN-21:08 | 40825.91 | 15-JAN-19:08 | 15215.89 | 09-JAN-21:08 | 12163.01 | 08-JAN-19:06 | 0.00 | 01-JAN-00:03 |
February | 0.380866E+11 | 0.976351E+10 | 593.34 | 0.282442E+11 | 0.984236E+10 | 0.00 | 1.00 | 01-FEB-21:06 | 0.00 | 01-FEB-00:12 | 51397.01 | 15-FEB-21:06 | 41444.20 | 24-FEB-21:07 | 14591.13 | 14-FEB-21:06 | 12261.01 | 26-FEB-19:05 | 0.00 | 01-FEB-00:10 |
March | 0.472742E+11 | 0.121153E+11 | 661.94 | 0.346234E+11 | 0.126508E+11 | 0.00 | 1.00 | 01-MAR-21:06 | 0.00 | 01-MAR-00:12 | 51623.11 | 26-MAR-05:43 | 40294.98 | 13-MAR-21:23 | 14818.58 | 26-MAR-06:23 | 12344.00 | 26-MAR-18:05 | 0.00 | 01-MAR-00:10 |
April | 0.520096E+11 | 0.132213E+11 | 642.48 | 0.366504E+11 | 0.153591E+11 | 0.00 | 1.00 | 01-APR-21:06 | 0.00 | 01-APR-00:33 | 52130.13 | 20-APR-20:43 | 40230.60 | 26-APR-20:42 | 17496.86 | 20-APR-20:43 | 12947.65 | 30-APR-18:43 | 0.00 | 01-APR-00:03 |
May | 0.590927E+11 | 0.148869E+11 | 666.27 | 0.401735E+11 | 0.189193E+11 | 0.00 | 1.00 | 01-MAY-20:06 | 0.00 | 01-MAY-00:33 | 52325.37 | 19-MAY-02:43 | 39578.97 | 31-MAY-20:43 | 18677.47 | 21-MAY-18:10 | 12833.28 | 29-MAY-18:06 | 0.00 | 01-MAY-00:03 |
June | 0.625648E+11 | 0.156739E+11 | 647.44 | 0.432877E+11 | 0.192771E+11 | 0.00 | 1.00 | 01-JUN-02:63 | 0.00 | 01-JUN-00:33 | 52367.31 | 10-JUN-02:43 | 40445.02 | 07-JUN-20:42 | 18303.38 | 28-JUN-20:10 | 12685.75 | 11-JUN-18:42 | 0.00 | 01-JUN-00:03 |
July | 0.506059E+11 | 0.125779E+11 | 663.37 | 0.363331E+11 | 0.142728E+11 | 0.00 | 1.00 | 01-JUL-21:08 | 0.00 | 01-JUL-00:10 | 51909.27 | 07-JUL-20:08 | 41202.67 | 20-JUL-02:63 | 15530.49 | 07-JUL-20:08 | 12356.90 | 30-JUL-18:06 | 0.00 | 01-JUL-00:05 |
August | 0.517020E+11 | 0.127708E+11 | 656.99 | 0.340049E+11 | 0.176970E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:07 | 52256.83 | 21-AUG-20:43 | 40072.00 | 24-AUG-03:23 | 17168.04 | 21-AUG-20:43 | 12382.58 | 27-AUG-18:06 | 0.00 | 01-AUG-00:03 |
September | 0.473662E+11 | 0.117705E+11 | 637.15 | 0.316577E+11 | 0.157084E+11 | 0.00 | 1.00 | 01-SEP-00:43 | 0.00 | 01-SEP-00:33 | 52202.83 | 18-SEP-20:43 | 39317.94 | 12-SEP-03:23 | 17193.96 | 18-SEP-20:08 | 12410.70 | 04-SEP-18:06 | 0.00 | 01-SEP-00:03 |
October | 0.428843E+11 | 0.106432E+11 | 646.04 | 0.281842E+11 | 0.147001E+11 | 0.00 | 1.00 | 01-OCT-04:23 | 0.00 | 01-OCT-00:12 | 52419.56 | 25-OCT-20:10 | 38004.36 | 10-OCT-00:03 | 17416.37 | 25-OCT-20:10 | 12123.36 | 12-OCT-20:06 | 0.00 | 01-OCT-00:10 |
November | 0.397647E+11 | 0.994674E+10 | 628.47 | 0.271796E+11 | 0.125851E+11 | 0.00 | 1.00 | 01-NOV-20:08 | 0.00 | 01-NOV-00:07 | 52281.15 | 11-NOV-19:10 | 37537.90 | 05-NOV-18:06 | 17043.42 | 11-NOV-19:10 | 12221.53 | 19-NOV-19:06 | 0.00 | 01-NOV-00:03 |
December | 0.371473E+11 | 0.942464E+10 | 648.01 | 0.263378E+11 | 0.108095E+11 | 0.00 | 1.00 | 01-DEC-21:08 | 0.00 | 01-DEC-00:13 | 52049.59 | 23-DEC-22:10 | 40922.47 | 20-DEC-21:08 | 16126.56 | 10-DEC-19:06 | 12133.17 | 10-DEC-19:06 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.566134E+12 | 0.142427E+12 | 7740.79 | 0.394201E+12 | 0.171933E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.371473E+11 | 0.942464E+10 | 593.34 | 0.263378E+11 | 0.984236E+10 | 0.00 | 1.00 | 0.00 | 51397.01 | 37537.90 | 14591.13 | 12123.36 | 0.00 | |||||||
Maximum of Months | 0.625648E+11 | 0.156739E+11 | 666.27 | 0.432877E+11 | 0.192771E+11 | 0.00 | 1.00 | 0.00 | 52419.56 | 41444.20 | 18677.47 | 12947.65 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.108997E+12 | 0.311404E+11 | 430.65 | 0.768094E+11 | 0.321876E+11 | 0.00 | 1.00 | 01-JAN-09:02 | 0.00 | 01-JAN-00:03 | 217256.90 | 02-JAN-07:02 | 160650.85 | 05-JAN-06:03 | 80119.41 | 02-JAN-07:04 | 52908.50 | 11-JAN-07:02 | 0.00 | 01-JAN-00:03 |
February | 0.105831E+12 | 0.303610E+11 | 392.69 | 0.750214E+11 | 0.308101E+11 | 0.00 | 1.00 | 01-FEB-07:02 | 0.00 | 01-FEB-00:10 | 215169.36 | 16-FEB-07:02 | 171783.14 | 23-FEB-06:03 | 74536.68 | 16-FEB-07:04 | 54463.78 | 20-FEB-09:02 | 0.00 | 01-FEB-00:10 |
March | 0.127896E+12 | 0.366790E+11 | 442.89 | 0.903421E+11 | 0.375535E+11 | 0.00 | 1.00 | 01-MAR-06:03 | 0.00 | 01-MAR-00:10 | 215658.66 | 25-MAR-06:02 | 164516.92 | 14-MAR-05:02 | 76101.95 | 25-MAR-06:04 | 55310.25 | 26-MAR-08:62 | 0.00 | 01-MAR-00:10 |
April | 0.133340E+12 | 0.378083E+11 | 427.14 | 0.894194E+11 | 0.439208E+11 | 0.00 | 1.00 | 01-APR-05:03 | 0.00 | 01-APR-00:03 | 218011.61 | 15-APR-06:02 | 162782.66 | 27-APR-05:02 | 84418.16 | 15-APR-06:04 | 55435.19 | 30-APR-08:62 | 0.00 | 01-APR-00:03 |
May | 0.141280E+12 | 0.396935E+11 | 441.19 | 0.894927E+11 | 0.517872E+11 | 0.00 | 1.00 | 01-MAY-05:02 | 0.00 | 01-MAY-00:03 | 222786.88 | 22-MAY-06:02 | 156507.71 | 11-MAY-05:03 | 102827.38 | 22-MAY-06:04 | 57619.83 | 28-MAY-07:02 | 0.00 | 01-MAY-00:03 |
June | 0.142305E+12 | 0.397847E+11 | 430.49 | 0.902761E+11 | 0.520293E+11 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:03 | 220115.79 | 29-JUN-06:02 | 157147.61 | 20-JUN-05:02 | 92682.61 | 29-JUN-06:04 | 56062.57 | 18-JUN-08:62 | 0.00 | 01-JUN-00:03 |
July | 0.121513E+12 | 0.339292E+11 | 434.45 | 0.806292E+11 | 0.408838E+11 | 0.00 | 1.00 | 01-JUL-06:02 | 0.00 | 01-JUL-00:05 | 218823.86 | 01-JUL-06:02 | 160336.17 | 06-JUL-05:03 | 86996.64 | 01-JUL-06:04 | 54084.33 | 30-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.133733E+12 | 0.367521E+11 | 444.04 | 0.826671E+11 | 0.510662E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:03 | 221786.43 | 21-AUG-06:02 | 156564.29 | 24-AUG-05:03 | 97125.06 | 21-AUG-06:04 | 55583.42 | 13-AUG-08:62 | 0.00 | 01-AUG-00:03 |
September | 0.126591E+12 | 0.349331E+11 | 425.93 | 0.798800E+11 | 0.467110E+11 | 0.00 | 1.00 | 01-SEP-06:02 | 0.00 | 01-SEP-00:03 | 220025.12 | 17-SEP-08:62 | 158635.50 | 13-SEP-05:03 | 91849.01 | 17-SEP-08:04 | 55239.72 | 10-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 0.119678E+12 | 0.330653E+11 | 434.42 | 0.748823E+11 | 0.447957E+11 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 219623.58 | 12-OCT-06:02 | 155890.70 | 09-OCT-07:03 | 89377.57 | 12-OCT-06:04 | 54760.09 | 29-OCT-08:62 | 0.00 | 01-OCT-00:10 |
November | 0.112253E+12 | 0.312988E+11 | 417.88 | 0.733650E+11 | 0.388879E+11 | 0.00 | 1.00 | 01-NOV-06:02 | 0.00 | 01-NOV-00:03 | 218268.16 | 09-NOV-07:02 | 154182.32 | 03-NOV-05:03 | 84943.46 | 09-NOV-07:04 | 54663.11 | 11-NOV-09:02 | 0.00 | 01-NOV-00:03 |
December | 0.109696E+12 | 0.310357E+11 | 433.23 | 0.751035E+11 | 0.345922E+11 | 0.00 | 1.00 | 01-DEC-07:02 | 0.00 | 01-DEC-00:10 | 217083.54 | 11-DEC-07:02 | 157684.08 | 21-DEC-07:02 | 80417.81 | 10-DEC-09:04 | 54728.61 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.148311E+13 | 0.416481E+12 | 5155.00 | 0.977888E+12 | 0.505225E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.105831E+12 | 0.303610E+11 | 392.69 | 0.733650E+11 | 0.308101E+11 | 0.00 | 1.00 | 0.00 | 215169.36 | 154182.32 | 74536.68 | 52908.50 | 0.00 | |||||||
Maximum of Months | 0.142305E+12 | 0.397847E+11 | 444.04 | 0.903421E+11 | 0.520293E+11 | 0.00 | 1.00 | 0.00 | 222786.88 | 171783.14 | 102827.38 | 57619.83 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.293634E+11 | 0.712608E+10 | 657.82 | 0.216442E+11 | 0.771916E+10 | 0.00 | 1.00 | 02-JAN-21:08 | 0.00 | 01-JAN-00:03 | 27834.56 | 09-JAN-21:08 | 22372.01 | 15-JAN-20:23 | 8564.86 | 09-JAN-21:08 | 6406.09 | 08-JAN-19:06 | 0.00 | 01-JAN-00:03 |
February | 0.276453E+11 | 0.679136E+10 | 596.31 | 0.203535E+11 | 0.729181E+10 | 0.00 | 1.00 | 01-FEB-00:23 | 0.00 | 01-FEB-00:12 | 27738.71 | 14-FEB-21:42 | 22687.96 | 20-FEB-22:23 | 8132.92 | 14-FEB-21:06 | 6459.12 | 26-FEB-19:05 | 0.00 | 01-FEB-00:10 |
March | 0.306790E+11 | 0.758479E+10 | 664.70 | 0.218706E+11 | 0.880842E+10 | 0.00 | 1.00 | 01-MAR-21:06 | 0.00 | 01-MAR-00:12 | 27929.36 | 28-MAR-22:42 | 21410.65 | 13-MAR-22:03 | 8908.84 | 24-MAR-04:43 | 6521.89 | 26-MAR-18:05 | 0.00 | 01-MAR-00:10 |
April | 0.306957E+11 | 0.755758E+10 | 642.53 | 0.203295E+11 | 0.103662E+11 | 0.00 | 1.00 | 01-APR-21:06 | 0.00 | 01-APR-00:33 | 28270.70 | 20-APR-20:10 | 20727.72 | 26-APR-20:42 | 10592.90 | 20-APR-20:10 | 6841.82 | 30-APR-18:43 | 0.00 | 01-APR-00:03 |
May | 0.333110E+11 | 0.811560E+10 | 664.72 | 0.207473E+11 | 0.125637E+11 | 0.00 | 1.00 | 01-MAY-20:06 | 0.00 | 01-MAY-00:33 | 28565.11 | 28-MAY-18:10 | 19686.98 | 11-MAY-03:23 | 11843.05 | 28-MAY-18:10 | 6795.38 | 29-MAY-18:06 | 0.00 | 01-MAY-00:03 |
June | 0.330680E+11 | 0.803373E+10 | 644.13 | 0.205937E+11 | 0.124744E+11 | 0.00 | 1.00 | 01-JUN-02:63 | 0.00 | 01-JUN-00:33 | 28513.40 | 03-JUN-21:08 | 19866.63 | 07-JUN-20:42 | 11365.50 | 03-JUN-21:08 | 6714.90 | 11-JUN-18:42 | 0.00 | 01-JUN-00:03 |
July | 0.275930E+11 | 0.665839E+10 | 655.85 | 0.182667E+11 | 0.932633E+10 | 0.00 | 1.00 | 01-JUL-21:08 | 0.00 | 01-JUL-00:10 | 28125.78 | 07-JUL-20:08 | 20553.93 | 13-JUL-20:08 | 9813.25 | 07-JUL-20:08 | 6542.54 | 30-JUL-18:06 | 0.00 | 01-JUL-00:05 |
August | 0.303583E+11 | 0.724163E+10 | 657.78 | 0.184308E+11 | 0.119275E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:07 | 28430.52 | 05-AUG-21:10 | 19848.67 | 24-AUG-01:23 | 10919.80 | 05-AUG-21:10 | 6556.96 | 27-AUG-18:06 | 0.00 | 01-AUG-00:03 |
September | 0.297312E+11 | 0.712146E+10 | 639.51 | 0.187141E+11 | 0.110172E+11 | 0.00 | 1.00 | 01-SEP-00:43 | 0.00 | 01-SEP-00:33 | 28271.38 | 18-SEP-20:08 | 20005.49 | 12-SEP-04:03 | 10379.36 | 18-SEP-20:08 | 6561.79 | 04-SEP-18:06 | 0.00 | 01-SEP-00:03 |
October | 0.293986E+11 | 0.699454E+10 | 654.72 | 0.186659E+11 | 0.107326E+11 | 0.00 | 1.00 | 01-OCT-04:23 | 0.00 | 01-OCT-00:12 | 28187.79 | 14-OCT-21:08 | 20208.63 | 11-OCT-02:63 | 10148.71 | 14-OCT-21:08 | 6400.47 | 15-OCT-18:06 | 0.00 | 01-OCT-00:10 |
November | 0.292286E+11 | 0.698622E+10 | 634.20 | 0.197539E+11 | 0.947471E+10 | 0.00 | 1.00 | 01-NOV-20:08 | 0.00 | 01-NOV-00:07 | 28068.39 | 11-NOV-19:08 | 21084.82 | 24-NOV-03:43 | 9652.38 | 12-NOV-19:08 | 6440.40 | 19-NOV-19:06 | 0.00 | 01-NOV-00:03 |
December | 0.295199E+11 | 0.708518E+10 | 657.17 | 0.211402E+11 | 0.837973E+10 | 0.00 | 1.00 | 01-DEC-21:06 | 0.00 | 01-DEC-00:13 | 28190.61 | 09-DEC-22:08 | 22257.26 | 26-DEC-21:42 | 9994.85 | 09-DEC-22:08 | 6392.38 | 10-DEC-19:06 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.360592E+12 | 0.872966E+11 | 7769.45 | 0.240510E+12 | 0.120082E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.275930E+11 | 0.665839E+10 | 596.31 | 0.182667E+11 | 0.729181E+10 | 0.00 | 1.00 | 0.00 | 27738.71 | 19686.98 | 8132.92 | 6392.38 | 0.00 | |||||||
Maximum of Months | 0.333110E+11 | 0.811560E+10 | 664.72 | 0.218706E+11 | 0.125637E+11 | 0.00 | 1.00 | 0.00 | 28565.11 | 22687.96 | 11843.05 | 6841.82 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.258626E+11 | 0.625864E+10 | 658.15 | 0.183413E+11 | 0.752126E+10 | 0.00 | 1.00 | 02-JAN-21:08 | 0.00 | 01-JAN-00:03 | 24895.86 | 09-JAN-21:08 | 19274.88 | 15-JAN-20:23 | 8730.15 | 09-JAN-21:08 | 5690.87 | 08-JAN-19:06 | 0.00 | 01-JAN-00:03 |
February | 0.245050E+11 | 0.599791E+10 | 596.63 | 0.173723E+11 | 0.713269E+10 | 0.00 | 1.00 | 01-FEB-00:23 | 0.00 | 01-FEB-00:12 | 24755.99 | 14-FEB-21:42 | 19607.02 | 20-FEB-22:23 | 8219.63 | 14-FEB-21:06 | 5736.75 | 26-FEB-19:05 | 0.00 | 01-FEB-00:10 |
March | 0.269271E+11 | 0.663224E+10 | 664.21 | 0.184088E+11 | 0.851831E+10 | 0.00 | 1.00 | 01-MAR-21:06 | 0.00 | 01-MAR-00:12 | 24901.49 | 28-MAR-22:42 | 18298.96 | 13-MAR-22:03 | 8727.55 | 25-MAR-04:03 | 5792.33 | 26-MAR-18:05 | 0.00 | 01-MAR-00:10 |
April | 0.271412E+11 | 0.663521E+10 | 642.19 | 0.171116E+11 | 0.100295E+11 | 0.00 | 1.00 | 01-APR-21:06 | 0.00 | 01-APR-00:33 | 25358.77 | 20-APR-20:10 | 17547.42 | 26-APR-20:42 | 10661.26 | 20-APR-20:10 | 6077.51 | 30-APR-18:43 | 0.00 | 01-APR-00:03 |
May | 0.296860E+11 | 0.716873E+10 | 664.88 | 0.175018E+11 | 0.121842E+11 | 0.00 | 1.00 | 01-MAY-20:06 | 0.00 | 01-MAY-00:33 | 25549.49 | 28-MAY-18:10 | 16588.43 | 11-MAY-02:43 | 11908.02 | 21-MAY-18:10 | 6032.74 | 29-MAY-18:06 | 0.00 | 01-MAY-00:03 |
June | 0.295954E+11 | 0.712481E+10 | 644.24 | 0.174533E+11 | 0.121421E+11 | 0.00 | 1.00 | 01-JUN-02:63 | 0.00 | 01-JUN-00:33 | 25559.54 | 28-JUN-20:10 | 16776.39 | 27-JUN-01:23 | 11336.06 | 28-JUN-20:10 | 5959.52 | 11-JUN-18:42 | 0.00 | 01-JUN-00:03 |
July | 0.240149E+11 | 0.577309E+10 | 656.13 | 0.150725E+11 | 0.894239E+10 | 0.00 | 1.00 | 01-JUL-21:08 | 0.00 | 01-JUL-00:10 | 25208.77 | 07-JUL-20:08 | 17543.33 | 03-JUL-00:03 | 10081.89 | 07-JUL-20:08 | 5810.42 | 30-JUL-18:06 | 0.00 | 01-JUL-00:05 |
August | 0.265607E+11 | 0.628944E+10 | 654.35 | 0.151513E+11 | 0.114094E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:07 | 25424.57 | 05-AUG-21:10 | 16861.85 | 28-AUG-04:03 | 10823.69 | 03-AUG-20:08 | 5822.18 | 27-AUG-18:06 | 0.00 | 01-AUG-00:03 |
September | 0.262192E+11 | 0.623684E+10 | 638.37 | 0.155892E+11 | 0.106300E+11 | 0.00 | 1.00 | 01-SEP-00:43 | 0.00 | 01-SEP-00:33 | 25361.05 | 18-SEP-20:08 | 16970.83 | 12-SEP-04:03 | 10651.08 | 18-SEP-20:08 | 5826.07 | 04-SEP-18:06 | 0.00 | 01-SEP-00:03 |
October | 0.256345E+11 | 0.606321E+10 | 651.40 | 0.153590E+11 | 0.102755E+11 | 0.00 | 1.00 | 01-OCT-04:23 | 0.00 | 01-OCT-00:12 | 25260.84 | 25-OCT-20:08 | 17163.53 | 08-OCT-03:03 | 10258.07 | 25-OCT-20:08 | 5686.43 | 15-OCT-18:06 | 0.00 | 01-OCT-00:10 |
November | 0.257906E+11 | 0.613514E+10 | 634.13 | 0.165912E+11 | 0.919937E+10 | 0.00 | 1.00 | 01-NOV-20:08 | 0.00 | 01-NOV-00:07 | 25090.38 | 30-NOV-21:08 | 18358.22 | 24-NOV-03:43 | 9586.64 | 08-NOV-21:10 | 5722.13 | 19-NOV-19:06 | 0.00 | 01-NOV-00:03 |
December | 0.260233E+11 | 0.622610E+10 | 657.57 | 0.178634E+11 | 0.815990E+10 | 0.00 | 1.00 | 01-DEC-21:06 | 0.00 | 01-DEC-00:13 | 25165.53 | 09-DEC-22:08 | 18984.66 | 26-DEC-22:23 | 9817.19 | 09-DEC-22:08 | 5677.91 | 10-DEC-19:06 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.317960E+12 | 0.765413E+11 | 7762.28 | 0.201816E+12 | 0.116145E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.240149E+11 | 0.577309E+10 | 596.63 | 0.150725E+11 | 0.713269E+10 | 0.00 | 1.00 | 0.00 | 24755.99 | 16588.43 | 8219.63 | 5677.91 | 0.00 | |||||||
Maximum of Months | 0.296860E+11 | 0.716873E+10 | 664.88 | 0.184088E+11 | 0.121842E+11 | 0.00 | 1.00 | 0.00 | 25559.54 | 19607.02 | 11908.02 | 6077.51 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 51.48 | 24.60 | 26.87 | 94.70 | 15.66 | 0.00 | 0.00 | 744.00 |
February | 59.56 | 30.94 | 28.62 | 111.29 | 16.16 | 0.00 | 0.00 | 672.00 |
March | 69.02 | 40.47 | 28.55 | 129.77 | 13.46 | 0.00 | 0.00 | 744.00 |
April | 69.91 | 39.19 | 30.72 | 132.08 | 9.51 | 0.00 | 0.00 | 720.00 |
May | 58.46 | 25.41 | 33.05 | 112.05 | 7.89 | 0.00 | 0.00 | 744.00 |
June | 63.18 | 31.25 | 31.93 | 120.71 | 7.82 | 0.00 | 0.00 | 720.00 |
July | 53.17 | 17.62 | 35.55 | 99.99 | 10.10 | 0.00 | 0.00 | 744.00 |
August | 58.73 | 25.21 | 33.52 | 106.83 | 9.51 | 0.00 | 0.00 | 744.00 |
September | 54.25 | 21.04 | 33.20 | 102.16 | 9.07 | 0.00 | 0.00 | 720.00 |
October | 49.57 | 17.53 | 32.03 | 90.01 | 9.59 | 0.00 | 0.00 | 744.00 |
November | 47.40 | 17.98 | 29.42 | 87.29 | 11.97 | 0.00 | 0.00 | 720.00 |
December | 47.80 | 21.45 | 26.35 | 87.70 | 16.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 56.83 | 26.00 | 30.83 | 106.13 | 11.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 47.40 | 17.53 | 26.35 | 87.29 | 7.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.91 | 40.47 | 35.55 | 132.08 | 16.20 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 760.57 | 317.25 | 443.32 | 1356.16 | 144.13 | 0.00 | 0.00 | 744.00 |
February | 645.80 | 210.46 | 435.34 | 1171.46 | 114.81 | 0.00 | 0.00 | 672.00 |
March | 440.55 | 58.94 | 381.61 | 835.18 | 76.88 | 0.00 | 0.00 | 744.00 |
April | 328.64 | 0.14 | 328.50 | 743.79 | 24.66 | 0.00 | 0.00 | 720.00 |
May | 328.87 | 0.00 | 328.87 | 776.23 | 31.78 | 0.00 | 0.00 | 744.00 |
June | 327.69 | 0.00 | 327.69 | 761.95 | 34.45 | 0.00 | 0.00 | 720.00 |
July | 337.57 | 0.00 | 337.57 | 690.65 | 67.57 | 0.00 | 0.00 | 744.00 |
August | 328.62 | 0.50 | 328.12 | 665.80 | 51.47 | 0.00 | 0.00 | 744.00 |
September | 363.73 | 11.79 | 351.93 | 729.31 | 54.25 | 0.00 | 0.00 | 720.00 |
October | 475.88 | 75.80 | 400.08 | 853.54 | 72.68 | 0.00 | 0.00 | 744.00 |
November | 618.83 | 188.73 | 430.10 | 1113.36 | 98.81 | 0.00 | 0.00 | 720.00 |
December | 760.22 | 323.39 | 436.82 | 1354.06 | 163.66 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 475.75 | 98.53 | 377.22 | 919.82 | 77.90 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 327.69 | 0.00 | 327.69 | 665.80 | 24.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 760.57 | 323.39 | 443.32 | 1356.16 | 163.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 760.57 | 317.25 | 443.32 | 1350.55 | 139.77 | 0.00 | 0.00 | 744.00 |
February | 645.80 | 210.46 | 435.34 | 1165.63 | 110.31 | 0.00 | 0.00 | 672.00 |
March | 440.55 | 58.94 | 381.61 | 830.09 | 71.36 | 0.00 | 0.00 | 744.00 |
April | 328.64 | 0.14 | 328.50 | 740.22 | 21.32 | 0.00 | 0.00 | 720.00 |
May | 328.87 | 0.00 | 328.87 | 773.16 | 29.70 | 0.00 | 0.00 | 744.00 |
June | 327.69 | 0.00 | 327.69 | 757.79 | 32.10 | 0.00 | 0.00 | 720.00 |
July | 337.57 | 0.00 | 337.57 | 685.63 | 64.27 | 0.00 | 0.00 | 744.00 |
August | 328.62 | 0.50 | 328.12 | 661.39 | 47.91 | 0.00 | 0.00 | 744.00 |
September | 363.73 | 11.79 | 351.93 | 724.36 | 51.12 | 0.00 | 0.00 | 720.00 |
October | 475.88 | 75.80 | 400.08 | 849.62 | 68.75 | 0.00 | 0.00 | 744.00 |
November | 618.83 | 188.73 | 430.10 | 1108.33 | 95.49 | 0.00 | 0.00 | 720.00 |
December | 760.22 | 323.39 | 436.82 | 1348.66 | 159.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 475.75 | 98.53 | 377.22 | 915.15 | 74.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 327.69 | 0.00 | 327.69 | 661.39 | 21.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 760.57 | 323.39 | 443.32 | 1350.55 | 159.86 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.50 | 65.28 | 91.22 | 243.10 | 51.66 | 0.00 | 0.00 | 744.00 |
February | 132.88 | 43.30 | 89.58 | 202.43 | 47.18 | 0.00 | 0.00 | 672.00 |
March | 90.65 | 12.13 | 78.52 | 133.24 | 37.18 | 0.00 | 0.00 | 744.00 |
April | 67.62 | 0.03 | 67.59 | 109.98 | 21.27 | 0.50 | 0.00 | 720.00 |
May | 67.67 | 0.00 | 67.67 | 114.00 | 21.37 | 71.33 | 0.00 | 744.00 |
June | 67.43 | 0.00 | 67.43 | 112.22 | 23.23 | 19.83 | 0.00 | 720.00 |
July | 69.46 | 0.00 | 69.46 | 110.54 | 28.25 | 0.17 | 0.00 | 744.00 |
August | 67.62 | 0.10 | 67.52 | 104.71 | 24.90 | 2.17 | 0.00 | 744.00 |
September | 74.84 | 2.43 | 72.42 | 116.75 | 26.74 | 0.00 | 0.00 | 720.00 |
October | 97.92 | 15.60 | 82.32 | 145.20 | 31.09 | 6.33 | 0.00 | 744.00 |
November | 127.33 | 38.83 | 88.50 | 196.34 | 38.97 | 1.50 | 0.00 | 720.00 |
December | 156.43 | 66.54 | 89.88 | 244.21 | 54.58 | 4.33 | 0.00 | 744.00 |
Annual Sum or Average | 97.89 | 20.27 | 77.62 | 152.53 | 33.83 | 106.17 | 0.00 | 8760.00 |
Minimum of Months | 67.43 | 0.00 | 67.43 | 104.71 | 21.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 156.50 | 66.54 | 91.22 | 244.21 | 54.58 | 71.33 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137880E+09 | 65900751.52 | 71979161.62 | 0.253634E+09 | 41934238.27 |
February | 0.144080E+09 | 74845188.53 | 69234425.20 | 0.269232E+09 | 39099333.96 |
March | 0.184855E+09 | 0.108394E+09 | 76460310.64 | 0.347586E+09 | 36061438.42 |
April | 0.181195E+09 | 0.101580E+09 | 79614572.63 | 0.342346E+09 | 24648131.23 |
May | 0.156579E+09 | 68061816.42 | 88517511.72 | 0.300127E+09 | 21144033.71 |
June | 0.163763E+09 | 81002897.36 | 82760400.86 | 0.312875E+09 | 20279395.37 |
July | 0.142404E+09 | 47181750.13 | 95222722.00 | 0.267814E+09 | 27047779.09 |
August | 0.157304E+09 | 67517222.42 | 89786812.35 | 0.286143E+09 | 25473593.44 |
September | 0.140608E+09 | 54547568.78 | 86060242.95 | 0.264792E+09 | 23505615.36 |
October | 0.132758E+09 | 46963125.99 | 85794815.63 | 0.241077E+09 | 25686816.75 |
November | 0.122871E+09 | 46612963.54 | 76258359.00 | 0.226254E+09 | 31024819.78 |
December | 0.128016E+09 | 57441806.01 | 70574012.10 | 0.234908E+09 | 43402122.64 |
Annual Sum or Average | 0.179231E+10 | 0.820050E+09 | 0.972263E+09 | 0.334679E+10 | 0.359307E+09 |
Minimum of Months | 0.122871E+09 | 46612963.54 | 69234425.20 | 0.226254E+09 | 20279395.37 |
Maximum of Months | 0.184855E+09 | 0.108394E+09 | 95222722.00 | 0.347586E+09 | 43402122.64 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203710E+10 | 0.849714E+09 | 0.118739E+10 | 0.363234E+10 | 0.386037E+09 |
February | 0.156231E+10 | 0.509141E+09 | 0.105317E+10 | 0.283400E+10 | 0.277754E+09 |
March | 0.117998E+10 | 0.157865E+09 | 0.102212E+10 | 0.223694E+10 | 0.205925E+09 |
April | 0.851845E+09 | 366780.05 | 0.851479E+09 | 0.192791E+10 | 63915956.27 |
May | 0.880858E+09 | 0.00 | 0.880858E+09 | 0.207905E+10 | 85116611.62 |
June | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.197498E+10 | 89305116.77 |
July | 0.904149E+09 | 0.00 | 0.904149E+09 | 0.184984E+10 | 0.180991E+09 |
August | 0.880174E+09 | 1338165.35 | 0.878836E+09 | 0.178329E+10 | 0.137863E+09 |
September | 0.942779E+09 | 30571648.28 | 0.912207E+09 | 0.189036E+10 | 0.140615E+09 |
October | 0.127460E+10 | 0.203015E+09 | 0.107159E+10 | 0.228611E+10 | 0.194667E+09 |
November | 0.160401E+10 | 0.489193E+09 | 0.111482E+10 | 0.288584E+10 | 0.256104E+09 |
December | 0.203616E+10 | 0.866177E+09 | 0.116999E+10 | 0.362671E+10 | 0.438346E+09 |
Annual Sum or Average | 0.150034E+11 | 0.310738E+10 | 0.118960E+11 | 0.290074E+11 | 0.245664E+10 |
Minimum of Months | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.178329E+10 | 63915956.27 |
Maximum of Months | 0.203710E+10 | 0.866177E+09 | 0.118739E+10 | 0.363234E+10 | 0.438346E+09 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203710E+10 | 0.849714E+09 | 0.118739E+10 | 0.361730E+10 | 0.374358E+09 |
February | 0.156231E+10 | 0.509141E+09 | 0.105317E+10 | 0.281989E+10 | 0.266872E+09 |
March | 0.117998E+10 | 0.157865E+09 | 0.102212E+10 | 0.222333E+10 | 0.191126E+09 |
April | 0.851845E+09 | 366780.05 | 0.851479E+09 | 0.191865E+10 | 55273379.02 |
May | 0.880858E+09 | 0.00 | 0.880858E+09 | 0.207084E+10 | 79543495.44 |
June | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.196419E+10 | 83204567.29 |
July | 0.904149E+09 | 0.00 | 0.904149E+09 | 0.183640E+10 | 0.172147E+09 |
August | 0.880174E+09 | 1338165.35 | 0.878836E+09 | 0.177146E+10 | 0.128321E+09 |
September | 0.942779E+09 | 30571648.28 | 0.912207E+09 | 0.187753E+10 | 0.132510E+09 |
October | 0.127460E+10 | 0.203015E+09 | 0.107159E+10 | 0.227563E+10 | 0.184148E+09 |
November | 0.160401E+10 | 0.489193E+09 | 0.111482E+10 | 0.287278E+10 | 0.247512E+09 |
December | 0.203616E+10 | 0.866177E+09 | 0.116999E+10 | 0.361225E+10 | 0.428158E+09 |
Annual Sum or Average | 0.150034E+11 | 0.310738E+10 | 0.118960E+11 | 0.288602E+11 | 0.234317E+10 |
Minimum of Months | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.177146E+10 | 55273379.02 |
Maximum of Months | 0.203710E+10 | 0.866177E+09 | 0.118739E+10 | 0.361730E+10 | 0.428158E+09 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.419164E+09 | 0.174841E+09 | 0.244323E+09 | 0.651123E+09 | 0.138361E+09 |
February | 0.321469E+09 | 0.104763E+09 | 0.216705E+09 | 0.489720E+09 | 0.114139E+09 |
March | 0.242798E+09 | 32482927.03 | 0.210315E+09 | 0.356880E+09 | 99595987.08 |
April | 0.175280E+09 | 75470.34 | 0.175204E+09 | 0.285080E+09 | 55134914.48 |
May | 0.181249E+09 | 0.00 | 0.181249E+09 | 0.305339E+09 | 57246782.82 |
June | 0.174771E+09 | 0.00 | 0.174771E+09 | 0.290866E+09 | 60199975.57 |
July | 0.186042E+09 | 0.00 | 0.186042E+09 | 0.296067E+09 | 75663388.91 |
August | 0.181109E+09 | 275347.01 | 0.180833E+09 | 0.280458E+09 | 66694677.59 |
September | 0.193990E+09 | 6290561.79 | 0.187700E+09 | 0.302628E+09 | 69312333.08 |
October | 0.262268E+09 | 41773245.91 | 0.220495E+09 | 0.388915E+09 | 83263226.58 |
November | 0.330048E+09 | 0.100659E+09 | 0.229390E+09 | 0.508915E+09 | 0.100999E+09 |
December | 0.418970E+09 | 0.178229E+09 | 0.240742E+09 | 0.654086E+09 | 0.146190E+09 |
Annual Sum or Average | 0.308716E+10 | 0.639389E+09 | 0.244777E+10 | 0.481008E+10 | 0.106680E+10 |
Minimum of Months | 0.174771E+09 | 0.00 | 0.174771E+09 | 0.280458E+09 | 55134914.48 |
Maximum of Months | 0.419164E+09 | 0.178229E+09 | 0.244323E+09 | 0.654086E+09 | 0.146190E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1515.14 | 250.50 | 823.66 | 393.67 | 429.98 | 0.00 | 0.00 |
February | 1780.64 | 258.59 | 952.91 | 495.01 | 457.90 | 0.00 | 0.00 |
March | 2076.38 | 215.42 | 1104.27 | 647.52 | 456.75 | 0.00 | 0.00 |
April | 2113.25 | 152.15 | 1118.49 | 627.04 | 491.45 | 0.00 | 0.00 |
May | 1792.87 | 126.31 | 935.36 | 406.58 | 528.78 | 0.00 | 0.00 |
June | 1931.33 | 125.18 | 1010.88 | 500.02 | 510.87 | 0.00 | 0.00 |
July | 1599.85 | 161.58 | 850.68 | 281.85 | 568.83 | 0.00 | 0.00 |
August | 1709.34 | 152.17 | 939.69 | 403.33 | 536.36 | 0.00 | 0.00 |
September | 1634.52 | 145.10 | 867.95 | 336.71 | 531.24 | 0.00 | 0.00 |
October | 1440.13 | 153.45 | 793.06 | 280.54 | 512.51 | 0.00 | 0.00 |
November | 1396.63 | 191.51 | 758.46 | 287.73 | 470.73 | 0.00 | 0.00 |
December | 1403.27 | 259.27 | 764.73 | 343.14 | 421.59 | 0.00 | 0.00 |
Annual Sum or Average | 1698.02 | 182.30 | 909.34 | 416.06 | 493.28 | 0.00 | 0.00 |
Minimum of Months | 1396.63 | 125.18 | 758.46 | 280.54 | 421.59 | 0.00 | 0.00 |
Maximum of Months | 2113.25 | 259.27 | 1118.49 | 647.52 | 568.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1356.16 | 144.13 | 760.57 | 317.25 | 443.32 | 0.00 | 0.00 |
February | 1171.46 | 114.81 | 645.80 | 210.46 | 435.34 | 0.00 | 0.00 |
March | 835.18 | 76.88 | 440.55 | 58.94 | 381.61 | 0.00 | 0.00 |
April | 743.79 | 24.66 | 328.64 | 0.14 | 328.50 | 0.00 | 0.00 |
May | 776.23 | 31.78 | 328.87 | 0.00 | 328.87 | 0.00 | 0.00 |
June | 761.95 | 34.45 | 327.69 | 0.00 | 327.69 | 0.00 | 0.00 |
July | 690.65 | 67.57 | 337.57 | 0.00 | 337.57 | 0.00 | 0.00 |
August | 665.80 | 51.47 | 328.62 | 0.50 | 328.12 | 0.00 | 0.00 |
September | 729.31 | 54.25 | 363.73 | 11.79 | 351.93 | 0.00 | 0.00 |
October | 853.54 | 72.68 | 475.88 | 75.80 | 400.08 | 0.00 | 0.00 |
November | 1113.36 | 98.81 | 618.83 | 188.73 | 430.10 | 0.00 | 0.00 |
December | 1354.06 | 163.66 | 760.22 | 323.39 | 436.82 | 0.00 | 0.00 |
Annual Sum or Average | 919.82 | 77.90 | 475.75 | 98.53 | 377.22 | 0.00 | 0.00 |
Minimum of Months | 665.80 | 24.66 | 327.69 | 0.00 | 327.69 | 0.00 | 0.00 |
Maximum of Months | 1356.16 | 163.66 | 760.57 | 323.39 | 443.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1350.55 | 139.77 | 760.57 | 317.25 | 443.32 | 0.00 | 0.00 |
February | 1165.63 | 110.31 | 645.80 | 210.46 | 435.34 | 0.00 | 0.00 |
March | 830.09 | 71.36 | 440.55 | 58.94 | 381.61 | 0.00 | 0.00 |
April | 740.22 | 21.32 | 328.64 | 0.14 | 328.50 | 0.00 | 0.00 |
May | 773.16 | 29.70 | 328.87 | 0.00 | 328.87 | 0.00 | 0.00 |
June | 757.79 | 32.10 | 327.69 | 0.00 | 327.69 | 0.00 | 0.00 |
July | 685.63 | 64.27 | 337.57 | 0.00 | 337.57 | 0.00 | 0.00 |
August | 661.39 | 47.91 | 328.62 | 0.50 | 328.12 | 0.00 | 0.00 |
September | 724.36 | 51.12 | 363.73 | 11.79 | 351.93 | 0.00 | 0.00 |
October | 849.62 | 68.75 | 475.88 | 75.80 | 400.08 | 0.00 | 0.00 |
November | 1108.33 | 95.49 | 618.83 | 188.73 | 430.10 | 0.00 | 0.00 |
December | 1348.66 | 159.86 | 760.22 | 323.39 | 436.82 | 0.00 | 0.00 |
Annual Sum or Average | 915.15 | 74.30 | 475.75 | 98.53 | 377.22 | 0.00 | 0.00 |
Minimum of Months | 661.39 | 21.32 | 327.69 | 0.00 | 327.69 | 0.00 | 0.00 |
Maximum of Months | 1350.55 | 159.86 | 760.57 | 323.39 | 443.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 243.10 | 51.66 | 156.50 | 65.28 | 91.22 | 0.00 | 0.00 |
February | 202.43 | 47.18 | 132.88 | 43.30 | 89.58 | 0.00 | 0.00 |
March | 133.24 | 37.18 | 90.65 | 12.13 | 78.52 | 0.00 | 0.00 |
April | 109.98 | 21.27 | 67.62 | 0.03 | 67.59 | 0.00 | 0.00 |
May | 114.00 | 21.37 | 67.67 | 0.00 | 67.67 | 0.00 | 0.00 |
June | 112.22 | 23.23 | 67.43 | 0.00 | 67.43 | 0.00 | 0.00 |
July | 110.54 | 28.25 | 69.46 | 0.00 | 69.46 | 0.00 | 0.00 |
August | 104.71 | 24.90 | 67.62 | 0.10 | 67.52 | 0.00 | 0.00 |
September | 116.75 | 26.74 | 74.84 | 2.43 | 72.42 | 0.00 | 0.00 |
October | 145.20 | 31.09 | 97.92 | 15.60 | 82.32 | 0.00 | 0.00 |
November | 196.34 | 38.97 | 127.33 | 38.83 | 88.50 | 0.00 | 0.00 |
December | 244.21 | 54.58 | 156.43 | 66.54 | 89.88 | 0.00 | 0.00 |
Annual Sum or Average | 152.53 | 33.83 | 97.89 | 20.27 | 77.62 | 0.00 | 0.00 |
Minimum of Months | 104.71 | 21.27 | 67.43 | 0.00 | 67.43 | 0.00 | 0.00 |
Maximum of Months | 244.21 | 54.58 | 156.50 | 66.54 | 91.22 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.405814E+10 | 0.670948E+09 | 0.220608E+10 | 0.105441E+10 | 0.115167E+10 | 0.00 | 0.00 |
February | 0.430771E+10 | 0.625589E+09 | 0.230527E+10 | 0.119752E+10 | 0.110775E+10 | 0.00 | 0.00 |
March | 0.556138E+10 | 0.576983E+09 | 0.295768E+10 | 0.173431E+10 | 0.122336E+10 | 0.00 | 0.00 |
April | 0.547754E+10 | 0.394370E+09 | 0.289912E+10 | 0.162528E+10 | 0.127383E+10 | 0.00 | 0.00 |
May | 0.480203E+10 | 0.338305E+09 | 0.250527E+10 | 0.108899E+10 | 0.141628E+10 | 0.00 | 0.00 |
June | 0.500600E+10 | 0.324470E+09 | 0.262021E+10 | 0.129605E+10 | 0.132417E+10 | 0.00 | 0.00 |
July | 0.428503E+10 | 0.432764E+09 | 0.227847E+10 | 0.754908E+09 | 0.152356E+10 | 0.00 | 0.00 |
August | 0.457829E+10 | 0.407577E+09 | 0.251686E+10 | 0.108028E+10 | 0.143659E+10 | 0.00 | 0.00 |
September | 0.423667E+10 | 0.376090E+09 | 0.224972E+10 | 0.872761E+09 | 0.137696E+10 | 0.00 | 0.00 |
October | 0.385724E+10 | 0.410989E+09 | 0.212413E+10 | 0.751410E+09 | 0.137272E+10 | 0.00 | 0.00 |
November | 0.362007E+10 | 0.496397E+09 | 0.196594E+10 | 0.745807E+09 | 0.122013E+10 | 0.00 | 0.00 |
December | 0.375852E+10 | 0.694434E+09 | 0.204825E+10 | 0.919069E+09 | 0.112918E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.535486E+11 | 0.574892E+10 | 0.286770E+11 | 0.131208E+11 | 0.155562E+11 | 0.00 | 0.00 |
Minimum of Months | 0.362007E+10 | 0.324470E+09 | 0.196594E+10 | 0.745807E+09 | 0.110775E+10 | 0.00 | 0.00 |
Maximum of Months | 0.556138E+10 | 0.694434E+09 | 0.295768E+10 | 0.173431E+10 | 0.152356E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.363234E+10 | 0.386037E+09 | 0.203710E+10 | 0.849714E+09 | 0.118739E+10 | 0.00 | 0.00 |
February | 0.283400E+10 | 0.277754E+09 | 0.156231E+10 | 0.509141E+09 | 0.105317E+10 | 0.00 | 0.00 |
March | 0.223694E+10 | 0.205925E+09 | 0.117998E+10 | 0.157865E+09 | 0.102212E+10 | 0.00 | 0.00 |
April | 0.192791E+10 | 63915956.27 | 0.851845E+09 | 366780.05 | 0.851479E+09 | 0.00 | 0.00 |
May | 0.207905E+10 | 85116611.62 | 0.880858E+09 | 0.00 | 0.880858E+09 | 0.00 | 0.00 |
June | 0.197498E+10 | 89305116.77 | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.00 | 0.00 |
July | 0.184984E+10 | 0.180991E+09 | 0.904149E+09 | 0.00 | 0.904149E+09 | 0.00 | 0.00 |
August | 0.178329E+10 | 0.137863E+09 | 0.880174E+09 | 1338165.35 | 0.878836E+09 | 0.00 | 0.00 |
September | 0.189036E+10 | 0.140615E+09 | 0.942779E+09 | 30571648.28 | 0.912207E+09 | 0.00 | 0.00 |
October | 0.228611E+10 | 0.194667E+09 | 0.127460E+10 | 0.203015E+09 | 0.107159E+10 | 0.00 | 0.00 |
November | 0.288584E+10 | 0.256104E+09 | 0.160401E+10 | 0.489193E+09 | 0.111482E+10 | 0.00 | 0.00 |
December | 0.362671E+10 | 0.438346E+09 | 0.203616E+10 | 0.866177E+09 | 0.116999E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.290074E+11 | 0.245664E+10 | 0.150034E+11 | 0.310738E+10 | 0.118960E+11 | 0.00 | 0.00 |
Minimum of Months | 0.178329E+10 | 63915956.27 | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.00 | 0.00 |
Maximum of Months | 0.363234E+10 | 0.438346E+09 | 0.203710E+10 | 0.866177E+09 | 0.118739E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.361730E+10 | 0.374358E+09 | 0.203710E+10 | 0.849714E+09 | 0.118739E+10 | 0.00 | 0.00 |
February | 0.281989E+10 | 0.266872E+09 | 0.156231E+10 | 0.509141E+09 | 0.105317E+10 | 0.00 | 0.00 |
March | 0.222333E+10 | 0.191126E+09 | 0.117998E+10 | 0.157865E+09 | 0.102212E+10 | 0.00 | 0.00 |
April | 0.191865E+10 | 55273379.02 | 0.851845E+09 | 366780.05 | 0.851479E+09 | 0.00 | 0.00 |
May | 0.207084E+10 | 79543495.44 | 0.880858E+09 | 0.00 | 0.880858E+09 | 0.00 | 0.00 |
June | 0.196419E+10 | 83204567.29 | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.00 | 0.00 |
July | 0.183640E+10 | 0.172147E+09 | 0.904149E+09 | 0.00 | 0.904149E+09 | 0.00 | 0.00 |
August | 0.177146E+10 | 0.128321E+09 | 0.880174E+09 | 1338165.35 | 0.878836E+09 | 0.00 | 0.00 |
September | 0.187753E+10 | 0.132510E+09 | 0.942779E+09 | 30571648.28 | 0.912207E+09 | 0.00 | 0.00 |
October | 0.227563E+10 | 0.184148E+09 | 0.127460E+10 | 0.203015E+09 | 0.107159E+10 | 0.00 | 0.00 |
November | 0.287278E+10 | 0.247512E+09 | 0.160401E+10 | 0.489193E+09 | 0.111482E+10 | 0.00 | 0.00 |
December | 0.361225E+10 | 0.428158E+09 | 0.203616E+10 | 0.866177E+09 | 0.116999E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.288602E+11 | 0.234317E+10 | 0.150034E+11 | 0.310738E+10 | 0.118960E+11 | 0.00 | 0.00 |
Minimum of Months | 0.177146E+10 | 55273379.02 | 0.849374E+09 | 0.00 | 0.849374E+09 | 0.00 | 0.00 |
Maximum of Months | 0.361730E+10 | 0.428158E+09 | 0.203710E+10 | 0.866177E+09 | 0.118739E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.651123E+09 | 0.138361E+09 | 0.419164E+09 | 0.174841E+09 | 0.244323E+09 | 0.00 | 0.00 |
February | 0.489720E+09 | 0.114139E+09 | 0.321469E+09 | 0.104763E+09 | 0.216705E+09 | 0.00 | 0.00 |
March | 0.356880E+09 | 99595987.08 | 0.242798E+09 | 32482927.03 | 0.210315E+09 | 0.00 | 0.00 |
April | 0.285080E+09 | 55134914.48 | 0.175280E+09 | 75470.34 | 0.175204E+09 | 0.00 | 0.00 |
May | 0.305339E+09 | 57246782.82 | 0.181249E+09 | 0.00 | 0.181249E+09 | 0.00 | 0.00 |
June | 0.290866E+09 | 60199975.57 | 0.174771E+09 | 0.00 | 0.174771E+09 | 0.00 | 0.00 |
July | 0.296067E+09 | 75663388.91 | 0.186042E+09 | 0.00 | 0.186042E+09 | 0.00 | 0.00 |
August | 0.280458E+09 | 66694677.59 | 0.181109E+09 | 275347.01 | 0.180833E+09 | 0.00 | 0.00 |
September | 0.302628E+09 | 69312333.08 | 0.193990E+09 | 6290561.79 | 0.187700E+09 | 0.00 | 0.00 |
October | 0.388915E+09 | 83263226.58 | 0.262268E+09 | 41773245.91 | 0.220495E+09 | 0.00 | 0.00 |
November | 0.508915E+09 | 0.100999E+09 | 0.330048E+09 | 0.100659E+09 | 0.229390E+09 | 0.00 | 0.00 |
December | 0.654086E+09 | 0.146190E+09 | 0.418970E+09 | 0.178229E+09 | 0.240742E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.481008E+10 | 0.106680E+10 | 0.308716E+10 | 0.639389E+09 | 0.244777E+10 | 0.00 | 0.00 |
Minimum of Months | 0.280458E+09 | 55134914.48 | 0.174771E+09 | 0.00 | 0.174771E+09 | 0.00 | 0.00 |
Maximum of Months | 0.654086E+09 | 0.146190E+09 | 0.419164E+09 | 0.178229E+09 | 0.244323E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.65 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.90 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.36 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 22.99 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.54 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.00 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.13 | 23.20 | 1.94 | 20.28 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.59 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 22.99 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.66 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.00 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 22.99 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.95 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.41 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.58 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.62 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.85 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.50 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.22 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.33 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.21 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.00 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.85 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.93 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.52 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.16 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.27 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.92 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.69 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.10 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.42 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.05 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.55 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.52 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.86 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.10 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.05 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.03 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.55 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.10 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.177305E+10 | -.138733E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385719859.3 | 58.99 | 0.00 | 0.00 |
February | 0.160356E+10 | -.125526E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -348303283.4 | 58.99 | 0.00 | 0.00 |
March | 0.178740E+10 | -.140189E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385507302.1 | 58.99 | 0.00 | 0.00 |
April | 0.167705E+10 | -.130411E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -372939497.9 | 58.99 | 0.00 | 0.00 |
May | 0.170562E+10 | -.132034E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385279870.7 | 58.99 | 0.00 | 0.00 |
June | 0.164791E+10 | -.127514E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -372765701.3 | 58.99 | 0.00 | 0.00 |
July | 0.165791E+10 | -.127253E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385383003.9 | 58.99 | 0.00 | 0.00 |
August | 0.170833E+10 | -.132282E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385502255.8 | 58.99 | 0.00 | 0.00 |
September | 0.165309E+10 | -.128001E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373076951.3 | 58.99 | 0.00 | 0.00 |
October | 0.171791E+10 | -.133233E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385587169.5 | 58.99 | 0.00 | 0.00 |
November | 0.168442E+10 | -.131118E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -373246038.0 | 58.99 | 0.00 | 0.00 |
December | 0.176831E+10 | -.138260E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -385711910.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.203846E+11 | -.158455E+11 | 8760.00 | -.453902E+10 | 58.99 | |||||
Minimum of Months | 0.160356E+10 | -.140189E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -385719859.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.178740E+10 | -.125526E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -348303283.4 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.77 | 0.50 | 02-JAN-11:30 | 450.68 | 8.23 | 0.00 | 85.50 | 379.13 | 6.73 | 0.00 | 55.50 |
February | 321.17 | 0.72 | 0.50 | 01-FEB-10:50 | 2563.17 | 8.80 | 0.00 | 126.50 | 2223.30 | 7.26 | 0.00 | 116.67 |
March | 361.17 | 0.77 | 0.50 | 01-MAR-10:20 | 378.81 | 9.71 | 0.00 | 44.33 | 313.06 | 8.03 | 0.00 | 33.67 |
April | 358.33 | 0.78 | 0.50 | 03-APR-09:00 | 355.48 | 11.25 | 0.00 | 37.33 | 294.46 | 9.48 | 0.00 | 14.83 |
May | 376.33 | 0.78 | 0.50 | 03-MAY-10:09 | 371.24 | 12.26 | 1.83 | 55.00 | 297.82 | 10.46 | 0.00 | 19.50 |
June | 370.50 | 0.75 | 0.50 | 02-JUN-10:39 | 649.46 | 15.73 | 53.17 | 111.17 | 302.30 | 11.06 | 0.00 | 19.50 |
July | 383.17 | 0.77 | 0.50 | 01-JUL-10:50 | 360.48 | 12.25 | 0.00 | 70.50 | 301.40 | 10.58 | 0.00 | 32.00 |
August | 369.33 | 0.77 | 0.50 | 02-AUG-10:30 | 373.28 | 11.92 | 0.00 | 72.00 | 311.41 | 10.22 | 0.00 | 24.33 |
September | 357.83 | 0.76 | 0.50 | 01-SEP-09:50 | 384.99 | 10.50 | 0.00 | 103.83 | 312.06 | 8.94 | 0.00 | 51.83 |
October | 356.83 | 0.73 | 0.50 | 01-OCT-09:00 | 664.88 | 9.77 | 0.00 | 167.83 | 414.98 | 8.17 | 0.00 | 75.50 |
November | 337.67 | 0.75 | 0.50 | 01-NOV-10:09 | 902.74 | 8.93 | 0.00 | 121.50 | 916.29 | 7.34 | 0.00 | 66.00 |
December | 349.33 | 0.79 | 0.50 | 01-DEC-10:20 | 342.49 | 8.10 | 0.00 | 55.67 | 288.17 | 6.60 | 0.00 | 38.17 |
Annual Sum or Average | 4292.33 | 0.76 | 629.32 | 10.69 | 55.00 | 1051.17 | 510.21 | 8.80 | 0.00 | 547.50 | ||
Minimum of Months | 321.17 | 0.72 | 0.50 | 342.49 | 8.10 | 0.00 | 37.33 | 288.17 | 6.60 | 0.00 | 14.83 | |
Maximum of Months | 383.17 | 0.79 | 0.50 | 2563.17 | 15.73 | 53.17 | 167.83 | 2223.30 | 11.06 | 0.00 | 116.67 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.376359E+11 | 0.275243E+11 | 51700.29 | 09-JAN-21:08 | 36484.40 | 0.00 |
February | 0.00 | 0.00 | 0.380866E+11 | 0.282442E+11 | 51397.01 | 15-FEB-21:06 | 36896.26 | 0.00 |
March | 0.00 | 0.00 | 0.472742E+11 | 0.346234E+11 | 51623.11 | 26-MAR-05:43 | 36808.31 | 0.00 |
April | 0.00 | 0.00 | 0.520096E+11 | 0.366504E+11 | 52130.13 | 20-APR-20:43 | 34633.27 | 0.00 |
May | 0.00 | 0.00 | 0.590927E+11 | 0.401735E+11 | 52325.37 | 19-MAY-02:43 | 34621.60 | 0.00 |
June | 0.00 | 0.00 | 0.625648E+11 | 0.432877E+11 | 52367.31 | 10-JUN-02:43 | 35493.58 | 0.00 |
July | 0.00 | 0.00 | 0.506059E+11 | 0.363331E+11 | 51909.27 | 07-JUL-20:08 | 36378.78 | 0.00 |
August | 0.00 | 0.00 | 0.517020E+11 | 0.340049E+11 | 52256.83 | 21-AUG-20:43 | 35088.79 | 0.00 |
September | 0.00 | 0.00 | 0.473662E+11 | 0.316577E+11 | 52202.83 | 18-SEP-20:43 | 35506.94 | 0.00 |
October | 0.00 | 0.00 | 0.428843E+11 | 0.281842E+11 | 52419.56 | 25-OCT-20:10 | 35003.19 | 0.00 |
November | 0.00 | 0.00 | 0.397647E+11 | 0.271796E+11 | 52281.15 | 11-NOV-19:10 | 35237.73 | 0.00 |
December | 0.00 | 0.00 | 0.371473E+11 | 0.263378E+11 | 52049.59 | 23-DEC-22:10 | 36456.03 | 0.00 |
Annual Sum or Average | 0.566134E+12 | 0.394201E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.371473E+11 | 0.263378E+11 | 51397.01 | 34621.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.625648E+11 | 0.432877E+11 | 52419.56 | 36896.26 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.108997E+12 | 0.768094E+11 | 217256.90 | 02-JAN-07:02 | 138210.49 | 0.00 |
February | 0.00 | 0.00 | 0.105831E+12 | 0.750214E+11 | 215169.36 | 16-FEB-07:02 | 141784.61 | 0.00 |
March | 0.00 | 0.00 | 0.127896E+12 | 0.903421E+11 | 215658.66 | 25-MAR-06:02 | 140646.45 | 0.00 |
April | 0.00 | 0.00 | 0.133340E+12 | 0.894194E+11 | 218011.61 | 15-APR-06:02 | 134536.83 | 0.00 |
May | 0.00 | 0.00 | 0.141280E+12 | 0.894927E+11 | 222786.88 | 22-MAY-06:02 | 120368.27 | 0.00 |
June | 0.00 | 0.00 | 0.142305E+12 | 0.902761E+11 | 220115.79 | 29-JUN-06:02 | 128116.64 | 0.00 |
July | 0.00 | 0.00 | 0.121513E+12 | 0.806292E+11 | 218823.86 | 01-JUL-06:02 | 132705.67 | 0.00 |
August | 0.00 | 0.00 | 0.133733E+12 | 0.826671E+11 | 221786.43 | 21-AUG-06:02 | 125247.29 | 0.00 |
September | 0.00 | 0.00 | 0.126591E+12 | 0.798800E+11 | 220025.12 | 17-SEP-08:62 | 128939.67 | 0.00 |
October | 0.00 | 0.00 | 0.119678E+12 | 0.748823E+11 | 219623.58 | 12-OCT-06:02 | 131066.12 | 0.00 |
November | 0.00 | 0.00 | 0.112253E+12 | 0.733650E+11 | 218268.16 | 09-NOV-07:02 | 134249.57 | 0.00 |
December | 0.00 | 0.00 | 0.109696E+12 | 0.751035E+11 | 217083.54 | 11-DEC-07:02 | 137949.24 | 0.00 |
Annual Sum or Average | 0.148311E+13 | 0.977888E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.105831E+12 | 0.733650E+11 | 215169.36 | 120368.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.142305E+12 | 0.903421E+11 | 222786.88 | 141784.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.293634E+11 | 0.216442E+11 | 27834.56 | 09-JAN-21:08 | 19269.69 | 0.00 |
February | 0.00 | 0.00 | 0.276453E+11 | 0.203535E+11 | 27738.71 | 14-FEB-21:42 | 19871.68 | 0.00 |
March | 0.00 | 0.00 | 0.306790E+11 | 0.218706E+11 | 27929.36 | 28-MAR-22:42 | 19364.39 | 0.00 |
April | 0.00 | 0.00 | 0.306957E+11 | 0.203295E+11 | 28270.70 | 20-APR-20:10 | 17677.80 | 0.00 |
May | 0.00 | 0.00 | 0.333110E+11 | 0.207473E+11 | 28565.11 | 28-MAY-18:10 | 16722.06 | 0.00 |
June | 0.00 | 0.00 | 0.330680E+11 | 0.205937E+11 | 28513.40 | 03-JUN-21:08 | 17147.90 | 0.00 |
July | 0.00 | 0.00 | 0.275930E+11 | 0.182667E+11 | 28125.78 | 07-JUL-20:08 | 18312.53 | 0.00 |
August | 0.00 | 0.00 | 0.303583E+11 | 0.184308E+11 | 28430.52 | 05-AUG-21:10 | 17510.72 | 0.00 |
September | 0.00 | 0.00 | 0.297312E+11 | 0.187141E+11 | 28271.38 | 18-SEP-20:08 | 17892.03 | 0.00 |
October | 0.00 | 0.00 | 0.293986E+11 | 0.186659E+11 | 28187.79 | 14-OCT-21:08 | 18039.08 | 0.00 |
November | 0.00 | 0.00 | 0.292286E+11 | 0.197539E+11 | 28068.39 | 11-NOV-19:08 | 18442.52 | 0.00 |
December | 0.00 | 0.00 | 0.295199E+11 | 0.211402E+11 | 28190.61 | 09-DEC-22:08 | 18195.76 | 0.00 |
Annual Sum or Average | 0.360592E+12 | 0.240510E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.275930E+11 | 0.182667E+11 | 27738.71 | 16722.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.333110E+11 | 0.218706E+11 | 28565.11 | 19871.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.258626E+11 | 0.183413E+11 | 24895.86 | 09-JAN-21:08 | 16165.71 | 0.00 |
February | 0.00 | 0.00 | 0.245050E+11 | 0.173723E+11 | 24755.99 | 14-FEB-21:42 | 16803.79 | 0.00 |
March | 0.00 | 0.00 | 0.269271E+11 | 0.184088E+11 | 24901.49 | 28-MAR-22:42 | 16402.34 | 0.00 |
April | 0.00 | 0.00 | 0.271412E+11 | 0.171116E+11 | 25358.77 | 20-APR-20:10 | 14697.51 | 0.00 |
May | 0.00 | 0.00 | 0.296860E+11 | 0.175018E+11 | 25549.49 | 28-MAY-18:10 | 14142.13 | 0.00 |
June | 0.00 | 0.00 | 0.295954E+11 | 0.174533E+11 | 25559.54 | 28-JUN-20:10 | 14223.47 | 0.00 |
July | 0.00 | 0.00 | 0.240149E+11 | 0.150725E+11 | 25208.77 | 07-JUL-20:08 | 15126.88 | 0.00 |
August | 0.00 | 0.00 | 0.265607E+11 | 0.151513E+11 | 25424.57 | 05-AUG-21:10 | 14603.45 | 0.00 |
September | 0.00 | 0.00 | 0.262192E+11 | 0.155892E+11 | 25361.05 | 18-SEP-20:08 | 14709.97 | 0.00 |
October | 0.00 | 0.00 | 0.256345E+11 | 0.153590E+11 | 25260.84 | 25-OCT-20:08 | 15002.78 | 0.00 |
November | 0.00 | 0.00 | 0.257906E+11 | 0.165912E+11 | 25090.38 | 30-NOV-21:08 | 15525.30 | 0.00 |
December | 0.00 | 0.00 | 0.260233E+11 | 0.178634E+11 | 25165.53 | 09-DEC-22:08 | 15348.33 | 0.00 |
Annual Sum or Average | 0.317960E+12 | 0.201816E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.240149E+11 | 0.150725E+11 | 24755.99 | 14142.13 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.296860E+11 | 0.184088E+11 | 25559.54 | 16803.79 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.203232E+10 | 0.49 | 2584.45 | 02-JAN-21:08 | 0.87 |
February | 0.193250E+10 | 0.50 | 2584.45 | 01-FEB-21:06 | 0.87 |
March | 0.231144E+10 | 0.51 | 2584.45 | 01-MAR-21:06 | 0.87 |
April | 0.244777E+10 | 0.53 | 2584.45 | 01-APR-21:06 | 0.87 |
May | 0.277617E+10 | 0.55 | 2584.45 | 01-MAY-20:06 | 0.87 |
June | 0.294345E+10 | 0.57 | 2584.45 | 01-JUN-02:63 | 0.87 |
July | 0.242202E+10 | 0.52 | 2584.45 | 01-JUL-21:08 | 0.87 |
August | 0.245817E+10 | 0.52 | 2584.45 | 01-AUG-00:03 | 0.87 |
September | 0.225881E+10 | 0.51 | 2584.45 | 01-SEP-00:43 | 0.87 |
October | 0.213074E+10 | 0.49 | 2584.45 | 01-OCT-04:23 | 0.87 |
November | 0.200830E+10 | 0.49 | 2584.45 | 01-NOV-20:08 | 0.87 |
December | 0.200782E+10 | 0.49 | 2584.45 | 01-DEC-21:08 | 0.87 |
Annual Sum or Average | 0.277295E+11 | 0.51 | |||
Minimum of Months | 0.193250E+10 | 0.49 | 2584.45 | 0.87 | |
Maximum of Months | 0.294345E+10 | 0.57 | 2584.45 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.881837E+10 | 0.50 | 13664.10 | 01-JAN-09:02 | 1.36 |
February | 0.801735E+10 | 0.50 | 13664.10 | 01-FEB-07:02 | 1.37 |
March | 0.903700E+10 | 0.51 | 13664.10 | 01-MAR-06:03 | 1.37 |
April | 0.879698E+10 | 0.51 | 13664.10 | 01-APR-05:03 | 1.37 |
May | 0.916124E+10 | 0.51 | 13664.10 | 01-MAY-05:02 | 1.36 |
June | 0.905367E+10 | 0.52 | 13664.10 | 01-JUN-05:03 | 1.37 |
July | 0.886348E+10 | 0.50 | 13664.10 | 01-JUL-06:02 | 1.36 |
August | 0.911142E+10 | 0.51 | 13664.10 | 01-AUG-06:02 | 1.36 |
September | 0.869310E+10 | 0.50 | 13664.10 | 01-SEP-06:02 | 1.36 |
October | 0.883432E+10 | 0.50 | 13664.10 | 01-OCT-07:03 | 1.37 |
November | 0.851189E+10 | 0.49 | 13664.10 | 01-NOV-06:02 | 1.36 |
December | 0.883830E+10 | 0.50 | 13664.10 | 01-DEC-07:02 | 1.36 |
Annual Sum or Average | 0.105737E+12 | 0.50 | |||
Minimum of Months | 0.801735E+10 | 0.49 | 13664.10 | 1.36 | |
Maximum of Months | 0.916124E+10 | 0.52 | 13664.10 | 1.37 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137415E+10 | 0.56 | 1334.50 | 02-JAN-21:08 | 0.90 |
February | 0.128867E+10 | 0.57 | 1334.50 | 01-FEB-00:23 | 0.90 |
March | 0.140475E+10 | 0.57 | 1334.50 | 01-MAR-21:06 | 0.90 |
April | 0.137321E+10 | 0.57 | 1334.50 | 01-APR-21:06 | 0.90 |
May | 0.147420E+10 | 0.58 | 1334.50 | 01-MAY-20:06 | 0.90 |
June | 0.146586E+10 | 0.58 | 1334.50 | 01-JUN-02:63 | 0.90 |
July | 0.124371E+10 | 0.54 | 1334.50 | 01-JUL-21:08 | 0.90 |
August | 0.135013E+10 | 0.55 | 1334.50 | 01-AUG-00:03 | 0.90 |
September | 0.132726E+10 | 0.56 | 1334.50 | 01-SEP-00:43 | 0.90 |
October | 0.132289E+10 | 0.55 | 1334.50 | 01-OCT-04:23 | 0.90 |
November | 0.133077E+10 | 0.56 | 1334.50 | 01-NOV-20:08 | 0.90 |
December | 0.136677E+10 | 0.56 | 1334.50 | 01-DEC-21:06 | 0.90 |
Annual Sum or Average | 0.163224E+11 | 0.56 | |||
Minimum of Months | 0.124371E+10 | 0.54 | 1334.50 | 0.90 | |
Maximum of Months | 0.147420E+10 | 0.58 | 1334.50 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115794E+10 | 0.56 | 1132.75 | 02-JAN-21:08 | 0.90 |
February | 0.109054E+10 | 0.57 | 1132.75 | 01-FEB-00:23 | 0.90 |
March | 0.117869E+10 | 0.56 | 1132.75 | 01-MAR-21:06 | 0.90 |
April | 0.115359E+10 | 0.56 | 1132.75 | 01-APR-21:06 | 0.90 |
May | 0.124689E+10 | 0.57 | 1132.75 | 01-MAY-20:06 | 0.89 |
June | 0.124388E+10 | 0.58 | 1132.75 | 01-JUN-02:63 | 0.90 |
July | 0.103832E+10 | 0.54 | 1132.75 | 01-JUL-21:08 | 0.90 |
August | 0.112804E+10 | 0.55 | 1132.75 | 01-AUG-00:03 | 0.90 |
September | 0.111615E+10 | 0.56 | 1132.75 | 01-SEP-00:43 | 0.90 |
October | 0.110505E+10 | 0.54 | 1132.75 | 01-OCT-04:23 | 0.90 |
November | 0.112064E+10 | 0.56 | 1132.75 | 01-NOV-20:08 | 0.90 |
December | 0.115232E+10 | 0.56 | 1132.75 | 01-DEC-21:06 | 0.90 |
Annual Sum or Average | 0.137320E+11 | 0.56 | |||
Minimum of Months | 0.103832E+10 | 0.54 | 1132.75 | 0.89 | |
Maximum of Months | 0.124689E+10 | 0.58 | 1132.75 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.50 | 0.00 |
February | 3.64 | 0.00 |
March | 4.46 | 0.00 |
April | 5.12 | 0.00 |
May | 4.15 | 0.00 |
June | 3.78 | 0.00 |
July | 4.22 | 0.00 |
August | 3.69 | 0.00 |
September | 3.61 | 0.00 |
October | 3.47 | 0.00 |
November | 3.28 | 0.00 |
December | 3.22 | 0.00 |
Annual Sum or Average | 46.15 | 0.00 |
Minimum of Months | 3.22 | 0.00 |
Maximum of Months | 5.12 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.46 | 0.00 |
February | 2.42 | 0.00 |
March | 0.26 | 0.00 |
April | 0.03 | 0.00 |
May | 0.92 | 0.00 |
June | 0.51 | 0.00 |
July | 1.06 | 0.00 |
August | 0.53 | 0.00 |
September | 0.46 | 0.00 |
October | 1.03 | 0.00 |
November | 2.34 | 0.00 |
December | 3.52 | 0.00 |
Annual Sum or Average | 16.55 | 0.00 |
Minimum of Months | 0.03 | 0.00 |
Maximum of Months | 3.52 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.116644E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.116960E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.144267E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.156691E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.176631E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.186174E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.149999E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.152290E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.140293E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.127740E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.119550E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.114325E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.170156E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.114325E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.186174E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.399587E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.383783E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.457160E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.466053E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.488548E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.488384E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.427927E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.458635E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.436262E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.418997E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.398106E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.398740E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.522218E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.383783E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.488548E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.850023E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.808003E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.898954E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.893079E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.958980E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.949958E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.790210E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.859176E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.844873E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.831743E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.831698E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.845194E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.103619E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.790210E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.958980E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.741657E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.708845E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.781093E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.778880E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.841562E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.836869E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.681141E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.741748E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.735299E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.716825E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.725578E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.737841E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.902734E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.681141E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.841562E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.203232E+10 | 0.376359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193250E+10 | 0.380866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231144E+10 | 0.472742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.244777E+10 | 0.520096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.277617E+10 | 0.590927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.294345E+10 | 0.625648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.242202E+10 | 0.506059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.245817E+10 | 0.517020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.225881E+10 | 0.473662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213074E+10 | 0.428843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200830E+10 | 0.397647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200782E+10 | 0.371473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277295E+11 | 0.566134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.193250E+10 | 0.371473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.294345E+10 | 0.625648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.881837E+10 | 0.108997E+12 | 0.00 | 9860504.69 | 0.460870E+11 | 0.00 | 0.00 | 0.00 |
February | 0.801735E+10 | 0.105831E+12 | 0.00 | 0.00 | 0.465967E+11 | 0.00 | 0.00 | 0.00 |
March | 0.903700E+10 | 0.127896E+12 | 0.00 | 0.00 | 0.577966E+11 | 0.00 | 0.00 | 0.00 |
April | 0.879698E+10 | 0.133340E+12 | 0.00 | 0.00 | 0.686107E+11 | 0.00 | 0.00 | 0.00 |
May | 0.916124E+10 | 0.141280E+12 | 0.00 | 0.00 | 0.792723E+11 | 0.00 | 0.00 | 0.00 |
June | 0.905367E+10 | 0.142305E+12 | 0.00 | 0.00 | 0.793392E+11 | 0.00 | 0.00 | 0.00 |
July | 0.886348E+10 | 0.121513E+12 | 0.00 | 0.00 | 0.596221E+11 | 0.00 | 0.00 | 0.00 |
August | 0.911142E+10 | 0.133733E+12 | 0.00 | 0.00 | 0.737235E+11 | 0.00 | 0.00 | 0.00 |
September | 0.869310E+10 | 0.126591E+12 | 0.00 | 0.00 | 0.684526E+11 | 0.00 | 0.00 | 0.00 |
October | 0.883432E+10 | 0.119678E+12 | 0.00 | 0.00 | 0.642055E+11 | 0.00 | 0.00 | 0.00 |
November | 0.851189E+10 | 0.112253E+12 | 0.00 | 0.00 | 0.557317E+11 | 0.00 | 0.00 | 0.00 |
December | 0.883830E+10 | 0.109696E+12 | 0.00 | 1378264.49 | 0.489330E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105737E+12 | 0.148311E+13 | 0.00 | 11238769.19 | 0.748371E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.801735E+10 | 0.105831E+12 | 0.00 | 0.00 | 0.460870E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.916124E+10 | 0.142305E+12 | 0.00 | 9860504.69 | 0.793392E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137415E+10 | 0.293634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128867E+10 | 0.276453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140475E+10 | 0.306790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137321E+10 | 0.306957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147420E+10 | 0.333110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146586E+10 | 0.330680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124371E+10 | 0.275930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135013E+10 | 0.303583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132726E+10 | 0.297312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132289E+10 | 0.293986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133077E+10 | 0.292286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136677E+10 | 0.295199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163224E+11 | 0.360592E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124371E+10 | 0.275930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147420E+10 | 0.333110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.115794E+10 | 0.258626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109054E+10 | 0.245050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117869E+10 | 0.269271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115359E+10 | 0.271412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124689E+10 | 0.296860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124388E+10 | 0.295954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103832E+10 | 0.240149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112804E+10 | 0.265607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111615E+10 | 0.262192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110505E+10 | 0.256345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112064E+10 | 0.257906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115232E+10 | 0.260233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137320E+11 | 0.317960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103832E+10 | 0.240149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124689E+10 | 0.296860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.203232E+10 | 0.00 | 0.00 | 0.00 | 0.963209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.193250E+10 | 0.00 | 0.00 | 0.00 | 0.976351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231144E+10 | 0.00 | 0.00 | 0.00 | 0.121153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.244777E+10 | 0.00 | 0.00 | 0.00 | 0.132213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.277617E+10 | 0.00 | 0.00 | 0.00 | 0.148869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.294345E+10 | 0.00 | 0.00 | 0.00 | 0.156739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.242202E+10 | 0.00 | 0.00 | 0.00 | 0.125779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.245817E+10 | 0.00 | 0.00 | 0.00 | 0.127708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.225881E+10 | 0.00 | 0.00 | 0.00 | 0.117705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.213074E+10 | 0.00 | 0.00 | 0.00 | 0.106432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.200830E+10 | 0.00 | 0.00 | 0.00 | 0.994674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200782E+10 | 0.00 | 0.00 | 0.00 | 0.942464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277295E+11 | 0.00 | 0.00 | 0.00 | 0.142427E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.193250E+10 | 0.00 | 0.00 | 0.00 | 0.942464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.294345E+10 | 0.00 | 0.00 | 0.00 | 0.156739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.881837E+10 | 0.00 | 0.00 | 0.00 | 0.311404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.801735E+10 | 0.00 | 0.00 | 0.00 | 0.303610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.903700E+10 | 0.00 | 0.00 | 0.00 | 0.366790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.879698E+10 | 0.00 | 0.00 | 0.00 | 0.378083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.916124E+10 | 0.00 | 0.00 | 0.00 | 0.396935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.905367E+10 | 0.00 | 0.00 | 0.00 | 0.397847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.886348E+10 | 0.00 | 0.00 | 0.00 | 0.339292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.911142E+10 | 0.00 | 0.00 | 0.00 | 0.367521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.869310E+10 | 0.00 | 0.00 | 0.00 | 0.349331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.883432E+10 | 0.00 | 0.00 | 0.00 | 0.330653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.851189E+10 | 0.00 | 0.00 | 0.00 | 0.312988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.883830E+10 | 0.00 | 0.00 | 0.00 | 0.310357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105737E+12 | 0.00 | 0.00 | 0.00 | 0.416481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.801735E+10 | 0.00 | 0.00 | 0.00 | 0.303610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.916124E+10 | 0.00 | 0.00 | 0.00 | 0.397847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.137415E+10 | 0.00 | 0.00 | 0.00 | 0.712608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128867E+10 | 0.00 | 0.00 | 0.00 | 0.679136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140475E+10 | 0.00 | 0.00 | 0.00 | 0.758479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137321E+10 | 0.00 | 0.00 | 0.00 | 0.755758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147420E+10 | 0.00 | 0.00 | 0.00 | 0.811560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146586E+10 | 0.00 | 0.00 | 0.00 | 0.803373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124371E+10 | 0.00 | 0.00 | 0.00 | 0.665839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135013E+10 | 0.00 | 0.00 | 0.00 | 0.724163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132726E+10 | 0.00 | 0.00 | 0.00 | 0.712146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132289E+10 | 0.00 | 0.00 | 0.00 | 0.699454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133077E+10 | 0.00 | 0.00 | 0.00 | 0.698622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136677E+10 | 0.00 | 0.00 | 0.00 | 0.708518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163224E+11 | 0.00 | 0.00 | 0.00 | 0.872966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.124371E+10 | 0.00 | 0.00 | 0.00 | 0.665839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147420E+10 | 0.00 | 0.00 | 0.00 | 0.811560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.115794E+10 | 0.00 | 0.00 | 0.00 | 0.625864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109054E+10 | 0.00 | 0.00 | 0.00 | 0.599791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117869E+10 | 0.00 | 0.00 | 0.00 | 0.663224E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115359E+10 | 0.00 | 0.00 | 0.00 | 0.663521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.124689E+10 | 0.00 | 0.00 | 0.00 | 0.716873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124388E+10 | 0.00 | 0.00 | 0.00 | 0.712481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103832E+10 | 0.00 | 0.00 | 0.00 | 0.577309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112804E+10 | 0.00 | 0.00 | 0.00 | 0.628944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111615E+10 | 0.00 | 0.00 | 0.00 | 0.623684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110505E+10 | 0.00 | 0.00 | 0.00 | 0.606321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112064E+10 | 0.00 | 0.00 | 0.00 | 0.613514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115232E+10 | 0.00 | 0.00 | 0.00 | 0.622610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137320E+11 | 0.00 | 0.00 | 0.00 | 0.765413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.103832E+10 | 0.00 | 0.00 | 0.00 | 0.577309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.124689E+10 | 0.00 | 0.00 | 0.00 | 0.716873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.943443E+10 | 0.00 | 0.00 | 4658417.26 | 0.00 | 0.00 | 0.00 | 0.25 |
February | 0.00 | 0.973564E+10 | 0.00 | 0.00 | 4230631.32 | 0.00 | 0.00 | 0.00 | 0.25 |
March | 0.00 | 0.121969E+11 | 0.00 | 0.00 | 1841083.01 | 0.00 | 0.00 | 0.00 | 0.26 |
April | 0.00 | 0.153582E+11 | 0.00 | 0.00 | 6563344.97 | 0.00 | 0.00 | 0.00 | 0.27 |
May | 0.00 | 0.185991E+11 | 0.00 | 0.00 | 3769311.52 | 0.00 | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.189561E+11 | 0.00 | 0.00 | 4011049.65 | 0.00 | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.137866E+11 | 0.00 | 0.00 | 7142973.15 | 0.00 | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.166269E+11 | 0.00 | 0.00 | 8740542.93 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.152926E+11 | 0.00 | 0.00 | 3334203.53 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.00 | 0.139774E+11 | 0.00 | 0.00 | 14754270.80 | 0.00 | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.119831E+11 | 0.00 | 0.00 | 6066179.96 | 0.00 | 0.00 | 0.00 | 0.25 |
December | 0.00 | 0.100805E+11 | 0.00 | 0.00 | 6060336.27 | 0.00 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.00 | 0.166028E+12 | 0.00 | 0.00 | 71172344.35 | 0.00 | 0.00 | 0.00 | 0.26 |
Minimum of Months | 0.00 | 0.943443E+10 | 0.00 | 0.00 | 1841083.01 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.00 | 0.189561E+11 | 0.00 | 0.00 | 14754270.80 | 0.00 | 0.00 | 0.00 | 0.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.268745E+11 | 0.00 | 0.00 | 0.776318E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
February | 0.00 | 0.269248E+11 | 0.00 | 0.00 | 0.721700E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
March | 0.00 | 0.334350E+11 | 0.00 | 0.00 | 0.684417E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
April | 0.00 | 0.409873E+11 | 0.00 | 0.00 | 0.694419E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.484710E+11 | 0.00 | 0.00 | 0.830725E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.488876E+11 | 0.00 | 0.00 | 0.733879E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.361272E+11 | 0.00 | 0.00 | 0.972310E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.460310E+11 | 0.00 | 0.00 | 0.938905E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.424714E+11 | 0.00 | 0.00 | 0.897849E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.397606E+11 | 0.00 | 0.00 | 0.105822E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 0.00 | 0.340860E+11 | 0.00 | 0.00 | 0.850332E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
December | 0.00 | 0.292161E+11 | 0.00 | 0.00 | 0.782154E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.00 | 0.453272E+12 | 0.00 | 0.00 | 0.994122E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.268745E+11 | 0.00 | 0.00 | 0.684417E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.00 | 0.488876E+11 | 0.00 | 0.00 | 0.105822E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.819783E+10 | 0.00 | 0.00 | 2319903.34 | 0.00 | 0.00 | 0.00 | 0.50 |
February | 0.00 | 0.813581E+10 | 0.00 | 0.00 | 3314999.70 | 0.00 | 0.00 | 0.00 | 0.51 |
March | 0.00 | 0.977289E+10 | 0.00 | 0.00 | 1440097.27 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.116521E+11 | 0.00 | 0.00 | 4978737.17 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 0.00 | 0.137846E+11 | 0.00 | 0.00 | 2461186.11 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.00 | 0.136638E+11 | 0.00 | 0.00 | 3859894.72 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.100656E+11 | 0.00 | 0.00 | 5327132.76 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.125034E+11 | 0.00 | 0.00 | 5344537.47 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.118267E+11 | 0.00 | 0.00 | 2513761.20 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.00 | 0.112876E+11 | 0.00 | 0.00 | 4081947.10 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.00 | 0.100167E+11 | 0.00 | 0.00 | 3854637.82 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.00 | 0.878625E+10 | 0.00 | 0.00 | 3381008.08 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.00 | 0.129693E+12 | 0.00 | 0.00 | 42877842.76 | 0.00 | 0.00 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.813581E+10 | 0.00 | 0.00 | 1440097.27 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.00 | 0.137846E+11 | 0.00 | 0.00 | 5344537.47 | 0.00 | 0.00 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.801198E+10 | 0.00 | 0.00 | 2314527.71 | 0.00 | 0.00 | 0.00 | 0.50 |
February | 0.00 | 0.798831E+10 | 0.00 | 0.00 | 3301149.55 | 0.00 | 0.00 | 0.00 | 0.51 |
March | 0.00 | 0.950541E+10 | 0.00 | 0.00 | 1419690.09 | 0.00 | 0.00 | 0.00 | 0.52 |
April | 0.00 | 0.113351E+11 | 0.00 | 0.00 | 4895833.43 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 0.00 | 0.134387E+11 | 0.00 | 0.00 | 1462898.29 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.00 | 0.133604E+11 | 0.00 | 0.00 | 2929986.84 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.969263E+10 | 0.00 | 0.00 | 5289381.95 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.120153E+11 | 0.00 | 0.00 | 10113493.29 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.114560E+11 | 0.00 | 0.00 | 2493835.03 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.00 | 0.108473E+11 | 0.00 | 0.00 | 5167111.65 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 0.00 | 0.975388E+10 | 0.00 | 0.00 | 3833233.00 | 0.00 | 0.00 | 0.00 | 0.50 |
December | 0.00 | 0.857712E+10 | 0.00 | 0.00 | 3347912.92 | 0.00 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.00 | 0.125982E+12 | 0.00 | 0.00 | 46569053.75 | 0.00 | 0.00 | 0.00 | 0.51 |
Minimum of Months | 0.00 | 0.798831E+10 | 0.00 | 0.00 | 1419690.09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.00 | 0.134387E+11 | 0.00 | 0.00 | 10113493.29 | 0.00 | 0.00 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:13:00
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |