Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12
Tabular Output Report in Format: HTML
Building: RetailStandalone
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2020-06-03 19:12:26
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1501.03 | 654.33 | 654.33 |
Net Site Energy | 1501.03 | 654.33 | 654.33 |
Total Source Energy | 4547.57 | 1982.38 | 1982.38 |
Net Source Energy | 4547.57 | 1982.38 | 1982.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2293.99 |
Net Conditioned Building Area | 2293.99 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 13.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 611.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 356.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 60.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 179.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 85.35 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1402.05 | 98.98 | 0.00 | 0.00 | 0.00 | 134.99 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 13.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 611.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 356.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 60.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 194.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 179.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 85.35 | 0.00 | 0.00 | 0.00 | 134.99 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 181.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 344.90 | 43.15 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 611.18 | 43.15 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 181.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 344.90 | 43.15 | 0.00 | 0.00 | 0.00 | 0.06 |
Other | 84.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 611.18 | 43.15 | 0.00 | 0.00 | 0.00 | 0.06 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1402.046 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1402.046 | 100.00 |
Total On-Site and Utility Electric Sources | 1402.046 | 100.00 |
Total Electricity End Uses | 1402.046 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 134.99 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 134.99 | 100.00 |
Total Water End Uses | 134.99 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 336.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Meter |ZoneCoolingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneHeatingSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ZoneElectricSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |PeakSpaceGainsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |SpaceGainComponentsAtCoolingPeakMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |ComfortReportSimple55Monthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |OccupantComfortDataSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |DXReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |WindowReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowEnergyReportMonthly
| SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | POINT_OF_SALE_WALL_SOUTH_GLAZING | FRONT_RETAIL_WALL_SOUTH_GLAZING | FRONT_ENTRY_WALL_SOUTH_GLAZING |WindowZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |WindowEnergyZoneSummaryMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | FRONT_ENTRY UNIT HEATER COIL | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL |FanReportMonthly
| FRONT_ENTRY UNIT HEATERFAN | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 |MechanicalVentilationLoadsMonthly
| BACK_SPACE | CORE_RETAIL | POINT_OF_SALE | FRONT_RETAIL | FRONT_ENTRY |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:12 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Above Ground Wall Area [m2] | 1177.02 | 330.83 | 257.68 | 330.83 | 257.68 |
Window Opening Area [m2] | 83.94 | 0.00 | 0.00 | 83.94 | 0.00 |
Gross Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Above Ground Window-Wall Ratio [%] | 7.13 | 0.00 | 0.00 | 25.37 | 0.00 |
Total | |
Gross Roof Area [m2] | 2293.99 |
Skylight Area [m2] | 23.78 |
Skylight-Roof Ratio [%] | 1.04 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BACK_SPACE | 379.89 | Yes | Yes | 2317.33 | 1.00 | 416.17 | 0.00 | 0.00 | 0.00 | 7.5670 | 6.19 | 8.0700 |
CORE_RETAIL | 1600.48 | Yes | Yes | 9762.95 | 1.00 | 356.86 | 0.00 | 0.00 | 0.00 | 15.5000 | 6.19 | 3.2300 |
POINT_OF_SALE | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 15.5000 | 6.19 | 21.5200 |
FRONT_RETAIL | 150.81 | Yes | Yes | 919.94 | 1.00 | 189.80 | 0.00 | 38.05 | 38.05 | 15.5000 | 6.19 | 3.2300 |
FRONT_ENTRY | 12.00 | Yes | Yes | 73.20 | 1.00 | 24.38 | 0.00 | 7.83 | 7.83 | 9.6875 | 0.0000 | |
Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 14.1559 | 6.23 | 5.2170 | |||
Conditioned Total | 2293.99 | 13993.36 | 1177.02 | 0.00 | 83.94 | 83.94 | 14.1559 | 6.23 | 5.2170 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-JUN-15:00 | 02-JAN-07:10 | - | - | - | 01-MAY-11:09 |
Heating | 0.00 | 114536.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 87881.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 26716.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16486.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 141825.34 | 116396.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 114536.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 87881.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 26716.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 16486.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 1860.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 14.77 | 0.00 | 0.00 | 0.00 |
Cooling | 1936.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1128.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 190.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 615.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 568.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 92.52 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4440.28 | 107.30 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 6.44 | 0.00 | 0.00 | 0.00 |
Cooling | 844.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 491.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 247.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.33 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1935.61 | 46.77 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 6.44 | 0.00 | 0.00 | 0.00 |
Cooling | 844.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 491.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 83.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 268.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 247.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 40.33 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1935.61 | 46.77 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BACK_SPACE DIRECT AIR | 2.99 |
CORE_RETAIL DIRECT AIR | 8.78 |
POINT_OF_SALE DIRECT AIR | 1.55 |
FRONT_RETAIL DIRECT AIR | 1.36 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATER | 0.722739 |
Design Size Maximum Flow Rate [m3/s] | |
FRONT_ENTRY UNIT HEATERFAN | 0.722739 |
Design Size Nominal Capacity [W] | |
FRONT_ENTRY UNIT HEATER COIL | 20778.58 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | 71349.24 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | 231256.19 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | 37969.94 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | 33635.78 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC:1 | 2.99 | 2.99 | 2.99 | 2.99 | 2.99 | 2.99 | 1.00 | 1.00 | 2.99 |
PSZ-AC:2 | 8.78 | 8.78 | 8.78 | 8.78 | 8.90 | 8.90 | 1.00 | 0.987012 | 8.90 |
PSZ-AC:3 | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.00 | 1.000000 | 1.55 |
PSZ-AC:4 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.00 | 1.00 | 1.36 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC:1_OA_CONTROLLER | 2.99 | 0.231567 |
PSZ-AC:2_OA_CONTROLLER | 8.90 | 1.89 |
PSZ-AC:3_OA_CONTROLLER | 1.55 | 0.178111 |
PSZ-AC:4_OA_CONTROLLER | 1.36 | 0.178111 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC:1_UNITARY_PACKAGE_DX | 2.99 | 2.99 | 2.99 | 1.97 | 61872.48 | 71349.24 | 40.00 | 1.00 |
PSZ-AC:2_UNITARY_PACKAGE_DX | 8.90 | 8.90 | 8.90 | 5.87 | 219554.75 | 231256.19 | 40.00 | 1.00 |
PSZ-AC:3_UNITARY_PACKAGE_DX | 1.55 | 1.55 | 1.55 | 1.02 | 33174.34 | 37969.94 | 40.00 | 1.00 |
PSZ-AC:4_UNITARY_PACKAGE_DX | 1.36 | 1.36 | 1.36 | 0.895770 | 29907.50 | 33635.78 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | Speed 2 Design Size Rated Total Cooling Capacity [W] | Speed 2 User-Specified Rated Total Cooling Capacity [W] | Speed 1 Design Size Rated Total Cooling Capacity [W] | Speed 1 User-Specified Rated Total Cooling Capacity [W] | Speed 2 Design Size Rated Sensible Heat Ratio | Speed 2 User-Specified Rated Sensible Heat Ratio | Speed 1 Design Size Rated Sensible Heat Ratio | Speed 1 User-Specified Rated Sensible Heat Ratio | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 2.99 | 1.50 | 1.99 | 57629.03 | 61872.48 | 30936.24 | 30936.24 | 0.725238 | 0.725240 | 0.725240 | 0.725240 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 8.90 | 4.45 | 5.93 | 207722.50 | 219554.75 | 109777.38 | 109777.38 | 0.677628 | 0.677630 | 0.677630 | 0.677630 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 1.55 | 0.774835 | 1.03 | 30999.45 | 33174.34 | 16587.17 | 16587.17 | 0.715295 | 0.715290 | 0.715290 | 0.715290 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 1.36 | 0.678615 | 0.904820 | 28016.48 | 29907.50 | 14953.75 | 14953.75 | 0.707188 | 0.707190 | 0.707190 | 0.707190 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.99 | 3200.86 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | 8.90 | 14893.16 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.55 | 1658.22 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.36 | 1502.67 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
BACK_SPACE_WALL_EAST | BACK_SPACE_WALL_EAST_ROLLDOOR | |
BACK_SPACE_WALL_NORTH | BACK_SPACE_WALL_NORTH_DOOR1 | BACK_SPACE_WALL_NORTH_DOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | |
BACK_SPACE_WALL_WEST | BACK_SPACE_WALL_WEST_ROLLDOOR | |
CORE_RETAIL_WALL_WEST_2 | CORE_RETAIL_WALL_WEST_2_DOOR3 | CORE_RETAIL_WALL_WEST_2_DOOR2 | CORE_RETAIL_WALL_WEST_2_DOOR1 | |
CORE_RETAIL_WALL_EAST_2 | CORE_RETAIL_WALL_EAST_2_DOOR1 | CORE_RETAIL_WALL_EAST_2_DOOR2 | CORE_RETAIL_WALL_EAST_2_DOOR3 | |
CORE_RETAIL_ROOF | SKYLIGHTS_R4C1 | SKYLIGHTS_R4C2 | SKYLIGHTS_R4C3 | SKYLIGHTS_R4C4 | SKYLIGHTS_R1C1 | SKYLIGHTS_R1C2 | SKYLIGHTS_R1C4 | SKYLIGHTS_R1C3 | SKYLIGHTS_R2C2 | SKYLIGHTS_R2C1 | SKYLIGHTS_R2C3 | SKYLIGHTS_R2C4 | SKYLIGHTS_R3C2 | SKYLIGHTS_R3C1 | SKYLIGHTS_R3C3 | SKYLIGHTS_R3C4 | |
POINT_OF_SALE_WALL_SOUTH | POINT_OF_SALE_WALL_SOUTH_GLAZING | |
FRONT_RETAIL_WALL_SOUTH | FRONT_RETAIL_WALL_SOUTH_GLAZING | |
FRONT_ENTRY_WALL_SOUTH | FRONT_ENTRY_WALL_SOUTH_GLAZING | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStandalone | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 5 | 73 | 32 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BACK_SPACE | 0.0 | 0.00 | 35.27 | 0.00 | 27.14 | 38.77 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 35.27 | 42.27 | 0.00 | 6.10 | 6.10 | 2317.33 | TARP | TARP | 379.89 | 416.17 | 375.11 | 0.00 | 6 | 7 | 0 | Yes |
2 | CORE_RETAIL | 0.0 | 0.00 | 6.00 | 0.00 | 27.14 | 14.41 | 3.05 | 1 | 1 | 1 | 0.00 | 54.27 | 3.00 | 35.27 | 0.00 | 6.10 | 6.10 | 9762.95 | TARP | TARP | 1600.48 | 356.86 | 345.15 | 23.78 | 10 | 22 | 0 | Yes |
3 | POINT_OF_SALE | 0.0 | 0.00 | 0.00 | 0.00 | 12.57 | 3.00 | 3.05 | 1 | 1 | 1 | 0.00 | 25.14 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
4 | FRONT_RETAIL | 0.0 | 29.14 | 0.00 | 0.00 | 41.70 | 3.00 | 3.05 | 1 | 1 | 1 | 29.14 | 54.27 | 0.00 | 6.00 | 0.00 | 6.10 | 6.10 | 919.94 | TARP | TARP | 150.81 | 189.80 | 151.75 | 38.05 | 7 | 1 | 0 | Yes |
5 | FRONT_ENTRY | 0.0 | 25.14 | 0.00 | 0.00 | 27.14 | 1.50 | 3.05 | 1 | 1 | 1 | 25.14 | 29.14 | 0.00 | 3.00 | 0.00 | 6.10 | 6.10 | 73.20 | TARP | TARP | 12.00 | 24.38 | 16.55 | 7.83 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BACK_SPACE | 379.89 | 61.3 | 6.193 | 0.161 | 7.567 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.637 | No |
2 | CORE_RETAIL | 1600.48 | 258.4 | 6.193 | 0.161 | 15.500 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.730 | No |
3 | POINT_OF_SALE | 150.81 | 24.4 | 6.193 | 0.161 | 15.500 | 21.520 | 0.000 | 0.000 | 0.000 | 0.000 | 37.020 | No |
4 | FRONT_RETAIL | 150.81 | 24.4 | 6.193 | 0.161 | 15.500 | 3.230 | 0.000 | 0.000 | 0.000 | 0.000 | 18.730 | No |
5 | FRONT_ENTRY | 12.00 | 0.0 | N/A | 0.000 | 9.688 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.688 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BACK_SPACE | BLDG_OCC_SCH | BACK_SPACE | 379.89 | 61.3 | 61.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 61 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_RETAIL | BLDG_OCC_SCH | CORE_RETAIL | 1600.48 | 258.4 | 258.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 258 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | POINT_OF_SALE | BLDG_OCC_SCH | POINT_OF_SALE | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | FRONT_RETAIL | BLDG_OCC_SCH | FRONT_RETAIL | 150.81 | 24.4 | 24.4 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 24 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | FRONT_ENTRY | BLDG_OCC_SCH | FRONT_ENTRY | 12.00 | 0.0 | 0.0 | 0.000 | N/A | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BACK_SPACE_LIGHTS | BLDG_LIGHT_BACK_SCH | BACK_SPACE | 379.89 | 61.3 | 2874.639 | 7.567 | 46.863 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2874.639 |
2 | CORE_RETAIL_LIGHTS | BLDG_LIGHT_CORE_SCH | CORE_RETAIL | 1600.48 | 258.4 | 24807.535 | 15.500 | 95.992 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24807.535 |
3 | POINT_OF_SALE_LIGHTS | BLDG_LIGHT_SCH | POINT_OF_SALE | 150.81 | 24.4 | 2337.560 | 15.500 | 95.992 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2337.560 |
4 | FRONT_RETAIL_LIGHTS | BLDG_LIGHT_FRONT_SCH | FRONT_RETAIL | 150.81 | 24.4 | 2337.560 | 15.500 | 95.992 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2337.560 |
5 | FRONT_ENTRY_LIGHTS | BLDG_LIGHT_ENTRY_SCH | FRONT_ENTRY | 12.00 | 0.0 | 116.250 | 9.688 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 116.250 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BACK_SPACE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | BACK_SPACE | 379.89 | 61.3 | 3065.712 | 8.070 | 49.978 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3065.712 |
2 | CORE_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_RETAIL | 1600.48 | 258.4 | 5169.560 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 5169.560 |
3 | POINT_OF_SALE_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | POINT_OF_SALE | 150.81 | 24.4 | 3245.431 | 21.520 | 133.273 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 3245.431 |
4 | FRONT_RETAIL_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | FRONT_RETAIL | 150.81 | 24.4 | 487.116 | 3.230 | 20.003 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 487.116 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 8.239 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | BACK_SPACE_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.2354 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | CORE_RETAIL_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.4655E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | POINT_OF_SALE_FLOOR_FFACTOR | 34 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | FRONT_RETAIL_FLOOR_FFACTOR | 35 | 2 | 7 | 0.167 | 0.2719 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | FRONT_ENTRY_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.4506 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1214 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.172 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 21.40 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.601 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.142 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9750000 | 3.9750000 | 3.9750000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 8.2386364 | 8.2386364 | 8.2386364 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
21 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
22 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
23 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
24 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
25 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
26 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
27 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
28 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
29 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
30 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
31 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
32 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
33 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
34 | 7 | -0.17867606E-08 | -0.41848128E-15 | 0.59564440E-14 | -0.80268503E-16 |
35 | 6 | 0.65885627E-05 | 0.45121803E-08 | 0.31870471E-02 | -0.26735622E-04 |
36 | 5 | -0.47407468E-03 | 0.26731137E-05 | -0.22356413 | 0.19547341E-02 |
37 | 4 | 0.10906669E-01 | 0.12168607E-03 | 4.8268734 | -0.45239294E-01 |
38 | 3 | -0.95781928E-01 | 0.96775432E-03 | -38.006321 | 0.39848689 |
39 | 2 | 0.34010998 | 0.16100142E-02 | 116.45457 | -1.4175463 |
40 | 1 | -0.49090295 | 0.49061009E-03 | -143.89001 | 2.0487556 |
41 | 0 | 0.23934032 | 0.11861159E-04 | 60.838472 | |
42 | 7 | -0.92098544E-08 | 0.58605081E-15 | -0.29904982E-14 | 0.25019681E-16 |
43 | 6 | 0.19387148E-05 | 0.91388609E-09 | 0.32017682E-02 | -0.26859115E-04 |
44 | 5 | -0.10799279E-03 | 0.53275402E-06 | -0.22440051 | 0.19621166E-02 |
45 | 4 | 0.22736042E-02 | 0.24052495E-04 | 4.8407977 | -0.45373149E-01 |
46 | 3 | -0.19287081E-01 | 0.18995237E-03 | -38.084949 | 0.39935605 |
47 | 2 | 0.67516478E-01 | 0.31394945E-03 | 116.60756 | -1.4195928 |
48 | 1 | -0.96817688E-01 | 0.94848058E-04 | -143.98006 | 2.0502357 |
49 | 0 | 0.47046370E-01 | 0.22824214E-05 | 60.838472 | |
50 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
51 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
52 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
53 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
54 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
55 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
56 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
57 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
58 | 7 | -0.15410587E-08 | -0.27131508E-15 | 0.13739895E-13 | -0.20869099E-15 |
59 | 6 | 0.75948721E-05 | 0.52202150E-08 | 0.31841660E-02 | -0.26711453E-04 |
60 | 5 | -0.54825752E-03 | 0.30939483E-05 | -0.22340036 | 0.19532886E-02 |
61 | 4 | 0.12624073E-01 | 0.14086823E-03 | 4.8241453 | -0.45213070E-01 |
62 | 3 | -0.11089483 | 0.11205317E-02 | -37.990908 | 0.39831653 |
63 | 2 | 0.39381345 | 0.18644394E-02 | 116.42457 | -1.4171450 |
64 | 1 | -0.56844024 | 0.56830838E-03 | -143.87235 | 2.0484654 |
65 | 0 | 0.27714917 | 0.13715070E-04 | 60.838472 | |
66 | 7 | -0.91256693E-09 | -0.65654920E-16 | 0.14763662E-14 | 0.25811017E-17 |
67 | 6 | 0.12659591E-04 | 0.87293215E-08 | 0.31698558E-02 | -0.26591407E-04 |
68 | 5 | -0.91895148E-03 | 0.51830142E-05 | -0.22258679 | 0.19461077E-02 |
69 | 4 | 0.21183618E-01 | 0.23613386E-03 | 4.8105909 | -0.45082779E-01 |
70 | 3 | -0.18612912 | 0.18798277E-02 | -37.914317 | 0.39746999 |
71 | 2 | 0.66101200 | 0.31293459E-02 | 116.27548 | -1.4151508 |
72 | 1 | -0.95411819 | 0.95507326E-03 | -143.78458 | 2.0470226 |
73 | 0 | 0.46518638 | 0.22828278E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 30 | 1 | VerySmooth | 3.241 | 0.252 | 0.162 | 0.276 |
2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 31 | 1 | VerySmooth | 4.262 | 0.355 | 0.203 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.20312 | 0.36283 | 0.36283 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CORE_RETAIL | 16 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CORE_RETAIL | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK | 0.1514 | 11722.8 | 0.731 | 0.1915 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BACK_SPACE_WALL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
3 | BACK_SPACE_WALL_NORTH | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
4 | BACK_SPACE_WALL_NORTH_DOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | 0 | 330.83 | 149.77 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
9 | BACK_SPACE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
11 | BACK_SPACE_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
12 | BACK_SPACE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
13 | BACK_SPACE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
14 | BACK_SPACE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 68.27 | 12.40 | 0.00 | 0 | No | No |
15 | CORE_RETAIL_WALL_SOUTH_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
16 | CORE_RETAIL_WALL_SOUTH_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
17 | CORE_RETAIL_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
18 | CORE_RETAIL_WALL_SOUTH_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
19 | CORE_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
20 | CORE_RETAIL_WALL_WEST_2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
24 | CORE_RETAIL_WALL_EAST_2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 4 | No | No |
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
28 | CORE_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
29 | CORE_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
30 | CORE_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
31 | SKYLIGHTS_R4C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
32 | SKYLIGHTS_R4C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
33 | SKYLIGHTS_R4C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
34 | SKYLIGHTS_R4C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
35 | SKYLIGHTS_R1C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
36 | SKYLIGHTS_R1C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
37 | SKYLIGHTS_R1C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
38 | SKYLIGHTS_R1C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
39 | SKYLIGHTS_R2C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
40 | SKYLIGHTS_R2C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
41 | SKYLIGHTS_R2C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
42 | SKYLIGHTS_R2C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
43 | SKYLIGHTS_R3C2 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
44 | SKYLIGHTS_R3C1 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
45 | SKYLIGHTS_R3C3 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
46 | SKYLIGHTS_R3C4 | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 2 | No | No |
47 | CORE_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 58.54 | 36.99 | 6.66E-002 | 0 | No | No |
48 | POINT_OF_SALE_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
50 | POINT_OF_SALE_WALL_EAST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
51 | POINT_OF_SALE_WALL_WEST | 0 | 257.68 | 96.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
52 | POINT_OF_SALE_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
53 | POINT_OF_SALE_WALL_EAST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
54 | POINT_OF_SALE_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
55 | POINT_OF_SALE_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
56 | POINT_OF_SALE_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
57 | FRONT_RETAIL_WALLL_EAST | 0 | 257.68 | 149.77 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
58 | FRONT_RETAIL_WALL_WEST_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
59 | FRONT_RETAIL_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
60 | FRONT_RETAIL_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 4 | No | No |
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 1 | No | No |
62 | FRONT_RETAIL_WALL_WEST_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
63 | FRONT_RETAIL_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
64 | FRONT_RETAIL_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
65 | FRONT_RETAIL_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 31.14 | 9.69 | 0.20 | 0 | No | No |
66 | FRONT_ENTRY_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
67 | FRONT_ENTRY_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
68 | FRONT_ENTRY_WALL_SOUTH | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 4 | No | No |
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | 0 | 330.83 | 120.73 | 6.10 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 1 | No | No |
70 | FRONT_ENTRY_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
71 | FRONT_ENTRY_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
72 | FRONT_ENTRY_ROOF | 0 | 2293.99 | 205.08 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
73 | FRONT_ENTRY_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 6.10 | 4.00 | 3.43 | 0.32 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | BACK_SPACE_INFILTRATION | INFIL_SCH_PNNL | BACK_SPACE | 379.89 | 61.3 | 0.249 | 6.557E-004 | 2.976E-004 | 0.387 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | CORE_RETAIL_INFILTRATION | INFIL_SCH_PNNL | CORE_RETAIL | 1600.48 | 258.4 | 0.204 | 1.274E-004 | 1.036E-004 | 7.518E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | POINT_OF_SALE_INFILTRATION | INFIL_SCH_PNNL | POINT_OF_SALE | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | FRONT_RETAIL_INFILTRATION | INFIL_SCH_PNNL | FRONT_RETAIL | 150.81 | 24.4 | 0.108 | 7.158E-004 | 3.169E-004 | 0.422 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | FRONT_ENTRY_INFILTRATION | INFIL_SCH_PNNL | FRONT_ENTRY | 12.00 | 0.0 | 1.387E-002 | 1.156E-003 | 3.812E-004 | 0.682 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | FRONT_ENTRY_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | FRONT_ENTRY | 12.00 | 0.0 | 1.419 | 0.118 | 3.899E-002 | 69.771 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BACK_SPACE | Mixing/Well-Stirred |
2 | CORE_RETAIL | Mixing/Well-Stirred |
3 | POINT_OF_SALE | Mixing/Well-Stirred |
4 | FRONT_RETAIL | Mixing/Well-Stirred |
5 | FRONT_ENTRY | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone BACK_SPACE | 1.2000 |
3 | Zone CORE_RETAIL | 1.2000 |
4 | Zone POINT_OF_SALE | 1.2000 |
5 | Zone FRONT_RETAIL | 1.2000 |
6 | Zone FRONT_ENTRY | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BACK_SPACE | Cooling | 33022.69508 | 39627.23409 | 2.49277 | 2.99133 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.11023E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
2 | BACK_SPACE | Heating | 23579.85157 | 28295.82189 | 1.01862 | 1.22235 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 379.89000 | 61.34184 | 0.23157 | 0.00000 |
3 | CORE_RETAIL | Cooling | 100497.28767 | 120596.74521 | 7.31804 | 8.78165 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.11022E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
4 | CORE_RETAIL | Heating | 50455.95149 | 60547.14179 | 2.13476 | 2.56171 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 1600.48290 | 258.43418 | 1.89021 | 0.00000 |
5 | POINT_OF_SALE | Cooling | 17107.65286 | 20529.18343 | 1.29139 | 1.54967 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.11023E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
6 | POINT_OF_SALE | Heating | 10541.68498 | 12650.02197 | 0.45640 | 0.54768 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
7 | FRONT_RETAIL | Cooling | 14983.18970 | 17979.82765 | 1.13102 | 1.35723 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.11023E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
8 | FRONT_RETAIL | Heating | 10533.75677 | 12640.50813 | 0.45605 | 0.54726 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 150.81000 | 24.35169 | 0.17811 | 0.00000 |
9 | FRONT_ENTRY | Cooling | 0.00000 | 0.00000 | 0.00000 | 1.41723E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00000 | 9.11023E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 | |
10 | FRONT_ENTRY | Heating | 17313.82692 | 20776.59230 | 0.60228 | 0.72274 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30000 | 6.07234E-003 | 12.00000 | 0.00000 | 1.41723E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC:1 | Cooling | Sensible | 43876.26 | 2.99133 | 2.99133 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
2 | PSZ-AC:1 | Heating | Sensible | 31515.06 | 1.22235 | 1.22235 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PSZ-AC:2 | Cooling | Sensible | 151347.17 | 8.89720 | 8.89720 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
4 | PSZ-AC:2 | Heating | Sensible | 90346.07 | 2.56171 | 2.56171 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PSZ-AC:3 | Cooling | Sensible | 23951.05 | 1.54967 | 1.54967 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
6 | PSZ-AC:3 | Heating | Sensible | 15403.07 | 0.54768 | 0.54768 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | PSZ-AC:4 | Cooling | Sensible | 21502.13 | 1.35723 | 1.35723 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | PSZ-AC:4 | Heating | Sensible | 15393.63 | 0.54726 | 0.54726 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BACK_SPACE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.99133 |
2 | AirTerminal:SingleDuct:Uncontrolled | CORE_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 8.78165 |
3 | AirTerminal:SingleDuct:Uncontrolled | POINT_OF_SALE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54967 |
4 | AirTerminal:SingleDuct:Uncontrolled | FRONT_RETAIL DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35723 |
5 | ZoneHVAC:UnitHeater | FRONT_ENTRY UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.72274 |
6 | Fan:ConstantVolume | FRONT_ENTRY UNIT HEATERFAN | Design Size Maximum Flow Rate [m3/s] | 0.72274 |
7 | Coil:Heating:Fuel | FRONT_ENTRY UNIT HEATER COIL | Design Size Nominal Capacity [W] | 20778.58333 |
8 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.99133 |
9 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.99133 |
10 | AirLoopHVAC | PSZ-AC:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.99133 |
11 | AirLoopHVAC | PSZ-AC:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.99133 |
12 | AirLoopHVAC | PSZ-AC:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.99133 |
13 | AirLoopHVAC | PSZ-AC:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.99133 |
14 | AirLoopHVAC | PSZ-AC:1 | User Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-AC:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
16 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 8.78165 |
17 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 8.78165 |
18 | AirLoopHVAC | PSZ-AC:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.78165 |
19 | AirLoopHVAC | PSZ-AC:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 8.78165 |
20 | AirLoopHVAC | PSZ-AC:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.89720 |
21 | AirLoopHVAC | PSZ-AC:2 | Adjusted Main Design Air Flow Rate [m3/s] | 8.89720 |
22 | AirLoopHVAC | PSZ-AC:2 | User Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-AC:2 | Calculated Heating Air Flow Ratio [] | 0.98701 |
24 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.54967 |
25 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.54967 |
26 | AirLoopHVAC | PSZ-AC:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.54967 |
27 | AirLoopHVAC | PSZ-AC:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.54967 |
28 | AirLoopHVAC | PSZ-AC:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.54967 |
29 | AirLoopHVAC | PSZ-AC:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.54967 |
30 | AirLoopHVAC | PSZ-AC:3 | User Heating Air Flow Ratio [] | 1.00000 |
31 | AirLoopHVAC | PSZ-AC:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
32 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35723 |
33 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35723 |
34 | AirLoopHVAC | PSZ-AC:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35723 |
35 | AirLoopHVAC | PSZ-AC:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35723 |
36 | AirLoopHVAC | PSZ-AC:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35723 |
37 | AirLoopHVAC | PSZ-AC:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.35723 |
38 | AirLoopHVAC | PSZ-AC:4 | User Heating Air Flow Ratio [] | 1.00000 |
39 | AirLoopHVAC | PSZ-AC:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
40 | AirLoopHVAC | PSZ-AC:1 | Design Supply Air Flow Rate [m3/s] | 2.99133 |
41 | AirLoopHVAC | PSZ-AC:2 | Design Supply Air Flow Rate [m3/s] | 8.89720 |
42 | AirLoopHVAC | PSZ-AC:3 | Design Supply Air Flow Rate [m3/s] | 1.54967 |
43 | AirLoopHVAC | PSZ-AC:4 | Design Supply Air Flow Rate [m3/s] | 1.35723 |
44 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.99133 |
45 | Controller:OutdoorAir | PSZ-AC:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.23157 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.99133 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.99133 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.99133 |
49 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.97428 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.99133 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.49567 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.99422 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 57629.02700 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 61872.48000 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 30936.24000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 30936.24000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.72524 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.72524 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.72524 |
60 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.72524 |
61 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 61872.48000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 71349.23643 |
63 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
64 | AirLoopHVAC:UnitarySystem | PSZ-AC:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
65 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.99133 |
66 | Fan:SystemModel | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3200.85998 |
67 | Coil:Heating:Fuel | PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 71349.23643 |
68 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.89720 |
69 | Controller:OutdoorAir | PSZ-AC:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.89021 |
70 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 8.89720 |
71 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 8.89720 |
72 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.89720 |
73 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.87215 |
74 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 8.89720 |
75 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 4.44860 |
76 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 5.93147 |
77 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 207722.50043 |
78 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 219554.75000 |
79 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 109777.37500 |
80 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 109777.37500 |
81 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.67763 |
82 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.67763 |
83 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.67763 |
84 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.67763 |
85 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 219554.75000 |
86 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 231256.18812 |
87 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
88 | AirLoopHVAC:UnitarySystem | PSZ-AC:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
89 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 8.89720 |
90 | Fan:SystemModel | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 14893.16336 |
91 | Coil:Heating:Fuel | PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 231256.18812 |
92 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.54967 |
93 | Controller:OutdoorAir | PSZ-AC:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
94 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.54967 |
95 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.54967 |
96 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.54967 |
97 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02278 |
98 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.54967 |
99 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77484 |
100 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03311 |
101 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 30999.45092 |
102 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 33174.34000 |
103 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 16587.17000 |
104 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 16587.17000 |
105 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.71529 |
106 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.71529 |
107 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.71529 |
108 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.71529 |
109 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 33174.34000 |
110 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37969.94226 |
111 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
112 | AirLoopHVAC:UnitarySystem | PSZ-AC:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
113 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.54967 |
114 | Fan:SystemModel | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1658.21619 |
115 | Coil:Heating:Fuel | PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 37969.94226 |
116 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35723 |
117 | Controller:OutdoorAir | PSZ-AC:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.17811 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35723 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35723 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35723 |
121 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89577 |
122 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35723 |
123 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67862 |
124 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.90482 |
125 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Total Cooling Capacity [W] | 28016.47996 |
126 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Total Cooling Capacity [W] | 29907.50000 |
127 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Total Cooling Capacity [W] | 14953.75000 |
128 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Total Cooling Capacity [W] | 14953.75000 |
129 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 Design Size Rated Sensible Heat Ratio | 0.70719 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 2 User-Specified Rated Sensible Heat Ratio | 0.70719 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 Design Size Rated Sensible Heat Ratio | 0.70719 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Speed 1 User-Specified Rated Sensible Heat Ratio | 0.70719 |
133 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29907.50000 |
134 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33635.78345 |
135 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
136 | AirLoopHVAC:UnitarySystem | PSZ-AC:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
137 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35723 |
138 | Fan:SystemModel | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1502.66584 |
139 | Coil:Heating:Fuel | PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Design Size Nominal Capacity [W] | 33635.78345 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 59520.4 | 11.43 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 212536.5 | 13.88 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 31955.1 | 111.01 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 28839.1 | 135.33 |
Zone Name | # Surfaces | |
1 | BACK_SPACE | 14 |
2 | CORE_RETAIL | 33 |
3 | POINT_OF_SALE | 9 |
4 | FRONT_RETAIL | 9 |
5 | FRONT_ENTRY | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BACK_SPACE_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 90.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BACK_SPACE_WALL_EAST_ROLLDOOR | Door | BACK_SPACE_WALL_EAST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 90.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
3 | BACK_SPACE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 304.63 | 330.83 | 304.63 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BACK_SPACE_WALL_NORTH_DOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | BACK_SPACE_WALL_NORTH_DOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
6 | BACK_SPACE_WALL_NORTH_ROLLDOOR1 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
7 | BACK_SPACE_WALL_NORTH_ROLLDOOR2 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
8 | BACK_SPACE_WALL_NORTH_ROLLDOOR3 | Door | BACK_SPACE_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
9 | BACK_SPACE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 35.24 | 42.67 | 35.24 | 270.00 | 90.00 | 7.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | BACK_SPACE_WALL_WEST_ROLLDOOR | Door | BACK_SPACE_WALL_WEST | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 8.239 | 8.239 | 7.43 | 7.43 | 7.43 | 270.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
11 | BACK_SPACE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 180.00 | 90.00 | 54.27 | 6.10 | 0.00 | CORE_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | BACK_SPACE_FLOOR | Floor | CTF - ConductionTransferFunction | BACK_SPACE_FLOOR_FFACTOR | 0.235 | 0.223 | 379.89 | 379.89 | 379.89 | 90.00 | 180.00 | 7.00 | 54.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | BACK_SPACE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 379.89 | 379.89 | 379.89 | 90.00 | 0.00 | 7.00 | 54.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
14 | BACK_SPACE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 759.78 | 759.78 | 759.78 | 0.00 | 90.00 | 759.78 | 1.00 | 0.00 | BACK_SPACE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | CORE_RETAIL_WALL_SOUTH_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | FRONT_RETAIL_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | CORE_RETAIL_WALL_SOUTH_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | POINT_OF_SALE_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | CORE_RETAIL_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | CORE_RETAIL_WALL_SOUTH_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | CORE_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 330.83 | 330.83 | 330.83 | 0.00 | 90.00 | 54.27 | 6.10 | 0.00 | BACK_SPACE_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 270.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_RETAIL_WALL_WEST_2_DOOR3 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
22 | CORE_RETAIL_WALL_WEST_2_DOOR2 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | CORE_RETAIL_WALL_WEST_2_DOOR1 | Door | CORE_RETAIL_WALL_WEST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
24 | CORE_RETAIL_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 172.58 | 178.43 | 172.58 | 90.00 | 90.00 | 29.27 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
25 | CORE_RETAIL_WALL_EAST_2_DOOR1 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
26 | CORE_RETAIL_WALL_EAST_2_DOOR2 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
27 | CORE_RETAIL_WALL_EAST_2_DOOR3 | Door | CORE_RETAIL_WALL_EAST_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
28 | CORE_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_RETAIL_FLOOR_FFACTOR | 4.655E-002 | 4.603E-002 | 1600.48 | 1600.48 | 1600.48 | 0.00 | 180.00 | 40.01 | 40.01 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
30 | CORE_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1576.70 | 1600.48 | 1576.70 | 180.00 | 0.00 | 40.01 | 40.01 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
31 | SKYLIGHTS_R4C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
32 | SKYLIGHTS_R4C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
33 | SKYLIGHTS_R4C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
34 | SKYLIGHTS_R4C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
35 | SKYLIGHTS_R1C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
36 | SKYLIGHTS_R1C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
37 | SKYLIGHTS_R1C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
38 | SKYLIGHTS_R1C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
39 | SKYLIGHTS_R2C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
40 | SKYLIGHTS_R2C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
41 | SKYLIGHTS_R2C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
42 | SKYLIGHTS_R2C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
43 | SKYLIGHTS_R3C2 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
44 | SKYLIGHTS_R3C1 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 1.11E-016 | 1.00 | 4 |
45 | SKYLIGHTS_R3C3 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
46 | SKYLIGHTS_R3C4 | Window | CORE_RETAIL_ROOF | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | N/A | 4.262 | No | 1.49 | 1.49 | 1.49 | 180.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
47 | CORE_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3200.97 | 3200.97 | 3200.97 | 0.00 | 90.00 | 3200.97 | 1.00 | 0.00 | CORE_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
48 | POINT_OF_SALE_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | POINT_OF_SALE_WALL_SOUTH_GLAZING | Window | POINT_OF_SALE_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
50 | POINT_OF_SALE_WALL_EAST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | POINT_OF_SALE_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 270.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | POINT_OF_SALE_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
53 | POINT_OF_SALE_WALL_EAST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | POINT_OF_SALE_FLOOR | Floor | CTF - ConductionTransferFunction | POINT_OF_SALE_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 180.00 | 180.00 | 25.14 | 6.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
55 | POINT_OF_SALE_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 180.00 | 0.00 | 25.14 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
56 | POINT_OF_SALE_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | POINT_OF_SALE_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
57 | FRONT_RETAIL_WALLL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 36.58 | 36.58 | 36.58 | 90.00 | 90.00 | 6.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | FRONT_RETAIL_WALL_WEST_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_ENTRY_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | FRONT_RETAIL_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 153.22 | 153.22 | 153.22 | 0.00 | 90.00 | 25.14 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | FRONT_RETAIL_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 115.17 | 153.22 | 115.17 | 180.00 | 90.00 | 25.14 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | FRONT_RETAIL_WALL_SOUTH_GLAZING | Window | FRONT_RETAIL_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 38.05 | 38.05 | 38.05 | 180.00 | 90.00 | 25.04 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | FRONT_RETAIL_WALL_WEST_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | FRONT_RETAIL_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_RETAIL_FLOOR_FFACTOR | 0.272 | 0.255 | 150.81 | 150.81 | 150.81 | 90.00 | 180.00 | 6.00 | 25.14 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
64 | FRONT_RETAIL_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 150.81 | 150.81 | 150.81 | 90.00 | 0.00 | 6.00 | 25.14 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
65 | FRONT_RETAIL_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 301.62 | 301.62 | 301.62 | 0.00 | 90.00 | 301.62 | 1.00 | 0.00 | FRONT_RETAIL_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
66 | FRONT_ENTRY_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 90.00 | 90.00 | 3.00 | 6.10 | 0.00 | FRONT_RETAIL_WALL_WEST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
67 | FRONT_ENTRY_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.38 | 24.38 | 24.38 | 0.00 | 90.00 | 4.00 | 6.10 | 0.00 | CORE_RETAIL_WALL_SOUTH_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | FRONT_ENTRY_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 5.069 | 2.882 | 16.55 | 24.38 | 16.55 | 180.00 | 90.00 | 4.00 | 6.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | FRONT_ENTRY_WALL_SOUTH_GLAZING | Window | FRONT_ENTRY_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.83 | 7.83 | 7.83 | 180.00 | 90.00 | 3.00 | 2.61 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | FRONT_ENTRY_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.29 | 18.29 | 18.29 | 270.00 | 90.00 | 3.00 | 6.10 | 0.00 | POINT_OF_SALE_WALL_EAST_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | FRONT_ENTRY_FLOOR | Floor | CTF - ConductionTransferFunction | FRONT_ENTRY_FLOOR_FFACTOR | 0.451 | 0.406 | 12.00 | 12.00 | 12.00 | 180.00 | 180.00 | 4.00 | 3.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
72 | FRONT_ENTRY_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 12.00 | 12.00 | 12.00 | 180.00 | 0.00 | 4.00 | 3.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
73 | FRONT_ENTRY_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 24.00 | 1.00 | 0.00 | FRONT_ENTRY_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 9 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BACK_SPACE | RunPeriod: RUNPERIOD 1 | 7.8780611080E-002 | 0.3482675251 | Pass | Pass | 6.0292701818E-002 | 0.2438427459 | Pass | Pass |
2 | CORE_RETAIL | RunPeriod: RUNPERIOD 1 | 3.8539759593E-002 | 0.1496019706 | Pass | Pass | 0.1056658611 | 0.3177160100 | Pass | Pass |
3 | POINT_OF_SALE | RunPeriod: RUNPERIOD 1 | 8.0758889315E-002 | 0.2202400484 | Pass | Pass | 0.1645040485 | 0.7859012725 | Pass | Pass |
4 | FRONT_RETAIL | RunPeriod: RUNPERIOD 1 | 7.0950027068E-002 | 0.2586803092 | Pass | Pass | 0.1144183278 | 0.3157862636 | Pass | Pass |
5 | FRONT_ENTRY | RunPeriod: RUNPERIOD 1 | 0.1619726848 | 0.3790247279 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BACK_SPACE_WALL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 90.00 | 90.00 | E |
BACK_SPACE_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 330.83 | 304.63 | 0.00 | 90.00 | N |
BACK_SPACE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 42.67 | 35.24 | 270.00 | 90.00 | W |
BACK_SPACE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 379.89 | 379.89 | 90.00 | 0.00 | |
CORE_RETAIL_WALL_WEST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 270.00 | 90.00 | W |
CORE_RETAIL_WALL_EAST_2 | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 178.43 | 172.58 | 90.00 | 90.00 | E |
CORE_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1600.48 | 1576.70 | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
POINT_OF_SALE_WALL_WEST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 270.00 | 90.00 | W |
POINT_OF_SALE_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 180.00 | 0.00 | |
FRONT_RETAIL_WALLL_EAST | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 36.58 | 36.58 | 90.00 | 90.00 | E |
FRONT_RETAIL_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 153.22 | 115.17 | 180.00 | 90.00 | S |
FRONT_RETAIL_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 150.81 | 150.81 | 90.00 | 0.00 | |
FRONT_ENTRY_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 2.882 | 5.069 | 24.38 | 16.55 | 180.00 | 90.00 | S |
FRONT_ENTRY_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 12.00 | 12.00 | 180.00 | 0.00 | |
BACK_SPACE_FLOOR | BACK_SPACE_FLOOR_FFACTOR | 1.00 | 0.235 | 379.89 | 379.89 | 90.00 | 180.00 | ||
CORE_RETAIL_FLOOR | CORE_RETAIL_FLOOR_FFACTOR | 1.00 | 0.047 | 1600.48 | 1600.48 | 0.00 | 180.00 | ||
POINT_OF_SALE_FLOOR | POINT_OF_SALE_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 180.00 | 180.00 | ||
FRONT_RETAIL_FLOOR | FRONT_RETAIL_FLOOR_FFACTOR | 1.00 | 0.272 | 150.81 | 150.81 | 90.00 | 180.00 | ||
FRONT_ENTRY_FLOOR | FRONT_ENTRY_FLOOR_FFACTOR | 1.00 | 0.451 | 12.00 | 12.00 | 180.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
SKYLIGHTS_R4C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R4C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R1C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R2C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C2 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C1 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C3 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
SKYLIGHTS_R3C4 | NONRESSKYLIGHT_U_0.75_SHGC_0.35 | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.355 | 0.401 | 0.000 | 0.000 | No | CORE_RETAIL_ROOF | 180.00 | 0.00 | |
POINT_OF_SALE_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.57_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.241 | 0.252 | 0.276 | No | POINT_OF_SALE_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_RETAIL_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.57_SHGC_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 3.241 | 0.252 | 0.276 | No | FRONT_RETAIL_WALL_SOUTH | 180.00 | 90.00 | S | ||
FRONT_ENTRY_WALL_SOUTH_GLAZING | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.83 | 0.00 | 0.00 | 7.83 | 7.83 | 3.241 | 0.252 | 0.276 | No | FRONT_ENTRY_WALL_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 107.72 | 3.466 | 0.275 | 0.303 | ||||||||||||
North Total or Average | 0.00 | - | - | - | ||||||||||||
Non-North Total or Average | 107.72 | 3.466 | 0.275 | 0.303 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BACK_SPACE_WALL_EAST_ROLLDOOR | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_EAST |
BACK_SPACE_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR1 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR2 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_NORTH_ROLLDOOR3 | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_NORTH |
BACK_SPACE_WALL_WEST_ROLLDOOR | OVERHEAD DOOR_CON | 3.689 | 8.239 | 7.43 | BACK_SPACE_WALL_WEST |
CORE_RETAIL_WALL_WEST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_WEST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_WEST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
CORE_RETAIL_WALL_EAST_2_DOOR3 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | CORE_RETAIL_WALL_EAST_2 |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
SKYLIGHTS_R4C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R4C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHTS_R3C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
POINT_OF_SALE_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_RETAIL_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
FRONT_ENTRY_WALL_SOUTH_GLAZING | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BACK_SPACE_LIGHTS | BACK_SPACE | 7.5670 | 379.89 | 2874.64 | LightsWired | BLDG_LIGHT_BACK_SCH | 55.08 | 168.00 | 54.34 | 0.0000 | Y | 29.32 |
CORE_RETAIL_LIGHTS | CORE_RETAIL | 15.5000 | 1600.48 | 24807.53 | LightsWired | BLDG_LIGHT_CORE_SCH | 69.21 | 168.00 | 57.27 | 0.0000 | Y | 266.70 |
POINT_OF_SALE_LIGHTS | POINT_OF_SALE | 15.5000 | 150.81 | 2337.56 | LightsWired | BLDG_LIGHT_SCH | 69.21 | 168.00 | 68.25 | 0.0000 | Y | 29.95 |
FRONT_RETAIL_LIGHTS | FRONT_RETAIL | 15.5000 | 150.81 | 2337.56 | LightsWired | BLDG_LIGHT_FRONT_SCH | 67.15 | 168.00 | 66.22 | 0.0000 | Y | 29.06 |
FRONT_ENTRY_LIGHTS | FRONT_ENTRY | 9.6875 | 12.00 | 116.25 | LightsWired | BLDG_LIGHT_ENTRY_SCH | 57.54 | 168.00 | 56.76 | 0.0000 | Y | 1.24 |
Interior Lighting Total | 14.1559 | 2293.99 | 32473.54 | 356.27 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CORE_RETAIL_DAYLREFPT1 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24807.53 | 6201.88 |
CORE_RETAIL_DAYLREFPT2 | CORE_RETAIL | CORE_RETAIL_DAYLCTRL | SplitFlux | Stepped | 0.25 | 24807.53 | 6201.88 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 316.30 | AstronomicalClock | - | 41.75 | 41.75 | 2.48 | |
EXTERIOR_LIGHTS_B | 4328.00 | AstronomicalClock | - | 83.75 | 71.15 | 57.81 | |
Exterior Lighting Total | 4644.30 | 60.29 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 61872.48 | 44872.40 | 17000.08 | 0.73 | 3.73 | |||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 219554.75 | 148776.89 | 70777.86 | 0.68 | 3.40 | |||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 33174.34 | 23729.27 | 9445.07 | 0.72 | 3.80 | |||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | 29907.50 | 21150.28 | 8757.22 | 0.71 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | 59520.4 | 11.43 | ||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | 212536.5 | 13.88 | ||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | 31955.1 | 111.01 | ||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | 28839.1 | 135.33 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FRONT_ENTRY UNIT HEATER COIL | Coil:Heating:Fuel | 20778.58 | 0.80 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 71349.24 | 0.80 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 231256.19 | 0.80 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 37969.94 | 0.80 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | 33635.78 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.72 | 800.19 | 1107.16 | 1.00 | 1.48 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.99 | 3200.86 | 1070.05 | 1.00 | 1.26 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 |
PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.61 | 1018.41 | 8.90 | 14893.16 | 1673.92 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 |
PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.55 | 1658.22 | 1070.05 | 1.00 | 1.36 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 |
PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.36 | 1502.67 | 1107.16 | 1.00 | 1.33 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK | WaterHeater:Mixed | 0.15 | 11722.84 | 0.82 | 0.73 | 0.19 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 33022.70 | 39627.23 | 104.31 | 2.493 | 2.991 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 23.89 | 23.89 | 0.00742 | 41.03 | 0.00911 | 0.232 | 0.00 |
CORE_RETAIL | 100497.29 | 120596.75 | 75.35 | 7.318 | 8.782 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 23.89 | 23.89 | 0.00783 | 34.82 | 0.00911 | 1.890 | 0.00 |
POINT_OF_SALE | 17107.65 | 20529.18 | 136.13 | 1.291 | 1.550 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 23.89 | 23.89 | 0.00732 | 41.16 | 0.00911 | 0.178 | 0.00 |
FRONT_RETAIL | 14983.19 | 17979.83 | 119.22 | 1.131 | 1.357 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 23.89 | 23.89 | 0.00737 | 41.61 | 0.00911 | 0.178 | 0.00 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 | 0.000 | 0.014 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 40.99 | 100.00 | 0.00001 | 42.00 | 0.00911 | 0.014 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BACK_SPACE | 23579.85 | 28295.82 | 74.48 | 1.019 | 1.222 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00798 | 6.30 | 0.00607 | 0.232 | 0.00 |
CORE_RETAIL | 50455.95 | 60547.14 | 37.83 | 2.135 | 2.562 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00798 | 6.30 | 0.00607 | 1.890 | 0.00 |
POINT_OF_SALE | 10541.68 | 12650.02 | 83.88 | 0.456 | 0.548 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00798 | 6.30 | 0.00607 | 0.178 | 0.00 |
FRONT_RETAIL | 10533.76 | 12640.51 | 83.82 | 0.456 | 0.547 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.11 | 0.00798 | 6.30 | 0.00607 | 0.178 | 0.00 |
FRONT_ENTRY | 17313.83 | 20776.59 | 1731.38 | 0.602 | 0.723 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 16.00 | 15.98 | 0.00663 | 6.30 | 0.00607 | 0.014 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC:1 | 2.99 | 2.99 | 1.22 | 1.22 | 2.9913 | 2.9913 | 2.9913 | 1.0000 | 1.0000 |
PSZ-AC:2 | 8.90 | 8.90 | 2.56 | 2.56 | 8.8972 | 8.7816 | 8.8972 | 0.9870 | 1.0000 |
PSZ-AC:3 | 1.55 | 1.55 | 0.55 | 0.55 | 1.5497 | 1.5497 | 1.5497 | 1.0000 | 1.0000 |
PSZ-AC:4 | 1.36 | 1.36 | 0.55 | 0.55 | 1.3572 | 1.3572 | 1.3572 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | 20778.583 | 20778.583 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 20778.58 | 20778.58 | 0.722739 | 15.79 | 11.21 | 0.00662048 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 15.98 | 0.00663144 | 57.3644 | 20776.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:1 | 30936.240 | 0.000 | 2.991330 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 30936.24 | 28600.68 | 2.991330 | 25.25 | 15.73 | 0.00755103 | 12.80 | 10.33 | 0.00700000 | 41.42 | 0.00911023 | 22.04 | 7.7413 | 23.89 | 0.00741973 | 39.2633 | 32994.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:1 | 71349.236 | 71349.236 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 71349.24 | 71349.24 | 2.991326 | 18.14 | 13.14 | 0.00761476 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 7.7413 | 21.11 | 0.00797526 | 49.9204 | 23579.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:2 | 109777.375 | 0.000 | 8.897200 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | 109777.38 | 97899.80 | 8.897200 | 27.92 | 17.00 | 0.00794654 | 12.80 | 10.33 | 0.00700000 | 42.00 | 0.00911023 | 22.20 | 21.2450 | 23.89 | 0.00783173 | 41.4204 | 93667.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:2 | 231256.188 | 231256.188 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 231256.19 | 231256.19 | 8.897203 | 10.10 | 8.67 | 0.00657258 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 21.2450 | 21.11 | 0.00798071 | 49.9539 | 50455.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:3 | 16587.170 | 0.000 | 1.549670 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 16587.17 | 15424.62 | 1.549670 | 25.93 | 15.96 | 0.00752888 | 12.80 | 10.33 | 0.00700000 | 41.61 | 0.00911023 | 22.09 | 11.4934 | 23.89 | 0.00732260 | 38.7551 | 17091.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:3 | 37969.942 | 37969.942 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37969.94 | 37969.94 | 1.549666 | 16.16 | 12.10 | 0.00735954 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 11.4935 | 21.11 | 0.00797990 | 49.9490 | 10541.68 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC:4 | 14953.750 | 0.000 | 1.357230 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 14953.75 | 13799.56 | 1.357230 | 26.26 | 16.13 | 0.00759770 | 12.80 | 10.33 | 0.00700000 | 41.90 | 0.00911022 | 22.17 | 13.1231 | 23.89 | 0.00736807 | 38.9930 | 14955.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC:4 | 33635.783 | 33635.783 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33635.78 | 33635.78 | 1.357227 | 16.15 | 12.10 | 0.00735903 | 40.00 | 20.85 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 13.1231 | 21.11 | 0.00797984 | 49.9486 | 10533.76 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
FRONT_ENTRY UNIT HEATER COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONT_ENTRY UNIT HEATER | FRONT_ENTRY | N/A | N/A | N/A | Yes | No | unknown | No | 20778.583 | 20778.583 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | FRONT_ENTRY UNIT HEATERFAN | Fan:ConstantVolume | 0.722739 | 0.84834081 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 20778.58 | 20778.58 | 1.0000 | 0.84834081 | 0.722739 | 15.79 | 11.21 | 0.00662048 | 32618.6 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20778.58 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 15.98 | 0.00663144 | 15.98 | 0.00663144 | 57.3644 | 20776.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30936.240 | 0.000 | 2.991330 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.8770 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 30936.24 | 28600.68 | 1.0000 | 3.51117966 | 2.991330 | 25.25 | 15.73 | 0.00755103 | 44607.5 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30936.24 | 41.42 | 0.00911023 | 22.04 | 0.23156651 | 7.7413 | 23.89 | 0.00742008 | 23.89 | 0.00741973 | 39.2633 | 32994.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:1 | BACK_SPACE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 71349.236 | 71349.236 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.991326 | 3.51117470 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 71349.24 | 71349.24 | 1.0000 | 3.51117470 | 2.991326 | 18.14 | 13.14 | 0.00761476 | 37529.7 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 71349.24 | 6.30 | 0.00607234 | 6.30 | 0.23156651 | 7.7413 | 20.91 | 0.00797526 | 21.11 | 0.00797526 | 49.9204 | 23579.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 109777.375 | 0.000 | 8.897200 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6122 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:20:00 | 109777.38 | 97899.80 | 1.0000 | 10.44340400 | 8.897200 | 27.92 | 17.00 | 0.00794654 | 48344.2 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 109777.38 | 42.00 | 0.00911023 | 22.20 | 1.89021192 | 21.2450 | 23.89 | 0.00761300 | 23.89 | 0.00783173 | 41.4204 | 93667.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:2 | CORE_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 231256.188 | 231256.188 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 8.897203 | 10.44340761 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 231256.19 | 231256.19 | 1.0000 | 10.44340761 | 8.897203 | 10.10 | 8.67 | 0.00657258 | 26708.9 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 231256.19 | 6.30 | 0.00607234 | 6.30 | 1.89021192 | 21.2450 | 20.79 | 0.00798071 | 21.11 | 0.00798071 | 49.9539 | 50455.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16587.170 | 0.000 | 1.549670 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.8358 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 16587.17 | 15424.62 | 1.0000 | 1.81898011 | 1.549670 | 25.93 | 15.96 | 0.00752888 | 45246.9 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16587.17 | 41.61 | 0.00911023 | 22.09 | 0.17811053 | 11.4934 | 23.89 | 0.00732307 | 23.89 | 0.00732260 | 38.7551 | 17091.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:3 | POINT_OF_SALE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37969.942 | 37969.942 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.549666 | 1.81897576 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37969.94 | 37969.94 | 1.0000 | 1.81897576 | 1.549666 | 16.16 | 12.10 | 0.00735954 | 34860.4 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37969.94 | 6.30 | 0.00607234 | 6.30 | 0.17811053 | 11.4935 | 20.91 | 0.00797990 | 21.11 | 0.00797990 | 49.9490 | 10541.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 14953.750 | 0.000 | 1.357230 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.9637 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 14953.75 | 13799.56 | 1.0000 | 1.59309684 | 1.357230 | 26.26 | 16.13 | 0.00759770 | 45755.9 | 12.80 | 10.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14953.75 | 41.90 | 0.00911022 | 22.17 | 0.17811053 | 13.1231 | 23.89 | 0.00736874 | 23.89 | 0.00736807 | 38.9930 | 14955.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC:4 | FRONT_RETAIL | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33635.783 | 33635.783 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.357227 | 1.59309343 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33635.78 | 33635.78 | 1.0000 | 1.59309343 | 1.357227 | 16.15 | 12.10 | 0.00735903 | 34855.4 | 40.00 | 20.85 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33635.78 | 6.30 | 0.00607234 | 6.30 | 0.17811053 | 13.1231 | 20.91 | 0.00797984 | 21.11 | 0.00797984 | 49.9486 | 10533.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BACK_SPACE | 3058.33 | 1406.00 | 86.67 |
CORE_RETAIL | 3409.00 | 1057.50 | 263.67 |
POINT_OF_SALE | 4016.17 | 386.33 | 17.83 |
FRONT_RETAIL | 3861.00 | 559.67 | 72.67 |
FRONT_ENTRY | 0.00 | 0.00 | 0.00 |
Facility | 4103.33 | 1655.33 | 336.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BACK_SPACE | 3.83 | 58.00 | 0.00 | 0.00 |
CORE_RETAIL | 0.00 | 0.00 | 0.00 | 0.00 |
POINT_OF_SALE | 0.33 | 92.83 | 0.00 | 0.00 |
FRONT_RETAIL | 0.50 | 68.33 | 0.00 | 0.00 |
FRONT_ENTRY | 56.00 | 0.00 | 0.00 | 0.00 |
Facility | 59.83 | 103.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.371 | 0.013 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.719 | 0.002 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.719 | 0.014 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.719 | 0.014 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BACK_SPACE | 30.42 | 61.34 | 2317.33 | 0.339 | 0.000 | 0.000 | 0.000 |
CORE_RETAIL | 128.15 | 258.43 | 9762.95 | 0.657 | 0.000 | 0.000 | 0.000 |
POINT_OF_SALE | 12.08 | 24.35 | 919.94 | 0.658 | 0.000 | 0.000 | 0.000 |
FRONT_RETAIL | 12.08 | 24.35 | 919.94 | 0.657 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Surfaces by ClassTotal | Outdoors | |
Wall | 26 | 10 |
Floor | 5 | 5 |
Roof | 5 | 5 |
Internal Mass | 5 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 19 | 19 |
Door | 13 | 13 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 4 |
Conditioned Zones | 5 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1402.05 | 3395.27 | 01-JAN-07:40 | 141825.34 | 10-JUN-16:00 |
Electricity:Building | 550.56 | 3188.54 | 12-FEB-08:50 | 39317.46 | 02-JAN-15:50 |
Electricity:Zone:BACK_SPACE | 79.09 | 597.55 | 01-JAN-00:10 | 4774.71 | 02-JAN-09:10 |
InteriorLights:Electricity | 356.27 | 1416.95 | 12-FEB-08:50 | 28576.57 | 02-JAN-15:50 |
InteriorLights:Electricity:Zone:BACK_SPACE | 29.32 | 143.73 | 01-JAN-00:10 | 2023.29 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 356.27 | 1416.95 | 12-FEB-08:50 | 28576.57 | 02-JAN-15:50 |
Electricity:Zone:CORE_RETAIL | 350.63 | 1798.89 | 12-FEB-08:50 | 26966.36 | 02-JAN-15:50 |
InteriorLights:Electricity:Zone:CORE_RETAIL | 266.70 | 1033.65 | 12-FEB-08:50 | 22326.78 | 02-JAN-15:50 |
Electricity:Zone:POINT_OF_SALE | 82.64 | 597.30 | 01-JAN-00:10 | 5016.52 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:POINT_OF_SALE | 29.95 | 116.88 | 01-JAN-00:10 | 2103.80 | 02-JAN-09:10 |
Electricity:Zone:FRONT_RETAIL | 36.97 | 188.99 | 01-JAN-00:10 | 2474.08 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_RETAIL | 29.06 | 116.88 | 01-JAN-00:10 | 2036.90 | 02-JAN-09:10 |
Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:FRONT_ENTRY | 1.24 | 5.81 | 01-JAN-00:10 | 85.79 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:BACK_SPACE | 49.77 | 453.82 | 01-JAN-00:10 | 2751.42 | 02-JAN-09:10 |
MiscPlug:InteriorEquipment:Electricity | 194.30 | 1771.59 | 01-JAN-00:10 | 10740.89 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:CORE_RETAIL | 83.93 | 765.25 | 01-JAN-00:10 | 4639.58 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:POINT_OF_SALE | 52.69 | 480.42 | 01-JAN-00:10 | 2912.71 | 02-JAN-09:10 |
InteriorEquipment:Electricity:Zone:FRONT_RETAIL | 7.91 | 72.11 | 01-JAN-00:10 | 437.18 | 02-JAN-09:10 |
ElectricityPurchased:Facility | 1402.05 | 3395.27 | 08-JAN-07:40 | 141825.34 | 10-JUN-16:00 |
ElectricityPurchased:Plant | 1402.05 | 3395.27 | 08-JAN-07:40 | 141825.34 | 10-JUN-16:00 |
Cogeneration:ElectricityPurchased | 1402.05 | 3395.27 | 08-JAN-07:40 | 141825.34 | 10-JUN-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1402.05 | 3395.27 | 08-JAN-07:40 | 141825.34 | 10-JUN-16:00 |
ElectricityNet:Plant | 1402.05 | 3395.27 | 08-JAN-07:40 | 141825.34 | 10-JUN-16:00 |
Cogeneration:ElectricityNet | 1402.05 | 3395.27 | 08-JAN-07:40 | 141825.34 | 10-JUN-16:00 |
Electricity:HVAC | 791.20 | 0.00 | 01-JAN-00:10 | 104368.45 | 10-JUN-16:00 |
Fans:Electricity | 179.59 | 0.00 | 01-JAN-00:10 | 16690.25 | 01-JUL-16:00 |
General:Fans:Electricity | 179.59 | 0.00 | 01-JAN-00:10 | 16690.25 | 01-JUL-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 611.60 | 0.00 | 01-JAN-00:10 | 87881.46 | 10-JUN-16:00 |
ExteriorLights:Electricity | 60.29 | 0.00 | 01-JAN-07:20 | 4644.30 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 60.29 | 0.00 | 01-JAN-07:20 | 4644.30 | 01-JAN-06:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 98.98 | 1860.00 | 01-JAN-20:10 | 116396.24 | 02-JAN-07:10 |
Gas:Plant | 85.35 | 1860.00 | 01-JAN-20:10 | 4923.56 | 23-JAN-12:30 |
WaterSystems:Gas | 85.35 | 1860.00 | 01-JAN-20:10 | 4923.56 | 23-JAN-12:30 |
Water Heater:WaterSystems:Gas | 85.35 | 1860.00 | 01-JAN-20:10 | 4923.56 | 23-JAN-12:30 |
Gas:HVAC | 13.63 | 0.00 | 01-JAN-00:10 | 114536.24 | 02-JAN-07:10 |
Heating:Gas | 13.63 | 0.00 | 01-JAN-00:10 | 114536.24 | 02-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water Heater:WaterSystems:Water | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
MainsWater:Facility | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
MainsWater:Plant | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Water Heater:WaterSystems:MainsWater | 134.99 | 0.00 | 01-JAN-00:10 | 0.00 | 01-MAY-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 3430.08 | 0.00 | 01-JAN-00:10 | 410938.56 | 01-JUL-16:00 |
EnergyTransfer:Building | 1226.40 | 0.00 | 01-JAN-00:10 | 145695.52 | 12-JUN-14:40 |
EnergyTransfer:Zone:BACK_SPACE | 222.76 | 0.00 | 01-JAN-00:10 | 38164.80 | 12-JUN-04:10 |
Heating:EnergyTransfer | 6.82 | 0.00 | 01-JAN-00:10 | 70717.48 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:BACK_SPACE | 4.09 | 0.00 | 01-JAN-00:10 | 31652.42 | 01-JAN-07:10 |
Cooling:EnergyTransfer | 1219.58 | 0.00 | 01-JAN-00:10 | 145695.52 | 12-JUN-14:40 |
Cooling:EnergyTransfer:Zone:BACK_SPACE | 218.66 | 0.00 | 01-JAN-00:10 | 38164.80 | 12-JUN-04:10 |
EnergyTransfer:Zone:CORE_RETAIL | 707.90 | 0.00 | 01-JAN-00:10 | 88120.86 | 29-MAY-08:10 |
Heating:EnergyTransfer:Zone:CORE_RETAIL | 2.37 | 0.00 | 01-JAN-00:10 | 52805.34 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_RETAIL | 705.53 | 0.00 | 01-JAN-00:10 | 85103.85 | 12-JUN-14:10 |
EnergyTransfer:Zone:POINT_OF_SALE | 163.90 | 0.00 | 01-JAN-00:10 | 16723.68 | 05-JUL-04:30 |
Heating:EnergyTransfer:Zone:POINT_OF_SALE | 0.10 | 0.00 | 01-JAN-00:10 | 7443.27 | 01-JAN-07:10 |
Cooling:EnergyTransfer:Zone:POINT_OF_SALE | 163.80 | 0.00 | 01-JAN-00:10 | 16723.68 | 05-JUL-04:30 |
EnergyTransfer:Zone:FRONT_RETAIL | 131.82 | 0.00 | 01-JAN-00:10 | 15487.30 | 31-MAY-04:10 |
Heating:EnergyTransfer:Zone:FRONT_RETAIL | 0.23 | 0.00 | 01-JAN-00:10 | 9450.49 | 01-JAN-07:10 |
Cooling:EnergyTransfer:Zone:FRONT_RETAIL | 131.58 | 0.00 | 01-JAN-00:10 | 15487.30 | 31-MAY-04:10 |
EnergyTransfer:Zone:FRONT_ENTRY | 0.02 | 0.00 | 01-JAN-00:10 | 2158.10 | 03-JAN-08:20 |
Heating:EnergyTransfer:Zone:FRONT_ENTRY | 0.02 | 0.00 | 01-JAN-00:10 | 2158.10 | 03-JAN-08:20 |
Cooling:EnergyTransfer:Zone:FRONT_ENTRY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 2203.68 | 0.00 | 01-JAN-00:10 | 288066.44 | 01-JUL-16:00 |
HeatingCoils:EnergyTransfer | 10.90 | 0.00 | 01-JAN-00:10 | 91628.99 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 2192.78 | 0.00 | 01-JAN-00:10 | 288066.44 | 01-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BACK_SPACE | 0.000 | 0.000 | 4.091 | -218.661 | 0.000 | 0.000 | 37.226 | 29.322 | 49.772 | 0.000 | 0.000 | 1.260 | 97.808 | 0.000 | 0.000 | 0.000 | -0.819 | -0.007 |
CORE_RETAIL | 0.000 | 0.000 | 2.373 | -705.522 | 0.000 | 0.000 | 155.503 | 266.698 | 83.927 | 48.956 | 0.000 | 1.067 | 160.817 | 0.000 | -13.058 | 0.000 | -0.762 | -0.004 |
POINT_OF_SALE | 0.000 | 0.000 | 0.100 | -163.797 | 0.000 | 0.000 | 14.595 | 29.949 | 52.689 | 36.042 | 0.000 | 0.533 | 41.175 | 0.000 | -10.825 | 0.000 | -0.462 | -0.001 |
FRONT_RETAIL | 0.000 | 0.000 | 0.234 | -131.581 | 0.000 | 0.000 | 14.638 | 29.059 | 7.908 | 36.006 | 0.000 | 0.541 | 54.010 | 0.000 | -10.390 | 0.000 | -0.425 | -0.001 |
FRONT_ENTRY | 0.020 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.239 | 0.000 | 6.425 | 0.000 | 3.422 | 0.000 | 0.000 | -2.303 | 0.000 | -5.300 | -3.503 |
Total Facility | 0.020 | 0.000 | 6.799 | -1219.561 | 0.000 | 0.000 | 221.962 | 356.267 | 194.297 | 127.429 | 0.000 | 6.823 | 353.811 | 0.000 | -36.576 | 0.000 | -7.768 | -3.515 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 09-MAY-04:01 | 0.00 | 0.00 | 0.00 | -57948.96 | 0.00 | 0.00 | 0.00 | 143.73 | 605.09 | 0.00 | 0.00 | 0.00 | 57200.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_RETAIL | 28-APR-05:01 | 0.00 | 0.00 | 0.00 | -190464.11 | 0.00 | 0.00 | 0.00 | 1240.38 | 1020.33 | 0.00 | 0.00 | 0.00 | 188975.82 | 0.00 | -772.31 | 0.00 | -0.11 | 0.00 |
POINT_OF_SALE | 23-OCT-04:01 | 0.00 | 0.00 | 0.00 | -31583.94 | 0.00 | 0.00 | 0.00 | 116.88 | 640.56 | 0.00 | 0.00 | 0.00 | 31973.92 | 0.00 | -1123.23 | 0.00 | -24.19 | 0.00 |
FRONT_RETAIL | 29-APR-04:01 | 0.00 | 0.00 | 0.00 | -27679.03 | 0.00 | 0.00 | 0.00 | 116.88 | 72.11 | 0.00 | 0.00 | 0.00 | 27992.18 | 0.00 | -502.13 | 0.00 | 0.00 | 0.00 |
FRONT_ENTRY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-MAY-04:01 | 0.00 | 0.00 | 0.00 | -295168.07 | 0.00 | 0.00 | 0.00 | 1623.68 | 2362.12 | 0.00 | 0.00 | 0.00 | 292811.69 | 0.00 | -1629.42 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BACK_SPACE | 01-JAN-07:01 | 0.00 | 0.00 | 69158.34 | 0.00 | 0.00 | 0.00 | 0.00 | 143.73 | 453.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -69755.88 |
CORE_RETAIL | 01-JAN-08:61 | 0.00 | 0.00 | 216425.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1240.38 | 765.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -702.60 | 0.00 | -1.58 | -217726.60 |
POINT_OF_SALE | 01-JAN-07:01 | 0.00 | 0.00 | 35338.40 | 0.00 | 0.00 | 0.00 | 0.00 | 116.88 | 480.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1223.60 | 0.00 | 0.00 | -34712.09 |
FRONT_RETAIL | 01-JAN-07:01 | 0.00 | 0.00 | 31424.56 | 0.00 | 0.00 | 0.00 | 0.00 | 116.88 | 72.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1171.74 | 0.00 | 0.00 | -30441.80 |
FRONT_ENTRY | 03-JAN-08:05 | 3363.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.13 | 0.00 | 36.65 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2467.13 | -971.52 |
Total Facility | 01-JAN-08:61 | 0.00 | 0.00 | 237819.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1623.68 | 1771.59 | 10.50 | 0.00 | 0.00 | 0.00 | 0.00 | -1032.61 | 0.00 | -2082.93 | -238109.37 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.9913 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.9913 | 0.0774 | 1.0000 | 0.2316 | 0.0774 | ||
PSZ-AC:2 | 8.7816 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.8972 | 0.2125 | 1.0000 | 1.8902 | 0.2125 | ||
PSZ-AC:3 | 1.5497 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.5497 | 0.1149 | 1.0000 | 0.1781 | 0.1149 | ||
PSZ-AC:4 | 1.3572 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3572 | 0.1312 | 1.0000 | 0.1781 | 0.1312 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC:1 | 2.9913 | 0.0000 | 61.3418 | 1.0000 | 0.2316 | 2.9913 | 1.0000 | 1.0000 | 0.2316 | 0.0774 | ||
PSZ-AC:2 | 8.7816 | 0.0000 | 258.4342 | 1.0000 | 1.8902 | 8.7816 | 1.0000 | 1.0000 | 1.8902 | 0.2152 | ||
PSZ-AC:3 | 1.5497 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.5497 | 1.0000 | 1.0000 | 0.1781 | 0.1149 | ||
PSZ-AC:4 | 1.3572 | 0.0000 | 24.3517 | 1.0000 | 0.1781 | 1.3572 | 1.0000 | 1.0000 | 0.1781 | 0.1312 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BACK_SPACE | PSZ-AC:1 | 0.000000 | 61.3418 | 0.000610 | 379.89 | 0.2316 | 1.0000 | 0.2316 | 1.000 | 0.2316 |
CORE_RETAIL | PSZ-AC:2 | 0.000000 | 258.4342 | 0.001181 | 1600.48 | 1.8902 | 1.0000 | 1.8902 | 1.000 | 1.8902 |
POINT_OF_SALE | PSZ-AC:3 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
FRONT_RETAIL | PSZ-AC:4 | 0.000000 | 24.3517 | 0.001181 | 150.81 | 0.1781 | 1.0000 | 0.1781 | 1.000 | 0.1781 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC:1 | 0.000000 | 61.34 | 0.000610 | 379.8900 | 0.2316 | 0.2316 | 0.2316 |
PSZ-AC:2 | 0.000000 | 258.43 | 0.001181 | 1600.4829 | 1.8902 | 1.8902 | 1.8902 |
PSZ-AC:3 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
PSZ-AC:4 | 0.000000 | 24.35 | 0.001181 | 150.8100 | 0.1781 | 0.1781 | 0.1781 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.9913 | 2.9913 | 2.9913 | 0.2316 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.7816 | 8.7816 | 8.7816 | 1.8902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.5497 | 1.5497 | 1.5497 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.3572 | 1.3572 | 1.3572 | 0.1781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.9913 | 2.9913 | 2.9913 | 2.9913 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.7816 | 8.8972 | 8.7816 | 8.7816 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.5497 | 1.5497 | 1.5497 | 1.5497 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.3572 | 1.3572 | 1.3572 | 1.3572 | 0.1781 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BACK_SPACE | PSZ-AC:1 | 2.9913 | 2.9913 | 2.9913 | 0.2316 | 0.1894 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_RETAIL | PSZ-AC:2 | 8.7816 | 8.7816 | 8.7816 | 1.8902 | 0.7379 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
POINT_OF_SALE | PSZ-AC:3 | 1.5497 | 1.5497 | 1.5497 | 0.1781 | 0.3252 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
FRONT_RETAIL | PSZ-AC:4 | 1.3572 | 1.3572 | 1.3572 | 0.1781 | 0.3255 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC:1 | 2.9913 | 2.9913 | 2.9913 | 2.9913 | 0.2316 | 1.0000 |
PSZ-AC:2 | 8.7816 | 8.7816 | 8.7816 | 8.7816 | 1.8902 | 1.0000 |
PSZ-AC:3 | 1.5497 | 1.5497 | 1.5497 | 1.5497 | 0.1781 | 1.0000 |
PSZ-AC:4 | 1.3572 | 1.3572 | 1.3572 | 1.3572 | 0.1781 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:12:26
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 2293.99 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BACK_SPACE | 379.89 | 379.89 | 0.00 | 94.22 |
CORE_RETAIL | 1600.48 | 1600.48 | 0.00 | 94.22 |
POINT_OF_SALE | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_RETAIL | 150.81 | 150.81 | 0.00 | 94.22 |
FRONT_ENTRY | 12.00 | 12.00 | 0.00 | 0.00 |
Totals | 2293.99 | 2293.99 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 0.00 | 0.00 | 13.63 | 114536.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 611.60 | 87881.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 356.27 | 28576.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 60.29 | 4644.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 194.30 | 10740.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 179.59 | 16690.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 85.35 | 4923.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 194.30 | 1402.05 |
Natural Gas | 0.00 | 98.98 |
Additional | 0.00 | 0.00 |
Total | 194.30 | 1501.03 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 155.30 |
Space Heating | 0.00 |
Space Cooling | 266.61 |
Fans (All) | 78.29 |
Service Water Heating | 0.00 |
Receptacle Equipment | 84.70 |
Miscellaneous (All) | 611.18 |
Subtotal | 611.18 |
Natural Gas [MJ/m2] | |
Space Heating | 5.94 |
Service Water Heating | 37.21 |
Miscellaneous (All) | 43.15 |
Subtotal | 43.15 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 23.73 |
Space Heating | 0.91 |
Space Cooling | 40.75 |
Fans (All) | 11.96 |
Service Water Heating | 5.69 |
Receptacle Equipment | 12.94 |
Miscellaneous | 4.02 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
FRONTENTRY_COILSCHED | 8760. | 8760. |
FRONTENTRY_FANSCHED | 8760. | 8760. |
BLDG_LIGHT_BACK_SCH | 2872. | 8760. |
BLDG_LIGHT_CORE_SCH | 3609. | 8760. |
BLDG_LIGHT_ENTRY_SCH | 3001. | 8760. |
BLDG_LIGHT_FRONT_SCH | 3501. | 8760. |
BLDG_LIGHT_SCH | 3609. | 8760. |
BLDG_OCC_SCH | 2410. | 4950. |
BLDG_EQUIP_SCH | 4552. | 8760. |
BLDG_ELEVATORS | 2743. | 4950. |
INFIL_SCH | 3551. | 3551. |
INFIL_HALF_ON_SCH | 6156. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
BLDG_SWH_SCH | 2009. | 4950. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6543. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4950. | 4950. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH_PNNL | 4774. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4950. | 4950. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_NO_OPTIMUM | BACK_SPACE DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | January | 21.11 | 365 | 15.56 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_RETAIL DUALSPSCHED | July | 23.89 | 365 | 29.44 | 365 |
HTGSETP_SCH_FRONTENTRY_STD2013 | FRONT_ENTRY DUALSPSCHED | January | 16.00 | 365 | 15.56 | 365 |
FRONT_ENTRY_COOLING | FRONT_ENTRY DUALSPSCHED | July | 100.00 | 365 | 100.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.973003E+10 |
February | 0.000 | 0.132529E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 5659785.783 |
December | 0.000 | 0.256527E+10 |
Annual Sum or Average | 0.136263E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.973003E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.973003E+10 |
February | 0.000 | 0.132529E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 5659785.783 |
December | 0.000 | 0.256527E+10 |
Annual Sum or Average | 0.136263E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.973003E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.973003E+10 |
February | 0.000 | 0.132529E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 5659785.783 |
December | 0.000 | 0.256527E+10 |
Annual Sum or Average | 0.136263E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.973003E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.973003E+10 |
February | 0.000 | 0.132529E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 5659785.783 |
December | 0.000 | 0.256527E+10 |
Annual Sum or Average | 0.136263E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.973003E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTANDALONE
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.973003E+10 |
February | 0.000 | 0.132529E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 5659785.783 |
December | 0.000 | 0.256527E+10 |
Annual Sum or Average | 0.136263E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.973003E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.973003E+10 |
February | 0.000 | 0.132529E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 5659785.783 |
December | 0.000 | 0.256527E+10 |
Annual Sum or Average | 0.136263E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.973003E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.973003E+10 |
February | 0.000 | 0.132529E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 5659785.783 |
December | 0.000 | 0.256527E+10 |
Annual Sum or Average | 0.136263E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.973003E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.973003E+10 |
February | 0.000 | 0.132529E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 5659785.783 |
December | 0.000 | 0.256527E+10 |
Annual Sum or Average | 0.136263E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.973003E+10 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.973003E+10 |
February | 0.000 | 0.132529E+10 |
March | 0.000 | 0.000 |
April | 0.000 | 0.000 |
May | 0.000 | 0.000 |
June | 0.000 | 0.000 |
July | 0.000 | 0.000 |
August | 0.000 | 0.000 |
September | 0.000 | 0.000 |
October | 0.000 | 0.000 |
November | 0.000 | 5659785.783 |
December | 0.000 | 0.256527E+10 |
Annual Sum or Average | 0.136263E+11 | |
Minimum of Months | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.973003E+10 |
Report: ZoneCoolingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.520284E+09 | 3584.15 | 14-JAN-17:00 | 20.70 | 14.70 | 0.190064E+10 | 2451.25 | 14-JAN-12:20 | 20.33 | 14.68 |
February | 0.245947E+10 | 7675.18 | 24-FEB-16:00 | 26.30 | 17.46 | 0.190970E+10 | 2451.30 | 23-FEB-15:50 | 24.97 | 14.29 |
March | 0.106067E+11 | 53268.22 | 29-MAR-04:01 | 21.45 | 17.79 | 0.227691E+10 | 2451.35 | 30-MAR-14:39 | 30.80 | 19.42 |
April | 0.233091E+11 | 57699.25 | 29-APR-04:01 | 26.47 | 17.99 | 0.215642E+10 | 2451.43 | 28-APR-14:39 | 39.00 | 21.05 |
May | 0.341394E+11 | 57947.94 | 09-MAY-04:01 | 27.65 | 19.15 | 0.223250E+10 | 2451.47 | 06-MAY-11:50 | 39.85 | 19.78 |
June | 0.343897E+11 | 55715.81 | 05-JUN-04:01 | 30.32 | 20.24 | 0.220159E+10 | 2451.43 | 03-JUN-10:30 | 37.25 | 23.36 |
July | 0.334493E+11 | 50204.84 | 07-JUL-04:01 | 31.73 | 26.03 | 0.218723E+10 | 2451.36 | 11-JUL-14:30 | 33.15 | 26.77 |
August | 0.307500E+11 | 50994.62 | 09-AUG-04:01 | 30.32 | 25.71 | 0.228101E+10 | 2451.33 | 05-AUG-11:50 | 34.73 | 26.32 |
September | 0.242479E+11 | 52507.94 | 27-SEP-04:01 | 23.75 | 21.10 | 0.215640E+10 | 2451.34 | 14-SEP-14:39 | 33.83 | 27.60 |
October | 0.174806E+11 | 55004.10 | 02-OCT-04:01 | 21.82 | 17.77 | 0.218401E+10 | 2451.32 | 27-OCT-14:30 | 30.75 | 19.05 |
November | 0.637913E+10 | 48136.54 | 01-NOV-04:01 | 15.75 | 12.60 | 0.208814E+10 | 2451.29 | 02-NOV-14:00 | 28.30 | 15.99 |
December | 0.932168E+09 | 4079.94 | 01-DEC-16:00 | 22.30 | 13.70 | 0.201695E+10 | 2451.26 | 19-DEC-15:00 | 16.70 | 11.13 |
Annual Sum or Average | 0.218664E+12 | 0.255915E+11 | ||||||||
Minimum of Months | 0.520284E+09 | 3584.15 | 15.75 | 12.60 | 0.190064E+10 | 2451.25 | 16.70 | 11.13 | ||
Maximum of Months | 0.343897E+11 | 57947.94 | 31.73 | 26.03 | 0.228101E+10 | 2451.47 | 39.85 | 27.60 |
Report: ZoneCoolingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198259E+11 | 33208.14 | 05-JAN-07:05 | 4.93 | 4.82 | 0.864649E+10 | 10327.15 | 11-JAN-15:00 | 21.30 | 11.66 |
February | 0.269820E+11 | 38743.89 | 23-FEB-16:00 | 24.80 | 14.33 | 0.825321E+10 | 10327.18 | 23-FEB-15:00 | 24.80 | 14.33 |
March | 0.500129E+11 | 157988.06 | 30-MAR-06:02 | 21.25 | 16.71 | 0.960425E+10 | 10327.33 | 30-MAR-14:39 | 30.80 | 19.42 |
April | 0.744926E+11 | 190461.97 | 28-APR-05:01 | 27.22 | 17.14 | 0.908832E+10 | 10327.28 | 15-APR-11:00 | 38.00 | 19.29 |
May | 0.918767E+11 | 187101.02 | 06-MAY-04:01 | 30.18 | 17.70 | 0.940931E+10 | 10327.49 | 06-MAY-10:09 | 36.52 | 19.41 |
June | 0.885995E+11 | 171677.84 | 07-JUN-04:01 | 33.27 | 20.22 | 0.927904E+10 | 10327.04 | 24-JUN-13:00 | 25.00 | 24.49 |
July | 0.822140E+11 | 153843.53 | 05-JUL-04:01 | 32.58 | 25.32 | 0.921878E+10 | 10326.99 | 18-JUL-14:00 | 26.30 | 25.64 |
August | 0.780406E+11 | 141629.21 | 07-AUG-04:01 | 30.00 | 25.70 | 0.961377E+10 | 10326.89 | 05-AUG-11:20 | 34.23 | 26.11 |
September | 0.680131E+11 | 152271.66 | 27-SEP-05:02 | 23.08 | 20.68 | 0.908857E+10 | 10326.93 | 11-SEP-14:09 | 30.67 | 26.81 |
October | 0.613338E+11 | 168054.05 | 02-OCT-05:03 | 21.60 | 17.46 | 0.920370E+10 | 10327.29 | 27-OCT-14:09 | 30.78 | 19.08 |
November | 0.400783E+11 | 45917.55 | 09-NOV-15:20 | 28.93 | 17.64 | 0.882786E+10 | 10327.29 | 13-NOV-15:39 | 27.80 | 16.42 |
December | 0.240619E+11 | 31857.10 | 21-DEC-07:05 | 5.68 | 4.75 | 0.891450E+10 | 10327.25 | 01-DEC-15:09 | 23.22 | 13.40 |
Annual Sum or Average | 0.705531E+12 | 0.109148E+12 | ||||||||
Minimum of Months | 0.198259E+11 | 31857.10 | 4.93 | 4.75 | 0.825321E+10 | 10326.89 | 21.30 | 11.66 | ||
Maximum of Months | 0.918767E+11 | 190461.97 | 33.27 | 25.70 | 0.961377E+10 | 10327.49 | 38.00 | 26.81 |
Report: ZoneCoolingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.545221E+10 | 8606.70 | 12-JAN-15:40 | 23.40 | 14.37 | 0.845600E+09 | 973.15 | 07-JAN-16:00 | 18.40 | 12.94 |
February | 0.705445E+10 | 28805.51 | 23-FEB-05:01 | 15.08 | 13.21 | 0.784396E+09 | 973.17 | 15-FEB-15:09 | 22.98 | 16.79 |
March | 0.116892E+11 | 30877.24 | 29-MAR-04:01 | 21.45 | 17.79 | 0.905464E+09 | 973.17 | 28-MAR-14:00 | 35.60 | 18.47 |
April | 0.158019E+11 | 31386.76 | 07-APR-04:01 | 21.75 | 15.07 | 0.856056E+09 | 973.24 | 20-APR-14:30 | 37.05 | 19.63 |
May | 0.187377E+11 | 30301.21 | 28-MAY-06:01 | 26.58 | 17.54 | 0.886266E+09 | 973.23 | 06-MAY-11:09 | 38.85 | 19.66 |
June | 0.181717E+11 | 28649.41 | 05-JUN-04:11 | 30.23 | 20.24 | 0.873991E+09 | 973.21 | 03-JUN-10:09 | 36.82 | 23.31 |
July | 0.178087E+11 | 24747.48 | 07-JUL-04:01 | 31.73 | 26.03 | 0.868289E+09 | 973.16 | 22-JUL-13:50 | 29.75 | 26.98 |
August | 0.172243E+11 | 25285.73 | 06-AUG-06:01 | 28.77 | 23.60 | 0.905511E+09 | 973.17 | 26-AUG-10:09 | 30.40 | 28.09 |
September | 0.158536E+11 | 28857.32 | 27-SEP-04:01 | 23.75 | 21.10 | 0.856036E+09 | 973.17 | 30-SEP-10:30 | 31.50 | 23.64 |
October | 0.165497E+11 | 31583.59 | 23-OCT-04:01 | 18.78 | 14.94 | 0.867018E+09 | 973.23 | 16-OCT-14:00 | 33.60 | 19.10 |
November | 0.124261E+11 | 30449.00 | 02-NOV-04:01 | 16.58 | 13.43 | 0.833936E+09 | 973.13 | 04-NOV-10:09 | 24.08 | 16.24 |
December | 0.702955E+10 | 12982.26 | 29-DEC-05:03 | 16.42 | 12.55 | 0.859659E+09 | 973.16 | 14-DEC-15:09 | 19.75 | 13.88 |
Annual Sum or Average | 0.163799E+12 | 0.103422E+11 | ||||||||
Minimum of Months | 0.545221E+10 | 8606.70 | 15.08 | 12.55 | 0.784396E+09 | 973.13 | 18.40 | 12.94 | ||
Maximum of Months | 0.187377E+11 | 31583.59 | 31.73 | 26.03 | 0.905511E+09 | 973.24 | 38.85 | 28.09 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331893E+10 | 6596.44 | 12-JAN-15:40 | 23.40 | 14.37 | 0.825151E+09 | 973.14 | 06-JAN-15:39 | 20.23 | 13.05 |
February | 0.493586E+10 | 25232.38 | 23-FEB-05:01 | 15.08 | 13.21 | 0.774197E+09 | 973.15 | 08-FEB-15:00 | 24.00 | 16.17 |
March | 0.897311E+10 | 26828.53 | 29-MAR-04:01 | 21.45 | 17.79 | 0.904776E+09 | 973.16 | 28-MAR-14:00 | 35.60 | 18.47 |
April | 0.130849E+11 | 27678.65 | 29-APR-04:01 | 26.47 | 17.99 | 0.856051E+09 | 973.22 | 15-APR-12:30 | 38.70 | 19.53 |
May | 0.158171E+11 | 27162.05 | 29-MAY-06:01 | 29.10 | 17.75 | 0.886259E+09 | 973.20 | 06-MAY-11:09 | 38.85 | 19.66 |
June | 0.151162E+11 | 25497.80 | 05-JUN-04:01 | 30.32 | 20.24 | 0.873987E+09 | 973.16 | 03-JUN-10:09 | 36.82 | 23.31 |
July | 0.148406E+11 | 22640.88 | 07-JUL-04:11 | 31.67 | 26.03 | 0.868290E+09 | 973.15 | 22-JUL-12:00 | 30.50 | 26.90 |
August | 0.142527E+11 | 22348.45 | 09-AUG-04:01 | 30.32 | 25.71 | 0.905511E+09 | 973.15 | 19-AUG-10:39 | 30.50 | 27.27 |
September | 0.130121E+11 | 25233.88 | 27-SEP-04:01 | 23.75 | 21.10 | 0.856033E+09 | 973.12 | 30-SEP-10:30 | 31.50 | 23.64 |
October | 0.137609E+11 | 27668.88 | 23-OCT-04:01 | 18.78 | 14.94 | 0.867003E+09 | 973.20 | 16-OCT-14:39 | 33.47 | 19.01 |
November | 0.979373E+10 | 26676.68 | 02-NOV-04:01 | 16.58 | 13.43 | 0.833279E+09 | 973.12 | 28-NOV-15:00 | 22.70 | 15.30 |
December | 0.467643E+10 | 8136.93 | 01-DEC-15:20 | 23.03 | 13.47 | 0.849416E+09 | 973.15 | 05-DEC-15:20 | 20.93 | 14.44 |
Annual Sum or Average | 0.131583E+12 | 0.103000E+11 | ||||||||
Minimum of Months | 0.331893E+10 | 6596.44 | 15.08 | 13.21 | 0.774197E+09 | 973.12 | 20.23 | 13.05 | ||
Maximum of Months | 0.158171E+11 | 27678.65 | 31.67 | 26.03 | 0.905511E+09 | 973.22 | 38.85 | 27.27 |
Report: ZoneCoolingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 7.49 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 | 7.84 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 | 12.95 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 | 0.00 | 0.00 | 01-APR-00:10 | 23.70 | 16.76 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 | 18.21 | 0.00 | 0.00 | 01-MAY-00:10 | 30.53 | 18.21 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 | 22.57 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 | 24.63 | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 | 24.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 | 26.26 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 | 25.91 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 | 21.84 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 | 15.09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 | 9.10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 7.83 | 7.49 | 0.00 | 0.00 | 7.83 | 7.49 | ||
Maximum of Months | 0.00 | 0.00 | 32.95 | 26.26 | 0.00 | 0.00 | 32.95 | 26.26 |
Report: ZoneHeatingSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253346E+10 | 69159.40 | 01-JAN-07:01 | 7.25 |
February | 0.493120E+09 | 67155.99 | 11-FEB-05:02 | 9.03 |
March | 2108918.87 | 627.99 | 27-MAR-05:10 | 20.63 |
April | 89373.25 | 446.87 | 23-APR-07:03 | 22.45 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 19852186.90 | 1534.92 | 26-NOV-12:03 | 24.98 |
December | 0.104289E+10 | 69154.58 | 22-DEC-05:01 | 11.18 |
Annual Sum or Average | 0.409152E+10 | |||
Minimum of Months | 0.00 | 0.00 | 7.25 | |
Maximum of Months | 0.253346E+10 | 69159.40 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.895676E+09 | 216429.89 | 01-JAN-08:61 | 8.17 |
February | 71414123.38 | 133347.54 | 02-FEB-07:03 | 7.12 |
March | 11593807.99 | 7682.26 | 11-MAR-07:06 | 23.87 |
April | 0.126949E+09 | 22282.38 | 16-APR-08:06 | 30.70 |
May | 0.244783E+09 | 26391.89 | 01-MAY-06:06 | 32.80 |
June | 0.221238E+09 | 25057.40 | 04-JUN-08:06 | 31.72 |
July | 0.224904E+09 | 25618.02 | 02-JUL-07:06 | 33.57 |
August | 0.224477E+09 | 18048.33 | 08-AUG-05:06 | 30.10 |
September | 0.176903E+09 | 11695.50 | 22-SEP-05:05 | 27.07 |
October | 42940560.44 | 11286.36 | 04-OCT-06:06 | 25.52 |
November | 475803.70 | 803.58 | 26-NOV-10:00 | 21.70 |
December | 0.131574E+09 | 144089.20 | 23-DEC-07:03 | 6.25 |
Annual Sum or Average | 0.237293E+10 | |||
Minimum of Months | 475803.70 | 803.58 | 6.25 | |
Maximum of Months | 0.895676E+09 | 216429.89 | 33.57 |
Report: ZoneHeatingSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 86661503.85 | 35339.31 | 01-JAN-07:01 | 7.25 |
February | 12886734.28 | 17327.39 | 11-FEB-05:02 | 9.03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 502951.40 | 1177.95 | 29-APR-05:04 | 25.92 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 109914.10 | 1465.52 | 24-JUN-05:04 | 26.80 |
July | 206697.79 | 2411.47 | 07-JUL-05:06 | 31.52 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 58935.89 | 135.43 | 23-DEC-06:10 | 5.43 |
Annual Sum or Average | 0.100427E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 86661503.85 | 35339.31 | 31.52 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187852E+09 | 31425.35 | 01-JAN-07:01 | 7.25 |
February | 34953316.72 | 30609.08 | 11-FEB-05:02 | 9.03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 40207.17 | 201.04 | 23-APR-07:07 | 22.45 |
May | 145231.53 | 1936.42 | 06-MAY-05:04 | 29.55 |
June | 136660.81 | 1594.38 | 12-JUN-05:06 | 34.12 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 11056715.36 | 16038.72 | 31-DEC-07:01 | 5.53 |
Annual Sum or Average | 0.234184E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.53 | |
Maximum of Months | 0.187852E+09 | 31425.35 | 34.12 |
Report: ZoneHeatingSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12711756.64 | 3365.55 | 03-JAN-08:05 | 6.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 7706668.15 | 2673.43 | 21-DEC-08:04 | 6.25 |
Annual Sum or Average | 20418424.78 | |||
Minimum of Months | 0.00 | 0.00 | 6.25 | |
Maximum of Months | 12711756.64 | 3365.55 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.245973E+10 | 2023.29 | 02-JAN-09:09 | 0.419292E+10 | 2751.42 | 02-JAN-09:09 |
February | 0.223751E+10 | 2023.29 | 01-FEB-09:09 | 0.380401E+10 | 2751.42 | 01-FEB-09:09 |
March | 0.255095E+10 | 2023.29 | 01-MAR-09:09 | 0.429860E+10 | 2751.42 | 01-MAR-09:09 |
April | 0.240752E+10 | 2023.29 | 01-APR-09:09 | 0.408483E+10 | 2751.42 | 01-APR-09:09 |
May | 0.250534E+10 | 2023.29 | 01-MAY-08:09 | 0.424576E+10 | 2751.42 | 01-MAY-08:09 |
June | 0.246168E+10 | 2023.29 | 01-JUN-08:09 | 0.415135E+10 | 2751.42 | 01-JUN-08:09 |
July | 0.245118E+10 | 2023.29 | 01-JUL-09:09 | 0.417924E+10 | 2751.42 | 01-JUL-09:09 |
August | 0.255095E+10 | 2023.29 | 01-AUG-08:09 | 0.429860E+10 | 2751.42 | 01-AUG-08:09 |
September | 0.240752E+10 | 2023.29 | 01-SEP-08:09 | 0.408483E+10 | 2751.42 | 01-SEP-08:09 |
October | 0.245973E+10 | 2023.29 | 02-OCT-08:09 | 0.419292E+10 | 2751.42 | 02-OCT-08:09 |
November | 0.237899E+10 | 2023.29 | 01-NOV-08:09 | 0.405935E+10 | 2751.42 | 01-NOV-08:09 |
December | 0.245118E+10 | 2023.29 | 01-DEC-09:09 | 0.417924E+10 | 2751.42 | 01-DEC-09:09 |
Annual Sum or Average | 0.293223E+11 | 0.497716E+11 | ||||
Minimum of Months | 0.223751E+10 | 2023.29 | 0.380401E+10 | 2751.42 | ||
Maximum of Months | 0.255095E+10 | 2023.29 | 0.429860E+10 | 2751.42 |
Report: ZoneElectricSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.242686E+11 | 22326.78 | 02-JAN-15:50 | 0.707031E+10 | 4639.58 | 02-JAN-09:09 |
February | 0.212157E+11 | 22326.78 | 01-FEB-16:10 | 0.641452E+10 | 4639.58 | 01-FEB-09:09 |
March | 0.221198E+11 | 22326.78 | 01-MAR-16:40 | 0.724851E+10 | 4639.58 | 01-MAR-09:09 |
April | 0.217415E+11 | 22326.78 | 01-APR-16:00 | 0.688804E+10 | 4639.58 | 01-APR-09:09 |
May | 0.225351E+11 | 22326.78 | 03-MAY-08:09 | 0.715941E+10 | 4639.58 | 01-MAY-08:09 |
June | 0.216458E+11 | 22326.78 | 15-JUN-16:00 | 0.700021E+10 | 4639.58 | 01-JUN-08:09 |
July | 0.204464E+11 | 22326.78 | 10-JUL-16:49 | 0.704724E+10 | 4639.58 | 01-JUL-09:09 |
August | 0.213512E+11 | 22326.78 | 10-AUG-16:40 | 0.724851E+10 | 4639.58 | 01-AUG-08:09 |
September | 0.205328E+11 | 22326.78 | 02-SEP-16:00 | 0.688804E+10 | 4639.58 | 01-SEP-08:09 |
October | 0.228878E+11 | 22326.78 | 02-OCT-16:30 | 0.707031E+10 | 4639.58 | 02-OCT-08:09 |
November | 0.235777E+11 | 22326.78 | 01-NOV-08:09 | 0.684509E+10 | 4639.58 | 01-NOV-08:09 |
December | 0.243760E+11 | 22326.78 | 01-DEC-15:30 | 0.704724E+10 | 4639.58 | 01-DEC-09:09 |
Annual Sum or Average | 0.266698E+12 | 0.839274E+11 | ||||
Minimum of Months | 0.204464E+11 | 22326.78 | 0.641452E+10 | 4639.58 | ||
Maximum of Months | 0.243760E+11 | 22326.78 | 0.724851E+10 | 4639.58 |
Report: ZoneElectricSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.251152E+10 | 2103.80 | 02-JAN-09:09 | 0.443872E+10 | 2912.71 | 02-JAN-09:09 |
February | 0.228515E+10 | 2103.80 | 01-FEB-09:09 | 0.402701E+10 | 2912.71 | 01-FEB-09:09 |
March | 0.260661E+10 | 2103.80 | 01-MAR-09:09 | 0.455059E+10 | 2912.71 | 01-MAR-09:09 |
April | 0.245935E+10 | 2103.80 | 01-APR-09:09 | 0.432429E+10 | 2912.71 | 01-APR-09:09 |
May | 0.255907E+10 | 2103.80 | 01-MAY-08:09 | 0.449465E+10 | 2912.71 | 01-MAY-08:09 |
June | 0.251531E+10 | 2103.80 | 01-JUN-08:09 | 0.439471E+10 | 2912.71 | 01-JUN-08:09 |
July | 0.250311E+10 | 2103.80 | 01-JUL-09:09 | 0.442423E+10 | 2912.71 | 01-JUL-09:09 |
August | 0.260661E+10 | 2103.80 | 01-AUG-08:09 | 0.455059E+10 | 2912.71 | 01-AUG-08:09 |
September | 0.245935E+10 | 2103.80 | 01-SEP-08:09 | 0.432429E+10 | 2912.71 | 01-SEP-08:09 |
October | 0.251152E+10 | 2103.80 | 02-OCT-08:09 | 0.443872E+10 | 2912.71 | 02-OCT-08:09 |
November | 0.242863E+10 | 2103.80 | 01-NOV-08:09 | 0.429732E+10 | 2912.71 | 01-NOV-08:09 |
December | 0.250311E+10 | 2103.80 | 01-DEC-09:09 | 0.442423E+10 | 2912.71 | 01-DEC-09:09 |
Annual Sum or Average | 0.299493E+11 | 0.526893E+11 | ||||
Minimum of Months | 0.228515E+10 | 2103.80 | 0.402701E+10 | 2912.71 | ||
Maximum of Months | 0.260661E+10 | 2103.80 | 0.455059E+10 | 2912.71 |
Report: ZoneElectricSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.243691E+10 | 2036.90 | 02-JAN-09:09 | 0.666220E+09 | 437.18 | 02-JAN-09:09 |
February | 0.221721E+10 | 2036.90 | 01-FEB-09:09 | 0.604426E+09 | 437.18 | 01-FEB-09:09 |
March | 0.252895E+10 | 2036.90 | 01-MAR-09:09 | 0.683011E+09 | 437.18 | 01-MAR-09:09 |
April | 0.238616E+10 | 2036.90 | 01-APR-09:09 | 0.649045E+09 | 437.18 | 01-APR-09:09 |
May | 0.248293E+10 | 2036.90 | 01-MAY-08:09 | 0.674616E+09 | 437.18 | 01-MAY-08:09 |
June | 0.244038E+10 | 2036.90 | 01-JUN-08:09 | 0.659615E+09 | 437.18 | 01-JUN-08:09 |
July | 0.242871E+10 | 2036.90 | 01-JUL-09:09 | 0.664046E+09 | 437.18 | 01-JUL-09:09 |
August | 0.252895E+10 | 2036.90 | 01-AUG-08:09 | 0.683011E+09 | 437.18 | 01-AUG-08:09 |
September | 0.238616E+10 | 2036.90 | 01-SEP-08:09 | 0.649045E+09 | 437.18 | 01-SEP-08:09 |
October | 0.243691E+10 | 2036.90 | 02-OCT-08:09 | 0.666220E+09 | 437.18 | 02-OCT-08:09 |
November | 0.235654E+10 | 2036.90 | 01-NOV-08:09 | 0.644998E+09 | 437.18 | 01-NOV-08:09 |
December | 0.242871E+10 | 2036.90 | 01-DEC-09:09 | 0.664046E+09 | 437.18 | 01-DEC-09:09 |
Annual Sum or Average | 0.290585E+11 | 0.790830E+10 | ||||
Minimum of Months | 0.221721E+10 | 2036.90 | 0.604426E+09 | 437.18 | ||
Maximum of Months | 0.252895E+10 | 2036.90 | 0.683011E+09 | 437.18 |
Report: ZoneElectricSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.103900E+09 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 94517577.03 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.107770E+09 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.101704E+09 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 |
May | 0.105835E+09 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.103997E+09 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.103541E+09 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 |
August | 0.107770E+09 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.101704E+09 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.103900E+09 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.100485E+09 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.103541E+09 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.123866E+10 | ||||
Minimum of Months | 94517577.03 | 85.79 | 0.00 | 0.00 | |
Maximum of Months | 0.107770E+09 | 85.79 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.524694E+10 | 0.245973E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11440.56 | 0.164847E+09 |
February | 0.479114E+10 | 0.223751E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3273179.80 | 0.202762E+09 |
March | 0.548013E+10 | 0.255095E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41012555.25 | 0.159831E+09 |
April | 0.518069E+10 | 0.240752E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156076E+09 | 17686478.18 |
May | 0.536353E+10 | 0.250534E+10 | 0.424576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288118E+09 | 17166795.25 |
June | 0.528933E+10 | 0.246168E+10 | 0.415135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219727E+09 | 4981908.34 |
July | 0.525489E+10 | 0.245118E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249079E+09 | 5830206.06 |
August | 0.548013E+10 | 0.255095E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147060E+09 | 9183655.01 |
September | 0.518069E+10 | 0.240752E+10 | 0.408483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96037934.44 | 10576166.32 |
October | 0.524694E+10 | 0.245973E+10 | 0.419292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47990009.90 | 15444354.28 |
November | 0.504819E+10 | 0.237899E+10 | 0.405935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11503928.73 | 47629433.28 |
December | 0.525489E+10 | 0.245118E+10 | 0.417924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 332674.89 | 0.162995E+09 |
Annual Sum or Average | 0.628175E+11 | 0.293223E+11 | 0.497716E+11 | 0.126022E+10 | 0.818935E+09 | ||||
Minimum of Months | 0.479114E+10 | 0.223751E+10 | 0.380401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11440.56 | 4981908.34 |
Maximum of Months | 0.548013E+10 | 0.255095E+10 | 0.429860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288118E+09 | 0.202762E+09 |
Report: SpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.221054E+11 | 0.242686E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162103E+09 |
February | 0.201852E+11 | 0.212157E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2656653.60 | 0.193375E+09 |
March | 0.230879E+11 | 0.221198E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33663297.21 | 0.148430E+09 |
April | 0.218263E+11 | 0.217415E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127930E+09 | 15679114.79 |
May | 0.225967E+11 | 0.225351E+11 | 0.715941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241886E+09 | 9643119.05 |
June | 0.222841E+11 | 0.216458E+11 | 0.700021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187013E+09 | 3724010.63 |
July | 0.221389E+11 | 0.204464E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219314E+09 | 2637778.69 |
August | 0.230879E+11 | 0.213512E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127023E+09 | 3957260.57 |
September | 0.218263E+11 | 0.205328E+11 | 0.688804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78616373.25 | 6421932.96 |
October | 0.221054E+11 | 0.228878E+11 | 0.707031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39409872.88 | 13245208.13 |
November | 0.212681E+11 | 0.235777E+11 | 0.684509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9400652.70 | 44298844.25 |
December | 0.221389E+11 | 0.243760E+11 | 0.704724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89633.19 | 0.158702E+09 |
Annual Sum or Average | 0.264651E+12 | 0.266698E+12 | 0.839274E+11 | 0.106700E+10 | 0.762218E+09 | ||||
Minimum of Months | 0.201852E+11 | 0.204464E+11 | 0.641452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2637778.69 |
Maximum of Months | 0.230879E+11 | 0.243760E+11 | 0.724851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241886E+09 | 0.193375E+09 |
Report: SpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.251152E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91201172.56 |
February | 0.190200E+10 | 0.228515E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1406127.70 | 0.107850E+09 |
March | 0.217552E+10 | 0.260661E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17259370.95 | 93261563.02 |
April | 0.205665E+10 | 0.245935E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65987384.48 | 12646248.72 |
May | 0.212923E+10 | 0.255907E+10 | 0.449465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122940E+09 | 10483180.16 |
June | 0.209978E+10 | 0.251531E+10 | 0.439471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93254837.57 | 2681783.80 |
July | 0.208610E+10 | 0.250311E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104312E+09 | 4156991.90 |
August | 0.217552E+10 | 0.260661E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61414235.98 | 6692329.08 |
September | 0.205665E+10 | 0.245935E+10 | 0.432429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40684861.12 | 8062336.34 |
October | 0.208295E+10 | 0.251152E+10 | 0.443872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20357279.25 | 9219917.14 |
November | 0.200405E+10 | 0.242863E+10 | 0.429732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4976887.93 | 26064295.42 |
December | 0.208610E+10 | 0.250311E+10 | 0.442423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47422.65 | 89507651.64 |
Annual Sum or Average | 0.249375E+11 | 0.299493E+11 | 0.526893E+11 | 0.532640E+09 | 0.461827E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.228515E+10 | 0.402701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2681783.80 |
Maximum of Months | 0.217552E+10 | 0.260661E+10 | 0.455059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122940E+09 | 0.107850E+09 |
Report: SpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.208295E+10 | 0.243691E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86009455.47 |
February | 0.190200E+10 | 0.221721E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1406120.60 | 0.101898E+09 |
March | 0.217552E+10 | 0.252895E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17306252.87 | 85662967.36 |
April | 0.205665E+10 | 0.238616E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66312590.36 | 10458759.55 |
May | 0.212923E+10 | 0.248293E+10 | 0.674616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124075E+09 | 7743353.19 |
June | 0.209978E+10 | 0.244038E+10 | 0.659615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 95197811.49 | 1948780.33 |
July | 0.208610E+10 | 0.242871E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107468E+09 | 2321365.42 |
August | 0.217552E+10 | 0.252895E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62712648.23 | 4378023.16 |
September | 0.205665E+10 | 0.238616E+10 | 0.649045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40998082.34 | 5782264.07 |
October | 0.208295E+10 | 0.243691E+10 | 0.666220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20409405.48 | 8354978.55 |
November | 0.200405E+10 | 0.235654E+10 | 0.644998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4976772.49 | 25032315.25 |
December | 0.208610E+10 | 0.242871E+10 | 0.664046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47402.75 | 85246810.54 |
Annual Sum or Average | 0.249375E+11 | 0.290585E+11 | 0.790830E+10 | 0.540911E+09 | 0.424837E+09 | ||||
Minimum of Months | 0.190200E+10 | 0.221721E+10 | 0.604426E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1948780.33 |
Maximum of Months | 0.217552E+10 | 0.252895E+10 | 0.683011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124075E+09 | 0.101898E+09 |
Report: SpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132834E+10 |
February | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837760E+09 |
March | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35091799.28 | 0.404549E+09 |
April | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496852E+09 | 54018754.43 |
May | 0.00 | 0.105835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100550E+10 | 14235592.64 |
June | 0.00 | 0.103997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921111E+09 | 18160190.81 |
July | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480006E+09 | 20333341.62 |
August | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287528E+09 | 44806552.87 |
September | 0.00 | 0.101704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168000E+09 | 49094551.50 |
October | 0.00 | 0.103900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28403734.59 | 0.311696E+09 |
November | 0.00 | 0.100485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846432E+09 |
December | 0.00 | 0.103541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137095E+10 |
Annual Sum or Average | 0.00 | 0.123866E+10 | 0.342249E+10 | 0.530037E+10 | |||||
Minimum of Months | 0.00 | 94517577.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14235592.64 |
Maximum of Months | 0.00 | 0.107770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100550E+10 | 0.137095E+10 |
Report: PeakSpaceGainsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5888.82 | 02-JAN-15:09 | 2023.29 | 02-JAN-09:09 | 2751.42 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 | 08-JAN-15:00 | 479.26 | 15-JAN-19:10 |
February | 5888.82 | 01-FEB-15:09 | 2023.29 | 01-FEB-09:09 | 2751.42 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.09 | 19-FEB-15:00 | 931.37 | 09-FEB-21:10 |
March | 5888.82 | 01-MAR-15:09 | 2023.29 | 01-MAR-09:09 | 2751.42 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.61 | 26-MAR-18:02 | 1712.49 | 24-MAR-24:00 |
April | 5888.82 | 01-APR-10:09 | 2023.29 | 01-APR-09:09 | 2751.42 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 647.01 | 02-APR-18:02 | 203.29 | 04-APR-24:00 |
May | 5888.82 | 01-MAY-14:09 | 2023.29 | 01-MAY-08:09 | 2751.42 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.33 | 28-MAY-18:01 | 274.13 | 15-MAY-03:00 |
June | 5888.82 | 01-JUN-14:09 | 2023.29 | 01-JUN-08:09 | 2751.42 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 919.19 | 17-JUN-21:02 | 211.17 | 18-JUN-02:00 |
July | 5888.82 | 01-JUL-10:09 | 2023.29 | 01-JUL-09:09 | 2751.42 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 695.13 | 03-JUL-04:20 | 151.79 | 19-JUL-03:00 |
August | 5888.82 | 01-AUG-14:09 | 2023.29 | 01-AUG-08:09 | 2751.42 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 430.56 | 31-AUG-04:10 | 241.57 | 15-AUG-23:40 |
September | 5888.82 | 01-SEP-14:09 | 2023.29 | 01-SEP-08:09 | 2751.42 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 265.47 | 02-SEP-21:02 | 82.18 | 08-SEP-21:30 |
October | 5888.82 | 02-OCT-14:09 | 2023.29 | 02-OCT-08:09 | 2751.42 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 255.57 | 03-OCT-15:00 | 268.58 | 12-OCT-03:00 |
November | 5888.82 | 01-NOV-14:09 | 2023.29 | 01-NOV-08:09 | 2751.42 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.04 | 13-NOV-14:00 | 358.70 | 29-NOV-24:00 |
December | 5888.82 | 01-DEC-15:09 | 2023.29 | 01-DEC-09:09 | 2751.42 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.23 | 24-DEC-14:00 | 745.83 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 | 82.18 | |||||
Maximum of Months | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1111.33 | 1712.49 |
Report: PeakSpaceGainsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 24809.68 | 02-JAN-15:09 | 22326.78 | 02-JAN-15:50 | 4639.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 439.24 | 15-JAN-19:30 |
February | 24809.68 | 01-FEB-15:09 | 22326.78 | 01-FEB-16:10 | 4639.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.45 | 19-FEB-15:00 | 858.23 | 09-FEB-21:10 |
March | 24809.68 | 01-MAR-15:09 | 22326.78 | 01-MAR-16:40 | 4639.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 278.11 | 26-MAR-18:02 | 1750.05 | 24-MAR-24:00 |
April | 24809.68 | 01-APR-10:09 | 22326.78 | 01-APR-16:00 | 4639.58 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 534.27 | 02-APR-18:02 | 162.75 | 04-APR-24:00 |
May | 24809.68 | 01-MAY-14:09 | 22326.78 | 03-MAY-08:09 | 4639.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 918.57 | 28-MAY-18:01 | 183.62 | 15-MAY-03:00 |
June | 24809.68 | 01-JUN-14:09 | 22326.78 | 15-JUN-16:00 | 4639.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 763.98 | 17-JUN-21:02 | 157.45 | 18-JUN-04:00 |
July | 24809.68 | 01-JUL-10:09 | 22326.78 | 10-JUL-16:49 | 4639.58 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 514.41 | 20-JUL-20:02 | 118.22 | 19-JUL-03:00 |
August | 24809.68 | 01-AUG-14:09 | 22326.78 | 10-AUG-16:40 | 4639.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 337.49 | 15-AUG-20:02 | 155.54 | 15-AUG-24:00 |
September | 24809.68 | 01-SEP-14:09 | 22326.78 | 02-SEP-16:00 | 4639.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 222.92 | 02-SEP-21:02 | 89.80 | 19-SEP-05:00 |
October | 24809.68 | 02-OCT-14:09 | 22326.78 | 02-OCT-16:30 | 4639.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 209.20 | 03-OCT-15:00 | 229.22 | 12-OCT-03:00 |
November | 24809.68 | 01-NOV-14:09 | 22326.78 | 01-NOV-08:09 | 4639.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.96 | 13-NOV-14:00 | 355.68 | 28-NOV-05:02 |
December | 24809.68 | 01-DEC-15:09 | 22326.78 | 01-DEC-15:30 | 4639.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.90 | 28-DEC-14:00 | 798.24 | 29-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 24809.68 | 22326.78 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.80 | |||||
Maximum of Months | 24809.68 | 22326.78 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 918.57 | 1750.05 |
Report: PeakSpaceGainsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2103.80 | 02-JAN-09:09 | 2912.71 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 234.11 | 12-JAN-04:00 |
February | 2337.76 | 01-FEB-15:09 | 2103.80 | 01-FEB-09:09 | 2912.71 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 19-FEB-15:00 | 451.41 | 09-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 2103.80 | 01-MAR-09:09 | 2912.71 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 136.07 | 26-MAR-18:02 | 1054.71 | 24-MAR-23:00 |
April | 2337.76 | 01-APR-10:09 | 2103.80 | 01-APR-09:09 | 2912.71 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 274.81 | 30-APR-18:01 | 134.84 | 04-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2103.80 | 01-MAY-08:09 | 2912.71 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 478.42 | 28-MAY-18:01 | 142.10 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 2103.80 | 01-JUN-08:09 | 2912.71 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 395.80 | 17-JUN-21:02 | 100.28 | 18-JUN-01:50 |
July | 2337.76 | 01-JUL-10:09 | 2103.80 | 01-JUL-09:09 | 2912.71 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 301.56 | 03-JUL-04:19 | 74.05 | 19-JUL-03:00 |
August | 2337.76 | 01-AUG-14:09 | 2103.80 | 01-AUG-08:09 | 2912.71 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 187.03 | 31-AUG-04:08 | 120.07 | 15-AUG-23:00 |
September | 2337.76 | 01-SEP-14:09 | 2103.80 | 01-SEP-08:09 | 2912.71 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.64 | 02-SEP-21:02 | 48.66 | 08-SEP-21:20 |
October | 2337.76 | 02-OCT-14:09 | 2103.80 | 02-OCT-08:09 | 2912.71 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.75 | 03-OCT-15:00 | 137.32 | 12-OCT-03:00 |
November | 2337.76 | 01-NOV-14:09 | 2103.80 | 01-NOV-08:09 | 2912.71 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.75 | 13-NOV-14:00 | 232.48 | 29-NOV-24:00 |
December | 2337.76 | 01-DEC-15:09 | 2103.80 | 01-DEC-09:09 | 2912.71 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 28-DEC-14:00 | 395.61 | 29-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2103.80 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.66 | |||||
Maximum of Months | 2337.76 | 2103.80 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 478.42 | 1054.71 |
Report: PeakSpaceGainsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2337.76 | 02-JAN-15:09 | 2036.90 | 02-JAN-09:09 | 437.18 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 225.14 | 26-JAN-21:10 |
February | 2337.76 | 01-FEB-15:09 | 2036.90 | 01-FEB-09:09 | 437.18 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 | 19-FEB-15:00 | 403.28 | 09-FEB-21:10 |
March | 2337.76 | 01-MAR-15:09 | 2036.90 | 01-MAR-09:09 | 437.18 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.70 | 26-MAR-18:02 | 954.81 | 24-MAR-23:00 |
April | 2337.76 | 01-APR-10:09 | 2036.90 | 01-APR-09:09 | 437.18 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 275.98 | 02-APR-18:02 | 113.56 | 04-APR-24:00 |
May | 2337.76 | 01-MAY-14:09 | 2036.90 | 01-MAY-08:09 | 437.18 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 479.46 | 28-MAY-18:01 | 117.78 | 15-MAY-03:00 |
June | 2337.76 | 01-JUN-14:09 | 2036.90 | 01-JUN-08:09 | 437.18 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 397.54 | 17-JUN-21:02 | 83.04 | 18-JUN-02:00 |
July | 2337.76 | 01-JUL-10:09 | 2036.90 | 01-JUL-09:09 | 437.18 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 301.33 | 03-JUL-04:30 | 61.10 | 19-JUL-03:00 |
August | 2337.76 | 01-AUG-14:09 | 2036.90 | 01-AUG-08:09 | 437.18 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 188.59 | 31-AUG-04:08 | 107.69 | 15-AUG-23:20 |
September | 2337.76 | 01-SEP-14:09 | 2036.90 | 01-SEP-08:09 | 437.18 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.65 | 02-SEP-21:02 | 37.79 | 19-SEP-04:00 |
October | 2337.76 | 02-OCT-14:09 | 2036.90 | 02-OCT-08:09 | 437.18 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.75 | 03-OCT-15:00 | 121.98 | 12-OCT-03:00 |
November | 2337.76 | 01-NOV-14:09 | 2036.90 | 01-NOV-08:09 | 437.18 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.75 | 13-NOV-14:00 | 216.56 | 29-NOV-24:00 |
December | 2337.76 | 01-DEC-15:09 | 2036.90 | 01-DEC-09:09 | 437.18 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 28-DEC-14:00 | 370.89 | 29-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2337.76 | 2036.90 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.79 | |||||
Maximum of Months | 2337.76 | 2036.90 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 479.46 | 954.81 |
Report: PeakSpaceGainsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 85.79 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3938.93 | 27-JAN-12:01 |
February | 0.00 | 01-FEB-00:10 | 85.79 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3004.87 | 09-FEB-12:01 |
March | 0.00 | 01-MAR-00:10 | 85.79 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.86 | 28-MAR-11:03 | 1990.68 | 16-MAR-07:01 |
April | 0.00 | 01-APR-00:10 | 85.79 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2831.03 | 16-APR-11:01 | 1315.98 | 05-APR-07:01 |
May | 0.00 | 01-MAY-00:10 | 85.79 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4691.21 | 03-MAY-11:01 | 770.55 | 31-MAY-16:53 |
June | 0.00 | 01-JUN-00:10 | 85.79 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4601.85 | 04-JUN-11:01 | 1369.24 | 27-JUN-11:02 |
July | 0.00 | 01-JUL-00:10 | 85.79 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2823.93 | 01-JUL-11:01 | 1084.09 | 18-JUL-11:02 |
August | 0.00 | 01-AUG-00:10 | 85.79 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1533.63 | 05-AUG-11:02 | 758.36 | 16-AUG-07:02 |
September | 0.00 | 01-SEP-00:10 | 85.79 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1238.28 | 11-SEP-11:02 | 951.93 | 29-SEP-15:55 |
October | 0.00 | 01-OCT-00:10 | 85.79 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1022.90 | 02-OCT-11:02 | 2061.10 | 30-OCT-07:01 |
November | 0.00 | 01-NOV-00:10 | 85.79 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2948.09 | 30-NOV-12:01 |
December | 0.00 | 01-DEC-00:10 | 85.79 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5528.83 | 21-DEC-12:01 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.36 | ||||
Maximum of Months | 0.00 | 85.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4691.21 | 5528.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3584.15 | 14-JAN-17:00 | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.72 |
February | 7675.18 | 24-FEB-16:00 | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 0.00 |
March | 53268.22 | 29-MAR-04:01 | 0.00 | 1437.32 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 57699.25 | 29-APR-04:01 | 0.00 | 1437.32 | 4538.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57947.94 | 09-MAY-04:01 | 0.00 | 1437.32 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 55715.81 | 05-JUN-04:01 | 0.00 | 1437.32 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 50204.84 | 07-JUL-04:01 | 0.00 | 1437.32 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 50994.62 | 09-AUG-04:01 | 0.00 | 1437.32 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 | 0.00 |
September | 52507.94 | 27-SEP-04:01 | 0.00 | 1437.32 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 55004.10 | 02-OCT-04:01 | 0.00 | 1437.32 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 48136.54 | 01-NOV-04:01 | 0.00 | 1293.59 | 5445.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.62 |
December | 4079.94 | 01-DEC-16:00 | 5888.82 | 2023.29 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3584.15 | 0.00 | 1293.59 | 2751.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 57947.94 | 5888.82 | 2023.29 | 6050.87 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 52.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33208.14 | 05-JAN-07:05 | 12404.84 | 19846.03 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38743.89 | 23-FEB-16:00 | 24809.68 | 20466.22 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 | 0.00 |
March | 157988.06 | 30-MAR-06:02 | 15506.05 | 24807.53 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
April | 190461.97 | 28-APR-05:01 | 0.00 | 9923.01 | 8162.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 |
May | 187101.02 | 06-MAY-04:01 | 0.00 | 12403.77 | 7652.47 | 0.00 | 0.00 | 0.00 | 0.00 | 45.64 | 0.00 |
June | 171677.84 | 07-JUN-04:01 | 0.00 | 12403.77 | 10203.29 | 0.00 | 0.00 | 0.00 | 0.00 | 133.40 | 0.00 |
July | 153843.53 | 05-JUL-04:01 | 0.00 | 12403.77 | 10203.29 | 0.00 | 0.00 | 0.00 | 0.00 | 106.86 | 0.00 |
August | 141629.21 | 07-AUG-04:01 | 0.00 | 12403.77 | 10203.29 | 0.00 | 0.00 | 0.00 | 0.00 | 27.44 | 0.00 |
September | 152271.66 | 27-SEP-05:02 | 0.00 | 6201.88 | 5101.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
October | 168054.05 | 02-OCT-05:03 | 0.00 | 4961.51 | 4081.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
November | 45917.55 | 09-NOV-15:20 | 24809.68 | 20466.22 | 4639.58 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 | 0.00 |
December | 31857.10 | 21-DEC-07:05 | 12404.84 | 19846.03 | 8248.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.64 |
Annual Sum or Average | |||||||||||
Minimum of Months | 31857.10 | 0.00 | 4961.51 | 4081.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 190461.97 | 24809.68 | 24807.53 | 10310.18 | 0.00 | 0.00 | 0.00 | 0.00 | 133.40 | 29.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8606.70 | 12-JAN-15:40 | 2337.76 | 2103.80 | 2912.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
February | 28805.51 | 23-FEB-05:01 | 0.00 | 818.15 | 4483.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 |
March | 30877.24 | 29-MAR-04:01 | 0.00 | 1168.78 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31386.76 | 07-APR-04:01 | 0.00 | 1168.78 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 |
May | 30301.21 | 28-MAY-06:01 | 0.00 | 1168.78 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 |
June | 28649.41 | 05-JUN-04:11 | 0.00 | 1168.78 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24747.48 | 07-JUL-04:01 | 0.00 | 1168.78 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 25285.73 | 06-AUG-06:01 | 0.00 | 1168.78 | 4804.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 |
September | 28857.32 | 27-SEP-04:01 | 0.00 | 1168.78 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31583.59 | 23-OCT-04:01 | 0.00 | 1168.78 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.19 |
November | 30449.00 | 02-NOV-04:01 | 0.00 | 1051.90 | 5765.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.29 |
December | 12982.26 | 29-DEC-05:03 | 0.00 | 467.51 | 2562.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8606.70 | 0.00 | 467.51 | 2562.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31583.59 | 2337.76 | 2103.80 | 6405.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6596.44 | 12-JAN-15:40 | 2337.76 | 2036.90 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 |
February | 25232.38 | 23-FEB-05:01 | 0.00 | 818.15 | 673.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 |
March | 26828.53 | 29-MAR-04:01 | 0.00 | 1168.78 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27678.65 | 29-APR-04:01 | 0.00 | 1168.78 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27162.05 | 29-MAY-06:01 | 0.00 | 1168.78 | 721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 22.26 | 0.00 |
June | 25497.80 | 05-JUN-04:01 | 0.00 | 1168.78 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 22640.88 | 07-JUL-04:11 | 0.00 | 1168.78 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22348.45 | 09-AUG-04:01 | 0.00 | 1168.78 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.84 | 0.00 |
September | 25233.88 | 27-SEP-04:01 | 0.00 | 1168.78 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27668.88 | 23-OCT-04:01 | 0.00 | 1168.78 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.57 |
November | 26676.68 | 02-NOV-04:01 | 0.00 | 1051.90 | 865.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.86 |
December | 8136.93 | 01-DEC-15:20 | 2337.76 | 2036.90 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6596.44 | 0.00 | 818.15 | 437.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27678.65 | 2337.76 | 2036.90 | 961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 22.26 | 42.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:05 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 | 0.00 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 5.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 11.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 | 5.79 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.720973E+11 | 64459.42 | 14-JAN-17:49 | 0.174151E+11 | 116396.24 | 02-JAN-07:10 |
February | 0.726442E+11 | 73921.12 | 24-FEB-16:40 | 0.822494E+10 | 67461.88 | 02-FEB-07:10 |
March | 0.991014E+11 | 91360.11 | 28-MAR-15:00 | 0.752601E+10 | 4891.87 | 01-MAR-12:50 |
April | 0.122205E+12 | 112081.97 | 28-APR-15:30 | 0.703287E+10 | 4839.64 | 03-APR-11:50 |
May | 0.153468E+12 | 129199.19 | 30-MAY-15:50 | 0.704691E+10 | 4788.64 | 01-MAY-11:30 |
June | 0.158045E+12 | 141825.34 | 10-JUN-15:00 | 0.668014E+10 | 4741.13 | 01-JUN-11:20 |
July | 0.156670E+12 | 134422.43 | 01-JUL-16:49 | 0.679391E+10 | 4712.71 | 03-JUL-11:50 |
August | 0.153033E+12 | 123370.97 | 07-AUG-14:00 | 0.688843E+10 | 4735.69 | 31-AUG-11:39 |
September | 0.133186E+12 | 114106.49 | 14-SEP-16:00 | 0.679256E+10 | 4777.76 | 29-SEP-11:20 |
October | 0.115626E+12 | 103496.91 | 03-OCT-15:09 | 0.720756E+10 | 4834.73 | 31-OCT-11:00 |
November | 0.908107E+11 | 82319.10 | 08-NOV-17:30 | 0.718998E+10 | 5267.29 | 27-NOV-07:30 |
December | 0.751581E+11 | 66702.55 | 01-DEC-17:19 | 0.101823E+11 | 74507.10 | 23-DEC-07:10 |
Annual Sum or Average | 0.140205E+13 | 0.989807E+11 | ||||
Minimum of Months | 0.720973E+11 | 64459.42 | 0.668014E+10 | 4712.71 | ||
Maximum of Months | 0.158045E+12 | 141825.34 | 0.174151E+11 | 116396.24 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.317806E+11 | 0.593541E+10 | 0.163682E+11 | 0.00 | 0.138915E+11 | 0.00 | 0.00 | 0.412165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.280500E+11 | 0.509539E+10 | 0.148500E+11 | 0.00 | 0.124025E+11 | 0.00 | 0.00 | 0.122463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.299141E+11 | 0.521089E+10 | 0.167807E+11 | 0.00 | 0.139228E+11 | 0.00 | 0.00 | 0.332729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.290962E+11 | 0.462158E+10 | 0.159462E+11 | 0.00 | 0.139869E+11 | 0.00 | 0.00 | 0.585542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.301883E+11 | 0.440557E+10 | 0.165744E+11 | 0.00 | 0.167986E+11 | 0.00 | 0.00 | 0.855015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.291672E+11 | 0.406426E+10 | 0.162059E+11 | 0.00 | 0.177899E+11 | 0.00 | 0.00 | 0.908181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.279330E+11 | 0.430804E+10 | 0.163148E+11 | 0.00 | 0.179150E+11 | 0.00 | 0.00 | 0.901992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.291455E+11 | 0.460621E+10 | 0.167807E+11 | 0.00 | 0.172840E+11 | 0.00 | 0.00 | 0.852169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.278875E+11 | 0.486122E+10 | 0.159462E+11 | 0.00 | 0.147873E+11 | 0.00 | 0.00 | 0.697041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.303999E+11 | 0.546169E+10 | 0.163682E+11 | 0.00 | 0.139387E+11 | 0.00 | 0.00 | 0.494573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.308423E+11 | 0.564983E+10 | 0.158468E+11 | 0.00 | 0.131548E+11 | 0.00 | 0.00 | 0.253170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318625E+11 | 0.606637E+10 | 0.163148E+11 | 0.00 | 0.137218E+11 | 0.00 | 0.00 | 0.719263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356267E+12 | 0.602865E+11 | 0.194297E+12 | 0.179594E+12 | 0.00 | 0.611602E+12 | |||||||
Minimum of Months | 0.278875E+11 | 0.406426E+10 | 0.148500E+11 | 0.00 | 0.124025E+11 | 0.00 | 0.00 | 0.412165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.318625E+11 | 0.606637E+10 | 0.167807E+11 | 0.00 | 0.179150E+11 | 0.00 | 0.00 | 0.908181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.973003E+10 | 0.00 | 0.768508E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.132529E+10 | 0.00 | 0.689964E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.752601E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.703287E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.704691E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.668014E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.679391E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.688843E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.679256E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.720756E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 5659785.78 | 0.00 | 0.718432E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.256527E+10 | 0.00 | 0.761703E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136263E+11 | 0.853545E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.668014E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.973003E+10 | 0.00 | 0.768508E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28576.57 | 02-JAN-15:50 | 4644.30 | 01-JAN-06:10 | 10740.89 | 02-JAN-09:09 | 0.00 | 11748.55 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28576.57 | 01-FEB-16:10 | 4644.30 | 01-FEB-06:10 | 10740.89 | 01-FEB-09:09 | 0.00 | 10324.98 | 02-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28576.57 | 01-MAR-16:40 | 4644.30 | 01-MAR-06:10 | 10740.89 | 01-MAR-09:09 | 0.00 | 10735.94 | 13-MAR-06:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28576.57 | 01-APR-16:00 | 4644.30 | 01-APR-05:10 | 10740.89 | 01-APR-09:09 | 0.00 | 11871.58 | 16-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28576.57 | 03-MAY-08:09 | 4644.30 | 01-MAY-05:10 | 10740.89 | 01-MAY-08:09 | 0.00 | 14801.56 | 30-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28576.57 | 15-JUN-16:00 | 4644.30 | 01-JUN-05:10 | 10740.89 | 01-JUN-08:09 | 0.00 | 16486.98 | 10-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28576.57 | 10-JUL-16:49 | 4644.30 | 01-JUL-05:10 | 10740.89 | 01-JUL-09:09 | 0.00 | 16690.25 | 01-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28576.57 | 10-AUG-16:40 | 4644.30 | 01-AUG-05:10 | 10740.89 | 01-AUG-08:09 | 0.00 | 14675.50 | 07-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28576.57 | 02-SEP-16:00 | 4644.30 | 01-SEP-05:10 | 10740.89 | 01-SEP-08:09 | 0.00 | 12761.30 | 14-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28576.57 | 02-OCT-16:30 | 4644.30 | 01-OCT-05:10 | 10740.89 | 02-OCT-08:09 | 0.00 | 12076.32 | 04-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28576.57 | 01-NOV-08:09 | 4644.30 | 01-NOV-05:10 | 10740.89 | 01-NOV-08:09 | 0.00 | 8574.59 | 09-NOV-15:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28576.57 | 01-DEC-15:30 | 4644.30 | 01-DEC-06:10 | 10740.89 | 01-DEC-09:09 | 0.00 | 10572.90 | 23-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 28576.57 | 4644.30 | 10740.89 | 0.00 | 8574.59 | 0.00 | 0.00 | |||||
Maximum of Months | 28576.57 | 4644.30 | 10740.89 | 0.00 | 16690.25 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 15308.43 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27115.54 | 24-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45137.61 | 28-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63919.30 | 28-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78150.72 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87881.46 | 10-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83180.79 | 01-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74959.71 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 64526.34 | 14-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 56508.26 | 03-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34412.33 | 09-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18117.36 | 28-DEC-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 15308.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87881.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 64459.42 | 14-JAN-17:49 | 28576.57 | 10740.89 | 4644.30 | 0.00 | 8501.96 | 0.00 | 0.00 | 11995.70 | 0.00 |
February | 73921.12 | 24-FEB-16:40 | 28576.57 | 10740.89 | 0.00 | 0.00 | 8501.96 | 0.00 | 0.00 | 26101.70 | 0.00 |
March | 91360.11 | 28-MAR-15:00 | 26716.01 | 10740.89 | 0.00 | 0.00 | 8765.61 | 0.00 | 0.00 | 45137.61 | 0.00 |
April | 112081.97 | 28-APR-15:30 | 26716.01 | 10740.89 | 0.00 | 0.00 | 11573.36 | 0.00 | 0.00 | 63051.72 | 0.00 |
May | 129199.19 | 30-MAY-15:50 | 26716.01 | 10740.89 | 0.00 | 0.00 | 14546.93 | 0.00 | 0.00 | 77195.37 | 0.00 |
June | 141825.34 | 10-JUN-15:00 | 26716.01 | 10740.89 | 0.00 | 0.00 | 16486.98 | 0.00 | 0.00 | 87881.46 | 0.00 |
July | 134422.43 | 01-JUL-16:49 | 26716.01 | 10740.89 | 0.00 | 0.00 | 16142.04 | 0.00 | 0.00 | 80823.50 | 0.00 |
August | 123370.97 | 07-AUG-14:00 | 22994.88 | 10740.89 | 0.00 | 0.00 | 14675.50 | 0.00 | 0.00 | 74959.71 | 0.00 |
September | 114106.49 | 14-SEP-16:00 | 28576.57 | 10740.89 | 0.00 | 0.00 | 12272.77 | 0.00 | 0.00 | 62516.27 | 0.00 |
October | 103496.91 | 03-OCT-15:09 | 26716.01 | 10740.89 | 0.00 | 0.00 | 10355.69 | 0.00 | 0.00 | 55684.33 | 0.00 |
November | 82319.10 | 08-NOV-17:30 | 28576.57 | 10740.89 | 4644.30 | 0.00 | 8501.96 | 0.00 | 0.00 | 29855.38 | 0.00 |
December | 66702.55 | 01-DEC-17:19 | 28576.57 | 10740.89 | 4644.30 | 0.00 | 8501.96 | 0.00 | 0.00 | 14238.83 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 64459.42 | 22994.88 | 10740.89 | 0.00 | 0.00 | 8501.96 | 0.00 | 0.00 | 11995.70 | 0.00 | |
Maximum of Months | 141825.34 | 28576.57 | 10740.89 | 4644.30 | 0.00 | 16486.98 | 0.00 | 0.00 | 87881.46 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 114536.24 | 02-JAN-07:10 | 0.00 | 4923.56 | 23-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 62929.17 | 02-FEB-07:10 | 0.00 | 4919.35 | 01-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 4891.87 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 4839.64 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 4788.64 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 4741.13 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4712.71 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 4735.69 | 31-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 4777.76 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 4834.73 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 1632.08 | 27-NOV-06:00 | 0.00 | 4884.25 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 72647.10 | 23-DEC-07:10 | 0.00 | 4914.40 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4712.71 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 114536.24 | 0.00 | 4923.56 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.50 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.82 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 25.48 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.58 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 25.49 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 25.18 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 24.87 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.63 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 20.42 | 0.00 | 58.00 | 25.26 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 20.49 | 0.00 | 0.00 | 10.67 | 25.58 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.71 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 26.02 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.33 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.17 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 26.72 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 26.50 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 25.68 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 25.53 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.59 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.45 | 0.00 | 92.83 | 26.27 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.45 | 0.00 | 0.00 | 15.50 | 27.17 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.66 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 25.31 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 25.68 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.56 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 25.65 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 25.54 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 24.86 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.54 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.34 | 0.00 | 68.33 | 25.40 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.34 | 0.00 | 0.00 | 11.50 | 25.68 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.33 | 14.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.67 | 15.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16.00 | 14.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 56.00 | 14.62 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.33 | 15.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.00 | 22.21 | 55.33 | 21.26 | 55.33 | 21.26 |
February | 313.67 | 23.10 | 6.83 | 23.35 | 1.33 | 21.11 |
March | 87.33 | 23.65 | 153.33 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 365.17 | 23.89 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 418.00 | 23.89 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 408.00 | 23.89 | 0.00 | 0.00 |
July | 0.50 | 23.89 | 415.00 | 23.89 | 0.50 | 23.89 |
August | 0.00 | 0.00 | 422.00 | 23.89 | 0.00 | 0.00 |
September | 9.33 | 23.89 | 405.00 | 23.89 | 9.33 | 23.89 |
October | 2.17 | 23.89 | 356.00 | 23.89 | 0.00 | 0.00 |
November | 164.00 | 23.52 | 33.50 | 23.89 | 0.00 | 0.00 |
December | 415.00 | 22.74 | 20.17 | 21.11 | 20.17 | 21.11 |
Annual Sum or Average | 1406.00 | 22.82 | 3058.33 | 23.82 | 86.67 | 21.52 |
Minimum of Months | 0.00 | 0.00 | 6.83 | 21.11 | 0.00 | 0.00 |
Maximum of Months | 415.00 | 23.89 | 422.00 | 23.89 | 55.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 355.33 | 22.74 | 4.17 | 21.16 | 4.17 | 21.16 |
February | 132.67 | 22.87 | 54.83 | 23.89 | 0.00 | 0.00 |
March | 16.67 | 23.37 | 281.67 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 395.17 | 23.89 | 0.00 | 0.00 |
May | 2.00 | 23.96 | 418.00 | 23.89 | 2.00 | 23.96 |
June | 22.17 | 23.92 | 408.00 | 23.89 | 22.17 | 23.92 |
July | 48.67 | 23.92 | 415.00 | 23.89 | 48.67 | 23.92 |
August | 85.33 | 23.91 | 422.00 | 23.89 | 85.33 | 23.91 |
September | 96.00 | 23.90 | 405.00 | 23.89 | 96.00 | 23.90 |
October | 5.00 | 23.89 | 403.50 | 23.89 | 5.00 | 23.89 |
November | 38.50 | 23.08 | 201.33 | 23.89 | 0.00 | 0.00 |
December | 255.17 | 22.87 | 0.33 | 21.30 | 0.33 | 21.30 |
Annual Sum or Average | 1057.50 | 23.10 | 3409.00 | 23.89 | 263.67 | 23.86 |
Minimum of Months | 0.00 | 0.00 | 0.33 | 21.16 | 0.00 | 0.00 |
Maximum of Months | 355.33 | 23.96 | 422.00 | 23.89 | 96.00 | 23.96 |
Report: ComfortReportSimple55Monthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 163.00 | 22.59 | 74.33 | 23.82 | 1.83 | 21.11 |
February | 74.17 | 22.84 | 199.50 | 23.89 | 0.00 | 0.00 |
March | 13.33 | 23.77 | 356.17 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 398.00 | 23.89 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 418.00 | 23.89 | 0.00 | 0.00 |
June | 1.83 | 23.89 | 408.00 | 23.89 | 1.83 | 23.89 |
July | 1.50 | 23.89 | 415.00 | 23.89 | 1.50 | 23.89 |
August | 0.83 | 23.89 | 422.00 | 23.89 | 0.83 | 23.89 |
September | 11.83 | 23.89 | 405.00 | 23.89 | 11.83 | 23.89 |
October | 0.00 | 0.00 | 414.00 | 23.89 | 0.00 | 0.00 |
November | 9.67 | 23.48 | 344.83 | 23.89 | 0.00 | 0.00 |
December | 110.17 | 22.94 | 161.33 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 386.33 | 22.86 | 4016.17 | 23.89 | 17.83 | 23.60 |
Minimum of Months | 0.00 | 0.00 | 74.33 | 23.82 | 0.00 | 0.00 |
Maximum of Months | 163.00 | 23.89 | 422.00 | 23.89 | 11.83 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 208.67 | 22.27 | 36.33 | 23.49 | 5.17 | 21.11 |
February | 98.50 | 22.41 | 173.50 | 23.89 | 0.00 | 0.00 |
March | 26.50 | 23.47 | 337.00 | 23.89 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 390.17 | 23.89 | 0.00 | 0.00 |
May | 0.67 | 23.89 | 418.00 | 23.89 | 0.67 | 23.89 |
June | 8.33 | 23.89 | 408.00 | 23.89 | 8.33 | 23.89 |
July | 7.33 | 23.89 | 415.00 | 23.89 | 7.33 | 23.89 |
August | 4.00 | 23.89 | 422.00 | 23.89 | 4.00 | 23.89 |
September | 47.17 | 23.89 | 405.00 | 23.89 | 47.17 | 23.89 |
October | 0.00 | 0.00 | 407.67 | 23.89 | 0.00 | 0.00 |
November | 18.67 | 23.18 | 334.00 | 23.89 | 0.00 | 0.00 |
December | 139.83 | 22.57 | 114.33 | 23.89 | 0.00 | 0.00 |
Annual Sum or Average | 559.67 | 22.65 | 3861.00 | 23.89 | 72.67 | 23.69 |
Minimum of Months | 0.00 | 0.00 | 36.33 | 23.49 | 0.00 | 0.00 |
Maximum of Months | 208.67 | 23.89 | 422.00 | 23.89 | 47.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.20110 | 49.65223 | -0.2028 | 7.21801 |
February | 376.00000 | 23.20616 | 48.28088 | 0.09971 | 6.51799 |
March | 422.00000 | 23.83489 | 43.79572 | 0.36883 | 8.11111 |
April | 405.00000 | 23.88977 | 41.58723 | 0.53496 | 11.13440 |
May | 418.00000 | 23.88967 | 45.38434 | -0.1373 | 5.55495 |
June | 408.00000 | 23.88954 | 48.22761 | -0.1078 | 5.47654 |
July | 415.00000 | 23.88949 | 50.81905 | -0.1113 | 5.40197 |
August | 422.00000 | 23.88959 | 51.59787 | -0.1428 | 5.49959 |
September | 405.00000 | 23.88967 | 51.86534 | -0.2183 | 6.08089 |
October | 414.00000 | 23.88979 | 45.41518 | 0.49017 | 10.11843 |
November | 399.00000 | 23.72373 | 45.31860 | 0.29283 | 7.23362 |
December | 415.00000 | 22.72191 | 47.73737 | -0.0620 | 6.58280 |
Annual Sum or Average | 4913.00000 | 23.57823 | 47.47536 | 0.06587 | 7.07516 |
Minimum of Months | 376.00000 | 22.20110 | 41.58723 | -0.2183 | 5.40197 |
Maximum of Months | 422.00000 | 23.88979 | 51.86534 | 0.53496 | 11.13440 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 22.87801 | 43.31056 | 0.04886 | 6.48181 |
February | 376.00000 | 23.50585 | 43.21444 | 0.27208 | 7.33894 |
March | 422.00000 | 23.86997 | 41.72819 | 0.44630 | 9.30364 |
April | 405.00000 | 23.91087 | 41.32527 | 0.55963 | 11.66697 |
May | 418.00000 | 23.91346 | 48.09580 | -0.1480 | 5.57417 |
June | 408.00000 | 23.91417 | 53.01159 | -0.1218 | 5.44177 |
July | 415.00000 | 23.91547 | 58.23445 | -0.1249 | 5.42585 |
August | 422.00000 | 23.91484 | 59.64246 | -0.1418 | 5.48494 |
September | 405.00000 | 23.91437 | 58.09481 | -0.1873 | 5.80222 |
October | 414.00000 | 23.90500 | 46.57972 | 0.53924 | 11.15804 |
November | 399.00000 | 23.80024 | 42.10595 | 0.39709 | 8.51174 |
December | 415.00000 | 23.23729 | 41.26812 | 0.15867 | 6.60586 |
Annual Sum or Average | 4913.00000 | 23.72446 | 48.10368 | 0.13962 | 7.39217 |
Minimum of Months | 376.00000 | 22.87801 | 41.26812 | -0.1873 | 5.42585 |
Maximum of Months | 422.00000 | 23.91547 | 59.64246 | 0.55963 | 11.66697 |
Report: OccupantComfortDataSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.35172 | 39.78871 | 0.21770 | 7.58821 |
February | 376.00000 | 23.66501 | 40.04310 | 0.37427 | 8.86674 |
March | 422.00000 | 23.88506 | 39.33845 | 0.52803 | 11.10119 |
April | 405.00000 | 23.88972 | 39.96800 | 0.63968 | 13.80266 |
May | 418.00000 | 23.88970 | 45.50547 | -0.0461 | 5.26917 |
June | 408.00000 | 23.88954 | 49.14457 | -0.0270 | 5.27984 |
July | 415.00000 | 23.88944 | 52.21747 | -0.0253 | 5.17914 |
August | 422.00000 | 23.88949 | 52.70549 | -0.0401 | 5.16482 |
September | 405.00000 | 23.88953 | 51.25295 | -0.0712 | 5.36979 |
October | 414.00000 | 23.88987 | 41.76893 | 0.66496 | 14.48126 |
November | 399.00000 | 23.87773 | 37.85716 | 0.55421 | 11.71253 |
December | 415.00000 | 23.61396 | 37.10260 | 0.32064 | 8.15007 |
Annual Sum or Average | 4913.00000 | 23.80246 | 43.93511 | 0.25558 | 8.47982 |
Minimum of Months | 376.00000 | 23.35172 | 37.10260 | -0.0712 | 5.16482 |
Maximum of Months | 422.00000 | 23.88987 | 52.70549 | 0.66496 | 14.48126 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 414.00000 | 23.04982 | 41.80170 | 0.13650 | 7.33657 |
February | 376.00000 | 23.48279 | 41.88765 | 0.31919 | 8.47144 |
March | 422.00000 | 23.86006 | 40.43424 | 0.50215 | 10.59629 |
April | 405.00000 | 23.88967 | 40.36732 | 0.61769 | 13.22385 |
May | 418.00000 | 23.88962 | 46.24048 | -0.0744 | 5.34824 |
June | 408.00000 | 23.88950 | 50.35565 | -0.0581 | 5.32653 |
July | 415.00000 | 23.88944 | 53.84595 | -0.0525 | 5.22259 |
August | 422.00000 | 23.88946 | 54.54186 | -0.0678 | 5.21965 |
September | 405.00000 | 23.88950 | 53.25206 | -0.0981 | 5.44448 |
October | 414.00000 | 23.88973 | 42.64933 | 0.64450 | 13.91233 |
November | 399.00000 | 23.85157 | 38.75102 | 0.52583 | 11.12772 |
December | 415.00000 | 23.41771 | 38.82440 | 0.26007 | 7.79743 |
Annual Sum or Average | 4913.00000 | 23.74219 | 45.28836 | 0.21946 | 8.23720 |
Minimum of Months | 376.00000 | 23.04982 | 38.75102 | -0.0981 | 5.21965 |
Maximum of Months | 422.00000 | 23.88973 | 54.54186 | 0.64450 | 13.91233 |
Report: OccupantComfortDataSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.257341E+09 | 72227754.36 | 29.13 | 0.194822E+09 | 62519083.09 | 0.00 | 0.22 | 14-JAN-16:20 | 0.00 | 01-JAN-00:10 | 5612.96 | 14-JAN-16:20 | 4085.47 | 14-JAN-16:30 | 1533.85 | 14-JAN-16:00 | 1529.70 | 14-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 0.345950E+10 | 0.967438E+09 | 199.17 | 0.277951E+10 | 0.679994E+09 | 0.00 | 0.46 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 | 12150.08 | 24-FEB-16:00 | 9711.33 | 24-FEB-16:00 | 3502.03 | 25-FEB-17:00 | 3357.49 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.154183E+11 | 0.431441E+10 | 409.59 | 0.130076E+11 | 0.241069E+10 | 0.00 | 1.00 | 10-MAR-05:01 | 0.00 | 01-MAR-00:10 | 64561.29 | 11-MAR-05:01 | 57329.52 | 29-MAR-04:01 | 14755.44 | 11-MAR-05:02 | 14368.55 | 11-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.318483E+11 | 0.911105E+10 | 455.43 | 0.286713E+11 | 0.317700E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 64737.31 | 17-APR-04:01 | 62714.32 | 29-APR-04:01 | 12050.19 | 17-APR-04:05 | 15227.93 | 27-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.489574E+11 | 0.141324E+11 | 490.93 | 0.419354E+11 | 0.702197E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:05 | 68208.58 | 24-MAY-04:01 | 63111.01 | 09-MAY-04:01 | 26046.43 | 24-MAY-04:06 | 16025.79 | 31-MAY-04:01 | 0.00 | 01-MAY-00:05 |
June | 0.526736E+11 | 0.150144E+11 | 490.36 | 0.423966E+11 | 0.102771E+11 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 70064.31 | 26-JUN-04:01 | 61571.21 | 05-JUN-04:01 | 32566.03 | 26-JUN-04:07 | 16376.88 | 12-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.559402E+11 | 0.148067E+11 | 492.65 | 0.405696E+11 | 0.153706E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:05 | 70343.62 | 20-JUL-04:01 | 56060.94 | 07-JUL-04:01 | 33134.29 | 20-JUL-04:08 | 16360.33 | 02-JUL-06:01 | 0.00 | 01-JUL-00:05 |
August | 0.528551E+11 | 0.135346E+11 | 478.59 | 0.370151E+11 | 0.158399E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 68716.03 | 19-AUG-04:01 | 56533.97 | 09-AUG-04:01 | 27727.39 | 19-AUG-04:07 | 15730.32 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.412871E+11 | 0.107191E+11 | 457.68 | 0.294560E+11 | 0.118311E+11 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 69375.23 | 03-SEP-06:01 | 56822.18 | 27-SEP-04:01 | 31852.58 | 10-SEP-06:03 | 15106.40 | 02-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.259930E+11 | 0.712781E+10 | 462.73 | 0.212544E+11 | 0.473858E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 66152.66 | 12-OCT-04:01 | 59014.29 | 02-OCT-04:01 | 21610.47 | 12-OCT-04:02 | 14516.72 | 04-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.947166E+10 | 0.266223E+10 | 341.82 | 0.780583E+10 | 0.166583E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 62771.17 | 01-NOV-04:01 | 51025.85 | 01-NOV-04:01 | 13061.53 | 09-NOV-05:01 | 13585.54 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 |
December | 0.835681E+09 | 0.236352E+09 | 98.67 | 0.653367E+09 | 0.182314E+09 | 0.00 | 0.24 | 01-DEC-15:30 | 0.00 | 01-DEC-00:10 | 5878.83 | 28-DEC-16:00 | 5070.91 | 01-DEC-15:20 | 1490.30 | 16-DEC-16:10 | 1660.50 | 28-DEC-16:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.338997E+12 | 0.926987E+11 | 4406.74 | 0.265739E+12 | 0.732576E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.257341E+09 | 72227754.36 | 29.13 | 0.194822E+09 | 62519083.09 | 0.00 | 0.22 | 0.00 | 5612.96 | 4085.47 | 1490.30 | 1529.70 | 0.00 | |||||||
Maximum of Months | 0.559402E+11 | 0.150144E+11 | 492.65 | 0.423966E+11 | 0.158399E+11 | 0.00 | 1.00 | 0.00 | 70343.62 | 63111.01 | 33134.29 | 16376.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.737716E+10 | 0.222909E+10 | 156.87 | 0.599223E+10 | 0.138493E+10 | 0.00 | 0.38 | 14-JAN-15:20 | 0.00 | 01-JAN-00:10 | 35100.59 | 14-JAN-15:20 | 27714.41 | 12-JAN-16:00 | 9037.02 | 14-JAN-15:20 | 10137.51 | 14-JAN-15:20 | 0.00 | 01-JAN-00:10 |
February | 0.270976E+11 | 0.801850E+10 | 271.75 | 0.218353E+11 | 0.526228E+10 | 0.00 | 0.65 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 | 63699.69 | 24-FEB-16:00 | 50708.04 | 22-FEB-15:10 | 20915.69 | 25-FEB-17:00 | 18312.08 | 24-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.754281E+11 | 0.221587E+11 | 402.48 | 0.617998E+11 | 0.136284E+11 | 0.00 | 1.00 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 | 227396.38 | 11-MAR-07:02 | 173941.44 | 13-MAR-06:03 | 57121.64 | 11-MAR-07:02 | 55671.97 | 11-MAR-07:02 | 0.00 | 01-MAR-00:10 |
April | 0.126641E+12 | 0.385441E+11 | 422.35 | 0.109942E+12 | 0.166994E+11 | 0.00 | 1.00 | 01-APR-06:02 | 0.00 | 01-APR-00:10 | 231690.67 | 24-APR-06:02 | 210893.88 | 28-APR-05:01 | 73333.42 | 24-APR-06:02 | 60718.45 | 27-APR-05:01 | 0.00 | 01-APR-00:10 |
May | 0.182781E+12 | 0.562027E+11 | 448.84 | 0.144859E+12 | 0.379217E+11 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:05 | 238695.65 | 24-MAY-06:02 | 211390.27 | 01-MAY-05:01 | 98388.23 | 24-MAY-06:04 | 62730.12 | 04-MAY-04:01 | 0.00 | 01-MAY-00:05 |
June | 0.200999E+12 | 0.599780E+11 | 439.59 | 0.142409E+12 | 0.585895E+11 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 246972.63 | 25-JUN-08:62 | 201329.59 | 07-JUN-04:01 | 125199.79 | 25-JUN-08:04 | 63717.90 | 14-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.216563E+12 | 0.594673E+11 | 445.69 | 0.128931E+12 | 0.876328E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:05 | 246894.52 | 19-JUL-06:02 | 180851.94 | 05-JUL-04:01 | 125344.46 | 19-JUL-06:04 | 64312.40 | 02-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.213281E+12 | 0.565744E+11 | 449.20 | 0.119412E+12 | 0.938694E+11 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 248652.64 | 20-AUG-08:62 | 164244.93 | 07-AUG-04:01 | 131102.49 | 20-AUG-08:62 | 61392.08 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.171923E+12 | 0.460474E+11 | 428.81 | 0.101742E+12 | 0.701803E+11 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:10 | 250266.71 | 10-SEP-08:62 | 169382.55 | 26-SEP-05:02 | 137715.58 | 10-SEP-08:62 | 59991.05 | 24-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.110581E+12 | 0.318026E+11 | 417.54 | 0.839302E+11 | 0.266504E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 239002.38 | 12-OCT-06:02 | 184159.20 | 02-OCT-05:03 | 104552.89 | 13-OCT-06:03 | 57602.01 | 04-OCT-06:02 | 0.00 | 01-OCT-00:10 |
November | 0.548974E+11 | 0.161456E+11 | 356.53 | 0.445752E+11 | 0.103222E+11 | 0.00 | 0.76 | 09-NOV-15:10 | 0.00 | 01-NOV-00:10 | 76172.49 | 09-NOV-15:10 | 64840.27 | 04-NOV-14:50 | 21968.99 | 09-NOV-07:05 | 22330.54 | 09-NOV-13:20 | 0.00 | 01-NOV-00:10 |
December | 0.140779E+11 | 0.422542E+10 | 224.29 | 0.112925E+11 | 0.278542E+10 | 0.00 | 0.44 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 39540.37 | 01-DEC-15:30 | 35492.26 | 01-DEC-15:10 | 9352.32 | 16-DEC-16:00 | 11634.65 | 28-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.140165E+13 | 0.401394E+12 | 4463.95 | 0.976720E+12 | 0.424927E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.737716E+10 | 0.222909E+10 | 156.87 | 0.599223E+10 | 0.138493E+10 | 0.00 | 0.38 | 0.00 | 35100.59 | 27714.41 | 9037.02 | 10137.51 | 0.00 | |||||||
Maximum of Months | 0.216563E+12 | 0.599780E+11 | 449.20 | 0.144859E+12 | 0.938694E+11 | 0.00 | 1.00 | 0.00 | 250266.71 | 211390.27 | 137715.58 | 64312.40 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.458195E+10 | 0.117169E+10 | 287.53 | 0.407006E+10 | 0.511891E+09 | 0.00 | 0.69 | 12-JAN-15:50 | 0.00 | 01-JAN-00:10 | 10038.93 | 12-JAN-16:00 | 9189.60 | 12-JAN-15:40 | 1453.75 | 13-JAN-14:20 | 2447.15 | 12-JAN-15:50 | 0.00 | 01-JAN-00:10 |
February | 0.759795E+10 | 0.190845E+10 | 322.32 | 0.668022E+10 | 0.917728E+09 | 0.00 | 1.00 | 23-FEB-05:01 | 0.00 | 01-FEB-00:10 | 33007.45 | 23-FEB-05:01 | 30365.36 | 23-FEB-05:01 | 5241.75 | 25-FEB-05:02 | 7028.65 | 23-FEB-05:01 | 0.00 | 01-FEB-00:10 |
March | 0.147403E+11 | 0.376174E+10 | 453.49 | 0.129953E+11 | 0.174503E+10 | 0.00 | 1.00 | 06-MAR-05:02 | 0.00 | 01-MAR-00:10 | 34769.30 | 11-MAR-05:01 | 32693.86 | 29-MAR-04:01 | 7418.23 | 11-MAR-05:03 | 7586.96 | 11-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.213806E+11 | 0.583438E+10 | 474.78 | 0.194639E+11 | 0.191669E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 35063.59 | 17-APR-04:01 | 33485.19 | 21-APR-04:01 | 7376.00 | 17-APR-04:05 | 8078.13 | 27-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.285715E+11 | 0.804585E+10 | 528.31 | 0.241733E+11 | 0.439822E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:10 | 36847.99 | 24-MAY-04:01 | 33499.76 | 29-MAY-06:01 | 14730.01 | 24-MAY-04:05 | 8475.31 | 04-MAY-04:01 | 0.00 | 01-MAY-00:05 |
June | 0.304092E+11 | 0.841304E+10 | 518.96 | 0.236991E+11 | 0.671013E+10 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 37958.32 | 26-JUN-04:01 | 31810.49 | 05-JUN-04:11 | 18403.13 | 26-JUN-04:06 | 8646.03 | 12-JUN-04:11 | 0.00 | 01-JUN-00:10 |
July | 0.329362E+11 | 0.843233E+10 | 515.04 | 0.226784E+11 | 0.102578E+11 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:05 | 38085.69 | 20-JUL-04:01 | 28184.72 | 07-JUL-04:01 | 18649.70 | 20-JUL-04:07 | 8623.03 | 02-JUL-06:01 | 0.00 | 01-JUL-00:05 |
August | 0.323426E+11 | 0.800804E+10 | 496.05 | 0.215419E+11 | 0.108007E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 37292.25 | 19-AUG-04:01 | 28144.79 | 06-AUG-06:01 | 16039.35 | 11-AUG-04:05 | 8300.68 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.277083E+11 | 0.688963E+10 | 471.80 | 0.194552E+11 | 0.825312E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 37617.05 | 03-SEP-06:01 | 30925.52 | 27-SEP-04:01 | 18013.07 | 10-SEP-06:03 | 7996.34 | 18-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.224487E+11 | 0.563569E+10 | 474.90 | 0.189902E+11 | 0.345852E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 35654.96 | 12-OCT-04:01 | 32937.00 | 23-OCT-04:01 | 11785.76 | 12-OCT-04:02 | 7707.39 | 04-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.146282E+11 | 0.358647E+10 | 425.92 | 0.129964E+11 | 0.163182E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 33804.75 | 09-NOV-05:01 | 31749.70 | 02-NOV-04:01 | 4867.01 | 30-NOV-05:02 | 7183.80 | 09-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.664207E+10 | 0.167444E+10 | 338.71 | 0.585502E+10 | 0.787051E+09 | 0.00 | 0.97 | 29-DEC-05:03 | 0.00 | 01-DEC-00:10 | 15612.46 | 29-DEC-05:03 | 13552.45 | 29-DEC-05:03 | 2060.01 | 29-DEC-05:03 | 3382.38 | 29-DEC-05:03 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.243988E+12 | 0.633618E+11 | 5307.82 | 0.192599E+12 | 0.513887E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.458195E+10 | 0.117169E+10 | 287.53 | 0.407006E+10 | 0.511891E+09 | 0.00 | 0.69 | 0.00 | 10038.93 | 9189.60 | 1453.75 | 2447.15 | 0.00 | |||||||
Maximum of Months | 0.329362E+11 | 0.843233E+10 | 528.31 | 0.241733E+11 | 0.108007E+11 | 0.00 | 1.00 | 0.00 | 38085.69 | 33499.76 | 18649.70 | 8646.03 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {Maximum}[W] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER {TIMESTAMP} | |
January | 0.248481E+10 | 0.648638E+09 | 219.30 | 0.217822E+10 | 0.306586E+09 | 0.00 | 0.61 | 12-JAN-15:40 | 0.00 | 01-JAN-00:10 | 7902.24 | 12-JAN-15:40 | 7126.45 | 12-JAN-15:30 | 1279.51 | 13-JAN-15:10 | 1972.12 | 12-JAN-15:40 | 0.00 | 01-JAN-00:10 |
February | 0.528720E+10 | 0.135190E+10 | 282.92 | 0.457933E+10 | 0.707867E+09 | 0.00 | 1.00 | 23-FEB-05:01 | 0.00 | 01-FEB-00:10 | 29669.68 | 23-FEB-05:01 | 26236.75 | 23-FEB-05:01 | 4596.25 | 25-FEB-05:02 | 6318.23 | 23-FEB-05:01 | 0.00 | 01-FEB-00:10 |
March | 0.117444E+11 | 0.303806E+10 | 425.45 | 0.101766E+11 | 0.156779E+10 | 0.00 | 1.00 | 07-MAR-05:01 | 0.00 | 01-MAR-00:10 | 31303.76 | 11-MAR-05:01 | 28228.44 | 29-MAR-04:01 | 7346.86 | 11-MAR-05:03 | 6835.03 | 11-MAR-05:01 | 0.00 | 01-MAR-00:10 |
April | 0.184631E+11 | 0.506468E+10 | 462.49 | 0.166182E+11 | 0.184488E+10 | 0.00 | 1.00 | 01-APR-04:01 | 0.00 | 01-APR-00:10 | 31521.25 | 17-APR-04:01 | 29907.52 | 28-APR-04:01 | 6846.12 | 17-APR-04:05 | 7254.85 | 27-APR-04:01 | 0.00 | 01-APR-00:10 |
May | 0.253329E+11 | 0.712052E+10 | 501.92 | 0.210855E+11 | 0.424735E+10 | 0.00 | 1.00 | 01-MAY-04:01 | 0.00 | 01-MAY-00:05 | 33201.34 | 24-MAY-04:01 | 29977.53 | 29-MAY-06:01 | 13778.52 | 24-MAY-04:05 | 7640.16 | 04-MAY-04:01 | 0.00 | 01-MAY-00:05 |
June | 0.269235E+11 | 0.741263E+10 | 492.80 | 0.204571E+11 | 0.646641E+10 | 0.00 | 1.00 | 01-JUN-04:01 | 0.00 | 01-JUN-00:10 | 34207.86 | 26-JUN-04:01 | 28455.47 | 05-JUN-04:01 | 17222.58 | 26-JUN-04:06 | 7785.00 | 12-JUN-04:01 | 0.00 | 01-JUN-00:10 |
July | 0.294501E+11 | 0.749287E+10 | 494.59 | 0.195346E+11 | 0.991546E+10 | 0.00 | 1.00 | 01-JUL-04:01 | 0.00 | 01-JUL-00:20 | 34335.21 | 20-JUL-04:01 | 25391.54 | 07-JUL-04:11 | 17385.38 | 20-JUL-04:07 | 7773.92 | 02-JUL-06:01 | 0.00 | 01-JUL-00:05 |
August | 0.288538E+11 | 0.709981E+10 | 484.60 | 0.183976E+11 | 0.104562E+11 | 0.00 | 1.00 | 01-AUG-04:01 | 0.00 | 01-AUG-00:10 | 33682.02 | 19-AUG-04:01 | 25020.39 | 09-AUG-04:01 | 15275.33 | 11-AUG-04:12 | 7483.47 | 08-AUG-04:01 | 0.00 | 01-AUG-00:10 |
September | 0.243584E+11 | 0.604796E+10 | 460.91 | 0.164636E+11 | 0.789482E+10 | 0.00 | 1.00 | 01-SEP-04:01 | 0.00 | 01-SEP-00:10 | 33907.13 | 03-SEP-06:01 | 26905.16 | 27-SEP-04:01 | 17452.78 | 10-SEP-06:02 | 7209.18 | 02-SEP-04:01 | 0.00 | 01-SEP-00:10 |
October | 0.193792E+11 | 0.489126E+10 | 469.40 | 0.160745E+11 | 0.330472E+10 | 0.00 | 1.00 | 01-OCT-06:01 | 0.00 | 01-OCT-00:10 | 32193.05 | 12-OCT-04:01 | 28585.28 | 23-OCT-04:01 | 11855.06 | 12-OCT-04:02 | 6922.73 | 04-OCT-04:01 | 0.00 | 01-OCT-00:10 |
November | 0.117684E+11 | 0.292263E+10 | 406.29 | 0.102717E+11 | 0.149676E+10 | 0.00 | 1.00 | 01-NOV-04:01 | 0.00 | 01-NOV-00:10 | 30477.60 | 09-NOV-05:01 | 27547.88 | 13-NOV-05:01 | 5705.94 | 18-NOV-05:02 | 6476.69 | 09-NOV-05:01 | 0.00 | 01-NOV-00:10 |
December | 0.410567E+10 | 0.105642E+10 | 291.95 | 0.353477E+10 | 0.570906E+09 | 0.00 | 0.70 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 | 9121.47 | 01-DEC-15:30 | 8600.87 | 01-DEC-15:10 | 1371.05 | 16-DEC-15:30 | 2210.19 | 01-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.208152E+12 | 0.541474E+11 | 4992.61 | 0.159372E+12 | 0.487798E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.248481E+10 | 0.648638E+09 | 219.30 | 0.217822E+10 | 0.306586E+09 | 0.00 | 0.61 | 0.00 | 7902.24 | 7126.45 | 1279.51 | 1972.12 | 0.00 | |||||||
Maximum of Months | 0.294501E+11 | 0.749287E+10 | 501.92 | 0.210855E+11 | 0.104562E+11 | 0.00 | 1.00 | 0.00 | 34335.21 | 29977.53 | 17452.78 | 7785.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.94 | 18.55 | 16.39 | 46.23 | 51.20 | 6.83 | 0.00 | 744.00 |
February | 44.68 | 25.03 | 19.65 | 66.80 | 43.11 | 0.00 | 0.00 | 672.00 |
March | 59.23 | 35.24 | 23.99 | 99.71 | 31.53 | 0.00 | 0.00 | 744.00 |
April | 77.11 | 54.03 | 23.08 | 143.98 | 20.03 | 0.00 | 0.00 | 720.00 |
May | 81.40 | 56.22 | 25.18 | 158.83 | 11.05 | 0.00 | 0.00 | 744.00 |
June | 76.29 | 48.54 | 27.75 | 151.96 | 6.94 | 0.00 | 0.00 | 720.00 |
July | 53.36 | 19.11 | 34.25 | 107.33 | 4.48 | 0.00 | 0.00 | 744.00 |
August | 45.98 | 13.00 | 32.98 | 91.38 | 6.42 | 0.00 | 0.00 | 744.00 |
September | 47.77 | 20.44 | 27.33 | 88.54 | 12.22 | 0.00 | 0.00 | 720.00 |
October | 52.98 | 33.55 | 19.43 | 93.86 | 28.86 | 0.00 | 0.00 | 744.00 |
November | 44.36 | 29.22 | 15.15 | 69.53 | 43.23 | 0.00 | 0.00 | 720.00 |
December | 33.98 | 18.22 | 15.76 | 45.34 | 52.46 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.34 | 30.90 | 23.44 | 97.02 | 25.88 | 6.83 | 0.00 | 8760.00 |
Minimum of Months | 33.98 | 13.00 | 15.15 | 45.34 | 4.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 81.40 | 56.22 | 34.25 | 158.83 | 52.46 | 6.83 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 904.59 | 549.75 | 354.85 | 1214.55 | 755.90 | 0.00 | 0.00 | 744.00 |
February | 860.00 | 477.70 | 382.29 | 1219.80 | 634.62 | 0.00 | 0.00 | 672.00 |
March | 735.08 | 324.58 | 410.49 | 1136.61 | 431.31 | 0.00 | 0.00 | 744.00 |
April | 516.20 | 145.52 | 370.68 | 977.77 | 208.64 | 0.00 | 0.00 | 720.00 |
May | 371.16 | 27.27 | 343.90 | 950.94 | 74.09 | 0.00 | 0.00 | 744.00 |
June | 339.62 | 5.69 | 333.93 | 969.79 | 38.97 | 0.00 | 0.00 | 720.00 |
July | 354.31 | 4.82 | 349.49 | 900.29 | 24.83 | 0.00 | 0.00 | 744.00 |
August | 375.85 | 20.02 | 355.83 | 843.46 | 57.94 | 0.00 | 0.00 | 744.00 |
September | 503.84 | 130.71 | 373.14 | 961.87 | 129.34 | 0.00 | 0.00 | 720.00 |
October | 866.93 | 484.08 | 382.86 | 1495.27 | 388.01 | 0.00 | 0.00 | 744.00 |
November | 1083.19 | 716.07 | 367.12 | 1700.65 | 624.65 | 0.00 | 0.00 | 720.00 |
December | 966.72 | 605.87 | 360.84 | 1352.26 | 767.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 655.29 | 289.93 | 365.36 | 1142.88 | 343.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 339.62 | 4.82 | 333.93 | 843.46 | 24.83 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1083.19 | 716.07 | 410.49 | 1700.65 | 767.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 904.59 | 549.75 | 354.85 | 1220.15 | 729.83 | 0.00 | 0.00 | 744.00 |
February | 860.00 | 477.70 | 382.29 | 1221.51 | 613.59 | 0.00 | 0.00 | 672.00 |
March | 735.08 | 324.58 | 410.49 | 1132.78 | 415.00 | 0.00 | 0.00 | 744.00 |
April | 516.20 | 145.52 | 370.68 | 972.80 | 195.54 | 0.00 | 0.00 | 720.00 |
May | 371.16 | 27.27 | 343.90 | 948.15 | 66.25 | 0.00 | 0.00 | 744.00 |
June | 339.62 | 5.69 | 333.93 | 970.91 | 32.73 | 0.00 | 0.00 | 720.00 |
July | 354.31 | 4.82 | 349.49 | 900.27 | 19.60 | 0.00 | 0.00 | 744.00 |
August | 375.85 | 20.02 | 355.83 | 840.41 | 49.18 | 0.00 | 0.00 | 744.00 |
September | 503.84 | 130.71 | 373.14 | 958.74 | 117.37 | 0.00 | 0.00 | 720.00 |
October | 866.93 | 484.08 | 382.86 | 1490.26 | 375.18 | 0.00 | 0.00 | 744.00 |
November | 1083.19 | 716.07 | 367.12 | 1697.63 | 609.18 | 0.00 | 0.00 | 720.00 |
December | 966.72 | 605.87 | 360.84 | 1355.99 | 745.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 655.29 | 289.93 | 365.36 | 1141.73 | 329.46 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 339.62 | 4.82 | 333.93 | 840.41 | 19.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1083.19 | 716.07 | 410.49 | 1697.63 | 745.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 186.13 | 113.12 | 73.01 | 263.14 | 133.40 | 0.00 | 0.00 | 744.00 |
February | 176.96 | 98.29 | 78.66 | 252.82 | 119.40 | 0.00 | 0.00 | 672.00 |
March | 151.25 | 66.79 | 84.47 | 217.78 | 91.06 | 0.00 | 0.00 | 744.00 |
April | 106.22 | 29.94 | 76.27 | 154.79 | 54.57 | 0.00 | 0.00 | 720.00 |
May | 76.37 | 5.61 | 70.76 | 124.54 | 27.79 | 0.00 | 0.00 | 744.00 |
June | 69.88 | 1.17 | 68.71 | 125.92 | 17.23 | 0.00 | 0.00 | 720.00 |
July | 72.90 | 0.99 | 71.91 | 125.95 | 12.20 | 4.17 | 0.00 | 744.00 |
August | 77.34 | 4.12 | 73.22 | 126.83 | 21.78 | 0.00 | 0.00 | 744.00 |
September | 103.67 | 26.89 | 76.78 | 158.03 | 39.13 | 9.83 | 0.00 | 720.00 |
October | 178.38 | 99.61 | 78.78 | 275.77 | 94.02 | 0.00 | 0.00 | 744.00 |
November | 222.88 | 147.34 | 75.54 | 335.64 | 129.77 | 0.00 | 0.00 | 720.00 |
December | 198.92 | 124.67 | 74.25 | 287.10 | 138.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 134.83 | 59.66 | 75.18 | 203.74 | 73.04 | 14.00 | 0.00 | 8760.00 |
Minimum of Months | 69.88 | 0.99 | 68.71 | 124.54 | 12.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 222.88 | 147.34 | 84.47 | 335.64 | 138.92 | 9.83 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C1
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C2
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C3
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R4C4
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C1
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C2
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C4
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R1C3
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C2
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C1
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C3
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R2C4
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C2
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C1
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C3
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHTS_R3C4
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 93582936.94 | 49689037.46 | 43893899.49 | 0.123818E+09 | 0.137124E+09 |
February | 0.108080E+09 | 60550051.79 | 47530230.69 | 0.161605E+09 | 0.104300E+09 |
March | 0.158635E+09 | 94390499.11 | 64244233.74 | 0.267053E+09 | 84443628.90 |
April | 0.199857E+09 | 0.140038E+09 | 59819144.85 | 0.373207E+09 | 51918763.15 |
May | 0.218029E+09 | 0.150582E+09 | 67446560.97 | 0.425416E+09 | 29604919.17 |
June | 0.197748E+09 | 0.125826E+09 | 71921288.58 | 0.393873E+09 | 17992157.78 |
July | 0.142918E+09 | 51184815.09 | 91732896.76 | 0.287472E+09 | 11997619.31 |
August | 0.123150E+09 | 34823934.76 | 88325722.26 | 0.244759E+09 | 17203656.56 |
September | 0.123819E+09 | 52975643.02 | 70843689.79 | 0.229503E+09 | 31662471.15 |
October | 0.141900E+09 | 89855506.29 | 52044900.79 | 0.251398E+09 | 77305995.44 |
November | 0.114994E+09 | 75729886.41 | 39263778.98 | 0.180216E+09 | 0.112054E+09 |
December | 91019776.13 | 48804775.96 | 42215000.17 | 0.121438E+09 | 0.140508E+09 |
Annual Sum or Average | 0.171373E+10 | 0.974450E+09 | 0.739281E+09 | 0.305976E+10 | 0.816116E+09 |
Minimum of Months | 91019776.13 | 34823934.76 | 39263778.98 | 0.121438E+09 | 11997619.31 |
Maximum of Months | 0.218029E+09 | 0.150582E+09 | 91732896.76 | 0.425416E+09 | 0.140508E+09 |
Report: WindowEnergyReportMonthly
For: POINT_OF_SALE_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.325304E+10 | 0.202460E+10 |
February | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.295095E+10 | 0.153528E+10 |
March | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.304431E+10 | 0.115521E+10 |
April | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.253439E+10 | 0.540794E+09 |
May | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.254699E+10 | 0.198448E+09 |
June | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.251369E+10 | 0.101020E+09 |
July | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.241134E+10 | 66499222.84 |
August | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.225911E+10 | 0.155174E+09 |
September | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.249316E+10 | 0.335244E+09 |
October | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.400494E+10 | 0.103924E+10 |
November | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.440808E+10 | 0.161910E+10 |
December | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.362190E+10 | 0.205453E+10 |
Annual Sum or Average | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.360419E+11 | 0.108251E+11 |
Minimum of Months | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.225911E+10 | 66499222.84 |
Maximum of Months | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.440808E+10 | 0.205453E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_RETAIL_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.326805E+10 | 0.195477E+10 |
February | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.295507E+10 | 0.148440E+10 |
March | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.303403E+10 | 0.111154E+10 |
April | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.252150E+10 | 0.506829E+09 |
May | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.253953E+10 | 0.177449E+09 |
June | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.251660E+10 | 84845130.37 |
July | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.241127E+10 | 52498986.58 |
August | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.225096E+10 | 0.131733E+09 |
September | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.248505E+10 | 0.304225E+09 |
October | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.399153E+10 | 0.100490E+10 |
November | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.440026E+10 | 0.157899E+10 |
December | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.363188E+10 | 0.199765E+10 |
Annual Sum or Average | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.360057E+11 | 0.103898E+11 |
Minimum of Months | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.225096E+10 | 52498986.58 |
Maximum of Months | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.440026E+10 | 0.199765E+10 |
Report: WindowEnergyReportMonthly
For: FRONT_ENTRY_WALL_SOUTH_GLAZING
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.498540E+09 | 0.302977E+09 | 0.195563E+09 | 0.704804E+09 | 0.357308E+09 |
February | 0.428095E+09 | 0.237795E+09 | 0.190300E+09 | 0.611632E+09 | 0.288845E+09 |
March | 0.405114E+09 | 0.178883E+09 | 0.226232E+09 | 0.583315E+09 | 0.243906E+09 |
April | 0.275312E+09 | 77610020.26 | 0.197702E+09 | 0.401214E+09 | 0.141440E+09 |
May | 0.204555E+09 | 15027040.58 | 0.189528E+09 | 0.333561E+09 | 74432954.61 |
June | 0.181132E+09 | 3034933.40 | 0.178097E+09 | 0.326387E+09 | 44671260.49 |
July | 0.195266E+09 | 2654389.84 | 0.192612E+09 | 0.337354E+09 | 32689529.47 |
August | 0.207136E+09 | 11031363.02 | 0.196105E+09 | 0.339693E+09 | 58340096.06 |
September | 0.268720E+09 | 69711043.12 | 0.199009E+09 | 0.409612E+09 | 0.101420E+09 |
October | 0.477784E+09 | 0.266784E+09 | 0.210999E+09 | 0.738621E+09 | 0.251829E+09 |
November | 0.577710E+09 | 0.381909E+09 | 0.195801E+09 | 0.869987E+09 | 0.336356E+09 |
December | 0.532776E+09 | 0.333908E+09 | 0.198869E+09 | 0.768969E+09 | 0.372095E+09 |
Annual Sum or Average | 0.425214E+10 | 0.188132E+10 | 0.237082E+10 | 0.642515E+10 | 0.230333E+10 |
Minimum of Months | 0.181132E+09 | 2654389.84 | 0.178097E+09 | 0.326387E+09 | 32689529.47 |
Maximum of Months | 0.577710E+09 | 0.381909E+09 | 0.226232E+09 | 0.869987E+09 | 0.372095E+09 |
Report: WindowZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 739.65 | 819.14 | 559.04 | 296.83 | 262.21 | 0.00 | 0.00 |
February | 1068.82 | 689.82 | 714.82 | 400.46 | 314.35 | 0.00 | 0.00 |
March | 1595.30 | 504.44 | 947.64 | 563.86 | 383.78 | 0.00 | 0.00 |
April | 2303.75 | 320.49 | 1233.68 | 864.43 | 369.25 | 0.00 | 0.00 |
May | 2541.31 | 176.85 | 1302.44 | 899.54 | 402.91 | 0.00 | 0.00 |
June | 2431.31 | 111.06 | 1220.66 | 776.71 | 443.96 | 0.00 | 0.00 |
July | 1717.28 | 71.67 | 853.75 | 305.76 | 547.99 | 0.00 | 0.00 |
August | 1462.12 | 102.77 | 735.66 | 208.03 | 527.63 | 0.00 | 0.00 |
September | 1416.68 | 195.45 | 764.32 | 327.01 | 437.31 | 0.00 | 0.00 |
October | 1501.78 | 461.80 | 847.67 | 536.77 | 310.90 | 0.00 | 0.00 |
November | 1112.44 | 691.69 | 709.84 | 467.47 | 242.37 | 0.00 | 0.00 |
December | 725.44 | 839.35 | 543.73 | 291.55 | 252.18 | 0.00 | 0.00 |
Annual Sum or Average | 1552.39 | 414.06 | 869.47 | 494.39 | 375.08 | 0.00 | 0.00 |
Minimum of Months | 725.44 | 71.67 | 543.73 | 208.03 | 242.37 | 0.00 | 0.00 |
Maximum of Months | 2541.31 | 839.35 | 1302.44 | 899.54 | 547.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1214.55 | 755.90 | 904.59 | 549.75 | 354.85 | 0.00 | 0.00 |
February | 1219.80 | 634.62 | 860.00 | 477.70 | 382.29 | 0.00 | 0.00 |
March | 1136.61 | 431.31 | 735.08 | 324.58 | 410.49 | 0.00 | 0.00 |
April | 977.77 | 208.64 | 516.20 | 145.52 | 370.68 | 0.00 | 0.00 |
May | 950.94 | 74.09 | 371.16 | 27.27 | 343.90 | 0.00 | 0.00 |
June | 969.79 | 38.97 | 339.62 | 5.69 | 333.93 | 0.00 | 0.00 |
July | 900.29 | 24.83 | 354.31 | 4.82 | 349.49 | 0.00 | 0.00 |
August | 843.46 | 57.94 | 375.85 | 20.02 | 355.83 | 0.00 | 0.00 |
September | 961.87 | 129.34 | 503.84 | 130.71 | 373.14 | 0.00 | 0.00 |
October | 1495.27 | 388.01 | 866.93 | 484.08 | 382.86 | 0.00 | 0.00 |
November | 1700.65 | 624.65 | 1083.19 | 716.07 | 367.12 | 0.00 | 0.00 |
December | 1352.26 | 767.07 | 966.72 | 605.87 | 360.84 | 0.00 | 0.00 |
Annual Sum or Average | 1142.88 | 343.26 | 655.29 | 289.93 | 365.36 | 0.00 | 0.00 |
Minimum of Months | 843.46 | 24.83 | 339.62 | 4.82 | 333.93 | 0.00 | 0.00 |
Maximum of Months | 1700.65 | 767.07 | 1083.19 | 716.07 | 410.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1220.15 | 729.83 | 904.59 | 549.75 | 354.85 | 0.00 | 0.00 |
February | 1221.51 | 613.59 | 860.00 | 477.70 | 382.29 | 0.00 | 0.00 |
March | 1132.78 | 415.00 | 735.08 | 324.58 | 410.49 | 0.00 | 0.00 |
April | 972.80 | 195.54 | 516.20 | 145.52 | 370.68 | 0.00 | 0.00 |
May | 948.15 | 66.25 | 371.16 | 27.27 | 343.90 | 0.00 | 0.00 |
June | 970.91 | 32.73 | 339.62 | 5.69 | 333.93 | 0.00 | 0.00 |
July | 900.27 | 19.60 | 354.31 | 4.82 | 349.49 | 0.00 | 0.00 |
August | 840.41 | 49.18 | 375.85 | 20.02 | 355.83 | 0.00 | 0.00 |
September | 958.74 | 117.37 | 503.84 | 130.71 | 373.14 | 0.00 | 0.00 |
October | 1490.26 | 375.18 | 866.93 | 484.08 | 382.86 | 0.00 | 0.00 |
November | 1697.63 | 609.18 | 1083.19 | 716.07 | 367.12 | 0.00 | 0.00 |
December | 1355.99 | 745.84 | 966.72 | 605.87 | 360.84 | 0.00 | 0.00 |
Annual Sum or Average | 1141.73 | 329.46 | 655.29 | 289.93 | 365.36 | 0.00 | 0.00 |
Minimum of Months | 840.41 | 19.60 | 339.62 | 4.82 | 333.93 | 0.00 | 0.00 |
Maximum of Months | 1697.63 | 745.84 | 1083.19 | 716.07 | 410.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 263.14 | 133.40 | 186.13 | 113.12 | 73.01 | 0.00 | 0.00 |
February | 252.82 | 119.40 | 176.96 | 98.29 | 78.66 | 0.00 | 0.00 |
March | 217.78 | 91.06 | 151.25 | 66.79 | 84.47 | 0.00 | 0.00 |
April | 154.79 | 54.57 | 106.22 | 29.94 | 76.27 | 0.00 | 0.00 |
May | 124.54 | 27.79 | 76.37 | 5.61 | 70.76 | 0.00 | 0.00 |
June | 125.92 | 17.23 | 69.88 | 1.17 | 68.71 | 0.00 | 0.00 |
July | 125.95 | 12.20 | 72.90 | 0.99 | 71.91 | 0.00 | 0.00 |
August | 126.83 | 21.78 | 77.34 | 4.12 | 73.22 | 0.00 | 0.00 |
September | 158.03 | 39.13 | 103.67 | 26.89 | 76.78 | 0.00 | 0.00 |
October | 275.77 | 94.02 | 178.38 | 99.61 | 78.78 | 0.00 | 0.00 |
November | 335.64 | 129.77 | 222.88 | 147.34 | 75.54 | 0.00 | 0.00 |
December | 287.10 | 138.92 | 198.92 | 124.67 | 74.25 | 0.00 | 0.00 |
Annual Sum or Average | 203.74 | 73.04 | 134.83 | 59.66 | 75.18 | 0.00 | 0.00 |
Minimum of Months | 124.54 | 12.20 | 69.88 | 0.99 | 68.71 | 0.00 | 0.00 |
Maximum of Months | 335.64 | 138.92 | 222.88 | 147.34 | 84.47 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.198109E+10 | 0.219399E+10 | 0.149733E+10 | 0.795025E+09 | 0.702302E+09 | 0.00 | 0.00 |
February | 0.258569E+10 | 0.166881E+10 | 0.172928E+10 | 0.968801E+09 | 0.760484E+09 | 0.00 | 0.00 |
March | 0.427284E+10 | 0.135110E+10 | 0.253816E+10 | 0.151025E+10 | 0.102791E+10 | 0.00 | 0.00 |
April | 0.597131E+10 | 0.830700E+09 | 0.319771E+10 | 0.224060E+10 | 0.957106E+09 | 0.00 | 0.00 |
May | 0.680665E+10 | 0.473679E+09 | 0.348846E+10 | 0.240932E+10 | 0.107914E+10 | 0.00 | 0.00 |
June | 0.630197E+10 | 0.287875E+09 | 0.316396E+10 | 0.201322E+10 | 0.115074E+10 | 0.00 | 0.00 |
July | 0.459955E+10 | 0.191962E+09 | 0.228668E+10 | 0.818957E+09 | 0.146773E+10 | 0.00 | 0.00 |
August | 0.391614E+10 | 0.275259E+09 | 0.197039E+10 | 0.557183E+09 | 0.141321E+10 | 0.00 | 0.00 |
September | 0.367205E+10 | 0.506600E+09 | 0.198111E+10 | 0.847610E+09 | 0.113350E+10 | 0.00 | 0.00 |
October | 0.402237E+10 | 0.123690E+10 | 0.227041E+10 | 0.143769E+10 | 0.832718E+09 | 0.00 | 0.00 |
November | 0.288345E+10 | 0.179287E+10 | 0.183990E+10 | 0.121168E+10 | 0.628220E+09 | 0.00 | 0.00 |
December | 0.194301E+10 | 0.224812E+10 | 0.145632E+10 | 0.780876E+09 | 0.675440E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.489561E+11 | 0.130579E+11 | 0.274197E+11 | 0.155912E+11 | 0.118285E+11 | 0.00 | 0.00 |
Minimum of Months | 0.194301E+10 | 0.191962E+09 | 0.145632E+10 | 0.557183E+09 | 0.628220E+09 | 0.00 | 0.00 |
Maximum of Months | 0.680665E+10 | 0.224812E+10 | 0.348846E+10 | 0.240932E+10 | 0.146773E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.325304E+10 | 0.202460E+10 | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.00 | 0.00 |
February | 0.295095E+10 | 0.153528E+10 | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.00 | 0.00 |
March | 0.304431E+10 | 0.115521E+10 | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.00 | 0.00 |
April | 0.253439E+10 | 0.540794E+09 | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.00 | 0.00 |
May | 0.254699E+10 | 0.198448E+09 | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.00 | 0.00 |
June | 0.251369E+10 | 0.101020E+09 | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.00 | 0.00 |
July | 0.241134E+10 | 66499222.84 | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.00 | 0.00 |
August | 0.225911E+10 | 0.155174E+09 | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.00 | 0.00 |
September | 0.249316E+10 | 0.335244E+09 | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.00 | 0.00 |
October | 0.400494E+10 | 0.103924E+10 | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.00 | 0.00 |
November | 0.440808E+10 | 0.161910E+10 | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.00 | 0.00 |
December | 0.362190E+10 | 0.205453E+10 | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.360419E+11 | 0.108251E+11 | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225911E+10 | 66499222.84 | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.00 | 0.00 |
Maximum of Months | 0.440808E+10 | 0.205453E+10 | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.326805E+10 | 0.195477E+10 | 0.242287E+10 | 0.147244E+10 | 0.950422E+09 | 0.00 | 0.00 |
February | 0.295507E+10 | 0.148440E+10 | 0.208051E+10 | 0.115566E+10 | 0.924844E+09 | 0.00 | 0.00 |
March | 0.303403E+10 | 0.111154E+10 | 0.196882E+10 | 0.869357E+09 | 0.109947E+10 | 0.00 | 0.00 |
April | 0.252150E+10 | 0.506829E+09 | 0.133799E+10 | 0.377179E+09 | 0.960814E+09 | 0.00 | 0.00 |
May | 0.253953E+10 | 0.177449E+09 | 0.994120E+09 | 73030265.73 | 0.921090E+09 | 0.00 | 0.00 |
June | 0.251660E+10 | 84845130.37 | 0.880289E+09 | 14749543.78 | 0.865540E+09 | 0.00 | 0.00 |
July | 0.241127E+10 | 52498986.58 | 0.948978E+09 | 12900131.21 | 0.936077E+09 | 0.00 | 0.00 |
August | 0.225096E+10 | 0.131733E+09 | 0.100667E+10 | 53611578.95 | 0.953056E+09 | 0.00 | 0.00 |
September | 0.248505E+10 | 0.304225E+09 | 0.130596E+10 | 0.338790E+09 | 0.967169E+09 | 0.00 | 0.00 |
October | 0.399153E+10 | 0.100490E+10 | 0.232199E+10 | 0.129655E+10 | 0.102544E+10 | 0.00 | 0.00 |
November | 0.440026E+10 | 0.157899E+10 | 0.280763E+10 | 0.185605E+10 | 0.951577E+09 | 0.00 | 0.00 |
December | 0.363188E+10 | 0.199765E+10 | 0.258925E+10 | 0.162277E+10 | 0.966486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.360057E+11 | 0.103898E+11 | 0.206651E+11 | 0.914309E+10 | 0.115220E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225096E+10 | 52498986.58 | 0.880289E+09 | 12900131.21 | 0.865540E+09 | 0.00 | 0.00 |
Maximum of Months | 0.440026E+10 | 0.199765E+10 | 0.280763E+10 | 0.185605E+10 | 0.109947E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.704804E+09 | 0.357308E+09 | 0.498540E+09 | 0.302977E+09 | 0.195563E+09 | 0.00 | 0.00 |
February | 0.611632E+09 | 0.288845E+09 | 0.428095E+09 | 0.237795E+09 | 0.190300E+09 | 0.00 | 0.00 |
March | 0.583315E+09 | 0.243906E+09 | 0.405114E+09 | 0.178883E+09 | 0.226232E+09 | 0.00 | 0.00 |
April | 0.401214E+09 | 0.141440E+09 | 0.275312E+09 | 77610020.26 | 0.197702E+09 | 0.00 | 0.00 |
May | 0.333561E+09 | 74432954.61 | 0.204555E+09 | 15027040.58 | 0.189528E+09 | 0.00 | 0.00 |
June | 0.326387E+09 | 44671260.49 | 0.181132E+09 | 3034933.40 | 0.178097E+09 | 0.00 | 0.00 |
July | 0.337354E+09 | 32689529.47 | 0.195266E+09 | 2654389.84 | 0.192612E+09 | 0.00 | 0.00 |
August | 0.339693E+09 | 58340096.06 | 0.207136E+09 | 11031363.02 | 0.196105E+09 | 0.00 | 0.00 |
September | 0.409612E+09 | 0.101420E+09 | 0.268720E+09 | 69711043.12 | 0.199009E+09 | 0.00 | 0.00 |
October | 0.738621E+09 | 0.251829E+09 | 0.477784E+09 | 0.266784E+09 | 0.210999E+09 | 0.00 | 0.00 |
November | 0.869987E+09 | 0.336356E+09 | 0.577710E+09 | 0.381909E+09 | 0.195801E+09 | 0.00 | 0.00 |
December | 0.768969E+09 | 0.372095E+09 | 0.532776E+09 | 0.333908E+09 | 0.198869E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.642515E+10 | 0.230333E+10 | 0.425214E+10 | 0.188132E+10 | 0.237082E+10 | 0.00 | 0.00 |
Minimum of Months | 0.326387E+09 | 32689529.47 | 0.181132E+09 | 2654389.84 | 0.178097E+09 | 0.00 | 0.00 |
Maximum of Months | 0.869987E+09 | 0.372095E+09 | 0.577710E+09 | 0.381909E+09 | 0.226232E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.37 | 7.87 | 1.20 | 0.37 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.77 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.59 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.31 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.95 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.37 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.28 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.69 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.73 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.45 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.87 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.75 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.37 | 7.87 | 0.66 | 0.37 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.18 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.17 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.47 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.63 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.60 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.49 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.34 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.56 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.67 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.02 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.14 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.28 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.18 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.67 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.55 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.57 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.73 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.61 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.36 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.40 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.17 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.16 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.05 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.91 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.61 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.17 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.47 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.24 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.03 | 0.00 | 15.60 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.69 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.40 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.58 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.47 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.221701E+10 | -.180388E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -413124249.1 | 58.99 | 0.00 | 0.00 |
February | 0.196739E+10 | -.160754E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -359847973.1 | 58.99 | 0.00 | 0.00 |
March | 0.208555E+10 | -.170245E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -383096353.1 | 58.99 | 0.00 | 0.00 |
April | 0.181300E+10 | -.145243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -360570621.1 | 58.99 | 0.00 | 0.00 |
May | 0.169401E+10 | -.132694E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -367074669.0 | 58.99 | 0.00 | 0.00 |
June | 0.152420E+10 | -.116832E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -355883246.6 | 58.99 | 0.00 | 0.00 |
July | 0.148475E+10 | -.111752E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -367225800.9 | 58.99 | 0.00 | 0.00 |
August | 0.156295E+10 | -.119402E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -368924312.9 | 58.99 | 0.00 | 0.00 |
September | 0.161594E+10 | -.125596E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -359979695.7 | 58.99 | 0.00 | 0.00 |
October | 0.182541E+10 | -.144866E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -376747359.9 | 58.99 | 0.00 | 0.00 |
November | 0.193762E+10 | -.156205E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -375573416.4 | 58.99 | 0.00 | 0.00 |
December | 0.215968E+10 | -.175316E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -406523806.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.218875E+11 | -.173929E+11 | 8760.00 | -.449457E+10 | 58.99 | |||||
Minimum of Months | 0.148475E+10 | -.180388E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -413124249.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.221701E+10 | -.111752E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -355883246.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.90 | 0.67 | 14-JAN-11:39 | 214.19 | 5.63 | 0.00 | 0.00 | 176.46 | 4.24 | 0.00 | 0.00 |
February | 303.83 | 0.86 | 0.67 | 01-FEB-10:00 | 255.59 | 6.46 | 0.00 | 0.00 | 211.55 | 4.98 | 0.00 | 0.00 |
March | 364.50 | 0.80 | 0.50 | 02-MAR-11:09 | 1665.61 | 7.54 | 0.00 | 62.33 | 1790.31 | 5.98 | 0.00 | 55.17 |
April | 379.83 | 0.84 | 0.50 | 02-APR-11:30 | 279.74 | 7.87 | 0.00 | 7.50 | 232.34 | 6.25 | 0.00 | 5.00 |
May | 406.00 | 0.84 | 0.50 | 12-MAY-11:30 | 281.29 | 9.09 | 0.00 | 13.17 | 233.95 | 7.39 | 0.00 | 8.50 |
June | 386.67 | 0.82 | 0.50 | 01-JUN-10:00 | 301.78 | 9.90 | 0.00 | 24.33 | 250.20 | 8.14 | 0.00 | 14.00 |
July | 379.83 | 0.78 | 0.50 | 05-JUL-11:30 | 352.27 | 10.72 | 0.00 | 70.67 | 297.11 | 9.10 | 0.00 | 39.00 |
August | 372.50 | 0.77 | 0.50 | 01-AUG-10:39 | 396.24 | 10.10 | 0.00 | 91.33 | 345.62 | 8.53 | 0.00 | 53.33 |
September | 344.33 | 0.78 | 0.50 | 01-SEP-10:39 | 922.57 | 8.93 | 0.00 | 72.50 | 916.05 | 7.34 | 0.00 | 48.83 |
October | 347.33 | 0.85 | 0.50 | 06-OCT-11:20 | 268.37 | 6.63 | 0.00 | 4.33 | 222.88 | 5.17 | 0.00 | 2.00 |
November | 317.83 | 0.90 | 0.75 | 28-NOV-10:50 | 213.90 | 5.34 | 0.00 | 0.00 | 177.04 | 3.93 | 0.00 | 0.00 |
December | 315.50 | 0.90 | 0.75 | 08-DEC-11:39 | 208.78 | 5.46 | 0.00 | 0.00 | 171.63 | 4.05 | 0.00 | 0.00 |
Annual Sum or Average | 4237.50 | 0.83 | 452.26 | 7.94 | 0.00 | 346.17 | 424.31 | 6.38 | 0.00 | 225.83 | ||
Minimum of Months | 303.83 | 0.77 | 0.50 | 208.78 | 5.34 | 0.00 | 0.00 | 171.63 | 3.93 | 0.00 | 0.00 | |
Maximum of Months | 406.00 | 0.90 | 0.75 | 1665.61 | 10.72 | 0.00 | 91.33 | 1790.31 | 9.10 | 0.00 | 55.17 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.309523E+10 | 71349.24 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.577553E+09 | 71349.24 | 11-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4527828.63 | 1435.41 | 27-NOV-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130262E+10 | 71349.24 | 22-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497993E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309523E+10 | 71349.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.374999E+10 | 231256.19 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316210E+09 | 160103.38 | 02-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.588054E+09 | 172492.01 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.465426E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.374999E+10 | 231256.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.298021E+09 | 37969.94 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44463106.29 | 18405.50 | 11-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39725262.87 | 2709.45 | 23-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382209E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.298021E+09 | 37969.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_HEATCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.635143E+09 | 33635.78 | 01-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122009E+09 | 33635.78 | 11-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119214E+09 | 17444.64 | 31-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876366E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.635143E+09 | 33635.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONT_ENTRY UNIT HEATER COIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5638561.61 | 2494.51 | 03-JAN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2605040.80 | 1357.28 | 21-DEC-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8243602.41 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5638561.61 | 2494.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:1_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.257341E+09 | 0.194822E+09 | 5612.96 | 14-JAN-16:20 | 4084.06 | 0.00 |
February | 0.00 | 0.00 | 0.345950E+10 | 0.277951E+10 | 12150.08 | 24-FEB-16:00 | 9711.33 | 0.00 |
March | 0.00 | 0.00 | 0.154183E+11 | 0.130076E+11 | 64561.29 | 11-MAR-05:01 | 50400.09 | 0.00 |
April | 0.00 | 0.00 | 0.318483E+11 | 0.286713E+11 | 64737.31 | 17-APR-04:01 | 57430.22 | 0.00 |
May | 0.00 | 0.00 | 0.489574E+11 | 0.419354E+11 | 68208.58 | 24-MAY-04:01 | 45451.01 | 0.00 |
June | 0.00 | 0.00 | 0.526736E+11 | 0.423966E+11 | 70064.31 | 26-JUN-04:01 | 39720.95 | 0.00 |
July | 0.00 | 0.00 | 0.559402E+11 | 0.405696E+11 | 70343.62 | 20-JUL-04:01 | 39467.09 | 0.00 |
August | 0.00 | 0.00 | 0.528551E+11 | 0.370151E+11 | 68716.03 | 19-AUG-04:01 | 44723.78 | 0.00 |
September | 0.00 | 0.00 | 0.412871E+11 | 0.294560E+11 | 69375.23 | 03-SEP-06:01 | 42090.98 | 0.00 |
October | 0.00 | 0.00 | 0.259930E+11 | 0.212544E+11 | 66152.66 | 12-OCT-04:01 | 45161.48 | 0.00 |
November | 0.00 | 0.00 | 0.947166E+10 | 0.780583E+10 | 62771.17 | 01-NOV-04:01 | 51025.85 | 0.00 |
December | 0.00 | 0.00 | 0.835681E+09 | 0.653367E+09 | 5878.83 | 28-DEC-16:00 | 4659.10 | 0.00 |
Annual Sum or Average | 0.338997E+12 | 0.265739E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.257341E+09 | 0.194822E+09 | 5612.96 | 4084.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.559402E+11 | 0.423966E+11 | 70343.62 | 57430.22 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:2_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.737716E+10 | 0.599223E+10 | 35100.59 | 14-JAN-15:20 | 26063.57 | 0.00 |
February | 0.00 | 0.00 | 0.270976E+11 | 0.218353E+11 | 63699.69 | 24-FEB-16:00 | 49856.28 | 0.00 |
March | 0.00 | 0.00 | 0.754281E+11 | 0.617998E+11 | 227396.38 | 11-MAR-07:02 | 170274.73 | 0.00 |
April | 0.00 | 0.00 | 0.126641E+12 | 0.109942E+12 | 231690.67 | 24-APR-06:02 | 158357.25 | 0.00 |
May | 0.00 | 0.00 | 0.182781E+12 | 0.144859E+12 | 238695.65 | 24-MAY-06:02 | 140981.36 | 0.00 |
June | 0.00 | 0.00 | 0.200999E+12 | 0.142409E+12 | 246972.63 | 25-JUN-08:62 | 121862.38 | 0.00 |
July | 0.00 | 0.00 | 0.216563E+12 | 0.128931E+12 | 246894.52 | 19-JUL-06:02 | 121605.22 | 0.00 |
August | 0.00 | 0.00 | 0.213281E+12 | 0.119412E+12 | 248652.64 | 20-AUG-08:62 | 117550.15 | 0.00 |
September | 0.00 | 0.00 | 0.171923E+12 | 0.101742E+12 | 250266.71 | 10-SEP-08:62 | 112551.13 | 0.00 |
October | 0.00 | 0.00 | 0.110581E+12 | 0.839302E+11 | 239002.38 | 12-OCT-06:02 | 134527.43 | 0.00 |
November | 0.00 | 0.00 | 0.548974E+11 | 0.445752E+11 | 76172.49 | 09-NOV-15:10 | 63924.89 | 0.00 |
December | 0.00 | 0.00 | 0.140779E+11 | 0.112925E+11 | 39540.37 | 01-DEC-15:30 | 35071.66 | 0.00 |
Annual Sum or Average | 0.140165E+13 | 0.976720E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.737716E+10 | 0.599223E+10 | 35100.59 | 26063.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216563E+12 | 0.144859E+12 | 250266.71 | 170274.73 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:3_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.458195E+10 | 0.407006E+10 | 10038.93 | 12-JAN-16:00 | 9162.15 | 0.00 |
February | 0.00 | 0.00 | 0.759795E+10 | 0.668022E+10 | 33007.45 | 23-FEB-05:01 | 30365.36 | 0.00 |
March | 0.00 | 0.00 | 0.147403E+11 | 0.129953E+11 | 34769.30 | 11-MAR-05:01 | 28493.67 | 0.00 |
April | 0.00 | 0.00 | 0.213806E+11 | 0.194639E+11 | 35063.59 | 17-APR-04:01 | 30763.33 | 0.00 |
May | 0.00 | 0.00 | 0.285715E+11 | 0.241733E+11 | 36847.99 | 24-MAY-04:01 | 23819.09 | 0.00 |
June | 0.00 | 0.00 | 0.304092E+11 | 0.236991E+11 | 37958.32 | 26-JUN-04:01 | 20732.04 | 0.00 |
July | 0.00 | 0.00 | 0.329362E+11 | 0.226784E+11 | 38085.69 | 20-JUL-04:01 | 20672.89 | 0.00 |
August | 0.00 | 0.00 | 0.323426E+11 | 0.215419E+11 | 37292.25 | 19-AUG-04:01 | 23310.34 | 0.00 |
September | 0.00 | 0.00 | 0.277083E+11 | 0.194552E+11 | 37617.05 | 03-SEP-06:01 | 22058.03 | 0.00 |
October | 0.00 | 0.00 | 0.224487E+11 | 0.189902E+11 | 35654.96 | 12-OCT-04:01 | 24304.46 | 0.00 |
November | 0.00 | 0.00 | 0.146282E+11 | 0.129964E+11 | 33804.75 | 09-NOV-05:01 | 30108.10 | 0.00 |
December | 0.00 | 0.00 | 0.664207E+10 | 0.585502E+10 | 15612.46 | 29-DEC-05:03 | 13552.45 | 0.00 |
Annual Sum or Average | 0.243988E+12 | 0.192599E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.458195E+10 | 0.407006E+10 | 10038.93 | 9162.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.329362E+11 | 0.241733E+11 | 38085.69 | 30763.33 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC:4_UNITARY_PACKAGE_COOLCOIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.248481E+10 | 0.217822E+10 | 7902.24 | 12-JAN-15:40 | 7116.75 | 0.00 |
February | 0.00 | 0.00 | 0.528720E+10 | 0.457933E+10 | 29669.68 | 23-FEB-05:01 | 26236.75 | 0.00 |
March | 0.00 | 0.00 | 0.117444E+11 | 0.101766E+11 | 31303.76 | 11-MAR-05:01 | 24748.58 | 0.00 |
April | 0.00 | 0.00 | 0.184631E+11 | 0.166182E+11 | 31521.25 | 17-APR-04:01 | 26981.50 | 0.00 |
May | 0.00 | 0.00 | 0.253329E+11 | 0.210855E+11 | 33201.34 | 24-MAY-04:01 | 20602.46 | 0.00 |
June | 0.00 | 0.00 | 0.269235E+11 | 0.204571E+11 | 34207.86 | 26-JUN-04:01 | 17688.41 | 0.00 |
July | 0.00 | 0.00 | 0.294501E+11 | 0.195346E+11 | 34335.21 | 20-JUL-04:01 | 17714.56 | 0.00 |
August | 0.00 | 0.00 | 0.288538E+11 | 0.183976E+11 | 33682.02 | 19-AUG-04:01 | 19903.74 | 0.00 |
September | 0.00 | 0.00 | 0.243584E+11 | 0.164636E+11 | 33907.13 | 03-SEP-06:01 | 18950.97 | 0.00 |
October | 0.00 | 0.00 | 0.193792E+11 | 0.160745E+11 | 32193.05 | 12-OCT-04:01 | 20615.28 | 0.00 |
November | 0.00 | 0.00 | 0.117684E+11 | 0.102717E+11 | 30477.60 | 09-NOV-05:01 | 25750.72 | 0.00 |
December | 0.00 | 0.00 | 0.410567E+10 | 0.353477E+10 | 9121.47 | 01-DEC-15:30 | 8529.46 | 0.00 |
Annual Sum or Average | 0.208152E+12 | 0.159372E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.248481E+10 | 0.217822E+10 | 7902.24 | 7116.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.294501E+11 | 0.210855E+11 | 34335.21 | 26981.50 | 0.00 |
Report: FanReportMonthly
For: FRONT_ENTRY UNIT HEATERFAN
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 6121431.04 | 0.00 | 800.19 | 03-JAN-08:05 | 0.93 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 4583928.75 | 0.00 | 800.19 | 21-DEC-08:04 | 0.93 |
Annual Sum or Average | 10705359.80 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6121431.04 | 0.00 | 800.19 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.214505E+10 | 0.35 | 3200.86 | 01-JAN-07:01 | 0.89 |
February | 0.187961E+10 | 0.33 | 3200.86 | 11-FEB-05:02 | 0.89 |
March | 0.210008E+10 | 0.34 | 3200.86 | 10-MAR-05:01 | 0.89 |
April | 0.208811E+10 | 0.35 | 3200.86 | 01-APR-04:01 | 0.89 |
May | 0.248509E+10 | 0.39 | 3200.86 | 01-MAY-04:01 | 0.90 |
June | 0.262992E+10 | 0.42 | 3200.86 | 01-JUN-04:01 | 0.89 |
July | 0.260420E+10 | 0.40 | 3200.86 | 01-JUL-04:01 | 0.89 |
August | 0.242299E+10 | 0.37 | 3200.86 | 01-AUG-04:01 | 0.89 |
September | 0.212930E+10 | 0.35 | 3200.86 | 01-SEP-04:01 | 0.89 |
October | 0.209644E+10 | 0.34 | 3200.86 | 01-OCT-06:01 | 0.89 |
November | 0.197869E+10 | 0.32 | 3200.86 | 01-NOV-04:01 | 0.89 |
December | 0.209502E+10 | 0.34 | 3200.86 | 22-DEC-05:01 | 0.90 |
Annual Sum or Average | 0.266545E+11 | 0.36 | |||
Minimum of Months | 0.187961E+10 | 0.32 | 3200.86 | 0.89 | |
Maximum of Months | 0.262992E+10 | 0.42 | 3200.86 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.968844E+10 | 0.51 | 14893.16 | 01-JAN-08:61 | 1.40 |
February | 0.867647E+10 | 0.51 | 12143.77 | 02-FEB-07:03 | 1.28 |
March | 0.972499E+10 | 0.52 | 14893.16 | 11-MAR-07:02 | 1.39 |
April | 0.970177E+10 | 0.52 | 14893.16 | 01-APR-06:02 | 1.40 |
May | 0.117026E+11 | 0.58 | 14893.16 | 01-MAY-05:01 | 1.40 |
June | 0.124514E+11 | 0.61 | 14893.16 | 01-JUN-05:03 | 1.39 |
July | 0.125664E+11 | 0.59 | 14893.16 | 01-JUL-04:01 | 1.39 |
August | 0.122038E+11 | 0.59 | 14893.16 | 01-AUG-05:02 | 1.38 |
September | 0.102615E+11 | 0.54 | 14893.16 | 01-SEP-05:02 | 1.38 |
October | 0.961838E+10 | 0.51 | 14893.16 | 01-OCT-07:01 | 1.39 |
November | 0.920040E+10 | 0.51 | 5957.27 | 09-NOV-13:50 | 0.85 |
December | 0.958771E+10 | 0.51 | 12622.48 | 23-DEC-07:03 | 1.30 |
Annual Sum or Average | 0.125384E+12 | 0.54 | |||
Minimum of Months | 0.867647E+10 | 0.51 | 5957.27 | 0.85 | |
Maximum of Months | 0.125664E+11 | 0.61 | 14893.16 | 1.40 |
Report: FanReportMonthly
For: PSZ-AC:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107097E+10 | 0.33 | 1658.22 | 01-JAN-07:01 | 0.89 |
February | 0.967940E+09 | 0.33 | 1658.22 | 23-FEB-05:01 | 0.90 |
March | 0.110294E+10 | 0.34 | 1658.22 | 06-MAR-05:02 | 0.89 |
April | 0.115778E+10 | 0.38 | 1658.22 | 01-APR-04:01 | 0.90 |
May | 0.137880E+10 | 0.44 | 1658.22 | 01-MAY-04:01 | 0.90 |
June | 0.143461E+10 | 0.45 | 1658.22 | 01-JUN-04:01 | 0.89 |
July | 0.144897E+10 | 0.43 | 1658.22 | 01-JUL-04:01 | 0.89 |
August | 0.140603E+10 | 0.41 | 1658.22 | 01-AUG-04:01 | 0.88 |
September | 0.126516E+10 | 0.39 | 1658.22 | 01-SEP-04:01 | 0.89 |
October | 0.117151E+10 | 0.36 | 1658.22 | 01-OCT-06:01 | 0.89 |
November | 0.103846E+10 | 0.34 | 1658.22 | 01-NOV-04:01 | 0.89 |
December | 0.106620E+10 | 0.33 | 734.28 | 23-DEC-06:10 | 0.58 |
Annual Sum or Average | 0.145094E+11 | 0.38 | |||
Minimum of Months | 0.967940E+09 | 0.33 | 734.28 | 0.58 | |
Maximum of Months | 0.144897E+10 | 0.45 | 1658.22 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.980889E+09 | 0.34 | 1502.67 | 01-JAN-07:01 | 0.92 |
February | 0.878474E+09 | 0.34 | 1502.67 | 11-FEB-05:02 | 0.92 |
March | 0.994806E+09 | 0.35 | 1502.67 | 07-MAR-05:01 | 0.92 |
April | 0.103926E+10 | 0.38 | 1502.67 | 01-APR-04:01 | 0.93 |
May | 0.123211E+10 | 0.42 | 1502.67 | 01-MAY-04:01 | 0.93 |
June | 0.127401E+10 | 0.44 | 1502.67 | 01-JUN-04:01 | 0.92 |
July | 0.129541E+10 | 0.43 | 1502.67 | 01-JUL-04:01 | 0.92 |
August | 0.125116E+10 | 0.41 | 1502.67 | 01-AUG-04:01 | 0.91 |
September | 0.113135E+10 | 0.39 | 1502.67 | 01-SEP-04:01 | 0.92 |
October | 0.105238E+10 | 0.37 | 1502.67 | 01-OCT-06:01 | 0.92 |
November | 0.937202E+09 | 0.34 | 1502.67 | 01-NOV-04:01 | 0.93 |
December | 0.968299E+09 | 0.34 | 840.78 | 31-DEC-08:62 | 0.69 |
Annual Sum or Average | 0.130354E+11 | 0.38 | |||
Minimum of Months | 0.878474E+09 | 0.34 | 840.78 | 0.69 | |
Maximum of Months | 0.129541E+10 | 0.44 | 1502.67 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 0.00 |
February | 0.56 | 0.00 |
March | 0.11 | 0.00 |
April | 1.03 | 0.00 |
May | 2.66 | 0.00 |
June | 2.30 | 0.00 |
July | 2.22 | 0.00 |
August | 2.63 | 0.00 |
September | 0.79 | 0.00 |
October | 0.37 | 0.00 |
November | 0.00 | 0.00 |
December | 0.33 | 0.00 |
Annual Sum or Average | 13.18 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.66 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.19 | 17.67 |
February | 0.39 | 5.54 |
March | 0.31 | 21.14 |
April | 0.59 | 0.00 |
May | 0.57 | 0.00 |
June | 0.38 | 0.00 |
July | 0.39 | 0.00 |
August | 0.61 | 0.00 |
September | 0.43 | 0.00 |
October | 0.31 | 21.14 |
November | 0.00 | 0.00 |
December | 0.81 | 10.69 |
Annual Sum or Average | 6.96 | 8.97 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.19 | 21.14 |
Report: ZoneTemperatureOscillationReportMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.50 | 0.00 |
February | 1.80 | 0.00 |
March | 2.23 | 0.00 |
April | 2.60 | 0.00 |
May | 2.59 | 0.00 |
June | 2.00 | 0.00 |
July | 2.17 | 0.00 |
August | 2.63 | 0.00 |
September | 2.05 | 0.00 |
October | 1.89 | 0.00 |
November | 1.60 | 0.00 |
December | 1.21 | 0.00 |
Annual Sum or Average | 23.29 | 0.00 |
Minimum of Months | 0.50 | 0.00 |
Maximum of Months | 2.63 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 0.00 |
February | 0.35 | 0.00 |
March | 1.51 | 0.00 |
April | 2.32 | 0.00 |
May | 2.66 | 0.00 |
June | 2.20 | 0.00 |
July | 2.15 | 0.00 |
August | 2.63 | 0.00 |
September | 1.59 | 0.00 |
October | 1.72 | 0.00 |
November | 1.03 | 0.00 |
December | 0.12 | 0.00 |
Annual Sum or Average | 18.39 | 0.00 |
Minimum of Months | 0.08 | 0.00 |
Maximum of Months | 2.66 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 7.23 | 0.00 |
February | 3.94 | 0.00 |
March | 0.50 | 0.00 |
April | 2.83 | 0.00 |
May | 2.85 | 0.00 |
June | 3.00 | 0.00 |
July | 2.44 | 0.00 |
August | 0.83 | 0.00 |
September | 1.08 | 0.00 |
October | 1.19 | 0.00 |
November | 5.38 | 0.00 |
December | 6.58 | 0.00 |
Annual Sum or Average | 37.87 | 0.00 |
Minimum of Months | 0.50 | 0.00 |
Maximum of Months | 7.23 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.221728E+10 | 0.386904E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.284704E+10 | 0.721941E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.641449E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.111992E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.166175E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.176443E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.174109E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.159576E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.128484E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.922425E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.464092E+10 | 5659785.78 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.233137E+10 | 0.162827E+10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.119353E+12 | 0.622491E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.221728E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.176443E+11 | 0.386904E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.119175E+11 | 0.468749E+10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.166950E+11 | 0.395263E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.318837E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.482459E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.679053E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.724294E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.720337E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.687783E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.563089E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.414209E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.253460E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.138131E+11 | 0.735068E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.526778E+12 | 0.581782E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119175E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.724294E+11 | 0.468749E+10 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.224266E+10 | 0.372526E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.287639E+10 | 55578882.86 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.486467E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.699216E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.942465E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.984766E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.988130E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.941407E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.815479E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.680720E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.462493E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.274064E+10 | 49656578.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.778711E+11 | 0.477762E+09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.224266E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.988130E+10 | 0.372526E+09 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.162953E+10 | 0.793928E+09 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.223038E+10 | 0.152512E+09 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.403287E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.610394E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.835263E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.868665E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.878828E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.835097E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.717931E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.594364E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.385983E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.202472E+10 | 0.149018E+09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.671827E+11 | 0.109546E+10 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.162953E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.878828E+10 | 0.793928E+09 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.214505E+10 | 0.257341E+09 | 0.309523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187961E+10 | 0.345950E+10 | 0.577553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210008E+10 | 0.154183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.208811E+10 | 0.318483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248509E+10 | 0.489574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262992E+10 | 0.526736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.260420E+10 | 0.559402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.242299E+10 | 0.528551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212930E+10 | 0.412871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209644E+10 | 0.259930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197869E+10 | 0.947166E+10 | 4527828.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209502E+10 | 0.835681E+09 | 0.130262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266545E+11 | 0.338997E+12 | 0.497993E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.187961E+10 | 0.257341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.262992E+10 | 0.559402E+11 | 0.309523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.968844E+10 | 0.737716E+10 | 0.374999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.867647E+10 | 0.270976E+11 | 0.316210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.972499E+10 | 0.754281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.970177E+10 | 0.126641E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117026E+11 | 0.182781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124514E+11 | 0.200999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125664E+11 | 0.216563E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122038E+11 | 0.213281E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102615E+11 | 0.171923E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.961838E+10 | 0.110581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.920040E+10 | 0.548974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.958771E+10 | 0.140779E+11 | 0.588054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125384E+12 | 0.140165E+13 | 0.465426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.867647E+10 | 0.737716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125664E+11 | 0.216563E+12 | 0.374999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107097E+10 | 0.458195E+10 | 0.298021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.967940E+09 | 0.759795E+10 | 44463106.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110294E+10 | 0.147403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115778E+10 | 0.213806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137880E+10 | 0.285715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143461E+10 | 0.304092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144897E+10 | 0.329362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140603E+10 | 0.323426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126516E+10 | 0.277083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117151E+10 | 0.224487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103846E+10 | 0.146282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106620E+10 | 0.664207E+10 | 39725262.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145094E+11 | 0.243988E+12 | 0.382209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.967940E+09 | 0.458195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144897E+10 | 0.329362E+11 | 0.298021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.980889E+09 | 0.248481E+10 | 0.635143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.878474E+09 | 0.528720E+10 | 0.122009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.994806E+09 | 0.117444E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103926E+10 | 0.184631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123211E+10 | 0.253329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127401E+10 | 0.269235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129541E+10 | 0.294501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125116E+10 | 0.288538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113135E+10 | 0.243584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105238E+10 | 0.193792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.937202E+09 | 0.117684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.968299E+09 | 0.410567E+10 | 0.119214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130354E+11 | 0.208152E+12 | 0.876366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.878474E+09 | 0.248481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129541E+10 | 0.294501E+11 | 0.635143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:1
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.214505E+10 | 0.00 | 0.00 | 0.00 | 72227754.36 | 0.00 | 0.386904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.187961E+10 | 0.00 | 0.00 | 0.00 | 0.967438E+09 | 0.00 | 0.721941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210008E+10 | 0.00 | 0.00 | 0.00 | 0.431441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.208811E+10 | 0.00 | 0.00 | 0.00 | 0.911105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.248509E+10 | 0.00 | 0.00 | 0.00 | 0.141324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262992E+10 | 0.00 | 0.00 | 0.00 | 0.150144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.260420E+10 | 0.00 | 0.00 | 0.00 | 0.148067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.242299E+10 | 0.00 | 0.00 | 0.00 | 0.135346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212930E+10 | 0.00 | 0.00 | 0.00 | 0.107191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209644E+10 | 0.00 | 0.00 | 0.00 | 0.712781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197869E+10 | 0.00 | 0.00 | 0.00 | 0.266223E+10 | 0.00 | 5659785.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209502E+10 | 0.00 | 0.00 | 0.00 | 0.236352E+09 | 0.00 | 0.162827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266545E+11 | 0.00 | 0.00 | 0.00 | 0.926987E+11 | 0.00 | 0.622491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.187961E+10 | 0.00 | 0.00 | 0.00 | 72227754.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.262992E+10 | 0.00 | 0.00 | 0.00 | 0.150144E+11 | 0.00 | 0.386904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:2
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.968844E+10 | 0.00 | 0.00 | 0.00 | 0.222909E+10 | 0.00 | 0.468749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.867647E+10 | 0.00 | 0.00 | 0.00 | 0.801850E+10 | 0.00 | 0.395263E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.972499E+10 | 0.00 | 0.00 | 0.00 | 0.221587E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.970177E+10 | 0.00 | 0.00 | 0.00 | 0.385441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117026E+11 | 0.00 | 0.00 | 0.00 | 0.562027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124514E+11 | 0.00 | 0.00 | 0.00 | 0.599780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125664E+11 | 0.00 | 0.00 | 0.00 | 0.594673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122038E+11 | 0.00 | 0.00 | 0.00 | 0.565744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102615E+11 | 0.00 | 0.00 | 0.00 | 0.460474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.961838E+10 | 0.00 | 0.00 | 0.00 | 0.318026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.920040E+10 | 0.00 | 0.00 | 0.00 | 0.161456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.958771E+10 | 0.00 | 0.00 | 0.00 | 0.422542E+10 | 0.00 | 0.735068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125384E+12 | 0.00 | 0.00 | 0.00 | 0.401394E+12 | 0.00 | 0.581782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.867647E+10 | 0.00 | 0.00 | 0.00 | 0.222909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125664E+11 | 0.00 | 0.00 | 0.00 | 0.599780E+11 | 0.00 | 0.468749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:3
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.107097E+10 | 0.00 | 0.00 | 0.00 | 0.117169E+10 | 0.00 | 0.372526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.967940E+09 | 0.00 | 0.00 | 0.00 | 0.190845E+10 | 0.00 | 55578882.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.110294E+10 | 0.00 | 0.00 | 0.00 | 0.376174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115778E+10 | 0.00 | 0.00 | 0.00 | 0.583438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137880E+10 | 0.00 | 0.00 | 0.00 | 0.804585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143461E+10 | 0.00 | 0.00 | 0.00 | 0.841304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144897E+10 | 0.00 | 0.00 | 0.00 | 0.843233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140603E+10 | 0.00 | 0.00 | 0.00 | 0.800804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126516E+10 | 0.00 | 0.00 | 0.00 | 0.688963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117151E+10 | 0.00 | 0.00 | 0.00 | 0.563569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103846E+10 | 0.00 | 0.00 | 0.00 | 0.358647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106620E+10 | 0.00 | 0.00 | 0.00 | 0.167444E+10 | 0.00 | 49656578.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145094E+11 | 0.00 | 0.00 | 0.00 | 0.633618E+11 | 0.00 | 0.477762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.967940E+09 | 0.00 | 0.00 | 0.00 | 0.117169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144897E+10 | 0.00 | 0.00 | 0.00 | 0.843233E+10 | 0.00 | 0.372526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC:4
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.980889E+09 | 0.00 | 0.00 | 0.00 | 0.648638E+09 | 0.00 | 0.793928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.878474E+09 | 0.00 | 0.00 | 0.00 | 0.135190E+10 | 0.00 | 0.152512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.994806E+09 | 0.00 | 0.00 | 0.00 | 0.303806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103926E+10 | 0.00 | 0.00 | 0.00 | 0.506468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.123211E+10 | 0.00 | 0.00 | 0.00 | 0.712052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127401E+10 | 0.00 | 0.00 | 0.00 | 0.741263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129541E+10 | 0.00 | 0.00 | 0.00 | 0.749287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.125116E+10 | 0.00 | 0.00 | 0.00 | 0.709981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113135E+10 | 0.00 | 0.00 | 0.00 | 0.604796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105238E+10 | 0.00 | 0.00 | 0.00 | 0.489126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.937202E+09 | 0.00 | 0.00 | 0.00 | 0.292263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.968299E+09 | 0.00 | 0.00 | 0.00 | 0.105642E+10 | 0.00 | 0.149018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130354E+11 | 0.00 | 0.00 | 0.00 | 0.541474E+11 | 0.00 | 0.109546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.878474E+09 | 0.00 | 0.00 | 0.00 | 0.648638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129541E+10 | 0.00 | 0.00 | 0.00 | 0.749287E+10 | 0.00 | 0.793928E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BACK_SPACE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.275330E+10 | 0.00 | 0.00 | 279261.10 | 0.00 | 0.179057E+10 | 0.233354E+09 | 0.00 | 0.22 |
February | 0.144040E+10 | 21495403.68 | 0.00 | 3640282.46 | 0.00 | 0.447315E+09 | 0.841662E+09 | 0.00 | 0.22 |
March | 0.307566E+09 | 0.123410E+10 | 0.00 | 7147207.10 | 27700.65 | 0.00 | 0.542191E+09 | 0.00 | 0.23 |
April | 0.00 | 0.421560E+10 | 0.00 | 2208537.01 | 127926.43 | 0.00 | 19222946.20 | 0.00 | 0.23 |
May | 0.00 | 0.947376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
June | 0.00 | 0.126215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.159880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.161781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
September | 0.00 | 0.120803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
October | 1974636.23 | 0.421232E+10 | 0.00 | 2235059.26 | 0.00 | 0.00 | 66797118.46 | 0.00 | 0.22 |
November | 0.651958E+09 | 0.433160E+09 | 0.00 | 5197786.86 | 0.00 | 0.00 | 0.694030E+09 | 0.00 | 0.22 |
December | 0.245031E+10 | 0.00 | 0.00 | 922447.96 | 0.00 | 0.113979E+10 | 0.754659E+09 | 0.00 | 0.22 |
Annual Sum or Average | 0.760551E+10 | 0.764584E+11 | 0.00 | 21630581.76 | 155627.07 | 0.337767E+10 | 0.315192E+10 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.275330E+10 | 0.161781E+11 | 0.00 | 7147207.10 | 127926.43 | 0.179057E+10 | 0.841662E+09 | 0.00 | 0.24 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216090E+11 | 0.00 | 0.00 | 16742608.36 | 0.00 | 0.165604E+10 | 0.104799E+11 | 0.00 | 0.42 |
February | 0.916722E+10 | 0.551492E+09 | 0.00 | 33548420.51 | 0.00 | 49459500.03 | 0.818707E+10 | 0.00 | 0.43 |
March | 0.197828E+10 | 0.112579E+11 | 0.00 | 32421627.39 | 29460813.45 | 0.00 | 0.322037E+10 | 0.00 | 0.44 |
April | 73401767.12 | 0.335100E+11 | 0.00 | 5507898.19 | 0.321778E+09 | 0.00 | 0.130300E+09 | 0.00 | 0.44 |
May | 0.00 | 0.695480E+11 | 0.00 | 65420.78 | 0.574292E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.897998E+11 | 0.00 | 0.00 | 0.865728E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.110940E+12 | 0.00 | 0.00 | 0.118179E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.112006E+12 | 0.00 | 0.00 | 0.124458E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.836973E+11 | 0.00 | 0.00 | 0.113225E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.457931E+09 | 0.313362E+11 | 0.00 | 8232577.09 | 0.382757E+09 | 0.00 | 0.565869E+09 | 0.00 | 0.43 |
November | 0.440390E+10 | 0.565200E+10 | 0.00 | 31016938.96 | 0.00 | 0.00 | 0.440457E+10 | 0.00 | 0.43 |
December | 0.172024E+11 | 43026.44 | 0.00 | 28680603.55 | 0.00 | 92987688.53 | 0.116066E+11 | 0.00 | 0.42 |
Annual Sum or Average | 0.548921E+11 | 0.548299E+12 | 0.00 | 0.156216E+09 | 0.573264E+10 | 0.179848E+10 | 0.385947E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.216090E+11 | 0.112006E+12 | 0.00 | 33548420.51 | 0.124458E+10 | 0.165604E+10 | 0.116066E+11 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: POINT_OF_SALE
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120198E+10 | 0.00 | 0.00 | 10870030.09 | 0.00 | 0.140533E+09 | 0.163357E+10 | 0.00 | 0.42 |
February | 0.547977E+09 | 0.143793E+09 | 0.00 | 9808569.73 | 0.00 | 24832566.91 | 0.801863E+09 | 0.00 | 0.43 |
March | 51150341.44 | 0.134712E+10 | 0.00 | 7176307.82 | 199478.57 | 0.00 | 0.318093E+09 | 0.00 | 0.44 |
April | 0.00 | 0.350249E+10 | 0.00 | 1409505.80 | 705042.40 | 0.00 | 9713060.95 | 0.00 | 0.45 |
May | 0.00 | 0.728384E+10 | 0.00 | 28750.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.956520E+10 | 0.00 | 0.00 | 405534.39 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.120729E+11 | 0.00 | 0.00 | 613011.88 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.122665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.941698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.381028E+10 | 0.00 | 2288380.52 | 0.00 | 0.00 | 16887297.24 | 0.00 | 0.44 |
November | 79313280.36 | 0.881006E+09 | 0.00 | 9576362.38 | 0.00 | 0.00 | 0.473243E+09 | 0.00 | 0.43 |
December | 0.885030E+09 | 6350408.09 | 0.00 | 13925821.21 | 0.00 | 3307338.05 | 0.142969E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.276545E+10 | 0.602965E+11 | 0.00 | 55083728.15 | 1923067.24 | 0.168672E+09 | 0.468306E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.120198E+10 | 0.122665E+11 | 0.00 | 13925821.21 | 705042.40 | 0.140533E+09 | 0.163357E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_RETAIL
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140253E+10 | 0.00 | 0.00 | 5626550.09 | 0.00 | 0.368649E+09 | 0.129386E+10 | 0.00 | 0.42 |
February | 0.714324E+09 | 0.109525E+09 | 0.00 | 6365614.70 | 0.00 | 77763972.60 | 0.681142E+09 | 0.00 | 0.43 |
March | 0.148026E+09 | 0.124840E+10 | 0.00 | 5254290.76 | 46948.49 | 0.00 | 0.281945E+09 | 0.00 | 0.44 |
April | 0.00 | 0.343869E+10 | 0.00 | 1041180.92 | 65530.65 | 0.00 | 11488210.37 | 0.00 | 0.44 |
May | 0.00 | 0.714310E+10 | 0.00 | 1107.86 | 119041.74 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.932591E+10 | 0.00 | 0.00 | 167437.81 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.117585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.119423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.907672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.367340E+10 | 0.00 | 1999309.04 | 0.00 | 0.00 | 24898822.39 | 0.00 | 0.44 |
November | 0.175498E+09 | 0.819641E+09 | 0.00 | 7150746.36 | 0.00 | 0.00 | 0.435526E+09 | 0.00 | 0.43 |
December | 0.110639E+10 | 3126671.57 | 0.00 | 8667341.03 | 0.00 | 72854179.34 | 0.127186E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.354677E+10 | 0.585393E+11 | 0.00 | 36106140.76 | 398958.70 | 0.519267E+09 | 0.400072E+10 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.140253E+10 | 0.119423E+11 | 0.00 | 8667341.03 | 167437.81 | 0.368649E+09 | 0.129386E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: FRONT_ENTRY
Timestamp: 2020-06-03 19:12:26
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |